Practical Power Guidelines for VoIP and Internet Telephony Applications

by David Slotten

WHITE PAPER

Cisco, Cisco Systems, the Cisco Systems logo, and the Cisco Square Bridge logo are registered trademarks or trademarks of Cisco Systems, Inc. and/or its affiliates in the U.S. and certain other countries.

95-2914

Page 2 of the Tripp Lite H2561 user manual — Integrate Backup Power into VoIP Networks
Page 2 · click to enlarge
Page 2

Integrate Backup Power into VoIP Networks

Voice over IP (VoIP) is exploding in popularity as an application for business data networks. VoIP promises to consolidate a company's data and telecommunications infrastructure as well as its support resources. As a result, a company can lower its hardware and service costs while raising productivity through the use of more elaborate and customizable telephony applications.

Unfortunately, there are serious limitations inherent to the data networks that are increasingly called upon to support VoIP. The primary limitation is power availability. Before moving voice traffic from traditional circuit- switched public phone systems to private data network connections, one must consider a public phone system's unique attribute—battery support. In order to deliver extremely high availability for such vital services as emergency 911 support in the event of extended power outages, public phone systems are connected to massive battery arrays.

While most data networks have some type of backup support during power outages (provided by UPS Systems and/or generators), the backup runtime is generally much less than the 4 to 8 hours of backup that is typically provided for public phone systems. Because of this shortcoming, VoIP applications generally require an increase in the UPS System-supported power capacity (e.g. more or larger UPS Systems). Increased UPS System capacity provides power for network-dependent phones and increases overall backup runtime to ensure that normal telephone operation (including 911 service) remains available in the event of an extended power outage.

Reflecting on important lessons learned during its own transition to IP telephony, Cisco provides several best-practice recommendations. One of the most important recommendations is installing a UPS System to guarantee availability:

“Plan Your Power: When an IP network carries voice, reliability is essential. In case of an emergency, people need to summon assistance by dialing 911. When using inline power to switches and routers, make sure they are connected to an uninterruptible power supply [UPS System] to guarantee dial tone if the power should go out.”

Source: Cisco Systems white paper “The Transition to IP Telephony at Cisco Systems”.

http://www.cisco.com/en/US/tech/tk652/tk701/technologies_white_paper09186a00800cb7fd.shtml

2 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 3 of the Tripp Lite H2561 user manual — Typical VoIP Network Design
Page 3 · click to enlarge
Page 3

Consider the Diverse Needs of VoIP Network Equipment

Before selecting a UPS System to ensure 100% availability of IP telephony systems, it's important to consider the unique requirements of VoIP network equipment. Network designs hosting VoIP applications will vary widely from business to business due to a number of variables, including the scale of the network and the variety of legacy equipment involved. However, three devices are common to all networks:

Client Devices (phones, PC-based soft phones, etc.) During the transition to IP telephony, these devices will either (a) derive their power from the network cable via a Power over Ethernet (PoE) connection scheme, or (b) plug into a local AC source.

If they plug into a local AC source, they must be protected by a UPS System. Often a desktop UPS not only safeguards phone service, but also guarantees file integrity for associated PC users.

Typical VoIP Network Design

Tripp Lite H2561 — Typical VoIP Network Design diagram (page 3)
Fig. 1 · Typical VoIP Network Design

Networking Devices (switches, routers, etc.) During the transition to IP telephony, port capacity on the network and in wiring closets will increase to accommodate additional devices (phones) connected to the network. Increased port capacity will increase the power requirements placed on your UPS System, either reducing runtime or overloading the UPS. Note that if a networking device also supplies Power over Ethernet, the aggregate load of all client devices will also be borne by the networking device's UPS System.

Generally, an existing UPS will be inadequate to (a) power the increased load [watts] and (b) power the load for an acceptable length of time. Five to fifteen minutes of runtime provided to gracefully shut down the typical data network is inadequate for IP telephony users who expect phone service to continue for HOURS, not minutes.

SourceCisco Systems white paper “Power and Cooling for VoIP and IP

Telephony Applications”.

http://www.cisco.com/application/pdf/en/

0900aecd801a2c5f.pdf

Call Processing Devices (servers and related storage systems) During the transition to IP telephony, dedicated servers are typically added to drive voice and messaging applications, while storage systems are required for voicemail and other messaging applications. Similar to the increased burden placed on networking devices, call processing devices will experience increased loads and will require increased runtime.

3 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

us/guest/netsol/ns412/c654/cdccont_

Page 4 of the Tripp Lite H2561 user manual — Select a UPS System which Provides the Highest Availability, Resiliency and Manageability
Page 4 · click to enlarge
Page 4

Select a UPS System which Provides the Highest Availability, Resiliency and Manageability

When selecting a UPS System, the most obvious criterion to consider is whether a UPS System has enough capacity (VA/watts) to power equipment while having enough battery capacity to operate during a power outage for your required duration. Specific Tripp Lite UPS System recommendations are listed at the end of this document. Often overlooked during the selection process, however, are more subtle, yet critical, criteria that should be considered, including availability, resiliency to power anomalies and manageability.

1. Availability Availability hinges on three considerations: the VoIP equipment's power supply configuration, the UPS System's battery configuration and the UPS System's power electronics topology.

A. VoIP Equipment Power Supply Configuration Many switches and routers are equipped with redundant power supply capability. If one power supply fails, a second power supply steps in and powers the device. Redundant power supply configurations are strongly recommended to ensure continuous system availability.

Whether one or two power supplies are deployed, the equipment can draw power from one of three sources: directly from facility power alone (for simplicity's sake we will use the term “wall” to describe this source), from a single UPS System or from multiple UPS Systems.

The following tables detail a switch's operational status, from a power perspective, in both redundant and combined (non-redundant) modes. The tables detail switch status under a variety of operational scenarios, including power supply failure, utility failure and UPS System failure.

Note: Larger switches often have the capability to be alternatively configured to operate in a combined (non-redundant) configuration. In combined mode, two power supplies' capacities will be summed. A true doubling is not generally achieved. A factor of 1.67x is typical. In combined mode, there is no redundancy. Should a power supply fail, the available power is generally reduced to the capacity of a single power supply.

4 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 5 of the Tripp Lite H2561 user manual — Multiple Power Supplies Operating in Dual (Combined, Non-Redundant) Mode
Page 5 · click to enlarge
Page 5

Single Power Supply, or Multiple Power Supplies Operating in Redundant Mode

STEP 1: Determine Configuration Configuration12345 Power SupplyPS1PS1 PS2PS1 PS2PS1 & PS2PS1 PS2 Power SourceWallWall WallUPS1 WallUPS1UPS1 UPS2 STEP 2: Consider Failure ScenariosSTEP 3: Consider System Status PS1 StatusUtility StatusUPS StatusSystem Status OKOKOKOKOKOKOKOK FailureOKOKCrashOKOKCrashOK OKBlackoutOKCrashCrashOKOKOK OKBlackoutUPS1 Battery FailsCrashCrashCrashCrashOK OKBlackoutUPS1 Internal FaultCrashCrashCrashCrashOK OKOKUPS1 Battery Fails——OK Hot swap batteryOK Hot swap batteryOK Hot swap battery OKOKUPS1 Internal Fault——Line-Interactive UPS Systems OK Replace UPS. System on PS2/Wall. Vulnerable to outage during UPS replacementCrash Replace UPS.OK Replace UPS. System on PS2/UPS2. Services OK during UPS replacement On-Line UPS Systems OK UPS on bypass, System on PS2/Wall. Replace UPS1. Vulnerable to outage during UPS replacementOK UPS on bypass. System on Wall. Services down* while replacing UPS1OK UPS on bypass, System on PS2/UPS2. Replace UPS1. Services OK during UPS replacement

*SmartOnline Hot-Swappable Modular 5-16KVA UPS system hardware can be hot swapped without service outage.

Multiple Power Supplies Operating in Dual (Combined, Non-Redundant) Mode

STEP 1: Determine Configuration Configuration123 Power SupplyPS1 PS2PS1 PS2PS1 PS2 Power SourceWall WallUPS1UPS1 UPS2
STEP 2: Consider Failure ScenariosSTEP 3: Consider System Status PS1 StatusUtility StatusUPS StatusSystem StatusSystem StatusSystem Status OKOKOKOKOKOK FailureOKOKReduced OutputOKOK OKBlackoutOKCrashOKOK OKBlackoutUPS1 Battery FailsCrashCrash Replace UPS1. Output reduced during UPS replacementReduced Output Replace UPS1. Output reduced during UPS replacement OKBlackoutUPS1 Internal Fault—Crash Replace UPS1Reduced Output Replace UPS1. Output reduced until UPS1 replacement OKOKUPS1 Battery Fails—OK Hot swap batteryOK Hot swap battery OKOKUPS1 Internal Fault—Line-Interactive UPS Systems Crash Replace UPS. Plug into wall until UPS replacementReduced Output Replace UPS1. Plug PS1 into wall to restore full power until UPS1 replacement. Output reduced until UPS1 replacement On-Line UPS Systems OK Replace UPS1. Both PS on UPS Bypass. Services down* while replacing UPS1OK Replace UPS1. PS1 on UPS1 Bypass circuit, vulnerable to outage. Reduced power during UPS1 replacement *SmartOnline Hot-Swappable Modular 5-16KVA UPS system hardware can be hot swapped without service outage. © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT. 5 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS. © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.5
Page 6 of the Tripp Lite H2561 user manual — Single Power Supply, or Multiple Power Supplies Operating in Redundant Mode
Page 6 · click to enlarge
Page 6

B. UPS System Battery Configuration UPS System availability, and therefore VoIP system availability, is most critically dependent upon the capacity of the UPS System's battery configuration. The number of UPS System batteries, both internal and external, determines the amount of runtime that is provided during a power outage. As mentioned previously, the runtime must fit the application. Most existing data networks are unlikely to provide reserve runtime power comparable to the public switched phone network. One has to determine a runtime estimate of what is adequate or desirable specifically for a VoIP application. Most users conclude that hours, not minutes, of backup runtime are required to maintain voice operations.

Like any estimate, a runtime estimate will be imperfect and will also be impacted by future capacity requirements (such as the addition of more phones). Therefore, it is critical that the selected UPS System can accommodate external battery packs to increase runtime as needs increase, or maintain runtime in a growing phone environment.

Runtime scalability with external battery packs also yields the ability to hot swap battery packs at the end of their useful life without a service interruption. Similar hot swap battery replacement is also the norm for the UPS System's internal batteries.

C. UPS System Power Electronics If a UPS System's power electronics fail during a utility power outage, the supported IP telephony system will obviously crash. If the UPS System failure occurs while utility power is present, however, different UPS power electronics topologies can impact IP telephony system availability in different ways.

On-Line UPS System with Internal Bypass With power present, an internal power electronics fault in an on-line UPS System will result in the load automatically being powered by a bypass path inside the UPS. As long as utility power remains present, the UPS will continue to power the connected IP telephony system without interruption and will continue to condition the power against basic power anomalies. In the event of a power outage, the system will crash.

Upon development of a bypass condition, a service interruption needs to be planned to replace the UPS System.

6 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 7 of the Tripp Lite H2561 user manual — Single Power Supply, or Multiple Power Supplies Operating in Redundant Mode
Page 7 · click to enlarge
Page 7

With power present, a battery system failure will not cause a system interruption. As long as utility power remains present, the UPS System will continue to power the connected IP telephony system without interruption and will continue to condition the power against most power anomalies. In the event of a power outage, the system will crash.

In the event of a battery system failure, the internal batteries of the UPS System and/or the external battery packs can be replaced without a service interruption.

On-Line UPS System with Internal Bypass and External Maintenance Bypass With power present, an internal power electronics fault will result in the load automatically being powered by a bypass path inside the UPS. As long as utility power remains present, the UPS will continue to power the connected VoIP system without interruption and will continue to condition the power against basic power anomalies. In the event of a power outage, the system will crash.

In the event of a bypass condition, the power electronics module of the UPS should be replaced. This can be performed while the system remains in service, as the input and output power connections are physically and electrically separated from the power module itself. This functionality is available presently in Tripp Lite's 5-16KVA SmartOnline™ Hot-Swappable Modular UPS Systems.

With power present, a battery system failure will not cause a system interruption. As long as utility power remains present, the UPS System will continue to power the connected IP telephony system without interruption and will continue to condition the power against most power anomalies. In the event of a power outage, the system will crash.

In the event of a battery system failure, the internal batteries of the UPS System and/or the external battery packs can be replaced without a service interruption.

Line-Interactive UPS System With power present, an internal power electronics fault can result in the load crashing. As the operational requirements of a line-interactive UPS System are very simple when power is present, this is extremely rare. Line-interactive power electronics failures are normally only detected when the power fails and the UPS attempts to power the load from its battery-driven inverter.

7 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 8 of the Tripp Lite H2561 user manual — Single Power Supply, or Multiple Power Supplies Operating in Redundant Mode
Page 8 · click to enlarge
Page 8

In the event of a power electronics failure, a service interruption needs to be planned to replace the UPS System.

With power present, a battery system failure will not cause a system interruption. As long as utility power remains present, the UPS System will continue to power the connected IP telephony system without interruption and will continue to condition the power against many power anomalies. In the event of a power outage, the system will crash.

In the event of a battery system failure, the internal batteries of the UPS System and/or the external battery packs can be replaced without a service interruption.

2. Resiliency to Power Anomalies The fundamental outcome one hopes for in adding UPS System support to a network is to enhance system availability. But an additional concept— resiliency—is very important as well. UPS System resiliency reflects the ability to respond positively to a number of operating variables.

A. Voltage Variation Currently, one of the most popular UPS System topologies for VoIP is provided by on-line UPS Systems. An on-line UPS System can deliver perfect power even if it encounters a very wide range of input voltages. The on-line UPS does this without relying on its battery reserves, leaving it well prepared to respond to a power outage. Because of its continuous AC-DC-AC conversion process, during an outage an on-line UPS System will also exhibit zero transfer time between power failure detection and power delivery to your equipment. On-line UPS Systems are widely acknowledged to be compatible with all types of VoIP devices.

In many networks with distributed UPS Systems, line-interactive UPS Systems are widely deployed. If input voltage levels are below the line- interactive UPS System's automatic correction capability, the UPS will switch to battery to maintain acceptable output voltage. In areas with chronic extreme brownouts, this frequent switching to battery can reduce reserve power as well as shorten battery service life—putting critical systems at risk in an outage.

While the transfer time of a line-interactive UPS System (several milliseconds) is extremely fast, this short delay has been theorized as the cause of packet losses, or even system shutdown in some applications. Depending on your power environment and the sensitivity of your IP telephony components, a line-interactive UPS System may or may not be

8 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 9 of the Tripp Lite H2561 user manual — Single Power Supply, or Multiple Power Supplies Operating in Redundant Mode
Page 9 · click to enlarge
Page 9

adequate. Generally, line-interactive UPS Systems do not pose a problem. This is the subject of some debate and is generally presented as a major issue by vendors biased towards selling online UPS Systems.

Line-interactive UPS Systems do tend to cost less than on-line UPS Systems and operate with higher efficiency, reducing electrical costs.

In theory, an on-line UPS System battery should be used less frequently due to input voltage variation, and will therefore last longer. This advantage will manifest itself more as the frequency of input voltage variation increases.

B. Harmonic Distortion Only an on-line UPS System will address input harmonic distortion. Because an on-line UPS System deconstructs and reconstructs the input power, it can deliver distortion-free power. A line-interactive UPS System will pass through input waveform distortions. Harmonic distortion tends to be an elusive “gremlin” issue when it affects connected loads.

C. Transient Spikes (or “Surges”) Both line-interactive and on-line UPS Systems address sudden increases in voltage.

D. Electromagnetic Interference While both line-interactive and on-line UPS Systems address these phenomena, an on-line UPS typically offers far superior filtering capability.

3. Manageability VoIP system availability is closely tied to UPS System manageability. To ensure continuous availability, UPS Systems must be incorporated as an integral part of a sound hardware management scheme. UPS Systems are

extremely manageable and responsive, communicating their status automatically and triggering application shutdowns prior to battery exhaustion in the event of a power outage or extreme voltage variation.

There are various methods to communicate with UPS systems, including SNMP, Web, network software and direct connection. While most users choose SNMP/Web accessory cards installed inside UPS Systems for communication, the most essential requirement is to deploy and use some method of communication. Without a management application running for your UPS Systems, the day will come when the UPS batteries fail and your system fails as your power fails. Simple management steps taken at installation can save significant problems later.

9 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 10 of the Tripp Lite H2561 user manual — Commands from the administrator to most UPS Systems include:
Page 10 · click to enlarge
Page 10

Alerts available from most UPS Systems and network cards include:

  • Voltage levels
  • Current levels
  • Temperature levels
  • Humidity levels
  • Dry contacts for fire, water, security, etc.
  • Battery capacity
  • Battery failure

Commands from the administrator to most UPS Systems include:

  • Reboot system
  • Reboot outlet(s)
  • Shut down system
  • Shut down outlet(s)
  • Run inverter/battery test

Tripp Lite presents a uniquely simple management scheme for VoIP UPS System hardware. Whether management is through an IP-addressed SNMP/Web accessory card or PowerAlert Software, Tripp Lite provides administrators with a single JAVA-based user interface. The commonality within this design approach makes it ideal for managing VoIP applications of all scales across multiple OS platforms.

During a power failure, Tripp Lite's PowerAlert Software ensures a smooth and customizable shutdown of call processing and voice messaging applications as well as the underlying operating system.

As a unique feature, Tripp Lite's PowerAlert Software and network accessory card (SNMPWEBCARD) are designed to accommodate multiple power supply and UPS System hardware deployments. With a single IP address assigned to the SNMPWEBCARD (or a single PC/Server running PowerAlert) users can manage multiple redundant UPS Systems working in tandem to provide optimal power to the IP telephony system's single or multiple power supplies.

Alternative UPS System manufacturers require each UPS to be managed individually. With these UPS Systems, there is no easy way to manage their redundant operation without expensive and space-consuming external power-switching accessories.

10 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 11 of the Tripp Lite H2561 user manual — Client Devices (phones, PC-based soft phones, etc.)
Page 11 · click to enlarge
Page 11

Tripp Lite's PowerAlert Software, version 12.5—which is part of an integrated VoIP power solution that includes a Tripp Lite UPS System—has met the Cisco Technology Developer Partner Program test criteria for interoperability with Media Convergence Servers running CallManager, versions 3.3(4) and 4.0(2). Through participation in the Cisco Technology Developer Partner Program, Tripp Lite's integrated VoIP solution provides continuous IP telephony availability to enterprise customers.

As an additional management tool, PowerAlert also offers centralized management within a NMS-style, management tool.

Another unique manageability product provided by Tripp Lite is its Watchdog Service Monitoring/Rebooting Software. Tripp Lite's Watchdog Software ensures maximum availability, eliminating call processing server downtime by automatically rebooting locked-up or poorly performing system service applications. If a locked service cannot be rebooted, Watchdog Software will automatically direct PowerAlert Software to reboot the server. If the server is non-responsive, the UPS System will power down and then restart the attached devices.

Recommended Tripp Lite UPS Systems for VoIP Applications

Establishing an adequate power protection infrastructure is essential. Again, three areas of demand must be addressed: Client, Network and Call Processing.

Client Devices (phones, PC-based soft phones, etc.)

  • IP Phones If the phone is powered by Ethernet (PoE), it is switch supported and no client UPS System is required. (Backup will be provided at the switch.)

If the phone plugs into the utility wall outlet, a UPS System is required. – Up to 4 hours - Tripp Lite UPS model: INTERNET750U

  • Soft Phones (PC based) Typically, a UPS System is required: – Up to 1 hour - Tripp Lite UPS model: OMNIVS1500XL – Up to 3 hours - Tripp Lite UPS model: OMNIVS1500XL

(Plus Tripp Lite battery pack model: BP24V28-2U • Soft Phones (Notebook PC based) – Up to 2 hours - internal notebook battery support – Up to 4 hours - Tripp Lite UPS model: INTERNET750U

11 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 12 of the Tripp Lite H2561 user manual — Recommended Tripp Lite UPS Systems for VoIP Applications
Page 12 · click to enlarge
Page 12

Networking Devices (switches, routers, etc.) Networking hardware will typically drive the most significant changes to your existing power infrastructure. With requirements spanning buildings and remote wiring closets, existing facility-wide backup plans are often impractical or unable to address the requirements of mid-size and large switches. Focused UPS System additions with extended runtime battery configurations more efficiently add the high level of availability that VoIP users demand.

Tripp Lite maintains interactive sizing and configuration resources at www.tripplite.com/selector We also welcome your contact with our technical staff via techsupport@tripplite.com or (773) 869-1234.

Basic sizing is as simple as… 1. Determining the power consumption of your equipment: Volts x Amps = VA. 2. Ensuring that the UPS System has enough power and outlets to accommodate your equipment.

Many larger routers and switches accommodate multiple power supplies. Once you have identified your power supply type and quantity, use the following details to find a specific UPS System solution for your needs:

1. Identify power supply configuration a. Single power supply or two supplies operating in redundant mode b. Dual (combined) mode 2. Determine UPS System protection scheme a. Single UPS System for both power supplies b. Single UPS System per power supply (higher availability) 3. Estimate desired runtime during power outage

12 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 13 of the Tripp Lite H2561 user manual — Call Processing Devices (servers and related storage systems)
Page 13 · click to enlarge
Page 13

Call Processing Devices (servers and related storage systems)

Typically, additional server and storage resources are added to handle call processing, voice messaging and other telephony applications. Such systems tend to reside within the data center and are multi-vendor in origin.

For configuration assistance specific to your rollout, please contact Tripp Lite. Tripp Lite maintains interactive sizing and configuration resources at www.tripplite.com/selector We also welcome your contact with our technical staff via techsupport@tripplite.com or (773) 869-1234.

Common Tripp Lite UPS Systems Recommended for VoIP Networking Device Applications (Specifications & Runtime Charts)

Input Nominal Voltage Output Capacity Outlet Outlet Input Plug Model Range Voltage (VA/Watts) Quantity Type Type RU Depth Bypass SmartOnline On-Line UPS Systems SU2200RTXL2Ua 65-138 120 2200/1600 7 6 (5-20R) 5-20P 2U 19 in. Internal (110/120) 1 (L5-20R) SU3000RTXL3U 65-138 120 3000/2400 9 4 (5-15R) 5-20P 3U 26 in. Internal (110/120) 4 (5-20R) 1 (L5-30R) SU3000RTXL3UHV 160-275 208/240 3000/2400 8 6 (6-20R) L6-20P 3U 21 in. Internal 2 (L6-20R) SU5000RT3U 156-276 208 & 120 5000/3500 16 2 (L6-20R) L6-30P 7U 21 in. Internal 2 (L6-30R) 12 (5-20R) SU5000RT3UHV 156-276 208/240 5000/3500 4 2 (L6-20R) L6-30P 5U 21 in. Internal 2 (L6-30R) SU5000RT4U 65-140 208/240 5000/3800 12 8 (5-15/20R) L14-30P 4U 30.75 in. Internal/External (L-N) & 120 2 (L6-20R) 2 (L6-30R) SU6000RT3U 156-276 208/240 6000/4200 Hardwire* Hardwire* Hardwire* 9U 26 in. Internal/External & 120 SU6000RT4U 65-140 208/240 6000/4200 12 8 (5-15/20R) L14-30P 4U 30.75 in. Internal/External (L-N) & 120 2 (L6-20R) 2 (L6-30R) SU8000RT3U 156-276 208/240 8000/6400 6 4 (L6-20R) Hardwire 6U 31.5 in. Internal/External 2 (L6-30R) SU8000RT3U1TF 156-276 208 & 120 7500/6000 18 12 (5-15/20R) Hardwire 8U 31.5 in. Internal/External 4 (L6-20R) 2 (L6-30R) SU8000RT4U 65-140 208/240 8000/5600 8 Hardwire Hardwire 4U 34 in. Internal/External (L-N) & 120 4 (5-15/20R) 2 (L6-20R) 2 (L6-30R) SU10000RT3U 156-276 208/240 10000/8000 6 4 (L6-20R) Hardwire 6U 31.5 in. Internal/External 2 (L6-30R) SU10000RT3U2TF 156-276 208 & 120 10000/8000 30 24 (5-15/20R) Hardwire 10U 31.5 in. Internal/External 4 (L6-20R) 2 (L6-30R) SU10KRT3U 156-276 208/240 10000/8000 Hardwire Hardwire Hardwire 9U 31.5 in. Internal/External & 120 SU16000RT4U 65-140 208/240 16000/11200 +13 Hardwire Hardwire 8U 40.5 in. Internal/External (L-N) & 120 5 (5-15/20R) 2 (L6-30R) 6 (C19)

* SU6000RT3U can provide outlets when used with optional back panel accessory (SUPDM12) which provides two L6-20R, one L6-30R and ten 5-20R outlets and a cord with a L6-30P input plug.

13 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

UPS System Specifications

Page 14 of the Tripp Lite H2561 user manual — Call Processing Devices (servers and related storage systems)
Page 14 · click to enlarge
Page 14

SmartPro® Line-Interactive UPS Systems

Input Nominal Voltage Output Capacity Outlet Outlet Input Plug Model Range Voltage (VA/Watts) Quantity Type Type RU Depth Bypass SMART1500CRMXL 83-145 120 1500/1440 8 8 (5-15R) 5-15P 2U 19 in. Internal SMART2200RMXL2U 120 120 2200/1600 8 4 (5-15R) 5-20P 2U 17 in. None 4 (5-20R) SMART2200CRMXL 83-145 120 2200/1900 8 4 (5-15R) 5-20P 4U 16.75 in. Internal SMART3000RM2U 120 120 3000/2250 9 4 (5-15R) L5-30P 2U 17 in. None 4 (5-20R) 1 (L5-30R) SMART3000CRMXL 83-145 120 3000/2880 9 8 (5-15R) L5-30P 4U 16.75 in. Internal 1 (L5-30R) SMART5000XFMRXL 208 208 & 120 5000/3750 11 8 (5-20R) L6-30P 3U 23 in. None 2 (L6-20R) 1 (L6-30R)

UPS System Extended Runtime SmartOnline On-Line UPS Systems Half load (Watts) Runtime (minutes) Non-Expandable Battery Pack Expandable Battery Pack* Full Load (Watts) with included batteries 1 2 3 4 BP48V24-2U BP48V60RT-3U SU2200RTXL2Ua Extended Runtime (Non-Expandable) (Expandable) 800 14 56 117 266 378 530 1600 4.5 23 50 122 186 246 BP72V15-2U BP72V28RT-3U SU3000RTXL3UHV & SU3000RTXL3U Extended Runtime (Non-Expandable) (Expandable) 1200 17 41 78 158 252 327 2400 6 17 33 69 108 150 BP240V10RT-3U SU5000RT3UHV & SU5000RT3U Extended Runtime (Expandable) 1750 20 N/A 73 161.6 225.8 291 3500 8 N/A 31 70 100 131

SU5000RT4U Extended Runtime 1900 14 N/A 97.4 158.4 221.5 285.5 3800 6 N/A 42.5 70.7 100.7 131.7 BP240V10RT-3U SU6000RT3U Extended Runtime (Expandable) 2100 37 N/A 79 131 174 222 4200 15 N/A 37 58 79 104

SU6000RT4U Extended Runtime 2100 24 N/A 86.6 141.4 198.2 256 4200 9 N/A 36.8 61.5 87.8 115.2 BP240V10RT-3U SU8000RT3U Extended Runtime (Expandable) 3200 15 N/A 46 76 109 142 6400 6 N/A 18 32 46 60

SU8000RT3U1TF Extended Runtime 3200 15 N/A 46 76.4 108.7 142 6400 6 N/A 18.6 31.6 45.6 60.4 BP192V12-3U SU8000RT4U Extended Runtime (Expandable) 2800 12 N/A 47 100 141.1 183.8 5600 5 N/A 19 42.8 61.5 81.1 BP240V10RT-3U SU10KRT3U, SU10000RT3U, & SU10000RT3U2TF Extended Runtime (Expandable) 4000 10 N/A 35.1 58.6 83.8 110 8000 4 N/A 13.7 23.5 34.1 45.3 BP192V18-4U SU16000RT4U Extended Runtime (Expandable) 5600 12 N/A 42.2 70.2 100 130.9 11200 5 N/A 17.1 29.2 42.2 55.9 * Included batteries are contained either internally within the UPS system or are included as an external module, depending on model. ** Battery packs which are expandable can be connected together for increased runtime. Call Tripp Lite's Application Specialists at (773) 869-1236 for additional extended runtime solutions to fit your specific load requirements.

14 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

Page 15 of the Tripp Lite H2561 user manual — (773) 869-1234 • www.tripplite.com
Page 15 · click to enlarge
Page 15

SmartPro Line-Interactive UPS Systems Half load (Watts) Runtime (minutes) Non-Expandable Battery Pack Expandable Battery Pack* Full Load (Watts) with included batteries 1 2 3 4 BP48V24-2U BP48V48RT4U SMART1500CRMXL Extended Runtime (Non-Expandable) (Expandable) 720 28.5 70.6 195.5 349.2 504.2 658.8 1440 11 28.1 82.1 152 225 299.3 BP48V24-2U BP48V60RT-3U SMART2200RMXL2U Extended Runtime (Non-Expandable) (Expandable) 800 16 62 128 264.3 403.4 542.9 1540 6 24.5 52.6 113 177.3 243.5 BP48V24-2U BP48V48RT4U SMART2200CRMXL Extended Runtime (Non-Expandable) (Expandable) 950 28.5 68.8 154 265.4 378.7 492.5 1900 11 27.7 64.5 114.8 167.7 222 BP48V24-2U BP48V60RT-3U SMART3000RM2U Extended Runtime (Non-Expandable) (Expandable) 1120 21.2 59.9 124.3 256.2 391.5 527.2 1600 8.5 24.9 53.4 114.5 179.7 246.6 BP48V24-2U BP48V48RT4U SMART3000CRMXL Extended Runtime (Non-Expandable) (Expandable) 1440 19 35.4 81.7 144.3 209.5 276 2880 7.5 14.7 35.2 63.8 94.5 126.4 BP48V60RT-3U SMART5000XFMRXL Extended Runtime (Expandable) 1875 27 N/A 63 117.9 175.8 235.2 3750 10 N/A 24.4 47 71.7 97.6 * Battery packs which are "expandable" can be connected together for increased runtime. Call Tripp Lite's Application Specialists at (773) 869-1236 for additional extended runtime solutions to fit your specific load requirements.

About the author: David Slotten is Director of Product Management at Tripp Lite. Mr. Slotten joined Tripp Lite in 1990 and has extensive experience in the sale, marketing, engineering and development of power protection systems. Mr. Slotten has an MBA from Lake Forest Graduate School of Management and a bachelor’s degree from the University of Wisconsin.

For Additional VoIP and Internet Telephony Application Assistance Call Tripp Lite's Application Specialists at (773) 869-1236

  • Tripp Lite World Headquarters
  • 1111 W. 35th Street
  • Chicago, IL 60609 USA

(773) 869-1234 • www.tripplite.com

Tripp Lite's PowerAlert Software, version 12.5, has tested compatible with Cisco CallManager, versions 4.0 and 4.1, Cisco 7600 Series Routers, 7500 Series Routers and Catalyst 65XX Layer 3 Switch. Tripp Lite PowerAlert Software, version 12, has tested compatible with Cisco CallManager, versions 3.3(4)-MCS and 4.0(2)-MCS. The Cisco Compatible logo signifies that Tripp Lite's product has undergone interoperability testing by Tripp Lite together with Cisco and a third-party test house based on testing criteria set by Cisco. Tripp Lite is solely responsible for the support and warranty of its product. Cisco makes no warranties, express or implied, with respect to Tripp Lite's product or its inter-operation with the listed Cisco product(s) and disclaims any implied warranties of merchantability, fitness for a particular use or against infringement.

Tripp Lite is a Cisco Technology Developer Partner in the Cisco Technology Developer Program.

Cisco, Cisco Systems, the Cisco Systems logo, and the Cisco Square Bridge logo are registered trademarks or trademarks of Cisco Systems, Inc. and/or its affiliates in the U.S. and certain other countries.

15 © 2008 TRIPP LITE. ALL RIGHTS RESERVED. THE POLICY OF TRIPP LITE IS ONE OF CONTINUOUS IMPROVEMENT.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.

200801210 95-2914

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Tripp Lite H2561

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Tripp Lite H2561

Be the first to ask — other owners or our team will answer.

Original document

Tripp Lite H2561 manual PDF

15 pages·133 KB·Telephone·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…