Table of Contents 80 sections SERIES 16C TEMPERATURE/PROCESS CONTROLLER · Instruction Manual · (Basic Operations) · Introduction · … ShowHide
SERIES 16C TEMPERATURE/PROCESS CONTROLLERp.1Instruction Manualp.1(Basic Operations)p.1Introductionp.2Precautionsp.2Featuresp.2Safety Warningp.3U Lp.3® U L C ®p.3Installationp.5Figure 1. Recommended Panel Layout for Multiple Controllersp.5Dimensionsp.6Figure 2. Case Dimensionsp.6Mountingp.6Wiringp.7Figure 4. Contact Identificationp.7N.O. RCVp.7COMp.7A1 RS 232 RS 485p.7XMT A (+)p.7B (-)p.7232/485 GND ALARMp.7OUTPUT 1p.7A2p.7SENSORp.7RTDp.7INPUT T/Cp.7OUTPUT 2p.710 T/Cp.8Output Typesp.9E 0.2p.9F 0.2p.9G 0.2p.9S 0.2p.9T 15*p.9Y >15p.9Output Type Descriptionp.9Operationp.10Figure 9. Front Panel Controls and Indicatorsp.10Power Onp.11Operations Overviewp.11Security Levelsp.12JMPØ3p.12Operating Modesp.13Menu System Overviewp.14Figure 10. Series C Functional Diagramp.15Menu Systemp.15Process Variable Displayp.15Mode Selectionp.15Menus and Parameter Descriptions Menus and Parametersp.18Input Menup.19Input Menu Display Parameter Selectionp.19Input Menu (continued) Display Parameter Selectionp.20Input Jumper Settingsp.20JMPØ2p.20JMPØ1p.20Temperature Input Type Display Parameter Selectionp.20Linear Input Type Display Parameter Selectionp.20Display Menup.21Output Menup.21Output Type Display Parameter Selectionp.21PID Output Typep.22*Recommended Cycle Time Settingsp.22Control Menup.22On/Off Output Typep.23Notes On Alarmsp.24a specified band centered around the setpoint. Latching Alarmsp.24Alarm Output Typep.25Autotune Damping Menup.26Recipe (Ramp/ Soak) Menup.26Supervisor Menup.28Calibration Menup.29Options Menup.29Autotuningp.30Autotuning Procedure Diagramp.31Manual Tuningp.32Manual Tuning Procedure (Zeigler-Nichols PID Method)p.32Error Codesp.33Autotune Errorsp.33Technical Specificationsp.34
Page 1 of the Athena Technologies Center Channel Speaker (16C) user manual — Instruction Manual
Page 1 · click to enlarge
Page 1

SERIES 16C TEMPERATURE/PROCESS CONTROLLER

Athena Technologies Center Channel Speaker (16C) — SERIES 16C TEMPERATURE/PROCESS CONTROLLER diagram (page 1)
Fig. 1
Athena Technologies Center Channel Speaker (16C) — SERIES 16C TEMPERATURE/PROCESS CONTROLLER diagram (page 1)
Fig. 2

Instruction Manual

(Basic Operations)

Page 2 of the Athena Technologies Center Channel Speaker (16C) user manual — Features
Page 2 · click to enlarge
Page 2

Introduction

Congratulations on your purchase of an Athena Series 16C Temperature/Process Controller. It is designed for ease of use and reliability wherever accurate control is required.

After following the instructions for installation, simply step through and set your operating parameters using the controller’s easy menu system. The instrument may then be automatically or manually tuned to your process for optimum setpoint control. A Quick Setup Reference Card is on page 5 and also attached as a tear-off card to the back of the instruction manual for experienced users of PID controllers.

As you look through this manual, you will notice blue italicized text appearing in the margins and adjacent to operating information. These notes impart important informa- tion about the controller and may answer questions you may have about its setup or operation. If you still have questions or require any assistance, please contact your Athena repre- sentative or call technical support at 1-800-782-6776. Outside the USA, please call 610-828-2490.

Precautions

After unpacking, inspect the instrument for any physical damage that may have occurred in shipping. Save all packing materials and report any damage to the carrier immediately.

Features

Field-Selectable Thermocouple, RTD, Current or Voltage Input On/Off Through Full PID Operation Autotuning - Heat or Cool Eight-Segment Ramp/Soak On/Off Output with Adjustable Hysteresis and Deadband Dual Output Capability Field-Configurable Process or Deviation Alarms Bumpless, Auto-Manual Transfer NEMA 4X Front Panel, “Watertight” Dual 4-Digit (0.36”), 7-Segment Alphanumeric Display Selectable Ramp to Setpoint Alarm Inhibit Loop Break Alarm Capability Available Options Include Serial Communications, Contact/ Digital Input, Remote Analog Setpoint, Transducer Excitation, Auxiliary Output, Dual Alarms, or Electromechanical Relay Alarm. Approvals: UL, cUL, CE

© Copyright 2004, Athena Controls, Inc.

Page 3 of the Athena Technologies Center Channel Speaker (16C) user manual — U L
Page 3 · click to enlarge
Page 3

Safety Warning

In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and cause severe injury or death. When installing or using this instrument, follow all instructions carefully and use approved safety controls. Electrical connections and wiring should be performed only by suitably trained personnel.

Do not locate this instrument where it is subject to excessive shock, vibration, dirt, moisture, oil, or other liquids. The safe operating temperature range for this unit is 32°F to 140°F (0°C to 60°C).

This unit has been tested and found to be compliant with “NEMA Type 4X Enclosure - For Indoor Use Only.” When properly installed, this controller will maintain the integrity of a NEMA enclosure and remain “Watertight.” This rating is only applicable when the controller is properly installed into a suitably rated NEMA Type 4X housing.

U L

® U L C ®

Page 4 of the Athena Technologies Center Channel Speaker (16C) user manual — Safety Warning
Page 4 · click to enlarge
Page 4
Page 4 of the Athena Technologies Center Channel Speaker (16C) user manual — Safety Warning
Page 5 of the Athena Technologies Center Channel Speaker (16C) user manual — Figure 1. Recommended Panel Layout for Multiple Controllers
Page 5 · click to enlarge
Page 5

Installation

Unpacking and Inspection 1. Inspect shipping carton for obvious signs of mishandling.

Measurements between centerlines of panel cut- outs are the minimum recommended.

2. After removing the controller from the shipping carton, inspect it carefully for damage. Never attempt to install and use a damaged unit.
3. Verify that the ordering code number indicated on the side of the controller matches what was ordered.

Figure 1. Recommended Panel Layout for Multiple Controllers

2.850” (72.4 mm)

2.150” (54.6 mm)

Page 6 of the Athena Technologies Center Channel Speaker (16C) user manual — Mounting
Page 6 · click to enlarge
Page 6

Dimensions

Figure 2. Case Dimensions

Athena Technologies Center Channel Speaker (16C) — Figure 2. Case Dimensions diagram (page 6)
Fig. 3 · Figure 2. Case Dimensions

Prior to mounting the Series C in your panel, make sure that the cutout opening is of the right size, 1.771” x 1.771” (45 mm x 45 mm), and deburred to enable a smooth fit. A mini- mum of 4” (100 mm) of depth behind the panel is required.

Mounting

Figure 3. Series C Mechanical Components Insert the Series C through the front panel cutout and slide the mounting collar back onto the unit from behind the panel. Push the mounting collar up tight to the back of the mounting panel.

When properly installed through a NEMA enclosure, the integrity of the enclosure will be maintained and will remain “Watertight.”

Bezel GripsCase Clip GasketCustomer Panel
Athena Technologies Center Channel Speaker (16C) — Mounting diagram (page 6)
Fig. 4 · Mounting
Page 7 of the Athena Technologies Center Channel Speaker (16C) user manual — RTD
Page 7 · click to enlarge
Page 7

Wiring

The Series C controller has built-in circuitry to reduce the effects of electrical noise (RFI) from various sources. However, power and signal wires should always be kept separate. We recommend separating connecting wires into bundles: power; signal; alarms; and outputs. These bundles should then be routed through individual conduits. Shielded sensor cables should always be terminated at one end only.

If additional RFI attenuation is required, noise suppression devices such as an R.C. snubber at the external noise source may be used. If you wish, you may order this suppressor directly from Athena, part number 235Z005U01.

Figure 4. Contact Identification

ALARM & COMM.

N.O. RCV

COM

A1 RS 232 RS 485

XMT A (+)

B (-)

N.O.

232/485 GND ALARM

COM

OUTPUT 1

A2

& COMM.

N.O.

N.C.

SENSOR

N.O.

RTD

INPUT T/C

OUTPUT 2

L1 L2 100 - 250 V 50/60 Hz 100 - 250 Vdc (Auto Polarity) 24 Vac/Vdc (Auto Polarity)

Page 8 of the Athena Technologies Center Channel Speaker (16C) user manual — Wiring
Page 8 · click to enlarge
Page 8

Wiring

Figure 5. Thermocouple Input Wiring Make sure that you are using the appropriate thermocouple and extension wire. Connect the negative lead (generally colored red in ISA-type thermocouples) to contact #9; connect the positive lead to contact #10. Extension wires must be the same polarity as the thermo- couple.

Thermocouple circuit resistance should not exceed 100 ohms for rated accuracy; errors will occur at higher resistance values. If shielded thermo- couple wire is used, terminate the shield only at one end.

10 T/C

Figure 6. RTD Wiring The Series C accepts input from 2- or 3-wire, 100 ohm platinum resistance temperature detectors (RTDs). Connect 2-wire RTDs to contacts #9 and #10, with a jumper across contacts #8 and #10. Keep leads short and use heavy gauge copper extension wire, if necessary, to minimize lead resistance. For long runs, 3-wire RTDs should be used.

RTD

Jumper 8 & 10

Wiring

Figure 7. Process and Linear Input Wiring Voltage Inputs: Connect the positive voltage input to contact #10; the negative input to contact #9. Current Inputs: Connect the positive current input to contact #10; the negative input to contact #9.

The Series C power supply accepts 100 to 250 Vac and 100 to 250 Vdc line power without any switch settings or polarity considerations. All connections should be made in accordance with the National Electrical Code and local regulations, using only NEC Class 1 wiring for all power terminals. It is advisable, but not necessary, to fuse one leg of the incoming power line, contact #11, with a 2AG, 0.5 amp rated fuse. It is recommended that instrument power and load power be fused independently. Figure 8. Power Wiring Connection

100. 250 V 50/60 Hz 100 - 250 Vdc (Auto Polarity)
Page 9 of the Athena Technologies Center Channel Speaker (16C) user manual — Output Type Description
Page 9 · click to enlarge
Page 9

Output Types

When you ordered your Series C controller specific output types were specified, designated as “B”, “E”, “F”, “G”, “S”, “T” or “Y”. You also had the option of configuring your con- troller with either one or two output actions. The numbers below are suggested for most typical applications.

The Type “B” output is a mechanical device and subject to wear. To extend the life of the relay, set the Cycle Time for the relay output to the longest duration that still affords good control.

For Control Output Type — Select Cycle Time

(in seconds) B >15

E 0.2

F 0.2

G 0.2

S 0.2

T 15*

Y >15

* “T” outputs directly driving non-inductive loads (small heaters) can have cycle times as low as 0.2 seconds.

Output Type Description

B 5 A (120/240 Vac) relay, normally open, used

for switching resistive loads. If relays or sole- noids are to be driven, select the “T” output. If a “B” output is selected, order snubber network 235Z005U01.

F 4-20 mA, full output to load with 500 ohm impedance max. (suppressed).

G High impedance ‘F’ (800 ohms).

S 20 Vdc pulsed output for solid-state relays.

T 1 A @ 120/240 Vac, solid-state relay, zero volt-

age-switched and optically isolated from drive signal. Only resistive loads to 1A may be con- trolled directly. Larger loads may be controlled using an external contactor.

Y 5 A (120/240 Vac) relay, but normally closed (output 2 only).

E 0-20 mA

Page 10 of the Athena Technologies Center Channel Speaker (16C) user manual — Figure 9. Front Panel Controls and Indicators
Page 10 · click to enlarge
Page 10

Operation

Figure 9. Front Panel Controls and Indicators

Athena Technologies Center Channel Speaker (16C) — Figure 9. Front Panel Controls and Indicators diagram (page 10)
Fig. 5 · Figure 9. Front Panel Controls and Indicators

Mode/Enter Key Used to enter Parameter selections, access operating modes, release latched alarms, and index through menu items. Lower Key Used to decrease values. (Hold for fast-step progression) Raise Key Used to increase values. (Hold for fast-step progression) Menu Access Key Used to enter or exit the menu system, index to the next menu, and enter the Security Level menu.

Page 11 of the Athena Technologies Center Channel Speaker (16C) user manual — Operations Overview
Page 11 · click to enlarge
Page 11

Power On

The Series C controller’s functional hierarchy is organized into three distinct user-program- mable groupings: Security Level, Menu System, and Operating Mode.

When power is first applied to the Series C, all segments of the LED displays will be momentarily illuminated while the instrument goes through a series of diagnostic checks to verify proper operation. A software version number will then appear in the lower display, followed by a configuration code (upper display) and the communications protocol which is supported (lower display).

Please provide the software version number, communications protocol, and the controller’s full model number, when contacting us regarding your controller.

1. Press and hold Mode/Enter key until a menu label appears in upper display (approximately three seconds).
2. Press Raise or Lower key until appears in the lower display.
3. Press Mode/Enter key. (The upper display will alternate between and process value.)

Operations Overview

The user interface of the Series C allows you to use menus to set up the instrument, set the desired security level, change the setpoint, and conveniently change operating modes. Figure 9 on page 15 provides a functional representation of the user interface and the key presses necessary to perform the basic functions.

Page 12 of the Athena Technologies Center Channel Speaker (16C) user manual — JMPØ3
Page 12 · click to enlarge
Page 12

Security Levels

The security level feature allows you to limit access to the menus, setpoint, and operating mode selection according to the needs of your application. The security levels provided are Key Lockout, Setpoint, Setpoint plus Mode, User, Configuration, and Factory. To view or change security level from the Process Variable display, press and hold the Menu Access key for approximately 10 seconds. (Ignore the menu label that will appear in the upper display after approximately three seconds.) The controller will display

The controller’s initial security level, set at the factory, is Configuration

. When you have completed configuring the instrument, we recommend the security level be set to the most restrictive level suitable for your application.

(Access Level) and the current security level label, e.g., . Use the Raise or Lower keys to index through the security levels. Press the Mode/Enter key once to select the new security level desired and return to the Process Value display.

Security Levels and Access Restrictions

Key Lockout Highest security level. No access to any

controller functions. To escape, follow instructions above for changing security levels.

Setpoint No access to menus. Only allows setpoint

value or output percentage (manual mode) to be changed.

Setpoint plus Mode No access to menus. Only allows setpoint

value, output percentage (manual mode), or operating mode to be changed.

User All “Setpoint” level privileges as well as

access to Operating Mode, Autotune, and Control menus.

Configuration All “User” level privileges as well as Input,

Output, Display, and Supervisor menus

Factory All “Configuration” level privileges as well

as access to Calibration menu.

Athena Technologies Center Channel Speaker (16C) — Security Levels diagram (page 12)
Fig. 6 · Security Levels

JMPØ3

Page 13 of the Athena Technologies Center Channel Speaker (16C) user manual — Operating Modes
Page 13 · click to enlarge
Page 13

Operating Modes

The Series C’s operating modes are: Manual, Standby, Normal, Autotune, Ramp/Soak Recipe, Run and Hold. To select a different operating mode, press the Mode/Enter key for three seconds. The operating mode that the controller is currently in will be dis- played. To index through the available operating modes, press the Raise or Lower keys. When the desired mode is displayed, press the Mode/Enter key once to select the mode.

Remember to press the Mode/Enter key after making your selection.

If both outputs are set to or , the Series C will func- tion as a non-control- ling indicator. Control outputs will be disabled and the Operating Modes will not be displayed.

Athena Technologies Center Channel Speaker (16C) — Operating Modes diagram (page 13)
Fig. 7 · Operating Modes

Autotune (Only available when unit is placed in Standby mode and one output is PID.)

Operating Modes

Manual Used to set control output percentage

(Fixed Output Percentage) independent of Process Value. To set percentage, use the Menu Access key to select and the Raise or Lower keys to set the value. is displayed if Output 1 is a control output. is displayed if Output 2 is a control output.

Manual operating mode overrides auto- matic control, allowing you to control the outputs using a fixed percentage of output power, regardless of the process variable or setpoint.

Standby Used to disable control outputs.

If current automatic control is PID, transfer to Manual mode is “bumpless.”

Normal Normal automatic control.

Autotune Used to initiate the autotuning

sequence (from Standby only).

Ramp/Soak Used to start ramp/soak recipe mode. Recipe

Run Used to enable Run function

Hold Used to enable Hold function

Page 14 of the Athena Technologies Center Channel Speaker (16C) user manual — Menu System Overview
Page 14 · click to enlarge
Page 14

Menu System Overview

The Parameter Menu System is organized into ten basic menus: Input, Display, Output, Control, Alarm, Tune, Recipe, Supervisor, Calibration, and Option. To access the Menus, press and hold the Menu Access key for approxi- mately 3 seconds until a menu label appears in the upper dis- play. There are additional menus presented when an option is selected under the Option menu; however, the options are non-functional unless the appropriate option board has been installed. Pressing the Menu Access key indexes from menu to menu. Pressing the Mode/Enter key indexes through the parameters in a particular menu. The Raise and Lower keys are used to modify the visible menu parameter.

If a key press is not sensed within five minutes, the control- ler automatically exits the Menu System and reverts to the Process Value display.

Each menu contains a logical group of parameters related to one another. Furthermore, the sequence of the menus has been carefully chosen to put the most important setup menus first.

Page 15 of the Athena Technologies Center Channel Speaker (16C) user manual — Figure 10. Series C Functional Diagram
Page 15 · click to enlarge
Page 15

Menu System Overview

To return to Process Value at any time, press and hold Menu Access key for three seconds

Figure 10. Series C Functional Diagram

Menu System

Process Variable Display

Security Levels

Mode Selection

Show 6 more labels / short text on this page
for 3 seconds · for 3 seconds · for 10 seconds · once · for 3 seconds · once
Page 16 of the Athena Technologies Center Channel Speaker (16C) user manual — Figure 10. Series C Functional Diagram
Page 16 · click to enlarge
Page 16
Athena Technologies Center Channel Speaker (16C) — Figure 10. Series C Functional Diagram diagram (page 16)
Fig. 8 · Figure 10. Series C Functional Diagram
Athena Technologies Center Channel Speaker (16C) — Figure 10. Series C Functional Diagram diagram (page 16)
Fig. 9 · Figure 10. Series C Functional Diagram

Menu Access

Page 17 of the Athena Technologies Center Channel Speaker (16C) user manual — Figure 10. Series C Functional Diagram
Page 17 · click to enlarge
Page 17
Athena Technologies Center Channel Speaker (16C) — Figure 10. Series C Functional Diagram diagram (page 17)
Fig. 10 · Figure 10. Series C Functional Diagram

Mode/ Enter Key (three seconds) Functional When Option Card Installed

Athena Technologies Center Channel Speaker (16C) — Figure 10. Series C Functional Diagram diagram (page 17)
Fig. 11 · Figure 10. Series C Functional Diagram

* See options manual for parameter selections.

Athena Technologies Center Channel Speaker (16C) — Figure 10. Series C Functional Diagram diagram (page 17)
Fig. 12 · Figure 10. Series C Functional Diagram

Raise/ Lower Key

Page 18 of the Athena Technologies Center Channel Speaker (16C) user manual — Menus and Parameter Descriptions Menus and Parameters
Page 18 · click to enlarge
Page 18

Menus and Parameter Descriptions Menus and Parameters

Input Used to select sensor-related parameters, such as input type,

limits, and scaling.

Display Used to set or change decimal position and display units.

Output Used to specify output usage, control methods, and alarms. Control Used to select parameters associated with the control methods. Alarm Used to select alarm parameters . Note: This menu is also functional for controllers not equipped with alarm hardware; however, alarm indication will be only visual via the A1 and A2 LEDs on the front panel. Tune Used to set the autotune damping parameter.

Recipe Used to set ramp and soak parameters.

Supervisor Used to set fail-safe and supervisory parameters.

Calibration Used to recalibrate input.

Option Used to select installed option.

Communications (Option) Used to set serial communications parameters.

Contact/Digital Input (Option) Used to select switch input functions.

Remote Analog Setpoint (Option) Used to enter remote analog setpoint parameters.

Auxiliary Output (Option) Used to set auxiliary output parameters.

Page 19 of the Athena Technologies Center Channel Speaker (16C) user manual — Input Menu Display Parameter Selection
Page 19 · click to enlarge
Page 19

Input Menu

The first parameter that needs to be set is Input Type. The remaining Input Menu parameters will change, depending upon whether a linear input type or a temperature input type is selected. Other menu param- eters related to the sensor range may also change. After selecting your Input Type, refer to the corresponding section on page 16 for the remainder of the Input Menu parameters.

Input Menu Display Parameter Selection

Input Type Type J thermocouple Type B thermocouple Type C thermocouple Type E thermocouple Type K thermocouple Type N thermocouple Type NIC thermocouple Type NNM thermocouple Type R thermocouple Type S thermocouple Type T thermocouple Platinel II thermocouple 100 ohm platinum RTD

Page 20 of the Athena Technologies Center Channel Speaker (16C) user manual — Linear Input Type Display Parameter Selection
Page 20 · click to enlarge
Page 20

Input Menu

Input Menu (continued) Display Parameter Selection

Input Jumper Settings

Athena Technologies Center Channel Speaker (16C) — Input Menu (continued) Display Parameter Selection diagram (page 20)
Fig. 13 · Input Menu (continued) Display Parameter Selection

Input Type 100 ohm compressed RTD 0-20 mA 4-20 mA 0-10 mV 0-50 mV 0-100 mV 10-50 mV 0-1 V 0-5 V 0-10 V 1-5 V

Thermocouple Out Out RTD Out Out Voltage 100 mV In Out Current Process In In

JMPØ2

Note: When you ordered your controller, an input type was specified and the controller was set up accordingly and calibrated for that input type at the factory. If you decide to change input type from thermocouple to RTD or vice-versa, you will need to recalibrate the controller unless you ordered the “Calibrate All” option. (Refer to page 56 for information on recalibration.) If you are changing from a temperature input type to a linear input type, you MUST recalibrate and change the jumper settings as indicated in the above table.

JMPØ1

Input Menu

Temperature Input Type Display Parameter Selection

Athena Technologies Center Channel Speaker (16C) — JMPØ1 diagram (page 20)
Fig. 14

Bias (Display offset) -100 to 100 Lower Setpoint Limit Span of Sensor Upper Setpoint Limit Span of Sensor Filtering 0.1-10.0 sec.

Linear Input Type Display Parameter Selection

Bias (Display offset) -100 to 100 Low Scale -1999 to 9999 High Scale -1999 to 9999 Lower Setpoint Limit Span of Sensor Upper Setpoint Limit Span of Sensor Filtering 0.1-10.0 sec.

Page 21 of the Athena Technologies Center Channel Speaker (16C) user manual — Output Type Display Parameter Selection
Page 21 · click to enlarge
Page 21

Display Menu

Athena Technologies Center Channel Speaker (16C) — Display Menu diagram (page 21)
Fig. 15 · Display Menu

Decimal Position 0-3 Linear Inputs 0-1 TC/RTD

Filter 0.1-10.0 sec Units* Fahrenheit Celsius Kelvin *NOTE: Does not appear for linear inputs.

Blanking , 0-9999 sec (Time selected before setpoint diplay turns off.)

Output Menu

The first parameter that needs to be set in the Output Menu is the Output Type. There are three possible Output Type configurations: PID, On/Off, Alarm, or Off. (If you are not sure which Output Type is best for your particular application, refer to the Glossary for an explanation of Output Types.) The remaining menu parameters in the Output Menu will change, depending on the Output Type selected. The Control Menu will also change, depending on the Output Type selected. If you ordered two outputs, you can select two different Output Types. After setting your Output Type, refer to the correspond- ing sections below for the remaining Output Menu parameters. For simplification purposes, the following sections assume the same Output Type for both outputs. If you selected different Output Types, refer to both of those sections.

Athena Technologies Center Channel Speaker (16C) — Output Menu diagram (page 21)
Fig. 16 · Output Menu

Output Type Display Parameter Selection

JMPØ1

Display Parameter Selection · Output 1 Type · Output 2 Type

Page 22 of the Athena Technologies Center Channel Speaker (16C) user manual — PID Output Type
Page 22 · click to enlarge
Page 22

Output Menu

PID Output Type

Athena Technologies Center Channel Speaker (16C) — PID Output Type diagram (page 22)
Fig. 17 · PID Output Type

Output 1 Action Reverse-acting (Heating) Direct-acting (Cooling)

Output 1 Cycle Time* 0.2; 1 to 120 seconds Output 1 Low Limit 1-100% Output 1 High Limit 1-100%

Output 2 Action Reverse-acting (Heating) Direct-acting (Cooling)

Output 2 Cycle Time* 0.2; 1 to 120 seconds Output 2 Low Limit 1-100% Output 2 High Limit 1-100%

*Recommended Cycle Time Settings

Output Type Recommended Setting (seconds) B (5A/3A) 15 to 120 E (0-20 mA) 0.2 F (4-20 mA) MUST be set to 0.2 G (4-20 mA) MUST be set 0.2 S (pulsed 20 Vdc) 0.2 T (S.S. relay) 15 to 120** Y (5A/3A) N.C. 15 to 120 (Output 2 only)

** “T” outputs directly driving non-inductive loads (small heaters) can have cycle times as low as 0.2 seconds.

Control Menu

PID Output Type

As with the Output Menu, the Control Menu will change, depending upon the Output Type selected. Note: These parameters are auto- matically set during the autotune procedure. We do not recommend altering the value of these control parameters unless your process requires manual tuning.

Athena Technologies Center Channel Speaker (16C) — PID Output Type diagram (page 22)
Fig. 18 · PID Output Type

Proportional Band 1 1...to span of sensor

Setting Derivative (Rate) or Integral (Reset) to disables that aspect of PID control.

Proportional Band 2 1...to span of sensor

Derivative Action (Rate) 0 to 2400 seconds

Manual Reset OFF, -100% to 100%

If BOTH outputs are set to direct-acting or BOTH outputs are set to reverse-acting, then only one proportional band selection will be displayed.

Integral Action (Auto Reset) 0 to 9600 seconds

Display Parameter Selection

Page 23 of the Athena Technologies Center Channel Speaker (16C) user manual — On/Off Output Type
Page 23 · click to enlarge
Page 23

Output Menu

On/Off Output Type

Athena Technologies Center Channel Speaker (16C) — On/Off Output Type diagram (page 23)
Fig. 19 · On/Off Output Type

Output 1 Action Reverse-acting (Heating) Direct-acting (Cooling)

Output 2 Action Reverse-acting (Heating) Direct-acting (Cooling)

Control Menu

On/Off Output Type

If both outputs are set to in the Output Type Menu, the controller will function as a non-controlling indicator. Control outputs will be disabled and the Operating Modes will not be displayed.

Athena Technologies Center Channel Speaker (16C) — On/Off Output Type diagram (page 23)
Fig. 20 · On/Off Output Type

Deadband 1 Negative span of sensor to positive span of sensor

Hysteresis Output 1 1...to span of sensor

Deadband 2 Negative span of sensor to positive span of sensor

Hysteresis Output 2 1...to span of sensor

Display Parameter Selection · Display Parameter Selection

Page 24 of the Athena Technologies Center Channel Speaker (16C) user manual — a specified band centered around the setpoint. Latching Alarms
Page 24 · click to enlarge
Page 24

Notes On Alarms

Outputs can be set up as an alarm, similar to the standard alarm format. Four types of alarms are available: Process, Deviation, Inverse Band, and Normal Band. All alarms may be configured to be inhibited on power-up for a configurable time duration.

Process Alarm: Activates at preset value, independent of setpoint. “High” process alarm activates at and above alarm setting. “Low” process alarm activates at and below alarm setting.

Deviation, Inverse Band, and Normal Band Alarms track with setpoint.

Deviation Alarm: Activates at a preset deviation value from setpoint. “High” or “Low” deviation alarm activates above or below setpoint according to the preset deviation value.

Inverse Band AlarmActivates when the process is within

a specified band centered around the setpoint.

Normal Band AlarmActivates when the process exceeds

a specified band centered around the setpoint. Latching Alarms

When a latching alarm has been activated and the alarm condition has been removed, the Mode/Enter key must be pressed to unlatch the alarm.

The Series C’s alarms may also be configured as latching alarms by selecting in the Alarm Action parameter selection.

Page 25 of the Athena Technologies Center Channel Speaker (16C) user manual — Alarm Output Type
Page 25 · click to enlarge
Page 25

Output Menu

Alarm Output Type

Athena Technologies Center Channel Speaker (16C) — Alarm Output Type diagram (page 25)
Fig. 21 · Alarm Output Type

Output 1 Alarm Action (Latching) (Normal) Output 1 Alarm Operation (Process Low) (Process High) (Inverse Band) (Normal Band) (Deviation Low) (Deviation High) Output 1 Alarm Delay 0-9999 sec Output 1 Alarm Inhibit 0-9999 sec Output 1 Alarm Setpoint Span of Sensor

Alarms A1 & A2 can be set up using this same information in the menu.

Output 2 Alarm Action (Latching) (Normal) Output 2 Alarm Operation (Process Low) (Process High) (Inverse Band) (Normal Band) (Deviation Low) (Deviation High) Output 2 Alarm Delay* 0-9999 sec Output 2 Alarm Inhibit** 0-9999 sec Output 2 Alarm Setpoint Span of Sensor

*Alarm Delay - the time delay between the detection of the alarm condition and the initiation and indication of the output action. **Alarm Inhibit - prevents low setpoint alarm activation during cold startup applications.

Display Parameter Selection

Page 26 of the Athena Technologies Center Channel Speaker (16C) user manual — Recipe (Ramp/ Soak) Menu
Page 26 · click to enlarge
Page 26

Autotune Damping Menu

Athena Technologies Center Channel Speaker (16C) — Autotune Damping Menu diagram (page 26)
Fig. 22 · Autotune Damping Menu

Recipe (Ramp/ Soak) Menu

Single Setpoint Ramp Time This selection will cause the controller to ‘ramp’ the process from the starting point (current process value) to the setpoint in the time specified. This ramp will take place at startup when selected from the Ramp/Soak menu. The setpoint must be at least ±0.2% of sensor span for the ramp to be employed. Multi-Step Ramp This selection will enable the programming of a recipe (make all ramp/soak recipe variables visible). Recipes can be resumed on startup if interrupted by a power failure or initiated, held, and terminated from the front panel via the Mode Menu or with the logic input option (initiate and held/resumed only). Holdback Band Specifies the maximum number of degrees above or below setpoint that the process can be for the segment timer to keep going. The timer will hold while the process settles back into the band and then continue. If this feature is not desired, this param- eter should be set to which will disable it. Termination State This parameter determines what the control will do at the completion of a recipe. Last Setpoint refers to the last temperature specified in the ramp/soak recipe. Default Setpoint refers to the standard setpoint which was in effect prior to recipe initiation. Recycle Number Specifies the number of times after the first time that the recipe is run before the program terminates.

Page 27 of the Athena Technologies Center Channel Speaker (16C) user manual — Recipe (Ramp/ Soak) Menu
Page 27 · click to enlarge
Page 27

Recipe (Ramp/ Soak) Menu

Power Fail Resume Setting this parameter to On will cause the control to resume a recipe which was active when a power failure occurred. The recipe will resume at the start of the last active ramp or soak segment.

Ramp/Soak Events (1-8) (If alarms are configured as ramp/soak events.) Ramp/Soak events occur at the beginning of their designated segment. All events are terminated once the recipe has been completed or terminated. This can be used as an alarm when a segment is reached.

If a ramp/soak error condition occurs, the upper display will toggle between and the numeric error code for three seconds before the recipe terminates. Possible error codes are: 02 = Recipe Empty (i.e. no non-zero ramp times) 05 = Insufficient Setpoint-Process Value Deviation

Recipe Option Single-Setpoint Ramp Multi-Step Ramp Disabled

Single-Setpoint 1-9999 mins. Ramp Time*

*NOTE: Only available when single-setpoint ramp is selected.

Holdback Band Off-100 degrees

Termination State Last Setpoint Default Setpoint Recipe to Standby

Display Parameter Selection

Page 28 of the Athena Technologies Center Channel Speaker (16C) user manual — Supervisor Menu
Page 28 · click to enlarge
Page 28

Recipe (Ramp/ Soak) Menu

For Ramp Events and Soak Events to be employed, Alarm 1 or Alarm 2 must be set for event usage in the Alarm Menu.

Recycle Number 0-99, (Recipe Executions)

Power Fail Resume Off On

Ramp Times 1-8 0-9999 mins.

Ramp Events 1-8 Alarm 1 On Alarm 1 Off Alarm 2 On Alarm 2 Off Disabled

Soak Levels 1-8 Display Units, FS

Soak Times 1-8 0-9999 mins.

Soak Events 1-8 Alarm 1 On Alarm 1 Off Alarm 2 On Alarm 2 Off Disabled

Supervisor Menu

Athena Technologies Center Channel Speaker (16C) — Supervisor Menu diagram (page 28)
Fig. 23 · Supervisor Menu

Output 1 0 to 100% Failsafe State of output

Output 2 0 to 100% Failsafe State of output

Loop Break Time Off, 4-9600 sec Highest Reading n/a Lowest Reading n/a Load Default Parameters

The Failsafe State is only enforced when a problem is detected with the process input. It is not reli- ably enforceable in instances of internal circuitry failure such as EEPROM problems.

Choosing “Yes” to Load Default Parameters resets all menu parameters to factory settings.

Output % High Limits are ignored when the unit enters a Failsafe State.

Display Parameter Selection · Display Parameter Selection

Page 29 of the Athena Technologies Center Channel Speaker (16C) user manual — Options Menu
Page 29 · click to enlarge
Page 29

Calibration Menu

Athena Technologies Center Channel Speaker (16C) — Calibration Menu diagram (page 29)
Fig. 24 · Calibration Menu

Toggles with the temperature value that should be input to

perform the low calibration operation. The low calibration operation is triggered by pressing the up

arrow key.

Toggles with the temperature value that should be input to

perform the high calibration operation. The high calibration operation is triggered by pressing the

up arrow key.

Options Menu

Athena Technologies Center Channel Speaker (16C) — Options Menu diagram (page 29)
Fig. 25 · Options Menu

Installed Card Serial Communications Serial Communications with Switch Input Remote Analog Setpoint Auxiliary Output Alarm Switch Input with Alarm

Display Parameter Selection

Page 30 of the Athena Technologies Center Channel Speaker (16C) user manual — Autotuning
Page 30 · click to enlarge
Page 30

Autotuning

To place the controller in Autotune mode:

1. Configure the controller by following the directions for Initial Setup Sequence through Step 3 on page 7. Set damping parameter. (See page 22.)

In order for the controller to autotune properly, the setpoint value must be at least 1% of span above or below the initial process value. Make sure that the Setpoint Target Time parameter is set to OFF.

2. If the controller is not already in Standby mode, place it in Standby now as follows. Press and hold the Mode/Enter key for three seconds. Display will indicate your current operating mode. Press the Raise key or Lower key to select Standby. Press Mode key again and the display will alternate between and the process value. This will deactivate all outputs.

Tuning accuracy increas- es as the spread between ambient and setpoint value increases. Tuning should be performed with system in equilibrium (no latent energy remaining).

3. If Setpoint Value has not been entered, adjust setpoint now by using the Raise or Lower key to set the desired setpoint.
4. Wait for process to stabilize before proceeding, e.g., in the case of a heating and cooling process, return to ambient temperature.
5. Initiate Autotuning. Press and hold the Mode/Enter key again for three seconds, then press the Raise or Lower key repeatedly until appears. Finally, press the Mode/Enter key again. The display will alternately indicate

and process value as the controller “learns” the proper proportional band, derivative, and integral values for the process. If unacceptable overshoot occurs on restart, shut down the process and increase the damping setting. If sluggish response is observed, shut down the process and decrease the damping setting.

Page 31 of the Athena Technologies Center Channel Speaker (16C) user manual — Autotuning Procedure Diagram
Page 31 · click to enlarge
Page 31

Autotuning

If a tune error condition occurs, the upper display will toggle between and a numeric error code for three seconds before the tune process terminates. The controller will then automatically go into Standby mode when a tuning error occurs. Possible error codes are: 02 = No PID Device Configured 03 = Incorrect Output Action 05 = Insufficient Setpoint-Process Value Deviation 08 = Invalid Tune Results 09 = Tune Timeout

Autotuning Procedure Diagram

Controller is now autotuning

Show 20 more labels / short text on this page
Current · Standby · Flashes · Mode · Mode · Hold for · Press Press · three seconds · Once · Standby · Autotune · Mode · Flashes · Mode · Press · Hold for · Press until · three seconds · Once · appears
Page 32 of the Athena Technologies Center Channel Speaker (16C) user manual — T
Page 32 · click to enlarge
Page 32

Manual Tuning

Manual Tuning Procedure (Zeigler-Nichols PID Method)

While some processes other than heat or cool applications may respond successfully to autotuning procedures, the controller may need to be manually tuned for non-temperature processes.

This tuning method may be used for non-temperature control processes or if the spread between ambient temperature and process operating temperature is small. For best results, the use of a recording device is required when tuning with this method.

1. For temperature control processes, disable any cooling device used.
2. With the power off and the controller NOT in the Key Lockout security level, apply power and immediately put the controller in Standby mode by pressing the Mode/ Enter key for three seconds, the Raise key until appears and press the Mode/Enter key again.
3. If you have a direct-acting output, it must be disabled before proceeding further = .
4. Under the Control menu, make sure that the derivative term , the offset term , and the integral term are all set to zero, and the proportional band or is set to the maximum setting.
5. Adjust setpoint to the desired value with the Raise/Lower keys.
6. Press the Mode/Enter key for four seconds, the Raise key twice , and the Mode/Enter key again to return the controller to normal operation.
7. While monitoring the recording device, decrease the proportional band value by repeatedly halving the value until a small, sustained temperature oscillation is observed. Measure the period of one cycle of oscillation (“T” on the diagram below).

T

8. Divide the period of oscillation (T) by eight. The resulting number is the correct Derivative time in seconds. Multiply this number by four. This is the correct Integral time in seconds.
9. Multiply the bandwidth value obtained in Step 7 by 1.66 and enter this as the new proportional band value.
Page 33 of the Athena Technologies Center Channel Speaker (16C) user manual — Autotune Errors
Page 33 · click to enlarge
Page 33

Error Codes

If an error code cannot be cleared by using the actions provided, contact factory.

Open Sensor Check sensor, wiring, and Input.

Reversed Sensor Check the type selection in the Input menu, and check sensor polarity.

Loop Break Correct problem and reset controller.

Checksum Error Press any key RAM Error to perform a Defaults Loaded soft reset and EEPROM Write Failure reinitialize controller.

Power Fail Resume No further resume Feature Disabled actions available.

Plus other Unexpected or Reset 2-Digit Invalid Interrupt controllers Code

Autotune Errors

If a tune error condition occurs, the upper display will toggle between and a numeric error code for three seconds before the tune process terminates. The controller will then automatically go into Standby mode when a tuning error occurs. Possible error codes are: 02 = No PID Device Configured 03 = Incorrect Output Action 05 = Insufficient Setpoint-Process Value Deviation 08 = Invalid Tune Results 09 = Tune Timeout

Ramp/Soak Errors Possible error codes are: 02 = Recipe Empty (i.e. no non-zero ramp times) 05 = Insufficient Setpoint-Process Value Deviation

Display Problem Actions

Page 34 of the Athena Technologies Center Channel Speaker (16C) user manual — Technical Specifications
Page 34 · click to enlarge
Page 34

Technical Specifications

Operating Limits Ambient Temperature 32°F to 140°F (0°C to 60°C) Relative Humidity Tolerance 90%, Non-Condensing Power 100 to 250 V 50/60 Hz (Single-Phase) 100 to 250 Vdc 24 Vac/dc Power Consumption Less than 6 VA Performance

Accuracy ±0.20% of Full Scale (±0.10% Typical), ±1 Digit Setpoint Resolution 1 Count / 0.1 Count Repeatability ±1 Count Temperature Stability 5 µV /°C (Maximum) TC Cold-End Tracking 0.05°C /°C Ambient Noise Rejection >100 dB Common Mode, >70 dB Series Mode Process Sampling 10 Hz (100 ms) Control Characteristics

Setpoint Limits Automatically Adjust to Selected TC/RTD Alarms Adjustable for High/Low; Selectable Process, Deviation, or Band Alarms Proportional Band 1 to Span of Sensor Integral 0 to 9600 Seconds Derivative 0 to 2400 Seconds Cycle Time 200 ms; 1 to 120 sec Control Hysteresis 1 to Span of Sensor Autotune Operator Initiated from Front Panel Manual Control Operator Initiated from Front Panel Mechanical Characteristics

Display Dual, 4-digit 0.36” (9.2 mm) LED display Process Value: Orange Setpoint Value/Menu: Green Numeric Range -1999 to 9999 Front-Panel Cutout 1.771” x 1.771” (45 mm x 45 mm) Depth Behind Panel 3.937” (100 mm) Front Panel Rating NEMA 4X Operating Temperature 32 to 140° F (0 to 60° C) Humidity Conditions 90% R.H. max., non-condensing Parameter Retention Solid-state, non-volatile memory Connections Input and output via barrier strip with locking terminals Contacts Twin bifurcated

Page 35 of the Athena Technologies Center Channel Speaker (16C) user manual — Technical Specifications
Page 35 · click to enlarge
Page 35

Technical Specifications

Input Type Thermocouple B, C, E, J, K, N, NIC, NNM, R, S, T, Platinel II Maximum lead resistance 100 ohms for rated accuracy RTD Platinum 2- and 3-wire, 100 ohms at 0° C, DIN curve standard (0.00385) 1000 ohms available Linear 0-50 mV/10-50 mV, 0-5 V/1-5 V 0-20 mA/4-20 mA, 0-100 mV, 0-10 V

Output Device B 5 A (120/240 Vac) relay, normally open, used for switching resistive loads. If relays or solenoids are to be driven, select the “T” output. If a “B” output is selected, order snubber network 235Z005U01.

F 4-20 mA, full output to load with 500 ohm impedance max.

G High impedance ‘F’ (800 ohms max.)

S 20 Vdc pulsed output for solid-state relays.

T 1 A @ 120/240 Vac , solid-state relay, zero voltage-switched and optically isolated from drive signal. Only resistive loads to 1A may be controlled directly. Larger loads may be controlled using an external contactor.

Y 5 A (120/240 Vac) relay, but normally closed (output 2 only).

Alarm Type See ordering code on page 55.

E 0-20 mA

Page 36 of the Athena Technologies Center Channel Speaker (16C) user manual — Ordering Codes
Page 36 · click to enlarge
Page 36

Ordering Codes

Options Special Options Output

Code Input Type CT Thermocouple CR RTD CS Compressed RTD CM Millivolt Linear CV Volt Linear CC Current Linear CA All CB TD & T/C

Code Output 1 0 None B Relay (N.O.) E 0 to 20 mA F 4 to 20 mA G High Impedance ‘F’ P 20 Vdc @ 35 mA S Pulsed 20 Vdc T Solid-State Relay X 0 to 10 Vdc

Code Option 00 None Alarms 10 Dual SSR, N.O. 20 Dual Open Collector 21 Dual 24 Vdc 22 Dual SSR, N.C. 23 Relay, N.O. Communications 30 RS-232/Athena+ RS-485, Athena+ with Contact/Digital Input 31 No Switch 36 Switch Close 37 Switch Open 38 5V Input Contact/Digital Input (with Alarm) 40 Switch Closed 41 Switch Open 42 5 V Input RS-485, Modbus with Contact/Digital Input 45 No Switch 46 Switch Close 47 Switch Open 48 5V Input Transducer Excitation 50 10 Vdc 51 12 Vdc 52 15 Vdc 53 5 Vdc Auxiliary Output 60 4 to 20 mA 61 1 to 5 V 62 0 to 20 mA 63 0 to 5 V

Code Option AB Back Cover: Screw Mount AD No-Name Overlay, Standard Athena Patterns and Colors AZ 24 Vac/Vdc Supply EO SPI Communications Protocol EP Engel/Arburg Communications Protocol

Code Output 2 0 None B Relay (N.O.) E 0 to 20 mA F 4 to 20 mA G High Impedance ‘F’ P 20 Vdc @ 35 mA S Pulsed 20 Vdc T Solid-State Relay Y T.C. Relay

Show 4 more labels / short text on this page
Input Calibration Type · 1 Output · Standard · 2 Model
Page 37 of the Athena Technologies Center Channel Speaker (16C) user manual — RTD Calibration Values
Page 37 · click to enlarge
Page 37

Recalibration Procedures

1. Remove power from the controller and disconnect all output devices. Disconnect input. Attach an appropriate calibrator to the input terminals. 2) Apply power to the calibrator, making sure that the displayed value is not outside the range of the controller. Then, apply power to the controller. 3) Index to the Calibration Low menu item in the Calibration Menu.

The Series C controller is precalibrated at the factory. Under normal circumstances, the factory calibration should be valid for the life of the instrument. If recalibration should be required, allow the controller to warm up for 15 minutes and follow these steps carefully.

(You must have Security Level set to “Factory” to access this menu.) 4) Dial Calibrator to prompted value on the controller’s dis- play. See chart below for RTD resistance vs. temperature values. 5) Allow the controller to settle for at least one minute.

6. Press Raise Key.
7. Repeat Steps 4, 5, and 6 for the Calibration High setting.
8. Press the Menu Access key for three seconds to return to the Process Value display.

RTD Calibration Values

RTD Cal Lo 0° C 32° F 100Ω

RTD Cal Hi 768° C 1414° F 366Ω

RT.D Mid-range 328° C 622.4° F 222Ω

Page 38 of the Athena Technologies Center Channel Speaker (16C) user manual — Quick-Helps
Page 38 · click to enlarge
Page 38

Quick-Helps

1. To return the unit to last operating mode (Normal, Standby, FOP, or Tune): Action Display From Menu System: Press and hold PV + SV + Mode for 3 sec.
From Security Level MenuPress PV+ SV + Mode
2. To enter Standby operating mode: Action Display

From Normal Press and hold operating mode: for 3 sec. Press

Athena Technologies Center Channel Speaker (16C) — Quick-Helps diagram (page 38)
Fig. 26 · Quick-Helps

From FOP (Manual) Press and hold operating mode: for 3 sec. Press Press + PV + SV From Menu System: Press and hold for 3 sec.

Press and hold for 3 sec. Press Press + PV + SV

From Security Level Menu: Press PV + SV Press and hold for 3 sec. Press Press + PV + SV 3. To escape from Standby Action Display operating mode: Press and hold for 3 sec.

4. To initiate Autotuning: Action Display Enter Standby operating mode (See Quick-Help #2) Press Press Press + PV + SV
Page 39 of the Athena Technologies Center Channel Speaker (16C) user manual — Quick-Helps
Page 39 · click to enlarge
Page 39

Quick-Helps

5. To abort Autotuning Action Display and return to normal Press and hold operation: for 3 sec. Press Press PV + SV 6. To enter FOP (Manual) Action Display operating mode: Press and hold for 3 sec. Press + PV + % of Power Value Press to set new
Athena Technologies Center Channel Speaker (16C) — Quick-Helps diagram (page 39)
Fig. 27 · Quick-Helps

% of Power Value Press to + PV + set % of Power % of Power

for Output 2 Value if desired. 7. To escape from FOP Action Display (Manual) operating mode: Press and hold for 3 sec. Press

Press PV + SV

Page 40 of the Athena Technologies Center Channel Speaker (16C) user manual — Warranty/ Repairs
Page 40 · click to enlarge
Page 40

Warranty/ Repairs

THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MATERIAL AND WORKMANSHIP. IT IS SOLD SUBJECT TO OUR MUTUAL AGREEMENT THAT THE LIABILITY OF ATHENA CONTROLS, INCORPORATED IS TO REPLACE OR REPAIR THIS EQUIPMENT AT ITS FACTORY, PROVIDED THAT IT IS RETURNED WITH TRANSPORTATION PREPAID WITHIN TWO (2) YEARS OF ITS PURCHASE.

THE PURCHASER AGREES THAT ATHENA CONTROLS, INCORPORATED ASSUMES NO LIABILITY UNDER ANY CIRCUMSTANCES FOR CONSEQUENTIAL DAMAGES RESULTING FROM ITS USE OR FROM IMPROPER HANDLING OR PACKAGING OF SHIPMENTS RETURNED TO THE FACTORY.

COMPONENTS WHICH WEAR OR WHICH ARE DAMAGED BY MISUSE ARE NOT WARRANTED. THESE INCLUDE CONTACT POINTS, FUSES, ELECTROMECHANICAL RELAYS, AND TRIACS. UNITS WHICH HAVE BEEN MODIFIED BY A CUSTOMER IN ANY WAY ARE NOT WARRANTED.

Other than those expressly stated herein, THERE ARE NO OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AND SPECIFICALLY EXCLUDED BUT NOT BY WAY OF LIMITATION, ARE THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY.

IT IS UNDERSTOOD AND AGREED THE SELLER’S LIABILITY WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE RETURN OF THE AMOUNT OF THE PURCHASE PRICE PAID BY THE PURCHASER AND UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE EQUIPMENT IS A CONSIDERATION IN LIMITING SELLER’S LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS OF THIS AGREEMENT MAY BE BROUGHT BY PURCHASER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.

SELLER’S MAXIMUM LIABILITY SHALL NOT EXCEED AND BUYER’S REMEDY IS LIMITED TO EITHER (i) REPAIR OR REPLACEMENT OF THE DEFECTIVE PART OR PRODUCT, OR AT SELLER’S OPTION (ii) RETURN OF THE PRODUCT AND REFUND OF THE PURCHASE PRICE, AND SUCH REMEDY SHALL BE BUYER’S ENTIRE AND EXCLUSIVE REMEDY. THE SPECIFICATIONS PUT FORTH IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Two-Year Limited Warranty

Page 41 of the Athena Technologies Center Channel Speaker (16C) user manual — Technical Specifications
Page 41 · click to enlarge
Page 41

Warranty/ Repairs Unit Repairs It is recommended that units requiring service be returned to an authorized service center. Before a controller is returned for service, please consult the service center nearest you. In many cases, the problem can be cleared up over the telephone. When the unit needs to be returned, the service center will ask for a detailed explanation of problems encountered and a Purchase Order to cover any charge. This information should also be put in the box with the unit. This should expedite return of the unit to you.

This document is based on information available at the time of its publication. While efforts have been made to render accuracy to its content, the information contained herein does not purport to cover all details or variations in hardware, nor to provide for every possible contingency in connection with the installation and maintenance. Features may be described herein which are not present in all hardware. Athena Controls assumes no obligation of notice to holders of this document with respect to changes subsequently made.

Proprietary information of Athena Controls, Inc. is furnished for customer use only. No other use is authorized without the written permission of Athena Controls, Inc.

Page 42 of the Athena Technologies Center Channel Speaker (16C) user manual — IEC Requirements
Page 42 · click to enlarge
Page 42

IEC Requirements

USE OF THIS EQUIPMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR PROTECTION PROVIDED BY THE EQUIPMENT!

The maximum supply current is line voltage dependent:

230 mA for a 24 Vac/dc input fuse rating=700 mA 60 mA for an 85-250 Vac input fuse rating=100 mA

Output Type Max current Voltage Leakage B 5 A 250 Vac 1000 M ohms T 1 A 250 Vpk 1 mA S 20 mA 5 V NA

CLEANING INSTRUCTIONS 1. Remove power from the unit prior to any cleaning operation.

2. Use a cotton cloth to gently and sparingly apply isopropyl alcohol only. Do not use cleaners or other solvents as they may damage the unit.
3. Allow the unit to dry completely prior to reapplying power.

Output Specifications

Page 43 of the Athena Technologies Center Channel Speaker (16C) user manual — Glossary
Page 43 · click to enlarge
Page 43

Glossary

Alarm Delay - the time delay between the detection of the alarm condi- tion and the initiation and indication of the output action. Alarm Inhibit - prevents low setpoint alarm activation during cold startup applications. Bias - allows the operator to compensate for any difference between sensor temperature and the point to be measured. The process display and set- point will be offset by the value entered in the Bias parameter in the input menu. Ex: Desired temperature is 150 degrees. Sensor is adjacent to heater and reads 50 degrees higher than the actual process temperature. Enter bias of -50. Enter setpoint of 150. Process will display 150 even though sensor will be measuring 200 degrees. Blanking - controls the time the setpoint value display remains on. After the set time, the setpoint value display turns off. Pressing any button causes the setpoint value display to reappear for the selected time interval. Cycle Time - The period of time in which the controller’s output completes an on-off cycle (Proportional Output Type only). Example: Output type = Mechanical relay Cycle time = 10 seconds Output power = 50% Controller output = 5 seconds closed, 5 seconds open Deadband - In On/Off temperature control, it is the band above or below the setpoint where there is no output action. It has the effect of moving the apparent setpoint. Derivative (rate) - Adjusts the controller gain quickly in response to load changes. Failsafe State - designates the percentage of power output that the con- troller defaults to after it detects a loop break condition and after the loop break time has elapsed. Filter (in Display menu) - changes the filtering speed for the process value display only. It does not affect control. This parameter is mainly used to slow down the flickering of the display when the decimal position chosen is greater than zero. Filtering (in Input menu) - sets the time period over which the process value is averaged. Highest Reading - records the highest process value read by the controller. It may be reset to zero by using the Raise or Lower arrow keys. Hysteresis - In On/Off temperature control, hysteresis represents the band where the output changes state from deactivated to activated. It prevents chattering around the setpoint and prevents rapid output cycling. Integral (automatic reset) - slowly adjusts the position of the Proportional Band (range of power output) to eliminate offset error. Loop Break - a condition where the input is not changing or responding properly to the output action. This could be caused by a thermocouple or

Page 44 of the Athena Technologies Center Channel Speaker (16C) user manual — Glossary
Page 44 · click to enlarge
Page 44

Glossary

input failure, or a heater or load failure. Loop Break Time - the time interval from when the controller detects a loop break condition and the initiation of the failsafe state. Lowest Reading - records the lowest process value read by the controller. May be reset to zero by using the Raise or Lower arrow keys.

Lower Setpoint Limit - prohibits users from adjusting the setpoint lower than the selected value. Manual Reset - an adjustment that moves the Proportional Band up or down by a fixed percentage so that more or less power is applied at set- point. It is used to eliminate offset error. On/Off Output Type - In a heating application, the controller applies 100% output power if the process temperature is below the setpoint and 0% at the setpoint. For a cooling application, the controller applies 100% output power if the process temperature is above the setpoint and 0% output power at the setpoint. There are only two output states: fully on and fully off. Applications for On/Off Control: 1. When temperature oscillation is acceptable. 2. When constant cycling of mechanical devices is prohibited (Compressors, Blowers, etc.) 3. Under-powered processes Output Low Limit % - Prohibits the controller’s output from going below the specified percentage. Output High Limit % - Prohibits the controller’s output from going above the specified percentage. PID Output Type (Proportional - Integral - Derivative) - The controller modulates output power by adjusting the output power percentage within a proportional band. Power is proportionally reduced as the process temperature gets closer to the setpoint temperature. PID control helps reduce overshoot on start-up, enhances stability, and compensates for process lag. The PID parameters are automatically calculated for a par- ticular application during the autotune procedure. Applications for PID Control: 1. Where process temperature lags exist 2. When load changes are present 3. When overshoot is prohibited 4. When very accurate control is required

Proportional Band - the band (expressed in degrees of temperature) in which the controller modulates its power percentage. Temperature Lag - The product of thermal resistance and thermal capac- ity. Also defined as delay of the transmission of heat from the controlled element to the sensor caused by thermal mass of the process material and/or process container, or the distance between the control element and the sensor. Upper Setpoint Limit - prohibits users from adjusting the setpoint higher than the selected value.

Page 45 of the Athena Technologies Center Channel Speaker (16C) user manual — Quick Setup Instructions - Series 16C Temperature Controller
Page 45 · click to enlarge
Page 45

Quick Setup Instructions - Series 16C Temperature Controller

Experienced users, already familiar with the Series 16C, and using the controller with PID outputs, may follow these condensed instructions to autotune the controller and get started quickly once the instrument is prop-

Athena Technologies Center Channel Speaker (16C) — Quick Setup Instructions - Series 16C Temperature Controller diagram (page 45)
Fig. 28 · Quick Setup Instructions - Series 16C Temperature Co…

erly mounted and wired, and the Security Level is set to . Once setup is complete, we recommend changing the Security Level back to the most restrictive level suitable for your application.

These quick setup instructions are not meant as a substitute for reading the full instruction manual supplied with the controller. Please be sure to read through the manual for specific details of operation and, most importantly, for safety precautions. If you have any questions, or experience problems with setting up your controller, consult the full instruction manual first and, if you still need assistance, contact your Athena representative or call 1-800-782-6776.

Menu Access Raise Lower Mode/Enter

1. Apply power. After self-check display stops, place controller in Standby mode by pressing and holding the Mode/Enter key for 3 seconds, the or key until appears, and then the key again. will flash, alternating with the Process Value.
Athena Technologies Center Channel Speaker (16C) — Quick Setup Instructions - Series 16C Temperature Controller diagram (page 45)
Fig. 29 · Quick Setup Instructions - Series 16C Temperature Co…
2. Press and hold the Menu Access key for 3 seconds until is displayed. Press key once until appears, then use or keys to select sensor input type.
3. Press to display . Then press once to display . Use or to select .
4. Press the key until Output 1 Action is displayed. Select the desired output action using the or keys. (Reverse = Heating)
Athena Technologies Center Channel Speaker (16C) — Quick Setup Instructions - Series 16C Temperature Controller diagram (page 45)
Fig. 30 · Quick Setup Instructions - Series 16C Temperature Co…
Page 46 of the Athena Technologies Center Channel Speaker (16C) user manual — Type
Page 46 · click to enlarge
Page 46

Keep This Information in a Safe Place Configured Parameters Reference Data Series C Temperature Controllers Model Number Zone Location Firmware Version No. (Displayed when the controller is powered up after all the segments on both lines of the display have been tested.) Dear Customer:

Athena Technologies Center Channel Speaker (16C) — Technical Specifications diagram (page 46)
Fig. 31 · Technical Specifications

Please keep this information handy – in case your controller should lose its configured initial parameter

values or for easy reference when setting up a new controller. After auto-tuning, and when your controller is controlling well, we suggest you write the displayed value for each of the menu parameters listed below. If you do not use a listed param- eter, indicate “N/A”. Using this information to document your parameter settings could reduce your downtime. If you have any questions, or need further assistance, please contact Athena Controls Technical Support: Toll-free (in USA): 800.782.6776 Telephone: 610.828.2490 Fax: 610.828.7084 E-Mail: techsupport@athenacontrols.com Website: athenacontrols.com

Configured Parameters Reference Data

Series C Temperature Controllers

Inp

OUTP

CtrL

ALr.

Type

01.tY

db.1

A1.AA

02.tY

BIAs

01.Ac

02.Ac

HYS.1

A1.AO

SCL.L

01.cY

02.cY

db.2

A1.dl

SCL.H

HYS.2

A1.IH

Sp.LL

01.HL

02.HL

Pb1

A1.SP

Sp.HL

01.AA

02.AA

Pb2

A2.AA

I.FIL

01.AO

dEr

A2.Ao

02.AO

Options

01.dl

02.dl

OFFS

A2.dl

01.IH

02.IH

Int

A2.IH

01.SP

A2.SP

02.SP

Page 47 of the Athena Technologies Center Channel Speaker (16C) user manual — Notes
Page 47 · click to enlarge
Page 47

Notes

Page 48 of the Athena Technologies Center Channel Speaker (16C) user manual — 900M011U00 REVISION “B” / 09-13-2004
Page 48 · click to enlarge
Page 48

For Toll-FreeTechnical Assistance in the USA,

Call Toll Free: 1-800-782-6776

Athena Technologies Center Channel Speaker (16C) — For Toll-FreeTechnical Assistance in the USA, diagram (page 48)
Fig. 32 · For Toll-FreeTechnical Assistance in the USA,

Athena Controls, Inc.

5145 Campus Drive Plymouth Meeting, PA 19462 U.S.A.

Tel: (610) 828-2490 Fax: (610) 828-7084 Toll-Free in U.S.: 1-800-782-6776 Internet: www.athenacontrols.com

900M011U00 REVISION “B” / 09-13-2004

Ask about the Athena Technologies Center Channel Speaker (16C)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Athena Technologies Center Channel Speaker (16C)

Be the first to ask — other owners or our team will answer.

Original document

Athena Technologies Center Channel Speaker (16C) manual PDF

48 pages·1.9 MB·Weather Radio·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…