Powerware 9335

100 pages·2.7 MB·Power Supply·PDF·ENDEFRITNLJA
Powerware 9335
Table of Contents 80 sections Uninterruptible Power · Supply · 80 kVA and 120 kVA Installation and Operation · Manual · … ShowHide
Uninterruptible Powerp.1Supplyp.180 kVA and 120 kVA Installation and Operationp.1Manualp.1IMPORTANT SAFETY INSTRUCTIONSp.3SAVE THESE INSTRUCTIONSp.3List of Figuresp.7List of Tablesp.8Introductionp.9Basic System Configurationsp.10Safety Considerationsp.12Section Ip.13Installationp.131 Getting Startedp.151.1 Installing the UPSp.151.1.1 Creating an Installation Planp.151.1.2 Preparing Your Sitep.161.1.5 Inspecting and Unpacking Each Cabinetp.17Installing the UPS Systemp.192.1 Preliminary Installation Informationp.192.2 UPS Cabinet Installationp.202.2.2 Installing External Battery Power Wiringp.212.2.3 Installing UPS External Power Wiringp.21WARNING:p.222.2.4 Installing Customer Connectionsp.222.2.5 Prepare for Installing Optional Accessoriesp.222.3 Battery Cabinet Installationp.232.4 Initial Startupp.232.5 Completing the Installation Checklistp.232.5.1 Installation Checklistp.243 Installing and Connecting Batteriesp.253.1 Important Safety Instructionsp.25Installing a Remote EPO Controlp.274.1 Installation Proceduresp.274.2 To Install a Remote EPO:p.27Table 4 – 1. Remote EPO Wire Terminations From Remote EPO Switch(s)p.28Table 4 – 2. Remote EPOp.28REMOTEp.28TWISTED WIRES (2)p.28EPO SWITCHp.28X1 UPSp.28(N.C.)p.284.3 To Operate a Remote EPO:p.28Section IIp.29Operationp.295 Understanding UPS Operationp.31IA1p.32K4p.32K1p.32K2p.32IA2p.325.2 Normal, Battery and Bypass Modesp.335.2.1 Normal Modep.34Normal Modep.34F1p.345.2.2 Bypass Modep.36Static Bypassp.365.2.3 Battery Modep.38Battery Modep.385.2.4 Maintenance Bypass Modep.40Maintenance Bypass Modep.405.3 Functional Descriptionp.41Operational Controls and Featuresp.436.1 Generalp.436.2 UPS Operational Controlsp.446.2.3 Maintenance Bypass Switchp.456.3.2 Battery Managementp.456.3.3 Installation Featuresp.457 Using the Control Panelp.497.1 Descriptionp.49LINE 2p.49BYPASSp.49BATTERYp.49LINE 1 INVp.49LOAD S PROTECTEDp.50ON/OFFp.50ALARMp.50LINE 1p.50INVp.50RESET ENTERp.50
Page 1 of the Powerware 9335 user manual — Uninterruptible Power
Page 1 · click to enlarge
Page 1
Powerware 9335 — Uninterruptible Power diagram (page 1)
Fig. 1 · Uninterruptible Power

Uninterruptible Power

Supply

80 kVA and 120 kVA Installation and Operation

Manual

Page 2 of the Powerware 9335 user manual — Uninterruptible Power
Page 2 · click to enlarge
Page 2
Page 2 of the Powerware 9335 user manual — Uninterruptible Power
Page 3 of the Powerware 9335 user manual — IMPORTANT SAFETY INSTRUCTIONS
Page 3 · click to enlarge
Page 3

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions for your Uninterruptible Power Supply (UPS) system. You should follow these instructions during the installation and maintenance of the UPS, options, accessories and batteries.

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference with the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense.

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation ii 164201396 REV. A 071103

Page 4 of the Powerware 9335 user manual — IMPORTANT SAFETY INSTRUCTIONS
Page 4 · click to enlarge
Page 4
Page 4 of the Powerware 9335 user manual — IMPORTANT SAFETY INSTRUCTIONS
Page 5 of the Powerware 9335 user manual — IMPORTANT SAFETY INSTRUCTIONS
Page 5 · click to enlarge
Page 5

Section II Operation 5 Understanding UPS Operation 5.1 Looking Inside the UPS System 5 - 1 5.2 Normal, Battery and Bypass Modes 5 - 3 5.2.1 Normal Mode 5 - 4 5.2.2 Bypass Mode 5 - 6 5.2.3 Battery Mode 5 - 8 5.2.4 Maintenance Bypass Mode 5 - 10 5.3 Functional Description 5 - 11 5.3.1 Input Rectifier 5 - 11 5.3.2 Boost Converter 5 - 11 5.3.3 Inverter and Filter 5 - 11 5.3.4 Battery and Battery Charger 5 - 11 5.3.5 Static Bypass 5 - 12 5.3.6 Maintenance Bypass 5 - 12 6 Operational Controls and Features 6.1 General 6 - 1 6.2 UPS Operational Controls 6 - 2 6.2.1 Control Panel 6 - 2 6.2.2 System and Load ON/OFF 6 - 2 6.2.3 Maintenance Bypass Switch 6 - 3 6.2.4 Cold Start Capability 6 - 3 6.3 UPS Standard Features 6 - 3 6.3.1 Customer Interface 6 - 3 6.3.2 Battery Management 6 - 3 6.3.3 Installation Features 6 - 3 6.4 Options and Accessories 6 - 4 6.4.1 Remote EMERGENCY POWER OFF 6 - 4 6.4.2 Battery Cabinets 6 - 4 6.4.3 Communications 6 - 4 6.4.4 Other Options 6 - 4 6.5 Safety Considerations 6 - 5 6.6 Symbols, Controls and Indicators 6 - 6 7 Using the Control Panel 7.1 Description 7 - 1 7.2 Using the Control Panel 7 - 2 7.2.1 Power Management Display 7 - 2 7.2.2 LED Indicators 7 - 2 7.2.3 Pushbutton Functions 7 - 3 7.2.4 ON/OFF Shutdown and Startup Pushbuttons 7 - 3 7.3 Description of the LCD Screen 7 - 4 7.3.1 Status Screens 7 - 4 7.3.2 LCD Display Structure and Navigation 7 - 5 7.3.3 Main Menu Screen 7 - 6 7.3.4 Event Log Screen 7 - 6 7.3.5 Measurements Screen 7 - 6 7.3.6 Command Screen 7 - 7

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation iv 164201396 REV. A 071103

Page 6 of the Powerware 9335 user manual — IMPORTANT SAFETY INSTRUCTIONS
Page 6 · click to enlarge
Page 6

7.3.7 UPS Data 7 - 8 7.3.8 Set-Up User 7 - 8 7.3.9 Set-Up Service 7 - 9 7.4 Operating Modes 7 - 10 7.4.1 “ON-LINE” Mode (Inverter Mode) 7 - 10 7.4.2 “OFF-LIINE” Mode (BYPASS or ECONOMY Mode) . 7 - 10 7.4.3 “MAINTENANCE BYPASS” Mode 7 - 11 7.4.4 Parallel Isolator (IA2) 7 - 12 8 UPS Operating Instructions 8.1 Operation 8 - 1 8.2 Start-Up Procedure for the UPS 8 - 1 8.3 Shut-Down Procedure for the UPS 8 - 3 8.4 Load Transfer to Maintenance Bypass 8 - 4 9 Responding to System Events 9.1 Alarms 9 - 1 9.2 Menu, Commands, Event Log, Measurements 9 - 1 9.3 Fault Identification and Correction 9 - 2 10 Communications 10.1 X – Slot Communication Modules 10 - 1 10.2 Single-Port Module 10 - 2 11 Options 11.1 Generator ON Facility 11 - 1 12 Maintaining the UPS System 12.1 General 12 - 1 12.2 Important Safety Instructions 12 - 1 12.3 Performing Preventive Maintenance 12 - 2 13 Product Specifications 13.1 System Information 13 - 1 13.2 UPS System Input 13 - 1 13.3 UPS System Output 13 - 2 13.4 Environmental Specifications 13 - 2 Appendix A – Customer Information A - 1 Warranty W - 1

v Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Page 7 of the Powerware 9335 user manual — List of Figures
Page 7 · click to enlarge
Page 7

List of Figures

Figure 1 – 1 Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet Figure 4 – 1 Typical Remote EPO Control Figure 5 – 1 Main Elements of the UPS System Figure 5 – 2 Path of Current through the UPS in Normal Mode Figure 5 – 3 Path of Current through the UPS in Bypass Mode Figure 5 – 4 Path of Current through the UPS in Battery Mode Figure 5 – 5 Path of Current through the UPS in Maintenance Bypass Mode Figure 6 – 1 Powerware 9335 (80 kVA and 120 kVA) Controls and Indicators Figure 6 – 2 Powerware 9335 (80 kVA and 120 kVA) Control Panel Figure 7 – 1 UPS Control Panel Figure 7 – 2 LCD Screen and Pushbuttons Figure 7 – 3 LCD Screen Navigation Chart Figure 10 – 1 X – Slot Location on Front of Powerware 9335 UPS Cabinet Figure 10 – 2 The Communication Port on the Single Port Serial Card Figure 11 – 1 Generator ON Connection

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation vi 164201396 REV. A 071103

Page 8 of the Powerware 9335 user manual — List of Tables
Page 8 · click to enlarge
Page 8

Table 4 – 1 Remote EPO Wire Terminations Table 4 – 2 Remote EPO Table 10 – 1 Communication Port Pin Assignments

List of Tables

vii Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Page 9 of the Powerware 9335 user manual — Introduction
Page 9 · click to enlarge
Page 9

Powerware 9335 UPS true double conversion online power protection can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment production due to unexpected power problems. The Powerware UPS System continuously monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power. Working with your building’s electrical system, the UPS System supplies clean consistent power that your sensitive electronic equipment requires for reliable operation. During brownouts, blackouts and other power interruptions, optional battery strings provide emergency power to safeguard your operation. The UPS system is housed in free-standing cabinets. The cabinet sections are matching in design and color, and have safety shields behind the front panels for hazardous voltage protection. The following illustration depicts a typical Powerware 9335 (80 kVA and 120 kVA) UPS System.

Introduction

Powerware 9335 — Introduction diagram (page 9)
Fig. 2 · Introduction

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation viii 164201396 REV. A 071103

Page 10 of the Powerware 9335 user manual — Basic System Configurations
Page 10 · click to enlarge
Page 10

Basic System Configurations

These basic UPS system configurations are possible:

  • Single Cabinet UPS with External Battery Cabinet, Single Utility Feed
  • Single Cabinet UPS with External Battery Cabinet, Dual Utility Feed You can enhance any of these system configurations by adding optional accessories, such as Remote Emergency Power Off (EPO) control and X–Slot communications connectivity features. Using This Manual

Your UPS functions automatically and requires very little attention during normal operation. However, you should read and understand the procedures described in this manual to ensure trouble-free operation. In particular, you should be thoroughly familiar with the Remote Emergency Power Off procedure described in Chapter 4 of this manual. The information in this manual is divided into the sections and chapters listed. The system you are installing dictates which parts of the manual you should read. Everyone should read the Introduction, Chapters 1, 2, 7, and 8. Introduction The introduction provides a brief description of the UPS system, a description of the content of each chapter, safety, and text conventions used in the manual and reference information. Section I – Installation

  • Chapter 1 – Getting Started – tells you how to prepare your site for the installation of your UPS system. It discusses equipment environmental requirements, inspecting, and unpacking cabinets.
  • Chapter 2 – Installing the UPS System – describes how to install the UPS cabinets and optional equipment.
  • Chapter 3 – Installing and Connecting Batteries – provides battery safety, installation and connection information.
  • Chapter 4 – Installing a Remote EPO Control – contains information for installing the optional Remote Emergency Power Off (REPO) control.

ix Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Page 11 of the Powerware 9335 user manual — Basic System Configurations
Page 11 · click to enlarge
Page 11

Section II – Operation

  • Chapter 5 – Understanding UPS Operation – provides information on understanding how your UPS works.
  • Chapter 6 – Operational Controls and Features – describes the standard and optional operational features and controls of the UPS system.
  • Chapter 7 – Using the Control Panel – describes the controls and indicators found on the Control Panel and shows the various information screens displayed on the LCD screen.
  • Chapter 8 - UPS Operating Instructions – contains startup and shutdown procedures for the UPS system.
  • Chapter 9 – Responding to System Events – lists all the alarm messages and notices that can occur during operation of the UPS system.
  • Chapter 10 – Communications – describes the communication feature available with the UPS system.
  • Chapter 11 – Options – describes the available options for this UPS system.
  • Chapter 12 – Maintaining the UPS System – contains maintenance instructions for the UPS system.
  • Chapter 13 – Product Specifications – provides detailed specifications for the UPS system.
  • Appendix A – Customer Information – contains important information on wiring requirements and recommendations, and important diagrams of the cabinet’s mechanical details and electrical access.
  • Warranty – provides the Powerware warranty for this product. Read through each procedure before you begin. Perform only those procedures that apply to the UPS system you are installing or operating. Conventions Used in This Manual The text in this manual uses these conventions:
  • Bold type highlights important concepts in discussions, key terms in procedures, and menu options.
  • Italic type highlights notes and new terms where they are defined.
  • Rectangular boxes containing bold type are warnings or cautions that pertain to the UPS system or its electrical connections. In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system-the UPS cabinet, battery strings and options or accessories installed.

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation x 164201396 REV. A 071103

Page 12 of the Powerware 9335 user manual — Safety Considerations
Page 12 · click to enlarge
Page 12

Safety Considerations

The UPS cabinet is designed for industrial or computer room applications, and contain safety shields behind the doors. However, the UPS system is a sophisticated power system and should be handled with appropriate care, following these guidelines:

  • Keep surroundings clean and free from excess moisture .
  • Do not operate the UPS system close to gas or electric heat sources.
  • The system is not intended for outdoor use.
  • The operating environment should be maintained within the parameters stated in the manual.
  • Keep the cabinet doors closed and locked to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit.
  • The UPS system contains its own power source. Lethal voltages are present even when the UPS is disconnected from utility power.

If service or routine maintenance is required:

  • Ensure all power is disconnected before performing installation or service.
  • Ensure the area around the UPS system is clean and uncluttered.
  • Battery maintenance or battery replacement should be performed only by authorized service personnel.
  • Observe all DANGER, CAUTION and WARNING notices affixed to the inside and outside of the equipment. Getting Help

If you need to schedule initial startup, need regional locations and telephone numbers, have a question about any of the information in this manual, or have a question this manual does not answer, please call Powerware Corporation at: United States 1 – 800 – 843 – 9433

Canada 1 – 800 – 461 – 9166

Outside the U.S. Call your local representative

xi Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Page 13 of the Powerware 9335 user manual — Section I
Page 13 · click to enlarge
Page 13

Section I

Installation

Page 14 of the Powerware 9335 user manual — Section I
Page 14 · click to enlarge
Page 14

This page left intentionally blank

Page 15 of the Powerware 9335 user manual — 1.1.1 Creating an Installation Plan
Page 15 · click to enlarge
Page 15

1 Getting Started

1.1 Installing the UPS

The complete UPS cabinet is shipped on a single pallet. Use a forklift or a pallet jack, rated to handle the weight of the cabinets (refer to Table J in Appendix A for cabinet weights) to move the packaged cabinet to the installation site, or as close as possible to the site, before unloading from the pallet. This is the basic sequence of the installation steps: 1. Create an installation plan for the UPS system. (Chapter 1)

2. Prepare your site for the UPS system (Chapter 1)
3. Inspect, unpack, and unload the UPS cabinet. (Chapter 1)
4. Wire the system. (Chapter 2)
5. Install features, accessories, and/or options, as applicable. (Chapter 4 and 10)
6. Complete the installation checklist. (Chapter 2)
7. Have authorized service personnel perform preliminary operational checks and startup.

personnel. This service is usually offered as part of the service contract for your UPS. Contact Global Services in advance (usually a two week notice is required) to reserve a preferred startup date.)

1.1.1 Creating an Installation Plan

Before beginning to install the UPS system, read and understand how this manual applies to the system being installed. Use the procedures and illustrations in the following chapters to create a logical plan for installing the system.

Page 16 of the Powerware 9335 user manual — 1.1.2 Preparing Your Site
Page 16 · click to enlarge
Page 16

1.1.2 Preparing Your Site

For your UPS to operate at peak efficiency, your installation site should meet the environmental parameters outlined in this manual. If you intend to operate the system at an altitude higher than 1500 meters (5000 feet), contact your local sales or service office for important information about high altitude operation. The operating environment must meet the weight, airflow, size and clearance requirements specified in Appendix A. The basic environmental requirements of the UPS system are: Ambient Temperature Range: 0 – 40˚C (32 – 104˚F) Recommended Operating Range: 20 – 25˚C (68 – 77˚F) Maximum Relative Humidity: 95% (non-condensing) The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the bottom sides and front of the cabinet, and outlets in the top of the cabinet. You must allow clearance in back of the cabinet for proper air circulation. Refer to Table K of Appendix A for clearance requirements. 1.1.3 Environmental Considerations

The life of the UPS system is adversely affected if the installation does not meet the following guidelines:

1. The system must be installed on a level floor suitable for computer or electronic equipment.
2. The system must be installed in a temperature-controlled indoor area free of conductive contaminants.

Failure to follow guidelines may invalidate the UPS warranty. 1.1.4 Preparing for Wiring the UPS System

For external wiring requirements, including the minimum AWG size of external wiring, refer to Tables A and B in Appendix A for the Powerware 9335 (80 kVA and 120 kVA) UPS. The power wiring connections for this equipment are rated using copper wire at 90˚C. Note that wiring to an external battery cabinet may be either 75˚C or 90˚C rated. Control wiring for EPO and optional accessories (such as building alarm and monitoring interface) should be connected at the customer interface connections inside the front of the UPS using class 1 wiring methods.

Page 17 of the Powerware 9335 user manual — 1.1.5 Inspecting and Unpacking Each Cabinet
Page 17 · click to enlarge
Page 17

1.1.5 Inspecting and Unpacking Each Cabinet

The first task in preparing for installation is inspecting and unpacking the UPS. The UPS and accessory cabinets are shipped bolted to wooden pallets, as shown in Figure 1–1, and protected with outer protective packaging material.

Powerware 9335 — 1.1.5 Inspecting and Unpacking Each Cabinet diagram (page 17)
Fig. 3 · 1.1.5 Inspecting and Unpacking Each Cabinet
Powerware 9335 — 1.1.5 Inspecting and Unpacking Each Cabinet diagram (page 17)
Fig. 4 · 1.1.5 Inspecting and Unpacking Each Cabinet
Powerware 9335 — 1.1.5 Inspecting and Unpacking Each Cabinet diagram (page 17)
Fig. 5 · 1.1.5 Inspecting and Unpacking Each Cabinet

Figure 1–1. Powerware 9335 (80 kVA and 120 kVA) UPS Packaging

Page 18 of the Powerware 9335 user manual — 1.1.5 Inspecting and Unpacking Each Cabinet
Page 18 · click to enlarge
Page 18
1. Carefully inspect the outer packaging for evidence of damage during transit.
2. Use a forklift or other material handling equipment to move the cabinet to a convenient unpacking area. Insert the forklift forks between the pallet supports on the bottom of the unit.
3. Set each cabinet on a firm, level surface, allowing a minimum clearance of 3 m (10 ft) on each side for removing the cabinets from the pallets. 4 . Remove accessory installation kit located at the top of the unit (see figure 1.1) by opening top of outer box.
5. Remove the protective covering from the cabinets.
6. Remove the packing material, and discard or recycle them in a responsible manner.
7. After removing the protective covering, inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact the Powerware Customer Service Department immediately to determine the extent of the damage and its impact upon further installation. NOTE: While awaiting installation, protect the unpacked UPS cabinet from moisture, dust,

and other harmful contaminants. Failure to store and protect the UPS properly may invalidate the warranty.

Page 19 of the Powerware 9335 user manual — 2.1 Preliminary Installation Information
Page 19 · click to enlarge
Page 19

Installing the UPS System

2.1 Preliminary Installation Information

Powerware 9335 — 2.1 Preliminary Installation Information diagram (page 19)
Fig. 6 · 2.1 Preliminary Installation Information

Refer to the following while installing the UPS system:

  • Refer to Appendix A of this manual for installation drawings and additional installation notes.
  • Dimensions in this manual, unless otherwise noted, are in millimeters and (inches).
  • Do not tilt the cabinets more than ± 10 degrees during installation.
  • The conduit landing plates are to be removed to add conduit landing holes as required. Plate material is 14 gauge steel (2 mm. thick)
  • The cabinets must be installed on a level floor suitable for computer or electronic equipment.
  • If perforated floor tiles are required for ventilation, place them in front of the UPS. Refer to Table J in Appendix A for equipment weight and point loading, and Figure A–5 in Appendix A for air inlet locations.
  • Details about control wiring are provided in each procedure for connecting options and features. Figure A–1 and Tables G and H in Appendix A identify the control wiring terminations.
Page 20 of the Powerware 9335 user manual — 2.2 UPS Cabinet Installation
Page 20 · click to enlarge
Page 20

2.2 UPS Cabinet Installation

To install an UPS cabinet, perform the procedures in the following paragraphs.

2.2.1 Unloading the Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet from the Pallet

The UPS cabinet is bolted to a wooden shipping base using two steel angles. To remove the shipping material, perform the following procedure.

1. Remove accessory installation kit located at the top of the unit (see figure 1.1) by opening top of outer box. Remove the 4 jacking bolts from the accessory pack. Use a forklift or other material handling equipment to move the cabinet to the installation area. Insert the forklift forks under the unit and keep the unit elevated approximately 3 inches above the ground.
2. Remove the outer stretch wrapping. The two steel angles which connect the UPS cabinet to the wooden shipping base contain 2 threaded holes for inserting jacking bolts..

3. Unbolt the wooden cross members on the shipping base by removing the four nuts (10 mm) which fasten the wooden pallet to the steel brackets. Remove the wooden cross members from the steel brackets. Insert the jacking bolts into the holes and lower them to the ground, in order for the weight of the unit to be supported by the 4 bolts. Place small metal plates under the jacking bolts to prevent floor damage. Ensure the unit does not tilt more than specified in the caution note above. Remove the forklift or pallet jack once the unit is supported on the jacking bolts. Slowly lower the UPS by alternating between the four jacking bolts, until the steel brackets are on the floor. Remove the jacking bolts. Detach the UPS cabinet from the angle steel by removing all of the M5 Phillips-head machine screws that fasten them, using a #3 Phillips head screwdriver. Tilt the unit slightly to enable the steel bracket to be removed from beneath two legs. Lower the unit down to the floor.

4. Repeat the process for the other side by tilting the unit and removing the steel bracket. (See illustrated procedure packed on the outside of the shipping carton.)
5. The UPS cabinet may now be moved to its final position for installation.
Page 21 of the Powerware 9335 user manual — 2.2.3 Installing UPS External Power Wiring
Page 21 · click to enlarge
Page 21

2.2.2 Installing External Battery Power Wiring

The Powerware 9335 contains no internal batteries and must therefore be used with an external battery system. The procedure for wiring the battery system to the 9335 is described as follows. Also read the manual provided with the battery system to ensure proper interconnections on the battery side.

1. If not already done, open the UPS cabinet door using the provided operator handle

and remove the bottom internal protective panel. Retain hardware.

holes as required. When reinstalling, ensure that the protective ground wire is reconnected if it has been removed for conduit hole punching in the plate.

3. Connect positive, negative and neutral DC power wiring from the external battery source to the DC input (positive and negative) and neutral (battery center tap) terminals in the UPS cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.

2.2.3 Installing UPS External Power Wiring

1. Open the front cabinet door using the provided removable operator handle (packed separately with the UPS). Remove the internal safety shield panel by removing the fastening hardware to gain access to the input and output terminals at the bottom front of the cabinet.

holes as required. When reinstalling, ensure that the protective ground wire is reconnected if it has been removed for conduit hole punching in the plate. 2. Route input and output cables through wireway to UPS terminal blocks. Refer to Appendix A of this manual for wiring access information.

3. For bypass input or single feed, connect phase A, B, C, Neutral (N) and earth ground (G) input power wiring from the source to the bypass input terminals (2A, 2B, 2C) in the UPS cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Note wiring connections for single feed systems.
Page 22 of the Powerware 9335 user manual — 2.2.5 Prepare for Installing Optional Accessories
Page 22 · click to enlarge
Page 22

WARNING:

An insulated grounding conductor must be provided per NEC.

4. If the installation is for a single utility feed with common rectifier and bypass input, proceed to step 7. For a separate bypass and rectifier input, proceed to step 5. 5. Remove the single feed bus bar jumper connections from between X6 and X7, Phase A, B, and C and discard them. They will not be used again. 6. Connect ground, phase A, B, C, and Neutral mains input power wiring from the source to the Mains input terminals (1A, 1B, 1C) on the In/Out Terminal Block. Phase A input connects to input terminal 1A, phase B to input terminal 1B and phase C to input terminal 1C. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Note wiring connections for dual feed systems. 7. Connect ground, phase A, B, C, and Neutral power wiring from the output terminals (3A, 3B, 3C) on the In/Out Terminal Block to the critical load. Output terminal 3A connects to phase A of the load, output 3B to phase B and output 3C to phase C, respectively. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. 8. Secure the UPS by reinstalling the safety shield panels, and closing the front cabinet door, latching the cabinet door with the removable door handle.

2.2.4 Installing Customer Connections

See Chapter 10, “Communications”

2.2.5 Prepare for Installing Optional Accessories

(REPO) switch, you must install conduit between each device and the UPS cabinet for wiring these options. 1. Be sure the UPS system is turned off and all power sources are removed. (See the operation section of this manual for shutdown instructions.)

Page 23 of the Powerware 9335 user manual — 2.5 Completing the Installation Checklist
Page 23 · click to enlarge
Page 23
2. Remove Customer Interface conduit landing plate from the UPS cabinet. Drill or punch conduit holes for interface wiring.
3. Open UPS cabinet front door and remove the front safety shield panel to gain access to the wire way to bring wires from the conduit landing panel at the bottom rear of the cabinet.
4. Locate required connection points by referring to Figure A–1 in Appendix A.
5. Refer to Appendix A of this manual for wiring and termination requirements.
6. Reinstall Customer Interface conduit landing plate.
7. Install conduit and wiring.
8. When wiring is complete, secure UPS by reinstalling all panels removed in previous steps.

2.3 Battery Cabinet Installation

The Powerware 9335 has no batteries within the UPS cabinet. An external battery cabinet with appropriate batteries installed is required for proper system operation. See installation instruction provided with the battery cabinet for proper installation of that portion of the system.

2.4 Initial Startup

Startup and operational checks should be performed only by authorized service personnel. Contact service in advance (usually a two week notice is required) to reserve a preferred startup date.

2.5 Completing the Installation Checklist

The final step in installing your UPS system is completing the following Installation Checklist. This checklist ensures that you have completely installed all hardware, cables, and other equipment. Completing all items listed on the checklist will ensure a smooth installation. You should make a copy of the Installation Checklist before filling it out, and retain the original. After your installation is complete, a service representative will be able to verify the operation of your UPS system and commission it to support your critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters. Service personnel may request a copy of the

Page 24 of the Powerware 9335 user manual — 2.5.1 Installation Checklist
Page 24 · click to enlarge
Page 24

completed Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the UPS

system for the first time.

2.5.1 Installation Checklist

All packing materials and restraints have been removed from each cabinet.

Each cabinet in the UPS system is placed in the installed location.

All conduits and cables are properly routed to the UPS and auxiliary cabinets.

All power cables are properly sized and terminated.

All network connections have been completed.

A ground conductor is properly installed.

Battery cabinet installation instructions have been completed.

Air conditioning equipment is installed and operating properly.

The area around the installed UPS system is clean and dust-free. (It is recommended

that the UPS be installed on a level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.

Adequate lighting is provided around all UPS equipment.

Any optional accessories are mounted in their installed location and properly wired.

Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)

Startup and operational checks performed by authorized service personnel.

Page 25 of the Powerware 9335 user manual — 3.1 Important Safety Instructions
Page 25 · click to enlarge
Page 25

3 Installing and Connecting Batteries

3.1 Important Safety Instructions

The Powerware 9335 UPS does not contain batteries. It must, however, be used with a properly configured battery cabinet or rack with a properly sized battery system for proper operation. The installation of batteries should be performed or supervised by personnel knowledgeable of batteries and their associated precautions. Keep unauthorized personnel away from batteries.

Page 26 of the Powerware 9335 user manual — 3 Installing and Connecting Batteries
Page 26 · click to enlarge
Page 26

This page left intentionally blank

Page 27 of the Powerware 9335 user manual — 4.2 To Install a Remote EPO:
Page 27 · click to enlarge
Page 27

Installing a Remote EPO Control

4.1 Installation Procedures

Powerware 9335 — 4.1 Installation Procedures diagram (page 27)
Fig. 7 · 4.1 Installation Procedures

Figure 4–1. Typical Remote EPO Control

4.2 To Install a Remote EPO:

to the instructions in Chapter 2. To Install a Remote EPO control:

1. Securely mount the remote EPO switch. Recommended locations include near operator’s consoles or near exit doors. Refer to Remote EPO switch manufacturers installation instructions for enclosure dimensions and wiring knockouts. 2. Install wiring from the remote EPO switch using appropriate sized conduit through the Customer Interface conduit landing plate on the bottom rear of the UPS cabinet. Refer to Figure A-10 for conduit landing area,
3. Connect the Remote EPO wiring as shown in Tables 4–1 and 4–2.
Page 28 of the Powerware 9335 user manual — 4.3 To Operate a Remote EPO:
Page 28 · click to enlarge
Page 28

Table 4 – 1. Remote EPO Wire Terminations From Remote EPO Switch(s)

To X1 connector on front

of inner UPS panel Remarks

X1 - 1 Refer to switch manufacturers installation instructions X1 - 2

Twisted wires (2) 14-

Table 4 – 2. Remote EPO

REMOTE

TWISTED WIRES (2)

EPO SWITCH

X1 UPS

(N.C.)

Remote EPO switch rating is 24 VDC, 1 Amp maximum NOTE: This switch must be a dedicated switch not tied into any other circuits.

4. If you are installing multiple Remote EPO stations, wire additional stations in series with the first Remote EPO.
5. If required, install appropriate sized conduit and wiring from the Remote EPO switch to trip circuitry of upstream protective devices. A separate contact block, with the appropriate normally open or normally closed contacts, must be used for this function. Remote EPO switch wiring must be in accordance with UL Class 1 requirements.
6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation.

4.3 To Operate a Remote EPO:

1. Activation of an EPO switch will interrupt the EPO circuit and immediately shut off UPS main circuit power to the load, as well as the DC input from the battery supply. 2 . Even though the EPO switch is opened, the UPS will not re-energize until the normal startup procedure is followed, which requires operator intervention at the UPS cabinet controls.

18 gauge

Page 29 of the Powerware 9335 user manual — Section II
Page 29 · click to enlarge
Page 29

Section II

Operation

Page 30 of the Powerware 9335 user manual — Section II
Page 30 · click to enlarge
Page 30

This page left intentionally blank

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 31 of the Powerware 9335 user manual — 5 Understanding UPS Operation
Page 31 · click to enlarge
Page 31

5 Understanding UPS Operation

5.1 Looking Inside the UPS System The Powerware 9335 is a continuous duty, solid-state, transformerless (at 480 VAC) three phase, true online system that provides conditioned and uninterruptible AC power to the UPS systems output. The UPS supports process control, data processing, telecommunications/PBX, and research equipment. The Powerware 9335 maintains power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage and out-of-tolerance frequency conditions.

The basic system consists of a:

  • rectifier
  • battery charger
  • DC booster
  • Inverter
  • monitoring/operation control panel
  • integrated communications server
  • microprocessor controlled logic

In this manual, the power required by your equipment is called the critical load. The UPS supplies the critical load with conditioned power that is synchronized with your utility power. Figure 5–1 shows the main elements of the UPS.

Page 32 of the Powerware 9335 user manual — IA1
Page 32 · click to enlarge
Page 32

IA1

K4

K1

K2

IA2

N

Fig. 5–1. Main Elements of the UPS System

If utility power is interrupted or falls outside the parameters specified in Chapter 13, “Product Specifications,” the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the utility power returns. For extended power outages, the UPS is designed to operate with an alternative power system (such as a generator) or will shut down your critical load in an orderly manner, if Powerware shutdown software is used.

In the event of a severe output overload or failure of a critical internal UPS component, an emergency bypass, consisting of a continuous duty static switch, and backfeed protection contactor (K4) is utilized. The backfeed protection contactor is located in series with the static switch, to ensure safety to anyone working upstream of the UPS system. For manual transfers to bypass, the static switch is also used. The static switch is armed and ready during both types of transfers. If maintenance of the UPS system is required, an internal Maintenance Bypass switch provides a means of isolating the UPS Rectifier/Booster/Inverter components for servicing, while still supplying power to the critical load. The operation of the UPS is described in greater detail in the following paragraphs.

5-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Show 16 more labels / short text on this page
Maintenance Bypass Switch · Contactor · Static Bypass · Switch · EMI Filter · Output Switch · Input Filter Booster · Rectifier · Inverter · Output Contactor · Contactor · Output filter · EMI Filter · EMI Filter · Battery Charger · Battery
Page 33 of the Powerware 9335 user manual — 5.2 Normal, Battery and Bypass Modes
Page 33 · click to enlarge
Page 33

5.2 Normal, Battery and Bypass Modes

The UPS system functions automatically to supply AC electrical power to the critical load. There are four standard operation modes.

  • In Normal mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power. In this mode, the battery charger also provides charging current for the battery, if needed.
  • In Battery mode, the critical load is supplied by the inverter which derives its power from the battery DC power.
  • In Bypass mode, the critical load is directly supported by utility power via the static switch. In this mode, the critical load is not protected.
  • In Maintenance Bypass mode, the critical load is directly supported by utility power, but the UPS can be shut down for maintenance. The operator switching the Maintenance Bypass Switch to the Bypass position accomplishes this, however, the critical load is not protected.

The UPS continually monitors itself and the incoming utility power, and automatically switches between these modes as required, with no operator intervention, except for the Maintenance Bypass mode. The sophisticated detection and switching logic inside the UPS ensures that operating mode changes are automatic and transparent to the critical load.

System events are alarms and notices that are displayed on the LCD monitor panel. They may or may not require operator intervention. See Chapter 9. The following descriptions provide the differences in UPS operating modes.

Page 34 of the Powerware 9335 user manual — IA2
Page 34 · click to enlarge
Page 34

5.2.1 Normal Mode

Figure 5–2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode.

Normal Mode

IA1

K4

Rectifier Input Filter Booster

IA2

F1

Figure 5–2. Path of Current Through the UPS in Normal Mode

During normal UPS operation, power for the system is derived from a utility input source through the input contactor K1 (and externally protected utility feed). “Load Protected” appears on the LCD display and indicates the incoming power is within voltage and frequency acceptance windows. Three phase AC input power is converted to DC using a full-wave, six-pulse, solid-state rectifier block which supplies unregulated DC voltage to a boost converter which in turn supplies a higher, regulated DC voltage to the inverter. A separate internal battery charger is used to maintain the proper charge level on the battery during normal operation. The battery charger derives its input from the booster output and provides regulated DC voltage and charge current to the battery. The battery charge condition is monitored by the UPS and, when abnormal, reported by the status indicators located on the LCD display. The battery is always connected to the UPS and ready to support the inverter should the utility input become unavailable.

5-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Show 13 more labels / short text on this page
Static Switch · K1 Inverter K2 · Battery Charger · Breaker Contactors · Switches · Closed · Main Power · Trickle Current · Open · Energized · Battery Breaker · De-Energized · Battery
Page 35 of the Powerware 9335 user manual — 5.2.1 Normal Mode
Page 35 · click to enlarge
Page 35

The DC boost converter derives power from the unregulated DC rectifier and produces a higher, stable DC voltage and current source for the inverter. A fixed system neutral is also carried through the boost converter to allow full support of single phase AC loads from any phase of the inverter output. The output neutral of the system is connected to the required neutral, both from the main utility supply and the bypass supply and should never be bonded to protective earth ground at the UPS output. The inverter produces three phase AC power to a customer load without the use of a transformer. The inverter derives power from the boost converter regulated DC and utilizes IGBT devices and pulse-width modulation (PWM) to produce a regulated and low harmonic content AC output. The AC output of the inverter is delivered to the system output through the output contactor K2. If the utility AC power is interrupted or is out of specification, the UPS automatically switches to Battery mode to support the critical load with no interruption. When utility power returns, the UPS returns to normal mode. If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode. The UPS automatically returns to Normal mode when the overload condition is cleared and system operation is restored within specified limits. If the UPS experiences an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service.

Page 36 of the Powerware 9335 user manual — IA1
Page 36 · click to enlarge
Page 36

5.2.2 Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly. Figure 5–3 shows the path of electrical power through the UPS system when operating in the Bypass mode.

Static Bypass

IA1

Powerware 9335 — IA1 diagram (page 36)
Fig. 8

Figure 5–3. Path of Current Through the UPS in Bypass Mode In BYPASS mode, the output of the system is provided with three phase AC power directly from the systems input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or power outages from the source. Some power line filtering and spike protection is provided to the load but no active power conditioning or battery support is available to the output of the system in the bypass mode of operation.

The internal bypass is comprised of a solid state silicon controlled rectifier (SCR) static switch (SSW), and a back feed protection contactor (K4). The static switch is rated as a continuous duty device that is used anytime the boost converter and inverter is unable to support the applied load. The static switch is wired in series with the back feed protection

5-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 37 of the Powerware 9335 user manual — 5.2.2 Bypass Mode
Page 37 · click to enlarge
Page 37

contactor and together are wired to enable the inverter and rectifier to be bypassed when this path is active. The static switch, as an electronically controlled device, can be turned on immediately to pick up the load from the inverter. The backfeed protection contactor is normally always closed, ready to support the static switch unless the bypass input source becomes unavailable. During an outage, transfers to bypass are prohibited and for the safety of those who may be working on the power lines upstream from the UPS, the back feed protection contactor is opened, preventing system output voltage from bleeding across the static switch snubber components to the bypass input source. In the bypass mode, which can be used for higher efficiency operation, the static switch is turned on to supply the load current directly from the bypass supply, with the inverter ready to take over the load if the bypass supply should vary outside preset limits. If the inverter is unable to support the load on the output of the system, the UPS will transfer the critical load to the internal bypass. The critical load will be transferred automatically to the internal bypass if any of the following abnormal conditions occur on the output of the system: If the output of the system exceeds acceptable voltage tolerances; Critical load current exceeds the overload specifications of the inverter; Inverter failure. The transfer is initiated by turning on the static switch and blocking the IGBT gate signal. This kind of transfer is normally referred to as a Make-Before-Break transfer. The transfer takes place in less than 4 ms (one-quarter cycle) to ensure loads on the systems output are not interrupted. The static switch remains on until either the inverter is able to support the system output or the unit is placed into a maintenance position where repairs can be made. If the UPS initiates its own transfer to bypass for any reason other than operator intervention, the UPS will attempt to restart the inverter (if not running already) and attempt a retransfer back on line to support the output of the system. Three attempts will be made within ten minutes to bring the inverter back on-line automatically before the UPS will lock out any further attempts. After three attempts have been made, the UPS will remain in bypass and an alarm condition will be annunciated. The UPS can also be transferred to bypass using the front panel controls. Bypass mode is a normal operating mode, not requiring an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded.

Page 38 of the Powerware 9335 user manual — IA2
Page 38 · click to enlarge
Page 38

5.2.3 Battery Mode

The UPS transfers to battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power.

Figure 5–4 shows the path of electrical power through the UPS system when operating in Battery mode.

Battery Mode

IA1

K4

Rectifier Input Filter Booster

IA2

F1

Figure 5–4. Path of Current Through the UPS in Battery Mode During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC output current required to support the battery charger and boost converter. The input contactor (K1) is opened, the battery charger is turned off, and the battery SCRs (+ and -) both receive signals to turn on to provide battery power to the system. Because the battery SCRs are electronic devices, battery power is instantly available to the boost converter so that the inverter and customers load can be supported without interruption. In a single feed installation, where the bypass input is connected to the rectifier input, the back feed protection contactor (K4) will also open. The opening of contactors K1 and K4 prevents static system voltage from bleeding backwards through the static switch and rectifier snubber components and re-energizing the input source.

5-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Show 13 more labels / short text on this page
Static Switch · K1 Inverter K2 · Battery Charger · Breaker Contactors · Switches · Closed · Main Power · Trickle Current · Open · Energized · Battery Breaker · De-Energized · Battery
Page 39 of the Powerware 9335 user manual — 5.2.3 Battery Mode
Page 39 · click to enlarge
Page 39

While in battery mode, the UPS will enunciate an audible horn, indicate the status change on the front panel display with the message “MAINS NOT OK”, and make an entry into the alarm event history. As the battery discharges, the boost converter and inverter constantly make small adjustments to ensure a steady output. The UPS will remain in this operating mode until the input power to the rectifier is again within the specified voltage or frequency acceptance window. If the input power fails to return or is not within the acceptance parameters required for normal operation, the battery will continue discharging until a DC voltage level is reached where the inverter output can no longer support the connected loads. When this occurs, the unit will issue another set of audible and visual alarms indicating “BATTERY IN DISCHARGE”. Unless the rectifier has a valid input soon, the critical load will only be supported for about 3 minutes before the output of the system shuts down completely. When this occurs, the LCD display will show the message “BATTERY DISCHARGED”. If at any time during the battery discharge, the input power becomes available again, contactors K1 and K4 are closed and the rectifier will begin to supply DC current to the boost converter and inverter. The battery SCRs will be switched off while the battery charger is turned back on to begin recharging the battery. At this point, the unit returns to normal operation. The systems total operating time on battery will depend on many factors. Some factors that affect battery support times are battery type and capacity, number of parallel strings, environmental temperatures, age of the battery, and fluctuations in load demand during the discharge. The greater the load, the less support time the battery will provide. Decrease the load and the battery support time will generally increase.

Page 40 of the Powerware 9335 user manual — IA2
Page 40 · click to enlarge
Page 40

5.2.4 Maintenance Bypass Mode

An internal maintenance switch (IA1) is used to safely supply utility power to the system output during periods of maintenance or repairs. Before this switch is used, the system should be transferred to bypass. This switch has two positions: “O” (OFF) and “l” (ON). When switched to “l” (ON), the bypass source supplies the commercial AC power to the load directly. While on internal (static) bypass, when a user rotates the maintenance switch from the “O” (OFF) to the “l” (ON) position, the load is wrapped around the UPS, and power is removed from the entire upper portion of the UPS allowing service work to be completed on the UPS safely. Figure 5–5 shows the path of electrical power through the UPS system when operating in Maintenance Bypass mode.

Maintenance Bypass Mode

IA1

K4

Rectifier Input Filter Booster

IA2

F1

Figure 5–5. Path of Current through the UPS in Maintenance Bypass Mode

5-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Show 13 more labels / short text on this page
Static Switch · K1 Inverter K2 · Battery Charger · Breaker Contactors · Switches · Closed · Main Power · Trickle Current · Open · Battery Breaker · Energized · De-Energized · Battery
Page 41 of the Powerware 9335 user manual — 5.3 Functional Description
Page 41 · click to enlarge
Page 41

5.3 Functional Description

The UPS is an online double-conversion unit with a series power train. An uncontrolled rectifier feeds a boost converter, which in turn powers the inverter. The internal static bypass utilizes a static switch and an independent maintenance bypass switch is also included internal to the UPS cabinet. The unit input must be 4-wire in (plus ground) at the rectifier and 4-wire in (plus ground) at the bypass. The output can be either 4-wire plus ground or 3-wire plus ground depending on customer requirement. The unit does not incorporate any galvanic isolation, input to output. The battery string comprises 240 cells (480 volts nominal) arranged in a positive string of 120 cells and a negative string of 120 cells with the center of the series connected strings tied to system neutral, for the 80 kVA model. The 120 kVA model utilizes 144 cells on each side of the center connection (nominal 288 volts positive and negative, for 576 volts total). The battery is charged by positive and negative side chargers, which are powered from the output of the boost converter. 5.3.1 Input Rectifier The Input Rectifier is a full wave bridge uncontrolled rectifier, which produces unregulated DC of approximately +390 and –390 volts DC. A pre-charge system charges the DC bus prior to the input contactor being closed, to control inrush current to no higher than rated current levels. 5.3.2 Boost Converter A Boost Converter converts the raw DC input to a regulated DC link voltage of approximately +450 and –450 volts DC. It is operated in the current mode and is controlled using a variable modulation technique with a frequency in the range of 20 kHz. The neutral connection is maintained from the input to the output as a fixed connection. 5.3.3 Inverter and Filter The inverter is a traditional (current mode controlled) hard-switched IGBT 3-phase topology. The IGBTs are modulated by a variable frequency, current-mode control technique at approximately 20 kHz. An output filter filters out the high frequency switching components (line to neutral). 5.3.4 Batteries and Battery Charger The battery for the Powerware 80 kVA system is comprised of a positive string of 120 cells and a negative string of 120 cells, each made up of twenty 12-volt battery blocks. For the Powerware 120 kVA system, the battery strings are 144 cells positive and negative, respectively. The battery charger is divided into a positive side charger and a negative side charger, each powered from the respective positive and negative controlled DC bus voltages. The chargers operate automatically in the constant current

Page 42 of the Powerware 9335 user manual — 5.3 Functional Description
Page 42 · click to enlarge
Page 42

or constant voltage mode (temperature compensated, available as an option) based on battery condition. All batteries used in conjunction with the Powerware 9335 are external to the UPS cabinet. The internal charger charges the entire battery system, with a maximum current as indicated in Chapter 13, “Product Specifications”. Note that the higher the battery capacity, the longer the recharge time required to fully recharge the batteries. 5.3.5 Static Bypass The bypass has a continuous-duty SCR switch and a back-feed contactor (K4) in the Bypass circuit. In normal mode, the contactor connects the inverter to the output. A contactor (K2) provides isolation to the inverter when the system is on bypass. 5.3.6 Maintenance Bypass A user accessible shrouded 4-wire Mechanical Maintenance Bypass switch is provided internal to the cabinet.

5-12 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 43 of the Powerware 9335 user manual — Operational Controls and Features
Page 43 · click to enlarge
Page 43

Operational Controls and Features

6.1 General

The UPS system should function automatically and require very little attention during normal operation. The controls and indicators identified in this section are used during startup to monitor normal operation and during abnormal events.

Figure 6–1 identifies and shows the location of the controls and indicators on the Powerware 9335 (80 kVA and 120 kVA) UPS. The descriptions provide a brief overview of the UPS controls, and standard and optional features.

operation before attempting to operate any of the UPS controls or optional components.

Powerware 9335 — Operational Controls and Features diagram (page 43)
Fig. 9 · Operational Controls and Features

Rear side of User control panel (mounted on UPS cabinet door)

Parallel Isolator Switch (IA2) (used only for inverter output isolation) Customer Power Connections

Figure 6–1. Powerware 9335 (80 kVA and 120 kVA) Controls and Indicators

Page 44 of the Powerware 9335 user manual — 6.2 UPS Operational Controls
Page 44 · click to enlarge
Page 44

6.2 UPS Operational Controls

The UPS has many standard features that provide cost effective and consistently reliable power protection. 6.2.1 Control Panel

The Control Panel on the front of the UPS, pictured in Fig. 6–2, contains a LCD screen to display the current status of the UPS system. You can view a statistical history and log of system events and display a real-time representation of power flow through the system components. LED status indicators show the operating mode of the UPS and alert you to system events. Panel push buttons provide navigation through the information and control screens. The load ON/OFF pushbuttons are located at the right of the control panel. Both must be pressed simultaneously to activate the LOAD ON/OFF function. Below the LCD screen are the user control pushbuttons, RESET, UP, DOWN, and ENTER, which provide access to the control and measurement functions of the UPS. The control panel is described in detail in chapter 7, “Using the Control Panel”.

System ON/OFF LCD Display

Powerware 9335 — 6.2 UPS Operational Controls diagram (page 44)
Fig. 10 · 6.2 UPS Operational Controls

Display and Operation Push Buttons System Status LEDs

Figure 6–2. Powerware 9335 (80 kVA and 120 kVA) Control Panel

6.2.2 System and Load ON/OFF Two load ON/OFF pushbuttons are located on the right side of the LCD display. Activating both pushbuttons simultaneously will effect immediate system shutoff. This feature prevents accidental system shutdown if one of the pushbuttons is inadvertently depressed. System turn on is achieved in the same manner, by simultaneously depressing both buttons. Operation of the system ON/OFF pushbuttons is described in detail in Chapter 7, “Using the Control Panel” and Chapter 8, “UPS Operating Instructions.”

6-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 45 of the Powerware 9335 user manual — 6.3.3 Installation Features
Page 45 · click to enlarge
Page 45

6.2.3 Maintenance Bypass Switch

An internal Maintenance Bypass Switch is provided to completely isolate the main power processing of the UPS during service. The Maintenance Bypass Switch is described in detail in Chapter 8, “UPS Operating Instructions.”

6.2.4 Cold Start Capability The 9335 UPS system cannot be powered up without a utility input initially present. Accordingly, it is not able to power a load if the system is not started first on utility power. 6.3 UPS Standard Features 6.3.1 Customer Interface

Computer Interface One serial communications port, using the standard Powerware XCP interface, is provided via a plug-in interface card inserted in the communications slot on the front of the unit. This interface is supplied as standard with each Powerware 9335. You can use this port to link the UPS to the features described in Chapter 10, “Communications” and Chapter 11, “Options.”

6.3.2 Battery Management

A two-stage charging system ensures that the initial recharge is done in an optimal time, with current limited, constant current, DC applied to the batteries. When terminal voltage reaches a certain level, the charger switches to constant voltage.

6.3.3 Installation Features

Power wiring can be routed through the rear and bottom of the UPS cabinet with connections made to easily accessible terminal blocks at the bottom front of the cabinet. External monitoring and communication control wiring must be installed in accordance with approved wiring methods. Communication wiring can be routed through the top of each cabinet. Communication option cards are quickly installed in the slot behind the front door panel. X-slot cards are hot pluggable.

Page 46 of the Powerware 9335 user manual — 6.2.3 Maintenance Bypass Switch
Page 46 · click to enlarge
Page 46

6.4 Options and Accessories Contact your sales representative for information about any of these available options:

6.4.1 Remote EMERGENCY POWER OFF A REMOTE EMERGENCY POWER OFF pushbutton is an option to provide for situations where you must instantaneously control the UPS output. The operation of the REMOTE EMERGENCY POWER OFF pushbutton is described in detail in Chapter 8, “UPS Operating Instructions.” 6.4.2 Battery Cabinets A complete UPS system requires one or more battery cabinets to provide the necessary DC backup power. Battery cabinets are designed to match with the UPS cabinet, although they do not directly bolt together. 6.4.3 Communications

See Chapter 10, “Communications”.

6.4.4 Other Options Refer to Chapter 11 of this manual to review other options available for the Powerware 9335 and their use.

6-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 47 of the Powerware 9335 user manual — 6.2.3 Maintenance Bypass Switch
Page 47 · click to enlarge
Page 47

6.5 Safety Considerations The UPS enclosure is designed for industrial or computer room applications and contains safety shields. However, the system is sophisticated and should be handled with appropriate care, following these guidelines.

  • Keep surroundings clean and free from excess moisture.
  • Do not operate the system close to gas or electric heat sources.
  • The system is not intended for outdoor use.
  • The system operating environment should be maintained within the parameters stated in this manual.
  • Keep the system doors closed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit.
  • The system contains its own power source. Lethal voltages are present even when the system is disconnected from utility power.

If service or routine maintenance is required: • Ensure all power is disconnected before performing installation or service.

  • Ensure the area around the UPS is clean and uncluttered.
  • Battery cabinet maintenance or battery replacement should be performed only by authorized service personnel.
  • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment.
  • Always conform to the more detailed safety precautions described in “Important Safety Instructions” section of Chapter 12, “Maintaining the UPS System”.
Page 48 of the Powerware 9335 user manual — 6.2.3 Maintenance Bypass Switch
Page 48 · click to enlarge
Page 48

6.6 Symbols, Controls, and Indicators These symbols may appear on your UPS system or on labels inside the UPS. Most international safety agents accept them. Everyone in your organization who works with your system should understand the meaning of these symbols:

PROTECTIVE GROUNDING TERMINAL A terminal which must be connected to earth ground prior to making any other connection to the equipment.

A terminal to which or from which a direct current or voltage may be applied or supplied.

This symbol indicates the word “phase”.

ON The principal power switch is in the “ON” position.

OFF The principal power switch is in the “OFF” position.

6-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 49 of the Powerware 9335 user manual — LINE 2
Page 49 · click to enlarge
Page 49

7 Using the Control Panel

7.1 Description

This chapter describes the UPS Control Panel, including controls and indicators, and how to monitor UPS operation. The control panel is located on the front of the UPS (see Figure 7–1).

Powerware 9335 — 7 Using the Control Panel diagram (page 49)
Fig. 11 · 7 Using the Control Panel

LINE 2

BYPASS

BATTERY

LINE 1 INV

Figure 7–1. UPS Control Panel The Control Panel contains:

1. the main power ON/OFF switches
2. a flat Liquid Crystal Display (LCD) screen
3. a horizontal row of navigation pushbuttons
4. an array of multi-color LED status indicators

Refer to Chapter 8, “UPS Operating Instructions” for use of the operational controls.

Page 50 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 50 · click to enlarge
Page 50

7.2 Using the Control Panel The Control Panel provides an operator interface with the UPS system. Figure 7–2 identifies the display and pushbutton areas discussed in the following sections as well as LED indicators that provide a visual display of system operating status.

Figure 7–2. LCD Screen and Pushbuttons

LOAD S PROTECTED

ON/OFF

LINE 2

BYPASS

BATTERY

ALARM

ON/OFF

LINE 1

INV

RESET ENTER

7.2.1 Power Management Display

The 2 x 20 character LCD Screen simplifies the communication with the UPS and provides the necessary monitoring information about the UPS. The menu driven LCD Screen enables access to the

1. EVENT REGISTER 2) Measurements of input and output voltage, current, frequency, power and battery runtime 3) System commands for start-up and shut-down of the UPS and load transfer from INVERTER to BYPASS and return 4) DIAGNOSIS (SERVICE MODE) 5) Adjustments and testing information 7.2.2 LED Indicators

The LED indicators display the general status of the UPS. Indicators show the power flow status and in the event of power failure or load transfer from inverter to bypass or vise-versa, the corresponding LED indicators will change color from green (normal) to red (warning). The LINE 1 and LINE 2 LEDs indicate the availability of the input power supply. The INVERTER and BYPASS LEDs, if green, indicate which of the two power paths is supplying power to the critical load. When the battery is supplying the load, due to supply failure, the BATTERY LED will be flashing. The ALARM LED is a visual indication of any internal or external alarm conditions. At the same time, an audible alarm will be activated.

7-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 51 of the Powerware 9335 user manual — KEYS FUNCTION ON/OFF ON/OFF
Page 51 · click to enlarge
Page 51

INDICATOR INDICATOR STATUS MEANING

ALARM OFF RED + BUZZER RED

No alarm condition Alarm condition Alarm condition persists LINE 1 GREEN RED

Utility supply to rectifier available Utility supply to rectifier not available LINE 2 GREEN RED

Bypass supply available Bypass supply not available or not OK BYPASS GREEN OFF

Load on bypass (Bypass or Eco-mode) Bypass not operating (or switched off) INV GREEN RED OFF

Load on inverter Inverter fault or load not transferable to inverter Inverter not operating (switched off) BATTERY GREEN RED Flashing GREEN Flashing GREEN

Battery OK Battery fault or battery is discharged Battery discharging or battery fuse open Load OFF command issued 7.2.3 Pushbutton Functions The pushbuttons allow the user to operate the UPS to perform settings and adjustments, to start-up and shutdown the UPS, and to monitor on the LCD display the voltages, currents, frequencies and other variables of system operation.

KEYS FUNCTION ON/OFF ON/OFF

Turn-on UPS system (press both pushbuttons simultaneously)

or Shutdown the UPS (press both pushbuttons simultaneously) UP ( ) Move upwards through the menu DOWN ( ) Move downwards through the menu RESET Move to the top of the menu. Cancel the audible alarm. If the alarm condition was only transient, the LED indicator (ALARM) will also extinguish, otherwise it will remain on (RED) ENTER Confirms a chosen menu item 7.2.4 ON/OFF Startup and Shutdown Pushbuttons

By pressing simultaneously both ON/OFF pushbuttons on the Control Panel, the UPS can be switched on (if currently OFF) or shutdown immediately (if currently ON). Requiring both to be simultaneously depressed prevents accidental operation of the UPS. The two main ON/OFF pushbuttons are also used as a security ON/OFF switch, making it possible to quickly disconnect the load from the UPS in emergency situations. Upon startup from initial install or power off disconnect, the UPS starts in NORMAL (inverter) mode. In subsequent startups, the system will return to the mode previously used before shutdown, except that ECO mode will require operator intervention to activate.

Page 52 of the Powerware 9335 user manual — LOAD S
Page 52 · click to enlarge
Page 52

If, for security or emergency reasons, it is necessary to immediately disconnect the load from the UPS, press the two red ON/OFF pushbuttons simultaneously. In this case, make sure that the maintenance bypass switch (IA1) is in the “O” position (Normal=Off). 7.3 Description of the LCD Screen 7.3.1 Status Screens DESCRIPTION LCD DISPLAY Load is protected by UPS power. It is supplied by the inverter (normal operation) Load is not protected by UPS power. It is supplied by utility power. (load on bypass) Load supply is completely interrupted. UPS has been switched off by “ON/OFF” buttons NOTE: On the right hand side of the LCD display there should be a character “S”

LOAD S

PROTECTED

LOAD S

NOT PROTECTED

LOAD OFF S

SUPPLY FAILURE

indicating the Single Module is operational.

7-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 53 of the Powerware 9335 user manual — UPS SERIAL NUMBER M-
Page 53 · click to enlarge
Page 53

7.3.2 LCD Display Structure and Navigation The menu structure is shown in Figure 7–3, below. Navigation through the menu is accomplished by using the “ENTER” pushbutton to go to the menu level, or to activate an action, then using the “UP” or “DOWN” arrows to select a specific function within each menu category. The “RESET” pushbutton will immediately return to the highest screen.

PRESS RESET, RETURNS TO TOP LEVEL

LOAD PROTECTED

EVENT LOG

  • HH-MM-SS LOAD TO INV.

BATT. RUN TIME (MIN) 0.0

OUTPUT FREQUENCY (HZ) 60.00

02-27-02 HH-MM-SS LOAD TO BYP.

LOAD NOT PROTECTED

BYPASS FREQUENCY (HZ) 60.00

02-27-02 HH-MM-SS LOAD OFF

BATTERY VOLTAGE (V) + 240 -240

LOAD OFF SUPPLY FAIL

BATT. CHARGE CUR. (A) + 0.0 -0.0

MEASUREMENTS

PRESS ENTER

DISCHARGE CURRENT (A) 0

LOAD TO INVERTER

RECTIFIER VOLTAGE (V) 000 000 000

LOAD TO BYPASS PERFORM BATT.TEST

COMMANDS

BYPASS VOLTAGE (V) 000 000 000

OUTPUT VOLTAGE (V) 000 000 000

OUTPUT CURRENT (A) 00 00 00

ACTIVE POWER (kW) 00 00 00

UPS SERIAL NUMBER M-

REACTIVE POWER (KVAR) 00 00 00

UPS DATA

DATE OF MANUFACTURE

APPARENT POWER ((KVA) 00 00 00

SET-UP USER

DATE TIME

OUTPUT POWER (%) 00.0 00.0 00.0

BATT. CAPACITY (%) 00

Figure 7–3. LCD Screen Navigation Chart

Page 54 of the Powerware 9335 user manual — BYPASS FREQUENCY (HZ) 60.00
Page 54 · click to enlarge
Page 54

7.3.3 Main Menu Screen DESCRIPTION LCD DISPLAY • Logging Control. A log of the last 64 events is

EVENT LOG

stored in the Power Management Display. • Menu Measurements allow monitoring voltages,

MEASUREMENTS

power, frequencies, current, battery run time, and other information. • Command Menu enables performance of

COMMANDS

“Load to Inverter”, “Load to Bypass”, and battery test functions. • UPS Data Menu shows UPS serial number,

UPS DATA

date of manufacture, current time & date. • Set-Up Menu allows user to set Date/Time,

SET-UP USER

automatic battery test and gen-set mode • Set-Up Menu for service allows trained.

SET-UP SERVICE

service personnel to troubleshoot and adjust system parameters. 7.3.4 Event Log Screen DESCRIPTION LCD DISPLAY • Logging Control (sample screen)

02-27-02 17-03-30 LOAD TO INV.

  • A log of the last 64 events is stored

02-27-02 17-03-30 LOAD TO BYP.

and presented under the Event Log. • All events and alarms are displayed

02-27-02 17-03-30 LOAD OFF

with their date and time of occurrence. 7.3.5 Measurements Screen DESCRIPTION LCD DISPLAY • Battery Runtime remaining (in minutes)

BATT. RUN TIME (MIN) 0.0

  • UPS Output Frequency

OUTPUT FREQUENCY (HZ) 60.00

  • Bypass Frequency

BYPASS FREQUENCY (HZ) 60.00

7-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 55 of the Powerware 9335 user manual — PERFORM BATT. TEST
Page 55 · click to enlarge
Page 55

BATTERY VOLTAGE (V)

  • Battery Voltage

BATT. CHARGE CUR. (A)

  • Battery Charger Current

+ 0.0 - 0.0

DISCHARGE CURRENT (A)

  • Discharge Current

+ 0.0 - 0.0

RECTIFIER VOLTAGE (V) 0 0 0

  • Rectifier Voltage (all three phases)

BYPASS VOLTAGE (V) 0 0 0

  • Bypass Voltage (all three phases)

OUTPUT VOLTAGE (V) 0 0 0

  • Output Voltage (all three phases)

OUTPUT CURRENT (A) 0 0 0

  • Output Current (all three phases)

ACTIVE POWER (kW) 0 0 0

  • Active Output Power (all three phases)

REACTIVE POWER (kVAR) 0 0 0

  • Reactive Output Power (all three phases)

APPARENT POWER (KVA) 0 0 0

  • Apparent Output Power (all three phases)

OUTPUT POWER (%) 0% 0% 0%

  • Output Power (%, all three phases)

BATT. CAPACITY (%) 0%

  • Battery Capacity remaining

7.3.6 Commands Screen DESCRIPTION LCD DISPLAY

LOAD TO INVERTER

  • Transfer Load to Inverter

LOAD TO BYPASS

  • Transfer Load to Bypass

PERFORM BATT. TEST

  • Battery Test

+240 -240

Page 56 of the Powerware 9335 user manual — BYPASS LOCK/UNLOCK
Page 56 · click to enlarge
Page 56
  • 7.3.7 UPS Data DESCRIPTION LCD DISPLAY
  • Information displayed is installed at the time of manufacture.
  • Manufacturing Date
  • EPROM Version

UPS SERIAL NUMBER M-

DATE OF MANUFACTURE DD-MM-YY

EPROM VERSION V-000

  • Actual Date and Time (set by user under user set-up menu.

DATE TIME DD-MM-YY HH-MM-SS

7.3.8 Set-Up User DESCRIPTION LCD DISPLAY

SET-UP DATE/TIME

  • Set-up Date and Time (Press ENTER to access)
  • Set-up Battery test (Press ENTER to access)

DD-MM-YY HH-MM-SS

SET-UP BATT. TEST

DAY OF MONTH

HOUR OF DAY

REPETITIVE (Y/N)

  • Set-up operation with Gen-Set (Press ENTER to access)

SET-UP GEN-SET OPER.

  • Command to prevent battery charger operation when on generator operation.

BATTERY CHARGE LOCK (Y/N)

  • Command to prevent use of static bypass when on generator operation.

BYPASS LOCK/UNLOCK

7-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 57 of the Powerware 9335 user manual — SET-UP SERVICE
Page 57 · click to enlarge
Page 57
  • 7.3.9 Set-Up Service DESCRIPTION LCD DISPLAY
  • This menu is reserved for authorized service engineers. It is not to be accessed by End-Users.
  • Type in password.

SET-UP SERVICE

PASSWORD

run time in the SET-UP Service menu, it is also possible to set and check the following parameters:

  • UPS Rated Power
  • Module configuration S or future alternate module configurations
  • Single (standard) or Dual Input feed
  • F-converter, 50/60Hz or 60/50Hz
  • Sync window (2-4%)
Page 58 of the Powerware 9335 user manual — LINE 2 BYPASS
Page 58 · click to enlarge
Page 58

7.4 O perating Modes

7.4.1 “ON LINE” Mode (INVERTER MODE)

The ON-LINE Mode is the UPS Operating Mode in which the load is supplied through the RECTIFIER and INVERTER. LED indicators are illuminated when shown shaded:

LINE 2 BYPASS

LED’s green when shown shaded

BATTERY LINE 1 INV.

Using the control panel (see Figure 7–2) the UPS can easily be transferred to the ON- LINE mode. The ON-LINE mode provides the highest degree of protection, especially in the event of a supply disturbance or failure. This operating mode is always recommended if the critical loads (computer systems) will not tolerate any interruption of the supply, even for a very short time. In the unlikely event of an inverter fault or overload condition, the UPS will transfer the load automatically and without interruption to the static bypass-utility supply.

7.4.2 “OFF LINE” Mode (BYPASS or ECONOMY MODE) In the OFF-LINE mode, the load is supplied from the utility supply through the bypass. Using the control panel (see Figure 7–2), the UPS may be easily transferred to “Bypass Mode”. LED’s green when shown shaded When the UPS is operating in “Bypass Mode”, the efficiency of the system is higher. In the event of a utility supply failure the load will automatically be transferred from utility to

LINE 2 BYPASS

BATTERY LINE 1 INV.

7-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 59 of the Powerware 9335 user manual — LINE 2 BYPASS
Page 59 · click to enlarge
Page 59

inverter within 5 milliseconds. When utility power returns, the UPS will startup in NORMAL (inverter) mode. Operator intervention is required to reset to ECO mode. The battery charger remains active in the “Bypass-Mode”. The “Bypass-Mode” is recommended only if the loads can tolerate power interruptions of up to 5 ms, the transfer time from Bypass Mode to ON-LINE Mode.

7.4.3 “MAINTENANCE BYPASS” Mode The Maintenance Bypass Mode is performed by means of the IA1 BYPASS SWITCH on the front of the UPS. When the switch is in the “O” (OFF) position, the Bypass Switch is OPEN. This is the normal operating condition, where the load is supplied by the inverter, or via the static bypass. When the switch is in the “I” (ON) position, the Bypass Switch is CLOSED, causing load power to be supplied directly from the utility source.

LED’s green when shown shaded, unless noted

LINE 2 BYPASS

BATTERY (Red) LINE 1 INV.

Page 60 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 60 · click to enlarge
Page 60

7.4.4 Parallel Isolator (IA2) The UPS unit is provided with an output isolator switch (IA2) which, when opened, isolates the corresponding unit from the LOAD. Once IA2 is open, there is no power coming from the inverter. This switch should always be in the “I” (ON) position, except for servicing the UPS when in the maintenance bypass mode. Rotating this switch to the “O” (OFF) position while the inverter is supplying power to the load will dump the critical load. This switch is also provided for future expansion requirements.

7-12 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 61 of the Powerware 9335 user manual — 8 UPS Operating Instructions
Page 61 · click to enlarge
Page 61

8 UPS Operating Instructions

8.1 Operation The following procedures provide instruction for operating the UPS system. Refer to Chapters 6 and 7 of this manual for a description of the UPS controls and monitor panel functions. NOTE: Before starting the UPS, ensure all installation tasks are complete and

authorized service personnel have performed a preliminary startup. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the UPS operates properly. 8.2 Start-Up Procedure for the UPS

Powerware 9335 — 8 UPS Operating Instructions diagram (page 61)
Fig. 12 · 8 UPS Operating Instructions

To start the UPS system for normal operation, perform the following procedure: 1. Ensure the UPS switches and external customer circuit breakers are set as follows:

Powerware 9335 — 8 UPS Operating Instructions diagram (page 61)
Fig. 13 · 8 UPS Operating Instructions

UPS Utility Supply Breaker (customer supplied) “O” (OPEN) UPS Bypass Input Breaker (dual source, customer supplied) “O” (OPEN) UPS Battery Cabinet Breaker (customer supplied) “O” (OPEN) UPS Maintenance Bypass Switch (IA1) “O” (OFF) UPS Parallel Isolator Switch (IA2) “O” (OFF) Verify Position of DIP Switches SW 2–9 are as in Fig. 6-1. As shown

2. Close the UPS utility supply breaker. (Screen event “MAIN RECTIFIER FAULT” appears) 3. If system is dual source, close the UPS Bypass input circuit breaker 4. Observe LED Line 1 indicator turns green and battery indicator LED flashes green. (Screen event “LOAD OFF SUPPLY FAILURE” appears) 5. Press both ON/OFF pushbuttons on the control panel simultaneously to turn on the UPS. “LOAD NOT PROTECTED” will appear on the LCD screen and LED indicators will display as follows:
Page 62 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 62 · click to enlarge
Page 62

LED Indicator Color LINE 1 Green LINE 2 Green BYPASS Green INVERTER OFF BATTERY Flashing Green 6. If necessary, perform Command: LOAD TO INVERTER (see sections 7.3.2 and 7.3.6) On LCD Display, “LOAD PROTECTED” will appear and the LED-indicators will display as follows:

Powerware 9335 — LOAD S PROTECTED diagram (page 62)
Fig. 14
Powerware 9335 — LOAD S PROTECTED diagram (page 62)
Fig. 15
  • LED Indicator Color LINE 1 Green LINE 2 Green BYPASS OFF INVERTER Green BATTERY Flashing Green 7. Close the external battery cabinet circuit breaker. 8. Scroll through the measurements menu and verify that battery polarity and voltage are proper and within prescribed limits (see sections 7.3.2 and 7.3.5). For the 80 kVA model, the voltages will be about +260 and –260. For the 120 kVA model, the voltages will about +312 and –312 volts. 9. Close Parallel Isolator Switch (IA2) to position “I” (ON). UPS power is now present on the output terminal block and “LOAD PROTECTED” will appear on the LCD display. After 45-120 seconds, the battery LED will change from Flashing Green to Solid Green. This state change will take up to one minute. On initial start-up follow steps 9-14. On re-start stop at 9. 10. Perform load transfer to Maintenance Bypass
  • Use Menu COMMANDS on UPS control panel and choose “LOAD TO BYPASS” (see sections 7.3.2 and 7.3.6) to transfer the load to the bypass source.
  • Close Maintenance Bypass Switch (IA1) to position “I” (ON). The LCD display will show “MANUAL BYP. CLOSED” and the LED indicators will appear as follows:
  • LED Indicator Color LINE 1 Green LINE 2 Green BYPASS Green INVERTER Red BATTERY Green 11. Connect load to the UPS output
  • Close external output circuit breakers in the load distribution panel
  • Verify on the LCD Display and LED indicators that the load is on Bypass.
Powerware 9335 — LOAD S PROTECTED diagram (page 62)
Fig. 16

8-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 63 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 63 · click to enlarge
Page 63
  • 12. Rotate the Maintenance Bypass Switch IA1 to the “O” (OFF) position. On the LCD Display, “MANUAL BYP. OPEN” will appear followed by “LOAD NOT PROTECTED”. 13. Using the Measurements menu (see sections 7.3.2 and 7.3.5) verify proper values for output powers, voltages, currents and frequencies. 14. Perform Load transfer to Inverter
  • Go to COMMANDS menu on UPS cabinet control panel and choose command “LOAD TO INVERTER” to transfer the load to inverter output. (see sections 7.3.2 and 7.3.6)
  • On LCD Display, “LOAD PROTECTED” will appear. 15. Repeat step 13 above to verify that all voltages, currents, power and frequency are correct. 16. Once the above procedure is performed at initial start-up, subsequent start-ups may be performed using only step 14, as long as other conditions are unchanged. THE POWERWARE 9335 UPS NOW PROTECTS THE LOAD. 8.3 Complete Shutdown Procedure for the UPS

The Powerware 9335 may be shut down completely if the load does not need input power for an extended period of time. The UPS system may be switched to Maintenance Bypass Mode for service or maintenance purposes, or transferred to the ECO-Mode if the load does not need the highest degree of protection and efficiency is to be maximized. The load may be disconnected by means of the two ON/OFF (LOAD-OFF) pushbuttons for security or operational reasons. 1. Verify that the loads are shut down and that there is no need for power supply to the load.

Page 64 of the Powerware 9335 user manual — 8.4 Load Transfer to Maintenance Bypass
Page 64 · click to enlarge
Page 64
2. If the loads are all disconnected, press simultaneously the two ON/OFF buttons on the UPS control panel. On the LCD Display, “LOAD OFF, SUPPLY FAILURE” will appear and the LED-indicator will indicate as shown below:

LED Indicator Color LINE 1 Green LINE 2 OFF BYPASS OFF INVERTER OFF BATTERY Flashing Green 3. Rotate the Parallel Isolator Switch (IA2) to the “O” (OFF) position. 4. Open battery cabinet breakers in external battery cabinets or racks.

5. Open the input utility supply circuit breakers, if used.

THE POWERWARE 9335 IS NOW VOLTAGE FREE.

8.4 Load Transfer to Maintenance Bypass

If it is necessary to perform service or maintenance on the UPS, it is possible to transfer the UPS to MAINTENANCE BYPASS.

Status of the UPS-System before starting the Transfer Procedure to Maintenance Bypass

The load is protected by the Powerware 9335 UPS system in normal operation (the UPS is operating on inverter). 1) Load transfer to Maintenance Bypass • Go to Menu COMMANDS and choose command “LOAD TO BYPASS” and transfer the load to utility supply on control panel of the UPS cabinet. On the LCD Display: “LOAD NOT PROTECTED” will appear.

8-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 65 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 65 · click to enlarge
Page 65
  • Rotate the Maintenance Bypass Switch IA1 to “I” (ON) On LCD Display: “MANUAL BYP CLOSED” will appear and the LED indicators will indicate as shown below:

LED Indicator Color LINE 1 Green LINE 2 Green BYPASS Green INVERTER Red BATTERY Green 2) Simultaneously press both ON/OFF pushbuttons on the UPS cabinet control panel. • On the LCD Display: “LOAD OFF, SUPPLY FAILURE” will appear and the LED indicators will indicate as shown below:

LED Indicator Color LINE 1 Green LINE 2 OFF BYPASS OFF INVERTER OFF BATTERY Flashing Green 3) Rotate the Parallel Isolator Switch IA2 to “O” (OFF). 4) Open battery breakers in the external battery cabinet or racks THE LOAD IS NOW SUPPLIED BY THE UTILITY MAINS AND IS NOT PROTECTED.

Page 66 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 66 · click to enlarge
Page 66

This page left intentionally blank.

8-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 67 of the Powerware 9335 user manual — 9.2 Menu, Commands, Event Log, and Measurements
Page 67 · click to enlarge
Page 67

9 Responding to System Events

9.1 Alarms

In the event of an alarm condition, the red LED-Indicator “Alarm” and the audible alarm will turn on.

In this case proceed as follows:

A. Silence the audible alarm by pressing the "Reset" button. B. Identify the cause of the alarm condition by means of the

EVENT LOG in the MAIN menu. C. In case of alarm conditions, please contact the Global

Service Center. D. Fault identification and suggested corrective action is given

on the following pages.

9.2 Menu, Commands, Event Log, and Measurements

In Chapter 4 there is a detailed description of the Menu, Commands, Event Log and Measurements that can be operated and displayed on the LCD. The List of Alarms and Messages are shown in Section 9.3.

Page 68 of the Powerware 9335 user manual — BATTERY CHARGER OFF
Page 68 · click to enlarge
Page 68

9.3 Fault Identification and Correction

The major alarm conditions that will be encountered are shown in the following table:

Alarm Condition Meaning Suggested Solution

UPS FAULT There is a fault in the UPS and therefore normal operation cannot be guaranteed.

Call the authorized service center for assistance

MAINS FAILURE The utility power supply is outside its prescribed tolerance.

The input power to UPS is too low or missing. If site power appears to be OK, check the input circuit breakers etc. supplying the UPS

OVERCURRENT OR SHORT CIRCUIT

There is a short circuit at the output of UPS. (on load side)

Check all output connections and repair as required.

OVERLOAD Load exceeds the UPS rated power.

Identify which piece of equipment is causing the overload and remove it from the UPS.

OVERTEMPERATURE UPS temperature has exceeded the allowed value.

Check that the ambient temperature of the UPS is less than 30° C. If the ambient temperature is normal call the authorized service center for assistance.

BATTERY CHARGER OFF

The attached battery and the battery charger set-up do not correspond or battery charger fault.

Call the authorized service center for assistance.

INVERTER FAULT Inverter is faulty. Call the authorized service center for assistance.

NON-SYNCH The inverter and utility power are not synchronized.

The frequency of the input voltage to the UPS is outside operational limits and the UPS static bypass has been temporarily disabled.

BATTERY LOW The battery is nearly discharged.

Shutdown load connected to UPS before the UPS switches itself off to protect its batteries MANUAL SWITCH OFF Maintenance Bypass closed. Load supplied by utility power.

This alarm is only displayed if the UPS is on Maintenance Bypass

9-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 69 of the Powerware 9335 user manual — 10.1 X – Slot Communication Modules
Page 69 · click to enlarge
Page 69

10 Communications

10.1 X – Slot Communication Modules

This section describes the several types of X–Slot cards, which can be used with the Powerware 9335. X-Slot cards allow the UPS to communicate to a variety of environments and with different types of devices. The Powerware 9335 is compatible with any X–Slot card, including, but not limited to:

  • ConnectUPS TM SNMP/WEB Card – provides 10Base-T Ethernet connectivity for web-based remote monitoring in addition to SNMP capabilities.
  • ConnectUPS M SNMP Card – provides 10Base-T Ethernet connectivity for SNMP-based remote monitoring.
  • Single-Port Card – provides one serial communication port.
  • USB Card – provides a USB connection to your Windows PC.
  • Multi-Server Card – provides additional serial communication ports that can communicate with additional computers.
  • Modbus Card – provides RS-485 and RS-232 Modbus RTU connectivity for integration with building management systems.
  • Relay Card – provides dry relay contacts for AS/400 signal compatibility. The Powerware 9335 is factory installed with a Single-Port Serial Card.
Page 70 of the Powerware 9335 user manual — 10.2 Single-Port Serial Card
Page 70 · click to enlarge
Page 70

X–Slot location for insertion of X–Slot Cards

JD8

SW2-9

SW1-1

X2 X3 X4

JD2

JD1

IA1 IA2

Figure 10–1. X–Slot Location on Front of Powerware 9335 UPS Cabinet

10.2 Single-Port Serial Card

To establish communications between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable. When the communication cable is installed, power management software installed on your computer can exchange data with the UPS. Powerware supplies monitoring software with each UPS. See instructions packaged with the software for installation and operation. The software polls the UPS for detailed information on the status of the

10-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Control Panel

Page 71 of the Powerware 9335 user manual — 4 5 2 3
Page 71 · click to enlarge
Page 71

power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the connected critical load. The cable pins are identified in Figure 10–2 and the pin functions are described in Table 10–1.

4 5 2 3

Figure 10–2. The Communication Port on the Single Port Serial Card Pin Number Function Input or Output 1 Low Battery Open Collector signal – pulls to common when the UPS reaches low battery level

2 RS-232 Transmit Data Output 3 RS-232 Receive Data Input 4 Plug and Play sense Input 5 Signal Common (tied to chassis) – 6 Tied internally to pin 4 Output 7 No Connection – 8 AC Fail Open Collector signal – pulls to common during a power failure

9 DC Supply Voltage (+8 to 24 volts DC power) Output

Table 10–1. Communication Port Pin Assignments

Output · Output

Page 72 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 72 · click to enlarge
Page 72

This page left intentionally blank.

10-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 73 of the Powerware 9335 user manual — 11.1 Generator ON Facility
Page 73 · click to enlarge
Page 73

11 Options

11.1 Generator ON Facility

The generator ON facility must use a normally open contact that closes to indicate that a generator is running and supplying input power to the UPS. When used, this facility disables the UPS static bypass and prevents the UPS from transferring the load into the generator power supply. The user may also elect prevention of battery charging while on generator input. Both or either of these features may be selected via the control panel. (See section 7.3.8, Set Up)

Powerware 9335 — 11.1 Generator ON Facility diagram (page 73)
Fig. 17 · 11.1 Generator ON Facility

Figure 11–1. Generator ON Connection

Page 74 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 74 · click to enlarge
Page 74

This page left intentionally blank

11-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 75 of the Powerware 9335 user manual — 12.2 Important Safety Instructions
Page 75 · click to enlarge
Page 75

Maintaining the UPS System

12.1 General

The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, and very little disassembly. This design allows authorized service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly. Regular routine checks of operation and system parameters will enable your system to function efficiently for many trouble-free years.

12.2 Important Safety Instructions

Remember that your UPS system is designed to supply power EVEN WHEN DISONNECTED FROM THE UTILITY POWER. The UPS cabinet interiors are unsafe until the DC power source is disconnected and all capacitors are discharged. After disconnecting the utility power and the DC power, authorized service personnel should wait at least 5 minutes for capacitor bleed off before attempting internal access to the UPS cabinet. Since each battery string is an energy source in itself, opening the Battery Circuit Breaker does not de-energize the voltage within the battery string. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, you should contact your local field service office.

Page 76 of the Powerware 9335 user manual — 12.3 Performing Preventive Maintenance
Page 76 · click to enlarge
Page 76

12.3 Performing Preventive Maintenance

The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verity that the units are operating normally and that the batteries are in good condition. Perform the following checks DAILY: 1. Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the unit. 2. Ensure the air intakes (vents on the bottom) and exhaust opening (on the top of the cabinet) are not blocked. 3. Ensure the operating environment is within the parameters specified in Chapter 13, “Product Specifications.” 4. Ensure the UPS is in Normal mode. (Proper LED indicators are illuminated and the LCD display shows “LOAD PROTECTED”). If the alarm LED is illuminated or the Normal status LEDs are not illuminated, contact Customer Service. Perform the following check MONTHLY: 1. Review the Event Log for any operational issues that need attention. ANNUAL maintenance: Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact your nearest field service office for more information about service offerings.

BATTERY TestThe battery test takes approximately 3 minutes and should be performed only if:
  • There are no alarm conditions
  • The battery is fully charged
  • Utility supply is present and normal The battery testing can be carried out independently of the operation mode (OFF-LINE or ON-LINE) and whether or not the load is connected. The battery test procedure can be performed from the UPS front panel. See Chapter 7, “Using the Control Panel”. BATTERY Maintenance: Contact your nearest field service office for battery maintenance. Only authorized service personnel should perform Battery replacement and maintenance.

12-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 77 of the Powerware 9335 user manual — 13 Product Specifications
Page 77 · click to enlarge
Page 77

13 Product Specifications

13.1 System Information The UPS systems are housed in freestanding cabinets with safety shields behind the front panels. The UPS systems are available in 50 or 60 Hz configurations with either 80 or 120 kVA output ratings. The following sections detail the input output, environmental and battery specifications for each model. 13.2 UPS System Input Operating Input Voltage (Nominal +15 / -20%)

Powerware 9335 — 13 Product Specifications diagram (page 77)
Fig. 18 · 13 Product Specifications

480 VAC for operation from 384 VAC to 552 VAC (50/60 Hz)

Operating Input Frequency Range 45 – 65 Hz (continuous duty)

80 kVA Model 158 amperes 120 kVA Model 225 amperes Input Current Harmonic Content Less than 9% input THD at full load

Power Factor Minimum 0.98 Battery Voltage 80 kVA model ±240 volts nominal 120 kVA model ±288 volts nominal (center point connected to neutral) Maximum Battery Current 315 amperes (120 kVA): 252 amperes (80 kVA)

Page 78 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 78 · click to enlarge
Page 78

13.3 UPS System Output DC Ripple less than 1% voltage ripple UPS Output Capacity 100% rated current at 0.8 power factor Output Voltage Regulation ±1.5% (10–100% load)

Powerware 9335 — LOAD S PROTECTED diagram (page 78)
Fig. 19

Output Voltage Balance Each phase may be loaded to 100% independently with

voltage regulation within stated tolerance. Output Voltage Phase Displacement 120 degrees between phases ±0.01 degree

Output Transients < ±4% for 0 to 100% or 100% to 0% load change Frequency Regulation ±0.1% free running Synchronous to Bypass No-break transfer Frequency Slew Rate 1 Hz per second maximum Overload Capacity 101% to 125% for 10 minutes (25C) 126% to 150% for 30 seconds Maximum Output Capability 200% RMS for 10 cycles without bypass

13.4 Environmental Specifications Dimensions (W x H x D) mm (in.) 700 (27.6) x 1800 (70.9) x 750 (29.6) Weight Kg (lb.) 80 kVA Model 333 (733) Weight Kg (lb.) 120 kVA Model 340 (748) Operating temperature 0 to 40˚C (32 to 104˚F) Operating Altitude 1500 meters (5000 feet) with no derating Storage Temperature 0 to 50˚C (32 to 122˚F) Relative Humidity Maximum 95%, non-condensing Audible Noise with 100%/75% Load 65/63 dBA (80 kVA) 70/65 dBA (120 kVA) EMI Suppression IEC 62040-3 & FCC A Electrostatic Discharge (ESD) Immunity IEC 801-2

Powerware 9335 — LOAD S PROTECTED diagram (page 78)
Fig. 20

13-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 79 of the Powerware 9335 user manual — A
Page 79 · click to enlarge
Page 79

Appendix A – Customer Information

A

The information in this appendix will help you plan for and install your UPS system. This appendix contains the following: Table A Input/Output Ratings and external wiring 9335 – 80 Table B Input/Output Ratings and external wiring 9335 – 120 Table C UPS Power Cable Terminations 9335 – 80 & –120 Table D Power Cable Conduit Requirements 9335 – 80 & –120 Table E Maximum Input Circuit Breaker Ratings Table F Maximum Output Circuit Breaker Ratings Table G Customer Interface Inputs and Outputs Table H Customer interface to JD2 Table I Customer connections to JD1 Table J Equipment Weight Table K System Clearances Table L Air Conditioning or Ventilation Requirements Figure A–1 Front View of Powerware 9335 showing customer connections Figure A–2 Label of Powerware 9335 Figure A–3 One-line diagram of Powerware 9335 Figure A–4 Power terminal connections for Powerware 9335 Figure A–5, –6 UPS System Information Figure A–7, –8 UPS Cabinet Dimensions

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-1 164201396 REV A 07/11/2003

Page 80 of the Powerware 9335 user manual — * Full load, nominal voltage D
Page 80 · click to enlarge
Page 80

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9335 – 80 kVA

Ratings Units Rating 50/60 Hz kVA

80 Basic unit ratings at 0.8 lagging PF load INPUT/ OUTPUT

W

VOLTAGE

Amps* 105 AC INPUT

AC Input to UPS Rectifier (0.95 min. PF) 3 phase, 1 neutral, 1 ground Minimum conductor size *Max. amps include full load current plus battery recharge current

AWG or kcmil (ea) 1/0

A

Amps* 97 AC INPUT

AC Input to UPS Bypass - Full Load Current 3 phase, 1 neutral, 1 ground

Minimum conductor size AWG or kcmil (ea) 1/0

B

167 DC INPUT

DC Input from Ext. Battery source to UPS (1) positive, (1) negative, (1) mid-point

+240 0 -240

Minimum conductor size AWG or kcmil (ea) 4/0

97 AC OUTPUT Minimum conductor size AWG or kcmil (ea) 1/0

AC Output to Critical Load - Full Load Current 3 phase, 1 neutral, 1 ground

* Full load, nominal voltage D

Read and understand the following notes while planning your installation: 1. Refer to national and local electrical codes for acceptable external wiring practices. 2. Material and labor for external wiring requirements are to be provided by designated personnel.

3. For external wiring, use 90 o C copper wire. See the appropriate column in Tables A and B. When wiring to an external battery cabinet, either 75 o C or 90 o C wiring may be used. 4. Wire ampacities are chosen from Table 310-16 of the NEC.
5. A neutral feeder is required for both the main and bypass inputs to this system.
6. Refer to section 1 of this manual for installation instructions.

A-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

VDC (nominal) · Amps* · Amps*

Page 81 of the Powerware 9335 user manual — *Full load, nominal voltage D
Page 81 · click to enlarge
Page 81

Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9335 – 120 kVA

Ratings Units Rating 50/60 Hz kVA

120 96 Basic unit ratings at 0.8 lagging PF load INPUT/OUTPUT

VOLTAGE 480

Amps* 150 AC INPUT

AC Input to UPS Rectifier (0.95 min.PF) 3 phase, 1 neutral, 1 ground Minimum conductor size *Max. amps include full load current plus battery recharge current

AWG or kcmil (ea)

A

4/0

Amps* 144 AC INPUT

AC Input to UPS Bypass - Full Load Current 3 phase, 1 neutral, 1 ground

Minimum conductor size (number/phase) AWG or kcmil (ea) 4/0

B

176 DC INPUT

DC Input from Ext. Battery source to UPS (1) positive, (1) negative, (1) mid-point

+288 0 -288

Minimum conductor size (number/pole) AWG or kcmil (ea) 4/0

Amps* 144 AC OUTPUT Minimum conductor size (number/phase) AWG or kcmil (ea) 4/0

AC Output to Critical Load - Full Load Current 3 phase, 1 neutral, 1 ground

*Full load, nominal voltage D

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-3 164201396 REV A 07/11/2003

kW · VDC (nominal) · Amps*

Page 82 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 82 · click to enlarge
Page 82
7. Terminals are UL rated at 90 o C. Refer to Table C for power cable terminations and Table D for conduit requirements. Figure A–1 shows the location of power cable terminals inside the UPS. Table C. UPS Cabinet Power Cable Terminations for Powerware 9335 (80 kVA & 120 kVA) Terminal Function

Terminal Function Size of Pressure Termination

Int.Hex Size (in.) A Phase A 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 B Phase B 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 C Phase C 1 - #6-250 kcmils Cooper 42.4 (375) 3/8

Vendor Tightening Torque N-M (lb-in.)

AC Input to UPS Rectifier

N Neutral 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 A Phase A 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 B Phase B 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 C Phase C 1 - #6-250 kcmils Cooper 42.4 (375) 3/8

AC Input to Bypass (Dual Input) N Neutral 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 A Phase A 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 B Phase B 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 C Phase C 1 - #6-250 kcmils Cooper 42.4 (375) 3/8

AC Output to Critical Load

N Neutral 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 + Battery(+) 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 N Mid-point 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 DC Input from Battery to UPS

- Battery (-) 1 - #6-250 kcmils Cooper 42.4 (375) 3/8

4. #6-250 kcmils Cooper As Required

8. Per NEC article 300-20 (a), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors. 9. Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one protective ground wire of the same size. 10. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, and THW-2. Table D. Power Cable Conduit Requirements Powerware 9335 (80 kVA & 120 kVA) Powerware Product Model

Powerware 9335 — LOAD S PROTECTED diagram (page 82)
Fig. 21

No. of Conduits Rectifier Input (A,B,C,N,G) 5 2.0 inches 1 Bypass Input (A,B,C,N,G) 5 2.0 inches 1 Ext. Battery Source (+,N,-,G) 4 2.5 inches 1

Output (A,B,C,N,G) 5 2.0 inches 1 Rectifier Input (A,B,C,N,G) 5 2.5 inches 1 Bypass Input (A,B,C,N,G) 5 2.5 inches 1 Ext. Battery Source (+,N,-,G) 4 2.5 inches 1

A-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Customer Ground · Protective Ground · Protective Ground

Page 83 of the Powerware 9335 user manual — Table F. Maximum Output Circuit Breaker Ratings (Amperes)
Page 83 · click to enlarge
Page 83
11. External overcurrent protection is not provided by this product, but is required by codes. Refer to A and B for wiring requirements. If an output lockable disconnect is required, it is to be supplied by designated personnel.
12. Table E lists the maximum rating for input circuit breakers. 13. Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at the computed voltage.

Table E. Maximum Input Circuit Breaker Ratings (Amperes)

Input Voltage Rating Powerware Model

480 VAC DC 9335 – 80 kVA 150 225 9335 – 120 kVA 225 300

14. The input and bypass feeds should be symmetrical about ground. 15. The line-to-line unbalanced output capability of the Powerware 9335 UPS is limited only by the full load per phase current values for AC output to critical load shown in Tables A and B.
16. Output overcurrent protection and output disconnect switches are to be provided by the user. Table F lists the maximum rating for output circuit breakers satisfying the criteria for both.

Table F. Maximum Output Circuit Breaker Ratings (Amperes)

Rated Output voltage Powerware Model 480 VAC 9335 – 80 kVA 150 9335 – 120 kVA 225

1. Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control wiring in separate conduit from the power wiring. The wire should be rated at 150 volts, 5 amperes minimum. 2. Refer to tables G, H, and I and to Chapters 2, 4, and 11 of this manual for customer interface wiring.

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-5 164201396 REV A 07/11/2003

Page 84 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 84 · click to enlarge
Page 84

Table G. Customer Interface Inputs and Outputs Terminal Name Description X1 Emergency Power Off X1 – 1 and X1 – 2 (no polarity) X2 Generator On X2 – 1 and X2 – 2 (no polarity) X3 Battery temperature sensor X3 – 1 and X3 – 2 (no polarity) X4 Battery Shunt trip breaker control X4 – 1 and X4 – 2 (+12V & com) JD-1-1 Not Used Not Used JD-1-2 TXD Input to UPS JD-1-3 RXD Output from UPS JD-1-4 Not Used Not Used JD-1-5 Return Common JD-1-6 Not Used Not Used JD-1-7 Not Used Not Used JD-1-8 Not Used Not Used JD-1-9 Not Used Not Used JD-2-1 Utility Fail Alarm (NO) Utility Fail Alarm JD-2-2 Utility OK Utility Present JD-2-3 Common Common JD-2-4 Load on Inverter message (NO) Load on inverter message JD-2-5 Load on inverter message (NC) Load not on inverter message JD-2-6 Common Common JD-2-7 Battery Low Alarm (NO) Battery voltage low alarm JD-2-8 Battery OK Battery voltage OK JD-2-9 Common Common JD-2-10 Load on utility (bypass mode) Load on utility/bypass JD-2-11 Load on utility/bypass (NC) Load not on utility/bypass JD-2-12 Common Common JD-2-13 Common Alarm (NO) Common alarm JD-2-14 No alarm condition No alarm JD-2-15 Common Common JD-2-16 Not used Not used JD-2-17 Not used Not used JD-2-18 Not used Not used JD-2-19 Not used Not used JD-2-20 Not used Not used JD-2-21 Not used Not used JD-2-22 Ground Ground JD-2-23 +12 volts +12 volts (Imax. = 100 ma.) JD-2-24 Not used Not used JD-2-25 Not used Not used

A-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 85 of the Powerware 9335 user manual — Table H. Definition of pin connections on JD2 (25 pin DB-25P/F)
Page 85 · click to enlarge
Page 85

Table H. Definition of pin connections on JD2 (25 pin DB-25P/F)

Powerware 9335 — Table H. Definition of pin connections on JD2 (25 pin DB-25P/F) diagram (page 85)
Fig. 22 · Table H. Definition of pin connections on JD2 (25 pi…

Contacts are rated at 60 volts maximum DC or 30 volts RMS AC, and 500 mA. maximum current and should be supplied by a LVLE source in compliance with UL 1778

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-7 164201396 REV A 07/11/2003

Page 86 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 86 · click to enlarge
Page 86

Table I. Definition of pins on JD1 and interface cable connections to 9 or 25 pin connectors.

JD1 connector at UPS DB-9 connector to computer

5.. .

JD1 connector at UPS DB-25 connector to computer

1. The UPS equipment operating environment must meet the size and weight requirements shown in Table J, according to your UPS system configuration. 2. In this UPS system, the UPS, associated battery cabinets and any additional system elements are all palleted separately for shipping. 3. Do not tilt cabinets more than ± 10 ˚ during handling. 4. All equipment dimensions are shown in millimeters (inches).

A-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 87 of the Powerware 9335 user manual — Table L. Air Conditioning or Ventilation Requirements
Page 87 · click to enlarge
Page 87

Table J. Equipment Weight

Weight Kg (lbs.) Powerware Model Shipping Installed Point Loading 9335 – 80 kVA 360 (792) 333 (733) 4 at 83 (183) 9335 – 120 kVA 367 (807) 340 (748) 4 at 85 (187) 5. The clearances required around the UPS system are shown in Table K. Table K. System Clearances From Front of Cabinet 36 inches working space From Back of Cabinet 30 inches working space From Right or Left side of Cabinet ~0 inches clearance 6. The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range: 0 – 40˚C. (32 – 104˚F.) Recommended Operating Range: 20 – 25˚C. (68 – 77˚F.) Maximum Relative Humidity: 95% (non-condensing) The UPS ventilation requirements for heat removal are shown in Table L.

Table L. Air Conditioning or Ventilation Requirements

During Full Load Operation Powerware 9335 80kVA and 120 kVA Powerware Model Input/Output Voltage Heat Rejection BTU/hr x 1000/hr (g-cal/hr)

9335 – 80 kVA 480/480 linear load pf = 0.8 14.0 (3.5) 9335 – 120 kVA 480/480 linear load pf = 0.8 20.8 (5.2) 9335 – 80 kVA 480/480 linear load pf = 1.0 16.4 (4.2) 9335 – 120 kVA 480/480 linear load pf = 1.0 24.6 (3.1) 9335 – 80 kVA 480/480 100% non-linear load 17.7 (4.4) 9335 – 120 kVA 480/480 100% non-linear load 26.6 (6.6)

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-9 164201396 REV A 07/11/2003

Page 88 of the Powerware 9335 user manual — 1 ON
Page 88 · click to enlarge
Page 88

ELEMENTS:

Powerware 9335 — ELEMENTS: diagram (page 88)
Fig. 23

IA1 Maintenance Bypass IA2 Parallel Isolator JD1 Smart Port- RS232 (SUB-D9P/F) JD2 Dry Port-volt-free relays (SUB-D25/F) JD8 Parallel Port SW1-1 Single/Parallel Switch SW2-9 System Configuration Switches X1 Emergency Power OFF (EPO) X2 Generator ON X3 Battery Temperature X4 Battery Breaker control

1 ON

2 ON 3 ON 4 ON 5 ON 6 ON 7 ON 8 ON 9 ON

2N - N + 3N 1A 1B 3C 3B 3A 2C 2B 2A 1N 1C

Output (To Load) Utility Input

Powerware 9335 — 1 ON diagram (page 88)
Fig. 24

Powerware 9335 80 kVA and 120 kVA Front View showing customer connections

A-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Show 11 more labels / short text on this page
SW1-1 Module Type · HIGH Single Module · LOW Parallel Module · SW2-9 Single Cabinet · External · Battery · Bypass Input · (Single · (Dual Feed) · Feed) · On request
Page 89 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 89 · click to enlarge
Page 89
Powerware 9335 — LOAD S PROTECTED diagram (page 89)
Fig. 25

1A 1B 1C 1N 2A 2B 2C 2N 3A 3B 3C 3N + N --

USE 75°C COPPER CONDUCTORS ONLY Refer to the installation manual for tightening torque specification

USE 75°C COPPER CONDUCTORS ONLY Refer to the installation manual for tightening torque specification 0

1A 1B 1C 1N 2A 2B 2C 2N 3A 3B 3C 3N + N --

Figure A–2. Powerware 9335 80 kVA and 120 kVA Label

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-11 164201396 REV A 07/11/2003

Page 90 of the Powerware 9335 user manual — 1A, 1B, 1C, 1N RECTIFIER INPUT
Page 90 · click to enlarge
Page 90

STANDARD VERSION (DUAL INPUT FEED CONNECTION) SHOWN

A

B

K4

F1

IA2

D

Figure A–3. Powerware 9335 Oneline Drawing

PE GRND

Powerware 9335 — PE GRND diagram (page 90)
Fig. 26

Figure A–4. Power Terminals on Powerware 9335

1A, 1B, 1C, 1N RECTIFIER INPUT

2A, 2B, 2C, 2N BYPASS INPUT

+BATT, N, - BATT 3A, 3B, 3C, 3N OUTPUT TO LOAD

Figure A–4. Power Terminals on Powerware 9335

A-12 Powerware 9335 (80 kVA and 12

0 kVA) Installation and Operation 164201396 REV A 07/11/2003

Show 13 more labels / short text on this page
Fuse A · Fuse B · Cable A · Cable B · Fuse C · Rectifier · Inverter · Cable C · Static Switch · Maintenance Bypass IA1 · Load · Cable D · Fuse D
Page 91 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 91 · click to enlarge
Page 91
Powerware 9335 — LOAD S PROTECTED diagram (page 91)
Fig. 27

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

NW6004 Bypass Control J1 NW6009 Relay Control & Customer Interface

9 TXD-232 9 10 RXD-232 10 11 Modem 11

37 37 T1_Par_L1 39 39 T2_Par_L1 41 41 T1_Par_L2 43 43 T2_Par_L2 45 45 T1_Par_L3 47 47 T2_Par_L3

3 3 Byp_Serv_Cntrl 4 4 5 5 Q2_Status 6 6 8 8 Byp_Serv_Cntrl 7 7 10 10 RXD_Par 9 9 11 11 M_S_Bus 12 12 14 14 T1_Bus_Par_L1 13 13 16 16 T2_Bus_Par_L1 15 15 18 18 T1_Bus_Par_L2 17 17 20 20 T2_Bus_Par_L2 19 19 22 22 T1_Bus_Par_L3 21 21 24 24 T2_Bus_Par_L3 23 23 26 26 Connector_Error 25 25 27 27 Inv_Fail_Bus 28 28 29 29 Frq_Temp_Batt 30 30

Figure A-5. System Information

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-13 164201396 REV A 07/11/2003

Page 92 of the Powerware 9335 user manual — H
Page 92 · click to enlarge
Page 92

H

G

F

E

D

B

A

S06-0001ULA

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

y Parallel transmission circuit, communication between UPSs

y CN21 K1 driver output (power mains input contactor)

DateSignature :

Signature :

Signature :

y CN22 K4 driver output (static bypass contactor)

y CN24 Maintenance bypass switch (IA1) status

y CN6 Neutral input mains current (TA4)

y CN11 customer interface supply (safety)

y CN20 K2 driver output (output contactor)

y X1 Emergency off (normally closed)

Sheet :5 of : 5

Powerware 9335 80 and 120 kVA

y J4 aux customer interface signal bus

y CN23 Output contactor (K2) status

y CN10 Parallel port power supply

y CN26 Output switch (IA2) status

y X2 Battery temperature input

y CN9 Start up power supply

y X4 Battery breaker control

Drawn by :RMo 28/10/02

y Free voltage contacts (safety)

y Power supply startup rectifier

y X3 Generator On input

y JD2 Voltage free contacts

y J7 parallel interface bus

y Aux. customer interface

y DC link charger circuit

y JD5 Parallel Port

Date:

Date:

y CN19 Mains input

Connectors:

Checked by :

Replace :

NW6009

Functions:

y J3 Static Bypass thyristor control command, static

y Manages multi-UPS communication in parallel

y Converts Newave communication protocol to

Powerware XCP and Powerware XCP to

y J9 Connects NW6027 to socket for XCP

y Bypass and load voltage measurement

format interface card, designed by

y CN41 Connects NW6027 to NW6009

y Static Bypass current measurement

bypass and load current and voltage

y Static Bypass IGBT driver circuit

Connectors:

Connectors:

NW6004

Functions:

NW6027

Functions:

y J1 Booster and Battery control and regulation bus

y CN1,3 battery charger IGBT driver signal

y J5 Display and customer interface bus input

y J51 Display and customer interface bus output

y CN2,4,5 Inverter current sensor input

y CN12,13 + Booster IGBT driver signal

y CN14,15 - Booster IGBT driver signal

y CN17..20 Inverter L1 IGBT driver signal

y CN22..25 Inverter L2 IGBT driver signal

y CN27..30 Inverter L3 IGBT driver signal

y CN21,26 Battery thyristor driver signal

y Display interface board (galvanic insulation)

y J2 Inverter control and regulation bus

y CN10 Udc supply voltage output

y CN7,8,11 Temperature sensor input

y CN12 Customer interface supply (safety)

y Battery charger current measurement

y Battery IGBT charger driver circuit

y CN6,16 Booster shunt input

y Inverter current measurement

y CN9 Electronic supply

y Inverter IGBT driver circuit

y Booster IGBT driver circuit

Connectors:

Connectors:

NW6002

Functions:

NW6029

Functions:

y J4 aux customer interface and parallel control signal bus

y J1 Booster and Battery control and regulation bus

y CN10 Power supply for parallel data transmission

y CN11,12 Customer and parallel interface supply

y J3 Static Bypass thyristor control command

y J7 parallel control signal galvanic isolation

y CN16,17,18 Inverter voltage measurement

y J5 Display and customer interface bus

y J2 Inverter control and regulation bus

y J5 Display and customer interface bus

y CN9 Start up power supply 550Vdc

y CN5 12Vdc electronic supply

y Battery charger rating control

y Battery charger regulation

y CN8 DC supply input

y Electronic power supply

y Inverter rating control

y Booster rating control

y CN39 Fan regulation

Connectors:

Connectors:

NW4001

Functions:

NW4007

Functions:

H

G

F

E

D

B

A

Figure A-6. System Information

A-14 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Show 17 more labels / short text on this page
y Contactor driver · y User setup · y EPO input · Electrical Diagram · (safety) · Newave communication protocol · Modification · Powervare · measurement · systems · Modification · (safety) · (safety) · y Inverter regulation · y Booster regulation · y Customer interface · y Display
Page 93 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 93 · click to enlarge
Page 93

700 mm. (27.6 inches)

Powerware 9335 — LOAD S PROTECTED diagram (page 93)
Fig. 28

1800 mm. (70.9 inches)

Removable Conduit Landing Plate

Figure A–7. UPS Cabinet Dimensions (Rear View)

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-15 164201396 REV A 07/11/2003

Page 94 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 94 · click to enlarge
Page 94

750 mm. (29.6 inches) 700 mm. (27.6 inches)

Powerware 9335 — LOAD S PROTECTED diagram (page 94)
Fig. 29

1800 mm. (70.9

Figure A–8. UPS Cabinet Dimensions

A-16 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 95 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 95 · click to enlarge
Page 95
Powerware 9335 — LOAD S PROTECTED diagram (page 95)
Fig. 30
Page 96 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 96 · click to enlarge
Page 96
Powerware 9335 — LOAD S PROTECTED diagram (page 96)
Fig. 31
Page 97 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 97 · click to enlarge
Page 97
Powerware 9335 — LOAD S PROTECTED diagram (page 97)
Fig. 32
Page 98 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 98 · click to enlarge
Page 98
Powerware 9335 — LOAD S PROTECTED diagram (page 98)
Fig. 33
Page 99 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 99 · click to enlarge
Page 99

LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE PRODUCTS Subject to the conditions herein, Invensys Powerware (Powerware ®) warrants solely, to the original end-user, the electronics (the “Unit”), and Powerware built battery cabinets, against defects in material and workmanship for the warranty period of 12 months, from the date of equipment start up, or 18 months from date of shipment, whichever occurs first. Should service be necessary, this warranty covers:

USA onlyThe Powerware 9315, 9330, 9335 three-phase UPS products are sold with a standard factory

warranty (described below), start up, and extended labor service. All three-phase UPS installations will have an authorized Invensys Powerware Service Engineer or Agent perform startup or the factory warranty and extended labor service will be void. The included first year extended labor service provides for a complete 12 months of onsite labor for your UPS purchase. Worldwide: All parts requiring replacement for the Factory Warranty period. If, in the opinion of Invensys Powerware, the Unit fails to meet published specifications and the defect is within the terms of this warranty, the Unit will be repaired or replaced at the option of Invensys Powerware with no charge for replacement parts. Labor required, to make upgrades, repairs or replacement installation, is not included under the terms of this Limited Warranty, except for labor and travel costs required during the first 90 days of this warranty (USA only), provided that startup of the unit onsite, has been performed by Invensys Powerware or its agent. Equipment sold, but not manufactured by Invensys Powerware, and only the manufacturer of such equipment shall warrant this equipment and is not included as part of this warranty agreement. Equipment repaired or replaced pursuant to this warranty will be warranted for the remaining portion of the original warranty subject to all the terms thereof. This warranty is not valid unless an authorized Invensys Powerware Service Engineer or Agent performs startup and commissioning. This warranty does not apply to any Unit that has been subject to neglect, accident, abuse, misuse, misapplication, incorrect installation, or that has been subject to repair or alteration, not authorized in writing by Invensys Powerware personnel or performed by an authorized Invensys Powerware Service Engineer or Agent. Purchaser shall be invoiced for, and shall pay for, all services not expressly provided for by the terms hereof, including, without limitation, site calls involving an inspection that determines no corrective maintenance is required. THIS WARRANTY IS THE PURCHASER’S (USER’S) SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NOT OTHER, EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED). In no case will Invensys Powerware’s liability under this Warranty exceed the replacement value of the Unit warranted. Invensys Powerware’s obligation, under said warranty, is expressly conditioned upon receipt by Invensys Powerware of all payments due it (including interest charges, if any). During such time as Invensys Powerware has not received payment of any amount due it, in accordance with the Contract terms under which the equipment is sold, Invensys Powerware shall have no obligation, under said warranty; also during this time, the period of said warranty shall continue to run and the expiration of said warranty shall not be extended upon payment of the overdue amount. These limitations, to said warranty, apply even in the event that the equipment is sold initially by Invensys Powerware for resale to an ultimate end-user. In no event shall Invensys Powerware be liable for any indirect, incidental special or consequential damages of any kind or type whatsoever, or based on any claim or cause of action, however denominated. Invensys Powerware shall not be responsible for failure to provide service or parts due to causes beyond Invensys Powerware’s reasonable control. This limited warranty applies only to the original end user of the unit. This factory warranty will not be in effect if the End-User does not properly store the equipment, including the “trickle charge” of batteries no later than the date indicated on the packaging, before installation and does not cover shipping damages if FOB Factory. Cost for replacement equipment, installation, material freight charges travel expenses and labor of Invensys Powerware representatives will be borne by the Purchaser (user). Any advice furnished the Purchaser before or after delivery in regard to use or application of Powerware equipment is furnished without charge and on the basis that it represents Invensys Powerware’s best judgment under the circumstances. The use of any such advice by the Purchaser is solely and entirely at its own risk. Any other agreements, such as Service contracts or Sales Concessions are not means to annul this Factory Warranty. For comment or questions, about this Limited Factory Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, NC 27601, or call (919) 872---3020

Powerware 9335 (80 kVA-120 kVA) Installation and Operation W-1 164201396 REV. A 071103

Page 100 of the Powerware 9335 user manual — LOAD S PROTECTED
Page 100 · click to enlarge
Page 100

This page left intentionally blank

W-2 Powerware 9335 (80 kVA – 120 kVA) Installation and Operation

Ask about the Powerware 9335

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Powerware 9335

Be the first to ask — other owners or our team will answer.