Thank you for your purchase of OutBack products. We make every eff ort to assure our power
conversion products will give you long and reliable service for your renewable energy system.
As with any manufactured device, repairs might be needed due to damage, inappropriate use,
or unintentional defect. Please note the following guidelines regarding warranty service of
OutBack products:
manuals with specifi ed over-current protection in order to maintain their warranties.
and shipping paid. We recommend insuring your package when shipping. Packages that are not
securely packaged can sustain additional damage not covered by the warranty or can void
warranty repairs.
disconnect, service, or reinstall the damaged component(s).
nental United States, where applicable. Shipments outside the U.S. will be sent freight collect.
losses, expenses, or damage to other components.
Dear OutBack Customer,

The OutBack Power Systems MX60 PV MPPT Charge Controller is ETL listed to UL1741 (Inverters,
Converters, Controllers, and Interconnection System Equipment for Use with Distributed Energy
Resources). It is also in compliance with European Union standards EN 61000-6-1 and
EN 61000-6-3 (see page 89).
About OutBack Power Systems
OutBack Power Systems is a leader in advanced energy conversion technology. Our products
include true sine wave inverter/chargers, a maximum power point charge controller, system com-
munication components, as well as breaker panels, breakers, accessories, and assembled systems.
MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller: Installation, Programming
Copyright © 2007 All rights reserved.
UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER SYSTEMS:
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL
OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
January 29, 2007 REV 7.0 Software REV 5.10 and 5.11
19009 62nd Ave. NE





The manual provides safety guidelines and installation information for the MX60 PV MPPT Charge
Controller. It does not provide information about specifi c brands of solar panels and supplies
limited information on batteries. Contact the supplier or manufacturer of the solar panels or
batteries for further information.
MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller
The OutBack MX60 PV MPPT Charge Controller off ers an effi cient, safe, multi-stage recharging
process that prolongs battery life and assures peak performance from a solar array. This
component allows customized battery recharging. The MX60 features include:
The following are the maximum recommended wattage for the most common solar arrays under
Standard Test Conditions (1000 watts per square meter of solar panel at 25° C or 77° F):
The MX60 also features Maximum Power Point Tracking (MPPT), which seeks out the maximum
power available from a solar array and uses it to recharge the batteries. Without this feature, the
solar array does not operate at the ideal operating voltage and can only recharge at the level of
the battery voltage itself. The MX60 “sweeps” the array’s operating voltage at user-determined
sweep intervals to track the Maximum Power Point (MPP) of the PV array.
This manual covers the wiring, installation, and use of the MX60, including explanations of all the
Menus displayed on the LCD screen. The MX60 is designed to seamlessly integrate with other
OutBack components and can be remotely monitored (up to 1000 feet) by the optional OutBack
Power Systems MATE display.

This product is intended to be installed as part of a permanently grounded electrical system
as shown in the system confi guration sections of this manual with the following important
restrictions:
the system. If a GFP is present, the battery negative and ground are not bonded.
(see page 61, Applications Notes).
qualifi ed service center. Please contact your renewable energy dealer/installer for assistance.
Incorrect reassembly risks malfunction, electric shock or fi re.
not be exposed to rain and should be installed out of direct sunlight.
XDisconnect all circuit breakers and related electrical connections before doing any cleaning
or adjustments.
XSolar modules may produce hazardous voltages when exposed to light; unless
servicing them at night, cover the modules with opaque material before servicing any
connected equipment.
All installations must comply with national (NEC) and local electrical codes; professional installation
is recommended.
DC and Battery-Related Installation Requirements:
reduce performance and possibly damage the unit).
currents to cancel.
both breakers and fuses for over-current protection.
Standards and Requirements

BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION. Design the
battery enclosure to prevent accumulation and concentration of hydrogen gas in “pockets”
at the top of the enclosure. Vent the battery compartment from the highest point to the
outside. A sloped lid can also be used to direct the fl ow of hydrogen to the vent opening.
calcium, gel cell or absorbed glass mat type rechargeable batteries. Other types of batteries
may burst, causing personal injury and damage. Never charge a frozen battery.

Maximum Open Circuit Voltage (Voc)
X 141 VDC J MX60 suspends operation to protect components
X 150 VDC J max open circuit voltage with the coldest environment (although the MX60
shuts down at 141 VDC, it can absorb up to 150 VDC from the array; anything higher than 150
VDC will damage the MX60)
X Allow for ambient temperature correction using the following table:
25° to 10° C (77° to 50° F) multiply by 1.06
9° to 0° C (49° to 32° F) multiply by 1.10
-1° to -10° C (31° to 14° F) multiply by 1.13
-11° to -20° C (13° to -4° F) multiply by 1.17
-21° to -40° C (-5° to -40° F) multiply by 1.25
X Check the PV array voltage before connecting it to the MX60.
ductors; a larger size might be required due to temperature and/or conduit fi ll corrections.
amps STC (Standard Test Conditions).
PV array. OutBack OBDC 100% duty continuous breakers only need to be rated at 1.25 times the
short-circuit current.
other suitable conductor/wire sizing.

Figure 1 Field Wiring Connections and Surge Protection

Use up to 2 AWG wire and torque to 30-inch pounds at terminals.
Battery Remote Temp Sensor (RTS) RJ11 jack
Programmable AUX Output Jack (supplies up to 200mA @ 12 VDC
If attaching to plywood, use a 1 5/8” wood screw to secure the MX60 at the top slotted hole and other screws as needed at interior bottom holes. PV+ PV- BAT- BAT+ Four-Position Terminal Block
The PV (-) and BAT (-) terminals are connected internally. Only one negative wire may be needed
to connect to the Four-Position Terminal Block if the PV - and BAT- conductors are bonded at the
negative bus bar. See Figures 2 and 3 for sample wiring diagrams.
MATE/HUB RJ45 jack · Chassis/Equipment Ground Lug

battery recharging (only one RTS is needed for multiple OutBack Series Inverter/Chargers
and MX60 units when an OutBack HUB and a MATE are parts of the system). When one RTS
is used, it must be connected to the component plugged into the Port 1 of the HUB.
extended warranty protection. A dwelling rooftop array requires ground fault protection
(OutBack OBDC-GFP/2 recommended).
installation and to retain warranty protection. Use a 1 5/8” wood screw through the slotted
hole at the top of the MX60 and at least two screws in the internally located holes at the
bottom of the MX60’s enclosure.









Figure 2 MX60 WIRING DIAGRAM WITHOUT A GFP/2, the ground conductors tie into the negative
terminal bus bar.








Figure 3 MX60 WITH GFP/2 WIRING DIAGRAM The GFP/2 requires a separate ground bus bar.

Soft keys:
(#1) (#2) (#3) (#4)
Solid black indicates key is to be pressed:
Down arrow will lead to the next screen:
Up arrow points to one or more keys that will change a value:
The keys correspond to any text immediately above them.

The MX60 power-up sequence fi rst activates the unit and brings up a series of screens; some
screens allow the user to change the battery voltage.
OFF SCREEN (this screen is initially blank at power up)
With the PV array and battery breakers off , press and
hold soft keys #1 and #3 and then turn on the battery
breaker (see Figure 4).

reads “Got Battery?” please see the Troubleshooting Guide on page 74.
Battery Breaker

Release both soft keys when the OutBack Power
OutBack 12V Power Systems MX60
Systems screen appears. The selected battery voltage
appears in the upper righthand corner. The BATTERY
VOLTAGE screen will appear next.
will read MX60AU for Australian versions and MX60ES
for Spanish versions.
“^^” indicates the selected battery voltage. Press
BATTERY VOLTAGE 12 24 36 48 60 ^^ EXIT J ENTER
the “J” or soft keys to proceed to the
PASSWORD screen, which prevents unauthorized
changes to the system.
Press the “ – “ soft key until the password 141 shows
on the screen. Press the soft key to return
to the BATTERY VOLTAGE.
displayed on a screen.

Press the “J” soft key to select a battery voltage. The
BATTERY VOLTAGE 12 24 36 48 60 ^^ EXIT J ENTER
MX60’s default values are based on a 12 VDC system.
Selecting a higher voltage system will change all the
default values (e.g., the values will double with a 24
VDC system, triple with a 36 VDC system, etc.). “^^”
indicates the chosen voltage. The MX60 will automat-
ically accept the selected battery voltage if left unat-
tended for 5 minutes in this screen. After choosing
the voltage, press the soft key to proceed.
Press the soft key to proceed if the selected
Are you sure? 12 24 36 48 60 ^^ NO Yes
battery voltage is correct. If incorrect, press to
re-enter the correct voltage.
The MX60 briefl y returns to the Power-Up screen and
OutBack 12V Power Systems MX60
then automatically opens the STATUS screen which
displays information regarding the recharging status.
Confi rm the battery voltage displayed in the upper
right corner is correct.
Battery Voltage Screen · Verifi cation Screen · Power-Up Screen

The STATUS Screen displays system information. See page 67 for detailed information of the dif-
ferent Operational Modes. The optional OutBack MATE displays MX STATUS screens for convenient
distant viewing from the installation location of the MX60. Please see page 71 to view the MX
screens displayed on the MATE.
The PV voltage will slowly rise to the battery
voltage level even when the PV breaker
is off – this is normal as the PV capacitor
charges up.
PV 005 V Bat 12.5 V 00.0 A 00.0 A Watts 0000 Aux Off kWHrs 00.0 Sleeping
Aux. Status (ON or OFF)

Turn the PV input breaker on. The MX60
PV 113 V Bat 12.5 V 00.0 A 00.0 A Watts 0000 Aux Off kWHrs 00.0 Sleeping
automatically detects the PV input voltage.
is on, please check the polarity of the PV wires.)
After 5 seconds of stable input voltage, the MX60
PV 087 V Bat 12.5 V 05.0 A 32.9 A Watts 0412 Aux Off kWHrs 00.0 B-MPPT
enters a “Wakeup” stage, transitions to “Sweeping”
and prepares to charge the batteries by tracking the
MPP of the solar array.

The MAIN Menu allows the user to adjust and calibrate the MX60 for maximum performance.
From the STATUS screen, press soft key #1 to open the MAIN Menu screen.
Press the soft key after aligning the asterisk
*Charger Aux Light EQ Misc Advanced Logging Log2 EXIT I J GO
in front of the selected menu choice.
Pressing the soft key in the MAIN Menu
returns to the STATUS Menu. Press the soft
key in your chosen menu to return to the STATUS
screen.
Press I or J to move the asterisk “*” to the left of the desired screen. The asterisk allows access to any screen to its right.
From the MAIN Menu, a user can choose among the following MX60 functions by aligning the
asterisk:
XAdjusts the Current Limit, Absorb, and Float recharging voltage set points
XSecondary control circuit for a vent fan, error alarm, and other system-related additions
XAdjusts the backlighting of LCD screen and soft key buttons
XActivates battery equalization recharging (manually or automatically)
XAdditional settings and service information
XOptimizing/fi ne-tuning the MX60 (these are advanced Menus that should be left alone until
the user has a good working knowledge of the MX60 and its operations)
XDisplays recorded power production information
XDisplays recorded peak system information

This screen allows changes to the MX60’s recharging voltage set points (Current Limit,
Absorb, Float):
70 amps, a 70A or 80A breaker must be used between the battery and the MX60.
dations are diff erent than the default values. Otherwise, see page 79 for suggested recharging
voltage set points.
viewed in the MISCELLANEOUS (Misc) screen under the Tmp Comp heading.
LIMIT ABSORB FLOAT Amps Volts Volts *60.0 14.4 13.6 EXIT J - +
and FLOAT setting voltage based on a 25°C / 77°F
setting. These are typically the manufacturer’s set
points (always consult the battery manufacturer’s
recommendations). If an RTS is not in use, please
see the Non-Battery Temperature Compensated
System values (page 85) and adjust the ABSORB/
FLOAT values accordingly.

The AUX is a secondary control circuit—essentially, a small power supply that provides a 12 VDC
(up to 200 milliamps) output current. It is either active (12 VDC on) or inactive (12 VDC off ).
front of the Aux selection.
put DC loads require a 12 VDC coil relay—also rated up to 200 milliamps or less for the DC
coil—which itself is connected to the AUX output. An internal, re-settable Positive Temperature
Coeffi cient (PTC) fuse protects the AUX internal components.
benefi cial with applications such as the Diversion mode where fast switching (often called PWM
control) allows a more constant battery voltage to be maintained. Both DC and AC load
switching solid state relays are widely available from many sources. Eurotherm and Power-IO
are two suggested solid state relay manufacturers.
infrequently used.
In this Menu, ON and
The second line indicates
OFF indicators show the
the present mode for the
Manual Off EXIT NEXT ON OFF
present state of the Aux
Aux Output.
terminals. Pressing the
or soft key
When the preferred mode
changes this value.
is displayed, press the
soft key to select
ON indicates 12 VDC is
it.
present at the Aux output
Pressing the soft key changes to the next mode.
terminals. OFF indicates
0 VDC.
Terms

*Charger Aux Light EQ Misc Advance Logging Log2 EXIT I J GO
Charger *Aux Light EQ Misc Advance Logging Log2 EXIT I J GO
Manual On EXIT NEXT ON OFF
PASSWORD
AUX MODE
Manual Off EXIT NEXT ON OFF
J
screen becomes active, requiring the user to input the 141 PASSWORD and press< ENTER>. This
screen will also appear after fi rst booting up the MX60 even though the password was entered
when setting the battery voltage.
AUX MODE
AUX MODE
Vent Fan Off EXIT NEXT VOLT
PV Trigger Off EXIT NEXT TIME VOLT
Float Off EXIT NEXT
AUX MODE ERROR ALARM On EXIT NEXT
AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT
Diversion Off EXIT NEXT TIME VOLT
AUX MODE
PV 005 V Bat 12.5 V 00.0 A 00.0 A Watts 0000 Aux Off kWHrs 00.0 Sleeping
Remote Off EXIT NEXT
AUX MODE Path · ***150***

AUX modes in order of appearance on the MX60 display:
The most commonly used AUX modes:
When an AUX MODE is ON, 12 VDC is available at the AUX terminals and a condition, such as a
voltage set point, is met. Other modes can be programmed in lieu of the specifi c ones listed here,
but the Vent Fan mode is most easily changed (e.g., to activate an alarm instead of a fan). Here are
the default AUX modes:
15 seconds (the fan helps remove hydrogen from battery enclosure), even if the set point is
exceeded for only a few seconds due to a surge. If the set point is exceeded for longer than 15
seconds, the fan will stay on until the voltage drops below the set point. It then takes 15 seconds
before the fan shuts off . This is an external fan and not to be confused with the MX60’s internal,
thermally activated fan which cools the unit.
high and exceeds the user-determined voltage set point (should not go over 150 VDC), the PV
Trigger disconnects after a minimal adjustable amount of “Hold Time.”
charged the batteries for 26 hours or more (not an audible alarm, only displayed as a printed
message on MX60 AUX Menu).
nected directly to the batteries.
and time levels are reached.
for details).

Programming the AUX MODES
Press the or soft keys to manually
activate or deactivate AUX MODE. Press the
Manual On EXIT NEXT ON OFF
soft key to view the Vent Fan screen. To view other
screens, continue to press the soft key.
The Vent Fan helps remove hydrogen from the bat-
tery room. The ventilation fan referred to here is not
Vent Fan On EXIT NEXT VOLT
the same as the MX60 cooling fan. Press the
soft key to determine the battery voltage that will
activate the AUX MODE and start the fan.
Adjust the voltage level using the < - > and < + >
soft keys. Press the soft key to return to the
Vent Fan screen.

Press the soft key to advance to the PV
Trigger soft screen.
Vent Fan On EXIT NEXT VOLT
When the PV input is too high and exceeds the
user-determined VOLT set point, the AUX MODE PV
PV Trigger Off EXIT NEXT TIME VOLT
Trigger activates. Press the soft key to adjust
the voltage.
Adjust the voltage within a range of 20V - 150V
by pressing the < - > or < + > soft key. Press the
soft key when fi nished to return to the PV
> 140 · Trigger screen

To adjust the minimum amount of time the PV volt-
age must remain high before deactivating the AUX
PV Trigger On EXIT NEXT TIME VOLT
MODE, press the soft key.
Press the < - > or the < + > soft key to adjust the
Hold Time, then press the soft key to return
to the PV Trigger screen. In this example, the AUX
MODE will remain active for 1.1 sec after the PV volt-
age is below the PV Trigger voltage before deactivat-
ing the PV Trigger and reconnecting to the array.
Press the soft key to view the Float screen.
PV Trigger Off EXIT NEXT TIME VOLT
The AUX MODE is active when the MX60 is in Float
and producing power. Press the soft key to
Float Off EXIT NEXT
advance to the ERROR ALARM screen.
Hold Time Sec

The default state of the ERROR ALARM is On,
AUX MODE ERROR ALARM On EXIT NEXT
meaning 12 VDC is present at the AUX terminal. If
the MX60 has not charged the batteries for 26 hours
or more continuously, the inaudible ERROR ALARM
goes into an Off state. The ERROR ALARM is intended
for remote locations to signal (e.g., a telecommunica-
tion signal to a computer) when the MX60 has not
recharged for 26 hrs or more. See MISCELLANEOUS
Screen 3 Err for a display of the hourly countdown.
Press the soft key to advance to the
Diversion screen.
When external DC sources (wind, hydro) are directly
connected to a battery bank, any excess power
Diversion Off EXIT NEXT TIME VOLT
should be sent to a diversion load, such as a heating
element. In Diversion, the user programs set points—
from -5.0 volts to 5.0 volts relative to the Absorb,
Float and EQ voltages—to activate the AUX MODE.
This is primarily an off -grid function. Pressing the
soft key advances to the Absorb-Float-EQ
screen to adjust the voltage set points.
Use this screen to establish the set points for starting
and ending the AUX MODE relative to the Absorb,
Relative Volts 00.0 00.2 BACK - + HYST+
Float, and EQ voltages. The < - > and < + > soft keys
set the Diversion set points. The (Hysteresis)
set point establishes when the AUX MODE becomes
inactive after the battery voltage falls below the
Relative Volts voltage minus the HYST value. After
establishing these values, press the soft key
to return to the Diversion screen (see example on
next page).
Absorb—Float—EQ

Press the soft key to advance to the Time
screen which allows the user to adjust the minimum
Diversion Off EXIT NEXT TIME VOLT
time the AUX MODE is active after the battery volt-
age falls below the Hysteresis voltage.
Hold Time shows how long the AUX MODE stays
active after the battery voltage has fallen below the
Hold Delay 01.0 Time 00 seconds BACK - + DLY+
HYST (Hysteresis) set point. The user can adjust the
Hold Time from 0.1 to 25 seconds. If a solid state relay
is used, set the Hold time to 0.1 seconds and the
Delay time to zero.
The Delay Time shows how long the battery voltage
must be above the Relative Volts before the AUX
MODE is activated. It can be adjusted from 0 to 24
seconds, but is rarely required. Pressing the
soft key returns to the AUX MODE DIVERSION screen.
Hold Delay 15.0 Time 10 Seconds BACK - + DLY +
Diversion Off EXIT NEXT TIME VOLT
Each recharging state—Absorb, Float, or EQ—has a recharging voltage set point. The Diversion
AUX MODE can be active (On) when the battery voltage is raised above one of these set points
for a certain amount of time or inactive (Off ) when it falls below. The user can determine these
voltages and times. In the example above, when the RE source (wind or hydro) raises the battery
voltage 00.2v above the chosen set point for a Delay time of 10 seconds—the AUX Output will be
active. When the battery voltage falls 00.3v below the HYST voltage set point for a Hold time of 15
sec – the AUX Output will be inactive (Off ). See Figure 5 for Diversion Load and AUX Wiring Set-Up.
Example of Diversion · Absorb—Float—EQ · Relative Volts








Figure 5 Diversion Load and AUX Wiring Set-Up Illustrated

Press the soft key to view the Low Batt(ery)
Disconnect screen.
Diversion Off EXIT NEXT TIME VOLT
When the battery voltage falls below the disconnect
AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT
volts, the AUX connected loads only are disconnected;
the loads are On when the battery voltage rises
above the reconnect volts. To adjust these set points,
press the and soft keys.
Press either the < - > or < + > soft key to adjust the
Delay Time Sec 01 Timer 001 BACK - +
delay time. This is the time period the MX60 waits
before either activating or deactivating the AUX
MODE when either the disconnect or reconnect volt-
ages are reached. When the low voltage occurs, the
timer shows the seconds remaining before discon-
necting. When the reconnect voltage is reached, the
timer shows the userdetermined time before con-
necting. Press the soft key to return to the
Low Batt Disconnect screen.

In the Low Batt Disconnect screen, press the
AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT
soft key to adjust the battery voltage disconnects
set point.
Press either the < - > or the < + > soft key to adjust
the disconnect voltage. Press the soft key
to open the RE-CONNECT VOLTS screen.
BACK - + ReCon
Press either the < - > or the < + > soft key to adjust
the RE-CONNECT VOLTS value. The AUX Output
>14.4
activates when the voltage goes above this setting
BACK - + DisV
after the timer has counted back to zero. Press the
soft key to return to the Low Batt Discon-
nect screen.

Press the soft key to view the Remote
AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT
screen.
In Remote AUX MODE, the OutBack MATE can control
the MX60’s AUX MODE. Press the EXIT soft key twice
Remote Off EXIT NEXT
to return to the MAIN Menu screen.
Press the soft key to move the asterisk to the
Charger *Aux Light Eq Misc Advanced Logging Log2 EXIT I J GO
Light option. When the asterisk is in front of Light,
press the soft key.

AUTO (default) leaves backlight and soft keys on for
60 seconds whenever any soft key is pressed (press-
ing any soft key when the LCD is not lighted does not
change any settings).
ON or OFF states are also available.
Press the #1soft key twice to return to the MAIN
Press the soft key to move the asterisk to the
Charger Aux *Light EQ Misc Optimize Logging Log2 EXIT I J GO
EQ option. When the asterisk is to the left of EQ, press
the soft key.
The intent of an equalization charge is to bring all battery cells to an equal voltage. Sealed batter-
ies should not be equalized unless specifi cally instructed by the manufacturer. Shut off or minimize
all AC and/or DC loads when equalizing and be sure the EQ voltage will not damage any DC load.
If possible, ensure the EQ cycle starts and stops the same day it is initiated or unnecessary battery
gassing can occur.
Menu screen

Press either the < –EQV> or soft key to
change the EQ voltage, following your battery man-
ufacturer’s recommendations. Note that the factory
default EQ voltage is set low, the same as the factory
default Absorb voltage. Press the soft key to
view the BATTERY EQUALIZE Time screen.
Press either the or soft key to set
the desired equalization time, up to a seven hour
Time 01 Hours EXIT NEXT -HRS +HRS
maximum, always following your battery manufac-
turer’s recommendations. Press the soft key
to view the battery equalization start screen
BATTERY EQUALIZE 01 Hrs 15.0 Volts Check water level BACK AUTO START STOP
an equalization cycle. To stop the cycle, press the
soft key.
reach the target equalize set point.
after the equalize set point is reached.
the next day unless the MX60 is powered off or
manually stopped. The remaining EQ time can be
viewed in the Log2 Menu.
reached.
and a Float cycle begins.
Press the soft key to view the auto equaliza-
tion screen.
Volts · Manual Mode

Use the and soft keys to preset
the interval day to initiate an automatic equalization
cycle. The EQ INTERVAL displays the number of days
in the interval between cycles and COUNT displays
how many days of the interval have passed.
manually stopped. The remaining EQ time can be viewed in the Log2 Menu.
been powered off .
screens, press the #1 soft key.
To view the MAIN EQ screens, press the #1 soft key.
Auto Mode

The MISCELLANEOUS screens display extra settings and technical information, some of which is
useful for OutBack Power Systems Technical Services.
The Grid Tie (GT) value is sent from G-
Each MPPT operation is
This is the duty cycle of
series inverter through the MATE and
a state. This number
the converter. At 50%,
HUB for Grid Tie control communica-
is useful for OutBack
the PV terminals would
tions. GT X means MX60 is in grid tie
troubleshooting.
be twice the battery
mode and communicating with the G
voltage.
Series Inverter.
GT State PWM% ChgT 255 07 50.0 005 Tmp Comp a14.4 f13.6 EXIT NEXT WIDE RSTRT
and Float (f) set points
up in Bulk and counts
rise and fall with tem-
down in Absorb.
perature. If no RTS is used,
these settings will be
the same as those in the
charger setting screen.
This soft key covers normal and
RSTRT forces the MX60 to restart or
wake-up from 5- minute (default)
voltage range. Press WIDE and
long Snoozing mode. Restart and
Screen.
LMIT mode appears, which limits
wakeup are mainly service features.
the Upper and Lower battery-
compensated voltage range.

During cold weather, a battery often requires a higher recharging voltage. Lower quality inverters
might not accommodate these higher voltages and can shut down during recharging, cutting off
power to their loads. The MX60 allows the user to lower the compensated voltage in the Absorb
cycle so these inverters will remain operating. Also, some batteries have an absolute voltage limit
that should not be exceeded and the WIDE/LMIT option allows the user to control this during re-
charging. WIDE allows the RTS full control over recharging; LMIT sets the ceiling and fl oor voltages
for the RTS.
During hot weather, the LMIT feature set point assures recharging will continue at a high enough
voltage rather than dropping too low in reaction to a higher ambient temperature. This assures
the recharging voltage adequately charges, but should be monitored according to the battery
manufacturer’s recommendations.
The RTS default compensated voltages apply if the WIDE/LMIT option is set to WIDE in the MISC
menu. The upper and lower LMIT settings can be viewed in the second menu of the Log2 screen
when LMIT is selected.
The LMIT set points can be set in the AUX MODE menu. To set the LMIT upper and lower set points,
press the #1 soft key once and return to the MAIN Menu. From the MAIN Menu, access the AUX
MODE screens and then the Low Batt Disconnect screen.
Path for Setting the LMIT Upper and Lower Set Points using AUX:
*Charger Aux Light EQ Misc Advance Logging Log2 EXIT I J GO
Charger *Aux Light EQ Misc Advance Logging Log2 EXIT I J GO
AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT
BACK - + ReCon
Press until Low Batt Disconnect appears, then press

Setting LMIT Upper and Lower Set Points
In the DISCONNECT VOLTS screen, press the < -> or
soft key to adjust the battery voltage range
limits. This should be the lowest Absorb voltage
when the battery temperature is highest. When the
desired low voltage is reached, simultaneously press
and hold the < - > and < + > soft keys until “Lower
Limit” displays on the screen. When “Lower Limit”
is displayed, the desired compensated voltage has
been stored, and the < - > and < + > soft keys can be
released (pressing the soft key will return to
the previous screen).
Press the soft key to adjust the upper
battery compensated voltage.
Press the < - > or < + > soft key to adjust the voltage.
When fi nished, simultaneously press and hold the
>14.8 BACK - + DisV
< - > and < + > soft keys until Upper Limit is dis-
played. This should be the highest Absorb voltage
when the battery temperature is coolest.

When the Upper Limit is displayed, the desired com-
pensated voltage has been stored and the < - > and
>14.8 Upper Limit BACK - + DisV
< + > soft keys can be released.
After setting these limits, AUX MODE should be set to
Manual (default setting) if not used.
Equalize charging mode.
Pressing the soft key returns to the Low Batt
Disconnect screen.
To confi rm the Upper Limit and Lower Limit voltages
*Charger Aux Light EQ Misc Advance Logging *Log2 EXIT I J GO
PkBatV Voc HiVoc 014.7 021.2 022.1 B-MPPT Sunrise EXIT NEXT 00:03:43
0000 fl oatTmin 0850 HighWatts Lo 13.2 Hi 14.8 BACK DCkWh
PkBatV Voc HiVoc 014.7 021.2 022.1 B-MPPT Sunrise EXIT NEXT 00:03:43
PV 011 V Bat 13.4 V 00.0 A 00.0 A Watts 0000 Aux On kWHrs 00.0 Sleeping
Limit Set Points (visible and active when WIDE/LMIT is set to LMIT in the Misc Menu)

After confi rming the Upper Limit and Lower Limit voltages, press the soft key in the MAIN
Menu. Press the soft key to advance to the fi rst MISC screen. From this screen, you can
access MISCELLANEOUS Screen 2.
From the MISC screen, press the soft key to
GT State PWM% ChgT 255 07 50.0 005 Tmp Comp a14.4 f13.6 EXIT NEXT WIDE RSTRT
view the FORCE, FLOAT, or BULK screen.
Pressing the or soft key forces the
MX60 to that specifi c recharging cycle and returns to
the STATUS screen. Forcing a FLOAT or BULK recharge
will end an EQ cycle. Press the soft key to
view the third MISCELLANEOUS screen.

This is the assigned number
Btmp is a battery temperature
increases hourly if the
sensor reference value used to
of the internal components
MX60 has not charged
compensate the charging volt-
to control the cooling fan. The
the batteries for 26+
age. This is an arbitrary number
lower the number, the higher
hours continuously.
between 0 and 255 and is not
the temperature. 25° C is ap-
The fi rst hour begins at
the actual temperature. An ‘X’
proximately a value of 525.
sleeping.
next to this value indicates a
Global external RTS is being used
(system with a HUB and MATE).
In Float, if the battery volt-
age falls below the ReBulk
voltage set point for at
PCB Err Btmp CFB 398 000 255 0760 ReBulk 06 V End 00 A EXIT +ReBV –AMP +AMP
of the internal cur-
least 90 seconds, the MX60
rent sensor is used
a Bulk charge cycle. The
default is set to a very low
value (6 volts) and there-
Power Point of the
fore the function will be
array.
disabled.
+ReBV increments the ReBulk
(End, -AMP, +AMP) Normally, an Absorb charge cycle is ter-
Voltage. It will return to a 6 volt
minated because the battery voltage was regulated at the
value when a 69 volt value is
Absorb set point for the maximum time period. Decreasing
reached.
(-AMP) or increasing (+AMP) sets an optional end current
level. While the battery voltage is at or above the Absorb
target and the End current level is reached at a time delay
of 15 seconds, the MX60 will switch to the Float charge
stage regardless of the charger time minutes. The charger
timer (ChgT) will be cleared. This is an optional set point
and its adjustment is not required in most installations. “00”
Absorb End amps is the default.

The ADVANCED MENU allows fi ne-tuning of the MX60 operations including “Snooze” periods and
Maximum Power Point limits. In order of appearance, the following modes occur in the ADVANCED
Menu selections:
XSnooze Mode XPark Mpp (% Voc) X MPP Range Limit % Voc X Sweep Interval XVbatt
Calibration XLow CutOff XMPPT Mode X Absorb Time Limits XWakeup Mode
From the MAIN Menu, choose Advanced and press
Charger Aux Light Eq Misc *Advanced Logging Log2 EXIT I J GO
the soft key.
The MX60 wakes up when an optimal amount of
open circuit voltage (Voc) is available. The Voc varies
with external conditions, primarily the weather and
time of day, which aff ect solar panels. If the Voc is
insuffi cient, the MX60 enters “Snoozing” until either
a fi ve-minute (default) period passes or there is a 1.5
volt (default) increase in Voc at which point the MX60
reevaluates the Voc for recharging purposes. What
is the optimal amount? The MX60 tries to recharge
when the Voc is greater than the battery voltage by 2
volts, but voltage alone isn’t suffi cient. An array might
have a big increase in voltage fi rst thing in the morn-
ing— more than 2 volts diff erence—but not enough
ampacity to recharge.
Snooze Mode < Lowcutoff EXIT NEXT MODE
Snoozing also occurs if the recharging current does
not reach the user-selected cutoff current set point in
the Lowcutoff menu. Press the soft key for
Snooze Mode options. Press the soft key for
the Park Mpp screen
during a full sweep
full sweep · full sweep · ongoing relay-clicking)

Auto Sweep MPPT Mode (see page 46) seeks the
solar array’s maximum available voltage to recharge
Park Mpp 77 % Voc EXIT NEXT -Voc +Voc
the batteries. The MX60 is best left in this default
mode for most recharging purposes. If the output
current is below fi ve amps (e.g., overcast day or early
mornings and late evenings), the MX60 will operate
at the percentage of the Voc shown on the Park Mpp
(Maximum Power Point) screen. The 77% Voc default
is close to the MPP for most arrays. A higher value
may be necessary for diff erent applications such as a
12 VDC array to a 12 VDC battery. To change the per-
centage of Voc, press either the or
soft key. Press the soft key to view the next
ADVANCED MENU screen.
The Mpp Range Limit % Voc adjusts the upper Mpp
ADVANCED MENU Mpp Range Limit %Voc min max EXIT NEXT 1/2 90%
limit of the Voc. The default MX60 MPP voltage limit
is set at 90% of the Voc and is normally left alone for
an array. If an MX60 sweep fi nds an MPP voltage out-
side of this range, it will revert to the Park Mpp value.
Setting to 1/2 reduces the initial sweep time on a
high input voltage array.
The MPP adjustable MX60 limits are 80%, 85%, 90%,
Use ½ value for high input arrays to speed up initial sweep.
and 99% of the Voc. The min range limit setting may
be set to FUL if something other than a PV array is
connected to the input of the MX60, such as a Micro-
Hydro generator (see page 54), but the Voc cannot
exceed 150 VDC at any time. Press the or
soft key to adjust the MPP range limit. When
done, press the soft key to view the Sweep
Interval screen.

The Sweep Interval mode or mini-sweep deter-
mines how often a sweep occurs, ranging from 0-15
Sweep Interval 07 Minutes EXIT NEXT -MIN MAX+
minutes. A sweep is a search for the best MPP for the
array. At zero minutes, the MPPT mini-sweep function
is disabled (this is not recommended for PV arrays).
No sweeping occurs if the output current is under
fi ve amps because it operates at the Park Mpp value.
Sweeping does occur when the output current is
higher than fi ve amps or to maintain user current
limit and to track the MPP of the array throughout
the day. A mini-sweep is an accurate but less exten-
sive version of the full initial sweep done at wakeup.
Press the soft key to decrease minisweep
interval minutes or press the soft key to
increase the minutes. Press the soft key to
view the Vbatt Calibration screen.
A quality calibrated voltmeter will provide even more
accurate MX60 battery voltage readings if an un-
Vbatt Calibration 12.8v 0.0v EXIT NEXT -V +V
desirable voltage drop is present. When measuring
battery voltage, ensure a good connection is made
to the Four-Position Terminal Block. Check the bat-
tery temperature compensation voltages if voltages
are much diff erent than you expect from the charger
setup Absorb and Float voltage settings. Use the
The present Vbatt meter reading is displayed here for convenience.
and soft keys to match the readings from
the voltmeter. When fi nished, press the soft
key to view the next screen.

Low Cutoff sets the battery charger’s lowest allow-
ADVANCED MENU Low Cutoff < .6 Amp EXIT NEXT +AMP
able current limit the MX60 will charge in MPPT
mode before stopping and returning to “Snoozing.”
The Low Cutoff is adjustable from .2 amps to 1 amp;
.6 amps is the default Low Cutoff current. Raising
this value will assist the MX60 in entering “Sleeping”
mode at night. Press the soft key to raise
this limit. When fi nished, press the soft key
to view the MPPT Mode screen.
This screen allows the user to choose one of these
modes:
MPPT Mode Auto Sweep EXIT NEXT nonGT MODE
mode), which sweeps the PV upon wakeup and
then does mini Sweeps from that point on at the
selected Sweep Interval. If the sweep interval is set
at 0 minutes, the MX60 awakes every 1.5 hours and
does a full sweep. Auto Restart applies here as well
(see LOG2 Auto Restart, page 52).
The default value is nonGT or non-grid-tied. Select GT mode if you have a GVFX or GTFX inverter, MATE and HUB connected to the MX60. Selecting GT estab- lishes the proper grid-tie mode communications between the G-series FX and the MX60.
at a user-selected percentage of the Voc which is
displayed in the Park Mpp % Voc screen. U_Pick %
acquires a new Voc value every Sweep Interval. If
the mini-sweep interval is set to 0 minutes, a new
Voc may be acquired once every 1.5 hrs. depend-
ing on the Auto Restart setting (see LOG2 Auto
Restart, page 52). This is an alternative to the Auto
Sweep mode and may also be useful for micro-hy-
dro applications.
Press the soft key to choose an MPPT
mode and the soft key if you have an Out-
Back G-series inverter system with a HUB and MATE.
Press the soft key to view the Absorb Time
Limits screen

In the Absorb Time Limits screen, the user can set the
ADVANCED MENU Absorb Time Limits 000m 2hr EXIT NEXT MIN+ MAX+
minimum and maximum times the MX60 stays in the
Absorb recharge cycle.
J MAXimum is adjustable from 0 to 4 hours.
J MINimum is adjustable from 0 minutes (the
default) up to the maximum absorb time limit
2 hours or 120 minutes Minimum Absorb time
adjusted up to 110 minutes)
To adjust the limits, press either the or
soft key. When fi nished, press the
soft key to view the next screen.
limit (zero minutes) while the Bulk/Absorb Charge Timer counts up in minutes.
tain this set point, employing the F(Float)-MPPT function.
will stop counting down and begin counting up towards the Max Absorb time as the MX60
transitions to Bulk (BMPPT). This up and down counting will continue until the charge timer counts
down to zero. The Absorb cycle can be disabled by setting the maximum to 0hr.
BULK
S N O O Z E
ABSORB
FLOAT
Z Z Z Z SLEEP
PV ARRAY VOLTAGE
SLEEP
Z Z Z Z
XBulk cycle begins XAbsorb charge is reached XAt zero, MX60 goes into FLOAT X Timer starts XTimer begins counting to zero
timer’s set points.

Wakeup Mode selects how often the MX60 does a
“Wakeup” during “Snoozing” periods. Since environ-
Wakeup Mode 01.5v 05m EXIT NEXT +VOC +Min
mental condition impact the open circuit voltage
(Voc) of an array, a user selectable Voc rise in value
will allow the controller to “wakeup” sooner or later
based on the last measured Voc value. A selectable
delay time in minutes will also allow the control-
ler to “Wakeup” sooner or later if the measured Voc
did not meet the user selectable Voc rise in value.
Before changing these values, monitor your system
for a week or so using the factory defaults and then
gradually adjust the set points. If they’re set too high,
the MX60 might not wake up soon or often enough,
which means a loss of power production. Note:
+VOC ranges from 1.5V up to 9.5V. +MIN ranges from
5 up to 15 minutes. Press the soft key to
return to the MAIN Menu.
From the MAIN Menu, press the soft key to
Charger Aux Light Eq Misc *Advanced Logging Log2 EXIT I J GO
move the asterisk next to the Logging function and
then press the soft key.

The MX60 records battery fl oat and daily kilowatt-hour (kWh) information for the previous 64 days.
This data can be compared, for instance, with weather reports to confi rm the MX60’s performance.
When 64 days are reached, for every new day of data recorded, a day is eliminated from the front
end of the count in the order they were recorded.
The minutes the MX60
spent fl oating the bat-
may be viewed as amp
teries for each of the
last 64 days. The pres-
ent day’s Float time can
setting in the STATUS
be found in the Log2
DAILY KWhours 00.0 Float time mins 0000 TotalKWh 0000 01 EXIT CLR +DAY -DAY
screen. The TotalKWh or
screens.
the daily values and
Day 01 is yesterday and
Day 02 is two days ago,
days of data.
etc.
Pressing CLR takes you to the CLEAR,
DALY (DAILY), and TOTL (TOTAL) Menu
goes forward one day
and EXIT takes you back to the main
STATUS screen.
If starting on Day 01 and +DAY is pressed, the
value from 64 days ago is presented.
Pressing and holding the TOTL or DALY (TO-
TAL AND DAILY) soft key will prompt you to
erase those total accumulated values. Press-
ing BACK returns to the Logging screen.

Clearing Totals and Daily Stats
to clear the total accumulated kWh and kAh statistical values in the MX60.
all of the 64 Daily logged values. After Yes is confi rmed, the values will be cleared. It may take a
few seconds for all 64 daily values to be cleared before the confi rmation screen goes away.
diff erent days, their numeric dates will not be the same. This can lead to some misunderstand-
ings when looking back and comparing data between the two or more units. A user looking
back at day 12 on both units would fi nd very diff erent results.
To return to the MAIN Menu, press the #1 soft key from any screen.
From the MAIN Menu, press the soft key to
move the asterisk next to the Log2 function and then
press the soft key.

The Log2 screen displays additional voltage and time information.
Daily high Voc value
The highest Voc seen by the MX60
Sunrise shows how long
PkBatV Voc HiVoc 012.2 070.2 076.9 B-MPPT Sunrise EXIT NEXT 00:06:12
ago the MX60 woke up
for the fi rst time each day
and when the daily and
total logged values were
updated and cleared from
the STATUS screen.
Pressing and holding the #3 soft key
toggles 24/25 hour save mode. Soft key
#4 addresses Auto RESTART mode.
PkBatV logs the peak battery voltage and operational mode simultaneously, updating daily at fi rst
wakeup; it can also be reset to the present battery voltage by powering off the controller. This
helps determine any degree of voltage overshooting. The peak battery voltage should not be used
to identify that the controller has charged the battery to a higher voltage than its regulation set
mode until the controller wakes up.
Daily peak · battery voltage · Operational mode

Pressing and holding the #4 soft key for several
PkBatV Voc HiVoc 012.2 070.2 076.9 B-MPPT Sunrise EXIT NEXT 00:06:12
seconds selects among the three MX60 Auto
allows the MX60 to perform internal recalibrations
and eliminate any possibility of software errors. To
change the mode, release the #4 soft key and press
and hold again.
MX60 recharges continuously from an available
source and never Restarts. Mode 0 would be
chosen to avoid spinning a microhydro generator
every 1.5 hours.
in Bulk, it will briefl y Restart and initiate a full panel
sweep. This will not reset any counters or charging
stages or statistics.
Absorb, and Float modes, it will briefl y Restart and
initiate a full panel sweep. This will not reset any
counters or charging stages or statistics.
The MX60’s sunrise-related activity can be infl uenced. During certain days of the year, the sun
never “sets” in parts of Alaska, for instance, and the PV output is constant. The MX60 responds to
these situations by generating its own sunrise reading at either 24 or 25 hours with 25 hours being
the default value. After this 24 or 25 hour period, the MX60 automatically initiates a BULK cycle and logs
the daily KiloWattHour / AmpHour statistics and Float Time to be logged and accumulated in the
Logging screen. Pressing down and holding the third soft key, then releasing and pressing and
holding again for a few seconds, will toggle the value between 24 and 25 hours. Mini-sweeps at
the selected sweep interval will initiate on time in either of these modes. Press the soft
key to view the secondary Log2 screen.
After 3 hours of sleeping, the MX60 displays “Zzzz….” This means that the next wakeup will cause
the daily KiloWattHour / AmpHour statistics and Float Time to be logged and accumulated in the
Logging screen. This (the next wakeup) will also initiate a Bulk charge cycle.

The Secondary Log2 screen shows the basic recharging state of the MX60 (EQ, FLOAT) time in min-
utes, and the daily maximum (HighWatts) wattage seen by the MX60 during the day.
The present day’s time—
displayed here.
Float stage.
0000 fl oat Tmin 0705 HighWatts Lo 13.2 Hi 14.8 BACK DCkWh
The lower and upper
This value is the peak
daily Watts seen by the
MX60.
is visible and active
mode is set to LMIT
(5.11 Rev.).
Press soft key #3 to display the accumulated total
kWh reading in AC or DC the Data
Logging screen.
should be used in a non grid tied system.
heading in the logging screen will change to
“TotalKWh AC”. TotalKWh AC is based on a 90%
inverter effi ciency (1kWH DC = 0.9kWH AC).
power source keeps the battery above fl oat voltage.

The MX60 is designed to work with solar arrays. Although it will work with micro-hydro and fuel
cell, OutBack Power Systems can only off er limited technical support for these applications be-
cause there is too much variance in micro-hydro and fuel cell generator specifi cations. When used
for micro-hydro or fuel cell applications, the MX60 warranty will be honored only if the manufac-
turer and turbine model have been approved by OutBack Power Systems. Please check with one of
the following manufacturers or OutBack Power Systems before employing the MX60:
Alternative Power & Machine
Energy Systems & Design
The MX60 is not compatible with wind turbine applications and OutBack cannot warranty its use in
these applications.
Micro-hydro and fuel cell systems are diff erent than PV systems, whose Voc output is more subject
to change due to weather and time of day. A PV system normally fi nds its Maximum Power Point
voltage between 50-90% of its Voc. The default value for the MX60 is 77% of a solar array’s Voc and
is displayed on the Park Mpp screen. A microhydro or fuel cell system’s MPP voltage can be outside
of this range.
The MX60 allows a user to experiment and fi nd more appropriate set points to best capture the
MPP voltage. If the output current is under fi ve amps, Auto Sweep will park the voltage using
whatever percentage value is displayed in the Park Mpp screen. Otherwise, Auto Sweep begins
sweeping the Voc output and works its way down until the optimum percentage of input voltage
yields the MPP voltage. If U-Pick % Voc is chosen, the MPP is calculated by whatever value is found
in Park Mpp, even if it’s not the optimal value for determining the MPP voltage. For this reason,
OutBack normally suggests leaving the system in Auto Sweep mode and the 77% default percent-
age value, but recommends experimenting with changing this value when a micro-hydro or fuel
cell system is in use.

To adjust these values and enhance the performance of these systems, use the MX60 ADVANCED
MENU to make changes. To determine your micro-hydro or fuel cell system’s best settings for MPP
voltage, do the following:
capacity.
watts value for each. This will require some experimentation.
screen in the ADVANCED MENU selection:
40%, 50%, 67%, 70%, 72%, 75%, 76%, 77%, 78%, 80%, 81%, 83% or 85% of the measured
determine an appropriate fi xed percentage value. Typical fi xed values between 67% up to
78% have provided optimal results; however, each system is diff erent and these fi xed
percentage values should be used as guidelines only
your system.
In addition to establishing the best mode and percentage values for determining the MPP voltage,
a user can also adjust the sweep interval and the range of values the MX60 uses to search for the
MPP voltage.
(If necessary, re-enter the system password 141 at any point while optimizing the
system’s performance.)
open circuit voltage

Mpp Range Limit % (Auto Sweep Mode only)
The MX60 searches for the MPP voltage by sweeping the input voltage up to one half (default) of
the Voc, which is based on values appropriate for a solar array. Micro-hydro and fuel cell systems
can require a broader range, normally on the lower end. Adjusting the lower limit, expressed as 1/2
on the display screen, for FULL allows the MX60 to sweep the input voltage close to the battery
voltage instead of 1/2 (or 50%) of the Voc.
This adjustment only aff ects the initial sweep at the beginning of the day and any subsequent sweeps
caused by Auto-Restart or any forced restart of the MX60.
In addition to adjusting the Mpp Range Limit, changing the Sweep Interval from its default three-
minute setting to zero minutes will also enhance the performance and reliability of some applica-
tions’ voltage input system.
To adjust the Lower Mpp Range Limit and disable the Sweep Interval:
From the MAIN Menu, with the asterisk in front of
Advanced, press the soft key. Charger Aux Light Eq Misc *Advanced Logging Log2 EXIT I J GO

In the ADVANCED MENU screen, press the
ADVANCED MENU Mpp Range Limit %Voc min max EXIT NEXT 1/2 90%
soft key until the Mpp Range Limit % VOC screen
appears. Press the soft key until FULL appears.
When fi nished, press the soft key to go to
the Sweep Interval screen.
In the Sweep Interval screen, press the soft
key to adjust the sweep interval from 03 minutes
Sweep Interval 03 Minutes EXIT NEXT -MIN MAX+
(default) to 00 minutes. Press the soft key
until the MPPT Mode screen appears.
To pick between Auto Sweep or U-Pick % MPPT
Mode and determine the MX60’s operating Voc per-
centage, press the soft key until the MPPT
Mode Menu appears.
Press the soft key to interchange between
Auto Sweep and U-Pick%Voc modes. Re-entering
MPPT Mode Auto Sweep EXIT NEXT nonGT MODE
the password might be required. Press the
soft key in the ADVANCED MENU until the Park Mpp
screen appears.

Press the or soft key to select one
of the 13 fi xed percentage values. Park Mpp applies
Park Mpp 77 % VOC EXIT NEXT –Voc +Voc
to Auto Sweep Mode if the output current is less
than 5 amps; U-Pick always uses the Park Mpp value.
Press the soft key until the MPPT Mode
screen appears.
new values.

In the STATUS screen, press the #3 and #4 soft keys
PV 087 V Bat 12.0 V 05.0 A 35.8A Watts 0430 Aux Off kWHrs 00.0 B-MPPT
simultaneously to perform a Mini-Sweep. The MX60
will track the new MPP based on the fi xed percent-
age value. Perform a Mini-Sweep any time a change
to the input system or the Park Mpp fi xed percent-
age value is changed. In U-Pick %Voc mode, press the
#3 and #4 soft keys and the New Voc is displayed; in
Auto Sweep mode, press the #3 and #4 soft keys until
Sweeping is displayed.
A user might want an MPP that falls outside of the fi xed percentages available in Park Mpp. With
the MX60, a user can manually adjust these values by single percentage points while observing a
change in the instantaneous watts made available with these adjustments.
To manually track and change the MPP voltage in either the Auto Sweep or U-Pick %Voc
MPPT Modes:
Press and hold the #3 soft key to decrease the power
PV 087 V Bat 12.0 V 05.0 A 35.8A Watts 0430 Aux Off kWHrs 00.0 B-MPPT
point voltage (PV voltage). Press and hold the #4 soft
key to increase the power point voltage (PV voltage).
Observe the changes in the Watts value to determine
whether increasing or decreasing the PV voltage will
improve the available power to the system.
Press either soft key to adjust PV voltage


OutBack Power System GTFX/GVFX Grid-tie settings
In a GFX/GVFX series inverter, MX60, HUB, and MATE installation set the MX60 to GT mode in the
ADVANCED MENU. The GT mode allows the GFX/GVFX series inverter to manage the MX60 fl oat
setting ensuring the MX60 is always keeping the battery above the sell voltage of the GFX/GVFX.
Grid-tie applications (non-OutBack inverter/chargers)
When selling electricity back to the grid, keep the inverter Sell/Float voltage below the MX60 fl oat
voltage. Appropriate values: 0.5 Volts diff erence for 24V battery system or 1.0 volt diff erence for 48V
battery systems.
Diversion using hydro or wind power
With wind or hydro generator applications, keep the MX60’s diversion voltage slightly above its
Absorb and Float voltages for effi cient functioning.
Telcom applications frequently require a positive grounded system. The MX60 switches the POSI-
TIVE PV and battery leads. Keep these separate. If code allows, ground ONLY the battery positive
lead in this case. Do not connect the MX60’s battery plus to the PV plus input while the MX60 is
running. The OutBack HUB cannot be used in a positive grounded system.
Battery temperature compensation with other slopes
The MX60 uses a -5mV per degree C per cell (2V) compensation slope required by UL. For other
slopes, you may be able to pick a diff erent battery voltage and change the charger Absorb and
Float voltage settings to achieve a more or less aggressive slope. If going lower in voltage, reduce
the Float voltage fi rst, since the Absorb voltage will not be adjustable below the Float voltage
setting. If going higher in voltage, increase the Absorb setting fi rst before raising the Float voltage
above the present setting. Here is a table of MX60 compensation based on system voltage for
reference:
12V system -30mV/degree C
24V system -60mV/degree C
36V system -90mV/degree C
48V system -120mV/degree C
60V system -150mV/degree C
Positive grounded systems

When calling OutBack Power for product assistance, please have the following information
ready:
the #1 soft key on the STATUS screen and then pressing a second time and holding the soft
key down.)
displays, such as B-MPPT, F-MPPT, Absorbing, or Float

Output Current Rating 60 amps continuous @ 25°C ambient
Default Battery System Voltage 12, 24, 36, 48 or 60 VDC (adjustable)
PV open circuit voltage 150 VDC Maximum (ETL Rating for UL1741
Standard); operational max = 141 VDC
Standby power consumption Less than 1 watt typical
Recharging regulation methods Five stage—Bulk, Absorption, Battery Full, Float,
Voltage regulation set points 13-80VDC
Temperature compensation With optional RTS sensor 5 millivolts °C per
Voltage step down capability Down convert from any PV array voltage within
PV voc limits of 141 VDC to any battery system
Digital Display 4 line 20 character per line backlit LCD display
Remote Interface RJ45 modular connector Cat 5 cable 8 wire
Operating Temperature Range* -40° to 60°C de-rated above 25°C
Environmental Rating Indoor type 1
Conduit knockouts Two 1/2-3/4” on the back; one 3/4-1” on each
side; two 3/4-1” on the bottom
Warranty Two years parts and labor, optional extended
Dimensions MX60—13.5”H x 5.75”W x 4”D
Boxed—18”H x 11W x 8”D
Weight MX60—12 pounds Boxed—15 pounds

*The MX60’s maximum current output at 25°C is 60 amps. In higher ambient temperatures, the
MX60’s current limit should be reduced in order to prevent possible damage to the unit. Realisti-
cally, given that the solar array also reduces its current output when the ambient temperature
increases, a user will probably never have to adjust the MX60’s current limit. To do so, go to the
STATUS screen and choose the Charger function.
Press the soft key after aligning the asterisk in
*Charger Aux Light EQ Misc Advanced Logging Log2 EXIT I J GO
front of the selected menu choice.
Press I or J to move the asterisk “*” to the left of the Charger function.
Press J to move the asterisk in front of the Amps
LIMIT ABSORB FLOAT Amps Volts Volts *60.0 14.4 13.6 EXIT J - +
selection (default is 60.0) and adjust this fi gure using
the “ –“ and “ + “ soft keys using the fi gures in follow-
ing MX60 Current vs. Temperature Chart. Remember
to change the current limit when the ambient tempera-
ture changes.

MX60 Current Vs Temperature (all temps Celsius)
Ambient Temperature Maximum Current (amps)
25 60.00
30 57.45
35 54.77
40 51.96
45 48.99
50 45.83
55 42.43
60 38.73
65 34.64
70 30.00
75 24.49
80 17.32
An easy de-rating rule to use in lieu of the above table is “1 amp per degree C.” Altitude should also
be factored into de-rating. Use the following table to determine altitude-related values.
0 / sea level 1.00
1000 / 3,000 0.95
1500 / 5,000 0.90
2000 / 7,000 0.86
3000 / 10,000 0.80
3500 /12,000 0.75
Table 1 · Altitude Meters/Feet Factor · Table 2

MX60 EFFICIENCY vs. INPUT POWER GRAPH

Figure 6 24V and 48V Battery System Effi ciency Curve

The MX60 modes of operation will change occasionally during the day based on the PV array
output and the battery system state of charge. The MX60 operating modes are displayed at the
bottom right hand corner of the STATUS screen.
Absorb-EX There is an external DC source other than solar keeping the battery above the Absorb
set point. The MX60 will not be producing power.
Absorbing The MX60 is in the Absorb (constant voltage) charge stage, regulating the battery volt-
age at the Absorb set point (modifi ed by battery temperature compensation if installed). During
this cycle, the ChgT counter in the Misc menu is counting down towards zero. If the system cannot
regulate the battery voltage at the Absorb voltage set point, then the MX60 reverts back to the
Bulk charge stage, display B-MPPT, and the ChgT counter will start counting up again towards the
MAX Absorb time set point or until the Absorb target is met.
AutoStart (Auto Re-Start) Mode 1—Once every 1.5 hours in Bulk cycle and in Mode 2, once every
1.5 hours in the Bulk, Absorb and Float recharging modes, the MX60 will start over from sleeping
and re-sweep (full sweep) and re-calibrate the current sensor. Mode 0 is disabled completely. It is
recommended that this mode be left to mode 2, Auto Re-Start in all 3 recharging cycles. (See Log2
Bat>Abs When the PV voltage exceeds the battery voltage by 2V and the battery voltage exceeds
the absorb set point, the MX60 has no need to recharge. This can also unintentionally occur if the
user inputs a lower battery voltage than is actually in use (e.g. establishing set points for a 12V
system when a 24V battery bank is used). In this case, the MX60 will always sense a higher (24V)
voltage than a 12V system would require for recharging.
Bat Full There is an external DC source other than solar keeping the battery above the Float set
point. The MX60 is transitioning from Absorb (upper target voltage) to Float (lower target voltage)
or it will not be producing power.
B-MPPT The MX60 is in Maximum Power Point Tracking mode trying to regulate the battery volt-
age towards the Absorb voltage set point. If the MX60 is in the Bulk charge stage, the Charge Timer
(ChgT), will count up to the max Absorb time.
screen)

Bat Tmp Err The battery temperature sensor is shorted or damaged.
EQ 0:00 This is the time elapsed in hours and minutes since the Equalization voltage was met.
If the EQ voltage set point is not maintained, the controller will revert back to EQ-MPPT – the EQ
timer will pause until the batteries are regulated at the EQ target again. The paused time can be
viewed in the Log2 menu.
EQ DONE Once the set EQ time, (between 1 and 7 hours), has successfully completed, EQ DONE
will be displayed either until a button is pressed, or the next morning’s wakeup. The MX60 will tran-
sition to Float cycle at the end of the EQ cycle.
EQ-MPPT The equalization process has started and the MX60 is trying to regulate towards the
Equalization voltage set point. EQ is not battery temperature compensated. After the EQ voltage
has been reached, EQ 0:00 will be displayed along with the EQ time in hours and minutes. The
AC/DC loads should be turned off and the battery should be charged so the MX60 can reach the
EQ voltage set point. Otherwise, the MX60 may not reach or maintain the EQ cycle.
Float The MX60 is in the Float charge stage and is regulating the battery at the Float voltage set
point. If the system cannot keep up with the Float voltage set point, (e.g. AC and/or DC loads are
on), the MX60 will employ the MPPT function, display F-MPPT, and try its best to regulate the bat-
teries to the Float set point.
F-MPPT The MX60 is in Maximum Power Point Tracking mode trying to regulate the battery volt-
age towards the Float voltage set point. Note: Charge Timer (ChgT) is inactive in the Float state.
GT Mode In a system with an OutBack FX G-series Inverter/Charger, HUB and MATE, the MX60 will
display GT Mode if and only if the inverter is in Sell mode and the MX60 is in Bulk (B-MPPT) or Float
(F-MPPT) cycle. This is also a good indicator for establishing proper Grid tie mode communication
between the FX G-Series Inverter(s) and MX60.
High Voc This indicates the PV array’s open circuit voltage is too high for the controller to safely
operate. This should only occur with systems using 72 VDC nominal PV arrays in very cold tem-
peratures (below 50 F / -150 C). The controller will automatically restart operation once the PV
array’s open circuit voltage falls to a safe level (141 VDC). The amount of time required to reset is
dependent on the module type, ambient temperature, and the amount of sunlight directly on the
PV array. Normally, the controller starts in the morning within a few minutes of the PV array being
in direct sunlight.

Low Light / Snoozing During the initial sweep (see Wakeup and Sweeping), if it is determined to
be too late (or too early) in the day, the MX60 will display Low Light for a few seconds and then
display Snoozing for 5 minutes (default). This reduces energy usage and unnecessary powering
of the MX60. This message is also displayed in extremely cloudy weather. The Snoozing mode
can be disabled and has two basic modes to choose from: one based on the speed of the PV to
charge the input capacitors and the second looks at the initial wakeup sweep current to see if it
reached the Low cutoff (default) current set point.
MX 2 Hot (Very rare) Either the MX60 is too hot or its internal temperature sensor is shorted. If
this message appears, carefully check if the MX60’s heat sink is extremely hot. The heat generated
by the MX60, and therefore its losses, is proportional to input voltage times output current. Avoid
installing the MX60 in direct sunlight to help control its operating temperature.
New Voc The MX60 is acquiring a new open circuit panel voltage (Voc) periodically in the UPick
MPPT mode or it found a new Voc during an initial sweep.
Re-Cal There are certain abnormal conditions that can confuse the current measuring method
in the MX60. When and if one happens, the MX60 will temporarily stop and re-calibrate. This may
happen because of negative current, i.e., current coming out of the input terminals instead of into
the input terminals, or a tripped PV breaker. A new Voc is also acquired during a Re-Cal.
Sleeping The PV voltage is two volts less than the battery voltage. This may also appear during the
day when the MX60 is transitioning between certain states, or due to other conditions.
Sweeping In Auto-Sweep MPPT mode, the MX60 is either (1) doing an initial sweep of the panel
voltage from Voc towards battery voltage after wakeup, (2) doing a periodic mini-sweep to stay
within its acquired Maximum Power Point voltage, or (3) sweeping to maintain the current limit.
Below 5 amps of battery output current, “Sweeping” briefl y fl ashes on the display as the MX60
operates at the Park Mpp voltage.
SysError (Very rare) System Error indicates an internal non-volatile memory error. The unit will stop
operating when this message is displayed. Call the factory if you see this message.
Unloaded The battery terminals abruptly unload. Unloaded is displayed if the battery breaker trips
while MPPTing or the battery voltage is set too low.

Wakeup As the PV open circuit voltage (Voc) rises above the battery system voltage by two volts,
the MX60 prepares to deliver power to the batteries. During this period, the MX60 is calculating
the pulse width modulation (PWM) duty cycles, turning on power supply voltages in the proper
sequences, and making internal calibrations. At wakeup, the MX60 closes its relays and then starts
sweeping the input voltage (the “initial” sweep) towards the battery voltage. At dawn and dusk this
may happen many times until there is (or is not) enough power from the PV array to keep going.
Wakeup is also a time when the MX60 acquires a new Voc.
Zzzz... At night (3 hours of Sleeping) the MX60 will display Zzzz... until the next wakeup. At the next
wakeup, (usually the next morning), the daily statistics, (AmpHours, KWh, etc.), will accumulate into
the total statistics and then the displayed daily statistics will clear. A Bulk charge will automatically
initiate at the next Wakeup.

The MX60 STATUS MODE Screens displayed on the optional OutBack MATE include MODE, METER,
and SET (SETPOINT). In STATUS Mode, these MX functions can be viewed by the MATE, but not
changed. Please see the MATE Installation and User Manual for more information.
STATUS choose product:
12:00:30P
SUM STATUS SETUP ADV
FX MX
MODE METER SETP MAIN
J J
STATUS/MX/MODE---P00 aux relay Low Batt mode DOWN UP TOP PORT
DOWN UP TOP PORT
J J
STATUS/MX/MODE end of mode menu
Press to view
MODE METER SETP MAIN
the MX METER screens.
ROR ALARM, Diversion, Low Batt(ery) Disconnect, or Remote)
MX MODE Screens

STATUS/MX/METER--P00 charger 0 w watts DOWN UP TOP PORT
STATUS/MX/METER--P00 charger .0 kwh kwhrs DOWN UP TOP PORT
STATUS/MX/METER--P00 charger +000 adc amps dc DOWN UP TOP PORT
STATUS/MX/METER--P00 battery 26.5 vdc voltage DOWN UP TOP PORT
STATUS/MX/METER--P00 panel 10.2 vdc voltage DOWN UP TOP PORT
STATUS/MX/METER end of meter menu
Press to view the
MODE METER SETP MAIN
J
battery voltage, and the outgoing amps to the battery
SETPOINT screens · MX METER Screens

STATUS/MX/SETPT P00 Absorb 28.8 VDC
STATUS/MX/SETPT---P00 Float 27.2 VDC
DOWN UP TOP PORT
J
Press the fi rst two soft keys simultaneously to return
STATUS/MX/METER end of setpoint menu UP TOP STATUS
to the MAIN Menu or press and then
press on the STATUS screen.
MX SETP(OINT) Screens

Be sure to check out the OutBack customer and user forum at www.outbackpower.com/forum/ for more MX60 information.
MX60 does not boot/power-up (blank LCD)
X Reverse polarity or an improper connection will cause power-up issues.
X Ensure that the battery breaker is sized appropriately.
Four- Position Terminal Block).
MX60 is always SLEEPING
voltage), the MX60 will not wake up.
connected to a MATE?
X GT mode is only applicable with a HUB 4 or HUB 10 installations with a grid-tie compatible
MATE.
X If so, the PV array polarity connection on the MX60 maybe reversed or the PV lines could
be shorted.
X Call the factory for support.
X Use a multi-meter to determine if a short circuit current is detected. The short circuit current
test will not harm the array.
breaker on?

MX60 not producing expected power
XThe lower current limit set point in the “Charger” menu will yield a loss of power or poor
performance symptoms.
MX60 will produce enough power to regulate the voltage at the ABSORB or FLOAT set point
voltage, therefore, requiring less power in these modes.
current is as expected. There might be a loose PV array connection.
Maximum Power Point to be at or lower than the battery voltage.
Point of the array. A sweep interval of seven to ten minutes is suggested

MX60 is not equalizing
X In the EQ Menu, press START to begin process. When the EQ cycle has been initiated,
“EQ-MPPT” will be displayed.
X The EQ cycle will begin when the target EQ set point voltage has been reached. A small ar
ray or cloudy weather will delay the EQ cycle. Accordingly, running too many AC and/or DC loads
will delay the EQ cycle, too.
Maximum Power Point to be at or lower than the battery voltage which can delay the EQ cycle.
to ten minutes is recommended.
targeted current limit.
MX60 Sweeping frequently

MX60 Battery Temperature Compensated Voltage
perature is < 77° F or fall below the ABSORB and FLOAT voltage if the battery temperature is
> 77° F.
X The RTS is faulty or damaged. Disconnect the RTS from the RTS jack to resume
normal operation.
The internal fan will run as needed. In the MISC Menu, the fan will run if and only if the value of
PCB is lower than the value 350. Note that the value 350 represents a temperature count value; it
does not itself equal 350° F.
tery voltage, beeping can occur. To disable the Extended Play feature, go to the MAIN Menu and
press and hold the #1 soft key until the MX60’s software version appears on the screen. Con-
tinue pressing the #1 soft key and press the #3 soft key at the same time until “X Off ” displays on
the screen. To reactivate Extended Play, repeat these steps and hold the #3 soft key until “X On”
displays. Extended Play is meant to optimize the performance of a hot array, but isn’t critical to
effi cient MX60 operations.
MX60 Internal Fan · MX60 is beeping

Below is a list of recommended array sizing for the MX60 for various nominal voltage batteries:
Nominal Battery Voltage Recommended Array Size
(in watts, Standard Test Conditions)
24 V 1600 W
36 V 2400 W
48 V 3200 W
60 V 4000 W
The MX60 PV MPPT Charge Controller is capable of an input open circuit voltage (Voc) of up to150
VDC. Cooler climates can cause the Voc to rise above the panel Voc rating. In climates that observe
temperatures less than approximately 5° F, a Voc greater than 125 VDC is not recommended.
When sizing an array, it is recommended that the nominal array voltage be higher than the nomi-
nal battery voltage. Below is a list of recommended nominal array sizing:
Nominal Battery Voltage Nominal Array Voltage (recommended)
12 V 24 V (or higher)*
24 V 36 V (or higher)*
36 V 48 V (or higher)*
48 V 60 V (or higher)*
60 V 60 V (low temp is less than 5° F) or
72v (low temp is greater than 5° F)
* When sizing an array to charge controller with a distance of 70 feet or greater, OutBack
recommends the nominal array voltage be slightly higher than the recommended nominal
array voltage. Example: A 36 VDC nominal array recharging a 12 V nominal battery with an array to
charge controller distance of about 70 feet or greater. Sizing the nominal array voltage higher than
the nominal battery voltage ensures that the Maximum Power Point is always above the battery
voltage. The Maximum Power Point will decrease as the panels warm up, thus lowering the output
of the array. The MX60 Charge Controller will not be able to boost the output if the Maximum
Power Point of the array is at or lower than the battery voltage.

The Australian version MX60 has a few default settings that diff er from the Standard version default
settings. However, there are no diff erences in performance and effi ciency between the two ver-
sions. The Standard and Australian version can be identifi ed as follows:
OutBack 12V Power Systems MX60
OutBack 12V Power Systems MX60-AU
Standard version Australian version
Below are a few default setting diff erences between the Standard and Australian version.
Charger Amps Absorb Float Amps Absorb Float
12 V 60 14.4 V 13.6 V 60 14.4 V 13.8 V
24 V 60 28.8 V 27.2 V 60 8.8 V 27.6 V
36 V 60 43.2 V 40.8 V 60 43.2 V 41.4 V
48 V 60 57.6 V 54.4 V 60 57.6 V 55.2 V
60 V 60 72.0 V 68.0 V 60 72.0 V 69.0 V
Equalize Equalize Volts Equalize Volts
24 V 28.8 29.4
36 V 43.2 44.1
48 V 57.6 58.8
60 V 72.0 73.5
Equalize Time 01 Hours 03 Hours
Settings Standard Australian

To meet NEC compliance, the largest PV array that can be connected to the MX60 should have a
rated short-circuit current of 48 amps. The following charts show the maximum distance of various
gauge two-conductor copper wire from the PV array to the MX60 with a 1.5% maximum voltage
drop. Temperature and conduit fi ll corrections may be required. Using a higher voltage PV array
with a low voltage battery system allows you to use a much smaller wire size or go up to 5 times as
far with the same gauge wire.
12 Volt PV Array
#8 #6 #4 #2 #1/0 #2/0 #4/0
8 22 35 57 90 145 180 290
10 18 28 45 72 115 145 230
15 12 19 30 48 76 96 150
1.5% Voltage Drop
20 9 14 22 36 57 72 116
12 Volt Battery System
30 6 9 15 24 38 48 77
40 4 7 11 18 29 36 56
50 3 5 9 4 23 29 46
24 Volt PV Array
#8 #6 #4 #2 #1/0 #2/0 #4/0
8 45 71 114 180 290 360 580
10 36 57 91 145 230 290 460
15 24 38 60 96 153 192 300
1.5% Voltage Drop
20 18 29 45 72 115 145 232
12 or 24 Volt Battery
30 12 19 30 48 77 97 154
40 9 14 23 36 58 72 112
50 7 11 18 29 46 58 86
48 Volt PV Array
#8 #6 #4 #2 #1/0 #2/0 #4/0
8 90 142 228 360 580 720 1160
10 72 114 182 290 460 580 920
15 48 76 120 192 306 384 600
1.5% Voltage Drop
20 36 58 90 144 230 290 464
12, 24 or 48 Volt Battery
30 24 38 60 96 154 194 308
40 18 28 46 72 116 144 224
50 14 22 36 58 92 116 172

60 Volt PV Array
#8 #6 #4 #2 #1/0 #2/0 #4/0
8 112 177 285 450 725 900 1450
10 90 142 227 362 575 725 1150
1.5% Voltage Drop
15 60 95 150 240 382 480 750
12, 24 or 48 Volt Battery
20 45 72 112 180 287 362 580
30 30 47 75 120 192 230 385
40 22.5 35 57 90 145 180 280
50 17.5 27 45 72 115 145 215
72 Volt PV Array
#8 #6 #4 #2 #1/0 #2/0 #4/0
8 140 221 356 562 906 1125 1812
1.5% Voltage Drop
10 113 178 284 453 719 906 1437
12, 24 or 48 Volt Battery
15 75 119 188 300 478 600 937
20 56 90 140 225 359 452 725
30 37 59 94 150 240 287 481
40 28 44 71 112 181 225 350

The MX60 has a 60 amp current output limit (default) and is listed to operate continuously at 60
amps depending on the nominal PV array voltage and the nominal battery voltage. There is no
80% de-rating as required by the NEC for fuses, conductors, and most circuit breakers.
The MX60 is a buck type converter and cannot boost the output current when the PV array peak
power point voltage is at or below the battery voltage as may happen on hot days in 24 VDC PV
and a 24 VDC battery system or a 48 VDC PV and a 48 VDC battery system.
To meet minimum NEC requirements (NEC 310.15, 690.8, 9), the output conductor should have
an ampacity of 75 amps after any temperature and conduit fi ll corrections. This would normally
indicate that the output conductors be 4 AWG, but a larger size may be required if there are
temperature and/or conduit fi ll corrections required. With an output conductor rated at 75 amps
(1.25 X the continuous output current), the OutBack OBDC-60 breaker—rated for continuous 100%
duty at 60 amps —can be used to provide the code-required disconnect and output circuit over
current protection.
The PV array output connected to the MX60 input may be as high 60 amps, but at this current
level, there is very little (if any) current boosting or maximum power-point tracking due to the
60-amp output current limit. Additionally, the input current may exceed 60 amps on bright sunny
days and any excess power would be lost. The size and ampacity of the input conductors must be
selected to handle 1.56 times the short-circuit current of the PV array. Any disconnect or circuit
breaker connected to the input conductors must also be rated at 1.56* times the short-circuit
current for the PV array unless the breaker is rated for 100% duty in its enclosure. If that is the case,
the circuit breaker may be rated at 1.25 times the PV array short-circuit current. OutBack OBDC-XX
breakers are 100% duty rated breakers.
In terms of NEC compliance and the MX60’s 60-amp output rating, the largest PV array it can con-
nect to should have a rated short-circuit current of 48 amps. This meets NEC requirements and
allows the MX60 to perform maximum power-point tracking functions. The following charts show
maximum distance in feet of various gauge two-conductor copper wire from the PV array to the
MX60 with a 1.5% maximum voltage drop. Temperature and conduit fi ll corrections may
be required.
*UL requires Isc to be multiplied by 125% for the conductor rating

BULK
SN O OZE
ABSORB
FLOAT
SLEEP ZZZZ SLEEP ZZZZ
XBulk cycle begins XAbsorb charge is reached XAt zero, MX60 goes into FLOAT XTimer starts XTimer begins counting to zero
Figure 7 MX60 MULTI-STAGE BATTERY CHARGING
The MX60 charge controller is a sophisticated, multi-stage battery charger that uses several regula-
tion stages to allow fast recharging of the battery system while ensuring a long battery life. This
process can be used with both sealed and non-sealed batteries. The MX60 has a preset recharg-
ing voltage set points (Absorb & Float) for the selected nominal battery voltage, however, always
follow the battery manufacturer’s recommended charging regulation voltages. The MX60 charging
regulation stages correspond to the chart in Figure 7.

BULK cycle provides the maximum power to the battery –the voltage increases
while recharging.
A Bulk cycle is automatically initiated when the battery voltage is below the Absorb and Float*
recharge voltage set points. The Bulk cycle will continue until the Absorb voltage set point is
achieved. “BMPPT” is displayed on the screen.
ABSORBING cycle limits the amount of power going to the battery—the voltage is
held constant.
The Absorb cycle will continue for the duration of the Bulk cycle or until the 2 hour (default) Ab-
sorb time limit is reached. For example, if a Bulk cycle takes 1 hour to reach the Absorb voltage set
point, then the Absorb cycle will continue for 1 hour as well. However, if a Bulk cycle takes 3 hours
to reach the Absorb voltage set point, then the Absorb cycle will continue for 2 hours only. A Bulk
cycle will be re-initiated if the battery voltage is not sustained at the Absorb voltage set point.
“Absorbing” is displayed on the screen at this time.
FLOAT cycle reduces the recharging voltage to prevent overcharging of the batteries.
A Float cycle follows after the Absorb cycle is completed; “Float” is displayed on the screen. The
MX60 will not re-initiate another Bulk cycle if the Float voltage set point is not sustained*. F-MPPT
is displayed. However, it will continue to recharge the battery until the Float voltage set point is
reached.
*Note: A Bulk cycle can be auto-initiated if the battery voltage falls below the Float voltage set
point and the Re-Bulk (ReBV) voltage option is set.

The temperature of a battery has an impact on the recharging process—in higher ambient tem-
peratures, the regulation set points (Absorb & Float) need to be reduced to prevent overcharging
of the batteries. In lower ambient temperature conditions, the voltage regulation set points need
to be increased to ensure complete recharging of the batteries.
The default charger settings of the MX60 are based on typical lead acid battery systems. Always
ensure that the Absorb & Float voltage regulation set points are set to the recommended battery manu-
facturer’s recharging regulation voltages.
Non-Battery Temperature Compensated System
If a battery remote temperature sensor is not available the Absorb and Float voltage regulation set
points can be adjusted for the expected weather conditions. The following table shows the appro-
priate adjustments for both Absorb and Float voltage regulation set points for weather conditions
above or below 77˚ F / 25˚ C
Average = 95˚ F / 35˚ C Subtract 0.30 V 0.60 V 1.20 V
Average = 86˚ F / 30˚ C Subtract 0.15 V 0.30 V 0.60 V
Average = 68˚ F / 20˚ C Add 0.15 V 0.30 V 0.60 V
Average = 59˚ F / 15˚ C Add 0.30 V 0.60 V 1.20 V
Battery Temperature Compensated System
A battery remote temperature sensor (RTS) will automatically compensate the Absorb & Float
voltage relative to the Absorb and Float set points in the Charger menu. Please reference page 38
of this manual for adjusting the upper and lower battery compensated limits.

The battery manufacturer should provide you with specifi c instructions on the following mainte-
nance and voltage set point limits for the specifi c batteries. The following information can be used
when the manufacturer’s information is not available.
SEALED LEAD ACID – AGM / GEL 12 V 24 V 48 V
ABSORB voltage set point 14.4 V 28.8 V 57.6 V
FLOAT voltage set point 13.4 V 26.8 V 53.6 V
NON-SEALED LEAD ACID 12v 24v 48v
ABSORB voltage set point 14.8 V 29.6 V 59.2 V
FLOAT voltage set point 13.8 V 27.6 V 55.2V
greater and excessive temperatures when recharging may occur.
Battery Voltage and State of Charge
A battery’s voltage can be used as a guideline to estimate the amount of power stored in the
battery that is available for use. When referencing the battery voltage on the display, be sure the
battery is not under signifi cant recharging or heavy loads. Otherwise, the DC voltage is not refl ec-
tive of the battery state of cycle. Often the best time to check the battery voltage is in the morning
(pre-charging) or at night (postcharging), with the battery disconnected from charging sources
and loads and a rest for at least three hours.
Operation of a battery below 50% state of cycle will adversely aff ect the long term health of the
battery system and will result in premature failure. Keeping the battery above the 50% level and
recharging it completely once a month will ensure proper operation and good performance.
Nominal Battery Charged Good (~75%) Average (~50%) Low (~25%) Discharged
12v over 12.6v 12.3v 12.0v 11.7v under 11.4v
24v over 25.2v 24.6v 24.0v 23.4v under 22.8v
48v over 50.4v 49.2v 48.0v 46.8v under 45.6v
60v over 63.0v 61.5v 60.0v 58.5v under 57.0v
Voltage


OutBack Power Systems Inc. warrants that the products it manufacturers will be free from
defects in materials and workmanship for a period of two (2) years subject to the conditions set
forth below.
The limited warranty is extended to the original user and is transferable. The limited warranty
term begins on the date of invoice to the original user of the product. The limited warranty does
not apply to any product or part thereof damaged by a) alteration or disassembly, b) accident or
abuse, c) corrosion, d) lightning, e) reverse polarity, f) repair or service provided by an unauthor-
ized repair facility, g) operation or installation contrary to instructions pertaining to the product.
OutBack Power Systems’ liability for any defective product or any part thereof shall be limited to
the repair or replacement of the product, at OutBack Power Systems’ discretion. OutBack Power
Systems does not warrant or guarantee the workmanship performed by any person or fi rm
installing its products.
THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER
RIGHTS THAT VARY FROM STATE TO STATE (OR JURISDICTION TO JURISDICTION). OUTBACK POWER
SYSTEMS’ RESPONSIBILITY FOR MALFUNCTIONS AND DEFECTS IN HARDWARE IS LIMITED TO
REPAIR AND REPLACEMENT AS SET FORTH IN THIS LIMITED WARRANTY STATEMENT. ALL EXPRESS
AND IMPLIED WARRANTIES FOR THE PRODUCT, INCLUDING BUT NOT LIMITED TO ANY IMPLIED
WARRANTIES OF AND CONDITIONS OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PUR-
POSE, ARE LIMITED IN DURATION TO THE LIMITED WARRANTY PERIOD SET FORTH ABOVE AND NO
WARRANTIES, WHETHER EXPRESS OR IMPLIED, WILL APPLY AFTER SUCH PERIOD. SOME STATES (OR
JURISDICTIONS) DO NOT ALLOW LIMITATIONS ON HOW LONG IMPLIED WARRANTY LASTS, SO THE
ABOVE LIMITATION MAY NOT APPLY TO YOU.
OUTBACK POWER SYSTEMS DOES NOT ACCEPT LIABILITY BEYOND THE REMEDIES SET FORTH IN
THIS LIMITED WARRANTY STATEMENT OR LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAM-
AGES, INCLUDING WITHOUT LIMITATION ANY LIABILITY FOR PRODUCTS NOT BEING AVAILABLE
FOR USE. SOME STATES (OR JURISDICTIONS) DO NOT ALLOW THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE EXCLUSION OR LIMITATION MAY NOT
APPLY TO YOU.

During the two year period beginning on the invoice date, OutBack Power Systems will repair
or replace products covered under this limited warranty that are returned to OutBack Power
Systems’ facility or to an OutBack Power Systems authorized repair facility, or that are repaired
on site by an OutBack Power Systems authorized repair technician. To request limited warranty
service, you must contact OutBack Power Systems at 360-435-6030 within the limited warranty
period. If limited warranty service is required, OutBack Power Systems will issue a Return Material
Authorization (RMA) Number. Mark the outside of the package with the RMA number and include
a copy of the purchase invoice in the package. You must ship the products back to OutBack Power
Systems in their original or equivalent packaging, prepay shipping cycles, and insure the ship-
ment or accept the risk of loss or damage during shipment. OutBack Power Systems will ship the
repaired or replacement products to you freight prepaid if you use an address in the continental
United States, where applicable. Shipments to other locations will be made freight collect.

According to ISO / IEC Guide 22 and EN 45014
This product complies with the following EU directives:
Electromagnetic Compatibility 89/336/EEC, “Council Directive of 3 May 1989
On the approximation of the laws of member States relating to Electromagnetic
Low Voltage Directive 73/23/EEC, “Council Directive of 19 February 1973 on the
harmonization of the laws of Member States relating to electrical equipment for use
within certain voltage limits”
The compliance of the above mentioned product with the directives and the following
essential requirements is hereby confi rmed:
EN 61000-6-3 (2001) EN 61000-6-1 (2001) EN 60335-1 Battery Chargers
All associated technical fi les are located in the Engineering Department at OutBack
Power Systems Inc., Arlington, Washington, USA.
As the manufacturer, we declare under our sole responsibility that the above-mentioned
product complies with the above-named directives.
19009 62nd Ave. NE Arlington, WA. 98223 USA (360) 435-6030
compatibility” · Emissions Immunity Safety · EN 60335-2-29Battery Chargers


Product Registration Please take a moment to register and provide us with some important information. Registering your products will help us maintain the standard of excellence you expect from us in terms of performance, quality and reliability. Send check or money order payable to OutBack Power Systems. Include a completed copy of this
application to.: OutBack Power Systems, 19009 62nd Avenue NE, Arlington, WA 98223 USA.
Check all that apply:
X Off -Grid Installation X Grid-Tie Installation XResidential Installation X Commercial Installation
EXTENDED WARRANTYAPPLICATION OutBack Power Systems off ers an optional three year extension to the standard two year limited warranty. Purchase of extended warranty coverage is available on products listed below provided conditions shown are met. Extended warranty coverage must be purchased within 90 days of the original sale of the product covered. WA state residents please add 8.5% sales tax.
PRODUCT REQUIRED SURGE EXTENDED WARRANTY PROTECTION COST All FX Series Inverter/Chargers AC Input; AC Output, DC Input $300.00 MX60 DC Input; DC Output $100.00 MATE NA $50.00 HUB 4 NA $35.00
Products Covered Serial Number Extended Warranty Cost


19009 62nd Avenue NE Arlington, WA USA (+1) 360-435-6030
European Sales Offi ce
Barcelona, España (+34) 600-843-845
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.