Powering the Planet, One System at a Time


Welcome
2001 OutBack Power started by a passionate group of engineers whom wanted to bring power conversion electronics technology into the 21st century.

This small startup quickly grew by off ering innovative and well designed solutions to renewable energy problems. OutBack listened to their customers and made many of the changes that were suggested, creating a truly customer fo- cused company in the power conversion electronics industry.
2002 OutBack introduces its fi rst sealed sinewave in- verter/charger - the FX2024, with resounding success.
This single model changed the way people looked at system design by off ering unprecedented fl exibility in system design and expansion while the sealed construction allowed for uses which previously would have been considered too “extreme” for other inverter/chargers.
Welcome to the fi ft h year of OutBack Power designing and manufacturing great products with you, our custom- ers, in mind. OutBack’s ability to continuously innovate and lead the industry as well as listen to our customers has been a major infl uence in our success.
OutBack releases the MX60 solar MPPT charge controller redefi ning performance and value.
This revolutionary product changed the way solar systems were being installed and quickly gained a reputation for get- ting the most power possible from a PV array - often making it more expensive to not use one.
Since our last catalog, OutBack has spent countless hours in research and development to engineer products at an elevated level of technological innovation. Our eff orts have resulted in new products and improved reliability. Some of these new products include: our vented higher power versions of our inverter/chargers, the world’s most effi cient grid-interactive inverter/charger, a fully integrated grid-interactive system and mobile inverter/chargers for when you are on the move.
2003 OutBack launches the fi rst of the vented versions of the FX series inverter/chargers.
These VFX models were introduced in direct response to our customer’s requests providing higher power at a similar price as the sealed counterpart.
OutBack launches the PS2 value - priced system integration accessories.
Despite our accomplishments we will not become complacent. In 2005 we expect to maintain a steady growth and pioneer solutions to challenging problems and developing even more cutting edge power electronics. We will continue to collaborate with our customers in order to develop our products and improve our industry leading technical support.
This line of accessories addressed the needs of our customers for competitively priced system integration accessories for smaller systems.
2004 OutBack releases the world’s most effi cient grid-interactive inverter/charger.
These models raise the bar for performance and value for battery-connected grid-interactive inverter/charger systems. OutBack introduces the PS1 fully integrated grid-interactive power system.
We are confi dent that OutBack is a company that is built to last, and we would like to thank you for your continued support in powering the planet, one system at a time...
This unique system sets a new standard for system integration, performance and ease of installation in grid-interactive applications.
2005 What’s new at OutBack? Read these pages to fi nd out...
Printed on Recycled Paper • Copyright 2005®



Solar. Wind. Hydro. Generator. No matter what your energy source OutBack’s products are engineered to provide your home or business with reliable electricity day-in and day- out. The OutBack modular system architecture allows your system to grow along with your power needs up to 36,000 watts. Power hungry appliances like washing machines, air conditioning and power tools are easily started by our inverter’s substantial surge power capability. When not being used, the inverter enters a power save mode, which consumes as little as 3 watts, saving your battery power for when you need it the most. OutBack’s innovative Maximum Power Point Tracking (MPPT) technology gets the most from your solar array or can also control hydro or wind turbine charging sources. Complete system status and control is easily monitored by a single control, instead of requiring the user to keep an eye on multiple displays and status indicators.

Grid-Interactive renewable energy systems enable you to demonstrate your personal commitment to a renewable energy future. With the OutBack grid-interactive system, backup AC power is made available 24 hours a day in the event of a utility outage, provid- ing reliable power and peace-of-mind. At night, the inverter’s automatic power save mode ensures that energy is not wasted by needlessly charging your batteries from the utility grid. An average conversion efficiency of 91% using the California Energy Commission (CEC) test protocol provides greater savings and a shorter time period for system payback. OutBack’s grid-interactive technology provides you more than a typical solar inverter, we also have an unmatched ability to utilize solar, wind and hydropower sources.

OutBack’s Mobile and Marine inverter/charger models provide the high performance and reliability you need no matter where your travels take you. Our die-cast metal construction allows mounting in any position, even upside down. The required AC input neutral/ground switching is taken care of by a fully integrated 30 amp AC transfer switch for shore chord or generator hook-up. Three circuit boards and a simple design make field servicing the unit easy no matter where you are. Rigorous testing at the factory ensures that each inverter/charger works the first time as well as for many years to come.

Wherever you are in the world, OutBack’s European and Export off-grid inverter/chargers are engineered to provide your home or business with reliable 50 Hz AC power. Our high surge power capability starts the most demanding of 230 volt appliances and the modular system architecture makes expanding a system’s power capacity or switching to three-phase output power simple and trouble free. Both sealed (FX) and vented (VFX) models are available with 50 Hz output to match your installation’s envi- ronmental conditions. The inverter/chargers low weight (as low as 27 kilograms) and compact dimensions allow easy transport and installation in less than ideal locations. Our field serviceable design eliminates the need to ship inverters if repair or upgrades are required. Superior technical support is available from our European office, allow- ing questions to be promptly answered and any problems to be quickly resolved.

OutBack inverter/chargers are the next generation in advanced power man- agement. Each is a DC to AC sinewave inverter, battery charger and AC transfer switch housed within a tough die-cast aluminum chassis.

environments that would normally destroy other inverter/chargers. Protection for internal components is provided by our die-cast aluminum chassis with a powder coated fi nish to prevent corrosion. Internal and external cooling fi ns allow for passive heat transfer, enabling peak operating effi ciencies as high as 93% and looking cool
Just like the local utility grid, the inverter produces true sinewave AC electric- ity for your stand-alone or backup power needs. Com- puters, TVs and pumps are just some of the examples of modern electronics that last longer and run better when powered with true sinewave electricity from an OutBack inverter. Starting up your air conditioning, washing machine or well pump is worry-free because of our high surge power capability.
are kept out through the generous use of
gaskets and 0-ring seals on all seams and openings. A protective conformal coating on all circuit boards provides the fi nal line of defense against corrosion. Th e now standard externally mounted “TURBO” cooling system improves performance in hot conditions.
VFX Vented Inverter/Chargers Th e VFX series is designed for more protected installations. By utilizing an effi cient active cooling design, the VFX models are available with AC output up to 3.6 kilowatts. Our tough die- cast aluminum chassis physically protects the internal components while the air intake includes an easily cleaned fi lter, which allows for ventilation while also keeping bugs and other debris out. All circuit boards are conformal coated to prevent corrosion from airborne moisture in humid conditions. Th e now standard DC wiring cover (DCC) protects the DC terminals and battery cables from damage.
Batteries and generators are the costly consumables when using inverters to generate electricity. Th e integrated smart battery charger uses multiple stages to perform quick recharging while prolonging battery life, saving your batteries and generator from unnecessary wear. Automatic switching between AC power sources is seamless due to an AC transfer switch that reacts in less than 16 milliseconds.




h die-
Unique networked communication is built into all OutBack products pro- viding complete integration. Expanding your system with your growing power needs is as simple as adding additional inverters with modular architecture. Further fl exibility is provided with the ability to be connected at any time in ei- ther parallel, series or three-phase power confi gurations. Industry leading OutBack reliability is achieved through simplifi ed design and rugged construction.

now
ver
ables
ables






MX60 The MX60 raises the bar for high performance solar controllers. OutBack’s ingenuity and engineering experience has been combined to maximize the output power of your expensive solar array. Our real time active Maximum Power Point Tracking (MPPT) system ensures that your solar array is operating at its peak power point regardless of age, shading or environmental conditions. Systems with large solar arrays are now a snap thanks to the MX60’s 60 amp DC output current rating for 12, 24 or 48 VDC systems - all with just one product model!
Real wiring flexibility of your solar array is finally here because of the MX60’s wide range DC input, up to 150 VOC. The ability to step-down a high voltage solar array to a low voltage battery can save you money by reducing the size of wire required and making the installation simpler and faster. Our smart multistage recharging process ensures your batteries are recharged efficiently and gently to prolong battery life and achieves the highest possible performance.
All of the MX60’s status information is displayed on the large built-in 3.1" (8 cm) backlit LCD screen. Monitoring your solar array’s performance is easy because of included data logging system that automatically records the last 64 days of system operation. OutBack’s network communication system allows your MX60 to communicate with the rest of your OutBack system, eliminating multiple product interaction problems and allowing remote monitoring via the OutBack MATE display up to 1000 feet / 300 meters away.
MX60 Specifications Nominal Battery Voltage 12, 24, 32, 36, 48, 54 or 60 VDC (Single model) Output Current 60 amps maximum with adjustable current limit for smaller systems Maximum Solar Array Size 12 VDC systems 800 Watts / 24 VDC systems 1600 Watts / 48 VDC systems 3200 Watts PV Open Circuit Voltage (VOC) 150 VDC absolute maximum coldest conditions / 135 VDC start-up and operating maximum Standby Power Consumption 1 Watt or less Charging Regulation Five Stages: Bulk, Absorption, Float, Silent and Equalization Voltage Regulation Set points 13 to 80 VDC User adjustable with password protection Equalization Voltage Up to 5.0 VDC above Absorb Set point Adjustable Timer - Automatic Termination when completed Battery Temperature Compensation Automatic with optional RTS installed / 5.0 mV per °C per battery cell / 30 mV per °C for a 12 VDC system Voltage Step-Down Capability Can charge a lower voltage battery from a higher voltage PV array Power Conversion Efficiency Typical 98% at 60 amps with a 48 V battery and nominal 48 V solar array Status Display 3.1” (8 cm) backlit LCD screen with 4 lines with 80 alphanumeric characters total Remote Interface Proprietary network system using RJ 45 Modular Connectors with CAT 5e Cable (8 wires) Data Logging Last 64 days of operation amp hours, watt hours and time in float for each day along with total lifetime power production Hydro / Wind Turbine Applications Consult factory for approved turbines Positive Ground Applications Requires two pole breakers for switching both positive and negative conductors on both solar array and battery connections Operating Temperature Range Minimum -40° to maximum 60° C (Power capacity of the controller is derated when above 25° C) Environmental Rating Indoor Type 1 Conduit Knockouts Two .5” (13 mm) and .75” (19 mm) on the back; One .75” (19 mm) and 1” (25 mm) on each side; Two .75” (19 mm) and 1” (25 mm) on the bottom Warranty Standard 2 year / Optional 5 year Weight Unit 11.6 lbs (5.3 kg) Shipping 14 lbs (6.4 kg) Dimensions (H x W x L) Unit 13.5 x 5.75 x 4” (40 x 14 x 10 cm) Shipping 18 x 11 x 8” (46 x 30 x 20 cm)
Use appropriate wire size in accordance with NEC. Note * Add 1% to the solar arrays open circuit voltage for every 2.5° C expected below the 25° C standard panel rating (STC). The resulting value must be below 150 VDC at the lowest expected temperatures conditions and less than 135 VDC for typical conditions to ensure reliable operation.


MATE Th e MATE system display and controllers are complete management tools for your OutBack Power system. Th rough the use of a single MATE you can remotely manage and monitor multiple inverter/ chargers, MX60s and any future OutBack power conversion and control products.
Th e MATE and MATE2 are packed full of features to make system management simple. Th e easy-to-read 3.1" (8 cm) LCD is backlit for dark operating conditions. Four soft keys allow easy context-based navigation of menus and functions. Two hot keys give immediate access to AC and inverter functions.



A built-in clock and calendar function enables timer based program- ming of inverter and charger operation. Th is permits you to set the system to work with time-of-day power rates or to limit a generator’s run time to a specifi c time period of the day or week. All of your settings are stored in permanent memory to eliminate the need to reprogram in the event of a system shutdown or battery replacement. Th e MATE and MATE2 include a RS232 port with DB9 jack for connection to the serial port of a PC computer. Th rough the use of optional WinVerter soft ware you can perform such operations as data logging and graphical display of the system’s operation and performance. MATE2M Th e MATE2M is the same technology as the MATE and MATE2 but is designed to be used with your M-series inverter/chargers in mobile applications. Incorporating a more simplifi ed menu, the settings needed for mobile power system management are more quickly accessed. A fl ush mount case design makes installation in boats and RVs more compact and attractive.


e

MATE Specifi cations
MATE Surface mount with RS232 Grey
MATE2 Flush mount with RS232 Black
MATE2M Flush mount without RS232 Black
Interface Display 3.1" (8 cm) backlit LCD
Control Keypad 6 backlit silicone keys - dedicated inverter and AC input keys
Status Indicators Two LED Status Indicators
Communication Protocol Proprietary OutBack Multi-drop using an OutBack HUB4 or HUB10
Interconnection Cabling Standard CAT 5 network cable with RJ45 modular jack - 50' (5 m) included
PC Computer Interface RS232 opto-isolated DB9 jack 9600 baud serial communication
Microprocessor 16 MHz low power consumption version
Set point and Data Memory 32K non-volatile fl ash RAM
Clock / Calendar On-board real time clock with battery backup
Environmental Rating Indoor Type 1
Maximum Cable Length 1000' (300 m)
Warranty Standard 2 year / Optional 5 year
Weight Shipping 1 lb (.5 kg)
Dimensions (H x W x L) Shipping 5.75 x 4.25 x 2” (15 x 11 x 5 cm)

HUB Th e HUB system communications man- agers are the backbone of your networked OutBack power conversion system. Th e OutBack HUB communicates stacking, load share and power save off /on signals. Interconnection cabling is standard Ethernet CAT5 with RJ45 modular jacks. Th rough the use of a HUB, your system is completely coordinated and managed by the MATE.




Number of Ports 4 Plus MATE 10 Plus MATE
Weight Unit 1 lb (.5 kg) 1 lb (.5 kg) Shipping 3 lbs (1.4 kg) 3 lbs (1.4 kg) Dimensions (H x W x L) Unit 10.5 x 6.25 x 1.27” (27 x 16 x 3 cm) 10.5 x 6.25 x 1.27” (27 x 16 x 3 cm) Shipping 12 x 6 x 5” (31 x 15 x 13 cm) 12 x 6 x 5” (31 x 15 x 13 cm)
HUB4
HUB10



RTS Th e OutBack Remote Temperature Sensor (RTS) is a necessary tool for proper battery charging. All OutBack products with integrated battery charging have a temperature compensation system built-in which benefi ts from the installation of the optional RTS. Th e RTS ensures that your OutBack system knows the precise ambient tem- perature so that it can recharge your batteries safely and effi ciently. Systems with multiple OutBack products connected to one HUB4 or HUB10 require only a single RTS to be installed.

Battery Charging Batteries are a key component in backup and off -grid systems, oft en serving as the only energy storage device. To guarantee that they function properly it is important that your batteries are maintained. A chief part of this maintenance is proper charging. Your batteries should always be maintained above a 50% level of charge and receive a complete recharge once a month to ensure operation at peak performance. Prolonged use of the battery below a 50% state of charge will adversely aff ect the long-term health of the battery and can result in premature failure.
Th e multistage charging process uses several regulation stages to allow fast recharging of the battery energy storage system while ensuring a long battery life, high performance and effi cient operation of the overall system. Th e charging process begins with the BULK stage, where maximum current is sent to the batteries until the target “absorb” voltage is reached and the absorb stage of the charge begins. During ABSORB, the charger provides the batteries with the just enough current to hold at the set voltage for a preset amount of time. Following this cycle, the charging system changes between available OutBack charging products. Using the MX-60, the batteries enter the FLOAT stage where they are given a maintenance charge until there is no excess renewable energy. Th e FX or VFX inverter/charger will go into SILENT mode where the charger turns off until the battery voltage drops to the “re-fl oat” setting. At this point the inverter/charger initiates the maintenance FLOAT charge. Th is method reduces fuel and utility consumption.
It should be noted that the temperature of your batteries has an impact on the charging process. Th e OutBack RTS should be used to monitor this. In higher ambient temperatures, the battery charging regulation settings will be reduced to prevent overcharging of the batteries. Conversely, in lower ambient temperature conditions, the regulation settings will be increased to ensure complete recharging of the batteries.
Batteries are composed of a group of individual cells. Th rough normal use, the charge of each individual cell will not be equal to the other cells. To address this, your batteries should be EQUALIZED either once each month or once every few months depending on usage. During the equalization charge the electrolyte in the battery is stirred up by gas bubbles, which help to create an equal mixture of water and acid. Simultaneously the full cells are overcharged which allows the low cells to “catch up” and all of the active material in the battery to be reconverted to its charged state. Depending on usage, the hardened battery plate material that is no longer active in the bat- tery-sulfation can also be reduced by an equalization charge.

Voltage · Time · * MATE Adjustable





PSX-2
T e Ou
generator and split phase output balancing or as a series stacked inverter to

load


am
25 amp dual breaker in a steal enclosure, the PSX-240 is ready to install in your custom application. Use for 120 or 240 VAC 60 Hz systems only.

Powering 240 volt items like deep well pumps with a single 120 volt inverter is possible thanks to the PSX-240’s step-up capability. Its step-down feature allows you to charge your batteries with a 240 volt generator through a single 120 volt inverter. Th e PSX-240’s ability to balance the output of series stacked inverter/chargers makes it a critical item when using the OutBack stacking 120/240 VAC confi guration.
inverter i
allows you to charge
T e PSX-240’s ability to balance t
0 VAC co
Th e X-240 is also available without the enclosure, for installation inside the PS2AC or PS4AC enclosures.
p

Step-Down

Generator Balancing
120/240 VAC Loads
120/240 VAC Generator
PSX-240 Inverter/Charger
OutBack Balancing
120/240 VAC Loads
120/240 VAC Generator
Inverter/Charger PSX-240

At OutBack, we adhere to a philosophy that a power system should be fully customizable to address your specifi c needs. Th erefore we set out to create the world’s only group of inverter/chargers that use a truly modular architecture. Th is modular architecture uses the next generation of a technique referred to as “stacking” to enable you to tailor your system for higher output power, increased charging capabilities and/or three-phase power confi guration.
Whether stacked in parallel, classic series, series/parallel or three-phase there is always an inverter/charger which performs the task of Master. Th e Master talks to the other units through the HUB system communications manager while performing three major roles, keeping all inverter/chargers properly phased, controlling inverter and charger output levels, as well as putting unused inverters into Power Save mode to improve effi ciency at low AC load levels.
Parallel Stacking - More power at same output voltage When the inverter/chargers are stacked in parallel all inverter and charger outputs are combined. Th is means that each inverters AC output is added up to equal your total system AC output, up to 36,000 watts, in phase at the same 120 VAC/60 Hz or 230 VAC/50 Hz output voltage. Charging output amperage is also combined in this same manner.
9 kW 120 VAC
3 kW 120 VAC 3 kW 120 VAC 3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC
Classic Series Stacking - More power at higher output voltage Stacking inverter/chargers in classic series provides a system with split phase 120/240VAC. Th is method does not allow balancing between separate legs on a system and is can only be used in dual inverter/charger systems without the X-240 Auto Transformer.
3 kW 120 VAC Leg 1
6 kW 240 VAC Leg 1
3 kW 120 VAC
3 kW 120 VAC Leg 2
3 kW 120 VAC
3 kW 120 VAC
OutBack Series/Parallel Stacking - More power at all output voltages Series/Parallel stacking or OutBack (OB) stacking is unique to OutBack inverter/chargers. Never before has it been possible to have inverter/char- gers balancing loads intelligently between two legs of AC power while seamlessly changing between series and parallel. OB Stacking uses the X-240 auto transformer to balance the loads between the two separate series legs of a system. Th e X-240 allows AC loads on leg 1 and leg 2 to be powered by any combination of inverter/chargers within your system. Even if there are only two inverter/chargers, connected in series, they can also func- tion as if connected in parallel. Th is allows larger AC loads to be operated by a system without risking overloading one of the 120 VAC outputs.
9 kW 120 VAC Leg 1
12 kW 240 VAC Leg 1
3 kW 120 VAC 3 kW 120 VAC
3 kW 120 VAC
9 kW 120 VAC Leg 2
3 kW 120 VAC 3 kW 120 VAC
3 kW 120 VAC
3-Phase Stacking - More power for three-phase loads Th ree inverter/chargers can be confi gured to provide 120/208 VAC or 230/400VAC four wire “Wye/Star” three-phase AC Power. An inverter/ charger is used to power each of the three legs for 3-phase AC power. Th e loads on each of the inverters does not need to be kept balanced, each phase is independently voltage regulated.
3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC
3 kW 120 VAC


PS1 The PS1 is advanced engineering and refinement that you have come to expect from OutBack Power in a next generation grid-interactive solar electric system. The system’s battery backup is a silent and hands-off alternative to noisy and maintenance intensive generators.
In side-by-side “real world” testing the PS1 system performs within 5% of the industry leading battery-less grid-tie inverter, translating into more savings when using net metering. The same field proven MPPT technology found in the MX60 solar charge controller is featured in the PS1. This cutting edge concept gives the system the ability to use your PV array at its peak output. Uninterrupted AC power is provided by the PS1’s system’s true sinewave inverter that has an industry leading, California Energy Commission (CEC) certified, efficiency of 91%, thus guaranteeing that your household appliances run seamlessly while utilizing all available solar power. Your recommended AGM batteries are maintained and charged by an innovative OutBack multistage charging process, a valuable feature that assists in providing reliable backup power and a battery life up to 10 years. An ultra-fast 16 millisecond transfer switch guarantees that even sensitive backup loads, such as computers, never know when a grid outage occurs.
Like every OutBack Power product, the PS1 is rugged. All components are protected within an aluminum type 3R rainproof enclosure. The ETL listed system is pre-wired by OutBack engineers to ensure that the PS1 system works reliably for years to come. A standard 5 year warranty provides peace of mind and satisfies state rebate requirements.
PS1 - 3000 Vented Inverter/Charger with MX60 and HUB4
PS1 - 2500 Sealed Inverter/Charger with MX60 and HUB4
PS1 - BE Battery Enclosure with all cables (Order batteries separately)
Model Rating Version Width
OBAC-20 25 amp 120 VAC Single Pole OutBack .05” (13 mm)
OBAC-15 15 amp 120 VAC Single Pole OutBack .05” (13 mm)
Model Rating Version Width
OBPV-8 8 amps 125 VDC Single Pole OutBack .05” (13 mm)
OBPV-10 10 amps 125 VDC Single Pole OutBack .05” (13 mm)
OBPV-15 15 amps 125 VDC Single Pole OutBack .05” (13 mm)
Model Description

Continuous Power Rating At 40° C 2500 VA 3000 VA
At 25° C 3000 VA 3600 VA
AC Voltage / Frequency Output 120 VAC 60 Hz 120 VAC 60 Hz
AC Input Current Maximum AC Transfer Switch 50 amps AC 50 amps AC
Battery Charger 16 amps AC with automatic back-off 20 amps AC with automatic back-off
Maximum AC Surge Current Peak (1 millisecond) 70 amps AC 70 amps AC
RMS (5 seconds) 50 amps AC 50 amps AC
Maximum PV Array Wattage 3300 watts DC stc rating 3300 watts DC stc rating
PV Open Circuit Voltage Maximum 150 VDC 150 VDC
MPPT Input Voltage Range 44 to 135 VDC 44 to 135 VDC
PV Array Ground Fault Protection Standard - 80 amp DC Standard - 80 amp DC
Inverter Efficiency Typical 91% (not CEC Certified) 91% (CEC Certified)
MPPT Efficiency 98% 98%
Overall System Efficiency Typical 89% 89%
Battery Voltage - Nominal 48 VDC 48 VDC
Minimum / maximum operating range 40 to 60 VDC 40 to 60 VDC
Battery Charge Rate Inverter 35 amps DC 45 amps DC
MX60 60 amps DC 60 amps DC
AC Output Voltage Regulation Typical 5% 5%
Nominal 120 VAC 120 VAC
AC Output Current Inverting 25.0 amps AC 30.0 amps AC
Selling 20.8 amps AC 25.0 amps AC
Total Harmonic Distortion Inverting 2% VAC THD 2% VAC THD
Selling < 5% current THD per UL1741 conditions < 5% current THD per UL1741 conditions
AC Transfer Switch Speed Typical < 16 Milliseconds < 16 Milliseconds
Battery Temperature Sensor Included Included
Operating Temperature Range -40° C to 60° C (power derated above 25° C) -40° C to 60° C (power derated above 25° C)
Recommended Minimum Energy Storage 4 kWHRS at 80% discharge 4 kWHRS at 80% discharge
Recommended Batteries Four AGM type 31 or type 27 sealed VRLA Four AGM type 31 or type 27 sealed VRLA
Communications Optional MATE system display with RS232 port Optional MATE system display with RS232 port
Enclosure Materials Powder coated aluminum, stainless steel hardware Powder coated aluminum, stainless steel hardware
Mounting Wall mount, 16 on center studs Wall mount, 16" on center studs
Recommended Mounting Hardware 5/16 x 2.5” Lag Bolts - three per side minimum 5/16 x 2.5” Lag Bolts - three per side minimum
System Enclosure Dimensions (H x W x D) Unit 31.3 x 17.25 x 12.9” (80 x 44 x 33 cm) 31.3 x 17.25 x 12.9” (80 x 44 x 33 cm)
Shipping 40.5 x 20.5 x 17.25” (103 x 52 x 44 cm) 40.5 x 20.5 x 17.25” (103 x 52 x 44 cm)
Battery Enclosure Dimensions (H x W x D) Unit 36.25 x 17.25 x 12.55” (92 x 44 x 32 cm) 36.25 x 17.25 x 12.55” (92 x 44 x 32 cm)
Shipping 43.25 x 20.25 x 16.75” (110 x 51 x 43 cm) 43.25 x 20.25 x 16.75” (110 x 51 x 43 cm)
System Weight Unit 107 lbs (49 kg) 107 lbs (49 kg)
Shipping 117 lbs (53 kg) 117 lbs (53 kg)
Battery Enclosure Weight (without batteries) Unit 29 lbs (13 kg) 29 lbs (13 kg)
Shipping 47 lbs (21 kg) 47 lbs (21 kg)
Certifications ETL certified to the UL1741 standard ETL certified to the UL1741 standard
Anti-Islanding Measures UL1741 compliant UL1741 compliant
Warranty 5 year limited repair warranty standard 5 year limited repair warranty standard
Field Installed Options MATE or MATE2 remote system display MATE or MATE2 remote system display
OBAC breakers for additional AC load circuits OBAC breakers for additional AC load circuits
OBPV breakers for PV array series string protection OBPV breakers for PV array series string protection
Peak 93% 93% · Peak 92% 92%




PS2 OutBack Power off ers compact enclosures for all of the AC and DC components of a renewable energy power conversion system. Th e PS2 series saves time, money and space by combining the disconnects, over-current protection devices and control components into easy- to-install enclosures. Capable of supporting one or two OutBack FX series inverter/chargers, up to three MX60 charge controllers, a MATE system controller and all the associated AC and DC components.
Th e OutBack PS2 series can be fully customized to your application and ordered pre-wired or as individual components for fi eld assembly.
PS2AC Breaker Panel Th e PS2AC is engineered to be a code-compliant steel enclosure for AC power routing and management.

Shown with 120/240 VAC/60 Hz dual inverter bypass (50D) or 230 VAC/50 Hz dual inverter bypass (50DE) and additional AC load breakers
PS2DC Breaker Panel Th e PS2DC is a code-compliant steel enclosure engineered to contain all DC power routing and management components.


Model Standard Breakers Dimensions Unit (H x W x D) Dimensions Shipping (H x W x D) Weight Unit
PS2AC-50D 50 amp 120/240 VAC 60 Hz Bypass assembly 18.5 x 11.5 x 9” (47 x 29 x 23 cm) 22 x 15 x 12” (56 x 38 x 30 cm) 22 lbs (10 kg)
PS2AC-50DE 50 amp 120/230 VAC 50 Hz Bypass assembly 18.5 x 11.5 x 9” (47 x 29 x 23 cm) 22 x 15 x 12” (56 x 38 x 30 cm) 22 lbs (10 kg)
PS2AC No breakers included 18.5 x 11.5 x 9” (47 x 29 x 23 cm) 22 x 15 x 12” (56 x 38 x 30 cm) 20 lbs (9 kg)
PS2DC-175 175 amp DC Breaker 18.5 x 11.5 x 9” (47 x 29 x 23 cm) 22 x 15 x 12” (56 x 38 x 30 cm) 22 lbs (10 kg)
PS2DC-250 250 amp DC Breaker 18.5 x 11.5 x 9” (47 x 29 x 23 cm) 22 x 15 x 12” (56 x 38 x 30 cm) 22 lbs (10 kg)
PS2DC No Breakers included 18.5 x 11.5 x 9” (47 x 29 x 23 cm) 22 x 15 x 12” (56 x 38 x 30 cm) 20 lbs (9 kg)
OutBack PS2AC Bypass Assemblies Specifi cations - for fi eld installations in bare PS2AC version
Model Inverter Output Bypass Breaker Rating Input Breaker Rating Output Breaker Rating
PS2-IOB-50D 120/240 VAC 60 Hz 50 amps at 120/240 VAC 50 amps at 120/240 VAC 50 amps at 120/240 VAC
PS2-IOB-50DE 230 VAC 50 Hz 50 amps at 230 VAC 50 amps at 230 VAC 50 amps at 230 VAC
Th e PS2DC Breaker Panel has eight small .75" (19 mm), three medium 1" (26 mm) or two large 1.5" (32 mm) breaker positions. Th e small sizes are 1-80 amps, medium sizes are 100 or 125 amps an the large sizes are 175 or 250 amps.
1S 2S 3S 4S 5S 6S 7S 8S 1L 2L
PS2 Mounting Plate Th e PS2MP is a steel powder coated, one-part mounting plate for all your PS2 series accessories and up to two OutBack Inverter/Chargers.




PS2 Mounting Plate Specifi cations
Model Dimensions Unit (H x W x D) Dimensions Shipping (H x W x D) Weight Shipping
PS2MP 20 x 44 x .75” (51 x 112 x 2 cm) 22.25 x 49.5 x 3” (56 x 126 x 8 cm) 24 lbs (10.8 kg)

PS4 Th e PS4 series is the ideal AC and DC enclosure system for medium to large size renewable energy power conversion system. Th e PS4 is comprised of two compact enclosures for all of your system’s AC and DC components. It saves time, money and space by combining disconnects, over-current protection devices and control components into easy-to-install enclosures.
Th e PS4 is capable of supporting up to four OutBack FX series inverter/chargers, six MX60 charge controllers, a MATE system controller and all the required AC and DC components and wiring.
Th e OutBack PS4 system can be fully customized to your application and ordered pre-wired or as individual components for fi eld assembly.






Model Standard Breakers Dimensions Unit (H x W x D) Dimensions Shipping (H x W x D) Weight Shipping
PS4AC-60Q 60 amp 120/240VAC 60 Hz Bypass assembly 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 26 lbs (12 kg)
PS4AC-100Q 100 amp 120/240VAC 60 Hz Bypass assembly 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 26 lbs (12 kg)
PS4AC-60QE 60 amp 230VAC 50 Hz Bypass assembly 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 26 lbs (12 kg)
PS4AC No bypass included 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 24 lbs (11 kg)
PS4DC-175 One 175 amp DC breaker 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 24 lbs (11 kg)
PS4DC-250 One 250 amp DC breaker 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 24 lbs (11 kg)
PS4DC No breakers included 18.26 x 11.45 x 8.8” (46 x 29 x 22 cm) 12 x 14 x 21” (31 x 36 x 53 cm) 22 lbs (10 kg)
OutBack PS4AC Bypass Assemblies Specifications - for field installations in bare PS4AC version
Model Inverter Output Bypass Breaker Input Breaker Output Breaker
PS4-IOB-60Q 120/240 VAC 60 Hz 60 amps at 120/240 VAC Four 50 amps at 120 VAC Four 50 amps at 120 VAC
PS4-IOB-100Q 120/240 VAC 60 Hz 100 amps at 120/240 VAC Four 50 amps at 120 VAC Four 50 amps at 120 VAC
PS4-IOB-60QE 230 VAC 50 Hz 60 amps at 230 VAC Four 30 amps at 230 VAC Four 30 amps at 120/230 VAC
1S 2S 3S 4S 5S 6S 7S 8S 9S 10S 1L 2L 3L 4L
The PS4DC Breaker Panel has ten small .75" (19 mm), up to six medium 1" (26 mm) or four large 1.5" (32 mm) breaker positions. The small sizes are 1-80 amps, medium sizes are 100 or 125 amps an the large sizes are 175 or 250.
PS4 Mounting Plate The PS4MP is a steel powder coated, one-part mounting plate for all your PS4 series accesso- ries and up to four OutBack Inverter/Chargers.

38.3" (97 cm)
PS4 Mounting Plate Specifications
Model Dimensions Unit (H x W xD) Dimensions Shipping (H x W x D) Weight Shipping
PS4MP 25.5 x 38.3 x 3” (65 x 97 x 8 cm) 36 x 50 x 1” (91 x 127 x 3 cm) 46 lbs (21 kg)

OutBack AC Breakers Hydraulic-Magnetic type breakers that are DIN rail “snap-in” mountable and can be used for in- put, output or load circuits. 1/2" (13 mm) wide.


Model Rating Version Width
OBAC-50 120VAC Single Pole 0.5” (13 mm)
OBAC-50D 120/240VAC Dual Pole 1.0” (26 mm)
OBAC-50-3P 120/208VAC Three Pole 1.5” (39 mm)
OBAC-50DE 240VAC Dual Pole 1.0” (26 mm)


OBAC-30 120VAC Single Pole 0.5” (13 mm)
OBAC-30D 120/240VAC Dual Pole 1.0” (26 mm)
OBAC-25D 120/240VAC Dual Pole 1.0” (26 mm)
OBAC-20 120VAC Single Pole 0.5” (13 mm)
OBAC-20D 120/240VAC Dual Pole 1.0” (26 mm)
OutBack DC Breakers Panel mounted Hydralic-Magnetic type breakers which can be used for DC sources, inverters or load circuits. 3/4" (18 mm) wide.
OBAC-15 120VAC Single Pole 0.5” (13 mm)
OBAC-15D 120/240VAC Dual Pole 1.0” (26 mm)


Model Current Rating Stud Terminal Size Width
OBDC-250 250 amp 125 VDC 3/8 “ stud 1.5" (39 mm)
OBDC-175 175 amp 125 VDC 3/8” stud 1.5" (39 mm)
OBDC-125 125 amp 125 VDC 5/16" stud 1.0” (26 mm)

OBDC-100 100 amp 125 VDC 5/16” stud 1.0” (26 mm)
OBDC-80 80 amp 150 VDC 5/16” stud 0.75" (19 mm)
OBDC-70 70 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-60 60 amp 150 VDC 1/4” stud 0.75" (19 mm)
OutBack PV Ground Fault Protection System Th e OBDC-GFP/2 is required by the NEC for PV arrays mounted on residential dwelling roofs. It can be used with the PS2DC, PS4DC or PS1. An OBDC-GFP/2 protects wiring and sys- tem components for one or two PV arrays: dual 80 amp PV circuits 150 VDC max VOC. Th e OBDC-GFP/2 system includes the GFP unit, a ground bus bar, neutral and ground connection wiring and mounting hardware.
OBDC-50 50 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-40 40 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-30 30 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-20 20 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-15 15 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-10 10 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-5 5 amp 150 VDC 1/4” stud 0.75" (19 mm)
OBDC-1 1 amp 150 VDC 1/4” stud 0.75" (19 mm)


Model Description Stud Terminal Size
OBDC-GFP/2 80 amp at 150 VDC 2 Poles - Requires 3


X-240 Auto Transformer Th e same auto transformer and breakers as the PSX-240 but designed to be housed within the PS2AC or PS4AC. It can be used for step-up, step-down, generator and split phase output balancing or as a series stacked inverter-to- load balancing auto-former. It can also transfer up to 2kW (3kW with the optional X fan kit) from one side of the total power rating of the generator or the total power rating of an OutBack stacked series/parallel 120/240 VAC inverter/charger confi guration.
X-240 120/240 VAC 60 Hz
2.0 kW without Fan Kit
3.0 kW with X-Fan Kit
X-Fan Kit Thermostatic controlled brushless fan 120 VAC Powered

X-Fan Kit Th e X-Fan Kit increases the power rating of the X-240 to a maximum of 6 kVA continuous. Th ermostatic controlled 120 VAC powered.
GBB Ground Bus Bar not insulated
TBB Terminal Bus Bar with black insulators
TBB-B Terminal Bus Bar with blue insulators
TBB-R Terminal Bus Bar with red insulators
TBB-W Terminal Bus Bar with white insulators

Use for adding more wire terminations or for isolating multiple positive / negative cir- cuits. All TBB and GBB models have three #1/0 to 14 AWG and eight #6 to 14 AWG screw type compression terminals, which means no ring lugs required. Available with black, white and red insulators. Th e Battery Bus is .25" (7 mm) thick tin plated copper and can be mounted on the back plate of the PS2DC / PS4DC or directly on the battery breaker terminals.
ACA FX and VFX AC end
DCA FX and VFX DC end
Conduit Adapters Allows connection of the FX and VFX inverter/chargers to the PS2 and PS4 breaker panels or 2" conduit.
Mounting Brackets Th e mounting bracket allows MX60 charge controllers to be mounted on the side of the PS2DC or PS4DC enclosures.

PV Array Combiner Box Th e PSPV is a solar array combiner which can be used with a wide variety of system confi gurations and solar module types. Th e PSPV is designed to provide NEC code compliant series over current protection of the wiring of multiple PV modules or subarrays for connection to charge controllers, inverters or other systems components. Th e rainproof aluminum enclosure is easily fi eld confi gured to match your PV system design and amperage requirements.


Photovoltaic (PV) Array Breakers PV breakers are Hydraulic-Magnetic type and are not aff ected by high ambient temperatures. All breakers have a 10 year warranty. Maximum of twelve OBPV in one PSPV enclosure.

OBPV-2 2 amps 150 VDC
OBPV-4 4 amps 150 VDC
OBPV-6 6 amps 150 VDC
OBPV-8 8 amps 150 VDC
OBPV-9 9 amps 150 VDC
OBPV-10 10 amps 150 VDC
OBPV-15 15 amps 150 VDC
OBPV-30 30 amps 150 VDC
PV Array Fuses and Fuse Holders DIN rail snap-in mount with #8 AWG setscrew type compression terminals. Touch-safe design. Not rated for load make or load break usage. UL listed for up to 600 VDC. Maximum of eight fuse holders in one PSPV enclosure.



OBFH Fuse Holder only
OBF-6 6 amp 600 VDC
OBF-10 10 amp 600 VDC



OBF-15 15 amp 600 VDC
Terminal and Ground Bus Bars Use for adding more wire terminations or for isolating multiple positive / negative circuits. Has three #1/0 to 14 AWG and eight #6 to 14 AWG screw type compression terminals, which means no ring lugs required.
TBB Terminal Bus bar with black insulators
GBB Ground terminal Bus bar

Model Rating · Model Description

Main Office 19009 62nd Avenue NE Arlington, WA 98223 USA Phone: (360) 435.6030 Fax: (360) 435.6019
European Office Urb. Garraf II, Buzón 214 C/. Eramprunya #26 08860 - Les Botígues de Sitges Barcelona, ESPAÑA Phone: (+34) 600.843.845
Owners and our team usually reply within a day — and your question helps the next person too.