BU1002SW/BU3002SW
Instruction Manual


Disclaimers We are not liable for any damage or secondary damage resulting from the use of our product, including malfunction and failure of equipment, connected devices, or software.
©OMRON Corporation. 2006 All Rights Reserved.

This manual contains important instructions for BU1002SW that should be followed when using the UPS and batteries.
This symbol indicates earth ground.
This symbol indicates turning on UPS.
This symbol indicates turning off UPS.
Internal battery voltage is 36V DC for BU1002SW and 72V DC for BU3002SW.
The maximum ambient temperature of the UPS is 40°C.
The unit is intended for installation in a temperature controlled, indoor area free of conductive contaminants.

Read “Safety precautions”
Remove the product from the package and check the contents
Are you using UPS monitoring
Read “Using the UPS monitoring software and contact signal” Page 65
Check the operation and displays Pages 31
Measure the backup time
Charge the battery again
Page 33 * Preparation for operation is complete.
battery? Fan stopped? Perform maintenance and inspection Page 53


* Property damage means damage to houses/household effects, livestock, and pets.
: Indicates prohibition. For example, indicates that disassembly is prohibited.
: Indicates obligation. For example, indicates that grounding is necessary.
Two or more people should work together to carry, unpack and install the BU3002SW. ●Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.
Keep plastic package bags out of reach of children. ●Children may suffocate if they place their heads into plastic bags.
Safety precautions

When an abnormality (unusual sound or smell) occurs, turn OFF the unit's power switch and disconnect the AC input plug from the wall outlet. Install the unit soon after the AC input plug is disconnected from the wall outlet. ●When performing maintenance on the connected devices, follow the above instructions to ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc. , which have a half-wave rectifier that allows only half-cycle AC power to flow through. ●Overcurrent may damage the UPS.
Provide secure grounding. ●After checking the plug shape of the wall outlet, directly connect the AC input plug of the unit to it. A failure or leak that occurs when the unit is not properly grounded may result in electric shock.
Do not disassemble, repair, or modify the unit. ●Doing so may cause an electric shock or a fire.
Safety precautions

All of the included accessories are designed to be used exclusively with the unit. Do not use the accessories with other devices. ●Doing so may compromise the safety of devices.
Do not connect devices that cannot be used with commercial power supply. ●When the unit’s power switch is turned ON and an error occurs with the connected device, bypass operation is performed and commercial power supply is supplied as is to the con- nected devices.
When in use, make sure the output terminal block cover is attached. Do not turn ON the power switch when it is detached. ●Voltage is applied to the output terminal block when the power switch is ON, which can result in electric shock.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installer near the equipment and shall be easily accessible.
Safety precautions

When the battery is dead, replace it immediately or stop using the unit.
* The values in the table are the expected life under standard use conditions and are not guaranteed.
Using a dry cloth, periodically wipe the dust from the AC input plug, power supply output receptacles and output terminal block. ●Accumulated dust may cause a fire.
Do not use the unit in a closed place and do not cover the unit. ●Doing so may cause abnormal heating or a fire.
Do not place objects on the unit that are 25 kg or heavier, and do not drop metal objects onto the unit. ●Doing so may cause distortion/damage to the case or a failure of the internal circuit, which may cause a fire.
Safety precautions

When maintaining the connected equipment, turn OFF the power switch and disconnect the AC input plug. ●Even if you disconnect the AC input plug while the UPS is operating, the power output of this unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit. ●Doing so may cause an electric shock or a fire.
Do not throw the unit into fire. ●The lead battery in the unit may explode, or leak dilute sulfuric acid.
Do not insert metal objects into the power supply output receptacle or terminal block of the UPS. ●Doing so may result in electric shock.
Do not insert metal objects into the battery connectors. ●Doing so may result in electric shock.
Do not replace the battery in a place where there is flammable gas. ●Spark may occur when connecting the battery, which may cause an explosion or fire.
Do not disassemble or modify the battery. ●Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery and do not expose it to strong impact. ●Dilute sulfuric acid may leak.
Do not short the battery with metal objects.
Safety precautions

Do not use a new battery and an old battery at the same time. ●Dilute sulfuric acid may leak.
Safety precautions

Do not short the output lines of the unit to each other, and do not short the output lines to the ground. ●The unit may fail.
Do not connect the AC input plug of the unit to its Power Supply Output Receptacle during the Battery Mode. ●The unit may fail.
Check system operation beforehand if the unit is used in combination with a device whose power supply frequency fluctuates widely, such as a personal electric generator. ●The unit automatically recognizes the input power frequency when input power is supplied.If the unit is connected when the input power frequency is not stable at the rated level, the unit may misidentify the power supply frequency and may fail to operate normally. (If the unit is in operation, changing from commer- cial power supply to another power supply source, such as generating equipment, will cause no problem. Set the generator's frequency to the same level as that of the commercial power supply.)
Do not install or store the unit in a place exposed to direct sunlight. ●The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Before stopping the commercial power to the unit, turn OFF the power switch of the unit. ●The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery Mode, the battery life may be significantly shortened.
Safety precautions

If this unit is used with an inductive device such as a coil or motor, check the operation beforehand. ●With some types of devices, the effect of inrush current may cause this unit to stop operating properly.
In the event you transfer or sell this unit to a third party, please include all of the documentation that came with the unit. This is to ensure that the unit is used in line with the conditions described in the included documentation. ●This manual contains important safety-related information. Please read and understand the contents of the manual before beginning operation.
Take measures for handling unforeseen accidents, such as data backup and system redundancy. ● The output may stop when there is a circuit failure in the UPS.
This unit uses lead acid batteries, ●Which are a valuable recyclable resource. Please recycle.
Explanation Usual operation ●You may either leave the power switch of the unit ON (operation status) or turn it OFF each time when stopping the connected system. Choose whichever operation method is more convenient. We recommend turning OFF the power switch when you do not use connected devices for a long time.
Quitting Battery Mode ●If a power failure lasts for an extended period of time, the battery discharges and power output from the unit stops. Shut down your computer after performing appropriate procedures (for example, saving data) while the unit is still supplying power.
Rebooting ●If the battery discharges completely during a power failure, the unit stops. After recovery from the power failure, the unit automatically restarts and supplies power. If you do not want to restart the connected devices, turn OFF the power switch of either the unit or the connected devices.
Setting switch 2 can be used to select whether or not auto restart is performed. See Page 43
Scheduled operation using the UPS monitoring software ●When performing scheduled operation in which the UPS is stopped and a device such as a breaker is used to stop the UPS at the same time that commercial power stops, specify a period of no more than 3 months for the start of the next operation. If you specify a period longer than 3 months, the internal timer is reset and the scheduled operation does not start. Note that this period reduces to approximately half when the battery is dead. If a period of 3 months is exceeded, you start operation by supplying commercial power and pressing the start switch. However, if the battery is dead, you may not be able to start operation. In this case, replace the battery according to the instructions in “6-2 Replacing the battery” on page 54.
Safety precautions · Pb · See also

1-1 Unpacking the product

Two or more people should work together to carry, unpack and install the BU3002SW. ● Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.
The weight of the product is 15.5 kg (BU1002SW) , 35 kg (BU3002SW). Unpack/transport this product considering this weight. ●Dropping may cause injury.
Open the package box and take out the UPS and accessories.
Check whether all the package contents are included and there is no damage found on their appearance. If you should notice defects or anything wrong, contact us;

Instruction manual (Japanese and English versions) 1 Warranty 1 User registration card 1 Label (How to determine operating status) 1 Connector for remote ON/OFF 1 Terminal block cover for output (with cable clamp) 1 Omron contact info label 1
Terminal block cover for BU3002SW (with cable clamp)
Instruction manual (Japanese/English edition)
Label (How to determine operating status)
Connector for remote ON/OFF
Terminal block cover for BU1002SW (with cable clamp)
OMRON contact info label Connection cable(RS-232C)
(Approx. 2.2 m)
(Approx. 2.2 m)

This section describes the name of each part of the UPS. For information on the function of each part, refer to "2. Installation and connection" on page 17 and "3. Opera- tion" on page 34 that provides the details.

A. Status indicator digital display B. Power switch C. Beep stop/test switch D. Battery addition lamp E. Battery replacement lamp F. Power supply output lamp G. Bypass operation lamp
(The input power supply is output as is.) H. Setting switch cover I. Connection capacity/battery level meter - バッテリ



<BU1002SW>
A
B C D
E
A. USB connector B. RS-232C connector C. Contact signal card D. Contact signal connector E. Remote ON/OFF connector F. Additional battery connector G. Power supply output receptacle A (IEC60320 C13) H. Power supply output receptacle B (IEC60320 C13) I. Power supply output receptacle C (IEC60320 C13) J. Terminal block for output K. Grounding terminal L. AC input cable M. AC input overcurrent protection N. Cooling fan
N
G
H
M
J
K
<BU3002SW>
A B C D
E
F
A. USB connector B. RS-232C connector C. Contact signal card D. Contact signal connector E. Remote ON/OFF connector F. Handle G. Additional battery connector H. Additional battery signal connector I. Power supply output receptacle A (IEC60320 C19) J. Power supply output receptacle A (IEC60320 C13) K. Power supply output receptacle B (IEC60320 C13) L. Overcurrent protection switch for output 15A M. Power supply output receptacle C (IEC60320 C13) N. AC input overcurrent protection switch 20A O. AC input cable P. Terminal block for output Q. Fixed stand R. Casters S. Grounding terminal T. Cooling fan
See installation Instructions before connecting to the supply. Not For Current Interrupting.
MAX
J
K
M
T
N
INPUT AC200–240V 50/60Hz 16A 1ø3W
P
S
Refer to the instruction manual for the tightening torque. Use Copper Conductor Only.
Q
R
R

Start the UPS.
Stop the UPS.
Suspend a beep.
UPS output power enabled, supplied by operating on line mode, battery mode.
UPS operating on battery mode.
Additional battery unit connected to the UPS. (For BU100XS only.)
Error occurred with UPS.
Batteries at end of useful life, necessary to replace the batteries.
Symbol Description

Caution (for installation and connection)
Two or more people should work together to carry, unpack and install the BU3002SW. ●Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.
Keep plastic package bags out of reach of children. ●Children may suffocate if they place their heads into plastic bags.
When an abnormality (unusual sound or smell) occurs, turn OFF the unit's power switch and disconnect the AC input plug from the wall outlet. Install the unit soon after the AC input plug is disconnected from the wall outlet. ●When performing maintenance on the connected devices, follow the above instructions to ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc. , which have a half-wave rectifier that allows only half-cycle AC power to flow through. ●Overcurrent may damage the UPS.
Provide secure grounding. ●After checking the plug shape of the wall outlet, directly connect the AC input plug of the unit to it. A failure or leak that occurs when the unit is not properly grounded may result in electric shock.
Do not disassemble, repair, or modify the unit. ●Doing so may cause an electric shock or a fire.

All of the included accessories are designed to be used exclusively with the unit. Do not use the accessories with other devices. ●Doing so may compromise the safety of devices.

Do not connect devices that cannot be used with commercial power supply. ●When the unit’s power switch is turned ON and an error occurs with the connected device, bypass operation is performed and commercial power supply is supplied as is to the con- nected devices.
When in use, make sure the output terminal block cover is attached. Do not turn ON the power switch when it is detached. ●Voltage is applied to the output terminal block when the power switch is ON, which can result in electric shock.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installer near the equipment and shall be easily accessible.

Do not connect the AC input plug of the unit to its Power Supply Output Receptacle during the Battery Mode. ●The unit may fail.
Check system operation beforehand if the unit is used in combination with a device whose power supply frequency fluctuates widely, such as a personal electric generator. ●The unit automatically recognizes the input power frequency when input power is supplied.If the unit is connected when the input power frequency is not stable at the rated level, the unit may misidentify the power supply frequency and may fail to operate normally. (If the unit is in operation, changing from commer- cial power supply to another power supply source, such as generating equipment, will cause no problem. Set the generator's frequency to the same level as that of the commercial power supply.)
Do not install or store the unit in a place exposed to direct sunlight. ●The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Before stopping the commercial power to the unit, turn OFF the power switch of the unit. ●The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery Mode, the battery life may be significantly shortened.
Check the operation beforehand if the unit is used in any mode other than “Output 200V mode”. ●In Battery Mode, the maximum voltage (peak voltage) of output (rectangular wave) may be lower than the maximum voltage in Commercial Power Mode. For this reason, some connected devices may fail to oper- ate normally.
If this unit is used with an inductive device such as a coil or motor, check the operation beforehand. ●With some types of devices, the effect of inrush current may cause this unit to stop operating properly.

This section describes how to install the UPS. Do not use this unit in any position other than the “correct positions” indicated in the illustration below.


Be careful not to get your fingers caught when arranging the unit.
* The feet can also be anchored to the floor with screws if you use BUP100S mounting brackets (sold separately).
Refer to the BUP100S instruction manual for more details.


Be careful not to get your fingers caught when arranging the unit.
Caster at the bottom may be removed when sitting horizontally.

Casters locked Casters unlocked

Use a monkey wrench or spanner to loosen the fixed stand nuts. Unscrew the feet of the fixed stand until they reach the floor. Continue to unscrew the feet of the fixed stand until the casters no longer touch the floor.

Once the fixed stand feet are firmly on the floor, turn the nuts counter-clockwise to tighten them and lock the feet in place.
* The feet can be anchored to the floor with screws if you use BUP300S mounting brackets (sold sepa- rately). Refer to the BUP300S instruction manual for more details.
Install the BU3002SW so that the control panel is facing upward. Loosen the screws in the 6 locations shown in the diagram below. Remove caster mounting plate.


* BUP300S mounting brackets (sold separately) can be used for easy mounting on an EIA/JIS 19-inch rack. Refer to the BUP300S instruction manual for more details.


When in use, make sure the output terminal block cover is attached. Do not turn ON the power switch when it is detached. ●Voltage is applied to the output terminal block when the power switch is ON, which can result in electric shock.
This function can be used with the UPS monitoring software included with the UPS. The output receptacles of the BU1002SW are separated into 3 groups: A, B, and C.
output group A, so they can be delayed or set to precede the output stop time. • The output start/stop time control funtion is available when using the included “PowerAct Pro” UPS
monitoring software, “UPS Power Manager” or “SNMP/Web card”. • Output ON/OFF can be controlled with the included UPS monitoring software while the BU1002SW is
operating. • The delay settings and ON/OFF control described here can be performed independently for power
supply output group B and power supply output group C. This function can be used to set the startup order of servers, peripheral devices, etc.
The output receptacles can also be forcibly turned ON/OFF remotely.


2-3-1 Connecting a device to the power supply output (BU1002SW) (1) Connect devices that require backup to the unit's power supply output receptacle or output terminal block.
Make sure that the total capacity of the devices connected to the output receptacle does not exceed the output rated capacity of the BU1002SW. If the overload indication ( ) is dis- played, reduce the number of connected devices.

“Power supply output” group Output receptacle Output terminal block Group A C13: 1 (Rated capacity: 15A) –

Group C

When in use, make sure the output terminal block cover is attached. Do not turn ON the power switch when it is detached. ●Voltage is applied to the output terminal block when the power switch is ON, which can result in electric shock.
emergency stop switch (ESD)
(1) Remove the terminal block cover on the lower right side of the
unit’s rear panel. (2) Connect the units that need to be backed up. Two types of connec-
tions can be made. 1) To turn ON/OFF at the same timing as that of output receptacle B:
L1B terminal: Connect the line L2B terminal: Connect the neutral line 2) To turn ON/OFF at the same timing as that of output receptacle C:
L1C terminal: Connect the line L2C terminal: Connect the neutral line Run the wires to be connected through the hole in the included terminal block cover (with cable clamp and cable guard tube). (See Figure 1.) If you have trouble running the wire through the hole, loosen the cable clamp dial by turning it counter-clockwise. Connect the ground wire to the G terminal. Use a flat head screwdriver to loosen the terminal block screws, insert the wire, and then retighten the screws. (See Figure 2.) Refer to Table 1 for wire sizes.
Table 1 Connectable wire size 1.0 to 2.5 mm2
Amount of stripped wire 5.5mm
Tightening torque 0.9Nm(8 lb-in) Recommended cable size 2mm2 (AWG14)
(3) Insert the tab on the right side of the terminal block cover (with cable clamp)
into the unit’s body, and fasten the previously removed screws to the two loca- tions on the left side of the cover. Tighten the cable clamp dial to stabilize the wire. (See Figure 2.)
UPS Load

(2) When using the included UPS monitoring software and the Windows standard UPS service, use a connec-
tion cable to connect the unit to the PC.
See also "7. Using the UPS monitoring software and Contact Signal" on page 65 * If you do not use the UPS monitoring software and Contact Signal, this step is not required.
(3) When the installation and connection is complete, connect the AC Input Plug of the UPS to a wall outlet
(commercial power).


Connect the ground wire to the Grounding terminal.


When one wire is used to ground the AC input power supply, make sure to use this unit's N terminal (phase) side as the ground. ●A misconnection may result in malfunction.
Input plug (L6-15P) · (Front view)

2-3-2 Connecting a device to the power supply output (BU3002SW) (1) Connect devices that require backup to the unit's power supply output receptacle or output terminal block.
Make sure that the total capacity of the devices connected to the output receptacle does not exceed the output rated capacity of the BU3002SW. If the overload indication ( ) is dis- played, reduce the number of connected devices.

“Power supply output” group Output receptacle Output terminal block Group A C19: 1 (Rated capacity: 20A) 1 line (Rated capacity: 20A)


Caution
emergency stop switch (ESD)
(1) Remove the terminal block cover on the lower right side of the unit’s
rear panel.
(2) Remove the transparent cover.
(3) Connect the units that need to be backed up.
Two-line connection can be made.
(4) Run the wires to be connected through the hole in the included terminal block cover (with cable
clamp and cable guard tube). (See Figure 1.)
Connect the ground wire to the G terminal.
Use a Phillips screwdriver to remove the terminal block screws, and connect the wire attached to the round pressure terminal. (See Figure 2.)
Refer to Table 1 for round pressure terminal sizes.
Figure 1 Table 1
Diameter of screw M5 Screw Tightening torque 2 Nm(17.7 lb-in)
(5) Cover the terminal block with terminal block cover (with cable clamp) , and fasten the previously
removed screws to the two locations on the upper side of the cover.
Tighten the cable clamp dial to stabilize the wire.(See Figure 3.)
UPS Load

(2) When using the included UPS monitoring software and the Windows standard UPS service, use a connec-
tion cable to connect the unit to the PC.
See also "7. Using the UPS monitoring software and Contact Signal" on page 65 * If you do not use the UPS monitoring software and Contact Signal, this step is not required.
(3) When the installation and connection is complete, connect the AC Input Plug of the UPS to a wall outlet
(commercial power).


Connect the ground wire to the Grounding terminal.


When one wire is used to ground the AC input power supply, make sure to use this unit's N terminal (phase) side as the ground. ●A misconnection may result in malfunction.
Input plug (L6-20P) · (Front view)

After you finish connecting devices to the unit, make sure the backup function operates properly.
Check that the Battery Mode is performed normally according to the following procedure.
(This operation check simulates a power failure by disconnecting the AC input plug from a wall outlet.)
(1) Turn ON the unit's power switch.
The beeper sounds and the current settings are displayed on the LED.
After 5 secounds, the self-diagnostic test is performed in Battery Mode for approximately 10 seconds.
When the self-diagnostic test finishes successfully, switching to AC output from commercial power is per- formed and the the display below is shown.
(If the battery voltage is low, the self-diagnostic test is not performed and the operation starts immediately, using output from commercial power.)

ON OFF ON, OFF, or blinking depending on status
(Including devices connected to the AC outlet of your PC.)
Operate the devices in a way in which abrupt power stop does not damage the connected devices, data, etc.
(3) Under this condition, check the the unit's LED display and beep sound.
Are they in the same status as shown below?
If the same as the one shown above: ➜The operation is normal. Proceed to (4). If not the same as the one shown above: ➜The operation is abnormal. One of the cases described in "4. Dis-
play and beeps when there is an equipment failure" of "3-3 Inter- preting a beep and displays" on page 39 must apply. Take necessary measures and then proceed to (4).
(4) Disconnect the AC input plug of this unit from a wall outlet (commercial power).
The UPS enters Battery Mode.

(5) In Battery Mode, check the unit's LED display and beep sound.
Does the status indicator appear as one of those shown below?
Backup is operating due to power failure or AC input error. Output will stop if Battery Mode continues.
OFF
(Same as above.) Battery level is low, so output will stop soon.
OFF
Battery is dead, so output stopped. (This is displayed only for a few seconds.)
If not the same as one of those shown above: ➜Operation is abnormal. Check the status of lamps and beep and
turn OFF the Power Switch.
After connecting the AC input plug to a wall outlet (commercial power) and waiting at least 8 hours for the battery to charge (24 hours when an additional battery unit is connected), go back to (4) on page 31.
See also Setting switch 1 can be used to turn the beeper ON/OFF. ➛ Page 43
(6) Connect the AC input plug to a wall outlet (commercial power) again.
The status indicator returns to its normal state and the beeping sound stops. (The status is as shown below.)
Power switch “ON” Operating normally
Checking the operation is now complete.
Installation and connection is now complete.

When you connect the AC input plug of this unit to a wall outlet (commercial power), the battery charg- ing automatically starts regardless of whether the power switch is ON or OFF, and it is fully charged within 8 hours. (When an additional battery unit is connected, the charging time is 24 hours.)
See also "5. Measuring the backup time" → Page 51
The battery is discharged completely when the backup time is measured, so you need to recharge it before using the UPS.
See also Charge the battery as described in "2-5 Charging the battery."
Preparation for starting operation is now complete.

3-1 Precautions and notes for operation
Caution (for use)
When the battery is dead, replace it immediately or stop using the unit.
4 to 5 years 2 to 2.5 years
* The values in the table are the expected life under standard use conditions and are not guaranteed.
Using a dry cloth, periodically wipe the dust from the AC input plug, power supply output receptacles and output terminal block. ●Accumulated dust may cause a fire.
Do not use the unit in a closed place and do not cover the unit. ●Doing so may cause abnormal heating or a fire.
Do not place objects on the unit that are 25 kg or heavier, and do not drop metal objects onto the unit. ●Doing so may cause distortion/damage to the case or a failure of the internal circuit, which may cause a fire.
Ambient temperature · Expected life

Take measures for handling unforeseen accidents, such as data backup and system redundancy. ● The output may stop when there is a circuit failure in the UPS.
Quitting Battery Mode ●If a power failure lasts for an extended period of time, the battery discharges and power output from the unit stops. Shut down your computer after performing appropriate procedures (for example, saving data) while the unit is still supplying power.
Rebooting ●If the battery discharges completely during a power failure, the unit stops. After recovery from the power failure, the unit automatically restarts and supplies power. If you do not want to restart the connected de- vices, turn OFF the power switch of either the unit or the connected devices.
See also Setting switch 2 can be used to select whether or not auto restart is performed. See Page 43
Scheduled operation using the UPS monitoring software ●When performing scheduled operation in which the UPS is stopped and a device such as a breaker is used to stop the UPS at the same time that commercial power stops, specify a period of no more than 3 months for the start of the next operation. If you specify a period longer than 3 months, the internal timer is reset and the scheduled operation does not start. Note that this period reduces to approximately half when the battery is dead. If a period of 3 months is exceeded, you start operation by supplying commercial power and pressing the start switch. However, if the battery is dead, you may not be able to start operation. In this case, replace the battery according to the instructions in “6-2 Replacing the battery” on page 54.

Operation Turn on the power switch of the UPS.
Power supply output receptacles
Outputs power (connected devices are powered)
See also Cold start ON/OFF setting ➛ Page 49
OFF
7 seg.
ON
OFF
Power supply output lamp
OFF
ON
OFF
about 10 sec. about 10 sec. about 2 to 3 sec.
1 sec.
D-1 : The most recently displayed error code (refer to item 4 on page 34) (If no errors have occurred, " " is displayed.)

See also Setting switch 1 can be used to turn the beeper ON/OFF. ➛ Page 43
Battery replacement Beep Output Charging Description Solution
Perform shutdown operations for the connected devices and stop them.
In Battery Mode due to power failure or AC power error.
(Same as above.) Battery level is low, so output will stop soon. (Same as above.)
Battery is dead, so output stopped. (This is displayed only for a few seconds.) Charge the battery.

See also Setting switch 2 can be used to select whether or not auto restart is performed. See Page 43
Operation Turn ON the power switch of the UPS.
Battery replacement Beep Output Charging Description
None ON OFF There is AC input Power switch “OFF”
BU1002SW: Displayed in 3 levels, with 1000VA/700W as 100%. BU3002SW: Displayed in 3 levels, with 3000VA/2100W as 100%.
When the power consumption of connected devices is 30% or less, the level meter turns OFF.
In Battery Mode, the battery level is displayed as a percentage.
Indicator is ON In Battery Mode Battery level Indicator blinks
In Commercial Power Mode Connection capacity Indicator is ON
90% lamp 90% or more 60% or more 60% lamp 60% or more 30 to 60% 30% lamp 30% or more 0 to 30% All OFF 30% or less —
Connection capacity Battery level
* In Commercial Power Mode (normal operation), the battery level is displayed when the beeper stop/ test switch is pressed.
(Please note that if the button is pressed and held for 5 seconds or more, the beeper begins to sound
and the self-diagnostic test starts.)
Status indicator

( indicates blinking) ( indicates the display is ON) ( indicates the display is OFF) ○ ●

Self-diagnostic test in progress.
OFF Auto battery test in progress.

In Battery Mode due to power failure or AC input error. Output will stop if Battery Mode continues.
Perform shutdown operations for the connected devices and stop them.
(Same as above.) Battery level is low, so output will soon stop.
Battery is dead, so output stopped. (This is displayed only for a few seconds.)
AC input voltage is too high (over). AC input frequency is too high (over).
Use within the AC input voltage/ frequency range described in the specifications. → See Page 88
AC input voltage is too low (under). AC input frequency is too low (under).
There are too many connected devices and the rated capacity is exceeded. If this state continues for as long as or longer than the times described below, commercial power continues to be supplied through bypass operation (Note 1). ・When connection capacity is at 100% or higher: Bypass operation begins after 10 seconds ・When connection capacity is at 120% or higher: Output stops after 1 minute (Go to No.12) ・When connection capacity is at 140% or higher: Output stops after 10 seconds (Go to No.12)
Intermittent 0.5-second intervals
Reduce the number of connected devices until the display appears as in status No. 3.
Turn OFF the power switches of all devices connected to the unit, reduce the number of connected devices, and turn the power switch back ON again.
or discharging ○ ○ ○
Output stopped due to exceeded connection capacity.

Beep Charging Description Solution Bypass operation
No. Status indicator
Check that the AC input of connected devices is not short-circuited.
Output stopped due to output short-circuit.
Replace the external cooling fan.
Moved to bypass operation due to problem with the external cooling fan (Note 1).
“Replacing the fan” Page 62
The fan can be replaced via the rear panel without stopping this unit. Use replacement fan sold separately. (Note 2)
Turn OFF this unit and all connected devices. Then, turn the power switch back ON for this unit only. If the display does not change, there is a problem with this unit. Contact the shop of purchase or our peripheral device customer support center at:
Failure occurred. When the beep stop switch is pressed, the details of the error are displayed (Nos. 16 to 23).
―― ―― (Note 3)
Moved to bypass operation due to output voltage error (over) (Note 1).
Displays the details of the error that occurred only while pressing the beep stop switch while in state No. 15.
Moved to bypass operation due to output voltage error (under) (Note 1).
(Same as above.)
Moved to Battery Mode due to battery charge voltage error (over). Output will stop when the battery is dead.
(Same as above.)
Output stopped because the output of the battery charge voltage short-circuited.
○ ○ ○ 19 ―― (Same as above.)
Moved to bypass operation due to problem with the internal temperature (Note 1).
Moved to bypass operation due to bypass bus voltage error (Note 1).
(1) Output stopped due to system error. (2) Other error occurred.
○ 22 ―― (Same as above.)
Replace the battery. You can replace the weak battery with a separately purchased replacement battery as needed.
23 ● ○ The battery test detected a weak battery (warning only, output continues).

4-1 Suspending a beep
When the beep is sounding, you can suspend it by pressing and holding the beep stop/test switch for 0.5 seconds or longer.
バッテリ
増設
- バッテリ
バイパス
運転
交換
4-2 Self-diagnosis test
This test performs a failure diagnosis on the unit and performs a simple test to check for battery deterioration.
Use the procedure below to check whether a circuit failure has occurred inside the unit and whether battery replacement is required.
If the battery is not fully charged, the self-diagnostic test is not executed immediately.
After charging is complete, it is automatically executed.
(1) Connect your computer and other devices to the UPS and then turn ON the power switch of the UPS.
(2) The Battery Mode starts for testing purpose automatically (Status indicator “ ”). (No beep sounds.) After about 10 seconds, when the test is complete the normal operation automatically starts.
(3) If the status indicator/battery replacement lamp blinks and the beeper sounds:
See also "3-3 Interpreting beeps and displays" ➛ Page 39
Follow the directions for the solutions described in “4. Displays and beeps when there is an equipment failure” and “5. Display and beep for battery replacement”.
* This test can also be run from the included UPS monitoring software. For more details, refer to the online help for the UPS monitoring software.
This test can also be performed manually.
バッテリ
Press and hold the Beep Stop/Test Switch of the UPS for 5 second or longer.
- バッテリ
When the beeper begins to sound intermittently, release the Switch.
運転
交換

This test performs a failure diagnosis on the unit and performs a test to check for battery deterioration.
(This test is more accurate than the self-diagnostic test.)
This test is performed automatically. (You do not have to perform any special operations.)
The test is performed at intervals of 4 weeks after the AC Input Plug is connected to a wall outlet (commercial power).
The test is not performed if the power switch is OFF or if the battery is not fully charged.
(1) When the auto battery test starts, the Battery Mode automatically starts (Status indicator “ ”). (No beep sounds.) After the auto battery test is complete, the normal operation automatically starts.
(2) If the status indicator/battery replacement lamp blinks and the beeper sounds:
See also "3-3 Interpreting beeps and displays" ➛ Page 39
Follow the directions for the solutions described in “4. Displays and beeps when there is an equipment failure” and “5. Display and beep for battery replacement”.
The setting switch on the Front of the UPS allows you to select the "disable the auto battery test" setting.
See also "4-4 Changing the setting of the functions" ➛ Page 42 See "Setting for whether or not to perform battery test"
This test can also be performed manually.
Press and hold the Beep Stop/Test Switch of the UPS for 10 second or longer.
When the beeper changes from intermittent beeps to a sustained beep, release the switch.
Caution
After changing the setting switch, disconnect the AC input plug, wait until the status indicator is completely OFF, and then reinsert the AC input plug.
1 2 5 6 7 8 3 4
ブザー停止/テスト 電源出力
バッテリ
増設
- バッテリ
バイパス
運転
交換

Setting switch function list
No.
OFF side ON side
Setting for beeper sound in the event of power failure, etc.
Beeper does not sound
Auto startup setting after recovery from power failure
Do not perform auto startup
Setting for whether or not to perform battery test
Do not perform test
Auto startup mode setting
Valid only during Battery Mode
BS signal valid range setting
* In the factory settings, everything is OFF.
1 2 5 6 7 8 3 4
OFF: The beeper sounds when an alarm is necessary.
ON: The beeper does not sound for backup operation or battery replacement. The beeper sounds for other errors (connection capacity exceeded, operation error, etc.).
1 2 5 3 4 8 6 7
OFF: Automatically starts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or contact signal(BS signal), the unit automatically starts and begins to output when the commercial power is restored.
ON: Does not automatically start when power is restored.
After the unit is shut down with the UPS monitoring software or contact signal (BS signal), it does not start up when commercial power is restored. Startup is performed by turning the power switch OFF once, and then back ON again.

1 2 5 3 4 8 6 7
OFF: The battery test is automatically executed once every 4 weeks.
ON: Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
1 2 5 3 4 8 6 7
OFF: (Mode A) After UPS stopped, the UPS is automatically started immediately when “ON” is detected for the AC input.
ON: (Mode B) After UPS stopped, the UPS is automatically started in the AC input’s “OFF to ON” timing that is detected.
* Setting switch 4 is valid when the auto startup after recovery from power failure setting (setting switch 2) is set to OFF (auto restart is performed).
* This setting mode is valid only after the UPS has been stopped by the contact signal backup stop signal (BS).
* When a cable is connected to the RS-232C connector and the UPS monitoring software is used, the unit operates in Mode A regardless of this setting.

(1) When BS signal is used to stop the UPS after a power failure occurs
(1)-1.
OFF
ON
OFF
Power output (Setting switch 4 OFF: Mode A)
OFF
Power output (Setting switch 4 ON: Mode B)
OFF
(2) When BS signal is used to shut down the UPS when AC input is ON
OFF
ON
Starts up when BS signal turns OFF
Power output (Setting switch 4 OFF: Mode A)
OFF
Starts up when AC input turns from OFF to ON
Power output (Setting switch 4 ON: Mode B)
OFF
* 1: BS signal reception time corresponds to the setting switch 7.

1 2 5 3 4 8 6 7
OFF: The BS signal is always valid (receivable).
The unit’s “power output ” can be stopped by inputting a “ON” backup power supply stop signal (BS) that continues for 10 seconds or more.
ON: The BS signal is valid (receivable) only when in Battery Mode. (The signal is not received when in Commercial Power Mode.) The unit’s “power output ” can be stopped by inputting a “ON” backup power supply stop signal (BS) that continues for 0.01 (10 ms) seconds or more.
Use this setting in commercial operation when you do not want to stop operations when a backup power supply stop signal (BS) is received.
Auto startup when power is restored is associated with setting switch 2.
However, the unit does not start up when the BS signal is ON.
OFF
Battery Mode Operationg Mode
OFF
10 sec 10 sec
Power supply output (Setting switch OFF)
OFF
0.01 sec
Power supply output (Setting switch ON)
OFF

2-1 Settable items and explanations
There are 4 items to select.
The settings available for this operation are shown below.
The unit can start up only when there is AC input.
It is possible to start up the unit even when there is no AC input plug. (It is not possible, however, to start up the unit by the remote signals.) Normal operation occurs when AC input is ON. The output frequency is the same as the frequency the last time there was AC input. 2) Output voltage setting (200V/220V/230V/240V) Four types of output voltage can be set. (Setting range: 200V/220V/230V/240V) Output is performed at the set voltage, with no relation to the input voltage.

ON
OFF
ON
OFF
Power output stop delay time This timing is 10 ms or 10 sec. Timing corresponds to the settings for switch 7 .
See also ➛ Page 46
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is “High”, the UPS stops the output immediately.

Signal input/output test end
Signal input test While the signal is being input, the status indicator blinks and the beep sounds.
Signal input/output test start
Signal output test Contact signal is forced to turn ON.
Battery Low signal (BL) (Between pins 1 and 5)
ON
Output signal Input signal
Trouble signal (TR) (Between pins 2 and 5)
ON
Backup signal (BU) (Between pins 8 and 5)
ON
Deteriorated battery signal (WB) (Between pins 9 and 5)
ON
Backup power supply stop signal (BS) (Between pins 3 and 5)
ON
Remote ON/OFF signal (Between pins 6 and 7)
ON
OFF
While the signal is being input, these status indications blink and the beep sounds.
Beep

The UPS operation mode can be set if the power switch is turned ON while the beeper stop switch is pressed.
バッテリ
増設
- バッテリ
バイパス
運転
交換
(1) When the beeper stop switch is briefly pressed (for less than 1 second), the next item is displayed.
Cold start ON/OFF setting
Power supply output stop delay time setting
(2) The unit enters the “individual item setting mode” when the beeper stop switch is pressed and held
(for more than 1 second).
(3) When the power switch is turned OFF, the setting mode quits and the unit enters power switch OFF
status (status No.2).
2-2 Settings · Output voltage setting · Signal input/output test


There is AC input Power switch “OFF” (Status No. 2) B C D
A Turn ON the power switch while the beep stop/test switch is pressed. Turn OFF the power switch. Press and hold the beep stop/test switch (for more than 3 seconds). Press the beep stop/test switch (for less than 3 seconds).

Caution
(1) When the AC input plug is connected to a wall outlet (commercial power), the battery automatically starts
charging, taking up to 8 hours to complete (24 hours when an additional battery unit is connected).
(2) Turn ON all devices connected to the power output to be “backed up during a power failure”.
(This includes devices connected to the AC outlet of your computer.) Operate the connected devices in a way that allows the power supply to be stopped at any time.
Perform measurement while the hard drive is stopped.
Choose "Shut Down" in Windows and follow the procedure below to shut down your OS.
Choose "Restart in MS-DOS mode" to exit from OS and display the MS-DOS mode screen.
(3) Disconnect the AC Input Plug of the UPS and measure the backup time.
Measure the time until the unit automatically stops and all displays disappear with the plug disconnected.
* The backup time you measure for the first time after purchase is the "initial value of the backup time."
The backup time varies depending on the capacity of connected devices. After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the backup time. (This is also applied to checking the battery.) (1) Convert the total capacity (power consumption) of the connected devices to watts (W).
For the indication of connected devices, check your computer and the rear of the display. The indicator can show values in three different ways: volt-amperes (VA), amperes (A), and watts (W).
Example 1) 200 VAC, 50/60Hz, 145 W
Example 2) 200 VAC, 50/60Hz, 1.8 A
VA × power factor = W
Example 3) 200 VAC, 50/60Hz, 150 VA
A × power factor × 200 = W
For devices that use the VA or A indication, convert the capacity into W. Multiply the value indicated on devices by the value in the right table for conversion.
(When the power factor is unknown, enter “1”. The power factor usually ranges between 0.6 and 1.)
(2) Add the values converted into W to obtain the total capacity of the connected devices.
Indication Value

(3) Calculate the initial value of the backup time for the total capacity of the connected devices from the graph
below.
Backup time (20°C, initial value)
BU1002SW + BUM100S
BU3002SW
BU1002SW
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
Power consumption of connected devices(W)
Model 20W 50W 100W 200W 300W 400W 500W 700W 1000W 1400W
BU1002SW 180 120 60 35 20 15 10 5 - -
720 420 240 120 80 60 50 30 - - BU1002SW+ BUM100S
Model 200W 400W 600W 800W 1000W 1200W 1400W 1600W 1800W 2000W 2100W
BU3002SW 92 46 30 20 15 12 10 8 7 5.5 5
BU3002SW 340 175 115 85 62 49 43 37 31 26 24 + BUM300S
* These backup times are for reference only. Times may vary according to battery life and external environmental conditions (temperature, etc.).
(Minutes)

Caution (for maintenance)
When maintaining the connected equipment, turn OFF the power switch and disconnect the AC input plug. ●Even if you disconnect the AC input plug while the UPS is operating, the power output of this unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit. ●Doing so may cause an electric shock or a fire.
Do not throw the unit into fire. ●The lead battery in the unit may explode, or leak dilute sulfuric acid.
Do not insert metal objects into the power supply output receptacles of the UPS. ●Doing so may result in electric shock.
Do not insert metal objects into the battery connectors. ●Doing so may result in electric shock.
The sealed lead battery used in the unit has a limited life. (The life varies depending on your storage/use environment and backup frequency.) The nearer the end of the life is, the more rapidly deterioration proceeds.
20 ° C 30 ° C
4 to 5 years 2 to 2.5 years
4 to 5 years after staring use 2 years after staring use
See also Measure the backup time according to "5-1 How to measure backup time" ➛ Page 51
If the measured value is equal to the "initial value of the backup time" or less than half the value obtained from the graph of "Estimated backup time" on page 46, replace the battery.
Replacement estimation · Ambient temperature · Life of battery

Check once every 6 months
Check once a month When 3 or more years have passed since purchase When 1.5 or more years have passed since purchase
For the first 3 years after purchase
For the first 1.5 years after purchase
* The battery deteriorates even if it is stored. The higher the temperature is, the shorter the life becomes.
The battery can be replaced while the unit is stopped (power supply output stopped).
When the unit is used in compliance with UL standards or CE marking, do not replace the battery while in operation (while power is being output). Replacing the battery while in operation does not comply with UL standards or CE marking. Make sure to stop the operation of the unit before replacing the battery.
* When replacing the battery, stop the connected devices, turn OFF the power switch of the UPS, and disconnect the AC input plug from the wall. * If an input power supply error such as a power failure occurs when replacing the battery while in opera- tion, backup cannot be performed and output stops. * Do not replace the battery during backup operation. Output will stop.
Do not replace the battery in a place where there is flammable gas. ●Spark may occur when connecting the battery, which may cause an explosion or fire.
Do not disassemble or modify the battery. ●Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery and do not expose it to strong impact. ●Dilute sulfuric acid may leak.
Do not short the battery with metal objects.
Ambient temperature


Do not put the battery into fire and do not break it. ●The battery may explode or leak dilute sulfuric acid.
Do not use a new battery and an old battery at the same time. ●Dilute sulfuric acid may leak.

<BU1002SW> 1. Use a screwdriver to loosen (turn clockwise) the 2 screws at the top of the front panel of the unit, until they turn freely. (The screws cannot be removed from the front panel.) ➀ Pull the front panel towards you to remove it. ➁


Pull the plate cover towards you ➁ and lift it up to remove it. ➂
Remove the 2 screws.

Do not hold the connector or cable of the battery pack.
Use the red tape on the top of the battery pack, which is 10 cm from the inner edge of the battery, to gauge how much further you need to pull the battery to remove it. Hold the battery securely with both hands so as not to drop it.

Pullout label (Pull this to remove.)

For BU1002SW: Model BP100XS Attach the plate cover.
Insert the lug at the bottom of the cover into the hole in the main body ➁ and push it towards the main body. ➂
Use a screwdriver to securely tighten (clockwise) the 2 screws you removed. √
Do not pinch the cable with the plate cover.

Secure the connector to the plate cover. ➁

You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this sound is not abnormal.
Secure the connector by the 3 supports on the plate cover.

If you cannot secure the connector to the plate cover, the connector is not inserted completely. Insert the connector again.

Insert the lug at the bottom of the front panel into the hole in the main body ➀ and push it towards the main body. ➁
Use a screwdriver to securely tighten (clockwise) the 2 screws at the top of the front panel. ➂
Tighten the 2 screws.

バイパス
運転
- バッテリ
バッテリ
交換
増設
Battery replacement is now complete.
<BU3002SW> 1. Use a screwdriver to loosen (anti-clockwise rotation) the 4screws on the front panel of the unit, until they turn freely. (The screws cannot be removed from the front panel.) Pull the front panel towards you to remove it. ➀




While pulling the plate cover toward you ➁, lift it up and remove the lower battery connector from the eyehole.

Remove the upper and lower sections one by one.
Do not hold the connector or cable of the battery pack.
Use the red tape on the top of the battery pack, which is 10 cm from the inner edge of the battery, to gauge how much further you need to pull the battery to remove it. Hold the battery securely with both hands so as not to drop it.


Pullout label (Pull this to remove.)

For BU3002SW: Model number BP150XS (two required) Run the top portion of the lower battery connector through the square hole in the plate cover. ➁
Insert the lug at the bottom of the cover into the hole in the main body and push it towards the main body.
Use a screwdriver to securely tighten (clockwise) the 2 screws you removed.➂
Do not pinch the cable with the plate cover.

Secure the connector to the plate cover. ➁

You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this sound is not abnormal.
Secure the connector by the 2 supports on the plate cover.

If you cannot secure the connector to the plate cover, the connector is not inserted completely. Insert the connector again.

Push the front panel toward the main body. ➀
Use a screwdriver to securely tighten (clockwise) the 4 screws on the front panel.➁
4 screws.

Battery replacement is now complete.
If the battery replacement indicator is displayed and the beeper sounds before replacement, press the beeper stop/test button once to stop the beeper, and hold it for 5 sec. to perform a self-diagnostic test. The beeper stops and normal operation resumes after the 10-second test is complete.
Connect the AC input plug to a wall outlet (commercial power) and turn ON the power switch of the UPS. When operation starts, the self-diagnostic test is automatically performed. Normal operation resumes after the 10-second test.
Write the usage start date on the label on the front. Also, by using the included UPS monitor- ing software, possible to keep a record of usage start date by the software.
Tighten the

The fan in the unit has an expected lifespan of approximately 5 years. Replace it when the Error Lamp is lit and the fan is stopped.
When this product is used in compliance with UL standards or CE marking, do not replace the fan.
The fan can be replaced while the unit is in operation (power supply is being output) or while the unit is stopped (power supply output is stopped). Choose whichever replacement method is more convenient.
* If the fan stops or is removed while the unit is in operation, the “EF” lamp blinks, the beep sounds continu- ously, and output is supplied through bypass operation. In this state, if an input power supply error occurs due to a power failure or other reason, the unit stops without entering Battery Mode. * Do not replace the fan while in Battery Mode. The unit will stop.

Do not insert your hand or metal objects into the fan recess. • Doing so may cause electric shock or short-circuit.
Detect abnormally working fans.
(Not rotating, abnormal noise, vibrating, the fan contacting the cover, etc)
BU3002SW Front view (after removing the front panel)


BU1002SW Rear view · BU1002SW Rear view

Pull the cooling fan toward you to remove it. ➁

1 Loosen the 3 screws.
* Different screw locations for BU3002SW front fan.
The beep stops, and the error lamp turns OFF.

The beep stops, and the "EF" status display lamp turns OFF.
Use a screwdriver to securely tighten (turn clockwise) the 3 removed screws. ➁ When doing so, make sure the cable does not become pinned under the fan cover.
Fan replacement is complete.
Fan recess · Fan

Do not use chemicals such as thinner and benzene. (They cause deformation or discoloration.)
Then, remove dust with a dry cloth and make the connection again.
(For information on the connection procedure:)
See also "2-3 Connecting the equipment" ➛ Page 24

7.Using the UPS monitoring software and contact signal
* If you do not use the UPS monitoring software and contact signal, this step is not required.
“PowerAct Pro (for Windows/Linux)” , “UPS service driver” and “UPS Power Manager (Mac)” UPS monitor- ing software is included with this product. Refer to the table below for details about compatibility. Choose which one to use based on the application. Refer to the table below for details about compatibility. For further details about the software functions, refer to the separate "UPS Monitoring Software Quick Installa- tion Guide."
Model OS Communication method
Windows server2003 Serial ⇒See 7-1
PowerAct Pro (Note 1)
x64 Edition (RS232C or USB 1.1) ⇒See 7-2 Windows XP/2000 x64 Edition Contact signal (Note 2) (Note 4) ⇒See 7-3 LAN ⇒See 8-1
UPS service (OS standard) + UPS service driver (included software) UPS service (OS standard) Shutdown software for SNMP/web card PowerAct Pro (Note 1) UPS service (OS standard) + UPS service driver (included software) UPS service (OS standard) Shutdown software for SNMP/web card UPS service (OS standard) Shutdown software for SNMP/web card
Serial ⇒See 7-1
(RS232C or USB 1.1)
Contact signal (Note 2) (Note 4) ⇒See 7-3 LAN ⇒See 8-1
BU1002SW BU3002SW
Windows NT 4.0 Contact signal (Note 2) (Note 3) ⇒See 7-3 LAN ⇒See 8-1
⇒See 7-1 (RS232C or USB 1.1)
PowerAct Pro (Note 1)
LAN ⇒See 8-1
Shutdown software for SNMP/web card
Serial ⇒See 7-1 (RS232C or USB 1.1) LAN ⇒See 8-1 Mac OS X (10.3、10.4) Serial (USB1.1) ⇒See 7-1 Mac OS X Server (10.3, 10.4) (Note 5) LAN ⇒See 8-1
PowerAct Pro (Note 1)
Shutdown software for SNMP/web card
Shutdown software for SNMP/web card
Note 1: The most recent version can be downloaded from our homepage (http://www.omron.co.jp/ped-j/download/ups_soft/). Note 2: Files cannot be automatically saved. Note 3: To automatically stop the UPS, it may be necessary to change the PC’s BIOS settings. Change the PC’s BIOS settings so that the PC’s power supply is not cut after OS shutdown is performed. Note 4: The UPS automatically stops once the battery is depleted. Note 5: Compatible only with Macintosh computers equipped with PowerPC CPU.

7.Using the UPS monitoring software and contact signal
General applications (Simple functions, standalone)
UPS service PowerAct Pro SNMP/Web
card UPS Power Manager (Mac)
Required options Connection cable
Windows Server 2003 x64 Edition Windows XP x64 Edition Windows Server 2003 Windows XP/2000 Windows NT4.0 Windows Me/98 Linux (Note 4) Mac OS X v10.4/Server v10.4 Mac OS X v10.3/Server v10.3 (Note 5) Auto shutdown UPS monitoring (operating status) UPS monitoring (data) Pop-up notification End when OS is inactive (Note 3) Auto file save (Note 3) Schedule operation UPS setting change External command execution Event log save Data log save Coordinated shutdown (shutdown of multiple units) Output receptacle control Redundant power supply support Remote UPS management Mail send SNMP management Telnet connection SYSLOG support
Compatible OS Software function
Note 1: The UPS stops automatically only when the battery is depleted. (Battery Mode continues until the battery is depleted.) Note 2: Only the battery capacity can be monitored. Note 3: This function can be used with Windows only. It cannot be used with Linux. Note 4: For the latest information, check our website at: http://www.omron.co.jp/ped-j/product/soft/index.htm Note 5: Compatible only with Macintosh computers equipped with PowerPC CPU.
[Explanation of software functions] 1 Auto shutdown The computer can be shut down automatically when a problem occurs with the power supply. 2 UPS monitoring (operating status) The operating status of the UPS can be monitored (in Commercial Power Mode/Battery Mode). 3 UPS monitoring (data) Monitoring can be performed for input voltage value, connection capacity, battery capacity, etc. 4 Pop-up notification When a problem such as a power failure occurs, a pop-up window that shows the details of the problem can be displayed. 5 Shutdown when OS is inactive Shutdown can be performed when the computer is in an inactive state. The operating status is retained at shutdown in inactive state, so operation details are not lost. 6 Auto file save Files such as open Word and Excel documents are automatically saved at shutdown. 7 Schedule operation Schedule settings can be made for UPS stop/start. 8 UPS setting change UPS settings (beep ON/OFF, etc.) can be changed. (Items that can be set vary according to the UPS.) 9 External command execution By executing commands at shutdown, items such as application programs can be launched. 10 Event log save Information of events that occur on the UPS (power supply problems, setting changes, occurrences of failure, etc.) are saved as a log. 11 Data log save Data of input/output voltage value, connection capacity, etc. is periodically saved as a log (the save frequency can be set). 12 Coordinated shutdown When a problem occurs with the power supply, multiple computers connected to the UPS can coordinate to perform auto shutdown. 13 Output receptacle control The UPS output receptacles can be individually set to ON/OFF. 14 Redundant power supply support Two or more UPS can be connected to computers equipped with redundant power supply. Shutdown is not performed when a power supply proble affects only one of the units. Shutdown is performed only when a power supply problem occurs with both UPS, so the system's operating rate is improved. 15 Remote UPS management The UPS can be managed remotely from a computer on the network. 16 Mail send When a problem such as a power failure occurs, a notification email describing the problem can be sent to the system administrator. 17 SNMP management UPS management information can be sent to the SNMP manager. 18 Telnet connection Settings such as shutdown parameters can be made via the Telnet connection. 19 SYSLOG support UPS management information can be recorded in SYSLOG.

7.Using the UPS monitoring software and contact signal
"PowerAct Pro" UPS monitoring software The included "PowerAct Pro" UPS monitoring software allows you to automatically save files and perform shutdown processing of your PC when a power failure occurs.(It is possible to shut down multiple com- puters on the network.)
Also, you can perform desired operation by setting the automatic start/stop of the UPS based on the schedule setting.
* The time between the occurrence of a power failure and the shutdown of your PC must be within the backup time measured in "5-1 How to measure backup time" on page 51. For more information, refer to the Instruction Manual and online help of the UPS monitoring software.


BU3002SW
<USB>



7.Using the UPS monitoring software and contact signal
* When connecting 2 or more computers to the UPS

Software to install: PowerAct Pro How to install: Refer to the separate “UPS monitoring software installation guide”.


Connect to USB Port on UPS Connector
Power cable

7.Using the UPS monitoring software and contact signal
Scheduled operation using the UPS monitoring software ●When performing scheduled operation in which the UPS is stopped and a device such as a breaker is used to stop the UPS at the same time that commercial power stops, specify a period of no more than 3 months for the start of the next operation. If you specify a period longer than 3 months, the internal timer is reset and the scheduled operation does not start. Note that this period reduces to approximately half when the battery is dead. If a period of 3 months is exceeded, you start operation by supplying commercial power and pressing the Start Switch. However, if the battery is dead, you may not be able to start operation. In this case, replace the battery according to "6-2 Replacing the battery" on page 54.
Start of operation in scheduled operation using the UPS monitoring software ●To manually start up this unit after it has been stopped by a scheduled operation, turn OFF the power switch and turn it back ON again. To stop the unit when it is in operation, turn OFF the power switch.
Auto restart after OS closing processing using the UPS monitoring software ●When a power failure occurs, certain PCs (*1) automatically restart immediately after the OS is shut down by auto shutdown. In this case, the UPS stops during or after the restart of the PC, which may damage files and the hard disk. You can avoid this phenomenon by disabling POWER MANAGEMENT in the BIOS settings of the PC. *1) Certain PC: It is known that this phenomenon occurs for MICRON's Millennia Mme.
Precautions when “setting the UPS to stop automatically” after OS shutdown ●If, after a power failure occurs, the power is restored while auto shutdown processing is being performed, UPS output stops once after the set time elapses. After shutdown processing is complete, do not turn ON the computer until the UPS has finished restarting.

7.Using the UPS monitoring software and contact signal
7-2 When performing auto-save functions using the UPS service in Windows Server 2003/XP/ 2000 + UPS service driver
When using the included "UPS service driver", the OS standard UPS service in Windows Server 2003/XP/2000 can be used. When there is a power failure, files can automatically be saved and the computer can be shut down. 1. Connect the UPS to a computer. * Only 1 computer can be connected to the UPS
* The RS232C cable and USB cable cannot be used at the same time.


BU3002SW
<USB>



7.Using the UPS monitoring software and contact signal
7-3 When performing auto-save functions using the standard UPS service in Windows Server 2003/XP/2000/NT
When using in combination with the BUC26 cable (sold separately), the OS standard UPS service in Windows Server 2003/XP/2000/NT can be used. When there is a power failure, the computer can be shut down.
* Only 1 computer can be connected to the UPS


Connection cable (BUC26)

7.Using the UPS monitoring software and contact signal
<When using the Windows Server 2003/XP/2000 standard UPS service>
Start up the computer after connecting it with the UPS. Perform "Log on to Windows" as the Administrator. After logging on, follow the instructions below to set up the UPS service.

Click the button on the right of the "Port (P)" window, and select from the list the port that the UPS is connected to. (In the example screen below, the UPS is connected to COM1.)
Click the "Next (N)" button.


7.Using the UPS monitoring software and contact signal
Set the polarity for each signal to "Negative". Click the "End" button.

Setup is complete.
When a power failure occurs, Windows shutdown starts once the Low battery level signal is detected.
If the power is restored before the Low battery level signal is detected, Windows shutdown does not start and the normal monitoring state is restored.
Recycling and Discarding the Battery In the Windows Server 2003/XP/2000 UPS service, there is no function to stop the UPS. After Win- dows is shut down, manually turn OFF the unit's power switch.

7.Using the UPS monitoring software and contact signal

In the window to the right, set the amount of time to wait before starting Windows shutdown after a power failure occurs. (Setting range: 2 to 720 minutes)
Click the "OK" button.

Click · Check Set · Click

7.Using the UPS monitoring software and contact signal
Setup is complete.
When a power failure occurs, Windows shutdown starts once the set time is exceeded or the low battery voltage signal is detected.
If the power is restored before the set time is exceeded, Windows shutdown does not start and the normal monitoring state is restored.
<When using the Windows NT standard UPS service>

Set each signal interface voltage setting as shown below.
- Power failure signal (P) ... Negative - Low battery signal (L) ... Negative - Remote uninterruptible power source shutdown ... Positive

7.Using the UPS monitoring software and contact signal

Set each signal interface voltage setting as shown below.
- Power failure signal (P) ... Negative
- Remote uninterruptible power source shutdown ... Positive
Set the attributes for the uninterruptible power source and the time for each UPS service item.
Please note that in the case of incorrect interface voltage signal settings, Windows NT will not receive the signal from the UPS and the UPS will not stop when there is a power failure.
Failure to put check marks in the boxes will lead to the same result.

By starting the alerter service, messenger service, and event log service in advance, the UPS service sends warning messages to the user and records a history of events such as power failures when they occur.
When a power failure occurs, Windows shutdown is performed once the Low battery level signal is detected. If the power is restored before the Low battery level signal is detected, Windows shutdown is not performed and the normal monitoring state is restored.

7.Using the UPS monitoring software and contact signal
You can develop your unique system based on the following specifications to automate the process at a power failure. You can perform power-failure processing by allowing the system to detect the backup signal and also perform system shutdown processing by allowing the system to detect the Low battery level signal. Also, by inputting the backup stop signal from the system, you can stop the UPS with a sufficient battery level to prepare for the next occurrence of a power failure.
BU-COM ON when a power failure occurs
BL-COM ON when the battery is low
TR-COM ON when a power failure occurs
WB-COM ON when battery deterioration is detected
(1) When the "BS signal valid range setting" (setting switch 7 ) is set to OFF:
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10 seconds from the outside.
(2) When the "BS signal valid range setting" (setting switch 7 ) is set to ON:
You can stop power output by inputting the voltage signal (HIGH) that lasts at least 0.01 second (10 ms) from the outside that is accepted only during backup.
See also "4-4 Changing the setting of the functions" "2. UPS operation mode settings" ➛ Page 42, 47
BS-COM UPS stops

7.Using the UPS monitoring software and contact signal
Connection terminals are at contact signal connector pins 6 ,7 and the remote ON/OFF connector.
See also "8. Example of the use of the Contact Signal circuit" ➛ Page 81
Jumper settings (8 digits)
DIP switches (3 digits)
After changing the setting switch, disconnect the AC input plug, wait until the status indicator is completely OFF, and then reinsert the AC input plug.
By using the switches of contact signal card, set the item below.
External contact Operate · Open Start · Close Stop

7.Using the UPS monitoring software and contact signal
BU-COM ON when there is a power failure
Continues during a power failure, and turns ON (OFF). By setting the contact signal card’s setting switch as shown in the table on the right, the length of time from when the power failure occurs until the power failure signal is output can be delayed between 0 and 3 minutes.
Setting Setting Delay time switch 1 switch 2 setting
The power failure signal is not output if the power supply error is resolved within the set delay time.
OFF OFF 0 second (factory setting)
ON OFF Signal output after 30 seconds
OFF ON Signal output after 60 seconds
ON ON Signal output after 180 seconds
BU and BL signals are output in reverse.
Setting switch 3 Backup signal output (BU) OFF Normal output (factory setting) ON Reverse output
OFF
OFF
OFF
Backup signal output (BU) delay time setting (setting switches 1, 2)
By making jumper settings, the contact signal card SC05/06 connector pin assignments can be changed. Turn over the contact signal card, and change all (8) of the jumper settings to "SC05/06".
Jumper settings (8)
SC05/06
SC07
SC07
AC input ON

7.Using the UPS monitoring software and contact signal
(1) Turn OFF the power switch, remove the top and bottom screws (2 screws) of the contact signal connector
on the back of the unit, and carefully remove the contact signal card.


(2) After changing the settings, carefully reinsert the contact signal card and securely tighten the 2 screws.


4. Contact Signal Connector (female DSUB9P)

Pin assignment Pin number For jumper setting “SC07” For jumper setting “SC05/06” * Factory settings 1 Battery LOW signal output (BL) NC 2 Trouble signal output (TR) Backup signal output (BU) 3 Backup stop signal input (BS) Backup reverse signal output (BU) 4 NC COMMON (COM) 5 COMMON (COM) Battery Low Signal output (BL) 6 Remote ON/OFF input (–) Backup stop signal input (BS) 7 Remote ON/OFF input (+) Remote ON/OFF input (–) 8 Backup signal output (BU) Trouble Signal output (TR) 9 Deteriorated battery signal output (WB) Remote ON/OFF input (+)

7.Using the UPS monitoring software and contact signal

Pin assignment Pin number Signal name 1 Remote ON/OFF (+) 2 Remote ON/OFF (-)
Photo coupler ratings Input voltage HIGH(ON) 5 to 12 VDC


UPS side GND System side Connecting cable (twisted or shielded)

7.Using the UPS monitoring software and contact signal
Example of remote ON/OFF
remote ON/OFF(+)
remote ON/OFF(-)
Notes
UPS side

8.Using an SNMP/Web card
An SNMP/Web card can be loaded into the card slot on the back of the unit. Remove the contact signal card that the unit came equipped with, and plug the SNMP/Web card in its place. Store the removed contact signal card in a safe place.
(1) Remove the 2 screws, and carefully pull out the contact signal card.


(2) Carefully insert the SNMP/Web card (model number: SC20G), and securely tighten the 2 screws. * Replace with BU50SW/BU75SW/BU100SW/BU150SW/BU1002SW/BU3002SW brackets.



8.Using an SNMP/Web card
LAN port 10/100 Mbit Network protocol SNMP, HTTP, APR, RARP, TFTP, ICMP Other communication route Serial connection: asynchronous method (setting only) Number of controllable computers 32 max. (including slave UPS when coordinated shutdown is enabled)
Support MIB UPSMIB (RFC1628) OMRON MIB Other Equipped with real-time lock Windows NT 4.0, Windows 2000, Windows XP, Windows Server 2003 Red Hat Linux 7.2/7.3/8.0 Shutdown software-compatible OS Red Hat Enterprise Linux AS/ES/WS (Red Hat Linux Advanced Server
2.1) Max OS X v10.3*/Server 10.39 (*1) Max OS X v10.4*/Server 10.4 (*1) (*1) Compatible only with Macintosh computers equipped with PowerPC CPU.
For more details, refer to the instruction manual included with the SNMP/Web card.
The most recent firmware can be downloaded from our homepage(http://www.omron.co.jp/ped-j/download/
sc20/sc20.htm).

9.Extending the backup time
You can extend the backup time by connecting an additional optional battery unit to the UPS.

When an additional battery unit is connected, the charging time is 24 hours.
Adding BUM100S to the BU1002SW For the BUM100S, the included battery connection cable is provided with cable clamps attached. Connect the battery connection cable according to the instructions below.
(1) Loosen the screws and remove the battery connector covers on the rear side of the unit and battery unit.
Use the removed screws to attach the cable clamps.
(2) Connect the battery connection cable to the battery connectors on the rear side of the unit and the battery
unit. To simplify the operation, do not yet tighten the screws that hold the battery connection cable on the cable clamp.
(3) Use screws to attach the cable clamps to the rear side of the unit and the battery unit (2 screws each).
(4) Tighten the screws that hold the battery connection cable on the cable clamps.
(5) Turn ON the overcurrent protection switch on the back of the battery unit.
(6) Connect the AC input plug of the unit to a wall outlet. The additional battery lamp on the unit's operation
panel turns ON.

For information on backup time, see the backup time table in ”5-2 Estimated backup time”.
Overcurrent protection switch · See also · ➛ Page 51

9.Extending the backup time
(1) Loosen the screws and remove the battery connector covers on the rear side of the unit and battery unit.
(2) Connect the battery connection cable to the battery connectors on the rear side of the unit and the battery
unit. Connect the battery connection cable to the additional battery signal connector also.
(3) Turn ON the overcurrent protection switch on the back of the battery unit. Connect the AC input plug of the
unit to a wall outlet. The additional battery lamp on the unit's operation panel turns ON.
Additional battery signal connection
Additional battery signal connection
OFF

Perform the checks shown below if the unit is operating abnormally. If the unit continues to operate abnormally, please contact our peripheral device customer support center at
UPS does not operate. The LED display does not light up, even though the AC input plug is connected to a wall outlet (commercial power) and the power switch is ON.
1. Check that the AC Input Plug is connected to the commercial power securely. 2. The AC Input Overcurrent Protection is working. (If the black button has popped up, there are probably too many connected devices or there is a short in the connected devices.) Disconnect all of the connected devices, push in the the black AC input overcurrent protection button and turn ON the Power Switch of the UPS again. If the status indicator does not display normally, there is a problem with the UPS. (See "Interpreting beeps and displays" on page 39.)
Backup is not possible. The computer stops when a power failure occurs.
Is charging insufficient? Perform the test after charging the battery for at least 8 hours. (When an additional battery is connected, the charging time is 24 hours.) (You can charge the battery by connecting the AC input plug of the UPS to a wall outlet (commercial power).)
Backup is performed too frequently. Frequent switching is performed although a power failure does not occur. You hear the sound of switching.
Does not turn ON when power switch is pressed.
The unit does not start up when the input power supply voltage/frequency is abnormal. (The status indicator displays “H-”, “-H”, “L-” or “-L”.) Check the voltage and frequency of the input power supply.
See also A. Specifications Input Allowable voltage range, frequency see Page 88
The display is abnormal.
The battery replacement lamp blinks and the beeper sounds at 2-second intervals.
The status indicator shows “ ”, and the beeper sounds at 0.5-second intervals.
There are too many connected devices. Reduce the number of connected devices until “ ” is displayed on the status indicator.
The status indicator blinks “ ”, and the beeper sounds continuously.
The UPS stopped because too many devices were connected for 3 minutes or more, or because 120% was exceeded. Turn OFF all power to the unit and connected devices, and reduce the number of connected devices. Then, turn the power to the unit and connected devices back ON and check whether " " is displayed on the status indicator.
Problem · Check and remedy

Method Operation method Full-time inverter supply method
Connectable devices PC, display, and peripherals
Input Rated input voltage 200 to 240V ± 10%
Allowable voltage range AC145±4 to 276±4V (with 85% or less connection load) AC170±4 to 276±4V (with 85% or more connection load)
Frequency 50/60Hz ± 4Hz
Maximum current 7.4A 16A
Input plug shape NEMAL6-15P NEMAL6-20P
Input protection Reset-type overcurrent protection device
Input protection capacity 10A 20A
Output Allowable connection capacity *1 1000VA/700W 3000VA/2100W
Voltage (effective value) *2
200V mode AC200V ± 3%
220V mode AC220V ± 3%
230V mode AC230V ± 3%
240V mode AC240V ± 3%
(In Commercial Power Mode) 230V mode:AC324V±6% 240V mode:AC338V±6%
Frequency 50/60Hz ± 1Hz
Output waveform Sine wave
Waveform distortion rate 200V mode: 6% max. 220V mode: 10% max.
(Rectified load, at rated output) 230V mode: 10% max. 240V mode: 12% max.
Number of output receptacles IEC60320 C13 : 3 pcs. IEC60320 C19 : 1 pcs. C13 : 5 pcs.
Power failure switching time Uninterrupted
Commercial direct shipment (switching time) 4msec. max.
Backup time *3 Minimum 5 minutes
Battery Type Compact sealed lead battery
Sealed lead battery life expectancy 4 to 5 years (long operating life) *At ambient temperature of 20°C
Battery capacity (V/Ah) (x Quantity) 12V DC/ 7.2 Ah (x 3) 12V DC/ 9 Ah (x 6)
Charging time 8 hours *4
Environment Operating ambient temperature 0 to 40°C (during operation)/ -15 to 50°C (during storage)
Operating ambient humidity 25 to 85%RH (during use)/10 to 90%RH (during storage)
Dimensions 145 x 395 x 224 (±1) mm *5 213 x 537 x 432 (±1) mm *6
Weight of unit Approx. 15.5 kg Approx. 35 kg Internal power consumption (max.) 50W (100W max.) 55W (155W max.) *7
Noise regulation (compliance standard) VCCI Class A Safety standard compliance UL/CE
Noise 50 dB max. 55 dB max.
*1: Make sure that both the VA value and the W value of the load capacity connected to the UPS are within the range specified here. *2: Check the operation beforehand if the unit is used in any mode other than “200V AC mode”. In some cases, the maximum voltage of output in Battery Mode may be lower than the maximum voltage in usual operation (commercial power supply). *3: The backup times shown here are for when rated load is connected, at 20°C, and for initial characteristics. *4: When an additional battery unit is connected, the charging time is 24 hours. *5: The height includes the 13-mm height of the rubber feet. *6: The height includes the 56mm height of the casters. *7: 170W max when and additional battery unit is connected.


Reference

200 to 240V AC input
At startup/capacity exceeded/error During Line mode During Battery mode
Description BU1002SW BU3002SW Replacement battery pack BP100XS BP150XS (two required) Additional battery unit BUM100S BUM300S Replacement fan BUF1002S for rear fan BUF1002S for rear fan
BUF3002S for front fan Mounting bracket BUP100S BUP300S SNMP/Web card SC20G Connection cable for Windows UPS service BUC26

No part or whole of this manual may be reproduced without permission. The contents of this manual are subject to change without notice.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| D-1 | The most recently displayed error code (refer to item 4 on page 34) | p.38 |
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS does not operate. The LED display does not light up, even though the AC input plug is connected to a wall outlet (commercial power) and the power switch is ON. | 1. Check that the AC Input Plug is connected to the commercial power securely. 2. The AC Input Overcurrent Protection is working. (If the black button has popped up, there are probably too many connected devices or there is a short in the connected devices.) Disconnect all of the connected devices, push in the the black AC input overcurrent protection button and turn ON the Power Switch of the UPS again. If the status indicator does not display normally, there is a problem with the UPS. (See "Interpreting beeps and displays" on page 39.) | p.89 | |
| Backup is not possible. The computer stops when a power failure occurs. | Is charging insufficient? Perform the test after charging the battery for at least 8 hours. (When an additional battery is connected, the charging time is 24 hours.) (You can charge the battery by connecting the AC input plug of the UPS to a wall outlet (commercial power).) | p.89 | |
| Backup is performed too frequently. Frequent switching is performed although a power failure does not occur. You hear the sound of switching. | Variations (decrease) in the input power occur frequently. Or, noise is included that significantly distorts the voltage waveform of the input power. ●Change the wall outlet (commercial power) to which you connect the UPS. Try connecting to a wall outlet (commercial power) away from equipment that consumes large power. ●This problem may occur also when you connect many devices to a plug strip or extension cord connected to the UPS if it is a long or thin cable. | p.89 | |
| Does not turn ON when power switch is pressed. | The unit does not start up when the input power supply voltage/frequency is abnormal. (The status indicator displays “H-”, “-H”, “L-” or “-L”.) Check the voltage and frequency of the input power supply. See also A. Specifications Input Allowable voltage range, frequency see Page 88 | p.89 | |
| The display is abnormal. ● The display is unstable. ● White lines occur. ● Noise increases. | The probable cause is noise that occurs inside the UPS. ●Ground all devices connected to the UPS. Connect them to a wall outlet (commercial power) for 3-pin plugs or connect their Grounding Terminal to the Grounding Terminal of a wall outlet. ●This problem may occur when power cords are long or placed closely or when the UPS and devices to be backed up are placed closely. Rearrange them. ●If the UPS or devices connected to the UPS are contained in a metal rack, attempt to ground the rack itself. | p.89 | |
| The battery replacement lamp blinks and the beeper sounds at 2-second intervals. | 1) The auto battery test or self-diagnostic test determined that the battery is dead. 2) Did the overcurrent protection switch on the rear panel of the additional battery unit get turned OFF when connecting an additional battery unit? If it is not ON, the auto battery test may falsely detect a deteriorated battery. | p.89 | |
| The status indicator shows “ ”, and the beeper sounds at 0.5-second intervals. | There are too many connected devices. Reduce the number of connected devices until “ ” is displayed on the status indicator. | p.89 | |
| The status indicator blinks “ ”, and the beeper sounds continuously. | The UPS stopped because too many devices were connected for 3 minutes or more, or because 120% was exceeded. Turn OFF all power to the unit and connected devices, and reduce the number of connected devices. Then, turn the power to the unit and connected devices back ON and check whether " " is displayed on the status indicator. | p.89 |