User’s Guide
02/20/2001

The Powerware9 9 Prestige Series UPS configurations vary. Some configurations may or may not be classified by the Federal Communications Commission (FCC). If your Prestige unit is classified by these standards, the corresponding information applies: Class A NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment in a residential area is likely to cause interference in which case the user will be required to correct the interference at his own expense. Class B NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: : Reorient or relocate the receiving antenna. : Increase the separation between the equipment and receiver. : Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. : Consult the dealer or an experienced radio/TV technician for help.
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies: WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take additional measures.
Units that are labeled with a CE mark comply with the following EU directives:
73/23/EEC Council Directive on equipment designed for use within certain voltage limits. 93/68/EEC Amending Directive 73/23/EEC. 89/336/EEC Council Directive relating to electromagnetic compatibility.
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452661 Fax: +358-9-452-66395
Powerware, PowerPass, Powercare, OnliNet, and OnliSafe are registered trademarks of Powerware Corporation. IBM and AS/400 are registered trademarks of International Business Machines Corp. Novell is a registered trademark of Novell, Inc. 3Com is a registered trademark of 3Com Corporation.
.Copyright 1993-99 Powerware Corporation, Raleigh, North Carolina, U.S.A. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.



1 Introduction 1
UPS Model and Battery Configurations 2 Load Requirements 2 Battery Times 3 Special Symbols 7 2 Safety Warnings 9
Sikkerhedsanvisninger 10 Belangrijke Veiligheidsinstructies 12 Tarkeita Turvaohjeita 13 Consignes de sécurité 15 Sicherheitswarnungen 16 ÐñïåéäïðïéÞóåéò ÁóöÜëåéáò 18 Avvisi di sicurezza 20 Viktig Sikkerhetsinformasion 21 Regulamentos de Segurança 23 Предупреждения по мерам безопасности 24 Advertencias de Seguridad 26 Säkerhetsföreskrifter 27 3 Installation 29
Unpacking and Inspection 29 UPS and Battery Cabinet Storage 29 UPS and Battery Cabinet Installation 29 UPS Startup for 120V Models 31 UPS Startup for 208V-240V Models 32 Troubleshooting Tips 34 4 UPS Operation 35
UPS Front Panel 35 Operating Modes 36 Normal Mode 36 Bypass Mode 37 Battery Mode 37
i Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Diagnostics 38 Battery Test on Demand 38 Battery Start 39 UPS Shutdown 39 Changing the Output Voltage 39 Using the PowerPass 40 Using Maintenance Bypass 41 5 Communication 45
Initial Communications Settings 45 Front Panel Communications Access 46 UPS Serial Communications Menu 48 Power Management Software 51 UPS Communications Interface Port 52 Communications Mode Reference Chart 53 6 Specifications 55
Prestige UPS Model Specifications 55 Prestige UPS Physical Specifications 56 Prestige UPS Technical Specifications 56 7 Troubleshooting 57
Resetting the UPS 59 Silencing the Alarm 59 Service and Support 60 Index 61
ii Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Table of Contents

Congratulations on the purchase of your Powerware9 9 Prestige Series uninterruptible power system (UPS). The Prestige UPS meets the toughest measures of superior design and manufacturing, including ISO 9001. You now own the most reliable power protection available.
The Prestige provides a steady, well-regulated power supply for your computing and communications equipment, while protecting it from the frequent irregularities that are inherent in commercially available power. Voltage spikes, power surges, brownouts, and power failures have the potential to corrupt critical data, destroy unsaved work sessions, and in some instances, damage expensive hardware.
With the Prestige, you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment. The optional PowerPass9 has a Maintenance Bypass feature that supplies power to your equipment even when the UPS electronics are removed for maintenance or upgrades. Figure 1 shows the Prestige UPS.
Figure 1. Prestige UPS
1 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

This UPS is designed to work with single-phase, three-wire, AC power sources. There are two important considerations when selecting the UPS model and battery configuration to properly safeguard your equipment:
: Load requirements
: Battery times
Load Requirements The load is the equipment to be protected by the UPS. Select the UPS model that meets the power consumption requirements of the load in volt-amperes (VA). The total load VA should not exceed the UPS VA rating. To determine the total load requirements:
If the rating is in amperes or amperes max, multiply by the input voltage to obtain the VA requirement.
2 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction

MODEM
100 WATTS 2 AMPS 50 VA
100 WATTS x 1.4 = 140 VA 2 AMPERES x 120 = 240 VA 50 VA
or 1 AMPERE x 240 = 240 VA
140 VA + 240 VA + 50 VA = 430 VA (Total Load Requirements)
Figure 2. Volt-Amperes Calculation Example
If the total load requirements of the equipment exceeds the capacity of the UPS, you must either reduce the number of pieces of equipment, or use a UPS with a larger load capacity.
When deciding on which pieces of equipment to remove from the UPS, select equipment that has a lower priority for power protection. Computers, monitors, and modems typically have a higher priority because they could be processing or transmitting data when a power outage occurs.
Battery Times During a power failure, the UPS battery supplies power to your equipment, providing time to complete computing activities prior to UPS shutdown. The duration of this time period is directly related to the UPS battery configuration. By adding battery cabinets (EXT models only), you can customize the UPS to provide enough battery time for normal processing activities.
The rating label on the UPS rear panel shows the model number. Model numbers with a “P2” are EXT units; numbers with “HV” are high voltage units (208 - 240V models). The following tables show the average battery times by product model.
3 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction


Load (VA) at Load Internal UPS Batteries (Rounded to the Nearest Minute) (VA) at
(W) 650 800 1000 750 EXT 1000 EXT 1250 EXT 1500 EXT
200 140 37 37 37 68
400 280 22 22 22 32
600 420 12 12 12 20
800 560 8 8 15A 14 14 14
External Battery Cabinet Configurations for EXT Models Load (VA) at
200 140 143 216 290 364 438 513 589 663
400 280 69 115 158 198 239 280 320 362
600 420 43 73 105 137 165 194 221 249
750 525 33 56 80 106 134 156 178 202
1000 700 23 39 57 75 95 114 135 151
1250 875 17 30 42 56 70 86 102 118
1500 1050 14 23 32 43 55 67 78 91
*Typical Power Factor (PF); A750 VA, 525W
4 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction


Prestige 600 - 1250 VA, 208 - 240V Models
Internal UPS Batteries (Rounded to the Nearest Minute) (VA)
200 140 133 203 274 346 418 491 564 637
400 280 70 117 159 201 243 285 328 371
600 420 46 76 110 141 171 200 230 260
800 560 33 55 79 105 132 153 176 199
1000 700 25 42 61 81 102 124 147 161
1250 875 19 32 46 61 77 94 111 129
*Typical Power Factor (PF)
5 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction

200 140 59 128 194 260 327 393 460 527 595
400 280 29 64 107 149 186 224 263 302 339
600 420 19 42 71 102 135 161 189 217 244
800 560 14 32 52 76 100 125 148 169 191
1000 700 11 24 41 59 77 98 119 138 156
1250 900 8 19 32 45 59 76 92 108 125
1500 1050 7 14 25 36 48 60 73 86 101
1800 1200 5 12 20 29 38 48 59 69 80
*Typical Power Factor (PF)
6 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction

The following common symbols may be found on the UPS:
LOAD ON - Press the button with this symbol to energize the output receptacles (Output On).
LOAD OFF - Press the button with this symbol to de-energize the output receptacles (Output Off).
SAFETY EARTHING TERMINAL - Indicates the primary safety ground.
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
This symbol indicates that the UPS batteries should not be discarded in the trash. The UPS contains sealed lead batteries and must be disposed of properly. For battery replacement or removal, call your Local Distributor or the Help Desk at one of the telephone numbers on page 60.
7 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction

8 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Introduction

current. Observe proper precautions.
: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
: This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
: Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
: Never open or mutilate batteries. Released electrolyte is harmful to the skin and
eyes, and may be extremely toxic.
: Use only the power supply cord provided with this UPS. The power cord is wired in
accordance with National Electrical Code (NEC) specifications. Be sure the wall outlet to be used with the UPS is wired in accordance with these same specifications in order to avoid damage to your equipment. Be sure that overcurrent protection for the AC outlet is provided at the time of installation. Be sure the input plug is completely inserted into the wall outlet. Use a single-phase, three-wire, grounded AC outlet only.
: To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants.Ambient temperature must not exceed 104F (40C). Do not operate near water or excessive humidity (95% max).
9 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

: Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
: To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current greater than 2.75 milliamperes.
: The wall outlet must be within 2 meters of the equipment and accessible to the
operator. The on/off switch on the UPS does not electrically isolate the internal parts. Unplug the input cord from the wall outlet when disconnecting the unit for long periods of time.
: Please note that the output sockets on the UPS are electrically live whenever the
UPS Output On button is pressed, even if the input cord is disconnected.
FARE Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres af brugeren.
kortslutningsspænding. De korrekte forholdsregler bør overholdes.
: Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
: Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
: Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere
ved åben ild.
: Batterierne bør aldrig åbnes eller skilles ad. Elektrolyt, der slipper ud, er skadelig
for hud og øjne og kan være overordentlig giftig.
10 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Safety Warnings

: Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben.
: Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 2,75 milliampère hebben.
: De hoofdvoedingcontactdoos moet zich op minder dan 2 meter van de apparatuur
bevinden en makkelijk bereikbaar zijn voor de gebruiker. De aan/uit-schakelaar op de UPS biedt geen elektrische isolatie voor de inwendige onderdelen. De stekker uit de voedingcontactdoos halen wanneer het apparaat voor lange tijd niet wordt gebruikt.
: Neem er nota van dat de uitgangaansluit punten op de UPS altijd onder stroom
staan wanneer de belastingschakelaar ( | ) wordt ingedrukt, ongeacht de aanwezigheid van de voeding.
VAARA Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
oikosulkuun. Noudata asianmukaisia ohjeita.
: Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia
määräyksiä.
: Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.
: Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
: Älä avaa tai riko akkuja. Paljastunut elektrolyytti on vahingollinen iholle ja silmille
ja voi olla erittäin myrkyllistä.
13 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Safety Warnings

: Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.
: Afin d’être conforme aux normes et règlements internationaux de câblage, le
courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 2,75 mA.
: La prise secteur doit se trouver à moins de 2 m du matériel et être accessible à
l’utilisateur. L’interrupteur de ON/OFF (marche/arrêt) de l’onduleur n’assure pas l’isolation électrique des pièces internes. Débrancher le cordon d’alimentation de la prise secteur en cas de déconnexion de l’appareil pendant une période prolongée.
: Noter que les prises de sortie de l’onduleur sont sous tension lorsque Output On buttonest enfoncé, même si le cordon d’alimentation est débranché de la prise secteur.
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten.
: Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen
Bestimmungen zu beachten.en.
: Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist.
: Batterien niemals verbrennen, da sie explodieren können.
: Batterien nie öffnen oder anderweitig beschädigen. Der darin enthaltene Elektrolyt
wirkt ätzend auf Haut und Augen. Es besteht Vergiftungsgefahr!
16 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Safety Warnings

: No retire o desenchufe el cable de entrada mientras el SIE se encuentre
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.
: Para cumplir con los estándares internacionales y las normas de instalación, la
totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 2,75 miliamperios.
: El tomacorriente debe encontrarse a menos de 2 metros del equipo y ser accesible
para el operador. El interruptor de encendido/apagado del SIE no tiene aislación eléctrica de las partes internas. Desenchufe el cable de entrada del tomacorriente de la pared cuando desconecte la unidad durante períodos largos.
: Tenga en cuenta que los receptáculos de salida del SIE tienen corriente eléctrica
siempre que se oprime el botón pulsador de conexión de salida del SIE (Output ON), aun cuando el cable de entrada esté desconectado.
FARA Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.
VIKTIGT: Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.
Följ tillämpliga anvisningar.
: Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.
: Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.
: Använda batterier får aldrig brännas upp. De kan explodera.
: Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig för hud
och ögon och kan vara mycket giftig.
27 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Safety Warnings

The following sections describe UPS storage requirements and the installation and startup of the UPS.
Carefully unpack the UPS and optional battery cabinets, making sure to retain the packaging materials. Examine each unit carefully for any signs of damage and immediately notify your distributor if damage is present.
UPS and Battery Cabinet Storage If you plan to store the UPS or battery cabinets prior to use, store them in a cool, dry environment. Storage temperature should not exceed 35C (95F) in order to preserve battery life. For longer term storage, energize the UPS and battery cabinet for approximately 8 hours every 90 days in order to maintain battery charge.
Whenever the units are not energized, verify the circuit breaker on all battery cabinets is returned to the OFF (O) position (see Figure 4 on page 31).
Use the following procedure to install the UPS and optional battery cabinets:
Steps 2 through 7 are for battery installation. If you do not have optional battery cabinets, skip to “UPS Startup for 120V Models” on page 31 or “UPS Startup for 208V-240V Models” on page 32.
You can install additional battery cabinets while the UPS is operating, but confirm the UPS is not in Battery mode (see page 37).
29 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

UPS Cabinet Battery Cabinet Stacked Cabinets Side-by-Side Cabinets
Figure 3. Cabinet Setup
30 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

UPS Cabinet Battery Cabinet
Battery Input Connector Battery Output Connector External Battery Connector
Figure 4. Typical UPS Rear Panel
UPS Startup for 120V Models To start up the UPS for 120V models:
The UPS performs diagnostic tests and enters Normal mode with the equipment (load) offline. The indicator remains lit. The startup should take about 15 seconds.
31 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements. The optional PowerPass has a surge-protected receptacle for laser printers.
The indicator remains lit and the Self Test indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 36 for more information.
UPS Startup for 208V-240V Models To start up the UPS for 208V, 220V, 230V, or 240V models:
Release the Output Off button when the alarm beeps.
All indicators flash simultaneously.
32 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Installation

Two indicators, corresponding with the current setting, remain flashing. The output voltage is factory-configured for 230V.
220V 230V 240V 208V
Figure 5. Output Voltage Indicators
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements. The optional PowerPass has a surge-protected receptacle for laser printers.
33 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Installation

The indicator remains lit and the Self Test indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 36 for more information.
If you should encounter any problems during startup, see the troubleshooting chart on page 57.
The UPS is shipped with the battery(s) charged. However, batteries may lose some of the charge during shipping and storage. You can use the UPS immediately after unpacking, but it may not provide the full-rated backup time during a power failure. Upon initial startup, the UPS may need to operate for approximately 8 hours before the battery is fully charged and full battery-backup time is available. If the Battery Fault indicator flashes, operate the UPS for 24 hours to fully charge the battery.
34 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Installation

This chapter covers the operation of the UPS including front panel functions, operating modes, using the Battery Start feature, shutting down the UPS, and using the PowerPass.
The UPS front panel has three distinct functions:
: Displays the UPS operational mode (Normal, Bypass, or Battery).
: Displays any alarm conditions present during operation (the
indicators flash).
: Displays the loading percentage during Normal mode and the battery
capacity during Battery mode.
You can also use the front panel to configure UPS communication options and to configure the UPS output voltage. See “Front Panel Communications Access” on page 46 or “Changing the Output Voltage” on page 39.
Output On Button (UPS on, load online)
Output Off Button (UPS off, load offline)
Unlit Amber Green Flashing
Overload Indicator Site Fault Indicator Overtemp Indicator Battery Fault Indicator Self Test Indicator
Figure 6. UPS Front Panel
35 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Indicator Legend · Sine Wave Indicator · Battery Online Indicator

After you install and apply power to the UPS, the UPS filters and regulates incoming AC power, eliminating noise and voltage spikes, and provides consistent power to your equipment (see Figure 7). While power is applied to the UPS, the maintenance-free battery is automatically kept in a fully-charged condition.
Utility Power Surge Suppression EMI/RFI Filters
Figure 7. UPS Block Diagram
Normal Mode During Normal mode, the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the protected equipment (see Figure 8).
LOAD OFF LOAD ON LOAD ON LOAD ON LOAD ON APPROX. 81-100% LOAD
APPROX. 41-60% LOAD
APPROX. 0-40% LOAD
NORMAL UTILITY
Figure 8. Normal Operation Indicators
36 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Bypass Mode The indicator and the indicator illuminate simultaneously, indicating Bypass mode (see Figure 9). When the UPS is in Bypass mode, the load is powered by utility power. However, utility power continues to be passively filtered by the UPS.
LOAD ON UNIT ON BYPASS
Figure 9. Bypass Operation Indicators
Battery Mode When the UPS is operating during a power outage, the alarm beeps several times initially, and then once every 10 seconds while in Battery mode. The indicator illuminates. The front panel displays the approximate percentage of battery capacity remaining (see Figure 10). When the utility power returns, the UPS switches to Normal mode operation while the battery recharges.
BATTERY ONLINE >75% CAPACITY REMAINS
BATTERY ONLINE >50% CAPACITY REMAINS
BATTERY ONLINE >25% CAPACITY REMAINS
BATTERY ONLINE
BATTERY ONLINE SHUTDOWN IMMINENT LOW BATTERY WARNING
Figure 10. Battery Operation Indicators
If battery capacity becomes low while in Battery mode, the Battery Fault indicator begins to flash and the Self Test indicator remains lit, indicating approximately two minutes before UPS shutdown. The alarm beeps every two seconds.
37 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
UPS Operation

When shutdown is imminent, the Self Test indicator flashes. These warnings are approximate, and the actual time to shutdown may vary significantly. Once these warnings are indicated, immediately complete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically connects to the load when the startup is complete.
The UPS periodically performs diagnostic tests while the unit is operating in Normal mode, ensuring proper operation. These tests include:
: Self Test
: Site Fault Test
: Utility Verification Test
: Battery Discharge Test
: Over Temperature Test
The UPS also runs a series of over 20 internal tests when power is first applied. If a diagnostic test fails, see Chapter 7, “Troubleshooting” on page 57.
Battery Test on Demand You can perform a battery test on the UPS while it is operating in Normal mode by pressing the Output On button. The UPS automatically distributes some of the load to the batteries for 30 seconds and tests the battery’s performance.
38 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
UPS Operation

This feature allows you to start the UPS without utility power. After utility power has been unavailable for one minute, press and hold the Output On button until the alarm beeps.
The UPS supplies power to your equipment and goes into Battery mode. The indicator remains lit and the front panel displays the percentage of battery capacity remaining to the UPS. This process should take about 15 seconds.
Performing a UPS shutdown turns off the power to your protected equipment. Confirm the equipment is prepared for a power-off before shutting down the UPS. To perform a UPS shutdown:
The indicator remains lit indicating Normal mode, load offline.
The UPS enters Battery mode for several seconds. The indicator turns off and the UPS shuts down.
To change the operating voltage of the UPS (208V - 240V units only):
39 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
UPS Operation

The PowerPass provides a high level of reliability with surge suppression and continuous online power for your equipment. It also maximizes uptime by providing a second source of power and surge protection. The PowerPass allows you to:
: Replace or upgrade the UPS without losing power to your equipment
: Provide surge protection if the UPS is not present
: Provide extra surge protection when the UPS is present
: Increase the number of output receptacles
: Protect a laser printer against power surges without overloading
This Maintenance Bypass feature is useful when replacing the UPS for maintenance or upgrades. Figure 11 shows the operation of the UPS with the PowerPass.
Figure 11. UPS and PowerPass Block Diagram (UPS Operation)
40 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Using Maintenance Bypass Use the following procedure to transfer the critical load to Maintenance Bypass (AC Line operation) and remove the UPS:
Figure 12. PowerPass Block Diagram (AC Line Operation)
41 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

UPS Circuit Breaker Access
Figure 13. PowerPass Front Panel (120V Model)
UPS Circuit Breaker Access
Figure 14. PowerPass Front Panel (208V - 240V, IEC Model)
42 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Use the following procedure to reinstall the UPS and transfer the critical load from Maintenance Bypass (AC Line operation) to the UPS:
The UPS performs diagnostic tests and enters Normal mode with the equipment (load) offline. The indicator remains lit.
The indicator remains lit and the Self Test indicator turns on.
The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online.
43 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
UPS Operation

44 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
UPS Operation

The UPS is equipped with a communications interface port that allows communication with a wide variety of external devices including:
: Video or dumb terminal
: Serial printer
: Computer with power management or shutdown software
The serial port enables you to monitor and record diagnostic data with the following communication interfaces:
: Serial Communications Interface
Terminal Mode Data Dump Mode Printer Mode, 2400 Baud, with Novell Contacts (default) Printer Mode, 19200 Baud, with Novell Contacts
: LAN Configuration
Novell-Style Network Interface 3Com-Style Network Interface AS/400-Style Network Interface Custom User-Configurable Interface
The UPS is factory-configured for one of several communication interfaces (usually determined by the customer). To determine the initial UPS communications configuration, you can:
: Look at the box label with the serial number (communication mode
is shown in the upper right corner).
: Use the Display Configuration option on the UPS Serial
Communications Menu (see page 48).
: Call the Help Desk at one of the telephone numbers on page 60.
If you want to change the UPS configuration settings, use the front panel or the UPS Serial Communications Menu.
45 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Before you access the front panel, review the following configurations and note the indicator that corresponds with the communication mode.
Printer Mode, 2400 Baud, Novell Contacts Select this mode for the OnliNet9 or LanSafe software.
Unlit Amber Green Flashing
FRONT PANEL COMMUNICATION OPTIONS
Novell-Style LAN Contacts Any baud rate other than 2400 or 19200 with Printer mode, or not Printer mode.
3Com LAN Manager Any communication mode and baud rate option.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
AS/400-Style LAN Contacts, No Serial Select this mode for the OnliSafe9 software.
Printer Mode, 19200 Baud (network devices), Novell Contacts
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
Figure 15. Front Panel Communication Options
46 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Communication · Indicator Legend

To access the front panel communication options, perform the following steps:
Press and hold the Output Off button until the long beep ceases (approximately three seconds).
Unplug the UPS. Wait until all indicators turn off and then continue to the next step.
A single indicator, corresponding with the current setting, remains flashing.
47 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Communication

With the UPS Serial Communications (Main) Menu, you can view or select UPS communication modes, baud rates, and LAN configurations. To change or display the current communications configuration:
836 6(5,$/ &20081,&$7,216 0(18 6(/(&7 23(5$7,21 02'(
! ' ',63/$< &21),*85$7,21
&217,18286 '803 $ % 3 / = 4 6
!
32//(' '803 60$57 '803 $6&,, 7(50,1$/ 97 7(50,1$/ 35,17(5 '803 /$1 &21),*85$7,21 6(7 %$8' 5$7( 48,7 :,7+287 6$9,1* 1(: &21),*85$7,21 6$9( $1' 5(67$57
(17(5 6(/(&7,21 ! ! !
D > Display Configuration displays the current communication settings and the new settings that you have selected prior to saving them. The new settings are not effective until you select save from the Main Menu.
48 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Communication · !

6HULDO 9HUVLRQ &200 PRGH %DXG [ /$1 PRGH
6LWH )DXOW 'HWHFWLRQ (QDEOHG
1HZ &200 $6&,,
1HZ %DXG 1HZ /$1 1RYHOO
3UHVV VSDFH EDU WR FRQWLQXH
1 > Continuous Dump The UPS regularly transmits status information to the computer. Baud rates of 1200 to 2400 are recommended to reduce host computer overhead when using this mode.
2 > Polled Dump Status information is transmitted only when requested by a poll character (Control-E).
3 > Smart Dump Status information is transmitted when polled, as in the previous mode. However, the transmission also occurs automatically whenever UPS status changes. For example, if there is a power outage, UPS status information changes and is therefore, automatically transmitted.
A > ASCII Terminal The UPS displays the formatted data on the attached video terminal.
B > VT100 Terminal The UPS displays the formatted data on the attached video terminal.
P > Printer Dump The UPS prints the formatted data on the attached printer.
L > LAN Configuration allows you to configure the UPS for a new LAN mode and displays the Select LAN Configuration Menu.
49 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Communication

4
!
$6 &20/$1 0$1$*(5 &86720 &21),*85$7,21 72 48,7 7+,6 0(18
Select the AS400 option if you are using OnliSafe software to monitor the UPS.
The Custom Configuration option has two screens: the first screen has options available for inverter shutdown, and the second screen has options available for the contact configuration. Consult your shutdown software documentation for details on the required signal states for configuring LAN communications.
6(/(&7 &86720 /$1 &21),*85$7,21
,QVWUXFWLRQV &KRRVH WKH GHVLUHG LQYHUWHU VKXWGRZQ IXQFWLRQ :DUQLQJ ,W LV UHFRPPHQGHG WKDW WKLV IHDWXUH VKRXOG QRW EH XVHG ZLWK QRUPDO 56 FRPPXQLFDWLRQV FRQIOLFWV PD\ RFFXU
$ ! ,QYHUWHU VKXWGRZQ FRQWURO LV HQDEOHG DFWLYH +,*+ 9
,QYHUWHU VKXWGRZQ FRQWURO LV GLVDEOHG
! 72 48,7 7+,6 0(18
(17(5 6(/(&7,21 ! !
6(/(&7 &86720 /$1 &21),*85$7,21
! 87,/B)$,/ LV DFWLYH FORVHG /2:B%$77 LV DFWLYH FORVHG
87,/B)$,/ LV DFWLYH FORVHG /2:B%$77 LV DFWLYH RSHQ
87,/B)$,/ LV DFWLYH RSHQ /2:B%$77 LV DFWLYH RSHQ
72 48,7 7+,6 0(18
(17(5 6(/(&7,21 ! !
50 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Z > Set Baud Rate allows you to select a new baud rate. The Select Baud Rate Menu displays a list of baud rate options.
4
!
48,7 7+,6 0(18
If you want to abandon the selections you have made, type Q to quit.
Power management software allows you to monitor UPS operations automatically. To use OnliNet or LanSafe software, the UPS must be configured for any one of the Data Dump, Terminal, or Printer modes; however, Printer mode is preferred.
OnliNet provides multiple levels of UPS monitoring and control, as well as automatic shutdown for many different operating systems. If you have any questions or would like further information, call the Help Desk at one of the telephone numbers on page 60.
51 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

In addition to configuring the UPS for specific communication options, you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment.
Use only the pins specified for your communications configuration. The use of any additional pins for any of the following interfaces can cause interference with system communications.
Even though your network uses the specified signal lines, the pins assigned to these signals at the network end of the cable may vary with those of the UPS serial port. The connector body and style may vary as well.
The UPS serial port complies with EIA RS-232 standards. RS-232 specifies a maximum cable length of 50 ft (15m). See Figure 16 for the location of the serial port.
Figure 16. Serial Port Location
52 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

The following chart defines the UPS serial port contacts. Serial communication is not available with 3Com and AS/400 network configurations. Use only the applicable pins for the selected communication mode; otherwise, interference problems may occur.
Communication Mode Function Signal Name Pin No. True Condition
Serial Data to UPS RS232 TxD 2 N/A
Data from UPS RS232 RxD 3 N/A
Novell (D f l )
Battery On ON.AC 14/16 Open (Default) Low Battery TWO.MIN 23/24 Closed
Battery On ON.AC 14/16 Closed (Custom) Low Battery TWO.MIN 23/24 Closed
3Com (D f l )
Shutdown (Remote) SHUT.DOWN 2 Positive Voltage (Default) Low Battery LOW.BATT 9 Positive Voltage
Battery On PWR.FAIL 10 Positive Voltage
AS/400 UPS Available UPS Available 11/13 Closed
Battery On Utility Failure 14/16 Closed
Bypass UPS Offline 17/19 Closed
Low Battery Low Battery 23/24 Closed
53 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

54 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Communication


55 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com

Parameter Standard Unit with Battery Standard EXT Unit with Battery External Battery Cabinet
Height 252 mm (9.91 in) 252 mm (9.91 in) 252 mm (9.91 in)
Width 142.5 mm (5.61 in) 142.5 mm (5.61 in) 142.5 mm (5.61 in)
Depth 400 mm (15.75 in) 400 mm (15.75 in) 400 mm (15.75 in)
Weight 12.93 kg (28.5 lb) 15.6 kg (34.3 lb) maximum EBC60-1 Battery: 12.25 kg (27 lb) EBC60-2 Battery: 22 kg (48.5 lb)
120V Model 208V - 240V Models
Input Voltage Range 85 to 144 Vac 140 to 276 Vac (600 - 1250 VA) 150 to 276 Vac (1500 - 1800 VA)
Input Power Factor 0.95 Typical 0.90 Typical
Frequency Range 50/60 Hz ±3 Hz
Surge Protection Meets IEEE 587/ANSI C62.41
Category A and B
Output Waveform Sine wave
Output Voltage 120 Vac ±3% 208/220/230/240 Vac ±3%
Common Mode Noise Rejection >60 dB @ 100 kHz
Transverse Mode Noise Rejection >80 dB @ 100 kHz
Audible Noise Normal Mode 45 dBA
Input Cord Detachable 2-meter cord with 5-15P
Outlets 5-15R (4) IEC 320 (3)
Operating Environment Temperature: 10C to 40C (50F to 104F) Humidity: 5 to 95% (noncondensing)
Batteries 12 Vdc, 5 Ah, maintenance-free rechargeable lead acid
or Class B (model dependent)
56 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Specifications

The Prestige UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Use the following troubleshooting chart to determine the UPS alarm condition.
Unlit Amber Green Flashing
Condition Possible Cause Action
UPS does not turn on. UPS is not plugged in. Plug UPS into working outlet.
Dead wall socket. Test wall socket, repair as required.
UPS circuit breaker is tripped. Reduce load, then reset breaker. If you are using a PowerPass, reset the breaker using a pencil through the circuit breaker (CB1) access hole.
PowerPass circuit breaker is tripped.
Reset breaker.
Load does not turn on. UPS has not been activated. Press the Output | On button for one second, then release.
UPS beeps occasionally. Normal operation. None. UPS is protecting your equipment.
UPS circuit breaker trips. Load fault. Check the load. Disconnect faulty load equipment. Wait several minutes before resetting the UPS circuit breaker. If you are using a PowerPass, reset the breaker using a pencil through the circuit breaker (CB1) access hole. Restart the load.
57 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Indicator Legend

Action Possible Cause Condition
indicator remains lit, even though line voltage is present
Utility line is out of specification.
Test wall socket, repair as required.
voltage is present.
UPS circuit breaker is tripped. Reduce load, then reset breaker.
PowerPass circuit breaker is tripped.
Reset breaker.
UPS does not provide the expected backup time.
Low battery capacity. Allow battery to charge for 24 hours, then retest.
Protected equipment power requirements exceed UPS capacity.
Reduce load, then retest.
Communications do not function properly.
Incorrect communications cabling.
Verify cable integrity (see page 52).
Incorrect baud rate. Select a new baud rate (see page 51).
Incorrect communication mode. Select a new communication mode (see Chapter 5).
Power requirements exceed UPS capacity. If overload is greater than 105%, the alarm beeps every second and the UPS may switch to Bypass mode.
Your UPS continues to operate. Reduce load.
The UPS switched to Bypass mode because the overload increased (above 105%). The alarm beeps.
Reduce load. If the Overload indicator remains lit, reset the UPS by pressing the Output | On button until the alarm beeps. You may need to obtain a larger capacity UPS.
Building wiring is out of specification. The UPS checks the utility power source during startup for reversed neutral and line conductors. The alarm beeps.
Have site wiring tested. Repair as required.
The utility line voltage and frequency are out of specification.
The inverter remains online, deriving power from the utility until it is no longer acceptable. Check the unit configuration. Refer to the product specifications (see page 55).
58 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Troubleshooting

Action Possible Cause Condition
UPS internal temperature is too high. The alarm beeps and the UPS switches to Bypass mode for approximately 10 minutes, allowing the UPS to cool down.
Shut down the UPS. Clear vents. Remove any heat sources. Wait approximately 5 minutes and retry. Contact your service representative if condition persists.
Weak battery while in Normal mode. The alarm beeps.
Allow the battery to charge for 24 hours, then retest. Have batteries replaced if condition persists.
BATTERY
Battery breaker is open (O). Verify that the battery circuit breaker is in the ON ( | ) position.
Battery cabinet is not properly connected to the UPS.
Verify that the battery cords are connected.
Weak battery while in Bypass mode.
This usually indicates that the batteries need replacing or the UPS requires service. Contact your service representative.
Self Test failure. UPS internal problem.
The UPS may switch to Bypass mode, depending on the circumstances. Reset the UPS by pressing the Output | On button until the alarm beeps. Contact your service representative if condition persists.
Resetting the UPS
To reset the UPS while an alarm condition is present, press the Output On button until the UPS alarm beeps.
To silence the alarm for an existing fault, press and hold the Output On button for one second. The alarm becomes quiet. If UPS status changes, the alarm beeps, overriding previous alarm silencing. Press the Output On button again to silence the alarm.
59 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Troubleshooting

The troubleshooting chart on page 57 covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
In the United States 1-800-365-4892 In Canada 1-800-461-9166 All other countries 1-919-870-3149
Please have the following information ready when you call the Help Desk:
: Model number
: Serial number
: Version number (if available)
: Date of failure or problem
: Symptoms of failure or problem
: Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you.
60 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com
Troubleshooting