
User's Manual

Mitsubishi Programmable Logic Controller



Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. For the safety instructions of the programmable logic controller system, please read the CPU module User's Manual. In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Please save this manual to make it accessible when required and always forward it to the end user.
! DANGER
Provide a safety circuit outside the programmable logic controller so that the entire system will
operate safely even when an external power supply error or PLC fault occurs.
Failure to observe this could lead to accidents for incorrect outputs or malfunctioning. (1) Configure an emergency stop circuit and interlock circuit such as a positioning upper
limit/lower limit to prevent mechanical damage outside the PLC. (2) The machine OPR operation is controlled by the OPR direction and OPR speed data.
Deceleration starts when the near-point dog turns ON. Thus, if the OPR direction is incorrectly set, deceleration will not start and the machine will continue to travel. Configure an interlock circuit to prevent mechanical damage outside the PLC. (3) When the module detects an error, normally deceleration stop or sudden stop will take
place according to the parameter stop group settings. Set the parameters to the positioning system specifications. Make sure that the OPR parameter and positioning data are within the parameter setting values.

! CAUTION
Do not bundle or adjacently lay the control wire or communication cable with the main circuit or
power wire.
Separate these by 100mm (3.94in.) or more.
Failure to observe this could lead to malfunctioning caused by noise.
! CAUTION
Use the PLC within the general specifications environment given in this manual.
Using the PLC outside the general specification range environment could lead to electric shocks, fires, malfunctioning, product damage or deterioration. While pressing the installation lever located at the bottom of module, insert the module fixing
tab into the fixing hole in the base unit until it stops. Then, securely mount the module with the fixing hole as a supporting point.
Incorrect loading of the module can cause a malfunction, failure or drop. When using the PLC in the environment of much vibration, tighten the module with a screw. Tighten the screw in the specified torque range. Undertightening can cause a drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to damage to the screw or module. Completely turn off the externally supplied power used in the system before mounting or
removing the module. Not doing so may damage the product.
! DANGER
Always confirm the terminal layout before connecting the wires to the module.
! DANGER
Completely turn off the externally supplied power used in the system before cleaning or
tightening the screws. Failure to turn all phases OFF could lead to electric shocks.

! CAUTION
Never disassemble or modify the module.
Failure to observe this could lead to trouble, malfunctioning, injuries or fires. Completely turn off the externally supplied power used in the system before installing or
removing the module.
Failure to turn all phases OFF could lead to module trouble or malfunctioning. Do not mount/remove the module onto/from the base unit more than 50 times (IEC61131-2-
compliant), after the first use of the product. Failure to do so may cause malfunction.
Before starting test operation, set the parameter speed limit value to the slowest value, and
make sure that operation can be stopped immediately if a hazardous state occurs.
Always make sure to touch the grounded metal to discharge the electricity charged in the body,
etc., before touching the module. Failure to do so may cause a failure or malfunctions of the module.
! CAUTION
the partner axis (2nd axis, 3rd axis and 4th axis) may be larger than the set speed (larger than the speed limit value).
! CAUTION
When disposing of the product, handle it as industrial waste.


Japanese Manual Version SH-0800047-L
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
A - 5


The following manuals are also related to this product. In necessary, order them by quoting the details in the tables below.
Manual Name Manual Number
Type QD75P/QD75D Positioning Module User's Manual
Describes the performance, specifications, I/O interface, component names, and startup procedure of
the respective positioning modules: QD75P1, QD75P2, QD75P4, QD75D1, QD75D2, and QD75D4.
(The manual is supplied with the module.)
GX Configurator-QP Operating Manual
Describes how to use GX Configurator-QP for the following and other purposes: creating data
(parameters, positioning data, etc.), sending the data to the module, monitoring the positioning
operations, and testing. (The manual is supplied with the software.)
The symbols used in this manual are shown below.
Pr Symbol indicating positioning parameter and OPR parameter item. Da Symbol indicating positioning data, block start data and condition data item. Md Symbol indicating monitor data item. Cd Symbol indicating control data item.
(A serial No. is inserted in the mark.)
Representation of numerical values used in this manual.
Buffer memory addresses, error codes and warning codes are represented in
decimal. X/Y devices are represented in hexadecimal. Setting data and monitor data are represented in decimal or hexadecimal. Data
ended by "H" are represented in hexadecimal.
(Example) 10 Decimal
10H Hexadecimal
Conformation to the EMC AND LOW-VOLTAGE DIRECTIVES
For details on making Mitsubishi PLC conform to the EMC and Low Voltage Directives when installing it in your product, please refer to Chapter 3, “EMC AND LOW-VOLTAGE DIRECTIVES” of the using PLC CPU module User’s Manual (Hardware). The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC and Low Voltage Directives. To make this product conform to the EMC and Low Voltage Directives, please refer to Section 4.3.1 "Precautions for wiring".

Generic Terms and Abbreviations
Unless specially noted, the following generic terms and abbreviations are used in this manual.
Generic term/abbreviation Details of generic term/abbreviation
PLC CPU Generic term for PLC CPU on which QD75 can be mounted.
QD75 Generic term for positioning module QD75P1, QD75P2, QD75P4, QD75D1, QD75D2, and QD75D4. The module type is described to indicate a specific module.
Peripheral device Generic term for DOS/V personal computer that can run the following "GX Developer" and "GX Configurator-QP".
GX Configurator-QP Abbreviation for GX Configurator-QP (SW2D5C-QD75P-E or later).
GX Developer Abbreviation for GX Developer (SW4D5C-GPPW-E or later).
Drive unit (servo amplifier) Abbreviation for pulse input compatible drive unit (servo amplifier).
Manual pulse generator Abbreviation for manual pulse generator (prepared by user).
DOS/V personal computer IBM PC/AT® and compatible DOS/V compliant personal computer.
Personal computer Generic term for DOS/V personal computer.
Workpiece Generic term for moving body such as workpiece and tool, and for various control targets.
Axis 1, axis 2, axis 3, axis 4
Indicates each axis connected to QD75.
1-axis, 2-axis, 3-axis, 4-axis Indicates the number of axes. (Example: 2-axis = Indicates two axes such as axis 1 and axis 2, axis 2 and axis 3, and axis 3 and axis 1.)

The table below shows the component included in respective positioning modules:
Module name Description Quantity
QD75P1 QD75P1 Positioning Module(1-axis open collector output system) 1
QD75P2 QD75P2 Positioning Module(2-axes open collector output system) 1
QD75P4 QD75P4 Positioning Module(4-axes open collector output system) 1
QD75D1 Positioning Module(1-axis differential driver output system) 1 QD75D1
Differential driver common terminal 1
QD75D2 Positioning Module(2-axes differential driver output system) 1 QD75D2
Differential driver common terminal 1
QD75D4 Positioning Module(4-axes differential driver output system) 1 QD75D4
Differential driver common terminal 1
Component List


Section 1
Section 1 is configured for the following purposes (1) to (5).
(1) To understand the outline of positioning control, and the QD75 specifications and functions (2) To carry out actual work such as installation and wiring (3) To set parameters and data required for positioning control (4) To create a sequence program required for positioning control (5) To understand the memory configuration and data transmission process
Read Section 2 for details on each control.
Chapter 1 Product outline 1- 1 to 1- 22
Chapter 2 System configuration 2- 1 to 2- 6
Chapter 3 Specifications and Functions 3- 1 to 3- 24
Chapter 4 Installation, Wiring and Maintenance of the Product 4- 1 to 4- 16
Chapter 5 Data Used for Positioning Control 5- 1 to 5-132
Chapter 6 Sequence Program Used for Positioning Control 6- 1 to 6- 44
Chapter 7 Memory Configuration and Data Process 7- 1 to 7- 12


The purpose and outline of positioning control using QD75 are explained in this chapter. Reading this chapter will help you understand what can be done using the positioning system and which procedure to use for a specific purpose.
By understanding "What can be done", and "Which procedure to use" beforehand, the positioning system can be structured smoothly.
1.1 Positioning control 1- 2 1.1.1 Features of QD75 1- 2 1.1.2 Purpose and applications of positioning control 1- 5 1.1.3 Mechanism of positioning control 1- 7 1.1.4 Outline design of positioning system 1- 9 1.1.5 Communicating signals between QD75 and each module 1- 12 1.2 Flow of system operation 1- 15 1.2.1 Flow of all processes 1- 15 1.2.2 Outline of starting 1- 18 1.2.3 Outline of stopping 1- 20 1.2.4 Outline for restarting 1- 21 1.3 Restrictions with a system using a stepping motor 1- 22 1.4 Function additions/modifications according to function version B 1- 22

1.1.1 Features of QD75
The features of the QD75 are shown below.
(a) One, two and four axis modules are available for both the open collector system pulse output (QD75P1, QD75P2, and QD75P4) and differential driver system pulse output (QD75D1, QD75D2, and QD75D4), comprising six different models. A model is determined by the drive unit type and number of axes. (Refer to Section 2.2.)
(b) For connecting any of the QD75 modules to the base unit, a single slot and 32 dedicated I/O channels are required. Within the limit imposed by the maximum number of inputs and outputs supported by the PLC CPU, up to 64 modules can be used. (Refer to Section 3.1.)
(a) A wide variety of positioning control functions essential to any positioning system are supported: positioning to an arbitrary position, fixed-feed control, equal-speed control, and so on. (Refer to Section 5.3 and 9.2.) 1) Up to 600 positioning data items, including such information as positioning addresses, control systems, and operation patterns, can be prepared for each axis. Using the prepared positioning data, the positioning control is performed independently for each axis. (In addition, such controls as interpolation involving two to four axes and simultaneous startup of multiple axes are possible.) 2) Independent control of each axis can be achieved in linear control mode (executable simultaneously over four axes). Such control can either be the independent positioning control using a single positioning data or the continuous positioning control enabled by the continuous processing of multiple positioning data. 3) Coordinated control over multiple axes can take the form of either the linear interpolation through the speed or position control of two to four axes or the circular interpolation involving two axes. Such control can either be the independent positioning control using a single positioning data or the continuous positioning control enabled by the continuous processing of multiple positioning data. (b) For each positioning data, the user can specify any of the following control systems: position control, speed control, speed-position switching control, position-speed switching control, and so on. (Refer to Section 5.3 and 9.2.)

(c) Continuous positioning control using multiple positioning data can be executed in accordance with the operation patterns the user assigned to the positioning data. (Refer to Section 5.3 and 9.1.2) Continuous positioning control can be executed over multiple blocks, where each block consists of multiple positioning data. (Refer to Section 10.3.2.)
(d) OPR control is given additional features (Refer to Section 8.2.)
(e) Two acceleration/deceleration control methods are provided: automatic trapezoidal acceleration/deceleration and S-pattern acceleration/deceleration. (Refer to Section 12.7.7.) (The S-pattern acceleration/deceleration control is disabled if stepping motors are used. Refer to Section 1.3.)
A positioning operation starts up quickly taking as little as 6 ms to 7 ms. When operation using simultaneous start function or interpolation operation is executed, the axes start without delay.
(Example) Axis 1 and Axis 3 are started by the simultaneous start function
: No delay in Axis 1 and
Axis 3 start Axis 2 and Axis 4 are started by the interpolation operation
: No delay in Axis 2 and
Each QD75 positioning module incorporates the following improvements in maintainability:
(a) Data such as the positioning data and parameters can be stored on a flash ROM inside the QD75, eliminating the need of a battery for retaining data. (Refer to Section 7.1.1.)
(b) Error messages are classified in more detail to facilitate the initial troubleshooting procedure. (Refer to Section 15.1.)
(c) The module retains 16 error messages and 16 warning messages recently output, offering more complete error and warning histories. (Refer to Section 5.6.1.)
Axis 4 start

Dedicated instructions such as the absolute position restoration instruction, positioning start instruction, and teaching instruction are provided. The use of such dedicated instruction simplifies sequence programs.(Refer to Chapter 14.)
Using GX Configurator-QP, the user can control the QD75 parameters and positioning data without having to be conscious of the buffer memory addresses. Moreover, GX Configurator-QP has a test function which allows the user to check the wiring before creating a sequence program for positioning control, or test operation the QD75 using created parameters and positioning data for checking their integrity. The control monitor function of GX Configurator-QP allows the user to debug programs efficiently.

"Positioning" refers to moving a moving body, such as a workpiece or tool (hereinafter, generically called "workpiece") at a designated speed, and accurately stopping it at the target position. The main application examples are shown below.
Punch press (X, Y feed positioning)
Gear and ball screw
320mm 160mm 15m/min (2000r/min)

Y axis X axis
15m/min (1875r/min) 12 s
X axis Gear and rack & pinion X axis servomotor PLC MELSEC-Q
AD75

Ball screw (From QD75)
QD75
AD75
Compact machining center (ATC magazine positioning)

Positioning pin Tool (12 pcs., 20 pcs.)
Rotation direction for calling 11, 12, 1, 2 or 3
Rotation direction for calling 17 to 20, 1 to 5
Current value retrieval position
Current value retrieval position
Rotation direction for calling 5, 6, 7, 8, 9 or 10
Rotation direction for calling 7 to 16

Lifter (Storage of Braun tubes onto aging rack)

Lifter C conveyor Counter- weight A conveyor Servo amplifier
G1 QD75
PLC MELSEC-Q Servo amplifier
Index table (High-accuracy indexing of angle)
QD75 • The index table is positioned at a high accuracy using the 1-axis servo.

PLC MELSEC-Q
Detector Servomotor Worm gears

Fix the grinding stone, feed the workpiece, and grind.
a. Total feed amount (mm) b. Finishing feed amount (mm) c. Compensation amount (mm)
d. Rough grind- ing speed (mm/s) e. Fine grinding speed (mm/s)

Positioning control using the QD75 is carried out with "pulse signals". (The QD75 is a module that generates pulses). In the positioning system using the QD75, various software and devices are used for the following roles. The QD75 realizes complicated positioning control when it reads in various signals, parameters and data and is controlled with the PLC CPU.
Stores the created program.
The QD75 outputs the start signal and stop signal following the stored program.
Creates control order and conditions as a sequence program.
QD75 errors, etc., are detected.
GX Developer PLC CPU
Outputs signals such as the start signal, stop signal, limit signal and control changeover signal to the QD75.
Issues commands by transmitting pulses.
Sets the parameters and positioning data for control.
Stores the parameter and data.
Outputs the start command for JOG operation, etc., during test operation with the test mode.
Outputs pulses to the servo according to the instructions from the PLC CPU, GX Configurator-QP, external signals and manual pulse generator.
Monitors the positioning operation. Servo amplifier
Receives pulse commands from QD75, and drives the motor.
Outputs the drive unit READY signal and zero signal to the QD75.
Carries out the actual work according to commands from the servo.

The principle of "position control" and "speed control" operation is shown below.
The total No. of pulses required to move the designated distance is obtained in the following manner.
Total No. of pulses required to move designated distance
Designated distance Movement amount of machine (load) side when motor rotates once
No. of pulses required for motor to rotate once
The No. of pulses required for the motor to rotate once is the "encoder resolution" described in the motor catalog specification list.
When this total No. of pulses is issued from the QD75 to the servo amplifier, control to move the designated distance can be executed. The machine side movement amount when one pulse is issued to the servo amplifier is called the "movement amount per pulse". This value is the min. value for the workpiece to move, and is also the electrical positioning precision.
The "Total No. of pulses" mentioned above is invariably required for controlling the distance. For positioning or speed control, the speed must be controlled as well. The speed is determined by the frequency of pulses sent from the QD75 to the drive unit.

This area is the total No. of commanded pulses.
Feedback pulses Speed = Pulses frequency Movement amount = No.of pulses Feedback pulses = Pulses generated by detector
Fig. 1.1 Relationship between position control and speed control
The QD75 controls the position with the "total No. of pulses", and the speed with the "pulse frequency".
=

The outline of the positioning system operation and design, using the QD75, is shown below.

Fig. 1.2 Outline of the operation of positioning system using QD75
1) The QD75 output is a pulse train. The pulse train output by the QD75 is counted by and stored in the deviation counter in the drive unit. The D/A converter outputs an analog DC current proportionate to the count maintained by the deviation counter (called "pulse droop"). The analog DC current serves as the servomotor speed control signal. 2) The motor rotation is controlled by the speed control signal from the drive unit. As the motor rotates, the pulse encoder (PLG) attached to the motor generates feedback pulses, the frequency of which is proportionate to the rotation speed. The feedback pulses are fed back to the drive unit and decrements the pulse droop, the pulse count maintained by the deviation counter. The motor keeps on rotating as the pulse droop is maintained at a certain level. 3) When the QD75 terminates the output of a pulse train, the motor decelerates as the pulse droop decreases and stops when the count drops to zero. Thus, the motor rotation speed is proportionate to the pulse frequency, while the overall motor rotation angle is proportionate to the total number of pulses output by the QD75. Therefore, when a movement amount per pulse is given, the overall movement amount can be determined by the number of pulses in the pulse train. The pulse frequency, on the other hand, determines the motor rotation speed (feed speed).

1) As shown in Fig. 1.3, the pulse frequency increases as the motor accelerates. The pulses are sparse when the motor starts and more frequent when the motor speed comes close to the target speed. 2) The pulse frequency stabilizes when the motor speed equals the target speed. 3) The QD75 decreases the pulse frequency (sparser pulses) to decelerate the motor before it finally stops the output. There will be a little difference in timing between the decrease in the pulse frequency and the actual deceleration and stopping of the motor. This difference, called "the stop settling time", is required for gaining a stopping accuracy.

Fig. 1.3 QD75 output pulses

A : Movement amount per pulse (mm/pulse) Vs : Command pulse frequency (pulse/s) n : Pulse encoder resolution (pulse/rev) L : Worm gear lead (mm/rev) R : Deceleration ratio V : Movable section speed (mm/s) N : Motor speed (r/min) K : Position loop gain (1/s) ε : Deviation counter droop pulse amount P0 : OP (pulse) P : Address (pulse)
Fig. 1.4 System using worm gears

(a) In the system shown in Fig. 1.4, the movement amount per pulse, command pulse frequency, and the deviation counter droop pulser amount are determined as follows: 1) Movement amount per pulse The movement amount per pulse is determined by the worm gear lead, deceleration ratio, and the pulse encoder resolution. The movement amount, therefore, is given as follows: (Number of pulses output) × (Movement amount per pulse).
L A = R × n [mm/pulse]
V Vs = A [pulse/s]
Vs ε = K [pulse]
(b) The QD75 allows the user to select from the following four units as the unit used by positioning commands to any of the axes (1 to 4, if the module supports four axes): mm, inch, degree, and pulse. The unit selected for one axis may differ from the unit selected for another axis. When such data as the movement amount per pulse, acceleration/deceleration time, positioning speed, and positioning address are correctly set in consideration of the chosen unit, the QD75 can calculate the number of pulses required for a movement amount to the target positioning address and execute the positioning by outputting a pulse train that includes the calculated number of pulses.

The outline of the signal communication between the QD75 and PLC CPU, peripheral device and drive unit, etc., is shown below. (A peripheral device communicates with the QD75 via the PLC CPU to which it is connected)


QD75 PLC CPU The QD75 and PLC CPU communicate the following data via the base unit.
Direction Communication QD75 PLC CPU PLC CPU QD75
Signal related to commands such as PLC READY signal, various start signals, stop signals
Control signal Signal indicating QD75 state, such as QD75 READY signal, BUSY signal.
Refer to Section 3.3 "Specifications of input/output signals with PLC CPU" for details.
QD75 Peripheral device The QD75 and peripheral device communicate the following data via the PLC CPU:
Direction Communication QD75 Peripheral device Peripheral device QD75
Operation monitor • Monitor data –
QD75 Drive unit The QD75 and drive unit communicate the following data via the external device connection connector.
Direction Communication QD75 Drive unit Drive unit QD75
Control signal Signals related to commands such as deviation counter clear signal
Signals indicating drive unit state such as drive unit READY signal
Pulse train • Pulse train output –
QD75 Manual pulse generator The QD75 and manual pulse generator communicate the following data via the external device connection connector. (The manual pulse generator should be connected to an external device connection connector for axis 1 or for axes 1 and 2.)
Direction Communication QD75 Manual pulse generator Manual pulse generator QD75
Pulse signal – Manual pulse generator A-phase, manual pulse generator B-phase
Data (read/write) · Data (read/write) · Test operation –

QD75 External signal The QD75 and external signal communicate the following data via the external device connection connector.
Direction Communication QD75 External signal External signal QD75
Control signal –

The positioning control processes, using the QD75, are shown below.

GX Configurator-QP Servo, etc. QD75 PLC CPU GX Developer
Design Understand the functions and performance, and determine the positioning operation method (system design)
Monitoring with test operation, and debugging of setting data
When not using GX Configurator -QP, carry out setting, monitoring and debugging of the data in 3) with GX Developer. Maintenance

The following work is carried out with the processes shown on the previous page.
Carry out test operation and adjustments in the test mode to check the connection with the QD75 and external connection device, and to confirm that the designated positioning operation is executed correctly. (Debug the set "parameters" and "positioning data", etc.)
Details Reference · 7)

MEMO

The outline for starting each control is shown with the following flowchart.
It is assumed that each module is installed, and the required system configuration, etc., has been prepared.

Major position- ing control High-level positioning control OPR control Manual control
·Position control ·Speed control ·Speed-position switching control ·Position-speed switching control ·Other control
·Block start (Normal start) ·Condition start ·Wait start ·Simultaneous start ·Repeated start
Control data Set the positioning start No. Set the JOG speed
Set the manual pulse generator enable flag to "1".
Set the inching movement amount to other than 0.
Set the manual pulse generator 1 pulse input magnification.
Input the start signal. Method (1) Turn ON the QD75 start signal from the PLC CPU Method (2) Issue the PSTRT instruction from the PLC CPU. Method (3) Turn the QD75 external start signal ON
Turn the QD75 JOG start signal ON from the PLC CPU

: Indicates the sequence program that must be created.

Set the parameter and data for executing main function, and the sub functions that need to be set beforehand.
When set with "GX Configurator-QP", this does not need to be created.

Create sequence program for outputting control signals, such as start signal, to QD75.
· Speed change · Current value changing · Torque limit · Restart, etc.
Setting method · ·

Each control is stopped in the following cases.
(1) When each control is completed normally. (2) When the drive unit READY signal is turned OFF. (3) When a PLC CPU error occurs (4) When the PLC READY signal is turned OFF. (5) When an error occurs in the QD75. (6) When control is intentionally stopped (Stop signal from PLC CPU turned ON, stop
signal from an external device, etc.)
The outline for the stopping process in these cases is shown below. (Excluding (1) for normal stopping.)

Axis error detection (Error other than stop group 1 or 2) Relatively safe stop (Stop group 3) “Stop signal”
Deceleration stop/sudden stop (Select with “ Pr.39 Sudden stop group3 sudden stop selection”)
"Stop signal" ON from external source Intentional stop (Stop group 3) "Axis stop

When a stop cause has occurred during operation with position control causing the axis to stop, positioning to the end point of the positioning data can be restarted from the stopped position by using the " Cd.6 Restart command".
If issued during a continuous positioning or continuous path control operation, the restart command will cause the positioning to be re-executed using the current position (pointed by the positioning data No. associated with the moment when the movement was interrupted) as the start point.
(1) If the " Md.26 Axis operation status" is stopped, positioning to the end point of
the positioning data will be restarted from the stopped position regardless of the absolute system or incremental system. (2) When " Md.26 Axis operation status" is not stopped, the warning "Restart not
possible" (warning code: 104) will be applied, and the restart command will be ignored.
[Example for incremental system]
(a) The restart operation when the axis 1 movement amount is 300, and the
axis 2 movement amount is 600 is shown below.
Stop position due to stop cause
Stop position due to stop cause
Designated end point position
Stop position after restart
100 300 700 Axis 2
100 300 700 Axis 2
If the positioning start signal [Y10 to Y13]/external command signal is turned ON while the " Md.26 Axis operation status" is waiting or stopped, positioning will be
restarted from the start of the positioning start data regardless of the absolute system or incremental system. ( : When the external command signal is set to "External positioning start") (Same as normal positioning.)
[Example for incremental system]
(a) The positioning start operation when the axis 1 movement amount is 300
and the axis 2 movement amount is 600 is shown below.
Stop position due to stop cause
Stop position after restart
Stop position due to stop cause
Designated end point position
Operation during positioning start
100 300 700 Axis 2
100 300 900 Axis 2

(1) The S-pattern acceleration/deceleration is disabled because it requires a
servomotor for the controlled axis.
(2) The circular interpolation control is disabled because it requires a servomotor
for each of the two controlled axes.
POINT
When it is desired to check the following items, refer to the corresponding explanation sections. How to check the function version and SERIAL No. (Refer to Section 2.4)
The following function additions/modifications according to the function version B of the QD75:
Multiple PLC compatible function Refer to QCPU User's Manual (Multiple CPU System).
Function which starts the axis under speed control, switches to position control at the external command signal input, then positions the axis to a stop at the designated address.
Speed-position switching control (ABS mode)
Section 9.2.17
Pre-reading start function Function which shortens virtual start time. Section 12.7.8
Function which monitors the external I/O signal monitor information in the module's detailed information which can be displayed on the system monitor of GX Developer 1.
External I/O signal monitor function
Section 13.5
Function that turns ON the flag when the constant speed status or acceleration status switches to the deceleration status during position control whose operation pattern is "Positioning complete".
Deceleration start flag function 2
Section 12.7.9
Function that selects a deceleration curve when a stop cause occurs during deceleration stop processing to speed 0.
Stop command processing for deceleration stop function 3
Section 12.7.10
Function Outline Reference

In this chapter, the general image of the system configuration of the positioning control using QD75, the configuration devices, applicable CPU and the precautions of configuring the system are explained. Prepare the required configuration devices to match the positioning control system.
2.1 General image of system 2- 2
2.2 Component list 2- 4
2.3 Applicable system 2- 5
2.4 How to check the function version and SERIAL No 2- 6

The general image of the system, including the QD75, PLC CPU and peripheral devices is shown below. (The Nos. in the illustration refer to the "No." in Section 2.2 "Component list".

1 Refer to Section 2.3 "Applicable system" for the CPU modules that can be used. 2 Refer to the CPU module User's Manual for the base units that can be used.


Near point dog Limit switch External command signal Stop signal

(For details, refer to GX Configurator -QP Operating Manual.)
Peripheral device

The positioning system using the QD75 is configured of the following devices.
No. Part name Type Remarks
QD75
No. of control axes
P: Open collector output system D: Differential driver output system
2 GX Configurator-QP SW D5C- QD75P-E Refer to GX Configurator-QP Operating Manual for details.
3 Personal computer DOS/V personal computer
(Prepared by user) Refer to GX Configurator-QP Operating Manual for details.
(Prepared by user) An RS-232 cable is needed for connecting the CPU module with a personal computer (DOS/V). For details, refer to GX Configurator-QP Operating Manual.
4 RS-232 cable QC30R2
(Prepared by user) A USB cable is needed for connecting the CPU module with a personal computer (DOS/V). For details, refer to GX Configurator-QP Operating Manual.
5 USB cable –
6 Drive unit – (Prepared by user)
7 Manual pulse generator – (Prepared by user) Recommended: MR-HDP01 (Mitsubishi Electric)
(Prepared by user) Cables are needed to connect the QD75 with the drive unit, manual pulse generator, and input devices in the machine system. (Prepare them referring to the manuals for the connected devices and information given in 3.4.2 of this manual.)
Connection cable (For connecting between the QD75 and the drive unit)

Pulse resolution 25pulse/rev (100 pulse/rev after magnification by 4)
Output method Voltage-output (power supply voltage -1V or more),
Operation temperature -10 to 60 (14 to 140 )
Number of max. revolution Instantaneous Max. 600r/min. normal 200r/min
1 Positioning module

The QD75 can be used in the following system.
The following table indicates the CPU modules and network modules (for remote I/O station) usable with the QD75 and the number of installable modules.

Applicable modules Number of installable modules Remarks Q00JCPU Max. 16 modules Q00CPU Q01CPU Max. 24 modules ( 1)
1 Refer to the User's Manual (Hardware Design, Maintenanse and Inspection) of the CPU module used. 2 Refer to the Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O Network).
The QD75 can be installed in any of the I/O slots ( 3) of a base unit. When installing the QD75, always consider the power supply capacity since a shortage of the power supply capacity may occur depending on the combination with the other installed module and the number of installed module.
3 Within the I/O point range of the CPU module and network module (for remote I/O station).
When using the QD75 in a multiple PLC system, first refer to the QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals).
The following table lists the compatibility between the systems using the QD75 and the software packages. GX Developer is required for use of the QD75.

I/O station Version 6 or more Version 2.10L or more
![Page 48 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Method using the software](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-48.webp?w=400)
2.4 How to check the function version and SERIAL No.
The function version and SERIAL No. of the QD75 can be checked in the following methods.
[1] Method using the rated plate on the module side face [2] Method using the software
Check the function version and SERIAL No. in the "SERIAL" field.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Method using the rated plate on the module side face diagram (page 48)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-48-1.webp)
SERIAL No. (The first five digits) Function version
Standard symbol for conformance is discribed
Check the function version and SERIAL No. in "Product information" displayed on System monitor "Module's Detailed Information" of GX Developer *1 or on "OS information" of GX Configurator-QP *2.
SERIAL No.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Method using the software diagram (page 48)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-8.webp)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Method using the software diagram (page 48)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-9.webp)
Function version

The various specifications of the QD75 are explained in this chapter.
The "General specifications", "Performance specifications", "List of functions", "Specifications of input/output signals with PLC CPU", and the "Specifications of input/output interfaces with external devices", etc., are described as information required when designing the positioning system. Confirm each specification before designing the positioning system.
3.1 Performance specifications 3- 2
3.2 List of functions 3- 4
3.2.1 QD75 control functions 3- 4
3.2.2 QD75 main functions 3- 6
3.2.3 QD75 sub functions and common functions 3- 8
3.2.4 Combination of QD75 main functions and sub functions 3- 12
3.3 Specifications of input/output signals with PLC CPU 3- 14
3.3.1 List of input/output signals with PLC CPU 3- 14
3.3.2 Details of input signals (QD75 PLC CPU) 3- 15
3.3.3 Details of output signals (PLC CPU QD75) 3- 16
3.4 Specifications of input/output interfaces with external devices 3- 17
3.4.1 Electrical specifications of input/output signals 3- 17
3.4.2 Signal layout for external device connection connector 3- 19
3.4.3 List of input/output signal details 3- 20
3.4.4 Input/output interface internal circuit 3- 22

QD75P4 1 QD75D4 No. of control axes 1 axis 2 axes 4 axes
QD75P2 1 QD75D2
2-, 3-, or 4-axis linear interpolation 2-axis circular interpolation
Interpolation function None 2-axis linear interpolation 2-axis circular interpolation
Control system PTP (Point To Point) control, path control (both linear and arc can be set), speed control, speed- position switching control, position-speed switching control Control unit mm, inch, degree, pulse
Positioning data 600 data (positioning data Nos. 1 to 600)/axis (Can be set with peripheral device or sequence program.)
Backup Parameters, positioning data, and block start data can be saved on flash ROM (battery-less backup)
PTP control: Incremental system/absolute system Speed-position switching control: Incremental system/absolute system 2 Position-speed switching control: Incremental system Path control: Incremental system/absolute system
0.01 to 20000000.00 (mm/min) 0.001 to 2000000.000 (inch/min) 0.001 to 2000000.000 (degree/min) 1 to 1000000 (pulse/s) Acceleration/ deceleration process Automatic trapezoidal acceleration/deceleration, S-pattern acceleration/deceleration
1 to 8388608 (ms) Four patterns can be set for each of acceleration time and deceleration time
Sudden stop deceleration time 1 to 8388608 (ms)

QD75P4 1 QD75D4 1-axis linear control 6 1-axis speed control 6 2-axis linear interpolation control (Composite speed) 7 2-axis linear interpolation control (Reference axis speed) 7 2-axis circular interpolation control 7 2-axis speed control 6 3-axis linear interpolation control (Composite speed) 7 3-axis linear interpolation control (Reference axis speed) 7 3-axis speed control 6 4-axis linear interpolation control 7
QD75P2 1 QD75D2
Factors in starting time extension
Starting time (ms) 3
4-axis speed control 7
Applicable wire size 0.3 mm2 (for A6CON1 or A6CON4), AWG #24 (for A6CON2)
Applicable connector for external device A6CON1, A6CON2, A6CON4 (sold separately)
Max. output pulse QD75P1, QD75P2, QD75P4 : 200kpps QD75D1, QD75D2, QD75D4 : 1Mpps Max. connection distance between servos
QD75P4 : 0.58A QD75D4 : 0.82A Flash ROM write count Max. 100000 times No. of occupied I/O points 32 points (I/O assignment: 32 points for intelligent function module) Outline dimensions 98 (H) × 27.4 (W) × 90 (D) mm Weight 0.15 kg 0.15 kg 0.16 kg
QD75P2 : 0.46A QD75D2 : 0.56A
QD75D4 only)

Solid wire: 0.2 to 0.8 mm2 2 pcs. Rated multiple wire connection size Stranded wire: 0.2 to 0.8 mm2 2 pcs.
Model Item

3.2.1 QD75 control functions
The QD75 has several functions. In this manual, the QD75 functions are categorized and explained as follows.
"OPR control" is a function that established the start point for carrying out positioning control, and carries out positioning toward that start point. This is used to return a workpiece, located at a position other than the OP when the power is turned ON or after positioning stop, to the OP. The "OPR control" is preregistered in the QD75 as the "Positioning start data No. 9001 (Machine OPR)", and "Positioning start data No. 9002 (Fast OPR). (Refer to Chapter 8 "OPR Control".)
(2) Major positioning control
This control is carried out using the "Positioning data" stored in the QD75. Positioning control, such as position control and speed control, is executed by setting the required items in this "positioning data" and starting that positioning data. An "operation pattern" can be set in this "positioning data", and with this whether to carry out control with continuous positioning data (ex.: positioning data No. 1, No. 2, No. 3, ...) can be set. (Refer to Chapter 9 "Major Positioning Control".)
(3) High-level positioning control
This control executes the "positioning data" stored in the QD75 using the "block start data". The following types of applied positioning control can be carried out.
By inputting a signal into the QD75 from an external source, the QD75 will output a random pulse train and carry out control. Use this manual control to move the workpiece to a random position (JOG operation), and to finely adjust the positioning (inching operation, manual pulse generator operation), etc. (Refer to Chapter 11 "Manual Control".)
When executing the main functions, control compensation, limits and functions can be added. (Refer to Chapter 12 "Control Sub Functions".)
Common control using the QD75 for "parameter initialization" or "backup of execution data" can be carried out. (Refer to Chapter 13 "Common Functions".)
(1) OPR control · (4) Manual control

Main functions Sub functions
OPR control Control registered in QD75
(Functions characteristic to machine OPR) OPR retry function
[Positioning start No.]
Backlash compensation function Electronic gear function Near pass function
Major positioning control Control using "Positioning data"
Speed limit function Torque limit function
·1-axis linear control ·2-, 3-, or 4-axis linear interpolation control ·1-axis fixed-feed control ·2-, 3-, or 4-axis fixed-feed control ·2-axis circular interpolation control ·1-axis linear control ·2-axis linear interpolation control ·3-axis linear interpolation control ·4-axis linear interpolation control ·Current value changing, NOP instruction ·JUMP instruction, LOOP to LEND
Independent positioning control (Positioning complete)
Software stroke limit function Hardware stroke limit function
Speed change function Override function Acceleration/deceleration time change function Torque change function
Control using "positioning data" + "Block start data"
Step function Skip function Continuous operation interrupt function M code output function Teaching function Target position change function Command in-position function Acceleration/deceleration processing function Pre-reading start function Deceleration start flag function
Block start (Normal start) Condition start Wait start Simultaneous start Repeated start (FOR loop) Repeated start (FOR condition) Multiple axes simultaneous start control
Major positioning control [Block start data]
[Positioning start No.]
Manual control Control with signals input from external source
JOG start signal ON Pulse input from manual pulse generator
JOG operation, Inching operation
Stop command processing for deceleration stop function
Manual pulse generator operation
Parameter initialization function Execution data backup function External I/O logic switching function
External I/O signal monitor function

The outline of the main functions for positioning control with the QD75 is described below. (Refer to Section 2 for details on each function.)
Main functions Details Reference
Machine OPR control Mechanically establishes the positioning start point using a near-point dog or stopper. (Positioning start No. 9001) 8.2
Positions a target to the OP address ( Md.21 Machine feed value) stored in the QD75 using machine OPR. (Positioning start No. 9002)
Linear control (1-axis linear control) (2-axis linear interpolation control) (3-axis linear interpolation control) (4-axis linear interpolation control)
9.2.2 9.2.3 9.2.4 9.2.5
Positions a target using a linear path to the address set in the positioning data or to the position designated with the movement amount.
Positions a target by the movement amount designated with the amount set in the positioning data.
Fixed-feed control (1-axis fixed-feed control) (2-axis fixed-feed control) (3-axis fixed-feed control) (4-axis fixed-feed control)
9.2.6 9.2.7 9.2.8 9.2.9
(With fixed-feed control, the " Md.20 Current feed value"
is set to "0" when the control is started. With 2-, 3-, or 4-axis fixed-feed control, the fixed-feed is fed along a linear path obtained by interpolation.)
2-axis circular interpolation control Positions a target using an arc path to the address set in the positioning data, or to the position designated with the movement amount, sub point or center point.
9.2.10 9.2.11
Linear control (1-axis linear control) (2-axis linear interpolation control) (3-axis linear interpolation control) (4-axis linear interpolation control)
9.2.12 9.2.13 9.2.14 9.2.15
Continuously outputs the pulses corresponding to the command speed set in the positioning data.
First, carries out speed control, and then carries out position control (positioning with designated address or movement amount) by turning the "speed-position switching signal" ON.
9.2.16 9.2.17
First, carries out position control, and then carries out speed control (continuous output of the pulses corresponding to the designated command speed) by turning the "position-speed switching signal" ON.
Changes the Current feed value ( Md.20 ) to the address
set in the positioning data. The following two methods can be used. (The machine feed value cannot be changed.)
No execution control system. When NOP instruction is set, this instruction is not executed and the operation of the next data is started.
JUMP instruction Unconditionally or conditionally jumps to designated positioning data No. 9.2.21
LOOP Carries out loop control with repeated LOOP to LEND. 9.2.22
LEND Returns to the beginning of the loop control with repeated LOOP to LEND. 9.2.23

Main functions Details Reference
Block start (Normal start) With one start, executes the positioning data in a random block with the set order. 10.3.2
Carries out condition judgment set in the "condition data" for the designated positioning data, and then executes the "block start data". When the condition is established, the "block start data" is executed. When not established, that "block start data" is ignored, and the next point's "block start data" is executed.
Carries out condition judgment set in the "condition data" for the designated positioning data, and then executes the "block start data". When the condition is established, the "block start data" is executed. When not established, stops the control until the condition is established. (Waits.)
Simultaneously executes the positioning data having the No. for the axis designated with the "condition data". (Outputs pulses at the same timing.)
Repeats the program from the block start data set with the "FOR loop" to the block start data set in "NEXT" for the designated No. of times.
Repeated start (FOR loop)
Repeats the program from the block start data set with the "FOR condition" to the block start data set in "NEXT" until the conditions set in the "condition data" are established.
Repeated start (FOR condition)
Starts the operation of multiple axes simultaneously according to the pulse output level. (Positioning start No. 9004, same as the "simultaneous start" above)
Multiple axes simultaneous start control
JOG operation Outputs a pulse to drive unit while the JOG start signal is ON. 11.2
Outputs pulses corresponding to minute movement amount by manual operation to drive unit. (Performs fine adjustment with the JOG start signal.)
Manual pulse generator operation Outputs pulses commanded with the manual pulse generator to drive unit. (Carry out fine adjustment, etc., at the pulse level.) 11.4
With the "major positioning control" ("high-level positioning control"), whether or not to continuously execute the positioning data can be set with the "operation pattern". Outlines of the "operation patterns" are given below.
Da.1 Operation pattern Details Reference
When "independent positioning control" is set for the operation pattern of the started positioning data, only the designated positioning data will be executed, and then the positioning will end.
Independent positioning control (Positioning complete)
When "continuous positioning control" is set for the operation pattern of the started positioning data, after the designated positioning data is executed, the program will stop once, and then the next following positioning data will be executed.
When "continuous path control" is set for the operation pattern of the started positioning data, the designated positioning data will be executed, and then without decelerating, the next following positioning data will be executed.

Sub functions
The functions that assist positioning control using the QD75 are described below. (Refer to Section 2 for details on each function.
Sub function Details Reference
This function retries the machine OPR with the upper/lower limit switches during machine OPR. This allows machine OPR to be carried out even if the axis is not returned to before the near-point dog with JOG operation, etc.
12.2.1 Functions characteristic to machine OPR OP shift function
After returning to the machine OP, this function compensates the position by the designated distance from the machine OP position and sets that position as the OP address.
This function compensates the mechanical backlash. Feed pulses equivalent to the set backlash amount are output each time the movement direction changes.
By setting the movement amount per pulse, this function can freely change the machine movement amount per commanded pulse. When the movement amount per pulse is set, a flexible positioning system that matches the machine system can be structured.
12.3.2 Functions that compensate control
Near pass function 1 This function suppresses the machine vibration when the speed changes during continuous path control in the interpolation control.
If the command speed exceeds " Pr.8 Speed limit value" during control, this function limits the commanded speed to
within the " Pr.8 Speed limit value" setting range.
If the torque generated by the servomotor exceeds " Pr.17
Torque limit setting value" during control, this function limits the
Functions that limit control
Torque limit function 2
generated torque to within the " Pr.17 Torque limit setting
value" setting range.
If a command outside of the upper/lower limit stroke limit setting range, set in the parameters, is issued, this function will not execute positioning for that command.
Software stroke limit function
Hardware stroke limit function
This function carries out deceleration stop with the limit switch connected to the QD75 external device connector. 12.4.4
This function changes the speed during positioning. Set the new speed in the speed change buffer memory
( Cd.14 New speed value), and change the speed with the
Speed change request ( Cd.15 ).
Functions that change control details
This function changes the speed within a percentage of 1 to
300% during positioning. This is executed using " Cd.13
Positioning operation speed override".
Acceleration/deceleration time change function
This function changes the acceleration/deceleration time during speed change. 12.5.3
Torque change function This function changes the "torque limit value" during control. 12.5.4 Absolute position restoration function 3 This function restores the absolute position of designated axis. 12.6

Sub function Details Reference
This function temporarily stops the operation to confirm the positioning operation during debugging, etc. The operation can be stopped at each "automatic deceleration" or "positioning data".
This function stops (decelerates to a stop) the positioning being executed when the skip signal is input, and carries out the next positioning.
This function issues a command for a sub work (clamp or drill stop, tool change, etc.) corresponding to the M code No. (0 to 65535) that can be set for each positioning data.
M code output function
This function stores the address positioned with manual control into the positioning address having the designated positioning data No. ( Cd.39 ).
Target position change function
This function changes the target position during positioning. Position and speed can be changed simultaneously. 12.7.5
At each automatic deceleration, this function calculates the remaining distance for the QD75 to reach the positioning stop position. When the value is less than the set value, the "command in-position flag" is set to "1". When using another auxiliary work before ending the control, use this function as a trigger for the sub work.
Acceleration/deceleration process function This function adjusts the control acceleration/deceleration. 12.7.7
This function interrupts continuous operation. When this request is accepted, the operation stops when the execution of the current positioning data is completed.
Continuous operation interrupt function
Pre-reading start function This function shortens the virtual start time. 12.7.8
Function that turns ON the flag when the constant speed status or acceleration status switches to the deceleration status during position control, whose operation pattern is "Positioning complete", to make the stop timing known.
Deceleration start flag function
Stop command processing for deceleration stop function
Function that selects a deceleration curve when a stop cause occurs during deceleration stop processing to speed 0. 12.7.10

The outline of the functions executed as necessary are described below. (Refer to Section 2 for details on each function.)
Common functions Details Reference
This function returns the "parameters" stored in the QD75 buffer memory and flash ROM to the default values. The following two methods can be used.
This functions stores the "setting data", currently being executed, into the flash ROM.
Execution data backup function
This function switches I/O signal logic according to externally connected devices. This function enables the use of the system that does not use b (N.C.)-contact signals, such as Drive unit READY or Upper/lower limit signal, by setting parameters to positive logic.
External I/O signal logic switching function
This function monitors the external I/O signal monitor information in the module's detailed information which can be displayed on the system monitor of GX Developer*4.
External I/O signal monitor function
section · Parameter initialization function

MEMO

With positioning control using the QD75, the main functions and sub functions can be combined and used as necessary. A list of the main function and sub function combinations is given below.
to machine OPR Sub functions
Main functions Combination with operation pattern. 1
Machine OPR control OPR control Fast OPR control
2-, 3-, or 4-axis linear interpolation control
(Continuous path control cannot be set)
2-, 3-, or 4-axis fixed- feed control (interpolation)
(Continuous path control cannot be set)
2-axis circular interpolation control
Speed control (1- to 4-axis) (Only independent positioning control can be set)
Speed-position switching control (Continuous path control cannot be set)
Position-speed switching control (Only independent positioning control can be set)
Current value changing (Continuous path control cannot be set)
JOG operation, inching operation Manual control Manual pulse generator operation
: Always combine, : Combination possible, : Combination limited, : Combination not possible 1 The operation pattern is one of the "positioning data" setting items. 2 The near pass function is featured as standard and is valid only for setting continuous path control for position control. 3 Invalid during creep speed. 4 Invalid during continuous path control. 5 Inching operation does not perform acceleration/deceleration processing. 6 Valid for the reference axis only. 7 Valid for only the case where a deceleration start is made during position control. 8 Disabled for a start of positioning start No. 9003.



3.3.1 List of input/output signals with PLC CPU
The QD75 uses 32 input points and 32 output points for exchanging data with the PLC CPU. The input/output signals when the QD75 is mounted in slot No. 0 of the main base unit are shown below. Device X refers to the signals input from the QD75 to the PLC CPU, and device Y refers to the signals output from the PLC CPU to the QD75.
Signal direction: QD75 PLC CPU Signal direction: PLC CPU QD75 Device No. Signal name Device No. Signal name X0 QD75 READY Y0 PLC READY X1 Synchronization flag Y1 X2 Y2 X3 Use prohibited Y3
X4 Axis 1 Y4 Axis 1 X5 Axis 2 Y5 Axis 2 X6 Axis 3 Y6 Axis 3 X7 Axis 4
X8 Axis 1 Y8 Axis 1 Forward run JOG start X9 Axis 2 Y9 Axis 1 Reverse run JOG start XA Axis 3 YA Axis 2 Forward run JOG start XB Axis 4
YB Axis 2 Reverse run JOG start XC Axis 1 YC Axis 3 Forward run JOG start XD Axis 2 YD Axis 3 Reverse run JOG start XE Axis 3 YE Axis 4 Forward run JOG start XF Axis 4
YF Axis 4 Reverse run JOG start X10 Axis 1 Y10 Axis 1 X11 Axis 2 Y11 Axis 2 X12 Axis 3 Y12 Axis 3 X13 Axis 4
X14 Axis 1 Y14 Axis 1 X15 Axis 2 Y15 Axis 2 X16 Axis 3 Y16 Axis 3 X17 Axis 4
X18 Y18 X19 Y19 X1A Y1A X1B Y1B X1C Y1C X1D Y1D X1E Y1E X1F
Important
[Y1 to Y3], [Y18 to Y1F], [X2, X3], and [X18 to X1F] are used by the system, and cannot be used by the user. If these devices are used, the operation of the QD75 will not be guaranteed.

The ON/OFF timing and conditions of the input signals are shown below.
No. Signal name Details
Watch dog timer error
PLC READY signal [Y0] OFF
QD75 READY signal [X0] OFF
Axis 1 Axis 2 Axis 3 Axis 4
Axis 1 Axis 2 Axis 3 Axis 4
Axis 1 Axis 2 Axis 3 Axis 4
when the " Da.9 Dwell time" has passed after positioning stops. (This signal
remains ON during positioning.) This signal turns OFF when the positioning is stopped with step operation.
Manual pulse generator enable flag" is ON. • This signal turns OFF at error completion or positioning stop. X10 X11 X12 X13
Axis 1 Axis 2 Axis 3 Axis 4
Positioning start signal [Y10]
ON
Start complete signal [X10]
X14 X15 X16 X17
Axis 1 Axis 2 Axis 3 Axis 4
time" from the instant when the positioning control for each positioning data No. is completed.
(It does not turn ON when " Pr.40 Positioning complete signal output time" is "0".)

The ON/OFF timing and conditions of the output signals are shown below.
Device No. Signal name Details Y0 PLC READY OFF:
(a) This signal notifies the QD75 that the PLC CPU is normal.
OFF depending on the parameter (Refer to Chapter 7.). (c) The following processes are carried out when the PLC READY
signal turns from OFF to ON.
signal turns from ON to OFF. In these cases, the OFF time should be set to 100ms or more.
"0" is stored in " Md.25 Valid M code".
(e) When parameters or positioning data (No. 1 to 600) are written
from the peripheral device or PLC CPU to the flash ROM, the PLC READY signal will turn OFF. Y4 Y5 Y6 Y7
Axis 1 Axis 2 Axis 3 Axis 4
Axis stop OFF:
Axis stop not requested ON:
" Pr.39 Stop group 3 sudden stop selection".
Axis 1 Axis 1 Axis 2 Axis 2 Axis 3 Axis 3 Axis 4 Axis 4
Forward run JOG start Reverse run JOG start Forward run JOG start Reverse run JOG start Forward run JOG start Reverse run JOG start Forward run JOG start Reverse run JOG start
JOG not started ON:
out at the " Cd.17 JOG speed". When the JOG start signal turns
OFF, the operation will decelerate and stop. • When inching movement amount is set, the designated movement amount is output for one control cycle and then the operation stops.
Axis 1 Axis 2 Axis 3 Axis 4
Positioning start OFF:
Positioning start not requested ON:
Axis 1 Axis 2 Axis 3 Axis 4
Not during execution prohibition ON:

3.4.1 Electrical specifications of input/output signals
Input specifications
Signal name Rated input voltage/current
Drive unit READY (READY) Stop signal (STOP) Upper limit signal (FLS) Lower limit signal (RLS)
24VDC/5mA 19.2 to 26.4VDC 17.5VDC or more/ 3.5mA or more 7VDC or less/ 1.7mA or less Approx. 4.7kΩ 4ms or less
5VDC/5mA 4.5 to 6.1VDC 2VDC or more/ 2mA or more 0.5VDC or less/ 0.5mA or less Approx. 0.3kΩ 1ms or less
24VDC/5mA 12 to 26.4VDC 10VDC or more/ 3mA or more 3VDC or less/ 0.2mA or less Approx. 4.7kΩ 1ms or less
3 s or less 1ms or more 3 s or less ON
Differential receiver equivalent to Am26LS32 (ON/OFF level ON: 1.8V or more, OFF: 0.6V or less)
5VDC/5mA 4.5 to 6.1VDC 2.5VDC or more/ 2mA or more 1VDC or less/ 0.1mA or less Approx. 1.5kΩ 1ms or less
Manual pulse generator A phase (PULSE GENERATOR A) Manual pulse generator B phase (PULSE GENERATOR B)
When the A phase leads the B phase, the positioning address (current value) increases.
Near-point dog signal (DOG) External command signal (CHG)
24VDC/5mA 19.2 to 26.4VDC 17.5VDC or more/ 3.5mA or more 7VDC or less/ 1.7mA or less Approx. 4.3kΩ 1ms or less

Max. load current/rush
Signal name Rated load
Working load voltage range
Max. voltage
at OFF Response time
output mode) according to the drive unit specifications. • The relation of the pulse output with the " Pr.5 Pulse output mode" and " Pr.23 Output signal logic
selection" is shown below:
Pr.23 Output signal logic selection (bit 0)
Positive logic Negative logic Pr.5 Pulse
Forward run Reverse run Forward run Reverse run
Pulse output (CW/PULSE/A phase) Pulse sign (CCW/SIGN/B phase)
SIGN High Low Low High
Aφ Bφ
The table below shows the rising/falling edge time and duty ratio when the QD75P is used.
OFF
5 to 24VDC 4.75 to 30VDC 50mA/1 point/ 200mA 10ms or less
0.5VDC (TYP) 0.1mA or less —
Deviation counter clear (CLEAR) 5 to 24VDC 4.75 to 30VDC 0.1A/1 point/0.4A 10ms or less 1VDC (TYP) 2.5VDC (MAX) 0.1mA or less 2ms or less (resistance load)
: Pulse rising/falling edge time when the QD75P is used (Unit for "tr" and "tf": µs, unit for "Duty": %) ... When ambient temperature is room temperature.
Load voltage (V) 26.4 4.75 Cable length (m) 1 2 1 2 Load current
200 2.33 0.08 6.6 2.20 0.08 14.6 0.57 0.07 44.8 0.95 0.07 39.0 100 2.42 0.09 34.7 4.44 0.10 12.6 0.57 0.07 47.5 1.01 0.08 45.3
2 10 2.44 0.09 48.7 4.52 0.10 47.7 0.60 0.07 49.7 1.04 0.08 49.5
200 1.00 0.09 39.8 1.77 0.11 24.5 0.32 0.07 48.4 0.45 0.08 45.8 100 1.01 0.09 45.3 1.76 0.10 40.3 0.31 0.07 49.2 0.45 0.08 48.7
5 10 1.00 0.10 49.6 1.72 0.10 49.2 0.33 0.08 49.9 0.49 0.08 49.8
200 0.27 0.10 50.1 0.44 0.11 48.0 0.15 0.08 50.7 0.15 0.08 51.3 100 0.29 0.10 49.8 0.48 0.11 49.1 0.15 0.08 50.4 0.18 0.08 50.4
20 10 0.30 0.10 49.9 0.48 0.12 49.9 0.17 0.08 50.1 0.18 0.08 49.9
200 0.19 0.11 50.5 0.24 0.12 50.6 0.15 0.10 51.8 0.14 0.11 51.7 100 0.19 0.11 50.4 0.24 0.12 50.4 0.14 0.10 50.7 0.15 0.10 50.8
50 10 0.18 0.12 50.0 0.22 0.13 50.1 0.14 0.10 50.1 0.15 0.12 50.1
The time for H/L width of differential output waveform with the QD75D . (Cable length: 2m, Ambient temperature: room temperature)


The specifications of the connector section, which is the input/output interface for the QD75 and external device, are shown below. The signal layout for the QD75 external device connection connector is shown.
QD75P2
QD75P4
RUN
AX1
RUN
AX1
RUN
AX1
AX2
AX2 AX3 AX4
ERR
ERR
ERR
AX1
AX1
AX2 AX3 AX4
AX1
AX2
Axis 4(AX4) Axis 3(AX3) Axis 2(AX2) Axis 1(AX1) Pin layout Pin No. Signal name Pin No. Signal name Pin No. Signal name Pin No. Signal name 2B20 Vacant 2A20 Vacant 1B20 PULSER B– 1A20 PULSER B+ 2B19 Vacant 2A19 Vacant 1B19 PULSER A– 1A19 PULSER A+ 2B18 3 PULSE COM
1B18 3 PULSE COM
1A18 3 PULSE COM
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16 B17 B18 B19 B20
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20
PULSE R–
PULSE R–
PULSE R–
1A17 3 PULSE R PULSE R+ 2B16 3 PULSE COM
1B17 3 PULSE R PULSE R+
2A16 3 PULSE COM
1B16 3 PULSE COM
1A16 3 PULSE COM
PULSE F– 2B15 3 PULSE F PULSE F+
PULSE F–
PULSE F–
PULSE F–
1A15 3 PULSE F PULSE F+ 2B14 CLRCOM 2A14 CLRCOM 1B14 CLRCOM 1A14 CLRCOM 2B13 CLEAR 2A13 CLEAR 1B13 CLEAR 1A13 CLEAR 2B12 RDYCOM 2A12 RDYCOM 1B12 RDYCOM 1A12 RDYCOM 2B11 READY 2A11 READY 1B11 READY 1A11 READY 2B10 PGOCOM 2A10 PGOCOM 1B10 PGOCOM 1A10 PGOCOM 2B9 PG05 2A9 PG05 1B9 PG05 1A9 PG05 2B8 PG024 2A8 PG024 1B8 PG024 1A8 PG024 2B7 COM 2A7 COM 1B7 COM 1A7 COM 2B6 COM 2A6 COM 1B6 COM 1A6 COM 2B5 CHG 2A5 CHG 1B5 CHG 1A5 CHG 2B4 STOP 2A4 STOP 1B4 STOP 1A4 STOP 2B3 DOG 2A3 DOG 1B3 DOG 1A3 DOG 2B2 RLS 2A2 RLS 1B2 RLS 1A2 RLS
1B15 3 PULSE F PULSE F+
Front view of the module

The details of each QD75 external device connection connector are shown below:
Pin No. Signal name
Signal details (Negative logic is selected by external I/O signal logic selection)
Manual pulse generator A phase Manual pulse generator B phase
[When increased] [When decreased]
Manual pulse generator A common Manual pulse generator B common
+1+1+1+1+1+1+1+1 -1
Zero signal (+24V) 1A8 1B8 2A8 2B8
Zero signal (+5V) 1A9 1B9 2A9 2B9
Zero signal common 1A10 1B10 2A10 2B10 • Common for zero signal (+5V) and zero signal (+24V).
Pulse output F (+) Pulse output F (–)
Pulse output R (+) Pulse output R (–)
1B17
2A17
2B17
1A18
1B18
2A18
2B18
Pulse output F Pulse output F common
1B15
2A15
2B15
1A16
1B16
2A16
2B16
Pulse output R Pulse output R common
1B17
2A17
2B17
1A18
1B18
2A18
2B18
Upper limit signal 1A1 1B1 2A1 2B1
Lower limit signal 1A2 1B2 2A2 2B2

Pin No. Signal name AX1 AX2 AX3 AX4
Signal details (Negative logic is selected by external I/O signal logic selection)
Stop signal 1A4 1B4 2A4 2B4
External command signal 1A5 1B5 2A5 2B5
Set the function to use this signal in " Pr.42 External command function
selection".
Common 1A6 1A7 1B6 1B7 2A6 2A7 2B6 2B7 • Common for upper/lower limit, near-point dog, stop, and external command signals.
Drive unit READY 1A11 1B11 2A11 2B11
Drive unit READY common 1A12 1B12 2A12 2B12 • Common for drive unit READY signal.
Pr.46
Pr.47
Deviation counter clear 1A13 1B13 2A13 2B13
Pr.55 Deviation counter
clear signal output time
OFF
ON
After feed pulse output stops
Deviation counter clear signal output time". • Use the drive unit that can reset the droop pulse amount in the internal deviation counter when the QD75 turns this signal ON. (Note) The deviation counter clear is a signal output by the QD75 during
machine OPR. It cannot be output randomly by the user.
Deviation counter clear common 1A14 1B14 2A14 2B14 • Common for deviation counter clear signal

The outline diagrams of the internal circuits for the QD75P1/QD75D1 external device connection interface are shown below.

External wiring Pin No. Internal circuit Signal name Need for wiring
1:The symbols in Need for wiring column indicate the following meanings:

The input signal ON/OFF status is defied by the external wiring and logic setting. This is explained below with the example of near-point dog signal (DOG). (The other input signals also perform the same operations as the near-point dog signal (DOG).)

3, 4 External wiring 4 ON/OFF status of near-point dog signal (DOG) as seen from QD75
In the QD75, the case where the internal circuit (photocoupler) is OFF in the negative logic setting is defined as "input signal OFF". Reversely, the case where the internal circuit (photocoupler) is OFF in the positive logic setting is defined as "input signal ON".


External wiring Pin No. Internal circuit Signal name Need for wiring

External wiring Pin No. Internal circuit Signal name Need for wiring

of the Product
The installation, wiring and maintenance of the QD75 are explained in this chapter.
4.1 Outline of installation, wiring and maintenance 4- 2 4.1.1 Installation, wiring and maintenance procedures 4- 2 4.1.2 Names of each part 4- 3 4.1.3 Handling precautions 4- 5 4.2 Installation 4- 7 4.2.1 Precautions for installation 4- 7 4.3 Wiring 4- 8 4.3.1 Precautions for wiring 4- 8 4.3.2 Wiring of the differential driver common terminal 4- 13 4.4 Confirming the installation and wiring 4- 14 4.4.1 Items to confirm when installation and wiring are completed 4- 14 4.5 Maintenance 4- 15 4.5.1 Precautions for maintenance 4- 15 4.5.2 Disposal instructions 4- 15

4.1.1 Installation, wiring and maintenance procedures
The outline and procedures for QD75 installation, wiring and maintenance are shown below.
Understand the "Handling precautions" and "Names of each part" of the module (QD75)
Refer to Section 4.1 Preparation
Install the module (QD75) on the base unit.
Refer to Section 4.2
The cables used to connect the QD75 with the drive unit, with the mechanical system input (each input/output signal), and with the manual pulse generator are manufactured by soldering each signal wire onto the "external device connection connector" sold separately.(Refer to "Applicable connector for external wiring" in Section 3.1 "Performance specifications" for the optional connector.)
Wire the external device connection connector pins, and assemble the connector.
Refer to Section 4.3
Connect the cable to the module (QD75)
Refer to Section 4.3
Wire and connect the manufactured cable to QD75 after reading the precautions for wiring.
Confirming the installation and wiring
Confirm the connection Check the connection using GX Configurator-QP.
Refer to Section 4.4
Operation of the positioning system.
Carry out maintenance Carry out maintenance as necessary.
Refer to Section 4.5
Dispose of the QD75 When the QD75 is no longer necessary, dispose of it with the specified methods.
Refer to Section 4.5
Installing the module · Wiring the module · Servicing the module

(1) The part names of the QD75 are shown below:


No. Name Details
(1) RUN indicator LED, ERR indicator LED
(2) Axis display LED (AX1 to AX4) Refer to the next page.
Connector for connection with the drive unit, mechanical system input or manual pulse generator. (40-pin connector) AX1: Axis 1, AX2: Axis 2, AX3: Axis 3, AX4: Axis 4 For details, refer to Section 3.4.2 "Signal layout for external device connection connector".
(3) External device connector
Differential driver common terminal (Differential driver output system (QD75D1, QD75D2, QD75D4) only)
Terminal connected to the differential receiver common of the drive unit. For details, refer to Section 4.3.2 "Wiring of the differential driver common terminal".

(2) The LED display indicates the following operation statuses of the QD75 and axes.


The symbols in the Display column indicate the following statuses:
: Turns OFF. : Illuminates. : Flashes.
(3) The interface of each QD75 is as shown below.
QD75P1
QD75P2
QD75P4
QD75D1
QD75D2
QD75D4
RUN
AX1
RUN
AX1
AX2
RUN
AX1
AX2 AX3 AX4
RUN
AX1
RUN
AX1
AX2
RUN
AX1
AX2 AX3 AX4
ERR
ERR
ERR
ERR
ERR
ERR
AX1
AX2 AX3 AX4
AX1
AX1
AX1
AX2 AX3 AX4
AX1
AX1
AX2
AX2
![Page 77 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Handling precautions](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-77.webp?w=400)
Handle the QD75 and cable while observing the following precautions.
! CAUTION
Use the PLC within the general specifications environment given in this manual.
Using the PLC outside the general specification range environment could lead to electric shocks, fires, malfunctioning, product damage or deterioration. Do not directly touch the conductive section and electronic parts of the module.
Failure to observe this could lead to module malfunctioning or trouble. Make sure that foreign matter, such as cutting chips or wire scraps, do not enter the module.
Failure to observe this could lead to fires, trouble or malfunctioning. Never disassemble or modify the module.
Failure to observe this could lead to trouble, malfunctioning, injuries or fires.

(1) Main body
Do not install the module in the following type of environment.

4.2.1 Precautions for installation
The precautions for installing the QD75 are given below. Refer to this section as well as "4.1.3 Handling precautions" when carrying out the work.
! DANGER
Completely turn off the externally supplied power used in the system before cleaning or
tightening the screws. Failure to turn all phases OFF could lead to electric shocks.
Never disassemble or modify the module.
Failure to observe this could lead to trouble, malfunctioning, injuries or fires. Completely turn off the externally supplied power used in the system before installing or
removing the module.
Failure to turn all phases OFF could lead to module trouble or malfunctioning. Do not mount/remove the module onto/from base unit more than 50 times (IEC61131-2-
compliant), after the first use of the product. Failure to do so may cause the module to malfunction due to poor contact of connector.
Use the PLC within the general specifications environment given in this manual.
Using the PLC outside the general specification range environment could lead to electric shocks, fires, malfunctioning, product damage or deterioration. Hold down the module mounting lever at the bottom of the module and securely insert the
module fixing projection into the fixing holes of the base module. Improper mounting of the module may lead to malfunctioning, faults, or dropping.
When using the module in the environment subject to much vibration, secure the module with a screw. Tighten the screw within the range of the specified tightening torque. Insufficient tightening may lead to dropping, short-circuit, or malfunctioning. Excessive tightening may damage the screw or module, leading to dropping, short-circuit, or malfunctioning.

The precautions for wiring the QD75 are given below. Refer to this section as well as "4.1.3 Handling precautions" when carrying out the work.
(1) Always confirm the terminal layout before connecting the wires to the QD75.
(For the terminal layout, refer to Section 3.4.2 "Signal layout for external device
connection connector".) (2) Correctly solder the external wiring connector. An incomplete soldering could lead
to malfunctioning. (3) Make sure that foreign matter such as cutting chips and wire scraps does not
enter the QD75. Failure to observe this could lead to fires, faults or malfunctioning. (4) A protective label is attached on the top of the QD75 to avoid foreign matter such
as wire scraps from entering inside during wiring process. Do not remove the label until the wiring is completed. Before starting the system, however, be sure to remove the label to ensure heat radiation. (5) Securely mount the external device connector to the connector on the QD75 with
two screws. (6) Do not disconnect the external wiring cable connected to the QD75 and the drive
unit by pulling the cable section. When the cable has a connector, be sure to hold the connector connected to the QD75 and the drive unit. Pulling the cable while it is connected to the QD75 and the drive unit may lead to malfunctioning or damage of the QD75 and the drive unit or cable. (7) Do not bundle or adjacently lay the connection cable connected to the QD75
external I/O signals or drive unit with the main circuit line, power line, or the load line other than that for the PLC. Separate these by 100mm as a guide. Failure to observe this could lead to malfunctioning caused by noise, surge, or induction. (8) The shielded cable for connecting QD75 can be secured in place.
If the shielded cable is not secured, unevenness or movement of the shielded cable or careless pulling on it could result in damage to the QD75 or drive unit or shielded cable or defective cable connections could cause mis-operation of the unit. (9) If the cable connected to the QD75 and the power line must be adjacently laid
(less than 100mm), use a shielded cable. Ground the shield of the cable securely to the control panel on the QD75 side. (A wiring example is given on the next page.)
![Page 81 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Processing example of shielded cables]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-81.webp?w=400)
The following shows a wiring example for noise reduction in the case where the connector A6CON1 is used.
![Mitsubishi Electronics MELSEC-Q QD75D — [Wiring example of shielded cable] diagram (page 81)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-81-1.webp)
Use the shortest possible length to ground the 2mm or more FG wire. (The shield must be grounded on the QD75 side.) The length between the connector and the shielded cables should be the shortest possible.
Remove the covering from all shielded cables and bind the appeared shield with a conductive tape.
![Mitsubishi Electronics MELSEC-Q QD75D — [Processing example of shielded cables] diagram (page 81)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-81-2.webp)
Solder the shield of any one of the shielded cables to the FG wire.


Wrap the coated parts with a heat contractile tube.
![Page 83 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [How to ground shielded cable using AD75CK]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-83.webp?w=400)
(10) To make this product conform to the EMC and Low Voltage Directive, be
sure to use of a AD75CK type cable clamp (manufactured by Mitsubishi Electric) for grounding to the control box.

20cm(7.88inch) to 30cm(11.82inch)
![Mitsubishi Electronics MELSEC-Q QD75D — [How to ground shielded cable using AD75CK] diagram (page 83)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-83-2.webp)
Ground terminal installation screw (M4 8 screw)
Using the AD75CK, you can tie four cables of about 7mm outside diameter together for grounding.
Ground terminal
![Page 84 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Wiring examples using duct (incorrect example and corrected example)]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-84.webp?w=400)
![Mitsubishi Electronics MELSEC-Q QD75D — [Wiring examples using duct (incorrect example and corrected example)] diagram (page 84)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-84-1.webp)
The drive units are placed
near the noise source.
The connection cable between
the QD75 and drive units is
too long.
The QD75 and drive units are
placed closely. The connection
cable between the QD75 and
drive units is separately laid
from the power line (in this
example, the cable is outside of
the duct) and is as short as possible.
(11) The influence of noise may be reduced by installing ferrite cores to the cable
connected to the QD75 as a noise reduction technique. For the noise reduction techniques related to connection with the servo amplifier, also refer to the instruction manual of the servo amplifier. (12) If compliance with the EMC directive is not required, the influence of external
noise may be reduced by making the configuration compliant with the EMC directive. For the configuration compliant with the EMC directive, refer to Chapter 3 "EMC AND LOW-VOLTAGE DIRECTIVES" in the User's Manual (Hardware) of the used CPU module.

When the differential driver output system (QD75D1, QD75D2, QD75D4) is used, a potential difference between commons may occur between the differential driver common terminal and the differential receiver common terminal of the drive unit. To remove the potential difference between commons, connect the differential driver common terminal of the QD75D1/QD75D2/QD75D4 and the differential receiver common terminal of the drive unit. When the common terminal of the drive unit is photocoupler-connected, the wiring to the differential driver common terminal of the QD75D1/QD75D2/QD75D4 is not needed since a potential difference between commons does not exist. (For the drive unit specifications, refer to the manual of the used drive unit.) The following shows an example of wiring to the differential driver common terminal of the QD75D1/QD75D2/QD75D4. Up to two cables can be connected to one differential driver common terminal. (For details, refer to Section 3.1 "Performance specifications".


4.4.1 Items to confirm when installation and wiring are completed
Check the following points when completed with the QD75 installation and wiring.
With this "connection confirmation", "whether the direction that the QD75 recognizes as forward run matches the address increment direction in the actual positioning work", and "whether the QD75 recognizes the external input/output signals such as the near-point dog signal and stop signal" can be checked.
Refer to GX Configurator-QP Operating Manual for details on "Connection confirmation".
If the QD75 is faulty, or when the required signals such as the near-point dog signal and stop signal are not recognized, unexpected accidents such as "not decelerating at the near-point dog during machine OPR and colliding with the stopper", or "not being able to stop with the stop signal" may occur. The "connection confirmation" must be carried out not only when structuring the positioning system, but also when the system has been changed with module replacement or rewiring, etc.

4.5.1 Precautions for maintenance
The precautions for servicing the QD75 are given below. Refer to this section as well as "4.1.3 Handling precautions" when carrying out the work.
Always turn all phases of the power supply OFF externally before cleaning or tightening the
screws. Failure to turn all phases OFF could lead to electric shocks.
Never disassemble or modify the module.
Failure to observe this could lead to trouble, malfunctioning, injuries or fires. Completely turn off the externally supplied power used in the system before installing or
removing the module.
Failure to turn all phases OFF could lead to module trouble or malfunctioning.
! CAUTION
When disposing of the product, handle it as industrial waste.

MEMO

The parameters and data used to carry out positioning control with the QD75 are explained in this chapter.
With the positioning system using the QD75, the various parameters and data explained in this chapter are used for control. The parameters and data include parameters set according to the device configuration, such as the system configuration, and parameters and data set according to each control. Read this section thoroughly and make settings according to each control or application.
Refer to Section 2 for details on each control.
5.1 Types of data 5- 2 5.1.1 Parameters and data required for control 5- 2 5.1.2 Setting items for positioning parameters 5- 4 5.1.3 Setting items for OPR parameters 5- 6 5.1.4 Setting items for positioning data 5- 7 5.1.5 Setting items for block start data 5- 10 5.1.6 Setting items for condition data 5- 11 5.1.7 Types and roles of monitor data 5- 12 5.1.8 Types and roles of control data 5- 16 5.2 List of parameters 5- 20 5.2.1 Basic parameters 1 5- 20 5.2.2 Basic parameters 2 5- 26 5.2.3 Detailed parameters 1 5- 28 5.2.4 Detailed parameters 2 5- 36 5.2.5 OPR basic parameters 5- 46 5.2.6 OPR detailed parameters 5- 54 5.3 List of positioning data 5- 58 5.4 List of block start data 5- 74 5.5 List of condition data 5- 80 5.6 List of monitor data 5- 86 5.6.1 System monitor data 5- 86 5.6.2 Axis monitor data 5- 96 5.7 List of control data 5-110 5.7.1 System control data 5-110 5.7.2 Axis control data 5-112

5.1.1 Parameters and data required for control
The parameters and data required to carry out control with the QD75 include the "setting data", "monitor data" and "control data" shown below.
Setting data (Data set beforehand according to the machine and application, and stored in the flash ROM.)
Parameters Positioning parameters Basic parameters 1 Set according to the machine and applicable motor when system is started up.
Pr.1 ) Pr.57
Pr.1 ) Pr.42 ,
Pr.150
Set according to the system configuration when the system is started up.
Set the values required for carrying out OPR control.
Pr.43 ) Pr.57
Positioning data Positioning data Set the data for "major positioning control".
Da.1 ) Da.10
Block start data Set the block start data for "high-level positioning control".
Da.11 ) Da.14
Da.11 ) Da.19
Condition data Set the condition data for "high-level positioning control".
Da.15 ) Da.19
Memo data Set the condition judgment values for the condition data used in "high-level positioning control".
The data is set with the sequence program or peripheral device.
In this chapter, the method using the peripheral device will be explained. (Refer to "Point" on the next page.) The basic parameters 1, detailed parameters 1, and OPR parameters become valid
when the PLC READY signal [Y0] turns from OFF to ON. Note, however, that the only valid value of the " Pr.5 Pulse output mode" is the value at the moment when
the PLC READY signal [Y0] turns from OFF to ON for the first time after the power is switched ON or the PLC CPU is reset. Once the PLC READY signal [Y0] has been turned ON, the value will not be reset even if another value is set to the parameter and the PLC READY signal [Y0] is turned from OFF to ON. The basic parameters 2 and detailed parameters 2 become valid immediately when
they are written to the buffer memory, regardless of the state of the PLC READY signal [Y0]. Even when the PLC READY signal [Y0] is ON, the values or contents of the
following can be changed: basic parameters 2, detailed parameters 2, positioning data, and block start data.

The only valid data assigned to these parameters are the data read at the moment
Monitor data (Data that indicates the control state. Stored in the buffer memory, and monitors as necessary.)
to Md.1 Md.48 :
System monitor data Monitors the QD75 specifications and the operation history.
Md.1 ) Md.19
Axis monitor data Monitors the data related to the operating axis, such as the current position and speed.
Md.20 ) Md.48
The data is monitored with the sequence program or peripheral device. In this chapter, the method using the peripheral device will be explained.
Control data (Data for user to control positioning system.)
to Cd.1 Cd.42 :
System control data Performs write/initialization, etc. of the "setting data" in the module.
Cd.1 Cd.2
Cd.41 ,
) Cd.42 ,
Axis control data Makes settings related to the operation, and controls the speed change during operation, and stops/restarts the operation.
Cd.3 ) Cd.40
Control using the control data is carried out with the sequence program.
Cd.41 " Deceleration start flag valid" is valid for only the value at the time when the PLC READY signal [Y0] turns from OFF to ON.
POINT (1) The "setting data" is created for each axis. (2) The "setting data" parameters have determined default values, and are set to
the default values before shipment from the factory. (Parameters related to axes that are not used are left at the default value.) (3) The "setting data" can be initialized with GX Configurator-QP or the sequence
program. (4) It is recommended to set the "setting data" with GX Configurator-QP. When
executed with the sequence program, many sequence programs and devices must be used. This will not only complicate the program, but will also increase the scan time.

The table below lists items set to the positioning parameters. Setting of positioning parameters is similarly done for individual axes for all controls achieved by the QD75. For details of controls, refer to Section 2. For details of setting items, refer to Section 5.2 "List of parameters".
Control Major positioning control Manual control Position control Other control
1-axis linear control 2/3/4-axis linear interpolation control
2-axis circular interpolation control
JUMP instruction, NOP instruction,
Manual pulse generator operation
1-axis fixed-feed control 2/3/4-axis fixed-feed control
1 to 4 axis speed control
Pr.1 Unit setting –
Pr.2 No. of pulses per rotation (Ap) (Unit: pulse)
Pr.3 Movement amount per rotation (Al)
Pr.4 Unit magnification (Am)
Pr.5 Pulse output mode –
Pr.6 Rotation direction setting –
Pr.7 Bias speed at start –
Pr.8 Speed limit value – – 12.4.1
Pr.9 Acceleration time 0 – – –
Pr.10 Deceleration time 0 – – –
Pr.11 Back compensation amount – – 12.3.1
Pr.12 Software stroke limit upper limit value – – –
Pr.13 Software stroke limit lower limit value – – –
Pr.14 Software stroke limit selection – – –
Pr.15 Software stroke limit valid/invalid selection –
Pr.16 Command in-position width – 12.7.6
Pr.17 Torque limit setting value – – 12.4.2
Pr.18 M code ON signal output timing – 12.7.3
Pr.19 Speed switching mode –
Pr.20 Interpolation speed designation method –
Pr.21 Current feed value during speed control –
Pr.22 Input signal logic selection –
Pr.23 Output signal logic selection –
Pr.24 Manual pulse generator input selection –
Pr.150 Speed-position function selection –
: Always set : Set as required (Read "–" when not required.) : Setting not possible : Setting restricted – : Setting not required. (This is an irrelevant item, so the set value will be ignored. If the value is the default value or within the setting range, there is no problem.)


Control Major positioning control Manual control Position control Other control
Pr.31 JOG speed limit value – 12.4.1
Pr.32 JOG operation acceleration time selection –
Pr.33 JOG operation deceleration time selection –
Pr.37 Stop group 1 sudden stop selection –
Pr.38 Stop group 2 sudden stop selection –
Pr.39 Stop group 3 sudden stop selection –
Pr.40 Positioning complete signal output time –
Pr.41 Allowable circular interpolation error width –
Pr.42 External command function selection – – 12.5.1 12.7.2
: Always set : Set as required ("–" when not set) – : Setting not required (This is an irrelevant item, so the setting value will be ignored. If the value is the default value or within the setting range, there is no problem.)
Pr.1 to Pr.42 are checked with the following timing.
(1) When the "PLC READY signal [Y0]" output from the PLC CPU to the QD75
changes from OFF to ON (2) When the test operation button is turned ON in the test mode using GX
Configurator-QP (3) When an error check is carried out with GX Configurator-QP

When carrying out "OPR control", the "OPR parameters" must be set. The setting items for the "OPR parameters" are shown below. The "OPR parameters" are set commonly for each axis. Refer to Chapter 8 "OPR control" for details on the "OPR control", and to Section 5.2 "List of parameters" for details on each setting item.

Pr.48 OPR retry R R R – R R
Pr.49 OPR dwell time –
Pr.50 Setting for the movement amount after near- point dog ON –
Pr.53 OP shift amount S
Pr.55 Deviation counter clear signal output time C –
Pr.56 Speed designation during OP shift S
Pr.57 Dwell time during OPR retry R R R – R R
: Always set : Preset parameters are used for machine OPR control. – : Setting not required (This is an irrelevant item, so the setting value will be ignored. If the value is the default value or
within the setting range, there is no problem.) R : Set when using the "12.2.1 OPR retry function". ("–" when not set.) S : Set when using the "12.2.2 OP shift function". ("–" when not set.) C : Set the deviation counter clear signal output time. (Read as "–" when the setting is not required.)
Checking the OPR parameters.
Pr.43 to Pr.57 are checked with the following timing.
(1) When the "PLC READY signal [Y0]" output from the PLC CPU to the QD75
changes from OFF to ON (2) When the test operation button is turned ON in the test mode using GX
Configurator-QP (3) When an error check is carried out with GX Configurator-QP

Positioning data must be set for carrying out any "major positioning control". The table below lists the items to be set for producing the positioning data. One to 600 positioning data items can be set for each axis. For details of the major positioning controls, refer to Chapter 9 "Major Positioning Control". For details of the individual setting items, refer to Section 5.3 "List of positioning data".

Da.3 Acceleration time No. –
Da.4 Deceleration time No. –
: 2 axes – : 1/3/4 axes –
Da.6 Positioning address/ movement amount – – New address – – –
Da.7 Arc address –
:Always set :Set as required (Read "–" when not required.) :Setting not possible – :Setting not required.
(This is an irrelevant item, so the set value will be ignored. If the value is the default value or within the setting range, there is no problem.) :Two control systems are available: the absolute (ABS) system and incremental (INC) system.

The items Da.1 to Da.10 are checked at the following timings:
(1) Startup of a positioning operation (2) Error check performed by GX Configurator-QP

MEMO

The "block start data" must be set when carrying out "high-level positioning control". The setting items for the " block start data" are shown below. Up to 50 points of " block start data" can be set for each axis. Refer to Chapter 10 "High-level Positioning Control" for details on the "high-level positioning control", and to Section 5.4 "List of block start data" for details on each setting item.

: Set as required ("–" when not set) – : Setting not required (This is an irrelevant item, so the setting value will be ignored. If the value is the default value or within the
setting range, there is no problem.)
Da.11 to Da.14 are checked with the following timing.
(1) When the "Block start data" starts (2) When an error check is carried out with GX Configurator-QP

When carrying out "high-level positioning control" or using the JUMP instruction in the "major positioning control", the "condition data" must be set as required. The setting items for the "condition data" are shown below. Up to 10 "condition data" items can be set for each axis. Refer to Chapter 10 "High-level Positioning Control" for details on the "high-level positioning control", and to Section 5.5" List of condition data" for details on each setting item.

: Set as required ("–" when not set) : Setting limited – : Setting not required (This is an irrelevant item, so the setting value will be ignored. If the value is the default value or within the
setting range, there is no problem.)
Da.15 to Da.19 are checked with the following timing.
(1) When the " Block start data" starts (2) When "JUMP instruction" starts (3) When an error check is carried out with GX Configurator-QP
![Page 100 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Monitoring the system](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-100.webp?w=400)
The monitor data area in the buffer memory stores data relating to the operating state of the positioning system, which are monitored as required while the positioning system is operating. The following data are available for monitoring.
Monitoring of the QD75 configuration and operation history (through the system monitor data Md.1 through Md.19 )
Monitoring of the current position and speed, and other data related to the movements of axes (through the axis monitor data Md.20 through Md.48 )
The axis monitor data are refreshed every 1.8 ms. Note that " Md.21 Machine
feed value", " Md.22 Feedrate", " Md.28 Axis feedrate" and " Md.30 External input/output signal" are refreshed every 56.8ms. Also, " Md.23 Valid M code", is
updated when the "M code ON signal [X4, X5, X6, X7]" turns ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Monitoring the system diagram (page 100)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-100-1.webp)
Whether the system is in the test mode or not Md.1 In test mode flag
Axis in which the error occurred Md.9 Axis in which the error occurred
Hour Md.11 Axis error occurrence Hour Axis error occurrence
Axis in which the warning occurred Md.14 Axis in which the warning occurred
Hour Md.16 Axis warning occurrence (Hour) Axis warning occurrence Minute:second Md.17 Axis warning occurrence (Minute:second)
Number of write accesses to the flash ROM after the power is switched ON
Number of write accesses to flash ROM Md.19 No. of write accesses to flash ROM

Monitoring the position
Monitor details Corresponding item
Monitor the current machine feed value Md.21 Machine feed value
Monitor the current "current feed value" Md.20 Current feed value
Monitor the current target value Md.32 Target value
Monitor details Corresponding item
Indicates the speed of each axis
During independent axis control
When "0:
Indicates the composite speed During interpola- tion control
Composite speed" is set for " Pr.20
Md.22 Feedrate Monitor the current speed
Interpolation speed designation method"
When "1:
Reference axis speed" is set for " Pr.20
Indicates the reference axis speed
Interpolation speed designation method"
Constantly indicates the speed of each axis Md.28 Axis feedrate
Monitor the current target speed Md.33 Target speed

Monitor details Corresponding item
Monitor the axis operation state Md.26 Axis operation status
Monitor the latest error code that occurred with the axis Md.23 Axis error No.
Monitor the latest warning code that occurred with the axis Md.24 Axis warning No.
Md.30
Monitor the external input/output signal and flag
Md.31
Monitor the valid M codes Md.25 Valid M code
Monitor whether the speed is being limited Md.39 In speed control flag
Monitor whether the speed is being changed Md.40 In speed change processing flag
Monitor the "start data" point currently being executed Md.43 Start data pointer being executed
Monitor the "positioning data No." currently being executed Md.44 Positioning data No. being executed
Monitor the remaining No. of repetitions (special start) Md.41 Special start repetition counter
Monitor the remaining No. of repetitions (control system) Md.42 Control system repetition counter
Monitor the block No. Md.45 Block No. being executed
Monitor the current torque limit value Md.35 Torque limit stored value
Monitor the "instruction code" of the special start data when using special start
Md.36 Special start data instruction code setting value
Monitor the "instruction parameter" of the special start data when using special start
Md.37 Special start data instruction parameter setting value
Monitor the "start data No." of the special start data when using special start
Md.38 Start positioning data No. setting value
Monitor the "positioning data No." executed last Md.46 Last executed positioning data No.
Monitor the positioning data currently being executed Md.47 Positioning data being executed
Monitor the movement amount after the current position control switching when using "speed-position switching control (INC mode)"
Md.29 Speed-position switching control positioning amount
Monitor switching from the constant speed status or acceleration status to the deceleration status during position control whose operation pattern is "Positioning complete"
Md.48 Deceleration start flag
External input/output signal · Status

MEMO
![Page 104 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Controlling the system data](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-104.webp?w=400)
Operation of the positioning system is achieved through the execution of necessary controls. (Data required for controls are given through the default values when the power is switched ON, which can be modified as required by the sequence program.) Controls are performed over system data or machine operation.
Performs write/initialization, etc. of the QD75 "setting data". (through the system
Setting operation parameters, changing speed during operation, interrupting or restarting operation (through the axis control data Cd.3 to Cd.40 )
Setting and resetting the setting data
Control details Controlled data item
Write setting data from buffer memory to flash ROM Cd.1 Flash ROM write request
Reset (initialize) parameters Cd.2 Parameter initialization request
)
![Page 105 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Controlling the operation](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-105.webp?w=400)
Controlling the operation
Control details Corresponding item
Set which positioning to execute (start No.) Cd.3 Positioning start No.
Clear (reset) the axis error ( Md.23 ) and warning ( Md.24 ) Cd.5 Axis error reset
Issue instruction to restart (When axis operation is stopped) Cd.6 Restart command
End current positioning (deceleration stop), and start next positioning Cd.37 Skip command
Set start point No. for executing block start Cd.4 Positioning starting point No.
Stop continuous control Cd.18 Interrupt request during continuous operation
Cd.30 Simultaneous starting axis start data No. (axis 1 start data No.)
Cd.31 Simultaneous starting axis start data No. (axis 2 start data No.)
Set start data Nos. for axes that start up simultaneously
Cd.32 Simultaneous starting axis start data No. (axis 3 start data No.)
Cd.33 Simultaneous starting axis start data No. (axis 4 start data No.)
Specify write destination for teaching results Cd.38 Teaching data selection
Specify data to be taught Cd.39 Teaching positioning data No.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Controlling the operation diagram (page 105)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-105-1.webp)
Stop positioning operation after each operation Cd.35 Step valid flag
Set unit to carry out step Cd.34 Step mode
Issue instruction to continuous operation or restart from stopped step
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Controlling the operation diagram (page 105)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-105-2.webp)
Set new speed when changing speed during operation Cd.14 New speed value
Issue instruction to change speed in operation to Cd.14 value
Change positioning operation speed between 1 and 300% range Cd.13 Positioning operation speed override
When changing acceleration time during speed change, set new acceleration time
When changing deceleration time during speed change, set new deceleration time

Control details Corresponding item
Turn M code ON signal OFF Cd.7 M code OFF request
Set new value when changing current value Cd.9 New current value
Validate speed-position switching signal from external source Cd.24 Speed-position switching enable flag
Change movement amount for position control during speed-position switching control (INC mode)
Cd.23 Speed-position switching control movement amount change register
Validate external position-speed switching signal Cd.26 Position-speed switching enable flag
Change speed for speed control during position-speed switching control
Cd.25 Position-speed switching control speed change register
Set up a flag when target position is changed during positioning Cd.29 Target position change request flag
Set new positioning address when changing target position during positioning
Cd.27 Target position change value(new address)
Set new speed when changing target position during positioning Cd.28 Target position change value(new speed)
Set absolute (ABS) moving direction in degrees Cd.40 ABS direction in degrees
Set manual pulse generator operation validity Cd.21 Manual pulse generator enable flag
Set scale per pulse of No. of input pulses from manual pulse generator
Cd.20 Manual pulse generator 1 pulse input magnification
Change OPR request flag from "ON to OFF" Cd.19 OPR request flag OFF request
Validate external command signal Cd.8 External command valid
Change " Md.35 Torque limit stored value" Cd.22 New torque value
Set whether " Md.48 Deceleration start flag" is valid or invalid Cd.41 Deceleration start flag valid
Set the stop command processing for deceleration stop function (deceleration curve re-processing/deceleration curve continuation) Cd.42 Stop command processing for deceleration stop selection

MEMO

5.2.1 Basic parameters 1

Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
1 to 65535 1 to 32767 :Set as a decimal 32768 to 65535 :Convert into hexadecimal and set
No. of pulses per rotation (Ap) (Unit : pulse)
The setting value range differs according to the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
Set the unit used for defining positioning operations. Choose from the following units depending on the type of the control target: mm, inch, degree, or pulse. Different units can be defined for different axes (axis 1 to 4).
(Example) Different units (mm, inch, degree, and pulse) are applicable to different
machine specifications.) degree Rotating body (360 degrees/rotation) pulse X-Y table, conveyor
When you change the unit, note that the values of other parameters and data
will not be changed automatically. After changing the unit, check if the parameter and data values are within the allowable range. Set "degree" to exercise speed-position switching control (ABS mode).

These parameters define the amount of movement achieved by each single pulse within a pulse train output by the QD75.
The following paragraphs explain how to set the individual parameters Pr.2 ,
Pr.3 , and Pr.4 assuming that the unit "mm" is selected with Pr.1 . The movement amount per pulse is given by the following expression:
Movement amount per rotation (Al) Movement amount per pulse = No. of pulses per rotation (Ap)
Due to the mechanical tolerance, the actual movement amount may differ
slightly from the instructed movement amount. The error can be compensated by adjusting the movement amount per pulse defined here. (Refer to Section 12.3.2 "Electronic gear function".)
If the movement amount per pulse is less than 1, command frequency variations will occur. Smaller setting will increase variations and may cause machine vibration. If the movement amount per pulse becomes less than 1, also use the electronic gear function of the drive unit and make setting so that the movement amount per pulse is 1 or greater.
Set the number of pulses required for a complete rotation of the motor shaft. If you are using the Mitsubishi servo amplifier MR-H, MR-J2/J2S , or MR-C, set the value given as the "resolution per servomotor rotation" in the speed/position detector specifications.
No. of pulses per rotation (Ap) = Resolution per servomotor rotation
Since the "Resolution per servomotor revolution" of Mitsubishi servo amplifier MR-J2S
exceeds 65535 pulses, make setting after referring to the Servo Amplifier Instruction Manual.
Pr.1 setting value Value set with peripheral device
Value set with sequence program
The amount how the workpiece moves with one motor rotation is determined by the mechanical structure. If the worm gear lead (mm/rev) is PB and the deceleration rate is 1/n, then
Movement amount per rotation (AL) = PB × 1/n
(unit) · (unit)

However, the maximum value that can be set for this "movement amount per rotation (Al)" parameter is 6553.5µm (approx. 6.5mm). Set the "movement amount per rotation (Al)" as shown below so that the "movement amount per rotation (AL)" does not exceed this maximum value.
Movement amount per rotation (AL)
= PB × 1/n = Movement amount per rotation (Al) × Unit magnification (Am)
1/n" value exceeds 6553.5µm, adjust with the unit magnification so that the "movement amount per rotation (Al) " does not exceed 6553.5µm.
When movement amount per rotation (AL) = PB × 1/n = 6000.0µm (= 6mm)
Movement amount per rotation (AL)
= Movement amount per rotation (Al) × Unit magnification (Am) = 6000 × 1
When movement amount per rotation (AL) = PB × 1/n = 60000.0µm (= 60mm)
Movement amount per rotation (AL)
= Movement amount per rotation (Al) × Unit magnification (Am) = 6000 × 10 = 600 × 100

: Worm gear lead (mm/rev) : Deceleration rate : No. of encoder pulses (pulse/rev)

Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
Example 1) · Example 2)

Set the pulse output mode to match the servo amplifier being used.

The only valid value of the " Pr.5 Pulse output mode" is the value at the moment
when the PLC READY signal [Y0] turns from OFF to ON for the first time after the power is switched ON or the PLC CPU is reset. Once the PLC READY signal [Y0] has been turned ON, the value will not be reset even if another value is set to the parameter and the PLC READY signal [Y0] is turned from OFF to ON.
Use " Pr.23 Output signal logic selection" to choose between the positive logic
(pulse rising edge detection) and negative logic (pulse falling edge detection). An example of the pulse output mode for positive and negative logic is shown below.

During forward run, the forward run feed pulse (PULSE F) will be output. During reverse run, the reverse run feed pulse (PULSE R) will be output.


Forward run and reverse run are controlled with the phase difference of the A phase (A ) and B phase (B ).

When B phase is 90° behind A phase When B phase is 90° ahead of A phase
When B phase is 90° behind A phase When B phase is 90° ahead of A phase
When B phase is 90° behind A phase When B phase is 90° ahead of A phase
When B phase is 90° behind A phase When B phase is 90° ahead of A phase
Set the relation of the motor rotation direction and current value address increment/decrement.

("0" is set as the default value for Pr.6 .)
rotation direction. 3) Carry out forward run JOG operation again, and if "W" moves toward the increment direction, the setting is complete.

When Pr.6 has been changed from "0" to "1", check if the upper and lower limit
switches operate properly by JOG operation. If any malfunction is identified, check and correct the wiring.


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting range differs depending on the " Pr.1 Unit setting".
Here, the value within the [Table 1] range is set.
0 6 7 156 157 306 307 456 457
Set the bias speed (minimum speed) upon starting. The bias speed has to be defined to allow the motor to start smoothly especially when a stepping motor is used. (A stepping motor will not start smoothly if a low rotation speed is instructed at the beginning.) The specified "bias speed at start" will be valid during the following operations:

value Axis 1 Axis 2 Axis 3 Axis 4
Value set with peripheral device Value set with sequence
The setting range differs depending on the " Pr.1 Unit setting".
Here, the value within the [Table 2] range is set.
200000 10 11 160 161 310 311 460 461
1 to 8388608 (ms) 1 to 8388608 (ms) 1000 12 13 162 163 312 313 462 463
1 to 8388608 (ms) 1 to 8388608 (ms) 1000 14 15 164 165 314 315 464 465

![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 115)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-115-1.webp)
Pr.1 setting value Value set with peripheral device (unit) Value set with sequence program (unit)
Pr.1 setting value Value set with peripheral device (unit) Value set with sequence program (unit)
[Select type 1 is QD75P] 1 to 200000 (pulse/s) [Select type 1 is QD75D] 1 to 1000000 (pulse/s)
1 to 1000000 (pulse/s) 2
Set the maximum speed during positioning and OPR operations. The maximum speed during positioning control has to be limited in consideration of the drive unit and control target specifications. Take account of the following when determining the speed limit value:
" Pr.9 Acceleration time 0" specifies the time for the speed to increase from zero
to the speed limit value ( Pr.8 ).
" Pr.10 Deceleration time 0" specifies the time for the speed to decrease from the


Setting value, setting range Setting value buffer memory
Value set with peripheral device Value set with sequence program
Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs according to the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
Pr.11
0 17 167 317 467
[Table 1] on right page
Pr.12
The setting value range differs according to the " Pr.1 Unit
2147483647 18 19 168 169 318 319 468 469
Software stroke limit upper limit value
setting". Here, the value within the [Table 2] range is set.
Pr.13
[Table 2] on right page –2147483648 20 21 170 171 320 321 470 471
Software stroke limit lower limit value
Software stroke limit selection
0 Pr.15
0 23 173 323 473
Software stroke limit valid/invalid setting
The error that occurs due to backlash when moving the machine via gears can be compensated. When the backlash compensation amount is set, pulses equivalent to the compensation amount will be output each time the direction changes during positioning.

address Item · Default value · Backlash compensation amount

Backlash compensation amount 0 ≤ Movement amount per pulse ≤ 255
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 117)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-117-1.webp)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 2] diagram (page 117)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-117-2.webp)
Set the upper limit for the machine's movement range during positioning control.
Set the lower limit for the machine's movement range during positioning control.


1) Generally, the OP is set at the lower limit or upper limit of the stroke limit. 2) By setting the upper limit value or lower limit value of the software stroke limit, overrun can be prevented in the software. However, an emergency stop limit switch must be installed nearby outside the range. 3) To invalidate the software stroke limit, set the setting value to "upper limit value = lower limit value". (The setting value can be anything.) 4) When the unit is "degree", the software stroke limit check is invalid during speed control (including speed-position switching control, position-speed switching control) or during manual control.
Set whether to apply the software stroke limit on the "current feed value" or the "machine feed value". The software stroke limit will be validated according to the set value.
Set whether to validate the software stroke limit during JOG/Inching operation and manual pulse generator operation.

Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
100 24 25 174 175 324 325 474 475
1 to 500 (%) 1 to 500 (%) 300 26 176 326 476
M code ON signal output timing 1 : AFTER mode 1 0 27 177 327 477
Set the remaining distance that turns the command in-position ON. The command in-position signal is used as a front-loading signal of the positioning complete signal. When positioning control is started, the "command in-position flag" (3rd flag from right) in " Md.31 Status" turns OFF, and the "command in-position flag" turns
ON at the set position of the command in-position signal.


Set the maximum value of the torque generated by the servomotor as a percentage between 1 and 500%.
The torque limit function limits the torque generated by the servomotor within the set range. If the torque required for control exceeds the torque limit value, it is controlled with the set torque limit value.

Usage conditions Limits for pulse train output type (a) A drive unit that can issue a torque limit command with the analog voltage is required. (b) The D/A conversion module and the D/A conversion module and drive unit must be wired.
(c) The set " Pr.17 Torque limit setting value" is set in the buffer memory
" Md.35 Torque limit stored value", so transmit that " Md.35 Torque limit
stored value" to the D/A conversion module with the sequence program.
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 119)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-119-2.webp)
This parameter sets the M code ON signal output timing. Choose either WITH mode or AFTER mode as the M code ON signal output timing.

WITH mode An M code is output and the M code ON
AFTER mode An M code is output and the M code ON
signal is turned ON when a positioning operation starts.
signal is turned ON when a positioning operation completes.
turned ON.

An M code is a number between 0 and 65535 that can be assigned to each positioning data ( Da.10 ).
The sequence program can be coded to read an M code from the buffer memory address specified by " Md.25 Valid M code" whenever the M code ON signal [X4, X5,
X6, X7] turns ON so that a command for the sub work (e.g. clamping, drilling, tool change) associated with the M code can be issued.

Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
b0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Always "0" is set to the part not used.
b0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Always "0" is set to the part not used.

Set whether to switch the speed switching mode with the standard switching or front-loading switching mode.
The next positioning data starts positioning at the designated speed
Switch the speed when executing the next positioning data
n: Positioning
data No.
When carrying out linear interpolation/circular interpolation, set whether to designate the composite speed or reference axis speed.
Designate speed for reference axis
speed control has to be performed. If you specify the composite speed for a positioning operation that involves the 4-axis linear interpolation or 2 to 4 axis speed control, the error code 523 "interpolation mode error" will be output when the positioning operation is attempted. For a positioning operation that involves the circular interpolation, specify the composite speed always.

Specify whether you wish to enable or disable the update of " Md.20 Current feed
value" while operations are performed under the speed control (including the speed-position and position-speed switching control). 0: The update of the current feed value is disabled The current feed value will not change. (The value at the beginning of the speed control will be kept.) 1: The update of the current feed value is enabled The current feed value will be updated. (The current feed value will change from the initial.) 2: The current feed value is cleared to zero The current feed will be set initially to zero and change from zero while the speed control is in effect. Note1: When the speed control is performed over two to four axes, the choice
between enabling and disabling the update of " Md.20 Current feed value"
depends on how the reference axis is set. Note2: Set "1" to exercise speed-position switching control (ABS mode).
Set the I/O signal logic that matches the signaling specification of the connected external device. Note1: A mismatch in the signal logic will disable normal operation. Be careful of
this when you change from the default value. Note2: Set the manual pulse generator input logic selection (b8) to axis 1. (Setting
of any of axes 2 to 4 is invalid.)
Set the manual pulse generator input pulse mode. (Only the value specified against the axis 1 is valid.)
Select the mode of speed-position switching control.
with the setting regarded as 0.

MEMO


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
Pr.25 Acceleration time 1 36 37 186 187 336 337 486 487
Pr.26 Acceleration time 2 38 39 188 189 338 339 488 489
Pr.27 Acceleration time 3 40 41 190 191 340 341 490 491
1 to 8388608 (ms) 1 to 8388608 (ms) 1000
Pr.28 Deceleration time 1 42 43 192 193 342 343 492 493
Pr.29 Deceleration time 2 44 45 194 195 344 345 494 495
The setting range differs depending on the " Pr.1 Unit setting".
Here, the value within the [Table 1] range is set.
20000 48 49 198 199 348 349 498 499
These parameters set the time for the speed to increase from zero to the speed limit value ( Pr.8 ) during a positioning operation.
These parameters set the time for the speed to decrease from the speed limit value ( Pr.8 ) to zero during a positioning operation.

Pr.1 setting value Value set with peripheral device
Value set with sequence program
[Select type 1 is QD75P] 1 to 200000 (pulse/s) [Select type 1 is QD75D] 1 to 1000000 (pulse/s)
1 to 1000000 (pulse/s) 2
Set the maximum speed for JOG operation.
If the "speed limit value" is exceeded, the "JOG speed limit value error" (error code: 956) will occur.
Set which of "acceleration time 0 to 3" to use for the acceleration time during JOG operation.
Set which of "deceleration time 0 to 3" to use for the deceleration time during JOG operation.
(unit) · (unit)


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
1 to 100 (%) 1 to 100 (%) 100 53 203 353 503
1 to 8388608 (ms) 1 to 8388608 (ms) 1000 54 55 204 205 354 355 504 505
Set whether to use automatic trapezoid acceleration/deceleration or S-pattern acceleration/deceleration for the acceleration/deceleration process.
The acceleration and deceleration are linear.
The acceleration and deceleration follow a Sin curve.
The S-pattern acceleration/deceleration is disabled when a stepping motor is used.

Set the S-pattern ratio (1 to 100%) for carrying out the S-pattern acceleration/deceleration process. The S-pattern ratio indicates where to draw the acceleration/deceleration curve using the Sin curve as shown below.


Set the time to reach speed 0 from " Pr.8 Speed limit value" during the sudden
stop. The illustration below shows the relationships with other parameters.

When positioning is started, the acceleration starts following the "acceleration time".

to
Pr.39 Stop group 3 sudden stop selection
The methods of stopping include "0: Normal deceleration stop" and "1: Sudden stop". If "1: Sudden stop" is selected, the axis will suddenly decelerate to a stop when the stop signal is input.


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
100 60 61 210 211 360 361 510 511
Set the output time of the positioning complete signal [X14, X15, X16, X17] output from the QD75. A positioning completes when the specified dwell time has passed after the QD75 had terminated the output.

Positioning complete signal output time

Pr.1 setting value Value set with peripheral device
Value set with sequence program
With the "allowable circular interpolation error width", the allowable error range of the calculated arc path and end point address is set. If the error of the calculated arc path and end point address is within the set range, circular interpolation will be carried out to the set end point address while compensating the error with spiral interpolation. The allowable circular interpolation error width is set in the following axis buffer memory addresses.
Path with spiral interpolation Error
End point address with calculation
Start point address Center point address
With circular interpolation control using the center point designation, the arc path calculated with the start point address and center point address and the end point address may deviate.
(unit) · (unit) · End point address

Select a command with which the external command signal should be associated.
To enable the position-speed switching control, set the " Cd.26 Position-speed switching enable flag" to "1".
To enable the external command signal, set the " Cd.8 External command enable"
to "1".

MEMO


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
Set the "OPR method" for carrying out machine OPR. 0 : Near-point dog method After decelerating at the near-point dog ON, stop at the zero signal and complete the machine OPR. 1 : Stopper method 1) After decelerating at the near-point dog ON, stop with the stopper, and complete the machine OPR after the dwell time has passed. 2 : Stopper method 2) After decelerating at the near-point dog ON, stop with the stopper, and complete the machine OPR with the zero signal. 3 : Stopper method 3) After starting with the creep speed, stop with the stopper, and complete the machine OPR with the zero signal. 4 : Count method 1) After decelerating at the near-point dog ON, move the designated distance, and complete the machine OPR with the zero signal. 5 : Count method 2) After decelerating at the near-point dog ON, move the designated distance, and complete the machine OPR.
methods.
(1) Start machine OPR.
(Start movement at the " Pr.46 OPR speed" in the

" Pr.44 OPR direction".)
(2) Detect the near-point dog ON, and start deceleration.
(3) Decelerate to " Pr.47 Creep speed", and move with the
creep speed. (At this time, the near-point dog must be ON. If the near- point dog is OFF, the axis will decelerate to a stop.) (4) At the first zero signal (one pulse output at one motor
revolution) after the near-point dog OFF, the pulse output from the QD75 stops, and the machine OPR is completed.
OPR method · Creep speed · t

(1) Start machine OPR.
(Start movement at the " Pr.46 OPR speed" in the
" Pr.44 OPR direction".)

(2) Detect the near-point dog ON, and start deceleration.
(3) Decelerate to " Pr.47 Creep speed", and move with the
creep speed. (At this time " Pr.54 OPR torque limit value" is required. If
Range to forcibly stop the servomotor rotation with the stopper.
the torque is not limited, the servomotor could be damaged in step (4).)
(4) The axis contacts against the stopper at " Pr.47 Creep
speed", and then stops.
(5) When the near-point dog turns ON and the " Pr.49 OPR
dwell time" is passed, the pulse output from the QD75 stops, and the machine OPR is completed.
(1) Start machine OPR.
(Start movement at the " Pr.46 OPR speed" in the
" Pr.44 OPR direction".)
(2) Detect the near-point dog ON, and start deceleration.
OPR speed Pr.46
Pr.47
(3) Decelerate to " Pr.47 Creep speed", and move with the
Creep speed Stop with stopper
creep speed. (At this time " Pr.54 OPR torque limit value" is required. If
the torque is not limited, the servomotor could be damaged in step (4).)
(4) The axis contacts against the stopper at " Pr.47 Creep
OFF
speed", and then stops. (5) After stopping, the pulse output from the QD75 stops with
the zero signal (signal that is output on detection of contact with the stopper. Input externally), and the machine OPR is completed.
(1) Start machine OPR.
(Start movement at the " Pr.47 Creep speed" in the
" Pr.44 OPR direction". At this time " Pr.54 OPR torque
Creep speed Pr.47
limit value" is required. If the torque is not limited, the servomotor could be damaged in step (2).)
(2) The axis contacts against the stopper at " Pr.47 Creep
speed", and then stops. (3) After stopping, the pulse output from the QD75 stops with
the zero signal (signal that is output on detection of contact with the stopper. Input externally), and the machine OPR is completed.

(1) Start machine OPR.
(Start movement at the " Pr.46 OPR speed" in the
" Pr.44 OPR direction".)
OPR speed Pr.46
Pr.50
Setting for the movement amount after near-poing dog ON
(2) Detect the near-point dog ON, and start deceleration.
Pr.47 Creep speed
(3) Decelerate to " Pr.47 Creep speed", and move with the
creep speed. (4) After the near-point dog turns ON and the movement
Movement amount after near-point dog ON Md.34
amount set in " Pr.50 Setting for the movement amount
The near-point dog must turn OFF at a sufficient distance away from the OP position.
after near-point dog ON" has passed, the pulse output from the QD75 stops with the first zero signal (one pulse output at one motor revolution), and the machine OPR is completed.
First zero signal after moving the movement amount after near- point dog ON
(1) Start machine OPR.
(Start movement at the " Pr.46 OPR speed" in the
" Pr.44 OPR direction".)
OPR speed Pr.46
Pr.50
Setting for the movement amount after near-poing dog ON
(2) Detect the near-point dog ON, and start deceleration.
Pr.47 Creep speed
(3) Decelerate to " Pr.47 Creep speed", and move with the
creep speed. (4) After the near-point dog turns ON and the movement
Movement amount after near-point dog ON Md.34
amount set in " Pr.50 Setting for the movement amount
after near-point dog ON" has passed, the pulse output from the QD75 stops with the first zero signal, and the machine OPR is completed.

Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
0 72 73 222 223 372 373 522 523
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 2] range is set.
1 74 75 224 225 374 375 524 525
![Page 137 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Table 2]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-137.webp?w=400)
Set the direction to start movement when starting machine OPR.
Normally, the OP is set near the lower limit or the upper limit, so " Pr.44 OPR
direction" is set as shown below.

When the zero point is set at the lower limit side, the OPR direction is in the direction of arrow 1). Set "1" for . Pr.44
When the OP is set at the upper limit side, the OPR direction is in the direction of arrow 2). Set "0" for . Pr.44
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 137)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-137-2.webp)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 2] diagram (page 137)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-137-3.webp)

Set the address used as the reference point for positioning control (ABS system). (When the machine OPR is completed, the stop position address is changed to the address set in " Pr.45 OP address". At the same time, the " Pr.45 OP address"
is stored in " Md.20 Current feed value" and " Md.21 Machine feed value".)
Set the speed for OPR.
limit value" is exceeded, the "OPR speed" will be limited by " Pr.8 Speed
limit value". The "OPR speed" should be equal to or faster than the " Pr.7 Bias speed
at start" and " Pr.47 Creep speed".
Setting value, setting range Setting value buffer memory
Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
Pr.47
1 76 77 226 227 376 377 526 527
[Table 1] on right page
![Page 139 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Table 1]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-139.webp?w=400)
Set the creep speed after near-point dog ON (the low speed just before stopping after decelerating from the OPR speed). The creep speed is set within the following range.
( Pr.46 OPR speed ) ( Pr.47 Creep speed) ( Pr.7 Bias speed at start)
method with zero signal, and the size of the collision if a collision occurs during OPR method using the stopper method. Set a speed equal to or faster than the bias speed at start.

![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 139)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-139-2.webp)

Set whether to carry out OPR retry. When the OPR retry function is validated and the machine OPR is started, first the axis will move in the OPR direction (1)). If the upper/lower limit signal turns OFF before the near-point dog signal ON is detected (2)), the axis will decelerate to a stop, and then will move in the direction opposite to the specified OPR direction (3)). If the falling edge of the near-point dog signal is detected during movement in the opposite direction, the axis will decelerate to a stop (4)), and will carry out machine OPR again (5), 6)).


MEMO


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
0 to 65535 (ms) 0 to 32767 : Set as a decimal 32768 to 65535 : Convert into hexadecimal and set
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
0 80 81 230 231 380 381 530 531
Setting for the movement amount after near-point dog ON
When stopper method 1) is set for " Pr.43 OPR method", set the time for the
machine OPR to complete after the near-point dog signal turns ON. The setting value must be longer than the movement time from the near-point dog signal ON to stopping with the stopper. (If the OPR method is not "stopper method 1)", the " Pr.49 OPR dwell time" value
is irrelevant.)
When using the count method 1) or 2), set the movement amount to the OP after the near-point dog signal turns ON. (The movement amount after near-point dog ON should be equal to or greater than the sum of the "distance covered by the deceleration from the OPR speed to the creep speed" and "distance of movement in 10 ms at the OPR speed".)

Pr.1 setting value Value set with peripheral device
Value set with sequence program
Example of setting for " Pr. 50 Setting for the movement amount after near-point dog ON"
Assuming that the " Pr. 8 Speed limit value" is set to 200 kpulse/s, " Pr. 46 OPR speed" to 10 kpulse/s, " Pr. 47 Creep speed" to 1 kpulse/s, and deceleration time to 300 ms, the minimum value of " Pr. 50 Setting for the movement amount after near-point dog ON" is calculated as follows:
1 2 Vz 1000 t + 0.01 Vz
Movement amount for 10ms at OPR speed
Vp + 0.01 Vz Vz 2000
300 10 10 200 10 10 10 2000
3 + 0.01 10 10
= 75 + 100 = 175
Pr.47
Setting for the movement amount after near-point dog ON ( Pr. 50 ) should be equal to or larger than 175.
Actual deceleration time:t = Tb t Vz Vp
Set which of "acceleration time 0 to 3" to use for the acceleration time during OPR.
Set which of "deceleration time 0 to 3" to use for the deceleration time during OPR.


value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs depending on the " Pr.1 Unit setting".
Here, the value within the [Table 1] range is set.
0 84 85 234 235 384 385 534 535
1 to 300 (%) 1 to 300 (%) 300 86 236 386 536
1 to 65535 (ms) 0 to 32767: Set the decimal value as it is. 32768 to 65535: Convert the decimal value into a hexadecimal value and set the latter.
Speed designation during OP shift 1 : Creep speed 1 0 88 238 388 538
0 to 65535 (ms) 0 to 32767 : Set as a decimal 32768 to 65535 : Convert into hexadecimal and set
Set the amount to shift (move) from the position stopped at with machine OPR.
The OP shift function is used to compensate the OP position stopped at with machine OPR. If there is a physical limit to the OP position, due to the relation of the near-point dog installation position, use this function to compensate the OP to an optimum position.


![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 145)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-145-1.webp)
Set the value to limit the servomotor torque after reaching the creep speed during machine OPR. Refer to Section 12.4.2 "Torque limit function" for details on the torque limits.
Set the duration of the deviation counter clear signal output during a machine OPR operation using any of the following methods: the near-point dog method, stopper methods 1) to 3), and count method 1). (For details, refer to your drive unit manual.)
Set the operation speed for when a value other than "0" is set for " Pr.53 OP shift amount". Select the setting from " Pr.46 OPR speed" or " Pr.47 Creep speed".
When OPR retry is validated (when "1" is set for Pr.48 ), set the stop time after
decelerating in 2) and 4) in the following drawing.

Temporarily stop for the time set in Pr. 57
Temporarily stop for the time set in Pr. 57 1) 2)

Before explaining the positioning data setting items Da.1 to Da.10 , the configuration
of the positioning data will be shown below. The positioning data stored in the QD75 buffer memory has the following type of configuration.

ˆÊ ’u Œ ˆ ‚ß ƒf [ ƒ^ ‡‚ @ 600
ˆÊ ’u Œ ˆ ‚ß ƒf [ ƒ^ ‡‚ @ 599
Up to 600 positioning data items can be set (stored) for each axis in the buffer memory address shown on the left. This data is controlled as positioning data No. 1 to 600 for each axis.
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
One positioning data item is configured of the items shown in the bold box.
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒf [ ƒ^ ‡‚ @ 599
ˆÊ ’u Œ ˆ ‚ß ƒf [ ƒ^ ‡‚ @ 600
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX


ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
ˆÊ ’u Œ ˆ ‚ß ƒA ƒh ƒŒ ƒX
The descriptions that follow relate to the positioning data set items Da.1 to Da.10 .
(The buffer memory addresses shown are those of the "positioning data No. 1" for the axes 1 to 4.)
Buffer memory address · Buffer memory address


value Axis 1 Axis 2 Axis 3 Axis 4
Value set with peripheral device Value set with sequence program
ABS1 :1-axis linear control (ABS) 01H INC1 :1-axis linear control (INC) 02H

The operation pattern designates whether positioning of a certain data No. is to be ended with just that data, or whether the positioning for the next data No. is to be carried out in succession.
Positioning complete Independent positioning control (Positioning complete)
Continuous positioning with one start signal Continuous positioning control
Continuous path positioning with speed change Continuous path control
Set the "control system" for carrying out positioning control.
Dwell time" and " Da.10 M code" setting details will differ.
M code" should be set differently from other cases. • Refer to Chapter 9 "Major positioning control" for details on the control systems.
cannot be carried out. (The "Circular interpolation not possible error" will occur when executed (error code: 535).)
Da.3 Acceleration time No.
Set which of "acceleration time 0 to 3" to use for the acceleration time during positioning.
[Operation pattern] · Positioning continued

Da.4 Deceleration time No.
Set which of "deceleration time 0 to 3" to use for the deceleration time during positioning.
Setting value, setting range Setting value buffer memory
Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs according to the " Da.2 Control
Da.6
system". Here, the value within the following range of [Table 1] range is set.
0 2006 2007 8006 8007 14006 14007 20006 20007
Positioning address/ movement amount
[Table 1] on right page
Set the address to be used as the target value for positioning control.
The setting value range differs according to the " Da.2 Control system".
Stop position (positioning start address)
![Page 151 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Table 1]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-151.webp?w=400)
fixed-feed 4
Stop position (positioning start position)
Moves in negative direction
Moves in positive direction
When " Pr.1 Unit Setting" is "mm"
The table below lists the control systems that require the setting of the positioning address or movement amount and the associated setting ranges. (With any control system excluded from the table below, neither the positioning address nor the movement amount needs to be set.)
Da.2 setting value Value set with peripheral device
Value set with sequence program 1 (×10-1µm)
ABS Linear 1 : 01H ABS Linear 2 : 0AH ABS Linear 3 : 15H ABS Linear 4 : 1AH Current value changing : 81H
◊ Set the address
◊ Set the address
-214748364.8 to 214748364.7
INC Linear 1 : 02H INC Linear 2 : 0BH INC Linear 3 : 16H INC Linear 4 : 1BH Fixed-feed 1 : 03H Fixed-feed 2 : 0CH Fixed-feed 3 : 17H Fixed-feed 4 : 1CH
◊ Set the movement amount
◊ Set the movement amount
-214748364.8 to 214748364.7
Forward run speed/position: 06H Reverse run speed/position: 07H Forward run position/speed: 08H Reverse run position/speed: 09H
◊ Set the movement amount
0 to 214748364.7 ◊ Set the movement amount
◊ Set the address
◊ Set the address
-214748364.8 to 214748364.7
◊ Set the movement amount
◊ Set the movement amount
-214748364.8 to 214748364.7

Movement amount setting (INC mode)
Speed control Target address setting (ABS mode)
When " Pr.1 Unit Setting" is "degree"
The table below lists the control systems that require the setting of the positioning address or movement amount and the associated setting ranges. (With any control system excluded from the table below, neither the positioning address nor the movement amount needs to be set.)
Da.2 setting value Value set with peripheral device
Value set with sequence program 1 (×10-5 degree)
ABS Linear 1 : 01H ABS Linear 2 : 0AH ABS Linear 3 : 15H ABS Linear 4 : 1AH Current value changing : 81H
◊ Set the address
0 to 359.99999 ◊ Set the address
INC Linear 1 : 02H INC Linear 2 : 0BH INC Linear 3 : 16H INC Linear 4 : 1BH Fixed-feed 1 : 03H Fixed-feed 2 : 0CH Fixed-feed 3 : 17H Fixed-feed 4 : 1CH
◊ Set the movement amount
◊ Set the movement amount
-21474.83648 to 21474.83647
In INC mode ◊ Set the movement amount
In INC mode ◊ Set the movement amount
0 to 21474.83647 In ABS mode ◊ Set the address
0 to 2147483647 In ABS mode ◊ Set the address
0 to 359.99999
◊ Set the movement amount
0 to 21474.83647 ◊ Set the movement amount

When " Pr.1 Unit Setting" is "pulse"
The table below lists the control systems that require the setting of the positioning address or movement amount and the associated setting ranges. (With any control system excluded from the table below, neither the positioning address nor the movement amount needs to be set.)
Value set with sequence program 1 (pulse) ABS Linear 1 : 01H ABS Linear 2 : 0AH ABS Linear 3 : 15H ABS Linear 4 : 1AH Current value changing : 81H
Da.2 setting value Value set with peripheral device
◊ Set the address
◊ Set the address
INC Linear 1 : 02H INC Linear 2 : 0BH INC Linear 3 : 16H INC Linear 4 : 1BH Fixed-feed 1 : 03H Fixed-feed 2 : 0CH Fixed-feed 3 : 17H Fixed-feed 4 : 1CH
◊ Set the movement amount
◊ Set the movement amount
Forward run speed/position: 06H Reverse run speed/position: 07H Forward run position/speed: 08H Reverse run position/speed: 09H
◊ Set the movement amount
0 to 2147483647 ◊ Set the movement amount
◊ Set the address
◊ Set the address
◊ Set the movement amount
◊ Set the movement amount

When " Pr.1 Unit Setting" is "inch"
The table below lists the control systems that require the setting of the positioning address or movement amount and the associated setting ranges. (With any control system excluded from the table below, neither the positioning address nor the movement amount needs to be set.)
Da.2 setting value Value set with peripheral device
Value set with sequence program 1 (×10-5 inch)
ABS Linear 1 : 01H ABS Linear 2 : 0AH ABS Linear 3 : 15H ABS Linear 4 : 1AH Current value changing : 81H
◊ Set the address
◊ Set the address
-21474.83648 to 21474.83647
INC Linear 1 : 02H INC Linear 2 : 0BH INC Linear 3 : 16H INC Linear 4 : 1BH Fixed-feed 1 : 03H Fixed-feed 2 : 0CH Fixed-feed 3 : 17H Fixed-feed 4 : 1CH
◊ Set the movement amount
◊ Set the movement amount
-21474.83648 to 21474.83647
Forward run speed/position: 06H Reverse run speed/position: 07H Forward run position/speed: 08H Reverse run position/speed: 09H
◊ Set the movement amount
0 to 21474.83647 ◊ Set the movement amount
◊ Set the address
◊ Set the address
-21474.83648 to 21474.83647
◊ Set the movement amount
◊ Set the movement amount
-21474.83648 to 21474.83647

MEMO


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs according to the " Da.2 Control
system". Here, the value within the [Table 1] range is set.
0 2008 2009 8008 8009 14008 14009 20008 20009
The arc address is data required only when carrying out circular interpolation control. (1) When carrying out circular interpolation with sub point designation, set the sub
point (passing point) address as the arc address. (2) When carrying out circular interpolation with center point designation, set the
center point address of the arc as the arc address.
End point address (Address set with Da.6 )
End point address (Address set with Da.6 )
Center point address (Address set with Da.7 )
Sub point (Address set with Da.7 )
Start point address (Address before starting positioning) Start point address (Address before starting positioning)
When not carrying out circular interpolation control, the value set in " Da.7 Arc
address" will be invalid.
point designation> · point designation>
![Page 157 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Table 1]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-157.webp?w=400)
When " Pr.1 Unit Setting" is "mm"
The table below lists the control systems that require the setting of the arc address and shows the setting range. (With any control system excluded from the table below, the arc address does not need to be set.)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 157)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-157-1.webp)
Value set with sequence program 1 (×10-1µm)
When " Pr.1 Unit Setting" is "degree"
No control system requires the setting of the arc address by "degree".
When " Pr.1 Unit Setting" is "pulse"
The table below lists the control systems that require the setting of the arc address and shows the setting range. (With any control system excluded from the table below, the arc address does not need to be set.)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 157)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-157-2.webp)
Value set with sequence program 1 (pulse) ABS circular sub : 0DH ABS circular right : 0FH ABS circular left : 10H
When " Pr.1 Unit Setting" is "inch"
The table below lists the control systems that require the setting of the arc address and shows the setting range. (With any control system excluded from the table below, the arc address does not need to be set.)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 157)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-157-3.webp)
Value set with sequence program 1 (×10-5 inch)


Value set with peripheral device Value set with sequence
value Axis 1 Axis 2 Axis 3 Axis 4
The setting value range differs depending on the " Pr.1 Unit
setting". Here, the value within the [Table 1] range is set.
0 2004 2005 8004 8005 14004 14005 20004 20005
The setting value range differs according to the " Da.2 Control
system". Here, the value within the [Table 2] range is set.
The setting value range differs according to the " Da.2 Control
system". Here, the value within the [Table 3] range is set.
Set the command speed for positioning.
(1) If the set command speed exceeds " Pr.8 Speed limit value", positioning will
be carried out at the speed limit value. (2) If "-1" is set for the command speed, the current speed (speed set for previous
positioning data No.) will be used for positioning control. Use the current speed for uniform speed control, etc. If "-1" is set for continuing positioning data, and the speed is changed, the following speed will also change.
(Note that when starting positioning, if the "-1" speed is set for the positioning
data that carries out positioning control first, the error "No command speed" (error code: 503) will occur, and the positioning will not start. Refer to Section 15.2 "List of errors" for details on the errors.)
![Page 159 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Table 3]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-159.webp?w=400)
Set an "M code", a "condition data No. ", or the "number of LOOP to LEND repetitions" depending on how the " Da.2 Control system" is set.
Set an "M code".
If no "M code" needs to be output, set "0" (default value).
Set the "condition data No." for JUMP.
by Da.9 .
1 to 10 : JUMP performed according to the condition data No. specified (a number between 1 and 10). Make sure that you specify the number of LOOP to LEND repetitions by a number other than "0". The "Control system LOOP setting error" will occur if you specify "0". (error code: 545) The condition data specifies the condition for the JUMP instruction to be
executed. (A JUMP will take place when the condition is satisfied.)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 1] diagram (page 159)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-159-1.webp)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 2] diagram (page 159)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-159-2.webp)
Da.2 setting value Setting item Value set with peripheral
Other than JUMP instruction Dwell time 0 to 65535 (ms) 0 to 65535 (ms)
![Mitsubishi Electronics MELSEC-Q QD75D — [Table 3] diagram (page 159)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-159-3.webp)
Da.2 setting value Setting item Value set with peripheral
Other than JUMP instruction M code 0 to 65535 0 to 65535

Da.9 Dwell time/JUMP designation positioning data No.
Set the "dwell time" or "positioning data No." corresponding to the " Da.2 Control
system".
Set the "dwell time".
Set the "positioning data No." for the JUMP destination.
When the "dwell time" is set, the setting details of the "dwell time" will be as follows according to " Da.1 Operation pattern".

Set the time from when the positioning ends to when the "positioning complete signal" turns ON as the "dwell time".
Set the time from when positioning control ends to when the next positioning control starts as the "dwell time".
The setting value is irrelevant to the control. (The "dwell time" is 0ms.)

MEMO

The illustrations below show the organization of the block start data stored in the QD75 buffer memory. The block start data setting items Da.11 to Da.14 are explained in
the pages that follow.

Up to 50 block start data points can be set (stored) for each axis in the buffer memory addresses shown on the left. Items in a single unit of block start data are shown included in a bold frame. Each axis has five start blocks (block Nos. 0 to 4).
œ ˆÊ ’u Œ ˆ ‚ß n “® ƒf [ ƒ^
For information on the organization of the buffer memory addresses assigned to the start blocks 1 to 4, refer to Appendix 12 "List of buffer memory addresses".
œ ˆÊ ’u Œ ˆ ‚ß n “® ƒf [ ƒ^


œ ˆÊ ’u Œ ˆ ‚ß n “® ƒf [ ƒ^
œ ˆÊ ’u Œ ˆ ‚ß n “® ƒf [ ƒ^
The pages that follow explain the block start data setting items ( Da.11 to Da.14 ).
(The buffer memory addresses shown are those of the "1st point block start data (block No. 7000)" for the axes 1 to 4.)

To perform an high-level positioning control using block start data, set a number between 7000 and 7004 to the " Cd.3 Positioning start No." and use the
" Cd.4 Positioning starting point No." to specify a point number between 1 and 50, a
position counted from the beginning of the block. The number between 7000 and 7004 specified here is called the "block No.". With the QD75, up to 50 "block start data" points and up to 10 "condition data" items can be assigned to each "block No.".

Block No. Axis Block start data Condition Buffer memory
: Setting cannot be made when the "Pre-reading start function" is used. If you set any of Nos.
7000 to 7004 and perform the Pre-reading start function, "Outside start No. range error (error code: 543)" will occur. (For details, refer to Section 12.7.8 "Pre-reading start function".)


value Axis 1 Axis 2 Axis 3 Axis 4
1 to 600 (01H to 258H)
1 to 10 (01H to 0AH) No. of repetitions:
0 to 255 (00H to FFH)

Set whether to carry out only the local "block start data" and then end control, or to execute the "block start data" set in the next point.
Setting value Setting details
Da.12 Start data No.
Set the "positioning data No." designated with the "block start data".
Set the "special start instruction " for using "high-level positioning control". (Set how to start the positioning data set in " Da.12 Start data No.".)
Setting value Setting details
00H : Block start (Normal start) Execute the random block positioning data in the set order with one start.
01H : Condition start Carry out the condition judgment set in "condition data" for the designated positioning data, and when the conditions are established, execute the "block start data". If not established, ignore that "block start data", and then execute the next point's "block start data".
02H : Wait start Carry out the condition judgment set in "condition data" for the designated positioning data, and when the conditions are established, execute the "block start data". If not established, stop the control (wait) until the conditions are established.
Simultaneous execute (output pulses at same timing) the positioning data with the No. designated for the axis designated in the "condition data". Up to four axes can start simultaneously.
Repeat the program from the block start data with the "FOR loop" to the block start data with "NEXT" for the designated No. of times.
Repeat the program from the block start data with the "FOR condition" to the block start data with "NEXT" until the conditions set in the "condition data" are established.
06H : NEXT start Set the end of the repetition when "05H: Repetition start (FOR loop)" or "06H: Repetition start (FOR condition)" is set.
Refer to Chapter 10 "High-level Positioning Control" for details on the control.

Set the value as required for " Da.13 Special start instruction ".
Da.13 Special start instruction Setting value Setting details
Block start (Normal start) – Not used. (There is no need to set.)
Set the condition data No. (No. of "condition data" set to perform condition judgment) (For details of the condition data, refer to Section 5.5.)
Repeated start (FOR loop) 0 to 255 Set the No. of repetitions.
Set the condition data No. (No. of "condition data" set to perform condition judgment) (For details of the condition data, refer to Section 5.5.)
Repeated start (FOR condition) 1 to 10

The illustrations below show the organization of the condition data stored in the QD75 buffer memory. The condition data setting items Da.15 to Da.19 are explained in the
pages that follow.

Up to 10 block start data points can be set (stored) for each axis in the buffer memory addresses shown on the left. Items in a single unit of condition data are shown included in a bold frame. Each axis has five start blocks (block Nos. 0 to 4).
For information on the organization of the buffer memory addresses assigned to the start blocks 1 to 4, refer to Appendix 12 "List of buffer memory addresses".
26191 26192 26193 26194 26195 26196 26197 26198 26199
26111 26112 26113 26114 26115 26116 26117 26118 26119
26101 26102 26103 26104 26105 26106 26107 26108 26109

27191 27192 27193 27194 27195 27196 27197 27198 27199
27111 27112 27113 27114 27115 27116 27117 27118 27119
27101 27102 27103 27104 27105 27106 27107 27108 27109


28191 28192 28193 28194 28195 28196 28197 28198 28199
28111 28112 28113 28114 28115 28116 28117 28118 28119
28101 28102 28103 28104 28105 28106 28107 28108 28109

29191 29192 29193 29194 29195 29196 29197 29198 29199
29111 29112 29113 29114 29115 29116 29117 29118 29119
29101 29102 29103 29104 29105 29106 29107 29108 29109
The pages that follow explain the condition data setting items ( Da.15 to Da.19 ).
(The buffer memory addresses shown are those of the "condition data No. 1 (block No. 7000)" for the axes 1 to 4.)

To perform an high-level positioning control using block start data, set a number between 7000 and 7004 to the " Cd.3 Positioning start No." and use the
" Cd.4 Positioning starting point No." to specify a point number between 1 and 50, a
position counted from the beginning of the block. The number between 7000 and 7004 specified here is called the "block No.". With the QD75, up to 50 "block start data" points and up to 10 "condition data" items can be assigned to each "block No.".

Block No. Axis Block start data Condition Buffer memory
: Setting cannot be made when the "Pre-reading start function" is used. If you set
any of Nos. 7000 to 7004 and perform the Pre-reading start function, "Outside start No. range error (error code: 543)" will occur. (For details, refer to Section 12.7.8 "Pre-reading start function".)


value Axis 1 Axis 2 Axis 3 Axis 4
Value set with peripheral device Value set with sequence program
0000H 26102 26103 27102 27103 28102 28103 29102 29103
0000H 26104 26105 27104 27105 28104 28105 29104 29105
0000H 26106 26107 27106 27107 28106 28107 29106 29107

Set the condition target as required for each control.

Setting value Setting details 01H : Device X 02H : Device Y Set the input/output signal ON/OFF as the conditions.
Set the value stored in the buffer memory as the condition. 03H: The target buffer memory is "1-word (16 bits)" 04H: The target buffer memory is "2-word (32 bits)" 05H : Positioning data No. Select only for "simultaneous start".
Set the condition operator as required for the " Da.15 Condition target".
Da.15 Condition target Setting value Setting details
07H :DEV=ON 01H: Device X 02H: Device Y 08H :DEV=OFF The state (ON/OFF) of an I/O signal is defined as the condition. Select ON or OFF as the trigger.
Select how to use the value (∗∗) in the buffer memory as a part of the condition.
10H :Axis 1 selected 20H :Axis 2 selected 30H :Axes 1 and 2 selected 40H :Axis 3 selected 50H :Axes 1 and 3 selected 60H :Axes 2 and 3 selected 70H :Axes 1, 2, and 3 selected 80H :Axis 4 selected 90H :Axes 1 and 4 selected A0H :Axes 2 and 4 selected B0H : Axes 1, 2, and 4 selected C0H : Axes 3 and 4 selected D0H : Axes 1, 3, and 4 selected
If "simultaneous start" is specified, select the axis (or axes) that should start simultaneously.
05H: Positioning data No.
E0H :Axes 2, 3, and 4 selected

Set the address as required for the " Da.15 Condition target".
01H : Device X 02H : Device Y – Not used. (There is no need to set.)
Set the target "buffer memory address". (For 2 word, set the low-order buffer memory address.)

Set the parameters as required for the " Da.16 Condition operator".
Da.16 Condition operator Setting value Setting details
The value of P1 should be equal to or smaller than the value of P2. (P1≤P2) If P1 is greater than P2 (P1>P2), the "condition data error" (error code 533) will occur.
Set the device bit No.
X: 0H to 1H, 4H to 11H Y: 0, 4H to 17H
Set the positioning data No. for starting axis 1 and/or axis 2.
Value (positioning data No.)
: Axis 1 positioning data No. 1 to 600 (01H to 258H) High-order 16-bit
: Axis 2 positioning data No. 1 to 600 (01H to 258H)
Set the parameters as required for the " Da.16 Condition operator".
Da.16 Condition operator Setting value Setting details
— Not used. (No need to be set.)
The value of P2 should be equal to or greater than the value of P1. (P1≤P2) If P1 is greater than P2 (P1>P2), the "condition data error" (error code 533) will occur. 07H : DEV=ON 08H : DEV=OFF 10H : Axis 1 selected 20H : Axis 2 selected 30H : Axes 1 and 2 selected
— Not used. (No need to be set.)
40H : Axis 3 selected 50H : Axes 1 and 3 selected 60H : Axes 2 and 3 selected 70H : Axes 1, 2, and 3 selected 80H : Axis 4 selected 90H : Axes 1 and 4 selected A0H : Axes 2 and 4 selected B0H : Axes 1, 2, and 4 selected C0H : Axes 3 and 4 selected D0H : Axes 1, 3, and 4 selected E0H : Axes 2, 3, and 4 selected
Set the positioning data No. for starting axis 3 and/or axis 4.
Value (positioning data No.)
: Axis 3 positioning data No. 1 to 600 (01H to 258H) High-order 16-bit
: Axis 4 positioning data No. 1 to 600 (01H to 258H)
Value · Low-order 16-bit · Low-order 16-bit

Storage item Storage details
Whether the mode is the test mode from the peripheral device or not is stored.
Md.1 In test mode flag

Storage buffer memory address (common for axis 1 to
Reading the monitor value Default value
Monitoring is carried out with a decimal.
Monitor value 0 1200
(Unless noted in particular, the monitor value is saved as binary data.)
axis 4)

Storage item Storage details Reading the monitor value
[Storage details] This area stores the start information (restart flag, start origin, and start axis):
b15 b12 b8 b4 b0 Buffer memory Monitor value
0
Md.3
Stored contents Storage value
Stored contents Storage value
Starting history (Up to 16 records can be stored)
Stored contents Storage value
1 Restart flag ON
Monitoring is carried out with a hexadecimal display.
b15 b12 b8 b4 b0
Start No.
Stored contents Storage value Reference
B C D
Md.4
0 0 0 to
The starting No. is stored.
Start No.
1 B 5 8 0 2 5 8 7000
1 B 5 9 7001 1 B 5 A 7002 1 B 5 B 7003 1 B 5 C 7004
JOG operation 2 3 3 2 9010
2 3 3 3 9011 Manual pulse generator
2 3 2 9 9001
Fast OPR 2 3 2 A 9002 Current value changing 2 3 2 B 9003
Simultaneous start 2 3 2 C 9004
Monitoring is carried out with a hexadecimal display.
Md.5
Buffer memory (stored with BCD code)
0 b15 b12 0 1 0 1 0 1 b8 b4 b0 0 1 5 0
The starting time is stored.
0 0 0 to 2 00 to 23 (hour) 0 to 3
Monitoring is carried out with a hexadecimal display.
Md.6
Buffer memory (stored with BCD code)
The starting time is stored.
0 b15 b12 1 0 0 1 0 0 1 0 1 1 1 b8 b4 b0 9 0 7 4
0 to 5 0 to 9 00 to 59 (minute) 0 to 9
0 to 5 00 to 59 (second)
record relating to an earlier start signal is output.

Default value Storage buffer memory address (common to axes 1 to 4)
1292 Md.8
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing starting history records.
Pointer No.
Pointer No. 0
Md.3
Md.4
Start No.
Md.5
Md.6
Md.7
Each group of buffer memory addresses storing a complete starting history
record is assigned a pointer No. Example: Pointer No. 0 = Buffer memory addresses 1212 to 1216
Item Buffer memory address
Pointer No. 1 = Buffer memory addresses 1217 to 1221 Pointer No. 2 = Buffer memory addresses 1222 to 1226
Pointer No. 15 = Buffer memory addresses 1287 to 1291 Each history record is assigned a pointer No. in the range between 0 and 15. If the pointer No. 15 has been assigned to a new record, the next record will
be assigned the pointer number 0. (A new record replaces an older record when a pointer No. is reassigned.)


[Storage details] This area stores the following results of the error judgment performed upon starting:
Starting history (Up to 16 records can be stored)
Error flag Error No. Convert the hexadecimal value "a, B, C, D" into a decimal value and match it with "15.2 List of errors".
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing starting history records.

Default value Storage buffer memory address (common to axes 1 to 4)
1292 Md.8
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing starting history records.
Pointer No.
Pointer No. 0
Md.3
Md.4
Start No.
Md.5
Md.6
Md.7
Each group of buffer memory addresses storing a complete starting history record is assigned a pointer No. Example: Pointer No. 0 = Buffer memory addresses 1212 to 1216 Pointer No. 1 = Buffer memory addresses 1217 to 1221 Pointer No. 2 = Buffer memory addresses 1222 to 1226
Item Buffer memory address
Pointer No. 15 = Buffer memory addresses 1287 to 1291 Each history record is assigned a pointer No. in the range between 0 and 15. If the pointer No. 15 has been assigned to a new record, the next record will be assigned the pointer number 0. (A new record replaces an older record when a pointer No. is reassigned.)


Stores a number (Axis No.) that indicates the axis that encountered an error.
Error history (Up to 16 records can be stored)
Monitor value Error No. For details on the error Nos. (Error codes),refer to Section 15.2 "List of errors".
Stores the time at which an axis error was detected.
0 b15 b12 0 1 0 1 0 1 b8 b4 b0 0 1 5 0
0 to 2 0 to 3 00 to 23 (hour)
Stores the time at which an axis error was detected.
0 b15 b12 1 0 0 1 0 0 1 0 1 1 1 b8 b4 b0 9 0 7 4
0 to 5 0 to 9 00 to 59 (minute) 00 to 59 (second) 0 to 9
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing records.

Default value Storage buffer memory address (common to axes 1 to 4)
1357 Md.13
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing error history records.
Pointer No.
Pointer No. 0
Md.9 Axis in which the error occured
Md.10
Axis error No.
Md.11 Axis error occurrence hour
Md.12
Each group of buffer memory addresses storing a complete error history record is assigned a pointer No. Example: Pointer No. 0 = Buffer memory addresses 1293 to 1296 Pointer No. 1 = Buffer memory addresses 1297 to 1300 Pointer No. 2 = Buffer memory addresses 1301 to 1304
Item Buffer memory address
Pointer No. 15 = Buffer memory addresses 1353 to 1356 Each history record is assigned a pointer No. in the range between 0 and 15. If the pointer No. 15 has been assigned to a new record, the next record will be assigned the pointer number 0. (A new record replaces an older record when a pointer No. is reassigned.)
Error history pointer · Error history

Storage item Storage details Reading the monitor value
Monitoring is carried out with a decimal display.
Md.14
Stores a number (Axis No.) that indicates the axis that encountered a warning.
Axis in which the warning occurred
Monitoring is carried out with a decimal display.
Md.15
Stores an axis warning No.
Axis warning No.
For details of warning Nos. (warning codes), refer to Section 15.3 "List of warnings".
Monitoring is carried out with a hexadecimal display.
Md.16
Buffer memory (stored with BCD code)
Stores the time at which an axis warning was detected.
Axis warning occurrence (Hour)
0 b15 b12 0 1 0 1 0 1 b8 b4 b0 0 1 5 0
0 to 2 0 to 3 00 to 23 (hour)
Md.17
Monitoring is carried out with a hexadecimal display.
Buffer memory (stored with BCD code)
Stores the time at which an axis warning was detected.
0 b15 b12 1 0 0 1 0 0 1 0 1 1 1 b8 b4 b0 9 0 7 4
0 to 5 0 to 9 00 to 59 (minute) 00 to 59 (second) 0 to 9
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing records.
Monitoring is carried out with a decimal display.
Md.18
Storage value (Pointer number)
Stores the number of write accesses to the flash ROM after the power is switched ON. The count is cleared to "0" when the number of write accesses reach 26 and an error reset operation is performed.
Md.19
Monitoring is carried out with a decimal display.
No. of write accesses to flash ROM

Default value Storage buffer memory address (common to axes 1 to 4)
1422 Md.18 Warning history pointer
Indicates a pointer No. that is next to the Pointer No. assigned to the latest of the existing warning history records.
Pointer No.
Pointer No. 0
Md.14 Axis in which the warning occured
Md.15
Axis warning No.
Md.16 Axis warning occurrence hour
Md.17
Each group of buffer memory addresses storing a complete warning history record is assigned a pointer No. Example: Pointer No. 0 = Buffer memory addresses 1358 to 1361 Pointer No. 1 = Buffer memory addresses 1362 to 1365 Pointer No. 2 = Buffer memory addresses 1366 to 1369
Item Buffer memory address
Pointer No. 15 = Buffer memory addresses 1418 to 1421 Each history record is assigned a pointer No. in the range between 0 and 15. If the pointer No. 15 has been assigned to a new record, the next record will be assigned the pointer number 0. (A new record replaces an older record when a pointer No. is reassigned.)
0 1424 1425

Storage item Storage details
The currently commanded address is stored. (Different from the actual motor position during operation) The current position address is stored. If "degree" is selected as the unit, the addresses will have a ring structure for values between 0 and 359.9999 degrees.
Md.20 Current feed value
The address of the current position according to the machine coordinates will be stored. (Different from the actual motor position during operation) Note that the current value changing function will not change the machine feed value. Under the speed control mode, the machine feed value is constantly updated always, irrespective of the parameter setting. The value will not be cleared to "0" at the beginning of fixed-feed control. Even if "degree" is selected as the unit, the addresses will not have a ring structure for values between 0 and 359.99999 degrees.
Md.21 Machine feed value
The command output speed of the operating workpiece is stored. (May be different from the actual motor speed during operation)
Md.22 Feedrate
(Set with Pr.20 )
When an axis error is detected, the error code corresponding to the error details is stored.
Md.23 Axis error No.


Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
0000H 800 801 900 901 1000 1001 1100 1101
0000H 802 803 902 903 1002 1003 1102 1103
0000H 804 805 904 905 1004 1005 1104 1105
Monitor value Error code Refer to Section 15.2 "List of errors" for details on the error Nos. (error codes).

Storage item Storage details
Whenever an axis warning is reported, a related warning code is stored.
Md.24 Axis warning No.
This area stores an M code that is currently active (i.e. set to the positioning data relating to the current operation).
Md.25 Valid M code
When the PLC READY signal (Y0) goes OFF, the value is set to "0".
Md.26 Axis operation status This area stores the axis operation status.
" Da.8 Command speed" of the positioning data currently in execution is stored.
(Stores "0" under the speed control.)
set by the positioning data used one step earlier.
Md.27 Current speed
(For details of the speed change function, refer to Section 12.5.1.)

Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
Monitoring is carried out with a decimal display.
0 807 907 1007 1107
Monitoring is carried out with a decimal display.
Monitor value M code No. (0 to 65535)
0 808 908 1008 1108
Monitoring is carried out with a decimal display.
Axis operation status -2: Step standby -1: Error 0: Standby 1: Stopped 2: Interpolation 3: JOG operation 4: Manual pulse generator operation 5: Analyzing 6: Special start standby 7: OPR 8: Position control 9: Speed control 10: Speed control in speed-position switching control 11: Position control in speed-position switching control 12: Position control in position-speed switching control 13: Speed control in position-speed switching control
0 809 909 1009 1109
Monitoring is carried out with a decimal display.
Monitor value Decimal integer value
Md.27
n Unit 0 810 811 910 911 1010 1011 1110 1111
Current speed Md.27

Storage item Storage details
Md.28 Axis feedrate
Md.29 Speed-position switching
The ON/OFF state of the external input/output signal is stored. The following items are stored.
Md.30 External input/output signal
control positioning amount


Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
0000H 812 813 912 913 1012 1013 1112 1113
0000H 814 815 914 915 1014 1015 1114 1115
0 b15 b0 b4 b8 b12

Storage item Storage details
This area stores the states (ON/OFF) of various flags. Information on the following flags is stored.
In speed control flag:
This signal that comes ON under the speed control can be used to judge whether the operation is performed under the speed control or position control. The signal goes OFF when the power is switched ON, under the position control, and during JOG operation or manual pulse generator operation. During the speed-position or position-speed switching control, this signal comes ON only when the speed control is in effect. During the speed- position switching control, this signal goes OFF when the speed-position switching signal executes a switching over from speed control to position control. During the position- speed switching control, this signal comes ON when the position-speed switching signal executes a switching over from position control to speed control. Speed-position switching latch flag:
This signal is used during the speed-position switching control (INC mode) for interlocking the movement amount change function. During the speed-position switching control (INC mode), this signal comes ON when position control takes over. This signal goes OFF when the next positioning data is processed, and during JOG operation or manual pulse generator operation. Command in-position flag:
This signal is ON when the remaining distance is equal to or less than the command in- position range (set by a detailed parameter). This signal remains OFF with data that specify the continuous path control (P11) as the operation pattern. The state of this signal is monitored every 1.8 ms except when the monitoring is canceled under the speed control or while the speed control is in effect during the speed-position or position-speed switching control. While operations are performed with interpolation, this signal comes ON only in respect of the starting axis. (This signal goes OFF in respect of all axes upon starting.) OPR request flag:
Md.31 Status
This signal comes ON when the power is switched ON, when the drive unit READY signal goes OFF, when the PLC READY signal goes ON, when a machine OPR operation starts. This signal goes OFF when a machine OPR operation completes. OPR complete flag:
This signal comes ON when a machine OPR operation completes normally. This signal goes OFF when the operation starts and when the drive unit READY signal goes OFF. Position-speed switching latch flag:
This signal is used during the position-speed switching control for interlocking the command speed change function. During the position-speed switching control, this signal comes ON when speed control takes over. This signal goes OFF when the next positioning data is processed, and during JOG operation or manual pulse generator operation. Axis warning detection flag:
This signal comes On when an axis warning is reported and goes OFF when the axis error reset signal comes ON. Speed change 0 flag:
This signal comes ON when a speed change request that specifies 0 as the new speed value is issued. This signal comes ON when a speed change request that specifies a new speed value other than 0 is issued.
This area stores the target value ( Da.6 Positioning address/movement amount)
for a positioning operation.
Md.32 Target value
address/movement amount". • At other times : Stores "0".


Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
0 b15 b0 b4 b8 b12
Not used Default value Stored items Meaning Not used
n Unit 0 818 819 918 919 1018 1019 1118 1119

Storage item Storage details
the override and speed limit value, etc., is stored. "0" is stored when positioning is completed. • During interpolation : The composite speed or reference
axis speed is stored in the reference axis address, and "0" is stored in the interpolation axis address. • During JOG operation : The actual target speed, considering
Md.33 Target speed
the JOG speed limit value for the JOG speed, is stored. • During manual pulse generator operation : "0" is stored.
Md.34 Movement amount after
The " Pr.17 Torque limit setting value" or " Cd.22 New torque value" is stored.
Md.35 Torque limit stored value
...The " Pr.17 Torque limit setting value" is stored.
...The " Cd.22 New torque value" is stored.
near-point dog ON


Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
0000H 820 821 920 921 1020 1021 1120 1121
0000H 822 823 922 923 1022 1023 1124 1125
Storage value 0 to 500 (%) Monitor value 300 826 926 1026 1126

Storage item Storage details
Md.36 Special start data instruction
The " instruction parameter" used with special start and indicated by the start data pointer currently being executed is stored.
Md.37 Special start data instruction
The stored value differs according to the value set for Md.36 .
Md.38 Start positioning data No.
Md.39 In speed limit flag
override, the speed limit functions, and the in speed limit flag turns ON.
stops, the in speed limit flag turns OFF.
Md.40 In speed change processing


Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
Storage value 1 to 600 Monitor value 0 829 929 1029 1129

Storage item Storage details
Md.41 Special start repetition
Md.42 Control system repetition
Md.43 Start data pointer being
Md.44 Positioning data No. being
Md.45 Block No. being executed
Md.46 Last executed positioning
data No.
Md.47 Positioning data being
being executed (positioning data No. given by Md.44 ).
Md.48 Deceleration start flag


Storage buffer memory address Reading the monitor value Default
value Axis 1 Axis 2 Axis 3 Axis 4
Storage value 0 to 255 0 832 932 1032 1132
Storage value 0 to FFFF 0000H 833 933 1033 1133
Storage value 1 to 600 0 835 935 1035 1135
Storage value 1 to 600 0 837 937 1037 1137

Setting item Setting details
Cd.1 Flash ROM write request • Requests writing of data (parameters, positioning data, and block start data) from the buffer memory to the flash ROM.
the PLC power.
Cd.2 Parameter initialization request
Parameters ( Pr.1 to Pr.57 , Pr.150 )
Positioning data (No. 1 to No. 600)
Block start data (No. 7000 to 7004)
Cd.41 Deceleration start flag valid Set whether " Md.48 Deceleration start flag" is made valid or invalid.
Cd.42 Stop command processing for
Initialized setting data · deceleration stop selection


Flash ROM write request 1: Requests write access to flash ROM.
The QD75 resets the value to "0" automatically when the write access completes. (This indicates the completion of write operation.)
The QD75 resets the value to "0" automatically when the initialization completes.
Stop command processing for deceleration stop selection 0: Deceleration curve re-processing 1: Deceleration curve continuation

Setting item Setting details
Cd.3 Positioning start No.
Cd.4 Positioning starting point No. • Set a " starting point No." (1 to 50) if block start data is used for positioning. (Handled as "1" if the value of other than 1 to 50 is set.)
Cd.5 Axis error reset
Cd.6 Restart command
"stopped"), set "1" in Cd.6 . Positioning will be carried out again from the stopped
position to the end point of the stopped positioning data.
Cd.7 M code OFF request • The M code ON signal turns OFF.

Storage buffer memory address Setting value Default
value Axis 1 Axis 2 Axis 3 Axis 4
Set with a decimal.
0 1500 1600 1700 1800
Positioning data No.
1 to 600 7000 to7004 9001 9002 9003 9004
: Positioning data No. : Block start designation : Machine OPR : Fast-OPR : Current value changing : Simultaneous starting of multiple axes
Set with a decimal.
Positioning starting point No.
0 1501 1601 1701 1801
The value is set to "0" by the QD75 automatically when the continuous operation is interrupted.
Set with a decimal.
0 1502 1602 1702 1802
After the axis error reset is completed, "0" is stored by the QD75 automatically. (Indicates that the axis error reset is completed.)
Set with a decimal.
0 1503 1603 1703 1803
After restart acceptance is completed, "0" is stored by the QD75 automatically. (Indicates that the restart acceptance is completed.)
Set with a decimal.
M code OFF request
0 1504 1604 1704 1804
After the M code ON signal turns OFF, "0" is stored by the QD75 automatically. (Indicates that the OFF request is completed.)

Setting item Setting details
Cd.8 External command valid • Validates or in validates external command signals.
Pr.1 mm (×10-1 µm)
inch (×10-5 inch)
degree (×10-5 degree)
Cd.9 New current value
0 to 35999999 -2147483648


value Axis 1 Axis 2 Axis 3 Axis 4
External command valid 0: Invalidates an external command. 1: Validates an external command.
0 1506 1507 1606 1607 1706 1707 1806 1807

Setting item Setting details
Cd.10 New acceleration time value
Cd.10 setting range (unit)
0 to 8388608 (ms)
Cd.11 New deceleration time value
Cd.11 setting range (unit)
0 to 8388608 (ms)
Cd.12 Acceleration/deceleration time
change during speed change, enable/disable selection


value Axis 1 Axis 2 Axis 3 Axis 4
0 1508 1509 1608 1609 1708 1709 1808 1809 Set with a decimal.
0 1510 1511 1610 1611 1710 1711 1810 1811
Acceleration/deceleration time change during speed change, enable/disable selection 1 : Enables modifications to acceleration/deceleration time Other than 1: Disables modifications to acceleration/deceleration time

Setting item Setting details
For details of the override function, refer to Section 12.5.2" Override function".
Cd.13 Positioning operation speed
If the speed resulting from a small override value (e.g. 1%) includes fractions below the minimum unit, the speed is raised to make a complete unit and the warning No. 110 is output.
Cd.14 New speed value
Pr.1 mm (×10-2 mm/min)
inch (×10-3 inch/min)
degree (×10-3 degree/min)
Setting range 0 to 2000000000 0 to 2000000000 0 to 2000000000 0 to 1000000
Cd.15 Speed change request
override · pulse (pulse/s)


value Axis 1 Axis 2 Axis 3 Axis 4
0 1514 1515 1614 1615 1714 1715 1814 1815
value" is set as "20000.00mm /min", the buffer memory stores "2000000".
The QD75 resets the value to "0" automatically when the speed change request has been processed. (This indicates the completion of speed change request.)


Setting range 0 to 65535 0 to 65535 0 to 65535 0 to 65535
Setting range 0 to 2000000000 0 to 2000000000 0 to 2000000000 0 to 1000000


value Axis 1 Axis 2 Axis 3 Axis 4
Example: When the " Cd. 16 Inching movement amount" is set as "1.0 m", the buffer memory stores "10".
0 1518 1519 1618 1619 1718 1719 1818 1819
speed" is set as "20000.00mm /min", the buffer memory stores "2000000".
Interruption request continuous operation 1: Interrupts continuous operation control or continuous path control.
The QD75 resets the value to "0" automatically when the continuous control interruption request is processed. (This indicates the completion of continuous operation interruption request.)

Setting item Setting details
Cd.19 OPR request flag OFF
Cd.20 Manual pulse generator 1
Cd.21 Manual pulse generator
Cd.22 New torque value
request · pulse input magnification · enable flag


value Axis 1 Axis 2 Axis 3 Axis 4
OPR request flag OFF request 1: Turns the "OPR request flag" from ON to OFF.
The QD75 resets the value to "0" automatically when the OPR request flag is turned OFF. (This indicates the completion of OPR request flag OFF request.)
1 1522 1523 1622 1623 1722 1723 1822 1823
Manual pulse generator enable flag 0: Disable manual pulse generator operation. 1: Enable manual pulse generator operation.
1 to Pr.17 Torque limit setting value 0 1525 1625 1725 1825

Setting item Setting details
Cd.23 Speed-position switching
control movement amount change register
Pr.1 mm (×10-1 µm)
inch (×10-5 inch)
degree (×10-5 degree)
Setting range 0 to 2147483647 0 to 2147483647 0 to 2147483647 0 to 2147483647
Cd.24 Speed-position switching
Cd.25 Position-speed switching
control speed change register
Pr.1 mm (×10-2 mm/min)
inch (×10-3 inch/min)
degree (×10-3 degree/min)
Setting range 0 to 2000000000 0 to 2000000000 0 to 2000000000 0 to 1000000
pulse (pulse) · enable flag · pulse (pulse/s)


value Axis 1 Axis 2 Axis 3 Axis 4
0 1526 1527 1626 1627 1726 1727 1826 1827
Example: If " Cd. 23 Speed-position switching control movement amount change register" is set as "20000.0 m", the buffer memory stores "200000".
Speed-position switching enable flag 0: Speed control will not be taken over by position control even when the external command signal comes ON. 1: Speed control will be taken over by position control when the external command signal comes ON.
0 1530 1531 1630 1631 1730 1731 1830 1831
Example: If " Cd. 25 Position-speed switching control speed change register" is set as "2000.00 mm/min", the buffer memory stores "200000".

Setting item Setting details
Cd.26 Position-speed switching
Pr.1 mm (×10-1 µm)
inch (×10-5 inch)
degree (×10-5 degree)
Cd.27 Target position change value
0 to 35999999 -2147483648
INC
Cd.28 Target position change value
Pr.1 mm (×10-2 mm/min)
inch (×10-3 inch/min)
degree (×10-3 degree/min)
Setting range 0 to 2000000000 0 to 2000000000 0 to 2000000000 0 to 1000000
Cd.29 Target position change

Storage buffer memory address Setting value Default
value Axis 1 Axis 2 Axis 3 Axis 4
Set with a decimal.
Position-speed switching enable flag 0: Position control will not be taken over by speed control even when the external command signal comes ON. 1: Position control will be taken over by speed control when the external command signal comes ON.
0 1532 1632 1732 1832
Set with a decimal.
Cd. 27 Target position change value (address) Cd. 28 Target position change value (speed)
0 1534 1535 1634 1635 1734 1735 1834 1835
Conversion into an integer value
Unit conversion table ( Cd.27 )
Unit conversion table ( Cd.28 )
Example: If " Cd. 28 Target position change value (speed) is set as "10000.00 mm/min", the buffer memory stores "1000000". 0 1536 1537 1636 1637 1736 1737 1836 1837
Set with a decimal.
Target position change request flag 1: Requests a change in the target position
0 1538 1638 1738 1838
The QD75 resets the value to "0" automatically when the new target position value has been written. (This indicates the completion of write operation.)

Setting item Setting details
Cd.30 Simultaneous starting axis
start data No. (axis 1 start data No.)
Cd.31 Simultaneous starting axis
start data No. (axis 2 start data No.)
Cd.32 Simultaneous starting axis
start data No. (axis 3 start data No.)
Cd.33 Simultaneous starting axis
start data No. (axis 4 start data No.)
Cd.34 Step mode
Cd.35 Step valid flag • This data item validates or invalidates step operations.


value Axis 1 Axis 2 Axis 3 Axis 4

Setting item Setting details
Cd.36 Step start information
Cd.37 Skip command • To skip the current positioning operation, set "1" in this data item.
Cd.38 Teaching data selection • This data item specifies the teaching result write destination.
Cd.39 Teaching positioning data No.
Cd.40 ABS direction in degrees


value Axis 1 Axis 2 Axis 3 Axis 4
The QD75 resets the value to "0" automatically when processing of the step start request completes.
Issues a skip request to have the machine decelerate, stop, and then start the next positioning operation.
The QD75 resets the value to "0" automatically when processing of the skip request completes.

MEMO

Positioning Control
The programs required to carry out positioning control with the QD75 are explained in this chapter.
The sequence program required for control is created allowing for the "start conditions", "start time chart", "device settings" and general control configuration. (The parameters, positioning data, block start data and condition data, etc., must be set in the QD75 according to the control to be executed, and program for setting the control data or a program for starting the various control must be created.)
The first half of this chapter explains the program configuration of general control, and the latter half explains the program details. Create the required program while referring to the various control details explained in Section 2, and to Chapter 5 "Data used for positioning control".
6.1 Precautions for creating program 6- 2 6.2 List of devices used 6- 5 6.3 Creating a program 6- 11 6.3.1 General configuration of program 6- 11 6.3.2 Positioning control operation program 6- 12 6.4 Positioning program examples 6- 15 6.5 Program details 6- 24 6.5.1 Initialization program 6- 24 6.5.2 Start details setting program 6- 25 6.5.3 Start program 6- 27 6.5.4 Continuous operation interrupt program 6- 37 6.5.5 Restart program 6- 39 6.5.6 Stop program 6- 42

The common precautions to be taken when writing data from the PLC CPU to the QD75 buffer memory are described below. When diverting any of the program examples introduced in this manual to the actual system, fully verify that there are no problems in the controllability of the target system.
Setting the data explained in this chapter (various parameters, positioning data, block start data) should be set using GX Configurator-QP. When set with the sequence program, many sequence programs and devices must be used. This will not only complicate the program, but will also increase the scan time. When rewriting the positioning data during continuous path control or continuous positioning control, rewrite the data four positioning data items before the actual execution. If the positioning data is not rewritten before the positioning data four items earlier is executed, the process will be carried out as if the data was not rewritten.
Provide an interval of 100ms or more when changing the speed with the QD75.
Overrun is prevented by the setting of the upper and lower stroke limits with the detail parameter 1. However, this applies only when the QD75 is operating correctly. It is recommended to create an external circuit including a boundary limit switch to ensure the whole system safety as follows: the external circuit powers OFF the motor when the boundary limit switch operates.

Unless particularly designated, the sequence program for the following system is shown in this chapter and subsequent. Refer to Section 6.2 for the application of the devices to be used.

Y50 to Y52 (for absolute position restoration) CH.1 output (for torque changing)
In the program, the unit of "0 (mm)" is set for the basic parameter 1.
There are two methods for communication with QD75 using the sequence program: a method using an "intelligent function device" and a method using a FROM/TO command. In the sequence program in this chapter and subsequent, the program example using the "intelligent function device" is shown without using an FROM/TO command for communication with QD75. When using the FROM/TO command for communication with QD75, change the circuit incorporating the "intelligent function device" as follows. (a) When the circuit uses the "intelligent function device" on the destination (D)
side of a MOV command, change the command to a TO command.

Number of write data (1)

(b) When the circuit uses the "intelligent function device" on the source(s) side
and the destination (D) side of a MOV command, change the command to a FROM command and a TO command.

Set the same device.
(c) When the circuit uses the "intelligent function device" for a COMPARISON
command, change the command to a FROM command and a COMPARISON command.

(d) When the circuit uses the "intelligent function device" for a WAND command,
change the command to a FROM command and a WAND command.

Refer to QCPU (Q mode) User's Manual (Functions and Programs Basic Part) for the intelligent function devices. Refer to QCPU (Q mode) Programming Manual (Common Commands Part) for detail commands used in those programs shown in this chapter and subsequent.
Data read out

In the sequence programs shown in this chapter and subsequent, the application of the devices used are as follows. The I/O numbers for QD75 indicate those when QD75 is mounted in the 0-slot of the main base. If it is mounted in the slot other than the 0-slot of the main base, change the I/O number to that for the position where QD75 was installed. In addition, change the external inputs, external outputs, internal relays, data resisters, and timers according to the system used.
of QD75

name Axis 1 Axis 2 Axis 3 Axis 4 Application Details when ON
X4 X5 X6 X7 M code ON signal M code outputting
X8 X9 XA XB Error detection signal Error detected
X10 X11 X12 X13 Start complete signal Start completed
X14 X15 X16 X17 Positioning complete signal Positioning completed
Y4 Y5 Y6 Y7 Axis stop signal Requesting stop
Y8 YA YC YE Forward run JOG start signal Starting forward run JOG
Y9 YB YD YF Reverse run JOG start signal Starting reverse run JOG
Y10 Y11 Y12 Y13 Positioning start signal Requesting start
X20 OPR request OFF command Commanding OPR request OFF
X21 External command valid command Commanding external command valid setting
X22 External command invalid command Commanding external command invalid
X29 Movement amount change command Commanding movement amount change


name Axis 1 Axis 2 Axis 3 Axis 4 Application Details when ON
X2C M code OFF command Commanding M code OFF
X2E Forward run JOG/inching command Commanding forward run JOG/inching operation
X2F Reverse run JOG/inching command Commanding reverse run JOG/inching operation
X3D Flash ROM write command Commanding flash ROM write
X45 Target position change command Target position change command
Positioning start command (Y start) Positioning start command being given


name Axis 1 Axis 2 Axis 3 Axis 4 Application Details when ON
M0 OPR request OFF command Commanding OPR request OFF
M1 OPR request OFF command pulse OPR request OFF commanded
M2 OPR request OFF command storage OPR request OFF command held
M4 Fast OPR command storage Fast OPR command held
M6 Positioning start command storage Positioning start command held
M9 Manual pulse generator operating flag Manual pulse generator operating flag
M12 Speed change command storage Speed change command held
M25 Parameter initialization command storage Parameter initialization command held
M26 Flash ROM write command pulse Flash ROM write commanded
M27 Flash ROM write command storage Flash ROM write command held
M30 Target position change command pulse Target position change commanded
M31 Target position change command storage Target position change command held
PSTRT1 instruction error complete device PSTRT1 instruction error completed


name Axis 1 Axis 2 Axis 3 Axis 4 Application Details when ON
M35 TEACH1 instruction error complete device TEACH1 instruction error completed
M37 PINIT instruction error complete device PINIT instruction error completed
M39 PFWRT instruction error complete device PFWRT instruction error completed
M43 ABRST instruction error complete device ABRST instruction error completed
Basic parameter 1 setting complete device Basic parameter 1 setting completed

name Axis 1 Axis 2 Axis 3 Axis 4 Application Details of storage
D0 OPR request flag ( Md.31 Status (bit 3))
D5 Inching movement amount ( Cd.16 Inching movement amount)
D8 Manual pulse generator 1 pulse input magnification (low-order)
( Cd.20 Manual pulse generator 1 pulse input magnification)
D9 Manual pulse generator 1 pulse input magnification (high-order)
D12 Speed change value (high-order 16 bits) ( Cd.14 New speed value)
D13 Speed change request ( Cd.15 Speed change request)


name Axis 1 Axis 2 Axis 3 Axis 4 Application Details of storage
( Cd.12 Acceleration/deceleration time change enable/disable selection in speed change)
D20 Step valid flag ( Cd.35 step valid flag)
D27 Target position change request ( Cd.29 New target position change
D49 Error code Error code at absolute position restoration
No. of pulses per rotation ( Pr.2 No. of pulses per rotation)


name Axis 1 Axis 2 Axis 3 Axis 4 Application Details of storage
D52 Movement amount per rotation ( Pr.3 Movement amount per
D54 Pulse output mode ( Pr.5 Pulse output mode)
D55 Rotation direction setting ( Pr.6 Rotation direction setting)
T0 PLC READY signal OFF confirmation Timer T1 — PLC READY signal OFF confirmation PLC READY signal OFF

The "positioning control operation program" actually used is explained in this chapter. The functions and programs explained in Section 2 are assembled into the "positioning control operation program" explained here. (To monitor the control, add the required monitor program that matches the system. Refer to Section 5.6 "List of monitor data" for details on the monitor items.)
The general configuration of the "positioning control operation program" is shown below.

Program required to carry out "OPR control", "major positioning control" and "high-level positioning control"

The various programs that configure the "positioning control operation program" are shown below. When creating the program, refer to the explanation of each program and Section 6.4 "Positioning program examples", and create an operation program that matches the positioning system. (Numbers are assigned to the following programs. Configuring the program in the order of these numbers is recommended.)

control", the OPR parameters do not need to be set.
Continued on next page

Continued from previous page

Program required to carry out
Program to reset the start signal and turn the M code ON signal OFF
Program required to carry out "manual control"
Continued on next page

Continued from previous page

Program added according to control details. (Create as required.)
Program used to stop control

An example of the "Axis 1" positioning program is given in this section.
[No. 1] to [No. 3] parameter and data setting program When setting the parameters or data with the sequence program, set them in the QD75 using the TO command from the PLC CPU. (Carry out the settings while the PLC READY signal [Y1D] is OFF.) When setting the parameters or data with GX Configurator-QP, the [No. 1] to [No. 3] program is not necessary.


Parameter setting program for speed-position switching control (ABS mode)
(Not needed when speed-position switching control (ABS mode) is not executed)

(For positioning data No. 1 ) No. 2 Positioning data setting program
Operation pattern: Positioning complete Control system: 1-axis linear control (ABS) Acceleration time No.: 1, deceleration time No.: 2

Block start data of start block 0 (axis 1) No. 3 Block start data setting program
For setting of points 1 to 5
Shape: Continued at points 1 to 4, ended at point 5 Special start instruction: Normal start at all of points 1 to 5
[Setting of shape and start data No.]

· · (Conditions)

[Setting of special start instruction to normal start]

No. 4 OPR request OFF program
No. 5 External command function valid setting program

No. 6 PLC READY signal [Y0] ON program
(M50 contact not required for synchronous mode.)

No. 7 Positioning start No. setting program


(3) Positioning with positioning data No. 1
(1) Machine OPR · (2) Fast OPR

(4) Speed-position switching operation (positioning data No. 2)
(In the ABS mode, new movement amount write is not needed.)

(5) Position-speed switching operation positioning data No. 3

(6) High-level positioning control

(7) Fast OPR command and fast OPR command storage OFF
(Not required when fast OPR is not used)

(1) When dedicated instruction (PSTRT1) is used No. 8 Positioning start program
(When fast OPR is not made, contacts of M3 and M4 are not needed.) (When M code is not used, contact of X04 is not needed.) (When JOG operation/inching operation is not performed, contact of M7 is not needed.) (When manual pulse generator operation is not performed, contact of M9 is not needed.)


·

(2) When positioning start signal (Y10) is used
(When fast OPR is not made, contacts of M3 and M4 are not needed.) (When M code is not used, contact of X04 is not needed.) (When JOG operation/inching operation is not performed, contact of M7 is not needed.) (When manual pulse generator operation is not performed, contact of M9 is not needed.)

No. 9 M code OFF program
(Not required when M code is not used)

No. 10 JOG operation setting program

No. 11 Inching operation setting program

No. 12 JOG operation/inching operation execution program

·

No. 13 Manual pulse generator operation program

No. 14 Speed change program

No. 15 Override program

No. 16 Acceleration/deceleration time change program




No. 23 Absolute position restoration program
(1) Absolute position restoration command acceptance

(2) Setting of transmit data to servo-amplifier and confirmation of absolute position restoration completion
ABRST1 instruction completed when M42 is ON and M43 is OFF. Absolute position data restoration completed when status = 0.

(3) ABS data setting and ABRST1 instruction execution

No. 24 Restart program

No. 25 Parameter initialization program



No. 26 Flash ROM write program

No. 27 Error reset program

No. 28 Stop program

![Page 244 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] External command function valid setting program](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-244.webp?w=400)
6.5.1 Initialization program
[1] OPR request OFF program
This program forcibly turns OFF the "OPR request flag" ( Md.31 Status : b3)
which is ON. When using a system that does not require OPR, assemble the program to cancel the "OPR request" made by the QD75 when the power is turned ON, etc.
Set the following data to use the OPR request flag OFF request.

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Cd.19 OPR request flag OFF request 1 Set to "1: Turn OPR request flag OFF". 1521 1621 1721 1821
Refer to Section 5.7 "List of control data" for details on the setting details.

Fig. 6.1 Time chart for OPR OFF request
This program is used to validate the "external command signal" beforehand when using the external command functions (external start, speed change, speed- position switching, position-speed switching, skip). (Set which function to use
beforehand in " Pr.42 External command function selection".)
Set the following data to validate the "external command signal".
![Mitsubishi Electronics MELSEC-Q QD75D — [2] External command function valid setting program diagram (page 244)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-244-3.webp)
value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Cd.8 External command valid 1 Set to "1: Validate external command". 1505 1605 1705 1805
Refer to Section 5.7 "List of control data" for details on the setting details.

This program sets which control, out of "OPR", "major positioning control" or "high-level positioning control" to execute. For " high-level positioning control", "fast OPR", "speed- position switching control" and "position-speed switching control", add the respectively required sequence program. (Refer to Chapter 10 for details on starting the " high-level positioning control.)
(1) Set the "positioning start No." corresponding to the control to be started in

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
1 to 600 : Positioning data No. 9001 : Machine OPR 9002 : Fast OPR 9003 : Current value changing 9004 : Simultaneous start 7000 to 7004 : Block No. (For "high-level positioning control")
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) For " high-level positioning control", set the "positioning start point No." of the
block to be started in " Cd.4 Positioning start point No.".

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Cd.4 Positioning start point No. 1 to 50 : Point No. of block start data 1501 1601 1701 1801
Refer to Section 5.7 "List of control data" for details on the setting details.
(3) Set the following control data for "speed-position switching control (INC
mode)". (Set " Cd.23 Speed-position switching control movement amount change
register as required". Setting is not required in the ABS mode.)

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Set the new value when the position control's movement amount is to be changed during speed control.
Cd.24 Speed-position switching enable flag 1 When "1" is set, the speed-position switching signal will be validated. 1528 1628 1728 1828
Refer to Section 5.7 "List of control data" for details on the setting details.

(4) For "position-speed switching control", set the control data shown below.
(As required, set the " Cd.25 Position-speed switching control speed change
resister".)
Buffer memory address Setting item Setting
value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Position-speed switching control speed change resister
Used to set a new value when speed is changed during positioning control.
1530 1531 1630 1631 1730 1731 1830 1831
Cd.25
Cd.26 Position-speed switching enable flag 1 To validate position-speed switching signal, this is set to 1. 1532 1632 1732 1832
Refer to Section 5.7 "List of control data" for details on the setting details.

This program is used to start the control with start commands. The control can be started with the following two methods.
[1] Starting by inputting positioning start signal [Y10, Y11, Y12, Y13] [2] Starting by inputting external command signal

When starting positioning with the scan after the completion of positioning, insert X10 as an interlock so that positioning is started after Y10 is turned OFF and X10 is turned OFF.
Fig. 6.2 Procedures for starting control (for axis 1)

To start the control, the following conditions must be satisfied. The necessary start conditions must be incorporated in the sequence program so that the control is not started when the conditions are not satisfied.

PLC READY signal ON PLC CPU preparation completed Y0
Axis stop signal OFF Axis stop signal is OFF. Y4 Y5 Y6 Y7
M code ON signal OFF M code ON signal is OFF. X4 X5 X6 X7
Error detection signal OFF No error is present. X8 X9 XA XB
BUSY signal OFF BUSY signal is OFF. XC XD XE XF
Start complete signal OFF Start complete signal is OFF. X10 X11 X12 X13
Drive unit READY signal ON Drive unit preparation completed –
Upper limit (FLS) ON Within limit range – External signal
: When the synchronous setting of the PLC CPU is made in the nonsynchronous mode, this must be
provided as an interlock. When it is made in the synchronous mode, no interlock must be provided in the program because the flag is turned ON when calculation is run on the PLC CPU.
![Page 249 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Starting by inputting positioning start signal](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-249.webp?w=400)
Operation when starting
(1) When the positioning start signal turns ON, the start complete signal and
BUSY signal turn ON, and the positioning operation starts. It can be seen that the axis is operating when the BUSY signal is ON. (2) When the positioning start signal turns OFF, the start complete signal also
turns OFF. If the positioning start signal is ON even after positioning is completed, the start complete signal will remain ON. (3) If the positioning start signal turns ON again while the BUSY signal is ON, the
(a) and (b) below.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Starting by inputting positioning start signal diagram (page 249)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-249-1.webp)
Fig. 6.3 ON/OFF timing of each signal at start of positioning
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Starting by inputting positioning start signal diagram (page 249)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-249-2.webp)
The BUSY signal [XC, XD, XE, XF] turns ON even when position control of movement amount 0 is executed. However, since the ON time is short, the ON status may not be detected in the sequence program. (The ON status of the start complete signal [X10, X11, X12, X13], positioning complete signal [X14, X15, X16, X17] and M code ON signal [X4, X5, X6, X7] can be detected in the sequence program.)

The time chart for starting each control is shown below.
(1) Time chart for starting "machine OPR"

Fig. 6.4 Time chart for starting "machine OPR"

(2) Time chart for starting "fast OPR"

Fig. 6.5 Time chart for starting "fast OPR"

(3) Time chart for starting "major positioning control"

Fig. 6.6 Time chart for starting "major positioning control"
(4) Time chart for starting "speed-position switching control"

Fig. 6.7 Time chart for starting "speed-position switching control"

(5) Time chart for starting "position-speed switching control"

Fig. 6.8 Time chart for starting "position-speed switching control"


Fig. 6.9 Machine OPR operation timing and process time
t1 t2 t3 t4
1.0 to 1.4 2.7 to 4.4 0 to 1.8 0 to 1.8


M code ON signal (WITH mode) [X4, X5, X6, X7]
Fig. 6.10 Position control operation timing and process time
t1 t2 t3 t4 t5 t6
1.2 to 2.3 0 to 1.8 0 to 1.8 2.7 to 4.4 0 to 1.8 Follows parameters

When starting positioning control by inputting the external command signal, the start command can be directly input into the QD75. This allows the variation time equivalent to one scan time of the PLC CPU to be eliminated. This is an effective procedure when operation is to be started as quickly as possible with the start command or when the starting variation time is to be suppressed. To start positioning control by inputting the external command signal, set the "data required to be set" and then turn ON the external command signal.
When starting by inputting the external command signal, the start complete signal [X10, X11, X12, X13] will not turn ON.
To execute positioning start with the external command signal, set parameter ( Pr.42 ) beforehand, and validate the "external command signal" with the
"external command signal validity setting program (program No. 5).

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Pr.42 External command function selection 0 Set to "0: External positioning start". 62 212 362 512
Cd.8 External command valid 1 Set to "1: Validate external command". 1505 1605 1705 1805
Refer to Chapter 5 "Data Used for Positioning Control" for details on the setting details.

Fig. 6.11 Time chart for starting with external start signal
![Page 257 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Restrictions](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-257.webp?w=400)
During positioning control, the control can be interrupted during continuous positioning control and continuous path control (continuous operation interrupt function). When "continuous operation interruption" is execution, the control will stop when the operation of the positioning data being executed ends. To execute continuous operation interruption, set "1: Continuous operation interrupt request" for " Cd.18
Interrupt request during continuous operation".
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Operation during continuous operation interruption diagram (page 257)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-257-1.webp)
Positioning data No. 10 Positioning data No. 11 Positioning data No. 12
Fig. 6.12 Operation during continuous operation interruption
(1) When the "continuous operation interrupt request" is executed, the positioning
will end. Thus, after stopping, the operation cannot be "restarted". When " Cd.6 Restart command" is issued, a warning "Restart not possible"
(warning code: 104) will occur. (2) Even if the stop command is turned ON after executing the "continuous
operation interrupt request", the "continuous operation interrupt request" cannot be canceled. Thus, if "restart" is executed after stopping by turning the stop command ON, the operation will stop when the positioning data No. where "continuous operation interrupt request" was executed is completed.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Restrictions diagram (page 257)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-257-2.webp)
Positioning for positioning data No. 12 is not executed
Axis 1
![Page 258 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Control data requiring settings](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-258.webp?w=400)
(3) If the operation cannot be decelerated to a stop because the remaining
distance is insufficient when "continuous operation interrupt request" is executed with continuous path control, the interruption of the continuous operation will be postponed until the positioning data shown below.
Even when the continuous operation interrupt is requested, the remaining distance is insufficient, and thus, the operation cannot stop at the positioning No. being executed.

Stop process when operation cannot stop at positioning data No. 10
Positioninig data No. 10 Positioning data No. 11 Positioning data No. 12
(4) When operation is not performed (BUSY signal [XC, XD, XE, XF] is OFF), the
interrupt request during continuous operation is not accepted. It is cleared to 0 at a start or restart.
Set the following data to interrupt continuous operation.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Control data requiring settings diagram (page 258)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-258-2.webp)
value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Cd.18 Interrupt request during continuous operation 1 Set "1: Interrupt request during continuous operation". 1520 1620 1720 1820
Refer to Section 5.7 "List of control data" for details on the setting details.
Start · t
![Page 259 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Restrictions](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-259.webp?w=400)
When a stop factor occurs during position control and the operation stops, the positioning can be restarted from the stopped position to the position control end point by using the "restart command" ( Cd.6 Restart command).
("Restarting" is not possible when "continuous operation is interrupted.")
Positioning with positioning data No. 11
Positioning data No. 11 continues with restart command
Positioning with positioning data No. 12
Stop with stop command
Positioning with positioning data No. 10
Fig. 6.13 Restart operation
(1) Restarting can be executed only when the " Md.26 Axis operation status" is
"stopped". If the axis operation is not "stopped", restarting is not possible. (2) Do not execute restart while the stop command is ON.
If restart is executed while stopped, an error "Stop signal ON at start" (error code: 106) will occur, and the " Md.26 Axis operation status" will change to
"error occurring". Thus, even if the error is reset, the operation cannot be restarted. (3) Restarting can be executed even while the positioning start signal is ON.
However, make sure that the positioning start signal does not change from OFF to ON while stopped. If the positioning start signal changes from OFF to ON, positioning will start from the positioning data No. of designated point's positioning data No. set in " Cd.3 Positioning start No.". (4) If positioning is ended with the continuous operation interrupt request, the
operation cannot be restarted. If restart is requested, a warning "Restart not possible" (warning code: 104) will occur. (5) When stopped with interpolation operation, write "1: Restarts" into
" Cd.6 Restart command" for the reference axis, and then restart.
(6) If the " Md.26 Axis operation status" is not "stopped" when restarting, a
Axis 1 · Axis 2
![Page 260 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Starting conditions](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-260.webp?w=400)
Set the following data to execute restart.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Control data requiring setting diagram (page 260)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-260-1.webp)
value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Cd.6 Restart command 1 Set "1: Restarts". 1503 1603 1703 1803
Refer to Section 5.7 "List of control data" for details on the setting details.
The following conditions must be satisfied when restarting. (Assemble the required conditions into the sequence program as an interlock.)
" Md.26 Axis operation status" is "1: Stopped"
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Starting conditions diagram (page 260)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-260-2.webp)
PLC READY signal ON PLC CPU preparation completed Y0
Axis stop signal OFF Axis stop signal is OFF Y4 Y5 Y6 Y7
M code ON signal OFF M code ON signal is OFF X4 X5 X6 X7
Error detection signal OFF No error is present X8 X9 XA XB
BUSY signal OFF BUSY signal is OFF XC XD XE XF
Start complete signal OFF Start complete signal is OFF X10 X11 X12 X13
Drive unit READY signal ON Drive unit preparation completed –
Upper limit (FLS) ON Within limit range – External signal
: When the synchronous setting of the PLC CPU is made in the nonsynchronous mode, this must be
provided as an interlock. When it is made in the synchronous mode, no interlock must be provided in the program because the flag is turned ON when calculation is run on the PLC CPU.
(1) Operation state · (2) Signal state


Fig. 6.14 Time chart for restarting
![Page 262 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Stop process](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-262.webp?w=400)
The axis stop signal [Y4, Y5, Y6, Y7] or a stop signal from an external source is used to stop the control. Create a program to turn ON the axis stop signal [Y4, Y5, Y6, Y7] as the stop program.
The process for stopping control is explained below. Each control is stopped in the following cases.
(1) When each control is completed normally. (2) When the drive unit READY signal is turned OFF. (3) When a PLC CPU error occurs (4) When the PLC READY signal is turned OFF. (5) When an error occurs in QD75. (6) When control is intentionally stopped
(Stop signal from PLC CPU turned ON, stop signal from peripheral devices)
The stop process for the above cases is shown below. (Excluding item (1) above "When each control is completed normally".)
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Stop process diagram (page 262)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-262-1.webp)
(Select with " Pr.37 Sudden stop group 1 sudden stop
(Select with " Pr.38 Sudden stop group 2 sudden stop
Axis error detection (Error other than stop group 1 or 2)
Relatively safe stop (Stop group 3) "Stop" input from peripheral device
(Select with " Pr.39 Sudden stop group 3 sudden stop
"Stop signal" ON from external source Intentional stop (Stop group 3) "Axis stop signal" ON from PLC CPU

The operation can be stopped with deceleration stop, sudden stop or immediate stop.
(1) Deceleration stop 1
The operation stops with "deceleration time 0 to 3" ( Pr.10 , Pr.28 , Pr.29 ,
Pr.30 ).
Which time from "deceleration time 0 to 3" to use for control is set in positioning data ( Da.4 ).
The operation stops with " Pr.36 Sudden stop deceleration time".
The operation does not decelerate. The QD75 immediately stops the pulse output, but the operation will coast for the droop pulses accumulated in the drive unit's deviation counter.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Types of stop processes diagram (page 263)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-263-1.webp)
Coast for the droop pulses accumulated in the drive unit's deviation counter.
Fig. 6.15 Types of stop processes
1 "Deceleration stop" and "sudden stop" are selected with the details parameter 2 "stop group 1 to 3 sudden stop selection". (The default setting is "deceleration stop".)
(2) Sudden stop · (3) Immediate stop
![Page 264 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Order of priority for stop process](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-264.webp?w=400)
The order of priority for the QD75 stop process is as follows.
Deceleration stop < Sudden stop < Immediate stop
(1) If the deceleration stop command ON (stop signal ON) or deceleration stop
cause occurs during deceleration to speed 0 (including automatic
deceleration), operation changes depending on the setting of " Cd.42
command processing for deceleration stop selection". (a) Manual control
Independently of the Cd.42
setting, a deceleration curve is re-processed
from the speed at stop cause occurrence. (b) OPR control, positioning control
= 0 (deceleration curve re-processing):
A deceleration curve is re-processed from the speed at stop cause occurrence.
= 1 (deceleration curve continuation):
The current deceleration curve is continued after stop cause occurrence. (For details, refer to "Section 12.7.10 Stop command processing for deceleration stop function".)
(2) If the stop signal ON or stop cause specified for a sudden stop occurs during
deceleration, sudden stop process will start at that point. However, if the sudden stop deceleration time is longer than the deceleration time, the deceleration stop process will be continued even if a sudden stop cause occurs during the deceleration stop process.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Order of priority for stop process diagram (page 264)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-264-1.webp)
The process when a sudden stop cause occurs during deceleration stop is shown below.
Sudden stop deceleration process Deceleration stop process continues Process for sudden stop
(3) Operation will stop immediately if the target reaches the positioning address
specified in the currently executed positioning data during deceleration of position control.
Stop

Process
The QD75 memory configuration and data transmission are explained in this chapter.
The QD75 is configured of two memories. By understanding the configuration and roles of two memories, the QD75 internal data transmission process, such as "when the power is turned ON" or "when the PLC READY signal changes from OFF to ON" can be easily understood. This also allows the transmission process to be carried out correctly when saving or changing the data.
7.1 Configuration and roles of QD75 memory 7- 2 7.1.1 Configuration and roles of QD75 memory 7- 2 7.1.2 Buffer memory area configuration 7- 5 7.2 Data transmission process 7- 6

7.1.1 Configuration and roles of QD75 memory
The QD75 is configured of the following two memories.

: Setting and storage area provided, Not possible: Data is lost when power is turned OFF – : Setting and storage area not provided, Possible: Data is held even when power is turned OFF

(Set the items indicated with Pr.1 to Pr.57 , Pr.150 for each axis.)
stored. (Set the items indicated with Cd.1 to Cd.42
.)
(Set the items indicated with Da.1 to Da.10 for each positioning data.)
high-level positioning is set and stored. (Set the items indicated with Da.11 to
Da.19 .)

User accesses here.
Data is backed up here.
(No.1 to 600)
(No.1 to 600)
Block start data area
Block start data area
(No.7000 to 7004)
(No. 7000 to 7004)
PLC CPU memo area

The QD75 buffer memory is configured of the following types of areas.
Buffer memory address Buffer memory area configuration Axis 1 Axis 2 Axis 3 Axis 4
Basic parameter area 0 to 15 150 to 165 300 to 315 450 to 465
Detailed parameter area 17 to 62 167 to 212 317 to 362 467 to 512
OPR basic parameter area 70 to 78 220 to 228 370 to 378 520 to 528 Parameter area
OPR detailed parameter area 79 to 89 229 to 239 379 to 389 529 to 539
System monitor area 1200 to 1425
Monitor data area Axis monitor area 800 to 847, 899 900 to 947, 999 1000 to 1047, 1099 1100 to 1147, 1199
System control data area 1900, 1901, 1905, 1907 Control data area Axis control data area 1500 to 1550 1600 to 1650 1700 to 1750 1800 to 1850 Possible
Positioning data area (No.1 to 600) Positioning data area 2000 to 7999 8000 to 13999 14000 to 19999 20000 to 25999
26000 to 26049 27000 to 27049 28000 to 28049 29000 to 29049 Block start data area 26050 to 26099 27050 to 27099 28050 to 28099 29050 to 29099 Block start data area (No.7000)
Condition data area 26100 to 26199 27100 to 27199 28100 to 28199 29100 to 29199
26200 to 26249 27200 to 27249 28200 to 28249 29200 to 29249 Block start data area 26250 to 26299 27250 to 27299 28250 to 28299 29250 to 29299 Block start data area (No.7001)
Condition data area 26300 to 26399 27300 to 27399 28300 to 28399 29300 to 29399
26400 to 26449 27400 to 27449 28400 to 28449 29400 to 29449 Block start data area 26450 to 26499 27450 to 27499 28450 to 28499 29450 to 29499
Block start data area (No.7002)
Condition data area 26500 to 26599 27500 to 27599 28500 to 28599 29500 to 29599
26600 to 26649 27600 to 27649 28600 to 28649 29600 to 29649 Block start data area 26650 to 26699 27650 to 27699 28650 to 28699 29650 to 29699 Block start data area (No.7003)
Condition data area 26700 to 26799 27700 to 27799 28700 to 28799 29700 to 29799
26800 to 26849 27800 to 27849 28800 to 28849 29800 to 29849 Block start data area 26850 to 26899 27850 to 27899 28850 to 28899 29850 to 29899 Block start data area (No.7004)
Condition data area 26900 to 26999 27900 to 27999 28900 to 28999 29900 to 29999
PLC CPU memo area PLC CPU memo area 30000 to 30099 Possible
Use of address Nos. skipped above is prohibited. If used, the system may not operate correctly.

The data is transmitted between the QD75 memories with steps (1) to (8) shown below.
The data transmission patterns numbered (1) to (8) on the right page correspond to
the numbers (1) to (8) on the left page.

(3) PLC READY signal [Y0] OFF ON (1) Power supply ON/ PLC CPU reset

(1) Transmitting data when power is turned ON or PLC CPU is reset
When the power is turned ON or the PLC CPU is reset, the "parameters", "positioning data" and "block start data" stored (backed up) in the flash ROM is transmitted to the buffer memory.
The parameters or data is written from the PLC CPU to the buffer memory using the TO command. At this time, when the "parameter area (b) 1", "positioning data (No. 1 to 600)", "block start data (No. 7000 to 7004)", "control data" and "PLC CPU memo area" are written into the buffer memory with the TO command, it is simultaneously valid.
1 Parameter area (b) Parameters validated simultaneously with the writing to the buffer memory with the TO command.
( Pr.8 to Pr.10 , Pr.25 to Pr.42 )
OFF to ON When the PLC READY signal [Y0] changes from OFF to ON, the data stored in the buffer memory's "parameter area (a) 2" is validated.
For Pr.5 , however, only the data obtained first after the PLC READY signal [Y0]
changes from OFF to ON when the power is turned ON or PLC CPU is reset becomes validate. (Refer to Section 5.2 "List of parameters" for details.)
( Pr.1 to Pr.7 , Pr.11 to Pr.24 , Pr.43
to Pr.57 , Pr.150 )
The setting values of the parameters that correspond to parameter area (b) are valid when written into the buffer memory with the TO command. However, the setting values of the parameters that correspond to parameter area (a) are not validated until the PLC READY signal [Y0] changes from OFF to ON.
The data is read from the buffer memory to the PLC CPU using the FROM command.



The following transmission process is carried out by setting "1" in " Cd.1 Flash
ROM write request" (buffer memory [1900]).
The following transmission processes are carried out with the [flash ROM request] (write) from the peripheral device.
(1) Do not turn the power OFF or reset the PLC CPU while writing to the flash
ROM. If the power is turned OFF or the PLC CPU is reset to forcibly end the process, the data backed up in the flash ROM will be lost. (2) Do not write the data to the buffer memory before writing to the flash ROM is
completed. (3) The number of writes to the flash ROM with the PLC program is 25 max. while
the power is turned ON. Writing to the flash ROM beyond 25 times will cause an error (error code: 805). Refer to Section 15.2 "List of errors" for details.



The following transmission processes are carried out with the [Read from module] from the peripheral device.
The following transmission processes are carried out with the [monitor] from the peripheral device.
The following transmission processes are carried out with the [Write to module] from the peripheral device.
At this time, when [Flash ROM write] is set with the peripheral device, the transmission processes indicated with the following are carried out.
(5) Flash ROM write

The data transmission is carried out as shown in the previous pages, but the main method of using this data process is shown below.
The following methods can be used to set the positioning data.
From peripheral device Using sequense program
Write positioning data into buffer memory using TO command.
Set the data according to the peripheral device menu.
Write the data set with the peripheral device into the buffer memory.
Completion · User work · QD75 state



The details and usage of "OPR control" are explained in this chapter.
OPR control includes "machine OPR" that establish a machine OP without using address data, and "fast OPR" that store the coordinates established by the machine OPR, and carry out positioning to that position. OPR carried out by sequence programs from the PLC CPU are explained in this chapter. Refer to GX Configurator-QP Operating Manual for details on OPR using the peripheral device.
8.1 Outline of OPR control 8- 2 8.1.1 Two types of OPR control 8- 2 8.2 Machine OPR 8- 4 8.2.1 Outline of the machine OPR operation 8- 4 8.2.2 Machine OPR method 8- 5 8.2.3 OPR method (1): Near-point dog method 8- 6 8.2.4 OPR method (2): Stopper method 1) 8- 8 8.2.5 OPR method (3): Stopper method 2) 8- 11 8.2.6 OPR method (4): Stopper method 3) 8- 14 8.2.7 OPR method (5): Count method 1) 8- 16 8.2.8 OPR method (6): Count method 2) 8- 18 8.3 Fast OPR 8- 20 8.3.1 Outline of the fast OPR operation 8- 20

8.1.1 Two types of OPR control
In "OPR control" a position is established as the starting point (or "OP") when carrying out positioning control, and positioning is carried out toward that starting point. It is used to return a machine system at any position other than the OP to the OP when the QD75 issues a "OPR request" with the power turned ON or others, or after a positioning stop.
In the QD75, the two types of controls shown below are defined as "OPR control", following the flow of the OPR work. These two types of OPR control can be executed by setting the "OPR parameters", setting "Positioning start No. 9001" and "Positioning start No. 9002" prepared beforehand in the
QD75 to " Cd.3 Positioning start No.", and turning ON the positioning start signal.
The PSTRT start numbers of the dedicated instruction can also be set to 9001 or 9002 to execute the OPR control. (For details, refer to Chapter 14 "Dedicated instructions".) (1) Establish a positioning control OP – "Machine OPR" (positioning start No. 9001) (2) Carry out positioning toward the OP – "Fast OPR" (positioning start No. 9002).
The "machine OPR" in (1) above must always be carried out before executing the "fast
OPR" in (2).
The "OPR request flag" ( Md.31 Status: b3) must be turned ON in the QD75, and a
machine OPR must be executed in the following cases.
The address information stored in the QD75 cannot be guaranteed while the "OPR request flag" is ON.
The "OPR request flag" turns OFF and the "OPR complete flag" ( Md.31 Status: b4) turns ON if the machine OPR is executed and is completed normally.
OPR request

Refer to Section 3.2.4 "Combination of QD75 main functions and sub functions" for details on "sub functions" that can be combined with OPR control. Also refer to Chapter 12 "Control sub functions" for details on each sub function.
The following two sub functions are only related to machine OPR.

: Combination possible, : Restricted, : Combination not possible
Control can be carried out ignoring the "OPR request flag" ( Md.31 Status: b3) in systems that do not require an OPR.
In this case, the "OPR parameters ( Pr.43 to Pr.57 )" must all be set to their initial values or a value at which an error does not occur.
"Machine OPR" and "fast OPR" can be executed from the test mode of the peripheral device. Refer to GX Configurator-QP Operating Manual for details on OPR from the peripheral device.
[Remarks]

8.2.1 Outline of the machine OPR operation
Important
Use the OPR retry function when the OP position is not always in the same direction from the workpiece operation area (when the OP is not set near the upper or lower limit of the machine).
The machine OPR may not complete unless the OPR retry function is used.
In a machine OPR, a machine OP is established. None of the address information stored in the QD75, PLC CPU, or servo is used at this time. The position mechanically established after the machine OPR is regarded as the "OP" to be the starting point for positioning control. The method for establishing an "OP" by a machine OPR differs according to the method set in " Pr.43 OPR method".
The following shows the operation when starting a machine OPR.
( Pr.43 to Pr.57 ).
machine stops. (Refer to Sections 8.2.2 to 8.2.8)
If "a" is set as " Pr.45 OP address", "a" will be stored as the current position in the
" Md.20 Current feed value" and " Md.21 Machine feed value" which are
monitoring the position.
The " Pr.45 OP address" is a fixed value set by the user.
OP
Fig. 8.1 Example of a machine OPR
4) · Machine OPR · Near-point dog

The method by which the machine OP is established (method for judging the OP position and machine OPR completion) is designated in the machine OPR according to the configuration and application of the positioning method. The following table shows the six methods that can be used for this OPR method.
(The OPR method is one of the items set in the OPR parameters. It is set in " Pr.43 OPR method" of the basic parameters for OPR.)
Pr.43 OPR method Operation details
Deceleration starts by the OFF ON of the near-point dog. (Speed is reduced to
" Pr.47 Creep speed".)
The operation stops at the first zero signal after the near-point dog turns from ON OFF. When a "deviation counter clear output" is completed, the machine OPR is completed.
The stopper position is regarded as the OP. After the deceleration starts by the OFF ON of the near-point dog, the machine presses
against the stopper at the " Pr.47 Creep speed" and stops.
The machine OPR is regarded as completed on completion of the deviation counter clear
output provided after " Pr.49 OPR dwell time" passed after stoppage.
The stopper position is regarded as the OP. After the deceleration starts by the OFF ON of the near-point dog, the machine presses
against the stopper at the " Pr.47 Creep speed" and stops.
The machine OPR is regarded as completed on completion of the deviation counter clear output provided after the zero signal is detected after stoppage.
The stopper position is regarded as the OP.
The machine starts at the " Pr.47 Creep speed" from the beginning, then presses
against the stopper at the " Pr.47 Creep speed" and stops.
The machine OPR is regarded as completed on completion of the deviation counter clear output provided after the zero signal is detected after stoppage.
The deceleration starts by the OFF ON of the near-point dog, and the machine moves
at the " Pr.47 Creep speed".
The machine stops at the zero signal after moving the distance set in the " Pr.50
Setting for the movement amount after near-point dog ON" from the near point dog OFF ON position. When a "deviation counter clear signal output" is completed, the machine OPR is regarded as completed.
The deceleration starts by the OFF ON of the near-point dog, and the machine moves
at the " Pr.47 Creep speed".
The machine moves the distance set in the " Pr.50 Setting for the movement amount
after near-point dog ON" from the near point dog OFF ON position, and stops at that position. The machine OPR is then regarded as completed.
: The following are the signals input as the zero signals of the QD75 in the corresponding OPR methods.
Near-point dog method, count method 1): Signal that is output as a single pulse at one motor revolution (e.g. Z-phase signal
output from the drive unit) Stopper method 2), 3) : Signal that is output on detection of contact with the stopper. (Input externally)
The stopping accuracy is poor when the machine suddenly stops from fast speeds. To improve the machine's stopping accuracy, its must change over to a slow speed before stopping. This speed is set in the " Pr.47 Creep speed".

The following shows an operation outline of the "near-point dog method" OPR method.
The machine OPR is started.
(The machine begins the acceleration designated in " Pr.51 OPR acceleration time selection", in the direction
designated in " Pr.44 OPR direction". It then moves at the " Pr.46 OPR speed" when the acceleration is
completed.) 2) The machine begins decelerating when the near-point dog ON is detected.
(At this time, the near-point dog must be ON. The workpiece will continue decelerating and stop if the near-point dog is OFF.)
After the near-point dog turns OFF, the pulse output from the QD75 will stop at the first zero signal, outputting a "deviation counter clear signal" to the drive unit. (The "deviation counter clear signal output time" is set in Pr.55 .)
b4) turns from OFF to ON and the OPR request flag ( Md.31 Status: b3) turns from ON to OFF.
Pr.46
OPR speed Deceleration at the near-point dog ON
Pr.47
Md.34
Movement amount after near-point dog ON
Adjust so the near-point dog OFF position is as close as possible to the center of the zero signal HIGH level. If the near-point dog OFF position overlaps with the zero signal, the machine OPR stop position may deviate by one servomotor rotation.
ON
Machine OPR start (Positioning start signal)
ON
OFF
Md.31
OFF
Md.31
Deviation counter clear output
signal output time Pr.55
Standing by In OPR Standing by Axis operation status
Md.26
Md.34
Inconsistent 0 Movement amount after near-point dog ON
Md.20 Md.21
Value of the machine moved is stored. OP address Current feed value Machine feed value
Fig. 8.2 Near-point dog method machine OPR

A pulse generator with a zero signal is required. When using a pulse generator without a zero signal, generate a zero signal using an external signal.
(1) An error "Start at OP (error code: 201)" will occur if another machine OPR is
attempted after a machine OPR completion when the OPR retry function is not set ("0" is set in " Pr.48 OPR retry").
(2) Machine OPR carried out from the near-point dog ON position will start at the
" Pr.47 Creep speed".
(3) The near-point dog must be ON during deceleration from the OPR speed " Pr.47
Creep speed".
The workpiece will continue decelerating and stop if the near-point dog is turned OFF
before it has decelerated to the creep speed, thus causing an error "Dog detection timing fault (error code: 203)".

Inconsistent Value the machine moved is stored Address at stop
Fig. 8.3 Operation when the near-point dog is turned OFF before the creep speed is reached
(4) When a machine OPR is stopped with the stop signal, perform a machine OPR again.
If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.

The following shows an operation outline of the "stopper method 1)" OPR method.
The machine OPR is started.
(The machine begins the acceleration designated in " Pr.51 OPR acceleration time selection", in the direction designated in
" Pr.44 OPR direction". It then moves at the " Pr.46 OPR speed" when the acceleration is completed.)
(Torque limiting is required at this time. If the torque is not limited, the servomotor may fail in step 4).) 4) The machine presses against the stopper at the creep speed and stops.
The pulse output from the QD75 will stop when the " Pr.49 OPR dwell time" has elapsed after the near-point dog turns ON,
outputting the "deviation counter clear output" to the drive unit.
(A "deviation counter clear signal output time" is set in the Pr.55 .)
and the OPR request flag ( Md.31 Status: b3) turns from ON to OFF.
Pr. 46 OPR speed
Pr. 47 Creep speed
Valid torque limit range
Time out of dwell time
OFF
Machine OPR start (Positioning start signal)
OFF
OPR request flag [ Md.31 Status : b3]
OPR complete flag [ Md.31 Status : b4]
Deviation counter clear output
Pr.55 Deviation counter clear signal
Md.26 Axis operation status Standing by
In OPR Standing by
Md.34 Movement amount after near-point dog ON
Md.20 Current feed value
OP address Value the machine moved is stored
Md.21 Machine feed value
Fig. 8.4 Stopper method 1) machine OPR

(1) Always limit the servomotor torque after the " Pr.47 Creep speed" is reached. If the
torque is not limited, the servomotor may fail when the machine presses against the stopper. (Refer to Section 12.4.2 "Torque limit function".) (2) In the "stopper method 1)", the OPR retry function is unusable.
(1) Set a value in the " Pr.49 OPR dwell time" that is equal to or higher than the
movement time from the near-point dog ON to the time the machine presses against the stopper. (2) The workpiece will continue decelerating and stop if the " Pr.49 OPR dwell time"
elapses during deceleration from the " Pr.46 OPR speed", thus causing an error
"Dwell time fault (error code: 205)".

Fig. 8.5 Operation when the dwell time elapses during deceleration from the OPR speed

(3) If the " Pr.49 OPR dwell time" elapses before the stop at the stopper, the workpiece
will stop at that position, and that position will be regarded as the OP. At this time, an error will not occur.

Fig. 8.6 Operation when the dwell time elapses before the stop at the stopper
(4) Machine OPR started while the near-point dog is ON will start at the " Pr.47 Creep
speed". (5) When a machine OPR is stopped with the stop signal, perform a machine OPR again.
If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.

The following shows an operation outline of the "stopper method 2)" OPR method.
The machine OPR is started.
(The machine begins the acceleration designated in " Pr.51 OPR acceleration time selection", in the direction designated in
" Pr.44 OPR direction". It then moves at the " Pr.46 OPR speed" when the acceleration is completed.)
(Torque limiting is required at this time. If the torque is not limited, the servomotor may fail in step 4).) 4) The machine presses against the stopper at the creep speed and stops.
The pulse output from the QD75 will stop at the zero signal after the machine stops, outputting the "deviation counter clear output" to the drive unit.
(A "deviation counter clear signal output time" is set in the Pr.55 .)
and the OPR request flag ( Md.31 Status: b3) turns from ON to OFF.
Pr. 46 OPR speed Pr. 47 Creep speed
Valid torque limit range
ON
Machine OPR start (Positioning start signal)
ON
OPR request flag [ Md.31 Status : b3]
ON
OPR complete flag [ Md.31 Status : b4]
Deviation counter clear output
Pr.55 Deviation counter clear signal output time
Md.26 Axis operation status Standing by
Md.34 Movement amount after near-point dog ON
Md.20 Current feed value
Value the machine moved is stored
Md.21 Machine feed value
Fig. 8.7 Stopper method 2) machine OPR

(1) Always limit the servomotor torque after the " Pr.47 Creep speed" is reached. If the
torque is not limited, the servomotor may fail when the machine presses against the stopper. (Refer to Section 12.4.2 "Torque limit function".) (2) Use an external input signal as the zero signal. (3) In the "stopper method 2)", the OPR retry function is unusable.
(1) Input a zero signal from an external source after the machine presses against the
stopper. The workpiece will continue decelerating and stop if a zero signal is input before
deceleration to the " Pr.47 Creep speed". An error "OP detection timing fault (error code: 204)" will occur after the machine stops. (2) The near-point dog must be turned ON until it presses against the stopper.

Fig. 8.8 Operation when a zero signal is input before the creep speed is reached

(3) If the zero signal is input before the workpiece stops at the stopper, the workpiece
will stop at that position, and that position will be regarded as the OP.

Fig. 8.9 Operation when the zero signal is input before the stop at the stopper
(4) Machine OPR started while the near-point dog is ON will start at the " Pr.47 Creep
speed". (5) When a machine OPR is stopped with the stop signal, perform a machine OPR again.
If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.

The following shows an operation outline of the "stopper method 3)" OPR method. The "stopper method 3)" method is effective when a near-point dog has not been installed. (Note that the operation is carried out from the start at the " Pr.47 Creep speed", so it will
take some time until the machine OPR completion.)
The machine OPR is started.
(The machine moves at the " Pr.47 Creep speed", in the direction designated in " Pr.44 OPR direction". Torque
limiting is required at this time. If the torque is not limited, the servomotor may fail when the machine presses against the stopper in step 2.)
The pulse output from the QD75 will stop at the zero signal after the machine stops, outputting the "deviation counter clear output" to the drive unit.
(A "deviation counter clear signal output time" is set in the Pr.55 .)
from OFF to ON, and the OPR request flag ( Md.31 Status: b3) turns from ON to OFF.
Pr. 47 Creep speed
Valid torque limit range
Machine OPR start (Positioning start signal)
ON
OFF
OPR request flag [ Md.31 Status : b3]
OFF
OPR complete flag [ Md.31 Status : b4]
Deviation counter clear output
Pr.55 Deviation counter clear signal output time
Md.26 Axis operation status Standing by
In OPR Standing by
Md.34 Movement amount after near-point dog ON
Md.20 Current feed value Md.21 Machine feed value
Inconsistent Value the machine moved is stored
Fig. 8.10 Stopper method 3) machine OPR

(1) Always limit the servomotor torque after the " Pr.47 Creep speed" is reached. If the
torque is not limited, the servomotor may fail when the machine presses against the stopper. (Refer to Section 12.4.2 "Torque limit function".) (2) Use an external input signal as the zero signal. (3) The OPR retry function cannot be used in "stopper stop method 3)".
(1) If the zero signal is input before the workpiece stops at the stopper, the workpiece
will stop at that position, and that position will become the OP. At this time an error will not occur.

Fig. 8.11 When the zero signal is input before the stop at the stopper
(2) When a machine OPR is stopped with the stop signal, perform a machine OPR again.
If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.

The following shows an operation outline of the "count method 1)" OPR method. In the "count method 1)" machine OPR, the following can be performed:
The machine OPR is started. (The machine begins the acceleration designated in " Pr.51 OPR acceleration time selection", in the direction
designated in " Pr.44 OPR direction". It then moves at the " Pr.46 OPR speed" when the acceleration is
completed.) 2) The machine begins decelerating when the near-point dog ON is detected.
On detection of the first zero signal after the axis has traveled the movement amount set in " Pr.50 Setting for the
movement amount after near-point dog ON" after near-point dog ON, the pulse output from the QD75 stops and the "deviation counter clear output" is output to the drive unit. (A "deviation counter clear signal output time" is set in Pr.55 .)
OFF to ON, and the OPR request flag ( Md.31 Status: b3) turns from ON to OFF.
Pr. 46 OPR speed
Pr. 50 Setting for the movement amount after near-point dog ON
Pr. 47 Creep speed
Md.34 Movement amount after near-point dog ON
Leave sufficient distance from the zero point position to the near-point dog OFF
Adjust the setting for the movement amount after near-point dog ON to be as near as possible to the center of the zero signal HIGH. If the setting for the movement amount after near-point dog ON falls within the zero signal, there may be produced an error of one servomotor rotation in the machine OPR stop position.
First zero signal after travel of the movement amount set to " Pr. 50 Setting for the movement amount after near-point dog ON"
OFF
Machine OPR start (Positioning start signal)
OPR request flag [ Md.31 Status : b3]
ON
OPR complete flag [ Md.31 Status : b4]
Deviation counter clear output
Pr.55 Deviation counter clear
Standing by In OPR Md.26 Axis operation status
Value of 1.
Md.34 Movement amount after near-point dog ON
Md.20 Current feed value
Value the machine moved is stored OP address
Md.21 Machine feed value
Fig. 8.12 Count method1) machine OPR

A pulse generator with a zero signal is required. When using a pulse generator without a zero signal, generate a zero signal using an external signal.
(1) An error "Count method movement amount fault (error code: 206)" will occur
and the operation will not start if the " Pr.50 Setting for the movement
amount after near-point dog ON" is smaller than the deceleration distance from the " Pr.46 OPR speed" to " Pr.47 Creep speed".
A deceleration stop will be carried out if the speed is changed during the operation and an error occurs. (2) The following shows the operation when a machine OPR is started while the
near-point dog is ON.
Pr. 50 Setting for the movement amount after near-point dog ON [Operation when a machine OPR is started at the near-point dog ON position]
selection" when the near-point dog OFF is detected. 4) After the machine stops, a machine OPR is carried out in the OPR direction.
" Pr.50 Setting for the movement amount
after near-point dog ON" on detection of the near-point dog signal ON.
Fig. 8.13 Count method 1) machine OPR on the near-point dog ON position
(3) Turn OFF the near-point dog at a sufficient distance from the OP.
Although there is no harm in operation if the near-point dog is turned OFF during a machine OPR, it is recommended to leave a sufficient distance from the OP when the near-point dog is turned OFF for the following reason.
If machine OPRs are performed consecutively after the near-point dog is turned OFF at the time of machine OPR completion, operation will be performed at the OPR speed until the hardware stroke limit (upper/lower limit) is reached. (4) When a machine OPR is stopped with the stop signal, perform a machine
OPR again. If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.
Near-point dog OFF · Zero signal

The following shows an operation outline of the "method 2)" OPR method. The "count method 2)" method is effective when a "zero signal" cannot be received. (Note that compared to the "count method 1)" method, using this method will result in more deviation in the stop position during machine OPR.)
The machine OPR is started.
(The machine begins the acceleration designated in " Pr.51 OPR acceleration time selection", in the
direction designated in " Pr.44 OPR direction". It then moves at the " Pr.46 OPR speed" when the
acceleration is completed.)
from the near-point dog ON position.
Pr. 46 OPR speed
Pr.50 Setting for the movement amount after near-point dog ON
Pr. 47 Creep speed
Md.34 Movement amount after near-point dog ON
Leave sufficient distance from the OP position to the near-point dog OFF
ON
Machine OPR start (Positioning start signal)
ON
OPR request flag [ Md.31 Status : b3]
ON
OFF
OPR complete flag [ Md.31 Status : b4]
Md.26 Axis operation status Standing by Standing by
Md.34 Movement amount after near-point dog ON
Value of .
Md.20 Current feed value
Value the machine moved is stored Inconsistent
Md.21 Machine feed value
Fig. 8.14 Count method 2) machine OPR

When this method is used, a deviation will occur in the stop position (OP) compared to other OPR methods because an error of about 1 ms occurs in taking in the near-point dog ON.
(1) An error "Count method movement amount fault (error code: 206)" will occur
and the operation will not start if the " Pr.50 Setting for the movement
amount after near-point dog ON" is smaller than the deceleration distance from the " Pr.46 OPR speed" to " Pr.47 Creep speed".
A deceleration stop will be carried out if the speed is changed during the operation and an error occurs. (2) The following shows the operation when a machine OPR is started while the
near-point dog is ON.
Pr.50 Setting for the movement amount after near-point dog ON
[Operation when a machine OPR is started at the near-point dog ON position]
selection" when the near-point dog OFF is detected. 4) After the machine stops, a machine OPR is carried out in the OPR direction.
the movement amount set in the " Pr.50
Setting for the movement amount after near- point dog ON".
Fig. 8.15 Count method 2) machine OPR on the near-point dog ON position
(3) Turn OFF the near-point dog at a sufficient distance from the OP.
Although there is no harm in operation if the near-point dog is turned OFF during a machine OPR, it is recommended to leave a sufficient distance from the OP when the near-point dog is turned OFF for the following reason.
If machine OPRs are performed consecutively after the near-point dog is turned OFF at the time of machine OPR completion, operation will be performed at the OPR speed until the hardware stroke limit (upper/lower limit) is reached. (4) When a machine OPR is stopped with the stop signal, perform a machine
OPR again. If the restart command is turned ON after a stop with the stop signal, an error "OPR restart not possible" (error code: 209) occurs.
Near-point dog OFF

8.3.1 Outline of the fast OPR operation
Fast OPR operation
In a fast OPR, positioning is carried out by a machine OPR to the " Md.21
Machine feed value" stored in the QD75. The following shows the operation during a fast OPR start.
in the OPR parameters ( Pr.43 to Pr.57 ).
Pr. 46 OPR speed
Machine OP (OP position)
Fast OPR start (Positioning start signal)
Md.26 Axis operation status In position control Standing by Standing by
OP
Positioning to the OP
Fig. 8.16 Fast OPR

The following shows details about the operation timing and time during fast OPR.

Fig. 8.17 Operation timing and processing time of fast OPR
1.0 to 1.3 2.7 to 4.4 0 to 1.8
When the OPR complete flag ( Md.31 Status: b3) is ON, executing a fast OPR start will result in an error "OPR request ON" (error code: 207)".
t1 t2 t3

MEMO

The details and usage of the major positioning controls (control functions using the "positioning data") are explained in this chapter. The major positioning controls include such controls as "positioning control" in which positioning is carried out to a designated position using the address information, "speed control" in which a rotating object is controlled at a constant speed, "speed-position switching control" in which the operation is shifted from "speed control" to "position control" and "position-speed switching control" in which the operation is shifted from "position control" to "speed control".
Carry out the required settings to match each control.
9.1 Outline of major positioning controls 9- 2 9.1.1 Data required for major positioning control 9- 4 9.1.2 Operation patterns of major positioning controls 9- 5 9.1.3 Designating the positioning address 9- 15 9.1.4 Confirming the current value 9- 16 9.1.5 Control unit "degree" handling 9- 18 9.1.6 Interpolation control 9- 21 9.2 Setting the positioning data 9- 25 9.2.1 Relation between each control and positioning data 9- 25 9.2.2 1-axis linear control 9- 27 9.2.3 2-axis linear interpolation control 9- 29 9.2.4 3-axis linear interpolation control 9- 33 9.2.5 4-axis linear interpolation control 9 -39 9.2.6 1-axis fixed-feed control 9- 43 9.2.7 2-axis fixed-feed control (interpolation) 9- 45 9.2.8 3-axis fixed-feed control (interpolation) 9- 47 9.2.9 4-axis fixed-feed control (interpolation) 9- 51 9.2.10 2-axis circular interpolation control with sub point designation 9- 53 9.2.11 2-axis circular interpolation control with center point designation 9- 59 9.2.12 1-axis speed control 9- 67 9.2.13 2-axis speed control 9- 70 9.2.14 3-axis speed control 9- 73 9.2.15 4-axis speed control 9- 77 9.2.16 Speed-position switching control (INC mode) 9- 82 9.2.17 Speed-position switching control (ABS mode) 9- 90 9.2.18 Position-speed switching control 9- 98 9.2.19 Current value changing 9-105 9.2.20 NOP instruction 9-110 9.2.21 JUMP instruction 9-111 9.2.22 LOOP 9-113 9.2.23 LEND 9-114

"Major positioning controls" are carried out using the "positioning data" stored in the QD75. The basic controls such as position control and speed control are executed by setting the required items in this "positioning data", and then starting that positioning data. The control system for the "major positioning controls" is set in setting item " Da.2 Control system" of the positioning data. Control defined as a "major positioning control" carries out the following types of control according to the " Da.2 Control system" setting.
Major positioning control Da.2 Control system Details
Positioning of a designated 1 axis is carried out from the start address (current stop position) to the designated position. 2-axis linear interpolation control
ABS Linear 1 INC Linear 1
Using a designated 2 axes, linear interpolation control is carried out from the start address (current stop position) to the designated position. 3-axis linear interpolation control
ABS Linear 2 INC Linear 2
Using a designated 3 axes, linear interpolation control is carried out from the start address (current stop position) to the designated position.
ABS Linear 3 INC Linear 3
4-axis linear interpolation control
Using a designated 4 axes, linear interpolation control is carried out from the start address (current stop position) to the designated position.
ABS Linear 4 INC Linear 4
Positioning of a designated 1 axis is carried out from the start address (current stop position). (The " Md.20 Current feed value" is set to "0" at the start.)
1-axis fixed- feed control Fixed-feed 1
Using a designated 2 axes, linear interpolation control is carried out from the start address (current stop position). (The " Md.20 Current feed value" is set to "0" at the start.)
2-axis fixed- feed control Fixed-feed 2
Using a designated 3 axes, linear interpolation control is carried out from the start address (current stop position).
3-axis fixed- feed control Fixed-feed 3
(The " Md.20 Current feed value" is set to "0" at the start.)
Using a designated 4 axes, linear interpolation control is carried out from the start address (current stop position).
4-axis fixed- feed control Fixed-feed 4
(The " Md.20 Current feed value" is set to "0" at the start.)
ABS Circular sub INC Circular sub
The axis in which the interpolation control system is set is regarded as the reference axis. Positioning is carried out in an arc path to a designated position, while controlling the other axis (interpolation axis) to match the positioning data set in the reference axis.
2-axis circular interpolation control Center point designation
ABS Circular right ABS Circular left INC Circular right INC Circular left
Forward run speed 1 Reverse run speed 1 The speed control of the designated 1 axis is carried out.
Forward run speed 2 Reverse run speed 2 The speed control of the designated 2 axes is carried out.
Forward run speed 3 Reverse run speed 3 The speed control of the designated 3 axes is carried out. Speed control
Forward run speed 4 Reverse run speed 4 The speed control of the 4 axes is carried out.

Major positioning control Da.2 Control system Details
Forward run speed/position Reverse run speed/position
The control is continued as position control (positioning for the designated address or movement amount) by turning ON the "speed-position switching signal" after first carrying out speed control.
Forward run position/speed Reverse run position/speed
The control is continued as speed control by turning ON the "position-speed switching signal" after first carrying out position control.
A nonexecutable control system. When this instruction is set, the operation is transferred to the next data operation, and the instruction is not executed.
NOP instruction NOP instruction
The current feed value ( Md.20 ) is changed to an address
set in the positioning data. This can be carried out by either of the following 2 methods. (The machine feed value cannot be changed.)
Current value changing Current value changing
Control is returned to the top of the repeat control by repeat LOOP to LEND. After the repeat operation is completed specified times, the next positioning data is run.
In "2-axis linear interpolation control", "3-axis linear interpolation control", "4-axis linear interpolation control", "2-axis fixed-feed control", "3-axis fixed-feed control", "4-axis fixed-feed control", "2-axis circular interpolation control", "2-axis speed control", "3-axis speed control" and "4-axis speed control", control is carried out so that linear and arc paths are drawn using a motor set in two or more axes directions. This kind of control is called "interpolation control". (Refer to Section 9.1.6 "Interpolation control" for details.)
Speed-position switching control · Position-speed switching control · Other control

The following table shows an outline of the "positioning data" configuration and setting details required to carry out the "major positioning controls".
Setting item Setting details
Da.1 Operation pattern Set the method by which the continuous positioning data (Ex: positioning data No. 1, No. 2, No. 3) will be controlled. (Refer to Section 9.1.2.)
Da.2 Control system Set the control system defined as a "major positioning control". (Refer to Section 9.1.)
Select and set the acceleration time at control start. (Select one of the four values set
Da.3 Acceleration time No.
in Pr.9 , Pr.25 , Pr.26 , and Pr.27 for the acceleration time.)
Select and set the deceleration time at control stop. (Select one of the four values set
Positioning data No. 1
Da.4 Deceleration time No.
in Pr.10 , Pr.28 , Pr.29 , and Pr.30 for the deceleration time.)
Da.5 Axis to be
Set an axis to be interpolated (partner axis) during the 2-axis interpolation operation (Refer to Section 9.1.6).
Da.6 Positioning address/
movement amount Set the target value during position control. (Refer to Section 9.1.3.)
Da.7 Arc address Set the sub point or center point address during circular interpolation control.
Da.8 Command speed Set the speed during the control execution.
Set the time the machine waits from the completion of the executed positioning control and the stopping of the workpiece until the judgment of the QD75 positioning completion.
Da.9 Dwell time
Da.10 M code Set this item when carrying out sub work (clamp and drill stops, tool replacement, etc.) corresponding to the code No. related to the positioning data execution.
The settings and setting requirement for the setting details of Da.1 to Da.10 differ according to the " Da.2 Control system". (Refer to Section 9.2 "Setting the positioning data".)
Refer to Section 3.2.4 "Combination of QD75 major functions and sub functions" for details on "sub functions" that can be combined with the major positioning control. Also refer to Chapter 12 "Control sub Functions" for details on each sub function.
"Major positioning control" can be executed from the peripheral device test mode. Refer to GX Configurator-QP Operating Manual for details on carrying out major positioning control from the peripheral device.
interpolated

In "major positioning control" (high-level positioning control), " Da.1 Operation pattern" can be set to designate whether to continue executing positioning data after the started positioning data. The "operation pattern" includes the following 3 types.
Positioning complete (1) Independent positioning control (operation pattern: 00) Positioning continue (2) Continuous positioning control (operation pattern: 01) (3) Continuous path control (operation pattern: 11)
The following shows examples of operation patterns when "1-axis linear control (ABS linear 1)" is set in positioning data No. 1 to No. 6 of axis 1. Details of each operation pattern are shown on the following pages.
< Operation example when "1-axis linear positioning" is set in the positioning data of axis 1 >

Positioning data No.1
No.2
Positioning to address [B] at command speed [b] Operation pattern = 11: Continuous path control
No.3
No.4
No.5
No.6

The machine stops, and then continues the next positioning.
(Direction in which axis 1 addresses increase)
(One motor is driven, and positioning is carried out to an addresses designated in one direction.)

POINT The BUSY signal [XC, XD, XE, XF] turns ON even when position control of movement amount 0 is executed. However, since the ON time is short, the ON status may not be detected in the sequence program.
![Page 306 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Independent positioning control (Positioning complete)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-306.webp?w=400)
This control is set when executing only one designated data item of positioning. If a dwell time is designated, the positioning will complete after the designated time elapses. This data (operation pattern [00] data) becomes the end of block data when carrying out block positioning. (The positioning stops after this data is executed.)
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Independent positioning control (Positioning complete) diagram (page 306)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-306-1.webp)
Fig. 9.1 Operation during independent positioning control
![Page 307 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Continuous positioning control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-307.webp?w=400)
(1) The machine always automatically decelerates each time the positioning is completed. Acceleration is then carried out after the QD75 command speed reaches 0 to carry out the next positioning data operation. If a dwell time is designated, the acceleration is carried out after the designated time elapses. (2) In operation by continuous positioning control (operation pattern "01"), the next positioning No. is automatically executed. Always set operation pattern "00" in the last positioning data to complete the positioning. If the operation pattern is set to positioning continue ("01" or "11"), the operation will continue until operation pattern "00" is found. If the operation pattern "00" cannot be found, the operation may be carried out until the positioning data No. 600. If the operation pattern of the positioning data No. 600 is not completed, the operation will be started again from the positioning data No. 1.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Continuous positioning control diagram (page 307)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-307-1.webp)
Fig. 9.2 Operation during continuous positioning control
![Page 308 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Continuous path control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-308.webp?w=400)
(1) Continuous path control
(a) The speed is changed without deceleration stop between the command speed of the positioning data currently being run and the speed of the positioning data that will be run next. The speed is not changed if the current speed and the next speed are equal. (b) The speed will become the speed used in the previous positioning operation if the command speed is set to "-1". (c) Dwell time will be ignored, even if set. (d) The next positioning No. is executed automatically in operations by continuous path control (operation pattern "11"). Always complete the positioning by setting operation pattern "00" in the last positioning data. If the operation pattern is set to positioning continue ("01" or "11"), the operation will continue until operation pattern "00" is found. If the operation pattern "00" cannot be found, the operation may be carried out until the positioning data No. 600. If the operation pattern of the positioning data No. 600 is not completed, the operation will be started again from the positioning data No. 1. (e) The speed switching patterns include the "front-loading speed switching pattern" in which the speed is changed at the end of the current positioning side, and the "standard speed switching pattern" in which the speed is at the start of the next positioning side. (Refer to
" Pr.19 Speed switching mode".)
Continuous path control Standard speed switching mode
Front-loading speed switching mode
(f) In the continuous path control, the positioning may be completed before the set address/movement amount and the current data may be switched to the "positioning data that will be run next". This is because a preference is given to the positioning at a command speed. In actuality, the positioning is completed before the set address/movement amount by an amount of remaining distance at speeds less than the command speed. The remaining distance ( ) at speeds less than the command speed is 0 (distance moved in 1.8ms at a speed at the time of completion of the positioning).


Fig. 9.3 Operation during continuous path control (Standard speed switching mode)

In the continuous path control, a speed variation will not occur using the near-pass function when the positioning data No. is switched (Refer to Section 12.3.3 "Near- pass function").
Deceleration stops are basically not carried out in continuous path control, but the machine will carry out a deceleration stop to speed "0" in the following cases (a) to (d).
(a) When the operation pattern of the positioning data currently being executed is "continuous path control: 11", and the movement direction of the positioning data currently being executed differs from that of the next positioning data. (Only for 1-axis positioning control (Refer to the "Point" in the next page.))


(b) When the operation pattern of the positioning data currently being executed is "continuous path control: 11", and the movement amount of the next positioning data is "0".
(c) During operation by step operation. (Refer to Section 12.7.1 Step function".)
(d) When there is an error in the positioning data to carry out the next operation.
POINTS (1) The movement direction is not checked during interpolation operations. Thus, automatic deceleration to a stop will
not be carried out even if the movement direction is changed (See the figures below). Because of this, the interpolation axis may suddenly reverse direction. To avoid this sudden direction reversal in the interpolation axis, set the pass point to continuous positioning control "01" instead of setting it to continuous path control "11".
[Positioning by interpolation] [Reference axis operation] [Interpolation axis operation]
No.1
No.2
No.1
No.2
No.1
No.2
(2) When the interpolation axis reveres direction suddenly, the command pulses from QD75 are output as shown in the
figure below.
The t1 and t2 are calculated using the following expressions, where a command frequency is f (pps). t1 = 1/2 f (s) t2 = 1/f (s) A time of t1 must be maintained by the drive unit for a specified period T (s). (T depends on the drive unit specifications.)
If t1 cannot be maintained for T or longer, lower the " Da.8 Command speed" of the positioning data.
(3) When a "0" is set in the " Da.6 Positioning address/movement amount" of the continuous path control positioning
data, the command speed of about 2 ms is reduced to 0.
When a "0" is set in the " Da.6 Positioning address/movement amount" to increase the number of speed change
points in the future, change the " Da.2 Control system" to the "NOP instruction" to make the control nonexecutable. (Refer to Section 9.2.20 "NOP instruction".) (4) In the continuous path control positioning data, assure a movement distance so that the execution time with that
data is 100 ms or longer, or lower the command speed.

(a) Continuous path control command speeds are set with each positioning data. The QD75 then carries out the positioning at the speed designated with each positioning data.
(b) The command speed can be set to "–1" in continuous path control. The control will be carried out at the speed used in the previous positioning data No. if the command speed is set to "–1". *1
(The "current speed" will be displayed in the command speed when the positioning data is set with a peripheral device. The current speed is the speed of the positioning control being executed currently.)
1) The speed does not need to be set in each positioning data when carrying out uniform speed control if "–1" is set beforehand in the command speed. 2) If the speed is changed in the previous positioning data when "–1" is set in the command speed, the operation can be continued at the new speed. 3) An error "no command speed" (error code: 503) occurs and positioning cannot be started if "–1" is set in the command speed of the first positioning data at start.
[Relation between the command speed and current speed]
P1 P2 P3 P4 P5 Speed
P1 P2 P3 P4 P5 Speed


Da. 7 Command speed
Da. 7 Command speed
Md. 36 Current speed
Md. 36 Current speed
The current speed is changed even if the command speed is not reached in P2.
POINTS (1) In the continuous path control, a speed variation will not occur using the near-pass function when the
positioning data is switched (Refer to Section 12.3.3 "Near-pass function").
(2) The QD75 holds the command speed set with the positioning data, and the latest value of the speed
set with the speed change request as the " Md.27 Current speed". It controls the operation at the
"current speed" when "-1" is set in the command speed. (Depending on the relation between the movement amount and the speed, the feedrate may not reach the command speed value, but even then the current speed will be updated. *2)
(3) When the address for speed change is identified beforehand, generate and execute the positioning
data for speed change by the continuous path control to carry out the speed change without requesting the speed change with a sequence program.
*2 *1

(Refer to " Pr.19 Speed switching mode".)
(a) Standard speed switching mode
1) If the respective command speeds differ in the "positioning data currently being executed" and the "positioning data to carry out the next operation", the machine will accelerate or decelerate after reaching the positioning point set in the "positioning data currently being executed" and the speed will change over to the speed set in the "positioning data to carry out the next operation". 2) The parameters used in acceleration/deceleration to the command speed set in the "positioning data to carry out the next operation" are those of the positioning data to carry out acceleration/deceleration. Speed switching will not be carried out if the command speeds are the same.

Fig. 9.4 Operation for the standard speed switching mode
3) Speed switching condition If the movement amount is small in regard to the target speed, the current speed may not reach the target speed even if acceleration/deceleration is carried out. In this case, the machine is accelerated/decelerated so that it nears the target speed. If the movement amount will be exceeded when automatic deceleration is required (Ex. Operation patterns "00", "01"), the machine will immediately stop at the designated positioning address, and a "insufficient movement distance warning (warning code: 513)" will occur.

[When the speed cannot change over in P2]
[When the movement amount is small during automatic deceleration]
When the relation of the speeds is P1 = P4, P2 = P3, P1 < P2.
The movement amount required to carry out the automatic deceleration cannot be secured, so the machine immediately stops in a speed ≠ 0 status.
Positioning address.
(b) Front-loading speed switching mode

Fig. 9.5 Operation for the front-loading speed switching mode

3) Speed switching condition If the movement amount is small in regard to the target speed, the current speed may not reach the target speed even if acceleration/deceleration is carried out. In this case, the machine is accelerated/decelerated so that it nears the target speed. If the movement amount will be exceeded when automatic deceleration is required (Ex. Operation patterns "00", "01"), the machine will immediately stop at the designated positioning address, and a "insufficient movement distance warning (warning code: 513)" will occur.
[When the speed cannot change over to the P2 speed in P1]
[When the movement amount is small during automatic deceleration]
When the relation of the speeds is P1 = P4, P2 = P3, P1 < P2.
The movement amount required to carry out the automatic deceleration cannot be secured, so the machine immediately stops in a speed ≠ 0 status.
Positioning address

The following shows the two methods for commanding the position in control using positioning data.
Positioning is carried out to a designated position (absolute address) having the OP as a reference. This address is regarded as the positioning address. (The start point can be anywhere.)

Fig. 9.6 Absolute system positioning
The position where the machine is currently stopped is regarded as the start point, and positioning is carried out for a designated movement amount in a designated movement direction.

Fig. 9.7 Incremental system positioning

Values showing the current value
The following two types of addresses are used as values to show the position in the QD75. These addresses ("current feed value" and "machine feed value") are stored in the monitor data area, and used in monitoring the current value display, etc.
The "current feed value" and "machine feed value" are used in monitoring the current value display, etc.
Current value changed to 20000 with current value
Address after the current value is changed is stored
0 1 to Md. 20 Current feed value
0 1 to Md. 21 Machine feed value
Address does not change even after the current value is changed
Fig. 9.8 Current feed value and machine feed value

(1) A 1.8ms error will occur in the current value update timing when the stored
"current feed value" is used in the control. A 56.8ms error will occur in the current value update timing when the stored "machine feed value" is used in the control.
(2) The "current feed value" and "machine feed value" may differ from the values
set in " Da.6 Positioning address/movement amount" of the positioning data if
the movement amount per pulse is not set to "1".
The "current feed value" and "machine feed value" are stored in the following buffer memory addresses, and can be read using a "DFRO (P) command" from the PLC CPU.

Md.20 Current feed value 800, 801 900, 900 1000, 1001 1100, 1101
Md.21 Machine feed value 802, 803 902, 903 1002, 1003 1102, 1103

Program in which the axis 1 current feed value is read to D104 and D105

When the control unit is set to "degree", the following items differ from when other control units are set.
The address of “ Md.20 Current feed value” becomes a ring address from 0 to
359.99999°.
But the address of “ Md.21 Machine feed value” doesn’t become a ring address.
359.99999° 359.99999°
With the control unit set to "degree", the software stroke limit upper and lower limit values are 0 to 359.99999. (a) Setting to validate software stroke limit
To validate the software stroke limit, set the software stroke limit lower limit value and the upper limit value in a clockwise direction.
315.00000
90.00000
To invalidate the software stroke limit, set the software stroke limit lower limit value equal to the software stroke limit upper limit value. The control can be carried out irrespective of the setting of the software stroke limit.
![Page 319 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Positioning control method when the control unit is set to "degree"](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-319.webp?w=400)
1) Absolute system (a) When the software stroke limit is invalid
Positioning is carried out in the nearest direction to the designated address, using the current value as a reference. (This is called "shortcut control".)
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Positioning control method when the control unit is set to "degree" diagram (page 319)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-319-1.webp)
Moved from 315° to 45° Moved from 45° to 315°
Using the " Cd.40 ABS direction in degrees", the shortcut control can be invalidated
to carry out positioning in the designated direction. This function can be performed when the software stroke limit is invalid. When the software stroke limit is valid, an error "ABS direction in degrees illegal" (error code: 546) occurs and positioning is not started. To designate the movement direction for the ABS control, write 1 or 2 to the " Cd.40
ABS direction in degrees" of the buffer memory. (The initial value is 0). The value written to the " Cd.40 ABS direction in degrees" becomes valid only when
the positioning control is started. In the continuous positioning control or continuous path control, the operation is continued with the setting made at a start if the setting is changed during the operation.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Positioning control method when the control unit is set to "degree" diagram (page 319)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-319-2.webp)
Buffer memory address Name Function Axis 1 Axis 2 Axis 3 Axis 4
Cd.40 ABS direction in degrees The ABS movement direction in the unit of degree is designated. 0: Shortcut (direction setting invalid) 1: ABS clockwise 2: ABS counterclockwise

The positioning is carried out in a clockwise/counterclockwise direction depending on the software stroke limit range setting method. Because of this, positioning with "shortcut control" may not be possible.

When the current value is moved from 0° to 315°, positioning is carried out in the clockwise direction if the software stroke limit lower limit value is 0° and the upper limit value is 345°.
POINT Positioning addresses are within a range of 0° to 359.99999°. Use the incremental system to carry out positioning of one rotation or more.

POINT Positioning of 360° or more can be carried out with the incremental system. At this time, set as shown below to invalidate the software stroke limit.
[Software stroke limit upper limit value = Software stroke limit lower limit value]

Meaning of interpolation control
In "2-axis linear interpolation control", "3-axis linear interpolation control", "4-axis linear interpolation control", "2-axis fixed-feed control", "3-axis fixed-feed control", "4-axis fixed-feed control", “2-axis speed control”, “3-axis speed control”, “4-axis speed control”, and "2-axis circular interpolation control", control is carried out so that linear and arc paths are drawn using a motor set in two to four axis directions. This kind of control is called "interpolation control". In interpolation control, the axis in which the control system is set is defined as the "reference axis", and the other axis is defined as the "interpolation axis". The QD75 controls the "reference axis" following the positioning data set in the "reference axis", and controls the "interpolation axis" corresponding to the reference axis control so that a linear or arc path is drawn. The following table shows the reference axis and interpolation axis combinations.
Axis definition Axis set to interpolation control in " Da.2 Control method"
Reference axis Interpolation axis
2-axis linear interpolation control, "2-axis fixed-feed control, 2-axis circular interpolation control, 2-axis speed control
"Axes to be interpolated" set in reference axis
Any of axes 1, 2, 3, and 4
Axis 1 Axis 2, Axis 3
Axis 3 Axis 4, Axis 1 3-axis linear interpolation control, "3-axis fixed-feed control, 3-axis speed control
Axis 2 Axis 3, Axis 4
Axis 4 Axis 1, Axis 2
Axis 1 Axis 2, Axis 3, Axis 4
Axis 3 Axis 4, Axis 1, Axis 2 4-axis linear interpolation control, "4-axis fixed-feed control, 4-axis speed control
Axis 2 Axis 3, Axis 4, Axis 1
Axis 4 Axis 1, Axis 2, Axis 3

When carrying out interpolation control, the same positioning data Nos. are set for the "reference axis" and the "interpolation axis". The following table shows the "positioning data" setting items for the reference axis and interpolation axis.
Axis Setting item Reference axis setting item Interpolation axis setting item
Da.1 Operation pattern –
Linear 2, 3, 4, Fixed-feed 2, 3, 4, Circular sub, Circular right, Circular left Forward run speed 2, 3, 4 Reverse run speed 2, 3, 4
Da.2 Control system
Da.3 Acceleration time No. –
Same positioning data Nos
Da.4 Deceleration time No. –
Da.5 Axis to be
interpolated. –
Da.6 Positioning address/
Forward run speed 2, 3, and 4. Reverse run speed 2, 3, and 4 not required.
Forward run speed 2, 3, and 4. Reverse run speed 2, 3, and 4 not required.
Da.7 Arc address (Only during circular sub, circular right, and circular left).
(Only during circular sub, circular right, and circular left).
Da.8 Command speed Only during forward run speed 2, 3, 4 and reverse run speed 2, 3, 4.
Da.9 Dwell time –
Da.10 M code –
: Setting always required : Set according to requirements (Set to "–" when not used.) : Setting restrictions exist – : Setting not required (Unrelated setting item, so any setting value will be ignored. Use the initial
value or a value within the setting range.) : For 2-axis interpolation, the partner axis is set. If the self-axis is set, an error "Illegal interpolation
description command (error code: 521)" will occur. For 3- and 4-axis interpolation, the axis setting is not required. : Refer to Section 5.3 "List of positioning data" for information on the setting details.
movement amount

The positioning data Nos. of the reference axis (axis in which interpolation control was set in " Da.2 Control system") are started when starting the interpolation
control. (Starting of the interpolation axis is not required.) The following errors or warnings will occur and the positioning will not start if both reference axis and the interpolation axis are started.
operation (warning code: 100).
When carrying out interpolation control in which "continuous positioning control" and "continuous path control" are designated in the operation pattern, the positioning method for all positioning data from the started positioning data to the positioning data in which "positioning complete" is set must be set to interpolation control. The QD75 may malfunction if a control system other than interpolation control is set.
Either the "composite speed" or "reference axis speed" can be designated as the speed during interpolation control. ( Pr.20 Interpolation speed designation method)
(1) If a stepping motor is used, the circular interpolation control cannot be carried
out. Ensure to use a servomotor when the circular interpolation control is carried out. (2) If either of the axes exceeds the " Pr.8 Speed limit value" in the 2 to 4 axes
speed control, the axis which exceeded the speed limit value is controlled by the speed limit value. For the other axes which perform interpolation, the speed can be suppressed by the ratio of a command speed. If the reference axis exceeds " Pr.8 Speed limit value" during 2- to 4-axis
linear interpolation control, 2- to 4-axis fixed-feed control or 2-axis circular interpolation control, the reference axis is controlled at the speed limit value. (The speed limit does not function on the interpolation axis side.) (3) In 2-axis interpolation, you cannot change the combination of interpolated axes
midway through operation.


reference axis, the major axis side speed may exceed the " Pr.8 Speed limit
There are limits to the interpolation control that can be executed and speed ( Pr.20 Interpolation speed designation method) that can be set, depending on
the " Pr.1 Unit setting" of the reference axis and interpolation axis. (For example,
circular interpolation control cannot be executed if the reference axis and interpolation axis units differ.) The following table shows the interpolation control and speed designation limits.

Reference axis and interpolation axis units are the same, or a combination of "mm" and "inch".
Composite speed Linear 2 (ABS, INC) Fixed-feed 2 Reference axis speed
Composite speed 2 Circular sub (ABS, INC) Circular right (ABS, INC) Circular left (ABS, INC) Reference axis speed
Composite speed Linear 3 (ABS, INC) Fixed-feed 3 Reference axis speed
Composite speed Linear 4 (ABS, INC) Fixed-feed 4 Reference axis speed
: Setting possible, : Setting not possible. 1 "mm" and "inch" unit mix possible. 2 "degree" setting not possible. A "Circular interpolation not possible (error code: 535)" will occur and the position cannot start if circular interpolation control is set when the unit is "degree". The machine will immediately stop if "degree" is set during positioning control. 3 The unit set in the reference axis will be used for the speed unit during control if the units differ or if "mm" and "inch" are combined.
"In interpolation" will be stored in the " Md.26 Axis operation status" during
interpolation control. "Standing by" will be stored when the interpolation operation is terminated. Both the reference axis and interpolation axis will carry out a deceleration stop if an error occurs during control, and "error occurring" will be stored in the operation status.

9.2.1 Relation between each control and positioning data
The setting requirements and details for the setting items of the positioning data to be set differ according to the " Da.2 Control system".
The following table shows the positioning data setting items corresponding to the different types of control. Details and settings for the operation of each control are shown in Section 9.2.2 and subsequent sections. (In this section, it is assumed that the positioning data setting is carried out using GX Configurator-QP.)
Position control Speed control Major positioning control
1-axis linear control 2-axis linear interpolation control 3-axis linear interpolation control 4-axis linear interpolation control
1-axis fixed-feed control 2-axis fixed-feed control 3-axis fixed-feed control 4-axis fixed-feed control
2-axis circular interpolation control
1-axis, 2-axis, 3-axis, 4-axis Speed control
Positioning data setting items
Continuous positioning control Da.1 Operation
Forward run speed 1 Reverse run speed 1 Forward run speed 2 Reverse run speed 2 Forward run speed 3 Reverse run speed 3 Forward run speed 4 Reverse run speed 4
Forward run speed/posi- tion Reverse run speed/posi- tion
Linear 1 Linear 2 Linear 3 Linear 4
Fixed-feed 1 Fixed-feed 2 Fixed-feed 3 Fixed-feed 4
Circular sub Circular right Circular left
Da.2 Control system
Da.3 Acceleration time No.
Da.4 Deceleration time No.
Da.6 Positioning address/movement
Da.7 Arc address –
Da.8 Command speed
Da.9 Dwell time
Da.10 M code
: Always set : Set as required ("–" when not set) : Setting not possible (If setting is made, an error (error code: 516) will occur at a start.) – : Setting not required (Setting value is invalid. Use the initial values or setting values within a range where no error occurs.)
: The "ABS (absolute) system" or "INC (incremental) system" can be used for the control system.


Continuous positioning control – Da.1 Operation
Da.3 Acceleration time No. – Da.4 Deceleration time No. – Da.5 Axis to be interpolated –
Da.7 Arc address – Da.8 Command speed –
: Always set : Set as required ("–" when not set) : Setting not possible (If setting is made, an error (error code: 515) will occur.) – : Setting not required (Setting value is invalid. Use the initial values or setting values within a range where no error occurs.)
![Page 327 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] 1-axis linear control (ABS linear 1)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-327.webp?w=400)
In "1-axis linear control" (" Da.2 Control system" = ABS linear 1, INC linear 1), one
motor is used to carry out position control in a set axis direction.
Operation chart
In absolute system 1-axis linear control, addresses established by a machine OPR are used. Positioning is carried out from the current stop position (start point address) to the address (end point address) set in " Da.6 Positioning
address/movement amount".
![Mitsubishi Electronics MELSEC-Q QD75D — [1] 1-axis linear control (ABS linear 1) diagram (page 327)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-327-1.webp)
When the start point address (current stop position) is 1000, and the end point address (positioning address) is 8000, positioning is carried out in the positive direction for a movement amount of 7000 (8000-1000)
The following table shows setting examples when "1-axis linear control (ABS linear 1)" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern Positioning
Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system ABS linear 1 Set absolute system 1-axis linear control.
Da.3 Acceleration time
No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the
Axis 1 Positioning data No. 1
acceleration time at start.
Da.4 Deceleration time
No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the
deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required (setting value will be ignored).
Da.6 Positioning address/
movement amount 8000.0µm Set the positioning address. (Assuming "mm" is set in " Pr.1 Unit
setting".)
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00mm/min Set the speed during movement to the positioning address.
Da.9 Dwell time 500ms Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete

Operation chart
In incremental system 1-axis linear control, addresses established by a machine OPR are used. Positioning is carried out from the current stop position (start point
address) to a position at the end of the movement amount set in " Da.6
Positioning address/movement amount". The movement direction is determined by the sign of the movement amount.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] 1-axis linear control (INC linear 1) diagram (page 328)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-328-1.webp)
When the start point address is 5000, and the movement amount is -7000, positioning is carried out to the -2000 position.
Address after positioning control Start point address (current stop position)
Positioning control in the reverse direction (movement amount -7000)
The following table shows setting examples when "1-axis linear control (INC linear 1)" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern Positioning
Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system INC linear 1 Set incremental system 1-axis linear control.
Da.3 Acceleration time
No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time
No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required (setting value will be ignored).
Da.6 Positioning address/
movement amount -7000.0µm Set the movement amount. (Assuming "mm" is set in " Pr.1 Unit setting".)
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00mm/min Set the speed during movement.
Da.9 Dwell time 500ms Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete
![Page 329 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] 2-axis linear interpolation control (ABS linear 2)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-329.webp?w=400)
In "2-axis linear interpolation control" (" Da.2 Control system" = ABS linear 2, INC
linear 2), two motors are used to carry out position control in a linear path while carrying out interpolation for the axis directions set in each axis. (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
Operation chart
In absolute system 2-axis linear control, addresses established by a machine OPR on a 2-axis coordinate plane are used. Linear interpolation positioning is carried out from the current stop position (start point address) to the address (end point address) set in " Da.6 Positioning address/movement amount".
Forward direction (Y axis)
![Mitsubishi Electronics MELSEC-Q QD75D — [1] 2-axis linear interpolation control (ABS linear 2) diagram (page 329)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-329-1.webp)
Start point address (X1,Y1) (current stop position)
Movement by linear interpolation of the X axis and Y axis
![Mitsubishi Electronics MELSEC-Q QD75D — [1] 2-axis linear interpolation control (ABS linear 2) diagram (page 329)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-329-2.webp)
When the start point address (current stop position) is (1000, 1000) and the end point address (positioning address) is (10000, 4000), positioning is carried out as follows.
Reverse direction

An error will occur and the positioning will not start in the following cases. The machine will immediately stop if the error is detected during a positioning control. • If the movement amount of each axis exceeds "1073741824 (=230)" when "0: Composite speed" is set in " Pr.20 Interpolation speed designation method" ... The "Outside linear movement amount range error (error code: 504)" occurs
at a positioning start. (The maximum movement amount that can be set in " Da.6 Positioning
address/movement amount" is "1073741824 (=230)".)
[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis linear interpolation control (ABS linear 2)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system ABS linear 2 – Set absolute system 2-axis linear interpolation control.
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as
the acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as
the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
movement amount 10000.0 µm 4000.0 µm Set the end point address. (Assuming "mm" is set in
Da.6 Positioning address/
" Pr.1 Unit setting".)
Da.7 Arc address – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – Set the speed during movement to the end point address.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.

the reference axis, the major axis side speed may exceed the " Pr.8 Speed limit
![Page 331 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] 2-axis linear interpolation control (INC linear 2)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-331.webp?w=400)
Operation chart
In incremental system 2-axis linear interpolation control, addresses established by a machine OPR on a 2-axis coordinate plane are used. Linear interpolation positioning is carried out from the current stop position (start point address) to a position at the end of the movement amount set in " Da.6 Positioning
address/movement amount". The movement direction is determined by the sign of the movement amount.
Forward direction (Y axis)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] 2-axis linear interpolation control (INC linear 2) diagram (page 331)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-331-1.webp)
Start point address (X1,Y1) (current stop position)
Movement by linear interpolation positioning of the X axis and Y axis
![Mitsubishi Electronics MELSEC-Q QD75D — [2] 2-axis linear interpolation control (INC linear 2) diagram (page 331)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-331-2.webp)
When the axis 1 movement amount is 9000 and the axis 2 movement amount is -3000, positioning is carried out as follows.
Reverse direction

An error will occur and the positioning will not start in the following cases. The machine will immediately stop if the error is detected during a positioning operation. • If the movement amount of each axis exceeds "1073741824 (=230)" when "0: Composite speed" is set in " Pr.20 Interpolation speed designation method" ... The "Outside linear movement amount range error (error code: 504)" occurs
at a positioning start. (The maximum movement amount that can be set in " Da.6 Positioning
address/movement amount" is "1073741824 (=230)".)
[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis linear interpolation control (INC linear 2)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system INC linear 2 – Set incremental system 2-axis linear interpolation control.
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as the acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
Set the movement amount. (Assuming "mm" is set in
Da.6 Positioning address/
movement amount 9000.0 µm -3000.0 µm
" Pr.1 Unit setting".)
Da.7 Arc address – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – Set the speed during movement.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.

the reference axis, the major axis side speed may exceed the " Pr.8 Speed limit
![Page 333 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] 3-axis linear interpolation control (ABS linear 3)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-333.webp?w=400)
In "3-axis linear interpolation control" (" Da.2 Control system" = ABS linear 3, INC
linear 3), three motors are used to carry out position control in a linear path while carrying out interpolation for the axis directions set in each axis. (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
Operation chart
In the absolute system 3-axis linear control, using an address established by a machine OPR in the 3-axis coordinate space, a linear interpolation positioning is carried out from the current stop position (start point address) to the address (end point address) set in the " Da.6 Positioning address/movement amount".
![Mitsubishi Electronics MELSEC-Q QD75D — [1] 3-axis linear interpolation control (ABS linear 3) diagram (page 333)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-333-1.webp)
End point address (X2,Y2,Z2)
Movement by linear interpolation of the X axis, Y axis and Z axis
Y axis movement amount
Forward direction (Z axis)
Start point address (X1,Y1,Z1) (Current stop position)
Forward direction (X axis)
Reverse direction Reverse direction
![Mitsubishi Electronics MELSEC-Q QD75D — [1] 3-axis linear interpolation control (ABS linear 3) diagram (page 333)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-333-2.webp)
When the start point address (current stop positon) is (1000, 2000, 1000) and the end point address (positioning address) is (4000, 8000, 4000), positioning is carried out as follows.

An error will occur and the positioning will not start in the following cases. The machine will immediately stop if the error is detected during a positioning control. • If the movement amount of each axis exceeds "1073741824 (=230)" when "0: Composite speed" is set in " Pr.20 Interpolation speed designation method" ... The "Outside linear movement amount range error (error code: 504)" occurs
at a positioning start. (The maximum movement amount that can be set in " Da.6 Positioning
address/movement amount" is "1073741824 (=230)".)
[Reference axis is designated as axis 1.] The following table shows setting examples when "3-axis linear interpolation control (ABS linear 3)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2 and axis 3.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system ABS linear 3 – – Set absolute system 3-axis linear interpolation control.
Designate the value set in " Pr.25
Da.3 Acceleration time
No. 1 – –
Acceleration time 1" as the acceleration time at start.
Designate the value set in " Pr.10
Da.4 Deceleration time
Axis 1 Positioning data No. 1
No. 0 – –
Deceleration time 0" as the deceleration time at deceleration.
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2 and 3.
Da.5 Axis to be
interpolated – – –
movement amount 4000.0 µm 8000.0 µm 4000.0 µm Set the end point address. (Assuming "mm" is
Da.6 Positioning address/
set in " Pr.1 Unit setting".)
Da.7 Arc address – – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – – Set the speed during movement to the end point address.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms – –
Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Da.10 M code 10 – –
Refer to Section 5.3 "List of positioning data" for information on the setting details.

the reference axis, the major axis side speed may exceed the " Pr.8 Speed limit
value".
![Page 336 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] 3-axis linear interpolation control (INC linear 3)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-336.webp?w=400)
Operation chart
In the incremental system 3-axis linear interpolation control, using an address established by a machine OPR in the 3-axis coordinate space, a linear interpolation positioning is carried out from the current stop position (start point address) to a position at the end of the movement amount set in the " Da.6
Positioning address/movement amount". The movement direction depends on the sign (+ or -) of the movement amount.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] 3-axis linear interpolation control (INC linear 3) diagram (page 336)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-336-1.webp)
Movement by linear interpolation positioning of the X axis, Y axis and Z axis
Z axis movement amount
Start point address (X1, Y1, Z1) (current stop position)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] 3-axis linear interpolation control (INC linear 3) diagram (page 336)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-336-2.webp)
When the axis 1 movement amount is 10000, the axis 2 movement amount is 5000 and the axis 3 movement amount is 6000, positioning is carried out as follows.

An error will occur and the positioning will not start in the following cases. The machine will immediately stop if the error is detected during a positioning operation. • If the movement amount of each axis exceeds "1073741824 (=230)" when "0: Composite speed" is set in " Pr.20 Interpolation speed designation method" ... The "Outside linear movement amount range error (error code: 504)" occurs
at a positioning start. (The maximum movement amount that can be set in " Da.6 Positioning
address/movement amount" is "1073741824 (=230)".)
[Reference axis is designated as axis 1.] The following table shows setting examples when "3-axis linear interpolation control (INC linear 3)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2 and axis 3.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system INC linear 3 – – Set incremental system 3-axis linear interpolation control.
Designate the value set in " Pr.25
Da.3 Acceleration time
No. 1 – –
Acceleration time 1" as the acceleration time at start.
Designate the value set in " Pr.10
Da.4 Deceleration time
Axis 1 Positioning data No. 1
No. 0 – –
Deceleration time 0" as the deceleration time at deceleration.
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2 and 3.
Da.5 Axis to be
interpolated – – –
movement amount 10000.0 µm 5000.0 µm 6000.0 µm Set the movement amount. (Assuming "mm"
Da.6 Positioning address/
is set in " Pr.1 Unit setting".)
Da.7 Arc address – – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – – Set the speed during movement.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms – –
Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Da.10 M code 10 – –
Refer to Section 5.3 "List of positioning data" for information on the setting details.

(1) When the "reference axis speed" is set during 3-axis linear intrpolation control,
set so the major axis side becomes the reference axis. If the minor axis side is
set as the reference axis, the major axis side speed may exceed the " Pr.8
Speed limit value". (2) Refer to Section 9.1.6 "Interpolation control" for the reference axis and
interpolation axis combinations.

In "4-axis linear interpolation control" (" Da.2 Control system" = ABS linear 4, INC
linear 4), four motors are used to carry out position control in a linear path while carrying out interpolation for the axis directions set in each axis. (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
In the absolute system 4-axis linear control, using an address established by a machine OPR in the 4-axis coordinate space, a linear interpolation positioning is carried out from the current stop position (start point address) to the address (end point address) set in the " Da.6 Positioning address/movement amount".
An error will occur and the positioning will not start in the following cases. The machine will immediately stop if the error is detected during a positioning control. • If the movement amount of each axis exceeds "1073741824 (=230)" when "0: Composite speed" is set in " Pr.20 Interpolation speed designation method" ... The "Outside linear movement amount range error (error code: 504)" occurs
at a positioning start. (The maximum movement amount that can be set in " Da.6 Positioning
address/movement amount" is "1073741824 (=230)".)

[Reference axis is designated as axis 1.] The following table shows setting examples when "4-axis linear interpolation control (ABS linear 4)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2, axis 3 and axis 4.)
Axis 1 (reference axis) setting
Set "Positioning complete" assuming the next positioning data will not be executed.
Da.1 Operation pattern Positioning
complete – – –
Da.2 Control system ABS linear 4 – – – Set absolute system 4-axis linear interpolation control.
Designate the value set in
Da.3 Acceleration time
" Pr.25 Acceleration time 1" as the acceleration time at start.
No. 1 – – –
Designate the value set in
" Pr.10 Deceleration time 0" as the deceleration time at deceleration.
Da.4 Deceleration time
No. 0 – – –
Axis 1 Positioning data No. 1
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2, 3 and 4.
Da.5 Axis to be
interpolated –
Set the end point address. (Assuming "mm" is set in
Da.6 Positioning address/
movement amount 4000.0 µm 8000.0 µm 4000.0 µm 3000.0 µm
" Pr.1 Unit setting".)
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – – – Set the speed during movement to the end point address.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms – – –
Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Da.10 M code 10 – – –
Refer to Section 5.3 "List of positioning data" for information on the setting details.

the reference axis, the major axis side speed may exceed the " Pr.8 Speed limit

Operation chart
In the incremental system 4-axis linear interpolation control, using an address established by a machine OPR in the 4-axis coordinate plane, a linear interpolation positioning is carried out from the current stop position (start point address) to a position at the end of the movement amount set in the " Da.6 Positioning
address/movement amount". The movement direction depends on the sign (+ or -) of the movement amount.
An error will occur and the positioning will not start in the following cases. The machine will immediately stop if the error is detected during a positioning operation. • If the movement amount of each axis exceeds "1073741824 (=230)" when "0: Composite speed" is set in " Pr.20 Interpolation speed designation method" ... The "Outside linear movement amount range error (error code: 504)" occurs
at a positioning start. (The maximum movement amount that can be set in " Da.6 Positioning
address/movement amount" is "1073741824 (=230)".)

[Reference axis is designated as axis 1.] The following table shows setting examples when "4-axis linear interpolation control (INC linear 4)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2, axis 3 and axis 4.)
Axis 1 (reference axis) setting
Set "Positioning complete" assuming the next positioning data will not be executed.
Da.1 Operation pattern Positioning
complete – – –
Da.2 Control system INC linear 4 – – – Set incremental system 4-axis linear interpolation control.
Designate the value set in
Da.3 Acceleration time
No. 1 – – –
" Pr.25 Acceleration time 1"
as the acceleration time at start.
Designate the value set in
Da.4 Deceleration time
" Pr.10 Deceleration time 0"
No. 0 – – –
as the deceleration time at deceleration.
Axis 1 Positioning data No. 1
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2, 3 and 4.
Da.5 Axis to be
interpolated –
Set the movement amount. (Assuming "mm" is set in
Da.6 Positioning address/
movement amount 4000.0 µm 8000.0 µm 4000.0 µm 3000.0 µm
" Pr.1 Unit setting".)
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – – – Set the speed during movement.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms – – –
Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Da.10 M code 10 – – –
Refer to Section 5.3 "List of positioning data" for information on the setting details.

(1) When the "reference axis speed" is set during 4-axis linear interpolation control,
set so the major axis side becomes the reference axis. If the minor axis side is
set as the reference axis, the major axis side speed may exceed the " Pr.8
Speed limit value". (2) Refer to Section 9.1.6 "Interpolation control" for the reference axis and

In "1-axis fixed-feed control" (" Da.2 Control system" = fixed-feed 1), one motor is
used to carry out fixed-feed control in a set axis direction. In fixed-feed control, any remainder of the movement amount designated in the positioning data is rounded down if less than that required for control accuracy to output the same amount of pulses. (The remainder of the movement amount with an accuracy below the control accuracy does not affect the regular controls.)
In 1-axis fixed-feed control, the address ( Md.20 Current feed value) of the current
stop position (start point address) is set to "0". Positioning is then carried out to a position at the end of the movement amount set in " Da.6 Positioning
address/movement amount". The movement direction is determined by the movement amount sign.
" Md. 20 Current feed value" is set to "0" at the positioning start
0
Designated movement Positioning start
Reverse direction Forward direction
a negative movement amount
a positive movement amount
(1) An axis error "Continuous path control not possible (error code: 516)" will
occur and the operation cannot start if "continuous path control" is set in " Da.1 Operation pattern". ("Continuous path control" cannot be set in fixed-
feed control.) (2) "Fixed-feed" cannot be set in " Da.2 Control system" in the positioning data
when "continuous path control" has been set in " Da.1 Operation pattern" of
the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", fixed-feed control cannot be set in positioning data No. 2.) An axis error "Continuous path control not possible (error code: 516)" will occur and the machine will carry out a deceleration stop if this type of setting is carried out.

The following table shows setting examples when "1-axis fixed-feed control (fixed- feed 1)" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern Positioning
Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system Fixed-feed 1 Set 1-axis fixed-feed control.
Da.3 Acceleration time
No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the
Axis 1 Positioning data No. 1
acceleration time at start.
Da.4 Deceleration time
No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the
deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required (setting value will be ignored).
movement amount 8000.0µm Set the positioning address. (Assuming "mm" is set in " Pr.1 Unit
Da.6 Positioning address/
setting".)
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00mm/min Set the speed during movement to the positioning address.
Da.9 Dwell time 500ms Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
* Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete

In "2-axis fixed-feed control" (" Da.2 Control system" = fixed-feed 2), two motors are
used to carry out fixed-feed control in a linear path while carrying out interpolation for the axis directions set in each axis. In fixed-feed control, any remainder of the movement amount designated in the positioning data is rounded down if less than that required for control accuracy to output the same amount of pulses. (The remainder of the movement amount with an accuracy below the control accuracy does not affect the regular controls.) (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
In incremental system 2-axis fixed-feed control, the addresses ( Md.20 Current
feed value) of the current stop position (start addresses) of both axes are set to "0". Linear interpolation positioning is then carried out from that position to a position at the end of the movement amount set in " Da.6 Positioning
address/movement amount". The movement direction is determined by the sign of the movement amount.
" Md. 20 Current feed value" of each axis is set to "0" at the positioning start
(1) An axis error "Continuous path control not possible (error code: 516)" will
occur and the operation cannot start if "continuous path control" is set in " Da.1 Operation pattern". ("Continuous path control" cannot be set in fixed-
feed control.) (2) If the movement amount of each axis exceeds "1073741824 (=230)" when "0:
Composite speed" is set in " Pr.20 Interpolation speed designation method", the "Outside linear movement amount range error (error code: 504)" occurs at a positioning start and positioning cannot be started. (The maximum movement amount that can be set in " Da.6 Positioning address/movement
amount" is "1073741824 (= 230)". (3) "Fixed-feed" cannot be set in " Da.2 Control system" in the positioning data
when "continuous path control" has been set in " Da.1 Operation pattern" of
the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", fixed-feed control cannot be set in positioning data No. 2.) An axis error "Continuous path control not possible (error code: 516)" will occur and the machine will carry out a deceleration stop if this type of setting is carried out.

[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis fixed-dimension feed control (fixed-feed 2)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control method Fixed-feed 2 – Set 2-axis fixed-feed control.
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as
the acceleration time at start.
Da.4 Deceleration time
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as
Axis 1 Positioning data No. 1
the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
Da.6 Positioning address/
movement amount 8000.0 µm 6000.0 µm Set the positioning address. (Assuming "mm" is set in
" Pr.1 Unit setting".)
Da.7 Arc address – – Setting not required (setting value will be ignored).
Set the speed during movement. (Designate the composite
Da.8 Command speed 6000.00 mm/min –
speed of reference axis speed in " Pr.20 Interpolation
speed designation method".)
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
* Refer to Section 5.3 "List of positioning data" for information on the setting details.

speed may exceed the " Pr.8 Speed limit value".

In "3-axis fixed-feed control" (" Da.2 Control system" = fixed-feed 3), three motors are
used to carry out fixed-feed control in a linear path while carrying out interpolation for the axis directions set in each axis. In fixed-feed control, any remainder of the movement amount designated in the positioning data is rounded down if less than that required for control accuracy to output the same amount of pulses. (The remainder of the movement amount with an accuracy below the control accuracy does not affect the regular controls.) (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)

In incremental system 3-axis fixed-feed control, the addresses ( Md.20 Current
feed value) of the current stop position (start addresses) of every axes are set to "0". Linear interpolation positioning is then carried out from that position to a position at the end of the movement amount set in " Da.6 Positioning
address/movement amount". The movement direction is determined by the sign of the movement amount.

" Current feed value" of each axis is set to "0" at the positioning start.
X axis

(1) An axis error "Continuous path control not possible (error code: 516)" will
occur and the operation cannot start if "continuous path control" is set in " Da.1 Operation pattern". ("Continuous path control" cannot be set in fixed-
feed control.) (2) If the movement amount of each axis exceeds "1073741824 (=230)" when "0:
Composite speed" is set in " Pr.20 Interpolation speed designation method", the "Outside linear movement amount range error (error code: 504)" occurs at a positioning start and positioning cannot be started. (The maximum movement amount that can be set in " Da.6 Positioning address/movement
amount" is "1073741824 (= 230)". (3) "Fixed-feed" cannot be set in " Da.2 Control system" in the positioning data
when "continuous path control" has been set in " Da.1 Operation pattern" of
the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", fixed-feed control cannot be set in positioning data No. 2.) An axis error "Continuous path control not possible (error code: 516)" will occur and the machine will carry out a deceleration stop if this type of setting is carried out.
[Reference axis is designated as axis 1.] The following table shows setting examples when "3-axis fixed-feed control (fixed- feed 3)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2 and axis 3.)

Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control method Fixed-feed 3 – – Set 3-axis fixed-feed control.
Designate the value set in " Pr.25
Da.3 Acceleration time
No. 1 – –
Acceleration time 1" as the acceleration time at start.
Designate the value set in " Pr.10
Da.4 Deceleration time
Axis 1 Positioning data No. 1
No. 0 – –
Deceleration time 0" as the deceleration time at deceleration.
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2 and 3.
Da.5 Axis to be
interpolated – – –
movement amount 10000.0 µm 5000.0 µm 6000.0 µm Set the positioning address. (Assuming "mm"
Da.6 Positioning address/
is set in " Pr.1 Unit setting".)
Da.7 Arc address – – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – – Set the speed during movement.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms – –
Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Da.10 M code 10 – –
Refer to Section 5.3 "List of positioning data" for information on the setting details.

(1) When the "reference axis speed" is set during 3-axis fixed-feed control, set so the major axis side
becomes the reference axis. If the minor axis side is set as the reference axis, the major axis side
speed may exceed the " Pr.8 Speed limit value".
(2)Refer to Section 9.1.6 "Interpolation control" for the reference axis and interpolation axis

In "4-axis fixed-feed control" (" Da.2 Control system" = fixed-feed 4), four motors are
used to carry out fixed-feed control in a linear path while carrying out interpolation for the axis directions set in each axis. In fixed-feed control, any remainder of the movement amount designated in the positioning data is rounded down if less than that required for control accuracy to output the same amount of pulses. (The remainder of the movement amount with an accuracy below the control accuracy does not affect the regular controls.) (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
In incremental system 4-axis fixed-feed control, the addresses ( Md.20 Current
feed value) of the current stop position (start addresses) of every axes are set to "0". Linear interpolation positioning is then carried out from that position to a position at the end of the movement amount set in " Da.6 Positioning
address/movement amount". The movement direction is determined by the sign of the movement amount.
(1) An axis error "Continuous path control not possible (error code: 516)" will
occur and the operation cannot start if "continuous path control" is set in " Da.1 Operation pattern". ("Continuous path control" cannot be set in fixed-
feed control.) (2) "Fixed-feed" cannot be set in " Da.2 Control system" in the positioning data
when "continuous path control" has been set in " Da.1 Operation pattern" of
the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", fixed-feed control cannot be set in positioning data No. 2.) An axis error "Continuous path control not possible (error code: 516)" will occur and the machine will carry out a deceleration stop if this type of setting is carried out.

[Reference axis is designated as axis 1.] The following table shows setting examples when "4-axis fixed-feed control (fixed- feed 4)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2, axis 3 and axis 4.)
Axis 1 (reference axis) setting
Set "Positioning complete" assuming the next positioning data will not be executed.
Da.1 Operation pattern Positioning
complete – – –
Da.2 Control method Fixed-feed 4 – – – Set 4-axis fixed-feed control.
Designate the value set in
Da.3 Acceleration time
No. 1 – – –
" Pr.25 Acceleration time 1"
as the acceleration time at start.
Designate the value set in
" Pr.10 Deceleration time 0"
Da.4 Deceleration time
No. 0 – – –
as the deceleration time at deceleration.
Axis 1 Positioning data No. 1
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2, 3 and 4.
Da.5 Axis to be
interpolated –
Set the positioning address. (Assuming "mm" is set in
Da.6 Positioning address/
movement amount 4000.0 µm 8000.0 µm 4000.0 µm 3000.0 µm
" Pr.1 Unit setting".)
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min – – – Set the speed during movement.
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms – – –
Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Da.10 M code 10 – – –
Refer to Section 5.3 "List of positioning data" for information on the setting details.

(1) For 4-axis fixed-feed control, set the "reference axis speed" and make setting so that the major
axis side becomes the reference axis. If the minor axis side is set as the reference axis, the major
axis side speed may exceed the " Pr.8 Speed limit value".
(2)Refer to Section 9.1.6 "Interpolation control" for the reference axis and interpolation axis

In "2-axis circular interpolation control" (" Da.2 Control system" = ABS circular sub,
INC circular sub), two motors are used to carry out position control in an arc path passing through designated sub points, while carrying out interpolation for the axis directions set in each axis. (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
circular sub)
Operation chart
In the absolute system, 2-axis circular interpolation control with sub point designation, addresses established by a machine OPR on a 2-axis coordinate plane are used. Positioning is carried out from the current stop position (start point address) to the address (end point address) set in " Da.6 Positioning
address/movement amount", in an arc path that passes through the sub point address set in " Da.7 Arc address".
The resulting control path is an arc having as its center the intersection point of perpendicular bisectors of a straight line between the start point address (current stop position) and sub point address (arc address), and a straight line between the sub point address (arc address) and end point address (positioning address).
Movement by circular interpolation
End point address (arc address)
(current stop position) Reverse direction

(1) 2-axis circular interpolation control cannot be set in the following cases.
and interpolation axis. ("mm" and "inch" combinations are possible.)
(2) An error will occur and the positioning start will not be possible in the following
cases. The machine will immediately stop if the error is detected during positioning control.
... An error "Outside radius range" (error code: 544) will occur at positioning
... A "Sub point setting error" (error code: 525) will occur.
designation method"

[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis circular interpolation control with sub point designation (ABS circular sub)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system ABS circular
sub – Set absolute system, 2-axis circular interpolation control with sub point designation.
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as
the acceleration time at start.
Da.4 Deceleration time
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as
Axis 1 Positioning data No. 1
the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
movement amount 8000.0 µm 6000.0 µm Set the positioning address. (Assuming "mm" is set in
Da.6 Positioning address/
" Pr.1 Unit setting".)
Da.7 Arc address 4000.0 µm 3000.0 µm Set the sub point address. (Assuming that the " Pr.1 Unit
setting" is set to "mm".)
Set the speed when moving to the end point address.
Da.8 Command speed 6000.00 mm/min –
(Designate the composite speed in " Pr.20 Interpolation
speed designation method".)
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.

Set a value in " Da.8 Command speed" so that the speed of each axis does not
exceed the " Pr.8 Speed limit value". (The speed limit does not function for the
![Page 356 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] 2-axis circular interpolation control with sub point designation (INC](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-356.webp?w=400)
circular sub)
In the incremental system, 2-axis circular interpolation control with sub point designation, positioning is carried out from the current stop position (start point address) to a position at the end of the movement amount set in " Da.6
Positioning address/movement amount" in an arc path that passes through the sub point address set in " Da.7 Arc address". The movement direction depends on
the sign (+ or -) of the movement amount. The resulting control path is an arc having as its center the intersection point of perpendicular bisectors of the straight line between the start point address (current stop position) and sub point address (arc address) calculated from the movement amount to the sub point, and a straight line between the sub point address (arc address) and end point address (positioning address) calculated from the movement amount to the end point.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] 2-axis circular interpolation control with sub point designation (INC diagram (page 356)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-356-1.webp)

(1) 2-axis circular interpolation control cannot be set in the following cases.
and interpolation axis. ("mm" and "inch" combinations are possible.)
(2) An error will occur and the positioning start will not be possible in the following
cases. The machine will immediately stop if the error is detected during positioning control.
... An error "Outside radius range" (error code: 544) will occur at positioning
start. • When the auxiliary point address is outside the range of -2147483648 (–231) to 2147483647 (231–1).
... A "Sub point setting error" (error code: 525) will occur.
designation method"

[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis circular interpolation control with sub point designation (INC circular sub)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Da.2 Control system INC circular
sub – Set incremental system, 2-axis circular interpolation control with sub point designation.
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as
the acceleration time at start.
Da.4 Deceleration time
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as
Axis 1 Positioning data No. 1
the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
Da.6 Positioning address/
movement amount 8000.0 µm 6000.0 µm Set the movement amount. (Assuming that the " Pr.1 Unit
setting" is set to "mm".)
Da.7 Arc address 4000.0 µm 3000.0 µm Set the sub point address. (Assuming that the " Pr.1 Unit
setting" is set to "mm".)
Set the speed during movement. (Designate the composite
Da.8 Command speed 6000.00 mm/min –
speed in " Pr.20 Interpolation speed designation
method".)
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.

Set a value in " Da.8 Command speed" so that the speed of each axis does not
exceed the " Pr.8 Speed limit value". (The speed limit does not function for the

In "2-axis circular interpolation control" (" Da.2 Control system" = ABS circular right,
INC circular right, ABS circular left, INC circular left), two motors are used to carry out position control in an arc path having a designated center point, while carrying out interpolation for the axis directions set in each axis. (Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
The following table shows the rotation directions, arc center angles that can be controlled, and positioning paths for the different control systems.


In circular interpolation control with center point designation, the arc path calculated from the start point address and arc address may deviate from the position of the end point address set in " Da.6 Positioning address/movement
amount". (Refer to " Pr.41 Allowable circular interpolation error width".)
(1) Calculated error < " Pr.41 Allowable circular interpolation error width"
Circular interpolation control to the set end point address is carried out while the error compensation is carried out. (This is called "spiral interpolation".)
Path using spiral interpolation
Calculated end point address
Center point address Start point address
In circular interpolation control with center point designation, an angular velocity is calculated on the assumption that operation is carried out at a command speed on the arc using the radius calculated from the start point address and center point address, and the radius is compensated in proportion to the angular velocity deviated from that at the start point. Thus, when there is a difference (error) between a radius calculated from the start point address and center point address (start point radius) and a radius calculated from the end point address and center point address (end point radius), the composite speed differs from the command speed as follows.
Start point radius > End point radius: As compared with the speed without
error, the speed becomes slower as end point address is reached. Start point radius < End point radius: As compared with the speed without
error, the speed becomes faster as end point address is reached.
(2) Calculated error > " Pr.41 Allowable circular interpolation error width"
At the positioning start, an error "Large arc error deviation" (error code: 506) will occur and the control will not start. The machine will immediately stop if the error is detected during positioning control.
Error · End point address
![Page 361 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] 2-axis circular interpolation control with center point designation](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-361.webp?w=400)
(ABS circular right, ABS circular left)
Operation chart
In the absolute system, 2-axis circular interpolation control with center point designation, addresses established by a machine OPR on a 2-axis coordinate plane are used. Positioning is carried out from the current stop position (start point address) to the address (end point address) set in " Da.6 Positioning
address/movement amount", in an arc path having as its center the address (arc address) of the center point set in " Da.7 Arc address".
Movement by circular interpolation Forward direction
End point address Start point address (current stop position)
Forward direction Reverse direction
Positioning of a complete round with a radius from the start point address to the arc center point can be carried out by setting the end point address (positioning address) to the same address as the start point address.
Start point address =
Reverese direction Forward direction

In circular interpolation control with center point designation, an angular velocity is calculated on the assumption that operation is carried out at a command speed on the arc using the radius calculated from the start point address and center point address, and the radius is compensated in proportion to the angular velocity deviated from that at the start point. Thus, when there is a difference (error) between a radius calculated from the start point address and center point address (start point radius) and a radius calculated from the end point address and center point address (end point radius), the composite speed differs from the command speed as follows.
Start point radius > End point radius: As compared with the speed without error,
the speed becomes slower as end point address is reached. Start point radius < End point radius: As compared with the speed without error,
the speed becomes faster as end point address is reached.
(1) 2-axis circular interpolation control cannot be set in the following cases.
and interpolation axis. ("mm" and "inch" combinations are possible.)
(2) An error will occur and the positioning start will not be possible in the following
cases. The machine will immediately stop if the error is detected during positioning control.
... An error "Outside radius range " (error code: 544) will occur at
designation method"

[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis circular interpolation control with center point designation (ABS right arc, ABS left arc)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Set absolute system, 2-axis circular interpolation control with center point designation. (Select clockwise or counterclockwise according to the control.)
Da.2 Control system
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as
the acceleration time at start.
Axis 1 Positioning data No. 1
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as
Da.4 Deceleration time
the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
movement amount 8000.0 µm 6000.0 µm Set the positioning address. (Assuming "mm" is set in
Da.6 Positioning address/
" Pr.1 Unit setting".)
Da.7 Arc address 4000.0 µm 3000.0 µm Set the arc address. (Assuming that the " Pr.1 Unit
setting" is set to "mm".)
Set the speed when moving to the end point address.
Da.8 Command speed 6000.00 mm/min –
(Designate the composite speed in " Pr.20 Interpolation
speed designation method".)
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.

Set a value in " Da.8 Command speed" so that the speed of each axis does not
exceed the " Pr.8 Speed limit value". (The speed limit does not function for the
![Page 364 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] 2-axis circular interpolation control with center point designation](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-364.webp?w=400)
(INC circular right, INC circular left)
Operation chart
In the incremental system, 2-axis circular interpolation control with center point designation, addresses established by a machine OPR on a 2-axis coordinate plane are used. Positioning is carried out from the current stop position (start point address) to a position at the end of the movement amount set in " Da.6
Positioning address/movement amount", in an arc path having as its center the address (arc address) of the center point set in " Da.7 Arc address".
Movement by circular interpolation Forward direction
Start point address (Current stop position)
Movement amount to the end point
Reverse direction Forward direction
Movement amount to the end point Reverse direction
Positioning of a complete round with a radius of the distance from the start point address to the arc center point can be carried out by setting the movement amount to "0".
Movement amount = 0
Reverese direction Forward direction

In circular interpolation control with center point designation, an angular velocity is calculated on the assumption that operation is carried out at a command speed on the arc using the radius calculated from the start point address and center point address, and the radius is compensated in proportion to the angular velocity deviated from that at the start point. Thus, when there is a difference (error) between a radius calculated from the start point address and center point address (start point radius) and a radius calculated from the end point address and center point address (end point radius), the composite speed differs from the command speed as follows.
Start point radius > End point radius: As compared with the speed without error,
the speed becomes slower as end point address is reached. Start point radius < End point radius: As compared with the speed without error,
the speed becomes faster as end point address is reached.
(1) 2-axis circular interpolation control cannot be set in the following cases.
and interpolation axis. ("mm" and "inch" combinations are possible.)
(2) An error will occur and the positioning start will not be possible in the following
cases. The machine will immediately stop if the error is detected during positioning control.
... An error "Outside radius range" (error code: 544) will occur at positioning
designation method"

[Reference axis and interpolation axis are designated as axis 1 and axis 2, respectively.] The following table shows setting examples when "2-axis circular interpolation control with center point designation (INC circular right, INC circular left)" is set in positioning data No. 1 of axis 1. (The required values are also set in positioning data No. 1 of axis 2.)
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Set "Positioning complete" assuming the next positioning data will not be executed.
Set incremental system, 2-axis circular interpolation control with center point designation. (Select clockwise or counterclockwise according to the control.)
Da.2 Control system
Da.3 Acceleration time
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as
the acceleration time at start.
Axis 1 Positioning data No. 1
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as
Da.4 Deceleration time
the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
movement amount 8000.0 µm 6000.0 µm Set the movement amount. (Assuming that the " Pr.1 Unit
Da.6 Positioning address/
setting" is set to "mm".)
Da.7 Arc address 4000.0 µm 3000.0 µm Set the center point address. (Assuming that the " Pr.1
Unit setting" is set to "mm".)
Set the speed when moving to the end point address.
Da.8 Command speed 6000.00 mm/min –
(Designate the composite speed in " Pr.20 Interpolation
speed designation method".)
Set the time the machine dwells after the positioning stop (pulse output stop) to the output of the positioning complete signal.
Da.9 Dwell time 500ms –
Da.10 M code 10 – Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.

Set a value in " Da.8 Command speed" so that the speed of each axis does not
exceed the " Pr.8 Speed limit value". (The speed limit does not function for the

In "1-axis speed control" (" Da.2 Control system" = Forward run: speed 1, Reverse
run: speed 1), control is carried out in the axis direction in which the positioning data has been set by continuously outputting pulses for the speed set in " Da.8 Command
speed" until the input of a stop command. The two types of 1-axis speed control are "Forward run: speed 1" in which the control starts in the forward run direction, and "Reverse run: speed 1" in which control starts in the reverse run direction.
The following chart shows the operation timing for 1-axis speed control with axis 1 as the reference axis. The "in speed control" flag ( Md.31 Status: b0) is turned ON during speed control.
The "Positioning complete signal" is not turned ON.

Does not turn ON even when control is stopped by stop command.
Fig.9.9 1-axis speed control operation timing
Operation chart

The following table shows the " Md.20 Current feed value" during 1-axis speed
control corresponding to the " Pr.21 Current feed value during speed control"
settings.
" Pr.21 Current feed value during speed
Md.20 Current feed value
Speed In speed control In speed control Speed
Current feed value during speed control start is maintained
Current feed value is updated
(a) Current feed value not updated
(b) Current feed value updated (c) Current feed value zero cleared
(1) Set "Positioning complete" in " Da.1 Operation pattern". An axis error
"Continuous path control not possible (error code: 516)" will occur and the operation cannot start if "continuous positioning control" or "continuous path control" is set in " Da.1 Operation pattern".
("Continuous positioning control" and "continuous path control" cannot be set in speed control.) (2) Set the WITH mode in " Pr.18 M code ON signal output timing" when using
an M code. The M code will not be output, and the M code ON signal will not turn ON if the AFTER mode is set. (3) An error "No command speed" (error code: 503) will occur if the current speed
(-1) is set in " Da.8 command speed".
(4) The software stroke limit check will not carried out if the control unit is set to
"degree".

The following table shows the setting examples when "1-axis speed control (forward run: speed 1)" is set in the positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern Positioning
Setting other than "Positioning complete" is not possible in speed control.
Da.2 Control system Forward run
speed 1 Set 1-axis speed control.
Da.3 Acceleration time
No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time
No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required (setting value will be ignored).
Da.6 Positioning address/
movement amount – Setting not required (setting value will be ignored).
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00mm/min Set the speed to be commanded.
Da.9 Dwell time – Setting not required (setting value will be ignored).
Set this when other sub operation commands are issued in combination
Da.10 M code 10
with the No. 1 positioning data. (" Pr.18 M code ON signal output
timing" setting only possible in the WITH mode.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete

In "2-axis speed control" (" Da.2 Control system" = Forward run: speed 2, Reverse
run: speed 2), control is carried out in the 2-axis direction in which the positioning data has been set by continuously outputting pulses for the speed set in " Da.8 Command
speed" until the input of a stop command. The two types of 2-axis speed control are "Forward run: speed 2" in which the control starts in the forward run direction, and "Reverse run: speed 2" in which control starts in the reverse run direction. (Refer to Section 9.1.6 "Interpolation control" for the combination of the reference axis with the interpolation axis.)
The following chart shows the operation timing for 2-axis (axes 1 and 2) speed control with axis 1 as the reference axis. The "in speed control" flag ( Md.31 Status: b0) is turned ON during speed control.
The "positioning complete signal" is not turned ON.

Axis stop signal (stop command) (Either Y4 or Y5)
Fig. 9.10 2-axis speed control operation timing

The following table shows the " Md.20 Current feed value" during 2-axis speed
control corresponding to the " Pr.21 Current feed value during speed control"
settings. (Note that the reference axis setting values are used for parameters.)

Current feed value during speed control start is maintained
(b) Current feed value updated (c) Current feed value zero cleared
(a) Current feed value not updated
(1) Set "Positioning complete" in " Da.1 Operation pattern". An axis error
"Continuous path control not possible (error code: 516)" will occur and the operation cannot start if "continuous positioning control" or "continuous path control" is set. ("Continuous positioning control" and "continuous path control" cannot be set in speed control.) (2) Set the WITH mode in " Pr.18 M code ON signal output timing" when using
an M code. The M code will not be output, and the M code ON signal will not turn ON if the AFTER mode is set. (3) Set the "reference axis speed" in " Pr.20 Interpolation speed designation
method". An "Interpolation mode error (error code: 523)" will occur and the operation cannot start if a composite speed is set. (4) When either of two axes exceeds the speed limit, that axis is controlled with
the speed limit value. The speeds of the other axes are limited at the ratios of " Da.8 Command speed".

With the settings shown above, the operation speed in speed control is as follows. Axis 1: 4000.00 mm/min (Speed is limited by Pr.8 ).
Axis 2: 3000.00 mm/min (Speed is limited at an ratio of an axis 1 command speed to an axis 2 command speed).
(Examples)

(5) An error "No command speed" (error code: 503) occurs if a current speed (-1)
is set in " Da.8 Command speed".
(6) The software stroke limit check is not carried out when the control unit is set to
"degree".
[Setting examples when the reference axis and interpolation axis are designated as axes 1 and 2, respectively.] The following table shows the setting examples when "2-axis speed control (forward run: speed 2)" is set in the positioning data No. 1 of axis 1 (reference axis).
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – Setting other than "Positioning complete" is not possible in speed control.
Da.2 Control system Forward run
speed 2 – Set 2-axis speed control.
No. 1 – Designate the value set in " Pr.25 Acceleration time 1" as the acceleration time at start.
Da.3 Acceleration time
Axis 1 Positioning data No. 1
Da.4 Deceleration time
No. 0 – Designate the value set in " Pr.10 Deceleration time 0" as the deceleration time at deceleration.
Da.5 Axis to be
interpolated 1 – Set the axis to be interpolated (partner axis). If the self-axis is set, an error will occur.
Da.6 Positioning address/
movement amount – – Setting not required (setting value will be ignored).
Da.7 Arc address – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min
3000.00 mm/min Set the speed to be commanded.
Da.9 Dwell time – – Setting not required (setting value will be ignored).
Set this when other sub operation commands are issued in
combination with the No. 1 positioning data. (" Pr.18 M
Da.10 M code 10 –
code ON signal output timing" setting only possible in the WITH mode.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.

In "3-axis speed control" (" Da.2 Control system" = Forward run: speed 3, Reverse
run: speed 3), control is carried out in the 3-axis direction in which the positioning data has been set by continuously outputting pulses for the speed set in " Da.8 Command
speed" until the input of a stop command. The two types of 3-axis speed control are "Forward run: speed 3" in which the control starts in the forward run direction, and "Reverse run: speed 3" in which control starts in the reverse run direction. (Refer to Section 9.1.6 "Interpolation control" for the combination of the reference axis with the interpolation axes.)
The following chart shows the operation timing for 3-axis (axes 1, 2, and 3) speed control with axis 1 as the reference axis. The "in speed control" flag ( Md.31 Status: b0) is turned ON during speed control.
The "positioning complete signal" is not turned ON.

Axis stop signal (stop command) (Either Y4,Y5 or Y6)
Fig. 9.11 3-axis speed control operation timing

The following table shows the " Md.20 Current feed value" during 3-axis speed
control corresponding to the " Pr.21 Current feed value during speed control"
settings. (Note that the reference axis setting values are used for parameters.)
" Pr.21 Current feed value during speed
Md.20 Current feed value
Speed In speed control In speed control Speed
Current feed value during speed control start is maintained
Current feed value is updated
(a) Current feed value not updated
(b) Current feed value updated (c) Current feed value zero cleared
(1) Set "Positioning complete" in " Da.1 Operation pattern". An axis error
"Continuous path control not possible (error code: 516)" will occur and the operation cannot start if "continuous positioning control" or "continuous path control" is set. ("Continuous positioning control" and "continuous path control" cannot be set in speed control.) (2) Set the WITH mode in " Pr.18 M code ON signal output timing" when using
an M code. The M code will not be output, and the M code ON signal will not turn ON if the AFTER mode is set. (3) Set the "reference axis speed" in " Pr.20 Interpolation speed designation
method". An "Interpolation mode error (error code: 523)" will occur and the operation cannot start if a composite speed is set.

(4) When either of three axes exceeds the speed limit, that axis is controlled with
the speed limit value. The speeds of the other axes are limited at the ratios of " Da.8 Command speed".
Axis 1 setting Axis 2 setting Axis 3 setting
Pr.8 Speed limit
value 4000.00mm/min 5000.00mm/min 6000.00mm/min
Da.8 Command
speed 8000.00mm/min 6000.00mm/min 4000.00mm/min
With the settings shown above, the operation speed in speed control is as follows. Axis 1: 4000.00 mm/min (Speed is limited by Pr.8 ).
command speeds). (5) An error "No command speed" (error code: 503) will occur if a current speed
(-1) is set in " Da.8 Command speed".
(6) The software stroke limit check is not carried out when the control unit is set to
"degree".
(Examples) · Axis · Setting item

The following table shows the setting examples when "3-axis speed control (forward run: speed 3)" is set in the positioning data No. 1 of axis 1 (reference axis).
Axis 1 (reference axis) setting
Da.1 Operation pattern Positioning
complete – – Setting other than "Positioning complete" is not possible in speed control.
Da.2 Control system Forward run
speed 3 – – Set 3-axis speed control.
Designate the value set in " Pr.25
Da.3 Acceleration time
No. 1 – –
Acceleration time 1" as the acceleration time at start.
Designate the value set in " Pr.10
Da.4 Deceleration time
No. 0 – –
Axis 1 Positioning data No. 1
Deceleration time 0" as the deceleration time at deceleration.
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2 and 3.
Da.5 Axis to be
interpolated – – –
Da.6 Positioning address/
movement amount – – – Setting not required (setting value will be ignored).
Da.7 Arc address – – – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min
3000.00 mm/min
2000.00 mm/min Set the speed to be commanded.
Da.9 Dwell time – – – Setting not required (setting value will be ignored).
Set this when other sub operation commands are issued in combination with the No. 1
Da.10 M code 10 – –
positioning data. (" Pr.18 M code ON signal
output timing" setting only possible in the WITH mode.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.

In "4-axis speed control" (" Da.2 Control system" = Forward run: speed 4, Reverse
run: speed 4), control is carried out in the 4-axis direction in which the positioning data has been set by continuously outputting pulses for the speed set in " Da.8 Command
speed" until the input of a stop command. The two types of 4-axis speed control are "Forward run: speed 4" in which the control starts in the forward run direction, and "Reverse run: speed 4" in which control starts in the reverse run direction. (Refer to Section 9.1.6 "Interpolation control" for the combination of the reference axis with the interpolation axes.)

The following chart shows the operation timing for 4-axis speed control with axis 1 as the reference axis. The "in speed control" flag ( Md.31 Status: b0) is turned ON during speed control.
The "positioning complete signal" is not turned ON.

Axis stop signal (stop command) (Either Y4,Y5,Y6 or Y7)
Fig. 9.12 4-axis speed control operation timing

The following table shows the " Md.20 Current feed value" during 4-axis speed
control corresponding to the " Pr.21 Current feed value during speed control"
settings. (Note that the reference axis setting values are used for parameters.)
" Pr.21 Current feed value during speed
Md.20 Current feed value
Speed In speed control In speed control Speed
Current feed value during speed control start is maintained
Current feed value is updated
(a) Current feed value not updated
(b) Current feed value updated (c) Current feed value zero cleared
(1) Set "Positioning complete" in " Da.1 Operation pattern". An axis error
"Continuous path control not possible (error code: 516)" will occur and the operation cannot start if "continuous positioning control" or "continuous path control" is set. ("Continuous positioning control" and "continuous path control" cannot be set in speed control.) (2) Set the WITH mode in " Pr.18 M code ON signal output timing" when using
an M code. The M code will not be output, and the M code ON signal will not turn ON if the AFTER mode is set. (3) Set the "reference axis speed" in " Pr.20 Interpolation speed designation
method". An "Interpolation mode error (error code: 523)" will occur and the operation cannot start if a composite speed is set.

(4) When either of four axes exceeds the speed limit, that axis is controlled with
the speed limit value. The speeds of the other axes are limited at the ratios of " Da.8 Command speed".
Pr.8 Speed limit
4000.00mm/ min
5000.00mm/ min
6000.00mm/ min
8000.00mm/ min
Da.8 Command
8000.00mm/ min
6000.00mm/ min
4000.00mm/ min
1500.00mm/ min
With the settings shown above, the operation speed in speed control is as follows. Axis 1: 4000.00 mm/min (Speed is limited by Pr.8 ).
command speeds). (5) An error "No command speed" (error code: 503) will occur if a current speed
(-1) is set in " Da.8 Command speed".
(6) The software stroke limit check is not carried out when the control unit is set to
"degree".

The following table shows the setting examples when "4-axis speed control (forward run: speed 4)" is set in the positioning data No. 1 of axis 1 (reference axis).
Axis 1 (reference axis) setting
Setting other than "Positioning complete" is not possible in speed control.
Da.1 Operation pattern Positioning
complete – – –
Da.2 Control system Forward run
speed 4 – – – Set 4-axis speed control.
Designate the value set in
Da.3 Acceleration time
" Pr.25 Acceleration time 1" as the acceleration time at start.
No. 1 – – –
Designate the value set in
" Pr.10 Deceleration time 0" as the deceleration time at deceleration.
Da.4 Deceleration time
No. 0 – – –
Axis 1 Positioning data No. 1
Setting not required (setting value will be ignored). When axis 1 is used as a reference axis, the interpolation axes are axes 2, 3 and 4.
Da.5 Axis to be
interpolated –
Da.6 Positioning address/
movement amount – Setting not required (setting value will be ignored).
Da.7 Arc address – Setting not required (setting value will be ignored).
Da.8 Command speed 6000.00 mm/min
3000.00 mm/min
2000.00 mm/min
1000.00 mm/min
Set the speed to be commanded.
Da.9 Dwell time – Setting not required (setting value will be ignored).
Set this when other sub operation commands are issued in combination with the No. 1
Da.10 M code 10 – – –
positioning data. (" Pr.18 M
code ON signal output timing" setting only possible in the WITH mode.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.

In "speed-position switching control (INC mode)" (" Da.2 Control system" = Forward
run: speed/position, Reverse run: speed/position), the pulses of the speed set in " Da.8 Command speed" are kept output on the axial direction set to the positioning
data. When the "speed-position switching signal" is input, position control of the movement amount set in " Da.6 Positioning address/movement amount" is exercised.
"Speed-position switching control (INC mode)" is available in two different types: "forward run: speed/position" which starts the axis in the forward run direction and "reverse run: speed/position" which starts the axis in the reverse run direction.
Use the detailed parameter 1 " Pr.150 Speed-position function selection" with regard to the choice for "speed-position switching control (INC mode)".
Buffer memory address Setting item Setting
value Setting details Axis 1 Axis 2 Axis 3 Axis 4
0 Speed-position switching control (INC mode) 34 184 334 484
Pr.150
If the set value is other than 0 and 2, it is regarded as 0 and operation is performed in the
INC mode. For details of the setting, refer to Section 5.2 "List of parameters".
(1) The control is switched over from speed control to position control by the
external signal "speed-position switching signal". (2) Besides setting the positioning data, the " Cd.24 Speed-position switching
enable flag" must also be turned ON to switch over from speed control to position control. (If the " Cd.24 Speed-position switching enable flag" turns
ON after the speed-position switching signal turns ON, the control will continue as speed control without switching over to position control. Only position control will be carried out when the " Cd.24 Speed-position switching enable
flag" and speed-position switching signal are ON at the operation start.)
Speed- position function selection

The following chart (Fig.9.13) shows the operation timing for speed-position switching control (INC mode). The "in speed control flag" ( Md.31 Status: b0) is
turned ON during speed control of speed-position switching control (INC mode).

Movement amount set in " Da. 6 Positioning address/movement amount"
Fig. 9.13 Speed-position switching control (INC mode) operation timing

The following operation assumes that the speed-position switching signal is input at the position of the current feed value of 90.00000 [degree] during execution of " Da.2 Control system" "Forward run: speed/position" at " Pr.1 Unit setting" of "2: degree" and " Pr.21 Current feed value during speed
control" setting of "1: Update current feed value". (The value set in " Da.6 Positioning address/movement amount" is 270.00000 [degree])

[Operation example]

control (INC mode)

Speed control carried out until speed-position switching signal turns ON
Position control movement amount is from the input position of the external speed-position switching signal
Cd. 23 Speed-position switching control movement amount change register
Fig. 9.14 Operation timing and processing time during speed-position switching control (INC mode)
t1 t2 t3 t4 t5 t6 t7
1.1 0 to 1.8 0 to 1.8 2.7 to 4.4 0 to 1.8 1.0 Follows parameters

The following table shows the " Md.20 Current feed value" during speed-position
switching control (INC mode) corresponding to the " Pr.21 Current feed value
during speed control" settings.

Speed control Speed Position control Speed control Speed Position control Speed control
(a) Current feed value not updated (b) Current feed value updated (c) Current feed value zero cleared
There is 1ms from the time the speed-position switching signal is turned ON to the time the speed-position switching latch flag ( Md.31 Status: b1) turns ON.
Speed-position switching signal OFF
Speed-position switching latch flag
Speed · 1ms

The following table shows the items that must be set to use the external command signals (CHG) as speed-position switching signals.

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
2 Set the "2: speed-position and position-speed switching requests".
Refer to Section 5.2 "List of parameters" and Section 5.7 "List of control data" for information on the setting details.
In "speed-position switching control (INC mode)", the position control movement amount can be changed during the speed control section.
(1) The position control movement amount can be changed during the speed
control section of speed-position switching control (INC mode). A movement amount change request will be ignored unless issued during the speed control section of the speed-position switching control (INC mode). (2) The "new movement amount" is stored in " Cd.23 Speed-position switching
control movement amount change register" by the sequence program during speed control. When the speed-position switching signal is turned ON, the movement amount for position control is stored in " Cd.23 Speed-position switching control
movement amount change register". (3) The movement amount is stored in the " Md.29 Speed-position switching
control positioning amount" of the axis monitor area from the point where the control changes to position control by the input of a speed-position switching signal from an external source.

Position control start Speed-position switching control (INC mode) start
Setting after the speed-position switching signal ON is ignored
Fig. 9.15 Position control movement amount change timing

POINT • The machine recognizes the presence of a movement amount change request when the data is written to " Cd.23 Speed-position switching control movement amount change register" with the
(1) An axis error (error code: 516) will occur and the operation cannot start if
"continuous positioning control" or "continuous path control" is set in " Da.1
Operation pattern". (2) "Speed-position switching control" cannot be set in " Da.2 Control system" of
the positioning data when "continuous path control" has been set in " Da.1
Operation pattern" of the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", "speed-position switching control" cannot be set in positioning data No. 2.) An axis error (error code: 516) will occur and the machine will carry out a deceleration stop if this type of setting is carried out. (3) An error (error code: 503) will occur if "current speed (-1)" is set in " Da.8
command speed". (4) The software stroke limit range check during speed control is made only when
the following (a) and (b) are satisfied: (a) " Pr.21 Current feed value during speed control" is "1: Update current feed
value". If the movement amount exceeds the software stroke limit range during speed control in case of the setting of other than "1: Update current feed value", an error (error code: 507 or 508) will occur as soon as speed control is changed to position control and the axis will decelerate to a stop. (b) When " Pr.1 Unit setting" is other than "2: degree"
If the unit is "degree", the software stroke limit range check is not performed. (5) If the value set in " Da.6 Positioning address/movement amount" is negative,
an error (error code: 530) will occur. (6) Deceleration processing is carried out from the point where the speed-position
switching signal is input if the position control movement amount set in " Da.6 Positioning address/movement amount" is smaller than the
deceleration distance from the " Da.8 Command speed".
(7) Turn ON the speed-position switching signal in the speed stabilization region
(constant speed status). A warning (warning code: 508) will occur because of large deviation in the droop pulse amount if the signal is turned ON during acceleration. During use of the servomotor, the actual movement amount after switching of speed control to position control is the "preset movement amount + droop pulse amount". If the signal is turned ON during acceleration/deceleration, the stop position will vary due to large variation of the droop pulse amount. Even though " Md.29 Speed-position switching control positioning amount" is the same, the stop position will change due to a change in droop pulse amount when " Da.8 Command speed" is different.

The following table shows setting examples when "speed-position switching control (INC mode) by forward run" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Set "Positioning complete" assuming the next positioning data will not be executed. ("Continuous path control" cannot be set in "speed- position switching control (INC mode)".)
Da.1 Operation pattern Positioning
Da.2 Control system Forward run: speed/position Set speed-position switching control by forward run.
Da.3 Acceleration time No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the
acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time
No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the
deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required. (Setting value is ignored.)
INC mode ( Pr.150 = 0) Set the movement amount after the switching to position control. (Assuming that the " Pr.1 Unit setting" is set to "mm".)
Da.6 Positioning address/
movement amount 10000.0µm
Da.7 Arc address – Setting not required. (Setting value is ignored.)
Da.8 Command speed 6000.00mm/min Set the speed to be controlled.
Da.9 Dwell time 500ms Set a time from the positioning stop (pulse output stop) by position control until the positioning complete signal is output. When the system is stopped by speed control, ignore the setting value.
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete

In case of "speed-position switching control (ABS mode)" (" Da.2 Control system" = Forward run: speed/position, Reverse run: speed/position), the pulses of the speed set in " Da.8 Command speed" are kept output in the axial direction set to the positioning data. When the "speed-position switching signal" is input, position control to the address set in " Da.6 Positioning address/movement amount" is exercised.
"Speed-position switching control (ABS mode)" is available in two different types: "forward run: speed/position" which starts the axis in the forward run direction and "reverse run: speed/position" which starts the axis in the reverse run direction.
"Speed-position switching control (ABS mode)" is valid only when " Pr.1 Unit setting"
is "2: degree".

: Setting allowed, : Setting disallowed (If setting is made, an error (error code: 935) will occur when the PLC
READY signal (Y0) turns ON.)
Use the detailed parameter 1 " Pr.150 Speed-position function selection" to choose "speed-position switching control (ABS mode)".

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
2 Speed-position switching control (ABS mode) 34 184 334 484
If the set value is other than 0 and 2, it is regarded as 0 and operation is performed in the INC
mode. For details of the setting, refer to Section 5.2 "List of parameters".
(1) The control is switched over from speed control to position control by the
external signal "speed-position switching signal". (2) Besides setting the positioning data, the " Cd.24 Speed-position switching
enable flag" must also be turned ON to switch over from speed control to position control. (If the " Cd.24 Speed-position switching enable flag" turns
ON after the speed-position switching signal turns ON, the control will continue as speed control without switching over to position control. Only position control will be carried out when the " Cd.24 Speed-position switching enable
flag" and speed-position switching signal are ON at the operation start.)

The following chart (Fig.9.16) shows the operation timing for speed-position switching control (ABS mode). The "in speed control flag" ( Md.31 Status: b0) is
turned ON during speed control of speed-position switching control (ABS mode).

Address set in " Da. 6 Positioning address/movement amount"
Fig. 9.16 Speed-position switching control (ABS mode) operation timing

The following operation assumes that the speed-position switching signal is input at the position of the current feed value of 90.00000 [degree] during execution of " Da.2 Control system" "Forward run: speed/position" at " Pr.1 Unit setting" of "2: degree" and " Pr.21 Current feed value during speed
control" setting of "1: Update current feed value". (The value set in " Da.6 Positioning address/movement amount" is 270.00000 [degree])

[Operation example]

control (ABS mode)

Speed control carried out until speed-position switching signal turns ON
Fig. 9.17 Operation timing and processing time during speed-position switching control (ABS mode)
t1 t2 t3 t4 t5 t6 t7
1.1 0 to 1.8 0 to 1.8 2.7 to 4.4 0 to 1.8 1.0 Follows parameters

The following table shows the " Md.20 Current feed value" during speed-position
switching control (ABS mode) corresponding to the " Pr.21 Current feed value
during speed control" settings.
" Pr.21 Current feed value during
Md.20 Current feed value
during speed control" in speed-position switching control (ABS mode). An error (error code: 935) will occur if the " Pr.21 Current feed value during
speed control" setting is other than 1.
Speed Position control Speed control
Current feed value updated
There is 1ms from the time the speed-position switching signal is turned ON to the time the speed-position switching latch flag ( Md.31 Status: b1) turns ON.
Speed-position switching signal OFF
Speed-position switching latch flag

The following table shows the items that must be set to use the external command signals (CHG) as speed-position switching signals.
Buffer memory address Setting item Setting
value Setting details Axis 1 Axis 2 Axis 3 Axis 4
External command function selection
2 Set the "2: speed-position and position-speed switching requests".
Pr.42
62 212 362 512
Cd.8
Refer to Section 5.2 "List of parameters" and Section 5.7 "List of control data" for information on the setting details.
External command valid

(1) An axis error (error code: 516) will occur and the operation cannot start if
"continuous positioning control" or "continuous path control" is set in " Da.1
Operation pattern". (2) "Speed-position switching control" cannot be set in " Da.2 Control system" of
the positioning data when "continuous path control" has been set in " Da.1
Operation pattern" of the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", "speed-position switching control" cannot be set in positioning data No. 2.) An axis error (error code: 516) will occur and the machine will carry out a deceleration stop if this type of setting is carried out. (3) An error (error code: 503) will occur if "current speed (-1)" is set in " Da.8
command speed". (4) If the value set in " Da.6 Positioning address/movement amount" is negative,
an error (error code: 530) will occur. (5) Even though the axis control data " Cd.23 Speed-position switching control
movement amount change register" was set in speed-position switching control (ABS mode), it would not function. The set value is ignored. (6) To exercise speed-position switching control (ABS mode), the following
(b) The software stroke limit function is invalid (upper limit value = lower limit
value) (c) " Pr.21 Current feed value during speed control" is "1: Update current
feed value" (d) The " Da.6 Positioning address/movement amount" setting range is 0 to
359.99999 (degree) If the value is outside of the range 0 to 359.99999 (degree), an error (error code: 530) will occur at a start. (e) The " Pr.150 Speed-position function selection" setting is "2: Speed-
position switching control (ABS mode)". (7) If any of the conditions in (6)(a) to (6)(c) is not satisfied in the case of (6)(e), an
error (error code: 935) will occur when the PLC READY signal [Y0] turns from OFF to ON. (8) If the axis reaches the positioning address midway through deceleration after
automatic deceleration started at the input of the speed-position switching signal, the axis will not stop immediately at the positioning address. The axis will stop at the positioning address after N revolutions so that automatic deceleration can always be made. (N: Natural number) In this case, make the movement amount after speed-position switching signal input within 21474.83647 (degree). If the movement amount exceeds 21474.83647 (degree), make the movement amount smaller by reducing the command speed or shortening the deceleration time, for example. In the following example, since making deceleration in the path of dotted line will cause the axis to exceed the positioning addresses twice, the axis will decelerate to a stop at the third positioning address.


The following table shows setting examples when "speed-position switching control (ABS mode) by forward run" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Set "Positioning complete" assuming the next positioning data will not be executed. ("Continuous path control" cannot be set in "speed- position switching control (ABS mode)".)
Da.1 Operation pattern Positioning
Da.2 Control system Forward run: speed/position Set speed-position switching control by forward run.
Da.3 Acceleration time No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the
acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the
deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required. (Setting value is ignored.)
ABS mode ( Pr.150 = 2) Set the address after the switching to position control. (Assuming that the " Pr.1 Unit setting" is set to "mm".)
Da.6 Positioning address/
270.00000 degree
Da.7 Arc address – Setting not required. (Setting value is ignored.)
Da.8 Command speed 6000.00mm/min Set the speed to be controlled.
Da.9 Dwell time 500ms Set a time from the positioning stop (pulse output stop) by position control until the positioning complete signal is output. When the system is stopped by speed control, ignore the setting value.
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete · movement amount

In "position-speed switching control" (" Da.2 Control system" = Forward run:
position/speed, Reverse run: position/speed), before the position-speed switching signal is input, position control is carried out for the movement amount set in " Da.6 Positioning address/movement amount" in the axis direction in which the
positioning data has been set. When the position-speed switching signal is input, the position control is carried out by continuously outputting the pulses for the speed set in " Da.8 command speed" until the input of a stop command.
The two types of position-speed switching control are "Forward run: position/speed" in which the control starts in the forward run direction, and "Reverse run: position/speed" in which control starts in the reverse run direction.
(1) The control is switched over from position control to speed control by the
external signal "position-speed switching signal". (2) Besides setting the positioning data, the " Cd.26 Position-speed switching
enable flag" must also be turned ON to switch over from position control to speed control. (If the " Cd.26 Position-speed switching enable flag" turns ON
after the position-speed switching signal turns ON, the control will continue as position control without switching over to speed control. Only speed control will be carried out when the " Cd.26 Position-speed switching enable flag" and
position-speed switching signal are ON at the operation start.)

The following chart shows the operation timing for position-speed switching control. The "in speed control" flag ( Md.31 Status: b0) is turned ON during speed control
of position-speed switching control.

Does not turn ON even when control is stopped by stop command.
Fig. 9.18 Position-speed switching control operation timing

control

Standing by In position control Standing by Axis operation status
Position control carried out until position-speed switching signal turns ON.
Speed control command speed is from the input position of the external position-speed switching signal.
Fig. 9.19 Operation timing and processing time during position-speed switching control
t1 t2 t3 t4 t5 t6
1.0 to 1.4 0 to 1.8 0 to 1.8 2.7 to 4.4 - 1.0

The following table shows the " Md.20 Current feed value" during position-speed
switching control corresponding to the " Pr.21 Current feed value during speed
control" settings.

The current feed value is updated during position control, and the current feed value at the time of switching is maintained as soon as position control is switched to speed control.
(a) Current feed value not updated (b) Current feed value updated
(c) Current feed value zero cleared
There is 1ms from the time the position-speed switching signal is turned ON to the time the position-speed switching latch flag ( Md.31 Status: b5) turns ON.
OFF
ON
Position-speed switching latch flag
t · Position-speed switching signal · 1ms

The following table shows the items that must be set to use the external command signals (CHG) as position-speed switching signals.

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
2 Set the "2: speed-position and position-speed switching requests".
Refer to Section 5.2 "List of parameters" and Section 5.7 "List of control data" for information on the setting details.
In "position-speed switching control", the speed control command speed can be changed during the position control. (1) The speed control command speed can be changed during the position control
of position-speed switching control. A command speed change request will be ignored unless issued during the position control of the position-speed switching control. (2) The "new command speed" is stored in " Cd.25 Position-speed switching
control speed change register" by the sequence program during position control. This value then becomes the speed control command speed when the position-speed switching signal turns ON.

Setting after the position-speed switching signal ON is ignored. Position-speed switching control speed change register
Fig. 9.20 Speed control speed change timing

POINTS • The machine recognizes the presence of a command speed change request when the data is written to " Cd.25 Position-speed switching control speed change register" with the sequence
(1) An axis error (error code: 516) will occur and the operation cannot start if
"continuous positioning control" or "continuous path control" is set in " Da.1 Operation pattern".
(2) "Position-speed switching control" cannot be set in " Da.2 Control system" of
the positioning data when "continuous path control" has been set in " Da.1 Operation pattern" of the immediately prior positioning data. (For
example, if the operation pattern of positioning data No. 1 is "continuous path control", "position-speed switching control" cannot be set in positioning data No. 2.) An axis error (error code: 516) will occur and the machine will carry out a deceleration stop if this type of setting is carried out. (3) The software stroke limit range is only checked during speed control if the "1:
Update current feed value" is set in " Pr.21 Current feed value during speed
control". The software stroke limit range is not checked when the control unit is set to "degree". (4) An error (error code: 507 or 508) will occur and the operation cannot start if
the start point address or end point address for position control exceeds the software stroke limit range. (5) Deceleration stop will be carried out if the position-speed switching signal is
not input before the machine is moved by a specified movement amount. When the position-speed switching signal is input during automatic deceleration by positioning control, acceleration is carried out again to the command speed to continue speed control. When the position-speed switching signal is input during deceleration to a stop with the stop signal, the control is switched to the speed control to stop the machine. Restart is carried out by speed control using the restart command. (6) A warning (warning code: 501) will occur and control is continued by
" Pr.8 Speed limit value" if a new speed exceeds " Pr.8 Speed limit value" at
the time of change of the command speed. (7) If the value set in " Da.6 Positioning address/movement amount" is negative,
an error (error code: 530) will occur.

The following table shows setting examples when "position-speed switching control (forward run: position/speed)" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Set "Positioning complete" assuming the next positioning data will not be executed. ("Continuous positioning control" and "Continuous path control" cannot be set in "position/speed changeover control".)
Da.1 Operation pattern Positioning
Da.2 Control system Forward run: position/speed Set position-speed switching control.
Da.3 Acceleration time No. 1 Designate the value set in " Pr.25 Acceleration time 1" as the
acceleration time at start.
Axis 1 Positioning data No. 1
Da.4 Deceleration time No. 0 Designate the value set in " Pr.10 Deceleration time 0" as the
deceleration time at deceleration.
Da.5 Axis to be
interpolated – Setting not required. (Setting value is ignored.)
Set the movement amount at the time of position control before the switching to speed control. (Assuming that the " Pr.1 Unit setting" is
Da.6 Positioning address/
movement amount 10000.0µm
set to "mm".)
Da.7 Arc address – Setting not required. (Setting value is ignored.)
Da.8 Command speed 6000.00mm/min Set the speed to be controlled.
Set the time the machine dwells after the positioning stop (pulse output stop) by position control to the output of the positioning complete signal. If the machine is stopped by speed control, the setting value will be ignored.
Da.9 Dwell time 500ms
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
complete

When the current value is changed to a new value, control is carried out in which the " Md.20 Current feed value" of the stopped axis is changed to a random address set
by the user. (The " Md.21 Machine feed value" is not changed when the current value
is changed.)
The two methods for changing the current value are shown below.
[1] Changing to a new current value using the positioning data [2] Changing to a new current value using the start No. (No. 9003) for a current
The current value changing using method [1] is used during continuous positioning of multiple blocks, etc.
Operation chart
The following chart shows the operation timing for a current value changing. The " Md.20 Current feed value" is changed to the value set in " Da.6 Positioning
address/movement amount" when the positioning start signal turns ON.
Positioning start signal [Y10,Y11,Y12,Y13]
Md.20 50000 0
Current feed value changes to the
positioning address designated by the
positioning data of the current value changing.
The above chart shows an example
when the positioning address is "0".
(1) An axis error "New current value not possible (error code: 515)" will occur and
the operation cannot start if "continuous path control" is set in " Da.1
Operation pattern". ("Continuous path control" cannot be set in current value changing.)
(2) "Current value changing" cannot be set in " Da.2 Control system" of the
positioning data when "continuous path control" has been set in " Da.1
Operation pattern" of the immediately prior positioning data. (For example, if the operation pattern of positioning data No. 1 is "continuous path control", "current value changing" cannot be set in positioning data No. 2.) An axis error "New current value not possible (error code: 515)" will occur and the machine will carry out a deceleration stop if this type of setting is carried out.
(3) An axis error "Outside new current value range (error code: 514)" will occur
and the operation cannot start if "degree" is set in " Pr.1 Unit setting" and the
value set in " Da.6 Positioning address/movement amount" is outside the
setting range (0 to 359.99999 [degree]).
value changing · Current feed value

(4) If the value set in " Da.6 Positioning address/movement amount" is outside
the software stroke limit ( Pr.12 , Pr.13 ) setting range, an error "Software
stroke limit +, – (error code: 507 or 508)" will occur at the positioning start, and the operation will not start.
the software stroke limit range.
The following table shows the setting examples when " current value changing" is set in the positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Set "Positioning complete" assuming that the next positioning data will be executed. ("Continuous path control" cannot be set by current value change.)
Da.1 Operation pattern Positioning complete
Da.2 Control system Current value changing Set the current value changing.
Da.3 Acceleration time No. – Setting not required (Setting value is ignored.)
Da.4 Deceleration time No. – Setting not required (Setting value is ignored.)
Da.5 Axis to be interpolated – Setting not required (Setting value is ignored.)
Positioning address/ movement amount
Set the address to which address change is desired. (Assuming that the " Pr.1 Unit
data No. 1
Da.6
10000.0 m
setting" is set to "mm".)
Da.7 Arc address – Setting not required (Setting value is ignored.)
Da.8 Command speed – Setting not required (Setting value is ignored.)
Da.9 Dwell time – Setting not required (Setting value is ignored.)
Da.10 M code 10 Set this when other sub operation commands are issued in combination with the No. 1 positioning data.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
Axis 1 positioning

[2] Changing to a new current value using the start No. (No. 9003) for
Operation chart
The current value is changed by setting the new current value in the current value changing buffer memory " Cd.9 Current value changing", setting "9003" in the
" Cd.3 Positioning start No.", and turning ON the positioning start signal.
OFF
[Y10,Y11,Y12,Y13]
Md.20 Current feed value 50000 0
Current value changes to the positioning address designated by the current value changing buffer memory.
The above chart shows an example when the positioning address is "0".
(1) An axis error "Outside new current value range (error code: 514)" will occur if the designated value is outside the setting range when "degree" is set in "Unit setting".
(2) An error "Software stroke limit +, (error code: 507 or 508)" will occur if the designated value is outside the software stroke limit range.
(3) The current value cannot be changed during stop commands and while the M
code ON signal is ON.
(4) The M code output function is made invalid.
The following shows the procedure for changing the current value to a new value.
Write the current value to " Cd. 9 Current value changing"
Write "9003" in " Cd. 3 Positioning start No."
Turn ON the positioning start signal.

The following shows an example of a sequence program and data setting to change the current value to a new value with the positioning start signal. (The " Md.20 Current feed value is changed to "5000.0µm" in the example shown.)
(1) Set the following data.
(Set with the sequence program shown in (3), while referring to the start time chart shown in (2).)

value Setting details Axis 1 Axis 2 Axis 3 Axis 4
Cd.3 Positioning start No. 9003 Set the start No. "9003" for the new current value. 1500 1600 1700 1800
Cd.9 Current value changing 50000 Set the new " Md.20 Current feed value". 1506 1507 1606 1607 1706 1707 1806 1807
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) The following shows a start time chart.

Fig. 9.21 Changing to a new current value using the start No. (No. 9003) for a current value changing

(3) Add the following sequence program to the control program, and write it to the
PLC CPU.

Store new current feed value in D106 and D107

The NOP instruction is used for the nonexecutable control system.
The positioning data No. to which the NOP instruction is set transfers, without any processing, to the operation for the next positioning data No.
The following table shows the setting examples when "NOP instruction" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern – Setting not required (Setting value is ignored.)
Da.2 Control system NOP instruction Set the NOP instruction
Da.3 Acceleration time No. – Setting not required (Setting value is ignored.)
Da.4 Deceleration time No. – Setting not required (Setting value is ignored.)
Da.5 Axis to be interpolated – Setting not required (Setting value is ignored.)
Positioning address/ movement amount
– Setting not required (Setting value is ignored.)
data No. 1
Da.6
Da.7 Arc address – Setting not required (Setting value is ignored.)
Da.8 Command speed – Setting not required (Setting value is ignored.)
Da.9 Dwell time – Setting not required (Setting value is ignored.)
Da.10 M code – Setting not required (Setting value is ignored.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.
An error "Control system setting error (error code: 524)" will occur if the "NOP instruction" is set for the control system of the positioning data No. 600.

If there is a possibility of speed switching or temporary stop (automatic deceleration) at a point between two points during positioning, that data can be reserved with the NOP instruction to change the data merely by the replacement of the identifier.
Axis 1 positioning

The JUMP instruction is used to control the operation so it jumps to a positioning data No. set in the positioning data during "continuous positioning control" or "continuous path control".
JUMP instruction include the following two types of JUMP.
When no execution conditions are set for the JUMP instruction (When "0" is set as the condition data No.)
When execution conditions are set for the JUMP instruction (The conditions are set in the "condition data" used with "high-level positioning control".)
Using the JUMP instruction enables repeating of the same positioning control, or selection of positioning data by the execution conditions during "continuous positioning control" or "continuous path control".
The JUMP instruction is unconditionally executed. The operation jumps to the positioning data No. set in " Da.9 Dwell time".
instruction have been established: the JUMP instruction is executed to jump the operation to the positioning data No. set in " Da.9 Dwell time".
instruction have not been established: the JUMP instruction is ignored, and the next positioning data No.is executed.
(1) When using a conditional JUMP instruction, establish the JUMP instruction
execution conditions by the 4th positioning data No. before the JUMP instruction positioning data No. If the JUMP instruction execution conditions are not established by the time the 4th positioning control is carried out before the JUMP instruction positioning data No., the operation will be processed as an operation without established JUMP instruction execution conditions. (During execution of continuous path control/continuous positioning control, the QD75 calculates the positioning data of the positioning data No. four items ahead of the current positioning data.)

(2) The operation pattern, if set, is ignored in the JUMP instruction.
(3) Positioning control such as loops cannot be executed by conditional JUMP
instructions alone until the conditions have been established. As the target of the JUMP instruction, specify a positioning data that is controlled by other than JUMP and NOP instructions.
The following table shows setting examples when "JUMP instruction" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern – Setting not required. (Setting value is ignored.)
Da.2 Control system JUMP instruction Set the JUMP instruction.
Da.3 Acceleration time No. – Setting not required. (Setting value is ignored.)
Da.4 Deceleration time No. – Setting not required. (Setting value is ignored.)
Axis 1 Positioning data No. 1
Da.5 Axis to be
interpolated – Setting not required. (Setting value is ignored.)
Da.6 Positioning address/
movement amount – Setting not required. (Setting value is ignored.)
Da.7 Arc address – Setting not required. (Setting value is ignored.)
Da.8 Command speed – Setting not required. (Setting value is ignored.)
Set the positioning data No. 1 to 600 for the JUMP destination. (The positioning data No. of the JUMP instruction cannot be set. Setting its own positioning data No. will result in an error "Illegal data No." (error code: 502).)
Da.9 Dwell time 500
Set the JUMP instruction execution conditions with the condition data No. 0 : Unconditional JUMP 1 to 10 : Condition data No. ("Simultaneous start" condition data cannot be set.)
Da.10 M code 1
Refer to Section 5.3 "List of positioning data" for information on the setting details.

The LOOP is used for loop control by the repetition of LOOP to LEND.
The LOOP to LEND loop is repeated by set repeat cycles.
The following table shows the setting examples when "LOOP" is set in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern – Setting not required. (Setting value is ignored.)
Da.2 Control system LOOP Set the LOOP.
Axis 1 Positioning data No. 1
Da.3 Acceleration time No. – Setting not required. (Setting value is ignored.)
Da.4 Deceleration time No. – Setting not required. (Setting value is ignored.)
Da.5 Axis to be
interpolated – Setting not required. (Setting value is ignored.)
Da.6 Positioning address/
movement amount – Setting not required. (Setting value is ignored.)
Da.7 Arc address – Setting not required. (Setting value is ignored.)
Da.8 Command speed – Setting not required. (Setting value is ignored.)
Da.9 Dwell time – Setting not required. (Setting value is ignored.)
Da.10 M code 5 Set the LOOP to LEND repeat cycles.
Refer to Section 5.3 "List of positioning data" for information on the setting details.
(1) An error "Control system LOOP setting error (error code: 545)" will occur if a
"0" is set for the repeat cycles.
(2) Even if LEND is absent after LOOP, no error will occur, but repeat processing
will not be carried out. (3) Nesting is not allowed between LOOP-LEND's. If such setting is made, only the
inner LOOP-LEND is processed repeatedly.
However LOOP to LEND cannot be set across block. Always set LOOP to LEND so that the processing ends within one block. (For details of the "block", refer to Section 10.1 "Outline of high-level positioning control".)

The LEND is used to return the operation to the top of the repeat (LOOP to LEND) loop.
When the repeat cycle designated by the LOOP becomes 0, the loop is terminated, and the next positioning data No. processing is started. (The operation pattern, if set to "Positioning complete", will be ignored.) When the operation is stopped after the repeat operation is executed by designated cycles, the dummy positioning data (for example, incremental positioning without movement amount) is set next to LEND.

Executed in the order of the positioning data No. 1 2 3 4 5 2 3 4 5 6. (The operation patterns of the positioning data Nos. 2 and 5 are ignored.)
2 Positioning complete LOOP Number of loop cycles: 2
The following table shows the setting examples when "LEND" is set in positioning data No. 8 of axis 1.
Setting item Setting example Setting details
Da.1 Operation pattern – Setting not required. (Setting value is ignored.)
Da.2 Control system LEND Set the LEND.
Axis 1 Positioning data No. 8
Da.3 Acceleration time No. – Setting not required. (Setting value is ignored.)
Da.4 Deceleration time No. – Setting not required. (Setting value is ignored.)
Da.5 Axis to be
interpolated – Setting not required. (Setting value is ignored.)
Da.6 Positioning address/
movement amount – Setting not required. (Setting value is ignored.)
Da.7 Arc address – Setting not required. (Setting value is ignored.)
Da.8 Command speed – Setting not required. (Setting value is ignored.)
Da.9 Dwell time – Setting not required. (Setting value is ignored.)
Da.10 M code – Setting not required. (Setting value is ignored.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.
(1) Ignore the "LEND" before the "LOOP" is executed.

The details and usage of high-level positioning control (control functions using the "block start data") are explained in this chapter.
High-level positioning control is used to carry out applied control using the "positioning data". Examples of applied control are using conditional judgment to control "positioning data" set with the major positioning control, or simultaneously starting "positioning data" for several different axes.
Read the execution procedures and settings for each control, and set as required.
10.1 Outline of high-level positioning control 10- 2 10.1.1 Data required for high-level positioning control 10- 3 10.1.2 " Block start data" and "condition data" configuration 10- 4 10.2 High-level positioning control execution procedure 10- 6 10.3 Setting the block start data 10- 7 10.3.1 Relation between various controls and block start data 10- 7 10.3.2 Block start (normal start) 10- 8 10.3.3 Condition start 10- 10 10.3.4 Wait start 10- 11 10.3.5 Simultaneous start 10- 12 10.3.6 Repeated start (FOR loop) 10- 13 10.3.7 Repeated start (FOR condition) 10- 14 10.3.8 Restrictions when using the NEXT start 10- 15 10.4 Setting the condition data 10- 16 10.4.1 Relation between various controls and the condition data 10- 16 10.4.2 Condition data setting examples 10- 19 10.5 Multiple axes simultaneous start control 10- 20 10.6 Start program for high-level positioning control 10- 23 10.6.1 Starting high-level positioning control 10- 23 10.6.2 Example of a start program for high-level positioning control 10- 24

In "high-level positioning control" the execution order and execution conditions of the "positioning data" are set to carry out more applied positioning. (The execution order and execution conditions are set in the "block start data" and "condition data".) The following applied positioning controls can be carried out with "high-level positioning control".
Block 1 start (Normal start) With one start, executes the positioning data in a random block with the set order.
2 Simultaneously executes the positioning data having the No. for the axis designated with the "condition data". (Outputs pulses at the same timing.)
Repeated start (FOR loop)
Repeats the program from the " block start data" set with the "FOR loop" to the " block start data" set in "NEXT" for the designated No. of times.
Repeated start (FOR condition)
Repeats the program from the " block start data" set with the "FOR condition" to the " block start data" set in "NEXT" until the conditions set in the "condition data" are established.
"High-level positioning control" uses the "positioning data" set with the "major positioning control". Refer to Section 3.2.4 "Combination of QD75 main functions and sub functions" for details on sub functions that can be combined with the major positioning control. Note that the sub function Section 12.7.8 "Pre-reading start function" cannot be used together with "high-level positioning control".
"High-level positioning control" (start of the "block start data") can be executed from GX Configurator-QP test mode. Refer to GX Configurator-QP Operating Manual for details on starting of the "block start data" from GX Configurator-QP.
Block 1: "1 block" is defined as all the data continuing from the positioning data in which "continuous positioning control" or "continuous path control" is set in the operation pattern ( Da.1 ) to the positioning data in which "independent
positioning control (Positioning complete)" is set.
Simultaneous start 2: Besides the simultaneous start of "block start data" system, the "simultaneous starts" include the "multiple axes simultaneous start control" of control system. Refer to Section 10.5 "Multiple axes simultaneous start control" for details.

"High-level positioning control" is executed by setting the required items in the "block start data" and "condition data", then starting that "block start data". Judgment about whether execution is possible, etc., is carried out at execution using the "condition data" designated in the "block start data".
"Block start data" can be set for each No. from 7000 to 7004 (called "block Nos."), and up to 50 points can be set for each axis. (This data is controlled with Nos. called "points" to distinguish it from the positioning data. For example, the 1st block start data item is called the "1st point block start data" or "point No. 1 block start data".)
"Condition data" can be set for each No. from 7000 to 7004 (called "block Nos."), and up to 10 data items can be set for each axis.
The " block start data" and "condition data" are set as 1 set for each block No.
The following table shows an outline of the " block start data" and "condition data" stored in the QD75.

Set whether to end the control after executing only the "block start data" of the shape itself, or continue executing the "block start data" set in the next point.
Da.12 Start data No. Set the "positioning data No." to be executed.
Set the method by which the positioning data set in Da.12
Set the conditions by which the start will be executed
according to the commands set in Da.13 . (Designate the
Designate the "device", "buffer memory storage details", and "positioning data No." elements for which the conditions are set.
Set the judgment method carried out for the target set in
Set the buffer memory address in which condition judgment is
carried out (only when the details set in Da.15 are "buffer
Set the required conditions according to the details set in
Set the required conditions according to the details set in

The "block start data" and "condition data" corresponding to "block No. 7000" can be stored in the buffer memory. (The following drawing shows an example for axis 1.)

Axis 1 block start data Axis 1 condition data
26191 26192 26193 26194 26195 26196 26197 26198 26199
26111 26112 26113 26114 26115 26116 26117 26118 26119
26101 26102 26103 26104 26105 26106 26107 26108 26109
(Same for axis 2, axis 3 and axis 4.)
7000 Block No. Set in the QD75 with a sequence program or GX Configurator-QP.

Set in QD75 the " block start data" and "condition data" corresponding to the following "block Nos. 7001 to 7004" using GX Configurator-QP or the sequence program. (The following drawing shows an example for axis 1.)


26391 26392 26393 26394 26395 26396 26397 26398 26399
26991 26992 26993 26994 26995 26996 26997 26998 26999
26311 26312 26313 26314 26315 26316 26317 26318 26319
26911 26912 26913 26914 26915 26916 26917 26918 26919
26301 26302 26303 26304 26305 26306 26307 26308 26309
26901 26902 26903 26904 26905 26906 26907 26908 26909

High-level positioning control is carried out using the following procedure.

"High-level positioning control" executes each control ("major positioning control") set in the positioning data with the designated conditions,so first carry out preparations so that "major positioning control" can be executed.
Set the block start data corresponding to each control. ( Da. 11 to Da. 14 ) × required data amount.
The 50 "block start data" points from 1 to 50 points
can be set.
Set the "condition data" ( Da. 15 to Da. 19 ) × required data amount .
Set the "condition data" for designation with the "block start data". Up to 10 condition data items can be set.
Create a sequence program in which "7000"*is set in
The QD75 recognizes that the control is high-level
the " Cd. 3 Positioning start No". (Control data setting)
positioning control using " block start data" by the
"7000" designation.
Create a sequence program in which the "block start
Use GX Developer to create a sequence program
data point No. to be started" (1 to 50) is set in the
to execute the "high-level positioning control".
(Set the control data in the QD75 buffer memory using
" Cd. 4 Positioning start point No". (Control data setting)
a TO command.)
start signal" is turned ON by a positioning start command.
Write the sequence program created in STEP 4 to the PLC CPU using GX Developer.
Same procedure as for the "major positioning control" start.
Turn ON the "positioning start command" of the axis to be started.
Use one of the following two methods. Method (1): Monitor using GX Configurator-QP. Method (2): Monitor using GX Developer.
Same procedure as for the "major positioning control" stop.
(1) Five sets of "block start data (50 points)" and "condition data (10 items)
corresponding to "7000" to "7004" are set with a sequence program. (2) Five sets of data from "7000" to "7004" can be set when GX Configurator-QP
is used. If GX Configurator-QP is used to set the "block start data" and "condition data" corresponding to "7001" to "7004" and write the data to the QD75, "7001" to "7004" can be set in " Cd.3 Positioning start No." in STEP
Starting the control · Monitoring the control · Control termination

10.3.1 Relation between various controls and block start data
The " block start data" must be set to carry out "high-level positioning control". The setting requirements and details of each " block start data" item to be set differ according to the " Da.13 Special start instruction" setting.
The following shows the " block start data" setting items corresponding to various control systems. The operation details of each control type are explained starting in Section 10.3.2. Also refer to Section 10.4 "Setting the condition data for details on "condition data" with which control execution is judged. (The " block start data" settings in this chapter are assumed to be carried out using GX Configurator-QP.)

Da.13 Special start instruction 0 1 2 3 4 5 6
Da.14 Parameter – Condition data No. No. of repetitions
: One of the two setting items must be set.
: Set when required (Set to " – " when not used.)
: Setting not possible – : Setting not required (Setting value will be ignored. Use the initial value or a value within the setting range.)
The "NEXT start" instruction is used in combination with "repeated start (FOR loop)" and "repeated start (FOR condition)". Control using only the "NEXT start" will not be carried out.
It is recommended that the "block start data" be set whenever possible with GX Configurator-QP. Execution by sequence program uses many sequence programs and devices. The execution becomes complicated, and the scan times will increase.

In a "block start (normal start)", the positioning data groups of a block are continuously executed in a set sequence starting from the positioning data set in " Da.12 Start data
No." by one start.
Section [2] shows a control example where the " block start data" and "positioning data" are set as shown in section [1].
(1) Block start data setting example
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Setting examples diagram (page 422)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-422-1.webp)
1st point 1: Continue 1 0: Block start – 2nd point 1: Continue 2 0: Block start – 3rd point 1: Continue 5 0: Block start – 4th point 1: Continue 10 0: Block start – 5th point 0: End 15 0: Block start –

1 00: Positioning complete 2 11: Continuous path control 3 01: Continuous positioning control 4 00: Positioning complete 5 11: Continuous path control 6 00: Positioning complete
Block : "1 block" is defined as all the data continuing from the positioning data in which "continuous positioning control" or "continuous path control" is set in the operation pattern ( Da.1 ) to the positioning data in which "independent positioning control
(Positioning complete)" is set.
1 block · 1 block
![Page 423 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Control examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-423.webp?w=400)
The following shows the control executed when the "block start data" of the 1st point of axis 1 is set as shown in section [1] and started.
The positioning data is executed in the following order before stopping.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Control examples diagram (page 423)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-423-1.webp)
Axis 1 positioning data No. 1 2 3 4 5 6 10 15.
Fig. 10.1 Block start control example
![Page 424 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Control examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-424.webp?w=400)
In a "condition start", the "condition data" conditional judgment designated in " Da.14
Parameter" is carried out for the positioning data set in " Da.12 Start data No.". If the
conditions have been established, the " block start data" set in "1: condition start" is executed. If the conditions have not been established, that " block start data" will be ignored, and the "block start data" of the next point will be executed.
Section [2] shows a control example where the " block start data" and "positioning data" are set as shown in section [1].
(1) Block start data setting example
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Setting examples diagram (page 424)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-424-1.webp)
The "condition data Nos." have been set in " Da.14 Parameter".

The following shows the control executed when the " block start data" of the 1st point of axis 1 is set as shown in section [1] and started. The conditional judgment set in "condition data No. 1" is carried out before
execution of the axis 1 "positioning data No. 1".
Conditions established Execute positioning data No. 1, 2, and 3 Go to . Conditions not established Go to .
The conditional judgment set in "condition data No. 2" is carried out before
execution of the axis 1 "positioning data No. 10".
Conditions established Execute positioning data No. 10, 11, and 12 Go to . Conditions not established Go to .
Execute axis 1 "positioning data No. 50" and stop the control.
![Page 425 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Control examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-425.webp?w=400)
In a "wait start", the "condition data" conditional judgment designated in " Da.14
Parameter" is carried out for the positioning data set in " Da.12 Start data No.". If the
conditions have been established, the " block start data" is executed. If the conditions have not been established, the control stops (waits) until the conditions are established.
Section [2] shows a control example where the " block start data" and "positioning data" are set as shown in section [1].
(1) Block start data setting example
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Setting examples diagram (page 425)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-425-1.webp)
The "condition data Nos." have been set in " Da.14 Parameter".

The following shows the control executed when the " block start data" of the 1st point of axis 1 is set as shown in section [1] and started. The conditional judgment set in "condition data No. 3" is carried out before
execution of the axis 1 "positioning data No. 1".
Conditions established Execute positioning data No. 1, 2, and 3 Go to . Conditions not established Control stops (waits) until conditions are established Go to .
Execute the axis 1 "positioning data No. 10, 11, 12, and 50" and stop the
control.

In a "simultaneous start", the positioning data set in the " Da.12 Start data No." and
positioning data of other axes set in the "condition data" are simultaneously executed (pulses are output with the same timing). (The "condition data" is designated with " Da.14 Parameter".)
Section [2] shows a control example where the " block start data" and "positioning data" are set as shown in section [1]. [1] Setting examples


The following shows the control executed when the " block start data" of the 1st point of axis 1 is set as shown in section [1] and started. Simultaneously start the axis 1 "positioning data No. 1" and axis 2
positioning data set in "condition data No. 4". After the execution of axis 1 "positioning data No. 1, 2, and 3" is completed, go to . Simultaneously start the axis 1 "positioning data No. 10" and axis 2
positioning data set in "condition data No. 5".
Standing by after completion of axis 2 positioning data simultaneously started in . Go to . Executing axis 2 positioning data simultaneously started in . "Error". Simultaneously start the axis 1 "positioning data No. 50" and the axis 2
positioning data set in "condition data No. 6" after the completion of the execution of axis 1 "positioning data No. 10, 11, and 12".
Standing by after completion of axis 2 positioning data simultaneously started in . Go to . Executing axis 2 positioning data simultaneously started in . "Error". After the execution of the axis 1 "positioning data No. 50" is completed, stop
the control.
![Page 427 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Control examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-427.webp?w=400)
In a "repeated start (FOR loop)", the data between the " block start data" in which "4: FOR loop" is set in " Da.13 Special start instruction" and the "block start data" in
executed for the No. of times set in " Da.14 Parameter". An endless loop will result if the No. of repetitions is set to "0".
(The No. of repetitions is set in " Da.14 Parameter" of the " block start data" in which "4: FOR loop" is set in " Da.13 Special start instruction".)
Section [2] shows a control example where the " block start data" and "positioning data" are set as shown in section [1].
(1) Block start data setting example
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Setting examples diagram (page 427)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-427-1.webp)
The "condition data Nos." have been set in " Da.14 Parameter".

The following shows the control executed when the " block start data" of the 1st point of axis 1 is set as shown in section [1] and started. Execute the axis 1 "positioning data No. 1, 2, 3, 10, 11, 50, and 51".
Return to the axis 1 "1st point block start data". Again execute the axis 1
"positioning data No. 1, 2, 3, 10, 11, 50 and 51", and then stop the control. (Repeat for the No. of times (2 times) set in Da.14 .)
![Page 428 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Control examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-428.webp?w=400)
In a "repeated start (FOR condition)", the data between the " block start data" in which "5: FOR condition" is set in " Da.13 Special start instruction" and the " block start
executed until the establishment of the conditions set in the "condition data". (The "condition data" designation is set in " Da.14 Parameter" of the " block start
Section [2] shows a control example where the " block start data" and "positioning data" are set as shown in section [1].
(1) Block start data setting example
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Setting examples diagram (page 428)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-428-1.webp)
The "condition data Nos." have been set in " Da.14 Parameter".

The following shows the control executed when the " block start data" of the 1st point of axis 1 is set as shown in section [1] and started. Carry out the conditional judgment set in "condition data No. 5" for the axis 1
"positioning data No. 1".
Conditions not established Go to . Conditions established Go to .
Execute axis 1 "positioning data No. 1, 2, 3, 10, 11, 50, and 51", then go to
.
Execute axis 1 "positioning data No. 1, 2, 3, 10, 11, 50, and 51", then stop
the control.

The "NEXT start" is a instruction indicating the end of the repetitions when executing Section 10.3.6 "Repeated start (FOR loop)" and Section 10.3.7 "Repeated start (FOR condition)".
The following shows the restrictions when setting "6: NEXT start" in the " block start data".
(1) The processing when "6: NEXT start" is set before execution of "4: FOR loop" or "5: FOR condition" is the same as that for a "0: block start".
(2) Repeated processing will not be carried out if there is no "6: NEXT start" instruction after the "4: FOR loop" or "5: FOR condition" instruction. (Note that an "error" will not occur.)
(3) Nesting is not possible between "4: FOR loop" and "6: NEXT start", or between "5: FOR condition" and "6: NEXT start". A warning "FOR to NEXT nest construction (warning code: 506)" will occur if nesting is attempted.
[Operating examples without nesting structure] [Operating examples with nesting structure]

A warning will occur when starting the 4th point "FOR". The JUMP destination of the 7th point "NEXT" is the 4th point. The 9th point "NEXT" is processed as normal start.

10.4.1 Relation between various controls and the condition data
"Condition data" is set in the following cases.
(1) When setting conditions during execution of Section 9.2.21 "JUMP instruction" (major positioning control) (2) When setting conditions during execution of "high-level positioning control"
The "condition data" to be set includes the 5 setting items from Da.15 to Da.19 , but
the setting requirements and details differ according to the control system and setting conditions.
The following shows the "condition data" " Da.15 Condition target" corresponding to
the different types of control. (The "condition data" settings in this chapter are assumed to be carried out using GX Configurator-QP.)

: One of the setting items must be set. : Setting not possible
It is recommended that the "condition data" be set whenever possible with GX Configurator-QP. Execution by sequence program uses many sequence programs and devices. The execution becomes complicated, and the scan times will increase.

The setting requirements and details of the following "condition data" Da.16 to
Da.19 setting items differ according to the " Da.15 Condition target" setting.
The following shows the Da.16 to Da.19 setting items corresponding to the
" Da.15 Condition target".
Da.16
Da.17
Da.18
Da.19
Da.15
02H: Device Y 07H : DEV=ON 08H : DEV=OFF – 0 to 1FH (bit No.) –
01H : =P1 02H : ≠P1 03H : ≤P1 04H : ≥P1 05H : P1≤ ≤P2 06H : ≤P1, P2 ≤
(Set only when Da.16 is
[05H] or [06H].)
10H : Axis 1 designation 20H : Axis 2 designation 30H : Axis 1 and axis 2 designation 40H : Axis 3 designation 50H : Axis 1 and axis 3 designation 60H : Axis 2 and axis 3 designation 70H : Axis 1, axis 2 and axis 3 designation 80H : Axis 4 designation 90H : Axis 1 and axis 4 designation A0H : Axis 2 and axis 4
Axis 1 positioning data No.
Axis 3 positioning data No.
05H: Positioning data No.
Axis 2 positioning data No.
Axis 4 positioning data No.
– : Setting not required (Setting value will be ignored. Use the initial value or a value within the setting range.)
: Value stored in buffer memory designated in Da.17 .
: Refer to Section 5.5 "List of condition data" for the setting contents.
Judgment whether the condition operator is "=" or "=” at the start of wait. Judgment on data is carried out for each control cycle of the QD75. Thus, in the judgment on the data such as current feed value which varies continuously, the operator "=" may not be detected. If this occurs, use a range operator.

The "PLC CPU memory area" can be designated as the buffer memory address to be designated in Da.17 . (Refer to Section 7.1.1 "Configuration and roles of QD75
memory".)
QD75 buffer memory · Address 30000

The following shows setting examples for "condition data".
[Condition] Device "X0" (=QD75 READY) is OFF

condition
The value stored in buffer memory addresses "800, 801" (= " Md.20 Current
feed value") is "1000" or larger.

started in "simultaneous start"
Simultaneously starting "axis 2 positioning data No.3".

[Condition] · [Condition]
![Page 434 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Multiple axes simultaneous start control procedure](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-434.webp?w=400)
The "multiple axes simultaneous start control" starts and controls the multiple axes simultaneously by outputting pulses to the axis to be started at the same timing as the start axis. The maximum of four axes can be started simultaneously.
The multiple axes simultaneous start control is carried out by setting the simultaneous start an object axis start data No. (positioning data No. to start simultaneously for each axis) to the multiple axes simultaneous start control buffer memory " Cd.30 to Cd.33 Simultaneous starting axis start data No. (1 to
4 axis start data No.)" of the axis control data, and the "9004" to " Cd.3 positioning start No." of the start axis, and then turning ON the positioning
start signal.
(1) An error will occur and all simultaneously started axes will not start (error
code: 501) if the simultaneously started axis start data No. is not set to the axis control data on the start axis or set outside the setting range. (2) An error will occur and all simultaneously started axes will not start (error
code: 501) if either of the simultaneously started axes is BUSY. (3) An error will occur and all simultaneously started axes will not start (error
code: 501) if an error occurs during the analysis of the positioning data on the simultaneously started axes. (4) No error or warning will occur if only the start axis is the simultaneously
started axis. (5) This function cannot be used with the sub function Section 12.7.8 "Pre-
reading start function".
The procedure for multiple axes simultaneous start control is as follows.
Set " Cd. 30 to Cd. 33 Simultaneously started data No.".
Write [9004] to " Cd. 3 Positioning start No.".
Turn ON the positioning start signal to be started.
1) · 2) · 3)
![Page 435 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [5] Setting examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-435.webp?w=400)
The following shows the setting of the data used to execute the multiple axes simultaneous start control with positioning start signals (The axis control data on the start axis is set).
value Setting details Axis
Cd.3 Positioning start No. 9004 Set the multiple axes simultaneous start control start No. "9004". 1500 1600 1700 1800
Simultaneous starting axis start data No. (Axis 1 start data No.)
Cd.30
1540 1640 1740 1840
Simultaneous starting axis start data No. (Axis 2 start data No.)
Cd.31
1541 1641 1741 1841
Set the simultaneously started axis start data No. Set a "0" for the axis other than the simultaneously started axes.
Simultaneous starting axis start data No. (Axis 3 start data No.)
Cd.32
1542 1642 1742 1842
Simultaneous starting axis start data No. (Axis 4 start data No.)
Cd.33
1543 1643 1743 1843
Refer to Section 5.7 "List of control data" for information on setting details.
The following shows the setting examples in which the axis 1 is used as the start axis and the simultaneously started axes are used as the axes 2 and 4.
value Setting details Buffer memory address
Cd.3 Positioning start No. 9004 Set the multiple axes simultaneous start control start No. "9004". 1500
Simultaneous starting axis start data No. (Axis 1 start data No.)
100 The axis 1 starts the positioning data No. 100. 1540
Cd.30
Simultaneous starting axis start data No. (Axis 2 start data No.)
200 Immediately after the start of the axis 1, the axis 2 starts the axis 2 positioning data No. 200.
Cd.31
Simultaneous starting axis start data No. (Axis 3 start data No.)
Cd.32
0 Will not start simultaneously. 1542
Simultaneous starting axis start data No. (Axis 4 start data No.)
300 Immediately after the start of the axis 1, the axis 4 starts the axis 4 positioning data No. 300.
Cd.33

(1) The "multiple axes simultaneous start control" carries out an operation equivalent to the
"simultaneous start" using the "block start data". (2) The setting of the "multiple axes simultaneous start control" is easier than that of the

10.6.1 Starting high-level positioning control
To execute high-level positioning control, a sequence program must be created to start the control in the same method as for major positioning control.
The following shows the procedure for starting the "1st point block start data" (regarded as block No. 7000) set in axis 1.
Drive unit Buffer memory
Control by designated positioning data
ON
When carrying out a positioning start with the next scan after a positioning operation is completed, input signal X10 as an interlock so that the start is carried out once the X10 signal turns OFF after the Y10 signal turns OFF.
Fig. 10.2 High-level positioning control start procedure

The following shows an example of a start program for high-level positioning control in which the 1st point " block start data" of axis 1 is started. (The block No. is regarded as "7000".)
The following control data must be set to execute high-level positioning control. The setting is carried out using a sequence program.

Cd.3 Positioning start No. 7000 Set "7000" to indicate control using " block start data". 1500 1600 1700 1800
Cd.4 Positioning starting point No. 1 Set the point No. of the " block start data" to be started. 1501 1601 1701 1801
Refer to Section 5.7 "List of control data" for details on the setting details.
The following conditions must be fulfilled when starting the control. The required conditions must also be integrated into the sequence program, and configured so the control does not start unless the conditions are fulfilled.

PLC READY signal ON PLC CPU preparation completed Y0
Axis stop signal OFF Axis stop signal is OFF Y4 Y5 Y6 Y7
Start complete signal OFF Start complete signal is OFF X10 X11 X12 X13
BUSY signal OFF BUSY signal is OFF XC XD XE XF
Error detection signal OFF There is no error X8 X9 XA XB
M code ON signal OFF M code ON signal is OFF X4 X5 X6 X7
Drive unit READY signal ON Drive unit preparation completed –
Upper limit (FLS) ON Within limit range – External signal

The following chart shows a time chart in which the positioning data No. 1, 2, 10, 11, and 12 of axis 1 are continuously executed as an example.
(1) Block start data setting example

(2) Positioning data setting example

(3) Start time chart

1st point [buffer memory address 26000] 2nd point [buffer memory address 26001]
Fig. 10.3 Start time chart for high-level positioning control (block start)


K1 K7000 K1500 H0 TO
K1 K1 K1501 H0 TO

The details and usage of manual control are explained in this chapter. In manual control, pulse output commands are issued during a JOG operation and an inching operation executed by the turning ON of the JOG START signal, or from a manual pulse generator connected to the QD75. Manual control using a sequence program from the PLC CPU is explained in this chapter. Refer to GX Configurator-QP Operating Manual for an explanation of manual control (JOG operation, inching operation and manual pulse generator operation) using the peripheral devices.
11.1 Outline of manual control 11- 2 11.1.1 Three manual control methods 11- 2 11.2 JOG operation 11- 4 11.2.1 Outline of JOG operation 11- 4 11.2.2 JOG operation execution procedure 11- 7 11.2.3 Setting the required parameters for JOG operation 11- 8 11.2.4 Creating start programs for JOG operation 11- 10 11.2.5 JOG operation example 11- 13 11.3 Inching operation 11- 17 11.3.1 Outline of inching operation 11- 17 11.3.2 Inching operation execution procedure 11- 20 11.3.3 Setting the required parameters for inching operation 11- 21 11.3.4 Creating a program to enable/disable the inching operation 11- 22 11.3.5 Inching operation example 11- 25 11.4 Manual pulse generator operation 11- 27 11.4.1 Outline of manual pulse generator operation 11- 27 11.4.2 Manual pulse generator operation execution procedure 11- 31 11.4.3 Setting the required parameters for manual pulse generator operation .11- 32 11.4.4 Creating a program to enable/disable the manual pulse generator operation 11- 33

11.1.1 Three manual control methods
"Manual control" refers to control in which positioning data is not used, and a positioning operation is carried out in response to signal input from an external source. The three types of this "manual control" are explained below.
"JOG operation" is a control method in which the machine is moved by only a movement amount (pulses are continuously transmitted while the JOG START signal is ON). This operation is used to move the workpiece in the direction in which the limit signal is ON, when the operation is stopped by turning the limit signal OFF to confirm the positioning system connection and obtain the positioning data address (Refer to Section 12.7.4 "Teaching function").
Movement continues while the JOG START signal is ON.
ON OFF
Fig. 11.1 JOG operation
"Inching operation" is a control method in which a minute movement amount of pulses is output manually in one control cycle. When the "inching movement amount" of the axis control data is set by JOG operation, the workpiece is moved by a set movement amount. (When the "inching movement amount" is set to "0", the machine functions as JOG operation.)
JOG start signal is turned ON to move the workpiece by the movement amount of pulses which is output in one control cycle.
Fig. 11.2 Inching operation
JOG start signal · JOG start signal

"Manual pulse generator operation" is a control method in which positioning is carried out in response to the No. of pulses input from a manual pulse generator (the No. of input pulses is output). This operation is used for manual fine adjustment, etc., when carrying out accurate positioning to obtain the positioning address.
Movement in response to the command pulses
M
Fig. 11.3 Manual pulse generator control
Refer to Section 3.2.4 "Combination of QD75 major functions and sub functions" for details on "sub functions" that can be combined with manual control. Also refer to Chapter 12 "Control sub functions" for details on each sub function.
"JOG operation", "Inching operation" and enabling/disabling of the "manual pulse generator operation" can be executed from GX Configurator-QP test mode. Refer to GX Configurator-QP Operating Manual for details on manual control from GX Configurator-QP.
Refer to Section 5.6 "List of monitor data" when directly monitoring the buffer memory using GX Developer. Also refer to GX Configurator-QP Operating Manual when monitoring with the monitor functions of GX Configurator-QP.
Output pulses · Pulse input · Manual pulse generator

11.2.1 Outline of JOG operation

Use the hardware stroke limit function when carrying out JOG operation near the upper or lower limits. (Refer to Section 12.4.4). * If the hardware stroke limit function is not used, the workpiece may exceed the
In JOG operation, the FORWARD run JOG start signal (Y8, YA, YC, YE) or REVERSE run JOG start signal (Y9, YB, YD, YF) turns ON, causing pulses to be output to the drive unit from the QD75 while the signal is ON. The workpiece is then moved in the designated direction. The following shows examples of JOG operation.
When the START signal turns ON, acceleration begins in the direction designated by the START signal, and continues for the acceleration time designated in " Pr.32 JOG
operation acceleration time selection". At this time, the BUSY signal changes from OFF to ON.
the movement continues at this speed. The constant speed movement takes place at 2) and 3).
When the START signal is turned OFF, deceleration begins from the speed set in " Cd.17 JOG speed", and continues for the deceleration time designated in " Pr.33
JOG operation deceleration time selection".
Cd. 17 JOG speed
Acceleration for the acceleration time selected in Pr. 32
Deceleration for the deceleration time selected in Pr. 33
PLC READY signal [Y0] OFF
QD75 READY signal [X0]
OFF ON
Forward run JOG start signal [Y8, YA, YC, YE]
Reverse run JOG start signal [Y9, YB, YD, YF]
ON
BUSY signal[XC, XD, XE, XF] OFF
Fig. 11.4 JOG operation

The following details must be understood before carrying out JOG operation.
(1) For safety, first set " Cd.17 JOG speed" to a smaller value and check the
movement. Then gradually increase the value. (2) An axis error will occur and the operation will not start (error code: 300) if the
"JOG speed" is outside the setting range at the JOG start. (3) An axis error will occur and the operation will not start (error code: 956) if
" Pr.31 JOG speed limit value" is set to a value larger than " Pr.8 speed limit
value". (4) If " Cd.17 JOG speed" exceeds the speed set in " Pr.31 JOG speed limit
value", the workpiece will move at the " Pr.31 JOG speed limit value" and an
"Axis warning" will occur in the QD75 (warning code: 301). (5) The JOG operation can be continued even if an "Axis warning" has occurred. (6) A JOG start signal OFF ON immediately after the stop signal ON OFF (within 100ms) will be ignored. (The operation will not start.) (7) Set a "0" in " Cd.16 inching movement amount". If a value other than "0" is
set, the operation will become an inching operation (Refer to Section 11.3 "Inching operation").
When the operation is stopped by the stroke limit (limit signal OFF), JOG operation can be performed in the direction in which the limit signal turns ON after an error reset. (An error will occur again if the JOG start signal in the direction in which the limit signal turns OFF is turned ON.)
JOG operation possible JOG operation not possible
OFF
JOG operation V · Upper/lower limit signal

The following drawing shows details of the JOG operation timing and processing time.

Forward run JOG start signal [Y8, YA, YC, YE] t2
Reverse run JOG start signal [Y9, YB, YD, YF]
Fig. 11.5 JOG operation timing and processing times
t1 t2 t3 t4
1.0 to 3.0 0 to 1.8 2.7 to 4.4 0 to 1.8

The JOG operation is carried out by the following procedure.
One of the following two methods can be used.
Refer to Chapter 5 and Section 11.2.3.
Pr.1 ) Pr.39
Directly set (write) the parameters in the QD75 using GX
Configurator-QP.
Set (write) the parameters from the PLC CPU to the QD75 using the sequence program (TO command).
Set a "0" in " Cd. 16 Inching movement amount".
Refer to Section 11.2.4.
Set the " Cd. 17 JOG speed".
Using GX Developer, set the control data and create a sequence program for executing the JOG operation. (Set the control data in the QD75 buffer memory using the TO command.)
Create a sequence program in which the "JOG start signal" is turned ON by a JOG operation start command.
STEP 3 Write the sequence program created in STEP 1 and STEP 2 to the PLC CPU using GX Developer.
Write the sequence program to the PLC CPU.
Refer to Chapter 6.
Turn ON the JOG start signal. STEP 4
Axis 3 Axis 2 JOG operation start
Turn ON the JOG start signal of the axis to be started.
Forward run JOG start signal Reverse run JOG start signal
YC
YE
Y8
Y9
YB
YD
YF
STEP 5
One of the following two methods can be used.
Monitoring of the JOG operation
Monitor the JOG operation status.
Monitor using GX Configurator-QP.
Monitor using GX Developer.
Stop the JOG operation when the JOG start signal is turned OFF using the sequence program in STEP 2.
Turn OFF the JOG operation start signal that is ON.

The "Parameters" must be set to carry out JOG operation. The following table shows the setting items of the required parameters for carrying out JOG operation. When only JOG operation will be carried out, no parameters other than those shown below need to be set. (Use the initial values or setting values within a range where no error occurs for trouble-free operation.)

Pr.2 No. of pulses per rotation (Ap) (Unit: pulse) 20000
Pr.3 Movement amount per rotation (Al) (Unit: pulse) 20000
Pr.6 Rotation direction setting 0 (current value increases by forward run pulse output)
Pr.12 Software stroke limit upper limit value (Unit: pulse) 2147483647
Pr.13 Software stroke limit lower limit value (Unit: pulse) –2147483648
Pr.14 Software stroke limit selection 0 (current feed value)
Pr.23 Output signal logic selection 0 (Pulse output to drive unit is negative logic.)
: Setting always required. : Set according to requirements (Leave set to the initial value when not used.)


Pr.32 JOG operation acceleration time selection 0 (acceleration time 0)
Pr.33 JOG operation deceleration time selection 0 (deceleration time 0)
Pr.34 Acceleration/deceleration process selection 0 (trapezoidal acceleration/ deceleration processing)
Pr.37 Stop group 1 sudden stop selection 0 (deceleration stop)
Pr.38 Stop group 2 sudden stop selection 0 (deceleration stop)
Pr.39 Stop group 3 sudden stop selection 0 (deceleration stop)
: Setting always required. : Set according to requirements (Leave set to the initial value when not used.)

A sequence program must be created to execute a JOG operation. Consider the "required control data setting", "start conditions" and "start time chart" when creating the program. The following shows an example when a JOG operation is started for axis 1. (" Cd.17 JOG speed" is set to "100.00mm/min" in the example shown.)
The control data shown below must be set to execute a JOG operation. The setting is carried out with the sequence program.

Cd.16 Inching movement amount 0 Set “0”. 1517 1617 1717 1817
Set a value equal to or above the " Pr.7 Bias
speed at start" and equal to or below the
Refer to Section 5.7 "List of control data" for details on the setting details.
The following conditions must be fulfilled when starting. The required conditions must also be assembled in the sequence program, and the sequence program must be configured so the operation will not start if the conditions are not fulfilled.

PLC READY signal ON PLC CPU preparation completed Y0
Axis stop signal OFF Axis stop signal is OFF Y4 Y5 Y6 Y7
Start complete signal OFF Start complete signal is OFF X10 X11 X12 X13
BUSY signal OFF QD75 is not operating XC XD XE XF
Error detection signal OFF There is no error X8 X9 XA XB
M code ON signal OFF M code ON signal is OFF X4 X5 X6 X7
Drive unit READY signal ON Drive unit preparation completed –
Upper limit (FLS) ON Within limit range – External signal
If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking. If it is set to the synchronous mode, it must not be
inserted in the program for interlocking because it is turned ON when the PLC CPU executes
calculation.


Fig. 11.6 JOG operation start time chart



When the "stop signal" is turned ON during JOG operation
When the "stop signal" is turned ON during JOG operation, the JOG operation will stop by the "deceleration stop" method. JOG start signals will be ignored while the stop signal is ON. The operation can be started by turning the stop signal OFF, and turning the JOG start signal from OFF to ON again.

A JOG start signal OFF ON while the stop signal is ON will be ignored.
ON Forward run JOG start signal [Y8, YA, YC, YE]
Fig. 11.7 Operation when the stop signal is turned ON during JOG operation
The QD75 will not receive a "JOG start signal" while the "stop signal" is ON.

When both the "forward run JOG start signal" and "reverse run JOG start signal" are turned ON simultaneously for one axis
When both the "forward run JOG start signal" and "reverse run JOG start signal" are turned ON simultaneously for one axis, the "forward run JOG start signal" is given priority. In this case, the "reverse run JOG start signal" is validated when the QD75 BUSY signal is turned OFF. If the forward run JOG operation is stopped due to stop or axis error by a stop signal, the reverse run JOG operation will not be executed even if the "reverse run JOG start signal" turns ON.

Forward run JOG start signal [Y8, YA, YC, YE]
Fig. 11.8 Operation when both the forward run JOG start signal and reverse run JOG start signal are
turned ON simultaneously

When the "JOG start signal" is turned ON again during deceleration caused by the ON OFF of the "JOG start signal"
When the "JOG start signal" is turned ON again during deceleration caused by the ON OFF of the "JOG start signal", the JOG operation will be carried out from the time the "JOG start signal" is turned ON.

Forward run JOG start signal [Y8, YA, YC, YE]
Fig. 11.9 Operation when the JOG start signal is turned ON during deceleration
When the "JOG start signal" is turned ON during a peripheral device test mode
When the "JOG start signal" is turned ON during a peripheral device test mode, it will be ignored and the JOG operation will not be carried out.

Forward run JOG operation execution JOG operation not possible because this is not the rising edge of the JOG start signal
JOG operation not possible because the operation is in the test mode
Fig. 11.10 Operation when the JOG start signal is turned ON during a test mode

When the "JOG start signal" is turned ON immediately after the stop signal OFF (within 100ms)
When the "JOG start signal" is turned ON immediately after the stop signal OFF (within 100ms), it will be ignored and the JOG operation will not be carried out.
Forward run JOG operation
Forward run JOG start signal [Y8, YA, YC, YE]
ON
OFF
[Y4, Y5, Y6, Y7]
A rise of JOG start signal is ignored.
Fig. 11.11 Operation when the JOG start signal is turned ON immediately after the stop signal OFF
Axis stop signal · 100ms

11.3.1 Outline of inching operation

When the inching operation is carried out near the upper or lower limit, use the hardware stroke limit function (Refer to Section 12.4.4).
If the hardware stroke limit function is not used, the workpiece may exceed the
In inching operation, pulses are input to the drive unit at the first control cycle (1.8 ms) to move the workpiece by a designated movement amount after the forward run JOG start signal [Y8, YA, YC, YE] or reverse JOG start signal [Y9, YB, YD, YF] is turned ON. The following shows the example of inching operation.
amount".
Forward run inching operation
PLC READY signal [Y0]
ON
OFF QD75 READY signal [X0]
Forward run JOG start signal [Y8,YA,YC,YE]
ON
BUSY signal [XC,XD,XE,XF] OFF
Positioning complete signal [X14,X15,X16,X17]
Positioning complete signal output time Pr.40
Fig. 11.12 Inching operation
2) · 1)

The following details must be understood before inching operation is carried out. (1) Acceleration/deceleration processing is not carried out during inching
operation. (Pulses corresponding to the designated inching movement amount are output at the first control cycle of the QD75 (1.8 ms). The movement direction of inching operation is reversed and, when a backlash compensation is carried out, first pulses corresponding to the backlash amount are output in the first control cycle of the QD75 and then pulses corresponding to the designated inching movement amount are output in the subsequent control cycles.) The " Cd.17 JOG speed" is ignored even if it is set. An error will occur in the
following cases (error code: 301). ( Cd.16 Inching movement amount) x (A) > ( Pr.31 JOG speed limit value)
(2) JOG start signal OFF ON immediately after stop signal ON OFF (within 100 ms) is ignored. (Operation will not start.)
(3) Set a value other than a "0" in " Cd.16 Inching movement amount".
If a "0" is set, the operation will become JOG operation (Refer to Section 11.2 "JOG operation".
When the operation is stopped by the stroke limit (limit signal OFF), inching operation can be performed in the direction in which the limit signal turns ON after an error reset. (An error will occur again if the JOG start signal in the direction in which the limit signal turns OFF is turned ON.)
Inching operation not possible
OFF

The following drawing shows the details of the inching operation timing and processing time.

Fig. 11.13 Inching operation timing and processing times
t1 t2 t3 t4
1.0 to 3.0 2.7 to 4.4 0 to 1.8 Depending on
parameters

The inching operation is carried out by the following procedure.
Set the parameters.
One of the following two methods can be used.
Refer to Chapter 5 and Section 11.3.3.
Pr.1 ) Pr.31
Directly set (write) the parameters in the QD75 using GX
Configurator-QP.
Set (write) the parameters from the PLC CPU to the QD75 using the sequence program (TO command).
Refer to Section 11.3.4.
Set the " Cd.16 inching movement amount". (Control data setting)
Using GX Developer, set the control data and create a sequence program for executing the inching operation. (Set the control data in the QD75 buffer memory using the TO command.)
Create a sequence program in which the "JOG start signal" is turned ON by an inching operation start command.
STEP 3 Write the sequence program created in STEP 1 and STEP 2 to the PLC CPU using GX Developer.
Write the sequence program to the PLC CPU.
Refer to Chapter 6.
Turn ON the JOG start signal. STEP 4
Axis 3 Axis 2 Inching operation start
Turn ON the JOG start signal of the axis to be started.
Forward run JOG start signal Reverse run JOG start signal
YC
YE
Y8
Y9
YB
YD
YF
STEP 5
One of the following two methods can be used.
Monitoring of the inching operation
Monitor the inching operation status.
Monitor using GX Configurator-QP.
Monitor using GX Developer.
End the inching operation after moving a workpiece by an inching movement amount with the sequence program created in STEP 2.
Turn OFF the JOG operation start signal that is ON.

The "Parameters" must be set to carry out inching operation. The following table shows the setting items of the required parameters for carrying out inching operation. When only inching operation will be carried out, no parameters other than those shown below need to be set. (Use the initial values or setting values within a range where no error occurs for trouble-free operation.)

Pr.2 No. of pulses per rotation (Ap) (Unit: pulse) 20000
Pr.3 Movement amount per rotation (Al) (Unit: pulse) 20000
Pr.6 Rotation direction setting 0 (current value increases by forward run pulse output)
Pr.12 Software stroke limit upper limit value (Unit: pulse) 2147483647
Pr.13 Software stroke limit lower limit value (Unit: pulse) –2147483648
Pr.14 Software stroke limit selection 0 (current feed value)
Pr.23 Output signal logic selection 0 (Pulse output to the drive unit is negative logic)
: Setting always required. : Set according to requirements (Leave set to the initial value when not used.)

A sequence program must be created to execute an inching operation. Consider the "required control data setting", "start conditions", and "start time chart" when creating the program. The following shows an example when an inching operation is started for axis 1. (The example shows the inching operation when a "10.0 µm" is set in " Cd.16 Inching
movement amount".)
The control data shown below must be set to execute an inching operation. The setting is carried out with the sequence program.

Set the setting value so that the command pulse is not increased larger than the maximum output pulse. (The maximum output pulse is 1 Mpps for QD75D : differential drive output system), or 200 kpps for QD75P : open collector output system.)
Refer to Section 5.7 "List of control data" for information on setting details.
The following conditions must be fulfilled when starting. The required conditions must also be assembled in the sequence program, and the sequence program must be configured so the operation will not start if the conditions are not fulfilled.

PLC READY signal ON PLC CPU preparation completed Y0
Axis stop signal OFF Axis stop signal is OFF Y4 Y5 Y6 Y7
Start complete signal OFF Start complete signal is OFF X10 X11 X12 X13
BUSY signal OFF QD75 is not operating XC XD XE XF
Error detection signal OFF There is no error X8 X9 XA XB
M code ON signal OFF M code ON signal is OFF X4 X5 X6 X7
Drive unit READY signal ON Drive unit preparation completed –
Upper limit (FLS) ON Within limit range – External signal
If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking. If it is set to the synchronous mode, it must not be inserted in the program for interlocking because it is turned ON when the PLC CPU executes calculation.
Start conditions


Fig. 11.14 Inching operation start time chart


Creating the program

When "stop signal" is turned ON during inching operation:
If "stop signal" is turned ON during inching operation, the inching operation will be stopped. While the stop signal is turned ON, the JOG start signal is ignored. The inching operation can be re-started when the stop signal is turned OFF and then re-turned ON.

while the stop signal is ON will be ignored.
Fig. 11.15 Operation when stop signal is turned ON during inching operation
The QD75 will not accept "JOG start signal" while "stop signal" is turned ON.

When "JOG start signal" is turned ON when peripheral devices are in the
If "JOG star signal" is turned ON when peripheral devices are in the test mode, the "JOG start signal" will be ignored and inching operation will not be carried out.

Inching operation not possible because JOG start signal does not rise
Forward run inching operation executed Inching operation not possible because the operation is in the test mode.
Fig. 11.16 Operation when JOG start signal is turned ON in test mode
(within 100 ms):
If "JOG start signal" is turned ON immediately after the stop signal is turned OFF (within 100 ms), the "JOG start signal" will be ignored and inching operation will not be carried out.

Fig. 11.17 Operation when JOG start signal is turned ON immediately after stop signal is turned OFF

11.4.1 Outline of manual pulse generator operation
Important
Create the sequence program so that " Cd.21 Manual pulse generator enable
flag" is always set to "0" (disabled) when a manual pulse generator operation is not carried out.
Mistakenly touching the manual pulse generator when the manual pulse generator enable flag is set to "1" (enable) can cause accidents or incorrect positioning.
In manual pulse generator operations, pulses are input to the QD75 from the manual pulse generator. This causes the same No. of input pulses to be output from the QD75 to the servo amplifier, and the workpiece is moved in the designated direction. The following shows and example of manual pulse generator operation.
turns ON and the manual pulse generator operation is enabled.
turns OFF and the manual pulse generator operation is disabled.
Manual pulse generator operation stops
1 0 Cd. 21 Manual pulse generator enable flag
BUSY signal [XC, XD, YE, XF]
Manual pulse generator input
Start complete signal [X10, X11, X12, X13]
Manual pulse generator operation enabled
1 If the input from the manual pulse generator stops, the machine will decelerate to a stop within 90 ms. 2 The start complete signal does not turn ON in manual pulse generator operation.
Fig. 11.18 Manual pulse generator operation

A manual pulse generator is required to carry out manual pulse generator operation.
The following details must be understood before carrying out manual pulse generator operation.
(1) The speed during manual pulse generator operation is not limited by the
" Pr.8 Speed limit value".
(2) If the " Cd.21 Manual pulse generator enable flag" is turned ON while the
QD75 is BUSY (BUSY signal ON), a warning will occur (warning code 100: start during operation). (3) If a stop factor occurs during manual pulse generator operation, the operation
will stop, and the BUSY signal will turn OFF. At this time, the " Cd.21 Manual pulse generator enable flag" will be left ON,
but manual pulse generator operation will not be possible. To carry out manual pulse generator operation again, measures must be carried out to eliminate the stop factor. Once eliminated, the operation can be carried out again by turning the " Cd.21 Manual pulse generator enable flag" ON OFF ON.
(4) Pulses will not be output if an error occurs when the manual pulse generator
operation starts.
When the operation is stopped by the stroke limit (limit signal OFF), manual pulse generator operation can be performed in the direction in which the limit signal turns ON after an error reset. (An error will occur again if pulse input is provided in the direction in which the limit signal turns OFF is turned ON.)
Manual pulse generator operation
Manual pulse generator operation possible
Manual pulse generator operation not possible
OFF
Upper/lower limit signal

The following drawing shows details of the manual pulse generator operation timing and processing time.

Cd. 21 Manual pulse generator enable flag (axis control data)
The start complete signal does not turn ON in manual pulse generator operation.
Fig. 11.19 Manual pulse generator operation timing and processing times
t1 t2 t3 t4
0 to 2.6 6.2 to 32 64 to 90 28.4 to 57.6

In manual pulse generator operation, the position is moved by a "manual pulse generator 1 pulse movement amount" per pulse. The current feed value in the positioning control by manual pulse generator operation can be calculated using the expression shown below.
Current feed value = Number of input pulses × Cd.20 Manual pulse generator 1
pulse input magnification × Manual pulse generator 1 pulse movement amount
Pr.1 Unit setting mm inch degree pulse
Manual pulse generator 1 pulse movement amount
0.1µm 0.00001inch 0.00001degree 1pulse
For example, when " Pr.1 Unit setting" is mm and " Cd.20 Manual pulse
generator 1 pulse input magnification" is 2, and 100 pulses are input from the manual pulse generator, the current feed value is as follows.
100 × 2 × 0.1 = 20 [µm]
The number of pulses output actually to the drive unit is "Manual pulse generator 1 pulse movement amount/movement amount per pulse ". For example, when " Pr.1 Unit setting" is mm and the movement amount per pulse is 1 µm, 0.1/1 =
1/10, i.e., the output to the drive unit per pulse from the manual pulse generator is 1/10 pulse. Thus, the QD75 outputs 1 pulse to the drive unit after receiving 10 pulses from the manual pulse generator.
Pr.3
Movement amount per rotation
Movement amount per pulse =
Unit magnification Pr.4
Pr.2
No. of pulses per rotation
The speed during positioning control by manual pulse generator operation is a speed corresponding to the No. of input pulses per unit time, and can be obtained using the following equation.
Output command frequency = Input frequency × Cd.20 Manual pulse generator
1 pulse input magnification

The manual pulse generator operation is carried out by the following procedure.
One of the following two methods can be used.
Refer to Chapter 5 and Section 11.4.3.
Pr.1 ) Pr.24
Directly set (write) the parameters in the QD75 using
GX Configurator-QP.
Set (write) the parameters from the PLC CPU to the QD75 using the sequence program (TO command).
Using GX Developer, set the control data and create a
Set " Cd. 20 Manual pulse generator 1 pulse input
sequence program to enable/disable the manual pulse
Refer to Section 11.4.4.
magnification". (control data setting)
generator operation. (Set the control data in the QD75 buffer memory using the TO command.)
Create a sequence program in which the enable/disable is
(" Cd. 21 Manual pulse generator enable flag" setting.) set for the manual pulse generator operation.
Write the sequence program created in STEP 1 and
Write the sequence program to the PLC CPU.
STEP 2 to the PLC CPU using GX Developer.
Manual pulse generator operation start
Issue a command to enable the manual pulse generator operation, and input the signals from the manual pulse generator.
Write "1" in " Cd.21 Manual pulse generator enable
flag", and operate the manual pulse generator.
One of the following two methods can be used.
Monitoring of the manual pulse generator operation
Monitor the manual pulse generator operation.
Monitor using GX Configurator-QP.
Monitor using GX Developer.
Manual pulse generator operation stop
End the input from the manual pulse generator, and issue a command to disable the manual pulse
Stop operating the manual pulse generator, and write "0"
in " Cd. 21 Manual pulse generator enable flag".

The "Parameters" must be set to carry out manual pulse generator operation. The following table shows the setting items of the required parameters for carrying out manual pulse generator operation. When only manual pulse generator operation will be carried out, no parameters other than those shown below need to be set. (Use the initial values or setting values within a range where no error occurs for trouble-free operation.)

Pr.2 No. of pulses per rotation (Ap) (Unit: pulse) 20000
Pr.3 Movement amount per rotation (Al) (Unit: pulse) 20000
Pr.6 Rotation direction setting 0 (current value increases by forward run pulse output)
Pr.12 Software stroke limit upper limit value (Unit: pulse) 2147483647
Pr.13 Software stroke limit lower limit value (Unit: pulse) –2147483648
Pr.14 Software stroke limit selection 0 (current feed value)
Pr.22 Input signal logic selection 0 (Manual pulse generator input is negative logic.)
Pr.23 Output signal logic selection 0 (Pulse output to drive unit is negative logic.)
Pr.24 Manual pulse generator input selection 0 (4 times multiplication of A phase/B phase)
: Setting always required. : Set according to requirements (Leave set to the initial value when not used.)
(b8), Pr.24 is set only for axis 1. (The setting for axes 2,3, and 4 is ignored.)

A sequence program must be created to execute a manual pulse generator operation. Consider the "required control data setting", "start conditions" and "start time chart" when creating the program. The following shows an example when a manual pulse generator operation is started for axis 1.
The control data shown below must be set to execute a manual pulse generator operation. The setting is carried out with the sequence program.

1 Set the manual pulse generator 1 pulse input magnification.
Set "1: Enable manual pulse generator operation". (Set "0: Disable manual pulse generator operation" when finished with the manual pulse generator operation.)
Refer to Section 5.7 "List of control data" for details on the setting details.
The following conditions must be fulfilled when starting. The required conditions must also be assembled in the sequence program, and the sequence program must be configured so the operation will not start if the conditions are not fulfilled.

PLC READY signal ON PLC CPU preparation completed Y0
Axis stop signal OFF Axis stop signal is OFF Y4 Y5 Y6 Y7
Start complete signal OFF Start complete signal is OFF X10 X11 X12 X13
BUSY signal OFF QD75 is not operating XC XD XE XF
Error detection signal OFF There is no error X8 X9 XA XB
M code ON signal OFF M code ON signal is OFF X4 X5 X6 X7
Drive unit READY signal ON Drive unit preparation completed –
Upper limit (FLS) ON Within limit range – External signal
If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking. If it is set to the synchronous mode, it must not be
inserted in the program for interlocking because it is turned ON when the PLC CPU executes
calculation.


Cd. 20 Manual pulse generator 1 pulse input magnification
Fig. 11.20 Manual pulse generator operation start time chart



MEMO

The details and usage of the "sub functions" added and used in combination with the main functions are explained in this chapter.
A variety of sub functions are available, including functions specifically for machine OPR and generally related functions such as control compensation, etc. More appropriate, finer control can be carried out by using these sub functions. Each sub function is used together with a main function by creating matching parameter settings and sequence programs. Read the execution procedures and settings for each sub function, and set as required.
12.1 Outline of sub functions 12- 2 12.1.1 Outline of sub functions 12- 2 12.2 Sub functions specifically for machine OPR 12- 4 12.2.1 OPR retry function 12- 4 12.2.2 OP shift function 12- 8 12.3 Functions for compensating the control 12- 11 12.3.1 Backlash compensation function 12- 11 12.3.2 Electronic gear function 12- 13 12.3.3 Near pass function 12- 18 12.4 Functions to limit the control 12- 21 12.4.1 Speed limit function 12- 21 12.4.2 Torque limit function 12- 23 12.4.3 Software stroke limit function 12- 26 12.4.4 Hardware stroke limit function 12- 32 12.5 Functions to change the control details 12- 34 12.5.1 Speed change function 12- 34 12.5.2 Override function 12- 41 12.5.3 Acceleration/deceleration time change function 12- 44 12.5.4 Torque change function 12- 48 12.6 Absolute position restoration function 12- 50 12.7 Other functions 12- 58 12.7.1 Step function 12- 58 12.7.2 Skip function 12- 63 12.7.3 M code output function 12- 66 12.7.4 Teaching function 12- 70 12.7.5 Target position change function 12- 77 12.7.6 Command in-position function 12- 81 12.7.7 Acceleration/deceleration processing function 12- 84 12.7.8 Pre-reading start function 12- 87 12.7.9 Deceleration start flag function 12- 92 12.7.10 Stop command processing for deceleration stop function 12- 96

"Sub functions" are functions that compensate, limit, add functions, etc., to the control when the main functions are executed. These sub functions are executed by parameter settings, commands from GX Configurator-QP, sub function sequence programs, etc.
The following table shows the types of sub functions available.
This function retries the machine OPR with the upper/lower limit switches during machine OPR. This allows machine OPR to be carried out even if the axis is not returned to before the near-point dog with JOG operation, etc. Functions characteristic to machine OPR OP shift function
After returning to the machine OP, this function offsets the position by the designated distance from the machine OP position and sets that position as the OP address.
This function compensates the mechanical backlash. Feed pulses equivalent to the set backlash amount are output each time the movement direction changes.
Functions that compensate control
By setting the movement amount per pulse, this function can freely change the machine movement amount per commanded pulse. When the movement amount per pulse is set, a flexible positioning system that matches the machine system can be structured.
Near pass function 1 This function suppresses the machine vibration when the speed changes during continuous path control in the interpolation control.
If the command speed exceeds " Pr.8 Speed limit value" during control,
this function limits the commanded speed to within the " Pr.8 Speed limit
value" setting range.
If the torque generated by the servomotor exceeds " Pr.17 Torque limit
Functions that limit control
Torque limit function 2
setting value" during control, this function limits the generated torque to within the " Pr.17 Torque limit setting value" setting range.
If a command outside of the upper/lower limit stroke limit setting range, set in the parameters, is issued, this function will not execute positioning for that command.
Software stroke limit function
Hardware stroke limit function
This function carries out deceleration stop with the limit switch connected to the QD75 external device connector.
This function changes the speed during positioning. Set the changed speed in the speed change buffer memory ( Cd.14 New
speed value), and change the speed with the speed change request ( Cd.15 Speed change request).
Functions that change control details
This function changes the speed within a percentage of 1 to 300% during positioning. This is executed using " Cd.13 Positioning operation speed
override". Acceleration/deceleration time change function
This function changes the acceleration/deceleration time during speed change.
Torque change function This function changes the "torque limit value" during control.
1 The near pass function is validated only when the machine of the standard specification carries out the position control with the continuous path control mode. It cannot be invalidated with parameters. 2 To carry out "torque limit", the "D/A conversion module" and a "drive unit capable of the torque limit command with an analog voltage" must be prepared.

Absolute position restoration function 3 This function restores the absolute position of the designated axis.
This function temporarily stops the operation to confirm the positioning operation during debugging, etc. The operation can be stopped at each "automatic deceleration" or "positioning data".
Skip function This function stops the positioning being executed (decelerates to a stop) when the skip signal is input, and carries out the next positioning.
M code output function This function issues a sub work (clamp or drill stop, tool change, etc.) according to the code No. (0 to 65535) set for each positioning data.
This function stores the address positioned with manual control into the positioning address ( Da.6 Positioning address/movement amount) having
the designated positioning data No.
Target position change function
This function changes the target position during the execution of positioning. At the same time, this also can change the speed.
At each automatic deceleration, this function calculates the remaining distance for the QD75 to reach the positioning stop position, and when the value is less than the set value, sets the "command in-position flag". When using another sub work before ending the control, use this function as a trigger for the sub work.
Acceleration/deceleration process function This function adjusts the control acceleration/deceleration.
Pre-reading start function This function shortens the virtual start time.
Function that turns ON the flag when the constant speed status or acceleration status switches to the deceleration status during position control, whose operation pattern is "Positioning complete", to make the stop timing known.
Deceleration start flag function
Stop command processing for deceleration stop function
Function that selects a deceleration curve when a stop cause occurs during deceleration stop processing to speed 0.
3 "The 16-point input module", "16-point output module", and "the drive unit capable of configuring an absolute position detection system" are required to execute the "absolute position restoration function".
![Page 480 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-480.webp?w=400)
The sub functions specifically for machine OPR include the "OPR retry function" and "OP shift function". Each function is executed by parameter setting.
When the workpiece goes past the OP without stopping during positioning control, it may not move back in the direction of the OP although a machine OPR is commanded, depending on the workpiece position. This normally means the workpiece has to be moved to a position before the near-point dog by a JOG operation, etc., to start the machine OPR again. However, by using the OPR retry function, a machine OPR can be carried out regardless of the workpiece position.
The details shown below explain about the "OPR retry function". [1] Control details [2] Precautions during control [3] Setting the OPR retry function
The following drawing shows the operation of the OPR retry function. (1) OPR retry point return retry operation when the workpiece is within the range
between the upper and lower limits.
direction opposite to the " Pr.44 OPR direction".
direction". 6) Machine OPR completion
Limit signal OFF ON
Fig. 12.1 OPR retry operation by limit signal detection

(2) OPR retry operation when the workpiece is outside the range between the upper and lower limits.
normal machine OPR is carried out.
Machine OPR start OP
Pr. 44 OPR direction
Upper limit Lower limit
direction", the operation carries out a deceleration stop when the near-point dog turns OFF, and then carries out a machine OPR in the direction set in " Pr.44 OPR direction".
Pr. 44 OPR direction
Upper limit Lower limit
direction". When "0: Positive direction" is set in Pr.44 , check that the limit switch placed in the OPR direction acts as the upper limit. When "1: Negative direction" is set in Pr.44 , check that the limit switch placed in the OPR direction acts as the lower limit. Incorrect wiring of these limit switches may cause improper OPR retry operation. If any malfunction is identified, check and correct " Pr.6 Rotation direction setting" and the wiring.
Fig. 12.2 OPR retry operation from on limit (limit switch OFF)

(3) Setting the dwell time during an OPR retry The OPR retry function can perform such function as the dwell time using " Pr.57 Dwell time at OPR retry" when the reverse run operation is carried
out due to detection by the limit signal for upper and lower limits and when the machine OPR is executed after the near point dog is turned OFF to stop the operation.
" Pr.57 Dwell time during OPR" is validated when the operation stops at
the "A" and "B" positions in the following drawing. (The dwell time is the same value at both positions "A" and "B".)

Fig. 12.3 Setting the dwell time during an OPR retry

(1) The following table shows whether the OPR retry function may be executed by the " Pr.43 OPR method".
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precaution during control diagram (page 483)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-483-1.webp)
Pr.43 OPR method Execution status of OPR retry function
(2) Always establish upper/lower limit switches at the upper/lower limit positions of the machine, and connect an QD75 module. If the OPR retry function is used without hardware stroke limit switches, the motor will continue rotation until a hardware stroke limit signal is detected.
(3) Always wire QD75 upper/lower limit switches even when the OPR function is invalidated. Control cannot be carried out with the QD75 unless the wiring is carried out.
(4) Do not carry out settings so that the drive unit power turns OFF by the upper/lower limit switches connected to the QD75. If the drive unit power is turned OFF, the OPR retry cannot be carried out.
To use the "OPR retry function", set the required details in the parameters shown in the following table, and write them to the QD75. When the parameters are set, the OPR retry function will be added to the machine OPR control. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0). Set " Pr.57 Dwell time during OPR retry"
according to the user's requirements.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the OPR retry function diagram (page 483)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-483-2.webp)
Pr.48 OPR retry 1 Set "1: Carry out OPR retry by limit switch". 0
Set the deceleration stop time during OPR retry. (Random value between 0 and 65535 (ms)) 0
Refer to Section 5.2 "List of parameters" for setting details.
![Page 484 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-484.webp?w=400)
When a machine OPR is carried out, the OP is normally established using the near- point dog, stopper, and zero signal. However, by using the OP shift function, the machine can be moved a designated movement amount from the position where the zero signal was detected. A mechanically established OP can then be interpreted at that point. The OP shift function can be used without relation to " Pr.43 OPR method".
The details shown below explain about the "OP shift function". [1] Control details [2] Setting range for the OP shift amount [3] Movement speed during OP shift [4] Precautions during control [5] Setting the OP shift function
The following drawing shows the operation of the OP shift function.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Control details diagram (page 484)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-484-1.webp)
Speed selected by the " Pr. 56 Speed designation during OP shift"
Shift operation carried out after the deviation counter clear and reset.
Fig. 12.4 OP shift operation
![Page 485 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Movement speed during OP shift](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-485.webp?w=400)
Set the OP shift amount within the range from the detected zero signal to the upper/lower limit switches.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Setting range for the OP shift amount diagram (page 485)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-485-1.webp)
Setting range of the negative OP shift amount Setting range of the positive OP shift amount
Fig. 12.5 Setting range for the OP shift amount
When using the OP shift function, the movement speed during the OP shift is set in " Pr.56 Speed designation during OP shift". The movement speed during the
OP shift is selected from either the " Pr.46 OPR speed" or the " Pr.47 Creep
speed". The following drawings show the movement speed during the OP shift when a mechanical OPR is carried out by the near-point dog method. (1) OP shift operation at the " Pr.46 OPR speed"
(When " Pr.56 speed designation during OP shift" is 0)
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Movement speed during OP shift diagram (page 485)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-485-2.webp)
When the " Pr. 53 OP shift amount" is positive
When the " Pr. 53 OP shift amount" is negative
Fig. 12.6 OP shift operation at the OPR speed

(2) OP shift operation at the " Pr.47 Creep speed"

(When " Pr.56 Speed designation during OP shift" is 1)
When the " Pr. 53 OP shift amount" is positive
When the " Pr. 53 OP shift amount" is negative
Fig. 12.7 OP shift operation at the creep speed
The following data are set after the OP shift amount is complete. • OPR complete flag (" Md.31 Status: b4)
amount" is not added.) • OPR request flag ( Md.31 Status: b3) is reset after completion of the OP
shift.
To use the "OP shift function", set the required details in the parameters shown in the following table, and write them to the QD75. When the parameters are set, the OP shift function will be added to the machine OPR control. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
![Mitsubishi Electronics MELSEC-Q QD75D — [5] Setting the OP shift function diagram (page 486)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-486-2.webp)
Pr.53 OP shift amount Set the shift amount during the OP shift. 0
Select the speed during the OP shift 0: Pr.46 OPR speed
Refer to Section 5.2 "List of parameters" for setting details.
![Page 487 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-487.webp?w=400)
The sub functions for compensating the control include the "backlash compensation function", "electronic gear function", and "near pass function". Each function is executed by parameter setting or sequence program creation and writing.
The "backlash compensation function" compensates the backlash amount in the mechanical system. When the backlash compensation amount is set, an extra amount of pulses equivalent to the set backlash amount is output every time the movement direction changes.
The details shown below explain about the "backlash compensation function". [1] Control details [2] Precautions during control [3] Setting the backlash compensation function
The following drawing shows the operation of the backlash compensation function.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Control details diagram (page 487)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-487-1.webp)
Fig. 12.8 Backlash compensation amount

(1) The feed pulses of the backlash compensation amount are not added to the " Md.20 Current feed value" or " Md.21 Machine feed value".
(2) Always carry out a machine OPR before starting the control when using the backlash compensation function (when " Pr.11 Backlash compensation
amount" is set). The backlash in the mechanical system cannot be correctly compensated if a machine OPR is not carried out.
(3) Set the No. of pulses output in one backlash compensation (value in which the " Pr.11 Backlash compensation amount" is divided by the "movement
amount per pulse") to a value of 255 or lower. A "Backlash amount compensation error (error code: 920)" will occur if a value over 255 is set. (Depending on the connected servo, tracking may not be possible if a large amount of pulses is output at once.)
Backlash compensation amount 0 ≤ Movement amount per pulse ≤ 255
(Omit values after the decimal point.)
(4) Backlash compensation, which includes the movement amount and " Pr.11 Backlash compensation amount", is output the moment at the
moving direction changes.
(5) Backlash compensation cannot be made when the stepping motor is used.
To use the "backlash compensation function", set the "backlash compensation amount" in the parameter shown in the following table, and write it to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
value Setting details Factory-set initial value
Pr.11
Set the backlash compensation amount. 0
Refer to Section 5.2 "List of parameters" for setting details.
Setting item Setting · Backlash compensation amount

The "electronic gear function" adjusts the pulses calculated and output according to the parameters set in the QD75 with the actual machine movement amount.
The "electronic gear function" has the following three functions.
[A] During machine movement, the function increments in the QD75 values less
than one pulse that could not be pulse output, and outputs the incremented amount of pulses when the total incremented value reached one pulse or more.
[B] When machine OPR is completed, current value changing is completed,
speed control is started (except when current feed value change is present), or fixed-feed control is started, the function clears to "0" the cumulative values of less than one pulse which could not be output. (If the cumulative value is cleared, an error will occur by a cleared amount in the feed machine value. Control can be constantly carried out at the same machine movement amount, even when the fixed-feed control is continued.)
[C] The function compensates the mechanical system error of the command
movement amount and actual movement amount by adjusting the "movement amount per pulse". (The "movement amount per pulse" value is defined by " Pr.2 No. of pulses
per rotation (Ap)", " Pr.3 Movement amount per rotation (Al)", and " Pr.4
Unit magnification (Am)".)
The QD75 automatically carries out the processing for [A] and [B].
The details shown below explain about the "electronic gear function", including the method for compensating the error in [C] above, etc. [1] Error compensation method [2] Relation between the movement amount per pulse and speed [3] Precautions during control

When position control is carried out by the "movement amount per pulse" set in the QD75 parameters, an error sometimes occurs between the command movement amount (L) and the actual movement amount (L'). That error is compensated in the QD75 by adjusting the values in " Pr.2 No. of
pulses per rotation (Ap)", " Pr.3 Movement amount per rotation (Al)", and
" Pr.4 Unit magnification (Am)". (When " Pr.1 Unit setting" is "0: mm") (1) Definition
The "error compensation amount" used to carry out the error compensation is defined as follows.
Actual movement amount (L') Error compensation amount = Designated movement amount (L)
The QD75 "movement amount per pulse" is calculated with the following equation. Movement amount per pulse is "A", " Pr.2 No. of pulses per rotation" is
(Ap), " Pr.3 Movement amount per rotation" is (Al), and " Pr.4 Unit
magnification" is (Am).
(a) Set the "command movement amount (L)", and carry out positioning. (Set the "movement amount per pulse (A)" according to Section 5.2 "List of parameters".)
(b) After positioning, measure the "actual movement amount (L')".
(c) Calculate the "error compensation amount".
L' Error compensation amount =
(d) Calculate the post-compensation " Pr.2 No. of pulses per rotation
(Ap')", " Pr.3 Movement amount per rotation (Al')", and " Pr.4 Unit
magnification (Am')" from the "post-compensation movement amount per pulse (A')".
A = A × Error compensation amount
Ap × Am ×
(Adjust with Am' so that Al' and Ap' do not exceed the setting range.)

Movement amount per pulse No. of pulses per rotation Unit magnification
: 500 (µm/rev) : 12000 (pulse/rev) : 1
Command movement amount Actual movement amount
: 100mm : 101mm
AL' 5×103 101×103 5050 101
101×103 = 12000 =
Movement amount per pulse No. of pulses per rotation Unit magnification
: 101 (µm/rev) : 240 (pulse/rev) : 1
[Set in Pr.3 ]
[Set in Pr.2 ]
[Set in Pr.4 ]
(e) Set the post-compensation " Pr.2 No. of pulses per rotation (Ap')",
" Pr.3 Movement amount per rotation (Al')", and " Pr.4 Unit
magnification (Am')" in the parameters, and write them to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
value Setting details Pre-compensation
Pr.2 No. of pulses per rotation Ap' Set the post-compensation value. Ap
Pr.3 Movement amount per rotation Al' Set the post-compensation value. Al
Pr.4 Unit magnification Am' Set the post-compensation value. Am
Refer to Section 5.2 "List of parameters" for setting details.
![Page 492 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Relation between the movement amount per pulse and speed](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-492.webp?w=400)
The following shows the relation of the "movement amount per pulse (A)" to the command speed and actual speed. The command speed is the speed commanded by each control, and the actual speed is the actual feedrate.
Command speed = V (The command frequency at that time is represented by "f") Actual speed = V' (The command frequency at that time is represented by " f' ")
Relation of the command speed and actual speed
Fig. 12.9 Relation of the movement amount per pulse to the command speed and actual speed

It is recommended that the "movement amount per pulse (A)" be set to a value close to "1" for the following reasons. The "movement amount per pulse" of "1" means the minimum value in each " Pr.1 Unit setting". (0.1 [µm] for the unit [mm]) (1) If the setting of the movement amount per pulse is less than 1, the command frequency may increase, causing the actual speed to exceed the speed limit value (" Pr.8 Speed limit value", " Pr.31 JOG speed limit
value") and the servomotor to result in overspeed.
(2) If the setting of the movement amount per pulse is less than 1, the mechanical system may oscillate. If the movement amount per pulse becomes less than 1, use the electronic gear function of the drive unit and make setting so that the movement amount per pulse is 1 or greater.
(3) Set the movement amount per pulse so that the pulse output frequency to the drive unit becomes a value of 200kpps/1Mpps or less. If a value is set so that the pulse output frequency to the drive unit exceeds 200kpps/1Mpps , the QD75 may not operate correctly. They indicate the values of QD75P / QD75D.
(4) When using a hundred-thirty thousand pulses encoder, use the electronic gear function of a drive unit.
(5) Use the electronic gear function among the range indicated below.
Movement amount per pulse (A) > 1 500
In the QD75, the general term for the functions in items [1] to [3] above is defined as the "electronic gear function". Refer to the User's Manual for the servomotor for the definition of the "electronic gear" on the servomotor side.
![Page 494 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-494.webp?w=400)
When continuous pass control is carried out using interpolation control, the near pass function is carried out.
The "near pass function" is a function to suppress the mechanical vibration occurring at the time of switching the positioning data when continuous pass control is carried out using interpolation control.
[Near pass function] The extra movement amount occurring at the end of each positioning data unit being continuously executed is carried over to the next positioning data unit. Alignment is not carried out, and thus the output speed drops are eliminated, and the mechanical vibration occurring during speed changes can be suppressed. Because alignment is not carried out, the operation is controlled on a path that passes near the position set in " Da.6 Positioning address/movement amount".
The details shown below explain about the "near pass function". [1] Control details [2] Precautions during control
The following drawing shows the path of the continuous path control.
[The path of the near pass]
Da. 6 Positioning address
Path of positioning data No.3
Path of positioning data No. 4
Speed dropping does not occur.
Positioning data No. 3
Positioning data No. 4
Fig. 12.10 The path of the continuous path control
t
![Page 495 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-495.webp?w=400)
(1) If the movement amount designated by the positioning data is small when the continuous path control is executed, the output speed may not reach the designated speed.
(2) If continuous path control is carried out, the output will suddenly reverse when the reference axis movement direction changes from the positioning data No. currently being executed to the next positioning data No. If the sudden output reversal affects the mechanical system, carry out control with continuous positioning control.
[Path during continuous path control]
Positioning data No.2
Positioning data No.1
Axis 1 (reference axis)
[Axis 1 output speed]
Output suddenly reverses. Positioning data No. 1
Positioning data No.2
[Axis 2 output speed]
Positioning data No.2 Positioning data No. 1
Fig. 12.11 Path and output speed of various axes when movement direction varies during continuous

(3) When continuous path control of a circular interpolation is being carried out in
the near pass, an address in which the extra movement amount is subtracted from the positioning address of the positioning data currently being executed is replaced by the starting point address of the next positioning data No. Because the starting point address will be replaced, an error "Large arc error deviation" (error code: 506) may occur. In this case, adjust the " Pr.41 Allowable circular interpolation error width".

Positioning data No.2 starting point address during the near pass
Fig. 12.12 Arc error during the near pass
(4) When a circle center is designated to continuously designate the circular
interpolation control by a continuous path designation in the near pass, and the positioning address and starting point address of that arc are the same address, the path will make one circle using the two data items. This is because the 2nd data starting point address is shifted by the extra amount of the movement amount occurring from the 1st data.

![Page 497 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Relation between the speed limit function and various controls](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-497.webp?w=400)
Functions to limit the control include the "speed limit function", "torque limit function", "software stroke limit", and "hardware stroke limit". Each function is executed by parameter setting or sequence program creation and writing.
The speed limit function limits the command speed to a value within the "speed limit value" setting range when the command speed during control exceeds the "speed limit value".
The details shown below explain about the "speed limit function". [1] Relation between the speed limit function and various controls [2] Precautions during control [3] Setting the speed limit function
The following table shows the relation of the "speed limit function" and various controls.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Relation between the speed limit function and various controls diagram (page 497)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-497-1.webp)
: Always set – : Setting not required (Setting value is invalid. Use the initial values or setting values
within a range where no error occurs.)

If any axis exceeds " Pr.8 Speed limit value" during 2- to 4-axis speed control,
the axis in excess of the speed limit value is controlled at the speed limit value. The speeds of the other axes interpolated are suppressed depending on their command speed ratios. If the reference axis exceeds " Pr.8 Speed limit value" during 2- to 4-axis linear
interpolation control, 2- to 4-axis fixed-feed control or 2-axis circular interpolation control, the reference axis is controlled at the speed limit value (The speed limit does not function on the interpolation axis side.)
To use the "speed limit function", set the "speed limit value" in the parameters shown in the following table, and write them to the QD75. The set details are validated after they are written to the QD75.
value Setting details Factory-set initial value
Pr.8 Speed limit value Set the speed limit value (max. speed during control). 200000
Set the speed limit value during JOG operation (max. speed during control). (Note that " Pr.31 JOG speed
Pr.31 JOG speed limit value
limit value" shall be less than or equal to " Pr.8
Speed limit value".)
Refer to Section 5.2 "List of parameters" for setting details.
Setting item Setting
![Page 499 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Relation between the torque limit function and various controls](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-499.webp?w=400)
The "torque limit function" limits the generated torque to a value within the "torque limit value" setting range when the torque generated in the servomotor exceeds the "torque limit value". The "torque limit function" protects the deceleration function, limits the power of the operation pressing against the stopper, etc. It controls the operation so that unnecessary force is not applied to the load and machine.
The details shown below explain about the "torque limit function". [1] Relation between the torque limit function and various controls [2] Control details [3] Precautions during control [4] Setting the torque limit function
The following table shows the relation of the "torque limit function" and various controls.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Relation between the torque limit function and various controls diagram (page 499)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-499-1.webp)
speed" is reached, this value becomes the " Pr.54 OPR
JOG operation, Inching operation Pr.17 Torque limit setting value Manual control Manual pulse generator operation Pr.17 Torque limit setting value
: Set when required (Set to " – " when not used.) – : Setting not required (Setting value is invalid. Use the initial values or setting values
within a range where no error occurs.) : Shows the torque limit value when " Cd.22 New torque value" is set to "0".
![Page 500 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-500.webp?w=400)
The following drawing shows the operation of the torque limit function.
PLC READY signal [Y0]
Pr.17 Torque limit setting value
Cd.22 New torque value
Torque limited at the parameter torque limit setting value (100%)
Torque limited at the parameter torque limit setting value (50%)
Md.35 Torque limit stored value
Fig. 12.13 Torque limit function operation
(1) When limiting the torque at the " Pr.17 Torque limit setting value", confirm
that " Cd.22 New torque value" is set to "0". If this parameter is set to a
value besides "0", the " Cd.22 New torque value" will be validated, and the
torque will be limited at that value. (Refer to Section 12.5.4 "Torque change function" for details about the "new torque value".) (2) When the “ Pr.54 OPR torque limit value “exceeds the “ Pr.17 Torque
limit setting value”, an error occurs. (Error code: 995)
(3) When limiting the torque, a D/A converter module and drive unit in which torque limit commands by analog voltage are possible.
(4) When the operation is stopped by torque limiting, the droop pulse will remain in the deviation counter. If a "deviation counter clear" is carried out by issuing an external signal at this time, positional deviation will occur when the operation is continued. If the load torque is eliminated, operation for the amount of droop pulses will be carried out.

(1) To use the "torque limit function", set the "torque limit value" in the parameters shown in the following table, and write them to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the torque limit function diagram (page 501)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-501-1.webp)
Pr.17 Torque limit setting value Set the torque limit value as a percentage. 300
Set the torque limit value after the " Pr.47 Creep
Refer to Section 5.2 "List of parameters" for setting details.
(2) The "torque limit value" set in the QD75 is set in the " Md.35 Torque limit
stored value". The " Md.35 Torque limit stored value" in the sequence
program is transferred to the "D/A converter module", and the torque is limited.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the torque limit function diagram (page 501)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-501-2.webp)
Fig. 12.14 Limiting the torque to the drive unit (Axis 1)
The following table shows the " Md.35 Torque limit stored value" of the
buffer memory address.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the torque limit function diagram (page 501)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-501-3.webp)
The "torque limit value" valid at that time is stored. ( Pr.17 , Pr.54 , or Cd.22 ) 826 926 1026 1126
Refer to Section 5.6 "List of monitor data" for information on the setting details.
![Page 502 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Differences in the moveable range when "current feed value" and](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-502.webp?w=400)
In the "software stroke limit function" the address established by a machine OPR is used to set the upper and lower limits of the moveable range of the workpiece. Movement commands issued to addresses outside that setting range will not be executed. In the QD75, the "current feed value" and "machine feed value" are used as the addresses indicating the current position. However, in the "software stroke limit function", the address used to carry out the limit check is designated in the " Pr.14
Software stroke limit selection". (Refer to Section 9.1.4 "Confirming the current value" or details on the "current feed value" and "machine feed value".) The upper and lower limits of the moveable range of the workpiece are set in " Pr.12
Software stroke limit upper limit value"/ " Pr.13 Software stroke limit lower limit
value".
The details shown below explain about the "software stroke limit function". [1] Differences in the moveable range when "current feed value" and "machine feed
value" are selected. [2] Software stroke limit check details [3] Relation between the software stroke limit function and various controls [4] Precautions during software stroke limit check [5] Setting the software stroke limit function [6] Invalidating the software stroke limit [7] Setting when the control unit is "degree"
"machine feed value" are selected. The following drawing shows the moveable range of the workpiece when the software stroke limit function is used.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Differences in the moveable range when "current feed value" and diagram (page 502)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-502-1.webp)
Software stroke limit (lower limit) Software stroke limit (upper limit)
Fig. 12.15 Workpiece moveable range

The following drawing shows the differences in the operation when " Md.20
Current feed value" and " Md.21 Machine feed value" are used in the moveable
range limit check.
Assume the current stop position is 2000, and the upper stroke limit is set to 5000.
Md. 20 Current feed value Md. 21 Machine feed value
When the current value is changed by a new current value command from 2000 to 1000, the current value will change to 1000, but the machine feed value will stay the same at 2000. 1) When the machine feed value is set at the limit The machine feed value of 5000 (current feed value: 4000) becomes the upper stroke limit.
Md. 20 Current feed value Md. 21 Machine feed value
4000 5000 5000 6000
Md. 20 Current feed value Md. 21 Machine feed value
4000 5000 5000 6000
Fig. 12.16 Software stroke limits of the current feed value and machine feed value
When "machine feed value" is set in " Pr.14 Software stroke limit selection", the
moveable range becomes an absolute range referenced on the OP. When "current feed value" is set, the moveable range is the relative range from the "current feed value".
![Page 504 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Relation between the software stroke limit function and various](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-504.webp?w=400)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Software stroke limit check details diagram (page 504)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-504-1.webp)
An error shall occur if the current value 1 is outside the software stroke limit range 2. (Check " Md.20 Current feed value" or " Md.21 Machine feed value".)
An "axis error" will occur (error code: 507, 508)
An error shall occur if the command address is outside the software stroke limit range. (Check " Da.6 Positioning address/movement amount".)
1Check whether the " Md.20 Current feed value" or " Md.21 Machine feed value" is set in
2Moveable range from the " Pr.12 Software stroke limit upper limit value" to the " Pr.13
Software stroke limit lower limit value".
controls
Control type Limit check Processing at check
Machine OPR control – OPR control Fast OPR control – Check not carried out.
1-axis linear control 2 to 4-axes axis linear interpolation control 1-axis fixed-feed control 2 to 4-axes fixed-feed control (interpolation)
Checks 1) and 2) in the previous section [2] are carried out. For speed control: The axis decelerates to a stop when it exceeds the software stroke limit range. For position control: The axis comes to an immediate
2-axis circular interpolation control
stop when it exceeds the software stroke limit range.
1 to 4-axes speed control 3, 4 Speed-position switching control Position-speed switching control 3, 4
Current value changing – The current value will not be changed if the new current value is outside the software stroke limit range.
Other control JUMP instruction, NOP instruction, LOOP to LEND – Check not carried out.
JOG operation, Inching operation 5
Check 1) in the previous section [2] is carried out. The machine will carry out a deceleration stop when the software stroke limit range is exceeded. If the address falls out of the software stroke limit range, the operation can be started only toward the movable range after an error reset.
Manual control Manual pulse generator operation 5
: Check valid
: Check is not made when the current feed value is not updated (Refer to Pr.21 ) at the setting of " current feed
value" in " Pr.14 Software stroke limit selection" during speed control.
– : Check not carried out (check invalid).
: Valid only when "1:valid" is set in the " Pr.15 Software stroke limit valid/invalid setting".
control" setting. 4: When the unit is "degree", check is not made during speed control. 5: When the unit is "degree", check is not carried out.
Position control · Major positioning control
![Page 505 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Precautions during software stroke limit check](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-505.webp?w=400)
(1) A machine OPR must be executed beforehand for the "software stroke limit function" to function properly. (2) During interpolation control, a stroke limit check is carried out for the every current value of both the reference axis and the interpolation axis. Every axis will not start if an error occurs, even if it only occurs in one axis. (3) During circular interpolation control, the " Pr.12 Software stroke limit upper
limit value"/" Pr.13 Software stroke limit lower limit value" may be
exceeded. In this case, a deceleration stop will not be carried out even if the stroke limit is exceeded. Always install an external limit switch if there is a possibility the stroke limit will be exceeded.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Precautions during software stroke limit check diagram (page 505)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-505-1.webp)
The software stroke limit check is carried out for the following addresses during circular interpolation control. (Note that " Da. 7 Arc address" is carried
out only for circular interpolation control with sub point designation.
Current value/end point address ( Da. 6 )/arc address ( Da. 7 )
(4) If an error is detected during continuous path control, the axis stops immediately on completion of execution of the positioning data located right before the positioning data in error.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Precautions during software stroke limit check diagram (page 505)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-505-2.webp)

(5) During simultaneous start, a stroke limit check is carried out for the current values of every axis to be started. Every axis will not start if an error occurs, even if it only occurs in one axis.
To use the "software stroke limit function", set the required values in the parameters shown in the following table, and write them to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
value Setting details Factory-set initial value
Software stroke limit upper limit value
Pr.12
Set the upper limit value of the moveable range. 2147483647
Software stroke limit lower limit value
Pr.13
Set the lower limit value of the moveable range. –2147483648
Set whether to use the " Md.20 Current feed value" or
Pr.14 Software stroke limit selection
" Md.21 Machine feed value" as the "current value".
Software stroke limit valid/invalid setting
0:Valid Set whether the software stroke limit is validated or invalidated during manual control (JOG operation, Inching operation, manual pulse generator operation).
Pr.15
Refer to Section 5.2 "List of parameters" for setting details.
To invalidate the software stroke limit, set the following parameters as shown, and write them to the QD75.
Pr.12 Software stroke limit upper limit value = Pr.13 Software stroke limit lower limit value
Software stroke limit valid/invalid setting".) The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0). When the unit is "degree", the software stroke limit check is not performed during speed control (including speed control in speed-position switching control or position-speed switching control) or during manual control, independently of the values set in Pr.12 , Pr.13 and Pr.15 .
Setting item Setting

Current value address
The " Md.20 Current feed value" address is a ring address between 0 and
359.99999° .
359.99999° 359.99999°
Fig. 12.17 Current value address when the control unit is "degree".
The upper limit value/lower limit value of the software stroke limit is a value between 0 and 359.99999° .
(1) Setting when the software stroke limit is to be validated.
When the software stroke limit is to be validated, set the upper limit value in a clockwise direction from the lower limit value.
315º Set in a clockwise direction
Fig. 12.18 Software stroke limit when the control unit is "degree"

! DANGER
When the hardware stroke limit is required to be wired, ensure to wire it in the negative logic using b-contact. If it is set in positive logic using a-contact, a serious accident may occur.
In the "hardware stroke limit function", limit switches are set at the upper/lower limit of the physical moveable range, and the control is stopped (by deceleration stop) by the input of a signal from the limit switch. Damage to the machine can be prevented by stopping the control before the upper/lower limit of the physical moveable range is reached. Hardware stroke limit switches are normally installed inside the stroke limit/stroke end on the drive unit side, and the control is stopped before the stroke limit/stoke end on the drive unit side is reached.
The details shown below explain about the "hardware stroke limit function". [1] Control details [2] Wiring the hardware stroke limit [3] Precautions during control [4] When the hardware stroke limit is not used
The following drawing shows the operation of the hardware stroke limit function.
QD75 control moveable range Lower limit Upper limit
Deceleration stop at upper limit switch detection
Deceleration stop at lower limit switch detection
Upper limit switch Lower limit switch Drive unit stroke limit Drive unit stroke limit
Fig. 12.19 Hardware stroke limit function operation

When using the hardware stroke limit function, wire the terminals of the QD75 upper/lower limit stroke limit as shown in the following drawing. (When " Pr.22 Input signal logic selection" is set to the initial value)
FLS
RLS
COM
24VDC
current feed values respectively. When these switches are connected in wrong directions, the hardware stroke limit function does not operate properly and the motor does not stop. For " Pr.6 Rotation direction setting", refer to "5.2.1 Basic parameters 1".
Fig. 12.20 Wiring when using the hardware stroke limit
(1) If the machine is stopped outside the QD75 control range (outside the upper/lower limit switches), or if stopped by hardware stroke limit detection, the "OPR control", "major positioning control", and "high-level positioning control" cannot start. To carry out these types of control again, return the workpiece to the QD75 control range by a "JOG operation", "inching operation" or "manual pulse generator operation". (2) When " Pr.22 Input signal logic selection" is set to the initial value, the
QD75 cannot carry out the positioning control if FLS (upper limit signal) is separated from COM or RLS (lower limit signal) is separated from COM (including when wiring is not carried out).
When not using the hardware stroke limit function, wire the terminals of the QD75 upper/lower limit stroke limit as shown in the following drawing. When the logic of FLS and RLS is set to "positive logic" using " Pr.22 Input
signal logic selection", positioning control can be carried out even if FLS and RLS are not wired. (For details, refer to Section 13.4 "External I/O signal logic switching function".)
FLS
RLS
COM
24VDC
Fig. 12.21 Wiring when not using the hardware stroke limit function
(When " Pr.22 Input signal logic selection" is the initial value)
![Page 510 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-510.webp?w=400)
Functions to change the control details include the "speed change function", "override function", "acceleration/deceleration time change function" and "torque change function". Each function is executed by parameter setting or sequence program creation and writing.
Both the "speed change function" or "override function" change the speed, but the differences between the functions are shown below. Use the function that corresponds to the application.
The speed control function is used to change the speed during control to a newly designated speed at any time. The new speed is directly set in the buffer memory, and the speed is changed by a speed change command ( Cd.15 Speed change request) or external command signal.
During the machine OPR, a speed change to the creep speed cannot be carried out after deceleration start because the near point dog ON is detected.
The details shown below explain about the "speed change function". [1] Control details [2] Precautions during control [3] Setting the speed change function from the PLC CPU [4] Setting the speed change function using an external command signal
The following drawing shows the operation during a speed change.
Speed changes to V2.
Speed changes to V3.
Operation during positioning by V1.
Md. 40 In speed change processing flag
Fig. 12.22 Speed change operation
"Speed change function" · "Override function" · t
![Page 511 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-511.webp?w=400)
(1) Control is carried out as follows at the speed change during continuous path control. a) When no speed designation (current speed) is provided in the next
positioning data:
The next positioning data is controlled at the " Cd.14 New speed
value". b) When a speed designation is provided in the next positioning data:
The next positioning data is controlled at its command speed ( Da.8 ).
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions during control diagram (page 511)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-511-1.webp)
[a] When no speed designation (current speed) is provided. [b] When a speed designation is provided.
Fig. 12.23 Speed change during continuous path control
(2) When changing the speed during continuous path control, the speed change will be ignored if there is not enough distance remaining to carry out the change.
(3) When the stop command was given to make a stop after a speed change
that had been made during position control, the restarting speed depends on the function version.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions during control diagram (page 511)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-511-2.webp)
Refer to Section 2.4 for the way to check the function version.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions during control diagram (page 511)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-511-3.webp)
Fig. 12.24 Restarting speed after speed change made during position control (Function version B)

(4) When the speed is changed by setting " Cd.14 New speed value" to "0",
the operation is carried out as follows.
(During interpolation control, the speed change 0 flag on the reference axis side turns ON.)
the BUSY signal remains ON. (If a stop signal is input, the BUSY signal will turn OFF, and " Md.26 Axis operation status" will change to
"stopped".)
In this case, setting the " Cd.14 New speed value" to a value besides "0"
will turn OFF the speed change 0 flag ( Md.31 Status: b10), and enable
continued operation.
[Y10, Y11, Y12, Y13]
OFF
ON
[XC,XD,XE,XF]
OFF
Cd. 14 New speed value
Cd. 15 Speed change request
ON
Speed change 0 flag
Fig. 12.25 Speed change at new speed value "0" (5) A warning "Deceleration/stop speed change (warning code: 500)" occurs and the speed cannot be changed in the following cases.
" Cd.14 New speed value" is equal to or larger than the " Pr.8 Speed limit
value". (7) When the speed is changed during interpolation control, the required speed is set in the reference axis. (8) When carrying out consecutive speed changes, be sure there is an interval between the speed changes of 100ms or more. (If the interval between speed changes is short, the QD75 will not be able to track, and it may become impossible to carry out commands correctly.) (9) When a speed change is requested simultaneously for multiple axes, change the speed in the ascending axis number order. (10) Speed change cannot be carried out during the machine OPR. A request
for speed change is ignored. (11) When deceleration is started by the speed change function, the deceleration
start flag does not turn ON.
Positioning start signal · BUSY signal · Positioning operation
![Page 513 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Setting the speed change function from the PLC CPU](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-513.webp?w=400)
The following shows the data settings and sequence program example for changing the control speed of axis 1 from the PLC CPU. (In this example, the control speed is changed to "20.00mm/min".)
(1) Set the following data. (Use the start time chart shown in section (2) below as a reference, and set using the sequence program shown in section (3).)
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the speed change function from the PLC CPU diagram (page 513)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-513-1.webp)
Cd.14 New speed value 2000 Set the new speed. 1514 1515 1614 1615 1714 1715 1814 1815
Cd.15 Speed change request 1 Set "1: Change the speed". 1516 1616 1716 1816
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) The following shows the speed change time chart.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the speed change function from the PLC CPU diagram (page 513)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-513-2.webp)
Fig. 12.26 Time chart for changing the speed from the PLC CPU

(3) Add the following sequence program to the control program, and write it to the PLC CPU.

![Page 515 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Setting the speed change function using an external command](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-515.webp?w=400)
signal The speed can also be changed using an "external command signal". The following shows the data settings and sequence program example for changing the control speed of axis 1 using an "external command signal". (In this example, the control speed is changed to "10000.00mm/min".)
(1) Set the following data to change the speed using an external command signal. (Use the start time chart shown in section (2) below as a reference, and set using the sequence program shown in section (3).)
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the speed change function using an external command diagram (page 515)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-515-1.webp)
Pr.42 External command function selection 1 Set "1: External speed change request". 62 212 362 512
Cd.8 External command valid 1 Set "1: Validate the external command". 1505 1605 1705 1805
Cd.14 New speed value 1000000 Set the new speed. 1514 1515 1614 1615 1714 1715 1814 1815
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) The following shows the speed change time chart.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the speed change function using an external command diagram (page 515)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-515-2.webp)
Fig. 12.27 Time chart for changing the speed using an external command signal

(3) Add the following sequence program to the control program, and write it to the PLC CPU.

[Speed change processing] K1 D108 K1514 H0 DTOP
K1 K1 K1505 H0 TOP
![Page 517 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-517.webp?w=400)
The override function changes the command speed by a designated percentage (1 to 300%) for all control to be executed. The speed can be changed by setting the percentage (%) by which the speed is changed in " Cd.13 Positioning operation speed override".
However, when a machine OPR is performed, an override cannot be made after a deceleration start to the creep speed following the detection of near-point dog ON. [1] Control details [2] Precautions during control [3] Setting the override function
The following shows that operation of the override function.
Feedrate". (When Md.22 " becomes "0", the warning "Less than minimum
speed" (warning code: 110) is generated and the axis is controlled in the then speed unit of "1".) 2) If " Cd.13 Positioning operation speed override" is set to 100%, the speed
will not change. 3) If " Cd.13 Positioning operation speed override" is set a value less than
100%, control will be carried out at speed unit "1" at the time " Md.22
Feedrate" becomes a value of "1" or less. (When Md.22 becomes "0", the
speed is changed during the position control of speed-position switching control or position-speed switching control, the operation will be carried out at the speed that could be changed. 5) If the speed changed by the "override function" is greater than the " Pr.8
Speed limit value", a warning "Speed limit value over (warning code: 501)" will occur and the speed will be controlled at the " Pr.8 Speed limit value".
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Control details diagram (page 517)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-517-1.webp)
The " Md.39 Speed limit flag" will turn ON.
Not enough remaining distance could be secured, so operation is carried out at an increased speed.
Fig. 12.28 Override function operation
![Page 518 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Setting the override function](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-518.webp?w=400)
(1) When changing the speed during continuous path control, the speed change will be ignored if there is not enough distance remaining to carry out the change. (2) A warning "Deceleration/stop speed change (warning code: 500)" occurs and the speed cannot be changed in the following cases. (The value set in " Cd.13 Positioning operation speed override" is validated
after a deceleration stop.)
The following shows the data settings and sequence program example for setting the override value of axis 1 to "200%". (1) Set the following data. (Use the start time chart shown in section (2) below as a reference, and set using the sequence program shown in section (3).)
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the override function diagram (page 518)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-518-1.webp)
200 Set the new speed as a percentage (%). 1513 1613 1713 1813
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) The following shows a time chart for changing the speed using the override function.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the override function diagram (page 518)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-518-2.webp)
Fig. 12.29 Time chart for changing the speed using the override function

(3) Add the following sequence program to the control program, and write it to the PLC CPU.

![Page 520 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-520.webp?w=400)
The "acceleration/deceleration time change function" is used to change the acceleration/deceleration time during a speed change to a random value when carrying out the speed change indicated in Section 12.5.1 "Speed change function". In a normal speed change (when the acceleration/deceleration time is not changed), the acceleration/deceleration time previously set in the parameters ( Pr.9 , Pr.10 ,
and Pr.25 to Pr.30 values) is set in the positioning parameter data items Da.3
and Da.4 , and control is carried out with that acceleration/deceleration time. However, by setting the new acceleration/deceleration time ( Cd.10 , Cd.11 ) in the
control data, and issuing an acceleration/deceleration time change enable command ( Cd.12 Acceleration/deceleration time change during speed change, enable/disable
selection) to change the speed when the acceleration/deceleration time change is enabled, the speed will be changed with the new acceleration/deceleration time ( Cd.10 , Cd.11 ).
The details shown below explain about the "acceleration/deceleration time change function". [1] Control details [2] Precautions during control [3] Setting the acceleration/deceleration time change function
The following drawing shows the operation during an acceleration/deceleration time change.
[For an acceleration/deceleration time change disable setting]
Operation with the acceleration/deceleration time set in Da. 3 and Da. 4 .
Cd.15 Speed change request
Cd.12 Acceleration/deceleration time change during speed change, enable/ disable selection
[For an acceleration/deceleration time change enable setting]
Operation with the acceleration/deceleration
time ( Cd. 10 and Cd. 11 ) set in the buffer memory.
Cd.15 Speed change request
Cd.12 Acceleration/deceleration time change during speed change, enable/ disable selection
Fig. 12.30 Operation during an acceleration/deceleration time change
![Page 521 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-521.webp?w=400)
(1) When "0" is set in " Cd.10 New acceleration time value" and " Cd.11 New
deceleration time value", the acceleration/deceleration time will not be changed even if the speed is changed. In this case, the operation will be controlled at the acceleration/deceleration time previously set in the parameters. (2) The "new acceleration/deceleration time" is valid during execution of the positioning data for which the speed was changed. In continuous positioning control and continuous path control, the speed is changed and control is carried out with the previously set acceleration/deceleration time at the changeover to the next positioning data, even if the acceleration/deceleration time is changed to the "new acceleration/deceleration time ( Cd.10 , Cd.11 )".
(3) Even if the acceleration/deceleration time change is set to disable after the "new acceleration/deceleration time" is validated, the positioning data for which the "new acceleration/deceleration time" was validated will continue to be controlled with that value. (The next positioning data will be controlled with the previously set acceleration/deceleration time.)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions during control diagram (page 521)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-521-1.webp)
Cd.12 Acceleration/deceleration time change during speed change, enable/disable selection
![Page 522 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Setting the acceleration/deceleration time change function](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-522.webp?w=400)
(4) If the "new acceleration/deceleration time" is set to "0" and the speed is changed after the "new acceleration/deceleration time" is validated, the operation will be controlled with the previous "new acceleration/deceleration time".

New acceleration/deceleration time ( Cd. 10 , Cd. 11 )
Controlled with the acceleration/ deceleration time in the parameter.
(5) The acceleration/deceleration time change function is disabled for JOG operation and inching operation.

If the speed is changed when an acceleration/deceleration change is enabled, the "new acceleration/deceleration time" will become the acceleration/deceleration time of the positioning data being executed. The "new acceleration/deceleration time" remains valid until the changeover to the next positioning data. (The automatic deceleration processing at the completion of the positioning will also be controlled by the "new acceleration/deceleration time".)
To use the "acceleration/deceleration time change function", write the data shown in the following table to the QD75 using the sequence program. The set details are validated when a speed change is executed after the details are written to the QD75.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the acceleration/deceleration time change function diagram (page 522)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-522-3.webp)
Cd.10 New acceleration time value Set the new acceleration time. 1508 1509 1608 1609 1708 1709 1808 1809
Cd.11 New deceleration time value Set the new deceleration time. 1510 1511 1610 1611 1710 1711 1810 1811
Acceleration/ deceleration time change during speed change, enable/disable selection
Refer to Section 5.7 "List of control data" for details on the setting details.


Example
![Page 524 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-524.webp?w=400)
The "torque change function" is used to change the torque limit value during torque limiting. The torque limit value during torque limiting is normally the value set in the " Pr.17
Torque limit setting value" that was previously set in the parameters. However, by setting the new torque limit value in the axis control data " Cd.22 New torque value",
and writing it to the QD75, the torque generated by the servomotor during control can be limited with the new torque value. (The " Cd.22 New torque value" is validated when written to the QD75.)
The details shown below explain about the "torque change function". [1] Control details [2] Precautions during control [3] Setting the torque change function start signal
The torque value of the axis control data can be changed at all times. The torque can be limited with a new torque value from the time the new torque value has been written to the QD75. (a torque change is made only during operation.) The toque limiting is not carried out from the time the power supply is turned ON to the time the PLC READY signal (Y0) is turned ON. The torque setting range is from 0 to " Pr.17 Torque limit setting value".
When the new torque value is 0, a torque change is considered not to be carried out. The torque change range is 1 to " Pr.17 Torque limit setting value".
The following drawing shows the torque change operation.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Control details diagram (page 524)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-524-1.webp)
Torque is limited by the torque limit setting value (50%) of the parameters.
Fig. 12.31 Torque change operation
![Page 525 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Setting the torque change function start signal](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-525.webp?w=400)
(1) If a value besides "0" is set in the " Cd.22 New torque value", the torque
generated by the servomotor will be limited by that value. To limit the torque with the value set in " Pr.17 Torque limit setting value", set the " Cd.22
New torque value" to "0".
(2) The " Cd.22 New torque value" is validated when written to the QD75.
(Note that it is not validated from the time the power supply is turned ON to the time the PLC READY signal (Y0) is turned ON.)
(3) If the setting value is outside the setting range, an axis warning "Outside new torque value range" (warning code: 113) will occur and the torque will not be changed.
(4) If the time to hold the new torque value is not more than 100ms, a torque change may not be executed.
To use the "torque change function", write the data shown in the following table to the QD75 using the sequence program. The set details are validated when written to the QD75.
Buffer memory address Setting item Setting
value Setting details Axis
Cd.22 New torque value Set the new torque limit value. 1525 1625 1725 1825
Refer to Section 5.7 "List of control data" for details on the setting details.
1 Axis · 2 Axis · 3 Axis
![Page 526 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Configuration and preparation of absolute position detection system](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-526.webp?w=400)

When the absolute position restoration is carried out, the servo ON signal may be turned OFF (servo OFF) for about 20 ms, and the motor may operate. If this is not desired, install an electromagnetic brake separately and lock the motor by that brake during the absolute position restoration.
The "absolute position restoration function" is a function to restore the absolute position of the designated axis by the absolute position detection system. By this function, the OPR after power OFF such as instantaneous power interruption and emergency stop is not required, and the restoration operation at site can be carried out easily. The details of the "absolute position restoration function" are described below. [1] Configuration and preparation of absolute position detection system [2] Outline of absolute position detection data communication [3] Absolute position signal transmission procedure [4] Precautions during control
The following drawing shows the configuration of the absolute position detection system.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Configuration and preparation of absolute position detection system diagram (page 526)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-526-2.webp)
Fig. 12.32 Configuration of absolute position detection system
(1) Configuration
![Page 527 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Outline of absolute position detection data communication](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-527.webp?w=400)
Prepare the absolute position detection system taking care of the following.
As shown in Fig. 12.33 System block diagram, the detector comprises an encoder for detecting its position in one rotation in addition to the A, B, Z phase signal for position control in normal operation and a cumulative rotation counter for detecting the number of rotations. The absolute position detection system detects the absolute position of the machine constantly and stores it with the backup of the battery irrespective of whether the PLC system power is turned ON/OFF. Thus, once the OP initial setting is carried out at the time of installation of the machine, the OPR is not required even when the power is later turned ON. The restoration can be carried out easily when an instantaneous power interruption or emergency stop occurs. In addition, because the absolute position data is backed up by a super condenser built in the detector, the absolute position data will be stored for a specified time even if the cable is disconnected or broken.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Outline of absolute position detection data communication diagram (page 527)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-527-1.webp)
Fig. 12.33 System block diagram
(2) Preparation

(1) Figure 12.34 shows the outline of the absolute position signal transmission
procedure between the servo amplifier and the PLC system (PLC CPU, QD75, I/O module). Refer to the operation manual of the servo amplifier for details on the communication between the servo amplifier and the PLC system. (2) Errors during communication
(a) If the system expires during communication, an error "ABS transmission
timeout" (error code: 213) will occur. (b) If the transmission data causes a sum error, an error "ABS transmission
SUM" (error code: 214) will occur. Refer to Section 15.2 "List of errors" for the remedial method to be taken when an error occurs.
Servo amplifier I/O module
QD75
Servo ON signal ABS transmission mode
Md.20 Current feed value Md.21 Machine feed value
ABRST3
ABRST4
Fig. 12.34 Absolute position signal transmission procedure
Refer to Chapter 14 "Dedicated instructions" for details of the dedicated instructions.

The following diagram shows the example of connection between the PLC system and the Mitsubishi Electric servo amplifier (MR-H-A).
QD75
24(PF)
0(X47)
16 points input module
1(X48)
Transmission data preparation completed
2(X49)
12(SON)
0(Y50)
16 points output module
1(Y51)
45(DI4)
2(Y52)
: The X and Y devices can be set arbitrarily with the sequence program.
Details of servo amplifier connector pins The following table shows the pins for setting the "absolute position detection system". Refer to the MR-H operation manual for the details when the ABS transmission mode is turned OFF.
Signal name Abbreviation Pin No. Function and application
mode DI3 44 ABS transmission mode terminal. While this is turned ON, the servo amplifier is in the ABS transmission mode, and the DI4/PF/ZSP/TLC functions are as shown in this table.
ABS request DI4 45 This is turned ON when ABS data is requested in the ABS transmission mode.
ABS bit 0 PF 24 This indicates the lower order bit among 2 bits of ABS data to be transferred from the servo amplifier to the PLC system in the ABS transmission mode.
ABS bit 1 ZSP 23 This indicates the upper order bit among 2 bits of ABS data to be transferred from the servo amplifier to the PLC system in the ABS transmission mode.
TLC 25 This indicates the transmission data preparation completed in the ABS transfer mode. When the preparation is completed, the signal is turned ON.
Refer to the MR-H operation manual for the I/O interface.

(1) When an absolute position detection system is constructed, absolute position
restoration must be made at least once after power supply on or resetting. Also, the servo amplifier does not switch on unless the absolute position restoration is completed. (2) For use of positioning in an absolute position detection system, the following
controls cannot be carried out:
a) Indicates the number of pulses that may be output to a servo amplifier
when an axis is to be positioned from the OP in an absolute position detection system. In the absolute position detection system, pulses within the range of the following expression can be output to the servo amplifier.
[-32768 (number of feedback pulses)]≤[number of output pulses]≤[32768 (number of feedback pulses)-1]
b) Pulses are positive in the address increasing direction from the OP, and
negative in the address decreasing direction from the OP.
0 -214748364.8 214748364.7
Negative pulse outputs Positive pulse outputs
c) The number of output pulses varies with the number of feedback pulses as
indicated below:
a) The following positioning addresses can be specified on the QD75:
![Page 531 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Calculation of positioning address and concept of absolute position detection system]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-531.webp?w=400)
Use the following expression to calculate the positioning address.
(Positioning address) = (movement amount per pulse) (number of output pulses) + (OP address) Expression 1
The concepts of the positioning addresses in mm, inch and pulse are identical, the following examples provide those of the mm unit.
Example 1.
(1) There are the following conditions to calculate the positioning address:
can be specified from the output pulse count using range in Condition 1 and the positioning address calculation expression (Expression 1).
(Positioning address) = (Movement amount per pulse)
(number of output pulses) + (OP address) =0.1 (-268435456) + 0.0 =-26843545.5 (µm)
(Positioning address) = (Movement amount per pulse)
(number of output pulses) + (OP address) =0.1 (-268435456) + 0.0 =-26843545.5 (µm)
(3) The upper and lower limit values of the positioning address calculated are
within the range of Condition 2. Hence, the positioning range [-26843545.6 (µm) to 26843545.5 (µm)] calculated in Condition 1 can be used in the absolute position detection system. Positioning outside of the range -26843545.6 (µm) to 26843545.5 (µm) cannot be used in the absolute position detection system.
0 -214748364.8 214748364.7 -26843545.6 26843545.5
Unusable range in absolute position detection system
Unusable range in absolute position detection system Usable range in absolute position detection system

Example 2.
(1) Using Expression 1, calculate the positioning address which can be specified
in the system where the OP address in Example 1 is 214740000.0 (µm).
(2) Since the lower limit value of the positioning address calculated is within the
range of Condition 2, the calculated address 187896454.4 (µm) is the lower limit for positioning in the absolute position detection system. Since the upper limit of the positioning address calculated is outside of the range of Condition 2, the upper limit value 214748364.7 (µm) is the upper limit for positioning in the absolute position detection system. In the absolute position detection system, use the positioning address within the range 187896454.4 (µm) to 214748364.7 (µm). Positioning in excess of 187896454.4 (µm) cannot be used in the absolute position detection system.
-214748364.8 214748364.7
Positioning address specifying range
241583545.5 214740000.0 187896454.4
Setting disallowed Usable range in absolute position detection system Unusable range in absolute
Example 3.
(1) There are the following conditions to calculate the positioning address:
Condition 1 and the positioning address calculation expression (Expression 1).
(Positioning address) = (Movement amount per pulse)
(number of output pulses) + (OP address) = 0.9 (-268435456) + 0.0 = -241591910.4 (µm)
(number of output pulses) + (OP address) = 0.9 268435455 + 0.0 = 241591909.5 (µm)
position detection system

(3) Since the upper and lower limit values of the positioning address calculated
are outside of the range of Condition 2, use the positioning address within the positioning range of Condition 2 (-2147483648 (µm) to 2147483647 (µm)).
0 -214748364.8 214748364.7 -241591910.4 241591909.5

Usable range in absolute position detection system Setting disallowed
Unusable in absolute position detection system. Current value cannot be restored properly at power-on or reset.

Unusable in absolute position detection system. Current value cannot be restored properly at power supply on or resetting
Usable range in absolute position detection system
0 359.99999 ( ~ )
![Page 534 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Relation between the step function and various controls](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-534.webp?w=400)
Other functions include the "step function", "skip function", "M code output function", "teaching function", "target position change function", "command in-position function", "acceleration/deceleration processing function", "pre-reading start function", "deceleration start flag function" and "stop command processing for deceleration stop function". Each function is executed by parameter setting or sequence program creation and writing.
The "step function" is used to confirm each operation of the positioning control one by one. It is used in debugging work for major positioning control, etc. A positioning operation in which a "step function" is used is called a "step operation". In step operations, the timing for stopping the control can be set. (This is called the "step mode".) Control stopped by a step operation can be continued by setting "step continue" (to continue the control)" or restarted by setting "restart" in the "step start information".
The details shown below explain about the "step function". [1] Relation between the step function and various controls [2] Step mode [3] Step start information [4] Using the step operation [5] Control details [6] Precautions during control [7] Step function settings
The following table shows the relation between the "step function" and various controls.
Control type Step function Step applicability Machine OPR control OPR control Fast OPR control Step operation not possible
1-axis linear control 2 to 4-axes linear interpolation control 1-axis fixed-feed control 2 to 4- axes fixed-feed control (interpolation)
2-axis circular interpolation control
1 to 4- axes Speed control Step operation not possible Speed-position switching control Position-speed switching control
Other control JUMP instruction, NOP instruction, LOOP to LEND Step operation not possible
JOG operation, Inching operation Manual control Manual pulse generator operation Step operation not possible
: Set when required. : Setting not possible
![Page 535 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Step start information](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-535.webp?w=400)
In step operations, the timing for stopping the control can be set. This is called the "step mode". (The "step mode" is set in the control data " Cd.34 Step
mode".) The following shows the two types of "step mode" functions. (1) Deceleration unit step
The operation stops at positioning data requiring automatic deceleration. (A normal operation will be carried out until the positioning data requiring automatic deceleration is found. Once found, that positioning data will be executed, and the operation will then automatically decelerate and stop.)
The operation automatically decelerates and stops for each positioning data. (Even in continuous path control, an automatic deceleration and stop will be forcibly carried out.)
Control stopped by a step operation can be continued by setting "step continue" (to continue the control) in the "step start information". (The "step start information" is set in the control data " Cd.36 Step start information".)
The following table shows the results of starts using the "step start information" during step operation.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Step start information diagram (page 535)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-535-1.webp)
1 step of positioning stopped normally Step standing by 1: Step continue The next positioning data is executed.
The warnings "Step not possible (warning code: 511)" will occur if the " Md.26
Axis operation status" is as shown below or the step valid flag is OFF when step start information is set.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Step start information diagram (page 535)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-535-2.webp)
Standing by Stopped In interpolation In JOG operation In manual pulse generator operation Analyzing Waiting for special start In OPR In position control In speed control In speed control of speed-position switching control In position control of speed-position switching control In speed control of position-speed switching control In position control of position-speed switching control

The following shows the procedure for checking positioning data using the step operation. (1) Turn ON the step valid flag before starting the positioning data.
(Write "1" (carry out step operation) in " Cd.35 Step valid flag".)
(2) Set the step mode before starting the positioning data.
(Set in " Cd.34 Step mode".)
positioning control starts normally.
(4) The control will stop for the following reasons.
a) One step of positioning stopped normally. (Go to step (6)) b) Control stopped by a stop signal (Take appropriate measures, go to step (5)) c) An error occurred and the control stopped. (Take appropriate measures, go to step (3))
the positioning data where the control stopped operates normally. (Go to (4)).
check that the next positioning data operates normally. a) One step of positioning stopped normally. (Go to step (6)) b) Control stopped by a stop signal (Take appropriate measures, go to step (5)) c) An error occurred and the control stopped. (Take appropriate measures, go to step (3)) d) All positioning data operated normally (Go to step (7))
(7) Turn OFF the step valid flag, and quit the "step function".
(Write "0" (do not carry out step operation) in " Cd.35 Step valid flag".)
![Page 537 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [5] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-537.webp?w=400)
(1) The following drawing shows a step operation during a "deceleration unit step".
![Mitsubishi Electronics MELSEC-Q QD75D — [5] Control details diagram (page 537)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-537-1.webp)
becomes one step of unit for carrying out automatic
Fig. 12.35 Operation during step execution by deceleration unit step
(2) The following drawing shows a step operation during a "data No. unit step".
![Mitsubishi Electronics MELSEC-Q QD75D — [5] Control details diagram (page 537)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-537-2.webp)
Operation pattern becomes one step of positioning data No. unit, regardless of continuous path control (11).
Fig. 12.36 Operation during step execution positioning data No. unit step
![Page 538 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [7] Step function settings](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-538.webp?w=400)
(1) When step operation is carried out using interpolation control positioning data, the step function settings are carried out for the reference axis.
(2) When the step valid flag is ON, the step operation will start from the beginning if the positioning start signal is turned ON while " Md.26 Axis
operation status" is "step standing by". (The step operation will be carried out from the positioning data set in " Cd.3 Positioning start No.".)
To use the "step function", write the data shown in the following table to the QD75 using the sequence program. Refer to section [4] "Using the step operation" for the timing of the settings. The set details are validated when written to the QD75.
Buffer memory address Setting item Setting
value Setting details Axis
Cd.35 Step valid flag 1 Set "1: Carry out step operation". 1545 1645 1745 1845
Cd.36 Step start information
Refer to Section 5.7 "List of control data" for details on the setting details.
1 Axis · 2 Axis · 3 Axis
![Page 539 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-539.webp?w=400)
The "skip function" is used to stop (deceleration stop) the control of the positioning data being executed at the time of the skip signal input, and execute the next positioning data. A skip is executed by a skip command ( Cd.37 Skip command) or external command
signal. The "skip function" can be used during control in which positioning data is used.
The details shown below explain about the "skip function". [1] Control details [2] Precautions during control [3] Setting the skip function from the PLC CPU [4] Setting the skip function using an external command signal
The following drawing shows the skip function operation.
[Y10, Y11, Y12, Y13]
OFF
ON
OFF
[XC, XD, XE, XF]
ON
OFF
[X14, X15, X16, X17]
Start of the next positioning
Deceleration by skip signal
OFF
Fig. 12.37 Operation when a skip signal is input during positioning control
(1) If the skip signal is turned ON at the last of an operation, a deceleration stop will occur and the operation will be terminated. (2) When a control is skipped (when the skip signal is turned ON during a control), the positioning complete signals (X14, X15, X16, X17) will not turn ON. (3) When the skip signal is turned ON during the dwell time, the remaining dwell time will be ignored, and the next positioning data will be executed. (4) When a control is skipped during interpolation control, the reference axis skip signal is turned ON. When the reference axis skip signal is turned ON, a deceleration stop will be carried out for every axis, and the next reference axis positioning data will be executed. (5) The M code ON signals (X4, X5, X6, X7) will not turn ON when the M code output is set to the AFTER mode (when "1: AFTER mode" is set in " Pr.18
M code ON signal output timing"). (In this case, the M code will not be stored in " Md.25 Valid M code".)
(6) The skip cannot be carried out by the speed-position and position-speed switching control. It is processed in the same manner as in the speed control.
![Page 540 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Setting the skip function from the PLC CPU](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-540.webp?w=400)
The following shows the settings and sequence program example for skipping the control being executed in axis 1 with a command from the PLC CPU. (1) Set the following data. (The setting is carried out using the sequence program shown below in section (2)).
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the skip function from the PLC CPU diagram (page 540)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-540-1.webp)
Cd.37 Skip command 1 Set "1: Skip request". 1547 1647 1747 1847
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) Add the following sequence program to the control program, and write it to the PLC CPU.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Setting the skip function from the PLC CPU diagram (page 540)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-540-2.webp)
Example
![Page 541 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Setting the skip function using an external command signal](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-541.webp?w=400)
The skip function can also be executed using an "external command signal". The following shows the settings and sequence program example for skipping the control being executed in axis 1 using an "external command signal". (1) Set the following data to execute the skip function using an external command signal. (The setting is carried out using the sequence program shown below in section (2)).
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the skip function using an external command signal diagram (page 541)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-541-1.webp)
Pr.42 External command function selection 3 Set "3: Skip request". 62 212 362 512
Cd.8 External command valid 1 Set "1: Validate external command". 1505 1605 1705 1805
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) Add the following sequence program to the control program, and write it to the PLC CPU.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the skip function using an external command signal diagram (page 541)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-541-2.webp)

The "M code output function" is used to command sub work (clamping, drill rotation, tool replacement, etc.) related to the positioning data being executed. When the M code ON signal (X4, X5, X6, X7) is turned ON during positioning execution, a No. called the M code is stored in " Md.25 Valid M code".
These " Md.25 Valid M code" are read from the PLC CPU, and used to command
auxiliary work. M codes can be set for each positioning data. (Set in setting item " Da.10 M code" of the positioning data.)
The timing for outputting (storing) the M codes can also be set in the "M code output function".
The details shown below explain about the "M code output function". [1] M code ON signal output timing [2] M code OFF request [3] Precautions during control [4] Setting the M code output function [5] Reading M codes
The timing for outputting (storing) the M codes can be set in the "M code output function". (The M code is stored in " Md.25 Valid M code" when the M code ON
signal is turned ON.) The following shows the two types of timing for outputting M codes: the "WITH" mode and the "AFTER" mode. (1) WITH mode
The M code ON signal (X4, X5, X6, X7) is turned ON at the positioning start, and the M code is stored in " Md.25 Valid M code".
OFF
[Y10, Y11, Y12, Y13]
ON
[XC, XD, XE, XF]
OFF
ON
M code ON signal
[X4, X5, X6, X7]
Cd. 7 M code OFF request
1 0 1 0 0 0
Md. 25 Valid M code
Da. 1 Operation pattern
m1 and m2 indicate set M codes.
Fig. 12.38 M code ON/OFF timing (WITH mode)
![Page 543 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] M code OFF request](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-543.webp?w=400)
The M code ON signal (X4, X5, X6, X7) is turned ON at the positioning completion, and the M code is stored in " Md.25 Valid M code".

Fig. 12.39 M code ON/OFF timing (AFTER mode)
When the M code ON signal (X4, X5, X6, X7) is ON, it must be turned OFF by the sequence program. To turn OFF the M code ON signal, set "1" (turn OFF the M code signal) in " Cd.7 M code OFF request".
![Mitsubishi Electronics MELSEC-Q QD75D — [2] M code OFF request diagram (page 543)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-543-2.webp)
Cd.7 M code OFF request 1 Set "1: Turn OFF the M code ON signal". 1504 1604 1704 1804
Refer to Section 5.7 "List of control data" for details on the setting details.
The next positioning data will be processed as follows if the M code ON signal is not turned OFF. (The processing differs according to the " Da.1 Operation
pattern".)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] M code OFF request diagram (page 543)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-543-3.webp)
The next positioning data will not be executed until the M code ON signal is turned OFF.
11 Continuous path control The next positioning data will be executed, but a warning "M code ON signal ON start" (warning code: 503) will occur.
![Page 544 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-544.webp?w=400)

Fig. 12.40 Warning due to an M code ON signal during continuous path control

If the M code output function is not required, set a "0" in setting item " Da.10 M
(1) During interpolation control, the reference axis M code ON signal is turned ON.
(2) The M code ON signal will not turn ON if "0" is set in " Da.10 M code". (The M code will not be output, and the previously output value will be held in " Md.25 Valid M code".)
(3) If the M code ON signal is ON at the positioning start, an error "M code ON signal start (error code: 536)" will occur, and the positioning will not start.
(4) If the PLC READY signal (Y0) is turned OFF, the M code ON signal will turn OFF and "0" will be stored in " Md.25 Valid M code".
(5) If the positioning operation time is short during continuous path control, there will not be enough time to turn OFF the M code ON signal, and a warning "M code ON signal ON (error code: 503)" may occur. In this case, set a "0" in
the " Da.10 M code" of that section's positioning data.
(6) In the AFTER mode during speed control, the M code is not output and the M code ON signal does not turn ON.
(7) If current value changing where "9003" has been set to " Cd.3 Positioning
start No." is performed, the M code output function is made invalid.
![Page 545 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [5] Reading M codes](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-545.webp?w=400)
The following shows the settings to use the "M code output function".
(1) Set the M code No. in the positioning data " Da.10 M code".
(2) Set the timing to output the M code ON signal (X4, X5, X6, X7).
Set the required value in the following parameter, and write it to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Setting the M code output function diagram (page 545)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-545-1.webp)
Set the timing to output the M code ON signal. 0: WITH mode 1: AFTER mode
Refer to Section 5.2 "List of parameters" for setting details.
"M codes" are stored in the following buffer memory when the M code ON signal turns ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [5] Reading M codes diagram (page 545)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-545-2.webp)
Md.25 Valid M code The M code No. ( Da.10 M code) set in the
Refer to Section 5.6 "List of monitor data" for information on the storage details.
The following shows a sequence program example for reading the " Md.25 Valid
M code" to the PLC CPU data register (D110). (The read value is used to command the sub work.) Read M codes not as "rising edge commands", but as "ON execution commands".
![Mitsubishi Electronics MELSEC-Q QD75D — [5] Reading M codes diagram (page 545)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-545-3.webp)

The "teaching function" is used to set addresses aligned using the manual control (JOG operation, inching operation manual pulse generator operation) in the positioning data addresses (" Da.6 Positioning address/movement amount", " Da.7 Arc
address").
The details shown below explain about the "teaching function". [1] Control details [2] Precautions during control [3] Data used in teaching [4] Teaching procedure [5] Teaching program example
(1) Teaching timing
Teaching is executed using the sequence program when the BUSY signal (XC, XD, XE, XF) is OFF. (During manual control, teaching can be carried out as long as the axis is not BUSY, even when an error or warning has occurred.)
The addresses for which teaching is possible are "current feed values" ( Md.20 Current feed value) having the OP as a reference. The settings of
the "movement amount" used in incremental system positioning cannot be used. In the teaching function, these "current feed values" are set in the
" Da.6 Positioning address/movement amount" or " Da.7 Arc address".
Positions aligned by manual control
"Current feed value" A Da.6 Positioning address/movement
"Current feed value" B Da.7 Arc address
TEACH 4, PFWRT" When the dedicated instructions "TEACH 1, TEACH 2, TEACH 3, TEACH 4, PFWRT" are used to execute the teaching function, the programming becomes easier. Refer to Chapter 14 "Dedicated instructions" for details.
Positioning data · amount
![Page 547 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Data used in teaching](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-547.webp?w=400)
(1) Before teaching, a "machine OPR" must be carried out to establish the OP. (When a current value changing, etc., is carried out, " Md.20 Current feed
value" may not show absolute addresses having the OP as a reference.) (2) Teaching cannot be carried out for positions to which movement cannot be executed by manual control (positions to which the workpiece cannot physically move). (During center point designation circular interpolation control, etc., teaching of " Da.7 Arc address" cannot be carried out if the
center point of the arc is not within the moveable range of the workpiece.) (3) Writing to the flash ROM can be executed up to 100,000 times. If writing to the flash ROM exceeds 100,000 times, the writing may become impossible (assured value is up to 100,000 times). If an error (error code: 805) occurs when writing to the flash ROM has been completed, check whether or not the program is created so as to write continuously to the flash ROM.
The following control data is used in teaching.
Buffer memory address Setting item Setting
value Setting details Axis
Cd.1 Flash ROM write request 1 Write the set details to the flash ROM (backup the changed data). 1900
Sets to which "current feed value" is written. 0: Written to " Da.6 Positioning
Cd.38 Teaching data selection
1548 1648 1748 1848
address/movement amount".
Designates the data to be taught. (Teaching is carried out when the setting value is 1 to 600.) When teaching has been completed, the QD75 is zero cleared in the initial stage.
Teaching positioning data No.
Cd.39
1549 1649 1749 1849
Refer to Section 5.7 "List of control data" for details on the setting details.
1 Axis · 2 Axis · 3 Axis
![Page 548 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Teaching procedure](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-548.webp?w=400)
The following shows the procedure for a teaching operation. (1) When teaching to the " Da.6 Positioning address/movement amount"
(Teaching example on axis 1)
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Teaching procedure diagram (page 548)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-548-1.webp)
Move the workpiece to the target position using a manual operation.
Using a JOG operation, inching operation, or manual pulse generator.
Set Writes the current feed value to Da.6 Positioning address/ movement amount in teaching data selection.
Set 0 in buffer memory address [1548].
Set the positioning data No. for which the teaching will be carried out.
Set the positioning data No. in buffer memory address [1549].
Confirm completion of the teaching. Confirm 0 in buffer memory address [1549].
Carry out a writing request to the flash ROM.
Set 1 in buffer memory address [1900].
Confirm 0 in buffer memory address [1900].

(2) When entering teaching data into " Da.7 Arc address" and then into
" Da.6 Positioning address/movement amount" (Teaching example for 2- axis circular interpolation control with sub point designation on axes 1 and 2)
Carry out a machine OPR.
Move the workpiece to the circular interpolation sub point using a manual operation. *1
Using a JOG operation, inching operation, or manual pulse generator.
Teaching arc sub point address on axis 1
Set Writes the current feed value to Da.7 Arc address in teaching data selection.
Set 1 in the buffer memory address [1548].
Set the positioning data No. for which the teaching will be carried out.
Set the positioning data No. in buffer memory address [1549].
Confirm completion of the teaching.
Confirm 0 in buffer memory address [1549].
Teach arc sub point address of axis 2. Entering teaching data to buffer memory address [1648] and [1649], in the same fashion as for axis 1.
Move the workpiece to the circular interpolation end point using a manual operation. *2
Using a JOG operation, inching operation, or manual pulse generator.
Teaching arc end point address on axis 1
Set Writes the current feed value to Da.6 Positioning address/ movement amount by teaching data selection.
Set 0 in buffer memory address [1548].
Set the positioning data No. for which the teaching will be carried out.
Set the positioning data No. in buffer memory address [1549].
Confirm completion of the teaching.
Confirm 0 in buffer memory address [1549].
Start


Teaching arc end point address on axis 2. Entering teaching data to buffer memory address [1648] and [1649], in the same fashion as for axis 1.
Carry out a writing request to the flash ROM.
Set 1 in buffer memory address [1900].
Confirm 0 in buffer memory address [1900].
(Axis 2) Forward direction

[Motion path] · Reverse direction

The following shows a sequence program example for setting (writing) the positioning data obtained with the teaching function to the QD75. (1) Setting conditions



POINT (1) Confirm the teaching function and teaching procedure before setting the positioning data. (2) The positioning addresses that are written are absolute address (ABS) values. (3) If the positioning operation is correctly completed with the written positioning data, it is
recommended that the positioning data be registered in the QD75 flash ROM.
Example
![Page 553 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Details of control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-553.webp?w=400)
The "target position change function" is a function to change a target position to a newly designated target position at any timing during the position control (1-axis linear control). A command speed can also be changed simultaneously. The target position and command speed changed are set directly in the buffer memory, and the target position change is executed by " Cd.29 Target position
change request flag".
The following shows the details of the "target position change function". [1] Details of control [2] Precaution during operation [3] Method of setting target position change function from PLC CPU
The following charts show the details of control of the target position change function.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Details of control diagram (page 553)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-553-1.webp)
(a) When the address after change is positioned away from the start point more than the positioning address:
Target position change request Positioning address Address after change
(b) When the speed is changed simultaneously with changing the address:
Target position change request Positiioning address Address after change
(c) When the direction of the operation is changed:
Fig. 12.41 Target position change operation

(1) If the positioning movement direction from the stop position to a new target
position is reversed, stop the operation once and then position to the new target position. (Refer to Fig. 12.41 (c).) (2) If a command speed exceeding the speed limit value is set to change the
command speed, a warning will be given, and the new command speed will be the speed limit value (warning code: 501). Also, if the command speed change disables the remaining distance to the target value from being assured, a warning will be given (warning code: 509). (3) During interpolation control, a target position change request given is ignored
and a warning (warning code: 518) occurs if a new target position value (address) is outside the software stroke limit range, if the axis is decelerating to a stop, or if the operation pattern is continuous path control. (4) When a command speed is changed, the current speed is also changed.
When the next positioning speed uses the current speed in the continuous positioning, the next positioning operation is carried out at the new speed value. When the speed is set with the next positioning data, that speed becomes the current speed and the operation is carried out at the current speed. (5) When a target position change request is given during automatic deceleration
in position control, positioning control to a new position is exercised after the axis has stopped once if the moving direction is reversed. If the moving direction is not reversed, the axis is accelerated to the command speed again and positioned to the new position. (6) If the constant speed status is regained or the output is reversed by a target
position change made while " Md.48 Deceleration start flag" is ON, the deceleration start flag remains ON. (For details, refer to Section 12.7.9.)
When carrying out the target position change continuously, take an interval of 100 ms or longer between the times of the target position changes. Also, take an interval of 100 ms or longer when the speed change is carried out after changing the target position or the target position change is carried out after the speed change.
![Page 555 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Method of setting target position change function from PLC CPU](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-555.webp?w=400)
The following table and chart show the example of a data setting and sequence program used to change the target position of the axis 1 by the command from the PLC CPU, respectively. (example in which the target position value and command speed are changed to a new target position of "300.0 m" and a new command speed of "10000.00 mm/min".) (1) The following data is set.
(Referring to the starting time chart shown in item (2) below, carry out the setting with the sequence program shown in item (3).)
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Method of setting target position change function from PLC CPU diagram (page 555)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-555-1.webp)
3000 Set the new address. 1534 1535 1634 1635 1734 1735 1834 1835
Cd.28 Target position value (new speed) 1000000 Set the new speed. 1536 1537 1636 1637 1736 1737 1836 1837
Cd.29 Target position change request flag 1 Set "1: Carry out speed change". 1538 1638 1738 1838
Refer to Section 5.7 "List of control data" for details on the setting details.
(2) The following shows the time chart for target position change.
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Method of setting target position change function from PLC CPU diagram (page 555)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-555-2.webp)
Target position change request flag 1 0 0 Cd.29
Fig. 12.42 Time chart for target position change from PLC CPU

(3) The following sequence program is added to the control program, and written
to the PLC CPU.

Example

The "command in-position function" checks the remaining distance to the stop position during the automatic deceleration of positioning control, and raises a flag. This flag is called the "command in-position flag". The command in-position flag is used as a front- loading signal indicating beforehand the completion of the position control.
The details shown below explain about the "command in-position function". [1] Control details [2] Precautions during control [3] Setting the command in-position function [4] Confirming the command in-position flag
The following shows control details of the command in-position function. (1) When the remaining distance to the stop position during the automatic deceleration of positioning control becomes equal to or less than the value set in " Pr.16 Command in-position width", "1" is stored in the command
in-position flag ( Md.31 Status: b2).
(Command in-position width check)
Remaining distance ≤ " Pr.16 Command in-position width" setting value
OFF Command in-position flag
Command in-position width setting value
Fig. 12.43 Command in-position operation
(2) A command in-position width check is carried out every 1.8ms.
t · Positioning

(1) A command in-position width check will not be carried out in the following cases.
Command in-position width setting value V
Speed to position switching
Speed-position switching control start
Command in-position width setting value
Command in-position flag [ Md. 31 Status: b2]
Execution of the command in-position width check
Execution of the command in-position width check
Fig. 12.44 Command in-position width check
(2) The command in-position flag will be turned OFF in the following cases.
("0" will be stored in " Md.31 Status: b2".)
(3) The " Pr.16 Command in-position width" and command in-position flag
control.
Positioning control start · t

To use the "command in-position function", set the required value in the parameter shown in the following table, and write it to the QD75. The set details are validated at the rising edge (OFF ON) of the PLC READY signal (Y0).
value Setting details Factory-set initial value
Turn ON the command in-position flag, and set the remaining distance to the stop position of the position control.
Pr.16 Command in- position width
Refer to Section 5.2 "List of parameters" for setting details.
The "command in-position flag" is stored in the following buffer memory.
Buffer memory address Monitor item Monitor
value Storage details Axis
Md.31 Status The command in-position flag is stored in the "b2" position. 817 917 1017 1117
Refer to Section 5.6 "List of monitor data" for information on the storage details.
![Page 560 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] "Acceleration/deceleration time 0 to 3" control details and setting](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-560.webp?w=400)
The "acceleration/deceleration processing function" adjusts the acceleration/deceleration when each control is executed. Adjusting the acceleration/deceleration processing to match the control enables more precise control to be carried out. There are two acceleration/deceleration adjustment items that can be set: "Acceleration/deceleration time 0 to 3", and "acceleration/deceleration method setting".
The details shown below explain about the "acceleration/deceleration processing function". [1] "Acceleration/deceleration time 0 to 3" control details and setting [2] "Acceleration/deceleration method setting" control details and setting
In the QD75, four types each of acceleration time and deceleration time can be set. By using separate acceleration/deceleration times, control can be carried out with different acceleration/deceleration times for positioning control, JOG operation, OPR, etc. Set the required values for the acceleration/deceleration time in the parameters shown in the following table, and write them to the QD75. The set details are validated when written to the QD75.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] "Acceleration/deceleration time 0 to 3" control details and setting diagram (page 560)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-560-1.webp)
Set the acceleration time at a value within the range of 1 to 8388608 ms.
Set the deceleration time at a value within the range of 1 to 8388608 ms.
Refer to Section 5.2 "List of parameters" for setting details.

setting In the "acceleration/deceleration method setting", the acceleration/deceleration processing method is selected and set. The set acceleration/deceleration processing is applied to all acceleration/deceleration. The two types of "acceleration/deceleration method setting" are shown below. (1) Automatic trapezoidal acceleration/deceleration processing
method This is a method in which linear acceleration/deceleration is carried out based on the acceleration time, deceleration time, and speed limit value set by the user.
Fig. 12.45 Automatic trapezoidal acceleration/deceleration processing method
In this method, the motor burden is reduced during starting and stopping. This is a method in which acceleration/deceleration is carried out gradually, based on the acceleration time, deceleration time, speed limit value, and " Pr.35 S-pattern proportion" (1 to 100%) set by the user.
When the stepping motor is used, the S-pattern acceleration/deceleration processing method cannot be carried out. When using this processing method, ensure to use a servomotor.
Fig. 12.46 S-pattern acceleration/deceleration processing method

When a speed change request is given during S-pattern acceleration/deceleration processing, S-pattern acceleration/deceleration processing begins at a speed change request start.
When speed change request is not given Speed change (acceleration)
Command speed before speed change
Fig. 12.47 Speed change during S-pattern acceleration/deceleration processing
Set the required values for the "acceleration/deceleration method setting" in the parameters shown in the following table, and write them to the QD75. The set details are validated when written to the QD75.
value Setting details Factory-set initial value
Set the acceleration/deceleration method.
Acceleration/ deceleration process selection
Pr.34
Set the acceleration/deceleration curve when "1" is set
Pr.35 S-pattern proportion
in " Pr.34 Acceleration/deceleration processing
selection".
Refer to Section 5.2 "List of parameters" for setting details.
Speed change request · Speed change (deceleration) · Setting item Setting
![Page 563 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Controls](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-563.webp?w=400)
The "pre-reading start function" does not output pulses while the execution prohibition flag is ON if a positioning start request is given with the execution prohibition flag ON, and starts outputting pulses within 3m after OFF of the execution prohibition flag is detected. The positioning start request is given when the axis is in a standby status, and the execution prohibition flag is turned OFF at the axis operating timing. This shortens the virtual start time. The QD75 normally takes 6 to 7ms from when it receives a positioning start request until it starts pulse output (start time). Some systems often need the start time to be shortened. This "pre-reading start function" can improve the tact time of the system.
The "pre-reading start function" will be explained below. [1] Controls [2] Controlling instructions [3] Program examples
The pre-reading start function is performed by turning ON the positioning start signal [Y10, Y11, Y12, Y13] with the execution prohibition flag [Y14, Y15, Y16, Y17] ON, or by executing the dedicated instruction (PSTRT1, PSTRT2, PSTRT3, PSTRT4). However, if positioning is started with the execution prohibition flag ON, the positioning data is analyzed but pulse output is not provided. While the execution prohibition flag is ON, " Md.26 Axis operation status" remains
unchanged from "5: Analyzing". Pulse output starts within 3ms after the execution prohibition flag [Y14, Y15, Y16, Y17] has turned OFF, and " Md.26 Axis
operation status" changes to the status (e.g. during position control, during speed control) that matches the control system. (Refer to Fig. 12.48)
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Controls diagram (page 563)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-563-1.webp)
Fig. 12.48 Operations of pre-reading start function

The pre-reading start function is effective for the system as shown below.
Fig. 12.49 System example using pre-reading start function
Fig. 12.49 shows a system example which repeats:


Fig. 12.50 Operation timings of system example
The cutter shaft starts from the moment the feed shaft has completed feeding the stock " 1 ", and the feed shaft starts from the moment the cutter shaft has returned to the standby position " 2 ". Actually, however, there is a delay of start time Ts (6 to 7ms) from when the QD75 receives a start request until it outputs pulses. The system's tact time can be reduced by the shortening of this delay with the Pre-reading start function. In Fig. 12.50, the feed shaft stands by during the stop time Tw. Hence, pre-reading of the next data starts during the stop time Tw. If Tw is a certain period of time, the analysis of the next data is completed during that period, and the system is placed in an execution prohibition flag OFF waiting status. Therefore, replacing the positioning start timing at 2 with the execution prohibition flag OFF allows the time from when the axis operation request turns ON until pulse output starts to be reduced to within 3ms in the sequence program. (Refer to Fig. 12.48)
![Page 566 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Program examples](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-566.webp?w=400)
(1) The time required to analyze the positioning data is up to 7ms. (2) After positioning data analysis, the system is put in an execution prohibition
flag OFF waiting status. Any change made to the positioning data in the execution prohibition flag OFF waiting status is not reflected on the positioning data. Change the positioning data before turning ON the positioning start signal. (3) The pre-reading start function is invalid if the execution prohibition flag is
turned OFF between when the positioning start signal has turned ON and when positioning data analysis is completed (Ta
start No." with the pre-reading start function are No. 1 to 600 only. Performing the pre-reading start function at the setting of No. 7000 to 7004 or 9001 to 9004 will result in an outside start No. range error (Error code: 543). (5) Always turn ON the execution prohibition flag at the same time or before
turning ON the positioning start signal. Pre-reading may not be started if the execution prohibition flag is turned ON during Ta after the positioning start signal is turned ON. The pre-reading start function is invalid if the execution prohibition flag is turned ON after positioning start (pulse output) with the execution prohibition flag OFF. (It is made valid at the next positioning start.)
Pre-reading start function (when positioning start signal Y10 is used)
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Program examples diagram (page 566)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-41.webp)

Pre-reading start function (when dedicated instruction PSTRT1 is used)

·
![Page 568 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [1] Control details](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-568.webp?w=400)
The "deceleration start flag function" turns ON the flag when the constant speed status or acceleration status switches to the deceleration status during position control whose operation pattern is "Positioning complete". This function can be used as a signal to start the operation to be performed by other equipment at each end of position control or to perform preparatory operation, etc. for the next position control.
For the "deceleration start flag function", the following will be explained. [1] Control details [2] Precautions during control [3] Deceleration start flag function setting method [4] Checking of deceleration start flag
When deceleration for a stop is started in the position control whose operation pattern is "Positioning complete", "1" is stored into " Md.48 Deceleration start flag". When the next operation start is made or the manual pulse generator operation enable status is gained, "0" is stored. (Refer to Fig. 12.51.)
(1) Start made with positioning data No. specified
Md.48 Deceleration start flag 0 1 0
Fig. 12.51 Operation of deceleration start flag
Time

At a block start, this function is valid for only the position control whose operation pattern is "Positioning complete" at the point whose shape has been set to "End". (Refer to Fig. 12.52.)
The following table indicates the operation of the deceleration start flag in the case of the following block start data and positioning data.

1st point 1: Continue 1 0: Block start 2nd point 1: Continue 3 0: Block start 3rd point 0: End 4 0: Block start
1 01: Continuous positioning control 2 00: Positioning complete 3 00: Positioning complete 4 11: Continuous path control 5 00: Positioning complete
Fig. 12.52 Operation of deceleration start flag at block start
(2) Block start
![Page 570 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions during control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-570.webp?w=400)
(1) The deceleration start flag function is valid for the control system of "1-axis
linear control", "2-axis linear interpolation control", "3-axis linear interpolation control", "4-axis linear interpolation control", "speed-position switching control" or "position-speed switching control". (In the case of linear interpolation control, the function is valid for only the reference axis.) Refer to Section 3.2.4 "Combination of QD75 main functions and sub functions". (2) The deceleration start flag does not turn ON when the operation pattern is
"continuous positioning control" or "continuous path control". (3) The deceleration start flag function is invalid for an OPR, JOG operation,
inching operation, manual pulse generator operation, and deceleration made with a stop signal. (4) The deceleration start flag does not turn ON when a speed change or
override is used to make deceleration. (5) If a target position change is made while the deceleration start flag is ON, the
deceleration start flag remains ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions during control diagram (page 570)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-570-1.webp)
(6) When the movement direction is reversed by a target position change, the
deceleration start flag turns ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions during control diagram (page 570)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-570-2.webp)
(7) During position control of position-speed switching control, the deceleration
start flag is turned ON by automatic deceleration. The deceleration start flag remains ON if position control is switched to speed control by the position-speed switching signal after the deceleration start flag has turned ON. (8) During skip operation, the deceleration start flag is valid for only the
positioning data whose operation pattern is "Positioning complete". (9) If the condition start of a block start is not made since the condition is not
satisfied, the deceleration start flag turns ON when the shape is "End". (10) When an interrupt request during continuous operation is issued, the
deceleration start flag turns ON at a start of deceleration in the positioning data being executed.
![Page 571 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Checking of deceleration start flag](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-571.webp?w=400)
To use the "deceleration start flag function", set "1" to the following control data using a sequence program. The set data is made valid on the rising edge (OFF to ON) of the PLC READY signal [Y0].
![Mitsubishi Electronics MELSEC-Q QD75D — [3] Deceleration start flag function setting method diagram (page 571)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-571-1.webp)
Set whether the deceleration start flag function is made valid or invalid. 0: Deceleration start flag invalid 1: Deceleration start flag valid
Refer to Section 5.7 "List of control data" for details on the setting details.
The "deceleration start flag" is stored into the following buffer memory addresses.
![Mitsubishi Electronics MELSEC-Q QD75D — [4] Checking of deceleration start flag diagram (page 571)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-571-2.webp)
Refer to Section 5.6 "List of monitor data" for information on the storage details.

The "stop command processing for deceleration stop function" is provided to set the deceleration curve if a stop cause occurs during deceleration stop processing (including automatic deceleration). This function is valid for both automatic trapezoidal and S-pattern acceleration/deceleration processing methods. (For the stop cause, refer to Section 1.2.3 Outline of stopping.)
The "stop command processing for deceleration stop function" performs the following two operations: (1) Deceleration curve re-processing Re-processes a deceleration curve starting from the speed at stop cause occurrence to stop, according to the preset deceleration time. (2) Deceleration curve continuation Continues the current deceleration curve after a stop cause has occurred.
This section explains the "stop command processing for deceleration stop function" as follows: [1] Control [2] Precautions for control [3] Setting method
The operation of "stop command processing for deceleration stop function" is explained below.
A deceleration curve is re-processed starting from the speed at stop cause occurrence to stop, according to the preset deceleration time. If a stop cause occurs during automatic deceleration of position control, the deceleration stop processing stops as soon as the target has reached the positioning address specified in the positioning data that is currently executed.
Deceleration curve according to preset deceleration time
Immediate stop at the specified positioning address
Deceleration stop processing (automatic
Deceleration curve when stop cause does not occur
Fig. 12.53 Deceleration curve re-processing operation (for position control or S-pattern
![Page 573 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions for control](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-573.webp?w=400)
The current deceleration curve is continued after a stop cause has occurred. If a stop cause occurs during automatic deceleration of position control, the deceleration stop processing may be complete before the target has reached the positioning address specified in the positioning data that is currently executed.

Fig. 12.54 Deceleration curve continuation operation (for position control or S-pattern
(1) In manual control (JOG operation, inching operation, manual pulse generator
operation), the stop command processing for deceleration stop function is invalid. (2) The stop command processing for deceleration stop function is valid when "0:
Normal deceleration stop" is set in " Pr.37 Stop group 1 sudden stop selection" to " Pr.39 Stop group 3 sudden stop selection" as the stopping method for stop cause occurrence. (3) The stop command processing for deceleration stop function is invalid when
"1: Sudden stop" is set in " Pr.37 Stop group 1 sudden stop selection" to " Pr.39 Stop group 3 sudden stop selection". (A deceleration curve is re- processed, according to the " Pr.36 Sudden stop deceleration time" (starting from the speed at stop cause occurrence to a stop)) In the position control (including position control of speed/position changeover control or position/speed changeover control) mode, positioning may stop immediately depending on the stop cause occurrence timing and " Pr.36 Sudden stop deceleration time" setting.
![Mitsubishi Electronics MELSEC-Q QD75D — [2] Precautions for control diagram (page 573)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-573-2.webp)
(Sudden stop cause) Deceleration curve according to sudden stop deceleration time
(Sudden stop in front of the specified positioning address)
Fig. 12.55 Sudden stop operation (for position control or S-pattern acceleration/deceleration processing)
acceleration/deceleration processing)
![Page 574 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [3] Setting method](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-574.webp?w=400)
To use the "stop command processing for deceleration stop function", set the following control data in a sequence program. The set data are made valid as soon as they are written to the buffer memory. The PLC ready signal [Y0] is irrelevant.
value Setting details Buffer memory address
Stop command processing for deceleration stop selection
Set the stop command processing for deceleration stop function. 0: Deceleration curve re-processing 1: Deceleration curve continuation
Cd.42
For details of the setting details, refer to "Section 5.7 Control data list".
Setting item Setting

The details and usage of the "common functions" executed according to the user's requirements are explained in this chapter.
Common functions include functions required when using the QD75, such as parameter initialization and execution data backup. Read the setting and execution procedures for each common function indicated in this chapter thoroughly, and execute the appropriate function where required.
13.1 Outline of common functions 13- 2 13.2 Parameter initialization function 13- 3 13.3 Execution data backup function 13- 5 13.4 External I/O signal logic switching function 13- 7 13.5 External I/O signal monitor function 13- 8

"Common functions" are executed according to the user's requirements, regardless of the control system, etc. These common functions are executed by peripheral devices or using sequence programs.
The following table shows the functions included in the "common functions".
Common function Details Sequence
This function returns the parameter stored in the QD75 buffer memory and flash ROM to the factory-set initial value.
This function writes the "execution data", currently being used for control, to the flash ROM.
This function switches I/O signal logic according to the equipment connected to the QD75. For the system in which drive unit READY with b-contact, upper limit switch, and lower limit switch are not used, the parameter logic setting can be controlled without wiring if it is changed to a "positive logic".
External I/O signal logic switching
This function monitors the external I/O signal monitor information in the module's detailed information which can be displayed on the system monitor of GX Developer .
External I/O signal monitor
Usable on GX Developer (SW6D5C-GPPW-E or later).

"The parameter initialization function" is used to return the setting data set in the QD75 buffer memory and flash ROM to their factory-set initial values.
The details shown below explain about the "parameter initialization function". [1] Parameter initialization means [2] Control details [3] Precautions during control [4] Parameter initialization method
Refer to GX Configurator-QP Operating Manual for the execution method by peripheral device.
The following table shows the setting data initialized by the "parameter initialization function". (The data initialized are "buffer memory" and " flash ROM " setting data.)
Basic parameters ( Pr.1 to Pr.10 )
Detailed parameters ( Pr.11 to Pr.42 , Pr.150 )
OPR basic parameters ( Pr.43 to Pr.48 )
OPR detailed parameters ( Pr.49 to Pr.57 )
Positioning data (No.1 to No.600)
Block start data (No.7000 to No.7004)
(1) Parameter initialization is only executed when the positioning control is not carried out (when the PLC READY signal (Y0) is OFF). A warning "In PLC READY (warning code: 111)" will occur if executed when the PLC READY signal (Y0) is ON. (2) A writing to the flash ROM is up to 100,000 times. If writing to the flash ROM exceeds 100,000 times, the writing may become impossible, and a flash ROM write error (error code: 801) will occur.
(3) A "PLC CPU reset" or "PLC power restart" must be carried out after the parameters are initialized.
(4) If an error occurs on the parameter set in the QD75 when the PLC READY signal [Y0] is turned ON, the QD75 READY signal [X0] will not be turned ON and the control cannot be carried out.
Parameter initialization takes about 10 seconds. (Up to 30 seconds are sometimes required.) Do not turn the power ON/OFF; reset the PLC CPU, etc., during parameter initialization. The flash ROM data may be corrupted.
Setting data
![Page 578 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Parameter initialization method](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-578.webp?w=400)
(1) Parameter initialization is carried out using the dedicated instruction "PINIT".
(Refer to Chapter 14 "Dedicated instructions" for details.)
(2) Parameter initialization can also be carried out by the writing of the data
shown in the table below to the buffer memory using the TO command/intelligent function device. The initialization of the parameter is executed at the time point the data is written to the QD75 buffer memory.
Buffer memory address Setting item Setting
value Setting details Axis
Cd.2 Parameter initialization request 1 Set "1" (parameter initialization request). 1901
Refer to Section 5.7 "List of control data" for details on the setting details.
When the initialization is complete, "0" will be set in " Cd.2 Parameter
initialization request" by the QD75 automatically.
1 Axis · 2 Axis · 3 Axis

When the QD75 buffer memory data is rewritten from the PLC CPU, "the data backed up in the QD75 flash ROM" may differ from "the data (buffer memory data) for which control is being executed". In cases like these, the data being executed will be lost when the PLC power is turned OFF. (Refer to Chapter 7.) In cases like these, the "execution data backup function" backs up the data being executed by writing it to the flash ROM. The data that was backed up is then written to the buffer memory when the power is turned ON next.
The details shown below explain about the "execution data backup function". [1] Execution data backup means [2] Control details [3] Precautions during control [4] Execution data backup method
Refer to GX Configurator-QP Operating Manual for execution data backup method by peripheral device.
The following shows the data that can be written to the flash ROM using the "execution data backup function".
Buffer memory Flash ROM
Parameters ( Pr.1 to Pr.57 , Pr.150 ) Parameters ( Pr.1 to Pr.57 , Pr.150 )
Positioning data (No. 1 to No. 600) Positioning data (No. 1 to No. 600) Block start data (No. 7000 to 7004) Block start data (No. 7000 to 7004)
(1) Data can only be written to the flash ROM when the positioning control is not carried out (when the PLC READY signal (Y0) is OFF).
(2) Writing to the flash ROM can be executed up to 100,000 times. If writing to the flash ROM exceeds 100,000 times, the writing may become impossible, and a "flash ROM write error (error code: 801)" will occur.
(3) After one power ON/PLC CPU reset operation, writing to the flash ROM using a sequence program is limited to up to 25 times. If the 26th writing is executed, a "flash ROM write number error (error code: 805)" will occur. If this error occurs, carry out the power OFF ON/PLC CPU reset operation again. Refer to Md.19 of Section 5.1.7 "Types and roles of monitor data" for
details.
Do not turn the power ON/OFF, reset the PLC CPU, during writing to the flash ROM. The flash ROM data may be corrupted.
![Page 580 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [4] Execution data backup method](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-580.webp?w=400)
(1) Execution data backup (writing to the flash ROM) is carried out using the
dedicated instruction "PFWRT". (Refer to Chapter 14 "Dedicated instructions" for details.)
(2) Refer to Section 7.2 "Data transmission process" for the data transmission
processing at the backup of the execution data.
(3) Execution data backup can also be carried out by the writing of the data
shown in the table below to the QD75 buffer memory using the TO command/intelligent function device. The writing to the flash ROM is executed at the time point the data is written to the QD75 buffer memory.
Buffer memory address Setting item Setting
value Setting details Axis
Cd.1 Flash ROM write request 1 Set "1" (flash ROM write request). 1900
Refer to Section 5.7 "List of control data" for details on the setting details.
When the writing to the flash ROM is complete, "0" will be set in " Cd.1 Flash
ROM write request" by the QD75 automatically.
1 Axis · 2 Axis · 3 Axis
![Page 581 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Precautions on parameter setting](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-581.webp?w=400)
This function switches the signal logic according to the external equipment connected to the QD75. For the system in which drive unit READY with b-contact, upper limit switch, and lower limit switch are not used, the parameter logic setting can be controlled without wiring if it is changed to a "positive logic". When the drive unit READY, upper limit switch, and lower limit switch are used, ensure to use them with b-contact.
The details shown below explain about the "External I/O signal logic switching function". [1] Parameter setting details [2] Precautions on parameter setting
To use the "External I/O signal logic switching function", set the parameters shown in the following table.
![Mitsubishi Electronics MELSEC-Q QD75D — [1] Parameter setting details diagram (page 581)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-581-1.webp)
Buffer memory address Setting item Setting details Factory-set initial value Axis 1 Axis 2 Axis 3 Axis 4
Refer to Section 5.2 "List of parameters" for the information on detail settings.
(1) The external I/O signal logic switching parameters are validated when the
PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right after power-on.)
(2) If each signal logic is set erroneously, the operation may not be carried out
correctly. Before setting, check the specifications of the equipment to be used.

The "External I/O signal monitor function" monitors the module's information and external I/O signal monitor information in the module's detailed information which can be displayed on the system monitor of GX Developer .
The information that can be monitored are the module's information (same as the QD75 front "RUN", "ERR" LED indicators) and the following external I/O signals. (Set the logic of the external I/O signals in " Pr.22 Input signal logic selection"
and " Pr.23 Output signal logic selection".)

Axis-by-axis external I/O signals and module RUN, ERR LEDs
Indicates that Drive unit ready of axis 1 is ON.
: Use GX Developer of "SW6D5C-GPPW-E or later". Refer to GX Developer
Operating Manual for the system monitor of GX Developer.

The QD75 dedicated instructions are explained in this chapter.
These instructions are used to facilitate the programming for the use of the functions of the intelligent function module. Using the dedicated instructions, the programming can be carried out without being aware of the QD75 buffer memory address and interlock signal.
14.1 List of dedicated instructions 14- 2 14.2 Interlock during dedicated instruction is executed 14- 2 14.3 ABRST1, ABRST2, ABRST3, ABRST4 14- 3 14.4 PSTRT1, PSTRT2, PSTRT3, PSTRT4 14- 8 14.5 TEACH1, TEACH2, TEACH3, TEACH4 14- 12 14.6 PFWRT 14- 16 14.7 PINIT 14- 20

The dedicated instructions explained in this Chapter are listed in Table 14.1.
Table 14.1 List of dedicated instructions
Application Dedicated instruction Outline of functions Reference
ABRST2
This function restores the absolute position of the designated axis of the QD75. Section 14.3
ABRST3 Absolute position restoration
PSTRT1
PSTRT2
This function starts the positioning control of the designated axis of the QD75. Section 14.4
TEACH1
TEACH2
This function carries out teaching the designated axis of the QD75. Section 14.5
Writing to flash ROM PFWRT This function writes the buffer memory parameters, positioning data and block start data to the flash ROM. Section 14.6
Parameter initialization PINIT This function initializes the buffer memory and flash ROM setting data to the factory-set data (initial values). Section 14.7
The absolute position restoration instruction (ABRST ), positioning start instruction (PSTRT ) and teaching instruction (TEACH ) cannot be executed simultaneously in each axis. If they are executed at the same time, the second and later instructions are ignored by an internal interlock (no error will occur). The timing of the positioning start dedicated instruction (PSTRT ) is as shown below.

Interlock provided by PLC CPU
BUSY (XC to XF)
OFF
Positioning completed (X14 to X17)
PSTRT3 Positioning start · TEACH3 Teaching · PSTRT instruction ON
![Page 585 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Setting data]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-585.webp?w=400)
These dedicated instructions restore the absolute position of the designated axis.

(S) – (D) –

When ABRST1, ABRST2, ABRST3, and ABRST4 are common to each other, they are designated as "ABRST ".
![Mitsubishi Electronics MELSEC-Q QD75D — [Setting data] diagram (page 585)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-585-3.webp)
"Un" QD75 head I/O number (00 to FE: High-order two digits of I/O number expressed in three digits) User BIN 16 bits
(S) Head number of a device in which control data is stored – Device
Head number of a bit device which turns ON the operation by one scan at the time of completion of the instruction. If the instruction is completed abnormally, ((D) + 1) will also be turned ON.

Device Item Setting data Setting range Setting side
( 1) (S)+0 System area – – –
The state at the time of completion is stored.
The following signal states taken in from the servo amplifier to the input module are written.
(S)+2 Signal received from servo amplifier
The ON/OFF states of the following data which are calculated using the dedicated instructions by the "signals received from the servo amplifier" and output to the servo amplifier are stored.
(S)+3 Signal transmitted to servo amplifier
Status of communication with servo amplifier
(Set by user at communication start) • Other than 0: During communication (System stores)
(S)+7 System area – – –
(1) The positioning data is read from the servo amplifier capable of processing the
absolute positions of the axes to be set (See below), and the values converted with respect to a unit are stored in " Md.20 current feed value" and " Md.21 machine
For absolute position detection system, carry out the absolute position restoration operation each time the power is turned ON or PLC CPU is reset.
QD75


(2) An I/O module is used for communication (data read/write) with the servo amplifier
(3) The ABRST instruction completion can be confirmed using the complete devices ((D)+0) and ((D)+1).
(a) Complete device ((D)+0)
This device is turned ON by the END processing of the scan for which ABRST instruction is completed, and turned OFF by the next END processing.
(b) Complete state display device ((D)+1)
processing of the scan for which ABRST instruction is completed, and turned OFF by the next END processing. (same ON/OFF operation as complete device).

Complete state display device
The completion of absolute position restoration can be confirmed using the ((S)+4) "status".
![Page 588 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Precautions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-588.webp?w=400)
(4) Using the ABRST instruction, the absolute position restoration is carried out in the following procedure.
Output the ((S)+3) data.
Output the servo ON, ABS transfer mode, and ABS request flag to the output module using the sequence program.
Set the data in ((S)+2).
Set the ABS data bit 0/bit 1 and transmission data READY flag using the sequence program.
Execute the ABRST instruction.
Is ((S)+4) "0"? Other than "0"
(1) When a dedicated instruction is completed abnormally, the error complete signal
((D)+1) is turned ON, and the error code is stored in the complete status ((S)+1). Check and take a measure against the error referring to Section 15.2 "List of error codes".
(1) After the absolute position detection system is configured, the absolute position
restoration must be carried out at least once after the power is turned ON or reset. Unless the absolute position restoration of the QD75 is completed, the servo amplifier will not be turned ON. (2) Execute absolute position restoration when the PLC READY signal [Y0] is OFF. (3) The restoration of the absolute position (ABRST instruction execution) can also be carried out when the servo amplifier is turned ON. If this is carried out, however, the servo ON signal is turned OFF for about 20 ms (servo OFF) and the motor may move. When carrying out the absolute position restoration during servo OFF, install an electromagnetic brake and output the ABRST instruction to that brake during the ABRST instruction execution. (4) The following dedicated instructions cannot be executed simultaneously for the
same axis. (Can be executed simultaneously for different axes.)
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H
Network System Reference Manual (Remote I/O Network).
Start · End
![Page 589 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Program examples]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-589.webp?w=400)
(6) If the ABRST instruction is executed in either of the following cases, an error
"Dedicated instruction error" (error code: 804) will occur and absolute position restoration cannot be carried out.
Program to restore the absolute position of axis 1. The X47 to X49 and Y50 to Y52 are used for communication with the servo amplifier.
X47: ABS data bit 0 X48: ABS data bit 1 X49: Transmission data READY flag Y50: Servo ON signal Y51: ABS transfer mode Y52: ABS request flag
No. 23 Absolute position restoration program
(1) Absolute position restoration command acceptance
![Mitsubishi Electronics MELSEC-Q QD75D — [Program examples] diagram (page 589)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-44.webp)
(2) Setting of transmit data to servo-amplifier and confirmation of absolute position restoration completion ABRST1 instruction completed when M42 is ON and M43 is OFF. Absolute position data restoration completed when status = 0.
![Mitsubishi Electronics MELSEC-Q QD75D — [Program examples] diagram (page 589)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-45.webp)
(3) ABS data setting and ABRST1 instruction execution
![Mitsubishi Electronics MELSEC-Q QD75D — [Program examples] diagram (page 589)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-46.webp)
·
![Page 590 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Setting data]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-590.webp?w=400)
These dedicated instructions are used to start the positioning of the designated axis.

(S) – (D) –

When PSTRT1, PSTRT2, PSTRT3, and PSTRT4 are common to each other, they are designated as "PSTRT ".
![Mitsubishi Electronics MELSEC-Q QD75D — [Setting data] diagram (page 590)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-590-3.webp)
"Un" QD75 head I/O number (00 to FE: High-order two digits of I/O number expressed in three digits) User BIN 16 bits
(S) Head number of a device in which control data is stored – Device
Head number of a bit device which turns ON the operation by one scan at the time of completion of the instruction. If the instruction is completed abnormally, ((D) + 1) will also be turned ON.
![Page 591 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Functions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-591.webp?w=400)
Device Item Setting data Setting range Setting side
( 1) (S)+0 System area – – –
The state at the time of completion is stored.
The following data Nos. to be started by the PSTRT instruction are designated.
1 to 600 7000 to 7004 9000 to 9004 User
(S)+2 Start No.
(1) The positioning start of the axes to be processed (See below) is carried out.
(2) The block start, OPR start, current value changing, and multiple axes
simultaneous start can be carried out by the setting of "start number" 7000 to 7004/9001 to 9004 in ((S)+2).
(3) The PSTRT instruction completion can be confirmed using the complete devices ((D)+0) and ((D)+1).
(a) Complete device ((D)+0)
This device is turned ON by the END processing of the scan for which PSTRT instruction is completed, and turned OFF by the next END processing.
(b) Complete state display device ((D)+1)
processing of the scan for which PSTRT instruction is completed, and turned OFF by the next END processing. (same ON/OFF operation as complete device).
(S)+1 Complete status
![Page 592 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Precautions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-592.webp?w=400)

Complete state display device
(1) When an PSTRT instruction is completed abnormally, the error complete signal ((D)+1) is turned ON, and the error code is stored in the complete status ((S)+1). Check and take a measure against the error referring to Section 15.2 "List of error codes".
(1) When positioning is started by the PSTRT instruction, the positioning start
signals (Y10 to Y13) and start complete signals (X10 to X13) will not turn ON. To confirm that positioning control is being executed, use the PSTRT start command or BUSY signals (XC to XF).
(2) If, after positioning has been started by the PSTRT instruction, a stop command
is input before positioning is complete, the complete device (D) turns ON one scan and the execution of the PSTRT instruction is completed.
(3) The following dedicated instructions cannot be executed simultaneously for the
(4) The PSTRT instruction can only be executed when the QD75 READY signal (X0) is turned ON. Even if the PSTRT instruction execution request is given when the QD75 READY signal is turned OFF, the PSTRT instruction will not be executed. (not processed.) Before executing the PSTRT instruction, turn ON the PLC READY signal (Y0), and turn ON the QD75 READY signal (X0).
(5) When the remote I/O station (Q Corresponding MELSECNET/H network remote I/O module) is used, the dedicated instruction (PSTRT ) is unusable.
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H
Network System Reference Manual (Remote I/O Network).

(6) If the PSTRT instruction is executed in either of the following cases, an error
"Dedicated instruction error" (error code: 804) will occur and positioning cannot be started. • Any value other than 1 to 600, 7000 to 7004, and 9001 to 9004 is set to
"Starting number" (device: (S)+2) of the control data. • The instruction for a non-existent axis is specified.
![Mitsubishi Electronics MELSEC-Q QD75D — [Program examples] diagram (page 593)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-47.webp)
Positioning start program (when dedicated instruction is not used)
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example for use when dedicated instruction is not used] diagram (page 593)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-48.webp)
Positioning start program · ·
![Page 594 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Setting data]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-594.webp?w=400)
These dedicated instructions are used to teach the designated axis.

(S) – (D) –

When TEACH1, TEACH2, TEACH3, and TEACH4 are common to each other, they are designated as "TEACH ".
![Mitsubishi Electronics MELSEC-Q QD75D — [Setting data] diagram (page 594)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-594-3.webp)
"Un" QD75 head I/O number (00 to FE: High-order two digits of I/O number expressed in three digits) User BIN 16 bits
(S) Head number of a device in which control data is stored – Device
Head number of a bit device which turns ON the operation by one scan at the time of completion of the instruction. If the instruction is completed abnormally, ((D) + 1) will also be turned ON.
![Page 595 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Functions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-595.webp?w=400)
Device Item Setting data Setting range Setting side
( 1) (S)+0 System area – – –
The state at the time of completion is stored.
The address (positioning address/arc address) to which the current feed value is written is set.
(S)+2 Teaching data selection
(S)+3 Positioning data No. The positioning data No. for which teaching is carried out
is set. 1 to 600 User
(1) The "current feed value" of the axes to be set (See below) is set in the positioning
(2) Teaching can be carried out for the positioning data No. 1 to 600.
(3) The movement of the machine to the address (position) set in the positioning
address/arc address of the positioning data is carried out by the JOG operation, inching operation, or manual pulse generator operation.
(4) The TEACH instruction completion can be confirmed using the complete devices ((D)+0) and ((D)+1).
(a) Complete device ((D)+0)
This device is turned ON by the END processing of the scan for which TEACH instruction is completed, and turned OFF by the next END processing.
(b) Complete state display device ((D)+1)
processing of the scan for which TEACH instruction is completed, and turned OFF by the next END processing. (same ON/OFF operation as complete device).
(S)+1 Complete status · 0, 1 User
![Page 596 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Precautions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-596.webp?w=400)

Complete state display device
(1) When a TEACH instruction is completed abnormally, the error complete signal
((D)+1) is turned ON, and the error code is stored in the complete status (S)+1. Check and take a measure against the error referring to Section 15.2 "List of error codes".
(1) The following dedicated instructions cannot be executed simultaneously for the
(2) The TEACH instruction can only be executed when the BUSY signal (XC, XD, XE, XF) is turned OFF. When the BUSY signal is turned ON, the TEACH instruction will not be executed. (not processed.) Before executing the PFWRT instruction, make sure that the BUSY signal for the axis to be processed is turned OFF.
(3) When the remote I/O station* (Q Corresponding MELSECNET/H network remote
I/O module) is used, the dedicated instruction (TEACH ) is unusable.
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H
Network System Reference Manual (Remote I/O Network).
(4) If the TEACH instruction is executed in any of the following cases, an error
"Dedicated instruction error" (error code: 804) will occur and teaching cannot be performed. • Any value other than 0 and 1 is set to "Teaching selection" (device: (S)+2) of the
control data. • Any value other than 1 to 600 is set to "Positioning No." (device: (S)+3) of the
control data. • The instruction for a non-existent axis is specified.
![Page 597 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Program example for use when dedicated instruction is not used]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-597.webp?w=400)
Program to execute the teaching of the positioning data No. 3 of the axis 1 when X39 is turned ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example] diagram (page 597)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-597-1.webp)
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example for use when dedicated instruction is not used] diagram (page 597)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-597-2.webp)
![Page 598 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Control data]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-598.webp?w=400)
These dedicated instructions are used to write the QD75 parameters, positioning data and block start data to the flash ROM.

(S) – (D) –

![Mitsubishi Electronics MELSEC-Q QD75D — [Setting data] diagram (page 598)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-598-3.webp)
"Un" QD75 head I/O number (00 to FE: High-order two digits of I/O number expressed in three digits) User BIN 16 bits
(S) Head number of a device in which control data is stored – Device
Head number of a bit device which turns ON the operation by one scan at the time of completion of the instruction. If the instruction is completed abnormally, ((D) + 1) will also be turned ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [Control data] diagram (page 598)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-598-4.webp)
The state at the time of completion is stored.
![Page 599 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Errors]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-599.webp?w=400)
(1) The PFWRT instruction completion can be confirmed using the complete devices
((D)+0) and ((D)+1).
(a) Complete device ((D)+0)
This device is turned ON by the END processing of the scan for which PFWRT instruction is completed, and turned OFF by the next END processing.
(b) Complete state display device ((D)+1)
processing of the scan for which PFWRT instruction is completed, and turned OFF by the next END processing. (same ON/OFF operation as complete device).
[Instruction symbol] [Execution condition]
PFWRT ZP.PFWRT "Un" (S) (D)
![Mitsubishi Electronics MELSEC-Q QD75D — [Functions] diagram (page 599)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-599-1.webp)
Complete state display device
(1) When a dedicated instruction is completed abnormally, the error complete signal
((D)+1) is turned ON, and the error code is stored in the complete status ((S)+1). Check and take measures against the error referring to Section 15.2 "List of error codes".
![Page 600 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Precautions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-600.webp?w=400)
(1) Do not turn ON the power and reset the PLC CPU while parameters, positioning
data and block start data are written to the flash ROM using the PFWRT instruction. A parameter error will occur or normal positioning start will become impossible because the parameters, positioning data and block start data are not written normally to the flash ROM. If this occurs, restart the operation by the method shown below. • For GX Configurator-QP, write the parameters, positioning data and block start
data again to the flash ROM. • For a sequence program, write the parameters, positioning data and block start
data to the QD75 after initializing the parameters (PINIT instruction execution and others). Then execute the PFWRT instruction again.
(2) A writing to the flash ROM is up to 100,000 times.
If writing to the flash ROM exceeds 100,000 times, the writing to the flash ROM will become impossible.
(3) After the power ON and PLC CPU reset operation, writing to the flash ROM using
a sequence program is limited to up to 25 times. (Not limited to up to 25 times when writing to the flash ROM is carried out by peripheral device.) If the 26th or more writing is requested after the power ON/PLC CPU reset operation, a flash ROM write number error (error code: 805) will occur, and the writing will be disabled. If a flash ROM write error occurs by one writing to the flash ROM, check and correct the flash ROM writing program. Then reset the error or turn ON the power and reset the PLC CPU again.
(4) The PFWRT instruction can only be executed when the QD75 READY signal (X0)
is turned OFF. When the QD75 READY signal is turned ON, the PFWRT instruction cannot be executed. Before executing the PFWRT instruction, turn OFF the PLC READY signal (Y0) and then turn OFF the QD75 READY signal.
(5) When the remote I/O station (Q Corresponding MELSECNET/H network remote I/O module) is used, the dedicated instruction (PFWRT) is unusable.
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H
Network System Reference Manual (Remote I/O Network).
![Page 601 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Program example for use when dedicated instruction is not used]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-601.webp?w=400)
Program used to write the parameters and positioning data stored in the buffer memory to the flash ROM when X3D is turned ON.
No. 26 Flash ROM write program
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example] diagram (page 601)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-49.webp)
Flash ROM write program (when dedicated instruction is not used)
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example for use when dedicated instruction is not used] diagram (page 601)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-50.webp)
![Page 602 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Control data]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-602.webp?w=400)
This dedicated instruction is used to initialize the setting data of the QD75.

(S) – (D) –

![Mitsubishi Electronics MELSEC-Q QD75D — [Setting data] diagram (page 602)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-602-3.webp)
"Un" QD75 head I/O number (00 to FE: High-order two digits of I/O number expressed in three digits) User BIN 16 bits
(S) Head number of a device in which control data is stored – Device
Head number of a bit device which turns ON the operation by one scan at the time of completion of the instruction. If the instruction is completed abnormally, ((D) + 1) will also be turned ON.
![Mitsubishi Electronics MELSEC-Q QD75D — [Control data] diagram (page 602)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-602-4.webp)
The state at the time of completion is stored.
![Page 603 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Precautions]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-603.webp?w=400)
(1) This dedicated instruction is used to return the setting data set in the QD75 buffer
memory and flash ROM to their factory-set data (initial values).
Parameters ( Pr.1 to Pr.57 , Pr.150 )
Positioning data (No. 1 to No. 600) Block start data (No. 7000 to 7004)
(2) The PINIT instruction completion can be confirmed using the complete devices
((D)+0) and ((D)+1).
(a) Complete device ((D)+0)
This device is turned ON by the END processing of the scan for which PINIT instruction is completed, and turned OFF by the next END processing.
(b) Complete state display device ((D)+1)
processing of the scan for which PINIT instruction is completed, and turned OFF by the next END processing. (same ON/OFF operation as complete device). END processing
![Mitsubishi Electronics MELSEC-Q QD75D — [Functions] diagram (page 603)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-603-1.webp)
Complete state display device
(1) When a dedicated instruction is completed abnormally, the error complete signal
((D)+1) is turned ON, and the error code is stored in the complete status ((S)+1). Check and take measures against the error referring to Section 15.2 "List of error codes".
(1) The PINIT instruction can only be executed when the QD75 READY signal (X0) is
turned OFF. When the QD75 READY signal is turned ON, the PINIT instruction cannot be executed. Before executing the PINIT instruction, turn OFF the PLC READY signal (Y0) and then turn OFF the QD75 READY signal. (2) When the remote I/O station (Q Corresponding MELSECNET/H network remote I/O module) is used, the dedicated instruction (PINIT) is unusable.
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H
Network System Reference Manual (Remote I/O Network).
![Page 604 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Program example for use when dedicated instruction is not used]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-604.webp?w=400)
The following program initializes the parameters in buffer memory and flash ROM when X3C turns ON.
No. 25 Parameter initialization program
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example] diagram (page 604)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-51.webp)
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example] diagram (page 604)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-52.webp)
Parameter initialization program (when dedicated instruction is not used)
![Mitsubishi Electronics MELSEC-Q QD75D — [Program example for use when dedicated instruction is not used] diagram (page 604)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/rimg-53.webp)
·

The "errors" and "warnings" detected by the QD75 are explained in this chapter.
Errors can be confirmed with the QD75 LED display and peripheral devices. When an error or warning is detected, confirm the detection details and carry out the required measures.
15.1 Error and warning details 15- 2 15.2 List of errors 15- 6 15.3 List of warnings 15- 32 15.4 LED display functions 15- 38

[1] Errors
Types of errors
Errors detected by the QD75 include parameter setting range errors and errors at the operation start or during operation.
(1) Parameter setting range errors
The parameters are checked when the power is turned ON and at the rising edge (OFF ON) of the PLC READY signal [Y0]. An error will occur if there is a mistake in the parameter setting details at that time. When this kind of error occurs, the QD75 READY signal does not turn ON. To cancel this kind of error, set the correct value in the parameter for which the error occurred, and then turn ON the PLC READY signal [Y0].
(2) Errors at the operation start or during operation
These are errors that occur at the operation start or during operation when the positioning control, JOG operation, or inching operation is used. If an axis error occurs during interpolation operation, the error No. will be stored in both the reference axis and the interpolation axis. Note that, in the following cases (a) and (b), the axis error No. will be stored only in the reference axis during analysis of the positioning data set in each point of the positioning start data table. (a) When the interpolation axis is BUSY. (b) When the error occurred in positioning data or parameters unrelated to
interpolation control.
(3) Types of error codes
Error code Error type 001 to 009 Fatal error 100 to 199 Common error 200 to 299 Error at OPR or absolute position restoration
300 to 399 Error during JOG operation or during inching operation 500 to 599 Error during positioning operation 800 to 899 I/F (Interface) error 900 to 999 Error during parameter setting range check
![Page 607 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] Warnings](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-607.webp?w=400)
When an error occurs, the error detection input turns ON, and the error code corresponding to the error details is stored in the following buffer memory address ( Md.23 Axis error No.) for axis error No. storage. Note that there is a delay of up
to 1.8 ms after the error detection signal turns ON until the error code is stored.
Axis No. Error detection signal Buffer memory address
2 X9 906
3 XA 1006
4 XB 1106
A new error code is stored in the buffer memory address ( Md.23 Axis error No.)
for axis error storage every time an error occurs.
Types of warnings
(1) Warnings include system warnings and axis warnings.
The types of system warnings are shown below.
(2) Axis warnings occur due to setting warnings from operations such as
positioning operations, JOG operations, manual pulse generator operations, or system errors. They can be canceled by turning ON the " Cd.5 Axis error
reset". Note that some warnings cannot be canceled unless the cause of the warning is eliminated. The axis operation status does not change even if an axis warning occurs.
(3) Types of warning codes
100 to 199 Common warning
300 to 399 Warning during JOG operation
400 to 499 Warning during manual pulse generator operation
500 to 599 Warning during positioning operation
![Page 608 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [5] Confirming the error and warning definitions](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-608.webp?w=400)
(1) When an axis warning occurs, the warning code corresponding to the warning
details is stored in the following buffer memory ( Md.24 Axis warning No.) for
axis warning No. storage.
Axis No. Buffer memory address
(2) When an axis warning occurs in a positioning operation, etc., "1" is set in bit 9
(b9) of the following buffer memory ( Md.31 Status) for axis status storage.
Axis No. Buffer memory address
An error or warning state is canceled after the following processing has been carried out by setting a "1" in the address [1502 (for axis 1)], [1602 (for axis 2)], [1702 (for axis 3)], and [1802 (for axis 4)] of the buffer memory for axis error resetting ( Cd.5 Axis error reset).
For the following operations, the setting details will be invalidated, and an error or warning will not occur.
The error and warning definitions can be confirmed with the error and warning codes. Confirming them requires GX Developer or GX Configurator-QP. For details, refer to GX Developer Operating Manual or GX Configurator-QP Operating Manual. (Refer to Section 15.2 and Section 15.3 for details of the error and warning codes.)

MEMO

The following table shows the error details and remedies to be taken when an error occurs.
Error code Error name Error Operation status at error occurrence
— 000 (Normal status) — —
001 Faults Fatal errors 002 Internal circuit fault Hardware is faulty. The system stops.
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 Sudden stop selection (stop group 2). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
101 PLC READY OFF during operation
A PLC READY signal (Y0) is turned OFF during operation.
102 Drive unit READY OFF
The drive unit READY signal is turned OFF during operation. The system stops immediately.
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 Sudden stop selection (stop group 2). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
103 Test mode faults during operation
The personal computer cannot communicate with the CPU unit.
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 Sudden stop selection (stop group 1). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
104 Hardware stroke limit (+)
The hardware stroke limit (upper limit signal FLS) is turned OFF.
105 Hardware stroke limit (–)
The hardware stroke limit (lower limit signal RLS) is turned OFF.
106 Stop signal ON at start
Start is requested when a stop signal is turned ON. The system does not start positioning.
The PLC READY signal is turned from OFF to ON when BUSY signal is turned ON.
107 READY OFF ON during BUSY
The QD75 READY signal (X0) is not turned ON.
When the OPR retry invalid is set, the near-point dog machine OPR is started with the OPR complete flag turned ON.
OPR 201 Start at OP
The machine OPR is not started.
Classification · of errors · Common

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
—
—
Check the drive unit power, wiring with the drive unit, and connection of connectors, and cancel the error with an axis error reset. (Refer to Section 15.1[3])
—
— Check that there is no error on the personal computer side I/F to which a cable is connected.
After making an axis error reset (refer to [3] in Section 15.1), perform manual control operation (refer to Chapter 11) to move the axis to the other position in order that the upper limit signal (FLS) will not turn OFF.
—
After making an axis error reset (refer to [3] in Section 15.1), perform manual control operation (refer to Chapter 11) to move the axis to the other position in order that the lower limit signal (RLS) will not turn OFF.
—
—
— Turn ON the PLC READY signal (Y0) with the BUSY signals of all axes OFF.
78 228 378 528
Related buffer memory · address · 0, 1

Error code Error name Error Operation status at error occurrence
The near-point dog signal is turned OFF during the deceleration from an OPR speed to a creep speed by the near-point dog machine OPR.
203 Dog detection timing fault
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 Sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
The zero signal is turned OFF during the deceleration from an OPR speed to a creep speed by the stopper method 2)-OPR.
204 OP detection timing fault
A dwell time is passed during the deceleration from a creep speed to a OPR speed by the stopper method 1)-OPR.
205 Dwell time fault
In the count method 1 and 2 machine OPR, a parameter "Setting of movement amount after near- point dog ON" is smaller than a distance necessary for deceleration stop from an OPR speed.
206 Count method movement amount fault
The machine OPR is not started.
The OPR request flag is turned ON when a fast-OPR is started (positioning start No. 9002).
207 OPR request ON
The fast OPR is not started.
The restart command is turned ON after the machine OPR is stopped using a stop signal.
209 OPR restart not possible
The restart is not carried out.
213 ABS transmission time
Communication cannot be carried out with the servo-amplifier using an absolute position restoration instruction.
The absolute position restoration is not carried out.
214 ABS transmission SUM
The JOG operation is not carried out when the JOG speed is outside the setting range at the time of JOG start. JOG inching
300 Outside JOG speed range
At the time of JOG starting, the JOG speed comes out of a specified range.
The inching operation is not carried out when the inching movement amount exceeds a JOG speed limit at the time of inching start.
301 Inching movement amount error
The inching movement amount exceeds the JOG speed limit.
The condition data No. is outside the setting range when a block using the condition data is started by a special starting (conditional start, wait start, simultaneous start, FOR (condition)). (1 Condition data No. 10)
operation 500 Illegal condition data No.
The operation is terminated.
Classification · of errors · Positioning

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
74 75 224 225 374 375 524 525
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or others]
74 75 224 225 374 375 524 525
74 75 224 225 374 375 524 525
79 229 379 529
80 81 230 231 380 381 530 531
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min]
74 75 224 225 374 375 524 525
1 to 600 7000 to 7004 9001 to 9004
Execute the machine OPR (positioning No. 9001). (Refer to Section 8.2)
1500 1600 1700 1800
1 to 600 7000 to 7004 9001 to 9004
Start the machine OPR (positioning start No. 9001) again. (Refer to Section 8.2)
1500 1600 1700 1800
—
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or others]
1518 1519 1618 1619 1718 1719 1818 1819
Bring the JOG speed into the setting range. (Refer to Section 11.2)
1517 1617 1717 1817
0 to 65535 Reduce the inching movement amount. (Refer to Section 11.3)
Refer to Section 5.4 "List of block start data"
1 to 10 Review the condition data No. (Refer to Section 5.4 Da.14 )

Error code Error name Error Operation status at error occurrence
simultaneously> • The partner axis for simultaneous start is BUSY.
501 Error before simultaneous start
The system stops immediately.
502 Illegal data No.
The positioning data is not executed.
At the start of positioning, operation does not start.
503 No command speed

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
Axis designation:
Refer to Section 5.5 "List of condition data"
Normalize the condition operators. (Refer to Section 5.5 Da.16)
10H, 20H, 30H, 40H, 50H, 60H, 70H, 80H, 90H, A0H, B0H, C0H, D0H, E0H
1540 1640 1740 1840 Axis 1 start data No.
Simultaneous start axis start
1541 1641 1741 1841 Axis 2 start data No.
Normalize the simultaneous start axis start data No. (Refer to Section 10.5)
data No.
1542 1642 1742 1842 Axis 3 start data No.
1543 1643 1743 1843 Axis 4 start data No.
1 to 600, 7000 to 7004, 9001 to 9004
1500 1600 1700 1800
Normalize the positioning start No., positioning start data (in block start), and positioning data (in JUMP instruction).
Refer to Section 5.3 "List of positioning data"
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or others] Normalize the positioning data.

Error code Error name Error Operation status at error occurrence
504 Outside linear movement amount range
The system stops immediately.
When an arc is interpolated by the designation of the center point, a difference between a radius of start point-center point and a radius of end point-center point exceeds the parameter "Circular interpolation error allowable limit".
control by center point designation is not executed. During operation :
506 Large arc error deviation
The system will stop immediately.

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
Review the positioning address.
Refer to Section 5.3 "List of positioning data"
60 61 210 211 360 361 510 511
Correct the circular interpolation error allowable limit value.

Error code Error name Error Operation status at error occurrence
Current value is not changed. During operation:
507 Software stroke limit+
508 Software stroke limit–
The new current address is outside the ranges of 0 to 359.99999, where the control unit is set to "degree".
514 Outside new current value range
The current value is not changed.
515 New current value not possible
516 Continuous path control not possible
At start, the system will not operate.

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
1506 1507 1606 1607 1706 1707 1806 1807
stroke limit using the manual control operation. (Refer to Chapter 11) Correct the positioning address (Also check the arc address in circular interpolation with sub points designated). New current value:
Bring the new current value into the software stroke limit. (Refer to Section 9.2.19)
18 19 168 169 318 319 468 469
During operation:
Correct the positioning address. (For the positioning and arc addresses, refer to Da.6 and Da.7 in Section 5.3.)
20 21 170 171 320 321 470 471
1506 1507 1606 1607 1706 1707 1806 1807 [degree] 0 to 35999999
Bring the new current value into the setting range. (Refer to Section 9.2.19)
Refer to Section 5.3 "List of positioning data"

Error code Error name Error Operation status at error occurrence
518 Outside operation pattern range
519 Interpolation while interpolation axis BUSY
Interpolation is started during the operation of the interpolation axis.
The reference and interpolation axis units are different at the parameter "interpolation speed designation method" setting of "composite speed".
520 Unit group unmatched
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 Sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
521 Illegal interpolation description command
The command speed is outside the setting range. Linear interpolation, circular interpolation: Reference axis is outside the setting range. Speed control interpolation: Either of reference axis and interpolation axis is outside the speed range.
522 Command speed setting error
523 Interpolation mode error

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
Correct the operation pattern. (Refer to Section 5.3 Da.1 ) Same as error codes 515 to 516
Correct the control system. (Refer to Section 5.3 Da.2 )
Correct the positioning data or change the parameter "Unit setting" of the axis to be interpolated. (Refer to Section 9.1.6)
0 150 300 450
0, 1, 2, 3
Same as error codes 515 to 516
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or others]
Correct the command speed. (Refer to Section 5.3 Da.8 )
data No. 1 to 600
Set the "Interpolation speed designation method" correctly. (Refer to Section 9.1.6)
29 179 329 479

Error code Error name Error Operation status at error occurrence
The system stops with the setting (deceleration stop/sudden stop) of the detail parameter 2 Sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
524 Control system setting error
525 Sub point setting error
The system stops immediately.
526 End point setting error
527 Center point setting error
The system stops immediately.
The system stops immediately with the setting (deceleration stop/sudden stop) of the detailed parameter 2 sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
530 Outside address range
Among the axes to be started simultaneously, there is an axis on which an error other than this error occurs.
532 Simultaneous start not possible

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
Same as error codes 515 to 516
Correct the sub address (arc address). (Refer to Section 9.2.10)
amount> • unit [mm] [pulse] [inch] –2147483648 to 2147483647 (Unit [degree]) cannot be set.
Correct the end address (positioning address). (Refer to Section 9.2.10)
Refer to Section 5.3 "List of positioning data"
Correct the center point address (arc address). (Refer to Section 9.2.11)
Same as in error codes 504, 506. Correct the positioning address. (Refer to Section 9.2.16, 9.2.17, 9.2.18)
Refer to Section 5.3 "List of positioning data"
In the error history, check the axis where the error other than this error occurred, and remove the error factor. Correct the block start data and positioning data.
and Section 5.4 "Block start data"

Error code Error name Error Operation status at error occurrence
533 Condition data error
The operation is terminated.
534 Special start instruction error
535 Circular interpolation not possible
Circular interpolation is carried out on an axis in the unit of degree.
The positioning start is carried out when an M code ON signal (X4 to X7) is turned ON.
536 M code ON signal start
The positioning start is carried out when the PLC READY signal (Y0) is turned OFF.
537 PLC READY OFF start
The positioning start is carried out when the QD75 READY signal (X0) is turned OFF.
538 READY OFF start
At start, the system will not operate.
543 Outside start No. range
544 Outside radius range The arc radius exceeds 536870912.
The system stops immediately.
545 Control system LOOP setting error
A "0" is set in the control system "LOOP". The operation is terminated.

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
— Normalize the block start data.
Refer to Section 5.4
00H to 06H Correct the instruction code of the special start data. (Refer to Section 5.4 Da.13 )
Refer to Section 5.3 "List of positioning data" — Correct the control system. (Refer to Section 5.3 Da.2 )
1504 1604 1704 1804 1: M code ON signal is turned OFF After turning OFF the M code ON signal, start the system. (Refer to Section 12.7.3)
Check the sequence program which turns ON/OFF the PLC READY signal (Y0), and turn ON the PLC READY signal. Then start the system.
—
— Check the QD75 READY ON signal, and then start the system. (Refer to Section 3.3.2)
1 to 600, 7000 to 7004, 9001 to 9004
Normalize the positioning start No. (Refer to Section 12.7.8)
1500 1600 1700 1800
536870912 Correct the positioning data. (Refer to Section 9.2.10, 9.2.11) Refer to Section 5.3 "List of positioning data"
1 to 65535 Set 1 to 65535 in LOOP. (Refer to Section 9.2.22)

Error code Error name Error Operation status at error occurrence
The system decelerates to a stop. (Note that, in the continuous positioning control and continuous path control, the system continues operating with the setting set at the time of start even if the setting is changed during the operation.)
operation 546 Illegal setting of ABS direction in unit of degree
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
In the PLC CPU unit parameter "Output at error stop", the setting for QD75 is "Hold".
801 Flash ROM write error Data is not written to the flash ROM.
At start: The system will not operate.
802 Flash ROM sum check error
While data is written to the flash ROM, the power is turned OFF.
803 PLC CPU error The PLC CPU resulted in an error.
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
804 Dedicated instruction error
Data is written to the flash ROM continuously 25 times or more from the sequence program.
805 Flash ROM write number error
At start: The system will not operate.
806 Dedicated instruction I/F error
Mismatching occurs between the PLC CPU and QD75.

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
ABS setting direction in the
1550 1650 1750 1850
18 19 168 169 318 319 468 469
Invalidate the software stroke limit. (To invalidate, set the software stroke limit upper limit value to the software stroke limit lower limit value.) (Refer to Section 9.1.5)
20 21 170 171 320 321 470 471
Clear the setting of the PLC CPU module parameter "Output at error stop". (Refer to "QCPU User’s Manual")
—
The flash ROM is expected to be at the end of its writable life. Replace the flash ROM with a new one.
—
1901
Return the parameter to that set at the time of delivery from the plant. (Refer to Section 13.2)
— (Refer to "QCPU User’s Manual")
0: The current feed value is written to the positioning address. 1: The current feed value is written to the arc address.
—
Review the sequence program so that data is not written continuously to the flash ROM. (Using Md.19 in Section 5.6.1, the number of flash ROM write times can be monitored.) (If this error has occurred in a proper using method, writing is enabled by resetting the error, switching power OFF, then ON, or resetting the PLC CPU.)
—
— A trouble occurs. Repair.

Error code Error name Error Operation status at error occurrence
900 Outside unit setting range
The set range of the basic parameter 1 "Unit setting" is outside the setting range.
901 Outside pulse number per rotation range
The set range of the basic parameter 1 "No. of pulses per rotation" is outside the setting range.
902 Outside movement amount per rotation range
The set range of the basic parameter 1 "Movement amount per rotation" is outside the setting range.
The set range of the basic parameter 1 "Unit magnification" is outside the setting range.
903 Outside unit magnification range
The QD75 READY signal (X0) is not turned ON.
The set range of the basic parameter 1 "Pulse output mode" is outside the setting range.
904 Pulse output mode error
905 Rotation direction setting error
The set range of the basic parameter 1 "Rotation direction setting" is outside the setting range.
906 Outside bias speed range
910 Outside speed limit value range
When the power is turned ON or PLC READY signal (Y0) is turned from OFF to ON:
QD75 READY signal (X0) is not turned ON. At start: The system will not operate.
The set range of the basic parameter 2 "Acceleration time 0" is outside the setting range.
911 Outside acceleration time 0 range
The set range of the basic parameter 2 "Deceleration time 0" is outside the setting range.
912 Outside deceleration time 0 range
920 Backlash compensation amount error
The value converted into pulse number using the movement amount per pulse is 256 pulses or more.
The QD75 READY signal (X0) is not turned ON.
921 Software stroke limit upper limit
Classification · of errors · Parameter

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
0 150 300 450 0, 1, 2, 3
1 151 301 451 1 to 65535
2 152 302 452 1 to 65535
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
3 153 303 453 1, 10, 100, 1000
4 154 304 454 0, 1, 2, 3
5 155 305 455 0, 1
Set the bias speed to not more than the speed limit value. With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
6 7 156 157 306 307 456 457 0 to 1000000 [pulse/s] 0 to 2000000000 [mm/min or others]
QD75P : 1 to 200000 [pulse/s] 1 to 2000000000 [mm/min or another] QD75D : 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
10 11 160 161 310 311 460 461
12 13 162 163 312 313 462 463 1 to 8388608
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
14 15 164 165 314 315 464 465 1 to 8388608
17 167 317 467 0 to 255 Set the value converted into the pulse number using "the movement amount per pulse" to less than 256 pulses. (Refer to Section 12.3.1)
18 19 168 169 318 319 468 469
Related buffer memory · address

Error code Error name Error Operation status at error
922 Software stroke limit lower limit
The set range of the detailed parameter 1 "Software stroke limit selection" is outside the setting range.
923 Software stroke limit selection
The set range of the detailed parameter 1 "Software stroke limit valid/invalid setting" is outside the setting range.
924 Software stroke limit valid/invalid setting
The set range of the detailed parameter 1 "Command in-position width" is outside the setting range.
925 Command in-position width
926 Illegal torque limit setting value
The set range of the detailed parameter 1 "Torque limit setting value" is outside the setting range.
The set range of the detailed parameter 1 "M code ON signal output timing" is outside the setting range.
927 M code ON timing error
The QD75 READY signal (X0) is not turned ON.
The set range of the detailed parameter 1 "Speed changeover mode" is outside the setting range.
928 Speed changeover mode error
929 Interpolation speed designation method error
The set range of the detailed parameter 1 "Interpolation speed designation method" is outside the setting range.
The set range of the detailed parameter 1 "Current feed value during speed control" is outside the setting range.
930 Current value update request error
932 Manual pulse generator input mode error
The set range of the detailed parameter 1 "Manual pulse generator input selection" is outside the setting range.
The detailed parameter 1 "speed- position function selection" is preset to 2 and the following three conditions are not satisfied: 1) Unit is "degree". 2) Software stroke limits are invalid. 3) Update current feed value.
935 Speed-position function selection error
950 Acceleration time 1 setting error
The set range of the detailed parameter 2 "Acceleration time 1" is outside the setting range.
operate. During operation:
The set range of the detailed parameter 2 "Acceleration time 2" is outside the setting range.
951 Acceleration time 2 setting error
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
The set range of the detailed parameter 2 "Acceleration time 3" is outside the setting range.
952 Acceleration time 3 setting error
The set range of the detailed parameter 2 "Deceleration time 1" is outside the setting range.
953 Deceleration time 1 setting error

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
20 21 170 171 320 321 470 471
22 172 322 472 0, 1
23 173 323 473 0, 1
24 25 174 175 324 325 474 475 1 to 2147483647
26 176 326 476 1 to 500
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
27 177 327 477 0, 1
28 178 328 478 0, 1
29 179 329 479 0, 1
30 180 330 480 0, 1, 2
33 0, 1, 2, 3
Speed-position switching control (ABS mode) should satisfy the conditions 1) to 3) given on the left. When speed-position switching control (ABS mode) is not to be exercised, set 0 to speed-position function selection and turn the PLC READY signal (Y0) from OFF to ON.
34 184 334 484 0, 2
36 37 186 187 336 337 486 487 1 to 8388608
38 39 188 189 338 339 488 489 1 to 8388608
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
40 41 190 191 340 341 490 491 1 to 8388608
42 43 192 193 342 343 492 493 1 to 8388608
Related buffer memory · address

Error code Error name Error Operation status at error occurrence
954 Deceleration time 2 setting error
The set range of the detailed parameter 2 "Deceleration time 2" is outside the setting range.
The set range of the detailed parameter 2 "Deceleration time 3" is outside the setting range.
955 Deceleration time 3 setting error
956 JOG speed limit value error
957 JOG acceleration time selection setting error
The set range of the detailed parameter 2 "JOG acceleration time selection setting" is outside the setting range.
958 JOG deceleration time selection setting error
The set range of the detailed parameter 2 "JOG deceleration time selection setting" is outside the setting range.
Acceleration/ deceleration process selection setting error
The set range of the detailed parameter 2 "Acceleration/deceleration process selection setting" is outside the setting range.
operate. During operation:
The system stops with the setting (deceleration stop/sudden stop) of the detailed parameter 2 Sudden stop selection (stop group 3). (Note that the deceleration stop only occurs during the manual pulse generator operation.)
The set range of the detailed parameter 2 "S-pattern ratio" is outside the setting range.
960 S-pattern ratio setting error
The set range of the detailed parameter 2 "Sudden stop deceleration time" is outside the setting range.
961 Illegal sudden stop deceleration time
The set range of the detailed parameter 2 "Stop group 1 sudden stop selection" is outside the setting range.
962 Stop group 1 sudden stop selection error
The set range of the detailed parameter 2 "Stop group 2 sudden stop selection" is outside the setting range.
963 Stop group 2 sudden stop selection error
The set range of the detailed parameter 2 "Stop group 3 sudden stop selection" is outside the setting range.
964 Stop group 3 sudden stop selection error
The set range of the detailed parameter 2 "Allowance circular interpolation error width" is outside the setting range.
966 Outside allowance circular interpolation error width
The set range of the detailed parameter 2 "External command function selection" is outside the setting range.
967 External command function selection error
The set range of the OPR basic parameter "OPR method" is outside the setting range.
The QD75 READY signal (X0) is not turned ON.
980 OPR method error
Classification · of errors · Parameter

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
44 45 194 195 344 345 494 495 1 to 8388608
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
46 47 196 197 346 347 496 497 1 to 8388608
QD75P : 1 to 200000 [pulse/s] 1 to 2000000000 [mm/min or another] QD75D : 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
48 49 198 199 348 349 498 499
50 200 350 500 0, 1, 2, 3
51 201 351 501 0, 1, 2, 3
52 202 352 502 0, 1
53 203 353 503 1 to 100
54 55 204 205 354 355 504 505 1 to 8388608
56 206 356 506 0, 1
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
57 207 357 507 0, 1
58 208 358 508 0, 1
60 61 210 211 360 361 510 511 0 to 10000
62 212 362 512 0, 1, 2, 3
70 220 370 520 0, 1, 2, 3, 4, 5
Related buffer memory · address

Error code Error name Error Operation status at error occurrence
The set range of the OPR basic parameter "OPR direction" is outside the setting range.
981 OPR direction error
The set range of the OPR basic parameter "OP address" is outside the setting range.
982 OP address setting error
983 OPR speed error
984 Creep speed error
The set range of the OPR basic parameter "OPR retry" is outside the setting range.
985 OPR retry error
The set range of the OPR detailed parameter "OPR dwell time" is outside the setting range.
990 OPR dwell time error
The QD75 READY signal (X0) is not turned ON.
Setting for the movement amount after near-point dog ON error
The set range of the OPR detailed parameter "Setting for the movement amount after near-point dog ON" is outside the setting range.
The set range of the OPR detailed parameter "OPR acceleration time selection" is outside the setting range.
992 OPR acceleration time selection error
The set range of the OPR detailed parameter "OPR deceleration time selection" is outside the setting range.
993 OPR deceleration time selection error
995 OPR torque limit value error
The set range of the OPR detailed parameter "Deviation counter clear signal output time" is outside the setting range.
996 Deviation counter clear signal output time setting error
The set range of the OPR detailed parameter "Speed designation during OP shift" is outside the setting range.
997 Speed designation during OP shift error
Classification · of errors · Parameter

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
71 221 371 521 0, 1
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
72 73 222 223 372 373 522 523
74 75 224 225 374 375 524 525 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or others]
76 77 226 227 376 377 526 527 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or others]
78 228 378 528 0, 1
79 229 379 529 0 to 65535
80 81 230 231 380 381 530 531 0 to 2147483647
82 232 382 532 0, 1, 2, 3
83 233 383 533 0, 1, 2, 3
With the setting brought into the setting range, turn the PLC READY signal [Y0] from OFF to ON.
86 236 386 536 1 to 300
87 237 387 537 1 to 65535
88 238 388 538 0, 1
Related buffer memory · address

The following table shows the warning details and remedies to be taken when a warning occurs.
code Warning name Warning Operation status at warning
— 000 (Normal status) — —
100 Start during operation
The start request is issued while the axis is BUSY. Continue the operation.
102 Deviation counter clear request
The deviation counter clear request is issued while the axis is BUSY.
The deviation counter clear request is ignored.
The restart command is issued when the axis operation status is not "Stopped".
104 Restart not possible
Continue the operation.
The warning is issued for the axis designated at the time of the teaching request.
109 Teaching in BUSY The teaching request is issued while the axis is BUSY.
110 Less than minimum speed The overridden speed becomes “0”. The system is controlled with the currently executing unit of 1.
The request for writing to the flash ROM is issued when the PLC READY is turned ON (at the time of teaching request).
111 In PLC READY
The warning for axis 1 is issued.
112 Illegal override value
A value other than 1 to 300 is set for the override value.
113 Outside new torque value range
A value other than 1 to 500 is set for the new torque value. The torque change is not carried out.
114 Below bias speed The command speed is below the bias speed at start. Operate by the bias speed at start.
The speed change request is issued during deceleration stop with JOG start signal OFF.
300 Speed change during deceleration
The speed change is not carried out.
The new speed value exceeds the JOG speed limit value when the speed is changed during operation.
301 JOG speed limit value

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
—
— Normalize the start request ON timing.
— Do not carry out the deviation counter clear while the axis is running. (Refer to Chapter 8)
Normalize the start request ON timing. (Do not issue the restart command when the axis operation is not stopped.)
1503 1603 1703 1803
1548 1549 1648 1649 1748 1749 1848 1849
0, 1
Carry out the teaching request when the axis is not BUSY. (Refer to Section 12.7.4)
1513 1613 1713 1813
Prevent the overridden speed from being reduced to 0. (Refer to Section 12.5.2)
Same as warning code 109 None (If the PLC READY signal (Y0) is turned OFF, respond to the teaching write request).
1513 1613 1713 1813
Set a value within the setting range.
1525 1625 1725 1825 1 to [Torque limit set value]
26 176 326 476
Refer to Section 5.3 "List of positioning data"
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
Re-set the command speed/bias speed at start so that the command speed is equal to or larger than the bias speed at start.
Bias speed at start
0 to 1000000 [pulse/s] 0 to 2000000000 [mm/min or another]
6 7 156 157 306 307 456 457
1516 1616 1716 1816 1: Speed change is requested Do not carry out the JOG speed change during deceleration with the JOG start signal OFF.
0 to 1000000 [pulse/s] 0 to 2000000000 [mm/min or another]
1514 1515 1614 1615 1714 1715 1814 1815
JOG speed limit value
QD75P : 1 to 200000 [pulse/s] 1 to 2000000000 [mm/min or another] QD75D : 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
Bring the set value into the setting range.
48 49 198 199 348 349 498 499

code Warning name Warning Operation status at warning
Outside manual pulse generator input magnification range
The manual pulse generator 1 pulse input magnification is set at 0 or 101 or higher.
500 Deceleration/stop speed change
The speed change request is issued during deceleration stop. The speed change is not carried out.
The new value exceeds the speed limit value when the speed is changed during operation.
501 Speed limit value over
The M code ON signal is turned ON when the positioning data is executed.
503 M code ON signal ON start
Continue executing the positioning data.
505 No operation termination setting
In the positioning by block starting, the 50th point of the positioning start data is set to CONTINUE.
The operation is terminated.
506 FOR to NEXT nest construction FOR to NEXT is nested.
Speed-position switching (during acceleration) signal ON
The switching signal for speed- position switching control (INC mode) is turned ON during acceleration.
The operation is continued.
509 Insufficient remaining distance
Code 1 is set for the step start information when the step is outside standby.
511 Step not possible
The step will not start.
The detailed parameter 2 "External command function selection" setting range is exceeded.
Even if the external command signal is turned ON, the system will not perform anything.
512 Illegal external command function
513 Insufficient movement amount
The movement amount is not large enough for automatic deceleration.
The system stops immediately after it reaches the positioning address.

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
1522 1523 1622 1623 1722 1723 1822 1823
Set the manual pulse generator 1 pulse input magnification to within the setting range.
Do not carry out the speed change during deceleration with a stop command, during stoppage, or during automatic deceleration with position control.
1516 1616 1716 1816 1: Speed change is requested
0 to 1000000 [pulse/s] 0 to 2000000000 [mm/min or another]
1514 1515 1614 1615 1714 1715 1814 1815
QD75P : 1 to 200000 [pulse/s] 1 to 2000000000 [mm/min or another] QD75D : 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
Set the new speed value to a range of 0 to "speed limit value".
10 11 160 161 310 311 460 461
1504 1604 1704 1804 1: M code ON signal is turned OFF Normalize the ON and OFF timings of the "M code OFF request". (Refer to Section 12.7.3)
Refer to Section 5.3 "List of positioning data"
Set the operation termination to the 50th point. (Refer to Chapter 10)
— Make 1 nest construction for FOR to NEXT. (Refer to Section 10.3.8)
Do not turn ON the speed-position switching signal during acceleration. (Refer to Section 9.2.16)
—
— Give a request at the position where there is an enough remaining distance.
1546 1646 1746 1846
Do not set a "1" to the step start information when the step is not in standby state. (Refer to Section 12.7.1)
62 212 362 512
Set the detailed parameter 2 "External command function selection" to within the setting range.
0, 1, 2, 3
Refer to Section 5.3 "List of positioning data" — Set a decelerating address or a movement amount to the positioning data.

code Warning name Warning Operation status at warning
514 Outside command speed range
The command speed exceeds the speed limit.
Teaching is not carried out when the set value is 0 or 601 or more. (A "0" is canceled by the QD75 automatically even when a "0" or "601" or more is set.)
516 Illegal teaching data No.
The positioning data No. is set outside the setting range.
517 Illegal teaching data selection
The teaching data selection set value is outside the setting range. Teaching is not carried out.
518 Target position change not possible
The target position change is not carried out.

Set range (Setting with sequence program) Remedy
Axis 1 Axis 2 Axis 3 Axis 4
refer to Section 5.3 "List of positioning data"
1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
QD75P : 1 to 200000 [pulse/s] 1 to 2000000000 [mm/min or another] QD75D : 1 to 1000000 [pulse/s] 1 to 2000000000 [mm/min or another]
Set the command speed to within the setting range.
10 11 160 161 310 311 460 461
1549 1649 1749 1849
1 to 600 Set the positioning data No. to within the setting range.
1548 1648 1748 1848
0, 1 Set the teaching data selection set value to within the setting range.
1538 1638 1738 1838

The states of QD75 and each axis control can be confirmed by the LEDs located on the front panel of the QD75 main unit.

Each axis can be monitored by the states of the LEDs. The operation and indications of the LEDs are as shown below.
AX1 AX2 AX3 AX4
The hardware is faulty or watch dog timer error occurs.
If the RUN LED does not light up even when the power is turned ON, the module may be out of order. Replace the module with a new one.
Extinguishment of RUN LED
RUN
AX1 AX2 AX3 AX4
Lighting of RUN LED, Extinguishment of ERR LED
The module is normal. —
An operation condition setting error or installation PLC CPU type error occurs. (The setting and PLC CPU type are outside the specification range.) Set the PLC CPU type to a one contained in the specification. RUN
AX1 AX2 AX3 AX4
Lighting of ERR LED System error
AX1 AX2 AX3 AX4
Extinguishment of AX1 to AX4 LEDs
During axis stop, during axis standby —
RUN
AX1 AX2 AX3 AX4
This lights up from the positioning start until the positioning is completed, stopped temporarily, or stopped by error (corresponding at a ratio of 1 : 1 to BUSY signals).
Lighting of AX1 (Same even if the other axis is lit)
RUN
AX1 AX2 AX3 AX4
Flashing of ERR LED Flashing of AX1 LED (Same even if the other axis flashes)
Check the error observed on the buffer memory batch processing monitor of a peripheral device and correct the applicable parameters and positioning data.
RUN
AX1 AX2 AX3 AX4
Lighting of all LEDs The hardware is faulty
The module comes out of order. Replace the module with a new one.

Appendix 1 Version up of the functions Appendix- 2
Appendix 1.1 Comparison of functions according to function versions Appendix- 2 Appendix 2 Format sheets Appendix- 4
Appendix 2.1 Positioning Module operation chart Appendix- 4 Appendix 2.2 Parameter setting value entry table Appendix- 6 Appendix 2.3 Positioning data setting value entry table Appendix- 12 Appendix 3 Positioning data (No. 1 to 600) List of buffer memory addresses Appendix- 13 Appendix 4 Connection examples with servo amplifiers manufactured by MITSUBISHI Electric Corporation Appendix- 37
Appendix 4.1 Connection example of QD75D and MR-H A (Differential driver) Appendix- 37 Appendix 4.2 Connection example of QD75D and MR-J2/J2S- A (Differential driver) Appendix- 38 Appendix 4.3 Connection example of QD75D and MR-C A (Differential driver) Appendix- 39 Appendix 5 Connection examples with stepping motors manufactured by ORIENTALMOTOR Co., Ltd Appendix- 40
Appendix 5.1 Connection example of QD75P and VEXTA UPD (Open collector) Appendix- 40 Appendix 6 Connection examples with servo amplifiers manufactured by Matsushita Electric Industrial Co., Ltd Appendix- 41
Appendix 6.1 Connection example of QD75D and MINAS-A series (Differential driver) Appendix- 41 Appendix 7 Connection examples with servo amplifiers manufactured by SANYO DENKI Co., Ltd Appendix- 42
Appendix 7.1 Connection example of QD75D and PYO series (Differential driver) Appendix- 42 Appendix 8 Connection examples with servo amplifiers manufactured by YASKAWA Electric Corporation Appendix- 43
Appendix 8.1 Connection example of QD75D and ∑- series (Differential driver) Appendix- 43 Appendix 9 Comparisons with conventional positioning modules Appendix- 44
Appendix 9.1 Comparisons with A1SD71S2 model Appendix- 44 Appendix 9.2 Comparisons with A1SD75P1-S3/A1SD75P2-S3/ A1SD75P3-S3
models Appendix- 45 Appendix 10 MELSEC Explanation of positioning terms Appendix- 68 Appendix 11 Positioning control troubleshooting Appendix- 92 Appendix 12 List of buffer memory addresses Appendix- 98 Appendix 13 External dimension drawing Appendix- 107
Appen- dices · Appendix - 1

Appendix 1.1 Comparison of functions according to function versions
The following tables list the QD75P1/QD75P2/QD75P4/QD75D1/QD75D2/QD75D4 functions compared according to function versions and the buffer memory for their additional functions. (1) Function comparison


Axis 1 Axis 2 Axis 3 Axis 4 Name Used function

Appendix - 2

MEMO
Appendix - 3

Appendix 2.1 Positioning Module operation chart
mm, inch, degree, pulse
Axis address mm, inch, degree, pulse
Axis address · Appendix - 4

mm, inch, degree, pulse
Axis address mm, inch, degree, pulse
Axis address · Appendix - 5

mm inch degree pulse
Pr.1 Unit setting 0 1 2 3
Pr.2 No. of pulses per rotation (Ap) 1 to 65535 pulse
Pr.3 Movement amount per rotation (Al)
1 to 65535 × 10-1µm
1 to 65535 × 10-5inch
1 to 65535 × 10-5degree
1 to 65535 pulse
Pr.5 Pulse output mode 0: PULSE/SIGN mode, 1: CW/CCW mode, 2: A phase/B phase (multiple of 4), 3: A phase/B phase (multiple of 1)
Pr.6 Rotation direction setting 0: Current value increment with forward run pulse output 1: Current value increment with reverse run pulse output
Pr.7 Bias speed at start 0 to 2000000000 × 10-2mm/min
0 to 2000000000 × 10-3inch/min
0 to 2000000000 × 10-3degree/min
0 to 1000000 pulse/s
1 to 1000000/ 1 to 200000 pulse
Pr.8 Speed limit value 1 to 2000000000 × 10-2mm/min
1 to 2000000000 × 10-3mm/min
1 to 2000000000 ×10-3degree/min
Pr.9 Acceleration time 0
Pr.10 Deceleration time 0
Pr.11 Backlash compensation amount 0 to 65535 × 10-1µm
0 to 65535 × 10-5inch
0 to 65535 × 10-5degree
0 to 65535 pulse
Pr.12 Software stroke limit upper limit value
–2147483648 to 2147483647 × 10-1µm
–2147483648 to 2147483647 × 10-5inch
0 to 35999999 × 10-5degree
–2147483648 to 2147483647 pulse
Pr.13 Software stroke limit lower limit value
Pr.14 Software stroke limit selection 0: Apply software stroke limit on current feed value 1: Apply software stroke limit on machine feed value
Pr.15 Software stroke limit valid/invalid selection
Pr.16 Command in-position width 1 to 2147483647 × 10-1µm
1 to 2147483647 × 10-5inch
1 to 2147483647 × 10-5degree
1 to 2147483647 pulse
Pr.17 Torque limit setting value 1 to 500%
Pr.18 M code ON signal output timing 0: WITH mode, 1: AFTER mode
Pr.20 Interpolation speed designation method 0: Composite speed, 1: Reference axis speed
Pr.21 Current feed value during speed control
: "1 to 1000000" for QD75D and "1 to 200000" for QD75P when the unit is "pulse".


Initial value Axis 1 Axis 2 Axis 3 Axis 4 Remarks
Appendix - 7

mm inch degree pulse
b0 Lower limit b3 Stop signal b6 Near-point signal
b7, b9 to b15 Unused Pr.22 Input signal logic selection
b1 Upper limit b4 External
Setting of each bit value 0: Negative logic 1: Positive logic ("0" is set for unused bit.)
b2 Drive unit READY b5 Zero signal b8 Manual pulse generator input
b0 Command pulse signal b2 Unused b4 Deviation counter clear Pr.23 Output signal logic selection
b1 Unused b3 Unused b5 to b15 Unused
Pr.24 Manual pulse generator input selection
Pr.150 Speed -position function
Pr.25 Acceleration time 1
Pr.26 Acceleration time 2
Pr.27 Acceleration time 3
Pr.28 Deceleration time 1
Pr.29 Deceleration time 2
Pr.30 Deceleration time 3
1 to 2000000000 × 10-2mm/min
1 to 1000000/ 1 to 200000 pulse
1 to 2000000000 × 10-3inch/min
1 to 2000000000 ×10-3degree/min
Pr.31 JOG speed limit value
Pr.32 JOG operation acceleration time selection
Pr.33 JOG operation deceleration time selection
Pr.34 Acceleration/deceleration process selection
Pr.35 S-pattern proportion 1 to 100%
Pr.36 Sudden stop deceleration time 1 to 8388608ms
Pr.37 Stop group 1 sudden stop selection
Pr.38 Stop group 2 sudden stop selection
Pr.39 Stop group 3 sudden stop selection
Pr.40 Positioning complete signal output time 0 to 65535ms
Pr.41 Allowable circular interpolation error width
1 to 100000 × 10-1µm
1 to 100000 × 10-5inch
1 to 100000 × 10-5degree
1 to 100000 pulse
Pr.42 External command function selection
: "1 to 1000000" for QD75D and "1 to 200000" for QD75P when the unit is "pulse".


Initial value Axis 1 Axis 2 Axis 3 Axis 4 Remarks
Appendix - 9

mm inch degree pulse
Pr.43 OPR method
–2147483648 to 2147483647 × 10-1µm
–2147483648 to 2147483647 × 10-5inch
0 to 35999999 × 10-5degree
–2147483648 to 2147483647 pulse/s
Pr.45 OP address
Pr.46 OPR speed
1 to 2000000000 × 10-2mm/min
1 to 2000000000 × 10-3inch/min
1 to 2000000000 ×10-3degree/min
1 to 1000000 pulse/s
Pr.47 Creep speed
Pr.48 OPR retry 0: Do not retry OPR with upper/lower limit switch 1: Retry OPR with upper/lower limit switch
Pr.49 OPR dwell time 0 to 65535ms
0 to 2147483647 × 10-1µm
0 to 2147483647 × 10-5inch
0 to 2147483647 × 10-5degree
Pr.50 Setting for the movement amount after near-point dog ON
0 to 2147483647 pulse
Pr.51 OPR acceleration time selection
Pr.52 OPR deceleration time selection
–2147483648 to 2147483647 × 10-1µm
–2147483648 to 2147483647 × 10-5inch
0 to 35999999 × 10-5degree
–2147483648 to 2147483647 pulse
Pr.53 OP shift amount
Pr.54 OPR torque limit value 0 to 300%
Pr.55 Deviation counter clear signal output time 1 to 65535ms
Pr.56 Speed designation during OP shift 0: OPR speed 1: Creep speed
Pr.57 Dwell time during OPR retry 0 to 65535ms


Initial value Axis 1 Axis 2 Axis 3 Axis 4 Remarks
Appendix - 11
![Page 654 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — Appendix 2.3 Positioning data setting value entry table [data No. to ]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-654.webp?w=400)
![Mitsubishi Electronics MELSEC-Q QD75D — Appendix 2.3 Positioning data setting value entry table [data No. to ] diagram (page 654)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-654-1.webp)
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
Appendix - 12

List of buffer memory addresses
(1) For axis 1

2509 2519 2529 539 2549 6 7 8 9 10
Appendix - 13


Appendix - 14


Appendix - 15


Appendix - 16


Appendix - 17


Appendix - 18


Appendix - 19


Appendix - 20


Appendix - 21


Appendix - 22


Appendix - 23


Appendix - 24


Appendix - 25


Appendix - 26


Appendix - 27


Appendix - 28


Appendix - 29


Appendix - 30


Appendix - 31


Appendix - 32


Appendix - 33


Appendix - 34


Appendix - 35


Appendix - 36

Electric Corporation
Appendix 4.1 Connection example of QD75D and MR-H A (Differential driver) 6

Configure a sequence to turn OFF the MC at alarms and emergency stops.
Near-point dog Upper limit 2 Lower limit 2 Stop External command
DOG 3 FLS 1 RLS 2 STOP 4 CHG 5
Servo ON Reset Torque limit Forward run stroke end Reverse run stroke end 3 3
When connecting an open collector, make connection as shown below.
15 16 PULSE F PULSE COM PULSE R PULSE COM
(1) It is recommended to make differential driver connection since differential driver connection is more excellent than
open collector connection in max. output pulse and max. connection distance between servos. (Refer to Section 3.1 "Performance specifications".) (2) 1: The logic for each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output
signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (3) 2: The QD75D upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals inside the servo amplifier limit switches. (4) 3: These are limit switches for the servo (for stop). (5) 4: Refer to the specification and handling instruction manual of the servo amplifier MR-H for details on connection. (6) 5: This indicates the distance between the QD75D and servo amplifier. (7) 6: Use the same logic (positive logic/negative logic) for the QD75D and servo amplifier. The QD75D is initially set to negative logic.
Appendix - 37

Configure a sequence to turn OFF the MC at alarms and emergency stops.
HC-MF, HA-FF series motor

OPC PP PG NP NG CR SG RD COM
11 3 13 2 12 8 10 19 9
PULSE F+ 15 PULSE F- 16 PULSE R+ 17 PULSE R- 18 CLEAR 13 CLEAR COM 14 READY 11 RDY COM 12
PG05 9 PG0 COM 10 COM 6 COM 7
Commercially available personal computer
Near-point dog Upper limit 2 Lower limit 2 Stop External command
EMG 15 SON RES PC TL LSP LSN SG SG VDD COM ALM ZSP TLC
RLS STOP CHG PULSER A+ PULSER A- PULSER B+ PULSER B-
5 14 8 9 16 17 10 20 3 13 18 19 6
4 MO1 3 LG 14 MO2 13 LG Plate SD
When connecting an open collector, make connection as shown below.
15 16 PULSE F PULSE COM PULSE R PULSE COM
(1) It is recommended to make differential driver connection since differential driver connection is more excellent than
open collector connection in max. output pulse and max. connection distance between servos. (Refer to Section 3.1 "Performance specifications".) (2) 1: The logic for each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output
signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (3) 2: The QD75D upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals inside the servo amplifier limit switches. (4) 3: These are limit switches for the servo amplifier (for stop). (5) 4: This indicates the distance between the QD75D and servo amplifier. (6) 5: Use the same logic (positive logic/negative logic) for the QD75D and servo amplifier. The QD75D is initially set to negative logic.
Appendix - 38


Configure a sequence to turn OFF the MC at alarms and emergency stops.
Power supply Single-phase 200VAC (A type) or single-phase 100VAC (A1 type)
PULSE F+ 15 PULSE F- 16 PULSE R+ 17 PULSE R- 18 CLEAR 13 CLEAR COM 14 PG024 8 PG0 COM 10
PP PG NP NG CR SG V+ OP SD
9 10 7 8 13 12 1 4 11
Near-point dog Upper limit Lower limit Stop External command
When connecting an open collector, make connection as shown below.
15 16 PULSE F PULSE COM PULSE R PULSE COM
(1) It is recommended to make differential driver connection since differential driver connection is more excellent than
open collector connection in max. output pulse and max. connection distance between servos. (Refer to Section 3.1 "Performance specifications".) (2) 1: The logic for each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output
signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (3) 2: The QD75D upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals inside the servo amplifier limit switches. (4) 3: These are limit switches for the servo amplifier (for stop). (5) 4: This indicates the distance between the QD75D and servo amplifier. (6) 5: Use the same logic (positive logic/negative logic) for the QD75D and servo amplifier. The QD75D is initially set to negative logic.
Appendix - 39

ORIENTALMOTOR Co., Ltd.

PULSE F PULSE COM PULSE R PULSE COM PGO24 PGO COM READY
RDY COM PULSER A+ PULSER A- PULSER B+ PULSER B-
12 A19 B19 A20 B20 DOG FLS RLS STOP CHG
Near-point dog Upper limit 2 Lower limit 2 Stop External command
(1) 1: The logic for each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output
signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (2) 2: The QD75P upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. (3) 3: Refer to the manual of the stepping motor drive for information on the stepping motor drive side wiring and various signal wire shields not shown above. (4) 4: Use the same logic (positive logic/negative logic) for the QD75P and stepping motor. The QD75P is initially set to negative logic. (5) 5: This indicates the distance between the QD75P and VEXTA UPD.
Appendix - 40

Industrial Co., Ltd.

Near-point dog Upper limit 2 Lower limit 2 Stop External command
(1) 1: The logic for each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output
signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (2) 2: The QD75D upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals inside the servo amplifier limit switches. (3) 3: Refer to the manual of the servo amplifier for information on the servo amplifier side wiring and various signal wire shields not shown above. (4) 4: Use the same logic (positive logic/negative logic) for the QD75D and servo amplifier. The QD75D is initially set to negative logic. (5) 5: This indicates the distance between the QD75D and MINAS-A.
Appendix - 41

Co., Ltd.

25 11 41 49 SON PROT 37 32 33
Near-point dog Upper limit 2 Lower limit 2 Stop External command
Differential driver common terminal
(1) 1: The logic for each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output
signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (2) 2: The QD75D upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals inside the servo amplifier limit switches. (3) 3: Refer to the manual of the servo amplifier for information on the servo amplifier side wiring and various signal wire shields not shown above. (4) 4: Use the same logic (positive logic/negative logic) for the QD75D and servo amplifier. The QD75D is initially set to negative logic. (5) 5: This indicates the distance between the QD75D and PYO.
Appendix - 42

Corporation
Appendix 8.1 Connection example of QD75D and ∑- series (Differential driver) 4

20 29 30 15 CLR PL3 18 40 42
Near-point dog Upper limit 2 Lower limit 2 Stop External command
(1) 1: The logic of each I/O terminal can be changed with " Pr.22 Input signal logic selection" and " Pr.23 Output signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.) (2) 2: The QD75D upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals inside the servo amplifier limit switches. (3) 3: Refer to the manual of the servo amplifier for information on the servo amplifier side wiring and various signal wire shields not shown above. (4) 4: Use the same logic (positive logic/negative logic) for the QD75D and servo amplifier. The QD75D is initially set to negative logic. (5) 5: This indicates the distance between the QD75D and ∑- .
Appendix - 43

Appendix 9.1 Comparisons with A1SD71S2 model
The following shows comparisons with the conventional positioning module A1SD71S2, centered on the QD75 specifications.

Speed-position switching control (INC/ABS mode) (Only INC mode) Positioning systems
Machine OPR function (OPR method) (6 types) (3 types)
History data storage (Start, error, warning) Provided (3 types, 16 items/axis) None
Appendix - 44

The following shows the comparisons between the QD75 and the conventional positioning modules A1SD75P1-S3/A1SD75P2-S3/A1SD75P3-S3.
QD75P2 QD75D2
QD75P4 QD75D4
A1SD75P1
A1SD75P2
A1SD75P3
-S3
-S3
-S3
No. of control axes 1 2 4 1 2 3
No. of positioning data items 600/axis 600/axis 1
Position control interpolation functions
-214748364.8 to 214748364.7 ( m) -21474.83648 to 21474.83647 (inch) 0 to 359.99999 (degree) -2147483648 to 2147483647 (pulse)
-214748364.8 to 214748364.7 ( m) /-13421772.8 to 13421772.7 ( m) -21474.83648 to 21474.83647 (inch)
/-1342.17728 to 1342.17727 (inch) 0 to 359.99999 (degree) /0 to 359.99999 (degree) -2147483648 to 2147483647 (pulse)
-214748364.8 to 214748364.7 ( m) -21474.83648 to 21474.83647 (inch) -21474.83648 to 21474.83647 (degree) -2147483648 to 2147483647 (pulse)
/-134217728 to 134217727 (pulse)
-214748364.8 to 214748364.7 ( m) /-13421772.8 to 13421772.7 ( m) -21474.83648 to 21474.83647 (inch)
0 to 214748364.7 ( m) 0 to 21474.83647 (inch) 0 to 21474.83647 (degree)/ 0 to 359.99999 (degree) 3 0 to 2147483647 (pulse)
/-1342.17728 to 1342.17727 (inch) -21474.83648 to 21474.83647 (degree)
/-1342.17728 to 1342.17727 (degree) -2147483648 to 2147483647 (pulse)
/-134217728 to 134217727 (pulse)
0 to 214748364.7 ( m) /0 to 13421772.7 ( m) 0 to 21474.83647 (inch) /0 to 1342.17727 (inch) 0 to 21474.83647 (degree) /0 to 1342.17727 (degree) 0 to 2147483647 (pulse) /0 to 134217727 (pulse)

QD75P2 QD75D2
QD75P4 QD75D4
A1SD75P1
A1SD75P2
A1SD75P3
-S3
-S3
-S3
0.01 to 20000000.00 (mm/min) 0.001 to 2000000.000 (inch/min) 0.001 to 2000000.000 (degree/min) 1 to 1000000 (pulse/s)
0.01 to 6000000.00 (mm/min) /0.01 to 375000.00 (mm/min) 0.001 to 600000.000 (inch/min) /0.001 to 37500.000 (inch/min) 0.001 to 600000.000 (degree/min) /0.001 to 37500.000 (degree/min) 1 to 1000000 (pulse/s) /1 to 62500 (pulse/s)
Speed command range 2
Machine OPR function (OPR method) (6 types) 4 (6 types)
Manual pulse generator function 1 generator/module 1 generator/axis
Automatic trapezoidal acceleration /deceleration Acceleration /deceleration processing S-pattern acceleration /deceleration
No. of patterns Acceleration time and deceleration time can
Acceleration time and deceleration time can
be set independently. (4 patterns each) Acceleration/deceler ation time
be set independently. (4 patterns each)
Setting range 1 to 8388608ms 1 to 65535ms/1 to 8388608ms selectable
Compensation Electronic gears, backlash compensation,
near pass 5 Electronic gears, backlash compensation,
near pass 5 Error display Error LED 17-segment LED History data storage (Start, error, warning) Provided (3 types, 16 items/axis) Provided (4 types, 16 items/axis) Data storage destination Flash ROM (battery-less backup) Flash ROM (battery-less backup) A6CON1 (Soldering type, sold separately) 10136-3000VE (Soldering type, supplied) A6CON2 (Crimp type, sold separately) 10136-6000EL (Crimp type, sold separately) Connection connector A6CON4 (Soldering type, usable for straight out and diagonal out, sold separately)
Both differential driver and open collector available
Max. output pulse
Max. connection distance between servos
0.46A QD75P4:
0.58A Internal current consumption (A) [5VDC] QD75D1:
0.7A or less
0.56A QD75D4:
0.82A
Flash ROM write count Max. 100000 times Max. 100000 times No. of occupied I/O points 32 32 No. of module occupied slots 1 1 Outline dimensions (mm (inch)) 98(3.86)(H)×27.4(1.08)(W)×90(3.55)(D) 130(5.12)(H)×34.5(1.36)(W)×93.6(3.69)(D) Weight (kg (lb)) 0.15 (0.33) 0.15 (0.33) 0.16 (0.35) 0.35 (0.77)


External command signal (External start or speed-position switching selectable with parameters)
Connection via PLC CPU, Q Corresponding Serial Communication Module, Q Corresponding MELSEC/H Remote I/O Module
1: Up to 100 data items/axis of positioning data (No. 1 to 100) can be set using the buffer memory. The positioning data in the buffer memory is not backed up. 2: Indicates the standard mode/stepping motor mode about A1SD75P -S3. 3: Indicates the INC mode/ABS mode in speed-position switching control. 4: The deviation counter clear signal output time can be set with parameters. 5: The near pass function is valid only during the continuous path control. (A1SD75: Selected with parameters, QD75: Standard function)
Functions added to those of A1SD75P1-S3/A1SD75P2-S3/A1SD75P3-S3
Added functions Remarks External I/O signal logic switching function Refer to Section 13.4. Inching operation Refer to Section 11.3. Target position change function Refer to Section 12.7.5. Multiple axes simultaneous start control Refer to Section 10.5.
3-axis linear interpolation control 4-axis linear interpolation control 3-axis fixed-feed control 4-axis fixed-feed control 2-axis speed control 3-axis speed control 4-axis speed control Position-speed switching control NOP instruction LOOP instruction, LEND instruction
Refer to Chapter 9.
Absolute position restoration Positioning start Teaching Flash ROM writing Parameter initialization
Refer to Chapter 14.
Automatic refresh of intelligent function modules Refer to GX Configurator-QP Operating Manual.
Output hold/clear parameter setting during PLC CPU error stop Refer to QCPU User's Manual (Function Explanation, Program Fundamentals). Flash ROM write limit Refer to Section 13.3. Speed-position switching control (ABS mode) Refer to Section 9.2.7. Pre-reading start function Refer to Section 12.7.8. External I/O signal monitor function Refer to Section 13.5. Multiple PLC compatible function Refer to QCPU User's Manual (Multiple CPU System). Deceleration start flag function Refer to Section 12.7.9 Stop command processing for deceleration stop function Refer to Section 12.7.10
Control systems · Dedicated instructions · Appendix - 47

Functions deleted from those of A1SD75P1-S3/A1SD75P2-S3/A1SD75P3-S3
Stepping motor mode –
Fast machine OPR –
Special start (stop) –
In the QD75, the start block area on the buffer memory is expanded to five blocks (0 to 4). Each start block can be directly designated with positioning start No. (7000 to 7004).
With the A1SD75, this interface is used to set positioning data Nos. 101 to 600 that do not exist on the buffer memory. Since all positioning data can be set in the buffer memory with the QD75, this function is deleted.
Start history storage during error The contents are the same as those of the start history. Therefore, the QD75 stores only the start history.
These data were deleted because they can be displayed in system monitor "Module's detailed information" of GX Developer. (Refer to GX Developer Operating Manual.)
System monitor data (module type, OS information)
Functions changed from those of A1SD75P1-S3/A1SD75P2-S3/A1SD75P3-S3
Pr.21 .
Software stroke limit function
Current value changing M code function

1. "Peripheral side (emergency) stop" is deleted from the stop causes of Stop group 2 sudden stop selection. "Test mode fault" in the stop causes of Stop group 3 sudden stop selection is changed to be in the stop causes of Stop group 2 sudden stop selection. 2. "Stop (QD75 peripheral)" is added to the stop causes of Stop group 3 sudden stop selection. 3. Error code 100 (Peripheral device stop during operation) is deleted. 4. "PLC CPU error occurrence" is added to the stop causes of Stop group 2 sudden stop selection.
Stop process and restart after stop Positioning operation stop
/WDT error READY signal (X0)
Manual pulse generator operation The No. of connectable manual pulse generator is changed from 1 generator/1 axis to 1 generator/1 module.
"Step stopped" is changed to "Stopped" and "Step error occurring" is changed to "Error occurring". "In position control for position-speed switching control", "In speed control for position-speed switching control", and "In absolute position restoration" are added.
control is internally changed into the continuous positioning control (restart after deceleration stop). QD75: Even if the reference axis operates in reverse direction with
interpolation, the control remains as the continuous path control. (In single-axis operation, the operation is the same as that of the A1SD75.)
Near pass For the continuous path control, only the near pass function is available.
The interpolation target axis can be randomly set with a positioning identifier.
Control unit "degree" handling The operating direction can be designated even for the ABS control in the unit of "degree".

No. 9004 (Multiple axes simultaneous start control) is added. Nos. 7004 to 7010 (block start designation) and 8000 to 8049 (indirect designation) are deleted.
Positioning start No.
Block start data With the QD75, the number of blocks is changed to 5 (7000 to 7004). (With the A1SD75, this data is called "positioning start information".)
Special start data "Simultaneous start" The simultaneous start is possible up to 4 axes.
List of errors/warnings Refer to the following "Error code comparisons" and "Warning code comparisons".
Start history The configuration of "start information" and "start No." is changed so that the start No. can be directly checked.
Synchronization flag (X1) When the PLC CPU starting method is set to asynchronous, interlock is established with the synchronization flag (X1) signal.
Basic parameter 1 " Pr.5 Pulse output mode" When the PLC is turned ON or the PLC CPU module is reset, the valid value is only the first value after the PLC READY signal (Y0) turns from OFF to ON.
Software stroke limits valid for manual operation Detailed parameters " Pr.15 Software stroke limit valid/invalid setting"
Software stroke limits invalid for manual operation
1 Software stroke limits valid for manual operation
Software stroke limits invalid for manual operation

Stop group 1 sudden stop selection error 963 962
Stop group 2 sudden stop selection error 964 963
Stop group 3 sudden stop selection error 965 964
Setting for the movement amount after near-point dog ON error 992 991

Positioning operation 523, 535, 545, 546 509 to 512
Parameter 920, 935, 990, 996 931, 933, 938, 971, 999


: Refer to "Section 15.2 List of errors" and "Section 15.3 List of warnings" for details on error codes and warning codes.
Input (X) Output (Y) Name A1SD75 QD75 Name A1SD75 QD75 (QD75/A1SD75) READY X00 X00 Axis 1 Positioning start Y10 Y10 Axis 1 Start complete X01 X10 Axis 2 Positioning start Y11 Y11 Axis 2 Start complete X02 X11 Axis 3 Positioning start Y12 Y12 Axis 3 Start complete X03 X12 Axis 4 Positioning start – Y13 Axis 4 Start complete – X13 Axis 1 Stop Y13 Y04 Axis 1 BUSY X04 X0C Axis 2 Stop Y14 Y05 Axis 2 BUSY X05 X0D Axis 3 Stop Y1C Y06 Axis 3 BUSY X06 X0E Axis 4 Stop – Y07
Axis 4 BUSY – X0F Axis 1 Forward run JOG start Y16 Y08
Axis 1 Positioning complete X07 X14 Axis 1 Reverse run JOG start Y17 Y09
Axis 2 Positioning complete X08 X15 Axis 2 Forward run JOG start Y18 Y0A
Axis 3 Positioning complete X09 X16 Axis 2 Reverse run JOG start Y19 Y0B
Axis 4 Positioning complete – X17 Axis 3 Forward run JOG start Y1A Y0C
Axis 1 Error detection X0A X08 Axis 3 Reverse run JOG start Y1B Y0D
Axis 2 Error detection X0B X09 Axis 4 Forward run JOG start – Y0E
Axis 3 Error detection X0C X0A Axis 4 Reverse run JOG start – Y0F
Axis 4 Error detection – X0B PLC READY Y1D Y00
Axis 1 M code ON X0D X04 Axis 1 Execution prohibition flag – Y14
Axis 2 M code ON X0E X05 Axis 2 Execution prohibition flag – Y15
Axis 3 M code ON X0F X06 Axis 3 Execution prohibition flag – Y16
Axis 4 M code ON – X07 Axis 4 Execution prohibition flag – Y13
Synchronization flag – X01 Use prohibited Y00 to Y0F Y1E to Y1F
Y01 to Y03 Y18 to Y1F
Use prohibited X10 to X1F X02, X03 X18 to X1F
: The ON/OFF statuses for READY are different between the QD75 and A1SD75.
Not READY/WDT error READY
A1SD75 ON OFF
Appendix - 51

The following table shows the buffer memory addresses of the QD75 (Axes 1 to 3) corresponding to the items of the A1SD75. The shaded area shows the differences between the A1SD75 and QD75.
A1SD75 QD75 Items of A1SD75
Axis 1 Axis 2 Axis 3 Axis 1 Axis 2 Axis 3
Pr.1 Unit setting 0 150 300 0 150 300
Pr.2 No. of pulses per rotation (Ap) 1 151 301 1 151 301
Pr.3 Movement amount per rotation (Al) 2 152 302 2 152 302
Pr.4 Unit magnification (Am) 3 153 303 3 153 303
Pr.5 Pulse output mode 4 154 304 4 154 304
Pr.6 Rotation direction setting 5 155 305 5 155 305
Pr.7 Speed limit value 6 7 156 157 306 307 10 11 160 161 310 311
Pr.8 Acceleration time 0 8 9 158 159 308 309 12 13 162 163 312 313
Pr.9 Deceleration time 0 10 11 160 161 310 311 14 15 164 165 314 315
Pr.10 Bias speed at start 12 13 162 163 312 313 6 7 156 157 306 307
Pr.11 Stepping motor mode selection amount 14 164 314 – – –
Pr.12 Backlash compensation amount 15 165 315 17 167 317
Pr.13 Software stroke limit upper limit value 16 17 166 167 316 317 18 19 168 169 318 319
Pr.14 Software stroke limit lower limit value 18 19 168 169 318 319 20 21 170 171 320 321
Pr.15 Software stroke limit selection 20 170 320 22 172 322
Pr.16 Software stroke limit valid/invalid setting 21 171 321 23 173 323
Pr.17 Command in-position width 22 23 172 173 322 323 24 25 174 175 324 325
Pr.18 Torque limit setting value 24 174 324 26 176 326
Pr.19 M code ON signal output timing 25 175 325 27 177 327
Pr.20 Speed switching mode 26 176 326 28 178 328
Pr.21 Interpolation speed designation method 27 177 327 29 179 329
Pr.22 Current feed value during speed control 28 178 328 30 180 330
Pr.23 Manual pulse generator selection 29 179 329 – – –
Pr.24 Logic selection for pulse output to the drive unit 30 180 330 – – –
Pr.25 Size selection for acceleration/deceleration time 31 181 331 – – –
Pr.26 Acceleration time 1 36 37 186 187 336 337 36 37 186 187 336 337
Pr.27 Acceleration time 2 38 39 188 189 338 339 38 39 188 189 338 339
Buffer memory address · Appendix - 52

A1SD75 QD75 Items of A1SD75
Axis 1 Axis 2 Axis 3 Axis 1 Axis 2 Axis 3
Pr.28 Acceleration time 3 40 41 190 191 340 341 40 41 190 191 340 341
Pr.29 Deceleration time 1 42 43 192 193 342 343 42 43 192 193 342 343
Pr.30 Deceleration time 2 44 45 194 195 344 345 44 45 194 195 344 345
Pr.31 Deceleration time 3 46 47 196 197 346 347 46 47 196 197 346 347
Pr.32 JOG speed limit value 48 49 198 199 348 349 48 49 198 199 348 349
Pr.33 JOG operation acceleration time selection 50 200 350 50 200 350
Pr.34 JOG operation deceleration time selection 51 201 351 51 201 351
Pr.35 Acceleration/deceleration process selection 52 202 352 52 202 352
Pr.36 S-pattern proportion 53 203 353 53 203 353
Pr.37 Sudden stop deceleration time 54 55 204 205 354 355 54 55 204 205 354 355
Pr.38 Stop group 1 sudden stop selection 56 206 356 56 206 356
Pr.39 Stop group 2 sudden stop selection 57 207 357 57 207 357
Pr.40 Stop group 3 sudden stop selection 58 208 358 58 208 358
Pr.41 Positioning complete signal output time 59 209 359 59 209 359
Pr.42 Allowable circular interpolation error width 60 61 210 211 360 361 60 61 210 211 360 361
Pr.43 External start function selection
62 212 362 62 212 362
Pr.44 Near pass mode selection for path control 66 216 366 – – –
Pr.45 OPR method 70 220 370 70 220 370
Pr.46 OPR direction 71 221 371 71 221 371
Pr.47 OP address 72 73 222 223 372 373 72 73 222 223 372 373
Pr.48 OPR speed 74 75 224 225 374 375 74 75 224 225 374 375
Pr.49 Creep speed 76 77 226 227 376 377 76 77 226 227 376 377
Pr.50 OPR retry 78 228 378 78 228 378
Pr.51 OPR dwell time 79 229 379 79 229 379
Pr.52 Setting for the movement amount after near-
80 81 230 231 380 381 80 81 230 231 380 381
Pr.53 OPR acceleration time selection 82 232 382 82 232 382
Pr.54 OPR deceleration time selection 83 233 383 83 233 383
Pr.55 OP shift amount 84 85 234 235 384 385 84 85 234 235 384 385
Pr.56 OPR torque limit value 86 236 386 86 236 386
Pr.57 Speed designation during OP shift 88 238 388 88 238 388
Pr.58 Dwell time during OPR retry 89 239 389 89 239 389
Buffer memory address · point dog ON · Appendix - 53


Common for axis 1, 2, 3 Common for axis 1, 2, 3, 4
Md.11 Error judgment 466 to 541 1216 to 1291
Md.19 Axis in which the error occurred 624 to 684 1293 to 1353
Md.20 Axis error No. 625 to 685 1294 to 1354
Appendix - 54


Common for axis 1, 2, 3 Common for axis 1, 2, 3, 4
Md.24 Axis in which the warning occurred 689 to 749 1358 to 1418
Md.25 Axis warning No. 690 to 750 1359 to 1419
Appendix - 55

A1SD75 QD75 Items of A1SD75
Axis 1 Axis 2 Axis 3 Axis 1 Axis 2 Axis 3
Md.29 Current feed value 800
Md.30 Machine feed value 802
Md.31 Feedrate 804
Md.32 Valid M code 806 906 1006 808 908 1008
Md.33 Axis error No. 807 907 1007 806 906 1006
Md.34 Axis warning No. 808 908 1008 807 907 1007
Md.35 Axis operation status 809 909 1009 809 909 1009
Md.36 Current speed 810
Md.37 Axis feedrate 812
Md.38 Speed-position switching control positioning
Md.39 External input/output signal 816 916 1016 816 916 1016
Md.40 Status 817 917 1017 817 917 1017
Md.41 Target value 818
Md.42 Target speed 820
Md.43 OP absolute position 822
1023 – – –
Md.44 Movement amount after near-point dog ON 824
Md.45 Torque limit stored value 826 926 1026 826 926 1026
Md.46 Special start data instruction code setting value 827 927 1027 827 927 1027
Md.47 Special start data instruction parameter setting
828 928 1028 828 928 1028
Md.48 Start positioning data No. setting value 829 929 1029 829 929 1029
Md.49 In speed control flag 830 930 1030 830 930 1030
Md.50 In speed change processing flag 831 931 1031 831 931 1031
Md.51 Start data pointer being executed 832 932 1032 834 934 1034
Md.52 Last executed positioning data No. 833 933 1033 837 937 1037
Md.53 Repetition counter
834 934 1034 832 932 1032
Md.54 Positioning data No. being executed 835 935 1035 835 935 1035
Md.55 Block No. being executed 836 936 1036 836 936 1036
Md.56 Positioning data being executed 838 to 847 938 to 947 1038 to
1047 838 to 847 938 to 947 1038 to


Axis 1 Axis 2 Axis 3 Axis 1 Axis 2 Axis 3
Cd.8 Read/write positioning data I/F 1108 to 1137 –
Cd.11 Positioning start No. 1150 1200 1250 1500 1600 1700
Cd.12 Axis error reset 1151 1201 1251 1502 1602 1702
Cd.13 Restart command 1152 1202 1252 1503 1603 1703
Cd.14 M code OFF request 1153 1203 1253 1504 1604 1704
Cd.17 Speed change request 1158 1208 1258 1516 1616 1716
Cd.18 Positioning operation speed override 1159 1209 1259 1513 1613 1713
Cd.20 Speed-position switching enable flag 1163 1213 1263 1528 1628 1728
Cd.22 Manual pulse generator enable flag 1167 1217 1267 1524 1624 1724
Cd.24 OPR return request flag OFF request 1170 1220 1270 1521 1621 1721
Cd.26 Step valid flag 1172 1222 1272 1545 1645 1745
Cd.27 Step mode 1173 1223 1273 1544 1644 1744
Cd.28 Step start information 1174 1224 1274 1546 1646 1746
Cd.29 Skip command 1175 1225 1275 1547 1647 1747
Cd.30 New torque value 1176 1226 1276 1525 1625 1725
Cd.31 Positioning starting point No. 1178 1228 1278 1501 1601 1701
Cd.32 Interrupt request during continuous operation 1181 1231 1281 1520 1620 1720
Appendix - 57

A1SD75 QD75 Items of A1SD75
Axis 1 Axis 2 Axis 3 Axis 1 Axis 2 Axis 3
Cd.34 New deceleration time value 1186
1510 1511 1610 1611 1710 1711
Cd.35 Acceleration/deceleration time change during
1188 1238 1288 1512 1612 1712
speed change, enable/disable selection
Da.1 Operation pattern
Da.2 Control system
1300 2300 3300 2000 8000 14000
Da.3 Acceleration time No.
Da.4 Deceleration time No.
Da.9 M code/condition data 1301 2301 3301 2001 8001 14001
Da.8 Dwell time/JUMP destination
No.1
1302 2302 3302 2002 8002 14002
positioning data No.
Da.7 Command speed 1304 1305 2304 2305 3306 3307 2004 2005 8004 8005 14004 14005
Da.5 Positioning address/movement
1306 1307 2306 2307 3306 3307 2006 2007 8006 8007 14006 14007
Da.6 Arc address
1308 1309 2308 2309 3308 3309 2008 2009 8008 8009 14008 14009
No.2 1310 to 1319 2320 to 2329 3310 to 3319 2010 to 2019 8010 to 8019 14010 to 14019
No.3 1320 to 1329 2330 to 2339 3320 to 3329 2020 to 2029 8020 to 8029 14020 to 14029
to
No.100 2290 to 2299 3290 to 3299 4290 to 4299 2990 to 2999 8990 to 8999 14990 to 14999
Refer to Appendix 12 "List of buffer memory addresses" for details.

A1SD75 QD75 Items of A1SD75
Axis 1 Axis 2 Axis 3 Axis 1 Axis 2 Axis 3
Da.10 Shape
Da.11 Start data No.
Start block data 2
1st point 4300 4350 4550 4600 4800 4850 26000 26050 27000 27050 28000 28050
Da.12 Special start
Da.13 Parameter
2nd point 4301 4351 4551 4601 4801 4851 26001 26051 27001 27051 28001 28051
3rd point 4302 4352 4552 4602 4802 4852 26002 26052 27002 27052 28002 28052
Positioning start information 2
to
50th point 4349 4399 4599 4649 4849 4899 26049 26099 27049 27099 28049 28099
Da.14 Condition target
4400 4650 4900 26100 27100 28100
Da.15 Condition operator
Da.16 Address 4402 4403 4652 4653 4902 4903 26102 26103 27102 27103 28102 28103
No. 1
Da.17 Parameter 1 4404 4405 4654 4655 4904 4905 26104 26105 27104 27105 28104 28105
Da.18 Parameter 2
4406 4407 4656 4657 4906 4907 26106 26107 27106 27107 28106 28107
No. 2 4410 to 4419 4660 to 4669 4910 to 4919 26110 to 26119 27110 to 27119 28110 to 28119
No. 3 4420 to 4429 4670 to 4679 4920 to 4929 26120 to 26129 27120 to 27129 28120 to 28129
to
No. 10 4490 to 4499 4740 to 4749 4990 to 4999 26190 to 26199 27190 to 27199 28190 to 28199
Start No. 8001 4500 4750 5000 – – –
Start No. 8002 4501 4751 5001 – – –
to
Start No. 8050 4549 4799 5049 – – –
to to PLC CPU memo area
Condition judgment target data of the condition data
Target axis 5100 –
Head positioning block No. 5101 –
No. of read/write data items 5102 –
Read/write request 5103 –
Read/write block 5110 to 6109 –
Refer to Appendix 12 "List of buffer memory addresses" for details.

The following table shows the comparisons of numbers for each symbols (Pr., Md., Cd., and Da.) indicating parameters or positioning data items. The shaded sections indicate the added or changed items with the QD75.

Logic selection for pulse output to the drive unit Pr.24 –
Parameters · Appendix - 60


Near pass mode selection for path control Pr.44 –
Setting for the movement amount after near-point dog ON Pr.52 Pr.50
Appendix - 61


Monitor data · Appendix - 62


No. of write accesses to flash ROM – Md.19
Special start data instruction code setting value Md.46 Md.36
Special start data instruction parameter setting value Md.47 Md.37
Appendix - 63


Speed-position switching control movement amount change register Cd.21 Cd.23
Manual pulse generator 1 pulse input magnification Cd.23 Cd.20
Control data · Appendix - 64


Simultaneous starting axis start data No. (Axis 1 start data No.) – Cd.30
Simultaneous starting axis start data No. (Axis 2 start data No.) – Cd.31
Simultaneous starting axis start data No. (Axis 3 start data No.) – Cd.32
Simultaneous starting axis start data No. (Axis 4 start data No.) – Cd.33
Acceleration/deceleration time change during speed change, enable/disable selection Cd.35 Cd.12
Stop command processing for deceleration stop selection – Cd.42
Appendix - 65

Positioning data, block start data, condition data

Appendix - 66


Drive unit READY Negative logic Not possible Negative logic Possible
Zero signal Negative logic Not possible Negative logic Possible
Manual pulse generator A phase Manual pulse generator B phase 1 Negative logic
Near-point signal Negative logic Not possible Negative logic Possible
Stop signal Negative logic Not possible Negative logic Possible
Upper limit Negative logic Not possible Negative logic Possible
Lower limit Negative logic Not possible Negative logic Possible
External start 2 Negative logic Not possible Negative logic Possible
Speed-position switching signal 2 Negative logic Not possible Negative logic Possible

Command pulse 3 Positive logic CW/CCW mode Possible Negative logic CW/CCW mode Possible
Deviation counter clear Negative logic Not possible Negative logic Possible

No. of connectable manual pulse generators 1 generator/1 axis 1 generator/1 module
Possible Multiple of 1 mode, multiple of 4 mode,

Mode selection (with parameter) PULSE/SIGN mode, A phase/B phase (multiple of 4) mode,
A phase/B phase (multiple of 1) mode, CW/CCW mode
Input signal comparisons · Output signal comparisons · Appendix - 67

1-2 PHASE EXCITATION SYSTEM
This is one system for exciting each stepping motor coil in a determined order. In this system, one phase and two phases are alternately excited.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Pulse count Forward run (addition)
In this positioning control method, the positioning pattern, positioning addresses (P1, P2), and positioning speeds (V1, V2) are set in the sequence program. Positioning is carried out to positioning address P1 by issuing the 1st positioning start command. When P1 is reached, the positioning then automatically changes to positioning at the V2 speed.
This is one system for exciting each stepping motor coil in a determined order. In this system, a current constantly flows to 2 phases to carry out step feed.

An A phase and B phase double pulse. There is a phase difference between the two phases, so that difference can be automatically added and subtracted in the pulse count. The standard phase difference is a 90ø electrical angle. If the B phase were to lag behind the A phase in a forward run (B phase turns ON after the A phase), the A phase would lag behind the B phase in a reverse run (A phase turns ON after the B phase). In this way the forward and reverse run (addition and subtraction) can be automatically carried out.

No.1 0 No.2 No.3
This is a detector that enables the angle data within 1 motor rotation to be output to an external destination. Absolute encoders are generally able to output 360° in 8 to 12 bits. Incremental encoders have a disadvantage in that the axis position is lost when a power failure occurs. However, with absolute encoders, the axis position is not lost even when a power failure occurs. Various codes such as a binary code and BCD code can be output. Absolute encoders are more expensive, more accurate, and larger than incremental encoders. Refer to "ENCODER".
The parameter acceleration time refers to the time from a stopped state to the time the speed limit value is reached, so it becomes proportionally shorter as the setting speed decreases. The acceleration time is determined by factors such as machine inertia, motor torque, and load resistance torque.

ABSOLUTE POSITION DETECTION SYSTEM
In the absolute position detection system, once an OPR is carried out at the system startup, the system stores the machine position in the memory and retains the current position even when the power is turned OFF. Mechanical deviation will be compensated, so that the OPR is not required after the power is turned ON next time. Configuring this system requires a motor with an absolute position detector and a servo amplifier and positioning module compatible with an absolute position detection system.
This is the mode that outputs the M code after positioning is complete (after stopping). Clamping can be commanded, drilling dimensions can be selected, etc., with this mode.
No.11 No.10 Positioning
This is one system for expressing a positioning address. Absolute address system. This system uses 0 as a reference, and expresses the address as the distance from 0. The direction is automatically determined, even when it is not designated. The other address system is the increment system.

BACKUP FUNCTION
Properties such as responsiveness and stability of machines driven with a servomotor are affected by changes in the inertia moment and rigidity due to changes in the machine load, etc. This function automatically adjusts the speed loop gain and position loop gain to match the machine state, so the machine's performance can be maintained at its optimum state. A real time automatic tuning function should be used for machines having large load fluctuations.
Backup functions consist of the following. 1) Functions for storing the sequence program and device statuses stored in the RAM memory of the PLC CPU, so that they are not lost during power failures, etc. 2) Functions for storing the current value in absolute position compatible systems so that it is not lost during power failures, etc. 3) Functions for reading the PLC CPU data (PLC programs, parameters, positioning data, etc.) by a peripheral device when the old PLC CPU is replaced, and then write it to the new PLC CPU after the replacement is completed.
BALL SCREW
An operation in which a graph of the time and speed takes a trapezoidal shape.
This is a type of screw, with balls lined up in the threads like ball bearings. This reduces backlash, and enables rotation with little force.
When a forward run operation changes to a reverse run operation, there is sometimes play (backlash) in the mesh of the toothed gears. This also occurs when using a worm gear. Because of this backlash, a left feed of 1m (3.28feet) carried out after a right feed of 1m (3.28feet) will not be sufficient to return the machine to its original position. The machine cannot be positioned to its original position without an extra feed equivalent to the backlash amount. This function compensates for that backlash amount.
1m (3.28feet) (right feed) Machine does not move.
Backlash 1m (3.28feet) (left feed)

BIN (Binary)
1) This is the abbreviation for "binary coded decimal", more accurately called a BCD code. Computers, PLCs, etc., use binary numbers made up of 1 (ON) and 0 (OFF). Because this is difficult for humans to understand, decimal digits are expressed by a pattern of binary digits. Many of the digital switches and digital displays used by humans use a BCD code. The significance of the bits is shown in the drawing below. Numbers from 0 to 9,999 can be handled by 16 bits, and numbers from 0 to 99,999,999 can be handled by 32 bits.
B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0 128+32+4+2+1=167
167 0 1 0 1 0 0 1 1 1 215214213212211210 29 28 27 26 25 24 23 22 21 20
4000+1000+800+40+20+10+2 = 5.872
B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0
5.872 1 0 1 1 0 1 1 1 0 0 1 0
167 0 1 0 1 0 0 1 1 1
167 0 1 0 1 1 0 0 1 1 1
167 0 1 0 1 1 0 0 1 1 1
167 0 1 0 1 0 0 1 1 1
A large amount of torque is required when the machine starts moving, but the torque may be unstable at speed 0 with stepping motors. Therefore, movement can be smoothly carried out by starting the movement at a given speed from the beginning. The bias speed at start is the speed set at that start.
Speed 0 Bias speed

CHANGE signal
The CHANGE signal is an external signal used to switch the speed-position control from the speed control being executed to position control.
This is one system for driving a stepping motor. In this method, the orientation of the excitation current flowing to the stator coil is reversed, and the excitation current direction is in both the positive and negative direction. This enables the motor coil to be used effectively, and a large output torque can be obtained at low speeds.
Automatic operation in which the machine path makes a circle when positioning is carried out by simultaneously operating both the longitudinal feed and latitudinal feed motors. The normal unit is 90ø. Round shapes can be created with this type of interpolation, and obstacles in the machine path can also be avoided. Refer to the terms "INTERPOLATION OPERATION" and "LINEAR INTERPOLATION"
Bipolar drive basic circuit (bridge method)
A B C D Collision
Memory used to temporarily store data. Before writing external data to the PLC CPU data memory, it is first temporarily stored in the buffer memory to be used for operation by the program. The buffer memory is used by the positioning module because the latest data can be read and written.
Refer to term "FEEDBACK PULSE".
The movement speed for the target control during interpolation operations.

External data Data is written/read using the following commands: Write : TO Read : FROM
Y axis speed Composite speed
The device is doing some other work. It is in a positioning operation or in dwell time.
This is one type of positioning reference data. The unit to be used is designated as mm, inch, degree, or pulse.
Rotation in the counterclockwise direction. In the motor, this is determined looking from the shaft end side. Also refer to "CW".

CW (Clockwise)
Continuous path is a control method in which a path is followed without interrupting such as in uniform speed control.
Rotation in the clockwise direction. Rotation in the clockwise direction looking from the motor shaft end side.
D/A CONVERTER (Digital-to-Analog converter)
A speed at which the machine moves very slowly. It is difficult for the machine to stop accurately when running at high speed, so the movement must first be changed to the creep speed before stopping. Refer to the term "NEAR-POINT DOG".
A device having a function to convert the digital value expressing the No. of pulses to an analog value expressing the voltage (or current).
No. of pulses
D/A Voltage 0 to ±10V.
0 to 80,000 pulses/second
The OP address at the completion of the machine OPR is stored. The position currently being executed is stored. This value changes when the current value is changed.
DATA NO.
To carry out positioning to 2 or more addresses, each position is assigned a sequence No. such as No. 1, No. 2, No. 3, etc. The positioning is then carried out following this sequence. The QD75 is capable of positioning up to No. 600.
One of the servo control modes in positioning. Mode which uses current for torque control. Also called the torque loop mode. Refer to the section of "position loop mode".
No.4
No.2
No.6
No.3
No.1
No.5
This is the current address (position) when stopped or during positioning.
A ratio used when the machine is decelerated using a toothed gear. This ratio is a numeral larger than 1.
Input gear speed Deceleration ratio = Output gear speed
Appendix - 73

Command device Servo amplifier
The parameter deceleration time is the same value as the acceleration time. Deceleration time refers to the time from the speed limit value to a stopped state, so it becomes proportionally shorter as the setting speed decreases.
Commands are generally output from the positioning module to the servo amplifier as a pulse train. Recently, however, devices are being digitalized. Accompanying that, a connection method has appeared in which the bus lines of both the positioning module and the servo amplifier CPUs are connected. This has enabled the construction of higher- accuracy, higher-speed systems. The MELSEC A70D, AD774M, A171SCPU, A273UCPU etc., models employ this digital bus connection.
Deviation counters have the following two functions. 1) To count the command pulses issued from the QD75, and transmit the count value to the D/A converter. 2) To subtract the feedback pulses from the command pulses, and run the motor by the deviation value (droop pulse) of the command pulses and feedback pulses until the command pulses reaches 0.
The near-point dog of the OPR.
Command pulses Deviation counter
The commands output from the positioning module are low-voltage, low-current commands with insufficient energy to run the motor. The drive unit increases the width of these commands so the motor can be run. It is an accessory on servomotors and stepping motors. Also called a servo amplifier.
This is one type of encoder feedback pulse output. When one signal is output with this method, a companion signal having the reverse polarity is simultaneously output. This method enables high-frequency transfer, and is resistant to noise, etc., so it is also used in high-speed signal transfer such as inputting and outputting of pulse trains. In general, the transmission side is called the driver, the reception side is called the receiver, and a dedicated IC is used.
This signal is output when the drive unit for the motor is in a READY state. This signal remains OFF when the drive unit power is OFF, or during faults, etc.

ELECTRONIC GEAR
Because of inertia (GD2) in the machine, it will lag behind and not be able to track if the positioning module speed commands are issued in their normal state. Thus, for a servomotor, a method is used in which the speed command pulses are delayed by accumulation in a deviation counter. These accumulated pulses are called the droop pulse. The deviation counter emits all pulses and returns to 0 when the machine stops.
This function electrically increases/decreases the command pulses from the pulse command module by 1/50 to 50-fold. Thus, the positioning speed and movement amount can be controlled by the electronic gear ratio magnification.
Emergency stops cannot be carried out by the QD75, so a method of shutting OFF the servo side power supply from outside the PLC, etc., must be considered.
800 pulses Voltage D/A
200 pulses accumulate in the counter
This device turns the input data into a binary code of 1 (ON) and 0 (OFF). A type of pulse generator.
This is the time taken immediately after the positioning is completed to adjust for the droop pulses in the deviation counter. The positioning will not be accurate if this time is too short.
For the main signal
For the zero point signal

When protection circuits operate due to power failures, emergency stops (EMG signal) etc., this function is used to short-circuit between servomotor terminals via a resistor, thermally consume the rotation energy, and cause a sudden stop without allowing coasting of the motor. Braking power is generated by electromagnetic brakes only when running motors with which a large brake torque can be obtained. Because electromagnetic brakes have no holding power, they are used in combination with mechanical brakes to prevent dropping of the vertical axis.
Photoreceptor (phototransistor) Index scale
Light source (light-emitting diode)
Light source (LED) Collimator lens
Reference zero point Index
This function is supplied on motors with electromagnetic brakes. Electromagnetic brakes are used to prevent slipping during power failures and faults when driving a vertical axis, or as a protective function when the machine is stopped. These brakes are activated when not excited.

FAST OPR
If a dimension error occurs in the machine, and that error is actually smaller or larger than 1m (3.28feet) in spite of a 1m (3.28feet) command being issued from the QD75, that error amount will be compensated. For example, when the error is actually smaller than 1m (3.28feet), the remaining distance to 1m (3.28feet) is fed, and the correct 1m (3.28feet) of positioning is carried out.
The axis returns to the machine OP at the OPR speed without detecting the near-point dog. (This is not validated unless a machine OPR has been carried out first.)
ERROR RESET
This resets error of axis. Note that if the cause of the error is not eliminated at that time, the error will occur again.
EXTERNAL REGENERATIVE BRAKE RESISTOR
This is a pulse issued from the positioning module to a servomotor or stepping motor. Also called a command pulse.
This is also called the regenerative brake. When a machine is moved with a motor, power is normally supplied to the motor from an amplifier. However, the rotation energy in the motor and machine counterflows (regenerates) to the amplifier when the motor is decelerating or when driving a descending load. The external regenerative resistor consumes this regeneration energy with resistance, obtains the regenerative brake torque, and enables the full capacity of the regeneration system during stopping. It is used when carrying out highly repetitive acceleration/deceleration.
This is the basic screw in mechanisms that position using screw rotation. Ball screws are often used to reduce backlash and dimension error.
1 rotation by the motor
Lead (feedrate per screw rotation)
FEEDBACK PULSE
In the QD75, F is a status where the module itself has a fault. [HOLD]
This is a method of using a returning pulse train to confirm whether the machine faithfully operated according to the commands issued in automatic control. If the machine did not faithfully operate according to the commands, a correction command is issued. For example, if a command is issued for 10,000 pulses, and a feedback pulse of 10,000 pulses is returned, then the balance becomes 0 and it can be judged that the command was faithfully followed. Refer to the term "DEVIATION COUNTER".

G CODE
This is the feeding of a set dimension for cutting sheet and bar workpieces into the designated dimensions. Incremental system positioning is often used. The current value is not incremented, even when the feed operation is repeated.
These are standardized (coded) 2-digit numerical values (00 to 99) designating various control functions of the NC module. Also called G functions. Example :
G01 Linear interpolation G02 Circular interpolation CW (clockwise) G04 Dwell G28 OPR G50 Max. spindle speed setting
This battery-less memory can be used to store parameters and positioning data for backup. Because it is battery-less, battery maintenance is not required
The changing of the ratio between two values having a proportional relation. Seen on a graph, the changing of the incline of the characteristics.
About 100mm shorter in axial dimension than the standard motor. Used when the servomotor is installed in a small space.
This is the input signal that notifies the user that the limit switch (b contact configuration, normally ON) installed at the upper limit of the positioning control enabled range has been activated. The positioning operation stops when the FLS signal turns OFF (non-continuity).
Output Lowering the gain
For example, when 10 is output for an input of 10, the output can be changed to 12, 5, etc., by changing the gain.
The inertia moment. The sum total of the mass (dm) of each small area configuring an object multiplied by the square of the distance (r) of each of those areas from a given straight line. The relation with I = r2dmGD2 is given by 4gI, with "g" being gravitational acceleration.
Raising the gain · Input · Appendix - 77

INCREMENTAL SYSTEM
A device that simply outputs ON/OFF pulses by the rotation of the axis. 1-phase types output only A pulses, and do not indicate the axis rotation direction. 2-phase types output both A and B pulse trains, and can judge the rotation direction. The direction is judged to be forward if the B pulse train turns ON when A is ON, and judged to be reverse if A turns ON when B is ON. There is also another type of incremental encoder with a zero signal. The most commonly used incremental encoders output between 100 and 10,000 pulses per axis rotation. Refer to "ENCODER".
The current value is 0 in this system. Positions are expressed by the designated direction and distance of travel. Also called the relative address system. This system is used in fixed- feed, etc. Compare ABSOLUTE SYSTEM.
No.1 No.2 No.3
Right Right No. 2 is several millimeters to the right of No. 1.
B
INERTIA
Z
Phototransistor Zero signal slit
The property of an object, when not being affected by external forces, where it tries to maintain its current condition. The inertia moment.
Rotating axis 1 pitch
B
1 pulse per axis rotation
Output waveform 2-phase + OP output

JOG
Jog. This refers to moving the tool little by little. Inching. Parameter setting is required to carry out JOG operation.
This is the abbreviation for "kilopulses per second". 80kPPS equals 80,000 pulses per second.
INTERLOCK
This is a switch set to stop a moving object at both ends, etc., of a movement device for safety reasons. A circuit is created in which the moving body itself presses against the switch to activate the contact and forcibly shut the power OFF. For example, pressing on the actuator in the drawing below activates the internal microswitch. There are various other types.
In this condition, the machine is blocked from moving to the next operation until the operation in progress is complete. This function is used to prevent damage to devices and malfunctioning.
Y0
Y0
Y1
INTERPOLATION OPERATION
The simultaneous operation of multiple motors to carry out a composite operation. Each motor can be freely set with the positioning distance, acceleration/deceleration time, speed, and other factors, which are combined to move a target in a straight line, circle, etc. Linear interpolation and circular interpolation are available. (The circular interpolation uses two motors.)
INVERTER
This refers to a device to change a direct current (DC) to an alternating current (AC). The device actually changes the motor speed by changing 50Hz or 60Hz of commercial frequency to direct current once, then changing it again to a 5 to 120Hz alternating current and controlling the motor speed.

M CODE (Machine Code)
This automatic operation simultaneously operates two motors for the latitudinal (X) feed and longitudinal (Y) feed to move a target in a diagonal line for positioning. Three or four motors can also be operated simultaneously. The QD75 combines the operation of axis 1 through 4 for the linear interpolation. The same positioning data No. must be used for the setting. Refer to the term "INTERPOLATION OPERATION".
These are sub functions that interlock with the positioning operation to replace drills, tighten and loosen clamps, raise and lower welding electrodes, display various data, etc. Either of two modes can be entered when the machine code turns ON: AFTER or WITH. The machine does not move to the next positioning when the machine code is ON. M codes are turned OFF by the PLC program. Code Nos. from 1 to 65535 assigned by the user and used (1: Clamp, 2: Loosen, etc.). Comments can be written after 50 of the M codes, and they can be monitored using a peripheral device or displayed on an external display. Refer to "AFTER MODE" and "WITH MODE".
No.9
No.8 No.1
The OP address at the completion of the machine OPR is stored. The current position of the machine coordinates determined by a machine having the OP address as a reference. Even if the current value is changed, this value will not change.
Refer to "GD2".
MANUAL PULSE GENERATOR
This is a motor used when frequent acceleration/deceleration is repeated. Low- inertia motors are longitudinally longer, to decrease the rotor diameter and cover the torque. This enables their inertia moment to be reduced up to 1/3 that of standard motors. The ideal load inertia ratio is 1 or less.
The handle of this device is manually rotated to generate pulses. This device is used when manually carrying out accurate positioning.
Made by Mitsubishi Electric Corp. (model: MR-HDP01)
When carrying out interpolation operations, this is the side on which the positioning data is executed in priority. For example, when positioning with the X axis and Y axis, the side with the largest movement distance will become the master axis, and the speed will follow that axis. The slave axis speed will be ignored.
Longitudinal feed · Latitudinal feed · Appendix - 80

NEAR-POINT DOG
When using mm, inch, or degree units, the movement amount is calculated and output from the machine side showing how much the motor shaft moves per pulse. Positioning accuracy in smaller units is not possible. On the motor side, the movement amount per axis rotation is normally designed as a reference, so it is calculated as follows.
This is a switch placed before the OP. When this switch turns ON, the feedrate is changed to the creep speed. Because of that, the time that this switch is ON must be long enough to allow for the time required for deceleration from the feedrate to the creep speed.
Movement amount per pulse =
No. of pulses per
Amount the motor moves (travel) per pulse.
MULTI-PHASE PULSE
The QD75 has no way of knowing the current value when the machine is assembled and the positioning module is connected, so this function is used to teach it a temporary approximate value as the current value. This function can also be used to write a temporary current value when the current value has been lost due to accidents, etc. If an OPR is carried out after that, the positioning module will recognize the zero point. To prevent the accumulated value from exceeding the stroke limit in fixed-feed, etc., rewrite the current value to 0 after the fixed- feed. The current value can be changed during a positioning stop.
A combination of pulses in which 2 or more phases differ. 2-phase pulses, etc.
Z phase (ZERO signal)
The P rate. Refer to the term "P RATE".
This is the language punched into the paper tape that instructs the machining to the NC module. The NC language consists of EIA codes (EIA language), ISO codes (ISO standards), and JIS codes (JIS standards).

OPR METHOD
This is the reference position for positioning. Positioning cannot start without a reference point. The OP is normally set to the upper or lower stroke limit.
The OPR methods are shown below. The method used depends on the machine structure, stopping accuracy, etc. OPR can be carried out when the OPR parameters are written. 1) Near-point dog method 2) Stopper method 3) Count method
This point is the reference.
OPR PARAMETER
OP SHIFT FUNCTION
This parameter is required when returning to the OP. It is determined by the machine side design, so subsequent changes of this parameter must be accompanied by changes in the machine design. The OP is the reference for positioning operations, so if the OP is lost due to a power failure during positioning, or because the power is turned OFF and the machine is moved manually, etc., it can be restored by carrying out an OPR. When a machine OPR command is issued, the machine will move in search of the near-point dog regardless of the current value, and will stop at the OP. At this time, the current value will be rewritten to the OP address. Data cannot be written during positioning. With the QD75, data is always written for all axes (from 1 to 4 axes). Refer to the term "NEAR-POINT DOG".
The OP position can be shifted in the positive or negative direction by executing a machine OPR and determining the shift amount from the machine OPR complete position. An OP can be set at a position besides the OP position, or outside the dog switch.
The kind of operation to be carried out after executing the positioning data is determined. 1) If "POSITIONING COMPLETE" is selected, the operation will stop after the positioning is complete. 2) If "CONTINUOUS POSITIONING CONTROL" is selected, the next data No. will be automatically executed after the positioning is complete. 3) If "CONTINUOUS PATH CONTROL" is selected, the positioning will not be completed. Only the speed will be automatically changed, and the next data No. will be executed.
Appendix - 82

P RATE (Pulse Rate)
This signal turns ON when there is an error with the QD75. It will turn ON in the following situations. 1) When the power is turned ON. 2) When the PLC READY signal turns from OFF to ON. 3) When the machine OPR starts. 4) When the drive unit READY signal turns from ON to OFF. The user judges whether to carry out a machine OPR in the above situations.
A coefficient that magnifies the feedback pulses per motor shaft rotation by 2-fold, 3- fold, 1/2 or 1/3. It is the ratio of the feed pulses and feedback pulses. For example, when the No. of pulses per motor shaft rotation is set to 2400 pulses, and the P rate is set to 2, the result will be equivalent to 1200 pulses. The rotation per pulse is 0.15° when 2400 pulses per rotation are set, but this becomes 0.3° when 1200 pulses. The positioning accuracy drops as the P rate is increased.
This is a pin connector for outputting data from the QD75 to an external source. It is connected to the motor drive unit. This terminal is used to output the following. • Feedback pulses for both forward run and
This is the basic data used in positioning. Parameters are determined by the machine side design, so subsequent changes of parameters must be accompanied by changes in the machine design. Data cannot be written during positioning. The initial parameter values are written by the maker.
Pronounced "pee-jee-zero". Refer to the term "ZERO SIGNAL".
With this function, the speed during positioning operations (current speed) can be varied between 1 and 300%. The speed can also be changed by the same variable rate for continuous positioning with differing designated speeds.
Feedback pulses · 1 axis rotation · Appendix - 83

POSITION LOOP MODE
This is mainly the control of position and dimension, such as in fixed-feed, positioning, numerical control, etc. This is always controlled with feed pulses. There is also speed control. Drive units may differ, even when the same motor is used.
This is one servo control mode used in positioning. It is a mode for carrying out position control. The other servo control modes are the speed loop mode for carrying out speed control, and the torque loop mode for carrying out torque control (current control).
This is an abridged version of positioning. There are two types on MELSEC, the A1S62LS. This module has positioning and limit switch functions, and can use a total of 16 channels. The following drawing shows an example for 5 channels. A resolver is used in the positioning detection.
Speed feedback Position feedback Interface
POSITIONING
ON
Accurately moving the machine from a point to a determined point. The distance, direction, speed, etc., for that movement are designated by the user. Positioning is used in operations such as cutting sheets, drilling holes in plates, mounting parts on a PCB, and welding. Positioning is also used with robots.
ON ON
ON
ON
POSITION LOOP GAIN
POSITIONING COMPLETE
This is the ratio of the deviation counter droop pulses to the command pulse frequency.
Refer to the term "OPERATION PATTERN".
Command pulse frequency Position loop gain = Droop pulses (1/s)
The position loop gain can be set with the drive unit. Raise the gain to improve the stopping accuracy. However, overshooting will occur if the position loop gain is raised too far, and the operation will become unstable. If the position loop gain is lowered too far, the machine will stop more smoothly but the stopping error will increase.
This is a signal that occurs when the positioning is complete. A timer set beforehand starts when this signal is output, and the machine movement stops for that time. When this signal turns ON, the positioning start signal turns OFF.
Positioning Different type of work

POSITIONING CONTINUED
Refer to the section of term "operation pattern".
The turning ON and OFF of the current (voltage) for short periods. A pulse train is a series of pulses. The QD75 is the module that generates the pulses.
This is data for the user to carry out positioning. The No. of points to which positioning is carried out (the No. of addresses) is designated by the user. In the QD75, these are 600 points. As a principle, positioning is executed in the order of the data Nos.
This is a device that generates pulses. Examples include devices installed on the motor shaft that create pulses when the shaft rotates, and digital devices. 1-phase types output one pulse train. 2-phase types output two pulse trains with a phase difference. From 600 to 1,000,000 pulses can be output per shaft rotation. Generators with a ZERO signal function to output 1 or 2 pulses per shaft rotation. Abbreviated as PLG. Refer to the term "ENCODER".
This is basic data for carrying out positioning control. Types of data include control unit, movement amount per pulse, speed limit value, upper and lower stroke limit values, acceleration/deceleration time, positioning system, etc. Parameters have an initial value, so that value is changed to match the control conditions.
POSITIONING START
There are two methods used to issue forward run and reverse run commands to the servomotor. The type used differs according to the machine maker. In type A, the forward run pulses and reverse run pulses are output from separate terminals. In type B, the forward run pulses and reverse run pulses are output from the same terminal, and a forward/reverse run identification signal is output from another terminal.
This refers the act of designating a target data No. and starting the positioning. The operation after the positioning is complete for that data No. is determined by the data No.'s positioning pattern.
This is a type of positioning control. With this control method, the points to be passed are designated at random locations on the path. Movement only to a given target positioning is requested. Path control is not required during movement from a given point to the next value.
A type B type

RLS SIGNAL (reverse limit signal)
This means that preparation is complete.
This is the input signal that notifies the user that the limit switch (b contact configuration, normally ON) installed at the lower limit of the positioning control enabled range is activated. The positioning operation stops when the RLS signal turns OFF (non-continuity).
Refer to "AUTO TUNING".
REFERENCE AXIS SPEED
This is the speed of the reference axis during interpolation operations.
A round table on which the workpiece is placed. Positioning control is carried out while rotating the workpiece in a 360° range.
Y axis speed (interpolation axis) X axis speed (reference axis)
In this pattern, the acceleration and deceleration follow a sine curve, and the movement is smooth. The S-pattern proportion can be set from 1 to 100%.
This function is an option. It is used when carrying out highly repetitive acceleration/deceleration. Refer to "EXTERNAL REGENERATIVE RESISTOR".
Refer to the term "DRIVE UNIT".
This device detects the angle by resolving the two voltages of the analog input. Also called a 2-phase synchro. For a 1-phase voltage input, the axis rotation angle is converted into a perpendicular 2-phase voltage (analog voltage) and output.
Movement distance for one resolver rotation
Resolver (addresses 0 to 4095, converted to digital)

SFC (Sequential Function Chart)
In positioning using a servomotor, stepping motor, etc., working power is required to hold the machine at the stop position. (The position will be lost if the machine is moved by external power.) This kind of state is called servo lock or servo lock torque.
A sequential function chart is a programming method optimally structured for running a machine's automatic control in sequence with the PLC.
Execution of advance operation servo program Positioning complete
Execution of extrusion operation servo program
Execution of retract operation servo program Positioning complete
Motor holds the position at the stop position.
When a SKIP signal is input, the positioning being executed is interrupted, the motor is deceleration stopped, and the next positioning is automatically carried out.
The servo amplifier will not operate if the servo amplifier is in a normal state and this servo ON signal is OFF.
READY Servo amplifier Servo ON
During interpolation operation, the positioning data is partially ignored on this side. This axis is moved by the master axis data.
PLG
SERVOMOTOR
A motor that rotates true to the command. Servomotors are highly responsive, and can carry out frequent high-speed and high- accuracy starts and stops. DC and AC types are available, as well as large-capacity motors. A pulse generator accessory for speed detection is common, and feedback control is often carried out.
This is one setting item of the positioning reference parameters. The unit to be used is designated as mm, inch, degree, or pulse.

SPEED-POSITION SWITCHING CONTROL
Speed control is mainly carried out with the servomotor. It is an application for grindstone rotation, welding speed, feedrate, etc. Speed control differs from position control in that the current position (address) is not controlled. Drive units may differ, even when the same motor is used.
With this control, positioning is carried out to the end point of the movement amount while changing the speed at the speed switching point during positioning control.
This is one method used for positioning. It is an application for operations such as high- speed movement to a point unrelated to positioning, then set dimension movement from the switching signal activation point.
This is one item in the parameters of the servo amplifier, and is used to raise the frequency response during speed control to improve transient characteristics. When adjusting the speed loop gain, raising this value is effective if the overshooting during acceleration/deceleration remains large. This compensation is set in ms units.
High speed Incremental positioning
SPEED LIMIT VALUE
This signal gives an immediate response notifying the user that the QD75 that was started is now in a normal state and can start positioning.
This is the max. speed for positioning. Even if other data is mistakenly set to a higher speed than this, the positioning will be carried out at this speed limit value when it is set in the parameters. The acceleration time becomes the time to accelerate from a stopped state to the speed limit value, and the deceleration time becomes the time to decelerate from the speed limit value to a stopped state.
One of the QD75 axis system axes (axis 1, axis 2, axis 3, or axis 4) or the reference axis for the interpolation operation is designated as the starting axis.
This is one item in the parameters of the servo amplifier, and expresses the speed of the control response during speed control. When the load inertia moment ratio increases, the control system speed response decreases and the operation may become unstable. If this happens, the operation can be improved by raising this setting value. The overshoot will become larger if the speed loop gain is raised too far, and motor vibration noise will occur during operation and when stopped.
Data showing the state of the machine. Collectively refers to signals that turn ON when the battery voltage drops, during OPR requests, during dwell time, etc.
When the operation is designed so that several positioning data Nos. are consecutively run, this function can be used to carry out a test operation for 1 data item at a time.
This is one servo control mode used in positioning. It is a mode for carrying out speed control. Refer to "POSITION LOOP MODE".
Start Switching signal · Appendix - 88

STOP SIGNAL
Stepping motors rotate in proportion to the No. of pulses (frequency), but the motor's rotation will deviate if the load is too large for the motor. This is called step out. If step out occurs, the motor must be replaced by one with a larger torque. Step out causes the positioning error to increase.
In positioning control, this is the input signal that directly stops the operation from an external source. The operation stops when the external stop signal (a-contact) turns ON (continuity).
This is one machine OPR method. With this method, a stopper is established at the OP, and the operation is stopped when the machine presses against it. Motor burning would occur or the stopper would be damaged if the machine were left in that state. There are two methods to prevent this; a timer can be used to shut OFF the motor after a fixed time, or the motor can be stopped by limiting sudden increase in the motor torque when the machine presses against the stopper.
A motor that rotates a given angle (example: 0.15ø) when 1 pulse is generated. For that reason, a rotation proportional to the No. of pulses can be obtained. 2-phase to 5- phase stepping motors are available. In the 3- phase type, the rotor rotates in order from A to C when a voltage is applied. Often found in compact motors, stepping motors rotate accurately without feedback. Be careful of step out when overloaded.
N
B
STROKE
N S
A A
A A
The stroke is the variation in the operation by the distance from a stopped state to the next stopped state after a movement.
S
B B
A A
A A
B
C B
Refer to the term "DWELL TIME".

TORQUE CONTROL
This is the range in which a positioning operation is possible, or the range in which the machine can be moved without damage occurring. (Movement outside this range is possible in the manual operation.) For operations using a worm gear, the stroke limit is determined by the length of the screw. For operations using a fixed-feed, it is determined by the max. dimension to be cut. The upper and lower limits are set in the parameters, but a separate limit switch should be established and an emergency stop circuit outside the PLC should be created. Refer to the term "LIMIT SWITCH".
In this function, a limit is established for the resistance torque applied to the motor used for positioning. The power is turned OFF if torque exceeding that value is applied to the motor. When excessive torque is applied to a motor, it causes the current to suddenly increase. Motor burning and other stress on the motor occurs, and the life of the motor is shortened. This function utilizes the sudden increase in the torque when the machine OPR to issue a command to stop the motor.
Also called the current loop mode. Refer to "POSITIONING LOOP MODE".
Limit switch for emergency stop
3m (9.84feet)
Torque width variations, deviations in the torque.
Positioning possible in a 3m (9.84feet) range
SUDDEN STOP
In this function, positioning is carried out at a speed relative to a moving target object by inputting the movement amount from an external encoder and adding it to the servo command value.
A stop carried out in a shorter time than the deceleration time designated in the parameters.
When the positioning address is uncertain, or gauging is required, this function is used by the user to search for and teach the position to the machine. For example, complex addresses such as drawings can be taught by tracing a model, and the positioning operation can be reproduced.

XY TABLE
A rotating table, which is turned using power. The table is used divided from one 360°
This is a device that moves a table in the X (latitudinal) and Y (longitudinal) directions so that positioning can be carried out easily. There are also commercially available products.
rotation into the required locations for work. The positioning control unit is "degree".
Y table Ball screw
Base table Y axis
Rotated by the motor
This is the setting of the unit for the actual address to which positioning is required, or for the movement amount. The following units can be set: mm, inch, degree and pulse. The initial value in the parameters is a pulse unit.
Also called "PG zero". Refer to "ZERO SIGNAL".
This refers to PG0 of the pulse generator (encoder) (one detection per shaft rotation). It also called "Z phase". Refer to the term "PULSE GENERATOR".
A warning is output as a warning code in when an abnormality is detected that is not serious enough to require cancellation or stoppage of the positioning operation. Warnings are handled differently than errors.
This is the mode that outputs the M code before the start of the positioning. This mode turns ON at the positioning start, enabling voltage to be applied to the welding electrodes, display of positioning speeds, etc. Refer to the term "AFTER MODE".

Trouble type Questions/Trouble Remedy No.
The PLC CPU power was turned OFF or the PLC CPU was reset, etc., during flash ROM writing, which deleted the data in the flash ROM. Initialize the parameters, and reset the required parameters. (Refer to Section 13.2 "Parameter initialization function" for details.)
Display reads "FFFFH" when a parameter is read with GX Configurator-QP.
How can the parameters be returned to their initial values (default values)?
Set the " Cd.2 Parameter initialization request" to "1". (Refer to Section 13.2 "Parameter initialization function" for details.)
A parameter error occurred although the parameter was set correctly by GX Configurator-QP.
The parameter may have been overwritten in the sequence program. Review the sequence program.
In the QD75, deceleration stops are executed after the machine exceeds hardware stroke limit range. Because of this, more time is required for the deceleration stop as the speed increases, and the overrun becomes larger. (The deceleration time becomes shorter at lower speeds, so the overrun becomes smaller.)
The machine overruns if operating at high speeds when the hardware stroke limit range is exceeded.
Use a "JOG operation", " Inching operation" or "Manual pulse generator operation" to return the machine to inside the hardware stroke limit range. (When the hardware stroke limit range is exceeded, positioning will not start toward inside the range even when so commanded. Once the range is exceeded, a return to inside the range can only be executed using a "JOG operation", "Inching operation" or "Manual pulse generator operation".)
When the machine exceeded the hardware stroke limit range, positioning toward inside the range was started, but the machine did not start.
Exactly one rotation is required, but the setting range for a "degree" unit setting is "0 to 359.999...". Won't the rotation deviate by "0.00...1"?
Designate "360.000" in the INC control. The motor will make exactly one rotation. 6
If the "movement amount per pulse" is calculated as written in the manual, settings smaller than the basic parameter setting range cannot be carried out.
Set "movement amount per pulse" in the QD75 using the
three parameter values of Pr.2 to Pr.4 .
Movement amount per pulse
Try setting the values following the explanations for each parameter.
Will an override setting value written before starting be valid? It will be valid. 8
During path control, will the override still be valid after the point is passed?
It will still be valid. 9 Override
Set the " Cd.13 Positioning operation speed override" to
How can the override be canceled?
"100".

Trouble type Questions/Trouble Remedy No.
How can the deceleration stop time during stopping be shortened using the hardware stroke limit?
Set "1: Sudden stop" in the " Pr.37 Stop group 1 sudden stop selection", and reduce the setting value of
" Pr.36 Sudden stop deceleration time".
The value set for the acceleration/deceleration time is the time required for the machine to accelerate from speed
The motor does not operate at "60000ms" although the acceleration/deceleration time is set to "60000ms".
"0" to the value set in " Pr.8 Speed limit value". Because of that, the acceleration/deceleration time will also be shorter than "60000ms" if the command speed value is
smaller than the " Pr.8 Speed limit value". (Refer to the
explanation for Pr.9 and Pr.10 for details.)
The trapezoidal and S-pattern acceleration/deceleration processing is a common setting for all acceleration/deceleration times, so individual setting is not possible. (Refer to Section 12.7.7 "Acceleration/deceleration process function".)
Can each acceleration/ deceleration time be individually set to trapezoidal or S-pattern acceleration/deceleration?
The machine starts and stops suddenly when carrying out JOG operations and positioning operations. (Using an MR-J2S servo amplifier.)
Review the parameter settings for acceleration/ deceleration time, speed limit value, JOG speed limit value, JOG acceleration/deceleration time, etc.
Are simplified absolute position detection system possible in the QD75P and QD75D Positional deviation models?
Simplified absolute position detection system
They are possible if the models are used in combination with a Mitsubishi "AC Servo". (Refer to "AC servo User's Manual" for details.)
The physical position position detection system from the commanded position, although the positioning is complete (and the monitored current position is correct).
If the deviation counter value is not "0", the servo side is still moving. Increase the torque.
In this case, the following values will result.
A setting of "1µm 1pulse" is required in the following system.

Trouble type Questions/Trouble Remedy No.
The machine only moves to "10081230", although positioning with a command value of "10081234" carried out. How can the error be compensated? The following values are currently set.
Reset Pr.3 and Pr.2 in the following order.
rotation", and the denominator in " Pr.2 No. of pulses
per rotation".
The near-point dog must be set to turn OFF at a position after the OP is passed. (When the machine OPR is started on the near-point dog on in a count-method machine OPR, the machine enters a normal machine OPR operation after returning to the near-point dog OFF region.) (If the near-point dog is turned OFF before the OP, and the machine OPR is started between the near-point dog OFF position and the OP, the machine will mistakenly interpret that its current position is before the near-point dog ON position, and it will pass over the OP and continue moving.)
When carrying out a count method machine OPR, the message "Leave Sufficient Distance From The OP Position To The Near- Point Dog OFF." appears. Is there a problem if the distance is short?
Carry out the following measures. 1) Separate the near-point dog signal and zero signal detection positions.
In the near-point dog method machine OPR, the stop positions are not uniform.
" Pr.47 Creep speed".
Can the machine OPR be carried out with the OPR retry function when it is started with the near- point dog ON and the upper/lower limit OFF?
A "Hardware stroke limit error" will occur and the operation will not be carried out. (The machine will interpret any position where the near- point dog is ON as being within the working range, and that the upper/lower limit is ON.)
Are ABS and INC positioning possible without carrying out an OPR?
They are possible. In this case, the position where the power is turned ON is handled as the current feed value "0".
The OPR request flag turns ON in the following cases. 1) When the power is turned ON. 2) When the PLC READY signal [YO] turns from OFF to ON. 3) When an OPR is carried out. 4) When the servo amplifier power is turned OFF. If no problem is found when the above are checked, then it is possible that the communication is being interrupted by "a fault in the bus cable", "noise influence", etc.
After an OPR, the OPR request flag sometimes turns ON for no apparent reason.
The OPR complete flag
Check whether the drive unit READY signal is weak or the power supply is unstable. 24
turns ON when it shouldn't be ON.
Error compensation · Appendix - 94

Trouble type Questions/Trouble Remedy No.
The positioning start signal [Y10] is kept ON until the BUSY signal is OFF, but is there any problem with turning it OFF before the BUSY signal turns OFF?
After the BUSY signal turns ON, there is no problem with turning [Y10] OFF before the BUSY signal turns OFF. (The QD75 detects the rising edge (OFF ON) of the positioning start signal [Y10].)
The operation will not start even when the start signal is turned ON.
Check the " Md.26 axis operation status" and
" Md.23 axis error No".
How many milliseconds should the axis stop signal [Y4] be turned ON for?
The signal should be turned ON at 4ms or more. (If possible, set the signal so it does not turn ON only momentarily, but instead stays ON until the BUSY signal turns OFF. This will keep the stop signal from skipping.)
How can a sudden stop be selected?
Pr.39 corresponding to the stop group, and reduce the
setting value of " Pr.36 Sudden stop deceleration time".
Stop "Normal deceleration stop" was
selected in " Pr.39 Stop group 3 sudden stop", and Y stop was
The operation will not change. Even if the same stop factor is input again during the deceleration stop, it will be ignored. The same deceleration stop process used when the stop signal was first input will be continued.
turned ON. If the Pr.39 setting is changed to "sudden stop" during a deceleration stop, and the Y stop signal turns from OFF to ON, will the operation change to a sudden stop from that point?
(This also applies for Pr.37 and Pr.38 .)
ABS system circular interpolation operates normally, but a vertically oblong circle results when INC system circular interpolation is carried out.
The address designation may be incorrect. When carrying out INC system circular interpolation, designate the relative addresses from the starting point of both the center point and end point.
Can the speed be changed during speed control and position control by speed-position switching control?
No. The speed for the speed control and position control cannot be set differently. 31
Either of the following is possible. 1) The sequence program may be incorrect. Check by creating a test program in which the JOG start signal is turned ON only. 2) If the machine is hitting something when the torque setting is low, it may be trying to move by JOG operation in the opposite direction. In this case, the machine will start moving only after the internal droop pulses have been reached 0 in the counter, even if the JOG start signal has been turned ON. This makes it seem that the response is slow.
Even if the JOG start signal is turned ON, the response until it turns ON is sometimes slow.
Either of the following is possible. 1) The JOG start signal may be chattering. Monitor the JOG start signal to confirm whether it is chattering. (When using the "BUSY signal" in the JOG operation start circuit, check the position of the BUSY signal.)
The operation is not carried out at the set JOG speed, although the speed limit value has not been reached.

Trouble type Questions/Trouble Remedy No.
The " Pr.31 JOG speed limit value" may be larger than
When a JOG operation is attempted, an error results and the machine does not move.
the " Pr.8 Speed limit value".
Review the parameters and carry out the JOG operation again.
If a value other than "0" is set for " Cd.16 Inching
Why does the positioning complete signal turns ON during the JOG operation?
movement amount", the inching operation is carried out and the positioning complete signal turns ON.
Confirm that the " Cd.16 Inching movement amount" is set to "0".
Is it possible to count the pulses when the B phase is set to "1", and only A phase pulses are input?
Not possible. (The QD75 counts 1, 0, 1, 0.) 36
Can a manual pulse generator other than the Mitsubishi MR- HDP01 be used?
Other manual pulse generators can be used if they conform to Section 3.4 "Specifications for input/output interfaces with external devices."
37 Manual pulse generator operation
Can one manual pulse generator be operated connected to several QD75 modules?
This is possible if the system conforms to the electrical specifications. 38
The BUSY signal is not canceled by the current value changing. How can it be canceled?
The BUSY signal may remain if the scan time is long. Use a complete signal to check whether the current value changing has been executed.
The QD75 READY signal does not turn ON even when the PLC READY signal [Y0] is turned ON.
"A parameter error" has occurred. Confirm the error No. in the error history, and correct the parameter.
The QD75 checks the M code ON signal OFF request every "1.8ms", so there is a possibility that the M code ON signal OFF may be delayed by a maximum of "1.8ms" after the M code ON signal ON, even if an M code ON signal OFF request is set.
Is there any problem with setting an M code ON signal OFF request in the next scan after the M code ON signal ON?
M code ON signal
How long is the output time for the deviation counter clear signal?
The time set in " Pr.55 Deviation counter signal output
43 Deviation counter clear
Is a deviation counter clear signal output when the positioning is complete?
A signal is not output. The only time the QD75 outputs a deviation counter clear signal is for a machine OPR.
How can a deviation counter clear signal be output?
The QD75 does not output a deviation counter clear signal except for machine OPR. 44
The internal parameters of the QD75 may be different. Check if the QD75 READY signal [X0] turns ON when the PLC READY signal [Y0] turns ON. When the PLC READY signal is ON but the QD75 READY signal is OFF, the parameter error has occurred. Check the error code and modify the parameter with the error.
Error 537 (PLC READY OFF start) occurs after the QD75 is replaced. (The sequence program is the same.)
The parameter settings on the QD75 side may not match those on the servo side. Check the parameter settings.
The motor only rotates in one direction.
The speed shown on the QD75 monitor is calculated from the number of pulses output from the module. Thus, the actual motor speed cannot be monitored.
Can the current motor speed be monitored?
(" Md.22 Feedrate" monitors the commanded speed. It does not show the actual motor speed.)

Trouble type Questions/Trouble Remedy No.
Backlash compensation value 0 ≤ Movement amount per pulse 255
Error 920 (backlash compensation amount error) occurs even when the backlash compensation value is set to "1".
Setting is not possible if the above equation is not satisfied.
Adjust by setting " Pr.4 Unit magnification" to 10-fold (or
100-fold, or 1000-fold), and setting " Pr.2 Movement
amount per rotation" to 1/10 (or 1/100, or 1/1000).
When a JOG operation is attempted, errors such as error 104 (hardware stroke limit+) or error 105 (hardware stroke limit ) occur and the machine does not move.
The hardware stroke limit wiring has probably not been carried out. Refer to Section 12.4.4 "Hardware stroke limit function" for details, and wire accordingly.
Error 997 (Speed selection at OP shift error) appears when the PLC READY signal [Y0] turns from OFF to ON.
A value besides "0" or "1" may be set in the " Pr.56 Speed designation during OP shift". Review the set sequence program, and reset the correct parameters.
The QD75 starts the deceleration stop process when the stop signal ON is detected. Thus, the machine interprets that "positioning is still being executed" immediately after the stop signal ON. Even if the start signal is turned ON at that time, the start request will be ignored and warning 100 will occur.
When the start signal was turned ON immediately after the stop signal ON, warning 100 (start during operation) was detected, and the start was ignored.
Does warning 500 (deceleration and stop speed change) occur only during "stop deceleration" and "automatically deceleration"? Is there any problem if the operation is continued in that state without resetting the error?
The warning occurs only at those times mentioned at the left. Because this is a warning, there is no problem if the operation can be continued without resetting the error. (When the speed is changed using the override, the new value will not be reflected on the data being executed, but will be reflected from the next start.)
Depending on the stop occurrence factor, positioning may have not been completed normally.
Check the axis monitor " Md.26 Axis operation status" after the BUSY signal has turned OFF. Stop : The stop signal has turned ON
during positioning. Check the condition under which the stop signal (Y stop, external stop) turns ON. Error occurrence : An error has occurred during
Position control was executed but the positioning complete signal does not turn ON.
positioning. Check the error occurrence factor
from " Md.23 Axis error No.".
The setting value of the detailed parameter 2 "Positioning complete signal output time" is 0 or shorter than the scan time. Using the sequence program, set the time when the signal can be detected securely.
Error/warning · Positioning complete signal · Appendix - 97

The following shows the relation between the buffer memory addresses and the various items. (Do not use ary address other than listed below. If used, the system may not operate correctly.)
Axis 1 Axis 2 Axis 3 Axis 4
0 150 300 450 Pr.1 Unit setting
1 151 301 451 Pr.2 No. of pulses per rotation (Ap)
2 152 302 452 Pr.3 Movement amount per rotation (Al)
3 153 303 453 Pr.4 Unit magnification (Am)
4 154 304 454 Pr.5 Pulse output mode
5 155 305 455 Pr.6 Rotation direction setting
6 7 156 157 306 307 456 457 Pr.7 Bias speed at start
8 9 158 159 308 309 458 459 Not used
10 11 160 161 310 311 460 461 Pr.8 Speed limit value
12 13 162 163 312 313 462 463 Pr.9 Acceleration time 0
14 15 164 165 314 315 464 465 Pr.10 Deceleration time 0
17 167 317 467 Pr.11 Backlash compensation amount
18 19 168 169 318 319 468 469 Pr.12 Software stroke limit upper limit value
20 21 170 171 320 321 470 471 Pr.13 Software stroke limit lower limit value
22 172 322 472 Pr.14 Software stroke limit selection
23 173 323 473 Pr.15 Software stroke limit valid/invalid selection
24 25 174 175 324 325 474 475 Pr.16 Command in-position width
26 176 326 476 Pr.17 Torque limit setting value
27 177 327 477 Pr.18 M code ON signal output timing
28 178 328 478 Pr.19 Speed switching mode
29 179 329 479 Pr.20 Interpolation speed designation method
30 180 330 480 Pr.21 Current feed value during speed control
31 181 331 481 Pr.22 Input signal logic selection
32 182 332 482 Pr.23 Output signal logic selection
33 Pr.24 Manual pulse generator input selection
34 184 334 484 Pr.150 Speed-position function selection
35 185 335 485 Not used 36 37 186 187 336 337 486 487 Pr.25 Acceleration time 1
38 39 188 189 338 339 488 489 Pr.26 Acceleration time 2

Axis 1 Axis 2 Axis 3 Axis 4
40 41 190 191 340 341 490 491 Pr.27 Acceleration time 3
42 43 192 193 342 343 492 493 Pr.28 Deceleration time 1
44 45 194 195 344 345 494 495 Pr.29 Deceleration time 2
46 47 196 197 346 347 496 497 Pr.30 Deceleration time 3
48 49 198 199 348 349 498 499 Pr.31 JOG speed limit value
50 200 350 500 Pr.32 JOG operation acceleration time selection
51 201 351 501 Pr.33 JOG operation deceleration time selection
52 202 352 502 Pr.34 Acceleration/deceleration process selection
53 203 353 503 Pr.35 S-pattern proportion
54 55 204 205 354 355 504 505 Pr.36 Sudden stop deceleration time
56 206 356 506 Pr.37 Stop group 1 sudden stop selection
57 207 357 507 Pr.38 Stop group 2 sudden stop selection
58 208 358 508 Pr.39 Stop group 3 sudden stop selection
59 209 359 509 Pr.40 Positioning complete signal output time
60 61 210 211 360 361 510 511 Pr.41 Allowable circular interpolation error width
62 212 362 512 Pr.42 External command function selection
70 220 370 520 Pr.43 OPR method
71 221 371 521 Pr.44 OPR direction
72 73 222 223 372 373 522 523 Pr.45 OP address
74 75 224 225 374 375 524 525 Pr.46 OPR speed
76 77 226 227 376 377 526 527 Pr.47 Creep speed
78 228 378 528 Pr.48 OPR retry
79 229 379 529 Pr.49 OPR dwell time
80 81 230 231 380 381 530 531 Pr.50 Setting for the movement amount after
82 232 382 532 Pr.51 OPR acceleration time selection
83 233 383 533 Pr.52 OPR deceleration time selection
84 85 234 235 384 385 534 535 Pr.53 OP shift amount
86 236 386 536 Pr.54 OPR torque limit value
87 237 387 537 Pr.55 Deviation counter clear signal output time
88 238 388 538 Pr.56 Speed designation during OP shift
89 239 389 539 Pr.57 Dwell time during OPR retry

Common to axes 1, 2, 3, and 4
1200 Md.1 In test mode flag
1201 1202 1203 1204 1205 1206 1207 1208 1209 1210 1211
(0) (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (Pointer No.)
1212 1217 1222 1227 1232 1237 1242 1247 1252 1257 1262 1267 1272 1277 1282 1287 Md.3 Start information
1213 1218 1223 1228 1233 1238 1243 1248 1256 1258 1263 1268 1273 1278 1283 1288 Md.4 Start No.
1214 1219 1224 1229 1234 1239 1244 1249 1254 1259 1264 1269 1274 1279 1284 1289 Md.5 Start (Hour)
1215 1220 1225 1230 1235 1240 1245 1250 1255 1260 1265 1270 1275 1280 1285 1290 Md.6 Start (Minute: second)
1216 1221 1226 1231 1236 1241 1246 1251 1256 1261 1266 1271 1276 1281 1286 1291 Md.7 Error judgment
1292 Md.8 Start history pointer
(0) (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (Pointer No.)
1293 1297 1301 1305 1309 1313 1317 1321 1325 1329 1333 1337 1341 1345 1349 1353 Md.9 Axis in which the error
1294 1298 1302 1306 1310 1314 1318 1322 1326 1330 1334 1338 1342 1346 1350 1354 Md.10 Axis error No.
1295 1299 1303 1307 1311 1315 1319 1323 1327 1331 1335 1339 1343 1347 1351 1355 Md.11 Axis error occurrence
1296 1300 1304 1308 1312 1316 1320 1324 1328 1332 1336 1340 1344 1348 1352 1356 Md.12 Axis error occurrence
1357 Md.13 Error history pointer
(0) (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (Pointer No.)
1358 1362 1366 1370 1374 1378 1382 1386 1390 1394 1398 1402 1406 1410 1414 1418 Md.14 Axis in which the
1359 1363 1367 1371 1375 1379 1383 1387 1391 1395 1399 1403 1407 1411 1415 1419 Md.15 Axis warning No.
1360 1364 1368 1372 1376 1380 1384 1388 1392 1396 1400 1404 1408 1412 1416 1420 Md.16 Axis warning
1361 1365 1369 1373 1377 1381 1385 1389 1393 1397 1401 1405 1409 1413 1417 1421 Md.17 Axis warning
1422 Md.18 Warning history pointer
1424 1425 Md.19 No. of write accesses to

Axis 1 Axis 2 Axis 3 Axis 4
800 801 900 901 1000 1001 1100 1101 Md.20 Current feed value
802 803 902 903 1002 1003 1102 1103 Md.21 Machine feed value
804 805 904 905 1004 1005 1104 1105 Md.22 Feedrate
806 906 1006 1106 Md.23 Axis error No.
807 907 1007 1107 Md.24 Axis warning No.
808 908 1008 1108 Md.25 Valid M code
809 909 1009 1109 Md.26 Axis operation status
810 811 910 911 1010 1011 1110 1111 Md.27 Current speed
812 813 912 913 1012 1013 1112 1113 Md.28 Axis feedrate
814 815 914 915 1014 1015 1114 1115 Md.29 Speed-position switching control positioning
816 916 1016 1116 Md.30 External input/output signal
817 917 1017 1117 Md.31 Status
818 819 918 919 1018 1019 1118 1119 Md.32 Target value
820 821 920 921 1020 1021 1120 1121 Md.33 Target speed
824 825 924 925 1024 1025 1124 1125 Md.34 Movement amount after near-point dog ON
826 926 1026 1126 Md.35 Torque limit stored value
827 927 1027 1127 Md.36 Special start data instruction parameter
828 928 1028 1128 Md.37 Special start data instruction No. setting
829 929 1029 1129 Md.38 Start positioning data No. setting value.
830 930 1030 1130 Md.39 In speed control flag
831 931 1031 1131 Md.40 In speed change processing flag
832 932 1032 1132 Md.41 Special start repetition counter
833 933 1033 1133 Md.42 Control system repetition counter
834 934 1034 1134 Md.43 Start data pointer being executed
835 935 1035 1135 Md.44 Positioning data No. being executed
836 936 1036 1136 Md.45 Block No. being executed
837 937 1037 1137 Md.46 Last executed positioning data No.
838 to 847 938 to 947 1038 to 1047 1138 to 1147 Md.47 Positioning data being executed
899 999 1099 1199 Md.48 Deceleration start flag

Axis 1 Axis 2 Axis 3 Axis 4
1500 1600 1700 1800 Cd.3 Positioning start No.
1501 1601 1701 1801 Cd.4 Positioning starting point No.
1502 1602 1702 1802 Cd.5 Axis error reset
1503 1603 1703 1803 Cd.6 Restart command
1504 1604 1704 1804 Cd.7 M code OFF request
1505 1605 1705 1805 Cd.8 External command valid
1506 1507 1606 1607 1706 1707 1806 1807 Cd.9 New current value
1508 1509 1608 1609 1708 1709 1808 1809 Cd.10 New acceleration time value
1510 1511 1610 1611 1710 1711 1810 1811 Cd.11 New deceleration time value
1512 1612 1712 1812 Cd.12 Acceleration/deceleration time change
during speed change, enable/disable selection
1513 1613 1713 1813 Cd.13 Positioning operation speed override
1514 1515 1614 1615 1714 1715 1814 1815 Cd.14 New speed value
1516 1616 1716 1816 Cd.15 Speed change request
1517 1617 1717 1817 Cd.16 Inching movement amount
1518 1519 1618 1619 1718 1719 1818 1819 Cd.17 JOG speed
1520 1620 1720 1820 Cd.18 Interrupt request during continuous
1521 1621 1721 1821 Cd.19 OPR request flag OFF request
1522 1523 1622 1623 1722 1723 1822 1823 Cd.20 Manual pulse generator 1 pulse input
1524 1624 1724 1824 Cd.21 Manual pulse generator enable flag
1525 1625 1725 1825 Cd.22 New torque value
1526 1527 1626 1627 1726 1727 1826 1927 Cd.23 Speed-position switching control movement
1528 1628 1728 1828 Cd.24 Speed-position switching enable flag
1529 1629 1729 1829 Not used
1530 1531 1630 1631 1730 1731 1830 1831 Cd.25 Position-speed switching control speed
1532 1632 1732 1832 Cd.26 Position-speed switching enable flag
1533 1633 1733 1833 Not used 1534 1535 1634 1635 1734 1735 1834 1835 Cd.27 Target position change value (new address)
1536 1537 1636 1637 1736 1737 1836 1837 Cd.28 Target position change value (new speed)
1538 1638 1738 1838 Cd.29 Target position change request flag
1539 1639 1739 1839 Not used
1540 1640 1740 1840 Cd.30 Simultaneous starting axis start data No.
(axis 1 start data No.)


1541 1641 1741 1841 Cd.31 Simultaneous starting axis start data No.
1542 1642 1742 1842 Cd.32 Simultaneous starting axis start data No.
1543 1643 1743 1843 Cd.33 Simultaneous starting axis start data No.
1549 1649 1749 1849 Cd.39 Teaching positioning data No.
1550 1650 1750 1850 Cd.40 ABS direction in degrees
Appendix - 103


2001 8001 14001 20001 Da.10 M code/condition data No.
positioning data No. 2003 8003 14003 20003 Not used 2004 2005 8004 8005 14004 14005 20004 20005 Da.8 Command speed
2006 2007 8006 8007 14006 14007 20006 20007 Da.6 Positioning address/movement
amount 2008 2009 8008 8009 14008 14009 20008 20009 Da.7 Arc address
Appendix - 104

Axis 1 Axis 2 Axis 3 Axis 4
Da.11 Shape
Da.12 Start data No.
26000 26050 27000 27050 28000 28050 29000 29050
Da.13 Specilal start instruction
Da.14 Parameter
26001 26051 27001 27051 28001 28051 29001 29051 2nd point
26002 26052 27002 27052 28002 28052 29002 29052 3rd point
to
26049 26099 27049 27099 28049 28099 29049 29099 50th point
Da.15 Condition target 26100 27100 28100 29100 Da.16 Condition operator
26102 26103 27102 27103 28102 28103 29102 29103 Da.17 Address
No. 1
26104 26405 27104 27405 28104 28405 29104 29405 Da.18 Parameter 1
26106 26107 27106 27107 28106 28107 29106 29107 Da.19 Parameter 2
Positioning data (Starting block data)
26110 to 26119 27110 to 27119 28110 to 28119 29110 to 29119 No. 2 26120 to 26129 27120 to 27129 28120 to 28129 29120 to 29129 No. 3 to 26190 to 26199 27190 to 27199 28190 to 28199 29190 to 29199 No. 10
26200 to 26299 27200 to 27299 28200 to 28299 29200 to 29299 Block start data
26300 to 26399 27300 to 27399 28300 to 28399 29300 to 29399 Condition data
26400 to 26499 27400 to 27499 28400 to 28499 29400 to 29499 Block start data
26500 to 26599 27500 to 27599 28500 to 28599 29500 to 29599 Condition data
26600 to 26699 27600 to 27699 28600 to 28699 29600 to 29699 Block start data
26700 to 26799 27700 to 27799 28700 to 28799 29700 to 29799 Condition data
26800 to 26899 27800 to 27899 28800 to 28899 29800 to 29899 Block start data
26900 to 26999 27900 to 27999 28900 to 28999 29900 to 29999 Condition data

Axis 1 Axis 2 Axis 3 Axis 4
Condition judgement target data of the condition data

[1] QD75P1/QD75P2/QD75P4

Appendix - 107
![Page 750 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [2] QD75D1/QD75D2/QD75D4](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-750.webp?w=400)
![Mitsubishi Electronics MELSEC-Q QD75D — [2] QD75D1/QD75D2/QD75D4 diagram (page 750)](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/fig-750-1.webp)
Appendix - 108
![Page 752 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [B]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-752.webp?w=400)
AFTER mode 12-63 AFTER mode (Explanation of positioning terms)
Basic parameters 1 5-20 Basic parameters 2 5-26 BCD (Explanation of positioning terms)
Appendix-69 Allowable circular interpolation error width
Appendix-71
( Pr.41 ) 5-43
Bias speed at start ( Pr.7 ) 5-26
Applicable system 2-5 Applicable wire size 3-2
Bias speed at start (Explanation of positioning terms) Appendix-71 BIN (Explanation of positioning terms)
Arc address ( Da.7 ) 5-68
Appendix-71 Bipolar drive constant-current system (Explanation of positioning terms) Appendix-72 Block 10-2
Auto tuning (Explanation of positioning terms)
Appendix-70 Automatic trapezoidal acceleration/deceleration (Explanation of positioning terms) ...Appendix-70 Automatic trapezoidal acceleration/deceleration processing method 12-81 Axis display LED 4-3 Axis error No. ( Md.10 , Md.23 ) 5-92,96
Block No. being executed ( Md.45 ) 5-108
Block start (Normal start) 10-2 Block start data 10-7 Block start data area (Nos. 7000 to 7004) 7-3 Buffer memory 7-2 Buffer memory (Explanation of positioning terms)
Axis error occurrence (Hour) ( Md.11 ) 5-92
Appendix-72 Buffer memory area configuration 7-5 BUSY (Explanation of positioning terms)
5-92
Axis error reset ( Cd.5 ) 5-112
Appendix-72 BUSY signal 3-14
Axis feedrate ( Md.28 ) 5-100
Axis in which the error occurred ( Md.9 ) 5-92 Axis in which the warning occurred ( Md.14 )
5-94 Axis monitor data 5-96
Cable clamp 4-9 CCW (Explanation of positioning terms)
Axis operation status ( Md.26 ) 5-98
Appendix-72 CHANGE signal (Explanation of positioning terms)
Axis stop signal 3-21 Axis to be interpolated ( Da.5 ) 5-62 Axis warning detection 5-102
Appendix-72 Circular interpolation (Explanation of positioning terms) Appendix-72 Combination of functions 3-12 Combination of main functions and sub functions
Axis warning No. ( Md.15 , Md.24 ) 5-94,98
Axis warning occurrence (Hour) ( Md.16 )... 5-94
3-12 Command in-position flag 5-102 Command in-position function 12-77
( Md.17 ) 5-94
Command in-position width ( Pr.16 ) 5-30
Backlash compensation amount ( Pr.11 ). 5-28
Command pulse (Explanation of positioning terms)
Backlash compensation (Explanation of positioning terms) Appendix-70 Backlash compensation function 12-11 Backup function (Explanation of positioning terms)
Appendix-72 Command pulse frequency 1-11
Command speed ( Da.8 ) 5-70
Common functions 3-8, 13-2
Appendix-70 Ball screw (Explanation of positioning terms)
Appendix-70
Index - 2
![Page 753 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [D]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-753.webp?w=400)
Communicating signals between QD75 and each module 1-12 Composite speed 5-32 Composite speed (Explanation of positioning terms) Appendix-72 Condition data 10-16 Condition operator 10-17
CW (Explanation of positioning terms)
Appendix-73 CW/CCW mode 5-23
D/A converter (Explanation of positioning terms)
Appendix-73 Data No. (Explanation of positioning terms)
Condition operator ( Da.16 ) 5-83
Condition start 10-10
Appendix-73 Data transmission process 7-6 Deceleration curve 12-96 Deceleration curve re-processing 12-96 Deceleration curve continuation 12-96 Deceleration ratio (Explanation of positioning terms) Appendix-73 Deceleration start flag ( Md.48 ) 5-108
Condition target ( Da.15 ) 5-83
Conditional JUMP 9-102 Configuration and roles of QD75 memory 7-2 Confirming the current value 9-16 Confirming the installation and wiring 4-14 Connection confirmation 4-14 Connector 4-3 Continuous operation interrupt program 6-37 Continuous path control 9-8 Continuous positioning control 9-7 Control data area 7-3 Control functions 3-4
Deceleration start flag valid ( Cd.41 ) 5-110 Deceleration stop 6-43 Deceleration time (Explanation of positioning terms) Appendix-74
Deceleration time 0 ( Pr.10 ) 5-27
Control system ( Da.2 ) 5-60
Deceleration time 1 ( Pr.28 ) 5-36
Control system repetition counter ( Md.42 )
Deceleration time 2 ( Pr.29 ) 5-36
5-108 Control unit (Explanation of positioning terms)
Deceleration time 3 ( Pr.30 ) 5-36
Deceleration time No. ( Da.4 ) 5-60
Appendix-72 Count method 1) machine OPR 8-16 Count method 2) machine OPR 8-18 CP control (Explanation of positioning terms)
Detailed parameters 1 5-28 Detailed parameters 2 5-36 Details of input signals (QD75 PLC CPU) 3-15 Details of output signals (PLC CPU QD75) 3-16 Deviation counter (Explanation of positioning terms) Appendix-74 Deviation counter clear 3-21 Deviation counter clear signal output time
Appendix-73
Creep speed ( Pr.47 ) 5-50
Creep speed (Explanation of positioning terms)
Appendix-73 Current feed value 9-16
Current feed value ( Md.20 ) 5-96
( Pr.55 ) 5-56
Current feed value (Explanation of positioning terms) Appendix-73
Deviation counter droop pulse amount 1-11 Differential driver common terminal (SG)
Current feed value during speed control ( Pr.21 )
5-32 Current loop mode (Explanation of positioning terms) Appendix-73
3-23, 4-3 Differential output type (Explanation of positioning terms) Appendix-74 Digital bus connection (Explanation of positioning terms) Appendix-74 Disposal instructions 4-15 DOG signal (Explanation of positioning terms)
Current speed ( Md.27 ) 5-98
Current value (Explanation of positioning terms)
Appendix-73
Appendix-74
Index - 3
![Page 754 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [E]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-754.webp?w=400)
DOS/V personal computer A-13 Drive unit (Explanation of positioning terms)
External command valid ( Cd.8 ) 5-114
External device connector 4-3 External dimension drawing Appendix-107
Appendix-74 Drive unit (Servo amplifier) A-21 Drive unit READY 3-21 Drive unit READY (Explanation of positioning terms) Appendix-74 Droop pulse (Explanation of positioning terms)
External input/output signal ( Md.30 ) 5-100
External I/O signal logic switching function...13-7 External I/O signal monitor function 13-8 External regenerative brake resistor (Explanation of positioning terms) Appendix-76
Appendix-75 Dwell time (Explanation of positioning terms)
Appendix-75 Dwell time (JUMP destination positioning data
F (Explanation of positioning terms)
Appendix-76 Fast OPR 8-20 Fast OPR (Explanation of positioning terms)
No.) ( Da.9 ) 5-70
Dwell time during OPR retry ( Pr.57 ) 5-56
Dynamic brake (Explanation of positioning terms)
Appendix-76 Fatal stop 6-42 Features of QD75 1-2 Feed pulse (Explanation of positioning terms)
Appendix-75
Electrical specifications 3-17 Electromagnetic brake (Explanation of positioning terms) Appendix-75 Electronic gear (Explanation of positioning terms)
Appendix-76 Feed screw (Explanation of positioning terms)
Appendix-76 Feedback pulse (Explanation of positioning terms)
Appendix-75 Electronic gear function 12-13 Emergency stop 6-42 Emergency stop (Explanation of positioning terms)
Appendix-76
Feedrate ( Md.22 ) 5-96
Fixed-feed (Explanation of positioning terms)
Appendix-77 Flash memory (Explanation of positioning terms)
Appendix-75 Encoder (Explanation of positioning terms)
Appendix-77 Flash ROM 7-2 Flash ROM write program 6-23
Appendix-75 Error and warning details 15-2 Error compensation method 12-14 Error correction (Explanation of positioning terms)
Flash ROM write request ( Cd.1 ) 5-110
Flat type motor (Pancake motor) (Explanation of positioning terms) Appendix-77 Flow of all processes 1-15 Flow of system operation 1-15 FLS signal (Explanation of positioning terms)
Appendix-76 Error detection signal 3-15 Error history 5-92 Error history pointer ( Md.13 ) 5-92 Error judgement ( Md.7 ) 5-90 Error reset (Explanation of positioning terms)
Appendix-77 For creating program 6-2 For installation 4-7 For maintenance 4-15 For restarting 6-41 For starting "fast OPR" 6-31 For starting "machine OPR" 6-30 For starting "major positioning control" 6-32 For starting "position-speed switching control"
Appendix-76 Error reset program 6-23 Execution data backup function 13-5 Execution prohibition flag 3-14 External command 3-21
External command function selection ( Pr.42 )
5-42 External command function valid setting program
6-33
6-12
Index - 4
![Page 755 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [I]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-755.webp?w=400)
For starting "speed-position switching control"
Incremental system (Explanation of positioning terms) Appendix-78 Independent positioning control 9-6 Inertia (Explanation of positioning terms)
6-32 For starting with external command signal... 6-36 For using stepping motor 1-22 For wiring 4-8 Forced stop 6-42 Front-loading speed switching mode 9-13 Functions for compensating the control 12-11 Functions to change the control details 12-34 Functions to limit the control 12-21 Function version Appendix-2
Appendix-78 Initialization program 6-24
Input signal logic selection ( Pr.22 ) 5-32
Input terminal (Explanation of positioning terms)
Appendix-79 Input/output interface internal circuit 3-22 Intentional stop 6-42 Interlock (Explanation of positioning terms)
Appendix-79 Internal circuit 3-22 Internal current consumption 3-3 Interpolation axis 9-21 Interpolation control 9-21 Interpolation operation (Explanation of positioning terms) Appendix-79
G code (Explanation of positioning terms)
Appendix-77 Gain (Explanation of positioning terms)
Appendix-77 GD
2 (Explanation of positioning terms) Appendix-77 General configuration of program 6-11 General image of system 2-2 GX Configurator-QP A-13, 2-4 GX Developer A-13
Interpolation speed designation method ( Pr.20 )
5-32 Interruption request during continuous operation
( Cd.18 ) 5-120
Inverter (Explanation of positioning terms)
Handling 4-5 Hardware stroke limit function 12-32 High-level positioning control 10-2
Appendix-79
JOG (Explanation of positioning terms)
Appendix-79 JOG operation 11-4 JOG operation acceleration time selection
Immediate stop 6-43
In speed change processing flag ( Md.40 )
5-106 In speed control flag 5-102
( Pr.32 ) 5-36
JOG operation deceleration time selection
In speed control flag ( Md.39 ) 5-106
( Pr.33 ) 5-36
In test mode flag ( Md.1 ) 5-86
JOG operation setting program 6-19 JOG operation start time chart 11-11 JOG operation timing and processing times
Inching movement amount ( Cd.16 ) 5-120
Inching operation setting program 6-19 Inching operation start time chart 11-23 Inching operation timing and processing times
11-6
JOG speed ( Cd.17 ) 5-120
11-19 Inching operation 11-17 Incremental encoder (Explanation of positioning terms) Appendix-78 Incremental system 9-15
JOG speed limit value ( Pr.31 ) 5-36
JOG start signal 3-16 JUMP instruction 9-102
Index - 5
![Page 756 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [M]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-756.webp?w=400)
M code output function 12-62 Machine feed value 9-16
kPPS (Explanation of positioning terms)
Appendix-79
Machine feed value ( Md.21 ) 5-96
Machine feed value (Explanation of positioning terms) Appendix-80 Machine OPR 8-4 Main functions 3-6 Major positioning controls 9-2 Manual control 11-2 Manual pulse generator 2-4 Manual pulse generator A-13 Manual pulse generator (Explanation of positioning terms) Appendix-80 Manual pulse generator 1 pulse input
Last executed positioning data No. ( Md.46 )
5-108 LED display functions 15-36 LEND 9-105 Limit switch (Explanation of positioning terms)
Appendix-79 Linear interpolation (Explanation of positioning terms) Appendix-80 List of block start data 5-74 List of condition data 5-80 List of configuration devices 2-4 List of control data 5-110 List of dedicated instructions 14-2 List of devices used 6-5 List of errors 15-6 List of functions 3-4 List of input/output signal details 3-20 List of input/output signals 3-14 List of monitor data 5-86 List of parameters 5-20 List of positioning data 5-58 List of warnings 15-30 Load inertia ratio (Explanation of positioning terms) Appendix-80 LOOP 9-104 Lower limit 3-20 Low-inertia motor (Explanation of positioning terms) Appendix-80
magnification ( Cd.20 ) 5-122
Manual pulse generator enable flag ( Cd.21 )
5-122
Manual pulse generator input selection ( Pr.24 )
5-36 Manual pulse generator operation 11-27 Manual pulse generator operation program
6-20 Manual pulse generator operation start time chart
11-34 Manual pulse generator operation timing and processing times 11-29 Master axis (Explanation of positioning terms)
Appendix-80 Max. connection distance 3-3 Max. output pulse 3-3 Mechanism of positioning control 1-7 Monitor data area 7-3 Movement amount after near-point dog ON
( Md.34 ) 5-104
M code (Condition data No., No. of LOOP to
Movement amount per pulse ( Pr.2 to Pr.4 )
LEND repetitions) ( Da.10 ) 5-70
5-20 Movement amount per pulse (Explanation of positioning terms) Appendix-81
M code (Explanation of positioning terms)
Appendix-80 M code OFF request 12-63
Movement amount per rotation ( Pr.3 ) 5-20
M code OFF request ( Cd.7 ) 5-112
Multi-phase pulse (Explanation of positioning terms) Appendix-81 Multiple axes simultaneous start control 10-20
M code ON signal 3-15 M code ON signal output timing 12-62
M code ON signal output timing ( Pr.18 )... 5-30
Index - 6
![Page 757 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [O]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-757.webp?w=400)
Multiple PLC 2-5 Multiplying rate setting (Explanation of positioning terms) Appendix-81
Operation pattern (Explanation of positioning terms) Appendix-82 Operation patterns 9-5 Operation timing and processing time during position-speed switching control 9-91 Operation timing and processing time during speed-position switching control (ABS mode)
Names of each part 4-3 NC language (Explanation of positioning terms)
Appendix-81 Near pass function 12-18 Near pass 12-18 Near-point dog (Explanation of positioning terms)
9-91 Operation timing and processing time during speed-position switching control (INC mode)
9-84 Operation timing and processing time of fast OPR
Appendix-81 Near-point dog method machine OPR 8-6 Near-point dog signal 3-20
8-21
OPR acceleration time selection ( Pr.51 ) ..5-54
New acceleration time value ( Cd.10 ) 5-116
OPR basic parameters 5-46 OPR complete flag 5-102
New current value 9-98
New current value ( Cd.9 ) 5-114
OPR deceleration time selection ( Pr.52 ) ..5-54
New current value (Explanation of positioning terms) Appendix-81
OPR detailed parameters 5-54
OPR direction ( Pr.44 ) 5-48
New deceleration time value ( Cd.11 ) 5-116
OPR dwell time ( Pr.49 ) 5-54
New speed value ( Cd.14 ) 5-118
OPR method 8-5
New torque value ( Cd.22 ) 5-122
OPR method ( Pr.43 ) 5-46
NEXT start 10-15 No. of control axes 3-2 No. of modules can be mounted 2-5 No. of occupied I/O points 3-3
OPR method (1): Near-point dog method 8-6 OPR method (2): Stopper method 1) 8-8 OPR method (3): Stopper method 2) 8-11 OPR method (4): Stopper method 3) 8-14 OPR method (5): Count method 1)
No. of pulses per rotation ( Pr.2 ) 5-20
8-16 OPR method (6): Count method 2)
No. of write accesses to flash ROM ( Md.19 )
5-94 NOP instruction 9-101 Normal start 10-7
8-18 OPR method (Explanation of positioning terms)
Appendix-82 OPR OFF request program 6-12 OPR parameter (Explanation of positioning terms)
OP (Explanation of positioning terms)
Appendix-82
Appendix-82 OPR request 8-2 OPR request (Explanation of positioning terms)
OP address ( Pr.45 ) 5-48
OP shift amount ( Pr.53 ) 5-56
Appendix-83 OPR request flag 5-102
OP shift function 12-8 OP shift function (Explanation of positioning terms)
OPR request flag OFF request ( Cd.19 )
Appendix-82 Operating principle 1-7
5-122
OPR retry ( Pr.48 ) 5-50
Operation pattern ( Da.1 ) 5-60
OPR retry function 12-4
Index - 7
![Page 758 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [P]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-758.webp?w=400)
OPR speed ( Pr.46 ) 5-48
PULSE/SIGN mode 5-23 Position control (Explanation of positioning terms)
OPR torque limit value ( Pr.54 )
Appendix-84 Position detection module (Explanation of positioning terms) Appendix-84 Position loop gain (Explanation of positioning terms) Appendix-84 Position loop mode (Explanation of positioning terms) Appendix-84 Position-speed switching control 9-89 Position-speed switching control speed change
5-56 Order of priority for stop process 6-44 Outline design of positioning system 1-9 Outline of installation, wiring and maintenance
4-2 Outline of OPR control 8-2 Outline of restarting 1-21 Outline of starting 1-18 Outline of stopping 1-20
register ( Cd.25 ) 5-124
Output signal logic selection ( Pr.23 ) 5-32
Position-speed switching control enable flag
Output terminal (Explanation of positioning terms)
( Cd.26 ) 5-126
Appendix-83 Override function 12-41 Override function (Explanation of positioning terms) Appendix-83 Override program 6-20
Position-speed switching latch flag 5-102 Position-speed switching signal 3-21 Positioning (Explanation of positioning terms)
Appendix-84
Positioning address/movement amount ( Da.6 )
5-62 Positioning complete (Explanation of positioning terms) Appendix-84 Positioning complete signal 3-15 Positioning complete signal (Explanation of positioning terms) Appendix-84
P rate (Explanation of positioning terms)
Appendix-83
Parameter ( Da.14 ) 5-77
Parameter (Explanation of positioning terms)
Appendix-83
Positioning complete signal output time ( Pr.40 )
Parameter 1 ( Da.18 ) 5-83
5-42 Positioning continued Appendix-85 Positioning control operation program 6-12 Positioning complete 9-6 Positioning data (Explanation of positioning terms)
Parameter 2 ( Da.19 ) 5-83 Parameter area 7-3 Parameter initialization program 6-22
Parameter initialization request ( Cd.2 ) 5-110
Performance specifications 3-2 Peripheral device A-13 Personal computer A-13 PFWRT 14-2 PG0 (Explanation of positioning terms)
Appendix-85 Positioning data area (Nos. 1 to 600) 7-3
Positioning data being executed ( Md.47 )
5-108
Appendix-83 PINIT 14-2 PLC CPU A-13 PLC CPU memo area 7-3 PLC CPU module 2-5 PLC READY signal 3-16 PLC READY signal [Y0] ON program 6-12
Positioning data No. being executed ( Md.44 )
5-108
Positioning operation speed override ( Cd.13 )
5-118 Positioning parameter (Explanation of positioning terms) Appendix-85 Positioning program examples 6-17
Index - 8
![Page 759 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Q]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-759.webp?w=400)
Positioning start (Explanation of positioning terms)
Appendix-85
Positioning start No. ( Cd.3 ) 5-112
Positioning start No. setting program 6-17 Positioning start program 6-12 Positioning start signal 3-16
Positioning starting point No. ( Cd.4 ) 5-112
9-91 • Operation timing and processing time during speed-position switching control (INC mode)
Appendix-85 Pulse (Explanation of positioning terms)
Appendix-85 Pulse generator (Explanation of positioning terms)
Appendix-85
Pulse output mode ( Pr.5 ) 5-22
Pulse output mode (Explanation of positioning terms) Appendix-85 Purpose and applications of positioning control
1-5
QD75 A-13 QD75 READY signal 3-15
Precautions · Index - 9
![Page 760 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [S]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-760.webp?w=400)
Setting the positioning data 9-22 Setting the torque limit function 12-25 Setting unit (Explanation of positioning terms)
READY (Explanation of positioning terms)
Appendix-86 Real-time AUTO tuning (Explanation of positioning terms) Appendix-86 Reference axis 9-22 Reference axis speed 5-33 Reference axis speed (Explanation of positioning terms) Appendix-86 Regeneration brake option (Explanation of positioning terms) Appendix-86 Relatively safe stop 6-42 Remote I/O station 2-5 Repeated start (FOR condition) 10-14 Repeated start (FOR loop) 10-13 Resolver (Explanation of positioning terms)
Appendix-87 SFC (Explanation of positioning terms)
Appendix-87
Shape ( Da.11 ) 5-77
Signal layout of connector 3-19 Signal name 3-14 Signals
Appendix-86
Restart command ( Cd.6 ) 5-112
Restart operation 6-39 Restart program 6-39 RLS signal (Explanation of positioning terms)
Appendix-86 Rotary table Appendix-86
Rotation direction setting ( Pr.6 ) 5-22
start data No.) ( Cd.30 ) 5-128
Simultaneous starting axis start data No. (Axis 2
start data No.)( Cd.31 ) 5-128
Simultaneous starting axis start data No. (Axis 3
Appendix-86 SERIAL No 1-22, Appendix-2 Servo amplifier (Explanation of positioning terms)
start data No.)( Cd.32 ) 5-128
Simultaneous starting axis start data No. (Axis 4
start data No.)( Cd.33 ) 5-128
Appendix-86 Servo lock (Explanation of positioning terms)
Skip command ( Cd.37 ) 5-130
Appendix-87 Servo ON (Explanation of positioning terms)
Skip function 12-59 Skip function (Explanation of positioning terms)
Appendix-87 Servomotor (Explanation of positioning terms)
Appendix-87 Skip operation program 6-14 Slave axis (Explanation of positioning terms)
Appendix-87 Setting data 5-2 Setting for the movement amount after near-point
Appendix-87 Slot 2-5 Software stroke limit lower limit value ( Pr.13 )
dog ON ( Pr.50 ) 5-54
Setting items for block start data 5-10 Setting items for condition data 5-11 Setting items for OPR parameters
5-28 Software stroke limit selection ( Pr.14 ) 5-28 Software stroke limit upper limit value ( Pr.12 )
5-6 Setting items for positioning data 5-7 Setting items for positioning parameters 5-4
5-28 Software stroke limit valid/invalid setting ( Pr.15 )
5-28
S-pattern acceleration/deceleration · Index - 10

S-pattern acceleration/deceleration processing method 12-81
Speed-position switching signal 3-21 Speed-position switching control mode (Explanation of positioning terms)... Appendix-88 Spiral interpolation 9-60 Standard speed switching mode 9-12
S-pattern proportion ( Pr.35 ) 5-38
Special start instruction ( Da.13 ) 5-77
Special start data instruction code setting value
Start Hour ( Md.5 ) 5-88
( Md.36 ) 5-106
Start complete (Explanation of positioning terms)
Special start data instruction parameter setting
Appendix-88 Start complete signal 3-15
value ( Md.37 ) 5-106
Special start repetition counter ( Md.41 )... 5-108
Start data No. ( Da.12 ) 5-77
Specifications of input/output interfaces 3-17 Specifications of input/output signals 3-14 Speed change 0 flag 5-102 Speed change function 12-34 Speed change program 6-20
Start data pointer being executed ( Md.43 )
5-108 Start details setting program 6-25 Start history 5-88 Start history pointer ( Md.8 ) 5-90
Speed change request ( Cd.15 ) 5-118
Start information ( Md.3 ) 5-88
Speed control (Explanation of positioning terms)
Appendix-88
Start No. ( Md.4 ) 5-88
Speed designation during OP shift ( Pr.56 )
Start positioning data No. setting value ( Md.38 )
5-56 Speed integral compensation (Explanation of positioning terms) Appendix-88 Speed limit function 12-21
5-106 Start program 6-27 Start program for high-level positioning control
Speed limit value ( Pr.8 ) 5-26
10-23 Starting axis (Explanation of positioning terms)
Speed limit value (Explanation of positioning terms) Appendix-88 Speed loop gain (Explanation of positioning terms)
Appendix-88
Status ( Md.31 ) 5-102
Appendix-88 Speed loop mode (Explanation of positioning terms) Appendix-88 Speed-position function selection ( Pr.150 ).. 5-34
Status (Explanation of positioning terms)
Appendix-88 Step function 12-54 Step function (Explanation of positioning terms)
Speed switching mode ( Pr.19 ) 5-32
Appendix-88 Step mode 12-55
Speed-position switching control (ABS mode)
Step mode ( Cd.34 ) 5-128
9-89 Speed-position switching control (INC mode)
Step operation program 6-21 Step out (Explanation of positioning terms)
9-82 Speed–position switching control (Explanation of positioning terms) Appendix-88 Speed-position switching control movement
Appendix-89 Step start information 12-55
Step start information ( Cd.36 ) 5-130
amount change register ( Cd.23 ) 5-124
Step valid flag ( Cd.35 ) 5-128
Speed-position switching control positioning
Stepping motor (Explanation of positioning terms)
amount ( Md.29 ) 5-100
Appendix-89 Stop cause 6-42
Speed-position switching enable flag ( Cd.24 )
5-124 Speed-position switching latch flag 5-102
Index - 11
![Page 762 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [T]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-762.webp?w=400)
Stop command processing for deceleration stop function 12-97 Stop command processing for deceleration stop
Target position change value (new speed)
( Cd.28 ) 5-126
Target speed ( Md.33 ) 5-104
selection ( Cd.42
) 5-110
Target value ( Md.32 ) 5-102
Stop group 1 sudden stop selection ( Pr.37 )
TEACH1 14-12 TEACH2 14-12 TEACH3 14-12 TEACH4 14-12 Teaching (Explanation of positioning terms)
5-38
Stop group 2 sudden stop selection ( Pr.38 )
5-38
Stop group 3 sudden stop selection ( Pr.39 )
Appendix-90 Teaching data selection ( Cd.38 ) 5-130 Teaching function 12-66 Teaching positioning data No. ( Cd.39 ) 5-130 Teaching program 6-21 Time chart
5-38 Stop process 6-42 Stop program 6-42 Stop settling time (Explanation of positioning terms) Appendix-89 Stop signal 3-21 STOP signal (Explanation of positioning terms)
Appendix-89 Stop with stopper (Explanation of positioning terms) Appendix-89 Stopper method 1) machine OPR 8-8 Stopper method 2) machine OPR 8-11 Stopper method 3) machine OPR 8-14 Stroke (Explanation of positioning terms)
Appendix-89 Stroke limit (Explanation of positioning terms)
Appendix-90 Sub functions 12-2 Sub functions specifically for machine OPR
12-4 Sudden stop 6-43 Sudden stop (Explanation of positioning terms)
Appendix-90
Sudden stop deceleration time ( Pr.36 ) 5-38
Synchronization flag (X1) 3-15 System control data 5-110 System monitor data 5-86
Appendix-90 Torque limit function 12-23
Tact time 12-87 Target position change function 12-72
Torque limit setting value ( Pr.17 ) 5-30
Target position change request flag ( Cd.29 )
Torque limit stored value ( Md.35 ) 5-104
5-126 Target position change value (new address)
Torque loop mode (Explanation of positioning terms) Appendix-90 Torque ripple (Explanation of positioning terms)
( Cd.27 ) 5-126
Appendix-90
Index - 12
![Page 763 of the Mitsubishi Electronics MELSEC-Q QD75D user manual — [Z]](/cdn/reader/0c/0c9140706abae27cc1a2500f46678b954a50a8176597f15aa36a672343e4e3e0/images/page-763.webp?w=400)
Tracking function (Explanation of positioning terms) Appendix-90 Turntable (Explanation of positioning terms)
Appendix-91 Types and roles of control data 5-16 Types and roles of monitor data 5-12 Types of data 5-2 Types of errors 15-2 Types of stop processes 6-43 Types of warnings 15-3
Unconditional JUMP 9-102
Unit magnification ( Pr.4 ) 5-20
Unit setting ( Pr.1 ) 5-20
Unit setting (Explanation of positioning terms)
Appendix-91 Upper limit 3-20
Valid M code ( Md.25 ) 5-98
Wait start 10-11 Warning (Explanation of positioning terms)
Appendix-91 Warning history 5-94 Warning history pointer ( Md.18 ) 5-94 Window (Explanation of positioning terms)
Appendix-91 Writing to the Flash ROM 13-6 WITH mode 12-62 WITH mode (Explanation of positioning terms)
Appendix-91 Workpiece A-13
X0 (QD75 READY) 3-15 X1 (Synchronization flag) 3-15 XY table (Explanation of positioning terms)
Appendix-91
Z phase (Explanation of positioning terms)
Appendix-91 Zero signal (Explanation of positioning terms)
Appendix-91
Index - 13

Index - 14

Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company. However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer’s discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on- site that involves replacement of the failed module. [Gratis Warranty Term]
The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range]
(1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc.,
which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product. (2) Even within the gratis warranty term, repairs shall be charged for in the following cases.
1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design. 2. Failure caused by unapproved modifications, etc., to the product by the user. 3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided. 4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced. 5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage. 6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi. 7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.
Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc. (2) Product supply (including repair parts) is not available after production is discontinued.
4. Exclusion of loss in opportunity and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation of damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not , compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
not lead to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault. (2) The Mitsubishi programmable logic controller has been designed and manufactured for applications in general
industries, etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or Public service purposes shall be excluded from the programmable logic controller applications. In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical applications, incineration and fuel devices, manned transportation, equipment for recreation and amusement, and safety devices, shall also be excluded from the programmable logic controller range of applications. However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi representative outlining the special requirements of the project, and providing that all parties concerned agree to the special circumstances, solely at the users discretion.

Microsoft Windows, Windows NT are registered trademarks of Microsoft Corporation in the United States and other countries. Other company and product names herein may be either trademarks or registered trademarks of their respective owners.



User's Manual
QD75-U-S-E
MODEL
13JR09
CODE
SH(NA)-080058-H(0506)MEE
HEAD OFFICE : 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212,JAPAN NAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| P2 | (P1≤P2) | p.173 | |
| E0H | Axes 2, 3, and 4 selected | p.173 | |
| P1 | (P1≤P2) | p.173 | |
| B0H | Axes 1, 2, and 4 selected | p.173 | |
| C0H | Axes 3 and 4 selected | p.173 | |
| D0H | Axes 1, 3, and 4 selected | p.173 | |
| X47 | ABS data bit 0 | p.589 | |
| X48 | ABS data bit 1 | p.589 | |
| X49 | Transmission data READY flag | p.589 | |
| Y50 | Servo ON signal | p.589 | |
| Y51 | ABS transfer mode | p.589 | |
| Y52 | ABS request flag | p.589 | |
| X7 | is turned ON. | p.624 | |
| QD75 | Even if the reference axis operates in reverse direction with | p.691 |
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Parameter | The PLC CPU power was turned OFF or the PLC CPU was reset, etc., during flash ROM writing, which deleted the data in the flash ROM. Initialize the parameters, and reset the required parameters. (Refer to Section 13.2 "Parameter initialization function" for details.) | p.734 | |
| Parameter | Set the " Cd.2 Parameter initialization request" to "1". (Refer to Section 13.2 "Parameter initialization function" for details.) | p.734 | |
| Parameter | The parameter may have been overwritten in the sequence program. Review the sequence program. | p.734 | |
| Hardware stroke limit | In the QD75, deceleration stops are executed after the machine exceeds hardware stroke limit range. Because of this, more time is required for the deceleration stop as the speed increases, and the overrun becomes larger. (The deceleration time becomes shorter at lower speeds, so the overrun becomes smaller.) | p.734 | |
| Hardware stroke limit | Use a "JOG operation", " Inching operation" or "Manual pulse generator operation" to return the machine to inside the hardware stroke limit range. (When the hardware stroke limit range is exceeded, positioning will not start toward inside the range even when so commanded. Once the range is exceeded, a return to inside the range can only be executed using a "JOG operation", "Inching operation" or "Manual pulse generator operation".) | p.734 | |
| Degree | Designate "360.000" in the INC control. The motor will make exactly one rotation. | p.734 | |
| Movement amount per pulse | Set "movement amount per pulse" in the QD75 using the three parameter values of Pr.2 to Pr.4 . Try setting the values following the explanations for each parameter. | p.734 | |
| Override | It will be valid. | p.734 | |
| Override | It will still be valid. | p.734 | |
| Override | Set the " Cd.13 Positioning operation speed override" to "100". | p.734 | |
| Error compensation | Reset Pr.3 and Pr.2 in the following order. 1) Calculate "8192/8000 × 10081230/10081234". 2) Obtain the reduced value. 3) Set the numerator in " Pr.3 Movement amount per rotation", and the denominator in " Pr.2 No. of pulses per rotation". | p.736 | |
| OPR | The near-point dog must be set to turn OFF at a position after the OP is passed. (When the machine OPR is started on the near-point dog on in a count-method machine OPR, the machine enters a normal machine OPR operation after returning to the near-point dog OFF region.) (If the near-point dog is turned OFF before the OP, and the machine OPR is started between the near-point dog OFF position and the OP, the machine will mistakenly interpret that its current position is before the near-point dog ON position, and it will pass over the OP and continue moving.) | p.736 | |
| OPR | Carry out the following measures. 1) Separate the near-point dog signal and zero signal detection positions. 2) Lower the values in " Pr.46 OPR speed" and " Pr.47 Creep speed". 3) Confirm whether the zero signal and near-point dog signal turn ON normally. 4) Check that there is no play (backlash) in the machine system. | p.736 | |
| OPR | A "Hardware stroke limit error" will occur and the operation will not be carried out. (The machine will interpret any position where the near- point dog is ON as being within the working range, and that the upper/lower limit is ON.) | p.736 | |
| OPR | They are possible. In this case, the position where the power is turned ON is handled as the current feed value "0". | p.736 | |
| OPR | The OPR request flag turns ON in the following cases. 1) When the power is turned ON. 2) When the PLC READY signal [YO] turns from OFF to ON. 3) When an OPR is carried out. 4) When the servo amplifier power is turned OFF. If no problem is found when the above are checked, then it is possible that the communication is being interrupted by "a fault in the bus cable", "noise influence", etc. | p.736 | |
| OPR | Check whether the drive unit READY signal is weak or the power supply is unstable. | p.736 | |
| Start | After the BUSY signal turns ON, there is no problem with turning [Y10] OFF before the BUSY signal turns OFF. (The QD75 detects the rising edge (OFF ON) of the positioning start signal [Y10].) | p.737 | |
| Start | Check the " Md.26 axis operation status" and " Md.23 axis error No". | p.737 | |
| Stop | The signal should be turned ON at 4ms or more. (If possible, set the signal so it does not turn ON only momentarily, but instead stays ON until the BUSY signal turns OFF. This will keep the stop signal from skipping.) | p.737 | |
| Stop | Set "1: Sudden stop" in the parameter from Pr.37 to Pr.39 corresponding to the stop group, and reduce the setting value of " Pr.36 Sudden stop deceleration time". | p.737 | |
| Stop | The operation will not change. Even if the same stop factor is input again during the deceleration stop, it will be ignored. The same deceleration stop process used when the stop signal was first input will be continued. (This also applies for Pr.37 and Pr.38 .) | p.737 | |
| Circular interpolation | The address designation may be incorrect. When carrying out INC system circular interpolation, designate the relative addresses from the starting point of both the center point and end point. | p.737 | |
| Speed-position switching control | No. The speed for the speed control and position control cannot be set differently. | p.737 | |
| JOG operation | Either of the following is possible. 1) The sequence program may be incorrect. Check by creating a test program in which the JOG start signal is turned ON only. 2) If the machine is hitting something when the torque setting is low, it may be trying to move by JOG operation in the opposite direction. In this case, the machine will start moving only after the internal droop pulses have been reached 0 in the counter, even if the JOG start signal has been turned ON. This makes it seem that the response is slow. | p.737 | |
| JOG operation | The " Pr.31 JOG speed limit value" may be larger than the " Pr.8 Speed limit value". Review the parameters and carry out the JOG operation again. | p.738 | |
| JOG operation | If a value other than "0" is set for " Cd.16 Inching movement amount", the inching operation is carried out and the positioning complete signal turns ON. Confirm that the " Cd.16 Inching movement amount" is set to "0". | p.738 | |
| Manual pulse generator operation | Not possible. (The QD75 counts 1, 0, 1, 0.) | p.738 | |
| Manual pulse generator operation | Other manual pulse generators can be used if they conform to Section 3.4 "Specifications for input/output interfaces with external devices." | p.738 | |
| Manual pulse generator operation | This is possible if the system conforms to the electrical specifications. | p.738 | |
| Current value changing | The BUSY signal may remain if the scan time is long. Use a complete signal to check whether the current value changing has been executed. | p.738 | |
| QD75 READY signal | "A parameter error" has occurred. Confirm the error No. in the error history, and correct the parameter. | p.738 | |
| M code ON signal | The QD75 checks the M code ON signal OFF request every "1.8ms", so there is a possibility that the M code ON signal OFF may be delayed by a maximum of "1.8ms" after the M code ON signal ON, even if an M code ON signal OFF request is set. | p.738 | |
| Deviation counter clear | The time set in " Pr.55 Deviation counter signal output time". (Initial value: 11 ms) | p.738 | |
| Deviation counter clear | A signal is not output. The only time the QD75 outputs a deviation counter clear signal is for a machine OPR. | p.738 | |
| Deviation counter clear | The QD75 does not output a deviation counter clear signal except for machine OPR. | p.738 | |
| Module | The internal parameters of the QD75 may be different. Check if the QD75 READY signal [X0] turns ON when the PLC READY signal [Y0] turns ON. When the PLC READY signal is ON but the QD75 READY signal is OFF, the parameter error has occurred. Check the error code and modify the parameter with the error. | p.738 | |
| Motor | The parameter settings on the QD75 side may not match those on the servo side. Check the parameter settings. | p.738 | |
| Motor | The speed shown on the QD75 monitor is calculated from the number of pulses output from the module. Thus, the actual motor speed cannot be monitored. (" Md.22 Feedrate" monitors the commanded speed. It does not show the actual motor speed.) | p.738 | |
| Error/warning | Backlash compensation value 0 ≤ 255 Movement amount per pulse Setting is not possible if the above equation is not satisfied. Adjust by setting " Pr.4 Unit magnification" to 10-fold (or 100-fold, or 1000-fold), and setting " Pr.2 Movement amount per rotation" to 1/10 (or 1/100, or 1/1000). | p.739 | |
| Error/warning | The hardware stroke limit wiring has probably not been carried out. Refer to Section 12.4.4 "Hardware stroke limit function" for details, and wire accordingly. | p.739 | |
| Error/warning | A value besides "0" or "1" may be set in the " Pr.56 Speed designation during OP shift". Review the set sequence program, and reset the correct parameters. | p.739 | |
| Error/warning | The QD75 starts the deceleration stop process when the stop signal ON is detected. Thus, the machine interprets that "positioning is still being executed" immediately after the stop signal ON. Even if the start signal is turned ON at that time, the start request will be ignored and warning 100 will occur. | p.739 | |
| Error/warning | The warning occurs only at those times mentioned at the left. Because this is a warning, there is no problem if the operation can be continued without resetting the error. (When the speed is changed using the override, the new value will not be reflected on the data being executed, but will be reflected from the next start.) | p.739 | |
| Positioning complete signal | Depending on the stop occurrence factor, positioning may have not been completed normally. Check the axis monitor " Md.26 Axis operation status" after the BUSY signal has turned OFF. Stop : The stop signal has turned ON during positioning. Check the condition under which the stop signal (Y stop, external stop) turns ON. Error occurrence : An error has occurred during positioning. Check the error occurrence factor from " Md.23 Axis error No.". | p.739 | |
| Positioning complete signal | The setting value of the detailed parameter 2 "Positioning complete signal output time" is 0 or shorter than the scan time. Using the sequence program, set the time when the signal can be detected securely. | p.739 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.