Thermal Mass Flow Controllers





A. Introduction 1. Unpacking All units are suitably packaged to prevent damage during shipping. If external damage is noted upon receipt of the package, please contact Omega Engineering immediately. Open the package from the top, taking care not to cut too deeply into the package. Remove all the documentation and contents. Take care to remove all the items and check them against the packing slip. The products should also be checked for any concealed shipping damage. If any shortages or damage is noted, please contact Omega Engineering to resolve the problem.
Typical Contents of Box: Controller, Calibration Certificate & Manual FMA 3200/3200ST shown; FMA 3400/3400ST have an integrated display.


sensor design. This proven design minimizes zero drift while maintaining fast response and linear outputs with virtually no maintenance.
The FMA 3200/3400 Series utilizes thermal flow sensing technology. A portion of the gas flowing through the unit is redirected into a small sensor tube. This tube has two coils on the outside. The first coil introduces a small amount of heat into the gas stream. As the gas passes through the tube heat is transferred from one coil to the other. The flow rate is proportional to the amount of heat transfer. Smart electronics analyze the amount of temperature change in the second coil and provide a linearized analog output. A patented system insures that the zero remains stable and the sensor is extremely repeatable. Flow in the FMA 3200/3400 Series is controlled by a proportional solenoid valve with active servo electronics. The flow measurement signal is analyzed by micro-processor controlled electronics and compared to a set- point. Adjustments are then made to the valve in order to achieve the required flow rate. The set point can be either externally input via a 0- 5VDC signal or in the case of the FMA 3400/3400ST Series it can be input manually on the unit. The output of the thermal mass flow sensor is directly related to the specific heat characteristic of the gas being measured. A sensor is calibrated for one gas but may be used with other gases by applying a correction factor to the output. The calibration gas for each specific flow controller is detailed on the product label. B. Installation

Caution: Do not exceed the pressure, temperature or power operating ranges detailed in the SPECIFICATIONS section of this manual. Omega Engineering shall not be liable for any damage or injury caused by incorrect operation of their products. 1. General Considerations It is recommended that a safety shut-off valve be installed upstream (before) of the controller. All wetted parts should be checked for compatibility with the gas to be used. If there are any incompatibilities eg. highly corrosive gas, then the

unit may be damaged or fail prematurely. Such damage will not be repaired under warranty. Units should be installed in a clean, dry environment with an ambient temperature that is as stable as possible. Avoid areas with strong magnetic fields, strong air flows or excessive vibration. In order to operate the differential pressure across the controller should be in the range 15-45psid (1-3 bar). For optimum performance a differential pressure of 25psid is recommended. For Example, consider the following system:
The differential pressure across the flow controller in this system would be 100 psi – 14 psi = 86 psid. Consequently the flow controller would NOT be able to control flow. For the unit to operate at optimum performance the supply pressure from the gas cylinder would need to be lowered to 39 psig to give 39 psi -14 psi = 25 psid.

Mounting View from Bottom (mounting hardware not included with sensor)


a) Overview The FMA 3200/3400 Series provides a 0-5VDC analog output proportional to the flow rate. This output may be connected to a display, data acquisition system or voltmeter with an impedance of greater than 2.5 kΩ (kilo ohms). The flow controller needs to be supplied with a 0-5 VDC set point signal to enable control. On the FMA 3400/3400ST Series this may be generated internally by altering the set-point potentiometer on the front panel of the unit. A stable D.C. power supply is required to operate the unit. The voltage and current requirements depend on the configuration of the unit. Full details may be found in the Specification section of this manual. Connecting wires should be as short as possible to avoid voltage drops. Twisted conductor cable should be used if the length of the wiring is to be longer than 2 meters. Units are supplied with either a 6 pin mini DIN type connector (requires mating cable assembly), a 9 Pin D Sub connector or 15 Pin D Sub connector.
Electrical connections to the units are made as detailed in the following sections.

b) Connecting The 6 Pin Mini Din Connector Using a suitable mating connector the pins of the integrated connector should be wired as follows:
Connecting To The Integrated 6 Pin Connector


Pin Out of Integrated
Pin 2 should be connected to the Positive of the power source. Pin 6 should be connected to the Negative (Ground) of the power source. Pin 3 provides the signal output and should be connected to the positive terminal of the display, data acquisition system or voltmeter. Pin 1 is the signal negative (ground) and should be connected to the negative (Ground) terminal of the display, data acquisition system or voltmeter. Pin 4 provides the input signal and should be connected to the positive terminal of the voltage source. The (0-5VDC) voltage control signal should be supplied from a low impedance source. Pin 5 is the input signal negative (ground) and should be connected to the negative (Ground) terminal of the voltage source.
Connector

c) Connecting The 6 Pin Mini Din Connector & FMA 3000C Cable The two mating connectors should be pushed together and the pigtail leads wired as follows:
Connecting To The Integrated 6 Pin Connector Using A FMA 3000C Cable

The RED wire should be connected to the Positive of the power source. The BLACK wire should be connected to the Negative (Ground) of the power source. The ORANGE wire provides the signal output and should be connected to the positive terminal of the display, data acquisition system or voltmeter. The BROWN wire is the signal negative (ground) and should be connected to the negative (Ground) terminal of the display, data acquisition system or voltmeter. The YELLOW wire provides the input signal and should be connected to the positive terminal of the voltage source. The (0-5VDC) voltage control signal should be supplied from a low impedance source. The GREEN wire is the input signal negative (ground) and should be connected to the negative (Ground) terminal of the voltage source. The wire colors above describe the pigtail leads of the FMA 3000C cable assembly and may not correspond with the internal wiring of your flow sensor.

d) Connections For The 9 Pin D Sub Connector Using a suitable mating connector the pins of the integrated connector should be wired as follows:
Connecting To The Integrated 9 Pin Connector


Pin Out of Integrated
PIN 3 should be connected to the Positive of the power source. PIN 4 should be connected to the Negative ( Ground ) of the power source. PIN 2 provides the signal output and should be connected to the positive terminal of the display, data acquisition system or voltmeter. PIN 8 is the signal negative (ground) and should be connected to the negative (Ground) terminal of the display, data acquisition system or voltmeter. Pin 6 is the input signal and should be connected to the positive terminal of the voltage source. The (0-5VDC) voltage control signal should be supplied from a low impedance source. Pin 7 is the input signal negative (ground) and should be connected to the negative (Ground) terminal of the voltage source. Pins 1, 5, and 9 are not used.
Connector

e) Connections For The 15 D Sub Connector Using a suitable mating connector the pins of the integrated connector should be wired as follows:
Connecting To The Integrated 15 Pin Connector


Pin Out of Integrated
PIN 7 should be connected to the Positive of the power source. PIN 5 should be connected to the Negative ( Ground ) of the power source. PIN 2 provides the signal output and should be connected to the positive terminal of the display, data acquisition system or voltmeter. PIN 10 is the signal negative (ground) and should be connected to the negative (Ground) terminal of the display, data acquisition system or voltmeter. Pin 8 is the input signal and should be connected to the positive terminal of the voltage source. The (0-5VDC) voltage control signal should be supplied from a low impedance source. Pin 1 is the input signal negative (ground) and should be connected to the negative (Ground) terminal of the voltage source. Pins 3, 4, 6, 9, 11, 12, 13, 14 and 15 are not used.
Connector

f) Using a 0-5VDC Input / Output Power Adapter Package. An optional 0-5VDC Input / Output Power Adapter Package is available for use with the FMA 3200/3400 Series. This consists of a power source (115VAC or 230VAC), a connection hub and two cable assemblies with pig- tail (soldered wire) ends. This should be assembled as shown in the following diagram.
Assembling a FMA 3215PW Power Adapter Package (the FMA 3223PW Power Adapter Package is similar)

The RED connector should be inserted in the RED socket on the connection hub. The WHITE connector should be inserted in the WHITE socket on the connection hub. The cable with a RED connector provides the input signal. The RED wire of this cable should be connected to the positive terminal of the voltage source. The (0-5VDC) voltage control signal should be supplied from a low impedance source. The bare wire of this cable assembly is the input signal negative (ground) and should be connected to the negative (Ground) terminal of the voltage source. The cable with a WHITE connector provides the signal output. The WHITE wire should be connected to the positive terminal of the display, data acquisition system or voltmeter with an impedance of greater than 2.5 kΩ (kilo ohms). The bare wire of this cable assembly is the signal negative (ground) and should be connected to the negative (Ground) terminal of the display, data acquisition system or voltmeter.

1. Warm Up Before applying power to the unit check all tubing and electrical connections. Once correct installation is verified switch on the power. The unit should then be allowed to warm up for 5 minutes before gas pressure is applied. 2. Verification of Zero Flow through the unit should be stopped by sealing or capping the inlet of the controller. It is not adequate to only stop flow by turning off the gas supply or closing a valve as there may be a leak in the system. This would give a false reading. After 5 minutes, the zero should be stable when there is no flow through the unit. If after 10-15 minutes the output is still not zero volts (within ±0.05 volts) the unit should be adjusted as detailed in section C part 6. It should be noted that power supply voltage variations and changes in ambient temperature can have an effect on zero readings. 3. Flow Readings Each controller is factory calibrated for a specific flow range and gas (or gas mixture). The calibration gas and flow range are shown on the unit’s label and calibration certificate. By monitoring the voltage output signal it is possible to determine the flow rate of the gas. Units are configured so that an output signal of 5.0VDC is provided when the maximum flow (i.e. Full Scale flow) is passing through the unit. The output signal is linear and scaleable enabling calculation of flow rates with in the sensor’s range. For example:
For a flow range of 0-500sccm:
At 500sccm the output signal would be 5VDC
If the output signal were 3.5VDC then the flow rate would be:
500 ÷ 5 × 3.5 = 350sccm
If the maximum flow rate is exceeded non-linear and inaccurate readings will result. Units may be used for gases other than the calibration gas. In this case a “K Factor” would need to be applied and a corrected value calculated using the following formula:

Q1 / Q2 = K1 / K2
Q1 is the flow rate of the new gas Q2 is the flow rate of the original calibration gas K1 is the K factor of the new gas K2 is the K factor of the original calibration gas Q1 = (K1 / K2) Q2
If K2 is larger than K1 then linear results will only be achieved if the unit does not exceed 5(K1/ K2)VDC for the full scale output. Example 1 For a 0-200sccm unit calibrated for air the flow at 5.0VDC would be 200sccm. The K factor for air is 1. If the unit is used with Helium (K factor 1.454 relative to air) then the flow at 5VDC (i.e. the maximum flow) would be (1.454/1)200 = 290.8 sccm Example 2 For a 0-10.0 l/min unit calibrated for Argon the flow at 5.0VDC would be 10.0l/min. The K factor for Argon is 1.45. If the unit is used with Carbon Dioxide (K factor 0.74) then the flow rate 5.0VDC would be (0.74/1.45)10.0 = 5.10l/min The accuracy of readings using K factors is not as good as that achieved for the calibration gas. The accuracy obtained (typically ±3% for K factors similar to the calibration gas) depends on the gas being used and the flow rate. For a list of common K Factors see Section J. 4. Changing The Flow Rate Set-Point (Using An External Voltage Source) The required flow rate is selected by adjusting the set-point voltage. The normal control signal voltage is 0-5VDC with 0VDC corresponding to zero flow and 5VDC being equivalent to the maximum rated flow of the unit. This input is linear and scaleable allowing different flow rates within the range of the unit to be selected. For example:
For a flow range of 0-500sccm:
A 5 VDC Input Signal would correspond to a flow rate of 500sccm
If a flow rate of 300sccm were required then the set-point would
be:

If a gas other than the calibration gas is used then the adjusted maximum (full scale) flow for the unit should be calculated using the K Factor for that gas (see section C3 above). A zero or negative set-point voltage will cause the solenoid valve to close fully. Whilst closed, the valve is configured to withstand pressures up to 60 psig (higher pressures on request).
Caution: The flow controller valve will open if the pressure exceeds 60psig. For safety it is recommended that a separate positive shut-off valve is installed upstream of the controller. 5. Changing The Flow Rate Set-Point – FMA3400/3400ST Series Only On the FMA 3400/3400ST Series the set-point may be input from an external source or be supplied internally. For an external set-point, dip switch 1 should be OFF and dip switch 2 ON. See section C4 above for details of how to adjust the set-point using an external voltage source. For an internal set-point, dip switch 1 should be ON and dipswitch 2 OFF. Adjustment of the internal set-point is made by turning the coarse and fine set-point potentiometers on the front panel of the display, with the gas is flowing, until the desired flow rate is achieved.
FMA 3400/3400ST Series Set-Point Potentiometers


Making Zero Adjustments Using a Small Flathead Screwdriver

Care should be taken to only make small adjustments to the zero potentiometer. If too much of an adjustment is made and difficulties are being experienced in achieving a zero reading then turn the potentiometer fully anti-clockwise and begin making small clockwise adjustments until a zero reading is obtained. 8. Recalibration If recalibration is required please contact the Omega Engineering Customer Service Department. 9. Changing the Calibration Gas – FMA 3400/3400ST Series Only The FMA 3400/3400ST Series may be calibrated for up to three gases. These gases, their corresponding flow ranges and accuracy specifications are detailed on the calibration certificate. The calibration gas required is determined by selecting the corresponding dip switch on the front panel of the display.

FMA 3400/3400ST Series Dip Switches

Dip switch 4 is allocated to the primary calibration gas. Dip switch 5 is allocated to the second calibration gas (if applicable). Dip switch 6 is allocated to the third calibration gas (if applicable). To select the gas, the dip switch should be turned ON. All other switches allocated to gases (i.e. 4, 5 or 6 except the required switch/gas) should be set to OFF. D. Maintenance and Product Care 1. General Inlet filters should be periodically checked and cleaned or replaced as necessary. Regularly check all electrical and process connections for damage or deterioration. If the sensor is to be stored, keep both the inlet and outlet ports sealed. Do not allow any liquid or moisture to enter the sensor or damage will occur. 2. Returning Units for Repair or Recalibration To return a unit for repair or recalibration please contact the Omega Engineering Customer Service Department. An Authorized Return (AR) number will then be issued. The AR number should then be noted on the outside of the package and on any correspondence. Further details may be found on page 25 of this manual.


Series FMA 3200 FMA 3400 FMA 3200ST FMA 3400ST
Pressure Rating 150 psig (10.3 bar) 500 psig (34.5 bar)
Pressure Sensitivity ±0.02% Full Scale* per psi (per 69 mbar)
Valve Normally Closed Positive Shut-off up to 60psig (4 bar)
Wetted Materials Aluminum 304 Stainless Steel 316 Stainless Steel
303 Stainless Steel 304 Stainless Steel 316 Stainless Steel Epoxy
Fitting Material Choose from acetal, brass, or stainless steel
Compatible gases Clean, dry gases compatible with wetted materials
*Specifications from 10-100% of rated flow. Linearity is best fit straight line. All calibrations performed with air unless otherwise stated on calibration certificate.

F. Dimensions ALL DIMENSIONS IN INCHES (MILLIMETERS IN BRACKETS) FMA 3200/3200ST Series - 1/4” Stainless Fittings Shown


FMA 3400/3400ST Series - 1/4” Stainless Fittings Shown



These K Factors are given for reference only and are not intended as a recommendation of application suitability. Accuracy and response will be affected depending on the gas and flow range. Check the compatibility of all wetted materials before using any gas other than the calibration gas for the unit.

Symptom Possible Cause Method of Correction
Clicking noise from controller
Unit in error mode Check there is sufficient pressure and that the flow path is not restricted or blocked
Unit wired incorrectly Check wiring is according to Section B5
Loose connection Check all connectors and wiring
Damaged connector pins Contact Omega Engineering
Blocked flow path Check flow path for obstructions.
Piping leak before sensor Check all piping and connections.
Insufficient power Check the power supply output and increase if necessary
Output load resistance too low Ensure the voltmeter or data acquisition system or display has an impedance of greater than of 2.5kohm
Flow too low for the unit Ensure that the flow being measured is within the capabilities of the unit
Unit damaged or faulty Contact Omega Engineering
Particles in flow path Add filtration before the sensor.
Flow path obscured Remove any debris or blockage in the flow path eg. PTFE tape.
Unit calibrated for a different gas
Check calibration certificate and apply a “K” Factor to readings if necessary.
Gas composition is variable Contact Omega Engineering
Fittings have been changed Replace the factory installed fittings
Moisture in gas Ensure gas is clean and dry
Insufficient warm-up period Allow the unit to warm-up for at least 5 minutes.
Zero drift Verify the zero and adjust as necessary as explained in Section C
The gain potentiometer has been adjusted
Unit needs recalibration Contact Omega Engineering
Flow too high for the unit Ensure that the flow being measured is within the capabilities of the unit
No response · Inaccurate control · Contact Omega Engineering

Symptom Possible Cause Method of Correction
Insufficient or varying power Check the power supply output and increase if necessary
Insufficient pressure Ensure the pressure (an differential pressure) is high enough o operate the unit.
Varying pressure Check the stability of the pressure regulation and improve if necessary.
Ambient temperature too high or too low
Place the unit in a suitable environment
Output load resistance too low Ensure the voltmeter or data acquisition system or display has an impedance of greater than of 2.5kohm
Gas temperature too high or too low
Ensure the gas temperature is within the recommended operating range
Unit damaged or faulty Contact Omega Engineering
Gas flow through unit not completely stopped
Ensure there is no flow through the unit. The easiest way to do this is to plug both the inlet and outlet.
Severe fluctuations in the ambient temperature e.g. unit in direct sunlight
Carry out the rezero procedure in a stable environment
Unstable power supply Check the stability and suitability of the power source
Insufficient warm-up period Allow the unit to warm-up for at least 5 minutes.
Inaccurate control · Problems with rezeroing




Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Clicking noise from controller | Unit in error mode | Check there is sufficient pressure and that the flow path is not restricted or blocked | p.23 |
| No response | Unit wired incorrectly | Check wiring is according to Section B5 | p.23 |
| No response | Loose connection | Check all connectors and wiring | p.23 |
| No response | Damaged connector pins | Contact Omega Engineering | p.23 |
| No response | Blocked flow path | Check flow path for obstructions. | p.23 |
| No response | Piping leak before sensor | Check all piping and connections. | p.23 |
| No response | Insufficient power | Check the power supply output and increase if necessary | p.23 |
| No response | Output load resistance too low | Ensure the voltmeter or data acquisition system or display has an impedance of greater than of 2.5kohm | p.23 |
| No response | Flow too low for the unit | Ensure that the flow being measured is within the capabilities of the unit | p.23 |
| No response | Unit damaged or faulty | Contact Omega Engineering | p.23 |
| Inaccurate control | Particles in flow path | Add filtration before the sensor. | p.23 |
| Inaccurate control | Flow path obscured | Remove any debris or blockage in the flow path eg. PTFE tape. | p.23 |
| Inaccurate control | Unit calibrated for a different gas | Check calibration certificate and apply a “K” Factor to readings if necessary. | p.23 |
| Inaccurate control | Gas composition is variable | Contact Omega Engineering | p.23 |
| Inaccurate control | Fittings have been changed | Replace the factory installed fittings | p.23 |
| Inaccurate control | Moisture in gas | Ensure gas is clean and dry | p.23 |
| Inaccurate control | Insufficient warm-up period | Allow the unit to warm-up for at least 5 minutes. | p.23 |
| Inaccurate control | Zero drift | Verify the zero and adjust as necessary as explained in Section C | p.23 |
| Inaccurate control | The gain potentiometer has been adjusted | Contact Omega Engineering | p.23 |
| Inaccurate control | Unit needs recalibration | Contact Omega Engineering | p.23 |
| Inaccurate control | Flow too high for the unit | Ensure that the flow being measured is within the capabilities of the unit | p.23 |
| Inaccurate control | Insufficient or varying power | Check the power supply output and increase if necessary | p.24 |
| Inaccurate control | Insufficient pressure | Ensure the pressure (an differential pressure) is high enough o operate the unit. | p.24 |
| Inaccurate control | Varying pressure | Check the stability of the pressure regulation and improve if necessary. | p.24 |
| Inaccurate control | Ambient temperature too high or too low | Place the unit in a suitable environment | p.24 |
| Inaccurate control | Output load resistance too low | Ensure the voltmeter or data acquisition system or display has an impedance of greater than of 2.5kohm | p.24 |
| Inaccurate control | Gas temperature too high or too low | Ensure the gas temperature is within the recommended operating range | p.24 |
| Inaccurate control | Unit damaged or faulty | Contact Omega Engineering | p.24 |
| Problems with rezeroing | Gas flow through unit not completely stopped | Ensure there is no flow through the unit. The easiest way to do this is to plug both the inlet and outlet. | p.24 |
| Problems with rezeroing | Severe fluctuations in the ambient temperature e.g. unit in direct sunlight | Carry out the rezero procedure in a stable environment | p.24 |
| Problems with rezeroing | Unstable power supply | Check the stability and suitability of the power source | p.24 |
| Problems with rezeroing | Insufficient warm-up period | Allow the unit to warm-up for at least 5 minutes. | p.24 |