Page 2
Technical specifications SIMATIC IPC427D
General features
Design• DIN rail mounting • Wall mounting • Portrait mounting
Processor• Intel Celeron 827E 1.4 GHz, 1,5 MB SLC • Intel Core i3-3217UE 1.6 GHz, 3 MB SLC • Intel Core i7-3517UE 1.7 GHz, 4 MB SLC
Main memoryMemory modules without ECC: • 1 GB DDR3-SDRAM SODIMM • 2 GB DDR3-SDRAM SODIMM • 4 GB DDR3-SDRAM SODIMM • 8 GB DDR3-SDRAM SODIMM Memory modules with ECC: • 4 GByte DDR3-ECC SODIMM • 8 GByte DDR3-ECC SODIMM
Free slots for expansionsUp to 2 x PCIe cards, depending on enclosure design (1 x PCIe x4 and 1 x PCIe x1)
Graphics• Integrated Intel HD2000 or HD4000 • DVI resolution of 640 x 480 pixels up to 1920 x 1200 pixels • Maximum display port resolution 1920 x 1200 pixels • Graphics memory is occupied in the main memory (UMA dynamic)
Power supply24 V DC (-20% / +20%) max. 4 A
Rated conditionsFan-free operation
Operating systems
Available• Without • Windows Embedded Standard 7 • Windows 7 Ultimate MUI
Project-specific• Linux • QNX • VxWorks
Drives and storage media
CFast card• 2 GB optional or • 4 GB optional or • 8 GB optional or • 16 GB optional
Hard disk2.5", ≥ 250 GB, SATA
Solid-State Drive (SSD)2.5"; ≥ 80 GB Standard, ≥ 50 GB High-Endurance
USB stickExternal, can be connected via USB port
Interfaces
Serial• COM1 (RS 232) • COM2 (RS 232); optional
Graphics• DVI-I: Can be used as DVI or VGA • DPP++: Display port, DVI via DPP-to-DVI adapter
USB4 x USB 3.0, max. 2 high-current at the same time, downwardcompatible with USB 2.0/1.1
Ethernet• 2 x RJ45 (10/100/1000 MBit/s) teaming-capable or • 1 x RJ45 (10/100/1000 MBit/s) with PROFINET versions
PROFIBUS DP12 Mbit/s (isolated, compatible with CP 5622), optional
PROFINET3 x RJ45 (10/100 Mbit/s), CP 1616 onboard, optional
CAN interfaceOptional
Keyboard, mouseConnection via USB port
Advanced device functions
Temperature• When permitted operating temperature range is exceeded • Warnings can be analyzed by application program (local, via LAN)
Watchdog• Monitoring function for program execution • Restart can be parameterized in the event of a fault • Warnings can be analyzed by application program (local, via LAN)
LED display4 LEDs for displaying system status, 3 of these can be programmed by the user
Short-term voltage dipsUp to 15 ms buffer time at full load
Buffer memory512 KB MRAM 1 optional
All rights reserved SIMATIC IPC427D © Copyright Siemens AG 2013
2/4