SAFETY INFORMATION
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE.
Installation and service must be per- formed by a qualified installer, service agency or the gas suppler.
DO NOT STORE OR USE GASO- LINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
E
S
G
N
This appliance may be installed in an after market permanently located manu- factured (mobile) home where not pro- hibited by local codes.
E
R
E
D
T
F
This appliance is only for use with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases unless a certified kit is used.
30002008 3/06 Rev. 6



The Dutchwest Natural Vent Room Heater, Model Nos. 2467 and 2468, is a vented gas appliance listed to the ANSI standard Z21.88b-2001 and CSA-2.33b-2001 for Vented Room Heaters, and CSA 2.17-M91, Gas-Fired Appliances For Use at High Al- titudes.
The Dutchwest Natural Vent Room Heater, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, (latest edition), or of the current Canadian Electri- cal Code C22.1.
The installation of the Dutchwest Natural Vent Room Heater must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edi- tion and CSA B-149.1 Installation Code. (EXCEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5 inches w.c. for Natural Gas and 10 inches w.c. for LP gas at maximum input.)
Due to high temperatures this appliance should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be carefully super- vised when they are in the same room as the appliance.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
Installation and replacement of gas piping, gas utilization equipment or accessories, and repair and servicing of equip- ment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation, or company that either in person or through a representative is engaged in and is responsible for (a) installation or replace- ment of gas piping, or (b), the connection, installation, repair, or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
Clothing or other flammable materials should not be placed on or near the appliance.
Any safety screen, glass or guard removed for servicing an appliance must be replaced prior to operating the appli- ance.
The appliance area must be kept clear and free from com- bustible materials, gasoline, and other flammable vapors and liquids.
The flow of combustion and ventilation air must not be ob- structed. The installation must include adequate accessibility and clearance for servicing and proper operation.
The Dutchwest Natural Vent Room Heater should be inspected before use and at least annually by a qualified service agency. It is imperative that control compartments, burners, and circulating air passageways of the appliance be kept clean.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
The Dutchwest Natural Vent Room Heater and its individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
Do not burn wood, trash or any other material for which this appliance was not designed. This appliance is designed to burn either natural gas or propane only.
The Dutchwest Natural Vent Room Heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
This gas appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
An accessible tap is located above the pilot/on-off knob for checking the inlet pressure.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
Verify proper operation after servicing.
This appliance must be properly connected to a listed 4” (100mm) Type B venting system or to an approved masonry or factory-built chimney system. In Canada, a complete reline of Class A chimneys is required. This heater is equipped with a vent safety shutoff system.
* Aftermarket: Completion of sale, nor for purpose of resale, from the manufacturer.
This appliance must be properly connected to a venting system. WARNING: Operation of this heater when not con- nected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxide (CO) poisoning and possible death.
Proposition 65 Warning: Fuels used in gas, woodburning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
This appliance is approved for bedroom installations in the U.S. and Canada.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
California Health & Safety Code Sec. 25249.6
30002008


Fig. 1 Dutchwest dimensions.
30002008


Combustible Materials
Measure side clearances as shown in Figures 2 through 5 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the sheet metal rear skirt.
The Dutchwest heater is approved for installation into an alcove constructed of combustible materials to the dimensions and clearances shown in Figure 5.
The same clearances apply in a standard parallel instal- lation.
Fig. 4 Minimum ceiling clearance; minimum alcove height.


A: 4” (102mm) B: 33” (838mm) C: 5” (125mm)
Fig. 5 The Dutchwest Natural Vent Stove is approved for installation into alcoves built of combustible materials.
Stove Clearances A: 5” (125mm) B: 4” (102mm) Pipe Centerlines C: 16” (406mm) D: 9¹⁄₄” (235mm) ST128c
Fig. 2 Parallel installation requirements.
The Dutchwest Heater must be installed on rigid floor- ing. When the heater is installed directly on any com- bustible surface other than wood flooring, a metal or wood panel extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.

Fig. 3 Corner installation requirements.
30002008

The Dutchwest must be properly connected to a listed 4” (102 mm) Type B venting system or to an approved Class A masonry or factory-built chimney system. In Canada, a complete relining of Class A chimney sys- tems is required.
The Dutchwest Natural Vent stove will accept decora- tive 6” (150mm) stove pipe around the Type B venting system, for aesthetic purposes.
Weight: Fully assembled 350 lbs.
Complete Type B vent systems are available from a number of manufacturers, and your dealer can usually supply one. Pipe sections from different makers are not interchangeable; do not mix pipe or vent sections from different makers. Follow the vent system manufactur- er’s instructions.
The vent system should conform to the specifications of the National Fuel Gas Code, latest edition.
Certified to: ANSI Z21.86b-2001 / CSA Z2.33b-2001
If connecting to a Class A chimney system, use 4” (102 mm) single wall or 4” Type B vent connector. Single wall vent connector requires a minimum 6” (152 mm) clear- ance to combustible surfaces.
Exterior chimneys may be subject to flow reversal or condensation. To lessen these conditions, enclose Type B vents in an insulated chase, or reline exterior Class A chimneys.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP- TION: Do not derate this appliance for altitude. Main- tain the manifold pressure at 3.5” w.c. for Natural Gas and 10” w.c. for Propane.)
An approved pass-through device is always required, whether the vent system passes through a wall or a ceiling. Use a pass-through device from the same maker who supplies the venting system.
Venting terminals shall not be recessed into a wall or siding.
Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
Venting for a Dutchwest can rise vertically through the home, or can pass through an exterior wall and rise along the outside of the home. Some codes require that a Type B vent system rising on the outside of the home be enclosed in a chase. Check your local codes for requirements.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).
The minimum vent system height for the Dutchwest Natural Vent Stove is 8’ (2.43 m), (Fig. 7) measured from the top of the stove. To determine the minimum height the vent system must extend through or past the roof, refer to the 1993 edition of the National Fuel Gas Code.
30002008

Venting Requirements
An approved pass-through device is always required when a vent passes through a combustible wall or ceil- ing. Check with the maker of the vent system for the correct listed devices that are available. A listed pass- through device is required whether or not the installa- tion includes decorative pipe around the Type B venting system. NOTE: It is essential to seal between the ceil- ing support (sometimes called a ‘firestop spacer’) and the decorative pipe, if installed, with a high-temperature silicone sealant. (Fig. 6)
(Measured from top of the unit before any elbow)
B
Vertical Run (in feet)
Complete the venting system installation according to the manufacturer’s instructions.
Air Space as Re- quired by Code
1 2 4 6 8 10 12 14 16 18 20 22 24
Horizontal Run (in feet)
Listed 4” (102mm) B-Vent
= Acceptable venting configuration
= Unacceptable venting configuration
Fig. 6 A ceiling pass-through, with decorative pipe around the vent.
A: Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.
B: Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two 45-degree elbows. (Ratio = 2/3, Hor./Vert.)
Fig. 7 Vent termination window.

1. The fan kit includes a blower assembly and a rheo- stat assembly, connected by a cable. The blower as- sembly mounts to the bottom rear of the stove, and the rheostat mounts to the left side of the valve. The assembly includes a ‘snapstat’ which automatically turns the fan ON (or OFF) above (or below) approxi- mately 109°F. The rheostat also provides a range of fan speed settings from Off (which overrides the snapstat function) to High. Unpack and inspect the blower assembly. Confirm that the fan spins freely. 2. Attach the fan assembly to the bracket provided in the log box. Use #10 sheet metal screws provided with fan kit. Do not remove finger guard screws. (Fig. 8)


Fig. 10 Attach snapstat wire assembly to inside of inner shroud with clamp screws.
6. Assemble the inner shroud to the outer shroud using previously removed screws. 7. Position the fan assembly so the ducts slide be- tween the inner and outer shroud. The inner shroud should engage with the two slots in the ends of the bracket so the bracket and shroud are interlocked. (Fig. 11) Secure the bracket with the four sheet metal screws provided in the finish bag. 8. Install the snapstat by loosening the front screw on the inner side of the duct. (Fig. 12) Slide the snapstat under the head of the screw and tighten. Connect the leads to the snapstat. Make sure the snapstat assembly is mounted straight front to back.
Fig. 8 Attach the fan assembly to the fan bracket.


Fig. 11 Position the fan to engage the inner shroud with the fan bracket slots and secure with sheet metal screws.
Fig. 9 Remove the snapstat and grommet from the bracket
30002008


The venting collar is on the sheet metal draft hood/heat exchanger assembly, over the firebox. Use a B-vent adapter, from the same maker as the rest of the B-vent components, to join the first section of venting to the draft hood.
The stove includes a spill switch. Operating this stove when not connected to a properly installed and main- tained venting system, or tampering with or disconnect- ing the spill switch, can result in carbon monoxide (CO) poisoning and possible death.
Fig. 12 Install the snapstat and connect the extension wire terminals. View is with top removed, however, access is available through the rear when installing fan before gas line connection.
The stove includes a bracket for installing decorative 6” (150mm) round stove pipe around the B-vent, for ap- pearance purposes only. The decorative pipe need not be concentric with the vent pipe.
If the installation includes decorative stove pipe around the venting system, make a cardboard template of the decorative pipe by tracing its circumference. Put this template in the flue recess in the stove top. Position the template to fit well against the front of the recess. (Fig. 16) Use this template to locate the bracket to hold the decorative pipe. Depending on spacing, the bracket may fit inside the decorative pipe without interfering with the vent system. Fasten the bracket to the draft hood/heat exchanger assembly with a sheet metal screw.


Fig. 16 Use a template to locate the bracket for decorative pipe to surround the B-vent pipe.
Insert the B-vent adapter into the flue collar and drill 1/8” (3mm) pilot holes through both the stove’s collar and the adapter. Attach the adapter to the flue collar with sheet metal screws. (Fig. 17)
Fig. 13 Attach rheostat to left side of valve.


Fig. 14 #2767 / FK26 fan wiring diagram.
30002008

Attach the first section of venting to the B-vent adapter. Depending on the length of the individual venting sections and the lengths of the decorative pipe, you may need to slip the decorative pipe over the venting sections before attaching upper sections to lower ones. The sections of decorative pipe should be oriented with their seams (if any) toward the wall; sections usually do not need to be fastened at each joint, other than slip sections. The decorative pipe need not be fastened to the locating bracket on the stove. If the layout includes a slip section, this should be the last section of pipe vis- ible in the room at the ceiling. Refer to Page 7, Figure 6 for details on joining the decorative pipe at the ceiling.
Check the Rating Plate attached by a steel cable to the firebox, to confirm that you have the appropriate firebox for the type of fuel to be used. The Dutchwest may be converted from one gas to another using the appropri- ate Fuel Conversion Kit listed on Page 23.
This appliance should only be connected by a qualified gas technician. Test to confirm manifold pressures as specified below.
The Dutchwest Heater and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Dutchwest Heater must be isolated from the gas supply piping system by closing its indi- vidual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove and the supply.
Fig. 18 Install decorative pipe over the B-vent pipe.
In order to connect Natural Gas, use a fitting with 3/8” NPT nipple on the valve side and 1/2” natural gas supply line with an input of 28,000 BTUs at a manifold pressure of 3.5” and a minimum inlet supply pressure of 5.5” w.c.
In order to connect Propane, use a fitting with 3/8” NPT nipple on the valve side and 1/2” pro- pane gas supply line with an input of 26,000 BTUs at a manifold pressure of 10.0” and a mini- mum inlet supply pressure of 11.0” w.c.
In the U.S.; Gas connection should be made in ac- cordance with current National Fuel Gas Code, ANSI Z223.1/NFPA 54. Since some municipalities have addi- tional local codes, be sure to consult you local authority.
In Canada; consult the local authority and CSA-B149.1 installation code.
Connect the gas supply and test for leaks. Use a 50/50 solution of liquid soap and water to test for leaks at gas fittings and joints. Apply water/soap solution with brush only - do not over apply. NEVER test with an open flame. Light the pilot according to the directions on Page 14, before going to the next step.


The appliance must only use the gas specified on the rating plate, unless converted using a CFM Corporation Fuel Conversion Kit. Refer to Page 23 for the correct Fuel Conversion Kit for your model.
Conversion instructions are provided with each kit and beginning on Page 16 in this manual.

THIS APPLIANCE SHOULD BE CONNECTED TO THE GAS SUPPLY ONLY BY A QUALI- FIED GAS SERVICE TECHNICIAN. FOLLOW ALL LOCAL CODES.
Fig. 20 Attach switch wires to valve.
THERE MUST BE A GAS SHUT-OFF BE- TWEEN THE STOVE AND THE SUPPLY.
Use only a thermostat rated for 500 - 750 millivolts.
Check the table below for the appropriate gauge ther- mostat wire to use for the length of lead required in your installation.
In order to connect Natural Gas, use a fitting with 3/8” NPT nipple on the valve side and 1/2” natural gas supply line with an input of 28,000 BTUs at a manifold pressure of 3.5” and a minimum inlet supply pressure of 5.5” w.c.
Thermostat Wire / Gauge Maximum Run 18 40 feet 20 25 feet 22 16 feet
In order to connect Propane, use a fitting with 3/8” NPT nipple on the valve side and 1/2” propane gas supply line with an input of 26,000 BTUs at a manifold pressure of 10.0” and a minimum inlet supply pressure of 11.0” w.c.
Install the Log Set
The switch assembly parts are found in the parts bag. 1. Attach switch assembly to left rear side of stove shroud (when facing shroud) using two screws and existing holes in shroud. (Fig. 19) 2. Run wires down back of stove, under bottom of rear shroud to valve. 3. Attach wires to valve terminals. (Fig. 20)
1. Remove the logs from their packaging, and inspect each piece for damage. DO NOT INSTALL DAM- AGED LOGS. 2. Install the rear log centering it side to side on the sheet metal shelf at the back of the firebox. (Fig. 21) The log will touch both sides and the back wall of the firebox. 3. Install the right log by engaging hole on bottom with pin on the rear log. (Fig. 21) Then set right bottom side on the burner so the edge of the log touches the right side of the firebox. The right log does not use the locator pins on the burner to stay in place. 4. Install the left log by engaging hole on bottom with pin on rear log. (Fig. 21) Then set left bottom side on the burner so the edge of the log touches the left side of the firebox. 5. Loosely sprinkle the lava rocks directly on top of the burner in front of and between the decorative grate and the right and left logs. Use the lava rock to cover brackets on the burner. (Fig. 22)



Insert the handle stub into the hole in the front casting. Fasten in place with the 3/8” locking nut provided. (Fig. 23)
The front attaches to the stove by four steel tabs that engage with corresponding cast ribs onto the sides and bottom of the stove body. Position the front about 3” down from stove top and lift the plate to engage the upper tabs behind the adjacent ribs on the sides. (Fig. 24) Then lower the front into position, so the lower tabs engage with the corresponding ribs at the bottom.
When properly installed, the bottom of the stove front cannot be pulled away from the sides without also lifting it.

Fig. 21 Install the back, left and right logs.

Fig. 23 Insert handle stub into hole in front. Secure with 3/8” locking nut.

Fig. 21 Completed log installation.
Fig. 24 Install the front plate.
30002008

Read these instructions carefully and familiarize your- self with the burner controls. Locate the pilot assembly, Figure 25. Follow the lighting instructions on Page 14 exactly.
During the first fire, it is not unusual to smell some odor associated with new logs, paint and metal being heated. Odors should dissipate within an hour or so, however, you can open a window to provide fresh air to alleviate the condition.
Fig. 26 Correct pilot flame pattern.
Each time you light your heater check that the pilot flame and burner flame patterns are as shown in Fig- ures 26 and 27. If flame patterns are incorrect, turn the heater off. Contact your dealer or a qualified gas techni- cian for assistance. Do not operate the heater until the pilot flame is correct.
Follow regular maintenance procedures as described on Page 19.
Fig. 27 Correct burner flame pattern.
Fig. 25 Pilot Assembly location.

may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manu-
ally. When lighting the pilot follow these instruc- tions exactly. B. BEFORE LIGHTING smell all around the heater
control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Applying force or any attempted repair may result in a fire or explosion. D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service techni- cian to inspect the heater and to replace any part of the control system and any gas control which has been under water.
P
O
T
PILOT
F
ON
F P
O
F
ON
F
O
F
F
O
Euro SIT SIT NOVA Honeywell

A. Defective or misaligned Using a match, light [ilot. If pilot lights, turn off pilot and electrode at the pilot push the ignitor button again. If pilot will not light, check gap at electrode and pilot - it should be 1/8” to have a strong spark. B. Defective ignitor (push Push piezo ignitor button. Check for spark at electrode button) and pilot. If there is no spark at the pilot, and electrode wire is properly connected, replace ignitor. A. Defective pilot generator Check pilot flame. It must impinge on the thermocouple (thermocouple) or thermopile. NOTE: This pilot burner assembly uses both a thermocouple adn a thermopile. The thermo- couple operates the pilot flame. Tighten the thermo- couple. The thermopile operates the main valve. (ON and OFF) Clean and/or adjust pilot for maximum flame impingement on thermocouple and thermopile. B. Defective automatic valve Turn valve knob to “Pilot”. Maintain flow to pilot; millivolt operator mete should read greater than 10mV. If the reading is okay and the pilot does not stay on, replace the gas valve. NOTE: An interrupter block (not supplied) must be used to conduct this test. C.Defective safety switch Check the continuity accross the safety limit switch with the unit cold. If there is no continuity, the safety switch needs to be replaced. A. Remote switch or wires Check rocker switch and wires for proper connection defective Use jumper wires across terminals at rocker switch. If burner lights, replace rocker switch. If okay, use jumper wires across rocker switch wires at the valve. If burner lights, wires are faulty or connections are bad. B. Thermopile may not gen- 1. Be sure wire connecitons from thermopile at gas ate sufficient voltage valve terminals are tight and thermopile is fully inserted into pilot bracket. 2. One of the rocker switch wires may be grounded Remove rocker switch wire form valve termianls. If burner now stays lit, trace rocker switch wiring from ground. It may be grounded to the appliance of the gas supply line. 3. Check the thermopile with a millivolt meter. Take reading at thermopile (“TP” and “TP/TH”) terminals of gas valve. Should read 325 millivolts minimum while holding valve knob depressed in PILOT position and with rocker switch OFF. Replace faulty thermopile if reading is below specified minimum. C. Plugged burner orifice Check burner orifices for debris, and remove. D. Defective automatic valve Turn knob to ON, place rocker switch to ON. Millivolt operator meter should read greater than 10mV. If the reading is okay and the burner does not light, replace the valve. A. Pilot flame may be too low Clean and/or adjust pilot flame for maximum flame or high, (blowing or lifting). impingement on thermocouple and thermopile. causing the pilot to drop out B. Possible blockage of the Check the vent termianl for blockage. vent terminal
30002008

WARNING! This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruc- tions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is respon- sible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

Fig. 29 Remove rear log bracket and left and right log bracket assembly.
6. Remove the right and left log bracket assembly by unfastening the two screws which hold the burner in place. (Fig. 29) 7. Hold the burner at the right hand side and lift to clear the right burner leg. Then pull to the right to clear the injectors on the left hand side. 8. Remove injector orifices from left burner leg using 1/2” wrench. (Fig. 35) 9. Install conversion orifices. (Refer to Table 2) 10. Remove cap from HI/LO knob. This can be accom- plished by lifting the plastic cap off the screw. (Fig. 30) 11. Remove the screw from center of HI/LO knob with small screwdriver turning counterclockwise. (Fig. 30) 12.Insert blue painted screw when converting to natural gas and red painted screw when converting to LP. 13. Tighten screw (do not over tighten), replace cap.
OFF
H
O
ON
PILOT
ADJ
Main Gas Line Gas Supply Inlet ST770
Fig. 28 Attach the gas line to the left side of the valve.
Conversion must be completed only by qualified per- sonnel. Before proceeding, turn control knob on valve to “OFF” and turn gas supply OFF. Turn OFF any electricity that may be going to the appliance. CAU- TION: Allow stove to cool completely before beginning conversion.

1. Remove stove front. Lift stove front up and then swing bottom out and away to disengage from the stove body. (Page 19, Fig. 36) 2. Swing open the swiveling latches at the top left and right corners of the glass frame. (Page 20, Fig. 37) 3. Pull the top edge of the glass and frame assembly away from the firebox face. Place the assembly out of the way on a flat, padded surface such as a coun- ter protected by a towel. 4. Remove the logset from the firebox.
Fig. 30 Remove center screw from Hi-Lo knob.
30002008


Configuration for Stove with Serial #’s up to #5483
Configuration for Stoves with Serial #’s Starting at #5484 ST726
16. Adjust air shutter on the burner. The air shutter is located on the bottom of the burner on the left. (Fig. 33) Loosen the two nuts holding the shutter in place. On natural gas units, the shutter is shipped fully closed. To convert to LP, reset the shutter as speci- fied in Table 2. (Fig. 34) On propane unit the shutter is set at 1/8” or 3/8” opening depending on rating plate serial number. To convert to natural gas, the shutter should set to fully closed. Refasten the two nuts.
firebox base after conversion. 17. Replace burner. Slide the burner in at an angle with left side lower than the right side. Slide the left side onto the injectors, making sure the burner leg remains at a 90° angle to the base. Lower the right hand side down in to place. Make sure the burner is as far left as possible and the injector shoulders are inside the burner. NOTE: It is very critical to keep the left burner leg,
which holds the injectors, at a 90° angel to the base. (Fig. 35) This keeps the orifices aligned with the tubes inside burner. Failure to do so could affect the flame appearance and performance of the unit. 18. Place conversion label on valve. 19. Reinstall the right and left log bracket assembly. 20. Replace logs. 21. Replace glass and stove front. 22. Check manifold pressure. Conversion is complete.

Configuration for Stove with Serial #’s up to #5250
Configuration for Stoves with Serial #’s Starting at 5251 ST718
Fig. 33 Natural gas air shutter setting.
30002008

Conversion to Natural Gas Input (BTU/h) Air Shutter Kit # Front Part # Rear Part # Minimum Maximum Setting 000-5021 #54 / .055” 20000130 #44 / .086” 30000334 19,000 28,000 Fully Closed
Conversion to LP Input (BTU/h) Air Shutter Kit # Front Part # Rear Part # Minimum Maximum Setting 000-5022 #69 / .029” 30000513 #54 / .055” 20000130 21,500 28,000 3/8” Open
30002008


Your Dutchwest Gas Heater will provide years of service with minimal upkeep. The following procedures will help ensure that your stove continues to function properly.
TURN THE PILOT OFF BEFORE PAINTING. ALLOW THE HEATER TO COOL COMPLETELY BEFORE PAINTING.
Have the entire heater and venting system inspected annually by a qualified gas technician. Replace any worn or broken parts.
It will be necessary to clean the glass periodically. Dur- ing start-up, condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also, initial paint curing may deposit a slight film on the glass. It is therefore recommended that the glass be cleaned two or three times with a non-ammonia household cleaner and warm water (we recommend gas fireplace glass cleaner). After that the glass should be cleaned two or three times during each heating season depend- ing on the circumstances present.
Cleanliness is critical to the proper function of the heater. The logset and burner must all be kept free of dust and unobstructed by debris. Inspect these areas before each use and clean as necessary.
1. Turn the burner OFF and let the heater cool com- pletely before cleaning. 2. Lift the Stove Front up and then swing the bottom out to disengage it from the heater shell. (Fig. 36) 3. Carefully remove the glass and frame assembly and place it out of the way on a flat, padded surface such as a counter protected by a towel. 4. Carefully inspect the Logs for damage. Contact your local dealer if any damage is evident. DO NOT OPERATE THE HEATER WITH DAMAGED LOGS. 5. Use a soft bristled brush to sweep dust or debris from the Logs, Pilot and Burner. Use care as the logs are fragile and susceptible to damage. 6. Replace the glass panel and frame assembly.
Clean glass after first two weeks of opera- tion.
Replace glass only with CFM Corporation approved parts. Refer to Page 22 for Replacement Parts. Refer to Figure 37 and previous instructions for removal of the damaged glass frame.

An occasional dusting with a dry rag will help keep the painted surfaces looking new. Use high-temperature stove paints, available through your local dealer, to touch-up areas as needed. Clean areas to be painted with a wire brush and be sure to cover the logs, burner and valve assembly, glass and frame assembly. Apply the paint sparingly; two light coats of paint will give bet- ter results than a single heavy coat.
Clean porcelain enamel surfaces with a soft, damp cloth. Do not use abrasive cleaning agents. If neces- sary, use only a cleaning agent formulated especially for use on porcelain enamel surfaces.
Fig. 36 Remove the Stove Front.
30002008


Have the vent system inspected annually by a quali- fied technician. Shut off the main gas supply before inspecting the system. Both the inner exhaust pipe and the outer combustion supply pipe must be checked to confirm that they are unblocked and in good condition.
To ensure that the stove is operating properly, check the flames periodically to confirm they match Figure 39. The flames will be blue during the first 15-20 minutes of operation, and will gradually turn to yellow.
Fig. 37 Release the latches to release the glass frame.
Do not use your stove if the flame pattern differs from that shown here. Contact your Dutchwest dealer or a qualified technician for help.
The Dutchwest Gas Heater uses a ‘tadpole’ type gasket to seal between the glass panel and the frame. In time, this gasket can become brittle and compressed and should be replaced. New gasket is available from your dealer.

Shut off the gas supply and allow the stove to cool. Wear safety goggles and a dust mask. 1. Remove the Front, Glass Frame and Glass Panel. (Figs. 36, 37) Remove the old gasket. Use a razor blade, with rounded corners, to separate the glass and gasket from the frame, and to clean the glass of any remaining cement or bits of gasket. 2. Determine the correct length of gasket by laying it out around the edge of the glass. Allow an extra 1 - 2” (25-50 mm). Mark the spot to be cut. Use a utility knife. 3. Starting on a long edge, remove about 6” of the pro- tective paper strip and apply the flat adhesive face of the gasket around the outside-facing edge of the panel. Continue around the panel, applying about 6” at a time and being careful to not stretch the mate- rial. Do not overlap the gasket ends. (Fig. 38) 4. Apply a thin bead of high temperature silicone rubber sealant along the inside corner of the glass frame, all around the perimeter. Place the flat gasketed side of the glass panel back into the steel frame. Pinch the rounded inside-facing gasket mate- rial to bulk it up. 5. Replace the glass frame and front panel as previ- ously described.
Fig. 39 Correct flame pattern.
If there is ever a need to remove the firebox assem- bly from the stove shell, support the firebox with solid stands about 6” (152 mm) tall under the left and right outer edges of the firebox base. Do not set the firebox assembly directly on the floor; this can damage the control valve and/or the gas lines from the valve to the firebox.
Before removing the firebox from the shell, disconnect the on/off switch wires from the valve. If the assembly includes the optional fan, disconnect the fan rheostat. If the installation includes a wall thermostat, disconnect the thermostat leads from valve.

Disconnection and reconnection to the gas line should only be done by a qualified gas service technician.
Upon reinstallation, the vent system must be sealed to the firebox as shown in the installation section, Page 9. Also be sure the logs are placed in the firebox correctly, as shown on Page 11, Figures 21, 22.
Fig. 38 Wrap the gasket material around the outside edge of the glass.
30002008



Fig. 40 On/off switch and optional thermostat circuit.

Fig. 42 Fan circuit.
Fig. 41 Safety Limit Switch wiring.
30002008


CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
Ref. Description Part Number 1. SDV30 Log Set Assembly 20003458 1a. Rear Log 20003459 1b. Right Log 20003460 1c. Left Log 20003461 2. Small Lava Rock Package 57897 3. Top, NV DW Gas 30002005 4. Grille, NV DW Gas 30002044 5. Front, DW Gas 30001928 6. Door, DW Gas 30001929 7. Leg, DW Gas 30001930

30002008

Ref. Description Part Number 8. End, Rt - DW Gas 30001927 9. End, Lt - DW Gas 30001926 10. Gasket, Glass Med. Knit - RDV40 1203702 11. Glass, DV25 1601691 12. Glass Frame Assembly SDV30 30000127 13. Manifold Tube Assembly - Double Bead 20003739 14a. Valve RN Honeywell VS8420E 2038 10001782 14b. Valve RP Honeywell VS9420E 2020 10001759 15a. Pilot Assembly 3Way N/DV Rn 0.199.706 10002264 15b. Pilot Assemlby 3Way RP 0.199.703 10002265 16. Thermocouple 24” 53373 7531137 17. Electrode Ignitor w/ cable SIT 24 10001297 18. Pilot Top Convertible 10002266 19. Thermopile 51827 7533113 20. Tubing Pilot w/Fitting SIT 10001296 21. Nut Electrode SIT #0.974.144 57886 22a. Orifice Hood #69 - 0.0292” (Front LP) 30000513 22b. Orifice Hood #54 (Front Natural) 20000130 22c. Orfice Hood #54 Rear LP 20000130 22d. Orfice Hood #44 Rear NG 30000334 23a. Orifice Pilot #62 NG Top Convertible 10002268 23b. Orifice Pilot #35 - LP Top Convertible 10002269 24. Burner Housing Assembly 20005264 25. Nut, Hex Jam 3/8 - 16 Top LK-Z 1203290 26. Front Pawl Assembly, Ash Door - ENC 5004025 27. Front Steel Handle/Shaft - NI/VER 5004237 28. Handle Package, Ceramic w/Screw 0004342 29. Grate Burner JDV 20002167 30a. Sensor Spill Switch, Bedroom 51866 30b. Spill Switch 20005039 31. Switch Rocker 30000874 32. Wire w/Straight Term 2 End 50” 10002582 33. Spill Switch Wire Assembly 30000108 34. Bracket - Right Log 20005259 35. Bracket - Left Log 20005258 37. Gasket Base Pan Inner 20002566 38. Interrupter block 30000069 39. Draft Hood/Flue Collector Assembly 20005227
Fuel Conversion Kits Conversion Kit, NG to LP - 2467 Kit #000-5022 Conversion Kit, LP to NG - 2468 Kit #000-5021
30002008

Decorative Rings
4” brass or black rings are available to add a decorative touch to the exposed stove pipe.
The FK26 fan kit helps distribute heated air from within the firebox out into the room.. The fan is controlled by a snapstat that turns power on and off as the firebox tem- perature rises above and falls below a preset tempera- ture. A rheostat provides for variable fan speeds.
4FSDRB/4 4” Black Rings (4) 4FSDRP/4 4” Polished Brass Rings (4)
115 Volt / 60Hz / .75 amps
An outside air adapter, #5076, may be added to the stove to bring fresh air for combustion directly from outside the building into the stove.
The fan itself does not require regular maintenance, however, periodic cleaning of the fan and the surround- ing area is required.
Refer to Page 8 for installation instructions.
The remote control allows you to turn the heater on or off from anywhere in the room. Refer to Page 21 for wiring diagrams.
MRC1 ON/OFF MRC2 ON/OFF and Temperature MRC3 ON/OFF and Temperature control with a digital display and a programmable 24 hour clock IMT Wall mounted thermostat control

30002008

30002008

PRODUCT COVERED BY THIS WARRANTY All Dutchwest gas stoves equipped with an Insta-Flame Ceramic Burner.
CFM Corporation Company (hereinafter referred to collectively as the Company) warrants that your new Dutchwest Gas Fireplace/Stove is free from manufacturing and material defects for a period of one year from the date of purchase, subject to the following conditions and limitations.
The heat exchanger, where applicable, and combustion chamber of every Dutchwest gas product is warranted for life against through wall perforation. All appliances equipped with an Insta-Flame Ceramic Burner have limited lifetime coverage on the ceramic burner plaque. Warrantees are made to the original owner subject to proof of purchase and the conditions and limitations listed on this Warranty Document
CAST IRON: All external and internal cast iron parts are warranted for a period of three years. Note: On porcelain enamel finished external parts and accessories The Company offers no Warranty on chipping of enamel surfaces. Inspect all product prior to accepting it for any damage to the enamel. The salt air environment of coastal areas or a high humidity environment can be corrosive to the porcelain enamel finish. These conditions can cause rusting of the cast iron beneath the porcelain enamel finish, which will cause the finish to flake off. Dye lot variations with replacement parts and/or accessories can occur and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year. Glass doors are not warranted for breakage due to misuse or accident. Glass doors are not covered for discoloration or burned in stains due to environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar mix and masonry cleaners may corrode the brass finish. The Company will not be responsible for, nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and mechanical components of the burner assembly are covered for one year. All steel tube burners are warranted for one year.
as near-by trees, buildings, roof tops, hills, or mountains. b) Inadequate ventilation or negative air pressure caused by
ACCESSORIES: Unless otherwise noted all components and CFM Corporation company supplied accessories are covered for a period of one year.
mechanical systems such as furnaces, fans, clothes dryers, etc. • This warranty is void if: a) The fireplace has been operated in atmospheres contaminated by
chlorine, fluorine, or other damaging chemicals. b) The fireplace has been subjected to prolonged periods of dampness
or condensation c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the result of but not limited to, improper chimney/venting installation. d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
30002008


Model EnerGuide Ratings Fireplace Efficiency (%) 2467 51.4 2468 51.4

Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| 1. Spark ignitor will not light | p.15 | ||
| 1. Spark ignitor will not light | p.15 | ||
| 2. Pilot will not stay lit after carefully fol- lowing the lighting instructions | p.15 | ||
| 2. Pilot will not stay lit after carefully fol- lowing the lighting instructions | p.15 | ||
| 3. Pilot lights, no gas to burner, valve knob ON, remote switch (rocker switch) ON | p.15 | ||
| 3. Pilot lights, no gas to burner, valve knob ON, remote switch (rocker switch) ON | p.15 | ||
| 4. Frequent pilot out- age | p.15 |