1 Instruction Manual PRINTED 0910 197425-005 KEEP THIS MANUAL IN THE POCKET ON HEA TER FOR FUTURE REFERENCE WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED. ALL TECHNICAL AND W ARRANTY QUESTIONS: SHOULD BE DIRECTED T O THE LOCAL DEALER FROM WHOM THE W A TER HEA TER W AS PURCHASED.
2 SAFE INST ALLA TION, USE AND SERVICE The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard.
3 GENERAL SAFETY INFORMA TION.
4 GENERAL SAFETY INFORMA TION at le as t 1 8" (4 5. 7 cm ) ab ov e the f loo r. This will reduce, but not eliminate, the ri sk.
5 Thank Y ou for purchasing this water heater . Properly installed and maintained, it should give you years of trouble free service. Abbreviations Found In This Instruction Manual: • CSA -C.
6 INST ALLA TION REQUIREMENTS FOR THE COMMONWEAL TH OF MASSACHUSETTS COMMONWEAL TH OF MASSACHUSETTS For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas.
7 PP SS (SEE ACCESS PA NE L CAUTION) W 6 (1 5 cm ) MA XIMU M AI R GA P TO A SUIT ABLE DRAI N TYPICAL INST ALLA TION * CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See “PLANNING THE VENT SYSTEM”, “CONDENSA TE” and “BLOWER ASSEMBL Y INST ALLA TION” for more information.
8 TYPICAL INST ALLA TION CONDENSA TE HOSE AND DRAIN P AN FIGURE 1A..
9 TYPICAL INST ALLA TION FIGURE 2. MIXING V AL VE / THERMAL EXP ANSION T ANK USAGE AND SP ACE HEA TING MIXING V AL VES DA NGER Wa ter temperatur e over 125° F (52°C) c an cause severe burns instantl y resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury .
10 F ACTS TO CONSIDER ABOUT THE LOCA TION Carefully choose an indoor location for the new water heater , because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance.
11 in an alcove or closet, the entire oor must be covered by the panel. Failuretoheedthiswarningmayresultinarehazard. Minimum clearances between water heater and combustible construction are 0 inch at the sides and rear , 5.
12 Such a condition often will result in a yellow , luminous burner flame, causing sooting of the combustion chamber , burners and flue tubes and creates a risk of asphyxiation.
13 Figure 7. The water heater should have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance.
14 Thi s water he ater sho uld n ot be c onn ect ed to any hea ting sys tems o r co mpo nent (s )usedw it hanon - pot abl ewaterh eati ngapp lian ce. Al l pipi ng c omp one nts c onn ecte d to th is unit f or spa ce h eatin g app lic ati ons s houl d be sui tab le fo r use w ith p ota ble wate r .
15 THERMAL EXP ANSION As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure d ue to thermal expansion.
16 discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.
17 A gas lin e of suf f i ci ent size mu st be r un to th e water hea ter . Co nsult t he c urr ent e diti on of N ati onal Fuel G as C ode (AN SI Z 22 3. 1 /N FP A5 4 )andyou rgassup pli erc onc er ningp ipes ize.
18 Never use this water heater unless it is completely full of water. To prevent damage to the tank, the tank must be lled with water. Water must ow from thehotwaterfaucetbeforeturning“ON”gastothewaterheater .
19 TERMINA TION CLEARANCES SIDEW ALL POWER VENT V X VEN T TERMINAL AIR SUPPL Y INLE TA RE A WHERE TERMINAL IS NO T PERMITTED v v A G V FIXED CLOSED FIXED CLOSED OPERABLE OPERABLE V C B B B B F B V V A J V H M X X V V K B E D L POWER VENT (using room air for combustion) EXTERIOR CLEARANCES FOR SIDE WA LL VENT TERMINA TION FIGURE 15.
20 PLANNING THE VENT SYSTEM Plan the route of the vent system from the discharge of the blower to the planned location of the vent terminal. Refer to V AA instruction on page 24 while planning the vent system. 1. Layout total vent system to use a min im um of vent pipe and elbows.
21 The condensate trap may be primed by lling the CONDENSA TE U-ASSEMBL Y with tap water while the water heater is not operating. The system is fully primed when the water level reaches the adaptor connected into the T ee.
22 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERA TION. VERIFY PROPER OPERA TION AFTER SERVICING. POWER VENT WIRING SCHEMA TIC - FIGURE 19. may be easier to mark both the inside and outside wall.
23 INST ALLA TION OF VENT SYSTEM, SIDEW ALL With the route of the venting system and selection of materials completed, as discussed in the section of this manual titled PLANNING THE VENT SYSTEM, th.
24 VENT A TTENUA TI ON ASSEMBL Y I N S T ALL A T I O N INSTRU C T I ON S The V ent Attenuation Assembly (V AA) is designed to provide a reduction in fan noise created in the blower wheel. This installation of this V AA is optional.
25 bar b, use a wi re ti e or ho se cl amp (not supp lie d wit h kit) and secure. 6. T ake the othe r end of t he f lexib le tub ing an d sli de it th roug h the h ose c lamp o n the j acket top c over an d inst all it i nto one of the f our bar b f it t ings i n vent pipe a sse mbly # 2 .
26 VENT PIPE PREP ARA TION 1. INITIAL PREP ARA TION A. Make sure the solvent cement you are planning to use is designedforthespecicapplicationyouareattempting. B. Know the physical and chemical characteristics and limitations of the PVC and CPVC piping materials that you are about to use.
27 B. Deburring Usea knife, plastic pipedeburring tool, or le toremove burrs from the end of small diameter pipe. Be sure to remove all burrs from around the inside as well as the outside of the pipe.
28.
29 It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperaturebe set for thelowest temperature whichsatises your hot water needs.
30 FOR YOUR INFORMA TION ST ART UP CONDITIONS SMOKE/ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start-up.
31 BURNER OPERA TION AND INSPECTION Flood damage to a water heater may not be readily visible or immediately detectable. However , over a period of time a ooded water heater will create dangerous conditions which can cause DEA TH, SERIOUS BODIL Y INJURY , OR PROPERTY DAMAGE.
32 TEMPERA TURE-PRESSURE RELIEF V AL VE TEST D ANGER • Burn hazard . • Hot water discharge. • Ke ep clear of Te mperatur e- Pressure Relief Valve discharge outlet . It is recommended that the T emperature-Pressure Relief V alve should be checked to ensure that it is in operating condition every 6 months.
33 LEAKAGE CHECKPOINTS Neveruse thiswaterheater unlessit iscompletelylled withwater . T o prevent damage tothe tank,the tank must be lled with water .
34 Key No. Part Description 1 Outer Door 2 Anode 3 Control Valve Assembly 4 Plastic T op 5 Blower Assembly 6 Switch and Harness Assembly 7 T&P V alve 8 Drain Valve 9 Wiring Harness 10 Anode Outlet.
35 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Pleasecheckguidelinesbelow .Foryoursafety ,waterheaterserviceshouldbeperformedonlybyaqualiedservicetechnician. ReadtheGENERAL SAFETYINFORMA TIONsectionrst.
36 # LED ST A TUS PROBLEM SOLUTION 7 8 9 Self diagnostic check has detected a problem with the gas valve driver circuit, internal microprocessor , or other internal circuits. 1 Turn the power of f for 10-20 seconds then on again to clear these error codes.
37 Theseguidelinesshouldbeutilizedbyaqualiedserviceagent. TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES.
38 TROUBLESHOOTING GUIDELINES NOTES.
39 36 THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY. If the glass lined tank in this water heater shall prove upon examination by (the w arrantor) t o h ave l eaked d uring t he w arranty p e.
40 www .statewaterheaters.com 500 T ennessee Waltz Parkway Ashland City , TN 37015 T echnical Support 800-365-0024 Parts 800-821-2017 Copyright © 2010 State Industries, Inc.
An important point after buying a device State Industries GP6 50 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought State Industries GP6 50 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data State Industries GP6 50 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, State Industries GP6 50 you will learn all the available features of the product, as well as information on its operation. The information that you get State Industries GP6 50 will certainly help you make a decision on the purchase.
If you already are a holder of State Industries GP6 50, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime State Industries GP6 50.
However, one of the most important roles played by the user manual is to help in solving problems with State Industries GP6 50. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device State Industries GP6 50 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center