MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1
These buttons are able to store the light from nature, fluorescent lamp, etc and shine in the dark.
TOO WARM
TOO COOL
ECONO COOL
FAN
I FEEL COOL
FAN SPEED CONTROL button
POWERFUL COOL
VANE
TIME MODE
SELECT
Indication of remote controller model is on back.
TIMER MODE SELECT button
SPECIFICATION 3

81.5 133.5
81.5 81.5
Wall hole [65
e r o m r o 7
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [37 O.D
Drain hose [16 (Connected part O.D)
161.5 161.5
81.5 81.5
Wall hole [65
Liquid line [6.35-0.5m Gas line
[9.52-0.43m
e r o m r o 7
Insulation [37 O.D
Drain hose [16 (Connected part O.D)





















MS-GD12NDC1
Refrigerant pipe (Option){12.7 (with heat insulator)
Refrigerant pipe (Option){9.52 (with heat insulator)
Indoor coil thermistor RT12
Indoor coil thermistor RT12
RT11
Refrigerant pipe (Option){6.35 (with heat insulator)
Refrigerant pipe (Option){6.35 (with heat insulator)
Refrigerant flow in cooling

7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 8-6.) Set time : 1-minute 1-second Set time : 3-minute 3-second It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board Remove batteries before modification. The board has a print as shown below :

teries and push the OPERATE/ STOP(ON/OFF)button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
How to set the remote controller exclusively for particular indoor unit After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.

When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature.
Operation 1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit automatically resumes the same operation as the memory has recorded. However, it takes the compressor at least 3 minutes to get started.
CN211
CN201
How to release “AUTO RESTART FUNCTION” 1 Turn off the main power for the unit. 2 Pull out the indoor electronic control P.C. board and the power monitor, receiver
CN1V1
CN111
P.C. board. (Refer to 9-1.) 3 Solder the Jumper wire to the JR07 on the indoor electronic control P.C.board.
SW1
(Refer to 8-6.)
JR07

8-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during servicing. 1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the electronic control P.C. board. 3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure 1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work. 2) Before servicing that the connector and terminal are connected properly. 3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discolouration. 4) When troubleshooting, refer to 8-2. and 8-3. 4. How to replace batteries Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the back lid and insert batteries. Then reattach the back lid.
2 Press the RESET button with tip end of ball point pen or the like, and then use the remote controller.
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
RESET button

If horizontal vanes are not installed correctly, both of the operation indicator lamps will flash. In this case, install the horizontal vanes correctly by following the procedures 1 to 6.

Insert this end first.
The holes on the insertion ends of the upper and lower horizontal vanes have different shapes.
Insert this end first.
In procedure 2,3,5, and 6, lock the stoppers until they click into place.

Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit doesn't operate even in Test run operation.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Outdoor unit operates in only Test run operation.
Check room temperature thermistor. Refer to 8-6. "Test point diagram and voltage".
Check of wiring diagram of outdoor unit.
Refer to 8-5. B "Check of remote controller and receiver P.C. board".
As for outdoor unit, refer to service manual TBH016 Both lamps (Left and right) Flash on and off at 0.5-second intervals Cause: Indoor unit • The horizontal vanes are not installed correctly.
Check room temperature thermistor and indoor coil thermistor. Refer to 8-6. "Test point diagram and voltage".
Refer to 8-5.A "Check of indoor fan motor".
Refer to 8-5. D "Check of installation of the horizontal vane".
Replace the indoor electronic control P.C. board.
Start

Operation Indicator · Flashing of the OPERATION INDICATOR lamp (on the left) indicates possible abnormalities. · The OPERATION INDICATOR lamp (on the left) is lighting during normal operation.
Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table
No.
Symptom Indication Detection method Check point
Both lamps flash at the same time.
When the electricity is not conducted to the safety device (FAN) of the horizontal vane.
1 0.5-second ON
Attachment of the horizontal vane
0.5-second OFF
Left lamp flashes.
Detect Indoor coil/room temperature thermistor short or open circuit every 8 seconds during operation.
Outdoor unit does not operate.
2.5-second OFF
Indoor fan motor repeats 12 seconds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping.
When rotational frequency feedback signal is not emitting during 12-second indoor fan operation.
Left lamp flashes.
3 Indoor fan motor.
2.5-second OFF
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
Left lamp flashes.
Outdoor unit does not operate.
2.5-second OFF

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1
Check method and criterion
Room temperature thermistor (RT11)
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)
Indoor coil thermistor (RT12)
8k" ~ 20k"
Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)
tr a p r o t o M tr a p r o s n e S
Color of lead wire
Indoor fan motor (MF)
MAIN
AUX.
Measure the voltage Power ON.
Color of lead wire
4.5 ~ 5.5V
BLK RED WHT
Remain 0V or 5V (When fan revolved one time)
0V→ → 5V 0V (Approx.)
Measure the resistance between the terminals with a tester. (Part temperature10°C ~ 30°C) RED
Open or short-circuit 240 ~ 260"

When left OPERATION INDICATOR lamp flashes 3-time.
Indoor fan motor doesn’t operate.
A Check of indoor fan motor Turn OFF the power supply. Check connector CN211 visually.
Are lead wires connected? Is soldering point of the connector
Resolder it. Yes
Reconnect the lead wires.
Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board. Measure resistance between lead wires: No.1 and No.5 and then No.3 and No.5.
Insert screwdriver into air outlet to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage No.2(+) and No.3(-) on CN121.
Is resistance 0 (short circuit) or ∞ (open circuit)?
Yes ( 0 or ∞)
Repair the indoor fan motor.
Does voltage repeat 0V DC and 5V DC?
Replace the indoor electronic control P.C. board.
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.
B Check of remote controller and receiver P.C. board
w Check if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the remote con- troller visible?
Replace the batteries. (Refer to 8-1.4.)
Remove batteries, then set them back and press the RESET button. Check if the unit operates with remote controller.
Does the unit operate with remote controller?
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Replace the remote controller.
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
Measure the voltage between receiver P.C. board connector CN302 No.3(-) and No.5(+) when the remote controller button is pressed.
Is the voltage approx. 4V DC? Replace the indoor electronic control P.C. board
No(5V or 0V DC)
Replace the power monitor, receiver P.C.board.

The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
C Check of indoor electronic control P.C. board
Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
L N
CN201
F12
L N
Does the unit operate with the remote controller? Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?
Turn OFF the power supply.
Turn OFF the power supply.
Replace the vane motor.
Replace the fuse.
Replace the indoor electronic control P.C. board.
1.Pull out the power supply cord. 2.Measure the resistance between CN201 1 on the indoor electronic control P.C. board and on the terminal block with a tester.
Is the winding resistance of vane motor 0 "?
Is there resistance approx. 0 "?
Be sure to check both fuse and varistor in any case.
Be sure to check both resistance.
Is the winding resistance of fan motor 0 "?
Replace the fuse (F12).
Replace the fan motor.
Replace the varistor.

When both OPERATION INDICATOR lamps flash ON and OFF every 0.5-second.
Indoor unit and outdoor unit don’t operate.
D Check of installation of the horizontal vane
Turn OFF the power supply.
Relock the stopper of the horizontal vane to the indoor unit. Refer to 8-1-5.
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Turn ON the power supply.
Is the OPERATION INDICATOR lamp flashing?
To check the continuity of safety device, measure the resistance of connector 1 - 3 connected to CN1R1 on the indoor electronic control P.C. board.
Turn OFF the power supply.
Is there resistance 0 "?
Replace the safety device.
Replace the indoor electronic control P.C. board.

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1
Power supply input 220 - 230V AC
Fuse 250V AC 3.15A

Indoor fan motor 220 - 230V AC
Safety device of fan by horizontal vane CN1R1
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12)
{ 12V DC + – }
Timer short mode point JPG, JPS (Refer to 7-1.) Emergency operation switch
}
+ –
Power monitor, receiver P.C. board
J23 J33
Release of Auto restart function Solder the Jumper wire to the JR07. (Refer to 7-3.)

Indoor coil thermistor (RT12) Room temperature thermistor (RT11)
Resistance (k")
Varistor (NR12) · Varistor (NR11)

The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. Sleeve
1 Slide the sleeve. 2 Pull the terminal while pushing the locking lever.
1 Hold the sleeve, and pull out the terminal slowly. Connector
OPERATING PROCEDURE PHOTOS
catches at the top.

Screws of the panel
Terminal block fixing screw
P.C. board work (3) is not necessary. (1) Remove the panel. (Refer to 1.) (2) Remove the power monitor, receiver P.C. board holder from the bottom of electrical box. (3) Open the power monitor, receiver P.C. board holder and
Screw of the ground wire
Indoor electronic control P.C. board

remove the power monitor, receiver P.C. board. (4) Remove the screw of the electrical cover and the electrical
cover. (5) Remove the screw of the V.A. clamp and the V.A. clamp. (6) Remove the screw of the cord clamp and the cord clamp. (7) Remove the screw of the terminal block. (8) Remove the screw of the ground wire. (9) Pull out indoor electronic control P.C. board slightly. (10) Disconnect all (except CN125, CN109) the connectors on
Screw of the V.A. clamp
Screw of the electrical cover
the electronic control P.C. board. (11) Remove the electronic control P.C. board. (12) Disconnect the connector of power monitor, receiver P.C.
board (CN 125, CN109) on the electronic control P.C. board.
Power monitor, receiver P.C. board holder
Locking lever

Indoor coil thermistor connector

Screw of the electrical box
(CN112), the fan motor connector (CN211 and CN121) and the vane motor connector (CN151)on the electronic control P.C. board. (8) Remove the fan motor lead wire and indoor coil thermistor
from the electrical box. (9) Remove the lead wire of vane motor from the bottom of electrical box.
(10) Remove the screw fixing the electrical box, remove the electrical box.
Screws of the vane motor 4. Removing the nozzle assembly and the vane motor (1) Remove the panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove

the nozzle assembly. (4) Remove the screws of the vane motor, disconnect the vane motor connector. (5) Remove the vane motor.

remove the nozzle assembly. (Refer to 4.) (4) Remove the screw of the lead cover and lead cover. (5) Release the hooks to open the motor band slightly. (6) Loosen the hexagon socket set screw from the line flow
Screws of the left side of the heat exchanger
fan. (7) Remove the screws fixing the motor bed, and remove the
fan motor with motor band and the motor bed. (8) Remove the screws fixing the left side of the heat exchanger. (9) Lift the left side of the heat exchanger. (10) Remove the line flow fan.
Photo 6
Hexagon socket set screw


Screw of the lead cover
Screws of the motor bed
Hooks of the motor band
Vane motor connector · Fan motor connectors · Drain hose

MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD. AMATA NAKORN INDUSTRIAL ESTATE 700/406 MOO 7, TAMBON DON HUA ROH, AMPHUR MUANG, CHONBURI 20000 THAILAND Made in Thailand
New publication, effective Feb. 2008 Specifications subject to change without notice.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Indoor unit and outdoor unit do not operate. | • Refer to 8-5. D "Check of installation of the horizontal vane". | p.13 | |
| Outdoor unit does not operate. | • Refer to the characteristics of indoor coil thermistor and room temperature thermistor shown in 8-6. | p.13 | |
| Outdoor unit does not operate. | p.13 | ||
| Indoor fan motor repeats 12 seconds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping. | • Refer to 8-5.A "Check of indoor fan motor". | p.13 | |
| Outdoor unit does not operate. | • Replace the indoor electronic control P.C. board. | p.13 |