Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat
ON -1.8°F(-1°C) or more OFF less than -1.8°F(-1°C)
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)
3.15°F (1.75°C)
When the indoor coil thermistor RT12 reads 37°F (3°C) or below the coil frost prevention mode starts immediately. However, the coil frost prevention does not work for 5 minutes since the compressor has started. The indoor fan operates at the set speed and the compressor stops for 5 minutes. After that, if the indoor coil thermistor still reads below 37°F (3°C), this mode is prolonged until the indoor coil thermistor reads over 37°F (3°C). Time control
When the 3 conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Low or Med. c. Room temperature is below 79°F (26°C). When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 79°F (26°C). However, when two of the above conditions (b. and c.) are satisfied again, time accumulation is resumed.
OFF
( Continuously at set speed) ON
1-2. DRY ( ) OPERATION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
Set temperature and initial room temperature in dry mode
50(10) 50 59 68 77 86 95
(10) (15) (20) (25) (30) (35)
Initial room temperature [°F(°C)]

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat
ON -3.6°F(-2°C) or more OFF less than -3.6°F(-2°C)
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)
3.15°F (1.75°C)
Operation time chart Example
OFF
ON
OFF
ON
OFF
8 minutes 1 minute 4 minutes 3 minutes

1-3. AUTO VANE OPERATION 1. Horizontal vane ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermistor). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. To cancel this operation, select a different mode or press one of the following buttons in ECONO COOL operation: ECONO COOL or VANE CONTROL button.
In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6°F (2°C), the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat
ON -1.8°F(-1°C) or more OFF less than -1.8°F(-1°C)
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)
3.15°F (1.75°C)
The outdoor fan rotational speed slows down to maintain sufficient cooling capacity. NOTE: Even when the unit is in the "thermostat-off" status under the low outside temperature operation mode, the out-
door fan rotation does not stop. (2) Dew drop prevention When the ambient temperature thermistor reads 14°F (-10°C) or less (the set temperature is different depending on the models), as coil frost or dew drop from indoor unit may occur, the compressor turns OFF with the outdoor fan OFF for prevention of them. (3) Outdoor temperature detecting control To detect the exact outdoor temperature in this mode, the compressor turns OFF but the outdoor fan stays ON for 3 minutes once 1 hour. If the outdoor temperature rises over about 64°F (18°C), the unit goes back to the normal COOL mode. If the outside temperature stays below about 64°F (18°C), the unit continues to run in the low outside tempera- ture operation mode. Other protections work as well as in the normal COOL mode.
Fan speed

2-2. DRY ( ) OPERATION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
Set temperature and initial room temperature in dry mode
(10) (15) (20) (25) (30) (35) 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.
50(10) 50 59 68 77 86 95
Initial room temperature [°F(°C)]
Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat
ON -3.6°F(-2°C) or more OFF less than -3.6°F(-2°C)
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)
3.15°F (1.75°C)
2-3. HEAT ( ) OPERATION (MSZ) 1. Thermostat control Thermostat turns ON or OFF by difference between room temperature and set temperature.
Room temperature minus set temperature (During operation) (MSZ-FE18 MSZ-GE24)
Room temperature minus set temperature (Initial)
ON less than 1.8°F(1°C) OFF 1.8°F(1°C) or more 1.35°F (0.75°C)
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
ON less than 3.6°F(2°C) OFF 3.6°F(2°C) or more 3.15°F (1.75°C)
In Auto the fan speed is as follows.
Set temperature minus room temperature (During operation) Set temperature minus room temperature (Initial)
7.2°F (4°C)
High Med. Low
Between 0.45 and 3.6°F 3.6°F(2°C) or more
Less than 0.45°F(0.25°C) 0.45°F (0.25°C)

(2) Cold air prevention control
When the compressor is not operating,
( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or more and
( ) if the temperature of indoor coil thermistor is less than 32°F (0°C), the fan stops. ( ) if the temperature of indoor coil thermistor is 32°F (0°C) or more, the fan operates at Very Low. When the compressor is operating,
( ) if the temperature of indoor coil thermistor is 104°F (40°C) or more, the fan operates at set speed. ( ) if the temperature of indoor coil thermistor is less than 104°F (40°C) and
( ) if heating operation starts after defrosting, the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or less, the fan stops. ( ) if the temperature of room temperature thermistor is more than 66°F (19°C), the fan operates at Very Low. NOTE: When 4 minutes (MSZ-FE18 MSZ-GE24)/3 minutes (Other models) have passed since the compressor started
operation, this control is released regardless of the temperature of room temperature thermistor and indoor coil thermistor. MSZ-A24 MSZ-GA
When the compressor is not operating,
( ) if the temperature of room temperature thermistor is 59°F (15°C) or less, or temperature of indoor coil thermis-
tor is less than 64°F (18°C), the fan stops. ( ) if the temperature of room temperature thermistor is more than 59°F (15°C), or temperature of indoor coil
thermistor is more than 64°F (18°C), the fan operates at Very Low. When the compressor is operating,
( ) if the temperature of indoor coil thermistor is 64°F (18°C) or more, the fan operates at set speed. ( ) if the temperature of indoor coil thermistor is less than 64°F (18°C) and
( ) if heating operation starts after defrosting, the fan stops. ( ) if the temperature of room temperature thermistor is 59°F (15°C) or less, the fan stops. ( ) if the temperature of room temperature thermistor is more than 59°F (15°C), the fan operates at Very Low. NOTE: When 3 minutes have passed since the compressor started operation, this control is released regardless of the
temperature of room temperature thermistor and indoor coil thermistor. (3) Warm air control (MSZ-FD MSZ-FE MSZ-GE)
When the following any condition of (a. ~ c.) and the condition of are satisfied at the same time, warm air control works.
a.) Fan speed is used in MANUAL. b.) When cold air prevention has been released. c.) When defrosting has been finished. When the temperature of indoor coil thermistor is less than 104°F (40°C). When warm air control works, the fan speed changes as follows to blow out warm air gradually. Gradation of fan speed in initial
Less than 4 minutes Low 4 to 8 minutes Med. More than 8 minutes High
Less than 2 minutes Low 2 to 4 minutes Med. More than 4 minutes High or Super high
The upper limit of the fan speed in MANUAL is the set speed. When the temperature of indoor coil thermistor has been 104°F (40°C) or more, or when the set speed has been changed, this control is released and the fan speed is the set speed. 3. Overload starting When the room temperature thermistor reads 64°F (18°C) or more, the compressor runs with its maximum frequency regu- lated for 10 minutes after the start-up. 4. Defrosting (1) Starting conditions of defrosting
When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads about 30.2°F (-1°C) or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min-
utes). c) More than 5 minutes have passed since the start-up of the compressor.
The defrost interval is decided by the previous defrosting time. The next defrost interval extends or shortens 0-20
minutes compared with the previous defrost interval.
(Other models)

(2) Releasing conditions of defrosting
Defrosting is released when any one of the following conditions is satisfied: a) The defrost thermistor continues to read "Defrost finish temperature" for 30 seconds.
Refer to "CHANGE IN DEFROST SETTING of SERVICE FUNCTIONS in OUTDOOR UNIT SERVICE MANUAL". b) Defrosting time has exceeded 10 minutes. c) Any other mode than HEAT mode is set during defrosting.
<Indoor unit>
horizontal (temperature of indoor coil thermistor < 102 °F)
set speed Indoor fan
Very Low (temperature of indoor coil thermistor > 64 °F)
OFF
<Outdoor unit>
OFF OFF
30 seconds 40 seconds 5 seconds 5 seconds
OFF
ON (HEAT)
ON (HEAT)
R.V. coil
2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ) Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation. 1. Mode selection (1) Initial mode
At first indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature. Following the conditions below, operation mode is selected.
If the room temperature thermistor reads more than set temperature, COOL mode is selected. If the room temperature thermistor reads set temperature or less, HEAT mode is selected.

In case of the following conditions, the operation mode is changed.
COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C)
below the set temperature. HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C)
above the set temperature.
In the other cases than the above conditions, the present operation mode is continued.
ON-timer. NOTE2: When two or more indoor units are operating simultaneously, the indoor unit, which is operating in AUTO ( ), might not be able to change over the operating mode (COOL ↔ HEAT) and becomes the standby state. (3) Indoor fan control/ Vane control
As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation mode changes over, they change to the exclusive ones.
2-5. OUTDOOR FAN MOTOR CONTROL Fan speed is switched according to the compressor frequency.
Compressor frequency Min. Max.
2-6. AUTO VANE OPERATION 1. Horizontal vane (1) Cold air prevention in HEAT operation (MUZ)
When any of the following conditions occur in HEAT operation, the vane angle changes to Horizontal position automati- cally to prevent cold air blowing on users.
Compressor is not operating. Defrosting is performed. Indoor coil thermistor temperature does not exceed 102°F (39°C) within about 3 minutes after compressor starts. NOTE: When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat OFF,
this control does not work in the indoor unit. (2) ECONO COOL ( ) operation (ECONOmical operation) (Excluding MSZ-FD and MSZ-FE09/12) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermistor). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. To cancel this operation, select a different mode or press one of the following buttons in ECONO COOL operation: ECONO COOL or VANE CONTROL button.

In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6°F (2°C), the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.
MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD MUZ-FE09/12 MSZ-GE06/09/12/15/18 MUY-GE09/12/15/18
CURRENT TRANSFORMER
DIODE MODULE1
REACTOR
U
U
NOISE FILTER CIRCUIT
RESISTOR
P
POWER SUPPLY
SMOOTHING CAPACITOR
MS
3~ V
N
W
W
RELAY
INTELLIGENT
COMPRESSOR
POWER MODULE
SWITCHING POWER TRANSISTOR
DIODE MODULE2
BOOSTER CHOPPER CIRCUIT
Function of main parts

MUZ-A24 MUY-A24 MUZ-D MUY-D MUZ-FE18 MUZ-GA MUY-GA MUZ-GE24 MUY-GE24
REACTOR
P
U
U
NOISE FILTER CIRCUIT
RESISTOR
POWER SUPPLY
SMOOTHING CAPACITOR
MS
3~ V
N
W
W
RELAY
INTELLIGENT POWER MODULE POWER FACTOR
COMPRESSOR
CORRECTION
MODULE
Function of main parts
INTELLIGENT POWER MODULE It supplies 3-phase AC power to compressor.
SMOOTHING CAPACITOR It stabilizes the DC voltage and supplies it to INTELLIGENT POWER MODULE.
CURRENT TRANSFORMER It measures the current of the compressor motor.
It rectifi es AC, controls its voltage and improves the power factor of power supply. POWER FACTOR CORRECTION MODULE
RESISTOR It absorbs the rush current not to run into the main power supply circuit when the electricity turns ON.
RELAY It keeps the RESISTOR, which restricts rush current, short-circuited while the compressor is operating.
2-7-2. Outline of main power supply circuit MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD MUZ-FE09/12 MUZ-GE09/12/15/18 MUY-GE09/12/15/18
1. At the start of operation Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup. To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR is placed in sub circuit. 2. At normal operation When AC runs into POWER P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT. After noise is eliminated from AC, it is rectifi ed to DC by DIODE MODULE 1. DC voltage, to which AC has been rectifi ed by process , is stabilized by SMOOTHING CAPACITOR and supplied to IN- TELLIGENT POWER MODULE. DC voltage, which has been stabilized in process , is converted to 3-phase AC by INTELLIGENT POWER MODULE and supplied to COMPRESSOR. CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, is used to measure the value
of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those pieces of information.
+

Outline of simple partial switching method In conventional inverter models, DIODE MODULE rectifi es AC voltage to DC voltage, SMOOTHING CAPACITOR makes its DC waveform smooth, and INTELLIGENT POWER MODULE converts its DC voltage to imitated AC voltage again in order to drive the compressor motor. However, it has been difficult to meet IEC harmonic current emission standard by above circuit because harmonic gets generated in the input current waveform and power factor gets down. The simple partial switching method with PAM, which has been adopted this time, places and utilizes BOOSTER CHOPPER CIRCUIT before rectifying AC voltage in the general passive-method converter circuit. As harmonic gets suppressed and the peak of waveform gets lower by adding BOOSTER CHOPPER CIRCUIT as mentioned above and by synchronizing the timing of switching with the zero-cross point of waveform, the input current waveform can be improved and the requirement of IEC harmonic current emission standard can be satisfi ed. Since the switching synchronized with the zero cross point, this simple partial switching method has the feature of lower en- ergy loss compared to active fi lter method. In addition, output and effi ciency is enhanced by combining with vector-controlled inverter in order to boost the voltage of power supplied to INTELLIGENT POWER MODULE.
Input current waveform without PAM Input current waveform with PAM
Release of energy stored in L.
Peak gets down.
Energized time is short in case L inductance is small.
Energized time is extended by optimization of L inductance.
No electricity runs into diode module because the voltage at both sides of smoothing capacitor is higher than input voltage.
Compulsory energizing by switching.
Input voltage · Input current

INTELLIGENT POWER MODULE consists of the following components · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from overcurrent. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIGENT POWER MODULE has a merit to make the control circuit simplify and miniaturize. 5. Elimination of electrical noise
NOISE FILTER CIRCUIT, which is formed by *CMC COILS and capacitors placed on the POWER P.C. board, eliminates electrical noise of AC power that is supplied to main power supply circuit. This circuit also prevents the electrical noise gen- erated in the inverter circuit from leaking out.
MUZ-A24 MUY-A24 MUZ-D MUY-D MUZ-FE18 MUZ-GA MUY-GA MUZ-GE24 MUY-GE24 1. At the start of operation Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup. To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR is placed in sub circuit. 2. At normal operation When AC runs into noise filter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT. After noise is eliminated from AC, it is rectified to DC by REACTOR and POWER FACTOR CORRECTION MODULE. If the
operating frequency becomes 25 Hz or more, DC voltage rises to 370 V. DC voltage, to which has AC been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IN- TELLIGENT POWER MODULE. The DC (Bus voltage), which has been stabilized in process , is converted to 3-phase AC by INTELLIGENT POWER MODULE and supplied to COMPRESSOR. CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, is used to measure the value
of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those pieces of information. 3. Power factor improvement Booster coil reactor and POWER FACTOR CORRECTION MODULE rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. POWER FACTOR CORRECTION MODULE and reactor stabilize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Intelligent power module INTELLIGENT POWER MODULE consists of the following components. · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from over current. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIGENT POWER MODULE has a merit to make the control circuit simplified and miniaturized. 5. Elimination of electrical noise NOISE FILTER CIRCUIT, which is formed by *CMC COILS, *NMC COILS and capacitors placed on the POWER P.C. board, eliminates electrical noise of AC power that is supplied to main power supply circuit. This circuit also prevents the electrical noise generated in the inverter circuit from leaking out.

2-7-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which does not have Hall element. In short, the motor is sensorless. However, it is necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor effi ciently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by unenergized stator. Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection when the voltage of supplied power is impressed. So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start & end of one heap in one waveform cycle (180°) when the voltage is impressed. However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase current waveform smoother (sine wave) in order to drive the motor more effi ciently and smoothly.
DC Motor AC Motor
Rotor Permanent magnet is embedded. Excited by magnetic fi eld of stator
Rotor Position Signal Necessary Unnecessary
In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it does not require energy to excite the rotor
like AC motor does. However, it is necessary to control the frequency of 3-phase AC current supplied to the stator accord- ing to the polar direction of magnet embedded in the rotor so as to drive the motor effi ciently. Controlling 3-phase AC current frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be detected. 2-7-5. Control Method of Rotational speed Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo- tor, locates the rotor position from the detected value, and decides if voltage should be impressed and if frequency should be changed. Compared to the conventional control and rotor position detection method, sine wave control can provide fi ner adjustment of the voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.

2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.
Operational frequency (Hz) COOL HEAT (MUZ) DRY Minimum Maximum Minimum Maximum Minimum Maximum MUZ-A09 32 70 32 76 32 57 MUZ-A12 32 73 32 71 32 57 MUZ-A15 MUY-A15 10 82 15 93 10 68 MUZ-A17 MUY-A17 10 87 15 93 10 68 MUZ-A24 MUY-A24 15 110 15 108 15 102 MUZ-FD09 10 52 10 100 10 41 MUZ-FD12 10 62 10 100 10 41 MUZ-FE09 10 52 10 100 10 41 MUZ-FE12 10 62 10 100 10 41 MUZ-FE18 26 120 26 124 26 120 MUZ-D30 20 84 20 87 20 83 MUZ-D36 20 91 20 94 20 83 MUY-D30 20 79 — — 20 79 MUY-D36 20 92 — — 20 79 MUZ-GA24 MUY-GA24 15 101 15 108 15 101 MUZ-GE09 MUY-GE09 28 93 30 105 28 48 MUZ-GE12 MUY-GE12 20 98 30 98 30 55 MUZ-GE15 MUY-GE15 15 90 15 102 15 54 MUZ-GE18 MUY-GE18 15 98 15 108 15 83 MUZ-GE24 MUY-GE24 26 120 26 124 26 120
The operation frequency in COOL mode is restricted by the upper limit frequency after 1 hour or 0.5 ~ 1 hour as shown
below for dew prevention. It is rated frequency or less.
Upper limit frequency Rated frequency or less
1 hour or 0.5~1 hour
Applied model · Maximum frequency · Time

(1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening degrees set for each opera- tional frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air conditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge tempera- ture (Shell temperature) of the compressor, developing the unit's performance.
59 pulses (MUZ-A24 MUY-A24 MUZ-GA MUY-GA) 54 pulses (MUZ-FD MUZ-FE MUZ-GE MUY-GE) 58 pulses (MUZ-D MUY-D) Maximum: 500 pulses
Actuating speed Open: 40 pulses/second Close: 90 pulses/second Opening degree adjustment LEV opening degree is always adjusted in opening direction. (When reduc- ing the opening degree, LEV is once over-closed, and then adjusted to the proper degree by opening.
Unit OFF LEV remains at maximum opening degree (reaches maximum opening degree approximate in 15 minutes after compressor stops) Remote controller ON LEV is positioned. (First full-closed at zero pulses and then positioned.) During 1 to 15 minutes after compressor starts
LEV is fixed to standard opening degree according to operational frequen- cy of compressor. More than about 15 minutes have passed since compressor start-up
LEV opening degree is corrected to get target discharge temperature of compressor. (For lower discharge temperature than target temperature, LEV is correct- ed in closing direction.) (For higher discharge temperature than target temperature, LEV is cor- rected in opening direction.)
It may take more than 30 minutes to reach target temperature, depend- ing on operating conditions. Thermostat OFF LEV is adjusted to exclusive opening degree for thermostat OFF. Thermostat ON LEV is controlled in the same way as that after the compressor has started up. Defrosting in HEAT mode LEV is adjusted to open 500 pulses
Air conditioner OFF (thermostat off)
Opening degree is corrected according to discharge temperature. (Refer to (3))
Commanded to open Standard opening degree

30 50 70 90 110 130 23 38 53 69 84 99 (Hz) (Hz)
(Other models) (MUZ-FE18 MUZ-GE24 MUY-GE24)
Operational frequency of the compressor
(a) Reference value of target discharge temperature
Applied model A B C D E F
MUZ-A09/12 COOL 122/50 127/53 140/60 151/66 158/70 158/70 HEAT 113/45 126/52 138/59 154/68 169/76 169/76
MUZ-A15/17 MUY-A15/17 COOL 129/54 136/58 147/64 158/70 158/70 158/70 HEAT 120/49 136/58 151/66 165/74 180/82 185/85
MUZ-A24 MUY-A24 MUZ-GA MUY-GA COOL 140/60 140/60 140/60 145/63 147/64 153/67 HEAT 140/60 145/63 149/65 153/67 158/70 158/70
MUZ-FD MUZ-FE09/12 COOL 120/49 131/55 142/61 153/67 162/72 169/76 HEAT 109/43 124/51 138/59 156/69 167/75 176/80
MUZ-FE18 MUZ-GE24 MUY-GE24 COOL 131/55 142/61 151/66 162/72 171/77 178/81 HEAT 115/46 133/56 151/66 167/75 181/83 187/86
MUZ-D MUY-D COOL 126/52 135/57 149/65 167/75 183/84 187/86 HEAT 131/55 140/60 149/65 154/68 162/72 167/75
MUZ-GE09 MUY-GE09 COOL 126/52 136/58 149/65 153/67 158/70 160/71 HEAT 109/43 122/50 131/55 138/59 149/65 156/69
MUZ-GE12 MUY-GE12 COOL 127/53 140/60 147/64 153/67 162/72 169/76 HEAT 109/43 124/51 138/59 156/69 167/75 176/80
MUZ-GE15 MUY-GE15 COOL 120/49 131/55 147/64 153/67 162/72 169/76 HEAT 109/43 124/51 138/59 156/69 167/75 176/80
MUZ-GE18 MUY-GE18 COOL 135/57 140/60 144/62 153/67 165/74 178/81 HEAT 140/60 149/65 158/70 167/75 167/75 167/75
In COOL operation, the indoor coil thermistors (main and sub) sense temperature ununiformity (super heat) at the heat exchanger, and when temperature difference develops, the indoor coil thermistors adjust LEV opening degree to get approximate 18°F (10°C) lower temperature than the target temperature in the table above, thus diminishing super heat.
(3) Control data · Target discharge temperature

2-10. PRE-HEAT CONTROL MUZ-FD MUZ-FE MUZ-GE 1. Outline Compressor is energized to improve the start-up of compressor at a low outside temperature even when compressor is stopped. 2. Pre-heat control
OFF
ON
OFF
68°F (20°C)
Pre-heat control ON condition (1) Compressor is not operating. (However, pre-heat control is still OFF for 30 minutes after compressor is stopped, regardless
30 minutes 1 hour
of the outside temperature.) (2) Outside temperature is 68°F (20°C) or below. Outside temperature is monitored hourly, and when outside temperature is
68°F (20°C) or below, pre-heat control is turned ON. When pre-heat control is turned ON, compressor is energized about 50 W (40-60 W). (Compressor and fan are not operated.)
MUZ-D MUY-D 1. Outline The compressor is energized even while it is not operating. This is to generate heat at the winding to improve the compressor's start-up condition.
30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 15 minutes
15 minutes 30minutes 30minutes
Stop operation Start operation
When the defrost thermistor reads 69.8°F(21°C) or more
is repeated as shown in the graph until the breaker is turned OFF. When the defrost thermistor reads less than 69.8°F (20°C), pre-heat control is ON for 30 minutes. When the defrost thermistor reads 69.8°F (21°C) or more, pre-heat control is ON for 15 minutes. NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF. Compressor uses 50 W when pre-
heat control is turned ON.

3-1-1. Inverter main power supply circuit
REACTOR
P
U
U
NOISE FILTER CIRCUIT
POWER SUPPLY
RESISTOR
SMOOTHING CAPACITOR
MS
3~ V
N
W
W
RELAY
INTELLIGENT POWER MODULE POWER FACTOR
COMPRESSOR
CORRECTION
MODULE
Function of main parts
INTELLIGENT POWER MODULE It supplies 3-phase AC power to compressor.
SMOOTHING CAPACITOR It stabilizes the DC voltage and supplies it to INTELLIGENT POWER MODULE.
CURRENT TRANSFORMER It measures the current of the compressor motor.
It rectifi es AC, controls its voltage and improves the power factor of power supply. POWER FACTOR CORRECTION MODULE
RESISTOR It absorbs the rush current not to run into the main power supply circuit when the power is turned ON.
RELAY It keeps the RESISTOR, which restricts rush current, short-circuited while the compressor is operating.
3-1-2. Outline of main power supply circuit
1. At the start of operation Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup. To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR is placed in sub circuit. 2. At normal operation When AC runs into noise fi lter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT. After noise is eliminated from AC, it is rectifi ed to DC by REACTOR and POWER FACTOR CORRECTION MODULE. If the
operating frequency becomes 25 Hz or more, DC voltage rises to 370 V. DC voltage, to which has AC been rectifi ed by process , is stabilized by SMOOTHING CAPACITOR and supplied to IN- TELLIGENT POWER MODULE. The DC (Bus voltage), which has been stabilized in process , is converted to 3-phase AC by INTELLIGENT POWER MODULE and supplied to COMPRESSOR. CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, is used to measure the value
of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those pieces of information.
+

3. Power factor improvement Booster coil reactor and POWER FACTOR CORRECTION MODULE rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. POWER FACTOR CORRECTION MODULE and reactor stabilize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Intelligent power module INTELLIGENT POWER MODULE consists of the following components. · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from over current. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIGENT POWER MODULE has a merit to make the control circuit simplifi ed and miniaturized. 5. Elimination of electrical noise NOISE FILTER CIRCUIT, which is formed by *CMC COILS, *NMC COILS and capacitors placed on the P.C. board, eliminates electrical noise of AC power that is supplied to main power supply circuit. This circuit also prevents the electrical noise gener- ated in the inverter circuit from leaking out. *CMC COILS: Common mode choke coils *NMC COILS: Normal mode choke coils
3-1-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which does not have Hall element. In short, the motor is sensorless. However, it is necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor effi ciently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by unenergized stator. Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection when the voltage of supplied power is impressed. So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start and end of one heap in one waveform cycle (180°) when the voltage is impressed. However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase current waveform smoother (sine wave) in order to drive the motor more effi ciently and smoothly.
DC Motor AC Motor
Rotor Permanent magnet is embedded. Excited by magnetic fi eld of stator
Rotor Position Signal Necessary Unnecessary
In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it does not require energy to excite the rotor
like AC motor does. However, it is necessary to control the frequency of 3-phase AC current supplied to the stator accord- ing to the polar direction of magnet embedded in the rotor so as to drive the motor effi ciently. Controlling 3-phase AC current frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be detected.
3-1-5. Control Method of Rotational speed Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo- tor, locates the rotor position from the detected value and decides if voltage should be impressed and if frequency should be changed. Compared to the conventional control and rotor position detection method, sine wave control can provide fi ner adjustment of the voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.

3-2. EXPANSION VALVE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit.
Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulses in 15 minutes
When outdoor unit is operating, some indoor units stop and some operate.
: (MXZ-3A30NA- 1 /4A/3B/4B): 100 → 59 pulses
When the outdoor unit operates (When the other indoor unit operates): 5 pulses When outdoor unit stops. (When the other indoor unit stops or thermo OFF): Maintain LEV opening before stop → 500 pulses in 15 minutes
Thermostat OFF in COOL or DRY mode
Thermostat ON in COOL or DRY mode
same. However, velocity and compressor operation frequency controls are differ- ent. See 3-3. OPERATIONAL FREQUENCY RANGE (As far as the indoor unit velocity control goes, refer to DRY operation in MICRO- PROCESSOR CONTROL in indoor unit.)
Thermostat OFF in HEAT mode
Thermostat ON in HEAT mode
1 LEV opening when the outdoor unit is operating: Upper limit 500 pulses, Lower limit 53 pulses (MXZ-2A/3A30NA/2B)/59 pulses (MXZ-3A30NA- 1 /4A/3B/4B).

The table below shows the role of Exclusive LEV and Receiver LEV in each operation mode.
COOL Exclusive LEV ○ Receiver LEV × × ○ ○ ○
HEAT Exclusive LEV × ○ ○ ○ — Receiver LEV ○ × ○ ○ —
LEV
(MXZ-3A30NA)
In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger, and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the super heat. This action is called Evaporation Temperature Protection.
The opening pulse of the Receiver LEV is fixed to the standard No.3 in cooling operation, and so is that of each Exclusive LEV in heating operation. However the opening pulse will be changed to the standard No.4 or No.5 when the discharge temperature protection or high- pressure protection is working.
In addition to that, it will also be changed to standard No.2 or No.1 when the opening pulse of the each Exclusive LEV becomes 100 pulse or less in cooling operation or so does that of Receiver LEV in heating operation.
LEV opening (pulse) COOL HEAT
1 unit 2 units 1 unit 2 units
Standard No.
1 200 150 120 120 2 300 320 140 140 3 400 360 160 160 4 450 410 220 220 5 500 500 280 280
LEV opening (pulse) COOL HEAT
1 unit 2 units 3 units 1 unit 2 units 3 units
Standard No.
1 150 250 2 250 320 320 300 300 300 3 350 360 370 450 380 380 4 400 410 420 460 400 390 5 450 460 470 470 450 440

Determination of LEV standard opening in each indoor unit
put opening is in a range from 59 to 500 pulses.
01 02 03 04 05 06 07 08 09 10
23 54 69 84 100 115 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A/2B MXZ-3A/4A 23
Compressor operating frequency (Hz)
Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 120 130 136 146 156 160 170 180 190 200 HEAT 100 110 120 130 146 160 170 180 190 200
Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 COOL 3 6 9 12 15 25 35 -20 HEAT 3 6 9 52 55 65 75 0
Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 126 130 134 138 140 142 182 228 296 310 HEAT 140 146 150 170 180 200 224 244 272 280
Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 3 COOL 3 6 9 12 15 25 35 -20 -30 HEAT 3 6 9 52 55 65 75 0 0
4Hz · LEV Opening (code)

Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 120 130 136 146 156 160 170 180 190 200 HEAT 248 248 258 266 274 280 286 292 300 306
Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 COOL 3 6 9 12 15 25 35 -20 HEAT 3 6 9 52 55 65 75 30
Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 140 150 160 170 180 190 200 HEAT 80 84 90 110 120 130 140 150 160 170
Operation number Difference in operation number
MXZ-3A30NA1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA
Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 126 130 134 138 150 160 170 180 190 200 HEAT 248 248 258 266 274 280 286 292 300 306
Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above 2 3 4(MXZ-4A/4B) COOL 3 6 9 12 15 25 35 -20 -30 -30 HEAT 3 6 9 52 55 65 75 -4 -8 -12
Standard opening (pulse) LEV Opening (code) 1 2 3 4 5 6 7 8 9 10 COOL 270 280 290 300 310 320 330 340 350 360 HEAT 140 152 160 170 180 200 224 244 274 280
Operation number Difference in operation number
2 3 4(MXZ-4A/4B) COOL 28 56 84 HEAT -45 -60 -60
Capacity code 3 4 7 9 10 12 Indoor unit 06 09 12 15 17 24
Receiver LEV · Exclusive LEV · Receiver LEV

1 Perform this, when number of operation units is 2 units or more. (MXZ-2A20NA and MXZ-3A30NA only) 2 Correct the LEV opening by discharge temperature.
(1) LEV opening correction by discharge temperature
The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor.
Target discharge temperature (°F/°C) COOL HEAT Number of operating unit 1 unit 2 units 1 unit 2 units Minimum ~ 23 95/35 136.4/58 122/50 122/50 24 ~ 38 104/40 140/60 132.8/56 122/50 39 ~ 54 120.2/49 149/65 140/60 132.8/56 55 ~ 69 136.4/58 154.4/68 140/60 140/60 70 ~ 85 149/65 158/70 140/60 140/60 86 ~ Maximum 158/70 158/70 140/60 140/60
Target discharge temperature (°F/°C) COOL HEAT Number of operating unit 1 unit 2 units 1 unit 2 units Minimum ~ 23 95/35 136.4/58 122/50 122/50 24 ~ 38 104/40 140/60 132.8/56 122/50 39 ~ 54 120.2/49 149/65 140/60 132.8/56 55 ~ 69 136.4/58 154.4/68 145.4/63 140/60 70 ~ 85 149/65 158/70 150.8/66 140/60 86 ~ Maximum 158/70 158/70 152.6/67 140/60
Target discharge temperature (°F/°C) COOL HEAT Number of operating unit 1 unit 2 units 3 units 1 unit 2 unit 3 units Minimum ~ 14 95/35 131/55 134.6/57 125.6/52 143.6/62 122/50 15 ~ 23 104/40 131/55 134.6/57 136.4/58 150.8/66 131/55 24 ~ 32 120.2/49 136.4/58 145.4/63 149/65 165.2/74 140/60 33 ~ 41 136.4/58 140/60 149/65 154.4/68 172.4/78 152.6/67 42 ~ 50 149/65 149/65 158/70 154.4/68 172.4/78 161.6/72 51 ~ 59 154.4/68 154.4/68 163.4/73 154.4/68 172.4/78 168.8/76 60 ~ 68 158/70 158/70 167/75 154.4/68 172.4/78 168.8/76 69 ~ 77 167/75 163.4/73 176/80 154.4/68 172.4/78 168.8/76 78 ~ 86 167/75 167/75 179.6/82 154.4/68 172.4/78 168.8/76 87 ~ Maximum 167/75 176/80 179.6/82 172.4/78 172.4/78 168.8/76

Target discharge temperature (°F/°C) COOL HEAT Number of operating unit
1 unit 2 units 3 units 4 units (MXZ-4A/4B) 1 unit 2 unit 3 units 4 units (MXZ-4A/4B) Minimum ~ 14 95/35 131/55 134.6/57 140/60 125.6/52 143.6/62 122/50 122/50 15 ~ 23 107.6/42 131/55 134.6/57 140/60 136.4/58 150.8/66 131/55 122/50 24 ~ 32 120.2/49 136.4/58 145.4/63 140/60 149/65 165.2/74 140/60 122/50 33 ~ 41 136.4/58 140/60 149/65 143.6/62 154.4/68 172.4/78 152.6/67 122/50 42 ~ 50 149/65 149/65 158/70 149/65 154.4/68 172.4/78 161.6/72 131/55 51 ~ 59 154.4/68 154.4/68 163.4/73 158/70 154.4/68 172.4/78 168.8/76 140/60 60 ~ 68 158/70 158/70 167/75 158/70 154.4/68 172.4/78 168.8/76 140/60 69 ~ 77 167/75 163.4/73 176/80 161.6/72 154.4/68 172.4/78 168.8/76 140/60 78 ~ 86 167/75 167/75 179.6/82 161.6/72 154.4/68 172.4/78 168.8/76 140/60 87 ~ Maximum 167/75 176/80 179.6/82 161.6/72 172.4/78 172.4/78 168.8/76 140/60
Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.
Discharge temperature (°F/°C) LEV opening correction (pulse)
COOL HEAT More than Target discharge temperature+18/10 5 8 Target discharge temperature + 18/10 to Target discharge temperature + 9 /5 4 3 Target discharge temperature + 9/5 to Target discharge temperature + 3.6/2 2 1 Target discharge temperature + 3.6/2 to Target discharge temperature - 3.6/2 0 0 Target discharge temperature - 3.6/2 to Target discharge temperature - 9/5 -1 -1 Target discharge temperature - 9/5 to Target discharge temperature - 18/10 -3 -2 Target discharge temperature - 18/10 or less -4 -3
Discharge temperature (°F/°C) LEV opening correction (pulse)
COOL HEAT More than Target discharge temperature + 21.6/12 4 6 Target discharge temperature + 21.6/12 to Target discharge temperature + 9/5 2 2 Target discharge temperature + 9/5 to Target discharge temperature + 5.4/3 1 1 Target discharge temperature + 5.4/3 to Target discharge temperature - 5.4/3 0 0 Target discharge temperature - 5.4/3 to Target discharge temperature - 9/5 -1 -1 Target discharge temperature - 9/5 to Target discharge temperature - 21.6/12 -3 -2 Target discharge temperature - 21.6/12 or less -8 -8
(2) Separate correction (COOL,DRY)
(Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all.
Calculate each super heat of the unit from the expression below;
(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature) Separate correction is performed according to each super heat in the table below.
MXZ-3A30NA
Superheat (°F/°C) LEV opening correction (pulse) More than 16.2/9 3 10.8/6 to 16.2/9 2 5.4/3 to 10.8/6 1 5.4/3 or less 0
Superheat (°F/°C) LEV opening correction (pulse) More than 16.2/9 12 10.8/6 to 16.2/9 8 5.4/3 to 10.8/6 4 5.4/3 or less 0
Operation frequency · of compressor (Hz)

b) Correct the LEV separately by temperature difference “ ∆RT” between main/sub indoor coil thermistor.
∆RT (°F/°C) LEV opening correction (pulse) 10.8/6 ∆RT 2 7.2/4 ∆RT < 10.8/6 1 ∆RT < 7.2/4 1
In addition, decrease the target discharge temperature corresponding ∆RT.
∆ RT (°F/°C) Temperature to be decreased (°F/°C) 10.8/6 ∆RT 18/10 7.2/4 ∆RT< 10.8/6 9/5 ∆RT < 7.2/4 9/5
MXZ-2A20NA
unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
4 20 65 25 48 92 92 7 20 85 30 48 92 92 9,10 20 100 75 48 100 100 12 20 100 75 48 100 100
8 ~ 10 30 105 52 58 112 100 11 ~ 13 30 105 52 58 112 100 14 ~ 16 30 105 52 58 112 100 17 ~ 20 105 100 58 112 100
unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
4 20 65 35 48 92 92 7 20 85 34 48 92 92 9,10 20 93 75 48 92 92 12 20 93 75 48 92 92
8 ~ 10 30 93 52 58 110 101 11 ~ 13 30 93 52 58 110 101 14 ~ 16 30 93 52 58 110 101 17 ~ 30 93 93 58 110 101
unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
4 20 65 25 30 92 92 7 20 85 34 30 92 92 9,10 20 93 75 30 92 92 12 20 93 75 30 92 92
8 ~ 10 40 93 53 58 112 100 11 ~ 13 40 93 53 58 112 100 14 ~ 16 40 93 53 58 112 100 17 ~ 40 93 93 58 112 100
Number of operating · Number of operating · Number of operating

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
3, 4 20 65 25 30 92 92 7 20 85 34 30 92 92 9, 10 20 93 75 30 92 92 12 20 93 75 30 92 92
2 ~ 7 30 93 53 58 112 100 8 ~ 10 30 93 53 58 112 100 11 ~ 13 30 93 53 58 112 100 14 ~ 16 30 93 53 58 112 100 17 ~ 30 93 93 58 112 100
unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
3, 4 20 65 30 30 92 92 7 20 85 30 30 92 92 9, 10 20 93 38 30 92 92 12 20 93 62 30 92 92
5 ~ 7 30 93 58 58 112 99 8 ~ 10 30 93 58 58 112 99 11 ~ 13 30 93 58 58 112 99 14 ~ 16 30 93 58 58 112 99 17 ~ 30 93 58 58 112 99
unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
4 15 58 20 22 48 48 7 15 58 25 22 48 48 9,10 15 62 44 22 62 58 12 15 68 44 22 90 58
8 ~ 10 24 80 31 35 70 58 11 ~ 13 24 80 31 35 90 58 14 ~ 16 24 80 31 35 94 58 17 ~ 24 80 59 35 94 58 3 12 ~ 52 90 65 39 94 58
unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
4 25 58 25 20 70 58 7 25 58 25 20 70 58 9,10 25 71 25 20 80 58 12 25 80 35 20 80 58
8 ~ 10 25 80 31 20 80 58 11 ~ 13 25 80 31 20 80 58 14 ~ 16 25 80 42 20 80 58 17 ~ 25 80 42 20 80 58 3 (MXZ-3A) 12 ~ 25 80 52 20 80 58 3 (MXZ-4A) 12 ~ 25 90 52 20 103 58 4 (MXZ-4A) 16 ~ 25 90 52 20 113 58

unit Capacity code COOL (Hz) DRY (Hz) HEAT (Hz) Min. Max. Min. Max. Defrost
3,4 15 58 22 25 70 70 7 15 58 22 25 70 70 9,10 15 71 31 25 80 80 12 15 80 42 25 80 80
5 ~ 7 25 80 35 35 80 80 8 ~ 10 25 80 35 35 80 80 11 ~ 13 25 80 35 35 80 80 14 ~ 16 25 80 35 35 80 80 17 ~ 25 80 52 35 80 80 3 (MXZ- 3B) 9 ~ 52 80 52 39 80 80 3 (MXZ-4B) 9 ~ 52 90 52 39 103 80 4 (MXZ-4B) 12 ~ 62 90 70 52 113 80
3-4. HEAT DEFROSTING CONTROL (1) Starting conditions of defrosting
When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F (-3°C) or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min-
utes). c) More than 5 minutes have passed since the start-up of the compressor.
The defrost interval is decided by the previous defrosting time. The next defrost interval extends or shortens 0-20
minutes compared with the previous defrost interval. (2) Releasing conditions of defrosting
Defrosting is released when any one of the following conditions is satisfied: a) The defrost thermistor continues to read 50.7°F (10.4°C). b) Defrosting time exceeds 10 minutes. c) Any other mode than HEAT mode is set during defrosting.
3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera- ture thermistor.
(1) Compressor ON/OFF When temperature of the discharge temperature thermistor exceeds 240.8°F (116°C), the control stops the compressor. When temperature of the discharge temperature thermistor is 176°F (80°C) (2A/3A30NA/2B)/ 212°F (100°C) (3A30NA-
1 /4A/3B/4B) or less, the controls starts the compressor. (2) Compressor operation frequency When temperature of the discharge temperature thermistor is expected to be higher than 240.8°F (116°C), the control decreases 12 Hz from the current frequency. When temperature of the discharge temperature thermistor is expected to be higher than 231.8°F (111°C) and less than 240.8°F (116°C), the control decreases 6 Hz from the current frequency. When temperature of the discharge temperature thermistor is expected to be higher than 219.2°F (104°C) and less than 231.8°F (111°C), the control is set at the current frequency.
Number of operating

3-6. OUTDOOR FAN CONTROL Fan speed is switched according to the number of operating indoor unit and the compressor frequency.
Up Down Fan speed
Down Up MXZ-2B20NA 30 40
Compressor frequency Min. Max.
Or, the indoor coil thermistor is 113 ˚F (45°C) or less on HEAT operation, fan speed is back to normal.
COOL Fan speed changes so that the condensing temperature stays within the target range.
Revolution per minutes (rpm)
1 100 100 2 150 150 3 200 200 4 250 250 5 300 300 6 350 350 7 400 400 8 450 450 9 500 500 10 550 550 11 600 600 12 650 650 13 700 700 14 750 750
Frequency (Hz) Target condensing temperature (°F/°C) ~24 87.8/31-95.0/35 25~34 91.4/33-98.6/37 35~44 95.0/35-102.2/39 45~54 98.6/37-105.8/41 55~64 98.6/37-105.8/41 65~ 98.6/37-105.8/41
HEAT Fan speed is switched according to the compressor frequency.
Up Down Fan speed
MXZ-2B20NA- 1 MXZ-3B MXZ-4B Up 30 50 Down 23 40
Compressor frequency Min. Max.

3-7. PRE-HEAT CONTROL MXZ-2A20NA- 1 , 2 MXZ-3A30NA- 1 MXZ-4A36NA MXZ-2B20NA MXZ-2B20NA- 1 MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA
The compressor is energized even while it is not operating. This is to generate heat at the winding to improve the compressor's start-up condition.
30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 30 minutes 15 minutes
15 minutes 30minutes 30minutes
Stop operation Start operation
When the defrost thermistor reads 69.8°F(21°C) or more
When the defrost thermistor reads less than 69.8°F (21°C), pre-heat control is ON for 30 minutes. When the defrost thermistor reads 69.8°F (21°C) or more, pre-heat control is ON for 15 minutes.
Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat
ON -1.8°F(-1°C) or more OFF less than -1.8°F(-1°C)

Room temperature minus set temperature (During operation) Room temperature minus set temperature (Initial) Thermostat
ON -3.6°F(-2°C) or more OFF less than -3.6°F(-2°C)
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
ON less than 3.6°F(2°C) OFF 3.6°F(2°C) or more 3.15°F (1.75°C)
MXZ-2B/3B/4B
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
ON less than 3.6°F(2°C) OFF 3.6°F(2°C) or more 1.35°F (0.75°C)
Thermostat · Thermostat

Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)
3.15°F (1.75°C)
4-2. DRY ( ) OPERATION The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
Set temperature and initial room temperature in dry mode
50 59 68 77 86 95
Room temperature minus set temperature (Initial)
Room temperature minus set temperature (During operation)
High 3.15°F(1.75°C) or more Med. between 1.8 and 3.15°F Low less than 1.8°F(1°C)
3.15°F (1.75°C)

In Auto the fan speed is as follows.
Set temperature minus room temperature (During operation) Set temperature minus room temperature (Initial)
7.2°F (4°C)
High Med. Low
Between 0.45 and 3.6°F 3.6°F(2°C) or more
Less than 0.45°F(0.25°C) 0.45°F (0.25°C)
(2) Cold air prevention control
When the compressor is not operating: ( ) If the temperature of room temperature thermistor RT11 is less than 66.2°F, the fan stops. ( ) If the temperature of room temperature thermistor RT11 is 66.2°F or more and
( ) if the temperature of indoor coil thermistor is less than 32°F, the fan stops. ( ) if the temperature of indoor coil thermistor is 32°F or more, the fan operates at Very Low. When the compressor is operating: ( ) If the temperature of indoor coil thermistor is 104°F or more, the fan operates at set speed. ( ) If the temperature of indoor coil thermistor is less than 104°F and
( ) if heating operation starts after defrosting, the fan stops. ( ) if the temperature of room temperature thermistor RT11 is 66.2°F or less, the fan stops. ( ) if the temperature of room temperature thermistor RT11 is more than 66.2°F, the fan operates at Very Low.
<Indoor unit>
set speed Indoor fan (upper)
Very Low (temperature of indoor coil thermistor > 64.4°F)
ON ON
OFF
OPEN or CLOSE OPEN or CLOSE

4-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation. 1. Mode selection (1) Initial mode
At first, indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature. Following the conditions below, operation mode is selected.
If the room temperature thermistor RT11 reads more than set temperature, COOL mode is selected. If the room temperature thermistor RT11 reads set temperature or less, HEAT mode is selected. (2) Mode change
In case of the following conditions, the operation mode is changed.
COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 35.6°F below the set
temperature. HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 35.6°F above the set
temperature.
In the other cases than the above conditions, the present operation mode is continued.
ON-timer. NOTE2: When two or more indoor units are operating simultaneously, the indoor unit, which is operating in AUTO ( ), might not be able to change over the operating mode (COOL HEAT) and becomes the standby state. (3) Indoor fan control/ Vane control
As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation mode changes over, they change to the exclusive ones.
4-5. INDOOR FAN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feed- back the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med., Low), the microprocessor adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
Super High Super High
Med.
(2) Fan motor lock-up protection When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect the signal for 12 seconds) energizing to the fan motor is stopped. Then the microprocessor retries detection 3 times every 30 seconds. If the microprocessor still cannot detect the signal, the fan motor is regarded locked-up. When the fan motor locks up, OPERATION INDICATOR lamp flashes ON and OFF to show the fan motor abnormality.

(1) Cold air prevention in HEAT operation
When any of the following conditions occurs in HEAT operation, the vane angle changes to Vertical position automati- cally to prevent cold air blowing on users.
Compressor is not operating. Defrosting is performed. Indoor coil thermistor reads 75.2°F or below. Indoor coil thermistor temperature is raising from 75.2°F or below, but it does not exceed 102.2°F.
Indoor coil thermistor temperature
Vertical Position 102.2°F (39°C) 75.2°F (24°C)
position.
Indoor fan motor (Lower) in COOL OPERATION
Difference between room temperature and set temperature during operation
Difference between room temperature and set temperature during operation Damper
CLOSE
35.6°F (2°C)
44.6°F (7°C)
Indoor fan motor (Lower) in HEAT OPERATION
Indoor coil thermistor temperature Damper
Indoor coil thermistor temperature
CLOSE
95°F (35°C)
104°F (40°C)
In swing operation of ECONO COOL operation mode, the initial airflow direction is adjusted to "Horizontal". According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 35.6°F, the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.
coil thermistor (°F) Downward blow time (second) Horizontal blow time (second)
A 59 or less 2 23
B 59 to 63 5 20
C 63 to 64 8 17
D 64 to 68 11 14
E 68 to 70 14 11
F 70 to 72 17 8
G 72 to 75 20 5
H More than 75 23 2