EN
Outback Power Systems logo
Official user manual

Outback Power Systems MX60

92 pages·901 KB·Battery Charger·PDF·ENDEFRITNLJA
Outback Power Systems MX60
Table of Contents 80 sections MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller · Installation, Programming and User’s Manual · Warranty Summary · SCOPE · … ShowHide
MX60 PV MPPT (Maximum Power Point Tracking) Charge Controllerp.1Installation, Programming and User’s Manualp.1Warranty Summaryp.2SCOPEp.6INTRODUCTIONp.6OUTBACK MX60 CHARGE CONTROLLER INSTALLATION GUIDELINES AND SAFETY INSTRUCTIONSp.7OPEN CIRCUIT VOLTAGE/WIRE AND DISCONNECT SIZINGp.9Wire and Disconnect Sizingp.9NOTESp.11BATTERY SYSTEM VOLTAGEp.14X KEY TO THE EXAMPLE DIAGRAMS Wp.14POWERING UPp.15PASSWORDp.16ENTER - +p.16STATUS SCREENp.18PREPARING FOR RECHARGINGp.19ACCESSING THE MAIN MENUp.20CHARGER SETUPp.21AUX MODEp.22J Jp.23VENT FAN VOLTSp.25> 14.4 BACK - +p.25PV VOLTSp.26BACK - +p.2600.2 00.3 BACK - + HYST +p.29DISCONNECT VOLTSp.32RE-CONNECT VOLTSp.32BACKLIGHTp.34BACKLIGHT CONTROLp.34ALWAYS EXIT AUTO ON OFFp.34EQ—BATTERY EQUALIZEp.34BATTERY EQUALIZEp.3515.0 EXIT NEX -EQV +EQVp.35COUNT EQ INTERVAL 00 000p.36EXIT -DAY +DAYp.36MISC—MISCELLANEOUSp.37WIDE/LMIT Battery Temperature Compensated Limitsp.38FORCE EXIT NEXT FLOAT BULKp.41MISCELLANEOUS Screen 3p.42ADVANCEDp.43ADVANCED MENUp.43S N O O Z Ep.47BULKp.47ABSORBp.47FLOATp.47Z Z Z Z SLEEPp.47PV ARRAY VOLTAGEp.47SLEEPp.47Z Z Z Zp.47(DATA) LOGGINGp.49CLEAR BACK TOTL DALYp.49Charger Aux Light Eq Misc Advanced *Logging Log2 EXIT I J GOp.50LOG2p.51MICRO-HYDRO, WIND TURBINE, AND FUEL CELL APPLICATIONSp.54MICRO-HYDRO AND FUEL CELL SYSTEMS PERFORMANCE OPTIMIZATIONp.54ADVANCED MENU (Micro-Hydro)p.56THIS PAGE INTENTIONALLY LEFT BLANKp.60APPLICATION NOTESp.61CALLING THE FACTORY FOR ASSISTANCEp.62SPECIFICATIONSp.63UNDERSTANDING THE VARIOUS OPERATIONAL MODESp.67MATE-DISPLAYED MX60 STATUS MODE Screensp.71MAIN------------------------p.71STATUS/MX-----------------p.7112:00:30Pp.71SUM STATUS SETUP ADVp.71FX MXp.71MODE METER SETP MAINp.71DOWN STATUS PORTp.71DOWN UP TOP PORTp.71UP TOP STATUSp.71MATE-DISPLAYED MX60 STATUS METER Screensp.72MATE-DISPLAYED MX60 STATUS SETPT (SETPOINT) Screensp.73TROUBLESHOOTING GUIDEp.74TYPICAL ARRAY SIZING GUIDEp.7812 V 800 Wp.7824 V 1600 Wp.7836 V 2400 Wp.7848 V 3200 Wp.7860 V 4000 Wp.78
Page 1 of the Outback Power Systems MX60 user manual — Installation, Programming and User’s Manual
Page 1 · click to enlarge
Page 1
Outback Power Systems MX60 — MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller diagram (page 1)
Fig. 1 · MX60 PV MPPT (Maximum Power Point Tracking) Charge C…

MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller

Installation, Programming and User’s Manual

Page 2 of the Outback Power Systems MX60 user manual — Warranty Summary
Page 2 · click to enlarge
Page 2

Warranty Summary

Thank you for your purchase of OutBack products. We make every eff ort to assure our power

conversion products will give you long and reliable service for your renewable energy system.

As with any manufactured device, repairs might be needed due to damage, inappropriate use,

or unintentional defect. Please note the following guidelines regarding warranty service of

OutBack products:

  • Any and all warranty repairs must conform to the terms of the warranty.
  • All OutBack equipment must be installed according to their accompanying instructions and

manuals with specifi ed over-current protection in order to maintain their warranties.

  • The customer must return the component(s) to OutBack, securely packaged, properly addressed,

and shipping paid. We recommend insuring your package when shipping. Packages that are not

securely packaged can sustain additional damage not covered by the warranty or can void

warranty repairs.

  • There is no allowance or reimbursement for an installer’s or user’s labor or travel time required to

disconnect, service, or reinstall the damaged component(s).

  • OutBack will ship the repaired or replacement component(s) prepaid to addresses in the conti-

nental United States, where applicable. Shipments outside the U.S. will be sent freight collect.

  • In the event of a product malfunction, OutBack cannot bear any responsibility for consequential

losses, expenses, or damage to other components.

  • Please read the full warranty at the end of this manual for more information.

Dear OutBack Customer,

Page 3 of the Outback Power Systems MX60 user manual — Warranty Summary
Page 3 · click to enlarge
Page 3

The OutBack Power Systems MX60 PV MPPT Charge Controller is ETL listed to UL1741 (Inverters,

Converters, Controllers, and Interconnection System Equipment for Use with Distributed Energy

Resources). It is also in compliance with European Union standards EN 61000-6-1 and

EN 61000-6-3 (see page 89).

About OutBack Power Systems

OutBack Power Systems is a leader in advanced energy conversion technology. Our products

include true sine wave inverter/chargers, a maximum power point charge controller, system com-

munication components, as well as breaker panels, breakers, accessories, and assembled systems.

MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller: Installation, Programming

Copyright © 2007 All rights reserved.

UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER SYSTEMS:

(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL

OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.

(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,

INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH

INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.

January 29, 2007 REV 7.0 Software REV 5.10 and 5.11

19009 62nd Ave. NE

www.outbackpower.com

Show 8 more labels / short text on this page
and User’s Manual · Disclaimer · Date and Revision · Contact Information · OutBack Power Systems · Arlington, WA 98223 · Phone (360) 435-6030 · Fax (360) 435-6019
Page 4 of the Outback Power Systems MX60 user manual — Warranty Summary
Page 4 · click to enlarge
Page 4
Page 4 of the Outback Power Systems MX60 user manual — Warranty Summary
Page 5 of the Outback Power Systems MX60 user manual — Warranty Summary
Page 5 · click to enlarge
Page 5
Page 5 of the Outback Power Systems MX60 user manual — Warranty Summary
Page 6 of the Outback Power Systems MX60 user manual — INTRODUCTION
Page 6 · click to enlarge
Page 6

SCOPE

The manual provides safety guidelines and installation information for the MX60 PV MPPT Charge

Controller. It does not provide information about specifi c brands of solar panels and supplies

limited information on batteries. Contact the supplier or manufacturer of the solar panels or

batteries for further information.

INTRODUCTION

MX60 PV MPPT (Maximum Power Point Tracking) Charge Controller

The OutBack MX60 PV MPPT Charge Controller off ers an effi cient, safe, multi-stage recharging

process that prolongs battery life and assures peak performance from a solar array. This

component allows customized battery recharging. The MX60 features include:

  • 60 amps maximum continuous output current
  • Engineered to work with 12, 24, 36, 48, and 60 VDC battery voltages
  • Backlit LCD display screen with 80 characters (4 lines, 20 characters per line)
  • Last 64 days of operational data are logged for review
  • Voltage step-down capability allowing a higher PV array voltage confi guration
  • Manual and auto-equalize cycle

The following are the maximum recommended wattage for the most common solar arrays under

Standard Test Conditions (1000 watts per square meter of solar panel at 25° C or 77° F):

  • 12 VDC battery systems—up to 800 watts of solar panels
  • 24 VDC battery systems—up to 1600 watts of solar panels
  • 48 VDC battery systems—up to 3200 watts of solar panels

The MX60 also features Maximum Power Point Tracking (MPPT), which seeks out the maximum

power available from a solar array and uses it to recharge the batteries. Without this feature, the

solar array does not operate at the ideal operating voltage and can only recharge at the level of

the battery voltage itself. The MX60 “sweeps” the array’s operating voltage at user-determined

sweep intervals to track the Maximum Power Point (MPP) of the PV array.

This manual covers the wiring, installation, and use of the MX60, including explanations of all the

Menus displayed on the LCD screen. The MX60 is designed to seamlessly integrate with other

OutBack components and can be remotely monitored (up to 1000 feet) by the optional OutBack

Power Systems MATE display.

Page 7 of the Outback Power Systems MX60 user manual — OUTBACK MX60 CHARGE CONTROLLER INSTALLATION GUIDELINES AND SAFETY INSTRUCTIONS
Page 7 · click to enlarge
Page 7

OUTBACK MX60 CHARGE CONTROLLER INSTALLATION GUIDELINES AND SAFETY INSTRUCTIONS

This product is intended to be installed as part of a permanently grounded electrical system

as shown in the system confi guration sections of this manual with the following important

restrictions:

  • The negative battery conductor should be bonded to the grounding system at only one point in

the system. If a GFP is present, the battery negative and ground are not bonded.

  • With the exception of certain telcom applications, the MX60 should never be positive grounded

(see page 61, Applications Notes).

  • The equipment ground on the MX60 is marked with this symbol:
  • If damaged or malfunctioning, the MX60 should only be disassembled and repaired by a

qualifi ed service center. Please contact your renewable energy dealer/installer for assistance.

Incorrect reassembly risks malfunction, electric shock or fi re.

  • The MX60 is designed for indoor installation or installation inside a weatherproof enclosure. It must

not be exposed to rain and should be installed out of direct sunlight.

  • For routine, user-approved maintenance:

XDisconnect all circuit breakers and related electrical connections before doing any cleaning

or adjustments.

XSolar modules may produce hazardous voltages when exposed to light; unless

servicing them at night, cover the modules with opaque material before servicing any

connected equipment.

All installations must comply with national (NEC) and local electrical codes; professional installation

is recommended.

DC and Battery-Related Installation Requirements:

  • All DC cables must meet NEC standards.
  • Shut off all DC breakers before connecting any wiring.
  • Torque the four-position terminal block and ground terminals to 30 inch pounds/4Nm.
  • All wiring must be rated at 75° C or higher.
  • Use up to 2 AWG to reduce losses and ensure high performance of MX60 (smaller cables can

reduce performance and possibly damage the unit).

  • Keep cables together (e.g., using a tie-wrap) as much as possible.
  • Ensure both cables pass through the same knockout and conduit fi ttings to allow the inductive

currents to cancel.

  • DC battery over-current protection must be provided as part of the installation. OutBack off ers

both breakers and fuses for over-current protection.

Standards and Requirements

Page 8 of the Outback Power Systems MX60 user manual — OUTBACK MX60 CHARGE CONTROLLER INSTALLATION GUIDELINES AND SAFETY INSTRUCTIONS
Page 8 · click to enlarge
Page 8

BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION. Design the

battery enclosure to prevent accumulation and concentration of hydrogen gas in “pockets”

at the top of the enclosure. Vent the battery compartment from the highest point to the

outside. A sloped lid can also be used to direct the fl ow of hydrogen to the vent opening.

calcium, gel cell or absorbed glass mat type rechargeable batteries. Other types of batteries

may burst, causing personal injury and damage. Never charge a frozen battery.

  • PERSONAL PRECAUTIONS
  • Someone should be within range of your voice to come to your aid if needed.
  • Keep plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes.
  • Wear complete eye protection. Avoid touching eyes while working near batteries. Wash your hands with soap and warm water when done.
  • If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters an eye, fl ood the eye with running cool water at once for at least 15 minutes and get medical attention immediately following.
  • Baking soda neutralizes lead acid battery electrolyte. Keep a supply on hand in the area of the batteries.
  • NEVER smoke or allow a spark or fl ame in vicinity of a battery or generator.
  • Be extra cautious to reduce the risk of dropping a metal tool onto batteries. It could shortcircuit the batteries or other electrical parts that can result in fi re or explosion.
  • Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery or other electrical current. A battery can produce a short circuit current high enough to weld a ring or the like to metal, causing severe burns.
Page 9 of the Outback Power Systems MX60 user manual — Wire and Disconnect Sizing
Page 9 · click to enlarge
Page 9

OPEN CIRCUIT VOLTAGE/WIRE AND DISCONNECT SIZING

Maximum Open Circuit Voltage (Voc)

  • Voc is the unloaded voltage generated by the solar array.

X 141 VDC J MX60 suspends operation to protect components

X 150 VDC J max open circuit voltage with the coldest environment (although the MX60

shuts down at 141 VDC, it can absorb up to 150 VDC from the array; anything higher than 150

VDC will damage the MX60)

  • As every brand of panel is diff erent, be sure to know the manufacturer’s specifi cations.
  • Local temperatures vary seasonally and will aff ect panel voltage.
X Hot weatherlower open circuit voltage/lower maximum power point voltage
X Cold weatherhigher open circuit voltage/higher power point voltage

X Allow for ambient temperature correction using the following table:

25° to 10° C (77° to 50° F) multiply by 1.06

9° to 0° C (49° to 32° F) multiply by 1.10

-1° to -10° C (31° to 14° F) multiply by 1.13

-11° to -20° C (13° to -4° F) multiply by 1.17

-21° to -40° C (-5° to -40° F) multiply by 1.25

X Check the PV array voltage before connecting it to the MX60.

Wire and Disconnect Sizing

  • The output current limit of the MX60 is 60 amps.
  • Use a minimum of 6 AWG wire for the output between the MX60 and the batterry bus bar con-

ductors; a larger size might be required due to temperature and/or conduit fi ll corrections.

  • Install OutBack OBDC-60 or OBDC-80 amp breakers for disconnect and over current protection.
  • The largest PV array that can connect to an MX60 should have a rated short-circuit current of 48

amps STC (Standard Test Conditions).

  • Input conductors and circuit breakers must be rated at 1.56 times the short-circuit current of the

PV array. OutBack OBDC 100% duty continuous breakers only need to be rated at 1.25 times the

short-circuit current.

  • Please see the wire Distance Chart and complete Wire and Disconnect Sizing on pages 80-82 for

other suitable conductor/wire sizing.

Page 10 of the Outback Power Systems MX60 user manual — OPEN CIRCUIT VOLTAGE/WIRE AND DISCONNECT SIZING
Page 10 · click to enlarge
Page 10

Figure 1 Field Wiring Connections and Surge Protection

Outback Power Systems MX60 — OPEN CIRCUIT VOLTAGE/WIRE AND DISCONNECT SIZING diagram (page 10)
Fig. 2

Use up to 2 AWG wire and torque to 30-inch pounds at terminals.

Battery Remote Temp Sensor (RTS) RJ11 jack

Programmable AUX Output Jack (supplies up to 200mA @ 12 VDC

If attaching to plywood, use a 1 5/8” wood screw to secure the MX60 at the top slotted hole and other screws as needed at interior bottom holes. PV+ PV- BAT- BAT+ Four-Position Terminal Block

The PV (-) and BAT (-) terminals are connected internally. Only one negative wire may be needed

to connect to the Four-Position Terminal Block if the PV - and BAT- conductors are bonded at the

negative bus bar. See Figures 2 and 3 for sample wiring diagrams.

MATE/HUB RJ45 jack · Chassis/Equipment Ground Lug

Page 11 of the Outback Power Systems MX60 user manual — NOTES
Page 11 · click to enlarge
Page 11

NOTES

  • An optional battery Remote Temperature Sensor (RTS) is recommended for accurate

battery recharging (only one RTS is needed for multiple OutBack Series Inverter/Chargers

and MX60 units when an OutBack HUB and a MATE are parts of the system). When one RTS

is used, it must be connected to the component plugged into the Port 1 of the HUB.

  • AUX modes include powering a relay, LED indicator, and Piezo-buzzer or brushless fan.
  • The OutBack MATE can display a single MX60 or multiple MX60s if connected to a HUB.
  • Surge protection on the input (PV) side of the MX60 and on the battery side is required for

extended warranty protection. A dwelling rooftop array requires ground fault protection

(OutBack OBDC-GFP/2 recommended).

  • Always install the MX60 in an upright position. The MX60 must be secured for a safe

installation and to retain warranty protection. Use a 1 5/8” wood screw through the slotted

hole at the top of the MX60 and at least two screws in the internally located holes at the

bottom of the MX60’s enclosure.

Page 12 of the Outback Power Systems MX60 user manual — NOTES
Page 12 · click to enlarge
Page 12
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 3
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 4
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 5
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 6
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 7
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 8
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 9
Outback Power Systems MX60 — NOTES diagram (page 12)
Fig. 10

Figure 2 MX60 WIRING DIAGRAM WITHOUT A GFP/2, the ground conductors tie into the negative

terminal bus bar.

Page 13 of the Outback Power Systems MX60 user manual — NOTES
Page 13 · click to enlarge
Page 13
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 11
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 12
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 13
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 14
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 15
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 16
Outback Power Systems MX60 — NOTES diagram (page 13)
Fig. 17

Figure 3 MX60 WITH GFP/2 WIRING DIAGRAM The GFP/2 requires a separate ground bus bar.

Page 14 of the Outback Power Systems MX60 user manual — X KEY TO THE EXAMPLE DIAGRAMS W
Page 14 · click to enlarge
Page 14

BATTERY SYSTEM VOLTAGE

  • The MX60’s default setting is for a 12 VDC battery.
  • Change the setting after powering up the MX60 if a diff erent battery voltage is used.
  • The PV array voltage—which must not exceed 150 VDC open circuit—is automatically detected.

X KEY TO THE EXAMPLE DIAGRAMS W

Soft keys:

(#1) (#2) (#3) (#4)

Solid black indicates key is to be pressed:

Down arrow will lead to the next screen:

Up arrow points to one or more keys that will change a value:

The keys correspond to any text immediately above them.

Page 15 of the Outback Power Systems MX60 user manual — POWERING UP
Page 15 · click to enlarge
Page 15

POWERING UP

The MX60 power-up sequence fi rst activates the unit and brings up a series of screens; some

screens allow the user to change the battery voltage.

OFF SCREEN (this screen is initially blank at power up)

With the PV array and battery breakers off , press and

hold soft keys #1 and #3 and then turn on the battery

breaker (see Figure 4).

Outback Power Systems MX60 — POWERING UP diagram (page 15)
Fig. 18

reads “Got Battery?” please see the Troubleshooting Guide on page 74.

Battery Breaker

Page 16 of the Outback Power Systems MX60 user manual — ENTER - +
Page 16 · click to enlarge
Page 16

Release both soft keys when the OutBack Power

OutBack 12V Power Systems MX60

Systems screen appears. The selected battery voltage

appears in the upper righthand corner. The BATTERY

VOLTAGE screen will appear next.

will read MX60AU for Australian versions and MX60ES

for Spanish versions.

“^^” indicates the selected battery voltage. Press

BATTERY VOLTAGE 12 24 36 48 60 ^^ EXIT J ENTER

the “J” or soft keys to proceed to the

PASSWORD screen, which prevents unauthorized

changes to the system.

Press the “ – “ soft key until the password 141 shows

PASSWORD

on the screen. Press the soft key to return

to the BATTERY VOLTAGE.

ENTER - +

displayed on a screen.

Show 4 more labels / short text on this page
Power-Up Screen · Press Either Key · Password Screen · ***150***
Page 17 of the Outback Power Systems MX60 user manual — PASSWORD
Page 17 · click to enlarge
Page 17

Press the “J” soft key to select a battery voltage. The

BATTERY VOLTAGE 12 24 36 48 60 ^^ EXIT J ENTER

MX60’s default values are based on a 12 VDC system.

Selecting a higher voltage system will change all the

default values (e.g., the values will double with a 24

VDC system, triple with a 36 VDC system, etc.). “^^”

indicates the chosen voltage. The MX60 will automat-

ically accept the selected battery voltage if left unat-

tended for 5 minutes in this screen. After choosing

the voltage, press the soft key to proceed.

Press the soft key to proceed if the selected

Are you sure? 12 24 36 48 60 ^^ NO Yes

battery voltage is correct. If incorrect, press to

re-enter the correct voltage.

The MX60 briefl y returns to the Power-Up screen and

OutBack 12V Power Systems MX60

then automatically opens the STATUS screen which

displays information regarding the recharging status.

Confi rm the battery voltage displayed in the upper

right corner is correct.

Battery Voltage Screen · Verifi cation Screen · Power-Up Screen

Page 18 of the Outback Power Systems MX60 user manual — NOTES
Page 18 · click to enlarge
Page 18

STATUS SCREEN

The STATUS Screen displays system information. See page 67 for detailed information of the dif-

ferent Operational Modes. The optional OutBack MATE displays MX STATUS screens for convenient

distant viewing from the installation location of the MX60. Please see page 71 to view the MX

screens displayed on the MATE.

The PV voltage will slowly rise to the battery

voltage level even when the PV breaker

is off – this is normal as the PV capacitor

charges up.

PV 005 V Bat 12.5 V 00.0 A 00.0 A Watts 0000 Aux Off kWHrs 00.0 Sleeping

Aux. Status (ON or OFF)

NOTES

  • Pressing the fi rst soft key opens the MAIN Menu screen.
  • Pressing soft key #2 toggles between Amp Hours and kW Hours displays.
Show 8 more labels / short text on this page
PV Input Voltage · Battery voltage · PV Input Current · Output current · Instantaneous Watts · Daily accumulated · Operational Mode · kiloWatt Hours
Page 19 of the Outback Power Systems MX60 user manual — PREPARING FOR RECHARGING
Page 19 · click to enlarge
Page 19

PREPARING FOR RECHARGING

Turn the PV input breaker on. The MX60

PV 113 V Bat 12.5 V 00.0 A 00.0 A Watts 0000 Aux Off kWHrs 00.0 Sleeping

automatically detects the PV input voltage.

(NoteIf PV voltage registers “000V” when the breaker

is on, please check the polarity of the PV wires.)

After 5 seconds of stable input voltage, the MX60

PV 087 V Bat 12.5 V 05.0 A 32.9 A Watts 0412 Aux Off kWHrs 00.0 B-MPPT

enters a “Wakeup” stage, transitions to “Sweeping”

and prepares to charge the batteries by tracking the

MPP of the solar array.

Page 20 of the Outback Power Systems MX60 user manual — ACCESSING THE MAIN MENU
Page 20 · click to enlarge
Page 20

ACCESSING THE MAIN MENU

The MAIN Menu allows the user to adjust and calibrate the MX60 for maximum performance.

From the STATUS screen, press soft key #1 to open the MAIN Menu screen.

Press the soft key after aligning the asterisk

*Charger Aux Light EQ Misc Advanced Logging Log2 EXIT I J GO

in front of the selected menu choice.

Pressing the soft key in the MAIN Menu

returns to the STATUS Menu. Press the soft

key in your chosen menu to return to the STATUS

screen.

Press I or J to move the asterisk “*” to the left of the desired screen. The asterisk allows access to any screen to its right.

From the MAIN Menu, a user can choose among the following MX60 functions by aligning the

asterisk:

  • Charger—CHARGER SETUP

XAdjusts the Current Limit, Absorb, and Float recharging voltage set points

  • Aux—AUX OUTPUT CONTROL

XSecondary control circuit for a vent fan, error alarm, and other system-related additions

  • Light—BACKLIGHT CONTROL

XAdjusts the backlighting of LCD screen and soft key buttons

  • EQ—BATTERY EQUALIZE

XActivates battery equalization recharging (manually or automatically)

  • Misc—MISCELLANEOUS

XAdditional settings and service information

  • Advanced —ADVANCE MENU

XOptimizing/fi ne-tuning the MX60 (these are advanced Menus that should be left alone until

the user has a good working knowledge of the MX60 and its operations)

  • Logging—DATA LOGGING

XDisplays recorded power production information

  • Log2—LOG 2

XDisplays recorded peak system information

Page 21 of the Outback Power Systems MX60 user manual — CHARGER SETUP
Page 21 · click to enlarge
Page 21

CHARGER SETUP

This screen allows changes to the MX60’s recharging voltage set points (Current Limit,

Absorb, Float):

  • The presently selected numerical value will have an asterisk “ * ” to the left of it.
  • Pressing “ J ” selects the value to be changed.
  • You may need to re-enter the password to change these settings.
  • The default charger output current limit setting is 60 amps and is adjustable up to 70 amps. At

70 amps, a 70A or 80A breaker must be used between the battery and the MX60.

  • Change Absorb and Float set points using this screen if the battery manufacturer’s recommen-

dations are diff erent than the default values. Otherwise, see page 79 for suggested recharging

voltage set points.

  • If a battery remote temperature sensor (RTS) is used, its compensated voltage values can be

viewed in the MISCELLANEOUS (Misc) screen under the Tmp Comp heading.

Please NoteIf an RTS is used, set the ABSORB

LIMIT ABSORB FLOAT Amps Volts Volts *60.0 14.4 13.6 EXIT J - +

and FLOAT setting voltage based on a 25°C / 77°F

setting. These are typically the manufacturer’s set

points (always consult the battery manufacturer’s

recommendations). If an RTS is not in use, please

see the Non-Battery Temperature Compensated

System values (page 85) and adjust the ABSORB/

FLOAT values accordingly.

Page 22 of the Outback Power Systems MX60 user manual — AUX MODE
Page 22 · click to enlarge
Page 22

AUX MODE

The AUX is a secondary control circuit—essentially, a small power supply that provides a 12 VDC

(up to 200 milliamps) output current. It is either active (12 VDC on) or inactive (12 VDC off ).

  • To access the AUX MODE from the MAIN Menu, press the < J >soft key until the asterisk is in

front of the Aux selection.

  • A 200 milliamps or less, 12 VDC device can be wired directly to the AUX terminal; higher out-

put DC loads require a 12 VDC coil relay—also rated up to 200 milliamps or less for the DC

coil—which itself is connected to the AUX output. An internal, re-settable Positive Temperature

Coeffi cient (PTC) fuse protects the AUX internal components.

  • For certain AUX control applications the use of a solid state relay is preferred. This is particularly

benefi cial with applications such as the Diversion mode where fast switching (often called PWM

control) allows a more constant battery voltage to be maintained. Both DC and AC load

switching solid state relays are widely available from many sources. Eurotherm and Power-IO

are two suggested solid state relay manufacturers.

  • Most AUX modes or functions are designed for specialized applications and are

infrequently used.

  • Only one AUX MODE can operate at a time ( even if other modes have been preset ).
  • Press the < EXIT > soft key to initiate the chosen AUX MODE.
  • See Figure 5, page 30, for an Aux set-up wiring diagram.

In this Menu, ON and

The second line indicates

AUX MODE

OFF indicators show the

the present mode for the

Manual Off EXIT NEXT ON OFF

present state of the Aux

Aux Output.

terminals. Pressing the

or soft key

When the preferred mode

changes this value.

is displayed, press the

soft key to select

ON indicates 12 VDC is

it.

present at the Aux output

Pressing the soft key changes to the next mode.

terminals. OFF indicates

0 VDC.

  • AUX MODE: what is displayed on the Menu
  • Aux Output: 12 VDC is either available or unavailable at the Aux Terminal
  • Aux Terminal: the jack to which a relay is wired

Terms

Page 23 of the Outback Power Systems MX60 user manual — J
Page 23 · click to enlarge
Page 23

*Charger Aux Light EQ Misc Advance Logging Log2 EXIT I J GO

Charger *Aux Light EQ Misc Advance Logging Log2 EXIT I J GO

AUX MODE

Manual On EXIT NEXT ON OFF

J J

PASSWORD

AUX MODE

Manual Off EXIT NEXT ON OFF

ENTER - +

J

  • Press the #1 soft key once from the STATUS Menu to open the MAIN Menu.
  • Press either of the arrow soft keys until the “*” is to the left of “Aux.”
  • Press the < GO > soft key. If more than ten minutes have passed since any activity, the PASSWORD

screen becomes active, requiring the user to input the 141 PASSWORD and press< ENTER>. This

screen will also appear after fi rst booting up the MX60 even though the password was entered

when setting the battery voltage.

AUX MODE

AUX MODE

AUX MODE

Vent Fan Off EXIT NEXT VOLT

PV Trigger Off EXIT NEXT TIME VOLT

Float Off EXIT NEXT

J J

AUX MODE ERROR ALARM On EXIT NEXT

AUX MODE

AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT

Diversion Off EXIT NEXT TIME VOLT

J J

AUX MODE

PV 005 V Bat 12.5 V 00.0 A 00.0 A Watts 0000 Aux Off kWHrs 00.0 Sleeping

Remote Off EXIT NEXT

J

AUX MODE Path · ***150***

Page 24 of the Outback Power Systems MX60 user manual — J J
Page 24 · click to enlarge
Page 24

AUX modes in order of appearance on the MX60 display:

  • Manual
  • Vent Fan
  • PV Trigger
  • Float
  • Error Alarm
  • Diversion
  • Low Battery Disconnect
  • Remote

The most commonly used AUX modes:

  • Vent Fan
  • Diversion
  • Low Battery Disconnect

When an AUX MODE is ON, 12 VDC is available at the AUX terminals and a condition, such as a

voltage set point, is met. Other modes can be programmed in lieu of the specifi c ones listed here,

but the Vent Fan mode is most easily changed (e.g., to activate an alarm instead of a fan). Here are

the default AUX modes:

  • Manual —pressing either the < ON> or <OFF> soft key manually activates or deactivates AUX.
  • Vent Fan — when the Vent Fan voltage set point is exceeded, the vent fan will run for at least

15 seconds (the fan helps remove hydrogen from battery enclosure), even if the set point is

exceeded for only a few seconds due to a surge. If the set point is exceeded for longer than 15

seconds, the fan will stay on until the voltage drops below the set point. It then takes 15 seconds

before the fan shuts off . This is an external fan and not to be confused with the MX60’s internal,

thermally activated fan which cools the unit.

  • PV Trigger —activates an alarm or relay (that disconnects the array); when the PV input is too

high and exceeds the user-determined voltage set point (should not go over 150 VDC), the PV

Trigger disconnects after a minimal adjustable amount of “Hold Time.”

  • Float —powers a load if the MX60 is producing power in the Float stage.
  • Error Alarm —useful for monitoring remote sites, switches to the “Off ” state if the MX60 has not

charged the batteries for 26 hours or more (not an audible alarm, only displayed as a printed

message on MX60 AUX Menu).

  • Diversion —diverts excess power away from batteries when a wind or hydro generator is con-

nected directly to the batteries.

  • Low Batt Disconnect —activates/deactivates the AUX load(s) when a user-determined voltage

and time levels are reached.

  • Remote —allows OutBack MATE to control the operation of the AUX MODE (see MATE manual

for details).

Page 25 of the Outback Power Systems MX60 user manual — > 14.4 BACK - +
Page 25 · click to enlarge
Page 25

Programming the AUX MODES

Press the or soft keys to manually

AUX MODE

activate or deactivate AUX MODE. Press the

Manual On EXIT NEXT ON OFF

soft key to view the Vent Fan screen. To view other

screens, continue to press the soft key.

The Vent Fan helps remove hydrogen from the bat-

AUX MODE

tery room. The ventilation fan referred to here is not

Vent Fan On EXIT NEXT VOLT

the same as the MX60 cooling fan. Press the

soft key to determine the battery voltage that will

activate the AUX MODE and start the fan.

Adjust the voltage level using the < - > and < + >

VENT FAN VOLTS

soft keys. Press the soft key to return to the

> 14.4 BACK - +

Vent Fan screen.

Page 26 of the Outback Power Systems MX60 user manual — BACK - +
Page 26 · click to enlarge
Page 26

Press the soft key to advance to the PV

AUX MODE

Trigger soft screen.

Vent Fan On EXIT NEXT VOLT

When the PV input is too high and exceeds the

AUX MODE

user-determined VOLT set point, the AUX MODE PV

PV Trigger Off EXIT NEXT TIME VOLT

Trigger activates. Press the soft key to adjust

the voltage.

Adjust the voltage within a range of 20V - 150V

PV VOLTS

by pressing the < - > or < + > soft key. Press the

soft key when fi nished to return to the PV

BACK - +

> 140 · Trigger screen

Page 27 of the Outback Power Systems MX60 user manual — AUX MODE
Page 27 · click to enlarge
Page 27

To adjust the minimum amount of time the PV volt-

AUX MODE

age must remain high before deactivating the AUX

PV Trigger On EXIT NEXT TIME VOLT

MODE, press the soft key.

Press the < - > or the < + > soft key to adjust the

Hold Time, then press the soft key to return

to the PV Trigger screen. In this example, the AUX

BACK - +

MODE will remain active for 1.1 sec after the PV volt-

age is below the PV Trigger voltage before deactivat-

ing the PV Trigger and reconnecting to the array.

Press the soft key to view the Float screen.

AUX MODE

PV Trigger Off EXIT NEXT TIME VOLT

The AUX MODE is active when the MX60 is in Float

AUX MODE

and producing power. Press the soft key to

Float Off EXIT NEXT

advance to the ERROR ALARM screen.

Hold Time Sec

Page 28 of the Outback Power Systems MX60 user manual — AUX MODE
Page 28 · click to enlarge
Page 28

The default state of the ERROR ALARM is On,

AUX MODE ERROR ALARM On EXIT NEXT

meaning 12 VDC is present at the AUX terminal. If

the MX60 has not charged the batteries for 26 hours

or more continuously, the inaudible ERROR ALARM

goes into an Off state. The ERROR ALARM is intended

for remote locations to signal (e.g., a telecommunica-

tion signal to a computer) when the MX60 has not

recharged for 26 hrs or more. See MISCELLANEOUS

Screen 3 Err for a display of the hourly countdown.

Press the soft key to advance to the

Diversion screen.

When external DC sources (wind, hydro) are directly

AUX MODE

connected to a battery bank, any excess power

Diversion Off EXIT NEXT TIME VOLT

should be sent to a diversion load, such as a heating

element. In Diversion, the user programs set points—

from -5.0 volts to 5.0 volts relative to the Absorb,

Float and EQ voltages—to activate the AUX MODE.

This is primarily an off -grid function. Pressing the

soft key advances to the Absorb-Float-EQ

screen to adjust the voltage set points.

Use this screen to establish the set points for starting

and ending the AUX MODE relative to the Absorb,

Relative Volts 00.0 00.2 BACK - + HYST+

Float, and EQ voltages. The < - > and < + > soft keys

set the Diversion set points. The (Hysteresis)

set point establishes when the AUX MODE becomes

inactive after the battery voltage falls below the

Relative Volts voltage minus the HYST value. After

establishing these values, press the soft key

to return to the Diversion screen (see example on

next page).

Absorb—Float—EQ

Page 29 of the Outback Power Systems MX60 user manual — 00.2 00.3 BACK - + HYST +
Page 29 · click to enlarge
Page 29

Press the soft key to advance to the Time

AUX MODE

screen which allows the user to adjust the minimum

Diversion Off EXIT NEXT TIME VOLT

time the AUX MODE is active after the battery volt-

age falls below the Hysteresis voltage.

Hold Time shows how long the AUX MODE stays

active after the battery voltage has fallen below the

Hold Delay 01.0 Time 00 seconds BACK - + DLY+

HYST (Hysteresis) set point. The user can adjust the

Hold Time from 0.1 to 25 seconds. If a solid state relay

is used, set the Hold time to 0.1 seconds and the

Delay time to zero.

The Delay Time shows how long the battery voltage

must be above the Relative Volts before the AUX

MODE is activated. It can be adjusted from 0 to 24

seconds, but is rarely required. Pressing the

soft key returns to the AUX MODE DIVERSION screen.

AUX MODE

Hold Delay 15.0 Time 10 Seconds BACK - + DLY +

Diversion Off EXIT NEXT TIME VOLT

00.2 00.3 BACK - + HYST +

Each recharging state—Absorb, Float, or EQ—has a recharging voltage set point. The Diversion

AUX MODE can be active (On) when the battery voltage is raised above one of these set points

for a certain amount of time or inactive (Off ) when it falls below. The user can determine these

voltages and times. In the example above, when the RE source (wind or hydro) raises the battery

voltage 00.2v above the chosen set point for a Delay time of 10 seconds—the AUX Output will be

active. When the battery voltage falls 00.3v below the HYST voltage set point for a Hold time of 15

sec – the AUX Output will be inactive (Off ). See Figure 5 for Diversion Load and AUX Wiring Set-Up.

Example of Diversion · Absorb—Float—EQ · Relative Volts

Page 30 of the Outback Power Systems MX60 user manual — 00.2 00.3 BACK - + HYST +
Page 30 · click to enlarge
Page 30
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 19
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 20
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 21
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 22
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 23
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 24
Outback Power Systems MX60 — 00.2 00.3 BACK - + HYST + diagram (page 30)
Fig. 25

Figure 5 Diversion Load and AUX Wiring Set-Up Illustrated

Page 31 of the Outback Power Systems MX60 user manual — AUX MODE
Page 31 · click to enlarge
Page 31

Press the soft key to view the Low Batt(ery)

AUX MODE

Disconnect screen.

Diversion Off EXIT NEXT TIME VOLT

When the battery voltage falls below the disconnect

AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT

volts, the AUX connected loads only are disconnected;

the loads are On when the battery voltage rises

above the reconnect volts. To adjust these set points,

press the and soft keys.

Press either the < - > or < + > soft key to adjust the

Delay Time Sec 01 Timer 001 BACK - +

delay time. This is the time period the MX60 waits

before either activating or deactivating the AUX

MODE when either the disconnect or reconnect volt-

ages are reached. When the low voltage occurs, the

timer shows the seconds remaining before discon-

necting. When the reconnect voltage is reached, the

timer shows the userdetermined time before con-

necting. Press the soft key to return to the

Low Batt Disconnect screen.

Page 32 of the Outback Power Systems MX60 user manual — RE-CONNECT VOLTS
Page 32 · click to enlarge
Page 32

In the Low Batt Disconnect screen, press the

AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT

soft key to adjust the battery voltage disconnects

set point.

Press either the < - > or the < + > soft key to adjust

DISCONNECT VOLTS

the disconnect voltage. Press the soft key

to open the RE-CONNECT VOLTS screen.

BACK - + ReCon

Press either the < - > or the < + > soft key to adjust

RE-CONNECT VOLTS

the RE-CONNECT VOLTS value. The AUX Output

>14.4

activates when the voltage goes above this setting

BACK - + DisV

after the timer has counted back to zero. Press the

soft key to return to the Low Batt Discon-

nect screen.

Page 33 of the Outback Power Systems MX60 user manual — AUX MODE
Page 33 · click to enlarge
Page 33

Press the soft key to view the Remote

AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT

screen.

In Remote AUX MODE, the OutBack MATE can control

AUX MODE

the MX60’s AUX MODE. Press the EXIT soft key twice

Remote Off EXIT NEXT

to return to the MAIN Menu screen.

Press the soft key to move the asterisk to the

Charger *Aux Light Eq Misc Advanced Logging Log2 EXIT I J GO

Light option. When the asterisk is in front of Light,

press the soft key.

Page 34 of the Outback Power Systems MX60 user manual — EQ—BATTERY EQUALIZE
Page 34 · click to enlarge
Page 34

BACKLIGHT

AUTO (default) leaves backlight and soft keys on for

BACKLIGHT CONTROL

60 seconds whenever any soft key is pressed (press-

ing any soft key when the LCD is not lighted does not

ALWAYS EXIT AUTO ON OFF

change any settings).

ON or OFF states are also available.

Press the #1soft key twice to return to the MAIN

Press the soft key to move the asterisk to the

Charger Aux *Light EQ Misc Optimize Logging Log2 EXIT I J GO

EQ option. When the asterisk is to the left of EQ, press

the soft key.

EQ—BATTERY EQUALIZE

The intent of an equalization charge is to bring all battery cells to an equal voltage. Sealed batter-

ies should not be equalized unless specifi cally instructed by the manufacturer. Shut off or minimize

all AC and/or DC loads when equalizing and be sure the EQ voltage will not damage any DC load.

If possible, ensure the EQ cycle starts and stops the same day it is initiated or unnecessary battery

gassing can occur.

  • Occasional equalization extends the life of fl ooded electrolyte batteries.
  • Proceed with caution! A vent fan is recommended in enclosed spaces.
  • The MX60 allows the user to set voltages and times of equalization process.
  • Both manual and auto modes are available.
  • EQ is not battery temperature compensated.
  • Always check the electrolyte level in the batteries before and after equalizing.

Menu screen

Page 35 of the Outback Power Systems MX60 user manual — BATTERY EQUALIZE
Page 35 · click to enlarge
Page 35

Press either the < –EQV> or soft key to

BATTERY EQUALIZE

change the EQ voltage, following your battery man-

ufacturer’s recommendations. Note that the factory

15.0 EXIT NEX -EQV +EQV

default EQ voltage is set low, the same as the factory

default Absorb voltage. Press the soft key to

view the BATTERY EQUALIZE Time screen.

Press either the or soft key to set

BATTERY EQUALIZE

the desired equalization time, up to a seven hour

Time 01 Hours EXIT NEXT -HRS +HRS

maximum, always following your battery manufac-

turer’s recommendations. Press the soft key

to view the battery equalization start screen

  • Press the < START > soft key to manually begin

BATTERY EQUALIZE 01 Hrs 15.0 Volts Check water level BACK AUTO START STOP

an equalization cycle. To stop the cycle, press the

soft key.

  • EQ-MPPT display indicates the MX60 is trying to

reach the target equalize set point.

  • Equalize time “EQ 0:00” in Hours:Minutes displays

after the equalize set point is reached.

  • The incomplete equalization cycle continues into

the next day unless the MX60 is powered off or

manually stopped. The remaining EQ time can be

viewed in the Log2 Menu.

  • EQ cycle terminates when EQ time period is

reached.

  • After equalizing, an EQ DONE message displayed

and a Float cycle begins.

Press the soft key to view the auto equaliza-

tion screen.

Volts · Manual Mode

Page 36 of the Outback Power Systems MX60 user manual — EXIT -DAY +DAY
Page 36 · click to enlarge
Page 36

Use the and soft keys to preset

COUNT EQ INTERVAL 00 000

the interval day to initiate an automatic equalization

cycle. The EQ INTERVAL displays the number of days

EXIT -DAY +DAY

in the interval between cycles and COUNT displays

how many days of the interval have passed.

  • Auto Mode initiates when a preset interval day (1-250 days) is reached.
  • The default equalize interval (EQ INTERVAL) setting is 000 day leaving the auto eq disabled.
  • “EQ-MPPT” display indicates the MX60 is trying to reach the target equalize set point.
  • The equalize time “EQ 0:00” in Hours:Minutes displays after the equalize set point is reached.
  • An incomplete equalization cycle continues into the next day unless the MX60 is powered off or

manually stopped. The remaining EQ time can be viewed in the Log2 Menu.

  • The COUNT value will be cleared to 000 when an EQ is started, manually stopped, or MX60 has

been powered off .

  • After recharging, an EQ DONE message displayed and a Float cycle begins. To view the MAIN EQ

screens, press the #1 soft key.

To view the MAIN EQ screens, press the #1 soft key.

Auto Mode

Page 37 of the Outback Power Systems MX60 user manual — MISC—MISCELLANEOUS
Page 37 · click to enlarge
Page 37

MISC—MISCELLANEOUS

The MISCELLANEOUS screens display extra settings and technical information, some of which is

useful for OutBack Power Systems Technical Services.

The Grid Tie (GT) value is sent from G-

Each MPPT operation is

This is the duty cycle of

series inverter through the MATE and

a state. This number

the converter. At 50%,

HUB for Grid Tie control communica-

is useful for OutBack

the PV terminals would

tions. GT X means MX60 is in grid tie

troubleshooting.

be twice the battery

mode and communicating with the G

voltage.

Series Inverter.

GT State PWM% ChgT 255 07 50.0 005 Tmp Comp a14.4 f13.6 EXIT NEXT WIDE RSTRT

and Float (f) set points

up in Bulk and counts

rise and fall with tem-

down in Absorb.

perature. If no RTS is used,

these settings will be

the same as those in the

charger setting screen.

This soft key covers normal and

RSTRT forces the MX60 to restart or

wake-up from 5- minute (default)

voltage range. Press WIDE and

long Snoozing mode. Restart and

Screen.

LMIT mode appears, which limits

wakeup are mainly service features.

the Upper and Lower battery-

compensated voltage range.

Show 8 more labels / short text on this page
The battery temperature · The Bulk/Absorb · compensated Absorb (a) · charge timer counts · Press NEXT to · Continue to the · limited battery compensation · Force Bulk/Float
Page 38 of the Outback Power Systems MX60 user manual — DISCONNECT VOLTS
Page 38 · click to enlarge
Page 38

WIDE/LMIT Battery Temperature Compensated Limits

During cold weather, a battery often requires a higher recharging voltage. Lower quality inverters

might not accommodate these higher voltages and can shut down during recharging, cutting off

power to their loads. The MX60 allows the user to lower the compensated voltage in the Absorb

cycle so these inverters will remain operating. Also, some batteries have an absolute voltage limit

that should not be exceeded and the WIDE/LMIT option allows the user to control this during re-

charging. WIDE allows the RTS full control over recharging; LMIT sets the ceiling and fl oor voltages

for the RTS.

During hot weather, the LMIT feature set point assures recharging will continue at a high enough

voltage rather than dropping too low in reaction to a higher ambient temperature. This assures

the recharging voltage adequately charges, but should be monitored according to the battery

manufacturer’s recommendations.

The RTS default compensated voltages apply if the WIDE/LMIT option is set to WIDE in the MISC

menu. The upper and lower LMIT settings can be viewed in the second menu of the Log2 screen

when LMIT is selected.

The LMIT set points can be set in the AUX MODE menu. To set the LMIT upper and lower set points,

press the #1 soft key once and return to the MAIN Menu. From the MAIN Menu, access the AUX

MODE screens and then the Low Batt Disconnect screen.

Path for Setting the LMIT Upper and Lower Set Points using AUX:

*Charger Aux Light EQ Misc Advance Logging Log2 EXIT I J GO

Charger *Aux Light EQ Misc Advance Logging Log2 EXIT I J GO

AUX MODE Low Batt Disconnect On EXIT NEXT TIME VOLT

DISCONNECT VOLTS

BACK - + ReCon

Press until Low Batt Disconnect appears, then press

Page 39 of the Outback Power Systems MX60 user manual — RE-CONNECT VOLTS
Page 39 · click to enlarge
Page 39

Setting LMIT Upper and Lower Set Points

In the DISCONNECT VOLTS screen, press the < -> or

DISCONNECT VOLTS

soft key to adjust the battery voltage range

limits. This should be the lowest Absorb voltage

when the battery temperature is highest. When the

desired low voltage is reached, simultaneously press

and hold the < - > and < + > soft keys until “Lower

Limit” displays on the screen. When “Lower Limit”

is displayed, the desired compensated voltage has

been stored, and the < - > and < + > soft keys can be

released (pressing the soft key will return to

the previous screen).

Press the soft key to adjust the upper

DISCONNECT VOLTS

battery compensated voltage.

Press the < - > or < + > soft key to adjust the voltage.

RE-CONNECT VOLTS

When fi nished, simultaneously press and hold the

>14.8 BACK - + DisV

< - > and < + > soft keys until Upper Limit is dis-

played. This should be the highest Absorb voltage

when the battery temperature is coolest.

Page 40 of the Outback Power Systems MX60 user manual — RE-CONNECT VOLTS
Page 40 · click to enlarge
Page 40

When the Upper Limit is displayed, the desired com-

RE-CONNECT VOLTS

pensated voltage has been stored and the < - > and

>14.8 Upper Limit BACK - + DisV

< + > soft keys can be released.

After setting these limits, AUX MODE should be set to

Manual (default setting) if not used.

Equalize charging mode.

Pressing the soft key returns to the Low Batt

Disconnect screen.

To confi rm the Upper Limit and Lower Limit voltages

*Charger Aux Light EQ Misc Advance Logging *Log2 EXIT I J GO

PkBatV Voc HiVoc 014.7 021.2 022.1 B-MPPT Sunrise EXIT NEXT 00:03:43

0000 fl oatTmin 0850 HighWatts Lo 13.2 Hi 14.8 BACK DCkWh

PkBatV Voc HiVoc 014.7 021.2 022.1 B-MPPT Sunrise EXIT NEXT 00:03:43

PV 011 V Bat 13.4 V 00.0 A 00.0 A Watts 0000 Aux On kWHrs 00.0 Sleeping

Limit Set Points (visible and active when WIDE/LMIT is set to LMIT in the Misc Menu)

Page 41 of the Outback Power Systems MX60 user manual — FORCE EXIT NEXT FLOAT BULK
Page 41 · click to enlarge
Page 41

After confi rming the Upper Limit and Lower Limit voltages, press the soft key in the MAIN

Menu. Press the soft key to advance to the fi rst MISC screen. From this screen, you can

access MISCELLANEOUS Screen 2.

From the MISC screen, press the soft key to

GT State PWM% ChgT 255 07 50.0 005 Tmp Comp a14.4 f13.6 EXIT NEXT WIDE RSTRT

view the FORCE, FLOAT, or BULK screen.

Pressing the or soft key forces the

MX60 to that specifi c recharging cycle and returns to

the STATUS screen. Forcing a FLOAT or BULK recharge

FORCE EXIT NEXT FLOAT BULK

will end an EQ cycle. Press the soft key to

view the third MISCELLANEOUS screen.

  • Force FLOAT = fl oat cycle
  • Force BULK = bulk cycle
Page 42 of the Outback Power Systems MX60 user manual — MISCELLANEOUS Screen 3
Page 42 · click to enlarge
Page 42

MISCELLANEOUS Screen 3

This is the assigned number

Btmp is a battery temperature

increases hourly if the

sensor reference value used to

of the internal components

MX60 has not charged

compensate the charging volt-

to control the cooling fan. The

the batteries for 26+

age. This is an arbitrary number

lower the number, the higher

hours continuously.

between 0 and 255 and is not

the temperature. 25° C is ap-

The fi rst hour begins at

the actual temperature. An ‘X’

proximately a value of 525.

sleeping.

next to this value indicates a

Global external RTS is being used

(system with a HUB and MATE).

In Float, if the battery volt-

age falls below the ReBulk

voltage set point for at

PCB Err Btmp CFB 398 000 255 0760 ReBulk 06 V End 00 A EXIT +ReBV –AMP +AMP

of the internal cur-

least 90 seconds, the MX60

rent sensor is used

a Bulk charge cycle. The

default is set to a very low

value (6 volts) and there-

Power Point of the

fore the function will be

array.

disabled.

+ReBV increments the ReBulk

(End, -AMP, +AMP) Normally, an Absorb charge cycle is ter-

Voltage. It will return to a 6 volt

minated because the battery voltage was regulated at the

value when a 69 volt value is

Absorb set point for the maximum time period. Decreasing

reached.

(-AMP) or increasing (+AMP) sets an optional end current

level. While the battery voltage is at or above the Absorb

target and the End current level is reached at a time delay

of 15 seconds, the MX60 will switch to the Float charge

stage regardless of the charger time minutes. The charger

timer (ChgT) will be cleared. This is an optional set point

and its adjustment is not required in most installations. “00”

Absorb End amps is the default.

Show 7 more labels / short text on this page
The Err(or) count · representing the temperature · The output value · will automatically reinitiate · to calculate output · amps, watts, and · track the Maximum
Page 43 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 43 · click to enlarge
Page 43

ADVANCED

The ADVANCED MENU allows fi ne-tuning of the MX60 operations including “Snooze” periods and

Maximum Power Point limits. In order of appearance, the following modes occur in the ADVANCED

Menu selections:

XSnooze Mode XPark Mpp (% Voc) X MPP Range Limit % Voc X Sweep Interval XVbatt

Calibration XLow CutOff XMPPT Mode X Absorb Time Limits XWakeup Mode

From the MAIN Menu, choose Advanced and press

Charger Aux Light Eq Misc *Advanced Logging Log2 EXIT I J GO

the soft key.

The MX60 wakes up when an optimal amount of

open circuit voltage (Voc) is available. The Voc varies

with external conditions, primarily the weather and

time of day, which aff ect solar panels. If the Voc is

insuffi cient, the MX60 enters “Snoozing” until either

a fi ve-minute (default) period passes or there is a 1.5

volt (default) increase in Voc at which point the MX60

reevaluates the Voc for recharging purposes. What

is the optimal amount? The MX60 tries to recharge

when the Voc is greater than the battery voltage by 2

volts, but voltage alone isn’t suffi cient. An array might

have a big increase in voltage fi rst thing in the morn-

ing— more than 2 volts diff erence—but not enough

ampacity to recharge.

ADVANCED MENU

Snooze Mode < Lowcutoff EXIT NEXT MODE

Snoozing also occurs if the recharging current does

not reach the user-selected cutoff current set point in

the Lowcutoff menu. Press the soft key for

Snooze Mode options. Press the soft key for

the Park Mpp screen

  • <90% Voc—MX60 snoozes if Voc does not rise to greater than 90% of last measured Voc during a
  • <50% Voc—snoozes if Voc does not rise to greater than 50% of last measured Voc during a
  • <Lowcutoff —default snooze mode, snoozes if initial sweep does not reach Low Cutoff Amps

during a full sweep

  • Disabled—no snoozing, MX60 will cycle on and off many times ( not recommended due to

full sweep · full sweep · ongoing relay-clicking)

Page 44 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 44 · click to enlarge
Page 44

Auto Sweep MPPT Mode (see page 46) seeks the

ADVANCED MENU

solar array’s maximum available voltage to recharge

Park Mpp 77 % Voc EXIT NEXT -Voc +Voc

the batteries. The MX60 is best left in this default

mode for most recharging purposes. If the output

current is below fi ve amps (e.g., overcast day or early

mornings and late evenings), the MX60 will operate

at the percentage of the Voc shown on the Park Mpp

(Maximum Power Point) screen. The 77% Voc default

is close to the MPP for most arrays. A higher value

may be necessary for diff erent applications such as a

12 VDC array to a 12 VDC battery. To change the per-

centage of Voc, press either the or

soft key. Press the soft key to view the next

ADVANCED MENU screen.

The Mpp Range Limit % Voc adjusts the upper Mpp

ADVANCED MENU Mpp Range Limit %Voc min max EXIT NEXT 1/2 90%

limit of the Voc. The default MX60 MPP voltage limit

is set at 90% of the Voc and is normally left alone for

an array. If an MX60 sweep fi nds an MPP voltage out-

side of this range, it will revert to the Park Mpp value.

Setting to 1/2 reduces the initial sweep time on a

high input voltage array.

The MPP adjustable MX60 limits are 80%, 85%, 90%,

Use ½ value for high input arrays to speed up initial sweep.

and 99% of the Voc. The min range limit setting may

be set to FUL if something other than a PV array is

connected to the input of the MX60, such as a Micro-

Hydro generator (see page 54), but the Voc cannot

exceed 150 VDC at any time. Press the or

soft key to adjust the MPP range limit. When

done, press the soft key to view the Sweep

Interval screen.

Page 45 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 45 · click to enlarge
Page 45

The Sweep Interval mode or mini-sweep deter-

ADVANCED MENU

mines how often a sweep occurs, ranging from 0-15

Sweep Interval 07 Minutes EXIT NEXT -MIN MAX+

minutes. A sweep is a search for the best MPP for the

array. At zero minutes, the MPPT mini-sweep function

is disabled (this is not recommended for PV arrays).

No sweeping occurs if the output current is under

fi ve amps because it operates at the Park Mpp value.

Sweeping does occur when the output current is

higher than fi ve amps or to maintain user current

limit and to track the MPP of the array throughout

the day. A mini-sweep is an accurate but less exten-

sive version of the full initial sweep done at wakeup.

Press the soft key to decrease minisweep

interval minutes or press the soft key to

increase the minutes. Press the soft key to

view the Vbatt Calibration screen.

A quality calibrated voltmeter will provide even more

ADVANCED MENU

accurate MX60 battery voltage readings if an un-

Vbatt Calibration 12.8v 0.0v EXIT NEXT -V +V

desirable voltage drop is present. When measuring

battery voltage, ensure a good connection is made

to the Four-Position Terminal Block. Check the bat-

tery temperature compensation voltages if voltages

are much diff erent than you expect from the charger

setup Absorb and Float voltage settings. Use the

The present Vbatt meter reading is displayed here for convenience.

and soft keys to match the readings from

the voltmeter. When fi nished, press the soft

key to view the next screen.

Page 46 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 46 · click to enlarge
Page 46

Low Cutoff sets the battery charger’s lowest allow-

ADVANCED MENU Low Cutoff < .6 Amp EXIT NEXT +AMP

able current limit the MX60 will charge in MPPT

mode before stopping and returning to “Snoozing.”

The Low Cutoff is adjustable from .2 amps to 1 amp;

.6 amps is the default Low Cutoff current. Raising

this value will assist the MX60 in entering “Sleeping”

mode at night. Press the soft key to raise

this limit. When fi nished, press the soft key

to view the MPPT Mode screen.

This screen allows the user to choose one of these

ADVANCED MENU

modes:

MPPT Mode Auto Sweep EXIT NEXT nonGT MODE

  • Auto Sweep MPPT Mode (the default and preferred

mode), which sweeps the PV upon wakeup and

then does mini Sweeps from that point on at the

selected Sweep Interval. If the sweep interval is set

at 0 minutes, the MX60 awakes every 1.5 hours and

does a full sweep. Auto Restart applies here as well

(see LOG2 Auto Restart, page 52).

The default value is nonGT or non-grid-tied. Select GT mode if you have a GVFX or GTFX inverter, MATE and HUB connected to the MX60. Selecting GT estab- lishes the proper grid-tie mode communications between the G-series FX and the MX60.

  • U-Pick % (Voc) MPPT mode operates the PV voltage

at a user-selected percentage of the Voc which is

displayed in the Park Mpp % Voc screen. U_Pick %

acquires a new Voc value every Sweep Interval. If

the mini-sweep interval is set to 0 minutes, a new

Voc may be acquired once every 1.5 hrs. depend-

ing on the Auto Restart setting (see LOG2 Auto

Restart, page 52). This is an alternative to the Auto

Sweep mode and may also be useful for micro-hy-

dro applications.

Press the soft key to choose an MPPT

mode and the soft key if you have an Out-

Back G-series inverter system with a HUB and MATE.

Press the soft key to view the Absorb Time

Limits screen

Page 47 of the Outback Power Systems MX60 user manual — S N O O Z E
Page 47 · click to enlarge
Page 47

In the Absorb Time Limits screen, the user can set the

ADVANCED MENU Absorb Time Limits 000m 2hr EXIT NEXT MIN+ MAX+

minimum and maximum times the MX60 stays in the

Absorb recharge cycle.

J MAXimum is adjustable from 0 to 4 hours.

J MINimum is adjustable from 0 minutes (the

default) up to the maximum absorb time limit

minus 10 minutes. (EXMaximum Absorb time =

2 hours or 120 minutes Minimum Absorb time

adjusted up to 110 minutes)

To adjust the limits, press either the or

soft key. When fi nished, press the

soft key to view the next screen.

  • A Bulk cycle starts each morning. The charge timer (ChgT) is preset to the minimum Absorb time

limit (zero minutes) while the Bulk/Absorb Charge Timer counts up in minutes.

  • The timer stops when it reaches the Maximum Absorb Time or the Absorb voltage set point is met.
  • The ChgT counts down to zero after the Absorb voltage is reached.
  • At zero, the MX60 goes into Float stage and may briefl y display “Bat Full” (Battery Full) then “Float.”
  • When the battery voltage drops below the fl oat voltage set point, the MX60 recharges to main-

tain this set point, employing the F(Float)-MPPT function.

  • If the system cannot maintain the Absorb voltage set point during the Absorb cycle, the timer

will stop counting down and begin counting up towards the Max Absorb time as the MX60

transitions to Bulk (BMPPT). This up and down counting will continue until the charge timer counts

down to zero. The Absorb cycle can be disabled by setting the maximum to 0hr.

S N O O Z E

BULK

S N O O Z E

ABSORB

FLOAT

Z Z Z Z SLEEP

PV ARRAY VOLTAGE

SLEEP

Z Z Z Z

XBulk cycle begins XAbsorb charge is reached XAt zero, MX60 goes into FLOAT X Timer starts XTimer begins counting to zero

timer’s set points.

Page 48 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 48 · click to enlarge
Page 48

Wakeup Mode selects how often the MX60 does a

ADVANCED MENU

“Wakeup” during “Snoozing” periods. Since environ-

Wakeup Mode 01.5v 05m EXIT NEXT +VOC +Min

mental condition impact the open circuit voltage

(Voc) of an array, a user selectable Voc rise in value

will allow the controller to “wakeup” sooner or later

based on the last measured Voc value. A selectable

delay time in minutes will also allow the control-

ler to “Wakeup” sooner or later if the measured Voc

did not meet the user selectable Voc rise in value.

Before changing these values, monitor your system

for a week or so using the factory defaults and then

gradually adjust the set points. If they’re set too high,

the MX60 might not wake up soon or often enough,

which means a loss of power production. Note:

+VOC ranges from 1.5V up to 9.5V. +MIN ranges from

5 up to 15 minutes. Press the soft key to

return to the MAIN Menu.

From the MAIN Menu, press the soft key to

Charger Aux Light Eq Misc *Advanced Logging Log2 EXIT I J GO

move the asterisk next to the Logging function and

then press the soft key.

Page 49 of the Outback Power Systems MX60 user manual — CLEAR BACK TOTL DALY
Page 49 · click to enlarge
Page 49

(DATA) LOGGING

The MX60 records battery fl oat and daily kilowatt-hour (kWh) information for the previous 64 days.

This data can be compared, for instance, with weather reports to confi rm the MX60’s performance.

When 64 days are reached, for every new day of data recorded, a day is eliminated from the front

end of the count in the order they were recorded.

The minutes the MX60

spent fl oating the bat-

may be viewed as amp

teries for each of the

last 64 days. The pres-

ent day’s Float time can

setting in the STATUS

be found in the Log2

DAILY KWhours 00.0 Float time mins 0000 TotalKWh 0000 01 EXIT CLR +DAY -DAY

screen. The TotalKWh or

screens.

the daily values and

Day 01 is yesterday and

Day 02 is two days ago,

days of data.

etc.

Pressing CLR takes you to the CLEAR,

Press – DAYgoes back one day Press +DAY :

DALY (DAILY), and TOTL (TOTAL) Menu

goes forward one day

and EXIT takes you back to the main

STATUS screen.

If starting on Day 01 and +DAY is pressed, the

value from 64 days ago is presented.

CLEAR BACK TOTL DALY

Pressing and holding the TOTL or DALY (TO-

TAL AND DAILY) soft key will prompt you to

erase those total accumulated values. Press-

ing BACK returns to the Logging screen.

Show 5 more labels / short text on this page
Total power production · hours or kilowatt-hours · depending on display · TotalKAh accumulates · continue beyond 64
Page 50 of the Outback Power Systems MX60 user manual — Charger Aux Light Eq Misc Advanced *Logging Log2 EXIT I J GO
Page 50 · click to enlarge
Page 50

Clearing Totals and Daily Stats

  • Pressing and holding TOTL for three seconds brings up the “ Are you sure? ” screen, prompting you

to clear the total accumulated kWh and kAh statistical values in the MX60.

  • Pressing and holding DALY for three seconds will bring up the “ Are you sure? ” screen for clearing

all of the 64 Daily logged values. After Yes is confi rmed, the values will be cleared. It may take a

few seconds for all 64 daily values to be cleared before the confi rmation screen goes away.

  • Pressing BACK brings back the Logging screen.

diff erent days, their numeric dates will not be the same. This can lead to some misunderstand-

ings when looking back and comparing data between the two or more units. A user looking

back at day 12 on both units would fi nd very diff erent results.

To return to the MAIN Menu, press the #1 soft key from any screen.

From the MAIN Menu, press the soft key to

Charger Aux Light Eq Misc Advanced *Logging Log2 EXIT I J GO

move the asterisk next to the Log2 function and then

press the soft key.

Page 51 of the Outback Power Systems MX60 user manual — LOG2
Page 51 · click to enlarge
Page 51

LOG2

The Log2 screen displays additional voltage and time information.

Daily high Voc value

The highest Voc seen by the MX60

Sunrise shows how long

PkBatV Voc HiVoc 012.2 070.2 076.9 B-MPPT Sunrise EXIT NEXT 00:06:12

ago the MX60 woke up

for the fi rst time each day

and when the daily and

total logged values were

updated and cleared from

the STATUS screen.

Pressing and holding the #3 soft key

toggles 24/25 hour save mode. Soft key

#4 addresses Auto RESTART mode.

PkBatV logs the peak battery voltage and operational mode simultaneously, updating daily at fi rst

wakeup; it can also be reset to the present battery voltage by powering off the controller. This

helps determine any degree of voltage overshooting. The peak battery voltage should not be used

to identify that the controller has charged the battery to a higher voltage than its regulation set

point. NoteIf controller power is disconnected, the BatTmpErr becomes the default operational

mode until the controller wakes up.

Daily peak · battery voltage · Operational mode

Page 52 of the Outback Power Systems MX60 user manual — LOG2
Page 52 · click to enlarge
Page 52

Pressing and holding the #4 soft key for several

PkBatV Voc HiVoc 012.2 070.2 076.9 B-MPPT Sunrise EXIT NEXT 00:06:12

seconds selects among the three MX60 Auto

ReStart modes0, 1, and 2 (default). Auto ReStart

allows the MX60 to perform internal recalibrations

and eliminate any possibility of software errors. To

change the mode, release the #4 soft key and press

and hold again.

  • Mode 0— Auto ReStart mode is disabled; the

MX60 recharges continuously from an available

source and never Restarts. Mode 0 would be

chosen to avoid spinning a microhydro generator

every 1.5 hours.

  • Mode 1—once every 1.5 hours, when the MX60 is

in Bulk, it will briefl y Restart and initiate a full panel

sweep. This will not reset any counters or charging

stages or statistics.

  • Mode 2— Auto ReStart every 1.5 hours; in Bulk,

Absorb, and Float modes, it will briefl y Restart and

initiate a full panel sweep. This will not reset any

counters or charging stages or statistics.

The MX60’s sunrise-related activity can be infl uenced. During certain days of the year, the sun

never “sets” in parts of Alaska, for instance, and the PV output is constant. The MX60 responds to

these situations by generating its own sunrise reading at either 24 or 25 hours with 25 hours being

the default value. After this 24 or 25 hour period, the MX60 automatically initiates a BULK cycle and logs

the daily KiloWattHour / AmpHour statistics and Float Time to be logged and accumulated in the

Logging screen. Pressing down and holding the third soft key, then releasing and pressing and

holding again for a few seconds, will toggle the value between 24 and 25 hours. Mini-sweeps at

the selected sweep interval will initiate on time in either of these modes. Press the soft

key to view the secondary Log2 screen.

After 3 hours of sleeping, the MX60 displays “Zzzz….” This means that the next wakeup will cause

the daily KiloWattHour / AmpHour statistics and Float Time to be logged and accumulated in the

Logging screen. This (the next wakeup) will also initiate a Bulk charge cycle.

Show 4 more labels / short text on this page
Auto Restart · 0 Auto Restart · 1 Auto Restart · 2 Auto Restart
Page 53 of the Outback Power Systems MX60 user manual — LOG2
Page 53 · click to enlarge
Page 53

The Secondary Log2 screen shows the basic recharging state of the MX60 (EQ, FLOAT) time in min-

utes, and the daily maximum (HighWatts) wattage seen by the MX60 during the day.

The present day’s time—

displayed here.

Float stage.

0000 fl oat Tmin 0705 HighWatts Lo 13.2 Hi 14.8 BACK DCkWh

The lower and upper

This value is the peak

daily Watts seen by the

MX60.

is visible and active

mode is set to LMIT

(5.11 Rev.).

Press soft key #3 to display the accumulated total

kWh reading in AC or DC the Data

Logging screen.

  • DCkWh (default) shows DC kiloWatthours and

should be used in a non grid tied system.

  • ACkWh is used with a grid tied system. The

heading in the logging screen will change to

“TotalKWh AC”. TotalKWh AC is based on a 90%

inverter effi ciency (1kWH DC = 0.9kWH AC).

power source keeps the battery above fl oat voltage.

Show 7 more labels / short text on this page
Secondary LOG2 Screen · When initiated, EQ · information will be · in minutes—spent in · battery temperature · compensation voltage · only when the
Page 54 of the Outback Power Systems MX60 user manual — MICRO-HYDRO AND FUEL CELL SYSTEMS PERFORMANCE OPTIMIZATION
Page 54 · click to enlarge
Page 54

MICRO-HYDRO, WIND TURBINE, AND FUEL CELL APPLICATIONS

The MX60 is designed to work with solar arrays. Although it will work with micro-hydro and fuel

cell, OutBack Power Systems can only off er limited technical support for these applications be-

cause there is too much variance in micro-hydro and fuel cell generator specifi cations. When used

for micro-hydro or fuel cell applications, the MX60 warranty will be honored only if the manufac-

turer and turbine model have been approved by OutBack Power Systems. Please check with one of

the following manufacturers or OutBack Power Systems before employing the MX60:

www.harrishydro.com

Alternative Power & Machine

www.apmhydro.com

Energy Systems & Design

www.microhydropower.com

The MX60 is not compatible with wind turbine applications and OutBack cannot warranty its use in

these applications.

MICRO-HYDRO AND FUEL CELL SYSTEMS PERFORMANCE OPTIMIZATION

Micro-hydro and fuel cell systems are diff erent than PV systems, whose Voc output is more subject

to change due to weather and time of day. A PV system normally fi nds its Maximum Power Point

voltage between 50-90% of its Voc. The default value for the MX60 is 77% of a solar array’s Voc and

is displayed on the Park Mpp screen. A microhydro or fuel cell system’s MPP voltage can be outside

of this range.

The MX60 allows a user to experiment and fi nd more appropriate set points to best capture the

MPP voltage. If the output current is under fi ve amps, Auto Sweep will park the voltage using

whatever percentage value is displayed in the Park Mpp screen. Otherwise, Auto Sweep begins

sweeping the Voc output and works its way down until the optimum percentage of input voltage

yields the MPP voltage. If U-Pick % Voc is chosen, the MPP is calculated by whatever value is found

in Park Mpp, even if it’s not the optimal value for determining the MPP voltage. For this reason,

OutBack normally suggests leaving the system in Auto Sweep mode and the 77% default percent-

age value, but recommends experimenting with changing this value when a micro-hydro or fuel

cell system is in use.

Show 7 more labels / short text on this page
• · Harris Hydroelectric · (831) 425-7652 · • · (541) 476-8916 · • · (506) 433-3151
Page 55 of the Outback Power Systems MX60 user manual — MICRO-HYDRO, WIND TURBINE, AND FUEL CELL APPLICATIONS
Page 55 · click to enlarge
Page 55

To adjust these values and enhance the performance of these systems, use the MX60 ADVANCED

MENU to make changes. To determine your micro-hydro or fuel cell system’s best settings for MPP

voltage, do the following:

1. Use Auto Sweep and record the watts yielded. This value should be in line with your generator

capacity.

2. Switch to U-Pick % Voc mode and input diff erent Park Mpp percentage values, checking the

watts value for each. This will require some experimentation.

  • The MX60 can operate at any of the following fi xed percentages, selected in the” Park Mpp”

screen in the ADVANCED MENU selection:

40%, 50%, 67%, 70%, 72%, 75%, 76%, 77%, 78%, 80%, 81%, 83% or 85% of the measured

  • The user will have to experiment with each of the 13 fi xed percentage values to

determine an appropriate fi xed percentage value. Typical fi xed values between 67% up to

78% have provided optimal results; however, each system is diff erent and these fi xed

percentage values should be used as guidelines only

3. Compare the Auto Sweep and U-Pick % Voc values and determine which will best fi t

your system.

In addition to establishing the best mode and percentage values for determining the MPP voltage,

a user can also adjust the sweep interval and the range of values the MX60 uses to search for the

MPP voltage.

(If necessary, re-enter the system password 141 at any point while optimizing the

system’s performance.)

open circuit voltage

Page 56 of the Outback Power Systems MX60 user manual — ADVANCED MENU (Micro-Hydro)
Page 56 · click to enlarge
Page 56

ADVANCED MENU (Micro-Hydro)

Mpp Range Limit % (Auto Sweep Mode only)

The MX60 searches for the MPP voltage by sweeping the input voltage up to one half (default) of

the Voc, which is based on values appropriate for a solar array. Micro-hydro and fuel cell systems

can require a broader range, normally on the lower end. Adjusting the lower limit, expressed as 1/2

on the display screen, for FULL allows the MX60 to sweep the input voltage close to the battery

voltage instead of 1/2 (or 50%) of the Voc.

This adjustment only aff ects the initial sweep at the beginning of the day and any subsequent sweeps

caused by Auto-Restart or any forced restart of the MX60.

In addition to adjusting the Mpp Range Limit, changing the Sweep Interval from its default three-

minute setting to zero minutes will also enhance the performance and reliability of some applica-

tions’ voltage input system.

To adjust the Lower Mpp Range Limit and disable the Sweep Interval:

From the MAIN Menu, with the asterisk in front of

Advanced, press the soft key. Charger Aux Light Eq Misc *Advanced Logging Log2 EXIT I J GO

Page 57 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 57 · click to enlarge
Page 57

In the ADVANCED MENU screen, press the

ADVANCED MENU Mpp Range Limit %Voc min max EXIT NEXT 1/2 90%

soft key until the Mpp Range Limit % VOC screen

appears. Press the soft key until FULL appears.

When fi nished, press the soft key to go to

the Sweep Interval screen.

In the Sweep Interval screen, press the soft

ADVANCED MENU

key to adjust the sweep interval from 03 minutes

Sweep Interval 03 Minutes EXIT NEXT -MIN MAX+

(default) to 00 minutes. Press the soft key

until the MPPT Mode screen appears.

To pick between Auto Sweep or U-Pick % MPPT

Mode and determine the MX60’s operating Voc per-

centage, press the soft key until the MPPT

Mode Menu appears.

Press the soft key to interchange between

ADVANCED MENU

Auto Sweep and U-Pick%Voc modes. Re-entering

MPPT Mode Auto Sweep EXIT NEXT nonGT MODE

the password might be required. Press the

soft key in the ADVANCED MENU until the Park Mpp

screen appears.

Page 58 of the Outback Power Systems MX60 user manual — ADVANCED MENU
Page 58 · click to enlarge
Page 58

Press the or soft key to select one

ADVANCED MENU

of the 13 fi xed percentage values. Park Mpp applies

Park Mpp 77 % VOC EXIT NEXT –Voc +Voc

to Auto Sweep Mode if the output current is less

than 5 amps; U-Pick always uses the Park Mpp value.

Press the soft key until the MPPT Mode

screen appears.

new values.

Page 59 of the Outback Power Systems MX60 user manual — ADVANCED MENU (Micro-Hydro)
Page 59 · click to enlarge
Page 59

In the STATUS screen, press the #3 and #4 soft keys

PV 087 V Bat 12.0 V 05.0 A 35.8A Watts 0430 Aux Off kWHrs 00.0 B-MPPT

simultaneously to perform a Mini-Sweep. The MX60

will track the new MPP based on the fi xed percent-

age value. Perform a Mini-Sweep any time a change

to the input system or the Park Mpp fi xed percent-

age value is changed. In U-Pick %Voc mode, press the

#3 and #4 soft keys and the New Voc is displayed; in

Auto Sweep mode, press the #3 and #4 soft keys until

Sweeping is displayed.

A user might want an MPP that falls outside of the fi xed percentages available in Park Mpp. With

the MX60, a user can manually adjust these values by single percentage points while observing a

change in the instantaneous watts made available with these adjustments.

To manually track and change the MPP voltage in either the Auto Sweep or U-Pick %Voc

MPPT Modes:

Press and hold the #3 soft key to decrease the power

PV 087 V Bat 12.0 V 05.0 A 35.8A Watts 0430 Aux Off kWHrs 00.0 B-MPPT

point voltage (PV voltage). Press and hold the #4 soft

key to increase the power point voltage (PV voltage).

Observe the changes in the Watts value to determine

whether increasing or decreasing the PV voltage will

improve the available power to the system.

Press either soft key to adjust PV voltage

Page 60 of the Outback Power Systems MX60 user manual — THIS PAGE INTENTIONALLY LEFT BLANK
Page 60 · click to enlarge
Page 60

THIS PAGE INTENTIONALLY LEFT BLANK

Page 61 of the Outback Power Systems MX60 user manual — APPLICATION NOTES
Page 61 · click to enlarge
Page 61

APPLICATION NOTES

OutBack Power System GTFX/GVFX Grid-tie settings

In a GFX/GVFX series inverter, MX60, HUB, and MATE installation set the MX60 to GT mode in the

ADVANCED MENU. The GT mode allows the GFX/GVFX series inverter to manage the MX60 fl oat

setting ensuring the MX60 is always keeping the battery above the sell voltage of the GFX/GVFX.

Grid-tie applications (non-OutBack inverter/chargers)

When selling electricity back to the grid, keep the inverter Sell/Float voltage below the MX60 fl oat

voltage. Appropriate values: 0.5 Volts diff erence for 24V battery system or 1.0 volt diff erence for 48V

battery systems.

Diversion using hydro or wind power

With wind or hydro generator applications, keep the MX60’s diversion voltage slightly above its

Absorb and Float voltages for effi cient functioning.

Telcom applications frequently require a positive grounded system. The MX60 switches the POSI-

TIVE PV and battery leads. Keep these separate. If code allows, ground ONLY the battery positive

lead in this case. Do not connect the MX60’s battery plus to the PV plus input while the MX60 is

running. The OutBack HUB cannot be used in a positive grounded system.

Battery temperature compensation with other slopes

The MX60 uses a -5mV per degree C per cell (2V) compensation slope required by UL. For other

slopes, you may be able to pick a diff erent battery voltage and change the charger Absorb and

Float voltage settings to achieve a more or less aggressive slope. If going lower in voltage, reduce

the Float voltage fi rst, since the Absorb voltage will not be adjustable below the Float voltage

setting. If going higher in voltage, increase the Absorb setting fi rst before raising the Float voltage

above the present setting. Here is a table of MX60 compensation based on system voltage for

reference:

12V system -30mV/degree C

24V system -60mV/degree C

36V system -90mV/degree C

48V system -120mV/degree C

60V system -150mV/degree C

Positive grounded systems

Page 62 of the Outback Power Systems MX60 user manual — CALLING THE FACTORY FOR ASSISTANCE
Page 62 · click to enlarge
Page 62

CALLING THE FACTORY FOR ASSISTANCE

When calling OutBack Power for product assistance, please have the following information

ready:

  • MX60 Serial number and software version (The software version can be viewed by pressing

the #1 soft key on the STATUS screen and then pressing a second time and holding the soft

key down.)

  • the nominal PV array and battery voltage
  • the PV array operating voltage and battery current and any Status screen operational mode

displays, such as B-MPPT, F-MPPT, Absorbing, or Float

Page 63 of the Outback Power Systems MX60 user manual — SPECIFICATIONS
Page 63 · click to enlarge
Page 63

SPECIFICATIONS

Output Current Rating 60 amps continuous @ 25°C ambient

Default Battery System Voltage 12, 24, 36, 48 or 60 VDC (adjustable)

PV open circuit voltage 150 VDC Maximum (ETL Rating for UL1741

Standard); operational max = 141 VDC

Standby power consumption Less than 1 watt typical

Recharging regulation methods Five stage—Bulk, Absorption, Battery Full, Float,

Voltage regulation set points 13-80VDC

Temperature compensation With optional RTS sensor 5 millivolts °C per

Voltage step down capability Down convert from any PV array voltage within

PV voc limits of 141 VDC to any battery system

Examples72V array to 24V; 60V array to 48V

Digital Display 4 line 20 character per line backlit LCD display

Remote Interface RJ45 modular connector Cat 5 cable 8 wire

Operating Temperature Range* -40° to 60°C de-rated above 25°C

Environmental Rating Indoor type 1

Conduit knockouts Two 1/2-3/4” on the back; one 3/4-1” on each

side; two 3/4-1” on the bottom

Warranty Two years parts and labor, optional extended

Dimensions MX60—13.5”H x 5.75”W x 4”D

Boxed—18”H x 11W x 8”D

Weight MX60—12 pounds Boxed—15 pounds

Show 5 more labels / short text on this page
temperature corrrected VOC · and Equalization · 2V cell · voltage · warranty available
Page 64 of the Outback Power Systems MX60 user manual — SPECIFICATIONS
Page 64 · click to enlarge
Page 64

*The MX60’s maximum current output at 25°C is 60 amps. In higher ambient temperatures, the

MX60’s current limit should be reduced in order to prevent possible damage to the unit. Realisti-

cally, given that the solar array also reduces its current output when the ambient temperature

increases, a user will probably never have to adjust the MX60’s current limit. To do so, go to the

STATUS screen and choose the Charger function.

Press the soft key after aligning the asterisk in

*Charger Aux Light EQ Misc Advanced Logging Log2 EXIT I J GO

front of the selected menu choice.

Press I or J to move the asterisk “*” to the left of the Charger function.

Press J to move the asterisk in front of the Amps

LIMIT ABSORB FLOAT Amps Volts Volts *60.0 14.4 13.6 EXIT J - +

selection (default is 60.0) and adjust this fi gure using

the “ –“ and “ + “ soft keys using the fi gures in follow-

ing MX60 Current vs. Temperature Chart. Remember

to change the current limit when the ambient tempera-

ture changes.

Page 65 of the Outback Power Systems MX60 user manual — SPECIFICATIONS
Page 65 · click to enlarge
Page 65

MX60 Current Vs Temperature (all temps Celsius)

Ambient Temperature Maximum Current (amps)

25 60.00

30 57.45

35 54.77

40 51.96

45 48.99

50 45.83

55 42.43

60 38.73

65 34.64

70 30.00

75 24.49

80 17.32

An easy de-rating rule to use in lieu of the above table is “1 amp per degree C.” Altitude should also

be factored into de-rating. Use the following table to determine altitude-related values.

0 / sea level 1.00

1000 / 3,000 0.95

1500 / 5,000 0.90

2000 / 7,000 0.86

3000 / 10,000 0.80

3500 /12,000 0.75

Table 1 · Altitude Meters/Feet Factor · Table 2

Page 66 of the Outback Power Systems MX60 user manual — SPECIFICATIONS
Page 66 · click to enlarge
Page 66

MX60 EFFICIENCY vs. INPUT POWER GRAPH

Outback Power Systems MX60 — SPECIFICATIONS diagram (page 66)
Fig. 26

Figure 6 24V and 48V Battery System Effi ciency Curve

Page 67 of the Outback Power Systems MX60 user manual — UNDERSTANDING THE VARIOUS OPERATIONAL MODES
Page 67 · click to enlarge
Page 67

UNDERSTANDING THE VARIOUS OPERATIONAL MODES

The MX60 modes of operation will change occasionally during the day based on the PV array

output and the battery system state of charge. The MX60 operating modes are displayed at the

bottom right hand corner of the STATUS screen.

Absorb-EX There is an external DC source other than solar keeping the battery above the Absorb

set point. The MX60 will not be producing power.

Absorbing The MX60 is in the Absorb (constant voltage) charge stage, regulating the battery volt-

age at the Absorb set point (modifi ed by battery temperature compensation if installed). During

this cycle, the ChgT counter in the Misc menu is counting down towards zero. If the system cannot

regulate the battery voltage at the Absorb voltage set point, then the MX60 reverts back to the

Bulk charge stage, display B-MPPT, and the ChgT counter will start counting up again towards the

MAX Absorb time set point or until the Absorb target is met.

AutoStart (Auto Re-Start) Mode 1—Once every 1.5 hours in Bulk cycle and in Mode 2, once every

1.5 hours in the Bulk, Absorb and Float recharging modes, the MX60 will start over from sleeping

and re-sweep (full sweep) and re-calibrate the current sensor. Mode 0 is disabled completely. It is

recommended that this mode be left to mode 2, Auto Re-Start in all 3 recharging cycles. (See Log2

Bat>Abs When the PV voltage exceeds the battery voltage by 2V and the battery voltage exceeds

the absorb set point, the MX60 has no need to recharge. This can also unintentionally occur if the

user inputs a lower battery voltage than is actually in use (e.g. establishing set points for a 12V

system when a 24V battery bank is used). In this case, the MX60 will always sense a higher (24V)

voltage than a 12V system would require for recharging.

Bat Full There is an external DC source other than solar keeping the battery above the Float set

point. The MX60 is transitioning from Absorb (upper target voltage) to Float (lower target voltage)

or it will not be producing power.

B-MPPT The MX60 is in Maximum Power Point Tracking mode trying to regulate the battery volt-

age towards the Absorb voltage set point. If the MX60 is in the Bulk charge stage, the Charge Timer

(ChgT), will count up to the max Absorb time.

screen)

Page 68 of the Outback Power Systems MX60 user manual — UNDERSTANDING THE VARIOUS OPERATIONAL MODES
Page 68 · click to enlarge
Page 68

Bat Tmp Err The battery temperature sensor is shorted or damaged.

EQ 0:00 This is the time elapsed in hours and minutes since the Equalization voltage was met.

If the EQ voltage set point is not maintained, the controller will revert back to EQ-MPPT – the EQ

timer will pause until the batteries are regulated at the EQ target again. The paused time can be

viewed in the Log2 menu.

EQ DONE Once the set EQ time, (between 1 and 7 hours), has successfully completed, EQ DONE

will be displayed either until a button is pressed, or the next morning’s wakeup. The MX60 will tran-

sition to Float cycle at the end of the EQ cycle.

EQ-MPPT The equalization process has started and the MX60 is trying to regulate towards the

Equalization voltage set point. EQ is not battery temperature compensated. After the EQ voltage

has been reached, EQ 0:00 will be displayed along with the EQ time in hours and minutes. The

AC/DC loads should be turned off and the battery should be charged so the MX60 can reach the

EQ voltage set point. Otherwise, the MX60 may not reach or maintain the EQ cycle.

Float The MX60 is in the Float charge stage and is regulating the battery at the Float voltage set

point. If the system cannot keep up with the Float voltage set point, (e.g. AC and/or DC loads are

on), the MX60 will employ the MPPT function, display F-MPPT, and try its best to regulate the bat-

teries to the Float set point.

F-MPPT The MX60 is in Maximum Power Point Tracking mode trying to regulate the battery volt-

age towards the Float voltage set point. Note: Charge Timer (ChgT) is inactive in the Float state.

GT Mode In a system with an OutBack FX G-series Inverter/Charger, HUB and MATE, the MX60 will

display GT Mode if and only if the inverter is in Sell mode and the MX60 is in Bulk (B-MPPT) or Float

(F-MPPT) cycle. This is also a good indicator for establishing proper Grid tie mode communication

between the FX G-Series Inverter(s) and MX60.

High Voc This indicates the PV array’s open circuit voltage is too high for the controller to safely

operate. This should only occur with systems using 72 VDC nominal PV arrays in very cold tem-

peratures (below 50 F / -150 C). The controller will automatically restart operation once the PV

array’s open circuit voltage falls to a safe level (141 VDC). The amount of time required to reset is

dependent on the module type, ambient temperature, and the amount of sunlight directly on the

PV array. Normally, the controller starts in the morning within a few minutes of the PV array being

in direct sunlight.

Page 69 of the Outback Power Systems MX60 user manual — UNDERSTANDING THE VARIOUS OPERATIONAL MODES
Page 69 · click to enlarge
Page 69

Low Light / Snoozing During the initial sweep (see Wakeup and Sweeping), if it is determined to

be too late (or too early) in the day, the MX60 will display Low Light for a few seconds and then

display Snoozing for 5 minutes (default). This reduces energy usage and unnecessary powering

of the MX60. This message is also displayed in extremely cloudy weather. The Snoozing mode

can be disabled and has two basic modes to choose from: one based on the speed of the PV to

charge the input capacitors and the second looks at the initial wakeup sweep current to see if it

reached the Low cutoff (default) current set point.

MX 2 Hot (Very rare) Either the MX60 is too hot or its internal temperature sensor is shorted. If

this message appears, carefully check if the MX60’s heat sink is extremely hot. The heat generated

by the MX60, and therefore its losses, is proportional to input voltage times output current. Avoid

installing the MX60 in direct sunlight to help control its operating temperature.

New Voc The MX60 is acquiring a new open circuit panel voltage (Voc) periodically in the UPick

MPPT mode or it found a new Voc during an initial sweep.

Re-Cal There are certain abnormal conditions that can confuse the current measuring method

in the MX60. When and if one happens, the MX60 will temporarily stop and re-calibrate. This may

happen because of negative current, i.e., current coming out of the input terminals instead of into

the input terminals, or a tripped PV breaker. A new Voc is also acquired during a Re-Cal.

Sleeping The PV voltage is two volts less than the battery voltage. This may also appear during the

day when the MX60 is transitioning between certain states, or due to other conditions.

Sweeping In Auto-Sweep MPPT mode, the MX60 is either (1) doing an initial sweep of the panel

voltage from Voc towards battery voltage after wakeup, (2) doing a periodic mini-sweep to stay

within its acquired Maximum Power Point voltage, or (3) sweeping to maintain the current limit.

Below 5 amps of battery output current, “Sweeping” briefl y fl ashes on the display as the MX60

operates at the Park Mpp voltage.

SysError (Very rare) System Error indicates an internal non-volatile memory error. The unit will stop

operating when this message is displayed. Call the factory if you see this message.

Unloaded The battery terminals abruptly unload. Unloaded is displayed if the battery breaker trips

while MPPTing or the battery voltage is set too low.

Page 70 of the Outback Power Systems MX60 user manual — UNDERSTANDING THE VARIOUS OPERATIONAL MODES
Page 70 · click to enlarge
Page 70

Wakeup As the PV open circuit voltage (Voc) rises above the battery system voltage by two volts,

the MX60 prepares to deliver power to the batteries. During this period, the MX60 is calculating

the pulse width modulation (PWM) duty cycles, turning on power supply voltages in the proper

sequences, and making internal calibrations. At wakeup, the MX60 closes its relays and then starts

sweeping the input voltage (the “initial” sweep) towards the battery voltage. At dawn and dusk this

may happen many times until there is (or is not) enough power from the PV array to keep going.

Wakeup is also a time when the MX60 acquires a new Voc.

Zzzz... At night (3 hours of Sleeping) the MX60 will display Zzzz... until the next wakeup. At the next

wakeup, (usually the next morning), the daily statistics, (AmpHours, KWh, etc.), will accumulate into

the total statistics and then the displayed daily statistics will clear. A Bulk charge will automatically

initiate at the next Wakeup.

Page 71 of the Outback Power Systems MX60 user manual — J
Page 71 · click to enlarge
Page 71

MATE-DISPLAYED MX60 STATUS MODE Screens

The MX60 STATUS MODE Screens displayed on the optional OutBack MATE include MODE, METER,

and SET (SETPOINT). In STATUS Mode, these MX functions can be viewed by the MATE, but not

changed. Please see the MATE Installation and User Manual for more information.

MAIN

STATUS choose product:

STATUS/MX

12:00:30P

SUM STATUS SETUP ADV

FX MX

MODE METER SETP MAIN

J J

STATUS/MX/MODE---P00 charger modeSilent

STATUS/MX/MODE---P00 aux relay Low Batt mode DOWN UP TOP PORT

STATUS/MX/MODE---P00 aux relay stateON

DOWN STATUS PORT

DOWN UP TOP PORT

J J

STATUS/MX/MODE end of mode menu

STATUS/MX

Press to view

UP TOP STATUS

MODE METER SETP MAIN

the MX METER screens.

J

  • charger mode: displays one of fi ve charging stages (Bulk, Absorption, Float, Silent, or Equalization)
  • aux relay mode: displays one of eight MX60 AUX modes (Manual, Vent Fan, PV Trigger, Float, ER-

ROR ALARM, Diversion, Low Batt(ery) Disconnect, or Remote)

  • aux relay state: indicates if the AUX is ON or OFF

MX MODE Screens

Page 72 of the Outback Power Systems MX60 user manual — UP TOP STATUS
Page 72 · click to enlarge
Page 72

MATE-DISPLAYED MX60 STATUS METER Screens

modeSilent P00 pv 10.0v bat 26.0v in 0a out 0a DOWN STATUS PORT

STATUS/MX/METER--P00 charger 0 w watts DOWN UP TOP PORT

STATUS/MX/METER--P00 charger .0 kwh kwhrs DOWN UP TOP PORT

J J

STATUS/MX/METER--P00 charger +000 adc amps dc DOWN UP TOP PORT

STATUS/MX/METER--P00 battery 26.5 vdc voltage DOWN UP TOP PORT

STATUS/MX/METER--P00 panel 10.2 vdc voltage DOWN UP TOP PORT

J J

STATUS/MX/METER end of meter menu

STATUS/MX

Press to view the

UP TOP STATUS

MODE METER SETP MAIN

J

  • mode/pv/in/bat/out: displays the charger mode, the PV array voltage, the incoming PV amps, the

battery voltage, and the outgoing amps to the battery

  • charger watts: charger output measured in watts
  • charger kwhrs: kilowatt hours produced in the last 60 minutes by the MX60
  • charger amps dc: the amount of amperage the MX60 is sending to the battery
  • battery voltage: current battery voltage
  • panel voltage: current voltage from the PV array

SETPOINT screens · MX METER Screens

Page 73 of the Outback Power Systems MX60 user manual — DOWN STATUS PORT
Page 73 · click to enlarge
Page 73

MATE-DISPLAYED MX60 STATUS SETPT (SETPOINT) Screens

STATUS/MX/SETPT P00 Absorb 28.8 VDC

STATUS/MX/SETPT---P00 Float 27.2 VDC

DOWN STATUS PORT

DOWN UP TOP PORT

J

Press the fi rst two soft keys simultaneously to return

STATUS/MX/METER end of setpoint menu UP TOP STATUS

to the MAIN Menu or press and then

press on the STATUS screen.

  • Absorb: displays the voltage that initiates and maintains the Absorb cycle
  • Float: displays the voltage that begins the Float cycle and is maintained during this cycle

MX SETP(OINT) Screens

Page 74 of the Outback Power Systems MX60 user manual — TROUBLESHOOTING GUIDE
Page 74 · click to enlarge
Page 74

TROUBLESHOOTING GUIDE

Be sure to check out the OutBack customer and user forum at www.outbackpower.com/forum/ for more MX60 information.

MX60 does not boot/power-up (blank LCD)

  • Check the battery connection and polarity.

X Reverse polarity or an improper connection will cause power-up issues.

  • Check the battery breaker.

X Ensure that the battery breaker is sized appropriately.

  • A battery voltage below 10.5 VDC may not power up the MX60 (measure the battery-side of

Four- Position Terminal Block).

  • If the MX60 still does not power up, call the factory for additional support.

MX60 is always SLEEPING

  • If the battery voltage is at or above the ABSORB voltage set point (compensated ABSORB

voltage), the MX60 will not wake up.

  • The PV voltage has to be at least two volts greater than the battery voltage for the initial wakeup.
  • Check the PV array breaker (or fuse).
  • Confi rm the PV array breaker (or fuse) is sized appropriately.
  • Which State (in MISC Menu) is it at? Is it transitioning between 00 and 01? Is it in GT mode and

connected to a MATE?

X GT mode is only applicable with a HUB 4 or HUB 10 installations with a grid-tie compatible

MATE.

  • Does the PV array voltage on the display rise with the PV breaker OFF, but reads 000 with the PV

X If so, the PV array polarity connection on the MX60 maybe reversed or the PV lines could

be shorted.

  • Does the PV voltage still read 000 with the PV breaker off after a minute?

X Call the factory for support.

  • Have you checked the short circuit current of the PV array?

X Use a multi-meter to determine if a short circuit current is detected. The short circuit current

test will not harm the array.

breaker on?

Page 75 of the Outback Power Systems MX60 user manual — TROUBLESHOOTING GUIDE
Page 75 · click to enlarge
Page 75

MX60 not producing expected power

  • Clouds, partial shading, or dirty panels can cause poor performance.

XThe lower current limit set point in the “Charger” menu will yield a loss of power or poor

performance symptoms.

  • Are the batteries charged? Is the MX60 in the Absorbing or Float stage? If either case is true, the

MX60 will produce enough power to regulate the voltage at the ABSORB or FLOAT set point

voltage, therefore, requiring less power in these modes.

  • What is the short circuit current of the PV array? Use a multi-meter to determine if a short circuit

current is as expected. There might be a loose PV array connection.

  • If the PV array voltage close to the battery voltage, the panels could be warm/hot causing the

Maximum Power Point to be at or lower than the battery voltage.

  • If the SWEEP INTERVAL is set to 00 mins, the MX60 will not periodically fi nd the Maximum Power

Point of the array. A sweep interval of seven to ten minutes is suggested

Page 76 of the Outback Power Systems MX60 user manual — TROUBLESHOOTING GUIDE
Page 76 · click to enlarge
Page 76

MX60 is not equalizing

  • Has the EQ cycle been initiated?

X In the EQ Menu, press START to begin process. When the EQ cycle has been initiated,

“EQ-MPPT” will be displayed.

  • The EQ cycle has been initiated, but the battery is not equalizing.

X The EQ cycle will begin when the target EQ set point voltage has been reached. A small ar

ray or cloudy weather will delay the EQ cycle. Accordingly, running too many AC and/or DC loads

will delay the EQ cycle, too.

  • An EQ set point that is too high relative to the battery voltage will delay the EQ cycle.
  • If the PV array voltage is close to the battery voltage, the panels could be warm/hot causing the

Maximum Power Point to be at or lower than the battery voltage which can delay the EQ cycle.

  • A short sweep interval time will cause the MX60 to sweep frequently. A sweep interval of seven

to ten minutes is recommended.

  • When the current limit set point is achieved, the MX60 will continue to sweep to maintain the

targeted current limit.

MX60 Sweeping frequently

Page 77 of the Outback Power Systems MX60 user manual — TROUBLESHOOTING GUIDE
Page 77 · click to enlarge
Page 77

MX60 Battery Temperature Compensated Voltage

  • Only the OutBack RTS (remote temperature sensor) can be used with the MX60.
  • The battery voltage can rise above the ABSORB and FLOAT voltage set points if the battery tem-

perature is < 77° F or fall below the ABSORB and FLOAT voltage if the battery temperature is

> 77° F.

  • Why does the MX60 show “BatTmpErr” on the STATUS screen?

X The RTS is faulty or damaged. Disconnect the RTS from the RTS jack to resume

normal operation.

  • The internal fan will only run when the internal temperature has reached approximately 115° F.

The internal fan will run as needed. In the MISC Menu, the fan will run if and only if the value of

PCB is lower than the value 350. Note that the value 350 represents a temperature count value; it

does not itself equal 350° F.

  • When the MX60 is in “Extended Play” mode, the array is very hot, and the MPP is close to the bat-

tery voltage, beeping can occur. To disable the Extended Play feature, go to the MAIN Menu and

press and hold the #1 soft key until the MX60’s software version appears on the screen. Con-

tinue pressing the #1 soft key and press the #3 soft key at the same time until “X Off ” displays on

the screen. To reactivate Extended Play, repeat these steps and hold the #3 soft key until “X On”

displays. Extended Play is meant to optimize the performance of a hot array, but isn’t critical to

effi cient MX60 operations.

MX60 Internal Fan · MX60 is beeping

Page 78 of the Outback Power Systems MX60 user manual — 12 V 800 W
Page 78 · click to enlarge
Page 78

TYPICAL ARRAY SIZING GUIDE

Below is a list of recommended array sizing for the MX60 for various nominal voltage batteries:

Nominal Battery Voltage Recommended Array Size

(in watts, Standard Test Conditions)

12 V 800 W

24 V 1600 W

36 V 2400 W

48 V 3200 W

60 V 4000 W

The MX60 PV MPPT Charge Controller is capable of an input open circuit voltage (Voc) of up to150

VDC. Cooler climates can cause the Voc to rise above the panel Voc rating. In climates that observe

temperatures less than approximately 5° F, a Voc greater than 125 VDC is not recommended.

When sizing an array, it is recommended that the nominal array voltage be higher than the nomi-

nal battery voltage. Below is a list of recommended nominal array sizing:

Nominal Battery Voltage Nominal Array Voltage (recommended)

12 V 24 V (or higher)*

24 V 36 V (or higher)*

36 V 48 V (or higher)*

48 V 60 V (or higher)*

60 V 60 V (low temp is less than 5° F) or

72v (low temp is greater than 5° F)

* When sizing an array to charge controller with a distance of 70 feet or greater, OutBack

recommends the nominal array voltage be slightly higher than the recommended nominal

array voltage. Example: A 36 VDC nominal array recharging a 12 V nominal battery with an array to

charge controller distance of about 70 feet or greater. Sizing the nominal array voltage higher than

the nominal battery voltage ensures that the Maximum Power Point is always above the battery

voltage. The Maximum Power Point will decrease as the panels warm up, thus lowering the output

of the array. The MX60 Charge Controller will not be able to boost the output if the Maximum

Power Point of the array is at or lower than the battery voltage.

Page 79 of the Outback Power Systems MX60 user manual — 12 V 14.4 14.7
Page 79 · click to enlarge
Page 79

STANDARD vs. AUSTRALIAN DEFAULT SETTINGS

The Australian version MX60 has a few default settings that diff er from the Standard version default

settings. However, there are no diff erences in performance and effi ciency between the two ver-

sions. The Standard and Australian version can be identifi ed as follows:

OutBack 12V Power Systems MX60

OutBack 12V Power Systems MX60-AU

Standard version Australian version

Below are a few default setting diff erences between the Standard and Australian version.

Charger Amps Absorb Float Amps Absorb Float

12 V 60 14.4 V 13.6 V 60 14.4 V 13.8 V

24 V 60 28.8 V 27.2 V 60 8.8 V 27.6 V

36 V 60 43.2 V 40.8 V 60 43.2 V 41.4 V

48 V 60 57.6 V 54.4 V 60 57.6 V 55.2 V

60 V 60 72.0 V 68.0 V 60 72.0 V 69.0 V

Equalize Equalize Volts Equalize Volts

12 V 14.4 14.7

24 V 28.8 29.4

36 V 43.2 44.1

48 V 57.6 58.8

60 V 72.0 73.5

Equalize Time 01 Hours 03 Hours

Settings Standard Australian

Page 80 of the Outback Power Systems MX60 user manual — TYPICAL ARRAY SIZING GUIDE
Page 80 · click to enlarge
Page 80

To meet NEC compliance, the largest PV array that can be connected to the MX60 should have a

rated short-circuit current of 48 amps. The following charts show the maximum distance of various

gauge two-conductor copper wire from the PV array to the MX60 with a 1.5% maximum voltage

drop. Temperature and conduit fi ll corrections may be required. Using a higher voltage PV array

with a low voltage battery system allows you to use a much smaller wire size or go up to 5 times as

far with the same gauge wire.

12 Volt PV Array

#8 #6 #4 #2 #1/0 #2/0 #4/0

8 22 35 57 90 145 180 290

10 18 28 45 72 115 145 230

15 12 19 30 48 76 96 150

1.5% Voltage Drop

20 9 14 22 36 57 72 116

12 Volt Battery System

30 6 9 15 24 38 48 77

40 4 7 11 18 29 36 56

50 3 5 9 4 23 29 46

24 Volt PV Array

#8 #6 #4 #2 #1/0 #2/0 #4/0

8 45 71 114 180 290 360 580

10 36 57 91 145 230 290 460

15 24 38 60 96 153 192 300

1.5% Voltage Drop

20 18 29 45 72 115 145 232

12 or 24 Volt Battery

30 12 19 30 48 77 97 154

40 9 14 23 36 58 72 112

50 7 11 18 29 46 58 86

48 Volt PV Array

#8 #6 #4 #2 #1/0 #2/0 #4/0

8 90 142 228 360 580 720 1160

10 72 114 182 290 460 580 920

15 48 76 120 192 306 384 600

1.5% Voltage Drop

20 36 58 90 144 230 290 464

12, 24 or 48 Volt Battery

30 24 38 60 96 154 194 308

40 18 28 46 72 116 144 224

50 14 22 36 58 92 116 172

Show 18 more labels / short text on this page
Wire Distance Chart · Wire Gauge · Amps · 16V MPP Typical · Distance in Feet · (Two Wires) · Wire Gauge · Amps · 32V MPP Typical · Distance in Feet · (Two Wires) · System · Wire Gauge · Amps · 64V MPP Typical · Distance in Feet · (Two Wires) · System
Page 81 of the Outback Power Systems MX60 user manual — TYPICAL ARRAY SIZING GUIDE
Page 81 · click to enlarge
Page 81

60 Volt PV Array

#8 #6 #4 #2 #1/0 #2/0 #4/0

8 112 177 285 450 725 900 1450

10 90 142 227 362 575 725 1150

1.5% Voltage Drop

15 60 95 150 240 382 480 750

12, 24 or 48 Volt Battery

20 45 72 112 180 287 362 580

30 30 47 75 120 192 230 385

40 22.5 35 57 90 145 180 280

50 17.5 27 45 72 115 145 215

72 Volt PV Array

#8 #6 #4 #2 #1/0 #2/0 #4/0

8 140 221 356 562 906 1125 1812

1.5% Voltage Drop

10 113 178 284 453 719 906 1437

12, 24 or 48 Volt Battery

15 75 119 188 300 478 600 937

20 56 90 140 225 359 452 725

30 37 59 94 150 240 287 481

40 28 44 71 112 181 225 350

Show 12 more labels / short text on this page
Wire Gauge · Amps · 80V MPP Typical · Distance in Feet · (Two Wires) · System · Wire Gauge · 96V MPP Typical · Amps · Distance in Feet · (Two Wires) · System
Page 82 of the Outback Power Systems MX60 user manual — WIRE AND DISCONNECT SIZING
Page 82 · click to enlarge
Page 82

WIRE AND DISCONNECT SIZING

The MX60 has a 60 amp current output limit (default) and is listed to operate continuously at 60

amps depending on the nominal PV array voltage and the nominal battery voltage. There is no

80% de-rating as required by the NEC for fuses, conductors, and most circuit breakers.

The MX60 is a buck type converter and cannot boost the output current when the PV array peak

power point voltage is at or below the battery voltage as may happen on hot days in 24 VDC PV

and a 24 VDC battery system or a 48 VDC PV and a 48 VDC battery system.

To meet minimum NEC requirements (NEC 310.15, 690.8, 9), the output conductor should have

an ampacity of 75 amps after any temperature and conduit fi ll corrections. This would normally

indicate that the output conductors be 4 AWG, but a larger size may be required if there are

temperature and/or conduit fi ll corrections required. With an output conductor rated at 75 amps

(1.25 X the continuous output current), the OutBack OBDC-60 breaker—rated for continuous 100%

duty at 60 amps —can be used to provide the code-required disconnect and output circuit over

current protection.

The PV array output connected to the MX60 input may be as high 60 amps, but at this current

level, there is very little (if any) current boosting or maximum power-point tracking due to the

60-amp output current limit. Additionally, the input current may exceed 60 amps on bright sunny

days and any excess power would be lost. The size and ampacity of the input conductors must be

selected to handle 1.56 times the short-circuit current of the PV array. Any disconnect or circuit

breaker connected to the input conductors must also be rated at 1.56* times the short-circuit

current for the PV array unless the breaker is rated for 100% duty in its enclosure. If that is the case,

the circuit breaker may be rated at 1.25 times the PV array short-circuit current. OutBack OBDC-XX

breakers are 100% duty rated breakers.

In terms of NEC compliance and the MX60’s 60-amp output rating, the largest PV array it can con-

nect to should have a rated short-circuit current of 48 amps. This meets NEC requirements and

allows the MX60 to perform maximum power-point tracking functions. The following charts show

maximum distance in feet of various gauge two-conductor copper wire from the PV array to the

MX60 with a 1.5% maximum voltage drop. Temperature and conduit fi ll corrections may

be required.

*UL requires Isc to be multiplied by 125% for the conductor rating

Page 83 of the Outback Power Systems MX60 user manual — PV ARRAY VOLTAGE
Page 83 · click to enlarge
Page 83

SN O OZE

BULK

SN O OZE

ABSORB

FLOAT

SLEEP ZZZZ SLEEP ZZZZ

PV ARRAY VOLTAGE

XBulk cycle begins XAbsorb charge is reached XAt zero, MX60 goes into FLOAT XTimer starts XTimer begins counting to zero

Figure 7 MX60 MULTI-STAGE BATTERY CHARGING

The MX60 charge controller is a sophisticated, multi-stage battery charger that uses several regula-

tion stages to allow fast recharging of the battery system while ensuring a long battery life. This

process can be used with both sealed and non-sealed batteries. The MX60 has a preset recharg-

ing voltage set points (Absorb & Float) for the selected nominal battery voltage, however, always

follow the battery manufacturer’s recommended charging regulation voltages. The MX60 charging

regulation stages correspond to the chart in Figure 7.

Page 84 of the Outback Power Systems MX60 user manual — TYPICAL ARRAY SIZING GUIDE
Page 84 · click to enlarge
Page 84

BULK cycle provides the maximum power to the battery –the voltage increases

while recharging.

A Bulk cycle is automatically initiated when the battery voltage is below the Absorb and Float*

recharge voltage set points. The Bulk cycle will continue until the Absorb voltage set point is

achieved. “BMPPT” is displayed on the screen.

ABSORBING cycle limits the amount of power going to the battery—the voltage is

held constant.

The Absorb cycle will continue for the duration of the Bulk cycle or until the 2 hour (default) Ab-

sorb time limit is reached. For example, if a Bulk cycle takes 1 hour to reach the Absorb voltage set

point, then the Absorb cycle will continue for 1 hour as well. However, if a Bulk cycle takes 3 hours

to reach the Absorb voltage set point, then the Absorb cycle will continue for 2 hours only. A Bulk

cycle will be re-initiated if the battery voltage is not sustained at the Absorb voltage set point.

“Absorbing” is displayed on the screen at this time.

FLOAT cycle reduces the recharging voltage to prevent overcharging of the batteries.

A Float cycle follows after the Absorb cycle is completed; “Float” is displayed on the screen. The

MX60 will not re-initiate another Bulk cycle if the Float voltage set point is not sustained*. F-MPPT

is displayed. However, it will continue to recharge the battery until the Float voltage set point is

reached.

*Note: A Bulk cycle can be auto-initiated if the battery voltage falls below the Float voltage set

point and the Re-Bulk (ReBV) voltage option is set.

Page 85 of the Outback Power Systems MX60 user manual — EXPECTED TEMPERATURE ADJUST SETPOINT 12V 24V 48V
Page 85 · click to enlarge
Page 85

BATTERY TEMPERATURE COMPENSATED VOLATGE SET POINT

The temperature of a battery has an impact on the recharging process—in higher ambient tem-

peratures, the regulation set points (Absorb & Float) need to be reduced to prevent overcharging

of the batteries. In lower ambient temperature conditions, the voltage regulation set points need

to be increased to ensure complete recharging of the batteries.

The default charger settings of the MX60 are based on typical lead acid battery systems. Always

ensure that the Absorb & Float voltage regulation set points are set to the recommended battery manu-

facturer’s recharging regulation voltages.

Non-Battery Temperature Compensated System

If a battery remote temperature sensor is not available the Absorb and Float voltage regulation set

points can be adjusted for the expected weather conditions. The following table shows the appro-

priate adjustments for both Absorb and Float voltage regulation set points for weather conditions

above or below 77˚ F / 25˚ C

EXPECTED TEMPERATURE ADJUST SETPOINT 12V 24V 48V

Average = 95˚ F / 35˚ C Subtract 0.30 V 0.60 V 1.20 V

Average = 86˚ F / 30˚ C Subtract 0.15 V 0.30 V 0.60 V

Average = 68˚ F / 20˚ C Add 0.15 V 0.30 V 0.60 V

Average = 59˚ F / 15˚ C Add 0.30 V 0.60 V 1.20 V

Battery Temperature Compensated System

A battery remote temperature sensor (RTS) will automatically compensate the Absorb & Float

voltage relative to the Absorb and Float set points in the Charger menu. Please reference page 38

of this manual for adjusting the upper and lower battery compensated limits.

Page 86 of the Outback Power Systems MX60 user manual — STATE OF CHARGE
Page 86 · click to enlarge
Page 86

SUGGESTED BATTERY CHARGER SET POINTS

The battery manufacturer should provide you with specifi c instructions on the following mainte-

nance and voltage set point limits for the specifi c batteries. The following information can be used

when the manufacturer’s information is not available.

SEALED LEAD ACID – AGM / GEL 12 V 24 V 48 V

ABSORB voltage set point 14.4 V 28.8 V 57.6 V

FLOAT voltage set point 13.4 V 26.8 V 53.6 V

NON-SEALED LEAD ACID 12v 24v 48v

ABSORB voltage set point 14.8 V 29.6 V 59.2 V

FLOAT voltage set point 13.8 V 27.6 V 55.2V

greater and excessive temperatures when recharging may occur.

Battery Voltage and State of Charge

A battery’s voltage can be used as a guideline to estimate the amount of power stored in the

battery that is available for use. When referencing the battery voltage on the display, be sure the

battery is not under signifi cant recharging or heavy loads. Otherwise, the DC voltage is not refl ec-

tive of the battery state of cycle. Often the best time to check the battery voltage is in the morning

(pre-charging) or at night (postcharging), with the battery disconnected from charging sources

and loads and a rest for at least three hours.

Operation of a battery below 50% state of cycle will adversely aff ect the long term health of the

battery system and will result in premature failure. Keeping the battery above the 50% level and

recharging it completely once a month will ensure proper operation and good performance.

STATE OF CHARGE

Nominal Battery Charged Good (~75%) Average (~50%) Low (~25%) Discharged

12v over 12.6v 12.3v 12.0v 11.7v under 11.4v

24v over 25.2v 24.6v 24.0v 23.4v under 22.8v

48v over 50.4v 49.2v 48.0v 46.8v under 45.6v

60v over 63.0v 61.5v 60.0v 58.5v under 57.0v

Voltage

Page 87 of the Outback Power Systems MX60 user manual — TWO YEAR LIMITED WARRANTY INFORMATION
Page 87 · click to enlarge
Page 87
Outback Power Systems MX60 — TYPICAL ARRAY SIZING GUIDE diagram (page 87)
Fig. 27

TWO YEAR LIMITED WARRANTY INFORMATION

OutBack Power Systems Inc. warrants that the products it manufacturers will be free from

defects in materials and workmanship for a period of two (2) years subject to the conditions set

forth below.

The limited warranty is extended to the original user and is transferable. The limited warranty

term begins on the date of invoice to the original user of the product. The limited warranty does

not apply to any product or part thereof damaged by a) alteration or disassembly, b) accident or

abuse, c) corrosion, d) lightning, e) reverse polarity, f) repair or service provided by an unauthor-

ized repair facility, g) operation or installation contrary to instructions pertaining to the product.

OutBack Power Systems’ liability for any defective product or any part thereof shall be limited to

the repair or replacement of the product, at OutBack Power Systems’ discretion. OutBack Power

Systems does not warrant or guarantee the workmanship performed by any person or fi rm

installing its products.

THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER

RIGHTS THAT VARY FROM STATE TO STATE (OR JURISDICTION TO JURISDICTION). OUTBACK POWER

SYSTEMS’ RESPONSIBILITY FOR MALFUNCTIONS AND DEFECTS IN HARDWARE IS LIMITED TO

REPAIR AND REPLACEMENT AS SET FORTH IN THIS LIMITED WARRANTY STATEMENT. ALL EXPRESS

AND IMPLIED WARRANTIES FOR THE PRODUCT, INCLUDING BUT NOT LIMITED TO ANY IMPLIED

WARRANTIES OF AND CONDITIONS OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PUR-

POSE, ARE LIMITED IN DURATION TO THE LIMITED WARRANTY PERIOD SET FORTH ABOVE AND NO

WARRANTIES, WHETHER EXPRESS OR IMPLIED, WILL APPLY AFTER SUCH PERIOD. SOME STATES (OR

JURISDICTIONS) DO NOT ALLOW LIMITATIONS ON HOW LONG IMPLIED WARRANTY LASTS, SO THE

ABOVE LIMITATION MAY NOT APPLY TO YOU.

OUTBACK POWER SYSTEMS DOES NOT ACCEPT LIABILITY BEYOND THE REMEDIES SET FORTH IN

THIS LIMITED WARRANTY STATEMENT OR LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAM-

AGES, INCLUDING WITHOUT LIMITATION ANY LIABILITY FOR PRODUCTS NOT BEING AVAILABLE

FOR USE. SOME STATES (OR JURISDICTIONS) DO NOT ALLOW THE EXCLUSION OR LIMITATION OF

INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE EXCLUSION OR LIMITATION MAY NOT

APPLY TO YOU.

Page 88 of the Outback Power Systems MX60 user manual — TYPICAL ARRAY SIZING GUIDE
Page 88 · click to enlarge
Page 88

During the two year period beginning on the invoice date, OutBack Power Systems will repair

or replace products covered under this limited warranty that are returned to OutBack Power

Systems’ facility or to an OutBack Power Systems authorized repair facility, or that are repaired

on site by an OutBack Power Systems authorized repair technician. To request limited warranty

service, you must contact OutBack Power Systems at 360-435-6030 within the limited warranty

period. If limited warranty service is required, OutBack Power Systems will issue a Return Material

Authorization (RMA) Number. Mark the outside of the package with the RMA number and include

a copy of the purchase invoice in the package. You must ship the products back to OutBack Power

Systems in their original or equivalent packaging, prepay shipping cycles, and insure the ship-

ment or accept the risk of loss or damage during shipment. OutBack Power Systems will ship the

repaired or replacement products to you freight prepaid if you use an address in the continental

United States, where applicable. Shipments to other locations will be made freight collect.

Page 89 of the Outback Power Systems MX60 user manual — EU DECLARATION OF CONFORMITY
Page 89 · click to enlarge
Page 89

EU DECLARATION OF CONFORMITY

According to ISO / IEC Guide 22 and EN 45014

Product TypePhotovoltaic Charge Controller
Product Model NumberMX60

This product complies with the following EU directives:

Electromagnetic Compatibility 89/336/EEC, “Council Directive of 3 May 1989

On the approximation of the laws of member States relating to Electromagnetic

Low Voltage Directive 73/23/EEC, “Council Directive of 19 February 1973 on the

harmonization of the laws of Member States relating to electrical equipment for use

within certain voltage limits”

The compliance of the above mentioned product with the directives and the following

essential requirements is hereby confi rmed:

EN 61000-6-3 (2001) EN 61000-6-1 (2001) EN 60335-1 Battery Chargers

All associated technical fi les are located in the Engineering Department at OutBack

Power Systems Inc., Arlington, Washington, USA.

As the manufacturer, we declare under our sole responsibility that the above-mentioned

product complies with the above-named directives.

19009 62nd Ave. NE Arlington, WA. 98223 USA (360) 435-6030

compatibility” · Emissions Immunity Safety · EN 60335-2-29Battery Chargers

Page 90 of the Outback Power Systems MX60 user manual — NOTES: ____________________________________________________________________
Page 90 · click to enlarge
Page 90

OWNER’S SYSTEM INFORMATION

Date of Purchase____________________________________________________________
Vendor____________________________________________________________________
Date of Installation___________________________________________________________
Installer___________________________________________________________________
Installer Contact Information____________________________________________________
MX60 Serial Number_________________________________________________________
Battery Voltage______________________________________________________________
PV Voltage_________________________________________________________________
PV Module Type and Manufacturer______________________________________________
Array Wattage_______________________________________________________________

NOTES:

Page 91 of the Outback Power Systems MX60 user manual — HUB 10 NA $50.00
Page 91 · click to enlarge
Page 91

Product Registration Please take a moment to register and provide us with some important information. Registering your products will help us maintain the standard of excellence you expect from us in terms of performance, quality and reliability. Send check or money order payable to OutBack Power Systems. Include a completed copy of this

application to.: OutBack Power Systems, 19009 62nd Avenue NE, Arlington, WA 98223 USA.

Name________________________________________________________________________
Address______________________________________________________________________
City, State, Zip Code_____________________________________________________________
Country______________________________________________________________________
Telephone Number_____________________________________________________________
E-mail________________________________________________________________________
Sold by_______________________________________________________________________
Installer______________________________________________________________________
Purchase Date_____________________ Model Number: ______________________________
Serial Number_________________________________________________________________

Check all that apply:

X Off -Grid Installation X Grid-Tie Installation XResidential Installation X Commercial Installation

EXTENDED WARRANTYAPPLICATION OutBack Power Systems off ers an optional three year extension to the standard two year limited warranty. Purchase of extended warranty coverage is available on products listed below provided conditions shown are met. Extended warranty coverage must be purchased within 90 days of the original sale of the product covered. WA state residents please add 8.5% sales tax.

PRODUCT REQUIRED SURGE EXTENDED WARRANTY PROTECTION COST All FX Series Inverter/Chargers AC Input; AC Output, DC Input $300.00 MX60 DC Input; DC Output $100.00 MATE NA $50.00 HUB 4 NA $35.00

HUB 10 NA $50.00

Products Covered Serial Number Extended Warranty Cost

Show 4 more labels / short text on this page
_____________________________________________________________________________ · _____________________________________________________________________________ · _____________________________________________________________________________ · Total ____________________
Page 92 of the Outback Power Systems MX60 user manual — 900-0028-01-00 REV B
Page 92 · click to enlarge
Page 92
Outback Power Systems MX60 — TYPICAL ARRAY SIZING GUIDE diagram (page 92)
Fig. 28

19009 62nd Avenue NE Arlington, WA USA (+1) 360-435-6030

European Sales Offi ce

Barcelona, España (+34) 600-843-845

www.outbackpower.com

900-0028-01-00 REV B

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Outback Power Systems MX60

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Outback Power Systems MX60

Be the first to ask — other owners or our team will answer.

Original document

Outback Power Systems MX60 manual PDF

92 pages·901 KB·Battery Charger·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…