GPC Plus Controlle r General Information & Application Guide.
.
Form: ORION-OE331-21-GPCPlusC ontroller-01A.doc Page 1 of 1 Description The OE331-21 General Purpose Con- troller Plus (GPC Plus) is used for con- trolling equipment or processes that cannot be controlled using HVAC con- trollers. The Prism computer front end software is used to interface with the GPC Plus controller functions.
1.)24 V AC Must Be Connected So That All Ground Wires Remain Common. 3.)All Communication Wiring T o Be 18 Ga. Minimum, 2 Conductor T wisted Pair With Shield. Belden #82760 Or Equivalent. 4.)It Is Recommended That All Controllers Address Switches Are Set Before Installation.
1.)24 V AC Must Be Connected So That All Ground Wires Remain Common. 3.)All Communication Wiring T o Be 18 Ga. Minimum, 2 Conductor T wisted Pair With Shield. Belden #82760 Or Equivalent. 4.)It Is Recommended That All Controllers Address Switches Are Set Before Installation.
.
1 General Purpose Controller (GPCPlus ) January 31, 2005 Description The GPCPlus is a controller designed to “fill in the blanks” between standard off the shelf programs and minor non-standard app lications.
2 accesses the configuration for the selected item and a right click accesses the force mode options if any are available. Analog Inputs Relays Analog Outputs.
3 Week Schedules & Holidays.
4 Analog Input Configurations The first five analog inputs and input #7 can be configured in several different ways. Input #6 can be used for Static Pressure and accepts the standard pressure sensor with the phone jack connector, available from WattMaster Controls.
5 8. Read Global Binary Broadcast from another Controller 9. Sensor #6 can be assigned to read Static Pressure Each input is separately configured so combinations of any type of input on the same controller are possible. All readings can be overridden to specific values for test purposes.
6 Any or all readings can also be “broadcast” to other controllers on the communications loop. For example, the Outdoor Air Temperature is broadcast on channel #2 by any unit that happens to have the sensor attached.
7 Each input can also have an appendix selected to display with the reading to make them more user friendly. The possible appendix values are: • (None) No Appendix Required • RH% Relative Humidity.
8 Wall Sensor Slide Offset If you have configured a specific input to be connected to one of WattMasters’ standard OE212 or OE213 Flush Mount Wall Sensors which contain the optional slide offset, be sure to enter a value for “Maximum Slide Offset Effect”.
9 to 72.0°F. If the slide is pushed down, the Hi Limit Setpoint will drop to 70.0°F and the Lo Limit Setpoint to 68.0°F. Push-Button Override If you have configured a specific input to be connected.
10 Analog Input #6 This analog input is reserved for Duct Static Pressure. This value can then be used to monitor the duct static or to actually control the duct static using an analog output and driving either inlet vanes or a VFD controller.
11 Relay Output Configuration Control Methods Each individual output relay can be configured separately for one of the following methods of control listed below.
12 8 = Follow Global Binary Only 9 = Ventilation Control 10 = Lead Relay for Lead/Lag Control 11 = Lag Relay for Lead/Lag Control Control/Reset Sources The Control Source is also selectable. This control source can be an analog value or an on/off contact closure.
13 such as outdoor air temperature. If no reset is required, simply enter the sam e values for the Control Source Hi and Lo Limit Setpoints. No Reset Source is required.
14 Run Time Alarm If the selected relay output is controlling a device that needs periodic maintenance, you can enter a Run Time Alarm Delay period that, once exceeded, generates an alarm condition that will notify the user when it occurs.
15 Ventilation Control You can configure an output to operate in a ventilation control mode. This m eans that the output is active for the Vent Mode ON Time and then cycles off for the Vent Mode OFF Time. If the output is not enabled by a schedule or another relay, it will continue to cycle indefinitely at this On/Off rate.
16 Analog Output Configuration Two Proportional Outputs ( 0 - 10 VDC ) are available to the user. This output operates using standard floating point control or a modified Proportional/Derivative control as configured by the user.
17 7 = Proportional Reset Signal 8 = Economizer Control 9 = Lead/Lag Pump VFD Control Possible Control Sources 0 = Not Configured 1 = Sensor Input #1 2 = Sensor Input #2 3 = Sensor Input #3 4 = Sensor.
18 Economizer Control If you have configured the GPCPlus as a very simple Air Handling Unit, it has the ability to control the outside air dampers in a true first stage economizer cooling m ode. This mode requires a Minimum Ventilation position that it maintains whenever the economizer is not enabled for cooling.
19 Lead/Lag Pump VFD Control If you are using the GPCPlus as a Lead/Lag controller and you need to maintain loop pressure or some other analog signal, configure an output for this method of control.
20 Sample Configurations Sample #1 The user would like to control 4 boilers. Each boiler is controlled from the same W ater Temperature sensor but at a different temperature reading. Once a boiler is activated it must remain on at least 5 m inutes and if a boiler is de-activated it must rem ain off at least 10 minutes.
21 Analog Input #2 Configured as Outdoor Air Thermister Sensor Notice that we set this reading to broadcast on Global Analog Channel #2. That is because the Outside Air is normally read by one controller on a job and the remaining controllers look at Global Analog #2 for this value, including the GPC Plus.
22 Relay Output #1 Programming ( Used for Outdoor Air Enable / Disable ) NOTE: Nothing is physically connected to Relay #1. Its only use is to enable or disable the other relays.
23 Relay Output #2 Programming ( Used for Boiler #1 ) As you can see, the first boiler stage is enabled to operate if the water temperature is below 175°F and will remain on until it rises to 190°F. This first stage can only operate if the outdoor air enabling relay #1 is active.
24 Relay Output #3 Programming ( Used for Boiler #2 ) The second boiler stage is enabled to operate if the water temperature is below 170°F and will remain on until it rises to 180°F. The second stage can only operate if the first boiler stage relay #2 has been active for at least 5 minutes.
25 Relay Output #4 Programming ( Used for Boiler #3 ) The third boiler stage is enabled to operate if the water temperature is below 160°F and will remain on until it rises to 175°F. The third stage can only operate if the second boiler stage relay #3 has been active for at least 5 minutes.
26 Relay Output #5 Programming ( Used for Boiler #4 ) The fourth boiler stage is enabled to operate if the water temperature is below 150°F and will remain on until it rises to 170°F. The fourth stage can only operate if the third boiler stage relay #4 has been active for at least 5 minutes.
27 Operation Relay #1 enables the boilers to operate if the outdoor air temperature is below the low setpoint and the schedule is occupied. Each boiler is enabled to operate if the previous boiler is currently active and has been on for at least 5 minutes.
28 This next sample screen shows that the outdoor air temperature has dropped enough to enable the boilers to operate. The system has been running long enough to satisfy all 4 Boilers 5 Minute Starting delay so they are all active at this point.
29 Sample #2 The user would like to use the GPC Plus as a Lead/Lag Air Handling Unit Controller. The installation is located in a critical area that does not tolerate the space temperature going out of control. The method chosen was to install a backup AHU that would take over in case of failure on the Lead AHU.
30 back alarm condition because the Lead/Lag control should have already generated an alarm if something was wrong and the standby AHU was called into action. Be sure to check the Alarming Enabled box if you want this alarm to be reported back to the PRISM screen or to a Remote Pager.
31 Relay Output #2 Programming ( Used for Lag AHU Enable Signal ) There are no other settings required for the Lag Controller. All control logic from the Lead relay is used in the decision making process.
32 Main Status Screen ( Normal Operations ) As you can see on the Status Screen shown above, the unit is operating normally and the Supply Temperature is at 51.9°F, well within the normal operating range and no alarm s are currently active. There are no schedules active since this unit is required to operate 24 hours a day.
33 Main Status Screen ( Failure Mode ) The Supply Air rose to 61.9°F and the Lag AHU was activated. The alarm screen indicates the Lead AHU failure..
34 Both AHU’s are now off because the Lag AHU failed to lower the Supply Air below 60°F..
35 The alarm screen indicates both outputs failed to control the Supply Temperature. At this point, the service personnel will need to correct the problem and then select the Reset Pump/Fan button to restart the GPC Plus Lead/Lag control sequence.
Form: OR-GPCPlus-APP-01A Printed in the USA March 2005 All rights reserved Copyright 2005 WattMaster Controls Inc. • 8500 NW River Park Drive • Parkville MO • 64152 Phone (816) 505- 1100 www.
An important point after buying a device Orion Car Audio OE331-21 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Orion Car Audio OE331-21 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Orion Car Audio OE331-21 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Orion Car Audio OE331-21 you will learn all the available features of the product, as well as information on its operation. The information that you get Orion Car Audio OE331-21 will certainly help you make a decision on the purchase.
If you already are a holder of Orion Car Audio OE331-21, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Orion Car Audio OE331-21.
However, one of the most important roles played by the user manual is to help in solving problems with Orion Car Audio OE331-21. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Orion Car Audio OE331-21 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center