SITRANS LC 500 is a high performance 2-wire capacitance instrument for continuous level and interface measurement in extreme or critical conditions. It uses a unique frequency- based measurement system and patented Active-Shield technology to deliver highly accurate, repeatable results. The measurement is unaffected by moisture, vapors, foam, temperature and pressure variations, or material build-up around the mounting glands.
SITRANS LC 500 combines a sophisticated, easy-to-adjust transmitter (MSP-2002-2) with a measurement electrode and process seal selected from a range of options1, to suit a wide variety of applications. The advanced electronics and integrated local display provide for one-step calibration without interrupting the process, and the probe shield design eliminates the need for frequent recalibration.
SITRANS LC 500 can be used as a level controller, by connecting the mA output and/or the solid-state switch to a relay, and activating a pump via an auxiliary power circuit.
The SITRANS LC 500 is equipped with:

Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes.
This manual will help you set up your SITRANS LC 500 for optimum performance. We always welcome suggestions and comments about manual content, design, and accessibility.
Please direct your comments to techpubs@siemens-milltronics.com. For the complete library of Siemens Milltronics manuals, go to www.siemens-milltronics.com


Loop current 3.6 to 22 mA / 22 to 3.6 mA (2-wire current loop)
Altitude 2000 m max.
–40 oC to 85 oC (–40 oF to 185 oF) for T5 to T1
Relative humidity suitable for outdoor (Type 4X / NEMA 4X / IP 65 enclosure)
Minimum span 3.3 pF
Measurement frequency 420 kHz @ Cx = 0 pF
Accuracy deviation
Non-linearity 0.1% full scale
Repeatability 0.1% actual measurement
Temperature stability 0.15 pF (0pF) or

Outputs
Solid-state switch 40 Vdc / 28 Vac / 100 mA at 2 VA max.
Local digital display 4 1/2 digit LCD
Rotary function switch for selecting programmable menu items
HART 1 Communication protocol

Hastelloy2 C22, Duplex) ANSI, DIN3
Probe insulation PFA, Enamel4
Probe insulation PFA / Enamel
Threaded connection AISI 316 L stainless steel
Flange AISI 316 L stainless steel or Teflon5 covered
Depends on configuration.
Example:
model: S-series rod: PFA insulated, 16 mm (0.63”) dia., 1 m (39.4”) insertion length weight: approx. 5 kg
Process connections · Probe diameter · Probe length

CE Complies with the requirements of E.C.C. as per EN 55011 and EN 61326
Dust Ignition Proof (DIP) ATEX II 3GD (EEx nA [ib] IIC T4...T6) FM/CSA: Class I, Div. 2, Gr. A,B,C,D T4 Class II, Div. 1, Gr. E,F,G T4 Class III, Div. 1, Gr. E,F,G T4
Intrinsically Safe (IS) ATEX II 1 G (EEx ia IIC T4...T6) FM/CSA: Class I, Div. 1, Gr. A,B,C,D T4
Flame-proof/ ATEX II 1/2 GD (EEx d [ia] IIC T6...T1) Explosion-proof enclosure FM/CSA: Class I, Div. 1, Gr. A,B,C,D T4
Lloyds Register of Shipping Categories ENV1, ENV2, ENV3, ENV5
European Pressure, PED 97 / 23 / EC
Pressure rating1 · Temperature rating1 · Sanitary 3A

Operating Principles
Capacitance1 measurement operates by forming a variable capacitor resulting from the installation of a vertical measurement electrode in a vessel or silo. The tank wall usually forms the reference electrode of the capacitor. Whatever material is sandwiched between the two electrodes forms the dielectric. This will be composed of the vessel contents (air, vapor, liquid, solid, or a combination) and, if the measurement electrode is insulated, the insulating layer (PFA, for example). The dielectric gives a capacitance value that is proportional to level.
Capacitance is affected by the surface area of the electrodes, the separation distance between the electrodes, and the dielectric constant of the vessel contents. The dielectric constant is the measure of a material’s ability to store energy. The relative dielectric constant of air (vacuum) is 1: all other materials have a higher value.
The SITRANS LC 500 variable frequency oscillator
The SITRANS LC 500 probe is equipped with a variable frequency oscillator which responds to the capacitance: a change in capacitance is registered as a change in frequency. The relationship between capacitance and frequency is inverse, resulting in high resolution and accuracy. The variable frequency maintains a constant relationship to the reading.
In a cylindrical tank, it is possible to determine the initial capacitance in air by factoring in the length of the probe, diameter of the probe, diameter of the tank, and the relative dielectric constant of air.

The formula1 is:
C K ε L × × Log D d ⁄ ( ) =
where C = capacitance
K = constant ε = dielectric constant L = active measurement length D = diameter of tank d = probe diameter.
(For detailed application examples, see page 91.)
The transmitter measures the capacitance of the measurement electrode relative to the tank wall (reference electrode) and transforms it to a 4-20 mA signal. Any material that covers the probe will cause an increase in capacitance relative to an uncovered probe surrounded by air. As the product level rises the capacitance will increase.
In practice, the SITRANS LC 500 probe is usually insulated. If the vessel contents are non- conductive, the dielectric is composed of the vessel contents and the insulation, and the separation distance is from the probe to the tank wall. The tank wall is the reference electrode, and it must be connected to the ground point on the instrument.
dielectric = contents plus insulation (non-conductive contents)
dielectric = insulation (conductive contents)
dia. (d)
probe sleeve internal tank wall
internal tank diameter (D)
If the vessel contents are conductive, the electrode must be insulated. In this case the dielectric is the insulation layer and the interface between the conductive contents and the insulating sleeve acts as the reference electrode. This reduces the separation distance for the filled portion of the tank to the thickness of the insulation. It also creates a linear reference electrode independent of the tank wall.
probe · (insulation)

Where the vessel contents are non-conductive:
Where the vessel contents are conductive:
The stilling well is a metal tube concentric with the electrode, with vent openings to facilitate level equalization. Its diameter is somewhat larger than that of the electrode, depending on the application. The stilling well can either be integral to the SITRANS LC 500, or it may be part of the tank1.
The SITRANS LC 500 electrode, comprising a measurement section and an active shield section, is the primary sensor of the system. It supplies the electrical capacitance value of the measurement section relative to the environment (tank wall or stilling well).
The SITRANS LC 500 patented Active-Shield Technology electrically isolates the measurement section and prevents any non-measurement capacitance from interfering with the measurement. (Capacitance changes could result from uncontrolled variations occurring in the connection cable, process connection, and non-active parts of the probe). This results in a better ratio of initial capacitance to total capacitance, resulting in higher accuracy.

SITRANS LC 500 with Active Shield
R = (C1 + C2 + C3) + Ca
(C1 + C2 + C3) + Ca + Cm
R = Ratio between initial
capacitance and total capacitance
Ca = Initial capacitance (air)
Cm = Capacitance Increase
C1 = Capacitance connection
C2 = Capacitance connection
C3 = Capacitance Process
connection (includes active part)
The measurement is further protected from interference by a buffer, which applies the frequency signal from the measurement section to the active shield section. This effectively eliminates any electrical potential difference between the shield and the measurement section and prevents additional changes in capacitance occurring.
SITRANS LC 500
frequency (f) ≈ K capacitance (C)
The relative lengths of the measurement section and active shield section can be specified to suit a particular application. If the measured range will be short relative to the total length of the electrode, specify a short measurement section. This increases the achievable resolution of the measurement, since any change in level will be greater relative to the length of the measurement section.

The entire SITRANS LC 500 transmitter is potted in epoxy resin as part of the intrinsic safety protection. The potting also protects the electronics against mechanical vibration and moisture influences.
The transmitter is connected to the electrode by a mini coaxial cable, and grounded to a connection point inside the enclosure. The external ground lug on the enclosure provides a means of connecting the instrument system ground to a grounded tank or stilling well1. (For more detailed information on grounding requirements, please see Grounding Examples, page 28.)
The measuring range of the SITRANS LC 500 is 3300 pF (1.0 pF ≅10–12F).
The SITRANS LC 500 provides an analog and a solid-state output. The analog output can be either a continuous signal proportional to the reading, or in 2-state mode, a mA signal operating according to NAMUR recommendations for fault signalling2.
0% (LRV) and 100% (URV) can be set anywhere within the measurement range.
a. an analog signal:
or:
b. in 2-state mode, provides a mA output:
covered probe: it can be wired to an external relay and used to activate an external alarm or a pump via an auxiliary power circuit. It can be activated under normal conditions by the threshold settings, or Fault signalling can be enabled at menu 18.

Indicator - dynamic Primary Variable (units or % of range)

0-100% auxiliary power pump power solid- state output current loop connection
URV = 100% Upper Threshold Setting = % (activation hysteresis)
solid- state switch output or 2-state mA output
2-state output, and/or the solid-state output: the settings can be modified to adjust the hysteresis (the window within which the probe is considered ‘covered’).
2-state output can be modified by Upper and/or Lower Threshold delays.
applying the Delta Range Setting.
precedence over the threshold settings (menus 07 and 17).
The continuous 4-20 or 20-4 mA signal is proportional to the surface level of the product, with an accuracy of 0.1% of the actual measurement (for example, 1mm/m).
Typically, Lower Range Value (LRV - 0%) is set to 4 mA and Upper Range Value (URV - 100%) is set to 20 mA: but the reverse is possible if required. The measurement takes place anywhere within that range. The LCD displays the value as mA, or pF, or percent, depending on the setting for the transmitter variable (TV). If you are using HART, you have the option to define the units.

The capacitance of the electrode system is dependent on the dielectric constant of the product surrounding the probe. By comparing the capacitances resulting from different products with different dielectric constants, it is possible to determine which product is surrounding the probe.
100% product A 4 mA 100% product B 20 mA Values in between 4 and 20 mA represent the ratio of the two products.
For immiscible products: The interface between two products can be detected by the change in capacitance from one to the other. (See example, For Vessels filled with Oil on page 91.)
The mA output can be used as a 2-state switch set to either 4 or 20 mA. It can be set to go to 4 mA if the probe is covered and 20 mA if the probe is uncovered, or the reverse.
Solid-state Switch
The solid-state output can be set to ‘contact open’ or ‘contact closed’ with a covered probe.
The adjustable hysteresis and time delay settings allow you to adjust the switch action for applications with a lot of surface movement.
Examples: With a moving surface that fluctuates between 79% and 80%, if the hysteresis is set so that 80 is on and 79 is off, the alarm will constantly alternate between on and off. Either set a time delay, or adjust the hysteresis:

The SITRANS LC 500 has three fault signalling options:
When using the mA signal, the SITRANS LC 500 operates according to NAMUR standards1 for fault signalling. The fault/failure signal can be triggered by a failure in the measuring system, such as:
You can set the Upper and Lower Sensor Limits (menus 0B and 0C) outside the Upper and Lower Range Value settings. In this case, if the process value is outside its nominal range (the span between LRV and URV), but still not at a fault/failure level, the continuous mA output will saturate to 3.8 mA or 20.5 mA. If the process value is outside the Upper or Lower Sensor Limits, this will be registered as a fault/failure.
Depending on the setting chosen for 2-state Fault Signalling (menu 08), the signal will go to either 3.6 mA (F: Lo) or to 22 mA (F:Hi). If you do not use communications to receive status information, we recommend enabling analog fault signalling (menu 08), in order to be warned if a fault or failure occurs. (This feature is disabled by default.)
See page 75 for HART Response Code Information. Each HART message is accompanied by a response code. It is then up to the Host to decide what to do in the case of a fault situation. The Host may decide to issue Command 48, which returns more detailed information.
The solid-state switch can be wired up to an external relay, to provide a second level of protection. It can then be used to activate a failure alarm, or a level switch. (See page 93 for details of an application using SITRANS LC 500 as a level indicator, with the two-state output connected to a relay that activates a pump.)

The probe (electrode) comprises a measurement section and an active shield section. This electrode connects to the capacitance detector portion of the two-wire loop powered electronic transmitter. The transmitter module is mounted in a powder-coated aluminum enclosure which provides reliable operation in environments with dust, moisture, and high-frequency interference.
Apply to all general connection configurations:
ment portion probe seal (inactive)
active shield · insertion length · measure-

SITRANS LC 500 electrodes come in a variety of formats to provide the necessary characteristics for correct mounting, chemical compatibility, temperature and pressure requirements, and dielectric constant of the medium. The main body of the manual discusses the standard configuration. Other options, with details, are shown in Appendix E: SITRANS LC 500, alternate versions and application details, page 83.
The standard threaded process connection (S-Series) with PFA insulated electrode, including the active shield, provides good results in all measurement situations within the temperature, pressure, and corrosive capabilities of the materials and seals. This remains true over a wide range of dielectric constants in both non-conducting and conducting materials.
Any standard process connection is available with the SITRANS LC 500, and special versions can be fabricated to match the mounting and application requirements. A wide range of threaded and flanged fittings is available. (Contact your local Siemens Milltronics representative for details, or check our website at: www.siemens-milltronics.com)
The basic internal seal for the SITRANS LC 500 has a conical-shaped, preloaded pressure/leak resistant construction. Up to three levels of seal protection are implemented depending on the integrity requirements of the application. A single or double cone internal seal forms one or two barriers against leaking, and a third flange face gasket is also available in the D and DD seal construction. The flange face seal also provides a design with no metal wetted parts if required.
Process Connection Seal Type Seal Description
Threaded S Single Cone
Welded Flange S Single Cone
D Single Cone + Teflon flange seal
DD Double Cone + Teflon flange seal. (Consult your local Siemens Milltronics representative.)
SD Double Cone (used for stilling well applications)
S Single Cone · Solid Machined Flange

The maximum temperature and pressure of operation for the standard SITRANS LC 500 level probe is 200°C (392°F) and 200 bar (2900 psi). Please consult the pressure curve on page 18 for qualifications that must be applied to these maximums.
Enamel probes are recommended when the process temperature exceeds 200 °C, and/or in combination with very high pressure.
As the temperature approaches 75°C (167°F), the maximum pressure must be derated1. When the temperature reaches 200°C (392°F), the maximum pressure is limited to 50 bar (725 psi). This curve is typical for water only. For other, more aggressive chemicals the derating curve will be more severe.
consult factory when pressure or temperatures fall within this area
200 bar (2920 psi)
150 bar (2190 psi)
100 bar (1460 psi)
70 bar (1022 psi)
50 bar (725 psi)
–1bar (– 14.6 psi)
70oC (158 oF) temperature
100 oC (212 oF) –100 oC (–148 oF)
200oC (392 oF) –50 oC (–58 oF)
0 oC (32 oF)
50 oC (122 oF)
150 oC (302 oF)
pressure

Applications outside the standard capabilities of the S-Series require a different design configuration. These non-standard applications include:
Non-metallic tanks with both conducting and non-conducting liquids.
Use stilling well for second electrode reference.
Non-conducting liquids in spherical and horizontal-cylindrical tanks.
Use a stilling well as linearizer.
Highly corrosive materials requiring no metallic wetted parts.
Use flange mount with D, DD seal version.
Sanitary/food safe applications. Use SITRANS LC 500 sanitary version.
For more details on alternate configurations, see, Appendix E: SITRANS LC 500, alternate versions and application details on page 83.

local governing regulations. • This product is susceptible to electrostatic discharge. Follow proper grounding
procedures.
a. Where an isolated probe is used in gas, vapor, or a non-
conductive liquid that is potentially explosive, requiring apparatus group IIC equipment. b. Where the probe is used in a potentially explosive dusty
atmosphere.

The SITRANS LC 500 is easily installed: simply mount the instrument on the process connection of the vessel.
500 mm (20”) min.

Available with the following features:
See Appendix E: SITRANS LC 500, alternate versions and application details, page 83 onward, for details on dimensions, and for application examples.

Wiring
Supply
The SITRANS LC 500 uses a switched power supply circuit, which makes the most efficient use of the available power present on the terminals. If the signal current is low, (4mA), the terminal voltage will be high, and if the signal current is high, (20 mA), the terminal voltage may be low, due to all the resistive elements in the loop, such as the barrier and sense resistor.
Voltage drop versus mA for current transmitter operation
voltage drop over 250 ohm measuring resistance
voltage drop over 280 ohm in barrier
voltage drop over blocking diode in barrier
margin or voltage drop over instrument cable operation voltage, transmitter
Examples:
The loop circuit is completely isolated from the measurement circuit. It is designed so that the internal capacitance and inductance on the terminals are isolated and do not factor in safety calculations.
V-supply · mA

t R C × = R C
(time constant = Resistance * Capacitance) is the sum of the load resistor and cable resistance.
is the sum of the cable capacitance and the capacitances of the connected device/devices.
device (or devices) on the loop from the total capacitance, and using the maximum allowable limit of 100 pF per meter (or 1 nF per 10 meters).
Example 1. Calculate the cable capacitance which will give a time constant of 65 µSec: A twisted pair cable with a conductor cross-section of 1 mm2 (AWG 18 equivalent) has a copper resistance of 73.6 Ohm/km and a capacitance of 100 pF/m (or 1 nF/10m).
For a standard 28 V 280 Ohm barrier and a 250 Ohm measuring resistance, with a 100 meter cable:
Resistance = 280 (barrier) + 250 (sensing device) + 7.36 (cable)= 537.36
t R C × =
C t R ⁄ =
C 65 10 6 – × 537.36 ⁄ ( ) 121 = =
s = nF · nF

device presents on the loop from the total capacitance. SITRANS LC 500 has no measurable capacitance value, but assume 5 nF. Then use the maximum capacitance limit (1 m /10 nF) to determine the cable length.
121 5 116 = –
116 10 1160 = ×
In an IS application, the IS side of the barrier allows for only 70 nF.
Example:
Subtract the capacitance for the device:
70 5 65 = –
65 10 × 650 =
This allows for a maximum 650 meters on the IS side.
On the other side of the barrier:
121 65 56 = –
which allows for 560 meters on that side.
In IIB type/class hazardous area applications the maximum allowed capacitance value is 330 nF, as long as you are not using HART. If you are using HART, the maximum cable length will be limited. Depending on cable specifications, the maximum length lies between 1 and 3 km.
In a multi-drop application, the total capacitance of all the devices must be calculated. With five devices, at 5 * 5 nF, the allowable cable length will be considerably limited.

The SITRANS LC 500 is equipped with two terminal blocks, both insensitive to polarity.
One terminal block is intended for connecting the instrument cable (loop power).
The other terminal block provides the solid-state switch output.
The processor integrated circuit is covered by a label which contains product information and which also acts as a protective seal against moisture.
protective label (see warning above)
solid-state switch relay (any polarity)
instrument system ground 4-20 mA current- loop connection (any polarity)
measuring signal (mini-coaxial cable)
ground connection point for instrument system
ground lug · Tampering voids warranty

Grounding instructions
Connect the housing and the process connection with either the stilling well1 and/or tank wall, using the ground lug on the housing.
label / protective seal
instrument system ground connection point

Grounding is important for two reasons:
Several common applications are illustrated. They are separated into two groups: the first group illustrates System Grounding and the second illustrates Safety Grounding.
For the measuring system to function correctly, the reference electrode must be properly grounded. Make sure that there is a reliable connection from the instrument housing to the reference electrode (usually a metal tank). Some common applications involving system grounding include:
If the metal tank is reliably grounded, connect the ground lug on the SITRANS LC 500 to the earth ground on the tank as shown.
(See page 26 for connection diagram.)
ground lug · metal


Cathodically protected metal tanks are never directly grounded. However, the impedance of the supply source is so low that it will not cause any problems. The shielding of the loop cable should be grounded at one end only (the tank end) to avoid short-circuiting the cathode protection voltage.
The ground lug on the SITRANS LC 500 can be connected to the tank as shown.

Non-metallic tanks always require a stilling well or proper grounded conductive medium.
Connect the ground lug on the SITRANS LC 500 to earth ground. If the stilling well is integral to the SITRANS LC 500, it is now grounded.
If the vessel has a stilling well provided, make sure that the metal parts of the stilling well are properly grounded.
ground lug · non- metallic

The safety grounding requirements are determined by the application and the connected instruments. The SITRANS LC 500 transmitter does not have any special requirements due to the galvanic separation between the measurement section and the loop section.
In hazardous applications a Stahl-type barrier is required, and it is typically mounted on a DIN rail inside a customer-supplied enclosure located in the non-hazardous area.
If no specific Ex conditions apply, the SITRANS LC 500 can be directly connected to the DCS. The supply voltage, however, should remain within the limits set by the SITRANS LC 500. Connecting a SITRANS LC 500 to a DCS does not influence that equipment. One of the connection cables can be grounded if desired.

In the case of Intrinsically Safe applications, where the DCS equipment measures the current in the positive connection and the negative connection can be grounded, a barrier type as shown below is sufficient.
non-hazardous area hazardous area


If you do not want to ground the negative connection directly, or in the case of Intrinsically Safe applications where the DCS measures the current in the negative connection, and that wire cannot be grounded, a barrier type is required as shown below.

In Intrinsically Safe applications where the DCS has galvanically separated inputs, you can use either the type of barrier shown below, or the type shown in Example 2.

When Ex applications are using an Ex approved Intrinsically Safe (I.S.) power supply unit, no barrier is required and grounding is optional.


The SITRANS LC 500 is equipped with HART communication1protocol2so that settings and values can be obtained and altered locally3or remotely.
Typical PLC configuration with HART
power supply1 R2= 250 Ω
PC/laptop with Simatic PDM or HART communicator3
The internal diagnostic functions continuously monitor the operation of the transmitter. An error signal is generated if a failure or irregularity occurs.
The SITRANS LC 500 sends the signal current according to the NAMUR NE 43 recommendation. During normal operation the current remains within the range from 3.8 to 20.5 mA. If the process exceeds its normal limits but is not in a fault or failure situation, the signal current will be outside the measurement range (4 to 20 mA) but will be limited to either 3.8 or 20.5 mA.
If a fault or a failure is detected, the signal current is set to either 3.6 mA or 22 mA, depending on the settings you have chosen. (This feature may be disabled by the user.)

Current values for signal detection
F = 1
F = 0
F = 1
0 3.6 3.8 4.0 20 22 20.5
Whenever the local situation allows, the zero adjustment and the full scale can be set using the push-button feature and the appropriate menu selection. In most cases it is possible to do a one point calibration1 by using the push-buttons to input the actual level in %.
The total isolation between the measurement circuit and the current- loop circuit provides immunity during the use of cathode protected measuring tanks. Connection to PLC equipment is possible without any difficulty.
The solid-state output is a polarity independent switch output. The solid-state switch has two possible functions.
See page 93 for an illustration of a typical application using SITRANS LC 500 as a level indicator, with the solid-state output connected to a relay which activates a pump.
The solid-state switch has its own parameter set: menu items 13 to18, (see Menu Levels 00 to 0F and 10 to 1F on page 37, and Rotary Switch Positions – Quick Reference chart on page 41).
In menu 0E and menu 0F, you set the Upper and Lower Range Values (URV and LRV) for relay operation. Within that range, the solid-state switch has independent settings for

Upper and Lower Threshold, (menus 13 and 14) and the accompanied delays (menus 15 and 16).
Initially the solid-state output is disabled for both signal output and fault/failure output (menu 17). When the solid-state switch is to be operated as fault/failure output (for example, for a separate shutdown system), we recommend disabling the operation for signal output (select Disabled Mode in menu 17 on page 70). There is no delay in the operation for fault/failure output.
The SITRANS LC 500 has a number of default factory settings. If the required settings for the application are known, the settings can be modified during final testing.
ID Has a unique serial number
TV0 UL 3300 pF [switch position (0)C]
TV0 LL 1.666 pF [switch position (0)B]
TV0 URV 3300 pF [switch Position (0)F]
TV0 LRV 0.00 pF [switch Position (0)E]
AO1 4-20 mA is 0-100% [position (0)8]
TAG "customer input data via HART"
DESCRIPTOR "customer input data via HART"
MESSAGE "Siemens Milltronics P I"
TV0 Units PF

DATE "customer input data via HART"
SENSOR SERIAL NUMBER "customer input data via HART"
FINAL ASSEMBLY NUMBER "customer input data via HART"
TV1 LRV 0 [switch position (0)E, TV1]
TV! URV 1.0 [switch position (0)F, TV1]
TV1 Units UNDEFINED

The SITRANS LC 500 user interface consists of the display (LCD), the rotary switch, and two push-buttons. The rotary switch enables you to select a particular item and/or variable for read-out and/or adjustment: the push-buttons allow you to select and/or alter a read-out or a value.
rotary switch menu selector

solid-state switch relay (any polarity)
current-loop connection (any polarity)
The seven-segment LCD (display) shows the value and/or diagnostic information. It is mainly for numeric data, but there are also a number of indicators which use alphabetic characters. A list of these LCD displays, together with the associated menu items, is shown in Appendix B: LCD display examples on page 74.
left-arrow indicates Menu Level 10 to 1F

The LCD will hold information for a long time even when not refreshed (for example, if there is a loss of power). The heartbeat indicator blinks continuously whenever the device is working. A still heartbeat signals that the device has stopped working.

Access data in the transmitter from 28 menu items divided between two menu levels: 00 to 0F and 10 to 1F. Use the rotary switch and push-buttons in combination to select an item and adjust the value.
The functions of each menu item are illustrated in application examples on page 93 to 94. Details on using each menu item are given in Appendix A: Menu Groups on page 54. (See also Rotary Switch Positions – Quick Reference on page 41 showing the switch position and button press combinations used to carry out different functions.)
User Interface
09 Stepsize Update Value
0A Damping page 56
0B Lower Sensor Limit page 56
0C Upper Sensor Limit page 57
0D Delta Range Setting page 57
0E Lower Range Value page 58
0F Upper Range Value page 59
00 Dynamic Value (PV)
02 Max./Min. Recorded Value page 60
01 Transmitter Variable select for PV page 60
Analog Output Signalling (loop-current)
07 Analog Signalling Mode page 64
08 Analog Fault Signalling page 66
Menu 10 to 1F Description Menu Group Details 10 Dynamic Value (PV) Transmitter Variable Values
page 59 1C Transmitter Variables Dynamic Value page 61 13 Upper Threshold Delay: solid-state output
page 67 14 Lower Threshold Delay: solid-state output page 68 15 Upper Threshold Setting: solid-state output page 68 16 Lower Threshold Setting: solid-state output page 69 17 Digital Signalling Mode page 70 18 Digital Fault Signalling page 71 11 Output Signal Processing Test
page 72 12 Factory Settings page 72 19 Range Inversion page 73 1F Keylock Level page 73 1A
Non-operational Spare 1B 1D 1E

The rotary switch gives you access first to the menu level and then to the menu item.
The rotary switch has a small slot where the current position can be read. The positions are read clockwise, and in increasing order: 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, and F. The position wraps from F to 0.
D
A
E
F
The switch can be turned in either direction. When it is turned to a new position, the LCD displays the new menu selection for 1 second, followed by the data for that position.
Certain menu selections return more than one piece of information per item: in that case the display alternates between the two values, for example, PV Value / Fault status.
The push-buttons
The push-buttons allow you to change the value of a menu item. Use the RED (+) button to adjust a value up; the BLUE (–) button to adjust a value down; or press both simultaneously for special applications. For a table showing the combinations of rotary switch positions and button presses used to carry out different functions, see page 41.
acceptance is indicated when the left-most colon on the LCD appears. (You have to press longer than the debounce time to have the action accepted: the debounce time varies according to the menu item selected.)

TV0
URV, LRV, Damping, USL and LSL
TV1 Can be user-defined
pF

Capacitance measurement systems require the instrument to be calibrated for a
particular application. Two methods of calibration are available:
We strongly recommend you read the full manual to use your device to its fullest
potential. However, if it is possible to adjust the level of the tank to the 0% and 100% levels, you can use the quick start sequence below to calibrate the instrument and get started.
Start Up
1 Calibrate the 0% setting (LRV - lower range value): menu 0E
For instruments without a stilling well, the 0% setting needs to be calibrated after the device is installed, and with the tank/vessel empty. Calibration is also sometimes neces- sary after installing a SITRANS LC 500 fitted with a stilling well, although in most cases the 0% setting is calibrated at the factory.
Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).
a Bring the product level to the height that corresponds to 0%.
b Turn the rotary switch to E (Empty).
c Press both buttons and hold for about 1 second: the 0% point is now set. 2 Calibrate the 100% setting (URV - upper range value): menu 0F
Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).
a Raise the product level to the height that corresponds to 100%.
b Turn the rotary switch to F (Full).
c Press both buttons and hold for about 1 second: the 100% point is now set. 3 View primary variable (PV): menu 00
Turn the rotary switch to 0. The LCD displays the actual pF reading. 4 The SITRANS LC 500 is now ready to operate.

cal PV Units PV Units PV Units PV Units PV Units
Default * TVO * 00 00 75% 25% Analog Disabled 1.0 1 1.666 pF 3300 pF 3300 pF 0 pF 3300 pF Menu LEVEL 1 (10 to 1F)
Settings Seconds Seconds % % O/ C O/C nor / inv Resp. Units Keylock
URV
Value (PV) URV =
0 1 2 3 4 5 6 7 8 9 A B C D E F
PV
PV
Default * * * 00 00 75% 25% Disabled Disabled nor * 0
= Min. LRV = Actual
PV
LRV
PV
LRV
for 4 c.q.
PV
PV
PV
PV
PV
Set to 1 Set to 1 Preset
PV
Rotary Switch Positions – Quick Reference
Selection PV Units Seconds Seconds % % mA mA Numeri-
to 0.01
MODE
MODE
Menu LEVEL 0 (00 to OF)
22 or 3.6 mA
Set FAULT:
Set FAULT:
for Solid-state Disable Fault
3.6 mA
Set Covered:
Set Covered:
4 to 20 mA (Anl)
00 < – > 100
00 < - > 100
00 < – > 100
do it Toggle Delay
00 < - > 100
% Mode Reset Hi/Lo
Units PV Units Numerical Factory
FAC
FAC
FAC
Units PV Units Num.
RED (+)
BLUE (–)
NO KEYS
RED (+)
BLUE (–)

Menu level 00 to 0F is the default start-up setting after power is applied or after a reset. Menu Level 10 through 1F is flagged in the LCD by an left-arrow indicator in the upper left corner of the LCD.
In menu 00 or 10, to see the current menu level selection, briefly press one of the buttons
(less than a second): the current selection is momentarily displayed.

Reset keylock level if necessary to enable settings to be changed: menu 1F (no change is necessary if the factory setting has not been changed)
Reset selection for transmitter variable if necessary to TV0 (units are pF): menu 01 (no change is necessary if the factory setting has not been changed)
For instruments without a stilling well, the 0% setting needs to be calibrated after the
device is installed, and with the tank/vessel empty. Calibration is also sometimes necessary after installing a SITRANS LC 500 fitted with a stilling well, although in most cases the 0% setting is calibrated at the factory.
a. Bring the product level to the height that corresponds to 0%. b. Set the rotary switch to E (Empty). c. Press both buttons and hold for about 1 second: the 0% point is now set.
Method 1. Set value for 100% (URV): units must be pF, (at Menu 01, Pv = 0)
a. Raise the product level to the height that corresponds to 100% b. Set the rotary switch to F (Full). c. Press both buttons and hold for about 1 second: the 100% point is now set.

Method 2. Set value for 100% (URV): values must be displayed as percent (at menu 01,
a. Calculate the percentage value of the current level. b. Set rotary switch to 1, and press both buttons to adjust the value to P. c. Set the rotary switch to F (Full). d. Press the RED (+) or BLUE (–) button to increase or decrease the reading on the
LCD until it matches the known (actual) percentage. The push-buttons appear to work in reverse for this function1. You may need to decrease the stepsize value (menu 09) in order to reach the desired value. e. 100% value is set.
Example: Set LRV in capacitance mode, then set menu 01 to Pv = P (percent mode) and immerse the probe in the product (values shown below are arbitrary example values only):
0% ( LRV) =14.20 pF 100% (URV) = 34.20 pF Span = 20 pF Current level = 28.20 pF Change in capacitance = 28.20 – 14.20 = 14 Current percent of span = 14/20 = 70% LCD displays 78.00 (percent)
In this example, to decrease the reading to 70.00, you need to press (+) to increase the span, which will reduce the percentage, until the value reaches 70.00. If the steps are too big you need to change the stepsize (menu 09) to a lower value.
Changing stepsize value: menu 09
Set rotary switch to 09, and press BLUE (–) button to reduce stepsize: values range from 0.01 to 1,000.
Example:
LCD displays 78.00 (percent) Known percent of span = 70% Decrease needed is 8, but setting for stepsize is 10: menu 09 set to U: 10. Press BLUE (–) button to reduce stepsize to 1: LCD displays U: 1.0. Return to OF, and decrease value to 70.00 (percent).
You may still need to reduce the stepsize further. If changing the stepsize value has no
apparent effect, press both buttons simultaneously to change the reading to 100%. From there you may adjust it until the correct percentage reading is reached.
Pv = P)

menu 01
a. To see the value displayed as percent, select menu 01 and press both buttons to
set Pv = P. b. To see the value displayed as pF, select menu 01 and increase or decrease the
value till Pv = 0.
The SITRANS LC 500 is now ready to operate. For a table showing the different functions
available, and the combinations of switch position and button presses used to carry out these functions, see page 41. For a detailed list of menu items, see Appendix A: Menu Groups on page 54.

The SITRANS LC 500 transmitter can be calibrated using HART, with a HART
communicator1; a laptop running Simatic PDM, or with the Host system (DCS). The local circumstances determine the manner in which calibration takes place. If the circumstances allow the product to be brought to the 0% and 100% point level, calibration is simple.
Examples of calibration using a Rosemount 275 hand-held communicator, fitted with the
GENERIC device descriptor:
For situations where the level of the product can be easily adjusted to 0 and 100%.
a. Select: Online b. Select: Device setup c. Select: Diag service d. Select: Calibration e. Select: Apply values (Display reads: Loop should be removed from automatic control. Select: Ok) f. Select: 4 mA g. Select: Apply new 4 mA input
a. Select: Read new value b. Select: Set as 4 mA value: the 4 mA point has now been set. c. Select: 20 mA d. Select: Apply new 20 mA input
a. Select: Read new value b. Select: Set as 20 mA value: the 20 mA point has now been set. c. Select: Exit
Calibration is complete.

For situations where the capacitance values are known in advance.
a. Select: Online b. Select: Device setup c. Select: Diag service d. Select: Calibration e. Select: Enter values f. Select: PV LRV
a. Select: Send (the values are now sent) b. Select: Put loop in manual c. Select: Return loop to auto
For situations where the capacitance values are unknown, and the level of the product
cannot be easily adjusted to 0% and 100%. In this case it is necessary to measure the capacitance value at various levels. These values can be read in % with the 275 communicator.
a. Select: Online b. Select: PV c. The measured value can be read continuously, even if the current loop value is
min. or max.
Example:
(181– 52)pF = 2.08 pF per %.
(79 – 17)%

The capacitance value for a 17% change in level is 17 * 2.08 = 35.37 pF.
The capacitance value for 0% is 52 – 35.37 = 16.62 pF (initial capacitance value).
The capacitance value for 100% is (100 * 2.08) + 16.62 = 208 + 16.62 = 224.6 pF.
described in Example 2.
For situations involving the re-adjustment of the LRV where the actual value is
determined to be one value but the measurement shows a different value.
The measured value can now be read continuously.
Example: Assume that the URV is set to 240 pF, that the actual value is 17%, but the
measurement is showing a different value.
the measured value = 80 pF
(100 – 17) % = 83%
(240 – 80) pF = 60 pF
160 pF = 1.927 pF per % 83%
The capacitance value for 100% (URV) is 100 * 1.927 = 192.7pF
The new LRV should be 240 –192.7 = 47.22 pF.
If the DCS and/or the 275 are fitted with the Device Descriptor for the SITRANS LC 500,
more functions can be used.
The available functions are:
(48) Read Additional Transmitter Status
(38) Reset Configuration Changed Flag
(128) Set Alarm Select
(129) Adjust for Product Build-up on Sensor

(130) Read Failsafe Mode selection
(131) Return device configuration info
(132) Set Variable Upper Limit
(133) Set Variable Lower Limit
(134) Write keylock value
(135) Read keylock value
(138) Write simulation time and value
(139) Read simulation time and value
(140) Write TV1 Units, URV and LRV
(141) Read TV1 Units, URV and LRV
(144) Reset Max/Min recorded PV
(145) Read Max/Min recorded PV
(150) Write analog signalling mode
(151) Read analog signalling mode
(152) Write digital signalling mode
(153) Read digital signalling mode
(154) Write analog threshold settings
(155) Read analog threshold settings
(156) Write digital threshold settings
(157) Read digital threshold settings
(160) Write timers analog signalling
(161) Read timers analog signalling
(162) Write timers digital signalling
(163) Read timers digital signalling

Test function
SITRANS LC 500 continuously performs a variety of tests to verify that the device is
functioning correctly. These include a test where a known capacitor is applied to the input of the device. The internal results must match the known capacitance value. If a deviation is detected the Fault/Failure can be flagged with a pre-set loop-current (user configurable) and as a status in each HART message.
In order to test the proper processing of signals in PLC/DCS equipment, SITRANS LC 500
allows you to invert the output signal status. In Menu 11, when both buttons are pressed simultaneously, the signal outputs switch to their opposite state. When the buttons are released, the outputs revert to the initial state.
If no Fault/Failure is present and no buttons are pressed, the display for menu 11
alternates between two test patterns which together illuminate all the segments of the display. If the loop-current control is in analog mode the loop current will hold the last value, during this test.
Under normal circumstances, the SITRANS LC 500 transmitter requires no maintenance.
However, we recommend that you schedule periodic inspections of SITRANS LC 500.
The inspection can be subdivided into two parts:
a. Inside enclosure is clean and dry.
b. Enclosure sealing is intact and functioning properly (not hardened).
c. All screw connections are tight.
d. Ground connections inside the housing are solid.
e. Ground connections outside the housing are solid.

f. The coaxial connector is free of dirt or deposits.
g. No cables or wires are jammed under the cover.
a. Check for required minimum terminal voltage (see page 23 for supply voltage
requirements).
b. Confirm that Menu 08 is set to enable analog fault signalling: display should read
F: Hi or F: Lo. (If there is a fault condition, it will read F= Hi or F= Lo, when buttons are released.)
c. Check that the current goes to the alarm position (3.6 or 22 mA) if the coaxial
plug is unplugged: at menu 00, the LCD should display ‘ooL’. After the test, replace the coaxial plug.
d. Confirm that Menu 18 is set to enable digital fault signalling: the LCD should
display F= cc or F= co, when buttons are released.
e. Check that the solid-state output goes to the alarm position (open/close) if the
coaxial plug is unplugged. After the test, replace the plug.
f. Via HART: Check that the PV goes to 0 pF when the coaxial plug is unplugged, (±0.15 pF is allowed). If it does, switch the output current to 4 mA and check the current through the loop, then to 20 mA and check the current through the loop. After the test, replace the plug.

If you are unable to change settings:
If you can change settings:
If the LCD displays a negative reading, typically around minus 300 pF, this often indicates a short circuit in the probe assembly:

Error Messages (push-button operation)
Fault/failure has been detected
The product level has risen above the Upper Sensor LImit, or fallen below the Lower Sensor Limit
ooLa Output out-of-limits
a. Alternates with the primary variable (PV).
32 program memory checksum error Device is faulty
Possible short circuit in the probe or the device wiring
8 DAC drive failure: the current as set by the DAC does not match the value measured by the ADC
Possible fault in the device, or lack of sufficient energy at the device terminals
Usually indicates a fault in the connection between the transmitter module and the probe (the coaxial connector is off)
0 PV value is outside the limits set (USL and LSL)
Flta

The data in the transmitter is accessible as 281 menu items divided between two menu levels: 00 to 0F and 10 to 1F. You can switch between the two levels at position 00 and 10.
The menu items are grouped according to function, with a detailed description of each item. The menu groups are shown below.
Damping Lower Sensor Limit
Menu 09 Menu 0A Menu 0B Menu 0C Menu 0D Menu 0E Menu 0F
s e e p a g e 5 5 s e e p a g e 5 6 s e e p a g e 5 6 s e e p a g e 5 7 s e e p a g e 5 7 s e e p a g e 5 8 s e e p a g e 5 9
Highest Lowest Recorded Value
– select for PV
Menus 00 and 10 Menu 02 Menu 01 Menu 1C
see page 59 see page 60 see page 60 see page 61
Menu 03 Menu 04 Menu 05 Menu 06 Menu 07 Menu 08
see page 62 see page 62 see page 63 see page 64 see page 64 see page 66
Menu 13 Menu 14 Menu 15 Menu 16 Menu 17 Menu 18
see page 67 see page 68 see page 68 see page 69 see page 70 see page 71
Output Signal Processing Test Factory Settings Range Inversion Keylock Level
Menu 11 Menu 12 Menu 19 Menu 1F
see page 72 see page 72 see page 73 see page 73

Transmitter: Variable Settings: menu level 0
This menu selection controls the increment/decrement step-size for the menus 0B, 0C, 0D, 0E, 0F, and 03.
Menu Item
Affected by:
Left Arrow Description Values
09 01 9 Off Stepsize Update Value Range: 0.01 to 1000

Damping slows the measurement response to a change in level, and is used to stabilize the reading1. The Damping Value is not in seconds but is a factor that controls the rate of change for the dynamic value of the TV currently selected.
The increment/decrement step size is subject to the setting on Menu 09.
Menu Item
Affected by:
Left Arrow Description Values
0A 01, 09 A Off Damping Range: 1 to 10,000
Factory setting 1.00
The Lower Sensor Limit (LSL) is the lower of two limit settings. Whenever the PV value (Menu level 0) drops below the Lower Sensor Limit, the measurement is considered at fault and the LCD displays ooL, alternating with PV.
If the display mode is in %, this selection is disabled and the LCD displays -. The transmitter variable on which this menu selection operates is chosen in Menu 01.
The increment/decrement step size is subject to the setting from Menu 09.
Menu Item
Affected by:
Left Arrow Description Values
0B 01, 09 B Off Lower Sensor Limit Range 0 to 3300
Factory setting 1.66

The Upper Sensor Limit (USL) is the upper of two limit settings. Whenever the PV value (Menu Level 0) rises above the upper limit setting, the measurement is considered at fault and the LCD displays ooL, alternating with PV.
If the display mode is in %, this selection is disabled and the LCD displays -. The transmitter variable on which this menu selection operates is chosen in Menu 01.
The increment/decrement step size is subject to the setting from Menu 09.
Menu Item
Affected by:
Left Arrow Description Values
0C 01, 09 C Off Upper Sensor Limit 3300 to 0
The Delta Range Setting allows you to commission the unit for overfill or underfill protection where it is impossible to bring the product to those levels in normal process conditions. This feature is not normally used for the SITRANS LC 500.
Overfill protection is used in applications where the probe is normally uncovered. Delta Range Setting adds the minimum span to the Lower Range Value: the result is used to update the Upper Range Value. If the process level exceeds the new URV, a fault is signalled.
Underfill protection would be used in applications where the probe is normally covered. In this case, Delta Range Setting subtracts the minimum span from the Upper Range Value and uses the result to update the Lower Range Value. If the process value drops below the new LRV, a fault is signalled.
The loop-current control must be in 2-state mode (Menu 07) for Menu 0D to display the Delta Range Setting. When the loop-current control is in Analog mode, Menu 0D displays -.
Factory setting 3300

The transmitter variable on which this selection is based is chosen in Menu 01. The increment/decrement step size is set at Menu 09.
Appendix A
Menu Item
Affected by:
Left Arrow Mode Description Values
2-state Delta Range Setting (enabled)
0D 01, 07, 09 D Off
Analog * Display shows -
Lower Range Value (LRV) is the setting for 0% of the operating range, in most cases an empty vessel/tank. If the display mode is in % this selection is disabled and the LCD displays -.
The transmitter variable on which this menu selection operates is chosen in Menu 01. For TV0 the LRV is in most cases Factory Set to the probe capacitance in free air.
The increment/decrement step size is subject to the setting from Menu 09.
Menu Item
Affected by:
Left Arrow Mode Description Values
Factory setting Probe capacitance in air
0E 01, 09, 0B, 0C E Off Analog
Display percent Display shows -
When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value is rejected and the previous value remains unchanged.
Span setting

Upper Range Value (URV) is the setting for 100% of the operating range, in most cases a full vessel/tank. The transmitter variable on which this menu selection operates is chosen in Menu 01. For TV0, the URV is in most cases Factory Set to the probe capacitance in water.
The increment/decrement step size is subject to the setting from Menu 09.
Menu Item
Affected by:
Left Arrow Mode Description Values
0F 01, 09, 0B, 0C F Off Analog
Factory setting Probe capaci- tance in water
Display percent Display shows -
When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value is rejected, and the previous value remains unchanged.
The value for the Primary Variable is displayed as either units or percent of range, selected in menu 01. When 2-state mode is selected in menu 07 the LCD display indicates the probe status:
If the internal diagnostics detect a fault or failure, the display alternates between the PV value and the fault/failure message ‘Flt’. If the product level goes outside the limit settings, then the display alternates between the PV value and ‘ooL’. Alternatively, if the simulation

(SIM) function has been selected via HART, the LCD alternately displays the text SIM or the applied simulation value for the duration of the simulation.
Appendix A
Menu Item
Affected by:
Left Arrow Description Values
00 01 0 Off Dynamic Value (PV) Units or % of range, selected in menu 01 10 On
To change from menu 10 to menu 00:
To change from menu 00 to menu 10:
Rotary Switch Position
Menu Item
Left Arrow Description
02 2 Off Highest / Lowest Recorded Value
1. Set the rotary switch to 2. The Highest / Lowest recorded values for TV currently selected are displayed alternately. 2. Press the RED (+) button to select the Highest recorded value for display, or: Press the BLUE (–) button to select the Lowest recorded value for display, 3. Press both buttons simultaneously for more than one second to reset the recorded values back to the dynamic value of this TV. (This will also occur after a reset [power-down] of the device.)
Select the Transmitter Variable (TV) for the Primary Variable (PV).
Menu Item
Left Arrow Description Values
0 * TVO (units are pF)
01 1 Off Transmitter Variable selection for PV
1 TV1 (units are user definable
P TV0 (values displayed as %)
only via HART)

If PV = 0, TV0 is selected for PV, URV, LRV, USL, LSL, Damping, and Highest/Lowest
recorded value. The units are implicitly1 pF.
If PV = 1, TV1 is selected for PV, URV, LRV, USL, LSL, Damping, and Highest/Lowest
recorded value. The units are user definable but only by HART.
If PV = P, TV0 is selected: however, the values for PV and URV are displayed in %; LRV,
USL, LSL, are blanked out with -; all other fields are identical to that of TV0.
This menu selection allows you to read the values of the dynamic variables TV0, TV1, TV22, and TV3. When no buttons are pressed, the LCD displays the dynamic value for TV0.
Menu Item
Left Arrow Mode Description Action Values
TV0 * Transmitter Variables Dynamic Value
Dynamic value for TV0
Transmitter Variables Dynamic Value
Dynamic value for TV1
Press and hold RED (+) button
Transmitter Variables Dynamic Value
Dynamic value for TV2
Press and hold BLUE(–) button
Transmitter Variables Dynamic Value
Both buttons pressed simultaneously
Dynamic value for TV3
Display shows 0.00
No buttons pressed · 1C C On · Invalid selection

Analog mode (the loop-current) can provide either:
The Upper Threshold Setting controls the Activation delay: the amount of time that has to pass uninterrupted with the probe covered to a level above the Upper Threshold Setting before the timer expires. When the timer expires, the output signal complies with the setting from Menu 08 for a covered probe. Whenever the level drops below the Upper Threshold Setting before the timer expires, the timer is restarted.
As an extra identifier, an upward running A is displayed to the right of the value.
Menu Item
Affected by:
Left Arrow Mode Added Indicator Description Values
Upward running A at right of value
03 07 3 Off
Display shows -
The Lower Threshold Setting controls the Deactivation delay: the amount of time that has to pass uninterrupted with the probe covered to a level below the Lower Threshold Setting before the timer expires. When the timer expires, the output signal will comply with the setting from Menu 08 for an uncovered probe. Whenever the level rises above the Lower Threshold Setting before the timer expires, the timer is restarted.
As an extra identifier, a downward running A is displayed to the right of the value..

Menu Item
Affected by:
Left Arrow Mode Added Indicator Description Values
Appendix A
Downward running A at right of value
04 07 4 Off
Ana- log * Display shows -
The Upper Threshold Setting is the % of range above which the probe is considered covered. In order to switch the output signal, the corresponding delay time has to be met (Menu 03).
The loop-current control (Menu 07) must be in 2-state mode for this menu to display the Upper Threshold Setting in percent. As an extra identifier, an upward ramp is displayed to the right of the value.
Menu Item
Affected by:
Left Arrow Mode Added Indicator Description Values
2-state Upward ramp at right of value
05 07 5 Off
Display shows -

The Lower Threshold Setting is the % of range below which the probe is considered uncovered. In order to switch the output signal, the corresponding delay time has to be met (Menu 04).
The loop-current control (Menu 07) must be in 2-state mode for this menu to display the Upper Threshold Setting in percent. As an extra identifier, a downward ramp is displayed to the right of the value.
Menu Item
Affected by:
Left Arrow Mode Added Indicator Description Values
2-state Downward ramp at right of value
06 07 6 Off
Display shows -
The factory setting is for Analog mode (the loop-current is proportional with the percentage of the range). When no buttons are pressed, the LCD displays the current mA value.
2-state Signalling Mode provides a 4 mA or 20 mA output. The settings are relative to a covered probe:
Lower Threshold Setting · % of range · Analog *

Menu selections 03, 04, 05, and 06 set the criteria for delay and threshold that have to be met for a change in output signal.
Menu Item
Affected by:
Left Arrow Mode Description Action Values
Appendix A
Signal propor- tional to % of range
Press both buttons simul- taneously
07 03, 04, 05, 06, 08 7 Off
2-state High Press RED (+)
2-state Low Press BLUE (–)
a. While button is pressed, display reads C: Hi. When button is released, display shows 20.00 if the probe is covered, or 4.00 if it is uncovered.
b. While button is pressed, display reads C: Lo. When button is released, display shows 4.00 if the probe is covered, or 20.00 if it is uncovered.
Set the rotary switch to 7. To change the mode to 2-state High, press the RED (+) button for more than one second: the LCD displays C: Hi. When the button is released, the loop- current will switch to 20 mA if the probe is covered, or 4 mA if it is uncovered.
To change the mode to 2-state Low, press the BLUE (–) button for more than one second: the LCD displays C: Lo. When the button is released, the loop-current will switch to 4 mA, and if the probe is uncovered, or 20 mA if the probe is covered.
Analog Mode may be restored at any time by pressing both buttons simultaneously for more than one second. The LCD displays C: An while the two buttons are pressed, and displays the current reading when the buttons are released.
The loop-current will be between 3.8 and 20.5 mA, and will saturate to one of these values if the level goes beyond the Upper or Lower range settings.
Analog * · 2- state

When 2-state fault signalling is enabled, in the case of a fault the mA output is 3.6 mA or 22 mA1, depending on the setting. The mA output is viewed at menu 07.
Menu Item
Left Arrow Description Action Values
2-state Fault Signalling (disabled) * Press both buttons simultaneously
2-state High Fault Sig- nalling (enabled) Press RED (+)
2-state Low Fault Signal- ling (enabled) Press BLUE (–)
a. If the LCD displays an equal sign (=) in place of the colon (:) this indicates that the loop-current is at fault/failure level. For example F: Hi becomes F= Hi.
Set the rotary switch to 8.
08 8 Off

To set values for Upper and Lower Threshold Delay, and Upper and Lower Threshold Setting, the solid-state switch output must be enabled (menu 17). When solid-state switch output is disabled these menu selections display only -.
Upper Threshold Delay (solid-state output)
The Upper Threshold Delay controls the Activation delay: the amount of time that has to pass uninterrupted with the probe covered to a level above the Upper Threshold Setting before the timer expires. After the timer expires, the output signal will comply to the setting from Menu 18 for a covered probe. Whenever the level drops below the Upper Threshold Setting before the timer expires, the timer is restarted.
When the solid-state switch control (Menu 17) is disabled, menu 13 displays -. When the solid-state switch control is enabled, menu 13 displays the Activation delay in seconds. As an extra identifier, an upward running d is displayed to the right of the value.
Menu Item
Affected by:
Left Arrow Mode Identifier Description Values
Solid-state switch con- trol enabled
Upward running d at right of value
13 17 3 On
Display shows -
Solid-state switch con- trol disabled
First select the solid-state switch output at menu 17 (contact open or contact closed).
Upper Threshold Delay · *

The Lower Threshold Delay controls the Deactivation delay: the amount of time that has to pass uninterrupted with the probe covered to a level below the Lower Threshold Setting before the timer expires. After the timer expires, the output signal will comply to the setting from Menu 18 for an uncovered probe. Whenever the level rises above the Lower Threshold Setting before the timer expires, the timer is restarted.
When the solid-state switch control (Menu 17) is disabled, menu 14 displays only -. When the solid-state switch control is enabled, this menu displays the Deactivation delay in seconds. As an extra identifier, a downward running d is displayed to the right of the value.
Menu Item
Affected by:
Left Arrow Mode Identifier Description Values
Solid-state switch con- trol enabled
Downward running d at right of value
14 17 4 On
Solid-state switch con- trol disabled
* Display shows -
First select the solid-state switch output at menu 17 (contact open or contact closed).
The Upper Threshold Setting is the % of range above which the probe is considered covered. In order to switch the output signal, the corresponding delay time has to be met (Menu 13).
When the solid-state switch control (Menu 17) is disabled, menu 15 displays only -. When the solid-state switch control is enabled, menu 15 displays the Upper Threshold setting in percent. As an extra identifier, an upward ramp is displayed to the right of the value.
Lower Threshold Delay

Menu Item
Affected by:
Left Arrow Mode Identifier Des-
cription Values
Appendix A
Solid-state switch con- trol enabled
Upward ramp at right of value
15 17 5 On
Solid-state switch con- trol disabled
* Display shows -
First select the solid-state switch output at menu 17 (contact open or contact closed).
The Lower Threshold Setting is the % of range below which the probe is considered uncovered. In order to switch the output signal, the corresponding delay time has to be met (Menu 14).
If the solid-state switch control (Menu 17) is disabled, menu 16 displays -. When the solid-state switch control is enabled, menu 16 displays the Lower Threshold Setting in percent. As an extra identifier, a downward ramp is displayed to the right of the value.
Menu Item
Affected by:
Left Arrow Mode Added indicator
Description Values
Solid-state switch con- trol enabled
Downward ramp at right of value
16 17 6 On
Solid-state switch con- trol disabled
* Display shows -
First select the solid-state switch output at menu 17 (contact open or contact closed).

Controls the solid-state switch output and allows you to set the switch to contact open or contact closed. The settings are relative to a covered probe, and the criteria are set in menu 15 and 16. With contact closed, the switch is on: with contact open the switch is off.
While a button is pressed, the LCD displays S: cc1 (contact closed) or S: co (contact open). When the button is released an equal sign (=) indicating status replaces the colon, and the reading depends on the status of the probe2.
Menu Item
Affected by:
Left Arrow Mode Description Action Values
Disabled * Press and hold both buttons
Press and hold RED (+) button
17 18 7 On
S: cc
Press and hold BLUE (–) button
S: co
a. While the button is pressed: when released the display depends on the probe status.
Menu selections 13, 14, 15 and 16 set the criteria for delay and threshold that have to be met for a change in output signal.
Display showsa · Digital Signal- ling Mode · Display showsa

Controls the solid-state switch response to a fault/failure and allows you to select either contact open or contact closed. With contact closed the solid-state switch will be on: with contact open the solid-state switch will be off.
While a button is pressed, the LCD displays F: cc1 (contact closed) or F: co (contact open). When the button is released an equal sign (=) indicating status replaces the colon, and the reading depends on the status of the probe.
Menu Item
Left Arrow Mode Description Action Values
Disabled * Press and hold both buttons
Press and hold RED (+) button
Press and hold BLUE (–) button
Set the rotary switch to 8. Press the RED (+) or BLUE (–) button to change the setting. The disabled mode can be restored at any time by pressing both buttons simultaneously for more than one second.
18 8 On · Digital Signalling Mode

Appendix A
Displays the Fault/Failure information. If operation is normal, two test displays alternate, which light up all the LCD segments in a cycle. If there is a fault or failure, an error code is displayed. See the detailed list of error codes and their meanings, page 53.
Menu Item
Left Arrow Description
11 1 On Output Signal Processing Test
Set the rotary switch to 1.
To change the state of the output signals, press and hold both buttons simultaneously: the digital mode outputs (the solid-state switch and the loop-current control in digital mode) change to their opposite state. Thus 4mA becomes 20mA and contact open becomes contact closed. This feature allows you to verify that the output signals are properly processed further on in the PLC/DCS system: if the normal state is non-alarm, changing the state should generate an alarm.
The outputs stay in the opposite state as long as both buttons are pressed.
Displays whether the factory settings are still in place, or how much they have been changed, and allows you to restore the factory settings.
Menu Item
Left Arrow Description LCD Display Meaning
No parameters changed from factory setting
Factory Settings FAC A
FAC ? More parameters have been changed
Set the rotary switch to 2. To restore the factory settings, press both buttons simultaneously to change the LCD to ‘do it’ and hold both buttons for more than one second. When the buttons are released, the LCD displays FAC A.
12 2 On

Displays whether the device is operating with a normal or inverted range setting. A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV (Menu 0F): the LCD displays inv.
Rotary Switch Position
Menu Item
Left Arrow Description Mode Values
19 9 On Range Inversion normal * Display shows nor
inverted Display shows inv
Controls the access protection level for the device. The factory setting is a local protection level of 0, which places no restriction on modifying settings locally.
Protection Display
Menu
Left Arrow
Item
Level Description local settings
HART settings
0 * No restrictions PL 0
No restrictions PH 0
1 Disables 2-button adjustments PL 1 PH 1
2 Disables 1-button adjustments PL 2 PH 2
3 Disables all changes PL 3 PH 3
1F F On

LCD: alphanumeric display examples
Menu Item Indicator:
Current-loop, output in Analog (proportional) mode:
An
Menu Level Indicator:
Indicator for range operation, normal (URV > LRV):
nor
Internal diagnostics detects anomaly:
Indicator for range operation, inverted (URV < LRV):
FLt
inv
Solid-state switch output closed when probe is covered (displayed while button pressed):
Output out of limits, PV outside Variable Limits:
S: oc
Solid-state switch output open when probe is covered (displayed while button pressed):
Indicator for Factory Set, all parameters are original:
FAC A
Solid-state switch output closed and probe covered, = sign indicates current probe status (displayed when button released):
Indicator for Factory Set, range settings have been changed:
S= oc
Indicator for Factory Set, other settings have been changed also:
Solid-state switch output disabled:
FAC?
Indicator for Factory Set, reset all variables back to factory setting:
Solid-state switch output open when Fault detected:
do it
Solid-state switch output closed when Fault detected:
Function test indicator, all outputs in digital mode invert their output status:
0 = /o
Solid-state switch / current-loop output functions due to Faults are disabled:
Transmitter variable selected for PV:
F: – –
Current-loop, current goes to 22 mA when Fault detected:
Keylock protection level:
Hi
Simulation is active. Transmitter Variable TVO driven by simulation value:
Current-loop, current goes to 3.6 mA when Fault detected:
SIM

HART 1 Communications for the SITRANS LC 500
Highway Addressable Remote Transducer (HART) is an industrial protocol that rides on top of a 4-20 mA signal. It is an open standard, and full details about HART can be obtained from the HART Communication Foundation at www.hartcomm.org
The SITRANS LC 500 can be configured over the HART network using either the HART Communicator 275 by Fisher-Rosemount, or a software package. There are a number of different software packages available.The recommended software package is the Simatic Process Device Manager (PDM) by Siemens.
In order to configure a HART device, the configurator must have the HART Device Descriptor for the unit in question. HART DD’s are controlled by the HART Communications Foundation. The HART DD for the SITRANS LC 500 will be released in 2003. Please check availability with the HART Communications Foundation. Older versions of the library will have to be updated in order to use all the features in the SITRANS LC 500.
Simatic Process Device Manager (PDM)
This software package is designed to permit easy configuration, monitoring, and troubleshooting of HART and Profibus PA devices. The HART DD for the SITRANS LC 500 was written with Simatic PDM in mind and has been extensively tested with this software.
Manufacturer Identification Code = 84 Manufacturer Device Type Code = 248 Expanded Device Type Code = 21752
Field Device Category = A Capacitance Number (CN) = 1

Root Menu Device Setup Menu Process Variables
Process variables menu Diagnostics/service Basic setup menu Detailed setup menu Autocal Review menu
Sensor digital value Input percent range A0 analog value PV maximum recorded PV minimum recorded Reset max/min records
Applied rerange Keypad rerange Zero correction
PV digital value PV upper range value PV lower range value SV digital value SV upper range value SV lower range value
Self test Loop test Calibration Dac trim
PV upper sensor limit PV lower sensor limit PV minimum span PV sensor units PV Upper range value PV Lower range value
Tag PV digital units Device info menu PV transfer function PV damping value
Damping value Upper range value Lower range value Transfer function Percent range
Measuring elements menu Signal conditioning menu Output conditioning menu Device info menu
PV analog value PV alarm select Dac trim Loop test
High calibration level Low calibration level
Analog output menu Hart output menu
Polling address Request preambles
Review Menu Device Info Menu
Device type Private label distribution PV digital units Sensor units Upper sensor limit Lower sensor limit Minimum span Damping value Input percent range Transfer function Input range units Upper range value Lower range value A0 analog value A0 alarm code Write protect Manufacturer ID Device ID Tag Descriptor Message Date Universal revision Transmitter revision Software revision Polling address Request preambles
Private label distribution Device type Device ID Tag Date Write Protect Descriptor Message PV sensor serial number Final assembly number Device revisions menu
Universal revision Transmitter revision Software revision

Additional response code information, Second Byte.
When the transmitter detects a malfunction, the Analog Output will be set in a fault state.
When any of the settings in EEROM is changed either by a write command or by manual ZERO or SPAN adjust, this bit is set. Use command 38 to reset.
This bit is issued once after an initialisation cycle is complete; this can occur after a power loss or as a result of a (watchdog) reset.
When any of the extended status bits is set this flag is raised. Use command 48 to get detailed status information.
This bit is set as long as the Primary Variable Analog Output is set to a fixed value.
Bit #2: Primary Variable Analog Output Saturated
Flag is set when the Primary Analog Output saturates below 3.8 mA and above 20.5 mA.
This flag is set whenever the Transmitter Variable #0 (in pF), the Primary Variable exceeds the Sensor Limits returned with Command 14, Read Primary Variable Sensor Limits.

SITRANS LC 500 transmitter Conformance and Command Class summary.
Number Description Usage
Conformance Class #1
0 Return Unique Identifier Universal
1 Read Primary Variable
0 Return Unique Identifier Universal
2 Read PV Current and Percent of Range
11 Read Unique Identifier Associated with Tag Universal
13 Read Tag, Descriptor, and Date
14 Read Primary Variable Sensor Information
15 Read Primary Variable Output Information
16 Read Final Assembly Number
Appendix C
3 Read Dynamic Variables and PV Current Universal
33 Read Selected Dynamic Variables Common Practice
48 Read Additional Transmitter Status Common Practice
50 Read Dynamic Variable Assignments Common Practice Conformance Class #4
34 Write PV Damping Value Common Practice
35 Write Primary Variable Range Values
36 Set Primary Variable Upper Range Value
37 Set Primary Variable Lower Range Value
38 Reset Configuration Changed Flag
40 Enter/Exit Fixed Primary Var. Current Mode
6 Write Polling Address Universal
18 Write Tag, Descriptor and Date
19 Write Final Assembly Number
44 Write Primary Variable Units Common Practice
45 Trim Primary Variable Current DAC Zero
46 Trim Primary Variable Current DAC Gain
49 Write Primary Variable Sensor Serial Number
59 Write Number of Response Preambles
12 Read Message · 17 Write Message

Number Description Usage
128 Set Alarm Select Transmitter Specific
129 Adjust for Product Build-up on Sensor
130 Read Failsafe Mode selection
131 Return Device Config. Info.
132 Write Variable Upper/Lower Limit Values
133 Read Variable Upper/Lower Limit Values
134 Write Keylock Value
135 Read Keylock Value
138 Write Simulation Timer and Value
139 Read Simulation Timer and Value
140 Write S.V. Units and Range Values
141 Read S.V. Unites and Range Values
144 Reset recorded PV min./max. values back to PV
145 Return recorded PV min./max. values
150 Write Analog Signalling Mode
151 Read Analog Signalling Mode
152 Write Digital Signalling Mode
153 Read Digital Signalling Mode
154 Write Analog Threshold Settings
155 Read Analog Threshold Settings
156 Write Digital Threshold Settings
157 Read Digital Threshold Settings
160 Write Delay Timers Analog Signalling
161 Read Delay Timers Analog Signalling
162 Write Delay Timers Digital Signalling
163 Read Delay Timers Digital Signalling
The SITRANS LC 500 transmitter implements damping on most of the transmitter variables. The damping setting may vary from 1 (shortest value) to 10000 (longest value).
The flags byte of Command #0 referenced in the Universal Command Specification document will have Bit #1 (Command #39, EEPROM Control Required) set to 0, indicating that all data sent to the transmitter will be saved automatically in the non-volatile memory upon receipt of the Write or Set Command. Command #39, EEPROM Control, is not implemented.

The SITRANS LC 500 transmitter supports MultiDrop Operation.
The SITRANS LC 500 transmitter does not support Burst Mode.
The Transmitter Variable #0 Units are in pF and cannot be changed.
The Transmitter Variable #1 Values may be set to any Units and Value with Command #140. The Transmitter Variable Range Values may be read at any time with Command #141.
The value returned as Secondary Variable (S.V.) is the result of the following calculation:
TV1 = TV0 Dynamic Range Value in percent x ({TV#1}URV – {TV#1}LRV) + {TV#1}LRV.
This method provides a means of converting TV#0, which is always in pF, to alternative units (level or volume).
For a document listing the additional Universal Command Specifications, please contact Technical Publications at techpubs@siemens-milltronics.com


SITRANS LC 500 Block Diagram Digital Fault/Failure (menu 18)

Range 0 - 100 % Current in mA Range 100 - 0 %
0 4.0 100
5 4.8 95
10 5.6 90
15 6.4 85
20 7.2 80
25 8.0 75
30 8.8 70
35 9.6 65
40 10.4 60
45 11.2 55
50 12.0 50
55 12.8 45
60 13.6 40
65 14.4 35
70 15.2 30
75 16.0 25
80 16.8 20
85 17.6 15
90 18.4 10
95 19.2 5
100 20.0 0

Standard Version
Standard Version S-Series, Threaded
ø160 (6.3”)
+175 (6.9”)
40 (1.57”)
ø16 (0.63”)
or ø24 (0.94”)

S-Series Cable Version
(with weight)
(with anchor)
ø160 (6.3”)
120 (4.72”)
55 (2.17”)
Length +175 (6.9”)
ø9 (0.35”)
125 (4.9”)



or ø24 (0.94”)

Probe Seal · (inactive)


ø16 (0.63”) or ø24 (0.94”) ø16 (0.63”) or ø24 (0.94”)





Designed specifically for interface level where a long distance active shield portion of the electrode is required (up to 35 meters) before the measurement portion of the electrode begins. Common in large storage tanks for oil where the bottom of the tank invariably has a layer of water below the oil. Often, when measurement spans as much as 5.5 meters (for the water), up to 35 meters of flexible bellows cable are used.


ø 16 mm (0.63”) or ø 24 mm (0.94”)
Conduit Entry:
100 mm (3.9”) inactive tip


The hygienic design includes threaded and tri-clamp versions for use in the food and pharmaceutical industry.


ø16 (0.63”) or







Generic Application Calculations
The capacitance expected in a cylindrical tank with a probe centrally mounted is estimated using the following formula:
C ε 24 L × Log D d ⁄ ( ) pF =
C ε 7.32 L × Log D d ⁄ ( ) pF =
(L in meters) or (L in feet)
Where: C = capacitance value in pF ε r = relative dielectric constant L = active measurement length D = internal tank diameter d = electrode diameter 24 = a K constant for dimensions in meters 7.32= a K constant for dimensions in feet or inches ε r = 1 (air) ε r = 2 (oil)
0.25 m (0.82’)
L = 0.95 m
(3.12’)
d = 16 mm
(0.05’)
D = 1.0 m (3.28’)
Capacitance in air:
24 0.95 × Log 1 0.016 ⁄ ( ) pF 12.7pF = =
Dimensions in meters:
7.32 0.82 × Log 1 0.06 ⁄ ( ) pF 12.7pF = =
Dimensions in feet:
If the same vessel is filled with oil, relative dielectric constant for oil (2) replaces the relative dielectric constant for air (1), and the resulting calculation is:
24 0.95 × Log 1 0.016 ⁄ ( ) pF 25.4pF = =
7.32 3.12 × Log 3.28 0.05 ⁄ ( ) pF 25.4pF = =
The initial capacitance value at 0% (probe in air) is 12.7 pF, and the capacitance value for 100% (tank filled with oil) is 25.4 pF.

After calibration:
12.7 pF ≅ 0% ≅ 4 mA or 20 mA
25.4 pF ≅ 100% ≅ 20 mA or 4 mA
7.32 4.5 × Log 60 0.63 ⁄ ( ) pF 16.6pF = =
500 6” (0.5ft)
7.32 4.5 × Log 60 0.63 ⁄ ( ) pF 33.2pF = =
For this slightly larger tank, the capacitance ranges from 16.6 pF for 0% (probe in air) to 33.2 pF for 100% (tank filled with oil).
(4.5ft)
d = 0.63”
After calibration:
16.6 pF ≅ 0% ≅ 4 mA or 20 mA 33.2 pF ≅ 100% ≅ 20 mA or 4 mA
60” (5.0ft)
Cair εair · Coil εoil

Example: The level is to be held between 90% and 8%.
units or% selected in menu 01 0-100% auxiliary power pump power
solid- state output current loop connection
75.8 pF
(menu 0F) URV = 100% Upper Threshold Setting = 90% menu 15 (activation hysteresis)
solid-state switch output: selected at menu 17 and controlled by menus 13 to 18.
menu 16 (deactivation hysteresis)
Lower Threshold Setting = 8%
14.3 pF
(menu 0E) LRV = 0%
Device settings: (The device is first restored to factory settings before being commissioned) TV0 selected: Transmitter Variable 0 is PV Menu 01 reads Pv = 0 Lower Range Value (0% of range) is set to 14.3 Menu 0E reads 14.30 Upper Range Value (100% of range) is set to 75.8. Menu 0F reads 75.80 Current loop is in analog mode, with both buttons pressed Menu 07 reads C:An Solid-state switch enabled, contact closed selected Menu 17 reads S:cc1
Activation hysteresis is set to 90. Menu 15 reads 90.0 Deactivation hysteresis is set to 8. Menu 16 reads 08.0.
When the level reaches 90%, the solid-state output is closed and the pump is started via the auxiliary circuit. When the level drops to 8% the solid-state output is opened, the auxiliary circuit is deactivated, and the pump stops.
Active Shield section · (menu 0C) USL · (menu 0B) LSL

In 2-state mode, the loop current signals whether the probe is covered or uncovered, and the continuous level measurement is unavailable.
Current activated relay module
83.5pF
75.8 pF
(menu 0F) URV = 100% Upper Threshold Level = 90% menu 05 (activation hysteresis)
2-state output (menu 07)
menu 06 (deactivation hysteresis)
Lower Threshold Level = 8%
14.3 pF
Menu 0E LRV = 0%
7.3 pF
Device settings: (The device is first restored to factory settings before being commissioned) TV0 selected: Transmitter Variable 0 is PV Menu 01 reads Pv = 0 Lower Range Value (0% of range) is set to 14.3 Menu 0E reads 14.30 Upper Range Value (100% of range) is set to 75.8 Menu 0F reads 75.80 Current loop is in 2-state mode (C: Hi selected) Menu 07 reads C:Hi 2-state fault signalling enabled (F: Hi selected Menu 08 reads F:Hi1
Activation hysteresis is set to 90 Menu 05 reads 90.0 Deactivation hysteresis is set to 8 Menu 16 reads 08.0.

USL is set to 83.50 pF Menu 0C reads 83.50
LSL is set to 7.3 pF Menu 0B reads 7.30
When the process level reaches 90%, the probe is considered covered and the output will be 20 mA. If the level exceeds USL, the output will be 22 mA. When the process level drops to 8%, the probe is considered uncovered, and the output will switch to 4 mA. If the level drops below LSL, the fault signal will be 22 mA.

CE Certificate
WRITTEN DECLARATION OF CONFORMITY
We, Siemens Milltronics Process Instruments B.V. Nikkelstraat 10 - 4823 AB BREDA - The Netherlands Declare, solely under own responsibility, that the product
Requirements Remarks Certificate No Environment Commercial, light Industrial and industrial 2008949-KRQ/EMC 01-4231
EN 61326: 1998 Product group standard for “Electrical equipment for measurement, control and laboratory use”, from which:
EN 50011 : 1998 Emission – Class B EN 61000-4-2: 1995 Electrostatic Discharge (ESD) Immunity EN 61000-4-3: 1996 Radiated Electro-Magnetic Field Immunity EN 61000-4-4: 1995 Electrostatic Fast Transient (EFT) Immunity EN 61000-4-5: 1995 Surge Transient Immunity EN 61000-4-6: 1996 Conducted Radio-Frequency Disturbances Immunity
ATEX Directive 94/9/EC Audit Report No 2003068 KEMA 00ATEXQ3047
II 1 G EEx ia IIC T4…T6 0344 KEMA 02ATEX1019 X II 1/2 GD EExd [ia] IIC T6…T1 0344 KEMA 01ATEX2076 X II 3 GD EEx nA [ib] IIC T4…T6 0344 KEMA 02ATEX1033 X
EN 50014: 1992 General Requirements EN 50018: 1994 Flameproof Enclosures “d” EN 50020: 1994 Intrinsic Safety “i” EN 50284: 1999 Special Requirements for Category 1G Equipment EN 50281-1-1: 1998 Dust Ignition Proof
97/23/EC Pressure Equipment Directive Lloyd’s Register, DAD No.:
8033474, 8033475, 8033476, 8033477, 8033478, 8033479, 8033480, 8033481, 8033482, 8033483, 8033484, 8033485
Location, Breda Representative Name, C.S. van Gils Date, August 28th, 2002 Function, Managing Director Remark: For specific safety specifications, please consult the instrument label



















The Intrinsic Safety Specifications of the SITRANS LC 500 have been defined and approved as follows:
Application Specifications
current loop insulated from the measuring circuit 3.6-22 mA
internal capacitance can be ignored
internal inductance 10 µH
maximum supply voltage 30 Vdc
maximum current 200 mA
maximum power consumption 1.5 W
The SITRANS LC 500 can be directly connected to an intrinsically safe supply for intrinsically safe applications. For non-intrinsically safe operations, such as explosion proof, a safety barrier must be used.
The operation of the SITRANS LC 500 conforms to the following:
This recommendation describes rules by which analog transmitters transfer their information to DCS equipment. This information can be divided into two types:
The application will determine which of these two ranges is more desirable. The SITRANS LC 500 can be set for 3.6 mA, or 22 mA, as required2.

SITRANS LC 500
Size:
Rev.
must not exceed barriers' Isc or It Current sum of both
Current sum of both
Appr. RM
barriers' Isc or It
1:1
following:
following:
FM/CSA_APPROVAL
Tolerance Unless Otherwise Noted:
Revision / ECN Description
2 Place Decimal ± 0.01
No Decimal ± 0.5
1 Place Decimal ± 0.1
DRAWING No:
Voc or Vt Voc or Vt SS relay barrier:
30 Vdc 30 Vdc
24 Vdc 30 Vdc
26 Vdc 24 Vdc
SS relay barrier:
The installation must meet all applicable sections of the Canadian Electrical Code (C.E.C.) 4) For Canada: Installation must be in accordance with the Canadian Electrical Code, Section 18.
Plot at:
Entity parameters specified in the barrier manufactures' control drawings are not used.
Supply voltage fused with 3 A fuse (power limited)
Instead, the instrument's cable length is limited to the lengths shown in the tables.
Nikkelstraat 10, 4823 AB Breda, The Netherlands
PROCESS INSTRUMENTS b.v. SIEMENS MILLTRONICS
Hazardous (Classified) Location Non - hazardous Location
For groups A, B, C or D
Current loop barriers:
For groups C or D only:
Current loop barriers:
A10324R0.rev A
Rev.
For FM Flame proof applications only:
RM
USE DIMENSIONS ONLY - DO NOT SCALE
Drawn:
Checked:
Approved:
Location:
File No.
Date:
OF THIS DRAWING DOES NOT IMPLY ANY LICENSE UNDER ANY SUCH R OTHERS, AND THE ISSUE THE SUBJECT OF PATENTS, INDUSTRIAL DESIGN REGISTRATIONS OR MILLTRONICS OR OTHERS. THE ITEM DEPICTED MAY THEMSELVES BE PROPRIETARY INFORMATION AND TRADE SECRETS OF SIEMENS IS TO BE MAINTAINED CONFIDENTIAL, SINCE IT MAY CONTAIN SPECIFICALLY HAVE BEEN AUTHORIZED BY SIEMENS MILLTRONICS. IT AND CAN BE UTILIZED ONLY FOR SUCH LIMITED PURPOSES AS MAY AND IS SUBJECT TO RECALL. IT MAY NOT BE COPIED, AND IS ISSUED THIS DOCUMENT REMAINS THE PROPERTY OF SIEMENS MILLTRONICS
COPYRIGHT SIEMENS MILLTRONICS PROCESS INSTRUMENTS b.v.
Associated Apparatus with entity parameters: Class I, Div. 1, Groups A, B, C and D
Associated Apparatus with entity parameters:
ALL RIGHTS RESERVED
Class I, Div. 1, Groups C and D
10 µH + Lcable
10 µH + Lcable
Siemens Milltronics PI b.v.
+31 (0) 76 542 7 542
+31 (0) 76 542 8 542
4823 AB Breda The Netherlands
Class I, Div. 2, Groups A, B, C and D: Vmax = 33 V, Imax = 24 mA, installation without associated apparatus.
Class I, Div. 1, Groups A, B, C, and D: Vmax = 30 V, Imax = 110 mA, Ci = 0, Li = 10µH
Class I, Div. 1, Groups C and D: Vmax = 30 V, Imax = 200 mA, Ci = 0, Li = 10 µH
CPU
Installation must be in accordance with the National Electrical Code (R)
Temperature class T4 for class I, Div. 1 applications
(NFPA 70, Article 504) and ANSI/ISA-RP12.6
-40°C < ambient temperature +85°C
MERCAP/N MERCAP/FTF
MERCAP/2
MERCAP/F

electricity when potential differences exist between the conductors. Its value is expressed as the ratio of a quantity of electricity to a potential difference, and the unit is a Farad.
capacitor: a device in a circuit that has the potential to store an electric charge. Typically a
capacitor has 2 conductors or electrodes separated by a layer of a nonconducting material called a dielectric. With the conductors on opposite sides of the dielectric layer oppositely charged by a source of voltage, the electrical energy of the charged system is stored in the polarized dielectric.
for different conditions.
influence of an electric field. This is measured by the ratio of the capacitance of a condenser with the material as dielectric to its capacitance with vacuum as dielectric. The value is usually given relative to a vacuum /dry air: the dielectric constant of air is 11.
immiscible: incapable of mixing or attaining homogeneity.
implicit: for example in “the units are implicit in pF”, the units are implied, or assumed to be pF,
because there is no other option.
miscible: capable of being mixed.
variable under the same conditions.
saturation: a condition in which any further change of input no longer results in a change of
output. For example, “the loop-current will saturate to 3.8 or 20.5 if the level exceeds the Range settings”.
otherwise completely static components such as resistors and capacitors.
stilling-well: a grounded metal tube with openings.



Quick Start
We strongly recommend you read the full manual to use your device to its fullest
potential. However, if it is possible to adjust the level of the tank to the 0% and 100% levels, you can use the quick start sequence below to calibrate the instrument and get started.
1 Calibrate the 0% setting (LRV - lower range value): menu 0E
For instruments without a stilling well, the 0% setting needs to be calibrated after the device is installed, and with the tank/vessel empty. Calibration is also sometimes neces- sary after installing a SITRANS LC 500 fitted with a stilling well, although in most cases the 0% setting is calibrated at the factory.
Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).
a Bring the product level to the height that corresponds to 0%.
b Turn the rotary switch to E (Empty).
c Press both buttons and hold for about 1 second: the 0% point is now set. 2 Calibrate the 100% setting (URV - upper range value): menu 0F
Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0).
a Raise the product level to the height that corresponds to 100%.
b Turn the rotary switch to F (Full).
c Press both buttons and hold for about 1 second: the 100% point is now set. 3 View primary variable (PV): menu 00
Turn the rotary switch to 0. The LCD displays the actual pF reading. 4 SITRANS LC 500 is now ready to operate.

cal PV Units PV Units PV Units PV Units PV Units
Default * TVO * 00 00 75% 25% Analog Disabled 1.0 1 1.666 pF 3300 pF 3300 pF 0 pF 3300 pF Menu LEVEL 1 (10 to 1F)
Settings Seconds Seconds % % O/ C O/C nor / inv Resp. Units Keylock
URV
Value (PV) URV =
0 1 2 3 4 5 6 7 8 9 A B C D E F
PV
PV
Default * * * 00 00 75% 25% Disabled Disabled nor * 0
= Min. LRV = Actual
PV
LRV
PV
LRV
for 4 c.q.
PV
PV
PV
PV
PV
Set to 1 Set to 1 Preset
PV
Rotary Switch Positions – Quick Reference
Selection PV Units Seconds Seconds % % mA mA Numeri-
to 0.01
MODE
MODE
Menu LEVEL 0 (00 to OF)
22 or 3.6 mA
Set FAULT:
Set FAULT:
for Solid-state Disable Fault
3.6 mA
Set Covered:
Set Covered:
4 to 20 mA (Anl)
00 < – > 100
00 < - > 100
00 < – > 100
do it Toggle Delay
00 < - > 100
% Mode Reset Hi/Lo
Units PV Units Numerical Factory
FAC
FAC
FAC
Units PV Units Num.
RED (+)
BLUE (–)
NO KEYS
RED (+)
BLUE (–)



Siemens Milltronics Process Instruments Inc. 1954Technology Drive, P.O. Box 4225 Peterborough, ON, Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 Email: techpubs@siemens-milltronics.com
Siemens Milltronics Process Instruments Inc. 2003 Subject to change without prior notice
Printed in Canada
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.