Instruction/ maintenance manual of the product SBL95 199NE State Industries
Go to page of 52
CommerCial gas w a ter hea ters instruction manual PRINTED 0512 323368-000 plaCe these instruCtions adjaCent to hea ter and notify owner to keep for future referenCe.
2 .
3 safe inst alla tion, use and serViCe .
4 general safety informa tion Fire Hazard Do not install water heater on carpeted floo r. Do not operate water heater if flood damaged. For continued protection against risk of fire: Fire or Explosion Hazard Read instruction manual before installing, using or servicing water heater .
5 preCautions .
6 .
fea tures and Components Controls CONTROL BOX ON/OFF SWITCH VARIABLE FREQUENCY DRIVE DIGITAL THERMOSTAT I/O MODULE LOW SPEED I/O MODULE HIGH SPEED IGNITION CONTROL BLOWER PROVER SWITCH BLOCKED INLET SWITCH BLOCKED FLUE SWITCH figure 1.
8 rough in dimensions inst alla tion Considera tions BACK VIEW K L TOP VIEW F M TOP OUTLET 1 1/2" NPT TOP INLET 1 1/2" NPT FRONT VIEW J B G E D H A C 1 1/2" NPT I t aBle 1.
9 .
10 insula tion Blanket Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death.
11 high al titude inst alla tions Fire and Explosion Hazard Gas and carbon monoxide detectors are available. Overfiring could result in fire or explosion. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label.
12 .
13 HO T WA TER OUTLET TO TA NK INLET CHECK VA LV E MIXING VA LV E COLD WA TER INLET TEMPERED WA TER OUTLET 12” TO 15” (30-38 cm) CHECK VA LV E figure 10.
14 .
15 unusually tight Construction .
16 mul tiple hea ter manifold .
.
18 type B gas Vent multiple gas fired t ank-t ype heaters .
19 t aBle 7. teChniCal da t a Venting (Continued) model sBl85 275ne(a) input: 275,000 Btu/hr t otal V ent height (feet) V ent Connector size: 6 inches 6 8 10 15 20 30 50 100 input Btu/hr rise V ent Co.
20 w a ter hea ter inst alla tion t&p V al Ve disCharge pipe Explosion Hazard Te mperature-Pressure Relief Va lv e must comply with ANSI Z21.22- CS A 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided.
21 inst alla tion diagrams - top inlet/outlet usage .
22 hea ter wiring .
23 gas piping .
24 prior to st art up .
25 .
26 .
seQuenCe of opera tion flow Chart .
28 Venting system .
29 draining and flushing Burn harzard. Hot water discharge. Keep hands clear of drain valve discharge. .
30 Chemical Hazard • Product contains phosphoric acid. • Keep out of reach of children. • Use rubber or neoprene gloves. .
31 .
32 .
33 Complaint Cause remedy user Qualified serViCe agenCy *W ater not hot enough .
34 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
35 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
36 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
38 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
39 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
40 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
41 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
42 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
43 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
44 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
45 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
46 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
48 N OTES : 1. P re f erred piping diagram . 2. T he t empera t ure and pre ss ure relie f valve se tt ing shall no t exceed pressure ra t ing o f any componen t in t he sys t em . 3. S ervi ce v al v es are s hown f or ser v icing uni t. Howeve r , local codes shall govern t heir usage .
49 .
50 notes.
limited w arranty limited w arranty .
www .statewaterheaters.com .
An important point after buying a device State Industries SBL95 199NE (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought State Industries SBL95 199NE yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data State Industries SBL95 199NE - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, State Industries SBL95 199NE you will learn all the available features of the product, as well as information on its operation. The information that you get State Industries SBL95 199NE will certainly help you make a decision on the purchase.
If you already are a holder of State Industries SBL95 199NE, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime State Industries SBL95 199NE.
However, one of the most important roles played by the user manual is to help in solving problems with State Industries SBL95 199NE. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device State Industries SBL95 199NE along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center