INSTALLATION INSTRUCTIONS AND PARTS LIST TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS

– FOR RESIDENTIAL INSTALLATIONS –

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS AND

ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE POINT OF INSTALLATION.

RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE REFERENCE.

Model No. Serial No.

FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do

Sterling RF-30 — – FOR RESIDENTIAL INSTALLATIONS – diagram (page 1)
Fig. 1

not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call your fire department.

Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operating, and maintenance instruction thoroughly before installing or servicing this equipment.

APPROVED FOR USE IN CALIFORNIA

Install, operate, and maintain unit in accordance with the manufacturer's instructions to avoid exposure to fuel substances, or substances from incomplete combustion, which can cause death or serious illness. The state of California has determined that these substances may cause cancer, birth defects, or other reproductive harm.

INSTALLER'S RESPONSIBILITY Installer Please Note: This equipment has been test fired and inspected. It has been shipped free from defects from our factory. However, shipment and installation problems such as loose wires, leaks, or loose fasteners may occur. It is the installer's responsibility to inspect and correct any problem that may be found.

RECEIVING INSTRUCTIONS Inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment. After the unit has been uncrated, check for any visible damage to the unit. If any damage is found, the consignee should sign the bill of lading indicating such damage and immediately file claim for damage with the transportation company.

HVAC PRODUCTS

260 NORTH ELM ST., WESTFIELD, MA 01085 TEL: (413) 564-5540 FAX: (413) 562-5311

www.sterlinghvac.com

MODELS: RF-30, 45, 60, 75, 90

10/05 Please utilize this toll free number to contact your local representative 800-490-2290.

Page 3 of the Sterling RF-30 user manual — GENERAL SAFETY INFORMATION
Page 3 · click to enlarge
Page 3

GENERAL SAFETY INFORMATION

Failure to comply with the general safety information may result in extensive property damage, severe personal injury, or death.

Make certain that the power source conforms to the electrical requirements of the heater.

Do not depend upon a thermostat or other switch as sole means of disconnecting power when installing or servicing heater. Always disconnect power at main circuit breaker as described above. Failure to do so could result in fatal electric shock.

This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.

Installation must be made in accordance with local codes, or in absence of local codes, with the latest edition of ANSI Standard Z223.1 (N.F.P.A. No. 54) National Fuel Gas Code. All of the ANSI and NFPA Standards referred to in these installation instructions are those that were applicable at the time the design of this appliance was certified.The ANSI Standards are available from CSA Information Services 1-800-463-6727. The NFPA Standards are available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.

Special attention must be given to any grounding information pertaining to this heater. To prevent the risk of electrocution, the heater must be securely and adequately grounded. This should be accomplished by connecting a ground conductor between the service panel and the heater. To ensure a proper ground, the grounding means must be tested by a qualified electrician.

Do not insert fingers or foreign objects into heater or its air moving device. Do not block or tamper with the heater in any manner while in operation, or just after it has been turned off, as some parts maybe hot enough to cause injury.

If installed in Canada, the installation must conform with local building codes, or in the absence of local building codes, with CGA-B149.1 "Installation Codes for Natural Gas Burning Appliances and Equipment" or CGA-B149.2 "Installation Codes for Propane Gas Burning Appliances and Equipment." These unit heaters have been designed and certified to comply with CGA 2.6.

This heater is intended for general heating applications ONLY. It must NOT be used in potentially dangerous locations such as flammable, explosive, chemical-laden, or wet atmospheres.

Do not alter the unit heater in any way or damage to the unit and/or severe personal injury or death may occur!

Do not attach ductwork to this product or use it as a makeup air heater. Such usage voids the warranty and will create unsafe operation.

In cases in which property damage may result from malfunction of the heater, a back-up system or temperature sensitive alarm should be used.

Disconnect all power and gas supplies before installing or servicing the heater. If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power. Failure to do so could result in fatal electric shock, or severe personal injury.

Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.

Ensure that all power sources conform to the requirements of the unit heater, or damage to the unit will result!

The open end of piping systems being purged shall not discharge into areas where there are sources of ignition or into confined spaces UNLESS precautions are taken as follows: (1) by ventilation of the space, (2) control of the purging rate, (3) elimination of all hazardous conditions. All precautions must be taken to perform this operation in a safe manner!

Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All wiring should be done and checked by a qualified electrician, using copper wire only. All gas connections should be made and leak- tested by a suitably qualified individual, per instructions in this manual. Also follow procedures listed on "Gas Equipment Start-Up Sheet" located in this manual.

Unless otherwise specified, the following conversions may be used for calculating SI unit measurements: 1 foot = 0.305 m 1 inch = 25.4 mm 1 gallon = 3.785 L 1 pound = 0.453 kg 1 psig = 6.894 kPa 1 cubic foot = 0.028m3

1000 BTU/cu. ft. = 37.5 MJ/m3 1000 BTU per hour = 0.293 kW 1 inch water column = 0.249 kPa liter/second = CFM x 0.472 meters/second = FPM ÷ 196.8

Use only the fuel for which the heater is designed (see rating plate). Using LP gas in a heater that requires natural gas, or vice versa, will create risk of gas leaks, carbon monoxide poisoning, and explosion.

Do not attempt to convert the heater for use with a fuel other than the one intended. Such conversion is dangerous, as it will create the risks previously listed.

Page 4 of the Sterling RF-30 user manual — GENERAL SAFETY INFORMATION
Page 4 · click to enlarge
Page 4

Table 1 - Performance and Dimensional Data - Tubular 30 thru 90 Propeller Unit Heater

Unit Size 3045 60 7590 PERFORMANCE DATA† Input - BTU/Hr. 30,000 (kW) (8.8) Output - BTU/Hr. 24,300 (kW) (7.1)45,000 60,000 75,000 (13.2) (17.6) (22.0) 36,450 48,600 60,750 (10.7) (14.2) (17.8)90,000 (26.4) 72,900 (21.4) Thermal Efficiency (%) 81 Free Air Delivery - CFM 500 (cu. m/s) (0.236) Air Temperature Rise - Deg. F 45 (Deg. C) (25) Full Load Amps at 120V 3.081 81 81 750 1,000 1,250 (0.355) (0.473) (0.591) 45 45 45 (25) (25) (25) 3.0 3.7 3.781 1,500 (0.710) 45 (25) 4.8 MOTOR DATA: Motor HP 1/20 Motor (kW) (0.04) Motor Type SP R.P.M. 1650 Motor Amps @ 115V 1.91/20 1/20 1/20 (0.04) (0.04) (0.04) SP SP SP 1650 1050 1050 1.9 2.6 2.61/20 (0.04) SP 1050 2.6 DIMENSIONAL DATA - inches (mm) “A” Jacket Height 12 (305) “B” Overall Height 13 (330) “C” Overall Depth 25-1/2 (648)12 17-3/4 17-3/4 (305) (451) (451) 13 18-3/4 18-3/4 (330) (476) (476) 25-1/2 26-3/4 26-3/4 (648) (679) (679)17-3/4 (451) 18-3/4 (476) 26-3/4 (679) “Center Line” Height of Flue* 7-1/4 (184) “Center Line” Electric Connection 10-1/4 (260) “F” Discharge Opening Height 10-1/2 (267) “G” Fan Diameter-in 107-1/4 10-1/2 10-1/2 (184) (267) (267) 10-1/4 16 16 (260) (406) (406) 10-1/2 16-1/4 16-1/4 (267) (413) (413) 10 16 1610-1/2 (267) 16 (406) 16-1/4 (413) 16 Unit Weight - lbs. 62 (kgs) (28) Shipping Weight - lbs. 72 (kgs) (33)68 87 93 (31) (39) (42) 78 102 108 (35) (46) (49)95 (43) 110 (50)

* For all installations, the flue collar is included with the unit and should be field installed per the instructions included with the unit.

† Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea

level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54), (also refer to Table 6).

For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certification.

DIMENSIONS .XXX STANDARD UNITS DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS

Figure 2 - Dimensional Drawing – Tubular 30 thru 90 Propeller Unit Heater

Page 5 of the Sterling RF-30 user manual — INSTALLATION
Page 5 · click to enlarge
Page 5

INSTALLATION

Do not install unit heaters in corrosive or flammable atmospheres! Premature failure of, or severe damage to the unit will result!

AIR FOR COMBUSTION: The unit heater shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas, proper venting, and the maintenance of ambient air at safe limits under normal conditions of use. The unit heater shall be located in such a manner as not to interfere with proper circulation of air within the confined space. When buildings are so tight that normal infiltration does not meet air requirements, outside air shall be introduced per Sections 1.3.4.2 and 1.3.4.3 of ANSI Z223.1 for combustion requirements. A permanent opening or openings having a total free area of not less than one square inch per 5,000 BTU/Hr (1.5 kW) of total input rating of all appliances within the space shall be provided.

Avoid locations where extreme drafts can affect burner operation. Unit heaters must not be installed in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!

Since the unit is equipped with an automatic gas ignition system, the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray, rain or dripping water.

CLEARANCES: Each Gas Unit Heater shall be located with respect to building construction and other equipment so as to permit access to the Unit Heater. Clearance between vertical walls and the vertical sides of the Unit Heater shall be no less than 1 inch (25.4mm). However, to ensure access to the control box and fan, a minimum of 18" (457mm) is required for the fan, and control box side. A minimum clearance of 1 inch (25.4mm) must be maintained between the top of the Unit Heater and the ceiling. The bottom of the Unit Heater must be no less than 1 inch (25.4mm) from any combustible. The distance between the flue collector and any combustible must be no less than 1 inch (25.4mm). Also see AIR FOR COMBUSTION and VENTING sections.

MOUNTING HEIGHT: If the unit heater is installed in a garage, it must be installed with a minimum clearance above the floor of 18 inches (457mm).

AIR DISTRIBUTION: Direct air towards areas of maximum heat loss. When multiple heaters are involved, circulation of air around the perimeter is recommended where heated air flows along exposed walls. Satisfactory results can also be obtained where multiple heaters are located toward the center of the area with heated air directed toward the outside walls. Be careful to avoid all obstacles and obstructions which could impede the warm air distribution patterns.

Unit heaters should not be installed to maintain low temperatures and/or freeze protection of buildings. A minimum of 50°F (10°C) thermostat setting must be maintained. If unit heaters are operated to maintain lower than 50°F (10°C), hot flue gases are cooled inside the heat exchanger to a point where water vapor (a flue gas by-product) condenses onto the heat exchanger walls. The result is a mildly corrosive acid that prematurely corrodes the aluminized heat exchanger and can actually drip water down from the unit heater onto floor surface. Additional unit heaters should be installed if a minimum 50°F (10°C) thermostat setting cannot be maintained.

MOUNTING: The Unit Heater may be mounted with the vent outlet, gas and electrical connections to the right or left of the air moving fan. The Unit Heater is shipped with the connections to the right of the fan when looking in the direction of the air flow. If connections to the right are required, remove hanger brackets from face of unit and attach as pictured in Figure 3. If connections to the left are required, invert the heater (180°), mount the hanging brackets as above, and remove, invert, and replace the control access panel and the air discharge louvers.

Page 6 of the Sterling RF-30 user manual — INSTALLATION (continued)
Page 6 · click to enlarge
Page 6

INSTALLATION (continued)

The Unit Heater may be mounted by fastening the hanging brackets directly to ceiling joists or by suspending from four rods. See Figures 3, 4 and 5.

Figure 3 - Hanger Bracket Installation Instructions

Sterling RF-30 — INSTALLATION (continued) diagram (page 6)
Fig. 2 · INSTALLATION (continued)

Make certain that the lifting methods used to lift the heater and the method of suspen- sion used in the field installation of the heater are capable of uniformly supporting the weight of the heater at all times. Failure to heed this warning may result in property damage or personal injury!

Make sure that the structure to which the unit heater is to be mounted is capable of safely supporting its weight. Under no circumstances must the gas lines, the venting system or the electrical conduit be used to support the heater; or should any other objects (i.e. ladder, person) lean against the heater gas lines, venting system or the electrical conduit for support. Failure to heed these warnings may result in property damage, personal injury, or death.

Figure 4 - Heater Mounting (Steel Construction)

Sterling RF-30 — INSTALLATION (continued) diagram (page 6)
Fig. 3 · INSTALLATION (continued)

Unit Heaters must be hung level from side to side and from front to back, see Figures 3, 4 and 5. Failure to do so will result in poor performance and/or premature failure of the unit.

Ensure that all hardware used in the suspension of each unit heater is more than adequate for the job. Failure to do so may result in extensive prop- erty damage, severe personal injury, or death!

Figure 5 - Heater Mounting (Wood Construction)

Sterling RF-30 — INSTALLATION (continued) diagram (page 6)
Fig. 4 · INSTALLATION (continued)

Refer to Figures 3, 4 and 5 for suspension of units.

Page 7 of the Sterling RF-30 user manual — GAS PIPING
Page 7 · click to enlarge
Page 7

GAS PIPING

To avoid damage or possible personal injury, do not connect gas piping to this unit until a supply line pressure/leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fire hazard.

Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak tests. These valves may not be completely shut off, exposing the gas valve to excessive pressure and damage.

PIPE SIZING To provide adequate gas pressure to the gas unit heater, size the gas piping as follows:

1. Find the cu. ft./hr. by using the following formula:

Input Cu. ft./hr. =

BTU 2. Refer to Table 2. Match “Length of Pipe in Feet” with appropriate “Gas Input - Cu. Ft./Hr.” figure. This figure can then be matched to the pipe size at the top of the column. Example: It is determined that a 67 foot (20.4m) run of gas pipe is required to connect a 75 MBTU gas unit heater to a 1,000 BTU/cu ft. (0.29kW) natural gas supply.

NOTICE: HEATER INSTALLATION FOR USE WITH PROPANE (BOTTLED) GAS MUST BE MADE BY A QUALIFIED L.P. GAS DEALER OR INSTALLER. HE WILL ENSURE THAT PROPER JOINT COMPOUNDS ARE USED FOR MAKING PIPE CONNECTIONS; THAT AIR IS PURGED FROM LINES; THAT A THOROUGH TEST IS MADE FOR LEAKS BEFORE OPERATING THE HEATER; AND THAT IT IS PROPERLY CONNECTED TO THE PROPANE GAS SUPPLY SYSTEM.

75,000 BTU/Hr = 75 Cu. ft./hr.

1,000 BTU/cu. ft. Using Table 2, a 3/4 inch pipe is needed.

Before any connection is made to the existing line supplying other gas appliances, contact the local gas company to make sure that the existing line is of adequate size to handle the combined load.

Table 2 - Gas Pipe Size

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less,

and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)

(Based on a 0.60 Specific Gravity Gas) Nominal

Iron Internal Length of Pipe, Feet (meters)

Pipe Size Dia. 10 20 30 40 50 60 70 80 90 100 125 150 175 200 in. in. (3.0) (6.1) (9.1) (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0) 1/2 0.622 175 120 97 82 73 66 61 57 53 50 44 40 37 35 (4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99) 3/4 0.824 360 250 200 170 151 138 125 118 110 103 93 84 77 72 (10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04) 1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 (19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82) 1 1/4 1.380 1400 950 770 660 580 530 490 460 430 400 360 325 300 280 (39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93) 1 1/2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430 (59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2) 2 2.067 3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020 950 850 800 (112) (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7) 2 1/2 2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850 1650 1500 1370 1280 (178) (123) (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2) 3 3.068 11000 7700 6250 5300 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280 (311) (218) (177) (150) (135) (122) (110) (105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6) 4 4.026 23000 15800 12800 10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600 (651) (447) (362) (309) (275) (249) (229) (212) (204) (190) (170) (156) (142) (130)

1. Determine the required Cu. Ft./Hr. by dividing the input by 1000. For SI/Metric measurements: Convert BTU/Hr. to kilowatts. Multiply the units inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE GAS: Multiply the Cu. Ft./Hr. value by 0.633; then, use the table. 4. Refer to the metric conversion factors listed in the General Safety section for SI Unit measurement conversions.
Page 8 of the Sterling RF-30 user manual — SINGLE STAGE GAS PIPING REQUIREMENTS*
Page 8 · click to enlarge
Page 8

PIPE INSTALLATION

1. Install the gas piping in accordance with applicable local codes. 2. Check gas supply pressure. Each unit heater must be connected to a gas supply capable of supplying its full rated capacity as specified in Table 3. A field LP tank regulator must be used to limit the supply pressure to a maximum of 14 in. W.C. (3.5 kPa). All piping should be sized in accordance with the latest edition of ANSI Standard Z223.1 National Fuel Gas Code; in Canada, according to CGA-B149. See Tables 1 & 2 for correct gas piping size, and also refer to Tables 3, 5 and 6. If gas pressure is excessive on natural gas applications, install a pressure regulating valve in the line upstream from the main shutoff valve. 3. Adequately support the piping to prevent strain on the gas manifold and controls. 4. To prevent the mixing of moisture with gas, run the take-off piping from the top, or side, of the main. 5. Standard Unit Heaters are supplied with a combination valve which includes: a. Manual "A" valve b. Manual "B" valve c. Solenoid valve d. Pressure regulator Pipe directly into the combination valve (see Figure 6). 6. Gas valve has a pressure test post requiring a 3/32" hex head wrench to read gas supply and manifold pressures. Open 1/4 turn counterclockwise to read, turn clockwise to close and reseat. A 5/16" ID hose fits the pressure post. 7. Provide a drip leg in the gas piping near the gas unit heater. A ground joint union and a manual gas shutoff valve should be installed ahead of the unit heater controls to permit servicing. The manual shutoff valve must be located external to the jacket. (See Figure 6) 8. Make certain that all connections have been adequately doped and tightened.

Do not over tighten the inlet gas piping into the valve. This may cause stresses that will crack the valve!

Check all pipe joints for leakage using a soap solution or other approved method. Never use an open flame or severe personal injury or death may occur!

Figure 6 - Pipe Installation, Standard Controls

Never use an open flame to detect gas leaks. Explosive conditions may exist which may result in personal injury or death!

The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system in excess of 1/2 psig (3.5 kPa).

Table 3 - Gas Piping Requirements

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

SINGLE STAGE GAS PIPING REQUIREMENTS*

GasType Natural Gas Propane (LP) Gas

Manifold 3.5 in. W.C. 10.0 in. W.C. Pressure (0.9 kPa) (2.5 kPa)

14.0 in. W.C. Max. 14.0 in. W.C. Max. Supply Inlet (3.5 kPa) (3.5 kPa) Pressure 5.0 in. W.C. Min. 11.0 in W.C. Min. (1.2 kPa) (2.7 kPa)

*For single stage application only at normal altitudes.

Page 9 of the Sterling RF-30 user manual — W R
Page 9 · click to enlarge
Page 9

ELECTRICAL CONNECTIONS

THERMOSTAT WIRING AND LOCATION:

HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.

Mount the thermostat approximately 5 feet (1.5m) above the floor, in an area where it will be exposed to a free circulation of average temperature air. Always refer to the thermostat instructions, as well as our unit wiring diagram, and wire accordingly. Avoid mounting the thermostat in the following locations: 1. Cold Areas- Outside walls or areas where drafts may affect the operation of the control. 2. Hot Areas- Areas where the sun's rays, radiation, or warm air currents may affect the operation of the control. 3. Dead Areas- Areas where the air cannot circulate freely, such as behind doors or in corners.

Standard units are shipped for use on 115 volt, 60 hertz, single phase electric power. The motor name-plate and electrical rating of the transformer should be checked before energizing the unit heater electrical system. All external wiring must conform to the latest edition of ANSI/NFPA No. 70, National Electrical Code, and applicable local codes; in Canada, to the Canadian Electrical Code, Part 1, CSA Standard C22.1.

Do not use any tools (i.e. screwdriver, pliers, etc.) across terminals to check for power. Use a voltmeter.

THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS: The initial heat anticipator setpoint should equal the thermostat's current amperage draw when the unit is firing. This setpoint should be measured for the best results. Use the recommended ranges for a guide. If further information is needed, consult your thermostat manufacturer's instructions.

It is recommended that the electrical power supply to each unit heater be provided by a separate, fused, and permanently live electrical circuit. A disconnect switch of suitable electrical rating should be located as close to the gas valve and controls as possible. Each unit heater must be electrically grounded in accordance with the latest edition of the National Electrical Code, ANSI/NFPA No. 70, or CSA Standard C22.1. Refer to Figures 7, 8 and 9.

Recommended heat anticipator setting:

30 thru 200250 thru 400 0.35 Amps0.65 Amps

Figure 7 - Low-voltage Thermostat Wiring Single Stage

Figure 8 - T834H-1009 or T834H-1017 Thermostat Wiring

between G and R inside control panel

W R

R G W1 W2

G

D6922

Honeywell T834H-1009 · or T834H-1017 · Thermostat

Page 10 of the Sterling RF-30 user manual — ELECTRICAL CONNECTIONS (continued)
Page 10 · click to enlarge
Page 10

ELECTRICAL CONNECTIONS (continued)

Figure 9 - Tubular Propeller Units Equipped with a Rollout Switch

Tubular 30 thru 90 Unit Sizes with Natural and Propane (LP) Gas

Sterling RF-30 — ELECTRICAL CONNECTIONS (continued) diagram (page 10)
Fig. 5 · ELECTRICAL CONNECTIONS (continued)
Page 11 of the Sterling RF-30 user manual — VENTING*
Page 11 · click to enlarge
Page 11

VENTING*

All unit heaters must be vented! All Venting installations shall be in accordance with the latest edition of Part 7, Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of local building codes. Refer to notes* below for Canadian installations. Refer to Figures 12-19.

CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow drifts, or any foreign matter. Inspect your venting system to ensure adequate ventilation exists at all times! Failure to heed these warnings could result in Carbon Monoxide Poisoning (symptoms include grogginess, lethargy, inappropriate tiredness, or flu-like symptoms).

When an existing heater is removed or replaced in venting system, the venting system may not be properly sized to vent the attached appliances. An improperly sized vent system can cause formulation of condensate or leakage or spillage of flue gases.

4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so that the appliance will operate continuously. 5. After it has been determined that each appliance connected to the venting system properly vents when tested as outline above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous condition of use. 6. If improper venting is observed during any of the above tests, the venting system must be corrected immediately so that the system conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the venting system, the venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the National Fuel Gas Code, ANSI Z223.1.

The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system; 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition. 3. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace damper.

The unit heater shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney is prohibited.

ADDITIONAL REQUIREMENTS FOR CANADIAN INSTALLATIONS *The following instructions apply to Canadian installations in addition to installation and operating instructions. 1. Installation must conform with local building codes, or in the absence of local codes, with current CGA-B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CGA-B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment. 2. Any reference to U.S. standards or codes in these instructions are to be ignored and the applicable Canadian standards or codes applied.

Page 12 of the Sterling RF-30 user manual — VERTICALLY VENTED UNIT HEATERS
Page 12 · click to enlarge
Page 12

VENTING

ANSI now organizes vented appliances into four categories.

Category I Includes non-condensing appliances with negative vent pressure, like the traditional atmospheric unit heater.

Category III Appliances are non-condensing and operate with a positive vent pressure.

Category IV Covers condensing appliances with positive vent pressure.

Category II Groups condensing appliances with negative vent pressure.

Negative Vent PressureIII Positive Vent PressureIIIIV

VERTICALLY VENTED UNIT HEATERS

(CATEGORY I )

Observe the following precautions when venting the unit: The unit heater shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney is prohibited. 1. Use flue pipe of the same size as the flue connections on the gas unit heater, 4 inch (102mm). All heaters must be vented with UL Listed Type B vent, or single wall pipe. 2. Provide as long a vertical run of flue pipe at the gas unit heater as possible. A minimum of 5 feet (1.5m) of vertical flue is required. The top of the vent pipe should extend at least 2 feet (0.61m) above the highest point on the roof. Install a weather cap over the vent opening. 3. Slope horizontal runs upward from the gas unit heater at least 1/4-inch per foot (21mm/m) minimum. Horizontal runs should not exceed 33% of the vertical height of the vent pipe, or chimney, above the flue pipe connection, up to a maximum length of 10 feet (3m). Horizontal portions of the venting system shall be supported at maximum intervals of 4 feet (1.22m). (See Figure 12)

4. Use as few elbows as possible. 5. Tape flue pipe joints with high temp, RTV or foil face tape. 6. Avoid running vent pipe through unheated spaces. 7. When this cannot be avoided, insulate the pipe to prevent condensation of moisture on the walls of the pipe. Insulate vent pipe runs longer than 10 feet (3m). Insulation should be a minimum of 1/2 inch (12.7mm) thick foil faced fiberglass, 1-1/2# density insulation. 8. Do not damper the flue piping. Failure to open such a damper prior to operating the gas unit heater will result in the spillage of flue gas into the occupied space. 9. Avoid installing units in areas under negative pressure due to large exhaust fans or air conditioning. When required, a flue vent fan should be installed in accordance with the instructions included with the fan. 10. Vent connectors serving Category I and Category II heaters shall not be connected into any portion of mechanical draft systems operating under positive pressure. 11. Also refer to Figures 17 and 19 for additional requirements.

Venting Categories

Page 13 of the Sterling RF-30 user manual — HORIZONTALLY VENTED UNIT HEATERS (CATEGORY I - U.S. RESIDENTIAL ONLY)
Page 13 · click to enlarge
Page 13

HORIZONTALLY VENTED UNIT HEATERS (CATEGORY I - U.S. RESIDENTIAL ONLY)

All venting of residential tubular unit heaters must comply with CSA International Requirement 10.96 U.S. for Unit Heaters for Residential Use (2nd Edition).

Maintain 1 inch (25.4mm) between the vent pipe and combustible materials.

The vent terminal must be installed with a minimum horizontal clearance of 4 feet (1.2m) from electric meters, gas meters, regulators, and relief equipment.

Category I horizontal venting arrangements are designed to be used with either single wall vent pipe or double wall (Type B) vent pipe. These arrangements must terminate external to the building using either single wall or double wall (Type B) vent. See Table 4 and Figures 13 and 14 for special installation requirements regarding these venting conditions.

The horizontal portion of the vent pipe must not exceed 8 feet (2.44m) for the 30 unit size or 10 feet (3.05m) for the 45 to 90 unit sizes. The minimum length for the horizontal portion of the vent pipe is 4 feet (1.22m). The vent system must be constructed as shown in Table 4 and Figure 13. The vent pipe and vertical extension must be supported as shown in Figure 14.

An Amerivent Americap, Fields Starkap, or Metalbestos vent cap must be supplied by the customer for each power vented unit.

Seal all vent pipe joints and seams to prevent leakage. Use General Electric RTV-108, Dow-Corning RTV-732, or equivalent silicone sealant with a temperature rating of 500°F, or 3M #425 aluminum foil tape (or equivalent). The vent system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot (21mm per meter) toward the outlet for condensate drainage. Install a tee with a condensate drain at the low point of the pipe (See Figure 13). As an alternate, a 3/8 inch diameter hole may be drilled at the low point of the pipe for condensate drainage.

Vent Systems Termination Clearance Requirements

Door, window or any gravity vent inlet

Forced air inlet within 10 ft.

Adjoining building or parapet

7 feet above grade

The venting system for these appliances shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontal from, or 1 foot (0.3m) above any door, window, or gravity vent air inlet into the building.

Horizontal portions of the venting systems shall be supported at maximum intervals of 4 feet (1.2m) to prevent sagging.

Insulate single wall vent pipe exposed to cold air or running through unheated areas.

The vent terminal must be at least 12 inches (305mm) from the exterior of the wall that it passes through to prevent degradation of the building material by flue gases.

Local codes may supersede any of the above provisions.

The vent terminal must be at least 3 feet (1m) above grade, or in snow areas, at least 3 feet (1m) above the snow line to prevent blockage by snow.

Each unit must have an individual vent pipe and vent terminal! Each unit MUST NOT be connected to other vent systems or to a chimney.

Through the wall vent for these appliances shall NOT terminate over public walkways, or over an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.

Show 8 more labels / short text on this page
Minimum Clearances for · Termination Locations Structure · 4 feet below · 4 feet horizontally · 1 foot above · 3 feet above · 6 feet · Adjacent public walkways
Page 14 of the Sterling RF-30 user manual — D-06838A
Page 14 · click to enlarge
Page 14

Table 4 - Category I Horizontal Venting Requirements

Vent Maximum Number Maximum Horizontal Minimum Extension Unit Diameter Elbows Vent Length Vertical Rise Distance Size (in) * (Ft.) (In.) from Wall

30 4 1 4 12 36 4 1 8 18 36 4 2 4 12 36 4 2 8 18 36

45 4 1 10 18 36 4 2 5 18 36 5 2 10 12 36

60 5 2 10 12 36

75 5 2 10 24 36

90 5 1 10 24 24 5 2 10 36 24

*One elbow is required to make the vertical extension, See Figure 13.

Figure 13 - Category I Horizontal Venting Requirements

D-06838A

Page 15 of the Sterling RF-30 user manual — D06839A
Page 15 · click to enlarge
Page 15

Figure 14 - Vent Support

D06839A

Page 16 of the Sterling RF-30 user manual — HORIZONTALLY VENTED UNIT HEATERS
Page 16 · click to enlarge
Page 16

HORIZONTALLY VENTED UNIT HEATERS

(CATEGORY III )

All venting of residential tubular unit heaters must comply with the latest edition of CSA .10.96 (2nd ed.) requirement.

The vent pipe equivalent length must not exceed 30 feet (9.14m) for the 30 and 45 unit sizes, and 40 feet (12.2m) for the 60, 75 and 90 unit sizes. Equivalent length is the total length of straight sections PLUS 5 feet (1.52m) for each 90 elbow and 2.5 feet (0.76m) for each 45 elbow.

Vent Systems Termination Clearance Requirements

Category III horizontal venting arrangements are designed to use single wall vent pipe. These arrange- ments must terminate external to the building using either single wall or double wall (Type B) vent. See Figures 15, 16, and 18 for installa- tion requirements regarding these venting conditions. If double wall venting is used, components that are UL Listed and approved for Category III positive pressure venting systems must be used with one exception: a single 5 foot (1.52 M) section of 4 inch (102mm) Type B vent pipe with a draft hood connector may be used between the appliance vent connection and the vent terminal. Use Metalbestos Type B Gas Vent with a Metalbestos 4RV-DH Draft Hood Connector or Amerivent Type B Gas Vent with an Amerivent 4EDC Draft Hood Connector. See Figure 15A. If using a single section of Type B vent pipe, seal the annular space between the inner and outer sections of the draft hood connector with high temperature silicone sealant. See Figure 15B. Attach the draft hood connector to the appliance vent connection with screws and seal the joint with silicone sealant. Install a Type B vent thimble in the wall. Insert the vent pipe through the thimble and attach it to the adapter on the appliance. Seal the joint with silicone sealant or two wraps of aluminum foil tape. Install a vent cap on the outlet of the pipe and secure it with screws.

Door, window or any gravity air inlet

Maintain 1 inch (25.4mm) between the vent pipe and combustible materials.

Forced air inlet within 10 ft.

The vent terminal must be installed with a minimum horizontal clearance of 4 feet (1.2m) from electric meters, gas meters, regulators, and relief equipment.

Adjoining building or parapet

7 feet above grade

The venting system for these appliances shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontal from, or 1 foot (0.3m) above any door, window, or gravity vent air inlet into the building.

Seal all vent pipe joints and seams to prevent leakage. Use General Electric RTV-108, Dow-Corning RTV-732, or equivalent silicone sealant with temperature rating of 500°F; or 3M #425 aluminum foil tape (or equivalent). The vent air system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot (21mm per meter) toward the outlet for condensate drainage.

The vent terminal must be at least 12 inches (305mm) from the exterior of the wall that it passes through to prevent degradation of the building material by flue gases.

The vent terminal must be at least 1 foot (305mm) above grade, or in snow areas, at least 3 feet (1m) above the snow line to prevent blockage by snow.

Horizontal portions of the venting systems shall be supported at maximum intervals of 4 feet (1.2m) to prevent sagging (in Canada, support at 3 feet (1m) minimum intervals).

Through the wall vent for these appliances shall NOT terminate over public walkways, or over an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.

Insulate single wall vent pipe exposed to cold air or running through unheated areas. Insulate vent pipe runs longer than 10 feet (3m). Insulation should be a minmum of 1/2 inch thick foil faced fiberglass, 1-1/2# density insulation.

Each unit must have an individual vent pipe and vent terminal! Each unit MUST NOT be connected to other vent systems or to a chimney.

An Amerivent Americap, Fields Starcap, or Metalbestos vent cap must be supplied by the customer for each power vented unit. The vent pipe diameter MUST be 4 inches (102mm).

Show 10 more labels / short text on this page
Minimum Clearances for · Structure · Termination · Locations · 4 feet below · 4 feet horizontally · 1 foot above · 3 feet above · 6 feet · Adjacent public walkways
Page 17 of the Sterling RF-30 user manual — HORIZONTALLY VENTED UNIT HEATERS
Page 17 · click to enlarge
Page 17

Figure 15 - Category III Horizontal Venting Requirements Using Single Wall Vent Pipe

Figure 15A - Category III Horizontal Venting Requirements Using Type B Double Wall Vent Pipe

Figure 15B - Type B Draft Hood Connector

Page 18 of the Sterling RF-30 user manual — VENTING (continued)
Page 18 · click to enlarge
Page 18

VENTING (continued)

Page 19 of the Sterling RF-30 user manual — VENTING (continued)
Page 19 · click to enlarge
Page 19

VENTING (continued)

Page 20 of the Sterling RF-30 user manual — DIRECT SPARK IGNITION
Page 20 · click to enlarge
Page 20

OPERATION POWER VENTED PROPELLER UNITS

DIRECT SPARK IGNITION

EXPLANATION OF CONTROLS (See Figure 20): 1. Each Unit Heater comes equipped with a power vent system that consists of a power venter motor and blower, pressure switch, and sealed flue collector in place of the conventional draft diverter. 2. The power venter motor is energized by the room thermostat through the integrated control board when a demand for heat is sensed. The pressure switch measures the flow through the vent system and energizes the direct spark ignition system beginning the pre-purge timing when the flow is correct.

8. The wall thermostat, supplied optionally, is a temperature sensitive switch that operates the vent system and ignition system to control the temperature of the space being heated. The thermostat must be mounted on a vertical, vibration-free surface free from air currents and in accordance with the furnished instructions (also refer to Electrical Section).

START-UP (Also refer to lighting instruction plate equipped on the unit) 1. Open the manual gas valve in the gas supply line to the unit heater with union connection loose, purge air from the gas line. Tighten the union and check for leaks.

The pressure switch MUST NOT be bypassed. The unit MUST NOT be fired unless the power venter is operating. An unsafe condition could result.

Never use an open flame to detect gas leaks. Explosive conditions may exist wich could result in personal injury or death.

3. The direct ignition system consists of an ignition control module and a gas valve. When the pre-purge period ends, the spark ignition system is energized, and the gas valve opens to supply gas to the burners. When the thermostat is satisfied, the vent system is de-energized and the valve closes to stop the flow of gas to the unit. 4. The limit switch interrupts the flow of electric current to the control board, interrupting the flow of gas to the gas valve if the unit heater becomes overheated. 5. The flame roll-out switch interrupts the flow of electric current to the control board, interrupting the flow of gas to the unit heater in the event of sustained flame roll-out from the burner area. If this switch trips, DETERMINE AND CORRECT THE CAUSE of the flame roll-out. 6. Once the thermostat is satisfied, or the limit switch interrupts the flow of electric current to the control board, the unit will begin a post-purge period. When the post-purge period ends, the power venter motor is de-energized. 7. The fan operation is delayed 30 seconds once the thermostat is closed, and continues operation for 30 seconds after the thermostat opens.The start-up fan delay must not exceed 30 seconds from a cold start.

2. Open the manual valve on the unit heater. 3. Turn ON the electrical power. 4. The unit should be under the control of the thermostat. Turn the thermostat to the highest point and determine that the power venter motor starts and the burners ignite. Turn the thermostat to the lowest point and determine that the power venter motor shuts off and the burners are extinguished. 5. Turn the thermostat to the desired position. 6. See Gas Input Rate and Adjustments sections.

SHUT DOWN 1. Turn the valve selector lever to the “OFF” position. 2. Turn off the electricity. 3. To relight, follow “start-up” instructions.

See Figure 20 for parts/identification.

Sterling RF-30 — DIRECT SPARK IGNITION diagram (page 20)
Fig. 6
Page 21 of the Sterling RF-30 user manual — FT 3 /HR ORIFICE DRILL
Page 21 · click to enlarge
Page 21

PRIMARY AIR SHUTTER ADJUSTMENT

Primary air adjustment is made at the factory. No field adjustments are necessary.

GAS INPUT RATE

Check the gas input rate as follows (Refer to General Safety Information section for metric conversions).

2. PROPANE GAS: An exact manifold pressure of 10.0 inches W.C. (2.5 kPa) must be maintained for proper operation of the unit heater. If the unit is equipped with a pressure regulator on the combination gas valve, follow steps "a" through "d" above. If the unit is not so equipped, the propane gas supply system pressure must be regulated to attain this manifold operating pressure. 3. The adjusted manifold pressure should not vary more than 10% from pressure specified in Tables 5 & 6.

Never overfire the unit heater, as this may cause unsatisfactory operation, or shorten the life of the heater.

1. Turn off all gas appliances that use gas through the same meter as the unit heater. 2. Turn the gas on to the unit heater. 3. Clock the time in seconds required to burn 1 cubic foot of gas by checking the gas meter. 4. Insert the time required to burn one cubic foot of gas into the following formula and compute the input rate.

Table 5 - Main Burner Orifice Schedule*

PROPANE TYPE OF GAS NATURAL

* INPUT

HEATING VALUE

(40.1 MJ/m3)

(93.1 MJ/m3)

3600 (Sec. per Hr.) X BTU/Cu. Ft. = Input Rate Time (Sec.)

IN 1000 BTU

NO. OF BURNER ORIFICES

MANIFOLD PRESSURE

3.5" W.C. (0.87kPA)

10" W.C. (2.49 kPA)

FT 3 /HR ORIFICE DRILL

28 49 42 49 56 49 70 49 84 47

12 57 18 57 24 57 30 57 36 55

For example: Assume the BTU content of one cubic foot of gas is 1000, and that it takes 48 seconds to burn one cubic foot of gas.

FT 3 /HR ORIFICE DRILL

FT 3 /HR ORIFICE DRILL

FT 3 /HR ORIFICE DRILL

3600 x 1000 = 75,000

FT 3 /HR ORIFICE DRILL

*This schedule is for units operating at normal altitudes of 2000 ft. (610m) or less.

When installed in Canada, any references to deration at altitudes in excess of 2000 ft. (610m) are to be ignored. At altitudes of 2000 to 4500 ft. (610 to 1372m), the unit heaters must be orificed to 90% of the normal altitude rating, and be so marked in accordance with ETL certification.

Adjust the gas pressure as follows:

TUBULAR UNIT HEATER HIGH ALTITUDE DERATION This Tubular Unit Heater has been manufactured utilizing standard burner orifices and a normal manifold pressure setting as per the specifications shown on your unit rating plate (refer to Tables 3, 5 and 6).

1. NATURAL GAS: Best results are obtained when the unit heater is operating at its full rated input with the manifold pressure of 3.5 inches W.C. (0.9 kPa). Adjustment of the pressure regulator is not normally necessary since it is preset at the factory. However, field adjustment may be made as follows: a. Attach manometer at the pressure tap plug below

All unit deration must be done through field adjustments by a qualified technician (refer to Table 6). Once the proper adjustments are made in the field, attach label #J17-06459 to the unit, and record adjusted manifold pressure, altitude of the unit installation and the technician’s name and date on the label using a permanent marker.

the control outlet. b. Remove the regulator adjustment screw cap,

located on the combination gas valve. c. With a small screwdriver, rotate the adjustment

screw counterclockwise to decrease pressure, or clockwise to increase pressure. d. Replace regulator adjustment screw cap.

1075 BTU/Ft3 · 2500 BTU/Ft3

Page 22 of the Sterling RF-30 user manual — PERIODIC SERVICE
Page 22 · click to enlarge
Page 22

PROPANE (LP) GAS NATURAL GAS

NATURAL GAS

PROPANE (LP) GAS

*Heating Value BTU/Cu. ft. Altitude

Manifold Pressure (In. W.C.)

*Heating Value BTU/Cu. ft.

Manifold Pressure (In. W.C.)

*Heating Value BTU/Cu. ft. Altitude

Manifold Pressure (In. W.C.)

*Heating Value BTU/Cu. ft.

Manifold Pressure (In. W.C.)

2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000

948 931 914 897 881 865 849 833 818

3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9

2,278 2,237 2,196 2,156 2,116 2,077 2,039 2,000 1,964

10.0 9.9 9.7 9.6 9.5

6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000

802 787 771 756 741 726 711 696

2.9 2.8 2.8 2.8 2.7 2.6 2.6 2.5

1,927 1,891 1,853 1,817 1,781 1,745 1,709 1,673

9.3 9.2 9.0 8.9 8.7 8.5 8.3 8.1

*Notes: 1. Consult local utility for actual heating value. 2. Tables based on heating value of 1,050 BTU/Cu. ft. at sea level.

MAINTENANCE

PERIODIC SERVICE

3. Remove service panel. 4. To clean or replace the burners, remove the four screws holding the manifold to the burner box and pull the manifold back slightly to disengage the orifices from the burners. Remove each burner by holding it against the tab on the burner bracket, then rotate the inlet end of the burner toward the fan side of the unit and slide the burner off the tabs. See Figure 20. 5. With the burners removed, wire brush the inside surfaces of the heat exchanger. 6. Remove any dirt, dust, or other foreign matter from the burners using a wire brush and/or compressed air. Ensure that all parts are unobstructed. 7. Reassemble the unit heater by replacing all parts in reverse order. 8. Complete the appropriate unit startup procedure as given in the “Operation” section of this manual. (See lighting instruction on the unit nameplate). 9. Check the burner adjustment. 10. Check all gas control valves and pipe connections for leaks. 11 Check the operation of the automatic gas valve by lowering the setting of the thermostat, stopping the operation of the gas unit heater.The gas valve should close tightly, completely extinguishing the flame on the burners. 12. Inspect and service motor/fan assembly. To maintain efficient air flow, inspect and clean the fan blades and guard to prevent buildup of foreign matter. 13. Check lubrication instructions on motor. If oiling is required, add 3 or 4 drops of electric motor oil as follows: a. Light Duty - After 3 years or 25,000 hours of

All Maintenance/Service information should be recorded accordingly on the Inspection Sheet provided in this manual.

Open all disconnect switches and disconnect all electrical and gas supplies and secure in that position before servicing unit. Failure to do so may result in personal injury or death from electrical shock.

Gas tightness of the safety shut- off valves must be checked on at least an annual basis.

To check gas tightness of the safety shut-off valves, turn off the manual valve upstream of the appliance combination control. Remove the 1/8 inch pipe plug on the inlet side of the combination control and connect a manometer to that tapping. Turn the manual valve on to apply pressure to the combination control. Note the pressure reading on the manometer, then turn the valve off. A loss of pressure indicates a leak. If a leak is detected, use a soap solution to check all threaded connections. If no leak is found, combination control is faulty and must be replaced before putting appliance back in service.

Should maintenance be required, perform the following inspection and service routine:

1. Inspect the area near the unit to be sure that there is no combustible material located within the minimum clearance requirements listed in this manual.

operation. b. Average Duty - Annually after 3 years or 8,000

hours of operation. c. Heavy Duty - Annually after 1 year or at least

Under no circumstances should combustible material be located within the clearances specified in this manual. Failure to provide proper clearance could result in personal injury or equipment damage from fire.

1500 hours of operation.

Never over oil the motor or premature failure may occur!

2. Turn off the manual gas valve and electrical power to the unit heater.
14. Check and test the operational functions of all safety devices supplied with your unit.

Table 6 · (Feet) · (Feet)

Page 23 of the Sterling RF-30 user manual — SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION
Page 23 · click to enlarge
Page 23

Table 7 - Tubular Propeller Troubleshooting Guide

SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION

A. Flame pops back.

1. Burner orifice too small.
1. Check with local gas supplier for proper orifice size and replace. Refer to “Operation”.

B. Noisy Flame.

1. Irregular orifice causing whistle or resonance. 2. Excessive gas input.
1. Replace orifice. 2. Test and reset manifold pressure.

C. Yellow tip flame (some yellow

1. Clogged main burners. 2. Misaligned orifices. 3. Insufficient combustion air. 4. Possibly over fired.
1. Clean main burner ports. 2. Replace manifold assembly. 3. Insufficient combustion air. 4. Check gas input and manifold pressures.

D. Floating flame.

1. Blocked venting. 2. Insufficient combustion air. 3. Blocked heat exchanger. 4. Air leak into combustion chamber or draft hood.
1. Clean Flue. Refer to “Installation”. 2. Clean combustion air inlet openings. 3. Clean heat exchanger. Refer to “Installation”. 4. Determine cause and repair accordingly.

E. Gas odor.

1. Shut off gas supply immediately! 2. Leaking gas test port on valve. 3. Blocked heat exchanger. 4. Blocked draft hood. 5. Negative pressure in the building.
1. Inspect all gas piping and repair. 2. Check to ensure gas test ports are seated. 3. Clean heat exchanger/flue. 4. Clean flue collector. 5. See “Installation”.

F. Delayed ignition.

1. Improper ground.
1. Check grounding wires and spark bracket connections. 2. Inspect spark cable connections and cuts. 3. Check to ensure spark is energized after pre purge period. 4. Test and reset manifold pressure refer to “Operations”. 5. Clean or replace orifices. 6. Refer to “Installation”.
2. Bad or broken spark cable. 3. Faulty control.
4. Pressure regulator set too low.
5. Main burner orifices dirty. 6. Improper venting.

G. Failure to ignite.

1. Gas supply is off. 2. No power supply to unit.

1. Open all manual valves “check for leaks”. 2. Turn on power supply, check fuses and replace if bad. 3. Turn up thermostat, Check for 24v on terminals R and W1 on terminal strip. 4. Check switch for continuity if open with no heat present, replace. 5. Check switch operation to ensure switch closes after draftor purge period. If it does not make/check tubing connections/ blockage. 6. Check all wiring per diagram. 7. Check all ground wires and connections. 8. Check both, for wiring according to diagram; check for 24V at gas valve terminals during trial for ignition period if present and valve does not open. Replace valve.

3. Thermostat not calling.
4. Defective high limit.
5. Defective drafter prove switch.
6. Loose wiring. 7. Improper ground. 8. Improper thermostat or transformer wiring.

H. Condensation.

1. Improper venting. 2. Unit under fired.
1. Refer to “Installation, Venting”. 2. Check gas supply pressures to unit. Refer to “Installation”. 3. Refer to “Installation”.
3. Building too cold.
Page 24 of the Sterling RF-30 user manual — SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION
Page 24 · click to enlarge
Page 24

Table 7 - Tubular Propeller Troubleshooting Guide (continued)

SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION

I. Burners will not shut off.

1. Thermostat located incorrectly.
1. Relocate thermostat away from outside wall or drafts. 2. Check thermostat circuit for open and close on terminal strip on heater “R” and “W”. 3. Check thermostat circuit for shorts “staples piercing wires”. 4. Check for 24v on gas valve terminals when thermostat is not calling. 5. Refer to “Installation”.
2. Improper thermostat wiring.
3. Shorted circuit.
4. Defective sticking gas valve.
5. Excessive gas supply pressure.

J. Rapid burner cycling.

1. Loose electrical connections at thermostat or gas valve. 2. Excessive thermostat heat anticipator setting. 3. Unit cycling on high limit. 4. Poor thermostat location.
1. Tighten all electrical connections. 2. Adjust heat anticipator setting for longer cycles. Refer to “Electrical Connections”. 3. Check for proper air supply across heat exchanger and proper gas supply. 4. Relocate thermostat .

K. Noisy power ventor.

1. Power ventor wheel loose. 2. Power ventor wheel is dirty. 3. Power ventor wheel is rubbing on the housing.
1. Replace or tighten. 2. Clean power ventor wheel. 3. Realign power ventor wheel.

L. Fan will not run.

1. Loose electrical connections. 2. Defective motor or overload.
1. Check and tighten wires on fan circuit. 2. Test for 115v on terminal ACB Heat and “L2” if voltage is present replace motor. 3. Test for 115v on terminal ACB Heat and “L2” on the control board, if voltage is not present 45 seconds after trial for ignition replace board.
3. Defective control board.

M. Fan motor turns on and off

1. Motor overload protection is tripping.
1. Check motor amps against motor name plate, check voltage, replace if found defective. 2. Check for 115v between motor leads. 3. Check terminal ACB Heat for voltage if voltage not constant, replace board.

while burner is operating.

2. Loose wiring or connection. 3. Control board is defective.

N. Fan will not stop.

1. Control Board is in flame failure mode.
1. Turn 115v power off to the unit, wait 10 seconds and reapply voltage to the unit. 2. Check wiring of fan circuit to wiring diagram. 3. If unit is not calling for heat and board is not in a flash code mode, replace board.
2. Fan improperly wired. 3. Defective board.

O. Not enough heat.

1. Incorrect gas input. 2. Heater undersized.
1. Refer to “Operation”. 2. Is the heater output sized correctly for heat loss of the space. Has the space been enlarged. 3. Check thermostat circuit, 24v on terminals “R” and “W” on terminal strip. 4. Check air movement across heat exchanger. Check voltage and amps at the fan motor. Check gas input to ensure unit is not over fired. Check heat exchanger to ensure unit is not dirty. 5. Check orifice size, replace if undersized.
3. Thermostat malfunction.
4. Heater cycling on limit.
5. Incorrect orifice sizes.

P. Too much heat.

1. Unit is over fired.
1. Refer to “Operation”. Check orifice size. If too big replace. 2. Check thermostat for operation, to ensure circuit open and closes. 3. Check wiring per diagram; check operation at the gas valve, look for a short in thermostat circuit.
2. Thermostat malfunction.
3. Heater runs continuously.
Page 25 of the Sterling RF-30 user manual — SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION
Page 25 · click to enlarge
Page 25

Table 7 - Tubular Propeller Troubleshooting Guide

SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION

Q. Cold air is delivered during

1. Incorrect manifold pressure or input. 2. Air throughput too high.
1. Refer to “Operation”. 2. Refer to “Operation”.

heater operation.

R. High limit tripping.

1. Unit is over fired.
1. Burner orifices may be too large, verify and replace. 2. Check for proper voltage, ensure fan blade is correct. 3. Check operation of switch, did the switch open when unit is running or is the switch open during start-up. 4. Check for 24v on line side of the high limit. Constant voltage should be recorded if not control board is suspect. Check flash code.
2. Air flow is low.
3. Defective switch.
4. Defective control board.

S. Power ventor will not run.

1. Loose wiring or connections.
1. Check all wring in the power vent circuit to ensure good connection, including “Neutral”. 2. Check for 115v between motor leads and check amp draw of motor. Replace if needed. 3. Check for continuous 115v on terminal “CBM Blower” and neutral during call for heat. If not present and all checks are normal, replace.
2. Motor overload is tripped or bad motor.
3. Bad control board.

T. Power ventor turns on and off

1. Power ventor improperly wired.
1. Check power ventor circuit per wiring diagram. 2. Check motor voltage and amp draw to motor name plate, replace if motor found defective. 3. Check for continuous 115v on terminal “CMB Blower” during call for heat, replace board if found defective.

during operation.

2. Motor overload cycling or defective motor.
3. Defective control board.

U. Power ventor will not stop.

1. Power ventor improperly wired.
1. Check power ventor circuit per wiring diagram. 2. Heater is in lockout mode check flash code table for problem. 3. No flash codes present along with no call for heat, replace control board.
2. Main burner did not light on call for heat.
3. Defective control board.
Page 26 of the Sterling RF-30 user manual — LED STATUS INDICATES CHECK/REPAIR
Page 26 · click to enlarge
Page 26

Table 8 - Troubleshooting with LED Indicator Assistance

No Cycling or appliance power or thermostat call for heat since appliance failure has occured.

LED STATUS INDICATES CHECK/REPAIR

Control OK, no call for heat.

Control OK, call for heat present.

Internal control fault, or no power.

1. Line voltage on terminals 120 and C on transformer. 2. Low voltage (24V) on terminals 24 and C on transformer. 3. 5 Amp fuse on circuit board.

Line voltage power can cause product damage, severe injury or death. Only a trained experienced service technician should perform this trouble- shooting.

Control internal failure or bad ground.

1. Common side of transformer grounded to chassis. 2. Loose spark ignitor.

In lockout from failed ignitions or flame losses.

1. Gas supply off or gas supply pressure too low. 2. Flame sense rod contaminated or loose wire. 3. Gas valve switch is off or wires are not connected. 4. Broken or cracked porcelain on flame probe or spark ignitor.
1. Check the system thermostat to make sure it is calling for heat. (Do not cycle the thermostat on and off at this time.) 2. Remove the appliance burner compartment door. Do not interrupt power to the control board by opening any electrically interlocked panels. 3. Observe the LED indicator on the control board (a green LED labeled “OK” indicates system faults); check and repair system as noted in the chart to the right.

Pressure Switch open with inducer on or closed with inducer off.

1. Obstructions or restrictions in appliance air intake or flue outlet are preventing proper combustion airflow. 2. Moisture or debris in tubing that connects pressure switch and draft inducer. 3. Airflow switch jumpered or miswired.

Limit or rollout switch is open.

1. Open manual reset rollout switch. 2. Gas pressure too high, over fire condition. 3. Incorrect airflow due to blockage or motor not operating.

Flame sensed while gas valve is off.

1. Flame probe miswired or shortened.

*NOTICE: Air flow proving switch and power venter hose barbs must be free of any dust or debris at all times. Periodically check these openings and/or if any problems occur.

On-board microprocessors disagree.

1. Thermostat is interfering with control board.
Show 11 more labels / short text on this page
Slow Flash · Not Applicable · Fast Flash · Not Applicable · Steady Off · Steady On · 2 Flashes · 3 Flashes · 4 Flashes · 5 Flashes · 6 Flashes
Page 27 of the Sterling RF-30 user manual — IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES
Page 27 · click to enlarge
Page 27

IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES

Sterling RF-30 — IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES diagram (page 27)
Fig. 7
Sterling RF-30 — IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES diagram (page 27)
Fig. 8

5 *Standard Orifice Natural Gas or Propane (LP) Gas

8 Gas Valve, Single Stage Natural or Propane (LP) Gas

*** The orifices shown are for units operating at normal altitudes of 0 to 2000 ft. (610m). *** When replacing a flue collector, make sure that the flue collector box is sealed completely to the vestibule panel using RTV Sealant.

Page 28 of the Sterling RF-30 user manual — D6963
Page 28 · click to enlarge
Page 28

IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES

Figure 21 - Propeller Parts Figure 22 - Component Parts

Sterling RF-30 — IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES diagram (page 28)
Fig. 9
Sterling RF-30 — IDENTIFICATION OF PARTS RESIDENTIAL TUBULAR 30-90 MBH UNIT SIZES diagram (page 28)
Fig. 10

D6963

Sterling RF-30 — D6963 diagram (page 28)
Fig. 11

Motor · Pressure Switch · Gas Valve

Page 29 of the Sterling RF-30 user manual — LIMITED WARRANTY Residential Power Vented Tubular Propeller Unit Heaters
Page 29 · click to enlarge
Page 29

HOW TO ORDER REPLACEMENT PARTS

  • Please send the following information to your local representative: if further assistance is needed, contact the manufacturer's customer service department.
  • Model Number
  • Serial Number (if any)
  • Part Description and Number as shown in Replacement parts Catalog

LIMITED WARRANTY Residential Power Vented Tubular Propeller Unit Heaters

1. The "Manufacturer" warrants to the original owner at original installation site that the above model Gas-Fired Heater ("the Product") will be free from defects in material or workmanship for (1) year from the date of shipment from the factory, or one and one-half (1-1/2) years from the date of manufacture, whichever occurs first. The Manufacturer further warrants that the complete heat exchanger, flue collector and burners be free from defects in material or workmanship for a period of ten (10) years from the date of manufacture. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.

2. This limited warranty does not apply: a. if the product has been subjected to misuse or neglect, has been accidentally or intentionally damaged,

has not been installed, maintained, or operated in accordance with furnished written instructions, or has been altered or modified in any way by any unauthorized person. b. to any expenses, including labor or material, incurred during removal or reinstallation of the Product c. to any damage due to corrosion by chemicals, including halogenated hydrocarbons, precipitated in the air d. to any workmanship of the installer of the Product

3. This limited warranty is conditional upon: a. advising the installing contractor, who in turn notify the distributor or manufacturer b. shipment to the Manufacturer of that part of the Product thought to be defective. Goods can only be

returned with prior written approval of the Manufacturer. All returns must be freight prepaid. c. determination in the reasonable opinion of the Manufacturer that there exists a defect in material or

4. Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.

5. THIS LIMITED WARRANTY IS IN LIEU OF ALL WARRANTIES, EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY JURISDICTION.

In the interest of product improvement, we reserve the right to make changes without notice.

workmanship

Page 30 of the Sterling RF-30 user manual — Remarks: _____________________________________________ __________________________________________________ __________________________________________________
Page 30 · click to enlarge
Page 30

GAS EQUIPMENT

START-UP

Customer Job Name & Number

PRE-INSPECTION INFORMATION

With power and gas off.

Type of EquipUnit Heater

Serial Number Model Number

Name Plate Voltage_____________ Name Plate Amperage: _____________

Type of Gas: Natural LP Tank Capacity lbs. Rating: BTU @ °F kg kw @ °C ❐ Are all panels, doors, vent caps in place? ❐ Has the unit suffered any external damage? Damage ❐ Does the gas piping and electric wiring appear to be installed in a professional manner? ❐ Has the gas and electric been inspected by the local authority having jurisdiction? ❐ Is the gas supply properly sized for the equipment? ❐ Were the installation instructions followed when the equipment was installed? ❐ Have all field installed controls been installed? ❐ Do you understand all the controls on this equipment? If not, contact your wholesaler or rep.

(DO NOT START this equipment unless you fully understand the controls.)

GENERAL With power and gas off. ❐Make certain all packing has been removed. ❐Tighten all electrical terminals and connections. ❐Check all fans & blowers for free movement. ❐Check all controls for proper settings.

GAS HEATING With power and gas on. ❐Inlet gas pressure in. W.C. or kPa ❐Burner ignition. ❐Manifold gas pressure in. W.C. or kPa ❐Cycle on HIGH LIMIT. ❐Cycle and check all other controls not listed. ❐Cycle by thermostat or operating control.

BLOWER With power on and gas off. ❐Check voltage L1 L2 L3 ❐Check rotation of main blower. ❐Check motor amps L1 L2 L3 ❐Blower RPM ❐Check air filters. (Record quantity & size.)

Remarks:

Page 31 of the Sterling RF-30 user manual — GAS EQUIPMENT
Page 31 · click to enlarge
Page 31
Page 31 of the Sterling RF-30 user manual — GAS EQUIPMENT
Page 32 of the Sterling RF-30 user manual — GAS EQUIPMENT
Page 32 · click to enlarge
Page 32
Page 32 of the Sterling RF-30 user manual — GAS EQUIPMENT
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
A. Flame pops back.1. Burner orifice too small.1. Check with local gas supplier for proper orifice size and replace. Refer to “Operation”. p.23
B. Noisy Flame.1. Irregular orifice causing whistle or resonance. 2. Excessive gas input.1. Replace orifice. 2. Test and reset manifold pressure. p.23
C. Yellow tip flame (some yellow tipping on LP gas is permissible).1. Clogged main burners. 2. Misaligned orifices. 3. Insufficient combustion air. 4. Possibly over fired.1. Clean main burner ports. 2. Replace manifold assembly. 3. Insufficient combustion air. 4. Check gas input and manifold pressures. p.23
D. Floating flame.1. Blocked venting. 2. Insufficient combustion air. 3. Blocked heat exchanger. 4. Air leak into combustion chamber or draft hood.1. Clean Flue. Refer to “Installation”. 2. Clean combustion air inlet openings. 3. Clean heat exchanger. Refer to “Installation”. 4. Determine cause and repair accordingly. p.23
E. Gas odor.1. Shut off gas supply immediately! 2. Leaking gas test port on valve. 3. Blocked heat exchanger. 4. Blocked draft hood. 5. Negative pressure in the building.1. Inspect all gas piping and repair. 2. Check to ensure gas test ports are seated. 3. Clean heat exchanger/flue. 4. Clean flue collector. 5. See “Installation”. p.23
F. Delayed ignition.1. Improper ground. 2. Bad or broken spark cable. 3. Faulty control. 4. Pressure regulator set too low. 5. Main burner orifices dirty. 6. Improper venting.1. Check grounding wires and spark bracket connections. 2. Inspect spark cable connections and cuts. 3. Check to ensure spark is energized after pre purge period. 4. Test and reset manifold pressure refer to “Operations”. 5. Clean or replace orifices. 6. Refer to “Installation”. p.23
G. Failure to ignite.1. Gas supply is off. 2. No power supply to unit. 3. Thermostat not calling. 4. Defective high limit. 5. Defective drafter prove switch. 6. Loose wiring. 7. Improper ground. 8. Improper thermostat or transformer wiring.1. Open all manual valves “check for leaks”. 2. Turn on power supply, check fuses and replace if bad. 3. Turn up thermostat, Check for 24v on terminals R and W1 on terminal strip. 4. Check switch for continuity if open with no heat present, replace. 5. Check switch operation to ensure switch closes after draftor purge period. If it does not make/check tubing connections/ blockage. 6. Check all wiring per diagram. 7. Check all ground wires and connections. 8. Check both, for wiring according to diagram; check for 24V at gas valve terminals during trial for ignition period if present and valve does not open. Replace valve. p.23
H. Condensation.1. Improper venting. 2. Unit under fired. 3. Building too cold.1. Refer to “Installation, Venting”. 2. Check gas supply pressures to unit. Refer to “Installation”. 3. Refer to “Installation”. p.23
I. Burners will not shut off.1. Thermostat located incorrectly. 2. Improper thermostat wiring. 3. Shorted circuit. 4. Defective sticking gas valve. 5. Excessive gas supply pressure.1. Relocate thermostat away from outside wall or drafts. 2. Check thermostat circuit for open and close on terminal strip on heater “R” and “W”. 3. Check thermostat circuit for shorts “staples piercing wires”. 4. Check for 24v on gas valve terminals when thermostat is not calling. 5. Refer to “Installation”. p.24
J. Rapid burner cycling.1. Loose electrical connections at thermostat or gas valve. 2. Excessive thermostat heat anticipator setting. 3. Unit cycling on high limit. 4. Poor thermostat location.1. Tighten all electrical connections. 2. Adjust heat anticipator setting for longer cycles. Refer to “Electrical Connections”. 3. Check for proper air supply across heat exchanger and proper gas supply. 4. Relocate thermostat . p.24
K. Noisy power ventor.1. Power ventor wheel loose. 2. Power ventor wheel is dirty. 3. Power ventor wheel is rubbing on the housing.1. Replace or tighten. 2. Clean power ventor wheel. 3. Realign power ventor wheel. p.24
L. Fan will not run.1. Loose electrical connections. 2. Defective motor or overload. 3. Defective control board.1. Check and tighten wires on fan circuit. 2. Test for 115v on terminal ACB Heat and “L2” if voltage is present replace motor. 3. Test for 115v on terminal ACB Heat and “L2” on the control board, if voltage is not present 45 seconds after trial for ignition replace board. p.24
M. Fan motor turns on and off while burner is operating.1. Motor overload protection is tripping. 2. Loose wiring or connection. 3. Control board is defective.1. Check motor amps against motor name plate, check voltage, replace if found defective. 2. Check for 115v between motor leads. 3. Check terminal ACB Heat for voltage if voltage not constant, replace board. p.24
N. Fan will not stop.1. Control Board is in flame failure mode. 2. Fan improperly wired. 3. Defective board.1. Turn 115v power off to the unit, wait 10 seconds and reapply voltage to the unit. 2. Check wiring of fan circuit to wiring diagram. 3. If unit is not calling for heat and board is not in a flash code mode, replace board. p.24
O. Not enough heat.1. Incorrect gas input. 2. Heater undersized. 3. Thermostat malfunction. 4. Heater cycling on limit. 5. Incorrect orifice sizes.1. Refer to “Operation”. 2. Is the heater output sized correctly for heat loss of the space. Has the space been enlarged. 3. Check thermostat circuit, 24v on terminals “R” and “W” on terminal strip. 4. Check air movement across heat exchanger. Check voltage and amps at the fan motor. Check gas input to ensure unit is not over fired. Check heat exchanger to ensure unit is not dirty. 5. Check orifice size, replace if undersized. p.24
P. Too much heat.1. Unit is over fired. 2. Thermostat malfunction. 3. Heater runs continuously.1. Refer to “Operation”. Check orifice size. If too big replace. 2. Check thermostat for operation, to ensure circuit open and closes. 3. Check wiring per diagram; check operation at the gas valve, look for a short in thermostat circuit. p.24
Q. Cold air is delivered during heater operation.1. Incorrect manifold pressure or input. 2. Air throughput too high.1. Refer to “Operation”. 2. Refer to “Operation”. p.25
R. High limit tripping.1. Unit is over fired. 2. Air flow is low. 3. Defective switch. 4. Defective control board.1. Burner orifices may be too large, verify and replace. 2. Check for proper voltage, ensure fan blade is correct. 3. Check operation of switch, did the switch open when unit is running or is the switch open during start-up. 4. Check for 24v on line side of the high limit. Constant voltage should be recorded if not control board is suspect. Check flash code. p.25
S. Power ventor will not run.1. Loose wiring or connections. 2. Motor overload is tripped or bad motor. 3. Bad control board.1. Check all wring in the power vent circuit to ensure good connection, including “Neutral”. 2. Check for 115v between motor leads and check amp draw of motor. Replace if needed. 3. Check for continuous 115v on terminal “CBM Blower” and neutral during call for heat. If not present and all checks are normal, replace. p.25
T. Power ventor turns on and off during operation.1. Power ventor improperly wired. 2. Motor overload cycling or defective motor. 3. Defective control board.1. Check power ventor circuit per wiring diagram. 2. Check motor voltage and amp draw to motor name plate, replace if motor found defective. 3. Check for continuous 115v on terminal “CMB Blower” during call for heat, replace board if found defective. p.25
U. Power ventor will not stop.1. Power ventor improperly wired. 2. Main burner did not light on call for heat. 3. Defective control board.1. Check power ventor circuit per wiring diagram. 2. Heater is in lockout mode check flash code table for problem. 3. No flash codes present along with no call for heat, replace control board. p.25

Ask about the Sterling RF-30

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Sterling RF-30

Be the first to ask — other owners or our team will answer.

Original document

Sterling RF-30 manual PDF

32 pages·1.4 MB·Gas Heater·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…