Bard Packaged Heat Pump (PH1236)

23 pages·164 KB·Electric Heater·PDF·EN
Bard Packaged Heat Pump (PH1236)
Table of Contents 78 sections INSTALLATION INSTRUCTIONS · SINGLE PACKAGE · HEAT PUMPS · MODELS PH1224 PH1230 PH1236 · … ShowHide
INSTALLATION INSTRUCTIONSp.1SINGLE PACKAGEp.1HEAT PUMPSp.1MODELS PH1224 PH1230 PH1236p.1Getting Other Information and Publicationsp.3For more information, contact these publishers:p.3ASHRAE — American Society of Heating Refrigerating, andp.3TABLE 1 ELECTRICAL DATAp.4TABLE 2p.4TABLE 3p.4OPTIONAL FIELD-INSTALLED ELECTRIC HEATER TABLEp.4GENERAL INSTRUCTIONSp.5IMPORTANTp.5FIELD INSTALLED HEATER PACKAGES (OPTIONAL)p.5SHIPPING DAMAGEp.5GENERALp.5WET COIL (COOLING)p.5ONE PIECE CONSTRUCTION – READY TO INSTALLp.6CURB AND ROOF DETAILSp.6FIGURE 2 FIELD FABRICATED CURBINGp.6INSTALLATIONp.7LOCATIONp.7TYPICAL INSTALLATIONSp.7SLAB MOUNTINGp.7ROOF MOUNTINGp.7WINTER INSTALLATION BELOW 32°Fp.7DUCT WORKp.7FIGURE 3 ELEVATED MOUNTING PLATFORMSp.8FIGURE 6 SLAB MOUNTING AT GROUND LEVELp.9CONDENSATE DRAIN TRAPp.10TABLE 5p.10AIR FILTERSp.10FIGURE 7 CONDENSATE DRAIN TRAPp.10WIRING – MAIN POWERp.11WIRING – 24V LOW VOLTAGE CONTROL CIRCUITp.11FIGURE 8 – LOW VOLTAGE WIRINGp.11TABLE 6 – THERMOSTAT WIRE SIZEp.11THERMOSTATSp.12TABLE 7p.12HEAT PUMP THERMOSTATSp.12THERMOSTAT INDICATOR LAMPSp.13COMPRESSOR CUTOFF THERMOSTAT WIRING (5 and 10 KW)p.13FIGURE 9 UNIT 24V TERMINAL BOARDp.13EMERGENCY HEAT POSITIONp.13REMOVE FACTORY JUMPER Y-Y1p.13OUTDOOR THERMOSTAT USED AS COMPRESSOR CUTOFFp.13COMPRESSOR CUTOFF THERMOSTAT and OUTDOOR THERMOSTAT WIRINGp.13COMPRESSOR CUTOFF THERMOSTAT WIRING (15 KW ONLY)p.13FIGURE 10 UNIT 24V TERMINAL BOARDp.13TABLE 9 15 KW ONLYp.13START UP AND OPERATIONp.14THREE PHASE SCROLL COMPRESSOR START UP INFORMATIONp.14DEFROST CYCLEp.14SEQUENCE OF OPERATIONp.14START UP NOTESp.14FIGURE 11 HEAT PUMP CONTROL BOARDp.15SERVICE AND TROUBLESHOOTINGp.16SERVICE HINTSp.16FIGURE 12 FAN BLADE SETTING DIMENSIONSp.16PRESSURE SERVICE PORTSp.16SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDUREp.16REFRIGERANT CHARGEp.16TABLE 10p.16FAN BLADE SETTINGSp.16TROUBLE SHOOTING GUIDEp.17CHECKING TEMPERATURE SENSOR CHECK OUTp.18F R F R F R F Rp.18SUCTION AND DISCHARGE TUBE BRAZINGp.19FIGURE 13 BRAZING DIAGRAMp.19PRESSURE TABLESp.20TABLE 11p.20COOLINGp.20TABLE 12p.20HEATINGp.20Wiring Diagram (4098-123) printedp.21from CAD to get size neededp.21Wiring Diagram (4098-124) printedp.22Wiring Diagram (4098-211) printedp.23
Page 1 of the Bard Packaged Heat Pump (PH1236) user manual — INSTALLATION INSTRUCTIONS
Page 1 · click to enlarge
Page 1

INSTALLATION INSTRUCTIONS

SINGLE PACKAGE

HEAT PUMPS

MODELS PH1224 PH1230 PH1236

Bard Packaged Heat Pump (PH1236) — INSTALLATION INSTRUCTIONS diagram (page 1)
Fig. 1

Bard Manufacturing Company Bryan, Ohio 43506

Manual2100-344 File: Volume II Tab 11 Date: 08-21-98

Since 1914...Moving ahead, just as planned.

© Copyright 1998

Page 2 of the Bard Packaged Heat Pump (PH1236) user manual — INSTALLATION INSTRUCTIONS
Page 2 · click to enlarge
Page 2
Page 2 of the Bard Packaged Heat Pump (PH1236) user manual — INSTALLATION INSTRUCTIONS
Page 3 of the Bard Packaged Heat Pump (PH1236) user manual — ASHRAE — American Society of Heating Refrigerating, and
Page 3 · click to enlarge
Page 3

Getting Other Information and Publications

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

For more information, contact these publishers:

ACCA — Air Conditioning Contractors of America

1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721

National Electrical Code ANSI/NFPA 70

Standard for the Installation ANSI/NFPA 90A of Air Conditioning and Ventilating Systems

ANSI — American National Standards Institute

11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286

Standard for Warm Air ANSI/NFPA 90B Heating and Air Conditioning Systems

ASHRAE — American Society of Heating Refrigerating, and

Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning

Air Conditioning Engineers, Incorporated 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478

Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection

NFPA — National Fire Protection Association

Commercial Low Pressure, ACCA Manual Q Low Velocity Duct System Design

Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057

Load Calculation For Commercial ACCA Manual N Summer and Winter Air Conditioning

Page 4 of the Bard Packaged Heat Pump (PH1236) user manual —
Page 4 · click to enlarge
Page 4

TABLE 1 ELECTRICAL DATA

ModelRated Volts& PhasesOperating Voltage RangeMaximum UnitAmps Maximum External Fusesor Ckt.Brk.Minimum Circuit Ampacity Field Power Wiring Ground WireSize Ckt.ACkt.ACkt.ACkt.A PH1224230/208-1197-25314.425181010 PH1230230/208-1197-25317.730221010 PH1236230/208-1197-25321.8402788 PH1236-B230/208-3197-25315.625191010

Maximum time delay fuse or HACR type circuit breaker. HACR type not applicable to 460 volt.

75 degree C cooper wire size, basic unit only.

TABLE 2

OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE HEAT PUMP MODELS INDICATED

HeaterPackage ModelNo.Voltsand PhasePH1224PH1230PH1236PH1236-B EH3PC-A05 EH3PB-A10 EH3PC-A10 EH3PC-A15240/1X XX X XX X X EH3PB-B09 EH3PB-B15240/3X X

TABLE 3

OPTIONAL FIELD-INSTALLED ELECTRIC HEATER TABLE

Heater Pkg.Model No.UnitVolts PhaseHtr.KW& Capacity @240V(or 480Vif applicable)Htr.KW& Capacity @208Volts@ 240V or480Vas applicable Htr.AmpsHeater Internal FusesCircuitB No. Field Ckts.Minimum Circuit Ampacity Maximum Overcurrent Protection Field Power Wiring Ground Wire Size KWBTUHKWBTUH EH3PB-A10240/208-11034,1007.5026,00041.715360610 EH3PC-A05 EH3PC-A10 EH3PC-A15240/208-1 240/208-1 240/208-15 10 1517,100 34,100 51,2003.75 7.50 11.2512,800 26,000 38,40020.8 41.7 62.530/601 1 126 53 7930 60 8010 6 410 10 8 EH3PB-B09 EH3PB-B15240/208-3 240/208-39 1530,700 51,2006.75 11.2523,000 38,40021.7 36.21 128 4630 5010 810 10

Time delay fuses or “HACR” type circuit breakers must be used for 60 and smaller sizes. Standard fuses or circuit breakers are suitable for sizes 70 and larger. 480V circuit breakers are not “HACR” type. Based on wire suitable for 75° C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based upon Table 250-95 of N.E.C. 1993. See electrical data for basic heat pump for Circuit A wiring specification requirements.

Page 5 of the Bard Packaged Heat Pump (PH1236) user manual — WET COIL (COOLING)
Page 5 · click to enlarge
Page 5

GENERAL INSTRUCTIONS

IMPORTANT

FIELD INSTALLED HEATER PACKAGES (OPTIONAL)

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work, supply and return ducts, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.

These packaged heat pumps are manufactured without supplementary electric heaters. Supplementary heaters EH3P series (to fit PH1224, PH1230, and PH1236) are available for simple, fast, field installation.

A separate field power circuit is required for the supplementary heaters.

SHIPPING DAMAGE

Refer to the electrical data shown on pages 2 and 3 for proper application information on all available heater combinations and what units they can be used with. It also shows the applicable circuit ampacities, fuse size, and wire size for each heater combination.

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

Refer to the installation instructions packed with the heater for details on how to insert it into the basic unit.

GENERAL

The refrigerant system is completely assembled and charged. All internal wiring is complete.

TABLE 4 RATED CFM AND EXTERNAL STATIC PRESSURE (ESP)

The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.

WET COIL (COOLING)

ModelRated CFMRated ESPRecommended AirFlowRange PH1224800.20680 - 880CFM PH12301000.30775 - 1100CFM PH12361100.20775 - 1210CFM

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

These instructions and any instructions packaged with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made.

Page 6 of the Bard Packaged Heat Pump (PH1236) user manual — FIGURE 2 FIELD FABRICATED CURBING
Page 6 · click to enlarge
Page 6

FIGURE 1 PREFABRICATED ROOF CURB SPECIFICATIONS HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP, WELDED/LEAKPROOF

ONE PIECE CONSTRUCTION – READY TO INSTALL

Bard Packaged Heat Pump (PH1236) — ONE PIECE CONSTRUCTION – READY TO INSTALL diagram (page 6)
Fig. 2

CURB AND ROOF DETAILS

Bard Packaged Heat Pump (PH1236) — CURB AND ROOF DETAILS diagram (page 6)
Fig. 3
A B C*D E F J*H*RoofH Modood AirConditi el Units 80-3/8 40-1/4 37-1/4 38-3/8 35-3/8 42 14-3/4 19-1/8 RHEPH1224, P 60 PH123

*Duct Sizing Information Return Air Dimension “C” is length Supply Air Dimension “C” is length Return Air Dimension “H” is width Supply Sir Dimension “J” is width

FIGURE 2 FIELD FABRICATED CURBING

Bard Packaged Heat Pump (PH1236) — FIGURE 2 FIELD FABRICATED CURBING diagram (page 6)
Fig. 4
Page 7 of the Bard Packaged Heat Pump (PH1236) user manual — DUCT WORK
Page 7 · click to enlarge
Page 7

INSTALLATION

LOCATION

TYPICAL INSTALLATIONS

GENERAL

1. ROOF MOUNTED – The unit is mounted on a sturdy base on the roof of the building. Return air to the unit is brought through a single return grille (grilles with built-in filters are best since they enable easy access for filter changing). Return air ducts are attached to the lower section of the front panel. Supply air is brought from the unit to attic duct work or to a furred down hall. Supply air duct is attached to the top of the front panel.

The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the living area or adjacent buildings.

SLAB MOUNTING

insulated and weatherproofed. All attic duct work must be thoroughly insulated. Two inch thick insulation with suitable vapor barrier is recommended for both outdoor and attic runs.

In areas where winter temperatures DO NOT go below 32° F for periods over twelve hours, the unit may be slab mounted at grade level. When installing unit at grade level, install on a concrete slab at least four inches above finished grade level. Slab should have a slope tolerance away from the building structure of at lease 1/4 inch per foot, while being level from side to side. This will prevent ice buildup under the unit during defrost cycles. Place slab in a location where runoff water from higher ground will not collect around unit. See Figure 3.

In roof top installation, as in all installations, the heat pump must be level from side to side. However, the unit should have a pitch along the length to assure complete external drainage of precipitation and of defrost condensate.

2. CRAWL SPACE – Duct work installed in crawl space must be well insulated and provided with a vapor barrier. In addition, the crawl space must be thoroughly ventilated and provided with a good vapor barrier as a ground cover. It is most desirable to install the unit outdoors rather than inside the crawl space, so that it will be readily accessible for service. In addition, it is

A minimum of 18 inches should be provided between the coil inlet and any building surfaces. Provide at least four feet between coil outlet and any building wall, fences or other vertical structures. Provide a minimum of three feet clearance on the service access side of the unit. See Figure 4

necessary to dispose of the condensate from the outdoor coil on the heating cycle, and this is virtually impossible with the unit installed inside the crawl space.

ROOF MOUNTING

When a unit is installed in areas where low ambient temperatures or strong winter winds exist, it should be placed so prevailing winter winds are not in direct line with the heat pump coil. If this is not possible, a wind barrier should be constructed. Place barrier 24 inches from the coil inlet side of the unit and in the direction of prevailing winds. Size barrier at least the same height and width as the unit. This may be necessary on ground level installations, also. See Figure 5.

3. SLAB MOUNTED AT GROUND LEVEL – This type installation is ideal for homes with a slab floor construction where a roof mounted unit is not desired. The supply and return duct work can be run through a furred closet space.
4. THROUGH THE WALL – This type installation requires a suitable framework to be fabricated capable of withstanding the unit weight. Normally the unit will be insulated so as to minimize supply and return duct work.

WINTER INSTALLATION BELOW 32°F

5. OTHER INSTALLATIONS – Many other installations are possible with the packaged heat pump. No matter what the installation, always consider the following facts: A. Insure that the discharge air is not obstructed in any

In areas where winter conditions go below 32°F for extended periods, the unit must be elevated above the mounting surface to prevent snowfall or defrost ice accumulation from interfering with the operation of the unit. A minimum of twelve inch elevation is recommended, while greater elevation may be required for areas of high snow accumulation. Poured concrete, steel framework, brick, cement block, etc., can be utilized to construct a suitable raised mounting platform. See Figure 6.

way so as to cause operation difficulties. B. The indoor coil drain pan is equipped with a

coupling that must be piped through a condensate drain trap to a suitable drain. C. Always mount the unit is such a position that it may

be easily reached for servicing and maintenance. D. Insure that the unit is clear so that proper air flow

DUCT WORK

over the outdoor coil will be maintained.

Refer to Tables 4, 5 and 5A when designing duct work for maximum static pressure available with the specific model and heater package being installed. Unit duct work is suitable for 0” clearance to combustible materials.

If this unit is operated in cooling below a 65° outdoor ambient temperature, the installation of low ambient controls (CMA-6) to unit is required.

Page 8 of the Bard Packaged Heat Pump (PH1236) user manual — FIGURE 3 ELEVATED MOUNTING PLATFORMS
Page 8 · click to enlarge
Page 8

FIGURE 3 ELEVATED MOUNTING PLATFORMS

Bard Packaged Heat Pump (PH1236) — FIGURE 3 ELEVATED MOUNTING PLATFORMS diagram (page 8)
Fig. 5
Page 9 of the Bard Packaged Heat Pump (PH1236) user manual — FIGURE 6 SLAB MOUNTING AT GROUND LEVEL
Page 9 · click to enlarge
Page 9

FIGURE 5 ROOF TOP APPLICATION (May also be required for ground level installations.)

Bard Packaged Heat Pump (PH1236) — FIGURE 6 SLAB MOUNTING AT GROUND LEVEL diagram (page 9)
Fig. 6

FIGURE 6 SLAB MOUNTING AT GROUND LEVEL

(Above 32° F Outside Temperature)

Bard Packaged Heat Pump (PH1236) — FIGURE 6 SLAB MOUNTING AT GROUND LEVEL diagram (page 9)
Fig. 7
Page 10 of the Bard Packaged Heat Pump (PH1236) user manual — FIGURE 7 CONDENSATE DRAIN TRAP
Page 10 · click to enlarge
Page 10

CONDENSATE DRAIN TRAP

maintained for proper operation. If this is not done, excessive energy use, poor performance, and multiple service problems will result. It is impossible to oversize air filters. Generous sizing will result in cleaner air and coils as well as lower operating costs and extend the time between required changes. Table 6 shows minimum filter areas and recommended filter sizes. Actual filter sizes can vary with the installation due to single or multiple returns utilizing a filter/grille arrangement or being placed immediately ahead of the indoor coil face in the return air duct.

It is very important to provide a trap in the condensate drain line to allow a positive liquid seal in the line and assure correct drainage from the coil condensate pan.

Install condensate drain trap shown in Figure 7. Use drain connection size or larger. Do not operate unit without trap. Unit must be level or slightly inclined toward drain. With a trap installed on a unit located in an unconditioned area, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes.

TABLE 5

AIR FILTERS

Bard Packaged Heat Pump (PH1236) — TABLE 5 diagram (page 10)
Fig. 8
ModelMinimumFilter AreasRecommended Size PH1224 PH1230 PH1236462squareinches (3.21squarefeet)15x30-5/8x1

Air filters for the return air side of the system are not provided as part of the various types of applications for these models, and must be field supplied and installed as part of the final installation.

Prior thought should be given to return air location and placement of the air filter(s). The air filter(s) must be of adequate size and readily accessible to the operator of the equipment. Filters must be adequate in size and properly

FIGURE 7 CONDENSATE DRAIN TRAP

Bard Packaged Heat Pump (PH1236) — FIGURE 7 CONDENSATE DRAIN TRAP diagram (page 10)
Fig. 9
Page 11 of the Bard Packaged Heat Pump (PH1236) user manual — TABLE 6 – THERMOSTAT WIRE SIZE
Page 11 · click to enlarge
Page 11

WIRING – MAIN POWER

WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT

Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Data” on pages 2.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.

Ten (10 ) wires should be run from thermostat subbase to the 24V terminal board in the unit. A ten conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8.

FIGURE 8 – LOW VOLTAGE WIRING

The electrical specifications on page 2 lists fuse and wire sizes (75° F copper) for all models including the most commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.

TABLE 6 – THERMOSTAT WIRE SIZE

Transformer VAFLAWire GaugeMaximumLength InFeet 552.320 18 16 14 1245 60 100 160 250
Page 12 of the Bard Packaged Heat Pump (PH1236) user manual — TABLE 7
Page 12 · click to enlarge
Page 12

THERMOSTATS

See specific wiring information for the different models, heater KWs, and voltages.

TABLE 7

HEAT PUMP THERMOSTATS

THERMOSTATSUBBASEDESCRIPTION 8403-045 (T841A1761)Partof Thermostat1stagecool,2stageheat;Mecurybulb;Manualchangeover FanSwitch: Auto-On; SystemSwitch: EmHeat-Heat-Off-Cool IndicatingLamps: Check-EmHeat-AuxHeat 8403-017 (T874R1129)8404-009 Q674L11811stagecool,2stageheat;Mercurybulb;Manualchangeover FanSwitch: Auto-On; SystemSwitch: EmHeat-Heat-Off-Cool IndicatingLamps: Check-EmHeat 8403-018 (T874N1024)8404-010 Q674F12611stagecool,2stageheat;Mercurybulb;Autochangeover FanSwitch: Auto-On; SystemSwitch: Off-EmHeat-Heat-Auto-Cool IndicatingLamps: Check-EmHeat 8403-042 (T8511G1070)Partof Thermostat1stagecool,2stageheat;Digitalnon-programmable(nobatteryrequired) Automaticormanualchangeover FanSwitch: Auto-On; SystemSwitch: Off-EmHeat-Auto orCool/Heat IndicatingLamps: Check DisplayIndication: EmHeat-AuxHeat 8403-034 (1F94-80)Partof Thermostat2stagecool,2stageheat;Digitalprogrammable(7day);Batterybackup Automaticormanualchangeover;1set-up/set-backperiodper24hours Programmableventilationterminalforeconomizerorenergyrecovery FanSwitch: Auto-On; SystemSwitch: Off-EmHeat-AutoorCool/Heat IndicatingLamps: Emer-Pump-Malf-Aux 8403-027 (1F92-71)Partof Thermostat2stagecool,3stageheat;Digitalproframmable(5day/2day);Batterybackup Automaticormanualchangeover:4set-ups/set-backperiodsper24hours FanSwitch: Auto-On; SystemSwitch: Off-EmHeat-AutoorCool/Heat IndicatingLamps: Emer-Pump-Malf-Aux

No automatic changeover position – must be manually placed in heat or cool. Reversing valve remains energized at all times system switch is in heat position (except during defrost cycle). No pressure equalization noise when thermostat is satisfied on either heating or cooling.

Allows thermostat to control both heating and cooling operation when set in “AUTO” position. Reversing valve de- energizes at end of each “ON” heating cycle.

·

Page 13 of the Bard Packaged Heat Pump (PH1236) user manual — REMOVE FACTORY JUMPER Y-Y1
Page 13 · click to enlarge
Page 13

THERMOSTAT INDICATOR LAMPS

COMPRESSOR CUTOFF THERMOSTAT WIRING (5 and 10 KW)

The red lamp marked “EM. HT.” comes on and stays on whenever the system switch is placed in Em. Ht. position. The green lamp marked “Check” will come on if there is any problem that prevents the compressor from running when it is supposed to be.

FIGURE 9 UNIT 24V TERMINAL BOARD

EMERGENCY HEAT POSITION

REMOVE FACTORY JUMPER Y-Y1

The operator of the equipment must manually place the system switch in this position. This is done when there is a known problem with the outdoor section, or when the green “Check” lamp comes on indicating a problem.

TRANSFORMER TAPS 230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

OUTDOOR THERMOSTAT USED AS COMPRESSOR CUTOFF

TABLE 8 5 and 10 KW

TAP RANGE 240 253 – 216 208 220 – 187 NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

l e d o M W K s tl o V e s a h P

COMPRESSOR CUTOFF THERMOSTAT and OUTDOOR THERMOSTAT WIRING

COMPRESSOR CUTOFF THERMOSTAT WIRING (15 KW ONLY)

Heat pump compressor operation at outdoor temperatures below 0° F are neither desirable nor advantageous in terms of efficiency. Since most equipment at time of manufacture is not designated for any specific destination of the county and most of the equipment is installed in areas not approaching the lower outdoor temperature range, the compressor cutoffs are not factory installed.

FIGURE 10 UNIT 24V TERMINAL BOARD

Outdoor thermostats are available to hold off various banks of electric heat until needed as determined by outdoor temperature. The set point of either type of thermostat is variable with geographic region and sizing of the heating equipment to the structure. Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points.

REMOVE FACTORY JUMPER Y-Y1

OUTDOOR THERMOSTAT USED AS COMPRESSOR CUTOFF

TABLE 9 15 KW ONLY

l e d o M W K s tl o V e s a h P

Page 14 of the Bard Packaged Heat Pump (PH1236) user manual — START UP NOTES
Page 14 · click to enlarge
Page 14

START UP AND OPERATION

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A thermostat demand for heat completes R-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on the solid state heat pump control.

When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32°F or below. This temperature is sensed by the coil sensor mounted near the bottom of the outdoor coil. Once the coil temperature reaches 32°F or below, the coil sensor sends a signal to the control logic of the heat pump control and defrost timer will start.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.

After 60 (90 or 30) minutes at 32°F or below, the heat pump control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57° F, the coil sensor will send a signal to the heat pump control which will return the system to heating operations automatically.

All three phase ZR*3 compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminals should maintain proper rotation direction.

If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 10 minutes.

There are three settings on the heat pump control -- 30 minutes, 60 minutes, and 90 minutes. Most models are shipped wired on the 60 minutes setting for greatest operating economy. If special circumstances require a change to another time, remove wire connected to terminal 60 and reconnect to desired terminal. (See Figure 11.)

The direction of rotation of the motor may be changed by reversing any two line connections to the unit.

SEQUENCE OF OPERATION

COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation, or can be energized by manual fan switch on subbase for constant air circulation.

There is a cycle speed up jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse.

There is an initial defrost (sen jmp) jumper on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature. This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.

HEATING – A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “AUTO” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season and thus eliminating pressure equalization noise except during defrost, are to be used. On “AUTO” option, a circuit is completed from R-W1 and R-Y on each heating “On” cycle energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second energizes

START UP NOTES

For improved start up performance, wash the indoor coil with dishwasher detergent

Page 15 of the Bard Packaged Heat Pump (PH1236) user manual — FIGURE 11 HEAT PUMP CONTROL BOARD
Page 15 · click to enlarge
Page 15

FIGURE 11 HEAT PUMP CONTROL BOARD

Page 16 of the Bard Packaged Heat Pump (PH1236) user manual — FAN BLADE SETTINGS
Page 16 · click to enlarge
Page 16

SERVICE AND TROUBLESHOOTING

SERVICE HINTS

FIGURE 12 FAN BLADE SETTING DIMENSIONS

1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the manual reset high pressure switch.

l e d o M A n o i s n e m i D

" 0 0 . 1 " 5 7 .

3. The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems.

" 5 7 .

4. Check all power fuses or circuit breakers to be sure that they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found in Tables 11 and 12 in this manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure table to the unit by model number.

SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE

1. Turn on AC power supply to indoor and outdoor units.
2. Turn thermostat blower switch to fan on. The indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)

REFRIGERANT CHARGE

3. Turn thermostat blower switch to Auto position. Indoor blower should stop.

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 10.

4. Set system switch to heat or cool. Adjust thermostat to call for heat or cool. The indoor blower, compressor, and outdoor fan should start.

TABLE 10

F e e r g e D 5 9 D O

F e e r g e D 2 8 D O

d e t a R

compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.

w o lfri A

e r u t a r e p m e T

e r u t a r e p m e T

0 0 8 0 0 0 1 0 0 1 1

6 5 - 6 5 6 5 - 6 5 2 5 - 0 5

2 6 - 1 6 0 6 - 8 5 4 5 - 2 5

The above suction line temperatures are based upon 80° F dry bulb/67° F wet bulb (50% RH) temperature and rated airflow across the evaporator during cooling cycle.

FAN BLADE SETTINGS

Shown in Figure 12 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions in Figure 12 be checked and blade adjusted in or out on the motor shaft accordingly.

Page 17 of the Bard Packaged Heat Pump (PH1236) user manual — TROUBLE SHOOTING GUIDE
Page 17 · click to enlarge
Page 17

TROUBLE SHOOTING GUIDE

m o t p m y S s e s u a C e l b i s s o P k c e h C o t t a h W ri a p e R r o k c e h C o t w o H

r o tc a tn o c r o s s e r p m o C

g niri w tiu c ric litn o C tin u t a n oitc e n n o c R r o f k c e h C

t a e h r e w o p o t tin u r o o d tu o o t n oitc e n n o c R n u R

e zig r e n e t o n s e o d

. C - R n e e w t e b tlo v 4 2 d n a

.lo rtn o c p m u p

) g nilo o c r o g nit a e h (

tu o k c ol r o s s e r p m o C n e e w t e b V 4 2 r o f k c e h C . 1 lo rtn o c p m u p t a e h n o C - 1 L

ff o t a ts o m r e h t n r u t , C - 1 L n e e w t e b e g a tlo v o n fI . 1 .h cti w s e r u s s e r p h gih t e s e r o t nia g a n o d n a

h gih s s o r c a k c e h C . 2 .h cti w s e r u s s e r p

,t e s e r t o n lli w d n a n e p o si h cti w s e r u s s e r p h gih fI . 2 .h cti w s e r u s s e r p h gih e c alp e r

elc y c tr o h s r o s s e r p m o C

C - C C n e e w t e b V 4 2 r o f k c e h C

p u d e e p s r e p m uj , C - C C n e e w t e b e g a tlo v o n fI

n oitc e t o r p

p m u p t a e h n o C - Y d n a

dlu o h s r e w o p s d n o c e s 0 1 nih ti w d n a ,la ni m r e t

.lo rtn o c

r e p m uj p u d e e p s e v o m e R . C - C C n e e w t e b r a e p p a

.s d n o c e s 0 1 r e tf a

lo rtn o c p m u p t a e H

elbis s o p r e h t o lla k c e h C

.lo rtn o c p m u p t a e h e c alp e R

e vitc e f e d

. 5 6 0 - 0 0 1 2 la u n a M .s e s u a c

e vitc e f e d r o tc a tn o C d e tr o h s r o n e p o r o f k c e h C

.r o tc a tn o c e c alp e R

. g nid ni w lio c

r o t o m r o o d tu o n a F

e vitc e f e d r o t o M d e tr o h s r o n e p o r o f k c e h C

.r o t o m e c alp e R

n u r t o n s e o d

. g nid ni w r o t o m

g nit a e h r o g nilo o c (

e vitc e f e d r o tic a p a c r o t o M . g nit a r r o tic a p a c k c e h C

.r o tic a p a c e c alp e R

)ts o rf e d g nir u d t p e c x e

d e tr o h s r o n e p o r o f k c e h C

.r o tic a p a c

lo rtn o c p m u p t a e H

n o y ale r n a f s s o r c a k c e h C

.lo rtn o c p m u p t a e h e c alp e R

e vitc e f e d

) C N - m o C ( .lo rtn o c p m u p t a e h

s e o d e vla v g nis r e v e R

dio n elo s e vlo v g nis r e v e R

d e tr o h s r o n e p o r o f k c e h C

.lio c dio n elo s e c alp e R

e zig r e n e t o n

e vitc e f e d lio c

.lio c

) yln o g nit a e h (

lo rtn o c p m u p t a e H

C - V R n e e w t e b V 4 2 r o f k c e h C

. g niri w tiu c ric lo rtn o c k c e h C . 1 lo rtn o c p m u p t a e h e c alp e R . 2

e vitc e f e d

. C - B d n a

o tni o g t o n lli w tin U

r o r o s n e s e r u t a r e p m e T

e r u t a r e p m e t tc e n n o c si D

e c alp e r , elc y c ts o rf e d h g u o r h t s e o g tin u fI . 1 .r o s n e s e r u t a r e p m e t

ts o rf e d

lo rtn o c p m u p t a e h

d n a d r a o b m o rf r o s n e s

) yln o g nit a e h (

e vitc e f e d

p u d e e p s s s o r c a r e p m uj

p m uj n e s d n a sla ni m r e t

e c alp e r , elc y c ts o rf e d h g u o r h t o g t o n s e o d tin u fI . 2 .lo rtn o c p m u p t a e h

e s u a c dlu o h s sih T .sla ni m r e t

a h g u o r h t o g o t tin u e h t

e n o nih ti w elc y c ts o rf e d

. e tu ni m

tu o e m o c t o n lli w tin U

r o r o s n e s e r u t a r e p m e T

p u d e e p s s s o r c a r e p m u J

e c alp e r , elc y c ts o rf e d f o tu o s e m o c tin u fI . 1 .r o s n e s e r u t a r e p m e t

ts o rf e d f o

lo rtn o c p m u p t a e h

e s u a c dlu o h s sih T .sla ni m r e t

) yln o g nit a e h (

. e vitc e f e d

ts o rf e d f o tu o e m o c o t tin u e h t

, elc y c ts o rf e d f o tu o e m o c t o n s e o d tin u fI . 2 .lo rtn o c p m u p t a e h e c alp e r

. e tu ni m e n o nih ti w

Page 18 of the Bard Packaged Heat Pump (PH1236) user manual — F R F R F R F R
Page 18 · click to enlarge
Page 18

CHECKING TEMPERATURE SENSOR CHECK OUT

3. Check resistance reading to chart of resistance; use sensor ambient temperature. (Tolerance of part is ± 10%.)
1. Disconnect temperature sensor from board and from outdoor coil.
4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
5. If sensor is out of tolerance, shorted, open, or reads very low ohms then it should be replaced.

TEMPERATURE F vs RESISTANCE R OF TEMPERATURE SENSOR

F R F R F R F R

0. 5 2 - 1 7 8 6 9 1 0 . 5 1 0 4 6 3 5 0 . 5 5 4 3 4 7 1 0 . 5 9 1 3 5 6
0. 4 2 - 9 9 0 0 9 1 0 . 6 1 1 5 0 2 5 0 . 6 5 4 8 9 6 1 0 . 6 9 3 8 3 6
0. 3 2 - 5 8 5 3 8 1 0 . 7 1 4 1 5 0 5 0 . 7 5 7 4 5 6 1 0 . 7 9 9 3 2 6
0. 2 2 - 8 1 3 7 7 1 0 . 8 1 8 2 0 9 4 0 . 8 5 2 2 1 6 1 0 . 8 9 8 9 0 6
0. 1 2 - 9 8 2 1 7 1 0 . 9 1 0 9 5 7 4 0 . 9 5 0 1 7 5 1 0 . 9 9 1 6 9 5
0. 0 2 - 7 8 4 5 6 1 0 . 0 2 0 0 2 6 4 0 . 0 6 0 1 3 5 1 0 . 0 0 1 7 2 8 5
0. 9 1 - 4 0 9 9 5 1 0 . 1 2 5 5 8 4 4 0 . 1 6 1 2 9 4 1 0 . 1 0 1 7 9 6 5
0. 8 1 - 9 2 5 4 5 1 0 . 2 2 4 5 5 3 4 0 . 2 6 4 4 5 4 1 0 . 2 0 1 0 7 5 5
0. 7 1 - 5 5 3 9 4 1 0 . 3 2 5 9 2 2 4 0 . 3 6 7 7 1 4 1 0 . 3 0 1 6 4 4 5
0. 6 1 - 4 7 3 4 4 1 0 . 4 2 7 7 0 1 4 0 . 4 6 0 2 8 3 1 0 . 4 0 1 6 2 3 5
0. 5 1 - 6 7 5 9 3 1 0 . 5 2 8 9 8 9 3 0 . 5 6 4 7 4 3 1 0 . 5 0 1 8 0 2 5
0. 4 1 - 6 5 9 4 3 1 0 . 6 2 7 5 7 8 3 0 . 6 6 7 3 1 3 1 0 . 5 0 1 4 9 0 5
0. 3 1 - 6 0 5 0 3 1 0 . 7 2 2 5 6 7 3 0 . 7 6 0 1 8 2 1 0 . 7 0 1 2 8 9 4
0. 2 1 - 9 1 2 6 2 1 0 . 8 2 3 8 5 6 3 0 . 8 6 2 9 4 2 1 0 . 8 0 1 3 7 8 4
0. 1 1 - 9 8 0 2 2 1 0 . 9 2 8 4 5 5 3 0 . 9 6 3 8 1 2 1 0 . 9 0 1 7 6 7 4
0. 0 1 - 8 0 1 8 1 1 0 . 0 3 5 4 5 4 3 0 . 0 7 3 8 8 1 1 0 . 0 1 1 3 6 6 4
0. 9 - 2 7 2 4 1 1 0 . 1 3 4 7 5 3 3 0 . 1 7 1 9 5 1 1 0 . 1 1 1 2 6 5 4
0. 8 - 5 7 5 0 1 1 0 . 2 3 4 3 6 2 3 0 . 2 7 7 0 3 1 1 0 . 2 1 1 4 6 4 4
0. 7 - 0 1 0 7 0 1 0 . 3 3 3 2 7 1 3 0 . 3 7 1 3 0 1 1 0 . 3 1 1 7 6 3 4
0. 6 - 4 7 5 3 0 1 0 . 4 3 0 4 8 0 3 0 . 4 7 2 6 7 0 1 0 . 4 1 1 4 7 2 4
0. 5 - 0 6 2 0 0 1 0 . 5 3 6 8 9 9 2 0 . 5 7 1 0 5 0 1 0 . 5 1 1 2 8 1 4
0. 4 - 4 6 0 7 9 0 . 6 3 7 5 1 9 2 0 . 6 7 7 4 2 0 1 0 . 6 1 1 3 9 0 4
0. 3 - 1 8 9 3 9 0 . 7 3 5 5 3 8 2 0 . 7 7 0 1 0 . 7 1 1 6 0 0 4
0. 2 - 8 0 0 1 9 0 . 8 3 7 7 5 7 2 0 . 8 7 0 6 7 9 0 . 8 1 1 1 2 9 3
0. 1 - 9 3 1 8 8 0 . 9 3 3 2 8 6 2 0 . 9 7 6 2 5 9 0 . 9 1 1 8 3 8 3
0. 0 1 7 3 5 8 0 . 0 4 2 9 0 6 2 0 . 0 8 9 9 2 9 0 . 0 2 1 7 5 7 3
0. 1 9 9 6 2 8 0 . 1 4 3 8 3 5 2 0 . 1 8 7 7 0 9 0 . 1 2 1 8 7 6 3
0. 2 1 2 1 0 8 0 . 2 4 6 9 6 4 2 0 . 2 8 2 6 8 8 0 . 2 2 1 1 0 6 3
0. 3 2 3 6 7 7 0 . 3 4 0 3 0 4 2 0 . 3 8 3 5 6 8 0 . 3 2 1 6 2 5 3
0. 4 0 3 2 5 7 0 . 4 4 4 8 3 3 2 0 . 4 8 9 4 4 8 0 . 4 2 1 2 5 4 3
0. 5 0 1 9 2 7 0 . 5 4 8 5 7 2 2 0 . 5 8 0 5 2 8
0. 6 0 7 6 0 7 0 . 6 4 0 5 1 2 2 0 . 6 8 7 5 0 8
0. 7 7 0 5 8 6 0 . 7 4 1 6 5 1 2 0 . 7 8 9 6 8 7
0. 8 8 1 4 6 6 0 . 8 4 9 8 9 0 2 0 . 8 8 6 8 6 7
0. 9 9 9 3 4 6 0 . 9 4 5 3 4 0 2 0 . 9 8 7 0 5 7
0. 0 1 9 4 4 2 6 0 . 0 5 6 9 8 9 1 0 . 0 9 4 3 3 7
0. 1 1 5 6 5 0 6 0 . 1 5 4 7 3 9 1 0 . 1 9 5 6 1 7
0. 2 1 5 4 7 8 5 0 . 2 5 7 6 8 8 1 0 . 2 9 0 0 0 7
0. 3 1 5 8 9 6 5 0 . 3 5 5 7 3 8 1 0 . 3 9 0 4 8 6
0. 4 1 4 8 2 5 5 0 . 4 5 8 9 8 7 1 0 . 4 9 3 8 6 6
Page 19 of the Bard Packaged Heat Pump (PH1236) user manual — FIGURE 13 BRAZING DIAGRAM
Page 19 · click to enlarge
Page 19

SUCTION AND DISCHARGE TUBE BRAZING

  • To connect:

– Recommended brazing materials: silfos with minimum 5% silver or silver braze material with flux.

Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used. • To disconnect: heat joint Areas 2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting. (See Figure 10.)

– Reinsert tube into fitting.

– Heat tube uniformly in Area 1 moving slowly to Area 2. When joint reaches brazing temperature, apply brazing material. (See Figure 10.)

– Heat joint uniformly around the circumference to flow braze material completely around the joint.

– Slowly move torch into Area 3 to draw braze material into joint. (See Figure 10.)

– Do not overheat joint.

FIGURE 13 BRAZING DIAGRAM

Page 20 of the Bard Packaged Heat Pump (PH1236) user manual — TABLE 12
Page 20 · click to enlarge
Page 20

PRESSURE TABLES

TABLE 11

COOLING

Air Temperature Entering Outdoor Coil Degrees F

ri A n r u t e R

e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D . g e d 5 7 B W . g e d 2 6 e di S w o L

3 7 1 9 1 5 7 5 0 2 6 7 9 1 2 8 7 4 3 2 9 7 1 5 2 0 8 7 6 2 1 8 5 8 2 2 8 3 0 3 3 8 3 2 3

e di S h gi H

B D . g e d 0 8 B W . g e d 7 6 e di S w o L

8 7 6 9 1 0 8 0 1 2 1 8 5 2 2 3 8 0 4 2 4 8 7 5 2 8 8 4 7 2 7 8 2 9 2 8 8 1 1 3 9 8 1 3 3

e di S h gi H

B D . g e d 5 8 B W . g e d 2 7 e di S w o L

1 8 3 0 2 3 8 7 1 2 4 8 3 3 2 6 8 8 4 2 7 8 6 6 2 9 8 4 8 2 0 9 2 0 3 1 9 2 2 3 2 9 3 4 3

e di S h gi H

B D . g e d 5 7 B W . g e d 2 6 e di S w o L

3 7 8 0 2 5 7 2 2 2 6 7 7 3 2 8 7 4 5 2 9 7 0 7 2 9 7 8 8 2 1 8 7 0 3 2 8 6 2 3 4 8 6 4 3

e di S h gi H

B D . g e d 0 8 B W . g e d 7 6 e di S w o L

8 7 3 1 2 0 8 8 2 2 1 8 3 4 2 3 8 0 6 2 4 8 7 7 2 5 8 5 9 2 7 8 5 1 3 8 8 4 3 3 0 9 5 5 3

e di S h gi H

B D . g e d 5 8 B W . g e d 2 7 e di S w o L

1 8 0 2 2 3 8 6 3 2 4 8 2 5 2 6 8 9 6 2 7 8 7 8 2 8 8 5 0 3 0 9 6 2 3 1 9 6 4 3 3 9 7 6 3

e di S h gi H

B D . g e d 5 7 B W . g e d 2 6 e di S w o L

2 7 1 1 2 4 7 5 2 2 5 7 2 4 2 7 7 8 5 2 8 7 6 7 2 9 7 4 9 2 0 8 4 1 3 1 8 3 3 3 2 8 5 5 3

e di S h gi H

B D . g e d 0 8 B W . g e d 7 6 e di S w o L

7 7 6 1 2 9 7 1 3 2 0 8 8 4 2 2 8 5 6 2 3 8 3 8 2 4 8 2 0 3 6 8 2 2 3 7 8 2 4 3 8 8 4 6 3

e di S h gi H

B D . g e d 5 8 B W . g e d 2 7 e di S w o L

0 8 4 2 2 2 8 9 3 2 3 8 7 5 2 5 8 4 7 2 6 8 3 9 2 7 8 3 1 3 9 8 3 3 3 0 9 4 5 3 1 9 7 7 3

e di S h gi H

TABLE 12

HEATING

Air Temperature Entering Outdoor Coil Degrees F

n r u t e R

p m e T ri A . e r u s s e r P 0 5 0 1 5 1 7 1 0 2 5 2 0 3 5 3 0 4 5 4 7 4 0 5 5 5

4 2 2 1 H P g e d 0 7 e di S w o L

2 2 4 7 1 4 2 2 8 1 7 2 0 9 1 0 3 8 9 1 1 3 1 0 2 3 3 5 0 2 7 3 3 1 2 1 4 1 2 2 5 4 9 2 2 0 5 7 3 2 6 5 5 4 2 8 5 8 4 2 2 6 3 5 2 8 6 1 6 2

e di S h gi H

0 3 2 1 H P g e d 0 7 e di S w o L

1 2 7 6 1 3 2 0 7 1 5 2 4 7 1 8 2 8 7 1 9 2 9 7 1 1 3 2 8 1 4 3 7 8 1 8 3 2 9 1 3 4 7 9 1 8 4 3 0 2 3 5 0 1 2 5 5 3 1 2 9 5 7 1 2 5 6 4 2 2

e di S h gi H

6 3 2 1 H P g e d 0 7 e di S w o L

4 2 4 9 1 5 2 5 9 1 6 2 7 9 1 8 2 1 0 2 8 2 2 0 2 0 3 5 0 2 3 3 1 1 2 7 3 8 1 2 2 4 6 2 2 7 4 5 3 2 3 5 6 4 2 6 5 0 5 2 0 6 7 5 2 8 6 0 7 2

e di S h gi H

Low side pressure ± 2 PSIG High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow across the evaporator coil and should be found under section titled “Refrigerant Charge” elsewhere in manual. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.

Page 21 of the Bard Packaged Heat Pump (PH1236) user manual — Wiring Diagram (4098-123) printed
Page 21 · click to enlarge
Page 21

Wiring Diagram (4098-123) printed

from CAD to get size needed

Page 22 of the Bard Packaged Heat Pump (PH1236) user manual — Wiring Diagram (4098-124) printed
Page 22 · click to enlarge
Page 22

Wiring Diagram (4098-124) printed

from CAD to get size needed

Page 23 of the Bard Packaged Heat Pump (PH1236) user manual — Wiring Diagram (4098-211) printed
Page 23 · click to enlarge
Page 23

Wiring Diagram (4098-211) printed

from CAD to get size needed

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Compressorcontactor doesnotenergize (heatingorcooling)ContilcircuitwiringCheckforRconnectionatunit and24voltbetweenR-C. p.17
Compressorcontactor doesnotenergize (heatingorcooling)Compressorlockout1.Checkfor24Vbetween L1-Conheatpumpcontrol 2.Checkacrosshigh pressureswitch. p.17
Compressorcontactor doesnotenergize (heatingorcooling)Compressorshortcycle protectionCheckfor24VbetweenCC-C andY-Conheatpump control. p.17
Compressorcontactor doesnotenergize (heatingorcooling)Heatpumpcontrol defectiveCheckallotherpossible causes. Manual2100-065. p.17
Compressorcontactor doesnotenergize (heatingorcooling)ContactordefectiveCheckforopenorshorted coilwinding. p.17
Fanoutdoormotor doesnotrun (coolingorheating exceptduringdefrost)MotordefectiveCheckforopenorshorted motorwinding. p.17
Fanoutdoormotor doesnotrun (coolingorheating exceptduringdefrost)MotorcapacitordefectiveCheckcapacitorrating. Checkforopenorshorted capacitor. p.17
Fanoutdoormotor doesnotrun (coolingorheating exceptduringdefrost)Heatpumpcontrol defectiveCheckacrossfanrelayon heatpumpcontrol.(Com-NC) p.17
Reversingvalvedoes notenergize (heatingonly)Reversingvolvesolenoid coildefectiveCheckforopenorshorted coil. p.17
Reversingvalvedoes notenergize (heatingonly)Heatpumpcontrol defectiveCheckfor24VbetweenRV-C andB-C. p.17
Unitwillnotgointo defrost (heatingonly)Temperaturesensoror heatpumpcontrol defectiveDisconnecttemperature sensorfromboardand jumperacrossspeedup terminalsandsenjump terminals. Thisshouldcause theunittogothrougha defrostcyclewithinone minute. p.17
Unitwillnotcomeout ofdefrost (heatingonly)Temperaturesensoror heatpumpcontrol defective.Jumperacrossspeedup terminals. Thisshouldcause theunittocomeoutofdefrost withinoneminute. p.17

Ask about the Bard Packaged Heat Pump (PH1236)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bard Packaged Heat Pump (PH1236)

Be the first to ask — other owners or our team will answer.

Original document

Bard Packaged Heat Pump (PH1236) manual PDF

23 pages·164 KB·Electric Heater·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…