Parameter List Issue 01/06


Getting Started Guide Is for quick commissioning with SDP and BOP.


Operating Instructions Gives information about features of the MICROMASTER 440, Installation, Commissioning, Control modes, System Parameter structure, Troubleshooting, Specifications and available options of the MICROMASTER 440.

Parameter List The Parameter List contains the description of all Parameters structured in functional order and a detailed description. The Parameter list also includes a series of function plans.
Catalogues In the catalogue you will find all needs to select a certain inverter, as well as filters chokes, operator panels or communications options.


Parameter List
MICROMASTER 440
Function Diagrams
Faults and Alarms
Abbreviations
Converter Type Software Version MICROMASTER 440 V2.1
Issue 01/06

Please get in touch with your contact for Technical Support in your Region for questions about services, prices and conditions of Technical Support.
The competent consulting service for technical issues with a broad range of requirements- based services around our products and systems.
The comprehensive, generally available information system over the Internet, from product support to service & support to the support tools in the shop. http://www.siemens.com/automation/service&support
Printed in the Federal Republic of Germany
Siemens-Aktiengesellschaft. Approved Siemens Quality for Software and Training is to DIN ISO 9001, Reg. No. 2160-01 The reproduction, transmission or use of this document, or its contents is not permitted unless authorized in writing. Offenders will be liable for damages. All rights including rights created by patent grant or registration of a utility model or design are reserved. © Siemens AG 2001 - 2006 All Rights Reserved. MICROMASTER® is a registered trademark of Siemens
Other functions not described in this document may be available. However, this fact shall not constitute an obligation to supply such functions with a new control, or when servicing.
We have checked that the contents of this document correspond to the hardware and software described. There may be discrepancies nevertheless, and no guarantee can be given that they are completely identical. The information contained in this document is reviewed regularly and any necessary changes will be included in the next edition. We welcome suggestions for improvement.
Siemens handbooks are printed on chlorine-free paper that has been produced from managed sustainable forests. No solvents have been used in the printing or binding process.
Document subject to change without prior notice.
Printed in the Federal Republic of Germany
Siemens-Aktiengesellschaft.


1 Block Diagram and Terminals
1.1 Block Diagram

1/3 AC 200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V SI
30 V DC / 5 A (resistive) 250 V AC / 2 A (inductive)

1.2 Power Terminals
You can gain access to the mains and motor terminals by removing the front covers.

Fig. 1-1 Frame Size A - F


Fig. 1-2 Frame Size FX


Fig. 1-3 Frame Size GX

1.3 Control Terminals


2 Parameters
2.1 Introduction to MICROMASTER System Parameters
The layout of the parameter description is as follows.
1 Par number 2 Parameter name 9 Min: [index] 3 CStat: 5 Datatype 7 Unit: 10 Def: 4 P-Group: 6 active: 8 Quick Comm: 11 Max:
13 Description:
1. Parameter number Indicates the relevant parameter number. The numbers used are 4-digit numbers in the range 0000 to 9999. Numbers prefixed with an “r” indicate that the parameter is a “read-only” parameter, which displays a particular value but cannot be changed directly by specifying a different value via this parameter number (in such cases, dashes “-“ are entered at the points “Unit”, “Min”, “Def” and “Max” in the header of the parameter description. All other parameters are prefixed with a “P”. The values of these parameters can be changed directly in the range indicated by the “Min” and “Max” settings in the header. [index] indicates that the parameter is an indexed parameter and specifies the number of indices available. 2. Parameter name Indicates the name of the relevant parameter. Certain parameter names include the following abbreviated prefixes: BI, BO, CI, and CO followed by a colon. These abbreviations have the following meanings:
BI =
BO =
Binector output, i.e. parameter connects as a binary signal
(999:9) r9999
CI =
Connector output, i.e. parameter connects as an analog signal
CO =
r9999 r9999 CO/BO =
Connector/Binector output, i.e. parameter connects as an analog signal and/or as a binary signal
To make use of BiCo you will need access to the full parameter list. At this level many new parameter settings are possible, including BiCo functionality. BiCo functionality is a different, more flexible way of setting and combining input and output functions. It can be used in most cases in conjunction with the simple, level 2 settings. The BiCo system allows complex functions to be programmed. Boolean and mathematical relationships can be set up between inputs (digital, analog, serial etc.) and outputs (inverter current, frequency, analog output, relays, etc.).
r9999 · r9999 [99]

♦ Confirm the “P” button on the operator panel (BOP or AOP) must be pressed before the changes take effect.
7. Unit Indicates the unit of measure applicable to the parameter values 8. QuickComm Indicates whether or not (Yes or No) a parameter can only be changed during quick commissioning, i.e. when P0010 (parameter groups for commissioning) is set to 1 (quick commissioning). 9. Min Indicates the minimum value to which the parameter can be set. 10. Def Indicates the default value, i.e. the value which applies if the user does not specify a particular value for the parameter. 11. Max Indicates the maximum value to which the parameter can be set. 12. Level Indicates the level of user access. There are four access levels: Standard, Extended, Expert and Service. The number of parameters that appear in each functional group depends on the access level set in P0003 (user access level).

Description: Brief explanation of the parameter function. Diagram: Where applicable, diagram to illustrate the effects of parameters on a characteristic curve, for example Settings: List of applicable settings. These include Possible settings, Most common settings, Index and Bitfields Example: Optional example of the effects of a particular parameter setting. Dependency: Any conditions that must be satisfied in connection with this parameter. Also any particular effects, which this parameter has on other parameter(s) or which other parameters have on this one. Warning / Caution / Notice / Note:
The following operators are used in the parameter list to represent mathematical interrelationships: Arithmetic operators + Addition - Subtraction * Multiplication / Division Comparison operators > Greater than >= Greater than / equal to < Less than

2.2 Quick commissioning (P0010 = 1)
The following parameters are necessary for quick commissioning (P0010 = 1).
P0100 Europe / North America 1 C P0205 Inverter application 3 C P0300 Select motor type 2 C P0304 Motor voltage rating 1 C P0305 Motor current rating 1 C P0307 Motor power rating 1 C P0308 Motor cosPhi rating 1 C P0309 Motor efficiency rating 1 C P0310 Motor frequency rating 1 C P0311 Motor speed rating 1 C P0320 Motor magnetizing current 3 CT P0335 Motor cooling 2 CT P0640 Motor overload factor [%] 2 CUT P0700 Selection of command source 1 CT P1000 Selection of frequency setpoint 1 CT P1080 Min. speed 1 CUT P1082 Max. speed 1 CT P1120 Ramp-up time 1 CUT P1121 Ramp-down time 1 CUT P1135 OFF3 ramp-down time 2 CUT P1300 Control mode 2 CT P1500 Selection of torque setpoint 2 CT P1910 Select motor data identification 2 CT P1960 Speed control optimisation 3 CT P3900 End of quick commissioning 1 C When P0010 = 1 is chosen, P0003 (user access level) can be used to select the parameters to be accessed. This parameter also allows selection of a user-defined parameter list for quick commissioning. At the end of the quick commissioning sequence, set P3900 = 1 to carry out the necessary motor calculations and clear all other parameters (not included in P0010 = 1) to their default settings.
To reset all parameters to the factory default settings; the following parameters should be set as follows: Set P0010 = 30 Set P0970 = 1

Seven-segment display
The seven-segment display is structured as follows:
9 8 11 10 13 12 15 14 Segment Bit
1 0 3 2 5 4 7 6
The significance of the relevant bits in the display is described in the status and control word parameters.
Segment Bit

2.3 Command and Drive Datasets - Overview
Command Datasets (CDS)


Drive Datasets (DDS)






2.4 Binector Input Parameters


2.5 Connector Input Parameters



2.7 Connector Output Parameters





Displays the user selected output as defined in P0005. Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output frequency, output voltage, output current, and chosen r0000 setting (defined in P0005). r0002 Drive state Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays actual drive state. Possible Settings:
0 Commissioning mode (P0010 != 0) 1 Drive ready 2 Drive fault active 3 Drive starting (DC-link precharging) 4 Drive running 5 Stopping (ramping down) Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted. P0003 User access level Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: ALWAYS Active: first confirm QuickComm.: No Max: 4
Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications. Possible Settings:
0 User defined parameter list - see P0013 for details on use 1 Standard: Allows access into most frequently used parameters. 2 Extended: Allows extended access e.g. to inverter I/O functions. 3 Expert: For expert use only. 4 Service: Only for use by authorized service personal - password protected. P0004 Parameter filter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: ALWAYS Active: first confirm QuickComm.: No Max: 22
Filters available parameters according to functionality to enable a more focussed approach to commissioning. Possible Settings:
0 All parameters 2 Inverter 3 Motor 4 Speed sensor 5 Technol. application / units 7 Commands, binary I/O 8 ADC and DAC 10 Setpoint channel / RFG 12 Drive features 13 Motor control 20 Communication 21 Alarms / warnings / monitoring 22 Technology controller (e.g. PID) Example:
P0004 = 22 specifies that only PID parameters will be visible.

Dependency:
The parameters are sub-divided into groups (P-Group) according to their functionality. This increases the transparency and allows a parameter to be quickly searched for. Furthermore, parameter P0004 can be used to control the ability to be visualized for the operator panel.
0 2 3 4 5 7 8 10 12 13 20 21 22
All parameters Drive inverter parameters Motor parameters Speed encoder Technical applications / units Control commands, digital I/O Analog inputs/outputs Setpoint channel and ramp-function gen. Drive inverter functions Motor open-loop/closed-loop control Communications Faults, warnings, monitoring functions
0200 0299
0300 ... 0399 + 0600 0699 0400 0499 0500 0599 0700 0749 + 0800 ... 0899 0750 0799 1000 1199 1200 1299 1300 1799 2000 2099 2100 2199 2200 2399
SETPOINT
FUNC CONTROL
COMM ALARMS
TECH Technological controller (PID controller)
Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010 = 1 (Quick Commissioning). P0005[3] Display selection Min: 2 CStat: CUT Datatype: U16 Unit: - Def: 21 P-Group: FUNC Active: first confirm QuickComm.: No Max: 4000
Selects display for parameter r0000 (drive display). Index:
P0005[0] : 1st. Drive data set (DDS) P0005[1] : 2nd. Drive data set (DDS) P0005[2] : 3rd. Drive data set (DDS) Common Settings:
21 Actual frequency 25 Output voltage 26 DC link voltage 27 Output current Notice:
These settings refer to read only parameter numbers ("rxxxx"). Details:
See relevant "rxxxx" parameter descriptions. P0006 Display mode Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 2 P-Group: FUNC Active: first confirm QuickComm.: No Max: 4
Defines mode of display for r0000 (drive display). Possible Settings:
0 In Ready state alternate between setpoint and output frequency. In run display output frequency 1 In Ready state display setpoint. In run display output frequency. 2 In Ready state alternate between P0005 value and r0020 value. In run display P0005 value 3 In Ready state alternate between r0002 value and r0020 value. In run display r0002 value 4 In all states just display P0005 Note:
- When inverter is not running, the display alternates between the values for "Not Running" and "Running". - Per default, the setpoint and actual frequency values are displayed alternately. P0007 Backlight delay time Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 2000
Defines time period after which the backlight display turns off if no operator keys have been pressed. Value:
P0007 = 0: Backlight always on (default state). P0007 = 1 - 2000: Number of seconds after which the backlight will turn off.

P0010 Commissioning parameter Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALWAYS Active: first confirm QuickComm.: No Max: 30
Filters parameters so that only those related to a particular functional group are selected. Possible Settings:
0 Ready 1 Quick commissioning 2 Inverter 29 Download 30 Factory setting Dependency:
- Reset to 0 for inverter to run. - P0003 (user access level) also determines access to parameters. Note:
P0010 = 1 The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after the other. The end of quick commissioning and the start of internal calculation will be done by setting P3900 = 1 - 3. Afterward parameter P0010 and P3900 will be reset to zero automatically. P0010 = 2 For service purposes only. P0010 = 29 To transfer a parameter file via PC tool (e.g.: DriveMonitor, STARTER) parameter P0010 will be set to 29 by the PC tool. When download has been finished PC tool resets parameter P0010 to zero. P0010 = 30 When resetting the parameters of inverter P0010 must be set to 30. Resetting of the parameters will be started by setting parameter P0970 = 1. The inverter will automatically reset all its parameters to their default settings. This can prove beneficial if you experience problems during parameter setup and wish to start again. Duration of factory setting will take about 60 s. P0011 Lock for user defined parameter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 65535
Details:
See parameter P0013 (user defined parameter) P0012 Key for user defined parameter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 65535
Details:
See parameter P0013 (user defined parameter). P0013[20] User defined parameter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 65535
Defines a limited set of parameters to which the end user will have access. Instructions for use: 1. Set P0003 = 3 (expert user) 2. Go to P0013 indices 0 to 16 (user list) 3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following values are fixed and cannot be changed: - P0013 index 19 = 12 (key for user defined parameter) - P0013 index 18 = 10 (commissioning parameter filter) - P0013 index 17 = 3 (user access level) 4. Set P0003 = 0 to activate the user defined parameter.

Index:
P0013[0] : 1st user parameter P0013[1] : 2nd user parameter P0013[2] : 3rd user parameter P0013[3] : 4th user parameter P0013[4] : 5th user parameter P0013[5] : 6th user parameter P0013[6] : 7th user parameter P0013[7] : 8th user parameter P0013[8] : 9th user parameter P0013[9] : 10th user parameter P0013[10] : 11th user parameter P0013[11] : 12th user parameter P0013[12] : 13th user parameter P0013[13] : 14th user parameter P0013[14] : 15th user parameter P0013[15] : 16th user parameter P0013[16] : 17th user parameter P0013[17] : 18th user parameter P0013[18] : 19th user parameter P0013[19] : 20th user parameter Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set P0003 to 0 to activate the user-defined list. When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock"). Note:
- Alternatively, set P0010 = 30 (commissioning parameter filter = factory setting) and P0970 = 1 (factory reset) to perform a complete factory reset. - The default values of P0011 ("lock") and P0012 ("key") are the same. P0014[3] Store mode Min: 0 CStat: UT Datatype: U16 Unit: - Def: 0 P-Group: - Active: first confirm QuickComm.: No Max: 1
Sets the store mode for parameters ("volatile" (RAM) or "nonvolatile" (EEPROM)). Possible Settings:
0 Volatile (RAM) 1 Nonvolatile (EEPROM) Index:
P0014[0] : Serial interface COM link P0014[1] : Serial interface BOP link P0014[2] : PROFIBUS / CB Note:
1. With the BOP the parameter will always be stored in the EEPROM. 2. P0014 itself will always be stored in the EEPROM. 3. P0014 will not be changed by performing a factory reset (P0010 = 30 and P0971 = 1). 4. P0014 can be transferred during a DOWNLOAD (P0010 = 29). 5. If "Store request via USS/CB = volatile (RAM)" and "P0014[x] = volatile (RAM)", you can make a transfer of all parameter values into the nonvolatile memory via P0971. 6. If "Store request via USS/CB" and P0014[x] are not consistent, the setting of P14[x] = "store nonvolatile (EEPROM)" has always higher priority.
Store request via USS/CB
Value of P0014[x] Result
RAM
EEPROM
EEPROM EEPROM
EEPROM
RAM
RAM RAM
RAM
EEPROM
EEPROM

Displays version number of installed firmware. r0019 CO/BO: BOP control word Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays status of operator panel commands. The settings below are used as the "source" codes for keypad control when connecting to BICO input parameters. Bitfields:
Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit08 JOG right 0 NO 1 YES Bit11 Reverse (setpoint inversion) 0 NO 1 YES Bit13 Motor potentiometer MOP up 0 NO 1 YES Bit14 Motor potentiometer MOP down 0 NO 1 YES Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual status of the relevant command. The following functions can be "connected" to individual buttons: - ON/OFF1, - OFF2, - JOG, - REVERSE, - INCREASE, - DECREASE r0020 CO: Freq. setpoint before RFG Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual frequency setpoint (input from ramp function generator).

r1119 r0021 CO: Act. filtered frequency 1 Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual inverter output frequency (r0021) excluding slip compensation, resonance damping and frequency limitation. r0022 Act. filtered rotor speed Min: - Datatype: Float Unit: 1/min Def: - P-Group: CONTROL Max: -
Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of poles.
60 [Hz] r0021 [1/min] r0022 ⋅ =
This calculation makes no allowance for load-dependent slip.
r0313
![Page 30 of the Siemens 440 user manual — P0210 2 100 [%] P1245 ⋅ ⋅](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-30.webp?w=400)
r0024 CO: Act. filtered output freq. Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual output frequency. Slip compensation, resonance damping and frequency limitation are included. r0025 CO: Act. filtered output voltage Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays [rms] voltage applied to motor. r0026 CO: Act. filtered DC-link volt. Min: - Datatype: Float Unit: V Def: - P-Group: INVERTER Max: -
Displays DC-link voltage.
Mains 200 - 240 V 380 - 480 V 500 - 600 V
1020 V 840 V (FS A - C) 820 V (FS D - F) 820 V (FS FX, GX)
420 V (FS A - C) 410 V (FS D - F) UDC_max_trip F0002
UDC_min_trip F0003 215 V 430 V (FS A - F) 380 V (FS FX, GX) 530 V
UDC_Comp (P1236) r1242 0.98⋅
UDC_Chopper (P1237) r1242 0.98⋅ r0027 CO: Act. filtered output current Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays [rms] value of motor current [A]. r0029 CO: Act. filtered current Isd Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays flux-generating current component. The flux-generating current component is based on the nominal flux, which is calculated from the motor parameters (P0340 - Calculation of motor parameters). Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero. Note:
The flux-generating current component is generally constant up to the base speed of the motor; above base speed, this component is weakened (field weakening) thus enabling an increase in motor speed but at reduced torque. r0030 CO: Act. filtered current Isq Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays torque-generating current component. Note:
For asynchronous motors, a limit is calculated for the torque generating current component (in conjunction with the maximum possible output voltage (r0071), motor leakage and current field weakening (r0377)) and this prevents motor stalling.

r0031 CO: Act. filtered torque Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays electrical torque.
i Z L L 2 3 m sq rd p R
m M ⋅ Ψ ⋅ ⋅ ⋅ = : mM
Motor torque Pole pair number Rotor flux Rotor inductance Magnetizing inductance Torque-generating current Motor counter EMF
: Zp
: rd Ψ
Valid for V/f-caracteristic:
: Lm
| i| R cos | i| u i
⋅ − ϕ ⋅ ⋅ ≈
: isq
: e
Output value will be zero at low speeds when the current injection is active (r1751.5 = 1). Note:
The electrical torque is not the same as the mechanical torque, which can be measured on the shaft. Due to windage and friction a part of the electrical torque is lost in the motor. r0032 CO: Act. filtered power Min: - Datatype: Float Unit: - Def: - P-Group: CONTROL Max: -
Displays motor power (power output at the motor shaft).

M f 2 M Pmech ⋅ ⋅ π ⋅ = ⋅ ω = ⇒
1 [kW ] r0032 ⋅ =
[Nm] r0031 [1/min] 60 r0022 π 2 1000
[kW] r0032 0.75 [hp] r0032 ⋅ =
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America). r0035[3] CO: Act. motor temperature Min: - Datatype: Float Unit: °C Def: - P-Group: MOTOR Max: -
Displays measured motor temperature. Index:
r0035[0] : 1st. Drive data set (DDS) r0035[1] : 2nd. Drive data set (DDS) r0035[2] : 3rd. Drive data set (DDS)

r0036 CO:Inverter overload utilization Min: - Datatype: Float Unit: % Def: - P-Group: INVERTER Max: -
Displays inverter overload utilization calculated via I2t model. The actual I2t value relative to the max. possible I2t value supplies utilization in [%]. If the current exceeds the threshold for P0294 (inverter I2t overload warning), alarm A0505 (inverter I2t) is generated and the output current of the inverter reduced via P0290 (inverter overload reaction). If 100 % utilization is exceeded, alarm F0005 (inverter I2t) is tripped. Example:
t i2t [%]
t Dependency:
r0036 > 0: If the nominal current of the inverter is exceed, utilization will be displayed. Otherwise, 0 % utilization is displayed. r0037[5] CO: Inverter temperature [°C] Min: - Datatype: Float Unit: °C Def: - P-Group: INVERTER Max: -
Displays measured heatsink temperature and calculated junction temperature of IGBTs based on thermal model. Index:
r0037[0] : Measured heat sink temperature r0037[1] : Chip temperature r0037[2] : Rectifier temperature r0037[3] : Inverter ambient temperature r0037[4] : Control board temperature r0038 CO: Act. power factor Min: - Datatype: Float Unit: - Def: - P-Group: CONTROL Max: -
Displays actual power factor. Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value 1. r0039 CO: Energy consumpt. meter [kWh] Min: - Datatype: Float Unit: kWh Def: - P-Group: INVERTER Max: -
Displays electrical energy used by inverter since display was last reset (see P0040 - reset energy consumption meter).
0 0 W ⋅ ϕ ⋅ ⋅ ⋅ ∫ = ⋅ ∫ =
dt cos i u 3 dt P r0039
Dependency:
Value is reset when P0040 = 1 (reset energy consumption meter).

P0040 Reset energy consumption meter Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 1
Resets value of parameter r0039 (energy consumption meter) to zero. Possible Settings:
0 No reset 1 Reset r0039 to 0 Dependency:
No reset until "P" is pressed. r0050 CO: Active command data set Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays currently selected and active command data set (CDS). Possible Settings:
0 1st. Command data set (CDS) 1 2nd. Command data set (CDS) 2 3rd. Command data set (CDS) Details:
See parameter P0810. r0051[2] CO: Active drive data set (DDS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays currently selected and active drive data set (DDS). Possible Settings:
0 1st. Drive data set (DDS) 1 2nd. Drive data set (DDS) 2 3rd. Drive data set (DDS) Index:
See parameter P0820.

r0052 CO/BO: Act. status word 1 Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays first active status word of inverter (bit format) and can be used to diagnose inverter status. Bitfields:
Bit00 Drive ready 0 NO 1 YES Bit01 Drive ready to run 0 NO 1 YES Bit02 Drive running 0 NO 1 YES Bit03 Drive fault active 0 NO 1 YES Bit04 OFF2 active 0 YES 1 NO Bit05 OFF3 active 0 YES 1 NO Bit06 ON inhibit active 0 NO 1 YES Bit07 Drive warning active 0 NO 1 YES Bit08 Deviation setpoint / act. value 0 YES 1 NO Bit09 PZD control 0 NO 1 YES Bit10 Maximum frequency reached 0 NO 1 YES Bit11 Warning: Motor current limit 0 YES 1 NO Bit12 Motor holding brake active 0 NO 1 YES Bit13 Motor overload 0 YES 1 NO Bit14 Motor runs right 0 NO 1 YES Bit15 Inverter overload 0 YES 1 NO Dependency:

r0052 Bit03 "Drive fault active": Output of Bit3 (Fault) will be inverted on digital output (Low = Fault, High = No Fault). r0052 Bit08 "Deviation setpoint / act. value" ==> see parameter P2164 r0052 Bit10 "f_act >= P1082 (f_max)" ==> see parameter P1082 r0052 Bit12 "Motor holding brake active" ==> see parameter P1215

r0052 Bit14 "Motor runs right" ==> see below
ON
left not defined last state is displayed
Details:
The 7-segment display of the bit-parameters (binary parameters) is explained in the Introduction of the Parameter List. r0053 CO/BO: Act. status word 2 Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays second status word of inverter (in bit format). Bitfields:
Bit00 DC brake active 0 NO 1 YES Bit01 f_act > P2167 (f_off) 0 NO 1 YES Bit02 f_act P2170 0 NO 1 YES Bit04 f_act > P2155 (f_1) 0 NO 1 YES Bit05 f_act = setpoint 0 NO 1 YES Bit07 Act. Vdc r0026 < P2172 0 NO 1 YES Bit08 Act. Vdc r0026 > P2172 0 NO 1 YES Bit09 Ramping finished 0 NO 1 YES Bit10 PID output r2294 == P2292 (PID_min) 0 NO 1 YES Bit11 PID output r2294 == P2291 (PID_max) 0 NO 1 YES Bit14 Download data set 0 from AOP 0 NO 1 YES Bit15 Download data set 1 from AOP 0 NO 1 YES Note:
- r0053 Bit00 ==> see parameter P1233 - r0053 Bit01 ==> see parameter P2167 - r0053 Bit02 ==> see parameter P1080 - r0053 Bit03 ==> see parameter P2170 - r0053 Bit04 ==> see parameter P2155 - r0053 Bit05 ==> see parameter P2155 - r0053 Bit06 ==> see parameter P2150 - r0053 Bit07 ==> see parameter P2172 - r0053 Bit08 ==> see parameter P2172

r0053 Bit09 "Ramping finished" ==> see below
OFF
Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System Parameters" in this manual. r0054 CO/BO: Act. control word 1 Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays first control word of inverter and can be used to diagnose which commands are active. Bitfields:
Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit02 OFF3: Fast stop 0 YES 1 NO Bit03 Pulses enabled 0 NO 1 YES Bit04 RFG enable 0 NO 1 YES Bit05 RFG start 0 NO 1 YES Bit06 Setpoint enable 0 NO 1 YES Bit07 Fault acknowledge 0 NO 1 YES Bit08 JOG right 0 NO 1 YES Bit09 JOG left 0 NO 1 YES Bit10 Control from PLC 0 NO 1 YES Bit11 Reverse (setpoint inversion) 0 NO 1 YES Bit13 Motor potentiometer MOP up 0 NO 1 YES Bit14 Motor potentiometer MOP down 0 NO 1 YES Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System Parameters" in this manual. r0055 CO/BO: Act. control word 2 Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays additional control word of inverter and can be used to diagnose which commands are active. Bitfields:
Bit00 Fixed frequency Bit 0 0 NO 1 YES Bit01 Fixed frequency Bit 1 0 NO 1 YES Bit02 Fixed frequency Bit 2 0 NO 1 YES Bit03 Fixed frequency Bit 3 0 NO 1 YES Bit04 Drive data set (DDS) Bit 0 0 NO 1 YES Bit05 Drive data set (DDS) Bit 1 0 NO 1 YES Bit08 PID enabled 0 NO 1 YES Bit09 DC brake enabled 0 NO 1 YES Bit11 Droop enabled 0 NO 1 YES Bit12 Torque control 0 NO 1 YES Bit13 External fault 1 0 YES 1 NO Bit15 Command data set (CDS) Bit 1 0 NO 1 YES Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System Parameters" in this handbook.

r0056 CO/BO: Status of motor control Min: - Datatype: U16 Unit: - Def: - P-Group: CONTROL Max: -
Displays status of motor control (MM420: V/f status), which can be used to diagnose inverter status. Bitfields:
Bit00 Init. control finished 0 NO 1 YES Bit01 Motor demagnetizing finished 0 NO 1 YES Bit02 Pulses enabled 0 NO 1 YES Bit03 Voltage soft start selected 0 NO 1 YES Bit04 Motor excitation finished 0 NO 1 YES Bit05 Starting boost active 0 NO 1 YES Bit06 Acceleration boost active 0 NO 1 YES Bit07 Frequency is negative 0 NO 1 YES Bit08 Field weakening active 0 NO 1 YES Bit09 Volts setpoint limited 0 NO 1 YES Bit10 Slip frequency limited 0 NO 1 YES Bit11 F_out > F_max Freq. limited 0 NO 1 YES Bit12 Phase reversal selected 0 NO 1 YES Bit13 I-max controller active 0 NO 1 YES Bit14 Vdc-max controller active 0 NO 1 YES Bit15 KIB (Vdc-min control) active 0 NO 1 YES Details:
See description of seven-segment display given in the introduction. r0061 CO: Act. encoder frequency Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual frequency detected by encoder. r0062 CO: Freq. setpoint Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays frequency setpoint of vector controller. r0063 CO: Act. frequency Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual unfiltered frequency. This value is not smoothed in contrary to r0021.
Act. frequencies:
Act. filtered speed r0313
Act. filtered frequency
Act. frequency
Act. encoder frequency
P1300 = 21,23 and P0400 = 0 --> F0090

r0064 CO: Dev. frequency controller Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual deviation of speed controller. This value is calculated from the frequency setpoint (r0062) and the actual frequency (r0063). Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero. r0065 CO: Slip frequency Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays slip frequency of motor in [%] relative to the rated motor frequency (P0310). Details:
For V/f control, see also P1335 (slip compensation). r0066 CO: Act. output frequency Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays actual output frequency. Note:
The output frequency is limited by the values entered in P1080 (min. frequency) and P1082 (max. frequency). r0067 CO: Act. output current limit Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays valid maximum output current of inverter. Parameter r0067 is influenced/determined by the following factors: - Rated motor current P0305 - Motor overload factor P0640 - Motor protection in dependency of P0610 - r0067 is less than or equal to maximum inverter current r0209 - Inverter protection in dependency of P0290
A reduction of r0067 may indicate an inverter overload or a motor overload. r0068 CO: Output current Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays unfiltered [rms] value of motor current [A]. Note:
This is used for the process control (contrary to the smoothed output current r0027, that is used for display). r0069[6] CO: Act. phase currents Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays phase currents. Index:
r0069[0] : U_phase r0069[1] : V_phase r0069[2] : W_phase r0069[3] : Offset U_phase r0069[4] : Offset V_phase r0069[5] : Offset W_phase

r0070 CO: Act. DC-link voltage Min: - Datatype: Float Unit: V Def: - P-Group: INVERTER Max: -
Displays (unfiltered) DC-link voltage. Note:
Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered and is used to display the value on the BOP/AOP). r0071 CO: Max. output voltage Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays maximum output voltage.
Vmax = f(Vdc,MODmax)
f f 1 ~
Dependency:
- The actual maximum output voltage depends on the actual incoming line supply voltage. - The maximum possible output voltage r0071 of the drive inverter is determined by the DC link voltage r0026 and the maximum modulation depth P1803 in the gating unit. - The maximum output voltage r0071 is tracked with the DC link voltage so that the highest possible value is always and automatically achieved. - The output voltage only reaches the calculated maximum value under steady-state conditions at the rated load. - In the no-load and partial load ranges, lower output voltages r0025 are obtained. r0072 CO: Act. output voltage Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays actual modulation index. The modulation index is defined as ratio between the magnitude of the fundamental component in the inverter phase output voltage and half of the dc-link voltage.

r0075 CO: Current setpoint Isd Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays setpoint of flux generating current component. Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero. r0076 CO: Act. current Isd Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays flux generating current component. Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero. r0077 CO: Current setpoint Isq Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays setpoint for component of torque generating current. Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero. r0078 CO: Act. current Isq Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays component of torque generating current. r0079 CO: Torque setpoint (total) Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays total torque setpoint. Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero. r0080 CO: Act. torque Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays actual torque. Output value will be zero at low frequencies when current injection is active (r1751.5 = 1). r0084 CO: Act. air gap flux Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays air gap flux in [%] relative to the rated motor flux. r0086 CO: Act. active current Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays active (real part) of motor current. Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero. r0090 CO: Act. rotor angle Min: - Datatype: Float Unit: ° Def: - P-Group: CONTROL Max: -
Indicates the current angle of the rotor. This function is not available on single input channel encoders.

P0095[10] CI: Display PZD signals Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source of display for PZD signals. Index:
P0095[0] : 1st PZD signal P0095[1] : 2nd PZD signal P0095[2] : 3rd PZD signal P0095[3] : 4th PZD signal P0095[4] : 5th PZD signal P0095[5] : 6th PZD signal P0095[6] : 7th PZD signal P0095[7] : 8th PZD signal P0095[8] : 9th PZD signal P0095[9] : 10th PZD signal r0096[10] PZD signals Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays PZD signals in [%]. Index:
r0096[0] : 1st PZD signal r0096[1] : 2nd PZD signal r0096[2] : 3rd PZD signal r0096[3] : 4th PZD signal r0096[4] : 5th PZD signal r0096[5] : 6th PZD signal r0096[6] : 7th PZD signal r0096[7] : 8th PZD signal r0096[8] : 9th PZD signal r0096[9] : 10th PZD signal Note:
r0096 = 100 % corresponds to 4000 hex.

P0100 Europe / North America Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: QUICK Active: first confirm QuickComm.: Yes Max: 2
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp]. The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082) are also set automatically here, in addition to reference frequency (P2000). Possible Settings:
0 Europe [kW], frequency default 50 Hz 1 North America [hp], frequency default 60 Hz 2 North America [kW], frequency default 60 Hz Dependency:
Where: - Stop drive first (i.e. disable all pulses) before you change this parameter. - P0100 can only be changed when P0010 = 1 (Commissioning mode) via the respective Commissioing interface (e.g. BOP). - Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (see P0340 - calculation of motor parameters). Changing P0100 overwrites the settings of the DIP50/60 switch (location shown in the diagram below): 1. Parameter P0100 has an higher priority than the DIP50/60 switch. 2. However, after the inverter is powered-on again and P0100 < 2, the DIP50/60 setting will take priority and overwrite P0100. 3. The DIP50/60 switch does not have any effect, if P0100 = 2.


DIP50/60
Power in kW Frequency 50 Hz
Power in kW Frequency 60 Hz
Power in hp Frequency 60 Hz
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see diagram above). P0199 Equipment system number Min: 0 CStat: UT Datatype: U16 Unit: - Def: 0 P-Group: - Active: first confirm QuickComm.: No Max: 255
Equipment system number This parameter has no operation effect.

r0200 Act. power stack code number Min: - Datatype: U32 Unit: - Def: - P-Group: INVERTER Max: -
Identifies hardware variant as shown in table below.
MLFB Input Voltage & Frequency CT Power
No.
41 6SE6440-2UC11-2AAx 1/3AC200-240V +10% -10% 47-63Hz 0,12 0,12 no A 42 6SE6440-2UC12-5AAx 1/3AC200-240V +10% -10% 47-63Hz 0,25 0,25 no A 43 6SE6440-2UC13-7AAx 1/3AC200-240V +10% -10% 47-63Hz 0,37 0,37 no A 44 6SE6440-2UC15-5AAx 1/3AC200-240V +10% -10% 47-63Hz 0,55 0,55 no A 45 6SE6440-2UC17-5AAx 1/3AC200-240V +10% -10% 47-63Hz 0,75 0,75 no A 46 6SE6440-2AB11-2AAx 1AC200-240V +10% -10% 47-63Hz 0,12 0,12 Cl. A A 47 6SE6440-2AB12-5AAx 1AC200-240V +10% -10% 47-63Hz 0,25 0,25 Cl. A A 48 6SE6440-2AB13-7AAx 1AC200-240V +10% -10% 47-63Hz 0,37 0,37 Cl. A A 49 6SE6440-2AB15-5AAx 1AC200-240V +10% -10% 47-63Hz 0,55 0,55 Cl. A A 50 6SE6440-2AB17-5AAx 1AC200-240V +10% -10% 47-63Hz 0,75 0,75 Cl. A A 51 6SE6440-2UC21-1BAx 1/3AC200-240V +10% -10% 47-63Hz 1,1 1,1 no B 52 6SE6440-2UC21-5BAx 1/3AC200-240V +10% -10% 47-63Hz 1,5 1,5 no B 53 6SE6440-2UC22-2BAx 1/3AC200-240V +10% -10% 47-63Hz 2,2 2,2 no B 54 6SE6440-2AB21-1BAx 1AC200-240V +10% -10% 47-63Hz 1,1 1,1 Cl. A B 55 6SE6440-2AB21-5BAx 1AC200-240V +10% -10% 47-63Hz 1,5 1,5 Cl. A B 56 6SE6440-2AB22-2BAx 1AC200-240V +10% -10% 47-63Hz 2,2 2,2 Cl. A B 57 6SE6440-2UC23-0CAx 1/3AC200-240V +10% -10% 47-63Hz 3 3 no C 58 6SE6440-2UC24-0CAx 3AC200-240V +10% -10% 47-63Hz 4 5,5 no C 59 6SE6440-2UC25-5CAx 3AC200-240V +10% -10% 47-63Hz 5,5 7,5 no C 60 6SE6440-2AB23-0CAx 1AC200-240V +10% -10% 47-63Hz 3 3 Cl. A C 61 6SE6440-2AC23-0CAx 3AC200-240V +10% -10% 47-63Hz 3 3 Cl. A C 62 6SE6440-2AC24-0CAx 3AC200-240V +10% -10% 47-63Hz 4 5,5 Cl. A C 63 6SE6440-2AC25-5CAx 3AC200-240V +10% -10% 47-63Hz 5,5 7,5 Cl. A C 64 6SE6440-2UC27-5DAx 3AC200-240V +10% -10% 47-63Hz 7,5 11 no D 65 6SE6440-2UC31-1DAx 3AC200-240V +10% -10% 47-63Hz 11 15 no D 66 6SE6440-2UC31-5DAx 3AC200-240V +10% -10% 47-63Hz 15 18,5 no D 67 6SE6440-2AC27-5DAx 3AC200-240V +10% -10% 47-63Hz 7,5 11 Cl. A D 68 6SE6440-2AC31-1DAx 3AC200-240V +10% -10% 47-63Hz 11 15 Cl. A D 69 6SE6440-2AC31-5DAx 3AC200-240V +10% -10% 47-63Hz 15 18,5 Cl. A D 70 6SE6440-2UC31-8EAx 3AC200-240V +10% -10% 47-63Hz 18,5 22 no E 71 6SE6440-2UC32-2EAx 3AC200-240V +10% -10% 47-63Hz 22 30 no E 72 6SE6440-2AC31-8EAx 3AC200-240V +10% -10% 47-63Hz 18,5 22 Cl. A E 73 6SE6440-2AC32-2EAx 3AC200-240V +10% -10% 47-63Hz 22 30 Cl. A E 74 6SE6440-2UC33-0FAx 3AC200-240V +10% -10% 47-63Hz 30 37 no F 75 6SE6440-2UC33-7FAx 3AC200-240V +10% -10% 47-63Hz 37 45 no F 76 6SE6440-2UC34-5FAx 3AC200-240V +10% -10% 47-63Hz 45 45 no F 77 6SE6440-2AC33-0FAx 3AC200-240V +10% -10% 47-63Hz 30 37 Cl. A F 78 6SE6440-2AC33-7FAx 3AC200-240V +10% -10% 47-63Hz 37 45 Cl. A F 79 6SE6440-2AC34-5FAx 3AC200-240V +10% -10% 47-63Hz 45 45 Cl. A F 80 6SE6440-2UD13-7AAx 3AC380-480V +10% -10% 47-63Hz 0,37 0,37 no A 81 6SE6440-2UD15-5AAx 3AC380-480V +10% -10% 47-63Hz 0,55 0,55 no A 82 6SE6440-2UD17-5AAx 3AC380-480V +10% -10% 47-63Hz 0,75 0,75 no A 83 6SE6440-2UD21-1AAx 3AC380-480V +10% -10% 47-63Hz 1,1 1,1 no A 84 6SE6440-2UD21-5AAx 3AC380-480V +10% -10% 47-63Hz 1,5 1,5 no A 85 6SE6440-2UD22-2BAx 3AC380-480V +10% -10% 47-63Hz 2,2 2,2 no B 86 6SE6440-2UD23-0BAx 3AC380-480V +10% -10% 47-63Hz 3 3 no B 87 6SE6440-2UD24-0BAx 3AC380-480V +10% -10% 47-63Hz 4 4 no B 88 6SE6440-2AD22-2BAx 3AC380-480V +10% -10% 47-63Hz 2,2 2,2 Cl. A B 89 6SE6440-2AD23-0BAx 3AC380-480V +10% -10% 47-63Hz 3 3 Cl. A B 90 6SE6440-2AD24-0BAx 3AC380-480V +10% -10% 47-63Hz 4 4 Cl. A B 91 6SE6440-2UD25-5CAx 3AC380-480V +10% -10% 47-63Hz 5,5 7,5 no C 92 6SE6440-2UD27-5CAx 3AC380-480V +10% -10% 47-63Hz 7,5 11 no C 93 6SE6440-2UD31-1CAx 3AC380-480V +10% -10% 47-63Hz 11 15 no C

MLFB Input Voltage & Frequency CT Power
No.
94 6SE6440-2AD25-5CAx 3AC380-480V +10% -10% 47-63Hz 5,5 7,5 Cl. A C 95 6SE6440-2AD27-5CAx 3AC380-480V +10% -10% 47-63Hz 7,5 11 Cl. A C 96 6SE6440-2AD31-1CAx 3AC380-480V +10% -10% 47-63Hz 11 15 Cl. A C 97 6SE6440-2UD31-5DAx 3AC380-480V +10% -10% 47-63Hz 15 18,5 no D 98 6SE6440-2UD31-8DAx 3AC380-480V +10% -10% 47-63Hz 18,5 22 no D 99 6SE6440-2UD32-2DAx 3AC380-480V +10% -10% 47-63Hz 22 30 no D 100 6SE6440-2AD31-5DAx 3AC380-480V +10% -10% 47-63Hz 15 18,5 Cl. A D 101 6SE6440-2AD31-8DAx 3AC380-480V +10% -10% 47-63Hz 18,5 22 Cl. A D 102 6SE6440-2AD32-2DAx 3AC380-480V +10% -10% 47-63Hz 22 30 Cl. A D 103 6SE6440-2UD33-0EAx 3AC380-480V +10% -10% 47-63Hz 30 37 no E 104 6SE6440-2UD33-7EAx 3AC380-480V +10% -10% 47-63Hz 37 45 no E 105 6SE6440-2AD33-0EAx 3AC380-480V +10% -10% 47-63Hz 30 37 Cl. A E 106 6SE6440-2AD33-7EAx 3AC380-480V +10% -10% 47-63Hz 37 45 Cl. A E 107 6SE6440-2UD34-5FAx 3AC380-480V +10% -10% 47-63Hz 45 55 no F 108 6SE6440-2UD35-5FAx 3AC380-480V +10% -10% 47-63Hz 55 75 no F 109 6SE6440-2UD37-5FAx 3AC380-480V +10% -10% 47-63Hz 75 90 no F 110 6SE6440-2AD34-5FAx 3AC380-480V +10% -10% 47-63Hz 45 55 Cl. A F 111 6SE6440-2AD35-5FAx 3AC380-480V +10% -10% 47-63Hz 55 75 Cl. A F 112 6SE6440-2AD37-5FAx 3AC380-480V +10% -10% 47-63Hz 75 90 Cl. A F 113 6SE6440-2UE17-5CAx 3AC500-600V +10% -10% 47-63Hz 0,75 1,5 no C 114 6SE6440-2UE21-5CAx 3AC500-600V +10% -10% 47-63Hz 1,5 2,2 no C 115 6SE6440-2UE22-2CAx 3AC500-600V +10% -10% 47-63Hz 2,2 4 no C 116 6SE6440-2UE24-0CAx 3AC500-600V +10% -10% 47-63Hz 4 5,5 no C 117 6SE6440-2UE25-5CAx 3AC500-600V +10% -10% 47-63Hz 5,5 7,5 no C 118 6SE6440-2UE27-5CAx 3AC500-600V +10% -10% 47-63Hz 7,5 11 no C 119 6SE6440-2UE31-1CAx 3AC500-600V +10% -10% 47-63Hz 11 15 no C 120 6SE6440-2UE31-5DAx 3AC500-600V +10% -10% 47-63Hz 15 18,5 no D 121 6SE6440-2UE31-8DAx 3AC500-600V +10% -10% 47-63Hz 18,5 22 no D 122 6SE6440-2UE32-2DAx 3AC500-600V +10% -10% 47-63Hz 22 30 no D 123 6SE6440-2UE33-0EAx 3AC500-600V +10% -10% 47-63Hz 30 37 no E 124 6SE6440-2UE33-7EAx 3AC500-600V +10% -10% 47-63Hz 37 45 no E 125 6SE6440-2UE34-5FAx 3AC500-600V +10% -10% 47-63Hz 45 55 no F 126 6SE6440-2UE35-5FAx 3AC500-600V +10% -10% 47-63Hz 55 75 no F 127 6SE6440-2UE37-5FAx 3AC500-600V +10% -10% 47-63Hz 75 90 no F 1001 6SE6440-2UD38-8FAx 3AC400-480V +10% -10% 47-63Hz 90 110 no FX 1002 6SE6440-2UD41-1FAx 3AC400-480V +10% -10% 47-63Hz 110 132 no FX 1003 6SE6440-2UD41-3GAx 3AC400-480V +10% -10% 47-63Hz 132 160 no GX 1004 6SE6440-2UD41-6GAx 3AC400-480V +10% -10% 47-63Hz 160 200 no GX 1005 6SE6440-2UD42-0GAx 3AC400-480V +10% -10% 47-63Hz 200 250 no GX
Parameter r0200 = 0 indicates that no power stack has been identified. P0201 Power stack code number Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 65535
Confirms actual power stack identified. r0203 Act. inverter type Min: - Datatype: U16 Unit: - Def: - P-Group: INVERTER Max: -
Type number of actual inverter identified. Possible Settings:
1 MICROMASTER 420 2 MICROMASTER 440 3 MICRO- / COMBIMASTER 411 4 MICROMASTER 410 5 Reserved 6 MICROMASTER 440 PX 7 MICROMASTER 430

Displays hardware features of power stack. Bitfields:
Bit00 DC input voltage 0 NO 1 YES Bit01 RFI filter 0 NO 1 YES Note:
Parameter r0204 = 0 indicates that no power stack has been identified. P0205 Inverter application Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: INVERTER Active: first confirm QuickComm.: Yes Max: 1
Selects inverter application. The inverter and motor requirements are determined by the speed range and torque requirements of the load. The relationship between speed and torque for different loads (constant torque loads or variable torque loads). Possible Settings:
0 Constant torque 1 Variable torque Note:
Constant torque (CT): CT is used if the application needs a constant torque on the whole frequency range. Many loads can be considered to be constant torque loads. Typical constant torque loads are conveyors, compressors and positve displacement pumps (see diagram). Variable torque (VT): VT is used if the application has a parabolic frequency-torque characteristic like many fans and pumps. Variable torque allows with the same inverter: - Higher rated inverter current r0207 - Higher rated inverter power r0206 - Higher threshold for I2t protection If P0205 is modified in quick commissioning it immediately calculates various motor parameters: - P0305 Rated motor current - P0307 Rated motor power - P0640 Motor overload factor
M = const. f 1 ~ M f ~ M M ~ f 2
P = const. P ~ f P ~ f 2 P ~ f 3
M
M
M
Winders Facing lathes Rotary cutting machines
Hoisting gear Belt conveyors Process machines Involving forming Rolling mills Planers Compressors
Calenders with viscous friction Eddy-current brakes

It is recommended to modify P0205 first. Afterwards motor parameter may be adapted. Motor parameter will be overridden by changing this sequence.
r0207 I r0208 P r0209 I
P0500 P0205 Control parameter
P0305 I P0307 P P0640 I
M,n M,max Technology parameter
- The parameter value is not reset by the factory setting (see P0970). - To set P0205 = 1 (variable torque) is not possible for all inverters. - Use setting 1 (variable torque) only for variable-torque applications (e.g. pumps and fans). If used for constant-load applications, I2t warning will be produced too late, causing overheating in the motor. r0206 Rated inverter power [kW] / [hp] Min: - Datatype: Float Unit: - Def: - P-Group: INVERTER Max: -
Displays nominal rated motor power from inverter. Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
[kW] r0206 0.75 [hp] r0206 ⋅ = r0207[3] Rated inverter current Min: - Datatype: Float Unit: A Def: - P-Group: INVERTER Max: -
Indicates the rated inverter current. Index:
VT (variable torque) and CT (constant torque) specify the overload capability (CT/VT application) of the inverter. The definition of the rated as well as the overload and base load values depend on the inverter type and inverter power. The different values can be taken from the appropriate Catalog or are saved in the drive inverter (refer to Fig.). The VT rated current r0207[1] or CT rated current r0207[2] represent the matching 4-pole Siemens IEC standard motor for the selected load duty cycle (refer to the diagram). Parameters r0207[1] or r0207[2] are used as default values for P0305 as a function of the CT/VT application (load duty cycle). If r0207[1] = r0207[2], then it is not possible to make a differentiation between a CT/VT application. Overload in operation is only possible if, before the overload condition, the load current was less than the rated current. For drives, which must be able to handle overload conditions, it is first necessary to define a base load current for the required load. If the full overload capability is used, then this is detected using an I²t monitoring and the power module is protected as a function of parameter P0290. r0208 Rated inverter voltage Min: - Datatype: U32 Unit: V Def: - P-Group: INVERTER Max: -
Displays nominal AC supply voltage of inverter. Value:
r0208 = 230 : 200 - 240 V +/- 10 % r0208 = 400 : 380 - 480 V +/- 10 % r0208 = 575 : 500 - 600 V +/- 10 %

Displays maximum output current of inverter. Dependency:
Parameter r0209 depends on the derating which is affected by pulse frequency P1800, ambient temperature and altitude. The data of deration is given in the OPERATING INSRTRUCTION. P0210 Supply voltage Min: 0 CStat: CT Datatype: U16 Unit: V Def: 230 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 1000
Parameter P0210 defines the supply voltage. Its default value depends upon the type of inverter. If P0210 does not correspond to the supply voltage, then it must be modified. When P0210 has been modified, the following thresholds are changed: Dependency:
Optimizes Vdc controller, which extends the ramp-down time if regenerative energy from motor would otherwise cause DC link overvoltage trips. Reducing the value enables controller to cut in earlier and reduce the risk of overvoltage. Set P1254 ("Auto detect Vdc switch-on levels") = 0. Cut-in levels for Vdc-controller and compound braking are then derived directly from P0210 (supply voltage).
Compound braking switch-on level
Dynamic braking switch-on level
- If mains voltage is higher than value entered, automatic deactivation of the Vdc controller may occur to avoid acceleration of the motor. An alarm will be issued in this case (A0910). - Default value is depending on inverter type and its rating data. r0231[2] Max. cable length Min: - Datatype: U16 Unit: m Def: - P-Group: INVERTER Max: -
Indexed parameter to display maximum allowable cable length between inverter and motor. Index:
For full EMC compliance, the screened cable must not exceed 25 m in length when an EMC filter is fitted.
Vdc_min switch-on level · Vdc_max switch-on level

P0290 Inverter overload reaction Min: 0 CStat: CT Datatype: U16 Unit: - Def: 2 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 3
Selects reaction of inverter to an internal over-temperature. Following physical values influence the inverter overload protection (see diagram): - heat sink temperature - junction temperature (IGBT temperature) - inverter I²t
i2t P0294
A0505
(SLVC, VC)
r0037 Heat sink temperature
F0004
F0005
Possible Settings:
0 Reduce output frequency 1 Trip (F0004) 2 Reduce pulse frequency and output frequency 3 Reduce pulse frequency then trip (F0004) Notice:
P0290 = 0: Reduction of output frequency is only effective if the load is also reduced. This is for example valid for variable torque applications with a quadratic torque characteristic as pumps or fans. A trip will always result, if the action taken does not sufficiently reduce internal temperature. The pulse frequency P1800 is reduced only if higher than 2 kHz. The actual pulse frequency is displayed in parameter r1801. P0291[3] Inverter protection Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 7
Bit 02 shows if phase loss dedection (input phase) of 3 phase inverters is enabled after factory reset. Default setting of phase loss is disabled for FSA - FSC. FSD and greater it is enabled. Bitfields:
Bit00 Reserved 0 NO 1 YES Bit01 Reserved 0 NO 1 YES Bit02 Phase loss detection enable 0 NO 1 YES Index:
P0291[0] : 1st. Drive data set (DDS) P0291[1] : 2nd. Drive data set (DDS) P0291[2] : 3rd. Drive data set (DDS) Details:
See P0290 (inverter overload reaction)

P0292 Inverter temperature warning Min: 0 CStat: CUT Datatype: U16 Unit: °C Def: 5 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 25
Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the user.
Temperature warning threshold of inverter T_warn
trip T = T - P0292
Temperature shutdown threshold of inverter T_trip
Temperature MM440, Frame Size
F 600 V
FX 95 kW CT
GX 132 kW CT
95 °C
80 °C
88 °C
91 °C
80 °C
82 °C
88 °C
IGBT
140 °C
145 °C
145 °C
150 °C
150 °C
145 °C
147 °C
150 °C
75 °C
75 °C
75 °C
75 °C
75 °C
55 °C
55 °C
55 °C
55 °C
50 °C
65 °C 65 °C
65 °C 65 °C
65 °C
If the actual inverter temperature (r0037) exceeds the corresponding threshold, a warning A0504, if the temperature still increases then a fault F0004 will be displayed. P0294 Inverter I2t overload warning Min: 10.0 CStat: CUT Datatype: Float Unit: % Def: 95.0 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 100.0
Defines the [%] value at which alarm A0505 (inverter I2t) is generated. Inverter I2t calculation is used to determine a maximum tolerable period for inverter overload. The I2t calculation value is deemed = 100 % when this maximum tolerable period is reached. Dependency:
That the output current of the inverter has been reduced and that the value of I2t does not exceed 100%. Note:
P0294 = 100 % corresponds to stationary nominal load. P0295 Inverter fan off delay time Min: 0 CStat: CUT Datatype: U16 Unit: s Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 3600
Defines inverter fan switch off delay time in seconds after drive has stopped. Note:
Setting to 0, inverter fan will switch off when the drive stops, that is no delay.

P0300[3] Select motor type Min: 1 CStat: C Datatype: U16 Unit: - Def: 1 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 2
Selects motor type. This parameter is required during commissioning to select motor type and optimize inverter performance. Most motors are asynchronous; if in doubt, use the formula below.
60 P0310 x ⋅ =
Synchronous motor x = 1, 2, ..., n :
x ≠ 1, 2, ..., n : Asynchronous motor
If the result is a whole number, the motor is synchronous. Possible Settings:
1 Asynchronous rotational motor 2 Synchronous rotational motor Index:
P0300[0] : 1st. Drive data set (DDS) P0300[1] : 2nd. Drive data set (DDS) P0300[2] : 3rd. Drive data set (DDS) Dependency:
Changeable only when P0010 = 1 (quick commissioning). If synchronous motor is selected, the following functions are not available: - P0308 Power factor - P0309 Motor efficiency - P0346 Magnetization time - P0347 Demagnetization time - P1335 Slip compensation - P1336 Slip limit - P0320 Motor magnetizing current - P0330 Rated motor slip - P0331 Rated magnetization current - P0332 Rated power factor - P0384 Rotor time constant - P1200, P1202, P1203 Flying start - P1230, P1232, P1233 DC braking

P0304[3] Rated motor voltage Min: 10 CStat: C Datatype: U16 Unit: V Def: 230 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 2000
Nominal motor voltage [V] from rating plate. Following diagram shows a typical rating plate with the locations of the relevant motor data.

1 AC 230 V
3 AC 230 V
3 AC 400 V
3 AC 500 V
MICROMASTER 410
MICROMASTER 411
MICROMASTER 420
MICROMASTER 430
MICROMASTER 440
*) Line supply voltage 1-ph. 110 V AC is stepped-up --> frequency inverter output voltage 3-ph. 230 V AC
Index:
P0304[0] : 1st. Drive data set (DDS) P0304[1] : 2nd. Drive data set (DDS) P0304[2] : 3rd. Drive data set (DDS) Dependency:
- Changeable only when P0010 = 1 (quick commissioning). - Default value is depending on inverter type and its rating data. Caution:
The input of rating plate data must correspond with the wiring of the motor (star / delta). This means, if delta wiring is used for the motor, delta rating plate data has to be entered.
U2
W2
U2
U1
W1
U1
W1
U1
U1
V1 W1
V1 W1
e.g.: Volts 230 V (Delta connection) / 400 V (Star connection)

NEMA Motor T1
Volts U V W
T1-T7 T2-T8 T3-T9 low T4-T5-T6 T1 T2 T3 high
T1-T7 T2-T8 T3-T9
T 6 T 9 T 8
e.g.: Volts 230 V YY (low) / 460 V Y (high)
T 3
T 2
T 1
U V W
T 4 T 7
T 9 T 6
T1-T6-T7 T2-T4-T8 T3-T5-T9 -
T1 T2 T3 T4-T7 T5-T8 T6-T9
P0305[3] Rated motor current Min: 0.01 CStat: C Datatype: Float Unit: A Def: 3.25 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 10000.00
Nominal motor current [A] from rating plate - see diagram in P0304. Index:
P0305[0] : 1st. Drive data set (DDS) P0305[1] : 2nd. Drive data set (DDS) P0305[2] : 3rd. Drive data set (DDS) Dependency:
- Changeable only when P0010 = 1 (quick commissioning). - Default value is depending on inverter type and its rating data. - Depends also on P0320 (motor magnetization current). Note:
The maximum value of P0305 depends on the maximum inverter current r0209 and the motor type:
It is recommanded that the ratio of P0305 (rated motor current) and r0207 (rated inverter current) should not be lower than:
U/f :
P0305 4 1 ≤ P0307[3] Rated motor power Min: 0.01 CStat: C Datatype: Float Unit: - Def: 0.12 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 2000.00
SLVC and VC :
Nominal motor power [kW/hp] from rating plate. Index:
P0307[0] : 1st. Drive data set (DDS) P0307[1] : 2nd. Drive data set (DDS) P0307[2] : 3rd. Drive data set (DDS) Dependency:
- If P0100 = 1, values will be in [hp] - see diagram P0304 (rating plate). - Changeable only when P0010 = 1 (quick commissioning). - Default value is depending on inverter type and its rating data.

P0308[3] Rated motor cosPhi Min: 0.000 CStat: C Datatype: Float Unit: - Def: 0.000 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 1.000
Nominal motor power factor (cosPhi) from rating plate - see diagram P0304. Index:
P0308[0] : 1st. Drive data set (DDS) P0308[1] : 2nd. Drive data set (DDS) P0308[2] : 3rd. Drive data set (DDS) Dependency:
- Changeable only when P0010 = 1 (quick commissioning). - Visible only when P0100 = 0 or 2, (motor power entered in [kW]). - Default value is depending on inverter type and its rating data. - Setting 0 causes internal calculation of value. Calculated value see r0332. P0309[3] Rated motor efficiency Min: 0.0 CStat: C Datatype: Float Unit: % Def: 0.0 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 99.9
Nominal motor efficiency in [%] from rating plate. Index:
P0309[0] : 1st. Drive data set (DDS) P0309[1] : 2nd. Drive data set (DDS) P0309[2] : 3rd. Drive data set (DDS) Dependency:
- Changeable only when P0010 = 1 (quick commissioning). - Visible only when P0100 = 1, (i.e. motor power entered in [hp]). - Default value is depending on inverter type and its rating data. - Setting 0 causes internal calculation of value. Calculated value see r0332. Note:
P0309 = 100 % corresponds to superconducting. Details:
See diagram in P0304 (rating plate). P0310[3] Rated motor frequency Min: 12.00 CStat: C Datatype: Float Unit: Hz Def: 50.00 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 650.00
Nominal motor frequency [Hz] from rating plate. Index:
P0310[0] : 1st. Drive data set (DDS) P0310[1] : 2nd. Drive data set (DDS) P0310[2] : 3rd. Drive data set (DDS) Dependency:
- Changeable only when P0010 = 1 (quick commissioning). - Pole pair number recalculated automatically if parameter is changed. Details:
See diagram in P0304 (rating plate) P0311[3] Rated motor speed Min: 0 CStat: C Datatype: U16 Unit: 1/min Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 40000
Nominal motor speed [rpm] from rating plate. Index:
P0311[0] : 1st. Drive data set (DDS) P0311[1] : 2nd. Drive data set (DDS) P0311[2] : 3rd. Drive data set (DDS) Dependency:
- Changeable only when P0010 = 1 (quick commissioning). - Setting 0 causes internal calculation of value. - Slip compensation in V/f control requires rated motor speed for correct operation. - Pole pair number recalculated automatically if parameter is changed. - Default value is depending on inverter type and its rating data. - Required for vector control and V/f control with speed controller. Details:
See diagram in P0304 (rating plate)

Displays number of motor pole pairs that the inverter is currently using for internal calculations. Index:
r0313[0] : 1st. Drive data set (DDS) r0313[1] : 2nd. Drive data set (DDS) r0313[2] : 3rd. Drive data set (DDS) Value:
Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed.
P0310 60 r0313 ⋅ =
P0314[3] Motor pole pair number Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 99
Specifies number of pole pairs of motor. Index:
P0314[0] : 1st. Drive data set (DDS) P0314[1] : 2nd. Drive data set (DDS) P0314[2] : 3rd. Drive data set (DDS) Value:
Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed. P0320[3] Motor magnetizing current Min: 0.0 CStat: CT Datatype: Float Unit: % Def: 0.0 P-Group: MOTOR Active: Immediately QuickComm.: Yes Max: 99.0
Defines motor magnetization current in [%] relative to P0305 (rated motor current). Index:
P0320[0] : 1st. Drive data set (DDS) P0320[1] : 2nd. Drive data set (DDS) P0320[2] : 3rd. Drive data set (DDS) Dependency:
Setting P0320 = 0: causes calculation by - P0340 = 1 (data entered from rating plate) or by - P3900 = 1 - 3 (end of quick commissioning). The calculated value is displayed in parameter r0331. r0330[3] Rated motor slip Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays nominal motor slip in [%] relative to P0310 (rated motor frequency) and P0311 (rated motor speed).
r0313 60 P0311 P0310 [%] r0330 ⋅ ⋅ − =
Index:
r0330[0] : 1st. Drive data set (DDS) r0330[1] : 2nd. Drive data set (DDS) r0330[2] : 3rd. Drive data set (DDS) r0331[3] Rated magnetization current Min: - Datatype: Float Unit: A Def: - P-Group: MOTOR Max: -
Displays calculated magnetizing current of motor in [A]. Index:
r0331[0] : 1st. Drive data set (DDS) r0331[1] : 2nd. Drive data set (DDS) r0331[2] : 3rd. Drive data set (DDS)

Displays power factor for motor Index:
r0332[0] : 1st. Drive data set (DDS) r0332[1] : 2nd. Drive data set (DDS) r0332[2] : 3rd. Drive data set (DDS) Dependency:
Value is calculated internally if P0308 (rated motor cosPhi) set to 0; otherwise, value entered in P0308 is displayed. r0333[3] Rated motor torque Min: - Datatype: Float Unit: Nm Def: - P-Group: MOTOR Max: -
Displays rated motor torque. Index:
r0333[0] : 1st. Drive data set (DDS) r0333[1] : 2nd. Drive data set (DDS) r0333[2] : 3rd. Drive data set (DDS) Dependency:
Value is calculated from P0307 (rated motor power) and P0311 (rated motor speed).
1000 [kW] P0307 [Nm] r0333
2 60 [1/min] P0311
P0335[3] Motor cooling Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 3
Selects motor cooling system used. Possible Settings:
0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan 2 Self-cooled and internal fan 3 Force-cooled and internal fan Index:
P0335[0] : 1st. Drive data set (DDS) P0335[1] : 2nd. Drive data set (DDS) P0335[2] : 3rd. Drive data set (DDS) Caution:
The following combination of parameter setting should not be combined: - P0610 = 1 and P0335 = 0 or 2 : When P0335 = 0 or 2 the inverter cools the motor using a shaft mounted fan. If this is used in conjunction with P0610 the cooling of the motor will be inefficient. In essence, if the i2t calculation reduces the output frequency, then the shaft mounted fan will also reduce its cooling effect, the motor will then eventually overheat and trip. - Exception: Applications with variable torque the reduction of max. current leeds automatically to a reduction of the load / output current. Notice:
Motors of series 1LA1 and 1LA8 have an internal fan. This internal motor fan must not be confused with the fan at the end of the motor shaft.
⋅ = · ⋅ · π

P0340[3] Calculation of motor parameters Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: No Max: 4
Calculates various motor parameters (see table below). This parameter is required during commissioning to optimize inverter performance. Possible Settings:
0 No calculation 1 Complete parameterization 2 Calculation of equivalent circuit data 3 Calculation of V/f and vector control data 4 Calculation of controller settings only Index:
P0340[0] : 1st. Drive data set (DDS) P0340[1] : 2nd. Drive data set (DDS) P0340[2] : 3rd. Drive data set (DDS) Note:
P0340 = 0: No calculation P0340 = 1: The motor weight/moment of inertia (P0344, P0341) are determined starting from the rating plate parameters (P0300 - P0335), the motor equivalent circuit diagram parameters (ESB, P0350 - P0369). The V/f control/vector control parameters and reference quantities are then pre-assigned (includes all of the calculations from P0340 = 2,3,4). P0340 = 2: The motor equivalent circuit diagram parameters (ESB, P0350 - P0369) are calculated starting from the rating plate parameters (without any other pre-assignments made). P0340 = 3: The V/f control/vector control parameters are determined (includes all calculations from P0340 = 4) starting from the motor equivalent circuit diagram parameters (ESB, P0350 - P0369) and motor weight/moment of inertia, moment of inertia ratio (P0344, P0341, P0342). P0340 = 4: The vector control parameters are pre-assigned starting from the motor equivalent circuit diagram parameters (ESB, P0350 - P0369) and motor weight/moment of inertia, moment of inertia ratio (P0344, P0341, P0342).

P0341[3] Motor inertia [kg*m^2]
P0342[3] Total/motor inertia ratio
P0350[3] Stator resistance (line-to-line)
P0356[3] Stator leakage inductance
P0358[3] Rotor leakage inductance
P0362[3] Magnetizing curve flux 1
P0363[3] Magnetizing curve flux 2
P0364[3] Magnetizing curve flux 3
P0365[3] Magnetizing curve flux 4
P0366[3] Magnetizing curve imag 1
P0367[3] Magnetizing curve imag 2
P0368[3] Magnetizing curve imag 3
P0369[3] Magnetizing curve imag 4 P0625[3] Ambient motor temperature
P1253[3] Vdc-controller output limitation
P1316[3] Boost end frequency P1460[3] Gain speed controller
P1462[3] Integral time speed controller
P1470[3] Gain speed controller (SLVC)
P1472[3] Integral time n-ctrl. (SLVC)
P1530[3] Motoring power limitation
P1531[3] Regenerative power limitation
P1715[3] Gain current controller
P1717[3] Integral time current controller
P1764[3] Kp of n-adaption (SLVC)
P1767[3] Tn of n-adaption (SLVC)
P2174[3] Torque threshold M_thresh
P2185[3] Upper torque threshold 1
P2186[3] Lower torque threshold 1
P2187[3] Upper torque threshold 2
P2188[3] Lower torque threshold 2 x
P2189[3] Upper torque threshold 3 P2190[3] Lower torque threshold 3

P0341[3] Motor inertia [kg*m^2] Min: 0.00010 CStat: CUT Datatype: Float Unit: - Def: 0.00180 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 1000.00000
Sets no-load inertia of motor. Together with P0342 (inertia ratio total/motor) and P1496 (scaling factor acceleration), this value produces the acceleration torque (r1517), which can be added to any additional torque produced from a BICO source (P1511), and incorporated in the torque control function. Index:
P0341[0] : 1st. Drive data set (DDS) P0341[1] : 2nd. Drive data set (DDS) P0341[2] : 3rd. Drive data set (DDS) Note:
The result of P0341 * P0342 is included in the speed controller calculation. P0341 * P0342 (inertia ratio total/motor) = total motor inertia P1496 (scaling factor acceleration) = 100 % activates acceleration pre-control for the speed controller and calculates the torque from P0341 (motor inertia) and P0342 (inertia ratio total/motor). P0342[3] Total/motor inertia ratio Min: 1.000 CStat: CUT Datatype: Float Unit: - Def: 1.000 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 400.000
Specifies ratio between total inertia (load + motor) and motor inertia. Index:
P0342[0] : 1st. Drive data set (DDS) P0342[1] : 2nd. Drive data set (DDS) P0342[2] : 3rd. Drive data set (DDS) P0344[3] Motor weight Min: 1.0 CStat: CUT Datatype: Float Unit: kg Def: 9.4 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 6500.0
Specifies motor weight [kg]. Index:
P0344[0] : 1st. Drive data set (DDS) P0344[1] : 2nd. Drive data set (DDS) P0344[2] : 3rd. Drive data set (DDS) Note:
- This value is used in the motor thermal model. - It is normally calculated automatically from P0340 (motor parameters) but can also be entered manually. - Default value is depending on inverter type and its rating data. r0345[3] Motor start-up time Min: - Datatype: Float Unit: s Def: - P-Group: MOTOR Max: -
Displays motor start-up time. This time corresponds to the standardized motor inertia. The start-up time is the time taken to reach rated motor speed from standstill at acceleration with rated motor torque (r0333). Index:
r0345[0] : 1st. Drive data set (DDS) r0345[1] : 2nd. Drive data set (DDS) r0345[2] : 3rd. Drive data set (DDS) P0346[3] Magnetization time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 1.000 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 20.000
Sets magnetization time [s], i.e. waiting time between pulse enable and start of ramp-up. Motor magnetization builds up during this time. Magnetization time is normally calculated automatically from the motor data and corresponds to the rotor time constant (r0384). Index:
P0346[0] : 1st. Drive data set (DDS) P0346[1] : 2nd. Drive data set (DDS) P0346[2] : 3rd. Drive data set (DDS) Note:
- If boost settings are higher than 100 %, magnetization time may be reduced. - Default value is depending on inverter type and its rating data. - An excessive reduction of this time can result in insufficient motor magnetization.

P0347[3] Demagnetization time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 1.000 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 20.000
Defines the de-magnetization time for the connected induction motor. The de-magnetization time is the time that must expire between powering-down the drive (OFF2 or a drive inverter fault/error) and powering-up again. The drive inverter is prevented from being powered-up again within this time interval. The flux in the induction motor is reduced to a low value during this de- magnetization time.
OFF1
OFF2
OFF2 Motor coasts down
Index:
P0347[0] : 1st. Drive data set (DDS) P0347[1] : 2nd. Drive data set (DDS) P0347[2] : 3rd. Drive data set (DDS) Note:
- The de-magnetization time is approximately 250% of the rotor time constant (r0384) in seconds. - The pre-assignment (default value) depends on the drive inverter type and its rated/nominal values. - It is not active after a normal ramp-down - i.e. after OFF1 or OFF3. - If this time is excessively shortened, then the drive inverter will be tripped (shut down) due to an overcurrent condition. - If a synchronous motor is connected, the de-magnetization time should be set to 0. P0350[3] Stator resistance (line-to-line) Min: 0.00001 CStat: CUT Datatype: Float Unit: Ohm Def: 4.00000 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 2000.00000
Stator resistance value in [Ohms] for connected motor (from line-to-line). The parameter value includes the cable resistance.
) R R ( 2 0350 P S Cable + ⋅ =
There are three ways to determine the value for this parameter: 1. Calculate using - P0340 = 1 (data entered from rating plate) or - P0010 = 1, P3900 = 1,2 or 3 (end of quick commissioning). 2. Measure using P1910 = 1 (motor data identification - value for stator resistance is overwritten). 3. Measure manually using an Ohmmeter. Index:
P0350[0] : 1st. Drive data set (DDS) P0350[1] : 2nd. Drive data set (DDS) P0350[2] : 3rd. Drive data set (DDS) Note:
- Since measured line-to-line, this value may appear to be higher (up to 2 times higher) than expected. - The value entered in P0350 (stator resistance) is the one obtained by the method last used. - Default value is depending on inverter type and its rating data.

P0352[3] Cable resistance Min: 0.0 CStat: CUT Datatype: Float Unit: Ohm Def: 0.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 120.0
Describes cable resistance between inverter and motor for one phase.
l R ⋅ ρ =
: Specific resistance ρ
⋅ Ω = ρ
Index:
P0352[0] : 1st. Drive data set (DDS) P0352[1] : 2nd. Drive data set (DDS) P0352[2] : 3rd. Drive data set (DDS) P0354[3] Rotor resistance Min: 0.0 CStat: CUT Datatype: Float Unit: Ohm Def: 10.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 300.0
Sets rotor resistance of motor equivalent circuit (phase value). Index:
P0354[0] : 1st. Drive data set (DDS) P0354[1] : 2nd. Drive data set (DDS) P0354[2] : 3rd. Drive data set (DDS) Dependency:
Calculated automatically using the motor model or determined using P1910 (motor identification). P0356[3] Stator leakage inductance Min: 0.00001 CStat: CUT Datatype: Float Unit: - Def: 10.00000 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 1000.00000
Sets stator leakage inductance [mH] of motor equivalent circuit (phase value).
Stator leakage reactance:
1000 0356 P 0310 P 2 L f 2 L X S S S ⋅ ⋅ π ⋅ = ⋅ ⋅ π ⋅ = ⋅ ω = σ σ σ
Index:
P0356[0] : 1st. Drive data set (DDS) P0356[1] : 2nd. Drive data set (DDS) P0356[2] : 3rd. Drive data set (DDS) Dependency:
Calculated automatically using the motor model or determined using P1910 (motor identification). P0358[3] Rotor leakage inductance Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 10.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 1000.0
Sets rotor leakage inductance [mH] of motor equivalent circuit (phase value).
Rotor leakage reactance:
1000 0358 P 0310 P 2 L f 2 L X R R R ⋅ ⋅ π ⋅ = ⋅ ⋅ π ⋅ = ⋅ ω = σ σ σ
Index:
P0358[0] : 1st. Drive data set (DDS) P0358[1] : 2nd. Drive data set (DDS) P0358[2] : 3rd. Drive data set (DDS) Dependency:
Calculated automatically using the motor model or determined using P1910 (motor identification).

P0360[3] Main inductance Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 10.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 3000.0
Sets main inductance [mH] of the motor equivalent circuit (phase value), see diagram below.
Main reactance:
1000 0360 P 0310 P 2 L f 2 L X m m m ⋅ ⋅ π ⋅ = ⋅ ⋅ π ⋅ = ⋅ ω =
Index:
P0360[0] : 1st. Drive data set (DDS) P0360[1] : 2nd. Drive data set (DDS) P0360[2] : 3rd. Drive data set (DDS) Dependency:
Calculated automatically using the motor model or determined using P1910 (motor identification). Caution:
The data of equivalent circuit relates to the star equivalent circuit. Any data of the delta equivalent circuit available, therefore must be transformed to the star equivalent circuit before entering into the inverter. Note:
T-equivalent circuit :
Stator res. (L2L) 0.00001 ... 2000.00000 [Ohm] P0350.D (4.00000)
Rotor leak.induct.
0.0 ... 1000.0 P0358.D (10.0)
0.0 ... 20.0 [V] P1825 (1.4)
0.00 ... 3.50 [us] P1828 (0.50)
Cable resistance 0.0 ... 120.0 [Ohm] P0352.D (0.0)
Stator leak.induct 0.00001 ... 1000.00000 P0356.D (10.00000)
Rotor resistance 0.0 ... 300.0 [Ohm] P0354.D (10.0)
iS iR
R S
R R
Lm Main inductance
LR = LσR + Lm LS = LσS + Lm
Invers - Γ -
equivalent circuit :
Cable res. [%]
Stator res. [%]
Tot.leak.react. [%]
Rotor res. [%]
r0372.D
r0370.D
r0377.D
r0374.D
iS iRΓ
RS Xσ
iµΓ (r0331)
r0382.D
![Page 62 of the Siemens 440 user manual — Φ [%]](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-62.webp?w=400)
equivalent circuit Invers - Γ -
L L 1 k
σ σ + =
R
R R 2 R
R R
k L L L
σ σ σ + =
R
Conversion:
T-equivalent curcuit equivalent circuit --> Invers - Γ -
L ) k 1 ( 1 k
σ σ Γ σ ⋅ + = ⋅ − + =
Γ
2 σΓ RΓ R ⋅ =
L 5 . 0 L k L S σ ⋅ = ⋅ =
k L 5 . 0 k L ) k 1 ( L R Γ σ σ Γ σ ⋅ ⋅ = ⋅ ⋅ − =
Rated motor impedance:
N
P0362[3] Magnetizing curve flux 1 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 60.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 300.0
Specifies first flux value of saturation characteristic in [%] relative to rated motor voltage (P0304). The parameter settings for the values of P0362 to P0365 respectively P0366 to P0369 are illustrated in the diagram below.
100 % P0364 P0365
[A] i [%] i
0 P0366 P0367 100 % P0368 P0369 iµ [%]
Index:
P0362[0] : 1st. Drive data set (DDS) P0362[1] : 2nd. Drive data set (DDS) P0362[2] : 3rd. Drive data set (DDS) Note:
- P0362 = 100 % corresponds to rated motor flux - Rated flux = rated EMF - The value belongs to the first magnetizing current value and must be smaller than or equal to magnetizing curve flux 2 (P0363). - If the magnetization values entered in P0362 to P0365 respectively P0366 to P0369 do not match the conditions (see below), a linear characteristic is applied internally.
P0365 ≥ P0364 ≥ P0363 ≥ P0362 P0369 ≥ P0368 ≥ P0367 ≥ P0366 P0363[3] Magnetizing curve flux 2 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 85.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 300.0
Specifies second flux value of saturation characteristic in [%] relative to rated motor voltage (P0304). Index:
P0363[0] : 1st. Drive data set (DDS) P0363[1] : 2nd. Drive data set (DDS) P0363[2] : 3rd. Drive data set (DDS) Details:
See P0362 (magnetizing curve flux 1).

P0364[3] Magnetizing curve flux 3 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 115.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 300.0
Specifies third flux value of saturation characteristic in [%] relative to rated motor voltage (P0304). Index:
P0364[0] : 1st. Drive data set (DDS) P0364[1] : 2nd. Drive data set (DDS) P0364[2] : 3rd. Drive data set (DDS) Details:
See P0362 (magnetizing curve flux 1). P0365[3] Magnetizing curve flux 4 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 125.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 300.0
Specifies fourth flux value of saturation characteristic in [%] relative to rated motor voltage (P0304). Index:
P0365[0] : 1st. Drive data set (DDS) P0365[1] : 2nd. Drive data set (DDS) P0365[2] : 3rd. Drive data set (DDS) Details:
See P0362 (magnetizing curve flux 1). P0366[3] Magnetizing curve imag 1 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 50.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 500.0
Specifies first magnetizing current value of the saturation characteristic in [%] relative to the rated magnetizing current (P0331). Index:
P0366[0] : 1st. Drive data set (DDS) P0366[1] : 2nd. Drive data set (DDS) P0366[2] : 3rd. Drive data set (DDS) Dependency:
Affects P0320 (motor magnetizing current). Details:
See P0362 (magnetizing curve flux 1). P0367[3] Magnetizing curve imag 2 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 75.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 500.0
Specifies second magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current (P0331). Index:
P0367[0] : 1st. Drive data set (DDS) P0367[1] : 2nd. Drive data set (DDS) P0367[2] : 3rd. Drive data set (DDS) Dependency:
Affects P0320 (motor magnetizing current). Details:
See P0362 (magnetizing curve flux 1). P0368[3] Magnetizing curve imag 3 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 135.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 500.0
Specifies third magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current (P0331). Index:
P0368[0] : 1st. Drive data set (DDS) P0368[1] : 2nd. Drive data set (DDS) P0368[2] : 3rd. Drive data set (DDS) Dependency:
Affects P0320 (motor magnetizing current). Details:
See P0362 (magnetizing curve flux 1).

P0369[3] Magnetizing curve imag 4 Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 170.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 500.0
Specifies fourth magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current (P0331). Index:
P0369[0] : 1st. Drive data set (DDS) P0369[1] : 2nd. Drive data set (DDS) P0369[2] : 3rd. Drive data set (DDS) Dependency:
Affects P0320 (motor magnetizing current). Details:
See P0362 (magnetizing curve flux 1). r0370[3] Stator resistance [%] Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays standardized stator resistance of motor equivalent circuit (phase value) in [%] of the temperature value in P0625. Index:
r0370[0] : 1st. Drive data set (DDS) r0370[1] : 2nd. Drive data set (DDS) r0370[2] : 3rd. Drive data set (DDS) Note:
Rated motor impedance:
N
N
Displays standardized cable resistance of motor equivalent circuit (phase value)in [%]. It is estimated to be 20 % of the stator resistance. Index:
r0372[0] : 1st. Drive data set (DDS) r0372[1] : 2nd. Drive data set (DDS) r0372[2] : 3rd. Drive data set (DDS) Note:
Rated motor impedance:
N
N
r0373[3] Rated stator resistance [%] Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays the nominal stator resistance of the motor equivalent circuit diagram (phase value) as a [%] at the ambient temperature + temperature rise of the stator winding. Index:
r0373[0] : 1st. Drive data set (DDS) r0373[1] : 2nd. Drive data set (DDS) r0373[2] : 3rd. Drive data set (DDS) Note:
- ambient temperature, refer to P0625 - temperature rise of the stator winding, refer to P0627
Rated motor impedance:
N
N

Displays the rotor resistance of the motor equivalent circuit diagram (phase value) as a [%] at the ambient temperature (in the cold state).
⋅ = ⋅ ⋅ = ⋅ =
P0360 P0354 % 100 Z k
R % 100 Z R 0374 r 2 N
Γ
R
% 100 P0358) (1 Z
N 2 R
N
Index:
r0374[0] : 1st. Drive data set (DDS) r0374[1] : 2nd. Drive data set (DDS) r0374[2] : 3rd. Drive data set (DDS) Note:
Ambient temperature, refer to P0625
Rated motor impedance:
N
r0376[3] Rated rotor resistance [%] Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays the nominal rotor resistance of the motor equivalent circuit diagram (phase value) as a [%] at the ambient temperature + temperature rise of the rotor winding. Index:
r0376[0] : 1st. Drive data set (DDS) r0376[1] : 2nd. Drive data set (DDS) r0376[2] : 3rd. Drive data set (DDS) Note:
- ambient temperature, refer to P0625 - temperature rise of the rotor winding, refer to P0628
Rated motor impedance:
N
N
r0377[3] Total leakage reactance [%] Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays standardized total leakage reactance of the motor equivalent circuit (phase value) in [%].
k L L % 100 Z L 0377 r
⋅ + = ⋅ + = ⋅ = σ
P0360 P0358 P0356 % 100 Z
R
P0360 P0358
% 100 Z
Index:
N N
r0377[0] : 1st. Drive data set (DDS) r0377[1] : 2nd. Drive data set (DDS) r0377[2] : 3rd. Drive data set (DDS) Note:
Rated motor impedance:
N
N
Displays standardized main reactance of the motor equivalent circuit (phase value) in [%].
L % 100 Z L 0382 r
P0360 % 100 Z k
m ⋅ + = ⋅ ⋅ = ⋅ =
% 100 P0358) (P0360 Z
Index:
N R
N
r0382[0] : 1st. Drive data set (DDS) r0382[1] : 2nd. Drive data set (DDS) r0382[2] : 3rd. Drive data set (DDS) Note:
Rated motor impedance:
N
N

Displays calculated rotor time constant [ms]. Index:
r0384[0] : 1st. Drive data set (DDS) r0384[1] : 2nd. Drive data set (DDS) r0384[2] : 3rd. Drive data set (DDS) r0386[3] Total leakage time constant Min: - Datatype: Float Unit: ms Def: - P-Group: MOTOR Max: -
Displays total leakage time constant of motor. Index:
r0386[0] : 1st. Drive data set (DDS) r0386[1] : 2nd. Drive data set (DDS) r0386[2] : 3rd. Drive data set (DDS) r0394 CO: Stator resistance IGBT [%] Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays stator resistance calculated in [%] from IGBT ON voltage and current amplitude. Note:
Rated motor impedance:
N
N
r0395 CO: Total stator resistance [%] Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays the actual stator resistance (combined stator/cable resistance) of the motor as a [%] as a function of the actual stator winding temperature. Note:
Actual stator winding temperature, refer to r0632
Rated motor impedance:
N
N
r0396 CO: Act. rotor resistance Min: - Datatype: Float Unit: % Def: - P-Group: MOTOR Max: -
Displays the actual rotor resistance of the motor equivalent circuit diagram (phase value) as a [%] as a function of the actual rotor winding temperature. Note:
- Actual rotor winding temperature, refer to r0633 - Values greater than 25 % tend to produce excessive motor slip. Check rated motor speed [rpm] value (P0311).
Rated motor impedance:
N
N

P0400[3] Select encoder type Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ENCODER Active: Immediately QuickComm.: No Max: 2
Selects encoder type (number of encoder channels). Possible Settings:
0 Disabled 1 Single channel encoder 2 Quadrature encoder without zero pulse Index:
P0400[0] : 1st. Drive data set (DDS) P0400[1] : 2nd. Drive data set (DDS) P0400[2] : 3rd. Drive data set (DDS) Dependency:
Following table displays the setting of P0400 which depends upon the number of encoder channels:
Parameter Terminal Track Encoder output
single ended P0400 = 1 A
P0400 = 2 single ended
B
A
AN
B
BN
Following table displays the setting the of the encoder DIPs on the encoder option modul which have to be set depending on the encoder type (TTL, HTL) and encoder output:

(e.g.
HTL
(e.g. 1XP8001-1)
When using Vector Control with encoder-feedback , the direction of rotation of the Encoder and Motor must be the same. If this is not achieved, then the functional operation of the Vector Control will not be guaranteed (positive instead of negative feedback). Extreme care must therefore be taken with respect to the connection of the motor to the inverter as well as the correct connection of the encoder to the Encoder module. Motor and Encoder must not be incorrectly wired up ! When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in - sign and - magnitude (with a deviation of only a few percent). Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23). P0400 = 1 (single channel encoder) will only allow operation in one direction. If operation in both directions is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating Instructions of the encoder module for more information. Note:
Encoders with zero pulse can also be connected, but the zero pulse is not used in MM4. The term "quadrature" in setting 2 refers to two periodic functions separated by a quarter cycle or 90 degrees.

r0403 CO/BO: Encoder status word Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays status word of encoder (in bit format). Bitfields:
Bit00 Encoder module active 0 NO 1 YES Bit01 Encoder error 0 NO 1 YES Bit02 Signal o.k. 0 NO 1 YES Bit03 Encoder low speed loss 0 NO 1 YES Bit04 HW timer used 0 NO 1 YES Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System Parameters" in this manual. P0408[3] Encoder pulses per revolution Min: 2 CStat: CT Datatype: U16 Unit: - Def: 1024 P-Group: ENCODER Active: Immediately QuickComm.: No Max: 20000
Specifies the number of encoder pulses per revolution. Index:
P0408[0] : 1st. Drive data set (DDS) P0408[1] : 2nd. Drive data set (DDS) P0408[2] : 3rd. Drive data set (DDS) Note:
The encoder resolution (pulses per revolution P0408) which may be entered will be limited by the max. pulse frequency of the encoder option board (f_max = 300 kHz). The following equation calculates the encoder frequency depending on the encoder resoulution and the rotational speed (rpm). The encoder frequency has to be less than the max. pulse frequency:
p0408 x rpm fmax > f = 60 P0491[3] Reaction on freq. signal loss Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ENCODER Active: first confirm QuickComm.: No Max: 1
Selects reaction on loss of frequency signal. Possible Settings:
0 Do not change to SLVC 1 Change to SLVC Index:
P0491[0] : 1st. Drive data set (DDS) P0491[1] : 2nd. Drive data set (DDS) P0491[2] : 3rd. Drive data set (DDS) P0492[3] Allowed frequency difference Min: 0.00 CStat: CT Datatype: Float Unit: Hz Def: 10.00 P-Group: ENCODER Active: Immediately QuickComm.: No Max: 100.00
Parameter P0492 is used for low and high frequency encoder loss detection (fault: F0090). 1. High frequency encoder loss detection: This condition occurs when the allowed frequency and the allowed difference of the frequency signals between samples, set in P0492 is exceeded. Condition: - Act. freq. > P0492 and f(t_2) - f(t_1) > P0492 2. Low frequency encoder loss detection: This condition occurs when the actual frequency is < P0492 when encoder loss occurs. Condition a): - r0061 = 0 and torque limit and then - r0061 = 0 with setpoint frequency > 0 for time > P0494 or Condition b): - Act. freq. < P0492 and f (t_2) < P0492 and ASIC detect channel B loss Dependency:
This parameter is updated when motor start-up time P0345 is changed or when a frequency-loop optimisation is performed (P1960 = 1). There is a fixed delay of 40 ms before acting upon loss of encoder at high frequencies. Caution:
P0492 = 0 (disabled): When allowed frequency difference is set to 0, both the high frequency and low frequency encoder loss detection is disabled, thus encoder loss will not be detected. If encoder loss detection is disabled and encoder loss occurs, then operation of the motor may become unstable.

The value of P0492 should be approx. 2x rated slip, if the motor power is less () 90 kW P0494[3] Delay frequency loss reaction Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ENCODER Active: first confirm QuickComm.: No Max: 65000
Used for low frequency encoder loss detection. If the motor shaft frequency is less than the value in P0492 then encoder loss is detected using a low frequency encoder loss detection algorithm. This parameter selects the delay between loss of encoder at low frequency and reaction to the encoder loss. Index:
P0494[0] : 1st. Drive data set (DDS) P0494[1] : 2nd. Drive data set (DDS) P0494[2] : 3rd. Drive data set (DDS) Dependency:
This parameter is updated when motor start-up time P0345 is changed or when a frequency-loop optimisation is performed (P1960 = 1). Caution:
P0494 = 0 (disabled): When the delay in P0494 is set to 0, then low frequency encoder loss detection is disabled and low frequency encoder loss cannot be detected (high frequency encoder loss detection will still operate if P0492 > 0). If low frequency encoder loss detection is disabled and encoder should be lost at low frequency, then operation of motor may become unstable.
P0500[3] Technological application Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: TECH_APL Active: first confirm QuickComm.: Yes Max: 3
Selects technological application. Sets control mode (P1300). Possible Settings:
0 Constant torque 1 Pumps and fans 3 Simple Positioning Index:
P0500[0] : 1st. Drive data set (DDS) P0500[1] : 2nd. Drive data set (DDS) P0500[2] : 3rd. Drive data set (DDS) Dependency:
P0601[3] Motor temperature sensor Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: No Max: 2
Selects motor temperature sensor. Possible Settings:
0 No sensor 1 PTC thermistor 2 KTY84 Index:
P0601[0] : 1st. Drive data set (DDS) P0601[1] : 2nd. Drive data set (DDS) P0601[2] : 3rd. Drive data set (DDS) Dependency:
If "no sensor" is selected, the motor temperature monitoring will be done based on the estimated value of the thermal motor model. The temperature of the motor, when a thermal sensor is connected is calculated using the thermal motor model. When a KTY sensor is fitted, the loss of connection can be detected (Alarm F0015). Using the methods described above the monitoring of the temperature will automatically switch to the thermal model using values derived from the estimated value. Using a PTC sensor the temperature of the motor is calculated by the sensor in conjunction with the thermal model. This allows for redundancy of the monitoring process.
See parameter P0205

T1 = 4 s
No sensor PTC KTY
Motor temp. reaction
PV,mot Power dissipation
Thermal motor model: The data, required for the thermal motor model, is estimated from the rating plate data entered during the quick commissioning. This data permits reliable, stable operation for standard Siemens motors. If required, parameter changes must be made for motors from third-party manufacturers. We always recommend that an automatic motor data identification run is made after quick commissioning so that the electrical equivalent circuit diagram data can be determined. This allows a more precise calculation of the losses which occur in the motor which has a positive impact on the accuracy of the thermal motor model. PTC sensor: A PTC temperature sensor (Positive-Temperature-Characteristic) is a resistor with a positive temperature characteristic which, at normal temperatures, has a low resistance value ( 50-100 Ohm). Normally, three PTC temperature sensors are connected in series in the motor (depending on the motor manufacturer), thus producing a "cold resistance value" ranging from 150 to 300 Ohm. PTC temperature sensors are also frequently referred to as cold conductors. However, at a certain threshold temperature, the resistance rises rapidly. The threshold temperature is selected by the motor manufacturer in such a way that it corresponds to the nominal temperature value of the motor insulation. This allows the change in the resistance value to be deployed to protect the motor, as the PTCs are embedded in the motor windings. PTC temperature sensors are not suitable for measuring temperature. When the PTC is connected to the control terminals 14 and 15 of the MM4 and the selection motor temperature sensor has been activated by the setting P0601 = 1 (PTC sensor), the PTC temperature sensor then protects the motor by means of the trip device in the MM4. Should the resistance value of 2000 Ohm be exceeded, the inverter displays error F0011 (motor overheating). If the resistance value is below 100 Ohm, the error F0015 (no motor temperature signal) is then output. This protects the motor from overheating and also from a sensor wire breakage. The motor is additionally monitored by the thermal motor model in the inverter, thus providing a redundant system for monitoring the motor. KTY84 sensor: The sensor KTY84 is basically a semi-conductor thermo-sensor (diode), the resistance value of which varies from some 500 Ohm at 0°C to 2600 Ohm at 300°C. It has a positive temperature coefficient and, in contrast to the PTCs, has an almost linear temperature characteristic. The resistor behaviour is comparable to that of a measuring resistor with a very high temperature coefficient. Note the following when connecting the polarity. Connect the sensor so that the diode is polarized in the operative direction. That means that the anode needs to be connected to terminal 14 = PTC A (+) and the cathode to terminal 15 = PTC B (-). If the temperature monitoring function is activated with the setting P0601 = 2, the temperature of the sensor (thus that of the motor windings) is then written to parameter r0035. The motor overheating warning threshold needs to be assigned with parameter P0604 (the works setting is 130°C). This warning threshold depends on the motors thermal class. Also refer to the table below in this context.

Extract of IEC 85
End temperature Insulation class
90 °C
A
105 °C
E
120 °C
B
130 °C
F
155 °C
H 180 °C
The motor overheating disturbance threshold is automatically set by the inverter at 10% higher than the temperature declared in parameter P0604. If the sensor KTY84 is activated, the motor temperature is then additionally calculated via the thermal motor model. Should the sensor KTY84 recognise a wire breakage, an alarm F0015 (loss of the motor temperature signal) is then generated and the thermal motor model is automatically switched to. Connection failure: If the connection to the PTC or KTY84 sensor becomes open circuit or short circuit, a fault will be indicated, and by default the drive will trip. P0604[3] Threshold motor temperature Min: 0.0 CStat: CUT Datatype: Float Unit: °C Def: 130.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 200.0
Enters warning threshold for motor temperature protection. The trip temperature defined always 10 % higher than the warning level P0604. When act. motor temperature exeeds trip temperature than inverter trip as defined in P0610.
P0604 1.1 1.1 warn trip ⋅ = ⋅ = ϑ ϑ Warning threshold (P0604)
ϑwarn :
Index:
P0604[0] : 1st. Drive data set (DDS) P0604[1] : 2nd. Drive data set (DDS) P0604[2] : 3rd. Drive data set (DDS) Dependency:
This value should be at least 40°C greater than the motor ambient temperature P0625.
P0604 ≥ P0625 + 40 °C Note:
Default value depends on P0300 (select motor type). P0610[3] Motor temperature reaction Min: 0 CStat: CT Datatype: U16 Unit: - Def: 2 P-Group: MOTOR Active: first confirm QuickComm.: No Max: 2
Defines reaction when motor temperature reaches warning threshold. Possible Settings:
0 Warning, no reaction, no trip 1 Warning, Imax reduction, trip F0011 2 Warning, no reaction, trip F0011 Index:
P0610[0] : 1st. Drive data set (DDS) P0610[1] : 2nd. Drive data set (DDS) P0610[2] : 3rd. Drive data set (DDS) Dependency:
P0604 1.1 1.1 warn trip ⋅ = ⋅ = ϑ ϑ Warning threshold (P0604)
ϑwarn :
P0610 = 1: If the max. permissible current Imax is reduced, this results in a lower output frequency. The motor temperature depends on many factors. These factors include the size of the motor, the ambient temperature, the previous motor load and naturally the load current. Because most motors are cooled by fans integrated in the motor and running at the motor speed, the speed of the motor is also important. Clearly a motor running with a high current (maybe due to boost) and a low speed, will overheat more quickly than one running at 50 or 60 Hz, full load. The MM4 take account of these factors.

P0625[3] Ambient motor temperature Min: -40.0 CStat: CUT Datatype: Float Unit: °C Def: 20.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 80.0
Ambient temperature of motor. The parameter for the stator resistance P0350 and rotor resistance P0354 relate to the ambient temperature.
P0304 P0305 P0307
P0310 P0311
P1910 Index:
P0625[0] : 1st. Drive data set (DDS) P0625[1] : 2nd. Drive data set (DDS) P0625[2] : 3rd. Drive data set (DDS) Note:
Following items should be considered when using P0625: - The ambient temperature has to be entered prior to motor data identification. - An accuracy of +/- 5°C is adequate. - The motor data identification should be carried out on a cold motor (ambient temperature = stator temperature = rotor temperature). - The highest accuracy at temperature adaption of the stator resistance and rotor resistance can be achieved by connecting a KTY84 sensor. P0626[3] Overtemperature stator iron Min: 20.0 CStat: CUT Datatype: Float Unit: °C Def: 50.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 200.0
Overtemperature of stator iron. Index:
P0626[0] : 1st. Drive data set (DDS) P0626[1] : 2nd. Drive data set (DDS) P0626[2] : 3rd. Drive data set (DDS) Note:

P0627[3] Overtemperature stator winding Min: 20.0 CStat: CUT Datatype: Float Unit: °C Def: 80.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 200.0
Overtemperature of the stator winding. Index:
P0627[0] : 1st. Drive data set (DDS) P0627[1] : 2nd. Drive data set (DDS) P0627[2] : 3rd. Drive data set (DDS) Note:
Temperature rise: The losses occurring in the motor are converted into heat (thermal energy). This is the reason that permissible limit temperature rises are defined for windings and other mechanical parts and components of the motors. The temperature rise of the motor is defined as the difference between the temperature of a motor component (e.g. rotor winding) and the temperature of the cooling medium (e.g. ambient air temperature) (EN 60034-1). The temperature rise determined by the motor manufacturer by making the appropriate measurements is the difference between the temperature of the winding at the end of the measurement and the temperature of the cooling medium.
ϑ ϑ ϑ − = K 2 ü ϑü ϑ2 ϑK The permissible temperature rises of the windings is classified in insulating classes. The insulating class valid for the particular motor is specified on the motor rating plate. The following points should be carefully observed: - The temperature rises of the stator/rotor winding are only applicable for sinusoidal operation (basic fundamental). - The temperature of stator/rotor winding rises when the motor is fed with a sinusoidal voltage as well as also losses (modulation losses, losses due to harmonics) caused as a result of drive converter operation. - The value may only be modified if the motor is in the cold condition (ambient temperature). The motor identification run should be carried-out after the value has been changed. P0628[3] Overtemperature rotor winding Min: 20.0 CStat: CUT Datatype: Float Unit: °C Def: 100.0 P-Group: MOTOR Active: Immediately QuickComm.: No Max: 200.0
: Temperature rise : Temperature at the end of the measurement : Cooling-medium temperature
Overtemperature of the rotor winding. Index:
P0628[0] : 1st. Drive data set (DDS) P0628[1] : 2nd. Drive data set (DDS) P0628[2] : 3rd. Drive data set (DDS) Note:
Displays ambient temperature of motor mass model. Index:
r0630[0] : 1st. Drive data set (DDS) r0630[1] : 2nd. Drive data set (DDS) r0630[2] : 3rd. Drive data set (DDS) r0631[3] CO: Stator iron temperature Min: - Datatype: Float Unit: °C Def: - P-Group: MOTOR Max: -
Displays iron temperature of motor mass model. Index:
r0631[0] : 1st. Drive data set (DDS) r0631[1] : 2nd. Drive data set (DDS) r0631[2] : 3rd. Drive data set (DDS) r0632[3] CO: Stator winding temperature Min: - Datatype: Float Unit: °C Def: - P-Group: MOTOR Max: -
Displays stator winding temperature of motor mass model. Index:
r0632[0] : 1st. Drive data set (DDS) r0632[1] : 2nd. Drive data set (DDS) r0632[2] : 3rd. Drive data set (DDS)

r0633[3] CO: Rotor winding temperature Min: - Datatype: Float Unit: °C Def: - P-Group: MOTOR Max: -
Displays rotor winding temperature of motor mass model. Index:
r0633[0] : 1st. Drive data set (DDS) r0633[1] : 2nd. Drive data set (DDS) r0633[2] : 3rd. Drive data set (DDS) P0640[3] Motor overload factor [%] Min: 10.0 CStat: CUT Datatype: Float Unit: % Def: 150.0 P-Group: MOTOR Active: Immediately QuickComm.: Yes Max: 400.0
Defines motor overload current limit in [%] relative to P0305 (rated motor current). Index:
P0640[0] : 1st. Drive data set (DDS) P0640[1] : 2nd. Drive data set (DDS) P0640[2] : 3rd. Drive data set (DDS) Dependency:
Limited to maximum inverter current or to 400 % of rated motor current (P0305), whichever is the lower.
P0305) 4 (r0209, min P0640max ⋅ ⋅ =
Details:
See function diagram for current limitation.

P0700[3] Selection of command source Min: 0 CStat: CT Datatype: U16 Unit: - Def: 2 P-Group: COMMANDS Active: first confirm QuickComm.: Yes Max: 6
Selects digital command source. Possible Settings:
0 Factory default setting 1 BOP (keypad) 2 Terminal 4 USS on BOP link 5 USS on COM link 6 CB on COM link Index:
P0700[0] : 1st. Command data set (CDS) P0700[1] : 2nd. Command data set (CDS) P0700[2] : 3rd. Command data set (CDS) Example:
Changing form P0700 = 1 to P0700 = 2 sets all digital inputs to default settings.

Be aware, by changing of parameter P0700 all BI parameters are reset to the default value or modified as listed in the table below. If the Inverter is being controlled via the AOP, select USS (with the corresponding interface) for the Command Source. If the AOP is connected to the BOP-Link Interface, then set Parameter P0700 to the value 4 (P0700 = 4). Note:
Changing this parameter sets (to default) all settings on item selected (see table).

P0700 = 0 P0700 = 1 P0700 = 2 P0700 = 4 P0700 = 5 P0700 = 6
P0733 0.0 P0800 0.0


P0852 1.0 1.0 1.0 2032.3 2036.3 2090.3 P0700 = 0 P0700 = 1 P0700 = 2 P0700 = 4 P0700 = 5 P0700 = 6
P1230 0.0 P1477 0.0
P2106 1.0 P2200 0.0
The following parameters are not overwritten when changing P0700:
P2816 P2818 P2820 P2822 P2824 P2826 P2828
P2830 P2832 P2834 P2837 P2840 P2843 P2846
P2849 P2854 P2859 P2864

P0701[3] Function of digital input 1 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 1.
DIN channel (e.g. DIN1 - PNP (P0725 = 1))
Kl.9 P24 (PNP) Kl.28 0 V (NPN)
Pxxxx BI : ...
Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 17 Fixed setpoint (Binary coded selection + ON) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0701[0] : 1st. Command data set (CDS) P0701[1] : 2nd. Command data set (CDS) P0701[2] : 3rd. Command data set (CDS) Dependency:
Setting 99 (enable BICO parameterization) requires - P0700 command source or - P0010 = 1, P3900 = 1, 2 or 3 quick commissioning or - P0010 = 30, P0970 = 1 factory reset in order to reset. Notice:
Setting 99 (BICO) for expert use only.
Function 0 · r0722 r0722

P0702[3] Function of digital input 2 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 12 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 2. Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 17 Fixed setpoint (Binary coded selection + ON) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0702[0] : 1st. Command data set (CDS) P0702[1] : 2nd. Command data set (CDS) P0702[2] : 3rd. Command data set (CDS) Details:
See P0701 (function of digital input1). P0703[3] Function of digital input 3 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 9 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 3. Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 17 Fixed setpoint (Binary coded selection + ON) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0703[0] : 1st. Command data set (CDS) P0703[1] : 2nd. Command data set (CDS) P0703[2] : 3rd. Command data set (CDS) Details:
See P0701 (function of digital input 1).

P0704[3] Function of digital input 4 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 15 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 4. Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 17 Fixed setpoint (Binary coded selection + ON) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0704[0] : 1st. Command data set (CDS) P0704[1] : 2nd. Command data set (CDS) P0704[2] : 3rd. Command data set (CDS) Details:
See P0701 (function of digital input 1). P0705[3] Function of digital input 5 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 15 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 5. Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0705[0] : 1st. Command data set (CDS) P0705[1] : 2nd. Command data set (CDS) P0705[2] : 3rd. Command data set (CDS) Details:
See P0701 (function of digital input 1).

P0706[3] Function of digital input 6 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 15 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 6. Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0706[0] : 1st. Command data set (CDS) P0706[1] : 2nd. Command data set (CDS) P0706[2] : 3rd. Command data set (CDS) Details:
See P0701 (function of digital input 1). P0707[3] Function of digital input 7 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 7 (via analog input). Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0707[0] : 1st. Command data set (CDS) P0707[1] : 2nd. Command data set (CDS) P0707[2] : 3rd. Command data set (CDS) Note:
Signals above 4 V are active, signals below 1,6 V are inactive. Details:
See P0701 (function of digital input 1).

P0708[3] Function of digital input 8 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 8 (via analog input) Possible Settings:
0 Digital input disabled 1 ON/OFF1 2 ON reverse /OFF1 3 OFF2 - coast to standstill 4 OFF3 - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization Index:
P0708[0] : 1st. Command data set (CDS) P0708[1] : 2nd. Command data set (CDS) P0708[2] : 3rd. Command data set (CDS) Note:
Signals above 4 V are active, signals below 1,6 V are inactive. Details:
See P0701 (function of digital input 1). P0719[3] Selection of cmd. & freq. setp. Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 67
Central switch to select control command source for inverter. Switches command and setpoint source between freely programmable BICO parameters and fixed command/setpoint profiles. Command and setpoint sources can be changed independently. The tens digit chooses the command source and the units digit chooses the setpoint source. Possible Settings:
0 Cmd = BICO parameter Setpoint = BICO parameter 1 Cmd = BICO parameter Setpoint = MOP setpoint 2 Cmd = BICO parameter Setpoint = Analog setpoint 3 Cmd = BICO parameter Setpoint = Fixed frequency 4 Cmd = BICO parameter Setpoint = USS on BOP link 5 Cmd = BICO parameter Setpoint = USS on COM link 6 Cmd = BICO parameter Setpoint = CB on COM link 7 Cmd = BICO parameter Setpoint = Analog 2 setp 10 Cmd = BOP Setpoint = BICO parameter 11 Cmd = BOP Setpoint = MOP setpoint 12 Cmd = BOP Setpoint = Analog setpoint 13 Cmd = BOP Setpoint = Fixed frequency 15 Cmd = BOP Setpoint = USS on COM link 16 Cmd = BOP Setpoint = CB on COM link 17 Cmd = BOP Setpoint = Analog 2 setp 40 Cmd = USS on BOP link Setpoint = BICO parameter 41 Cmd = USS on BOP link Setpoint = MOP setpoint 42 Cmd = USS on BOP link Setpoint = Analog setpoint 43 Cmd = USS on BOP link Setpoint = Fixed frequency 44 Cmd = USS on BOP link Setpoint = USS on BOP link 45 Cmd = USS on BOP link Setpoint = USS on COM link 46 Cmd = USS on BOP link Setpoint = CB on COM link 47 Cmd = USS on BOP link Setpoint = Analog 2 setp 50 Cmd = USS on COM link Setpoint = BICO parameter 51 Cmd = USS on COM link Setpoint = MOP setpoint 52 Cmd = USS on COM link Setpoint = Analog setpoint 53 Cmd = USS on COM link Setpoint = Fixed frequency 54 Cmd = USS on COM link Setpoint = USS on BOP link 55 Cmd = USS on COM link Setpoint = USS on COM link 57 Cmd = USS on COM link Setpoint = Analog 2 setp 60 Cmd = CB on COM link Setpoint = BICO parameter 61 Cmd = CB on COM link Setpoint = MOP setpoint 62 Cmd = CB on COM link Setpoint = Analog setpoint 63 Cmd = CB on COM link Setpoint = Fixed frequency 64 Cmd = CB on COM link Setpoint = USS on BOP link 66 Cmd = CB on COM link Setpoint = CB on COM link 67 Cmd = CB on COM link Setpoint = Analog 2 setp

Index:
P0719[0] : 1st. Command data set (CDS) P0719[1] : 2nd. Command data set (CDS) P0719[2] : 3rd. Command data set (CDS) Note:
Using parameter P0719, it is possible to select the command or setpoint sources without changing the BICO connections (this is contrary to P0700 / P1000). However, it is not possible to change the complete connection table (refer to P0700 and P1000). Using P0719, depending on the value, only the BICO parameters listed in the following table are internally overwritten - this means that these BICO parameters are inactive.
Command source:
40 ... 49 0 ... 9 10 ... 19 50 ... 59 60 ... 69
P0844 X − − − −
P0848 X X − − −
P0852 X X − − −
P1035 X − − − −
P1036 X X − − −
P1055 X − − − −
P1056 X X − − −
P1113 X − − − −
P1140 X X − − −
P1141 X X − − −
P1142 X X − − −
P1143 X X − − −
Setpoint source:
X =
BICO parameter inactive − = BICO connections made previously remain unchanged. r0720 Number of digital inputs Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays number of digital inputs. r0722 CO/BO: Binary input values Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays status of digital inputs. Bitfields:
Bit00 Digital input 1 0 OFF 1 ON Bit01 Digital input 2 0 OFF 1 ON Bit02 Digital input 3 0 OFF 1 ON Bit03 Digital input 4 0 OFF 1 ON Bit04 Digital input 5 0 OFF 1 ON Bit05 Digital input 6 0 OFF 1 ON Bit06 Digital input 7 (via ADC 1) 0 OFF 1 ON Bit07 Digital input 8 (via ADC 2) 0 OFF 1 ON Note:
Segment is lit when signal is active.
all other values · BICO parameter active

P0724 Debounce time for digital inputs Min: 0 CStat: CT Datatype: U16 Unit: - Def: 3 P-Group: COMMANDS Active: Immediately QuickComm.: No Max: 3
Defines debounce time (filtering time) used for digital inputs. Possible Settings:
0 No debounce time 1 2.5 ms debounce time 2 8.2 ms debounce time 3 12.3 ms debounce time P0725 PNP / NPN digital inputs Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: COMMANDS Active: Immediately QuickComm.: No Max: 1
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs simultaneously. The following is valid by using the internal supply: Possible Settings:
0 NPN mode ==> low active 1 PNP mode ==> high active Value:
NPN: Terminals 5/6/7/8/16/17 must be connected via terminal 28 ( O V). PNP: Terminals 5/6/7/8/16/17 must be connected via terminal 9 (24 V).

r0730 Number of digital outputs Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays number of digital outputs (relays). P0731[3] BI: Function of digital output 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 52:3 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of digital output 1.
0 ... 7 P0748 (0) CO/BO: State DOUTs
int. 24 V max. 100 mA
Kl.9
xxxx.y rxxxx.y
Kl.20
(52:3)
P0731 = xxxx.y
Kl.19
Kl.18
Relay :
max. load capability
DC 30 V / 5 A AC 250 V / 2 A
Kl.28
max. opening / closing time
5 / 10 ms Index:
P0731[0] : 1st. Command data set (CDS) P0731[1] : 2nd. Command data set (CDS) P0731[2] : 3rd. Command data set (CDS) Common Settings:
52.0 Drive ready 0 Closed 52.1 Drive ready to run 0 Closed 52.2 Drive running 0 Closed 52.3 Drive fault active 0 Closed 52.4 OFF2 active 1 Closed 52.5 OFF3 active 1 Closed 52.6 Switch on inhibit active 0 Closed 52.7 Drive warning active 0 Closed 52.8 Deviation setpoint/actual value 1 Closed 52.9 PZD control (Process Data Control) 0 Closed 52.A Maximum frequency reached 0 Closed 52.B Warning: Motor current limit 1 Closed 52.C Motor holding brake (MHB) active 0 Closed 52.D Motor overload 1 Closed 52.E Motor running direction right 0 Closed 52.F Inverter overload 1 Closed 53.0 DC brake active 0 Closed 53.1 Act. freq. f_act > P2167 (f_off) 0 Closed 53.2 Act. freq. f_act P2170 0 Closed 53.4 Act. freq. f_act > P2155 (f_1) 0 Closed 53.5 Act. freq. f_act = setpoint 0 Closed 53.7 Act. Vdc r0026 < P2172 0 Closed 53.8 Act. Vdc r0026 > P2172 0 Closed 53.A PID output r2294 == P2292 (PID_min) 0 Closed 53.B PID output r2294 == P2291 (PID_max) 0 Closed Details:
Display functions ==> see parameter r0052, r0053 Motor holding brake ==> see parameter P1215 DC brake ==> see parameter P1232, P1233

P0732[3] BI: Function of digital output 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 52:7 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of digital output 2. Index:
P0732[0] : 1st. Command data set (CDS) P0732[1] : 2nd. Command data set (CDS) P0732[2] : 3rd. Command data set (CDS) Common Settings:
52.0 Drive ready 0 Closed 52.1 Drive ready to run 0 Closed 52.2 Drive running 0 Closed 52.3 Drive fault active 0 Closed 52.4 OFF2 active 1 Closed 52.5 OFF3 active 1 Closed 52.6 Switch on inhibit active 0 Closed 52.7 Drive warning active 0 Closed 52.8 Deviation setpoint/actual value 1 Closed 52.9 PZD control (Process Data Control) 0 Closed 52.A Maximum frequency reached 0 Closed 52.B Warning: Motor current limit 1 Closed 52.C Motor holding brake (MHB) active 0 Closed 52.D Motor overload 1 Closed 52.E Motor running direction right 0 Closed 52.F Inverter overload 1 Closed 53.0 DC brake active 0 Closed 53.1 Act. freq. f_act > P2167 (f_off) 0 Closed 53.2 Act. freq. f_act P2170 0 Closed 53.4 Act. freq. f_act > P2155 (f_1) 0 Closed 53.5 Act. freq. f_act = setpoint 0 Closed 53.7 Act. Vdc r0026 < P2172 0 Closed 53.8 Act. Vdc r0026 > P2172 0 Closed 53.A PID output r2294 == P2292 (PID_min) 0 Closed 53.B PID output r2294 == P2291 (PID_max) 0 Closed P0733[3] BI: Function of digital output 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of digital output 3. Index:
P0733[0] : 1st. Command data set (CDS) P0733[1] : 2nd. Command data set (CDS) P0733[2] : 3rd. Command data set (CDS) Common Settings:
52.0 Drive ready 0 Closed 52.1 Drive ready to run 0 Closed 52.2 Drive running 0 Closed 52.3 Drive fault active 0 Closed 52.4 OFF2 active 1 Closed 52.5 OFF3 active 1 Closed 52.6 Switch on inhibit active 0 Closed 52.7 Drive warning active 0 Closed 52.8 Deviation setpoint/actual value 1 Closed 52.9 PZD control (Process Data Control) 0 Closed 52.A Maximum frequency reached 0 Closed 52.B Warning: Motor current limit 1 Closed 52.C Motor holding brake (MHB) active 0 Closed 52.D Motor overload 1 Closed 52.E Motor running direction right 0 Closed 52.F Inverter overload 1 Closed 53.0 DC brake active 0 Closed 53.1 Act. freq. f_act > P2167 (f_off) 0 Closed 53.2 Act. freq. f_act P2170 0 Closed 53.4 Act. freq. f_act > P2155 (f_1) 0 Closed 53.5 Act. freq. f_act = setpoint 0 Closed 53.7 Act. Vdc r0026 < P2172 0 Closed 53.8 Act. Vdc r0026 > P2172 0 Closed 53.A PID output r2294 == P2292 (PID_min) 0 Closed 53.B PID output r2294 == P2291 (PID_max) 0 Closed

r0747 CO/BO: State of digital outputs Min: - Datatype: U16 Unit: - Def: - P-Group: COMMANDS Max: -
Displays status of digital outputs (also includes inversion of digital outputs via P0748). Bitfields:
Bit00 Digital output 1 energized 0 NO 1 YES Bit01 Digital output 2 energized 0 NO 1 YES Bit02 Digital output 3 energized 0 NO 1 YES Dependency:
Bit 0 = 0 : Relay de-energized / contacts open Bit 0 = 1 : Relay energized / contacts closed P0748 Invert digital outputs Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 7
Defines high and low states of relay for a given function. Bitfields:
Bit00 Invert digital output 1 0 NO 1 YES Bit01 Invert digital output 2 0 NO 1 YES Bit02 Invert digital output 3 0 NO 1 YES
Displays number of analog inputs available. r0751 BO: Status word of ADC Min: - Datatype: U16 Unit: - Def: - P-Group: TERMINAL Max: -
Displays status of analog input. Bitfields:
Bit00 Signal lost on ADC 1 0 NO 1 YES Bit01 Signal lost on ADC 2 0 NO 1 YES Dependency:
The following limitations/secondary conditions apply for the wire breakage monitoring: - For P0756, the monitoring must be activated - Width of the ADC deadzone P0761 > 0 - Wire breakage / signal loss F0080 is detected if the ADC input quantity is less than 0.5 * P0761.
Fault acknowl.
Act. ADC after scaling r0755

r0752[2] Act. input of ADC [V] or [mA] Min: - Datatype: Float Unit: - Def: - P-Group: TERMINAL Max: -
Displays smoothed analog input value in volts before the characteristic block.

Index:
r0752[0] : Analog input 1 (ADC 1) r0752[1] : Analog input 2 (ADC 2) P0753[2] Smooth time ADC Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 3 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 10000
Defines filter time (PT1 filter) in [ms] for analog input. Index:
Increasing this time (smooth) reduces jitter but slows down response to the analog input. P0753 = 0 : No filtering r0754[2] Act. ADC value after scaling [%] Min: - Datatype: Float Unit: % Def: - P-Group: TERMINAL Max: -
Shows smoothed value of analog input in [%] after scaling block. Index:
P0757 to P0760 define range (ADC scaling).
ADC channel

r0755[2] CO: Act. ADC after scal. [4000h] Min: - Datatype: I16 Unit: - Def: - P-Group: TERMINAL Max: -
Displays analog input, scaled using ASPmin and ASPmax. Analog setpoint (ASP) from the analog scaling block can vary from min. analog setpoint (ASPmin) to a max. analog setpoint (ASPmax) as shown in P0757 (ADC scaling). The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384. By associating parameter r0755 with an internal value (e.g. frequency setpoint), a scaled value is calculated internally by the MM4. The frequency value is calculated using the following equation:
r0755 [Hex] r0755 [Hz]
) ASP , ASP ( max 2000 P [Hex] 4000 [Hex] r0755 [Hz] r0755
min max ⋅ ⋅ =
Index:
Case a: - ASPmin = 300 %, ASPmax = 100 % then 16384 represents 300 %. - This parameter will vary from 5461 to 16384. Case b: - ASPmin = -200 %, ASPmax = 100 % then 16384 represents 200 %. - This parameter will vary from -16384 to +8192.
) ASP , ASP max( h 4000 min max =
4000 h 16384 dez
10 V 20 mA
10 V 20 mA
ASPmin -200 %
7FFF h -16383 dez
- This value is used as an input to analog BICO connectors. - ASPmax represents the highest analog setpoint (this may be at 10 V). - ASPmin represents the lowest analog setpoint (this may be at 0 V). Details:
See parameters P0757 to P0760 (ADC scaling) P0756[2] Type of ADC Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 4
Defines type of analog input and also enables analog input monitoring. To switch over from voltage to current analog input it is not sufficient to merely modify parameter P0756. Rather, the DIPs on the terminal board must also be set to the correct position. The DIP settings are as follows: - OFF = voltage input (10 V) - ON = current input (20 mA) Allocation of DIPs to analog inputs is as follows: - DIP on left (DIP 1) = Analog input 1 - DIP on right (DIP 2) = Analog input 2


OFF = [V], 0 - 10 V ON = [A], 0 - 20 mA
ADC2 OFF = [V], 0 - 10 V ON = [A], 0 - 20 mA
Possible Settings:
0 Unipolar voltage input (0 to +10 V) 1 Unipolar voltage input with monitoring (0 to 10 V) 2 Unipolar current input (0 to 20 mA) 3 Unipolar current input with monitoring (0 to 20 mA) 4 Bipolar voltage input (-10 V to +10 V) Index:
When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F0080) if the analog input voltage falls below 50 % of the deadband voltage. On account of h/w restirction it is not possible to select the bipolar voltage (see Enum declaration) for analog input 2 (P0756[1] = 4). Details:
See P0757 to P0760 (ADC scaling). P0757[2] Value x1 of ADC scaling [V / mA] Min: -20 CStat: CUT Datatype: Float Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 20
Parameters P0757 - P0760 configure the input scaling as shown in the diagram:
V mA x100%
10 V 20 mA
Where: - Analog setpoints represent a [%] of the normalized frequency in P2000. - Analog setpoints may be larger than 100 %. - ASPmax represents highest analog setpoint (this may be at 10 V or 20 mA). - ASPmin represents lowest analog setpoint (this may be at 0 V or 20 mA). - Default values provide a scaling of 0 V or 0 mA = 0 %, and 10 V or 20 mA = 100 %.

10 V V x100%
Index:
The ADC-linear characteristic is described by 4 coordinates, based on a two-point equation:
0758 P 0760 P P0757 - x
For calculations the point-gradient form (offset and gradient) is more advantageous:
0 y x m y + ⋅ = The transformation between these two forms is given by:
0758 P 0760 P m − − =
0760 P 0757 P 0759 P 0758 P y0 −
⋅ − ⋅ =
For scaling of the input the value of y_max and x_min has to be determined. This is done by the following equations:
0757 P 0759 P
0759 P 0758 P 0757 P 0760 P x in m −
⋅ − ⋅ =
0758 P 0760 P ) x x ( y min max max − − ⋅ − =
P0757 x1 P0759 x2 Notice:
The value x2 of ADC scaling P0759 must be greater than the value x1 of ADC scaling P0757. P0758[2] Value y1 of ADC scaling Min: -99999.9 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 99999.9
Sets value of Y1 in [%] as described in P0757 (ADC scaling) Index:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.

P0759[2] Value x2 of ADC scaling [V / mA] Min: -20 CStat: CUT Datatype: Float Unit: - Def: 10 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 20
Sets value of X2 as described in P0757 (ADC scaling). Index:
The value x2 of ADC scaling P0759 must be greater than the value x1 of ADC scaling P0757. P0760[2] Value y2 of ADC scaling Min: -99999.9 CStat: CUT Datatype: Float Unit: % Def: 100.0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 99999.9
Sets value of Y2 in [%] as described in P0757 (ADC scaling). Index:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated. P0761[2] Width of ADC deadband [V / mA] Min: 0 CStat: CUT Datatype: Float Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 20
Defines width of deadband on analog input. The diagrams below explain its use. Index:
The below example produces a 2 to 10 V analog input 0 to 50 Hz (ADC value 2 to 10 V, 0 to 50 Hz): - P2000 = 50 Hz - P0759 = 8 V P0760 = 75 % - P0757 = 2 V P0758 = 0 % - P0761 = 2 V - P0756 = 0 or 1
P0761 > 0 and (0 < P0758 < P0760 or 0 > P0758 > P0760)
V mA x100%
10 V 20 mA
P0757 = P0761
P0757 < P0761
The below example produces a 0 to 10 V analog input (-50 to +50 Hz) with center zero and a "holding point" 0.2 V wide (0.1 V to each side of center, ADC value 0 to 10 V, -50 to +50 Hz): - P2000 = 50 Hz - P0759 = 8 V P0760 = 75 % - P0757 = 2 V P0758 = -75 % - P0761 = 0.1 V - P0756 = 0 or 1

P0761 > 0 and P0758 < 0 < P0760
V mA x100%
10 V 20 mA
The below example produces a -10 to +10 V analog input (-50 to +50 Hz) with center zero and a "holding point" 0.2 V wide (0.1 V to each side of center).
P0756 = 4 and P0761 > 0 and P0758 < 0 < P0760
10 V V x100%
P0761[x] = 0 : No deadband active. Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC scaling) are positive or negative respectively. However, deadband is active in both directions from point of intersection (x axis with ADC scaling curve), if sign of P0758 and P0760 are opposite. Min. frequency P1080 should be zero when using center zero setup. There is no hysteresis at the end of the deadband. P0762[2] Delay for loss of signal action Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: TERMINAL Active: Immediately QuickComm.: No Max: 10000
Defines time delay between loss of analog setpoint and appearance of fault code F0080. Index:
Expert users can choose the desired reaction to F0080 (default is OFF2).

Displays number of analog outputs available. P0771[2] CI: DAC Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 21:0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 4000:0
Defines function of the 0 - 20 mA analog output. Index:
21 CO: Act. frequency (scaled to P2000) 24 CO: Act. output frequency (scaled to P2000) 25 CO: Act. output voltage (scaled to P2001) 26 CO: Act. filtered DC-link volt. (scaled to P2001) 27 CO: Act. output current (scaled to P2002)
r0774 P0781 P0773 DAC channel
xxx r0xxx P0771 D
A P0771 = xxx
P0773[2] Smooth time DAC Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 2 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 1000
Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC using a PT1 filter. Index:
P0773 = 0: Deactivates filter. r0774[2] Act. DAC value [mA] Min: - Datatype: Float Unit: - Def: - P-Group: TERMINAL Max: -
Shows value of analog output in [mA] after filtering and scaling. Index:
r0774[0] : Analog output 1 (DAC 1) r0774[1] : Analog output 2 (DAC 2) P0775[2] Permit absolute value Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 1
Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute value of the value to be outputed. If the value was originally negative then the corresponding bit in R0783 is set, otherwise it is cleared. Possible Settings:
0 OFF 1 ON Index:
DAC dead zone · Function · DAC scaling

P0776[2] Type of DAC Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 1
Defines type of analog output. Possible Settings:
0 Current output 1 Voltage output Index:
The analog output is designed as a current output with a range of 0...20 mA. For a voltage output with a range of 0...10 V an external resistor of 500 Ohms has to be connected at the terminals (12/13 or 26/27). P0777[2] Value x1 of DAC scaling Min: -99999.0 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 99999.0
Defines x1 output characteristic in [%]. Scaling block is responsible for adjustment of output value defined in P0771 (DAC connector input). Parameters of DAC scaling block (P0777 ... P0781) work as follows:
The default values of the scaling block provides a scaling of: P1: 0.0 % = 0 mA P2: 100.0 % = 20 mA Dependency:
Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to be generated.

The DAC-linear characteristic is described by 4 coordinates, based on a two-point equation:
0778 P 0780 P P0777 - x
For calculations the point-gradient form (offset and gradient) is more advantageous:
0 y x m y + ⋅ = The transformation between these two forms is given by:
0778 P 0780 P m − − = % 200 0777 P 0779 P
0780 P 0777 P 0779 P 0778 P y0 ≤ −
⋅ − ⋅ =
For scaling of the input the value of y_max and x_min has to be determined. This is done by the following equations:
0779 P 0778 P 0777 P 0780 P x in m −
⋅ − ⋅ =
0778 P 0780 P ) x x ( y min max max − − ⋅ − =
xmin xmax
P0779 x2 P0778[2] Value y1 of DAC scaling Min: 0 CStat: CUT Datatype: Float Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 20
Defines y1 of output characteristic. Index:
P0778[0] : Analog output 1 (DAC 1) P0778[1] : Analog output 2 (DAC 2) P0779[2] Value x2 of DAC scaling Min: -99999.0 CStat: CUT Datatype: Float Unit: % Def: 100.0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 99999.0
Defines x2 of output characteristic in [%]. Index:
Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to be generated. P0780[2] Value y2 of DAC scaling Min: 0 CStat: CUT Datatype: Float Unit: - Def: 20 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 20
Defines y2 of output characteristic. Index:

P0781[2] Width of DAC deadband Min: 0 CStat: CUT Datatype: Float Unit: - Def: 0 P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 20
Sets width of dead-band in [mA] for analog output.
Index:
P0781[0] : Analog output 1 (DAC 1) P0781[1] : Analog output 2 (DAC 2) r0785 CO/BO: Status word of DAC Min: - Datatype: U16 Unit: - Def: - P-Group: TERMINAL Max: -
Displays status of analog output. Bit 0 indicates that the value of analog output 1 is negative. Bit 1 indicates that the value of analog output 2 is negative. Bitfields:
Bit00 Analog output 1 -ve 0 NO 1 YES Bit01 Analog output 2 -ve 0 NO 1 YES

P0800[3] BI: Download parameter set 0 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of command to start download of parameter set 0 from attached AOP. Index:
P0800[0] : 1st. Command data set (CDS) P0800[1] : 2nd. Command data set (CDS) P0800[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) Dependency:
Parameter set 0 Parameter set 1
(0:0)
r0002 = 1 "Drive ready"
Transmission of "Parameter set 0" from AOP to inverter P0801[3] BI: Download parameter set 1 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines sources of command to start download of parameter set 1 from attached AOP. Index:
P0801[0] : 1st. Command data set (CDS) P0801[1] : 2nd. Command data set (CDS) P0801[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) Note:

P0809[3] Copy command data set (CDS) Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 2
Calls "copy Command Data Set (CDS)" function. The list of all Command Data Sets (CDS) are shown in the opening instructions of the Parameter List (PLI). Index:
Copying of all values from CDS1 to CDS3 can be accomplished by the following procedure:
P0809[0] = 0 P0809[1] = 2 P0809[2] = 1

P0700 P0701 P0702 P0703 P0704 P2253 P2254 P2264
2. CDS 3. CDS
Start value in index 2 is automatically reset to "0" after execution of function. P0810 BI: CDS bit 0 (Local / Remote) Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4095:0
Selects command source from which to read Bit 0 for selecting a command data set (CDS).


The actual active command data set (CDS) is displayed in parameter r0050.
CDS
1. CDS 0 0
2. CDS 0 1
3. CDS 1 0
3. CDS 1 1
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) Example:
Typical procedure for CDS switch-over: - CDS1: Command source via terminal and setpoint source via analog input (ADC) - CDS2: Command source via BOP and setpoint source via MOP - CDS switch-over takes place via digital input 4 (DIN 4) Steps: 1. Perform commissioning with CDS1 parameters (P0700[0] = 2 and P1000[0] = 2) 2. Connect P0810 (P0811 if necessary) with the source of CDS switch-over (P0704[0] = 99, P0810 = 722.3) 3. Copy CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2) 4. Change CDS2 parameter as required (set parameters for CDS2 [P0700=1 and P1000=1])
BOP
MOP
P0811 is also relevant for command data set (CDS) set selection. P0811 BI: CDS bit 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4095:0
Selects command source from which to read Bit 1 for selecting a command data set (see P0810). Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) Note:
P0810 is also relevant for command data set (CDS) selection.

P0819[3] Copy drive data set (DDS) Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 2
Calls "Copy Drive Data Set (DDS)" function. The list of all Drive Data Sets (DDS) are shown in the opening instructions of the Parameter List (PLI). Index:
Copying of all values from DDS1 to DDS3 can be accomplished by the following procedure:
P0819[0] = 0 P0819[1] = 2 P0819[2] = 1

P0005 P0291 P0300 P0304 P0305 P2484 P2487 P2488
2. DDS 3. DDS
Start value in index 2 is automatically reset to "0" after execution of function. P0820 BI: DDS bit 0 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4095:0
Selects command source from which to read Bit 0 for selecting a drive data set (DDS).

(0:0)
(0:0)
approx. 50 ms approx. 50 ms Changeover time Changeover time

The actual active drive data set (DDS) is displayed in parameter r0051[1].
DDS
1. DDS 0 0
2. DDS 0 1
3. DDS 1 0
3. DDS 1 1
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) Example:
a) Commissioning procedure with one motor: - Apply commissioning to DDS1 - Connect P0820 (P0821 if necessary) with DDS source (i.e. via DIN 4: P0704[0] = 99, P0820 = 722.3) - Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2) - Adapt DDS2 parameters (e.g. Ramp-up time P1120[1] and Ramp-down time P1121[1])
M
AFM RFG Motor control
DIN4
P1120 P1121
[0] DDS1
[1] DDS2
[2] DDS3
b) Commissioning procedure with two motors (Motor 1, Motor 2): - Commission Motor 1; Adapt all other DDS1 parameters (as required) - Connect P0820 (P0821 if necessary) with DDS source (i.e. via DIN 4: P0704[0] = 99, P0820 = 722.3) - Switch-over to DDS2 (check it via r0051) - Commission Motor 2; Adapt all other DDS2 parameters (as required)
MM4
K1
M2
K2
P0821 is also relevant for drive data set (DDS) selection.

P0821 BI: DDS bit 1 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4095:0
Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter P0820). Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) Note:
P0820 is also relevant for drive data set (DDS) selection.
P0840[3] BI: ON/OFF1 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Allows ON/OFF1 command source to be selected using BICO. The first three digits describe the parameter number of the command source; the last digit denotes the bit setting for that parameter. The default setting (ON right) is digital input 1 (722.0). Alternative source possible only when function of digital input 1 is changed (via P0701) before changing value of P0840.
OFF1
2 1 OFF , down ⋅ =
Index:
P0840[0] : 1st. Command data set (CDS) P0840[1] : 2nd. Command data set (CDS) P0840[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.0 = ON/OFF1 via BOP Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source). Note:
- OFF1 means a ramp stop down to 0 using P1121. - OFF1 is low active. - For the priority of all soft commands, the following applies: OFF2, OFF3, OFF1

P0842[3] BI: ON reverse/OFF1 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Allows ON/OFF1 reverse command source to be selected using BICO. Normally in this case at a positive frequency setpoint, it is getting approached ccw (negative frequency setpoint) The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. Index:
P0842[0] : 1st. Command data set (CDS) P0842[1] : 2nd. Command data set (CDS) P0842[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.0 = ON/OFF1 via BOP Details:
See parameter P0840. P0844[3] BI: 1. OFF2 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines first source of OFF2. The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.
Index:
P0844[0] : 1st. Command data set (CDS) P0844[1] : 2nd. Command data set (CDS) P0844[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.0 = ON/OFF1 via BOP 19.1 = OFF2: Electrical stop via BOP Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source). Note:
- OFF2 means an immediate pulse inhibit; the motor coasts down. - OFF2 is low active. - The following applies for the priority of all of the OFF commands: OFF2, OFF3, OFF1

P0845[3] BI: 2. OFF2 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 19:1 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines second source of OFF2. The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active. Index:
P0845[0] : 1st. Command data set (CDS) P0845[1] : 2nd. Command data set (CDS) P0845[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.0 = ON/OFF1 via BOP Details:
See parameter P0844. P0848[3] BI: 1. OFF3 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines first source of OFF3. The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active.
2 3 OFF , down ⋅ =
Index:
P0848[0] : 1st. Command data set (CDS) P0848[1] : 2nd. Command data set (CDS) P0848[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.0 = ON/OFF1 via BOP Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source). Note:
- OFF3 means fast ramp-down to 0 Hz through P1135. - OFF3 is low-active. - Priority of all OFF commands: OFF2, OFF3, OFF1

P0849[3] BI: 2. OFF3 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines second source of OFF3. The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active. Index:
P0849[0] : 1st. Command data set (CDS) P0849[1] : 2nd. Command data set (CDS) P0849[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.0 = ON/OFF1 via BOP Dependency:
In contrast to P0848 (first source of OFF3), this parameter is always active, independent of P0719 (selection of command and frequency setpoint). Details:
See parameter P0848. P0852[3] BI: Pulse enabling Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of pulse enable/disable signal. Index:
P0852[0] : 1st. Command data set (CDS) P0852[1] : 2nd. Command data set (CDS) P0852[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).
P0918 CB address Min: 0 CStat: CT Datatype: U16 Unit: - Def: 3 P-Group: COMM Active: first confirm QuickComm.: No Max: 65535
Defines address of CB (communication board) or address of the other option modules. There are two ways to set the bus address: - via DIP switches on the PROFIBUS module - via a user-entered value Note:
Possible PROFIBUS settings: - 1 ... 125 - 0, 126, 127 are not allowed The following applies when a PROFIBUS module is used: - DIP switch = 0 Address defined in P0918 (CB address) is valid - DIP switch not = 0 DIP switch setting has priority and P0918 indicates DIP switch setting.

P0927 Parameter changeable via Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 15 P-Group: COMM Active: first confirm QuickComm.: No Max: 15
Specifies the interfaces which can be used to change parameters. This parameter allows the user to easily protect the inverter from unauthorized modification of parameters. Annotation: Parameter P0927 is not password protected. Bitfields:
Bit00 PROFIBUS / CB 0 NO 1 YES Bit01 BOP 0 NO 1 YES Bit02 USS on BOP link 0 NO 1 YES Bit03 USS on COM link 0 NO 1 YES Example:
Bits 0, 1, 2 and 3 set: The default setting allows parameters to be changed via any interface. If all bits are set, the parameter is displayed on BOP as follows:
BOP: P0927 Bits 0, 1, 2 and 3 reset: This setting allows no parameters to be modified via any interface with the exception of P0003 and P0927. If all bits are reset, the parameter is displayed on BOP as follows:
The seven-segment display is explained in the "Introduction to MICROMASTER System Parameters" in this handbook. r0947[8] CO: Last fault code Min: - Datatype: U16 Unit: - Def: - P-Group: ALARMS Max: -
Displays fault history according to the diagram below where: - "F1" is the first active fault (not yet acknowledged). - "F2" is the second active fault (not yet acknowledged). - "F1e" is the occurrence of the fault acknowledgement for F1 & F2. This moves the value in the 2 indices down to the next pair of indices, where they are stored. Indices 0 & 1 contain the active faults. When faults are acknowledged, indices 0 & 1 are reset to 0.
F2
Most recent Fault Codes - 1
Most recent Fault Codes - 2 r0947[4] r0947[5]
Most recent Fault Codes - 3 r0947[6] r0947[7]
Index:
r0947[0] : Recent fault trip --, fault 1 r0947[1] : Recent fault trip --, fault 2 r0947[2] : Recent fault trip -1, fault 3 r0947[3] : Recent fault trip -1, fault 4 r0947[4] : Recent fault trip -2, fault 5 r0947[5] : Recent fault trip -2, fault 6 r0947[6] : Recent fault trip -3, fault 7 r0947[7] : Recent fault trip -3, fault 8 Example:
If the inverter trips on undervoltage and then receives an external trip before the undervoltage is acknowledged, you will obtain: - r0947[0] = 3 Undervoltage (F0003) - r0947[1] = 85 External trip (F0085) Whenever a fault in index 0 is acknowledged (F1e), the fault history shifts as indicated in the diagram above. Dependency:
Index 1 used only if second fault occurs before first fault is acknowledged. Details:
See "Faults and Warnings"

Time stamp to indicate when the fault has occurred. Index:
r0948[0] : Recent fault trip --, time stamp r0948[1] : Recent fault trip --, time stamp r0948[2] : Recent fault trip --, time stamp r0948[3] : Recent fault trip -1, time stamp r0948[4] : Recent fault trip -1, time stamp r0948[5] : Recent fault trip -1, time stamp r0948[6] : Recent fault trip -2, time stamp r0948[7] : Recent fault trip -2, time stamp r0948[8] : Recent fault trip -2, time stamp r0948[9] : Recent fault trip -3, time stamp r0948[10] : Recent fault trip -3, time stamp r0948[11] : Recent fault trip -3, time stamp Details:
Parameter r2114 (runtime counter) is a possible source of the time stamp. When using the runtime counter, the time is entered into the first two indices of the fault trip (shutdown) essentially the same as for r2114. Time stamp when using r2114 (Refer to parameter r2114):
r0948[0] : r0948[1] : r0948[2] : r0948[3] : r0948[4] : r0948[5] : r0948[6] : r0948[7] : r0948[8] : r0948[9] : r0948[10] : r0948[11] :
Last fault trip --, system time, seconds, upper word Last fault trip --, system time, seconds, lower word 0
Last fault trip --, system time, seconds, upper word Last fault trip --, system time, seconds, lower word
Last fault trip --, system time, seconds, upper word Last fault trip --, system time, seconds, lower word
Last fault trip --, system time, seconds, upper word Last fault trip --, system time, seconds, lower word
Parameter P2115 (AOP real-time clock) is an additional possible source of the time stamp. When using the real-time counter, instead of the system runtime r2114[0] and r2114[1], the value of the real-time clock P2115[0] to P2115[2] is read-in. If the contents of parameter P2115 = 0, then the system assumes that there was no synchronization with the real time. In this case, if there is a fault, values are transferred from parameter r2114 into parameter P0948. If the contents of parameter P2115 are not equal to zero, then a synchronization with real time has taken place. In this case, if there is a fault, the values from parameter P2115 are transferred into parameter P0948. Time stamp when using P2115 (Refer to parameter P2115 (AOP real-time clock)):
Last fault trip --, fault time, seconds + minutes Last fault trip --, fault time, hours + days Last fault trip --, fault time, month + year Last fault trip -1, fault time, seconds + minutes Last fault trip -1, fault time, hours + days Last fault trip -1, fault time, month + year Last fault trip -2, fault time, seconds + minutes Last fault trip -2, fault time, hours + days Last fault trip -2, fault time, month + year Last fault trip -3, fault time, seconds + minutes Last fault trip -3, fault time, hours + days Last fault trip -3, fault time, month + year r0949[8] CO: Fault value Min: - Datatype: U16 Unit: - Def: - P-Group: ALARMS Max: -
r0948[0] : r0948[1] : r0948[2] : r0948[3] : r0948[4] : r0948[5] : r0948[6] : r0948[7] : r0948[8] : r0948[9] : r0948[10] : r0948[11] :
Displays drive fault values. It is for service purposes and indicate the type of fault reported. The values are listed in the code where faults are reported. Index:
r0949[0] : Recent fault trip --, fault value 1 r0949[1] : Recent fault trip --, fault value 2 r0949[2] : Recent fault trip -1, fault value 3 r0949[3] : Recent fault trip -1, fault value 4 r0949[4] : Recent fault trip -2, fault value 5 r0949[5] : Recent fault trip -2, fault value 6 r0949[6] : Recent fault trip -3, fault value 7 r0949[7] : Recent fault trip -3, fault value 8

P0952 Total number of faults Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: first confirm QuickComm.: No Max: 8
Displays number of faults stored in r0947 (last fault code). Dependency:
Setting 0 resets fault history. (changing to 0 also resets parameter r0948 - fault time). r0964[5] Firmware version data Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Firmware version data. Index:
r0964[0] : Company (Siemens = 42) r0964[1] : Product type r0964[2] : Firmware version r0964[3] : Firmware date (year) r0964[4] : Firmware date (day/month) Example:
No. Value Meaning
1002 MICROMASTER 440
1003 MICRO- / COMBIMASTER 411
1004 MICROMASTER 410
MICROMASTER 440 PX
1007 MICROMASTER 430
Firmware V1.05
r0964[4] 2710 27.10.2001
Identification of profile number and version for PROFIDrive. r0967 Control word 1 Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 1. Bitfields:
Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit02 OFF3: Fast stop 0 YES 1 NO Bit03 Pulses enabled 0 NO 1 YES Bit04 RFG enable 0 NO 1 YES Bit05 RFG start 0 NO 1 YES Bit06 Setpoint enable 0 NO 1 YES Bit07 Fault acknowledge 0 NO 1 YES Bit08 JOG right 0 NO 1 YES Bit09 JOG left 0 NO 1 YES Bit10 Control from PLC 0 NO 1 YES Bit11 Reverse (setpoint inversion) 0 NO 1 YES Bit13 Motor potentiometer MOP up 0 NO 1 YES Bit14 Motor potentiometer MOP down 0 NO 1 YES Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES

Displays active status word of inverter (in binary) and can be used to diagnose which commands are active. Bitfields:
Bit00 Drive ready 0 NO 1 YES Bit01 Drive ready to run 0 NO 1 YES Bit02 Drive running 0 NO 1 YES Bit03 Drive fault active 0 NO 1 YES Bit04 OFF2 active 0 YES 1 NO Bit05 OFF3 active 0 YES 1 NO Bit06 ON inhibit active 0 NO 1 YES Bit07 Drive warning active 0 NO 1 YES Bit08 Deviation setpoint / act. value 0 YES 1 NO Bit09 PZD control 0 NO 1 YES Bit10 Maximum frequency reached 0 NO 1 YES Bit11 Warning: Motor current limit 0 YES 1 NO Bit12 Motor holding brake active 0 NO 1 YES Bit13 Motor overload 0 YES 1 NO Bit14 Motor runs right 0 NO 1 YES Bit15 Inverter overload 0 YES 1 NO P0970 Factory reset Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: PAR_RESET Active: first confirm QuickComm.: No Max: 1
P0970 = 1 resets all parameters to their default values. Possible Settings:
0 Disabled 1 Parameter reset Dependency:
- First set P0010 = 30 (factory settings). - Stop drive (i.e. disable all pulses) before you can reset parameters to default values. Note:
The following parameters retain their values after a factory reset: - P0014 Store mode - r0039 CO: Energy consumption meter [kWh] - P0100 Europe / North America - P0918 CB address - P2010 USS baud rate - P2011 USS address P0971 Transfer data from RAM to EEPROM Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: COMM Active: first confirm QuickComm.: No Max: 1
Transfers values from RAM to EEPROM when set to 1. Possible Settings:
0 Disabled 1 Start transfer Note:
All values in RAM are transferred to EEPROM. Parameter is automatically reset to 0 (default) after successful transfer. The storage from RAM to EEPROM is accomplished via P0971. The communications are reset, if the transfer was successful. During the reset process communications will be interrupted. This creates the following conditions: - PLC (e.g. SIMATIC S7) enters Stop mode - Starter automatically recovers communications once they are re-established. - Drivemonitor is displayed "NC" (not connected) in the status line or "drive busy". - BOP displays "busy" After completion of the transfer process, the communication between the inverter and the PC-tools (e.g. Starter) or BOP is automatically re-established.

P1000[3] Selection of frequency setpoint Min: 0 CStat: CT Datatype: U16 Unit: - Def: 2 P-Group: SETPOINT Active: first confirm QuickComm.: Yes Max: 77
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the least significant digit (i.e., 0 to 7) and any additional setpoint from the most significant digit (i.e., x0 through to x7). Possible Settings:
0 No main setpoint 1 MOP setpoint 2 Analog setpoint 3 Fixed frequency 4 USS on BOP link 5 USS on COM link 6 CB on COM link 7 Analog setpoint 2 10 No main setpoint + MOP setpoint 11 MOP setpoint + MOP setpoint 12 Analog setpoint + MOP setpoint 13 Fixed frequency + MOP setpoint 14 USS on BOP link + MOP setpoint 15 USS on COM link + MOP setpoint 16 CB on COM link + MOP setpoint 17 Analog setpoint 2 + MOP setpoint 20 No main setpoint + Analog setpoint 21 MOP setpoint + Analog setpoint 22 Analog setpoint + Analog setpoint 23 Fixed frequency + Analog setpoint 24 USS on BOP link + Analog setpoint 25 USS on COM link + Analog setpoint 26 CB on COM link + Analog setpoint 27 Analog setpoint 2 + Analog setpoint 30 No main setpoint + Fixed frequency 31 MOP setpoint + Fixed frequency 32 Analog setpoint + Fixed frequency 33 Fixed frequency + Fixed frequency 34 USS on BOP link + Fixed frequency 35 USS on COM link + Fixed frequency 36 CB on COM link + Fixed frequency 37 Analog setpoint 2 + Fixed frequency 40 No main setpoint + USS on BOP link 41 MOP setpoint + USS on BOP link 42 Analog setpoint + USS on BOP link 43 Fixed frequency + USS on BOP link 44 USS on BOP link + USS on BOP link 45 USS on COM link + USS on BOP link 46 CB on COM link + USS on BOP link 47 Analog setpoint 2 + USS on BOP link 50 No main setpoint + USS on COM link 51 MOP setpoint + USS on COM link 52 Analog setpoint + USS on COM link 53 Fixed frequency + USS on COM link 54 USS on BOP link + USS on COM link 55 USS on COM link + USS on COM link 57 Analog setpoint 2 + USS on COM link 60 No main setpoint + CB on COM link 61 MOP setpoint + CB on COM link 62 Analog setpoint + CB on COM link 63 Fixed frequency + CB on COM link 64 USS on BOP link + CB on COM link 66 CB on COM link + CB on COM link 67 Analog setpoint 2 + CB on COM link 70 No main setpoint + Analog setpoint 2 71 MOP setpoint + Analog setpoint 2 72 Analog setpoint + Analog setpoint 2 73 Fixed frequency + Analog setpoint 2 74 USS on BOP link + Analog setpoint 2 75 USS on COM link + Analog setpoint 2 76 CB on COM link + Analog setpoint 2 77 Analog setpoint 2 + Analog setpoint 2

Index:
P1000[0] : 1st. Command data set (CDS) P1000[1] : 2nd. Command data set (CDS) P1000[2] : 3rd. Command data set (CDS) Example:
Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor potentiometer.
Example P1000 = 12 :
ADC
FF
ADC2
Be aware, by changing of parameter P1000 all BICO parameters (see table below) are modified. Note:
Single digits denote main setpoints that have no additional setpoint. Changing this parameter sets (to default) all settings on item selected (see table).

y = 0 y = 1 y = 2 y = 3 y = 4 y = 5 y = 6 y = 7
0.0 1050.0 755.0 1024.0 2015.1 2018.1 2050.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.0 1024.0 2015.1 2018.1 2050.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.0 1024.0 2015.1 2018.1 2050.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.01 1024.0 2015.1 2018.1 2050.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.0 1024.0 2015.1 2018.1 2050.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.0 1024.0 2015.1 2018.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.0 1024.0 2015.1 2050.1 755.1 P1070 1.0 P1071
0.0 1050.0 755.0 1024.0 2015.1 2018.1 2050.1 755.1 P1070 1.0 P1071
Example:
P1000 = 21 → P1070 = 1050.0 P1071 = 1.0 P1075 = 755.0 P1076 = 1.0

P1001[3] Fixed frequency 1 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 0.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 1. There are three options available for selection of the fixed frequencies: 1. Direct selection 2. Direct selection + ON command 3. Binary coded selection + ON command 1. Direct selection (P0701 - P0706 = 15): - In this mode of operation 1 digital input selects 1 fixed frequency. - If several inputs are active together, the selected frequencies are summed. - E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6. 2. Direct selection + ON command (P0701 - P0706 = 16): - The fixed frequency selection combines the fixed frequencies with an ON command. - In this mode of operation 1 digital input selects 1 fixed frequency. - If several inputs are active together, the selected frequencies are summed. - E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6. 3. Binary coded selection + ON command (P0701 - P0706 = 17): - Up to 16 fixed frequencies can be selected using this method. - The fixed frequencies are selected according to the following table: Index:
P1001[0] : 1st. Drive data set (DDS) P1001[1] : 2nd. Drive data set (DDS) P1001[2] : 3rd. Drive data set (DDS) Example:
Binary coded selection :
DIN4 DIN3 DIN2 DIN1 FF0 P1001 FF1 0 Hz 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 0 0 0 1 0 0 1 1 0 1 0 1 0 1 0 0 1 1 0 1 0
P1002 FF2 P1003 FF3 P1004 FF4 P1005 FF5 P1006 FF6 P1007 FF7 P1008 FF8
FF10
FF11
FF12
FF13
FF14
FF15 1 1 1 1

Direct selection of FF P1001 via DIN 1:
P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1
P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1
r0722.0
DIN2 r0722.1
Dependency:
Select fixed frequency operation (using P1000). Inverter requires ON command to start in the case of direct selection (P0701 - P0706 = 15). Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command. P1002[3] Fixed frequency 2 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 5.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 2. Index:
P1002[0] : 1st. Drive data set (DDS) P1002[1] : 2nd. Drive data set (DDS) P1002[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1003[3] Fixed frequency 3 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 10.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 3. Index:
P1003[0] : 1st. Drive data set (DDS) P1003[1] : 2nd. Drive data set (DDS) P1003[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1004[3] Fixed frequency 4 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 15.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 4. Index:
P1004[0] : 1st. Drive data set (DDS) P1004[1] : 2nd. Drive data set (DDS) P1004[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1005[3] Fixed frequency 5 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 20.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 5. Index:
P1005[0] : 1st. Drive data set (DDS) P1005[1] : 2nd. Drive data set (DDS) P1005[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1).

P1006[3] Fixed frequency 6 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 25.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 6. Index:
P1006[0] : 1st. Drive data set (DDS) P1006[1] : 2nd. Drive data set (DDS) P1006[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1007[3] Fixed frequency 7 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 30.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 7. Index:
P1007[0] : 1st. Drive data set (DDS) P1007[1] : 2nd. Drive data set (DDS) P1007[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1008[3] Fixed frequency 8 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 35.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 8. Index:
P1008[0] : 1st. Drive data set (DDS) P1008[1] : 2nd. Drive data set (DDS) P1008[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1009[3] Fixed frequency 9 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 40.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 9. Index:
P1009[0] : 1st. Drive data set (DDS) P1009[1] : 2nd. Drive data set (DDS) P1009[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1010[3] Fixed frequency 10 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 45.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 10. Index:
P1010[0] : 1st. Drive data set (DDS) P1010[1] : 2nd. Drive data set (DDS) P1010[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1011[3] Fixed frequency 11 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 50.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 11. Index:
P1011[0] : 1st. Drive data set (DDS) P1011[1] : 2nd. Drive data set (DDS) P1011[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1).

P1012[3] Fixed frequency 12 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 55.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 12. Index:
P1012[0] : 1st. Drive data set (DDS) P1012[1] : 2nd. Drive data set (DDS) P1012[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1013[3] Fixed frequency 13 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 60.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 13. Index:
P1013[0] : 1st. Drive data set (DDS) P1013[1] : 2nd. Drive data set (DDS) P1013[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1014[3] Fixed frequency 14 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 65.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 14. Index:
P1014[0] : 1st. Drive data set (DDS) P1014[1] : 2nd. Drive data set (DDS) P1014[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1015[3] Fixed frequency 15 Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 65.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 15. Index:
P1015[0] : 1st. Drive data set (DDS) P1015[1] : 2nd. Drive data set (DDS) P1015[2] : 3rd. Drive data set (DDS) Details:
See parameter P1001 (fixed frequency 1). P1016[3] Fixed frequency mode - Bit 0 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the mode of selection Bit 0. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P1016[0] : 1st. Command data set (CDS) P1016[1] : 2nd. Command data set (CDS) P1016[2] : 3rd. Command data set (CDS) Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1017[3] Fixed frequency mode - Bit 1 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1017 defines the mode of selection Bit 1. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P1017[0] : 1st. Command data set (CDS) P1017[1] : 2nd. Command data set (CDS) P1017[2] : 3rd. Command data set (CDS) Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies. P1018[3] Fixed frequency mode - Bit 2 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1018 defines the mode of selection Bit 2. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P1018[0] : 1st. Command data set (CDS) P1018[1] : 2nd. Command data set (CDS) P1018[2] : 3rd. Command data set (CDS) Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies. P1019[3] Fixed frequency mode - Bit 3 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1019 defines the mode of selection Bit 3. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P1019[0] : 1st. Command data set (CDS) P1019[1] : 2nd. Command data set (CDS) P1019[2] : 3rd. Command data set (CDS) Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies. P1020[3] BI: Fixed freq. selection Bit 0 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection. Index:
P1020[0] : 1st. Command data set (CDS) P1020[1] : 2nd. Command data set (CDS) P1020[2] : 3rd. Command data set (CDS) Common Settings:
P1020 = 722.0 ==> Digital input 1 P1021 = 722.1 ==> Digital input 2 P1022 = 722.2 ==> Digital input 3 P1023 = 722.3 ==> Digital input 4 P1026 = 722.4 ==> Digital input 5 P1028 = 722.5 ==> Digital input 6 Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)

P1021[3] BI: Fixed freq. selection Bit 1 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection. Index:
P1021[0] : 1st. Command data set (CDS) P1021[1] : 2nd. Command data set (CDS) P1021[2] : 3rd. Command data set (CDS) Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO) Details:
See P1020 (fixed frequency selection Bit 0) for most common settings P1022[3] BI: Fixed freq. selection Bit 2 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection. Index:
P1022[0] : 1st. Command data set (CDS) P1022[1] : 2nd. Command data set (CDS) P1022[2] : 3rd. Command data set (CDS) Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO) Details:
See P1020 (fixed frequency selection Bit 0) for most common settings P1023[3] BI: Fixed freq. selection Bit 3 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:3 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection. Index:
P1023[0] : 1st. Command data set (CDS) P1023[1] : 2nd. Command data set (CDS) P1023[2] : 3rd. Command data set (CDS) Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO) Details:
See P1020 (fixed frequency selection Bit 0) for most common settings r1024 CO: Act. fixed frequency Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays sum total of selected fixed frequencies. P1025[3] Fixed frequency mode - Bit 4 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 2
Direct selection or direct selection + ON for bit 4 Possible Settings:
1 Direct selection 2 Direct selection + ON command Index:
P1025[0] : 1st. Command data set (CDS) P1025[1] : 2nd. Command data set (CDS) P1025[2] : 3rd. Command data set (CDS) Details:
See parameter P1001 for description of how to use fixed frequencies. P1026[3] BI: Fixed freq. selection Bit 4 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:4 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection. Index:
P1026[0] : 1st. Command data set (CDS) P1026[1] : 2nd. Command data set (CDS) P1026[2] : 3rd. Command data set (CDS) Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO). Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.

P1027[3] Fixed frequency mode - Bit 5 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 2
direct selection or direct selection + ON for bit 5 Possible Settings:
1 Direct selection 2 Direct selection + ON command Index:
P1027[0] : 1st. Command data set (CDS) P1027[1] : 2nd. Command data set (CDS) P1027[2] : 3rd. Command data set (CDS) Details:
See parameter P1001 for description of how to use fixed frequencies. P1028[3] BI: Fixed freq. selection Bit 5 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:5 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection. Index:
P1028[0] : 1st. Command data set (CDS) P1028[1] : 2nd. Command data set (CDS) P1028[2] : 3rd. Command data set (CDS) Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO). Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.

P1031[3] Setpoint memory of the MOP Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 1
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down. Possible Settings:
0 MOP setpoint will not be stored 1 MOP setpoint will be stored (P1040 is updated) Index:
P1031[0] : 1st. Drive data set (DDS) P1031[1] : 2nd. Drive data set (DDS) P1031[2] : 3rd. Drive data set (DDS) Note:
On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint of the MOP). P1032 Inhibit negative MOP setpoints Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 1
This parameter suppresses negative setpoints of the MOP output r1050. Possible Settings:
0 Neg. MOP setpoint is allowed 1 Neg. MOP setpoint inhibited Note:
The reversing functions (e.g. BOP-Reverse button if P0700 = 1) are not affected by the settings of P1032. Use P1110 to fully prevent change of direction in setpoint channel. P1035[3] BI: Enable MOP (UP-command) Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 19:13 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source for motor potentiometer setpoint increase frequency. Index:
P1035[0] : 1st. Command data set (CDS) P1035[1] : 2nd. Command data set (CDS) P1035[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.D = MOP up via BOP P1036[3] BI: Enable MOP (DOWN-command) Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 19:14 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source for motor potentiometer setpoint decrease frequency. Index:
P1036[0] : 1st. Command data set (CDS) P1036[1] : 2nd. Command data set (CDS) P1036[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.E = MOP down via BOP

P1040[3] Setpoint of the MOP Min: -650.00 CStat: CUT Datatype: Float Unit: Hz Def: 5.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Determines setpoint for motor potentiometer control (P1000 = 1). Index:
P1040[0] : 1st. Drive data set (DDS) P1040[1] : 2nd. Drive data set (DDS) P1040[2] : 3rd. Drive data set (DDS) Note:
- If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse direction will be inhibited by default of P1032 (inhibit reverse direction of MOP). - To re-enable reverse direction, set P1032 = 0. r1050 CO: Act. Output freq. of the MOP Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays output frequency of motor potentiometer setpoint ([Hz]).

Possible parameter settings for the selection of MOP:

or P0719 = 0, P0700 = 2, P1000 = 1
P0719 = 0, P0700 = 1, P1000 = 1
or P0719 = 0, P0700 = 4, P1000 = 1
or P0719 = 0, P0700 = 5, P1000 = 1
or P0719 = 0, P0700 = 6, P1000 = 1

P1055[3] BI: Enable JOG right Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of JOG right. Index:
P1055[0] : 1st. Command data set (CDS) P1055[1] : 2nd. Command data set (CDS) P1055[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.8 = JOG right via BOP Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source). P1056[3] BI: Enable JOG left Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of JOG left. Index:
P1056[0] : 1st. Command data set (CDS) P1056[1] : 2nd. Command data set (CDS) P1056[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.9 = JOG left via BOP Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

P1058[3] JOG frequency right Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 5.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Jogging increases the motor frequency by small amounts. The JOG buttons uses a non-latching switch on one of the digital inputs to control the motor frequency. If JOG clockwise (jogging clockwise) or JOG counter-clockwise is selected, the speed is increased until the value, set in P1058 is reached.
DIN
BOP
Index:
P1058[0] : 1st. Drive data set (DDS) P1058[1] : 2nd. Drive data set (DDS) P1058[2] : 3rd. Drive data set (DDS) Dependency:
P1060 and P1061 set up and down ramp times respectively for jogging. P1059[3] JOG frequency left Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 5.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
While JOG left is selected, this parameter determines the frequency at which the inverter will run. Index:
P1059[0] : 1st. Drive data set (DDS) P1059[1] : 2nd. Drive data set (DDS) P1059[2] : 3rd. Drive data set (DDS) Dependency:
P1060 and P1061 set up and down ramp times respectively for jogging.

P1060[3] JOG ramp-up time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 10.00 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 650.00
Sets jog ramp-up time. This is the time used while jogging is active.
1058 P tup ⋅ =
Index:
P1060[0] : 1st. Drive data set (DDS) P1060[1] : 2nd. Drive data set (DDS) P1060[2] : 3rd. Drive data set (DDS) Notice:
Ramp times will be used as follows: - P1060 / P1061 : JOG mode is active - P1120 / P1121 : Normal mode (ON/OFF) is active - P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active P1061[3] JOG ramp-down time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 10.00 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 650.00
Sets ramp-down time. This is the time used while jogging is active.
1058 P tdown ⋅ = P1061
Index:
P1061[0] : 1st. Drive data set (DDS) P1061[1] : 2nd. Drive data set (DDS) P1061[2] : 3rd. Drive data set (DDS) Notice:
Ramp times will be used as follows: - P1060 / P1061 : JOG mode is active - P1120 / P1121 : Normal mode (ON/OFF) is active - P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active

P1070[3] CI: Main setpoint Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 755:0 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 4000:0
Defines source of main setpoint. Index:
P1070[0] : 1st. Command data set (CDS) P1070[1] : 2nd. Command data set (CDS) P1070[2] : 3rd. Command data set (CDS) Common Settings:
755 = Analog input 1 setpoint 1024 = Fixed frequency setpoint 1050 = Motor potentiometer (MOP) setpoint P1071[3] CI: Main setpoint scaling Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 4000:0
Defines source of the main setpoint scaling. Index:
P1071[0] : 1st. Command data set (CDS) P1071[1] : 2nd. Command data set (CDS) P1071[2] : 3rd. Command data set (CDS) Common Settings:
755 = Analog input 1 setpoint 1024 = Fixed frequency setpoint 1050 = Motor potentiometer (MOP) setpoint P1074[3] BI: Disable additional setpoint Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Disables additional setpoint Index:
P1074[0] : 1st. Command data set (CDS) P1074[1] : 2nd. Command data set (CDS) P1074[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)) P1075[3] CI: Additional setpoint Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 4000:0
Defines source of the additional setpoint (to be added to main setpoint). Index:
P1075[0] : 1st. Command data set (CDS) P1075[1] : 2nd. Command data set (CDS) P1075[2] : 3rd. Command data set (CDS) Common Settings:
755 = Analog input 1 setpoint 1024 = Fixed frequency setpoint 1050 = Motor potentiometer (MOP) setpoint

P1076[3] CI: Additional setpoint scaling Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 4000:0
Defines source of scaling for additional setpoint (to be added to main setpoint). Index:
P1076[0] : 1st. Command data set (CDS) P1076[1] : 2nd. Command data set (CDS) P1076[2] : 3rd. Command data set (CDS) Common Settings:
1 = Scaling of 1.0 (100%) 755 = Analog input 1 Setpoint 1024 = Fixed Frequency Setpoint 1050 = MOP Setpoint r1078 CO: Total frequency setpoint Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays sum of main and additional setpoints in [Hz]. r1079 CO: Selected frequency setpoint Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays selected frequency setpoint. Following frequency setpoints are displayed: - r1078 Total frequency setpoint - P1058 JOG frequency right - P1059 JOG frequency left Dependency:
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG left respectively. Note:
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.

P1080[3] Min. frequency Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 0.00 P-Group: SETPOINT Active: Immediately QuickComm.: Yes Max: 650.00
Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint. The minimum frequency P1080 represents a masking frequency of 0 Hz for all frequency target value sources (e.g. ADC, MOP, FF, USS), with the exception of the JOG target value source (analogous to P1091). Thus the frequency band +/- P1080 is run through in optimum time by means of the acceleration/deceleration ramps. Dwelling in the frequency band is not possible (see example). Furthermore, an undershoot of the actual frequency f_act below min. frequency P1080 is output by the following signal function. Index:
P1080[0] : 1st. Drive data set (DDS) P1080[1] : 2nd. Drive data set (DDS) P1080[2] : 3rd. Drive data set (DDS) Example:
P1080 + P2150
-P1080 - P2150
Value set here is valid both for clockwise and for anticlockwise rotation. Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.

P1082[3] Max. frequency Min: 0.00 CStat: CT Datatype: Float Unit: Hz Def: 50.00 P-Group: SETPOINT Active: first confirm QuickComm.: Yes Max: 650.00
Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation. Futhermore, the monitoring function |f_act| >= P1082 (r0052 Bit10, see example below) is affected by this parameter. Index:
P1082[0] : 1st. Drive data set (DDS) P1082[1] : 2nd. Drive data set (DDS) P1082[2] : 3rd. Drive data set (DDS) Example:
|f_act| ≥ P1082 (f_max)
Dependency:
The maximal value of motor frequency P1082 is limited to pulse frequency P1800. P1082 is dependent on the derating characteristic as followed:
If closed-loop vector control (P1300 > 19) is selected, then the maximum frequency is internally limited by the following equation:
200.00) P0310, 5 min(P1082, = fmax ⋅ The resultant value is displayed in r1084 (resultant maximum frequency). The maximum output frequency of inverter can be exceeded if one of the following is active:
(Slip compensation active ) :
p0310 100 r0330 100 p1336 p1082 f f (p1335) f max , slip max max ⋅ ⋅ + = + =
(Flying restart active) :
p0310 100 r0330 2 p1082 f 2 f (p1200) f nom , slip max max ⋅ ⋅ + = ⋅ + =
When using the setpoint source - Analog Input - USS - CB (e.g. PROFIBUS) The setpoint frequency (in Hz) is cyclically calculated using a percentage value (e.g. for the analog input r0754) or a hexadecimal value (e.g. for the USS r2018[1]) and the reference frequency P2000. If for example P1082 = 80 Hz, P2000 = 50 Hz and the analog input is parameterised with P0757 = 0 V, P0758 = 0 %, P0759 = 10 V, P0760 = 100 %, a setpoint frequency of 50 Hz will be applied at 10 V of the analog input.

Displays resultant maximum frequency.
P1800 ≤ 6 kHz → 650.00) , 15 P1800 (P1082, min r1084 =
P1800 ≥ 8 kHz → 650.00) (P1082, min r1084=
200.00) P0310, 5 (P1082, min r1084 ⋅ = P1300 ≥ 20
P1091[3] Skip frequency 1 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 0.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).
Skip frequency Index:
P1091[0] : 1st. Drive data set (DDS) P1091[1] : 2nd. Drive data set (DDS) P1091[2] : 3rd. Drive data set (DDS) Notice:
- Stationary operation is not possible within the suppressed frequency range; the range is merely passed through (on the ramp). - For example, if P1091 = 10 Hz and P1101 = 2 Hz, it is not possible to operate continuously between 10 Hz +/- 2 Hz (i.e. between 8 and 12 Hz). P1092[3] Skip frequency 2 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 0.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines skip frequency 2 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth). Index:
P1092[0] : 1st. Drive data set (DDS) P1092[1] : 2nd. Drive data set (DDS) P1092[2] : 3rd. Drive data set (DDS) Details:
See P1091 (skip frequency 1). P1093[3] Skip frequency 3 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 0.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines skip frequency 3 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth). Index:
P1093[0] : 1st. Drive data set (DDS) P1093[1] : 2nd. Drive data set (DDS) P1093[2] : 3rd. Drive data set (DDS) Details:
See P1091 (skip frequency 1).
fout · Skip frequency bandwidth · fin

P1094[3] Skip frequency 4 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 0.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth). Index:
P1094[0] : 1st. Drive data set (DDS) P1094[1] : 2nd. Drive data set (DDS) P1094[2] : 3rd. Drive data set (DDS) Details:
See P1091 (skip frequency 1). P1101[3] Skip frequency bandwidth Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 2.00 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 10.00
Delivers frequency bandwidth to be applied to skip frequencies (in [Hz]). Index:
P1101[0] : 1st. Drive data set (DDS) P1101[1] : 2nd. Drive data set (DDS) P1101[2] : 3rd. Drive data set (DDS) Details:
See P1091 (skip frequency 1). P1110[3] BI: Inhibit neg. freq. setpoint Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited to the setpoint channel. Index:
P1110[0] : 1st. Command data set (CDS) P1110[1] : 2nd. Command data set (CDS) P1110[2] : 3rd. Command data set (CDS) Common Settings:
0 = Disabled 1 = Enabled Notice:
Where - If a min. frequency (P1080) and a negative setpoint are given, the motor is accelerated by a positive value in relationship to the min. frequency. - This function does not disable the "reverse command functions" (e.g. Reverse, ON left); rather, a reverse command causes motor to run in the positive direction only, as described above.

P1113[3] BI: Reverse Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:1 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of reverse command. Index:
P1113[0] : 1st. Command data set (CDS) P1113[1] : 2nd. Command data set (CDS) P1113[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 19.B = Reverse via BOP Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source). r1114 CO: Freq. setp. after dir. ctrl. Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays setpoint frequency after change of direction. r1119 CO: Freq. setpoint before RFG Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays output frequency after modification by other functions, e.g.: - P1110 BI: Inhibit neg. freq. setpoint, - P1091 - P1094 skip frequencies, - P1080 Min. frequency, - P1082 Max. frequency, - limitations, - etc.
P1120[3] Ramp-up time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 10.00 P-Group: SETPOINT Active: first confirm QuickComm.: Yes Max: 650.00
Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no rounding is used.
1 2 up ⋅ − =
Setting the ramp-up time too short can cause the inverter to trip (overcurrent). Index:
P1120[0] : 1st. Drive data set (DDS) P1120[1] : 2nd. Drive data set (DDS) P1120[2] : 3rd. Drive data set (DDS) Note:
If an external frequency setpoint with set ramp rates is used (e.g. from a PLC). The best way to achieve optimum drive performance is to set ramp times in P1120 and P1121 slightly shorter than those of the PLC. Notice:
Ramp times will be used as follows: - P1060 / P1061 : JOG mode is active - P1120 / P1121 : Normal mode (ON/OFF) is active - P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active

P1121[3] Ramp-down time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 10.00 P-Group: SETPOINT Active: first confirm QuickComm.: Yes Max: 650.00
Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used.
1 2 down ⋅ − =
Index:
P1121[0] : 1st. Drive data set (DDS) P1121[1] : 2nd. Drive data set (DDS) P1121[2] : 3rd. Drive data set (DDS) Notice:
Setting the ramp-down time too short can cause the inverter to trip (overcurrent (F0001) / overvoltage (F0002)). Ramp times will be used as follows: - P1060 / P1061 : JOG mode is active - P1120 / P1121 : Normal mode (ON/OFF) is active - P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active P1124[3] BI: Enable JOG ramp times Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source for switching between jog ramp times (P1060, P1061) and normal ramp times (P1120, P1121) as applied to the RFG. This parameter is valid for normal mode (ON/OFF) only. Index:
P1124[0] : 1st. Command data set (CDS) P1124[1] : 2nd. Command data set (CDS) P1124[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) Notice:
P1124 does not have any impact when JOG mode is selected. In this case, jog ramp times (P1060, P1061) will be used all the time. Ramp times will be used as follows: - P1060 / P1061 : JOG mode is active - P1120 / P1121 : Normal mode (ON/OFF) is active - P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active

P1130[3] Ramp-up initial rounding time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines initial rounding time in seconds as shown on the diagram below.
P1133 P1132 P1131 P1130 t
tup tdown where:
for P1131) P1130 ( 2 1 P1120 P1082
f - f 1 2 + ≥ ⋅
f - f P1131) P1130 ( 2 1 t 1 2 up ⋅ + + =
for P1133) P1132 ( 2 1 P1121 P1082
f - f 1 2 + ≥ ⋅
f - f P1133) P1132 ( 2 1 t 1 2 down ⋅ + + =
Index:
P1130[0] : 1st. Drive data set (DDS) P1130[1] : 2nd. Drive data set (DDS) P1130[2] : 3rd. Drive data set (DDS) Note:
- If short or zero ramp times (P1120, P1121 < P1130, P1131, P1132, P1133) are set, the total ramp up time (t_up) or ramp down time (t_down) will not depend on P1130. - See equations above for valid conditions to calculate t_up and t_down. - Rounding times are recommended, since they prevent an abrupt response, thus avoiding detrimental effects on the mechanics. - Rounding times are not recommended when analog inputs are used, since they would result in overshoot/undershoot in the inverter response. P1131[3] Ramp-up final rounding time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines rounding time at end of ramp-up as shown in P1130 (ramp-up initial rounding time). Index:
P1131[0] : 1st. Drive data set (DDS) P1131[1] : 2nd. Drive data set (DDS) P1131[2] : 3rd. Drive data set (DDS) Details:
See parameter P1130. P1132[3] Ramp-down initial rounding time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines rounding time at start of ramp-down as shown in P1130 (ramp-up initial rounding time). Index:
P1132[0] : 1st. Drive data set (DDS) P1132[1] : 2nd. Drive data set (DDS) P1132[2] : 3rd. Drive data set (DDS) Details:
See parameter P1130.
f · f2 · f1

P1133[3] Ramp-down final rounding time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines rounding time at end of ramp-down as shown in P1130 (ramp-up initial rounding time). Index:
P1133[0] : 1st. Drive data set (DDS) P1133[1] : 2nd. Drive data set (DDS) P1133[2] : 3rd. Drive data set (DDS) Details:
See parameter P1130. P1134[3] Rounding type Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 1
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g. new setpoint, OFF1, OFF3, REV). This smoothing is applied, if the motor is ramped-up or ramped-down and - P1134 = 0, - P1132 > 0, P1133 > 0 and - the setpoint is not yet reached.
f P1132 > 0, P1133 > 0
Setpoint reached f Set
ON
OFF1
Possible Settings:
0 Continuous smoothing 1 Discontinuous smoothing Index:
P1134[0] : 1st. Drive data set (DDS) P1134[1] : 2nd. Drive data set (DDS) P1134[2] : 3rd. Drive data set (DDS) Dependency:
No effect until P1132 (Ramp-down initial rounding time) or P1133 (Ramp-down final rounding time) > 0 s.

P1135[3] OFF3 ramp-down time Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 5.00 P-Group: SETPOINT Active: first confirm QuickComm.: Yes Max: 650.00
Defines ramp-down time from maximum frequency to standstill for OFF3 command.

Index:
P1135[0] : 1st. Drive data set (DDS) P1135[1] : 2nd. Drive data set (DDS) P1135[2] : 3rd. Drive data set (DDS) Note:
This time may be exceeded if the VDC_max. level is reached. P1140[3] BI: RFG enable Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of RFG enable command (RFG: ramp function generator). If binary input is equal to zero then the RFG output will be set immediately to 0. Index:
P1140[0] : 1st. Command data set (CDS) P1140[1] : 2nd. Command data set (CDS) P1140[2] : 3rd. Command data set (CDS) P1141[3] BI: RFG start Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal to zero then the RFG output is held at it present value. Index:
P1141[0] : 1st. Command data set (CDS) P1141[1] : 2nd. Command data set (CDS) P1141[2] : 3rd. Command data set (CDS) P1142[3] BI: RFG enable setpoint Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary input is equal to zero then the RFG input will be set to zero and the RFG output will be ramp-down to zero. Index:
P1142[0] : 1st. Command data set (CDS) P1142[1] : 2nd. Command data set (CDS) P1142[2] : 3rd. Command data set (CDS) r1170 CO: Frequency setpoint after RFG Min: - Datatype: Float Unit: Hz Def: - P-Group: SETPOINT Max: -
Displays overall frequency setpoint after ramp generator.

P1200 Flying start Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 6
Starts inverter onto a spinning motor by rapidly changing the output frequency of the inverter until the actual motor speed has been found. Then, the motor runs up to setpoint using the normal ramp time.
(fmax + 2fslip nom)
'ramps to set point
as per V/f characteristic
Possible Settings:
0 Flying start disabled 1 Flying start is always active, start in direction of setpoint 2 Flying start is active if power on, fault, OFF2, start in direction of setpoint 3 Flying start is active if fault, OFF2, start in direction of setpoint 4 Flying start is always active, only in direction of setpoint 5 Flying start is active if power on, fault, OFF2, only in direction of setpoint 6 Flying start is active if fault, OFF2, only in direction of setpoint Note:
- Useful for motors with high inertia loads. - Settings 1 to 3 search in both directions. - Settings 4 to 6 search only in direction of setpoint. - Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or can be driven by the load. Otherwise, overcurrent trips will occur.

P1202[3] Motor-current: Flying start Min: 10 CStat: CUT Datatype: U16 Unit: % Def: 100 P-Group: FUNC Active: first confirm QuickComm.: No Max: 200
Defines search current used for flying start. Value is in [%] based on rated motor current (P0305). Index:
P1202[0] : 1st. Drive data set (DDS) P1202[1] : 2nd. Drive data set (DDS) P1202[2] : 3rd. Drive data set (DDS) Note:
- If the search current is reduced, the flying restart behavior can be improved if the system inertia is not very high. - The search algorithm for the flying restart is different for V/f control and closed-loop vector control. - This is the reason that, depending on the control technique, parameter P1202 must be appropriately adapted. - Values gained from experience indicate that good results can be achieved by - Increasing P1202 for V/f controls - Reducing P1202 for closed-loop vector controls P1203[3] Search rate: Flying start Min: 10 CStat: CUT Datatype: U16 Unit: % Def: 100 P-Group: FUNC Active: first confirm QuickComm.: No Max: 200
Sets factor by which the output frequency changes during flying start to synchronize with turning motor. This value is entered in [%] defines the reciprocal initial gradient in the search sequence (see curve below). Parameter P1203 influences the time taken to search for the motor frequency. The search time is the time taken to search through all frequencies between max. frequency P1082 + 2 x f_slip to 0 Hz.
P0310 100 r0330 2 P1082 f 2 + f nom slip, max ⋅ ⋅ + =
fsearch ∆f
[ms] t [%] P1203
nom slip, ⋅ ⋅ ∆ ⇒ ⋅ ⋅ ∆ ∆ =
[Hz] f [Hz] f
[%] 2 = f [%] 2 [ms] 1
0310 P 100 r0330 [%] P1203
P1203 = 100 % is defined as giving a rate of 2 % of f_slip,nom / [ms]. P1203 = 200 % would result in a rate of frequency change of 1 % of f_slip,nom / [ms]. Index:
P1203[0] : 1st. Drive data set (DDS) P1203[1] : 2nd. Drive data set (DDS) P1203[2] : 3rd. Drive data set (DDS) Example:
For a motor with 50 Hz, 1350 rpm, 100 % would produce a maximum search time of 600 ms. If the motor is turning, the motor frequency is found in a shorter time. Note:
- A higher value produces a flatter gradient and thus a longer search time. - A lower value has the opposite effect. - For closed-loop vector control, parameter P1203 is de-activated
1 ms · fmotor · t

r1204 Status word: Flying start V/f Min: - Datatype: U16 Unit: - Def: - P-Group: FUNC Max: -
Bit parameter for checking and monitoring states during search, if V/f control mode is selected (see P1300). Bitfields:
Bit00 Current applied 0 NO 1 YES Bit01 Current could not be applied 0 NO 1 YES Bit02 Voltage reduced 0 NO 1 YES Bit03 Slope-filter started 0 NO 1 YES Bit04 Current less threshold 0 NO 1 YES Bit05 Current-minimum 0 NO 1 YES Bit07 Speed could not be found 0 NO 1 YES r1205 Status word: Flying start SLVC Min: - Datatype: U16 Unit: - Def: - P-Group: FUNC Max: -
Bit parameter for checking status of flying start performed with n-adaption of observer. Parameter is only valid, if sensorless vector control (SLVC) is selected (see P1300). Bitfields:
Bit00 Transformation active 0 NO 1 YES Bit01 Initialize n-adaption 0 NO 1 YES Bit02 Current applying 0 NO 1 YES Bit03 N-controller closed 0 NO 1 YES Bit04 Isd-controller open 0 NO 1 YES Bit05 RFG hold 0 NO 1 YES Bit06 N-adaption set to zero 0 NO 1 YES Bit07 Reserved 0 NO 1 YES Bit08 Reserved 0 NO 1 YES Bit09 Reserved 0 NO 1 YES Bit10 Direction Positive 0 NO 1 YES Bit11 Search is started 0 NO 1 YES Bit12 Current is applied 0 NO 1 YES Bit13 Search is aborted 0 NO 1 YES Bit14 Deviation is zero 0 NO 1 YES Bit15 N-controller is active 0 NO 1 YES

P1210 Automatic restart Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: FUNC Active: first confirm QuickComm.: No Max: 6
Configures automatic restart function Possible Settings:
0 Disabled 1 Trip reset after power on, P1211 disabled 2 Restart after mains blackout, P1211 disabled 3 Restart after mains brownout or fault, P1211 enabled 4 Restart after mains brownout, P1211 enabled 5 Restart after mains blackout and fault, P1211 disabled 6 Restart after mains brown- /blackout or fault P1211 disabled Dependency:
Automatic restart requires constant ON command via a digital input wire link. Caution:
P1210 > 2 can cause the motor to restart automatically without toggling the ON command ! Notice:
A "mains brownout" is where the power in interrupted and re-applied before the display on the BOP (if one is fitted to the inverter) has gone dark (a very short mains break where the DC link has not fully collapsed).
A "mains blackout" is where the display has gone dark (a long mains break where the DC link has fully collapsed) before the power is re-applied.
P1210 = 0: Automatic restart is disabled.
P1210 = 1: The inverter will acknowledge (reset) faults i.e. it will reset a fault when the is re-applied. This means the inverter must be fully powered down, a brownout is not sufficed. The inverter will not run until the ON command has been toggled.
P1210 = 2: The inverter will acknowledge the fault F0003 at power on after blackout and restarts the drive. It is necessary that the ON command is wired via digital input (DIN).
P1210 = 3: For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the faults (F0003, etc.). The inverter will acknowledge the fault and restarts the drive after a blackout or bronwout. It is necessary that the ON command is wired via digital input (DIN).
P1210 = 4: For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the fault (F0003). The inverter will acknowledge the fault and restarts the drive after a blackout or bronwout. It is necessary that the ON command is wired via digital input (DIN).
P1210 = 5: The inverter will acknowledge the faults F0003 etc. at power on after blackout and restarts the drive. It is necessary that the ON command is wired via digital input (DIN).
P1210 = 6: The inverter will acknowledge the faults (F0003 etc.) at power on after blackout or brownout and restarts the drive. It is necessary that the ON command is wired via digital input (DIN). Setting 6 causes the motor to restart immediately. Following table presents an overview of parameter P1210 and its functionality.

ON always active (permanent) P1210 ON in no-voltage condition
Fault F0003 on All other faults on Brownout Blackout Brownout Blackout
0 −
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
2 + − − −
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
+ Fault acknowl.
3 +
Fault acknowl.
Fault acknowl.
4 + + − − −
Fault acknowl.
Fault acknowl.
Fault acknowl.
5 + − + +
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
6 +
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or can be driven by the load (P1200). P1211 Number of restart attempts Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 3 P-Group: FUNC Active: first confirm QuickComm.: No Max: 10
Specifies number of times inverter will attempt to restart if automatic restart P1210 is activated.

P1215 Holding brake enable Min: 0 CStat: T Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 1
Enables/disables holding brake function. This function applies the following profile to the inverter:
ON / OFF1/OFF3:

1 r0052.C Bit 12
Brake Release Time Brake Closing Time
ON / OFF2:

OFF1/OFF3
1 r0052.C Bit 12
Possible Settings:
Brake Release Time Brake Closing Time
0 Motor holding brake disabled 1 Motor holding brake enabled

1. To activate the motor holding brake, in addition to parameter P1215 = 1, the status signal r0052 bit 12 "motor holding brake active" must be output via a digital output. The user must also select the signal - e.g. in parameter P0731. 2. If the motor holding brake is controlled by the drive inverter, then for potentially hazardous loads (e.g. suspended/hanging loads for crane applications) the drive inverter may not be conditioned unless the load has been secured. Before commissioning, potentially hazardous loads can be secured as follows: - lower the load to the floor, or - during commissioning or after replacing the drive inverter, prevent the drive inverter from controlling the motor holding brake. Only then should STARTER be used to carry-out a quick commissioning or a parameter download, etc. The motor holding brake terminals can then be re-used (for the motor holding brake, in this case, it is not permissible to parameterize the system so that the digital output P0748 is inverted). 3. In order to hold the motor against the mechanical brake at a certain frequency, it is important that the min. frequency P1080 approximately corresponds to the slip frequency. - If the value is selected to be too high, then the current drawn can be too high so that the drive inverter trips (shuts down) due to an overcurrent condition. - For a low value, it is possible that the torque cannot be established to hold the load. 4. It is not permissible to use the motor holding brake as operating brake as generally it is only designed and dimensioned for a limited number of emergency braking operations. Note:
Parameter settings: - To open/close, a digital output controls the motor holding brake at point 1/2 (refer to the diagram). In this case, as prerequisite, the motor holding brake P1215 must be activated as well as the motor holding brake selected at the digital output. - Brake opening time P1216 greater than/equal to the time for the holding brake to open. - Brake delay time P1217 greater than/equal to the time to close the holding brake. - Select the minimum frequency P1080 so that it acts like weight equalization. - A typical value of the minimum frequency P1080 for the motor holding brake is the slip frequency of the motor r0330. The rated slip frequency can be calculated using the following formula:
n n P0310 100 r0330 [Hz] f ⋅ − = ⋅ =
n n sy Slip f n
The following closed-loop control parameters should be observed in conjunction with the motor holding brake: - P1310, P1311, P1333, P1335 for U/f - P1610, P1611, P1750, P1755 for SLVC P1216 Holding brake release delay Min: 0.0 CStat: T Datatype: Float Unit: s Def: 1.0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 20.0
Defines the brake opening time of the motor holding brake (MHB). When the motor holding brake (P1215) is activated, then the setpoint enable is delayed by the selected time. The time that it takes to open the mechanical brake is subject to certain fluctuations. This is the reason that the drive inverter applies the min. frequency P1080 to the motor during this time. This means that the brake can reliably open before the motor starts.
Release time of the brake + relay opening time(s) P1216 ≥ Details:
See parameter P1215. P1217 Holding time after ramp down Min: 0.0 CStat: T Datatype: Float Unit: s Def: 1.0 P-Group: FUNC Active: first confirm QuickComm.: No Max: 20.0
Defines the brake delay time of the motor holding brake (MHB). When the motor holding brake (P1215) is activated, after an off command, the pulse inhibit is delayed by this selected time. The time that it takes to open the mechanical brake is subject to certain fluctuations. This means that after braking to the min. frequency P1080, the motor is held at the minimum frequency for this time. This means that the brake can reliably close before the motor is switched into a no-current condition.
Application time of the brake + relay closing time P1217 ≥ Details:
See parameter P1215.
n n sy

P1230[3] BI: Enable DC braking Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Enables DC braking via a signal applied from an external source. Function remains active while external input signal is active. DC braking causes the motor to stop rapidly by applying a DC braking current (current applied also holds shaft stationary). When the DC braking signal is applied, the inverter output pulses are blocked and the DC current is not applied until the motor has been sufficiently demagnetized.
P1230.C BI: Enable DC brk.
(0:0)
P1230[0] : 1st. Command data set (CDS) P1230[1] : 2nd. Command data set (CDS) P1230[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) Caution:
With the DC braking, the kinetic energy of the motor is converted into heat in the motor. The drive could overheat if the remains in this status for an exessive period of time ! DC braking is not possible when using a synchronous motor (i.e. P0300 = 2). Notice:
This delay time is set in P0347 (demagnetization time). If this delay is too short, overcurrent trips can occur.

P1232[3] DC braking current Min: 0 CStat: CUT Datatype: U16 Unit: % Def: 100 P-Group: FUNC Active: Immediately QuickComm.: No Max: 250
Defines level of DC current in [%] relative to rated motor current (P0305).
1 [A] r0027 Brake DC ⋅ ⋅ ≈ −
The current of the DC-braking is limited by r0067. Index:
P1232[0] : 1st. Drive data set (DDS) P1232[1] : 2nd. Drive data set (DDS) P1232[2] : 3rd. Drive data set (DDS) P1233[3] Duration of DC braking Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: FUNC Active: Immediately QuickComm.: No Max: 250.00
Defines duration for which DC injection braking is to be active following an OFF1 or OFF3 command. When an OFF1 or OFF3 command is received by the drive, the output frequency starts to ramp to 0 Hz. When the output frequency reaches the value set in P1234, the drive injects a DC braking current P1232 for the time duration set in P1233.

The DC current, that is impressed during time P1233, is specified by parameter P1232.

Index:
P1233[0] : 1st. Drive data set (DDS) P1233[1] : 2nd. Drive data set (DDS) P1233[2] : 3rd. Drive data set (DDS) Value:
P1233 = 0.00 : Not active following OFF1 / OFF3. P1233 = 0.01 - 250.00 : Active for the specified duration. Caution:
With the DC braking, the kinetic energy of the motor is converted into heat in the motor. The drive could overheat if the remains in this status for an exessive period of time ! DC braking is not possible when using a synchronous motor (i.e. P0300 = 2). Notice:
The DC braking function causes the motor to stop rapidly by applying a DC braking current (the current applied also holds the shaft stationary). When the DC braking signal is applied, the inverter output pulses are blocked and the DC current not applied until the motor has been sufficiently demagnetized. Demagnetization time is calculated automatically from motor data. The inverter will not restart if an ON-command is given during this period. P1234[3] DC braking start frequency Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 650.00 P-Group: FUNC Active: Immediately QuickComm.: No Max: 650.00
Sets start frequency for DC braking. When an OFF1 or OFF3 command is received by the drive, the output frequency starts to ramp to 0 Hz. When the output frequency reaches the value set in start frequency of DC braking P1234, the drive injects a DC braking current P1232 for the time duration set in P1233. Index:
P1234[0] : 1st. Drive data set (DDS) P1234[1] : 2nd. Drive data set (DDS) P1234[2] : 3rd. Drive data set (DDS) Details:
See P1232 (DC braking current) and P1233 (duration of DC braking)

P1236[3] Compound braking current Min: 0 CStat: CUT Datatype: U16 Unit: % Def: 0 P-Group: FUNC Active: Immediately QuickComm.: No Max: 250
Defines DC level superimposed on AC waveform after exeeding DC-link voltage threshold of compound braking. The value is entered in [%] relative to rated motor current (P0305).
Compound braking switch-on level P0210 2 13 . 1 V 2 1.13 U mains DC_Comp ⋅ ⋅ = ⋅ ⋅ = If P1254 = 0 :
1242 r 0.98 UDC_Comp ⋅ = Compound braking switch-on level otherwise :
The Compound Brake is an overlay of the DC brake function with regenerative braking (effective braking at the ramp) after OFF1 or OFF3. This enables braking with controlled motor frequency and a minimum of energy returned to the motor. Through optimization of the ramp-down time and the compound braking an efficient braking without additional HW components is possible.
P1236 = 0 Without Compound braking
P1236 > 0 With Compound braking
Index:
P1236[0] : 1st. Drive data set (DDS) P1236[1] : 2nd. Drive data set (DDS) P1236[2] : 3rd. Drive data set (DDS) Value:
P1236 = 0 : Compound braking disabled. P1236 = 1 - 250 : Level of DC braking current defined as a [%] of rated motor current (P0305). Dependency:
Compound braking depends on the DC link voltage only (see threshold above). It will be active with OFF1/OFF3 and at regenerating conditions. It is disabled, when: - DC braking is active - Flying start is active - Vector mode (SLVC, VC) is selected Notice:
Increasing the value will generally improve braking performance; however, if you set the value too high, an overcurrent trip may result. If used with dynamic braking enabled as well compound braking will take priority. If used with the Vdc max controller enabled the drive behaviour whilst braking may be worsened paticularly with high values of compound braking. Compound braking does not function when the drive is in vector control.

P1237 Dynamic braking Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: Immediately QuickComm.: No Max: 5
Dynamic braking absorbs the braking energy. This parameter activates the function "Dynamic braking" and defines the rated duty cycle of the braking resistor (chopper resistor). Dynamic braking is active when the function is enabled and DC-link voltage exeeds the dynamic braking switch-on level, see below. If a motor is quickly ramped down by the inverter or a big load is dropped by a lifting application, the motor works in regenerating mode and saves energy back to the inverter. In this case the DC-link voltage of the inverter raises. If that voltage gets too high (overvaltage , F0002), the inverter pulses are disabled and the motor coasts to standstill. With dynamic braking the regenerative energy is fed by the chopper to the external braking resistor and converted into heat. So it is possible to brake down the drive in a controlled way.
Dynamic braking switch-on level
0210 P 2 13 . 1 V 2 13 . 1 V mains Chopper , DC ⋅ ⋅ = ⋅ ⋅ = If P1254 = 0 :
otherwise :
1242 r 98 . 0 V Chopper , DC ⋅ =
Possible Settings:
0 Disabled 1 5 % duty cycle 2 10 % duty cycle 3 20 % duty cycle 4 50 % duty cycle 5 100 % duty cycle Dependency:
This function is not available for for MM440 PX (FSFX and FSGX). If used with DC braking enabled as well compound braking will take priority.
braking P1236 > 0
braking P1237 > 0
Initially the brake will operate at a high duty cycle dependant on the DC link level until the thermal limit is approached. The duty cycle specified by this parameter will then be imposed. The resistor should be able to operate at this level indefinitely without overheating.
B+
B-
= ~
=
~
~

t Chopper , ON
Chopper t f 1 =
tChopper , ON t 100 x ⋅ = Chopper
Alarm A0535 Duty cycle monitoring
380 - 480 V
500 - 600 V
21.3 V The threshold for the warning A0535 is equivalent to 10 seconds running at 95 % duty cycle. The duty cycle will be limited when it was running 12 seconds at 95 % duty cycle.
3.28 Vdc controller
P1240[3] Configuration of Vdc controller Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: FUNC Active: Immediately QuickComm.: No Max: 3
Enables / disables Vdc controller. The Vdc controller dynamically controls the DC link voltage to prevent overvoltage trips on high inertia systems. Possible Settings:
0 Vdc controller disabled 1 Vdc-max controller enabled 2 Kinetic buffering (Vdc-min controller) enabled 3 Vdc-max controller and kinetic buffering (KIB) enabled Index:
P1240[0] : 1st. Drive data set (DDS) P1240[1] : 2nd. Drive data set (DDS) P1240[2] : 3rd. Drive data set (DDS)

If P1245 increased too much, it may interfere with the drive normal operation. Note:
Vdc max controller automatically increases ramp-down times to keep the DC-link voltage (r0026) within limits (r1242). Vdc min is activated if DC-link voltage falls below the switch on level,P1245. The kinetic energy of the motor is then used to buffer the DC-link voltage, thus causing deceleration of the drive. If the drive trips F0003 immediately, try increasing the dynamic factor first, P1247. If still tripping F0003 try then increasing the switch on level, P1245. r1242 CO: Switch-on level of Vdc-max Min: - Datatype: Float Unit: V Def: - P-Group: FUNC Max: -
Displays switch-on level of Vdc max controller.
-controller active VDC_max
Following equation is only valid , if P1254 = 0 :
0210 P 2 15 . 1 V 2 1.15 = r1242 mains ⋅ =
otherwise :
r1242 is internally calculated Note:
Parameter r1242 (switch-in threshold) is determined by each power cycle, when precharging of the DC-link is finished. P1243[3] Dynamic factor of Vdc-max Min: 10 CStat: CUT Datatype: U16 Unit: % Def: 100 P-Group: FUNC Active: Immediately QuickComm.: No Max: 200
Defines dynamic factor for DC link controller in [%]. Index:
P1243[0] : 1st. Drive data set (DDS) P1243[1] : 2nd. Drive data set (DDS) P1243[2] : 3rd. Drive data set (DDS) Dependency:
P1243 = 100 % means parameters P1250, P1251 and P1252 (gain, integration time and differential time) are used as set. Otherwise, these are multiplied by P1243 (dynamic factor of Vdc-max). Note:
Vdc controller adjustment is calculated automatically from motor and inverter data.

P1245[3] Switch on level kin. buffering Min: 65 CStat: CUT Datatype: U16 Unit: % Def: 76 P-Group: FUNC Active: Immediately QuickComm.: No Max: 115
Enter switch-on level for kinetic buffering (KIB) in [%] relative to supply voltage (P0210).
P0210 2 100 [%] P1245 = [V] P1245 ⋅ ⋅
Index:
P1245[0] : 1st. Drive data set (DDS) P1245[1] : 2nd. Drive data set (DDS) P1245[2] : 3rd. Drive data set (DDS) Warning:
Increasing the value too much, may interfere with the drive normal operation. Note:
Changing P1254 does not affect the switch-on-level for KIB. r1246[3] CO:Switch-on level kin buffering Min: - Datatype: Float Unit: V Def: - P-Group: FUNC Max: -
Displays switch-on level of kinetic buffering (KIB, Vdc min controller). Depending on the setting selected, the frequency limit defined in P1245 is used to either hold the speed or disable pulses. If not enough regeneration is produced, drive may trip undervoltage. P1247[3] Dyn. factor of kinetic buffering Min: 10 CStat: CUT Datatype: U16 Unit: % Def: 100 P-Group: FUNC Active: Immediately QuickComm.: No Max: 200
Enters dynamic factor for kinetic buffering (KIB, Vdc-min controller). P1247 = 100 % means parameters P1250, P1251 and P1252 (gain, integration time and differential time) are used as set. Otherwise, these are multiplied by P1247 (dynamic factor of Vdc-min). Index:
P1247[0] : 1st. Drive data set (DDS) P1247[1] : 2nd. Drive data set (DDS) P1247[2] : 3rd. Drive data set (DDS) Note:
Vdc controller adjustment is calculated automatically from motor and inverter data. P1250[3] Gain of Vdc-controller Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 1.00 P-Group: FUNC Active: Immediately QuickComm.: No Max: 10.00
Enters gain for Vdc controller. Index:
P1250[0] : 1st. Drive data set (DDS) P1250[1] : 2nd. Drive data set (DDS) P1250[2] : 3rd. Drive data set (DDS) P1251[3] Integration time Vdc-controller Min: 0.1 CStat: CUT Datatype: Float Unit: ms Def: 40.0 P-Group: FUNC Active: Immediately QuickComm.: No Max: 1000.0
Enters integral time constant for Vdc controller. Index:
P1251[0] : 1st. Drive data set (DDS) P1251[1] : 2nd. Drive data set (DDS) P1251[2] : 3rd. Drive data set (DDS) P1252[3] Differential time Vdc-controller Min: 0.0 CStat: CUT Datatype: Float Unit: ms Def: 1.0 P-Group: FUNC Active: Immediately QuickComm.: No Max: 1000.0
Enters differential time constant for Vdc controller. Index:
P1252[0] : 1st. Drive data set (DDS) P1252[1] : 2nd. Drive data set (DDS) P1252[2] : 3rd. Drive data set (DDS)

P1253[3] Vdc-controller output limitation Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 10.00 P-Group: FUNC Active: Immediately QuickComm.: No Max: 600.00
Limits maximum effect of Vdc max controller. Index:
P1253[0] : 1st. Drive data set (DDS) P1253[1] : 2nd. Drive data set (DDS) P1253[2] : 3rd. Drive data set (DDS) P1254 Auto detect Vdc switch-on levels Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: FUNC Active: Immediately QuickComm.: No Max: 1
Enables/disables auto-detection of switch-on levels for Vdc control functionalities. Following switch-on levels are calculated
- Switch-on level chopper
- Switch-on level compound brake - Switch-on level Vdc_max controller r1242 P1254 does not have any effect on the
- Switch-on level kin. buffering r1246 Possible Settings:
0 Disabled 1 Enabled Note:
The switch-on thresholds are only calculated during the start-up of the inverter after connection to the mains. An online-adaption is not performed during operation. This means that modification of P1254 does not immediately take effect and variations in the mains are also not initially taken into account. P1254 = 0 (Automatic Detection disabled): The above thresholds are calculated via P0210, if automatic detection is disabled. P1256[3] Reaction of kinetic buffering Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: FUNC Active: Immediately QuickComm.: No Max: 2
Enters reaction for kinetic buffering controller (Vdc-min controller). Depending on the setting selected, the frequency limit defined in P1257 is used to either hold the speed or disable pulses. If not enough regeneration is produced, drive may trip undervoltage. Possible Settings:
0 Maintain DC-link until trip 1 Maintain DC-link until trip / stop 2 Control stop Index:
P1256[0] : 1st. Drive data set (DDS) P1256[1] : 2nd. Drive data set (DDS) P1256[2] : 3rd. Drive data set (DDS) Note:
P1256 = 0: Maintain dclink voltage until mains is returned or drive is tripped undervoltage. The frequency is kept above the frequency limit provided in P1257.

P1256 = 1: Maintain dclink voltage until mains is returned or drive is tripped undervoltage or pulses disabled when frequency falls below the limit in P1257.
P1256 = 2: This option ramps down the frequency to stand still even when mains return. If mains return, then an OFF1 is active until P1257 limit then pulses disabled. If mains does not return, frequency brought down under the control of vdc-min controller until P1257 limit then pulses disabled or undervoltage has occurred.
OFF1
OFF2
P1257[3] Freq limit for kinetic buffering Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 2.50 P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 600.00
Frequency which kinetic buffering (KIB) either hold speed or disable pulses depending on P1256. Index:
P1257[0] : 1st. Drive data set (DDS) P1257[1] : 2nd. Drive data set (DDS) P1257[2] : 3rd. Drive data set (DDS)

P1300[3] Control mode Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: CONTROL Active: first confirm QuickComm.: Yes Max: 23
Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram below.
f0 0 Hz f2 P1322
Possible Settings:
0 V/f with linear characteristic 1 V/f with FCC 2 V/f with parabolic characteristic 3 V/f with programmable characteristic 4 Reserved 5 V/f for textile applications 6 V/f with FCC for textile applications 19 V/f control with independent voltage setpoint 20 Sensorless vector control 21 Vector control with sensor 22 Sensorless vector torque-control 23 Vector torque-control with sensor Index:
P1300[0] : 1st. Drive data set (DDS) P1300[1] : 2nd. Drive data set (DDS) P1300[2] : 3rd. Drive data set (DDS) Dependency:
See parameter P0205, P0500 Caution:
When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in - sign and - magnitude (with a deviation of only a few percent). Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23). P0400 = 1 (single channel encoder) will only allow operation in one direction. If operation in both directions is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating Instructions of the encoder module for more information. Note:
P1300 = 1 : V/f with FCC (flux current control) - Maintains motor flux current for improved efficiency. - If FCC is chosen, linear V/f is active at low frequencies. P1300 = 2 : V/f with a quadratic characteristic - Suitable for centrifugal fans / pumps P1300 = 3 : V/f with a programmable characteristic - User defined characteristic (see P1320) - For synchronous motors (e.g. SIEMOSYN motors) P1300 = 5,6 : V/f for textil applications - Slip compensation disabled. - Imax controller modifies the output voltage only. - Imax controller does not influence the output frequency.

P1300 = 19 : V/f control with independent voltage setpoint The following table presents an overview of control parameters (V/f) that can be modify in relationship to P1300 dependencies:
ParNo. Level
0 1 2 3 5 6 19 20 22 21 23
P1300[3] 2 x
Control mode Continuous boost
P1310[3] 2 x − P1311[3] 2 x − P1312[3] 2 x − P1316[3] 3 x − P1320[3] 3 − − − x − P1321[3] 3 − − − x − P1322[3] 3 − − − x − P1323[3] 3 − − − x − P1324[3] 3 − − − x − P1325[3] 3 − − − x − P1330[3] 3 − x − P1333[3] 3 − x − − − x − P1335[3] 2 x − P1336[3] 2 x − P1338[3] 3 x − P1340[3] 3 x − P1341[3] 3 x − P1345[3] 3 x − P1346[3] 3 x − P1350[3] 3 x −
Acceleration boost Starting boost
Boost end frequency Programmable V/f freq. coord. 1
Programmable V/f volt. coord. 1 Programmable V/f freq. coord. 2
Programmable V/f volt. coord. 2 Programmable V/f freq. coord. 3
Programmable V/f volt. coord. 3
Start frequency for FCC Slip compensation CO: U/f Slip limit
Resonance damping gain V/f Imax freq. controller prop. gain
Imax controller integral time Imax controller prop. gain
Imax voltage ctrl. integral time Voltage soft start
SLVC / VC can provide excellent performance for the following types of application: - Applications which require high torque performance - Applications which require fast respond to shock loading - Applications which require torque holding while passing through 0 Hz - Applications which require very accurate speed holding - Applications which require motor pull out protection SLVC/VC-Restrictions: - SLVC / VC is dependent on the accuracy of the motor model being used and the measurements being performed by the inverter. There are therefore certain restrictions on the use of SLVC / VC:
(max. frequency) fmax = min(200 Hz, 5 P0310)
P0305 4 1 ≤ ≤ (ratio of rated motor current to rated inverter current)
no synchronuos motor Recommended means of SLVC/VC-commissioning: - For correct operation under SLVC / VC control it is imperative that the name plate data of the motor (P0304 - P0310) is correctly entered and that the motor data identification (P1910) must be carried out on a cold motor. It is also necessary to ensure that the motor ambient temperature is correctly entered in P0625 if this is significantly different from the default value of 20°C. This must be done after the quick commissioning has been completed (P3900) but before the motor data identification measurements are carried out. - See parameter P0400 and documentation of encoder and encoder module when commissioning VC (P1300 = 21 or 23). SLVC/VC-Optimisation: The following parameters can be adjusted by the user to improve performance. - P0003 = 3 - P0342: Total / motor inertia ratio Sensorless Vector Control (SLVC): - P1470: P gain (SLVC) - P1472: I term (SLVC) - P1610: Continuous torque boost (SLVC, open loop boost) - P1611: Acceleration torque boost (SLVC, open loop boost) - P1750: Control word of motor model - P1755: Start-frequency motor model (SLVC)

Vector Control (VC): - P1460: P gain - P1462: I term The following table presents an overview of control parameters (SLVC, VC) that can be modify in relationship to P1300 dependencies:
ParNo. Le ve l
P1300 = Parameter name
V C V/f SLVC
0 1 2 3 5 6 19 20 22 21 23
P1400[3] 3 − x − P1442[3] 3 − x − P1452[3] 3 − x − − − P1460[3] 2 − x − P1462[3] 2 − x − P1470[3] 2 − x − − − P1472[3] 2 − x − − − P1477[3] 3 − x − x − P1478[3] 3 − x − x − P1488[3] 3 − x − x − P1489[3] 3 − x − x − P1492[3] 3 − x − x − P1496[3] 3 − x − x − P1499[3] 3 − x − −
Configuration of speed control Filter time for act. speed Filter time for act.speed (SLVC) Gain speed controller Integral time speed controller Gain speed controller (SLVC) Integral time n-ctrl. (SLVC) BI: Set integrator of n-ctrl. CI: Set integrator value n-ctrl. Droop input source Droop scaling Enable droop Scaling accel. precontrol Scaling accel. torque control
P1500[3] 2 − x
Selection of torque setpoint BI: Change to torque control CI: Torque setpoint CI: Additional torque setpoint CO: Upper torque limit CO: Lower torque limit CI: Upper torque limit CI: Lower torque limit Scaling lower torque limit Motoring power limitation Regenerative power limitation CO: Fixed value flux setpoint Dynamic voltage headroom Efficiency optimization Smooth time for flux setpoint Int. time field weak. controller Continuous torque boost (SLVC) Acc. torque boost (SLVC) Gain for oscillation damping Control word of motor model Start-freq. motor model (SLVC) Hyst.-freq. motor model (SLVC) T(wait) transit to feed-fwd-mode T(wait) for n-adaption to settle Kp of n-adaption (SLVC) Control word of Rs/Rr-adaption
P1501[3] 3 − x
P1503[3] 3 − x − x
P1511[3] 3 − x
P1520[3] 2 − x
P1521[3] 2 − x
P1522[3] 3 − x
P1523[3] 3 − x
P1525[3] 3 − x
P1530[3] 2 − x
P1531[3] 2 − x
P1570[3] 2 − x
P1574[3] 3 − x
P1580[3] 2 − x
P1582[3] 3 − x
P1596[3] 3 − x
P1610[3] 2 − x x − − P1611[3] 2 − x x − − P1740 3 − x x − − P1750[3] 3 − x
P1755[3] 3 − x x − − P1756[3] 3 − x x − − P1758[3] 3 − x x − − P1759[3] 3 − x x − − P1764[3] 3 − x x − − P1780[3] 3 − x x − −
P0400[3] 2 − x x
Select encoder type Encoder pulses per revolution Reaction on speed signal loss Allowed speed difference Delay speed loss reaction
P0408[3] 2 − x x
P0491[3] 2 − x x
P0492[3] 2 − x x
P0494[3] 2 − x x

P1310[3] Continuous boost Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 50.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 250.0
P1310 causes a voltage boost depending on the output frequency (see diagran). At low output frequencies the output voltage is low to keep the flux level constant. However, the output voltage may be too low - for magnetisation the asynchronous motor - to hold the load - to overcome losses in the system. To compensate these effects, the output voltage can be increased using parameter P1310. Defines boost level in [%] relative to P0305 (rated motor current) applicable to both linear and quadratic V/f curves according to the diagram below:
OFF
ON
OFF
where voltage values are given
100 P1310 0350 P 0305 P V 100 , ConBoost ⋅ ⋅ =
2 V 00 ConBoost,1 0 ConBoost,5 V =
Index:
P1310[0] : 1st. Drive data set (DDS) P1310[1] : 2nd. Drive data set (DDS) P1310[2] : 3rd. Drive data set (DDS)

Dependency:
Continous boost P1310 has no effect during vector operation because the inverter calculates continously the optimum operating conditions. Note:
- Increasing the boost levels increases motor heating (especially at standstill). - The boost values are combined when continuous boost (P1310) used in conjunction with other boost parameters (acceleration boost P1311 and starting boost P1312). - However priorities are allocated to these parameters as follows: P1310 > P1311 > P1312 - The total boost is limited by following equation:
∑ P0350 P0305 3 I R 3 V Mot s Boost ⋅ ⋅ = ⋅ ⋅ ≤
- Setting in P0640 (motor overload factor [%]) limits the boost:
V Boost ≤ ⋅ P1311[3] Acceleration boost Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 250.0
P1311 will only produce boost during ramping, and is therefore useful for additional torque during acceleration and deceleration. Contrary to P1312, that is only active when an ON command is given, p1311 is active after each acceleration resp. deceleration. The boost is active, if P1311 > 0 resp. if the conditiones given below are fulfilled. Applies boost in [%] relative to P0305 (rated motor current) following a positive setpoint change and drops back out once the setpoint is reached. It is activated when the setpoint changes and deactivated when the setpoint is reached.
Boost voltage Validity range
OFF
where voltage values are given
100 P1311 0350 P 0305 P V 100 , AccBoost ⋅ ⋅ =
00 AccBoost,1 0 AccBoost,5 =
Index:
P1311[0] : 1st. Drive data set (DDS) P1311[1] : 2nd. Drive data set (DDS) P1311[2] : 3rd. Drive data set (DDS) Dependency:
Acceleration boost P1311 has no effect during vector operation. Note:

P1312[3] Starting boost Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 250.0
Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either linear or quadratic) after an ON command and is active until 1) ramp output reaches setpoint for the first time respectively 2) setpoint is reduced to less than present ramp output This is useful for starting loads with high inertia. Setting the starting boost (P1312) too high will cause the inverter to limit the current, which will in turn restrict the output frequency to below the setpoint frequency.
OFF
where voltage values are given
100 P1312 0350 P 0305 P V 100 , StartBoost ⋅ ⋅ =
,100 StartBoost ,50 StartBoost =
Index:
P1312[0] : 1st. Drive data set (DDS) P1312[1] : 2nd. Drive data set (DDS) P1312[2] : 3rd. Drive data set (DDS) Example:
Setpoint = 50Hz. Ramping up with starting boost. During ramp up, setpoint changed to 20Hz. As soon as setpoint changed, starting boost removed because setpoint smaller than present ramp output. Dependency:
Acceleration boost P1312 has no effect during vector operation. Note:
See parameter P1310 r1315 CO: Total boost voltage Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays total value of voltage boost (in volts).

P1316[3] Boost end frequency Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 20.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 100.0
Defines point at which programmed boost reaches 50 % of its value. This value is expressed in [%] relative to P0310 (rated motor frequency). The default frequency is defined as follows:
153 ( 2 = f
motor min Boost + ⋅
Index:
P1316[0] : 1st. Drive data set (DDS) P1316[1] : 2nd. Drive data set (DDS) P1316[2] : 3rd. Drive data set (DDS) Note:
- The expert user may change this value to alter the shape of the curve, e.g. to increase torque at a particular frequency. - Default value is depending on inverter type and its rating data. Details:
See diagram in P1310 (continuous boost). P1320[3] Programmable V/f freq. coord. 1 Min: 0.00 CStat: CT Datatype: Float Unit: Hz Def: 0.00 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 650.00
Sets V/f coordinates (P1320/1321 to P1324/1325) to define V/f characteristic.
Vmax = f(Vdc, Mmax)
f0 0 Hz f2 P1322
] P0304[V 100[%] r0395[%] 100[%] P1310[%] P1310[V] ⋅ ⋅ =
Index:
P1320[0] : 1st. Drive data set (DDS) P1320[1] : 2nd. Drive data set (DDS) P1320[2] : 3rd. Drive data set (DDS) Example:
This parameter can be used to provide correct torque at correct frequency and is useful when used with synchronous motors. Dependency:
To set parameter, select P1300 = 3 (V/f with programmable characteristic). Note:
Linear interpolation will be applied between the individual data points. V/f with programmable characteristic (P1300 = 3) has 3 programmable points. The two non-programmable points are: - Continuous boost P1310 at zero 0 Hz - Rated motor voltage P0304 at rated motor frequency P0310 The acceleration boost and starting boost defined in P1311 and P1312 are applied to V/f with programmable characteristic.

P1321[3] Programmable V/f volt. coord. 1 Min: 0.0 CStat: CUT Datatype: Float Unit: V Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 3000.0
See P1320 (programmable V/f freq. coord. 1). Index:
P1321[0] : 1st. Drive data set (DDS) P1321[1] : 2nd. Drive data set (DDS) P1321[2] : 3rd. Drive data set (DDS) P1322[3] Programmable V/f freq. coord. 2 Min: 0.00 CStat: CT Datatype: Float Unit: Hz Def: 0.00 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 650.00
See P1320 (programmable V/f freq. coord. 1). Index:
P1322[0] : 1st. Drive data set (DDS) P1322[1] : 2nd. Drive data set (DDS) P1322[2] : 3rd. Drive data set (DDS) P1323[3] Programmable V/f volt. coord. 2 Min: 0.0 CStat: CUT Datatype: Float Unit: V Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 3000.0
See P1320 (programmable V/f freq. coord. 1). Index:
P1323[0] : 1st. Drive data set (DDS) P1323[1] : 2nd. Drive data set (DDS) P1323[2] : 3rd. Drive data set (DDS) P1324[3] Programmable V/f freq. coord. 3 Min: 0.00 CStat: CT Datatype: Float Unit: Hz Def: 0.00 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 650.00
See P1320 (programmable V/f freq. coord. 1). Index:
P1324[0] : 1st. Drive data set (DDS) P1324[1] : 2nd. Drive data set (DDS) P1324[2] : 3rd. Drive data set (DDS) P1325[3] Programmable V/f volt. coord. 3 Min: 0.0 CStat: CUT Datatype: Float Unit: V Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 3000.0
See P1320 (programmable V/f freq. coord. 1). Index:
P1325[0] : 1st. Drive data set (DDS) P1325[1] : 2nd. Drive data set (DDS) P1325[2] : 3rd. Drive data set (DDS) P1330[3] CI: Voltage setpoint Min: 0:0 CStat: T Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
BICO parameter for selecting source of voltage setpoint for independent V/f control. Index:
P1330[0] : 1st. Command data set (CDS) P1330[1] : 2nd. Command data set (CDS) P1330[2] : 3rd. Command data set (CDS)

P1333[3] Start frequency for FCC Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 10.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 100.0
Defines the FCC starting frequency as a percentage of the rated motor frequency (P0310). When FCC is activated using P1300 = 1, then as a function of the FCC starting frequency plus hysteresis and the actual frequency, a changeover is made with a continuous transition between the linear V/f characteristic (P1300 = 0) and FCC (refer to the diagram).
1333 P 100 P0310 fFCC ⋅ =
( ) % 6 1333 P 100 P0310 f Hys FCC + ⋅ = +
fFCC f fFCC+Hys
Index:
P1333[0] : 1st. Drive data set (DDS) P1333[1] : 2nd. Drive data set (DDS) P1333[2] : 3rd. Drive data set (DDS) Notice:
- A value that is excessively low can result in instability. - The constant voltage boost P1310 is continuously de-activated - essentially the same as when switching-in FCC. - Contrary, the voltage boosts P1311 and P1312 remain active over the complete frequency range.
Switch-over · V/f

P1335[3] Slip compensation Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 600.0
Dynamically adjusts output frequency of inverter so that motor speed is kept constant independent of motor load. In the V/f-control, the motor speed will always be less than the command speed due to the slip speed. For a given speed command, the speed will drop as load is increased. The speed regulation of drive can be improved by the technique known as slip compensation. Increasing the load from M1 to M2 (see diagram) will decrease the motor speed from f1 to f2, due to the slip. The inverter can compensate for this by increasing the output frequency slightly as the load increases. The inverter measures the current and increases the output frequency to compensate for the expected slip.
M
M 2
M 2
M 1
M 1
f ∆f f2 f1
f ∆f f2 f1
Index:
P1335[0] : 1st. Drive data set (DDS) P1335[1] : 2nd. Drive data set (DDS) P1335[2] : 3rd. Drive data set (DDS) Value:
P1335 = 0 % : Slip compensation disabled. P1335 = 50 % - 70 % : Full slip compensation at cold motor (partial load). P1335 = 100 % : Full slip compensation at warm motor (full load).
Range of slip compensation :
out 6 % 10 %
set 6 % 10 %
N
The applied value of the slip compensation (scaled by P1335) is limited by following equation:
r0330 100 P1336 f max Slip_comp_ ⋅ =

P1336[3] Slip limit Min: 0 CStat: CUT Datatype: U16 Unit: % Def: 250 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 600
Compensation slip limit in [%] relative to r0330 (rated motor slip), which is added to frequency setpoint. Index:
P1336[0] : 1st. Drive data set (DDS) P1336[1] : 2nd. Drive data set (DDS) P1336[2] : 3rd. Drive data set (DDS) Dependency:
Slip compensation (P1335) active. r1337 CO: V/f slip frequency Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays actual compensated motor slip as [%] Dependency:
Slip compensation (P1335) active.
P1338[3] Resonance damping gain V/f Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 0.00 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 10.00
Defines resonance damping gain for V/f. Here, di/dt of the acitve current will be scaled by P1338 (see diagram below). If di/dt increases the resonance damping circuit decreases the inverter output frequency.
T 1338 P f i
Index:
P1338[0] : 1st. Drive data set (DDS) P1338[1] : 2nd. Drive data set (DDS) P1338[2] : 3rd. Drive data set (DDS) Note:
- The resonance damping function is used to dampen oscillations in the active current. These especially occur when rotating field motors are operating under no-load conditions. The parameter is not used to optimize the stabilizing behavior. - In the V/f control modes (refer to P1300), the resonance damping controller is activate in a range from approximately 5 % up to 70 % of the rated motor frequency (P0310). - An excessively high value results in instability (positive feedback).
active res damping

P1340[3] Imax freq. controller prop. gain Min: 0.000 CStat: CUT Datatype: Float Unit: - Def: 0.000 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 0.499
Proportional gain of the I_max frequency controller. The Imax controller reduces inverter current if the output current exceeds the maximum motor current (r0067). In linear V/f, parabolic V/f, FCC, and programmable V/f modes the I_max controller uses both a frequency controller (see parameters P1340 and P1341) and a voltage controller (see parameters P1345 and P1346). The frequency controller seeks to reduce current by limiting the inverter output frequency (to a minimum of the two times nominal slip frequency). If this action does not successfully remove the overcurrent condition, the inverter output voltage is reduced using the I_max voltage controller. When the overcurrent condition has been removed successfully, frequency limiting is removed using the ramp-up time set in P1120.
-controller active Imax
In linear V/f for textiles, FCC for textiles, or external V/f modes only the I_max voltage controller is used to reduce current (See parameters P1345 and P1346). Index:
P1340[0] : 1st. Drive data set (DDS) P1340[1] : 2nd. Drive data set (DDS) P1340[2] : 3rd. Drive data set (DDS) Note:
The I_max controller can be disabled by setting the frequency controller integral time P1341 to zero. This disables both the frequency and voltage controllers. Note that when disabled, the I_max controller will take no action to reduce current but overcurrent warnings will still be generated, and the Drive will trip in excessive overcurrent or overload conditions. P1341[3] Imax freq. ctrl. integral time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 0.300 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 50.000
Integral time constant of the I_max controller. P1341 = 0 : I_max frequency and voltage controllers disabled P1340 = 0 and P1341 > 0 : frequency controller enhanced integral P1340 > 0 and P1341 > 0 : frequency controller normal PI control See description in parameter P1340 for further information. Index:
P1341[0] : 1st. Drive data set (DDS) P1341[1] : 2nd. Drive data set (DDS) P1341[2] : 3rd. Drive data set (DDS)

r1343 CO: Imax controller freq. output Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays effective frequency limitation. Dependency:
If I_max controller not in operation, parameter normally shows max. frequency P1082. r1344 CO: Imax controller volt. output Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays amount by which the I_max controller is reducing the inverter output voltage. P1345[3] Imax voltage ctrl. prop. gain Min: 0.000 CStat: CUT Datatype: Float Unit: - Def: 0.250 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 5.499
Proportional gain of the I_max voltage controller. See parameter P1340 for further information. Index:
P1345[0] : 1st. Drive data set (DDS) P1345[1] : 2nd. Drive data set (DDS) P1345[2] : 3rd. Drive data set (DDS) P1346[3] Imax voltage ctrl. integral time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 0.300 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 50.000
Integral time constant of the I_max voltage controller. P1341 = 0 : I_max frequency and voltage controllers disabled. P1345 = 0 and P1346 > 0 : I_max voltage controller enhanced integral P1345 > 0 and P1346 > 0 : I_max voltage controller normal PI control See description in parameter P1340 for further information. Index:
P1346[0] : 1st. Drive data set (DDS) P1346[1] : 2nd. Drive data set (DDS) P1346[2] : 3rd. Drive data set (DDS)

P1350[3] Voltage soft start Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 1
Selecting the soft starting function. With soft starting, the flux in the motor is established with some delay. This ensures that the motor only rotates in the required direction of rotation even with existing residual magnetism. When activated, at powered-on, the output voltage is ramped-up to the value of the characteristic voltage within the magnetizing time P0346.
Possible Settings:
0 OFF 1 ON Index:
P1350[0] : 1st. Drive data set (DDS) P1350[1] : 2nd. Drive data set (DDS) P1350[2] : 3rd. Drive data set (DDS) Note:
The settings for this parameter bring benefits and drawbacks: - P1350 = 0: (jump to boost voltage) Benefit: flux is built up quickly Drawback: motor may move - P1350 = 1: (smooth voltage build-up) Benefit: motor less likely to move Drawback: flux build-up takes longer

P1400[3] Configuration of speed control Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 3
Configuration for speed control. Bitfields:
Bit00 Automatic Kp adaption 0 NO 1 YES Bit01 Integral freeze (SLVC) 0 NO 1 YES Index:
P1400[0] : 1st. Drive data set (DDS) P1400[1] : 2nd. Drive data set (DDS) P1400[2] : 3rd. Drive data set (DDS) Note:
P1400 Bit 00 = 1: Automatic gain adaption of speed controller is enabled. In the area of field weakening the gain is reduced in dependence on flux.
P1400 Bit01 = 1: The integrator of the speed controller is frozen if Sensorless Vector Control (SLVC) is selected and the control is switched from closed-loop to open-loop operation. Advantage: The correct amount of slip compensation is calculated and applied to the open-loop function for a motor under load. r1407 CO/BO: Status 2 of motor control Min: - Datatype: U16 Unit: - Def: - P-Group: CONTROL Max: -
Displays status of motor control, which can be used to diagnose inverter status. Bitfields:
Bit00 V/f control enable 0 NO 1 YES Bit01 SLVC enable 0 NO 1 YES Bit02 Torque control enable 0 NO 1 YES Bit05 Stop I-comp. speed control 0 NO 1 YES Bit06 Set I-comp. speed controller 0 NO 1 YES Bit08 Upper torque limit active 0 NO 1 YES Bit09 Lower torque limit active 0 NO 1 YES Bit10 Enable droop 0 NO 1 YES Bit15 DDS change active 0 NO 1 YES Details:
See P052 (CO/BO: Status word 1) r1438 CO: Freq. setpoint to controller Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays setpoint of speed controller.
Kp · f(Φ) · fN

P1442[3] Filter time for act. speed Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 4 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 32000
Sets time constant of PT1 filter to smooth actual speed of speed controller. Index:
P1442[0] : 1st. Drive data set (DDS) P1442[1] : 2nd. Drive data set (DDS) P1442[2] : 3rd. Drive data set (DDS) r1445 CO: Act. filtered frequency 2 Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays filtered actual frequency at speed controller input. P1452[3] Filter time for act. freq (SLVC) Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 4 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 32000
Sets time constant of PT1 filter to filter the frequency deviation of speed controller in operation mode SLVC (sensorless vector control). Index:
P1452[0] : 1st. Drive data set (DDS) P1452[1] : 2nd. Drive data set (DDS) P1452[2] : 3rd. Drive data set (DDS) P1460[3] Gain speed controller Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 3.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2000.0
Enters gain of speed controller.

*) only active, if pre-control is enabled (P1496 > 0)
Index:
P1460[0] : 1st. Drive data set (DDS) P1460[1] : 2nd. Drive data set (DDS) P1460[2] : 3rd. Drive data set (DDS) P1462[3] Integral time speed controller Min: 25 CStat: CUT Datatype: U16 Unit: ms Def: 400 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 32001
Enters integral time of speed controller. Index:
P1462[0] : 1st. Drive data set (DDS) P1462[1] : 2nd. Drive data set (DDS) P1462[2] : 3rd. Drive data set (DDS)
evel

P1470[3] Gain speed controller (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 3.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2000.0
Enters gain of speed controller for sensorless vector control (SLVC).

*) only active , if pre-control is enabled (P1496 > 0) Index:
P1470[0] : 1st. Drive data set (DDS) P1470[1] : 2nd. Drive data set (DDS) P1470[2] : 3rd. Drive data set (DDS) P1472[3] Integral time n-ctrl. (SLVC) Min: 25 CStat: CUT Datatype: U16 Unit: ms Def: 400 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 32001
Enters integral time of speed controller for sensorless vector control (SLVC). Index:
P1472[0] : 1st. Drive data set (DDS) P1472[1] : 2nd. Drive data set (DDS) P1472[2] : 3rd. Drive data set (DDS) P1477[3] BI: Set integrator of n-ctrl. Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source to read in command to enable speed controller. Index:
P1477[0] : 1st. Command data set (CDS) P1477[1] : 2nd. Command data set (CDS) P1477[2] : 3rd. Command data set (CDS) P1478[3] CI: Set integrator value n-ctrl. Min: 0:0 CStat: UT Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source for integral part of speed controller. Index:
P1478[0] : 1st. Command data set (CDS) P1478[1] : 2nd. Command data set (CDS) P1478[2] : 3rd. Command data set (CDS) Dependency:
In case of sensorless vector control, integrator freezing must be selected (Bit 1 "Integral freeze (SLVC)" of P1400 has to be set) to save the integrator output. Note:
- If the setting command is not connected (P1477=0), a pending value is read in after pulse enable at the end of the excitation time (P0346) and the integral component of the speed controller is set once. - If the P1482 (integral component of speed controller) is connected upon pulse enable, the integral component of the controller is set to the last value prior the pulse inhibit. - Neither function works after flying start.

r1482 CO: Integral output of n-ctrl. Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays integral part of speed controller output.
P1488[3] Droop input source Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 3
Selects source of droop input signal. With mechanically coupled motors it is very important that an even load distribution is applied to each motor. The load sharing can be achieved by enabling the droop function on both inverters.
0 ... 3 P1488.D (0) Droop scaling

*) only active, if pre-control is enabled (P1496 > 0) 1. Droop is applied as a frequency setpoint on each inverter. The droop increases the slip via the negative feedback of the torque setpoint to the frequency setpoint. In a steady-state an even load distribution can be achieved if the slip characteristics are identical. - P1488 > 0 - P1489 > 0 - P1492 = 1 2. Droop can act as a setpoint or limitation for a group of inverters (i.e. master-slave inverters) By use of the master-slave inverter technique an even load distribution is achieved across the whole application. This is accomplished by setting the torque setpoint (r1490) on the master inverter which then controls the frequency of the master inverter and all connected slave inverters. - P1488 > 0 - P1489 > 0 - P1492 = 0 Possible Settings:
0 Droop input disabled 1 Torque setpoint 2 Speed controller output 3 Speed controller integral output Index:
P1488[0] : 1st. Drive data set (DDS) P1488[1] : 2nd. Drive data set (DDS) P1488[2] : 3rd. Drive data set (DDS) Dependency:
Droop scaling (P1489) must be > 0 for droop to be effective.
Droop input source

P1489[3] Droop scaling Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 0.05 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 0.50
Defines amount of droop in per unit at full load in [%]. Index:
P1489[0] : 1st. Drive data set (DDS) P1489[1] : 2nd. Drive data set (DDS) P1489[2] : 3rd. Drive data set (DDS) Note:
If 0 is entered as value, no droop is applied. r1490 CO: Droop frequency Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays output signal of droop function. This result of droop calculation is subtracted from the speed controller setpoint. P1492[3] Enable droop Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 1
Enables droop. Possible Settings:
0 Disabled 1 Enabled Index:
P1492[0] : 1st. Drive data set (DDS) P1492[1] : 2nd. Drive data set (DDS) P1492[2] : 3rd. Drive data set (DDS) Dependency:
Effective only if droop scaling P1489 > 0.

P1496[3] Scaling accel. precontrol Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 400.0
Enters scaling of acceleration in [%]. The response of setpoint changes for the speed control loop can be improved using the precontrol function (P1496). Precontrol is derived from the differential frequency setpoint multiplied by the mass inertia P0341; P0342 is then supplied as a torque setpoint to the current controller. If the filter (VC: P1442, SLVC: P1452) is applied in the correct manner, the derived speed controller is only required to control a small deviation in the value of the corrected variable. Setpoint changes are then passed by the speed controller and are quickly executed.

r0079 r1508 Index:
P1496[0] : 1st. Drive data set (DDS) P1496[1] : 2nd. Drive data set (DDS) P1496[2] : 3rd. Drive data set (DDS) Note:
P1496 = 0: Precontrol disabled P1496 > 0: Precontrol enabled P1496 = 100: Standard setting for precontrol P1499[3] Scaling accel. torque control Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 100.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 400.0
Enters scaling of acceleration in [%] for sensorless torque control (SLVC) at low frequencies. Index:
P1499[0] : 1st. Drive data set (DDS) P1499[1] : 2nd. Drive data set (DDS) P1499[2] : 3rd. Drive data set (DDS)

P1500[3] Selection of torque setpoint Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: CONTROL Active: first confirm QuickComm.: Yes Max: 77
Selects torque setpoint source. In the table of possible settings below, the main setpoint is selected from the least significant digit (i.e., 0 to 7) and any additional setpoint from the most significant digit (i.e., x0 through to x7). Possible Settings:
0 No main setpoint 2 Analog setpoint 4 USS on BOP link 5 USS on COM link 6 CB on COM link 7 Analog setpoint 2 20 No main setpoint + Analog setpoint 22 Analog setpoint + Analog setpoint 24 USS on BOP link + Analog setpoint 25 USS on COM link + Analog setpoint 26 CB on COM link + Analog setpoint 27 Analog setpoint 2 + Analog setpoint 40 No main setpoint + USS on BOP link 42 Analog setpoint + USS on BOP link 44 USS on BOP link + USS on BOP link 45 USS on COM link + USS on BOP link 46 CB on COM link + USS on BOP link 47 Analog setpoint 2 + USS on BOP link 50 No main setpoint + USS on COM link 52 Analog setpoint + USS on COM link 54 USS on BOP link + USS on COM link 55 USS on COM link + USS on COM link 57 Analog setpoint 2 + USS on COM link 60 No main setpoint + CB on COM link 62 Analog setpoint + CB on COM link 64 USS on BOP link + CB on COM link 66 CB on COM link + CB on COM link 67 Analog setpoint 2 + CB on COM link 70 No main setpoint + Analog setpoint 2 72 Analog setpoint + Analog setpoint 2 74 USS on BOP link + Analog setpoint 2 75 USS on COM link + Analog setpoint 2 76 CB on COM link + Analog setpoint 2 77 Analog setpoint 2 + Analog setpoint 2 Index:
P1500[0] : 1st. Command data set (CDS) P1500[1] : 2nd. Command data set (CDS) P1500[2] : 3rd. Command data set (CDS) Example:
Setting 24 selects the main setpoint (4) derived from the USS on BOP link with the additional setpoint (2) derived from the analog input. Single digits are main setpoints only with no additional setpoint.
Example P1500 = 24 :
P1500 = 24 ⇒ P1511 = r2015.1
P1000 = 24 Additonal torque setpoint

Be aware, by changing of parameter P1500 all BICO parameters (see table below) are modified. Note:
Changing this parameter sets (to default) all settings on item selected (see table).

y = 0 y = 2 y = 4 y = 5 y = 6 y = 7
0.0 755.0 2015.1 2018.1 2050.1 755.1 P1503 x = 0
0.0 755.0 2015.1 2018.1 2050.1 755.1 P1503 x = 2
0.0 755.0 2015.1 2018.1 2050.1 755.1 P1503 x = 4
0.0 755.0 2015.1 2018.1 755.1 P1503 x = 5
0.0 755.0 2015.1 2050.1 755.1 P1503 x = 6
Example:
P1500 = 24 → P1503 = 2015.1 P1511 = 755.0

P1501[3] BI: Change to torque control Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects command source from which it is possible to change between master (speed control) and slave (torque control).

*) only active, if pre-control is enabled (P1496 > 0)
Index:
P1501[0] : 1st. Command data set (CDS) P1501[1] : 2nd. Command data set (CDS) P1501[2] : 3rd. Command data set (CDS) Caution:
If direct selection of torque control is used (P1300=22, 23) the OFF1 command is recognized as OFF2. However, the OFF1 command is not recognized when torque control is selected indirectly (P1300=20, 21 and P1501=1). If indirect selection of torque control is used, it is recommended to program an OFF2 command using, for example a digital input or create the following circuit using the Free Function Blocks (FFB):

Details:
Speed control with encoder feedback see P1460 Speed control without encoder feedback see P1470

P1503[3] CI: Torque setpoint Min: 0:0 CStat: T Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source of torque setpoint for torque control. Index:
P1503[0] : 1st. Command data set (CDS) P1503[1] : 2nd. Command data set (CDS) P1503[2] : 3rd. Command data set (CDS) Details:
Displays torque setpoint before limitation. Details:
See parameter P1501.
P1511[3] CI: Additional torque setpoint Min: 0:0 CStat: T Datatype: U32 Unit: - Def: 0:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source of additional torque setpoint for torque and speed control. Index:
P1511[0] : 1st. Command data set (CDS) P1511[1] : 2nd. Command data set (CDS) P1511[2] : 3rd. Command data set (CDS) Details:
See parameter P1501. r1515 CO: Additional torque setpoint Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays additional torque setpoint. Details:
Displays acceleration torque. Details:
See parameter P1501. P1520[3] CO: Upper torque limit Min: -99999.00 CStat: CUT Datatype: Float Unit: Nm Def: 5.13 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 99999.00
Specifies fixed value for upper torque limitation.
P1520def r0333 1.5 ⋅ =
r0333 4 ⋅ ± = Index:
P1520[0] : 1st. Drive data set (DDS) P1520[1] : 2nd. Drive data set (DDS) P1520[2] : 3rd. Drive data set (DDS)
P1520max

P1521[3] CO: Lower torque limit Min: -99999.00 CStat: CUT Datatype: Float Unit: Nm Def: -5.13 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 99999.00
Enters fixed value of lower torque limitation.
P1521def r0333 1.5 ⋅ − =
r0333 4 ⋅ ± = Index:
P1521[0] : 1st. Drive data set (DDS) P1521[1] : 2nd. Drive data set (DDS) P1521[2] : 3rd. Drive data set (DDS) P1522[3] CI: Upper torque limit Min: 0:0 CStat: T Datatype: U32 Unit: - Def: 1520:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source of upper torque limitation. Index:
P1522[0] : 1st. Command data set (CDS) P1522[1] : 2nd. Command data set (CDS) P1522[2] : 3rd. Command data set (CDS) P1523[3] CI: Lower torque limit Min: 0:0 CStat: T Datatype: U32 Unit: - Def: 1521:0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 4000:0
Selects source of lower torque limitation. Index:
P1523[0] : 1st. Command data set (CDS) P1523[1] : 2nd. Command data set (CDS) P1523[2] : 3rd. Command data set (CDS) P1525[3] Scaling lower torque limit Min: -400.0 CStat: CUT Datatype: Float Unit: % Def: 100.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 400.0
Enters scaling of lower torque limitation in [%]. Index:
P1525[0] : 1st. Drive data set (DDS) P1525[1] : 2nd. Drive data set (DDS) P1525[2] : 3rd. Drive data set (DDS) Note:
P1525 = 100 % = standard setting r1526 CO: Upper torque limitation Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays actual upper torque limitation.
P1530 P1531
Stall power Dependency:
The parameters r1526 and r1527 depend on P1520, P1521, P1522, P1523 and P1525.

r1527 CO: Lower torque limitation Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays actual lower torque limitation. Details:
See parameter r1526. P1530[3] Motoring power limitation Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 0.12 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 8000.00
Defines fixed value for the max. permissible motoring active power (motoring power limitation).
P1530def P1530max 0307 P 3⋅ =
Parameter P1530 limits the torque in addition to the act. frequency as displayed in the following characteristic.
Power limitation (motoring, regenerative)
P M ⋅ π ⋅ =
P1531 P1530
Index:
P1530[0] : 1st. Drive data set (DDS) P1530[1] : 2nd. Drive data set (DDS) P1530[2] : 3rd. Drive data set (DDS) P1531[3] Regenerative power limitation Min: -8000.00 CStat: CUT Datatype: Float Unit: - Def: -0.12 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 0.00
Enters fixed value for the max. permissible regenerative active power (regenerative power limitation).
P1531max P0307 3 - ⋅ = P1531def P0307 2.5 - ⋅ =
Index:
P1531[0] : 1st. Drive data set (DDS) P1531[1] : 2nd. Drive data set (DDS) P1531[2] : 3rd. Drive data set (DDS) Details:
See parameter P1530. r1536 CO: Max. trq. motoring current Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays maximum torque motoring current component. r1537 CO: Max trq regenerative current Min: - Datatype: Float Unit: A Def: - P-Group: CONTROL Max: -
Displays maximum torque of the regenerative current component.
f 2 · f

r1538 CO: Upper torque limit (total) Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays total upper torque limitation.
Torque limitation :
P1530 Motoring power lim
P1531 Regener. power lim

r1539 CO: Lower torque limit (total) Min: - Datatype: Float Unit: Nm Def: - P-Group: CONTROL Max: -
Displays total lower torque limitation. Details:
See parameter r1538.
P1570[3] CO: Fixed value flux setpoint Min: 50.0 CStat: CUT Datatype: Float Unit: % Def: 107.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 200.0
Parameter to set the flux setpoint as a % relative to the rated motor flux. Index:
P1570[0] : 1st. Drive data set (DDS) P1570[1] : 2nd. Drive data set (DDS) P1570[2] : 3rd. Drive data set (DDS) Note:
- In the base speed range, the flux setpoint P1570 is converted into the field-generating current component isd (P1570 = 100% corresponds to r0331). - For values below 100%, the drive is under-magnetized and above this, is over-magnetized. - If P1570 is set to more than 100%, then the flux setpoint, depending on the load, is increased from 100% (under no-load conditions) to this value (under rated load, refer to the diagram). - If in so doing, the maximum drive inverter output voltage is reached, the rotor flux is reduced in order to keep the output voltage constant (or the EMF) with increasing speed. - The maximum possible output voltage r0071 of the drive inverter is determined by the DC link voltage r0026 and the maximum modulation depth P1803 in the gating unit.
Ψ

set · (100 %) · f

P1574[3] Dynamic voltage headroom Min: 0 CStat: CUT Datatype: U16 Unit: V Def: 10 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 150
Sets dynamic voltage headroom for vector control. If max. output voltage is reached, the voltage headroom is used for balancing lead values and disturbances. Parameter P1574 gives a control-reserve, that is valid also in field weakening Index:
P1574[0] : 1st. Drive data set (DDS) P1574[1] : 2nd. Drive data set (DDS) P1574[2] : 3rd. Drive data set (DDS) Note:
- Increasing of the reserve decreases the maximum output voltage (r0071). - Decreasing the voltage headroom can lead to instabilities of the control. P1580[3] Efficiency optimization Min: 0 CStat: CUT Datatype: U16 Unit: % Def: 0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 100
The efficiency for load-dependent magnetization can be optimized using parameter P1580. P1580 = 0% : No load-dependent magnetization (de-activated) P1580 > 0% : Load-dependent magnetization activated When the flux is decreased, the motor stator losses in the partial load range are reduced. When the load increases, the setpoint flux increases and therefore the magnetizing current corresponding to the torque- generating current. Index:
P1580[0] : 1st. Drive data set (DDS) P1580[1] : 2nd. Drive data set (DDS) P1580[2] : 3rd. Drive data set (DDS) Note:
- When using the optimization routine, it is necessary to increase the smoothing time of the flux setpoint (P1582). - The load-dependent magnetization (P1580 > 0) in the partial load range restricts the dynamic performance of the drive. - Under no-load conditions, a value of 100 % represents the full flux reduction (i.e. 50 % of the rated motor flux, refer to the diagram).
P1580 = x %
isd,N ⋅ 5 . 0
isq = isd,N
- P1580 can be activated at the same time with P1570. This allows an optimum adaptation both under no-load conditions/in the partial load range using P1580 as well as in the full load range using P1570.
i 100 1570 P
N , sd ⋅
P1580 = x %
isd,N ⋅ 5 . 0
isq = isd ,N

P1582[3] Smooth time for flux setpoint Min: 4 CStat: CUT Datatype: U16 Unit: ms Def: 15 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 500
Sets time constant of PT1 filter to smooth flux setpoint. Index:
P1582[0] : 1st. Drive data set (DDS) P1582[1] : 2nd. Drive data set (DDS) P1582[2] : 3rd. Drive data set (DDS) r1583 CO: Flux setpoint (smoothed) Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays smoothed flux setpoint in [%] relative to rated motor flux. P1596[3] Int. time field weak. controller Min: 20 CStat: CUT Datatype: U16 Unit: ms Def: 50 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 32001
Sets integral time for field weakening controller. Index:
P1596[0] : 1st. Drive data set (DDS) P1596[1] : 2nd. Drive data set (DDS) P1596[2] : 3rd. Drive data set (DDS) r1597 CO: Outp. field weak. controller Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays output signal of field weakening controller in [%] relative to rated motor flux. r1598 CO: Flux setpoint (total) Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays total flux setpoint in [%] relative to the rated motor flux. P1610[3] Continuous torque boost (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 50.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 200.0
Sets the constant torque boost for the low frequency range when sensorless closed-loop vector control is being used (SLVC). The parameter is entered as a % referred to the rated motor torque (r0333). For sensorless closed-loop vector control, when the motor model is disabled, an absolute current is impressed. P1610 represents the maximum load that occurs at a constant setpoint.

Index:
P1610[0] : 1st. Drive data set (DDS) P1610[1] : 2nd. Drive data set (DDS) P1610[2] : 3rd. Drive data set (DDS) Caution:
P1610 should always be set at least 10% higher than the maximum steady-state load that occurs. Note:
- For P1610 = 0 %, a current setpoint is calculated that corresponds to the no-load case (rated magnetization current). - For P1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque.

P1611[3] Acc. torque boost (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 0.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 200.0
Enters the dynamic torque boost for the low frequency range for sensorless closed-loop vector control (SLVC). The parameter is entered as a % referred to the rated motor torque (r0333). Index:
P1611[0] : 1st. Drive data set (DDS) P1611[1] : 2nd. Drive data set (DDS) P1611[2] : 3rd. Drive data set (DDS) Note:
- When accelerating and braking, P1611 is added to P1610 and the resulting total torque is converted into an appropriate current setpoint and controlled (closed-loop). - For pure accelerating torques, it is always more favorable to utilize the torque pre-control of the speed controller (P1496).
P1654[3] Smooth time for Isq setpoint Min: 2.0 CStat: CUT Datatype: Float Unit: ms Def: 6.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 20.0
Sets time constant of PT1 filter to filter setpoint of torque generating current component in field weakening range. Index:
P1654[0] : 1st. Drive data set (DDS) P1654[1] : 2nd. Drive data set (DDS) P1654[2] : 3rd. Drive data set (DDS) P1715[3] Gain current controller Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 0.25 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 5.00
Enters gain of current controller. Index:
P1715[0] : 1st. Drive data set (DDS) P1715[1] : 2nd. Drive data set (DDS) P1715[2] : 3rd. Drive data set (DDS) P1717[3] Integral time current controller Min: 1.0 CStat: CUT Datatype: Float Unit: ms Def: 4.1 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 50.0
Enters integral time of current controller. Index:
P1717[0] : 1st. Drive data set (DDS) P1717[1] : 2nd. Drive data set (DDS) P1717[2] : 3rd. Drive data set (DDS) r1718 CO: Output of Isq controller Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays actual output of Isq current (torque current) controller (PI controller). It contains the proportional and integral part of the PI controller. r1719 CO: Integral output of Isq ctrl. Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays integral output of Isq current (torque current) controller (PI controller). r1723 CO: Output of Isd controller Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays actual output of Isd current (flux current) controller (PI controller). It contains the proportional and integral part of the PI controller. r1724 CO: Integral output of Isd ctrl. Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays integral output of Isd current (flux current) controller (PI controller).

r1725 CO: Integral limit of Isd ctrl. Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays limit of integral output voltage setpoint of Isd current controller. r1728 CO: Decoupling voltage Min: - Datatype: Float Unit: V Def: - P-Group: CONTROL Max: -
Displays actual output voltage setpoint of cross channel decoupling. P1740 Gain for oscillation damping Min: 0.000 CStat: CUT Datatype: Float Unit: - Def: 0.000 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 10.000
Sets the controller gain to dampen oscillations in the sensorless vector control (SLVC) at low frequencies (open-loop).
T 1740 P f isq
Dependency:
Siehe P1750, P1755, P1756 P1745[3] Variance flux error Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 5.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 1000.0
Allowed variance error between flux setpoint and measured flux. Index:
P1745[0] : 1st. Drive data set (DDS) P1745[1] : 2nd. Drive data set (DDS) P1745[2] : 3rd. Drive data set (DDS) r1746 CO: Variance flux error Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Variance error between flux setpoint and measured flux.
P1750[3] Control word of motor model Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 3
Control word of motor model. This parameter controls the operation of the sensorless vector control (SLVC) at very low frequencies. This therefore includes the following conditions: - Operation directly after an ON command - zero crossing.


SLVC open loop means that the speed controller does not get any frequency feedback from the observer model.

Bitfields:
Bit00 Start SLVC open loop 0 NO 1 YES Bit01 Zero crossing SLVC open loop 0 NO 1 YES Index:
P1750[0] : 1st. Drive data set (DDS) P1750[1] : 2nd. Drive data set (DDS) P1750[2] : 3rd. Drive data set (DDS) r1751 Status word of motor model Min: - Datatype: U16 Unit: - Def: - P-Group: CONTROL Max: -
Displays status of transition from feed-forward to observer-control and vice versa. Bitfields:
Bit00 Transit to SLVC open loop 0 NO 1 YES Bit01 N-adaption enabled 0 NO 1 YES Bit02 Transit to SLVC closed loop 0 NO 1 YES Bit03 Speed controller enabled 0 NO 1 YES Bit04 Current injection 0 NO 1 YES Bit05 Start flux decrease 0 NO 1 YES Bit14 Rs adapted 0 NO 1 YES Bit15 Xh adapted 0 NO 1 YES

P1755[3] Start-freq. motor model (SLVC) Min: 0.1 CStat: CUT Datatype: Float Unit: Hz Def: 5.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 250.0
Enter the start frequency of sensorless vector control (SLVC), thereby SLVC switches over from open-loop to closed-loop at that frequency. The default setting depends on the motor power: - 0 kW to 0.749 kW: 5.0 Hz - 0.75 kW to 75 kW: 1.5 Hz - 75.1 kW to 200 kW: 1.0 Hz
[%] 100 [%] P1756 [Hz] P1755 [Hz] P1756 ⋅ =
Index:
P1755[0] : 1st. Drive data set (DDS) P1755[1] : 2nd. Drive data set (DDS) P1755[2] : 3rd. Drive data set (DDS) P1756[3] Hyst.-freq. motor model (SLVC) Min: 10.0 CStat: CUT Datatype: Float Unit: % Def: 50.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 100.0
Enters hysteresis frequency (in percent of start-frequency) to switch back from sensorless-vector-control (SLVC) to current model. Value is entered in the range 0 % to 50 % relative to P1755 (SLVC stop frequency). Index:
P1756[0] : 1st. Drive data set (DDS) P1756[1] : 2nd. Drive data set (DDS) P1756[2] : 3rd. Drive data set (DDS) P1758[3] Chng-ov. del. t SLVC op.-lp ctrl Min: 100 CStat: CUT Datatype: U16 Unit: ms Def: 1500 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2000
Sets the minimum time when the changeover frequency is fallen below when changing from the closed-loop into the open-loop controlled mode. Index:
P1758[0] : 1st. Drive data set (DDS) P1758[1] : 2nd. Drive data set (DDS) P1758[2] : 3rd. Drive data set (DDS) Dependency:
Refer to P1750, P1755, P1756 P1759[3] Chng-ov. del. t SLVC cl.-lp ctrl Min: 50 CStat: CUT Datatype: U16 Unit: ms Def: 100 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2000
Sets the minimum time when the changeover frequency is exceeded when changing from the open-loop controlled into the closed-loop controlled mode. Index:
P1759[0] : 1st. Drive data set (DDS) P1759[1] : 2nd. Drive data set (DDS) P1759[2] : 3rd. Drive data set (DDS) Dependency:
Refer to P1750, P1755, P1756

P1764[3] Kp of n-adaption (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 0.2 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2.5
Enters gain of speed adaptation controller for sensorless vector control.

) ˆ i ( Im ψ ⋅ ∆
Index:
P1764[0] : 1st. Drive data set (DDS) P1764[1] : 2nd. Drive data set (DDS) P1764[2] : 3rd. Drive data set (DDS) P1767[3] Tn of n-adaption (SLVC) Min: 1.0 CStat: CUT Datatype: Float Unit: ms Def: 4.0 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 200.0
Enters speed adaptation controller integral time. Index:
P1767[0] : 1st. Drive data set (DDS) P1767[1] : 2nd. Drive data set (DDS) P1767[2] : 3rd. Drive data set (DDS) r1770 CO: Prop. output of n-adaption Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays proportional part of speed adaptation controller. r1771 CO: Int. output of n-adaption Min: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL Max: -
Displays integral part of speed adaptation controller. r1778 CO: Flux angle difference Min: - Datatype: Float Unit: ° Def: - P-Group: CONTROL Max: -
Displays flux angle difference between motor model and current transformation before motor model is active. P1780[3] Control word of Rs/Rr-adaption Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 3 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 3
Enables thermal adaptation of stator and rotor resistance to reduce torque errors in speed/torque regulation with speed sensor, or frequency errors in speed/torque regulation without speed sensor. Bitfields:
Bit00 Enable thermal Rs/Rr-adapt. 0 NO 1 YES Bit01 Enable observer Rs/Xm-adapt. 0 NO 1 YES Index:
P1780[0] : 1st. Drive data set (DDS) P1780[1] : 2nd. Drive data set (DDS) P1780[2] : 3rd. Drive data set (DDS) Note:
Only stator resistance adaptation is carried out for synchronous motors.

P1781[3] Tn of Rs-adaption Min: 10 CStat: CUT Datatype: U16 Unit: ms Def: 100 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2000
Enters Rs-adaptation controller integral time. Index:
P1781[0] : 1st. Drive data set (DDS) P1781[1] : 2nd. Drive data set (DDS) P1781[2] : 3rd. Drive data set (DDS) r1782 Output of Rs-adaptation Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays stator resistance adaptation from controller in [%] relative to rated motor resistance.
Stator resistance is obtained as a function of the motor temperature as:
: P0625 act ≈ ϑ
% 100 r1782 - r0370 Z R R R N s s s adapt Start act ⋅ = + = with (P0625) R R s sStart =
: r0633 act = ϑ
% 100 r1782 - r0395 Z R (r0633) R R N s s s adapt act ⋅ = + =
Rated motor impedance:
N N
⋅ = ⋅ =
P1786[3] Tn of Xm-adaption Min: 10 CStat: CUT Datatype: U16 Unit: ms Def: 100 P-Group: CONTROL Active: Immediately QuickComm.: No Max: 2000
Enters Xm-adaptation controller integral time. Index:
P1786[0] : 1st. Drive data set (DDS) P1786[1] : 2nd. Drive data set (DDS) P1786[2] : 3rd. Drive data set (DDS) r1787 Output of Xm-adaption Min: - Datatype: Float Unit: % Def: - P-Group: CONTROL Max: -
Displays main reactance adaptation from controller in [%] relative to rated impedance.
For Nf f ≤ is valid
% 100 r1787 - r0382 Z X X X N m m m adapt Start act ⋅ = + = Γ Γ Γ
Rated motor impedance:
N N
⋅ = ⋅ =
a) · b)

P1800 Pulse frequency Min: 2 CStat: CUT Datatype: U16 Unit: kHz Def: 4 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 16
Sets pulse frequency of power switches in inverter. The frequency can be changed in steps of 2 kHz. Dependency:
Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency). - see derating in P1082 - P1800 > 30 * P0310 Note:
- If the pulse frequency is increased, max. inverter current r0209 can be reduced (derating). The derating characteristic depends on the type and power of the inverter (see manuall OPERATING INSTRUCTION). - If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce inverter losses and radio-frequency emissions. - Under certain circumstances, the inverter may reduce the switching frequency to provide protection against over-temperature (see P0290). r1801 CO: Act. pulse frequency Min: - Datatype: U16 Unit: kHz Def: - P-Group: INVERTER Max: -
Actual pulse frequency of power switches in inverter. Notice:
Under certain conditions (inverter overtemperature, see P0290), this can differ from the values selected in P1800 (pulse frequency). P1802 Modulator mode Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 2
Selects inverter modulator mode. Possible Settings:
0 SVM/ASVM automatic mode 1 Asymmetric SVM 2 Space vector modulation Notice:
- Asymmetric space vector modulation (ASVM) produces lower switching losses than space vector modulation (SVM), but may cause irregular rotation at very low frequencies. - Space vector modulation (SVM) with over-modulation may produce current waveform distortion at high output voltages. - Space vector modulation (SVM) without over-modulation will reduce maximum output voltage available to motor. P1803[3] Max. modulation Min: 20.0 CStat: CUT Datatype: Float Unit: % Def: 106.0 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 150.0
Sets maximum modulation index. Index:
P1803[0] : 1st. Drive data set (DDS) P1803[1] : 2nd. Drive data set (DDS) P1803[2] : 3rd. Drive data set (DDS) Note:
- P1803 = 100 % : Limit for over-control (for ideal inverter without switching delay). - For vector control the modulation limit will be reduced automatically with 4 %. P1820[3] Reverse output phase sequence Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 1
Changes direction of motor rotation without changing setpoint polarity. Possible Settings:
0 OFF 1 ON Index:
P1820[0] : 1st. Drive data set (DDS) P1820[1] : 2nd. Drive data set (DDS) P1820[2] : 3rd. Drive data set (DDS) Dependency:
If positive and negative revolution is enabled, frequency setpoint is directly used. If both positive and negative revolution are disabled, reference value is set to zero. Details:
See P1000 (select frequency setpoint)

P1825 On-state voltage of IGBT Min: 0.0 CStat: CUT Datatype: Float Unit: V Def: 1.4 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 20.0
Corrects on-state voltage of the IGBTs. P1828 Gating unit dead time Min: 0.00 CStat: CUT Datatype: Float Unit: us Def: 0.50 P-Group: INVERTER Active: first confirm QuickComm.: No Max: 3.50
Sets compensation time of gating unit interlock.
P1909[3] Ctrl. word of motor data ident. Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 1
Control word of motor data identification. Bitfields:
Bit00 Estimation of Xs 0 NO 1 YES Index:
P1909[0] : 1st. Drive data set (DDS) P1909[1] : 2nd. Drive data set (DDS) P1909[2] : 3rd. Drive data set (DDS) P1910 Select motor data identification Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 20
Performs a motor data identification. Possible Settings:
0 Disabled 1 Identification of all parameters with parameter change 2 Identification of all parameters without parameter change 3 Identification of saturation curve with parameter change 4 Identification of saturation curve without parameter change 5 Identification of XsigDyn (r1920) without parameter change 6 Identification of Tdead (r1926) without parameter change 7 Identification of Rs (r1912 ) without parameter change 8 Identification of Xs (r1915) without parameter change 9 Identification of Tr (r1913) without parameter change 10 Identification of Xsigma (r1914) without parameter change 20 Set voltage vector Common Settings:
P1910 = 1: All motor data and inverter characteristic will be identified and parameter will be changed. - P0350 stator resistance, - P0354 rotor resistance, - P0356 stator leakage inductance, - P0358 rotor leakage inductance, - P0360 main inductance - P1825 on-state voltage of IGBTs - P1828 compensation time of gating unit interlock P1910 = 3: Saturation curve will be identified and parameter will be changed. - P0362 ... P0365 magnetizing curve flux 1 .. 4 - P0366 ... P0369 magnetizing curve imag 1 .. 4 Caution:
Motor identification should normally be performed on a cold motor. However, the identification of the motor data should only be performed if the motor temperature is within 5°C of the measured ambient temperature stored in P0625. If the motor identification is not within the 5ºC limit then the correct functioning of Vector Control (VC, SLVC) cannot be guaranteed. This may cause instabilities when using vector control. The motor rating plate information with respect to the connection of the motor windings (Star or delta connection) must be correct in order to establish the correct equivalent circuit data. The motor identification calculates this data based on a Phase of a Star equivalent circuit P0350 - P0360, irrespective of whether the motor is connected star or delta. This must be considered when the motor data is input directly. Note:
- In order to that the motor identification routine supplies the correct data, before selecting, fast commissioning should be carried-out. - If the motor data identification routine is activated (e.g. P1910 = 1), then at the next ON command, the measuring operation is started and alarm A0541 is generated. After the measurement is completed, both P1910 and the alarm are reset.

When choosing the setting for measurement, observe the following: 1. "with parameter change" means that the values are actually adopted as Pxxxx parameter settings (see common settings above) and applied to the controller as well as being shown in the read-only parameters below. 2. "without parameter change" means that the values are only displayed, i.e. shown for checking purposes in the read-only parameters r1912 (identified stator resistance), r1913 (identified rotor time constant), r1914 (ident. total leakage reactance), r1915/r1916/r1917/r1918/r1919 (identified nominal stator reactance/identified stator reactance 1 to 4), r1925 (IGBT on-state voltage) and r1926 (identified gating unit dead time). The values are not applied to the controller. P1911 No. of phase to be identified Min: 1 CStat: CT Datatype: U16 Unit: - Def: 3 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 3
Selects maximum number of motor phases to be identified. r1912[3] Identified stator resistance Min: - Datatype: Float Unit: Ohm Def: - P-Group: MOTOR Max: -
Displays measured stator resistance value (line-to-line) in [Ohms] Index:
This value is measured using P1910 = 1 or 2 , i.e., identification of all parameters with/without change. r1913[3] Identified rotor time constant Min: - Datatype: Float Unit: ms Def: - P-Group: MOTOR Max: -
Displays identified rotor time constant. Index:
r1913[0] : U_phase r1913[1] : V_phase r1913[2] : W_phase r1914[3] Ident. total leakage inductance Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified total leakage inductance. Index:
r1914[0] : U_phase r1914[1] : V_phase r1914[2] : W_phase r1915[3] Ident. nom. stator inductance Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified stator inductance. Index:
If the value identified (Ls = stator inductance) does not lie within the range 50 % < Xs [p. u.] < 500 % fault message 41 (motor data identification failure) is issued. r0949 provides further information (fault value = 4 in this case). r1916[3] Identified stator inductance 1 Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified stator inductance. Index:
See P1915 (identified nominal stator inductance).

r1917[3] Identified stator inductance 2 Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified stator inductance. Index:
See P1915 (identified nominal stator inductance) r1918[3] Identified stator inductance 3 Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified stator inductance. Index:
See P1915 (identified nominal stator reactance) r1919[3] Identified stator inductance 4 Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified stator inductance. Index:
See P1915 (identified nominal stator inductance) r1920[3] Identified dyn. leak. inductance Min: - Datatype: Float Unit: - Def: - P-Group: MOTOR Max: -
Displays identified total dynamic leakage inductance. Index:
r1920[0] : U_phase r1920[1] : V_phase r1920[2] : W_phase r1925 Identified on-state voltage Min: - Datatype: Float Unit: V Def: - P-Group: INVERTER Max: -
Displays identified on-state voltage of IGBT. r1926 Ident. gating unit dead time Min: - Datatype: Float Unit: us Def: - P-Group: INVERTER Max: -
Displays identified dead time of gating unit interlock. P1930 Voltage setpoint for calibration Min: 0 CStat: CUT Datatype: Float Unit: V Def: 0 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 1000
Specifies reference voltage for generation of a test voltage vector (e.g. used for shunt calibration). P1931 Phase Min: 1 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: INVERTER Active: Immediately QuickComm.: No Max: 6
Defines phase of voltage vector

P1960 Speed control optimisation Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR Active: first confirm QuickComm.: No Max: 1
The drive should be set into a vector mode (P1300 = 20 or 21) to carry out speed controller optimisation. When speed controller optimisation is enabled (P1960 = 1) the warning A0542 will become active. When the drive is next started it will do the optimisation tests. The drive will accelerate the motor to 20 % of P0310 (rated motor frequency) using the ramp up time P1120 and then under torque control go to 50 % of P0310 (rated motor frequency). The drive will then ramp back down to 20 % using the ramp down time P1121. This procedure is repeated several times and then average time taken. From this an estimation of the inertia of the load on the motor can be derived. From this the inertia ratio parameter (P0342) and the Kp gains for VC (P1460) and SLVC (P1470) are modified to give a response suitable for the measured inertia. Possible Settings:
0 Disabled 1 Enabled Note:
- When the test is complete P1960 will be cleared to zero. - If there is a problem due to instability the drive may trip with an F0042 fault if a stable value has not been obtained on the ramp up within a reasonable time. - It should be noted that the DC-link controller should be enabled whilst doing the test as otherwise overvoltage trips maybe experienced. This will however depend on the ramp down time and the system inertia. - The speed loop optimisation may not be suitable for some applications due to the nature of the test i.e. accelerating under torque control from 20 % to 50 %.
P2000[3] Reference frequency Min: 1.00 CStat: CT Datatype: Float Unit: Hz Def: 50.00 P-Group: COMM Active: first confirm QuickComm.: No Max: 650.00
Parameter P2000 represents the reference frequency for frequency values which are displayed/transferred as a percentage or a hexadecimal value. Where: - hexadecimal 4000 H ==> P2000 (e.g.: USS-PZD) - percentage 100 % ==> P2000 (e.g.: ADC) Index:
P2000[0] : 1st. Drive data set (DDS) P2000[1] : 2nd. Drive data set (DDS) P2000[2] : 3rd. Drive data set (DDS) Example:
If a BICO connection is made between two parameters or alternatively using P0719 or P1000, the "unit" of the parameters (standardized (Hex) or physical (i.e. Hz) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target value.
[0] [1] [2] [3]
r0021[Hz] y[Hex] ⋅ = USS-PZD
] Hex [ 4000 P2000[Hz]
r2015 [0] [1] [2] [3]
2000 P 4000[Hex] r2015[1] y[Hz] ⋅ =

Parameter P2000 represents the reference frequency of the above mentioned interfaces. A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface. Unlike parameter P1082 (Max. Frequency) this limits the inverter frequency internally independent of the reference frequency. By modification of P2000 it will also adapt the parameter to the new settings.
Motor control f_act f_act,limit
f(Hex) f[Hz] ⋅ = ⋅ = f_act,limit = min(P1082, f_act)
f(%) 2000 P 4000(Hex)
Reference variables are intended as an aid to presenting setpoint and actual value signals in a uniform manner. This also applies to fixed settings entered as a precentage. A value of 100 % (USS / CB) corresponds to a process data value of 4000H, or 4000 0000H in the case of double values. In this respect, the following parameters are available:
P2001[3] Reference voltage Min: 10 CStat: CT Datatype: U16 Unit: V Def: 1000 P-Group: COMM Active: first confirm QuickComm.: No Max: 2000
Full-scale output voltage (i.e. 100 % ) used over serial link (corresponds to 4000H). Index:
P2001[0] : 1st. Drive data set (DDS) P2001[1] : 2nd. Drive data set (DDS) P2001[2] : 3rd. Drive data set (DDS) Example:
P2001 = 230 specifies that 4000H received via USS denotes 230 V. If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or physical (i.e. V) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target value.
r0026[V] y[Hex] ⋅ =
] Hex [ 4000 P2001[V]

P2002[3] Reference current Min: 0.10 CStat: CT Datatype: Float Unit: A Def: 0.10 P-Group: COMM Active: first confirm QuickComm.: No Max: 10000.00
Full-scale output current used over serial link (corresponds to 4000H). Index:
P2002[0] : 1st. Drive data set (DDS) P2002[1] : 2nd. Drive data set (DDS) P2002[2] : 3rd. Drive data set (DDS) Example:
If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or physical (i.e. A) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target value.
[0] [1] [2] [3]
r0027[A] y[Hex] ⋅ = USS-PZD
] Hex [ 4000 P2002[A]
P2003[3] Reference torque Min: 0.10 CStat: CT Datatype: Float Unit: Nm Def: 0.12 P-Group: COMM Active: first confirm QuickComm.: No Max: 99999.00
Full-scale reference torque used over the serial link (corresponds to 4000H). Index:
P2003[0] : 1st. Drive data set (DDS) P2003[1] : 2nd. Drive data set (DDS) P2003[2] : 3rd. Drive data set (DDS) Example:
If a BICO connection is made between two parameters or alternatively using P1500, the "unit" of the parameters (standardized (Hex) or physical (i.e. Nm) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target value.
[0] CB-PZD COM link [1] [2] [3]
r0080[Nm] y[Hex] ⋅ =
] Hex [ 4000 P2003[Nm]
P2004[3] Reference power Min: 0 CStat: CT Datatype: Float Unit: - Def: P-Group: COMM Active: first confirm QuickComm.: No Max: 0
Full-scale reference power used over the serial link (corresponds to 4000H).
P2003 P2000 M f 2 2 1 r2004 ⋅ ⋅ π = ⋅ ⋅ π ⋅ ⋅ =
Index:
P2004[0] : 1st. Drive data set (DDS) P2004[1] : 2nd. Drive data set (DDS) P2004[2] : 3rd. Drive data set (DDS) Example:
If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or physical (i.e. kW / hp) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target value.
[0] USS COM link [1] [2] [3]
] Hex [ 4000 r2004 r0032 y[Hex] ⋅ =
or x[hp] depending on P0100

P2009[2] USS denormalization Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMM Active: first confirm QuickComm.: No Max: 1
Enables denormalization for USS. Possible Settings:
0 Disabled 1 Enabled Index:
If denormalization is enabled, the main setpoint (word 2 in PZD) is not interpreted as 100 % = 4000H, but as "absolute" instead (e.g. 4000H = 16384 means 163.84 Hz ) if this is a frequency. Denormalization (P2009 = 1) only works for frequencies and is intended for backwards compatibility with MM3. P2010[2] USS baudrate Min: 4 CStat: CUT Datatype: U16 Unit: - Def: 6 P-Group: COMM Active: first confirm QuickComm.: No Max: 12
Sets baud rate for USS communication. Possible Settings:
4 2400 baud 5 4800 baud 6 9600 baud 7 19200 baud 8 38400 baud 9 57600 baud 10 76800 baud 11 93750 baud 12 115200 baud Index:
P2010[0] : Serial interface COM link P2010[1] : Serial interface BOP link P2011[2] USS address Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: COMM Active: first confirm QuickComm.: No Max: 31
Sets unique address for inverter. Index:
You can connect up to a further 30 inverters via the serial link (i.e. 31 inverters in total) and control them with the USS serial bus protocol.

P2012[2] USS PZD length Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 2 P-Group: COMM Active: first confirm QuickComm.: No Max: 8
Defines the number of 16-bit words in PZD part of USS telegram. Index:
USS protocol consists of PZD and PKW which can be changed by the user via parameters P2012 and P2013 respectively.
PKW PZD
PKE IND PWE
PZD1 PZD2 PZD3 PZD4
STX LGE ADR
Start of text Length Address Parameter ID value Process data Block check character
Parameter ID Sub-index Parameter value
PZD transmits a control word and setpoint or status word and actual values. The number of PZD-words in a USS-telegram are determined by parameter P2012, where the first two words (P2012 >= 2) are either: - control word and main setpoint or - status word and actual value. Restrictions: - If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word. - If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word, - When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the serial interface controls the inverter (P0700 or P0719).
HSW
HIW
STW2
P2012 PZD1 PZD2 PZD3 PZD4
STW ZSW PZD
Control word Status word Process data
Main setpoint Main actual value
USS telegram · Process data Parameter

P2013[2] USS PKW length Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 127 P-Group: COMM Active: first confirm QuickComm.: No Max: 127
Defines the number of 16-bit words in PKW part of USS telegram. The PKW part consists of the PKE part (1. word), IND part (2. word) resp. PWE part (3. - n. word). In contrary to the IND and PKE part, the PWE part can be varied. Depending on the particular requirement, 3- word, 4-word or variable word lengths can be parameterized. The PKW part of the USS telegram is used to read and write individual parameter values. Possible Settings:
0 No words 3 3 words 4 4 words 127 Variable Index:
U16 (16 Bit) U32 (32 Bit) Float (32 Bit)
P2013 = 4 X X X
P2013 = 127 X X X
USS protocol consists of PZD and PKW which can be changed by the user via parameters P2012 and P2013 respectively. Parameter P2013 determines the number of PKW-words in a USS-telegram. Setting P2013 to 3 or 4 determines the length of the PKW (3 = three words and 4 = four words). When P2013 set to 127 automatically adjusts the length of the PKW words are required.
1 word each 16 Bit
Parameter ID Sub-index Parameter value If a fixed PKW length is selected only one parameter value can be transferred. In the case of indexed parameter, you must use the variable PKW length if you wish to have the values of all indices transferred in a single telegram. In selecting the fixed PKW length, it is important to ensure the value in question can be transferred using this PKW length. P2013 = 3, fixes PKW length, but does not allow access to many parameter values. A parameter fault is generated when an out-of-range value is used, the value will not be accepted but the inverter state will not be affected. Useful for applications where parameters are not changed, but MM3s are also used. Broadcast mode is not possible with this setting. P2013 = 4, fixes PKW length. Allows access to all parameters, but indexed parameters can only be read one index at a time. Word order for single word values are different to setting 3 or 127, see example below. P2013 = 127, most useful setting. PKW reply length varies depending on the amount of information needed. Can read fault information and all indices of a parameter with a single telegram with this setting. Example: Set P0700 to value 5 (0700 = 2BC (hex))
P2013 = 4 P2013 = 127
Master → MM4 22BC 0000 0005 22BC 0000 0000 0005 22BC 0000 0005 0000
MM4 → Master 12BC 0000 0005 12BC 0000 0000 0005 12BC 0000 0005
Data type · Parameter access fault · Parameter access fault

P2014[2] USS telegram off time Min: 0 CStat: CT Datatype: U16 Unit: ms Def: 0 P-Group: COMM Active: Immediately QuickComm.: No Max: 65535
Defines the telegram failure time for the serial interfaces with USS protocol. The telegram failure time defines the time within which a valid telegram must have been received. If a valid telegram is not received within the specified time, the drive inverter outputs fault F0070. Index:
By default (time set to 0), no fault is generated (i.e. watchdog disabled). r2015[8] CO: PZD from BOP link (USS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays process data received via USS on BOP link (RS232 USS).
... r2033
[7] PZD1 STW1 PZD2
STX LGE ADR
Start of text Length Address PKW PZD BCC
Parameter ID value Process data Block check character
STX LGE ADR BCC PKW PZD Process data Parameter
Control word Main setpoint
USS on BOP link
PZD mapping to parameter r2015
Index:
r2015[0] : Received word 0 r2015[1] : Received word 1 r2015[2] : Received word 2 r2015[3] : Received word 3 r2015[4] : Received word 4 r2015[5] : Received word 5 r2015[6] : Received word 6 r2015[7] : Received word 7 Note:
The control words can be viewed as bit parameters r2032 and r2033. Restrictions: - If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word. - If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word, - When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).

P2016[8] CI: PZD to BOP link (USS) Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 52:0 P-Group: COMM Active: Immediately QuickComm.: No Max: 4000:0
Selects signals (process data PZD) to be transmitted to serial interface via USS on BOP link
HIW PZD3 PZD4 ZSW2
STX LGE ADR PKW PZD BCC ZSW HIW
Start of text Length Address Parameter ID value Process data Block check character
STX LGE ADR BCC PKW PZD Process data Parameter Status word Main actual value
USS on BOP link
PZD mapping from parameter P2016
Index:
P2016[0] : Transmitted word 0 P2016[1] : Transmitted word 1 P2016[2] : Transmitted word 2 P2016[3] : Transmitted word 3 P2016[4] : Transmitted word 4 P2016[5] : Transmitted word 5 P2016[6] : Transmitted word 6 P2016[7] : Transmitted word 7 Example:
P2016[0] = 52.0 (default). In this case, the value of r0052[0] (CO/BO: Status word) is transmitted as 1st PZD to the BOP link. Note:
If r0052 not indexed, display does not show an index (".0" ).

r2018[8] CO: PZD from COM link (USS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays process data received via USS on COM link.
... r2037
PZD1 STW1 PZD2
STX LGE ADR
Start of text Length Address PKW PZD BCC
Parameter ID value Process data Block check character
PKW PZD Process data Parameter
STW HSW
Control word Main setpoint
USS on COM link
PZD mapping to parameter r2018
Index:
r2018[0] : Received word 0 r2018[1] : Received word 1 r2018[2] : Received word 2 r2018[3] : Received word 3 r2018[4] : Received word 4 r2018[5] : Received word 5 r2018[6] : Received word 6 r2018[7] : Received word 7 Note:
The control words can be viewed as bit parameters r2036 and r2037. Restrictions: - If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word. - If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word, - When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).

P2019[8] CI: PZD to COM link (USS) Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 52:0 P-Group: COMM Active: Immediately QuickComm.: No Max: 4000:0
Selects signals (process data PZD) to be transmitted to serial interface via USS on COM link
HIW PZD3 PZD4 ZSW2
STX LGE ADR PKW PZD BCC ZSW HIW
Start of text Length Address Parameter ID value Process data Block check character
STX LGE ADR BCC PKW PZD Process data Parameter Status word Main actual value
PZD mapping from parameter P2019 USS on COM link
Index:
P2019[0] : Transmitted word 0 P2019[1] : Transmitted word 1 P2019[2] : Transmitted word 2 P2019[3] : Transmitted word 3 P2019[4] : Transmitted word 4 P2019[5] : Transmitted word 5 P2019[6] : Transmitted word 6 P2019[7] : Transmitted word 7 Details:
See P2016 (PZD to BOP link) r2024[2] USS error-free telegrams Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of error-free USS telegrams received. Index:
r2024[0] : Serial interface COM link r2024[1] : Serial interface BOP link r2025[2] USS rejected telegrams Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays the number of rejected USS telegrams. The sum of all USS errors (r2026 - r2031) is displayed in parameter r2025. The following monitoring mechanisms have been implemented - when a telegram is received, then initially, the correct start of a telegram (start interval + STX) must be identified and then the length must be evaluated (LGE). If the length does not correspond to the selected value for a fixed telegram or it does not have a valid value for a variable telegram length, the telegram is rejected. - the appropriate times are monitored before and while receiving telegrams. - the block check character (BCC) is generated while the telegram is received and after the complete telegram has been read-in, this is compared with the received BCC. If these do not match, then the telegram is not evaluated. - if a character frame error or a parity error has not occurred in any of the received characters, then the node number (ADR) of the received telegram can be evaluated. - the telegram is rejected if the address byte (ADR) does not correspond to the node number (for slave) or the expected slave node number (for the master). Index:

r2026[2] USS character frame error Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of USS character frame errors. Index:
r2026[0] : Serial interface COM link r2026[1] : Serial interface BOP link r2027[2] USS overrun error Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of USS telegrams with overrun error. Index:
r2027[0] : Serial interface COM link r2027[1] : Serial interface BOP link r2028[2] USS parity error Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of USS telegrams with parity error. Index:
r2028[0] : Serial interface COM link r2028[1] : Serial interface BOP link r2029[2] USS start not identified Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of USS telegrams with unidentified start. Index:
r2029[0] : Serial interface COM link r2029[1] : Serial interface BOP link r2030[2] USS BCC error Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of USS telegrams with BCC error. Index:
r2030[0] : Serial interface COM link r2030[1] : Serial interface BOP link r2031[2] USS length error Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays number of USS telegrams with incorrect length. Index:
r2031[0] : Serial interface COM link r2031[1] : Serial interface BOP link r2032 BO: CtrlWrd1 from BOP link (USS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 1 from BOP link (word 1 within USS). Bitfields:
Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit02 OFF3: Fast stop 0 YES 1 NO Bit03 Pulses enabled 0 NO 1 YES Bit04 RFG enable 0 NO 1 YES Bit05 RFG start 0 NO 1 YES Bit06 Setpoint enable 0 NO 1 YES Bit07 Fault acknowledge 0 NO 1 YES Bit08 JOG right 0 NO 1 YES Bit09 JOG left 0 NO 1 YES Bit10 Control from PLC 0 NO 1 YES Bit11 Reverse (setpoint inversion) 0 NO 1 YES Bit13 Motor potentiometer MOP up 0 NO 1 YES Bit14 Motor potentiometer MOP down 0 NO 1 YES Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES

r2033 BO: CtrlWrd2 from BOP link (USS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 2 from BOP link (i.e. word 4 within USS). Bitfields:
Bit00 Fixed frequency Bit 0 0 NO 1 YES Bit01 Fixed frequency Bit 1 0 NO 1 YES Bit02 Fixed frequency Bit 2 0 NO 1 YES Bit03 Fixed frequency Bit 3 0 NO 1 YES Bit04 Drive data set (DDS) Bit 0 0 NO 1 YES Bit05 Drive data set (DDS) Bit 1 0 NO 1 YES Bit08 PID enabled 0 NO 1 YES Bit09 DC brake enabled 0 NO 1 YES Bit11 Droop enabled 0 NO 1 YES Bit12 Torque control 0 NO 1 YES Bit13 External fault 1 0 YES 1 NO Bit15 Command data set (CDS) Bit 1 0 NO 1 YES Dependency:
P0700 = 4 (USS on BOP link) and P0719 = 0 (Cmd / Setpoint = BICO parameter). r2036 BO: CtrlWrd1 from COM link (USS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 1 from COM link (i.e. word 1 within USS). Bitfields:
Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit02 OFF3: Fast stop 0 YES 1 NO Bit03 Pulses enabled 0 NO 1 YES Bit04 RFG enable 0 NO 1 YES Bit05 RFG start 0 NO 1 YES Bit06 Setpoint enable 0 NO 1 YES Bit07 Fault acknowledge 0 NO 1 YES Bit08 JOG right 0 NO 1 YES Bit09 JOG left 0 NO 1 YES Bit10 Control from PLC 0 NO 1 YES Bit11 Reverse (setpoint inversion) 0 NO 1 YES Bit13 Motor potentiometer MOP up 0 NO 1 YES Bit14 Motor potentiometer MOP down 0 NO 1 YES Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES Details:
See r2033 (control word 2 from BOP link). r2037 BO: CtrlWrd2 from COM link (USS) Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 2 from COM link (i.e. word 4 within USS). Bitfields:
Bit00 Fixed frequency Bit 0 0 NO 1 YES Bit01 Fixed frequency Bit 1 0 NO 1 YES Bit02 Fixed frequency Bit 2 0 NO 1 YES Bit03 Fixed frequency Bit 3 0 NO 1 YES Bit04 Drive data set (DDS) Bit 0 0 NO 1 YES Bit05 Drive data set (DDS) Bit 1 0 NO 1 YES Bit08 PID enabled 0 NO 1 YES Bit09 DC brake enabled 0 NO 1 YES Bit11 Droop enabled 0 NO 1 YES Bit12 Torque control 0 NO 1 YES Bit13 External fault 1 0 YES 1 NO Bit15 Command data set (CDS) Bit 1 0 NO 1 YES Details:
See r2033 (control word 2 from BOP link).

P2040 CB telegram off time Min: 0 CStat: CT Datatype: U16 Unit: ms Def: 20 P-Group: COMM Active: Immediately QuickComm.: No Max: 65535
Defines time after which a fault will be generated (F0070) if no telegram is received via the link. The telegramm off time defines the time, within which a valid telegram must be received. If no valid telegram is received within that time, the inverter trips with F0070. Dependency:
Setting 0 = watchdog disabled P2041[5] CB parameter Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMM Active: first confirm QuickComm.: No Max: 65535
Configures a communication board (CB). Index:
P2041[0] : CB parameter 0 P2041[1] : CB parameter 1 P2041[2] : CB parameter 2 P2041[3] : CB parameter 3 P2041[4] : CB parameter 4 Details:
See relevant communication board manual for protocol definition and appropriate settings. r2050[8] CO: PZD from CB Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays PZD received from communication board (CB).
... r2091
PZD1 STW1 PZD2
CB-Frame PKW PZD CB-Frame Process data Parameter
Parameter ID value Process data Control word Main setpoint
CB on COM link PZD mapping to parameter r2050
Index:
r2050[0] : Received word 0 r2050[1] : Received word 1 r2050[2] : Received word 2 r2050[3] : Received word 3 r2050[4] : Received word 4 r2050[5] : Received word 5 r2050[6] : Received word 6 r2050[7] : Received word 7 Note:
The control words can be viewed as bit parameters r2090 and r2091. Restrictions: - If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word. - If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word, - When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).

P2051[8] CI: PZD to CB Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 52:0 P-Group: COMM Active: Immediately QuickComm.: No Max: 4000:0
Selects signals (process data PZD) to be transmitted via CB on COM link
PZD1 ZSW1 PZD2
PKW PZD ZSW HIW
Parameter ID value Process data CB-Frame PKW PZD CB-Frame Process data Parameter Status word Main actual value
PZD mapping from parameter P2051 CB on COM link
Index:
P2051[0] : Transmitted word 0 P2051[1] : Transmitted word 1 P2051[2] : Transmitted word 2 P2051[3] : Transmitted word 3 P2051[4] : Transmitted word 4 P2051[5] : Transmitted word 5 P2051[6] : Transmitted word 6 P2051[7] : Transmitted word 7 Common Settings:
- Status word 1 = 52 CO/BO: Act. status word 1 (see r0052) - Actual value 1 = 21 inverter output frequency (see r0021) - Other BICO settings are possible r2053[5] CB identification Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays identification data of the communication board (CB). The different CB types (r2053[0]) are given in the Enum declaration. Possible Settings:
0 No CB option board 1 PROFIBUS DP 2 DeviceNet 256 not defined Index:
r2053[0] : CB type (PROFIBUS = 1) r2053[1] : Firmware version r2053[2] : Firmware version detail r2053[3] : Firmware date (year) r2053[4] : Firmware date (day/month) r2054[7] CB diagnosis Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays diagnostic information of communication board (CB). Index:
r2054[0] : CB diagnosis 0 r2054[1] : CB diagnosis 1 r2054[2] : CB diagnosis 2 r2054[3] : CB diagnosis 3 r2054[4] : CB diagnosis 4 r2054[5] : CB diagnosis 5 r2054[6] : CB diagnosis 6 Details:
See relevant communications board manual.

r2090 BO: Control word 1 from CB Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 1 received from communication board (CB). Bitfields:
Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit02 OFF3: Fast stop 0 YES 1 NO Bit03 Pulses enabled 0 NO 1 YES Bit04 RFG enable 0 NO 1 YES Bit05 RFG start 0 NO 1 YES Bit06 Setpoint enable 0 NO 1 YES Bit07 Fault acknowledge 0 NO 1 YES Bit08 JOG right 0 NO 1 YES Bit09 JOG left 0 NO 1 YES Bit10 Control from PLC 0 NO 1 YES Bit11 Reverse (setpoint inversion) 0 NO 1 YES Bit13 Motor potentiometer MOP up 0 NO 1 YES Bit14 Motor potentiometer MOP down 0 NO 1 YES Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES Details:
See relevant communication board manual for protocol definition and appropriate settings. r2091 BO: Control word 2 from CB Min: - Datatype: U16 Unit: - Def: - P-Group: COMM Max: -
Displays control word 2 received from communication board (CB). Bitfields:
Bit00 Fixed frequency Bit 0 0 NO 1 YES Bit01 Fixed frequency Bit 1 0 NO 1 YES Bit02 Fixed frequency Bit 2 0 NO 1 YES Bit03 Fixed frequency Bit 3 0 NO 1 YES Bit04 Drive data set (DDS) Bit 0 0 NO 1 YES Bit05 Drive data set (DDS) Bit 1 0 NO 1 YES Bit08 PID enabled 0 NO 1 YES Bit09 DC brake enabled 0 NO 1 YES Bit11 Droop enabled 0 NO 1 YES Bit12 Torque control 0 NO 1 YES Bit13 External fault 1 0 YES 1 NO Bit15 Command data set (CDS) Bit 1 0 NO 1 YES Details:
See relevant communication board manual for protocol definition and appropriate settings.

P2100[3] Alarm number selection Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: first confirm QuickComm.: No Max: 65535
Selects up to 3 faults or warnings for non-default reactions. Index:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0] = 5, then select the desired reaction in P2101[0] (in this case, set P2101[0] = 3). Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g. overcurrent) cannot be changed from the default reactions. P2101[3] Stop reaction value Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: first confirm QuickComm.: No Max: 4
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction). This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2. Possible Settings:
0 No reaction, no display 1 OFF1 stop reaction 2 OFF2 stop reaction 3 OFF3 stop reaction 4 No reaction warning only Index:
P2101[0] : Stop reaction value 1 P2101[1] : Stop reaction value 2 P2101[2] : Stop reaction value 3 Note:
- Settings 0 - 3 only are available for fault codes. - Settings 0 and 4 only are available for warnings. - Index 0 (P2101) refers to fault/warning in index 0 (P2100). P2103[3] BI: 1. Faults acknowledgement Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:2 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines first source of fault acknowledgement, e.g. keypad/DIN, etc. (depending on setting). Index:
P2103[0] : 1st. Command data set (CDS) P2103[1] : 2nd. Command data set (CDS) P2103[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)

P2104[3] BI: 2. Faults acknowledgement Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Selects second source of fault acknowledgement. Index:
P2104[0] : 1st. Command data set (CDS) P2104[1] : 2nd. Command data set (CDS) P2104[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) P2106[3] BI: External fault Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 1:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Selects source of external faults. Index:
P2106[0] : 1st. Command data set (CDS) P2106[1] : 2nd. Command data set (CDS) P2106[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) r2110[4] Warning number Min: - Datatype: U16 Unit: - Def: - P-Group: ALARMS Max: -
Displays warning information. A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be viewed. Index:
r2110[0] : Recent Warnings --, warning 1 r2110[1] : Recent Warnings --, warning 2 r2110[2] : Recent Warnings -1, warning 3 r2110[3] : Recent Warnings -1, warning 4 Note:
- Indices 0 and 1 are not stored. - The keypad will flash while a warning is active. The LEDs indicate the warning status in this case. - If an AOP is in use, the display will show number and text of the active warning. P2111 Total number of warnings Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: first confirm QuickComm.: No Max: 4
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.

Displays run time counter. It is the total time the drive has been powered up. When power goes value is saved, then restored on powerup. The run time counter r2114 will be calculate as followed: - Multiply the value in r2114[0], by 65536 and then add it to the value in r2114[1]. - The resultant answer will be in seconds. When AOP is not connected, the time in this parameter is used by r0948 to indicate when a fault has occured. Index:
If r2114[0] = 1 & r2114[1] = 20864 We get 1 * 65536 + 20864 = 86400 seconds which equals 1 day. P2115[3] AOP real time clock Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 65535
Displays AOP real time. All of the frequency inverters have an internal time generator function which is used to time-stamp and log erroneous conditions. Therefore there is no battery-buffered real-time clock (RTC). The frequency inverters can support a software-controlled RTC where the RTC must be set from the AOP or via an interface. When using the AOP, this synchronization is automatic. When a serial interface is used, a task must be sent from the higher-level control to write into the parameter. If the AOP is withdrawn during operation, or if the bus is interrupted, then the real-time clock runs further using the runtime counter. The real-time clock is reset to zero only after power off. The time is stored in a word array parameter P2115. This parameter number is common to all invertes. Inverters not supporting this feature would respond with parameter not recognised - a Master will ignore this. The time will be set by USS Protocol standard word array parameter write telegrams. Within the AOP, while it is acting as a USS Master, at each tick of the heartbeat, the list of available USS Slaves will be flagged with a time update request. As the Master runs around the list of USS slaves on its next USS update cycle, if there are no higher priority tasks to perform, and the slave still has its time update flag set, then an array parameter write telegram will be issued, containing the current time. The request for that slave is cancelled if the slave responds correctly. The AOP will not need to read the time from the slave. Time is maintained in a word array parameter and encoded as follows - the same format will be used in fault report logs.
High Byte (MSB) Index
Low Byte (LSB) Seconds (0 - 59)
Minutes (0 - 59)
Hours (0 - 23)
Days (1 - 31)
Years (00 - 250) Time is measured from Jan 1st 2000. Values are in binary form. Index:
Month (1 - 12)

Example:
P2115[0] = 13625 P2115[1] = 2579 P2115[2] = 516 The conversion into binary quantities (U16) results in the following bit pattern: Seconds + minutes: - High byte (MSB) = 00110101 corresponding to the number 53, i.e. seconds 53 - Low byte (LSB) = 00111001 corresponding to the number 57, i.e. minutes 57 Hours + days: - High byte (MSB) = 00001010 corresponding to the number 10, i.e. hours 10 - Low byte (LSB) = 00010011 corresponding to the number 19, i.e. days 19 Months + year: - High byte (MSB) = 00000010 corresponding to the number 2, i.e. months 2 - Low byte (LSB) = 00000100 corresponding to the number 4, i.e. years 4 This means that the real time displayed in P2115 is 19.02.2004, 10:57:53. P2120 Indication counter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 65535
Indicates total number of alarm events. This parameter is incremented whenever an alarm event occurs. It also gets incremented when a warning is cleared or faults are cleared. This parameter is used by the PC tools. P2150[3] Hysteresis frequency f_hys Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 3.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.00
Defines hysteresis level applied for comparing frequency and speed to threshold as illustrated in the diagram below.
r2197 Bit03 r0052 Bit14
Hyst. freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
| f_act | >= | f_set |
r2197 Bit04 r0053 Bit06
Hyst . freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Index:
P2150[0] : 1st. Drive data set (DDS) P2150[1] : 2nd. Drive data set (DDS) P2150[2] : 3rd. Drive data set (DDS) P2153[3] Time-constant frequency filter Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 5 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 1000
Specifies time constant of first-order frequency filter. The filtered frequency is then compared to the thresholds. Index:
P2153[0] : 1st. Drive data set (DDS) P2153[1] : 2nd. Drive data set (DDS) P2153[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2155, P2157 and P2159

P2155[3] Threshold frequency f_1 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 30.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Sets a threshold for comparing actual frequency or frequency to threshold values f_1. This threshold controls status bits 4 and 5 in status word 2 (r0053).
Threshold freq f_1 0.00 ... 650.00 [Hz] P2155.D (30.00)
Delay time of f _1

Threshold freq f_1 0.00 ... 650.00 [Hz] P2155.D (30.00)
Hyst . freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Delay time of f _1
Hyst. freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
0 ... 10000 [ms] P2156.D (10)
Index:
P2155[0] : 1st. Drive data set (DDS) P2155[1] : 2nd. Drive data set (DDS) P2155[2] : 3rd. Drive data set (DDS) P2156[3] Delay time of threshold freq f_1 Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Sets delay time prior to threshold frequency f_1 comparison (P2155). Index:
P2156[0] : 1st. Drive data set (DDS) P2156[1] : 2nd. Drive data set (DDS) P2156[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2155 (threshold frequency f_1) P2157[3] Threshold frequency f_2 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 30.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Threshold_2 for comparing frequency or frequency to thresholds as illustrated in the diagram below.
Threshold freq f_2 0.00 ... 650.00 [Hz] P2157.D (30.00)
Delay time of f _2

Threshold freq f_2 0.00 ... 650.00 [Hz] P2157.D (30.00)
Hyst . freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Delay time of f _2
Hyst. freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
0 ... 10000 [ms] P2158.D (10)
Index:
P2157[0] : 1st. Drive data set (DDS) P2157[1] : 2nd. Drive data set (DDS) P2157[2] : 3rd. Drive data set (DDS) P2158[3] Delay time of threshold freq f_2 Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for comparing frequency to threshold f_2 (P2157). Index:
P2158[0] : 1st. Drive data set (DDS) P2158[1] : 2nd. Drive data set (DDS) P2158[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2157 (threshold frequency f_2)

P2159[3] Threshold frequency f_3 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 30.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Threshold_3 for comparing frequency to thresholds.

Threshold freq f_3 0.00 ... 650.00 [Hz] P2159.D (30.00)
Threshold freq f_3 0.00 ... 650.00 [Hz] P2159.D (30.00)
Hyst . freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Hyst. freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Index:
P2159[0] : 1st. Drive data set (DDS) P2159[1] : 2nd. Drive data set (DDS) P2159[2] : 3rd. Drive data set (DDS) P2160[3] Delay time of threshold freq f_3 Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for comparing frequency to threshold f_3 (P2159). Index:
P2160[0] : 1st. Drive data set (DDS) P2160[1] : 2nd. Drive data set (DDS) P2160[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2159 (threshold frequency f_3) P2161[3] Min. threshold for freq. setp. Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 3.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.00
Minimum threshold value for comparing frequency setpoint.

Hyst . freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Hyst . freq. f_hys 0.00 ... 10.00 [Hz] P2150.D (3.00)
Index:
P2161[0] : 1st. Drive data set (DDS) P2161[1] : 2nd. Drive data set (DDS) P2161[2] : 3rd. Drive data set (DDS)

P2162[3] Hysteresis freq. for overfreq. Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 20.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Hysteresis frequency for overfrequency-detection as illustrated in the diagram below.
Max. frequency 0.00 ... 650.00 [Hz] P1082.D (50.00)
f_act f_act > f_max
Overspd. hyst.freq 0.00 ... 650.00 [Hz] P2162.D (20.00)
Index:
P2162[0] : 1st. Drive data set (DDS) P2162[1] : 2nd. Drive data set (DDS) P2162[2] : 3rd. Drive data set (DDS) P2163[3] Entry freq. for perm. deviation Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 3.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 20.00
Threshold for detecting frequency deviation from setpoint as illustrated in the diagram P2164. Index:
P2163[0] : 1st. Drive data set (DDS) P2163[1] : 2nd. Drive data set (DDS) P2163[2] : 3rd. Drive data set (DDS) P2164[3] Hysteresis frequency deviation Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 3.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.00
Hysteresis frequency for detecting permitted deviation (from setpoint). This frequency controls bit 8 in status word 1 (r0052) and bit 6 in status word 2 (r0053).
Entry freq. deviat 0.00 ... 20.00 [Hz] P2163.D (3.00) Delay_T perm. dev.
0 ... 10000 [ms] P2165.D (10)
f_act == f_set 0 T
r2197 Bit07 r0052 Bit08 r0053 Bit06
Hyster freq deviat 0.00 ... 10.00 [Hz] P2164.D (3.00)
Index:
P2164[0] : 1st. Drive data set (DDS) P2164[1] : 2nd. Drive data set (DDS) P2164[2] : 3rd. Drive data set (DDS) P2165[3] Delay time permitted deviation Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for detecting permitted deviation of frequency from setpoint. Index:
P2165[0] : 1st. Drive data set (DDS) P2165[1] : 2nd. Drive data set (DDS) P2165[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2164.

P2166[3] Delay time ramp up completed Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for signal that indicates completion of ramp-up. Index:
P2166[0] : 1st. Drive data set (DDS) P2166[1] : 2nd. Drive data set (DDS) P2166[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2174. P2167[3] Switch-off frequency f_off Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 1.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.00
Defines the threshold of the monitoring function |f_act|
OFF1/OFF3
OFF1/OFF3
P2168 P2168
OFF2
Index:
P2167[0] : 1st. Drive data set (DDS) P2167[1] : 2nd. Drive data set (DDS) P2167[2] : 3rd. Drive data set (DDS) P2168[3] Delay time T_off Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Defines time for which the inverter may operate below switch-off frequency (P2167) before switch off occurs. Index:
P2168[0] : 1st. Drive data set (DDS) P2168[1] : 2nd. Drive data set (DDS) P2168[2] : 3rd. Drive data set (DDS) Dependency:
Active if holding brake (P1215) not parameterized. Details:
See diagram in P2167 (switch-off frequency)
![Page 215 of the Siemens 440 user manual — 0.0 ... 400.0 [%] P2170.D (100.0)](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-215.webp?w=400)
r2169 CO: Act. filtered frequency 3 Min: - Datatype: Float Unit: Hz Def: - P-Group: ALARMS Max: -
Filtered frequency for monitoring behind first-order lowpass filter. - |f_act| > f_1 (see P2155) - |f_act| > f_2 (see P2157) - |f_act| > f_3 (see P2159) P2170[3] Threshold current I_thresh Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 100.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 400.0
Defines threshold current in [%] relative to P0305 (rated motor current) to be used in comparisons of I_act and I_Thresh as illustrated in the diagram below.
I_act | I_act | > I_thresh
0 ... 10000 [ms] P2171.D (10)
Index:
P2170[0] : 1st. Drive data set (DDS) P2170[1] : 2nd. Drive data set (DDS) P2170[2] : 3rd. Drive data set (DDS) Note:
This threshold controls bit 3 in status word 3 (r0053). P2171[3] Delay time current Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Defines delay time prior to activation of current comparison. Index:
P2171[0] : 1st. Drive data set (DDS) P2171[1] : 2nd. Drive data set (DDS) P2171[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2170 (threshold current I_thresh)
r0053 Bit03 · Delay time current · Threshold current

P2172[3] Threshold DC-link voltage Min: 0 CStat: CUT Datatype: U16 Unit: V Def: 800 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 2000
Defines DC link voltage to be compared to actual voltage as illustrated in the diagram below.
Vdc_act < P2172
Vdc_act > P2172
Index:
P2172[0] : 1st. Drive data set (DDS) P2172[1] : 2nd. Drive data set (DDS) P2172[2] : 3rd. Drive data set (DDS) Note:
This voltage controls bits 7 and 8 in status word 3 (r0053). P2173[3] Delay time DC-link voltage Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Defines delay time prior to activation of threshold comparison. Index:
P2173[0] : 1st. Drive data set (DDS) P2173[1] : 2nd. Drive data set (DDS) P2173[2] : 3rd. Drive data set (DDS) Details:
See diagram in P2172 (threshold DC-link voltage)

P2174[3] Torque threshold M_thresh Min: 0.00 CStat: CUT Datatype: Float Unit: Nm Def: 5.13 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.00
Defines torque threshold for comparing actual torque.

| M_act | > M_thresh M_act | > M_thresh M_actNoAcc | > M_thresh
0 ... 10000 [ms] P2166.D (10) Torque threshold 0.00 ... 99999.00 [Nm] P2174.D (5.13)
Entry freq. deviat 0.00 ... 20.00 [Hz] P2163.D (3.00)
Hyster freq deviat 0.00 ... 10.00 [Hz] P2164.D (3.00)
Index:
P2174[0] : 1st. Drive data set (DDS) P2174[1] : 2nd. Drive data set (DDS) P2174[2] : 3rd. Drive data set (DDS) P2176[3] Delay time for torque threshold Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for comparing actual torque to threshold. Index:
P2176[0] : 1st. Drive data set (DDS) P2176[1] : 2nd. Drive data set (DDS) P2176[2] : 3rd. Drive data set (DDS) P2177[3] Delay time for motor is blocked Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for identification that motor is blocked. Index:
P2177[0] : 1st. Drive data set (DDS) P2177[1] : 2nd. Drive data set (DDS) P2177[2] : 3rd. Drive data set (DDS) P2178[3] Delay time for motor pulled out Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for identification that motor is pulled out. Index:
P2178[0] : 1st. Drive data set (DDS) P2178[1] : 2nd. Drive data set (DDS) P2178[2] : 3rd. Drive data set (DDS)

P2179 Current limit for no load ident. Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 3.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.0
Threshold current for A0922 (load missing) in [%] relative to P0305 (rated motor current) as illustrated in the diagram below.
Cur.lim:no-load ID
Load missing T 0
0 ... 10000 [ms] P2180 (2000)
- It may be that the motor is not connected (load missing) or a phase could be missing. - If a motor setpoint cannot be entered and the current limit (P2179) is not exceeded, Alarm A0922 (no load applied) is issued when delay time (P2180) expires. P2180 Delay time for load missing Min: 0 CStat: CUT Datatype: U16 Unit: ms Def: 2000 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time to identify that the current is less than the threshold defined in P2179. Details:
See diagram in P2179 (current limit for no load identification).
P2181[3] Belt failure detection mode Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: first confirm QuickComm.: No Max: 6
Parameter P2181 activates or de-activates the load torque monitoring and defines the response to a load torque fault. Using the load torque monitoring, it is possible to detect a mechanical failure or an overload condition of the mechanical transmission line, e.g. a broken drive belt or a stalled conveyor belt. In this case, the actual torque/frequency actual value is compared to a programmed envelope characteristic (refer to P2182 - P2190). If the actual torque/frequency actual value lies above or below the envelope curve, then after the delay time P2192 expires, as a function of P2181, alarm A0952 is output or the drive inverter is tripped with fault message F0452. Possible Settings:
0 Belt failure detection disabled 1 Warning: Low torque / frequency 2 Warning: High torque / frequency 3 Warning: High / low torque / frequency 4 Trip: Low torque / frequency 5 Trip: High torque / frequency 6 Trip: High / low torque / frequency Index:
P2181[0] : 1st. Command data set (CDS) P2181[1] : 2nd. Command data set (CDS) P2181[2] : 3rd. Command data set (CDS)

P2182[3] Belt threshold frequency 1 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 5.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Sets a frequency threshold 1 for comparing actual torque to torque the envelope for belt failure detection. The frequency torque envelope is defined by 9 parameters - 3 are frequency parameters (P2182 - P2184), and the other 6 define the low and high torque limits (P2185 - P2190) for each frequency (see diagram below).
P1082 Max. frequency P1080 Min. frequency
P2189 Upper torque threshold 3
P2190 Lower torque threshold 3
P2187 Upper torque threshold 2
P2188 Lower torque threshold 2
P2185 Upper torque threshold 1 P2186 Lower torque threshold 1
P2183 Threshold frequency 2 P2184 Threshold frequency 3
P2182 Threshold frequency 1
Boundary zones De-activated monitoring
Envelope curve Active monitoring
The allowed frequency/torque region is defined by the shaded area. When the torque falls outside the area shown, a trip or warning occurs (see parameter P2181). Index:
P2182[0] : 1st. Drive data set (DDS) P2182[1] : 2nd. Drive data set (DDS) P2182[2] : 3rd. Drive data set (DDS) Note:
- The load torque monitoring function is not active below the frequency defined in P2182 and above the frequency defined in P2184. - The current and torque limits of the drive inverter and motor still apply over the complete frequency range. - The drive inverter output frequency is defined using Parameter P1080 and P1082. These limits should be carefully observed for the load torque monitoring frequencies. P2183[3] Belt threshold frequency 2 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 30.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Sets a threshold F2 for comparing actual torque to torque the envelope for belt failure detection. Index:
P2183[0] : 1st. Drive data set (DDS) P2183[1] : 2nd. Drive data set (DDS) P2183[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1).
|Torque| [Nm] · |Frequency| · [Hz]

P2184[3] Belt threshold frequency 3 Min: 0.00 CStat: CUT Datatype: Float Unit: Hz Def: 50.00 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection. Index:
P2184[0] : 1st. Drive data set (DDS) P2184[1] : 2nd. Drive data set (DDS) P2184[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1). P2185[3] Upper torque threshold 1 Min: 0.0 CStat: CUT Datatype: Float Unit: Nm Def: 99999.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Upper limit threshold value 1 for comparing actual torque. Index:
P2185[0] : 1st. Drive data set (DDS) P2185[1] : 2nd. Drive data set (DDS) P2185[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1). P2186[3] Lower torque threshold 1 Min: 0.0 CStat: CUT Datatype: Float Unit: Nm Def: 0.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Lower limit threshold value 1 for comparing actual torque. Index:
P2186[0] : 1st. Drive data set (DDS) P2186[1] : 2nd. Drive data set (DDS) P2186[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1). P2187[3] Upper torque threshold 2 Min: 0.0 CStat: CUT Datatype: Float Unit: Nm Def: 99999.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Upper limit threshold value 2 for comparing actual torque. Index:
P2187[0] : 1st. Drive data set (DDS) P2187[1] : 2nd. Drive data set (DDS) P2187[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1). P2188[3] Lower torque threshold 2 Min: 0.0 CStat: CUT Datatype: Float Unit: Nm Def: 0.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Lower limit threshold value 2 for comparing actual torque. Index:
P2188[0] : 1st. Drive data set (DDS) P2188[1] : 2nd. Drive data set (DDS) P2188[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1). P2189[3] Upper torque threshold 3 Min: 0.0 CStat: CUT Datatype: Float Unit: Nm Def: 99999.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Upper limit threshold value 3 for comparing actual torque. Index:
P2189[0] : 1st. Drive data set (DDS) P2189[1] : 2nd. Drive data set (DDS) P2189[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1).

P2190[3] Lower torque threshold 3 Min: 0.0 CStat: CUT Datatype: Float Unit: Nm Def: 0.0 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Lower limit threshold value 3 for comparing actual torque. Index:
P2190[0] : 1st. Drive data set (DDS) P2190[1] : 2nd. Drive data set (DDS) P2190[2] : 3rd. Drive data set (DDS) Details:
See P2182 (belt threshold frequency 1). P2192[3] Time delay for belt failure Min: 0 CStat: CUT Datatype: U16 Unit: s Def: 10 P-Group: ALARMS Active: Immediately QuickComm.: No Max: 65
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events caused by transient conditions. It is used for both methods of fault detection. Index:
P2192[0] : 1st. Drive data set (DDS) P2192[1] : 2nd. Drive data set (DDS) P2192[2] : 3rd. Drive data set (DDS) r2197 CO/BO: Monitoring word 1 Min: - Datatype: U16 Unit: - Def: - P-Group: ALARMS Max: -
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function. Bitfields:
Bit00 f_act zero 0 NO 1 YES Bit04 f_act >= setp. (f_set) 0 NO 1 YES Bit05 f_act = P1082 (f_max) 0 NO 1 YES Bit07 f_act == setp. (f_set) 0 NO 1 YES Bit08 Act. current r0068 > P2170 0 NO 1 YES Bit09 Act. unfilt. Vdc < P2172 0 NO 1 YES Bit10 Act. unfilt. Vdc > P2172 0 NO 1 YES Bit11 Load missing 0 NO 1 YES r2198 CO/BO: Monitoring word 2 Min: - Datatype: U16 Unit: - Def: - P-Group: ALARMS Max: -
Monitoring word 2 which indicates the state of monitor functions. Each bit represents one monitor function. Bitfields:
Bit00 |f_act| P2157 (f_2) 0 NO 1 YES Bit02 |f_act| P2159 (f_3) 0 NO 1 YES Bit04 |f_set| < P2161 (f_min_set) 0 NO 1 YES Bit05 f_set > 0 0 NO 1 YES Bit06 Motor blocked 0 NO 1 YES Bit07 Motor pulled out 0 NO 1 YES Bit08 | I_act r0068 | > P2170 0 NO 1 YES Bit09 | m_act | > P2174 & setpoint reached 0 NO 1 YES Bit10 | m_act | > P2174 0 NO 1 YES Bit11 Belt failure warning 0 NO 1 YES Bit12 Belt failure trip 0 NO 1 YES

P2200[3] BI: Enable PID controller Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Allows user to enable/disable the PID controller.
P2200 settings :
0 1 BICO parameters
: PID controller de-activated : PID controller permanently activated : PID controller event-controlled, de-activated/activated
ADC
PID SUM PID PID
P2253 PID RFG
PID PT1
FF
−∆ PID
&
P2264 PID PT1
PID SCL
ADC2
Index:
P2200[0] : 1st. Command data set (CDS) P2200[1] : 2nd. Command data set (CDS) P2200[2] : 3rd. Command data set (CDS) Common Settings:
Parameter text Setting Meaning
PID controller always active 1.0
Digital input x 722.x
PID mode P2251 0 PID as setpoint
2224 Fixed PID setpoint (PID-FF)
Analog input 1 755.0
USS on BOP link 2015.1
USS on COM link 2019.1
CB on COM link 2050.1
Analog input 2 755.1
Dependency:
Setting 1 automatically disables normal ramp times set in P1120 and P1121 and the normal frequency setpoints. Following an OFF1 or OFF3 command, however, the inverter frequency will ramp down to zero using the ramp time set in P1121 (P1135 for OFF3). Note:
The PID setpoint source is selected using P2253. The PID setpoint and the PID feedback signal are interpreted as [%] values (not [Hz]). The output of the PID controller is displayed as [%] and then normalized into [Hz] through P2000 (reference frequency) when PID is enabled. In level 3, the PID controller source enable can also come from the digital inputs in settings 722.0 to 722.5 for DIN1 to DIN6 or from any other BiCo source. The minimum and maximum motor frequencies (P1080 and P1082) as well as the skip frequencies (P1091 to P1094) remain active on the inverter output. However, enabling skip frequencies with PID control can produce instabilities.

P2201[3] Fixed PID setpoint 1 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 0.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 1 There are three options available for selection of the PID fixed setpoints: 1. Direct selection 2. Direct selection + ON command 3. Binary coded selection + ON command 1. Direct selection (P0701 - P0706 = 15): - In this mode of operation, 1 digital input selects one PID fixed setpoint. - If several inputs are active together, the selected setpoints are summed. - E.g.: PID-FF1 + PID-FF2 + PID-FF3 + PID-FF4 + PID-FF5 + PID-FF6. 2. Direct selection + ON command (P0701 - P0706 = 16): - In this mode of operation the PID fixed setpoints are combined with an ON command. - Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint selection. - If several inputs are active together, the selected setpoints are summed. - E.g.: PID-FF1 + PID-FF2 + PID-FF3 + PID-FF4 + PID-FF5 + PID-FF6. 3. Binary coded selection + ON command (P0701 - P0706 = 17): - Using this method to select the fixed PID setpoint (FF-PID) allows you to choose up to 16 different PID setpoints. - The setpoints are selected according to the following table: Index:
P2201[0] : 1st. Drive data set (DDS) P2201[1] : 2nd. Drive data set (DDS) P2201[2] : 3rd. Drive data set (DDS) Example:
Binary coded selection :
DIN4 DIN3 DIN2 DIN1 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 0 0 0 1 0 0 1 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1
PID - FF0 PID - FF1 PID - FF2 PID - FF3 PID - FF4 PID - FF5 PID - FF6 PID - FF7 PID - FF8 PID - FF9 PID - FF10 PID - FF11 PID - FF12 PID - FF13 PID - FF14 PID - FF15
P1010 P1011 P1012 P1013 P1014 P1015
0 %

Direct selection of PID-FF1 P2201 via DIN 1:
P0701 = 15 or P0701 = 99, P2220 = 722.0, P2216 = 1
r0722.0
Dependency:
P2200 = 1 required in user access level 2 to enable setpoint source. Note:
You may mix different types of frequencies; however, remember that they will be summed if selected together. P2201 = 100 % corresponds to 4000 hex P2202[3] Fixed PID setpoint 2 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 10.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 2 Index:
P2202[0] : 1st. Drive data set (DDS) P2202[1] : 2nd. Drive data set (DDS) P2202[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2203[3] Fixed PID setpoint 3 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 20.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 3 Index:
P2203[0] : 1st. Drive data set (DDS) P2203[1] : 2nd. Drive data set (DDS) P2203[2] : 3rd. Drive data set (DDS) Details:
See P2201 fixed PID setpoint 1 (FF-PID 1). P2204[3] Fixed PID setpoint 4 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 30.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 4 Index:
P2204[0] : 1st. Drive data set (DDS) P2204[1] : 2nd. Drive data set (DDS) P2204[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2205[3] Fixed PID setpoint 5 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 40.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 5 Index:
P2205[0] : 1st. Drive data set (DDS) P2205[1] : 2nd. Drive data set (DDS) P2205[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1).
2,3 · r2224

P2206[3] Fixed PID setpoint 6 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 50.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 6 Index:
P2206[0] : 1st. Drive data set (DDS) P2206[1] : 2nd. Drive data set (DDS) P2206[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2207[3] Fixed PID setpoint 7 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 60.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 7 Index:
P2207[0] : 1st. Drive data set (DDS) P2207[1] : 2nd. Drive data set (DDS) P2207[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2208[3] Fixed PID setpoint 8 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 70.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 8 Index:
P2208[0] : 1st. Drive data set (DDS) P2208[1] : 2nd. Drive data set (DDS) P2208[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2209[3] Fixed PID setpoint 9 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 80.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 9 Index:
P2209[0] : 1st. Drive data set (DDS) P2209[1] : 2nd. Drive data set (DDS) P2209[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2210[3] Fixed PID setpoint 10 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 90.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 10 Index:
P2210[0] : 1st. Drive data set (DDS) P2210[1] : 2nd. Drive data set (DDS) P2210[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2211[3] Fixed PID setpoint 11 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 11 Index:
P2211[0] : 1st. Drive data set (DDS) P2211[1] : 2nd. Drive data set (DDS) P2211[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1).

P2212[3] Fixed PID setpoint 12 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 110.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 12 Index:
P2212[0] : 1st. Drive data set (DDS) P2212[1] : 2nd. Drive data set (DDS) P2212[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2213[3] Fixed PID setpoint 13 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 120.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 13 Index:
P2213[0] : 1st. Drive data set (DDS) P2213[1] : 2nd. Drive data set (DDS) P2213[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2214[3] Fixed PID setpoint 14 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 130.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 14 Index:
P2214[0] : 1st. Drive data set (DDS) P2214[1] : 2nd. Drive data set (DDS) P2214[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2215[3] Fixed PID setpoint 15 Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 130.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 15 Index:
P2215[0] : 1st. Drive data set (DDS) P2215[1] : 2nd. Drive data set (DDS) P2215[2] : 3rd. Drive data set (DDS) Details:
See P2201 (Fixed PID Setpoint 1). P2216[3] Fixed PID setpoint mode - Bit 0 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 3
Fixed frequencies for PID setpoint can be selected in three different modes. Parameter P2216 defines the mode of selection Bit 0. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P2216[0] : 1st. Command data set (CDS) P2216[1] : 2nd. Command data set (CDS) P2216[2] : 3rd. Command data set (CDS) P2217[3] Fixed PID setpoint mode - Bit 1 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 3
BCD or direct selection Bit 1 for PID setpoint. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P2217[0] : 1st. Command data set (CDS) P2217[1] : 2nd. Command data set (CDS) P2217[2] : 3rd. Command data set (CDS)

P2218[3] Fixed PID setpoint mode - Bit 2 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 3
BCD or direct selection Bit 2 for PID setpoint. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P2218[0] : 1st. Command data set (CDS) P2218[1] : 2nd. Command data set (CDS) P2218[2] : 3rd. Command data set (CDS) P2219[3] Fixed PID setpoint mode - Bit 3 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 3
BCD or direct selection Bit 3 for PID setpoint. Possible Settings:
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command Index:
P2219[0] : 1st. Command data set (CDS) P2219[1] : 2nd. Command data set (CDS) P2219[2] : 3rd. Command data set (CDS) P2220[3] BI: Fixed PID setp. select Bit 0 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 0 Index:
P2220[0] : 1st. Command data set (CDS) P2220[1] : 2nd. Command data set (CDS) P2220[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) P2221[3] BI: Fixed PID setp. select Bit 1 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 1. Index:
P2221[0] : 1st. Command data set (CDS) P2221[1] : 2nd. Command data set (CDS) P2221[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)

P2222[3] BI: Fixed PID setp. select Bit 2 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 0:0 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 2 Index:
P2222[0] : 1st. Command data set (CDS) P2222[1] : 2nd. Command data set (CDS) P2222[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) P2223[3] BI: Fixed PID setp. select Bit 3 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:3 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 3 Index:
P2223[0] : 1st. Command data set (CDS) P2223[1] : 2nd. Command data set (CDS) P2223[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) r2224 CO: Act. fixed PID setpoint Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays total output of PID fixed setpoint selection. Note:
r2224 = 100 % corresponds to 4000 hex P2225[3] Fixed PID setpoint mode - Bit 4 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 2
Direct selection or direct selection + ON Bit 4 for PID setpoint. Possible Settings:
1 Direct selection 2 Direct selection + ON command Index:
P2225[0] : 1st. Command data set (CDS) P2225[1] : 2nd. Command data set (CDS) P2225[2] : 3rd. Command data set (CDS) P2226[3] BI: Fixed PID setp. select Bit 4 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:4 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 4 Index:
P2226[0] : 1st. Command data set (CDS) P2226[1] : 2nd. Command data set (CDS) P2226[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)

P2227[3] Fixed PID setpoint mode - Bit 5 Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 2
Direct selection / direct selection + ON Bit 5 for PID setpoint. Possible Settings:
1 Direct selection 2 Direct selection + ON command Index:
P2227[0] : 1st. Command data set (CDS) P2227[1] : 2nd. Command data set (CDS) P2227[2] : 3rd. Command data set (CDS) P2228[3] BI: Fixed PID setp. select Bit 5 Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 722:5 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 5 Index:
P2228[0] : 1st. Command data set (CDS) P2228[1] : 2nd. Command data set (CDS) P2228[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) P2231[3] Setpoint memory of PID-MOP Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: Immediately QuickComm.: No Max: 1
Setpoint memory Possible Settings:
0 PID-MOP setpoint will not be stored 1 PID-MOP setpoint will be stored (P2240 is updated) Index:
P2231[0] : 1st. Drive data set (DDS) P2231[1] : 2nd. Drive data set (DDS) P2231[2] : 3rd. Drive data set (DDS) Dependency:
If 0 selected, setpoint returns to value set in P2240 (setpoint of PID-MOP) after an OFF command. If 1 is selected, active setpoint is "remembered" and P2240 updated with current value. Details:
See P2240 (setpoint of PID-MOP) P2232 Inhibit neg. PID-MOP setpoints Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: TECH Active: first confirm QuickComm.: No Max: 1
This parameter suppresses negative setpoints of the PID-MOP output r2250. Possible Settings:
0 Neg. PID-MOP setpoint is allowed 1 Neg. PID-MOP setpoint inhibited Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease frequency either by using digital inputs or motor potentiometer up/down buttons.

P2235[3] BI: Enable PID-MOP (UP-cmd) Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 19:13 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of UP command. Index:
P2235[0] : 1st. Command data set (CDS) P2235[1] : 2nd. Command data set (CDS) P2235[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 19.D = Keypad UP button Dependency:
To change setpoint: 1. Use UP / DOWN key on BOP or 2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3) P2236[3] BI: Enable PID-MOP (DOWN-cmd) Min: 0:0 CStat: CT Datatype: U32 Unit: - Def: 19:14 P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of DOWN command. Index:
P2236[0] : 1st. Command data set (CDS) P2236[1] : 2nd. Command data set (CDS) P2236[2] : 3rd. Command data set (CDS) Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO) 722.1 = Digital input 2 (requires P0702 to be set to 99, BICO) 722.2 = Digital input 3 (requires P0703 to be set to 99, BICO) 722.3 = Digital input 4 (requires P0704 to be set to 99, BICO) 722.4 = Digital input 5 (requires P0705 to be set to 99, BICO) 722.5 = Digital input 6 (requires P0706 to be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99) 722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99) 19.E = Keypad DOWN button Dependency:
To change setpoint: 1. Use UP / DOWN key on BOP or 2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3) P2240[3] Setpoint of PID-MOP Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 10.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Setpoint of the motor potentiometer. Allows user to set a digital PID setpoint in [%]. Index:
P2240[0] : 1st. Drive data set (DDS) P2240[1] : 2nd. Drive data set (DDS) P2240[2] : 3rd. Drive data set (DDS) Note:
P2240 = 100 % corresponds to 4000 hex


r2250 CO: Output setpoint of PID-MOP Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
r2250 = 100 % corresponds to 4000 hex P2251 PID mode Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: Immediately QuickComm.: No Max: 1
Configuration of PID controller. Possible Settings:
0 PID as setpoint 1 PID as trim Common Settings:
In addition to the open-loop/closed-loop control of a three-phase motor (standard applications for a drive inverter), MICROMASTER has a technological controller that can be used to control (closed-loop) process quantities such as pressure, filling level or control a winder. These applications and the closed-loop control structures required to implement these are shown in the following diagram.


These structures are selected using parameters P2200 and P2251 (refer to the following table).

Closed-loop dancer roll control is selected with P2251 = P2200 = 1. Important parameters and the structure are shown in the following diagrams.

Dependency:
Active when PID loop is enabled (see P2200).

P2253[3] CI: PID setpoint Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Defines setpoint source for PID setpoint input.

FF
ADC2
Index:
P2253[0] : 1st. Command data set (CDS) P2253[1] : 2nd. Command data set (CDS) P2253[2] : 3rd. Command data set (CDS) Common Settings:

P2254[3] CI: PID trim source Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to the PID setpoint. Index:
P2254[0] : 1st. Command data set (CDS) P2254[1] : 2nd. Command data set (CDS) P2254[2] : 3rd. Command data set (CDS) Common Settings:
See parameter P2253 P2255 PID setpoint gain factor Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 100.00
Gain factor for PID setpoint. The PID setpoint input is multiplied by this gain factor to produce a suitable ratio between setpoint and trim. P2256 PID trim gain factor Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 100.00
Gain factor for PID trim. This gain factor scales the trim signal, which is added to the main PID setpoint.
USS BOP link · USS COM link · CB COM link

P2257 Ramp-up time for PID setpoint Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 1.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 650.00
Sets the ramp-up time for the PID setpoint.
t12 P2257 % 100 x x t
1 2 12 ⋅ − =
Dependency:
P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120). PID ramp time effective only on PID setpoint and only active - when PID setpoint is changed or - when RUN command is given. Notice:
Setting the ramp-up time too short may cause the inverter to trip, on overcurrent for example. P2258 Ramp-down time for PID setpoint Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 1.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 650.00
Sets ramp-down time for PID setpoint.
t21 P2258 % 100 x x t
2 1 21 ⋅ − =
Dependency:
- P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120). - PID setpoint ramp effective only on PID setpoint changes. - P1121 (ramp-down time) and P1135 (OFF3 ramp-down time) define the ramp times used after OFF1 and OFF3 respectively. Notice:
Setting the ramp-down time too short can cause the inverter to trip on overvoltage (F0002) / overcurrent (F0001). r2260 CO: PID setpoint after PID-RFG Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays total active PID setpoint after PID-RFG in [%]. Note:
r2260 = 100 % corresponds to 4000 hex

P2261 PID setpoint filter timeconstant Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 60.00
Sets a time constant for smoothing the PID setpoint. Note:
0 = no smoothing r2262 CO: Filtered PID setp. after RFG Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays the filtered PID setpoint after the PID ramp-function generator (PID_HLG) as percentage. Parameter r2262 is obtained from the filtered parameter r2260 that is filtered using the PT1 filter with time constant P2261. Note:
r2262 = 100 % corresponds to 4000 hex P2263 PID controller type Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: Immediately QuickComm.: No Max: 1
Sets the PID controller type. Possible Settings:
0 D component on feedback signal 1 D component on error signal P2264[3] CI: PID feedback Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Selects the source of the PID feedback signal. Index:
P2264[0] : 1st. Command data set (CDS) P2264[1] : 2nd. Command data set (CDS) P2264[2] : 3rd. Command data set (CDS) Common Settings:
Parameter text Setting Meaning
PID controller always active 1.0
Digital input x 722.x
PID mode P2251 0 PID as setpoint
2224 Fixed PID setpoint (PID-FF)
Analog input 1 755.0
USS on BOP link 2015.1
USS on COM link 2019.1
CB on COM link 2050.1
Analog input 2 755.1
When analog input is selected, offset and gain can be implemented using parameters P0756 to P0760 (ADC scaling). P2265 PID feedback filter timeconstant Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 0.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 60.00
Defines time constant for PID feedback filter. r2266 CO: PID filtered feedback Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays PID feedback signal in [%]. Note:
r2266 = 100 % corresponds to 4000 hex
Parameter · PID controller de-activated · BICO parameter

P2267 Max. value for PID feedback Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Sets the upper limit for the value of the feedback signal in [%]. Note:
- P2267 = 100 % corresponds to 4000 hex - When PID is enabled (P2200 = 1) and the signal rises above this value, the inverter will trip with F0222 . P2268 Min. value for PID feedback Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 0.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Sets lower limit for value of feedback signal in [%]. Note:
- P2268 = 100 % corresponds to 4000 hex - When PID is enabled (P2200 = 1) and the signal rises below this value, the inverter will trip with F0221. P2269 Gain applied to PID feedback Min: 0.00 CStat: CUT Datatype: Float Unit: - Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 500.00
Allows the user to scale the PID feedback as a percentage value [%]. A gain of 100.0 % means that feedback signal has not changed from its default value. P2270 PID feedback function selector Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: Immediately QuickComm.: No Max: 3
Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269 (gain applied to PID feedback). Possible Settings:
0 Disabled 1 Square root (root(x)) 2 Square (x*x) 3 Cube (x*x*x) P2271 PID transducer type Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: Immediately QuickComm.: No Max: 1
Allows the user to select the transducer type for the PID feedback signal. Possible Settings:
0 Disabled 1 Inversion of PID feedback signal Notice:
It is essential that you select the correct tranducer type. If you are unsure whether 0 or 1 is applicable, you can determine the correct type as follows: 1. Disable the PID function (P2200 = 0). 2. Increase the motor frequency while measuring the feedback signal. 3. If the feedback signal increases with an increase in motor frequency, the PID transducer type should be 0. 4. If the feedback signal decreases with an increase in motor frequency the PID transducer type should be set to 1. r2272 CO: PID scaled feedback Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays PID scaled feedback signal in [%]. Note:
r2272 = 100 % corresponds to 4000 hex r2273 CO: PID error Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays PID error (difference) signal between setpoint and feedback signals in [%]. Note:
r2273 = 100 % corresponds to 4000 hex

P2274 PID derivative time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 0.000 P-Group: TECH Active: Immediately QuickComm.: No Max: 60.000
Sets PID derivative time. P2274 = 0: The derivative term does not have any effect (it applies a gain of 1). P2280 PID proportional gain Min: 0.000 CStat: CUT Datatype: Float Unit: - Def: 3.000 P-Group: TECH Active: Immediately QuickComm.: No Max: 65.000
Allows user to set proportional gain for PID controller. The PID controller is implemented using the standard model.

For best results, enable both P and I terms. Dependency:
P2280 = 0 (P term of PID = 0): I term acts on the square of the error signal. P2285 = 0 (I term of PID = 0): PID controller acts as a P or PD controller respectively. Note:
- If the system is prone to sudden step changes in the feedback signal, P term should normally be set to a small value (0.5) with a faster I term for optimum performance. - The D term (P2274) multiplies the difference between the present and previous feedback signal thus accelerating the controller reaction to an error that appears suddenly. - The D term should be used carefully, since it can cause the controller output to fluctuate as every change in the feedback signal is amplified by the controller derivative action. P2285 PID integral time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 0.000 P-Group: TECH Active: Immediately QuickComm.: No Max: 60.000
Sets integral time constant for PID controller. Details:
See P2280 (PID proportional gain). P2291 PID output upper limit Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Sets upper limit for PID controller output in [%]. Dependency:
If F max (P1082) is greater than P2000 (reference frequency), either P2000 or P2291 (PID output upper limit) must be changed to achieve F max. Note:
P2291 = 100 % corresponds to 4000 hex (as defined by P2000 (reference frequency)).

P2292 PID output lower limit Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 0.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Sets lower limit for the PID controller output in [%]. Dependency:
A negative value allows bipolar operation of PID controller. Note:
P2292 = 100 % corresponds to 4000 hex P2293 Ramp-up /-down time of PID limit Min: 0.00 CStat: CUT Datatype: Float Unit: s Def: 1.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 100.00
Sets maximum ramp rate on output of PID. When PI is enabled, the output limits are ramped up from 0 to the limits set in P2291 (PID output upper limit) and P2292 (PID output lower limit). Limits prevent large step changes appearing on the output of the PID when the inverter is started. Once the limits have been reached, the PID controller output is instantaneous. These ramp times are used whenever a RUN command is issued. Note:
If an OFF1 or OFF 3 are issued, the inverter output frequency ramps down as set in P1121 (ramp-down time) or P1135 (OFF3 ramp-down time). r2294 CO: Act. PID output Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Displays PID output in [%] Note:
r2294 = 100 % corresponds to 4000 hex P2295 Gain applied to PID output Min: -100.00 CStat: CUT Datatype: Float Unit: - Def: 100.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 100.00
Allows the user to scale the PID output as a percentage value [%]. A gain of 100.0 % means that output signal has not changed from its default value. P2350 PID autotune enable Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: Immediately QuickComm.: No Max: 4
Enables autotune function of PID controller. Possible Settings:
0 PID autotuning disabled 1 PID autotuning via Ziegler Nichols (ZN) standard 2 PID autotuning as 1 plus some overshoot (O/S) 3 PID autotuning as 2 little or no overshoot (O/S) 4 PID autotuning PI only, quarter damped response Dependency:
Active when PID loop is enabled (see P2200). Note:
P2350 = 1 This is the standard Ziegler Nichols (ZN) tuning which should be a quarter damped response to a step. P2350 = 2 This tuning will give some overshoot (O/S) but should be faster than option 1 P2350 = 3 This tuning should give little or no overshoot but will not be as fast as option 2. P2350 = 4 This tuning only changes values of P and I and should be a quarter damped response. The option to be selected depends on the application but braodly speaking option 1 will give an all round good respsonse, whereas if a faster response is desired option 2 should be selected. If no overshoot is desired then option 3 is the choice. For cases where no D term is wanted then option 4 can be selected. The tuning procedure is the same for all options. It is just the calculation of P,I and D values that is different. After autotune this parameter is set to zero (autotune completed).

P2354 PID tuning timeout length Min: 60 CStat: CUT Datatype: U16 Unit: s Def: 240 P-Group: TECH Active: Immediately QuickComm.: No Max: 65000
This parameter determines the time that the auto tuning code will wait before aborting a tuning run if no oscillation has been obtained. P2355 PID tuning offset Min: 0.00 CStat: CUT Datatype: Float Unit: % Def: 5.00 P-Group: TECH Active: Immediately QuickComm.: No Max: 20.00
Sets applied offset and deviation for PID autotuning. Note:
This can be varied depending on plant conditions e.g. a very long system time constant might require a larger value.
P2480[3] Position mode Min: 1 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 1
Sets the mode for positioning mode. Possible Settings:
1 Open loop positioning Index:
P2480[0] : 1st. Drive data set (DDS) P2480[1] : 2nd. Drive data set (DDS) P2480[2] : 3rd. Drive data set (DDS) P2481[3] Gearbox ratio input Min: 0.01 CStat: CUT Datatype: Float Unit: - Def: 1.00 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 9999.99
Defines the ratio between number of motor shaft revolutions to equal one revolution of the gearbox output shaft.
n n Motor Load
Ü = P2482 P2481 = Motor revolutions
Index:
P2481[0] : 1st. Drive data set (DDS) P2481[1] : 2nd. Drive data set (DDS) P2481[2] : 3rd. Drive data set (DDS) P2482[3] Gearbox ratio output Min: 0.01 CStat: CUT Datatype: Float Unit: - Def: 1.00 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 9999.99
Defines the ratio between number of motor shaft revolutions to equal one revolution of the gearbox output shaft. Index:
P2482[0] : 1st. Drive data set (DDS) P2482[1] : 2nd. Drive data set (DDS) P2482[2] : 3rd. Drive data set (DDS)
Motor Gear · Load · Load revolutions

P2484[3] No. of shaft turns = 1 Unit Min: 0.01 CStat: CUT Datatype: Float Unit: - Def: 1.00 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 9999.99
Sets the number of rotations of the motor shaft required to represent 1 unit of user selected units.
U P2484
No. of revolutions
The following equation determines the number of motor shaft revolutions to stop:
2481 P 2484 P 2488 P ⋅ ⋅ = Revolutions Motor
Index:
P2484[0] : 1st. Drive data set (DDS) P2484[1] : 2nd. Drive data set (DDS) P2484[2] : 3rd. Drive data set (DDS) P2488[3] Distance / No. of revolutions Min: 0.01 CStat: CUT Datatype: Float Unit: - Def: 1.00 P-Group: CONTROL Active: first confirm QuickComm.: No Max: 9999.99
Sets the required distance or number of revolutions (see P2484).
f ⋅ = = 2 1 P2488 s
. t P2488 .
Index:
P2488[0] : 1st. Drive data set (DDS) P2488[1] : 2nd. Drive data set (DDS) P2488[2] : 3rd. Drive data set (DDS) r2489 Act. number of shaft revolutions Min: - Datatype: Float Unit: - Def: - P-Group: CONTROL Max: -
Displayes the actual number of shaft revolutions since trigger of positioning. Note:
Positioning ramp down is an open loop control method. So, there might be a difference between the position setpoint and the calculated actual position shown in r2489. That means, it could happen that the setpoint position is already reached, although r2489 displays a different actual position .
![Page 241 of the Siemens 440 user manual — P2801 [16] RS-FF 3](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-241.webp?w=400)
P2800 Enable FFBs Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 1
Free function blocks (FFB) are enabled in two steps. 1. Parameter P2800 enables all free function blocks , normally (P2800 = 1). 2. Parameters P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0 oder P2802[x] > 0). Possible Settings:
0 Disabled 1 Enabled Dependency:
All active function blocks will be calculated in every 132 ms. P2801[17] Activate FFBs Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 3
Free function blocks (FFB) are enabled in two steps. 1. Parameter P2800 enables all free function blocks , normally (P2800 = 1) 2. Parameters P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0 oder P2802[x] > 0) In addition, Parameters P2801 and P2802 determine the chronological order of each function block. The following table shows that the priority increases from left to right and from bottom to top.
3 2 1 0
P2802 [3] Timer 4
P2802 [2] Timer 3
P2802 [1] Timer 2
P2802 [0] Timer 1
P2801 [15] RS-FF 2
P2801 [14] RS-FF 1
P2802 [13] CMP 2
P2802 [12] CMP 1
P2802 [9] MUL 2
P2802 [8] MUL 1
P2802 [7] SUB 2
P2802 [6] SUB 1
P2802 [5] ADD 2
P2802 [4] ADD 1
P2801 [13] D-FF 2
P2801 [12] D-FF 1
P2801 [11] NOT 3
P2801 [10] NOT 2
P2801 [9] NOT 1
P2801 [8] XOR 3
P2801 [7] XOR 2
P2801 [6] XOR 1
P2801 [2] AND 3
P2801 [1] AND 2
P2801 [0] AND 1
P2802 [11] DIV 2
P2802 [10] DIV 1
P2801 [5] OR 3
P2801 [4] OR 2
P2801 [3] OR 1
Possible Settings:
0 Not Active 1 Level 1 2 Level 2 3 Level 3 Index:
P2801[0] : Enable AND 1 P2801[1] : Enable AND 2 P2801[2] : Enable AND 3 P2801[3] : Enable OR 1 P2801[4] : Enable OR 2 P2801[5] : Enable OR 3 P2801[6] : Enable XOR 1 P2801[7] : Enable XOR 2 P2801[8] : Enable XOR 3 P2801[9] : Enable NOT 1 P2801[10] : Enable NOT 2 P2801[11] : Enable NOT 3 P2801[12] : Enable D-FF 1 P2801[13] : Enable D-FF 2 P2801[14] : Enable RS-FF 1 P2801[15] : Enable RS-FF 2 P2801[16] : Enable RS-FF 3 Example:
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2 FFBs will be calculated in following order: P2802[3], P2801[3] , P2801[4], P2802[4] Dependency:
- Set P2800 to 1 to enable function blocks. - All active function blocks will be calculated in every 132 ms.
![Page 242 of the Siemens 440 user manual — P2801 [16] RS-FF 3](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-242.webp?w=400)
P2802[14] Activate FFBs Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 3
Free function blocks (FFB) are enabled in two steps. 1. Parameter P2800 enables all free function blocks , normally (P2800 = 1) 2. Parameters P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0 oder P2802[x] > 0) In addition, Parameters P2801 and P2802 determine the chronological order of each function block. The following table shows that the priority increases from left to right and from bottom to top.
3 2 1 0
P2802 [3] Timer 4
P2802 [2] Timer 3
P2802 [1] Timer 2
P2802 [0] Timer 1
P2801 [15] RS-FF 2
P2801 [14] RS-FF 1
P2802 [13] CMP 2
P2802 [12] CMP 1
P2802 [11] DIV 2
P2802 [10] DIV 1
P2802 [9] MUL 2
P2802 [8] MUL 1
P2802 [7] SUB 2
P2802 [6] SUB 1
P2802 [5] ADD 2
P2802 [4] ADD 1
P2801 [13] D-FF 2
P2801 [12] D-FF 1
P2801 [11] NOT 3
P2801 [10] NOT 2
P2801 [9] NOT 1
P2801 [8] XOR 3
P2801 [7] XOR 2
P2801 [6] XOR 1
P2801 [2] AND 3
P2801 [1] AND 2
P2801 [0] AND 1
P2801 [5] OR 3
P2801 [4] OR 2
P2801 [3] OR 1
Possible Settings:
0 Not Active 1 Level 1 2 Level 2 3 Level 3 Index:
P2802[0] : Enable timer 1 P2802[1] : Enable timer 2 P2802[2] : Enable timer 3 P2802[3] : Enable timer 4 P2802[4] : Enable ADD 1 P2802[5] : Enable ADD 2 P2802[6] : Enable SUB 1 P2802[7] : Enable SUB 2 P2802[8] : Enable MUL 1 P2802[9] : Enable MUL 2 P2802[10] : Enable DIV 1 P2802[11] : Enable DIV 2 P2802[12] : Enable CMP 1 P2802[13] : Enable CMP 2 Example:
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2 FFBs will be calculated in following order: P2802[3], P2801[3] , P2801[4], P2802[4] Dependency:
- Set P2800 to 1 to enable function blocks. - All active function blocks will be calculated in every 132 ms.

P2810[2] BI: AND 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2810[0], P2810[1] define inputs of AND 1 element, output is P2811.
A B C 0 1 0 1 0 0 1 1 1
C &
Index:
P2801[0] is active level for the AND element. r2811 BO: AND 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of AND 1 element. Displays and logic of bits defined in P2810[0], P2810[1]. Dependency:
P2801[0] is active level for the AND element. P2812[2] BI: AND 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2812[0], 2812[1] define inputs of AND 2 element, output is P2813. Index:
P2801[1] is active level for the AND element. r2813 BO: AND 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of AND 2 element. Displays and logic of bits defined in P2812[0], P2812[1]. Dependency:
P2801[1] is active level for the AND element. P2814[2] BI: AND 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2814[0], P2814[1] define inputs of AND 3 element, output is P2815. Index:
P2801[2] is active level for the AND element. r2815 BO: AND 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of AND 3 element. Displays and logic of bits defined in P2814[0], P2814[1]. Dependency:
P2801[2] is active level for the AND element.
Index0 · r2811 · Index1

P2816[2] BI: OR 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2816[0], P2816[1] define inputs of OR 1 element, output is P2817.
A B C 0 1 1 1 0 1
Index:
P2801[3] is active level for the OR element. r2817 BO: OR 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of OR 1 element. Displays or logic of bits defined in P2816[0], P2816[1]. Dependency:
P2801[3] is active level for the OR element. P2818[2] BI: OR 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2818[0], P2818[1] define inputs of OR 2 element, output is P2819. Index:
P2801[4] is active level for the OR element. r2819 BO: OR 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of OR 2 element. Displays or logic of bits defined in P2818[0], P2818[1]. Dependency:
P2801[4] is active level for the OR element. P2820[2] BI: OR 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2820[0], P2820[1] define inputs of OR 3 element, output is P2821. Index:
P2801[5] is active level for the OR element. r2821 BO: OR 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of OR 3 element. Displays or logic of bits defined in P2820[0], P2820[1]. Dependency:
P2801[5] is active level for the OR element.
Index0 · r2817 · Index1

P2822[2] BI: XOR 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2822[0], P2822[1] define inputs of XOR 1 element, output is P2823.
A B C 0 1 1 1 0 1 1 1 0 1 =
Index:
P2801[6] is active level for the XOR element. r2823 BO: XOR 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of XOR 1 element. Displays exclusive-or logic of bits defined in P2822[0], P2822[1]. Dependency:
P2801[6] is active level for the XOR element. P2824[2] BI: XOR 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2824[0], P2824[1] define inputs of XOR 2 element, output is P2825. Index:
P2801[7] is active level for the XOR element. r2825 BO: XOR 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of XOR 2 element. Displays exclusive-or logic of bits defined in P2824[0], P2824[1]. Dependency:
P2801[7] is active level for the XOR element. P2826[2] BI: XOR 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2826[0], P2826[1] define inputs of XOR 3 element, output is P2827. Index:
P2801[8] is active level for the XOR element. r2827 BO: XOR 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of XOR 3 element. Displays exclusive-or logic of bits defined in P2826[0], P2826[1]. Dependency:
P2801[8] is active level for the XOR element.
Index0 · r2823 · Index1

P2828 BI: NOT 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2828 defines input of NOT 1 element, output is P2829.

Dependency:
P2801[9] is active level for the NOT element. r2829 BO: NOT 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of NOT 1 element. Displays not logic of bit defined in P2828. Dependency:
P2801[9] is active level for the NOT element. P2830 BI: NOT 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2830 defines input of NOT 2 element, output is P2831. Dependency:
P2801[10] is active level for the NOT element. r2831 BO: NOT 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of NOT 2 element. Displays not logic of bit defined in P2830. Dependency:
P2801[10] is active level for the NOT element. P2832 BI: NOT 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2832 defines input of NOT 3 element, output is P2833. Dependency:
P2801[11] is active level for the NOT element. r2833 BO: NOT 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Output of NOT 3 element. Displays not logic of bit defined in P2832. Dependency:
P2801[11] is active level for the NOT element.

P2834[4] BI: D-FF 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2834[0], P2834[1], P2834[2], P2834[3] define inputs of D-FlipFlop 1, outputs are P2835, P2836.

Index:
P2834[0] : Binector input: Set P2834[1] : Binector input: D input P2834[2] : Binector input: Store pulse P2834[3] : Binector input: Reset Dependency:
P2801[12] is active level for the D-FlipFlop. r2835 BO: Q D-FF 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of D-FlipFlop 1, inputs are defined in P2834[0], P2834[1], P2834[2], P2834[3] Dependency:
P2801[12] is active level for the D-FlipFlop. r2836 BO: NOT-Q D-FF 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of D-FlipFlop 1, inputs are defined in P2834[0], P2834[1], P2834[2], P2834[3] Dependency:
P2801[12] is active level for the D-FlipFlop. P2837[4] BI: D-FF 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2837[0], P2837[1], P2837[2], P2837[3] define inputs of D-FlipFlop 2, outputs are P2838, 2839. Index:
P2837[0] : Binector input: Set P2837[1] : Binector input: D input P2837[2] : Binector input: Store pulse P2837[3] : Binector input: Reset Dependency:
P2801[13] is active level for the D-FlipFlop.

r2838 BO: Q D-FF 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of D-FlipFlop 2, inputs are defined in P2837[0], P2837[1], P2837[2], P2837[3] Dependency:
P2801[13] is active level for the D-FlipFlop. r2839 BO: NOT-Q D-FF 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of D-FlipFlop 2, inputs are defined in P2837[0], P2837[1], P2837[2], P2837[3] Dependency:
P2801[13] is active level for the D-FlipFlop. P2840[2] BI: RS-FF 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2840[0], P2840[1] define inputs of RS-FlipFlop 1, outputs are P2841, P2842.

Index:
P2801[14] is active level for the RS-FlipFlop. r2841 BO: Q RS-FF 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of RS-FlipFlop 1, inputs are defined in P2840[0], P2840[1] Dependency:
P2801[14] is active level for the RS-FlipFlop. r2842 BO: NOT-Q RS-FF 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of RS-FlipFlop 1, inputs are defined in P2840[0], P2840[1] Dependency:
P2801[14] is active level for the RS-FlipFlop. P2843[2] BI: RS-FF 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2843[0], P2843[1] define inputs of RS-FlipFlop 2, outputs are P2844, P2845. Index:
P2801[15] is active level for the RS-FlipFlop. r2844 BO: Q RS-FF 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of RS-FlipFlop 2, inputs are defined in P2843[0], P2843[1] Dependency:
P2801[15] is active level for the RS-FlipFlop.

r2845 BO: NOT-Q RS-FF 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of RS-FlipFlop 2, inputs are defined in P2843[0], P2843[1] Dependency:
P2801[15] is active level for the RS-FlipFlop. P2846[2] BI: RS-FF 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2846[0], P2846[1] define inputs of RS-FlipFlop 3, outputs are P2847, P2848. Index:
P2801[16] is active level for the RS-FlipFlop. r2847 BO: Q RS-FF 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1] Dependency:
P2801[16] is active level for the RS-FlipFlop. r2848 BO: NOT-Q RS-FF 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1] Dependency:
P2801[16] is active level for the RS-FlipFlop.

P2849 BI: Timer 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define input signal of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
P2800 P2802.0

P2851 = 3 (Pulse Generator)

Dependency:
P2802[0] is active level for the timer. P2850 Delay time of timer 1 Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 0.0 P-Group: TECH Active: first confirm QuickComm.: No Max: 9999.9
Defines delay time of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853. Dependency:
P2802[0] is active level for the timer.

P2851 Mode timer 1 Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 13
Selects mode of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853. Possible Settings:
0 ON delay (seconds) 1 OFF delay (seconds) 2 ON/OFF delay (seconds) 3 Pulse generator (seconds) 10 ON delay (minutes) 11 OFF delay (minutes) 12 ON/OFF delay (minutes) 13 Pulse generator (minutes) Dependency:
P2802[0] is active level for the timer. r2852 BO: Timer 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853. Dependency:
P2802[0] is active level for the timer. r2853 BO: Nout timer 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853. Dependency:
P2802[0] is active level for the timer. P2854 BI: Timer 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define input signal of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858. Dependency:
P2802[1] is active level for the timer. P2855 Delay time of timer 2 Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 0.0 P-Group: TECH Active: first confirm QuickComm.: No Max: 9999.9
Defines delay time of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858. Dependency:
P2802[1] is active level for the timer. P2856 Mode timer 2 Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 13
Selects mode of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858. Possible Settings:
0 ON delay (seconds) 1 OFF delay (seconds) 2 ON/OFF delay (seconds) 3 Pulse generator (seconds) 10 ON delay (minutes) 11 OFF delay (minutes) 12 ON/OFF delay (minutes) 13 Pulse generator (minutes) Dependency:
P2802[1] is active level for the timer. r2857 BO: Timer 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858. Dependency:
P2802[1] is active level for the timer.

r2858 BO: Nout timer 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of timer 2 P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858. Dependency:
P2802[1] is active level for the timer. P2859 BI: Timer 3 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define input signal of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863. Dependency:
P2802[2] is active level for the timer. P2860 Delay time of timer 3 Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 0.0 P-Group: TECH Active: first confirm QuickComm.: No Max: 9999.9
Defines delay time of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863. Dependency:
P2802[2] is active level for the timer. P2861 Mode timer 3 Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 13
Selects mode of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863. Possible Settings:
0 ON delay (seconds) 1 OFF delay (seconds) 2 ON/OFF delay (seconds) 3 Pulse generator (seconds) 10 ON delay (minutes) 11 OFF delay (minutes) 12 ON/OFF delay (minutes) 13 Pulse generator (minutes) Dependency:
P2802[2] is active level for the timer. r2862 BO: Timer 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863. Dependency:
P2802[2] is active level for the timer. r2863 BO: Nout timer 3 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863. Dependency:
P2802[2] is active level for the timer. P2864 BI: Timer 4 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 0:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define input signal of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868. Dependency:
P2802[3] is active level for the timer. P2865 Delay time of timer 4 Min: 0.0 CStat: CUT Datatype: Float Unit: - Def: 0.0 P-Group: TECH Active: first confirm QuickComm.: No Max: 9999.9
Defines delay time of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868. Dependency:
P2802[3] is active level for the timer.

P2866 Mode timer 4 Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: TECH Active: first confirm QuickComm.: No Max: 13
Selects mode of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868. Possible Settings:
0 ON delay (seconds) 1 OFF delay (seconds) 2 ON/OFF delay (seconds) 3 Pulse generator (seconds) 10 ON delay (minutes) 11 OFF delay (minutes) 12 ON/OFF delay (minutes) 13 Pulse generator (minutes) Dependency:
P2802[3] is active level for the timer. r2867 BO: Timer 4 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays output of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868. Dependency:
P2802[3] is active level for the timer. r2868 BO: Nout timer 4 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays Not-output of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868. Dependency:
P2802[3] is active level for the timer. P2869[2] CI: ADD 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Adder 1, result is in P2870.

Index:
P2802[4] is the active level for the Adder. r2870 CO: ADD 1 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Adder 1. Dependency:
P2802[4] is active level for the Adder. P2871[2] CI: ADD 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Adder 2, result is in P2872. Index:
P2802[5] is active level for the Adder. r2872 CO: ADD 2 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Adder 2. Dependency:
P2802[5] is active level for the Adder.

P2873[2] CI: SUB 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Subtracter 1, result is in P2874.

x1 - x2 > 200% → x1 - x2 < -200% →
Index:
P2802[6] is active level for the Subtracter. r2874 CO: SUB 1 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Subtracter 1. Dependency:
P2802[6] is active level for the Subtracter. P2875[2] CI: SUB 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Subtracter 2, result is in P2876. Index:
P2802[7] is active level for the Subtracter. r2876 CO: SUB 2 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Subtracter 2. Dependency:
P2802[7] is active level for the Subtracter. P2877[2] CI: MUL 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Multiplier 1, result is in P2878.

Index:
P2802[8] is active level for the Multiplier. r2878 CO: MUL 1 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Multiplier 1. Dependency:
P2802[8] is active level for the Multiplier.

P2879[2] CI: MUL 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Multiplier 2, result is in P2880. Index:
P2802[9] is active level for the Multiplier. r2880 CO: MUL 2 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Multiplier 2. Dependency:
P2802[9] is active level for the Multiplier. P2881[2] CI: DIV 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Divider 1, result is in P2882.
100% x1∗ P2800 P2802[10]
∗ Result = 200%
If:
% 100 1 x ∗
< - 200% → x2 100% x1
Index:
P2802[10] is active level for the Divider. r2882 CO: DIV 1 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Divider 1. Dependency:
P2802[10] is active level for the Divider. P2883[2] CI: DIV 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Define inputs of Divider 2, result is in P2884. Index:
P2802[11] is active level for the Divider. r2884 CO: DIV 2 Min: - Datatype: Float Unit: % Def: - P-Group: TECH Max: -
Result of Divider 2. Dependency:
P2802[11] is active level for the Divider.
![Page 256 of the Siemens 440 user manual — P2800 P2802[12]](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-256.webp?w=400)
P2885[2] CI: CMP 1 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Defines inputs of Comparator 1, output is P2886.
Out x1 ≥ x2 → Out = 1 x1 < x2 → Out = 0
Out = x1 ≥ x2
Index:
P2802[12] is active level for the Comparator. r2886 BO: CMP 1 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays result bit of Comparator 1. Dependency:
P2802[12] is active level for the Comparator. P2887[2] CI: CMP 2 Min: 0:0 CStat: CUT Datatype: U32 Unit: - Def: 755:0 P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
Defines inputs of Comparator 2, output is P2888. Index:
P2802[13] is active level for the Comparator. r2888 BO: CMP 2 Min: - Datatype: U16 Unit: - Def: - P-Group: TECH Max: -
Displays result bit of Comparator 2. Dependency:
P2802[13] is active level for the Comparator. P2889 CO: Fixed setpoint 1 in [%] Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 0.00 P-Group: TECH Active: first confirm QuickComm.: No Max: 200.00
Fixed percent setting 1.
Connector Setting in %
P2890 CO: Fixed setpoint 2 in [%] Min: -200.00 CStat: CUT Datatype: Float Unit: % Def: 0.00 P-Group: TECH Active: first confirm QuickComm.: No Max: 200.00
Fixed percent setting 2.
CMP Index0 · r2886 · Index1

P3900 End of quick commissioning Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: QUICK Active: first confirm QuickComm.: Yes Max: 3
Performs calculations necessary for optimized motor operation. After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically reset to their original value 0. Possible Settings:
0 No quick commissioning 1 Start quick commissioning with factory reset 2 Start quick commissioning 3 Start quick commissioning only for motor data Dependency:
Changeable only when P0010 = 1 (quick commissioning) Note:
P3900 = 1 : When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning", are retained; all other parameter changes, including the I/O settings, are lost. Motor calculations are also performed. P3900 = 2 : When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the motor calculations performed. P3900 = 3 : When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with this setting saves time (for example, if only motor rating plate data have been changed). Calculates a variety of motor parameters, overwriting previous values (see parameter P0340, setting P0340 = 1). P3950 Access of hidden parameters Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: ALWAYS Active: first confirm QuickComm.: No Max: 255
Accesses special parameters for development (expert only) and factory functionality (calibration parameter). r3954[13] CM version and GUI ID Min: - Datatype: U16 Unit: - Def: - P-Group: - Max: -
Used to classify firmware (only for SIEMENS internal purposes). Index:
r3954[0] : CM version (major release) r3954[1] : CM version (minor release) r3954[2] : CM version (baselevel or patch) r3954[3] : GUI ID r3954[4] : GUI ID r3954[5] : GUI ID r3954[6] : GUI ID r3954[7] : GUI ID r3954[8] : GUI ID r3954[9] : GUI ID r3954[10] : GUI ID r3954[11] : GUI ID major release r3954[12] : GUI ID minor release

P3980 Commissioning command selection Min: 0 CStat: T Datatype: U16 Unit: - Def: 0 P-Group: - Active: first confirm QuickComm.: No Max: 67
Toggles command and setpoint sources between freely programmable BICO parameters and fixed command/setpoint profiles for commissioning. The command and setpoint sources can be changed independently. The tens digit selects the command source, the ones digit the setpoint source. Possible Settings:
0 Cmd = BICO parameter Setpoint = BICO parameter 1 Cmd = BICO parameter Setpoint = MOP setpoint 2 Cmd = BICO parameter Setpoint = Analog setpoint 3 Cmd = BICO parameter Setpoint = Fixed frequency 4 Cmd = BICO parameter Setpoint = USS on BOP link 5 Cmd = BICO parameter Setpoint = USS on COM link 6 Cmd = BICO parameter Setpoint = CB on COM link 7 Cmd = BICO parameter Setpoint = Analog 2 setp 10 Cmd = BOP Setpoint = BICO parameter 11 Cmd = BOP Setpoint = MOP setpoint 12 Cmd = BOP Setpoint = Analog setpoint 13 Cmd = BOP Setpoint = Fixed frequency 15 Cmd = BOP Setpoint = USS on COM link 16 Cmd = BOP Setpoint = CB on COM link 17 Cmd = BOP Setpoint = Analog 2 setp 40 Cmd = USS on BOP link Setpoint = BICO parameter 41 Cmd = USS on BOP link Setpoint = MOP setpoint 42 Cmd = USS on BOP link Setpoint = Analog setpoint 43 Cmd = USS on BOP link Setpoint = Fixed frequency 44 Cmd = USS on BOP link Setpoint = USS on BOP link 45 Cmd = USS on BOP link Setpoint = USS on COM link 46 Cmd = USS on BOP link Setpoint = CB on COM link 47 Cmd = USS on BOP link Setpoint = Analog 2 setp 50 Cmd = USS on COM link Setpoint = BICO parameter 51 Cmd = USS on COM link Setpoint = MOP setpoint 52 Cmd = USS on COM link Setpoint = Analog setpoint 53 Cmd = USS on COM link Setpoint = Fixed frequency 54 Cmd = USS on COM link Setpoint = USS on BOP link 55 Cmd = USS on COM link Setpoint = USS on COM link 57 Cmd = USS on COM link Setpoint = Analog 2 setp 60 Cmd = CB on COM link Setpoint = BICO parameter 61 Cmd = CB on COM link Setpoint = MOP setpoint 62 Cmd = CB on COM link Setpoint = Analog setpoint 63 Cmd = CB on COM link Setpoint = Fixed frequency 64 Cmd = CB on COM link Setpoint = USS on BOP link 66 Cmd = CB on COM link Setpoint = CB on COM link 67 Cmd = CB on COM link Setpoint = Analog 2 setp P3981 Reset active fault Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALARMS Active: first confirm QuickComm.: No Max: 1
Resets active faults when changed from 0 to 1. Possible Settings:
0 No fault reset 1 Reset fault Note:
Automatically reset to 0. Details:
See r0947 (last fault code) r3986[2] Number of parameters Min: - Datatype: U16 Unit: - Def: - P-Group: - Max: -
Number of parameters on the drive Index:

4 Function Diagrams
- 10 - Function diagram 8 7 6 5 4 3 2 1
0010_Symbols.vsd MICROMASTER 440 16.01.2006 V2.1 Symbols in funktion diagrams
Selection switch (1 out of 4)
ON and OFF delay
Explanation of symbols used in the function diagrams
0 T
T 1 T 2
&
D
A
A
D
Parameter number.Command/Drive data set [Number indexes] (Default)
Parameter number.Command/Drive data set [Number indexes]
Parameter number.Command/Drive data set [Number indexes]
Parameter number.Command/Drive data set
Parameter number [Number indexes]
Connector/Binector output (Monitoring parameter)
Minimum ... Maximum value [Unit]
Connector output (Monitoring parameter)
Binector output (Monitoring parameter)
Connector input (Setting parameter)
Binector input (Setting parameter)
PNumber.C/D [3] (Default)
Min ... Max [Dim]
PNumber.C/D [3]
(Default) PNum.C/D [3]
PNum.C/D

- 1100 - Function diagram 8 7 6 5 4 3 2 1
functions Setpoint channel Motor control Modulator
Motor and inverter protection, Adaption of motor parameters
MICROMASTER 440 16.01.2006 V2.1 General Overview
1100_Overview.vsd Overview
AFM
MOP 3100 DOUT
FF 3200
JOG
PID
MOP
DIN 2000
ADC 2200
DAC 2300
BOP 2400
USS
USS
CB


- 1200 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Connection of External and Internal Setpoints


- 2000 - Function diagram 8 7 6 5 4 3 2 1

- 2100 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Digital Outputs
Kl.20
Kl.19
Kl.18
COM Kl.22
Kl.21
Kl.25
Kl.24
Kl.23
COM
2100_DOUT.vsd External Interfaces
NC
NO
NO
NC
0 ... 7 P0748 (0) CO/BO: State DOUTs
0 ... 7 P0748 (0) CO/BO: State DOUTs
0 ... 7 P0748 (0) CO/BO: State DOUTs
(52:3)
(52:7)
(0:0)
P0733.C
P0732.C


- 2200 - Function diagram 8 7 6 5 4 3 2 1
0 ... 10000 [ms] P0762 [2] (10) 50 % of P0761

Act. DAC value[mA]
- 2300 - Function diagram
8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Analog Output (DAC)
x20mA 100 %
-99999.0 ... 99999.0 [%]
Value x2:DAC scal.
x2 x1
-99999.0 ... 99999.0 [%]
Value x1:DAC scal.
4000 h 4000 h 20 mA
Value y2:DAC scal.
Value y1:DAC scal.
Enable ab. value
0 ... 1000 [ms] P0773 [2] (2)


is selected, a changeover to the value display has taken place with the toggle key and the
- 2400 - Function diagram 8 7 6 5 4 3 2 1
Activation of the raise and lower keys is only effective if the operating display (r0000)

- 2500 - Function diagram 8 7 6 5 4 3 2 1
Bit14 Motor potentiometer MOP down
Bit15 Command data set (CDS) Bit 1
Bit11 Reverse (setpoint inversion)
Bit13 Motor potentiometer MOP up
Bit15 CDS Bit 0 (Local/Remote)
Bit04 Drive data set (DDS) Bit 0
Bit05 Drive data set (DDS) Bit 1
MICROMASTER 440 16.01.2006 V2.1 USS on BOP link, Receiving
Bit00 Fixed frequency Bit 0
Bit01 Fixed frequency Bit 1
Bit02 Fixed frequency Bit 2
Bit03 Fixed frequency Bit 3
Bit09 DC brake enabled
Bit10 Control from PLC
Bit13 External fault 1
2500_USSonBOP.vsd External Interfaces
telegram received via USS so that the converter
Bit 10 must be set in the first PZD word of the
being valid. For this reason, the control word 1
must be transferred to the converter in the first
will accept the process data as
PZD word.
Receive telegram RxD Receive
USS
PKW 0 7 6 5 4 3 2 1
Change par. via
0 ... 65535 [ms] P2014 [2] (0)
All parameters:

- 2510 - Function diagram 8 7 6 5 4 3 2 1
USS
ADR BCC PZD
MICROMASTER 440 16.01.2006 V2.1 USS on BOP link, Transmitting
Change par. via
0 ... 65535 [ms] P2014 [2] (0)
PKW 0 7 6 5 4 3 2 1
All parameters:
2510_USSonBOP.vsd External Interfaces
Bit2 = 1 Note:
PZD
Bit10 PID output r2294 == P2292 (PID_min)
Bit11 PID output r2294 == P2291 (PID_max)
Bit02 Act. freq. r0021 > P1080 (f_min)
Bit01 Act. freq. r0021 > P2167 (f_off)
Bit04 Act. freq. r0021 >= P2155 (f_1)
Bit05 Act. freq. r0021 < P2155 (f_1)
Bit08 Deviation setpoint / act. value
Bit14 Download data set 0 from AOP
Bit15 Download data set 1 from AOP
Bit10 Maximum frequency reached
Bit03 Act. current r0027 >= P2170
Bit06 Act. freq. r0021 >= setpoint
Bit12 Motor holding brake active
Bit07 Act. Vdc r0026 < P2172
Bit08 Act. Vdc r0026 > P2172
Bit07 Drive warning active
Bit01 Drive ready to run
Bit03 Drive fault active
Bit06 ON inhibit active
Bit14 Motor runs right
Bit00 DC brake active

- 2600 - Function diagram 8 7 6 5 4 3 2 1
Bit14 Motor potentiometer MOP down
Bit15 Command data set (CDS) Bit 1
Bit11 Reverse (setpoint inversion)
Bit13 Motor potentiometer MOP up
Bit15 CDS Bit 0 (Local/Remote)
Bit04 Drive data set (DDS) Bit 0
Bit05 Drive data set (DDS) Bit 1
Bit00 Fixed frequency Bit 0
Bit01 Fixed frequency Bit 1
Bit02 Fixed frequency Bit 2
Bit03 Fixed frequency Bit 3
MICROMASTER 440 16.01.2006 V2.1 USS on COM link, Receiving
Bit09 DC brake enabled
Bit10 Control from PLC
Bit13 External fault 1
2600_USSonCOM.vsd External Interfaces
telegram received via USS so that the converter
Bit 10 must be set in the first PZD word of the
word 1 must be transferred to the converter
being valid. For this reason, the control
will accept the process data as
in the first PZD word.
PZD
Receive telegram RxD Receive
USS
PKW 0 7 6 5 4 3 2 1
Change par. via
0 ... 65535 [ms] P2014 [2] (0)
All parameters:

- 2610 - Function diagram 8 7 6 5 4 3 2 1
USS
ADR BCC PZD
MICROMASTER 440 16.01.2006 V2.1 USS on COM link, Transmitting
Change par. via
0 ... 65535 [ms] P2014 [2] (0)
All parameters:
2610_USSonCOM.vsd External Interfaces
PZD
Bit10 PID output r2294 == P2292 (PID_min)
Bit11 PID output r2294 == P2291 (PID_max)
Bit01 Act. freq. r0021 > P2167 (f_off)
Bit02 Act. freq. r0021 > P1080 (f_min)
Bit04 Act. freq. r0021 >= P2155 (f_1)
Bit05 Act. freq. r0021 < P2155 (f_1)
Bit14 Download data set 0 from AOP
Bit15 Download data set 1 from AOP
Bit08 Deviation setpoint / act. value
Bit10 Maximum frequency reached
Bit03 Act. current r0027 >= P2170
Bit12 Motor holding brake active
Bit06 Act. freq. r0021 >= setpoint
Bit07 Act. Vdc r0026 < P2172
Bit08 Act. Vdc r0026 > P2172
Bit07 Drive warning active
Bit01 Drive ready to run
Bit03 Drive fault active
Bit06 ON inhibit active
Bit14 Motor runs right
Bit00 DC brake active

- 2700 - Function diagram 8 7 6 5 4 3 2 1
Bit14 Motor potentiometer MOP down
Bit15 Command data set (CDS) Bit 1
Bit11 Reverse (setpoint inversion)
Bit13 Motor potentiometer MOP up
Bit15 CDS Bit 0 (Local/Remote)
Bit04 Drive data set (DDS) Bit 0
Bit05 Drive data set (DDS) Bit 1
MICROMASTER 440 16.01.2006 V2.1 CB on COM link, Receiving
Bit00 Fixed frequency Bit 0
Bit01 Fixed frequency Bit 1
Bit02 Fixed frequency Bit 2
Bit03 Fixed frequency Bit 3
Bit09 DC brake enabled
Bit10 Control from PLC
Bit13 External fault 1
2700_CBonCOM.vsd External Interfaces
telegram received via USS so that the converter
Bit 10 must be set in the first PZD word of the
word 1 must be transferred to the converter
being valid. For this reason, the control
will accept the process data as
in the first PZD word.
PZD
Receive telegram RxD Receive
CB
Change par. via
0 ... 65535 [ms] P2040 (20)
CB tel. off time

- 2710 - Function diagram 8 7 6 5 4 3 2 1
PKW 7 6 5 4 3 2 1 CB-Frame CB-Frame 0
MICROMASTER 440 16.01.2006 V2.1 CB on COM link, Transmitting
Change par. via
CB tel. off time
0 ... 65535 [ms] P2040 (20)
2710_CBonCOM.vsd External Interfaces
PZD
Bit10 PID output r2294 == P2292 (PID_min)
Bit11 PID output r2294 == P2291 (PID_max)
Bit02 Act. freq. r0021 > P1080 (f_min)
Bit01 Act. freq. r0021 > P2167 (f_off)
Bit04 Act. freq. r0021 >= P2155 (f_1)
Bit05 Act. freq. r0021 < P2155 (f_1)
Bit08 Deviation setpoint / act. value
Bit14 Download data set 0 from AOP
Bit15 Download data set 1 from AOP
Bit10 Maximum frequency reached
Bit03 Act. current r0027 >= P2170
Bit06 Act. freq. r0021 >= setpoint
Bit12 Motor holding brake active
Bit07 Act. Vdc r0026 < P2172
Bit08 Act. Vdc r0026 > P2172
Bit07 Drive warning active
Bit01 Drive ready to run
Bit03 Drive fault active
Bit06 ON inhibit active
Bit14 Motor runs right
Bit00 DC brake active

- 3100 - Function diagram 8 7 6 5 4 3 2 1
CO: MOP outp.freq.
MICROMASTER 440 16.01.2006 V2.1 Motor Potentiometer (MOP)
Inh. neg. MOP setp
3100_MOP.vsd Internal Setpoint Source
MOP setp. memory
MOP output start value
-650.00 ... 650.00 [Hz]
0.00 ... 650.00 [Hz] P1082.D (50.00) MOP
&
Max. frequency
BI:Enable MOP(DWN)
(722:0)
(19:13)
(19:14)
P1035.C
P1036.C
r1050 · control · MOP setpoint


- 3200 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Fixed Frequency (FF) bit coded
(P1016 - P1019, P1025, P1027 = 1 or 2)


- 3210 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Fixed Frequency (FF) binary coded


- 3300 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Fixed PID setpoint, bit coded
(P2216 - P2219, P2225, P2227 = 1 or 2)


- 3310 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Fixed PID setpoint, binary coded

- 3400 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 PID Motor Potentiometer (PID-MOP)
Inh. neg. PID-MOP
3400_PIDMOP.vsd Internal Setpoint Source
PID-MOP setp. mem.
PID-MOP output start value
-200.00 ... 200.00 [%]
Setp. of PID-MOP
0.00 ... 650.00 [Hz] P1082.D (50.00) PID-MOP
12.00 ... 650.00 [Hz] P0310.D (50.00)
BI: PID-MOP (DWN)
(19:13)
(19:14)
Max. frequency
P2236.C


- 4100 - Function diagram 8 7 6 5 4 3 2 1


- 4110 - Function diagram 8 7 6 5 4 3 2 1


so that the converter will accept the process data as being
- 4150 - Function diagram 8 7 6 5 4 3 2 1
0 = ON/OFF1, Shutdown via ramp, followed by pulse disable 1 = ON, operating condition (edge-controlled)
0 = NO 1 = Motor potentiometer MOP down
0 = NO 1 = Motor potentiometer MOP up
1 = Reverse (setpoint inversion) 0 = Revers disabled
0 = NO 1 = CDS Bit 0 (local/remote)
1 = RFG setpoint enable 0 = Setpoint disable
1 = Control from PLC 0 = No control from PLC
1 = RFG enable 0 = Set RFG to 0
9 8 11 10 13 12 15 14 Segment Bit


- 4160 - Function diagram 8 7 6 5 4 3 2 1
0 = NO 1 = Torque control (only SLVC/VC)
0 = NO 1 = Command data set (CDS) Bit 1
0 = NO 1 = Drive data set (DDS) Bit 0
0 = NO 1 = Drive data set (DDS) Bit 1
0 = NO 1 = Fixed frequency Bit 0
0 = NO 1 = Fixed frequency Bit 1
0 = NO 1 = Fixed frequency Bit 2
0 = NO 1 = Fixed frequency Bit 3
0 = External fault 1 1 = No external fault
9 8 11 10 13 12 15 14 Segment Bit

control (software) for realizing the drive
- 4170 - Function diagram 8 7 6 5 4 3 2 1
1 (x.x) P0731..P0733
MICROMASTER if connected to a digital
output which means that the relay will be
Signal "Fault active" is inverted by
in the de-energised state.
MICROMASTER 440 16.01.2006 V2.1 Status word 1 (r0052)
r0052.03 r0052
4170_ZSW1.vsd Technology Functions
1 = Drive ready to run (DC link loaded, pulses disabled) 0 = Drive not ready to run
1 = Drive running (voltage at output terminals) 0 = Pulses disabled
Bit No. Meaning
1 = Drive fault active (pulses disabled) 0 = No fault
1 = ON inhibit active 0 = No On inhibit (possible to switch on)
0 = Deviation setpoint / act. value 1 = No deviation setpoint / act. Value
1 = Maximum frequency reached 0 = Maximum frequency not reached
1 = Motor holding brake active 0 = Motor holding brake not active
1 = PZD control (always 1)
1 = Motor runs right 0 = Motor does not run right
1 = Drive warning active 0 = No warning
0 = Inverter overload 1 = No inverter overload
0 = Motor overload 1 = No Motor overload
1 = Drive ready 0 = Drive not ready
0 = OFF2 active 1 = No OFF2
0 = OFF3 active 1 = No OFF3
9 8 11 10 13 12 15 14 Segment Bit
1 0 3 2 5 4 7 6

control (software) for realizing the drive
- 4180 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Status word 2 (r0053)
4180_ZSW2.vsd Technology Functions
1 = PID output r2294 == P2291 (PID_max)
Bit No. Meaning
1 = PID output r2294 == P2292 (PID_min)
1 = Act. current r0027 >= P2170
Download data set 0 from AOP
Download data set 1 from AOP
1 = f_act >= P1080 (f_min)
1 = Act. Vdc r0026 < P2172
1 = Act. Vdc r0026 > P2172
1 = f_act > P2167 (f_off)
1 = f_act
1 = DC brake active 0 = DC brake not active
1 = f_act > P2155 (f_1)
1 = f_act >= setpoint
1 = Ramping finished
9 8 11 10 13 12 15 14 Segment Bit
1 0 3 2 5 4 7 6
![Page 285 of the Siemens 440 user manual — 65 ... 115 [%] P1245.D (76)](/cdn/reader/de/dee006756e12cacab78582f800e5bac4a6b2c84421626904a73f70b66751dc07/images/page-285.webp?w=400)
- 4600 - Function diagram 8 7 6 5 4 3 2 1
1 CO/BO:Stat MotCtrl
r0056.15
FP 7900
MICROMASTER 440 16.01.2006 V2.1 Vdc Control (max, min)
0.00 ... 600.00 [Hz] P1253.D (10.00)
Vdc ctrl outp. lim
4600.vsd Technology Functions
0.0 ... 1000.0 [ms] P1252.D (1.0)
Diff.time Vdc ctrl
Dyn. factor of KIP
Int. time Vdc ctrl
0.1 ... 1000.0 [ms] P1251.D (40.0)
Vdc-max dyn. fact.
Gain of Vdc ctrl.
0 ... 3 P1240.D (1)
0 ... 3 P1240.D (1)


- 4800 - Function diagram 8 7 6 5 4 3 2 1


- 4810 - Function diagram 8 7 6 5 4 3 2 1


- 4820 - Function diagram 8 7 6 5 4 3 2 1


- 4830 - Function diagram 8 7 6 5 4 3 2 1
2 Adders with 2 Inputs (1 Word) 2 Subtracters with 2 Inputs (1 Word)


- 5000 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Setpoint channel and Motor control


- 5100 - Function diagram 8 7 6 5 4 3 2 1
P2251 = PID mode (0 = PID as setpoint, 1 = PID as trim)


- 5200 - Function diagram 8 7 6 5 4 3 2 1

CO:Setp. after RFG [Hz]
- 5300 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Ramp Function Generator
P1140.C 1 = Enable RFG 0 = Set RFG to zero 1 fy = 0
5300_RFG.vsd Setpoint Channel
Ramp-dwn fin. Trnd
0.00 ... 40.00 [s] P1133.D (0.00)
0.00 ... 650.00 [s] P1121.D (10.00)
Ramp-dwn ini. Trnd
0.00 ... 40.00 [s] P1132.D (0.00)
0.00 ... 40.00 [s] P1131.D (0.00)
0.00 ... 650.00 [s] P1120.D (10.00)
Ramp-up ini. Trnd
0.00 ... 40.00 [s] P1130.D (0.00)
0 ... 1 P1134.D (0)
Bring RFG to a standstill
CO:Setp before RFG [Hz]
BI:RFG enable setp
(1:0)
(1:0)
P1142.C


- 6100 - Function diagram 8 7 6 5 4 3 2 1


- 7000 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Overview of Speed Control without Encoder (SLVC):


- 7010 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Overview of Speed Control with Encoder (VC): P1300 = 21 and P1501 = 0


- 7200 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Overview of Torque Control without Encoder:
P1300 = 22 or P1300 = 20 and P1501 = 1
**) The speed integrator doesn't work in the range of the observer model


- 7210 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Overview of Torque Control with Encoder:
P1300 = 23 or P1300 = 21 and P1501 = 1
**) The speed integrator doesn't work in the range of the observer model


- 7500 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Speed Controller without Encoder (SLVC):


- 7510 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Speed Controller with Encoder (VC):


- 7700 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Torque Controller and Torque Limitation (SLVC)


- 7710 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Torque Controller and Torque Limitation (VC)


- 7800 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Flux Setpoint (SLVC and VC)


- 7900 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Current Controller & Observer Model (SLVC and VC)


- 8000 - Function diagram 8 7 6 5 4 3 2 1
MICROMASTER 440 16.01.2006 V2.1 Analog outputs and display values
*) Access level 4 **) Reference values P2000 = Reference frequency


5 Faults and Alarms
5.1 Fault messages
In the event of a failure, the inverter switches off and a fault code appears on the display.
button on the BOP or AOP. 3. Via Digital Input 3 (default setting)
Fault messages are stored in parameter r0947 under their code number (e.g. F0003 = 3). The associated error value is found in parameter r0949. The value 0 is entered if a fault has no error value. It is furthermore possible to read out the point in time that a fault occurred (r0948) and the number of fault messages (P0952) stored in Parameter r0947.
Remove fault and reset fault memory by disconnecting the - drive converter from the line supply and powering-up again - Press the Fn key on the BOP or AOP - Acknowledge fault P2103, P2104 - P0952 (complete fault memory) Cause
- short-circuit at the output - ground fault - excessively large motor (the motor power rating P0307 is greater than the inverter power r0206) - defective final stage (end stage) Diagnosis & Remedy
Please check the following: - are the cable lengths within the limit values ? - does the motor cable or motor have either a short-circuit or ground fault ? - do the motor parameters correspond to those of the motor being used ? - is the motor overloaded or stalled (locked rotor) ? - increase the accelerating time. - reduce the gain - use a motor with a lower power rating - is the stator resistance value (P0350) correct ?
Refer to F0001 Cause
- DC link voltage (r0026) higher than the overvoltage threshold (refer to parameter r0026) - ground fault Diagnosis & Remedy
Please check the following: - is the line supply voltage within the permissible range? - has the DC current DC link monitoring been enabled (P1240) and correctly parameterized? - extend the deceleration ramp (ramp-down time P1121, P1135) - remove the ground fault - is the required braking power within the permissible limits? NOTE - a higher moment of inertia requires longer deceleration times; if required, use a braking resistor. - overvoltage can either be caused by an excessively high line supply voltage or by the fact that the motor is generating (regenerative mode). - the motor can be generating as it is decelerating quickly or due to the fact that an active load is driving the motor.
Quit · Quit

F0003 Undervoltage STOP II
Refer to F0001 Cause
- line voltage failed - shock stressing outside the permissible limits. Diagnosis & Remedy
Please check the following: - is the line supply voltage within the permissible range? - is the line supply voltage stable with respect to sporadic failures and voltage dips (brown-outs) ?
Refer to F0001 Cause
- inadequate cooling - ambient temperature is too high. ambient temperature is too high. Diagnosis & Remedy
Please check the following: - is the pulse frequency P1800 set to the factory setting ? If required reset P1800. - does the ambient temperature lie within the permissible limits ? - reduce the load and / or ensure adequate cooling Please check the following: - does the fan rotate if the inverter is operational ?
Refer to F0001 Cause
- inverter overloaded. - load duty cycle too high. - the motor power rating (P0307) is greater than that of the inverter (r0206). - 100 % overload reached (refer to utilization r0036) Diagnosis & Remedy
Please check the following: - does the load duty cycle lie within the permissible limits? - use a motor with a lower rating (motor power P0307 is greater than ls inverter power r0206)
Refer to F0001 Cause
Motor overloaded Diagnosis & Remedy
Please check the following: - is the load cycle correct ? - are the rated/nominal motor overtemperatures correct (P0626-P0628) ? - is the alarm threshold correct for the motor temperature (P0604) ?
Refer to F0001 Cause
- wire breakage of the inverter-temperature sensor (heatsink) Diagnosis & Remedy
- replace the inverter

F0015 No motor temperature signal STOP II
Refer to F0001 Cause
- motor temperature sensor either short-circuited or open-circuit. - if it is identified that a signal has been lost, then the temperature monitoring changes-over to monitoring based on the thermal-motor model.
Refer to F0001 Cause
- a fault is output if one of the three input phases is missing, the pulses are enabled and a load is present Diagnosis & Remedy
Please check the following: - are the power connections ok ?
Refer to F0001 Cause
- the fault occurs if the sum of the phase currents is greater than 5 % of the inverter rated current. NOTE - this fault only occurs for inverters with 3 current sensors (sizes D to F, GX, FX).
Please check the following: - are the connections at the motor terminal boxes o.k. ? - are the motor cable connections at the inverter o.k. ?
Refer to F0001 Cause
This fault (r0947 = 22 and r0949 = 1) occurs under the following circumstances: (1) DC link overcurrent condition = IGBT short-circuit (2) Braking chopper short-circuit (3) Ground fault (4) I/O module not correctly inserted For the following sizes the above faults can occur: - size A to C (1),(2),(3),(4) - size D to E (1),(2), (4) - size F (1),(2) The following faults only occur in conjunction with sizes FX / GX: - UCE faults are identified if r0947 = 22 and the fault value r0949 = 12 or 13 or 14. - I2C bus error is identified if r0947 = 22 and the fault value r0949 = 21 (power-down and then power-up again). NOTE
All of these faults are assigned to a signal in the power module. This means that it is not possible to determine which fault actually occurred.
You must first identify as to whether the fault is permanent (i.e. the inverter cannot be started without the fault occurring) or it sporadically occurs (occasionally occurs or under certain operating conditions). Permanent fault F0022: - check whether the I/O module is correctly inserted (refer to the Operating Instructions). - is there a ground fault or short-circuit at the inverter output or at an IGBT? You can identify this by disconnecting the motor cable. In the case that the fault occurs, if all of the external cables (with the exception from the line supply voltage) are disconnected, then with a high degree of probability, the drive unit is defective and must be repaired. Sporadic fault F0022: - this fault should be treated as "overcurrent". If fault F0022 sporadically occurs, the causes can be as follows: - sudden load changes or mechanical obstructions - extremely short ramp-up times (accelerating times) - poor optimization of the sensorless closed-loop vector control - incorrect braking resistor is installed with an excessively low resistance

F0023 Output fault STOP II
Refer to F0001 Cause
- one output phase has not been correctly connected. Diagnosis & Remedy
Please check the following: - are the connections at the motor terminal box o.k. ? - are the motor cable connections at the inverter o.k. ?
Refer to F0001 Cause
- inadequate cooling - fan is not operational - ambient temperature is too high. Diagnosis & Remedy
Please check the following: - does the fan rotate when the inverter is powered-up (A0520, A0521) ? - is the pulse frequency set to the factory setting ? If required, reset. - is the ambient temperature within the permissible limits (A0520, A0521) ?
Refer to F0001 Cause
- fan no longer functions Diagnosis & Remedy
- fault cannot be suppressed if an AOP or BOP is connected. - a new fan is required.
reset fault memory or Power On / Stop Cause
- restart fault after n attempts, refer to P1211
Refer to F0001 Cause
- a calibration error has occurred for the automatic calibration of the analog inputs / outputs or the current actual value sensing. - the calibration is only carried-out once in the factory. - a fault F0040 is therefore only to be expected while the inverter is being manufactured and not in operation. Diagnosis & Remedy
- change the drive

F0041 Failure, motor data identification STOP II
Refer to F0001 Cause
Motor data identification run unsuccessful (refer to fault value r0949): - r0949 = 0: Load missing. - r0949 = 1: Current limit was reached during the identification run. - r0949 = 2: Identified stator resistance less than 0.1% or greater than 100%. - r0949 = 3: Identified rotor resistance less than 0.1% or greater than 100%. - r0949 = 4: Identified stator reactance less than 50% or greater than 500% - r0949 = 5: Identified magnetizing reactance less than 50% or greater than 500% - r0949 = 6: Identified rotor time constant less than 10ms or greater than 5s - r0949 = 7: Identified total leakage reactance less than 5% or greater than 50% - r0949 = 8: Identified stator leakage reactance less than 25% or greater than 250% - r0949 = 9: Identified rotor leakage reactance less than 25% or greater than 250% - r0949 = 20: Identified IGBT response voltage less than 0.5 or greater than 10V - r0949 = 30: Current controller at voltage limit value - r0949 = 40: Identified data set inconsistent; at least one identification run unsuccessful NOTE
Percentage values based on the impedence Zb = Vmot,rated / sqrt(3) / Imot,rated
Please check the following: - r0949 = 0: Is the motor connected to the inverter ? - r0949 = 1-40: Is the motor data in P0304-P0311 correct ? - r0949 = 1-40: Motor circuit configuration correct (star, delta configuration) ?
Refer to F0001 Cause
Automatic data identification run unsuccessful (refer to fault value r0949): - r0949 = 0: Time slice overflow while waiting for a stable speed - r0949 = 1: No matching/appropriate value when reading
Refer to F0001 Cause
- read or write operation while saving parameters in the EEPROM was unsuccessful. Diagnosis & Remedy
- reset to factory setting and then re-parameterize - if required, change the drive
Refer to F0001 Cause
- read error, power data or invalid power module data. Diagnosis & Remedy
- change the drive
Refer to F0001 Cause
- fault with I/O EEPROM read operation or invalid data. Diagnosis & Remedy
Please check the following: - check I/O data and if required repeat the operation - the installation of the I/O module in the inverter if required, replace the I/O module

F0054 Incorrect I/O module STOP II
Refer to F0001 Cause
- incorrect I/O module inserted. - no ID of the I/O module found, no data. Diagnosis & Remedy
Please check the following: - check I/O data, if required repeat the operation - the installation of the I/O module in the inverter if required, replace the I/O module
Refer to F0001 Cause
- internal communications failure/error Diagnosis & Remedy
- if the error still occurs, replace the inverter. - contact customer service!
Refer to F0001 Cause
- no setpoints received via the communications bus during the telegram failure time. Diagnosis & Remedy
- check the communications module (CB) and communications partner.
Refer to F0001 Cause
- no setpoint was received via the USS during the telegram off time Diagnosis & Remedy
- check USS master
Refer to F0001 Cause
- no setpoints received via the USS during the telegram off time Diagnosis & Remedy
- check USS master
Refer to F0001 Cause
- wire breakage - signal outside the limit values
Refer to F0001 Cause
- external fault as a result of command input via terminals. Diagnosis & Remedy
- inhibit terminal input to initiate fault.

F0090 Signal loss, encoder STOP II
Refer to F0001 Cause
- encoder signal between the encoder and inverter is interrupted - excessively large difference between the setpoint (reference) and actual frequency Diagnosis & Remedy
Please check the following: - is there an integrated encoder? If there is no integrated encoder, then set P0400 = 0 and select the operating mode sensorless closed-loop vector control (P1300 = 20 or 22) - the connection between the encoder and the inverter - is the encoder faulty? (select P1300 = 0, operation with fixed speed, check the encoder signal in r0061) - increase the encoder signal threshold in P0492, P0494
Refer to F0001 Cause
- software error or processor failure Diagnosis & Remedy
- carry-out self-test routines
Refer to F0001 Cause
- PID feedback below the minimum value P2268. Diagnosis & Remedy
- change value of P2268. - set feedback gain.
Refer to F0001 Cause
- PID feedback above maximum value P2267. Diagnosis & Remedy
- change value of P2267. - set the feedback gain.
Refer to F0001 Cause
No Load is applied to the inverter. As a result, some functions may not work as under normal load conditions.
Refer to F0001 Cause
Self-test routine unsuccessful (refer to fault value r0949): - r0949 = 1: Self-test routine for power module components unsuccessful - r0949 = 2: Self-test routine for closed-loop control module components unsuccessful - r0949 = 4: Several function tests were unsuccessful - r0949 = 8: Several tests carried-out at the I/O module were unsuccessful (only MICROMASTER 420) - r0949 = 16: Failure of the internal RAM at the switch-on test Diagnosis & Remedy
- the drive is functional, but several functions are not correctly executed. - replace the drive

F0452 Load torque fault detected STOP II
Refer to F0001 Cause
- load conditions at the motor signify a load torque fault (e.g. belt failure) or a mechanical fault Diagnosis & Remedy
Please check the following: - no braking, failure or destruction of the mechanical drive transmission line - if required, lubricate the mechanical drive transmission line. If you are using an external encoder, please check the following parameter settings: - P2192 (delay time, load torque monitoring) If you are operating within a specific speed range, please check the following: - P2182 (load torque monitoring F1) - P2183 (load torque monitoring F1f2) - P2184 (load torque monitoring F1f3) - P2185 (upper torque threshold 1) - P2186 (lower torque threshold 1) - P2187 (upper torque threshold 2) - P2188 (lower torque threshold 2) - P2189 (upper torque threshold 3) - P2190 (lower torque threshold 3) - P2192 (delay time, load torque monitoring)
Refer to F0001 Cause
- up/ or down ramp too steep (excessive gradient) - inverter connected to an already spinning motor without using the flying restart function - motor incorrectly connected - motor too small - voltage boost P1611 for sensorless vector control too low Diagnosis & Remedy
Please check the following: - the motor connections - increase the ramp-up time P1120 or the ramp-down time P1121 - activate the flying restart function P1200 - use a larger motor - increase the voltage boost P1611 for sensorless closed-loop vector control - use closed-loop vector control with encoder instead of sensorless closed-loop vector control. - activate the V/f closed-loop control mode (P1300 less than 20) instead of closed-loop vector control
Quit · Quit

5.2 Alarm Messages
Alarm messages are stored in parameter r2110 under their code number (e.g. A0503 = 503) and can be read out from there.
- the motor power rating does not correspond to the inverter power rating - motor cables are too long - ground fault Diagnosis & Remedy
Please check the following: - does the motor power rating (P0307) match the inverter power rating (r0206) ? - are the limit values for the cable lengths maintained ? - does the motor cable or motor have a short-circuit or ground fault ? - do the motor parameters correspond to those of the motor being used ? - stator resistance value (P0350) correct ? - is the motor overloaded or is the rotor locked (cannot rotate) ? - ramp-up time P1120 too low ?
- the overvoltage limit value has been reached (actual value of the DC link voltage r0026 greater than r1242). Diagnosis & Remedy
- if this alarm is permanently displayed, check the inverter input voltage. - is the DC link voltage controller (Vdc_max controller) de-activated (refer to parameter P1240) ? - short ramp times and/or large flywheel masses (moment of inertia) ?
- line supply has failed. - line voltage and therefore also the DC link voltage (r0026) below the defined limit value (refer to parameter r0026). Diagnosis & Remedy
- check the line voltage.
- alarm threshold of the inverter heatsink temperature (P0614) was exceeded; this results in a reduction of the pulse frequency and/or the output frequency (dependent on the parameterization in (P0610). Diagnosis & Remedy
Please check the following: - is the ambient temperature within the permissible limits ? - are the load and load duty cycle within the permissible limits ?
- overload alarm limit P0294 is exceeded (refer to utilization r0036) - the pulse frequency and/or the output frequency is reduced as a function of the setting of parameter P0290. Diagnosis & Remedy
- check whether the load duty cycle lies within the permissible limits.
- difference between the temperature at the heatsink and IGBT exceeds the alarm limit values. Diagnosis & Remedy
- please ensure that the load duty cycle and load surge lie within the permissible limits.

A0510 Motor overtemperature
A0511 Motor overtemperature
- motor is overloaded. - load duty cycle is exceeded. Diagnosis & Remedy
Check, independently of the type of temperature monitoring: - P0604 alarm threshold, motor overtemperature - P0625 motor ambient temperature If P0601 = 0 or 1, please check the following: - is the motor data correct (rating plate)?, if not, carry-out a fast commissioning routine - precise temperature values from the motor identification routine (P1910=1). - is the motor weight correct (P0344)? - the permissible overtemperature can be changed using P0626, P0627, P0628, if the motor is not a standard Siemens motor. If P0601 = 2, then please check the following: - is the temperature displayed in r0035 plausible? - is an KTY84 temperature sensor being used? (others are not supported).
- alarm threshold of the rectifier heatsink exceeded. Diagnosis & Remedy
Please check the following: - is the ambient temperature within the permissible range ? - are the load and load duty cycle within the permissible range ? - does the fan operate if the inverter is operational ?
- alarm threshold of the permissible ambient temperature exceeded. Diagnosis & Remedy
Please check the following: - is the ambient temperature within the permissible range ? - does the fan operate if the inverter is operational ? - is the air feed to the fan obstructed ?
- cyclic access to UCE values and power module data via i2c bus (only for sizes FX and GX) is faulted.
- an output cable is not connected. Diagnosis & Remedy
- alarm can be suppressed.
- the load duty cycle of the braking resistor has been exceeded. - when the load duty cycle is exceeded, then it is automatically limited to the value P1237. Diagnosis & Remedy
- use a braking resistor with higher power rating / higher load duty cycle.
- motor data identification routine (P1910) selected and is active
- speed controller optimization (P1960) is selected and is presently active.

A0590 Alarm, no signals from the speed encoder
- no speed encoder signals - inverter has changed-over to encoderless vector control. Diagnosis & Remedy
Stop the inverter, and - check the speed encoder, if an encoder is not being used, set P0400 to 0 and select the sensorless closed-loop vector control mode (P1300 = 20 or 22) - check the encoder connections - check whether the encoder is operating correctly (set P1300 = 0 and operate the drive at a fixed speed and check the encoder signal in r0061 - increase the permissible speed deviation in P0492
- time slice overflow was identified Diagnosis & Remedy
- use lower baud rate for USS - de-activate inverter functions
- CB-(communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(Communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(Communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual

A0707 CB alarm 8
- CB-(Communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(Communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- CB-(Communications module)-specific Diagnosis & Remedy
- refer to the CB User Manual
- loss of communications with the CB (communications module) Diagnosis & Remedy
- check the CB hardware
- CB (communications module) signals a communications error. Diagnosis & Remedy
- check the CB parameters
- Vdc max controller was de-activated, as it was not able to keep the DC link voltage (r0026) within the limit values (refer to r0026 and P1240). This occurs, - if the line supply voltage is permanently too high. - if the motor is driven by an active load, which means that the motor goes into regenerative operation. - while decelerating (short down-ramps P1121) for extremely high load torques Diagnosis & Remedy
Please check the following: - is the input voltage (P0756) within the permissible range ? - are load duty cycle and load limits within the permissible limits ?
- Vdc max controller is active - the ramp-down times are automatically increased in order to keep the DC link voltage (r0026) within the limit values (refer to r0026 and P1240).
- Vdc min controller is activated, if the DC link voltage (r0026) falls below the minimum value (refer to r0026 or P1240). - the kinetic energy of the motor is used to buffer the DC link voltage and therefore to slow down the drive. - therefore brief line failures no longer automatically result in an undervoltage trip.

A0920 ADC parameters not correctly set
ADC parameters should not be set to identical values, as this would lead to illogical results. - Index 0: Parameter settings for output identical. - Index 1: Parameter settings for input identical. - Index 2: Parameter settings for input do not correspond to ADC type.
- DAC parameters (P0777 and P0779) have identical values. OR - DAC parameters (P0778 and P0780) have identical values. Identical values would produce illogical results. Diagnosis & Remedy
Check the following: - Output parameter settings. Ensure P0777 and P0779 are not identical. - Input parameter settings. Ensure P0778 and P0780 are not identical.
- no load is connected to the inverter. - therefore several functions can run differently than under normal load conditions.
- both JOG clockwise and JOG counter-clockwise (P1055/P1056) have been requested. This is the reason that the RFG output frequency has been frozen to the actual value.
- load conditions at the motor indicate a load fault or mechanical fault. Diagnosis & Remedy
Please check the following: - no braking, failure or destruction of the mechanical transmission line - if required, lubricate the mechanical transmission line. If you are using an external encoder, please check the following parameter settings: - P2192 (delay time, load torque monitoring) If you are using a specific speed range, then please check the following: - P2182 (load torque monitoring F1) - P2183 (load torque monitoring F1f2) - P2184 (load torque monitoring F1f3) - P2185 (upper torque threshold 1) - P2186 (lower torque threshold 1) - P2187 (upper torque threshold 2) - P2188 (lower torque threshold 2) - P2189 (upper torque threshold 3) - P2190 (lower torque threshold 3) - P2192 (delay time, load torque monitoring)
- PID auto tuning (P2350) is selected or is presently running. Diagnosis & Remedy
- after automatic PID optimization has been completed, the alarm is reset.


6 Abbreviations AC Alternating current AD Analog digital converter ADC Analog digital converter ADR Address AFM Additional frequency modification AG Automation unit AIN Analog input AOP Advanced operator panel AOUT Analog output ASIC Application-specific integrated circuit ASP Analog setpoint ASVM Asymmetric space vector modulation BCC Block check character BCD Binary-coded decimal code BI Binector input BICO Binector / connector BO Binector output BOP Basic operator panel C Commissioning CB Communication board CCW Counter-clockwise CDS Command data set CI Connector input CM Configuration management CMD Commando CMM Combimaster CO Connector output CO/BO Connector output / Binector output COM Common (terminal that is connected to NO or NC) COM-Link Communication link CT Commissining, ready to run CT Constant torque CUT Commissining, run, ready to run CW Clockwise DA Digital analog converter DAC Digital analog converter DC Direct current DDS Drive data set DIN Digital input DIP DIP switch DOUT Digital output DS Drive state EEC European Economic Community EEPROM Electrical erasable programmable read-only memory ELCB Earth leakage circuit breaker

EMC Electro-magnetic compatibility EMF Electromotive force EMI Electro-magnetic interference ESB Equivalent circuit FAQ Frequently asked questions FB Function block FCC Flux current control FCL Fast current limit FF Fixed freqeuncy FFB Free function block FOC Field orientated control FSA Frame size A GSG Getting started guide GUI ID Global unique identifier HIW Main actual value HSW Main setpoint HTL High-threshold logic I/O Input and output IBN Commissioning IGBT Insulated gate bipolar transistor IND Sub-index JOG Jog KIB Kinetic buffering LCD Liguid crystal display LED Light emitting diode LGE Length MHB Motor holding brake MM4 MICROMASTER 4th. Generation MOP Motor potentiometer NC Normally closed NO Normally open NPN Negative positive negative OPI Operating instructions PDS Power drive system PID PID controller (proportional, integral, derivative) PKE Parameter ID PKW Parameter ID value PLC Programmable logic controller PLI Parameter list PNP Positive negative positive POT Potentiometer PPO Parameter process data object PTC Positive temperature coefficient PWE Parameter value PWM Pulse-width modulation PX Power extension PZD Process data QC Quick commissioning RAM Random-access memory

RCCB Residual current circuit breaker RCD Residual current device RFG Ramp function generator RFI Radio-frequency interference RPM Revolutions per minute SCL Scaling SDP Status display panel SLVC Sensorless vector control STW Control word STX Start of text SVM Space vector modulation TTL Transistor-transistor logic USS Universal serial interface VC Vector control Vdc DC-link voltage VT Variable torque ZSW Status word ZUSW Additional setpoint


Suggestions Corrections To Siemens AG Automation & Drives Group SD SPA PM 4 P.O. Box 3269 D-91050 Erlangen Federal Republic of Germany
Email: [email protected]
From
Should you come across any printing errors when reading this publication, please notify us on this sheet. Suggestions for improvement are also welcome.





Siemens AG Automation and Drives Group (A&D) Standard Drives (SD) Division Postfach 3269, D-91050 Erlangen Federal Republic of Germany
© Siemens AG, 2001, 2002, 2003, 2004, 2005 Subject to change without prior notice

Pages referenced in this manual — manufacturer, support and downloads.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| P1121 | This procedure is repeated several times and then average time taken. From this an estimation of | p.192 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.