40 pages·1.1 MB·Water Heater·PDF·ENDEFRITNLJA
State Industries 100
Table of Contents 80 sections ULTRA FORCE SUF 60 120 THRU SUF 100 250 · SERIES 100 AND 101 · COMMERCIAL GAS WATER HEATER · GAS-FIRED POWER BURNER · … ShowHide
ULTRA FORCE SUF 60 120 THRU SUF 100 250p.1SERIES 100 AND 101p.1COMMERCIAL GAS WATER HEATERp.1GAS-FIRED POWER BURNERp.1FOR DOMESTIC HOT WATERp.1– WHAT TO DO IF YOU SMELL GAS:p.1PLACE THESE INSTRUCTIONS ADJACENT TO HEATER ANDp.1500 Tennessee Waltz Parkway Ashland City, TN 37015p.1PRINTED 0407 197784-000p.1ULTRA FORCE SUF 120 - 250A ROUGH-IN-DIMENSIONSp.2FOREWORDp.2TABLE OF CONTENTSp.3PAGEp.3FEATURESp.3WATER TEMPERATURE CONTROLp.3DISHWASHING MACHINE REQUIREMENTp.4CIRCULATING PUMPp.4INSTALLATION INSTRUCTIONSp.4REQUIRED ABILITYp.4INSULATION BLANKETSp.4HIGH LIMIT SWITCH (E.C.O.)p.4LOCATING THE HEATERp.5CLEARANCESp.5HARD WATERp.6AIR REQUIREMENTSp.6CHEMICAL VAPOR CORROSIONp.6MECHANICAL EXHAUSTING OF ROOM AIRp.6VENTINGp.6UNCONFINED SPACEp.6VENT PIPE TERMINATIONp.6CONFINED SPACEp.6INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTSp.7U.S. POWER VENTp.8CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKEp.8IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEENp.8CANADIAN POWER VENTp.8U.S. DIRECT VENTp.9CANADIAN DIRECT VENTp.9IMPORTANTp.10FOR ALL MODELSp.10DIRECT VENTINGp.10INSTALLATION SEQUENCEp.10DIRECT VENT TERMINAL INSTALLATIONp.10VERTICAL VENT TERMINAL INSTALLATIONp.11INSTALLATION OF VENT SYSTEMp.12VENT PIPE PREPARATIONp.122. SELECTION OF MATERIALSp.12CONTROLS AND SWITCHESp.13LOW GAS PRESSURE SWITCHp.13(SEE FIGURE 12)p.13HOT SURFACE IGNITERp.13GAS PIPINGp.13BLOWER PROVER SWITCHp.13BLOCKED OUTLET PROVER SWITCHp.13BLOCKED INLET PROVER SWITCHp.13CONNECTION OF GAS PIPEp.14RELIEF VALVEp.15PURGINGp.15GAS METER SIZE - CITY GASES ONLYp.15GAS PRESSURE REGULATIONp.15WATER LINE CONNECTIONSp.15CLOSED SYSTEMp.15GAS VALVESp.15SYSTEM CONNECTIONSp.15THERMOMETERS (Not Supplied)p.15WATER (POTABLE) HEATING AND SPACE HEATINGp.15HEATER WIRINGp.16USING THE ELECTRONIC CONTROLLERp.17DISPLAY:p.18PRIOR TO START UPp.20OPERATING INSTRUCTIONSp.21BTUH = ?p.21ADJUSTMENT PROCEDURE Initial Start-up - 120 AND 150 MODELSp.21ADJUSTMENT PROCEDURE Initial Start-up - 199 AND 250 MODELSp.21HIGH ALTITUDE INSTALLATIONSp.22CATHODIC PROTECTIONp.22PRECAUTIONSp.22MAINTENANCEp.22GENERALp.222. EXTERNAL FIRINGp.22
Page 1 of the State Industries 100 user manual — PRINTED 0407 197784-000
Page 1 · click to enlarge
Page 1

ULTRA FORCE SUF 60 120 THRU SUF 100 250

SERIES 100 AND 101

COMMERCIAL GAS WATER HEATER

GAS-FIRED POWER BURNER

State Industries 100 — ULTRA FORCE SUF 60 120 THRU SUF 100 250 diagram (page 1)
Fig. 1

FOR DOMESTIC HOT WATER

  • INSTALLATION
  • OPERATION
  • SERVICE
  • MAINTENANCE
  • LIMITED WARRANTY
State Industries 100 — FOR DOMESTIC HOT WATER diagram (page 1)
Fig. 2

– Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

– WHAT TO DO IF YOU SMELL GAS:

  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
  • If you cannot reach your gas supplier, call the fire department.

– Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Thank you for buying this energy efficient water heater from State Water Heaters. We appreciate your confidence in our products.

State Industries 100 — – WHAT TO DO IF YOU SMELL GAS: diagram (page 1)
Fig. 3

PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND

500 Tennessee Waltz Parkway Ashland City, TN 37015

NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.

PRINTED 0407 197784-000

Page 2 of the State Industries 100 user manual — FOREWORD
Page 2 · click to enlarge
Page 2

ULTRA FORCE SUF 120 - 250A ROUGH-IN-DIMENSIONS

State Industries 100 — ULTRA FORCE SUF 120 - 250A ROUGH-IN-DIMENSIONS diagram (page 2)
Fig. 4
State Industries 100 — ULTRA FORCE SUF 120 - 250A ROUGH-IN-DIMENSIONS diagram (page 2)
Fig. 5
GAS VALVE PIPING SUF-120, 199 & 2501/2" NPT SUF-1503/4" NPT

Table 1. RECOVERY CAPACITIES - NATURAL GAS / L.P.

ModelInput BTU/Hr.Gas UsageApprox. Gallon CapacityTEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR 30405060708090100110120130140 SUF 120120,000nat/lp6046134527623019717315413812611510699 SUF 150150,000nat/lp100576432345288247216192173157144133123 SUF 199199,900nat/lp100767575460384329288256230209192177164 SUF 250250,000nat/lp100960720576480411360320288262240221206
ModelGas kW-HrLiter UsageApprox. TEMP CapacityERATURE RISE - DEGREES C - Liters PER HOUR 172228333944505661677278 SUF 12035nat/lp227174413081046872747654581523476436402374 SUF 15044nat/lp3792179163513081090934817726654594545503467 SUF 19958nat/lp379290421781743145212451089968871792726670622 SUF 25073nat/lp37936322724217918161557136212111090991908838778

Recovery capacities are based on 95% thermal efficiency.

FOREWORD

These designs comply with the current version of the American National Standard for Gas Water Heaters, Volume III, ANSI Z21.10.3 / CSA 4.3 as an automatic circulating tank water heater, and automatic storage water heaters.

In addition to these instructions, the equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.

Detailed installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary. It is highly essential that all water, gas piping and wiring be installed as shown on the diagrams.

In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70 or CAN/CSA-B149.1, the Natural Gas and Propane Installation Code and CSA C22.1, the Canadian Electrical Code. All documents are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131. NFPA documents are also available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.

Particular attention should be given to the installation of thermometers at the locations indicated on the diagrams as these are necessary for checking the proper functioning of the heater.

Page 3 of the State Industries 100 user manual — Table of Contents
Page 3 · Contents
Contents

Contents

ULTRA FORCE SUF 60 120 THRU SUF 100 250p.1SERIES 100 AND 101p.1COMMERCIAL GAS WATER HEATERp.1GAS-FIRED POWER BURNERp.1FOR DOMESTIC HOT WATERp.1– WHAT TO DO IF YOU SMELL GAS:p.1PLACE THESE INSTRUCTIONS ADJACENT TO HEATER ANDp.1500 Tennessee Waltz Parkway Ashland City, TN 37015p.1PRINTED 0407 197784-000p.1ULTRA FORCE SUF 120 - 250A ROUGH-IN-DIMENSIONSp.2FOREWORDp.2TABLE OF CONTENTSp.3PAGEp.3FEATURESp.3WATER TEMPERATURE CONTROLp.3DISHWASHING MACHINE REQUIREMENTp.4CIRCULATING PUMPp.4INSTALLATION INSTRUCTIONSp.4REQUIRED ABILITYp.4INSULATION BLANKETSp.4HIGH LIMIT SWITCH (E.C.O.)p.4LOCATING THE HEATERp.5CLEARANCESp.5HARD WATERp.6AIR REQUIREMENTSp.6CHEMICAL VAPOR CORROSIONp.6MECHANICAL EXHAUSTING OF ROOM AIRp.6VENTINGp.6UNCONFINED SPACEp.6VENT PIPE TERMINATIONp.6CONFINED SPACEp.6INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTSp.7U.S. POWER VENTp.8CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKEp.8IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEENp.8CANADIAN POWER VENTp.8U.S. DIRECT VENTp.9CANADIAN DIRECT VENTp.9IMPORTANTp.10FOR ALL MODELSp.10DIRECT VENTINGp.10INSTALLATION SEQUENCEp.10DIRECT VENT TERMINAL INSTALLATIONp.10VERTICAL VENT TERMINAL INSTALLATIONp.11INSTALLATION OF VENT SYSTEMp.12VENT PIPE PREPARATIONp.122. SELECTION OF MATERIALSp.12CONTROLS AND SWITCHESp.13LOW GAS PRESSURE SWITCHp.13(SEE FIGURE 12)p.13HOT SURFACE IGNITERp.13GAS PIPINGp.13BLOWER PROVER SWITCHp.13BLOCKED OUTLET PROVER SWITCHp.13BLOCKED INLET PROVER SWITCHp.13CONNECTION OF GAS PIPEp.14RELIEF VALVEp.15PURGINGp.15GAS METER SIZE - CITY GASES ONLYp.15GAS PRESSURE REGULATIONp.15WATER LINE CONNECTIONSp.15CLOSED SYSTEMp.15GAS VALVESp.15SYSTEM CONNECTIONSp.15THERMOMETERS (Not Supplied)p.15WATER (POTABLE) HEATING AND SPACE HEATINGp.15HEATER WIRINGp.16USING THE ELECTRONIC CONTROLLERp.17DISPLAY:p.18PRIOR TO START UPp.20OPERATING INSTRUCTIONSp.21BTUH = ?p.21ADJUSTMENT PROCEDURE Initial Start-up - 120 AND 150 MODELSp.21ADJUSTMENT PROCEDURE Initial Start-up - 199 AND 250 MODELSp.21HIGH ALTITUDE INSTALLATIONSp.22CATHODIC PROTECTIONp.22PRECAUTIONSp.22MAINTENANCEp.22GENERALp.222. EXTERNAL FIRINGp.22
Page 4 of the State Industries 100 user manual — HIGH LIMIT SWITCH (E.C.O.)
Page 4 · click to enlarge
Page 4

temperature be set for the lowest temperature which satisfies your hot water needs. This will also provide the most energy efficient operation of the water heater and minimize scale formation.

DISHWASHING MACHINE REQUIREMENT

All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 Kpa and 173 Kpa). Flow pressures above 25 pounds per square inch (173 Kpa), or below 15 pounds per square inch (103 Kpa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180°F (82°C) line to the dishwashing machine, and should be adjusted to deliver water between these limits.

SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C WILL REDUCE THE RISK OF SCALDS. Some states require settings at specific lower temperatures.

Figure 1 shows the approximate time-to-burn relationship for normal adult skin. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F/11°C. If you experience this type of use, you should consider using lower temperature settings to reduce scald hazards.

The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. Where this is done, the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater. The circulation should be just enough to provide 180°F (82°C) water at the point of take-off to the dishwashing machine. Adjust flow by means of the plug cock in the circulating line. (See installation diagrams.)

Temperature Time to Produce 2nd & 3rd Setting Degree Burns on Adult Skin 180°F / 82°C Nearly instantaneous 170°F / 77°C Nearly instantaneous 160°F / 71°C About 1/2 second 150°F / 66°C About 1-1/2 seconds 140°F / 60°C Less than 5 seconds 130°F / 54°C About 30 seconds 120°F / 49°C More than 5 minutes

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the heater. Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1.

FIGURE 1.

Valves for reducing point-of-use temperature by mixing cold and hot water are available (see Figure 2). Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority.

All bronze circulators are recommended for used with commercial water heaters.

Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operated. Please refer to manufacturer's instructions.

State Industries 100 — CIRCULATING PUMP diagram (page 4)
Fig. 6

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.

INSULATION BLANKETS

Insulation blankets available to the general public for external use on gas water heaters are not approved for use on your water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your water heater meets or exceeds the ASHRAE/IES 90.1 1999 standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

FIGURE 2.

HIGH LIMIT SWITCH (E.C.O.)

The top immersion well of the dual bulb controller also contains the high limit (energy cutoff) sensor. The high limit switch interrupts the main burner gas flow should the water temperature reach approximately 202°F/94°C.

Should the high limit switch activate, the control system will automatically reset the unit once the water temperature in the tank falls below 140°F/60°C. If the unit is manually shut down and restarted, as long as the temperature in the tank is lower than 160°F/71°C, the unit will reset and initiate operation.

  • Do not apply insulation to the top, or the upper 15" (38 cm) of the water heater, as this will interfere with safe operation.
  • Do not cover the temperature & pressure relief valve.

High limit switch operation is the likely cause when higher than normal water temperatures occur with a recurring need to restart the water heater. This could be due to a malfunctioning thermostat allowing the gas valve to remain open and the burner to continue firing even after water temperature in the tank has already reached the set point. Contact your dealer or servicer if continued high limit switch operation occurs.

  • Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
  • Do obtain new labels from State for placement on the blanket directly over the existing labels.

Page 5 of the State Industries 100 user manual — CLEARANCES
Page 5 · click to enlarge
Page 5

LOCATING THE HEATER

WARNING This water heater is a condensing unit and requires a drain to be located in close proximity to allow the condensate to drain safely. The condensate drains from the unit at the exhaust elbow located at the bottom of the unit. Note: It is important that the condensate hose not be elevated above the exhaust elbow (see Figure 3). The condensate build-up will block the exhaust outlet, which will cause improper operation.

WARNING THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER’S IGNITER OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IF INSTALLED 18 INCHES (46 cm) OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.

State Industries 100 — LOCATING THE HEATER diagram (page 5)
Fig. 7

THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

DO NOT LOCATE THE HEATER WHERE NOISE FROM THE EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS INCLUDES LOCATIONS CLOSE TO OR ACROSS FROM WINDOWS AND DOORS. AVOID ANCHORING THE VENT AND INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OF CEILINGS UNLESS RUBBER ISOLATION PIPE HANGERS ARE USED. THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES.

FIGURE 3.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the intake and exhaust termination points as practicable, with adequate air supply and as centralized with the piping system as possible.

CLEARANCES

These heaters are approved for installation on combustible flooring in an alcove when the minimum clearances from any combustion construction are followed as indicated in Figure 4.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING.

In all installations the minimum combustible clearances from any vent piping shall be 0". Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints).

LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.

A service clearance of 24" (61 cm) should be maintained from serviceable parts such as relief valves, flue baffles, flue damper devices, thermostats, cleanout openings or drain valves.

When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.

Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:

Always disconnect electrical power before servicing the unit.

State Industries 100 — CLEARANCES diagram (page 5)
Fig. 8
  • Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected.
  • Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan.
  • Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater.

FIGURE 4.

  • Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply.

*ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE.

Page 6 of the State Industries 100 user manual — CONFINED SPACE
Page 6 · click to enlarge
Page 6

HARD WATER

If the confined space is within a building of tight construction, air for combustion and ventilation must be obtained from outdoors. When directly communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch (6.5 cm²) per 4000 Btuh of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch (6.5 cm²) per 2000 Btuh of the total input of all appliances in the enclosure.

Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment.

See MAINTENANCE section for details of tank cleanout procedure.

AIR REQUIREMENTS

CHEMICAL VAPOR CORROSION

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.

DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR.

WARNING FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN CONTAMINATION THAT MAY BE HAZARDOUS TO LIFE. SUCH A CONDITION OFTEN WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION.

Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, and process chemicals are typical compounds which are potentially corrosive.

PRODUCTS OF THIS SORT SHOULD NOT BE STORED NEAR THE HEATER. ALSO, AIR WHICH IS BROUGHT IN CONTACT WITH THE HEATER SHOULD NOT CONTAIN ANY OF THESE CHEMICALS. IF NECESSARY, UNCONTAMINATED AIR SHOULD BE OBTAINED FROM REMOTE OR OUTSIDE SOURCES.

MECHANICAL EXHAUSTING OF ROOM AIR

VENTING

Where an exhaust fan is installed in the same room with a heater, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE HEATER’S VENTING SYSTEM, CAUSING POOR COMBUSTION. SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR EXPLOSION. IT CAN ALSO CREATE A RISK OF ASPHYXIATION.

Heater must be protected from freezing downdrafts during shutdown periods.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion and ventilation.

If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion and ventilation must be obtained from outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.

VENT PIPE TERMINATION

CONFINED SPACE

When drawing combustion air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12" (31 cm) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12" (31 cm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch (6.5 cm²) per 1000 Btuh appliances in the enclosure, but not less than 100 square inches (645 cm²).

Page 7 of the State Industries 100 user manual — INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
Page 7 · click to enlarge
Page 7

INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.

SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONSThe following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Page 8 of the State Industries 100 user manual — CANADIAN POWER VENT
Page 8 · click to enlarge
Page 8

U.S. POWER VENT

State Industries 100 — U.S. POWER VENT diagram (page 8)
Fig. 9

FIGURE 5a.

CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE

IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN

THESE TWO TERMINALS IS RECOMMENDED.

CANADIAN POWER VENT

State Industries 100 — CANADIAN POWER VENT diagram (page 8)
Fig. 10

FIGURE 5b.

Page 9 of the State Industries 100 user manual — CANADIAN DIRECT VENT
Page 9 · click to enlarge
Page 9

U.S. DIRECT VENT

State Industries 100 — U.S. DIRECT VENT diagram (page 9)
Fig. 11

FIGURE 6a.

CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE

IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN

THESE TWO TERMINALS IS RECOMMENDED.

CANADIAN DIRECT VENT

State Industries 100 — CANADIAN DIRECT VENT diagram (page 9)
Fig. 12

FIGURE 6b.

Page 10 of the State Industries 100 user manual — DIRECT VENT TERMINAL INSTALLATION
Page 10 · click to enlarge
Page 10

IMPORTANT

FOR ALL MODELS

State Industries 100 — IMPORTANT diagram (page 10)
Fig. 13

The vent system must terminate so that proper clearances are maintained as cited in local codes or the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CAN/CSA-B149.1.

Do not terminate the exhaust vent terminal over public area where condensate or vapor can cause nuisance or hazard.

Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as "vent connectors". Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and CLEARANCES, and with National Fuel Gas Code and local Codes.

FIGURE 8.

IMPORTANT

IMPORTANT

WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED.

Plan the layout of the vent system backwards from the vent termination to the appliance.

1. The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24" (61cm) from the vertical centerline of the exhaust vent terminal (see Figure 9). In colder climates increasing the 24" (61cm) minimum will reduce possibility of frost over from side winds blowing exhaust vapors to the air intake of the direct vent.

DIRECT VENTING

2. The horizontal centerline of the intake vent terminal may not be located lower than the horizontal centerline of the exhaust vent terminal (see Figure 9).

The air intake provided on the unit contains a mesh screen (see Figure 7) to prevent large particles from entering the unit.

INSTALLATION SEQUENCE

State Industries 100 — INSTALLATION SEQUENCE diagram (page 10)
Fig. 14

For installations in the City of Los Angeles, California Category IV PVC Pipe such as that manufactured by Brownline Pipe Company, must be used as vent pipe material

1. After the points of termination have been determined, use the cover plates as templates to mark the holes for the vent pipes to be inserted through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL.

FIGURE 7.

2. If the vent terminals are being installed on the outside of a finished wall, it may be easier to mark both the inside and outside wall. Align the holes by drilling a hole through the center of the template from the inside through to the outside. The template can now be positioned on the outside wall using the drilled holes as a centering point for the template.
3. A) MASONRY SIDE WALLS Chisel an opening approximately 1/2" (1.3 cm) larger than the marked circle.

DIRECT VENT TERMINAL INSTALLATION

IMPORTANT

B) WOODEN SIDE WALLS Drill a pilot hole approximately one quarter inch outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately one quarter inch outside of the line. (This will allow the vent pipe to easily slide through the opening. The resulting gap will be covered by the vent terminal cover plates.) Repeat this step on the inside wall if necessary.

THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE VENT TERMINAL AND AN EXHAUST VENT TERMINAL. THE INTAKE VENT TERMINAL IS A 3" 45° PVC ELBOW WITH A DOME MESH WIRE SCREEN AND THE EXHAUST VENT TERMINAL IS A 3" 45°PVC ELBOW WITH A MESH WIRE SCREEN.

4. Cut a length of 3" PVC pipe about 3.5" (8.9 cm) longer than the wall thickness at the opening.
Page 11 of the State Industries 100 user manual — INSTALLATION SEQUENCE
Page 11 · click to enlarge
Page 11
5. Glue the intake vent terminal to the section of the pipe.

VERTICAL VENT TERMINAL INSTALLATION

6. Slide the wall plate over the pipe to stop against intake vent terminal.

IMPORTANT

7. Place a bead of caulking (not supplied) around the gap between the pipe and the wall. Place some of the caulking on the back of the plate to hold it against the wall after installation.

WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED.

8. If the vent pipe is installed up to the wall, with a coupling on the end against the wall opening, the pipe with the vent terminal can be prepared for gluing before inserting through the wall. Slide the pipe through the wall and insert into coupling on the other side of the wall, making sure that the vent terminal ends up pointed in the correct position (See Figure 9) .
1. Proper support must be provided for all pipe protruding through the roof.
2. The vertical roof terminations should be sealed with a plumbing roof boot or equivalent flashing.
3. The intake vent termination and the exhaust vent termination must penetrate the same side of roof.
State Industries 100 — IMPORTANT diagram (page 11)
Fig. 15
4. The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24" (61cm).
5. The intake vent terminal and the exhaust vent terminal must be oriented facing downward and the same direction.

The specifications are displayed in Figure 10 & 11.

INSTALLATION SEQUENCE

1. After the points of termination have been determined, use the cover plates as templates to mark the holes for the vent pipes to be inserted through the roof.
2. Drill a pilot hole approximately 1/4" (6 mm) outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately one quarter inch outside the line. (This will allow the vent pipe to easily slide through the opening). The resulting gap will be covered by the roof boot/flashing.
3. Suspend the pipe through the center of the hole using proper support.
4. Slide roof boot or equivalent flashing over pipe and secure roof boot equivalent flashing to roof.

FIGURE 9.

5. Seal around flashing.
State Industries 100 — INSTALLATION SEQUENCE diagram (page 11)
Fig. 16
6. Terminate intake terminal and exhaust vent terminal facing down as shown in Figure 11.
State Industries 100 — INSTALLATION SEQUENCE diagram (page 11)
Fig. 17

FIGURE 10.

FIGURE 11.

Page 12 of the State Industries 100 user manual — IMPORTANT
Page 12 · click to enlarge
Page 12

INSTALLATION OF VENT SYSTEM

WARNING THE OPTIONAL INTAKE VENTING ARRANGEMENT AND THE EXHAUST VENTING ARRANGEMENT MUST BE INSTALLED TO RUN DIRECTLY TO THE OUTDOORS AND NOT IN ANY WAY BE CONNECTED TO ANOTHER VENTING SYSTEM (I.E. FURNACE, DRYERS OR SPACE HEATERS). IT IS CRUCIAL THAT THE VENTING ARRANGEMENT BE KEPT SEPARATE FROM OTHER VENTING SYSTEMS. IF THIS WARNING IS IGNORED, AND THE SYSTEM IS VENTED INCORRECTLY, IT MAY CAUSE IMPROPER OPERATION, FIRE, EXPLOSION, OR ASPHYXIATION.

4. It is important that condensate not be allowed to buildup in the exhaust vent pipe. To prevent this from happening the pipe should be installed with a slight, 1/8" (3mm) per 5' (152 cm) of pipe maximum downward slope.
5. The vent system should be supported every 5' (152 cm) of vertical run and every 3' (91cm) of horizontal run of vent pipe length.

NOTE: Stress levels in the pipe and fittings can be significantly increased by improper installation. If rigid pipe clamps are used to hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be directly stressed, or high thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses.

1. Plan the route of the vent system from the vent termination to the planned location of the appliance. Layout the total vent system to use the minimum of vent pipe and elbows possible.
2. The installer may add up to a MAXIMUM OF FIFTY (50) EQUIVALENT FEET (15.2 m) of pipe to the exhaust venting arrangement. This addition of FIFTY (50) EQUIVALENT FEET (15.2 m) of pipe on both the intake venting arrangement and exhaust venting arrangement must include any 3" PVC elbows which equals (5) EQUIVALENT FEET (1.5 m) of pipe.

VENT PIPE PREPARATION

1. INITIAL PREPARATION A. Make sure the solvent cement you are planning to use is designed for the specific application you are attempting.

Table 2. VENT LENGTH TABLE

B. Know the physical and chemical characteristics and limitations of the PVC, PVC cellular core, ABS or CPVC piping materials that you are about to use.

Number 3" 3" 4" of 90° Minimum Maximum Maximum Elbows Pipe (Ft./M.) Pipe (Ft./M.) Pipe (Ft./M.) ONE (1) 7/2 45/13.7 115/35 TWO (2) 7/2 40/12.2 110/33.5 THREE (3) 7/2 35/10.7 105/32 FOUR (4) 7/2 30/9.1 100/30.5 FIVE (5) 7/2 --- 95/29 SIX (6) 7/2 --- 90/27.4

C. Know the reputation of your pipe and cement manufacturer and their products.

D. Know your own qualifications or those of your contractor. The solvent welding technique of joining PVC, PVC cellular core, ABS or CPVC pipe is a specialized skill just as any other pipe fitting technique. E. Closely supervise the installation and inspect the finished job before start-up. F. Contact the manufacturer, supplier, or competent consulting agency if you have any questions about the application or installation of PVC, PVC cellular core, ABS or CPVC pipe. G. Take the time and effort to do a professional job. Shortcuts will only cause you problems and delays in start-up. The majority of failures in these systems are the result of shortcuts and/or improper joining techniques.

4" PVC may be used for a MAXIMUM intake of ONE HUNDRED TWENTY (120) EQUIVALENT FEET (36.6m) and a MAXIMUM exhaust of ONE HUNDRED TWENTY (120) EQUIVALENT FEET (36.6m). The maximum number of 90° elbows with the 4" venting is six (6) on the intake and six (6) on the exhaust. A 90° elbow is equal to five (5) equivalent feet (1.5m) of pipe. One (1) 90° elbow is equal to two (2) 45° elbows. Any venting configuration using less than 50 equivalent feet should use 3" venting. See Table 2.

The 3" venting terminals (provided) must be used with the 3" vent pipe. Two, approved 4" vent terminals (not provided) must be used with 4" vent pipe. See replacement parts list for terminals.

2. SELECTION OF MATERIALS

PRIMER It is recommended that Tetrahydrofuran (THF) be used to prepare the surfaces of pipe and fittings for solvent welding. Do not use water, rags, gasoline or any other substitutes for cleaning PVC cellular core, ABS or CPVC surfaces. A chemical cleaner such as MEK may be used.

IMPORTANT

When multiple units are direct vented through a wall (3" or 4" venting), all intake vent terminals should be no lower than the highest exhaust vent terminal.

CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10-20% (by weight) virgin PVC material solvated with tetrahydrofuran (THF). Small quantities of dimethyl formamide (DMF) may be included to act as a retarding agent to extend curing time. Select the proper cement; Schedule 40 cement should be used for Schedule 40 pipe. Never use all-purpose cements, commercial glues and adhesives or ABS cement to join PVC or CPVC pipe and fittings.

NOTE: This unit can be vented using only PVC (Class 160, ASTM D-2241 Schedule 40, ASTM D-1785 ; or Cellular Core Schedule 40 DWV, ASTM F-891) , Schedule 40 CPVC (ASTM F-411), or ABS (ASTM D-2661) pipe. The fittings, other than the TERMINATIONS should be equivalent to PVC- DWV fittings meeting ASTM D-2665 (Use CPVC fittings, ASTM F-438 for CPVC pipe and ABS fittings, ASTM D-2661/3311 for ABS pipe. If CPVC or ABS pipe and fittings are used, then the proper cement must be used for all joints, including joining the pipe to the Termination (PVC Material). PVC Materials should use ASTM D-2564 Grade Cement; CPVC Materials should use ASTM F-493 Grade Cement and ; ABS Materials should use ASTM D-2235 Grade Cement.

SAFETY PRECAUTION: PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME. ALSO, USE ONLY IN A WELL-VENTILATED AREA.

Page 13 of the State Industries 100 user manual — (SEE FIGURE 12)
Page 13 · click to enlarge
Page 13

CONTROLS AND SWITCHES

LOW GAS PRESSURE SWITCH

(SEE FIGURE 12)

All models are provided with four pressure switches. These switches are essential to the safe and proper operation of the unit. All switches are wired in series. The controller is set up to shut the unit down whenever there is a failure of any of the switches. It is important to understand the purpose of each switch.

The Low Gas Switch (LGS) is a single-pole, normally open pressure switch that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa) W.C. is encountered. The contacts will open when the pressure falls below the fixed set point of 4.8"WC (1.18Kpa) for natural gas models and 8.5"WC (2.08Kpa) for propane models. The LGS monitors the gas supply pressure to the heater. If the gas supply falls below 5.0 in. (1.25Kpa) W.C., the main burner is extinguished (if heater is running) or the heater will not start up.

State Industries 100 — LOW GAS PRESSURE SWITCH diagram (page 13)
Fig. 18

ON/OFF SWITCH The ON/OFF Switch is a single-pole, single-throw rocker switch. This switch provides 120V from the line source to the heater.

HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by high temperature (>1800°F or >982°C). When 120VAC is applied to the igniter, sufficient heat is generated to ignite the main burner. Although improvements have been made to strengthen the igniter, it is still fragile and care must be taken when handling the igniter to prevent breakage.

GAS PIPING

FIGURE 12.

Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.

BLOWER PROVER SWITCH

Size the main gas line in accordance with Table 3. The figures shown are for straight lengths of pipe at 0.5" (125Pa) W.C. pressure drop, which is considered normal for low pressure systems Note that fittings such as elbows and tees will add to the pipe pressure drop.

(SEE FIGURE 12)

The Blower Prover Switch is provided on the heater to verify that the fan is operating. It is a positive pressure switch whose electrical contacts are normally open. When the fan increases the pressure in the burner, the pressure switch will allow the electrical contacts to close. The pressure switch is connected to the burner tap by a piece of tygon tubing. This tubing must be connected in order for the switch to change the electrical contacts. The controller requires that the electrical contacts on this air flow switch be open before it will allow the blower to come on.

TABLE 3. MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (Based upon a Pressure Drop of 0.5") Water Column and 0.6 Specific Gravity Gas and max. gas pressure of 0.5 psig)

BLOCKED OUTLET PROVER SWITCH

LENGTH NORMAL IRON PIPE SIZES (INCHES) IN INPUT IN THOUSANDS BTU/HR FEET 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990 1900 3000 5300 10900 50 73 151 285 580 900 1680 2650 4750 9700 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 1850 3250 6700 125 44 93 175 360 550 1020 1650 2950 6000 150 40 84 160 325 500 950 1500 2650 5500 175 37 77 145 300 460 850 1370 2450 5000 200 35 72 135 280 430 800 1280 2280 4600

(SEE FIGURE 12)

The Blocked Outlet Prover Switch is set up to shut the unit off when a build-up of positive pressure in the exhaust vent pipe occurs. This switch is a positive pressure switch that requires an increase in pressure to change the electrical contacts from normally closed to open. When this switch prevents the unit from igniting, most likely the exhaust is blocked by some means Check to see if the condensate is allowed to flow freely from the exhaust elbow and for obstructions in the exhaust venting and exhaust vent terminal. Also verify that there is no more than fifty equivalent feet (15.2 m) of three inch PVC vent pipe on the exhaust.

BLOCKED INLET PROVER SWITCH

LENGTH NORMAL IRON PIPE SIZES (INCHES) IN INPUT IN KW METERS 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 3.0 51 105 199 410 615 1160 1845 3221 6735 6.1 35 73 142 278 428 805 1277 2255 4626 9.1 28 59 110 225 346 644 1031 1830 3748 12.2 24 50 94 193 290 556 878 1552 3192 15.2 21 44 83 170 264 492 776 1391 2840 18.3 19 40 76 155 237 445 703 1259 2577 21.3 18 37 70 143 220 410 659 1142 2372 24.4 17 35 64 135 202 381 600 1083 2196 27.4 16 32 60 126 190 357 571 1010 2108 30.5 15 30 57 117 182 337 542 952 1962 38.1 13 27 51 105 161 299 483 864 1757 45.7 12 25 47 95 146 278 439 776 1610 53.3 11 23 42 88 135 249 401 717 1464 61.0 10 21 40 82 126 234 375 688 1347

(SEE FIGURE 12)

The Blocked Inlet Prover Switch is set up to shut the unit off when a build-up of negative pressure in the intake vent pipe occurs. This switch is a negative pressure switch that requires an increase in negative pressure to change the electrical contacts from normally closed to open. The switch is connected to the pressure tap on the PVC flange connected to the inlet of the blower. When this switch prevents the unit from igniting, most likely the intake is blocked by some means. Check to see if there is no more than fifty equivalent feet (15.2 m) of three inch PVC vent pipe on the intake. Also verify that the intake and intake vent terminal is free of obstructions that may prevent air from entering the unit.

Page 14 of the State Industries 100 user manual — CONNECTION OF GAS PIPE
Page 14 · click to enlarge
Page 14
State Industries 100 — CONNECTION OF GAS PIPE diagram (page 14)
Fig. 19

WARNING THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 10.5" (2.59 KPa) WATER COLUMN SUPPLY GAS PRESSURE. HIGHER GAS SUPPLY PRESSURES REQUIRE SUPPLEMENTAL REDUCING SERVICE REGULATION. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS CONTROLS WHICH COULD RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR DURING ICE STORMS.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIGURE 13). THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE NATIONAL FUEL GAS CODE.

FIGURE 14b. 150 Models Only

State Industries 100 — CONNECTION OF GAS PIPE diagram (page 14)
Fig. 20
State Industries 100 — CONNECTION OF GAS PIPE diagram (page 14)
Fig. 21

FIGURE 13.

CONNECTION OF GAS PIPE

1. When connecting gas pipe to unit, apply wrench to flange only. Note: Do not use wrench on gas valve or gas bracket. See Figure 14a, b, c.
2. PERFORM THE GAS LEAK TEST ANY TIME WORK IS DONE ON A GAS SYSTEM TO AVOID THE POSSIBILITY OF FIRE OR EXPLOSION WITH PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
State Industries 100 — CONNECTION OF GAS PIPE diagram (page 14)
Fig. 22

FIGURE 14c. 120 Models Only

The Gas Leak Test is performed as follows: Paint pipe connections upstream of gas control with a rich soap and water solution to test for leaks before operating main burner. Bubbles indicate gas leak. To stop leak, tighten pipe connections. After piping connections are checked, turn on main burner. With main burner in operation, paint pipe joints (including flanges), pilot gas tubing connections and control inlet and outlet with rich soap and water solution. Bubbles indicate gas leak. To stop leak, tighten flange screws, joints and pipe connections. Replace part if leak can’t be stopped.

To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

FIGURE 14a. 199/250 Models Only

Page 15 of the State Industries 100 user manual — THERMOMETERS (Not Supplied)
Page 15 · click to enlarge
Page 15

DISCONNECT THE APPLIANCE AND ITS MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45Kpa). GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45Kpa) OR LESS, THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE.

RELIEF VALVE

This heater is equipped with an approved temperature and pressure relief valve. ASME ratings cover pressure relief. CSA ratings cover release rate with temperature actuation.

FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED OR PLUGGED.

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING GAS LEAKS. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.

In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved temperature (ANSI) and pressure (ASME) relief valve(s). This relief valve shall comply with the standard for relief valves for hot water supply systems. ANSI Z21.22-CSA 4.4.

PURGING

Your local code authority may have other specific relief valve requirements.

Gas line purging is required with new piping or systems in which air has entered.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES OR RESTRICTIONS, NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. THE DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.

GAS METER SIZE - CITY GASES ONLY

Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If the gas meter is too small, ask the gas company to install a larger meter having adequate capacity.

GAS PRESSURE REGULATION

WATER LINE CONNECTIONS

Main line gas pressure to the water heater should be between a maximum 10.5" (2.59Kpa) W.C. (14.0"/3.45Kpa for propane) and a minimum as shown in Table 4: that is, for Natural Gas, 4.8" (1.18Kpa) W.C. and 8.5" (2.08Kpa) for Propane Gas. The inlet gas pressure must not exceed the maximum value. A service regulator must be installed within 10' (305 cm) of unit.

This manual provides detailed installation diagrams (see back section of this manual) for typical methods of application for the water heaters.

The water heater may be installed by itself, or with a separate storage tank.

CLOSED SYSTEM

GAS VALVES

Excessive pressure may develop causing premature tank failure or intermittent relief valve operation. This type of failure is not covered by the limited warranty. An expansion tank or a similar device may be required in the inlet supply line between the appliance and the meter or valve to compensate for the thermal expansion of water under supply pressure.

SYSTEM CONNECTIONS

If a water heater is installed in a closed water system, check local codes or contact the water supplier or local plumbing inspector on how to control this situation.

The system installation must conform to these instructions and to the local code authority having jurisdiction. Good practice requires that all heavy piping be supported.

THERMOMETERS (Not Supplied)

WATER (POTABLE) HEATING AND SPACE HEATING

Thermometers should be obtained and field installed as shown in the installation diagrams.

1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.

2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.
Page 16 of the State Industries 100 user manual — HEATER WIRING
Page 16 · click to enlarge
Page 16
3. This unit may never be connected to any existing heating system or component(s) previously used with non-potable water heating appliance.

CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST. MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT COVERED UNDER YOUR WARRANTY.

4. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams on pages 23 through 28 in back of manual for suggested piping arrangements.

The controller is wired to the heater as shown in Figure 15. The model and rating plate provides the electrical information needed to size the complete heater branch supply.

All electrical work must be installed in accordance with the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1 and local requirements.

HEATER WIRING

IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH 105°C OR ITS EQUIVALENT, EXCEPT IN THE BURNER HOUSING. IN THIS CASE USE 200°C WIRE.

When installed, the appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1.

THE COMPUTER CONTROL REQUIRES A SOURCE OF STABLE CLEAN ELECTRICITY FOR PROPER OPERATION. INSTALLING THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE, IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO MALFUNCTION. A HIGH QUALITY POWER

DO NOT ENERGIZE THE BRANCH CIRCUIT BEFORE THE HEATER TANK IS FILLED WITH WATER.

State Industries 100 — HEATER WIRING diagram (page 16)
Fig. 23

FIGURE 15.

Page 17 of the State Industries 100 user manual — USING THE ELECTRONIC CONTROLLER
Page 17 · click to enlarge
Page 17

USING THE ELECTRONIC CONTROLLER

1. Overview Interaction with the water heater controller is done through an up, a down, and three operation buttons. These buttons are illustrated to the right. Operation of the three lower buttons is defined immediately above them on the screen. The [UP] and [DN] buttons are used to navigate through the menus and make adjustments to the water heater.

While the water heater is operating, the user interface will display the desktop screen (if there are no active faults or warnings). An example of this screen is shown to the right. The first temperature on this screen is the temperature of the water inside the tank. The second temperature on this screen is the Operating Set Point. The Operating Set Point is the temperature at which the water heater will maintain the water inside the tank. The third line on the screen is a text description of the Operational State of the water heater (please see Operating States for more details).

The following status icons describe graphically operational details of the heater. The legend of all the status icons is listed below.

State Industries 100 — USING THE ELECTRONIC CONTROLLER diagram (page 17)
Fig. 24
State Industries 100 — USING THE ELECTRONIC CONTROLLER diagram (page 17)
Fig. 25
Page 18 of the State Industries 100 user manual — DISPLAY:
Page 18 · click to enlarge
Page 18
2. Operating States In the main desktop screen, there are some specific Operating States that are indicated on the status line. These are summarized below:
State Industries 100 — DISPLAY: diagram (page 18)
Fig. 26
3. Adjusting the Operating Set Point The Operating Set Point of this water heater determines the regulated temperature for the water in the tank. This parameter is adjusted in the Temperature menu. Items in this menu allow you to monitor different temperature readings in the tank along with adjusting the Operating Set Point and Differential .

ACTION: Press Change then use the UP and DOWN buttons to change the Set Point.

ACTION: From the desktop screen, press Menu.

DISPLAY:

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 18)
Fig. 27
State Industries 100 — DISPLAY: diagram (page 18)
Fig. 28

ACTION: From the Main Menu, press Select to enter the "Temperatures" screen.

ACTION: Press Update to accept the change or Cancel to reset it.

DISPLAY:

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 18)
Fig. 29
State Industries 100 — DISPLAY: diagram (page 18)
Fig. 30
Page 19 of the State Industries 100 user manual — DISPLAY:
Page 19 · click to enlarge
Page 19
4. Changing the Display Units The display interface to the heater has the option of selecting between degrees Fahrenheit and degrees Celsius for temperature displays. This can be found in the “Display Settings” menu. Also in this menu, you may adjust how the backlight operates and the contrast of the LCD screen.

There are two types of conditions that can occur during operation. These are Warnings and Faults:

  • Warnings: This is a non-safety related condition that the control has detected that may cause the water heater to operate in a less than optimal condition, but does not pose a safety concern.

ACTION: From the Main Menu, press the Down button to highlight "Display Set- tings" then press Select.

DISPLAY:

Example of a Warning:

State Industries 100 — DISPLAY: diagram (page 19)
Fig. 31
State Industries 100 — DISPLAY: diagram (page 19)
Fig. 32

ACTION: Use the UP and DOWN buttons to highlight the desired setting. Then press Change. Again, use the UP and DOWN buttons to scroll through the options for that setting.

  • Faults: This is a safety related condition that has been detected by the heater.

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 19)
Fig. 33

Example of a Fault:

State Industries 100 — DISPLAY: diagram (page 19)
Fig. 34

ACTION: Press Update to accept the change or Cancel to reject it.

Advanced Diagnostics Information When a fault or warning has been declared, advanced information can be found in the control. By pressing the Advanced button, detailed information can be found regarding diagnosing and resolving the problem.

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 19)
Fig. 35
6. Access to the Current Fault or Warning When a fault or warning has been detected by the control, it will automatically be displayed on the screen and the back light will blink. If you choose to leave the current fault or warning by pressing the Back key, you can always return to the fault screen through the menu.
State Industries 100 — DISPLAY: diagram (page 19)
Fig. 36

5. Fault and Warning Conditions This water heater is equipped with electronic controls that have the ability to monitor almost all aspects of the water heater operation. In the case that there is an undesirable or unsafe condition that occurs, the water heater controls will detect this condition and determine the appropriate action. Part of this is displaying the information on the LCD in plain text that accurately describes the condition and diagnostics information that can be used to correct the issue.

Page 20 of the State Industries 100 user manual — REQUIRED ABILITY
Page 20 · click to enlarge
Page 20

ACTION: To get to the current fault information screen, press Menu.

7. Viewing the Fault History The controller for this water heater will store a history of ten of the last Fault and Warning conditions that occurred. This is stored in the Fault History. Along with all the information about the fault, including a estimate time of when the fault occurred, information regarding the advanced diagnostics for that fault can be accessed at any time.

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 20)
Fig. 37

ACTION: Press the DOWN button for more information.

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 20)
Fig. 38

ACTION: Press the DOWN button to highlight "current Fault" and press Select.

DISPLAY:

ACTION: Press the DOWN key to scroll through the fault history. If you select a specific fault or warning, you may press the VIEW button to view details regarding this fault.

DISPLAY:

State Industries 100 — DISPLAY: diagram (page 20)
Fig. 39

ACTION: Press the DOWN button for more information.

DISPLAY:

8. Viewing Information About the Heater The electronic control for this water heater monitors many different aspects of the water to ensure safe and optimal operation. Much of the information monitored is available to view in two areas of the control. The first is the "Heater Status" and; the second is "Heater Information." These items can be selected through the main menu in the same fashion as described above. In these menus, detailed information about the water heater and the current status of specific conditions can be found.

PRIOR TO START UP

REQUIRED ABILITY

Be certain that the water heater is full of water, that air is purged from all lines, there are no leaks (gas and water), and all inlet water lines are open.

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.

The following test equipment should be on hand (all test equipment must be acclimated to ambient temperature before calibration and use.)

Before attempting start-up, thoroughly study and familiarize yourself with the exact sequence of operation and all other details on the specific heater being used.

– Two U-tube manometers or calibrated pressure gages that can read

0-10" (0-2.5Kpa) and 0-35" (0-8.7Kpa) W.C. pressure gauges.

The power burner is equipped with an ignition system which automatically sequences prepurge and ignition, senses and ignites main burner flame and sequences burner operation. Heater is equipped with an ignition control which locks out after three unsuccessful ignition attempts. Familiarize yourself with the sequence of operation of this unit prior to start-up.

  • Attach a gas pressure gauge or manometer to the upstream side of main gas cock and a gas pressure gauge or manometer to the manifold pressure tap (see Figure 15).
  • You are now ready to begin the burner start-up procedure.
Page 21 of the State Industries 100 user manual — ADJUSTMENT PROCEDURE Initial Start-up - 199 AND 250 MODELS
Page 21 · click to enlarge
Page 21

OPERATING INSTRUCTIONS

5. Check the vent system seams and joints and ensure that there is no discharge of flue products into the room.
6. Check the input rate.

For appliance installation locations with elevations above 6500 feet (1982 meters) refer to HIGH ALTITUDE INSTALLATIONS section of this manual.

a. Attach a pressure gauge (manometer) to the manifold pressure tap (Figure 16) and refer to Table 4, page 20 for correct pressure.

b. Use this formula to “clock” the meter. Be sure other gas consuming appliances are not operating during this interval.

NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND A PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER. DO NOT ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET VALVE CLOSED.

3600 X H = Btuh T

Should it be necessary to adjust the gas pressure to the burner, to obtain the full input rate, the steps below should be followed:

FILLING: 1. Close the heater drain valve. 2. Open a nearby hot water faucet to permit the air in the system to escape. 3. Fully open the cold water inlet pipe valve allowing the heater and piping

T = Time in seconds to burn 1 cubic foot of gas. (With a stopwatch read

the gas meter and measure the amount of time required for the heater to consume 1 cubic foot of gas.) H = Heating value of gas (in Btu’s per cubic foot of gas). Btuh = Actual heater input rate, in Btuh.

to be filled. 4. Close the hot water faucet as water starts to flow. 5. The heater is ready to be operated.

EXAMPLE(Using SUF-199 heater)

THE MAIN MANUAL GAS SHUTOFF VALVE MUST HAVE BEEN CLOSED FOR AT LEAST FIVE (5) MINUTES. THIS WAITING PERIOD IS AN IMPORTANT SAFETY STEP. ITS PURPOSE IS TO PERMIT GAS THAT MIGHT HAVE ACCUMULATED IN THE COMBUSTION CHAMBER TO CLEAR. IF YOU DETECT GAS AT THE END OF THIS PERIOD, DO NOT PROCEED WITH LIGHTING. RECOGNIZE THAT GAS ODOR, EVEN IF IT SEEMS WEAK, MAY INDICATE THE PRESENCE OF ACCUMULATED GAS SOMEPLACE IN THE AREA WITH A RISK OF FIRE OR EXPLOSION. SEE THE FRONT PAGE FOR STEPS TO BE TAKEN.

T = 25.25 seconds H = 1050 Btu/ft.3

3600 X 1050 = 150,000 Btuh (44 Kw) 25.25

BTUH = ?

For high altitude installations, compare result to the derated input required for the elevation at the installation location.

c. Remove the pressure regulator cover screw (Figure 16) and adjust the

pressure by turning the adjusting screw with a small screwdriver. Do not exceed 4.0" (1 kPa) natural gas models and 10.0" W.C. (2.5Kpa) on the propane models.

DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE HEATER AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.

Clockwise to increase gas pressure and input rate.

Counterclockwise to decrease gas pressure and input rate.

LIGHT THE UNIT IN ACCORDANCE WITH THE OPERATING INSTRUCTIONS LABEL ATTACHED TO THE HEATER.

d. “Clock” the meter as in step (b) above. e. Repeat steps (c) and (d) until the specified input rate is achieved. f. Turn the manual gas valve to “OFF”. Replace the pressure regulator cover screw. Remove the pressure gauge or manometer from the manifold pressure tap. Replace the set screw in the manifold pressure tap. If the gas pressure regulator cannot be adjusted to give the full input rating with sufficient gas pressure at the valve, check to ensure the unit is equipped with the correct orifice.

THESE INSTRUCTIONS ARE REPEATED IN THE LIGHTING AND OPERATING LABEL ILLUSTRATION ON PAGE 20 IN THIS MANUAL.

ADJUSTMENT PROCEDURE Initial Start-up - 120 AND 150 MODELS

Main line gas pressure to the water heater for natural gas should be between a maximum of 10.5" (2.59Kpa for natural gas) W.C. (14.0"/3.45Kpa for propane) and a minimum as shown in Table 4: that is, for Natural Gas, 4.8 (1.18Kpa) W.C. and 8.5" (2.08Kpa) for Propane Gas. The inlet gas pressure must not exceed the maximum value. A service regulator must be installed within 10' (305 cm) of the unit.

ADJUSTMENT PROCEDURE Initial Start-up - 199 AND 250 MODELS

Main line gas pressure to the water heater for natural gas should be between a maximum of 10.5" (2.59Kpa for natural gas) W.C. (14.0"/3.45Kpa for propane) and a minimum as shown in Table 4: that is, for Natural Gas 4" (.98Kpa) W.C. and 9.0" (1.97Kpa) for Propane Gas. The inlet gas pressure must not exceed the maximum value. A service regulator must be installed within 10' (305 cm) of the unit.

1. Check gas line pressure with a manometer. 2. Check manifold pressure (see Table 4, page 20) using a pressure gauge (manometer) connected to the manifold pressure tap on the gas control valve, (Figure 15).

The SUF 199 and 250 models incorporate a new gas control, which operates at 0"W.C. (0kPa) for both natural and propane gas. These models are configured prior to being shipped from the factory and no adjustments are necessary prior to startup. The controller monitors the air-flow and makes adjustments to the fan speed which in effect controls the amount of gas flow. Therefore, the unit will self-adjust to acquire the correct amount of input.

If full rate adjustment is required, remove cover screw from top of the gas control valve, (Figure 15).

Using a small screwdriver, turn adjusting screw clockwise

to decrease gas pressure to obtain 4.0" (1 kPa) for natural gas and 10.0" W.C. (2.5 Kpa) for L.P. Gas.

Once the unit is installed and filled with water and the inlet pressures confirmed, simply turn the switch "on" and observe operation. Cycle the unit

3. Cycle the burner on and off several times to check its operation.
4. Check the operation of the limit and operating controls.

"off" and "on" several times to ensure proper operation.

to increase · or counterclockwise

Page 22 of the State Industries 100 user manual — TABLE 4
Page 22 · click to enlarge
Page 22

HIGH ALTITUDE INSTALLATIONS

CATHODIC PROTECTION

CAUTION HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR MORE). HYDROGEN GAS IS EXTREMELY FLAMMABLE. To reduce the risk of injury under these conditions, it is recommended that a hot water faucet be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.

Some gas utility companies derate their gas for altitude, making it unnecessary to install high altitude orifices. Call the local gas or utility company to verify BTU content.

Due to the input rating reduction at high altitudes, the output rating of the appliance is also reduced and should be compensated for in the sizing of the equipment for applications.

PRECAUTIONS

MAINTENANCE

IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE BEEN MADE BY A QUALIFIED SERVICEMAN.

GENERAL

1. FLOODING TO OR ABOVE THE LEVEL OF THE BURNER OR CONTROLS

KEEP APPLIANCE AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. (SEE WARNING ON PAGE 5, LOCATING THE HEATER).

2. EXTERNAL FIRING

3. DAMAGE

Water heater maintenance includes periodic tank flushing and cleaning, and removal of lime scale. The unit should be inspected and adjusted to maintain proper combustion. Refer to the following table. A periodic inspection of the venting system should be made. Where used, the water circulating pump should be oiled.

4. FIRING WITHOUT WATER

5. SOOTING

NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER.

MAINTENANCE SCHEDULE

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.

Following are the instructions for performing some of the recommended maintenance. Unit inspection and adjustment should be performed by a competent technician.

GENERAL INFORMATION

POWER BURNER

The initial start-up procedure of the unit is provided on page 18.

COMPONENT OPERATION INTERVAL REQUIRED

The sequence of operation of the unit is provided on page 15.

Tank Sediment Monthly Flushing Removal

It is important to note that the controller has a reset button on the control box, Figure 1. The reset button is a safety device and would not normally be used.

Tank Lime Scale Semi UN-LIME®

HIGH LIMIT

The high limit (not adjustable) is factory set to cutout at 202°F (94°C). The controller must be manually reset by depressing the reset button on front of the control when water temperature drops to below 160°F (71°C).

Relief Valve Inspect Semi Annually

TABLE 4

State Industries 100 — TABLE 4 diagram (page 22)
Fig. 40

Clean Inlet Blower Screen and As Required Soft Brush Blower Wheel

Vent System Inspect Every 3 Joints should Months be sealed

Removal Annually Delimer

Page 23 of the State Industries 100 user manual — FOR YOUR SAFETY READ BEFORE OPERATING
Page 23 · click to enlarge
Page 23
State Industries 100 — HIGH ALTITUDE INSTALLATIONS diagram (page 23)
Fig. 41

FOR YOUR SAFETY READ BEFORE OPERATING

120 MODELS ONLY.

Page 24 of the State Industries 100 user manual — OPERATING INSTRUCTIONS
Page 24 · click to enlarge
Page 24
State Industries 100 — HIGH ALTITUDE INSTALLATIONS diagram (page 24)
Fig. 42

FOR YOUR SAFETY READ BEFORE OPERATING

OPERATING INSTRUCTIONS

TURN OFF GAS TO APPLIANCE

150 MODELS ONLY.

Page 25 of the State Industries 100 user manual — OPERATING INSTRUCTIONS
Page 25 · click to enlarge
Page 25
State Industries 100 — HIGH ALTITUDE INSTALLATIONS diagram (page 25)
Fig. 43

FOR YOUR SAFETY READ BEFORE OPERATING

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS

TURN OFF GAS TO APPLIANCE

TURN OFF GAS TO APPLIANCE

199/250 MODELS ONLY.

Page 26 of the State Industries 100 user manual — POWERED ANODE SYSTEM
Page 26 · click to enlarge
Page 26

FLUSHING

State Industries 100 — FLUSHING diagram (page 26)
Fig. 44
1. Turn off the heater electrical disconnect switch.
2. Open the drain valve and allow water to flow until it runs clean.
3. Close the drain valve when finished flushing.
4. Turn on the heater electrical disconnect switch.

DRAINING

The heater must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater.

1. Turn off the heater electrical disconnect switch.
2. Close the cold water inlet valve to heater.

FIGURE 16.

3. Open a nearby hot water faucet to vent the system.

To dissolve and remove the more stubborn mineral deposits, State UN•LIME® Professional Delimer should be used.

4. Open the heater drain valve.
5. If the heater is being drained for an extended shutdown, it is suggested the drain valve be left open during this period.

State UN•LIME® Professional Delimer is an easy to handle patented food grade acid formulated specifically for lime scale removal from all types of water using equipment. Available in 1 gallon (3.8L) (part no. 4763) and 5 gallon (19L) (part no. 4813) sizes. Hydrochloric base acids are not recommended for use on glass-lined tanks.

  • Follow FILLING instructions when restoring hot water service.

SEDIMENT REMOVAL

Waterborne impurities consist of the particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank.

State Form No. 4800, entitled “Why, When and How”, describes tank cleaning methods and materials. UN•LIME and the booklet may be obtained through your State dealer or distributor.

For convenience, sediment removal and lime scale removal should be performed at the same time.

The cleanout opening is shown in Figure 16. To clean heater through cleanout opening, proceed as follow:

LIME SCALE REMOVAL

1. Turn off water inlet valve, the heater electrical disconnect switch and open drain valve.

The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils.

2. Remove outer cover plate from lower side of heater jacket.
3. Remove cover from cleanout opening.

Lime accumulation not only reduces the life of the equipment but also reduces efficiency of the heater and increases fuel consumption.

4. Remove lime, scale or sediment using care not to damage the glass-lining.

The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.

5. Inspect cleanout plate gasket: If new gasket is required, replace with State part no. 99038.

The depth of lime buildup should be measured periodically. Heaters will have about 3" (7.6cm) of lime buildup when the level of lime has reached the bottom of the cleanout opening or about 1" (2.5cm) of lime buildup if it has reached the drain valve opening. A schedule for deliming should be set up, based on the amount of time it would take for a 1" (2.5cm) buildup of lime.

6. Install cleanout plate. Be sure to draw plate up tight by tightening screws securely.
7. Close drain valve, open water inlet line and turn on the power burner electrical disconnect switch.

Example 1: Initial inspection shows 1/2" (1.3cm) of lime accumulation. Therefore, the heater can be delimed once a year.

8. Check for water leakage.
9. Replace outer jacket cover plate.

Example 2 : Initial inspection shows 2" (5cm) of lime accumulation. Therefore, the heater should be delimed every 3 months.

POWERED ANODE SYSTEM

Sediment and lime scale removal may be accomplished through the cleanout opening furnished on the heater, see Figure 25. The heater must be drained, see DRAINING, before removing cleanout cover on tank.

The SUF heaters are factory equipped with a powered anode system. The anodes are of a permanent design and do not need replacing unless damaged.

Page 27 of the State Industries 100 user manual — VENT SYSTEM
Page 27 · click to enlarge
Page 27

DRAIN VALVE AND ACCESS PANELS

to build until the relief valve actuation pressure is equaled. Then, the relief valve will open, allowing some water to escape, slightly lowering the pressure.

The heaters are equipped with a 3/4" drain valve.

An access panel covers the cleanout opening in the tank which is sealed by a gasket and cover, figure 25.

Contact your water supplier or local plumbing inspector on how to control this situation.

RELIEF VALVE

Two common corrections are listed in the Checklist and Service Information which appears later in this manual.

At least twice a year, the temperature and pressure relief valve should be checked to ensure that it is in operating condition. To check the relief valve, lift the lever at the end of the valve several times. The valve should seat properly and operate freely.

ABOVE ALL, DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE. THIS IS NOT A SOLUTION AND CAN CREATE A HAZARDOUS SITUATION.

If water does not flow, remove and inspect for obstructions or corrosion. Replace with a new valve of the recommended size as necessary. Inspection of the valve should be performed at least every three years. Do not attempt to repair the valve, as this could result in improper operation and a tank explosion. In areas with poor water conditions, it may be necessary to inspect the T&P valve more often than every three years.

CIRCULATING PUMP

The water heating system may include a circulating pump. Where used, it should be lubricated as directed by the circulator manufacturer.

VENT SYSTEM

Examine the vent system every 3 months. Points of inspection are as follows:

1. Check for obstructions and/or deterioration of vent piping and vent hood. Replace immediately where needed.
2. Vent pipe and vent hood screen should be cleaned of foreign material and soot. The screen is located inside the vent hood outlet and is accessible from the outside of the hood. Do not reach inside the vent hood when the heater is in operation.

If the temperature and pressure relief valve on the heater discharges periodically or continuously, it may be due to thermal expansion of water in a closed water supply system, or, it may be due to a faulty relief valve.

Thermal expansion is the normal response of water when it is heated. In a closed system, thermal expansion will cause the system pressure

3. Check all vent system connections for leakage and reseal as required using Hi Temp Silicone sealer or equivalent.
Page 28 of the State Industries 100 user manual — * PIPE TO OPEN DRAIN
Page 28 · click to enlarge
Page 28

INSTALLATION DIAGRAMS

ONE TEMPERATURE - ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION

WITH OR WITHOUT BUILDING RECIRCULATION

State Industries 100 — ONE TEMPERATURE - ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION diagram (page 28)
Fig. 45
State Industries 100 — ONE TEMPERATURE - ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION diagram (page 28)
Fig. 46
State Industries 100 — ONE TEMPERATURE - ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION diagram (page 28)
Fig. 47

* PIPE TO OPEN DRAIN

INSTALL IN ACCORDANCE WITH LOCAL CODES

ONE TEMPERATURE - ONE HEATER HORIZONTAL STORAGE TANK FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION

State Industries 100 — * PIPE TO OPEN DRAIN diagram (page 28)
Fig. 48

* PIPE TO OPEN DRAIN

INSTALL IN ACCORDANCE WITH LOCAL CODES

State Industries 100 — * PIPE TO OPEN DRAIN diagram (page 28)
Fig. 49
Page 29 of the State Industries 100 user manual — TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE
Page 29 · click to enlarge
Page 29

TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE

WITH OR WITHOUT BUILDING RECIRCULATION

*PIPE RELIEF VALVE TO OPEN DRAIN.

INSTALL IN ACCORDANCE WITH LOCAL CODES.

State Industries 100 — TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE diagram (page 29)
Fig. 50
State Industries 100 — TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE diagram (page 29)
Fig. 51
State Industries 100 — TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE diagram (page 29)
Fig. 52
Page 30 of the State Industries 100 user manual — MUST BE IDENTICAL HEATERS
Page 30 · click to enlarge
Page 30

TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE

WITH OR WITHOUT BUILDING RECIRCULATION

State Industries 100 — TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE diagram (page 30)
Fig. 53
State Industries 100 — TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE diagram (page 30)
Fig. 54
State Industries 100 — TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE diagram (page 30)
Fig. 55

TWO TEMPERATURE - THREE HEATERS (TWO PRE-HEATERS/ONE BOOSTER HEATER)

WITH OR WITHOUT BUILDING RECIRCULATION

MUST BE IDENTICAL HEATERS

FOR MULTIPLE HEATER INSTALLATION SEE MANIFOLD KIT SPECIFICATIONS, PAGE 33.

Page 31 of the State Industries 100 user manual — TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)
Page 31 · click to enlarge
Page 31

TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)

WITH OR WITHOUT BUILDING RECIRCULATION

* PIPE RELIEF VALVE TO OPEN DRAIN

** 140°F (60°C) TO 150°F (66°C) SHOULD BE MAXIMUM WATER TEMPERATURE MAINTAINED IN THE PRE-HEATERS.

120°F (49°C) SHOULD BE THE MINIMUM TEMPERATURE OF WATER IN THE PRE- HEATERS.

CONNECT CIRCULATING LINE FROM FIXTURES, IF USED, TO COLD WATER SUPPLY LINE OF PRE-HEATER.

CONNECT CIRCULATING LINE OF 180°F (82°C) OR BOOSTED WATER, IF USED, TO INLET WATER LINE TO BOOSTER.

State Industries 100 — TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER) diagram (page 31)
Fig. 56

INSTALL IN ACCORDANCE WITH LOCAL CODES.

State Industries 100 — TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER) diagram (page 31)
Fig. 57
Page 32 of the State Industries 100 user manual — INSTALL IN ACCORDANCE WITH LOCAL CODES
Page 32 · click to enlarge
Page 32

TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE

WITH RECIRCULATION OF SANITIZING LOOP

State Industries 100 — TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE diagram (page 32)
Fig. 58

*PIPE RELIEF VALVE TO OPEN DRAIN

INSTALL IN ACCORDANCE WITH LOCAL CODES

Page 33 of the State Industries 100 user manual — MANIFOLD KITS
Page 33 · click to enlarge
Page 33

MANIFOLD KITS

Precision cut type “L” all copper State manifold kits assure water flow balance of all units. Without this balance, the full water heating and storage potential of the system cannot be achieved. Plus, the units with the higher water flow may have a shortened life.

Dimensions shown are for minimum space occupied by the water heaters assemblies.

Space for the venting system and unit servicing must be added.

State Industries 100 — MANIFOLD KITS diagram (page 33)
Fig. 59
State Industries 100 — MANIFOLD KITS diagram (page 33)
Fig. 60
State Industries 100 — MANIFOLD KITS diagram (page 33)
Fig. 61
Page 34 of the State Industries 100 user manual — WATER HEATER MAKES SOUNDS
Page 34 · click to enlarge
Page 34

CHECKLIST AND SERVICE INFORMATION

2. Some of the electrical components of the water heater make sounds

which are normal.

  • Contacts click or snap as the heater starts and stops.
  • Transformers often hum.

WATER LEAKAGE IS SUSPECTED

1. Check to see if the water heater drain valve is tightly closed. Also

check the cleanout opening for leakage.

BE SURE TO TURN OFF THE ELECTRICITY WHENEVER POSSIBLE OR APPROPRIATE WHILE CHECKING EQUIPMENT.

2. The apparent leakage may be condensation which forms on cool

surfaces of the heater and piping.

3. If the outlet of the relief valve is leaking it may represent:
  • Excessive water pressure.
  • Excessive water temperature.
  • Faulty relief valve.

Excessive water pressure is the most common cause of relief valve leakage. It is often caused by a “closed system”. If a check valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main. The relief valve must release this water or the water heater or plumbing system will be damaged. Refer to MAINTENANCE-RELIEF VALVE section in this manual.

VERIFY PROPER OPERATION AFTER SERVICING.

BURNER OPERATIONAL PROBLEMS

1. Refer to TROUBLESHOOTING.

When such a condition is encountered, local codes or inspection agency should be consulted to determine which system is acceptable in your area. See CLOSED SYSTEM section in this manual also.

NOT ENOUGH OR NO HOT WATER

1. Be certain the electrical disconnect switch serving the water heater

is in the ON position.

TROUBLE-SHOOTING

2. Check the fuses.
1. Verify that the allowable vent length has not been exceeded and that the blower inlet screen has been removed if direct venting.
  • The electrical disconnect switch usually contains fuses.
2. Verify that the condensation, which WILL be present in the heater and exhaust vent, will drain.
3. The capacity of the heater may have been exceeded by a large demand

for hot water.

3. Check supply wire polarity - hot to hot and neutral to neutral and no "stray" current in neutral.
  • Large demands require a recovery period to restore water temperature.
4. Heater is properly grounded.
4. Colder incoming water temperature will lengthen the time required to

heat water to the desired temperature.

Checking these four (4) items first will often result in a timely solution to the service call.

  • If the heater was installed when incoming water temperature was warm, colder water creates the effect of less hot water.
5. Look for hot water wastage and leaking or open hot water faucets.
6. Sediment or lime scale may be affecting water heater operation. Refer

to MAINTENANCE for details.

7. Burner may not be firing at proper rate.
  • Check gas pressure. Adjust to obtain required manifold pressure.

ALTERING THE CONTROLLER AND/OR CONTROLLER WIRING IN ANY WAY COULD RESULT IN INTERNAL DAMAGE TO THE MODULE CIRCUITS, POSSIBLY ALTERING THE IGNITION SEQUENCE ALLOWING GAS VALVES TO OPEN BEFORE THE HOT SURFACE IGNITER IS UP TO IGNITION TEMPERATURE.

8. Burner fan wheel may be dirty.
  • Clean fan wheel with a stiff brush.
9. Condensate hose may be blocked where it connects to the exhaust

elbow.

  • Verify the condensate drains from the unit without restriction.

Before performing any troubleshooting familiarize yourself with the particular appliance.

WATER IS TOO HOT

Refer to the SEQUENCE OF OPERATION and the connection diagram located on page 15 before continuing.

1. Refer to WATER TEMPERATURE CONTROL.

Make sure the appliance is connected to a 120V AC power supply, manual gas valve is in the ON position, and all electrical connections are secure before continuing to troubleshoot this appliance.

WATER HEATER MAKES SOUNDS

1. Sediment or lime scale accumulations cause rumbling and pounding

noises when the heater is operating.

  • The sounds are normal, however, the tank bottom should be cleaned.

Refer to MAINTENANCE for details.

Page 35 of the State Industries 100 user manual — REPLACEMENT PARTS
Page 35 · click to enlarge
Page 35

MOTOR WILL NOT RUN

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Confirm 120V AC to the controller. Also, to verify correct polarity, check for 120 V AC between hot supply and ground.
1. Reset the appliance two more times to ensure that all of the air has been purged from the gas line.

If there is no voltage, check for a loose connection where it connects to the controller.

2. If the burner lights momentarily but does not sustain ignition, verify that the inlet pressure is not greater than 10.5" WC (2.59 kPa) for natural gas and 14.0" WC (3.45 kPa) for propane gas or lower than the minimal supply pressure which is 4.0" WC (.09kPa) for natural gas and 11.0"WC (2.74 kPa) for propane gas. Also, verify that the manifold pressure is correct, that is, 4.0"WC (.98kPa) for natural gas and 10.0"WC (2.46kPa) for propane gas for the 120 and 150 models and 0"WC (0kPa) for both natural and propane gas 199 and 250 models. If the manifold pressure is not correct then adjust accordingly. See "ADJUSTMENT PROCEDURE" in "OPERATING INSTRUCTIONS" sections for manifold pressure adjustment procedure.

2. If there is 120 volts to the controller, check for loose connections or a locked rotor. If the rotor cannot be freed the motor and blower assembly must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN

FLAME NOT ESTABLISHED.

1. Check to see if main manual gas valve is open.
2. Check for a loose connection at the transformer, or a defective transformer.
3. Check for the reversed polarity in the supply wiring. This controller is polarity sensitive. If the hot and neutral supply wires are reversed, the controller will not sense flame. Reverse the supply wires and try to fire the unit.
3. Check for a loose connection at the gas valve.
4. Check for open pressure switches or open reset button. Check for blockage in the intake and exhaust venting or at the vent hoods. If no blockage is found, check vinyl tubing for cuts or crimps. If this tubing is damaged it must be replaced. If these steps do not eliminate the problem, replace the pressure switches.
4. Check connecting wire to the flame sensor. Verify that the flame sensor has not been damaged in any way.
5. Check to see if there is resistance across the igniter terminal with an OHM meter. If there is no continuity, the igniter is broken and should be replaced.
5. Verify that the air supply is adequate. The air inlet screen or blower wheel may be restricted. Also, check the installation for proper ventilation. See AIR REQUIREMENTS.

If the igniter appears to function properly, then verify that the inlet pressure is within the range shown in Table 4. The gas valve supplied on the appliance is not designed to open against a higher inlet pressure of 10.5"WC (2.59kPa) for natural gas and 14.0"WC (3.45kPa) for propane gas. At this time, also check to make sure the inlet pressure is not lower than 4.0"WC (.98kPa) for natural gas and 11.0"WC (2.74kPa) for propane gas. If the inlet pressure is not within these limits then adjust the supply pressure accordingly.

6. Check the venting system for the correct sizing, excess or insufficient. See VENTING.

7. Check for maximum inlet pressure of 10.5"WC (2.59 kPa) for natural gas and 14.0"WC (3.45 kPa) for propane gas and the manifold pressure which is 4.0"WC (.98 kPa) for natural gas and 10.0"WC (2.46 kPa) for propane gas for the 120 and 150 models and 0"WC (o kPa) for both natural and propane gas 199 and 250 models. Please note that the manifold pressure listed is the maximum value for the manifold pressure. Do not set the manifold pressure higher than the value show in Table 4. OVER FIRING the heater will result in a rough ignition and/or noisy operation.

If the inlet pressure falls within the allowable limits, then verify that the manifold pressure, when the gas is fully open, with the heater running, is as called out in Table 4: that is, 4.0"WC (.98kPa) for natural gas and 10.0"WC (2.46kPa) for propane gas for the 120 and 150 models and 0"WC (0kPa) for both natural and propane gas 199 and 250 models. If the manifold pressure is not correct then adjust accordingly. See "ADJUSTMENT PROCEDURE" in "OPERATING INSTRUCTIONS" sections for manifold pressure adjustment procedure.

8. Confirm that the air inlet screen (see Figures 7 & 8) is free of obstructions.
6. If the inlet and manifold pressures are within the limits specified in step 5, then reset the appliance. Verify 24V AC at the gas valve during the three (3) second ignition trial, after the igniter reaches operating temperature. If 24V AC at the gas valve is not seen during this period, the controller must be replaced.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect, replace.

If there is 24V AC at the gas valve during the four second ignition trial and the manifold pressure does not increase above 0" W.C. then verify that the manual gas control valve is in the “ON” position (see page 20). If the valve is in the “ON” position and the previous voltage and gas pressure conditions are met, then the gas valve is defective and must be replaced.

REPLACEMENT PARTS

Replacement parts may be ordered through State dealers, authorized servicers or distributors. Refer to the Yellow Pages for where to call or contact the State Water Heaters, 500 Tennessee Waltz Parkway, Ashland City, TN 37015, 1-800-821-2017. When ordering parts be sure to state the quantity, part number and description of the items including the complete model and serial number as it appears on the product. Refer to the parts list for more information.

Page 36 of the State Industries 100 user manual — MODEL SUF LIMITED WARRANTY
Page 36 · click to enlarge
Page 36

MODEL SUF LIMITED WARRANTY

State Water Heaters, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.

1. THE TANK If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable water therein, during the first THREE years after initial installation, the warrantor will supply a replacement tank less burner and controls or a complete new State water heater of equivalent size and current model at the warrantor’s option. Some government agencies are requiring energy efficient standards for water heaters. In the event regulations prohibit sale of a model of equivalent size and construction, State will provide a model which complies with the regulations of your area., in which case the consumer will be charged the difference in price between the like replacement and the energy efficient model required. The warranty on the replacement water heater will be limited to the unexpired term of the original warranty. 2. ALL OTHER PARTS If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in material or workmanship, the warrantor will repair or replace such part or portion at its option. 3. CONDITIONS AND EXCEPTIONS This warranty shall apply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by CSA and approved by the American Society of Mechanical Engineers, must have been installed. a. This warranty shall apply only when the heater is used: (1) at temperatures not exceeding the maximum setting of its thermostat; (2) at water pressure not exceeding the working pressure shown on the heater; (3) when operated free of the damaging effects of uncontrolled water hammer; (4) when filled with potable water, free to circulate at all times; (5) in a non-corrosive and non-contaminated atmosphere; (6) with factory approved anode(s) installed; (7) in the United States, its territories or possessions, and Canada; (8) sized in accordance with proper sizing techniques for commercial and/or residential water heaters; (9) bearing a rating plate which has not been altered, defaced or removed, except as required by the warrantor; (10) operated with properly installed dirt leg; (11) fired with the fuel for which it was factory built; (12) fired at the factory rated input; b. Any accident to the water heater, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, or any attempt to repair tank leaks will void this warranty. c. This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is connected to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The relief valve installed on the heater is not an acceptable method. d. This warranty shall be void and shall have no effect if the design or structure of the water heater is, or is attempted to be modified or altered in any way, including, but not limited to, by attaching non-company approved appliances or equipment. 4. SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs. Such costs may include but are not limited to: a. Labor charges for service removal, repair or reinstallation of the water heater or any component part; b. Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and returning the claimed defective heater or part to such distributor. c. All cost necessary or incidental for any material and/or permits required for installation of the replacement. 5. LIMITATIONS ON IMPLIED WARRANTIES Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state law are limited to one (1) year duration for the heater or any of its parts. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. 6. CLAIM PROCEDURE Any claim under the warranty should be initiated with the dealer who sold the boiler, or with any other dealer handling the warrantor’s products. If this is not practicable, the owner should contact: U.S. Customers Canadian Customers State Water Heaters State Water Heaters 500 Tennessee Waltz Parkway P. O. Box, 310 - 768 Erie Street Ashland City, TN 37015 Stratford (Ontario) N5A 6T3 Telephone: 1-(800)-365-0024 Telephone: 1-(800)-265-8520 a. The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor. b. Dealer replacements are made subject to in-warranty validation by warrantor. 7. DISCLAIMERS NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE BOILER. THE WARRANTOR SHALL NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR TORT. a. Some states do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may not apply to you. b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the heater’s rating plate.

Model No Serial No Date Installed

Dealer’s Address Phone No

City and State Zip Code

KEEP THIS WARRANTY POSTED ADJACENT TO THE HEATER FOR FUTURE REFERENCE

Dealer’s Name

Page 37 of the State Industries 100 user manual — NOTES:
Page 37 · click to enlarge
Page 37

NOTES:

Page 38 of the State Industries 100 user manual — NOTES:
Page 38 · click to enlarge
Page 38

NOTES:

Page 39 of the State Industries 100 user manual — NOTES:
Page 39 · click to enlarge
Page 39

NOTES:

Page 40 of the State Industries 100 user manual — 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY, TN 37015
Page 40 · click to enlarge
Page 40
State Industries 100 — HIGH ALTITUDE INSTALLATIONS diagram (page 40)
Fig. 62

500 TENNESSEE WALTZ PARKWAY ASHLAND CITY, TN 37015

PHONE1-800-365-0024 www.statewaterheaters.com
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
F-891, Schedule 40 CPVC (ASTM F-411), or ABS (ASTM D-2661) pipe. p.12

Ask about the State Industries 100

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the State Industries 100

Be the first to ask — other owners or our team will answer.

Original document

State Industries 100 manual PDF

40 pages·1.1 MB·Water Heater·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…