UPSp.18–15 kVAp.1USER’S GUIDEp.1Class A EMC Statements FCC Part 15p.2ICES-003p.2IEC 62040-2p.2VCCI Noticep.2Requesting a Declaration of Conformityp.3Special Symbolsp.4Table of Contentsp.5Chapter 1 Introductionp.7Figure 1. The Powerware 9155 UPS and EBM (2-High Cabinets Shown)p.7 Maintenance Bypass Module (MBM)p.9 Power Distribution Module (PDM)p.9 Wall-Mounted Bypass Switchp.9 Parallel Tie Cabinetp.9 Input Isolation Transformerp.9 Seismic Kitp.9Chapter 2 Safety Warningsp.11IMPORTANT SAFETY INSTRUCTIONSp.11SAVE THESE INSTRUCTIONSp.11D A N G E Rp.11W A R N I N Gp.11Chapter 3 UPS Setupp.15Inspecting the Equipmentp.15Floor Loadingp.16Clearancesp.16Unloading the Cabinet(s)p.17Figure 2. Removing the Stabilizing Bracket Boltsp.17Figure 3. Removing the Brackets and Shipping Padp.18Figure 4. Unloading the Cabinetp.19Selecting an Installation Optionp.20Chapter 4 UPS Only Installationp.21Table 1. Circuit Breaker Ratingsp.22Figure 5. UPS Rear Viewp.23Table 2. UPS Terminal Block Wiringp.24L2 TB1-5 3 AWGp.24TB1p.24Figure 6. UPS Terminal Blockp.24Figure 7. UPS Only Wiring Diagramp.25Chapter 5 Input Isolation Transformer Installationp.27Table 3. Circuit Breaker Ratingsp.28Figure 8. UPS with Input Isolation Transformer Rear Viewp.29Figure 9. Input Isolation Transformer Hardwiringp.30Table 4. Input Isolation Transformer Terminal Block Wiringp.31Table 5. UPS Terminal Block Wiringp.31Figure 10. UPS Terminal Blockp.32Figure 11. UPS with Input Isolation Transformer Wiring Diagramp.33Figure 12. UPS with Input Isolation Transformer and MBM/PDM Wiring Diagramp.34Chapter 6 UPS-Mounted Bypass Switch Installationp.35Maintenance Bypass/Power Distribution Module Setupp.35Figure 13. UPS Rear View (2-High Cabinet Shown)p.35Figure 14. Attaching the L-Bracketsp.36Figure 15. Installing the MBM or PDM (MBM Shown)p.37Figure 16. Attaching the L-Bracketsp.38Wiring the MBM/PDMp.38Table 6. Circuit Breaker Ratingsp.39Figure 17. UPS with MBM Rear Viewp.40Figure 18. MBM/PDM Hardwiring (PDM Shown)p.41Table 7. MBM/PDM Terminal Block Wiringp.41L2 TB10-4 3 AWGp.41Figure 19. Wiring from Maintenance Bypass Switch to UPSp.42Figure 20. UPS with MBM Wiring Diagramp.43Figure 21. UPS with PDM Wiring Diagramp.44Chapter 7 Wall-Mounted Bypass Switch Installationp.45Figure 22. Wall-Mounted Bypass Switch Dimensionsp.45Wall-Mounted Bypass Switch Setupp.46Figure 23. Wall-Mounted Bypass Switch Knockoutsp.46Wiring the Wall-Mounted Bypass Switchp.47Table 8. Circuit Breaker Ratingsp.48Figure 24. UPS Rear Viewp.49Figure 25. Wall-Mounted Bypass Switch Terminal Strip Wiringp.50Table 9. UPS Terminal Block Wiringp.51
Page 1 of the Powerware 9155 user manual — 8–15 kVA
Page 1 · click to enlarge
Page 1
Powerware 9155 — UPS diagram (page 1)
Fig. 1

UPS

8–15 kVA

USER’S GUIDE

www.powerware.com

Page 2 of the Powerware 9155 user manual — VCCI Notice
Page 2 · click to enlarge
Page 2

Class A EMC Statements FCC Part 15

NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

ICES-003

This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.

Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.

IEC 62040-2

Some configurations are classified under IEC 62040-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:

VCCI Notice

Powerware 9155 — VCCI Notice diagram (page 2)
Fig. 2 · VCCI Notice

Powerware, ABM, and FERRUPS are registered trademarks and X-Slot, ConnectUPS, and Powerware Hot Sync are trademarks of Eaton Power Quality Corporation. Greenlee is a registered trademark of Greenlee Textron. Modbus is a registered trademark of Modicon.

ECopyright 2004–2005 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.

Page 3 of the Powerware 9155 user manual — Requesting a Declaration of Conformity
Page 3 · click to enlarge
Page 3

Requesting a Declaration of Conformity

Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:

Harmonized StandardsIEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition

EU Directives:

73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC

The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:

Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68

Page 4 of the Powerware 9155 user manual — Special Symbols
Page 4 · click to enlarge
Page 4

Special Symbols

The following are examples of symbols used on the UPS to alert you to important information:

RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.

This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.

This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.

Page 5 of the Powerware 9155 user manual — Table of Contents
Page 5 · Contents
Contents

Contents

UPSp.18–15 kVAp.1USER’S GUIDEp.1Class A EMC Statements FCC Part 15p.2ICES-003p.2IEC 62040-2p.2VCCI Noticep.2Requesting a Declaration of Conformityp.3Special Symbolsp.4Table of Contentsp.5Chapter 1 Introductionp.7Figure 1. The Powerware 9155 UPS and EBM (2-High Cabinets Shown)p.7 Maintenance Bypass Module (MBM)p.9 Power Distribution Module (PDM)p.9 Wall-Mounted Bypass Switchp.9 Parallel Tie Cabinetp.9 Input Isolation Transformerp.9 Seismic Kitp.9Chapter 2 Safety Warningsp.11IMPORTANT SAFETY INSTRUCTIONSp.11SAVE THESE INSTRUCTIONSp.11D A N G E Rp.11W A R N I N Gp.11Chapter 3 UPS Setupp.15Inspecting the Equipmentp.15Floor Loadingp.16Clearancesp.16Unloading the Cabinet(s)p.17Figure 2. Removing the Stabilizing Bracket Boltsp.17Figure 3. Removing the Brackets and Shipping Padp.18Figure 4. Unloading the Cabinetp.19Selecting an Installation Optionp.20Chapter 4 UPS Only Installationp.21Table 1. Circuit Breaker Ratingsp.22Figure 5. UPS Rear Viewp.23Table 2. UPS Terminal Block Wiringp.24L2 TB1-5 3 AWGp.24TB1p.24Figure 6. UPS Terminal Blockp.24Figure 7. UPS Only Wiring Diagramp.25Chapter 5 Input Isolation Transformer Installationp.27Table 3. Circuit Breaker Ratingsp.28Figure 8. UPS with Input Isolation Transformer Rear Viewp.29Figure 9. Input Isolation Transformer Hardwiringp.30Table 4. Input Isolation Transformer Terminal Block Wiringp.31Table 5. UPS Terminal Block Wiringp.31Figure 10. UPS Terminal Blockp.32Figure 11. UPS with Input Isolation Transformer Wiring Diagramp.33Figure 12. UPS with Input Isolation Transformer and MBM/PDM Wiring Diagramp.34Chapter 6 UPS-Mounted Bypass Switch Installationp.35Maintenance Bypass/Power Distribution Module Setupp.35Figure 13. UPS Rear View (2-High Cabinet Shown)p.35Figure 14. Attaching the L-Bracketsp.36Figure 15. Installing the MBM or PDM (MBM Shown)p.37Figure 16. Attaching the L-Bracketsp.38Wiring the MBM/PDMp.38Table 6. Circuit Breaker Ratingsp.39Figure 17. UPS with MBM Rear Viewp.40Figure 18. MBM/PDM Hardwiring (PDM Shown)p.41Table 7. MBM/PDM Terminal Block Wiringp.41L2 TB10-4 3 AWGp.41Figure 19. Wiring from Maintenance Bypass Switch to UPSp.42Figure 20. UPS with MBM Wiring Diagramp.43Figure 21. UPS with PDM Wiring Diagramp.44Chapter 7 Wall-Mounted Bypass Switch Installationp.45Figure 22. Wall-Mounted Bypass Switch Dimensionsp.45Wall-Mounted Bypass Switch Setupp.46Figure 23. Wall-Mounted Bypass Switch Knockoutsp.46Wiring the Wall-Mounted Bypass Switchp.47Table 8. Circuit Breaker Ratingsp.48Figure 24. UPS Rear Viewp.49Figure 25. Wall-Mounted Bypass Switch Terminal Strip Wiringp.50Table 9. UPS Terminal Block Wiringp.51
Page 7 of the Powerware 9155 user manual — Figure 1. The Powerware 9155 UPS and EBM (2-High Cabinets Shown)
Page 7 · click to enlarge
Page 7

Chapter 1 Introduction

The Powerware® 9155 is a double-conversion, split-phase, online uninterruptible power system (UPS) for protecting computer systems and other intelligent devices. It is ideal for protecting essential information technology and electrical engineering infrastructure in corporate, telecom, health care, banking, and industrial applications.

The UPS provides a steady, well-regulated power supply for your computing and communications equipment, while protecting it from the frequent irregularities that are inherent in commercially available power. Voltage spikes, power surges, brownouts, and power failures have the potential to corrupt critical data, destroy unsaved work sessions, and in some instances, damage expensive hardware.

With the Powerware 9155, you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment. Figure 1 shows the Powerware 9155 UPS and an optional Extended Battery Module (EBM).

Figure 1. The Powerware 9155 UPS and EBM (2-High Cabinets Shown)

1 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 8 of the Powerware 9155 user manual — Chapter 1 Introduction
Page 8 · click to enlarge
Page 8

Providing outstanding performance and reliability, the Powerware 9155’s unique benefits including the following:

Online UPS design with pure sine wave output. The UPS filters and

regulates incoming AC power and provides consistent power to your equipment without draining the battery.

More wattage in less space with a 0.9 power factor – protecting more

equipment and leaving more room for expansion.

Support for Powerware Hot Synct paralleling of multiple modules for

redundancy or extra capacity.

Input current total harmonic distortion (THD) of less than five

percent, using active input power factor correction.

ABM® technology that uses advanced battery management to increase

battery service life, optimize recharge time, and provide a warning before the end of useful battery life.

Up to four hours of extended runtime with added EBMs.

Advanced power management with the Powerware Software Suite CD

for graceful shutdowns and power monitoring.

Emergency shutdown control through the Remote Emergency

Power-off (REPO) port.

Start-on-battery capability for powering up the UPS even if utility

power is not available.

Standard communication options with a DB-9 serial port, relay output

contacts, and programmable signal inputs.

Optional X-Slott cards enhance communication capabilities for

increased power protection and control.

Backed by worldwide agency approvals.

2 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Introduction

Page 9 of the Powerware 9155 user manual —  Seismic Kit
Page 9 · click to enlarge
Page 9

The following options for the Powerware 9155 are available:

Maintenance Bypass Module (MBM)

The optional MBM is installed on the UPS rear panel and is used to bypass the UPS during maintenance or servicing. The Maintenance Bypass switch on the MBM provides a Make-Before-Break (MBB) wrap-around bypass for UPS service without shutting down the load.

Power Distribution Module (PDM)

The optional PDM provides the same functionality as the MBM and also comes equipped with several different types of output receptacles.

Wall-Mounted Bypass Switch

The optional wall-mounted bypass switch is used to bypass the UPS during maintenance or servicing, providing wrap-around bypass for UPS service without shutting down the load.

Parallel Tie Cabinet

A parallel system with up to three UPSs can be installed to provide a parallel capacity and/or redundant system. This load sharing system provides more capacity than a single UPS and can provide backup, depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load. A parallel Powerware Hot Sync Computer Area Network (CAN) Bridge Card provides connectivity for system metering and operational mode control. The parallel system consists of two to three UPSs, each with a parallel CAN Bridge Card, and a parallel tie cabinet. Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User’s Guide for more information.

Input Isolation Transformer

The optional input isolation transformer is located at the bottom of a 3-high UPS model. The input isolation transformer provides a neutral from a 208V or 240V input source with 240V output and can be wired to the UPS or to an MBM/PDM.

Seismic Kit

The seismic kit secures the UPS and optional EBMs for Zone 4 seismic installations.

3 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Introduction

Page 10 of the Powerware 9155 user manual —  Maintenance Bypass Module (MBM)
Page 10 · click to enlarge
Page 10

4 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Introduction

Page 11 of the Powerware 9155 user manual — W A R N I N G
Page 11 · click to enlarge
Page 11

Chapter 2 Safety Warnings

The only user operations permitted are:

Starting up and shutting down the UPS

Operating the user interface

Connecting data interface cables

Monitoring the UPS with power management software

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.

D A N G E R

This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.

W A R N I N G

This UPS contains its own energy source (batteries). The UPS output may carry live voltage even when the UPS is not connected to an AC supply.

To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).

To reduce the risk of fire, connect only to a circuit provided with 100 amperes maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.

Output overcurrent protection and disconnect switch must be provided by others.

5 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 15 of the Powerware 9155 user manual — Inspecting the Equipment
Page 15 · click to enlarge
Page 15

Chapter 3 UPS Setup

This chapter describes:

Unloading the cabinet(s)

Selecting an installation option

The instructions are intended for the chief operator/system supervisor, electrical consultants, and installation electricians. Local regulations and electrical code must be followed during the UPS installation.

Inspecting the Equipment

If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.

To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.

9 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Equipment inspection · Floor loading

Page 16 of the Powerware 9155 user manual — Clearances
Page 16 · click to enlarge
Page 16

Floor Loading

When planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate weights are shown in the following table.

Standard Model Floor Loadings (2-High/3-High Cabinets)

Powerware 9155 Maximum Weight (lb)

Distributed Loading (lb/ft2)

2-High UPS 352 88 166

3-High UPS 590 148 278

3-High UPS with Isolation Transformer

2-High EBM 480 120 226

3-High EBM 710 178 335

Clearances

The following clearances are recommended for the Powerware 9155 UPS:

From Front of Cabinet 36” (91.4 cm) working space

From Back of Cabinet 6” (15.2 cm) without MBM/PDM installed; with MBM/PDM installed, clearance determined by customer-supplied mating plug

10 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 4 more labels / short text on this page
UPS Setup · Point Loading · (lb/in2) · 558 140 263
Page 17 of the Powerware 9155 user manual — Figure 2. Removing the Stabilizing Bracket Bolts
Page 17 · click to enlarge
Page 17

Unloading the Cabinet(s)

The following tools are required for unloading the cabinet(s):

15 mm wrench or socket

7 mm nutdriver or socket

C A U T I O N

The UPS and EBM are heavy (see page 10). Unloading the cabinets requires at least two people to safely remove the cabinets from the pallet.

To remove the UPS or EBM from the shipping pallet:

1. Remove the two M10 bolts securing the stabilizing bracket to the pallet (see Figure 2).
Powerware 9155 — C A U T I O N diagram (page 17)
Fig. 3

Figure 2. Removing the Stabilizing Bracket Bolts

11 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Setup

Page 18 of the Powerware 9155 user manual — Figure 3. Removing the Brackets and Shipping Pad
Page 18 · click to enlarge
Page 18
2. Remove the four M4 screws securing the stabilizing bracket to the cabinet rear panel and remove the bracket (see Figure 3). Retain the hardware for later use.
Powerware 9155 — Figure 3. Removing the Brackets and Shipping Pad diagram (page 18)
Fig. 4 · Figure 3. Removing the Brackets and Shipping Pad
3. Remove the three M10 bolts securing the rear shipping pad to the pallet and remove the shipping pad (see Figure 3).
4. Remove the two M10 bolts securing the front shipping bracket and remove the bracket (see Figure 3).
Powerware 9155 — Figure 3. Removing the Brackets and Shipping Pad diagram (page 18)
Fig. 5 · Figure 3. Removing the Brackets and Shipping Pad

Figure 3. Removing the Brackets and Shipping Pad

12 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 4 more labels / short text on this page
UPS Setup · M10 Bolts · M10 Bolts · M4 Screws
Page 19 of the Powerware 9155 user manual — Figure 4. Unloading the Cabinet
Page 19 · click to enlarge
Page 19
5. Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue rolling the cabinet down the pallet until the cabinet is clear of the pallet (see Figure 4).

If needed, adjust the leveling feet so that the cabinet will roll.

6. Roll the cabinet to the desired location.
Powerware 9155 — Figure 4. Unloading the Cabinet diagram (page 19)
Fig. 6 · Figure 4. Unloading the Cabinet

Figure 4. Unloading the Cabinet

13 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Setup

Page 20 of the Powerware 9155 user manual — Selecting an Installation Option
Page 20 · click to enlarge
Page 20

Selecting an Installation Option

You are now ready to install the Powerware 9155 UPS. Select one of the following installation options according to your UPS configuration:

UPS Configuration Installation Chapter

UPS only Chapter 4, “UPS Only Installation” on page 15

UPS with an optional input isolation transformer

Chapter 5, “Input Isolation Transformer Installation” on page 21

UPS with an optional UPS-mounted bypass switch

Chapter 6, “UPS-Mounted Bypass Switch Installation” on page 29

UPS with an optional wall-mounted bypass switch

Chapter 7, “Wall-Mounted Bypass Switch Installation” on page 39

Parallel UPS configuration Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User’s Guide.

14 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Setup

Page 21 of the Powerware 9155 user manual — Chapter 4 UPS Only Installation
Page 21 · click to enlarge
Page 21

Chapter 4 UPS Only Installation

The Powerware 9155 has the following power connections:

2-phase (L1 and L2), neutral, and ground connection for

2-phase (L1 and L2), neutral, and ground connection for load output

The nominal input/output voltages are:

100/200, 110/220, or 120/240 Vac with 180° phase displacement

120/208 or 127/220 Vac with 120° phase displacement

Output overcurrent protection and disconnect switch must be provided by others.

Figure 7 on page 19 shows a oneline diagram of the UPS.

15 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

rectifier/bypass input

Page 22 of the Powerware 9155 user manual — Table 1. Circuit Breaker Ratings
Page 22 · click to enlarge
Page 22

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.

Use the following procedure to hardwire the UPS:

1. Verify that the electrical connections to the installation site have been properly installed.
2. A wall-mounted, user-supplied, readily-accessible disconnection device must be incorporated in the input wiring.

Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:

Table 1. Circuit Breaker Ratings

UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*

8 kVA 60A 4 AWG (21.2 mm2)

10 kVA 80A 3 AWG (26.7 mm2)

12 kVA 100A 2 AWG (33.6 mm2)

15 kVA 100A 2 AWG (33.6 mm2)

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

3. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.
4. Determine your equipment’s grounding requirements according to your local electrical code.
5. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 5).

16 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Only Installation

Page 23 of the Powerware 9155 user manual — Figure 5. UPS Rear View
Page 23 · click to enlarge
Page 23
Powerware 9155 — Figure 5. UPS Rear View diagram (page 23)
Fig. 7 · Figure 5. UPS Rear View

UPS Wiring Access Cover

Figure 5. UPS Rear View

6. Remove the UPS wiring access cover and retain (see Figure 5).
7. Hardwire the input (TB1-1 through TB1-5) and output (TB1-6 through TB1-9) terminations for the UPS.

See Table 2 for specifications and Figure 6 for a detailed view of the UPS terminal block.

17 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Only Installation · Battery Connector · Conduit Landing

Page 24 of the Powerware 9155 user manual — Figure 6. UPS Terminal Block
Page 24 · click to enlarge
Page 24

Table 2. UPS Terminal Block Wiring

Input Ground TB1-1 8 AWG p

L1 TB1-3 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

L2 TB1-5 3 AWG

Output L1 TB1-6 3 AWG p

Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

Ground TB1-9 8 AWG

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

TB1

1 2 3 4 5 6 7 8 9

Figure 6. UPS Terminal Block

8. Replace the UPS wiring access cover.
9. Continue to “Stabilizing the Cabinet” on page 49 to complete the UPS installation.

18 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 9 more labels / short text on this page
UPS Only Installation · Wire Function Terminal · Minimum Wire Size* · Tightening · Conduit Connection · Position · Torque · (Entry Size) · Input Output
Page 25 of the Powerware 9155 user manual — Figure 7. UPS Only Wiring Diagram
Page 25 · click to enlarge
Page 25

Figure 7. UPS Only Wiring Diagram

19 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Only Installation

Page 26 of the Powerware 9155 user manual — Figure 7. UPS Only Wiring Diagram
Page 26 · click to enlarge
Page 26

20 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Only Installation

Page 27 of the Powerware 9155 user manual — C A U T I O N
Page 27 · click to enlarge
Page 27

Chapter 5 Input Isolation Transformer Installation

The Powerware 9155 has the following power connections:

2-phase (L1 and L2), neutral, and ground connection for

2-phase (L1 and L2), neutral, and ground connection for load output

C A U T I O N

The input isolation transformer output is always 240V (180° phase angle).

If installing an MBM/PDM, the UPS MUST be set up for 240V output only; otherwise, the “Bypass Not Available” alarm annunciates. Any equipment connected to the output requiring 208V (120° phase angle) is at risk for damage when using the Maintenance Bypass switch.

The input isolation transformer cannot be used with a wall-mounted bypass switch.

Output overcurrent protection and disconnect switch must be provided by others.

Figure 11 and Figure 12 beginning on page 27 show the oneline diagrams of the input isolation transformer with the UPS.

21 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

rectifier/bypass input

Page 28 of the Powerware 9155 user manual — Table 3. Circuit Breaker Ratings
Page 28 · click to enlarge
Page 28

Input Isolation Transformer Installation

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.

Use the following procedure to hardwire the input isolation transformer and UPS. All hardware is supplied in the accessory kit.

1. Verify that the electrical connections to the installation site have been properly installed.
2. A wall-mounted, user-supplied, readily-accessible disconnection device must be incorporated in the input wiring.

Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:

Table 3. Circuit Breaker Ratings

UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*

8 kVA 60A 4 AWG (21.2 mm2)

10 kVA 80A 3 AWG (26.7 mm2)

12 kVA 100A 2 AWG (33.6 mm2)

15 kVA 100A 2 AWG (33.6 mm2)

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

3. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.
4. Determine your equipment’s grounding requirements according to your local electrical code.
5. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 8).

22 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 29 of the Powerware 9155 user manual — Figure 8. UPS with Input Isolation Transformer Rear View
Page 29 · click to enlarge
Page 29

Input Isolation Transformer Installation

6. Verify that the input circuit breaker is in the OFF position.
7. Remove the UPS wiring access cover and retain.
8. Remove the input isolation transformer wiring cover and retain.
Powerware 9155 — Figure 8. UPS with Input Isolation Transformer Rear View diagram (page 29)
Fig. 8 · Figure 8. UPS with Input Isolation Transformer Rear…

UPS Wiring Access Cover

Input Isolation Transformer Wiring Cover

Figure 8. UPS with Input Isolation Transformer Rear View

9. If you are also installing an optional Maintenance Bypass Module or Power Distribution Module, proceed to Step 15 on page 26; otherwise, continue to Step 10.
10. On the input isolation transformer, punch the two pilot holes in the conduit landing for the input and output conduit using a Greenlee ® punch or similar device (see Figure 9).
11. Hardwire the input, output, and ground terminations for the input isolation transformer.

See Table 4 for specifications and Figure 9 for a detailed view of the input isolation transformer terminal block.

23 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 30 of the Powerware 9155 user manual — Figure 9. Input Isolation Transformer Hardwiring
Page 30 · click to enlarge
Page 30

Input Isolation Transformer Installation

Powerware 9155 — Figure 9. Input Isolation Transformer Hardwiring diagram (page 30)
Fig. 9 · Figure 9. Input Isolation Transformer Hardwiring

Figure 9. Input Isolation Transformer Hardwiring

24 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 31 of the Powerware 9155 user manual — L2 TB1-5 3 AWG
Page 31 · click to enlarge
Page 31

Input Isolation Transformer Installation

Table 4. Input Isolation Transformer Terminal Block Wiring

Wire Function Terminal Position Minimum Wire Size* Tightening Torque

Input L1 TB1-1 2 AWG p

L2 (208V) TB1-2 2 AWG 25 lb in (2 83 Nm) L2 (240V) TB1-3 2 AWG (2.83 Nm)

Output L1 TB1-4 3 AWG p

L2 TB1-5 3 AWG 25 lb in (2 83 Nm) Neutral TB1-6 3 AWG (2.83 Nm)

Ground Output TB1-7 8 AWG 25 lb in Ground Input TB1-8 8 AWG 25 lb in (2.83 Nm)

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

12. Wire the output of the input isolation transformer terminal block to the UPS input terminal block (see Table 5 and Figure 10).

Table 5. UPS Terminal Block Wiring

Input Ground TB1-1 8 AWG p

L1 TB1-3 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

L2 TB1-5 3 AWG

Output L1 TB1-6 3 AWG p

Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

Ground TB1-9 8 AWG

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

25 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 7 more labels / short text on this page
Wire Function Terminal · Minimum Wire Size* · Tightening · Conduit Connection · Position · Torque · (Entry Size)
Page 32 of the Powerware 9155 user manual — Figure 10. UPS Terminal Block
Page 32 · click to enlarge
Page 32

Input Isolation Transformer Installation

TB1

1 2 3 4 5 6 7 8 9

Figure 10. UPS Terminal Block

13. Replace the UPS wiring access cover and the input isolation transformer wiring cover.
14. Continue to “Stabilizing the Cabinet” on page 49 to complete the UPS installation.
15. On the input isolation transformer, punch one pilot hole in the conduit landing for the input conduit using a Greenlee punch or similar device (see Figure 9 on page 24).
16. Install the supplied edge grommet in the top of the input isolation transformer wiring cover.
17. Hardwire the input (TB1-1 through TB1-3) terminations for the input isolation transformer.

See Table 4 for specifications and Figure 9 for a detailed view of the input isolation transformer terminal block.

18. Punch a hole in the bottom of the MBM/PDM using a Greenlee punch or similar device for wiring access.

Insert the supplied nylon bushing inside the wiring access hole.

19. Continue to the following chapter, “UPS-Mounted Bypass Switch Installation,” to complete the installation.

26 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Output

Page 33 of the Powerware 9155 user manual — Figure 11. UPS with Input Isolation Transformer Wiring Diagram
Page 33 · click to enlarge
Page 33

Input Isolation Transformer Installation

Figure 11. UPS with Input Isolation Transformer Wiring Diagram

27 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 34 of the Powerware 9155 user manual — Figure 12. UPS with Input Isolation Transformer and MBM/PDM Wiring Diagram
Page 34 · click to enlarge
Page 34

Input Isolation Transformer Installation

Powerware 9155 — Figure 12. UPS with Input Isolation Transformer and MBM/PDM Wiring Diagram diagram (page 34)
Fig. 10 · Figure 12. UPS with Input Isolation Transformer and…

Figure 12. UPS with Input Isolation Transformer and MBM/PDM Wiring Diagram

28 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 35 of the Powerware 9155 user manual — Figure 13. UPS Rear View (2-High Cabinet Shown)
Page 35 · click to enlarge
Page 35

Chapter 6 UPS-Mounted Bypass Switch Installation

This chapter describes the Maintenance Bypass Module and Power Distribution Module installation. Both modules have a Make-Before-Break Maintenance Bypass switch.

Maintenance Bypass/Power Distribution Module Setup

If you purchased an optional MBM/PDM, attach the module to the UPS before any wiring installation. All hardware is supplied in the accessory kit. Use the following procedure to attach the optional MBM/PDM to the UPS:

1. Remove the connecting plate between the top cabinet and the cabinet below it on the UPS rear panel (see Figure 13). Discard the plate. Retain the screws for later use.
2. Remove the lowest top cover screw on each side of the UPS and discard.
Powerware 9155 — Maintenance Bypass/Power Distribution Module Setup diagram (page 35)
Fig. 11 · Maintenance Bypass/Power Distribution Module Setup

Lowest Top Cover Screw (one each side)

Connecting Plate (8 screws)

Figure 13. UPS Rear View (2-High Cabinet Shown)

29 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 36 of the Powerware 9155 user manual — Figure 14. Attaching the L-Brackets
Page 36 · click to enlarge
Page 36

UPS-Mounted Bypass Switch Installation

3. Attach the supplied L-bracket to the lower rear (for 2-high) or middle rear (for 3-high) cabinet using three screws (see Figure 14).

Repeat for the other side.

4. Remove the UPS wiring access cover and retain.
Powerware 9155 — Figure 14. Attaching the L-Brackets diagram (page 36)
Fig. 12 · Figure 14. Attaching the L-Brackets

UPS Wiring Access Cover

Figure 14. Attaching the L-Brackets

30 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

L-Bracket and Screws

Page 37 of the Powerware 9155 user manual — Figure 15. Installing the MBM or PDM (MBM Shown)
Page 37 · click to enlarge
Page 37

UPS-Mounted Bypass Switch Installation

5. Insert the two supplied nylon bushings inside the wiring access holes on the UPS conduit landing plate (see Figure 15).
6. Remove the MBM/PDM wiring access cover and the conduit landing plate and retain.
7. Tilt the top of the module forward and slide the module onto the L-brackets. The top left flange on the module fits up under the UPS electronics unit through an access slot.
Powerware 9155 — Figure 15. Installing the MBM or PDM (MBM Shown) diagram (page 37)
Fig. 13 · Figure 15. Installing the MBM or PDM (MBM Shown)

Nylon Bushings in UPS Wiring Access Holes

MBM/PDM Wiring Access Cover and the Conduit Landing Plate (Removed)

Figure 15. Installing the MBM or PDM (MBM Shown)

31 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Electronics Unit

Page 38 of the Powerware 9155 user manual — Figure 16. Attaching the L-Brackets
Page 38 · click to enlarge
Page 38

UPS-Mounted Bypass Switch Installation

8. Secure the sides of the module to the L-brackets using six screws (see Figure 16).
9. Secure the top of the module to the top cabinet using four of the screws removed in Step 1.
10. Continue to the following section, “Wiring the MBM/PDM.”
Powerware 9155 — Figure 16. Attaching the L-Brackets diagram (page 38)
Fig. 14 · Figure 16. Attaching the L-Brackets

Screws for Top of Module

Figure 16. Attaching the L-Brackets

Wiring the MBM/PDM

The Powerware 9155 UPS has the following power connections:

2-phase (L1 and L2), neutral, and ground connection for

2-phase (L1 and L2), neutral, and ground connection for load output

The nominal input/output voltages are:

100/200, 110/220, or 120/240 Vac with 180° phase displacement

120/208 or 127/220 Vac with 120° phase displacement

32 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Screws to L-Bracket · rectifier/bypass input

Page 39 of the Powerware 9155 user manual — Table 6. Circuit Breaker Ratings
Page 39 · click to enlarge
Page 39

UPS-Mounted Bypass Switch Installation

Output overcurrent protection and disconnect switch must be provided by others.

Figure 20 and Figure 21 beginning on page 37 show the oneline diagrams of the MBM and PDM with the UPS.

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.

Use the following procedure to hardwire the MBM/PDM:

1. Verify that the electrical connections to the installation site have been properly installed.
2. A wall-mounted, user-supplied, readily-accessible disconnection device must be incorporated in the input wiring.

Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:

Table 6. Circuit Breaker Ratings

UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*

8 kVA 60A 4 AWG (21.2 mm2)

10 kVA 80A 3 AWG (26.7 mm2)

12 kVA 100A 2 AWG (33.6 mm2)

15 kVA 100A 2 AWG (33.6 mm2)

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

3. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.

33 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 40 of the Powerware 9155 user manual — Figure 17. UPS with MBM Rear View
Page 40 · click to enlarge
Page 40

UPS-Mounted Bypass Switch Installation

4. Determine your equipment’s grounding requirements according to your local electrical code.
5. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 17).
Powerware 9155 — Figure 17. UPS with MBM Rear View diagram (page 40)
Fig. 15 · Figure 17. UPS with MBM Rear View

Figure 17. UPS with MBM Rear View

6. Punch two holes in the MBM/PDM conduit landing plate for the input and output conduit using a Greenlee punch or similar device.
7. Hardwire the input (TB10-1 through TB10-4) and output (TB10-5 through TB10-8) terminations for the MBM/PDM.

See Table 7 for specifications and Figure 18 for a detailed view of the MBM/PDM terminal block.

34 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 41 of the Powerware 9155 user manual — L2 TB10-4 3 AWG
Page 41 · click to enlarge
Page 41

UPS-Mounted Bypass Switch Installation

Powerware 9155 — Figure 18. MBM/PDM Hardwiring (PDM Shown) diagram (page 41)
Fig. 16 · Figure 18. MBM/PDM Hardwiring (PDM Shown)

Figure 18. MBM/PDM Hardwiring (PDM Shown)

Table 7. MBM/PDM Terminal Block Wiring

Input Ground TB10-1 8 AWG p

L1 TB10-2 3 AWG 25 lb in 2” access hole for Neutral TB10-3 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

L2 TB10-4 3 AWG

Output L1 TB10-5 3 AWG p

Neutral TB10-6 3 AWG 25 lb in 2” access hole for L2 TB10-7 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

Ground TB10-8 8 AWG

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

35 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 7 more labels / short text on this page
Wire Function Terminal · Minimum Wire Size* · Tightening · Conduit Connection · Position · Torque · (Entry Size)
Page 42 of the Powerware 9155 user manual — Figure 19. Wiring from Maintenance Bypass Switch to UPS
Page 42 · click to enlarge
Page 42

UPS-Mounted Bypass Switch Installation

8. Connect the factory-installed wiring from the Maintenance Bypass switch to the UPS terminal block (see Figure 19).

Connect the maintenance bypass (red and black) wires to TB1-2 (the A/B maintenance bypass auxiliary contacts) on the UPS terminal block.

TB1

1 2 3 4 5 6 7 8 9

A/B Maintenance Bypass Auxiliary Contacts

Figure 19. Wiring from Maintenance Bypass Switch to UPS

9. Replace the wiring access cover on the UPS and the optional isolation transformer, if applicable.
10. Replace the MBM/PDM wiring access cover and conduit landing plate.
11. Continue to “Stabilizing the Cabinet” on page 49 to complete the installation.

36 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Output

Page 43 of the Powerware 9155 user manual — Figure 20. UPS with MBM Wiring Diagram
Page 43 · click to enlarge
Page 43

UPS-Mounted Bypass Switch Installation

Figure 20. UPS with MBM Wiring Diagram

37 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 44 of the Powerware 9155 user manual — Figure 21. UPS with PDM Wiring Diagram
Page 44 · click to enlarge
Page 44

UPS-Mounted Bypass Switch Installation

Figure 21. UPS with PDM Wiring Diagram

38 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 45 of the Powerware 9155 user manual — Figure 22. Wall-Mounted Bypass Switch Dimensions
Page 45 · click to enlarge
Page 45

Chapter 7 Wall-Mounted Bypass Switch Installation

This chapter describes the wall-mounted bypass switch installation with the UPS. The wall-mounted bypass switch is a Make-Before-Break Maintenance Bypass switch.

Figure 22 shows the wall-mounted bypass switch and dimensions.

Height (A) 21.0” (53.4 cm)

Width (B) 14.0” (35.6 cm)

Depth (C) 6.8” (17.2 cm)

(D) 11.0” (28.0 cm) g Centers (E) 20.0” (50.8 cm)

Weight 31 lb (14.1 kg)

Powerware 9155 — Chapter 7 Wall-Mounted Bypass Switch Installation diagram (page 45)
Fig. 17 · Chapter 7 Wall-Mounted Bypass Switch Installation

Figure 22. Wall-Mounted Bypass Switch Dimensions

39 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Dimension Measurement · Mounting C t

Page 46 of the Powerware 9155 user manual — Figure 23. Wall-Mounted Bypass Switch Knockouts
Page 46 · click to enlarge
Page 46

Wall-Mounted Bypass Switch Installation

Wall-Mounted Bypass Switch Setup

Use the following procedure to set up the wall-mounted bypass switch:

1. Remove the knockouts in the bottom or side of the bypass switch for AC Line Input, AC to UPS Input, AC from UPS Output, and AC to the UPS load (see Figure 23).

Figure 23. Wall-Mounted Bypass Switch Knockouts

2. Mount the bypass switch cabinet to a sturdy surface within sight of the UPS. You may need to rotate the cabinet 90 degrees to enable operator access to the switch handle.
3. Remove the six screws from the bypass switch front cover and remove the cover (see Figure 23).
4. Remove and discard any packing material from inside the bypass switch.

40 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 47 of the Powerware 9155 user manual — Wiring the Wall-Mounted Bypass Switch
Page 47 · click to enlarge
Page 47

Wall-Mounted Bypass Switch Installation

Wiring the Wall-Mounted Bypass Switch

The Powerware 9155 UPS has the following power connections:

2-phase (L1 and L2), neutral, and ground connection for

2-phase (L1 and L2), neutral, and ground connection for load output

The nominal input/output voltages are:

100/200, 110/220, or 120/240 Vac with 180° phase displacement

120/208 or 127/220 Vac with 120° phase displacement

Output overcurrent protection and disconnect switch must be provided by others.

Figure 28 on page 47 shows a oneline diagram of the UPS with a wall-mounted bypass switch.

41 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

rectifier/bypass input

Page 48 of the Powerware 9155 user manual — Table 8. Circuit Breaker Ratings
Page 48 · click to enlarge
Page 48

Wall-Mounted Bypass Switch Installation

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Risk of electrical shock.

Use the following procedure to hardwire the wall-mounted bypass switch:

1. Verify that the electrical connections to the installation site have been properly installed.
2. A wall-mounted, user-supplied, readily-accessible disconnection device must be incorporated in the input wiring.

Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:

Table 8. Circuit Breaker Ratings

UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*

8 kVA 60A 4 AWG (21.2 mm2)

10 kVA 80A 3 AWG (26.7 mm2)

12 kVA 100A 2 AWG (33.6 mm2)

15 kVA 100A 2 AWG (33.6 mm2)

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

3. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.
4. Determine your equipment’s grounding requirements according to your local electrical code.

42 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 49 of the Powerware 9155 user manual — Figure 24. UPS Rear View
Page 49 · click to enlarge
Page 49

Wall-Mounted Bypass Switch Installation

5. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 24).
6. Remove the UPS wiring access cover and retain (see Figure 24).
Powerware 9155 — Figure 24. UPS Rear View diagram (page 49)
Fig. 18 · Figure 24. UPS Rear View

UPS Wiring Access Cover

Figure 24. UPS Rear View

43 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Battery Connector · Conduit Landing

Page 50 of the Powerware 9155 user manual — Figure 25. Wall-Mounted Bypass Switch Terminal Strip Wiring
Page 50 · click to enlarge
Page 50

Wall-Mounted Bypass Switch Installation

7. Install the conduit to the bypass switch cabinet. AC input and AC output conductors must be run through separate conduit. UPS output circuits must be installed in a dedicated conduit system and not shared with other electrical circuits.
8. Hardwire the terminal strip inside the bypass switch cabinet. Use copper wire that is the appropriate size for the current draw.

See Figure 25 for a detailed view of the terminal strip label.

Powerware 9155 — Figure 25. Wall-Mounted Bypass Switch Terminal Strip Wiring diagram (page 50)
Fig. 19 · Figure 25. Wall-Mounted Bypass Switch Terminal Strip…

Figure 25. Wall-Mounted Bypass Switch Terminal Strip Wiring

44 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 51 of the Powerware 9155 user manual — Figure 26. UPS Terminal Block
Page 51 · click to enlarge
Page 51

Wall-Mounted Bypass Switch Installation

9. Connect the wiring from the bypass switch to the UPS terminal block.

See Table 9 for specifications and Figure 26 for a detailed view of the UPS terminal block.

Table 9. UPS Terminal Block Wiring

Input Ground TB1-1 8 AWG p

L1 TB1-3 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

L2 TB1-5 3 AWG

Output L1 TB1-6 3 AWG p

Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)

2 access hole for 1-1/2” conduit

Ground TB1-9 8 AWG

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

TB1

1 2 3 4 5 6 7 8 9

Figure 26. UPS Terminal Block

45 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 8 more labels / short text on this page
Wire Function Terminal · Minimum Wire Size* · Tightening · Conduit Connection · Position · Torque · (Entry Size) · Input Output
Page 52 of the Powerware 9155 user manual — Figure 27. Signal Cable Installation
Page 52 · click to enlarge
Page 52

Wall-Mounted Bypass Switch Installation

10. Route the gray signal cable through the grommet on the left side of the bypass switch cabinet (see Figure 27). Connect the white and black pair of wires to TB1-2 (the A/B maintenance bypass auxiliary contacts) on the UPS terminal block.

Secure each connection, tightening the terminal screws to a maximum 3.5 in lb (0.4 Nm). Provide strain relief for cables by installing plastic cable ties.

Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 52)
Fig. 20 · Table 9. UPS Terminal Block Wiring

Figure 27. Signal Cable Installation

11. Replace the bypass switch front cover and the UPS wiring access cover.

46 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Signal Cable

Page 53 of the Powerware 9155 user manual — Figure 28. UPS with Wall-Mounted Bypass Switch Wiring Diagram
Page 53 · click to enlarge
Page 53

Wall-Mounted Bypass Switch Installation

Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 53)
Fig. 21 · Table 9. UPS Terminal Block Wiring

Figure 28. UPS with Wall-Mounted Bypass Switch Wiring Diagram

47 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 54 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 54 · click to enlarge
Page 54

Wall-Mounted Bypass Switch Installation

48 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 55 of the Powerware 9155 user manual — Figure 29. Lowering the Leveling Feet
Page 55 · click to enlarge
Page 55

Chapter 8 Stabilizing the Cabinet

1. Lower the leveling feet to prevent the cabinet from rolling.

Figure 29. Lowering the Leveling Feet

2. Attach the stabilizing bracket to the bottom of the cabinet rear panel using the retained hardware from the shipping pallet (see Figure 30).

Use the holes and slots in the bottom of the bracket to attach the cabinet to the flooring if desired.

49 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 56 of the Powerware 9155 user manual — Figure 30. Installing the Stabilizing Bracket
Page 56 · click to enlarge
Page 56
Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 56)
Fig. 22 · Table 9. UPS Terminal Block Wiring

Figure 30. Installing the Stabilizing Bracket

3. Continue to one of the following sections:

“Extended Battery Module Installation” on page 51 to install

optional EBMs.

“Communication” on page 53 to install UPS communication

options, such as X-Slot cards or Remote Emergency Power-off.

“Operation” on page 65 to start up the UPS.

50 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Stabilizing the Cabinet · M4 Screws

Page 57 of the Powerware 9155 user manual — Chapter 9 Extended Battery Module Installation
Page 57 · click to enlarge
Page 57

Chapter 9 Extended Battery Module Installation

If you are installing an optional EBM(s), use the following steps:

1. For cabinets using a stabilizing bracket: Position the EBM at least 8 ” (20.3 cm) away from the adjacent cabinet to allow space for the stabilizing bracket.
2. Verify that all battery circuit breakers are in the OFF position (see Figure 31).
3. Install the supplied ground strap (both ends attached to the EBM rear panel) between the UPS and the EBM:

Disconnect the end of the ground strap farthest from the adjacent cabinet and retain the screw. Remove the screw from the adjacent cabinet’s connecting plate. Attach the loose end of the ground strap to the adjacent cabinet.

4. If additional EBMs are installed, attach another ground strap between the first and second EBM. Repeat for each additional EBM.
5. Reinstall the remaining screw in the open hole where the ground strap was attached to the last EBM.
6. Plug the EBM cable into the UPS battery connector.

51 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 58 of the Powerware 9155 user manual — Figure 31. Typical EBM Installation (2-High Cabinets Shown)
Page 58 · click to enlarge
Page 58

Extended Battery Module Installation

7. If additional EBMs are installed, plug the EBM cable of the second cabinet into the battery connector on the first EBM. Repeat for each additional EBM.
8. Attach a stabilizing bracket to each EBM if needed (see “Stabilizing the Cabinet” on page 49).
9. Continue to one of the following sections:

“Communication” on page 53 to install UPS communication

options, such as X-Slot cards or REPO.

“Operation” on page 65 to start up the UPS.

Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 58)
Fig. 23 · Table 9. UPS Terminal Block Wiring

Figure 31. Typical EBM Installation (2-High Cabinets Shown)

52 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Ground Strap

Page 59 of the Powerware 9155 user manual — Figure 32. Communication Options and Control Terminals
Page 59 · click to enlarge
Page 59

Chapter 10 Communication

This section describes the:

DB-9 communication port

LanSafe Power Management Software

Remote Emergency Power-off

Relay output contacts

Programmable signal inputs

Figure 32 shows the location of the communication options and control terminals on the UPS.

Powerware 9155 — Chapter 10 Communication diagram (page 59)
Fig. 24 · Chapter 10 Communication

X-Slot Communication Bay #1

X-Slot Communication Bay #2

Figure 32. Communication Options and Control Terminals

53 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 7 more labels / short text on this page
X-Slot cards · Signal Input 1 · Signal Input 2 · REPO (Normally Open) · REPO (Normally Closed) · DB-9 Communication Port · Relay Contact
Page 60 of the Powerware 9155 user manual — Figure 33. Removing the Front Covers
Page 60 · click to enlarge
Page 60

Installing Communication Options and Control Terminals

To access and install the communication options and control terminals:

1. Remove the front covers of all cabinets, starting with the top cabinet. Press and release the handle latch at the bottom of each cover and then lift the cover up and off the cabinet (see Figure 33).
Powerware 9155 — Installing Communication Options and Control Terminals diagram (page 60)
Fig. 25 · Installing Communication Options and Control Termina…

Figure 33. Removing the Front Covers

2. Install the appropriate X-Slot card and/or necessary cable(s) into the top cabinet (see Figure 32 and Figure 34).

54 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication

Page 61 of the Powerware 9155 user manual — Figure 35. Removing Knockout Tabs
Page 61 · click to enlarge
Page 61
Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 61)
Fig. 26 · Table 9. UPS Terminal Block Wiring

Figure 34. Installing Communication Cables

3. On the bottom cover (and also the middle cover if 3-high), remove a knockout tab in the top edge of the cover for each cable:

With wire cutters, cut either side of the tab and twist down to remove the tab (see Figure 35).

Powerware 9155 — Figure 34. Installing Communication Cables diagram (page 61)
Fig. 27 · Figure 34. Installing Communication Cables

Figure 35. Removing Knockout Tabs

55 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication

Page 62 of the Powerware 9155 user manual — Figure 36. Reinstalling the Front Covers
Page 62 · click to enlarge
Page 62
4. Route the cable(s) to the approximate location of the cover access holes.
5. Connect the cables to the appropriate location.

See “Communication Options” on page 57 or “Control Terminals” on page 61 for detailed information.

6. Reinstall the front covers, starting with the bottom cabinet (see Figure 36).

Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. Be sure the cables fit in the access holes in the covers.

Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 62)
Fig. 28 · Table 9. UPS Terminal Block Wiring

Figure 36. Reinstalling the Front Covers

7. Continue to “Operation” on page 65 to start up the UPS.

56 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication

Page 63 of the Powerware 9155 user manual — DB-9 Communication Port
Page 63 · click to enlarge
Page 63

Communication Options

The Powerware 9155 has serial communication capabilities through the DB-9 communication port or through an X-Slot card in one of the available bays. In addition, the LanSafe Power Management Software can be installed and used to communicate with the UPS via one of the serial communication connections.

The UPS supports two serial communication devices according to the following table:

X-Slot 1 X-Slot 2 DB-9 Communication Port

Any X-Slot card Any X-Slot card Not in use

Any X-Slot card Powerware Relay Interface Card Powerware Hot Sync CAN Card

Any X-Slot card Not in use Available

DB-9 Communication Port

To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.

When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.

57 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication · Independent Multiplexed · Available

Page 64 of the Powerware 9155 user manual — X-Slot Cards
Page 64 · click to enlarge
Page 64

The cable pins are identified in Figure 37 and the pin functions are described in Table 10. See Figure 32 on page 53 for serial port location.

Figure 37. Communication Port

Table 10. Communication Port Pin Assignment

Signal Name Function Direction from the UPS

2 TxD Transmit to external device Out

3 RxD Receive from external device In

5 GND Signal common (tied to chassis) —

X-Slot Cards

X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 9155 has two available communication bays for any X-Slot card, including:

ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as

well as monitoring through a Web browser interface; connects to a twisted-pair Ethernet (10/100BaseT) network. It has a built-in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops. In addition, a Powerware Environmental Monitoring Probe can be attached to obtain humidity, temperature, smoke alarm, and security information.

Relay Interface Card - has isolated dry contact (Form-C) relay outputs

for UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass.

Modbus® Card - allows you to continuously and reliably monitor the

UPSs in your Building Management System (BMS).

58 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication · Pin Number · t

Page 65 of the Powerware 9155 user manual — Figure 38. Optional X-Slot Cards
Page 65 · click to enlarge
Page 65

Industrial Relay Card (IRC) - is used to indicate the operating status of

the UPS system using the customer’s monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm mode can be monitored.

Multi-Server Card - has six serial communication ports that can

communicate simultaneously with other computers using LanSafe Power Management Software (provided on the Powerware Software Suite CD).

Modem Card - provides out-of-band remote notification and

monitoring using modem communication directly to cell phones and pagers.

Single-Port Card - connects to the Powerware Expansion Chassis to

enable multiple communication options or to a PC for power management control.

ConnectUPS-MX SNMP Card - has Ethernet, modem, and SNMP

capabilities.

USB Card - connects to a USB port on your computer.

See Figure 32 on page 53 for the location of the two X-Slot communication bays.

Powerware 9155 — Table 9. UPS Terminal Block Wiring diagram (page 65)
Fig. 29 · Table 9. UPS Terminal Block Wiring

Figure 38. Optional X-Slot Cards

59 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 8 more labels / short text on this page
Communication · ConnectUPS-X Web/SNMP Card · Multi-Server Card · Relay Interface Card · Modem Card · Modbus Card · Single-Port Card · USB Card
Page 66 of the Powerware 9155 user manual — LanSafe Power Management Software
Page 66 · click to enlarge
Page 66

LanSafe Power Management Software

Each Powerware 9155 UPS ships with LanSafe Power Management Software and an interface cable. To begin installing LanSafe software, see the instructions accompanying the Powerware Software Suite CD.

LanSafe software provides up-to-date graphics of UPS power and system data and power flow. It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Powerware 9155 UPS battery power becomes low, LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.

60 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication

Page 67 of the Powerware 9155 user manual — Figure 39. External Control Terminal Connections
Page 67 · click to enlarge
Page 67

Control Terminals

The cables should be connected to the control terminals with cable clips. Input and output terminals have a functional isolation from terminal to terminal. They are connected to the UPS chassis through individual 1 MΩ resistors.

Signal Input 1 (Programmable)

Signal Input 2 (Programmable)

UPS Connectors (see Figure 32 on page 53)

Figure 39. External Control Terminal Connections

61 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 11 more labels / short text on this page
Communication · + Polarity · – Polarity · + Polarity · – Polarity · REPO Normally Open · REPO Normally Closed · Common 3 · Normally Closed · Relay Output · Normally Open
Page 68 of the Powerware 9155 user manual — C A U T I O N
Page 68 · click to enlarge
Page 68

Remote Emergency Power-off

REPO is used to shut down the UPS from a distance. This feature can be used for shutting down the load and the UPS by thermal relay, for instance in the event of room overtemperature. When REPO is activated, the UPS shuts down all converters, de-energizes all system relays, and fully powers down within 10-15 seconds.

There are two REPO positions that may be used, normally-open or normally-closed.

The pins on the normally-closed REPO connector are connected together. When this connection is open, the logic circuitry completely shuts down the UPS, thus preventing the power from supplying the load.

If the use of normally-closed REPO operation is desired, replace the connector with a normally-closed external switch (see Figure 32 on page 53).

If the use of normally-open REPO operation is desired, connect a normally-open external switch (see Figure 32 on page 53).

C A U T I O N

The REPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The REPO switch must have a minimum rating of 24 Vdc and 20 mA.

To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be disconnected from the UPS when the emergency power-off function is activated.

Wire Function Terminal Wire Size Rating Suggested Wire Size

REPO L1 12–22 AWG 18 AWG (0 82 mm2) L2

12–22 AWG (4–0.32 mm2) 18 AWG (0.82 mm2)

62 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication · REPO Connections

Page 69 of the Powerware 9155 user manual — Programmable Signal Inputs
Page 69 · click to enlarge
Page 69

Relay Contacts

The UPS incorporates a programmable relay output with potential free contacts for remote alarm indications (see Figure 32 on page 53). An additional four relay outputs can be obtained with the X-Slot compatible Relay Interface Card.

W A R N I N G

The relay contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The relay contacts must have a maximum rating of 30 Vdc/1A and 60 Vdc/2A nominal values.

Programmable Signal Inputs

The UPS incorporates two programmable signal inputs (see Figure 32 on page 53). Use of non-polar (relay) control input is recommended. The pins must be shorted with maximum resistance of 10 ohm in order to activate the specific input.

The default and programmable settings for the signal inputs are shown in Table 11.

63 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication

Page 70 of the Powerware 9155 user manual — Table 11. Programmable Signal Inputs
Page 70 · click to enlarge
Page 70

Table 11. Programmable Signal Inputs

Disable Bypass Operation If active, the automatic transfer to the static bypass is prevented.

Charger Off If active, the battery charge function is disabled. In a utility power outage, the discharge of batteries is supported.

Remote ON/OFF If active, the UPS output turns off regardless of the mode of operation. Auxiliary power, fan, communication, and rectifier/battery charger remain functional. Restart is initiated immediately when this signal is inactive.

Request Bypass If active, the UPS transfers to bypass if the bypass voltage, frequency, and synchronization are all okay.

Request Normal If active, the UPS transfers to inverter operation if not prohibited by REPO or an alarm condition.

Force Bypass If active, the UPS is forced to static bypass operation regardless of the bypass status.

External Battery Breaker Status If active, the UPS knows that the batteries are disconnected.

Building Alarm 1–6 These alarms can be activated separately or at the same time with other building alarms.

Not in Use Default

Shutdown If active, the UPS shuts down immediately.

Delayed Shutdown If active, the UPS shuts down after a user-configured delay time. Default shutdown delay is 120 seconds. The UPS automatically restarts when the signal changes to inactive.

Normal/Bypass If active, the UPS transfers to bypass if okay. If inactive, the UPS transfers to the inverter when possible.

On Generator If active, the UPS knows that input is fed from the generator. Bypass is disabled; the automatic battery test is disabled.

This option is not used.

64 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Communication · Signal Description · External Transformer Overtemperature

Page 71 of the Powerware 9155 user manual — Figure 40. Powerware 9155 Control Panel
Page 71 · click to enlarge
Page 71

Chapter 11 Operation

This chapter contains information on how to use the Powerware 9155, including front panel operation, UPS startup and shutdown, and operation of the Maintenance Bypass switch.

Control Panel Functions

The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 40).

Power On Indicator (Green) On Battery Indicator (Yellow)

Control Buttons for the LCD Menu Options

Figure 40. Powerware 9155 Control Panel

65 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Bypass Indicator (Yellow) · Alarm Indicator (Red)

Page 72 of the Powerware 9155 user manual — Display Functions
Page 72 · click to enlarge
Page 72

The following table shows the indicator status and description.

On The UPS is operating normally.

Green Flashing S The UPS is starting up or is shut down and waiting for power to return. S A new information message is active. S Bypass is not available.

Off The UPS is turned off and will not turn on automatically.

On The UPS is in Battery mode.

On The UPS is in Bypass mode.

On The UPS has an active alarm.

Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 91 for additional information.

Changing the Language

Press and hold the first button on the left for approximately five seconds to select the language menu. This action is possible from any LCD menu screen.

Display Functions

As the default or after 15 minutes of inactivity, the LCD displays the selectable startup screen. The default is the Eaton Powerware logo and can be changed to the Mimic screen in the User Settings menu.

The backlit LCD automatically dims after a long period of inactivity. Press any button to restore the screen.

Use the two middle buttons ( and ) to scroll through the menu structure. Press the button to enter a submenu. Press the button to select an option. Press the ESC button to cancel or return to the previous menu.

66 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 5 more labels / short text on this page
Operation · Indicator Status Description · Yellow · Yellow · Red
Page 73 of the Powerware 9155 user manual — Table 12. Menu Map for Display Functions
Page 73 · click to enlarge
Page 73

The following table shows the basic menu structure.

Table 12. Menu Map for Display Functions

Main Menu Submenu Display Information or Menu Function

UPS Status UPS off / System normal / UPS supporting load / UPS on battery / UPS on bypass / Active alarm list / Battery status

Event Log Displays up to 100 events and alarms

Measurements Output L-N and L-L / Current / Frequency / Power

Battery Voltage / Current / Runtime

Input L-N and L-L / Current / Frequency

Bypass L-N and L-L / Frequency

Control Go to Bypass Mode Forces the UPS to go to Bypass When this command is active, the option changes to Go to Normal Mode.

Start Battery Test Initiates a battery test

Display Test Four different selectable tests for the front panel functions: the LEDs cycle through, the alarm beep sounds, the backlight turns off and on, and the pixels scroll through to test the LCD.

Settings User Settings See Table 13 for detail. g

Service Settings This screen is password-protected.

Identification UPS Type / Part Number / Serial Number / Firmware / Display / CAN Bridge

Turn UPS ON/OFF ON and OFF Options

67 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 74 of the Powerware 9155 user manual — Table 13. User Settings
Page 74 · click to enlarge
Page 74

User Settings

The following table displays the options that can be changed by the user.

Table 13. User Settings

Description Available Settings Default Setting

Set Date and Time Set Month Date: mm/dd/yyyy Time: 24:00

01/01/2003 00:00

Display Contrast Adjust contrast with up/down arrow buttons

Change Language Select Language<English> or <Spanish>

Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4] Setup: [Battery Low] [On Battery] [On Bypass] [UPS ok] [custom] [empty]

Alarm 1: UPS ok X-Slots (1 or 2) #1: On Battery #2: Battery Low #3: UPS ok #4: On Bypass

Signal Inputs [empty] [Logic] (see “Programmable Signal Inputs” on page 63)

Serial Port Config Port[X-Slot-1] [X-Slot-2/Serv] Speed: [19200] [9600] [2400] [1200]

Parallel Operation Settings Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User’s Guide.

Start Screen Eaton Powerware logo Mimic Screen

User Password Enabled/Disabled If Enabled is selected, the password is USER.

Audible Alarms Normal Sound/Disabled Normal Sound

Battery Charging ABM cycling/constant ABM cycling

68 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 6 more labels / short text on this page
Operation · Moderate · English · Empty · Eaton Powerware logo · Disabled
Page 75 of the Powerware 9155 user manual — 120V/208V
Page 75 · click to enlarge
Page 75

Table 13. User Settings (continued)

Default Setting Available Settings Description

Automatic Battery Tests Enabled/Disabled Enabled automatically runs the battery test once a month.

Number of Battery Strings 0 through 22 (see “Configuring the UPS for EBMs” on page 75)

2 strings for UPS-32 models 4 strings for UPS-64 models

Battery Capacity 1 through 65535 watts per cell 34 W/cell

Battery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell

Set Nominal Output Voltage 120V/240V 120V/208V 110V/220V 100V/200V 127V/220V

120V/208V

Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%

Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%

Nominal Output Frequency 50 Hz or 60 Hz 60 Hz

Synchronization Window ±0.5 through ±3.0 Hz (0.1 Hz increments)

±2.0 Hz

Unsynchronized Transfer to Bypass Allowed/Not Allowed Not Allowed

Usage of Bypass Enabled/Disabled Enabled

Transfer to Bypass When Overload After a delay/Immediately After a delay

Automatic Start Delay -1 through 32767 seconds (-1 means disabled)

Automatic On Battery Shutdown Delay

-1 through 32767 seconds (-1 means disabled)

Control Commands from X-Slot1 Allowed/Disabled Allowed

Control Commands from X-Slot2/Serv

X-Slot Signal Input Activation Delay

0 through 65 seconds 5s

Input signal delayed shutdown delay

1 through 65535 seconds 120s

69 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 6 more labels / short text on this page
Operation · Enabled · Synchronization Enabled/Disabled Enabled · 0s · -1s · Allowed/Disabled Allowed
Page 76 of the Powerware 9155 user manual — Maintenance Bypass Startup
Page 76 · click to enlarge
Page 76

Table 13. User Settings (continued)

Default Setting Available Settings Description

Site Wiring Fault Notice Enabled/Disabled Enabled

Reset Custom Event Settings 0 through 32 Empty

Full Power Battery Test Enabled/Disabled Enabled

Auto Output Configuration Enabled/Disabled Enabled for initial startup Disabled after initial startup

UPS Startup

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.

Verify that UPS installation has been carried out correctly and the UPS ground has been connected.

Maintenance Bypass Startup

If you have an optional Maintenance Bypass Module or Power Distribution Module, you can start up the UPS in maintenance bypass, allowing utility power to supply the load.

To start up the UPS in maintenance bypass:

1. Verify that the Maintenance Bypass switch is in the BYPASS position (see Figure 41 on page 79).
2. Switch on utility power where the UPS is connected. The load is now powered by utility power.

70 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 77 of the Powerware 9155 user manual — Internal Bypass Startup
Page 77 · click to enlarge
Page 77

To switch to Normal mode from maintenance bypass:

1. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
2. Turn the Maintenance Bypass switch to the SERVICE position.

The UPS starts up in Bypass mode, with the load still powered by utility power.

3. Remove the breaker tie from all battery circuit breakers.
4. Switch all battery circuit breakers to the ON position.
5. Turn the Maintenance Bypass switch to the UPS position to return to Normal mode. The UPS is now powering the load.

Internal Bypass Startup

To start up the UPS in Bypass mode without an MBM/PDM:

1. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
2. Switch on utility power where the UPS is connected.
3. Wait for the front panel LCD to illuminate.

The indicator flashes.

4. Remove the breaker tie from all battery circuit breakers.

71 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 78 of the Powerware 9155 user manual — Normal Mode Startup
Page 78 · click to enlarge
Page 78
5. Switch all battery circuit breakers to the ON position.

The indicator stops flashing.

6. Press any button on the front panel display to activate the menu options.
7. Using the button on the front panel display, scroll to the Control menu option and press the button.
8. Press the button to select the Go to Bypass Mode option.

The and indicators illuminate, indicating the UPS is operating in Bypass mode. The load is now powered by utility power.

To switch to Normal mode from internal Bypass mode:

1. Press the button to select the Go To Normal Mode option.
2. Press the ESC button until the Eaton Powerware logo appears.

Normal Mode Startup

To start up the UPS:

1. If you have an optional MBM/PDM, verify that the Maintenance Bypass switch is in the UPS position (see Figure 41 on page 79).
2. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
3. Switch on utility power where the UPS is connected.
4. Wait for the front panel LCD to illuminate.

The indicator flashes.

5. Remove the breaker tie from all battery circuit breakers.
6. Switch all battery circuit breakers to the ON position.

The indicator stops flashing.

72 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 79 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 79 · click to enlarge
Page 79
7. Press any button on the front panel display to activate the menu options.
8. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu.
9. Select the ON option. Press and hold the button for three seconds, until the UPS stops beeping.

The indicator illuminates. The UPS is now powering the load.

If the indicator is flashing, check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.

73 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 80 of the Powerware 9155 user manual — Starting the UPS on Battery
Page 80 · click to enlarge
Page 80

Starting the UPS on Battery

To start the UPS on battery:

1. If you have an optional MBM/PDM, verify that the Maintenance Bypass switch is in the UPS position (see Figure 41 on page 79).
2. Switch all battery circuit breakers to the ON position.
3. Wait for the front panel LCD to illuminate.
4. Press any button on the front panel display to activate the menu options.
5. Within three minutes, press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu.
6. Select the ON option. Press and hold the button for three seconds, until the UPS stops beeping.

The UPS starts within two minutes. The UPS supplies power to your equipment and goes into Battery mode.

74 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 81 of the Powerware 9155 user manual — UPS + 1 EBM 10
Page 81 · click to enlarge
Page 81

Configuring the UPS for EBMs

To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:

1. Press any button on the front panel display to activate the menu options.
2. Using the button, scroll to the Settings menu.
3. Press the button twice to select the User Settings menu.
4. Using the button, scroll to the Number of Battery Strings option and press the button.
5. Use the or arrow buttons to select the number of strings according to your UPS configuration:

All 2-High UPS and EBM Cabinets* Number of Strings

UPS + 1 EBM 6

UPS + 2 EBMs 10

UPS + 3 EBMs 14

UPS + 4 EBMs 18

All 3-High UPS and EBM Cabinets* Number of Strings

UPS + 1 EBM 10

UPS + 2 EBMs 16

UPS + 3 EBMs 22

*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings. UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.

6. Press the button to save the setting.
7. Press the ESC button until the Eaton Powerware logo appears.

75 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 82 of the Powerware 9155 user manual — UPS Shutdown
Page 82 · click to enlarge
Page 82

UPS Shutdown

To shut down the UPS:

1. Press any button on the front panel display to activate the menu options.
2. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu.
3. Select the OFF option; press the button.
4. Confirm the selection. Press and hold the button for three seconds, until the UPS stops beeping.

The input contactor opens.

5. Switch the UPS battery circuit breaker to the OFF position.

The UPS is disconnected from the batteries and is on logic power only.

6. Switch off utility power where the UPS is connected.

76 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Operation

Page 83 of the Powerware 9155 user manual — Storing the UPS and Batteries
Page 83 · click to enlarge
Page 83

Chapter 12 UPS Maintenance

This section explains how to:

Care for the UPS and batteries

Recycle used batteries

Use the Maintenance Bypass switch

UPS and Battery Care

For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.

For full battery life, keep the UPS at an ambient temperature of 77°F (25°C).

Storing the UPS and Batteries

When storing the UPS and optional cabinets, the following requirements should be met:

Verify that the battery circuit breaker is in the OFF position.

Avoid temperature and humidity extremes. To maximize battery life,

the recommended storage temperature is 59°F (15°C) to 77°F (25°C).

If you store the UPS for a long period, recharge the batteries every

10 months by applying utility power. The batteries charge to 80% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 48 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the

date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative.

77 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 84 of the Powerware 9155 user manual — C A U T I O N
Page 84 · click to enlarge
Page 84

When to Replace Batteries

When the indicator flashes and the LCD panel displays Battery Failure, the batteries may need replacing. Contact your service representative to order new batteries.

Change the batteries approximately every five years.

Recycling the Used Battery

Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.

W A R N I N G

Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.

Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

C A U T I O N

Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.

C A U T I O N

Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.

78 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Maintenance

Page 85 of the Powerware 9155 user manual — Table 14. UPS-Mounted Bypass Switch Positions
Page 85 · click to enlarge
Page 85

Using the UPS-Mounted Maintenance Bypass Switch

The UPS-mounted Maintenance Bypass switch is part of the optional Maintenance Bypass Module or Power Distribution Module and is located on the back of the UPS (see Figure 41).

Powerware 9155 — Using the UPS-Mounted Maintenance Bypass Switch diagram (page 85)
Fig. 30 · Using the UPS-Mounted Maintenance Bypass Switch

Figure 41. Maintenance Bypass Switch (PDM Shown)

The UPS-mounted bypass switch has three positions as described in Table 14.

Table 14. UPS-Mounted Bypass Switch Positions

UPS Connects the UPS output to the load.

SERVICE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected to the UPS input.

BYPASS Like the SERVICE position, BYPASS connects the load directly to AC input power and disconnects UPS output. However, because BYPASS also disconnects AC input from the UPS, this is the appropriate position for UPS maintenance or repair.

79 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Maintenance · Switch Position Description

Page 86 of the Powerware 9155 user manual — UPS
Page 86 · click to enlarge
Page 86

Figure 42 shows a UPS with a separate battery cabinet and a UPS-mounted bypass switch.

UPS

UPS

UPS

UPS EBM

Figure 42. Typical Hardwired Installation with UPS-Mounted Bypass Switch

80 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 14 more labels / short text on this page
UPS Maintenance · UPS-Mounted Bypass Switch · Bypass · User-supplied · Service · Building · Load Distribution · Service · Panel · Panel · Bypass · Service · Bypass · Service
Page 87 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 87 · click to enlarge
Page 87

To switch the UPS to maintenance bypass from Normal mode (UPS-mounted operation):

1. Turn the Maintenance Bypass switch through the SERVICE position to the BYPASS position.

The battery circuit breaker trips, and the UPS is now bypassed, with the load powered by utility power.

2. The UPS automatically shuts down.

To return to Normal mode from maintenance bypass (UPS-mounted operation):

1. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
2. Turn the Maintenance Bypass switch to the SERVICE position.

The UPS starts up in Bypass mode, with the load still powered by utility power.

3. Switch the UPS battery circuit breaker to the ON position.
4. Turn the Maintenance Bypass switch to the UPS position to return to Normal mode. The UPS is now powering the load.

81 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Maintenance

Page 88 of the Powerware 9155 user manual — Figure 43. Wall-Mounted Maintenance Bypass Switch
Page 88 · click to enlarge
Page 88

Using the Wall-Mounted Bypass Switch

The wall-mounted bypass switch is rated at 80A/300 Vac and has four positions as described in Table 15.

Table 15. Wall-Mounted Bypass Switch Positions

UPS Connects the UPS output to the load.

LINE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected to the UPS input.

SERVICE Like the LINE position, SERVICE connects the load directly to AC input power and disconnects UPS output. However, because SERVICE also disconnects AC input from the UPS, this is the appropriate position for UPS maintenance or repair.

OFF Disconnects the load from the UPS output power and AC input power, as well as AC input power to the UPS input.

You must press the red button beside the switch before turning the Maintenance Bypass switch.

Powerware 9155 — Table 15. Wall-Mounted Bypass Switch Positions diagram (page 88)
Fig. 31 · Table 15. Wall-Mounted Bypass Switch Positions

Figure 43. Wall-Mounted Maintenance Bypass Switch

82 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Maintenance · Switch Position Description

Page 89 of the Powerware 9155 user manual — UPS
Page 89 · click to enlarge
Page 89

Figure 44 shows a UPS with a separate battery cabinet and a wall-mounted bypass switch.

UPS

UPS

UPS

UPS EBM

Figure 44. Typical Hardwired Installation with Wall-Mounted Bypass Switch

83 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 14 more labels / short text on this page
UPS Maintenance · External Bypass Switch · Off Service · Line · Building · Load Distribution · Service · Panel · Panel · Off Service · Line · Off Service · Line · User-supplied
Page 90 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 90 · click to enlarge
Page 90

To switch the UPS to maintenance bypass from Normal mode (wall-mounted operation):

1. Press the red button beside the Maintenance Bypass switch.
2. Turn the switch handle through the LINE position to the SERVICE position.

The battery circuit breaker trips, and the UPS is now bypassed, with the load powered by utility power.

3. The UPS automatically shuts down.

To return to Normal mode from maintenance bypass (wall-mounted operation):

1. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
2. Turn the Maintenance Bypass switch to the LINE position.

The UPS starts up in Bypass mode, with the load still powered by utility power.

3. Switch the UPS battery circuit breaker to the ON position.
4. Turn the Maintenance Bypass switch to the UPS position to return to Normal mode. The UPS is now powering the load.

84 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS Maintenance

Page 91 of the Powerware 9155 user manual — Table 16. Model List
Page 91 · click to enlarge
Page 91

Chapter 13 Specifications

This section provides the following specifications for the Powerware 9155 models:

Dimensions and weights

Environmental and safety specifications

Table 16. Model List

UPS Description Power Rating

PW9155-8-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 8 kVA, 7.2 kW

PW9155-8-64 3-highUPS with two battery sections 8 kVA, 7.2 kW

PW9155-10-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 10 kVA, 9 kW

PW9155-10-64 3-highUPS with two battery sections 10 kVA, 9 kW

PW9155-12-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 12 kVA, 10.8 kW

PW9155-12-64 3-highUPS with two battery sections 12 kVA, 10.8 kW

PW9155-15-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 15 kVA, 13.5 kW

PW9155-15-64 3-highUPS with two battery sections 15 kVA, 13.5 kW
PW9155-EBM-64 2-hightwo battery sections
PW9155-EBM-96 3-highthree battery sections

85 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 6 more labels / short text on this page
Model list · Technical specifications · Model specifications · Battery specifications · Battery runtimes · EBM Description
Page 92 of the Powerware 9155 user manual — Table 18. Environmental and Safety Specifications
Page 92 · click to enlarge
Page 92

Table 17. Dimensions and Weights

Dimensions (H x W x D) Weight

2-High UPS 32.2” × 12” × 32” (81 × 30 × 81 cm) 352 lb (160 kg)

3-High UPS-32 47.8” × 12” × 32” (121.5 × 30 × 81 cm) 550 lb (250 kg)

3-High UPS-64 47.8” × 12” × 32” (121.5 × 30 × 81 cm) 590 lb (268 kg)

2-High EBM 32.2” × 12” × 30.3” (81 × 30 × 77 cm) 480 lb (218 kg)

3-High EBM 47.8” × 12” × 30.3” (121.5 × 30 × 77 cm) 710 lb (322 kg)

PDM (rear UPS mount) 16.5” × 12” × 7” (42 × 30 × 17.8 cm) 25 lb (11 kg)

MBM (rear UPS mount) 16.5” × 12” × 7” (42 × 30 × 17.8 cm) 18 lb (8 kg)

Table 18. Environmental and Safety Specifications

Operating Temperature 10°C to 40°C (50°F to 104°F) Optimal battery performance: 25°C (77°F)

Transit Temperature -25°C to 55°C (-13°F to 131°F)

Storage Temperature 0°C to 25°C (32°F to 77°F) Recommended battery storage: 59°F (15°C) to 77°F (25°C)

Ventilation Front air intake, forced air, two fans, positive pressurization,

Altitude 9,843 ft (3,000m) operating without derating 32,810 ft (10,000m) during transportation

Relative Humidity 5–95% noncondensing

Heat Dissipation 5582 BTU/hr maximum online 5294 BTU/hr maximum on battery

Audible Noise

Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3; EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1

Agency Markings UL, cUL, CE, NOM-NYCE

EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003, VCCI

Surges IEEE/ANSI C62.41 Cat B3

86 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Specifications · temperature UPS-monitored

Page 93 of the Powerware 9155 user manual — Table 19. Technical Specifications
Page 93 · click to enlarge
Page 93

Table 19. Technical Specifications

Technology Online, double-conversion, split-phase topology with Static Bypass switch and

optional 3-position Maintenance Bypass switch.

Frequency independent operation.

Input Voltage Range 75–144 Vac per phase

Input Isolation Transformer Input Voltage Range

208V or 240V ±20%

Input Power Factor >0.99 at full load nominal line conditions

Input Rated Voltage 100/200, 110/220, or 120/240 Vac with 180° phase displacement 120/208 or 127/220 Vac with 120° phase displacement

Input Frequency Range 45–65 Hz

Input Rated Frequency 50/60-Hz selectable, auto-configuring

±1% static, Phase to Neutral

±2% static, Phase to Phase ±5% dynamic at 100% resistive load change

Response time

Output Frequency 50/60-Hz selectable or auto-configuring

Frequency/phase-converter operation with derated output load capacity to 80%;

Frequency Conversion mode can be configured through the front panel or

through XCP commands. Bypass is not available in Frequency Conversion mode.

Output Overload 101–110% for 10 minutes 111–125% for 60 seconds 126–149% for 5 seconds >150% for 300 milliseconds

87 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 6 more labels / short text on this page
Specifications · Output Voltage Regulation · Output Voltage Distortion · Output Frequency Regulation · Synchronization to line · Output Frequency Conversion
Page 94 of the Powerware 9155 user manual — Table 20. Model Specifications
Page 94 · click to enlarge
Page 94

Table 20. Model Specifications

Powerware 9155 — Table 20. Model Specifications diagram (page 94)
Fig. 32 · Table 20. Model Specifications

Output kVA (line–line loads) 12.5 13.8 15.0 13.0 13.0

Output kVA (line–neutral loads) 12.5 13.8 15.0 15.0 15.0

Output kVA (line–line loads) 12.0 12.0 12.0 10.4 10.4

Output kVA (line–neutral loads) 12.0

*Input current for the input isolation transformer is 4% higher than for the UPS.

88 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Specifications

Page 95 of the Powerware 9155 user manual — Table 20. Model Specifications (continued)
Page 95 · click to enlarge
Page 95

Table 20. Model Specifications (continued)

Powerware 9155 — Table 20. Model Specifications (continued) diagram (page 95)
Fig. 33 · Table 20. Model Specifications (continued)

Output kVA (line–line loads) 10.0 10.0 10.0 8.7 8.7

Output kVA (line–neutral loads) 10.0

Output kVA (line–line loads) 8.0 8.0 8.0 6.9 6.9

Output kVA (line–neutral loads) 8.0

*Input current for the input isolation transformer is 4% higher than for the UPS.

89 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Specifications

Page 96 of the Powerware 9155 user manual — Table 22. Battery Runtimes (in Minutes) at Full Load
Page 96 · click to enlarge
Page 96

Table 21. Battery Specifications

Battery Type 9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float service life at 77°F (25°C), voltage 192 Vdc (96 cells per string)

Number of Strings Maximum of 22 strings per full configuration, including UPS batteries (4 EBM-64

cabinets or 3 EBM-96 cabinets, plus UPS batteries)

UPS-322 strings; UPS-64: 4 strings EBM-64: 4 strings; EBM-96: 6 strings

Battery Replacement Must be replaced by qualified service technician

Charger Service configurable 0.5–34A per string, with overall maximum of 34A (limited by

input current). Default3.4A per string

Charging Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage after full load discharge External battery: no more than 10x discharge time to 90% usable capacity at nominal line voltage after full load discharge

Start-on-Battery Allows start of UPS without utility input

Performance ABM technology increases battery service life, optimizes recharge time, and

provides a warning before the end of useful battery life

Protection Extended Battery Module output protected by 100A circuit breaker

Table 22. Battery Runtimes (in Minutes) at Full Load

Load 32 Internal UPS Batteries (1) EBM-64 (2) EBM-64 (3) EBM-64 (4) EBM-64

15 kVA/13.5 kW 4 23 43 65 88

12 kVA/10.8 kW 6 30 56 85 116

10 kVA/9 kW 8 37 69 106 144

8 kVA/7.2 kW 11 49 91 139 189

Load 64 Internal UPS Batteries (1) EBM-96 (2) EBM-96 (3) EBM-96

15 kVA/13.5 kW 13 43 76 113

12 kVA/10.8 kW 18 56 101 149

10 kVA/9 kW 22 69 124 184

8 kVA/7.2 kW 29 91 164 242

90 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Specifications · 2-High Cabinets · 3-High Cabinets

Page 97 of the Powerware 9155 user manual — Typical Alarms and Conditions
Page 97 · click to enlarge
Page 97

Chapter 14 Troubleshooting

The Powerware 9155 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user. Use the following troubleshooting chart to determine the UPS alarm condition.

Typical Alarms and Conditions

The following table describes typical alarms and conditions; check the Event Log through the control panel for a list of active alarms. If an alarm appears with a service code, please contact the help desk (see page 93).

Alarm or Condition Possible Cause Action

A utility failure has occurred and the UPS is in Battery mode.

The UPS is powering the equipment with battery power. Prepare your equipment for shutdown.

LED is on. 1 beep every second.

The battery is running low. Five minutes or less of battery power remains (depending on load configuration and battery charge). Save your work and turn off your equipment. When utility power is restored, the UPS restarts automatically, provides power to the load, and charges the battery.

LED is on. Continuous beep for 10 seconds.

The UPS does not recognize the internal batteries.

Verify the battery circuit breaker is in the ON position. If the condition persists, contact your service representative.

LED is on. 1 beep every second.

91 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

On Battery · Battery Low · Battery Breaker

Page 98 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 98 · click to enlarge
Page 98

Action Possible Cause Alarm or Condition

Power requirements exceed the UPS capacity (greater than 100% of nominal; see page 87 for specific output overload ranges).

Remove some of the equipment from the UPS. The UPS continues to operate, but may switch to Bypass Mode if the load increases. The alarm resets when the condition becomes inactive.

LED is on. 1 beep every second.

UPS internal temperature is too high or the fan has failed.

If you have an optional Maintenance Bypass Module or Power Distribution Module, turn the Maintenance Bypass switch to the SERVICE position. Otherwise, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. If the alarm disappears, turn the Maintenance Bypass switch back to the UPS position (or restart the UPS if you do not have a switch). If the condition persists, contact your service representative.

LED is on. 1 beep every second.

Battery test failed The batteries need service. Contact your service representative.

The UPS does not

The main utility breaker is off. Verify that the main utility breaker is on. start. If an optional isolation transformer is installed, the input circuit breaker is off.

Verify that the isolation transformer input circuit breaker is on.

The Remote Emergency Power-off switch is active or the REPO connector is missing.

Reset the REPO switch and restart the UPS. Verify that the REPO connector is present.

Power is not available at the UPS output receptacles.

The UPS is in Standby mode. Supply power to the connected equipment: Press any button on the front panel display to activate the menu options. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu. Select the ON option. Press and hold the button for three seconds, until the UPS stops beeping.

The UPS does not provide the expected backup time.

Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service representative. p

The batteries need charging or service.

Battery circuit breakers are in the OFF position.

Switch all battery circuit breakers to the ON position.

92 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Show 4 more labels / short text on this page
Troubleshooting · Overload · Overtemperature · t t
Page 99 of the Powerware 9155 user manual — Service and Support
Page 99 · click to enlarge
Page 99

Silencing the Alarm

Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition.

Press any button on the front panel display to silence the alarm. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing.

Service and Support

If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.

In the United States1-800-843-9433 or 1-919-870-3028 In Canada: 1-800-461-9166 All other countries: Call your service representative

Please have the following information ready when you call for service:

Firmware version number

Date of failure or problem

Symptoms of failure or problem

Customer return address and contact information

93 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Troubleshooting · Model number · Serial number

Page 100 of the Powerware 9155 user manual — Powerware Models: 9150, 9155, 9170+, and FERRUPS ® 4.3–18 kVA
Page 100 · click to enlarge
Page 100

Two-Year Limited Warranty

Powerware Models: 9150, 9155, 9170+, and FERRUPS ® 4.3–18 kVA

(US and Canada)

WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).

LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original end-user (the “End-user”) of any Powerware 9150, 9155, 9170+, and FERRUPS 4.3–18 kVA Products (individually and collectively, the “Product”) purchased on or after June 1, 2004 and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-user.

LIMITED WARRANTY PERIOD: The period covered by this Warranty for the Product installed [and currently located] in the fifty (50) United States, the District of Columbia, and Canada is twenty-four (24) months from the date of purchase for parts and ninety (90) days from the date of purchase for parts and labor, as further clarified in the following sections.

WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually and collectively, the “Warranted Items”) are free of defects in material and workmanship. If, in the opinion of Company, a Warranted Item is defective and the defect is within the terms of this Warranty, Company’s sole obligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor, as applicable), at the option of Company, and such repair or replacement shall be at either the End-user’s location, Company’s site, or such other location as determined by Company. All Warranted Items returned to Company and all parts replaced by Company shall become the property of Company. Expenses for any labor to repair the Warranted Item beyond the initial ninety (90) days are the sole responsibility of the End-user

PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS when shipment is required of End-user: When Company determines that the Warranted Item will be repaired or replaced at a Company site or such other location, and the End-user must ship to Company the defective Warranted item, the following procedures are required.

If the Warranted Item is to be replaced by Company, and the End-user supplies a credit card number or purchase order for the value of the replacement product, Company will use commercially reasonable business efforts to ship (via standard ground shipment and at no cost to the End-user) the replacement Warranted Item to the End-user within one (1) business day after Company receives notice of the warranty claim. In such case, the End-user must return (at Company’s expense) the defective Warranted Item to Company in the same packaging as the replacement Warranted Item received by the End-user or as otherwise instructed by Company. If Company does not receive the defective Warranted Item, Company will either charge the End-user’s credit card, or send the End-user an invoice (which the End-user agrees to pay), for the value of the replacement product.

If the Warranted Item is to be replaced by Company, but the End-user is unwilling or unable to supply a credit card number or purchase order for the value of the replacement product, Company will use commercially reasonable business efforts to ship (via standard ground shipment and at no cost to the End-user) the replacement Warranted Item to the End-user within one (1) business day after Company receives the defective product from the End-user.

94 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Two-Year Limited Warranty

Page 101 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 101 · click to enlarge
Page 101

In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for return of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that are replaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced by Company shall become the property of Company.

WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.

This Warranty is not valid if the Product’s serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof.

Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.

COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO END-USER.

COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE.

THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE, NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE LIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.

LIMITATION OF LIABLITY: The remedies of the End-user set forth herein are exclusive and are the sole remedies for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract, in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of customers of the End-user or any special, indirect, incidental or consequential damages whatsoever. The total cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort (including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability is based.

Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s reasonable control.

END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-user must use the Product in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect.

95 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Two-Year Limited Warranty

Page 102 of the Powerware 9155 user manual — within 30 days of purchase. Powerware Models: 5115, 5125, 5140, 9104, 9120,
Page 102 · click to enlarge
Page 102

Extended Ten-Year Pro-Rated Limited Warranty

OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.

COSTS NOT RELATED TO WARRANTY: The End-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End-user.

OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3028. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.

Extended Ten-Year Pro-Rated Limited Warranty

Applies only to original purchasers for end use in the United States and Canada who file the Warranty Registration Card

within 30 days of purchase. Powerware Models: 5115, 5125, 5140, 9104, 9120,

9125, 9155, 9170+, and FERRUPS

WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).

LIMITED WARRANTY: This pro-rated limited warranty (this “Warranty”) applies only to the original End-user (the “End-user”) of any Powerware 5115, 5125, 5140, 9104, 9120, 9125, 9155, 9170+, and FERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-user.

WHAT THIS WARRANTY COVERS: In addition to the standard Two-Year Limited Warranty covering the applicable Product, the warrantor warrants that the Product will have a service life (defined below) of Ten years from the date of purchase (the “Ten-Year Service Life”) when used in accordance with the storage, handling, installation, operation and maintenance procedures prescribed in the Product’s operation and maintenance manual. “Service life” means the Product’s ability to deliver at least 80% of its original rated backup time.

If Company finds, in its sole discretion, that any Product has not provided the Ten-Year Service Life, Company will, as its sole obligation and the End-user’s sole remedy for Company’s breach of this warranty, repair or replace the Product, at its option, F.O.B. Company’s factory, for a charge, payable by the End-user to Company pro-rated on the following basis:

96 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 103 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 103 · click to enlarge
Page 103

The End-user will be allowed a credit against Company’s list price of equivalent equipment at the time of return of the Product to Company, in proportion to the percentage of Ten-Year Service Life remaining at the time of return of the Product to Company. In calculating the available credit, the remaining portion of the Ten-Year Service Life will be rounded up or down to the nearest whole year. The End-user will assume responsibility to pay the balance of the list price; and Company reserves the right to require payment prior to delivery of the repaired or replacement equipment.

For the avoidance of doubt, Company’s responsibilities under this Warranty are as follows:

Years 1-2 - Product repaired or replaced pursuant to terms of Limited Warranty

Years 3-10 - Credit ($) = Current List Price × Years of Unexpired Life 10 Years of Warranted Life

WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.

This Warranty is not valid: (a) unless the End-user returns to Company the Warranty Registration Card within thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof.

Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.

COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO END-USER.

COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE.

THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE, NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE LIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.

97 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

ExtendedTen-YearPro-RatedLimitedWarranty

Page 104 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 104 · click to enlarge
Page 104

Extended Ten-Year Pro-Rated Limited Warranty

LIMITATION OF LIABLITY: The remedies of the End-user set forth herein are exclusive and are the sole remedies for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract, in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of customers of the End-user or any special, indirect, incidental or consequential damages whatsoever. The total cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort (including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability is based.

Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s reasonable control.

END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-user must use the Product in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect.

OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.

COSTS NOT RELATED TO WARRANTY: The End-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End-user.

OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3028. Company will not accept any product for return, credit or exchange unless expressly authorized by Company in writing and delivered FOB Company factory. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.

98 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Page 105 of the Powerware 9155 user manual — Powerware Models 3110, 3115, 5115, 5125, 9120, 9125, 9150, 9155, 9170+,
Page 105 · click to enlarge
Page 105

Load Protection Guarantee

Powerware Models 3110, 3115, 5115, 5125, 9120, 9125, 9150, 9155, 9170+,

and FERRUPS (US and Canada)

GUARANTOR: The guarantor for the load protection guaranty set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).

LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-user (the “End-user”) of any Powerware 3110, 3115, 5115, 5125, 9120, 9125, 9150, 9155, 9170+, and FERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Guaranty applies even in the event that the Product is initially sold by Company for resale to an End-user.

WHAT THIS GUARANTY COVERS: For the lifetime of the Product, guarantor promises to repair or replace, at guarantor’s option, the equipment (valued up to the limits shown below*) that is damaged by an AC power line surge, spike, or other transient when properly connected to guarantor’s uninterruptible power system (“UPS”). Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the following circumstances arise:

1. The UPS is plugged in properly grounded and wired outlets, using no extension cords, adapters, other ground wires or other electrical connectors;
2. The installation of the UPS complies with all applicable electrical and safety codes described by the National Electric Code (NEC);
3. The UPS was used under normal operating conditions and in accordance with all labels and instructions; and
4. The UPS was not damaged by accident (other than AC power line transient), misuse, or abuse.

*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:

$25,000 for Powerware Models 3110 and 3115

$150,000 for Powerware Models 5115 and 5125

$250,000 for Powerware Models 9120, 9125, 9150, 9155, 9170+, and FERRUPS products

WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-user’s equipment does not include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.

This Guaranty is not valid: (a) unless the End-user returns to Company the Warranty Registration Card within thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible.

99 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Load Protection Guarantee

Page 106 of the Powerware 9155 user manual — Table 9. UPS Terminal Block Wiring
Page 106 · click to enlarge
Page 106

Company shall not be responsible for any charges for testing, checking, removal or installation of any items.

LIMITATION OF LIABILITY: THE REMEDIES OF THE END-USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER. EXCEPT AS OTHERWISE PROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE PRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE, LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OF CAPITAL, CLAIMS OF CUSTOMERS OF THE END-USER OR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES WHATSOEVER. THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE BASED IN CONTRACT (INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE, SHALL NOT EXCEED THOSE SET FORTH ABOVE. Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes beyond Company’s reasonable control.

END-USER’S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End-user must use the Product in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect.

OTHER LIMITATIONS: Company’s obligations under this Guaranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Guaranty.

COSTS NOT RELATED TO GUARANTY: The End-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Guaranty will be borne by the End-user.

TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3028. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.

100 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Load Protection Guarantee

Ask about the Powerware 9155

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Powerware 9155

Be the first to ask — other owners or our team will answer.