Ethernet Converter Device FMod-TCP BOX User Manual
Version 1.2



Version: 1.2 Last revision: August 14th, 2006 Printed in Switzerland © Copyright 2003-2006 FiveCo Sàrl. All rights reserved. The contents of this manual may be modified by FiveCo without any warning.
Trademarks Windows® is a registered trademark of Microsoft Corporation. Ethernet® is a registered trademark of Xerox Corporation. Java® is a registered trademark of Sun Microsystem. Philips® is a registered trademark of Koninklijke Philips Electronics N.V. Borland® is a registered trademark of Borland Software Corporation. Warning This device is not intended to be used in medical, life-support or space products. Any failure of this device that may cause serious consequences should be prevented by implementation of backup systems. The user agrees that protection against consequences resulting from device system failure is the user's responsibility. Changes or modifications to this device not explicitly approved by FiveCo will void the user's authority to operate this device. Support Web page: http://www.fiveco.ch/section_motion/support_motion_E.htm e-mail: [email protected]



1 Package and operating conditions
The FMod-TCP BOX “Starter kit” should contain:
FMod-TCP BOX device RS232 DSub cable DIN 41651 40 lines cable CD-Rom with dedicated software and Java applet sample This manual
Damage may occur if the device is operated using values beyond those mentioned below; device operation is not guaranteed.
Parameter Conditions Min Typ Max Unit Supply voltage 0 24 33 V Supply current No device connected to extension connector.
Supply current Device(s) connected to extension connector.
Outputs 1, 2 current Relays. 1 A Outputs 1, 2 voltage Max voltage to GND. 50 V Outputs 3-14 current 0.5 A Outputs 15, 16 current 1 A Inputs voltage -15 28 V +5V output current Pin 17 on extension connector. 0.4 A Power output current Pin 40 on extension connector. 1 A Operating temperature 0 70 °C Storage temperature -40 120 °C All external pins are protected against destruction by ESD (2kV). The power supply input is protected against over and inverted voltage by a 33V Zener diode. The protection is guaranteed during 10ms within the following current values:
For inverted voltage: 100A (the internal polifuse will cut the supply). For over voltage: 3.25A max (the diode will be destroyed before the
fuse after 10ms!). Damages to the device due to over or inverted voltage are not covered by the warranty.
60 100 mA

2 Overview
The operating principle for PC softwares that must exchange data with an FMod-TCP BOX device depends on which interface is used. In case of RS232 use, the operation is really simple. Any byte sent to port TCP #8000 will be redirected to the serial bus and any byte received from the serial bus will be redirected to the TCP connection. In the other cases (I/O, A/D and I2C), the software has to use a dedicated protocol layer on top of the TCP Layer (see chapter 4). This protocol is

"Question & Answer" oriented. The PC should send a Question, wait for the Answer and so on. To configure the device's parameters and to access I/O and A/D features, the protocol uses an Internal Registers Access routine (see chapter 4 and 7). The code samples available on the FiveCo's web site can help programmers get started with development.

Inputs, Outputs, I2C bus, Supply voltage, 5V and GND
Ethernet connector SOS button
Beware: Before connecting any cable to the device, shut down power supply!

RJ45 Ethernet connector SOS button
Power connector · RS232 connector · Dimensions in mm



aDo not supply the device throu s r connector.
gh thi pin. Use powe
Here are the equivalent electrical specif s of I/O pins (illustra black dots):
Inputs Outputs 3-16 Outputs 1-2
B

The I2C pins are provided through a Philips PCA9512 driver chip. 10kΩ pull
-ups are connected to A.
ht side
Standard RS232 DSub 9 connector
(male like on a computer)
The RS232 connector is the same as the ones found on any computer.
A button is dedicated to restore default IP address or factory settings. There are tow possible scenarios:
If you press it while the device is running, the IP address will be
r l TC tions a have to send the Save Settings command to the device in order to save it into EEPROM.
estored as soon as al P connec re closed. Warning: you
and factory settings of all parameters will be restored AND saved into EEPROM. In this case, you do not need to send the Save Parameters command.
If the button is pressed during startup, the default IP address
SCL and SD

3 Quick start
This section is intended to help users to quickly plug the module into their system and establish a connection between the computer and the device. You can find the device’s factory communication settings on the following label.
This device is not intended to be used in a medical, life-support or space product. Any failure of this device that may cause serious consequences should be prevented by implementation of backup systems. The user agrees that protection against consequences resulting from device system failure is the user's responsibility. [email protected] / www.fiveco.ch
The Ethernet MAC Address is fixed and cannot be changed. The IP Address can be changed. The complete procedure is described below. Note: If the device has already been configured and the IP address has been changed to an unknown value, you can retrieve an SOS IP address (the one on label) by pressing the “SOS button” during the normal operation of the device. (See section Erreur ! Source du renvoi introuvable.).
To easily change the factory IP address, use the Win32 software provided on the CD-Rom.
1. Plug your new device on your PC network. 2. Start the Win32 application. 3. Click on "File->Easy change IP address". 4. The software will scan the network and display a list of all FiveCo's devices found. 5. Select the MAC address corresponding to your new device. 6. If you have more than one network adapter on your PC, the software will ask you to select the one which is connected to the same network as the FMod-TCP BOX. 7. The software will suggest a new IP address with the last byte left open. Choose a new IP (Not already used on your network!!) and click the "Change IP address" button. That’s it! The device has a new address and a new subnet mask (the same as your PC). They are automatically saved into EEPROM.

You can now connect the device with the Win32 software or open its web page by typing its new IP address into a web browser. Notes:
The IP address won't be changed if a TCP connection exists with the
device. The protocol used to change the IP address is described later in this
manual.

4 Controlling the FMod-TCP BOX by TCP or UDP
All the device's parameters (configuration registers) and features can be accessed through a TCP or UDP port. In addition, an HTTP-TCP port is available for web pages downloading and another TCP port for RS232 bus access. Those ports are:
TCP Port #80 for HTTP communication. TCP Port #8000 for RS232 transceiver. TCP Port #8010 to access I/O registers (see chapter 7) and I2C bus. UDP Port #7010 to access I/O registers (see chapter 7) and I2C bus. With regards to TCP connections, the device allows up to 4 simultaneous connections. These ports are described below.
The RS232 bus of the microcontroller is accessible through the TCP port number 8000. The module acts simply as a transceiver for this port. Any byte sent from the network (ex: TCP-IP from a PC) to the module will be sent to the other side’s RS232 bus, and vice versa. Thus there is no particular protocol dedicated to this feature. See later chapters to know how to change parameters such as baud rate and hardware flow control. Note: This port supports only one user at a time. RS232 fixed settings: No parity / 1 Start Bit / 8 Data Bits / 1 Stop Bit Important note about baud rate greater than 9600bds: Common TCP/IP stacks (on PC, Unix station …) use a delay of 200ms for the acknowledgement of the TCP received data packets. This is done to reduce traffic on the network because TCP allows the acknowledgement of several packets at one time. Unfortunately, the FMod-TCP BOX device needs this acknowledgement to remove the data from its internal RS232 receive buffer (if no acknowledge is received from the PC, the module will resend those data).

So, with speeds greater than 9600bds, the buffer may be filled faster than data can be sent by TCP and part of those will be lost if no RS232 hardware flow control is used between the FMod-TCP BOX and the RS232 device (CTS and RTS lines). If you cannot use hardware flow control on RS232 bus and you have to get more than 2048 bytes at one time, the solution is to reduce the TCP acknowledgement delay on your computer. For WindowsTM 2000/XP users, you can add/change the following value in the registry. BEWARE: improperly changes done in the Windows registry can results in a system crash! Such changes are the user’s full responsibility!
Entry: HKey_Local_Machine\SYSTEM\CurrentControlSet\Services\ Tcpip\Parameters\Interfaces\Interface-name Key: TcpDelAckTicks Value: DWORD with value 0x00 The interface-name is the registry name (32 digits number) of your Ethernet card which you use to access the module. The following web page describes this feature in details: http://www.microsoft.com/resources/documentation/Windows/2000/server/reskit/en- us/regentry/58801.asp?frame=true
Device parameters and I/O, A/D and I2C features (TCP # 8010 or UDP # 7010)
The main TCP port number 8010 or UDP port number 7010 can be used to change some important parameters of the module:
TCP timeout value IP address Subnet mask Module name Baud rate and flow control I2C speed The user should use the Win32 application enclosed in the package or the default java applet loaded in the module to change those parameters. If the user wants to change the parameters by himself, the protocol is defined below. This port is also used to access Inputs and Outputs value, A/D conversion result registers (see page 34 for a complete description of those registers) and I2C bus. The I2C feature is described after “registers access feature”. The last feature accessible through this port is the "Easy IP config" that is used in the "Quick start" chapter of this document.

TCP/IP works in big endian: most significant byte first, followed by least significant byte. The access to the data is done through an easy (6 byte header) protocol over TCP. Structure of each packet:

Byte# Number of bits Example 0x00 Read (0x0021) 16 bits 0x0021 0x02 TransactionID 16 bits 0x1B34 0x04 Number of registers to read (X)
0x06 X * Registers Addresses X * 8 bits 0x02 0x06+X Checksum 16 bits 0x…
The maximum number of registers that can be read at one time is almost 30. The answer sequence should not be greater than 180 bytes. If the number of registers is too big, the FMod-TCP BOX will answer only with the value of some of them. The module answers with the following sequence:

Byte# Number of bits Example 0x00 Read Answer (0x0023) 16 bits 0x0023 0x02 TransactionID (same as demand)
0x04 Number of bytes in answer 16 bits 0x0019 0x06 Register address 8 bits 0x02 … Register value 8—128 bits (16B) 0x12345
The two previous entries are replicated for every register that has been asked for reading
… Checksum 16 bits 0x…

Write register(s) command:

Byte# Number of bits Example 0x00 Write (0x0022) 16 bits 0x0022 0x02 TransactionID 16 bits 0x1B34 0x04 Number of bytes in command
0x06 Register Addresses 8 bits 0x02 0x07 Register value 8 — 64 bits 0x1234
The two previous entries are replicated for every register that has been asked for reading
The max length of this sequence is 180 bytes. The module answers with the following sequence:

Byte# Number of bits Example 0x00 Write Answer (0x0024) 16 bits 0x0024 0x02 TransactionID (same as demand)
0x04 0x0000 16 bits 0x0000 0x06 Checksum 16 bits 0x…
The Inter-IC bus, commonly known as the I²C bus, is a control bus that provides the communications link between integrated circuits in a system. Developed by Philips in the early 1980’s, this simple two-wire bus has become the de facto worldwide standard for system control, finding its way into everything from temperature sensors and voltage level translators to EEPROMs, general-purpose I/O, A/D and D/A converters, CODECs, and microprocessors of all kinds. You can find the I2C’s specifications on the Philips web site at the following link: http://www.semiconductors.philips.com/ The I2C protocol can access a device by three different manners:
Write (Start, AddW, Byte1, Byte2, …, Stop)
St AddW A Bytes to W A Sp Read (Start, AddR, Byte1, Byte2, …, Stop)
St AddR A Bytes to R nA Sp Read After Write (Start, AddW, ByteW1, ByteW2, …, ReStart,
AddR, ByteR1, ByteR2, …Stop)
St AddW A Bytes to W R A AddR A Bytes to R nA Sp

To be able to do all of these 3 sequences, use this command:
Byte# Number of bits Example 0x00 I2CRWwithAck (0x0007) 16 bits 0x0007 0x02 TransactionID 16 bits 0x1B34 0x04 LengthOfParameters (X + 3) 16 bits 0x0005 0x06 7 bits Address (bit 7 = 0) 8 bits 0x28 0x07 X (number of bytes to write) 8 bits 0x02 0x08 xBytes X bytes 0xAF1D …. Y (number of bytes to read) 8 bits 0x05 The four previous entries can be replicated to access the same or other I2C slaves within this command sequence. Checksum 16 bits 0x… If X = 0, the Read method is used. If Y = 0, the Write method is used. If X & Y ≠ 0, the Read after Write method is used. The answer sequence is the following one:

Byte# Number of bits Example 0x00 I2CReadAnswer (0x0008) 16 bits 0x0008 0x02 TransactionID (same as demand)
0x04 Number of bytes in answer 16 bits 0x0005 0x06 Answer bytes Y bytes 0x1A25… … Ack state of the I2C com. 1 byte 0x87 If the same or other I2C slave have been accessed in the command, the answer bytes and ack state is added here. … Checksum 16 bits 0x… The "Ack state" byte is composed of the following bits:
0 Address ack in write sequence 0 = No answer to this address 1 = ack received 1 Bytes written ack (each byte was acked) 0 = Bytes not acknowledged 1 = ack received 2 Address ack in read sequence 0 = No answer to this address 1 = ack received 3-6 Reserved - 7 Must be always 1 1 The user can use these bits to check for the presence of his I2C devices and monitor hardware issues.


Note that the max length of those sequences is 180 bytes. Pay close attention to building sequences that do not exceed this and not to ask too much byte in answer ! The FMod-TCP BOX translates automatically those sequences to I2C sequences. It is mandatory that the sequence has to be transmitted within one TCP packet. Otherwise, the FMod-TCP BOX will ignore it.
The following command allows user to ask an I2C bus scanning to list which addresses answer with an acknowledge. I2C scan command:
Byte# Number of bits Example 0x00 I2CScan (0x0005) 16 bits 0x0005 0x02 TransactionID 16 bits 0x2001 0x04 Number of addresses to scan 16 bits 0x0001 0x08 X Addresses X bytes 0x1A Checksum 16 bits 0x… The FMod-TCP BOX answers with the following sequence:


Byte# Number of bits Example 0x00 I2CScanAnswer (0x0006) 16 bits 0x0006 0x02 TransactionID (same as demand)
0x04 Number of valid addresses 16 bits 0x0001 0x06 Valid addresses list n bytes 0x1A Checksum 16 bits 0x… Note: If there is no address in the I2C Scan command, the FMod-TCP BOX will scan all addresses between 1 and 127!
The I2C bus speed can be changed at any time by changing the content of the I2CSPD parameter. Beware:

1 2 10 2
wanted CSpeed I CSPD I
The I2C speed cannot be saved in EEPROM.
7 − =

A really useful feature of the UDP port #7010 is the "Easy IP config" one. The user who wants to design his own software can use this feature to do a "quick start/install" method. Indeed, since this protocol uses a broadcast UDP packet, even if the device is not in the same subnet, it should receive its new IP address and subnet mask. Procedure: Send a UDP broadcast message (using a local or direct broadcast IP address) to your network (inside which the FMod-TCP BOX is connected) with the following command:

Byte# Number of bits Example 0x00 Change IP fct (0x002A) 16 bits 0x002A 0x02 TransactionID 16 bits 0x0000 0x04 Length of params (0x000E) 16 bits 0x000E 0x06 FMod-TCP BOX Mac Address 6 bytes 0x0050C2308101 0x0C FMod-TCP BOX new IP Address
0x14 Checksum 16 bits 0x… If the FMod-TCP BOX recognizes its MAC address, it will answer this command with a simple acknowledges and change its IP address and subnet mask IF NO TCP CONNECTION IS MADE TO THE DEVICE.
Byte# Number of bits Example 0x00 Change IP fct ack (0x002B) 16 bits 0x002B 0x02 TransactionID 16 bits 0x0000 0x04 Length of params (0x0000) 16 bits 0x0000 0x14 Checksum 16 bits 0x…


This checksum is the same as the IP checksum. Definition: sum of 1’s complement of all 16 bits words of whole message (FiveCo packet) except checksum bytes. Note: all values are unsigned! Sequence: 1. Clear accumulator Loop x. Only if last word is not made of two bytes, the data byte is the upper byte (big endian) 2. Compute 1’s complement of each 16bits word, result is 16bits 3. Convert last result from 16 bits to 32 bits, result is 32bits: 0x0000+last result 4. Add last result to the 32 bits accumulator Try the Loop 5. Convert accumulator in two 16bits words 6. Add those two 16bits words, result is 16bits word. 7. If an overflow occurs with the last addition (Carry), add 1 to the last result. 8. Last result is the final result Example (in hexadecimal): !0x0021 (0XFFDE) Æ 0x0000FFDE (Read) +!0x1234 (0xEDCB) Æ 0x0001EDA9 (TransID) +!0x0003 (0xFFFC) Æ 0x0002EDA5 (3 reg to read) +!0x0A10 (0XF5EF) Æ 0x0003E394 (reg 0A,10,02) +!0x02(00)(0XFDFF) Æ 0x0004E193 Note that in this case a last 00 is implicitly used. (02 Æ 02 00).
0x0004 + 0xE193 = 0xE197, (carry=0) 0
xE197 + carry = 0xE197
Checksum = 0xE197

Here is an example of a checksum calculation function in C: int RetCheckSum(Byte* ByteTab, int Size) { // This function returns the calculated checksum unsigned int Sum=0; bool AddHighByte=true; unsigned int ChecksumCalculated; for(int i=0;i>16)&0xFFFF)
+(ChecksumCalculated&0xFFFF); return ChecksumCalculated; } This function needs a Byte array (ByteTab) containing the command sequence and this array’s length (Size) as input, it returns the checksum as an int.

5 Java Applet
A specific Java Applet is provided with the module to control any of its ports without having to write any specific code.
To connect to the http server on the device, simply open your web browser and type the IP address of the module. Example with default address: “http://169.254.5.5” The applet is downloaded from the device to your computer and runs as a local process (on your computer). You need to use an internet web browser that is compatible with Java 1.1. Please note that on an MSWindowsTM based computer, a few seconds delay can occur when you download the applet due to an MSWindowsTM NetBios issue. The navigation through the four panels of the applet is done through the menu bar:




This page can be used to access Inputs state and voltage and change Outputs state. The Inputs state and voltage are regularly updated automatically (20 kHz). You can change the low to high threshold of the inputs between 0 and 24V. This page display also the device supply voltage and warnings (Too low/high supply voltage, Outputs driver over current or temperature).


This page can be used to access RS232 bus. If you click on the "Connect to RS232 TCP Port" you can send ASCII data to RS232 bus and receive data from it (only ASCII is visible in this application).

You can check "Add LF", "Add CR" and/or "Add Null" boxes to add a Line Feed, a Carriage Return and/or a Null Byte at the end of the ASCII chain sent to the device.

This page can be used to access I2C bus. The panel is divided in two parts:
The part on the right allows scanning the I2C bus to find available
slave devices. The part on the left allows sending a read or a write command to a
device on the I2C bus.

You should first check if you want a read or a write. Then you have to write hex data to write to the device in the "Hex data to write" field (if you

checked the "Read" box, the FMod-TCP BOX will use the read after write I2C feature). After writing the I2C address (7bits hexa) and the number of bytes to read (if applicable), click on the "Send" button. The answer is displayed in hex in the "Data received" field.

6 Win32 Application
A specific application is provided with the module to control any of its ports without having to write a specific code.

IP address of the module Open or close TCP port
To open a TCP port on the module, the user has to set the correct IP address of the module, to choose the correct TCP port in the list and to click on the "Open" button. To close the port, simply click on the "Close" button. The status bar displays the status of the connection:
Connected Disconnected Error of connection (if connection was not established within 30s) Note: If you forgot the IP address of the module, you can use the "Scan network" feature of the "Connection" menu.


This application uses the IP address of your computer and its subnet mask to find the scan broadcast address. When you click on scan, a broadcast message will be sent to all devices in your subnet and answers will be listed. WARNING: it only works with devices in your subnet! How does it work? When you click "Scan", the software simply sends a "Read registers" command to a broadcast address on UDP port number 7010 (see chapter about main port at page 13). The broadcast address depends on the network subnet mask present on your PC.


chain to send Send ASCII, Hex, or Decimal chain
Bytes received from RS232
The RS232 interface is easy to use. Just write the ASCII, HEX or decimal string in the dedicated text box and click corresponding "Send" button. The received bytes are displayed into the "Data received" boxes (same data but different representation).


File(s) list operations List of files to load
Number of bytes in list
Create file for factory upload
Load files into module
This option allows users to load their personal web files (html, java, jpeg, gif, txt …) into the flash memory. A maximum of 44kB is available for that application. An example of pages and Default Java Applet code is available on the Starter Kit CDRom or on the FiveCo's web page. For factory web upload, the user can save a single file yourname.web. See FMod-TCP BOX_WebPageUploading manual on the FiveCo web site.


Change RS232 baud rate Outputs state and flow control
Inputs state and voltage Change IP address of the module
Change subnet mask of the module Scan I2C bus
Number of bytes to read from I2C
Change module name Hex data to write to
Bytes received from I2C I2C operation
I2C Address The configuration interface allows the user to change the device’s settings. RS232 baud rate: The user can change the RS232 baud rate and enable or
disable the hardware flow control (CTS/RTS). TCP timeout: The user can change the number of seconds allowed before TCP port is disconnected. This feature avoids the problems due to the crash of a TCP client (PC). IP address: The user can change the IP address of the module. Subnet mask: The user can change the subnet mask of the module. MAC address: Mac address of the module (cannot be changed). Name: Module name. The Inputs state and voltage are simply obtained with a click on the corresponding “Read” button. The Outputs state and the analog threshold are send to the device with a click on the corresponding "Write" button.
Change disconnection timeout · Module MAC address

The I2C interface is an easy way to test the I2C connection between the module and the user's electronic. The user has to choose between an I2C Read or Write operation. In Write mode, the bytes (in hexadecimal like 41 42 45 separated by spaces!) must be written in the dedicated line and the I2C address in the dedicated Address space (in hexadecimal or in decimal). Then click "Send". In Read mode, the steps are the same except that the user must specify how many bytes have to be read. Data to write is optional (only used for ReadAfterWrite I2C method).

7 Registers management
The user must know that a new register value sent through the communication port is loaded to the running parameters in RAM and used for the current process. All these parameters are lost upon power-down. It is required to save them to “User Parameters” or “Factory Parameters” with the corresponding function.
NON VOLATILE DATA.
EEPROM EEPROM ROM USER Parameters
5 1 2 3 4
VOLATILE DATA.
WRITE
READ
PROCESSES
(TCP/UDP) [Web page or Software]
Action Number and description: 1 SaveUserParameters (0x03) function During standard power-up or calling 2 RestoreUserParameters (0x04) function 3 RestoreFactoryParameters (0x05) function SaveFactoryParameters (0x06) function + 1 4 [For integrators engineers only] 5 By setting “SOS Jumper” after power-up 3 5 + + 1 By setting “SOS Jumper” during power-up

List of registers
Address Bytes Name General Information
0x00 (00) 4 TYPE 0x01 (01) 4 VERSION 0x02 (02) 0 (fct) RESETCPU 0x03 (03) 0 (fct) SAVEUSERPARAMETERS 0x04 (04) 0 (fct) RESTOREUSERPARAMETERS 0x05 (05) 0 (fct) RESTOREFACTORYPARAMETERS 0x06 (06) 0 (fct) SAVEFACTORYPARAMETERS 0x07 (07) 4 VOLTAGE 0x08 (08) 4 WARNINGS Communication
0x10 (16) 4 COMOPTIONS 0x11 (17) 6 ETHERNETMAC 0x12 (18) 4 IPADDRESS 0x13 (19) 4 SUBNETMASK 0x14 (20) 1 TCPTIMEOUT 0x15 (21) 16 MODULENAME 0x16 (22) 1 RS232CONFIG 0x18 (24) 1 I2CSPD 0x1A (26) 1 TCPCONNECTIONSOPENED I/Os and AD
0x20 (32) 4 ANALOGINPUTSTHRESHOLD 0x21 (33) 2 OUTPUTS 0x23 (35) 2 INPUTS Analog voltage at inputs
0x30 (48) 4 INPUTVOLTAGE0VALUE 0x31 (49) 4 INPUTVOLTAGE1VALUE 0x32 (50) 4 INPUTVOLTAGE2VALUE 0x33 (51) 4 INPUTVOLTAGE3VALUE 0x34 (52) 4 INPUTVOLTAGE4VALUE 0x35 (53) 4 INPUTVOLTAGE5VALUE 0x36 (54) 4 INPUTVOLTAGE6VALUE 0x37 (55) 4 INPUTVOLTAGE7VALUE 0x38 (56) 4 INPUTVOLTAGE8VALUE 0x39 (57) 4 INPUTVOLTAGE9VALUE 0x3A (58) 4 INPUTVOLTAGE10VALUE 0x3B (59) 4 INPUTVOLTAGE11VALUE 0x3C (60) 4 INPUTVOLTAGE12VALUE 0x3D (61) 4 INPUTVOLTAGE13VALUE 0x3E (62) 4 INPUTVOLTAGE14VALUE 0x3F (63) 4 INPUTVOLTAGE15VALUE

Register Address Register Name Function Read/Write Control
0x00 TYPE Product ID Read only
Register Size Register structure
4 Bytes Unsigned Int 16bits (HH-HL) TYPE Unsigned Int 16bits (LH-LL) MODEL
Description: Product identifier composed with a Type and Model number. It defines which kind of peripheral it is. Normally different modules TYPE are not software compatible.

Register Address Register Name Function Read/Write Control
0x01 VERSION Software ID Read only
Register Size Register structure
4 Bytes Unsigned Int 16bits (HH-HL) Version Unsigned Int 16bits (LH-LL) Revision
Description: Firmware identifier composed with a Version and Revision number. Same Version with different Revision is backward compatible.
Example: Firmware 0x0001000A = Version 1, Revision 10 is compatible with all earlier revisions of the same version (ver 1.0 to 1.9). However, it has new functionalities (which are deactivated by default) or code optimizations.

Function Address Function Name Function Read/Write Control
0x02 RESETCPU Restart processor Write only
0 Byte none none
Description: Reboots the device. The communication will be lost.

Function Address Function Name Function Read/Write Control
0x03 SAVEUSERPARAMETERS Saves all in EEPROM Write only
0 Byte none none
0x12 IPADDRESS 0x13 SUBNETMASK 0x14 TCPTIMEOUT 0x15 MODULENAME 0x16 RS232CONFIG

Function Address Function Name Function Read/Write Control
0x04 RESTOREUSERPARAMETERS Restores saved values Write only
0 Byte none none
0x12 IPADDRESS 0x13 SUBNETMASK 0x14 TCPTIMEOUT 0x15 MODULENAME 0x16 RS232CONFIG

Function Address Function Name Function Read/Write Control
0x05 RESTOREFACTORYPARAMETERS Factory default Write only
0 Byte none none
0x12 IPADDRESS 0x13 SUBNETMASK 0x14 TCPTIMEOUT 0x15 MODULENAME 0x16 RS232CONFIG

Function Address Function Name Function Read/Write Control
0x06 SAVEFACTORYPARAMETERS Save factory default Write only
0 Byte none none
0x12 IPADDRESS 0x13 SUBNETMASK 0x14 TCPTIMEOUT 0x15 MODULENAME 0x16 RS232CONFIG

Register Address Register Name Function Read/Write Control
0x07 VOLTAGE Power input voltage Read only
4 Bytes Signed (2’s cplt) Int 16 (HH-HL) +16 bits fixed point (LH-LL) Volt
Information: Over 32 V (0x00200000) the overvoltage warning bit is set and the overvoltage protection diode should increase power current. Below 12 V (0x000C0000) the undervolatge warning bit is set. Below effective 6.5 V (0x00068000), this value has no meaning.
Active: Each time the processor is running.

Register Address Register Name Function Read/Write Control
0x08 WARNING Bit to bit state R/W
4 Byte Unsigned Int 32 bits , each bit independent none
Description: Each information/warning/error is contained in 2 bits: the first one (from LSB to MSB) shows the actual state, the next one shows if this state appeared previously. Only the bits that show the past states can be cleared by writing 0x00000000 to WARNING register.
Bits when set 0-1 Over-temperature occurred on outputs stage. 2-3 Over-current occurred on outputs stage. 4-5 Under-voltage of the power input. 6-7 Over-voltage of the power input. Other bits are reserved. If any warning bit is set, the LED on the SOS button will become red.
Active: Each time the processor is running.

Register Address Register Name Function Read/Write Control
0x10 COMOPTIONS Communication options Read/Write
4 Bytes 32 individual bits none
Description: This register is reserved for future use.

Register Address Register Name Function Read/Write Control
0x11 ETHERNETMAC Hardware network ID Read only
6 Bytes 6 x Unsigned Bytes none
Description: A standard hardware unique identifier (worldwide) for each device on an Ethernet network.

Register Address Register Name Function Read/Write Control
0x12 IPADDRESS IP network ID Read/Write
4 Bytes 4 x Unsigned Bytes none
Description: Network identifier used for TCP/IP and UDP/IP. The values 255 (0xFF) and 0 (0x00) are reserved for broadcast and network addresses and should not be used in this register.
Example: For the IP=192.168.16.14 (0xC0, 0xA8, 0x10, 0x0E), write 0xC0A8100E to IPADDRESS.

Register Address Register Name Function Read/Write Control
0x13 SUBNETMASK IP subnet mask Read/Write
4 Bytes 4 x Unsigned Bytes none
Description: Network IP subnet mask used for TCP/IP and UDP/IP.
Notes: The module will change for a new subnet mask only when all of its communications ports are closed. Do not forget to use a SAVEUSERPARAMETERS command. If you do not want to use subnets, use the following subnet mask when IP address byte 0 is: >0 and 127 and 191 and
Example: For the IP=10.2.6.45 and subnet mask = 255.255.0.0: IP address class = A Æ netID = 10, subNetID = 2 and hostID = 6.45

Register Address Register Name Function Read/Write Control
0x14 TCPTIMEOUT Timeout for TCP connection Read/Write
1 Byte Unsigned Int 8 bits sec
Description: The TCP timeout is a value (in seconds) after which the user will be disconnected if the device has not been accessed in the meantime. If the value is 0, the TCP timeout is deactivated. In this case however, if the client crashes during connection, the communication will never be closed on the module’s side! Because a maximum of 4 communications are allowed at the same time on the module, one of them will be blocked. If the client crashes four times, all of the 4 communications will be blocked and the module will have to be reset! The timeout for each TCP/IP connection is reloaded when there is traffic through the port.

Register Address Register Name Function Read/Write Control
0x15 MODULENAME Module’s ASCII name Read/Write
16 Bytes 16 (only) x Unsigned Bytes (CHAR) none
Description: Name and/or description of the module.
Example: For the name “Hello Module”; extend to 16 byte the name: “Hello Module”+5x space=16 Byte. So write 0x48656C6C 6F204D6F 64756C65 20202020.

Register Address Register Name Function Read/Write Control
RS232 baud rate and flow control configuration
1 Byte Unsigned Int 8 bits none
Description: RS232 baud rate and flow control configuration.
Bits 0-2 Baud rate configuration : 0 : 4800 bds 1 : 9600 bps (default) 2 : 19200 bps 3 : 38400 bps 4 : 57600 bps 5 : 115200 bps 6 : 115200 bps 7 : 115200 bps Bits 3-6 Reserved Bit 7 Hardware flow control bit (0 = disabled, 1 = enabled)
0x16 RS232CONFIG · Read/Write

Register Address Register Name Function Read/Write Control
0x18 I2CSPD I2C speed setting Read/Write
1 Byte Unsigned Int 8 bits none
Description: I2C speed setting between ~39kHz and 400kHz. The value of this parameter must be computed with the following formula based on the wanted speed:
1 2 10 2
wanted CSpeed I CSPD I
7 − =

Register Address Register Name Function Read/Write Control
Number of TCP connections that are opened
1 Byte Unsigned Int 8 bits none
Description: Number of users connected to the device using TCP. Value can be 0 to 4.
0x1A TCPCONNECTIONSOPENED · Read only

Register Address Register Name Function Read/Write Control
AD converter threshold on inputs
4 Bytes Signed (2’s cplt) Int 16 (HH-HL) +16 bits fixed point (LH-LL) Volt
Description: Defines the threshold used by the AD converter on inputs pins to define input state as low or high (0 or 1).
Example: If your inputs use 5V TTL signals, set this value between 1 and 4 V.
0x20 ANALOGINPUTSTHRESHOLD · Read/Write

Register Address Register Name Function Read/Write Control
0x21 INPUTS 16 inputs states Read only
2 Bytes Unsigned Int 16 bits, each bit independent none
Description: Show digital state of each inputs pin. The state is defined by comparing actual input voltage with the ANALOG INPUTS THRESHOLD.
Bit 0 INPUT #1 Bit 1 INPUT #2 Bit 2 INPUT #3 Bit 3 INPUT #4 Bit 4 INPUT #5 Bit 5 INPUT #6 Bit 6 INPUT #7 Bit 7 INPUT #8 Bit 8 INPUT #9 Bit 9 INPUT #10 Bit 10 INPUT #11 Bit 11 INPUT #12 Bit 12 INPUT #13 Bit 13 INPUT #14 Bit 14 INPUT #15 Bit 15 INPUT #16
Example: b'0000 0000 0000 0111' Æ Inputs number 1, 2 and 3 are high and others are low.

Register Address Register Name Function Read/Write Control
0x23 OUTPUTS Sets outputs states Read/Write
2 Bytes Unsigned Int 16 bits, each bit independent none
Description: Controls the state of each of the output pins.
Bit 0 OUTPUT#1 (Relay A) Bit 1 OUTPUT#2 (Relay B) Bit 2 OUTPUT#3 Bit 3 OUTPUT#4 Bit 4 OUTPUT#5 Bit 5 OUTPUT#6 Bit 6 OUTPUT#7 Bit 7 OUTPUT#8 Bit 8 OUTPUT#9 Bit 9 OUTPUT#10 Bit 10 OUTPUT#11 Bit 11 OUTPUT#12 Bit 12 OUTPUT#13 Bit 13 OUTPUT#14 Bit 14 OUTPUT#15 Bit 15 OUTPUT#16
Example: b'0000 0000 0000 0111' Æ Outputs number 1, 2 and 3 are high and others are low.

Registers Addresses Register Name Function Read/Write Control
0x30 to 0x3F INPUTVOLTAGExVALUE Last INPUTVx A/D conversion result Read only
4 Bytes Signed (2’s cplt) Int 16 (HH-HL) +16 bits fixed point (LH-LL) Volt
Description: Voltage value of the 16 inputs pins between -12V and 12V. This value saturates at ~ -15.5V and 24V.

Contact address : FiveCo - Innovative Engineering PSE-C CH-1015 Lausanne Switzerland Tel: +41 21 693 86 71 Fax: +41 21 693 86 70 www.fiveco.ch [email protected]