ATHENA CONTROLS, INC. 5145 Campus Drive Plymouth Meeting PA 19462 U.S.A. Tel: (610) 828-2490 Fax: (610) 828-7084 AthenaControls.com

Controller Indicator Transmitter 1 / 32 DIN - 48 x 24

LISTED
UL

Controller Indicator Transmitter 1 / 32 DIN - 48 x 24
LISTED
UL

COMPATIBILITY.
SAFETY AND
All the information and warnings about safety and electromagnetic compatibility are marked with the B sign, at the side of the note.
The device has no user serviceable parts and requires special equipment and specialised engineers. Therefore, a repair can be hardly carried on directly by the user. For this purpose, the manufacturer provides techni- cal assistance and the repair service for its Customers. Please, contact your nearest Agent for further information.
It is important to understand that it’s responsibility of the installer to ensure the compliance of the regulations on safety requirements and EMC.
Regulations on Electromagnetic Compatibility according to the European Community directive n089/336/CEE, amended by the European Community directive n° 92/31/CEE and the following regulations: Regulations on RF emissions EN50081 - 1 residential environments EN50081 - 2 for industrial environments Regulation on RF immunity EN500082-2 for industrial equipment and system
This controller has been designed with compliance to: Regulations on electrical apparatus (appliance, systems and installa- tions) according to the European Community directive 73/23 CEE amend- ed by the European Comunity directive 93/68 CEE and the Regulations on the essential protection requirements in electrical apparatus EN 61010- 1 (IEC 1010 - 1) : 90 +A1:92 + A2:95.
Please, read carefully these instructions before proceeding with the installation of the controller. Class II instrument, rear panel mounting.


Table of contents TABLE OF CONTENTS 1 INSTALLATION Page 4 2 ELECTRICAL CONNECTIONS Page 8 3 PRODUCT CODING Page 14 4 OPERATIONS Page 18 5 AUTOMATIC TUNE Page 28 6 TECHNICAL SPECIFICATIONS Page 29

Modbus RS485 Parameterisation Supervision

2 Single OP2 OP1 OP4 output
1 Single OP1 OP2 OP4 output
0 Indication OP1 OP2 OP4 only
One shot Natural frequency

B To prevent hands or metal touch- ing parts that may be electrically live, the controllers must be installed in an enclosure and/or in a cubicle.
Before proceeding with the instal- lation of this controller, follow the instructions illustrated in this man- ual and, particularly the installation precautions marked with the B symbol, related to the European Community directive on electrical protection and electromagnetic compatibility.
Installation must only be carried out by qualified personnel.
Sealin front panel gasket
IP 20 Termination Unit EN61010 - 1 (IEC1010 - 1)
Front panel IP65 protection EN 60529 (IEC 529)
Mounting clamps · Product code label · Panel surface

48 mm 1.89 in
120 mm 4.72 in
25 mm 0.99 in
20 mm max 0.79 in max
22.2+0.3 mm 0.87+0.01 in
45+0.6 mm 1.78+0.023 in
65 mm min 2.56 in min
42 mm min. 1.65 in min.

E Explosive atmosphere
P Conducting atmosphere Use filter
T Temperature >50°C
Use 24V ~ supply version
Use forced air ventilation
Suggestions · Warm up


1 Prepare panel cut-out 2 Check front panel gasket posi- tion 3 Insert the instrument through the cut-out

Electrostatic discharges can dam- age the instrument Before removing the instrument the operator must discharge himself to ground 1
1 Push and 2 pull to remove the instrument
1 Position the mounting clamps 2 Push the mounting clamps towards the panel surface to secure the instrument
1 Insert the screwdriver in the clips of the clamps 2 Rotate the screwdriver


Recommended wire terminal leads

Ø Fork-shape AMP 165004 Ø 5.5 mm - 0.21 in
L Stripped wire L 5.5 mm - 0.21 in
Pin connector q 1.4 mm - 0.055 in max
Negative screw driver 0,8 x 4 mm
Positive screw driver PH1
Holding screw 0.5 Nm
Cable size 0,5…1,5 mm2 (22 a 16 AWG)
5.7 mm 0.22 in
Option terminals · 12 screw terminals · Rear terminal cover

Keep the low level sensor input wires away from the power lines and the output cables. If this is not achievable, use shield- ed cables on the sensor input, with the shield connected to earth.
The supply wiring should be rout- ed away from the power cables. Avoid to use electromagnetic con- tactors, power relays and high power motors nearby. Avoid power units nearby, espe- cially if controlled in phase angle
A All the wiring must comply with the local regulations.
Despite the fact that the instrument has been designed to work in an harsh and noisy environmental (level IV of the industrial standard IEC 801-4), it is strongly recom- mended to follow the following suggestions.
2.2 RECOMMENDED ROUTING OF WIRES B
L N IN
7 8 9 10 11 12
1 2 3 4 5 6
Conduit for supply and output cables
Conduit for low level sensor cables
L N IN
7 8 9 10 11 12
1 2 3 4 5 6
A = Supply B = Outputs C = Analog inputs D = Analogue output Serial communications E = SSR drive output

2.3 TYPICAL INSTRUMENT WIRING B
V ~
Current 2.5 Ω external shunt resistor Coil of the load contactor
Load Solid state relays
Fuse 0.2 A T
5 4 3 2 1
12 11 10 9 8 7
V ~
0P4
OP1
OP2
B B
A
PV
Notes: 1] Make sure that the power supply voltage is the same indicated on the instrument. 2] Switch on the power supply only after that all the electrical con- nections have been completed. 3] In accordance with the safety reg- ulations, the power supply switch shall bring the identification of the relevant instrument. The power supply switch shall be easily accessible from the operator. 4] The instrument is protected with a 0.2 A~ T fuse. In case of fail- ure it is suggested to return the instrument to the manufacturer for repair. 5] To protect the instrument internal circuits use: - 2 A~ T fuses for Relay outputs - 1 A~ T fuses for Triac outputs 6] Relay contacts are already pro- tected with varistors. Only in case of 24 V ~ induc- tive loads, use model A51-065- 30D7 varistors (on request)

0.2A included fuse
Load Solid state relay 10 11
Varistor for inductive loads 24V~ only
Varistor for inductive loads 24V~ only
Coil of the load contactor
Coil of the load contactor
Supply L N · Fuse · Fuse


A When the distance between the controller and the sensor is 15 mt. using a cable of 1.5 mm2
diameter, produces an error on the measure of 1°C.
For L J K S T thermocouple type
wire resistance 150Ωmax
Use wires of the same length and 1.5 mm2 size. 20 Ω/lead maxi- mum resistance.
For 3 wires only 20 Ω/lead maxi- mum resistance
With 3 wire transducer
With 2 wire transducer
For mA, mV and V
18Vdc 9 5 6
external shunt 2.5Ω
external shunt 2.5Ω
External shunt 2.5Ω

2.3.6 SERIAL COMMUNICATIONS (option) B
2.3.5 OP4 OUTPUT (option) B
A Please, read the user instructions on the “C10 controller MODBUS/JBUS protocol”
Load · mA

The complete code is shown on the instrument label. The informa- tions about product coding are accessible from the front panel by mean of a particular procedure described at section 4.2.2 page 19 3000
M N
C D
Basic product code (hardware)
IND. CON. EQ. 23 FA UL
; C10-3000-0300 : A0A-9809/0013
Configuration code (software) · Instrument label · Made in Italy

The product code indicate the spe- cific hardware configuration of the instrument, that can be modified by specialized engineers only.
DIN rail without display (requires CD option code 50 or 56) 2
Mounting (DIN rail mounting does not include UL) Panel (standard) DIN rail with display
Dark Grey High accuracy resistor 2 Beige High accuracy resistor 3
Front Bezel Color [2] G Dark Grey (standard) 0 Beige 1
Option 3 E Not provided 0
Option 1 D Option 2
Output 1 [1] B Relay 0 Triac 3
Power supply A 100 - 240V~ (-15% + 10%) 3 24V~ (-25% + 12%) or 24V– (-15% + 25%) 5
Model:
C 10 A B C D - E F G H
0 Not provided 6 Transmitter Power Supply
7 Transmitter PS + Retransmission 0
0 Not provided 6 Transmitter Power Supply (PS)
User manual 3 F
0/4-20mA Input Shunt Resistor [2]

The configuration code can be dis- played on the front panel, follow- ing the instructions at pag 19 sec- tion 4.2.2.
The configuration code consists of 4 digits that identify the operat- ing characteristic of the controller, as chosen by the user. Section 4.5 at pag. 26 reports the instructions how to set a new con- figuration code.
0 Safety 0% 1 Safety 0% Reverse (AL1 active low) Direct (AL1 active high)
Type of control and safety M Reverse (AL1 active low) Direct (AL1 active high)
On - Off 2 Control OP1 / alarm AL2 on OP2 3 Control OP2 / alarm AL2 on OP1
7 DC input 10…50 mV, linear 8 Custom input and range
DC input 0…50 mV, linear
TC T Cu-CuNi 4 TC K Cromel -Alumel IEC584 5 TC S Pt10%Rh-Pt IEC584 6
TC J Fe-Cu45% Ni IEC584 3
TC L Fe-Const DIN43710 2
TR Pt100 IEC751 1
TR Pt100 IEC751 0
Input type and range I
Alarm AL1 on OP2/ alarm AL2 on OP1
Alarm AL1 on OP1/ alarm AL2 on OP2
Control OP1 / alarm AL2 on OP2 1 Control OP2 / alarm AL2 on OP1
2 Safety 100% 3 Safety 100%
-99.9…572.9 °F -328…1112 °F 32…1112 °F 32…1112 °F -200 …400 °C 0…1200 °C 0…1600 °C engineering units [1]
-99.9…300.0 °C
32…2192 °F 32…2912 °F
-328…752 °F

The controller remains in stand-by until the configuration code is set correctly (see chapter 4.6 pag 26).
it means that the controller has not been configured yet.
A If, when the controller is pow- ered up for the first time, the dis- play shows the following mes- sage
Deviation [1] active high 4 active low 5 Deviation band [1]
Absolute 2 active high 3 active low
Alarm 2 type and function N Not active 0 Sensor break alarm 1
active out (of the band) 6 active in (the band) 7

OP2 output ON (red)
OP1 output ON (red)
Tuning in progress (green) • PV control input (operator mode) (in engineering units) when the measured value is greater than sensor high range

when the measured value is less than the sensor low range
Values modification

When the display operation is selected, the controller presents automatically all the most impor- tant parameters and configuration information. During the operation, the para- meters values cannot be modi- fied by the user After 2 sec from the end of the operation, the controller flashes the display and returns to the normal operating conditions.
4.2.1 OF THE PROCESS VARIABLES

after 0,5 sec. after 0,5 sec.
Configuration code (see page 16)
Basic product code (see page 15)
rel.
°C Hard
Unit

Press S or G momentarily to change the value of 1 unit every push Continued pressing of S or G changes the value, at rate that doubles every second. Releasing the button the rate of change decreases. In any case the change of the value stops when it has reached the max/min limit set for the parameter.
(i.e. the modification of the value of a stored Setpoint from 275.0 to 240.0)
after 2 sec.
Setpoint entry. The operation is acknowledged by one flash of the display.

Press the S or G to display the next or previous mnemonic for the selected parameter. Continued pressing of S or G will display further mnemonics at a rate of one mnemonic every 0.5 sec. The mnemonic displayed at the time the next parameter is selected, is the one stored in the parameter.
(e.g. configuration see pages 26, 27)
°f
none
°f
°C
Unit

Pressing the Q key, the next group of parameters is present- ed on the display.
After having selected the parame- ter or the code, press S and G to display or modify the value (see pag. 20) The value is entered when the next parameter is selected, by pressing the R key.
A The parameter setting procedure has a timeout. If no keys are pressed for, at least, 30 seconds, the controller switches back, auto- matically, to the operator mode.

Values modification Modification/ selection entry
Note [1] It is presented only if the controller has been configured with 2 alarms. Digit L of the con- figuration code is assigned to 4 or 5 [2] It is not presented if the controller has been configured with alarm n° 2 not active or of sensor break type. Digit N of the configu- ration code is assigned to 0 or 1. [3] If password is 0000 to 4999, parameter set- ting will be available to the operator with- out entering this password number. If pass- word is 5000 to 9999, parameter setting will only be available by entering this pass- word number.

Operator mode 1st GROUP AL1 alarm threshold [1] (see pag. 24)
Code entry [3] from 5000 to 9999 Must be equal to the value of the parame- ter Code
Password entry [3] only if Code value ≥5000 (see pages 26…27)
P 1:00
P 0
t.c.
t.d.
Cycle time (PID algorithm only) 1 ... 200 sec.
Derivative time (PID algorithm only) 0ff / 0.01 ... 10.00 min.
Integral time (PID algorithm only) 0ff / 0.0 ...100.0 min.
Proportional band (PID algorithm only) 0.5…999.9% of span
AL2 alarm threshold [2] (see pag. 24)
Parameter menù selection


Back to the 1st parameter group
Control output hysteresis (On-Off control only) 0.1… 10.0% of span
Control output high limit (PID algorithm only) 10.0…100.0%
Overshoot control (PID algorithm only) 0.01…1.00

Setpoint high limit (not available with 2 alarms) s.p. l…high range
Setpoint low limit (not available with 2 alarms) low range …s.p. H
Setpoint ramp down (not available with 2 alarms) 0ff/0.1…999.9 digit/min
Setpoint ramp up (not available with 2 alarms) 0ff/0.1…999.9 digit/min
Back to the 1st parameter of the 2nd group
rt.lo
Addr
In.sh
t.fil
pass
Retransmission high range (if option installed) full scale
Retransmission low range (if option installed) full scale
Communication address (if option installed) 0ff / 1…247
Input shift 0ff/ -60...60 digits
Filter time constant 0ff/ 1...30 sec.
Password entry [3] only if Code value
Direct access to the configuration (pages 26 … 27)

Integral time It is the integral time value, that #t.i.
Proportional band This parameter specifies the pro- portional band coefficient that mul- tiplies the error (SP - PV)
#p.b.
AL2 alarm threshold The alarm occurrences handle the OP1 and OP2 outputs, in different ways, according to the configured types of alarms, as illustrated.
AL1 alarm threshold The threshold is presented only if the controller have been configured with 2 alarms. ( Digit L of the con- figuration code assigned to 4 or 5)
1st GROUP The controller parameters have been organized in group, accord- ing to their functionality area.

+ high range - low range Alarm threshold



Sensor break or input disconnection
high range low range Alarm threshold
Overshoot control This parameter specifies the span of action of the overshoot control. Setting lower values (0.99 —> 0.01) the overshoot generated by a Setpoint change is reduced. The overshoot control doesn’t affect the
Control output cycle time It’s the cycle time of the time propor- tioning control output. The PID con- trol output is provided through the pulse width modulation of the digital waveform.
Derivative time It is the derivative term coefficient that specifies the time required by the pro- portional term P to reach the level of D. When Off the derivative term is not included in the control algorithm.
specifies the time required by the integral term to generate an output equivalent to the proportional term. When Off the integral term is not included in the control algorithm.
#O.C.
#t.c.
#t.d.
alarm threshold

Setpoint ramp up Setpoint ramp down This parameter specifies the max- imum rate of change of the Setpoint in digit/min. When the parameter is Off, this function is disabled.
#sl. u
Control output hysteresis span, set in % of the full scale.
#hy.
Control output high limit It specifies the maximum value the control output can be set
effectiveness of the PID algorithm. Setting 1, the overshoot control is disabled.
Hysteresis of the threshold
Input filter time constant Time constant, in seconds, of the RC input filter applied to the PV input. When this parameter is set to Off the filter is bypassed.
AL2 alarm hysteresis Hysteresis of the threshold of both the alarms, that activate OP1 and OP2 control output. It is specified as a % of the full scale.
#AIhy
Setpoint high limit High limit of the setpoint value. When the parameter is Off, this function is disabled.
Setpoint low limit Low limit of the setpoint value. When the parameter is Off, this function is disabled.
Retransmission low range Retransmission high range These parameters define the range of the OP4 retransmission output. Example: 4..20 mA output corre- sponding to 20…120°C.
Controller address the address range is from 1 to 247 and must be unique for each con- troller on the communication bus to the supervisor. When set to Off the controller is not communicating
This value is added to the measured PV input value. Its effect is to shift the whole PV scale of up to ± 60 digits.
#rt.lo
#Addr
#In.sh
t.Fil Time

Press S or G to display the next parameter or the next code and change its value. The new value entered is stored into the controller when the next parameter is selected by pressing R.

The configuration of the controller is specified through a 4 digit code that defines the type of input, of control output and of the alarms. (sect. 3.2 pag16) Other parameters specifie the type of auxiliary functions.
Values modification Modification/ selection entry


Password [3] 0…9999 (33 default from factory)
Retransmission range (only if present) 0=20 / 4=20 mA
Baude rate (only if comm. is installed) 1200/2400 4800/9600
prot
sc.Hi
Code entry [3] from 5000 to 9999 Must be equal to the value of the parameter Code
Password entry [3] only if Code value ≥5000
Communication protocol (only if communication is installed) M.bu5 / jbus
High range [2] (linear scale only) -999…9999
Low range [2] (linear scale only) -999…9999
Parameter menù selection


Entry of digits I-L-M-N of the configuration code (chapter 3.2 page 16)
If the controller has not been configured Conf is shown on the front panel at the power up. In this situation, the controller has its outputs and inputs not active. This situation ends when a correct configuration code is entered.
Code entry [3] from 0 to 4999 (33 default from factory) The entered password must correspond to the one store in the Code parameter.
* For inputs from thermocouple or resistance thermometer, the choice is between °C and °F only. [2] Range of min 100 digits. [3] If password is 0000 to 4999, parameter set- ting will be available to the operator with- out entering this password number. If pass- word is 5000 to 9999, parameter setting will only be available by entering this pass- word number.
Centigrade degrees * °C Fahrenheit degrees * °f none none mV nU Volt U mA MA Ampere A Bar bAr PSI psI Rh rh pH ph
[1] Table of the supported Engineering Units.

Start/stop of the Fuzzy Tuning The Tuning operation can be started or stopped any time.
strt
stop
tune
To stop select stop
To start select strt
Natural frequency This type is selected when the PV is close to the SP setpoint.
Step response This type is selected when, at the start of the autotune operation, the PV is far from the Setpoint of more than 5% of the span. This method has the big advantage of fast calculation, with a reasonable accuracy in the term calculation.
The green led 3 goes on when the Fuzzy Tuning is in progress. At the end of this operation, the calculat- ed PID terms parameter are stored and used by the control algorithm and the controller goes back to the operator mode. The green led 3 becomes off. This function allows the calculation of the optimal PID terms parame- ters, monitoring the response of the process to disturbances. The controller provides 2 types of “one shot” tuning algorithm, that are selected automatically according to the process condition when the operation is started.
This method has the advantage of a better accuracy in the term cal- culation with a reasonable speed calculation. The Fuzzy Tuning determines automatically the best method to use to calculate the PID term, according the process conditions.
Setpoint change End of the tuning operating and setting of the new calculated terms.
End of the tuning operating and setting of the new calculated terms.
Start of autotune operation

PV Input (see pag.12 and pag. 16)
Total configurability see par. 3.2 pag. 16 par. 4.6 pag. 26
Features (at 25°C enviromental temp.)
From keypad or serial communication the user selects: the type of input - the associated functions and the corresponding outputs - the type of control algo- rithm - the type of output and the safe conditions - the type and functionality of the alarms - the values of all the control parameters.
4…20mA,0-20mA with external shunt 2.5Ω Rj >10MΩ
Pt100Ωat 0°C (IEC 751)
0.25% ± 1 digits for temperature sensors 0.1% ±1 digits (for mV) 0.1% ±1 digits + accuracy of the used external shunt resistor (for mA)
A/D converter with resolution of 50.000 points Update measurement time: 0.2 seconds Sampling time: 0.5 seconds Input bias: - 60…+ 60 digit Input filter with enable/disable: 1…30 seconds
Engineering units Conf.decimal point position Init. Sc. -999…9999 Full Sc. -999…9999 (min. range of 100 digits)
Internal cold junction compensation in °C/°F
2 or 3 wires connection
Max.wire Res.: 150Ωmax Input drift:
Max. wire Res.: 20Ωmax (3 wires) Input drift: 0.3°C/10°C Env.Temp.
Between 100…240V~ the error is minimal

AL1 alarm (indicator with 2 alarms)
Operating mode and Outputs
Features (at 25°C enviromental temp.)
Hysteresis 0.1…10,0% c.s.
Hysteresis 0.1…10,0% full scale Active high Active low
SPST Relay N.O., 2A/250V~ for resistive load Triac, 1A/250V~ for resistive load
Proportional band (P) 0.5…999.9% Integral time (I) 0.1…100.0 min Off = 0 Derivative time (D) 0.01…10.00 min Cycle time 1…200 sec Overshoot control 0.01…1.00 High limit 100.0…10.0% Hysteresis 0.1…10.0%
Algorithm PID with overshoot control or ON OFF
1 PID loop or 1 ON-OFF loop with 1 Alarm
Indicator with 2 alarms
Special function Sensor break
Absolute threshold, whole range
OP1 - Relay or Triac OP2 - Logic OP2 - Logic OP1 - Relay or Triac
OP2 - Logic OP1 - Relay or Triac
OP1 - Relay or Triac OP2 - Logic
AL1 alarm AL2 alarm
Absolute threshold whole range

One shot Fuzzy-Tuning with automatic selection Serial comm. (option) Auxiliary Supply
OP4 PV retransmission (option)
Features (at 25°C enviromental temp.)
+18V– ±20%, 30mA max for an external transmitter supply
RS485 isolated, Modbus/Jbus protocol, 1200, 2400, 4800, 9600 bit/sec 2 wires
Galvanic isolation: 500 V~/1 min Resolution 12bit (0.025%) Accuracy: 0.1 % The controller selects automatically the best method according to the process conditions Natural frequency
Ramp up and down Low limit High limit
1/32 DIN - 48 x 24, depth 120 mm, weight 100 gr. apx.
IP20 termination unit IP65 front panel
Compliance to the CE standards for industrial system and equipment
Password to access the configuration and parameters data
Safety value: 0…+100%. (user enabled/disabled) parameter and configuration data are stored in a non volatile memory for an unlimited time
Detection of out of range, short circuit or sensor break with automatic activation of the safety strategies and alerts on display
From low limit to the high range
From low range to the high limit
0.1…999.9 digit/min (Off = 0)

We warrant that the prod- ucts will be free from defects in material and workmanship for 3 years from the date of delivery. The warranty above shall not apply for any failure caused by the use of the product not in line with the instructions reported on this manual.
warranty