Installation and Operation Manual

About Xantrex Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from 50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute electrical power.
Trademarks DR Inverter/Charger is a trademark of Xantrex International. Xantrex is a registered trademark of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only.
Disclaimer UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision March 2005 Revision
Part Number 975-0012-01-02 Rev A
1 360 925 5097 (direct) Fax: 1 800 994 7828 (toll free North America) 1 360 925 5143 (direct) Email: customerservice@xantrex.com Web: www.xantrex.com
Contact Information

Purpose
The purpose of this Installation and Operation Manual is to provide explanations and procedures for installing, operating, maintaining, and troubleshooting the DR Inverter/Charger.
The Manual provides safety guidelines, detailed planning and setup information, procedures for installing the inverter, as well as information about operating and troubleshooting the unit. It does not provide details about particular brands of batteries. You need to consult individual battery manufacturers for this information.
The Manual is intended for anyone who needs to install and operate the DR Inverter/Charger. Installers should be certified technicians or electricians.
This Manual is organized into four chapters and three appendices.
Chapter 1, “Introduction” contains information about the features and functions of the DR Inverter/Charger.
Chapter 2, “Installation” contains information about how to plan for and install the DR Inverter/Charger.
Chapter 3, “Operation” contains information about how to operate the DR Inverter/Charger.
Chapter 4, “Troubleshooting” contains information about how to troubleshoot possible error conditions while using the DR Inverter/Charger.
Appendix A, “Specifications” contains information about the electrical specifications and environmental specifications of the DR Inverter/Charger.
Appendix B, “Appendix B, “Battery Information” supplies general information about batteries such as battery types, battery bank sizing, battery configurations, and battery care. For detailed information, see your battery manufacturer or your system designer.”
Appendix C, “Multi-wire Branch Circuit Wiring” supplies information about Multi-wire Branch Circuit Wiring Precautions when using stand-alone 120 Vac inverters or generators.
975-0012-01-02 Rev A iii

The following conventions are used in this guide.
ASC Authorized Service Center
AHJ Authority Having Jurisdiction
CW Clockwise (rotates to the right)
CCW Counter-clockwise (rotates to the left)
DR Inverter DR Inverter/Charger
DRI DR Interface (for stacking)
LED Light Emitting Diode
PVGFP PV Ground Fault Protection
RMA Return Material Authorization
You can find more information about Xantrex Technology Inc. as well as its products and services at www.xantrex.com
iv 975-0012-01-02 Rev A

SAVE THESE INSTRUCTIONS
This manual contains important instructions for all DR Inverter/Charger models that shall be followed during installation and maintenance of the inverter.
975-0012-01-02 Rev A v

Working in the vicinity of lead-acid batteries is dangerous. Batteries generate explosive gases during normal operation. Therefore, you must read this guide and follow the instructions exactly before installing or using your DR Inverter/ Charger.
vi 975-0012-01-02 Rev A
Safety

Follow all instructions published by the battery manufacturer and the manufacturer of the equipment in which the battery is installed.
975-0012-01-02 Rev A vii
Safety




Batteries -2–15
Battery Types -2–15 Battery Bank Sizing -2–15 Battery Configuration -2–15 Battery Cable Sizing -2–16 DC Disconnect and Over-current Protection -2–17
Battery Cable Connections -2–18 Connecting the Battery Bank to the Inverter -2–19
Installing a Battery Temperature Sensor -2–21 AC Wiring -2–22
AC Distribution Panel (Sub-panel) Mounting and Conduit Installation -2–22 Accessing the AC Terminals -2–22 AC Output Wiring to the AC Distribution Panel (Sub-panel) -2–25 AC Input Wiring - On-Grid Applications -2–26 AC Input Wiring using a Generator in an On-Grid Application -2–27 AC Input Wiring - Off-Grid Applications using a 120 Vac Generator -2–28 AC Input Wiring - Off-Grid Applications using a 240 Vac Generator for 120 Vac Loads - - -2–29 Series Stacking (120 Vac/60 Hz Models only) -2–30
Front Panel Controls and Indicators- 3–2
POWER ON/OFF Switch - 3–2 Ports - 3–3
BATTERY SENSE Port - 3–3 COM Port - 3–3 Remote Controls (RC8/RC4) - 3–3 Stacking Interface - 3–4 Controls - 3–4
Battery Type Selector - 3–4 SEARCH MODE WATTS Potentiometer - 3–6 Battery Charger Rate - 3–7
Over Discharge Protection/AC Transfer Voltage - 3–8 Over Discharge Protection (ODP) - 3–9 AC Transfer Voltage -3–10 Battery Capacity -3–12 LED Indicators -3–13
Inverter Mode LED - Green -3–13 Over Temp / Overload LED - Red / Green (error condition) -3–13 Battery High/Battery Low LED - Red/Green (error condition) -3–13 Charger LED - Orange / Green -3–14 Audible Indicator (internal) -3–14 Circuit Breakers -3–15
x 975-0012-01-02 Rev A
Contents

Start-up - 3–16 Charger Mode - 3–17
3-Stage Charging Process - 3–17 Equalize Charging - 3–18
Troubleshooting the DR Inverter - 4–2 Problem Loads - 4–3
Ceiling Fans - 4–3 Cell Phones - 4–3 Computers and Sensitive Electronics - 4–3 Consumer Electronics - 4–3 Clocks - 4–4 Decreasing Loads - 4–4 Dimmer Switches - 4–4 Fluorescent Lights - 4–4 Heavy Loads - 4–4 Microwave Ovens - 4–4 Printers - 4–5 Rechargeable Devices - 4–5 Undersized Loads - 4–5
Specifications of the DR Inverter -A–2
Introduction -B–2 Battery Types -B–2
Deep-cycle Flooded Lead Acid (FLA) -B–2 Sealed Batteries (Gel and AGM) -B–3 NiCad and NiFe Batteries -B–3 Understanding Battery Capacity Ratings -B–4 Battery Bank Sizing-B–4
Understanding Amp-hour Requirements -B–5 Calculating Amp Hours -B–5
Amp Hour Example Worksheet -B–6 Battery bank size worksheet -B–7 Battery Configurations -B–8
Wiring Batteries in Series -B–8 Wiring Batteries in Parallel -B–9 Wiring Batteries in Series-Parallel - B–10 Battery Connections for Stacked Inverters - B–12
975-0012-01-02 Rev A xi
Contents

Battery Maintenance - B–13
Battery Charging - B–13 Equalization Charging - B–15 General Maintenance - B–16
Multi-wire Branch Circuits - C–2 Identifying Multi-wire Branch Circuits - C–4 Correcting Multi-wire Branch Circuit Wiring - C–5
Warranty and Return Information - WA–1
Index - IX–1
xii 975-0012-01-02 Rev A
Contents

Figure 1-1 Front Panel Features - 1–3 Figure 1-2 AC Side of the DR Inverter- 1–3 Figure 1-3 DC Side of the DR Inverter- 1–4 Figure 1-4 Product Identification - 1–5 Figure 1-5 Model/Serial Number Sticker - 1–6 Figure 2-1 On-Grid Basic Configuration (Utility Backup)- 2–7 Figure 2-2 Off-Grid Configuration (Generator only) - 2–7 Figure 2-3 On-Grid Configuration - with Renewable Energy Sources - 2–8 Figure 2-4 Off-Grid Configuration - with Renewable Energy Sources- 2–9 Figure 2-5 Charge Rate versus Peak AC Voltage- 2–10 Figure 2-6 Dimensions (not to scale) - 2–11 Figure 2-7 Suggested Mounting Method - 2–12 Figure 2-8 Mounting on Plywood - 2–12 Figure 2-9 DC Grounding - 2–14 Figure 2-10 Battery Cable Connections - 2–18 Figure 2-11 DC Terminals on the DR Inverter - 2–19 Figure 2-12 Connecting the Battery Bank to the DR Inverter/Charger- 2–20 Figure 2-13 Battery Temperature Sensor (BTS) RJ11 Jack Location - 2–21 Figure 2-14 Connecting the BTS to the DR Inverter - 2–21 Figure 2-15 AC Side Cover Panels - 2–23 Figure 2-16 AC Terminals for AC Input to the Inverter - 2–24 Figure 2-17 AC Terminals for AC output to the Sub-panel - 2–25 Figure 2-18 AC Wiring- On-Grid Application - 2–26 Figure 2-19 AC Wiring using a Generator - On-Grid Application - 2–27 Figure 2-20 AC Wiring using a 120 Vac Generator - Off-Grid Application - 2–28 Figure 2-21 AC Wiring using a 240 Vac Generator with 120 Vac Loads only- Off-Grid Application2–29 Figure 2-22 AC Wiring for dual-inverters - On-Grid Application (120 Vac models only) - 2–31 Figure 2-23 Wiring for dual-inverters - On-Grid Application (120 Vac models only) - 2–32 Figure 3-1 Front Panel Controls and Indicators - 3–2 Figure 3-2 Battery Type Selector Adjustment - 3–4 Figure 3-3 Battery Type Selector Adjustment - 3–7 Figure 3-4 Battery Charger Rate Potentiometer (DR1512 values used) - 3–8 Figure 3-5 ODP Enabled/Disabled Positions- 3–9 Figure 3-6 Automatically Calculated Discharge Cutoff Voltage per Cell - 3–9 Figure 3-7 ODP Enabled/Disabled Positions- 3–11 Figure 3-8 Typical Setting for Most Utility Application - 3–11
975-0012-01-02 Rev A xiii

Figure 3-9 Battery Capacity Potentiometer (new) -3–12 Figure 3-10 Battery Capacity Potentiometer (old)-3–12 Figure 3-11 LED Indicators -3–13 Figure 3-12 AC Pass-through and Charger AC Input Circuit Breakers-3–15 Figure 3-13 Startup Items -3–16 Figure 3-14 Charger Controls and Indicators -3–18 Figure 3-15 Equalize Positions on Battery Type Selector Switch -3–19 Figure 3-16 Equalize 1 Battery Charger Rate Potentiometer (Position “1”)-3–20 Figure 3-17 Equalize 2 Battery Capacity Rate Potentiometer (Position “0”) -3–20 Figure B-1 6-volt Battery Wiring - “Series” Configuration - B–8 Figure B-2 12-volt Battery Wiring - “Series” Configuration - B–9 Figure B-3 Battery Wiring in Parallel - B–9 Figure B-4 Battery Wiring 24-volt - Parallel Configuration - Step 1- B–10 Figure B-5 Battery Wiring 24-volt - Parallel Configuration - Step 2- B–10 Figure B-6 Battery Wiring 24-volt - Parallel Configuration - Step 3- B–11 Figure B-7 Example of Battery Connections for Stacked Inverters (24 Vdc shown) - B–12 Figure C-1 Conventional Home-type Wiring - C–2 Figure C-2 Multi-wire Branch Circuit Wiring and Current Flow - C–3 Figure C-3 120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit - C–3 Figure C-4 Multi-wire Branch Circuit Wiring- C–4 Figure C-5 Using a Step-down Autotransformer in Multi-wire Branch Circuit Wiring - C–6S
xiv 975-0012-01-02 Rev A
Figures

Table 1-1 Model Identification and Numbering Conventions - 1–5 Table 1-2 Letter Suffix Code Definitions - 1–6 Table 2-1 Peak Input Filtrate versus Charging Current - 2–10 Table 2-2 Safety Ground Conductor Size - 2–13 Table 2-3 Minimum Recommended Battery Cable Size versus Length - 2–16 Table 2-4 Battery Cable to Maximum Breaker/Fuse Size- 2–17 Table 2-5 Minimum Recommended Wire Size, Torque Values (Input and Output), and Maximum Output Breaker Size - 2–23 Table 3-1 Battery Type Selector Switch Settings - 3–5 Table 3-2 Approximate Charge rate Setting/Amperage - 3–8 Table 3-3 ODP/AC Transfer Voltage - 3–10 Table 3-4 AC Pass-through Circuit Breakers - 3–15 Table 3-5 Battery Charger Circuit Breakers- 3–15 Table 4-1 Troubleshooting the DR Inverter - 4–2 Table A-1 Electrical Specifications for the DR Inverter/Charger - 120 Vac/60 Hz Models-A–2 Table A-2 Electrical Specifications for the DR Inverter/Chargers - 220 Vac/60 Hz Models -A–4 Table A-3 Electrical Specifications for the DR Inverter/Charger - 230 Vac/50 Hz Models-A–5 Table A-4 Environmental Specifications for the DR Inverter/Charger -A–7 Table B-1 Determining Average Daily Load in Amp-hours (Example -B–6 Table B-2 Determining Battery Bank Size -B–7 Table B-3 Typical Appliance Wattage-B–7 Table B-4 Variances in Charging Voltage based on Battery Temperature - B–14 Table B-5 Temperature Compensation Calculation -B–14 Table B-6 Battery State-of-Charge - B–17
975-0012-01-02 Rev A xv



Chapter 1, “Introduction” contains information about the features and functions of the DR Inverter/Charger.

Thank you for purchasing the DR Inverter/Charger from Xantrex Technology Inc. The DR Inverter is one of the finest inverter/chargers on the market today, incorporating state-of-the-art technology and high reliability.
The inverter features an AC pass-through circuit, powering your home appliances from utility or generator power while charging the batteries. When utility power fails, the battery backup system keeps your appliances powered until utility power is restored. Internal protection circuits prevent over-discharge of the batteries by shutting down the inverter when a low battery condition occurs. When utility or generator power is restored, the inverter transfers to the AC source and recharges the batteries.
The front panel features LEDs for reading system status, and controls to customize the inverter settings for your battery bank.
The DR Inverter is an economical product designed to provide a reliable supply of electricity to all the essential circuits in the home or business during a power outage. The critical loads can be powered for hours or days, depending on the size of the system battery bank. When utility grid power returns, the batteries are quickly recharged to ensure they will be ready to supply backup power during the next outage.
Accessories allow the DR Series to also serve as a central hub of a renewable energy system.
Modified Sine Wave Power
The DR Inverter provide a modified sine wave output which operates most AC appliances and equipment.
Battery Charger/AC Transfer Relay
The inverter/charger includes a 3-stage battery charger designed to recharge any type of battery in the shortest possible time. The built-in, fully automatic AC transfer relay automatically transfers power from the utility to the inverter and handles a full 60 amps of current at 120 Vac (30 amps for pass-through plus 20 to 30 amps for charging - depending on the model).
Simplicity The DR Inverter is simple to operate. All inverter and battery charger controls are located on the front panel.
High Efficiency The inverter/charger operates at over 90% efficiency through most of its power range in Invert-mode.
DR Inverter use extremely low current while in the search mode, consuming less than 1 watt of power. In the ON mode, the inverter/charger uses less than 12 watts of power.
The following sections illustrate the features of the DR Inverter. Figure 1-1 shows the features of the front side of the DR Inverter and identifies the AC side from the DC side.
Introduction · Low Power Consumption


Battery Sense Port COM Port
Figure 1-1 Front Panel Features
The AC side of the DR Inverter has one 30-amp breaker for pass-thru AC Input, and one 30-amp (20 amp in certain models) breaker for charger AC input.

30 Amp Breaker for Pass-thru AC Input
20 or 30 Amp Breaker for Charger AC Input
Cover plate is not shown in this photo.
Figure 1-2 AC Side of the DR Inverter

The DC side of the DR Inverter has the equipment ground lug, the positive (+) battery terminal, and the negative (–) battery terminal.

Ventilation Holes Battery Positive (+) Terminal
Battery Negative (–) Terminal
Figure 1-3 DC Side of the DR Inverter
The following options are available for the DR Inverter/Chargers.
The RC8 allows the inverter to be switched ON or OFF remotely and includes an LED status indicator. This unit is also compatible with the RC4 (the predecessor to the RC8); although the RC4 is no longer available for purchase from Xantrex.
The DRI stacking interface provides 3-wire 120/240 Vac at twice the power using dual DR Inverters (120 Vac/60 Hz units only).
The DRCB conduit box connects to the DC side of the inverter and accepts a DC conduit run.
Carefully unpack the inverter/charger from its shipping carton.
Introduction · Ventilation Holes · Ground Lug

❐ Verify all of the items listed on the packing material sheet are present. Please call Xantrex Customer Service at (800) 670-0707 if any items are missing. ❐ Save your proof-of-purchase. This is required if the unit should require warranty service. ❐ Save the original shipping carton and packing materials! If the inverter ever needs to be returned for service, it should be shipped in the original carton. This is also a good way to protect the inverter if it ever needs to be moved. ❐ Record the unit’s model, serial number and date of purchase in the appropriate fields in section “Information About Your System” on page WA–4.
The DR Inverter is identified by the model/serial number labels. The Serial Number can be located on the mounting rail or inside the top cover. Model Number labels may be located on the bottom side of the front cover or possibly inside the front cover. All the necessary information is provided on the label such as AC output voltage, power and frequency (punch holes).
The inverter also has a letter designator followed by 4 or 5 digits (depending on revision). The model number describes the type of inverter, the output specifications, the required battery voltage and the output voltage and frequency
Table 1-1 Model Identification and Numbering Conventions
DR indicates the type of inverter/charger - DR Series.
15 the first two digits of the numerical designator indicate the inverter’s output power - 1500 Watts.
12 the second two digits indicate the required nominal battery bank voltage - 12 Vdc.
the letter suffix code indicates the output voltage and frequency of the inverter - 230 Vac/50 Hz.
Figure 1-4 Product Identification

Table 1-2 Letter Suffix Code Definitions
Letter Suffix Output Voltage Output frequency
(no letter) 120 Vac 60 Hz
E 230 Vac 50 Hz
J 105 Vac 50 Hz
K 105 Vac 60 Hz
W 220 Vac 60 Hz

Figure 1-5 Model Number Sticker
The 120 Vac/60 Hz models of the DR Series inverter/charger (models DR1512, DR1524, DR2412, DR2424, and DR3624) are ETL Listed to UL Standard 1741, (First Edition) Power Conditioning Units for use in Residential and Commercial Photovoltaic Power Systems.
These standards guarantee that the DR Inverter/Charger has been tested to nationally recognized safety standards (UL for the US) and have been found to be free from reasonably foreseeable risk of fire, electric shock and related hazards.
The DR Inverter/Charger is intended to be used for residential or commercial applications. Do NOT use this unit for applications for which it is not listed (i.e., land vehicles or marine craft). It may not comply with the safety code requirements or could possibly present other operational or safety hazards.
Introduction

Chapter 2, “Installation” contains information about how to plan for and install the DR Inverter/Charger.

Take some time prior to installing the equipment to pre-plan the installation. Location, mounting, and ventilation should be taking into consideration before any cabling can be done.
Inverters contain sophisticated electronic components and should be located in a well protected, dry environment away from sources of fluctuating or extreme temperatures and moisture. Exposure to saltwater is particularly destructive and potentially hazardous.
Locate the inverter as close to the batteries as possible in order to keep the battery cable length short. However, do not locate the inverter above the batteries or in the same compartment as vented batteries. Batteries generate hydrogen sulfide gas which is corrosive to electronic equipment. They also generate hydrogen and oxygen. If accumulated, an arc caused by connecting the battery cables or switching a relay could ignite this mixture. Mounting the inverter in a ventilated enclosure with sealed batteries is acceptable.
Installation

The National Building Code requires the inverter be mounted on a vertical surface (or wall). The keyhole slots must not be used as the only method of mounting. The purpose of the wall mounting requirement is to orient the inverter so that its bottom cover, which has no holes, will not allow burning material to be ejected in the event of an internal fire. Use 0.25-inch diameter bolts for mounting. The mounting surface must be capable of supporting twice the weight of the inverter to comply with UL 1741.
Install the inverter in a well ventilated area/enclosure for proper operation. The inverter’s thermal shutdown point will be reached sooner than normal in a poorly ventilated environment, resulting in reduced peak power output and surge capability, as well as shorter inverter life.
The inverter contains an internal fan. Ensure the air vents and intakes are not obstructed in any way. Provide a minimum clearance of 6 inches around the top and sides of the inverter for ventilation.
The following tools may be required to complete this installation.
❐ #2 Phillips screw driver
❐ Slotted screw driver
❐ Assorted open-end wrenches
❐ Socket wrench and fittings
❐ Multimeter (True rms)

The following hardware or materials may be required to complete this installation.
❐ 4 ft. x 4 ft. sheet of 3/4" plywood or 2 x 4’s studding material
❐ #12 wood screws (or 1/2" x 1-1/4" lag bolts)
❐ Conduit and appropriate fittings
All wiring and installation methods should conform to applicable electrical and building codes.
Pre-plan the wire and conduit runs.
For maximum safety, run both AC and DC cables in conduit.
Battery-to-inverter cabling should be only as long as required.
For Example: If #4/0 AWG cables are used, do not exceed 5 feet (one way) in 12 Vdc systems; do not exceed 10 feet (one way) in 24 Vdc systems.
For optimum performance, use pre-assembled battery cables designed specifically for this application (available from Xantrex).
The inverter/charger should be connected to a grounded, permanent wiring system. Neutral and ground conductors should only be bonded at the main electrical service panel.
The negative battery conductor should be bonded to the grounding system at only one point in the system. The size for the conductor is usually based on the size of the largest conductor in the DC system.
Installation · ❐ Wire nuts

Determine all wire routes both to and from the inverter and which knockouts are best suited for connecting the AC conduits. Possible routing scenarios include:
Check for existing electrical or plumbing prior to making cuts in the walls. Cut holes in the walls at appropriate locations for routing wiring/cables.
The following electrical panels and circuit breakers may be required for this installation.
Loads backed up by the inverter will need to be rerouted from the main electrical panel to a sub-panel. This can be done several different ways, depending upon the installation. Always refer to electrical codes for safe wiring practices.
Install a DC disconnect breaker or fuse in the positive battery line. This breaker protects the DC wiring in the event of an accidental short. Size the breaker in accordance with the battery cables. Switch this breaker OFF whenever servicing the batteries.
The DR Inverter can support either 12-volt battery banks or 24-volt battery banks. The battery voltage MUST match the voltage requirements of the inverter. To determine the correct voltage for the system, check the last two digits on the inverter’s model number. For example, the DR1512 is a 12-volt inverter and requires a 12 Vdc battery system. The DR2424 is a 24-volt inverter and requires a 24 Vdc battery system.
Pre-installation Planning

Locate the batteries in an accessible location. Two feet clearance above the batteries is recommended for access to the battery caps. They should be located as close to the inverter as possible without limiting access to the inverter’s disconnects. Install the batteries to the left of a wall mounted inverter for easy access to the DC side of the inverter and shorter cable runs.
For safety and to limit access to the batteries, a lockable, ventilated, battery enclosure or dedicated room should be used. If an enclosure is used, it should be vented to the outside via a one inch vent pipe located at the top of the enclosure. Install an intake vent at the bottom of the enclosure to promote air circulation. These vents exhaust explosive hydrogen gases and must not be overlooked when designing an enclosure.
The enclosure should be made of an acid resistant material or have a finish that resists acid to prevent corrosion. It should be capable of holding the electrolyte from at least one battery should a leak occur.
Place a layer of baking soda on the shelves to neutralize any acid that may be spilled in the future (lead-acid batteries only).
Enclosures located outside must be rainproof and screened to prevent access by rodents or insects.
The battery enclosure should provide a fairly stable temperature for the batteries. If it is installed in a cold environment, insulation should be used to protect the batteries from the cold. The insulation also provides a more consistent temperature and better system performance.
The battery enclosure should not be installed in direct sunlight where the summer sun can overheat the batteries. Locate the enclosure where it will be protected from the afternoon sun and provide vents in the top and bottom of the enclosure to provide air flow. High battery temperatures greatly shortens the life of the batteries.
The following illustrations show basic applications for the DR Inverter/Charger. They include the following configurations.
Consult with your system design for other possible configurations depending on site and code requirements.
Installation


Figure 2-1 On-Grid Basic Configuration (Utility Backup)

Figure 2-2 Off-Grid Configuration (Generator only)
Pre-installation Planning


Figure 2-3 On-Grid Configuration - with Renewable Energy Sources
Installation


Figure 2-4 Off-Grid Configuration - with Renewable Energy Sources
Pre-installation Planning

An AC generator can be used as an input source instead of the utility power, or can be connected (using additional hardware) to power the loads when utility is not present (utility outage), and to charge the batteries. The generator must be of the permanently installed type and not a portable type unit used for emergency power. Small emergency type (lower power) generators may not have a stable enough voltage for the inverter to synchronize to or provide enough current to fully charge the batteries.
The maximum charge rate the battery charger can deliver is dependant upon the peak AC voltage available. Since the battery charger uses only the top portion of the input sine wave, small variations in peak voltage result in large variations in the amount of energy to the charger. The charger’s rated output is based on a utility voltage of 120 Vac RMS (the usual measured value). This should have a peak voltage of 169 Vacpp (230 Vac has a peak voltage of 325 Vac). For every 10 volts of peak lost, the charge rate is reduced by approximately half.
Size the generator appropriately for the system, including battery charge and load current (typically twice the wattage output of the inverter).
Table 2-1 and Figure 2-5 demonstrates how the peak voltage available affects the charging current.
Table 2-1 Peak Input Filtrate versus Charging Current
Peak Voltage Available DR1512 DR2412 DR1524 DR242 DR3624
170 Vacp 70 amps 120 amps 35 amps 70 amps 70 amps
160 Vacp 35 amps 60 amps 17.5 amps 35 amps 35 amps
145 Vacp 15 amps 25 amps 7 amps 15 amps 15 amps

Figure 2-5 Charge Rate versus Peak AC Voltage
Installation

The DR Series inverter can weigh as much as 45 lb. (20.4 kg). Wallboard is not strong enough to support its weight so additional support must be used or added. The inverter can be mounted directly to the wall studs if the wall studs are 16" apart. If not, then 2x4’s or plywood can be used.
To secure the DR Inverter to the wall studs:

Figure 2-6 Dimensions (not to scale)
To secure the DR Inverter to the mounting location using 2 x 4’s or plywood:
Pre-installation Planning


Figure 2-7 Suggested Mounting Method

Ensure the plywood spans across a minimum of three wall studs for adequate support.
Figure 2-8 Mounting on Plywood
Installation

This section describes the DC wiring requirements and how to make the connections. It provides the required cable and wire sizes, recommended lengths for cables, and disconnect/circuit breaker requirements.
Grounding is an important part of the system installation and must be performed correctly to ensure safe operation of the equipment. Grounding requirements vary by country and application. Consult the NEC for specific requirements.
The ground conductor should be sized appropriately for the over-current protection device being used and according to NEC 250-95 (Ninth Edition) (see Table 2-2 below for a portion of the NEC code).
Table 2-2 Safety Ground Conductor Size
Size of Over-current Device Protecting the Conductor
Minimum Size of the Copper Ground Wire
30 or 60 amp #10 AWG
100 amp #8 AWG
200 amp #6 AWG
300 amp #4 AWG
400 amp #3 AWG
This product is intended to be installed as part of a permanently grounded electrical system per the National Electric Code ANSI/NFPA 70 (current edition). This is the single point earth ground for the inverter system.
To ground the DC circuits:
The system ground is the same ground used by the AC side of the system.
DC Wiring


Figure 2-9 DC Grounding
Installation

The DR Inverter can support either 12-volt battery banks or 24-volt battery banks. Before proceeding, ensure you have the appropriate sized batteries for this inverter.
Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel, vented or non-vented, chemistries, etc. They are also available for starting applications (such as an automobile starting battery) and deep discharge applications. Only the deep discharge types are recommended for inverter applications. Choose the batteries best suited for the inverter installation and cost. Use only the same battery type for all batteries in the bank. For best performance, all batteries should be from the same lot and date. This information is usually printed on a label located on the battery.
Additional information regarding batteries can be found in the Appendix B, “Battery Information”.
The size of the battery bank determines how long the AC loads will operate in a backup mode without utility power. The larger the battery bank, the longer the run time. Size the battery bank to the AC load requirements and length of time required to run from the batteries. In general, the battery bank should not be discharged more than 50%. Additional DC charging devices such as solar, wind, hydro, etc., can provide longer run times by recharging the batteries in the absence of AC utility or generator power.
Additional details on estimating battery bank size and capacity can be found in “Battery Bank Sizing” on page B–4.
The battery bank must be wired to match the inverter’s DC input voltage specifications (12 Vdc, 24 Vdc, or 48 Vdc). In addition, the batteries can be wired to provide additional run time. The various wiring configurations are:
For additional information on how to wire these battery-bank configurations, see “Battery Configurations” on page B–8.
DC Wiring

Proper cable sizing (diameter and length) is critical to the safe and efficient operation of an inverter system. Larger diameter cables (smaller AWG number) have less voltage drop and are, therefore, more efficient when transferring power to and from the batteries. If a cable is undersized (diameter too small), it could potentially overheat, creating a fire hazard.
Cable length is another important factor. Runs should be kept as short as practical. Longer cable runs increase resistance, thus lowering the overall efficiency of the system. This is especially true in lower voltage systems (i.e., 12 Vdc) where, depending upon the length of the cable run, it may be necessary to oversize the diameter of the wire, or parallel (double) the cables.
Table 2-3 provides recommended minimum cable sizes for various cable lengths and inverter amperages. These recommendations may not meet all local or NEC requirements.
Table 2-3 Minimum Recommended Battery Cable Size versus Length
Typical Amperage 1 to 3 feet (one-way) 3 to 5 feet (one-way) 5 to 10 feet (one-way)
DR1512 150 A #2/0 AWG (67.4 mm2) #2/0 AWG (67.4 mm2) #4/0 AWG (107 mm2)
DR2412 240 A #4/0 AWG (107 mm2) #2/0 AWG (67.4 mm2) #2/0 AWG (67.4 mm2)
DR1524 75 A #2/0 AWG (67.4 mm2) #2/0 AWG (67.4 mm2) #2/0 AWG (67.4 mm2)
DR2424 120 A #2/0 AWG (67.4 mm2) #4/0 AWG (107 mm2) #4/0 AWG (107 mm2)
DR3624 180 A #4/0 AWG (107 mm2) #4/0 AWG (107 mm2) #4/0 AWG (107 mm2)
Installation · Inverter Model

For safety and to comply with regulations, battery over-current protection is required. Fuses and disconnects must be sized to protect the wiring in the system and are required to open before the wire reaches its maximum current carrying capability.
The National Electrical Code (NEC) requires both over-current protection and a disconnect switch for residential and commercial electrical systems. These items are not supplied as part of the inverter. However, Xantrex offers a DC rated, ETL Listed, circuit breaker disconnect module specifically designed for use with Xantrex™ inverters to meet NEC compliance. Two amperage ratings are available: a DC250 (250 amps) and a DC175 (175 amps) in either single or dual breaker configurations for single- or dual-inverter installations.
Some installations may not require conduit or a disconnect device, although over-current protection is still required. Xantrex offers a fuse block (TFB) providing the code required inverter over-current protection for these applications. Refer to the table below for the proper size disconnect device for specific cable diameters.
Table 2-4 Battery Cable to Maximum Breaker/Fuse Size
Cable Size Required Rating in Conduit
Rating in “Free Air”
#2 AWG 115 amps max N/A 170 amps max TFB200
#2/0 AWG 175 amps max DC175 265 amps max TFB300
#4/0 AWG 250 amps max DC250 360 amps max TFB400
Important: The NEC allows rounding to the next standard fuse size from the cable rating (i.e., 150 amp cable size rounds up to a standard 175 amp size). The term “free air” is defined by the NEC as cabling that is not enclosed in a conduit or a raceway. Cables enclosed in conduit or raceways have substantially lower continuous current carrying ability due to heating factors.
DC Wiring · Maximum Breaker Size · Maximum Fuse Size

Battery cables must have crimped (or preferably, soldered and crimped) copper compression lugs unless aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed battery cables are available from Xantrex in an assortment of lengths: 1½ to 10 feet, and in #2/0 AWG or #4/0 AWG sizes. These cables are color-coded with pressure crimped, sealed ring terminals.
Figure 2-10 illustrates the proper method to connect the battery cables to the DR Inverter’s DC terminals.
Do not place anything between battery cable lug
and terminal surface. Assemble exactly as shown.
2/0 Copper Compression Lug 2/0 Aluminum Mechanical Lug
Figure 2-10 Battery Cable Connections
Installation


Positive (+) Battery Terminal
Negative (–) Battery Terminal
Torque the Positive (+) Battery terminal to 10-15 ft-lbs (13.6 to 20.3 nm)
Torque the Negative (–) Battery terminal to 10-15 ft-lbs (13.6 to 20.3 nm)
Torque value for the Ground Lug is 10-15 in-lbs (1.1 to 1.7 nm)
Figure 2-11 DC Terminals on the DR Inverter
Follow the procedure below to connect the battery bank to the inverter.
:
To connect the battery bank to the inverter:
DC Wiring · Ground Lug

: Equip

Figure 2-12 Connecting the Battery Bank to the DR Inverter/Charger
Installation

A battery temperature sensor (BTS) option can easily be installed in the system to ensure proper charging of the batteries based on temperature. Installing a BTS extends battery life by preventing overcharging in warm temperatures and undercharging in cold temperatures.
To install the Battery Temperature Sensor:

Battery Sense (RJ11) port
Figure 2-13 Battery Temperature Sensor (BTS) RJ11 Jack Location

Figure 2-14 Connecting the BTS to the DR Inverter
DC Wiring

This section describes the AC wiring requirements and how to make the connections. It provides the required wire sizes, recommended lengths for conductors, and disconnect/circuit breaker requirements.
All AC wiring connects to the terminal block located on the right-hand side of the inverter.
To make the AC connections to the inverter:
Installation



Standard Cover Plate High Power Conduit Box DR15XX DR24XX and DR36XX models
Figure 2-15 AC Side Cover Panels
Before wiring the input of the inverter, refer to Table 2-5 below for the minimum recommended wire size.
Table 2-5 Minimum Recommended Wire Size, Torque Values (Input and Output), and Maximum Output Breaker Size
Maximum Output Breaker Size 120 Vac 220-240 Vac 120 Vac 220-240 Vac
AC Input AC Output Torque Value for Terminal Connections
DR1512 #8 or 6 AWG #10 AWG #10 AWG #16 AWG 16 in-lbs (1.8 nm)
DR2412 #6 AWG #10 AWG #10 AWG #14 AWG 16 in-lbs (1.8 nm)
DR1524 #8 or 6 AWG #10 AWG #10 AWG #16 AWG 16 in-lbs (1.8 nm)
DR2424 #6 AWG #10 AWG #10 AWG #14 AWG 16 in-lbs (1.8 nm)
DR3624 #6 AWG Not Available #8 AWG Not Available 16 in-lbs (1.8 nm)

To connect the AC Input to the Inverter:
a) Connect the GROUND (green) wire to the inverter’s AC GROUND terminal. b) Connect the NEUTRAL (white) wire from the AC source to the inverter’s NEUTRAL INPUT terminal. c) Connect the HOT (black) wire from the AC source to the inverter’s AC HOT INPUT terminal.

Torque the terminal connections to 16 in-lbs (1.8 nm)
NEUTRAL IN
HOT IN
Figure 2-16 AC Terminals for AC Input to the Inverter
Installation

Important: The ground and neutral must be bonded at one place, and only one place, in the system. If the generator is the main source of power, (i.e., no utility grid power) then the neutral and ground connections are bonded at the generator. If the generator is acting as a backup for the utility grid, then the bond should be at the main utility service entrance box. In this case, ensure that no bond exists at the generator output.
To connect the AC output wiring to the sub-panel:

Torque the terminal connections to 16 in-lbs (1.8 nm)
OUT
Figure 2-17 AC Terminals for AC output to the Sub-panel
AC Wiring

The following diagrams illustrate the AC wiring for the following basic 120/240 Vac scenarios. Consult your system design for other possible configurations.
Follow the example below to complete the wiring for an on-grid application.

Figure 2-18 AC Wiring- On-Grid Application
Installation

If a generator is used as a backup for the utility, then a manual transfer switch must be added to provide a means to switch the generator power to the inverter’s inputs. The generator can be used during extended outages to recharge the batteries and provide pass through power for the loads. Start and stop the generator manually using the generator’s pull-cord, ON/OFF switch, etc.

Figure 2-19 AC Wiring using a Generator - On-Grid Application
AC Wiring

Follow the example below to complete the wiring for an off-grid application.

Figure 2-20 AC Wiring using a 120 Vac Generator - Off-Grid Application
Installation

AC Input Wiring - Off-Grid Applications using a 240 Vac Generator for 120 Vac Loads
Follow the example below to complete the wiring for an off-grid application.

Figure 2-21 AC Wiring using a 240 Vac Generator with 120 Vac Loads only- Off-Grid Application
AC Wiring

This COM port allows two DR Inverters (120 Vac/60 Hz models only) to be used in the same system in a “SERIES” configuration to operate 240 Vac loads. Series stacking can also be used to connect to 240 Vac only power systems providing both 120 and 240 Vac outputs. A series stacking interface cable (DRI) is required to connect the series stacking port of the inverters.
In this mode, one of the inverters will function as the “primary” and the other inverter becomes the “secondary.” The first unit switched ON becomes the primary and ensures the secondary’s output is 180 degrees out of phase for 240 Vac operation. Both units can charge the batteries or provide battery backup power during a utility outage.
The following illustrations provide a general overview of AC configurations using stacked inverters. Detailed wiring and operating instructions are provided with the DRI interface kit available from Xantrex Technology Inc.
The following diagrams illustrate the AC Wiring for a basic On-Grid and Off-Grid application.
Installation


Figure 2-22 AC Wiring for dual-inverters - On-Grid Application (120 Vac models only)
AC Wiring


Figure 2-23 Wiring for dual-inverters - On-Grid Application (120 Vac models only)
Installation

Chapter 3, “Operation” contains information about how to operate the DR Inverter/Charger.

All operating controls, indicators and sense connectors are located on the front panel of the unit. The controls are easily accessible, and the LEDs provide inverter/charger status at a glance.

Figure 3-1 Front Panel Controls and Indicators
The POWER ON/OFF control is a momentary contact switch that turns the inverter/charger ON or OFF by pressing it once. When the inverter is first connected to the batteries, it will run through a self test consisting of flashing the LEDs in sequence, operating the cooling fan momentarily and switching the transfer relay three times. Once the self test has successfully completed, the POWER ON/OFF switch is activated. Pressing the switch once turns the inverter ON. Another press turns the inverter OFF.
Operation · COM Port

Front Panel Controls and Indicators
There are two ports on the inverter/charger. Both ports are RJ11 type telephone style connectors. One is used for connecting a remote control to the inverter. The other is used for regulating the charger voltage based on the temperature of the battery bank.
The BATTERY SENSE Port is used for connecting a battery temperature sensor (BTS) to control the charging rate based on battery temperature. The sensor should be taped onto the side of one of the batteries. The information received in this port adjusts the charger’s output higher in cold temperatures, assuring the batteries receive a full charge, and lowers it during warm temperatures, reducing battery gassing and providing overcharge protection.
Refer to the Installation section for the BTS location on the battery.
COM PORT (J1) is a dual function RJ11 (6-pin) connector. Its primary function is to provide serial communications to an optional Xantrex™ remote control unit (RC4 or RC8). The port also acts as a stacking interface control when two DR Inverters are used in a series configuration. When two inverters are stacked, a remote control cannot be used with either unit.
DR Inverter are designed to operate with either an RC8 or RC4 remote control units. Both remotes incorporate a membrane switch with a single red LED display combination to start and stop the inverter, as well as provide overall system operating status.

The remote control must be connected prior to switching the inverter ON; otherwise, the micro-controller will not recognize (or respond to) the remote. If the remote is not recognized, switch the inverter OFF and then ON using the inverter’s front panel POWER ON/OFF switch.
Whenever two DR Series inverters are used in a series (stacked) configuration, one unit (primary) controls the other unit (secondary). Communication between the two inverters is done via the COM port (J1). The first unit switched ON, using its front panel POWER ON/OFF switch, becomes the controlling (primary) inverter.
There are several controls on the inverter’s front panel that provide adjustments for the battery charger, and AC output energy saving mode.
The Battery Type Selector is a 10 position rotary switch used to set the inverter’s charger for the proper Float and Bulk voltage levels. These levels are selected depending on the type of batteries used.
There are also 2 positions (0 and 1) which allow the batteries to be equalized. Equalizing batteries should only be done on liquid lead acid batteries and never on gel batteries. Refer to the table below for the charge voltages in the various switch positions. Consult the battery manufacturer for optimum battery voltage charging settings.

Figure 3-2 Battery Type Selector Adjustment
Operation

Front Panel Controls and Indicators
Table 3-1 Battery Type Selector Switch Settings
12-volt Models 24-volt Models Charge Function
Equalize Charge Rate Equalize Time
0 Equalize 1 - equalizes at a rate equal to the battery bank capacity (in amp- hours) divided by 40.
13.2 *15.0 26.4 *30.0 Battery Capacity Setting (C/40)
6 hrs. minimum 12 hrs. maximum
1 Equalize 2 - charges at a rate set by the BATTERY CHARGER RATE control.
13.2 *15.5 26.4 *31.0 Battery Charger Rate Setting (manual)
6 hrs. minimum 12 hrs. maximum
2 Deep Cell Lead Acid 2
13.3 15.0 26.6 30.0 Provides an additional Float and Bulk settings for deep cycle, lead acid batteries. Refer to the battery manufacturer’s recommendation for Float and Bulk settings.
3 Not Specified 13.6 14.3 27.2 28.6 Provides an additional setting of Bulk and Float voltages.
4 Gel Cel 2 13.7 14.4 27.4 28.8 Recommended for gel cell batteries that specify high float voltages. Check with the battery’s manufacturer.
5 Gel Cell 1 13.5 14.1 27.0 28.2 Typical gel cell setting.
13.2 14.3 26.4 28.6 Use this setting for sealed type car batteries.
7 Deep Cycle Lead Acid 1 (Default Setting)
13.4 14.6 26.6 29.2 Factory setting for typical deep cycle lead acid batteries.
8 NiCad 1 14.0 16.0 28.0 32.0 Use for NiCad battery systems.
9 NiCad 2 14.5 16.0 29.0 32.0 Recommended for use with nickel iron batteries.
See Important notes that follow.

The Search Mode Watts potentiometer adjusts the current threshold required to bring the inverter out of search mode into full wave operation. With search mode enabled, the inverter pulses the AC output looking for an applied load. With no load detected, the inverter goes into the search mode to minimize energy consumption. When a load is applied, the load current is sensed, bringing the inverter into full power operation. Disabling the threshold (setting the potentiometer fully CCW) causes the inverter to remain ON (in full power operation) regardless of an applied load.
To set the Search Mode Watts:
Operation

Front Panel Controls and Indicators

Higher wattage device turns ON inverter DEFEAT Switches Search Mode OFF
Figure 3-3 Battery Type Selector Adjustment
The Battery Charger Rate potentiometer sets the maximum charge current supplied to the battery bank and is also used to regulate constant current in the Bulk Charge Mode. The level should be adjusted to provide a charge rate less than or equal to the amp-hour capacity of the battery bank divided by a factor of five.
Example:
a) Battery bank amp-hour capacity = 500 amp-hours using gel cell batteries. b) Divide the amp-hour capacity by 5 (500/5 = 100). c) Set the potentiometer to MAX (70 amps) as it is less than 100.
a) Battery bank amp/hour capacity is 250 amp-hours using gel cell batteries. b) Divide the amp-hour capacity by 5 (250/5 = 50). c) Set the potentiometer to approximately 71% (50 amps).
Search Mode Potentiometer

Use Table 3-2 to find the approximate setting of the Battery Charge Rate potentiometer. The settings do not need to be exact, but should be as close as possible to the actual value required.
Table 3-2 Approximate Charge rate Setting/Amperage
Percent of Potentiometer Rotation (between stops)
0% Min. 25% 50% 75% 100% Max
0 amps 17.5 amps 35 amps 52.5 amps 70 amps
DR2412 0 amps 30 amps 60 amps 90 amps 120 amps
DR1524 0 amps 8.75 amps 17.5 amps 26.25 amps 35 amps
25% (17.5 amps

75% (50 amps) Example 2
100% (70 amps) Example 1
Figure 3-4 Battery Charger Rate Potentiometer (DR1512 values used)
The Over Discharge Protection/AC Transfer Voltage potentiometer performs two related functions. When set between the 2 and 5 o’clock position (right), both ODP and the AC Transfer Voltage function simultaneously (see table on next page). When the potentiometer is set between the 9 and 1 o’clock position (left), only the AC Transfer Voltage is functional (ODP is disabled).

Front Panel Controls and Indicators
When enabled, ODP shuts down the inverter at a specified voltage (low battery cutoff) to protect the batteries from over discharge damage. The inverter circuitry calculates the lowest (safe) DC voltage (leaving approximately 20% battery capacity) based on the position the Battery Type Selector switch and the amount of current drawn by the load. Under no-load conditions this level is typically between 11.8 and 12.0 Vdc (for a 12-volt battery bank).

Figure 3-5 ODP Enabled/Disabled Positions
1 0.1 0.01 0.001
Figure 3-6 Automatically Calculated Discharge Cutoff Voltage per Cell

During normal operation, the inverter supplies AC power to the applied loads through the pass-through circuit and simultaneously charges the system batteries. Whenever the external AC source drops below the AC Transfer Voltage (set by the potentiometer), the inverter switches to battery power in order to maintain the connected load.
Examples (120 Vac inverter system):
Important: To achieve the fastest transfer time (typically less than 16 ms), set the AC Transfer Voltage potentiometer near the 2:00 o’clock position (with the ODP enabled); or, near the 1:00 o’clock position (with the ODP disabled). If a high number of “nuisance transfers” caused by transients on the AC line occur, adjust the potentiometer from the maximum position toward the minimum position (i.e., 2 o’clock toward 5 o’clock with ODP enabled; or 1 o’clock toward 9 o’clock with ODP disabled).
Table 3-3 ODP/AC Transfer Voltage
ODP Adjustment AC Transfer Voltage
100 to 105 Vac (-J/-K Models) 120 Vac Models 220 to 230 Vac (-W /-E Models)
ODP Disabled ODP Enabled
9:00 5:00 30 Vac 45 Vac 90 Vac
Approximate Approximate 77 Vac 85 Vac 170 Vac
Approximate Approximate 81 Vac 90 Vac 180 Vac
Approximate Approximate 86 Vac 95 Vac 190 Vac
Approximate Approximate 90 Vac 100 Vac 200 Vac
Approximate Approximate 95 Vac 105 Vac 210 Vac
Operation

Front Panel Controls and Indicators
Maximum (105 Vac for 120 Vac models)
AC Transfer Voltage (Adjustable)
Maximum (105 Vac for 120 Vac models)
Minimum (45 Vac for 120 Vac models)
AC Transfer Voltage (Adjustable)
Minimum (45 Vac for 120 Vac models)
Figure 3-7 ODP Enabled/Disabled Positions
Important: Most AC appliances will operate properly with an AC pass-through voltage between 95 and 105 volts. Setting the AC Transfer Voltage potentiometer between these values will allow the incoming source voltage to drop to this level and still operate the connected appliances (load). If the appliances do not operate properly at the lower AC utility pass-through voltage, increasing the setting of the potentiometer (toward MAX) allows the inverter to transfer to battery power (providing full AC output) during these periods.
Typical Setting Range for Utility
Typical Setting Range for Utility
Figure 3-8 Typical Setting for Most Utility Application

The Battery Capacity potentiometer is used to set the correct charge profile for the battery capacity (amp-hours) used with the inverter (see illustration below). The setting allows the inverter to calculate over-discharge protection values and also the end of the Bulk/Absorption charge mode, at which point the inverter switches to the Float mode of battery charging.
The potentiometer should be adjusted as close as possible to the actual capacity of the battery bank for optimum charging. If the system’s battery bank is larger than 1000 amp-hours, set the potentiometer for 1K.

1000 amp-hours (1000 amp-hour or larger
50 amp-hours (small battery bank)
Figure 3-9 Battery Capacity Potentiometer (new)

50 amp-hours (small battery bank)
1000 amp-hours (1000 amp-hour or larger battery banks)
Figure 3-10 Battery Capacity Potentiometer (old)

Front Panel Controls and Indicators
There are four LEDs on the inverter’s front panel, indicating inverter status, battery condition, over temperature/overload conditions and charger status. These LEDs blink or change color depending on the condition or function they are displaying.
INVERTER
BATTERY HIGH/LOW
MODE
BATTERY CHARGER

Figure 3-11 LED Indicators
The green Inverter Mode LED lights (solid) to indicate the inverter is running on batteries (full wave operation). When the inverter is in search mode (no load applied) the LED flashes 2 to 3 times per second. During AC line operation, with AC passing directly through to the connected load, the LED remains OFF.
The Over Temp / Overload LED is a dual color, dual function indicator. When the inverter’s temperature is too high for safe operation, the LED lights (red) to indicate the Over Temp condition. When the temperature returns to a safe level, the LED turns OFF. If the condition persists, the inverter will shut down, cool and then restart.
Whenever the current draw exceeds a value programmed into the micro- controller, the LED lights (green) to indicate the Overload condition. The LED can remain ON for up to one hour (before inverter shutdown) if the condition is caused by a fault in the charger circuit. When the fault condition clears, the LED turns OFF. If the condition is caused by backfeed (connecting the AC line to the inverter’s output) the LED will remain ON for approximately 10 seconds before the inverter shuts down.
The Battery Hi / Battery Low LED is a dual-color, dual-function indicator. Whenever battery voltage exceeds a safe value, the LED lights red to indicate the condition. This value is typically 15.5 volts DC for a 12 volt system (31 volts DC for a 24 volt system). If the condition persists, the inverter will shut down until the battery voltage returns to a safe level and then restart.

Whenever the battery voltage drops to its lowest (safe) level (as calculated by the ODP), the LED lights green to indicate the condition. If the condition persists, the inverter will shut down until the battery voltage returns to a safe level and then restart.
Important: The inverter automatically restarts when the following error conditions are detected: LOW/HIGH BATTERY, OVER TEMPERATURE, or a quick duration SHORTED OUTPUT or OVER-CURRENT. The inverter shuts OFF and requires a MANUAL restart if the following conditions are detected: a prolonged overload condition (approximately 10 seconds) or the inverter’s output is connected directly to an AC power source (utility grid or generator).
The Charger LED is a dual color (red/green), triple function indicator.
A buzzer is located on the control board as an audible alert to fault conditions such as Battery High/Battery Low, or Overload. Steady buzzing indicates an impending inverter shut down. A pulsing chirp indicates the inverter is temporarily off-line due to a fault condition (either within the inverter or related to the system).
Operation

Front Panel Controls and Indicators
The DR Inverter contains two circuit breakers located on the right-hand side of the chassis, directly above the AC input terminal block. The pass-through AC input circuit breaker protects the AC wiring and connected load. The charger AC input circuit breaker protects the charger circuit. The breakers are rated for the maximum charge rate and pass-through current allowed according to the rating of the internal relay.
Table 3-4 AC Pass-through Circuit Breakers
Models DR15XX DR24XX DR36XX
120 Vac 30 amps 30 amps 30 amps
210-230 Vac 15 amps 15 amps N/A
Table 3-5 Battery Charger Circuit Breakers
Models DR15XX DR24XX DR36XX
120 Vac 20 amps 30 amps 30 amps
210-230 Vac 8 amps 15 amps N/A

AC Pass-through Circuit Breaker
Charger AC Input Circuit Breaker
Figure 3-12 AC Pass-through and Charger AC Input Circuit Breakers

Once the inverter is properly connected to the batteries, AC source, and loads (using a sub-panel) the inverter is ready for operation. Recheck the controls and ensure they are in the proper position. Recheck all wiring and ensure it is correct.
Starting the inverter:

SEARCH MODE WATTS Potentiometer
Figure 3-13 Startup Items
Operation · POWER ON/OFF Switch · Charger LED

The charging cycle uses a 3-stage charging process to maintain the batteries. Whenever nominal AC is present at the inverter’s input, it passes power through to the connected load and begins charging the batteries, indicated by the dual color BATTERY CHARGER LED.
Bulk charge is the first stage in the charging process and provides the batteries with a controlled, constant current. A solid orange BATTERY CHARGER LED indicates bulk charge. The bulk charge level is adjustable using the BATTERY CHARGER RATE potentiometer. Once the battery voltage rises to the bulk voltage threshold, the charger then switches to the absorption mode.
Absorption charge is the second stage of battery charging and provides the batteries a controlled, constant voltage for a set period of time. A blinking orange BATTERY CHARGER LED indicates absorption charge.
During this stage the current supplied to the batteries slowly decreases. When the current equals the programmed return amps value (battery bank capacity/40) set with the BATTERY BANK CAPACITY potentiometer, the charger switches to the third stage–float.
Important: If there are DC loads connected to the battery, the current may never decrease to the level to initiate the float stage. The inverter/charger incorporates a timer circuit which starts counting when AC voltage is applied. To ensure that the charger does not stay indefinitely in the absorption charge mode, the timer automatically switches to the float charge mode when 12 hours have elapsed.
Float charge, the final stage of battery charging, maintains a charge to the batteries whenever AC is present on the inverter’s input. A solid green BATTERY CHARGER LED indicates float charging which reduces battery gassing, minimizes watering requirements (for flooded batteries) and ensures the batteries are in a constant state of readiness.
A new 3-stage charging cycle is initiated after an AC source is reapplied to the inverter’s AC input terminals such as after a utility outage.

Battery Charger LED Solid Orange = Bulk Blinking Orange = Absorption Solid Green = Float
Figure 3-14 Charger Controls and Indicators
Equalize charging is a special mode of battery charging. During use, the battery’s cells can become unequal in the voltage and current they can deliver. This is due to a buildup of sulfate on the plates as well as stratified electrolyte. Sulfate prevents the cells from receiving or delivering full power. If the sulfate is left on the plates, it will harden, and permanently reduce the battery’s capacity. Stratification separates the heaver acid from the water, and the concentrated acid remains at the lower portion of the plates, eventually corroding them.
Equalize charging holds the battery at the Equalize voltage for a minimum of 6 hours. This stirs up the electrolyte, distributing the acid, and removing the sulfate from the plates. Equalizing the batteries every month or two (depending on usage) prolongs the life of the batteries and provides better battery performance.
To Set the Equalize Charge:
Operation · Battery Capacity

a) Position “0” equalizes the batteries at the rate of the battery bank capacity divided by 40 (C/40) at a voltage of 15 volts for 12-volt systems or 30 volts for 24-volt systems. This is set with the BATTERY CAPACITY potentiometer. b) Position “1” equalizes the batteries at the rate set with the BATTERY CHARGER RATE CONTROL at a voltage of 15.5 volts for 12-volt systems or 31 volts for 24-volt systems. When the voltage condition is met and 6 hours have elapsed, the charger will switch to the float mode. If the condition is not met (i.e., the current draw is above the rate set with the BATTERY CAPACITY potentiometer (position “0”) or BATTERY CHARGER RATE potentiometer (position “1”)), the charger will continue until the condition is met, or for a maximum of 12 hours. At this point the charger switches to float at the equalize 1 or 2 voltage setting (see Figure 3-1, “Battery Type Selector Switch Settings” on page 3–5).

Figure 3-15 Equalize Positions on Battery Type Selector Switch
Charger Mode · Equalize 1 · Equalize 2

See Table 3-1 Switch Position “1”.
Figure 3-16 Equalize 1 Battery Charger Rate Potentiometer (Position “1”)

See Table 3-1 Switch Position “0”.
Figure 3-17 Equalize 2 Battery Capacity Rate Potentiometer (Position “0”)
Operation

Chapter 4, “Troubleshooting” contains information about how to troubleshoot possible error conditions while using the DR Inverter/Charger.

Table 4-1 provides a list of possible error conditions that may occur, their possible causes, and possible solutions to resolve the error condition.
Table 4-1 Troubleshooting the DR Inverter
Error Condition Possible Cause Solution
No AC output voltage and no warning LEDs on ON.
Battery voltage at the inverter terminals is too high or low.
Check the battery voltage, fuses or breakers, and cable connections.
AC output voltage is low and the inverter turns loads ON and OFF.
Low Battery. Check the condition of the batteries and recharge if possible.
Replace the batteries.
AC output is low. Loose or corroded battery connections.
Check and clean all DC connections.
Loose AC output connections.
Check all AC output connections.
Wrong voltmeter is being used.
Use a True RMS voltmeter.
Charger is inoperative. AC voltage has dropped out-of-tolerance
Check the AC voltage for proper voltage and frequency (depending on model).
Loose AC input connections.
Check all AC output wiring connections
Charger is supplying a lower charge rate.
Charger controls are improperly set.
Refer to the section on adjusting the “Charger Rate”.
Low peak AC input voltage (169 Vacp required for full charger output)
Use larger generator (increasing AC voltage/RPM’s may help).
Check and clean all DC connections.
Loose or corroded battery connections.
Check all AC output wiring connections.
Loose AC input connections.
Turn BATTERY CHARGER RATE potentiometer down to less than halfway until problem is gone.
Generator is unstable - charger is losing synchronization.
AC LEDs flicker while charging. Generator is unstable and charger is losing synchronization.
Turn BATTERY CHARGER RATE potentiometer down to less than halfway until problem is gone.
Troubleshooting

Table 4-1 Troubleshooting the DR Inverter
Error Condition Possible Cause Solution
- indicates charging, but no charge is going to the batteries.
Circuit Breaker on the side of the inverter is open.
Reset the AC CHARGER circuit breaker on the side of the unit.
- is ON, but there is no output power.
No AC voltage on inverter’s AC terminal block.
Check “AC PASS-THRU” Circuit Breaker on the side of the inverter.
Good AC voltage on inverter’s AC terminal block.
Check for open AC output breakers or uses and AC wiring connections.
Charger turns OFF while charging from a generator
High peak AC input voltages from the generator
Load the generator down with a heavy load.
Turn the generator output voltage down.
The inverter can drive most loads, however, there are special conditions that can cause a load to behave differently than expected. The following describes some of the common problems encountered when using an inverter.
Most large diameter, slow turning fans run correctly, but generate more noise than when connected to utility power. High speed fans tend to operate normally.
Some cellular telephones experience interference in the form of a clicking sound.
Some computers and sophisticated electronics have power supplies that do not present a load until correct line voltage is available. When this occurs, each unit waits for the other to begin. This can usually be solved by plugging in an additional load (such as a lamp) to bring the inverter out of its search mode. Also, when using a computer, avoid starting large loads.
AM radios tend to pick up inverter noise, especially on the lower half of their band. Inexpensive tape recorders are likely to experience noise as well. When using sensitive electronic devices, avoid starting large loads.
Problem Loads

The inverter’s crystal controlled oscillator keeps the frequency accurate to within a few seconds a day; however, external loads in the system may alter the inverter’s output waveform causing clocks to run at different speeds. There may be periods where clocks keep time and then mysteriously do not. This is because most clocks do not draw enough power to trigger the load sensing circuit. In order to operate, especially with no other loads present, the inverter’s load sensing circuit will have to be defeated. Refer to the Operation/Search Mode Watts.
If the amount of power a load draws decreases after it has been switched on (such as with a small motor) and its current draw becomes less than the load sensing threshold, it will be turned alternately ON and OFF by the inverter. This can usually be solved by plugging in an additional load (such as a lamp).
Most dimmer switches lose their ability to dim the lights when used with an inverter and operate only in the fully ON or OFF position. Newer, microprocessor controlled dimmers tend to work better in inverter applications.
Some devices cannot be detected by the inverter’s load sensor and will not operate. Small fluorescent lights are the most common example. This can usually be solved by plugging in an additional load. Also, try turning the lamps AC plug over.
If the battery bank cannot deliver the necessary amperage to drive a heavy load, the inverter will shut OFF. The battery voltage will then slowly rise back above the low voltage threshold causing the inverter to resume operation. As soon as the heavy load draws the batteries down, the cycle will continue unless the load is reduced or an additional source of power is added.
Microwave ovens are sensitive to peak output voltages. The higher the voltage, the faster they cook. Since the inverter’s peak output voltage is dependent upon battery voltage and load size, the microwave’s cook time may need to be increased.
Troubleshooting

Most inkjet type printers work well in inverter applications. Laser printers, however, require high current for their fusing circuit and are not recommended for use with an inverter.
When first using a rechargeable device, monitor its temperature for 10 minutes to ensure it does not become abnormally hot. Excessive heat will indicate that it is incompatible with the inverter.
If the power consumed by a device is less than the inverter’s search mode circuitry threshold, it will not run. This can usually be solved by plugging in an additional load such as a 100 watt light bulb.
Problem Loads



Specifications
Appendix A, “Specifications” contains information about the electrical specifications and environmental specifications of the DR Inverter/Charger.

Table A-1 provides the electrical specifications for the DR Inverter/Charger (120 Vac/60 Hz. models).
Table A-2 provides the electrical specifications for the DR Inverter/Charger (220 Vac/60 Hz. models).
Table A-3 provides the electrical specifications for the DR Inverter/Charger (230 Vac/50 Hz. models).
Table A-4 provides the environmental specifications for all models of the DR Inverter/Charger.
Table A-1 Electrical Specifications for the DR Inverter/Chargera - 120 Vac/60 Hz Models
Model DR1512 DR2412 DR1524 DR2424 DR3624
AC Input Voltage 120 Vac 120 Vac 120 Vac 120 Vac 120 Vac
AC Input Low Transfer Voltage
40-105 Vac 40-105 Vac 40-105 Vac 40-105 Vac 40-105 Vac
AC Input Currentb 45 amps 55 amps 45 amps 55 amps 55 amps
Continuous Power (@ 25°C)
1500 VA 2400 VA 1500 VA 2400 VA 3600 VA
Continuous Output (@25 °C)
12.5 amps AC 20 amps AC 12.5 amps AC 20 amps AC 30 amps AC
Efficiency 94% max 94% max 94% max 95% max 95% max
AC Output Voltage (rms)
120 Vac 120 Vac 120 Vac 120 Vac 120 Vac
60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
Surge Capability:
5 sec Rating 2400 watts 4200 watts 3500 watts 6200 watts 7500 watts
1 mSec Rating 38 amps AC 77 amps AC 412 amps AC 80 amps AC 100 amps AC
100 mSec Rating 27 amps AC 55 amps AC 29 amps AC 58 amps AC 72 Amps AC
DC Input Current:
Search Mode 0.045 amps 0.055 amps 0.030 amps 0.030 amps 0.030 amps
Full Voltage 0.700 amps 0.900 amps 0.350 amps 0.450 amps 0.500 amps
DC Current at Rated Power
165 amps 280 amps 80 amps 140 amps 210 amps
400 amps 800 amps 280 amps 560 amps 720 amps
A–2 975-0012-01-02 Rev A
Specifications · Short Circuit Current

Specifications of the DR Inverter
Table A-1 Electrical Specifications for the DR Inverter/Chargera - 120 Vac/60 Hz Models
Model DR1512 DR2412 DR1524 DR2424 DR3624
DC Input Voltage (nominal)c
12.6 Vdc 12.6 Vdc 25.2 Vdc 25.2 Vdc 25.2 Vdc
DC Input Voltage Range
10.8 to 15.5 Vdc 10.8 to 15.5 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc
Auto Low Battery Protection enabled
11 V 11 V 22 V 22 V 22 V
DC Charger Rate (Adjustable)
0 to 70 amps 0 to 120 amps 0 to 35 amps 0 to 70 amps 0 to 70 amps
Common Specifications:
±2. 5%
Waveform modified sine wave
Load Power Factor (allowed)
0.5 to 1.0 (leading or lagging)
Adjustable Load Sensing Range
5 watts minimum to 100 watts maximum
Force Air Cooling Variable speed fan
Number of Charging Profiles
Yes (float, absorption, bulk)
Temperature Comp Probe (BTS)
Remote Control (RC8)d
a.Specifications subject to change without notice. b.This is the minimum AC current required to obtain full pass-through and maximum battery charging. c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load. d.Also compatible with the RC4.
975-0012-01-02 Rev A A–3

Table A-2 Electrical Specifications for the DR Inverter/Chargersa - 220 Vac/60 Hz Models
AC Input Voltage 220 Vac 220 Vac
AC Input Low Transfer Voltage 80 to 210 Vac 80 to 210 Vac
AC Input Currentb 45 amps 55 amps
Continuous Power (@ 25°C) 1500 VA 2400 VA
Continuous Output (@25 °C) 6.8 amps AC 6.8 amps AC
Efficiency 94% max 94% max
AC Output Voltage (rms) 220 Vac 220 Vac
Frequency: (± 0.04% Crystal controlled) 60 Hz. 60 Hz.
Surge Capability:
1 mSec Rating 20 amps AC 20 amps AC
DC Input Current:
Search Mode 0.045 amps 0.055 amps
Full Voltage 0.700 amps 0.900 amps
DC Current at Rated Power 150 amps 80 amps
Short Circuit Current 400 amps 800 amps
DC Input Voltage (nominal)c 12.6 Vdc 12.6 Vdc
DC Input Voltage Range 10.8 to 15.5 Vdc 10.8 to 15.5 Vdc
Auto Low Battery Protection enabled 11 V 11 V
Charger Rate (Adjustable) 0 to 70 amps 0 to 120 amps
Common Specifications:
Voltage Regulation (maximum) ± 5%
Voltage Regulation (Typical) ±2. 5%
Waveform modified sine wave
Load Power Factor (allowed) 0.5 to 1.0 (leading or lagging)
Adjustable Load Sensing Range 5 watts minimum to 100 watts maximum
Force Air Cooling Variable speed fan
Automatic Transfer Relay 20 amps
Number of Charging Profiles 10
Three-stage Charging Yes (float, absorption, bulk)
A–4 975-0012-01-02 Rev A
Specifications · Model DR1512W DR2412W · Series Operation NO

Specifications of the DR Inverter
Table A-2 Electrical Specifications for the DR Inverter/Chargersa - 220 Vac/60 Hz Models
Temperature Comp Probe (BTS) optional
Remote Control (RC8)d optional
a.Specifications subject to change without notice. b.This is the minimum AC current required to obtain full pass-through and maximum battery charging. c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load. d.Also compatible with the RC4.
Table A-3 Electrical Specifications for the DR Inverter/Chargera - 230 Vac/50 Hz Models
Model DR1512E DR1524E DR1548E DR2424E
AC Input Voltage 230 Vac 230 Vac 230 Vac 230 Vac
AC Input Low Transfer Voltage
80 to 210 Vac 80 to 210 Vac 80 to 210 Vac 80 to 210 Vac
AC Input Currentb 55 amps 55 amps 55 amps 55 amps
Continuous Power (@ 25°C)
Continuous Output (@25 °C)
12.5 amps AC 20 amps AC 12.5 amps AC 20 amps AC
Efficiency 94% max 94% max 94% max 95% max
AC Output Voltage (rms)
230 Vac 230 Vac 230 Vac 230 Vac
Surge Capability:
1 mSec Rating 20 amps AC 20 amps AC 20 amps AC 40 amps AC
DC Input Current:
Search Mode 0.045 amps 0.055 amps 0.030 amps 0.030 amps
Full Voltage 0.700 amps 0.900 amps 0.350 amps 0.450 amps
DC Current at Rated Power
165 amps 280 amps 80 amps 140 amps
Short Circuit Current 400 amps 800 amps 280 amps 560 amps
DC Input Voltage (nominal)c
12.6 Vdc 25.2 Vdc 50.4 Vdc 25.2 Vdc
DC Input Voltage Range
10.9 to 15.5 Vdc 21.8 to 31 Vdc 43.6 to 62 Vdc 21.8 to 31 Vdc
975-0012-01-02 Rev A A–5
Model DR1512W DR2412W

Table A-3 Electrical Specifications for the DR Inverter/Chargera - 230 Vac/50 Hz Models
Model DR1512E DR1524E DR1548E DR2424E
Auto Low Battery Protection enabled
DC Charger Rate (Adjustable)
0 to 70 amps 0 to 35 amps 0 to 17.5 amps 0 to 70 amps
Common Specifications:
±2. 5%
Waveform modified sine wave
Load Power Factor (allowed)
0.5 to 1.0 (leading or lagging)
Adjustable Load Sensing Range
5 watts minimum to 100 watts maximum
Force Air Cooling Variable speed fan
Number of Charging Profiles
Three-stage Charging Yes (float, absorption, bulk)
Temperature Comp Probe (BTS)
Remote Control (RC8)d optional
a.Specifications subject to change without notice. b.This is the minimum AC current required to obtain full pass-through and maximum battery charging. c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load. d.Also compatible with the RC4.
A–6 975-0012-01-02 Rev A

Specifications of the DR Inverter
Table A-4 Environmental Specifications for the DR Inverter/Chargera
Model DR1512 DR2412 DR1524 DR2424 DR3624
8.5" w x 7.25" H x 21" D (21.6 cm W x 18.4 cm H x 54.6 cm D
Unit Weight 35 lbs (16 kg) 45 lbs (21 kg) 35 lbs (16 kg) 40 lbs (16 kg) 45 lbs (21 kg)
“E” Models 38 lbs (18 kg) N/A 39 lbs (18 kg) (45 lbs (21 kg) N/A
Ambient Temp Range (rated 0 to 25 °C):
Operating 0 °C to +50 °C
Storage -55 °C to +75 °C
Altitude:
Mounting Wall-mount (with 16" mounting centers) Shelf Mount
a.Specifications subject to change without notice.
b.Allows for hardware extensions such as mounting rails, DC terminals, and front panel controls.
975-0012-01-02 Rev A A–7
Dimensionsb · Operating 15,000 feet · Non-operating 50,000 feet


Battery Information
Appendix B, “Battery Information” supplies general information about batteries such as battery types, battery bank sizing, battery configurations, and battery care. For detailed information, see your battery manufacturer or your system designer.

Batteries Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel, vented or non-vented, chemistries, etc. They are also available for starting applications (such as an automobile starting battery) and deep discharge applications.
Recommendations Consider the following recommendations for battery use.
There are two principal types of batteries: starting and deep-discharge (with several different types of chemistries). Batteries can be either sealed or non-sealed (vented).
Deep discharge The battery types recommended for use in an inverter system are: Flooded Lead Acid (FLA), Sealed Gel Cells (GEL), Sealed Absorbed Glass Mat (AGM); and alkaline types Nickel-iron (NiFe) and Nickel-Cadmium (NiCad).
Starting Automotive (starting) batteries are designed to provide high starting current for short periods of time and are not appropriate for inverter applications.
Description A flooded lead acid battery is designed to be deep-discharged before being recharged, making it suitable for inverter applications. Flooded batteries require periodic maintenance consisting mainly of adding distilled water to the cells.
Types of FLA Batteries Attributes
B–2 975-0012-01-02 Rev A
Battery Information · Attributes

Description Gel Cell and absorbed glass mat (AGM) batteries are sealed and do not require the addition of distilled water. Since these batteries are valve regulated, over-charging can cause irreversible damage.
Attributes Attributes of sealed batteries are:
Types of Sealed Batteries Attributes
Disadvantages These types of batteries can be used but are not optimized for the DR Inverter for the following reasons:
Consult the battery manufacturer or supplier regarding system requirements and battery charger settings for alkaline type batteries.
975-0012-01-02 Rev A B–3
Battery Types

Discharge rate Deep cycle batteries have their amp-hour rating expressed as “at the x-hour rate”. The hour rating refers to the time it takes to discharge the batteries. A faster hour rate (6 hour rate) means more current is withdrawn from the batteries during their discharge period. There is an inevitable amount of heat associated with the flow of current through a battery and the higher amount of current the greater the amount of heat will be generated. The heat is energy which is no longer available to the battery to power loads. a relatively long discharge rate (72 hour rate) will result in a larger number of amp-hours being available for electrical loads.
Calculation This calculation shows how to determine the level of current drawn from a battery at any given hour rate—battery capacity divided by the hour rate equals the current drawn from the battery. For example, a battery rated 220 Ah at a 6 hour rate would be discharged at 36 amps (220/6).
For most residential applications of the DR Inverter the 72 hour rate is appropriate because on average a household uses low amounts of current (lights, TV, radio for example) with occasional bursts or higher consumption appliances like toasters or washing machines. For those installations where high continuous electrical consumption rates are anticipated it is more appropriate to use the 20 hour rate.
CCA rating The CCA rating (cold cranking amps) shown on starting batteries expresses battery capacity in terms of its ability to provide large amounts of current for intervals measured in minutes, not hours. This is why starting batteries are not appropriate for inverter systems.
Running time and size
The battery bank’s size determines the length of time the inverter can supply AC output power. The larger the bank, the longer the inverter can run.
Depth of discharge In general, the battery bank should be designed so the batteries do not discharge more than 60% of their capacity on a regular basis. Discharging up to 80% is acceptable on a limited basis, such as a prolonged utility outage. Totally discharging a battery can reduce its effective life or permanently damage it.
Days of autonomy For off-grid, stand-alone applications, design a battery bank that can power the loads for three to five days without requiring recharging. This design calculation assumes a worst case scenario where there is no recharging taking place during these days of autonomy.
Days of autonomy may vary depending upon the availability of other charging sources, the critical nature of the load and other factors. If the system is to be powered by renewable energy sources such as solar, wind, and micro-hydro, determine the appropriate number of days of autonomy by allowing for cloudy or calm weather as well as other seasonal variations in available energy.
If an engine generator is part of the system design, the days of autonomy can be determined by simply deciding how often you are prepared to run the generator. Significant battery cost reductions can be achieved by shortening the days of autonomy and allowing a generator to run for a schedule time period daily.
B–4 975-0012-01-02 Rev A
Battery Information

Back up power systems which use utility power for recharging should use the estimated number of days of maximum power outage for determining days of autonomy.
Amp-hours To estimate the battery bank requirements, you must first calculate the amount of power you will draw from the batteries during your period of autonomy. This power draw is then translated into amp hours (Ah)—the unit of measure to express deep-cycle battery capacity.
Amp hours are calculated multiplying the current drawn by the load by the length of time it will operate.
Watts to amps To calculate amps when the power consumption is expressed in watts, use the following equation:
A = W/V where W = watts and V = volts DC
For example:
A 100 watt light bulb will draw approximately 8.33 amps 8.33 = 100 /12 If the light runs for three hours it will consume (8.33 x 3) or 25 Ah of power. Time and power The length of time a load is operated will affect the power draw. In some cases, an appliance which draws a large wattage may not consume as many amp hours as a load drawing fewer watts but running for a longer period of time.
For Example:
A circular saw draws 1500 watts or 125 amps. It takes 5 seconds to complete a cross cut. Twelve such cuts would take a minute and you would consume 125 A x 0.016* hour = 2 Ah *1/60 = 0.016 Observation The circular saw, while it draws more power, consumed fewer amp hours of electricity because it ran for a short period of time.
Calculations To determine the amp hours you will consume, you need to list your anticipated loads and the length of time you will operate each one. Determine the number of hours per day and the number of days during the week you will use the appliance. For example, you use the microwave every day, but a breadmaker only once a week. If you use an appliance for less than an hour, express the time as a decimal portion of an hour.
Amps to watts All electrical appliances have labels which state their energy consumption. Look for an amps rating on motors and a watts rating on other appliances.
If the label plate has expressed power consumption in amps, multiply by volts for the watts required. (watts = volts x amps).
975-0012-01-02 Rev A B–5
Battery Bank Sizing

Considerations When calculating battery bank size, consider the following:
Complete the following steps to calculate the amp-hour requirements per day for your system. Use and Table B-2 as examples to complete your own.
To calculate amp-hour requirements:
This figure represents the average amp-hours per day that you will use.
Table B-1 Determining Average Daily Load in Amp-hours (Example
Days per week used
Load Watts Hours per Day
Breadmaker 1200 0.75 2 1800
200 x 0.3 24 10080
Laptop computer 50 6 5 1500
Total weekly watt-hours of AC load 16005 Wh
Divided by days per week 7
Average total watt-hours per day 2286
Divided by DC nominal voltage 24
Average amp-hours per day (Ah/d) 95
B–6 975-0012-01-02 Rev A
Battery Information · Weekly watt-hours · Energy-efficient refrigerator

Calculation To calculate the battery bank size, use the average amp-hours per day that you calculated using Table B-1, then make the other calculation shown in Table B-2 to calculate the battery bank size you need to support your loads.
Table B-2 Determining Battery Bank Size
Average amp hours per day 95
Divided by inverter efficiency (90%) for DR Inverter 0.9
Divided by battery efficiency (usually 0.75) 0.75
Adjusted hours per day 140
Divided by Depth of Discharge (usually 60%) 0.6
Multiplied by days of autonomy 5
Battery bank size required 1173 Ah
Worksheets Table B-1 and Table B-2 are examples only. Use the specifications noted on the label of each AC appliance and fill in the values specific for the appliances used in this installation on the a work sheet.
Table B-3 provides a typical wattage for selected appliances. However, you should try to find the exact wattage on the appliance label.
Table B-3 Typical Appliance Wattage
Appliance Watts Appliance Watts
Fluorescent Type Light 10 Blender 400
Computer 200-300 Toaster 1000
Microwave (compact) 600-800 Hot Plate 1800
Microwave (full-size) 1500 Washer/Dryer 375-1000
Stereo or VCR 50 3/8" Drill 500
Color Television (19") 150 Hair Dryer or Iron 1000
Refrigerator (3 cu ft) 180 Vacuum Cleaner 1200
Refrigerator (12 cu ft) 480 Coffee Maker 1200
975-0012-01-02 Rev A B–7
Battery Bank Sizing

The battery bank must be wired to match the inverter’s DC input voltage specifications (12 or 24 Vdc). In addition, the batteries can be wired to provide additional run time. The various wiring configurations are:
Series Wiring batteries in series increases the total bank output voltage. This voltage MUST match the DC requirements of the inverter or inverter and/or battery damage may occur.
Parallel Wiring the batteries in parallel increases the total run time the batteries can operate the AC loads. The more batteries connected in parallel the longer the loads can be powered from the inverter.
Series-Parallel Series-parallel configurations increase both the battery voltage (to match the inverter’s DC requirements) and run-time for operating the AC loads. This voltage must match the DC requirements of the inverter.
Batteries with more than two or three series strings in parallel often exhibit poor performance characteristics and shortened life.
Effect Wiring the batteries in a series configuration increases the voltage of the battery string. Six-volt batteries can be combined to form 12-volt, 24-volt, or 48-volt battery banks. In the same way, 12-volt batteries connected in series form 24-volt battery banks. The total current capacity of the bank does not increase and remains the same amp-hour rating as it does for a single battery.
rating is 100 Ah.
rating is 100 Ah.
+ - + -
+ - + -
6 V 6 V
6 V 6 V
SHUNT
SHUNT
fuse with a disconnect)
12 V INVERTER (Total battery capacity = 100 Ah)
fuse with a disconnect)
24 V INVERTER (Total battery capacity = 100 Ah)
Figure B-1 6-volt Battery Wiring - “Series” Configuration
B–8 975-0012-01-02 Rev A

Each battery's amp-hour rating
is 100 Ah.
SHUNT
+ -
fuse with a disconnect)
24 V INVERTER (Total battery capacity = 100 Ah)
Figure B-2 12-volt Battery Wiring - “Series” Configuration
Effect Wiring the batteries in a parallel configuration increases the current of the battery string. The voltage of the battery bank remains the same as an individual battery. “Parallel” configurations extend the run times of the AC loads by providing increased current for the inverter to draw from. In a parallel configuration, all the negative battery terminals are connected together and all the positive battery terminals are connected together.
Wiring example Figure B-3 is an example of how to wire batteries in a parallel configuration.
Each battery's amp-hour rating
is 100 Ah.
SHUNT
+ -
fuse with a disconnect)
12 V INVERTER (Total battery capacity = 200 Ah)
Figure B-3 Battery Wiring in Parallel
975-0012-01-02 Rev A B–9

Effect Wiring the batteries in a series-parallel configuration increases the current and voltage of the battery bank. “Series-parallel” wiring is more complicated and care should be taken when wiring these banks.
Steps It is done in three steps; wiring the batteries in series, wiring them in parallel, then wiring the string to the inverter.
Series wiring To wire in series:
Two identical strings of batteries are now wired in series.
+ – + –
+ – + –
6 V 6 V
rating is 100 Ah.
+ – + –
+ – + –
6 V 6 V
Figure B-4 Battery Wiring 24-volt - Parallel Configuration - Step 1
Parallel wiring To wire the batteries in parallel:
rating is 100 Ah.
+ – + –
6 V 6 V
+ – + –
+ – + –
6 V 6 V
Figure B-5 Battery Wiring 24-volt - Parallel Configuration - Step 2
B–10 975-0012-01-02 Rev A

Connect to inverter To connect to the inverter:
Connection from Series String 1 to inverter's positive (+) terminal
+ – + –
6 V 6 V
rating is 100 Ah.
– + – + – +
6 V 6 V
SHUNT
DC Disconnect (can be either a circuit breaker or a
Connection from Series String 2 to
inverter's negative (–) terminal
fuse with a disconnect)
24 V INVERTER (Total battery capacity = 200 Ah)
Figure B-6 Battery Wiring 24-volt - Parallel Configuration - Step 3
975-0012-01-02 Rev A B–11

When using inverters in a stacked configuration, the same battery bank must be used for both inverters. To ensure even charging of the batteries, each inverter must be connected to both strings (i.e., positive cable to string two, and negative cable to string one for inverter 1, and positive cable to string one and negative cable to string two for inverter 2) as shown in the diagram below.
DC CONDUIT
FOR INVERTER 2
FOR INVERTER 1
DC Disconnect (either a circuit
fuse with a disconnect)
fuse with a disconnect)
– + 12 Volt Battery 200 Ah
– + 12 Volt Battery
Parallel 24 VDC 400 Ah
– + 12 Volt Battery
12 Volt Battery 200 Ah
Figure B-7 Example of Battery Connections for Stacked Inverters (24 Vdc shown)
B–12 975-0012-01-02 Rev A

To get the best performance from an inverter system, the batteries must be properly setup and maintained. This includes setting the proper voltages for Bulk and Float charging. See the “CAUTIONS” in the section on Equalization Charging that follows. In addition, the battery terminals should be inspected, cleaned, and re-torqued if necessary.
Neglecting any of these items may result in poor inverter performance and greatly reduce battery life.
Charge Rate The maximum safe charge rate is related to the size and type of the batteries. Flooded lead acid batteries (with removable caps) can be charged at a high rate. Small batteries may require a lower charge rate. Check with your battery vendor for the proper battery charging rate for the batteries used in the system.
Bulk Voltage This is the maximum voltage the batteries will be charged to during a normal charge cycle. Gel cell batteries are set to a lower value and non-sealed batteries are set to a higher voltage setting.
Float Voltage The Float voltage is set lower than the Bulk voltage and provides a maintenance charge on the batteries to keep them in a ready state.
For optimal battery charging, the Bulk and Float charge rates should be adjusted according to the temperature of the battery. This can be accomplished automatically by using a BTS. The sensor attaches directly to the side of one of the batteries in the bank and provides precise battery temperature information.
When battery charging voltages are compensated based on temperature, the charge voltage will vary depending on the temperature around the batteries. The following table describes approximately how much the voltage may vary depending on the temperature of the batteries.
If you have liquid lead acid batteries (non-sealed), you may need to periodically equalize your batteries. Check the water level monthly to maintain it at the appropriate level.
975-0012-01-02 Rev A B–13
Battery Maintenance · Maintenance strategy · Temperature Compensation

Table B-4 Variances in Charging Voltage based on Battery Temperature
Temperature (around the BTS) 12-volt units 24-volt units 48-volt units
NiCad (40 cells) 60 140 -1.05 -0.70 -2.10 -1.40 -4.20 -2.80 55 131 -0.90 -0.60 -1.80 -1.20 -3.60 -2.40 50 122 -0.75 -0.50 -1.50 -1.00 -3.00 -2.00 45 113 -0.60 -0.40 -1.20 -0.80 -2.40 -1.60 40 104 -0.45 -0.30 -0.90 -0.60 -1.80 -1.20 35 95 -0.30 -0.20 -0.60 -0.40 -1.20 -0.80 30 86 -0.15 -0.10 -0.30 -0.20 -0.60 -0.40 25 77 0.00 20 68 0.15 0.10 0.30 0.20 0.60 0.40 15 59 0.30 0.20 0.60 0.40 1.20 0.80 10 50 0.45 0.30 0.90 0.60 1.80 1.20 5 41 0.90 0.60 1.20 0.80 2.40 1.60 0 32 0.75 0.50 1.50 1.00 3.00 2.00 -5 23 0.90 0.60 1.80 1.20 3.60 2.40 -10 14 1.05 1.20 2.10 1.40 4.20 2.80 -15 5 1.20 0.80 2.40 1.60 4.80 3.20 -20 -4 1.35 1.40 2.70 1.80 5.40 3.60 -25 -13 1.50 1.00 3.00 2.00 6.00 4.00 -30 -22 1.65 1.10 3.30 2.20 6.60 4.40 -35 -31 1.80 1.20 3.60 2.40 7.20 4.80 -40 -40 1.95 1.30 3.90 2.60 7.80 5.20
Lead Acid (6 cells)
Lead Acid (12 cells)
Lead Acid (24 cells)
Temperature compensation is based on battery type — 5 mv/cell for lead acid type batteries and 2 mv/cell for alkaline type batteries (NiCad or NiFe). The temperature compensation calculations are derived from Table B-5.
Table B-5 Temperature Compensation Calculation
Battery Type 24-volt Systems 48-volt Systems
Lead Acid 0.060 volts (60 mV) per degree Celsius
0.120 Volts (120 mV) per degree Celsius
NiCad 0.040 volts (40 mV) per degree Celsius
0.080 volts (80 mV) per degree Celsius
B–14 975-0012-01-02 Rev A

Purpose An equalize charge helps to remove sulfate buildup on the battery plates and balances the charge of individual cells.
Effect Equalize charging also produces gassing which stirs up the electrolyte mixture and helps distribute the acid more evenly.
Batteries that are not equalize charged can be damaged by sulfate accumulation, thus sealing off a percentage of the plates and reducing battery capacity. They may also have sulfuric acid accumulate at the bottom of the battery, potentially damaging the plates. At the same time, the electrolyte at the top of the battery gets watery. This effect is called stratification.
Frequency Every month or two the batteries should be equalize charged.
975-0012-01-02 Rev A B–15
Battery Maintenance · Non-equalized batteries

Water Levels Flooded lead acid batteries require periodic water refills in each battery cell. Only distilled water should be used in a battery, as tap or mineral water may contain contaminants which will upset the battery chemistry and may damage the battery.
When filling the battery, clean the surface first to prevent dirt from entering the cell. Fill the cell to just above the plates or to the bottom of the internal collar inside the battery. Never fill the cells to the top or acid will leak out during charging.
Check the water level in the batteries frequently when performing an equalize charge and add water if necessary. Always follow the safety steps covered in the front of the manual.
Battery Cables and Posts
Battery posts must be clean to reduce the resistance between the battery post and cable connection. A buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high current draw.
Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables. Use an alkaline solution of baking soda and water to clean the terminals and neutralize any battery acid on the terminals or cable lugs.
After the terminals are clean, reassemble the cable to the battery terminal and torque the connections to the battery manufacturer’s recommendations.
Coat the battery terminals with an antioxidant compound.
B–16 975-0012-01-02 Rev A
Battery Information · Torque Battery Connections

State of Charge The battery’s state-of-charge should be checked often and only when the battery at a state of rest (when the battery is not powering loads or actively being charged). First thing in the morning is usually the best time to check the state of charge. If the batteries are readily accessible, measure the voltage across the individual battery terminals. There should be less than a 0.2 volt difference between each battery.
To determine the individual cell voltage, divide the voltage by the number of cells in the battery (25.2 volts divided by 12 cells = 2.1 volts per cell). If a greater difference is measured, the batteries may need to be equalized (liquid lead-acid types only) or replaced.
All batteries in the bank should measure the same voltage (this is not an accurate measurement for cross-tied batteries’ as each battery is in parallel with another battery making individual battery measurements impossible).
The voltage should match the following table for the entire battery bank output. These values indicate the overall battery’s state of charge for the entire bank. Individual cell voltages (if available) are also shown as a percentage of charge.
The values given are for a temperature of 77 °F (25 °C). Cooler temperatures produce lower voltage measurements.
Table B-6 Battery State-of-Charge
Percent of Full Charge 12 Volt 24 Volt 48 Volt
100% 12.7 25.4 50.8 2.12
90% 12.6 25.2 50.4 2.10
80% 12.5 25.0 50.0 2.08
70% 12.3 24.6 49.2 2.05
60% 12.2 24.4 48.8 2.03
50% 12.1 24.2 48.4 2.02
40% 12.0 24.0 48.0 2.00
30% 11.8 23.6 47.2 1.97
20% 11.7 23.4 46.8 1.95
10% 11.6 23.2 46.4 1.93
0% < 11.6 < 23.2 < 46.4 < 1.93
975-0012-01-02 Rev A B–17
Battery Maintenance · System Voltage · Individual Cell Voltage


Appendix C, “Multi-wire Branch Circuit Wiring” supplies information about Multi-wire Branch Circuit Wiring Precautions when using stand-alone 120 Vac inverters or generators.

Multi-wire Branch Circuit Wiring
Problem A potential safety problem exists when installing stand-alone 120 Vac inverters into existing 120/240 Vac wired panels where multi-wire branch circuit wiring methods were used.
Legacy situation Multi-wire branch circuits are wired differently from “home run” type wiring (Figure C-1) in that only one neutral wire is used to provide the neutral-return path for each circuit connected to both phases of the AC grid. This method has been employed by electricians in recent years to keep construction costs down by saving copper and labor costs involved in running a separate Romex™ for each circuit.
Normal condition Under normal conditions, this technique is quite safe and meets code requirements. When used as originally installed, the current for each circuit is 180° out-of-phase with each other, so the neutral wire never receives more current than it was designed to handle as the current from each circuit subtracts (or cancels out, leaving only the difference current between the two circuits). Refer to Figure C-2.
Safety issue A safety problem occurs when a stand-alone 120 Vac inverter is installed to power these circuits, causing the one neutral wire to now carry the in-phase currents for both circuits. Since the current is in-phase, the two circuits add instead of subtract, potentially doubling the current flow in the neutral return wire! Refer to Figure C-3. The branch circuit breakers do not protect the neutral wire from overload under this condition. This excess current will overheat the neutral wire, potentially creating a fire hazard.
240 Vac from Grid
Black - Hot (Current Flow 15A)
Black - Hot (Current Flow 15A)
White - Neutral (Current Flow 15 A)
White - Neutral (Current Flow 15 A)
Figure C-1 Conventional Home-type Wiring
C–2 975-0012-01-02 Rev A

240 Vac from Grid
240 Vac from Grid
15 A Breaker (Ganged)
15 A Breaker (Ganged)
15 A Breaker (Ganged)
15 A Breaker (Ganged)
Red - Hot (Current Flow 15 A)
Red - Hot (Current Flow 15 A)
Black - Hot (Current Flow 15 A)
Black - Hot (Current Flow 5 A)
Single White - Neutral (Current Flow 0 A)
120 Vac 120 Vac
Single White - Neutral (Current Flow 10 A)
120 Vac 120 Vac
Bare - Ground Splice
When unbalanced current flows through each leg, only the difference current flows through the neutral return wire.
White - Neutral Splice (Current Flow 15 A) Out-of-Phase current subtract at this point (Current Flow 0 A)
White - Neutral Splice (Current Flow 15 A)
Figure C-2 Multi-wire Branch Circuit Wiring and Current Flow
120 Vac Inverter or Generator
15 A Breaker (Ganged)
15 A Breaker (Ganged)
Red - Hot (Current Flow 15 A
Black - Hot (Current Flow 15 A)
Single White - Neutral (Current Flow 30 A)
120 Vac 120 Vac
White - Neutral Splice (Current Flow 15 A) WARNING: FIRE HAZARD The in-phase currents ADDS at this point exceeding wire capacity!
Figure C-3 120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit
975-0012-01-02 Rev A C–3

Multi-wire Branch Circuit Wiring
Multi-wire branch circuits can be identified by removing the cover on the load center and inspecting the wiring. Conventional 120 Vac circuits are identified by a 2-wire-plus-ground (black, white, and copper) “romex” for each circuit. Multi-wire branch circuits use a 3-wire-plus-ground arrangement (black, red, white and copper) for each circuit run.
If this arrangement exists in the panel and it is being powered by a stand-alone 120 Vac inverter, a potential fire hazard exists! For safety, these circuits must be rewired to meet code.
Figure C-4 Multi-wire Branch Circuit Wiring
C–4 975-0012-01-02 Rev A

Correcting Multi-wire Branch Circuit Wiring
Acceptable options Correcting multi-wire branch circuit wiring is not easy. Two options which will correct multi wiring branch circuit wiring are:
Add a step-down autotransformer to the output of the inverter to restore the split-phase configuration. This is the least expensive and easiest method to correct for multi-wire branch circuit wiring. Refer to Figure C-5. Using this method, half of the current is supplied to one leg of the circuit and half to the other in a split-phase arrangement (180° out-of-phase). This will restore the original functionality and safety to the multi-wire branch circuit.
975-0012-01-02 Rev A C–5

Multi-wire Branch Circuit Wiring
120 Vac Inverter or Generator
HOT
HOT - L1
HOT - L2
15 A Breaker (Ganged)
15 A Breaker (Ganged)
Red - Hot (Current Flow 15 A
Black - Hot (Current Flow 15 A)
Single White - Neutral (Current Flow 0 A)
120 Vac 120 Vac
White - Neutral Splice (Current Flow 15 A)
The out-of-phase current SUBTRACTS at this point.
Figure C-5 Using a Step-down Autotransformer in Multi-wire Branch Circuit Wiring
C–6 975-0012-01-02 Rev A

Warranty
What does this warranty cover? This Limited Warranty is provided by Xantrex Technology, Inc. ("Xantrex") and covers defects in workmanship and materials in your DR Inverter/Charger. This warranty period lasts for Warranty period from the date of purchase at the point of sale to you, the original end user customer. You require proof of purchase to make warranty claims. This Limited Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty Period. Subsequent owners also require proof of purchase. What will Xantrex do? Xantrex will, at its option, repair or replace the defective product free of charge, provided that you notify Xantrex of the product defect within the Warranty Period, and provided that Xantrex through inspection establishes the existence of such a defect and that it is covered by this Limited Warranty. Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and building replacement products. Xantrex reserves the right to use parts or products of original or improved design in the repair or replacement. If Xantrex repairs or replaces a product, its warranty continues for the remaining portion of the original Warranty Period or 90 days from the date of the return shipment to the customer, whichever is greater. All replaced products and all parts removed from repaired products become the property of Xantrex. Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer via a Xantrex-selected non-expedited surface freight within the contiguous United States and Canada. Alaska and Hawaii are excluded. Contact Xantrex Customer Service for details on freight policy for return shipments outside of the contiguous United States and Canada. How do you get service? If your product requires troubleshooting or warranty service, contact your merchant. If you are unable to contact your merchant, or the merchant is unable to provide service, contact Xantrex directly at:
1 360 925 5097 (direct) Fax: 1 800 994 7828 (toll free North America) 1 360 925 5143 (direct) Email: customerservice@xantrex.com
975-0012-01-02 Rev A WA–1

What does this warranty not cover? This Limited Warranty does not cover normal wear and tear of the product or costs related to the removal, installation, or troubleshooting of the customer's electrical systems. This warranty does not apply to and Xantrex will not be responsible for any defect in or damage to: a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either inter- nally or externally, or damaged from improper use or use in an unsuitable environment; b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input voltage that creates operating conditions beyond the maximum or minimum limits listed in the Xantrex product specifi- cations including high input voltage from generators and lightning strikes; c) the product if repairs have been done to it other than by Xantrex or its authorized service centers (hereafter "ASCs"); d) the product if it is used as a component part of a product expressly warranted by another manufacturer; e) the product if its original identification (trade-mark, serial number) markings have been defaced, altered, or removed.
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN CONNECTION WITH YOUR XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS, GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE IN CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD STIPULATED UNDER THIS LIMITED WARRANTY.
IN NO EVENT WILL XANTREX BE LIABLE FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR TORT INCLUDING WITHOUT RESTRICTION ANY ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO PROPERTY, ANY PERSONAL INJURY, ANY DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION, INTEGRATION OR OPERATION OF THE PRODUCT.
If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To the extent you are entitled to implied warranties under federal law, to the extent permitted by applicable law they are limited to the duration of this Limited Warranty. Some states and provinces do not allow limitations or exclusions on implied warranties or on the duration of an implied warranty or on the limitation or exclusion of incidental or consequential damages, so the above limitation(s) or exclusion(s) may not apply to you. This Limited Warranty gives you specific legal rights. You may have other rights which may vary from state to state or province to province.
Please refer to your product manual for limitations on uses of the product. SPECIFICALLY, PLEASE NOTE THAT THE DR INVERTER/CHARGER SHOULD NOT BE USED IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES. WITHOUT LIMITING THE GENERALITY OF THE FOREGOING, XANTREX MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE USE OF THE XANTREX DR INVERTER/CHARGER IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES. Please note that the DR Inverter/Charger is not intended for use as an uninterruptible power supply and Xantrex makes no warranty or representation in connection with any use of the product for such purposes.
WA–2 975-0012-01-02 Rev A
Warranty and Return

Record these details in on page WA–4.
If you are returning a product from outside of the USA or Canada In addition to the above, you MUST include return freight funds and are fully responsible for all documents, duties, tariffs, and deposits. If you are returning a product to a Xantrex Authorized Service Center (ASC) A Xantrex return material authorization (RMA) number is not required. However, you must contact the ASC prior to returning the product or presenting the unit to verify any return procedures that may apply to that particular facility.
If the warranty period for your DR Inverter/Charger has expired, if the unit was damaged by misuse or incorrect installation, if other conditions of the warranty have not been met, or if no dated proof of purchase is available, your inverter may be serviced or replaced for a flat fee. To return your DR Inverter/Charger for out of warranty service, contact Xantrex Customer Service for a Return Material Authorization (RMA) number and follow the other steps outlined in “Return Procedure” on page WA–3. Payment options such as credit card or money order will be explained by the Customer Service Representative. In cases where the minimum flat fee does not apply, as with incomplete units or units with excessive damage, an additional fee will be charged. If applicable, you will be contacted by Customer Service once your unit has been received.
975-0012-01-02 Rev A WA–3
Warranty and Return

As soon as you open your DR Inverter/Charger package, record the following information and be sure to keep your proof of purchase.
❐ Serial Number
❐ Purchased From
❐ Purchase Date
If you need to contact Customer Service, please record the following details before calling. This information will help our representatives give you better service.
❐ Type of installation (e.g. On-Grid, Off-grid)
❐ Length of time inverter has been installed
❐ Battery/battery bank size
❐ Battery type (e.g. flooded, sealed gel cell, AGM)
❐ DC wiring size and length
❐ Alarm sounding?
❐ Description of indicators on front panel
❐ Appliances operating when problem occurred
❐ Description of problem
WA–4 975-0012-01-02 Rev A
Warranty and Return

P peak output voltage 4–4 Problem Loads 4–3 proof of purchase WA–4 purchase date WA–4
R Reverse Polarity 2–18
Battery Care and Maintenance
Equalization Charging B–15 Temperature Compensation B–13 Battery Types
Absorbed Glass Mat B–3 Flooded Lead Acid (FLA) B–2 Gel Cell B–3 Golf Cart B–2 Industrial (electric forklift) B–2 NiCad and NiFe B–3 Charging
out of warranty service WA–3 terms and conditions WA–1
Bulk Voltage B–13 Charge Rates B–13 Float Voltage B–13 batteries
first aid when working with vii precautions when working with vii Battery B–13
preparing to call WA–4
I Information about Your System form WA–4 inverter
purchase date WA–4 serial number WA–4
web site iv





Xantrex Technology Inc.
1 800 670 0707 Tel. toll free NA 1 360 925 5097 Tel direct 1 800 994 7828 Fax toll free NA 1 360 925 5143 Fax direct customerservice@xantrex.com www.xantrex.com
975-0012-01-02 Rev A PC Printed in the DR
Pages referenced in this manual — manufacturer, support and downloads.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| C-3 | The branch circuit breakers do not protect the neutral wire from overload | p.110 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.