TRIA D Boiler Sy stems, Inc. Series 8900 SH Space Heat ing Control Panel Operation and Installation M anual T RIAD Boil er System s, Inc. W est Chicago, IL 6 0185 Phone: 630-562-2700 Fax : 630-562-2 800 w w w.
Series 8900SH Control Panel O peration And Installation M anual TABLE OF CONTE NTS Section Introduction 1 Sequence of Operation 2 Entry Codes 3 Sensor Calibration 4 Sensor Troubl eshooting 5 Monitorin.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications SECTION 1: INTRODUCTION This manual explains the ope ration, installation and control of TRI AD Boilers using the Series 8900 Micr oprocessor Control Pa nel.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications terminals of each pair should be connecte d to the same termi nal in each boiler control center.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications In the event of power loss o r damage to the control pane l the boilers wi ll r evert to self control. At that point each boiler will cycl e on and off according to its high limit control.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications WIRIN G DIA GRAM.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications OUTDOOR A N D RETURN WA T ER LIN E SENSORS :.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications SERIES 8900 SH SPECIFI CA TION S: Input Voltage 9.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications GLOSSA RY: Entry Codes: The set of two digit n umbers that allow the operator to interact with the control pane l. Error Code: A code shown o n the display that indicates a problem exists either in the sensors or in the computer itself.
Series 8900SH Control Panel O peration And Installation M anual Section 1 Introduction A nd Specifications LIM I TE D FI VE -YEAR FULL TE RM W AR RA NT Y The Manufacturer warrants the equipment described as the Series 8900 Control Panel to be free f rom def ects in mate rial or workmanship under n ormal use and service.
Series 8900SH Control Panel O peration And Installation M anual Section 2 Sequence of Operations SECTION 2: SEQUEN CE OF OPERATION All f unctions of the Control Panel are activated through the use of two-digit Entry Codes that provide ins tructi on to the panel.
Series 8900SH Control Panel O peration And Installation M anual Section 2 Sequence of Operations If the outside temperature continues to drop, then the calculated Reset Ratio (code 23) will be activated. M ore heat wi ll be required to maintain the building temperature.
Series 8900SH Control Panel O peration And Installation M anual Section 3 Entry Codes SECTION 3: ENTRY CODES The control panel is o perated by Entry Codes, which are simpl e two digit numbers that provide the pane l instructions. However, bef ore entering a ny cod es, you should become f amiliar wi th the f eatures of the control panel.
Series 8900SH Control Panel O peration And Installation M anual Section 3 Entry Codes 69 This code displays the month and year. Pres s 69, then enter Month, 1 to 1 2, and the year, 01, 02, 03, etc. Then p res s #. 20 T his code starts the se quence for the 20 c odes.
Series 8900SH Control Panel O peration And Installation M anual Section 3 Entry Codes Record your settings the f ollow ing worksheet and keep for f uture reference.
Series 8900SH Control Panel O peration And Installation M anual Section 4 Sensor Calibration SECTION 4: SENSOR CALIBRATION This section will deal with the calibration of the sensors that measure b oth outside air temperatures and water system te mperatures.
Series 8900SH Control Panel O peration And Installation M anual Section 4 Sensor Calibration rotate the screwdri ver slot on the potentiometer R26 until the temperature shown on the display matches the outside temperature. The sensor is n ow calibrated.
Series 8900SH Control Panel O peration And Installation M anual Section 5 Sensor T roubleshooting SECTION 5: SENS OR TROUBLESHOOTING The wiri ng wi thin the contr ol panel from the Ter minal Strip For Field Connecti ons to the sensor input terminals on the cir cuit board are completed at the f actory.
Series 8900SH Control Panel O peration And Installation M anual Section 6 Monitoring Codes SECTION 6: MONITORING CODES M onitoring codes display the information programm ed into the control pane l, such as what temperatures it was asked to maintain, what temperature setbacks it was instructed to use, and any other customi zed settings.
Series 8900SH Control Panel O peration And Installation M anual Section 6 Monitoring Codes 90 This code , and the one s th at f oll ow , are all ti me clocks, prov iding elaps ed ru nning tim e s ince the bo il ers w ere o riginall y i ns tall ed. Pres s Co de 9 0 to start the dis play.
Series 8900SH Control Panel O peration And Installation M anual Section 7 Error Codes SECTION 7: ERROR CODE S Error codes are the way th e control p anel indicates if there are any system problems or f aults.
.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details SECTION 8: ENTRY CODE DETAILS This section provides more detail to better unde rstand the control pane l Entry Codes.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details ENT RY CODE 22: MI NIM UM RETURN WATER T EMPERA T URE SETT ING PRESS + = ENTRY CODE ENTER YOUR CHOICE PRESS = SAV E KEY FOR A MINIM UM RETURN W ATER TEMPERA TURE SETTING OF 10 0°F.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details every 1°F the outside temperature drops, the Return W ater Line temperature is increased 1°F. If the ratio is set at 1.50 , the Return W ater Line will increase 1.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details ENTRY CODE 27: DESI GN RETURN WATER T EMPE RA T URE S ETT ING PRESS + = ENTRY CODE ENTER YOUR CHOICE PRESS = SAVE K EY, TO SET DESIGN RETURN W ATER TEMPERATURE.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details ENTRY CODE 30 – 37: WA TER T EMPE RA T URE SETBA CK SCH EDULES PRESS + = ENTRY CODE FOR ALL 7 DAYS OF THE.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details days is to input the times and temperatures that will be the same f or the most of the days into the 30 code, and then enter the times and temperatures that will be different into the appropriate Entry Code(s) 31 through 37.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details Example 1: ENTER CODE “40” DISPLAY W ILL SHOW ENTER STAGE “1” ENTER A BLANK “0” ENTER BOILER NO. 1 PRESS = SA VE K EY, TO HAVE BOILER #1 OPERATE AS THE FIRST STAGE.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details ENT RY CODE 61: KEYBOA RD LOCK - UNLO CK PRESS + = ENTRY CODE PRESS + + + = LOCK OR UNLOCK DISPLAY SHOW S OR PRESS = SAV E KEY Code 61 prevents tamperi ng wi th the entries by locking the pane l.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details The code allows f or manual control of up to 24 stages. During normal operation, the pan el controls all the boilers. Code 63 will overri de that to control any boiler you choose.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details ENT RY CODE 67: 24 HOUR CLOCK - HOUR AND MI NUT E PRESS + = ENTRY CODE DISPLAY S HOW S = 6:30 PM This code allows you to set or observe the 24 hour military time clock.
Series 8900SH Control Panel O peration And Installation M anual Section 8 Entry Code Details ENT RY CODE 81: SE T BACK OVERRI DE PRESS + = ENTRY CODE ENTER CHOICE = M INUTES OF SETBACK RANGE IS FROM 1 TO 240 MINUTES PRESS = SAV E KEY This provides f lexibil ity to the setback schedu le.
Series 8900SH Control Panel O peration And Installation M anual Section 9 Fine T uning The Heating System SECTION 9: FINE TUNING THE HEATING SYSTEM The key to fine tuning any boiler sy stem is to understand the buil ding use. A hospital, an of fice building, a school, and an apartment all h ave very diff erent hosting needs.
Series 8900SH Control Panel O peration And Installation M anual Section 9 Fine T uning The Heating System Code 23: The next step is to use Code 23 to ensure the pa nel has au tomatic control of the Reset Ratio. Enter code 23 and input 0 to have it a utomatically calculated.
Series 8900SH Control Panel O peration And Installation M anual Section 10 T roubleshooting SECTION 10: TROUBLESHOOTING THE BUILDI NG EXPERIENCES A P OW ER OUTAGE In the case of a power outag e, the c.
Series 8900SH Control Panel O peration And Installation M anual Section 10 T roubleshooting THE CONTROL PANEL IS DAMAGED Turn of f the control panel and conta ct your TRI AD service contractor or TRIAD representative.
An important point after buying a device Panasonic 8900 SH (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Panasonic 8900 SH yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Panasonic 8900 SH - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Panasonic 8900 SH you will learn all the available features of the product, as well as information on its operation. The information that you get Panasonic 8900 SH will certainly help you make a decision on the purchase.
If you already are a holder of Panasonic 8900 SH, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Panasonic 8900 SH.
However, one of the most important roles played by the user manual is to help in solving problems with Panasonic 8900 SH. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Panasonic 8900 SH along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center