Instruction/ maintenance manual of the product V-180 Slant/Fin
Go to page of 20
HO T W A TER MODELS V -33 THR OUGH V -180 INST ALLA TION AND OPERA TING INSTR UCTIONS GAS-FIRED CAST -IR ON BOILERS FOR NA TURAL AND L.P . PR OP ANE GASES CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P A GE Ratings and Dimensions .
2 V ICTOR Y Dimensions (inches) Figure 1. Left End View Figure 2. Front View Figure 3. Right End View NO TE: Height Dimension increases to 30-3/16" and depth dimension increases to 22-1/4" when combustib le floor kit is used.
V ICTOR Y 3 I NST ALLA TION REQUIREMENTS The installation must conf or m to the requirements of the a uthority having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code , ANSI Z223.1- l atest edition. This installation must also conf or m to the additional require- ments in this Slant/Fin instruction book.
4 V ICTOR Y Reference T able No. * Appliance Connector Requirements* (ANSI Z223.1) Victor y Boilers T ype “B” See table 11-1 f or minimum and maximum of v ent 11-1 (V -90, V -120, V -150 and V -180) height and lateral length restriction.
V ICTOR Y 5 HORIZONT AL PRESSURE VENTING All VICT OR Y models are cer tified for horizontal pressure venting with the f ollowing restrictions: 1. V ent Material A . The vent system f or horizontal venting m ust be UL list- ed single wall Saf-T 3" diameter #AL 29-4C s stainless steel manuf actured by Heat-F ab, Inc.
Model/V ent Siz e V -90, V -120, V -150 and V -180 boilers ma y be vented into a chimney (see “Chimney and type “B” v enting” paragraph on page 4) or into a type “B” v ent, ONL Y when converted to the 5" dia.
V ICTOR Y 7 Figure 6b. V enting with “B” vent or metal-lined chimney for V -90, V -120, V -150 and V -180 only Minim um vent connector s diameter is 5 inches.
8 V I CTOR Y Figure 7. Horizontal V enting (3 IN.): All Victor y Models All items shown belo w are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT . Use only 3" dia. Saf-T vent (#AL 29-4C* stainless steel) venting materials by Heat-F ab Inc.
V I CTOR Y 9 Figure 8. Horizontal V enting (3 IN.): All Victor y Models All items shown belo w are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT . Use only 3" dia. Saf-T vent (#AL 29-4C* stainless steel) venting materials by Heat-F ab Inc.
1 0 V ICTOR Y Figure 9. V ertical V enting (3 IN.): All Victory Models All items shown belo w are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT . Use only 3" dia. Saf-T vent (#AL 29-4C* stainless steel) venting materials by Heat-F ab Inc.
V ICTOR Y 1 1 at test pressures equal to or less than 1/2 PSIG. D . All gas piping used should be inspected thoroughly f or cleanliness bef ore makeup .
1 2 V ICTOR Y B . PUMP LOCA TION-Locating low-head pump(s) on return to boiler is acceptable for smaller boiler siz es in residences of one or two stories. The alter nate pump location shown in illustration on page 11 is required in l arge, multi-story building installations, especially when high-head pumps are used.
V ICTOR Y 1 3 8. T urn on all electr ic power to the appliance . 9. Set ther mostat to desired setting. 10. If the appliance will not operate, f ollow the instructions "T o T ur n Off Gas T o Appliance" and call your service technician or gas supplier .
1 4 V ICTOR Y 2. Safety Shutdown Chec kout a. For proper operation the pilot should engulf the thermocouple, powerpile generator or flame sen- sor as shown belo w .
V ICTOR Y 1 5 burners as described on page 13. * T o clean burners run a clean flue brush up the tube until all f oreign matter is removed. IV . SAFETY CHECK FOR CONTR OL SYSTEM 1. Remove Control Co ver T o remov e control cov er , remov e the two sheet metal screws in the top of the top co ver .
1 6 V ICTOR Y A PPENDIX A Remov al Of Existing Boiler From Common V ent System "At the time of remov al of an existing boiler , the follo wing s teps shall be f ollowed with each appliance remain.
V ICTOR Y 1 7 Sequence of Operations Wiring Diagrams CA UTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. “V er ify proper oper ation after ser vicing. ” THERMOST A T CALLS FOR H EA T C IRCULA TOR CONTINUES TO RUN.
1 8 V I CTOR Y PUMP OR V AL VE ZONING OF W A TER BOILERS COMBINA TION CONTROLS WITH T TV Z TERMINALS* Pump Zoning system using R845 Rela y . One R-845A needed f or each circulator . NO TE: Pumps are powered from C1. T otal pump load must not e xceed 7.
V ICTOR Y 1 9 B URNERS F AIL T O OPERA TE C A USE 1. Safety pilot out, or flame too lo w . 2. Gas supply valv e shut off . 3. Electric switch open. 4. Blown or def ective line fuse . 5. Operating or limit control contacts open or dir ty . 6. Defectiv e gas v alve or pressure regulator; or plugged bleed l ine.
20 V I CTOR Y PIPING A HEA TING - COOLING SYSTEM T O A W A TER BOILER AND CHILLER Figure below illustrates a method of piping a heating-cooling system to a water boiler and a chiller . Hand valves (sho wn) or automatic valv es must be installed to prev ent circulation of c hilled water in the boiler or hot w ater in the chiller .
An important point after buying a device Slant/Fin V-180 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Slant/Fin V-180 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Slant/Fin V-180 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Slant/Fin V-180 you will learn all the available features of the product, as well as information on its operation. The information that you get Slant/Fin V-180 will certainly help you make a decision on the purchase.
If you already are a holder of Slant/Fin V-180, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Slant/Fin V-180.
However, one of the most important roles played by the user manual is to help in solving problems with Slant/Fin V-180. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Slant/Fin V-180 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center