4200 FA XT1 September 6, 2004 1 TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200 FA 50 kVA XT – Transformer / External Battery 208v Input / 208/1.
4200 FA XT1 September 6, 2004 2 (50 kVA XT) 1.0 SCOPE 1.1 System This specification describes a conti nuous duty, three-phase, on-line, solid- state uninterruptible power supply system, hereafter referred to as the UPS.
4200 FA XT1 September 6, 2004 3 H. Input / Output EMI / RFI Filters 2.3 System Operation The UPS shall operate as an on-line, fully automatic system in the following modes: A. NORMAL - Incoming AC power is boosted using a chopper circuit, and converted into DC power.
4200 FA XT1 September 6, 2004 4 protection against spikes, common/normal mode noise, load steps and frequency shifts (without battery back-up capability).
4200 FA XT1 September 6, 2004 5 +/- 3% (loss or return of input power) +/- 8% (bypass to inverter) 13) Transient Voltage Recovery 50ms maximum to within 2% of nominal 14) Overload Cap. (on inverter) 125% for 90 sec., 150% for 30 sec. 15) Overload Cap.
4200 FA XT1 September 6, 2004 6 4.0 FUNCTIONAL DESCRIPTION A. Converter / Charger / DC Chopper DESCRIPTION - The converter/charger s hall consist of a solid-state three phase rectifier, DC to DC converter (chopper), output filter, and transient suppresser network to regulate and maintain DC power to the inverter.
4200 FA XT1 September 6, 2004 7 2) INPUT ISOLATION TRANSFORMER - The inverter network shall incorporate a shielded isolation transfo rmer to provide complete isolation of the load from utility AC, as well as providing attenuation for high frequency noise common mode).
4200 FA XT1 September 6, 2004 8 See “System Diagnostics” for specific fault. 3) SYSTEM METERING - The UPS s hall be provided with a single read- out display which displays, upon request, the follo.
4200 FA XT1 September 6, 2004 9 B. Matching Battery Enclosure The battery cabinet shall consist of a freestanding, matching NEMA1 enclosure equipped with casters and leve ling feet. The maximum overall dimensions and weights shall be as follows: UPS Size Dimensions Weight Runtimes 50 kVA 30”L x 32”W x 59.
4200 FA XT1 September 6, 2004 10 D. Battery Test Function The UPS shall be provided with a “Battery Test” pushbutton to periodically check the condition of the batteries. Upon detection of a battery problem, the UPS shall notify the us er of this condition allowing the user to perform a detailed check of the battery string.
An important point after buying a device Toshiba 4200FA XT1 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Toshiba 4200FA XT1 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Toshiba 4200FA XT1 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Toshiba 4200FA XT1 you will learn all the available features of the product, as well as information on its operation. The information that you get Toshiba 4200FA XT1 will certainly help you make a decision on the purchase.
If you already are a holder of Toshiba 4200FA XT1, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Toshiba 4200FA XT1.
However, one of the most important roles played by the user manual is to help in solving problems with Toshiba 4200FA XT1. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Toshiba 4200FA XT1 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center