Page 1 of the Siemens SIMATIC IPC427D user manual — Design
Page 1 · click to enlarge
Page 1

SIMATIC IPC427D

  • High investment security in order to reduce engineering costs
  • Long-term availability: Service and support period of 8 to 10 years after market launch
  • Installation and interface compatibility with predecessor versions as of 2004
Siemens SIMATIC IPC427D — SIMATIC IPC427D diagram (page 1)
Fig. 1

Design

  • Basic design
  • All-metal enclosure, resistant to vibrations and shocks, also with high electromagnetic compatibility
  • Graphics onboard, on AGP bus: DVI-I: VGA (analog) and DVI (digital); display port - CRT resolution: Up to 1920 x 1200 pixels / true color /
  • 60 to 120 Hz - DVI-D resolution: Up to 1920 x 1200 pixels / true color
  • Optical drives can be connected externally via USB interface, not included in scope of supply
  • Interfaces (accessible from one side) - 2 x LAN 10/100/1000 Mbit/s Ethernet interface (RJ45) - 4 x High-Speed USB V3.0 - 1 x COM1 (RS232)
  • Vacant slots (when using the versions with one or two expansion slots): - Up to 2 x PCIe cards (1 x PCIe x4 and 1 x PCIe x1)
  • Isolated power supply: 24 V DC (19.2 to 28.8 V)
  • SIMATIC IPC427D (Microbox PC): The powerful embedded IPC - maintenance-free with versatile configuration
  • Ultra-compact and maintenance-free
  • Third generation Intel Core i technology
  • High data processing speed for high productivity
  • Up to Core I 7, fan-free
  • DDR3 memory technology up to 8 GB
  • Maximum compactness and ruggedness for use directly on the machine
  • Low mounting depth, ambient temperature up to 55 °C
  • Upright mounting as second standard mounting position (ambient temperature 50 °C)
  • Solid State Drive (SSD) (50 GB high endurance or 80 GB standard, optional), SATA hard disk, or up to 2 CFast cards with 16 GB

Design versions • Processor: - Celeron 827E; 1.4 GHz, 1.5 MB Cache - Core i3-3217UE; 2 x 1.6 GHz, 3 MB Cache - Core i7-3517UE; 2 x 1.7 GHz (Turboboost to 2.8 GHz),

  • 3 MB Cache
  • Main memory capacity 1 GB (2/4/8 GB optional), DDR3 SDRAM
  • Fieldbus - PROFINET onboard, 3 x RJ45, CP 1616-compatible - PROFIBUS DP/MPI onboard, CP 5622-compatible
  • Hardware expansion - Second RS232 interface (COM2) onboard
  • Drives: - Solid State Drive 50 GB high endurance or 80 GB standard,
  • High degree of industrial functionality and flexibility for implementing embedded solutions
  • Flexible memory concepts (e.g. 2 mass storage units possible)
  • 2 x LAN 10/100/1000 Mbit/s connections; teaming-capable
  • Onboard PROFIBUS or PROFINET interface (optional)
  • 4 x high-speed USB 3.0 ports; 2 serial interfaces (2nd interface is optional)
  • Flexible installation with mounting options (rail, wall, front upright mounting)
  • Simple expansion capability (up to 2 PCIe slots)
  • On/off switch

rugged alternative to hard disk - FlashDrive (replaceable, accessible): 2 GB, 4 GB,

8 GB or 16 GB - FlashDrive (internal, not accessible): 2 GB, 4 GB, 8 GB,

  • High system availability in order to reduce the risk of potential failures and maintenance costs
  • Maintenance-free since no rotating parts (fans, hard disks) and operation without battery possible
  • 512 KB NVRAM, of which 256 KB can be written by the WinAC RTX within the buffer time
  • Front LED for efficient self-diagnostics; optimized for headless operation through special BIOS properties
  • SIMATIC software system-tested

16 GB - Hard disk serial ATA, 2.5" • Preinstalled operating systems: - Windows 7 Ultimate MUI - Windows Embedded Standard 7

All rights reserved SIMATIC IPC427D © Copyright Siemens AG 2013

Product Data Sheet · 1/4

Page 2 of the Siemens SIMATIC IPC427D user manual — Technical specifications SIMATIC IPC427D
Page 2 · click to enlarge
Page 2

Technical specifications SIMATIC IPC427D

General features Design• DIN rail mounting • Wall mounting • Portrait mounting Processor• Intel Celeron 827E 1.4 GHz, 1,5 MB SLC • Intel Core i3-3217UE 1.6 GHz, 3 MB SLC • Intel Core i7-3517UE 1.7 GHz, 4 MB SLC Main memoryMemory modules without ECC: • 1 GB DDR3-SDRAM SODIMM • 2 GB DDR3-SDRAM SODIMM • 4 GB DDR3-SDRAM SODIMM • 8 GB DDR3-SDRAM SODIMM Memory modules with ECC: • 4 GByte DDR3-ECC SODIMM • 8 GByte DDR3-ECC SODIMM Free slots for expansionsUp to 2 x PCIe cards, depending on enclosure design (1 x PCIe x4 and 1 x PCIe x1) Graphics• Integrated Intel HD2000 or HD4000 • DVI resolution of 640 x 480 pixels up to 1920 x 1200 pixels • Maximum display port resolution 1920 x 1200 pixels • Graphics memory is occupied in the main memory (UMA dynamic) Power supply24 V DC (-20% / +20%) max. 4 A Rated conditionsFan-free operation Operating systems Available• Without • Windows Embedded Standard 7 • Windows 7 Ultimate MUI Project-specific• Linux • QNX • VxWorks Drives and storage media CFast card• 2 GB optional or • 4 GB optional or • 8 GB optional or • 16 GB optional Hard disk2.5", ≥ 250 GB, SATA Solid-State Drive (SSD)2.5"; ≥ 80 GB Standard, ≥ 50 GB High-Endurance
USB stickExternal, can be connected via USB port Interfaces Serial• COM1 (RS 232) • COM2 (RS 232); optional Graphics• DVI-I: Can be used as DVI or VGA • DPP++: Display port, DVI via DPP-to-DVI adapter USB4 x USB 3.0, max. 2 high-current at the same time, downwardcompatible with USB 2.0/1.1 Ethernet• 2 x RJ45 (10/100/1000 MBit/s) teaming-capable or • 1 x RJ45 (10/100/1000 MBit/s) with PROFINET versions PROFIBUS DP12 Mbit/s (isolated, compatible with CP 5622), optional PROFINET3 x RJ45 (10/100 Mbit/s), CP 1616 onboard, optional CAN interfaceOptional Keyboard, mouseConnection via USB port Advanced device functions Temperature• When permitted operating temperature range is exceeded • Warnings can be analyzed by application program (local, via LAN) Watchdog• Monitoring function for program execution • Restart can be parameterized in the event of a fault • Warnings can be analyzed by application program (local, via LAN) LED display4 LEDs for displaying system status, 3 of these can be programmed by the user Short-term voltage dipsUp to 15 ms buffer time at full load Buffer memory512 KB MRAM 1 optional

All rights reserved SIMATIC IPC427D © Copyright Siemens AG 2013

2/4

Page 3 of the Siemens SIMATIC IPC427D user manual — Dimension drawings SIMATIC IPC427D
Page 3 · click to enlarge
Page 3

Dimension drawings SIMATIC IPC427D

All dimensions in mm.

Siemens SIMATIC IPC427D — Dimension drawings SIMATIC IPC427D diagram (page 3)
Fig. 2 · Dimension drawings SIMATIC IPC427D
Siemens SIMATIC IPC427D — Dimension drawings SIMATIC IPC427D diagram (page 3)
Fig. 3 · Dimension drawings SIMATIC IPC427D

SIMATIC IPC427D, for DIN rail mounting

Siemens SIMATIC IPC427D — Dimension drawings SIMATIC IPC427D diagram (page 3)
Fig. 4 · Dimension drawings SIMATIC IPC427D

SIMATIC IPC427D, for portrait mounting

Siemens SIMATIC IPC427D — Dimension drawings SIMATIC IPC427D diagram (page 3)
Fig. 5 · Dimension drawings SIMATIC IPC427D

SIMATIC IPC427D, for wall mounting

SIMATIC IPC427D, with expansion cards

SIMATIC IPC427D All rights reserved © Copyright Siemens AG 2013 3/4

Page 4 of the Siemens SIMATIC IPC427D user manual — Dimension drawings SIMATIC IPC427D
Page 4 · click to enlarge
Page 4
SIMATIC IPC – the more Industrial PC More information on SIMATIC IPC is available at:www.siemens.com/simatic-ipc A current overview of the configurations is provided by the SIMATIC IPC Online-Konfigurator:www.siemens.com/ipc-configurator In-depth information is available in the SIMATIC manuals:www.siemens.com/simatic-doku Information material for download:www.siemens.com/simatic/printmaterial Technical documentation is available in our Service& Support portal:www.siemens.com/automation/support Your personal contact partner is listed at:www.siemens.com/automation/partner Electronic ordering via the Internet with the Mall:www.siemens.com/industrymall Additional information on PC-based Automation with SIMATIC is available under:www.siemens.com/pc-based-automation Additional information on the TIA Portal:www.siemens.com/tia-portal Additional information on SIMATIC Safety Integrated:www.siemens.com/f-cpu Online Service Tool PED – for fast information on the equipment of your SIMATIC PC and the management of your field inventory:www.siemens.com/ped

All rights reserved SIMATIC IPC427D © Copyright Siemens AG 2013

4/4

Ask about the Siemens SIMATIC IPC427D

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.