INSTALLER/CONSUMERp.1SAFETY INFORMATIONp.1Homeowner’s Installationp.1and Operating Manualp.1Installation & Operating Instructionsp.2Locating Your Fireplacep.2A Ap.2LU584-2p.2Clearance to Combustiblesp.7F G H Ip.7CFM197p.7Mantelsp.7CFM170p.7Hearthp.7Framing & Finishingp.8360DVS2/ 360DVS3/ 360DVSL/ 360DVSR CERTIFIED TOp.8ANSI Z21.88-2005 / CSA 2.33-2005p.8Final Finishingp.8Gas Line Installationp.8EB-1 Electrical Junction Box Connectionp.9Remote ON/OFF Switch Installationp.9TP THp.9TPp.9THp.9Alternate Switch Locationp.9Optional Top Vent Applicationp.10Electronic Gas Control Valvep.11PILOTp.11HONEYWELL IGNITION MODULEp.11MV MV/VP PV GRD 24V SENSE SPARKp.11REDp.11ORANGEp.11LOp.11HIp.11NOVA SIT 822 VALVEp.11BLUEp.11WHITEp.11POWER CORD W/FEMALE SPADEp.11120 VAC RTNp.1124 VAC HOTp.11BLACKp.11OFFp.11YELLOWp.11GREENp.1124 VAC RETp.11120 VAC HOTp.1140VA TRANSFORMERp.11WALL SWITCHp.11BLACK WHITEp.11General Ventingp.11General Information Assembling Vent Pipesp.13Twist Lock Pipesp.13How to Use the Vent Graphp.14Rear Wall Applicationp.14Rear Wall Installationp.14STEP 5p.15Vertical Sidewall Applicationp.15STEP 3p.15Vertical Side Wall Installationp.16STEP 1p.16STEP 4p.17STEP 6p.17Below Grade Installationp.18Vertical Through-the-Roof Applicationp.19Vertical Through-the-Roof Installationp.20Twist Lock Venting Componentsp.21Operating Instructionsp.22Glass Informationp.22Louvre Removalp.22Window Frame Assembly Removalp.22Glass Cleaningp.23Log Installationp.23Ceramic Refractory Installationp.23B122p.24B120p.24B126 B125p.24B123 B124p.24B121p.24LG320p.24B120 B121p.24
Page 1 of the Vermont Casting 360DVSR user manual — D
Page 1 · click to enlarge
Page 1

Multisided Top/Rear Vent Convertible Direct Vent Fireplaces: 360DVS2 360DVS3 360DVSL 360DVSR

INSTALLER/CONSUMER

SAFETY INFORMATION

PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard, and will void the warranty. WARNING: If the information in this manual is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or loss of life.

  • FOR YOUR SAFETY:
  • Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
  • Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. If you smell gas: 1. Open windows 2. Do not touch electrical switches. 3. Do not try to light any appliance. 4. Extinguish any open flame. 5. Do not use any telephone in your building. 6. Immediately call your gas supplier from a neighbor’s phone. 7. Follow your gas supplier’s instructions. 8. If you cannot reach your gas supplier, call the fire department.

Homeowner’s Installation

and Operating Manual

D

E

S

G

N

E

R

T

F

E

D

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

10006326 6/06 Rev. 1

,/

Page 2 of the Vermont Casting 360DVSR user manual — Locating Your Fireplace
Page 2 · click to enlarge
Page 2

Installation & Operating Instructions

This gas appliance should be installed by a qualified installer in accordance with local building codes and current CSA-B149.1 Installation Codes for Gas Burning Appliances and Equipment. If the unit is being installed in a mobile home, the installation should comply with the current CAN/CSA Z 240.4 code. For U.S.A. Instal- lations, follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54. In the Commonwealth of Massachusetts, all gas fittings and installation of this appliance shall be done by a licensed gas fitter or licensed plumber. FOR SAFE INSTALLATION AND OPERATION PLEASE NOTE THE FOLLOWING: 1. This fireplace gives off high temperatures and should be located out of high traffic areas and away from furniture and draperies. 2. Children and adults should be alerted to the hazards of high surface temperatures of this fireplace and should stay away to avoid burns or ignition of clothing. 3. CAUTION: Due to high glass surface temperature, chil- dren should be carefully supervised when in the same room as fireplace. 4. Under no circumstances should this fireplace be modified. Parts removed for servicing should be replaced prior to operating this fireplace again. 5. Installation and any repairs to this fireplace must be per- formed by a qualified installer, service agency or gas sup- plier. A professional service person should be contacted to inspect this fireplace annually. Make it a practice to have all of your gas fireplaces checked annually. More frequent cleaning may be required due to excess lint and dust from carpeting, bedding material, etc. 6. Control compartments, burners and air passages in this fireplace should be kept clean and free of dust and lint. Make sure the gas valve and pilot light are turned off be- fore you attempt to clean this fireplace. 7. The venting system (chimney) of this fireplace should be checked at least once a year, and if needed, your venting system should be cleaned. 8. Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor and liquids. This fireplace should not be used as a drying rack for clothing, nor should Christmas stockings or decorations be hung on or around the fireplace. 9. Under no circumstances should any solid fuels (wood, coal, paper or cardboard, etc.) be used in this fireplace. 10. The flow of combustion and ventilation air must not be obstructed in any way. 11. When the fireplace is installed directly on carpeting, vinyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace. 12. This fireplace requires adequate ventilation and combus- tion air to operate properly. 13. This fireplace must not be connected to a chimney flue serving a separate solid fuel-burning fireplace. 14. When the fireplace is not in use, it is recommended the gas valve be left in the “OFF” position.

This appliance may be installed in an aftermarket, per- manently located, manufactured home, or mobile home where not prohibited by local codes. This appliance is only for use with type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

IMPORTANT: PLEASE REVIEW THE FOLLOWING CAREFULLY Remove any plastic from trim parts before turning the fireplace ON. It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process. Please ensure that your room is well ventilated - open all windows. It is recommended that you burn your fireplace for at least ten (10) hours the first time you use it. If the optional fan kit has been installed, place the fan switch in the “OFF” position during this time.

Proposition 65 Warning: Fuels used in gas, wood- burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth de- fects and other reproductive harm. California Health & Safety Code Sec. 25249.6

Locating Your Fireplace

B

Y

A A

Y

Y

Z

LU584-2

Fig. 1 Locating your gas fireplace

A Wall Location (Fig. 1) Y (Minimum distance between a glass panel and a parallel wall) = 3’ (914mm) Z (Minimum distance between edge of a glass panel and an adjacent wall) = 3” (76mm) B Island Location (Fig. 1) X (Maximum length of horizontal venting) = 20’ (6.1m)

Refer to the venting section in this manual for specific dimen- sions.

10006326

Page 3 of the Vermont Casting 360DVSR user manual — Installation & Operating Instructions
Page 3 · click to enlarge
Page 3
Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 3)
Fig. 1 · Installation & Operating Instructions

Fig. 2a Fireplace specifications—360DVS2

Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 3)
Fig. 2 · Installation & Operating Instructions
Appliance Dimensions Ref.Rear Vent ConfigurationTop Vent Configuration A38¹⁄₈” (968 mm)38¹⁄₈” (968 mm) B43¹⁄₄” (1099 mm)43¹⁄₄” (1099 mm) C24” (610 mm)24” (610 mm) D24” (610 mm)24” (610 mm) E37³⁄₈” (949 mm)37³⁄₈” (949 mm) F35⁷⁄₈” (911 mm)35⁷⁄₈” (911 mm) G30¹⁄₂” (775 mm)7” (178 mm) H12” (305 mm)12” (305 mm) I3¹⁄₈” (80 mm)3¹⁄₈” (80 mm) J2³⁄₄” (70 mm)2³⁄₄” (70 mm) K1¹⁄₄” (33 mm)1¹⁄₄” (33 mm)

10006326

Page 4 of the Vermont Casting 360DVSR user manual — Installation & Operating Instructions
Page 4 · click to enlarge
Page 4
Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 4)
Fig. 3 · Installation & Operating Instructions

Fig. 2b Fireplace specifications—360DVS3/ 360DDVSL/ 360DVSR

Appliance Dimensions Ref.Rear Vent ConfigurationTop Vent Configuration A38¹⁄₈” (968 mm)38¹⁄₈” (968 mm) B40⁵⁄₈” (1032 mm)40⁵⁄₈” (1032 mm) C24” (610 mm)24” (610 mm) D24” (610 mm)24” (610 mm) E37³⁄₈” (949 mm)37³⁄₈” (949 mm) F35⁷⁄₈” (911 mm)35⁷⁄₈” (911 mm) G30¹⁄₂” (775 mm)7” (178 mm) H12” (305 mm)12” (305 mm) I3¹⁄₈” (80 mm)3¹⁄₈” (80 mm) J2³⁄₄” (70 mm)2³⁄₄” (70 mm) K1¹⁄₄” (33 mm)1¹⁄₄” (33 mm)
Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 4)
Fig. 4 · Installation & Operating Instructions

10006326

Page 5 of the Vermont Casting 360DVSR user manual — Installation & Operating Instructions
Page 5 · click to enlarge
Page 5
Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 5)
Fig. 5 · Installation & Operating Instructions

Fig. 3a Fireplace framing dimensions—360DVS2

Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 5)
Fig. 6 · Installation & Operating Instructions
Framing Dimensions Ref.Rear Vent ConfigurationTop Vent Configuration ROD24” (610 mm) minus two times finishing material thickness to be even with face of unit. ROH38⁵⁄₈” (981 mm)Not to be framed until unit is set in place, due to 3¹⁄₈” (79 mm) allowance for flue collar ROWNot to be framed until unit is set in place due to 3¹⁄₈” (79 mm) allowance for flue collar43³⁄₄” (1111 mm)

10006326

Page 6 of the Vermont Casting 360DVSR user manual — Installation & Operating Instructions
Page 6 · click to enlarge
Page 6
Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 6)
Fig. 7 · Installation & Operating Instructions

Fig. 3b Fireplace framing dimensions—360DVS3/ 360DVSL/ 360DVSR

Vermont Casting 360DVSR — Installation & Operating Instructions diagram (page 6)
Fig. 8 · Installation & Operating Instructions
Framing Dimensions Ref.Rear Vent ConfigurationTop Vent Configuration Model360DVS3360DVSL/R360DVS3360DVSL/R ROD(See Note 1)(See Note 2)(See Note 1)( See Note 2) ROH38⁵⁄₈” (981 mm)Not to be framed until unit is set in place, due to 3¹⁄₈” (79 mm) allowance for flue collar ROW40⁵⁄₈” (1032 mm) minus one time (1x) finishing material thickness to be even with face of unit.

10006326

Page 7 of the Vermont Casting 360DVSR user manual — Hearth
Page 7 · click to enlarge
Page 7

Clearance to Combustibles

Appliance Top 0” (0 mm) to standoff Bottom 0” (0 mm) Vent End 1/2” (13 mm) to rear panel Nonvent End (DVS2) 0” (0 mm) Venting Concentric sections of DV Vent: Top, bottom & sides 1” (25 mm) Nonconcentric sections of DV Vent: Side and bottom 1” (25 mm) Top 2” (51 mm)

J

F G H I

CFM197

Mantels

K

M

Side of Combustion Chamber

N

The height at which a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if so fitted) and the fireplace. For correct mounting height and width, refer to Fig. 4a and 4b and the Mantel Chart below.

O

The fitting of a bay window trim kit does not affect the distances and reference points referred to in the dia- gram and chart.

Noncombustible mantels and legs may be installed at any height and width around the appliance.

CFM170

When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent dis- coloration.

Mantel Mantel Leg From Side Ref. Leg Depth Ref. of Comb. Opening F 10” (254 mm) K 11¹⁄₂” (292 mm) G 8” (203 mm) L 9¹⁄₂” (241 mm) H 6” (152 mm) M 7¹⁄₂” (191 mm) I 4” (102 mm) N 5¹⁄₂” (140 mm) J 2” (51 mm) O 3¹⁄₂” (89 mm)

V W X Y Z A B C D E Fireplace Louvre Assembly Top Top of Combustion Chamber Bottom of Door Trim CFM146 Mantel Chart Ref.Mantel Shelf or Breast PlateRef.Mantel from Top of Comb. Chamber V10” (254 mm)A19” (483 mm) W8” (203 mm)B17” (432 mm) X6” (152 mm)C15” (381 mm) Y4” (102 mm)D13” (330 mm) Z2” (51 mm)E11” (297 mm)

Fig. 4b Combustible mantel leg minimum installation.

Hearth

A hearth is not mandatory; however, for aesthetic purposes, we recommend installing a noncombustible hearth that projects out 12” (305mm) or more from the front of the fireplace.

Cold climate installation recommendation:

When installing this unit against a noninsu- lated exterior wall or chase, it is mandatory the outer walls be insulated to conform to applicable insulation codes.

Fig. 4a Combustible mantel minimum installation.

Show 5 more labels / short text on this page
Top View · Mantel Leg · Front View · Mantel Leg · 10006326
Page 8 of the Vermont Casting 360DVSR user manual — Final Finishing
Page 8 · click to enlarge
Page 8
Gas Inlet & Manifold Pressures NaturalLP (Propane) Inlet Minimum4.5” w.c.11.0” w.c. Inlet Maximum14.0” w.c.14.0” w.c. Manifold Pressure3.5” w.c.10.0” w.c.

Framing & Finishing

1. Choose the unit location. 2. Place the unit into position and secure it to the floor with 1¹⁄₂” (38mm) screws or nails. Holes to secure the unit to the floor are located behind the access door grille on the left and right sides of the unit. 3. Frame in the fireplace with a header across the top. It is important to allow for the finished wall face when setting the depth of the frame. 4. Drywall (sheetrock) or wood material may be placed with a zero clearance to the top edges of the appli- ance when finishing walls above sides of the appli- ance with glass windows. NOTE: Attach wall finish- ing to constructed frame, not the appliance. 5. On 360DVSL and 360DVSR, drywall, wood, or wood molding may be placed with zero clearance to the rear wall of the unit, along the vertical edge formed by the standoffs, to intersection of the rear wall, to the side wall having the small glass window. NOTE: Attach wall finishing to constructed frame, not the appliance.

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370 m) above sea level.

For elevations above 4,500 feet (1,370 m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations above 4,500 feet (1,370 m).

360DVS2/ 360DVS3/ 360DVSL/ 360DVSR CERTIFIED TO

ANSI Z21.88-2005 / CSA 2.33-2005

Vented Gas Fireplace Heaters

Final Finishing

Gas Line Installation

Noncombustible materials such as brick or tile may be extended over the edges of the face of the appliance. DO NOT cover any vent or grille panels.

When purging the gas lines, the window frame assembly must be removed.

If a Trim Kit is going to be installed on the fireplace, the brick or tile will have to be installed flush with the edges of the appliance.

The gas pipeline can be brought in through the vent end of the fireplace as well as the bottom. Knockouts (to allow gas pipe installation and testing any gas con- nection) are provided on the bottom behind the valve. It is most convenient to bring the gas line in from the vent end of the valve, as this allows fan installation or removal without disconnecting the gas line.

Gas Specifications ModelFuelGas ControlMax. Input BTU/hMax. Input BTU/h 360DVS2RNNatMillivolt38,00026,600 360DVS2RPPropMillivolt38,00028,500 360DVS2ENNat24V Hi/Lo38,00026,600 360DVS2EPProp24V Hi/Lo38,00028,500 360DVS3RNNatMillivolt38,00026,600 360DVS3RPPropMillivolt38,00028,500 360DVS3ENNat24V Hi/Lo38,00026,600 360DVS3EPProp24V Hi/Lo38,00028,500 360DVSLRNNatMillivolt38,00026,600 360DVSLRPPropMillivolt38,00028,500 360DVSLENNat24V Hi/Lo38,00026,600 360DVSLEPProp24V Hi/Lo38,00028,500 360DVSRRNNatMillivolt38,00026,600 360DVSRRPPropMillivolt38,00028,500 360DVSRENNat24V Hi/Lo38,00026,600 360DVSREPProp24V Hi/Lo38,00028,500

The gas line connection can be made with properly tinned 3/8” copper tubing, 3/8” rigid pipe, or an ap- proved flex connector. Since some municipalities have additional local codes, it is always best to consult your local authority and the CSA-B149.1 installation codes.

For USA installations, consult the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.

Always check for gas leaks with a mild soap and water solution. Do not use an open flame for leak testing.

Vermont Casting 360DVSR — Final Finishing diagram (page 8)
Fig. 9 · Final Finishing

1/2” Gas Supply 1/2” NPT X 1/2” Flare Shut-Off Valve

Fig. 5 Gas shutoff valve and flex connector.

10006326

Page 9 of the Vermont Casting 360DVSR user manual — Alternate Switch Location
Page 9 · click to enlarge
Page 9

The gas control is equipped with a captured-screw type pressure test point, therefore it is not necessary to pro- vide a 1/8” test point upstream of the control. When using copper or flex connector, use only ap- proved fittings. Always provide a union when using black iron pipe so that the gas line can be easily discon- nected for burner or fan servicing. Refer to the gas specification for pressure details and ratings.

Isolate or disconnect this or any other gas appliance control from the gas line when pressure testing.

DO NOT subject the fireplace valve to test pressures exceeding 1/2 psi.

EB-1 Electrical box Depend- ing on the specific model, this box may be installed on either side of the appliance. FP1428

EB-1 Electrical Junction Box Connection

Fig. 6 EB-1 attachment.

The fireplace, when installed, must be electrically connected and grounded in ac- cordance with local codes; in the absence of local codes, use the current CSA C22.1

Remote ON/OFF Switch Installation

Do not wire the remote ON/OFF wall switch for this gas appliance into a 120V power supply.

Canadian Electrical Code.

For USA installations, follow the local codes and National Electrical Code ANSI/ NFPA No. 70.

1. Thread the wiring through the holes on the end panels of the appliance. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box. 2. Attach the wire to the ON/OFF switch and install the switch into the receptacle box. 3. Connect the other ends of the wire to the gas control valve, as shown in Figure 7.

It is strongly suggested the wiring of the EB-1 Electrical Junction Box be carried out by a licensed electrician.

Ensure power to the supply line has been disconnected before commencing with this procedure.

The EB-1 electrical junction box has been supplied standard on this model to allow for easy connection of the optional fan kits. (Fig. 6)

To connect the EB-1 box to the house electrical supply follow the steps below.

1. Remove the front cover of the EB-1 box. 2. Remove the plug socket assembly from the EB-1 box. 3. Feed the supply line in from the out through the elec- trical knockout. 4. Connect the ground wire of the supply line to the green screw of the socket assembly. 5. Connect the white wire of the power line to the chrome screw of the socket assembly. 6. Connect the black wire of the power supply line to the brass screw (polarized) of the socket assembly. 7. Refit the socket assembly back into the electrical box and replace the cover plate. 8. The EB-1 electrical junction box is now ready to sup- ply power to the FK12 or FK24 fan kit, if used.

TP TH

TP

TH

Fig. 7 Remote switch wiring diagram for R models.

Alternate Switch Location

The remote switch can be installed on the front or the side of the access door. Simply mount the switch to the bracket provided and screw the bracket to either side of the frame, lining up the screws with the prepunched holes. (Fig. 8)

Show 5 more labels / short text on this page
Electrical Inlet Hole · Gas Inlet Hole · Remote ON/OFF Switch · Gas Control Valve · 10006326
Page 10 of the Vermont Casting 360DVSR user manual — Optional Top Vent Application
Page 10 · click to enlarge
Page 10

Fig. 8 Alternate switch location.

Optional Top Vent Application

This appliance is shipped as a rear vent unit. If the installation layout requires the unit to be a top vent con- figuration, the appliance can be converted by following the steps below.

Fig. 9 Remove screws from outer collar adapter.

Insulation Pad (Must be removed) Flue PipeFP1432 10Remove flue cover and pipe. FP1433Flue Cover Plate Flue Pipe

When removing and refitting the plates and adapter, be sure the associated gasket is undamaged and refitted as required.

1. Remove the ten (10) screws securing the outer col- lar adapter to the fireplace body. (Fig. 9) 2. Set the collar aside, complete with the gasket. NOTE: Do not damage the gasket, as the adapter and gasket must be refitted. 3. Remove the insulation material (exposed in Step 2) from the top of the unit. (Fig. 10) This material can be discarded; however, if the unit is converted back to rear-vent, a new piece of insulation material approved by CFM Corporation must be used for this purpose. NOTE: When converting appliance to top vent, ensure the insulation material referred to in step 3 is completely removed. 4. Remove the 4 screws securing the flue cover plate to the top of the intake box and remove the cover and gasket. (Fig. 11) 5. Remove 4 screws securing the flue pipe to back of the intake box and remove pipe and gasket. (Fig. 11) 6. Secure the plate and gasket removed in step 4 over the flue opening in the back of the intake box. En- sure the gasket is in place and undamaged. 7. Install the flue pipe and gasket removed in step 5 over the flue opening in the top of the intake box. 8. Refit the outer collar adapter and gasket to the unit with the round collar on the top. Secure the adapter with the 10 screws removed in step 1.

Fig. 11 Flue pipe removal.

Show 4 more labels / short text on this page
Remove These Screws · Remove These Screws · Outer Collar Adapter · 10006326
Page 11 of the Vermont Casting 360DVSR user manual — General Venting
Page 11 · click to enlarge
Page 11

Electronic Gas Control Valve

This appliance may be fitted with a Honeywell ignition module.

Installation of the remote ON/OFF starter switch on electronic ignition units (Fig. 12):

1. Thread the wiring through the holes on the side panels of the appliance. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box. 2. Attach the wire to the ON/OFF switch and install the switch into the receptacle box. 3. Connect the white wire from the wall switch to the black wire from the transformer, using an approved wire nut. Connect the black wire from the wall switch to the black wire running from the #6 position of the ignition module, also using an approved wire nut.

PILOT

HONEYWELL IGNITION MODULE

MV MV/VP PV GRD 24V SENSE SPARK

56 89 GREEN

RED

ORANGE

ORANGE

LO

HI

NOVA SIT 822 VALVE

BLUE

WHITE

POWER CORD W/FEMALE SPADE

120 VAC RTN

24 VAC HOT

BLACK

WHITE

BLACK

OFF

WHITE

BLACK

YELLOW

GREEN

24 VAC RET

120 VAC HOT

40VA TRANSFORMER

WALL SWITCH

BLACK WHITE

Fig. 12 Honeywell ignition module.

General Venting

garden shed, fencing, deck or utility building within 24” (610mm) from the front of the termination hood.

Your fireplace is approved to be vented either through the side wall, or vertically through the roof.

Do not locate the termination hood where excessive snow or ice buildup may occur. Be sure to check the vent termination area after snow falls; clear it to prevent accidental blockage of the venting system. When using a snow blower, make sure snow is not directed toward the vent termination area. Location of Vent Termination

  • Only CFM Corporation venting components, specifically approved and labeled for this fireplace, may be used.
  • Venting terminals shall not be recessed into a wall or siding.
  • Horizontal venting must be installed on a level plane without an inclining or declining slope.

It is imperative the vent termination be located observ- ing minimum clearances as shown on the following page.

There must not be any obstruction such as bushes,

10006326

Page 12 of the Vermont Casting 360DVSR user manual — Electronic Gas Control Valve
Page 12 · click to enlarge
Page 12
General Venting Information - Termination Location INSIDE CORNER DETAIL G V D A H N N E V B C B V L V Fixed B V Closed V Fixed Operable Closed G Operable F V V B B B V J X M G A I V K X V A V VENT TERMINATION X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED CFM145a Canadian Installations1 US Installations2 A = Clearance above grade, veranda, porch, deck, or balcony12” (30cm)12” (30cm) B = Clearance to window or door that may be opened6” (15cm) for appliances < 10,000Btuh (3kW), 12” (30cm) for appliances > 10,000 Btuh (3kW) and < 100,000 Btuh (30kW), 36” (91cm) for appliances > 100,000 Btuh (30kW)6” (15cm) for appliances < 10,000 Btuh (3kW), 9” (23cm) for appliances > 10,000 Btuh (3kW) and < 50,000 Btuh (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW) C = Clearance to permanently closed window12” (305mm) recommended to prevent window condensation12” (305mm) recommended to prevent window condensation D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2’ (610mm) from the center line of the terminal18” (458mm)18” (458mm) E = Clearance to unventilated soffit12” (305mm)12” (305mm) F = Clearance to outside cornersee next pagesee next page G = Clearance to inside corner (see next page)see next pagesee next page H = Clearance to each inside of center line extended above meter/regulator assembly3’ (91cm) within a height of 15’ (5m) above the meter/regulator assembly3’ (91cm) within a height of 15’ (5m) above the meter/regulator assy I = Clearance to service regulator vent outlet3’ (91cm)3’ (91cm) J = Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliances6” (15cm) for appliances < 10,000 Btuh (3kW), 12” (30cm) for appliances > 10,000 Btuh (3kW) and < 100,000 Btuh (30kW), 36” (91cm) for appliances > 100,000 Btuh (30kW)6” (15cm) for appliances < 10,000 Btuh (3kW), 9” (23cm) for appliances > 10,000 Btuh (3kW) and < 50,000 Btuh (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW) K = Clearance to a mechanical air supply inlet6’ (1.83m)3’ (91cm) above if within 10 feet (3m) horizontally L = Clearance above paved sidewalk or paved driveway located on public property7’ (2.13m)†7’ (2.13m)† M = Clearance under veranda, porch, deck or balcony12” (30cm)‡12” (30cm)‡ N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18” (450mm). 1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes † A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings ‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor: NOTE: 1. Local codes or regulations may require different clearances. 2. The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and approved by the listing agency.

Fig. 13 Vent termination clearances.

10006326

Page 13 of the Vermont Casting 360DVSR user manual — Twist Lock Pipes
Page 13 · click to enlarge
Page 13
Vermont Casting 360DVSR — General Information Assembling Vent Pipes diagram (page 13)
Fig. 10 · General Information Assembling Vent Pipes

Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors.

C = Maximum depth of 48" (1219mm) for recessed location. D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)

E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)

Fig. 14 Termination clearances.

General Information Assembling Vent Pipes

Canadian Installations: Venting system must be installed in accordance with the current CSA-B149.1 installation code. USA Installations:

To join the twist lock pipes together, align the beads of the male end with the grooves of the female end. While bringing the pipes together, twist the pipe until the flange on the female end contacts the external flange on the male end. It is recommended that you secure the joints with three (3) sheet metal screws; however, this is not mandatory with twist lock pipe.

The venting system must conform with local codes and/ or current National Fuel Gas Code ANSI Z223.1/NFPA 54.

Only venting components manufactured by CFM Corpo- ration can be used in Direct Vent systems.

Twist Lock Pipes

Vermont Casting 360DVSR — Twist Lock Pipes diagram (page 13)
Fig. 11 · Twist Lock Pipes

When using twist-lock pipe, it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high-temperature silicone sealant are the collars on the fireplace and ter- mination, and sliding joints of telescopic vent sections used in the system.

Fig. 15 Twist lock pipe joints.

10006326

Page 14 of the Vermont Casting 360DVSR user manual — Rear Wall Installation
Page 14 · click to enlarge
Page 14

How to Use the Vent Graph

Rear Wall Application

The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system.

  • When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.
  • Specific rear vent starter kits must be used in these applica tions (see ‘venting components’). The appliance has been approved for installation flat against a rear wall. (Fig. 17)
  • Maximum horizontal distance between the rear of the appliance and the outside face of the rear wall is 20” (508 mm). (Fig. 17)
  • Minimum clearances between any combustible material and the vent pipe sections are: Top ..............................................2” (51 mm) Sides ...........................................1” (25 mm) Bottom .........................................1” (25 mm)

1. Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph bellow, locate the point intersecting with slanted graph line. 2. From the point of this intersection, draw a vertical line to the bottom of the graph. 3. Select the indicated dimension, and position the fireplace in accordance with same. Example A: If vertical dimension from floor of the fireplace is 11’ (3.4 m), horizontal run to the face of outer wall must not exceed 14’ (4.3 m). Example B: If vertical dimension from floor of the unit is 7’ (2.14 m), horizontal run to the face of outer wall must not exceed 8¹⁄₂’ (2.6 m).

Max. 20” (508mm)

Vertical dimension from floor of the unit to center of the horizontal vent pipe

Fig. 17 Rear vent application.

Rear Wall Installation

Locate and cut vent opening in the rear wall.

Combustible walls: Cut a rectangular hole measuring 10³⁄₈” H x 9³⁄₈” W (265 x 240 mm) through the exterior wall and frame. Frame in the opening per Figure 18.

egA

Noncombustible walls: Cut a round hole measuring 7¹⁄₂” (190 mm) diameter through the exterior wall and frame. (Fig. 18) STEP 2

egB

For combustible walls: Measure wall thickness and cut zero clearance sleeve parts to proper length. Max. length is 12” (305 mm). Assemble sleeve to its maximum opening of 10³⁄₈” x 9³⁄₈” (265 x 240 mm), and attach to firestop with #8 sheetmetal screws (supplied). Install firestop assembly. (Fig. 19)

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Horizontal dimension from outside of the wall

to the center of the fireplace vent flange Sidewall vent graph showing the relationship between vertical and

horizontal dimensions for a Direct Vent flue system.

Fig. 16 Sidewall vent graph.

Step 1 · DV Graph · 10006326

Page 15 of the Vermont Casting 360DVSR user manual — STEP 3
Page 15 · click to enlarge
Page 15

STEP 5

Vermont Casting 360DVSR — STEP 5 diagram (page 15)
Fig. 12

Guide vent through the vent hole as you place the appli- ance in its installed position. Guide the 4” (102 mm) and 7” (178 mm) collars of the vent termina- tion into the outer ends of the venting.

Do not force the termination. If the vent pipes do not align with the termination, remove and realign the vent- ing at the appliance flue collars.

Attach the termination to the wall as outlined in the instruction sheet supplied with the termination.

Vertical Sidewall Application

  • It is very important the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations concerning vent configurations must be strictly adhered to.
  • The vent graph (Fig. 16), showing relationship between vertical and horizontal side wall venting, will help determine allowable dimensions.
  • Minimum clearance between vent pipes and combustible materials is 1” (25 mm) on top, bottom, and sides, unless otherwise noted.
  • When the vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must flush up with the siding.
  • It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length. The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

Fig. 19 Adjustable zero clearance sleeve.

STEP 3

Measure the horizontal length requirement for the vent- ing including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51 mm), or the distance required if installing a second 90˚ elbow. (Fig. 20) STEP 4

Vermont Casting 360DVSR — STEP 3 diagram (page 15)
Fig. 13

Install the 4” (102 mm) vent to the appliance collar and secure with three (3) sheetmetal screws. Install the 7” (178 mm) vent pipe to the appliance collar and secure with three (3) sheetmetal screws. It is not neces- sary to seal this connection.

It is critical there be no downward slope away from the appliance when connecting the vent or elbow.

Fig. 20 Maximum three (3) 90° elbows per installation.

10006326

Page 16 of the Vermont Casting 360DVSR user manual — Vertical Side Wall Installation
Page 16 · click to enlarge
Page 16
  • Horizontal plane means no vertical rise exists on this portion of the vent assembly.
  • The maximum number of 90˚ elbows per side wall installation is three (3).
  • If a 90˚ elbow is fitted directly on top of the fireplace flange, the maximum horizontal vent run before the termination or a vertical rise is 36” (914mm).
  • The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.
  • For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (45 cm). This does not apply if 45° elbows are installed on the vertical part of the vent system.
  • The maximum number of elbow degrees in a system is 270°. Example shown in Figure 23:

Max. 20” (508mm)

Max. 36” (914mm)

Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total angular variation = 270°

1 + 2 + 3 + 4 = 270°

Fig. 21 Maximum horizontal run w/no rise.

  • If a 90° elbow is used in the horizontal vent run (level height maintained), the maximum horizontal vent length is reduced by 36” (914 mm). (Fig. 21) This does not apply if the 90° elbows are used to increase or redirect a vertical rise. Example: According to the vent graph (Fig. 16), the maximum horizontal vent length in a system with a 7 ¹⁄₂ ” (191mm) vertical rise is 20 ft. (6.1m), but if a 90° is required in the horizontal vent, it must be reduced to 17 ft. (5.2m). NOTE: The sum of Dim. A and Dim. B must not be greater than 17 ft. (5.2m). (Fig. 22)

FP1438 Fig. 23 Maximum elbow usage.

Vertical Side Wall Installation

STEP 1

Vermont Casting 360DVSR — Vertical Side Wall Installation diagram (page 16)
Fig. 14 · Vertical Side Wall Installation

Locate and cut vent opening in the side wall. It may be necessary to first position the fireplace and measure to obtain the hole location. Depending on whether the wall is combustible or noncombustible, cut the opening to size per Figure 24.

Combustible walls: Cut a rectangular hole measuring 9³⁄₈” H x 9³⁄₈” W (240 x 240mm) through the exterior wall and frame. Frame in the opening per Figure 24.

Noncombustible walls: Cut a round hole measuring 7¹⁄₂” (190 mm) diameter through the exterior wall and frame. (Fig. 24) STEP 2

For combustible walls: Measure wall thickness and cut zero clearance sleeve parts to proper length. Max. length is 12” (305mm). Assemble the sleeve and attach it to the firestop with #8 sheet metal screws (supplied). Install the firestop assembly. (Fig. 25)

Zero clearance sleeve is required only for combustible walls.

Fig. 22 Horizontal run reduction.

10006326

Page 17 of the Vermont Casting 360DVSR user manual — STEP 6
Page 17 · click to enlarge
Page 17
Vermont Casting 360DVSR — STEP 4 diagram (page 17)
Fig. 15

STEP 4

Apply a bead of silicone to the inner and outer flue collars of the fireplace and using appropriate length of pipe section(s) attach to fireplace with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints as described in “Connecting Vent Pipes” section. STEP 5

Measure the horizontal length requirement including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51 mm) (or the distance required if installing a second 90° elbow. (Fig. 27)

Vermont Casting 360DVSR — STEP 4 diagram (page 17)
Fig. 16

Fig. 25 Adjustable zero clearance sleeve.

STEP 3

Place fireplace into position. (Fig. 26) Measure the verti- cal height (X) required from the base of the flue collars to the center of the wall opening.

Fig. 27 Horizontal length requirement.

Vermont Casting 360DVSR — STEP 3 diagram (page 17)
Fig. 17

STEP 6

Use appropriate length of pipe section—telescopic or fixed—and install. The 20” (508 mm) section of pipe which goes through the wall is packaged with the 7DVSK starter kit, and can be cut to suit if necessary.

Seal vent pipe and firestop gaps with high temperature sealant to restrict cold air being drawn in around the fireplace. STEP 7

Apply high temperature sealant to 4” (102 mm) and 7” (178 mm) collars, or to the termination 1” (25 mm) away from the crimped end. Guide 4” and 7” collars of vent terminations into respective vent pipes. Double check vent pipes to see that they overlap the collars by

Fig. 26 Vertical height requirement.

10006326

Page 18 of the Vermont Casting 360DVSR user manual — Below Grade Installation
Page 18 · click to enlarge
Page 18

2” (51 mm). Secure termination to the wall with screws provided, and caulk around the wall plate to weather- proof.

Zero Clearance Sleeve (if required)

One alternative to screwing the termination directly to the wallis the use of expanding plugs or an approved exterior construction adhesive.

Min. 4” (102mm) Clearance

Or, you may attach the termination with screws through the inner body into the 4” (102 mm) vent pipe; however, for this method, you must extend the 4” (102mm) pipe approximately 6” (153 mm) beyond the outer face of the wall.

  • A minimum of 24” (610mm) vertical pipe must be installed when using the 7TDVSNORK Kit.
  • The 22” (559mm) vertical rise (center to center) of the snorkel may be included for calculation of maximum horizontal run. FP1442 Fig. 28 Below grade installation.

Support the horizontal pipes with metal pipe straps every 36” (914mm).

Below Grade Installation

When it is not possible to meet required vent terminal clearances of 12” (305 mm) above grade level, we rec- ommend using a starter kit. It allows installation depth down to 7” (178 mm) below grade level. Measure 7” (178 mm) from the center of the horizontal vent pipe as it penetrates through the wall.

Do not backfill around the snorkel. A clear- ance of at least 4” (102mm) must be main- tained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fas- ten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2 sheetmetal screws. It will be necessary to extend vent pipes out as far as protruding wall face. (Fig. 29)

If installing a snorkel, a minimum 24” (610 mm) vertical rise is necessary. The maximum horizontal run with 24” (610 mm) vertical pipe is 36” (914mm). The measurement is taken from the collar of the fireplace (or transition elbow) to the face of exterior wall. See sidewall vent graph, Page 15, for extended horizontal runs if the vertical exceeds 24” (610 mm).

Vermont Casting 360DVSR — Below Grade Installation diagram (page 18)
Fig. 18 · Below Grade Installation

1. Establish vent hole through the wall. (Fig. 24) 2. Remove soil to depth of about 16” (406 mm) below base of snorkel. Install window well (not supplied). Refill hole with 12” (305 mm) of coarse gravel, leav- ing a clearance of about 4” (102 mm) below snorkel. (Fig. 28) 3. Install vent system. 4. Ensure a watertight seal is made around the vent pipe coming through the wall. 5. Apply high-temperature sealant caulking (supplied) around 4 in. and 7 in. snorkel collars. 6. Slide snorkel into vent pipes and secure to wall. 7. Level the soil so as to maintain a 4” (102 mm) clear- ance below snorkel. (Fig. 29)

Fig. 29 Snorkel installation / recessed foundation.

Show 11 more labels / short text on this page
7TDVSNORK (Snorkel) · Firestop · Screws · 7” Pipe · (Ground) · Window Well · 24” (610mm) Minimum · Gravel · Drain · Foundation Wall · 10006326
Page 19 of the Vermont Casting 360DVSR user manual — Vertical Through-the-Roof Application
Page 19 · click to enlarge
Page 19
Vermont Casting 360DVSR — Vertical Through-the-Roof Application diagram (page 19)
Fig. 19 · Vertical Through-the-Roof Application

Vertical Through-the-Roof Application

This Gas Fireplace has been approved for: • Vertical installations up to 40’ (12 m) in height. Up to a 10’ (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. (Fig. 30)

1 + 2 + 3 + 4 = 270°

Vermont Casting 360DVSR — Vertical Through-the-Roof Application diagram (page 19)
Fig. 20 · Vertical Through-the-Roof Application

FP1444 Fig. 31 Maximum elbow usage.

Vermont Casting 360DVSR — Vertical Through-the-Roof Application diagram (page 19)
Fig. 21 · Vertical Through-the-Roof Application
  • FP1443 Fig. 30 Support straps for horizontal runs.
  • Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal level the maximum horizontal length must be reduced by 18” (457 mm). Example: Maximum horizontal length: Zero elbows = 10’ (3 m) 1 x 45° elbows = 8 ¹⁄₂ ’ (2.6 m) 2 x 45° elbows = 7’ (2.1 m)
  • A minimum of an 8 ft. (2.43 m) vertical rise.
  • Two (2) sets of 45° elbow offsets may be used within the vertical sections. From zero to max 8 ft. (2.43 m) vent pipe can be used between elbows. (Fig. 30)
  • 7DVCS supports offsets. (Fig. 33) This application will require you first determine the roof pitch and use the appropriate starter kit. See Venting Components List, Page 22.
  • The maximum angular variation allowed in the system is 270˚. (Fig. 31)
  • The minimum height of the vent above the highest point of penetration through the roof is 2’ (610mm). (Fig. 32)

Fig. 32 Maximum termination to roof clearance.

10006326

Page 20 of the Vermont Casting 360DVSR user manual — Vertical Through-the-Roof Installation
Page 20 · click to enlarge
Page 20

If there is a room above ceiling level, a firestop spacer must be installed on both the bottom and the top sides of the ceiling joists. (Fig. 35) If an attic is above ceiling level, a 7DVAIS (Attic Insulation Shield) must be installed.

Vertical Through-the-Roof Installation

1. Locate your fireplace. 2. Plumb to center of the (4”) flue collar from ceiling above and mark position. 3. Cut an opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240mm). 4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1” (25 mm) clearance to the vent pipe, i.e., the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240mm). 5. Place fireplace into position. 6. Place firestop(s) #7DVFS or Attic Insulation Shield #7DVAIS into position and secure. (Fig. 35) 7. Install roof support (Fig. 33) and roof flashing making sure upper flange is below the shingles. (Fig. 34) 8. Install appropriate pipe sections until the venting is above the flashing. (Fig. 34) 9. Install storm collar and seal around the pipe. 10. Add additional vent lengths for proper height. (Fig. 32) 11. Apply high temperature sealant to 4” and 7” collars of vertical vent termination and install.

Vermont Casting 360DVSR — Vertical Through-the-Roof Installation diagram (page 20)
Fig. 22 · Vertical Through-the-Roof Installation
Vermont Casting 360DVSR — Vertical Through-the-Roof Installation diagram (page 20)
Fig. 23 · Vertical Through-the-Roof Installation

Fig. 35 Firestop and attic insulation shield.

Fig. 33 Chimney support.

Vermont Casting 360DVSR — Vertical Through-the-Roof Installation diagram (page 20)
Fig. 24 · Vertical Through-the-Roof Installation

Fig. 34 Roof flashing.

10006326

Page 21 of the Vermont Casting 360DVSR user manual — Twist Lock Venting Components
Page 21 · click to enlarge
Page 21

Twist Lock Venting Components

7TDVRVT Through-the-Wall Rear Vent Termination

Starter Kit Model 7TDVSK - Sidewall Starter Kit Model 7TDVSKV - Vertical Venting for 7TDVSKV-A: order 1/12 to 6/12 roof pitch for 7TDVSKV-B: order 7/12 to 12/12 roof pitch for 7TDVSKV-F: order flat roof Starter Kit Model 7TDVSKS - Snorkel Kit Snorkel Termination - 7TDVSNORK for Below Grade Installation

45˚ Elbow 7TDVT45 for Rear Vent to Vertical Vent or Vertical/Horizontal Offsets 90˚ Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90° Elbow 7TDV90 Vertical/Horizontal Offset

Telescopic Vent Sections7TDVP1218 - 12” to 18” adjustable length 7TDVP3564 - 35” to 64” adjustable length

Pipe Sections for vertical or horizontal venting: Model 7TDVP8” 4 per box Model 7TDVP12” 4 per box Model 7TDVP24” 4 per box Model 7TDVP36” Model 7TDVP48”

Firestop Spacer Model 7DVFS

Attic Insulation Shield Model 7DVAIS

Vertical/ Horizontal Combination Offset Support Model 7DVCS

10006326

Page 22 of the Vermont Casting 360DVSR user manual — Window Frame Assembly Removal
Page 22 · click to enlarge
Page 22

Operating Instructions

Glass Information

7. To reinstall the window frame assembly reverse this procedure. Front Window Frame Assembly 1. Remove the top and bottom louvre assembly. 2. Remove the lower window trim (held in place with magnets). 3. Remove both lower retaining screws. Access to these screws is gained through the holes along the lower edge of the frame behind the trim. (Fig. 38) 4. Tilt lower edge of frame out slightly and lift window frame assembly up and away from the fireplace. 5. To reinstall the window frame assembly reverse the process.

Only glass approved by CFM Corporation should be used on this fireplace.

  • The use of any non-approved replacement glass will void all product warranties.
  • Care must be taken to avoid breakage of the glass.
  • Do not operate appliance with glass front removed, cracked or broken.
  • Replacement glass (complete with gasket) is available through your Majestic Fireplaces dealer and should only be installed by a licensed qualified service person.

Louvre Removal

  • The top side and top end louvres are removed by simply lifting the louvre assembly and pulling the assembly away from the fireplace. (Fig. 36)
  • The lower side louvres are hinged along there lower edge and are folded down for access to components in the base cavity of the fireplace.
  • The lower end louvre assembly on the 360DVS3/ SL/ SR units is removed in the same manner as the top louvre assemblies.

Pull Clamp Hook Push Clamp Han-

Fig. 37 Window frame assembly removal.

Fig. 36 Remove louvre assembly top.

Window Frame Assembly Removal

Side Window Frame Assemblies 1. Shut off the gas supply. 2. Allow the fireplace to cool if it has been in operation. 3. Remove the top louvre assembly. 4. Lower the bottom louvre assembly. 5. Release the two clamps along lower edge of the frame by pulling down on clamp handles. (Fig. 37) 6. Tilt lower edge of frame out slightly and lift window frame assembly up and away from the fireplace.

Location of Lower Retaining Screws

Fig. 38 Retaining screw.

Show 6 more labels / short text on this page
Lower Clamps · Window Frame Assembly · Window Frame Assembly · Louvre · Glass Panel FP1227 · 10006326
Page 23 of the Vermont Casting 360DVSR user manual — Ceramic Refractory Installation
Page 23 · click to enlarge
Page 23

Glass Cleaning

Log Installation

It is necessary to periodically clean glass. During start- up, condensation, which is normal, forms on the inside of the glass. This condensation causes lint, dust and other airborne particles to cling to glass surface.

Refer to Figures 40 and 41 for log location and align- ment.

Because of the log stack design, these instructions can be followed from either side of the fireplace. To follow these instructions, identify the logs by the number cast into the underside.

Also initial paint curing may deposit a slight film on the glass. It is therefore recommended glass be cleaned two or three times with a non-ammonia based house- hold cleaner and warm water. The use of fireplace glass cleaner is recommended within the first few weeks of operation.

For correct operation of the fireplace, the logs must be correctly placed in the sequence described below:

1. Unpack the logs from the shipping carton. The logs are fragile; handle them carefully.

After the initial cleaning process the glass should be cleaned two or three times during each operating sea- son depending on the environment in the house.

Handle and dispose of plastic bags in which logs were shipped in a safe manner. As with all plastics, they are not toys and should be kept away from infants. 2. Remove both sides of the window frame assembly (where applicable). 3. Place the log rear (B120) on the grate. The square hole located on the underside of the log is to be placed over the center of the grate. The inner end of the log ensures that the bottom hole is located on the pin of the support. 4. Place the log front left (B121) on the grate. The square hole located on the underside of the log is to place over the corner leg of the grate. The inner end of the log ensures the bottom holes are located on the pin of the support. 5. Place the log front right (B122). Once more, the square hole fits over the corner leg of the grate. The inner end of this log maintains a recess on the underside, which locates over the knob on the top of the log front left (B121) to secure the inner end in place. 6. Place the log rear left (B123). The bottom back of the log rests on the grate. The notch at the back of the log locates over the knob on the top of the log rear (B120). The bottom of the log rests on top of the log front left (B121). 7. Place the log bottom left (B124). The log maintains a step on the outer end, which rests against the prong of the grate. The alternate end rests on the side floor refractory panel. 8. Place the log rear right (B125). The log maintains a hole on the underside, which rests over the knob on the top of the log rear (B120). The bottom of the log rests against the side floor refractory panel, and the side rests against the last prong of the grate. 9. Place the log center (B126). The log maintains a hole on the underside, which rests over the knob on the top of the log front right (B122). The alternate end rests against the side floor refractory panel and positions between the two (2) prongs of the grate.

Clean the glass after the first two weeks of operation.

Do not clean the glass when hot.

Do not use an abrasive cleaner.

Do not strike or slam the glass.

Ceramic Refractory Installation

The vertical refractory panels are installed in the unit prior to shipment. For assembly procedures, refer to Figure 39.

1. Unpack the ceramic refractory panels from the carton.

Handle the refractory material carefully, the panels are fragile.

2. Place the two end floor refractory panels on the base of the fireplace. 3. Place both side panels along the side of the base. NOTE: 360DVS2 is the only 360DV unit that is fitted

with two (2) end vertical panels, as shown in Figure 39. 360DVSL and 360DVSR units are each fitted with one end vertical panel and two side vertical panel. The 360DVS3 has only one end vertical panel.

Vertical Panels in Place When Shipped

Floor Panels Placed During Installation

Fig. 39 Ceramic panel installation.

10006326

Page 24 of the Vermont Casting 360DVSR user manual — LO
Page 24 · click to enlarge
Page 24

B122

B120

B126 B125

Vermont Casting 360DVSR — B122 diagram (page 24)
Fig. 25

B123 B124

B121

LG320

Fig. 40 360DVS log placement.

B120 B121

B123

Vermont Casting 360DVSR — B120 B121 diagram (page 24)
Fig. 26

B122

B126 B125

LG321

Fig. 41 360DVS log placement.

Lava Rock and Ember Material Placement

Flame & Temperature Adjustment

Your log set contains Ember Material and two types of Lava Rocks. Set these materials in place after the logs have been installed. Ember Material (Pt. #51915)

For units equipped with ‘HI/LO’ valves the flame adjust- ment is accomplished by rotating the ‘HI/LO’ adjustment knob located near the center of the gas control valve. (Fig. 42 and Fig. 43)

Remove ember material from the bag and separate it into small pieces, then scatter it over burner tiles in a random fashion. Do not pack down ember material; leave it in a ‘fluffy’ state. Lava Rock (Pt. #10001454)

LO

HI

to decrease flame height

to increase flame height

Remove lav rock material from packaging and spread it over ceramic floor panels outside log stack. Do not place this lava rock material on burner tiles.

Fig. 42 Flame adjustment knob for Honeywell valve.

Show 8 more labels / short text on this page
Side of Fireplace · Venting Side · Side of Fireplace · Venting Side · RN/ RP Models · Turn counterclockwise · Turn clockwise · 10006326
Page 25 of the Vermont Casting 360DVSR user manual — LG323
Page 25 · click to enlarge
Page 25

H

3/8” - 1/2” (10 - 13mm)

to decrease flame height

to increase flame height

O

Fig. 43 Flame adjustment knob for SIT valve.

F584-703

Flame Characteristics

Fig. 45 Correct pilot flame appearance.

It is important to periodically perform a visual check of the pilot and burner flames. Compare them to the pictorials illustrated below. (Figs. 45 & 46) If the flame patterns appear abnormal, contact a qualified service provider for service and adjustment.

Vermont Casting 360DVSR — F584-703 diagram (page 25)
Fig. 27

LG322

Vermont Casting 360DVSR — LG322 diagram (page 25)
Fig. 28

LG323

Fig. 46 Correct log flame appearance.

Turn counterclockwise · Turn clockwise · 10006326

Page 26 of the Vermont Casting 360DVSR user manual — Cleaning the Standing Pilot Control S ystem
Page 26 · click to enlarge
Page 26

Maintenance

Burner and Burner Compartment

To obtain proper operation, it is imperative that the pilot and burner’s flame characteristics are steady, not lifting or floating.

It is important to keep the burner and the burner com- partment clean. At least once per year remove the logs and lava rock/ember material. Vacuum and wipe out the burner compartment. Remove and refit the logs per the instructions in this manual.

Typically, the top 3/8 – 1/2” (10 – 13 mm) of the thermo- pile should be engulfed in the pilot flame. (Page 26, Fig. 46)

Always handle the logs with care as they are fragile and may also be hot if the fire- place has been in use. FK24/FK12 Fan Assembly

To adjust pilot burner (to be done by a qualified service technician):

1. Remove pilot adjustment cap. 2. Adjust pilot screw to provide properly sized flame. 3. Replace pilot adjustment cap.

The fan unit requires periodic cleaning. At least once per month in the operating season, open the lower lou- vre panels and wipe or vacuum the area around the fan to remove any build up of dust or lint. Brass Trim

The primary air shutter is set at factory and should be adjusted, if necessary, only by a qualified service tech- nician.

Cleaning Electronic Ignition System

Clean the brass trim pieces using a soft cloth lightly dampened with lemon oil. Do not use water or house- hold cleaners on any brass components.

The Electronic Ignition burner/control system consists of:

Cleaning the Standing Pilot Control S ystem

  • main burner
  • gas orifice
  • pilot burner
  • 24VAC valve with transformer
  • The burner and control system consists of:
  • burner tube
  • gas orifice
  • pilot assembly
  • thermopile
  • millivolt gas valve

The process for taking care of Electronic Ignition units is identical to that for taking care of Standing Pilot models.

Most of these components may require only an occa- sional checkup and cleaning and some may require ad- justment. If repair is necessary, it should be performed by a qualified technician.

1. Turn off pilot light at gas valve side. 2. Let fireplace cool if it has been running. 3. Remove window frame assembly. (Refer to Window Frame Assembly Removal section) 4. Remove logs. 5. Vacuum burner compartment especially around orifice primary air openings. 6. Visually inspect pilot. Brush or blow away any dust or lint accumulation. 7. Reinstall logs. 8. Ignite pilot; refer to Lighting Instructions. 9. Reinstall window frame assembly.

10006326

Page 27 of the Vermont Casting 360DVSR user manual — B122
Page 27 · click to enlarge
Page 27
Vermont Casting 360DVSR — B122 diagram (page 27)
Fig. 29

CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. 360DVS Series

10006326

Page 28 of the Vermont Casting 360DVSR user manual — B122
Page 28 · click to enlarge
Page 28

360DVS Series (Items marked ‘*’ are not shown in the parts illustration) Ref. Description 360DVS2 360DVS3 360DVSL 360DVSR 1. Log Set (complete) 10006350 1a. Log - Rear (B120) 10006315 1b. Log - Front Left (B121) 10006316 1c. Log - Front Right (B122) 10006317 1d. Log - Rear Left (B123) 10006318 1e. Log - Bottom Left (B124) 10006319 1f. Log - Rear Right (B125) 10006320 1g. Log - Center Right (B126) 10006321 2. Grate Assembly 10006014 3a. Burner Housing Assembly, Nat. 10006148 3b. Burner Housing Assembly, Prop. 10006299 * Ceramic Burner Tile 10002165 * Orifice/s, Main burner (Nat.) Refer to the rating plate for specific orifice information * Orifice/s, Main Burner (Prop.) Refer to the rating plate for specific orifice information 4a. Pilot assembly PSE (Nat.) 10001741 4b. Pilot assembly PSE (Prop.) 10001742 5a. Pilot assembly SIT Top Conv. (Nat.) 10002264 5b. Pilot assembly SIT Top Conv. (Prop.) 10002265 6. Pilot, PSE (with cable & electrode) 10001824 7. Pilot SIT Top Convertible 10002266 8. Pilot Hood, SIT Top Convertible 10002385 * Orifice, Pilot PSE (Nat.) 10001822 * Orifice, Pilot PSE (Prop.) 10001823 * Orifice, Pilot SIT Top convertible (Nat.) 10002268 * Orifice, Pilot SIT Top conv. (Prop.) 10002269 * Pilot tube & fittings (Top convertible) 10001296 * Manifold tube & fittings 10002492 * Flexible Gas Line (18”) with fittings 20002500 9. Thermocouple, PSE 10001828 10. Thermocouple, SIT Top Convertible 53373 11. Thermopile 51827 12. Ignitor electrode (with cable), SIT 10001297 13. Ignitor (Piezo), SIT 820 valve 52464 14. Ignitor (Piezo), Honeywell Valve 20000062 15a. Valve, SIT 820 (Nat.) 52677 15b. Valve, SIT 820 (Prop.) 52678 16a. Valve, Honeywell (Nat.) 10001782 16b. Valve, Honeywell (Prop.) 10001759 17. Fan & Bracket FK12 (optional) ZA1110 18. Fan & Bracket FK24 (optional) 54103 * Temperature Sensor (optional) 51704 * Fan Speed Control (optional) 51738 * Fan Speed Control Knob (optional) 51882 * Electric Cord 51865 19. Remote ON/OFF switch (RN/RP models) 51842 * Wiring Harness (remote switch) 55923 * Remote ON/OFF Switch Kit (incls. bracket) 53875 20. Louvre Assembly, side top. 10000039

10006326

Page 29 of the Vermont Casting 360DVSR user manual — B122
Page 29 · click to enlarge
Page 29

Ref. Description 360DVS2 360DVS3 360DVSL 360DVSR 360DVS Series (continued) (Items marked ‘*’ are not shown in the parts illustration)

21. Louvre Assembly, side bottom 10000040 22. Louvre Assembly, end top N/A 10002411 10002411 10002411 23. Louvre Assembly, end bottom N/A 10002412 10002412 10002412 24. Hinge, lower louvre assemblies 52356 25. Trim Window Top/Bottom w/Magnets PB 57483 26. Trim Window Top/Bottom w/Magnets PB n/a 10006197 10006197 10006197 * Window Frame Assembly, side 10002483 * Window Frame Assembly, end N/A 10002484 10002484 10002484 * Window Glass (complete with gasket), side 10002533 * Window Glass (complete with gasket), end N/A 10002534 10002534 10002534 * Gasket Kit (glass replacement, 1x11’ length) 57317 27. Window Frame Clamp 54174 28. Refractory Lining (vertical end walls) 10006254 29. Refractory Lining (vertical side wall) N/A N/A 10006285 10006285 30. CR Bottom Kit w/out Rear 10006257 * Air Inlet Cover Plate Assembly 10006174 * Air Inlet Cover Plate Gasket 10006171 10006171 10006174 10006171 * Flue Pipe Plate Assembly 10002554 * FluePipe Plate Gasket 10002237 10002237 10002237 1000223 * Flue Cover Plate 10002298 * Flue Cover Plate Gasket 10002233 * Relief Plate (with gasket) 10002429 * Deflector, Cabinet Top Short N/A 10002260 10002260 10002260 * Corner Post (left) N/A 10006190 10006190 10006190 * Corner Post (right) N/A 10006191 10006191 10006191 * Corner Post Mounting Bracket N/A 10006195 10006195 10006195 * Deflector Cabinet Top Long 54364 31a. Pilot Assembly SIT Top Convertible EN 10002387 31b. Pilot Assembly SIT Top Convertible EP 10002388 32. Ignitor Electrode SIT EN/EP 52465 33. Cable Ignitor SIT EN/EP 10000696 34a. SIT822 Gas Control Valve EN 57884 34b. SIT822 Gas Control Valve EP 57883 35. Sensing Electrode (w/ Cable) EN/EP 57885 36. Transformer 24V EN/EP 7522409 37. Ignition Module Honeywell EP 20000005 * Wire Harness Honeywell EN/EP 10001979

10006326

Page 30 of the Vermont Casting 360DVSR user manual — IF WARRANTY SERVICE IS NEEDED…
Page 30 · click to enlarge
Page 30

LIMITED LIFETIME WARRANTY

PRODUCT COVERED BY THIS WARRANTY All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.

BASIC WARRANTY

CFM Corporation (hereinafter referred to collectively as the Company) warrants that your new Vermont Castings or Majestic Gas Fireplace/ Stove is free from manufacturing and material defects for a period of one year from the date of purchase, subject to the following conditions and limitations.

  • Any part and/or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty, whichever is longest.
  • This warranty is limited to the repair of or replacement of part(s) found to be defective in material or workmanship, provided that such part(s) have been subjected to normal conditions of use and service, after said defect is confirmed by the Company’s inspection.
  • The company may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of the defective part(s)
  • Any installation, labor, construction, transportation, or other related costs/expenses arising from defective part(s), repair, replacement, or otherwise of same, will not be covered by this warranty, nor shall the Company assume responsibility for same. Further, the Company will not be responsible for any incidental, indirect, or consequential damages except as provided by law.
  • SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
  • All other warranties-expressed or impliedwith respect to the product, its components and accessories, or any obligations/liabilities on the part of the Company are hereby expressly excluded.
  • The Company neither assumes, nor authorizes any third party to assume on its behalf, any other liabilities with respect to the sale of this Vermont Castings or Majestic product
  • The warranties as outlined within this document do not apply to chimney components or other non CFM Corporation accessories used in conjunction with the installation of this product..
  • Damage to the unit while in transit is not covered by this warranty but is subject to claim against the common carrier. Contact the dealer from whom you purchased your fireplace/stove (do not operate the appliance as this might negate the ability to process the claim with the carrier).
  • The Company will not be responsible for: a) Down drafts or spillage caused by environmental conditions such

EXTENDED LIFETIME WARRANTY

The heat exchanger, where applicable, and combustion chamber of every Vermont Castings or Majestic gas product is warranted for life against through wall perforation. All appliances equipped with an Insta-Flame Ceramic Burner have limited lifetime coverage on the ceramic burner plaque. Warrantees are made to the original owner subject to proof of purchase and the conditions and limitations listed on this Warranty Document

COMPONENT WARRANTY

CAST IRON: All external and internal cast iron parts are warranted for a period of three years. Note: On porcelain enamel finished external parts and accessories The Company offers no Warranty on chipping of enamel surfaces. Inspect all product prior to accepting it for any damage to the enamel. The salt air environment of coastal areas or a high humidity environment can be corrosive to the porcelain enamel finish. These conditions can cause rusting of the cast iron beneath the porcelain enamel finish, which will cause the finish to flake off. Dye lot variations with replacement parts and/or accessories can occur and are not covered by warranty.

GLASS DOORS: Glass doors are covered for a period of one year. Glass doors are not warranted for breakage due to misuse or accident. Glass doors are not covered for discoloration or burned in stains due to environmental issues, or improper cleaning and maintenance.

BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar mix and masonry cleaners may corrode the brass finish. The Company will not be responsible for, nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.

GAS VALVESGas valves are covered for a period of one year

ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and mechanical components of the burner assembly are covered for one year. All steel tube burners are warranted for one year.

as near-by trees, buildings, roof tops, hills, or mountains. b) Inadequate ventilation or negative air pressure caused by

ACCESSORIES: Unless otherwise noted all components and CFM Corporation company supplied accessories are covered for a period of one year.

mechanical systems such as furnaces, fans, clothes dryers, etc. • This warranty is void if: a) The fireplace has been operated in atmospheres contaminated

CONDITIONS AND LIMITATIONS

  • This new Vermont Castings or Majestic product must be installed by a competent, authorized, service contractor. A licensed technician, as prescribed by the local jurisdiction must perform any installation/service work. It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
  • This warranty is non-transferable, and is made to the original owner, provided that the purchase was made through an authorized supplier of the Company.
  • The customer must pay for any Authorized Dealer in-home travel fees or service charges for in-home repair work. It is the dealers option whether the repair work will be done in the customer’s home or in the dealer’s shop.
  • If upon inspection, the damage is found to be the fault of the manufacturer, repairs will be authorized at no charge to the customer parts and/or labor.

by chlorine, fluorine, or other damaging chemicals. b) The fireplace has been subjected to prolonged periods of dampness

or condensation c) Any damages to the fireplace, combustion chamber, heat exchanger

or other components due to water, or weather damage, which is the result of but not limited to, improper chimney/venting installation. d) Any alteration, willful abuse, accident, or misuse of the product

has occurred.

IF WARRANTY SERVICE IS NEEDED…

1. Contact your supplier. Make sure you have your warranty, your sales receipt, and the model/serial number of your CFM Corporation product. 2) DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.

10006326

Page 31 of the Vermont Casting 360DVSR user manual — CFM Corporation
Page 31 · click to enlarge
Page 31
Vermont Casting 360DVSR — B122 diagram (page 31)
Fig. 30

Efficiency Ratings

Model EnerGuide Ratings Steady State (%) D.O.E. Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%) 360DVS2RN 62.4 83 84 65 360DVS2RP 62.4 83 84 65 360DVS2EN 62.4 83 84 65 360DVS2EP 62.4 83 84 65 360DVS3RN 62.4 83 84 65 360DVS3RP 62.4 83 84 65 360DVS3EN 62.4 83 84 65 360DVS3EP 62.4 83 84 65 360DVSLRN 62.4 83 84 65 306DVSLRP 62.4 83 84 65 360DVSLEN 62.4 83 84 65 360DVSLEP 62.4 83 84 65 360DVSRRN 62.4 83 84 65 360DVSRRP 62.4 83 84 65 360DVSREN 62.4 83 84 65 360DVSREP 62.4 83 84 65

Vermont Casting 360DVSR — Efficiency Ratings diagram (page 31)
Fig. 31 · Efficiency Ratings

CFM Corporation

  • 2695 Meadowvale Blvd.
  • Mississauga, Ontario, Canada L5N 8A3 800-668-5323
  • <a href="http://www.cfmcorp.com" rel="nofollow noopener" target="_blank">www.cfmcorp.com</a>

Ask about the Vermont Casting 360DVSR

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Vermont Casting 360DVSR

Be the first to ask — other owners or our team will answer.

Original document

Vermont Casting 360DVSR manual PDF

31 pages·2.2 MB·Ventilation Hood·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…