SINGLE STAGE HEAT PUMPS
LOW VOLTAGE CONTROL CIRCUIT WIRING
MODELS W**H W**H*D S**H S**H*D T**H T**H*D

Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.



“L” terminal is compressor lockout output. This terminal is activated on a high or low pressure trip by the electronic heat pump control. This is a 24 VAC output. “W2” terminal is second stage heat (if equipped). “O1” terminal is the ventilation input. This terminal energizes any factory installed ventilation option. “E” terminal is the emergency heat input. This terminal energizes the emergency heat relay.
230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240V and 208V taps are:

FOR DDC CONTROL Fan Only Energize G Cooling Mode Energize Y, G Heat Pump Heating Energize Y, G, B 2nd Stage Heating Energize G, W2, Y, B w/Heat Pump (if employed) Ventilation Energize G, O1 Emergency Heat Energize B, W2, E, G Dehumidification Energize W3
connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
An 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in this Manual. See Table above.
Low Voltage Connection These units use a grounded 24-volt AC low voltage circuit. The “R” terminal is the hot terminal and the “C” terminal is grounded. “G” terminal is the fan input. “Y” terminal is the compressor input. “B” terminal is the reversing valve input. The reversing valve must be energized for heating mode. “R” terminal is the 24 VAC hot. “C” terminal is the 24 VAC grounded.



NO ECONOMIZER or VENTILATION PACKAGES

"L" is constant 24V output when thermostat is in Em Heat mode
Electronic Bard part #8403-060 A Y2 L Y O/D Thermostat W2 G R Y1 O/B
24V Low Voltage Terminal Block W3 E L DH O1 W2 W1 Y1 B Y R G

FIGURE 2 HEAT PUMP WITH OPTIONAL MFAD, CRV & ERV VENTILATION PACKAGING WITH PROGRAMMABLE THERMOSTAT (RECOMMENDED)

C O/B Y1 R G W2 Y O/D W1/E Bard part #8403-060
Unit C G R Y E Y1 W2 W1 O1 DH L B W3 Terminal Block 24V Low Voltage
optional CO controller is used. Connect orange wire to "G" only if 3
during scheduled occupied periods set to programmed for the "A" output to function Must be configured to programmable and fan

FIGURE 3 HEAT PUMP WITH OPTIONAL MFAD, CRV and ERV VENTILATION PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL)
"L" is constant 24V output 1
thermostat is in Em Heat mode
W3 24V Low Voltage
L B
W1 O1
DH
ERV Orange Black Brown/White CRV
whenever blower operates. Add jumper, ventilation will be active
Do not connect orange wire.

FIGURE 4 HEAT PUMP WITH OPTIONAL MFAD, CRV and ERV VENTILATION PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT WITH CO2 CONTROLLER
"L" is constant 24V output when thermostat is in Em Heat mode
G
6 3 2 4
Unit C G R Y E Y1 W2 W1 O1 DH L B W3
MFAD
MIS-2634 E
is used. only if optional CO controller Connect orange wire to "G"

“E” VENT OPTION

2 Stage Heat
Unit C R B Y E Y1 W2 W1 O1 DH Terminal Block L W3 G
2 be active as first stage cooling. Must be configured for economizer with YO/D output to
These wires are used in special control applications only.

FIGURE 6 HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE AND NO VENTILATION PACKAGE USING THERMOSTAT #8403-060 COMBINATION TEMPERATURE & HUMIDITY CONTROLLER

Unit
Must be configured for "No economizer" for YO/D to be active for humidity control 2

WITH NON-PROGRAMMABLE THERMOSTAT
2 Stage Heat 1 Stage Cool
AUX G Rc O/B
"L" is constant 24V output when thermostat is in Em Heat mode
W3 24V Low Voltage
O1 DH L B Terminal Block
Bard part #8403-047 Electronic Humidistat
Jumper needs to be added.
Mechanical Humidistat · Red Yellow

FIGURE 8 HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION
HUMIDITY CONTROL WITH OPTIONAL CO2 CONTROLLER

Y2 R G W2 YO/D L Y1 W1/E A
L Y1 DH Y B W1 O1 R W2
Must be configured to "no economizer" to make YO/D output
active for humidity control. Must be configured to programmable
and fan set to programmed fan for the "A" output to function
during scheduled occupied periods.
Do not connect "A" from thermostat if optional CO
controller is used. Connect orange wire to "G" only
when optinal CO controller is used.

FIGURE 9 HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION
Bard part #8403-058 Rc Thermostat
AUX L
"L" is constant 24V output when thermostat is in Em Heat mode
O1
ERV
MFAD
active whenever blower operates. Add jumper, ventilation will be
Jumper needs to be added. 3
Orange wire is not connected.
Bard part #8403-038 Mechanical Humidistat

FIGURE 10 HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION
"L" is constant 24V output when thermostat is in Em Heat mode
Cool
E Rc L G R Y O/B
Heat 2 Stage
6 5 4 3 2
W2 W3 O1 DH L B W1 E
Unit
CRV
ERV
4 3 5 6
Jumper needs to be added.
Connect Orange wire to "G".

WH/SH HEAT PUMP CONNECTION DIAGRAM
DO NOT CONNECT "L" UNTIL AFTER

IF OPTIONAL VENT PACKAGE IS INSTALLED, THE "G" WIRE MUST
BE CONNECTED TO ASSURE CONTINUOUS BLOWER DURING OCCUPIED PERIODS WHEN VENT
LIGHTING CONTROL CIRCUIT IS OPTIONAL AND FIELD SUPPLIED. LIGHTING CONTROL RELAY REQUIRES NORMALLY CLOSED CONTACTS AND MUST BE SIZED ACCORDING TO CONTROLLED LOAD.
FUNCTION SWITCHES
TEMPERATURE SWITCHES

48 54 58 62

& #8403-060 THERMOSTAT (EIFM)
“E” VENT OPTION
Thermostat Part #8403-060*

1.) Configured for "Heat Pump" 2.) Configured for "Multi-Stage" 3.) Configured for "No Economizer" 4.) Configured CS2000A Attached = NO

FIGURE 13 1-STAGE HEAT PUMP WITH OPTIONAL ELECTRIC HEAT WITH OR WITHOUT DEHUMIDIFICATION
“W” OR “T” VENT OPTION

Must be energized to enable minimum position. NOTE: Economizer Control Default Setting
1 is 10V (100%). Depending upon application may require setting to lower value.
Must be configured for heat pump / multistage/ no economizer/ 2
to enable YO/D output to be active as dehumidification output

FIGURE 14 HEAT PUMP WITH OPTIONAL CRVMWH-3 OR CHCRV-5 VENTILATION PACKAGING WITH PROGRAMMABLE THERMOSTAT (RECOMMENDED)

C O/B Y1 R G W2 Y O/D W1/E Bard part #8403-060
Unit C G R Y E Y1 W2 W1 O1 DH L B W3 Terminal Block 24V Low Voltage
if optional CO controller is used. Do not connect "A" from tstat #8403-060
Wire only needed for dehumidification units 3
Must be configured to programmable and fan
during scheduled occupied periods set to programmed for the "A" output to function

FIGURE 15 HEAT PUMP WITH OPTIONAL CRVMWH-3 OR CHCRV-5 VENTILATION PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL)
Thermostat #TH5220D1151 Bard part #8403-058
AUX G R Rc O/B C
R E Y1 W2 W1 O1 DH L B
OR CRVMWH-3
MIS-2998 A
Add jumper, ventilation will be active
whenever blower operates.
Ventilation · Package