EN
Siemens logo
Official user manual

Siemens Sitrans

122 pages·3.4 MB·Treadmill·PDF·ENDEFRITNLJA
Siemens Sitrans
Table of Contents 182 sections SITRANS LC 500 · Applications · Safety Notes · Safety marking symbols · … ShowHide
SITRANS LC 500p.7Applicationsp.7Safety Notesp.8Safety marking symbolsp.8The Manualp.8Abbreviations and Identificationsp.9Technical Specifications: SITRANS LC 500p.10Powerp.10Environmentalp.10Performancep.10Outputsp.11User Interfacep.11Communicationsp.11Electrodesp.12Wetted Partsp.12Enclosure (electronic)p.12Weightp.12Process Conditionsp.13Approvalsp.13SITRANS LC 500: Transmitterp.14Operating Principlesp.14The SITRANS LC 500 variable frequency oscillatorp.14Capacitance measurement in a cylindrical metal tankp.14The SITRANS LC 500 electrodep.16Application: SITRANS LC 500p.18Level Measurementp.19Interface Measurementp.20Switch actionp.20Fault Signallingp.21SITRANS LC 500: Probe Configurationp.22SITRANS LC 500 Electrode (Probe) Characteristicsp.22Electrode Assemblyp.23Process Connectionsp.23Seal Typesp.23Process Connection and Seal Configuration of SITRANS LC 500p.23Pressure and Temperature Considerationsp.24Non-standard applicationsp.25SITRANS LC 500: Installationp.26Handling Electrodesp.26Mounting Instructionsp.27Protection for solid-state switchp.27Process Cautionsp.27SITRANS LC 500: Standard Level Versionp.28Interconnection: SITRANS LC 500p.29Wiringp.29Supplyp.29Cablep.30Selecting the correct instrumentation cablep.30Terminalsp.32Connecting SITRANS LC 500p.32Connection Diagramp.32Protection for solid-state switchp.33Grounding instructionsp.33Grounding Examples: SITRANS LC 500p.34System Grounding (referencing)p.34Metal Tanksp.34Cathodically Protected Metal Tanksp.35Non-Conductive Tanksp.35Safety Groundingp.36Example 1p.36Example 2p.36Example 3p.37Example 4p.37Communicationsp.38Typical PLC configuration with HARTp.38Diagnosticsp.38Applications for Solid-state Outputp.39Switch Protection (Diode)p.40Factory Settingsp.40Settings:p.40The SITRANS LC 500 User Interfacep.42The LCD (display)p.42How to access the data:p.43Menu Levels 00 to 0F and 10 to 1Fp.43The rotary switchp.44The push-buttonsp.44Access to a menu item:p.44Adjusting the valuep.44Transmitter Variablesp.45Start-up: SITRANS LC 500p.46Quick Startp.46Menu levels 0 and 1p.48Start up using push-button calibration: (overview)p.48Calibration using push-button adjustmentp.49Calibration using HARTp.52Maintenancep.56Test functionp.56Inspectionsp.56Troubleshooting: SITRANS LC 500p.58Error Messages and Error Codesp.59Error Messages (push-button operation)p.59Error Codes (HART)p.59Appendix A: Menu Groupsp.60Menu Itemsp.61Appendix B: LCD display examplesp.80LCD: alphanumeric display examplesp.80M 00p.80SEL 1p.80FLtp.80S: ocp.80S: oop.80S= ocp.80S: – –p.80F: oop.80F: ocp.80F: – –p.80Hip.80Lop.80Anp.80norp.80invp.80ooLp.80FAC Ap.80FAC Pp.80FAC?p.80do itp.800 = /op.80Pv=0p.80PL 0p.80SIMp.80Appendix C: HART Documentationp.81HART Communications for the SITRANS LC 500p.81HART Device Descriptor (DD)p.81Simatic Process Device Manager (PDM)p.81HART informationp.81Expanded Device Type Code:p.81Physical Layer Informationp.81SITRANS LC 500 DD Menu/Variable Organizationp.82HART Response Code Informationp.83Bit #7: Field Device Malfunctionp.83Bit #6: Configuration Changedp.83Bit #5: Cold Startp.83Bit #4: Extended Status Availablep.83Bit #3: Output Current Fixedp.83Bit #2: Primary Variable Analog Output Saturatedp.83Bit #0: Primary Variable Out of Limitsp.83HART Conformance and Command Classp.84General Transmitter Informationp.85Damping informationp.85Non-volatile Memory Data Storagep.85MultiDrop operationp.86Burst modep.86Units conversionsp.86Additional Universal Command Specificationsp.86Appendix D: Block Diagram, and Correlation table, mA to %p.87Correlation Table: 0% - 100% to 4-20 mA or 20-4 mAp.88Appendix E: SITRANS LC 500, alternate versions and application detailsp.89Standard Versionp.89Standard Version S-Series, Threadedp.89S-Series: Threadedp.89Standard Version S-Series, Threadedp.90S-Series Cable Versionp.90(with weight)p.90Standard Version S-Series, Welded and Machined Flanged Versionsp.91S-Series, Welded Flangep.91Standard Version D-Series, Machined Flangep.92D-Seriesp.92SD-Seriesp.93Interface Versionp.94Interface Version, threaded (optional sanitary and flanged)p.94Sanitary Versionp.95Sanitary Versions, threaded and tri-clampp.95Sanitary Thread Couplingp.95Flangesp.96Flange Standardsp.96Applications Examplesp.97Generic Application Calculationsp.97Examples (using dimensions above):p.97Application: level indicator and solid-state switch outputp.99Application: Analog fault signalling (2-state output)p.100Appendix F: Approvalsp.102CE Certificatep.102Instrument label: SITRANS LC 500p.104KEMA certificate and schedulesp.105Certificates and Approvalsp.113NAMUR recommendation NE 43p.113Control Drawing FM/CSA Approvalp.114SITRANS LC 500p.114Glossaryp.115Indexp.117Quick Reference: SITRANS LC 500p.119Quick Startp.119
Page 1 of the Siemens Sitrans user manual — LC 500 sitrans
Page 1 · click to enlarge
Page 1

Instruction Manual January 2003

Siemens Sitrans — Instruction Manual January 2003 diagram (page 1)
Fig. 1 · Instruction Manual January 2003

LC 500 sitrans

Page 2 of the Siemens Sitrans user manual
Page 2 · click to enlarge
Page 2

This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.

Copyright Siemens Milltronics ProcessDisclaimer of Liability Instruments Inc. 2003. All Rights Reserved This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement. Technical data subject to change.

MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.

Contact SMPI Technical Publications at the following address:

Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs@siemens-milltronics.com

For the library of SMPI instruction manuals, visit our Web site: www.siemens-milltronics.com

© Siemens Milltronics Process Instruments Inc. 2003

Safety Guidelines · Qualified Personnel

Page 3 of the Siemens Sitrans user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

SITRANS LC 500p.7Applicationsp.7Safety Notesp.8Safety marking symbolsp.8The Manualp.8Abbreviations and Identificationsp.9Technical Specifications: SITRANS LC 500p.10Powerp.10Environmentalp.10Performancep.10Outputsp.11User Interfacep.11Communicationsp.11Electrodesp.12Wetted Partsp.12Enclosure (electronic)p.12Weightp.12Process Conditionsp.13Approvalsp.13SITRANS LC 500: Transmitterp.14Operating Principlesp.14The SITRANS LC 500 variable frequency oscillatorp.14Capacitance measurement in a cylindrical metal tankp.14The SITRANS LC 500 electrodep.16Application: SITRANS LC 500p.18Level Measurementp.19Interface Measurementp.20Switch actionp.20Fault Signallingp.21SITRANS LC 500: Probe Configurationp.22SITRANS LC 500 Electrode (Probe) Characteristicsp.22Electrode Assemblyp.23Process Connectionsp.23Seal Typesp.23Process Connection and Seal Configuration of SITRANS LC 500p.23Pressure and Temperature Considerationsp.24Non-standard applicationsp.25SITRANS LC 500: Installationp.26Handling Electrodesp.26Mounting Instructionsp.27Protection for solid-state switchp.27Process Cautionsp.27SITRANS LC 500: Standard Level Versionp.28Interconnection: SITRANS LC 500p.29Wiringp.29Supplyp.29Cablep.30Selecting the correct instrumentation cablep.30Terminalsp.32Connecting SITRANS LC 500p.32Connection Diagramp.32Protection for solid-state switchp.33Grounding instructionsp.33Grounding Examples: SITRANS LC 500p.34System Grounding (referencing)p.34Metal Tanksp.34Cathodically Protected Metal Tanksp.35Non-Conductive Tanksp.35Safety Groundingp.36Example 1p.36Example 2p.36Example 3p.37Example 4p.37Communicationsp.38Typical PLC configuration with HARTp.38Diagnosticsp.38Applications for Solid-state Outputp.39Switch Protection (Diode)p.40Factory Settingsp.40Settings:p.40The SITRANS LC 500 User Interfacep.42The LCD (display)p.42How to access the data:p.43Menu Levels 00 to 0F and 10 to 1Fp.43The rotary switchp.44The push-buttonsp.44Access to a menu item:p.44Adjusting the valuep.44Transmitter Variablesp.45Start-up: SITRANS LC 500p.46Quick Startp.46Menu levels 0 and 1p.48Start up using push-button calibration: (overview)p.48Calibration using push-button adjustmentp.49Calibration using HARTp.52Maintenancep.56Test functionp.56Inspectionsp.56Troubleshooting: SITRANS LC 500p.58Error Messages and Error Codesp.59Error Messages (push-button operation)p.59Error Codes (HART)p.59Appendix A: Menu Groupsp.60Menu Itemsp.61Appendix B: LCD display examplesp.80LCD: alphanumeric display examplesp.80M 00p.80SEL 1p.80FLtp.80S: ocp.80S: oop.80S= ocp.80S: – –p.80F: oop.80F: ocp.80F: – –p.80Hip.80Lop.80Anp.80norp.80invp.80ooLp.80FAC Ap.80FAC Pp.80FAC?p.80do itp.800 = /op.80Pv=0p.80PL 0p.80SIMp.80Appendix C: HART Documentationp.81HART Communications for the SITRANS LC 500p.81HART Device Descriptor (DD)p.81Simatic Process Device Manager (PDM)p.81HART informationp.81Expanded Device Type Code:p.81Physical Layer Informationp.81SITRANS LC 500 DD Menu/Variable Organizationp.82HART Response Code Informationp.83Bit #7: Field Device Malfunctionp.83Bit #6: Configuration Changedp.83Bit #5: Cold Startp.83Bit #4: Extended Status Availablep.83Bit #3: Output Current Fixedp.83Bit #2: Primary Variable Analog Output Saturatedp.83Bit #0: Primary Variable Out of Limitsp.83HART Conformance and Command Classp.84General Transmitter Informationp.85Damping informationp.85Non-volatile Memory Data Storagep.85MultiDrop operationp.86Burst modep.86Units conversionsp.86Additional Universal Command Specificationsp.86Appendix D: Block Diagram, and Correlation table, mA to %p.87Correlation Table: 0% - 100% to 4-20 mA or 20-4 mAp.88Appendix E: SITRANS LC 500, alternate versions and application detailsp.89Standard Versionp.89Standard Version S-Series, Threadedp.89S-Series: Threadedp.89Standard Version S-Series, Threadedp.90S-Series Cable Versionp.90(with weight)p.90Standard Version S-Series, Welded and Machined Flanged Versionsp.91S-Series, Welded Flangep.91Standard Version D-Series, Machined Flangep.92D-Seriesp.92SD-Seriesp.93Interface Versionp.94Interface Version, threaded (optional sanitary and flanged)p.94Sanitary Versionp.95Sanitary Versions, threaded and tri-clampp.95Sanitary Thread Couplingp.95Flangesp.96Flange Standardsp.96Applications Examplesp.97Generic Application Calculationsp.97Examples (using dimensions above):p.97Application: level indicator and solid-state switch outputp.99Application: Analog fault signalling (2-state output)p.100Appendix F: Approvalsp.102CE Certificatep.102CE Certificatep.103Instrument label: SITRANS LC 500p.104KEMA certificate and schedulesp.105Certificates and Approvalsp.113NAMUR recommendation NE 43p.113Control Drawing FM/CSA Approvalp.114SITRANS LC 500p.114Glossaryp.115Indexp.117Quick Reference: SITRANS LC 500p.119Quick Startp.119
Page 4 of the Siemens Sitrans user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

SITRANS LC 500p.7Applicationsp.7Safety Notesp.8Safety marking symbolsp.8The Manualp.8Abbreviations and Identificationsp.9Technical Specifications: SITRANS LC 500p.10Powerp.10Environmentalp.10Performancep.10Outputsp.11User Interfacep.11Communicationsp.11Electrodesp.12Wetted Partsp.12Enclosure (electronic)p.12Weightp.12Process Conditionsp.13Approvalsp.13SITRANS LC 500: Transmitterp.14Operating Principlesp.14The SITRANS LC 500 variable frequency oscillatorp.14Capacitance measurement in a cylindrical metal tankp.14The SITRANS LC 500 electrodep.16Application: SITRANS LC 500p.18Level Measurementp.19Interface Measurementp.20Switch actionp.20Fault Signallingp.21SITRANS LC 500: Probe Configurationp.22SITRANS LC 500 Electrode (Probe) Characteristicsp.22Electrode Assemblyp.23Process Connectionsp.23Seal Typesp.23Process Connection and Seal Configuration of SITRANS LC 500p.23Pressure and Temperature Considerationsp.24Non-standard applicationsp.25SITRANS LC 500: Installationp.26Handling Electrodesp.26Mounting Instructionsp.27Protection for solid-state switchp.27Process Cautionsp.27SITRANS LC 500: Standard Level Versionp.28Interconnection: SITRANS LC 500p.29Wiringp.29Supplyp.29Cablep.30Selecting the correct instrumentation cablep.30Terminalsp.32Connecting SITRANS LC 500p.32Connection Diagramp.32Protection for solid-state switchp.33Grounding instructionsp.33Grounding Examples: SITRANS LC 500p.34System Grounding (referencing)p.34Metal Tanksp.34Cathodically Protected Metal Tanksp.35Non-Conductive Tanksp.35Safety Groundingp.36Example 1p.36Example 2p.36Example 3p.37Example 4p.37Communicationsp.38Typical PLC configuration with HARTp.38Diagnosticsp.38Applications for Solid-state Outputp.39Switch Protection (Diode)p.40Factory Settingsp.40Settings:p.40The SITRANS LC 500 User Interfacep.42The LCD (display)p.42How to access the data:p.43Menu Levels 00 to 0F and 10 to 1Fp.43The rotary switchp.44The push-buttonsp.44Access to a menu item:p.44Adjusting the valuep.44Transmitter Variablesp.45Start-up: SITRANS LC 500p.46Quick Startp.46Menu levels 0 and 1p.48Start up using push-button calibration: (overview)p.48Calibration using push-button adjustmentp.49Calibration using HARTp.52Maintenancep.56Test functionp.56Inspectionsp.56Troubleshooting: SITRANS LC 500p.58Error Messages and Error Codesp.59Error Messages (push-button operation)p.59Error Codes (HART)p.59Appendix A: Menu Groupsp.60Menu Itemsp.61Appendix B: LCD display examplesp.80LCD: alphanumeric display examplesp.80M 00p.80SEL 1p.80FLtp.80S: ocp.80S: oop.80S= ocp.80S: – –p.80F: oop.80F: ocp.80F: – –p.80Hip.80Lop.80Anp.80norp.80invp.80ooLp.80FAC Ap.80FAC Pp.80FAC?p.80do itp.800 = /op.80Pv=0p.80PL 0p.80SIMp.80Appendix C: HART Documentationp.81HART Communications for the SITRANS LC 500p.81HART Device Descriptor (DD)p.81Simatic Process Device Manager (PDM)p.81HART informationp.81Expanded Device Type Code:p.81Physical Layer Informationp.81SITRANS LC 500 DD Menu/Variable Organizationp.82HART Response Code Informationp.83Bit #7: Field Device Malfunctionp.83Bit #6: Configuration Changedp.83Bit #5: Cold Startp.83Bit #4: Extended Status Availablep.83Bit #3: Output Current Fixedp.83Bit #2: Primary Variable Analog Output Saturatedp.83Bit #0: Primary Variable Out of Limitsp.83HART Conformance and Command Classp.84General Transmitter Informationp.85Damping informationp.85Non-volatile Memory Data Storagep.85MultiDrop operationp.86Burst modep.86Units conversionsp.86Additional Universal Command Specificationsp.86Appendix D: Block Diagram, and Correlation table, mA to %p.87Correlation Table: 0% - 100% to 4-20 mA or 20-4 mAp.88Appendix E: SITRANS LC 500, alternate versions and application detailsp.89Standard Versionp.89Standard Version S-Series, Threadedp.89S-Series: Threadedp.89Standard Version S-Series, Threadedp.90S-Series Cable Versionp.90(with weight)p.90Standard Version S-Series, Welded and Machined Flanged Versionsp.91S-Series, Welded Flangep.91Standard Version D-Series, Machined Flangep.92D-Seriesp.92SD-Seriesp.93Interface Versionp.94Interface Version, threaded (optional sanitary and flanged)p.94Sanitary Versionp.95Sanitary Versions, threaded and tri-clampp.95Sanitary Thread Couplingp.95Flangesp.96Flange Standardsp.96Applications Examplesp.97Generic Application Calculationsp.97Examples (using dimensions above):p.97Application: level indicator and solid-state switch outputp.99Application: Analog fault signalling (2-state output)p.100Appendix F: Approvalsp.102CE Certificatep.102CE Certificatep.103Instrument label: SITRANS LC 500p.104KEMA certificate and schedulesp.105Certificates and Approvalsp.113NAMUR recommendation NE 43p.113Control Drawing FM/CSA Approvalp.114SITRANS LC 500p.114Glossaryp.115Indexp.117Quick Reference: SITRANS LC 500p.119Quick Startp.119
Page 5 of the Siemens Sitrans user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

SITRANS LC 500p.7Applicationsp.7Safety Notesp.8Safety marking symbolsp.8The Manualp.8Abbreviations and Identificationsp.9Technical Specifications: SITRANS LC 500p.10Powerp.10Environmentalp.10Performancep.10Outputsp.11User Interfacep.11Communicationsp.11Electrodesp.12Wetted Partsp.12Enclosure (electronic)p.12Weightp.12Process Conditionsp.13Approvalsp.13SITRANS LC 500: Transmitterp.14Operating Principlesp.14The SITRANS LC 500 variable frequency oscillatorp.14Capacitance measurement in a cylindrical metal tankp.14The SITRANS LC 500 electrodep.16Application: SITRANS LC 500p.18Level Measurementp.19Interface Measurementp.20Switch actionp.20Fault Signallingp.21SITRANS LC 500: Probe Configurationp.22SITRANS LC 500 Electrode (Probe) Characteristicsp.22Electrode Assemblyp.23Process Connectionsp.23Seal Typesp.23Process Connection and Seal Configuration of SITRANS LC 500p.23Pressure and Temperature Considerationsp.24Non-standard applicationsp.25SITRANS LC 500: Installationp.26Handling Electrodesp.26Mounting Instructionsp.27Protection for solid-state switchp.27Process Cautionsp.27SITRANS LC 500: Standard Level Versionp.28Interconnection: SITRANS LC 500p.29Wiringp.29Supplyp.29Cablep.30Selecting the correct instrumentation cablep.30Terminalsp.32Connecting SITRANS LC 500p.32Connection Diagramp.32Protection for solid-state switchp.33Grounding instructionsp.33Grounding Examples: SITRANS LC 500p.34System Grounding (referencing)p.34Metal Tanksp.34Cathodically Protected Metal Tanksp.35Non-Conductive Tanksp.35Safety Groundingp.36Example 1p.36Example 2p.36Example 3p.37Example 4p.37Communicationsp.38Typical PLC configuration with HARTp.38Diagnosticsp.38Applications for Solid-state Outputp.39Switch Protection (Diode)p.40Factory Settingsp.40Settings:p.40The SITRANS LC 500 User Interfacep.42The LCD (display)p.42How to access the data:p.43Menu Levels 00 to 0F and 10 to 1Fp.43The rotary switchp.44The push-buttonsp.44Access to a menu item:p.44Adjusting the valuep.44Transmitter Variablesp.45Start-up: SITRANS LC 500p.46Quick Startp.46Menu levels 0 and 1p.48Start up using push-button calibration: (overview)p.48Calibration using push-button adjustmentp.49Calibration using HARTp.52Maintenancep.56Test functionp.56Inspectionsp.56Troubleshooting: SITRANS LC 500p.58Error Messages and Error Codesp.59Error Messages (push-button operation)p.59Error Codes (HART)p.59Appendix A: Menu Groupsp.60Menu Itemsp.61Appendix B: LCD display examplesp.80LCD: alphanumeric display examplesp.80M 00p.80SEL 1p.80FLtp.80S: ocp.80S: oop.80S= ocp.80S: – –p.80F: oop.80F: ocp.80F: – –p.80Hip.80Lop.80Anp.80norp.80invp.80ooLp.80FAC Ap.80FAC Pp.80FAC?p.80do itp.800 = /op.80Pv=0p.80PL 0p.80SIMp.80Appendix C: HART Documentationp.81HART Communications for the SITRANS LC 500p.81HART Device Descriptor (DD)p.81Simatic Process Device Manager (PDM)p.81HART informationp.81Expanded Device Type Code:p.81Physical Layer Informationp.81SITRANS LC 500 DD Menu/Variable Organizationp.82HART Response Code Informationp.83Bit #7: Field Device Malfunctionp.83Bit #6: Configuration Changedp.83Bit #5: Cold Startp.83Bit #4: Extended Status Availablep.83Bit #3: Output Current Fixedp.83Bit #2: Primary Variable Analog Output Saturatedp.83Bit #0: Primary Variable Out of Limitsp.83HART Conformance and Command Classp.84General Transmitter Informationp.85Damping informationp.85Non-volatile Memory Data Storagep.85MultiDrop operationp.86Burst modep.86Units conversionsp.86Additional Universal Command Specificationsp.86Appendix D: Block Diagram, and Correlation table, mA to %p.87Correlation Table: 0% - 100% to 4-20 mA or 20-4 mAp.88Appendix E: SITRANS LC 500, alternate versions and application detailsp.89Standard Versionp.89Standard Version S-Series, Threadedp.89S-Series: Threadedp.89Standard Version S-Series, Threadedp.90S-Series Cable Versionp.90(with weight)p.90Standard Version S-Series, Welded and Machined Flanged Versionsp.91S-Series, Welded Flangep.91Standard Version D-Series, Machined Flangep.92D-Seriesp.92SD-Seriesp.93Interface Versionp.94Interface Version, threaded (optional sanitary and flanged)p.94Sanitary Versionp.95Sanitary Versions, threaded and tri-clampp.95Sanitary Thread Couplingp.95Flangesp.96Flange Standardsp.96Applications Examplesp.97Generic Application Calculationsp.97Examples (using dimensions above):p.97Application: level indicator and solid-state switch outputp.99Application: Analog fault signalling (2-state output)p.100Appendix F: Approvalsp.102CE Certificatep.102CE Certificatep.103Instrument label: SITRANS LC 500p.104KEMA certificate and schedulesp.105Certificates and Approvalsp.113NAMUR recommendation NE 43p.113Control Drawing FM/CSA Approvalp.114SITRANS LC 500p.114Glossaryp.115Indexp.117Quick Reference: SITRANS LC 500p.119Quick Startp.119
Page 6 of the Siemens Sitrans user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

SITRANS LC 500p.7Applicationsp.7Safety Notesp.8Safety marking symbolsp.8The Manualp.8Abbreviations and Identificationsp.9Technical Specifications: SITRANS LC 500p.10Powerp.10Environmentalp.10Performancep.10Outputsp.11User Interfacep.11Communicationsp.11Electrodesp.12Wetted Partsp.12Enclosure (electronic)p.12Weightp.12Process Conditionsp.13Approvalsp.13SITRANS LC 500: Transmitterp.14Operating Principlesp.14The SITRANS LC 500 variable frequency oscillatorp.14Capacitance measurement in a cylindrical metal tankp.14The SITRANS LC 500 electrodep.16Application: SITRANS LC 500p.18Level Measurementp.19Interface Measurementp.20Switch actionp.20Fault Signallingp.21SITRANS LC 500: Probe Configurationp.22SITRANS LC 500 Electrode (Probe) Characteristicsp.22Electrode Assemblyp.23Process Connectionsp.23Seal Typesp.23Process Connection and Seal Configuration of SITRANS LC 500p.23Pressure and Temperature Considerationsp.24Non-standard applicationsp.25SITRANS LC 500: Installationp.26Handling Electrodesp.26Mounting Instructionsp.27Protection for solid-state switchp.27Process Cautionsp.27SITRANS LC 500: Standard Level Versionp.28Interconnection: SITRANS LC 500p.29Wiringp.29Supplyp.29Cablep.30Selecting the correct instrumentation cablep.30Terminalsp.32Connecting SITRANS LC 500p.32Connection Diagramp.32Protection for solid-state switchp.33Grounding instructionsp.33Grounding Examples: SITRANS LC 500p.34System Grounding (referencing)p.34Metal Tanksp.34Cathodically Protected Metal Tanksp.35Non-Conductive Tanksp.35Safety Groundingp.36Example 1p.36Example 2p.36Example 3p.37Example 4p.37Communicationsp.38Typical PLC configuration with HARTp.38Diagnosticsp.38Applications for Solid-state Outputp.39Switch Protection (Diode)p.40Factory Settingsp.40Settings:p.40The SITRANS LC 500 User Interfacep.42The LCD (display)p.42How to access the data:p.43Menu Levels 00 to 0F and 10 to 1Fp.43The rotary switchp.44The push-buttonsp.44Access to a menu item:p.44Adjusting the valuep.44Transmitter Variablesp.45Start-up: SITRANS LC 500p.46Quick Startp.46Menu levels 0 and 1p.48Start up using push-button calibration: (overview)p.48Calibration using push-button adjustmentp.49Calibration using HARTp.52Maintenancep.56Test functionp.56Inspectionsp.56Troubleshooting: SITRANS LC 500p.58Error Messages and Error Codesp.59Error Messages (push-button operation)p.59Error Codes (HART)p.59Appendix A: Menu Groupsp.60Menu Itemsp.61Appendix B: LCD display examplesp.80LCD: alphanumeric display examplesp.80M 00p.80SEL 1p.80FLtp.80S: ocp.80S: oop.80S= ocp.80S: – –p.80F: oop.80F: ocp.80F: – –p.80Hip.80Lop.80Anp.80norp.80invp.80ooLp.80FAC Ap.80FAC Pp.80FAC?p.80do itp.800 = /op.80Pv=0p.80PL 0p.80SIMp.80Appendix C: HART Documentationp.81HART Communications for the SITRANS LC 500p.81HART Device Descriptor (DD)p.81Simatic Process Device Manager (PDM)p.81HART informationp.81Expanded Device Type Code:p.81Physical Layer Informationp.81SITRANS LC 500 DD Menu/Variable Organizationp.82HART Response Code Informationp.83Bit #7: Field Device Malfunctionp.83Bit #6: Configuration Changedp.83Bit #5: Cold Startp.83Bit #4: Extended Status Availablep.83Bit #3: Output Current Fixedp.83Bit #2: Primary Variable Analog Output Saturatedp.83Bit #0: Primary Variable Out of Limitsp.83HART Conformance and Command Classp.84General Transmitter Informationp.85Damping informationp.85Non-volatile Memory Data Storagep.85MultiDrop operationp.86Burst modep.86Units conversionsp.86Additional Universal Command Specificationsp.86Appendix D: Block Diagram, and Correlation table, mA to %p.87Correlation Table: 0% - 100% to 4-20 mA or 20-4 mAp.88Appendix E: SITRANS LC 500, alternate versions and application detailsp.89Standard Versionp.89Standard Version S-Series, Threadedp.89S-Series: Threadedp.89Standard Version S-Series, Threadedp.90S-Series Cable Versionp.90(with weight)p.90Standard Version S-Series, Welded and Machined Flanged Versionsp.91S-Series, Welded Flangep.91Standard Version D-Series, Machined Flangep.92D-Seriesp.92SD-Seriesp.93Interface Versionp.94Interface Version, threaded (optional sanitary and flanged)p.94Sanitary Versionp.95Sanitary Versions, threaded and tri-clampp.95Sanitary Thread Couplingp.95Flangesp.96Flange Standardsp.96Applications Examplesp.97Generic Application Calculationsp.97Examples (using dimensions above):p.97Application: level indicator and solid-state switch outputp.99Application: Analog fault signalling (2-state output)p.100Appendix F: Approvalsp.102CE Certificatep.102CE Certificatep.103Instrument label: SITRANS LC 500p.104KEMA certificate and schedulesp.105Certificates and Approvalsp.113NAMUR recommendation NE 43p.113Control Drawing FM/CSA Approvalp.114SITRANS LC 500p.114Glossaryp.115Indexp.117Quick Reference: SITRANS LC 500p.119Quick Startp.119
Page 7 of the Siemens Sitrans user manual — Applications
Page 7 · click to enlarge
Page 7

SITRANS LC 500

Introduction

SITRANS LC 500 is a high performance 2-wire capacitance instrument for continuous level and interface measurement in extreme or critical conditions. It uses a unique frequency- based measurement system and patented Active-Shield technology to deliver highly accurate, repeatable results. The measurement is unaffected by moisture, vapors, foam, temperature and pressure variations, or material build-up around the mounting glands.

SITRANS LC 500 combines a sophisticated, easy-to-adjust transmitter (MSP-2002-2) with a measurement electrode and process seal selected from a range of options1, to suit a wide variety of applications. The advanced electronics and integrated local display provide for one-step calibration without interrupting the process, and the probe shield design eliminates the need for frequent recalibration.

SITRANS LC 500 can be used as a level controller, by connecting the mA output and/or the solid-state switch to a relay, and activating a pump via an auxiliary power circuit.

The SITRANS LC 500 is equipped with:

  • Smart 2-wire transmitter
  • Remote adjustable commissioning / control capabilities via HART 2
  • Analog (2-wire) 4 to 20mA / 20 to 4 mA output
  • Solid-state and Current detection (4 or 20 mA / 20 or 4 mA, two-state functionality)
  • Adjustable hystereses on/off for solid-state output and for current signal
  • Damping functionality
  • Signal current (measurement/detection) according to NAMUR NE 43
  • Integrated local display for commissioning and services activities
  • Full range of local/remote diagnostic facilities
  • Pre-detection of trip point for high safety requirements
  • Polarity-insensitive current loop
  • Integrated zener safety barrier for Intrinsically Safe applications

Applications

  • General Purpose, Dust Ignition Proof, Explosion Proof, and Intrinsically Safe
  • A wide range of applications in high pressure and temperature, chemically aggressive, and other extreme measurement/detection environments
  • Liquids, Solids, Quality, and Interface measurement
  • Viscous non-conducting and conducting liquids
1. Customized probe configurations can also be provided. 2. HART® is a registered trademark of the HART Communications Foundation, Austin, Texas, USA.
Page 8 of the Siemens Sitrans user manual — The Manual
Page 8 · click to enlarge
Page 8

Safety Notes

Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes.

Introduction

Safety marking symbols

Alternating Current Direct Current Earth (ground) Terminal Protective Conductor Terminal Frame or Chassis Terminal Cathodic protection resulting in a potential difference: for example, between the ground on the instrument and the potential of the vessel or tank

The Manual

  • Notes:
  • Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your SITRANS LC 500.
  • This manual applies to the SITRANS LC 500 only.

This manual will help you set up your SITRANS LC 500 for optimum performance. We always welcome suggestions and comments about manual content, design, and accessibility.

Please direct your comments to techpubs@siemens-milltronics.com. For the complete library of Siemens Milltronics manuals, go to www.siemens-milltronics.com

Page 9 of the Siemens Sitrans user manual — Introduction
Page 9 · click to enlarge
Page 9

Abbreviations and Identifications

Short formLong FormDescriptionUnits A/D Analog to Digital CE / FM / CSAConformitè Europèene / Factory Mutual / Canadian Standards Associationsafety approval D/A Digital to Analog DACDigital Analog Converter DCS Distributed Control System control room apparatus ESDElectrostatic Discharge Ex Explosion Proof safety approval ExdFlame Proofsafety approval FV Full Vacuum HARTHighway Addressable Remote Transducer IS Intrinsically Safe safety approval LRVLower Range Valuevalue for 0 %4 mA below which no PV is LSL Lower Sensor Limit anticipated µFmicro Farads10-6Farad µs micro Seconds 10-6 Seconds PEDPressure Equipment Directivesafety approval pF pico Farads 10-12 Farad ppmparts per million PV Primary Variable measured value Stilling WellGrounded metal tube with openings SV Secondary Variable equivalent value SVLRVSecondary Variable Lower Range Value0% equivalent value Secondary Variable Upper SVURV 100% equivalent value Range Value TVTransmitter Variable URV Upper Range Value value for 100% 20 mA USLUpper Sensor Limitabove which no PV is anticipated

Introduction

Page 10 of the Siemens Sitrans user manual — Performance
Page 10 · click to enlarge
Page 10

Technical Specifications: SITRANS LC 500

Power

  • maximum: 33 Vdc, (30 Vdc for IS)
  • minimum 12 Vdc at 3.6 mA (9.5 Vdc at 22 mA)

Loop current 3.6 to 22 mA / 22 to 3.6 mA (2-wire current loop)

Environmental

Specifications

Altitude 2000 m max.

  • standard: –40 o C to 85 o C (–40 o F to 185 o F)
  • ATEX-Explosion Proof –40 o C to 70 o C (–40 o F to 158 o F) for T6

–40 oC to 85 oC (–40 oF to 185 oF) for T5 to T1

Relative humidity suitable for outdoor (Type 4X / NEMA 4X / IP 65 enclosure)

Performance

  • MSP-2002-2 0 to 3300 pF

Minimum span 3.3 pF

Measurement frequency 420 kHz @ Cx = 0 pF

Accuracy deviation

Non-linearity 0.1% full scale

Repeatability 0.1% actual measurement

Temperature stability 0.15 pF (0pF) or

Show 6 more labels / short text on this page
Supply voltage · Location indoor/outdoor · Ambient temperature · Installation category II · Pollution degree 4 · Measurement range
Page 11 of the Siemens Sitrans user manual — Communications
Page 11 · click to enlarge
Page 11
  • Safety
  • current signalling according to NAMUR NE 43; 3.6 to 22 mA / 22 to 3.6 mA
  • probe input ESD protected to 55 kV
  • inputs/outputs fully galvanically isolated
  • polarity-insensitive current loop
  • fully potted
  • integrated safety barrier
  • Diagnostics (Includes
  • primary variable (PV) out of limits fault alarm)
  • system failure measurement circuit
  • deviation between A/D and D/A converter values
  • check sum
  • watch dog
  • self-checking facility

Specifications

Outputs

  • galvanically isolated
  • damping range 1 to 10,000 Current loop
  • continuous signal 4 to 20 mA / 20 to 4 mA
  • 2-state functionality 4 or 20 mA / 20 or 4 mA, on or off
  • time delay 1 to 100 sec. activating / de-activating
  • adjustable hysteresis (on / off) 0 to 100%, min. 1% of range

Solid-state switch 40 Vdc / 28 Vac / 100 mA at 2 VA max.

  • time delay 1 to 100 sec. activating / de-activating
  • adjustable hysteresis (on / off) 0 to 100%, min. 1% of range

User Interface

Local digital display 4 1/2 digit LCD

Rotary function switch for selecting programmable menu items

  • 16 Positions 0 to 9, A to F
Push-buttonsRED (+), BLUE (–) used in conjunction with rotary switch, for programming menu items

Communications

HART 1 Communication protocol

1. HART® is a registered trademark of the HART Communications Foundation.
Page 12 of the Siemens Sitrans user manual — Weight
Page 12 · click to enlarge
Page 12

Electrodes

  • threaded connection AISI 316 L stainless steel, 3/4”, 1”, 1-1/4”, 1-1/2”, 2”, NPT, BSPT, JIS
  • flat-faced flanges AISI 316 L stainless steel (optional C 22.8 N, Monel 1 400,

Hastelloy2 C22, Duplex) ANSI, DIN3

  • Cable: 9 mm (0.35”)
  • Rod: 16 mm (0.63”) or 24 mm (0.95”)

Specifications

  • Rod version: up to 3500 mm (138”) with 16 mm (0.63”) diameter probe up to 5500 mm (216”) with 24 mm (0.95”) diameter probe
  • Cable version: 35 m (15 ft.)

Probe insulation PFA, Enamel4

Wetted Parts

Probe insulation PFA / Enamel

Threaded connection AISI 316 L stainless steel

Flange AISI 316 L stainless steel or Teflon5 covered

Enclosure (electronic)

  • construction aluminum, epoxy-coated; diameter 160 mm (6.3")
  • cable entry 2 x 1/2” NPT
  • ingress protection Type 4X / NEMA 4X / IP 65

Weight

Depends on configuration.

Example:

model: S-series rod: PFA insulated, 16 mm (0.63”) dia., 1 m (39.4”) insertion length weight: approx. 5 kg

1. Monel® is a registered trademark of the International Nickel Company. 2. Hastelloy® is a registered trademark of Haynes International Inc. 3. Please see Flange Standards on page 90 for a table showing flange sizes. 4. Only available as Rod version, max. length 1500 mm (59”), and only for use in applications where pH ≤ 7. 5. Teflon® is a registered trademark of Dupont.

Process connections · Probe diameter · Probe length

Page 13 of the Siemens Sitrans user manual — Specifications
Page 13 · click to enlarge
Page 13

Process Conditions

  • standard FV (full vacuum) to 200 bar (2920 psi)
  • option up to 525 bar (7665 psi)
  • standard –200 ° C to 200 ° C ( –328 ° F to 392 ° F )
  • option up to 400 ° C (752 ° F )

Approvals

CE Complies with the requirements of E.C.C. as per EN 55011 and EN 61326

Specifications

Dust Ignition Proof (DIP) ATEX II 3GD (EEx nA [ib] IIC T4...T6) FM/CSA: Class I, Div. 2, Gr. A,B,C,D T4 Class II, Div. 1, Gr. E,F,G T4 Class III, Div. 1, Gr. E,F,G T4

Intrinsically Safe (IS) ATEX II 1 G (EEx ia IIC T4...T6) FM/CSA: Class I, Div. 1, Gr. A,B,C,D T4

Flame-proof/ ATEX II 1/2 GD (EEx d [ia] IIC T6...T1) Explosion-proof enclosure FM/CSA: Class I, Div. 1, Gr. A,B,C,D T4

Lloyds Register of Shipping Categories ENV1, ENV2, ENV3, ENV5

European Pressure, PED 97 / 23 / EC

1. Please refer to page 18, Temperature/ Pressure Curve chart, for specific combinations of temperature and pressure.

Pressure rating1 · Temperature rating1 · Sanitary 3A

Page 14 of the Siemens Sitrans user manual — Capacitance measurement in a cylindrical metal tank
Page 14 · click to enlarge
Page 14

SITRANS LC 500: Transmitter

Operating Principles

Capacitance1 measurement operates by forming a variable capacitor resulting from the installation of a vertical measurement electrode in a vessel or silo. The tank wall usually forms the reference electrode of the capacitor. Whatever material is sandwiched between the two electrodes forms the dielectric. This will be composed of the vessel contents (air, vapor, liquid, solid, or a combination) and, if the measurement electrode is insulated, the insulating layer (PFA, for example). The dielectric gives a capacitance value that is proportional to level.

Capacitance is affected by the surface area of the electrodes, the separation distance between the electrodes, and the dielectric constant of the vessel contents. The dielectric constant is the measure of a material’s ability to store energy. The relative dielectric constant of air (vacuum) is 1: all other materials have a higher value.

Operation & Application

The SITRANS LC 500 variable frequency oscillator

The SITRANS LC 500 probe is equipped with a variable frequency oscillator which responds to the capacitance: a change in capacitance is registered as a change in frequency. The relationship between capacitance and frequency is inverse, resulting in high resolution and accuracy. The variable frequency maintains a constant relationship to the reading.

Capacitance measurement in a cylindrical metal tank

In a cylindrical tank, it is possible to determine the initial capacitance in air by factoring in the length of the probe, diameter of the probe, diameter of the tank, and the relative dielectric constant of air.

1. For definitions relating to capacitance, see the glossary, page 109.
Page 15 of the Siemens Sitrans user manual — Operation & Application
Page 15 · click to enlarge
Page 15

The formula1 is:

C K ε L × × Log D d ⁄ ( ) =

where C = capacitance

K = constant ε = dielectric constant L = active measurement length D = diameter of tank d = probe diameter.

(For detailed application examples, see page 91.)

The transmitter measures the capacitance of the measurement electrode relative to the tank wall (reference electrode) and transforms it to a 4-20 mA signal. Any material that covers the probe will cause an increase in capacitance relative to an uncovered probe surrounded by air. As the product level rises the capacitance will increase.

Non-conductive or conductive contents

In practice, the SITRANS LC 500 probe is usually insulated. If the vessel contents are non- conductive, the dielectric is composed of the vessel contents and the insulation, and the separation distance is from the probe to the tank wall. The tank wall is the reference electrode, and it must be connected to the ground point on the instrument.

dielectric = contents plus insulation (non-conductive contents)

dielectric = insulation (conductive contents)

Operation & Application

dia. (d)

probe sleeve internal tank wall

internal tank diameter (D)

If the vessel contents are conductive, the electrode must be insulated. In this case the dielectric is the insulation layer and the interface between the conductive contents and the insulating sleeve acts as the reference electrode. This reduces the separation distance for the filled portion of the tank to the thickness of the insulation. It also creates a linear reference electrode independent of the tank wall.

1. This formula applies to a centrally mounted probe: for a probe mounted off-centre, the formula must be adjusted.

probe · (insulation)

Page 16 of the Siemens Sitrans user manual — Operation & Application
Page 16 · click to enlarge
Page 16

In a non-conductive or irregular tank

Where the vessel contents are non-conductive:

  • a reference electrode parallel to the measurement electrode is required
  • the reference electrode must be grounded to the instrument
  • a stilling well can form the reference electrode.

Where the vessel contents are conductive:

  • the interface between the contents and the electrode insulation acts as the reference electrode
  • a connection from the vessel contents to the instrument ground is required
  • a stilling well can provide a means of connecting the contents to the instrument ground.

The stilling well

The stilling well is a metal tube concentric with the electrode, with vent openings to facilitate level equalization. Its diameter is somewhat larger than that of the electrode, depending on the application. The stilling well can either be integral to the SITRANS LC 500, or it may be part of the tank1.

The SITRANS LC 500 electrode

The SITRANS LC 500 electrode, comprising a measurement section and an active shield section, is the primary sensor of the system. It supplies the electrical capacitance value of the measurement section relative to the environment (tank wall or stilling well).

Operation & Application

The SITRANS LC 500 patented Active-Shield Technology electrically isolates the measurement section and prevents any non-measurement capacitance from interfering with the measurement. (Capacitance changes could result from uncontrolled variations occurring in the connection cable, process connection, and non-active parts of the probe). This results in a better ratio of initial capacitance to total capacitance, resulting in higher accuracy.

1. The tank wall, or the stilling well if it is part of the tank, must be grounded.
Page 17 of the Siemens Sitrans user manual — Operation & Application
Page 17 · click to enlarge
Page 17

SITRANS LC 500 with Active Shield

R = (C1 + C2 + C3) + Ca

(C1 + C2 + C3) + Ca + Cm

R = Ratio between initial

capacitance and total capacitance

Ca = Initial capacitance (air)

Cm = Capacitance Increase

C1 = Capacitance connection

C2 = Capacitance connection

C3 = Capacitance Process

connection (includes active part)

The measurement is further protected from interference by a buffer, which applies the frequency signal from the measurement section to the active shield section. This effectively eliminates any electrical potential difference between the shield and the measurement section and prevents additional changes in capacitance occurring.

Operation & Application

SITRANS LC 500

frequency (f) ≈ K capacitance (C)

The relative lengths of the measurement section and active shield section can be specified to suit a particular application. If the measured range will be short relative to the total length of the electrode, specify a short measurement section. This increases the achievable resolution of the measurement, since any change in level will be greater relative to the length of the measurement section.

Show 22 more labels / short text on this page
Conventional Capacitance · Measurement · R = Ca · Ca + Cm · Measuring- · Measuring- · Circuit · Circuit · (product) · point · cable · Ca Ca · Cm Cm · active shield · empty · full tank · tank · active measurement section · 100% · buffer · probe seal (inactive) · 0%
Page 18 of the Siemens Sitrans user manual — Operation & Application
Page 18 · click to enlarge
Page 18

The entire SITRANS LC 500 transmitter is potted in epoxy resin as part of the intrinsic safety protection. The potting also protects the electronics against mechanical vibration and moisture influences.

The transmitter is connected to the electrode by a mini coaxial cable, and grounded to a connection point inside the enclosure. The external ground lug on the enclosure provides a means of connecting the instrument system ground to a grounded tank or stilling well1. (For more detailed information on grounding requirements, please see Grounding Examples, page 28.)

The measuring range of the SITRANS LC 500 is 3300 pF (1.0 pF ≅10–12F).

Application: SITRANS LC 500

The SITRANS LC 500 provides an analog and a solid-state output. The analog output can be either a continuous signal proportional to the reading, or in 2-state mode, a mA signal operating according to NAMUR recommendations for fault signalling2.

0% (LRV) and 100% (URV) can be set anywhere within the measurement range.

Operation & Application

1. The loop current provides either:

a. an analog signal:

  • a reading proportional to level (PV) under normal conditions
  • an out-of-limits display, ‘ooL’, alternating with PV, in fault conditions (if the process level exceeds the limit settings [USL] or [LSL])

or:

b. in 2-state mode, provides a mA output:

  • 4 mA or 20 mA output for 0% and 100%, under normal conditions
  • a 3.6 or 22 mA output in fault conditions (when 2-state fault signalling [menu 08] is enabled, if the process level exceeds the limit settings [USL or LSL])
2. The solid-state output can be set to ‘contact open’ or ‘contact closed’, relative to a

covered probe: it can be wired to an external relay and used to activate an external alarm or a pump via an auxiliary power circuit. It can be activated under normal conditions by the threshold settings, or Fault signalling can be enabled at menu 18.

1. Where the stilling well is welded to the tank.
2. See page 93 for detailed examples.
Page 19 of the Siemens Sitrans user manual — Level Measurement
Page 19 · click to enlarge
Page 19

Indicator - dynamic Primary Variable (units or % of range)

Siemens Sitrans — Level Measurement diagram (page 19)
Fig. 2 · Level Measurement

0-100% auxiliary power pump power solid- state output current loop connection

URV = 100% Upper Threshold Setting = % (activation hysteresis)

solid- state switch output or 2-state mA output

3. Upper Threshold Setting and Lower Threshold Setting activate and deactivate the

2-state output, and/or the solid-state output: the settings can be modified to adjust the hysteresis (the window within which the probe is considered ‘covered’).

Operation & Application

4. The speed of response to activation and deactivation of the solid-state and/or

2-state output can be modified by Upper and/or Lower Threshold delays.

5. The PV reading can be stabilized if necessary by applying Damping.
6. Overfill or underfill protection can be set in the absence of those conditions by

applying the Delta Range Setting.

7. Analog Fault Signalling (menu 08) and Digital Fault Signalling (menu 18) take

precedence over the threshold settings (menus 07 and 17).

Level Measurement

The continuous 4-20 or 20-4 mA signal is proportional to the surface level of the product, with an accuracy of 0.1% of the actual measurement (for example, 1mm/m).

Typically, Lower Range Value (LRV - 0%) is set to 4 mA and Upper Range Value (URV - 100%) is set to 20 mA: but the reverse is possible if required. The measurement takes place anywhere within that range. The LCD displays the value as mA, or pF, or percent, depending on the setting for the transmitter variable (TV). If you are using HART, you have the option to define the units.

Page 20 of the Siemens Sitrans user manual — Adjustable hysteresis and time delay
Page 20 · click to enlarge
Page 20

Interface Measurement

The capacitance of the electrode system is dependent on the dielectric constant of the product surrounding the probe. By comparing the capacitances resulting from different products with different dielectric constants, it is possible to determine which product is surrounding the probe.

For miscible productsContamination of one product by another can be measured:

100% product A 4 mA 100% product B 20 mA Values in between 4 and 20 mA represent the ratio of the two products.

For immiscible products: The interface between two products can be detected by the change in capacitance from one to the other. (See example, For Vessels filled with Oil on page 91.)

Switch action

2-state Switch

The mA output can be used as a 2-state switch set to either 4 or 20 mA. It can be set to go to 4 mA if the probe is covered and 20 mA if the probe is uncovered, or the reverse.

Operation & Application

Solid-state Switch

The solid-state output can be set to ‘contact open’ or ‘contact closed’ with a covered probe.

Adjustable hysteresis and time delay

The adjustable hysteresis and time delay settings allow you to adjust the switch action for applications with a lot of surface movement.

Examples: With a moving surface that fluctuates between 79% and 80%, if the hysteresis is set so that 80 is on and 79 is off, the alarm will constantly alternate between on and off. Either set a time delay, or adjust the hysteresis:

  • Set the time delay to 10 seconds (for example): the alarm will be on only after the surface has been at 80% for at least 10 seconds.
  • Reset the hysteresis for 70 (for example): the unit will ignore small surface fluctuations between 79 and 80%.
Page 21 of the Siemens Sitrans user manual — Via the solid-state output
Page 21 · click to enlarge
Page 21

Fault Signalling

The SITRANS LC 500 has three fault signalling options:

  • via the loop-current
  • via HART
  • via the solid-state output or solid-state relay.

Via the loop current

When using the mA signal, the SITRANS LC 500 operates according to NAMUR standards1 for fault signalling. The fault/failure signal can be triggered by a failure in the measuring system, such as:

  • a checksum error
  • a loss of signal caused by a defect in the module
  • a short circuit in the sensor
  • a process failure if the level exceeds the limit settings and if the unit is programmed to detect this

You can set the Upper and Lower Sensor Limits (menus 0B and 0C) outside the Upper and Lower Range Value settings. In this case, if the process value is outside its nominal range (the span between LRV and URV), but still not at a fault/failure level, the continuous mA output will saturate to 3.8 mA or 20.5 mA. If the process value is outside the Upper or Lower Sensor Limits, this will be registered as a fault/failure.

Operation & Application

Depending on the setting chosen for 2-state Fault Signalling (menu 08), the signal will go to either 3.6 mA (F: Lo) or to 22 mA (F:Hi). If you do not use communications to receive status information, we recommend enabling analog fault signalling (menu 08), in order to be warned if a fault or failure occurs. (This feature is disabled by default.)

Via HART

See page 75 for HART Response Code Information. Each HART message is accompanied by a response code. It is then up to the Host to decide what to do in the case of a fault situation. The Host may decide to issue Command 48, which returns more detailed information.

Via the solid-state output

The solid-state switch can be wired up to an external relay, to provide a second level of protection. It can then be used to activate a failure alarm, or a level switch. (See page 93 for details of an application using SITRANS LC 500 as a level indicator, with the two-state output connected to a relay that activates a pump.)

1. See NAMUR recommendation NE 43 on page 107 for more details.
Page 22 of the Siemens Sitrans user manual — Probe Configuration
Page 22 · click to enlarge
Page 22

SITRANS LC 500: Probe Configuration

The probe (electrode) comprises a measurement section and an active shield section. This electrode connects to the capacitance detector portion of the two-wire loop powered electronic transmitter. The transmitter module is mounted in a powder-coated aluminum enclosure which provides reliable operation in environments with dust, moisture, and high-frequency interference.

SITRANS LC 500 Electrode (Probe) Characteristics

Apply to all general connection configurations:

  • The standard SITRANS LC 500 insulated electrode is designed for use in both conducting and non-conducting liquid applications.
  • Most electrodes consist of an active shield portion and a measurement portion, which combine to form the complete electrode. (This is not the case for cable electrodes or electrodes with ceramic/enamel insulation.)
  • The sum of the active shield length and the measurement length is the total insertion length.
  • The active shield design provides continuous immunity from changes in conditions at the top of the vessel where levels of vapors, dust, and condensation may be constantly changing.
  • The design of the active shield isolates the starting capacitance of the electrode from the effects of changes in capacitance due to temperature and pressure fluctuations that could cause small changes in the seal geometry.
  • The carefully-controlled diameter of the electrodes and insulation produces a linear output over a wide range of capacitance values (1 pF to 3300 pF).
  • The end seal is formed as an integral part of the electrode insulation, giving smooth and uniform characteristics (tested to 55 kV).
  • Standard single cone seal

Probe Configuration

ment portion probe seal (inactive)

active shield · insertion length · measure-

Page 23 of the Siemens Sitrans user manual — Probe Configuration
Page 23 · click to enlarge
Page 23

Electrode Assembly

SITRANS LC 500 electrodes come in a variety of formats to provide the necessary characteristics for correct mounting, chemical compatibility, temperature and pressure requirements, and dielectric constant of the medium. The main body of the manual discusses the standard configuration. Other options, with details, are shown in Appendix E: SITRANS LC 500, alternate versions and application details, page 83.

Process Connections

The standard threaded process connection (S-Series) with PFA insulated electrode, including the active shield, provides good results in all measurement situations within the temperature, pressure, and corrosive capabilities of the materials and seals. This remains true over a wide range of dielectric constants in both non-conducting and conducting materials.

Any standard process connection is available with the SITRANS LC 500, and special versions can be fabricated to match the mounting and application requirements. A wide range of threaded and flanged fittings is available. (Contact your local Siemens Milltronics representative for details, or check our website at: www.siemens-milltronics.com)

Seal Types

The basic internal seal for the SITRANS LC 500 has a conical-shaped, preloaded pressure/leak resistant construction. Up to three levels of seal protection are implemented depending on the integrity requirements of the application. A single or double cone internal seal forms one or two barriers against leaking, and a third flange face gasket is also available in the D and DD seal construction. The flange face seal also provides a design with no metal wetted parts if required.

Process Connection and Seal Configuration of SITRANS LC 500

Process Connection Seal Type Seal Description

Probe Configuration

Threaded S Single Cone

Welded Flange S Single Cone

D Single Cone + Teflon flange seal

DD Double Cone + Teflon flange seal. (Consult your local Siemens Milltronics representative.)

SD Double Cone (used for stilling well applications)

S Single Cone · Solid Machined Flange

Page 24 of the Siemens Sitrans user manual — Probe Configuration
Page 24 · click to enlarge
Page 24

Pressure and Temperature Considerations

The maximum temperature and pressure of operation for the standard SITRANS LC 500 level probe is 200°C (392°F) and 200 bar (2900 psi). Please consult the pressure curve on page 18 for qualifications that must be applied to these maximums.

Enamel probes are recommended when the process temperature exceeds 200 °C, and/or in combination with very high pressure.

Temperature Versus Pressure Curve for SITRANS LC 500 PFA-insulated Level Probe

As the temperature approaches 75°C (167°F), the maximum pressure must be derated1. When the temperature reaches 200°C (392°F), the maximum pressure is limited to 50 bar (725 psi). This curve is typical for water only. For other, more aggressive chemicals the derating curve will be more severe.

consult factory when pressure or temperatures fall within this area

200 bar (2920 psi)

150 bar (2190 psi)

100 bar (1460 psi)

70 bar (1022 psi)

50 bar (725 psi)

–1bar (– 14.6 psi)

70oC (158 oF) temperature

100 oC (212 oF) –100 oC (–148 oF)

200oC (392 oF) –50 oC (–58 oF)

0 oC (32 oF)

50 oC (122 oF)

150 oC (302 oF)

Probe Configuration

Reference ProductWater
  • Notes:
  • For high temperature and pressure ratings for the Enamel probe, please contact your Siemens Milltronics representative.
  • For FM / CSA Explosion Proof applications: if the process temperature exceeds 135 o C (275 o F), select process seal type SD,DD,HP or HT.
1. Decreased within the limits specified in the diagram (maximum 200 bar).

pressure

Page 25 of the Siemens Sitrans user manual — Probe Configuration
Page 25 · click to enlarge
Page 25

Non-standard applications

Applications outside the standard capabilities of the S-Series require a different design configuration. These non-standard applications include:

Non-Standard Application SITRANS LC 500 Configuration

Non-metallic tanks with both conducting and non-conducting liquids.

Use stilling well for second electrode reference.

Non-conducting liquids in spherical and horizontal-cylindrical tanks.

Use a stilling well as linearizer.

Highly corrosive materials requiring no metallic wetted parts.

Use flange mount with D, DD seal version.

Sanitary/food safe applications. Use SITRANS LC 500 sanitary version.

For more details on alternate configurations, see, Appendix E: SITRANS LC 500, alternate versions and application details on page 83.

Probe Configuration

Page 26 of the Siemens Sitrans user manual — Installation
Page 26 · click to enlarge
Page 26

SITRANS LC 500: Installation

Notes:

  • Installation shall only be performed by qualified personnel and in accordance with

local governing regulations. • This product is susceptible to electrostatic discharge. Follow proper grounding

procedures.

  • WARNINGS:
  • Disconnect the device before any welding is carried out in the vicinity of the instrument.
  • Provide protection when the solid-state switch is activating an external relay to prevent possible switch/relay damage resulting from inductive spikes generated by the relay coil. (See Protection for solidstate switch on page 21 for details.)

Handling Electrodes

  • WARNINGS:
  • Do not scratch or gouge the PFA electrode insulation since this could reduce the integrity of the insulation and the useful life of the electrode.
  • Be careful with an enamel-insulated electrode 1 .
  • Do not damage the insulation jacket on the electrode during shipping, packing, and installation 2 . Any damage to the electrode can prevent proper performance.
  • (ATEX 100): Precautions MUST be taken to avoid ignition due to hazardous electrostatic discharges:

a. Where an isolated probe is used in gas, vapor, or a non-

conductive liquid that is potentially explosive, requiring apparatus group IIC equipment. b. Where the probe is used in a potentially explosive dusty

atmosphere.

1. Normally the enamel insulation is protected by a stilling well, which is part of the design. 2. Most electrodes use PFA insulation, a very dense and reliable type of Teflon® that prevents leakage and corrosion of the metal electrode and acts as an insulator when conductive materials are being measured.

Installation

Page 27 of the Siemens Sitrans user manual — Installation
Page 27 · click to enlarge
Page 27

Mounting Instructions

The SITRANS LC 500 is easily installed: simply mount the instrument on the process connection of the vessel.

  • Notes:
  • The transmitter is specified for use at temperatures ranging from –40 ° C to 85 ° C (–40 o F to 185 o F): if your process temperature is outside this range, a standard option is available with a thermal isolator.
  • Before mounting the SITRANS LC 500, check to ensure the threads are matching to avoid damaging them.

Protection for solid-state switch

  • for dc circuits: connect protection diodes in the correct polarity across the relay coil
  • for ac circuits: connect a Voltage Dependent Resistor (VDR) or other ac compatible component (such as zeners and protection diodes in combination) in the correct polarity across the relay coil

Process Cautions

CAUTIONS:

  • With a centrally mounted cable version, take care that the tensile load does not exceed probe or vessel rating
  • With a cable version mounted close to the tank wall, take care that the product does not push the cable against the tank wall: a spring can be used as a retainer.

? ?

500 mm (20”) min.

Installation

Page 28 of the Siemens Sitrans user manual — Installation
Page 28 · click to enlarge
Page 28

SITRANS LC 500: Standard Level Version

Available with the following features:

  • Threaded flanges, welded flanges, and single-piece flanges
  • S series, D series, SD series, DD series, and HP series process seals
  • Selections of standard ANSI and DIN flanges
  • The most common electrode is insulated with PFA. Enamel (HP seal) is also available (rigid design only).
  • Various process connection materials
  • Both Rod and Cable versions

See Appendix E: SITRANS LC 500, alternate versions and application details, page 83 onward, for details on dimensions, and for application examples.

Installation

Page 29 of the Siemens Sitrans user manual — Interconnection
Page 29 · click to enlarge
Page 29

Interconnection: SITRANS LC 500

Interconnection

Wiring

Supply

  • Notes:
  • The transmitter is powered by the current loop and needs at least 9.5-13 Volt on the terminals: 9.5 V at 22 mA or 12 V at 3.6 mA.
  • The maximum supply is 33 Volt. If the voltage is higher the device will shut down.
  • The loop-circuit will withstand voltages up to 250 Vac/Vdc without any damage.

The SITRANS LC 500 uses a switched power supply circuit, which makes the most efficient use of the available power present on the terminals. If the signal current is low, (4mA), the terminal voltage will be high, and if the signal current is high, (20 mA), the terminal voltage may be low, due to all the resistive elements in the loop, such as the barrier and sense resistor.

Voltage drop versus mA for current transmitter operation

voltage drop over 250 ohm measuring resistance

voltage drop over 280 ohm in barrier

voltage drop over blocking diode in barrier

margin or voltage drop over instrument cable operation voltage, transmitter

Examples:

  • With a 250 Ohm sensing resistor, no barrier and negligible cable resistance, the overall supply voltage should be at least 15.0 V.
  • With a 250 Ohm sensing resistor, a barrier of 280 Ohm, and 20 Ohm cable resistance (500 m), the total resistance is 550 Ohm, so the overall supply voltage should be at least 20.5 Volts.
  • For a multi-drop application, where the measuring supply is fixed to 4 mA, the voltage on the terminals of the SITRANS LC 500 should be at least 12 Volts.

The loop circuit is completely isolated from the measurement circuit. It is designed so that the internal capacitance and inductance on the terminals are isolated and do not factor in safety calculations.

V-supply · mA

Page 30 of the Siemens Sitrans user manual — 65 10 6 – × 537.36 C ×
Page 30 · click to enlarge
Page 30

Cable

Interconnection

  • Notes:
  • To maintain reliable transfer of the HART modem signals, the RC 1 time constant of the connections should be less than 65 µSec.
  • Cable capacitance must also be considered when selecting cable for intrinsically safe installations.
  • For output signals (from the SITRANS LC 500), only the cable and barrier resistance are relevant. For input signals the measurement resistance is also relevant.
  • Use twisted pair cable, screened as a pair. 2
1. RC = Resistance * Capacitance 2. Or, if you use a common screen over a cable containing multiple twisted pairs, do not use other pairs for signals that could interfere with HART signals.

Selecting the correct instrumentation cable

  • you need to know the cable length, the barrier type (if applicable), and the measurement resistance
  • select a cable that will give you a capacitance time constant of less than 65 µSec
1. Calculate the capacitance for a time constant of 65 µSec, using the following formula:

t R C × = R C

(time constant = Resistance * Capacitance) is the sum of the load resistor and cable resistance.

is the sum of the cable capacitance and the capacitances of the connected device/devices.

2. Determine the cable length allowed, by subtracting the capacitance value of the

device (or devices) on the loop from the total capacitance, and using the maximum allowable limit of 100 pF per meter (or 1 nF per 10 meters).

Example 1. Calculate the cable capacitance which will give a time constant of 65 µSec: A twisted pair cable with a conductor cross-section of 1 mm2 (AWG 18 equivalent) has a copper resistance of 73.6 Ohm/km and a capacitance of 100 pF/m (or 1 nF/10m).

For a standard 28 V 280 Ohm barrier and a 250 Ohm measuring resistance, with a 100 meter cable:

Resistance = 280 (barrier) + 250 (sensing device) + 7.36 (cable)= 537.36

t R C × =

C t R ⁄ =

65 10 6 – × 537.36 C ×

C 65 10 6 – × 537.36 ⁄ ( ) 121 = =

s = nF · nF

Page 31 of the Siemens Sitrans user manual — Multi-drop applications: maximum cable length
Page 31 · click to enlarge
Page 31
2. Calculate the length of cable allowed, by subtracting the capacitance value that the

device presents on the loop from the total capacitance. SITRANS LC 500 has no measurable capacitance value, but assume 5 nF. Then use the maximum capacitance limit (1 m /10 nF) to determine the cable length.

Interconnection

121 5 116 = –

116 10 1160 = ×

IS applications: maximum cable length

In an IS application, the IS side of the barrier allows for only 70 nF.

Example:

Subtract the capacitance for the device:

70 5 65 = –

65 10 × 650 =

This allows for a maximum 650 meters on the IS side.

On the other side of the barrier:

121 65 56 = –

which allows for 560 meters on that side.

IIB type/class hazardous area applications: maximum cable length

In IIB type/class hazardous area applications the maximum allowed capacitance value is 330 nF, as long as you are not using HART. If you are using HART, the maximum cable length will be limited. Depending on cable specifications, the maximum length lies between 1 and 3 km.

Multi-drop applications: maximum cable length

In a multi-drop application, the total capacitance of all the devices must be calculated. With five devices, at 5 * 5 nF, the allowable cable length will be considerably limited.

  • Notes:
  • If the device is part of a multi-drop setup, the SITRANS LC 500 sets the current to 4 mA, which inhibits analog signalling, including fault signalling.
  • Multi-drop is a HART mode where devices are set to a fixed current, and the device is interrogated periodically. The maximum number of devices on one loop is 15, one of which can be an analog mode device.
Show 5 more labels / short text on this page
nF · m · nF · m · nF
Page 32 of the Siemens Sitrans user manual — Connection Diagram
Page 32 · click to enlarge
Page 32

Terminals

The SITRANS LC 500 is equipped with two terminal blocks, both insensitive to polarity.

Interconnection

One terminal block is intended for connecting the instrument cable (loop power).

The other terminal block provides the solid-state switch output.

Connecting SITRANS LC 500

The processor integrated circuit is covered by a label which contains product information and which also acts as a protective seal against moisture.

1. Loosen the retaining set-screw and remove the enclosure cover. 2. Loosen the cable gland and thread the cable through it. 3. Connect the power / signal conductor wires to the current loop terminal block (any polarity). 4. Ground the enclosure: (see instructions on next page for details). 5. Check to ensure all connections are good. 6. Tighten the cable gland to form a good seal. 7. Replace the enclosure cover and tighten the retaining set-screw.

Connection Diagram

protective label (see warning above)

solid-state switch relay (any polarity)

instrument system ground 4-20 mA current- loop connection (any polarity)

measuring signal (mini-coaxial cable)

TypeSer.: Date: Rev.:

ground connection point for instrument system

ground lug · Tampering voids warranty

Page 33 of the Siemens Sitrans user manual — (DO NOT REMOVE)
Page 33 · click to enlarge
Page 33

Protection for solid-state switch

  • For dc circuits: connect protection diodes in the the correct polarity across the relay coil.
  • For ac circuits: connect a Voltage Dependent Resistor (VDR) or other ac compatible component (such as zeners and protection diodes in combination) in the correct polarity across the relay coil.

Interconnection

Grounding instructions

  • Notes:
  • Since the measurement occurs between the Measurement and Ground connections, it is important to have good, low-resistance, reliable connections in this circuit.
  • Use a ground connection wire with a sufficiently large diameter relative to its length, and not less than 1 mm 2 .
  • The SITRANS LC 500 measurement circuit is completely isolated from the loop circuitry: this allows either line of the loop circuit to be grounded if requirements for Ex safety are followed and if the power supply voltage is less than 33 Vdc.

Connect the housing and the process connection with either the stilling well1 and/or tank wall, using the ground lug on the housing.

label / protective seal

(DO NOT REMOVE)

TypeSer.: Date: Rev.:

instrument system ground connection point

1. Where the stilling well is welded to the tank.
Show 4 more labels / short text on this page
ground lug · instrument system ground · (connected at factory) · Tampering voids warranty
Page 34 of the Siemens Sitrans user manual — Metal Tanks
Page 34 · click to enlarge
Page 34

Grounding Examples: SITRANS LC 500

Interconnection

Grounding is important for two reasons:

1. To prevent interference to the signal: system grounding 2. For safety purposes: safety grounding

Several common applications are illustrated. They are separated into two groups: the first group illustrates System Grounding and the second illustrates Safety Grounding.

System Grounding (referencing)

For the measuring system to function correctly, the reference electrode must be properly grounded. Make sure that there is a reliable connection from the instrument housing to the reference electrode (usually a metal tank). Some common applications involving system grounding include:

  • metal tanks
  • metal tanks, cathodically protected
  • non-conductive tanks

Metal Tanks

If the metal tank is reliably grounded, connect the ground lug on the SITRANS LC 500 to the earth ground on the tank as shown.

(See page 26 for connection diagram.)

ground lug · metal

Page 35 of the Siemens Sitrans user manual — Non-Conductive Tanks
Page 35 · click to enlarge
Page 35
Siemens Sitrans — Cathodically Protected Metal Tanks diagram (page 35)
Fig. 3 · Cathodically Protected Metal Tanks

Interconnection

Cathodically protected metal tanks are never directly grounded. However, the impedance of the supply source is so low that it will not cause any problems. The shielding of the loop cable should be grounded at one end only (the tank end) to avoid short-circuiting the cathode protection voltage.

The ground lug on the SITRANS LC 500 can be connected to the tank as shown.

Non-Conductive Tanks

Siemens Sitrans — Non-Conductive Tanks diagram (page 35)
Fig. 4 · Non-Conductive Tanks

Non-metallic tanks always require a stilling well or proper grounded conductive medium.

Connect the ground lug on the SITRANS LC 500 to earth ground. If the stilling well is integral to the SITRANS LC 500, it is now grounded.

If the vessel has a stilling well provided, make sure that the metal parts of the stilling well are properly grounded.

ground lug · non- metallic

Page 36 of the Siemens Sitrans user manual — Example 2
Page 36 · click to enlarge
Page 36

Safety Grounding

The safety grounding requirements are determined by the application and the connected instruments. The SITRANS LC 500 transmitter does not have any special requirements due to the galvanic separation between the measurement section and the loop section.

Interconnection

  • Depending on the DCS characteristics, there are three possible grounding options:
  • If the DCS measures the current through the loop compared to a common zero Volt point, do not ground the negative side of the current loop because measurement inputs can be short-circuited.
  • If the DCS measures the current in the positive wire or connector, the negative side of the current loop can be grounded.
  • If the DCS has galvanically separated inputs for each measurement channel the grounding method can be chosen as required.

In hazardous applications a Stahl-type barrier is required, and it is typically mounted on a DIN rail inside a customer-supplied enclosure located in the non-hazardous area.

Example 1

If no specific Ex conditions apply, the SITRANS LC 500 can be directly connected to the DCS. The supply voltage, however, should remain within the limits set by the SITRANS LC 500. Connecting a SITRANS LC 500 to a DCS does not influence that equipment. One of the connection cables can be grounded if desired.

Siemens Sitrans — Example 1 diagram (page 36)
Fig. 5 · Example 1

Example 2

In the case of Intrinsically Safe applications, where the DCS equipment measures the current in the positive connection and the negative connection can be grounded, a barrier type as shown below is sufficient.

non-hazardous area hazardous area

Siemens Sitrans — Example 2 diagram (page 36)
Fig. 6 · Example 2
Page 37 of the Siemens Sitrans user manual — Example 4
Page 37 · click to enlarge
Page 37

Example 3

If you do not want to ground the negative connection directly, or in the case of Intrinsically Safe applications where the DCS measures the current in the negative connection, and that wire cannot be grounded, a barrier type is required as shown below.

Interconnection

Siemens Sitrans — Interconnection diagram (page 37)
Fig. 7 · Interconnection

Example 4

In Intrinsically Safe applications where the DCS has galvanically separated inputs, you can use either the type of barrier shown below, or the type shown in Example 2.

Siemens Sitrans — Example 4 diagram (page 37)
Fig. 8 · Example 4

When Ex applications are using an Ex approved Intrinsically Safe (I.S.) power supply unit, no barrier is required and grounding is optional.

Siemens Sitrans — Example 4 diagram (page 37)
Fig. 9 · Example 4
Page 38 of the Siemens Sitrans user manual — Diagnostics
Page 38 · click to enlarge
Page 38

Communications

The SITRANS LC 500 is equipped with HART communication1protocol2so that settings and values can be obtained and altered locally3or remotely.

Interconnection

Typical PLC configuration with HART

power supply1 R2= 250 Ω

SITRANS LC 500

PC/laptop with Simatic PDM or HART communicator3

Diagnostics

The internal diagnostic functions continuously monitor the operation of the transmitter. An error signal is generated if a failure or irregularity occurs.

The SITRANS LC 500 sends the signal current according to the NAMUR NE 43 recommendation. During normal operation the current remains within the range from 3.8 to 20.5 mA. If the process exceeds its normal limits but is not in a fault or failure situation, the signal current will be outside the measurement range (4 to 20 mA) but will be limited to either 3.8 or 20.5 mA.

If a fault or a failure is detected, the signal current is set to either 3.6 mA or 22 mA, depending on the settings you have chosen. (This feature may be disabled by the user.)

1. Depending on the system design, the power supply may be separate from the PLC, or it may be part of the PLC. 2. A 250 Ohm resistor is required only when the PLC is connected to a HART modem or a HART communicator. 3. The HART communicator and a PCL/laptop computer cannot both be connected to the 4-20 mA loop simultaneously.
Page 39 of the Siemens Sitrans user manual — Applications for Solid-state Output
Page 39 · click to enlarge
Page 39

Current values used as signals from digital transmitters

Current values for signal detection

Interconnection

F = 1

F = 0

F = 1

0 3.6 3.8 4.0 20 22 20.5

Whenever the local situation allows, the zero adjustment and the full scale can be set using the push-button feature and the appropriate menu selection. In most cases it is possible to do a one point calibration1 by using the push-buttons to input the actual level in %.

The total isolation between the measurement circuit and the current- loop circuit provides immunity during the use of cathode protected measuring tanks. Connection to PLC equipment is possible without any difficulty.

  • The Upper Range Value (URV) and Lower Range Value (LRV) should be within the USL to LSL range, but can be set anywhere within that range.
  • An interruption of the measuring connection will be detected: a loose or interrupted connection results in up to 0.5 pF capacitance, which is below the adjusted LSL and thus signals a FAULT condition.

Applications for Solid-state Output

The solid-state output is a polarity independent switch output. The solid-state switch has two possible functions.

  • it can be activated/deactivated when the product level reaches the upper/ lower threshold settings (set in menus 15 and 16)
  • or it can be activated if a fault or failure is detected 2 (set in menu 18)

See page 93 for an illustration of a typical application using SITRANS LC 500 as a level indicator, with the solid-state output connected to a relay which activates a pump.

The solid-state switch has its own parameter set: menu items 13 to18, (see Menu Levels 00 to 0F and 10 to 1F on page 37, and Rotary Switch Positions – Quick Reference chart on page 41).

In menu 0E and menu 0F, you set the Upper and Lower Range Values (URV and LRV) for relay operation. Within that range, the solid-state switch has independent settings for

1. See Calibration using push-button adjustment on page 43. 2. See Fault Signalling on page 15 for details of fault conditions.
Show 4 more labels / short text on this page
Measurement value · Fault- mA Value (F) · Fault- mA Value (F) · mA
Page 40 of the Siemens Sitrans user manual — Setting Description
Page 40 · click to enlarge
Page 40

Upper and Lower Threshold, (menus 13 and 14) and the accompanied delays (menus 15 and 16).

Interconnection

Initially the solid-state output is disabled for both signal output and fault/failure output (menu 17). When the solid-state switch is to be operated as fault/failure output (for example, for a separate shutdown system), we recommend disabling the operation for signal output (select Disabled Mode in menu 17 on page 70). There is no delay in the operation for fault/failure output.

  • Notes:
  • The solid-state output should only be used in circuits where the current is limited by a proper load.
  • Due to the limited switching capabilities of the solid-state switch component, an auxiliary relay must be applied when switching high-current/high-voltage apparatus.

Switch Protection (Diode)

Factory Settings

The SITRANS LC 500 has a number of default factory settings. If the required settings for the application are known, the settings can be modified during final testing.

Settings:

Setting Description

ID Has a unique serial number

TV0 UL 3300 pF [switch position (0)C]

TV0 LL 1.666 pF [switch position (0)B]

TV0 URV 3300 pF [switch Position (0)F]

TV0 LRV 0.00 pF [switch Position (0)E]

AO1 4-20 mA is 0-100% [position (0)8]

TAG "customer input data via HART"

DESCRIPTOR "customer input data via HART"

MESSAGE "Siemens Milltronics P I"

TV0 Units PF

Page 41 of the Siemens Sitrans user manual — Interconnection
Page 41 · click to enlarge
Page 41

Setting Description

DATE "customer input data via HART"

SENSOR SERIAL NUMBER "customer input data via HART"

Interconnection

FINAL ASSEMBLY NUMBER "customer input data via HART"

TV1 LRV 0 [switch position (0)E, TV1]

TV! URV 1.0 [switch position (0)F, TV1]

  • The Upper Sensor Limit (USL) and Lower Sensor Limit (LSL) are set to 3300 and 1.666 pF respectively, and the following conditions apply: the Upper Range Value (URV) and Lower Range Value (LRV) should be within the USL to LSL range, but can be set anywhere within that range.
  • An interruption of the measuring connection will be detected: a loose or interrupted connection results in up to 0.5 pF capacitance, which is below the adjusted LSL and thus signals a FAULT condition.

TV1 Units UNDEFINED

Page 42 of the Siemens Sitrans user manual — The LCD (display)
Page 42 · click to enlarge
Page 42

The SITRANS LC 500 User Interface

The SITRANS LC 500 user interface consists of the display (LCD), the rotary switch, and two push-buttons. The rotary switch enables you to select a particular item and/or variable for read-out and/or adjustment: the push-buttons allow you to select and/or alter a read-out or a value.

rotary switch menu selector

Siemens Sitrans — The SITRANS LC 500 User Interface diagram (page 42)
Fig. 10 · The SITRANS LC 500 User Interface

solid-state switch relay (any polarity)

User Interface

current-loop connection (any polarity)

The LCD (display)

The seven-segment LCD (display) shows the value and/or diagnostic information. It is mainly for numeric data, but there are also a number of indicators which use alphabetic characters. A list of these LCD displays, together with the associated menu items, is shown in Appendix B: LCD display examples on page 74.

left-arrow indicates Menu Level 10 to 1F

Siemens Sitrans — The LCD (display) diagram (page 42)
Fig. 11 · The LCD (display)
left-most colonindicates value accepted (debounce time passed)

The LCD will hold information for a long time even when not refreshed (for example, if there is a loss of power). The heartbeat indicator blinks continuously whenever the device is working. A still heartbeat signals that the device has stopped working.

Show 5 more labels / short text on this page
RED (+) push-button · increment value · BLUE (–) push-button · decrement value · measurement connection
Page 43 of the Siemens Sitrans user manual — Menu 00 to 0F Description Menu Group Details
Page 43 · click to enlarge
Page 43

How to access the data:

Access data in the transmitter from 28 menu items divided between two menu levels: 00 to 0F and 10 to 1F. Use the rotary switch and push-buttons in combination to select an item and adjust the value.

The functions of each menu item are illustrated in application examples on page 93 to 94. Details on using each menu item are given in Appendix A: Menu Groups on page 54. (See also Rotary Switch Positions – Quick Reference on page 41 showing the switch position and button press combinations used to carry out different functions.)

Menu Levels 00 to 0F and 10 to 1F

Menu 00 to 0F Description Menu Group Details

User Interface

09 Stepsize Update Value

0A Damping page 56

0B Lower Sensor Limit page 56

0C Upper Sensor Limit page 57

0D Delta Range Setting page 57

0E Lower Range Value page 58

0F Upper Range Value page 59

00 Dynamic Value (PV)

02 Max./Min. Recorded Value page 60

01 Transmitter Variable select for PV page 60

03 Upper Threshold Delay2-state mode
04 Lower Threshold Delay2-state mode page 62

Analog Output Signalling (loop-current)

05 Upper Threshold Setting2-state mode page 63
06 Lower Threshold Setting2-state mode page 64

07 Analog Signalling Mode page 64

08 Analog Fault Signalling page 66

Menu 10 to 1F Description Menu Group Details 10 Dynamic Value (PV) Transmitter Variable Values

page 59 1C Transmitter Variables Dynamic Value page 61 13 Upper Threshold Delay: solid-state output

page 67 14 Lower Threshold Delay: solid-state output page 68 15 Upper Threshold Setting: solid-state output page 68 16 Lower Threshold Setting: solid-state output page 69 17 Digital Signalling Mode page 70 18 Digital Fault Signalling page 71 11 Output Signal Processing Test

page 72 12 Factory Settings page 72 19 Range Inversion page 73 1F Keylock Level page 73 1A

Non-operational Spare 1B 1D 1E

Show 7 more labels / short text on this page
page 55 · Transmitter Variable Settings · page 59 · Transmitter Variable Value · page 62 · Digital Output Signalling · Miscellaneous
Page 44 of the Siemens Sitrans user manual — Adjusting the value
Page 44 · click to enlarge
Page 44

The rotary switch

The rotary switch gives you access first to the menu level and then to the menu item.

The rotary switch has a small slot where the current position can be read. The positions are read clockwise, and in increasing order: 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, and F. The position wraps from F to 0.

B

D

A

E

F

The switch can be turned in either direction. When it is turned to a new position, the LCD displays the new menu selection for 1 second, followed by the data for that position.

Certain menu selections return more than one piece of information per item: in that case the display alternates between the two values, for example, PV Value / Fault status.

User Interface

The push-buttons

The push-buttons allow you to change the value of a menu item. Use the RED (+) button to adjust a value up; the BLUE (–) button to adjust a value down; or press both simultaneously for special applications. For a table showing the combinations of rotary switch positions and button presses used to carry out different functions, see page 41.

Access to a menu item:

  • Notes:
  • For a detailed description of each menu item, see Appendix A, page 54: the functions of each menu item are illustrated in application examples on page 93 to 94.
  • Change over from Menu LEVEL 0 to Menu LEVEL 1 is only possible at position 0, from menu item 00 to 10 or vice-versa. (See page 42 for detailed instructions.)
1. First select Menu LEVEL 0 or Menu LEVEL 1.
2. Turn the rotary switch to the number of the desired item.

Adjusting the value

  • Notes:
  • The push buttons are preset with a delay called the debounce time.
  • Keeping one or both buttons pressed continuously will trigger an auto-repeat in some menus.
1. Select a menu item. 2. Press the RED (+) or BLUE (–) push button to adjust the value up or down:

acceptance is indicated when the left-most colon on the LCD appears. (You have to press longer than the debounce time to have the action accepted: the debounce time varies according to the menu item selected.)

Page 45 of the Siemens Sitrans user manual — User Interface
Page 45 · click to enlarge
Page 45

Transmitter Variables

  • Transmitter Variable 0 (TV0) is the capacitance as measured by the device.
  • Transmitter Variable 1 (TV1) is a computed variable: the dynamic value is a computed derivative from the range settings for TV0.

Transmitter Variable User-defined Functions Units

TV0

URV, LRV, Damping, USL and LSL

TV1 Can be user-defined

User Interface

pF

Page 46 of the Siemens Sitrans user manual — Quick Start Sequence
Page 46 · click to enlarge
Page 46

Start-up: SITRANS LC 500

Capacitance measurement systems require the instrument to be calibrated for a

particular application. Two methods of calibration are available:

  • push-button (for instructions, see page 43).
  • HART (for instructions, see page 46).

Quick Start

We strongly recommend you read the full manual to use your device to its fullest

potential. However, if it is possible to adjust the level of the tank to the 0% and 100% levels, you can use the quick start sequence below to calibrate the instrument and get started.

  • Notes:
  • Change over from Menu LEVEL 0 to Menu LEVEL 1 is only possible at position 0, from menu item 00 to 10 or vice-versa. (See page 42 for detailed instructions.)
  • For a table showing all the combinations of rotary switch positions and button presses used to carry out different functions, see page 41.
  • For a detailed description of each menu item, see Appendix A, page 54.

Quick Start Sequence

Start Up

1 Calibrate the 0% setting (LRV - lower range value): menu 0E

For instruments without a stilling well, the 0% setting needs to be calibrated after the device is installed, and with the tank/vessel empty. Calibration is also sometimes neces- sary after installing a SITRANS LC 500 fitted with a stilling well, although in most cases the 0% setting is calibrated at the factory.

Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).

a Bring the product level to the height that corresponds to 0%.

b Turn the rotary switch to E (Empty).

c Press both buttons and hold for about 1 second: the 0% point is now set. 2 Calibrate the 100% setting (URV - upper range value): menu 0F

Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).

a Raise the product level to the height that corresponds to 100%.

b Turn the rotary switch to F (Full).

c Press both buttons and hold for about 1 second: the 100% point is now set. 3 View primary variable (PV): menu 00

Turn the rotary switch to 0. The LCD displays the actual pF reading. 4 The SITRANS LC 500 is now ready to operate.

Page 47 of the Siemens Sitrans user manual — NO KEYS
Page 47 · click to enlarge
Page 47

cal PV Units PV Units PV Units PV Units PV Units

Default * TVO * 00 00 75% 25% Analog Disabled 1.0 1 1.666 pF 3300 pF 3300 pF 0 pF 3300 pF Menu LEVEL 1 (10 to 1F)

Settings Seconds Seconds % % O/ C O/C nor / inv Resp. Units Keylock

URV

URV

Value (PV) URV =

0 1 2 3 4 5 6 7 8 9 A B C D E F

PV

PV

PV

Default * * * 00 00 75% 25% Disabled Disabled nor * 0

= Min. LRV = Actual

PV

PV

LRV

PV

LRV

for 4 c.q.

URV– LRV

PV

PV

PV

PV

PV

Set to 1 Set to 1 Preset

PV

PV

Rotary Switch Positions – Quick Reference

Selection PV Units Seconds Seconds % % mA mA Numeri-

to 0.01

MODE

MODE

MODE

Menu LEVEL 0 (00 to OF)

22 or 3.6 mA

Set FAULT:

Set FAULT:

for Solid-state Disable Fault

3.6 mA

Set Covered:

Set Covered:

4 to 20 mA (Anl)

00 < – > 100

00 < - > 100

00 < – > 100

do it Toggle Delay

00 < - > 100

% Mode Reset Hi/Lo

Units PV Units Numerical Factory

PV

FAC

FAC

FAC

Units PV Units Num.

NO KEYS

RED (+)

BLUE (–)

NO KEYS

RED (+)

BLUE (–)

Show 265 more labels / short text on this page
URV Value · for 20 mA · Decrease · Value (PV) · Spare Keylock · Increase · Keylock · Decrease · Keylock · Increase · Actual · Level · Level · Level · LRV Value · for 4 mA · Increase · Decrease · Spare — · PV Delta Value · 20 mA · Increase · Decrease · Delta · Delta · PV UPPER limit · Increase · UPPER limit · Decrease · UPPER limit · Preset Upper · Actual (PV) · Spare Transmitter · Read-Out · Transmitter · Read-Out · Transmitter · Read-Out · Transmitter · Read-Out · Limit to · Var 0 · Var 1 · Var 2 · Var 3 · Value LOWER limit · Increase · LOWER limit · Decrease · LOWER limit · Lower Limit to · Actual (PV) · Spare — · cal Numeri- · Damping · Increase · Damping · Decrease · Damping · Value · Value · Step Size · Decrease · Step Size · Operating · Actual · Increase · to 10000 · Normal / · Inverse · Normal / · Inverse · Normal / · Inverse · for Solid-state Toggle · Mode · Step · Size · Solid-state OFF · Fault signal · Fault signal · Fault signal · (Solid-state · Set FAULT = · Solid-state ON · Set FAULT = · 22 mA · Disable · Output) · Loop Current · Set Covered = · Solid-state ON · Set Covered = · Solid-state OFF · Disable Switch · 20 mA (Hi) · 4 mA (Lo) · Set Analog · Range · Status · Solid-state · in mA · Output · tion Transistor · Lower Thresh- · De-Activation · Current signal · Increase · Threshold · Decrease · Lower Thresh- · Preset Lower · Threshold · Point to 25% · Lower Thresh- · old De-Activa- · Increase · Lower Thresh- · Decrease · Lower Thresh- · Preset Lower · Threshold · Point to 25% · Lower · Point · old Point · Switch · old Point · old Point · old · Upper Thresh- · Current signal · Upper Thresh- · Preset Upper · Point to 75% · Upper Thresh- · old Activation · Upper Thresh- · Upper Thresh- · Preset Upper · Point to 75% · Activation · Increase · Upper · Threshold · Decrease · Threshold · Transistor · Switch · Increase · old Point · Decrease · old Point · Threshold · old · Point · old · Point · De-Activation · Current signal · De-Activation · Toggle Delay · Time Delay · Increase · Delay Time · Decrease · Delay Time · Delay Time · Time Delay · Transistor · Switch) · Increase · Delay Time · Decrease · Delay Time · Toggle · Time · Time Delay · Activation · Time Delay · Current sig- · Increase · Delay Time · Decrease · Delay Time · Delay Time · Activation · Transistor · Switch · Increase · Delay Time · Decrease · Delay Time · nal · Toggle · Time · PV Memory · PV Memory · memories to · (factory set- · (factory set- · (factory set- · Highest/ · Lowest · Memory · TVmax Highest · Read-out · to TV0 Lowest · Read-out · actual PV · tings) · tings) · tings) · Step TV0 to · Step TVmax · Set · Show · select PV · variable · Display · Fault code · Invert Sig- · nalling Sta- · check · tus · PV Value · Menu · 00 to 0F · Menu · 10 to 1F · Menu · PV Value · Set Menu · 00 to 0F · Set Menu · 10 to 1F · Show · Menu · or · Fault · Set · Level · Set · Level · Show- · Level · or · Fault · Level · Level · Level · read-out · Up Key- · read-out · Up Key- · Value · Down · Both · Keys · Value · Down · Both · Keys · Key- · Key-
Page 48 of the Siemens Sitrans user manual — Start up using push-button calibration: (overview)
Page 48 · click to enlarge
Page 48

Menu levels 0 and 1

Menu level 00 to 0F is the default start-up setting after power is applied or after a reset. Menu Level 10 through 1F is flagged in the LCD by an left-arrow indicator in the upper left corner of the LCD.

To change from menu 00 to menu 10:

1. Set the rotary switch to 0. 2. Press and hold the BLUE (–) button. 3. While the button is pressed, the display shows : M 10 followed by : SEL 1, indicating that the current menu level is now 10 to 1F: a left-arrow is displayed in the top left corner of the LCD. 4. When the button is released, the LCD displays PV (primary variable): the leftarrow remains visible.

To change from menu 10 to menu 00:

1. Make sure the rotary switch is set to 0. 2. Press and hold the RED (+) button. 3. While the button is pressed, the display shows: M 00 followed by : SEL 0, indicating that the current menu level is 00 to 0F: no left-arrow is displayed in the top left corner of the LCD. 4. When the button is released, the LCD displays PV.

In menu 00 or 10, to see the current menu level selection, briefly press one of the buttons

(less than a second): the current selection is momentarily displayed.

Start Up

  • Notes:
  • Check the menu level when using the rotary switch to select a menu item: the leftarrow in the top left corner of the LCD indicates menu level 1.
  • The rotary switch must be set to 0, in order to change from one menu to the other.
  • Hold the RED (+) or BLUE(–) buttons for longer than the preset delay, or debounce time, when altering a value: the debounce time is generally about a second, but varies from one menu item to another.
  • Keylock level (menu 1F) must be set to 0 (no restrictions) to enable you to change settings.

Start up using push-button calibration: (overview)

  • Check that Keylock level is set to enable calibration
  • If required, change the transmitter variable: select units as pF, units user-defined, or values as percent
  • Calibrate value for 0%
  • Calibrate value for 100%
  • Set display for dynamic PV (primary variable): select values displayed as percent or units
  • SITRANS LC 500 is ready to operate
Page 49 of the Siemens Sitrans user manual — Calibrate the 100% setting (URV - upper range value): menu 0F
Page 49 · click to enlarge
Page 49

Calibration using push-button adjustment

  • Notes:
  • To toggle between menu level 0 and menu level 1, set rotary switch to 0, and use RED (+) or BLUE (–) push-button to select menu.
  • To reset values to factory settings, select menu 12. Press and hold both buttons: the LCD displays do it, followed by FAC A when the buttons are released.
  • For a complete list of menu items, see Appendix A: Menu Groups, page 54.

Reset keylock level if necessary to enable settings to be changed: menu 1F (no change is necessary if the factory setting has not been changed)

1. Select menu 10, then set the rotary switch to F. 2. Use the BLUE (–) push-button to decrease the value to 0: display reads PL 0 (no restrictions).

Reset selection for transmitter variable if necessary to TV0 (units are pF): menu 01 (no change is necessary if the factory setting has not been changed)

1. Select menu 00, then turn the rotary switch to 1. 2. Use the BLUE (–) button to adjust the value to 0: the display reads Pv = 0.

Calibrate the 0% setting (LRV - lower range value): menu 0E

For instruments without a stilling well, the 0% setting needs to be calibrated after the

Start Up

device is installed, and with the tank/vessel empty. Calibration is also sometimes necessary after installing a SITRANS LC 500 fitted with a stilling well, although in most cases the 0% setting is calibrated at the factory.

1. Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0)

a. Bring the product level to the height that corresponds to 0%. b. Set the rotary switch to E (Empty). c. Press both buttons and hold for about 1 second: the 0% point is now set.

Calibrate the 100% setting (URV - upper range value): menu 0F

  • method 1: if it is possible to bring the actual product level to 100%
  • method 2: if the current product level is known, you can calculate the percentage value, and calibrate for full scale in %. The closer the actual level is to 100%, the more accurate this result will be.

Method 1. Set value for 100% (URV): units must be pF, (at Menu 01, Pv = 0)

a. Raise the product level to the height that corresponds to 100% b. Set the rotary switch to F (Full). c. Press both buttons and hold for about 1 second: the 100% point is now set.

Page 50 of the Siemens Sitrans user manual — Start Up
Page 50 · click to enlarge
Page 50

Method 2. Set value for 100% (URV): values must be displayed as percent (at menu 01,

a. Calculate the percentage value of the current level. b. Set rotary switch to 1, and press both buttons to adjust the value to P. c. Set the rotary switch to F (Full). d. Press the RED (+) or BLUE (–) button to increase or decrease the reading on the

LCD until it matches the known (actual) percentage. The push-buttons appear to work in reverse for this function1. You may need to decrease the stepsize value (menu 09) in order to reach the desired value. e. 100% value is set.

Example: Set LRV in capacitance mode, then set menu 01 to Pv = P (percent mode) and immerse the probe in the product (values shown below are arbitrary example values only):

0% ( LRV) =14.20 pF 100% (URV) = 34.20 pF Span = 20 pF Current level = 28.20 pF Change in capacitance = 28.20 – 14.20 = 14 Current percent of span = 14/20 = 70% LCD displays 78.00 (percent)

In this example, to decrease the reading to 70.00, you need to press (+) to increase the span, which will reduce the percentage, until the value reaches 70.00. If the steps are too big you need to change the stepsize (menu 09) to a lower value.

Start Up

Changing stepsize value: menu 09

The factory setting is 1the LCD displays U: 1.0

Set rotary switch to 09, and press BLUE (–) button to reduce stepsize: values range from 0.01 to 1,000.

Example:

LCD displays 78.00 (percent) Known percent of span = 70% Decrease needed is 8, but setting for stepsize is 10: menu 09 set to U: 10. Press BLUE (–) button to reduce stepsize to 1: LCD displays U: 1.0. Return to OF, and decrease value to 70.00 (percent).

You may still need to reduce the stepsize further. If changing the stepsize value has no

apparent effect, press both buttons simultaneously to change the reading to 100%. From there you may adjust it until the correct percentage reading is reached.

1. In capacitance mode, the display for menu 0F shows the actual URV, but in percent mode, when you adjust the reading, you are in fact stepping the capacitance value. As you step the capacitance down, you decrease the range and reduce the span, so the percentage increases in relation to the smaller span. Therefore the (+) and (–) buttons appear to function in reverse.

Pv = P)

Page 51 of the Siemens Sitrans user manual — Start Up
Page 51 · click to enlarge
Page 51

Select capacitance or percent mode for dynamic primary variable (PV):

menu 01

a. To see the value displayed as percent, select menu 01 and press both buttons to

set Pv = P. b. To see the value displayed as pF, select menu 01 and increase or decrease the

value till Pv = 0.

The SITRANS LC 500 is now ready to operate. For a table showing the different functions

available, and the combinations of switch position and button presses used to carry out these functions, see page 41. For a detailed list of menu items, see Appendix A: Menu Groups on page 54.

  • Notes:
  • During normal operation, the 4 and/or 20 mA point can be calibrated at any time.
  • If the difference in the capacitance value between the 4 mA point and the 20 mA point is smaller than the minimum span value (3.3 pF), the new value will not be accepted.
  • To revert to factory settings, select menu 12 and press both buttons: the display will read FAC A.

Start Up

Page 52 of the Siemens Sitrans user manual — Start Up
Page 52 · click to enlarge
Page 52

Calibration using HART

The SITRANS LC 500 transmitter can be calibrated using HART, with a HART

communicator1; a laptop running Simatic PDM, or with the Host system (DCS). The local circumstances determine the manner in which calibration takes place. If the circumstances allow the product to be brought to the 0% and 100% point level, calibration is simple.

  • Notes:
  • Use the arrow keys, up, down, forward and back, to navigate within the menus.
  • Use the back arrow to return to previous screens.

Examples of calibration using a Rosemount 275 hand-held communicator, fitted with the

GENERIC device descriptor:

Example 1

For situations where the level of the product can be easily adjusted to 0 and 100%.

1. Switch on the 275 and request connection with the SITRANS LC 500.

a. Select: Online b. Select: Device setup c. Select: Diag service d. Select: Calibration e. Select: Apply values (Display reads: Loop should be removed from automatic control. Select: Ok) f. Select: 4 mA g. Select: Apply new 4 mA input

Start Up

2. Bring the level of the product to the level which corresponds with 4 mA.

a. Select: Read new value b. Select: Set as 4 mA value: the 4 mA point has now been set. c. Select: 20 mA d. Select: Apply new 20 mA input

3. Bring the level of the product to the level which corresponds with 20 mA.

a. Select: Read new value b. Select: Set as 20 mA value: the 20 mA point has now been set. c. Select: Exit

(Display readsLoop may be returned to automatic control. Select: Ok)

Calibration is complete.

1. For a diagram showing how to connect the HART communicator, see Typical PLC configuration with HART on page 32.
Page 53 of the Siemens Sitrans user manual — Start Up
Page 53 · click to enlarge
Page 53

Example 2

For situations where the capacitance values are known in advance.

1. Switch on the 275 and establish connection with the SITRANS LC 500.

a. Select: Online b. Select: Device setup c. Select: Diag service d. Select: Calibration e. Select: Enter values f. Select: PV LRV

2. Enter required capacitance value for 0% of the range.
a. SelectPV URV
3. Enter required capacitance value for 100% of the range.

a. Select: Send (the values are now sent) b. Select: Put loop in manual c. Select: Return loop to auto

Example 3

For situations where the capacitance values are unknown, and the level of the product

cannot be easily adjusted to 0% and 100%. In this case it is necessary to measure the capacitance value at various levels. These values can be read in % with the 275 communicator.

Start Up

1. Switch on the 275 and establish connection with the SITRANS LC 500.

a. Select: Online b. Select: PV c. The measured value can be read continuously, even if the current loop value is

min. or max.

2. Write down the measured value in pF, and record the corresponding level.

Example:

  • the measured PV value is 181 pF at 79%
  • the measured PV value is 52 pF at 17%

(181– 52)pF = 2.08 pF per %.

(79 – 17)%

Page 54 of the Siemens Sitrans user manual — Number Description
Page 54 · click to enlarge
Page 54

The capacitance value for a 17% change in level is 17 * 2.08 = 35.37 pF.

The capacitance value for 0% is 52 – 35.37 = 16.62 pF (initial capacitance value).

The capacitance value for 100% is (100 * 2.08) + 16.62 = 208 + 16.62 = 224.6 pF.

3. Enter the calculated values for 0% and 100%, to calibrate the SITRANS LC 500 as

described in Example 2.

Example 4

For situations involving the re-adjustment of the LRV where the actual value is

determined to be one value but the measurement shows a different value.

1. Switch on the 275 and establish connection with the SITRANS LC 500.
a. SelectOnline
b. SelectPV

The measured value can now be read continuously.

2. Write down the measured value in pF: assume it is 80 pF.

Example: Assume that the URV is set to 240 pF, that the actual value is 17%, but the

measurement is showing a different value.

the measured value = 80 pF

(100 – 17) % = 83%

Start Up

(240 – 80) pF = 60 pF

160 pF = 1.927 pF per % 83%

The capacitance value for 100% (URV) is 100 * 1.927 = 192.7pF

The new LRV should be 240 –192.7 = 47.22 pF.

3. Adjust URV and LRV by following the steps in Example 2.

If the DCS and/or the 275 are fitted with the Device Descriptor for the SITRANS LC 500,

more functions can be used.

The available functions are:

Number Description

(48) Read Additional Transmitter Status

(38) Reset Configuration Changed Flag

(128) Set Alarm Select

(129) Adjust for Product Build-up on Sensor

Page 55 of the Siemens Sitrans user manual — Start Up
Page 55 · click to enlarge
Page 55

Number Description

(130) Read Failsafe Mode selection

(131) Return device configuration info

(132) Set Variable Upper Limit

(133) Set Variable Lower Limit

(134) Write keylock value

(135) Read keylock value

(138) Write simulation time and value

(139) Read simulation time and value

(140) Write TV1 Units, URV and LRV

(141) Read TV1 Units, URV and LRV

(144) Reset Max/Min recorded PV

(145) Read Max/Min recorded PV

(150) Write analog signalling mode

(151) Read analog signalling mode

(152) Write digital signalling mode

(153) Read digital signalling mode

(154) Write analog threshold settings

(155) Read analog threshold settings

(156) Write digital threshold settings

(157) Read digital threshold settings

(160) Write timers analog signalling

(161) Read timers analog signalling

Start Up

(162) Write timers digital signalling

(163) Read timers digital signalling

Page 56 of the Siemens Sitrans user manual — Maintenance
Page 56 · click to enlarge
Page 56

Maintenance

Test function

Auto Self-testing

SITRANS LC 500 continuously performs a variety of tests to verify that the device is

functioning correctly. These include a test where a known capacitor is applied to the input of the device. The internal results must match the known capacitance value. If a deviation is detected the Fault/Failure can be flagged with a pre-set loop-current (user configurable) and as a status in each HART message.

Manual testing

In order to test the proper processing of signals in PLC/DCS equipment, SITRANS LC 500

allows you to invert the output signal status. In Menu 11, when both buttons are pressed simultaneously, the signal outputs switch to their opposite state. When the buttons are released, the outputs revert to the initial state.

If no Fault/Failure is present and no buttons are pressed, the display for menu 11

alternates between two test patterns which together illuminate all the segments of the display. If the loop-current control is in analog mode the loop current will hold the last value, during this test.

Inspections

Under normal circumstances, the SITRANS LC 500 transmitter requires no maintenance.

However, we recommend that you schedule periodic inspections of SITRANS LC 500.

The inspection can be subdivided into two parts:

Maintenance

1. Visual Inspection: confirm the following conditions:

a. Inside enclosure is clean and dry.

b. Enclosure sealing is intact and functioning properly (not hardened).

c. All screw connections are tight.

d. Ground connections inside the housing are solid.

e. Ground connections outside the housing are solid.

Page 57 of the Siemens Sitrans user manual — Maintenance
Page 57 · click to enlarge
Page 57

f. The coaxial connector is free of dirt or deposits.

g. No cables or wires are jammed under the cover.

2. Functional Checks

a. Check for required minimum terminal voltage (see page 23 for supply voltage

requirements).

b. Confirm that Menu 08 is set to enable analog fault signalling: display should read

F: Hi or F: Lo. (If there is a fault condition, it will read F= Hi or F= Lo, when buttons are released.)

c. Check that the current goes to the alarm position (3.6 or 22 mA) if the coaxial

plug is unplugged: at menu 00, the LCD should display ‘ooL’. After the test, replace the coaxial plug.

d. Confirm that Menu 18 is set to enable digital fault signalling: the LCD should

display F= cc or F= co, when buttons are released.

e. Check that the solid-state output goes to the alarm position (open/close) if the

coaxial plug is unplugged. After the test, replace the plug.

f. Via HART: Check that the PV goes to 0 pF when the coaxial plug is unplugged, (±0.15 pF is allowed). If it does, switch the output current to 4 mA and check the current through the loop, then to 20 mA and check the current through the loop. After the test, replace the plug.

Maintenance

Page 58 of the Siemens Sitrans user manual — Troubleshooting
Page 58 · click to enlarge
Page 58

Troubleshooting: SITRANS LC 500

If you are unable to change settings:

  • check that keylock level (menu 1F) is set to 0: the display should read PL = 0
  • check that menu 01 is set appropriately: if Pv = 1, changes can only be made via HART

If you can change settings:

  • reset menu 12 to factory settings: press both buttons, and the display should read FAC A

If the LCD displays a negative reading, typically around minus 300 pF, this often indicates a short circuit in the probe assembly:

  • check the enclosure and make sure no water has got in
  • check that all the connections in the probe assembly are solid

Troubleshooting

Page 59 of the Siemens Sitrans user manual — Troubleshooting
Page 59 · click to enlarge
Page 59

Error Messages and Error Codes

Error Messages (push-button operation)

Error Message Description Cause

  • Device is faulty
  • Possible short circuit in the probe or the device wiring
  • Possible fault in the device, or lack of sufficient energy at the device terminals

Fault/failure has been detected

The product level has risen above the Upper Sensor LImit, or fallen below the Lower Sensor Limit

ooLa Output out-of-limits

a. Alternates with the primary variable (PV).

Error Codes (HART)

Error Code Description Cause

32 program memory checksum error Device is faulty

16 signal errorthe measurement circuitry stopped functioning

Possible short circuit in the probe or the device wiring

8 DAC drive failure: the current as set by the DAC does not match the value measured by the ADC

Possible fault in the device, or lack of sufficient energy at the device terminals

Usually indicates a fault in the connection between the transmitter module and the probe (the coaxial connector is off)

0 PV value is outside the limits set (USL and LSL)

Troubleshooting

Flta

Page 60 of the Siemens Sitrans user manual — Miscellaneous
Page 60 · click to enlarge
Page 60

Appendix A: Menu Groups

Appendix A

The data in the transmitter is accessible as 281 menu items divided between two menu levels: 00 to 0F and 10 to 1F. You can switch between the two levels at position 00 and 10.

The menu items are grouped according to function, with a detailed description of each item. The menu groups are shown below.

Transmitter – Variable Settings

Damping Lower Sensor Limit

Menu 09 Menu 0A Menu 0B Menu 0C Menu 0D Menu 0E Menu 0F

s e e p a g e 5 5 s e e p a g e 5 6 s e e p a g e 5 6 s e e p a g e 5 7 s e e p a g e 5 7 s e e p a g e 5 8 s e e p a g e 5 9

Transmitter – Variable Values

Dynamic ValuePrimary Variable (PV)

Highest Lowest Recorded Value

– select for PV

Menus 00 and 10 Menu 02 Menu 01 Menu 1C

see page 59 see page 60 see page 60 see page 61

Analog Output Signalling (loop current)

Menu 03 Menu 04 Menu 05 Menu 06 Menu 07 Menu 08

see page 62 see page 62 see page 63 see page 64 see page 64 see page 66

Digital Output Signalling (solid-state output)

Menu 13 Menu 14 Menu 15 Menu 16 Menu 17 Menu 18

see page 67 see page 68 see page 68 see page 69 see page 70 see page 71

Miscellaneous

Output Signal Processing Test Factory Settings Range Inversion Keylock Level

Menu 11 Menu 12 Menu 19 Menu 1F

see page 72 see page 72 see page 73 see page 73

1. Only 28 of the possible 32 items are currently used.
Show 37 more labels / short text on this page
Stepsize · Lower Range · Upper Range · Upper Sensor Limit · Delta Range · Update · Setting · Value · Value · Value · Transmitter Variable · Transmitter Variables · Dynamic Value · Upper Threshold · Lower Threshold · Upper Threshold · Lower Threshold · Analog Signalling · Analog · Fault Signalling · Delay · Delay · Setting · Setting · Mode · Upper Threshold · Lower Threshold · Upper Threshold · Lower Threshold · Digital Signalling · Digital · Fault Signalling · Delay · Delay · Setting · Setting · Mode
Page 61 of the Siemens Sitrans user manual — Rotary Switch Position
Page 61 · click to enlarge
Page 61

Menu Items

  • Notes:
  • Check that you are at the correct menu level before selecting a menu item.
  • Hold the RED or BLUE buttons for longer than the preset delay, or debounce time to change a setting: this debounce time is generally around a second, but varies from one menu item to another.
  • Protection is set at keylock level, menu 1F: make sure the setting is appropriate.
  • The transmitter variable, units as pF, units user-defined, or values as percent, is set at menu 01; make sure the setting is appropriate.
  • Reset to factory settings at menu 12: factory settings are indicated with an asterisk in the tables, unless explicitly described.

Appendix A

Transmitter: Variable Settings: menu level 0

  • Notes:
  • You must select menu level 0 before you can access the items at that level.
  • The transmitter variable must be set for units in pF to enable settings to be changed by push-button adjustment: (menu 01 must be set to PV = 0).

Stepsize Update Value

This menu selection controls the increment/decrement step-size for the menus 0B, 0C, 0D, 0E, 0F, and 03.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Description Values

09 01 9 Off Stepsize Update Value Range: 0.01 to 1000

Factory setting U1.0
1. Set the rotary switch to 9. 2. Press the RED (+) or BLUE (–) button to increase or decrease this value in decades: you can step the value up to 10, 100, and 1000 (1E3), or down to 0.1 and 0.01. 3. Press and hold both buttons simultaneously to restore the value to U:1.0
Page 62 of the Siemens Sitrans user manual — Rotary Switch Position
Page 62 · click to enlarge
Page 62

Damping

Damping slows the measurement response to a change in level, and is used to stabilize the reading1. The Damping Value is not in seconds but is a factor that controls the rate of change for the dynamic value of the TV currently selected.

Appendix A

The increment/decrement step size is subject to the setting on Menu 09.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Description Values

0A 01, 09 A Off Damping Range: 1 to 10,000

Factory setting 1.00

1. Set the rotary switch to A. 2. Press the RED (+) or the BLUE (–) button to alter the value between 1 and 10,000. or: Press and hold a button to start a repeat function, or: Press and hold both buttons simultaneously to reset the value back to 1.00.

Lower Sensor Limit

The Lower Sensor Limit (LSL) is the lower of two limit settings. Whenever the PV value (Menu level 0) drops below the Lower Sensor Limit, the measurement is considered at fault and the LCD displays ooL, alternating with PV.

If the display mode is in %, this selection is disabled and the LCD displays -. The transmitter variable on which this menu selection operates is chosen in Menu 01.

The increment/decrement step size is subject to the setting from Menu 09.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Description Values

0B 01, 09 B Off Lower Sensor Limit Range 0 to 3300

Factory setting 1.66

1. Set the rotary switch to B. 2. Press the RED (+) or BLUE (–) buttons to alter this value. or: Press and hold a button to start a repeat function, or: Press and hold both buttons simultaneously to take the current PV reading as the new setting.
1. For example, in an application with an agitated surface.
Page 63 of the Siemens Sitrans user manual — Delta Range Setting
Page 63 · click to enlarge
Page 63

Upper Sensor Limit

The Upper Sensor Limit (USL) is the upper of two limit settings. Whenever the PV value (Menu Level 0) rises above the upper limit setting, the measurement is considered at fault and the LCD displays ooL, alternating with PV.

Appendix A

If the display mode is in %, this selection is disabled and the LCD displays -. The transmitter variable on which this menu selection operates is chosen in Menu 01.

The increment/decrement step size is subject to the setting from Menu 09.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Description Values

0C 01, 09 C Off Upper Sensor Limit 3300 to 0

1. Set the rotary switch to C. 2. Press the RED (+) or BLUE (–) button to increase or decrease this value. or: Press and hold a button to start a repeat function. or: Press and hold both buttons simultaneously to take the current PV reading as the new setting.

Delta Range Setting

The Delta Range Setting allows you to commission the unit for overfill or underfill protection where it is impossible to bring the product to those levels in normal process conditions. This feature is not normally used for the SITRANS LC 500.

Overfill protection is used in applications where the probe is normally uncovered. Delta Range Setting adds the minimum span to the Lower Range Value: the result is used to update the Upper Range Value. If the process level exceeds the new URV, a fault is signalled.

Underfill protection would be used in applications where the probe is normally covered. In this case, Delta Range Setting subtracts the minimum span from the Upper Range Value and uses the result to update the Lower Range Value. If the process value drops below the new LRV, a fault is signalled.

The loop-current control must be in 2-state mode (Menu 07) for Menu 0D to display the Delta Range Setting. When the loop-current control is in Analog mode, Menu 0D displays -.

Factory setting 3300

Page 64 of the Siemens Sitrans user manual — Rotary Switch Position
Page 64 · click to enlarge
Page 64

The transmitter variable on which this selection is based is chosen in Menu 01. The increment/decrement step size is set at Menu 09.

Rotary Switch Position

Appendix A

Menu Item

Affected by:

Left Arrow Mode Description Values

2-state Delta Range Setting (enabled)

0D 01, 07, 09 D Off

Analog * Display shows -

Lower Range Value

Lower Range Value (LRV) is the setting for 0% of the operating range, in most cases an empty vessel/tank. If the display mode is in % this selection is disabled and the LCD displays -.

The transmitter variable on which this menu selection operates is chosen in Menu 01. For TV0 the LRV is in most cases Factory Set to the probe capacitance in free air.

The increment/decrement step size is subject to the setting from Menu 09.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Description Values

Lower Range Value Range0.00 to 3300

Factory setting Probe capacitance in air

0E 01, 09, 0B, 0C E Off Analog

Display percent Display shows -

1. Set the rotary switch to E. 2. Press and hold both buttons simultaneously to take the current PV reading as the new setting. or: Press the RED (+) or BLUE (–) button to step the value up or down. or: Press and hold a button for a prolonged time to start a repeat function.

When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value is rejected and the previous value remains unchanged.

Span setting

Page 65 of the Siemens Sitrans user manual — Dynamic Value, Primary Variable (PV): menu 00 and menu 10
Page 65 · click to enlarge
Page 65

Upper Range Value

Upper Range Value (URV) is the setting for 100% of the operating range, in most cases a full vessel/tank. The transmitter variable on which this menu selection operates is chosen in Menu 01. For TV0, the URV is in most cases Factory Set to the probe capacitance in water.

Appendix A

The increment/decrement step size is subject to the setting from Menu 09.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Description Values

Upper Range Value Range3300 to

0F 01, 09, 0B, 0C F Off Analog

Factory setting Probe capaci- tance in water

Display percent Display shows -

1. Set the rotary switch to F. 2. Press and hold both buttons simultaneously to take the current PV reading as the new setting. or: Press the RED (+) or BLUE(–) button to step this value up or down. or: Press and hold a button for a prolonged time to start a repeat function.

When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value is rejected, and the previous value remains unchanged.

Transmitter Variable Values: menu level 0

Dynamic Value, Primary Variable (PV): menu 00 and menu 10

The value for the Primary Variable is displayed as either units or percent of range, selected in menu 01. When 2-state mode is selected in menu 07 the LCD display indicates the probe status:

  • blinking for an uncovered probe
  • steady for a covered probe

If the internal diagnostics detect a fault or failure, the display alternates between the PV value and the fault/failure message ‘Flt’. If the product level goes outside the limit settings, then the display alternates between the PV value and ‘ooL’. Alternatively, if the simulation

Page 66 of the Siemens Sitrans user manual — Rotary Switch Position
Page 66 · click to enlarge
Page 66

(SIM) function has been selected via HART, the LCD alternately displays the text SIM or the applied simulation value for the duration of the simulation.

Rotary Switch Position

Appendix A

Menu Item

Affected by:

Left Arrow Description Values

00 01 0 Off Dynamic Value (PV) Units or % of range, selected in menu 01 10 On

To change from menu 10 to menu 00:

1. Set the rotary switch to 0. 2. Press the RED (+) button for about a second. The LCD briefly displays : M 00 followed by : SEL 0, to indicate that menu 00 is selected. When the button is released the LCD displays the current PV value. No left-arrow is displayed at the top left corner of the LCD in menu 00.

To change from menu 00 to menu 10:

1. Set the rotary switch to 0. 2. Press the BLUE button for more than one second. The LCD briefly displays : M 10 followed by : SEL1, to indicate that menu level 1 is selected. Then the LCD displays PV, and a left-arrow is visible in the top left corner of the LCD, indicating menu level 1.

Display the Highest / Lowest Recorded Value

Rotary Switch Position

Menu Item

Left Arrow Description

02 2 Off Highest / Lowest Recorded Value

1. Set the rotary switch to 2. The Highest / Lowest recorded values for TV currently selected are displayed alternately. 2. Press the RED (+) button to select the Highest recorded value for display, or: Press the BLUE (–) button to select the Lowest recorded value for display, 3. Press both buttons simultaneously for more than one second to reset the recorded values back to the dynamic value of this TV. (This will also occur after a reset [power-down] of the device.)

Select the Transmitter Variable (TV) for the Primary Variable (PV).

Rotary Switch Position

Menu Item

Left Arrow Description Values

0 * TVO (units are pF)

01 1 Off Transmitter Variable selection for PV

1 TV1 (units are user definable

P TV0 (values displayed as %)

only via HART)

Page 67 of the Siemens Sitrans user manual — TV3 2
Page 67 · click to enlarge
Page 67
1. Set the rotary switch to 1. The LCD displays Pv = 0, 1, or P. 2. Press the RED (+) or BLUE (–) button to select a higher or lower value. 3. Press both buttons to select Pv = P.

Appendix A

  • Notes:
  • When PV is set to 1, settings cannot be changed using push-button adjustment.
  • Many settings cannot be changed using push-button calibration when PV = P.

If PV = 0, TV0 is selected for PV, URV, LRV, USL, LSL, Damping, and Highest/Lowest

recorded value. The units are implicitly1 pF.

If PV = 1, TV1 is selected for PV, URV, LRV, USL, LSL, Damping, and Highest/Lowest

recorded value. The units are user definable but only by HART.

If PV = P, TV0 is selected: however, the values for PV and URV are displayed in %; LRV,

USL, LSL, are blanked out with -; all other fields are identical to that of TV0.

Transmitter Variables Dynamic Value: menu level 1

This menu selection allows you to read the values of the dynamic variables TV0, TV1, TV22, and TV3. When no buttons are pressed, the LCD displays the dynamic value for TV0.

Rotary Switch Position

Menu Item

Left Arrow Mode Description Action Values

TV0 * Transmitter Variables Dynamic Value

Dynamic value for TV0

Transmitter Variables Dynamic Value

Dynamic value for TV1

TV1

Press and hold RED (+) button

Transmitter Variables Dynamic Value

Dynamic value for TV2

TV2 2

Press and hold BLUE(–) button

Transmitter Variables Dynamic Value

Both buttons pressed simultaneously

Dynamic value for TV3

TV3 2

Display shows 0.00

1. The units are pF: there is no other option.
2. TV2 and TV3 are not currently used, but are available for future development.

No buttons pressed · 1C C On · Invalid selection

Page 68 of the Siemens Sitrans user manual — Lower Threshold Delay (2-state mode)
Page 68 · click to enlarge
Page 68

Analog Output Signalling (proportional or 2-state): menu level 0

Analog mode (the loop-current) can provide either:

Appendix A

  • a 4 to 20 / 20 to 4 mA output proportional to the percent of the range or
  • a 4 or 20 / 20 or 4 mA output, when 2-state mode is selected

Upper Threshold Delay (2-state mode)

The Upper Threshold Setting controls the Activation delay: the amount of time that has to pass uninterrupted with the probe covered to a level above the Upper Threshold Setting before the timer expires. When the timer expires, the output signal complies with the setting from Menu 08 for a covered probe. Whenever the level drops below the Upper Threshold Setting before the timer expires, the timer is restarted.

As an extra identifier, an upward running A is displayed to the right of the value.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Added Indicator Description Values

Upward running A at right of value

03 07 3 Off

Display shows -

1. Set the loop-current control (Menu 07) to 2-state mode. 2. Set the rotary switch to 3. 3. Press the RED (+) or BLUE(–) button to increase or decrease the value. or: Press and hold a button to start a repeat function. or: Press and hold both buttons simultaneously to toggle the value between minimum (0) and maximum (100).

Lower Threshold Delay (2-state mode)

The Lower Threshold Setting controls the Deactivation delay: the amount of time that has to pass uninterrupted with the probe covered to a level below the Lower Threshold Setting before the timer expires. When the timer expires, the output signal will comply with the setting from Menu 08 for an uncovered probe. Whenever the level rises above the Lower Threshold Setting before the timer expires, the timer is restarted.

As an extra identifier, a downward running A is displayed to the right of the value..

Show 4 more labels / short text on this page
Upper Threshold Delay · 2- state · in seconds · Analog *
Page 69 of the Siemens Sitrans user manual — Rotary Switch Position
Page 69 · click to enlarge
Page 69

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Added Indicator Description Values

Appendix A

Downward running A at right of value

04 07 4 Off

Ana- log * Display shows -

1. Set the loop-current control (Menu 07) to 2-state mode. 2. Set the rotary switch to 4. 3. Press the RED (+) or BLUE(–) buttons to increase or decrease the value. or: Press and hold a button to start a repeat function. or: Press and hold both buttons simultaneously to toggle the value between minimum (0) and maximum (100).

Upper Threshold Setting (2-state mode)

The Upper Threshold Setting is the % of range above which the probe is considered covered. In order to switch the output signal, the corresponding delay time has to be met (Menu 03).

The loop-current control (Menu 07) must be in 2-state mode for this menu to display the Upper Threshold Setting in percent. As an extra identifier, an upward ramp is displayed to the right of the value.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Added Indicator Description Values

2-state Upward ramp at right of value

05 07 5 Off

Display shows -

1. Set the loop-current control (Menu 07) to 2-state mode. 2. Set the rotary switch to 5. 3. Press the RED (+) or BLUE (–) button to increase or decrease the value. or: Press and hold a button to start a repeat function.
Show 6 more labels / short text on this page
Lower Threshold Delay · 2- state · in seconds · Upper Threshold Setting · % of range · Analog *
Page 70 of the Siemens Sitrans user manual — Analog Signalling Mode ( 2-state): menu level 0
Page 70 · click to enlarge
Page 70

Lower Threshold Setting (2-state mode)

The Lower Threshold Setting is the % of range below which the probe is considered uncovered. In order to switch the output signal, the corresponding delay time has to be met (Menu 04).

Appendix A

The loop-current control (Menu 07) must be in 2-state mode for this menu to display the Upper Threshold Setting in percent. As an extra identifier, a downward ramp is displayed to the right of the value.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Added Indicator Description Values

2-state Downward ramp at right of value

06 07 6 Off

Display shows -

1. Set the loop-current control (Menu 07) to 2-state mode. 2. Set the rotary switch to 6. 3. Press the RED (+) or BLUE (–) button to increase or decrease the value. or: Press and hold a button to start a repeat function.

Analog Signalling Mode ( 2-state): menu level 0

The factory setting is for Analog mode (the loop-current is proportional with the percentage of the range). When no buttons are pressed, the LCD displays the current mA value.

2-state Signalling Mode provides a 4 mA or 20 mA output. The settings are relative to a covered probe:

  • C: Hi selects a 20 mA signal for a covered probe, which switches to 4 mA if the probe becomes uncovered.
  • C: Lo selects a 4 mA signal for a covered probe, which switches to 20 mA if the probe becomes uncovered.

Lower Threshold Setting · % of range · Analog *

Page 71 of the Siemens Sitrans user manual — Rotary Switch Position
Page 71 · click to enlarge
Page 71

Menu selections 03, 04, 05, and 06 set the criteria for delay and threshold that have to be met for a change in output signal.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Description Action Values

Appendix A

Signal propor- tional to % of range

Press both buttons simul- taneously

Display shows CAn
Display shows CHi a

07 03, 04, 05, 06, 08 7 Off

2-state High Press RED (+)

Display shows CLo b

2-state Low Press BLUE (–)

a. While button is pressed, display reads C: Hi. When button is released, display shows 20.00 if the probe is covered, or 4.00 if it is uncovered.

b. While button is pressed, display reads C: Lo. When button is released, display shows 4.00 if the probe is covered, or 20.00 if it is uncovered.

Set the rotary switch to 7. To change the mode to 2-state High, press the RED (+) button for more than one second: the LCD displays C: Hi. When the button is released, the loop- current will switch to 20 mA if the probe is covered, or 4 mA if it is uncovered.

To change the mode to 2-state Low, press the BLUE (–) button for more than one second: the LCD displays C: Lo. When the button is released, the loop-current will switch to 4 mA, and if the probe is uncovered, or 20 mA if the probe is covered.

Analog Mode may be restored at any time by pressing both buttons simultaneously for more than one second. The LCD displays C: An while the two buttons are pressed, and displays the current reading when the buttons are released.

The loop-current will be between 3.8 and 20.5 mA, and will saturate to one of these values if the level goes beyond the Upper or Lower range settings.

Analog * · 2- state

Page 72 of the Siemens Sitrans user manual — Rotary Switch Position
Page 72 · click to enlarge
Page 72

Analog Fault Signalling (2-state)

  • Note:
  • 2-state mode must be selected at menu 07.
  • This menu selection controls the current-loop fault/failure signal output. This signal has precedence over the settings on Menu 07.

Appendix A

When 2-state fault signalling is enabled, in the case of a fault the mA output is 3.6 mA or 22 mA1, depending on the setting. The mA output is viewed at menu 07.

Rotary Switch Position

Menu Item

Left Arrow Description Action Values

2-state Fault Signalling (disabled) * Press both buttons simultaneously

Display shows F- -

2-state High Fault Sig- nalling (enabled) Press RED (+)

Display shows FHi a
Display shows FLo

2-state Low Fault Signal- ling (enabled) Press BLUE (–)

a. If the LCD displays an equal sign (=) in place of the colon (:) this indicates that the loop-current is at fault/failure level. For example F: Hi becomes F= Hi.

Set the rotary switch to 8.

  • To change the mode to 2-state High, press the RED (+) button for more than a second: the display reads F: Hi. In the case of a fault/failure the loop-current goes to 22.0 mA.
  • To change the mode to 2-state Low, press the BLUE (–) button for more than a second: the display reads F: Lo. In the case of a fault/failure the loop-current goes to 3.6 mA.
1. For detailed information, see Fault Signalling on page 15.

08 8 Off

Page 73 of the Siemens Sitrans user manual — Rotary Switch Position
Page 73 · click to enlarge
Page 73

Digital Output Signalling (solid-state output): menu level 1

To set values for Upper and Lower Threshold Delay, and Upper and Lower Threshold Setting, the solid-state switch output must be enabled (menu 17). When solid-state switch output is disabled these menu selections display only -.

Appendix A

Upper Threshold Delay (solid-state output)

The Upper Threshold Delay controls the Activation delay: the amount of time that has to pass uninterrupted with the probe covered to a level above the Upper Threshold Setting before the timer expires. After the timer expires, the output signal will comply to the setting from Menu 18 for a covered probe. Whenever the level drops below the Upper Threshold Setting before the timer expires, the timer is restarted.

When the solid-state switch control (Menu 17) is disabled, menu 13 displays -. When the solid-state switch control is enabled, menu 13 displays the Activation delay in seconds. As an extra identifier, an upward running d is displayed to the right of the value.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Identifier Description Values

Solid-state switch con- trol enabled

Upward running d at right of value

Range0 to 100 (seconds)

13 17 3 On

Display shows -

Solid-state switch con- trol disabled

First select the solid-state switch output at menu 17 (contact open or contact closed).

1. Set the rotary switch to 3. 2. Press the RED (+) or BLUE (–) button to increase or decrease the value. or: Press and hold a button to start a repeat function. or: Press both buttons simultaneously to toggle the value between minimum (0) and maximum (100).

Upper Threshold Delay · *

Page 74 of the Siemens Sitrans user manual — Upper Threshold Setting: (solid-state output)
Page 74 · click to enlarge
Page 74

Lower Threshold Delay (solid-state output)

The Lower Threshold Delay controls the Deactivation delay: the amount of time that has to pass uninterrupted with the probe covered to a level below the Lower Threshold Setting before the timer expires. After the timer expires, the output signal will comply to the setting from Menu 18 for an uncovered probe. Whenever the level rises above the Lower Threshold Setting before the timer expires, the timer is restarted.

Appendix A

When the solid-state switch control (Menu 17) is disabled, menu 14 displays only -. When the solid-state switch control is enabled, this menu displays the Deactivation delay in seconds. As an extra identifier, a downward running d is displayed to the right of the value.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Identifier Description Values

Solid-state switch con- trol enabled

Downward running d at right of value

Range0 to 100 (seconds)

14 17 4 On

Solid-state switch con- trol disabled

* Display shows -

First select the solid-state switch output at menu 17 (contact open or contact closed).

1. Set the rotary switch to 4. 2. Press the RED (+) or BLUE(–) button to increase or decrease the value. 3. or: Press and hold a button to start a repeat function. 4. or: Press both buttons simultaneously to toggle the value between minimum (0) and maximum (100).

Upper Threshold Setting: (solid-state output)

The Upper Threshold Setting is the % of range above which the probe is considered covered. In order to switch the output signal, the corresponding delay time has to be met (Menu 13).

When the solid-state switch control (Menu 17) is disabled, menu 15 displays only -. When the solid-state switch control is enabled, menu 15 displays the Upper Threshold setting in percent. As an extra identifier, an upward ramp is displayed to the right of the value.

Lower Threshold Delay

Page 75 of the Siemens Sitrans user manual — Rotary Switch Position
Page 75 · click to enlarge
Page 75

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Identifier Des-

cription Values

Appendix A

Solid-state switch con- trol enabled

Upward ramp at right of value

15 17 5 On

Solid-state switch con- trol disabled

* Display shows -

First select the solid-state switch output at menu 17 (contact open or contact closed).

1. Set the rotary switch to 5. 2. Press the RED (+) or BLUE (–) button to increase or decrease the value. or: Press and hold a button for a prolonged time start a repeat function.

Lower Threshold Setting: (solid-state output)

The Lower Threshold Setting is the % of range below which the probe is considered uncovered. In order to switch the output signal, the corresponding delay time has to be met (Menu 14).

If the solid-state switch control (Menu 17) is disabled, menu 16 displays -. When the solid-state switch control is enabled, menu 16 displays the Lower Threshold Setting in percent. As an extra identifier, a downward ramp is displayed to the right of the value.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Added indicator

Description Values

Solid-state switch con- trol enabled

Downward ramp at right of value

16 17 6 On

Solid-state switch con- trol disabled

* Display shows -

First select the solid-state switch output at menu 17 (contact open or contact closed).

1. Set the rotary switch to 6. 2. Press the RED (+) or BLUE (–) button to increase or decrease the value. or: Press and hold a button to start a repeat function.
Show 4 more labels / short text on this page
Upper Threshold Setting · % of range · Lower Threshold Setting · % of range
Page 76 of the Siemens Sitrans user manual — Rotary Switch Position
Page 76 · click to enlarge
Page 76

Digital Signalling Mode (solid-state output)

Appendix A

Controls the solid-state switch output and allows you to set the switch to contact open or contact closed. The settings are relative to a covered probe, and the criteria are set in menu 15 and 16. With contact closed, the switch is on: with contact open the switch is off.

While a button is pressed, the LCD displays S: cc1 (contact closed) or S: co (contact open). When the button is released an equal sign (=) indicating status replaces the colon, and the reading depends on the status of the probe2.

ExampleS = cc is selected (contact closed with a covered probe)
  • If the probe is uncovered when the button is released, the display changes from S: cc to S = co.
  • If the probe is covered when the buttons are released, the display changes to S = cc.
  • If you press either button briefly, the LCD displays the current setting, in this case, S: cc.

Rotary Switch Position

Menu Item

Affected by:

Left Arrow Mode Description Action Values

Disabled * Press and hold both buttons

Display shows S- -
Contact Closedswitch on

Press and hold RED (+) button

17 18 7 On

S: cc

Contact Openswitch off

Press and hold BLUE (–) button

S: co

a. While the button is pressed: when released the display depends on the probe status.

1. Set the rotary switch to 7. 2. Press and hold the RED (+) or BLUE (–) button to select contact open or contact closed. or: Press and hold both buttons to disable this function.

Menu selections 13, 14, 15 and 16 set the criteria for delay and threshold that have to be met for a change in output signal.

1. A colon at the extreme left of the display appears while the button is pressed to indicate when a setting is accepted, for example : S: cc. 2. If digital fault signalling is enabled at menu 18, it takes precedence, and no equal sign will appear in the display for menu 17 if the device is responding to a fault.

Display showsa · Digital Signal- ling Mode · Display showsa

Page 77 of the Siemens Sitrans user manual — Rotary Switch Position
Page 77 · click to enlarge
Page 77

Digital Fault Signalling

Appendix A

Controls the solid-state switch response to a fault/failure and allows you to select either contact open or contact closed. With contact closed the solid-state switch will be on: with contact open the solid-state switch will be off.

While a button is pressed, the LCD displays F: cc1 (contact closed) or F: co (contact open). When the button is released an equal sign (=) indicating status replaces the colon, and the reading depends on the status of the probe.

ExampleF = cc is selected (contact closed when fault is detected)
  • If a fault condition exists when the button is released, the display changes from F: cc to F = cc.
  • If no fault condition exists when the button is released, the display shows F: cc.
  • If you press either button briefly, the LCD displays the current setting, in this case, F: cc.

Rotary Switch Position

Menu Item

Left Arrow Mode Description Action Values

Display shows F- -

Disabled * Press and hold both buttons

Display shows Fcc
Contact Closedswitch on

Press and hold RED (+) button

Contact Openswitch off

Press and hold BLUE (–) button

Display shows Fco

Set the rotary switch to 8. Press the RED (+) or BLUE (–) button to change the setting. The disabled mode can be restored at any time by pressing both buttons simultaneously for more than one second.

1. A colon at the extreme left of the display appears while the button is pressed to indicate when a setting is accepted, for example : S: cc.

18 8 On · Digital Signalling Mode

Page 78 of the Siemens Sitrans user manual — FAC P
Page 78 · click to enlarge
Page 78

Miscellaneous

Output Signal Processing Test

Appendix A

Displays the Fault/Failure information. If operation is normal, two test displays alternate, which light up all the LCD segments in a cycle. If there is a fault or failure, an error code is displayed. See the detailed list of error codes and their meanings, page 53.

Rotary Switch Position

Menu Item

Left Arrow Description

11 1 On Output Signal Processing Test

Set the rotary switch to 1.

To change the state of the output signals, press and hold both buttons simultaneously: the digital mode outputs (the solid-state switch and the loop-current control in digital mode) change to their opposite state. Thus 4mA becomes 20mA and contact open becomes contact closed. This feature allows you to verify that the output signals are properly processed further on in the PLC/DCS system: if the normal state is non-alarm, changing the state should generate an alarm.

The outputs stay in the opposite state as long as both buttons are pressed.

Factory Settings

Displays whether the factory settings are still in place, or how much they have been changed, and allows you to restore the factory settings.

Rotary Switch Position

Menu Item

Left Arrow Description LCD Display Meaning

No parameters changed from factory setting

Factory Settings FAC A

Range settings alteredtimers and thresholds unchanged

FAC P

FAC ? More parameters have been changed

Set the rotary switch to 2. To restore the factory settings, press both buttons simultaneously to change the LCD to ‘do it’ and hold both buttons for more than one second. When the buttons are released, the LCD displays FAC A.

12 2 On

Page 79 of the Siemens Sitrans user manual — Rotary Switch Position
Page 79 · click to enlarge
Page 79

Range Inversion

Displays whether the device is operating with a normal or inverted range setting. A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV (Menu 0F): the LCD displays inv.

Appendix A

Rotary Switch Position

Menu Item

Left Arrow Description Mode Values

19 9 On Range Inversion normal * Display shows nor

inverted Display shows inv

1. Set the rotary switch to 9. 2. Press both buttons simultaneously for more than one second to toggle between the two modes, effectively switching the values for LRV and URV.

Keylock Level

Controls the access protection level for the device. The factory setting is a local protection level of 0, which places no restriction on modifying settings locally.

  • Note: HART settings override local settings:
  • If the HART setting is 0, there are no restrictions, and you cannot change the protection to a higher level locally.
  • If the HART setting is 3, no changes can be made, and this protection level cannot be changed locally.
  • Protection level 1 disables the ability to set a value by pressing two buttons simultaneously.
  • Protection level 2 disables the ability to change a value by stepping it up or down.
  • Protection level 3 completely disables all changing of values.

Rotary Switch Position

Protection Display

Menu

Left Arrow

Item

Level Description local settings

HART settings

0 * No restrictions PL 0

No restrictions PH 0

1 Disables 2-button adjustments PL 1 PH 1

2 Disables 1-button adjustments PL 2 PH 2

3 Disables all changes PL 3 PH 3

1. Set the rotary switch to F. 2. Press the RED (+) or BLUE (–) button to change the setting.

1F F On

Page 80 of the Siemens Sitrans user manual — Lo
Page 80 · click to enlarge
Page 80

Appendix B: LCD display examples

LCD: alphanumeric display examples

Menu Item Indicator:

Current-loop, output in Analog (proportional) mode:

M 00

An

Menu Level Indicator:

Indicator for range operation, normal (URV > LRV):

SEL 1

nor

Internal diagnostics detects anomaly:

Indicator for range operation, inverted (URV < LRV):

Appendix B

FLt

inv

Solid-state switch output closed when probe is covered (displayed while button pressed):

Output out of limits, PV outside Variable Limits:

ooL

S: oc

Solid-state switch output open when probe is covered (displayed while button pressed):

Indicator for Factory Set, all parameters are original:

S: oo

FAC A

Solid-state switch output closed and probe covered, = sign indicates current probe status (displayed when button released):

Indicator for Factory Set, range settings have been changed:

FAC P

S= oc

Indicator for Factory Set, other settings have been changed also:

Solid-state switch output disabled:

S: – –

FAC?

Indicator for Factory Set, reset all variables back to factory setting:

Solid-state switch output open when Fault detected:

F: oo

do it

Solid-state switch output closed when Fault detected:

Function test indicator, all outputs in digital mode invert their output status:

F: oc

0 = /o

Solid-state switch / current-loop output functions due to Faults are disabled:

Transmitter variable selected for PV:

Pv=0

F: – –

Current-loop, current goes to 22 mA when Fault detected:

Keylock protection level:

PL 0

Hi

Simulation is active. Transmitter Variable TVO driven by simulation value:

Current-loop, current goes to 3.6 mA when Fault detected:

Lo

SIM

Page 81 of the Siemens Sitrans user manual — Physical Layer Information
Page 81 · click to enlarge
Page 81

Appendix C: HART Documentation

HART 1 Communications for the SITRANS LC 500

Highway Addressable Remote Transducer (HART) is an industrial protocol that rides on top of a 4-20 mA signal. It is an open standard, and full details about HART can be obtained from the HART Communication Foundation at www.hartcomm.org

The SITRANS LC 500 can be configured over the HART network using either the HART Communicator 275 by Fisher-Rosemount, or a software package. There are a number of different software packages available.The recommended software package is the Simatic Process Device Manager (PDM) by Siemens.

HART Device Descriptor (DD)

In order to configure a HART device, the configurator must have the HART Device Descriptor for the unit in question. HART DD’s are controlled by the HART Communications Foundation. The HART DD for the SITRANS LC 500 will be released in 2003. Please check availability with the HART Communications Foundation. Older versions of the library will have to be updated in order to use all the features in the SITRANS LC 500.

Appendix C

Simatic Process Device Manager (PDM)

This software package is designed to permit easy configuration, monitoring, and troubleshooting of HART and Profibus PA devices. The HART DD for the SITRANS LC 500 was written with Simatic PDM in mind and has been extensively tested with this software.

HART information

Expanded Device Type Code:

Manufacturer Identification Code = 84 Manufacturer Device Type Code = 248 Expanded Device Type Code = 21752

Physical Layer Information

Field Device Category = A Capacitance Number (CN) = 1

1. HART® is a registered trademark of the HART Communications Foundation.
Page 82 of the Siemens Sitrans user manual — Appendix C
Page 82 · click to enlarge
Page 82

SITRANS LC 500 DD Menu/Variable Organization

Root Menu Device Setup Menu Process Variables

Process variables menu Diagnostics/service Basic setup menu Detailed setup menu Autocal Review menu

Sensor digital value Input percent range A0 analog value PV maximum recorded PV minimum recorded Reset max/min records

Applied rerange Keypad rerange Zero correction

PV digital value PV upper range value PV lower range value SV digital value SV upper range value SV lower range value

Self test Loop test Calibration Dac trim

PV upper sensor limit PV lower sensor limit PV minimum span PV sensor units PV Upper range value PV Lower range value

Tag PV digital units Device info menu PV transfer function PV damping value

Damping value Upper range value Lower range value Transfer function Percent range

Measuring elements menu Signal conditioning menu Output conditioning menu Device info menu

PV analog value PV alarm select Dac trim Loop test

High calibration level Low calibration level

Analog output menu Hart output menu

Polling address Request preambles

Review Menu Device Info Menu

Device type Private label distribution PV digital units Sensor units Upper sensor limit Lower sensor limit Minimum span Damping value Input percent range Transfer function Input range units Upper range value Lower range value A0 analog value A0 alarm code Write protect Manufacturer ID Device ID Tag Descriptor Message Date Universal revision Transmitter revision Software revision Polling address Request preambles

Private label distribution Device type Device ID Tag Date Write Protect Descriptor Message PV sensor serial number Final assembly number Device revisions menu

Appendix C

Universal revision Transmitter revision Software revision

Show 12 more labels / short text on this page
Device setup menu · Auto Calibration Menu · Diagnostics/service · Measuring Elements · Basic Setup Menu · Signal Conditioning Menu · Detailed Setup Menu · Analog Output · Autocal Menu · Output Condition Menu · Hart Output Menu · Device Revisions
Page 83 of the Siemens Sitrans user manual — Bit #0: Primary Variable Out of Limits
Page 83 · click to enlarge
Page 83

HART Response Code Information

Additional response code information, Second Byte.

Bit #7: Field Device Malfunction

When the transmitter detects a malfunction, the Analog Output will be set in a fault state.

Bit #6: Configuration Changed

When any of the settings in EEROM is changed either by a write command or by manual ZERO or SPAN adjust, this bit is set. Use command 38 to reset.

Bit #5: Cold Start

This bit is issued once after an initialisation cycle is complete; this can occur after a power loss or as a result of a (watchdog) reset.

Bit #4: Extended Status Available

When any of the extended status bits is set this flag is raised. Use command 48 to get detailed status information.

Bit #3: Output Current Fixed

This bit is set as long as the Primary Variable Analog Output is set to a fixed value.

Appendix C

Bit #2: Primary Variable Analog Output Saturated

Flag is set when the Primary Analog Output saturates below 3.8 mA and above 20.5 mA.

Bit #0: Primary Variable Out of Limits

This flag is set whenever the Transmitter Variable #0 (in pF), the Primary Variable exceeds the Sensor Limits returned with Command 14, Read Primary Variable Sensor Limits.

Page 84 of the Siemens Sitrans user manual — Conformance Class #5
Page 84 · click to enlarge
Page 84

HART Conformance and Command Class

SITRANS LC 500 transmitter Conformance and Command Class summary.

Command

Number Description Usage

Conformance Class #1

0 Return Unique Identifier Universal

1 Read Primary Variable

Conformance Class #1A

0 Return Unique Identifier Universal

2 Read PV Current and Percent of Range

Conformance Class #2

11 Read Unique Identifier Associated with Tag Universal

13 Read Tag, Descriptor, and Date

14 Read Primary Variable Sensor Information

15 Read Primary Variable Output Information

16 Read Final Assembly Number

Conformance Class #3

Appendix C

3 Read Dynamic Variables and PV Current Universal

33 Read Selected Dynamic Variables Common Practice

48 Read Additional Transmitter Status Common Practice

50 Read Dynamic Variable Assignments Common Practice Conformance Class #4

34 Write PV Damping Value Common Practice

35 Write Primary Variable Range Values

36 Set Primary Variable Upper Range Value

37 Set Primary Variable Lower Range Value

38 Reset Configuration Changed Flag

40 Enter/Exit Fixed Primary Var. Current Mode

Conformance Class #5

6 Write Polling Address Universal

18 Write Tag, Descriptor and Date

19 Write Final Assembly Number

44 Write Primary Variable Units Common Practice

45 Trim Primary Variable Current DAC Zero

46 Trim Primary Variable Current DAC Gain

49 Write Primary Variable Sensor Serial Number

59 Write Number of Response Preambles

12 Read Message · 17 Write Message

Page 85 of the Siemens Sitrans user manual — Non-volatile Memory Data Storage
Page 85 · click to enlarge
Page 85

Command

Number Description Usage

128 Set Alarm Select Transmitter Specific

129 Adjust for Product Build-up on Sensor

130 Read Failsafe Mode selection

131 Return Device Config. Info.

132 Write Variable Upper/Lower Limit Values

133 Read Variable Upper/Lower Limit Values

134 Write Keylock Value

135 Read Keylock Value

138 Write Simulation Timer and Value

139 Read Simulation Timer and Value

140 Write S.V. Units and Range Values

141 Read S.V. Unites and Range Values

144 Reset recorded PV min./max. values back to PV

145 Return recorded PV min./max. values

150 Write Analog Signalling Mode

151 Read Analog Signalling Mode

152 Write Digital Signalling Mode

153 Read Digital Signalling Mode

154 Write Analog Threshold Settings

155 Read Analog Threshold Settings

156 Write Digital Threshold Settings

Appendix C

157 Read Digital Threshold Settings

160 Write Delay Timers Analog Signalling

161 Read Delay Timers Analog Signalling

162 Write Delay Timers Digital Signalling

163 Read Delay Timers Digital Signalling

General Transmitter Information

Damping information

The SITRANS LC 500 transmitter implements damping on most of the transmitter variables. The damping setting may vary from 1 (shortest value) to 10000 (longest value).

Non-volatile Memory Data Storage

The flags byte of Command #0 referenced in the Universal Command Specification document will have Bit #1 (Command #39, EEPROM Control Required) set to 0, indicating that all data sent to the transmitter will be saved automatically in the non-volatile memory upon receipt of the Write or Set Command. Command #39, EEPROM Control, is not implemented.

Page 86 of the Siemens Sitrans user manual — Appendix C
Page 86 · click to enlarge
Page 86

MultiDrop operation

The SITRANS LC 500 transmitter supports MultiDrop Operation.

Burst mode

The SITRANS LC 500 transmitter does not support Burst Mode.

Units conversions

The Transmitter Variable #0 Units are in pF and cannot be changed.

The Transmitter Variable #1 Values may be set to any Units and Value with Command #140. The Transmitter Variable Range Values may be read at any time with Command #141.

The value returned as Secondary Variable (S.V.) is the result of the following calculation:

TV1 = TV0 Dynamic Range Value in percent x ({TV#1}URV – {TV#1}LRV) + {TV#1}LRV.

This method provides a means of converting TV#0, which is always in pF, to alternative units (level or volume).

Additional Universal Command Specifications

For a document listing the additional Universal Command Specifications, please contact Technical Publications at techpubs@siemens-milltronics.com

Appendix C

Page 87 of the Siemens Sitrans user manual — Appendix D: Block Diagram, and Correlation table, mA to %
Page 87 · click to enlarge
Page 87
Siemens Sitrans — Appendix D: Block Diagram, and Correlation table, mA to % diagram (page 87)
Fig. 12 · Appendix D: Block Diagram, and Correlation table, mA…

Appendix D: Block Diagram, and Correlation table, mA to %

SITRANS LC 500 Block Diagram Digital Fault/Failure (menu 18)

Page 88 of the Siemens Sitrans user manual — Appendix D
Page 88 · click to enlarge
Page 88

Correlation Table: 0% - 100% to 4-20 mA or 20-4 mA

Range 0 - 100 % Current in mA Range 100 - 0 %

0 4.0 100

5 4.8 95

10 5.6 90

15 6.4 85

20 7.2 80

25 8.0 75

30 8.8 70

35 9.6 65

40 10.4 60

45 11.2 55

50 12.0 50

55 12.8 45

60 13.6 40

65 14.4 35

70 15.2 30

75 16.0 25

80 16.8 20

85 17.6 15

90 18.4 10

95 19.2 5

100 20.0 0

Appendix D

Page 89 of the Siemens Sitrans user manual — Appendix E
Page 89 · click to enlarge
Page 89

Appendix E: SITRANS LC 500, alternate versions and application details

Standard Version

Standard Version S-Series, Threaded

S-Series: Threaded

ø160 (6.3”)

+175 (6.9”)

40 (1.57”)

ø16 (0.63”)

or ø24 (0.94”)

Appendix E

Show 7 more labels / short text on this page
Insertion Length · Active Shield · Insertion · Length · Active Length · Probe Seal · (inactive)
Page 90 of the Siemens Sitrans user manual — Appendix E
Page 90 · click to enlarge
Page 90

Standard Version S-Series, Threaded

S-Series Cable Version

S-Series Cable Version

(with weight)

(with anchor)

ø160 (6.3”)

120 (4.72”)

55 (2.17”)

Length +175 (6.9”)

ø9 (0.35”)

125 (4.9”)

Features: Standard Version S-Series, Threaded

  • single process seal
  • suitable for most level, interface, or detection applications
  • high temperature and pressure resistant

Appendix E

Show 13 more labels / short text on this page
Transmitter Enclosure · Seal Gland · Threaded Process Connector · Insertion · See Order Instructions · Insertion · PFA Insulation · Length · Insertion Length · +/- Varies · Tensile Weight · Dimension · Varies
Page 91 of the Siemens Sitrans user manual — Appendix E
Page 91 · click to enlarge
Page 91

Standard Version S-Series, Welded and Machined Flanged Versions

S-Series, Welded Flange S-Series, Machined Flange

Siemens Sitrans — S-Series, Welded Flange S-Series, Machined Flange diagram (page 91)
Fig. 13 · S-Series, Welded Flange S-Series, Machined Flange
Siemens Sitrans — S-Series, Welded Flange S-Series, Machined Flange diagram (page 91)
Fig. 14 · S-Series, Welded Flange S-Series, Machined Flange

or ø24 (0.94”)

FeaturesStandard Version S-Series, Flanged
  • single process seal
  • suitable for most level, interface, or detection applications
  • high temperature and pressure resistant
Siemens Sitrans — S-Series, Welded Flange S-Series, Machined Flange diagram (page 91)
Fig. 15 · S-Series, Welded Flange S-Series, Machined Flange

Appendix E

Probe Seal · (inactive)

Page 92 of the Siemens Sitrans user manual — Appendix E
Page 92 · click to enlarge
Page 92

Standard Version D-Series, Machined Flange

D-Series DD-Series

Siemens Sitrans — D-Series DD-Series diagram (page 92)
Fig. 16 · D-Series DD-Series

ø16 (0.63”) or ø24 (0.94”) ø16 (0.63”) or ø24 (0.94”)

FeaturesStandard Version D-Series
FeaturesStandard Version DD-Series
  • single process seal
  • all wetted parts made of PFA (probe lining) or PTFE (flange face)
  • according to NACE requirements
  • double process seal
  • redundant safety (e.g. Phenol, Phosgene applications, etc.)
  • all wetted parts made of PFA (probe lining) or PTFE (flange face)
  • according to NACE requirements
  • suitable for turbulent and toxic chemical applications
Siemens Sitrans — D-Series DD-Series diagram (page 92)
Fig. 17 · D-Series DD-Series

Appendix E

Page 93 of the Siemens Sitrans user manual — Appendix E
Page 93 · click to enlarge
Page 93

SD-Series Probe/Thermal Isolator

Siemens Sitrans — SD-Series Probe/Thermal Isolator diagram (page 93)
Fig. 18 · SD-Series Probe/Thermal Isolator
FeaturesStandard Version SD-Series
FeaturesStandard Version, Probe/ Thermal Isolator
  • double process seal
  • redundant safety (e.g. Phenol, Phosgene applications, etc.)
  • all wetted parts made of PFA/ PTFE
  • according to NACE requirements
  • suitable for turbulent and toxic chemical applications
  • thermal isolator (to prevent temperature at the electronics reaching higher than 85 o C)
Siemens Sitrans — SD-Series Probe/Thermal Isolator diagram (page 93)
Fig. 19 · SD-Series Probe/Thermal Isolator

Appendix E

Page 94 of the Siemens Sitrans user manual — Appendix E
Page 94 · click to enlarge
Page 94

Interface Version

Designed specifically for interface level where a long distance active shield portion of the electrode is required (up to 35 meters) before the measurement portion of the electrode begins. Common in large storage tanks for oil where the bottom of the tank invariably has a layer of water below the oil. Often, when measurement spans as much as 5.5 meters (for the water), up to 35 meters of flexible bellows cable are used.

Interface Version, threaded (optional sanitary and flanged)

Siemens Sitrans — Interface Version, threaded (optional sanitary and flanged) diagram (page 94)
Fig. 20 · Interface Version, threaded (optional sanitary and f…
Siemens Sitrans — Interface Version, threaded (optional sanitary and flanged) diagram (page 94)
Fig. 21 · Interface Version, threaded (optional sanitary and f…
process connectionflange or threaded mounting
  • threaded version: ¾", 1", 1½", 2" NPT, BSPT, or JIS
  • sanitary version: on customer request
  • flanged version: on customer request
  • thermal isolator
  • stilling well
  • NEMA 4 / Type 4 / IP65

ø 16 mm (0.63”) or ø 24 mm (0.94”)

Conduit Entry:

  • ½" NPT (2x)

100 mm (3.9”) inactive tip

Siemens Sitrans — Interface Version, threaded (optional sanitary and flanged) diagram (page 94)
Fig. 22 · Interface Version, threaded (optional sanitary and f…

Appendix E

Show 7 more labels / short text on this page
transmitter enclosure · seal gland · Process Connection Size · flexible tube · Options · probe · Aluminum Enclosure
Page 95 of the Siemens Sitrans user manual — Appendix E
Page 95 · click to enlarge
Page 95

Sanitary Version

The hygienic design includes threaded and tri-clamp versions for use in the food and pharmaceutical industry.

Sanitary Versions, threaded and tri-clamp

Sanitary Thread Coupling Sanitary Tri-Clamp

Siemens Sitrans — Sanitary Thread Coupling Sanitary Tri-Clamp diagram (page 95)
Fig. 23 · Sanitary Thread Coupling Sanitary Tri-Clamp
Siemens Sitrans — Sanitary Thread Coupling Sanitary Tri-Clamp diagram (page 95)
Fig. 24 · Sanitary Thread Coupling Sanitary Tri-Clamp

ø16 (0.63”) or

FeaturesSanitary Version, Tri-Clamp
  • maximum active length 5.5 m (18 ft)
  • minimum active length 50 mm (2”)
Siemens Sitrans — Sanitary Thread Coupling Sanitary Tri-Clamp diagram (page 95)
Fig. 25 · Sanitary Thread Coupling Sanitary Tri-Clamp

Appendix E

Show 4 more labels / short text on this page
Transmitter Enclosure · IDF Nut · Probe Seal · (inactive) Probe Seal
Page 96 of the Siemens Sitrans user manual — Appendix E
Page 96 · click to enlarge
Page 96

Flanges

Siemens Sitrans — Flanges diagram (page 96)
Fig. 26 · Flanges

Flange Standards

Siemens Sitrans — Flange Standards diagram (page 96)
Fig. 27 · Flange Standards
  • All measurements are given in mm
  • One (1) inch = 25.4 mm
  • For details, see drawings, technical data, and measuring probe details on pages 83 to 89.
Siemens Sitrans — Flange Standards diagram (page 96)
Fig. 28 · Flange Standards
Siemens Sitrans — Flange Standards diagram (page 96)
Fig. 29 · Flange Standards

Appendix E

Page 97 of the Siemens Sitrans user manual — Appendix E
Page 97 · click to enlarge
Page 97

Applications Examples

Generic Application Calculations

The capacitance expected in a cylindrical tank with a probe centrally mounted is estimated using the following formula:

C ε 24 L × Log D d ⁄ ( ) pF =

C ε 7.32 L × Log D d ⁄ ( ) pF =

(L in meters) or (L in feet)

Where: C = capacitance value in pF ε r = relative dielectric constant L = active measurement length D = internal tank diameter d = electrode diameter 24 = a K constant for dimensions in meters 7.32= a K constant for dimensions in feet or inches ε r = 1 (air) ε r = 2 (oil)

SITRANS LC 500

0.25 m (0.82’)

L = 0.95 m

(3.12’)

d = 16 mm

(0.05’)

D = 1.0 m (3.28’)

Examples (using dimensions above):

Capacitance in air:

24 0.95 × Log 1 0.016 ⁄ ( ) pF 12.7pF = =

Dimensions in meters:

7.32 0.82 × Log 1 0.06 ⁄ ( ) pF 12.7pF = =

Dimensions in feet:

Capacitance in oil:

If the same vessel is filled with oil, relative dielectric constant for oil (2) replaces the relative dielectric constant for air (1), and the resulting calculation is:

24 0.95 × Log 1 0.016 ⁄ ( ) pF 25.4pF = =

7.32 3.12 × Log 3.28 0.05 ⁄ ( ) pF 25.4pF = =

The initial capacitance value at 0% (probe in air) is 12.7 pF, and the capacitance value for 100% (tank filled with oil) is 25.4 pF.

Appendix E

Show 7 more labels / short text on this page
Cair εair · Cair εair · Coil εoil · (dimensions in meters) · or · Coil εoil · (dimensions in feet)
Page 98 of the Siemens Sitrans user manual — Appendix E
Page 98 · click to enlarge
Page 98

After calibration:

12.7 pF ≅ 0% ≅ 4 mA or 20 mA

25.4 pF ≅ 100% ≅ 20 mA or 4 mA

Larger tank, dimensions in feet:

7.32 4.5 × Log 60 0.63 ⁄ ( ) pF 16.6pF = =

SITRANS LC

500 6” (0.5ft)

7.32 4.5 × Log 60 0.63 ⁄ ( ) pF 33.2pF = =

L = 54”

For this slightly larger tank, the capacitance ranges from 16.6 pF for 0% (probe in air) to 33.2 pF for 100% (tank filled with oil).

(4.5ft)

d = 0.63”

After calibration:

16.6 pF ≅ 0% ≅ 4 mA or 20 mA 33.2 pF ≅ 100% ≅ 20 mA or 4 mA

60” (5.0ft)

Appendix E

Cair εair · Coil εoil

Page 99 of the Siemens Sitrans user manual — Appendix E
Page 99 · click to enlarge
Page 99

Application: level indicator and solid-state switch output

  • The loop current provides:
  • a reading proportional to level, within the 0 - 100% range, at menu 00 or 10 on the device, or at a remote indicator
  • an out-of-range signal ooL alternating with PV if the level is above URV or below LRV
  • The solid-state switch is activated at Upper Threshold Setting and deactivated at Lower Threshold Setting. In the diagram below, it is used to activate a pump via an auxiliary power circuit.
  • The activation and deactivation can be modified by Upper and/or Lower Threshold delays (menus 13 and 14).
  • The reading can be stabilized if necessary by applying Damping (menu 0A): the update value for Damping is controlled by menu 09.

Example: The level is to be held between 90% and 8%.

Indicatorprimary variable viewed at menus 00 or 01;

units or% selected in menu 01 0-100% auxiliary power pump power

solid- state output current loop connection

P

75.8 pF

(menu 0F) URV = 100% Upper Threshold Setting = 90% menu 15 (activation hysteresis)

solid-state switch output: selected at menu 17 and controlled by menus 13 to 18.

menu 16 (deactivation hysteresis)

Lower Threshold Setting = 8%

14.3 pF

(menu 0E) LRV = 0%

Device settings: (The device is first restored to factory settings before being commissioned) TV0 selected: Transmitter Variable 0 is PV Menu 01 reads Pv = 0 Lower Range Value (0% of range) is set to 14.3 Menu 0E reads 14.30 Upper Range Value (100% of range) is set to 75.8. Menu 0F reads 75.80 Current loop is in analog mode, with both buttons pressed Menu 07 reads C:An Solid-state switch enabled, contact closed selected Menu 17 reads S:cc1

Activation hysteresis is set to 90. Menu 15 reads 90.0 Deactivation hysteresis is set to 8. Menu 16 reads 08.0.

Appendix E

When the level reaches 90%, the solid-state output is closed and the pump is started via the auxiliary circuit. When the level drops to 8% the solid-state output is opened, the auxiliary circuit is deactivated, and the pump stops.

1. S:cc appears while the button is pressed. See menu 17 on page 70 for more details.

Active Shield section · (menu 0C) USL · (menu 0B) LSL

Page 100 of the Siemens Sitrans user manual — Appendix E
Page 100 · click to enlarge
Page 100

Application: Analog fault signalling (2-state output)

In 2-state mode, the loop current signals whether the probe is covered or uncovered, and the continuous level measurement is unavailable.

  • 2-state mode provides:
  • a 4 mA or 20 mA output to menu 07, when the level reaches one of the threshold settings
  • a 3.6 or 22 mA output to menu 07 (if 2-state fault signalling is enabled at menu 08) when the process level exceeds one of the limit settings (menu 0B and 0C).
  • The above settings can be modified:
  • The response time when thresholds are reached can be modified by Upper and/ or Lower Threshold delays (menus 03 and 04).
  • The mA reading can be stabilized if necessary by applying Damping (menu 0A): the increment value is controlled at menu 09.

Example:

Current activated relay module

P

83.5pF

75.8 pF

(menu 0F) URV = 100% Upper Threshold Level = 90% menu 05 (activation hysteresis)

2-state output (menu 07)

menu 06 (deactivation hysteresis)

Lower Threshold Level = 8%

14.3 pF

Menu 0E LRV = 0%

7.3 pF

Device settings: (The device is first restored to factory settings before being commissioned) TV0 selected: Transmitter Variable 0 is PV Menu 01 reads Pv = 0 Lower Range Value (0% of range) is set to 14.3 Menu 0E reads 14.30 Upper Range Value (100% of range) is set to 75.8 Menu 0F reads 75.80 Current loop is in 2-state mode (C: Hi selected) Menu 07 reads C:Hi 2-state fault signalling enabled (F: Hi selected Menu 08 reads F:Hi1

Activation hysteresis is set to 90 Menu 05 reads 90.0 Deactivation hysteresis is set to 8 Menu 16 reads 08.0.

Appendix E

1. F: Hi appears while the button is pressed. See Analog Fault Signalling (2-state) on page 66 for more details.
Show 4 more labels / short text on this page
current loop connection · Active Shield section · (menu 0C) USL · Menu 0B LSL
Page 101 of the Siemens Sitrans user manual — Appendix E
Page 101 · click to enlarge
Page 101

USL is set to 83.50 pF Menu 0C reads 83.50

LSL is set to 7.3 pF Menu 0B reads 7.30

When the process level reaches 90%, the probe is considered covered and the output will be 20 mA. If the level exceeds USL, the output will be 22 mA. When the process level drops to 8%, the probe is considered uncovered, and the output will switch to 4 mA. If the level drops below LSL, the fault signal will be 22 mA.

Appendix E

Page 102 of the Siemens Sitrans user manual — T 100 °C IP 66
Page 102 · click to enlarge
Page 102

Appendix F: Approvals

CE Certificate

Appendix F

WRITTEN DECLARATION OF CONFORMITY

We, Siemens Milltronics Process Instruments B.V. Nikkelstraat 10 - 4823 AB BREDA - The Netherlands Declare, solely under own responsibility, that the product

Capacitance Level and Flow Measurement/Detection, SITRANS LC 500 / Pointek CLS 500

Mentioned in this declaration, complies with the following standards and/or normative documents:

Requirements Remarks Certificate No Environment Commercial, light Industrial and industrial 2008949-KRQ/EMC 01-4231

EN 61326: 1998 Product group standard for “Electrical equipment for measurement, control and laboratory use”, from which:

EN 50011 : 1998 Emission – Class B EN 61000-4-2: 1995 Electrostatic Discharge (ESD) Immunity EN 61000-4-3: 1996 Radiated Electro-Magnetic Field Immunity EN 61000-4-4: 1995 Electrostatic Fast Transient (EFT) Immunity EN 61000-4-5: 1995 Surge Transient Immunity EN 61000-4-6: 1996 Conducted Radio-Frequency Disturbances Immunity

ATEX Directive 94/9/EC Audit Report No 2003068 KEMA 00ATEXQ3047

II 1 G EEx ia IIC T4…T6 0344 KEMA 02ATEX1019 X II 1/2 GD EExd [ia] IIC T6…T1 0344 KEMA 01ATEX2076 X II 3 GD EEx nA [ib] IIC T4…T6 0344 KEMA 02ATEX1033 X

T 100 °C IP 66

EN 50014: 1992 General Requirements EN 50018: 1994 Flameproof Enclosures “d” EN 50020: 1994 Intrinsic Safety “i” EN 50284: 1999 Special Requirements for Category 1G Equipment EN 50281-1-1: 1998 Dust Ignition Proof

The notified bodyN.V. KEMA – Utrechtseweg 310 – 6812 AR Arnhem – The Netherlands

97/23/EC Pressure Equipment Directive Lloyd’s Register, DAD No.:

8033474, 8033475, 8033476, 8033477, 8033478, 8033479, 8033480, 8033481, 8033482, 8033483, 8033484, 8033485

The notified bodyStoomwezen B.V. – Weena Zuid 168 – 3012 NC Rotterdam - The Netherlands

Location, Breda Representative Name, C.S. van Gils Date, August 28th, 2002 Function, Managing Director Remark: For specific safety specifications, please consult the instrument label

Page 104 of the Siemens Sitrans user manual — Appendix F
Page 104 · click to enlarge
Page 104
Siemens Sitrans — Instrument label: SITRANS LC 500 diagram (page 104)
Fig. 30 · Instrument label: SITRANS LC 500

Appendix F

Page 105 of the Siemens Sitrans user manual — Appendix F
Page 105 · click to enlarge
Page 105

KEMA certificate and schedules

Siemens Sitrans — KEMA certificate and schedules diagram (page 105)
Fig. 31 · KEMA certificate and schedules

Appendix F

Page 106 of the Siemens Sitrans user manual — Appendix F
Page 106 · click to enlarge
Page 106
Siemens Sitrans — KEMA certificate and schedules diagram (page 106)
Fig. 32 · KEMA certificate and schedules

Appendix F

Page 107 of the Siemens Sitrans user manual — Appendix F
Page 107 · click to enlarge
Page 107
Siemens Sitrans — KEMA certificate and schedules diagram (page 107)
Fig. 33 · KEMA certificate and schedules

Appendix F

Page 108 of the Siemens Sitrans user manual — Appendix F
Page 108 · click to enlarge
Page 108
Siemens Sitrans — KEMA certificate and schedules diagram (page 108)
Fig. 34 · KEMA certificate and schedules

Appendix F

Page 109 of the Siemens Sitrans user manual — Appendix F
Page 109 · click to enlarge
Page 109
Siemens Sitrans — KEMA certificate and schedules diagram (page 109)
Fig. 35 · KEMA certificate and schedules

Appendix F

Page 110 of the Siemens Sitrans user manual — Appendix F
Page 110 · click to enlarge
Page 110
Siemens Sitrans — KEMA certificate and schedules diagram (page 110)
Fig. 36 · KEMA certificate and schedules

Appendix F

Page 111 of the Siemens Sitrans user manual — Appendix F
Page 111 · click to enlarge
Page 111
Siemens Sitrans — KEMA certificate and schedules diagram (page 111)
Fig. 37 · KEMA certificate and schedules

Appendix F

Page 112 of the Siemens Sitrans user manual — Appendix F
Page 112 · click to enlarge
Page 112
Siemens Sitrans — KEMA certificate and schedules diagram (page 112)
Fig. 38 · KEMA certificate and schedules

Appendix F

Page 113 of the Siemens Sitrans user manual — NAMUR recommendation NE 43
Page 113 · click to enlarge
Page 113

Certificates and Approvals

The Intrinsic Safety Specifications of the SITRANS LC 500 have been defined and approved as follows:

Appendix F

Application Specifications

current loop insulated from the measuring circuit 3.6-22 mA

internal capacitance can be ignored

internal inductance 10 µH

maximum supply voltage 30 Vdc

maximum current 200 mA

maximum power consumption 1.5 W

The SITRANS LC 500 can be directly connected to an intrinsically safe supply for intrinsically safe applications. For non-intrinsically safe operations, such as explosion proof, a safety barrier must be used.

The operation of the SITRANS LC 500 conforms to the following:

NAMUR recommendation NE 43

This recommendation describes rules by which analog transmitters transfer their information to DCS equipment. This information can be divided into two types:

  • measurement information For measurement information the current signal should be within the range of 3.8 to 20.5 mA.
  • failure signalling For failure information which indicates a failure in the measuring system 1 the current signal should be in the range of either 0 to 3.6 mA, or 21 mA or greater.

The application will determine which of these two ranges is more desirable. The SITRANS LC 500 can be set for 3.6 mA, or 22 mA, as required2.

1. It may also signal a process level outside the Upper and Lower Sensor Limits, if the unit has been programmed for this. For more information, see Fault Signalling on page 15. 2. See Analog Fault Signalling (2-state) on page 66 for details.
Page 114 of the Siemens Sitrans user manual — MERCAP/FTS
Page 114 · click to enlarge
Page 114

Control Drawing FM/CSA Approval

SITRANS LC 500

Appendix F

Size:

A1

Rev.

A

must not exceed barriers' Isc or It Current sum of both

Current sum of both

Appr. RM

barriers' Isc or It

± 0.5° AnglesScale:

1:1

following:

following:

CONTROL_DRAWING

FM/CSA_APPROVAL

3. FM: Installation must be in accordance with the National Electrical Code (ANSI/NFPA 70) and ANSI/ISA-RP12.6
1. Two FMRC or CSA approved single or dual channel barriers which meet the voltage (Voc or Vt) and current (Isc or It) parameters shown in the tables for the appropriate group can be used. The Ca and La

Tolerance Unless Otherwise Noted:

A10324R0

Revision / ECN Description

2 Place Decimal ± 0.01

2. All other installation instruction provided in the barrier manufactures' control drawing must be followed.

No Decimal ± 0.5

1 Place Decimal ± 0.1

DRAWING No:

Voc or Vt Voc or Vt SS relay barrier:

30 Vdc 30 Vdc

24 Vdc 30 Vdc

26 Vdc 24 Vdc

SS relay barrier:

The installation must meet all applicable sections of the Canadian Electrical Code (C.E.C.) 4) For Canada: Installation must be in accordance with the Canadian Electrical Code, Section 18.

TITLE:

Plot at:

Entity parameters specified in the barrier manufactures' control drawings are not used.

Supply voltage fused with 3 A fuse (power limited)

Instead, the instrument's cable length is limited to the lengths shown in the tables.

Nikkelstraat 10, 4823 AB Breda, The Netherlands

PROCESS INSTRUMENTS b.v. SIEMENS MILLTRONICS

Hazardous (Classified) Location Non - hazardous Location

For groups A, B, C or D

Current loop barriers:

For groups C or D only:

Current loop barriers:

A10324R0.rev A

Rev.

For FM Flame proof applications only:

RM

RM

USE DIMENSIONS ONLY - DO NOT SCALE

Drawn:

Checked:

Approved:

Location:

File No.

Date:

DIMENSIONS ARE IN MILLIMETERS

OF THIS DRAWING DOES NOT IMPLY ANY LICENSE UNDER ANY SUCH R OTHERS, AND THE ISSUE THE SUBJECT OF PATENTS, INDUSTRIAL DESIGN REGISTRATIONS OR MILLTRONICS OR OTHERS. THE ITEM DEPICTED MAY THEMSELVES BE PROPRIETARY INFORMATION AND TRADE SECRETS OF SIEMENS IS TO BE MAINTAINED CONFIDENTIAL, SINCE IT MAY CONTAIN SPECIFICALLY HAVE BEEN AUTHORIZED BY SIEMENS MILLTRONICS. IT AND CAN BE UTILIZED ONLY FOR SUCH LIMITED PURPOSES AS MAY AND IS SUBJECT TO RECALL. IT MAY NOT BE COPIED, AND IS ISSUED THIS DOCUMENT REMAINS THE PROPERTY OF SIEMENS MILLTRONICS

IMPORTANT NOTICE CONFIDENTIAL

COPYRIGHT SIEMENS MILLTRONICS PROCESS INSTRUMENTS b.v.

Associated Apparatus with entity parameters: Class I, Div. 1, Groups A, B, C and D

Associated Apparatus with entity parameters:

COPYRIGHTS OF SIEMENS MILLTRONICS O

ALL RIGHTS RESERVED

Class I, Div. 1, Groups C and D

RIGHTS

10 µH + Lcable

10 µH + Lcable

NOTES:

Siemens Milltronics PI b.v.

+31 (0) 76 542 7 542

+31 (0) 76 542 8 542

4823 AB Breda The Netherlands

Class I, Div. 2, Groups A, B, C and D: Vmax = 33 V, Imax = 24 mA, installation without associated apparatus.

Class I, Div. 1, Groups A, B, C, and D: Vmax = 30 V, Imax = 110 mA, Ci = 0, Li = 10µH

Class I, Div. 1, Groups C and D: Vmax = 30 V, Imax = 200 mA, Ci = 0, Li = 10 µH

MERCAP 500 / POINTEK CLS500 UNIT

CPU

Installation must be in accordance with the National Electrical Code (R)

Temperature class T4 for class I, Div. 1 applications

(NFPA 70, Article 504) and ANSI/ISA-RP12.6

-40°C < ambient temperature +85°C

MERCAP/FTS

MERCAP/N MERCAP/FTF

MERCAP/2

MERCAP/F

Show 51 more labels / short text on this page
05-04-02 · Date · must not exceed · Sheet 1 · Of · 100 mA · 120 mA · 150 mA · 260 mA · 310 mA · Drawn RM · 05-04-02 · 30 Vdc · 24 Vdc · Voc or Vt · Capacitance · 30 Vdc · 30 Vdc · CvG · Breda · Voc or Vt · Product Group · Third Angle Projection · Ø + Lcable · Ø + Lcable · 30 Vdc · 110 mA · 30 Vdc · 200 mA · < · < · Nikkelstraat 10 · Voc · < · Lsc · Ca · < · La · < · Voc · Lsc · < · Ca · < · La · < · Current loop output · solid state output · Merflame enclosure · External earth terminal · <
Page 115 of the Siemens Sitrans user manual — Glossary
Page 115 · click to enlarge
Page 115

Glossary

capacitancethe property of a system of conductors and dielectrics that permits the storage of

electricity when potential differences exist between the conductors. Its value is expressed as the ratio of a quantity of electricity to a potential difference, and the unit is a Farad.

capacitor: a device in a circuit that has the potential to store an electric charge. Typically a

capacitor has 2 conductors or electrodes separated by a layer of a nonconducting material called a dielectric. With the conductors on opposite sides of the dielectric layer oppositely charged by a source of voltage, the electrical energy of the charged system is stored in the polarized dielectric.

deratingto decrease a rating suitable for normal conditions according to guidelines specified

for different conditions.

dielectrica nonconductor of direct electric current. 1
dielectric constantthe ability of a dielectric to store electrical potential energy under the

influence of an electric field. This is measured by the ratio of the capacitance of a condenser with the material as dielectric to its capacitance with vacuum as dielectric. The value is usually given relative to a vacuum /dry air: the dielectric constant of air is 11.

immiscible: incapable of mixing or attaining homogeneity.

Glossary

implicit: for example in “the units are implicit in pF”, the units are implied, or assumed to be pF,

because there is no other option.

miscible: capable of being mixed.

repeatabilitythe closeness of agreement among repeated measurements of the same

variable under the same conditions.

saturation: a condition in which any further change of input no longer results in a change of

output. For example, “the loop-current will saturate to 3.8 or 20.5 if the level exceeds the Range settings”.

solid-state devicea device whose function is performed by semi-conductors or the use of

otherwise completely static components such as resistors and capacitors.

stilling-well: a grounded metal tube with openings.

1. Many conductive liquids/electrolytes exhibit dielectric properties; the relative dielectric constant of water is 80.
Page 116 of the Siemens Sitrans user manual — Glossary
Page 116 · click to enlarge
Page 116

Notes

Glossary

Page 117 of the Siemens Sitrans user manual — Table of Contents
Page 117 · Contents
Contents

Contents

SITRANS LC 500p.7Applicationsp.7Safety Notesp.8Safety marking symbolsp.8The Manualp.8Abbreviations and Identificationsp.9Technical Specifications: SITRANS LC 500p.10Powerp.10Environmentalp.10Performancep.10Outputsp.11User Interfacep.11Communicationsp.11Electrodesp.12Wetted Partsp.12Enclosure (electronic)p.12Weightp.12Process Conditionsp.13Approvalsp.13SITRANS LC 500: Transmitterp.14Operating Principlesp.14The SITRANS LC 500 variable frequency oscillatorp.14Capacitance measurement in a cylindrical metal tankp.14The SITRANS LC 500 electrodep.16Application: SITRANS LC 500p.18Level Measurementp.19Interface Measurementp.20Switch actionp.20Fault Signallingp.21SITRANS LC 500: Probe Configurationp.22SITRANS LC 500 Electrode (Probe) Characteristicsp.22Electrode Assemblyp.23Process Connectionsp.23Seal Typesp.23Process Connection and Seal Configuration of SITRANS LC 500p.23Pressure and Temperature Considerationsp.24Non-standard applicationsp.25SITRANS LC 500: Installationp.26Handling Electrodesp.26Mounting Instructionsp.27Protection for solid-state switchp.27Process Cautionsp.27SITRANS LC 500: Standard Level Versionp.28Interconnection: SITRANS LC 500p.29Wiringp.29Supplyp.29Cablep.30Selecting the correct instrumentation cablep.30Terminalsp.32Connecting SITRANS LC 500p.32Connection Diagramp.32Protection for solid-state switchp.33Grounding instructionsp.33Grounding Examples: SITRANS LC 500p.34System Grounding (referencing)p.34Metal Tanksp.34Cathodically Protected Metal Tanksp.35Non-Conductive Tanksp.35Safety Groundingp.36Example 1p.36Example 2p.36Example 3p.37Example 4p.37Communicationsp.38Typical PLC configuration with HARTp.38Diagnosticsp.38Applications for Solid-state Outputp.39Switch Protection (Diode)p.40Factory Settingsp.40Settings:p.40The SITRANS LC 500 User Interfacep.42The LCD (display)p.42How to access the data:p.43Menu Levels 00 to 0F and 10 to 1Fp.43The rotary switchp.44The push-buttonsp.44Access to a menu item:p.44Adjusting the valuep.44Transmitter Variablesp.45Start-up: SITRANS LC 500p.46Quick Startp.46Menu levels 0 and 1p.48Start up using push-button calibration: (overview)p.48Calibration using push-button adjustmentp.49Calibration using HARTp.52Maintenancep.56Test functionp.56Inspectionsp.56Troubleshooting: SITRANS LC 500p.58Error Messages and Error Codesp.59Error Messages (push-button operation)p.59Error Codes (HART)p.59Appendix A: Menu Groupsp.60Menu Itemsp.61Appendix B: LCD display examplesp.80LCD: alphanumeric display examplesp.80M 00p.80SEL 1p.80FLtp.80S: ocp.80S: oop.80S= ocp.80S: – –p.80F: oop.80F: ocp.80F: – –p.80Hip.80Lop.80Anp.80norp.80invp.80ooLp.80FAC Ap.80FAC Pp.80FAC?p.80do itp.800 = /op.80Pv=0p.80PL 0p.80SIMp.80Appendix C: HART Documentationp.81HART Communications for the SITRANS LC 500p.81HART Device Descriptor (DD)p.81Simatic Process Device Manager (PDM)p.81HART informationp.81Expanded Device Type Code:p.81Physical Layer Informationp.81SITRANS LC 500 DD Menu/Variable Organizationp.82HART Response Code Informationp.83Bit #7: Field Device Malfunctionp.83Bit #6: Configuration Changedp.83Bit #5: Cold Startp.83Bit #4: Extended Status Availablep.83Bit #3: Output Current Fixedp.83Bit #2: Primary Variable Analog Output Saturatedp.83Bit #0: Primary Variable Out of Limitsp.83HART Conformance and Command Classp.84General Transmitter Informationp.85Damping informationp.85Non-volatile Memory Data Storagep.85MultiDrop operationp.86Burst modep.86Units conversionsp.86Additional Universal Command Specificationsp.86Appendix D: Block Diagram, and Correlation table, mA to %p.87Correlation Table: 0% - 100% to 4-20 mA or 20-4 mAp.88Appendix E: SITRANS LC 500, alternate versions and application detailsp.89Standard Versionp.89Standard Version S-Series, Threadedp.89S-Series: Threadedp.89Standard Version S-Series, Threadedp.90S-Series Cable Versionp.90(with weight)p.90Standard Version S-Series, Welded and Machined Flanged Versionsp.91S-Series, Welded Flangep.91Standard Version D-Series, Machined Flangep.92D-Seriesp.92SD-Seriesp.93Interface Versionp.94Interface Version, threaded (optional sanitary and flanged)p.94Sanitary Versionp.95Sanitary Versions, threaded and tri-clampp.95Sanitary Thread Couplingp.95Flangesp.96Flange Standardsp.96Applications Examplesp.97Generic Application Calculationsp.97Examples (using dimensions above):p.97Application: level indicator and solid-state switch outputp.99Application: Analog fault signalling (2-state output)p.100Appendix F: Approvalsp.102CE Certificatep.102Instrument label: SITRANS LC 500p.104KEMA certificate and schedulesp.105Certificates and Approvalsp.113NAMUR recommendation NE 43p.113Control Drawing FM/CSA Approvalp.114SITRANS LC 500p.114Glossaryp.115Indexp.117Quick Reference: SITRANS LC 500p.119Quick Startp.119
Page 119 of the Siemens Sitrans user manual — Quick Start Sequence
Page 119 · click to enlarge
Page 119

Quick Reference: SITRANS LC 500

Quick Reference

Quick Start

We strongly recommend you read the full manual to use your device to its fullest

potential. However, if it is possible to adjust the level of the tank to the 0% and 100% levels, you can use the quick start sequence below to calibrate the instrument and get started.

  • Notes:
  • Change over from Menu LEVEL 0 to Menu LEVEL 1 is only possible at position 0, from menu item 00 to 10 or vice-versa. (See page 42 for detailed instructions.)
  • For a table showing all the combinations of rotary switch positions and button presses used to carry out different functions, see next page.
  • For a detailed description of each menu item, see Appendix A: Menu Groups, page 54.

Quick Start Sequence

1 Calibrate the 0% setting (LRV - lower range value): menu 0E

For instruments without a stilling well, the 0% setting needs to be calibrated after the device is installed, and with the tank/vessel empty. Calibration is also sometimes neces- sary after installing a SITRANS LC 500 fitted with a stilling well, although in most cases the 0% setting is calibrated at the factory.

Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).

a Bring the product level to the height that corresponds to 0%.

b Turn the rotary switch to E (Empty).

c Press both buttons and hold for about 1 second: the 0% point is now set. 2 Calibrate the 100% setting (URV - upper range value): menu 0F

Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).

a Raise the product level to the height that corresponds to 100%.

b Turn the rotary switch to F (Full).

c Press both buttons and hold for about 1 second: the 100% point is now set. 3 View primary variable (PV): menu 00

Turn the rotary switch to 0. The LCD displays the actual pF reading. 4 SITRANS LC 500 is now ready to operate.

Page 120 of the Siemens Sitrans user manual — NO KEYS
Page 120 · click to enlarge
Page 120

cal PV Units PV Units PV Units PV Units PV Units

Default * TVO * 00 00 75% 25% Analog Disabled 1.0 1 1.666 pF 3300 pF 3300 pF 0 pF 3300 pF Menu LEVEL 1 (10 to 1F)

Settings Seconds Seconds % % O/ C O/C nor / inv Resp. Units Keylock

URV

URV

Value (PV) URV =

0 1 2 3 4 5 6 7 8 9 A B C D E F

PV

PV

PV

Default * * * 00 00 75% 25% Disabled Disabled nor * 0

= Min. LRV = Actual

PV

PV

LRV

PV

LRV

for 4 c.q.

URV– LRV

PV

PV

PV

PV

PV

Set to 1 Set to 1 Preset

PV

PV

Rotary Switch Positions – Quick Reference

Selection PV Units Seconds Seconds % % mA mA Numeri-

to 0.01

MODE

MODE

MODE

Menu LEVEL 0 (00 to OF)

22 or 3.6 mA

Set FAULT:

Set FAULT:

for Solid-state Disable Fault

3.6 mA

Set Covered:

Set Covered:

4 to 20 mA (Anl)

00 < – > 100

00 < - > 100

00 < – > 100

do it Toggle Delay

00 < - > 100

% Mode Reset Hi/Lo

Units PV Units Numerical Factory

PV

FAC

FAC

FAC

Units PV Units Num.

NO KEYS

RED (+)

BLUE (–)

NO KEYS

RED (+)

BLUE (–)

Show 265 more labels / short text on this page
URV Value · for 20 mA · Decrease · Value (PV) · Spare Keylock · Increase · Keylock · Decrease · Keylock · Increase · Actual · Level · Level · Level · LRV Value · for 4 mA · Increase · Decrease · Spare — · PV Delta Value · 20 mA · Increase · Decrease · Delta · Delta · PV UPPER limit · Increase · UPPER limit · Decrease · UPPER limit · Preset Upper · Actual (PV) · Spare Transmitter · Read-Out · Transmitter · Read-Out · Transmitter · Read-Out · Transmitter · Read-Out · Limit to · Var 0 · Var 1 · Var 2 · Var 3 · Value LOWER limit · Increase · LOWER limit · Decrease · LOWER limit · Lower Limit to · Actual (PV) · Spare — · cal Numeri- · Damping · Increase · Damping · Decrease · Damping · Value · Value · Step Size · Decrease · Step Size · Operating · Actual · Increase · to 10000 · Normal / · Inverse · Normal / · Inverse · Normal / · Inverse · for Solid-state Toggle · Mode · Step · Size · Solid-state OFF · Fault signal · Fault signal · Fault signal · (Solid-state · Set FAULT = · Solid-state ON · Set FAULT = · 22 mA · Disable · Output) · Loop Current · Set Covered = · Solid-state ON · Set Covered = · Solid-state OFF · Disable Switch · 20 mA (Hi) · 4 mA (Lo) · Set Analog · Range · Status · Solid-state · in mA · Output · tion Transistor · Lower Thresh- · De-Activation · Current signal · Increase · Threshold · Decrease · Lower Thresh- · Preset Lower · Threshold · Point to 25% · Lower Thresh- · old De-Activa- · Increase · Lower Thresh- · Decrease · Lower Thresh- · Preset Lower · Threshold · Point to 25% · Lower · Point · old Point · Switch · old Point · old Point · old · Upper Thresh- · Current signal · Upper Thresh- · Preset Upper · Point to 75% · Upper Thresh- · old Activation · Upper Thresh- · Upper Thresh- · Preset Upper · Point to 75% · Activation · Increase · Upper · Threshold · Decrease · Threshold · Transistor · Switch · Increase · old Point · Decrease · old Point · Threshold · old · Point · old · Point · De-Activation · Current signal · De-Activation · Toggle Delay · Time Delay · Increase · Delay Time · Decrease · Delay Time · Delay Time · Time Delay · Transistor · Switch) · Increase · Delay Time · Decrease · Delay Time · Toggle · Time · Time Delay · Activation · Time Delay · Current sig- · Increase · Delay Time · Decrease · Delay Time · Delay Time · Activation · Transistor · Switch · Increase · Delay Time · Decrease · Delay Time · nal · Toggle · Time · PV Memory · PV Memory · memories to · (factory set- · (factory set- · (factory set- · Highest/ · Lowest · Memory · TVmax Highest · Read-out · to TV0 Lowest · Read-out · actual PV · tings) · tings) · tings) · Step TV0 to · Step TVmax · Set · Show · select PV · variable · Display · Fault code · Invert Sig- · nalling Sta- · check · tus · PV Value · Menu · 00 to 0F · Menu · 10 to 1F · Menu · PV Value · Set Menu · 00 to 0F · Set Menu · 10 to 1F · Show · Menu · or · Fault · Set · Level · Set · Level · Show- · Level · or · Fault · Level · Level · Level · read-out · Up Key- · read-out · Up Key- · Value · Down · Both · Keys · Value · Down · Both · Keys · Key- · Key-
Page 121 of the Siemens Sitrans user manual — Quick Reference: SITRANS LC 500
Page 121 · click to enlarge
Page 121
Siemens Sitrans — Quick Reference: SITRANS LC 500 diagram (page 121)
Fig. 39 · Quick Reference: SITRANS LC 500
Page 122 of the Siemens Sitrans user manual — *7ml19985GE01* Rev. 1.2
Page 122 · click to enlarge
Page 122

www.siemens-milltronics.com

Siemens Milltronics Process Instruments Inc. 1954Technology Drive, P.O. Box 4225 Peterborough, ON, Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 Email: techpubs@siemens-milltronics.com

Siemens Milltronics Process Instruments Inc. 2003 Subject to change without prior notice

*7ml19985GE01* Rev. 1.2

Printed in Canada

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
16signal error: the measurement circuitry stopped functioning p.59
0PV value is outside the limits set (USL and LSL) p.59

Ask about the Siemens Sitrans

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.