Cat.No. W371–E1–1
Programmable Controller
OPERATION MANUAL

Operation Manual

OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or dam- age to property.
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for any- thing else.
The following headings appear in the left column of the manual to help you locate different types of information.
of the product.
1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis- sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa- tion contained in this publication.


This manual describes the installation and operation of the CPM2B and includes the sections described below.
The CPM2B is a compact, high-speed board Programmable Controller (PC) designed for control opera- tions. There are two manuals describing the setup and operation of the CPM2B: The CPM2B Operation Manual (this manual) and the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353). (The CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual is referred to as simply the Programming Manual in this manual.)
This manual describes the system configuration and installation of the CPM2B and provides a basic explanation of operating procedures for the Programming Consoles. Read this manual first to acquaint yourself with the CPM2B.
The Programming Manual (W353) provides detailed descriptions of the CPM2B’s programming func- tions. The SYSMAC Support Software Operation Manuals: Basics and C-series PCs (W247 and W248) provide descriptions of SSS operations for the CPM2B and other SYSMAC C-series PCs. The SYSMAC- CPT Support Software Quick Start Guide (W332) and User Manual (W333) provide descriptions of ladder diagram operations in the Windows environment. The WS02-CXPC1-E CX-Programmer User Manual (W361) and the CX-Server User Manual (W362) provide details of operations for the WS02-CXPC1-E CX-Programmer.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the CP2MB.
Section 1 describes the CPM2B’s special features and functions, shows the possible system configura- tions, and outlines the steps required before operation. Read this section first when using the CPM2B for the first time. Refer to the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353) for details on programming.
Section 2 provides the technical specifications of the CPM2B Boards and describes the main compo- nents of the Boards.
Section 3 provides information on installing and wiring a CPM2B PC. Be sure to follow the directions and precautions in this section when installing the CPM2B in a panel or cabinet, wiring the power supply, or wiring I/O.
Section 4 describes the structure of the PC memory areas and explains how to use them.
Section 5 provides a brief summary of the instruction set. Refer to the CPM1/CPM1A/CPM2A/ CPM2C/SRM1(-V2) Programming Manual (W353) for details on specific instructions.
Section 6 provides information on Programming Console operations.
Section 7 describes procedures for trial CPM2B operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during PC operation.
Appendices provides lists of standard models and Board dimensions.
personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.

This section provides general precautions for using the Programmable Controller (PC) and related devices.
The information contained in this section is important for the safe and reliable application of the Programmable Con- troller. You must read this section and understand the information contained before attempting to set up or operate a PC system.
1 Intended Audience xii 2 General Precautions xii 3 Safety Precautions xii 4 Operating Environment Precautions xiii 5 Application Precautions xiii 6 EC Directives xv

1 Intended Audience
The user must operate the product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement ma- chines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative. Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms. This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the above-mentioned applications.
so may result in electric shock.
board or expansion I/O board while the power is being supplied. Doing so may result in electric shock.
short-circuit, heat to a high temperature, or throw into fire. Otherwise the Battery may explode, catch fire, or leak fluid.
may result in malfunction, fire, or electric shock.
Controller), including the following items, in order to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents.

memory, confirm the safety of the destination node before transfer. Not doing so may result in injury.
Caution The operating environment of the PC System can have a large effect on the lon- gevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installa- tion and remains within the specified conditions during the life of the system.
Observe the following precautions when using the PC System.
could lead to serious or possibly fatal injury.


6-1 Applicable Directives
EMC Directives OMRON devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the stan- dards in the system used by the customer, however, must be checked by the customer. EMC-related performance of the OMRON devices that comply with EC Direc- tives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The cus- tomer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
EMS (Electromagnetic Susceptibility): EN61131-2 EMI (Electromagnetic Interference): EN50081-2 (Radiated emission: 10-m regulations) Low Voltage Directive Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to 1,500 VDC meet the required safety standards for the PC (EN61131-2).

6-3 Conformance to EC Directives
The CPM2B PCs comply with EC Directives. To ensure that the machine or de- vice in which the CPM2B PC is used complies with EC directives, the PC must be installed as follows:
1, 2, 3... 1. The CPM2B PC must be installed within a control panel. 2. Reinforced insulation or double insulation must be used for the DC power supplies used for the communications and I/O power supplies. 3. CPM2B PCs complying with EC Directives also conform to the Common Emission Standard (EN50081-2). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other condi- tions. You must therefore confirm that the overall machine or equipment complies with EC Directives.
The CPM2B PCs conform to the Common Emission Standards (EN50081-2) of the EMC Directives. However, the noise generated when the PC is switched ON or OFF using the relay output may not satisfy these standards. In such a case, a noise filter must be connected to the load side or other appropriate countermea- sures must be provided external to the PC. Countermeasures taken to satisfy the standards vary depending on the devices on the load side, wiring, configuration of machines, etc. Following are examples of countermeasures for reducing the generated noise.
(Refer to EN50081-2 for more details.) Countermeasures are not required if the frequency of load switching for the whole system with the PC included is less than 5 times per minute. Countermeasures are required if the frequency of load switching for the whole system with the PC included is 5 times or more per minute.

Countermeasure Examples
When switching an inductive load, connect a surge protector, diodes, etc., in par- allel with the load or contact as shown below.
Circuit Current Characteristic Required element
Yes Yes If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset.
The capacitance of the capacitor must be 1 to 0.5 µF per contact current of 1 A and resistance of the resistor must be 0.5 to 1 Ω per contact voltage of 1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again.
If the supply voltage is 24 to 48 V, insert the surge protector in parallel with the load. If the supply voltage is 100 to 200 V, insert the surge protector between the contacts.
The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity.
No Yes The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load.
The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value. The forward current of the diode must be the same as or larger than the load current.
This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method.
The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the surge protector is applied to electronic circuits with low circuit voltages.
Yes Yes The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset.
If the supply voltage is 24 to 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to 200 V, insert the varistor between the contacts.

This section describes the CPM2B’s special features and functions, shows the possible system configurations, and outlines the steps required before operation. Read this section first when using the CPM2B for the first time.
Refer to the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353) for details on programming.
1-1 CPM2B Features and Functions 2 1-1-1 CPM2B Features 2 1-1-2 Overview of CPM2B Functions 5 1-2 System Configurations 6 1-2-1 CPU Boards 6 1-2-2 Expansion I/O Boards 7 1-2-3 Connecting a Programming Console 8 1-2-4 Support Software 8 1-2-5 One-to-one Computer Connections 9 1-2-6 One-to-N Computer Connections 10 1-2-7 OMRON PT Connections 11 1-2-8 One-to-one PC Link Connections 12 1-3 Structure and Operation 13 1-3-1 CPU Board Structure 13 1-3-2 Operating Modes 14 1-3-3 Operating Mode at Startup 14 1-3-4 PC Operation at Startup 15 1-3-5 Cyclic Operation and Interrupts 16

1-1 CPM2B Features and Functions
1-1-1 CPM2B Features
Peripheral Port Programming Devices are compatible with other models of OMRON PCs. This port can also be used for Host Link or no-protocol communications.
RS-232C Port This port can be used for a Host Link, no-protocol, 1:1 PC Link, or 1:1 NT Link communications.

Relay Output Board Transistor Output Board
The CPU Board has 32 I/O points and Expansion I/O Boards can be added to provide a total I/O ca- pacity of up to 128 I/O points.
The CPM2B CPU Board itself is equipped with 32 I/O points in I/O terminals or I/O connectors. There are 2 types of outputs available (relay outputs and sinking transistor outputs). The power supply is 24 V DC only.
Up to 3 Expansion I/O Boards can be connected to the CPU Board to increase the PC’s I/O capacity to a maximum of 128 I/O points. There are 2 types of 32-point Expansion I/O Boards available: one with relay outputs and the other with sinking transistor outputs.
The same Programming Devices, such as Programming Consoles and Support Software, can be used for the C200H, C200HS, C200HX/HG/HE, CQM1, CPM1, CPM1A, CPM2A, CPM2C, and SRM1 (-V2) PCs, so existing ladder pro- gram resources can be used effectively.
Synchronized pulse control provides an easy way to synchronize the operation of a peripheral piece of equipment with the main equipment. The output pulse frequency can be controlled as some multiple of the input pulse frequency, al-

lowing the speed of a peripheral piece of equipment (such as a supply conveyor) to be synchronized with the speed of the main piece of equipment.

Pulses are output as a fixed multiple of the input frequency.
The CPM2B has a total of five high-speed counter inputs. The one high-speed counter input has a response frequency of 20 kHz/5 kHz and the four interrupt inputs in counter mode have a response frequency of 2 kHz. The high-speed counter can be used in any one of the four input modes: differen- tial phase mode (5 kHz), pulse plus direction input mode (20 kHz), up/down pulse mode (20 kHz), or increment mode (20 kHz). Interrupts can be triggered when the count matches a set value or falls within a specified range. The interrupt inputs in counter mode can be used for incrementing counters or decrementing counters (2 kHz) and trigger an interrupt (executing the interrupt program) when the count matches the target value.
CPM2B PCs with transistor outputs have two outputs that can produce 10 Hz to 10 kHz pulses (single-phase outputs). When used as single-phase pulse outputs, there can be two outputs with a fre- quency range of 10 Hz to 10 kHz with a fixed duty ratio or 0.1 to 999.9 Hz with a variable duty ratio (0 to 100% duty ratio). When used as pulse plus direction or up/down pulse outputs, there can be just one output with a frequency range of 10 Hz to 10 kHz.
There are four inputs used for interrupt inputs (shared with quick-response in- puts and interrupt inputs in counter mode) with a minimum input signal width of 50 µs and response time of 0.3 ms. When an interrupt input goes ON, the main program is stopped and the interrupt program is executed.
There are four inputs used for quick-response inputs (shared with interrupt in- puts and interrupt inputs in counter mode) that can reliably read input signals with a signal width as short as 50 µs.
The input time constant for all inputs can be set to 1 ms, 2 ms, 3 ms, 5 ms, 10 ms, 20 ms, 40 ms, or 80 ms. The effects of chattering and external noise can be reduced by increasing the input time constant.
The interval timer can be set between 0.5 and 319,968 ms and can be set to gen- erate just one interrupt (one-shot mode) or periodic interrupts (scheduled inter- rupt mode).
There are two controls on the CPU Board that can be turned to change the ana- log settings (0 to 200 BCD) in IR 250 and IR 251. These controls can be used to easily change or fine-tune machine settings such as a conveyor belt’s pause time or feed rate.
A DIP switch is provided that controls the status of four input bits.
The built-in clock (accuracy within 1 minute/month) can be read from the pro- gram to show the current year, month, day, day of the week, and time. The clock can be set from a Programming Device (such as a Programming Console) or the time can be adjusted by rounding up or down to the nearest minute.
TIML(––) is a long-term timer that accommodates set values up to 99,990 sec- onds (27 hours, 46 minutes, 30 seconds). When combined with the SECONDS
Encoder · Motor driver Motor

TO HOURS conversion instruction (HMS(––)), the long-term timer provides an easy way to control equipment scheduling.
The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for small- size or micro PCs. Using the CPM1-EMU01-V1, simple on-site transfer of user programs and data memory is possible with PCs.

CPM2C-CN111 (0.1 m) (See note 2.)

CS1W-CN114 (0.05 m)
UPLOAD+DM Button UPLOAD Button
A Host Link connection can be made through the PC’s RS-232C port or Periph- eral port. A personal computer or Programmable Terminal connected in Host Link mode can be used for operations such as reading/writing data in the PC’s I/O memory or reading/changing the PC’s operating mode.
1:N Host Link Communications
1:1 Host Link Communications


CPM2B
(Up to 32 PCs can be connected.)
The TXD(48) and RXD(47) instructions can be used in no-protocol mode to ex- change data with standard serial devices. For example, data can be received

from a bar code reader or transmitted to a serial printer. The serial devices can be connected to the RS-232C port or Peripheral port.
Inputting data from a bar code reader

Outputting data to a serial printer
High-speed 1:1 NT Link Communications
In a 1:1 NT Link, an OMRON Programmable Terminal (PT) can be connected directly to the CPM2B. The PT must be connected to the RS-232C port; it cannot be connected to the Peripheral port.

OMRON PT
One-to-one PC Link
A CPM2B can be linked directly to another CPM2B, CQM1, CPM1, CPM1A, CPM2A, CPM2C, SRM1(-V2), C200HS or C200HX/HG/HE PC. The 1:1 PC Link allows automatic data link connections. The PCs must be connected through the RS-232C ports; they cannot be connected through the Peripheral ports.

Main function Variations/Details Interrupts Interrupt inputs 4 inputs, see note 1.
Bar code reader · Serial printer · One-shot interrupt

Main function Variations/Details High-speed counters High-speed counter No interrupt 1 input, see note 2.
Differential phase mode (5 kHz) Pulse plus direction input mode (20 kHz) Up/down input mode (20 kHz) Increment mode (20 kHz)
(An interrupt can be generated when the count equals the set value or the count lies within a preset range.)
Interrupt inputs in counter mode 4 inputs, see note 1. No interrupt
Incrementing counter (2 kHz) Decrementing counter (2 kHz)
2 outputs: Variable duty ratio pulse output (See note 3.) 0.1 to 999.9 Hz, duty ratio 0 to 100%
1 output: Pulse output with trapezoidal acceleration/deceleration (See note 3.) Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz Synchronized pulse control 1 point, see notes 2 and 3.
Input frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz Output frequency range: 10 Hz to 10 kHz Quick-response input 4 inputs, see note 1.
Analog settings 2 controls (setting ranges: 0 to 200 BCD)
Input time constant Determines the input time constant for all inputs. (Settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)
Calendar/Clock Shows the current year, month, day of the week, day of the month, hour, minute, and second. Error log Records the time of occurrence and error code.
1-2-1 CPU Boards
CPU Board with 32 I/O points (Relay outputs)
CPU Board with 32 I/O points (Transistor outputs)

Count-check interrupt · Count-up interrupt

CPU Board Inputs Outputs Battery Clock RS-232C
32 I/O points 16 inputs, 16 relay outputs --- --- --- CPM2B-32C1DR-D
(16 inputs, 16 outputs) 24 V DC (Terminal-block) Yes Yes Yes CPM2B-32C2DR-D (16 inputs, 16 outputs)
16 inputs, 16 sinking transistor --- --- --- CPM2B-32C1DT-D 24 V DC outputs (Connector) Yes Yes Yes CPM2B-32C2DT-D
Up to 3 Expansion I/O Boards can be connected to the CPU Board.
Expansion I/O Board with 32 I/O points (Relay outputs)
Expansion I/O Board with 32 I/O points (Transistor outputs)

CPU Board Expansion connector
Expansion I/O Board Expansion connector
A PC with 128 I/O points (the maximum) can be assembled by connecting three Expansion I/O Boards. The following configuration provides 64 inputs and 64 sinking transistor outputs:
CPM2B-32C1DT-D (16 inputs, 16 outputs)
CPM2B-32EDT (16 inputs, 16 outputs) × 1 Board + × 3 Boards = 64 inputs, 64 outputs
32 I/O points 16 inputs, 24 V DC 16 relay outputs (Terminal-block)
(16 inputs, 16 outputs) 16 inputs, 24 V DC 16 sinking transistor outputs (Connector)
pansion I/O Board can be connected because of power supply limitations.

1-2-3 Connecting a Programming Console
A Programming Console can be connected to the CPM2B CPU Board’s periph- eral port, as shown below.

CS1W-CN114 Connecting Cable (0.05 m)
SW201 (See note 1.)
Attached cable (2 m) Peripheral port connector
CPM2C-CN111 Connecting Cable (0.1 m) (See note 2.)
C200H-CN222 (2 m) or C200H-CN422 (4 m) Connecting Cable
CS1W-CN224 (2 m) or CS1W-CN624 (4 m) Connecting Cable
A personal computer running the CX-Programmer or SYSMAC-CPT Support Software (in MS Windows) or the SSS (in MS-DOS) can be connected to the CPU Board’s Peripheral port or RS-232C port. Refer to 1-2-5 One-to-one Com- puter Connections for details on the computer connection.
Always turn ON Communications Switch SW201 when using Support Software instead of a Programming Console. The setting on Communications Switch SW202 determines whether the communications settings in the PC Setup or the standard settings will be used, as shown in the following table.
SW202 Communications settings setting Peripheral port RS-232C port ON Standard settings (The standard settings and PC Setup default settings are Host Link communications at 9,600 bps with 1 start bit, 7-bit data, 2 stop bits, and even parity.)
OFF PC Setup settings in DM 6650 and DM 6651
PC Setup settings in DM 6645 and DM 6646
When using the SSS, set the PC Model to “CQM1.” When using the SYSMAC- CPT, set the PC Model to “CQM1” with the “CPU43” CPU version.
Peripheral port · CPM2B CPU Board

1-2-5 One-to-one Computer Connections
Use one of the connecting cables shown in the following diagram to connect a personal computer with Support Software to the CPM2B for a 1:1 Host Link com- munications or no-protocol (serial) communications.
IBM PC/AT or compatible computer
IBM PC/AT or compatible computer
CQM1-CIF02 (3.3 m)
XW2Z-200S-V (2 m) XW2Z-500S-V (5 m)

CS1W-CN114 (0.05 m)
RS-232C port (D-sub 9-pin)
XW2Z-200S-V (2 m) XW2Z-500S-V (5 m)
Note 1. The CQM1-CIF11 Connecting Cable cannot be used. (If one is connected, the CPM2C will not recognize it; the PC will enter RUN mode at startup if Communications Switch SW201 is ON and DM 6600 of the PC Setup is set to its default setting so that the Programming Console’s mode switch con- trols the startup mode.) 2. Refer to Appendix A Standard Models for details on the Support Software that can be used with the CPM2B.

1-2-6 One-to-N Computer Connections
Up to 32 OMRON PCs, including CPM2B PCs, can be connected to a host com- puter.

3G2A9-AL004-E or NT-AL001-E (requires +5 V) (See notes 1 and 2.)
NT-AL001-E (See note 1.)
IBM PC/AT or compatible computer
NT-AL001-E (See note 1.)
NT-AL001-E (See note 1.)
CPM2B CPU Board CPM2B CPU Board CPM2B CPU Board
Up to 32 PCs

3G2A9-AL004-E or NT-AL001-E (requires +5 V) (See notes 1.) Connecting Cable
CPM1-CIF11 (See note 3.)
CPM1-CIF11 (See note 3.)
CPM1-CIF11 (See note 3.)
IBM PC/AT or compatible computer
CPM2B CPU Board CPM2B CPU Board CPM2B CPU Board
Up to 32 PCs
Note 1. The NT-AL001-E must be supplied externally with 5 V DC. When an NT- AL001-E is connected to a CPM2B PC, pin 6 of the CPM2B’s RS-232C port supplies +5 V DC and an external power supply is not necessary. When the NT-AL001-E is connected to a host computer, it is necessary to supply 5 V DC from an external power supply.
If an NT-AL001-E is connected to the CPM2B’s RS-232C port, only one Ex- pansion I/O Board can be connected to the CPU Board because the NT- AL001-E draws its 5-V DC power from the CPU Board.
Use an XW2Z-070T-1 (0.7 m) or XW2Z-200T-1 (2 m) cable to connect the NT-AL001-E to the CPM2B’s RS-232C port.
Connecting Cable

1-2-7 OMRON PT Connections
In a 1:1 NT Link, a CPM2B can be connected directly to a Programmable Termi- nal through the RS-232C port. (The Programmable Terminal cannot be con- nected directly to the peripheral port.) An OMRON PT can also be connected to the CPM2B with a host link connection. Either the RS-232C port or peripheral port can be used for a host link connection.
XW2Z-200T (2 m) XW2Z-500T (5 m)
RS-232C port (D-sub 9-pin)

XW2Z-200T (2 m) XW2Z-500T (5 m)
CS1W-CN114 (0.05 m)
XW2Z-070T-1 (0.7 m) XW2Z-200T-1 (2 m)
for direct access.

1-2-8 One-to-one PC Link Connections
A CPM2B can be linked to another CPM2B, a CQM1, CPM1, CPM1A, CPM2A, CPM2C, SRM1 (-V2) or a C200HS or C200HX/HG/HE PC. The PCs must be connected through the RS-232C ports; they cannot be connected through the Peripheral ports.
1:1 Link Master
1:1 Link Slave
RS-232C port (D-sub 9-pin)
RS-232C port (D-sub 9-pin)

XW2Z-200T (2 m) XW2Z-500T (5 m)
CPM2B CPU Board CPM2B CPU Board
OMRON PC (CQM1, CPM1, CPM1A, CPM2A, CPM2B, CPM2C, SRM1(-V2), C200HS, or C200HX/HG/HE)
OMRON PC (CQM1, CPM1, CPM1A, CPM2A, CPM2B, CPM2C, SRM1(-V2), C200HS, or C200HX/HG/HE)
Connecting Cable

1-3 Structure and Operation
1-3-1 CPU Board Structure
The following diagram shows the internal structure of the CPU Board.

The program reads and writes data in this memory area during execution. Part of the I/O memory contains the bits that reflect the status of the PC’s inputs and outputs. Parts of the I/O memory are cleared when the power is turned ON and other parts are retained.
This is the program written by the user. The CPM2B executes the program cycli- cally. (Refer to 1-3-5 Cyclic Operation and Interrupts for details.)
The program can be divided broadly into two parts: the “main program” that is executed cyclically and the “interrupt programs” that are executed only when the corresponding interrupt is generated.
The PC Setup contains various startup and operating parameters. The PC Set- up parameters can be changed from a Programming Device only; they cannot be changed from the program.
Some parameters are accessed only when PC’s power supply is turned on and others are accessed regularly while the power is on. It will be necessary to turn the power off and then on again to enable a new setting if the parameter is ac- cessed only when the power is turned on.
The Communications Switches determine whether the peripheral port and RS-232C port operate with the standard communications settings or the com- munications settings in the PC Setup. Refer to 2-2 Board Components and their Functions for more details.

1-3-2 Operating Modes
CPM2B CPU Boards have 3 operating modes: PROGRAM, MONITOR, and RUN.
The program is executed at normal speed in RUN mode. Operations such as online editing, force-setting/force-resetting I/O bits, and changing set values/ present values cannot be performed in RUN mode, but the status of I/O bits can be monitored.
The operating mode of the CPM2B when the power is turned ON depends upon the PC Setup settings and the Programming Console’s mode switch setting if a Programming Console is connected.
PC Setup setting Operating mode
DM 6600 08 to 15 00 See note.
01 Startup mode is the same as the operating mode before power was interrupted.
02 Startup mode is determined by bits 00 to 07.
00 to 07 00 PROGRAM mode
and the Programming Device connected to the peripheral port.
None PROGRAM mode RUN mode (see note 2)
PROGRAM mode (see note 1) Other device PROGRAM mode (see note 1) PROGRAM mode
Operating mode set on the Programming Console’s mode switch
Note 1. The CPM2B will not be able to communicate with the Programming Device in these cases. 2. The default setting of bits 08 to 15 of DM 6600 is 00. With this default setting, the PC will automatically enter RUN mode if a Programming Console is not connected and SW201 is ON. Be sure that it is safe for the PC to operate before turning it ON under these conditions.

1-3-4 PC Operation at Startup
The time required for startup initialization depends on several factors, such as the operating conditions (including power supply voltage, system configuration, and ambient temperature) and the program contents.
Minimum Power Supply Voltage The PC will stop and all outputs will be turned OFF if the power supply voltage falls below 85% of the rated value. Momentary Power Interruption A power interruption will not be detected and CPU Board operation will continue if the power interruption lasts less than 2 ms for a DC power supply. A power interruption may or may not be detected for power interruptions some- what longer than 2 ms for a DC power supply. When a power interruption is detected, the CPU Board will stop operating and all outputs will be turned OFF.
Automatic Reset Operation will restart automatically when the power supply voltage is restored to more than 85% of the rated voltage.
Timing Chart of Power OFF Operation The power interruption detection time is the time required for a power interrup- tion to be detected after the power supply voltage drops below 85% of the rated value.
1, 2, 3... 1. Minimum power interruption detection time Power interruptions that are shorter than 2 ms will not be detected. 2. Undetermined additional time Power interruptions only slightly longer than the minimum power interrup- tion time may not be detected.
85% of rated voltage

Detection of power interruption
CPU Board operation will continue if voltage is restored in this region.
CPU Board operation may continue if voltage is restored in this region.
operation may stop and restart repeatedly. When repeated stopping and starting will cause problems with the controlled system, set up a protective circuit such as a circuit that shuts off the power supply to sensitive equipment until the power supply voltage returns to the rated value.
Program execution · Executing Stopped · CPU reset signal

1-3-5 Cyclic Operation and Interrupts
Initialization processing is performed when the power is turned on. If there are no initialization errors, the overseeing processes, program execution, I/O refresh- ing, and communications port servicing are performed repeatedly (cyclically).

Check hardware.
Check memory.
Read data from flash memory (program,
read-only DM data, and PC Setup settings).
Check for battery error.
Preset the watch (maximum) cycle time.
Check program memory.
Refresh bits for expansion functions.
Execute the program.
(Refer to the Programming Manual (W353) for details on cycle time and I/O response times.)
Wait for minimum cycle time if a minimum
cycle time has been set in the PC Setup (DM 6619).
Calculate cycle time.
Read input data from input bits.
Write output data to output bits.
Perform RS-232C port communications
processing. (Can be changed in DM 6616.)
Perform Peripheral port communications
processing. (Can be changed in DM 6617.)
The cycle time can be read from a Programming Device.
AR 14 contains the maximum cycle time and AR 15 contains the present cycle time in 4-digit BCD.

The cycle time will vary slightly depending on the processing being performed in each cycle, so the calculated cycle time will not always match the actual cycle time.
The following diagram shows the cyclic operation of the CPM2B when the pro- gram is being executed normally.
Normally, the results of program execution are transferred to I/O memory just after program execution (during I/O refreshing), but IORF(97) can be used to re- fresh a specified range of I/O words during program execution. The specified range of I/O words will be refreshed when IORF(97) is executed.
The cycle time is the sum of the time required for program execution, I/O refresh- ing, and communications port servicing.
A minimum cycle time (1 to 9,999 ms) can be set in the PC Setup (DM 6619). When a minimum cycle time has been set, CPU operation is paused after pro- gram execution until the minimum cycle time is reached. CPU operation will not be paused if the actual cycle time is longer than the minimum cycle time set in DM 6619.
been set in the PC Setup (DM 6618) and the actual cycle time exceeds that set- ting.
The default settings for RS-232C port servicing and Peripheral port servicing are 5% of the cycle time, but these settings can be changed (between 1% and 99%) in the PC Setup. The RS-232C port’s setting is in DM 6616 and the Peripheral port’s setting is in DM 6617.

If a minimum cycle time has been set in DM 6619, CPU operation is paused until the minimum cycle time is reached.
I/O refreshing RS-232C port servicing
The servicing time can be set in DM 6616. The servicing time can be set in DM 6617.

When an interrupt is generated during execution of the main program, main pro- gram execution is interrupted immediately and the interrupt program is execut- ed. The following diagram shows the cyclic operation of the CPM2B when an interrupt program is executed.
Normally, the results of interrupt program execution are transferred to I/O memory just after program execution (during I/O refreshing), but IORF(97) can be used to refresh a specified range of I/O words during execution of the inter- rupt program. The specified range of I/O words will be refreshed when IORF(97) is executed.
The normal cycle time is extended by the time required for execution of the inter- rupt program.
Refer to Section 7 PC Operations and Processing Time in the CPM1/CPM1A/ CPM2A/CPM2C/SRM1(-V2) Programmable Controllers Programming Manual (W353) for more details and precautions on the cycle time.

Interrupt generated.
I/O refreshing RS-232C port servicing
IORF(97) can be executed in the program to refresh a specified range of I/O words. The specified I/O words will be refreshed when IORF(97) is executed.
IORF(97) can be used to refresh I/O from the main program or the interrupt pro- gram.

When IORF(97) is used, the cycle time is extended by the time required to re- fresh the specified I/O words.

IORF(97) executed.
I/O refreshing RS-232C port servicing

This section provides the technical specifications of the CPM2B Boards and describes the main components of the Boards.
2-1 Specifications 22 2-1-1 General Specifications 22 2-1-2 Characteristics 23 2-1-3 I/O Specifications 25 2-2 Board Components and their Functions 29 2-2-1 CPU Board Components 29 2-2-2 Expansion I/O Boards 32 2-3 I/O Connector and Terminal Pin Allocation 33

2-1 Specifications
2-1-1 General Specifications
Item CPU Boards Expansion I/O Boards
With relay outputs With transistor
With relay outputs With transistor
outputs Supply voltage 24 V DC (Allowable range: 20.4 to 26.4 V DC)
Supplied from CPU Board.
Power consumption 20 W max. ---
Inrush current 20 A max. ---
Insulation resistance 20 MΩ min. (at 500 V DC) between the external DC terminals and non-current carrying metal parts Dielectric strength 1,000 V AC 50/60 Hz for 1 min between the external DC terminals and non-current carrying metal parts Noise immunity Conforms to IEC6100-4-4; 2 kV (power lines)
Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 80 minutes each (8 minutes of vibration × 10 repetitions= total time 80 minutes)
Shock resistance 147 m/s2 three times each in X, Y, and Z directions
Ambient temperature Operating: 0 to 55°C Storage: –25 to 70°C (excluding the battery) Ambient humidity Operating: 10% to 90% (with no condensation)
2 ms min.
Weight 300 g max. 300 g max.
outputs

2-1-2 Characteristics
With relay outputs With transistor outputs
Control method Stored program method
I/O control method Cyclic scan with direct output (Immediate refreshing can be performed with IORF(97).)
Programming language Ladder diagram
Instruction length 1 step per instruction, 1 to 5 words per instruction
Instructions Basic instructions 14 Special instructions
105 instructions, 185 variations
Execution time Basic instructions 0.64 µs (LD instruction) Special instructions
7.8 µs (MOV instruction)
Program capacity 4,096 words
Max. I/O CPU Board only 32 points capacity With Expansion I/O Boards
128 points max.
Input bits IR 00000 to IR 00915 (Words not used for input bits can be used for work bits.)
Output bits IR 01000 to IR 01915 (Words not used for output bits can be used for work bits.)
Special bits (SR area) 448 bits: SR 22800 to SR 25515
Temporary bits (TR area) 8 bits (TR0 to TR7)
Holding bits (HR area) 320 bits: HR 0000 to HR 1915 (Words HR 00 to HR 19)
Auxiliary bits (AR area) 384 bits: AR 0000 to AR 2315 (Words AR 00 to AR 23)
Link bits (LR area) 256 bits: LR 0000 to LR 1515 (Words LR 00 to LR 15)
Timers/Counters 256 timers/counters (TIM/CNT 000 to TIM/CNT 255)
1-ms timers: TMHH(––) 10-ms timers: TIMH(15) 100-ms timers: TIM 1-s/10-s timers: TIML(––) Decrementing counters: CNT Reversible counters: CNTR(12) Data memory Read/Write 2,048 words (DM 0000 to DM 2047) The Error Log is contained in DM 2000 to DM 2021. Read-only 456 words (DM 6144 to DM 6599) PC Setup 56 words (DM 6600 to DM 6655)
External interrupts 4 (Also used for external interrupt inputs in counter mode and quick-response inputs.) Interval timer interrupts
1 (Scheduled Interrupt Mode or Single Interrupt Mode)
High-speed High-speed counter 1 (20 kHz single-phase or 5 kHz two-phase (linear count method)) counter Counter interrupt 1 (set value comparison or set-value range comparison) Interrupt Inputs (Counter mode)
4 inputs (Also used for interrupt inputs and quick-response inputs.)
Counter interrupts 4 (Also used for the external interrupt inputs and quick-response inputs.)
Pulse output 2 points with no acceleration/deceleration, 10 Hz to 10 kHz each, and no direction control. 1 point with trapezoidal acceleration/deceleration, 10 Hz to 10 kHz, and direction control. 2 points with variable duty-ratio outputs.
(Pulse outputs can be used with transistor outputs only, they cannot be used with relay outputs.)
Item CPU Boards · Interrupt processing

Item CPU Boards Item
With transistor outputs With relay outputs
Synchronized pulse control 1 point: A pulse output can be created by combining the high-speed counter with pulse outputs and multiplying the frequency of the input pulses from the high-speed counter by a fixed factor.
(This output is possible with transistor outputs only, it cannot be used with relay outputs.)
Quick-response inputs 4 points (Min. input pulse width: 50 µs max.) (Also used for interrupt inputs and for interrupt inputs in counter mode.) Input time constant (ON response time = OFF response time)
Can be set for all input points. (1 ms, 2 ms, 3 ms, 5 ms, 10 ms, 20 ms, 40 ms, or 80 ms)
Clock function Shows the year, month, day of the week, day, hour, minute, and second. (Backed up by the battery.)
(The clock function is available only in CPU Boards equipped with a clock.) Communications functions Built-in peripheral port: Supports Host Link, peripheral bus, no-protocol, or Programming Console connections.
Built-in RS-232C port: Supports Host Link, no-protocol, 1:1 PC Link (Master/Slave), or 1:1 NT Link connections. (RS-232C communications are available only in CPU Boards equipped with an RS-232C port.) Memory protection (See notes 1 and 2.)
HR area, AR area, program contents, read/write DM area contents, and counter values maintained during power interruptions. Memory backup (See notes 1 and 2.)
Battery or capacitor backup: The read/write DM area, HR area, AR area, and counter values are backed up by a battery. CPU Boards with clock: Backup is approximately 5 years at 25°C. CPU Boards without clock:Backup is approximately 5 days at 25°C. Self-diagnostic functions CPU error (watchdog timer), I/O bus error, battery error, and memory error
Program checks No END instruction, programming errors (checked when operation is started)
Note 1. The DM area, HR area, AR area, and counter values are backed up by the CPU Board’s built-in battery or capacitor. If the battery or capacitor is dis- charged, the contents of these areas will be lost and the data values will re- vert to the defaults. 2. The contents of the program area, read-only DM area (DM 6144 to DM 6599), and PC Setup (DM 6600 to DM 6655) are stored in flash memory. The contents of these areas will be read from flash memory the next time the power is turned ON, even if the backup battery or capacitor is discharged. When data has been changed in any of these areas, write the new values to flash memory by switching the CPM2B to MONITOR or RUN mode, or by turning the power OFF and then ON again.

2-1-3 I/O Specifications
CPU Board Input Specifications

Input voltage All 24 V DC +10%/–15% Input impedance IN00000 to IN00001 2.7 kΩ IN00002 to IN00006 3.9 kΩ IN00007 and up 4.7 kΩ Input current IN00000 to IN00001 8 mA typical IN00002 to IN00006 6 mA typical IN00007 and up 5 mA typical ON voltage/current IN00000 to IN00001 17 V DC min., 5 mA IN00002 and up 14.4 V DC min., 3 mA OFF voltage/current All 5.0 V DC max., 1 mA
ON delay All 1 to 80 ms max. Default: 10 ms (See note.)
OFF delay All 1 to 80 ms max. Default: 10 ms (See note.) Circuit configuration IN00000 to IN00001
Setup. See page 66.
The maximum number of inputs that can be ON simultaneously depends upon the ambient operating temperature and the installation orientation, as shown in the following diagrams.
1, 2, 3... 1. Installation orientation: Vertical with edge down
All inputs can be ON simultaneously with this orientation.


Input voltage 26.4 V DC Input voltage 24 V DC
Max. number of inputs ON
Max. number of inputs ON


at the same time
at the same time
0 10 20 30 40 50 55
(°C) 0 10 20 30 40 50 55
Input voltage 26.4 V DC
Input voltage 24 V DC

Max. number of inputs ON
Max. number of inputs ON

at the same time
at the same time
0 10 20 30 40 50 55
0 10 20 30 40 50 55
High-speed Counter Inputs
Inputs IN00000 through IN00002 can be used as high-speed counter inputs, as shown in the following table. The maximum count frequency is 5 kHz in differen- tial phase mode and 20 kHz in the other modes.
Differential phase mode Pulse plus direction
Up/down input mode Increment mode
IN00000 A-phase pulse input Pulse input Increment pulse input Increment pulse input
IN00001 B-phase pulse input Direction input Decrement pulse input Normal input
IN00002 Z-phase pulse input or hardware reset input (IN00002 can be used as a normal input when it is not used as a high-speed counter input.)
The minimum pulse widths for inputs IN00000 (A-phase input) and IN00001 (B- phase input) are as follows:
Pulse plus direction input mode, Up/down input mode, Increment mode
100 µs min.

50 µs min.
12.5 µs min.
12.5 µs min.
T1 T2 T3 T4 : 12.5 µs min.
The minimum pulse width for input IN00002 (Z-phase input) is as follows:
50 µs min.

500 µs min.

Inputs IN00003 through IN00006 can be used as interrupt inputs (interrupt input mode or counter mode) and quick-response inputs. The minimum pulse width for these inputs is 50 µs.
Input voltage 24 V DC +10%/–15% Input impedance 4.7 kΩ
Input current 5 mA typical
ON voltage 14.4 V DC min.
OFF voltage 5.0 V DC max.
ON delay 1 to 80 ms max. Default: 10 ms (See note.)
OFF delay 1 to 80 ms max. Default: 10 ms (See note.)

4.7 kΩ
COM
Setup. See page 66.
Max. switching capacity 2 A, 250 V AC (cosφ = 1) 2 A, 24 V DC (4 A/common)
Min. switching capacity 10 mA, 5 V DC
Service life of relay (See note.)
Electrical: 150,000 operations (24-V DC resistive load) 100,000 operations (240-V AC inductive load, cosφ = 0.4) Mechanical: 20,000,000 operations
ON delay 15 ms max.
OFF delay 15 ms max.

COM

sumes the worst conditions. The following graph shows the results of OMRON’s service life tests at a switching rate of 1,800 times/hour.

120 V AC, resistive load
24 V DC, τ = 7 ms 120 V AC, cosφ = 0.4 240 V AC, cosφ = 0.4
Life (x 104)
24 V DC/240 V AC, resistive load
Max. switching capacity
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
ON delay OUT01000 and OUT01001: 20 µs max. OUT01002 and up: 0.1 ms max. OFF delay OUT01000 and OUT01001: 40 µs max. for 4.5 to 26.4 V, 10 to 100 mA 0.1 ms max. for 4.5 to 30 V, 10 to 200 mA
OUT01002 and up: 1 ms max. for 4.5 to 30 V, 10 to 300 mA Fuse 1 fuse/output (cannot be replaced by user)

OUT 24 V DC
COM (–)
sistor as required to bring the load current between 0.01 and 0.1 A. If the load current is below 0.01 A, the ON-to-OFF response time will be too long and high- speed pulses will not be output.

2-2 Board Components and their Functions
2-2-1 CPU Board Components



1, 2, 3... 1. Power Supply Terminals
Connect the power supply (24 V DC) to these terminals.
Connects the CPU Board to external input devices.
Connects the CPU Board to external output devices.
These indicators show the operating status of the PC, as shown in the fol- lowing table.
Indicator Status Meaning PWR Lit Power is being supplied to the PC. (green) Not lit Power isn’t being supplied to the PC. RUN Lit The PC is operating in RUN or MONITOR mode. (green) Not lit The PC is in PROGRAM mode or a fatal error has occurred. ERR Lit A fatal error has occurred. (PC operation stops.) (red) Flashing A non-fatal error has occurred. (PC operation continues.) Not lit Indicates normal operation. PERI Flashing Data is being transferred through the peripheral port. (orange) Not lit The peripheral port is not in use. COMM Flashing Data is being transferred through the RS-232C port. (orange) Not lit The RS-232C port is not in use.
The input indicators are lit when the corresponding input terminal is ON. The status of an input indicator will reflect the status of the input even when that input is being used for a high-speed counter.
tor may not light even when the interrupt condition is met if the in- put is not ON long enough. When a high-speed counter is being used, the indicator may not light depending on the speed of the pulses.
b) Input indicators will reflect the status of the corresponding inputs
even when the PC is stopped, but the corresponding input bits will not be refreshed.
The output indicators are lit when the corresponding output terminal is ON. The indicators are lit during I/O refreshing. When an output is being used as a pulse output, the corresponding will remain lit while pulses are being out- put.
Connects the PC to a Programming Device (including Programming Consoles), host computer, or standard external device.
Connects the PC to a Programming Device (excluding Programming Consoles), host computer, Programmable Terminal, or standard external device.

The Communications Switches control the communications settings for the peripheral port and RS-232C port.

OFF OFF
(OFF when shipped.) (OFF when shipped.)
Switch settings Peripheral port RS-232C port
SW202 SW201 communications communications
OFF OFF Programming Console connection The settings in the PC
Setup (DM 6645 to DM 6649) are used.
OFF ON Other Programming Device: The settings in the PC Setup (DM 6650 to DM 6654) are used.
ON OFF Programming Console connection The standard settings
are used.
ON ON Other Programming Device: The standard settings are used.
parity, and 9,600 bps baud rate.
b) Be sure that Communications Switch SW201 is OFF when con-
necting a Programming Console.
The ON/OFF status of IR 00108 through IR 00111 reflects the ON/OFF sta- tus of these DIP switch pins.
Pin Corresponding input bit
2 IR 00109
3 IR 00110
4 IR 00111
This battery backs up memory in CPU Boards equipped with an internal clock. The battery is connected when the Unit is shipped.

2-2-2 Expansion I/O Boards


1, 2, 3... 1. Input Connector Connects the Expansion I/O Board to external input devices. 2. Output Terminals/Connector Connects the Expansion I/O Board to external output devices. 3. Input Indicators The input indicators are lit when the corresponding input terminal is ON. 4. Output Indicators The output indicators are lit when the corresponding output terminal is ON. 5. Expansion I/O Connector Connects the Expansion I/O Board to the CPU Board or the previous Expan- sion Unit or Expansion I/O Unit. Up to 3 Expansion I/O Boards can be con- nected to a CPU Board. An Expansion I/O Cable is included with each Ex- pansion I/O Board.

eration due to static discharge.

03 02 01 00 COM 03 02 01 00 COM
07 06 05 04 NC 07 06 05 04 NC
Inputs (24 V DC)
CPU Board with relay outputs CPU Board with transistor outputs
Sinking transistor outputs Relay outputs
00 01 02 03 COM 04 05 06 07 COM 1 10 00 01 02 03 COM 04 05 06 07 COM 1 10
00 01 02 03 COM 00 01 02 03 COM
04 05 06 07 04 04 06 07


11 10 09 08 COM 03 02 01 00 COM
15 14 13 12 NC 07 06 05 04 NC
Inputs (24 V DC)
Expansion I/O Board with relay outputs
Expansion I/O Board with transistor outputs
00 01 02 03 COM 04 05 06 07 COM 1 10 08 09 10 11 COM 12 13 14 15 COM 1 10
00 01 02 03 COM 08 09 10 11 COM
04 05 06 07 12 13 14 15
Relay outputs · Sinking transistor outputs

This section provides information on installing and wiring a CPM2B PC. Be sure to follow the directions and precautions in this section when installing the CPM2B in a panel or cabinet, wiring the power supply, or wiring I/O.
3-1 Design Precautions 36 3-1-1 Power Supply Wiring 36 3-1-2 Power Supply Voltage 36 3-1-3 Interlock and Limit Circuits 36 3-2 Selecting an Installation Site 36 3-2-1 Installation Site Conditions 37 3-2-2 Panel/Cabinet Installation 37 3-3 Assembling the CPM2B Boards 38 3-4 Installing the CPM2B 39 3-5 Wiring and Connections 40 3-5-1 Power Supply Wiring 41 3-5-2 I/O Wiring Procedures 42 3-5-3 Connecting Input Devices 45 3-5-4 Output Wiring 49

3-1 Design Precautions
Observe the following precautions when designing a system incorporating a CPM2B PC.
Separate the power supply wiring from the power system, control system, CPM2B system, and DC I/O system wiring. Separate the control circuits that supply power to the main Unit from the main circuits using dedicated circuit pro- tectors and fuses.
Caution Use the power supply voltages indicated in Section 2-1 Specification. Failure to adhere to the specifications may result in fire. If the power supply voltage falls below 85% of the rated voltage, the CPM2B will stop and all outputs will be turned OFF. If low voltage affects the equipment, etc., provide a protection circuit which shuts off the output until the supply voltage re- turns to the rated value. In places where power supply conditions are poor, take steps to ensure that power is supplied at the rated voltage. Be sure to adhere to safety precautions, such as providing breakers to prevent short circuits in external wiring. When conducting any of the following operations, turn OFF the power to the PC. Electrocution, product damage and malfunction may result.
measures must be provided in external control circuits (i.e., not in the Programmable Controller) to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not providing proper safety measures may result in serious accidents.
The following diagram shows an example of an interlock circuit.

CPM2B
MC2
MC2
MC1
In the interlock circuit above, MC1 and MC2 can’t be ON at the same time even if CPM2B outputs 01005 and 01006 are both ON (an incorrect PC operation).
The CPM2B is resistant to harsh conditions and highly reliable, but installing the PC in a favorable site will maximize its reliability and operating lifetime.
Interlock Circuit · Motor forward · Motor reverse

Consider PC operation, maintenance, and surrounding conditions when instal- ling the CPM2B in a panel or cabinet.

Electrical Noise

200 mm min.
200 mm min.
Control panel · Fan · Air vent

Ensure that the CPM2B can be accessed for normal operation and mainte- nance. High-voltage equipment, power lines, and moving machinery could be dangerous if they are in the way during routine operations.
Up to 3 Expansion I/O Boards can be connected to a CPM2B CPU Board. The following diagram shows how to assemble the Boards. The screws and stand- offs are included with the CPU Board, Expansion I/O Board, and Mounting Bracket.

CPM2B-ATT01 Mounting Bracket (See note.)
when the system must meet UL/CSA standards.
Board or Bracket Hardware and cables included
Four M3 standoffs (short)
Four M3 standoffs (long)

One CPM2B-CN601 Expansion I/O Cable
touch the components or the surface of the circuit board.

1, 2, 3... 1. Insert the Expansion I/O Cable into the connectors on the CPU Board and Expansion I/O Board.

Expansion I/O Board Expansion I/O Cable (included with the Expansion I/O Board)
The cable from the CPU Board connects to the upper Expansion I/O Connector (the one with the short locks.)
Install the shorter connector of the cable in the lower Board and the longer connector in the up- per Board.

To remove the Expansion I/O Cable, open the connectors lock levers and pull out the cable’s connector.

Install the CPM2B as shown in the following diagram. The CPM2B cannot be installed on DIN Track.



Screw and nut installation
Screw and tapped panel installation
This section provides basic information on power supply wiring and I/O wiring.
Do not run CPM2B I/O lines in the same duct or conduit as power lines.
Hanging Ducts Leave at least 300 mm between the power cables and the I/O or control wiring, as shown in the following diagram.

300 mm min.
Control cables and CPM2B power lines
300 mm min.
Floor Ducts Leave at least 200 mm between the wiring and the top of the duct, as shown in the following diagram.
Control cables and CPM2B power lines Power cables
Metal plate (iron) CPM2B I/O lines

200 mm min.
Mounting Bracket · CPM2B I/O lines · Power cables

Conduits Separate the CPM2B I/O lines, power and control lines, and power cables, as shown in the following diagram.
Control cables and CPM2B power linesPower cables

The power supply terminal specifications are shown below. Supply the power supply terminals with 24 V DC.
24 V DC (Not connected)
Recommended torque 0.5 to 0.6 Nm Recommended screwdriver: OMRON XW4E-00C
Solid wire 0.2 to 2.5 mm2 (AWG 24 to AWG 12) Strip 7 mm (1/4 inch) of insulation. Stranded wire 0.2 to 2.5 mm2 (AWG 24 to AWG 12) Strip 7 mm (1/4 inch) of insulation. Two-condu Solid 2 × (0.2 to 1.0 mm2) (AWG 24 to AWG 20) ctor wires Stranded 2 × (0.2 to 1.5 mm2) (AWG 24 to AWG 16) Stranded with pin terminal
2 × (0.25 to 1.0 mm2) (AWG 24 to AWG 20) without an insulating sleeve
Pin terminals 0.2 to 2.5 mm2 diameter, 7-mm long pin terminal
The following diagram shows how to wire the power supply.

The power supply terminal block is removable.

3-5-2 I/O Wiring Procedures
Removing and Wiring I/O Terminal Blocks
The following tables provide output terminal block specifications.
CPU Boards and Expansion I/O Boards with relay outputs

0.5 to 0.6 Nm Recommended screwdriver: OMRON XW4E-00C
Solid wire 0.2 to 2.5 mm2 (AWG 24 to AWG12) (Strip 7 mm.)
Stranded wire (See notes.) 0.2 to 2.5 mm2 (AWG 24 to AWG12) (Strip 7 mm.) Two-cond Solid 2 × (0.2 to 1.0 mm2) (AWG 24 to AWG 20) uctor Stranded 2 × (0.2 to 1.5 mm2) (AWG 24 to AWG 16) wires Stranded with pin terminal
2 × (0.25 to 1.0 mm2) (AWG 24 to AWG 20) without an insulating sleeve Pin terminals 0.2 to 2.5 mm2 diameter, 7-mm long pin terminal
Bridge (shorts terminals) Terminal pitch 5.08 mm
Note 1. When using stranded wire, be sure to avoid stray wire strands that might short-circuit an adjacent terminal. 2. Do not solder the ends of stranded wires. Solder can break and cause wiring problems. Also, the solder can cause corrosion on the contact surface. 3. Be sure to use the correct pin allocation when assembling and wiring con- nectors or terminal blocks.
Use the following procedure when wiring a terminal block.
1, 2, 3... 1. Use a flatblade screwdriver to loosen the screws at the left and right sides of the terminal block.





The following tables provide specifications of compatible OMRON I/O connec- tors.

current at the common terminal does not exceed 1A.
XG4T-2004 Strain Relief · XG4M-2030 Set · XG4M-2030 Socket

MIL 20P Loose-wire Pressure Connector

Pressing Tool Set (Handy Press) XY2B-2104
Simple Pressing Tool XY2B-7006
A G79-AC (Loose-wire Connecting Cable) can be used to connect to a Relay Terminal. (A pressure connector must be attached on the PC side of the cable.)
A special cable is not provided for connection to the XW2B-20G4 or XW2B-20G5 Terminal Blocks, so one must be made. (The Terminal Block re- quires the kind of MIL 20P connector described above.)
When inserting a cable, first open the lock levers on each side of the connector and then insert the cable’s connector. Press the cable’s connector firmly until both lock levers lock onto the connector.

To remove the cable, open the lock levers to the left and right before removing the cable’s connector.


3-5-3 Connecting Input Devices
Wire inputs to the CPM2B CPU Board and Expansion I/O Boards as shown in the following diagrams.
use a power supply with double insulation or reinforced insulation.

COM
19 17 15 13 11 9 7 5 3 1
20 18 16 14 12 10 8 6 4 2
NC
Expansion I/O Boards (All Models)

COM
19 17 15 13 11 9 7 5 3 1
20 18 16 14 12 10 8 6 4 2
NC

The following table shows how to connect various input devices.

5 mA/6 mA/8 mA CPM2B

Sensor power supply Output
5 mA/6 mA/8 mA CPM2B
Use the same power supply for the input and sensor.

5 mA/6 mA/8 mA

5 mA/6 mA/8 mA CPM2B

IN
CPM2B

Sensor power supply Incorrect Wiring
CPM2B
COM(+)

Using IR 00000 to IR 00002 as High-speed Counter Inputs In these examples, Encoders with an external 24-V DC open-collector output are connected.
Pulse Plus Direction Input Mode


COM
24 V DC
24 V DC


COM
24 V DC
24 V DC
Using IR 00003 to IR 00006 as Interrupt Inputs (Counter Mode) In these examples, an Encoder with an external 24-V DC open-collector output is connected.

Input (00003 to 00006)
24 V DC
PC Setup Settings
The input bits shown in the following tables can operate as normal inputs or they can be assigned special functions in the PC Setup. Special functions for input bits IR 00000 through IR 00002 are set in DM 6642:
Bit PC Setup setting (DM 6642 bits 08 to15) address 00 01 02, 03, or 04 IR 00000 Used as normal Used as high-speed Used as inputs for
inputs. counter inputs. synchronized pulse control.
IR 00002 Used as a normal input.

Special functions for input bits IR 00003 through IR 00006 are set in DM 6628:
Bit Bits in PC Setup setting (in DM 6628) address DM 6628 0 1 2 IR 00003 00 to 03 Used as normal Used as interrupt Used as
IR 00004 04 to 07 inputs. inputs (including quick-response
IR 00005 08 to 11 counter mode). inputs.
IR 00006 12 to 15
Pulse Plus Direction Input mode
E6B2-CWZ6C Encoder (NPN open-col- lector output)


00002 Reset input Sensor or switch
COM
24 V DC
24 V DC
Leakage Current
A leakage current can cause false inputs when using 2-wire sensors (proximity switches or photoelectric switches) or limit switches with LEDs. False inputs won’t occur if the leakage current is less than 1.0 mA (2.5 mA for IN00000 to IN00002). If the leakage current exceeds these values, insert a bleeder resistor in the circuit to reduce the input impedance, as shown in the following diagram.

2-wire sensor, etc.
I: Device’s leakage current (mA) R: Bleeder resistance (kΩ) W: Bleeder resistor’s power rating (W)
LC: CPM2B’s input impedance (kΩ) IC: CPM2B’s input current (mA) EC: CPM2B’s OFF voltage (V) = 5.0 V
LC 5.0 I LC–5.0 k max. W 2.3
R W min.
The equations above were derived from the following equations:
R Input voltage (24)
Input Current (IC)
R Input voltage (24)
Input Current (IC)
W Input voltage (24)
R Input voltage (24) tolerance (4)
Refer to 2-1-3 I/O Specifications for details on the values LC, IC, and EC. The input impedance, input current, and OFF voltage may vary depending on the input being used. (IN00000 through IN00002 have different values.)
When connecting an inductive load to an input, connect a diode in parallel with the load. The diode should satisfy the following requirements:
1, 2, 3... 1. Peak reverse-breakdown voltage must be at least 3 times the load voltage.


COM
3-5-4 Output Wiring
Relay Output Wiring
Wire the outputs to the CPM2B’s CPU Board and Expansion I/O Boards as shown in the following diagrams.
Don’t exceed the output capacity or the maximum common current. Refer to 2-1-3 I/O Specifications for details.
relays or destruction of the output transistors. External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.

Terminal Block #2 (Right side) 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
COM
COM
COM
L
Output capacity Max. common capacity
2 A (250 V AC or 24 V DC) 4 A/common
Terminal Block #2 (Right side)

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
COM
COM
COM
L
Output capacity Max. common capacity
2 A (250 V AC or 24 V DC) 4 A/common


COM
COM
19 17 15 13 11 9 7 5 3 1
18 16 14 12 10 8 6 4 2 20
COM
L L L L L L L L
Output capacity Max. common capacity
1.2 A/common

COM COM
COM COM
19 17 15 13 11 9 7 5 3 1
18 16 14 12 10 8 6 4 2 20
Output capacity Max. common capacity
300 mA (30 V DC) 1.2 A/common

Use the PULS(65), SPED(––), ACC(––), PWM(––), and SYNC(––) instructions to produce pulse outputs (rather than normal outputs) from output bits IR 01000 and IR 01001. Pulse outputs are possible from CPU Boards with transistor out- puts only.
CPM2B


COM
Pulse plus direction output
CPM2B


COM
Observe the following precautions to protect the PC’s internal components.
Output Short Protection The output or internal circuitry might be damaged when the load connected to an output is short-circuited, so it is recommended to install a protective fuse in each output circuit.
Inductive Loads When connecting an inductive load to an input, connect a surge protector or diode in parallel with the load.
The surge protector’s components should have the following ratings:

COM CPM2B Surge protector
Relay Output Transistor Output (Sinking)

COM

The diode should satisfy the following requirements:
Peak reverse-breakdown voltage must be at least 3 times the load voltage. Average rectified current must be 1 A. Inrush Current Considerations When a relay or transistor output is used to switch a load with a high inrush cur- rent such as an incandescent lamp, suppress the inrush current as shown below.


OUT
OUT
R
COM
COM
Providing a dark current of approx. one-third of the rated value through an incandescent lamp
Providing a limiting resistor
Fuse Insertion The CPM2B with transistor output may burn if the load is short-circuited, there- fore, insert a protective fuse in series with the load.
Countermeasure 1 · Countermeasure 2

This section describes the structure of the PC memory areas and explains how to use them.
4-1 Introduction 54 4-1-1 Functions 54 4-2 I/O Allocation 55 4-3 SR Area 58 4-4 AR Area 60 4-5 PC Setup 64 4-5-1 Changing the PC Setup 64 4-5-2 PC Setup Settings 65 4-6 Error Log 69

4-1 Introduction
Most data areas in the CPM2B can be accessed as bits or words. (The TR area can be accessed by bit address only and the DM area can be accessed by word address only.) The following diagram shows the structure of the IR area and the relationship between bit and word addresses.

Bit addresses 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
IR 00011
IR 001
IR 010
IR 011
IR 01107
Data area Size Words Bits Function
Input area 160 bits (10 words)
These bits can be allocated to the external I/O terminals. Output area 160 bits (10 words)
IR 000 to IR 009 IR 00000 to IR 00915 (See note 1.)
IR 010 to IR 019 IR 01000 to IR 01915
Work area 928 bits (58 words)
Work bits can be freely used within the program. SR area 448 bits (28 words)
IR 020 to IR 049 IR 200 to IR 227
IR 02000 to IR 04915 IR 20000 to IR 22715
SR 22800 to SR 25515 These bits serve specific functions such as flags and control bits. TR area 8 bits TR 0 to TR 7 These bits are used to temporarily store ON/OFF status at program branches. HR area 320 bits (20 words)
SR 228 to SR 255
HR 00 to HR 19 HR 0000 to HR 1915 These bits store data and retain their ON/OFF status when power is turned off. AR area 384 bits (24 words)
AR 00 to AR 23 AR 0000 to AR 2315 These bits serve specific functions such as flags and control bits. LR area 256 bits (16 words)
LR 00 to LR 15 LR 0000 to LR 1515 Used for a 1:1 data link with another PC.
256 bits TIM/CNT 000 to TIM/CNT 255 The same numbers are used for both timers and counters. DM area
DM 0000 to DM 1999 DM 2022 to DM 2047
DM area data can be accessed in word units only. Word values are retained when
Error log 22 words DM 2000 to DM 2021 the power is turned off.
Read-only 456 words DM 6144 to DM 6599 The read-only area and PC Setup cannot
be overwritten from program. Change these settings with a Programming Device.
PC Setup 56 words DM 6600 to DM 6655
Note 1. Input bits IR 00108 to IR 00111 reflect the status of the DIP switch on the CPU Board. 2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by the CPU Board’s backup battery or capacitor. If the battery or capacitor discharges completely, memory contents will be re- turned to their default settings. 3. The program and data in DM 6144 to DM 6655 are stored in flash memory.
The functions of the IR area are explained below. IR area bits in the input and output areas are allocated to terminals on the CPU Board and Expansion I/O Boards. They reflect the ON/OFF status of input and output signals. Input bits begin at IR 00000, and output bits begin at IR 01000.

IR words that are not allocated to inputs or outputs can be used as work words.
The work bits can be used freely within the program. They can only be used with- in the program, however, and not for direct external I/O.
These bits mainly serve as flags for CPM2B operation or contain present and set values for various functions. SR 253 to SR 255 are read-only. Refer to 4-3 SR Area for details on the various bit functions.
When a complex ladder diagram cannot be programmed in mnemonic code just as it is, these bits are used to temporarily store ON/OFF execution conditions at program branches. They are used only for mnemonic code. When programming directly with ladder diagrams using the Support Software, TR bits are automati- cally processed for you.
The same TR bits cannot be used more than once within the same instruction block, but can be used again in different instruction blocks. The ON/OFF status of TR bits cannot be monitored from a Programming Device.
These bits retain their ON/OFF status even after the PC power supply has been turned off or when operation begins or stops. They are used in the same way as work bits.
These bits mainly serve as flags related to PC operation. These bits retain their status even after the PC power supply has been turned off or when operation begins or stops. Refer to 4-4 AR Area for details on the various bit functions.
When the CPM2B is linked 1:1 with another CPM2B or a CPM1/CPM1A/ CPM2A/CPM2C/SRM1(-V2), a CQM1, a C200HS or a C200HX/HG/HE PC, these bits are used to share data.
LR words can be used as work words when they are not used for a 1:1 PC Link.
This area is used to manage timers and counters created with TIM, TIMH(15), TMHH(––), TIML(––), CNT, and CNTR(12). The same numbers are used for both timers and counters and each number can be used only once in the user program. Do not use the same TC number twice even for different instructions.
Use TC numbers 000 to 003 for TIMH(15) and TC numbers 004 to 007 for TMHH(––). When these timer numbers are used, timing is performed as an in- terrupt process and the cycle time is not affected.
TC numbers are used to create timers and counters, as well as to access Completion Flags and present values (PVs). If a TC number is designated for word data, it will access the present value (PV); if it is used for bit data, it will ac- cess the Completion Flag for the timer/counter.
DM area data is accessed in word units only. The contents of the DM area are retained even after the PC power supply has been turned off or when operation begins or stops.
DM words DM 0000 to DM 1999 and DM 2022 to DM 2047 can be used freely in the program; other DM words are allocated specific functions.
DM 2000 to DM 2021 contain the error log information. Refer to Section 4-6 Error Log for details on the error log.
DM 6600 to DM 6655 contain the PC Setup. Refer to 4-5 PC Setup for details.
IR bits are allocated to actual input terminals and output terminals on the CPU Board and Expansion I/O Boards. IR words that are not allocated to inputs or outputs can be used as work words.

CPU Board inputs are allocated input bits starting from IR 00000 and CPU Board outputs are allocated output bits starting from IR 01000. Input bits IR 00108 to IR 00111 are allocated to the CPU Board’s DIP switch inputs.
16 inputs IR 00000 to IR 00007 IR 00100 to IR 00107
16 outputs IR 01000 to IR 01007 IR 01100 to IR 01107
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
ÉÉÉÉÉÉÉ
IR 001
ÉÉÉÉÉÉÉ
IR 010
IR 011
Up to 3 Expansion I/O Boards can be connected.
Input bits are allocated to Expansion I/O Boards starting from word (m+1), where “m” is the last input word allocated to the CPU Board or to the previous Expan- sion I/O Board if one is already connected.
Output bits are allocated to Expansion I/O Boards starting from word (n+1), where “n” is the last output word allocated to the CPU Board or to the previous Expansion I/O Board if one is already connected.
16 inputs Bits 00 to 15 in IR (m+1)
16 outputs Bits 00 to 15 in IR (n+1)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Bits
The following example shows the I/O allocation when one Expansion I/O Board is connected to the CPU Board. Expansion I/O Board inputs are allocated IR 00200 through IR 00215 and the outputs are allocated IR 01200 through IR 01215.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Do not use as work bits.
IR 001
IR 002
IR 010
IR 011
IR 012

The following example shows the I/O allocation when three Expansion I/O Boards are connected to the CPU Board.
CPU Board (32 I/O points)
Expansion I/O Board (32 I/O points)
Expansion I/O Board (32 I/O points)
Expansion I/O Board (32 I/O points)
16 inputs IR 00000 to IR 00007 IR 00100 to IR 00107
16 inputs IR 00200 to IR 00215
16 inputs IR 00300 to IR 00315
16 inputs IR 00400 to IR 00415
16 outputs IR 01000 to IR 01007 IR 01100 to IR 01107
16 outputs IR 01200 to IR 01215
16 outputs IR 01300 to IR 01315
16 outputs IR 01400 to IR 01415
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Do not use as work bits.
IR 001
ÉÉÉÉÉÉÉ
IR 002
IR 003
IR 004
IR 010
IR 011
IR 012
IR 013
IR 014
Bits · Inputs · Outputs

4-3 SR Area
These bits mainly serve as flags related to CPM2A/CPM2C operation or contain present and set values for various functions. The functions of the SR area are explained in the following table.
they cannot be written from the ladder program. Bits and words that are “Not used” are also read-only.
Word(s) Bit(s) Function Read/
write SR 228, SR 229
00 to 15 Pulse Output PV 0 Contains the pulse output PV (–16,777,215 to 16,777,215). SR 22915 acts as the sign bit; a negative number is indicated when SR 22915 is ON. (The same PV data can be read immediately with PRV(62).)
Only Pulse Output PV 0 is used for ACC(––).
00 to 15 Pulse Output PV 1 Contains the pulse output PV (–16,777,215 to 16,777,215). SR 23115 acts as the sign bit; a negative number is indicated when SR 23115 is ON. (The same PV data can be read immediately with PRV(62).) SR 232 to SR 235
00 to 15 Macro Function Input Area Contains the input operands for MCRO(99). (Can be used as work bits when MCRO(99) is not used.)
SR 236 to SR 239
00 to 15 Macro Function Output Area Contains the output operands for MCRO(99). (Can be used as work bits when MCRO(99) is not used.)
SR 240 00 to 15 Interrupt Input 00003 Counter Mode SV SV when interrupt input 00003 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00003 is not used in counter mode.)
SR 241 00 to 15 Interrupt Input 00004 Counter Mode SV SV when interrupt input 00004 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00004 is not used in counter mode.)
SR 242 00 to 15 Interrupt Input 00005 Counter Mode SV SV when interrupt input 00005 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00005 is not used in counter mode.)
SR 243 00 to 15 Interrupt Input 00006 Counter Mode SV SV when interrupt input 00006 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00006 is not used in counter mode.)
SR 244 00 to 15 Interrupt Input 00003 Counter Mode PV Counter PV when interrupt input 00003 is used in counter mode (4 digits hexadecimal). SR 245 00 to 15 Interrupt Input 00004 Counter Mode PV Counter PV when interrupt input 00004 is used in counter mode (4 digits hexadecimal). SR 246 00 to 15 Interrupt Input 00005 Counter Mode PV Counter PV when interrupt input 00005 is used in counter mode (4 digits hexadecimal). SR 247 00 to 15 Interrupt Input 00006 Counter Mode PV Counter PV when interrupt input 00006 is used in counter mode (4 digits hexadecimal). SR 248, SR 249
00 to 15 High-speed Counter PV Area
The PVs can have the following values. The leftmost digit of SR 249 acts as the sign indicator; a negative number is indicated when the leftmost digit of SR 249 is F.
Differential phase input mode: –8,388,608 (F838 8608) to 8,388,607 Pulse +direction input mode: –8,388,608 (F838 8608) to 8,388,607 Up/down pulse input mode: –8,388,608 (F838 8608) to 8,388,607 Increment mode: 0 to 16,777,215 Synchronized pulse control: 0 to 20,000 Hz
(Can be used as work bits when the high-speed counter is not used.)
SR 250 00 to 15 Analog Setting 0 Used to store the 4-digit BCD set value (0000 to 0200) from analog control 0. SR 251 00 to 15 Analog Setting 1 Used to store the 4-digit BCD set value (0000 to 0200) from analog control 1.
Read- only · Read/ write · Read- only

SR 252 00 High-speed Counter Reset Bit Read/ write 01 to 03 Not used. 04 Pulse Output 0 PV Reset Bit Turn ON to clear the PV of pulse output 0.
Read/ write 05 Pulse Output 1 PV Reset Bit Turn ON to clear the PV of pulse output 1. 06, 07 Not used. 08 Peripheral Port Reset Bit Turn ON to reset the peripheral port. Automatically turns OFF when reset is complete.
Read/ write 09 RS-232C Port Reset Bit Turn ON to reset the RS-232C port. Automatically turns OFF when reset is complete. 10 PC Setup Reset Bit Turn ON to initialize PC Setup (DM 6600 through DM 6655). Automatically turns OFF again when reset is complete. Only effective if the PC is in PROGRAM mode.
11 Forced Status Hold Bit (See note.) OFF:The forced status of bits that are forced set/reset is cleared when switching be-
tween PROGRAM mode and MONITOR mode. ON: The status of bits that are forced set/reset are maintained when switching between
PROGRAM mode and MONITOR mode. The PC Setup can be set to maintain the status of this bit when the PC is turned off. 12 I/O Hold Bit (See note.) OFF:IR and LR bits are reset when starting or stopping operation. ON: IR and LR bit status is maintained when starting or stopping operation. The PC Setup can be set to maintain the status of this bit when the PC is turned off. 13 Not used. 14 Error Log Reset Bit Turn ON to clear error log. Automatically turns OFF again when operation is complete.
Read/ write 15 Not used. SR 253 00 to 07 FAL Error Code The error code (a 2-digit number) is stored here when an error occurs. The FAL number is stored here when FAL(06) or FALS(07) is executed. This word is reset (to 00) by executing a FAL 00 instruction or by clearing the error from a Programming Device.
08 Battery Error Flag Turns ON when the CPU Board backup battery’s voltage is too low. 09 Cycle Time Overrun Flag Turns ON when a cycle time overrun occurs (i.e., when the cycle time exceeds the maxi- mum cycle time set in the PC Setup).
10,11 Not used. 12 Changing RS-232C Setup Flag Turns ON when the RS-232C port’s settings are being changed.
Read/ write 13 Always ON Flag Read-
14 Always OFF Flag only
15 First Cycle Flag Turns ON for 1 cycle at the start of operation.
Word(s) Read/ · write Function Bit(s) · Read- only

SR 254 00 1-minute clock pulse (30 seconds ON; 30 seconds OFF) Read-
01 0.02-second clock pulse (0.01 second ON; 0.01 second OFF) only
02 Negative (N) Flag Turns ON when the result of a calculation is negative (leftmost bit of binary result ON.) 03 Not used. 04 Overflow (OF) Flag Turns ON when an overflow occurs in a signed binary calculation.
Read- only 05 Underflow (UF) Flag Turns ON when an underflow occurs in a signed binary calculation. 06 Differential Monitor Complete Flag Turns ON when differential monitoring is completed. 07 STEP(08) Execution Flag Turns ON for 1 cycle only at the start of process based on STEP(08). 08 to 15 Not used.
SR 255 00 0.1-second clock pulse (0.05 second ON; 0.05 second OFF) Read-
01 0.2-second clock pulse (0.1 second ON; 0.1 second OFF) only
02 1.0-second clock pulse (0.5 second ON; 0.5 second OFF) 03 Instruction Execution Error (ER) Flag Turns ON when an error occurs during execution of an instruction. 04 Carry (CY) Flag Turns ON when there is a carry in the results of an instruction execution. 05 Greater Than (GR) Flag Turns ON when the result of a comparison operation is “greater.” 06 Equals (EQ) Flag Turns ON when the result of a comparison operation is “equal,” or when the result of an instruction execution is 0.
07 Less Than (LE) Flag Turns ON when the result of a comparison operation is “less.” 08 to 15 Not used.
Forced Status Hold Bit (SR 25211) and the I/O Hold Bit (SR 25212) when power is turned OFF. Refer to 4-5 PC Setup for details.
These bits mainly serve as flags related to CPM2B operation. These bits retain their status even after the CPM2B power supply has been turned off or when operation begins or stops.

AR 02 00 to 07 Not used. 08 to 11 Number of Expansion I/O Boards Connected 12 to 15 Not used.
Word(s) Read/ · write Function Bit(s)

Word(s) Function Bit(s) AR 08 00 to 03 RS-232C Port Error Code (1-digit BCD) 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error
04 RS-232C Communications Error Flag Turns ON when an RS-232C port communications error occurs. 05 RS-232C Transmit Ready Flag Turns ON when the PC is ready to transmit data. (No-protocol and Host Link only) 06 RS-232C Reception Completed Flag Turns ON when the PC has completed reading data. (No-protocol only) 07 RS-232C Reception Overflow Flag Turns ON when an overflow has occurred. (No-protocol only) 08 to 11 Peripheral Port Error Code (1-digit BCD) 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error
12 Peripheral Port Communications Error Flag Turns ON when a peripheral port communications error occurs. 13 Peripheral Port Transmit Ready Flag Turns ON when the PC is ready to transmit data. (No-protocol and Host Link only) 14 Peripheral Port Reception Completed Flag Turns ON when the PC has completed reading data. (No-protocol only) 15 Peripheral Port Reception Overflow Flag Turns ON when an overflow has occurred. (No-protocol only) AR 09 00 to 15 RS-232C Port Reception Counter (4-digit BCD) Valid only when no-protocol communications are used. AR 10 00 to 15 Peripheral Port Reception Counter (4-digit BCD) Valid only when no-protocol communications are used.

Word(s) Function Bit(s) AR 11
00 to 07 High-speed Counter Range Comparison Flags 00 ON: Counter PV is within comparison range 1 01 ON: Counter PV is within comparison range 2 02 ON: Counter PV is within comparison range 3 03 ON: Counter PV is within comparison range 4 04 ON: Counter PV is within comparison range 5 05 ON: Counter PV is within comparison range 6 06 ON: Counter PV is within comparison range 7 07 ON: Counter PV is within comparison range 8 08 High-speed Counter Comparison Operation ON: Operating OFF: Stopped
09 High-speed Counter PV Overflow/Underflow Flag ON: An overflow or underflow occurred. OFF: Normal operation
10 Not used. 11 Pulse Output 0 Output Status ON: Pulse output 0 is accelerating or decelerating. OFF: Pulse output 0 is operating at a constant rate.
12 Pulse Output 0 Overflow/Underflow Flag ON: An overflow or underflow occurred. OFF: Normal operation
13 Pulse Output 0 Pulse Quantity Set Flag ON: Pulse quantity has been set. OFF: Pulse quantity has not been set.
14 Pulse Output 0 Pulse Output Completed Flag ON: Completed OFF: Not completed
15 Pulse Output 0 Output Status ON: Pulses being output. OFF: Stopped. AR 12 00 to 10 Not used.
(Note 1) 11 Pulse Output 1 Output Status ON: Pulse output 1 is accelerating or decelerating. OFF: Pulse output 1 is operating at a constant rate.
12 Pulse Output 1 Overflow/Underflow Flag ON: An overflow or underflow occurred. OFF: Normal operation
13 Pulse Output 1 Pulse Quantity Set Flag ON: Pulse quantity has been set. OFF: Pulse quantity has not been set.
14 Pulse Output 1 Pulse Output Completed Flag ON: Completed OFF: Not completed
15 Pulse Output 1 Output Status ON: Pulses being output. OFF: Stopped.
(Note 1)

Word(s) Function Bit(s) AR 13 00 Power-up PC Setup Error Flag Turns ON when there is an error in DM 6600 to DM 6614 (the part of the PC Setup area that is read at power-up).
01 Start-up PC Setup Error Flag Turns ON when there is an error in DM 6615 to DM 6644 (the part of the PC Setup area that is read at the beginning of operation).
02 RUN PC Setup Error Flag Turns ON when there is an error in DM 6645 to DM 6655 (the part of the PC Setup area that is always read).
03, 04 Not used. 05 Cycle Time Too Long Flag Turns ON if the actual cycle time is longer than the cycle time set in DM 6619. 06, 07 Not used. 08 Memory Area Specification Error Flag Turns ON when a non-existent data area address is specified in the program. 09 Flash Memory Error Flag Turns ON when there is an error in flash memory. 10 Read-only DM Error Flag Turns ON when a checksum error occurs in the read-only DM (DM 6144 to DM 6599). 11 PC Setup Error Flag Turns ON when a checksum error occurs in the PC Setup area. 12 Program Error Flag Turns ON when a checksum error occurs in the program memory (UM) area, or when an im- proper instruction is executed.
13 Expansion Instruction Area Error Flag Turns ON when a checksum error occurs in the expansion instruction assignments area. The expansion instruction assignments will be cleared to their default settings.
14 Data Save Error Flag Turns ON if data could not be retained with the backup battery or capacitor.
The following words are normally backed up: DM read/write words (DM 0000 to DM 1999 and DM 2022 to DM 2047), Error Log (DM 2000 to DM 2021), HR area, counter area, SR 25511, SR 25512 (if DM 6601 is set to hold I/O memory at startup), AR 23, operating mode (if DM 6600 is set to use the previous operating mode).
If the above words cannot be retained, all data will be cleared except that AR 2114 will be turned ON in CPU Boards equipped with a clock. The CPU Board will start in PROGRAM mode if DM 6600 is set to use the previous operating mode. (If DM 6604 is set to generate an error, the PC will start in PROGRAM mode regardless.)
15 Not used.
AR 14 00 to 15 Maximum Cycle Time (4-digit BCD, see note 3) The longest cycle time since the beginning of operation is stored. It is not cleared when opera- tion stops, but it is cleared when operation starts again.
AR 15 00 to 15 Current Cycle Time (4-digit BCD, see note 3) The most recent cycle time during operation is stored. The Current Cycle Time is not cleared when operation stops.
AR 16 00 to 15 Not used.
AR 17 00 to 07 Minute (00 to 59, BCD)
(Note 2) 08 to 15 Hour (00 to 59, BCD)
AR 18 00 to 07 Second (00 to 59, BCD)
(Note 2) 08 to 15 Minute (00 to 59, BCD)
AR 19 00 to 07 Hour (00 to 23, BCD)
(Note 2) 08 to 15 Day of the Month (01 to 31, BCD)
AR 20 00 to 07 Month (01 to 12, BCD)
(Note 2) 08 to 15 Year (00 to 99, BCD)

Word(s) Function Bit(s) AR 21
00 to 07 Day of the Week (00 to 06, BCD) 00: Sunday 01: Monday 02: Tuesday 03: Wednesday 04: Thursday 05: Friday 06: Saturday
08 to 12 Not used. 13 30-second Compensation Bit Turn this bit ON to round off to the nearest minute. When the seconds are 00 to 29, the seconds are cleared to 00 and the rest of the time setting is left unchanged. When the seconds are 30 to 59, the seconds are cleared to 00 and the time is incremented by one minute. 14 Clock Stop Bit Turn this bit ON to stop the clock. The time/date can be overwritten while this bit is ON. 15 Clock Set Bit To change the time/date, turn ON AR 2114, write the new time/date (being sure to leave AR 2114 ON), and then turn this bit ON to enable a new time/date setting. The clock will restart and both AR 2114 and AR 2115 will be turned OFF automatically. AR 22 00 to 15 Not used.
AR 23 00 to 15 Power-off Counter (4-digit BCD) This is the count of the number of times that the power has been turned off. To clear the count, write “0000” from a Programming Device.
Note 1. The same data can be read immediately with PRV(62). 2. The time and date can be set while AR 2114 is ON. The new setting be- comes effective when AR 2115 is turned ON. (AR 2114 and AR 2115 are turned OFF automatically when the new setting goes into effect.) 3. The units for the maximum and current cycle times are determined by the setting in bits 08 to 15 of DM 6618. A setting of 00 specifies 0.1-ms units, 01 specifies 0.1-ms units, 02 specifies 1-ms units, and 03 specifies 10-ms units.
The PC Setup comprises various operating parameters that control PC opera- tion. In order to make the maximum use of PC functionality when using interrupt processing and communications functions, the PC Setup may be customized according to operating conditions. After the PC Setup has been changed, be sure to switch the CPM2B to MON- ITOR or RUN mode or turn the power OFF and then ON again.
The PC Setup settings in DM 6600 to DM 6655 can be changed from a Program- ming Device. The CPM2B must be in PROGRAM mode in order to change the settings in DM 6600 to DM 6644. The settings in DM 6645 to DM 6655 can be changed in MONITOR or PROGRAM mode, but CPM2B’s cycle time will be long if the settings are changed in MONITOR mode. All of the PC Setup settings are set to their defaults when the CPM2B is shipped. The default values for the PC Setup are 0000 for all words (except for the low battery error enable in DM 6655 bits 12 to 15).
PC Setup settings are accessed at various times depending on the setting, as described below.
DM 6600 to DM 6614 Accessed only when PC’s power supply is turned ON.
DM 6615 to DM 6644 Accessed only when program execution begins.
DM 6645 to DM 6655 Accessed regularly when the power is ON.
Since changes in the PC Setup become effective only at the times given above, the PC will have to be restarted to make changes in DM 6600 to DM 6614 effec-
(Note 2) · Words Timing

tive, and program execution will have to be restarted to make changes in DM 6615 to DM 6644 effective.
If an incorrect PC Setup setting is accessed, a non-fatal error (error code 9B) will be generated, the corresponding error flag (AR 1300 to AR 1302) will be turned ON, and the default setting will be used instead of the incorrect setting.
Startup Processing (DM 6600 to DM 6614)
The following settings are effective after transfer to the PC only after the PC is restarted. DM 6600 00 to 07 Startup mode (effective when bits 08 to 15 are set to 02). 00: PROGRAM; 01: MONITOR; 02: RUN 08 to 15 Startup mode designation 00: According to communications switch SW201 and peripheral port connection (See table at the bottom of this page.) 01: Continue operating mode last used before power was turned OFF. 02: Setting in 00 to 07
DM 6601 00 to 07 Not used. 08 to 11 IOM Hold Bit (SR 25212) Status at Startup 0: Reset to 0; 1: Maintain previous status 12 to 15 Forced Status Hold Bit (SR 25211) Status at Startup 0: Reset to 0; 1: Maintain previous status DM 6602 00 to 03 Program memory write-protection 0: Program memory unprotected 1: Program memory write-protected (except DM 6602 itself)
04 to 07 Programming Console display language 0: English; 1: Japanese 08 to 11 Expansion instruction function code assignments 0: Default settings 1: User assignments
12 to 15 Not used. DM 6603 00 to 15 Not used. DM 6604 00 to 07 00: A memory error will not be generated if data could not be retained by the battery.
00 to 15 Not used.
of DM 6600 are set to 00.

Peripheral port Communications switch SW201 connected to OFF ON Nothing PROGRAM RUN
PROGRAM (The CPM2B will not be able to communicate with Programming Console.)
PROGRAM (The CPM2B will not be able to communicate with Programming Device.)
The following settings are effective after transfer to the PC the next time operation is started. DM 6615 00 to 15 Not used.
Word(s) Bit(s) Function

Word(s) Function Bit(s) DM 6616 00 to 07 Servicing time for RS-232C port (Effective when bits 08 to 15 are set to 01.) 00 to 99 (BCD): Percentage of cycle time used to service RS-232C port. 08 to 15 RS-232C port servicing setting enable 00: 5% of the cycle time 01: Use time in bits 00 to 07.
DM 6617 00 to 07 Servicing time for peripheral port (Effective when bits 08 to 15 are set to 01.) 00 to 99 (BCD): Percentage of cycle time used to service peripheral. 08 to 15 Peripheral port servicing setting enable 00: 5% of the cycle time 01: Use time in bits 00 to 07.
DM 6618 00 to 07 Cycle monitor time (Effective when bits 08 to 15 are set to 01, 02, or 03.) 00 to 99 (BCD): Setting (See bits 08 to 15, below.)
A fatal error will be generated and PC operation will stop if the cycle time exceeds the cycle mon- itor time set here. 08 to 15 Cycle monitor enable (Setting in 00 to 07 × units; 99 s max.) 00: 120 ms (setting in bits 00 to 07 disabled) 01: Setting units: 10 ms 02: Setting units: 100 ms 03: Setting units: 1 s
DM 6619 00 to 15 Minimum cycle time 0000: Variable (no minimum) 0001 to 9999 (BCD): Minimum time in ms
Interrupt Processing (DM 6620 to DM 6639)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6620 00 to 03 Input time constant for IR 00000 to IR 00002 0: 10 ms; 1: 1 ms; 2: 2 ms; 3: 3 ms; 4: 5 ms; 5: 10 ms; 6: 20 ms; 7: 40 ms; 8: 80 ms 04 to 07 Input time constant for IR 00003 and IR 00004 (Setting same as bits 00 to 03) 08 to 11 Input time constant for IR 00005 and IR 00006 (Setting same as bits 00 to 03) 12 to 15 Input time constant for IR 00007 to IR 00011 (Setting same as bits 00 to 03) DM 6621 00 to 07 Input time constant for IR 001 00: 10 ms 01: 1 ms 02: 2 ms 03: 3 ms 04: 5 ms 05: 10 ms 06: 20 ms 07: 40 ms 08: 80 ms
08 to 15 Input constant for IR 002 (Setting same as for IR 001.) DM 6622 00 to 07 Input constant for IR 003 (Setting same as for IR 001.) 08 to 15 Input constant for IR 004 (Setting same as for IR 001.) DM 6623 00 to 07 Input constant for IR 005 (Setting same as for IR 001.) 08 to 15 Input constant for IR 006 (Setting same as for IR 001.) DM 6624 00 to 07 Input constant for IR 007 (Setting same as for IR 001.) 08 to 15 Input constant for IR 008 (Setting same as for IR 001.) DM 6625 00 to 07 Input constant for IR 009 (Setting same as for IR 001.) 08 to 15 Not used.
DM 6626 to DM 6627
00 to 15 Not used.
DM6628 00 to 03 Interrupt enable for IR 00003 (0: Normal input; 1: Interrupt input; 2: Quick-response) 04 to 07 Interrupt enable for IR 00004 (0: Normal input; 1: Interrupt input; 2: Quick-response) 08 to 11 Interrupt enable for IR 00005 (0: Normal input; 1: Interrupt input; 2: Quick-response) 12 to 15 Interrupt enable for IR 00006 (0: Normal input; 1: Interrupt input; 2: Quick-response)
DM 6629 00 to 03 PV coordinate system for pulse output 0 0: Relative coordinates; 1: Absolute coordinates 04 to 07 PV coordinate system for pulse output 1 0: Relative coordinates; 1: Absolute coordinates 08 to 15 Not used.
DM 6630 to DM 6641
00 to 15 Not used.

High-speed Counter Settings (DM 6642 to DM 6644)
The following settings are effective after transfer to the PC the next time operation is started. DM 6642 00 to 03 High-speed counter mode (Effective only when bits 08 to 15 are not set to 00.)
04 to 07 High-speed counter reset mode (Effective only when bits 08 to 15 are set to 01.) 0: Z phase and software reset; 1: Software reset only 08 to 15 High-speed counter/Synchronized pulse control for IR 00000 to IR 00002
00 to 15 Not used.
RS-232C Port Communications Settings
The following settings are effective after transfer to the PC.
If CPU Board communications switch SW202 is ON, communications through the RS-232C port are governed by the default settings (all 0) regardless of the settings in DM 6645 through DM 6649. DM 6645 00 to 03 Port settings
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.) 04 to 07 CTS control setting 0: Disable CTS control; 1: Enable CTS control
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
08 to 11 Link words for 1:1 PC Link 0: LR 00 to LR 15 (Any other settings are ineffective.) 12 to 15 Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: NT Link
(Any other setting causes a non-fatal error and turns ON AR 1302.) DM 6646 00 to 07 Baud rate 00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps 08 to 15 Frame format
Start bits Data bits Stop bits Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bits Even 04: 1 bit 7 bits 2 bits Odd 05: 1 bit 7 bits 2 bits None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bits Even 10: 1 bit 8 bits 2 bits Odd 11: 1 bit 8 bits 2 bits None
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits), causes a non-fatal error, and turns ON AR 1302.) DM 6647 00 to 15 Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.)
(Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.)
Word(s) Function Bit(s)

Word(s) Function Bit(s) DM 6648 00 to 07 Node number (Host Link) 00 to 31 (BCD)
(Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR 1302.) 08 to 11 Start code selection for no-protocol communications 0: Disables start code; 1: Enables start code in DM 6649
(Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.)
12 to 15 End code selection for no-protocol communications 0: Disables end code; 1: Enables end code in DM 6649; 2: Sets end code of CR, LF.
(Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.) DM 6649 00 to 07 Start code (00 to FF)
(This setting is valid only when bits 8 to 11 of DM 6648 are set to 1.) 08 to 15 When bits 12 to 15 of DM 6648 set to 0: Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes)
When bits 12 to 15 of DM 6648 set to 1: Sets the end code. (00 to FF) Peripheral Port Communications Settings
The following settings are effective after transfer to the PC.
If CPU Board Communications Switch SW202 is ON, communications through the peripheral port are governed by the default settings (all 0) regardless of the settings in DM 6650 through DM 6654. Communications through the peripheral port are governed by the Programming Console protocol if Communications Switch SW201 is OFF.
DM 6650 00 to 03 Port settings
(Any other setting specifies standard settings, causes a non-fatal error, and turns ON AR 1302.) 04 to 11 Not used. 12 to 15 Communications mode 0: Host Link or peripheral bus; 1: No-protocol
(Any other setting specifies Host Link, causes a non-fatal error, and turns ON AR 1302.) DM 6651 00 to 07 Baud rate 00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps 08 to 15 Frame format
Start bits Data bits Stop bits Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bits Even 04: 1 bit 7 bits 2 bits Odd 05: 1 bit 7 bits 2 bits None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bits Even 10: 1 bit 8 bits 2 bits Odd 11: 1 bit 8 bits 2 bits None
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits), causes a non-fatal error, and turns ON AR 1302.)

DM 6652 00 to 15 Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.)
(Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.) DM 6653 00 to 07 Node number (Host Link) 00 to 31 (BCD)
(Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR 1302.) 08 to 11 Start code selection for no-protocol communications 0: Disables start code; 1: Enables start code in DM 6654
(Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.)
12 to 15 End code selection for no-protocol communications 0: Disables end code; 1: Enables end code in DM 6654; 2: Sets end code of CR, LF.
(Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.) DM 6654 00 to 07 Start code (00 to FF)
(This setting is valid only when bits 8 to 11 of DM 6653 are set to 1.) 08 to 15 When bits 12 to 15 of DM 6653 set to 0: Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes)
When bits 12 to 15 of DM 6653 set to 1: Sets the end code. (00 to FF) Error Log Settings (DM 6655)
The following settings are effective after transfer to the PC. DM 6655 00 to 03 Style 0: Shift after 7 records have been stored 1: Store only first 7 records (no shifting) 2 to F: Do not store records 04 to 07 Not used. 08 to 11 Cycle time monitor enable 0: Generate a non-fatal error for a cycle time that is too long. 1: Do not generate a non-fatal error.
12 to 15 Low battery error enable 0: Generate a non-fatal error for low battery voltage. 1: Do not generate a non-fatal error.
Low battery error detection is disabled (i.e., set to 1) by default in CPU Boards that do not have a clock. If the PC Setup is cleared, the setting will changed to 0 and a low battery error will occur.
The error log function registers the error code of any fatal or non-fatal error that occurs in the PC. The date and time at which the error occurred are registered along with the error code. The error code is also stored in AR 253. The error log is stored in DM 2000 through DM 2021. Up to 7 error records can be stored.
DM 2000 Error log pointer
Indicates the number of records stored in the log (0 to 7). A 0 indi- cates no records.
DM 2021 Error log record 1 (3 words used.) DM 2022 DM 2023
15 8 7 0 Each error log record is configured as follows:
Leading word Leading word + 1 Leading word + 2
Error classification Error code Min Sec Day Hour
Each stored in 2 digits BCD.
DM 2019 Error log record 7 (3 words used.) DM 2020 DM 2021
Word(s) Function Bit(s) · to

1, 2, 3... 1. DM 6655 bits 00 to 03 set to 0: Stores the most recent 7 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record (record 0) is lost whenever a new record is generated.
Error log record 1
Error log record 2
Error log record 6
Error log record 7
2. DM 6655 bits 00 to 03 set to 1: Stores only the first 7 error log records, and ignores any subsequent errors beyond those 7. 3. DM 6655 bits 00 to 03 set to any value other than 0 or 1: Disables the log so that no records are stored. The default setting is the first method. Refer to the preceding page for details on the error log settings in DM 6655. Clearing the Error Log To clear the entire error log, turn ON SR 25214 from a Programming Device. (Af- ter the error log has been cleared, SR 25214 will turn OFF again automatically.)
Lost · All records shifted · New record added

The CPM2B PCs have large a programming instruction set that allows for easy programming of complicated control pro- cesses. This section provides a brief summary of the instruction set.
5-1 CPM2B Function Codes 72 5-2 Alphabetic List by Mnemonic 73 5-3 Expansion Instructions 76

5-1 CPM2B Function Codes
The following table lists the CPM2B instructions that have fixed function codes. Each instruction is listed by mnemonic and by instruction name. Use the num- bers in the leftmost column as the left digit and the number in the column heading as the right digit of the function code.

Left Right digit digit 0 1 2 3 4 5 6 7 8 9

5-2 Alphabetic List by Mnemonic
Dashes (“––”) in the Code column indicate expansion instructions, which do not have fixed function codes. “None” indicates instructions for which function codes are not used.



PWM (@) –– 4 PULSE WITH VARIABLE DUTY RATIO
SCL2 (@) –– 4 SIGNED BINARY TO BCD SCALING
SCL3 (@) –– 4 BCD TO SIGNED BINARY SCALING



5-3 Expansion Instructions
A set of expansion instructions is provided to aid in special programming needs. Function codes can be assigned to up to 18 of the expansion instructions to en- able using them in programs. This allows the user to pick the instructions needed by each program to more effectively use the function codes required to input instructions. The mnemonics of expansion instructions are followed by “(––)” as the function code to indicate that they must be assigned function codes by the user in the instructions table before they can be used in programming (unless they are used under their default settings). Refer to the 6-2-5 Assigning Expansion Instruction Function Codes for a de- scription of the Programming Console operations used to change expansion in- struction allocations. Refer to the SYSMAC Support Software Operation Manuals: C-series PCs (W248), the SYSMAC-CPT Support Software User Manual (W333), or the WS02-CXPC1-E CX-Programmer User Manual (W361) for a description of the corresponding Support Software operations.
The following 18 function codes can be used for expansion instructions: 17, 18, 19, 47, 48, 60, 61, 62, 63, 64, 65, 66, 67, 68, 69, 87, 88, and 89 The 35 expansion instructions that can be used are listed below, along with the default function codes that are assigned when the CPM2B is shipped.



(open) 19 RXD (@) 47 TXD (@) 48 CMPL 60 INI (@) 61
(open) 87 (open) 88 INT (@) 89 ACC (@) --- AVG ---
SCL2 (@) --- SCL3 (@) --- SEC (@) --- SRCH (@) --- STUP (@) ---
PRV (@) 62 CTBL (@) 63 SPED (@) 64 PULS (@) 65 SCL (@) 66
FCS (@) --- HEX (@) --- HMS (@) --- MAX (@) --- MIN (@) ---
SUM (@) --- SYNC (@) --- TIML --- TMHH --- ZCP ---

This section outlines the operations possible with the Programming Consoles.
6-1 Using a Programming Console 78 6-1-1 Compatible Programming Consoles 78 6-1-2 Changing the CPM2B’s Mode with the Mode Switch 80 6-1-3 Connecting the Programming Console 81 6-1-4 Preparation for Operation 82 6-1-5 Entering the Password 83 6-2 Programming Console Operations 84 6-2-1 Overview 84 6-2-2 Clearing Memory 85 6-2-3 Reading/Clearing Error Messages 86 6-2-4 Buzzer Operation 86 6-2-5 Assigning Expansion Instruction Function Codes 87 6-2-6 Setting and Reading a Program Memory Address and Monitoring I/O Bit Status 88 6-2-7 Entering or Editing Programs 88 6-2-8 Instruction Search 91 6-2-9 Bit Operand Search 92 6-2-10 Inserting and Deleting Instructions 93 6-2-11 Checking the Program 94 6-2-12 Bit, Digit, Word Monitor 94 6-2-13 Differentiation Monitor 96 6-2-14 Binary Monitor 97 6-2-15 Three-Word Monitor 98 6-2-16 Signed Decimal Monitor 98 6-2-17 Unsigned Decimal Monitor 99 6-2-18 Three-Word Data Modification 99 6-2-19 Changing Timer, Counter SV 100 6-2-20 Hexadecimal, BCD Data Modification 101 6-2-21 Binary Data Modification 101 6-2-22 Signed Decimal Data Modification 102 6-2-23 Unsigned Decimal Data Modification 103 6-2-24 Force Set, Reset 104 6-2-25 Clear Force Set/Reset 104 6-2-26 Hex-ASCII Display Change 105 6-2-27 Displaying the Cycle Time 105 6-2-28 Reading and Setting the Clock 106 6-3 Programming Example 106 6-3-1 Preparatory Operations 106 6-3-2 Example Program 108 6-3-3 Programming Procedures 109 6-3-4 Checking the Program 111 6-3-5 Test Run in MONITOR Mode 112

6-1 Using a Programming Console
This section provides information on connecting and using a Programming Con- sole.
There are two Programming Consoles that can be used with the CPM2B: The CQM1-PRO01-E and the C200H-PRO27-E. The key functions for these Pro- gramming Consoles are identical. Press and hold the Shift Key to input a letter shown in the upper-left corner of the key or the upper function of a key that has two functions. For example, the CQM1-PRO01-E’s AR/HR Key can specify either the AR or HR Area; press and release the Shift Key and then press the AR/HR Key to specify the AR Area.

Attached Connecting Cable (2 m)

Cassette recorded jack (Cannot be used with the CPM2B).

C200H-CN222 (2 m) C200H-CN422 (4 m)

The following keys are labeled differently on the CQM1-PRO01-E and the C200H-PRO27-E, but the operation of the keys in each pair is identical.
CQM1-PRO01-E Keys C200H-PRO27-E Keys
HR
HR
SET PLAY
SET
RESET REC
RESET
use SHIFT and AR/HR Keys for the CQM1-PRO01-E.
A shift symbol will be displayed in the upper-right corner of the screen when the Shift Key is pressed. The shift input can be cleared by pressing the Shift Key again.
Shift input symbol SHIFT
The mode switch controls the CPM2B’s operating mode. The key can be re- moved when the switch is set to RUN or MONITOR but it cannot be removed when the switch is set to PROGRAM.
The display contrast can be adjusted with the control on the right side of the Pro- gramming Console.

The C200H-PRO27-E’s buzzer volume can be adjusted with the lever on the right side of the Programming Console. The CQM1-PRO01-E’s buzzer volume cannot be adjusted.

Buzzer Operation for details.
Contrast control · Low volume · High volume

6-1-2 Changing the CPM2B’s Mode with the Mode Switch
Once the Programming Console has been connected, its mode switch can be used to change the CPM2B’s operating mode. The mode display (, , or ) will appear on the Programming Console screen.
MONITOR
MONITOR
RUN
PROGRAM RUN
PROGRAM RUN
PROGRAM
CLR SHIFT CLR
Operating Modes
PROGRAM Mode The CPM2B program isn’t executed in PROGRAM mode. Use PROGRAM mode to create and edit the program, clear memory, or check the program for errors, or check output wiring.
MONITOR Mode The CPM2B program is executed in MONITOR mode and I/O is processed just as it is in RUN mode. Use MONITOR mode to test system operations, such as monitoring CPM2B operating status, force-setting and resetting I/O bits, chang- ing the SV/PV of timers and counters, changing word data, and online editing.
RUN Mode This is the CPM2B’s normal operating mode. The CPM2B’s operating status can be monitored from a Programming Device, but bits can’t be force-set/force-reset and the SV/PV of timers and counters can’t be changed.

The operating mode of the CPM2B when the power is turned ON depends upon the PC Setup setting in DM 6600 and the Programming Console’s mode switch setting if the Programming Console is connected.
connected 00xx The startup mode determined by the mode switch setting.
RUN mode if no Programming Device is connected. PROGRAM mode if another Programming Device is connected. 01xx The startup mode is the same as the operating mode before power was interrupted. 0200 PROGRAM mode
enter RUN mode if a Programming Console is not connected and SW201 is ON. Be sure that it is safe for the PC to operate before turning it ON under these conditions.
Connect the Programming Console’s connecting cable to the CPM2B’s periph- eral port, as shown below.
CS1W-CN114 Connecting Cable (0.05 m)
SW201 (See note 1.)
Attached cable (2 m) Peripheral port connector
CPM2C-CN111 Connecting Cable (0.1 m) (See note 2.)
C200H-CN222 (2 m) or C200H-CN422 (4 m) Connecting Cable
CS1W-CN224 (2 m) or CS1W-CN624 (4 m) Connecting Cable

Panel Installation The C200H-PRO27-E Programming Console can be installed in a control panel as shown in the following diagram. (The C200H-ATT01 Mounting Bracket is sold separately.)

Mounting hole dimensions (DIN43700 standards)
186+1.1 –0
92+0.8 –0
Allow at least 80 mm for the cable connector above the Programming Console.

At least 80 mm is required.
Either connector may be used.
About 70 mm is required.
This section describes the procedures required to begin Programming Console operation when using the Programming Console for the first time.
The following sequence of operations must be performed before beginning ini- tial program input.
1, 2, 3... 1. Be sure that the PC is OFF. 2. Connect the Programming Console to the CPU Board’s peripheral port. See 6-1-3 Connecting the Programming Console for details. (The CPU Board’s Communications Switch setting has no effect on commu- nications with the Programming Console.) 3. Set the mode switch to PROGRAM mode. 4. Turn ON the PC. 5. Enter the password. See 6-1-5 Entering the Password for details. 6. Clear (All Clear) the PC’s memory. See 6-2-2 Clearing Memory for details. 7. Read and clear all errors and messages. See 6-2-3 Reading/Clearing Error Messages for details.
Mounting Bracket · Two screws

To gain access to the PC’s programming functions, you must first enter the pass- word. The password prevents unauthorized access to the program. The PC prompts you for a password when PC power is turned on or, if PC power is already on, after the Programming Console has been connected to the PC. To gain access to the system when the “Password!” message appears, press CLR and then MONTR. Then press CLR to clear the display. If the Programming Console is connected to the PC when PC power is already on, the first display below will indicate the mode the PC was in before the Pro- gramming Console was connected. Ensure that the PC is in PROGRAM mode before you enter the password. When the password is entered, the PC will shift to the mode set on the mode switch, causing PC operation to begin if the mode is set to RUN or MONITOR. The mode can be changed to RUN or MON- ITOR with the mode switch after entering the password.
Indicates the mode set by the mode selector switch.
·

6-2 Programming Console Operations
6-2-1 Overview
The following table lists the programming and monitoring operations that can be performed from a Programming Console. Refer to the rest of this section for details on operational procedures.
Clearing memory Clears all or part of the Program Memory and any data areas that are not read-only, as well as the contents of the Programming Console’s memory.
Displays and clears error messages and displays MESSAGE instruction messages.
Buzzer operation Turns on and off the buzzer that sounds when Programming Console keys are pressed.
Assigning expansion instruction function codes
Reads or changes the function codes assigned to expansion instructions 87
Setting a program memory address
Sets the specified program memory address when reading, writing, inserting and deleting programs.
Reading a program memory address
Reads the contents of the Program Memory. Displays the status of the currently displayed bit in PROGRAM and MONITOR modes.
Instruction search Finds occurrences of the specified instruction in the program. 91
Bit operand search Finds occurrences of the specified operand bit in the program. 92
Inserting and deleting instructions
Inserts or deletes instructions from the program. 93
Entering or editing programs Overwrites the contents of the current Program Memory to either input a program for the first time or to change a program that already exists.
Checking the program Checks for programming errors and displays the program address and error when errors are found.
Bit, digit, word monitor Monitors the status of up to 16 bits and words, although only 3 can be shown on the display at one time.
Multiple address monitor Monitors the status of up to 6 bits and words simultaneously. 96
Differentiation monitor Monitors the up or down differentiation status of a particular bit. 96
Binary monitor Monitors the ON/OFF status of any word’s 16 bits. 97
Three-word monitor Monitors the status of three consecutive words. 98
Signed decimal monitor Converts the contents of the specified word from signed hexadecimal (two’s complement format) to signed decimal for display.
Unsigned decimal monitor Converts hexadecimal data in a word to unsigned decimal for display. 99
3-word data modification Changes the contents of one or more of the 3 consecutive words displayed in the 3-Word Monitor operation.
Changing timer, counter SV 1 Changes the SV of a timer or counter. 100
Changing timer, counter SV 2 Makes fine adjustment changes to the SV of the timer or counter. 100
Hexadecimal, BCD data modification
Changes the BCD or hexadecimal value of a word being monitored. 101
Binary data modification Changes the status of a word’s bits when the word is being monitored. 101
Signed decimal data modification
Changes the decimal value of a word being monitored as signed decimal data, within a range of –32,768 to 32,767. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format.)
Unsigned decimal data modification
Changes the decimal value of a word being monitored as unsigned decimal data, within a range of 0 to 65,535. A change into hexadecimal data is made automatically.
Force set/reset Forces bits ON (force set) or OFF (force reset.) 104
Clear force set/reset Restores the status of all bits which have been force set of reset. 104
Hex-ASCII display change Converts word data displays back and forth between 4-digit hexadecimal data and ASCII.
Name Function Page · Reading/clearing error messages

Displaying the cycle time Displays the current average cycle time (scan time.) 105
Reading and setting the clock Reads or sets the internal clock. 106
This operation is used to clear all or part of the Program Memory and data areas, as well as the contents of the Programming Console’s memory. This operation is possible in PROGRAM mode only.
Before beginning to program for the first time or when installing a new program, clear all areas.
All Clear The following procedure is used to clear memory completely, including the pro- gram, all data areas, counter PVs, Data Memory, and the PC Setup (DM 6600 to DM 6655).
1, 2, 3... 1. Bring up the initial display by pressing the CLR Key repeatedly. 2. Press the SET, NOT, and then the RESET Key to begin the operation.
Partial Clear It is possible to retain the data in specified areas or part of the Program Memory. To retain the data in the HR, TC, or DM Areas, press the appropriate key after pressing SET, NOT, and RESET. Any data area that still appears on the display will be cleared when the MONTR Key is pressed. The HR Key is used to specify both the AR and HR Areas, the CNT Key is used to specify the entire timer/counter area, and the DM Key is used to specify the DM Area.
It is also possible to retain a portion of the Program Memory from the first memory address to a specified address. After designating the data areas to be retained, specify the first Program Memory address to be cleared. For example, input 030 to leave addresses 000 to 029 untouched, but to clear addresses from 030 to the end of Program Memory.
As an example, follow the procedure below to retain the timer/counter area and Program Memory addresses 000 through 122:
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Press the SET, NOT, and then the RESET Key to begin the operation. 3. Press the CNT Key to remove the timer/counter area from the data areas shown on the display. (Counter PVs will not be cleared.)
B 1
Name Page Function · No No OK ·

6-2-3 Reading/Clearing Error Messages
This operation is used to display and clear error messages. It is possible to dis- play and clear non-fatal errors and MESSAGE instruction messages in any mode, but fatal errors can be cleared in PROGRAM mode only.
OK OK OK
Before inputting a new program, any error messages recorded in memory should be cleared. It is assumed here that the causes of any of the errors for which error messages appear have already been taken care of. If the buzzer sounds when an attempt is made to clear an error message, eliminate the cause of the error, and then clear the error message. (Refer to Section 7 Test Runs and Error Processing for troubleshooting information.)
Key Sequence Follow the procedure below to display and clear messages.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Press the FUN and then the MONTR Key to begin the operation. If there are no messages, the following display will appear:
If there are messages, the most serious message will be displayed when the MONTR Key is pressed. Pressing MONTR again will clear the present mes- sage and display the next most serious error message. Continue pressing MONTR until all messages have been cleared. These are some examples of error messages: A memory error:
A system error:
A message (displayed with MSG(46)):
All messages cleared:
6-2-4 Buzzer Operation
This operation is used to turn on and off the buzzer that sounds when Program- ming Console keys are pressed. This buzzer will also sound whenever an error occurs during PC operation. Buzzer operation for errors is not affected by this setting. This operation is possible in any mode.
OK OK OK

Key Sequence Follow the procedure below to turn the key-input buzzer on and off.
1, 2, 3... 1. Press the CLR, SHIFT, and then the CLR Key to bring up the mode display. In this case the PC is in PROGRAM mode and the buzzer is ON.
The buzzer will not sound when “BZ” is not displayed. 3. Press the SHIFT and then the 1 Key again to turn the buzzer back ON.
6-2-5 Assigning Expansion Instruction Function Codes
This operation is used to display or change the expansion instructions assigned to expansion instruction function codes. The assignments can be displayed in any mode, but can be changed in PROGRAM mode only.
Operation RUN MONITOR PROGRAM
Read assignment OK OK OK
Change assignment No No OK
Assign expansion instruction function codes before inputting the program. The CPM2B will not operate properly if expansion instructions aren’t as- signed correctly. An expansion instruction can be assigned to one function code only.
The PC Setup must be set for user-defined expansion instruction assign- ments. Set bits 8 to 11 of DM 6602 to 1 and turn the PC’s power off and then on again to enable the new setting.
There are tables in Section 5 Instruction Set showing the default function code assignments in the CPM2B.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
↓ ! $#!
↓ ! $#! %&

6-2-6 Setting and Reading a Program Memory Address and Monitoring I/O Bit Status
This operation is used to display the specified program memory address and is possible in any mode. In the RUN or MONITOR mode, the I/O bit status of bits in the program will be displayed.
OK OK OK
When inputting a program for the first time, it is generally written to Program Memory starting from address 000. Because this address appears when the display is cleared, it is not necessary to specify it.
When inputting a program starting from other than 000 or to read or modify a program that already exists in memory, the desired address must be desig- nated.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
A 0
In the RUN or MONITOR mode, ON/OFF status of the bit will be displayed. Pressing the MONTR Key will change to the I/O monitor display. Bits can be force-set or force-reset from the I/O monitor display. Press the CLR Key to return to I/O bit status monitoring of the initial address.
RUN or MONITOR mode.
↓
↑ !!
This operation is used enter or edit programs. It is possible in PROGRAM mode only.
The same procedure is used to either input a program for the first time or to change a program that already exists. In either case, the current contents of Program Memory is overwritten.
!! · ↓ · No No OK

The program shown in the following diagram will be entered to demonstrate this operation.
00200 LD IR 00002 00201 TIM 000 #0123 00202 MOV(021)
#0123 12.3 s
#0100 LR 10 00203 ADB(050)
LR 10
ADB(050)
#0100 #FFF6 DM 0000
#FFF6
DM 0000
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Specify the address where the program will begin. 3. Input the address where the program will begin and press the Down Arrow Key. It is not necessary to input leading zeroes.
A 0
If a mistake was made inputting the instruction, press the Up Arrow Key to return to the previous program address and input the instruction again. The mistaken instruction will be overwritten To specify the Completion Flag for a timer or counter, press the LD, AND, OR, or NOT Key followed by the TIM or CNT Key, and then input the timer/ counter number last. 6. Input the second instruction and operand. (In this case it isn’t necessary to enter the timer number, because it’s 000.) Press the WRITE Key to write the instruction to Program Memory.
TIM Timer number WRITE )
D 3 WRITE ' (
If a mistake was made inputting the operand, press the Up Arrow Key to return to display the mistaken operand and input the operand again.
CNT Key is pressed instead of the TIM Key. b) Timer and counter SVs are input in BCD, so it isn’t necessary to
press the CONT/# Key.
Address Instruction Operands · #0100 · #0100

FUN
To input the differentiated version of an instruction, press the NOT Key after the function code (FUN 2 1 NOT). The “@” symbol will be displayed next to differentiated instructions. Press the NOT Key again to change back the instruction back to a non-differentiated instruction. The “@” symbol will dis- appear.
To change an instruction after it has been entered, simply scroll through the program until the desired instruction is displayed and press the NOT Key. The “@” symbol should be displayed next to the instruction.
The operands of MOV (21) are normally word addresses, but a constant can be input by pressing the CONT/# Key first. When the CONT/# Key is pressed, the display will change to “#0000,” indicating that a constant can be entered.
CONT
B 1
A 0
Press the WRITE Key to write the instruction to Program Memory. The input display for the second operand will appear.
Key must be pressed to input a constant.
B 1
A 0 *
LR
Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
immediately without pressing the Shift and CH/# Keys.
A 0 ' + (
FUN
Press the WRITE Key to write the instruction to Program Memory.
#

CONT
Input the value of the operand from 0 to 65535.
prior to the input. Then enter the correct input.
sound and the hexadecimal display will not be displayed.
SHIFT TR
Input the value of the operand from –32,768 to 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
B 1
RESET
).
prior to the input. Then enter the correct input.
WRITE
DM
WRITE / ' (
6-2-8 Instruction Search
This operation is used to find occurrences of the specified instruction in the pro- gram and is possible in any mode.
OK OK OK
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or MONITOR mode.

1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Input the address from which the search will begin and press the Down Arrow Key. It is not necessary to input leading zeroes.
A 0
A 0 ↓
A 0
A 0
A 0 SRCH
OUT
Indicates the address of END instruction.
' ( 1/
Indicates the amount used by the user program in units of 0.1 Kwords. 6-2-9 Bit Operand Search This operation is used to find occurrences of the specified operand bit in the pro- gram and is possible in any mode.
OK OK OK
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or MONITOR mode.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Input the operand address. It is not necessary to input leading zeroes.
SHIFT CONT
Indicates the address of END instruction.
' ( 1/
Indicates the amount used by the user program in units of 0.1 Kwords.
#

6-2-10 Inserting and Deleting Instructions
This operation is used to insert or delete instructions from the program. It is pos- sible in PROGRAM mode only.
To demonstrate this operation, an IR 00105 NO condition will be inserted at program address 00206 and an IR 00103 NO condition deleted from address 00205, as shown in the following diagram.


00205 AND 00103 00206 AND NOT 00104 00207 OUT 01000 00208 END(01) -
Insertion Follow the procedure below to insert the IR 00105 NO condition at address 00206.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Input the address where the NO condition will be inserted and press the Down Arrow Key. It is not necessary to input leading zeroes.
A 0
F 5 INS , +
↓ " /
input the operands and then press the WRITE Key.
Deletion Follow the procedure below to delete the IR 00103 NO condition at address 00205.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Input the address where the NO condition will be deleted and press the Down Arrow Key. It is not necessary to input leading zeroes.
F 5 ↓ +
↑ + +
No No OK · Original Program

After completing the insertion and deletion procedures, use the Up and Down Arrow Keys to scroll through the program and verify that it has been changed correctly, as shown in the following diagram.
00104 00100 00105 00101
00205 AND 00105 00206 AND NOT 00104 00207 OUT 01000 00208 END(01) -
6-2-11 Checking the Program
This operation checks for programming errors and displays the program address and error when errors are found. It is possible in PROGRAM mode only.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH ' . (
A display like this will appear if an END instruction is reached:
No more errors exist if the END instruction is displayed. If errors are displayed, edit the program to correct the errors and check the pro- gram again. Continue checking the program by pressing the SRCH Key again until all errors have been corrected. 6-2-12 Bit, Digit, Word Monitor
This operation is used to monitor the status of up to 16 bits and words, although only 3 can be shown on the display at any one time. Operation is possible in any mode.
OK OK OK
Corrected Program · Address Instruction Operands · No No OK

Program Read then Monitor When a program address is being displayed, the status of the bit or word in that address can be monitored by pressing the MONTR Key.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
A 0 ↓
If the status of a bit is being monitored, that bit’s status can be changed using the Force Set/Reset operation. Refer to 6-2-24 Force Set, Reset for details.
If the status of a word is being monitored, that word’s value can be changed using the Hexadecimal/BCD Data Modification operation. Refer to 4-3-19 Hexadecimal, BCD Data Modification, 4-3-20 Binary Data Modification, 4-3-21 Signed Decimal Data Modification, and 4-3-22 Unsigned Decimal Data Modification for details.
Bit Monitor Follow the procedure below to monitor the status of a particular bit.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
B 1 MONTR
The Up or Down Arrow Key can be pressed to display the status of the pre- vious or next bit.
The displayed bit’s status can be changed using the Force Set/Reset opera- tion. Refer to 6-2-24 Force Set, Reset for details.
Word Monitor Follow the procedure below to monitor the status of a particular word.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
SHIFT CH
The Up or Down Arrow Key can be pressed to display the status of the pre- vious or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD Data Modification operation. Refer to Refer to 4-3-19 Hexadecimal, BCD Data Modification, 4-3-20 Binary Data Modification, 4-3-21 Singed Decimal Data Modification, and 4-3-22 Unsigned Decimal Data Modification for de- tails.

by holding down the SHIFT Key and then changing the operating mode.
The status of up to six bits and words can be monitored simultaneously, although only three can be shown on the display at any one time.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Input the address of the first bit or word and press the MONTR Key.
B 1 MONTR
EM MONTR
DM
If 4 or more bits and words are being monitored, the bits and words that do not appear on the display can be displayed by pressing the MONTR Key. If the MONTR Key is pressed alone, the display will shift to the right. If more than six bits and words are input, monitoring of the bit or word input first will be canceled. 4. Press the CLR Key to stop monitoring the leftmost bit or word and clear it from the display.
Programming Console display with the multiple address monitoring state unchanged. Press the SHIFT Key and then the MONTR Key from the initial dis- play to return to the multiple address monitoring state. The monitoring states can be retained for 6 bits and words. The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
This operation is used to monitor the up or down differentiation status of a particular bit. When detected, the up or down differentiation will be displayed and the buzzer will sound. It is possible in any mode.
OK OK OK
1, 2, 3... 1. Monitor the status of the desired bit according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. If 2 or more bits are being monitored, the de- sired bit should be leftmost on the display. In this case the differentiation status of LR 00 will be monitored.
!! !! !!
# · !! · !!

3!! !! !!
Indicates waiting for the bit to turn ON. To specify down-differentiation monitoring, press the SHIFT and then the Down Arrow Key. The symbols “D@” will appear.
!! !!
6-2-14 Binary Monitor
This operation is used to monitor the ON/OFF status of any word’s 16 bits. It is possible in any mode.
OK OK OK
1, 2, 3... 1. Monitor the status of the desired word according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. The desired word should be leftmost on the display if 2 or more words are being monitored.
Bit 15 Bit 00 The status of force-set bits is indicated by “S,” and the status of a force-reset bits is indicated by “R,” as shown below.
6-2-21 Binary Data Modification for details. b) The Up or Down Arrow Key can be pressed to display the status of
the previous or next word’s bits.

6-2-15 Three-Word Monitor
This operation is used to monitor the status of three consecutive words. It is possible in any mode.
OK OK OK
1, 2, 3... 1. Monitor the status of the first of the three words according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. If 2 or more words are being monitored, the desired first word should be left- most on the display.
The Up and Down Arrow Keys can be used to shift one address up or down. The status of the displayed words can be changed at this point. Refer to 6-2-18 Three-word Data Modification. The display can be changed to display ASCII text, which is useful when three consecutive words containing an ASCII message are displayed. Refer to 6-2-26 Hex-ASCII Display Change. 3. Press the CLR Key to end 3-word monitoring and return to the normal moni- toring display. The rightmost word on the 3-word monitor display will be monitored.
by holding down the SHIFT Key and then changing the operating mode.
This operation converts the contents of the specified word from signed hexa- decimal (two’s complement format) to signed decimal for display. The opera- tion can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK OK OK
1, 2, 3... 1. Monitor the word that is to be used for decimal monitor with sign. During mul- tiple address monitoring, the leftmost word will be converted.

At this point, the contents of the displayed word can be changed with a signed-decimal input. Refer to 6-2-22 Signed Decimal Data Modification. 3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal dis- play and return to normal monitoring.
6-2-17 Unsigned Decimal Monitor
This operation is used to convert hexadecimal data in a word to unsigned decimal for display. The operation can be executed while using I/O monitor- ing, multiple address monitoring or 3-word monitoring.
OK OK OK
1, 2, 3... 1. Monitor the word that is to be used for decimal monitor without sign. During multiple address monitoring, the leftmost word will be converted.
At this point, the contents of the displayed word can be changed with an un- signed-decimal input. Refer to 6-2-23 Unsigned Decimal Data Modification. 3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal dis- play and return to normal monitoring.
6-2-18 Three-Word Data Modification
This operation is used to change the contents of one or more of the 3 con- secutive words displayed in the Three-Word Monitor operation. It is possible in MONITOR or PROGRAM mode only.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3... 1. Monitor the status of the desired words according to the procedure de- scribed 6-2-15 Three-Word Monitor.
/+," $0

(Input the new value and press the WRITE Key to write the changes in memory if no more changes will be made.)
D 3
and the 3-word monitor display will return without any changes in data memory.
There are two operations that can be used to change the SV of a timer or counter. They are possible in MONITOR or PROGRAM mode only. In MON- ITOR mode, the SV can be changed while the program is being executed.
The timer or counter SV can be changed either by inputting a new value or by incrementing or decrementing the current SV.
This operation can be used to input a new SV constant, as well as to change an SV from a constant to a word address designation and vice versa. The following examples show how to input a new SV constant and how to change the SV from a constant to an address.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Display the desired timer or counter.
TIM
Key.
E 4 WRITE ) /
b) To change to a word address designation, input the word address and
press the WRITE Key.
SHIFT CH
AR
B 1
HR
*DM
Incrementing and Decrementing a Constant
This operation can be used to increment and decrement an SV constant. It is possible only when the SV has been entered as a constant.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Display the desired timer or counter.
No OK OK

↓ CHG EXT ) )
The constant on the left is the old SV and the constant on the right will be- come the new SV constant in step 5. 4. Press the Up and Down Arrow Keys to increment and decrement the con- stant on the right. (In this case the SV is incremented once.)
↓ ) ) /
6-2-20 Hexadecimal, BCD Data Modification
This operation is used to change the BCD or hexadecimal value of a word being monitored using the procedure described in 6-2-12 Bit, Digit, Word Monitor. It is possible in MONITOR or PROGRAM mode only.
Words SR 253 to SR 255 cannot be changed.
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3... 1. Monitor the status of the desired word according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired word should be leftmost on the display.
A 0
6-2-21 Binary Data Modification
This operation is used to change the status of a word’s bits when the word is monitored using the procedure described in 6-2-14 Binary Monitor. It is pos- sible in MONITOR or PROGRAM mode only.
Bits SR 25300 to SR 25507 and timer/counter flags cannot be changed.

Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3... 1. Monitor the status of the desired word according to the procedure described 6-2-14 Binary Monitor.
Bit 15 Bit 00 2. Press the CHG Key to begin binary data modification.
A flashing cursor will appear over bit 15. The cursor indicates which bit can be changed. 3. Three sets of keys are used to move the cursor and change bit status: a) Use the Up and Down Arrow Keys to move the cursor to the left and right.
↓ ↓ 2
b) Use the 1 and 0 Keys to change a bit’s status to on or off. The cursor will
move one bit to the right after one of these keys is pressed.
c) Use the SHIFT+SET and SHIFT+RESET Keys to force-set or force-re-
set a bit’s status. The cursor will move one bit to the right after one of these keys is pressed. The NOT Key will clear force-set or force-reset status.
6-2-22 Signed Decimal Data Modification
This operation is used to change the decimal value of a word being moni- tored as signed decimal data, within a range of –32,768 to 32,767. The con- tents of the specified word are converted automatically to signed hexadeci- mal (two’s complement format).
Words SR 253 to SR 255 cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
2 · (Binary monitor) · No OK OK

1, 2, 3... 1. Monitor (signed decimal) the status of the word for which the present value is to be changed.
. ,
C2 7 6 8 WRITE . ",$
RESET
If an erroneous input has been made, press the CLR Key to restore the sta- tus prior to the input. Then enter the correct input. The buzzer will sound if a value outside the specified range is input, allowing no writing.
This operation is used to change the decimal value of a word being moni- tored as unsigned decimal data, within a range of 0 to 65,535. A change into hexadecimal data is made automatically.
Words SR 253 to SR 255 cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3... 1. Monitor (unsigned decimal) the status of the word for which the present val- ue is to be changed.
C 2 7 6 8 WRITE 2 ",$
If an erroneous input has been made, press the CLR Key to restore the sta- tus prior to the input. Then enter the correct input. The buzzer will sound if a value outside the specified range is input, allowing no writing.

6-2-24 Force Set, Reset
This operation is used to force bits ON (force set) or OFF (force reset) and is useful when debugging the program or checking output wiring. It is possible in MONITOR or PROGRAM mode only.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3... 1. Monitor the status of the desired bit according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired bit should be leftmost on the display.
The cursor in the lower left corner of the display indicates that the force set/ reset is in progress. Bit status will remain ON or OFF only as long as the key is held down; the original status will return one cycle after the key is re- leased. 3. Press the SHIFT and SET Keys or SHIFT and RESET Keys to maintain the status of the bit after the key is released. In this case, the force-set status is indicated by an “S” and the force-reset status is indicated by an “R.” To return the bit to its original status, press the NOT Key or perform the Clear Force Set/Reset operation. Refer to 6-2-25 Clear Force Set/Reset for de- tails. Forced status will also be cleared in the following cases: a) When the PC’s operating mode is changed (although the forced status
will not be cleared when the mode is changed from PROGRAM to MON- ITOR if SR 25211 is ON) b) When the PC stops because a fatal error occurred c) When the PC stops because of a power interruption d) When the Clear Force Set/Reset Operation is performed
This operation is used to restore the status of all bits which have been force set or reset. It is possible in MONITOR or PROGRAM mode only.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.

1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Press the SET and then the RESET Key. A confirmation message will ap- pear.
from the beginning.
6-2-26 Hex-ASCII Display Change
This operation is used to convert word data displays back and forth between 4-digit hexadecimal data and ASCII. It is possible in any mode.
The displayed PV of the timer or counter cannot be changed.
OK OK OK
1, 2, 3... 1. Monitor the status of the desired word(s) according to the procedure de- scribed in 6-2-12 Bit, Digit, Word Monitor. While the multiple addresses are being monitored, the leftmost word is subject to change.
TR
This operation is used to display the current average cycle time (scan time). It is possible only in RUN or MONITOR mode while the program is being executed.
1, 2, 3... 1. Press the CLR Key to bring up the initial display. 2. Press the MONTR Key to display the cycle time.
“MS” in the display indicates the unit “ms” for the cycle time. There might be differences in displayed values when the MONTR Key is pressed repeatedly. These differences are caused by changing execution conditions.

6-2-28 Reading and Setting the Clock
This operation is used to read or set the CPU’s clock. The clock can be read in any mode, but can be set in MONITOR or PROGRAM mode only.
Operation RUN MONITOR PROGRAM
Read clock OK OK OK
Set clock No OK OK
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
FUN SHIFT MONTR 00. .
# /# ' (
The digit that can be changed will flash. If necessary, input a new value with the Up and Down Arrow Keys or Numeric Keys. Press the CHG Key to move the cursor to the next digit. The following table shows the setting ranges for each value.
Year Month Day Hour Minute Second Day-of-week
00 to 99 01 to 12 01 to 31 00 to 23 00 to 59 00 to 59 0 to 6 (SUN to SAT)
Press the CLR Key to return to the initial display.
This section demonstrates all of the steps needed to write a program with the Programming Console.
Use the following procedure when writing a program to the CPM2B for the first time.
1, 2, 3... 1. Set the Programming Console’s mode switch to PROGRAM mode and turn on the CPM2B’s power supply. The password input display will appear on the Programming Console.
RUN
PROGRAM

SET NOT RESET
MONTR
FUN ! ' (
MONTR
!
·

6-3-2 Example Program
The following ladder program will be used to demonstrate how to write a pro- gram with the Programming Console. This program makes output IR 01000 flicker ON/OFF (one second ON, one second OFF) ten times after input IR 00000 is turned ON.

Flicker output (10 counts)
The mnemonic list for the example program is shown in the following table. The steps required to enter this program from a Programming Console are described in 6-3-3 Programming Procedures.


6-3-3 Programming Procedures The example program will be written to the CPM2B according to the mnemonic list in 6-3-2 Example Program. The procedure is performed beginning with the initial display. (Clear the memory before entering a new program.)
for details on correcting the error.
1, 2, 3... 1. Input the normally open condition IR 00000. (It isn’t necessary to input leading zeroes.)
WRITE ' (

WRITE ' (

1, 2, 3... 1. Input the normally open condition IR 20000.


TIM
WRITE , )

A 0 , )
WRITE " ' (
(3) Inputting the Two-second Timer
The following key operations are used to input the 2-second timer.
1, 2, 3... 1. Input the normally open condition IR 20000.


TIM
WRITE 0 )
WRITE ' (
(4) Inputting the 10-count Counter
The following key operations are used to input the 10-count counter.
1, 2, 3... 1. Input the normally open condition IR 20000.

AND TIM
WRITE ' (


CNT
WRITE )
B 1
WRITE / ' (
(5) Inputting the Flicker Output
1, 2, 3... 1. Input the normally open condition IR 20000.



Input END(01). (The display shows three digits in the function code, but only the last two digits are input for CPM2B PCs.)

Check the program syntax in PROGRAM mode to make sure that the program has been input correctly.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.

SRCH ' . (
A0 " ' ( 1
programming errors that may be displayed during a program check.
The search will continue until an END(01) instruction or the end of Program Memory is reached.
If errors are displayed, edit the program to correct the errors and check the pro- gram again. Continue checking the program until all errors have been corrected.
Switch the CPM2B in MONITOR mode and check the operation of the program.
1, 2, 3... 1. Set the Programming Console’s mode switch to MONITOR mode.
RUN
PROGRAM
MONTR
SET
The cursor in the lower left corner of the display indicates that the force set is in progress. The bit will remain ON as long as the Set Key is held down.
There is a mistake in the program if the output indicator doesn’t flash. In this case, check the program and force set/reset bits to check operation.
· !!

This section describes procedures for test runs of CPM2B operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during PC operation.
7-1 Initial System Checks and Test Run Procedure 114 7-1-1 Initial System Checks 114 7-1-2 Flash Memory Precautions 114 7-2 CPM2B Test Run Procedure 114 7-3 Self-diagnostic Functions 115 7-3-1 Identifying Errors 115 7-3-2 User-defined Errors 116 7-3-3 Non-fatal Errors 116 7-3-4 Fatal Errors 117 7-4 Troubleshooting Flowcharts 118 7-5 Maintenance Inspections 125 7-6 Battery Replacement 126

7-1 Initial System Checks and Test Run Procedure
7-1-1 Initial System Checks
Check the following items after setting up and wiring the CPM2B, but before per- forming a test run.
Item Points to check
Power supply and I/O connections
Is the wiring correct? Are the terminals securely tightened? Are there any shorts between crimp terminals or wires?
Refer to 3-5 Wiring and Connections for details.
Connecting cables Are the cables all connected correctly and locked?
Refer to 3-5 Wiring and Connections for details.
Always clear memory before beginning to program the CPM2B. Although memory is cleared before the CPU Board is shipped, the contents of the DM, HR, AR, and counter areas may change in transit. When a CPU Board without a clock is being used and the contents of DM have been cleared, battery error detection must be disabled in the PC Setup by setting the leftmost digit of DM 6655 to 1.
See 1-3-3 Operating Mode at Startup to determine what mode the CPM2B will enter when the power is turned on.
Observe the following precautions to protect the flash memory and ensure proper operation.
1, 2, 3... 1. Power Supply Application a) Check the CPM2B’s power supply voltage and terminal connections. b) Check the I/O devices’ power supply voltage and terminal connections. c) Turn on the power supply and check that the “PWR” indicator lights.

d) Use a Programming Device to set the CPM2B to PROGRAM mode. 2. I/O Wiring Checks a) With the CPM2B in PROGRAM mode, check the output wiring by turning
on the output bits with the force set and force reset operations. b) Check the input wiring with the CPM2B’s input indicators or a Program-
ming Device’s monitor operations. 3. Test Run a) Use a Programming Device to set the CPM2B to RUN or MONITOR
mode and check that the “RUN” indicator lights. b) Check the sequence of operation with the force set/reset operations, etc. 4. Debugging Correct any programming errors that are detected. 5. Saving the Program a) Use a Programming Device to write the program to a backup floppy disk. b) Print out a hard copy of the program with a printer.
ware and Programming Console operations.
The CPM2B is equipped with a variety of self-diagnostic functions to help iden- tify and correct errors and reduce down time.
An error can be identified by the error message displayed on a Programming Device, error flags in the AR and SR areas, and the error code output to SR 253.
When an error is detected, a corresponding error message will be displayed on the Programming Console or other Programming Device connected to the PC.
When a hardware error is detected, the corresponding error flag in the AR or SR area will be turned ON.
When an error is detected, a specific 2-digit hexadecimal error code is output to SR 25300 to SR 25307. The error code and time of occurrence are also output to the Error Log Area (DM 2000 to DM 2021).
severe failure alarm (FALS) instruction is executed, PC operation will stop and all outputs will be turned OFF. External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.

7-3-2 User-defined Errors There are three instructions that can be used to define errors or messages. FAL(06) causes a non-fatal error, FAL(07) causes a fatal error, and MSG(46) sends a message to the Programming Console or host computer connected to the PC.
FAL(06) is an instruction that causes a non-fatal error. The following will occur when an FAL(06) instruction is executed:
1, 2, 3... 1. The ERR indicator on the CPU Board will flash. PC operation will continue. 2. The instruction’s 2-digit BCD FAL number (01 to 99) will be written to SR 25300 to SR 25307. The FAL numbers can be set arbitrarily to indicate particular conditions, but the same number should not be used as both an FAL number and an FALS number. To clear an FAL error, correct the cause of the error and then execute FAL 00 or use a Programming Device to clear the error.
FALS(07) is an instruction that causes a fatal error. The following will occur when an FALS(07) instruction is executed:
1, 2, 3... 1. Program execution will be stopped and all outputs will be turned OFF. 2. The ERR indicator on the CPU Board will be lit. 3. The instruction’s 2-digit BCD FALS number (01 to 99) will be written to SR 25300 to SR 25307. The FALS numbers can be set arbitrarily to indicate particular conditions, but the same number should not be used as both an FAL number and an FALS number. To clear an FALS error, use a Programming Device to switch the PC to PRO- GRAM Mode, correct the cause of the error, and then clear the error.
MSG(46) is used to display a message on a Programming Device connected to the CPM2B. The message, which can be up to 16 characters long, is displayed when the instruction’s execution condition is ON. 7-3-3 Non-fatal Errors
PC operation and program execution will continue after one or more of these errors have occurred. Although PC operation will continue, the cause of the error should be corrected and the error cleared as soon as possible. When one of these errors occurs, the POWER and RUN indicators will remain lit and the ERR indicator will flash.
Message FAL No. Meaning and appropriate response SYS FAIL FAL** (** is 01 to 99 or 9B.)
01 to 99 An FAL(06) instruction has been executed in the program. Check the FAL number to determine conditions that would cause execution, correct the cause, and clear the error.
9B An error has been detected in the PC Setup. Check flags AR 1300 to AR 1302, and correct as directed.
AR 1300 ON: An incorrect setting was detected in the PC Setup (DM 6600 to DM 6614) when power was turned on. Correct the settings in PROGRAM Mode and turn on the power again.
AR 1301 ON: An incorrect setting was detected in the PC Setup (DM 6615 to DM 6644) when switching to RUN or MONITOR mode. Correct the settings in PROGRAM Mode and switch to RUN or MONITOR mode again.
AR 1302 ON: An incorrect setting was detected in the PC Setup (DM 6645 to DM 6655) during operation. Correct the settings and clear the error.
SCAN TIME OVER F8 The cycle time has exceeded 100 ms. (SR 25309 will be ON.)
This indicates that the program cycle time is longer than recommended. Reduce cycle time if possible. (The CPM2B can be set so that this error won’t be detected.) Battery error (no message)
F7 If the voltage of the C500-BAT08 backup battery is below the minimum level, the ERR indicator will flash and SR 25308 will be turned ON. Replace the battery. (See 7-6 Battery Replacement for details.)

7-3-4 Fatal Errors
PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of these errors have occurred. CPM2B operation can’t be restarted until the PC is turned off and then on again or a Programming Device is used to switch the PC to PROGRAM mode and clear the fatal error. All CPU Board indicators will be OFF for the power interruption error. For all other fatal operating errors, the POWER and ERR indicators will be lit. The RUN indicator will be OFF.
Meaning and appropriate response
No.
Power interruption (no message)
00 Power has been interrupted for more than 2 ms. Check power supply voltage and power lines. Try to power-up again. MEMORY ERR F1 AR 1308 ON: There is a non-existent bit or word address in the user program. Check the program and correct errors. AR 1309 ON: An error has occurred in flash memory. Replace the CPU Board. AR 1310 ON: A checksum error has occurred in read-only DM (DM 6144 to DM 6599). Check and correct the settings in the read-only DM area. AR 1311 ON: A checksum error has occurred in the PC Setup. Initialize the PC Setup and input the settings again. AR 1312 ON: A checksum error has occurred in the program. Check the program and correct any errors detected. AR 1313 ON: A checksum error has occurred in the expansion instructions data and all function codes have been set the their default values. Reset the expansion instructions.
AR 1314 ON: Data was not maintained in an area specified for holding. Clear the error, check the data in the areas specified for holding, and try again. NO END INST F0 END(01) is not written in the program. Write END(01) at the end of the program.
I/O BUS ERR C0 An error has occurred during data transfer between the CPU Board and an Expansion I/O Board. Check the Board’s connecting cable. I/O UNIT OVER E1 Too many Expansion I/O Boards have been connected. Check the Board configuration.
SYS FAIL FALS** (** is 01 to 99 or 9F.)
01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to determine the conditions that caused execution, correct the cause, and clear the error. 9F The cycle time has exceeded the Maximum (Watch) Cycle Time setting (DM 6618). Check the cycle time and adjust the Maximum Cycle Time setting if necessary.
Message FALS

7-4 Troubleshooting Flowcharts
Use the following flowcharts to troubleshoot errors that occur during operation.
Check power supply. (See page 119.) No
Operation stopped. Check for fatal errors.
(See page 120.)
Check for non-fatal errors. (See page 121.)
Check I/O. (See page 122.)
Check operating environment. (See page 124.)
Replace the CPU Board.

PWR indicator not lit.
Connect power supply.
Is PWR indicator lit?
Set supply voltage within acceptable limits.
Is PWR indicator lit?
Are there any loose terminal screws or bro-
Tighten screws or replace wires.
Is PWR indicator lit? Yes
Correct the short circuit or limit the connected load to the spec- ification range.
Has the external power supply shorted
Is PWR indicator lit? Yes
Replace the CPU Board.

RUN indicator not lit.
Is the ERR indi-
Determine the cause of the error with a Programming Device.
Is PC mode displayed
Is PC mode displayed on
Turn the power supply OFF, and then ON again.
Is a fatal error
Identify the error, eliminate its cause, and clear the error. Follow the Memory Error Check flowchart if a memory error has occurred.
Switch to RUN or MONITOR mode.
Is the RUN indicator lit?
Replace the CPU Board.

ERR indicator flashing.
Determine the cause of the error with a Programming Device.
Is a non-fatal error
Identify the error, eliminate its cause, and clear the error.
Is the ERR indicator flashing?
Replace the CPU Board.

The I/O check flowchart is based on the following ladder diagram section.
00003 (LS2)
SOL1
SOL1 malfunction.
No Is the IR 01003 output indicator
Check the voltage at the IR 01003 terminals.
Wire correctly.
Correct the short circuit or limit the connected load to the specified range.
Monitor the ON/OFF status of IR 01003 with a Programming Device.
Operation OK? Is output wiring
Is the external power supply shorted
Disconnect the external wires and check the conductivity of each wire.
Operation OK? No Yes
Replace the CPU Board or Expansion I/O Board with the problem.
Check output device SOL1.

Are the IR 00002 and IR 00003 input indi-
Check the voltage at the IR 00002 and IR 00003 terminals.
Check the voltage at the IR 00002 and IR 00003 terminals.
Check operation by using a dummy input signal to turn the input ON and OFF.
Wire correctly.
Tighten the terminal screws
Replace the CPU Board or Expansion I/O Board.
Replace the CPU Board or Expansion I/O Board.
Return to “start.”
Check input devices LS1 and LS2.

Consider using a fan or cooler. Is the ambient
temperature below 55°C?
Is the ambient temperature above
Consider using a heater.
Is the ambient humidity
Consider using an air conditioner.
Install surge protec- tors or other noise- reducing equipment at noise sources.
Consider constructing an instrument panel or cabinet.
Is the installation environment okay?
End.

Memory error occurred.
Replace the CPU Board.
AR 1314 ON?
Check/correct backed-up data and clear error.
Check the program, correct any errors, and clear the error.
Check the error indicated by the flag that is ON, correct set- tings as required, and write data to the flash memory.
AR 1310 to AR 1312 ON?
Check the external environment.
In order for your SYSMAC system to operate in optimum condition, be sure to carry out daily or periodical inspections.
The main system components of a SYSMAC system are semiconductors, and it contains few components with limited lifetimes. Poor environmental conditions, however, can lead to deterioration of the electrical components, making regular maintenance necessary.

The standard period for maintenance checks is 6 months to 1 year, but more fre- quent checks are required if the PC is operated in more demanding conditions. If the criteria are not met, adjust to within the specified ranges.
Inspection items Details Criteria Remarks
Power supply Determine whether the voltage fluctuation at the power supply terminals is within specifications.
Within the voltage variation range (20.4 to 26.4 VDC)
Is the ambient temperature inside the panel appropriate?
0 to 55C Thermometer
Is the ambient humidity inside the panel appropriate?
35% to 85% RH with no condensation
Has dirt or dust collected? None Visual inspection I/O power supply Is the voltage fluctuation measured at the I/O terminals within the standard range?
Each I/O terminal must conform to the specifications
Installation status Are all Boards securely installed? Nothing is loose Phillips screwdriver Are all connection cables and connectors inserted completely and locked?
Nothing is loose Visual inspection
Are any of the external wiring screws loose?
Nothing is loose Phillips screwdriver
Are any of the external wiring cables frayed?
No external abnormalities Visual inspection
Product service life Contact output relay Electrical:
Mechanical:
Battery (C500-BAT08) 5 years ---
battery in fire. The battery may explode, burn, or leak and cause personal injury.
Turn ON the power supply for at least 5 minutes before replacing the battery in order to recharge the backup capacitor. Turn OFF the power supply to the CPU Board before replacing the battery. Use the procedure below when replacing the battery. This procedure must be completed within 5 minutes to prevent loss of memory contents. Dispose of the old battery properly.
CPU Boards that are equipped with a clock are also equipped with a backup bat- tery that has a 5-year lifetime at 25C. Use the following procedure when replac- ing the backup battery.
1, 2, 3... 1. Stop CPM2B operation and turn OFF the CPM2B’s power supply.




CPU Boards



CPM2B-CN601 Connects an Expansion I/O Board to the CPU Board or another Expansion I/O Board. (This cable is identical to the cable supplied with an Expansion I/O Board.)


I/O Connectors

XG5M-2035-N Socket (for AWG 26 to AWG 28 wire)
XG5S-2012 Full Cover (two are required for each socket)
XG5S-1001 Partial Cover (two are required for each socket)


C200H-PRO27-E Hand-held, w/backlight; requires a C200H-CN222 or C200H-CN422 Connecting Cable, see below.
C200H-CN422 4-m cable CS1W-CN224 Connects the C200H-PRO27-E 2-m cable CS1W-CN624 directly to a CPM2B CPU Board. 6-m cable
WS01-CPTB1-E SYSMAC-CPT For IBM PC/AT or compatible computers (3.5” disks (2HD) and CDROM)

Maintenance Accessories

CPM1-EMU01-V1 Expansion Memory Unit Uploads the ladder program and DM 6144 to DM 6655 from the PC to the EEPROM and downloads the ladder program and DM 6144 to DM 6655 from the EEPROM to the PC.

CPM2B port Appearance Model number Name Comments Cable length Peripheral
XW2Z-200S-V RS-232C For a 9-pin computer serial port 2 m
Appearance Model number Name Specifications
NT-AL001-E RS-422 Adapter Use for CPM2B RS-232C port to RS-422A conversion. Requires a 5-VDC, 150 mA power supply which is supplied through the CPM2B connection. (Can also be connected to a personal computer, but this connection requires an external 5-VDC power supply.)
3G2A9-AL004-E Link Adapter Use for personal computer RS-232C port to RS-422A. (Can also be connected to a CPM2B.)
CPM1-CIF11 RS-422 Adapter Use for CPM2B peripheral port to RS-422A conversion.
XW2Z-070T-1 RS-232C Cables Use for CPM2B RS-232C port to NT-AL001-E connection. (0.7-m cable) XW2Z-200T-1
(For use with the NT-AL001-E.) Use for CPM2B RS-232C port to NT-AL001-E connection. (2-m cable)

Dimensions
All dimensions are in millimeters.

Six 3.5 dia.

Four 4.5 dia.

Assembly Dimensions
Front view Side view

CPU Board · Expansion I/O Board · Mounting Bracket

A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code Date Revised content 1 February 2000 Original production
Revision code
What the fault codes shown on the display mean and how to clear them.