Instruction/ maintenance manual of the product GETB Trane
Go to page of 32
WSHP -S VN08B-EN F ebr uary 2006 Models “ A ” and later Design S equence Installation Owner Diagnostics V er tical Stac k W at er -Sour ce Heat Pump Model GETB GETB 0 09-036 – 60 HZ 0 09-036 –.
© 2006 American Standard Inc All r ights reserved WSHP-SVN08B-EN Notice NO TICE: W arnings and Cautions appear at approp riate sections through out this manual. Re ad these careful ly . WARNING – Indicates a potentially hazardous situation whic h, if not av oided, could result in death or serious injur y .
WSHP-SVN08B-EN 3 Contents Installation/Star tup/Commissioning 4 Pre-installation Chec klist 4 General Information 5 Dimensions/W eights 6 Installation Instructions 9 Electrical Requirements 18 Pre-Sta.
4 WSHP-SVN08B-EN W ARNING Fiberglass W ool! Pr oduct contains fiberglass wool. Disturbing the insulation in this product duri ng installation, maintena nce or repair will expose y ou to airborne particles of glass wool fibe rs and ceramic f ibers known to the state of California to cause cancer thr ough inhalation.
WSHP-SVN08B-EN 5 Unit Na meplate The unit namepl ate is located at the front of the unit. It includes the un it model number, serial number, electri- cal characteristics, refrigerant charge, and other pertinent unit data. Compressor Nameplate The nameplate for the compressors are located on th e compressor shell.
6 WSHP-SVN08B-EN ALL O W 36" (914 mm) A T UNIT FRONT FOR CHASSIS REMO V AL RS D T a ble 1: Unit w eights Size Shipping Weight with pallet (lb) Shipping Weight w/o pallet (lb) Cabinet 009 135 115 .
WSHP-SVN08B-EN 7 SWA GE 3" (76) G G H J UNITS WITH TOP DISCHARGE ARE 80" (2032) IN HEIGHT ALL OTHER UNITS ARE 88" (2235) IN HEIGHT FROM 96" (2438) T O 120" (3048) 2 1/2" (63.5) E F DRAIN CONNECTION D 4 3/4" (121) 60" (1524) 3/4" (1 9) O.
8 WSHP-SVN08B-EN RETURN-AIR OPENING FLANGE ON CABINET RETURN-AIR OPENING FLANGE ON CABINET 2 X 4 STUD A B Unit Size 09 012 015 018 024 036 A 19 1/4” (489) 23 1/4” (591) 27 1/8” (689) B 44 1/8”.
WSHP-SVN08B-EN 9 General Installation Checks The checklist below is a summary of the steps required to successfully in- stall a unit. This checklist is intended to acquaint the installing personnel wi th procedures req uired in the installation process.
10 WSHP-SVN08B-EN FL OOR FL OOR 3" SW AGE W ARNING Impr oper Unit Lif t! T e st lif t unit appr oximatel y 24 inc hes to verify pr oper center of gravity lif t point.
WSHP-SVN08B-EN 11 Field Installed Power Wiring Power wiring to the equipment must conform to National and Local Electric Codes (NEC) by a professional electri- cian. WARNING Liv e Electrical Components! During installation, testing, ser- vicing and troubleshoo ting of this product, it ma y be necessar y to work with live electrical compo- nents.
12 WSHP-SVN08B-EN RETURN-AIR OPENING FLANGE ON CABINET RETURN-AIR OPENING FLANGE ON CABINET 2 X 4 STUD A B Unit Size 09 012 015 018 024 036 A 19 1/4” (489) 23 1/4” (591) 27 1/8” (689) B 44 1/8.
WSHP-SVN08B-EN 13 1 Secure the door frame to the side studs using the holes located in the door frame and field provided screws, Figure 6 . Note: If the gap between the door frame, and the side stud is over 1/16- inch, place a shim in between the door frame and the stud to prevent the door frame from bending/denting.
14 WSHP-SVN08B-EN WARNING Liv e Electrical Components! During installation, testing, ser- vicing and troublesh ooting of this product, it m ay be necessary to work with liv e electrical compo- nents.
WSHP-SVN08B-EN 15 Using Antifreeze In areas of the coun try where entering water temperatures drop below 45°F or where pipi ng is being run through areas subject to freezing, the loop must be freeze protected by using an approved antifreez e solution to pre- vent the earth loop water from freez- ing inside the heat exc hanger .
16 WSHP-SVN08B-EN Low Voltage Wiring Factory ordered thermostats and zone sensors are pre-wired with a quick connecting plug. 1 After installing the cabinet assem- bly, simply plu g the male portion of thermostat/zone sens or plug into the female port ion of the plug locat- ed inside the unit’s junction box .
WSHP-SVN08B-EN 17 Blower Motor Sp eed Retrofit Motors installed in the unit have mul- tiple speed config urations. To modify the rpm of the motor, the following steps ma y be followed. WARNING Hazardous V oltage! Disconnect all electric po wer , in- cluding remote disconnects and disc harge motor start/run capaci- tors before ser vici ng.
18 WSHP-SVN08B-EN Electrical Req uirements T able F2: Bl o wer External Static P ressure with Return Air Door (RAD), with filter 1 The NO "Ducted" option is for no n-ducted (free return) units. 2 Units specified as "non-ducted" (free return) are factory wired to low-speed.
WSHP-SVN08B-EN 19 P re-Star t Chec klist Pre-Start-up Checklist Before energizing the un it, the following system devices must be checked: ____ Is the high voltage power supply correct and in accordan.
20 WSHP-SVN08B-EN Initial Unit Start-up Start-up with deluxe cont rols is included below: Note: Start-up for the Tracer TM ZN510 controll er may be found in WSHP-IOP-2. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components.
WSHP-SVN08B-EN 21 Table OP-1: Operating Pressures GENERAL: There are many variable s (airflow, air temperatures) in an air conditioning system that will a ffect operating re- frigerant pressures and temperatures. The chart below shows approximate conditions and is based on air flow at the rated SCFM, entering air at 80.
22 WSHP-SVN08B-EN Operating P ressure Table OP-1: Operating Pressures Operating Data Model Entering Water Temp, °F Water Flow GPM Cooling Heating Suction Pressure, PSIG Discharge Pressure, PSIG Water Temp Rise, °F Air Temp Drop, °FDB Suction Pressure, PSIG Discharge Pressure, PSIG Water Temp Drop, °F Air Temp Rise, °FDB GET 018 35 3.
WSHP-SVN08B-EN 23 Operating P ressures Water Pressure Drop Table 7 should be used to define feet of hea d/pressure drop. Note: To calculate feet of hea d, when using gauges tha t read in PSIG, m ultiply PSI by 2.31. Water Volume Table 8 is provided for use in calculat ing glycol requirement s for the unit.
24 WSHP-SVN08B-EN Star t-up Chec klist and Log Installing Contractor: Use this form to thorou ghly check-out the system and units before and during start- up. (This f orm need not be retu rned to the factor y un less requested during technical service support).
WSHP-SVN08B-EN 25 Prev en ti ve M ai nt en an ce Maintenance on the unit is s implified with the following preventive sugge s- tions: Filter maintenance must be performed to assure proper opera tion of the equipment. Filte rs should be inspect- ed at least every three months, and re- placed when it is evident they are dirty.
26 WSHP-SVN08B-EN Warranty Information Standard Warranty The standard water-source h eat pump warranty is Tran e’s parts-only warranty, running 12-month s from star- tup, not to exceed 18-months from shipment . Extended Warranty The optional extended warran ty is a second thro ugh fifth year warranty.
WSHP-SVN08B-EN 27 WARNING Hazardous S er vice P rocedures! The maintenance and tr ouble shooting procedu res recommend- ed in this section of the manual could result in e xposure to electri- cal, mec hanical or other potential safety hazar ds. Al ways refer to the safety warnings pro vided throughout this manual concern- ing these pr ocedures.
28 WSHP-SVN08B-EN T r oubleshooting Chec klist Problem Heating Cooling Cause Correction No respons e to any thermost at setting X X Main power of f Check fuses X X Defective co ntrol transformer Repla.
WSHP-SVN08B-EN 29 60 59 58 57 56 55 54 53 52 51 50 49 46 48 47 45 44 41 43 42 40 39 38 37 36 35 34 33 32 31 30 29 19 24 28 27 26 25 23 22 21 20 18 17 16 15 14 13 12 11 10 8 9 7 6 5 2 4 3 1 W ARNING A .
30 WSHP-SVN08B-EN Unit Wiring Delux e Diagram 208V -50/60 Hz-1PH.
WSHP-SVN08B-EN 31 Unit Wiring ZN51 0 Diagram 230V -50/60 Hz-1PH.
T rane has a policy of con tinuous product and data improveme nt and reserves the right to c hange design and specifications without n otice. Literature Order Number WSHP-SVN 08B-EN File Number SV -UN- WSHP-SVN08B-EN -0206 Supersedes SV -UN- WSHP-SVN08A-EN -1 1 05 Stoc king Location Inland T rane A business of American Standard Companies www .
An important point after buying a device Trane GETB (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Trane GETB yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Trane GETB - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Trane GETB you will learn all the available features of the product, as well as information on its operation. The information that you get Trane GETB will certainly help you make a decision on the purchase.
If you already are a holder of Trane GETB, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Trane GETB.
However, one of the most important roles played by the user manual is to help in solving problems with Trane GETB. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Trane GETB along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center