SIMATIC IPC227D

  • Design versions
  • Processor / main memory configuration: - Intel Atom E660 1.3 GHz, 2 GB RAM - Intel Atom E640 1.0 GHz, 1 GB RAM - Intel Atom E620 600 MHz, 512 MB RAM
  • Retentive memory - 512 KB retentive memory (MRAM), 128 KB of which can be
Siemens IPC227D — SIMATIC IPC227D diagram (page 1)
Fig. 1
  • written to within the buffer time (optional)
  • Hardware expansion as device versions: - COM2-4 - 4 dig. inputs/outputs each, 24 V - 1 PCIe slot (x1)
  • Drives: - CompactFlash drive (replaceable, accessible): 2 GB, 4 GB,

8 GB or 16 GB - Solid-State Drive 50 GB (High Endurance), 2.5" - Solid-State Drive 80 GB (Standard), 2.5" - Hard disk 250 MB Serial ATA, 2.5" • Preinstalled operating systems: - Windows XP Embedded Standard 2009 - Windows XP Professional Multi-Language - Windows Embedded Standard 7 - Windows 7 Multi-Language, 32-bit

  • SIMATIC IPC227D available for implementing simple control, data collector or communication tasks:
  • Maximum compactness with approx. 1 liter enclosure volume or more with integrated industrial power supply for minimum space requirements in the control cabinet
  • Maximum flexibility thanks four mounting options and interfaces on one side suitable for every installation situation
  • Optimum variety of interfaces due to a large number of integrated interfaces such as a selectable serial port (RS232/RS485/CAN) and 2 x teaming-capable Gigabit LAN
  • Maximum industrial functionality due to closed enclosure for optimum dust protection and non-volatile retentive memory
  • Further device options for optimum adaptation to the application with additional PCIe slot or RS232 interfaces or digital I/O

SIMATIC IPC227D (bottom side), basic version:

Siemens IPC227D — SIMATIC IPC227D (bottom side), basic version: diagram (page 1)
Fig. 2 · SIMATIC IPC227D (bottom side), basic version:

Design

  • Basic design
  • All-metal enclosure, resistant to vibrations and shocks, also with high electromagnetic compatibility
  • Onboard graphics, DVI (digital) - DVI-D resolution: Up to 1920 x 1200 pixels
  • Optical drives can be connected externally via USB interface, not included in scope of supply
  • Interfaces (accessible from one side): - 2 x LAN 10/100/1000 Mbit/s Ethernet interface (RJ45) - 4 x high-speed USB V2.0 - 1 x COM1 (RS232)
  • Fieldbus - PROFINET Realtime via Standard Ethernet interface - Isolated power supply: 24 V DC (20.4 to 28.8 V)

SIMATIC IPC227D (bottom side), COM version:

Siemens IPC227D — SIMATIC IPC227D (bottom side), COM version: diagram (page 1)
Fig. 3 · SIMATIC IPC227D (bottom side), COM version:

Product Data Sheet · 1/7

Page 2 of the Siemens IPC227D user manual — SIMATIC IPC227D bundles: HMI, RTX, RTX F and HMI/RTX
Page 2 · click to enlarge
Page 2

SIMATIC IPC227D (bottom side), IO version:

Expansion components

Siemens IPC227D — SIMATIC IPC227D (bottom side), IO version: diagram (page 2)
Fig. 4 · SIMATIC IPC227D (bottom side), IO version:
  • SIMATIC IPC DiagMonitor
  • PC diagnostics/alarm software for early detection and diagnostics of PC problems
  • Comprehensive monitoring of temperature, watchdog
  • Operating hours counter for preventive maintenance
  • Integrated log functions, comprehensive text messages, online help (English/German)
  • Network-wide monitoring via SNMP and OPC interface possible
  • SIMATIC IPC Image & Partition Creator
  • Software tool for preventive data back-up of the contents of bulk storage (CF cards, hard disks, SSD)
  • High-speed restoring of system and data partitions with bit accuracy; user software and special installations are also backed up
  • Software tool for adaptation of mass storage partitioning

SIMATIC IPC227D (bottom side), PCIe version:

Siemens IPC227D — SIMATIC IPC227D (bottom side), PCIe version: diagram (page 2)
Fig. 5 · SIMATIC IPC227D (bottom side), PCIe version:
  • SIMATIC IPC Service USB FlashDrive
  • Mobile memory medium for backing up/restoring mass memories
  • Pre-installed Image & Partition Creator V3.1
  • Ultra-compact and rugged

SIMATIC IPC227D bundles: HMI, RTX, RTX F and HMI/RTX

  • HMI, RTX, RTX F and HMI/RTX complete turnkey solutions (the software is already preinstalled and configured) for visualization and automation in combination with WinCC RT Advanced and WinAC RTX 2010 /F
  • Quick start in automation solutions with Embedded Automation
  • HMI: SIMATIC WinCC RT Advanced preinstalled and ready to run
  • RTX: SIMATIC WinAC RTX 2010 preinstalled and ready to run
  • RTX F: SIMATIC WinAC RTX 2010 F preinstalled and ready to run
  • HMI/RTX (F): SIMATIC WinCC RT Advanced and SIMATIC WinAC RTX 2010(F) preinstalled and ready to run
  • PROFINET (RT) pre-configured for use in a SIMATIC environment
  • Configuration and programming with SIMATIC WinCC Engineering System and SIMATIC STEP 7 via Industrial Ethernet
  • Flexibility of a PC-based automation environment
  • Open for additional PC applications
  • Connection option for USB devices
  • Use of WinAC ODK with SIMATIC WinAC RTX
  • Data retentivity for WinAC RTX without uninterruptible power supply (UPS)

2/7

Page 3 of the Siemens IPC227D user manual — Technical specifications SIMATIC IPC227D
Page 3 · click to enlarge
Page 3

Technical specifications SIMATIC IPC227D

SIMATIC Box PCSIMATIC IPC227D DesignRail, wall, portrait or side mounting Processor• Intel Atom E620 600 MHz, 512 MB RAM • Intel Atom E640 1.0 GHz, 1 GB RAM • Intel Atom E660 1.3 GHz, 2 GB RAM ChipsetIntel Controller Hub EG20T Buffered MRAM512 KB, of which 128 KB can be written within the buffer time Free slots for expansionsOptional PCIe expansion slot Graphics• Integrated into Intel Atom CPU E6xx • 8 to 256 MB (shared memory), 1920 x 1200, 60 Hz, 32-bit colors Operating system• without • Windows Embedded Standard 2009 preinstalled, in combination with CF card or solid-state drive or hard drive (optional) • Windows XP Professional MUI preinstalled (in combination with solid-state drive or hard drive; MUI: Multi Language User Interface) (optional) • Windows Embedded Standard 7, 32-bit, preinstalled, in combination with CF card or solidstate drive or hard drive (optional) • Windows 7 Ultimate MUI 32 bit preinstalled (in combination with solid-state drive or hard drive; MUI: Multi Language User Interface) (optional) • Linux 1) (project-specific, on request) • RMOS (project-specific on request) • Others on request project-specifically Power supply• 24 V DC (20.4 V ... 28.8 V) • Isolated • With buffering of temporary power failures: max. 10 ms • Line side switch • With power failure indication by means of Power Fail signal
SIMATIC Box PCSIMATIC IPC227D Drives Flash driveOptional; replaceable, accessible, diagnosable • 2 GB • 4 GB • 8 GB • 16 GB Solid State Drive (SSD)Optional: • 50 GB SATA, High Endurance, 2.5" • 80 GB SATA, Standard, 2.5" Hard diskOptional 250 GB SATA CD-ROMVia USB (not included in scope of delivery) DVD-RWVia USB (not included in scope of delivery) Floppy diskVia USB (not included in scope of delivery) Interfaces PROFINETPROFINET RT via Standard Ethernet controller PROFIBUS/MPI- Ethernet• 2 x 10/100/1000 Mbit/s (RJ 45) • Two independent Intel Controllers: Intel 82574L / Intel Controller Hub EG20T • With teaming function USBV2.0/High Speed: 4 x SerialCOM1 (V.24), optional COM2-4 DVI-I1 x DVI-D KeyboardVia USB (not included in scope of delivery) MouseVia USB (not included in scope of delivery) Monitoring functions Temperature• Processor temperature • Motherboard Messages can be evaluated by the application program

SIMATIC IPC227D All rights reserved © Copyright Siemens AG 2012 3/7

Page 4 of the Siemens IPC227D user manual — Technical specifications SIMATIC IPC227D
Page 4 · click to enlarge
Page 4
SIMATIC Box PCSIMATIC IPC227D Watchdog• Monitoring of program execution • Monitoring time can be parameterized in software • Can be parameterized for a fault or restart Messages can be evaluated by the application program. Monitoring functions via the network• DiagBase • SIMATIC IPC DiagMonitor Remote monitoring capability for: • Watchdog • Temperature • Mass memory monitoring (SMART) • System/Ethernet monitoring (Heart Beat) • Runtime meter Communication: • Ethernet interface (SNMP protocol) • OPC for integration in SIMATIC software • Configuration of client/server architectures • Structure of log files Ambient conditions Degree of protection to EN 60529 (front/rear)IP20 Vibration load during operationDevices without hard disk: • Requirements according to: IEC 61131-2 • Tested according to: IEC 60068-2-6, Test Fc • 10-58 Hz: 0.0375 mm • 58-200 Hz: 9.8 m/s2 • 10 x /axis Devices with hard disk: • Requirements according to: IEC 61131-2 • Tested according to: IEC 60068-2-6, Test Fc • 10-58 Hz: 0.0375 mm • 58-200 Hz: 4.9 m/s2 • 10 x /axis Shock loading during operationDevices without hard disk: • Requirements according to: IEC 61131-2 • Tested according to: IEC 60068-2-27, Test Ea • 150 m/s2, 30 ms shock duration Devices with hard disk: • Requirements according to: IEC 61131-2 • Tested according to: IEC 60068-2-27, Test Ea 50 m/s2, 30 ms shock duration
SIMATIC Box PCSIMATIC IPC227D Moist heatWith CompactFlash card/SSD: 95 % With hard disk: 80 % Ambient temperature during operation0 °C up to 50 °C Electromagnetic compatibility (EMC) Emitted interferenceEN 55022 Class B Interference immunity, burstEN 61000-6-2 or IEC 61131-2: • 2 kV - tested acc. to IEC 61000-4-4 • 1 kV symmetrical / 2 kV asymmetrical - tested acc. to IEC 61000-4-5 Interference immunity, surge• 1 kV to IEC 61000-4-5; symmetrical • 2 kV to IEC 61000-4-5; asymmetrical ESD interference immunityAccording to NAMUR Recommendation NE 21 and EN 61000-6-2: • 6 kV contact discharge - tested acc. to IEC 61000-4-2 • 8 kV air discharge - tested acc. to IEC 61000-4-2 Immunity to high radio frequency interferenceAccording to EN 61000-6-2 or IEC 61131-2: • Interference immunity 80 ... 1000 MHz: 10 V/m with 80% AM (1 kHz); tested acc. to IEC 61000-4-3; • 1.4 GHz ... 2 Hz: 10 V/m with 50% pulse modulation; tested according to IEC 61000-4-3 Immunity to high-frequency current feedAcc. to NAMUR Recommendation NE 21 and EN 61000-6-2 or IEC 61131-2: • 10 kHz ... 80 MHz: 10 V with 80% AM (1 kHz) tested acc. to IEC 61000-4-6 Immunity to magnetic fieldsAcc. to NAMUR Recommendation NE 21 and EN 61000-6-2 or IEC 61131-2: • 50/60 Hz; 100 A/m rms value - tested acc. to IEC 61000-4-8 Approvals Marine approval Only for configurations with CompactFlash or SSD memory• GL – Germanische Lloyd • BV – Bureau Veritas • LR – Lloyds Register of Shipping • ABS – American Bureau of Shipping • DNV – Det Norske Veritas • NKK – Nippon Kaiji Kyokai

4/7

Page 5 of the Siemens IPC227D user manual — Dimensional drawings
Page 5 · click to enlarge
Page 5
SIMATIC Box PCSIMATIC IPC227D Device versions Basic versionWidth x Height x Depth: approx. 191 x 100 x 60 mm COM• 3 additional, integrated serial interfaces (COM2-4); only sending/receiving of data • Width x Height x Depth: approx. 191 x 100 x 89 mm IO• 4 digital inputs/outputs each, 24 V, integrated • Width x Height x Depth: approx. 191 x 100 x 89 mm PCIe• 1 PCIe (x1) slot, integrated • Width x Height x Depth: approx. 191 x 187 x 89 mm
Siemens IPC227D — Dimensional drawings diagram (page 5)
Fig. 6 · Dimensional drawings
Siemens IPC227D — Dimensional drawings diagram (page 5)
Fig. 7 · Dimensional drawings
1. Suitable for specific LINUX versions in accordance with the specifica-

tions of the Siemens manufacturer's declaration "Suitable for LINUX",

see http://www.siemens.de/simatic-pc/geeignet-fuer-linux (LINUX is a

SIMATIC IPC227D basic unit, standard rail mounting

trademark of Linus Torvald).

Siemens IPC227D — Dimensional drawings diagram (page 5)
Fig. 8 · Dimensional drawings

Dimensional drawings

All dimensions in mm.

Siemens IPC227D — Dimensional drawings diagram (page 5)
Fig. 9 · Dimensional drawings

SIMATIC IPC227D COM version, portrait mounting

SIMATIC IPC227D basic unit, portrait mounting

SIMATIC IPC227D All rights reserved © Copyright Siemens AG 2012 5/7

Page 6 of the Siemens IPC227D user manual — Dimensional drawings
Page 6 · click to enlarge
Page 6
Siemens IPC227D — Dimensional drawings diagram (page 6)
Fig. 10 · Dimensional drawings
Siemens IPC227D — Dimensional drawings diagram (page 6)
Fig. 11 · Dimensional drawings

SIMATIC IPC227D COM version, standard rail mounting

SIMATIC IPC227D PCIe version, standard rail mounting

Siemens IPC227D — Dimensional drawings diagram (page 6)
Fig. 12 · Dimensional drawings

SIMATIC IPC227D PCIe version, portrait mounting

6/7

Page 7 of the Siemens IPC227D user manual — Dimensional drawings
Page 7 · click to enlarge
Page 7
SIMATIC IPC – the more Industrial PC More information on SIMATIC IPC is available at:www.siemens.com/simatic-ipc A current overview of the configurations is provided by the SIMATIC IPC Online-Konfigurator:www.siemens.com/ipc-configurator In-depth information is available in the SIMATIC manuals:www.siemens.com/simatic-doku Information material for download:www.siemens.com/simatic/printmaterial Technical documentation is available in our Service& Support portal:www.siemens.com/automation/support Your personal contact partner is listed at:www.siemens.com/automation/partner Electronic ordering via the Internet with the Mall:www.siemens.com/industrymall Additional information on PC-based Automation with SIMATIC is available under:www.siemens.com/pc-based-automation Additional information on the TIA Portal:www.siemens.com/tia-portal Additional information on SIMATIC Safety Integrated:www.siemens.com/f-cpu Online Service Tool PED – for fast information on the equipment of your SIMATIC PC and the management of your field inventory:www.siemens.com/ped

SIMATIC IPC227D All rights reserved © Copyright Siemens AG 2012 7/7

Ask about the Siemens IPC227D

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Siemens IPC227D

Be the first to ask — other owners or our team will answer.

Original document

Siemens IPC227D manual PDF

7 pages·635 KB·Welder·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…