CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBEp.42.2. Indoor Unitp.4Automatic Operation Switchp.4Quiet Modep.424-Hour Real Time Timer Controlp.4Operation Indication Lamps (LED)p.4Automatic Restart Controlp.4Microcomputer-controlled Room Temperature Controlp.4Breakdown Self Diagnosis Functionp.4Low Pressure Control (Gas Leakeage Detection)p.4Indoor Power Relay Controlp.4Anti-Dew Formation Controlp.4Four Operation Modesp.4Anti Freezing Controlp.4Automatic and 5 Manual Indoor Fan Speedsp.4Anti-Cold Draft Controlp.4Hot Startp.4Airflow Direction Controlp.4Intake Air Temperature Controlp.4High Pressure Controlp.4Deodorizing Controlp.4Powerful Modep.4Deice Operationp.43.1. CS-E15DB4EW CU-E15DBE 3 Product Specificationsp.6SIDE VIEWp.6TOP VIEWp.6INTAKEp.63.2. CS-E18DB4EW CU-E18DBEp.83.3. CS-E21DB4ES CU-E21DBEp.104 Dimensionsp.124.1. Indoor Unit & Remote Controlp.124.1.1. CS-E15DB4EW CS-E18DB4EW CS-E21DB4ESp.124.2. Outdoor Unitp.134.2.1. CU-E15DBE CU-E18DBE CU-E21DBEp.135 Refrigeration Cycle Diagramp.146 Block Diagramp.157 Wiring Diagramp.168 Operation Detailsp.178.1. Basic Operationp.178.1.1. Temperature Shifting Flowp.178.1.2. Cooling Operationp.188.1.2.1. Thermostat controlp.188.1.3. Soft Dry Operationp.188.1.3.1. Thermostat controlp.188.1.4. Heating Operationp.188.1.4.1. Thermostat controlp.188.1.5. Automatic Operationp.19ON OFF ONp.238.1.7. Outdoor Fan Motor Operationp.238.1.8. Airflow Directionp.248.1.8.1. Vertical Airflowp.248.1.9. Quiet operation (Cooling Mode/Cooling area of Dry Mode)p.248.1.9.1. Quiet operation (Heating)p.258.1.10. Powerful Mode Operationp.268.1.11. 24-Hour Real Time Timer Controlp.268.1.12. Auto Restart Controlp.278.1.13. Indication Panelp.278.1.14. Drain Pump Control Operationp.278.2. Protection Control Featuresp.288.2.1. Protection Control For All Operationsp.288.2.1.1. Time Delay Safety Controlp.288.2.1.2. 30 Seconds Forced Operationp.288.2.1.3. Total Running Current Controlp.288.2.1.4. IPM (Power transistor) Prevention Controlp.288.2.1.5. Compressor Overheating Prevention Controlp.298.2.1.6. Low Pressure Prevention Control (Gas Leakage Detection)p.298.2.1.7. Low Frequency Protection Control 1p.298.2.1.8. Low Frequency Protection Control 2p.2930 Tp.2938 Tp.298.2.2. Protection Control For Cooling & Soft Dry Operationp.308.2.2.1. Outdoor Air Temperature Controlp.308.2.2.2. Cooling Overload Controlp.308.2.2.3. Anti-Freezing Controlp.318.2.2.4. Anti-Dew Formation Controlp.318.2.3. Protection Control For Heating Operationp.328.2.3.1. Intake Air Temperature Controlp.328.2.3.2. Outdoor Air Temperature Controlp.328.2.3.3. Overload Protection Controlp.328.2.3.4. Deice Controlp.33
Page 1 of the Philips CS-E15DB4EW user manual
Page 1 · click to enlarge
Page 1
Philips CS-E15DB4EW diagram (page 1)
Fig. 1

10 Installation And Servicing Air Conditioner Using R410A 42

© 2005 Panasonic HA Air-Conditioning (M) Sdn Bhd (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.

Page 2 of the Philips CS-E15DB4EW user manual
Page 2 · click to enlarge
Page 2
Philips CS-E15DB4EW diagram (page 2)
Fig. 2

18.5. Print PatternOutdoor Unit Printed Circuit Board View 97

− Discharged air can be swung automatically or manually

− Air filter with function to reduce dust and smoke.

Page 3 of the Philips CS-E15DB4EW user manual
Page 3 · click to enlarge
Page 3
Philips CS-E15DB4EW diagram (page 3)
Fig. 3
  • Increase or decrease set temperature. (16°C to 30°C)
  • AUTO Automatic Operation
  • HEAT Heating Operation
  • COOL Cooling Operation
  • DRY Soft Dry Operation
  • 24-hour, OFF / ON Real Timer Setting. Timer Setting
  • ON Timer and OFF Timer setting and cancellation.
  • AUTO Vertical Automatic Airflow Direction Control.
  • MANUAL Vertical Manual Airflow Direction Control.
  • Indoor Fan Speed Selection
  • Low
  • Medium-
  • Medium
  • Medium+
  • High
  • AUTO Automatic Fan Speed
Page 4 of the Philips CS-E15DB4EW user manual — Deice Operation
Page 4 · click to enlarge
Page 4

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

2.2. Indoor Unit

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 4)
Fig. 4
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 4)
Fig. 5
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 4)
Fig. 6
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 4)
Fig. 7

Automatic Operation Switch

Quiet Mode

  • To run automatic operation, force cooling or heating operation, or change remote control signal type.
  • To provide quiet operation.

24-Hour Real Time Timer Control

Operation Indication Lamps (LED)

Automatic Restart Control

  • POWER (Green) ........Lights up in operation,
  • Operation is restarted after power failure at previous setting mode.

blinks in Automatic Operation Mode judging, deice, On Timer sampling and Hot Start operation. • TIMER (Orange) Lights up in Timer Setting.

Microcomputer-controlled Room Temperature Control

Blinks in Self Diagnosis Control. • QUIET (Orange) Lights up in Quiet Mode

Breakdown Self Diagnosis Function

  • Operation.
  • POWERFUL (Orange) ... Lights up when Powerful Mode is selected.
  • AIR SWING (Orange).... Lights up in Auto Air Swing.

Low Pressure Control (Gas Leakeage Detection)

Indoor Power Relay Control

Anti-Dew Formation Control

Four Operation Modes

  • Automatic, Heating, Cooling and Soft Dry Operation.

Anti Freezing Control

Automatic and 5 Manual Indoor Fan Speeds

Anti-Cold Draft Control

Hot Start

Airflow Direction Control

Intake Air Temperature Control

  • Vertical discharged air can be swung automatically or manually by remote control.
  • Horizontal discharged air can be adjusted by hand.

High Pressure Control

Deodorizing Control

Powerful Mode

  • For quick cooling or heating.

Deice Operation

Page 5 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 5 · click to enlarge
Page 5
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 5)
Fig. 8
Page 6 of the Philips CS-E15DB4EW user manual — INTAKE
Page 6 · click to enlarge
Page 6

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

3.1. CS-E15DB4EW CU-E15DBE 3 Product Specifications

Cooling Capacity kW kcal/h BTU/h

4.10 (0.90 - 4.80) 3,530 (770 - 4,130) 14,000 (3,070 - 16,400)

Heating Capacity kW kcal/h BTU/h

5.10 (0.90 - 6.20) 4,390 (770 - 5,330) 17,400 (3,070 - 21,100)

Moisture Removal l/h Pint/h

2.3 (4.9)

Power Source (Phase, Voltage, Cycle) ø V Hz

Single 230 - 240 50

SIDE VIEW

TOP VIEW

Philips CS-E15DB4EW — SIDE VIEW diagram (page 6)
Fig. 9
Philips CS-E15DB4EW — SIDE VIEW diagram (page 6)
Fig. 10

INTAKE

Air Volume Lo m3/min (cfm) Cooling; 7.5 (260) — Heating; 9.0 (320)

Me m3/min (cfm) Cooling; 9.0 (320) — Heating; 10.1 (360)

Hi m3/min (cfm) Cooling; 10.5 (370) Cooling; 46.8 (1,650) Heating; 10.8 (380) Heating; 48.5 (1,710)

dB (A) Cooling; High 34, Low 26 Cooling; 45 Heating; High 35, Low 28 Heating; 47 Noise Level

Power level dB Cooling; High 47 Cooling; High 58 Heating; High 48 Heating; High 60

Electrical Data Input Power W Cooling; 1,300 (255 - 1,710) Heating; 1,770 (260 - 2,180)

Running Current A Cooling; 6.0 - 5.9 Heating; 8.0 - 7.9

EER W/W Cooling; 3.15 (3.53 - 2.81) BTU/hW Cooling; 10.8 (12.0 - 9.6) COP W/W Heating; 2.88 (3.46 - 2.84) BTU/hW Heating; 9.8 (11.8 - 9.7) Starting Current A 8.0 Piping Connection Port (Flare piping)

G ; Half Union 1/2”

G ; 3-way valve 1/2”

L ; Half Union 1/4”

L ; 2-way valve 1/4”

Unit CS-E15DB4EW CU-E15DBE · Airflow Method OUTLET · inch inch

Page 7 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 7 · click to enlarge
Page 7

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

UnitCS-E15DB4EWCU-E15DBE Pipe Size (Flare piping)inch inchG (gas side) ; 1/2” L (liquid side) ; 1/4”G (gas side) ; 1/2” L (liquid side) ; 1/4” Drain HoseInner diametermm30— Lengthm0.193— Power Cord Length Number of core-wire——— — DimensionsHeightinch (mm)10 - 1/4 (260)29 - 17/32 (750) Widthinch (mm)22 - 5/8 (575)34 - 7/16 (875) Depthinch (mm)22 - 5/8 (575)13 - 19/32 (345) Net Weightlb (kg)40 (18)106 (48) CompressorType—Involute scroll MotorType—Brushless (4-pole) RatedOutputW—900 Air CirculationTypeBackward FanPropeller Fan MaterialABS + GF 10%P.P MotorTypeDC Brushless Motor (8-poles)Transistor (8-poles) Rate OutputW4040 Fan SpeedLo (Cool/Heat)rpm400 / 480— Me (Cool/Heat)rpm480 / 540— Hi (Cool/Heat)rpm560 / 600640 / 660 Heat ExchangerDescriptionEvaporatorCondenser Tube materialCopperCopper Fin materialAluminium (Pre Coat)Aluminium Fin TypeSlit FinCorrugated Fin Row / Stage(Plate fin configuration, forced draft) 2 / 101 / 28 FPI1818 Size (W × H × L)mm1,330 1,270× 210 × 25.4871.7× 711.2 × 22 Refrigerant Control Device—Expansion Valve Refrigeration Oil(cm3)—RB68A (400) Refrigerant (R410A)kg (oz)—1.23 (43.4) ThermostatElectronic Control— Protection DeviceElectronic ControlElectronic Control
  • Specifications are subjected to change without notice for further improvement.
Page 8 of the Philips CS-E15DB4EW user manual — SIDE VIEW
Page 8 · click to enlarge
Page 8

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

3.2. CS-E18DB4EW CU-E18DBE

Cooling Capacity kW kcal/h BTU/h

4.80 (0.90 - 5.70) 4,130 (770 - 4,900) 16,400 (3,070 - 19,400)

Heating Capacity kW kcal/h BTU/h

5.60 (0.90 - 7.10) 4,820 (770 - 6,110) 19,100 (3,070 - 24,200)

Moisture Removal l/h Pint/h

2.6 (5.5)

Power Source (Phase, Voltage, Cycle) ø V Hz

Single 230 - 240 50

SIDE VIEW

TOP VIEW

INTAKE

Air Volume Lo m3/min (cfm) Cooling; 8.0 (280) — Heating; 9.1 (320)

Me m3/min (cfm) Cooling; 9.5 (340) — Heating; 10.4 (370)

Hi m3/min (cfm) Cooling; 11.0 (390) 40.0 (1,410) Heating; 11.5 (405)

dB (A) Cooling; High 36, Low 28 Cooling; 47 Heating; High 37, Low 29 Heating; 48 Noise Level

Power level dB Cooling; High 49 Cooling; High 60 Heating; High 50 Heating; High 61

Electrical Data Input Power W Cooling; 1,530 (255 - 1,930) Heating; 1,900 (260 - 2,450)

Running Current A Cooling; 7.0 - 6.9 Heating; 8.5 - 8.3

EER W/W Cooling; 3.14 (3.53 - 2.95) BTU/hW Cooling; 10.7 (12.0 - 10.1) COP W/W Heating; 2.95 (3.46 - 2.90) BTU/hW Heating; 10.1 (11.8 - 9.9) Starting Current A 8.5 Piping Connection Port (Flare piping)

G ; Half Union 1/2”

G ; 3-way valve 1/2”

L ; 2-way valve 1/4” Pipe Size (Flare piping)

L ; Half Union 1/4”

G (gas side) ; 1/2” L (liquid side) ; 1/4”

G (gas side) ; 1/2” L (liquid side) ; 1/4”

Show 4 more labels / short text on this page
Unit CS-E18DB4EW CU-E18DBE · Airflow Method OUTLET · inch inch · inch inch
Page 9 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 9 · click to enlarge
Page 9

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

UnitCS-E18DB4EWCU-E18DBE Drain HoseInner diametermm30— Lengthm0.193— Power Cord Length Number of core-wire——— — DimensionsHeightinch (mm)10 - 1/4 (260)29 - 17/32 (750) Widthinch (mm)22 - 5/8 (575)34 - 7/16 (875) Depthinch (mm)22 - 5/8 (575)13 - 19/32 (345) Net Weightlb (kg)40 (18)106 (48) CompressorType—Involute scroll MotorType—Brushless (4-pole) RatedOutputW—900 Air CirculationTypeBackward FanPropeller Fan MaterialABS + GF 10%P.P MotorTypeDC Brushless Motor (8-poles)Transistor (8-poles) Rate OutputW4040 Fan SpeedLo (Cool/Heat)rpm430 / 490— Me (Cool/Heat)rpm510 / 560— Hi (Cool/Heat)rpm590 / 640660 / 660 Heat ExchangerDescriptionEvaporatorCondenser Tube materialCopperCopper Fin materialAluminium (Pre Coat)Aluminium Fin TypeSlit FinCorrugated Fin Row / Stage(Plate fin configuration, forced draft) 2 / 102 / 34 FPI1816 Size (W × H × L)mm1,330 1,270× 210 × 25.4849.3 878× 714 × 36.4 Refrigerant Control Device—Expansion Valve Refrigeration Oil(cm3)—RB68A (400) Refrigerant (R410A)kg (oz)—1.06 (37.4) ThermostatElectronic Control— Protection DeviceElectronic ControlElectronic Control
  • Specifications are subjected to change without notice for further improvement.
Page 10 of the Philips CS-E15DB4EW user manual — SIDE VIEW
Page 10 · click to enlarge
Page 10

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

3.3. CS-E21DB4ES CU-E21DBE

Cooling Capacity kW kcal/h BTU/h

5.90 (0.90 - 6.30) 5,070 (770 - 5,420) 20,100 (3,070 - 21,500)

Heating Capacity kW kcal/h BTU/h

7.00 (0.90 - 8.00) 6,020 (770 - 6,880) 23,900 (3,070 - 27,300)

Moisture Removal l/h Pint/h

3.3 (7.0)

Power Source (Phase, Voltage, Cycle) ø V Hz

Single 230 - 240 50

SIDE VIEW

TOP VIEW

INTAKE

Air Volume Lo m3/min (cfm) Cooling; 9.3 (330) — Heating; 10.6 (370)

Me m3/min (cfm) Cooling; 11.0 (390) — Heating; 12.3 (430)

Hi m3/min (cfm) Cooling; 12.8 (450) Cooling; 42.8 (1,510) Heating; 14.0 (495) Heating; 41.5 (1,460)

dB (A) Cooling; High 41, Low 33 Cooling; 49 Heating; High 42, Low 34 Heating; 49 Noise Level

Power level dB Cooling; High 54 Cooling; High 62 Heating; High 55 Heating; High 62

Electrical Data Input Power W Cooling; 2,050 (255 - 2,200) Heating; 2,450 (260 - 2,820)

Running Current A Cooling; 9.2 - 9.0 Heating; 10.9 - 10.6

EER W/W Cooling; 2.88 (3.53 - 2.86) BTU/hW Cooling; 9.8 (12.0 - 9.8) COP W/W Heating; 2.86 (3.46 - 2.84) BTU/hW Heating; 9.8 (11.8 - 9.7) Starting Current A 10.9 Piping Connection Port (Flare piping)

G ; Half Union 1/2”

G ; 3-way valve 1/2”

L ; 2-way valve 1/4” Pipe Size (Flare piping)

L ; Half Union 1/4”

G (gas side) ; 1/2” L (liquid side) ; 1/4”

G (gas side) ; 1/2” L (liquid side) ; 1/4”

Show 4 more labels / short text on this page
Unit CS-E21DB4ES CU-E21DBE · Airflow Method OUTLET · inch inch · inch inch
Page 11 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 11 · click to enlarge
Page 11

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

UnitCS-E21DB4ESCU-E21DBE Drain HoseInner diametermm30— Lengthm0.193— Power Cord Length Number of core-wire——— — DimensionsHeightinch (mm)10 - 1/4 (260)29 - 17/32 (750) Widthinch (mm)22 - 5/8 (575)34 - 7/16 (875) Depthinch (mm)22 - 5/8 (575)13 - 19/32 (345) Net Weightlb (kg)40 (18)108 (49) CompressorType—Involute scroll MotorType—Brushless (4-pole) RatedOutputW—900 Air CirculationTypeBackward FanPropeller Fan MaterialABS + GF 10%P.P MotorTypeDC Brushless Motor (8-poles)Transistor (8-poles) Rate OutputW4040 Fan SpeedLo (Cool/Heat)rpm510 / 580— Me (Cool/Heat)rpm600 / 670— Hi (Cool/Heat)rpm700 / 770700 / 680 Heat ExchangerDescriptionEvaporatorCondenser Tube materialCopperCopper Fin materialAluminium (Pre Coat)Aluminium Fin TypeSlit FinCorrugated Fin Row / Stage(Plate fin configuration, forced draft) 2 / 102 / 34 FPI1818 Size (W × H × L)mm1,330 1,270× 210 × 25.4839.5 868× 714 × 36.4 Refrigerant Control Device—Expansion Valve Refrigeration Oil(cm3)—RB68A (400) Refrigerant (R410A)kg (oz)—1.15 (40.6) ThermostatElectronic Control— Protection DeviceElectronic ControlElectronic Control
  • Specifications are subjected to change without notice for further improvement.
Page 12 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 12 · click to enlarge
Page 12

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

4 Dimensions

4.1. Indoor Unit & Remote Control

4.1.1. CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 12)
Fig. 11
Page 13 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 13 · click to enlarge
Page 13

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

4.2. Outdoor Unit

4.2.1. CU-E15DBE CU-E18DBE CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 13)
Fig. 12
Page 14 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 14 · click to enlarge
Page 14

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

5 Refrigeration Cycle Diagram

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 14)
Fig. 13
Page 15 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 15 · click to enlarge
Page 15

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

6 Block Diagram

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 15)
Fig. 14
Page 16 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 16 · click to enlarge
Page 16

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

7 Wiring Diagram

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 16)
Fig. 15
Page 17 of the Philips CS-E15DB4EW user manual — 8.1.1. Temperature Shifting Flow
Page 17 · click to enlarge
Page 17

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8 Operation Details

8.1. Basic Operation

Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjust output power for maximum comfort always.

In order to achieve the suitable operation mode, the microcomputer maintains the set temperature by measuring the temperature of environment and performing temperature shifting.

8.1.1. Temperature Shifting Flow

Philips CS-E15DB4EW — 8.1.1. Temperature Shifting Flow diagram (page 17)
Fig. 16 · 8.1.1. Temperature Shifting Flow

The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that judging the condition according to internal setting temperature.

Philips CS-E15DB4EW — 8.1.1. Temperature Shifting Flow diagram (page 17)
Fig. 17 · 8.1.1. Temperature Shifting Flow
Page 18 of the Philips CS-E15DB4EW user manual — 8.1.4. Heating Operation
Page 18 · click to enlarge
Page 18

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.1.2. Cooling Operation

8.1.2.1. Thermostat control

  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF

point.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 18)
Fig. 18

8.1.3. Soft Dry Operation

8.1.3.1. Thermostat control

  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF

point.

Philips CS-E15DB4EW — 8.1.3. Soft Dry Operation diagram (page 18)
Fig. 19 · 8.1.3. Soft Dry Operation

8.1.4. Heating Operation

8.1.4.1. Thermostat control

  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF

point.

Philips CS-E15DB4EW — 8.1.4. Heating Operation diagram (page 18)
Fig. 20 · 8.1.4. Heating Operation
Page 19 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 19 · click to enlarge
Page 19

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.1.5. Automatic Operation

This mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake air temperature and outdoor air temperature.

During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 19)
Fig. 21

Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2 and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on the above operation mode chart, every 30 minutes.

Remote Control Setting Temperature (°C) T1 T2 T3 16 ~ 18 +10 -3 -5 19 ~ 22 +8 -3 -7 23 ~ 26 +7 -3 -7 27 ~ 30 +6 -3 -8

There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice verse.

Operation Mode change from Temperature shifts (°C) Cooling/Soft Dry →Heating -2 Heating →Cooling/Soft Dry +2

Example of operation mode chart adjustment:

From the above table, if remote control setting temperature = 25,

T1 = 25 + 7 = 32; T2 = 25 - 3 = 22; T3 = 25 - 7 = 18

The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on indoor intake air temperature and outdoor air temperature at the time when the judgment is made.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 19)
Fig. 22
Page 20 of the Philips CS-E15DB4EW user manual — 8.1.5. Automatic Operation
Page 20 · click to enlarge
Page 20
Philips CS-E15DB4EW — 8.1.5. Automatic Operation diagram (page 20)
Fig. 23 · 8.1.5. Automatic Operation
  • Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)

Remote Control — — O — — — Tab (rpm) PSHI SHI Hi Me+ Me Me- Lo Lo- SLo SSLo E15D 600 560 560 495 480 425 400 370 310 200 E18D 680 640 590 563 510 488 430 410 350 200 E21D 800 750 700 660 600 560 510 480 410 200

Remote Control — — O — — — Tab (rpm) PSHi SSHi SHi Me+ Me Me- Lo Lo- SLo SSLo E15D 650 610 600 545 540 495 480 440 300 200 E18D 740 690 640 618 560 553 490 490 320 200 E21D 870 820 770 745 670 655 580 570 370 200

Page 21 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 21 · click to enlarge
Page 21

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

2. Heating
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 21)
Fig. 24

ii. Auto Fan Speed

1. Cooling
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 21)
Fig. 25
Page 22 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 22 · click to enlarge
Page 22

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

2. Heating
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 22)
Fig. 26

a. UP:

  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm.
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm.

b. DOWN:

  • The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.

c. Current Output Fixed:

  • Maintain at present fan speed.

d. Instantaneous Maximum:

  • Fan speed will be increased to maximum auto fan speed.

e. Temperature in ( ) is for Powerful Mode operation.

C. Fan Motor Control

1. Motor specification

High voltage PWM Motor

2. Feedback Control

a. Number-of-rotations feedback

Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed. For high voltage PWM motor, it is done once every 0.5 second.

b. Offset duty T max/min limit

High voltage PWM motor has maximum offset duty.

(Refer Indoor fan motor control basic rotation speed)

3. Abnormal Detection Control

Conditions:

a. Out of rhythm signal input

b. If feedback number of rotations exceeded #2550 r/min or when less than #50 r/min.

ControlFans stop
ReturnRestart after 5 seconds

* It will not detect the out of rhythm condition within 5s for phase control motor (PWM motor is when duty=0) after start.

A fan stops when condition (1) and (2) happen within 25.0 seconds after fan starting, and if this happens for continuously 7 times, it will not retry.

→FM lock processing

4. Restart Prohibition Control

Restart is prohibited within 5s for phase control motor (PWM motor is when duty=0) after fan stop (except re-ON the power supply).

Page 23 of the Philips CS-E15DB4EW user manual — 8.1.7. Outdoor Fan Motor Operation
Page 23 · click to enlarge
Page 23

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

D. Deodorizing Control

i. Control condition

Control at cooling/dry operation and auto fan speed.

No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.

ii. Operation

The odor status is arranged as below and it is shifted as follow.

* When COMP is ON 1 →2 →3 (Shift to 4 when COMP is OFF) * When COMP is OFF 4 →5 →6 →7 →6 ←→7 (Shift to 1 when COMP is ON) * Start from 4 if the Thermostat is OFF during the start operation.

Odor Status 1 2 3 4 5 6 7 6.7.6... 1 Status Shift according to COMP

ON OFF ON

zone 40 50 — 30 90 20 90 20.90.20... to time (s) Dry zone ON

SSLo OFF SSLo OFF SSLo.OFF... Dry zone SLo

Philips CS-E15DB4EW — ON OFF ON diagram (page 23)
Fig. 27

8.1.7. Outdoor Fan Motor Operation

Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation for speed no.8.

Philips CS-E15DB4EW — 8.1.7. Outdoor Fan Motor Operation diagram (page 23)
Fig. 28 · 8.1.7. Outdoor Fan Motor Operation

No. RPM during Fan Speed (rpm) E21D E18D E15D 15 75 73 71 14 75 73 71 13 70 68 66 12 68 66 64 11 64 62 60 10 62 60 60 9 58 58 58 8 50 50 50 7 45 45 45 6 40 40 40 5 35 35 35 4 30 30 30 3 25 25 25 2 20 20 20 1 15 15 15

Show 7 more labels / short text on this page
Status Shift · Cooling · according · Cooling · Auto Fan Speed · Fan Speed · zone OFF SSLo
Page 24 of the Philips CS-E15DB4EW user manual — 8.1.9. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
Page 24 · click to enlarge
Page 24

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.1.8. Airflow Direction

1. There are one types of airflow, vertical airflow (directed by horizontal vane).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature

and intake air temperature) and manual (angles of direction can be adjusted using remote control).

8.1.8.1. Vertical Airflow

Operation Mode Airflow Direction Vane Angle (°) 1 2 3 4 5 Heating Auto with Heat Exchanger A Downward fix 70 Temperature B Downward fix 70 C Upward fix 20 D Upward fix 20 Manual 20 - - - 70 Cooling, Soft Dry and Ion Auto 20 ~ 70 Manual 20 - - - 70

1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated

above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions

of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

Philips CS-E15DB4EW — 8.1.8.1. Vertical Airflow diagram (page 24)
Fig. 29 · 8.1.8.1. Vertical Airflow

8.1.9. Quiet operation (Cooling Mode/Cooling area of Dry Mode)

A. Purpose

To provide quiet cooling operation compare to normal operation.

B. Control condition

a. Quiet operation start condition

  • When “quiet” button at remote control is pressed.

Quiet LED illuminates.

b. Quiet operation stop condition

1. When one of the following conditions is satisfied, quiet operation stops:

a. Powerful button is pressed.

b. Stop by OFF/ON switch.

c. Timer “off” activates.

d. Quiet button is pressed again.

2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
Page 25 of the Philips CS-E15DB4EW user manual — 8.1.9.1. Quiet operation (Heating)
Page 25 · click to enlarge
Page 25

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

C. Control contents

1. Fan speed is changed from normal setting to quiet setting of respective fan speed.

This is to reduce sound of Hi, Me, Lo for 3dB.

2. Fan speed for quiet operation is -1 step from setting fan speed.

8.1.9.1. Quiet operation (Heating)

A. Purpose

To provide quiet heating operation compare to normal operation.

B. Control condition

a. Quiet operation start condition

  • When “quiet” button at remote control is pressed.

Quiet LED illuminates.

b. Quiet operation stop condition

1. When one of the following conditions is satisfied, quiet operation stops:

a. Powerful button is pressed.

b. Stop by OFF/ON switch.

c. Timer “off” activates.

d. Quiet button is pressed again.

2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.

C. Control contents

a. Fan Speed manual

1. Fan speed is changed from normal setting to quiet setting of respective fan speed.

This is to reduce sound of Hi, Me, Lo for 3dB.

2. Fan speed for quiet operation is -1 step from setting fan speed.
3. Fan Speed Auto

Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.

Page 26 of the Philips CS-E15DB4EW user manual — 8.1.11. 24-Hour Real Time Timer Control
Page 26 · click to enlarge
Page 26

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.1.10. Powerful Mode Operation

When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 26)
Fig. 30

(b) Soft Dry Operation

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 26)
Fig. 31
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 26)
Fig. 32

8.1.11. 24-Hour Real Time Timer Control

ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable environment when reaching the set ON time.

Outdoor fan-ON instructions are transmitted to outdoor unit 60 minutes before setting time, then sampling the outdoor / indoor temperature with indoor fan at Lo- for 30 seconds. After detecting the indoor/outdoor temperature, the unit determines the operation starting time according to the load. However, when outdoor unit is operating, the preparation starting time will be set to minimum.

When the OFF timer is set by using the remote control, the unit stop operate according to the desired setting.

1. By pressing ON/OFF operation button, the ON Timer/OFF Timer setting will not be cancelled.
2. To cancel the previous timer setting, press CANCEL button.
3. To activate the previous timer setting, press SET button.
4. If main power supply is switched off, the Timer setting will be cancelled.
Show 4 more labels / short text on this page
(a) Cooling Operation · (c) Heating Operation · ON Timer · OFF Timer
Page 27 of the Philips CS-E15DB4EW user manual — 8.1.14. Drain Pump Control Operation
Page 27 · click to enlarge
Page 27

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.1.12. Auto Restart Control

1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four

minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.

2. This type of control is not applicable during ON/OFF Timer setting.

8.1.13. Indication Panel

LED POWER TIMER QUIET POWERFUL AIR SWING Color Green Orange Light ON Operation ON Timer Setting ON Quiet Mode ON Powerful Mode ON Auto Air Swing ON Light OFF Operation OFF Timer Setting OFF Quiet Mode OFF Powerful Mode OFF Auto Air Swing OFF

  • If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode

judgment, or delay ON timer sampling.

  • If Timer LED is blinking, there is an abnormality operation occurs.

8.1.14. Drain Pump Control Operation

  • To drain out the condensed watar trapped in the drain pan in order to prevent the condensed water from overflowing from the

drain pan and leaking.

Philips CS-E15DB4EW — 8.1.14. Drain Pump Control Operation diagram (page 27)
Fig. 33 · 8.1.14. Drain Pump Control Operation
  • Drain Pump starts to operate 10 sec. after compressor and Indoor fan ON.
  • Drain Pump stop to operate 90 sec. after compressor OFF.

Drain Pump Error occurs when:

- Within 20 minutes, the float switch is ON twice.

- Float switch is ON continuously for 2 minutes 30 seconds.

When error occurs, the timer indicator blinks and the unit stops its operation.

Drain Pump Error

Page 28 of the Philips CS-E15DB4EW user manual — 8.2.1.4. IPM (Power transistor) Prevention Control
Page 28 · click to enlarge
Page 28

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.2. Protection Control Features

8.2.1. Protection Control For All Operations

8.2.1.1. Time Delay Safety Control

1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off for 20 seconds and on again or after 4-way valve deices condition.

8.2.1.2. 30 Seconds Forced Operation

1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.

8.2.1.3. Total Running Current Control

1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be

decreased.

2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 2 minutes.

Model E15D E18D E21D Operation Mode X (A) Y (A) X (A) Y (A) X (A) Y (A) Cooling/Soft Dry (A) 7.20 17 8.74 17 11.02 17 Cooling/Soft Dry (B) & (C) 6.30 17 7.70 17 9.59 17 Heating 8.60 17 10.71 17 11.53 17

4. The first 30 minutes of cooling operation, (A) will be applied.
Philips CS-E15DB4EW — 8.2.1.3. Total Running Current Control diagram (page 28)
Fig. 34 · 8.2.1.3. Total Running Current Control

8.2.1.4. IPM (Power transistor) Prevention Control

A. Overheating Prevention Control

1. When the IPM temperature rises to 100°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95°C.

B. DC Peak Current Control

1. When electric current to IPM exceeds set value of 22.33 A, the compressor will stop operate. Then, operation will restart

after three minutes.

2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 1 minute.
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.

If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.

Page 29 of the Philips CS-E15DB4EW user manual — 38 T
Page 29 · click to enlarge
Page 29

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.2.1.5. Compressor Overheating Prevention Control

Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below figure.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 29)
Fig. 35

8.2.1.6. Low Pressure Prevention Control (Gas Leakage Detection)

a. Control start conditions

Control will perform when (1) - (3) condition continues operation for 5 minute and (4) is fulfill.

1. During cooling and dry operation: Frequency more than normal Fcmax 78 Hz (E15D), 86 Hz (E18D), 102 Hz (E21D).

During heating operation: Frequency more than normal Fh 71 Hz (E15D), 86 Hz (E18D), 92 Hz (E21D).

2. Outdoor total current I cooling: Ib
HeatingIb

Ic = Ia = 1.65 A

Ib = 0.65 A

3. It is not during deice operation.
4. During cooling and dry operation: indoor suction-indoor piping temperature is below 4°C.

During of heating operation: Indoor piping temperature-indoor suction is under 5°C.

Control contents:

  • compressor stops (restart after 3 minutes)
  • if happen 2 times within (20 minutes), perform the following operation
1. Unit stop operation
2. Timer LED blink and “F91” indicated

8.2.1.7. Low Frequency Protection Control 1

When the compressor operate at frequency lower than 25 Hz continued for 20 minutes, the operation frequency will be increased to 24 Hz for two minutes.

8.2.1.8. Low Frequency Protection Control 2

When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz for cooling mode operation and 20 Hz for heating mode operation.

Temperature, T, forCooling/Soft Dry Heating Indoor intake air (°C) T

28 Outdoor air (°C) T

30 T

24 Indoor heat exchanger (°C) T

38 T

30 T

Show 5 more labels / short text on this page
Ia · 14 or T · 14 or T · 13 or T · 4 or T
Page 30 of the Philips CS-E15DB4EW user manual — 8.2.2.2. Cooling Overload Control
Page 30 · click to enlarge
Page 30

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.2.2. Protection Control For Cooling & Soft Dry Operation

8.2.2.1. Outdoor Air Temperature Control

The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.

This control will begin one minute after the compressor starts.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 30)
Fig. 36

8.2.2.2. Cooling Overload Control

i. Pipe temperature limitation/restriction

  • Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)
  • The compressor stop if outdoor pipe temperature exceeds 63°C
  • If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection)
Philips CS-E15DB4EW — 8.2.2.2. Cooling Overload Control diagram (page 30)
Fig. 37 · 8.2.2.2. Cooling Overload Control

ii. Electrical part temperature rise protection control

1. Purpose

To prevent electronic components temperature rise during cooling overload.

2. Judgement Conditions
Philips CS-E15DB4EW — 8.2.2.2. Cooling Overload Control diagram (page 30)
Fig. 38 · 8.2.2.2. Cooling Overload Control

b) Outdoor total current above 5 A.

a) Outdoor temperature

Page 31 of the Philips CS-E15DB4EW user manual — 8.2.2.4. Anti-Dew Formation Control
Page 31 · click to enlarge
Page 31

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

3. Control contents

In the outdoor fan speed no.

i) In protectorate Domain A is referred to as min 660 rpm.

ii) In protectorate Domain B, it is referred to as min 600 rpm.

4. Condition resolutive

It is canceled when it stops satisfying all of the above-mentioned.

8.2.2.3. Anti-Freezing Control

1. When indoor heat exchanger temperature is lower than 7°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 13°C.
3. At the same time, indoor fan speed increase +20 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 13°C for five minutes, the fan speed will return to its normal operation.
Philips CS-E15DB4EW — 8.2.2.3. Anti-Freezing Control diagram (page 31)
Fig. 39 · 8.2.2.3. Anti-Freezing Control

8.2.2.4. Anti-Dew Formation Control

a. Purpose

To prevent dew.

b. Control start conditions

When indoor are ceiling floor, duct and mini casette.

c. Control contents

Hz control is carried out according to the spray prevention status transmitted from indoor.

Spray prevention status(transmitted indoor)

Control contents Relative control domain MAX domain 0 (it usually controls Usually, control Usually, control 1 (rise) Relative change control priority On tap up/10 seconds 2 (changeless) Changeless Changeless 3 (down) -2 Hz/10 seconds -2 Hz/10 seconds

Change is once to 10 seconds.

* Once the standup went into the down domain by Fcmax as for the Fcmax domain, it shifts to relative change control domain.

When the higher rank of relative control has this control and the status signal of 2-3 has come out.

Relative change control is stopped and follows directions of spray control.

Priority is given to the which is larger when freeze prevention down status and spray prevention down status are transmitted simultaneously.

In the case of spray status

0, it is referred to as maxFc.

Page 32 of the Philips CS-E15DB4EW user manual — 8.2.3.3. Overload Protection Control
Page 32 · click to enlarge
Page 32

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.2.3. Protection Control For Heating Operation

8.2.3.1. Intake Air Temperature Control

Compressor will operate at Max freq 94 (E15D), 128 (E18D, E21D) Hz if either one of the below conditions occur:

1. When the indoor intake air temperature is less than 21°C and remote control setting fan speed is lower Me-.
2. When the indoor intake air temperature is 35°C or above.

8.2.3.2. Outdoor Air Temperature Control

The Max current value is regulated in accordance to the outdoor air temperature as shown in the below figures.

Philips CS-E15DB4EW — 8.2.3.2. Outdoor Air Temperature Control diagram (page 32)
Fig. 40 · 8.2.3.2. Outdoor Air Temperature Control

8.2.3.3. Overload Protection Control

The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.

Philips CS-E15DB4EW — 8.2.3.3. Overload Protection Control diagram (page 32)
Fig. 41 · 8.2.3.3. Overload Protection Control
Page 33 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 33 · click to enlarge
Page 33

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8.2.3.4. Deice Control

  • Deice starts to prevent frosting at outdoor heat exchanger.
  • Deice operation detection commences after minimum 60 minutes of Heating Operation.
  • The outdoor heat exchanger temperature drops below 3°C for long period (minimum 40 minutes) during compressor is in

operation, the deice operation may starts.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 33)
Fig. 42
Page 34 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 34 · click to enlarge
Page 34

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

9 Operating Instructions

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 34)
Fig. 43
Page 35 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 35 · click to enlarge
Page 35

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 35)
Fig. 44
Page 36 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 36 · click to enlarge
Page 36

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 36)
Fig. 45
Page 37 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 37 · click to enlarge
Page 37

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 37)
Fig. 46
Page 38 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 38 · click to enlarge
Page 38

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 38)
Fig. 47
Page 39 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 39 · click to enlarge
Page 39

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 39)
Fig. 48
Page 40 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 40 · click to enlarge
Page 40

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 40)
Fig. 49
Page 41 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 41 · click to enlarge
Page 41

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 41)
Fig. 50
Page 42 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 42 · click to enlarge
Page 42

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

10 Installation And Servicing Air Conditioner Using R410A

10.1. Outline

10.1.1. About R410A Refrigerant

1. Converting air conditioners to R410A

Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction. The R22 refrigerant which has conventionally been used in ACs is an HCFC refrigerant and, therefore, possesses this ozone- destroying potential. International regulations (the Montreal Protocol on Ozone-Damaging Substances) and the domestic laws of various countries call for the early substitution of R22 by a refrigerant which will not harm the ozone layer.

  • In ACs, the HFC refrigerant which has become the mainstream alternative is called <a href="http://R410A.Com" rel="nofollow noopener" target="_blank">R410A.Com</a>pared with R22, the

pressure of R410A is approximately 1.6 times as high at the same refrigerant temperature, but the energy efficiency is about the same. Consisting of hydrogen (H), fluorine (F) and carbon (C), R410A is an HFC refrigerant. Another typical HFC refrigerant is R407C. While the energy efficiency of R407C is somewhat inferior to that of R410A, it offers the advantage of having pressure characteristics which are about the same as those of R22, and is used mainly in packaged ACs.

2. The characteristics of HFC (R410A) refrigerants

a. Chemical characteristics

The chemical characteristics of R410A are similar to those of R22 in that both are chemically stable, non-flammable refrigerants with low toxicity. However, just like R22, the specific gravity of R410A gas is heavier than that of air. Because of this, it can cause an oxygen deficiency if it leaks into a closed room since it collects in the lower area of the room. It also generates toxic gas when it is directly exposed to a flame, so it must be used in a well ventilated environment where it will not collect.

Table 1 Physical comparison of R410A and R22

R410A R22 Composition (wt%) R32/R125 (50/50) R22 (100) Boiling point (°C) -51.4 -40.8 Vaporizing pressure (25°C) 1.56 Mpa (15.9 kgf/cm2) 0.94 Mpa (9.6 kgf/cm2) Saturated vapor density 64.0 kg/m3 44.4 kg/m3

Flammability Non-flammable Non-flammable Ozone-destroying point (ODP) 0 0.055 Global-warming point (GWP) 1730 1700

b. Compositional change (pseudo-azeotropic characteristics)

R410A is a pseudo-azeotropic mixture comprising the two components R32 and R125. Multi-component refrigerants with these chemical characteristics exhibit little compositional change even from phase changes due to vaporization (or condensation), which means that there is little change in the circulating refrigerant composition even when the refrigerant leaks from the gaseous section of the piping. Accordingly, R410A can be handled in almost the same manner as the single-component refrigerant R22. However, when charging, because there is a slight change in composition between the gas phase and the liquid phase inside a cylinder or other container, charging should basically begin with the liquid side.

c. Pressure characteristics

As seen in Table 2, the gas pressure of R410A is approximately 1.6 times as high as that of R22 at the same refrigerant temperature, which means that special R410A tools and materials with high-pressure specifications must be used for all refrigerant piping work and servicing.

Table 2 Comparison of R410A and R22 saturated vapor density

Unit: MPa Refrigerant Temperature (°C) R410A R22 -20 0.30 0.14 0 0.70 0.40 20 1.35 0.81 40 2.32 1.43 60 3.73 2.33 65 4.15 2.60

Page 43 of the Philips CS-E15DB4EW user manual — 10.2.1. Necessary Tools
Page 43 · click to enlarge
Page 43

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

d. R410A refrigerating machine oil

Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyester and other synthetic oils which have a high compatibility with R410A are used as refrigerating machine oil. Because of the high hygroscopic property of synthetic oil, more care must be taken in its handling than was necessary with conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil or alkylbenzene, causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.

10.1.2. Safety Measures When Installing/Servicing Refrigerant Piping

Cause the gas pressure of R410A is approximately 1.6 times as high as that of R22, a mistake in installation or servicing could result in a major accident. It is essential that you use R410A tools and materials, and that you observe the following precautions to ensure safety.

1. Do not use any refrigerant other than R410A in ACs that have been used with R410A.
2. If any refrigerant gas leaks while you are working, ventilate the room. Toxic gas may be generated if refrigerant gas is exposed

to a direct flame.

3. When installing or transferring an AC, do not allow any air or substance other than R410A to mix into the refrigeration cycle. If

it does, the pressure in the refrigeration cycle can become abnormally high, possibly causing an explosion and/or injury.

4. After finishing the installation, check to make sure there is no refrigerant gas leaking.
5. When installing or transferring an AC, follow the instructions in the installation instructions carefully. Incorrect installation can

result in an abnormal refrigeration cycle or water leakage, electric shock, fire, etc.

6. Do not perform any alterations on the AC unit under any circumstances. Have all repair work done by a specialist. Incorrect

repairs can result in an water leakage, electric shock, fire, etc.

10.2. Tools For Installing/Servicing Refrigerant Piping

10.2.1. Necessary Tools

In order to prevent an R410A AC from mistakenly being charged with any other refrigerant, the diameter of the 3-way valve service port on the outdoor unit has been changed. Also, to increase its ability to withstand pressure, the opposing dimensions have been changed for the refrigerant pipe flaring size and flare nut. Accordingly, when installing or servicing refrigerant piping, you must have both the R410A and ordinary tools listed below.

Table 3 Tools for installation, transferring or replacement Type of work Ordinary tools R410A tools Flaring Flaring tool (clutch type), pipe cutter, reamer

Copper pipe gauge for clearance Adjustment, flaring tool (clutch type)*1) Bending, connecting pipes Torque wrench (nominal diameter 1/4, 3/8,1/2). Fixed spanner (opposing sides 12 mm, 17 mm, 19 mm). Adjustable wrench, Spring bender Air purging Vacuum pump. Hexagonal wrench (opposing sides 4 mm)

Manifold gauge, charging hose, vacuum pump adaptor Gas leak inspection Gas leak inspection fluid or soapy water Electric gas leak detector for HFC refrigerant*2)

*1) You can use the conventional (R22) flaring tool. If you need to buy a new tool, buy the R410A type.

*2) Use when it is necessary to detect small gas leaks.

For other installation work, you should have the usual tools, such as screwdrivers (+,-), a metal-cutting saw, an electrical drill, a hole core drill (65 or 70 dia.), a tape measure, a level, a thermometer, a clamp meter, an insulation tester, a voltmeter, etc.

Table 4 Tools for serving Type of work Ordinary tools R410A tools Refrigerant charging Electronic scale for refrigerant charging. Refrigerant cylinder. Charging orifice and packing for refrigerant cylinder Brazing (Replacing refrigerating cycle part*1)

Nitrogen blow set (be sure to use nitrogen blowing for all brazing), and brazing machine

*1) Always replace the dryer of the outdoor unit at the same time. The replacement dryer is wrapped in a vacuum pack. Replace it last among the refrigerating cycle parts. Start brazing as soon as you have opened the vacuum pack, and begin the vacuuming operation within 2 hours.

Page 44 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 44 · click to enlarge
Page 44

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

10.2.2. R410A Tools

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 44)
Fig. 51
1. Copper tube gauge for clearance adjustment

(used when flaring with the conventional flaring tool (clutch type))

  • This gauge makes it easy to set the clearance for the

copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.

Fig. 1 Copper tube gauge for clearance adjustment

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 44)
Fig. 52
2. Flaring tool (clutch type)
  • In the R410A flaring tool, the receiving hole for the

clamp bar is enlarged so the clearance from the clamp bar can be set to 0-0.5 mm, and the spring inside the tool is strengthened to increase the strength of the pipe- expanding torque. This flaring tools can also be used with R22 piping, so we recommend that you select it if you are buying a new flaring tool.

Fig. 2 Flaring tool (clutch type)

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 44)
Fig. 53
3. Torque wrenches

Fig. 3 Torque wrenches

Table 5 Conventional wrenches R410A wrenches For 1/4 (opposite side x torque) 17 mm x 18 N.m (180 kgf.cm) 17 mm x 18 N.m (180 kgf.cm) For 3/8 (opposite side x torque) 22 mm x 42 N.m (420 kgf.cm) 22 mm x 42 N.m (420 kgf.cm) For 1/2 (opposite side x torque) 24 mm x 55 N.m (550 kgf.cm) 26 mm x 55 N.m (550 kgf.cm)

4. Manifold gauge
  • Because the pressure is higher for the R410A type, the conventional type cannot be used.

Table 6 Difference between R410A and conventional high / low-pressure gauges

Conventional gauges R410A gauges High-pressure gauge (red) -76 cmHg - 35 kgf/cm3 -0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm3

Low-pressure gauge (blue) -76 cmHg - 17 kgf/cm3 -0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm3

  • The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of

refrigerant.

Table 7 Difference between R410A and conventional manifold port size

Conventional gauges R410A gauges Port size 7/16 UNF 20 threads 1/2 UNF 20 threads

Page 45 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 45 · click to enlarge
Page 45

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

5. Charging hose
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 45)
Fig. 54
  • The pressure resistance of the charging hose has been

raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.

Fig. 4 Manifold gauge charging hose

Table 8 Difference between R410A and conventional charging hoses

Conventional hoses R410A hoses Pressure resistance

Working pressure 3.4 MPa (35 kgf/cm3) 5.1 MPa (52 kgf/cm3) Bursting pressure 17.2 MPa (175 kgf/cm3) 27.4 MPa (280 kgf/cm3) Material NBR rubber HNBR rubber Nylon coating inside

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 45)
Fig. 55
6. Vacuum pump adaptor
  • When using a vacuum pump for R410A, it is necessary

to install an electromagnetic valve to prevent the vacuum pump oil from flowing back into the charging hose. The vacuum pump adaptor is installed for that purpose. if the vacuum pump oil (mineral oil) becomes mixed with R410A, it will damage the unit.

Fig. 5 Vacuum pump adaptor

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 45)
Fig. 56
7. Electric gas leak detector for HFC refrigerant
  • The leak detector and halide torch that were used with

CFC and HCFC cannot be used with R410A (because there is no chlorine in the refrigerant).

  • The present R134a leak detector can be used, but the

detection sensitivity will be lower (setting the sensitivity for R134a at 1, the level for R410A will drop to 0.6).

  • For detecting small amounts of gas leakage, use the

electric gas leak detector for HFC refrigerant. (Detection sensitivity with R410A is about 23 g/year).

Fig. 6 Electric gas leak detector for HFC refrigerant

Page 46 of the Philips CS-E15DB4EW user manual — 10.2.3. R410A Tools Which Are Usable for R22 Models
Page 46 · click to enlarge
Page 46

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

8. Electronic scale for refrigerant charging
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 46)
Fig. 57
  • Because of the high pressure and fast vaporizing speed

of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading. (Naturally, the conventional R22 charging cylinder cannot be used because of the differences in the pressure resistance, scale gradation, connecting port size, etc.)

  • The electronic scale has been strengthened by using a

structure in which the weight detector for the refrigerant cylinder is held by four supports. It is also equipped with two connection ports, one for R22 (7/16 UNF, 20 threads) and one for R410A (1/2 UNF, 20 threads), so it can also be used for conventional refrigerant charging.

Fig. 7 Electronic scale for refrigerant charging

  • There are two types of electronic scales, one for 10-kg

cylinders and one for 20-kg cylinders. (The 10-kg cylinder is recommended.)

Refrigerant charging is done manually by opening and closing the valve.

9. Refrigerant cylinders
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 46)
Fig. 58
  • The R410A cylinders are labeled with the refrigerant

name, and the coating color of the cylinder protector is pink, which is the color stipulated by ARI of the U.S.

  • Cylinders equipped with a siphon tube are available to

allow the cylinder to stand upright for liquid refrigerant charging.

Fig. 8 Refrigerant cylinders

10. Charging orifice and packing for refrigerant cylinders
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 46)
Fig. 59
  • The charging orifice must match the size of the charging

hose fitting (1/2 UNF, 20 threads).

  • The packing must also be made of an HFC-resistant

material.

Fig. 9 Charging orifice and packing

10.2.3. R410A Tools Which Are Usable for R22 Models

Table 9 R410A tools which are usable for R22 models

R410A tools Usable for R22 models (1) Copper tube gauge for clearance adjustment OK (2) Flaring tool (clutch type) OK (3) Manifold gauge NG (4) Charging hose NG (5) Vacuum pump adaptor OK (6) Electric gas leak detector for HFC refrigerant NG (7) Electronic scale for refrigerant charging OK (8) Refrigerant cylinder NG (9) Charging orifice and packing for refrigerant cylinder NG

Page 47 of the Philips CS-E15DB4EW user manual — 10.3.2. Processing and Connecting Piping Materials
Page 47 · click to enlarge
Page 47

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

10.3. Refrigerant Piping Work

10.3.1. Piping Materials

It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not use pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries. Because the pressure of ACs using R410A is higher than those using R22, it is essential that you select materials that are appropriate for these standards. The thickness of the copper tubing used for R410A is shown in Table 10. Please be aware that tubing with a thickness of only 0.7 mm is also available on the market, but this should never be used.

Table 10 Copper tube thickness (mm) Soft pipe Thickness (mm) Nominal diameter Outside diameter (mm) R410A (Reference) R22 1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.7 0.80 0.80

10.3.2. Processing and Connecting Piping Materials

When working with refrigerant piping, the following points must be carefully observed: no moisture od dust must be allowed to enter the piping, and there must be no refrigerant leaks.

Philips CS-E15DB4EW — 10.3.2. Processing and Connecting Piping Materials diagram (page 47)
Fig. 60 · 10.3.2. Processing and Connecting Piping Materials
1. Procedure and precautions for flaring work

a. Cut the pipe

Use a pipe cutter, and cut slowly so the pipe will not be deformed.

b. Remove burrs and clean shavings from the cut surface

If the shape of the pipe end is poor after removing burrs, or if shavings adhere to the flared area, it may lead to refrigerant leaks. To prevent this, turn the cut surface downward and remove burrs, then clean the surface, carefully.

Fig. 10 Flaring dimensions

c. Insert the flare nut (be sure to use the same nut that is

used on the AC unit)

d. Flaring

Check the clamp bar and the cleanliness of the copper pipe. Be sure to use the clamp bar to do the flaring with accuracy. Use either an R410A flaring tool, or a conventional flaring tool. flaring tools come in different sizes, so be sure to check the size before using. When using a conventional flaring tool, use the copper pipe gauge for clearance adjustment, etc., to ensure the correct A dimension (see Fig. 10)

Philips CS-E15DB4EW — 10.3.2. Processing and Connecting Piping Materials diagram (page 47)
Fig. 61 · 10.3.2. Processing and Connecting Piping Materials

Fig. 11 Relation between the flare nut structure and flaring tool end

Page 48 of the Philips CS-E15DB4EW user manual — 10.3.3. Storing and Managing Piping Materials
Page 48 · click to enlarge
Page 48

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Table 11 R410A flaring dimensions Nominal diameter

A (mm) R410A flaring tool, clutch type

Conventional flaring tool Clutch type Wing-nut type 1/4 6.35 0.8 0 - 0.5 1.0 - 1.5 1.5 - 2.0 3/8 9.52 0.8 0 - 0.5 1.0 - 1.5 1.5 - 2.0 1/2 12.70 0.8 0 - 0.5 1.0 - 1.5 2.0 - 2.5

Table 12 R22 flaring dimensions Nominal diameter

A (mm) R410A flaring tool, clutch type

Conventional flaring tool Clutch type Wing-nut type 1/4 6.35 0.8 0 - 0.5 0.5 - 1.0 1.0 - 1.5 3/8 9.52 0.8 0 - 0.5 0.5 - 1.0 1.0 - 1.5 1/2 12.70 0.8 0 - 0.5 0.5 - 1.0 1.5 - 2.0

Table 13 R410A flare and flare nut dimensions Unit: mm Nominal diameter

A +0, -0.4 B dimension

width 1/4 6.35 0.8 9.1 9.2 6.5 13 17 3/8 9.52 0.8 13.2 13.5 9.7 20 22 1/2 12.70 0.8 16.6 16.0 12.9 23 26

Table 14 R22 flare and flare nut dimensions Unit: mm Nominal diameter

A +0, -0.4 B dimension

width 1/4 6.35 0.8 9.0 9.2 6.5 13 17 3/8 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24

2. Procedure and precautions for flare connection

a. Check to make sure there is no scratches, dust, etc., on the flare and union.

b. Align the flared surface with the axial center of the union.

c. Use a torque wrench, and tighten to the specified torque. The tightening torque for R410A is the same as the conventional

torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split the flare nut or make it impossible to remove the flare nut.

Table 15 R410A tightening torque Nominal diameter

Torque wrench tightening torque

N.m (kgf.cm) 1/4 6.35 14 - 18 (140 - 180) 18 (180) 3/8 9.52 33 - 42 (330 -420) 42 (420) 1/2 12.70 55 (550) 55 (550)

N.m (kgf.cm)

10.3.3. Storing and Managing Piping Materials

1. Types of piping and their storage

The following is a general classification of the refrigerant pipe materials used for ACs.

Philips CS-E15DB4EW — 10.3.3. Storing and Managing Piping Materials diagram (page 48)
Fig. 62 · 10.3.3. Storing and Managing Piping Materials

Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.

2. Makings and management

a. Sheathed copper pipes and copper-element pipes

When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same nut that is used on the AC unit.

Show 22 more labels / short text on this page
Outside diameter · Wall thickness · (mm) · (mm) · Outside diameter · Wall thickness · (mm) · (mm) · Outside diameter (mm) · Wall thickness · C dimension · D dimension · Flare nut · (mm) · Outside diameter (mm) · Wall thickness · C dimension · D dimension · Flare nut · (mm) · Outside diameter (mm) · Tightening torque
Page 49 of the Philips CS-E15DB4EW user manual — 10.4. Installation, Transferring, Servicing
Page 49 · click to enlarge
Page 49

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

b. Copper pipes

Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.

3. Precautions during refrigerant piping work

Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and dust is even more important that in conventional piping).

a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.

b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil,

and lead to malfunctions in the equipment.

c. Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing

the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.

10.4. Installation, Transferring, Servicing

10.4.1. Inspecting Gas Leaks with a Vacuum Pump for New Installations (Using New Refrigerant Piping)

1. From the viewpoint of protecting the global environment, please do not release refrigerant into the atmosphere.

a. Connect the projecting side (pin-pushing side) of the charging hose for the manifold gauge to the service port of the 3-way

valve. (1)

b. Fully open the handle Lo of the manifold gauge and run the vacuum pump. (2) (If the needle of the low-pressure gauge

instantly reaches vacuum, re-check step a).)

c. Continue the vacuum process for at least 15 minutes, then check to make sure the low-pressure gauge has reached -0.1

MPa (-76 cmHg). Once the vacuum process has finished, fully close the handle Lo of the manifold gauge and stop the vacuum pump operation, then remove the charging hose that is connected to the vacuum pump adaptor. (Leave the unit in that condition for 1-2 minutes, and make sure that the needle of the manifold gauge does not return.) (2) and (3)

d. Turn the valve stem of the 2-way valve 90° counter-clockwise to open it, then, after 10 seconds, close it and inspect for a

e. Remove the charging hose from the 3-way valve service port, then open both the 2-way valve and 3-way valve. (1) (4) (Turn

the valve stem in the counter-clockwise direction until it gently makes contact. Do not turn it forcefully).

f. Tighten the service port cap with a torque wrench (18 N.m (1.8 kgf.m)). (5) Then tighten the 2-way valve and 3-way valve

caps with a torque wrench (42 N.m (4.2 kgf.m)) or (55 N.m (5.5 kgf.m)). (6)

g. After attaching each of the caps, inspect for a gas leak around the cap area. (5) (6)

Philips CS-E15DB4EW — 10.4. Installation, Transferring, Servicing diagram (page 49)
Fig. 63 · 10.4. Installation, Transferring, Servicing
  • Be sure to read the instructions for the vacuum pump,

vacuum pump adaptor and manifold gauge prior to use, and follow the instructions carefully.

  • Make sure that the vacuum pump is filled with oil up to

the designated line on the oil gauge.

  • The gas pressure back flow prevention valve on the

charging hose is generally open during use. When you are removing the charging hose from the service port, it will come off more easily if you close this valve.

Fig. 12 Vacuum pump air purging configuration

gas leak (4) · Precautions

Page 50 of the Philips CS-E15DB4EW user manual — 10.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)
Page 50 · click to enlarge
Page 50

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

10.4.2. Transferring (Using New Refrigerant Piping)

1. Removing the unit

a. Collecting the refrigerant into the outdoor unit by pumping down

The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.

  • Check to make sure that the valve stems of the 2-way valve and 3-way valve have been opened by turning them counter-

clockwise. (Remove the valve stem caps and check to see that the valve stems are fully opened position. Always use a hex wrench (with 4-mm opposing sides) to operate the valve stems.)

  • Press the TEST RUN button on the indoor unit, and allow preliminary operation for 5-6 minutes. (TEST RUN mode)
  • After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valve by turning the valve stem in

the clockwise direction.

  • Press the TEST RUN button on the indoor unit again, and after 2-3 minutes of operation, turn the valve stem of the 3-

way valve quickly in the clockwise direction to close it, then stop the operation.

  • Tighten the caps of the 2-way valve and 3-way valve to the stipulated torque.
  • Remove the connection pipes (liquid side and gas side).

b. Removing the indoor and outdoor units.

  • Disconnect the pipes and connecting electric cables from between the indoor and outdoor units.
  • Put capped flare nuts onto all of the pipe connections of the indoor and outdoor units, to make sure no dust or other

foreign matter enters.

  • Remove the indoor and outdoor units.
2. Installing the unit

Install the unit using new refrigerant piping. Follow the instructions in section 4.1 to evacuate the pipes connecting the indoor and outdoor units, and the pipes of the indoor unit, and check for gas leaks.

10.4.3. AC Units Replacement (Using Existing Refrigerant Piping)

When replacing an R410A AC unit with another R410A AC unit, you should re-flare the refrigerant piping. Even though the replacement AC unit uses the R410A, problems occur when, for example, either the AC unit maker or the refrigerating machine oil is different. When replacing an R22 AC unit with an R410A AC unit, the following checks and cleaning procedures are necessary but are difficult to do because of the chemical characteristics of the refrigerating machine oil (as described in items c) and d) of section About R410A Refrigerant). In this case, you should use new refrigerant piping rather than the existing piping.

1. Piping check

Because of the different pressure characteristics of R22 and R410A, the design pressure for the equipment is 1.6 times different. the wall thickness of the piping must comply with that shown in Table 10, but this is not easy to check. Also, even if the thickness is correct, there may be flattened or bent portions midway through the piping due to sharp curves. Buried sections of the piping also cannot be checked.

2. Pipe cleaning

A large quantity of refrigerating machine oil (mineral oil) adheres to existing pipes due to the refrigeration cycle circulation. If the pipes are used just as they are for the R410A cycle, the capacity will be lowered due to the incompatibility of this oil with the R410A, or irregularities may occur in the refrigeration cycle. For this reason, the piping must be thoroughly cleaned, but this is difficult with the present technology.

10.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)

Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.

Page 51 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 51 · click to enlarge
Page 51

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

10.4.5. Recharging Refrigerant During Servicing

When recharging is necessary, insert the specified amount of new refrigerant in accordance with the following procedure.

1. Connect the charging hose to the service port of the outdoor unit.
2. Connect the charging hose to the vacuum pump adaptor. At this time, fully open the 2-way valve and 3-way valve.
3. Fully open the handle Lo of the manifold gauge, turn on the power of the vacuum pump and continue the vacuum process for

at least one hour.

4. Confirm that the low pressure gauge shows a reading of -0.1 Mpa (-76 cmHg), then fully close the handle Lo, and turn off the

vacuum pump. Wait for 1-2 minutes, then check to make sure that the needle of the Low pressure gauge has not returned. See Fig. 13 for the remaining steps of this procedure.

5. Set the refrigerant cylinder onto the electronic scale, then connect the hose the cylinder and to the connection port for the

electronic scale. (1)(2)

Precaution:

Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid without having to turn the cylinder around

6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the

electronic scale. (2)(3)

7. Open the valve of the refrigerant cylinder, then open the charging valve slightly and close it. Next, press the check valve of the

manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closely at this point.)

8. After adjusting the electronic scale to zero, open the charging valve, then open the valve Lo of the manifold gauge and charge

with the liquid refrigerant. (2)(5) (Be sure to read the operating instructions for the electronic scale.)

9. If you cannot charge the stipulated amount, operate the unit in the cooling mode while charging a little of the liquid at a time

(about 150 g/time as a guideline). If the charging amount is insufficient from one operation, wait about one minute, then use the same procedure to do the liquid charging again.

Precaution:

Never use the gas side to allow a larger amount of liquid refrigerant to be charged while operating the unit.

10. Close the charging valve, and after charging the liquid refrigerant inside the charging hose, fully close the valve Lo of the

manifold gauge, and stop the operation of the unit. (2)(5)

11. Quickly remove the charging hose from the service port. (6) If you stop midway through, the refrigerant that is in the cycle will

be discharged.

12. After putting on the caps for the service port and operating valve, inspect around the caps for a gas leak. (6)(7)
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 51)
Fig. 64

Fig. 13 Re-charging refrigerant

Page 52 of the Philips CS-E15DB4EW user manual — 10.4.7. Servicing Tips
Page 52 · click to enlarge
Page 52

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

10.4.6. Brazing

As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N2) flow.

<Brazing Method for Preventing Oxidation>

1. Attach a reducing valve to the nitrogen gas cylinder.
2. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to prevent the nitrogen gas

from flowing backward.

3. When the nitrogen gas is flowing, be sure to keep the piping end open.
4. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m 3 /h, or 0.02 MPa (0.2 kgf/cm 2 ) by means of the reducing valve.
5. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at

which pipes are touchable with finger).

6. Completely remove the flux after brazing.
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 52)
Fig. 65

Fig. 14 Prevention of Oxidation during Brazing

1. General Cautions

a. The brazing strength should be high as required.

b. After operation, airtightness should be kept under pressurized condition.

c. During brazing do not allow component materials to become damaged due to overheating.

d. The refrigerant pipe work should not become blocked with scale or flux.

e. The brazed part should not restrict the flow in the refrigerant circuit.

f. No corrosion should occur from the brazed part.

2. Prevention of Overheating

Due to heating, the interior and exterior surfaces of treated metal may oxidize. Especially, when the interior of the refrigerant circuit oxidizes due to overheating, scale occurs and stays in the circuit as dust, thus exerting a fatally adverse effect. So, make brazing at adequate brazing temperature and with minimum of heating area.

3. Overheating Protection

In order to prevent components near the brazed part from overheating damage or quality deterioration due to flame or heat, take adequate steps for protection such as (1) by shielding with a metal plate, (2) by using a wet cloth, and (3) by means of heat absorbent.

4. Movement during Brazing

Eliminate all vibration during brazing to protect brazed joints from cracking and breakage.

5. Oxidation Preventative

In order to improve the brazing efficiency, various types of antioxidant are available on the market. However, the constituents of these are widely varied, and some are anticipated to corrode the piping materials, or adversely affect HFC refrigerant, lubricating oil, etc. Exercise care when using an oxidation preventive.

10.4.7. Servicing Tips

The drier must also be replaced whenever replacing the refrigerant cycle parts. Replacing the refrigerant cycle parts first before replacing the drier. The drier is supplied in a vacuum pack. Perform brazing immediately after opening the vacuum pack, and then start the vacuum within two hours. In addition, the drier also needs to be replaced when the refrigerant has leaked completely. (Applicable for drier models only)

Page 53 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 53 · click to enlarge
Page 53

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

11 Installation Instructions

11.1. Safety Precautions

  • Read the following “SAFETY PRECAUTIONS” carefully before installation.
  • Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit

for the model to be installed.

  • The caution items stated here must be followed because these important contents are related to safety. The meaning of each

indication used is as below.

Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.

The items to be followed are classified by the symbols:

Symbol with background white denotes item that is PROHIBITED from doing.

  • Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and

maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

WARNING 1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire. 2. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock. 4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, unit will drop and cause injury. 5. For electrical work, please follow the local national wiring standard & regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 6. Use the specified cable and connect tightly for indoor/outdoor connection. Please clamp the cable firmly so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. 7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock. 8. When carrying out piping connection, please take care not to let air or other substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury. 9. When connecting the piping, do not allow air or any substances other than the specified refrigerant (R410A) to enter the refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and injury.

10. • When connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A materials.
  • Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8

mm.

  • It is desirable that the amount of residual oil is less than 40 mg/10 m.
11. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
Page 54 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 54 · click to enlarge
Page 54

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

ATTENTION 1. Selection of the installation location and installation. Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance. 2. Power supply connection to the room air conditioner. Connect the power supply cord of the room air conditioner to the mains using one of the following method. Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited. 1. Power supply connection to the socket using a power plug.

Use an approved 15A power plug with earth pin for the connection to the socket.

2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for the permanent

connection. It must be a double pole switch with a minimum 3.5 mm contact gap. 3. Do not release refrigerant. Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite. 4. Installation work. It may need two people to carry out the installation work. 5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

Page 55 of the Philips CS-E15DB4EW user manual — 11.2.1. SELECTING THE LOCATION FOR THE INDOOR UNIT
Page 55 · click to enlarge
Page 55

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 55)
Fig. 66
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 55)
Fig. 67

CZ-4F5, 7, 10BP

Select the best location

OUTDOOR UNIT

  • If an awning is built over the unit to prevent direct

sunlight or rain, be careful that heat radiation from the condenser is not obstructed.

  • There should not be any animal or plant which could

be affected by hot air discharged.

  • Keep the spaces indicated by arrows from wall,

ceiling, fence or other obstacles.

  • Do not place any obstacles which may cause a short

circuit of the discharged air.

  • If piping length is over 10m, additional refrigerant
  • This illustration is for explanation purposes only.

should be added as shown in the table.

The indoor unit will actually face a different way.

Philips CS-E15DB4EW — OUTDOOR UNIT diagram (page 55)
Fig. 68

11.2. Indoor Unit

11.2.1. SELECTING THE LOCATION FOR THE INDOOR UNIT

Provide a check port on the piping side ceiling for repair and maintenance.

  • Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air throughout

the room.

3. Recommended installation height for indoor unit shall be at least 2.5 m.

Attached accessories · Applicable piping kit

Page 56 of the Philips CS-E15DB4EW user manual — NOTE
Page 56 · click to enlarge
Page 56

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 56)
Fig. 69

* If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.

WARNING

4. The installation position must be able to support a load four times the indoor unit weight.
5. The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
6. The indoor unit must allow easy draining.
7. The indoor unit must allow easy connection to the outdoor unit.
8. Place the indoor unit according to the height from the ceiling shown in the illustration below.
9. The indoor unit must be from at least 3m away from any noise-generating equipment. The electrical wiring must be shielded

with a steel conduit.

10. If the power supply is subject to noise generation, add a suppressor.
11. Do not install the indoor unit in a laundry. Electric shocks may result.

NOTE

− Thoroughly study the following installation locations

1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo fan, the fin

of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying, dispersing of water drops, drain pump malfunction, etc.

In these cases, take the following actions:

− Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws

oily steam which should not flow into the suction of the air conditioner.

− Make enough distance from the cooking room to install the air conditioner in such place where it may not suck in oily

steam.

Philips CS-E15DB4EW — NOTE diagram (page 56)
Fig. 70
2. Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially in

factories, etc.

3. Avoid places where inflammable gas is generated, flows-in, contaminated, or leaked.
4. Avoid places where sulphurous acid gas or corrosive gas can be generated.
5. Avoid places near high frequency generators.

Model Name Height in the ceiling CS-E15DB4** CS-E21DB4** CS-E18DB4**

280 mm or more

Page 57 of the Philips CS-E15DB4EW user manual — 11.2.3. REFRIGERANT PIPING
Page 57 · click to enlarge
Page 57

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

11.2.2. INSTALLATION OF INDOOR UNIT

This air conditioner uses a drain up motor. Horizontally install the unit using a level gauge.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 57)
Fig. 71

CEILING OPENING DIMENSIONS AND HANGING BOLT

LOCATION

The paper model for installation expand or shrink according to temperature and humidity.

Check on dimensions before using it.

  • The dimensions of the paper model for installations the

same as those of the ceiling opening dimensions.

  • Be sure to discuss the ceiling drilling work with the workers

concerned.

POSITIONS OF AIR CONDITIONER BODY AND CEILING SURFACE

Philips CS-E15DB4EW — POSITIONS OF AIR CONDITIONER BODY AND CEILING SURFACE diagram (page 57)
Fig. 72

11.2.3. REFRIGERANT PIPING

Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit. (Additional charging, etc.)

Philips CS-E15DB4EW — 11.2.3. REFRIGERANT PIPING diagram (page 57)
Fig. 73
1. Brazing for piping.

a. Execute brazing before tightening the flare nut.

b. Brazing must be executed while blowing nitrogen gas.

(This prevents generation of oxidized scale in copper pipe.)

2. When there is a lot of brazings for long piping, install a

strainer midway of the piping. (The strainer is locally supplied.)

3. Use clean copper pipe with inner wall surface free from mist

and dust. Blow nitrogen gas or air to blow off dust in the pipe before connection.

4. Form the piping according to its routing. Avoid bending and

bending back the same piping point more than three times.

(This will result in hardening of the pipe).

5. After deforming the pipe, align centers of the union fitting of

the indoor unit and the piping, and tighten them firmly with wrenches.

6. Connect pipe to the service valve or ball valve which is

located below the outdoor unit.

7. After completed the piping connection, be sure to check if

there is gas leakage in indoor and outdoor connection.

Page 58 of the Philips CS-E15DB4EW user manual — 11.2.4. INDOOR UNIT DRAIN PIPING
Page 58 · click to enlarge
Page 58

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.

The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.

Flare nut fastening torque N·m (kgf·cm) ø6.35 mm 18 (180) ø12.7 mm 55 (560) ø19.05 mm 100 (1020) ø9.52 mm 42 (430) ø15.88 mm 65 (660)

Liquid size piping Gas side piping ø6.35 mm (1/4”) ø12.7 mm (1/2”)

11.2.4. INDOOR UNIT DRAIN PIPING

  • Drain piping must have down-slope (1/50 to 1/100); be sure not to provide up-and-down slope to prevent reversal flow.
  • Be sure to check no air trap and to ensure smooth water flow and no abnormal.
  • During drain piping connection, be careful not to exert extra force on the drain port at the indoor unit.
  • The outside diameter of the drain connection at the indoor unit is 32mm.

Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings.

  • Be sure to perform heat insulation on the drain piping.

Heat insulation material: Polyvinylene foam with thickness more than 8 mm (local supply).

Philips CS-E15DB4EW — 11.2.4. INDOOR UNIT DRAIN PIPING diagram (page 58)
Fig. 74
  • The height of drain may be possible up to 750 mm.
  • When drain set piping, install as shown in the figure below.
Philips CS-E15DB4EW — 11.2.4. INDOOR UNIT DRAIN PIPING diagram (page 58)
Fig. 75
Philips CS-E15DB4EW — 11.2.4. INDOOR UNIT DRAIN PIPING diagram (page 58)
Fig. 76

Drain Test The air conditioner uses a drain up motor to drain water. Use the following procedure to test the drain up motor operation.

  • Connect the main drain pipe to exterior and leave it provisionally until the test comes to an end.
  • Feed water to the flexible drain hose and check the piping for leakage.
  • Be sure to check the drain up motor for normal operating and noise when electric wiring is complete.
  • When the test is complete, connect the flexible drain hose to the drain port.
  • Pour about 600-700cc of water in the drain pan of the indoor unit. (Pour from the position specified in the drawing by using a

water supply bottle or other suitable tool.)

  • Press the drain pump test run on pcb to start the drain motor, and verity water drainage.

(The drain motor will automatically stop after operating for about five minutes.)

Vacuum drying

Page 59 of the Philips CS-E15DB4EW user manual — 11.2.5. HEAT INSULATION
Page 59 · click to enlarge
Page 59

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 59)
Fig. 77

11.2.5. HEAT INSULATION

1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
Philips CS-E15DB4EW — 11.2.5. HEAT INSULATION diagram (page 59)
Fig. 78
2. Precautions in high humidity circumstance.

This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:

  • Heat insulation material to be prepared Adiabatic glass wool with thickness 10 to 20 mm.
  • Stick glass wool on all air conditioners that are located in ceiling atmosphere.
  • In addition to the normal heat insulation (thickness: more than 8 mm) for refrigerant piping (gas piping: thick piping) and

drain piping, add a further of 10 mm to 30 mm thickness material.

Philips CS-E15DB4EW — 11.2.5. HEAT INSULATION diagram (page 59)
Fig. 79
  • When the outdoor unit is installed on a higher position

than the indoor unit, install the trap so as not to instill rain water into the wall by transmitting in piping.

  • Stuff the space among piping, the electric wire, andthe

drain hose with “Putty” and seal the penetration wall hole.

Make sure that rain water do not instill into the wall.

Wall seal

Page 60 of the Philips CS-E15DB4EW user manual — CAUTION
Page 60 · click to enlarge
Page 60

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

11.2.6. CONNECTING THE CABLE TO THE INDOOR

  • Remove the mounting screw, remove the control box cover,

Earth lead wire shall be longer than other wires as shown in the figure for the electrical safety in case of the slipping out of the cord from anchorage.

and then connect the wires by following the procedure given in the illustration.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 60)
Fig. 80
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 60)
Fig. 81

11.2.7. INSTALLATION OF DECORATIVE PANEL

The decorative panel has its installation direction. Confirm the direction by displaying the piping side.

1. Remove the air inlet grille by moving the catchers to center.
Philips CS-E15DB4EW — 11.2.7. INSTALLATION OF DECORATIVE PANEL diagram (page 60)
Fig. 82
2. Fitting the decorative panel
Philips CS-E15DB4EW — 11.2.7. INSTALLATION OF DECORATIVE PANEL diagram (page 60)
Fig. 83
  • Temporarily secure the fixing screws (3 pcs.) before fitting

the decorative panel. (For temporarily securing the front grille.)

  • Place decorative panel on the screws (3 pcs.) before fitting,

move decorative panel as illustrated and tighten all the screws (4 pcs.).

CAUTION

  • Check before hand the height from the ceiling to the

unit.

  • The front grille fitting direction is determined by the unit

direction.

  • Only use the screws with the length of 35mm which is

provided, to fix the decorative panel.

  • Do not use other screw which is longer it may cause

damage to the drain-pan and other components.

Page 61 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 61 · click to enlarge
Page 61

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

3. Fit the decorative panel and ceiling wall together and confirm no gap in between. Readjust indoor unit height, if there is a gap between ceiling wall and decorative panel.
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 61)
Fig. 84
4. Open the indoor control box cover. (2 pcs)
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 61)
Fig. 85
5. Insert firmly the connector of cosmetic louver to indoor pcb CN-STM1, CN-DISP and CN-STM2.

Be caution not to clamp the cord in between control board and control board cover.

6. After complete, install back removed part follow opposite procedure.
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 61)
Fig. 86
Page 62 of the Philips CS-E15DB4EW user manual — CUTTING AND FLARING THE PIPING
Page 62 · click to enlarge
Page 62

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

11.3. Outdoor Unit

11.3.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section)

11.3.2. INSTALL THE OUTDOOR UNIT

  • After selecting the best location, start installation according
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 62)
Fig. 87

to Indoor/Outdoor Unit Installation Diagram.

1. Fix the unit on concrete or rigid frame firmly and horizontally

by bolt nut. (ø10 mm).

2. When installing at roof, please consider strong wind and

earthquake. Please fasten the installation stand firmly with bolt or nails.

11.3.3. CONNECTING THE PIPING

Connecting The Piping To Indoor Unit

Philips CS-E15DB4EW — 11.3.3. CONNECTING THE PIPING diagram (page 62)
Fig. 88

Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)

  • Align the center of piping and sufficiently tighten the flare

nut with fingers.

Piping size (Torque) Gas Liquid 1/2” (55 N.m) 1/4” (18 N.m)

  • Further tighten the flare nut with torque wrench in specified

torque as stated in the table.

Connecting The Piping To Outdoor Unit

Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (located at valve) onto the copper pipe.

Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.

CUTTING AND FLARING THE PIPING

1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.

Turn the piping end down to avoid the metal powder entering the pipe.

3. Please make flare after inserting the flare nut onto the copper pipes.
Philips CS-E15DB4EW — CUTTING AND FLARING THE PIPING diagram (page 62)
Fig. 89

Connect the piping

Page 63 of the Philips CS-E15DB4EW user manual — CAUTION
Page 63 · click to enlarge
Page 63

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

11.3.4. EVACUATION OF THE EQUIPMENT

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 63)
Fig. 90
1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
  • Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to

-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.

4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not

move after approximately five minutes.

5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal

wrench (4 mm).

8. Mount valve caps onto the 2-way valve and the 3-way valve.
  • Be sure to check for gas leakage.

CAUTION

  • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
  • If the leak stops when the piping connections are tightened further, continue working from step 3.
  • If the leak does not stop when the connections are retightened, repair the location of leak.
  • Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause

frostbite.

Page 64 of the Philips CS-E15DB4EW user manual — 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
Page 64 · click to enlarge
Page 64

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

11.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT

(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)

1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5 mm 2 flexible cord,

type designation 245 IEC 57 or heavier cord.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 64)
Fig. 91
3. Secure the cable onto the control board with the holder (clamper).
4. Cable connection to the power supply through knife switch (Disconnecting means).
  • Connect the approved polychloroprene sheathed power supply cable (3 x 2.5 mm 2 ), type designation 245 IEC 57 or heavier

cord to the terminal board, and connect the other end of the cable to knife switch (Disconnecting means).

− Secure the cable onto the control board with the holder (clamper).

11.3.6. PIPE INSULATION

1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap

the insulated piping end to prevent water from going inside the piping.

2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM

with thickness 6 mm or above.

DISPOSAL OF OUTDOOR UNIT DRAIN WATER

Philips CS-E15DB4EW — DISPOSAL OF OUTDOOR UNIT DRAIN WATER diagram (page 64)
Fig. 92
  • If a drain elbow is used, the unit should be placed on a

stand which is taller than 3 cm.

  • If the unit is used in an area where temperature falls below

0°C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.

AUTO SWITCH OPERATION

Philips CS-E15DB4EW — AUTO SWITCH OPERATION diagram (page 64)
Fig. 93

The following operations can be performed by pressing the “AUTO” switch.

1. AUTO OPERATION MODE

The Auto operation will be activated immediately once the Auto Switch is pressed.

2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING

PURPOSE)

The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below 8 sec. A “beep” sound will occur at the fifth sec., in order to identify the starting of Test Run operation.

Page 65 of the Philips CS-E15DB4EW user manual — HAND OVER
Page 65 · click to enlarge
Page 65

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

CHANGING THE REMOTE CONTROL TRANSMISSION

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 65)
Fig. 94

CODE

1. Press AUTO SW continuously for 11 seconds (buzzer

sound = pep pep pep)

2. After 11 seconds, release AUTO SW, then press Remo-

” SW continuously for 5 seconds. Reset code will be transmitted. After the reset code is transmitted, release TIMER “

” SW.

3. Press Remo-Con “OFF/ON” button. The new Remo-Con

No. will be accepted and memorized, after which the new Remo-Con No. can be used.

Philips CS-E15DB4EW — CODE diagram (page 65)
Fig. 95

REMO-CON NO. CHANGE IN REMOTE CONTROL

1. Remove the batteries from the battery compartment of the

Remote Control.

2. On the left side of the battery compartment, there is a small

opening in the centre in which Jumper (J_A) can be seen. In the accepted Remo-Con PCB shown beside, Jumper (J_B) can be seen.

J_A J_B Remo-Con No. Short Open A (Default) Open Open B Short Short C Open Short D

CHECK ITEMS

Is there any gas leakage at flare nut connections?

Is the cooling operation normal?

Has the heat insulation been carried out at flare nut connections?

Is the indoor unit property secured to the installation plate?

Is the power supply voltage complied with rated value?

Is the connecting cable being fixed to the terminal board firmly?

Is there any abnormal sound?

Is the connecting cable being clamped firmly?

Is the thermostat operation normal?

Is the drainage OK?

Is the remote control’s LCD operation normal?

Is the Earth wire connection properly done?

HAND OVER

  • Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature

control, etc.)

As to parts to be sold separately

  • With regards to installation of the parts sold separately, follow the installation manual which is provided with the parts sold

separately.

Con TIMER “

Page 66 of the Philips CS-E15DB4EW user manual — 12.1. Troubleshooting
Page 66 · click to enlarge
Page 66

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

12 Servicing Information

  • Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use

a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).

  • Pb free solder will tend to splash when heated too high (about 1100° F/600°C).

12.1. Troubleshooting

1. Rated Frequency Operation

During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the specification and technical data. Below are the methods used to obtain rated compressor operating specification.

(i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency.

(“beep” will be heard at the 5th second.)

Philips CS-E15DB4EW — 12.1. Troubleshooting diagram (page 66)
Fig. 96 · 12.1. Troubleshooting

(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency.

Philips CS-E15DB4EW — 12.1. Troubleshooting diagram (page 66)
Fig. 97 · 12.1. Troubleshooting

Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated frequency. (“beep” “beep” will be heard at the 8th second.)

(a) Cooling · (b) Heating

Page 67 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 67 · click to enlarge
Page 67

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

2. Troubleshooting Air Conditioner
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 67)
Fig. 98

In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.

The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 67)
Fig. 99

Refrigeration cycle system

Page 68 of the Philips CS-E15DB4EW user manual — 12.2. Breakdown Self Diagnosis Function
Page 68 · click to enlarge
Page 68

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

1. Relationship between the condition of the air conditioner and pressure and electric current

Cooling Mode Heating Mode Condition of the air

conditoner Low Pressure High Pressure Electric current during operation

Low Pressure High Pressure Electric current during operation

Insufficient refrigerant (gas leakage)

Clogged capillary tube or Strainer

Short circuit in the indoor unit

Heat radiation deficiency of the outdoor unit

  • Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

12.2. Breakdown Self Diagnosis Function

Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below breakdown diagnosis method:

  • Press “CHECK” button at remote control continuously for more than five seconds to turn on the diagnosis mode, “H11” will be

displayed at remote control.

  • By pressing the TMER “

” button once, next error code will be displayed; press “V” button once, previous error code will be displayed.

  • If error code displayed matches the error code saved in unit memory (abnormality detected), “beep, beep, beep....” sounds will

be heard for 4 seconds and Power LED will light on. Otherwise, one “beep” sound is heard.

If “CHECK” button is press again or without any operation for 30 seconds, the diagnosis mode will turn off.

Inefficient compression

Page 69 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 69 · click to enlarge
Page 69

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Abnormality / Protection control Abnormality

Primary location to verify

H11 Indoor / outdoor abnormal communication

> 1 min after starting operation

  • Internal / external cable connections
  • Indoor / Outdoor PCB H12 Connection capability rank abnormal — — — H14 Indoor intake air temperature sensor abnormality

Continue for 5 sec. — • Intake air temperature sensor

(defective or disconnected) H15 Outdoor compressor temperature sensor abnormality

Continue for 5 sec. — • Compressor temperature sensor

(defective or disconnected) H16 Outdoor Current Transformer open circuit

— — • Outdoor PCB

  • IPM (Power transistor) module H19 Indoor fan motor merchanism lock — —
  • Indoor PCB
  • Fan motor H21 Indoor float switch operation abnormal — — — H23 Indoor heat exchanger temperature sensor abnormality

Continue for 5 sec. O (Cooling only)

  • Heat exchanger temperature sensor

(defective or disconnected) H27 Outdoor air temperature sensor abnormality

Continue for 5 sec. O • Outdoor temperature sensor

(defective or disconnected) H28 Outdoor heat exchanger temperature sensor abnormality

Continue for 5 sec. O • Outdoor heat exchanger

temperature sensor (defective or disconnected) H30 Discharge temperature sensor abnormality

Continue for 5 sec. — • Discharge temperature sensor

H33 Indoor/Outdoor wrong connection — — • Indoor/Outdoor supply voltage H35 Indoor drain water adverse current abnormal

H38 Indoor/Outdoor mismatch (brand code) — — — H97 Outdoor Fan Motor lock abnormality — — • Outdoor PCB

  • Outdoor Fan Motor H98 Indoor high pressure protection — —
  • Air filter dirty
  • Air circulation short circuit H99 Indoor heat exchanger anti-freezing protection

— — • Insufficient refrigerant

  • Air filter dirty F11 Cooling / Heating cycle changeover abnormality

4 times occurance within 30 minutes

— • 4-way valve

  • V-coil F90 PFC control 4 times occurance within 10 minutes

— • Voltage at PFC

F91 Refrigeration cycle abnormality 7 times occurance continuously

— • No refrigerant

(3-way valve is closed) F93 Outdoor compressor abnormal revolution 4 times occurance within 20 minutes

— • Outdoor compressor

F95 Cool high pressure protection 4 times occurance within 20 minutes

— • Outdoor refrigerant circuit

F96 IPM (power transistor) overheating protection

— — • Excess refrigerant

  • Improper heat radiation
  • IPM (Power transistor) F97 Outdoor compressor overheating protection

4 times occurance within 20 minutes

— • Insufficient refrigerant

  • Compressor F98 Total running current protection 3 times occurance within 20 minutes

— • Excess refrigerant

  • Improper heat radiation F99 Outdoor Direct Current (DC) peak detection

7 times occurance continuously

— • Outdoor PCB

  • IPM (Power transistor)
  • Compressor

“O” - Frequency measured and fan speed fixed.

The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “RESET” button at Remote Control.

Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is changed from one “beep” to four “beep” sounds.

Show 8 more labels / short text on this page
Error Codes Table · Diagnosis · Emergency · display · Judgement · operation · Indoor fan operation · only
Page 70 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 70 · click to enlarge
Page 70

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

12.3. Remote Control

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 70)
Fig. 100
  • When the batteries are inserted for the first time or the

batteries are replaced, you may notice the indications at remote control’s display screen blink continuously and not functionable. If this condition happens, try to reset the remote control by pushing the reset terminal with a pointing device.

  • You may also do the reset to erase the setting at remote

control and restore back the default setting.

Setting Remote Control Transmission Code

  • There are 4 types of remote control transmission code could be selected. The indoor unit will only operate when received

signal with same transmission code from remote control. This could prevent signal interference when there are 2 or more indoor unit installed nearby together.

  • To change remote control transmission code, short or open jumpers at the remote control printed circuit board.
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 70)
Fig. 101
  • Under various setting mode, after select the transmission code combination of remote control, press “Timer Decrement”

button of remote control for 5 seconds to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.

  • After signal is received, the various setting mode is cancelled and return to normal operation.

Remote Control Reset

Page 71 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 71 · click to enlarge
Page 71

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

12.4. Auto OFF/ON Button

  • The “Auto OFF/ON” button is used to operate the air conditioner if remote control is misplaced or malfunctioning.
  • Auto operation is started once “Auto OFF/ON” button is pressed.
  • Forced cooling operation is possible by pressing the “Auto OFF/ON” button for more than 5 seconds where “beep” sound is

heard, then release the button.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 71)
Fig. 102
  • By continuously pressing the “Auto OFF/ON” button, it will enable standby states for Forced Heating Operation, Various Setting

Mode and Individual Correspondence Mode. At standby state, the unit still operates with Forced Cooling Operation.

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 71)
Fig. 103
  • Press “Timer Decrement” button of remote control for 5 seconds to activate the standby mode, where “beep” sound is heard.
  • In Various Setting Mode, the unit captures remote control transmission code when “Check” button is pressed.
  • In Individual Correspondence Mode, press “Check” button at remote control to enter remote control signal receiving sound

selection mode.

Press “Auto OFF/ON” button to trigger the remote control signal receiving sound.

− Short “Beep”: Turn OFF remote control signal receiving sound.

− Long “Beep”: Turn ON remote control signal receiving sound.

  • After signal is received, the unit returns to normal operation.
Page 72 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 72 · click to enlarge
Page 72

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

12.5. Disassembly of Parts

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 72)
Fig. 104
1. Open the Intake Grille from the Front Grille by moving the

catchers to center (Fig. 1).

2. Remove the Control Board Cover by removing the screws
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 72)
Fig. 105

(Fig. 2).

3. Release the (Fig. 3):
  • CN-STM1 (WHT) connector.
  • CN-STM2 (YLW) connector.
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 72)
Fig. 106
  • CN-DISP (WHT) connector.
  • CN-FM (WHT) connector.
  • CN-TH1 (WHT) connector.
  • CN-TH2 (BLU) connector.
  • CN-DRMTR1 (BLU) connector.
  • AC01 (BLK), AC02 (WHT) and CN-DRMTR2 (RED)

from Terminal Board.

  • G01 (GRN) screw.
  • Two T-BLK connectors.
  • CN-T1 (WHT).
  • CN-T2 (YLW).
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 72)
Fig. 107
4. To remove the Electronic Controller, release the 6 hooks

that hold it to the Control Board (Fig. 4).

Page 73 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 73 · click to enlarge
Page 73

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 73)
Fig. 108
5. Remove the Front Grille by removing the screw A and

screws B, C & D half way open (Fig. 5).

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 73)
Fig. 109
6. Remove the Air Guider and Drain Pan complete by

removing the screws (Fig. 6).

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 73)
Fig. 110
7. Remove the Turbo Fan by removing the bolt (Fig. 7).
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 73)
Fig. 111
8. Remove the Fan Motor by release the Fan Motor lead wire

connectors and Fan Motor screws (Fig. 8).

Page 74 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 74 · click to enlarge
Page 74

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Outdoor Electronic Controller Removal Procedure

  • Be save to return the wiring to its original position
1. Remove the top panel and front panel
  • There are many high voltage components within the heat
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 74)
Fig. 112

sink cover so never touch the interior during operation. Wait at least two minutes after power has been turned off.

2. Remove the Outdoor Electronic Controller
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 74)
Fig. 113
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 74)
Fig. 114
Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 74)
Fig. 115
Page 75 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 75 · click to enlarge
Page 75

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

13 Technical Data

13.1. Operation Characteristics

13.1.1. CS-E15DB4EW CU-E15DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 75)
Fig. 116
Page 76 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 76 · click to enlarge
Page 76

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

13.1.2. CS-E18DB4EW CU-E18DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 76)
Fig. 117
Page 77 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 77 · click to enlarge
Page 77

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

13.1.3. CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 77)
Fig. 118
Page 78 of the Philips CS-E15DB4EW user manual — G CS-E21DB4ES CU-E21DBE
Page 78 · click to enlarge
Page 78

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

13.2. Sensible Capacity Chart

G CS-E15DB4EW CU-E15DBE

Outdoor Temp. (°C) Indoor wet bulb temp.

30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 4.07 3.08 1.19 3.80 2.96 1.28 3.53 2.84 1.37 3.21 2.70 1.48 19.0°C 4.10 1.30 19.5°C 4.46 3.23 1.21 4.17 3.10 1.31 3.88 2.99 1.40 3.53 2.84 1.51 22.0°C 4.87 3.35 1.24 4.55 3.22 1.33 4.23 3.11 1.42 3.85 2.96 1.53

G CS-E18DB4EW CU-E18DBE

Outdoor Temp. (°C) Indoor wet bulb temp.

30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 4.76 3.61 1.40 4.45 3.46 1.51 4.14 3.33 1.61 3.76 3.16 1.74 19.0°C 4.80 1.53 19.5°C 5.23 3.78 1.43 4.89 3.63 1.54 4.55 3.50 1.64 4.13 3.33 1.77 22.0°C 5.70 3.92 1.45 5.32 3.77 1.56 4.95 3.64 1.67 4.50 3.47 1.80

G CS-E21DB4ES CU-E21DBE

Outdoor Temp. (°C) Indoor wet bulb temp.

30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 5.85 4.44 1.88 5.47 4.26 2.02 5.09 4.09 2.16 4.63 3.89 2.33 19.0°C 5.90 2.05 19.5°C 6.43 4.65 1.91 6.01 4.46 2.06 5.59 4.30 2.20 5.08 4.09 2.37 22.0°C 7.00 4.82 1.95 6.54 4.63 2.10 6.09 4.47 2.24 5.53 4.26 2.42

TC - Total Cooling Capacity (kW) Indoor 27°C/19°C SHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°C IP - Input Power (kW)

Page 79 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 79 · click to enlarge
Page 79

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

14 Exploded View (Indoor Unit)

14.1. CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 79)
Fig. 119
Page 80 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 80 · click to enlarge
Page 80

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 80)
Fig. 120

The above exploded view is for the purpose of parts disassembly and replacement.

The non-numbered parts are not kept as standard service parts.

Page 81 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 81 · click to enlarge
Page 81

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

14.2. CZ-BT20E (Front Grille Complete)

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 81)
Fig. 121

The above exploded view is for the purpose of parts disassembly and replacement.

The non-numbered parts are not kept as standard service parts.

Page 82 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 82 · click to enlarge
Page 82

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

15 Replacement Parts List (Indoor Unit)

15.1. CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES

REF. NO. PARTS NAME & DESCRIPTION QTY CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES REMARKS 1 BASE PAN ASS’Y 1 CWD52K1100 ← ← 2 INNER POLYSTYRENE COMPLETE 1 CWG07C1047 ← ← 3 CABINET SIDE PLATE ASS’Y 1 CWE041121 ← ← 4 CABINET SIDE PLATE ASS’Y 1 CWE041122 ← ← 5 LEAD WIRE - FAN MOTOR 1 CWA67C5136 ← ← 6 FAN MOTOR 1 EHDS50A40AC ← ← O 7 ANTI - VIBRATION BUSHING 3 CWH501065 ← ← 8 CORD HOLDER 1 CWD741024 ← ← 9 SCREW - FAN MOTOR 3 CWH7080300 ← ← 11 TURBO FAN 1 CWH03K1022 ← ← 12 NUT for TURBO FAN 1 CWH561042 ← ← 13 SP WASHER 1 XWA8 ← ← 14 WASHER 1 XWG8H22 ← ← 15 EVAPORATOR COMPLETE 1 CWB30C1668 ← CWB30C1526 16 FLARE NUT (1/2”) 1 CWT251032 ← ← 17 HEATPROOF TUBE 1 CWG021024 ← ← 18 HEATPROOF TUBE 1 CWG021064 ← ← 19 FLARE NUT (1/4”) 1 CWT251030 ← ← 21 PIPE COVER 1 CWD93C1050 ← ← 22 SENSOR - EVAPORATOR 1 CWA50C2274 ← ← 23 HOLD SENSOR 1 CWH32143 ← ← 24 EVAPORATOR SUPPORTER 3 CWD911529A ← ← 25 TUBE ASS’Y (CAPIL. TUBE) 1 CWT07K1188 ← ← 26 DRAIN PUMP COMPLETE 1 CWB53C1015 ← ← 27 PANEL DRAIN PUMP ASS’Y 1 CWD93K1008 ← ← 28 DRAIN PUMP 1 CWB532043 ← ← 29 ANTI - VIBRATION BUSHING 3 CWH501080 ← ← 30 FLOAT SWITCH - DRAIN PUMP 1 CWA121215 ← ← 31 FLEXIBLE PIPE 1 CWH85C1033 ← ← 32 DRAIN NOZZLE 1 CWH411011 ← ← 33 DRAIN HOSE HEAT INSULATION 1 CWG321050 ← ← 35 DRAIN PAN - COMPLETE 1 CWH40C1034 ← ← 36 DRAIN PLUG 1 CWB821008 ← ← 37 AIR GUIDER BLOWER WHEEL 1 CWD321058 ← ← 38 CONTROL BOARD CASING 1 CWH10K1048 ← ← 39 ELECTRONIC CONTROLLER (MAIN) 1 CWA73C1778 CWA73C1779 CWA73C1780 O 40 SPACER 6 CWH541026 ← ← 41 TRANSFORMER 1 CWA40C1030 ← ← 43 TERMINAL BOARD - (3 PIN) 1 CWA28K1076 ← ← O 44 LEADWIRE-AIR TEMP. SENSOR 1 CWA67C5139 ← ← O 47 CONTROL BOARD COVER 1 CWH13C1100 ← ← 48 ACCESSORY COMPLETE 1 CWH82C1270 ← ← 48A HEATPROOF TUBE 1 CWG021025 ← ← 51 WIRELESS REMOTE CONTROL COMPLETE 1 CWA75C2610 ← ← O

  • All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
  • “O” marked parts are recommended to be kept in stock.

(Note)

Page 83 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 83 · click to enlarge
Page 83

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

15.2. CZ-BT20E (Front Grille Complete)

REF. NO. PART DESCRIPTION QTY PART NO. 1 FRONT GRILLE - COMPLETE 1 CWE11C3105 2 FRONE - FRONT GRILLE CO. 1 CWE11C3353 4 A.S MOTOR DC SINGLE 12V 250 OHM 2 CWA981105 5 BRACKET - A.S.MOTOR 1 CWD932522 6 VANE 4 CWE241159 7 SHAFT 6 CWH631038 8 SHAFT 2 CWH631045 9 CONNECTOR - SHAFT 4 CWH081007 10 BEARING 6 CWH641008 11 LEAD WIRE - A.S.MOTOR 1 CWA67C5117 12 PLATE COVER FOR A.S.MOTOR 1 CWD911459 13 PLATE COVER FOR CONNECTING SHAFT 2 CWD911460 14 PLATE COVER FOR END SHAFT 1 CWD911461 21 ELECTRONIC CONT. (RECEIVER & INDICATOR) 1 CWA743610 22 LEAD WIRE - COMPLETE 1 CWA67C5576 24 INTAKE GRILLE 1 CWE221131 28 LEVER ARM 2 CWH651029 29 AIR FILTER 1 CWD001142

  • All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
  • “O” marked parts are recommended to be kept in stock.

(Note)

Page 84 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 84 · click to enlarge
Page 84

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

16 Exploded View (Outdoor Unit)

16.1. CU-E15DBE CU-E18DBE CU-E21DBE

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 84)
Fig. 122

The above exploded view is for the purpose of parts disassembly and replacement.

The non-numbered parts are not kept as standard service parts.

Page 85 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 85 · click to enlarge
Page 85

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

17 Replacement Parts List (Outdoor Unit)

17.1. CU-E15DBE CU-E18DBE CU-E21DBE

REF NO. DESCRIPTION & NAME QTY. CU-E15DBE CU-E18DBE CU-E21DBE REMARKS 1 CHASSY ASSY 1 CWD50K2085 ← ← 2 ANTI-VIBRATION BUSHING 3 CWH50077 ← ← 3 COMPRESSOR 1 5CS130XAD04 ← ← O 4 NUT-COMPRESSOR MOUNT 3 CWH56000 ← ← 5 SOUND PROOF MATERIAL 1 CWG302302 ← ← 6 FAN MOTOR BRACKET 1 CWD541084 CWD541054 ← 7 FAN MOTOR 1 CWA981166 ← ← O 8 SCREW - FAN MOTOR BRACKET 2 CWH551060 ← ← 9 SCREW - FAN MOTOR MOUNT 3 CWH551106 ← ← 10 PROPELLER FAN ASSY 1 CWH03K1016 ← ← 11 NUT - PROPELLER FAN 1 CWH56053 ← ← 12 CONDENSER 1 CWB32C1583 CWB32C1527 CWB32C1526 14 TUBE ASS’Y COMPLETE (CAP TUBE/EXP.VALVE) 1 CWT023679 ← CWT023610 O 15 4 WAYS VALVE 1 CWB001026 ← ← 16 STRAINER 1 CWB11094 ← ← 18 HOLDER - COUPLING 1 CWH351035 ← ← 19 3 WAYS VALVE (GAS) 1 CWB011170 ← ← O 20 2 WAYS VALVE (LIQUID) 1 CWB021292 ← CWB021306 O 22 SOUND PROOF BOARD 1 CWH151050 ← ← 23 TERMINAL COVER 1 CWH171001 ← ← 24 NUT-TERMINAL COVER 1 CWH7080300 ← ← 25 SENSOR COMPLETE (COMP. TOP) 1 CWA50C2185 ← ← 26 HOLDER SENSOR 1 CWH321010 ← ← 27 V-COIL COMPLETE (4-WAYS VALVE) 1 CWA43C2168 ← ← 28 V-COIL COMPLETE (EXPAND VALVE) 1 CWA43C2141 ← ← 29 SENSOR COMPLETE (COMP. DISC.) 1 CWA50C2180 ← ← 30 SENSOR COMPLETE 1 CWA50C2181 ← ← 31 REACTOR 1 CWA421069 ← ← 32 CONTROL BOARD CASING (SIDE) 1 CWH102273 ← ← 33 TERMINAL BOARD ASSY 1 CWA28K1110 ← ← 34 FUSE HOLDERS 1 K3GB1PH00016 ← ← 35 FUSE 1 K5D303BBA002 ← ← 36 CONTROL BOARD CASING (TOP) 1 CWH102204 ← ← 37 CONTROL BOARD CASING (BOTTOM) 1 CWH102282 ← ← 38 ELECTRONIC CONTROLLER - MAIN 1 CWA73C1767R CWA73C1768R CWA73C1769R O 40 CONTROL BOARD COVER (TOP) 1 CWH131167 ← ← 41 CABINET SIDE PLATE (LEFT) 1 CWE041082A ← ← 42 HANDLE 1 CWE161010 ← ← 43 CABINET SIDE PLATE (RIGHT) 1 CWE041083A ← ← 44 HANDLE 2 CWE16000E ← ← 45 CABINET FRONT PLATE CO. 1 CWE06K1043 ← ← 46 WIRE NET 1 CWD041041A ← ← 47 CABINET TOP PLATE 1 CWE031031A ← ← 48 CONTROL BOARD COVER (BOTTOM) 1 CWH131168 ← ← 49 CONTROL BOARD COVER (TOP) 1 CWH131169A ← ← 50 OPERATING INSTRUCTION 1 CWF564379 ← ← 51 OPERATING INSTRUCTION 1 CWF564380 ← ← 52 INSTALLATION INSTRUCTION 1 CWF612604 ← ← 53 INSTALLATION INSTRUCTION 1 CWF612605 ← ← 54 INSTALLATION INSTRUCTION 1 CWF612606 ← ← 56 DRAIN HOSE 1 CWH5850080 ← ← 57 PACKING 1 CWB81012 ← ← 58 SOUND PROOF MATERIAL 1 CWG302290 CWG302270 ← 59 SOUND PROOF MATERIAL 1 CWG302301 CWG302300 ←

  • All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
  • “O” marked parts are recommended to be kept in stock.

(Note)

Page 86 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 86 · click to enlarge
Page 86
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 86)
Fig. 123 · 8.2.3.4. Deice Control
Page 87 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 87 · click to enlarge
Page 87
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 87)
Fig. 124 · 8.2.3.4. Deice Control

72 73 74 75 76 77 78 79 80

21 22 23 24 25 26 27 28 29

Page 88 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 88 · click to enlarge
Page 88
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 88)
Fig. 125 · 8.2.3.4. Deice Control
Page 89 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 89 · click to enlarge
Page 89
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 89)
Fig. 126 · 8.2.3.4. Deice Control
Page 90 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 90 · click to enlarge
Page 90
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 90)
Fig. 127 · 8.2.3.4. Deice Control

R93 100k 1/4W R94 100k 1/4W R95 100k 1/4W

Page 91 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 91 · click to enlarge
Page 91
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 91)
Fig. 128 · 8.2.3.4. Deice Control

C43 0.01µ C49 0.01µ C54 0.01µ

Page 92 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 92 · click to enlarge
Page 92
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 92)
Fig. 129 · 8.2.3.4. Deice Control

92 93 94 95 96 97 98 99 100

P70 P71 P72 P73 P74/IRQ00 P75/IRQ01 P76/IRQ02 P77/IRQ03 P80/ADIN00 P81/ADIN01 P82/ADIN10 P83/ADIN11 VSS VREF- P84/ADIN20 VREF+ VDD P85/ADIN21 P86/ADIN22 P87/ADIN23 P90/ADIN24 P91/ADIN25 P92/ADIN26 P93/ADIN27 P94/ADIN28

26 27 28 29 30 31 32 33 34

Page 93 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 93 · click to enlarge
Page 93
Philips CS-E15DB4EW — 8.2.3.4. Deice Control diagram (page 93)
Fig. 130 · 8.2.3.4. Deice Control

C62 10µ 50V C83 10µ 50V C97 0.1µ 16V

6 CN-STM 7 6 5 4 3 2 1 8

9 10 11 12 13 14 15 16 EXPAND

Page 94 of the Philips CS-E15DB4EW user manual — TIMER TABLE <OUTDOOR>
Page 94 · click to enlarge
Page 94

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

How to use electronic circuit diagram

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 94)
Fig. 131

TIMER TABLE <INDOOR>

Test mode Name Time (When test point

Short-circuited) 4 way valve abnormality 4 min. 24 sec. Outdoor air temp. for Hz No. decision 30 min. 0 sec. Anti-dew formation control 20 min. 0 sec. Anti-freezing control 6 min. 0 sec. Thermo OFF delay 3 min. 0 sec. Low pressure control (gas leakage) compressor OFF time 3 min. 0 sec. Time delay safety control 2 min. 58 sec. 0 sec. 20 sec. Odour timer status shift time 90 sec. 0 sec. 20 sec. 120 sec. Intake air temp. sampling time 2 min. 0 sec. Self diagnosis display time 10 sec. 0 sec. Auto mode judgement sampling time 20 sec. 0 sec. 24 hours Real Timer 1 hour 1 min. Heating SSHi fan speed shift 120 min. 12 sec. Cooling SHi fan speed shift 30 min. 3 sec. Hot start forced completion 4 min. 0.4 sec. Auto mode judgement interval 30 min. 3 sec. After Hot start / Deice 2 min. 12 sec.

TIMER TABLE <OUTDOOR>

Test mode Name Time (When test point

Short-circuited) DC PEAK 30 sec. 3 sec. 120 min. 24 sec. Deice detection 80 min. 16 sec. 40 min. 8 sec. 40 min. 8 sec. Hz lock time 30 sec. 0 sec. Outdoor fan delay operation control 30 sec. 3 sec. 4 way valve delay operation control 3 min. 18 sec.

Page 95 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 95 · click to enlarge
Page 95

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

18.3. Remote Control

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 95)
Fig. 132
Page 96 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 96 · click to enlarge
Page 96

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

18.4. Print Pattern Indoor Unit Printed Circuit Board

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 96)
Fig. 133
Page 97 of the Philips CS-E15DB4EW user manual — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE
Page 97 · click to enlarge
Page 97

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

18.5. Print Pattern Outdoor Unit Printed Circuit Board View

Philips CS-E15DB4EW — CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE diagram (page 97)
Fig. 134

[PHAAM] Printed in Malaysia

Page 98 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Page 98 · click to enlarge
Page 98
Page 98 of the Philips CS-E15DB4EW user manual — 8.2.3.4. Deice Control
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Philips CS-E15DB4EW

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.