6000 Watts
Voltage: 200-240 Vac
Frequency: 50/60 Hz
Configuration: 6U rack-mount
for standard 19-inch racks
T
o meet the power protection needs of
In addition to its exceptional power rating
and size, the Powerware 5140 also
A Power Factor Corrected (PFC) design
(formerly Exide Electronics) proudly intro-
Management (ABM™) which assures
reliability and improves performance by
A 6U rack height conserves valuable
duces the Powerware 5140 Rack-Mount
uninterruptible power system (UPS). The
doubling battery service life, optimizing
A Advanced Battery Management
Powerware 5140 is powerful and flexible
recharge time, and providing up to a 60-
(ABM™) doubles battery service life
day notice of the end of useful battery life.
enough to respond to the demands of
A Buck and Boost voltage
virtually any Enterprise computing
The Powerware 5140 utilizes multiple
regulation with pure sine wave output
network.
receptacle groups, called Load Segments,
A Extended Battery Modules (EBMs)
The Powerware 5140 is designed with a
which can be pre-configured to shutdown
unity power factor rating, meaning it is
peripherals first to effectively triple battery
A Modular design eases setup and
ideally suited to meet the requirements of
run times for the most critical equipment.
today's Power Factor Corrected (PFC)
Extended Battery Modules (EBMs) are also
A Load Segments (separate receptacle
loads. With proven and reliable technology,
available to extend run times, and to
groups) enable scheduled shutdowns and maximize run time for critical devices
it delivers up to a third more power than
preserve data integrity, the Powerware
traditionally rated UPSs while still
5140 is bundled with award-winning
A Hot-Swappable batteries and Manual
occupying only 6U (10.5 inches) of
LanSafe III and FailSafe III power
Bypass Switch simplify service
valuable rack space.
management software.
A Backed by 10-Year Pro-rated
Warranty (U.S. and Canada)




The lead-acid batteries typically used in a
UPS are considered viable as long as they


can maintain backup times of at least half
that of new batteries. The illustration to the
right shows that batteries that are constantly
trickle charged (as are virtually all other UPS
batteries on the market today) reach the end
of their useful life in less than half the time
of batteries charged using ABM. ABM uses a
patented three-stage charging technique that
not only doubles battery service life, but
Data based upon tests performed by an independent battery manufacturer.
also optimizes battery recharge time and
provides up to a 60-day advanced notifi-
cation of pending end of useful battery life.
C OMMUNICATIONS
Voltage 200, 208, 220, 230, & 240 Vac user-selectable; see Model Selection Guide for default settings
Serial Ports (2) Serial communication ports for use with power management software and installable option cards, including ConnectUPS SLC-EM SNMP Adapter and the Port Expander Card User LEDs Normal Operation (green), On Battery (yellow), On Bypass (yellow), and Alarm (red) LCD Two-line LCD with three button control LCD Languages Danish, Dutch, English, French, German, Spanish, Italian, and Japanese Front Panel Buttons On, Off, and Alarm Silence/Self Test Communications 6-foot communication cable included Cable ENVIRONMENTAL AND SAFETY
Normal Voltage ±20% of nominal voltage without using batteries Range
Extended Voltage 160-288V without using batteries (set via front panel) Range
Frequency 50/60 Hz, ±3 Hz (+5/-3 Hz with extended voltage range)
Power Out 6000 VA/6000 Watts
Voltage Range ±10% of nominal voltage (online)
Operating 10°C to 40°C (25°C for optimal performance) Temperature
Voltage Range ±5% of nominal voltage (on battery)
Transit Temperature -20°C to 55°C
Storage Temperature 0°C to 25°C
Wave Form Sine Wave (on battery)
Humidity (Operation) 20 to 80% (noncondensing)
Frequency Same as input (±0.5% during battery operation)
Humidity 5 to 95% (Non-operating)
Connections Receptacles or hardwired; see Model Selection Guide
Operating Altitude 0 to 10,000 feet (non-operating: 0 to 30,000 feet)
Max Current 29A at 208 Vac; 26A at 230 Vac
Audible Noise 55 dBA at 1 meter
Safety Markings UL, CSA, NOM. Models PW5140 6000i and PW5140 6000 HW also CE and VDE
Type Maintenance-free, sealed, valve-regulated lead-acid (VRLA), (28), 12V 5 AH
Safety UL1778; CSA22.2 No.107.1,No.107.2,No.950; CB Certifications Bulletin No.86AI; EN50091-1; EN60950; EMKO-TSE207/95; NOM-019-SCFI-1993
Extended Batteries Maximum of 2 Extended Battery Modules (EBMs)
Backup Time See Battery Run Times table
EMC Markings FCC-A; CISPR-A; VCCI
Recharge Time
Immunity IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5
Extended Battery
Surge Suppression Conforms to IEEE 587B and ANSI C62.41
REPO Port Meets NEC code 645-11 intent and UL requirements
Connection Hardwired

Unity Power Factor Rating
Load Segments are groups of receptacles that can be independently controlled via the front
panel LCD interface and/or LanSafe III/FailSafe III, which is bundled with the Powerware
What does unity power factor rating mean?
5140. Load Segments provide extended battery run times and flexible management of the
Quite simply, it means that the watt rating of the
UPS. The five Load Segments of model PW5140 6000i are outlined below.
UPS is equal to its VA rating. Traditionally,
Load Segments divide the Powerware 5140 into five virtual UPSs
UPSs have been designed, built, and sold with a
power factor rating of approximately 0.6 to 0.7.
For example, a 1000 VA UPS could supply a

Shut down Load Segments to decrease load and extend backup time for other Load Segments
maximum of 600 to 700 watts. Historically, this
0.7 power factor was appropriate for the
majority of computer loads the UPS was
intended to support since most computers
Reboot a locked up server by turning a Load Segment off and on
demanded power at a 0.7 power factor.
Today, however, a large percentage of high-end
computers, utilize Power Factor Corrected
(PFC) power supplies, which have a power
factor of approximately 1.0. Take a look at the
configuration below:

(3) Servers* 3300 3366
(2) Workstations* 1000 1020
(1) Color Monitor 200 300
*Equipment with PFC power supplies.
To support this load, you need to select a
UPS with a rating that meets or exceeds both
the watt and VA demand shown above.
To extend battery backup times, you can connect up to two EBMs. Each EBM occupies
A traditionally rated 5000 VA/3750 watt UPS
3U (5.25 inches) of rack space.
without a unity power factor rating cannot be
used. The Powerware 5140, on the other

hand, has capacity to spare.
You can hot-swap both the standard batteries and EBMs without powering down the connected load. This makes it possible to extend the life of the UPS without returning the unit for service.

MODEL POWER OUT INPUT/OUTPUT FREQUENCY INPUT OUTPUT DIMENSIONS WEIGHT NUMBER (VA/WATT) VOLTAGE (VAC) (HZ) CONNECTION RECEPTACLES (HXWXD) 1 (KG/LB) (12) IEC-320, C13 & 10.5 x 17.25 x 24.3 in PW5140 6000i 6000/6000 208/2302 50/603 Hardwired (3) IEC-320, C194 26.7 x 43.8 x 61.7 cm 136/3006
(2) L6-30R & 10.5 x 17.25 x 24.3 in PW5140 6000 6000/6000 208/2302 50/603 Hardwired (2) IEC-3205 26.7 x 43.8 x 61.7 cm 136/3006
Hardwired & 10.5 x 17.25 x 24.3 in PW5140 6000 HW 6000/6000 208/2302 50/603 Hardwired (2) IEC-3205 26.7 x 43.8 x 61.7 cm 136/3006
Custom 5.25 x 17.25 x 22.5 in PW5140 BATT – – – Adapter – 13.3 x 43.8 x 57.2 cm 81.6/180 Custom 1.98 x 19.28 x 9.90 in PW5140 PDU7 250/250 120 60 Adapter (2) 5-15R 5.03 x 48.97 x 25.15 cm 8.6/19 Adjustable; fits PW5119 MK23 – standard 19-inch rack 4.5/10
STANDARD ONE ADDITIONAL TWO ADDITIONAL
LOAD BATTERIES EXTENDED BATTERY MODULE EXTENDED BATTERY MODULES 1000 Watts 1 hour 2 minutes 2 hours 24 minutes 3 hours 56 minutes 2000 Watts 28 minutes 1 hour 6 minutes 1 hour 47 minutes 3000 Watts 18 minutes 40 minutes 1 hour 6 minutes 4000 Watts 12 minutes 28 minutes 47 minutes 5000 Watts 8 minutes 21 minutes 36 minutes 6000 Watts 6 minutes 18 minutes 28 minutes
This table provides typical information. Battery times are approximate and may vary with equipment, configuration, disk access, battery use, temperature, etc.


PW5140 6000i PW5140 6000
A (2) I NSTALLABLE O PTION S LOTS
E H ARDWIRE I NPUT
I L OAD S EGMENT 4
B (2) C OMMUNICATION P ORTS
F L OAD S EGMENT 1
J L OAD S EGMENT 5
C M ANUAL B YPASS S WITCH
G L OAD S EGMENT 2
K C IRCUIT B REAKER ( S )
D REPO P ORT
H L OAD S EGMENT 3
L IEC-320 R ECEPTACLES FOR PDU C ONNECTION
M H ARDWIRE O UTPUT
Powerware Corporation Corporate Headquarters
China and North Asia Hong Kong: 852.2745.6682
8609 Six Forks Road Raleigh, NC 27615 U.S.A. Toll Free: 1.877.797.9273 (PWRWARE) or 919.872.3020 Fax: 1.800.753.9433 or 919.870.3411 E-mail: info@powerware.com www.powerware.com
Europe/Middle East/Africa Berkshire, England: 44.1753.606700
Australia and South Pacific Sydney, Australia: 61.2.9878.5000
Revision 5140FXA 7/99 Reprint 7/99