EN
Weil-McLain logo
Official user manual

Weil-McLain CF3500A-W

4 pages·528 KB·Burner·PDF·EN
Weil-McLain CF3500A-W
Table of Contents 16 sections Water & Steam Boilers – Series 2 88 · Beckett · Burner Specification · Oil Burners · … ShowHide
Page 1 of the Weil-McLain CF3500A-W user manual — Models CF1400-W, CF2300A-W,
Page 1 · click to enlarge
Page 1

Water & Steam Boilers – Series 2 88

For Gas, Light Oil, & Gas/Light Oil – Fired Burners

Beckett

Burner Specification

Oil Burners

& Data Sheet

Models CF1400-W, CF2300A-W,

CF2500-W, CF3500A-W

Model CF1400-W Figure 1 Model CF2300A-W Figure 2

Weil-McLain CF3500A-W — Models CF1400-W, CF2300A-W, diagram (page 1)
Fig. 1 · Models CF1400-W, CF2300A-W,
Weil-McLain CF3500A-W — Models CF1400-W, CF2300A-W, diagram (page 1)
Fig. 2 · Models CF1400-W, CF2300A-W,
Weil-McLain CF3500A-W — Models CF1400-W, CF2300A-W, diagram (page 1)
Fig. 3 · Models CF1400-W, CF2300A-W,
Weil-McLain CF3500A-W — Models CF1400-W, CF2300A-W, diagram (page 1)
Fig. 4 · Models CF1400-W, CF2300A-W,
Weil-McLain CF3500A-W — Models CF1400-W, CF2300A-W, diagram (page 1)
Fig. 5 · Models CF1400-W, CF2300A-W,
Dimensions in Inches Burner Model NumberLength (From Mounting Flange To Label Area On Burner Front)Overall WidthMotor Size H.P.Standard Motor Electrical CharacteristicsOptional Motor Electrical Characteristics CF1400-W20.7522.501/2120/60/1208-240/60/1* 208-240-480/60/3 CF2300A-W21.2524.003/4120/60/1208-240/60/1* 208-240-480/60/3 CF2500-W23.5027.002240/60/1208-240-480/60/3 CF3500A-W23.5027.002240/60/1208-240-480/60/3 * Optional motor contactor supplied.
Page 2 of the Weil-McLain CF3500A-W user manual — Burner data Table 1
Page 2 · click to enlarge
Page 2

Weil-McLain 88 Water and Steam Boilers — Series 2 — For Gas, Light Oil, & Gas/Light Oil-Fired Burners

Burner specifications and settings

Burner data Table 1

Boiler Model NumberBurner Input (Forced Draft) No. 2 OilLow Fire Firing Rate No. 2 OilPositive Pressure in FireboxStandard Burner Model DesignationBecket Part Number for Ordering GPHGPHInches W.C. 488R6.904.900.60CF1400-WWL 7001 4887.005.000.60CF1400-WWL 7001 5889.406.80.60CF2300A-WWL7101 68811.808.510.65CF2300A-WWL7102 78814.2010.410.65CF2300A-WWL7103 88816.608.300.65CF2500A-WWL7201 988R17.2011.600.65CF2500A-WWL7202 98818.809.530.65CF2500A-WWL7202 1088R20.009.540.65CF2500A-WWL7301 108821.5011.260.65CF2500-WWL7301 118823.5012.300.65CF2500-WWL7302 128826.0013.000.65CF3500A-WWL7401 138828.5015.000.70CF3500A-WWL7402
Weil-McLain CF3500A-W — Burner data Table 1 diagram (page 2)
Fig. 6 · Burner data Table 1
Boiler Model NumberStandard Combustion ControlAir Tube CombinationStarting Head SettingApproximate Air Settings Low FireHigh Fire 488RBeckett 7505P1515/CCCF66KD43954 488Beckett 7505P1515/CCCF66KD43954 588Beckett 7505P1515/CCCF66KG03442 688Beckett 7505P1515/CCCF66KG34151 788Beckett 7505P1515/CCCF66KG64354 888Beckett 7505P1515/CCCF66KP22550 988RBeckett 7505P1515/CCCF66KP42854 988Beckett 7505P1515/CCCF66KP42752 1088RHoneywell RM7840MCF66KP82959 1088Honeywell RM7840MCF66KP82959 1188Honeywell RM7840MCF66KP32944 1288Honeywell RM7840MCF80KM33163 1388Honeywell RM7840MCF80KM63398
Weil-McLain CF3500A-W — Burner data Table 1 diagram (page 2)
Fig. 7 · Burner data Table 1
Page 3 of the Weil-McLain CF3500A-W user manual — a) Beckett 7505P1515/CC combustion control uses
Page 3 · click to enlarge
Page 3

Burner Specification & Data sheet — Beckett Oil Burners

Burner specifications and settings (continued)

Burner data, continued Table 2

Boiler Model NumberOil Nozzle(s)Operating Oil Pressures PSIGFuel Unit Burner-Motor Driven 3450 RPM Preferred nozzlesAlternate nozzles Qty.Size GPHBrandTypeSpray AngleQty.Size GPHBrandTypeSpray AngleLow FireHigh FireType (Suntec)Nozzle Capacity GPHGearse Capacit GPH 488R14.00DelavanB70°None150290B2TA-88511633 48814.00DelavanB70°None150300B2TA-88511633 58815.50HagoP60°15.50DelavanB60°150300B2TA-88511633 68817.00DelavanB60°None150300B2GA-88522339 78818.50DelavanB60°18.50HagoP60°150300J4PA-C1050G3046 88825.00DelavanB60°25.00MonarchPLP45°300300J4PA-C1050G3046 988R25.50HagoP60°25.50DelavanB60°290290J4PA-C1050G3046 98825.50HagoP60°25.50DelavanB60°300300J4PA-C1050G3046 1088R26.00DelavanB70°26.00DelavanB60°300300J4PA-C1050G3046 108826.50DelavanB70°26.50DelavanB60°300300J4PA-C1050G3046 118827.00DelavanB45°27.00DelavanB60°300300J4PA-C1050G3046 128827.50DelavanB45°27.50MonarchPLP45°300300J4PA-C1050G3046 138828.50DelavanB60°28.50HagoP45°300300J4PA-C1050G3046

Notes for Table 1 and Table 2

Burner capacities listed for elevations up to 2,000 feet. For 1. higher elevations, consult local Weil-McLain distributor/ agent or sales office. Light oil ratings based on No. 2 fuel oil with heating value of 2. 140,000 Btu per gallon. Boiler-burner unit to be adjusted to achieve +0.10 inches 3. W.C. pressure at the flue collar, resulting in positive pressure in firebox as listed. Control Systems: 4.

cadmium cell for flame detector to monitor oil burner flame, also furnishes intermittent ignition.

b) RM7840M flame safeguard control monitors the oil burner flame, provides pre-purge and post-purge programming. Timed low fire start is provided by means of timing built into control. Control is used with UL on-off (low fire start) systems. Photocell electronic flame detector is standard with ultraviolet and infrared detector available.

  • LHO: On-off operation, low fire start, high fire run. Two-position air, two-position oil.

Burners will be completely assembled and wired. 7.

  • LHL: Low-high-low-off firing conditions. Twoposition air, two-position oil. 120/60/1 control circuit is used for all burners. 5. Combustion Controls: 6.

Burners listed by Underwriters Laboratories, Inc., Underwrit- 8. ers Laboratory Canada, State of Connecticut, Fire Marshal state of Massachusetts, city of New York MEA, and others.

Settings shown are for initial set-up. Final settings should be 9. determined after combustion readings.

a) Beckett 7505P1515/CC combustion control uses

Page 4 of the Weil-McLain CF3500A-W user manual — Burner dimensions
Page 4 · click to enlarge
Page 4

Weil-McLain 88 Water and Steam Boilers — Series 2 — For Gas, Light Oil, & Gas/Light Oil-Fired Burners

Burner dimensions

Weil-McLain CF3500A-W — Burner dimensions diagram (page 4)
Fig. 8 · Burner dimensions
Weil-McLain CF3500A-W — Burner dimensions diagram (page 4)
Fig. 9 · Burner dimensions
Dimensions in Inches Burner Model NumberAir Tube CombinationABCDEFG H Overall LengthInsertion DepthMaximum Tube O.D.Burner Length (External To Appliance)Overall HeightBolt CircleCenterline Centerlin To Pump To Motor F1400-WCF66KD24.754.005.5020.6313.5010.259.50 9.82 F2300A-WCF66KG25.254.006.5021.1315.6010.2510.40 12.00 F2300A-WCF66KS25.254.008.1321.1315.6010.2510.40 12.00 F2500-WCF66KP26.254.006.5022.1317.7010.2512.70 14.10 F3500A-WCF80KM27.504.507.8723.3817.7010.2512.70 14.10

Ask about the Weil-McLain CF3500A-W

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Weil-McLain CF3500A-W

Be the first to ask — other owners or our team will answer.

Original document

Weil-McLain CF3500A-W manual PDF

4 pages·528 KB·Burner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…