Mitsumi electronic MSZ-DNA

40 pages·287 KB·Air Conditioner·PDF·ENDEFRITNLJA
Mitsumi electronic MSZ-DNA
Table of Contents 80 sections SPLIT-TYPE AIR CONDITIONERS · No. OBT16 REVISED EDITION-H · SERVICE TECHNICAL GUIDE · CONTENTS · … ShowHide
SPLIT-TYPE AIR CONDITIONERSp.1No. OBT16 REVISED EDITION-Hp.1SERVICE TECHNICAL GUIDEp.1CONTENTSp.1CONFIDENTIAL (FOR INTERNAL USE ONLY)p.11 MS MICROPROCESSOR CONTROLp.41-1. COOL ( ) OPERATIONp.4-1.8°F -1.35°F (-1°C) (-0.75°C)p.45.4°F (3°C) 1.8°F (1°C)p.43.15°F (1.75°C)p.4ONp.4OFFp.4-3.6°F -1.35°F (-2°C) (-0.75°C)p.54.5°F (2.5°C) 1.8°F (1°C)p.52 MSZ, MSY MICROPROCESSOR CONTROLp.72-1. COOL ( ) OPERATIONp.71.8°F (1°C)p.83.6°F (2°C)p.87.2°F (4°C)p.8MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GEp.9(MSZ-FE18 MSZ-GE24)p.9Time chart of defrosting in HEAT mode (reverse type)p.10<Indoor unit>p.10(39°C)p.10(18°C)p.10<Outdoor unit>p.10OFF OFFp.10ON ONp.10ON (HEAT)p.10(21S4) OFF (COOL)p.102-7. INVERTER SYSTEM CONTROL 2-7-1. Inverter main power supply circuitp.12MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD MUZ-FE09/12 MSZ-GE06/09/12/15/18 MUY-GE09/12/15/18p.12CURRENT TRANSFORMERp.12DIODE MODULE1p.12REACTORp.12NOISE FILTER CIRCUITp.12RESISTORp.12POWER SUPPLYp.12SMOOTHING CAPACITORp.12MSp.123~ Vp.12RELAYp.12INTELLIGENTp.12COMPRESSORp.12POWER MODULEp.12SWITCHING POWER TRANSISTORp.12DIODE MODULE2p.12BOOSTER CHOPPER CIRCUITp.12INTELLIGENT POWER MODULE POWER FACTORp.13CORRECTIONp.13MODULEp.13NAME FUNCTIONp.132-9. EXPANSION VALVE CONTROL (LEV CONTROL)p.18F E D C B Ap.19COOL / HEAT ( MUZ ) °F/°Cp.1968°F (20°C)p.2069.8°F (21°C)p.203 MXZ MICROPROCESSOR CONTROLp.213-1. INVERTER SYSTEM CONTROLp.21MXZ-2A20NA/3A30NAp.24LEVp.24(MXZ-3A30NA)p.24<MXZ-2A20NA>p.24<MXZ-3A30NA>p.24MXZ-2A20NAp.25MXZ-3A30NAp.25MXZ-2A20NA1 , 2 MXZ-2B20NA MXZ-2B20NA1 Exclusive LEVp.262 COOL -20 HEAT 30p.26MXZ-3A30NA1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NAp.26MXZ-2A20NA1 , 2 MXZ-2B20NA MXZ-2B20NA1p.27MXZ-2A MXZ-2Bp.28MXZ-3A MXZ-4A MXZ-3B MXZ-4Bp.283-3. OPERATIONAL FREQUENCY RANGEp.29MXZ-2A20NA1p.29MXZ-2A20NA2p.29MXZ-2B20NAp.30MXZ-2B20NA1p.30MXZ-3A30NA1 MXZ-4A36NAp.30MXZ-3B24NA MXZ-3B30NA MXZ-4B36NAp.31MXZ-2B20NA1 MXZ-3B MXZ-4Bp.32
Page 1 of the Mitsumi electronic MSZ-DNA user manual — Table of Contents
Page 1 · Contents
Contents

Contents

SPLIT-TYPE AIR CONDITIONERSp.1No. OBT16 REVISED EDITION-Hp.1SERVICE TECHNICAL GUIDEp.1CONTENTSp.1CONFIDENTIAL (FOR INTERNAL USE ONLY)p.11 MS MICROPROCESSOR CONTROLp.41-1. COOL ( ) OPERATIONp.4-1.8°F -1.35°F (-1°C) (-0.75°C)p.45.4°F (3°C) 1.8°F (1°C)p.43.15°F (1.75°C)p.4ONp.4OFFp.4-3.6°F -1.35°F (-2°C) (-0.75°C)p.54.5°F (2.5°C) 1.8°F (1°C)p.52 MSZ, MSY MICROPROCESSOR CONTROLp.72-1. COOL ( ) OPERATIONp.71.8°F (1°C)p.83.6°F (2°C)p.87.2°F (4°C)p.8MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GEp.9(MSZ-FE18 MSZ-GE24)p.9Time chart of defrosting in HEAT mode (reverse type)p.10<Indoor unit>p.10(39°C)p.10(18°C)p.10<Outdoor unit>p.10OFF OFFp.10ON ONp.10ON (HEAT)p.10(21S4) OFF (COOL)p.102-7. INVERTER SYSTEM CONTROL 2-7-1. Inverter main power supply circuitp.12MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD MUZ-FE09/12 MSZ-GE06/09/12/15/18 MUY-GE09/12/15/18p.12CURRENT TRANSFORMERp.12DIODE MODULE1p.12REACTORp.12NOISE FILTER CIRCUITp.12RESISTORp.12POWER SUPPLYp.12SMOOTHING CAPACITORp.12MSp.123~ Vp.12RELAYp.12INTELLIGENTp.12COMPRESSORp.12POWER MODULEp.12SWITCHING POWER TRANSISTORp.12DIODE MODULE2p.12BOOSTER CHOPPER CIRCUITp.12INTELLIGENT POWER MODULE POWER FACTORp.13CORRECTIONp.13MODULEp.13NAME FUNCTIONp.132-9. EXPANSION VALVE CONTROL (LEV CONTROL)p.18F E D C B Ap.19COOL / HEAT ( MUZ ) °F/°Cp.1968°F (20°C)p.2069.8°F (21°C)p.203 MXZ MICROPROCESSOR CONTROLp.213-1. INVERTER SYSTEM CONTROLp.21MXZ-2A20NA/3A30NAp.24LEVp.24(MXZ-3A30NA)p.24<MXZ-2A20NA>p.24<MXZ-3A30NA>p.24MXZ-2A20NAp.25MXZ-3A30NAp.25MXZ-2A20NA1 , 2 MXZ-2B20NA MXZ-2B20NA1 Exclusive LEVp.262 COOL -20 HEAT 30p.26MXZ-3A30NA1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NAp.26MXZ-2A20NA1 , 2 MXZ-2B20NA MXZ-2B20NA1p.27MXZ-2A MXZ-2Bp.28MXZ-3A MXZ-4A MXZ-3B MXZ-4Bp.283-3. OPERATIONAL FREQUENCY RANGEp.29MXZ-2A20NA1p.29MXZ-2A20NA2p.29MXZ-2B20NAp.30MXZ-2B20NA1p.30MXZ-3A30NA1 MXZ-4A36NAp.30MXZ-3B24NA MXZ-3B30NA MXZ-4B36NAp.31MXZ-2B20NA1 MXZ-3B MXZ-4Bp.32
Page 4 of the Mitsumi electronic MSZ-DNA user manual — ON
Page 4 · click to enlarge
Page 4

1 MS MICROPROCESSOR CONTROL

1-1. COOL ( ) OPERATION

1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat

ON -1.8°F(-1°C) or more OFF less than -1.8°F(-1°C)

-1.8°F -1.35°F (-1°C) (-0.75°C)

2. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat's OFFON. In AUTO the fan speed is as follows.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)

5.4°F (3°C) 1.8°F (1°C)

3.15°F (1.75°C)

3. Coil frost prevention Temperature control

When the indoor coil thermistor RT12 reads 37°F (3°C) or below the coil frost prevention mode starts immediately. However, the coil frost prevention does not work for 5 minutes since the compressor has started. The indoor fan operates at the set speed and the compressor stops for 5 minutes. After that, if the indoor coil thermistor still reads below 37°F (3°C), this mode is prolonged until the indoor coil thermistor reads over 37°F (3°C). Time control

When the 3 conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Low or Med. c. Room temperature is below 79°F (26°C). When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 79°F (26°C). However, when two of the above conditions (b. and c.) are satisfied again, time accumulation is resumed.

ON

OFF

( Continuously at set speed) ON

1-2. DRY ( ) OPERATION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.

Set temperature and initial room temperature in dry mode

50(10) 50 59 68 77 86 95

(10) (15) (20) (25) (30) (35)

Initial room temperature [°F(°C)]

Show 10 more labels / short text on this page
Fan speed · Operation chart Example · Compressor Outdoor fan · Indoor fan · 95(35) · Set temperature [°F(°C)] · 86(30) · 77(25) · 68(20) · 59(15)
Page 5 of the Mitsumi electronic MSZ-DNA user manual — ON
Page 5 · click to enlarge
Page 5
1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat

ON -3.6°F(-2°C) or more OFF less than -3.6°F(-2°C)

-3.6°F -1.35°F (-2°C) (-0.75°C)

2. Indoor fan speed control Indoor fan operates at the set speed by FAN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes Very Low. In AUTO the fan speed is as follows.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)

4.5°F (2.5°C) 1.8°F (1°C)

3.15°F (1.75°C)

3. The operation of the compressor and indoor/outdoor fan Compressor operates by room temperature control and time control. Set temperature is controlled to fall 4°F (2°C) from initial room temperature. Indoor fan and outdoor fan operate in the same cycle as the compressor.
  • When the room temperature is 73°F (23°C) or over:
  • When The Thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
  • When The thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
  • When the room temperature is under 73°F (23°C).
  • When The Thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
  • When The thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

Operation time chart Example

ON

OFF

ON

OFF

ON

OFF

8 minutes 1 minute 4 minutes 3 minutes

4. Coil frost prevention Coil frost prevention is as same as COOL mode. (2-1.3.) The indoor fan maintains the actual speed of the moment. However, when coil frost prevention works while the compressor is not operating, its speed becomes the set speed.
Show 4 more labels / short text on this page
Fan speed · Thermostat · Indoor fan · Outdoor fan Compressor
Page 6 of the Mitsumi electronic MSZ-DNA user manual — -3.6°F -1.35°F (-2°C) (-0.75°C)
Page 6 · click to enlarge
Page 6

1-3. AUTO VANE OPERATION 1. Horizontal vane ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermistor). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. To cancel this operation, select a different mode or press one of the following buttons in ECONO COOL operation: ECONO COOL or VANE CONTROL button.

In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6°F (2°C), the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.

Temperature of indoor coil thermistor (°F/°C)Downward blow time (second)Horizontal blow time (second) A59/15 or less223 B59/15 to 63 /17520 C63/17/ to 64/18817 D64/18 to 68/201114 E68/20 to 70/211411 F70/21 to 72/22178 G72/22 to 75/24205 Hmore than 75/24232
Page 7 of the Mitsumi electronic MSZ-DNA user manual — 5.4°F (3°C) 1.8°F (1°C)
Page 7 · click to enlarge
Page 7

2 MSZ, MSY MICROPROCESSOR CONTROL

2-1. COOL ( ) OPERATION

1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat

ON -1.8°F(-1°C) or more OFF less than -1.8°F(-1°C)

-1.8°F -1.35°F (-1°C) (-0.75°C)

2. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat's OFFON. In AUTO the fan speed is as follows.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)

5.4°F (3°C) 1.8°F (1°C)

3.15°F (1.75°C)

3. Coil frost prevention The compressor operational frequency is controlled to prevent the temperature of indoor heat exchanger from falling excessively. The compressor is turned OFF for 5 minutes when the temperature of indoor coil thermistor continues 37°F (3°C) or less for 5 minutes or more. The indoor fan maintains the actual speed of the moment.
4. Low outside temperature operation If the outside temperature falls to 64°F (18°C) or less during operation in COOL mode, the unit will switch to the low outside temperature operation mode. (1) Outdoor fan control

The outdoor fan rotational speed slows down to maintain sufficient cooling capacity. NOTE: Even when the unit is in the "thermostat-off" status under the low outside temperature operation mode, the out-

door fan rotation does not stop. (2) Dew drop prevention When the ambient temperature thermistor reads 14°F (-10°C) or less (the set temperature is different depending on the models), as coil frost or dew drop from indoor unit may occur, the compressor turns OFF with the outdoor fan OFF for prevention of them. (3) Outdoor temperature detecting control To detect the exact outdoor temperature in this mode, the compressor turns OFF but the outdoor fan stays ON for 3 minutes once 1 hour. If the outdoor temperature rises over about 64°F (18°C), the unit goes back to the normal COOL mode. If the outside temperature stays below about 64°F (18°C), the unit continues to run in the low outside tempera- ture operation mode. Other protections work as well as in the normal COOL mode.

Fan speed

Page 8 of the Mitsumi electronic MSZ-DNA user manual — 3.15°F (1.75°C)
Page 8 · click to enlarge
Page 8

2-2. DRY ( ) OPERATION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.

Set temperature and initial room temperature in dry mode

(10) (15) (20) (25) (30) (35) 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

50(10) 50 59 68 77 86 95

Initial room temperature [°F(°C)]

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat

ON -3.6°F(-2°C) or more OFF less than -3.6°F(-2°C)

-3.6°F -1.35°F (-2°C) (-0.75°C)

2. Indoor fan speed control Indoor fan operates at the set speed by FAN SPEED CONTROL button. When the thermostat turns OFF (compressor OFF), fan speed becomes Very Low. In AUTO the fan speed is as follows.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)

4.5°F (2.5°C) 1.8°F (1°C)

3.15°F (1.75°C)

3. Coil frost prevention Coil frost prevention is as same as COOL mode. (2-1.3.) The indoor fan maintains the actual speed of the moment. However, when coil frost prevention works while the compressor is not operating, its speed becomes the set speed. 4. Low outside temperature operation Low outside temperature operation is as same as COOL mode. (2-1.4.)

2-3. HEAT ( ) OPERATION (MSZ) 1. Thermostat control Thermostat turns ON or OFF by difference between room temperature and set temperature.

Room temperature minus set temperature (During operation) (MSZ-FE18 MSZ-GE24)

Room temperature minus set temperature (Initial)

ON less than 1.8°F(1°C) OFF 1.8°F(1°C) or more 1.35°F (0.75°C)

1.8°F (1°C)

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

ON less than 3.6°F(2°C) OFF 3.6°F(2°C) or more 3.15°F (1.75°C)

3.6°F (2°C)

2. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.

In Auto the fan speed is as follows.

Set temperature minus room temperature (During operation) Set temperature minus room temperature (Initial)

3.6°F (2°C)

7.2°F (4°C)

High Med. Low

Between 0.45 and 3.6°F 3.6°F(2°C) or more

Less than 0.45°F(0.25°C) 0.45°F (0.25°C)

3.15°F (1.75°C)

Show 11 more labels / short text on this page
95(35) · Set temperature [°F(°C)] · 86(30) · 77(25) · 68(20) · 59(15) · Fan speed · Thermostat · (Other models) · Thermostat · Fan speed
Page 9 of the Mitsumi electronic MSZ-DNA user manual — (MSZ-FE18 MSZ-GE24)
Page 9 · click to enlarge
Page 9

(2) Cold air prevention control

MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GE

When the compressor is not operating,

( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or more and

( ) if the temperature of indoor coil thermistor is less than 32°F (0°C), the fan stops. ( ) if the temperature of indoor coil thermistor is 32°F (0°C) or more, the fan operates at Very Low. When the compressor is operating,

( ) if the temperature of indoor coil thermistor is 104°F (40°C) or more, the fan operates at set speed. ( ) if the temperature of indoor coil thermistor is less than 104°F (40°C) and

( ) if heating operation starts after defrosting, the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or less, the fan stops. ( ) if the temperature of room temperature thermistor is more than 66°F (19°C), the fan operates at Very Low. NOTE: When 4 minutes (MSZ-FE18 MSZ-GE24)/3 minutes (Other models) have passed since the compressor started

operation, this control is released regardless of the temperature of room temperature thermistor and indoor coil thermistor. MSZ-A24 MSZ-GA

When the compressor is not operating,

( ) if the temperature of room temperature thermistor is 59°F (15°C) or less, or temperature of indoor coil thermis-

tor is less than 64°F (18°C), the fan stops. ( ) if the temperature of room temperature thermistor is more than 59°F (15°C), or temperature of indoor coil

thermistor is more than 64°F (18°C), the fan operates at Very Low. When the compressor is operating,

( ) if the temperature of indoor coil thermistor is 64°F (18°C) or more, the fan operates at set speed. ( ) if the temperature of indoor coil thermistor is less than 64°F (18°C) and

( ) if heating operation starts after defrosting, the fan stops. ( ) if the temperature of room temperature thermistor is 59°F (15°C) or less, the fan stops. ( ) if the temperature of room temperature thermistor is more than 59°F (15°C), the fan operates at Very Low. NOTE: When 3 minutes have passed since the compressor started operation, this control is released regardless of the

temperature of room temperature thermistor and indoor coil thermistor. (3) Warm air control (MSZ-FD MSZ-FE MSZ-GE)

When the following any condition of (a. ~ c.) and the condition of are satisfied at the same time, warm air control works.

a.) Fan speed is used in MANUAL. b.) When cold air prevention has been released. c.) When defrosting has been finished. When the temperature of indoor coil thermistor is less than 104°F (40°C). When warm air control works, the fan speed changes as follows to blow out warm air gradually. Gradation of fan speed in initial

(MSZ-FE18 MSZ-GE24)

Less than 4 minutes Low 4 to 8 minutes Med. More than 8 minutes High

Less than 2 minutes Low 2 to 4 minutes Med. More than 4 minutes High or Super high

The upper limit of the fan speed in MANUAL is the set speed. When the temperature of indoor coil thermistor has been 104°F (40°C) or more, or when the set speed has been changed, this control is released and the fan speed is the set speed. 3. Overload starting When the room temperature thermistor reads 64°F (18°C) or more, the compressor runs with its maximum frequency regu- lated for 10 minutes after the start-up. 4. Defrosting (1) Starting conditions of defrosting

When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads about 30.2°F (-1°C) or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min-

utes). c) More than 5 minutes have passed since the start-up of the compressor.

The defrost interval is decided by the previous defrosting time. The next defrost interval extends or shortens 0-20

minutes compared with the previous defrost interval.

(Other models)

Page 10 of the Mitsumi electronic MSZ-DNA user manual — (21S4) OFF (COOL)
Page 10 · click to enlarge
Page 10

(2) Releasing conditions of defrosting

Defrosting is released when any one of the following conditions is satisfied: a) The defrost thermistor continues to read "Defrost finish temperature" for 30 seconds.

Refer to "CHANGE IN DEFROST SETTING of SERVICE FUNCTIONS in OUTDOOR UNIT SERVICE MANUAL". b) Defrosting time has exceeded 10 minutes. c) Any other mode than HEAT mode is set during defrosting.

Time chart of defrosting in HEAT mode (reverse type)

<Indoor unit>

horizontal (temperature of indoor coil thermistor < 102 °F)

(39°C)

set speed Indoor fan

Very Low (temperature of indoor coil thermistor > 64 °F)

(18°C)

OFF

<Outdoor unit>

OFF OFF

30 seconds 40 seconds 5 seconds 5 seconds

ON ON

OFF

ON (HEAT)

ON (HEAT)

R.V. coil

(21S4) OFF (COOL)

2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ) Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation. 1. Mode selection (1) Initial mode

At first indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature. Following the conditions below, operation mode is selected.

If the room temperature thermistor reads more than set temperature, COOL mode is selected. If the room temperature thermistor reads set temperature or less, HEAT mode is selected.

Show 11 more labels / short text on this page
horizontal · set position · set position · Horizontal vane · set speed · 30 seconds · Maximum frequency · Compressor normal · 40 seconds · 30 seconds · Outdoor fan
Page 11 of the Mitsumi electronic MSZ-DNA user manual — Time chart of defrosting in HEAT mode (reverse type)
Page 11 · click to enlarge
Page 11

In case of the following conditions, the operation mode is changed.

COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C)

below the set temperature. HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C)

above the set temperature.

In the other cases than the above conditions, the present operation mode is continued.

ON-timer. NOTE2: When two or more indoor units are operating simultaneously, the indoor unit, which is operating in AUTO ( ), might not be able to change over the operating mode (COOL ↔ HEAT) and becomes the standby state. (3) Indoor fan control/ Vane control

As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation mode changes over, they change to the exclusive ones.

2-5. OUTDOOR FAN MOTOR CONTROL Fan speed is switched according to the compressor frequency.

Compressor frequency (Hz) DownUp MUZ-A MUY-A MUZ-FD MUZ-FE09/12 MUZ-GA MUY-GA MUZ-GE12/15/18 MUY-GE12/15/183344 MUZ-D MUY-D MUZ-GE09 MUY-GE093954 MUZ-FE18 MUZ-GE24 MUY-GE243343

Compressor frequency Min. Max.

2-6. AUTO VANE OPERATION 1. Horizontal vane (1) Cold air prevention in HEAT operation (MUZ)

When any of the following conditions occur in HEAT operation, the vane angle changes to Horizontal position automati- cally to prevent cold air blowing on users.

Compressor is not operating. Defrosting is performed. Indoor coil thermistor temperature does not exceed 102°F (39°C) within about 3 minutes after compressor starts. NOTE: When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat OFF,

this control does not work in the indoor unit. (2) ECONO COOL ( ) operation (ECONOmical operation) (Excluding MSZ-FD and MSZ-FE09/12) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermistor). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. To cancel this operation, select a different mode or press one of the following buttons in ECONO COOL operation: ECONO COOL or VANE CONTROL button.

Show 5 more labels / short text on this page
(2) Mode change · Fan speed · Down Up · High · Low
Page 12 of the Mitsumi electronic MSZ-DNA user manual — 2-7. INVERTER SYSTEM CONTROL 2-7-1. Inverter main power supply circuit
Page 12 · click to enlarge
Page 12

In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6°F (2°C), the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.

Temperature of indoor coil thermistor (°F/°C)Downward blow time (second)Horizontal blow time (second) A59/15 or less223 B59/15 to 63/17520 C63/17 to 64/18817 D64/18 to 68/201114 E68/20 to 70/211411 F70/21 to 72/22178 G72/22 to 75/24205 Hmore than 75/24232

2-7. INVERTER SYSTEM CONTROL 2-7-1. Inverter main power supply circuit

MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD MUZ-FE09/12 MSZ-GE06/09/12/15/18 MUY-GE09/12/15/18

CURRENT TRANSFORMER

DIODE MODULE1

REACTOR

U

U

NOISE FILTER CIRCUIT

RESISTOR

P

POWER SUPPLY

SMOOTHING CAPACITOR

MS

3~ V

N

W

W

RELAY

INTELLIGENT

COMPRESSOR

POWER MODULE

SWITCHING POWER TRANSISTOR

DIODE MODULE2

BOOSTER CHOPPER CIRCUIT

Function of main parts

NAMEFUNCTION INTELLIGENT POWER MODULEIt supplies 3-phase AC power to compressor. SMOOTHING CAPACITORIt stabilizes the DC voltage and supplies it to INTELLIGENT POWER MODULE. CURRENT TRANSFORMERIt measures the current of the compressor motor. DIODE MODULE 1It converts the AC voltage to DC voltage. RESISTORIt absorbs the rush current not to run into the main power supply circuit when the electricity turns ON. RELAYIt keeps the RESISTOR, which restricts rush current, short-circuited while the compressor is operating. BOOSTER CHOPPER CIRCUITDIODE MODULE 2It improves power factor. It controls the bus-bar voltage. SWITCHING POWER TRANSISTOR REACTOR
Show 5 more labels / short text on this page
+ · ~ ~ · + · + · ~ ~
Page 13 of the Mitsumi electronic MSZ-DNA user manual — REACTOR
Page 13 · click to enlarge
Page 13

MUZ-A24 MUY-A24 MUZ-D MUY-D MUZ-FE18 MUZ-GA MUY-GA MUZ-GE24 MUY-GE24

CURRENT TRANSFORMER

REACTOR

P

U

U

NOISE FILTER CIRCUIT

RESISTOR

POWER SUPPLY

SMOOTHING CAPACITOR

MS

3~ V

N

W

W

RELAY

INTELLIGENT POWER MODULE POWER FACTOR

COMPRESSOR

CORRECTION

MODULE

Function of main parts

NAME FUNCTION

INTELLIGENT POWER MODULE It supplies 3-phase AC power to compressor.

SMOOTHING CAPACITOR It stabilizes the DC voltage and supplies it to INTELLIGENT POWER MODULE.

CURRENT TRANSFORMER It measures the current of the compressor motor.

REACTOR

It rectifi es AC, controls its voltage and improves the power factor of power supply. POWER FACTOR CORRECTION MODULE

RESISTOR It absorbs the rush current not to run into the main power supply circuit when the electricity turns ON.

RELAY It keeps the RESISTOR, which restricts rush current, short-circuited while the compressor is operating.

2-7-2. Outline of main power supply circuit MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD MUZ-FE09/12 MUZ-GE09/12/15/18 MUY-GE09/12/15/18

1. At the start of operation Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup. To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR is placed in sub circuit. 2. At normal operation When AC runs into POWER P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT. After noise is eliminated from AC, it is rectifi ed to DC by DIODE MODULE 1. DC voltage, to which AC has been rectifi ed by process , is stabilized by SMOOTHING CAPACITOR and supplied to IN- TELLIGENT POWER MODULE. DC voltage, which has been stabilized in process , is converted to 3-phase AC by INTELLIGENT POWER MODULE and supplied to COMPRESSOR. CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, is used to measure the value

of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those pieces of information.

+

Page 14 of the Mitsumi electronic MSZ-DNA user manual — INTELLIGENT POWER MODULE POWER FACTOR
Page 14 · click to enlarge
Page 14
3. Purpose of PAM adoption PAM (Pulse Amplitude Modulation) has been adopted for the effi ciency improvement and the adaptation to IEC harmonic current emission standard

Outline of simple partial switching method In conventional inverter models, DIODE MODULE rectifi es AC voltage to DC voltage, SMOOTHING CAPACITOR makes its DC waveform smooth, and INTELLIGENT POWER MODULE converts its DC voltage to imitated AC voltage again in order to drive the compressor motor. However, it has been difficult to meet IEC harmonic current emission standard by above circuit because harmonic gets generated in the input current waveform and power factor gets down. The simple partial switching method with PAM, which has been adopted this time, places and utilizes BOOSTER CHOPPER CIRCUIT before rectifying AC voltage in the general passive-method converter circuit. As harmonic gets suppressed and the peak of waveform gets lower by adding BOOSTER CHOPPER CIRCUIT as mentioned above and by synchronizing the timing of switching with the zero-cross point of waveform, the input current waveform can be improved and the requirement of IEC harmonic current emission standard can be satisfi ed. Since the switching synchronized with the zero cross point, this simple partial switching method has the feature of lower en- ergy loss compared to active fi lter method. In addition, output and effi ciency is enhanced by combining with vector-controlled inverter in order to boost the voltage of power supplied to INTELLIGENT POWER MODULE.

Input current waveform without PAM Input current waveform with PAM

  • Due to the time of no electricity;
  • Power factor gets worse.
  • Harmonic gets increased.
  • Owing to the increase of energized time;
  • Power factor gets better.
  • Harmonic gets suppressed.

Release of energy stored in L.

Peak gets down.

Energized time is short in case L inductance is small.

Energized time is extended by optimization of L inductance.

No electricity runs into diode module because the voltage at both sides of smoothing capacitor is higher than input voltage.

Compulsory energizing by switching.

Input voltage · Input current

Page 15 of the Mitsumi electronic MSZ-DNA user manual — INTELLIGENT POWER MODULE POWER FACTOR
Page 15 · click to enlarge
Page 15
4. Intelligent power module

INTELLIGENT POWER MODULE consists of the following components · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from overcurrent. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIGENT POWER MODULE has a merit to make the control circuit simplify and miniaturize. 5. Elimination of electrical noise

NOISE FILTER CIRCUIT, which is formed by *CMC COILS and capacitors placed on the POWER P.C. board, eliminates electrical noise of AC power that is supplied to main power supply circuit. This circuit also prevents the electrical noise gen- erated in the inverter circuit from leaking out.

*CMC COILSCommon mode choke coils

MUZ-A24 MUY-A24 MUZ-D MUY-D MUZ-FE18 MUZ-GA MUY-GA MUZ-GE24 MUY-GE24 1. At the start of operation Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup. To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR is placed in sub circuit. 2. At normal operation When AC runs into noise filter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT. After noise is eliminated from AC, it is rectified to DC by REACTOR and POWER FACTOR CORRECTION MODULE. If the

operating frequency becomes 25 Hz or more, DC voltage rises to 370 V. DC voltage, to which has AC been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IN- TELLIGENT POWER MODULE. The DC (Bus voltage), which has been stabilized in process , is converted to 3-phase AC by INTELLIGENT POWER MODULE and supplied to COMPRESSOR. CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, is used to measure the value

of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those pieces of information. 3. Power factor improvement Booster coil reactor and POWER FACTOR CORRECTION MODULE rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. POWER FACTOR CORRECTION MODULE and reactor stabilize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Intelligent power module INTELLIGENT POWER MODULE consists of the following components. · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from over current. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIGENT POWER MODULE has a merit to make the control circuit simplified and miniaturized. 5. Elimination of electrical noise NOISE FILTER CIRCUIT, which is formed by *CMC COILS, *NMC COILS and capacitors placed on the POWER P.C. board, eliminates electrical noise of AC power that is supplied to main power supply circuit. This circuit also prevents the electrical noise generated in the inverter circuit from leaking out.

*CMC COILSCommon mode choke coils *NMC COILS: Normal mode choke coils
Page 16 of the Mitsumi electronic MSZ-DNA user manual — INTELLIGENT POWER MODULE POWER FACTOR
Page 16 · click to enlarge
Page 16

2-7-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which does not have Hall element. In short, the motor is sensorless. However, it is necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor effi ciently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by unenergized stator. Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection when the voltage of supplied power is impressed. So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start & end of one heap in one waveform cycle (180°) when the voltage is impressed. However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase current waveform smoother (sine wave) in order to drive the motor more effi ciently and smoothly.

  • 2-7-4. Characteristics of sine wave control in case of brushless DC motor
  • Although ordinary 3-phase induction motor requires energy to excite the magnetic fi eld of rotor, brushless DC motor does not need it. So, higher effi ciency and torque are provided.
  • This control provides the most effi cient waveform corresponding to the rotational speed of compressor motor.
  • The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner can be operated with less energy is longer than conventional models. This can save annual electric consumption.
  • Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.
  • Since the response and effi ciency of motor are enhanced in sine wave control, fi ner adjustment can be provided.

DC Motor AC Motor

Rotor Permanent magnet is embedded. Excited by magnetic fi eld of stator

Rotor Position Signal Necessary Unnecessary

In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it does not require energy to excite the rotor

like AC motor does. However, it is necessary to control the frequency of 3-phase AC current supplied to the stator accord- ing to the polar direction of magnet embedded in the rotor so as to drive the motor effi ciently. Controlling 3-phase AC current frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be detected. 2-7-5. Control Method of Rotational speed Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo- tor, locates the rotor position from the detected value, and decides if voltage should be impressed and if frequency should be changed. Compared to the conventional control and rotor position detection method, sine wave control can provide fi ner adjustment of the voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.

Page 17 of the Mitsumi electronic MSZ-DNA user manual — INTELLIGENT POWER MODULE POWER FACTOR
Page 17 · click to enlarge
Page 17

2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.

2. Maximum/minimum frequency in each operation mode.

Operational frequency (Hz) COOL HEAT (MUZ) DRY Minimum Maximum Minimum Maximum Minimum Maximum MUZ-A09 32 70 32 76 32 57 MUZ-A12 32 73 32 71 32 57 MUZ-A15 MUY-A15 10 82 15 93 10 68 MUZ-A17 MUY-A17 10 87 15 93 10 68 MUZ-A24 MUY-A24 15 110 15 108 15 102 MUZ-FD09 10 52 10 100 10 41 MUZ-FD12 10 62 10 100 10 41 MUZ-FE09 10 52 10 100 10 41 MUZ-FE12 10 62 10 100 10 41 MUZ-FE18 26 120 26 124 26 120 MUZ-D30 20 84 20 87 20 83 MUZ-D36 20 91 20 94 20 83 MUY-D30 20 79 — — 20 79 MUY-D36 20 92 — — 20 79 MUZ-GA24 MUY-GA24 15 101 15 108 15 101 MUZ-GE09 MUY-GE09 28 93 30 105 28 48 MUZ-GE12 MUY-GE12 20 98 30 98 30 55 MUZ-GE15 MUY-GE15 15 90 15 102 15 54 MUZ-GE18 MUY-GE18 15 98 15 108 15 83 MUZ-GE24 MUY-GE24 26 120 26 124 26 120

The operation frequency in COOL mode is restricted by the upper limit frequency after 1 hour or 0.5 ~ 1 hour as shown

below for dew prevention. It is rated frequency or less.

Upper limit frequency Rated frequency or less

1 hour or 0.5~1 hour

Applied model · Maximum frequency · Time

Page 18 of the Mitsumi electronic MSZ-DNA user manual — ON
Page 18 · click to enlarge
Page 18

2-9. EXPANSION VALVE CONTROL (LEV CONTROL)

(1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening degrees set for each opera- tional frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air conditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge tempera- ture (Shell temperature) of the compressor, developing the unit's performance.

Minimum33 pulses ( MUZ-A09/12/15/17 MUY-A15/17 )

59 pulses (MUZ-A24 MUY-A24 MUZ-GA MUY-GA) 54 pulses (MUZ-FD MUZ-FE MUZ-GE MUY-GE) 58 pulses (MUZ-D MUY-D) Maximum: 500 pulses

Actuating speed Open: 40 pulses/second Close: 90 pulses/second Opening degree adjustment LEV opening degree is always adjusted in opening direction. (When reduc- ing the opening degree, LEV is once over-closed, and then adjusted to the proper degree by opening.

Unit OFF LEV remains at maximum opening degree (reaches maximum opening degree approximate in 15 minutes after compressor stops) Remote controller ON LEV is positioned. (First full-closed at zero pulses and then positioned.) During 1 to 15 minutes after compressor starts

LEV is fixed to standard opening degree according to operational frequen- cy of compressor. More than about 15 minutes have passed since compressor start-up

LEV opening degree is corrected to get target discharge temperature of compressor. (For lower discharge temperature than target temperature, LEV is correct- ed in closing direction.) (For higher discharge temperature than target temperature, LEV is cor- rected in opening direction.)

It may take more than 30 minutes to reach target temperature, depend- ing on operating conditions. Thermostat OFF LEV is adjusted to exclusive opening degree for thermostat OFF. Thermostat ON LEV is controlled in the same way as that after the compressor has started up. Defrosting in HEAT mode LEV is adjusted to open 500 pulses

Air conditioner OFF (thermostat off)

Opening degree is corrected according to discharge temperature. (Refer to (3))

Commanded to open Standard opening degree

ON

Show 12 more labels / short text on this page
Standard specification · Control range · General operation · (2) Time chart · Air conditioner ON · Positioning · LEV opening degree · About 15 minutes · Time · Operational frequency · of the compressor · OFF Time
Page 19 of the Mitsumi electronic MSZ-DNA user manual — COOL / HEAT ( MUZ ) °F/°C
Page 19 · click to enlarge
Page 19

F E D C B A

30 50 70 90 110 130 23 38 53 69 84 99 (Hz) (Hz)

(Other models) (MUZ-FE18 MUZ-GE24 MUY-GE24)

Operational frequency of the compressor

(a) Reference value of target discharge temperature

COOL / HEAT ( MUZ ) °F/°C

Applied model A B C D E F

MUZ-A09/12 COOL 122/50 127/53 140/60 151/66 158/70 158/70 HEAT 113/45 126/52 138/59 154/68 169/76 169/76

MUZ-A15/17 MUY-A15/17 COOL 129/54 136/58 147/64 158/70 158/70 158/70 HEAT 120/49 136/58 151/66 165/74 180/82 185/85

MUZ-A24 MUY-A24 MUZ-GA MUY-GA COOL 140/60 140/60 140/60 145/63 147/64 153/67 HEAT 140/60 145/63 149/65 153/67 158/70 158/70

MUZ-FD MUZ-FE09/12 COOL 120/49 131/55 142/61 153/67 162/72 169/76 HEAT 109/43 124/51 138/59 156/69 167/75 176/80

MUZ-FE18 MUZ-GE24 MUY-GE24 COOL 131/55 142/61 151/66 162/72 171/77 178/81 HEAT 115/46 133/56 151/66 167/75 181/83 187/86

MUZ-D MUY-D COOL 126/52 135/57 149/65 167/75 183/84 187/86 HEAT 131/55 140/60 149/65 154/68 162/72 167/75

MUZ-GE09 MUY-GE09 COOL 126/52 136/58 149/65 153/67 158/70 160/71 HEAT 109/43 122/50 131/55 138/59 149/65 156/69

MUZ-GE12 MUY-GE12 COOL 127/53 140/60 147/64 153/67 162/72 169/76 HEAT 109/43 124/51 138/59 156/69 167/75 176/80

MUZ-GE15 MUY-GE15 COOL 120/49 131/55 147/64 153/67 162/72 169/76 HEAT 109/43 124/51 138/59 156/69 167/75 176/80

MUZ-GE18 MUY-GE18 COOL 135/57 140/60 144/62 153/67 165/74 178/81 HEAT 140/60 149/65 158/70 167/75 167/75 167/75

In COOL operation, the indoor coil thermistors (main and sub) sense temperature ununiformity (super heat) at the heat exchanger, and when temperature difference develops, the indoor coil thermistors adjust LEV opening degree to get approximate 18°F (10°C) lower temperature than the target temperature in the table above, thus diminishing super heat.

(3) Control data · Target discharge temperature

Page 20 of the Mitsumi electronic MSZ-DNA user manual — 69.8°F (21°C)
Page 20 · click to enlarge
Page 20

2-10. PRE-HEAT CONTROL MUZ-FD MUZ-FE MUZ-GE 1. Outline Compressor is energized to improve the start-up of compressor at a low outside temperature even when compressor is stopped. 2. Pre-heat control

ON

OFF

ON

OFF

68°F (20°C)

Pre-heat control ON condition (1) Compressor is not operating. (However, pre-heat control is still OFF for 30 minutes after compressor is stopped, regardless

30 minutes 1 hour

of the outside temperature.) (2) Outside temperature is 68°F (20°C) or below. Outside temperature is monitored hourly, and when outside temperature is

68°F (20°C) or below, pre-heat control is turned ON. When pre-heat control is turned ON, compressor is energized about 50 W (40-60 W). (Compressor and fan are not operated.)

MUZ-D MUY-D 1. Outline The compressor is energized even while it is not operating. This is to generate heat at the winding to improve the compressor's start-up condition.

69.8°F (21°C)

30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 15 minutes

15 minutes 30minutes 30minutes

Stop operation Start operation

When the defrost thermistor reads 69.8°F(21°C) or more

2. Pre-heat control ON condition (1) Pre-heat control is turned ON for 15 or 30 minutes after the breaker is turned ON. (2) 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This

is repeated as shown in the graph until the breaker is turned OFF. When the defrost thermistor reads less than 69.8°F (20°C), pre-heat control is ON for 30 minutes. When the defrost thermistor reads 69.8°F (21°C) or more, pre-heat control is ON for 15 minutes. NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF. Compressor uses 50 W when pre-

heat control is turned ON.

Show 8 more labels / short text on this page
Compressor · Pre-heat control · Outside temperature · Power ON OFF · Compressor ON OFF · Defrost thermistor · Pre-heat ON OFF · Breaker ON
Page 21 of the Mitsumi electronic MSZ-DNA user manual — REACTOR
Page 21 · click to enlarge
Page 21

3 MXZ MICROPROCESSOR CONTROL

3-1. INVERTER SYSTEM CONTROL

3-1-1. Inverter main power supply circuit

CURRENT TRANSFORMER

REACTOR

P

U

U

NOISE FILTER CIRCUIT

POWER SUPPLY

RESISTOR

SMOOTHING CAPACITOR

MS

3~ V

N

W

W

RELAY

INTELLIGENT POWER MODULE POWER FACTOR

COMPRESSOR

CORRECTION

MODULE

Function of main parts

NAME FUNCTION

INTELLIGENT POWER MODULE It supplies 3-phase AC power to compressor.

SMOOTHING CAPACITOR It stabilizes the DC voltage and supplies it to INTELLIGENT POWER MODULE.

CURRENT TRANSFORMER It measures the current of the compressor motor.

REACTOR

It rectifi es AC, controls its voltage and improves the power factor of power supply. POWER FACTOR CORRECTION MODULE

RESISTOR It absorbs the rush current not to run into the main power supply circuit when the power is turned ON.

RELAY It keeps the RESISTOR, which restricts rush current, short-circuited while the compressor is operating.

3-1-2. Outline of main power supply circuit

1. At the start of operation Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup. To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR is placed in sub circuit. 2. At normal operation When AC runs into noise fi lter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT. After noise is eliminated from AC, it is rectifi ed to DC by REACTOR and POWER FACTOR CORRECTION MODULE. If the

operating frequency becomes 25 Hz or more, DC voltage rises to 370 V. DC voltage, to which has AC been rectifi ed by process , is stabilized by SMOOTHING CAPACITOR and supplied to IN- TELLIGENT POWER MODULE. The DC (Bus voltage), which has been stabilized in process , is converted to 3-phase AC by INTELLIGENT POWER MODULE and supplied to COMPRESSOR. CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, is used to measure the value

of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those pieces of information.

+

Page 22 of the Mitsumi electronic MSZ-DNA user manual — 3 MXZ MICROPROCESSOR CONTROL
Page 22 · click to enlarge
Page 22

3. Power factor improvement Booster coil reactor and POWER FACTOR CORRECTION MODULE rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. POWER FACTOR CORRECTION MODULE and reactor stabilize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Intelligent power module INTELLIGENT POWER MODULE consists of the following components. · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from over current. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIGENT POWER MODULE has a merit to make the control circuit simplifi ed and miniaturized. 5. Elimination of electrical noise NOISE FILTER CIRCUIT, which is formed by *CMC COILS, *NMC COILS and capacitors placed on the P.C. board, eliminates electrical noise of AC power that is supplied to main power supply circuit. This circuit also prevents the electrical noise gener- ated in the inverter circuit from leaking out. *CMC COILS: Common mode choke coils *NMC COILS: Normal mode choke coils

3-1-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which does not have Hall element. In short, the motor is sensorless. However, it is necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor effi ciently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by unenergized stator. Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection when the voltage of supplied power is impressed. So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start and end of one heap in one waveform cycle (180°) when the voltage is impressed. However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase current waveform smoother (sine wave) in order to drive the motor more effi ciently and smoothly.

  • 3-1-4. Characteristics of sine wave control in case of brushless DC motor
  • Although ordinary 3-phase induction motor requires energy to excite the magnetic fi eld of rotor, brushless DC motor does not need it. So, higher effi ciency and torque are provided.
  • This control provides the most effi cient waveform corresponding to the rotational speed of compressor motor.
  • The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner can be operated with less energy is longer than conventional models. This can save annual electric consumption.
  • Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.
  • Since the response and effi ciency of motor are enhanced in sine wave control, fi ner adjustment can be provided.

DC Motor AC Motor

Rotor Permanent magnet is embedded. Excited by magnetic fi eld of stator

Rotor Position Signal Necessary Unnecessary

In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it does not require energy to excite the rotor

like AC motor does. However, it is necessary to control the frequency of 3-phase AC current supplied to the stator accord- ing to the polar direction of magnet embedded in the rotor so as to drive the motor effi ciently. Controlling 3-phase AC current frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be detected.

3-1-5. Control Method of Rotational speed Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo- tor, locates the rotor position from the detected value and decides if voltage should be impressed and if frequency should be changed. Compared to the conventional control and rotor position detection method, sine wave control can provide fi ner adjustment of the voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.

Page 23 of the Mitsumi electronic MSZ-DNA user manual — 3 MXZ MICROPROCESSOR CONTROL
Page 23 · click to enlarge
Page 23

3-2. EXPANSION VALVE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit.

Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulses in 15 minutes

When outdoor unit is operating, some indoor units stop and some operate.

COOL5 pulses (full closed) HEAT: ( MXZ-2A / 3A30NA/2B ): 140 pulses (slightly opened)

: (MXZ-3A30NA- 1 /4A/3B/4B): 100 → 59 pulses

When the outdoor unit operates (When the other indoor unit operates): 5 pulses When outdoor unit stops. (When the other indoor unit stops or thermo OFF): Maintain LEV opening before stop → 500 pulses in 15 minutes

Thermostat OFF in COOL or DRY mode

  • LEV opening for each indoor unit is determined by adding adjustment according to the number of operating unit and the capacity class to standard opening, based on the operation frequency: e.g.) Opening 130 pulses in standard opening 1 → Minimum 80 pulses/Maximum 205 pulses (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)
  • After starting operation, adjustment according to intake super heat, discharge temperature is included in standard opening. 1 NOTE : LEV opening in each frequency at DRY operation and COOL operation is the

Thermostat ON in COOL or DRY mode

same. However, velocity and compressor operation frequency controls are differ- ent. See 3-3. OPERATIONAL FREQUENCY RANGE (As far as the indoor unit velocity control goes, refer to DRY operation in MICRO- PROCESSOR CONTROL in indoor unit.)

  • When the outdoor unit operates. (When the other indoor unit operates): 140 pulses
  • When the outdoor unit stops. (When the other indoor unit stops or thermo OFF): Maintain LEV opening before stop → 500 pulses in 15 minutes “

Thermostat OFF in HEAT mode

  • LEV opening for each indoor unit is determined by adding adjustment according to the number of operating unit and the capacity class to standard opening, based on the operation frequency: e.g.) Opening 120 pulses in standard opening 1 → Minimum 70 pulses/Maximum 165 pulses (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)
  • After starting operation, opening becomes the one that adjustment according to discharge temperature was added to basic opening. 1 “

Thermostat ON in HEAT mode

1 LEV opening when the outdoor unit is operating: Upper limit 500 pulses, Lower limit 53 pulses (MXZ-2A/3A30NA/2B)/59 pulses (MXZ-3A30NA- 1 /4A/3B/4B).

Page 24 of the Mitsumi electronic MSZ-DNA user manual — <MXZ-3A30NA>
Page 24 · click to enlarge
Page 24

MXZ-2A20NA/3A30NA

The table below shows the role of Exclusive LEV and Receiver LEV in each operation mode.

COOL Exclusive LEV ○ Receiver LEV × × ○ ○ ○

HEAT Exclusive LEV × ○ ○ ○ — Receiver LEV ○ × ○ ○ —

LEV

LEV

(MXZ-3A30NA)

In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger, and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the super heat. This action is called Evaporation Temperature Protection.

The opening pulse of the Receiver LEV is fixed to the standard No.3 in cooling operation, and so is that of each Exclusive LEV in heating operation. However the opening pulse will be changed to the standard No.4 or No.5 when the discharge temperature protection or high- pressure protection is working.

In addition to that, it will also be changed to standard No.2 or No.1 when the opening pulse of the each Exclusive LEV becomes 100 pulse or less in cooling operation or so does that of Receiver LEV in heating operation.

<MXZ-2A20NA>

LEV opening (pulse) COOL HEAT

1 unit 2 units 1 unit 2 units

Standard No.

1 200 150 120 120 2 300 320 140 140 3 400 360 160 160 4 450 410 220 220 5 500 500 280 280

<MXZ-3A30NA>

LEV opening (pulse) COOL HEAT

1 unit 2 units 3 units 1 unit 2 units 3 units

Standard No.

1 150 250 2 250 320 320 300 300 300 3 350 360 370 450 380 380 4 400 410 420 460 400 390 5 450 460 470 470 450 440

Show 18 more labels / short text on this page
Circulation Amount · Discharge Temperature · High Pressure · Evaporation · Control Capacity Distribution · Temperature Protection · Protection · Protection · Indoor heat · Exclusive · Outdoor heat exchanger · exchanger · Receiver · Receiver · Number of · operating indoor units · Number of · operating indoor units
Page 25 of the Mitsumi electronic MSZ-DNA user manual — MXZ-3A30NA
Page 25 · click to enlarge
Page 25

Determination of LEV standard opening in each indoor unit

  • The standard opening is on the straight line, which connects an each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below. (LEV opening is controlled in proportion to the operation frequency.) NOTE : Opening is adjusted at the standard opening according to the indoor unit conditions.
  • However, inclination of standard opening in each point of opening does not change with the original curve.
  • Add opening provided in Difference in capacity in the table below to the standard opening from 1 to 8, when capacity of the indoor unit is excluding code 1.
  • Add opening provided in Difference in operation number in the table below to determined LEV opening for each indoor unit, when 2 or 3 indoor units are operated at the same time. NOTE : Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual driving out-

put opening is in a range from 59 to 500 pulses.

01 02 03 04 05 06 07 08 09 10

23 54 69 84 100 115 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A/2B MXZ-3A/4A 23

Compressor operating frequency (Hz)

MXZ-2A20NA

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 120 130 136 146 156 160 170 180 190 200 HEAT 100 110 120 130 146 160 170 180 190 200

Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 COOL 3 6 9 12 15 25 35 -20 HEAT 3 6 9 52 55 65 75 0

MXZ-3A30NA

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 126 130 134 138 140 142 182 228 296 310 HEAT 140 146 150 170 180 200 224 244 272 280

Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 3 COOL 3 6 9 12 15 25 35 -20 -30 HEAT 3 6 9 52 55 65 75 0 0

4Hz · LEV Opening (code)

Page 26 of the Mitsumi electronic MSZ-DNA user manual — 2 COOL -20 HEAT 30
Page 26 · click to enlarge
Page 26

MXZ-2A20NA1 , 2 MXZ-2B20NA MXZ-2B20NA1 Exclusive LEV

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 120 130 136 146 156 160 170 180 190 200 HEAT 248 248 258 266 274 280 286 292 300 306

Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 COOL 3 6 9 12 15 25 35 -20 HEAT 3 6 9 52 55 65 75 30

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 140 150 160 170 180 190 200 HEAT 80 84 90 110 120 130 140 150 160 170

Operation number Difference in operation number

2 COOL -20 HEAT 30

MXZ-3A30NA1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 126 130 134 138 150 160 170 180 190 200 HEAT 248 248 258 266 274 280 286 292 300 306

Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 3 4(MXZ-4A/4B) COOL 3 6 9 12 15 25 35 -20 -30 -30 HEAT 3 6 9 52 55 65 75 -4 -8 -12

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 270 280 290 300 310 320 330 340 350 360 HEAT 140 152 160 170 180 200 224 244 274 280

Operation number Difference in operation number

2 3 4(MXZ-4A/4B) COOL 28 56 84 HEAT -45 -60 -60

Capacity code 3 4 7 9 10 12 Indoor unit 06 09 12 15 17 24

Receiver LEV · Exclusive LEV · Receiver LEV

Page 27 of the Mitsumi electronic MSZ-DNA user manual — MXZ-3A30NA
Page 27 · click to enlarge
Page 27
  • COOL DRY HEAT Discharge temperature
  • Each correction
  • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermistor) 1
  • (Main indoor coil thermistor - Sub indoor coil thermistor)

1 Perform this, when number of operation units is 2 units or more. (MXZ-2A20NA and MXZ-3A30NA only) 2 Correct the LEV opening by discharge temperature.

(1) LEV opening correction by discharge temperature

The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor.

MXZ-2A20NA

Target discharge temperature (°F/°C) COOL HEAT Number of operating unit 1 unit 2 units 1 unit 2 units Minimum ~ 23 95/35 136.4/58 122/50 122/50 24 ~ 38 104/40 140/60 132.8/56 122/50 39 ~ 54 120.2/49 149/65 140/60 132.8/56 55 ~ 69 136.4/58 154.4/68 140/60 140/60 70 ~ 85 149/65 158/70 140/60 140/60 86 ~ Maximum 158/70 158/70 140/60 140/60

MXZ-2A20NA1 , 2 MXZ-2B20NA MXZ-2B20NA1

Target discharge temperature (°F/°C) COOL HEAT Number of operating unit 1 unit 2 units 1 unit 2 units Minimum ~ 23 95/35 136.4/58 122/50 122/50 24 ~ 38 104/40 140/60 132.8/56 122/50 39 ~ 54 120.2/49 149/65 140/60 132.8/56 55 ~ 69 136.4/58 154.4/68 145.4/63 140/60 70 ~ 85 149/65 158/70 150.8/66 140/60 86 ~ Maximum 158/70 158/70 152.6/67 140/60

MXZ-3A30NA

Target discharge temperature (°F/°C) COOL HEAT Number of operating unit 1 unit 2 units 3 units 1 unit 2 unit 3 units Minimum ~ 14 95/35 131/55 134.6/57 125.6/52 143.6/62 122/50 15 ~ 23 104/40 131/55 134.6/57 136.4/58 150.8/66 131/55 24 ~ 32 120.2/49 136.4/58 145.4/63 149/65 165.2/74 140/60 33 ~ 41 136.4/58 140/60 149/65 154.4/68 172.4/78 152.6/67 42 ~ 50 149/65 149/65 158/70 154.4/68 172.4/78 161.6/72 51 ~ 59 154.4/68 154.4/68 163.4/73 154.4/68 172.4/78 168.8/76 60 ~ 68 158/70 158/70 167/75 154.4/68 172.4/78 168.8/76 69 ~ 77 167/75 163.4/73 176/80 154.4/68 172.4/78 168.8/76 78 ~ 86 167/75 167/75 179.6/82 154.4/68 172.4/78 168.8/76 87 ~ Maximum 167/75 176/80 179.6/82 172.4/78 172.4/78 168.8/76

Show 7 more labels / short text on this page
<Correction> · Operation frequency · of compressor (Hz) · Operation frequency · of compressor (Hz) · Operation frequency · of compressor (Hz)
Page 28 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2A20NA
Page 28 · click to enlarge
Page 28

MXZ-3A30NA1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA

Target discharge temperature (°F/°C) COOL HEAT Number of operating unit

1 unit 2 units 3 units 4 units (MXZ-4A/4B) 1 unit 2 unit 3 units 4 units (MXZ-4A/4B) Minimum ~ 14 95/35 131/55 134.6/57 140/60 125.6/52 143.6/62 122/50 122/50 15 ~ 23 107.6/42 131/55 134.6/57 140/60 136.4/58 150.8/66 131/55 122/50 24 ~ 32 120.2/49 136.4/58 145.4/63 140/60 149/65 165.2/74 140/60 122/50 33 ~ 41 136.4/58 140/60 149/65 143.6/62 154.4/68 172.4/78 152.6/67 122/50 42 ~ 50 149/65 149/65 158/70 149/65 154.4/68 172.4/78 161.6/72 131/55 51 ~ 59 154.4/68 154.4/68 163.4/73 158/70 154.4/68 172.4/78 168.8/76 140/60 60 ~ 68 158/70 158/70 167/75 158/70 154.4/68 172.4/78 168.8/76 140/60 69 ~ 77 167/75 163.4/73 176/80 161.6/72 154.4/68 172.4/78 168.8/76 140/60 78 ~ 86 167/75 167/75 179.6/82 161.6/72 154.4/68 172.4/78 168.8/76 140/60 87 ~ Maximum 167/75 176/80 179.6/82 161.6/72 172.4/78 172.4/78 168.8/76 140/60

Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.

MXZ-2A MXZ-2B

Discharge temperature (°F/°C) LEV opening correction (pulse)

COOL HEAT More than Target discharge temperature+18/10 5 8 Target discharge temperature + 18/10 to Target discharge temperature + 9 /5 4 3 Target discharge temperature + 9/5 to Target discharge temperature + 3.6/2 2 1 Target discharge temperature + 3.6/2 to Target discharge temperature - 3.6/2 0 0 Target discharge temperature - 3.6/2 to Target discharge temperature - 9/5 -1 -1 Target discharge temperature - 9/5 to Target discharge temperature - 18/10 -3 -2 Target discharge temperature - 18/10 or less -4 -3

MXZ-3A MXZ-4A MXZ-3B MXZ-4B

Discharge temperature (°F/°C) LEV opening correction (pulse)

COOL HEAT More than Target discharge temperature + 21.6/12 4 6 Target discharge temperature + 21.6/12 to Target discharge temperature + 9/5 2 2 Target discharge temperature + 9/5 to Target discharge temperature + 5.4/3 1 1 Target discharge temperature + 5.4/3 to Target discharge temperature - 5.4/3 0 0 Target discharge temperature - 5.4/3 to Target discharge temperature - 9/5 -1 -1 Target discharge temperature - 9/5 to Target discharge temperature - 21.6/12 -3 -2 Target discharge temperature - 21.6/12 or less -8 -8

(2) Separate correction (COOL,DRY)

(Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all.

Calculate each super heat of the unit from the expression below;

(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature) Separate correction is performed according to each super heat in the table below.

MXZ-2A20NA

MXZ-3A30NA

Superheat (°F/°C) LEV opening correction (pulse) More than 16.2/9 3 10.8/6 to 16.2/9 2 5.4/3 to 10.8/6 1 5.4/3 or less 0

Superheat (°F/°C) LEV opening correction (pulse) More than 16.2/9 12 10.8/6 to 16.2/9 8 5.4/3 to 10.8/6 4 5.4/3 or less 0

Operation frequency · of compressor (Hz)

Page 29 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2A20NA2
Page 29 · click to enlarge
Page 29

b) Correct the LEV separately by temperature difference “ ∆RT” between main/sub indoor coil thermistor.

∆RT (°F/°C) LEV opening correction (pulse) 10.8/6 ∆RT 2 7.2/4 ∆RT < 10.8/6 1 ∆RT < 7.2/4 1

In addition, decrease the target discharge temperature corresponding ∆RT.

∆ RT (°F/°C) Temperature to be decreased (°F/°C) 10.8/6 ∆RT 18/10 7.2/4 ∆RT< 10.8/6 9/5 ∆RT < 7.2/4 9/5

3-3. OPERATIONAL FREQUENCY RANGE

MXZ-2A20NA

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

4 20 65 25 48 92 92 7 20 85 30 48 92 92 9,10 20 100 75 48 100 100 12 20 100 75 48 100 100

8 ~ 10 30 105 52 58 112 100 11 ~ 13 30 105 52 58 112 100 14 ~ 16 30 105 52 58 112 100 17 ~ 20 105 100 58 112 100

MXZ-2A20NA1

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

4 20 65 35 48 92 92 7 20 85 34 48 92 92 9,10 20 93 75 48 92 92 12 20 93 75 48 92 92

8 ~ 10 30 93 52 58 110 101 11 ~ 13 30 93 52 58 110 101 14 ~ 16 30 93 52 58 110 101 17 ~ 30 93 93 58 110 101

MXZ-2A20NA2

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

4 20 65 25 30 92 92 7 20 85 34 30 92 92 9,10 20 93 75 30 92 92 12 20 93 75 30 92 92

8 ~ 10 40 93 53 58 112 100 11 ~ 13 40 93 53 58 112 100 14 ~ 16 40 93 53 58 112 100 17 ~ 40 93 93 58 112 100

Number of operating · Number of operating · Number of operating

Page 30 of the Mitsumi electronic MSZ-DNA user manual — MXZ-3A30NA1 MXZ-4A36NA
Page 30 · click to enlarge
Page 30

MXZ-2B20NA

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

3, 4 20 65 25 30 92 92 7 20 85 34 30 92 92 9, 10 20 93 75 30 92 92 12 20 93 75 30 92 92

2 ~ 7 30 93 53 58 112 100 8 ~ 10 30 93 53 58 112 100 11 ~ 13 30 93 53 58 112 100 14 ~ 16 30 93 53 58 112 100 17 ~ 30 93 93 58 112 100

MXZ-2B20NA1

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

3, 4 20 65 30 30 92 92 7 20 85 30 30 92 92 9, 10 20 93 38 30 92 92 12 20 93 62 30 92 92

5 ~ 7 30 93 58 58 112 99 8 ~ 10 30 93 58 58 112 99 11 ~ 13 30 93 58 58 112 99 14 ~ 16 30 93 58 58 112 99 17 ~ 30 93 58 58 112 99

MXZ-3A30NA

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

4 15 58 20 22 48 48 7 15 58 25 22 48 48 9,10 15 62 44 22 62 58 12 15 68 44 22 90 58

8 ~ 10 24 80 31 35 70 58 11 ~ 13 24 80 31 35 90 58 14 ~ 16 24 80 31 35 94 58 17 ~ 24 80 59 35 94 58 3 12 ~ 52 90 65 39 94 58

MXZ-3A30NA1 MXZ-4A36NA

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

4 25 58 25 20 70 58 7 25 58 25 20 70 58 9,10 25 71 25 20 80 58 12 25 80 35 20 80 58

8 ~ 10 25 80 31 20 80 58 11 ~ 13 25 80 31 20 80 58 14 ~ 16 25 80 42 20 80 58 17 ~ 25 80 42 20 80 58 3 (MXZ-3A) 12 ~ 25 80 52 20 80 58 3 (MXZ-4A) 12 ~ 25 90 52 20 103 58 4 (MXZ-4A) 16 ~ 25 90 52 20 113 58

Show 4 more labels / short text on this page
Number of operating · Number of operating · Number of operating · Number of operating
Page 31 of the Mitsumi electronic MSZ-DNA user manual — MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA
Page 31 · click to enlarge
Page 31

MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost

3,4 15 58 22 25 70 70 7 15 58 22 25 70 70 9,10 15 71 31 25 80 80 12 15 80 42 25 80 80

5 ~ 7 25 80 35 35 80 80 8 ~ 10 25 80 35 35 80 80 11 ~ 13 25 80 35 35 80 80 14 ~ 16 25 80 35 35 80 80 17 ~ 25 80 52 35 80 80 3 (MXZ- 3B) 9 ~ 52 80 52 39 80 80 3 (MXZ-4B) 9 ~ 52 90 52 39 103 80 4 (MXZ-4B) 12 ~ 62 90 70 52 113 80

3-4. HEAT DEFROSTING CONTROL (1) Starting conditions of defrosting

When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F (-3°C) or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min-

utes). c) More than 5 minutes have passed since the start-up of the compressor.

The defrost interval is decided by the previous defrosting time. The next defrost interval extends or shortens 0-20

minutes compared with the previous defrost interval. (2) Releasing conditions of defrosting

Defrosting is released when any one of the following conditions is satisfied: a) The defrost thermistor continues to read 50.7°F (10.4°C). b) Defrosting time exceeds 10 minutes. c) Any other mode than HEAT mode is set during defrosting.

3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera- ture thermistor.

(1) Compressor ON/OFF When temperature of the discharge temperature thermistor exceeds 240.8°F (116°C), the control stops the compressor. When temperature of the discharge temperature thermistor is 176°F (80°C) (2A/3A30NA/2B)/ 212°F (100°C) (3A30NA-

1 /4A/3B/4B) or less, the controls starts the compressor. (2) Compressor operation frequency When temperature of the discharge temperature thermistor is expected to be higher than 240.8°F (116°C), the control decreases 12 Hz from the current frequency. When temperature of the discharge temperature thermistor is expected to be higher than 231.8°F (111°C) and less than 240.8°F (116°C), the control decreases 6 Hz from the current frequency. When temperature of the discharge temperature thermistor is expected to be higher than 219.2°F (104°C) and less than 231.8°F (111°C), the control is set at the current frequency.

Number of operating

Page 32 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2B20NA1 MXZ-3B MXZ-4B
Page 32 · click to enlarge
Page 32

3-6. OUTDOOR FAN CONTROL Fan speed is switched according to the number of operating indoor unit and the compressor frequency.

MXZ-2B20NA

Up Down Fan speed

Down Up MXZ-2B20NA 30 40

Compressor frequency Min. Max.

Or, the indoor coil thermistor is 113 ˚F (45°C) or less on HEAT operation, fan speed is back to normal.

MXZ-2B20NA1 MXZ-3B MXZ-4B

COOL Fan speed changes so that the condensing temperature stays within the target range.

Revolution per minutes (rpm)

MXZ-2B20NA1 MXZ-3B MXZ-4B

1 100 100 2 150 150 3 200 200 4 250 250 5 300 300 6 350 350 7 400 400 8 450 450 9 500 500 10 550 550 11 600 600 12 650 650 13 700 700 14 750 750

Frequency (Hz) Target condensing temperature (°F/°C) ~24 87.8/31-95.0/35 25~34 91.4/33-98.6/37 35~44 95.0/35-102.2/39 45~54 98.6/37-105.8/41 55~64 98.6/37-105.8/41 65~ 98.6/37-105.8/41

HEAT Fan speed is switched according to the compressor frequency.

Up Down Fan speed

MXZ-2B20NA- 1 MXZ-3B MXZ-4B Up 30 50 Down 23 40

Compressor frequency Min. Max.

Show 8 more labels / short text on this page
Compressor frequency (Hz) · High · Low · Fan speed · Compressor speed (Hz) · Fan speed · High · Low
Page 33 of the Mitsumi electronic MSZ-DNA user manual — -1.8°F -1.35°F (-1°C) (-0.75°C)
Page 33 · click to enlarge
Page 33

3-7. PRE-HEAT CONTROL MXZ-2A20NA- 1 , 2 MXZ-3A30NA- 1 MXZ-4A36NA MXZ-2B20NA MXZ-2B20NA- 1 MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA

The compressor is energized even while it is not operating. This is to generate heat at the winding to improve the compressor's start-up condition.

69.8°F (21°C)

30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 15 minutes

15 minutes 30minutes 30minutes

Stop operation Start operation

When the defrost thermistor reads 69.8°F(21°C) or more

1. Pre-heat control is turned ON for 15 or 30 minutes, after the breaker is turned ON. 2. 30 minutes after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF.

When the defrost thermistor reads less than 69.8°F (21°C), pre-heat control is ON for 30 minutes. When the defrost thermistor reads 69.8°F (21°C) or more, pre-heat control is ON for 15 minutes.

3-8. COOL OPERATION

1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat

ON -1.8°F(-1°C) or more OFF less than -1.8°F(-1°C)

-1.8°F -1.35°F (-1°C) (-0.75°C)

2. Coil frost prevention The compressor operational frequency is controlled to prevent the indoor heat exchanger temperature from falling excessively. Compressor is turned OFF for 5 minutes when temperature of indoor coil thermistor continues 37.4°F (3°C) or less for 5 minutes or more.
Show 5 more labels / short text on this page
Power ON OFF · Compressor ON OFF · Defrost thermistor · Pre-heat ON OFF · Breaker ON
Page 34 of the Mitsumi electronic MSZ-DNA user manual — 1.8°F (1°C)
Page 34 · click to enlarge
Page 34

3-9. DRY OPERATION

1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat

ON -3.6°F(-2°C) or more OFF less than -3.6°F(-2°C)

-3.6°F -1.35°F (-2°C) (-0.75°C)

2. Coil frost prevention Coil frost prevention is as same as COOL mode. (3-8.2.)

3-10. HEAT OPERATION

1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

MXZ-2A/3A/4A

ON less than 3.6°F(2°C) OFF 3.6°F(2°C) or more 3.15°F (1.75°C)

3.6°F (2°C)

MXZ-2B/3B/4B

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

ON less than 3.6°F(2°C) OFF 3.6°F(2°C) or more 1.35°F (0.75°C)

1.8°F (1°C)

2. High pressure protection In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor operational frequency is controlled to prevent the condensing pressure from increasing excessively.

Thermostat · Thermostat

Page 35 of the Mitsumi electronic MSZ-DNA user manual — 4.5°F (2.5°C) 1.8°F (1°C)
Page 35 · click to enlarge
Page 35

4 MFZ MICROPROCESSOR CONTROL

4-1. COOL ( ) OPERATION

1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERATION (3-8.1.).
2. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat's OFFON. In AUTO the fan speed is as follows.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)

5.4°F (3°C) 1.8°F (1°C)

3.15°F (1.75°C)

3. Coil frost prevention Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERATION (3-8.2.).

4-2. DRY ( ) OPERATION The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.

Set temperature and initial room temperature in dry mode

°F

50 59 68 77 86 95

°F

1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, DRY OPERATION (3-9.1.).
2. Indoor fan speed control Indoor fan operates at the set speed by FAN SPEED CONTROL button. When thermostat OFF (compressor OFF) fan speed becomes Very Low. In AUTO the fan speed is as follows.

Room temperature minus set temperature (Initial)

Room temperature minus set temperature (During operation)

High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)

4.5°F (2.5°C) 1.8°F (1°C)

3.15°F (1.75°C)

3. Coil frost prevention Coil frost prevention is as same as COOL mode. (4-1.3.) The indoor fan maintains the actual speed of the moment.
Show 4 more labels / short text on this page
Fan speed · Set temperature · Initial room temperature · Fan speed
Page 36 of the Mitsumi electronic MSZ-DNA user manual — CLOSE
Page 36 · click to enlarge
Page 36

4-3. HEAT ( ) OPERATION

1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, HEAT OPERATION (3-10.1.).
2. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.

In Auto the fan speed is as follows.

Set temperature minus room temperature (During operation) Set temperature minus room temperature (Initial)

3.6°F (2°C)

7.2°F (4°C)

High Med. Low

Between 0.45 and 3.6°F 3.6°F(2°C) or more

Less than 0.45°F(0.25°C) 0.45°F (0.25°C)

3.15°F (1.75°C)

(2) Cold air prevention control

When the compressor is not operating: ( ) If the temperature of room temperature thermistor RT11 is less than 66.2°F, the fan stops. ( ) If the temperature of room temperature thermistor RT11 is 66.2°F or more and

( ) if the temperature of indoor coil thermistor is less than 32°F, the fan stops. ( ) if the temperature of indoor coil thermistor is 32°F or more, the fan operates at Very Low. When the compressor is operating: ( ) If the temperature of indoor coil thermistor is 104°F or more, the fan operates at set speed. ( ) If the temperature of indoor coil thermistor is less than 104°F and

( ) if heating operation starts after defrosting, the fan stops. ( ) if the temperature of room temperature thermistor RT11 is 66.2°F or less, the fan stops. ( ) if the temperature of room temperature thermistor RT11 is more than 66.2°F, the fan operates at Very Low.

  • NOTE:
  • When 2 or more indoor units are operated with a multi type outdoor unit, the fan operates intermittently at Very Low or stops in the thermostat-OFF units while at least one unit is thermostat-ON.
  • When 3 minutes have passed since the compressor started operation, this control is released regardless of the temperature of RT11 and indoor coil thermistor.
3. High pressure protection In HEAT operation, the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor operational frequency is controlled to prevent the condensing pressure from increasing excessively. 4. Defrosting Refer to MXZ MICROPROCESSOR CONTROL, HEAT DEFROSTING CONTROL (3-4.).

Time chart of defrosting in HEAT mode (reverse type)

<Indoor unit>

set speed Indoor fan (upper)

Very Low (temperature of indoor coil thermistor > 64.4°F)

OFF

ON ON

OFF

OPEN or CLOSE OPEN or CLOSE

CLOSE

Show 9 more labels / short text on this page
Fan speed · vertical · set position · set position · Horizontal vane · set speed · 30 seconds · Indoor fan (lower) · Damper
Page 37 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2B20NA1 MXZ-3B MXZ-4B
Page 37 · click to enlarge
Page 37

4-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation. 1. Mode selection (1) Initial mode

At first, indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature. Following the conditions below, operation mode is selected.

If the room temperature thermistor RT11 reads more than set temperature, COOL mode is selected. If the room temperature thermistor RT11 reads set temperature or less, HEAT mode is selected. (2) Mode change

In case of the following conditions, the operation mode is changed.

COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 35.6°F below the set

temperature. HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 35.6°F above the set

temperature.

In the other cases than the above conditions, the present operation mode is continued.

ON-timer. NOTE2: When two or more indoor units are operating simultaneously, the indoor unit, which is operating in AUTO ( ), might not be able to change over the operating mode (COOL HEAT) and becomes the standby state. (3) Indoor fan control/ Vane control

As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation mode changes over, they change to the exclusive ones.

4-5. INDOOR FAN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feed- back the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med., Low), the microprocessor adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.

Super High Super High

Med.

(2) Fan motor lock-up protection When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect the signal for 12 seconds) energizing to the fan motor is stopped. Then the microprocessor retries detection 3 times every 30 seconds. If the microprocessor still cannot detect the signal, the fan motor is regarded locked-up. When the fan motor locks up, OPERATION INDICATOR lamp flashes ON and OFF to show the fan motor abnormality.

Show 4 more labels / short text on this page
Rotational frequency · High · Low · time
Page 38 of the Mitsumi electronic MSZ-DNA user manual — OPEN
Page 38 · click to enlarge
Page 38

4-6. AUTO VANE OPERATION Horizontal vane

(1) Cold air prevention in HEAT operation

When any of the following conditions occurs in HEAT operation, the vane angle changes to Vertical position automati- cally to prevent cold air blowing on users.

Compressor is not operating. Defrosting is performed. Indoor coil thermistor reads 75.2°F or below. Indoor coil thermistor temperature is raising from 75.2°F or below, but it does not exceed 102.2°F.

Indoor coil thermistor temperature

Vertical Position 102.2°F (39°C) 75.2°F (24°C)

position.

Indoor fan motor (Lower) in COOL OPERATION

Difference between room temperature and set temperature during operation

Difference between room temperature and set temperature during operation Damper

OPEN

CLOSE

35.6°F (2°C)

44.6°F (7°C)

Indoor fan motor (Lower) in HEAT OPERATION

Indoor coil thermistor temperature Damper

Indoor coil thermistor temperature

OPEN

CLOSE

95°F (35°C)

104°F (40°C)

  • As for indoor fan motor (upper), refer to "Indoor fan speed control (2-1.2, 2-2.2, 2-3.2)" and "INDOOR FAN MOTOR CONTROL (2-5.)".

In swing operation of ECONO COOL operation mode, the initial airflow direction is adjusted to "Horizontal". According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 35.6°F, the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.

coil thermistor (°F) Downward blow time (second) Horizontal blow time (second)

A 59 or less 2 23

B 59 to 63 5 20

C 63 to 64 8 17

D 64 to 68 11 14

E 68 to 70 14 11

F 70 to 72 17 8

G 72 to 75 20 5

H More than 75 23 2

Show 5 more labels / short text on this page
Horizontal vane · Released · Set position · Cold Air Prevention · Temperature of indoor
Page 39 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2B20NA1 MXZ-3B MXZ-4B
Page 39 · click to enlarge
Page 39
Page 39 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2B20NA1 MXZ-3B MXZ-4B
Page 40 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2B20NA1 MXZ-3B MXZ-4B
Page 40 · click to enlarge
Page 40
Page 40 of the Mitsumi electronic MSZ-DNA user manual — MXZ-2B20NA1 MXZ-3B MXZ-4B

Ask about the Mitsumi electronic MSZ-DNA

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsumi electronic MSZ-DNA

Be the first to ask — other owners or our team will answer.

Original document

Mitsumi electronic MSZ-DNA manual PDF

40 pages·287 KB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…