Table of Contents 80 sections SPLIT-TYPE, AIR CONDITIONERS · No. TBH014 · SERVICE MANUAL · Wireless type Models · … ShowHide
Page 2 of the Mitsumi electronic MSGD10ND user manual — MS-A10NDC1 ➔ MS-GD10NDC1
Page 2 · click to enlarge
Page 2

1 TECHNICAL CHANGES

MS-A08NDC1 ➔ MS-GD08NDC1 MS-A12NDC1 ➔ MS-GD12NDC1

1. Indoor unit has been changed. • Front panel has been changed. (Flat Flat Shining) 2. Terminal block has been changed. 3P (L~, N~, 2~) 4P (L~, N~, 2~, Earth)

MS-A10NDC1 ➔ MS-GD10NDC1

1. Indoor unit has been changed. • Front panel has been changed. (Flat Flat Shining)
Page 3 of the Mitsumi electronic MSGD10ND user manual — MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1
Page 3 · click to enlarge
Page 3

PART NAMES AND FUNCTIONS

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1 diagram (page 3)
Fig. 1
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1 diagram (page 3)
Fig. 2
MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1 1Installation plate1 2Installation plate fixing screw 4 x 25 mm5 3Remote controller holder1 4Fixing screw for 3 3.5 x 16 mm (Black)2 5Battery (AAA) for remote controller2 6Wireless remote controller1 7Felt tape (Used for left or left-rear piping)1 8Air cleaning filter2
Page 4 of the Mitsumi electronic MSGD10ND user manual — RESET
Page 4 · click to enlarge
Page 4

REMOTE CONTROLLER

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

These buttons are able to store the light from nature, fluorescent lamp, etc and shine in the dark.

ON/OFF

TOO WARM

TOO COOL

ECONO COOL

FAN

I FEEL COOL

FAN SPEED CONTROL button

DRY FAN

POWERFUL COOL

VANE

TIME MODE

SELECT

Indication of remote controller model is on back.

TIMER MODE SELECT button

RESET

SPECIFICATION 3

Indoor modelMS-GD08NDC1MS-GD10NDC1MS-GD12NDC1 FunctionCooling Power supplySingle phase 220-230V, 60Hz CapacityAir flow (High/Med/Low)K/h588/456/372630/498/336666/498/336 Electrical dataPower outletA10 Running currentA0.19 Power inputW40 Auxiliary heaterA (kW)— Power factor%96-92 Fan motor currentA0.19 Fan motorModelRC4N19-BA Winding resistance (at 20ºC)"WHT-BLK 312 BLK-RED 255 Dimensions WoHoDmm815o278o244 Weightkg910 Special remarksAir direction5 Sound level (High/Med/Low)dB39/32/2639/32/2642/36/29 Fan speed (High/Med/Low)rpm1030/800/650960/800/6501000/800/650 Fan speed regulator3 Thermistor RT11 (at 25ºC)kΩ10 Thermistor RT12 (at 25ºC)kΩ10 Remote controller modelMP2B
Show 11 more labels / short text on this page
Signal transmitting section · Operation display section · h · OPERATE/STOP (ON/OFF) button · TEMPERATURE buttons · ECONO COOL button · VANE CONTROL button · POWERFUL COOL button · OPERATION SELECT button · TIME SET button · RESET button
Page 5 of the Mitsumi electronic MSGD10ND user manual — [ 21 I.D {
Page 5 · click to enlarge
Page 5

OUTLINES AND DIMENSIONS 4

MS-GD08NDC1

Unit : mm

81.5 133.5

5. 1 3 2

81.5 81.5

Wall hole [65

[ 21 I.D {

e r o m r o 7

Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [37 O.D

Drain hose [16 (Connected part O.D)

161.5 161.5

MS-GD10NDC1 MS-GD12NDC1

5. 7 1
5. 8 1 2

81.5 81.5

Wall hole [65

[ 21 I.D {

Liquid line [6.35-0.5m Gas line

[9.52-0.43m

e r o m r o 7

Insulation [37 O.D

Drain hose [16 (Connected part O.D)

Show 16 more labels / short text on this page
Installation plate · 326 326 · Air in · Installation plate · 149 606 · Air out · Insulation [28 · Wireless remote controller · Installation plate · 326 326 · Air in · Installation plate · 149 606 · Air out · Insulation [28 · Wireless remote controller
Page 6 of the Mitsumi electronic MSGD10ND user manual — MS-GD10NDC1
Page 6 · click to enlarge
Page 6

WIRING DIAGRAM 5

MS-GD08NDC1 MS-GD12NDC1

Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 3
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 4
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 5
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 6
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 7
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 8
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 9
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 10
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 11
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD12NDC1 diagram (page 6)
Fig. 12

MS-GD10NDC1

Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 13
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 14
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 15
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 16
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 17
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 18
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 19
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 20
Mitsumi electronic MSGD10ND — MS-GD10NDC1 diagram (page 6)
Fig. 21
Page 7 of the Mitsumi electronic MSGD10ND user manual — RT11
Page 7 · click to enlarge
Page 7

REFRIGERANT SYSTEM DIAGRAM 6

MS-GD08NDC1 MS-GD10NDC1

MS-GD12NDC1

Refrigerant pipe (Option){12.7 (with heat insulator)

Refrigerant pipe (Option){9.52 (with heat insulator)

Indoor coil thermistor RT12

Indoor coil thermistor RT12

RT11

RT11

Refrigerant pipe (Option){6.35 (with heat insulator)

Refrigerant pipe (Option){6.35 (with heat insulator)

Refrigerant flow in cooling

Show 8 more labels / short text on this page
Indoor heat exchanger · Indoor heat exchanger · Flared connection · Flared connection · Room temperature thermistor · Room temperature thermistor · Flared connection · Flared connection
Page 8 of the Mitsumi electronic MSGD10ND user manual — Table 1
Page 8 · click to enlarge
Page 8

SERVICE FUNCTIONS 7

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 8-6.) Set time : 1-minute 1-second Set time : 3-minute 3-second It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.

7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.

How to modify the remote controller P.C. board Remove batteries before modification. The board has a print as shown below :

Remote controller modelMP2B
Mitsumi electronic MSGD10ND — MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1 diagram (page 8)
Fig. 22

J2 J1

teries and push the OPERATE/ STOP(ON/OFF)button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.

The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.

Table 1

1 unit operation2 units operation3 units operation4 units operation No. 1 unitNo modificationSame as at leftSame as at leftSame as at left No. 2 unit—Solder J1Same as at leftSame as at left No. 3 unit——Solder J2Same as at left No. 4 unit———Solder both J1 and J2

How to set the remote controller exclusively for particular indoor unit After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.

Page 9 of the Mitsumi electronic MSGD10ND user manual — CN151
Page 9 · click to enlarge
Page 9

7-3. AUTO RESTART FUNCTION

When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature.

Operation 1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit automatically resumes the same operation as the memory has recorded. However, it takes the compressor at least 3 minutes to get started.

52C/X10

CN211

CN201

How to release “AUTO RESTART FUNCTION” 1 Turn off the main power for the unit. 2 Pull out the indoor electronic control P.C. board and the power monitor, receiver

CN1R1 CN121

CN1V1

CN111

P.C. board. (Refer to 9-1.) 3 Solder the Jumper wire to the JR07 on the indoor electronic control P.C.board.

CN112

SW1

(Refer to 8-6.)

CN151

JR07

  • controller.
  • If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is cancelled.
  • If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off.
  • To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same time.
  • When some air conditioners are connected to the same supply system, if they are operated before power failure, the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
Page 10 of the Mitsumi electronic MSGD10ND user manual — Lead wiring Housing point
Page 10 · click to enlarge
Page 10

TROUBLESHOOTING 8

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

8-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during servicing. 1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the electronic control P.C. board. 3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

Lead wiring Housing point

3. Troubleshooting procedure 1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work. 2) Before servicing that the connector and terminal are connected properly. 3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discolouration. 4) When troubleshooting, refer to 8-2. and 8-3. 4. How to replace batteries Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.

1 Remove the back lid and insert batteries. Then reattach the back lid.

2 Press the RESET button with tip end of ball point pen or the like, and then use the remote controller.

Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.

RESET button

Page 11 of the Mitsumi electronic MSGD10ND user manual — TROUBLESHOOTING 8
Page 11 · click to enlarge
Page 11
5. How to install the horizontal vanes

If horizontal vanes are not installed correctly, both of the operation indicator lamps will flash. In this case, install the horizontal vanes correctly by following the procedures 1 to 6.

Mitsumi electronic MSGD10ND — TROUBLESHOOTING 8 diagram (page 11)
Fig. 23

Insert this end first.

The holes on the insertion ends of the upper and lower horizontal vanes have different shapes.

Insert this end first.

In procedure 2,3,5, and 6, lock the stoppers until they click into place.

Show 4 more labels / short text on this page
Upper vane · Upper right · Lower vane · Lower right
Page 12 of the Mitsumi electronic MSGD10ND user manual — 8-2. Instruction of troubleshooting
Page 12 · click to enlarge
Page 12

8-2. Instruction of troubleshooting

Indoor unit operates. Outdoor unit doesn't operate.

Indoor unit doesn't receive the signal from remote controller.

OPERATION INDICATOR lamp on the indoor unit is flashing on and off.

Outdoor unit doesn't operate even in Test run operation.

Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.

Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.

Outdoor unit operates in only Test run operation.

Check room temperature thermistor. Refer to 8-6. "Test point diagram and voltage".

Check of wiring diagram of outdoor unit.

Refer to 8-5. B "Check of remote controller and receiver P.C. board".

1. Check indoor / outdoor connecting wire. 2. Refer to 8-5. C "Check of indoor electronic control P.C. board".

As for outdoor unit, refer to service manual TBH016 Both lamps (Left and right) Flash on and off at 0.5-second intervals Cause: Indoor unit • The horizontal vanes are not installed correctly.

Left lamp 2-time flash CauseIndoor unit • Trouble of room temperature/ indoor coil thermistor
Left lamp 3-time flash CauseIndoor unit • Trouble of indoor fan motor
Left lamp 4-time flash CauseIndoor unit • Trouble of indoor control system

Check room temperature thermistor and indoor coil thermistor. Refer to 8-6. "Test point diagram and voltage".

Refer to 8-5.A "Check of indoor fan motor".

Refer to 8-5. D "Check of installation of the horizontal vane".

Replace the indoor electronic control P.C. board.

Start

Page 13 of the Mitsumi electronic MSGD10ND user manual — 8-3. Troubleshooting check table
Page 13 · click to enlarge
Page 13

8-3. Troubleshooting check table

  • The following indication applies regardless of shape of the indicator.

Operation Indicator · Flashing of the OPERATION INDICATOR lamp (on the left) indicates possible abnormalities. · The OPERATION INDICATOR lamp (on the left) is lighting during normal operation.

Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table

No.

Symptom Indication Detection method Check point

Both lamps flash at the same time.

  • Refer to 8-5. D "Check of installation of the horizontal vane". Indoor unit and outdoor unit do not operate.

When the electricity is not conducted to the safety device (FAN) of the horizontal vane.

1 0.5-second ON

Attachment of the horizontal vane

0.5-second OFF

  • Refer to the characteristics of indoor coil thermistor and room temperature thermistor shown in 8-6.

Left lamp flashes.

Detect Indoor coil/room temperature thermistor short or open circuit every 8 seconds during operation.

Outdoor unit does not operate.

2.5-second OFF

Indoor fan motor repeats 12 seconds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping.

  • Refer to 8-5. A "Check of indoor fan motor".

When rotational frequency feedback signal is not emitting during 12-second indoor fan operation.

Left lamp flashes.

3 Indoor fan motor.

2.5-second OFF

When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.

  • Replace the indoor electronic control P.C. board.

Left lamp flashes.

Outdoor unit does not operate.

2.5-second OFF

Show 9 more labels / short text on this page
flashing · Abnormal · point · Indoor coil thermistor · 2-time flash · Room tempera- ture thermistor · 3-time flash · Indoor control system · 4-time flash
Page 14 of the Mitsumi electronic MSGD10ND user manual — ORN GRN
Page 14 · click to enlarge
Page 14

8-4. Trouble criterion of main parts

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

Check method and criterion

Room temperature thermistor (RT11)

Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)

Indoor coil thermistor (RT12)

8k" ~ 20k"

Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)

tr a p r o t o M tr a p r o s n e S

Color of lead wire

299~324 " WHT-BLK

Indoor fan motor (MF)

BLK-RED

MAIN

INNER FUSE 145 i 2CUT OFF

AUX.

Measure the voltage Power ON.

FUSE

Color of lead wire

BRN-YLW

4.5 ~ 5.5V

BLK RED WHT

Remain 0V or 5V (When fan revolved one time)

YLW-GRY

0V→ → 5V 0V (Approx.)

Measure the resistance between the terminals with a tester. (Part temperature10°C ~ 30°C) RED

YLW BRN

Open or short-circuit 240 ~ 260"

ORN GRN

Show 13 more labels / short text on this page
Part name · Figure · Normal · Abnormal · Open or short-circuit · Normal · Abnormal · Open or short-circuit · 244~265" · Normal · Abnormal · ROTOR Normal Abnormal · Vane motor (MV)
Page 15 of the Mitsumi electronic MSGD10ND user manual — OK
Page 15 · click to enlarge
Page 15

8-5. Troubleshooting flow

When left OPERATION INDICATOR lamp flashes 3-time.

Indoor fan motor doesn’t operate.

A Check of indoor fan motor Turn OFF the power supply. Check connector CN211 visually.

Are lead wires connected? Is soldering point of the connector

Resolder it. Yes

Reconnect the lead wires.

Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board. Measure resistance between lead wires: No.1 and No.5 and then No.3 and No.5.

Insert screwdriver into air outlet to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage No.2(+) and No.3(-) on CN121.

Is resistance 0 (short circuit) or ∞ (open circuit)?

Yes ( 0 or ∞)

Repair the indoor fan motor.

Does voltage repeat 0V DC and 5V DC?

Replace the indoor electronic control P.C. board.

Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.

B Check of remote controller and receiver P.C. board

w Check if the remote controller is exclusive for this air conditioner.

Switch on the remote controller.

Is LCD display on the remote con- troller visible?

Replace the batteries. (Refer to 8-1.4.)

Remove batteries, then set them back and press the RESET button. Check if the unit operates with remote controller.

Does the unit operate with remote controller?

Turn on a radio to AM and press switch on the remote controller.

Is noise heard from radio?

Replace the remote controller.

OK

Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?

  • Reinstall the unit away from lights.
  • Attach a filter on receiving part.

Measure the voltage between receiver P.C. board connector CN302 No.3(-) and No.5(+) when the remote controller button is pressed.

Is the voltage approx. 4V DC? Replace the indoor electronic control P.C. board

No(5V or 0V DC)

Replace the power monitor, receiver P.C.board.

Show 15 more labels / short text on this page
No No Yes · correctly soldered? · No (others) · No · Yes · No · (not clear) · Yes · No · Yes · No · Yes · Yes · No · Yes
Page 16 of the Mitsumi electronic MSGD10ND user manual — CN201 1 2
Page 16 · click to enlarge
Page 16

The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.

C Check of indoor electronic control P.C. board

MS-GD10ND MS-GD08/GD12ND

Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.

Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.

CN201 1 2

L N

CN201

F12

L N

Does the unit operate with the remote controller? Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?

Turn OFF the power supply.

Turn OFF the power supply.

Replace the vane motor.

Replace the fuse.

Replace the indoor electronic control P.C. board.

1.Pull out the power supply cord. 2.Measure the resistance between CN201 1 on the indoor electronic control P.C. board and on the terminal block with a tester.

Is the winding resistance of vane motor 0 "?

Is there resistance approx. 0 "?

Be sure to check both fuse and varistor in any case.

Be sure to check both resistance.

Is the winding resistance of fan motor 0 "?

Replace the fuse (F12).

Replace the fan motor.

Replace the varistor.

Show 16 more labels / short text on this page
Terminal block · No · Terminal block · Yes · Yes · Yes · No · No · Is fuse(F11) blown? · Yes · No(∞) · No · Is varistor(NR11) burnt? · No · Yes · Yes
Page 17 of the Mitsumi electronic MSGD10ND user manual — OK
Page 17 · click to enlarge
Page 17

When both OPERATION INDICATOR lamps flash ON and OFF every 0.5-second.

Indoor unit and outdoor unit don’t operate.

D Check of installation of the horizontal vane

Turn OFF the power supply.

Relock the stopper of the horizontal vane to the indoor unit. Refer to 8-1-5.

Is the stopper of the horizontal vane locked to the indoor unit correctly?

Turn ON the power supply.

Is the OPERATION INDICATOR lamp flashing?

OK

To check the continuity of safety device, measure the resistance of connector 1 - 3 connected to CN1R1 on the indoor electronic control P.C. board.

Turn OFF the power supply.

Is there resistance 0 "?

Replace the safety device.

Replace the indoor electronic control P.C. board.

Show 7 more labels / short text on this page
Start · No · Yes · No · Yes · No(∞) · Yes
Page 18 of the Mitsumi electronic MSGD10ND user manual — CN302
Page 18 · click to enlarge
Page 18

8-6. Test point diagram and voltage

MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

Power supply input 220 - 230V AC

Indoor electronic control P.C. board

Fuse 250V AC 3.15A

}

Mitsumi electronic MSGD10ND — } diagram (page 18)
Fig. 24

}

Indoor fan motor 220 - 230V AC

Safety device of fan by horizontal vane CN1R1

Room temperature thermistor (RT11)

Indoor coil thermistor (RT12)

J12

{ 12V DC + – }

Timer short mode point JPG, JPS (Refer to 7-1.) Emergency operation switch

J33

}

+ –

Power monitor, receiver P.C. board

J23 J33

Release of Auto restart function Solder the Jumper wire to the JR07. (Refer to 7-3.)

Mitsumi electronic MSGD10ND — J33 diagram (page 18)
Fig. 25

}

5V DC

Indoor coil thermistor (RT12) Room temperature thermistor (RT11)

CN302

Resistance (k")

Temperature ()

Varistor (NR12) · Varistor (NR11)

Page 19 of the Mitsumi electronic MSGD10ND user manual — Photo 2
Page 19 · click to enlarge
Page 19

DISASSEMBLY INSTRUCTIONS 9

<”Terminal with locking mechanism” Detaching points>

The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.

(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. Sleeve

1 Slide the sleeve. 2 Pull the terminal while pushing the locking lever.

1 Hold the sleeve, and pull out the terminal slowly. Connector

9.1 MS-GD08NDC1 MS-GD10NDC1 MS-GD12NDC1

OPERATING PROCEDURE PHOTOS

1. Removing the panel (1) Remove the screw caps of the panel. Remove the screws. (2) Pull the panel down to your side slightly and unhook the

Photo 1

catches at the top.

Mitsumi electronic MSGD10ND — Photo 1 diagram (page 19)
Fig. 26 · Photo 1

Screws of the panel

2. Removing the electronic control P.C. board and the power monitor, receiver P.C. board NOTE : In case of removing only indoor electronic control

Photo 2

Terminal block fixing screw

P.C. board work (3) is not necessary. (1) Remove the panel. (Refer to 1.) (2) Remove the power monitor, receiver P.C. board holder from the bottom of electrical box. (3) Open the power monitor, receiver P.C. board holder and

Screw of the ground wire

Indoor electronic control P.C. board

Mitsumi electronic MSGD10ND — Photo 2 diagram (page 19)
Fig. 27 · Photo 2

remove the power monitor, receiver P.C. board. (4) Remove the screw of the electrical cover and the electrical

cover. (5) Remove the screw of the V.A. clamp and the V.A. clamp. (6) Remove the screw of the cord clamp and the cord clamp. (7) Remove the screw of the terminal block. (8) Remove the screw of the ground wire. (9) Pull out indoor electronic control P.C. board slightly. (10) Disconnect all (except CN125, CN109) the connectors on

Screw of the V.A. clamp

Screw of the electrical cover

the electronic control P.C. board. (11) Remove the electronic control P.C. board. (12) Disconnect the connector of power monitor, receiver P.C.

board (CN 125, CN109) on the electronic control P.C. board.

Power monitor, receiver P.C. board holder

Locking lever

Page 20 of the Mitsumi electronic MSGD10ND user manual — Photo 7
Page 20 · click to enlarge
Page 20

OPERATING PROCEDURE PHOTOS

3. Removing the electrical box (1) Remove the panel. (Refer to 1.) (2) Remove the electrical cover. (Refer to 2.) (3) Remove the V.A. clamp. (Refer to 2.) (4) Remove the cord clamp. (Refer to 2.) (5) Remove the terminal block. (Refer to 2.) (6) Remove the screw of ground wire. (Refer to 2.) (7) Disconnect the connector of the indoor coil thermistor

Photo 3

Indoor coil thermistor connector

Mitsumi electronic MSGD10ND — Photo 3 diagram (page 20)
Fig. 28 · Photo 3

Screw of the electrical box

(CN112), the fan motor connector (CN211 and CN121) and the vane motor connector (CN151)on the electronic control P.C. board. (8) Remove the fan motor lead wire and indoor coil thermistor

from the electrical box. (9) Remove the lead wire of vane motor from the bottom of electrical box.

(10) Remove the screw fixing the electrical box, remove the electrical box.

Screws of the vane motor 4. Removing the nozzle assembly and the vane motor (1) Remove the panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove

Photo 4

Mitsumi electronic MSGD10ND — Photo 4 diagram (page 20)
Fig. 29 · Photo 4

the nozzle assembly. (4) Remove the screws of the vane motor, disconnect the vane motor connector. (5) Remove the vane motor.

5. Removing the indoor fan motor and the line flow fan (1) Remove the panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, and

Photo 5

Mitsumi electronic MSGD10ND — Photo 5 diagram (page 20)
Fig. 30 · Photo 5

remove the nozzle assembly. (Refer to 4.) (4) Remove the screw of the lead cover and lead cover. (5) Release the hooks to open the motor band slightly. (6) Loosen the hexagon socket set screw from the line flow

Screws of the left side of the heat exchanger

fan. (7) Remove the screws fixing the motor bed, and remove the

fan motor with motor band and the motor bed. (8) Remove the screws fixing the left side of the heat exchanger. (9) Lift the left side of the heat exchanger. (10) Remove the line flow fan.

Photo 7

Photo 6

Hexagon socket set screw

Mitsumi electronic MSGD10ND — Photo 7 diagram (page 20)
Fig. 31 · Photo 7
Mitsumi electronic MSGD10ND — Photo 7 diagram (page 20)
Fig. 32 · Photo 7

Screw of the lead cover

Screws of the motor bed

Hooks of the motor band

Vane motor connector · Fan motor connectors · Drain hose

Page 21 of the Mitsumi electronic MSGD10ND user manual — TM
Page 21 · click to enlarge
Page 21

TM

HEAD OFFICETOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD. AMATA NAKORN INDUSTRIAL ESTATE 700/406 MOO 7, TAMBON DON HUA ROH, AMPHUR MUANG, CHONBURI 20000 THAILAND Made in Thailand

New publication, effective Feb. 2008 Specifications subject to change without notice.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Indoor unit and outdoor unit do not operate.• Refer to 8-5. D "Check of installation of the horizontal vane". p.13
Outdoor unit does not operate.• Refer to the characteristics of indoor coil thermistor and room temperature thermistor shown in 8-6. p.13
Outdoor unit does not operate. p.13
Indoor fan motor repeats 12 seconds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping.• Refer to 8-5.A "Check of indoor fan motor". p.13
Outdoor unit does not operate.• Replace the indoor electronic control P.C. board. p.13

Ask about the Mitsumi electronic MSGD10ND

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsumi electronic MSGD10ND

Be the first to ask — other owners or our team will answer.

Original document

Mitsumi electronic MSGD10ND manual PDF

21 pages·3.4 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…