Supply
80 kVA and 120 kVA Installation and Operation
Manual



SAVE THESE INSTRUCTIONS
This manual contains important instructions for your Uninterruptible Power Supply (UPS) system. You should follow these instructions during the installation and maintenance of the UPS, options, accessories and batteries.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference with the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense.
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation ii 164201396 REV. A 071103



Section II Operation 5 Understanding UPS Operation 5.1 Looking Inside the UPS System 5 - 1 5.2 Normal, Battery and Bypass Modes 5 - 3 5.2.1 Normal Mode 5 - 4 5.2.2 Bypass Mode 5 - 6 5.2.3 Battery Mode 5 - 8 5.2.4 Maintenance Bypass Mode 5 - 10 5.3 Functional Description 5 - 11 5.3.1 Input Rectifier 5 - 11 5.3.2 Boost Converter 5 - 11 5.3.3 Inverter and Filter 5 - 11 5.3.4 Battery and Battery Charger 5 - 11 5.3.5 Static Bypass 5 - 12 5.3.6 Maintenance Bypass 5 - 12 6 Operational Controls and Features 6.1 General 6 - 1 6.2 UPS Operational Controls 6 - 2 6.2.1 Control Panel 6 - 2 6.2.2 System and Load ON/OFF 6 - 2 6.2.3 Maintenance Bypass Switch 6 - 3 6.2.4 Cold Start Capability 6 - 3 6.3 UPS Standard Features 6 - 3 6.3.1 Customer Interface 6 - 3 6.3.2 Battery Management 6 - 3 6.3.3 Installation Features 6 - 3 6.4 Options and Accessories 6 - 4 6.4.1 Remote EMERGENCY POWER OFF 6 - 4 6.4.2 Battery Cabinets 6 - 4 6.4.3 Communications 6 - 4 6.4.4 Other Options 6 - 4 6.5 Safety Considerations 6 - 5 6.6 Symbols, Controls and Indicators 6 - 6 7 Using the Control Panel 7.1 Description 7 - 1 7.2 Using the Control Panel 7 - 2 7.2.1 Power Management Display 7 - 2 7.2.2 LED Indicators 7 - 2 7.2.3 Pushbutton Functions 7 - 3 7.2.4 ON/OFF Shutdown and Startup Pushbuttons 7 - 3 7.3 Description of the LCD Screen 7 - 4 7.3.1 Status Screens 7 - 4 7.3.2 LCD Display Structure and Navigation 7 - 5 7.3.3 Main Menu Screen 7 - 6 7.3.4 Event Log Screen 7 - 6 7.3.5 Measurements Screen 7 - 6 7.3.6 Command Screen 7 - 7
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation iv 164201396 REV. A 071103

7.3.7 UPS Data 7 - 8 7.3.8 Set-Up User 7 - 8 7.3.9 Set-Up Service 7 - 9 7.4 Operating Modes 7 - 10 7.4.1 “ON-LINE” Mode (Inverter Mode) 7 - 10 7.4.2 “OFF-LIINE” Mode (BYPASS or ECONOMY Mode) . 7 - 10 7.4.3 “MAINTENANCE BYPASS” Mode 7 - 11 7.4.4 Parallel Isolator (IA2) 7 - 12 8 UPS Operating Instructions 8.1 Operation 8 - 1 8.2 Start-Up Procedure for the UPS 8 - 1 8.3 Shut-Down Procedure for the UPS 8 - 3 8.4 Load Transfer to Maintenance Bypass 8 - 4 9 Responding to System Events 9.1 Alarms 9 - 1 9.2 Menu, Commands, Event Log, Measurements 9 - 1 9.3 Fault Identification and Correction 9 - 2 10 Communications 10.1 X – Slot Communication Modules 10 - 1 10.2 Single-Port Module 10 - 2 11 Options 11.1 Generator ON Facility 11 - 1 12 Maintaining the UPS System 12.1 General 12 - 1 12.2 Important Safety Instructions 12 - 1 12.3 Performing Preventive Maintenance 12 - 2 13 Product Specifications 13.1 System Information 13 - 1 13.2 UPS System Input 13 - 1 13.3 UPS System Output 13 - 2 13.4 Environmental Specifications 13 - 2 Appendix A – Customer Information A - 1 Warranty W - 1
v Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Figure 1 – 1 Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet Figure 4 – 1 Typical Remote EPO Control Figure 5 – 1 Main Elements of the UPS System Figure 5 – 2 Path of Current through the UPS in Normal Mode Figure 5 – 3 Path of Current through the UPS in Bypass Mode Figure 5 – 4 Path of Current through the UPS in Battery Mode Figure 5 – 5 Path of Current through the UPS in Maintenance Bypass Mode Figure 6 – 1 Powerware 9335 (80 kVA and 120 kVA) Controls and Indicators Figure 6 – 2 Powerware 9335 (80 kVA and 120 kVA) Control Panel Figure 7 – 1 UPS Control Panel Figure 7 – 2 LCD Screen and Pushbuttons Figure 7 – 3 LCD Screen Navigation Chart Figure 10 – 1 X – Slot Location on Front of Powerware 9335 UPS Cabinet Figure 10 – 2 The Communication Port on the Single Port Serial Card Figure 11 – 1 Generator ON Connection
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation vi 164201396 REV. A 071103

Table 4 – 1 Remote EPO Wire Terminations Table 4 – 2 Remote EPO Table 10 – 1 Communication Port Pin Assignments
vii Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Powerware 9335 UPS true double conversion online power protection can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment production due to unexpected power problems. The Powerware UPS System continuously monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power. Working with your building’s electrical system, the UPS System supplies clean consistent power that your sensitive electronic equipment requires for reliable operation. During brownouts, blackouts and other power interruptions, optional battery strings provide emergency power to safeguard your operation. The UPS system is housed in free-standing cabinets. The cabinet sections are matching in design and color, and have safety shields behind the front panels for hazardous voltage protection. The following illustration depicts a typical Powerware 9335 (80 kVA and 120 kVA) UPS System.

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation viii 164201396 REV. A 071103

These basic UPS system configurations are possible:
Your UPS functions automatically and requires very little attention during normal operation. However, you should read and understand the procedures described in this manual to ensure trouble-free operation. In particular, you should be thoroughly familiar with the Remote Emergency Power Off procedure described in Chapter 4 of this manual. The information in this manual is divided into the sections and chapters listed. The system you are installing dictates which parts of the manual you should read. Everyone should read the Introduction, Chapters 1, 2, 7, and 8. Introduction The introduction provides a brief description of the UPS system, a description of the content of each chapter, safety, and text conventions used in the manual and reference information. Section I – Installation
ix Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Section II – Operation
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation x 164201396 REV. A 071103

The UPS cabinet is designed for industrial or computer room applications, and contain safety shields behind the doors. However, the UPS system is a sophisticated power system and should be handled with appropriate care, following these guidelines:
If service or routine maintenance is required:
If you need to schedule initial startup, need regional locations and telephone numbers, have a question about any of the information in this manual, or have a question this manual does not answer, please call Powerware Corporation at: United States 1 – 800 – 843 – 9433
Canada 1 – 800 – 461 – 9166
Outside the U.S. Call your local representative
xi Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103

Installation

This page left intentionally blank

1.1 Installing the UPS
The complete UPS cabinet is shipped on a single pallet. Use a forklift or a pallet jack, rated to handle the weight of the cabinets (refer to Table J in Appendix A for cabinet weights) to move the packaged cabinet to the installation site, or as close as possible to the site, before unloading from the pallet. This is the basic sequence of the installation steps: 1. Create an installation plan for the UPS system. (Chapter 1)
personnel. This service is usually offered as part of the service contract for your UPS. Contact Global Services in advance (usually a two week notice is required) to reserve a preferred startup date.)
Before beginning to install the UPS system, read and understand how this manual applies to the system being installed. Use the procedures and illustrations in the following chapters to create a logical plan for installing the system.

For your UPS to operate at peak efficiency, your installation site should meet the environmental parameters outlined in this manual. If you intend to operate the system at an altitude higher than 1500 meters (5000 feet), contact your local sales or service office for important information about high altitude operation. The operating environment must meet the weight, airflow, size and clearance requirements specified in Appendix A. The basic environmental requirements of the UPS system are: Ambient Temperature Range: 0 – 40˚C (32 – 104˚F) Recommended Operating Range: 20 – 25˚C (68 – 77˚F) Maximum Relative Humidity: 95% (non-condensing) The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the bottom sides and front of the cabinet, and outlets in the top of the cabinet. You must allow clearance in back of the cabinet for proper air circulation. Refer to Table K of Appendix A for clearance requirements. 1.1.3 Environmental Considerations
The life of the UPS system is adversely affected if the installation does not meet the following guidelines:
Failure to follow guidelines may invalidate the UPS warranty. 1.1.4 Preparing for Wiring the UPS System
For external wiring requirements, including the minimum AWG size of external wiring, refer to Tables A and B in Appendix A for the Powerware 9335 (80 kVA and 120 kVA) UPS. The power wiring connections for this equipment are rated using copper wire at 90˚C. Note that wiring to an external battery cabinet may be either 75˚C or 90˚C rated. Control wiring for EPO and optional accessories (such as building alarm and monitoring interface) should be connected at the customer interface connections inside the front of the UPS using class 1 wiring methods.

The first task in preparing for installation is inspecting and unpacking the UPS. The UPS and accessory cabinets are shipped bolted to wooden pallets, as shown in Figure 1–1, and protected with outer protective packaging material.



Figure 1–1. Powerware 9335 (80 kVA and 120 kVA) UPS Packaging

and other harmful contaminants. Failure to store and protect the UPS properly may invalidate the warranty.


Refer to the following while installing the UPS system:

To install an UPS cabinet, perform the procedures in the following paragraphs.
2.2.1 Unloading the Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet from the Pallet
The UPS cabinet is bolted to a wooden shipping base using two steel angles. To remove the shipping material, perform the following procedure.
3. Unbolt the wooden cross members on the shipping base by removing the four nuts (10 mm) which fasten the wooden pallet to the steel brackets. Remove the wooden cross members from the steel brackets. Insert the jacking bolts into the holes and lower them to the ground, in order for the weight of the unit to be supported by the 4 bolts. Place small metal plates under the jacking bolts to prevent floor damage. Ensure the unit does not tilt more than specified in the caution note above. Remove the forklift or pallet jack once the unit is supported on the jacking bolts. Slowly lower the UPS by alternating between the four jacking bolts, until the steel brackets are on the floor. Remove the jacking bolts. Detach the UPS cabinet from the angle steel by removing all of the M5 Phillips-head machine screws that fasten them, using a #3 Phillips head screwdriver. Tilt the unit slightly to enable the steel bracket to be removed from beneath two legs. Lower the unit down to the floor.

The Powerware 9335 contains no internal batteries and must therefore be used with an external battery system. The procedure for wiring the battery system to the 9335 is described as follows. Also read the manual provided with the battery system to ensure proper interconnections on the battery side.
and remove the bottom internal protective panel. Retain hardware.
holes as required. When reinstalling, ensure that the protective ground wire is reconnected if it has been removed for conduit hole punching in the plate.
holes as required. When reinstalling, ensure that the protective ground wire is reconnected if it has been removed for conduit hole punching in the plate. 2. Route input and output cables through wireway to UPS terminal blocks. Refer to Appendix A of this manual for wiring access information.

An insulated grounding conductor must be provided per NEC.
4. If the installation is for a single utility feed with common rectifier and bypass input, proceed to step 7. For a separate bypass and rectifier input, proceed to step 5. 5. Remove the single feed bus bar jumper connections from between X6 and X7, Phase A, B, and C and discard them. They will not be used again. 6. Connect ground, phase A, B, C, and Neutral mains input power wiring from the source to the Mains input terminals (1A, 1B, 1C) on the In/Out Terminal Block. Phase A input connects to input terminal 1A, phase B to input terminal 1B and phase C to input terminal 1C. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Note wiring connections for dual feed systems. 7. Connect ground, phase A, B, C, and Neutral power wiring from the output terminals (3A, 3B, 3C) on the In/Out Terminal Block to the critical load. Output terminal 3A connects to phase A of the load, output 3B to phase B and output 3C to phase C, respectively. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. 8. Secure the UPS by reinstalling the safety shield panels, and closing the front cabinet door, latching the cabinet door with the removable door handle.
See Chapter 10, “Communications”
(REPO) switch, you must install conduit between each device and the UPS cabinet for wiring these options. 1. Be sure the UPS system is turned off and all power sources are removed. (See the operation section of this manual for shutdown instructions.)

The Powerware 9335 has no batteries within the UPS cabinet. An external battery cabinet with appropriate batteries installed is required for proper system operation. See installation instruction provided with the battery cabinet for proper installation of that portion of the system.
Startup and operational checks should be performed only by authorized service personnel. Contact service in advance (usually a two week notice is required) to reserve a preferred startup date.
The final step in installing your UPS system is completing the following Installation Checklist. This checklist ensures that you have completely installed all hardware, cables, and other equipment. Completing all items listed on the checklist will ensure a smooth installation. You should make a copy of the Installation Checklist before filling it out, and retain the original. After your installation is complete, a service representative will be able to verify the operation of your UPS system and commission it to support your critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters. Service personnel may request a copy of the

completed Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the UPS
system for the first time.
All packing materials and restraints have been removed from each cabinet.
Each cabinet in the UPS system is placed in the installed location.
All conduits and cables are properly routed to the UPS and auxiliary cabinets.
All power cables are properly sized and terminated.
All network connections have been completed.
A ground conductor is properly installed.
Battery cabinet installation instructions have been completed.
Air conditioning equipment is installed and operating properly.
The area around the installed UPS system is clean and dust-free. (It is recommended
that the UPS be installed on a level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.
Adequate lighting is provided around all UPS equipment.
Any optional accessories are mounted in their installed location and properly wired.
Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
Startup and operational checks performed by authorized service personnel.

The Powerware 9335 UPS does not contain batteries. It must, however, be used with a properly configured battery cabinet or rack with a properly sized battery system for proper operation. The installation of batteries should be performed or supervised by personnel knowledgeable of batteries and their associated precautions. Keep unauthorized personnel away from batteries.

This page left intentionally blank


Figure 4–1. Typical Remote EPO Control
to the instructions in Chapter 2. To Install a Remote EPO control:

To X1 connector on front
of inner UPS panel Remarks
X1 - 1 Refer to switch manufacturers installation instructions X1 - 2
Twisted wires (2) 14-
REMOTE
TWISTED WIRES (2)
EPO SWITCH
X1 UPS
(N.C.)
Remote EPO switch rating is 24 VDC, 1 Amp maximum NOTE: This switch must be a dedicated switch not tied into any other circuits.
18 gauge

Operation

This page left intentionally blank
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

5.1 Looking Inside the UPS System The Powerware 9335 is a continuous duty, solid-state, transformerless (at 480 VAC) three phase, true online system that provides conditioned and uninterruptible AC power to the UPS systems output. The UPS supports process control, data processing, telecommunications/PBX, and research equipment. The Powerware 9335 maintains power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage and out-of-tolerance frequency conditions.
The basic system consists of a:
In this manual, the power required by your equipment is called the critical load. The UPS supplies the critical load with conditioned power that is synchronized with your utility power. Figure 5–1 shows the main elements of the UPS.

K4
K1
K2
IA2
N
Fig. 5–1. Main Elements of the UPS System
If utility power is interrupted or falls outside the parameters specified in Chapter 13, “Product Specifications,” the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the utility power returns. For extended power outages, the UPS is designed to operate with an alternative power system (such as a generator) or will shut down your critical load in an orderly manner, if Powerware shutdown software is used.
In the event of a severe output overload or failure of a critical internal UPS component, an emergency bypass, consisting of a continuous duty static switch, and backfeed protection contactor (K4) is utilized. The backfeed protection contactor is located in series with the static switch, to ensure safety to anyone working upstream of the UPS system. For manual transfers to bypass, the static switch is also used. The static switch is armed and ready during both types of transfers. If maintenance of the UPS system is required, an internal Maintenance Bypass switch provides a means of isolating the UPS Rectifier/Booster/Inverter components for servicing, while still supplying power to the critical load. The operation of the UPS is described in greater detail in the following paragraphs.
5-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The UPS system functions automatically to supply AC electrical power to the critical load. There are four standard operation modes.
The UPS continually monitors itself and the incoming utility power, and automatically switches between these modes as required, with no operator intervention, except for the Maintenance Bypass mode. The sophisticated detection and switching logic inside the UPS ensures that operating mode changes are automatic and transparent to the critical load.
System events are alarms and notices that are displayed on the LCD monitor panel. They may or may not require operator intervention. See Chapter 9. The following descriptions provide the differences in UPS operating modes.

Figure 5–2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode.
K4
Rectifier Input Filter Booster
F1
Figure 5–2. Path of Current Through the UPS in Normal Mode
During normal UPS operation, power for the system is derived from a utility input source through the input contactor K1 (and externally protected utility feed). “Load Protected” appears on the LCD display and indicates the incoming power is within voltage and frequency acceptance windows. Three phase AC input power is converted to DC using a full-wave, six-pulse, solid-state rectifier block which supplies unregulated DC voltage to a boost converter which in turn supplies a higher, regulated DC voltage to the inverter. A separate internal battery charger is used to maintain the proper charge level on the battery during normal operation. The battery charger derives its input from the booster output and provides regulated DC voltage and charge current to the battery. The battery charge condition is monitored by the UPS and, when abnormal, reported by the status indicators located on the LCD display. The battery is always connected to the UPS and ready to support the inverter should the utility input become unavailable.
5-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The DC boost converter derives power from the unregulated DC rectifier and produces a higher, stable DC voltage and current source for the inverter. A fixed system neutral is also carried through the boost converter to allow full support of single phase AC loads from any phase of the inverter output. The output neutral of the system is connected to the required neutral, both from the main utility supply and the bypass supply and should never be bonded to protective earth ground at the UPS output. The inverter produces three phase AC power to a customer load without the use of a transformer. The inverter derives power from the boost converter regulated DC and utilizes IGBT devices and pulse-width modulation (PWM) to produce a regulated and low harmonic content AC output. The AC output of the inverter is delivered to the system output through the output contactor K2. If the utility AC power is interrupted or is out of specification, the UPS automatically switches to Battery mode to support the critical load with no interruption. When utility power returns, the UPS returns to normal mode. If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode. The UPS automatically returns to Normal mode when the overload condition is cleared and system operation is restored within specified limits. If the UPS experiences an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service.

The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly. Figure 5–3 shows the path of electrical power through the UPS system when operating in the Bypass mode.

Figure 5–3. Path of Current Through the UPS in Bypass Mode In BYPASS mode, the output of the system is provided with three phase AC power directly from the systems input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or power outages from the source. Some power line filtering and spike protection is provided to the load but no active power conditioning or battery support is available to the output of the system in the bypass mode of operation.
The internal bypass is comprised of a solid state silicon controlled rectifier (SCR) static switch (SSW), and a back feed protection contactor (K4). The static switch is rated as a continuous duty device that is used anytime the boost converter and inverter is unable to support the applied load. The static switch is wired in series with the back feed protection
5-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

contactor and together are wired to enable the inverter and rectifier to be bypassed when this path is active. The static switch, as an electronically controlled device, can be turned on immediately to pick up the load from the inverter. The backfeed protection contactor is normally always closed, ready to support the static switch unless the bypass input source becomes unavailable. During an outage, transfers to bypass are prohibited and for the safety of those who may be working on the power lines upstream from the UPS, the back feed protection contactor is opened, preventing system output voltage from bleeding across the static switch snubber components to the bypass input source. In the bypass mode, which can be used for higher efficiency operation, the static switch is turned on to supply the load current directly from the bypass supply, with the inverter ready to take over the load if the bypass supply should vary outside preset limits. If the inverter is unable to support the load on the output of the system, the UPS will transfer the critical load to the internal bypass. The critical load will be transferred automatically to the internal bypass if any of the following abnormal conditions occur on the output of the system: If the output of the system exceeds acceptable voltage tolerances; Critical load current exceeds the overload specifications of the inverter; Inverter failure. The transfer is initiated by turning on the static switch and blocking the IGBT gate signal. This kind of transfer is normally referred to as a Make-Before-Break transfer. The transfer takes place in less than 4 ms (one-quarter cycle) to ensure loads on the systems output are not interrupted. The static switch remains on until either the inverter is able to support the system output or the unit is placed into a maintenance position where repairs can be made. If the UPS initiates its own transfer to bypass for any reason other than operator intervention, the UPS will attempt to restart the inverter (if not running already) and attempt a retransfer back on line to support the output of the system. Three attempts will be made within ten minutes to bring the inverter back on-line automatically before the UPS will lock out any further attempts. After three attempts have been made, the UPS will remain in bypass and an alarm condition will be annunciated. The UPS can also be transferred to bypass using the front panel controls. Bypass mode is a normal operating mode, not requiring an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded.

The UPS transfers to battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power.
Figure 5–4 shows the path of electrical power through the UPS system when operating in Battery mode.
K4
Rectifier Input Filter Booster
F1
Figure 5–4. Path of Current Through the UPS in Battery Mode During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC output current required to support the battery charger and boost converter. The input contactor (K1) is opened, the battery charger is turned off, and the battery SCRs (+ and -) both receive signals to turn on to provide battery power to the system. Because the battery SCRs are electronic devices, battery power is instantly available to the boost converter so that the inverter and customers load can be supported without interruption. In a single feed installation, where the bypass input is connected to the rectifier input, the back feed protection contactor (K4) will also open. The opening of contactors K1 and K4 prevents static system voltage from bleeding backwards through the static switch and rectifier snubber components and re-energizing the input source.
5-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

While in battery mode, the UPS will enunciate an audible horn, indicate the status change on the front panel display with the message “MAINS NOT OK”, and make an entry into the alarm event history. As the battery discharges, the boost converter and inverter constantly make small adjustments to ensure a steady output. The UPS will remain in this operating mode until the input power to the rectifier is again within the specified voltage or frequency acceptance window. If the input power fails to return or is not within the acceptance parameters required for normal operation, the battery will continue discharging until a DC voltage level is reached where the inverter output can no longer support the connected loads. When this occurs, the unit will issue another set of audible and visual alarms indicating “BATTERY IN DISCHARGE”. Unless the rectifier has a valid input soon, the critical load will only be supported for about 3 minutes before the output of the system shuts down completely. When this occurs, the LCD display will show the message “BATTERY DISCHARGED”. If at any time during the battery discharge, the input power becomes available again, contactors K1 and K4 are closed and the rectifier will begin to supply DC current to the boost converter and inverter. The battery SCRs will be switched off while the battery charger is turned back on to begin recharging the battery. At this point, the unit returns to normal operation. The systems total operating time on battery will depend on many factors. Some factors that affect battery support times are battery type and capacity, number of parallel strings, environmental temperatures, age of the battery, and fluctuations in load demand during the discharge. The greater the load, the less support time the battery will provide. Decrease the load and the battery support time will generally increase.

An internal maintenance switch (IA1) is used to safely supply utility power to the system output during periods of maintenance or repairs. Before this switch is used, the system should be transferred to bypass. This switch has two positions: “O” (OFF) and “l” (ON). When switched to “l” (ON), the bypass source supplies the commercial AC power to the load directly. While on internal (static) bypass, when a user rotates the maintenance switch from the “O” (OFF) to the “l” (ON) position, the load is wrapped around the UPS, and power is removed from the entire upper portion of the UPS allowing service work to be completed on the UPS safely. Figure 5–5 shows the path of electrical power through the UPS system when operating in Maintenance Bypass mode.
IA1
K4
Rectifier Input Filter Booster
F1
Figure 5–5. Path of Current through the UPS in Maintenance Bypass Mode
5-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The UPS is an online double-conversion unit with a series power train. An uncontrolled rectifier feeds a boost converter, which in turn powers the inverter. The internal static bypass utilizes a static switch and an independent maintenance bypass switch is also included internal to the UPS cabinet. The unit input must be 4-wire in (plus ground) at the rectifier and 4-wire in (plus ground) at the bypass. The output can be either 4-wire plus ground or 3-wire plus ground depending on customer requirement. The unit does not incorporate any galvanic isolation, input to output. The battery string comprises 240 cells (480 volts nominal) arranged in a positive string of 120 cells and a negative string of 120 cells with the center of the series connected strings tied to system neutral, for the 80 kVA model. The 120 kVA model utilizes 144 cells on each side of the center connection (nominal 288 volts positive and negative, for 576 volts total). The battery is charged by positive and negative side chargers, which are powered from the output of the boost converter. 5.3.1 Input Rectifier The Input Rectifier is a full wave bridge uncontrolled rectifier, which produces unregulated DC of approximately +390 and –390 volts DC. A pre-charge system charges the DC bus prior to the input contactor being closed, to control inrush current to no higher than rated current levels. 5.3.2 Boost Converter A Boost Converter converts the raw DC input to a regulated DC link voltage of approximately +450 and –450 volts DC. It is operated in the current mode and is controlled using a variable modulation technique with a frequency in the range of 20 kHz. The neutral connection is maintained from the input to the output as a fixed connection. 5.3.3 Inverter and Filter The inverter is a traditional (current mode controlled) hard-switched IGBT 3-phase topology. The IGBTs are modulated by a variable frequency, current-mode control technique at approximately 20 kHz. An output filter filters out the high frequency switching components (line to neutral). 5.3.4 Batteries and Battery Charger The battery for the Powerware 80 kVA system is comprised of a positive string of 120 cells and a negative string of 120 cells, each made up of twenty 12-volt battery blocks. For the Powerware 120 kVA system, the battery strings are 144 cells positive and negative, respectively. The battery charger is divided into a positive side charger and a negative side charger, each powered from the respective positive and negative controlled DC bus voltages. The chargers operate automatically in the constant current

or constant voltage mode (temperature compensated, available as an option) based on battery condition. All batteries used in conjunction with the Powerware 9335 are external to the UPS cabinet. The internal charger charges the entire battery system, with a maximum current as indicated in Chapter 13, “Product Specifications”. Note that the higher the battery capacity, the longer the recharge time required to fully recharge the batteries. 5.3.5 Static Bypass The bypass has a continuous-duty SCR switch and a back-feed contactor (K4) in the Bypass circuit. In normal mode, the contactor connects the inverter to the output. A contactor (K2) provides isolation to the inverter when the system is on bypass. 5.3.6 Maintenance Bypass A user accessible shrouded 4-wire Mechanical Maintenance Bypass switch is provided internal to the cabinet.
5-12 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

6.1 General
The UPS system should function automatically and require very little attention during normal operation. The controls and indicators identified in this section are used during startup to monitor normal operation and during abnormal events.
Figure 6–1 identifies and shows the location of the controls and indicators on the Powerware 9335 (80 kVA and 120 kVA) UPS. The descriptions provide a brief overview of the UPS controls, and standard and optional features.
operation before attempting to operate any of the UPS controls or optional components.

Rear side of User control panel (mounted on UPS cabinet door)
Parallel Isolator Switch (IA2) (used only for inverter output isolation) Customer Power Connections
Figure 6–1. Powerware 9335 (80 kVA and 120 kVA) Controls and Indicators

The UPS has many standard features that provide cost effective and consistently reliable power protection. 6.2.1 Control Panel
The Control Panel on the front of the UPS, pictured in Fig. 6–2, contains a LCD screen to display the current status of the UPS system. You can view a statistical history and log of system events and display a real-time representation of power flow through the system components. LED status indicators show the operating mode of the UPS and alert you to system events. Panel push buttons provide navigation through the information and control screens. The load ON/OFF pushbuttons are located at the right of the control panel. Both must be pressed simultaneously to activate the LOAD ON/OFF function. Below the LCD screen are the user control pushbuttons, RESET, UP, DOWN, and ENTER, which provide access to the control and measurement functions of the UPS. The control panel is described in detail in chapter 7, “Using the Control Panel”.
System ON/OFF LCD Display

Display and Operation Push Buttons System Status LEDs
Figure 6–2. Powerware 9335 (80 kVA and 120 kVA) Control Panel
6.2.2 System and Load ON/OFF Two load ON/OFF pushbuttons are located on the right side of the LCD display. Activating both pushbuttons simultaneously will effect immediate system shutoff. This feature prevents accidental system shutdown if one of the pushbuttons is inadvertently depressed. System turn on is achieved in the same manner, by simultaneously depressing both buttons. Operation of the system ON/OFF pushbuttons is described in detail in Chapter 7, “Using the Control Panel” and Chapter 8, “UPS Operating Instructions.”
6-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

An internal Maintenance Bypass Switch is provided to completely isolate the main power processing of the UPS during service. The Maintenance Bypass Switch is described in detail in Chapter 8, “UPS Operating Instructions.”
6.2.4 Cold Start Capability The 9335 UPS system cannot be powered up without a utility input initially present. Accordingly, it is not able to power a load if the system is not started first on utility power. 6.3 UPS Standard Features 6.3.1 Customer Interface
Computer Interface One serial communications port, using the standard Powerware XCP interface, is provided via a plug-in interface card inserted in the communications slot on the front of the unit. This interface is supplied as standard with each Powerware 9335. You can use this port to link the UPS to the features described in Chapter 10, “Communications” and Chapter 11, “Options.”
A two-stage charging system ensures that the initial recharge is done in an optimal time, with current limited, constant current, DC applied to the batteries. When terminal voltage reaches a certain level, the charger switches to constant voltage.
Power wiring can be routed through the rear and bottom of the UPS cabinet with connections made to easily accessible terminal blocks at the bottom front of the cabinet. External monitoring and communication control wiring must be installed in accordance with approved wiring methods. Communication wiring can be routed through the top of each cabinet. Communication option cards are quickly installed in the slot behind the front door panel. X-slot cards are hot pluggable.

6.4 Options and Accessories Contact your sales representative for information about any of these available options:
6.4.1 Remote EMERGENCY POWER OFF A REMOTE EMERGENCY POWER OFF pushbutton is an option to provide for situations where you must instantaneously control the UPS output. The operation of the REMOTE EMERGENCY POWER OFF pushbutton is described in detail in Chapter 8, “UPS Operating Instructions.” 6.4.2 Battery Cabinets A complete UPS system requires one or more battery cabinets to provide the necessary DC backup power. Battery cabinets are designed to match with the UPS cabinet, although they do not directly bolt together. 6.4.3 Communications
See Chapter 10, “Communications”.
6.4.4 Other Options Refer to Chapter 11 of this manual to review other options available for the Powerware 9335 and their use.
6-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

6.5 Safety Considerations The UPS enclosure is designed for industrial or computer room applications and contains safety shields. However, the system is sophisticated and should be handled with appropriate care, following these guidelines.
If service or routine maintenance is required: • Ensure all power is disconnected before performing installation or service.

6.6 Symbols, Controls, and Indicators These symbols may appear on your UPS system or on labels inside the UPS. Most international safety agents accept them. Everyone in your organization who works with your system should understand the meaning of these symbols:
PROTECTIVE GROUNDING TERMINAL A terminal which must be connected to earth ground prior to making any other connection to the equipment.
A terminal to which or from which a direct current or voltage may be applied or supplied.
This symbol indicates the word “phase”.
ON The principal power switch is in the “ON” position.
OFF The principal power switch is in the “OFF” position.
6-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

7.1 Description
This chapter describes the UPS Control Panel, including controls and indicators, and how to monitor UPS operation. The control panel is located on the front of the UPS (see Figure 7–1).

BYPASS
BATTERY
LINE 1 INV
Figure 7–1. UPS Control Panel The Control Panel contains:
Refer to Chapter 8, “UPS Operating Instructions” for use of the operational controls.

7.2 Using the Control Panel The Control Panel provides an operator interface with the UPS system. Figure 7–2 identifies the display and pushbutton areas discussed in the following sections as well as LED indicators that provide a visual display of system operating status.
Figure 7–2. LCD Screen and Pushbuttons
ON/OFF
LINE 2
BYPASS
BATTERY
ALARM
ON/OFF
LINE 1
INV
RESET ENTER
7.2.1 Power Management Display
The 2 x 20 character LCD Screen simplifies the communication with the UPS and provides the necessary monitoring information about the UPS. The menu driven LCD Screen enables access to the
The LED indicators display the general status of the UPS. Indicators show the power flow status and in the event of power failure or load transfer from inverter to bypass or vise-versa, the corresponding LED indicators will change color from green (normal) to red (warning). The LINE 1 and LINE 2 LEDs indicate the availability of the input power supply. The INVERTER and BYPASS LEDs, if green, indicate which of the two power paths is supplying power to the critical load. When the battery is supplying the load, due to supply failure, the BATTERY LED will be flashing. The ALARM LED is a visual indication of any internal or external alarm conditions. At the same time, an audible alarm will be activated.
7-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

ALARM OFF RED + BUZZER RED
No alarm condition Alarm condition Alarm condition persists LINE 1 GREEN RED
Utility supply to rectifier available Utility supply to rectifier not available LINE 2 GREEN RED
Bypass supply available Bypass supply not available or not OK BYPASS GREEN OFF
Load on bypass (Bypass or Eco-mode) Bypass not operating (or switched off) INV GREEN RED OFF
Load on inverter Inverter fault or load not transferable to inverter Inverter not operating (switched off) BATTERY GREEN RED Flashing GREEN Flashing GREEN
Battery OK Battery fault or battery is discharged Battery discharging or battery fuse open Load OFF command issued 7.2.3 Pushbutton Functions The pushbuttons allow the user to operate the UPS to perform settings and adjustments, to start-up and shutdown the UPS, and to monitor on the LCD display the voltages, currents, frequencies and other variables of system operation.
Turn-on UPS system (press both pushbuttons simultaneously)
or Shutdown the UPS (press both pushbuttons simultaneously) UP ( ) Move upwards through the menu DOWN ( ) Move downwards through the menu RESET Move to the top of the menu. Cancel the audible alarm. If the alarm condition was only transient, the LED indicator (ALARM) will also extinguish, otherwise it will remain on (RED) ENTER Confirms a chosen menu item 7.2.4 ON/OFF Startup and Shutdown Pushbuttons
By pressing simultaneously both ON/OFF pushbuttons on the Control Panel, the UPS can be switched on (if currently OFF) or shutdown immediately (if currently ON). Requiring both to be simultaneously depressed prevents accidental operation of the UPS. The two main ON/OFF pushbuttons are also used as a security ON/OFF switch, making it possible to quickly disconnect the load from the UPS in emergency situations. Upon startup from initial install or power off disconnect, the UPS starts in NORMAL (inverter) mode. In subsequent startups, the system will return to the mode previously used before shutdown, except that ECO mode will require operator intervention to activate.

If, for security or emergency reasons, it is necessary to immediately disconnect the load from the UPS, press the two red ON/OFF pushbuttons simultaneously. In this case, make sure that the maintenance bypass switch (IA1) is in the “O” position (Normal=Off). 7.3 Description of the LCD Screen 7.3.1 Status Screens DESCRIPTION LCD DISPLAY Load is protected by UPS power. It is supplied by the inverter (normal operation) Load is not protected by UPS power. It is supplied by utility power. (load on bypass) Load supply is completely interrupted. UPS has been switched off by “ON/OFF” buttons NOTE: On the right hand side of the LCD display there should be a character “S”
PROTECTED
LOAD S
NOT PROTECTED
LOAD OFF S
SUPPLY FAILURE
indicating the Single Module is operational.
7-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

7.3.2 LCD Display Structure and Navigation The menu structure is shown in Figure 7–3, below. Navigation through the menu is accomplished by using the “ENTER” pushbutton to go to the menu level, or to activate an action, then using the “UP” or “DOWN” arrows to select a specific function within each menu category. The “RESET” pushbutton will immediately return to the highest screen.
LOAD PROTECTED
EVENT LOG
OUTPUT FREQUENCY (HZ) 60.00
02-27-02 HH-MM-SS LOAD TO BYP.
BYPASS FREQUENCY (HZ) 60.00
02-27-02 HH-MM-SS LOAD OFF
BATTERY VOLTAGE (V) + 240 -240
LOAD OFF SUPPLY FAIL
BATT. CHARGE CUR. (A) + 0.0 -0.0
MEASUREMENTS
PRESS ENTER
DISCHARGE CURRENT (A) 0
LOAD TO INVERTER
RECTIFIER VOLTAGE (V) 000 000 000
LOAD TO BYPASS PERFORM BATT.TEST
COMMANDS
BYPASS VOLTAGE (V) 000 000 000
OUTPUT VOLTAGE (V) 000 000 000
OUTPUT CURRENT (A) 00 00 00
ACTIVE POWER (kW) 00 00 00
REACTIVE POWER (KVAR) 00 00 00
UPS DATA
DATE OF MANUFACTURE
APPARENT POWER ((KVA) 00 00 00
SET-UP USER
DATE TIME
OUTPUT POWER (%) 00.0 00.0 00.0
BATT. CAPACITY (%) 00
Figure 7–3. LCD Screen Navigation Chart

7.3.3 Main Menu Screen DESCRIPTION LCD DISPLAY • Logging Control. A log of the last 64 events is
stored in the Power Management Display. • Menu Measurements allow monitoring voltages,
power, frequencies, current, battery run time, and other information. • Command Menu enables performance of
“Load to Inverter”, “Load to Bypass”, and battery test functions. • UPS Data Menu shows UPS serial number,
date of manufacture, current time & date. • Set-Up Menu allows user to set Date/Time,
automatic battery test and gen-set mode • Set-Up Menu for service allows trained.
service personnel to troubleshoot and adjust system parameters. 7.3.4 Event Log Screen DESCRIPTION LCD DISPLAY • Logging Control (sample screen)
02-27-02 17-03-30 LOAD TO INV.
02-27-02 17-03-30 LOAD TO BYP.
and presented under the Event Log. • All events and alarms are displayed
with their date and time of occurrence. 7.3.5 Measurements Screen DESCRIPTION LCD DISPLAY • Battery Runtime remaining (in minutes)
7-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

+ 0.0 - 0.0
+ 0.0 - 0.0
ACTIVE POWER (kW) 0 0 0
REACTIVE POWER (kVAR) 0 0 0
+240 -240

DATE OF MANUFACTURE DD-MM-YY
EPROM VERSION V-000
7.3.8 Set-Up User DESCRIPTION LCD DISPLAY
SET-UP DATE/TIME
SET-UP BATT. TEST
DAY OF MONTH
HOUR OF DAY
REPETITIVE (Y/N)
SET-UP GEN-SET OPER.
7-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

PASSWORD
run time in the SET-UP Service menu, it is also possible to set and check the following parameters:

The ON-LINE Mode is the UPS Operating Mode in which the load is supplied through the RECTIFIER and INVERTER. LED indicators are illuminated when shown shaded:
LED’s green when shown shaded
BATTERY LINE 1 INV.
Using the control panel (see Figure 7–2) the UPS can easily be transferred to the ON- LINE mode. The ON-LINE mode provides the highest degree of protection, especially in the event of a supply disturbance or failure. This operating mode is always recommended if the critical loads (computer systems) will not tolerate any interruption of the supply, even for a very short time. In the unlikely event of an inverter fault or overload condition, the UPS will transfer the load automatically and without interruption to the static bypass-utility supply.
7.4.2 “OFF LINE” Mode (BYPASS or ECONOMY MODE) In the OFF-LINE mode, the load is supplied from the utility supply through the bypass. Using the control panel (see Figure 7–2), the UPS may be easily transferred to “Bypass Mode”. LED’s green when shown shaded When the UPS is operating in “Bypass Mode”, the efficiency of the system is higher. In the event of a utility supply failure the load will automatically be transferred from utility to
BATTERY LINE 1 INV.
7-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

inverter within 5 milliseconds. When utility power returns, the UPS will startup in NORMAL (inverter) mode. Operator intervention is required to reset to ECO mode. The battery charger remains active in the “Bypass-Mode”. The “Bypass-Mode” is recommended only if the loads can tolerate power interruptions of up to 5 ms, the transfer time from Bypass Mode to ON-LINE Mode.
7.4.3 “MAINTENANCE BYPASS” Mode The Maintenance Bypass Mode is performed by means of the IA1 BYPASS SWITCH on the front of the UPS. When the switch is in the “O” (OFF) position, the Bypass Switch is OPEN. This is the normal operating condition, where the load is supplied by the inverter, or via the static bypass. When the switch is in the “I” (ON) position, the Bypass Switch is CLOSED, causing load power to be supplied directly from the utility source.
LED’s green when shown shaded, unless noted
BATTERY (Red) LINE 1 INV.

7.4.4 Parallel Isolator (IA2) The UPS unit is provided with an output isolator switch (IA2) which, when opened, isolates the corresponding unit from the LOAD. Once IA2 is open, there is no power coming from the inverter. This switch should always be in the “I” (ON) position, except for servicing the UPS when in the maintenance bypass mode. Rotating this switch to the “O” (OFF) position while the inverter is supplying power to the load will dump the critical load. This switch is also provided for future expansion requirements.
7-12 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

8.1 Operation The following procedures provide instruction for operating the UPS system. Refer to Chapters 6 and 7 of this manual for a description of the UPS controls and monitor panel functions. NOTE: Before starting the UPS, ensure all installation tasks are complete and
authorized service personnel have performed a preliminary startup. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the UPS operates properly. 8.2 Start-Up Procedure for the UPS

To start the UPS system for normal operation, perform the following procedure: 1. Ensure the UPS switches and external customer circuit breakers are set as follows:

UPS Utility Supply Breaker (customer supplied) “O” (OPEN) UPS Bypass Input Breaker (dual source, customer supplied) “O” (OPEN) UPS Battery Cabinet Breaker (customer supplied) “O” (OPEN) UPS Maintenance Bypass Switch (IA1) “O” (OFF) UPS Parallel Isolator Switch (IA2) “O” (OFF) Verify Position of DIP Switches SW 2–9 are as in Fig. 6-1. As shown

LED Indicator Color LINE 1 Green LINE 2 Green BYPASS Green INVERTER OFF BATTERY Flashing Green 6. If necessary, perform Command: LOAD TO INVERTER (see sections 7.3.2 and 7.3.6) On LCD Display, “LOAD PROTECTED” will appear and the LED-indicators will display as follows:



8-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The Powerware 9335 may be shut down completely if the load does not need input power for an extended period of time. The UPS system may be switched to Maintenance Bypass Mode for service or maintenance purposes, or transferred to the ECO-Mode if the load does not need the highest degree of protection and efficiency is to be maximized. The load may be disconnected by means of the two ON/OFF (LOAD-OFF) pushbuttons for security or operational reasons. 1. Verify that the loads are shut down and that there is no need for power supply to the load.

LED Indicator Color LINE 1 Green LINE 2 OFF BYPASS OFF INVERTER OFF BATTERY Flashing Green 3. Rotate the Parallel Isolator Switch (IA2) to the “O” (OFF) position. 4. Open battery cabinet breakers in external battery cabinets or racks.
THE POWERWARE 9335 IS NOW VOLTAGE FREE.
If it is necessary to perform service or maintenance on the UPS, it is possible to transfer the UPS to MAINTENANCE BYPASS.
Status of the UPS-System before starting the Transfer Procedure to Maintenance Bypass
The load is protected by the Powerware 9335 UPS system in normal operation (the UPS is operating on inverter). 1) Load transfer to Maintenance Bypass • Go to Menu COMMANDS and choose command “LOAD TO BYPASS” and transfer the load to utility supply on control panel of the UPS cabinet. On the LCD Display: “LOAD NOT PROTECTED” will appear.
8-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

LED Indicator Color LINE 1 Green LINE 2 Green BYPASS Green INVERTER Red BATTERY Green 2) Simultaneously press both ON/OFF pushbuttons on the UPS cabinet control panel. • On the LCD Display: “LOAD OFF, SUPPLY FAILURE” will appear and the LED indicators will indicate as shown below:
LED Indicator Color LINE 1 Green LINE 2 OFF BYPASS OFF INVERTER OFF BATTERY Flashing Green 3) Rotate the Parallel Isolator Switch IA2 to “O” (OFF). 4) Open battery breakers in the external battery cabinet or racks THE LOAD IS NOW SUPPLIED BY THE UTILITY MAINS AND IS NOT PROTECTED.

This page left intentionally blank.
8-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

In the event of an alarm condition, the red LED-Indicator “Alarm” and the audible alarm will turn on.
In this case proceed as follows:
A. Silence the audible alarm by pressing the "Reset" button. B. Identify the cause of the alarm condition by means of the
EVENT LOG in the MAIN menu. C. In case of alarm conditions, please contact the Global
Service Center. D. Fault identification and suggested corrective action is given
on the following pages.
In Chapter 4 there is a detailed description of the Menu, Commands, Event Log and Measurements that can be operated and displayed on the LCD. The List of Alarms and Messages are shown in Section 9.3.

The major alarm conditions that will be encountered are shown in the following table:
UPS FAULT There is a fault in the UPS and therefore normal operation cannot be guaranteed.
Call the authorized service center for assistance
MAINS FAILURE The utility power supply is outside its prescribed tolerance.
The input power to UPS is too low or missing. If site power appears to be OK, check the input circuit breakers etc. supplying the UPS
There is a short circuit at the output of UPS. (on load side)
Check all output connections and repair as required.
OVERLOAD Load exceeds the UPS rated power.
Identify which piece of equipment is causing the overload and remove it from the UPS.
OVERTEMPERATURE UPS temperature has exceeded the allowed value.
Check that the ambient temperature of the UPS is less than 30° C. If the ambient temperature is normal call the authorized service center for assistance.
The attached battery and the battery charger set-up do not correspond or battery charger fault.
Call the authorized service center for assistance.
INVERTER FAULT Inverter is faulty. Call the authorized service center for assistance.
NON-SYNCH The inverter and utility power are not synchronized.
The frequency of the input voltage to the UPS is outside operational limits and the UPS static bypass has been temporarily disabled.
BATTERY LOW The battery is nearly discharged.
Shutdown load connected to UPS before the UPS switches itself off to protect its batteries MANUAL SWITCH OFF Maintenance Bypass closed. Load supplied by utility power.
This alarm is only displayed if the UPS is on Maintenance Bypass
9-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

This section describes the several types of X–Slot cards, which can be used with the Powerware 9335. X-Slot cards allow the UPS to communicate to a variety of environments and with different types of devices. The Powerware 9335 is compatible with any X–Slot card, including, but not limited to:

X–Slot location for insertion of X–Slot Cards
SW2-9
SW1-1
X2 X3 X4
JD2
JD1
IA1 IA2
Figure 10–1. X–Slot Location on Front of Powerware 9335 UPS Cabinet
To establish communications between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable. When the communication cable is installed, power management software installed on your computer can exchange data with the UPS. Powerware supplies monitoring software with each UPS. See instructions packaged with the software for installation and operation. The software polls the UPS for detailed information on the status of the
10-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation
Control Panel

power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the connected critical load. The cable pins are identified in Figure 10–2 and the pin functions are described in Table 10–1.
Figure 10–2. The Communication Port on the Single Port Serial Card Pin Number Function Input or Output 1 Low Battery Open Collector signal – pulls to common when the UPS reaches low battery level
2 RS-232 Transmit Data Output 3 RS-232 Receive Data Input 4 Plug and Play sense Input 5 Signal Common (tied to chassis) – 6 Tied internally to pin 4 Output 7 No Connection – 8 AC Fail Open Collector signal – pulls to common during a power failure
9 DC Supply Voltage (+8 to 24 volts DC power) Output
Table 10–1. Communication Port Pin Assignments
Output · Output

This page left intentionally blank.
10-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The generator ON facility must use a normally open contact that closes to indicate that a generator is running and supplying input power to the UPS. When used, this facility disables the UPS static bypass and prevents the UPS from transferring the load into the generator power supply. The user may also elect prevention of battery charging while on generator input. Both or either of these features may be selected via the control panel. (See section 7.3.8, Set Up)

Figure 11–1. Generator ON Connection

This page left intentionally blank
11-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, and very little disassembly. This design allows authorized service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly. Regular routine checks of operation and system parameters will enable your system to function efficiently for many trouble-free years.
Remember that your UPS system is designed to supply power EVEN WHEN DISONNECTED FROM THE UTILITY POWER. The UPS cabinet interiors are unsafe until the DC power source is disconnected and all capacitors are discharged. After disconnecting the utility power and the DC power, authorized service personnel should wait at least 5 minutes for capacitor bleed off before attempting internal access to the UPS cabinet. Since each battery string is an energy source in itself, opening the Battery Circuit Breaker does not de-energize the voltage within the battery string. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, you should contact your local field service office.

The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verity that the units are operating normally and that the batteries are in good condition. Perform the following checks DAILY: 1. Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the unit. 2. Ensure the air intakes (vents on the bottom) and exhaust opening (on the top of the cabinet) are not blocked. 3. Ensure the operating environment is within the parameters specified in Chapter 13, “Product Specifications.” 4. Ensure the UPS is in Normal mode. (Proper LED indicators are illuminated and the LCD display shows “LOAD PROTECTED”). If the alarm LED is illuminated or the Normal status LEDs are not illuminated, contact Customer Service. Perform the following check MONTHLY: 1. Review the Event Log for any operational issues that need attention. ANNUAL maintenance: Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact your nearest field service office for more information about service offerings.
12-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

13.1 System Information The UPS systems are housed in freestanding cabinets with safety shields behind the front panels. The UPS systems are available in 50 or 60 Hz configurations with either 80 or 120 kVA output ratings. The following sections detail the input output, environmental and battery specifications for each model. 13.2 UPS System Input Operating Input Voltage (Nominal +15 / -20%)

480 VAC for operation from 384 VAC to 552 VAC (50/60 Hz)
Operating Input Frequency Range 45 – 65 Hz (continuous duty)
80 kVA Model 158 amperes 120 kVA Model 225 amperes Input Current Harmonic Content Less than 9% input THD at full load
Power Factor Minimum 0.98 Battery Voltage 80 kVA model ±240 volts nominal 120 kVA model ±288 volts nominal (center point connected to neutral) Maximum Battery Current 315 amperes (120 kVA): 252 amperes (80 kVA)

13.3 UPS System Output DC Ripple less than 1% voltage ripple UPS Output Capacity 100% rated current at 0.8 power factor Output Voltage Regulation ±1.5% (10–100% load)

Output Voltage Balance Each phase may be loaded to 100% independently with
voltage regulation within stated tolerance. Output Voltage Phase Displacement 120 degrees between phases ±0.01 degree
Output Transients < ±4% for 0 to 100% or 100% to 0% load change Frequency Regulation ±0.1% free running Synchronous to Bypass No-break transfer Frequency Slew Rate 1 Hz per second maximum Overload Capacity 101% to 125% for 10 minutes (25C) 126% to 150% for 30 seconds Maximum Output Capability 200% RMS for 10 cycles without bypass
13.4 Environmental Specifications Dimensions (W x H x D) mm (in.) 700 (27.6) x 1800 (70.9) x 750 (29.6) Weight Kg (lb.) 80 kVA Model 333 (733) Weight Kg (lb.) 120 kVA Model 340 (748) Operating temperature 0 to 40˚C (32 to 104˚F) Operating Altitude 1500 meters (5000 feet) with no derating Storage Temperature 0 to 50˚C (32 to 122˚F) Relative Humidity Maximum 95%, non-condensing Audible Noise with 100%/75% Load 65/63 dBA (80 kVA) 70/65 dBA (120 kVA) EMI Suppression IEC 62040-3 & FCC A Electrostatic Discharge (ESD) Immunity IEC 801-2

13-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

The information in this appendix will help you plan for and install your UPS system. This appendix contains the following: Table A Input/Output Ratings and external wiring 9335 – 80 Table B Input/Output Ratings and external wiring 9335 – 120 Table C UPS Power Cable Terminations 9335 – 80 & –120 Table D Power Cable Conduit Requirements 9335 – 80 & –120 Table E Maximum Input Circuit Breaker Ratings Table F Maximum Output Circuit Breaker Ratings Table G Customer Interface Inputs and Outputs Table H Customer interface to JD2 Table I Customer connections to JD1 Table J Equipment Weight Table K System Clearances Table L Air Conditioning or Ventilation Requirements Figure A–1 Front View of Powerware 9335 showing customer connections Figure A–2 Label of Powerware 9335 Figure A–3 One-line diagram of Powerware 9335 Figure A–4 Power terminal connections for Powerware 9335 Figure A–5, –6 UPS System Information Figure A–7, –8 UPS Cabinet Dimensions
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-1 164201396 REV A 07/11/2003

Powerware 9335 – 80 kVA
Ratings Units Rating 50/60 Hz kVA
80 Basic unit ratings at 0.8 lagging PF load INPUT/ OUTPUT
W
VOLTAGE
Amps* 105 AC INPUT
AC Input to UPS Rectifier (0.95 min. PF) 3 phase, 1 neutral, 1 ground Minimum conductor size *Max. amps include full load current plus battery recharge current
AWG or kcmil (ea) 1/0
Amps* 97 AC INPUT
AC Input to UPS Bypass - Full Load Current 3 phase, 1 neutral, 1 ground
Minimum conductor size AWG or kcmil (ea) 1/0
DC Input from Ext. Battery source to UPS (1) positive, (1) negative, (1) mid-point
Minimum conductor size AWG or kcmil (ea) 4/0
97 AC OUTPUT Minimum conductor size AWG or kcmil (ea) 1/0
AC Output to Critical Load - Full Load Current 3 phase, 1 neutral, 1 ground
Read and understand the following notes while planning your installation: 1. Refer to national and local electrical codes for acceptable external wiring practices. 2. Material and labor for external wiring requirements are to be provided by designated personnel.
A-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation
VDC (nominal) · Amps* · Amps*

Powerware 9335 – 120 kVA
Ratings Units Rating 50/60 Hz kVA
120 96 Basic unit ratings at 0.8 lagging PF load INPUT/OUTPUT
VOLTAGE 480
Amps* 150 AC INPUT
AC Input to UPS Rectifier (0.95 min.PF) 3 phase, 1 neutral, 1 ground Minimum conductor size *Max. amps include full load current plus battery recharge current
AWG or kcmil (ea)
Amps* 144 AC INPUT
AC Input to UPS Bypass - Full Load Current 3 phase, 1 neutral, 1 ground
Minimum conductor size (number/phase) AWG or kcmil (ea) 4/0
DC Input from Ext. Battery source to UPS (1) positive, (1) negative, (1) mid-point
Minimum conductor size (number/pole) AWG or kcmil (ea) 4/0
Amps* 144 AC OUTPUT Minimum conductor size (number/phase) AWG or kcmil (ea) 4/0
AC Output to Critical Load - Full Load Current 3 phase, 1 neutral, 1 ground
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-3 164201396 REV A 07/11/2003
kW · VDC (nominal) · Amps*

Terminal Function Size of Pressure Termination
Int.Hex Size (in.) A Phase A 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 B Phase B 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 C Phase C 1 - #6-250 kcmils Cooper 42.4 (375) 3/8
Vendor Tightening Torque N-M (lb-in.)
AC Input to UPS Rectifier
N Neutral 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 A Phase A 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 B Phase B 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 C Phase C 1 - #6-250 kcmils Cooper 42.4 (375) 3/8
AC Input to Bypass (Dual Input) N Neutral 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 A Phase A 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 B Phase B 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 C Phase C 1 - #6-250 kcmils Cooper 42.4 (375) 3/8
AC Output to Critical Load
N Neutral 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 + Battery(+) 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 N Mid-point 1 - #6-250 kcmils Cooper 42.4 (375) 3/8 DC Input from Battery to UPS
- Battery (-) 1 - #6-250 kcmils Cooper 42.4 (375) 3/8
8. Per NEC article 300-20 (a), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors. 9. Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one protective ground wire of the same size. 10. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, and THW-2. Table D. Power Cable Conduit Requirements Powerware 9335 (80 kVA & 120 kVA) Powerware Product Model

No. of Conduits Rectifier Input (A,B,C,N,G) 5 2.0 inches 1 Bypass Input (A,B,C,N,G) 5 2.0 inches 1 Ext. Battery Source (+,N,-,G) 4 2.5 inches 1
Output (A,B,C,N,G) 5 2.0 inches 1 Rectifier Input (A,B,C,N,G) 5 2.5 inches 1 Bypass Input (A,B,C,N,G) 5 2.5 inches 1 Ext. Battery Source (+,N,-,G) 4 2.5 inches 1
A-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation
Customer Ground · Protective Ground · Protective Ground

Input Voltage Rating Powerware Model
480 VAC DC 9335 – 80 kVA 150 225 9335 – 120 kVA 225 300
Rated Output voltage Powerware Model 480 VAC 9335 – 80 kVA 150 9335 – 120 kVA 225
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-5 164201396 REV A 07/11/2003

Table G. Customer Interface Inputs and Outputs Terminal Name Description X1 Emergency Power Off X1 – 1 and X1 – 2 (no polarity) X2 Generator On X2 – 1 and X2 – 2 (no polarity) X3 Battery temperature sensor X3 – 1 and X3 – 2 (no polarity) X4 Battery Shunt trip breaker control X4 – 1 and X4 – 2 (+12V & com) JD-1-1 Not Used Not Used JD-1-2 TXD Input to UPS JD-1-3 RXD Output from UPS JD-1-4 Not Used Not Used JD-1-5 Return Common JD-1-6 Not Used Not Used JD-1-7 Not Used Not Used JD-1-8 Not Used Not Used JD-1-9 Not Used Not Used JD-2-1 Utility Fail Alarm (NO) Utility Fail Alarm JD-2-2 Utility OK Utility Present JD-2-3 Common Common JD-2-4 Load on Inverter message (NO) Load on inverter message JD-2-5 Load on inverter message (NC) Load not on inverter message JD-2-6 Common Common JD-2-7 Battery Low Alarm (NO) Battery voltage low alarm JD-2-8 Battery OK Battery voltage OK JD-2-9 Common Common JD-2-10 Load on utility (bypass mode) Load on utility/bypass JD-2-11 Load on utility/bypass (NC) Load not on utility/bypass JD-2-12 Common Common JD-2-13 Common Alarm (NO) Common alarm JD-2-14 No alarm condition No alarm JD-2-15 Common Common JD-2-16 Not used Not used JD-2-17 Not used Not used JD-2-18 Not used Not used JD-2-19 Not used Not used JD-2-20 Not used Not used JD-2-21 Not used Not used JD-2-22 Ground Ground JD-2-23 +12 volts +12 volts (Imax. = 100 ma.) JD-2-24 Not used Not used JD-2-25 Not used Not used
A-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation


Contacts are rated at 60 volts maximum DC or 30 volts RMS AC, and 500 mA. maximum current and should be supplied by a LVLE source in compliance with UL 1778
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-7 164201396 REV A 07/11/2003

Table I. Definition of pins on JD1 and interface cable connections to 9 or 25 pin connectors.
JD1 connector at UPS DB-9 connector to computer
JD1 connector at UPS DB-25 connector to computer
A-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Weight Kg (lbs.) Powerware Model Shipping Installed Point Loading 9335 – 80 kVA 360 (792) 333 (733) 4 at 83 (183) 9335 – 120 kVA 367 (807) 340 (748) 4 at 85 (187) 5. The clearances required around the UPS system are shown in Table K. Table K. System Clearances From Front of Cabinet 36 inches working space From Back of Cabinet 30 inches working space From Right or Left side of Cabinet ~0 inches clearance 6. The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: 0 – 40˚C. (32 – 104˚F.) Recommended Operating Range: 20 – 25˚C. (68 – 77˚F.) Maximum Relative Humidity: 95% (non-condensing) The UPS ventilation requirements for heat removal are shown in Table L.
During Full Load Operation Powerware 9335 80kVA and 120 kVA Powerware Model Input/Output Voltage Heat Rejection BTU/hr x 1000/hr (g-cal/hr)
9335 – 80 kVA 480/480 linear load pf = 0.8 14.0 (3.5) 9335 – 120 kVA 480/480 linear load pf = 0.8 20.8 (5.2) 9335 – 80 kVA 480/480 linear load pf = 1.0 16.4 (4.2) 9335 – 120 kVA 480/480 linear load pf = 1.0 24.6 (3.1) 9335 – 80 kVA 480/480 100% non-linear load 17.7 (4.4) 9335 – 120 kVA 480/480 100% non-linear load 26.6 (6.6)
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-9 164201396 REV A 07/11/2003


IA1 Maintenance Bypass IA2 Parallel Isolator JD1 Smart Port- RS232 (SUB-D9P/F) JD2 Dry Port-volt-free relays (SUB-D25/F) JD8 Parallel Port SW1-1 Single/Parallel Switch SW2-9 System Configuration Switches X1 Emergency Power OFF (EPO) X2 Generator ON X3 Battery Temperature X4 Battery Breaker control
2 ON 3 ON 4 ON 5 ON 6 ON 7 ON 8 ON 9 ON
2N - N + 3N 1A 1B 3C 3B 3A 2C 2B 2A 1N 1C
Output (To Load) Utility Input

Powerware 9335 80 kVA and 120 kVA Front View showing customer connections
A-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation


1A 1B 1C 1N 2A 2B 2C 2N 3A 3B 3C 3N + N --
USE 75°C COPPER CONDUCTORS ONLY Refer to the installation manual for tightening torque specification
USE 75°C COPPER CONDUCTORS ONLY Refer to the installation manual for tightening torque specification 0
1A 1B 1C 1N 2A 2B 2C 2N 3A 3B 3C 3N + N --
Figure A–2. Powerware 9335 80 kVA and 120 kVA Label
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-11 164201396 REV A 07/11/2003

A
B
K4
F1
IA2
D
Figure A–3. Powerware 9335 Oneline Drawing

Figure A–4. Power Terminals on Powerware 9335
2A, 2B, 2C, 2N BYPASS INPUT
+BATT, N, - BATT 3A, 3B, 3C, 3N OUTPUT TO LOAD
Figure A–4. Power Terminals on Powerware 9335
A-12 Powerware 9335 (80 kVA and 12
0 kVA) Installation and Operation 164201396 REV A 07/11/2003


1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
NW6004 Bypass Control J1 NW6009 Relay Control & Customer Interface
9 TXD-232 9 10 RXD-232 10 11 Modem 11
37 37 T1_Par_L1 39 39 T2_Par_L1 41 41 T1_Par_L2 43 43 T2_Par_L2 45 45 T1_Par_L3 47 47 T2_Par_L3
3 3 Byp_Serv_Cntrl 4 4 5 5 Q2_Status 6 6 8 8 Byp_Serv_Cntrl 7 7 10 10 RXD_Par 9 9 11 11 M_S_Bus 12 12 14 14 T1_Bus_Par_L1 13 13 16 16 T2_Bus_Par_L1 15 15 18 18 T1_Bus_Par_L2 17 17 20 20 T2_Bus_Par_L2 19 19 22 22 T1_Bus_Par_L3 21 21 24 24 T2_Bus_Par_L3 23 23 26 26 Connector_Error 25 25 27 27 Inv_Fail_Bus 28 28 29 29 Frq_Temp_Batt 30 30
Figure A-5. System Information
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-13 164201396 REV A 07/11/2003

G
F
E
D
B
A
S06-0001ULA
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
y Parallel transmission circuit, communication between UPSs
y CN21 K1 driver output (power mains input contactor)
Signature :
Signature :
y CN22 K4 driver output (static bypass contactor)
y CN24 Maintenance bypass switch (IA1) status
y CN6 Neutral input mains current (TA4)
y CN11 customer interface supply (safety)
y CN20 K2 driver output (output contactor)
y X1 Emergency off (normally closed)
Sheet :5 of : 5
Powerware 9335 80 and 120 kVA
y J4 aux customer interface signal bus
y CN23 Output contactor (K2) status
y CN10 Parallel port power supply
y CN26 Output switch (IA2) status
y X2 Battery temperature input
y CN9 Start up power supply
y X4 Battery breaker control
Drawn by :RMo 28/10/02
y Free voltage contacts (safety)
y Power supply startup rectifier
y X3 Generator On input
y JD2 Voltage free contacts
y J7 parallel interface bus
y Aux. customer interface
y DC link charger circuit
y JD5 Parallel Port
Date:
Date:
y CN19 Mains input
Connectors:
Checked by :
Replace :
Functions:
y J3 Static Bypass thyristor control command, static
y Manages multi-UPS communication in parallel
y Converts Newave communication protocol to
Powerware XCP and Powerware XCP to
y J9 Connects NW6027 to socket for XCP
y Bypass and load voltage measurement
format interface card, designed by
y CN41 Connects NW6027 to NW6009
y Static Bypass current measurement
bypass and load current and voltage
y Static Bypass IGBT driver circuit
Connectors:
Connectors:
Functions:
Functions:
y J1 Booster and Battery control and regulation bus
y CN1,3 battery charger IGBT driver signal
y J5 Display and customer interface bus input
y J51 Display and customer interface bus output
y CN2,4,5 Inverter current sensor input
y CN12,13 + Booster IGBT driver signal
y CN14,15 - Booster IGBT driver signal
y CN17..20 Inverter L1 IGBT driver signal
y CN22..25 Inverter L2 IGBT driver signal
y CN27..30 Inverter L3 IGBT driver signal
y CN21,26 Battery thyristor driver signal
y Display interface board (galvanic insulation)
y J2 Inverter control and regulation bus
y CN10 Udc supply voltage output
y CN7,8,11 Temperature sensor input
y CN12 Customer interface supply (safety)
y Battery charger current measurement
y Battery IGBT charger driver circuit
y CN6,16 Booster shunt input
y Inverter current measurement
y CN9 Electronic supply
y Inverter IGBT driver circuit
y Booster IGBT driver circuit
Connectors:
Connectors:
Functions:
Functions:
y J4 aux customer interface and parallel control signal bus
y J1 Booster and Battery control and regulation bus
y CN10 Power supply for parallel data transmission
y CN11,12 Customer and parallel interface supply
y J3 Static Bypass thyristor control command
y J7 parallel control signal galvanic isolation
y CN16,17,18 Inverter voltage measurement
y J5 Display and customer interface bus
y J2 Inverter control and regulation bus
y J5 Display and customer interface bus
y CN9 Start up power supply 550Vdc
y CN5 12Vdc electronic supply
y Battery charger rating control
y Battery charger regulation
y CN8 DC supply input
y Electronic power supply
y Inverter rating control
y Booster rating control
y CN39 Fan regulation
Connectors:
Connectors:
Functions:
Functions:
G
F
E
D
B
A
Figure A-6. System Information
A-14 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

700 mm. (27.6 inches)

1800 mm. (70.9 inches)
Removable Conduit Landing Plate
Figure A–7. UPS Cabinet Dimensions (Rear View)
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-15 164201396 REV A 07/11/2003

750 mm. (29.6 inches) 700 mm. (27.6 inches)

1800 mm. (70.9
Figure A–8. UPS Cabinet Dimensions
A-16 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation









LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE PRODUCTS Subject to the conditions herein, Invensys Powerware (Powerware ®) warrants solely, to the original end-user, the electronics (the “Unit”), and Powerware built battery cabinets, against defects in material and workmanship for the warranty period of 12 months, from the date of equipment start up, or 18 months from date of shipment, whichever occurs first. Should service be necessary, this warranty covers:
warranty (described below), start up, and extended labor service. All three-phase UPS installations will have an authorized Invensys Powerware Service Engineer or Agent perform startup or the factory warranty and extended labor service will be void. The included first year extended labor service provides for a complete 12 months of onsite labor for your UPS purchase. Worldwide: All parts requiring replacement for the Factory Warranty period. If, in the opinion of Invensys Powerware, the Unit fails to meet published specifications and the defect is within the terms of this warranty, the Unit will be repaired or replaced at the option of Invensys Powerware with no charge for replacement parts. Labor required, to make upgrades, repairs or replacement installation, is not included under the terms of this Limited Warranty, except for labor and travel costs required during the first 90 days of this warranty (USA only), provided that startup of the unit onsite, has been performed by Invensys Powerware or its agent. Equipment sold, but not manufactured by Invensys Powerware, and only the manufacturer of such equipment shall warrant this equipment and is not included as part of this warranty agreement. Equipment repaired or replaced pursuant to this warranty will be warranted for the remaining portion of the original warranty subject to all the terms thereof. This warranty is not valid unless an authorized Invensys Powerware Service Engineer or Agent performs startup and commissioning. This warranty does not apply to any Unit that has been subject to neglect, accident, abuse, misuse, misapplication, incorrect installation, or that has been subject to repair or alteration, not authorized in writing by Invensys Powerware personnel or performed by an authorized Invensys Powerware Service Engineer or Agent. Purchaser shall be invoiced for, and shall pay for, all services not expressly provided for by the terms hereof, including, without limitation, site calls involving an inspection that determines no corrective maintenance is required. THIS WARRANTY IS THE PURCHASER’S (USER’S) SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NOT OTHER, EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED). In no case will Invensys Powerware’s liability under this Warranty exceed the replacement value of the Unit warranted. Invensys Powerware’s obligation, under said warranty, is expressly conditioned upon receipt by Invensys Powerware of all payments due it (including interest charges, if any). During such time as Invensys Powerware has not received payment of any amount due it, in accordance with the Contract terms under which the equipment is sold, Invensys Powerware shall have no obligation, under said warranty; also during this time, the period of said warranty shall continue to run and the expiration of said warranty shall not be extended upon payment of the overdue amount. These limitations, to said warranty, apply even in the event that the equipment is sold initially by Invensys Powerware for resale to an ultimate end-user. In no event shall Invensys Powerware be liable for any indirect, incidental special or consequential damages of any kind or type whatsoever, or based on any claim or cause of action, however denominated. Invensys Powerware shall not be responsible for failure to provide service or parts due to causes beyond Invensys Powerware’s reasonable control. This limited warranty applies only to the original end user of the unit. This factory warranty will not be in effect if the End-User does not properly store the equipment, including the “trickle charge” of batteries no later than the date indicated on the packaging, before installation and does not cover shipping damages if FOB Factory. Cost for replacement equipment, installation, material freight charges travel expenses and labor of Invensys Powerware representatives will be borne by the Purchaser (user). Any advice furnished the Purchaser before or after delivery in regard to use or application of Powerware equipment is furnished without charge and on the basis that it represents Invensys Powerware’s best judgment under the circumstances. The use of any such advice by the Purchaser is solely and entirely at its own risk. Any other agreements, such as Service contracts or Sales Concessions are not means to annul this Factory Warranty. For comment or questions, about this Limited Factory Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, NC 27601, or call (919) 872---3020
Powerware 9335 (80 kVA-120 kVA) Installation and Operation W-1 164201396 REV. A 071103

This page left intentionally blank
W-2 Powerware 9335 (80 kVA – 120 kVA) Installation and Operation