/ Mar le y Sigma F Ser ies Cooling T ower / Engineer ing Data & Specifications.
Mar ley / Sigma F Ser ies Cooling T ower / T able of Contents Engineer ing Data Sc hematic 4 Support 5 Piping 7 T emperature Control 1 0 Environmental 1 1 Specifications / Base Base 12 Thermal P erfor.
Mar ley / Sigma F Ser ies Cooling T ower / 3 T he Sigma F Series is a field-erected, crossflow , fiberglass-str ucture cooling to wer designed to ser ve normal air conditioning and refrigeration systems as w ell as medium sized industrial loads.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Schematic 4 H B T OP OF F AN CYLINDER BASE OF T OWER COLUMNS F AN DECK 13'-6" N O T E 1 U se this bulletin for preliminary layouts only . Obtain current drawings from y our Marley representative.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Support 5 A SP ACES A T 4'-0" = L W OVERALL OF BASIN SUMP OVERFLOW MAKEUP V AL VE INTERMEDIA TE BEAM AIR INLET F ACE AIR INLET.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Support 6 A SP ACES AT 4'-0" = L 6 " MIN TYP SUMP SEE NOTE 7 OPTIONAL PA RTITION W ALL FOR INDIVIDU AL CELL OPERA TION B .
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Piping Plan 2 7 C MOTOR C F COLUMN AND ANCHOR BOLT TYP. SINGLE CELL D TYP. MULTICELL C L COLUMN AND ANCHOR BOLT C L INLET C L TOWER AND .
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Piping Plan 3 8 C H MO TO R C F COLUMN AND ANCHOR BOL T TY P. SINGLE CELL D TY P. MUL TICELL C L COLUMN AND ANCHOR BOL T C L RISER C L T.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Piping Plan 4 9 C H MO TO R C F COLUMN AND ANCHOR BOL T TY P. SINGLE CELL D TY P. MUL TICELL C L COLUMN AND ANCHOR BOL T C L RISER AND HEADER C L T OWER AND F AN C L FA N C L FA N C L RISER C L H E G F AN FLANGE IS 3 / 4 " THICK.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata: Energ y Management 10 CAUTION The cooling tower must be located at suc h distance and direction to avoid the possibility of contaminated tower disc harge air being drawn into building fresh air intake ducts.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata: Envir onmental 11 Sound Control Sound produced by a Sigma to wer operating in an unobstructed environment will meet all but the most restrictiv e noise limit a- tions—and will react fa vorably to natural at tenuation.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 12 1.0 Base: 1.1 Furnish and inst all an induced-draft, crossflow-type, field-erected, structural fiberglass-framed, P VC film-fill, industrial- duty cooling tower of _____ cell(s), as shown on Plans.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 13 2.0 Ther mal P erfor mance: 2.1 The tow er shall be capable of cooling _____ GPM of water from ____ °F to _____ °F at a design entering air wet- bulb temperature of _____ °F .
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 14 3.0 Constr uction: 3.1 The tow er shall be capable of with- standing water having a pH of 6.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 15 4.0 F an Deck and F an Cylinder: 4.1 The fan dec k shall act as a working platform for maintenance personnel.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 16 5.4 A st ainless steel oil fill and drain line shall extend from the gear reducer to the vicinit y of the motor , and shall be equipped with a bronze-bodied oil lev el sight-glass gauge.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 17 7.0 Hot W ater Distribution Syst em: 7.1 The mechanical equipment support/ crossover pipe for each cell shall be equipped with a flange for the attachment of customer supply piping.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 18 9.0 Access and Saf ety: 9.1 Single cell towers shall include a 33" (838 mm) wide by 61" (1 .55 m) high molded FRP access door in one endwall casing for access to the inte- rior of the tow er .
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 19 11.0 Scope of Wor k : 11.1 The cooling tow er manufact urer shall be responsible for the design, fabrica- tion, and deliver y of materials to the project site, and for the erection of the tower over supports pro vided by others.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 20 Specification V alue Cold W ater Basin Options Stainless Steel Cold W ater Basin : 10.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 21 Specification V alue and a solid state circuit board for tem- perature control and low water cutof f . A control probe shall be located in the basin to monitor water lev el and tem- perature.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 22 Specification V alue Plenum W alkwa y: 9.1 Add the following to the end of this paragraph: Pro vide a 30" (7 62 mm) minimum wide walkwa y extending from one endwall access door to the other through the length of the tow er .
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 23 Specification V alue Air Inlet Screens: 6.3 Add the following paragraph in the Fill, Louver s and Drift Eliminator s section: The air inlet faces of the tow er shall be covered by 1" mesh stainless steel w elded wire screens.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 24 Specification V alue Control Options Control Syst em: 5.7 Add the following paragraphs in the Mechanical Equipment .
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 25 Specification V alue F an Motor V ariable Speed Dr ive: Marle y All W eather ACH550 System 6.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 26 Specification V alue and cooling is no longer required. The fluid cooler manufact urer shall supply VFD st art-up assistance.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 27 Specification V alue ■ Unless specified otherwise, a Robertshaw or Metrix switch will be provided. Double-pole, double-throw models are also avail- able. If purc hased in conjunction with the Control System, it is also factory- wired.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 28 Specification V alue Fiberglass Ladder: 9.3 Change paragraph 9.3 to read as follows: One endwall of the tow er shal.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 29 Specification V alue.
7 4 01 WEST 1 29 STRE ET OVER LAN D P AR K, KANSAS 6 621 3 U N ITE D ST A TES 913 6 64 7 400 spxcooling@ct.spx.com spxcooling.com In the interest of techno logical progr ess, all products are subject to design and/or material change without notice. ©2008 SPX Cooling T ech nologies , Inc.
An important point after buying a device SPX Cooling Technologies FSIG-TS-08A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought SPX Cooling Technologies FSIG-TS-08A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data SPX Cooling Technologies FSIG-TS-08A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, SPX Cooling Technologies FSIG-TS-08A you will learn all the available features of the product, as well as information on its operation. The information that you get SPX Cooling Technologies FSIG-TS-08A will certainly help you make a decision on the purchase.
If you already are a holder of SPX Cooling Technologies FSIG-TS-08A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime SPX Cooling Technologies FSIG-TS-08A.
However, one of the most important roles played by the user manual is to help in solving problems with SPX Cooling Technologies FSIG-TS-08A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device SPX Cooling Technologies FSIG-TS-08A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center