COMSPHERE –48 Vdc CENTRAL OFFICE

POWER UNIT

INSTALLATION GUIDE

Document No. 3000-A2-GB41-40

May 1998

Page 2 of the Paradyne 3610 user manual — Trademarks
Page 2 · click to enlarge
Page 2

COMSPHERE –48 Vdc Central Office Power Unit Installation Guide 3000-A2-GB41-40

5th Edition (May 1998)

Changes and enhancements to the product and to the information herein will be documented and issued as a new release.

Warranty, Sales, and Service Information

Contact your local sales representative, service representative, or distributor directly for any help needed. For additional information concerning warranty, sales, service, repair, installation, documentation, training, distributor locations, or Paradyne worldwide office locations, use one of the following methods:

  • Via the Internet: Visit the Paradyne World Wide Web site at <a href="http://www.paradyne.com" rel="nofollow noopener" target="_blank">http://www.paradyne.com</a>
  • Via Telephone: Call our automated call system to receive current information via fax or to speak with a company representative.

— Within the U.S.A., call 1-800-870-2221 — Outside the U.S.A., call 1-727-530-2340

Trademarks

All products and services mentioned herein are the trademarks, service marks, registered trademarks or registered service marks of their respective owners.

Printed on recycled paper

COPYRIGHT 1998 Paradyne Corporation. All rights reserved.

This publication is protected by federal copyright law. No part of this publication may be copied or distributed, transmitted, transcribed, stored in a retrieval system, or translated into any human or computer language in any form or by any means, electronic, mechanical, magnetic, manual or otherwise, or disclosed to third parties without the express written permission of Paradyne Corporation, 8545 126th Avenue North, P.O. Box 2826, Largo, Florida 33779-2826.

Paradyne Corporation makes no representation or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose. Further, Paradyne Corporation reserves the right to revise this publication and to make changes from time to time in the contents hereof without obligation of Paradyne Corporation to notify any person of such revision or changes.

A May 1998 3000-A2-GB41-40

Page 3 of the Paradyne 3610 user manual — Important Safety Instructions
Page 3 · click to enlarge
Page 3

Important Safety Instructions

1. Read and follow all warning notices and instructions marked on the product or included in the manual.
2. This product is intended to be used with a three-wire grounding type plug — a plug which has a grounding pin. This is a safety feature. Equipment grounding is vital to ensure safe operation. Do not defeat the purpose of the grounding type plug by modifying the plug or using an adaptor.

Prior to installation, use an outlet tester or a voltmeter to check the ac receptacle for the presence of earth ground. If the receptacle is not properly grounded, the installation must not continue until a qualified electrician has corrected the problem.

If a three-wire grounding type power source is not available, consult a qualified electrician to determine another method of grounding the equipment.

3. Slots and openings in the cabinet are provided for ventilation. To ensure reliable operation of the product and to protect it from overheating, these slots and openings must not be blocked or covered.
4. Do not allow anything to rest on the power cord and do not locate the product where persons will walk on the power cord.
5. Do not attempt to service this product yourself, as opening or removing covers may expose you to dangerous high voltage points or other risks. Refer all servicing to qualified service personnel.
6. General purpose cables are provided with this product. Special cables, which may be required by the regulatory inspection authority for the installation site, are the responsibility of the customer.
7. When installed in the final configuration, the product must comply with the applicable Safety Standards and regulatory requirements of the country in which it is installed. If necessary, consult with the appropriate regulatory agencies and inspection authorities to ensure compliance.
8. A rare phenomenon can create a voltage potential between the earth grounds of two or more buildings. If products installed in separate buildings are interconnected , the voltage potential may cause a hazardous condition. Consult a qualified electrical consultant to determine whether or not this phenomenon exists and, if necessary, implement corrective action prior to interconnecting the products.
9. In addition, if the equipment is to be used with telecommunications circuits, take the following precautions:

— Never install telephone wiring during a lightning storm.

— Never install telephone jacks in wet locations unless the jack is specifically

designed for wet locations.

— Never touch uninsulated telephone wires or terminals unless the telephone line

has been disconnected at the network interface

— Use caution when installing or modifying telephone lines.

— Avoid using a telephone (other than a cordless type) during an electrical storm.

There may be a remote risk of electric shock from lightning.

— Do not use the telephone to report a gas leak in the vicinity of the leak.

B 3000-A2-GB41-40 May 1998

Safety Instructions

Page 4 of the Paradyne 3610 user manual — ! WARNING:
Page 4 · click to enlarge
Page 4

Notices

! WARNING:

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

The authority to operate this equipment is conditioned by the requirements that no modifications will be made to the equipment unless the changes or modifications are expressly approved by Paradyne Corporation.

! WARNING:

To Users of Digital Apparatus in Canada:

This Class A digital apparatus meets all requirements of the Canadian interference-causing equipment regulations.

Cet appareil numérique de la classe A respecte toutes les exigences du règlement sur le matérial brouilleur du Canada.

C May 1998 3000-A2-GB41-40

Page 7 of the Paradyne 3610 user manual — List of Figures
Page 7 · click to enlarge
Page 7

List of Figures

1-1. Central Office (CO) Power Unit with One Power Module 1-3 1-2. Central Office (CO) Power Unit with Two Power Modules 1-3 2-1. Installing the Optional Second Power Module 2-5 2-2. Option Straps (S1 through S5) on the CO Power Unit’s Backplane 2-6 2-3. CO Power Unit Installation 2-9 2-4. COMSPHERE 3000 Series Carrier (Rear) 2-10 2-5. Using One Power Source and One Input Power Cable for Basic (shown) or Redundant Mode 2-11 2-6. Using Two Separate Power Sources for Independent Mode or Redundant Mode 2-13 . . 2-7. Using One Power Source and Two Input Power Cables for Independent Mode or Redundant Mode 2-14 2-8. Installing the SDCP 2-15 2-9. Connecting an NMS Adapter Cable to a Modular 3611 DSU When the DTE Interface is EIA-232 2-18 2-10. Connecting an NMS Adapter Cable to a Modular 3611 DSU When the DTE Interface is V.35 2-19 2-11. Air Filter Brackets Installation 2-21 3-1. LED Status Indicators 3-1 3-2. Replacing a Power Module 3-3 A-1. CO Power Unit (Rear) A-2 A-2. Connector Housing and Contact A-3 A-3. NMS Adapter Cable (Feature Number 3000-F2-510) A-6

iii 3000-A2-GB41-40 May 1998

Figure Page

Page 8 of the Paradyne 3610 user manual — List of Tables
Page 8 · click to enlarge
Page 8

List of Tables

1-1 Technical Specifications for Central Office (CO) Power Unit 1-4 2-1 Maximum Ambient Temperatures Permitted 2-2 2-2 Settings for Basic Mode 2-6 2-3 Settings for Independent Mode 2-7 2-4 Settings for Redundant Mode Using a Single –48 Vdc Power Source and a Single Input Power Cable 2-7 2-5 Settings for Redundant Mode with Either a Single Power Source and Two Input Power Cables, or Two Separate Power Sources and Two Input Power Cables 2-7 2-6 Jumper Settings 2-17 A-1 Pin Assignments of the DC Inputs A-2 A-2 AMP Part Numbers A-3 A-3 Pin Assignments for the CO Alarm System Outputs A-4 A-4 Pin Assignments for the NMS Adapter Cable A-5

iv May 1998 3000-A2-GB41-40

Table Page

Page 9 of the Paradyne 3610 user manual — Related Documents
Page 9 · click to enlarge
Page 9

Preface

Objectives and Reader Assumptions

Chapter 3 describes the status indicators on the faceplate of the power module. It also provides troubleshooting guidelines and replacement instructions for the power module, and a preventive maintenance schedule for the optional air filter.

This guide contains installation information for the COMSPHERE –48 Vdc Central Office (CO) Power Unit which is designed to be used with COMSPHERE 3000 Series Carriers.

Appendix A contains interface connector pin assignment information.

The Glossary provides definitions for acronyms and product-specific terms used in this guide.

It is assumed that you are familiar with the functional operation of data equipment, digital network services, data service units (DSUs), dial/lease modems, T1 channel service units (CSUs) and T1 data service units/channel service units (DSU/CSUs).

The Index lists key terms, acronyms, concepts, and sections in alphaorder.

Related Documents

Abstract

3000-A2-GA31 COMSPHERE 3000 Series Carrier Installation Manual

Chapter 1 provides descriptive information about the –48 Vdc CO Power Unit.

Contact your sales or service representative to order additional product documentation.

Chapter 2 provides installation consideration information and procedures for installing an optional second power module, setting the option straps, installing the –48 Vdc CO Power Unit, providing power to the power unit, installing a Shared Diagnostic Control Panel (SDCP), connecting to a CO Alarm System or a COMSPHERE 6800 Series Network Management System (NMS), and installing an optional air filter and brackets.

Paradyne documents are also available on the World Wide Web at:

http://www.paradyne.com

Select Service & Support –> Technical Manuals

v 3000-A2-GB41–40 May 1998

Page 10 of the Paradyne 3610 user manual — Preface
Page 10 · click to enlarge
Page 10

vi May 1998 3000-A2-GB41-40

Page 11 of the Paradyne 3610 user manual — Overview
Page 11 · click to enlarge
Page 11

Introduction

Overview 1-1 Feature 1-2 Technical Specifications. 1-4 Equipment Warranty and Support 1-5

Overview

  • Alarm cables and NMS adapter cable, if needed. These components are used to connect the CO Power Unit to a CO alarm system and/or a COMSPHERE 6800 Series Network Management System (NMS) through a Modular 3611 Data Service Unit (DSU).

The COMSPHERE –48 Vdc Central Office (CO) Power Unit is designed to provide low voltage dc power to any data communication equipment (DCE) operating in a COMSPHERE 3000 Series Carrier.

The –48 Vdc CO Power Unit (hereafter referred to as the CO Power Unit) consists of the following components:

(A Modular 3611 DSU has a row of contacts on the rear edge of the circuit card and is shipped with a rear connector plate. The rear connector plate allows the removal of a Modular 3611 DSU from the front of the carrier without first disconnecting the DTE cables at the rear of the carrier. The NMS adapter cable is only compatible with the Modular 3611 DSU. For more information on the Modular 3611 DSU, see the COMSPHERE 3600 Series Data Service Units, Models 3610 and 3611, Operator’s Guide.)

  • One CO power tray with mounted backplane
  • One power module
  • Two backplane connector cable assemblies
  • Two air filter brackets
  • One installation kit which includes the following:

The total number of components required depends upon your configuration. The ACCULINK 3151 CSUs and 3161 DSU/CSUs do not support forwarding of CO Power Unit alarms to a 6800 Series NMS.

— Two dc input connector housings and six

contacts for the customer-supplied dc input cable

— Four air filter bracket screws

The CO Power Unit can send alarms to a CO alarm system and a 6800 Series NMS simultaneously. To connect to a CO alarm system, you need one customer-supplied alarm cable for each power module. To forward alarms to a 6800 Series NMS, you need one Modular 3611 DSU (configured to forward alarms to a 6800 Series NMS) and one NMS adapter cable. You can also use a non-modular Model 3611 DSU, but you must build your own cable. This guide provides information on forwarding alarms to a 6800 Series NMS via a Modular 3611 DSU, but reminds you that a non-modular Model 3611 DSU can also be used.

— Two nylon cable ties

You must supply the following related components:

  • A second power module, if desired.
  • One or two –48V power input cables. The required number of input cables depends upon your configuration.
  • One air filter, if needed.
Page 12 of the Paradyne 3610 user manual — Features
Page 12 · click to enlarge
Page 12

— Redundant mode – the mode in which two

power modules supply power to the entire carrier. If one power module fails, the remaining power module assumes the full load of the carrier. To operate in this mode of operation, you must install an optional second power module in the CO Power Unit.

Customer-supplied cable assemblies must comply with items 5 and 6 of the Important Safety Instructions at the front of this guide.

— Independent mode – the mode in which each

of the two power modules supplies power to one-half of the carrier. To operate in this mode of operation, you must install an optional second power module in the CO Power Unit.

For more information on the alarm cables and NMS adapter cable, see Appendix A of this guide.

Part numbers for the CO Power Unit and its related components are listed in Appendix B of this guide.

  • Provides forced air cooling for the carrier via a –48 Vdc fan in the power module.
  • Provides an optional air filter which prevents dust from entering the CO Power Unit and the COMSPHERE 3000 Series Carrier.

Features

The CO Power Unit provides the following features:

  • Detects power module and fan failures by monitoring the power output levels and the fan’s low-speed sensor for proper operation of the power module. When a failure occurs, an alarm indication light appears on the power module’s faceplate.
  • Enables DCEs supported by the COMSPHERE 3000 Series Carrier to operate in a –48 Vdc central office environment.
  • Provides the following three modes of operation:

— Basic mode – the mode in which the single

  • Sends power failure and/or fan failure alarms to a CO alarm system and/or a 6800 Series NMS via a Modular 3611 DSU.

power module supplies power to the entire carrier. This mode of operation is the only mode available for the CO Power Unit with one power module.

Figure 1-1 illustrates the CO Power Unit with one power module in the left side of the CO power tray. In Basic mode, the single power module can be installed in either the left or right side of the CO power tray. Figure 1-2 illustrates the CO Power Unit with two power modules.

Page 13 of the Paradyne 3610 user manual — Introduction
Page 13 · click to enlarge
Page 13
Paradyne 3610 — Introduction diagram (page 13)
Fig. 1 · Introduction

Figure 1-1. Central Office (CO) Power Unit with One Power Module

Paradyne 3610 — Introduction diagram (page 13)
Fig. 2 · Introduction

Tray Power Module Handle

Figure 1-2. Central Office (CO) Power Unit with Two Power Modules

Show 10 more labels / short text on this page
Introduction · Power Module Handle · Captive Screws · Tray Captive Screws · CO Power · CO Power Unit · Backplane · Power Module Handle · Right Power Module · 98-13694-01
Page 14 of the Paradyne 3610 user manual — PHYSICAL DIMENSIONS
Page 14 · click to enlarge
Page 14

Technical Specifications

Technical specifications for the CO Power Unit (which includes one power module) are listed in Table 1-1.

(1 of 2) Technical Specifications for Central Office (CO) Power Unit

ENVIRONMENT

32°F (0°C) to 122°F (50°C) (See the Installation Considerations section in Chapter 2 for additional operating temperature limits.)

5% to 95% (noncondensing)

–4°F (–20°C) to 158 5F (70°C)

Withstands normal shipping and handling

POWER REQUIREMENTS

CO Power Unit (with 16 fully equipped 3611 DSUs in the carrier)

–60 Vdc to –40 Vdc (4.5 amps maximum)

CO Power Unit (with 16 fully equipped 3151 CSUs in the carrier)

–60 Vdc to –40 Vdc (2.3 amps maximum)

CO Power Unit (with 16 fully equipped 3161 DSU/CSUs in the carrier)

–60 Vdc to –40 Vdc (4.8 amps maximum)

HEAT DISSIPATION (MAX.) AT –48 Vdc

CO Power Unit (with 16 fully equipped cards in the carrier)

160 watts (CO Power Unit efficiency is approximately 76%)

PHYSICAL DIMENSIONS

2.4 inches ( 6.2 cm)

Height (including air filter brackets)

3.0 inches ( 7.7 cm)

16.9 inches (43.3 cm)

13.5 inches (34.6 cm)

2.4 inches ( 6.2 cm)

8.5 inches (21.8 cm)

11.7 inches (30.0 cm)

0.5 inches ( 1.3 cm)

14.2 inches (36.4 cm)

5.5 inches (14.1 cm)

Show 18 more labels / short text on this page
Table 1-1 · Technical Specifications Criteria · Operating Temperature · Relative Humidity · Storage Temperature · Shock and Vibration · CO Power Unit · Height · Width · Depth · Power Module · Height · Width · Depth · Air Filter · Height · Width · Depth
Page 15 of the Paradyne 3610 user manual — Equipment Warranty and Support
Page 15 · click to enlarge
Page 15

(2 of 2) Technical Specifications for Central Office (CO) Power Unit

WEIGHT

CO Power Unit (includes one power module)

10.6 pounds (4.8 kg)

CO Power Unit (includes two power modules)

15.8 pounds ( 7.2 kg)

5.2 pounds ( 2.4 kg)

0.2 pounds ( 0.1 kg)

CENTRAL OFFICE (CO) ALARM RELAY CONTACTS

0.1 amp maximum at 70 Vdc maximum

APPROVALS

Underwriters Laboratories, Inc. (UL) Recognized Component

Recognized component as part of 3000 Series Carrier, UL 1950

Canadian Standards Association (CSA) Certified Component

Certified Component as part of 3000 Series Carrier, CSA 22.2 No. 950

Equipment Warranty and Support

If you experience trouble with this equipment, please contact your sales or service representative (as appropriate) for repair or warranty information. If the product needs to be returned to the company service center for repair, contact them directly for return instructions using one of the following methods:

  • Via the Internet: Visit the Paradyne World Wide Web site at <a href="http://www.paradyne.com" rel="nofollow noopener" target="_blank">http://www.paradyne.com</a>
  • Via Telephone: Call our automated call system to receive current information via fax or to speak with a company representative.

— Within the U.S.A., call 1-800-870-2221

— Outside the U.S.A., call 727-530-2340

If the trouble is causing harm to the telephone network, the telephone company may request that you remove the equipment from the network until the problem is resolved.

Show 5 more labels / short text on this page
Introduction · Table 1-1 · Technical Specifications Criteria · Power Module · Air Filter
Page 16 of the Paradyne 3610 user manual — Introduction
Page 16 · click to enlarge
Page 16

This page intentionally left blank.

Page 17 of the Paradyne 3610 user manual — Basic Mode of Operation
Page 17 · click to enlarge
Page 17

Installation

Overview 2-1 Installation Considerations 2-1 Basic Mode of Operation 2-1 Independent Mode of Operation 2-2 Redundant Mode of Operation 2-3 Alarm Forwarding to a 6800 Series NMS 2-3 CO Power Unit Installation 2-4 Installing the Optional Second Power Module 2-4 Setting the Option Straps 2-6 Installing the CO Power Unit 2-9 Providing Power to a CO Power Unit 2-11 Installing an SDCP 2-16 Connecting the Alarm Contacts to a CO Alarm System 2-17 Connecting the Alarm Contacts to a 6800 Series NMS Via a Modular 3611 DSU 2-18 Air Filter and Brackets Installation (Optional) 2-21

Overview

In addition, if you want to forward alarms to a 6800 Series Network Management System (NMS), you must connect the CO Power Unit to the external leads of a Modular 3611 DSU. Model 3151 CSUs and Model 3161 DSU/CSUs do not support forwarding of CO Power Unit alarms to a 6800 Series NMS. To access these external leads, use an NMS adapter cable to connect the external leads of a Modular 3611 DSU to the CO Power Unit.

The CO Power Unit consists of one power module in a CO power tray. When installed, the CO Power Unit provides low voltage dc power to the DCEs in the carrier. This chapter provides information on how to install the CO Power Unit into a COMSPHERE 3000 Series Carrier.

This section describes the three modes of operation and provides information you need to know in order to send alarms to a 6800 Series NMS.

Installation Considerations

The CO Power Unit is shipped with one power module and operates in Basic mode. With an optional second power module the CO Power Unit can be configured to operate in either Independent mode or Redundant mode. If you order a second power module for your CO Power Unit, you must determine the mode in which you wish to operate before installing the CO Power Unit.

Basic Mode of Operation

The CO Power Unit with one power module operates in Basic mode. In this mode of operation, the single power module supplies power to the entire carrier.

When stacking multiple carriers equipped with CO Power Units with single power modules, you must install the power module in each of the CO Power Units in alternating sequence (that is, left side, right side, left side, right side, etc.) for proper cooling. For example, if the CO Power Unit in the bottom carrier has its power module installed in the left side of the CO power tray, the carrier

The CO Power Unit installation procedure must be performed by a qualified service personnel.

Page 18 of the Paradyne 3610 user manual — NOTES:
Page 18 · click to enlarge
Page 18

directly above the bottom carrier should have its power module installed in the right side of its CO power tray. Then, the next carrier directly above should have its power module installed in the left side of its CO power tray, and so on for the remainder of the carriers in the cabinet. For information on removing and installing a power module, see the Power Module Replacement Instructions section in Chapter 3.

failed power module until a replacement is available. To replace a power module, see the Power Module Replacement Instructions section in Chapter 3 of this guide.

When the power modules are configured for Independent mode of operation, up to six carriers can be mounted in a cabinet. The maximum ambient temperature is 50°C.

With the power modules placed in alternating sequence, the maximum operating ambient temperatures listed in Table 2-1 are permitted.

The –48 Vdc input can be provided in one of two powering options:

  • Using two separate –48 Vdc power sources and two input power cables.

Independent Mode of Operation

  • Using one –48 Vdc power source and two input power cables.

In the Independent mode of operation, the left power module (as viewed from the front of the carrier) powers Slots 1 through 8 of the carrier and the right power module powers Slots 9 through 16 of the carrier. The Shared Diagnostic Unit (SDU), contained in Slot 0, is powered by both power modules. If a power module fails, only the service to that side of the carrier is disrupted. The other side of the carrier is unaffected. Do not remove a

For maximum reliability, use the first option. For more information on these powering options, see the Providing Power to a CO Power Unit section.

To change the mode of operation, see the Setting the Option Straps section.

Table 2-1 Maximum Ambient Temperatures Permitted

Allowable Number of Stacked COMSPHERE 3000 Series

Carriers in a Cabinet Maximum

Ambient Temperature 3551 and 3611 DSUs without DBMs, 3511 DSUs, 3151 and CSUs2

3551, 3611, and 3616 DSUs with DBMs and

3811 Modems2 3161 DSU/CSUs1

122°F (50°C) 4 2 See Note 4

113°F (45°C) 5 3 13, 2

104°F (40°C) 6 4 3

95°F (35°C) 6 5 4

86°F (30°C) 6 5 5

77°F (25°C) 6 6 6

NOTES:

1 These operating ambient temperatures can be increased by 5°C by placing 3161 DSU/CSUs in cooler slots (2, 3, 4, 5, 10, 11, 12, 13), or by leaving a slot empty next to each 3161 DSU/CSU. 2 Use the strictest cooling requirements when there is a mixture of units installed.

3 Requires a power module on each side, otherwise the ambient temperature must be restricted to 35°C. 4 A single carrier, equipped with two power modules, can operate at 50°C provided the cooler slots (2, 3, 4, 5, 10, 11, 12, 13) are used.

Maximum

Page 19 of the Paradyne 3610 user manual — Redundant Mode of Operation
Page 19 · click to enlarge
Page 19

Redundant Mode of Operation

Alarm Forwarding to a 6800 Series NMS

In the Redundant mode of operation, both power modules share the load (that is, both modules supply power to all slots in the carrier). If one power module fails, the remaining power module assumes the full load of the carrier. Operation of the CO Power Unit continues, but it is recommended that you replace the failed power module as soon as possible. Do not remove a failed power module until a replacement is available. For instructions on how to replace a power module, see the Power Module Replacement Instructions section in Chapter 3 of this guide.

In order to send power module failure and fan failure alarm signals to a 6800 Series NMS, you must have a Modular 3611 DSU (configured to forward alarms to a 6800 Series NMS) and an NMS adapter cable. (Model 3151 CSUs and Model 3161 DSU/CSUs do not support this feature.) When these components are properly configured and alarm conditions occur, alarm signals are sent to the 3611 DSU and then routed to the 6800 Series NMS where an alarm event is reported to the NMS operator. (Remember, you can also use a nonmodular Model 3611 DSU, but you must build your own adapter cable to connect Pin 9 of the EIA 25-pin male connector to Pin 6 of the modular plug for the +12 Vdc source, Pin 19 of the EIA 25-pin male connector to Pin 2 of the modular plug for the fan alarm, and Pin 23 of the EIA 25-pin male connector to Pin 1 of the modular plug for the power alarm).

When the power modules are configured for Redundant mode of operation, up to four carriers can be mounted in a cabinet and meet the stated maximum temperature operating limits of 50°C. The reduction of carriers per cabinet is necessary to compensate for the loss of cooling capability if one of the power modules fails. If the operating temperature limit in the room is less than 45°C, then up to five carriers can be mounted in a cabinet. If the operating temperature limit in the room is less than 40°C, then up to six carriers can be mounted in a cabinet.

For the Basic or Independent mode of operation, the Modular 3611 DSU (configured for alarm forwarding) must be installed in a different carrier in the cabinet (that is, a carrier in the cabinet other than the one you want to manage). This arrangement enables you to send alarms to the 6800 Series NMS even if one of the CO Power Unit’s power modules fails. If the Modular 3611 DSU is installed in the same carrier, a power module failure will disrupt alarm forwarding to the 6800 Series NMS. In the Independent mode of operation, a power module failure disrupts service to one-half of the carrier. If that half of the carrier contains the Modular 3611 DSU (configured for alarm forwarding), then the DSU is inoperable and is unable to forward alarms.

The –48 Vdc input can be provided in one of three power options:

  • Using one –48 Vdc power source and one fused input power cable.
  • Using one –48 Vdc power source and two fused input power cables.
  • Using two separate –48 Vdc power sources and two fused input power cables.

The second power option is more reliable than the first power option because it protects the CO Power Unit against a short circuit failure in the input circuit of one power module from interrupting the power source to the other power module. However, the third power option is the most reliable for the Redundant mode of operation because it protects against short circuit and input power failures. For more information on these powering options, see the Providing Power to a CO Power Unit section. To change the mode of operation, see the Setting the Option Straps section.

In the Redundant mode of operation, you may want to install the Modular 3611 DSU (configured for alarm forwarding) in a different carrier in the cabinet in the unlikely event of a double power module failure.

For information on connecting the CO Power Unit to a 6800 Series NMS, see the Connecting the Alarm Contacts to a 6800 Series NMS section.

Installation

Page 20 of the Paradyne 3610 user manual — Installing the Optional Second Power Module
Page 20 · click to enlarge
Page 20

CO Power Unit Installation

4. Install the Shared Diagnostic Control Panel (SDCP) on the carrier in which you installed the CO Power Unit, if desired. (See the Installing an SDCP section.)

The CO Power Unit is installed at the bottom of the carrier. You will need a large, flat-blade screwdriver to install the CO Power Unit and a medium, flat-blade screwdriver to set the option straps.

5. Connect the alarm contacts for the CO Power Unit to a CO alarm system and/or a Modular 3611 DSU, if desired. (See the Connecting the Alarm Contacts to a CO Alarm System section or the Connecting the Alarm Contacts to a 6800 Series NMS Via a Modular 3611 DSU section.)

If you plan to use two power modules in your CO Power Unit, you must install the second power module before proceeding to Step 1. (See the Installing the Optional Second Power Module section.)

Steps 4 and 5 are optional.

Installing the Optional Second Power Module

You can order a second power module for your CO Power Unit. This additional power module allows you to choose between two modes of operation: Redundant or Independent. You must install the optional second power module into the CO power tray before installing the CO Power Unit into the carrier.

The following is an overview of the CO Power Unit installation procedure:

1. Set the option straps on the CO Power Unit’s backplane to the desired mode of operation. (See the Setting the Option Straps section.)

To install the optional second power module:

If your CO Power Unit has a single power module, you do not need to set the option straps. The option straps are factory set for the Basic mode of operation. However, you should compare the option strap setting on backplane to the strap settings listed in Table 2-2 in the Setting the Option Straps section to ensure correct settings.

1. Remove the coverplate by loosening the two captive screws on the bottom of the coverplate.
2. Place the second power module in the card guides on the right side of the CO power tray (as viewed from the front of the tray) and then slide power module to the rear of tray. See Figure 2-1 .
3. Tighten the two captive screws on the bottom of the power module’s faceplate.
2. Install the CO Power Unit into the carrier. (See the Installing the CO Power Unit section.)
3. Provide power to the CO Power Unit. (See the Providing Power to a CO Power Unit section.)

Procedure · Procedure

Page 21 of the Paradyne 3610 user manual — Installation
Page 21 · click to enlarge
Page 21
Paradyne 3610 — Installation diagram (page 21)
Fig. 3 · Installation

Figure 2-1. Installing the Optional Second Power Module

Installation

Page 22 of the Paradyne 3610 user manual — S1
Page 22 · click to enlarge
Page 22

Setting the Option Straps

Table 2-2 Settings for Basic Mode

The option straps are screw switches that are set by raising (loosening) or lowering (tightening) the screw to break or make the contact. There are five option straps, S1 through S5, on the CO Power Unit’s backplane (see Figure 2-2).

Paradyne 3610 — Setting the Option Straps diagram (page 22)
Fig. 4 · Setting the Option Straps

Older power modules have straps labeled S1 and S2. These should always be in the raised position.

To set the option straps for Basic mode of operation:

1. Tighten the screws on all five straps (S1 through S5) on the CO Power Unit’s backplane. Make sure that the screws are securely touching the contacts, but do not screw the straps too tight because doing so can damage the equipment.

If you want to operate in the Basic mode, you must use one –48 Vdc power source and configure the option straps as shown in Table 2-2.

S1

Paradyne 3610 — S1 diagram (page 22)
Fig. 5

Figure 2-2. Option Straps (S1 through S5) on the CO Power Unit’s Backplane

Procedure · Basic Mode

Page 23 of the Paradyne 3610 user manual — Installation
Page 23 · click to enlarge
Page 23

that the screws are securely touching the contacts, but do not screw the straps too tight because doing so can damage the equipment.

If you want to operate in Independent mode and you plan to use either one or two –48 Vdc power sources, configure the option straps as shown in Table 2-3.

Redundant Mode — Two Cables

Table 2-3 Settings for Independent Mode

If you want to operate in Redundant mode and you plan to use either a single –48 Vdc power source and two input power cables or two separate –48 Vdc power sources and two input power cables, configure the option straps as shown in Table 2-5.

Table 2-5 Settings for Redundant Mode with Either

a Single Power Source and Two Input

Power Cables, or Two Separate Power Sources and Two Input Power Cables

To set the option straps for Independent mode of operation:

1. Loosen the screws on all five straps (S1 through S5) on the CO Power Unit’s backplane so that the screws are not touching the contacts. (Two complete turns will suffice.)

To set the option straps for Redundant mode of operation with either a single power source and two input power cables, or two separate power sources and two input power cables:

Redundant Mode — One Source, One Cable

If you want to operate in Redundant mode and you plan to use a single –48 Vdc power source and a single input power cable, configure the option straps as shown in Table 2-4.

1. Tighten the screws on the S1, S2, and S3 straps on the CO Power Unit’s backplane. Do not screw the straps too tight because doing so can damage the equipment. Make sure that the screws are securely touching the contacts. Then loosen the screws on the S4 and S5 straps. (Two complete turns will suffice.)

Table 2-4 Settings for Redundant Mode Using a Single –48 Vdc Power Source

and a Single Input Power Cable

In either Independent or Redundant mode of operation, the S4 and S5 straps on the backplane must be raised (loosened) when two separate –48 Vdc power sources are used to prevent operational problems and voltage incompatibilities.

To set the option straps for Redundant mode of operation using a single –48 Vdc power source and a single input power cable:

1. Tighten the screws on all five straps (S1 through S5) on the CO Power Unit’s backplane. Make sure
Show 20 more labels / short text on this page
Installation · Independent Mode · S1 Raised · S2 Raised · S3 Raised · S4 Raised · S5 Raised · S1 Lowered · S2 Lowered · Procedure · S3 Lowered · S4 Raised · S5 Raised · Procedure · S1 Lowered · S2 Lowered · S3 Lowered · S4 Lowered · S5 Lowered · Procedure
Page 24 of the Paradyne 3610 user manual — Installing the CO Power Unit
Page 24 · click to enlarge
Page 24

Installing the CO Power Unit

To install the CO Power Unit:

If installing an SDCP in the carrier in which you plan to install a CO Power Unit, be sure to install the SDCP ribbon cable that provides power to the SDCP before installing the CO Power Unit. (For instructions on how to install the SDCP ribbon cable, see the SDCP Ribbon Cable Installation section in the COMSPHERE 3000 Series Carrier Installation Manual.)

1. If an air filter is desired, follow the procedure in the Air Filter and Brackets Installation section later in this chapter. Then, return to this procedure and proceed to the next step.
2. At the front of the carrier, place the CO Power Unit on the flanges at the bottom of the carrier (see Figure 2-3 ). Slide the CO Power Unit into place against the rear rail of the enclosure, guiding the ground strap through the opening in the carrier’s backplane.

After installing the CO Power Unit, you can then install the SDCP. (For instructions on how to install the SDCP, see Installing the SDCP section later in this chapter.)

If an SDCP ribbon cable has been installed, hold the ribbon cable to the left of the CO Power Unit when sliding the power unit into place against the rear rail of the enclosure. Place the ribbon cable between the power module and the side of the CO power tray (see Figure 2-3). The SDCP ribbon cable is connected to the back of the SDCP after the CO Power Unit is installed.

Make a ground connection before installing the CO Power Unit. Locate the ground symbol label at the rear of the CO Power Unit. Remove the ground screw next to the label. Attach one end of a ground strap (minimum 18 AWG) and securely fasten the ground screw. Secure the other end of the ground strap to the nearest solid frame ground point (see Step 2).

Connect the ground strap to the nearest solid frame ground point (e.g., the rails on which the carrier is mounted). Do not connect the ground strap to the carrier.

Procedure

Page 25 of the Paradyne 3610 user manual — Installation
Page 25 · click to enlarge
Page 25
Paradyne 3610 — Installation diagram (page 25)
Fig. 6 · Installation

Tray and Power Module

Figure 2-3. CO Power Unit Installation

3. At the rear of the carrier, use a large flat-blade screwdriver to engage and tighten the two captive screws that fasten the CO Power Unit to the carrier.
4. Plug one backplane connector cable assembly from the P20 connector on the carrier’s backplane to the P6 connector on the CO Power Unit’s backplane. Then, plug the second backplane connector cable assembly from the P19 connector on the carrier’s backplane to the P3 connector on the CO Power Unit’s backplane. The backplane connector cable assemblies enable a backplane-to-backplane connection which provides low voltage dc power to the carrier (see Figure 2-4 ).
Show 4 more labels / short text on this page
Installation · Built-in Retainer · Clips · SDCP Ribbon
Page 26 of the Paradyne 3610 user manual — Providing Power to a CO Power Unit
Page 26 · click to enlarge
Page 26
Paradyne 3610 — Installation diagram (page 26)
Fig. 7 · Installation

BACKPLANE CONNECTOR

CABLE ASSEMBLIES

NETWORK MANAGEMENT

CONNECTOR

ALARM B ALARM A

Figure 2-4. COMSPHERE 3000 Series Carrier (Rear)

Providing Power to a CO Power Unit

(AMP part number 350550-1) to attach the connector to your –48 Vdc power input cable.

After the CO Power Unit installation procedure is completed, you must provide power to the unit. There are a number of powering options available depending upon your configuration.

(The contacts are crimp type and are intended for use with 20 AWG through 14 AWG wire with a maximum insulation diameter of .130 inches. For additional information, see Appendix A of this guide.)

The option strap settings are factory set for the Basic mode of operation.

2. Provide external fusing, if desired. (The fuse shown in Figure 2-5 is optional as per your requirements.) The optional fuse should have a rating of 6 amperes, 250 volts, and be a fast-acting type. Use a fuse similar to Littlefuse #312006.

To provide power to the CO Power Unit operating in Basic mode:

3. Plug the input power cable to either the –48VDC A connector or the –48VDC B connector. See Figure 2-5 . (The option strap settings for this power option are listed in Table 2-2 .)
1. Use one connector housing (AMP part number 1-480698-0) and two crimp-type contacts

497-13673-01 · Procedure

Page 27 of the Paradyne 3610 user manual — Installation
Page 27 · click to enlarge
Page 27
Paradyne 3610 — Installation diagram (page 27)
Fig. 8 · Installation

Figure 2-5. Using One Power Source and One Input Power Cable for Basic (shown) or Redundant Mode

Installation · 496-13755-01

Page 28 of the Paradyne 3610 user manual — Installation
Page 28 · click to enlarge
Page 28

If you have two input power cables and one –48 Vdc power source, plug one input power cable into the –48VDC A connector and the second input power cable into the –48VDC B connector. Then, connect both power cables into the same –48 Vdc power source. See Figure 2-7. (The option strap settings for this power option are listed in Table 2-3.)

The option straps must be set for the Independent mode of operation. For the correct settings, see the Setting the Option Straps section earlier in this guide.

To provide power to the CO Power Unit operating in Independent mode:

The appropriate option strap settings must be set. For the correct settings, see the Setting the Option Straps section earlier in this guide.

1. Use the two connector housings (AMP part number 1-480698-0) and four crimp-type contacts (AMP part number 350550-1) to attach the connector(s) to your –48 Vdc power input cable(s). Note that you need a hand crimping tool (AMP part number 90296-2 or equivalent) to build the connector(s).

To provide power to the CO Power Unit operating in the Redundant mode:

(The contacts are crimp type and are intended for use with 20 AWG through 14 AWG wire with a maximum insulation diameter of .130 inches. For additional information, see Appendix A of this guide.)

1. Use the two connector housings (AMP part number 1-480698-0) and four crimp-type contacts (AMP part number 350550-1) to attach the connector(s) to your –48 Vdc power input cable(s). Note that you need a hand crimping tool (AMP part number 90296-2 or equivalent) to build the connector(s).
2. Provide external fusing, if desired. (The fuses shown in Figures 2-6 and 2-7 are optional as per your requirements.) An optional external fuse should have a rating of 6 amperes, 250 volts and be a fast-acting type. Use a fuse similar to Littlefuse #312006.

(The contacts are crimp type and are intended for use with 20 AWG through 14 AWG wire with a maximum insulation diameter of .130 inches. For additional information, see Appendix A of this guide.)

3. If you have two input power cables and two separate –48 Vdc power sources (e.g., Source A and Source B), plug one input power cable from one of your –48 Vdc power sources (e.g., Source A) to the –48VDC A connector to provide power to the left side of the carrier. Plug the other input power cable from a different –48 Vdc power source (e.g., Source B) to the –48VDC B connector to provide power to the right side of the carrier. See Figure 2-6. (The option strap settings for this power option are listed in Table 2-3.)

2. Provide external fusing, if desired. (The fuses shown in Figures 2-5 , 2-6 , and 2-7 are optional as per your requirements.) An optional fuse should have a rating of 6 amperes, 250 volts and be a fast-acting type. Use a fuse similar to Littlefuse #312006.

Procedure · Procedure

Page 29 of the Paradyne 3610 user manual — Installation
Page 29 · click to enlarge
Page 29
3. If you have one input power cable and one –48 Vdc power source, plug the input power cable to either the –48VDC A connector or the –48VDC B connector. See Figure 2-5 . (The option strap settings for this power option are listed in Table 2-4 .)

(The option strap settings for this power option are listed in Table 2-5.)

If you have two power cables and two separate –48 Vdc power sources (e.g., Source A and Source B), plug one input cable from a –48 Vdc power source (e.g., Source A) to the –48VDC A connector. Plug an input power cable from a different –48 Vdc power source (e.g., Source B) to the –48VDC B connector. See Figure 2-6. (The option strap settings for this power option are listed in Table 2-5.)

If you have two input power cables and one –48 Vdc power source, plug one input power cable to the –48VDC A connector and the second input power cable to the –48VDC B connector. Then, connect both input power cables to your single –48 Vdc power source. See Figure 2-7.

Paradyne 3610 — Installation diagram (page 29)
Fig. 9 · Installation

Figure 2-6. Using Two Separate Power Sources for Independent Mode or Redundant Mode

Installation · 496-13675-01

Page 30 of the Paradyne 3610 user manual — Installation
Page 30 · click to enlarge
Page 30
Paradyne 3610 — Installation diagram (page 30)
Fig. 10 · Installation

Figure 2-7. Using One Power Source and Two Input Power Cables for

Independent Mode or Redundant Mode

496-13676-01

Page 31 of the Paradyne 3610 user manual — TOP CAPTIVE
Page 31 · click to enlarge
Page 31

Installing an SDCP

If you want to mount a shared Diagnostic Control Panel (SDCP) on the carrier and the SDCP ribbon cable is installed (refer to Figure 2-8):

If you want to mount an SDCP and the SDCP ribbon cable is not installed, remove the CO Power Unit from the carrier and follow the instructions in the SDCP Ribbon Cable Installation section in the COMSPHERE 3000 Series Carrier Installation Manual.

1. Raise the carrier 1.5 inches above the carrier below it.
Paradyne 3610 — Installing an SDCP diagram (page 31)
Fig. 11 · Installing an SDCP

(In a Paradyne COMSPHERE 72-inch cabinet (4000-B2-201), if you mount an SDCP onto a carrier operating with a CO Power Unit, then only five carriers can be installed in the cabinet instead of the usual six.)

This procedure is only used when installing an SDCP onto a carrier operating with a CO Power Unit. All other carriers use the standard SDCP installation procedure as described in the Shared Diagnostic Control Panel (SDCP) Installation section in the COMSPHERE 3000 Series Carrier Installation Manual.

2. Remove the power module (the left power module if there are two power modules in the CO Power Unit) by loosening the two captive screws on the front of the power module. Hold onto the power module handle and slide the power module out. Then, remove the handle on the power module by using a small Phillips-head screwdriver to loosen the screws behind the power module’s faceplate.
Paradyne 3610 — Installing an SDCP diagram (page 31)
Fig. 12 · Installing an SDCP

TOP CAPTIVE

CONTROL PANEL

(SDCP)

SCREW

Figure 2-8. Installing the SDCP

Installation · Procedure · 497-13757-02

Page 32 of the Paradyne 3610 user manual — Connecting the Alarm Contacts to a CO Alarm System
Page 32 · click to enlarge
Page 32
3. Secure a nylon cable tie in the handle mounting holes.

The CO alarm cables and mating connectors are customer-supplied components.

4. Place the power module in the card guides and slide the power module to the rear of the carrier. When sliding the left power module into the CO Power Unit, hold the SDCP ribbon cable to the left of the power module. Then, tighten the two captive screws on the front of the power module (see Figure 2-3 ).

To connect the CO Power Unit to a CO alarm system:

5. If the CO Power Unit has an optional second power module, repeat Steps 2 through 4 for the right power module and proceed to the next step.
1. At the rear of the carrier, locate the cable connectors labeled Alarm A and Alarm B (see Figure 2-4 ).
6. Attach the SDCP ribbon cable to the back of the SDCP as shown in Figure 2-8 .
2. To send alarm signals from the left power module to a CO alarm system, plug a customer-supplied mating connector (AMP part number 103957-4) and cable into the Alarm A connector. To send alarm signals from the right power module, if the CO Power Unit has two power modules, to a CO alarm system, plug a customer-supplied mating connector (AMP part number 103957-4) and cable into the Alarm B connector.
7. Mount the SDCP to the front of the carrier by securing the two top captive screws of the SDCP into the two bottom screw holes of the carrier.

Connecting the Alarm Contacts to a CO Alarm System

The CO Power Unit monitors the power output levels and the fan’s low-speed sensor for proper operation of the power module. Both major (power failure) and minor (fan failure) alarms can be sent to a CO alarm system. A major alarm is sent to a CO alarm system if a power failure occurs in either the –48V input or low voltage output. A minor alarm is sent to a CO alarm system if a fan failure occurs or if the fan speed drops below 1900 rpm. After the CO Power unit is installed, you can connect the power unit to a CO alarm system.

For pin assignments of the Alarm A and Alarm B connectors, see Appendix A of this guide.

Procedure

Page 33 of the Paradyne 3610 user manual — Installation
Page 33 · click to enlarge
Page 33

Connecting the Alarm Contacts to a 6800 Series NMS Via a Modular 3611 DSU

After setting the jumpers, reinstall the Modular 3611 DSU in the carrier. Then, set the firmware configuration External Leads (Ext Leads, in the General branch) parameter as shown:

The CO Power Unit can also send alarms to a 6800 Series NMS using the external alarm functions of a Modular 3611 DSU. After the CO Power Unit is installed, connect the power unit to the external leads of a Modular 3611 DSU by using an NMS adapter cable.

Ext LeadsRPowr

Before you can forward CO alarms to the 6800 Series NMS via the external leads, you must configure the Modular 3611 DSU for alarm forwarding by setting the appropriate jumpers. To do this, remove the Modular 3611 DSU from the carrier and set Jumpers J20 and J21 (for Model 3611-B3) or Jumper E5 and Switch S1-2 (for Model 3611-B4) as shown in Table 2-6.

Remember, for Basic or Independent mode of operation, the Modular 3611 DSU (configured for alarm forwarding) must be installed in a different carrier (that is, a carrier in the cabinet other than the one you want to manage). This arrangement ensures that all alarm signals are forwarded even if power has disrupted service to the carrier. For Redundant mode of operation, you may want to install the Modular 3611 DSU in a different carrier in the unlikely event of a double power module failure.

Table 2-6 Jumper Settings

3611-B3 Jumper J20 Left

3611-B3 Jumper J21 Left

3611-B4 Jumper E5 Left

3611-B4 Switch S1-2 On

Show 7 more labels / short text on this page
Installation · Setting to Enable · Jumper or · –48 Vdc Alarm · Model · Switch · Monitoring
Page 34 of the Paradyne 3610 user manual — Installation
Page 34 · click to enlarge
Page 34

To connect the alarm contacts to the external leads of a Modular 3611 DSU (configured for alarm forwarding):

rear connector plate, remove the ferrite choke and the EIA-232 cable. Plug the DB25 male end of the NMS adapter cable into the top connector of the rear connector plate. Tighten the screws to hold the cable in place. Then, attach the ferrite choke to the NMS adapter cable. Plug the EIA-232 cable into the DB25 female end of the NMS adapter cable. Tighten the screws to hold the cable in place. See Figure 2-9.

1. At the rear of the carrier, plug the 6-wire modular plug end of the NMS adapter cable into the J1 connector (a 6-position modular jack) on the CO Power Unit’s backplane (see Figure 2-9 ).
2. If there is an EIA-232 cable on the top connector (labeled EIA232/V.24) of a Modular 3611 DSU’s
Paradyne 3610 — Installation diagram (page 34)
Fig. 13 · Installation

Figure 2-9. Connecting an NMS Adapter Cable to a Modular 3611 DSU

When the DTE Interface is EIA-232

Procedure

Page 35 of the Paradyne 3610 user manual — Installation
Page 35 · click to enlarge
Page 35
3. If there is a V.35 cable on the bottom connector, labeled V.35 (3600/3500), of a Modular 3611 DSU’s rear connector plate, then plug the DB25 male end of the NMS adapter cable into the top

connector of the rear connector plate. Note that the DB25 female end of the NMS adapter cable has no connection. See Figure 2-10.

Paradyne 3610 — Installation diagram (page 35)
Fig. 14 · Installation

Figure 2-10. Connecting an NMS Adapter Cable to a Modular 3611 DSU

When the DTE Interface is V.35

Installation

Page 36 of the Paradyne 3610 user manual — Air Filter and Brackets Installation (Optional)
Page 36 · click to enlarge
Page 36

Air Filter and Brackets Installation (Optional)

Keep in mind that the air filter brackets take up an additional 0.6 inches (1.5 cm) in height and if mounted on one of the carriers in the COMSPHERE 72-inch cabinet (4000-B2-201), then only five carriers can be installed in the cabinet instead of the usual six.

The air filter (part number 3000-F1-020) prevents dust from entering the carrier. It is an optional component and must be ordered separately. However, the air filter brackets and screws are supplied with the CO Power Unit.

To install the air filter and brackets:

Only the 3000-F1-020 air filter may be used. Under normal environmental conditions, you should inspect and/or replace the 3000-F1-020 air filter every three months.

1. Raise the carrier 0.6 inches from the bottom of the cabinet (or above the carrier below it).
2. Fasten the two identical brackets to the bottom of the CO power tray using the four #6 Phillips-head screws provided. See Figure 2-11 .

This section describes the procedure for installing the air filter and brackets. This procedure must be performed before installing the carrier into the cabinet.

3. Place the air filter with the grill-side face up on the guides of the brackets and slide the air filter in place.

If the carriers in the cabinet are stacked directly on top of each other, then only the bottom carrier in the cabinet needs an air filter.

If you were directed to this section during the CO Power Unit Installation procedure, then return to that procedure now.

Procedure

Page 37 of the Paradyne 3610 user manual — #6 PHILLIPS-HEAD
Page 37 · click to enlarge
Page 37

#6 PHILLIPS-HEAD

SCREWS

Paradyne 3610 — #6 PHILLIPS-HEAD diagram (page 37)
Fig. 15

Figure 2-11. Air Filter Brackets Installation

Installation

Page 38 of the Paradyne 3610 user manual — Installation
Page 38 · click to enlarge
Page 38

This page intentionally left blank.

Page 39 of the Paradyne 3610 user manual — Indicators and Controls
Page 39 · click to enlarge
Page 39

Troubleshooting and Maintenance

Overview 3-1 Indicators and Controls 3-1 Troubleshooting 3-2 Power Module Replacement Instructions 3-3 Preventive Maintenance 3-4

Overview

There are two LED status indicators (Figure 3-1) on the power module’s faceplate: the Power LED and the Fan Alarm LED. The Power LED provides the status of the power module. A green light indicates that the power module is operating properly. A red light indicates a power module failure. No light indicates that the CO Power Unit is not receiving input power. The Fan Alarm LED provides the status of the fan in the power module. If the Fan Alarm LED is not lit and the Power LED is green, the fan is operating properly. If the LED is yellow, it indicates either a fan failure or a fan speed below 1900 rpm.

This chapter describes the status indicators on the power module’s faceplate, provides troubleshooting guidelines and replacement instructions for the power module, and a preventive maintenance schedule for the optional air filter.

Indicators and Controls

The CO Power Unit detects power module and/or fan failures by monitoring the power output levels and the fan’s low-speed sensor for proper operation of the power module. When a failure occurs, an alarm indication light appears on the faceplate of the affected power module.

3000 DC Power Module

Figure 3-1. LED Status Indicators

Power · Fan Alarm · 491-13698

Page 40 of the Paradyne 3610 user manual — Troubleshooting
Page 40 · click to enlarge
Page 40

Troubleshooting

Also in Independent mode, if the Fan Alarm LED is yellow and the DCEs in the carrier appear to be working, you may want to schedule maintenance after peak hours.

If operating in the Basic mode and the power module’s Power LED is red, check the DCEs in the carrier. If the LEDs on the DCEs are not lit, try resetting the power module. (Reset the power module by removing the power module and then reinstalling it.) If the Power LED remains red after resetting the power module, you should replace the power module. Do not remove the failed power module until a replacement power module is available. If the power LED is red and the DCEs appear to be working, schedule maintenance for the power module after peak hours at which time you can try resetting the power power module and/or replacing it. If the Fan Alarm LED is yellow and the DCEs in the carrier appear to be working, you may want to schedule maintenance after peak hours.

If operating in the Redundant mode and one of the power module’s Power LED is red, try resetting the power module by removing the power module and then reinstalling it. If the Power LED remains red, you should replace the power module.

In addition, if the Fan Alarm LED is yellow, try resetting the power module. If the Fan Alarm LED remains yellow, you should replace the power module.

In all modes of operation, if the Power LED is not lit, check the input power source and external fuses before replacing the power module. If –48V is present at the input connector, replace the power module. If –48V is not present, check your distribution system.

If operating in the Independent mode and one of the power module’s Power LED is red, check the DCEs in the carrier.

  • If the LEDs on the DCEs above the power modules are not lit, try resetting the power module. (Reset the power module by removing the power module and then reinstalling it.) If the Power LED remains red after resetting the power module, you should replace the power module. Do not remove the failed power module until a replacement power module is available.
  • If the DCEs appear to be working, schedule maintenance for the power module after peak hours at which time you can try resetting the power module and/or replacing it.
Page 41 of the Paradyne 3610 user manual — Power Module Replacement Instructions
Page 41 · click to enlarge
Page 41

Power Module Replacement Instructions

To replace a power module (refer to Figure 3-2):

If the power module fails, you should replace it immediately. In the Redundant mode of operation, you can replace a failed power module without disrupting service to the carrier. In the Independent mode of operation, you will only disrupt service to one-half of the carrier (the affected half).

The power module replacement procedure contained in this section must be performed by a qualified service person.

Paradyne 3610 — Power Module Replacement Instructions diagram (page 41)
Fig. 16 · Power Module Replacement Instructions

In any mode of operation (Basic, Independent, or Redundant), you must have either one power module and cover plate, or two power modules in the CO Power Unit at all times. Do not remove a defective power module until a replacement is available. Leaving half of the CO Power Unit exposed is a safety hazard.

1. Make sure the new power module is configured with the same option settings as the failed power module. To set the option straps, see the Setting the Option Straps section in Chapter 2.
2. If an SDCP is not associated with this carrier and the power modules’ faceplates are visible, loosen the two captive screws on the front of the failed power module. Remove the failed power module from the CO power tray by holding onto the power module handle and sliding the power module out.
Paradyne 3610 — Power Module Replacement Instructions diagram (page 41)
Fig. 17 · Power Module Replacement Instructions

Figure 3-2. Replacing a Power Module

Troubleshooting and Maintenance · Procedure

Page 42 of the Paradyne 3610 user manual — Preventive Maintenance
Page 42 · click to enlarge
Page 42

If an SDCP is mounted on this carrier, remove the SDCP by loosening the two captive screws and disconnecting the SDCP cable. Set the SDCP aside for mounting later on. Loosen the two captive screws on the failed power module. Then, remove the failed power module from the CO power tray by holding onto the nylon cable tie and sliding the power module out.

Remember, if an SDCP needs to be remounted on this carrier, you must remove the handle on the new power module and install a nylon cable tie prior to installing the power module. Also, if installing a new power module into the left side of the power unit, hold the SDCP ribbon cable to the left of the power module when sliding the power module into the CO Power Unit. Once the power module is installed and proper operation is verified, then the SDCP can be mounted.

3. When the failed power module is removed, place the new power module in the card guides and slide the power module to the rear of the carrier. Then, tighten the two captive screws on the bottom of the power module’s faceplate.

Preventive Maintenance

In normal environments, you should inspect and/or replace the optional air filter (part number 3000-F1-020) every three months.

Page 43 of the Paradyne 3610 user manual — Overview
Page 43 · click to enlarge
Page 43

A

Interface Connections

Overview A-1 DC Inputs A-1 CO Alarm System Outputs A-4 NMS Alarm Outputs A-5

Overview

DC Inputs

This appendix provides pin assignments for the dc input connectors and alarm output connectors. It also provides illustrations of the connectors on the rear of the CO Power Unit and an NMS alarm adapter cable.

A pair of 2-pin AMP connectors on the CO Power Unit’s backplane provides an interface between the dc power input cable and the CO Power Unit (see Figure A-1). Table A-1 lists the pin assignments for the dc inputs.

A-1 3000-A2-GB41–40 May 1998

Page 44 of the Paradyne 3610 user manual — B
Page 44 · click to enlarge
Page 44
Paradyne 3610 — Interface Connections diagram (page 44)
Fig. 18 · Interface Connections

–48 Vdc B Connector

B

Figure A-1. CO Power Unit (Rear)

The backplane connector is a Universal MATE-N-LOK connector (AMP part number 350428-1). The corresponding supplied connector housing is also a Universal MATE-N-LOK connector (AMP part number 1-480698-0). Table A-2 lists AMP part numbers for the individual contacts that can be used for various wire sizes. Figure A-2 illustrates the connector housing and contact.

Table A-1 Pin Assignments of the DC Inputs

Pin Number Assigned To ...

2 –48V CO ground return

A-2 May 1998 3000-A2-GB41-40

Show 5 more labels / short text on this page
Network Management · Connector · 496-13699-01 –48 Vdc · A Alarm · Alarm
Page 45 of the Paradyne 3610 user manual — Interface Connections
Page 45 · click to enlarge
Page 45

Table A-2 AMP Part Numbers

Paradyne 3610 — Interface Connections diagram (page 45)
Fig. 19 · Interface Connections

1 Six contacts are provided in the installation kit.

Paradyne 3610 — Interface Connections diagram (page 45)
Fig. 20 · Interface Connections

Figure A-2. Connector Housing and Contact

A-3 3000-A2-GB41–40 May 1998

Interface Connections · 496-13674-01

Page 46 of the Paradyne 3610 user manual — CAUTION
Page 46 · click to enlarge
Page 46

CO Alarm System Outputs

A contact closure is provided between Pin Numbers 1 and 2 to indicate a power failure. A contact closure is provided between Pin Numbers 4 and 5 to indicate a fan failure. Note that a major alarm signal is sent to a CO alarm system upon a failure in either the –48V input or low voltage output circuits, and that a minor alarm signal is sent if the fan speed falls below 1900 rpm.

Both major (power) and minor (fan) alarms can be sent to the CO alarm system via the Alarm A and Alarm B output connectors. Figure A-1 illustrates these connectors. The connector on the CO Power Unit’s backplane is an AMP 5-position single row header. The mating connector is an AMP MTE-type connector (part number 103957-4).

The CO alarm system outputs are relay contact closures. Table A-3 lists the pin assignments for the CO alarm system outputs.

CAUTION

The relay contacts on the CO Power Unit for the CO alarm system have a rating of 0.1 amp maximum at 70 Vdc maximum.

Table A-3 Pin Assignments for the CO Alarm System Outputs

Pin Number Assigned To ...

1 Major Alarm (power failure)

2 Major Alarm (power failure)

4 Minor Alarm (fan failure)

5 Minor Alarm (fan failure)

A-4 May 1998 3000-A2-GB41-40

3 No Connection

Page 47 of the Paradyne 3610 user manual — NMS Alarm Outputs
Page 47 · click to enlarge
Page 47

NMS Alarm Outputs

voltage output circuits, and that a fan failure alarm signal is sent if the fan speed falls below 1900 rpm.

CO alarms can be sent to a Modular 3611 DSU (which will then notify a 6800 Series NMS) via a 6-wire modular jack on the CO Power Unit’s backplane (see Figure A-1). (The Modular 3611 DSU must be configured to forward alarms to a 6800 Series NMS.) Table A-4 lists the pin assignments for the NMS adapter cable. Figure A-3 illustrates the NMS adapter cable.

To avoid potential problems caused by incorrect connections (e.g., grounding the +12 Vdc source), do not set Jumper J21 as shown in Figure 2-10 of Chapter 2 if you are not using an NMS adapter cable.

Table A-4 Pin Assignments for the NMS Adapter Cable

Modular Plug End NMS Alarm Function

12 6 +12 Vdc Source

19 2 Fan Status Alarm

23 1 Power Status Alarm

1 All other pins on the 25-pin male connector are wired straight through to the 25-pin female connector. 2 This pin only functions as a +12 Vdc source when Jumper J21 is set as shown in Figure 2-10 of Chapter 2.

A-5 3000-A2-GB41–40 May 1998

Show 6 more labels / short text on this page
Interface Connections · EIA 25-Pin · Male End1 · 11 4 None · 14 3 None · 16 5 None
Page 48 of the Paradyne 3610 user manual — Interface Connections
Page 48 · click to enlarge
Page 48
Paradyne 3610 — Interface Connections diagram (page 48)
Fig. 21 · Interface Connections

Figure A-3. NMS Adapter Cable (Feature Number 3000-F2-510)

A-6 May 1998 3000-A2-GB41-40

Page 49 of the Paradyne 3610 user manual — Glossary
Page 49 · click to enlarge
Page 49

Glossary

Basic mode A mode of operation in which the single power module in the CO Power Unit supplies power to the entire carrier.

carrier The rack mounting that contains 17 slots: 1 control slot and 16 DSU or modem slots.

data communication equipment (DCE)

A device, such as a DSU, that provides an interface between a DTE device and a digital or analog network. (Also called data circuit-terminating equipment.)

data service unit (DSU)

A DCE device that interprets, interfaces, and provides timing and signal control between a DTE device and a digital network.

data terminal equipment (DTE)

A computer or peripheral device, such as a terminal or printer; a data source or sink.

Independent mode A mode of operation in which each power module in the CO Power Unit supplies power to one-half of the carrier.

LED Light-emitting diode. A light or status indicator on the front panel that glows in response to the presence of a certain condition (e.g., Fan Alarm).

Modular 3611 DSU A circuit card that contains ‘‘gold finger’’ contacts on its rear edge. A modular DSU can be removed from the front of the carrier without disturbing the DTE cables at the rear of the carrier.

rear connector plate Used with a modular DSU, such as the Modular 3611 DSU. The rear connector plate is a panel that is attached to the rear of the 3000 Series Carrier. It contains two DTE connectors and functions as an interface between the Modular 3611 DSU and the DTE.

Redundant mode A mode of operation in which both power modules in the CO Power Unit supply power to all the slots in the carrier.

A feature that allows carrier-mounted DSUs and modems to share the same diagnostic control panel. Installed at eye-level into one COMSPHERE 3000 Series Carrier, it controls and monitors the DSUs and modems in all the carriers in the cabinet. A single SDCP can control up to 8 carriers, with a total of 128 DSUs (and if present, 128 DBMs) and modems.

shared diagnostic control panel (SDCP)

Glossary-1 3000-A2-GB41-40 May 1998

Page 50 of the Paradyne 3610 user manual — Glossary
Page 50 · click to enlarge
Page 50

shared diagnostic unit (SDU)

A circuit card that plugs into a dedicated slot in the COMSPHERE 3000 Series Carrier to provide the shared diagnostic control panel and network management interfaces to the DSUs in the carrier. It translates the network management protocol to the devices in the carrier and routes incoming messages to the appropriate slots.

6800 Series Network Management System (NMS)

A Paradyne automated network management system that supports the CO Power Unit and other devices. It allows an operator to monitor network conditions, analyze problems, and take restorative measures.

Glossary-2 May 1998 3000-A2-GB41-40

Page 52 of the Paradyne 3610 user manual — O
Page 52 · click to enlarge
Page 52

E

J

EIA-232 interface, connecting NMS adapter cable, 2-19 enhanced support services, 1-6 environment, 1-4 equipment

service, 1-5 support, 1-5 warranty, 1-5

LED status indicators, 3-1

M

F

Basic, 1-2 Independent, 1-2 Redundant, 1-2

H

heat dissipation, 1-4 height

air filter, 1-4 CO power unit, 1-4 power module, 1-4 humidity, 1-4

N

NMS

connecting, 2-19, 2-20 pin assignments, A-5 alarm outputs, A-5

Independent mode, 1-2, 2-2

strap settings, 2-7 using one power source, two cables, 2-15 using two power sources, 2-14 indicators, 3-1

O

one power source, 2-12 operating temperature, 1-4 option straps

LED status, 3-1 inputs, dc, A-1 installation, 2-1

on backplane, 2-6 on power module, 2-7 setting, 2-6 out of warranty, 1-6 outputs

and brackets, 2-21 brackets, 2-22 CO power unit, 2-4, 2-9, 2-10 considerations, 2-1

Basic mode, 2-1 Independent mode, 2-2 Redundant mode, 2-3 SDCP, 2-16 second power module, 2-4, 2-5 instructions, power module replacement, 3-3

pin assignments, A-4 NMS alarm, A-5

Index-2 May 1998 3000-A2-GB41-40

Show 8 more labels / short text on this page
jumpers, 2-18 · features, 1-2 · maintenance, 3-1 · preventative, 3-4 mode · adapter cable, A-6 · location · air filter · alarm system, A-4
Page 53 of the Paradyne 3610 user manual — S
Page 53 · click to enlarge
Page 53

P

T

part numbers, AMP, A-3 physical dimensions, 1-4 pin assignments

technical specifications, 1-4 temperature, 1-4

ambient, 2-2 troubleshooting, 3-1, 3-2 two power sources, 2-14

alarm system outputs, A-4 dc inputs, A-2 NMS adapter cable, A-5 power

physical dimensions, 1-4 replacement, 3-3 replacing, 3-3 weight, 1-5 requirements, 1-4 to CO power unit, 2-11 preventative maintenance, 3-4 providing power, 2-11

U

UL, 1-5

V.35 interface, connecting NMS adapter cable, 2-20 vibration, 1-4

R

W

Redundant mode, 1-2, 2-3

strap settings, 2-8 using one power source, one cable, 2-12 using one power source, two cables, 2-15 using two power sources, 2-14 relative humidity, 1-4 replacement, power module, 3-3 replacing power module, 3-3 requirements, power, 1-4

warranty, 1-5, 1-6 weight

air filter, 1-5 CO power unit, 1-5 power module, 1-5 width

air filter, 1-4 CO power unit, 1-4 power module, 1-4

S

SDCP, installation, 2-16 second power module, installation, 2-4, 2-5 service, 1-5 setting option straps, 2-6 shock, 1-4 status indicators, LED, 3-1 storage temperature, 1-4 strap settings

Basic mode, 2-6 Independent mode, 2-7 Redundant mode, 2-8 straps, setting, 2-6 support, services, 1-6 system outputs, alarm, A-4

Index-3 3000-A2-GB41-40 May 1998

Index · module, 1-4

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
S5on the CO Power Unit’s backplane so that the p.23

Ask about the Paradyne 3610

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Paradyne 3610

Be the first to ask — other owners or our team will answer.

Original document

Paradyne 3610 manual PDF

53 pages·563 KB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…