O P E R AT I N G I N S T R U C T I O N S Steam Humidifier 2401935 EN 0801 Nor dmann ec onoV ap N O R D M A N N ENGINEERING.
2 Intr oduction You have purchased a NORDMANN steam humidifier which, provided you observe the operating instructions, will ensure fully automatic operation and reliable, low-maintenance service. Therefore, read these operating instructions carefully and pay particular attention to the safety instructions and warnings.
3 General Safety Instructions The econoVap steam humidifier has been designed and constructed in accordance with the latest technology and the accepted safety regulations.
3.1 Dimensions Dimensions of the units Positioning of the humidifier 4 210 5 6 2 354 195 4 0 0 340 6 7 2 490 335 4 9 0 3 Installation Type Dimensions Fixing holes Steam outlet Drainage 4–8 kg/h Fig. 3.1 Fig. 3.2 1 x Ø 22 1 x Ø 22 15–32 kg/h Fig.
5 Dimensions of the steam distribution pipes 3.2 Steam Nozzle For smaller outputs of up to 4 kg/h steam, we offer a nozzle which can be either fitted in air ducts, for instance, or used for direct room humidification. The rules for vaporisation lines (lines needed to mix the steam adequately with air) must be observed here too.
Dimensions of the steam blowers 4-23 kg/h Fixing holes for the Dimensions of the steam blowers 4-23 kg/h steam blowers 4-23 kg/h Dimensions of the Turbo steam blowers 32, 45 und 65 kg/h 6 A B == B A == BA D E CG F BC A D E G F H J B C A D E G F H J A B D C E FG Type A B 4 - 8 kg 1 00 130 1 5-23 kg 1 80 240 Fig.
7 3.3 Fitting the humidifier For the fitting of the humidifier use the material supplied with the unit. Observe the various minimum distances as indicated in figure 3.5. Ensure that there is sufficient room to perform servicing and maintenance work and that the unit is easily accessible.
Steam-distribution pipe fitted on suction side: Because of the under-pressure in the appliance or the duct part, condensate may be kept back in the steam-distribution pipe. If there is an outlet in the empty part of the humidifier, the condensate can be bled off in the immediate vicinity.
9 Technical specifications steam blowers: 3.6 Laying the steam hose The steam hose should be kept as short as possible. It should not be possible to block or obstruct the steam supply lines in any way. Furthermore, they must be protected from outside interference (e.
10 4 W ater connections 3.7 Laying the condensate hose It is advisable to lay the condensate hose as near to the ver- tical as possible and to feed the condensate either directly into an open funnel or below the siphon.
4.2 W ater intake and drainage Please observe the local regulations concerning the connection of appliances to the pressure and drainage system. The humidifier is designed to operate on ordinary tap water only. If you intend to use treated or de-mineralised water, consult your NORDMANN representative beforehand.
6.1 Start-up Prior to starting the unit up, check the correct connections of the steam pipe, water feed pipe, drainage pipes and electrical cables. Open the shut-off valve in the water feed pipe and switch the unit on with the black power switch.
13 6.4 System- and servicing indications LED shining “green” continuously Operation Humidification is demanded. The humidifier operates automatically. Without demand of humidity the LED remains dark. red flash in the shining “green” Niveau max.
14 ! Regular servicing helps to maintain the operation of the humidifier. The following work must be carried out by qualified personnel. 7.1 Regular checks • Inspect the steam cylinder: Are there any deposits in the steam cylinder? ⇒ Remove the drainage strainer and flush the cylinder thoroughly with tap water (without chemical additives).
15 black red white black red white Fig. 7.1 7.4 T aking the humidifier out of operation If the humidifier is out of operation for a longer period of time ( e.g. in summer or when the air conditioning system is not operating), the steam cylinder must be emptied and the power supply disconnected.
9. T echnical specifications Other heating voltages on request. T ype mark: Type 434 834 1 534 2364 3264 4564 6564 Heating voltage V olt 400 V olt, 50/60 Hz Number of phases ~ 3 3 3 3 3 3 3 Heating current A 4.4 8.8 16.5 25.2 35.1 49.4 7 1.3 External fuses p.
An important point after buying a device Nordmende 2401935EN0801 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Nordmende 2401935EN0801 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Nordmende 2401935EN0801 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Nordmende 2401935EN0801 you will learn all the available features of the product, as well as information on its operation. The information that you get Nordmende 2401935EN0801 will certainly help you make a decision on the purchase.
If you already are a holder of Nordmende 2401935EN0801, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Nordmende 2401935EN0801.
However, one of the most important roles played by the user manual is to help in solving problems with Nordmende 2401935EN0801. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Nordmende 2401935EN0801 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center