USER’S GUIDE

NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Some configurations are classified under IEC 62040-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:

Powerware, ABM, and FERRUPS are registered trademarks and X-Slot, ConnectUPS, and Powerware Hot Sync are trademarks of Eaton Power Quality Corporation. Greenlee is a registered trademark of Greenlee Textron. Modbus is a registered trademark of Modicon.
ECopyright 2004–2005 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.

Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
EU Directives:
73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68

The following are examples of symbols used on the UPS to alert you to important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.


The Powerware® 9155 is a double-conversion, split-phase, online uninterruptible power system (UPS) for protecting computer systems and other intelligent devices. It is ideal for protecting essential information technology and electrical engineering infrastructure in corporate, telecom, health care, banking, and industrial applications.
The UPS provides a steady, well-regulated power supply for your computing and communications equipment, while protecting it from the frequent irregularities that are inherent in commercially available power. Voltage spikes, power surges, brownouts, and power failures have the potential to corrupt critical data, destroy unsaved work sessions, and in some instances, damage expensive hardware.
With the Powerware 9155, you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment. Figure 1 shows the Powerware 9155 UPS and an optional Extended Battery Module (EBM).
1 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Providing outstanding performance and reliability, the Powerware 9155’s unique benefits including the following:
Online UPS design with pure sine wave output. The UPS filters and
regulates incoming AC power and provides consistent power to your equipment without draining the battery.
More wattage in less space with a 0.9 power factor – protecting more
equipment and leaving more room for expansion.
Support for Powerware Hot Synct paralleling of multiple modules for
redundancy or extra capacity.
Input current total harmonic distortion (THD) of less than five
percent, using active input power factor correction.
ABM® technology that uses advanced battery management to increase
battery service life, optimize recharge time, and provide a warning before the end of useful battery life.
Up to four hours of extended runtime with added EBMs.
Advanced power management with the Powerware Software Suite CD
for graceful shutdowns and power monitoring.
Emergency shutdown control through the Remote Emergency
Power-off (REPO) port.
Start-on-battery capability for powering up the UPS even if utility
power is not available.
Standard communication options with a DB-9 serial port, relay output
contacts, and programmable signal inputs.
Optional X-Slott cards enhance communication capabilities for
increased power protection and control.
Backed by worldwide agency approvals.
2 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Introduction

The following options for the Powerware 9155 are available:
The optional MBM is installed on the UPS rear panel and is used to bypass the UPS during maintenance or servicing. The Maintenance Bypass switch on the MBM provides a Make-Before-Break (MBB) wrap-around bypass for UPS service without shutting down the load.
The optional PDM provides the same functionality as the MBM and also comes equipped with several different types of output receptacles.
The optional wall-mounted bypass switch is used to bypass the UPS during maintenance or servicing, providing wrap-around bypass for UPS service without shutting down the load.
A parallel system with up to three UPSs can be installed to provide a parallel capacity and/or redundant system. This load sharing system provides more capacity than a single UPS and can provide backup, depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load. A parallel Powerware Hot Sync Computer Area Network (CAN) Bridge Card provides connectivity for system metering and operational mode control. The parallel system consists of two to three UPSs, each with a parallel CAN Bridge Card, and a parallel tie cabinet. Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User’s Guide for more information.
The optional input isolation transformer is located at the bottom of a 3-high UPS model. The input isolation transformer provides a neutral from a 208V or 240V input source with 240V output and can be wired to the UPS or to an MBM/PDM.
The seismic kit secures the UPS and optional EBMs for Zone 4 seismic installations.
3 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Introduction

4 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Introduction

The only user operations permitted are:
Starting up and shutting down the UPS
Operating the user interface
Connecting data interface cables
Monitoring the UPS with power management software
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
This UPS contains its own energy source (batteries). The UPS output may carry live voltage even when the UPS is not connected to an AC supply.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).
To reduce the risk of fire, connect only to a circuit provided with 100 amperes maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.
Output overcurrent protection and disconnect switch must be provided by others.
5 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

This chapter describes:
Unloading the cabinet(s)
Selecting an installation option
The instructions are intended for the chief operator/system supervisor, electrical consultants, and installation electricians. Local regulations and electrical code must be followed during the UPS installation.
If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
9 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Equipment inspection · Floor loading

When planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate weights are shown in the following table.
Standard Model Floor Loadings (2-High/3-High Cabinets)
Powerware 9155 Maximum Weight (lb)
Distributed Loading (lb/ft2)
2-High UPS 352 88 166
3-High UPS 590 148 278
3-High UPS with Isolation Transformer
2-High EBM 480 120 226
3-High EBM 710 178 335
The following clearances are recommended for the Powerware 9155 UPS:
From Front of Cabinet 36” (91.4 cm) working space
From Back of Cabinet 6” (15.2 cm) without MBM/PDM installed; with MBM/PDM installed, clearance determined by customer-supplied mating plug
10 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

The following tools are required for unloading the cabinet(s):
15 mm wrench or socket
7 mm nutdriver or socket
The UPS and EBM are heavy (see page 10). Unloading the cabinets requires at least two people to safely remove the cabinets from the pallet.
To remove the UPS or EBM from the shipping pallet:

11 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Setup



12 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

If needed, adjust the leveling feet so that the cabinet will roll.

13 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Setup

You are now ready to install the Powerware 9155 UPS. Select one of the following installation options according to your UPS configuration:
UPS Configuration Installation Chapter
UPS only Chapter 4, “UPS Only Installation” on page 15
UPS with an optional input isolation transformer
Chapter 5, “Input Isolation Transformer Installation” on page 21
UPS with an optional UPS-mounted bypass switch
Chapter 6, “UPS-Mounted Bypass Switch Installation” on page 29
UPS with an optional wall-mounted bypass switch
Chapter 7, “Wall-Mounted Bypass Switch Installation” on page 39
Parallel UPS configuration Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User’s Guide.
14 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Setup

The Powerware 9155 has the following power connections:
2-phase (L1 and L2), neutral, and ground connection for
2-phase (L1 and L2), neutral, and ground connection for load output
The nominal input/output voltages are:
100/200, 110/220, or 120/240 Vac with 180° phase displacement
120/208 or 127/220 Vac with 120° phase displacement
Output overcurrent protection and disconnect switch must be provided by others.
Figure 7 on page 19 shows a oneline diagram of the UPS.
15 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
rectifier/bypass input

Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Use the following procedure to hardwire the UPS:
Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:
UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*
8 kVA 60A 4 AWG (21.2 mm2)
10 kVA 80A 3 AWG (26.7 mm2)
12 kVA 100A 2 AWG (33.6 mm2)
15 kVA 100A 2 AWG (33.6 mm2)
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
16 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Only Installation


UPS Wiring Access Cover
See Table 2 for specifications and Figure 6 for a detailed view of the UPS terminal block.
17 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Only Installation · Battery Connector · Conduit Landing

Input Ground TB1-1 8 AWG p
L1 TB1-3 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Output L1 TB1-6 3 AWG p
Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Ground TB1-9 8 AWG
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
1 2 3 4 5 6 7 8 9
18 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

19 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Only Installation

20 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Only Installation

The Powerware 9155 has the following power connections:
2-phase (L1 and L2), neutral, and ground connection for
2-phase (L1 and L2), neutral, and ground connection for load output
The input isolation transformer output is always 240V (180° phase angle).
If installing an MBM/PDM, the UPS MUST be set up for 240V output only; otherwise, the “Bypass Not Available” alarm annunciates. Any equipment connected to the output requiring 208V (120° phase angle) is at risk for damage when using the Maintenance Bypass switch.
The input isolation transformer cannot be used with a wall-mounted bypass switch.
Output overcurrent protection and disconnect switch must be provided by others.
Figure 11 and Figure 12 beginning on page 27 show the oneline diagrams of the input isolation transformer with the UPS.
21 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
rectifier/bypass input

Input Isolation Transformer Installation
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Use the following procedure to hardwire the input isolation transformer and UPS. All hardware is supplied in the accessory kit.
Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:
UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*
8 kVA 60A 4 AWG (21.2 mm2)
10 kVA 80A 3 AWG (26.7 mm2)
12 kVA 100A 2 AWG (33.6 mm2)
15 kVA 100A 2 AWG (33.6 mm2)
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
22 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Isolation Transformer Installation

UPS Wiring Access Cover
Input Isolation Transformer Wiring Cover
See Table 4 for specifications and Figure 9 for a detailed view of the input isolation transformer terminal block.
23 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Isolation Transformer Installation

24 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Isolation Transformer Installation
Wire Function Terminal Position Minimum Wire Size* Tightening Torque
Input L1 TB1-1 2 AWG p
L2 (208V) TB1-2 2 AWG 25 lb in (2 83 Nm) L2 (240V) TB1-3 2 AWG (2.83 Nm)
Output L1 TB1-4 3 AWG p
L2 TB1-5 3 AWG 25 lb in (2 83 Nm) Neutral TB1-6 3 AWG (2.83 Nm)
Ground Output TB1-7 8 AWG 25 lb in Ground Input TB1-8 8 AWG 25 lb in (2.83 Nm)
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
Input Ground TB1-1 8 AWG p
L1 TB1-3 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Output L1 TB1-6 3 AWG p
Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Ground TB1-9 8 AWG
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
25 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Isolation Transformer Installation
1 2 3 4 5 6 7 8 9
See Table 4 for specifications and Figure 9 for a detailed view of the input isolation transformer terminal block.
Insert the supplied nylon bushing inside the wiring access hole.
26 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Input Output

Input Isolation Transformer Installation
27 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Input Isolation Transformer Installation

28 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

This chapter describes the Maintenance Bypass Module and Power Distribution Module installation. Both modules have a Make-Before-Break Maintenance Bypass switch.
If you purchased an optional MBM/PDM, attach the module to the UPS before any wiring installation. All hardware is supplied in the accessory kit. Use the following procedure to attach the optional MBM/PDM to the UPS:

Lowest Top Cover Screw (one each side)
Connecting Plate (8 screws)
29 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS-Mounted Bypass Switch Installation
Repeat for the other side.

UPS Wiring Access Cover
30 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
L-Bracket and Screws

UPS-Mounted Bypass Switch Installation

Nylon Bushings in UPS Wiring Access Holes
MBM/PDM Wiring Access Cover and the Conduit Landing Plate (Removed)
31 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Electronics Unit

UPS-Mounted Bypass Switch Installation

Screws for Top of Module
Wiring the MBM/PDM
The Powerware 9155 UPS has the following power connections:
2-phase (L1 and L2), neutral, and ground connection for
2-phase (L1 and L2), neutral, and ground connection for load output
The nominal input/output voltages are:
100/200, 110/220, or 120/240 Vac with 180° phase displacement
120/208 or 127/220 Vac with 120° phase displacement
32 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Screws to L-Bracket · rectifier/bypass input

UPS-Mounted Bypass Switch Installation
Output overcurrent protection and disconnect switch must be provided by others.
Figure 20 and Figure 21 beginning on page 37 show the oneline diagrams of the MBM and PDM with the UPS.
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Use the following procedure to hardwire the MBM/PDM:
Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:
UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*
8 kVA 60A 4 AWG (21.2 mm2)
10 kVA 80A 3 AWG (26.7 mm2)
12 kVA 100A 2 AWG (33.6 mm2)
15 kVA 100A 2 AWG (33.6 mm2)
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
33 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS-Mounted Bypass Switch Installation

See Table 7 for specifications and Figure 18 for a detailed view of the MBM/PDM terminal block.
34 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS-Mounted Bypass Switch Installation

Input Ground TB10-1 8 AWG p
L1 TB10-2 3 AWG 25 lb in 2” access hole for Neutral TB10-3 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Output L1 TB10-5 3 AWG p
Neutral TB10-6 3 AWG 25 lb in 2” access hole for L2 TB10-7 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Ground TB10-8 8 AWG
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
35 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS-Mounted Bypass Switch Installation
Connect the maintenance bypass (red and black) wires to TB1-2 (the A/B maintenance bypass auxiliary contacts) on the UPS terminal block.
1 2 3 4 5 6 7 8 9
A/B Maintenance Bypass Auxiliary Contacts
36 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Input Output

UPS-Mounted Bypass Switch Installation
37 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

UPS-Mounted Bypass Switch Installation
38 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

This chapter describes the wall-mounted bypass switch installation with the UPS. The wall-mounted bypass switch is a Make-Before-Break Maintenance Bypass switch.
Figure 22 shows the wall-mounted bypass switch and dimensions.
Height (A) 21.0” (53.4 cm)
Width (B) 14.0” (35.6 cm)
Depth (C) 6.8” (17.2 cm)
(D) 11.0” (28.0 cm) g Centers (E) 20.0” (50.8 cm)
Weight 31 lb (14.1 kg)

39 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Dimension Measurement · Mounting C t

Wall-Mounted Bypass Switch Installation
Use the following procedure to set up the wall-mounted bypass switch:
40 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Wall-Mounted Bypass Switch Installation
The Powerware 9155 UPS has the following power connections:
2-phase (L1 and L2), neutral, and ground connection for
2-phase (L1 and L2), neutral, and ground connection for load output
The nominal input/output voltages are:
100/200, 110/220, or 120/240 Vac with 180° phase displacement
120/208 or 127/220 Vac with 120° phase displacement
Output overcurrent protection and disconnect switch must be provided by others.
Figure 28 on page 47 shows a oneline diagram of the UPS with a wall-mounted bypass switch.
41 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
rectifier/bypass input

Wall-Mounted Bypass Switch Installation
Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Risk of electrical shock.
Use the following procedure to hardwire the wall-mounted bypass switch:
Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:
UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*
8 kVA 60A 4 AWG (21.2 mm2)
10 kVA 80A 3 AWG (26.7 mm2)
12 kVA 100A 2 AWG (33.6 mm2)
15 kVA 100A 2 AWG (33.6 mm2)
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
42 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Wall-Mounted Bypass Switch Installation

UPS Wiring Access Cover
43 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Battery Connector · Conduit Landing

Wall-Mounted Bypass Switch Installation
See Figure 25 for a detailed view of the terminal strip label.

44 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Wall-Mounted Bypass Switch Installation
See Table 9 for specifications and Figure 26 for a detailed view of the UPS terminal block.
Input Ground TB1-1 8 AWG p
L1 TB1-3 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Output L1 TB1-6 3 AWG p
Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Ground TB1-9 8 AWG
*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
1 2 3 4 5 6 7 8 9
45 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Wall-Mounted Bypass Switch Installation
Secure each connection, tightening the terminal screws to a maximum 3.5 in lb (0.4 Nm). Provide strain relief for cables by installing plastic cable ties.

46 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Signal Cable

Wall-Mounted Bypass Switch Installation

47 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Wall-Mounted Bypass Switch Installation
48 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Use the holes and slots in the bottom of the bracket to attach the cabinet to the flooring if desired.
49 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com


“Extended Battery Module Installation” on page 51 to install
optional EBMs.
“Communication” on page 53 to install UPS communication
options, such as X-Slot cards or Remote Emergency Power-off.
“Operation” on page 65 to start up the UPS.
50 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Stabilizing the Cabinet · M4 Screws

If you are installing an optional EBM(s), use the following steps:
Disconnect the end of the ground strap farthest from the adjacent cabinet and retain the screw. Remove the screw from the adjacent cabinet’s connecting plate. Attach the loose end of the ground strap to the adjacent cabinet.
51 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Extended Battery Module Installation
“Communication” on page 53 to install UPS communication
options, such as X-Slot cards or REPO.
“Operation” on page 65 to start up the UPS.

52 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Ground Strap

This section describes the:
DB-9 communication port
LanSafe Power Management Software
Remote Emergency Power-off
Relay output contacts
Programmable signal inputs
Figure 32 shows the location of the communication options and control terminals on the UPS.

X-Slot Communication Bay #1
X-Slot Communication Bay #2
53 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

To access and install the communication options and control terminals:

54 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication


With wire cutters, cut either side of the tab and twist down to remove the tab (see Figure 35).

55 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication

See “Communication Options” on page 57 or “Control Terminals” on page 61 for detailed information.
Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. Be sure the cables fit in the access holes in the covers.

56 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication

The Powerware 9155 has serial communication capabilities through the DB-9 communication port or through an X-Slot card in one of the available bays. In addition, the LanSafe Power Management Software can be installed and used to communicate with the UPS via one of the serial communication connections.
The UPS supports two serial communication devices according to the following table:
X-Slot 1 X-Slot 2 DB-9 Communication Port
Any X-Slot card Any X-Slot card Not in use
Any X-Slot card Powerware Relay Interface Card Powerware Hot Sync CAN Card
Any X-Slot card Not in use Available
To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
57 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication · Independent Multiplexed · Available

The cable pins are identified in Figure 37 and the pin functions are described in Table 10. See Figure 32 on page 53 for serial port location.
Table 10. Communication Port Pin Assignment
Signal Name Function Direction from the UPS
2 TxD Transmit to external device Out
3 RxD Receive from external device In
5 GND Signal common (tied to chassis) —
X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 9155 has two available communication bays for any X-Slot card, including:
ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as
well as monitoring through a Web browser interface; connects to a twisted-pair Ethernet (10/100BaseT) network. It has a built-in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops. In addition, a Powerware Environmental Monitoring Probe can be attached to obtain humidity, temperature, smoke alarm, and security information.
Relay Interface Card - has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass.
Modbus® Card - allows you to continuously and reliably monitor the
UPSs in your Building Management System (BMS).
58 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication · Pin Number · t

Industrial Relay Card (IRC) - is used to indicate the operating status of
the UPS system using the customer’s monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm mode can be monitored.
Multi-Server Card - has six serial communication ports that can
communicate simultaneously with other computers using LanSafe Power Management Software (provided on the Powerware Software Suite CD).
Modem Card - provides out-of-band remote notification and
monitoring using modem communication directly to cell phones and pagers.
Single-Port Card - connects to the Powerware Expansion Chassis to
enable multiple communication options or to a PC for power management control.
ConnectUPS-MX SNMP Card - has Ethernet, modem, and SNMP
capabilities.
USB Card - connects to a USB port on your computer.
See Figure 32 on page 53 for the location of the two X-Slot communication bays.

59 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Each Powerware 9155 UPS ships with LanSafe Power Management Software and an interface cable. To begin installing LanSafe software, see the instructions accompanying the Powerware Software Suite CD.
LanSafe software provides up-to-date graphics of UPS power and system data and power flow. It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Powerware 9155 UPS battery power becomes low, LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
60 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication

The cables should be connected to the control terminals with cable clips. Input and output terminals have a functional isolation from terminal to terminal. They are connected to the UPS chassis through individual 1 MΩ resistors.
Signal Input 1 (Programmable)
Signal Input 2 (Programmable)
UPS Connectors (see Figure 32 on page 53)
61 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

REPO is used to shut down the UPS from a distance. This feature can be used for shutting down the load and the UPS by thermal relay, for instance in the event of room overtemperature. When REPO is activated, the UPS shuts down all converters, de-energizes all system relays, and fully powers down within 10-15 seconds.
There are two REPO positions that may be used, normally-open or normally-closed.
The pins on the normally-closed REPO connector are connected together. When this connection is open, the logic circuitry completely shuts down the UPS, thus preventing the power from supplying the load.
If the use of normally-closed REPO operation is desired, replace the connector with a normally-closed external switch (see Figure 32 on page 53).
If the use of normally-open REPO operation is desired, connect a normally-open external switch (see Figure 32 on page 53).
The REPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The REPO switch must have a minimum rating of 24 Vdc and 20 mA.
To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be disconnected from the UPS when the emergency power-off function is activated.
Wire Function Terminal Wire Size Rating Suggested Wire Size
REPO L1 12–22 AWG 18 AWG (0 82 mm2) L2
12–22 AWG (4–0.32 mm2) 18 AWG (0.82 mm2)
62 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication · REPO Connections

The UPS incorporates a programmable relay output with potential free contacts for remote alarm indications (see Figure 32 on page 53). An additional four relay outputs can be obtained with the X-Slot compatible Relay Interface Card.
The relay contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The relay contacts must have a maximum rating of 30 Vdc/1A and 60 Vdc/2A nominal values.
The UPS incorporates two programmable signal inputs (see Figure 32 on page 53). Use of non-polar (relay) control input is recommended. The pins must be shorted with maximum resistance of 10 ohm in order to activate the specific input.
The default and programmable settings for the signal inputs are shown in Table 11.
63 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication

Disable Bypass Operation If active, the automatic transfer to the static bypass is prevented.
Charger Off If active, the battery charge function is disabled. In a utility power outage, the discharge of batteries is supported.
Remote ON/OFF If active, the UPS output turns off regardless of the mode of operation. Auxiliary power, fan, communication, and rectifier/battery charger remain functional. Restart is initiated immediately when this signal is inactive.
Request Bypass If active, the UPS transfers to bypass if the bypass voltage, frequency, and synchronization are all okay.
Request Normal If active, the UPS transfers to inverter operation if not prohibited by REPO or an alarm condition.
Force Bypass If active, the UPS is forced to static bypass operation regardless of the bypass status.
External Battery Breaker Status If active, the UPS knows that the batteries are disconnected.
Building Alarm 1–6 These alarms can be activated separately or at the same time with other building alarms.
Not in Use Default
Shutdown If active, the UPS shuts down immediately.
Delayed Shutdown If active, the UPS shuts down after a user-configured delay time. Default shutdown delay is 120 seconds. The UPS automatically restarts when the signal changes to inactive.
Normal/Bypass If active, the UPS transfers to bypass if okay. If inactive, the UPS transfers to the inverter when possible.
On Generator If active, the UPS knows that input is fed from the generator. Bypass is disabled; the automatic battery test is disabled.
This option is not used.
64 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Communication · Signal Description · External Transformer Overtemperature

This chapter contains information on how to use the Powerware 9155, including front panel operation, UPS startup and shutdown, and operation of the Maintenance Bypass switch.
The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 40).
Power On Indicator (Green) On Battery Indicator (Yellow)
Control Buttons for the LCD Menu Options
65 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Bypass Indicator (Yellow) · Alarm Indicator (Red)

The following table shows the indicator status and description.
On The UPS is operating normally.
Green Flashing S The UPS is starting up or is shut down and waiting for power to return. S A new information message is active. S Bypass is not available.
Off The UPS is turned off and will not turn on automatically.
On The UPS is in Battery mode.
On The UPS is in Bypass mode.
On The UPS has an active alarm.
Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 91 for additional information.
Press and hold the first button on the left for approximately five seconds to select the language menu. This action is possible from any LCD menu screen.
As the default or after 15 minutes of inactivity, the LCD displays the selectable startup screen. The default is the Eaton Powerware logo and can be changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu structure. Press the button to enter a submenu. Press the button to select an option. Press the ESC button to cancel or return to the previous menu.
66 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

The following table shows the basic menu structure.
Main Menu Submenu Display Information or Menu Function
UPS Status UPS off / System normal / UPS supporting load / UPS on battery / UPS on bypass / Active alarm list / Battery status
Event Log Displays up to 100 events and alarms
Measurements Output L-N and L-L / Current / Frequency / Power
Battery Voltage / Current / Runtime
Input L-N and L-L / Current / Frequency
Bypass L-N and L-L / Frequency
Control Go to Bypass Mode Forces the UPS to go to Bypass When this command is active, the option changes to Go to Normal Mode.
Start Battery Test Initiates a battery test
Display Test Four different selectable tests for the front panel functions: the LEDs cycle through, the alarm beep sounds, the backlight turns off and on, and the pixels scroll through to test the LCD.
Settings User Settings See Table 13 for detail. g
Service Settings This screen is password-protected.
Identification UPS Type / Part Number / Serial Number / Firmware / Display / CAN Bridge
Turn UPS ON/OFF ON and OFF Options
67 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

The following table displays the options that can be changed by the user.
Description Available Settings Default Setting
Set Date and Time Set Month Date: mm/dd/yyyy Time: 24:00
01/01/2003 00:00
Display Contrast Adjust contrast with up/down arrow buttons
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4] Setup: [Battery Low] [On Battery] [On Bypass] [UPS ok] [custom] [empty]
Alarm 1: UPS ok X-Slots (1 or 2) #1: On Battery #2: Battery Low #3: UPS ok #4: On Bypass
Signal Inputs [empty] [Logic] (see “Programmable Signal Inputs” on page 63)
Parallel Operation Settings Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User’s Guide.
Start Screen Eaton Powerware logo Mimic Screen
User Password Enabled/Disabled If Enabled is selected, the password is USER.
Audible Alarms Normal Sound/Disabled Normal Sound
Battery Charging ABM cycling/constant ABM cycling
68 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Default Setting Available Settings Description
Automatic Battery Tests Enabled/Disabled Enabled automatically runs the battery test once a month.
Number of Battery Strings 0 through 22 (see “Configuring the UPS for EBMs” on page 75)
2 strings for UPS-32 models 4 strings for UPS-64 models
Battery Capacity 1 through 65535 watts per cell 34 W/cell
Battery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell
Set Nominal Output Voltage 120V/240V 120V/208V 110V/220V 100V/200V 127V/220V
Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%
Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%
Nominal Output Frequency 50 Hz or 60 Hz 60 Hz
Synchronization Window ±0.5 through ±3.0 Hz (0.1 Hz increments)
±2.0 Hz
Unsynchronized Transfer to Bypass Allowed/Not Allowed Not Allowed
Usage of Bypass Enabled/Disabled Enabled
Transfer to Bypass When Overload After a delay/Immediately After a delay
Automatic Start Delay -1 through 32767 seconds (-1 means disabled)
Automatic On Battery Shutdown Delay
-1 through 32767 seconds (-1 means disabled)
Control Commands from X-Slot1 Allowed/Disabled Allowed
Control Commands from X-Slot2/Serv
X-Slot Signal Input Activation Delay
0 through 65 seconds 5s
Input signal delayed shutdown delay
1 through 65535 seconds 120s
69 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Default Setting Available Settings Description
Site Wiring Fault Notice Enabled/Disabled Enabled
Reset Custom Event Settings 0 through 32 Empty
Full Power Battery Test Enabled/Disabled Enabled
Auto Output Configuration Enabled/Disabled Enabled for initial startup Disabled after initial startup
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Verify that UPS installation has been carried out correctly and the UPS ground has been connected.
If you have an optional Maintenance Bypass Module or Power Distribution Module, you can start up the UPS in maintenance bypass, allowing utility power to supply the load.
To start up the UPS in maintenance bypass:
70 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

To switch to Normal mode from maintenance bypass:
The UPS starts up in Bypass mode, with the load still powered by utility power.
To start up the UPS in Bypass mode without an MBM/PDM:
The indicator flashes.
71 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

The indicator stops flashing.
The and indicators illuminate, indicating the UPS is operating in Bypass mode. The load is now powered by utility power.
To switch to Normal mode from internal Bypass mode:
To start up the UPS:
The indicator flashes.
The indicator stops flashing.
72 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

The indicator illuminates. The UPS is now powering the load.
If the indicator is flashing, check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.
73 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

To start the UPS on battery:
The UPS starts within two minutes. The UPS supplies power to your equipment and goes into Battery mode.
74 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
All 2-High UPS and EBM Cabinets* Number of Strings
UPS + 2 EBMs 10
UPS + 3 EBMs 14
UPS + 4 EBMs 18
All 3-High UPS and EBM Cabinets* Number of Strings
UPS + 2 EBMs 16
UPS + 3 EBMs 22
*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings. UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.
75 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

To shut down the UPS:
The input contactor opens.
The UPS is disconnected from the batteries and is on logic power only.
76 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Operation

This section explains how to:
Care for the UPS and batteries
Recycle used batteries
Use the Maintenance Bypass switch
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 77°F (25°C).
When storing the UPS and optional cabinets, the following requirements should be met:
Verify that the battery circuit breaker is in the OFF position.
Avoid temperature and humidity extremes. To maximize battery life,
the recommended storage temperature is 59°F (15°C) to 77°F (25°C).
If you store the UPS for a long period, recharge the batteries every
10 months by applying utility power. The batteries charge to 80% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the
date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative.
77 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

When the indicator flashes and the LCD panel displays Battery Failure, the batteries may need replacing. Contact your service representative to order new batteries.
Change the batteries approximately every five years.
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
78 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Maintenance

The UPS-mounted Maintenance Bypass switch is part of the optional Maintenance Bypass Module or Power Distribution Module and is located on the back of the UPS (see Figure 41).

The UPS-mounted bypass switch has three positions as described in Table 14.
UPS Connects the UPS output to the load.
SERVICE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected to the UPS input.
BYPASS Like the SERVICE position, BYPASS connects the load directly to AC input power and disconnects UPS output. However, because BYPASS also disconnects AC input from the UPS, this is the appropriate position for UPS maintenance or repair.
79 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Maintenance · Switch Position Description

Figure 42 shows a UPS with a separate battery cabinet and a UPS-mounted bypass switch.
UPS
UPS
UPS EBM
Figure 42. Typical Hardwired Installation with UPS-Mounted Bypass Switch
80 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

To switch the UPS to maintenance bypass from Normal mode (UPS-mounted operation):
The battery circuit breaker trips, and the UPS is now bypassed, with the load powered by utility power.
To return to Normal mode from maintenance bypass (UPS-mounted operation):
The UPS starts up in Bypass mode, with the load still powered by utility power.
81 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Maintenance

The wall-mounted bypass switch is rated at 80A/300 Vac and has four positions as described in Table 15.
UPS Connects the UPS output to the load.
LINE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected to the UPS input.
SERVICE Like the LINE position, SERVICE connects the load directly to AC input power and disconnects UPS output. However, because SERVICE also disconnects AC input from the UPS, this is the appropriate position for UPS maintenance or repair.
OFF Disconnects the load from the UPS output power and AC input power, as well as AC input power to the UPS input.
You must press the red button beside the switch before turning the Maintenance Bypass switch.

82 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Maintenance · Switch Position Description

Figure 44 shows a UPS with a separate battery cabinet and a wall-mounted bypass switch.
UPS
UPS
UPS EBM
Figure 44. Typical Hardwired Installation with Wall-Mounted Bypass Switch
83 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

To switch the UPS to maintenance bypass from Normal mode (wall-mounted operation):
The battery circuit breaker trips, and the UPS is now bypassed, with the load powered by utility power.
To return to Normal mode from maintenance bypass (wall-mounted operation):
The UPS starts up in Bypass mode, with the load still powered by utility power.
84 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
UPS Maintenance

This section provides the following specifications for the Powerware 9155 models:
Dimensions and weights
Environmental and safety specifications
UPS Description Power Rating
PW9155-8-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 8 kVA, 7.2 kW
PW9155-10-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 10 kVA, 9 kW
PW9155-12-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 12 kVA, 10.8 kW
PW9155-15-32 2-high: UPS with one battery section 3-high: UPS with one battery & one input isolation transformer section 15 kVA, 13.5 kW
85 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Dimensions (H x W x D) Weight
2-High UPS 32.2” × 12” × 32” (81 × 30 × 81 cm) 352 lb (160 kg)
3-High UPS-32 47.8” × 12” × 32” (121.5 × 30 × 81 cm) 550 lb (250 kg)
3-High UPS-64 47.8” × 12” × 32” (121.5 × 30 × 81 cm) 590 lb (268 kg)
2-High EBM 32.2” × 12” × 30.3” (81 × 30 × 77 cm) 480 lb (218 kg)
3-High EBM 47.8” × 12” × 30.3” (121.5 × 30 × 77 cm) 710 lb (322 kg)
PDM (rear UPS mount) 16.5” × 12” × 7” (42 × 30 × 17.8 cm) 25 lb (11 kg)
MBM (rear UPS mount) 16.5” × 12” × 7” (42 × 30 × 17.8 cm) 18 lb (8 kg)
Operating Temperature 10°C to 40°C (50°F to 104°F) Optimal battery performance: 25°C (77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Storage Temperature 0°C to 25°C (32°F to 77°F) Recommended battery storage: 59°F (15°C) to 77°F (25°C)
Ventilation Front air intake, forced air, two fans, positive pressurization,
Altitude 9,843 ft (3,000m) operating without derating 32,810 ft (10,000m) during transportation
Relative Humidity 5–95% noncondensing
Heat Dissipation 5582 BTU/hr maximum online 5294 BTU/hr maximum on battery
Audible Noise
Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3; EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1
Agency Markings UL, cUL, CE, NOM-NYCE
EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003, VCCI
Surges IEEE/ANSI C62.41 Cat B3
86 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Specifications · temperature UPS-monitored

Technology Online, double-conversion, split-phase topology with Static Bypass switch and
optional 3-position Maintenance Bypass switch.
Frequency independent operation.
Input Voltage Range 75–144 Vac per phase
Input Isolation Transformer Input Voltage Range
208V or 240V ±20%
Input Power Factor >0.99 at full load nominal line conditions
Input Rated Voltage 100/200, 110/220, or 120/240 Vac with 180° phase displacement 120/208 or 127/220 Vac with 120° phase displacement
Input Frequency Range 45–65 Hz
Input Rated Frequency 50/60-Hz selectable, auto-configuring
±1% static, Phase to Neutral
±2% static, Phase to Phase ±5% dynamic at 100% resistive load change
Response time
Output Frequency 50/60-Hz selectable or auto-configuring
Frequency/phase-converter operation with derated output load capacity to 80%;
Frequency Conversion mode can be configured through the front panel or
through XCP commands. Bypass is not available in Frequency Conversion mode.
Output Overload 101–110% for 10 minutes 111–125% for 60 seconds 126–149% for 5 seconds >150% for 300 milliseconds
87 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com


Output kVA (line–line loads) 12.5 13.8 15.0 13.0 13.0
Output kVA (line–neutral loads) 12.5 13.8 15.0 15.0 15.0
Output kVA (line–line loads) 12.0 12.0 12.0 10.4 10.4
Output kVA (line–neutral loads) 12.0
*Input current for the input isolation transformer is 4% higher than for the UPS.
88 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Specifications


Output kVA (line–line loads) 10.0 10.0 10.0 8.7 8.7
Output kVA (line–neutral loads) 10.0
Output kVA (line–line loads) 8.0 8.0 8.0 6.9 6.9
Output kVA (line–neutral loads) 8.0
*Input current for the input isolation transformer is 4% higher than for the UPS.
89 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Specifications

Battery Type 9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float service life at 77°F (25°C), voltage 192 Vdc (96 cells per string)
Number of Strings Maximum of 22 strings per full configuration, including UPS batteries (4 EBM-64
cabinets or 3 EBM-96 cabinets, plus UPS batteries)
Battery Replacement Must be replaced by qualified service technician
Charger Service configurable 0.5–34A per string, with overall maximum of 34A (limited by
Charging Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage after full load discharge External battery: no more than 10x discharge time to 90% usable capacity at nominal line voltage after full load discharge
Start-on-Battery Allows start of UPS without utility input
Performance ABM technology increases battery service life, optimizes recharge time, and
provides a warning before the end of useful battery life
Protection Extended Battery Module output protected by 100A circuit breaker
Load 32 Internal UPS Batteries (1) EBM-64 (2) EBM-64 (3) EBM-64 (4) EBM-64
15 kVA/13.5 kW 4 23 43 65 88
12 kVA/10.8 kW 6 30 56 85 116
10 kVA/9 kW 8 37 69 106 144
8 kVA/7.2 kW 11 49 91 139 189
Load 64 Internal UPS Batteries (1) EBM-96 (2) EBM-96 (3) EBM-96
15 kVA/13.5 kW 13 43 76 113
12 kVA/10.8 kW 18 56 101 149
10 kVA/9 kW 22 69 124 184
8 kVA/7.2 kW 29 91 164 242
90 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Specifications · 2-High Cabinets · 3-High Cabinets

The Powerware 9155 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user. Use the following troubleshooting chart to determine the UPS alarm condition.
The following table describes typical alarms and conditions; check the Event Log through the control panel for a list of active alarms. If an alarm appears with a service code, please contact the help desk (see page 93).
Alarm or Condition Possible Cause Action
A utility failure has occurred and the UPS is in Battery mode.
The UPS is powering the equipment with battery power. Prepare your equipment for shutdown.
LED is on. 1 beep every second.
The battery is running low. Five minutes or less of battery power remains (depending on load configuration and battery charge). Save your work and turn off your equipment. When utility power is restored, the UPS restarts automatically, provides power to the load, and charges the battery.
LED is on. Continuous beep for 10 seconds.
The UPS does not recognize the internal batteries.
Verify the battery circuit breaker is in the ON position. If the condition persists, contact your service representative.
LED is on. 1 beep every second.
91 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
On Battery · Battery Low · Battery Breaker

Action Possible Cause Alarm or Condition
Power requirements exceed the UPS capacity (greater than 100% of nominal; see page 87 for specific output overload ranges).
Remove some of the equipment from the UPS. The UPS continues to operate, but may switch to Bypass Mode if the load increases. The alarm resets when the condition becomes inactive.
LED is on. 1 beep every second.
UPS internal temperature is too high or the fan has failed.
If you have an optional Maintenance Bypass Module or Power Distribution Module, turn the Maintenance Bypass switch to the SERVICE position. Otherwise, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. If the alarm disappears, turn the Maintenance Bypass switch back to the UPS position (or restart the UPS if you do not have a switch). If the condition persists, contact your service representative.
LED is on. 1 beep every second.
Battery test failed The batteries need service. Contact your service representative.
The UPS does not
The main utility breaker is off. Verify that the main utility breaker is on. start. If an optional isolation transformer is installed, the input circuit breaker is off.
Verify that the isolation transformer input circuit breaker is on.
The Remote Emergency Power-off switch is active or the REPO connector is missing.
Reset the REPO switch and restart the UPS. Verify that the REPO connector is present.
Power is not available at the UPS output receptacles.
The UPS is in Standby mode. Supply power to the connected equipment: Press any button on the front panel display to activate the menu options. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu. Select the ON option. Press and hold the button for three seconds, until the UPS stops beeping.
The UPS does not provide the expected backup time.
Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service representative. p
The batteries need charging or service.
Battery circuit breakers are in the OFF position.
Switch all battery circuit breakers to the ON position.
92 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition.
Press any button on the front panel display to silence the alarm. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing.
If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
Please have the following information ready when you call for service:
Firmware version number
Date of failure or problem
Symptoms of failure or problem
Customer return address and contact information
93 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Troubleshooting · Model number · Serial number

(US and Canada)
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).
LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original end-user (the “End-user”) of any Powerware 9150, 9155, 9170+, and FERRUPS 4.3–18 kVA Products (individually and collectively, the “Product”) purchased on or after June 1, 2004 and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-user.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for the Product installed [and currently located] in the fifty (50) United States, the District of Columbia, and Canada is twenty-four (24) months from the date of purchase for parts and ninety (90) days from the date of purchase for parts and labor, as further clarified in the following sections.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually and collectively, the “Warranted Items”) are free of defects in material and workmanship. If, in the opinion of Company, a Warranted Item is defective and the defect is within the terms of this Warranty, Company’s sole obligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor, as applicable), at the option of Company, and such repair or replacement shall be at either the End-user’s location, Company’s site, or such other location as determined by Company. All Warranted Items returned to Company and all parts replaced by Company shall become the property of Company. Expenses for any labor to repair the Warranted Item beyond the initial ninety (90) days are the sole responsibility of the End-user
PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS when shipment is required of End-user: When Company determines that the Warranted Item will be repaired or replaced at a Company site or such other location, and the End-user must ship to Company the defective Warranted item, the following procedures are required.
If the Warranted Item is to be replaced by Company, and the End-user supplies a credit card number or purchase order for the value of the replacement product, Company will use commercially reasonable business efforts to ship (via standard ground shipment and at no cost to the End-user) the replacement Warranted Item to the End-user within one (1) business day after Company receives notice of the warranty claim. In such case, the End-user must return (at Company’s expense) the defective Warranted Item to Company in the same packaging as the replacement Warranted Item received by the End-user or as otherwise instructed by Company. If Company does not receive the defective Warranted Item, Company will either charge the End-user’s credit card, or send the End-user an invoice (which the End-user agrees to pay), for the value of the replacement product.
If the Warranted Item is to be replaced by Company, but the End-user is unwilling or unable to supply a credit card number or purchase order for the value of the replacement product, Company will use commercially reasonable business efforts to ship (via standard ground shipment and at no cost to the End-user) the replacement Warranted Item to the End-user within one (1) business day after Company receives the defective product from the End-user.
94 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Two-Year Limited Warranty

In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for return of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that are replaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced by Company shall become the property of Company.
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Warranty is not valid if the Product’s serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO END-USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE, NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE LIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
LIMITATION OF LIABLITY: The remedies of the End-user set forth herein are exclusive and are the sole remedies for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract, in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of customers of the End-user or any special, indirect, incidental or consequential damages whatsoever. The total cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort (including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s reasonable control.
END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-user must use the Product in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect.
95 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Two-Year Limited Warranty

Extended Ten-Year Pro-Rated Limited Warranty
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End-user.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3028. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Applies only to original purchasers for end use in the United States and Canada who file the Warranty Registration Card
9125, 9155, 9170+, and FERRUPS
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).
LIMITED WARRANTY: This pro-rated limited warranty (this “Warranty”) applies only to the original End-user (the “End-user”) of any Powerware 5115, 5125, 5140, 9104, 9120, 9125, 9155, 9170+, and FERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-user.
WHAT THIS WARRANTY COVERS: In addition to the standard Two-Year Limited Warranty covering the applicable Product, the warrantor warrants that the Product will have a service life (defined below) of Ten years from the date of purchase (the “Ten-Year Service Life”) when used in accordance with the storage, handling, installation, operation and maintenance procedures prescribed in the Product’s operation and maintenance manual. “Service life” means the Product’s ability to deliver at least 80% of its original rated backup time.
If Company finds, in its sole discretion, that any Product has not provided the Ten-Year Service Life, Company will, as its sole obligation and the End-user’s sole remedy for Company’s breach of this warranty, repair or replace the Product, at its option, F.O.B. Company’s factory, for a charge, payable by the End-user to Company pro-rated on the following basis:
96 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

The End-user will be allowed a credit against Company’s list price of equivalent equipment at the time of return of the Product to Company, in proportion to the percentage of Ten-Year Service Life remaining at the time of return of the Product to Company. In calculating the available credit, the remaining portion of the Ten-Year Service Life will be rounded up or down to the nearest whole year. The End-user will assume responsibility to pay the balance of the list price; and Company reserves the right to require payment prior to delivery of the repaired or replacement equipment.
For the avoidance of doubt, Company’s responsibilities under this Warranty are as follows:
Years 1-2 - Product repaired or replaced pursuant to terms of Limited Warranty
Years 3-10 - Credit ($) = Current List Price × Years of Unexpired Life 10 Years of Warranted Life
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Warranty is not valid: (a) unless the End-user returns to Company the Warranty Registration Card within thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO END-USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE, NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE LIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
97 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
ExtendedTen-YearPro-RatedLimitedWarranty

Extended Ten-Year Pro-Rated Limited Warranty
LIMITATION OF LIABLITY: The remedies of the End-user set forth herein are exclusive and are the sole remedies for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract, in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of customers of the End-user or any special, indirect, incidental or consequential damages whatsoever. The total cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort (including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s reasonable control.
END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-user must use the Product in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End-user.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3028. Company will not accept any product for return, credit or exchange unless expressly authorized by Company in writing and delivered FOB Company factory. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
98 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

and FERRUPS (US and Canada)
GUARANTOR: The guarantor for the load protection guaranty set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).
LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-user (the “End-user”) of any Powerware 3110, 3115, 5115, 5125, 9120, 9125, 9150, 9155, 9170+, and FERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Guaranty applies even in the event that the Product is initially sold by Company for resale to an End-user.
WHAT THIS GUARANTY COVERS: For the lifetime of the Product, guarantor promises to repair or replace, at guarantor’s option, the equipment (valued up to the limits shown below*) that is damaged by an AC power line surge, spike, or other transient when properly connected to guarantor’s uninterruptible power system (“UPS”). Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the following circumstances arise:
*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:
$25,000 for Powerware Models 3110 and 3115
$150,000 for Powerware Models 5115 and 5125
$250,000 for Powerware Models 9120, 9125, 9150, 9155, 9170+, and FERRUPS products
WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-user’s equipment does not include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Guaranty is not valid: (a) unless the End-user returns to Company the Warranty Registration Card within thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible.
99 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Load Protection Guarantee

Company shall not be responsible for any charges for testing, checking, removal or installation of any items.
LIMITATION OF LIABILITY: THE REMEDIES OF THE END-USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER. EXCEPT AS OTHERWISE PROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE PRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE, LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OF CAPITAL, CLAIMS OF CUSTOMERS OF THE END-USER OR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES WHATSOEVER. THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE BASED IN CONTRACT (INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE, SHALL NOT EXCEED THOSE SET FORTH ABOVE. Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes beyond Company’s reasonable control.
END-USER’S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End-user must use the Product in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Company’s obligations under this Guaranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Guaranty.
COSTS NOT RELATED TO GUARANTY: The End-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Guaranty will be borne by the End-user.
TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3028. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
100 Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com