Instruction/ maintenance manual of the product XL-2000 Slant/Fin
Go to page of 15
X X L L - - 2 2 0 0 0 0 0 0 OIL-FIRED W A TER BOILERS/NO . 2 OIL INST ALLA TION AND OPERA TING INSTR UCTIONS SAFETY W ARNING: KEEP BOILER AREA CLEAR AND FREE FROM COM- BUSTIBLE MA TERIALS, GASOLINE AND O THER FLAM- MABLE V APORS AND LIQUIDS.
XL-2000 2 XL-20 0.65 91,000 78 68 8 x8x15 6 x 15 83.56 8 11 / 16 4 9 / 16 6¶ 1 1 / 4 25 3 / 8 XL-30H 0.85 119,000 104 90 8 x8x15 6 x 15 86.00 12 3 / 16 6 5 / 16 61 1 / 4 28 7 / 8 XL-30 1.00 140,000 121 105 8 x8x15 6 x 15 85.04 12 3 / 16 6 5 / 16 6 1 1 / 4 28 7 / 8 1.
T HE INST ALLA TION INSTRUCTIONS IN THIS MANU AL ARE ABBREVIA TED . SEE THE FRONT CO VER OF THIS MANU AL FOR REFERENCES TO CODES AND ST AN- D ARDS. BOILER LOCA TION Provide a le vel, solid f oundation f or the boiler . Location should be near the chimney so that the Flue Pipe Connector or B reeching to the chimney is short and direct.
tion, heavy sooting and health hazards . Any oil-fired boiler must ha ve a steady dr aft* and an ample supply of combustion air at all times during fir ing. If air supply or chimne y draft* is unreliable , CO 2 and ov erfire draft* will change unpredictably .
XL-2000 5 Figure 3a. Appliances located in confined spaces. Air from inside the building. See T able 2 (2.3). Figure 3b. Appliances located in confined spaces. Air from out- doors. See T ab le 2 (2.4). Figure 3c. Appliances located in confined spaces.
XL-2000 6 The opening size recommendation just giv en is for guidance only . It is the installer’ s responsibility to provide air for comb us- t ion and ventilation to all appliances , under all operating con- ditions, f or each installation. See NFP A 31, latest edition for more specific details.
DOMESTIC HO T W A TER F or Indirect-fired storage water heater application, see S lant/Fin publication WH-10, Sizing Guide WH-SG and Installation manual WH-40. The installation manual includes se ver al control systems and relay centers f or space and domestic water heating in addition to plumbing.
smoke and dry soot formation in the fire box. F . If smoke reading is satisf actor y , but CO 2 can not be increased to a satisf actor y lev el (12%) or overfire dr aft of 0 .
6. Use the flue br ush to clean the pinned fluew ays b etween the sections.† A wire brush ma y be used to remov e any carbon accumulation that may ha ve d e veloped in the comb ustion chamber. V acuum the loose soot and debris from the boiler . 7. Inspect the burner combustion head.
XL-2000 10.
BURNER D A T A—CARLIN BURNERS FOR P A CKA GED BOILERS ONL Y XL-2000 11 XL-20 99-FRD 0.65 0.65 70° A DELA V AN 100 0 50 Closed 71399-00F-XL-20 0.65 70° W DELA V AN 100 0 50 Closed XL-30 99-FRD 1.00 1.00 70° A DELA V AN 100 2 80 Closed 71399-00F-XL-30 1.
XL-2000 12 BURNER D A T A—BECKETT BURNERS FOR P A CKA GED BOILERS ONL Y XL-20 (4) AFG F0 0.65 0.65 80° A DELA V AN 100 7 Blank/Closed 3 3 / 8 SF2201 XL-30H AFG F3 0.85 0.85 70° W DELA V AN 100 6 Blank/Closed 2 3 / 4 SF2204 XL-30 AFG F3 1.00 1.00 80° W DELA V AN 100 8 0 2 3 / 4 S F2202 1.
BURNER DA T A - RIELLO BURNERS FOR P A CKA GED BOILERS ONL Y (RIELLO R-40 SERIES W/SHORT TUBE) † Air shutter and head settings shown are appro ximate ONL Y .
XL-2000 14 BURNER DA T A - RIELLO (continued) REGULA TION OF THE TURBULA TOR AND AIR SHUTTER F OR PROPER COMB USTION T urbulator Setting 1. Loosen n ut, 1, then turn the screw , 2, until the index marker , 3, is aligned with the correct inde x number .
SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE, Mississauga, Ontar io www .
An important point after buying a device Slant/Fin XL-2000 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Slant/Fin XL-2000 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Slant/Fin XL-2000 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Slant/Fin XL-2000 you will learn all the available features of the product, as well as information on its operation. The information that you get Slant/Fin XL-2000 will certainly help you make a decision on the purchase.
If you already are a holder of Slant/Fin XL-2000, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Slant/Fin XL-2000.
However, one of the most important roles played by the user manual is to help in solving problems with Slant/Fin XL-2000. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Slant/Fin XL-2000 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center