Instruction/ maintenance manual of the product HFC R-410A Toshiba
Go to page of 108
4-way ceiling cassette MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H 2-way ceiling cassette MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP01.
.
3 Super Modular Multi System Contents 1. Outline of T oshiba Super Modular Multi System (S-MMS) .................................................................................. 4 2. Summary of system equipment .......................................
4 1. Outline of T oshiba Super Modular Multi System (S-MMS) Branching Combination of line and header branching is highly flexible. This allows for the shortest design route possible, ther eby saving on installation time and cost. Line/header branching after header branching is only available with T oshiba Super MMS.
5 • Non-polarized control wiring between outdoor and indoor units • Wiring diagnosis system Use the switches on the micro processor PCB of the outdoor unit. • Detects wiring to the indoor unit a4 which should not be in system A. • b4 is missing in system B.
6 Compact The design of the modular T oshiba Super MMS outdoor unit allows for easy unit manoeuvring into any standard lift. Its compactness also allows it to be easily installed in limited spaces. Largest system capacity T oshiba Super MMS can be combined up to 48 hp (135 kW) as one refrigerant system.
7 2. Summary of system equipment T echnical specifications - outdoor units Rating hp 5 6 8 10 12 Cooling only model MMY -MAP 0501T8 0601T8 0801T8 1001T8 1201T8 Heat pump model MMY -MAP 0501HT8 0601HT8 0801HT8 1001HT8 1201HT8 Cooling capacity kW 14.0 16.
8 Outdoor unit model line-up - cooling only units hp Model No. of Inverter Q’ty Inverter Q’ty Inverter Qty Inverter Q’ty Inverter Q’ty (capacity MMY - combined 5 hp used 6 hp used 8 hp used 10.
9 Outdoor unit model line-up - heat pump units hp Model No. of Inverter Q’ty Inverter Q’ty Inverter Qty Inverter Q’ty Inverter Q’ty (capacity MMY - combined 5 hp used 6 hp used 8 hp used 10 hp.
10 4. T echnical specifications - indoor units Model type Model Capacity Cooling Heating Height Width Depth Weight name code capacity capacity mm mm mm kg kW kW 4-way ceiling cassette MMU-AP0091H 1 2.8 3.2 256 840 840 20 MMU-AP0121H 1.25 3.6 4.0 MMU-AP0151H 1.
11 5. Remote contr oller Appearance Application Function Wired r emote controller Connected to indoor unit • Start/stop • Mode change RBC-AMT31E • T emperature adjustment • Air flow adjustmen.
12 Appearance Application Function Infrared r emote controller Connected to indoor unit • Start/stop • Mode change WH-H2UE • T emperature adjustment • Air flow adjustment (5 steps) • Clock • Timer function - ON/OFF timer (10 min.
13 3. Basic system configuration System legend (example) 8 hp system • Max. number of indoor units: 13 units • Indoor unit capacity code: Min. 4 Max. 10.8 Capacity code - total 10.4 T otal number of units - 13 Remote controller 8HP Outdoor unit Capacity code over the branch (0.
14 10 hp system • Max. number of indoor units: 16 units • Indoor unit capacity code: Min. 5 Max. 13.5 Capacity code - total 12.8 T otal number of units - 16 Remote controller 10HP Outdoor unit Ind.
15 20 hp system • Max. number of indoor units: 33 units • Indoor unit capacity code: Min. 10 Max. 27 Capacity code - total 26.75 T otal number of units - 19 10HP 10HP Remote controller Outdoor uni.
16 30 hp system • Max. number of indoor units: 48 units • Indoor unit capacity code: Min. 15 Max. 40.5 Capacity code - total 40 T otal number of units - 28 10HP Remote controller Outdoor unit Indo.
17 40 hp system • Max. number of indoor units: 48 units • Indoor unit capacity code: Min. 20 Max. 54 Capacity code - total 53.75 T otal number of units - 32 Remote controller Outdoor unit Indoor u.
18 48 hp system • Max. number of indoor units: 48 units • Indoor unit capacity code: Min. 24 Max. 64.8 Capacity code - total 61.9 T otal number of units - 40 Remote controller Outdoor unit Indoor .
19 4. Equipment selection pr ocedure 1. Selection flow chart 1. Determination of indoor air conditioning load 2. Preliminary selection of indoor units 3. Preliminary selection of outdoor unit with indoor units 4. Capacity correction for piping length/height between indoor and outdoor units 5.
20 3. Cooling/heating capacity characteristics Cooling capacity calculation method: Requir ed cooling capacity = cooling capacity x factor ( , , , , *1 ) kW Indoor air wet bulb temperature vs. capacity corr ection value Indoor air wet bulb temperature (°C) Outdoor air dry bulb temperature vs.
21 Connecting pipe length and lift differ ence between indoor and outdoor units vs. capacity correction value Indoor unit Correction of outdoor unit diversity Indoor unit total capacity ratio .
22 Heating capacity calculation method: Requir ed heating capacity = heating capacity x factor ( , , , , *1 , *2 ) k W Indoor air dry bulb temperature vs. capacity corr ection value Indoor air dry bulb temperature (°C) Outdoor air wet bulb temperature vs.
23 Connecting pipe length and lift differ ence between indoor and outdoor units vs. capacity correction value Correction of outdoor unit diversity Indoor unit total capacity ratio (%) Outdoor .
24 Capa city corr ect ion f or fr osting on the outd oor h eat e xchan ger (h eatin g mod e) Correct the heating capacity when fr ost was found on the outdoor heat exchanger .
25 Example of equipment selection The following shows an example of equipment selection based upon a building model. Fig. 1 - Overview of building model Outside view Floor configuration Non-air conditioning zone • Steel frame, reinfor ced concrete building, four floors above ground.
26 Procedur e and r esult of equipment selection 1. Procedur e of equipment selection a. Calculate cooling for every room. b. Select an indoor unit to match the cooling load for every room from the table on page 10. c. Select the outdoor module to match the indoor units selected in point b.
27 Example: Equipment selection based on system load profile Since the five rooms on the 4th floor face dif ferent dir ections, their hourly cooling load profile will also be dif ferent. W e select each indoor unit based on the individual room peak load.
28 Schematic diagram MMY -AP2801T8 MMY -AP2801HT8 Outdoor unit 1st branching joint 3rd branching joint 5th branching joint 4th branching joint 2nd branching joint Indoor unit MMU-AP0241H Indoor unit M.
29 5. Refrigerant piping design 1. W ar nings on r efrigerant leakage Check of concentration limit The room in which the air conditioner is to be installed r equires a design that ensur es that the concentration of refrigerant gas will not exceed a set limit if ther e is a leak.
30 Note 3: The minimum indoor floor area compar ed with the amount of refrigerant is r oughly as follows (when the ceiling is 2.7 m high): T otal refrigerant amount 2.
31 3. Allowable length/height dif ference of r efrigerant piping Note: In case of connecting method in Example 2, a large amount of refrigerant and r efrigerant oil may return to the master unit. Therefore, set the T -shape joint so that oil does not enter directly .
32 4. Selection of r efrigerant piping Pipe size of outdoor unit (T able 1) Model name MMY - Gas side Liquid side MAP0501T8 MAP0501HT8 Ø5/8” Ø3/8” MAP0601T8 MAP0601HT8 Ø3/4” Ø3/8” MAP0.
33 5. Charging r equirement with additional r efrigerant After the system has been evacuated, replace the vacuum pump with a r efrigerant cylinder and char ge the system with additional refrigerant.
34 6. Wiring design 1. General (1) Perform wiring of the power supply in conformance with the regulations of the local electric company . (2) For the control wir es connecting indoor units, outdoor units, and between indoor and outdoor units, use of double-core shielded wir es is recommended to pr event noise disturbance.
35 4. Indoor unit power supply (must be independent fr om outdoor unit power) Model Power supply wiring Wire size Field-supplied fuse All models of indoor units 2.
36 6. Contr ol wiring diagram 1. All control wiring is 2-cor e non-polarity wire. 2. Be sure to use shielded wir e for the following wiring to prevent noise disturbance. • Outdoor -outdoor/indoor -indoor/outdoor -indoor control wiring, central control wiring.
37 7. Design T ype Model Nominal voltage V oltage range Fan motor Power supply (V -ph-Hz) Min. Max. kW FLA MCA MOCP 4-way ceiling cassette MMU-AP0091H 230-1-50 198 264 0.060 0.20 0.25 15 MMU-AP0121H 230-1-50 198 264 0.060 0.20 0.25 15 MMU-AP0151H 230-1-50 198 264 0.
38 Single outdoor unit Heat pump Cooling only Nominal V oltage Compressor Fan motor Power supply MMY - MMY - voltage range (V -ph-Hz) Min. Max. RLA kW FLA MCA MOCP MAP0501HT8 MAP0501T8 400-3-50 342 457 4.0 + 4.0 0.60 0.8 16.5 20 MAP0601HT8 MAP0601T8 400-3-50 342 457 4.
39 7. Contr ols A range of contr ols to meet various system needs As the size of the building increases so does the number of air conditioning units r equired. The multiple air conditioning system Super MMS ensures ener gy savings and comfort by allowing contr ol of multiple units requiring differ ent loads.
40 1. Applications for indoor r emote controller Basic function System diagram Model 1-1 Individual control • Wired remote contr oller Air conditioner is individually RBC-AMT31E operated at a distance.
41 2. Application contr ols for central remote contr oller Basic function System diagram Model 2-1 Central management • Central remote controller controller for 64 units TCB-SC642TLE Indoor remote c.
42 Basic function System diagram Model 2-3 Remote central control • Central remote controller without indoor remote TCB-SC642TLE controller Indoor remote controller • Wired remote contr oller RBC-.
43 3. Application contr ol for network Basic function System diagram Model 3-1-1 LONWORKS • LON Gateway TCB-1FLN**** • “1:1 model” connection interface TCB-PCNT30TLE (RAV -SM560KRT -E, SM800KR.
44 Basic function System diagram Model 3-2-1 T ouch screen controller • T ouch screen controller BMS-TP5120ACE • Intelligent server BMS-LSV2E BMS-STC01E • TCS-Net relay interface BMS-1FLSV1E •.
45 8. Accessories Indoor unit accessories Remote controller Indoor unit type Accessory name Model Applicable model 4-way ceiling cassette Wir ed remote controller RBC-AMT31E Common parts for 2-way cei.
46 9. T echnical specifications Indoor units 4-way ceiling cassettes Model MMU-AP 0091H 0121H 0151H 0181H 0241H 0271H 0301H 0361H 0481H 0561H Cooling capacity* kW 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 Heating capacity kW 3.2 4.0 5.0 6.3 8.0 9.0 10.
47 Indoor units 2-way ceiling cassettes Model MMU-AP 0071WH 0091WH 0121WH 0151WH 0181WH 0241WH 0271WH 0301WH Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
48 Indoor units 1-way ceiling cassettes Model MMU-AP 0071YH 0091YH 0121YH 0151SH 0181SH 0241SH Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
49 Indoor units Standard ducted units Model MMD-AP 0071BH 0091BH 0121BH 0151BH 0181BH 0241BH 0271BH 0301BH 0361BH 0481BH 0561BH Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.
50 Indoor units High-pressur e ducted units Model MMD-AP 0181H 0241H 0271H 0361H 0481H 0721H 0961H Cooling capacity* kW 5.6 7.1 8.0 11.2 14.0 22.4 28.0 Heating capacity kW 6.3 8.0 9.0 12.5 16.0 25.0 31.5 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
51 Indoor units Slim duct units Model MMD-AP 0071SPH 0091SPH 0121SPH 0151SPH 0181SPH Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
52 Indoor units Ceiling-suspended units Model MMC-AP 0151H 0181H 0241H 0271H 0361H 0481H Cooling capacity* kW 4.5 5.6 7.1 8.0 11.2 14.0 Heating capacity kW 5.0 6.3 8.0 9.0 12.5 16.0 Electrical data Power supply V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
53 Indoor units High-wall units (1 Series) Model MMK-AP 0071H 0091H 0121H 0151H 0181H 0241H Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
54 Indoor units High-wall units (2 Series) Model MMK-AP 0072H 0092H 0122H Cooling capacity* kW 2,2 2,8 3,6 Heating capacity kW 2,5 3,2 4,0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range.
55 Indoor units Floor -mounted console units Model MML-AP 0071H 0091H 0121H 0151H 0181H 0241H Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
56 Indoor units Concealed chassis units Model MML-AP 0071BH 0091BH 0121BH 0151BH 0181BH 0241BH Cooling capacity* kW 2.2 2.8 3.6 4.5 5.6 7.1 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
57 Indoor units Floor -mounted cabinet units Model MMF-AP 0151H 0181H 0241H 0271H 0361H 0481H 0561H Cooling capacity* kW 4.5 5.6 7.1 8.0 11.2 14.0 16.0 Heating capacity kW 5.0 6.3 8.0 9.0 12.5 16.0 18.0 Electrical data Power supply V -ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only Operating current A 0.
58 Outdoor units Rating hp 5 6 8 10 12 Cooling only model MMY MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 Heat pump model MMY MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Cooling capacity kW 14.
59 Outdoor units (combination) Rating hp 14 16 18 20 Cooling only system MMY AP1401T8 AP1601T8 AP1801T8 AP2001T8 Heat pump system MMY AP1401HT8 AP1601HT8 AP1801HT8 AP2001HT8 Outdoor unit type Inverter.
60 Outdoor units (combination) Rating hp 22 22 Cooling only system MMY AP2201T8 AP2211T8 Heat pump system MMY AP2201HT8 AP2211HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Outdoor.
61 Outdoor units (combination) Rating hp 24 24 Cooling only system MMY AP2401T8 AP2411T8 Heat pump system MMY AP2401HT8 AP2411HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Outdoor.
62 Outdoor units (combination) Rating hp 26 28 30 Cooling only system MMY AP2601T8 AP2801T8 AP3001T8 Heat pump system MMY AP2601HT8 AP2801HT8 AP3001HT8 Outdoor unit type Inverter Inverter Inverter Inv.
63 Outdoor units (combination) Rating hp 32 32 Cooling only system MMY AP3201T8 AP3211T8 Heat pump system MMY AP3201HT8 AP3211HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Inverte.
64 Outdoor units (combination) Rating hp 34 34 Cooling only system MMY AP3401T8 AP3411T8 Heat pump system MMY AP3401HT8 AP3411HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Inverte.
65 Outdoor units (combination) Rating hp 36 36 Cooling only system MMY AP3601T8 AP3611T8 Heat pump system MMY AP3601HT8 AP3611HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Inverte.
66 Outdoor units (combination) Rating hp 38 40 Cooling only system MMY AP3801T8 AP4001T8 Heat pump system MMY AP3801HT8 AP4001HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Inverte.
67 Outdoor units (combination) Rating hp 42 44 Cooling only system MMY AP4201T8 AP4401T8 Heat pump system MMY AP4201HT8 AP4401HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Inverte.
68 Outdoor units (combination) Rating hp 46 48 Cooling only system MMY AP4601T8 AP4801T8 Heat pump system MMY AP4601HT8 AP4801HT8 Outdoor unit type Inverter Inverter Inverter Inverter Inverter Inverte.
69 10. Fan characteristics In case of squar e duct flange of discharge section MMD-AP0071BH, AP0091BH Legend 1. High static pressur e 2H tap 2. High static pressur e 1H tap 3.
70 MMD-AP0241BH, AP0271BH MMD-AP0361BH MMD-AP0301BH MMD-AP0481BH, AP0561BH Standard air flow 317 l/s (1140 m 3 /h) Standard air flow 350 l/s (1260 m 3 /h) Standard air flow 550 l/s (1980 m 3 /h) St.
71 MMD-AP0181H MMD-AP0361H MMD-AP0241H, AP0271H MMD-AP0481H High-pr essure ducted unit Standard air flow 250 l/s (900 m 3 /h) Standar d air flow 367 l/s (1320 m 3 /h) Standard air flow 583 l/s (2100 m 3 /h) Standard air flow 444 l/s (1600 m 3 /h) Legend 1.
72 MMD-AP0721H MMD-AP0961H 1. High static pressur e tap 2. Medium static pressur e tap 3. Low static pressur e tap Add an air flow damper to the air supply duct, and adjust the air flow in the range from 80% to 120% of the standard air flow rate.
73 MMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unit 300 0 10 20 30 40 50 60 400 500 600 700 400 0 10 20 30 40 50 60 500 600 700 800 400 0 10 20 30 40 50 60 500 600 700 900 800 300 0 10 20 30 40 5.
74 MMD-AP0071SPH, AP0091SPH Slim duct unit - with filter attached 1 2 3 4 5 6 7 8 0 9 ! @ # % $ ^ 1 2 3 4 5 6 7 8 0 9 ! @ # % $ ^ 1 2 3 4 5 6 7 8 0 9 ! @ # % $ ^ 1 2 3 4 5 6 7 8 0 9 ! @ # % $ ^ 300 0.
75 11. Dimensional drawings Indoor unit - 4-way ceiling cassette All dimensions are given in mm. Legend 1. Control box 2. Hanging bolt pitch 3. Overall panel dimension 4. Air inlet 5. Air outlet (4-way) 6. Ceiling opening 7. Hanging bolt M10 or W3/8 field-supplied 8.
76 Indoor unit - 2-way ceiling cassette MMU-AP0071WH, AP0091WH, AP0121WH All dimensions are given in mm. Legend 1. Centre of main unit 2. Centre of panel 3. Control box 4. Hanging bolt pitch 5. Unit dimension 6. Ceiling opening 7. Overall panel dimension 8.
77 Indoor unit - 2-way ceiling cassette MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH All dimensions are given in mm. Legend 1. Centre of main unit 2. Centre of panel 3. Control box 4. Hanging bolt pitch 5. Unit dimension 6. Ceiling opening 7. Overall panel dimension 8.
78 Indoor unit - 2-way ceiling cassette MMU-AP0481WH All dimensions are given in mm. Legend 1. Centre of main unit 2. Centre of panel 3. Control box 4. Hanging bolt pitch 5. Unit dimension 6. Ceiling opening 7. Overall panel dimension 8. Air outlet (2-way) 9.
79 Indoor unit - 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YH All dimensions are given in mm. Legend 1. Overall panel dimension 2. Ceiling opening 3. Centre of panel 4. Power supply connection 5. Drain pipe connection (VP25) 6. Refrigerant pipe connection (gas Ø3/8”) 7.
80 Indoor unit - 1-way ceiling cassette MMU-AP0151SH, AP0181SH, AP0241SH All dimensions are given in mm. Legend 1. Ø150 knockout hole (for air intake) 2. Overall panel dimension 3. Ceiling opening 4. Centre of panel 5. Air inlet 6. Air outlet 7. Pitch 200 x N 8.
81 Indoor unit - standar d ducted unit MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH, AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH All dimensions are given in mm. Legend 1. Ø125 knockout hole (for air intake) 2. 10-Ø4 tapping screw Ø160 3.
82 Indoor unit - high-pr essure ducted unit MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0271H, AP0961H All dimensions are given in mm. Legend 1. Power supply/communication piping (Ø26) (under control box) 2. Hanging bolt slot (4-Ø2 x 72) 3. Hanging bolt mounting pitch 4.
83 Indoor unit - slim duct unit MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH 511 67 67 910 372 359 422 502 103 31 163 33 40 21 803 57 210 845 168 21 21 21 120 805 19 645 168 20 80 59 80 4.
84 Indoor unit - ceiling-suspended unit MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H All dimensions are given in mm. Legend 1. Hanging position 2. Remote controller cable conduit (knockout hole) 3. Power supply cable inlet (knockout hole) 4.
85 Indoor unit - high-wall unit (1 Series) MMK-AP0071H, AP0091H, AP0121H All dimensions are given in mm. Legend 1. (Installation board) 2. T op of installation board 3. W ood screw slot 15-6 x 30 4. Anchor bolt slot 10-10 x 20 5. Air outlet Air flow direction adjustable (up/down/left/right) 6.
86 Indoor unit - high-wall unit (1 Series) MMK-AP0151H, AP0181H All dimensions are given in mm. Legend 1. (Installation board) 2. T op of installation board 3. W ood screw slot 15-6 x 30 4. Anchor bolt slot 10-10 x 20 5. Air outlet Air flow direction adjustable (up/down/left/right) 6.
87 Indoor unit - high-wall unit (1 Series) MMK-AP0241H All dimensions are given in mm. Legend 1. (Installation board) 2. T op of installation board 3. W ood screw slot 21-6 x 30 4. Anchor bolt slot 16-10 x 20 5. Air outlet Air flow direction adjustable (up/down/left/right) 6.
88 Indoor unit - high-wall unit (2 Series) MMK-AP0072H, AP0092H, AP0122H All dimensions are given in mm. Legend 1. Air inlet 2. Air outlet 3. Knockout hole 4. Hook for insulation plate 5. Refrigerant pipe connection (gas Ø3/8”) 6. Drain pipe connection 7.
89 Indoor unit - floor -mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H All dimensions are given in mm. Legend 1. Hole for floor fixing (2-Ø10) 2. Lower refrigerant pipe connection (50 x 100 knockout hole) 3. Switch section (switch sold separately) 4.
90 Indoor unit - concealed chassis unit MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH All dimensions are given in mm. Legend 1. Hole for floor fixing 2. Service space 3. Air outlet 4. Ceiling board 5. G-Ø4.7 hole (front and r ear each) 6.
91 Indoor unit - floor -mounted cabinet unit MMF-AP0151H, AP0181H, AP0241H, AP0271H All dimensions are given in mm. Legend 1. W all 2. With 50 mm wall clearance 3. Lower refrigerant pipe connection (50 x 120 knockout hole) 4. Installation plate 5. Air outlet 6.
92 Indoor unit - floor -mounted cabinet unit MMF-AP0361H, AP0481H, AP0561H All dimensions are given in mm. Legend 1. W all 2. With 50 mm wall clearance 3. Lower refrigerant pipe connection (50 x 120 knockout hole) 4. Installation plate 5. Air outlet 6.
93 Remote contr oller Wired r emote contr oller RBC-AMT31E Simplified remote contr oller RBC-AS21E All dimensions are given in mm..
94 Wireless r emote contr oller TCB-AX21U (W)-E Wireless r emote contr oller kit RBC-AX22CE All dimensions are given in mm..
95 Wireless r emote contr oller kit TCB-AX21E W eekly timer RBC-EXW21E 4.4 x 9.4 slot 4.4 x 5.4 slot All dimensions are given in mm..
96 Central remote contr oller TCB-SC642TLE LON Gateway TCB-IFLN** All dimensions are given in mm. 200 22 78 78 22 22 78 78 22 66 64 147 150 170.
97 TCS-Net relay interface BMS-IFLSV1E T ouch-screen contr oller BMS-TP5120ACE 6 x 5.5 mounting hole All dimensions are given in mm..
98 Intelligent server BMS-LSV2E Energy monitoring relay interface BMS-IFWH3E 6 x 5.5 mounting hole All dimensions are given in mm..
99 Digital I/O relay interface BMS-IFDD01E Windows-based central controller BMS-LSV** 7 (2.4) 63.6 7 156 170 144.9 12.55 12.55 146.9 22 22 78 78 200 6 – Ø5.5 (2.4) 63.6 234 18 18 63.5 93.5 18 18 63.5 93.5 63.6 220 246 6 x 5.5 mounting hole All dimensions are given in mm.
100 Outdoor module MMY -MAP0501T8, MAP0601T8, MAP0801T8, MAP1001T8, MAP1201T8, MMY -MAP0501HT8, MAP0601HT8, MAP0801HT8, MAP1001HT8, MAP1201HT8, Legend 1. Anchor bolt pitch 2. (including feet) 3. 4-15 x 20 (slot) 4. 2-60 x 150 square hole (for forklift truck) 5.
101 Outdoor module - T wo units connected MMY -AP1401T8, AP1601T8, AP1801T8, AP2001T8, AP2211T8, AP2411T8, MMY -AP1401HT8, AP1601HT8, AP1801HT8, AP2001HT8, AP2211HT8, AP2411HT8, Legend 1. Anchor bolt pitch 2. (including feet) 3. 8-15 x 20 (slot) All dimensions are given in mm.
102 Outdoor module - Thr ee units connected MMY - AP2201T8, AP2401T8, AP2601T8, AP2801T8, AP3001T8, AP3211T8, AP3411T8, AP3611T8 MMY - AP2201HT8, AP2401HT8, AP2601HT8, AP2801HT8, AP3001HT8, AP3211HT8, AP3411HT8, AP3611HT8 Notes: 1.
103 Outdoor module - Four units connected MMY - AP3201T8, AP3401T8, AP3601T8, AP3801T8, AP4001T8, AP4201T8, AP4401T8, AP4601T8, AP4801T8 MMY - AP3201HT8, AP3401HT8, AP3601HT8, AP3801HT8, AP4001HT8, AP4201HT8, AP4401HT8, AP4601HT8, AP4801HT8 Legend 1. Anchor bolt pitch 2.
104 Branch header/branch joint Branch header RBM-HY1043E, HY1083E, HY2043E,HY2083E T -shape branching joint RBM-BT13E Gas side Liquid side Insulation Insulation Gas side Liquid side Balance pipe Model.
105 Y -shape branching joint RBM-BY53E, BY103E RBM-BY203E, BY303E Gas side Liquid side Insulation Insulation Gas side Liquid side Insulation Insulation Model A B ØC ØD Accessory socket x quantity RB.
106 Accessory socket Outside diameter Outside diameter Outside diameter Outside diameter Outside diameter Outside diameter Outside diameter Outside diameter.
107.
108 T oshiba Air Conditioning United T echnologies House Guildford Road Leatherhead Surrey KT22 9UT Customer Response Centre: 0870 843 0333 E-mail: general.enquiries@toshiba-ac.com www .toshiba-aircon.co.uk Specifications are subject to change without notice.
An important point after buying a device Toshiba HFC R-410A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Toshiba HFC R-410A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Toshiba HFC R-410A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Toshiba HFC R-410A you will learn all the available features of the product, as well as information on its operation. The information that you get Toshiba HFC R-410A will certainly help you make a decision on the purchase.
If you already are a holder of Toshiba HFC R-410A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Toshiba HFC R-410A.
However, one of the most important roles played by the user manual is to help in solving problems with Toshiba HFC R-410A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Toshiba HFC R-410A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center