-QD64D2 -GX Configurator-CT (SW0D5C-QCTU-E)






(Read these precautions before use.)
Before using this product, please read this manual carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product. For the safety precautions of the programmable controller system, please read the User's Manual for the CPU module.
In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION".
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
Always follow the precautions of both levels because they are important to personal safety. Please save this manual to make it accessible when required and always forward it to the end user.
WARNING
Do not write data to "read-only area" or "reserved area" in the buffer memory of the intelligent function module. Also do not turn ON/OFF the "reserved" signal in I/O signals to the programmable controller CPU. Doing any of these operations may cause a malfunction of the programmable controller system.
When a transistor for external output fails, the output may be ON or OFF status. Create a circuit for monitoring output signal that may lead to serious accident.
Do not install the control lines and/or pulse input wiring together with the main circuit or power lines, and also do not bring them close to each other. Keep a distance of 150mm (5.91 inch) or more between them. Failure to do so may cause a malfunction due to noise.
CAUTION
Use the programmable controller in the environment conditions given in the general specifications of the User's Manual for the CPU module. Failure to do so may cause an electric shock, fire, malfunction, or damage to or deterioration of the product.

CAUTION
While pressing the installation lever located at the bottom of the module, fully insert the module fixing projection into the fixing hole in the base unit and press the module using the hole as a fulcrum. Incorrect module mounting may cause a malfunction, failure, or drop of the module. In an environment of frequent vibrations, secure the module with screws.
The screws must be tightened within the specified torque range. If the screw is too loose, it may cause a drop, short circuit, or malfunction. Excessive tightening may damage the screw and/or the module, resulting in a drop, short circuit or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the module. Failure to do so may cause damage to the product.
Do not directly touch any conductive part or electronic part of the module. Doing so may cause a malfunction or failure of the module.
CAUTION
For wiring and connection, properly crimp or solder the connector with the tools specified by the manufactures and attach the connector to the module securely.
Be careful to prevent foreign matter such as dust or wire chips from entering the module. Failure to do may cause a fire, failure or malfunction.
A protective film is attached to the module top to prevent foreign matter such as wire chips from entering the module during wiring. Do not remove the film during wiring. Be sure to remove it for heat dissipation before system operation.
Be sure to place the cables connected to the module in a duct or clamp them. If not, dangling cables may swing or inadvertently be pulled, resulting in damage to the module and/ or cables, or malfunctions due to poor cable connection.
When disconnecting the cable, do not pull it by holding the cable part. Disconnect the cable with connector with holding the connector plugged into the module. Pulling the cable part with the cable still connected to the module may cause a malfunction or damage to the module and/or cable.

CAUTION
Always ground the shielded cable on the module side. Failure to do may cause a malfunction.
Correctly wire cables to the module after checking the rated voltage and terminal layout of the product. Connecting a voltage different from the rated voltage or incorrect wiring may result in a fire or failure.
CAUTION
Do not disassemble or remodel each of the modules. Doing so may cause failure, malfunctions, personal injuries and/or a fire.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the module. Not doing so may result in a failure or malfunction of the module.
Do not mount/remove the module onto/from the base unit more than 50 times (IEC 61131-2 compliant), after the first use of the product. Doing so may cause malfunctions.
Do not touch the terminal while the power is ON. Failure to do may cause a malfunction.
Be sure to shut off all phases of the external power supply used by the system when cleaning the module or retightening the terminal or module fixing screws. Not doing so may result in a failure or malfunction of the module. If the screw is too loose, it may cause a drop, short circuit or malfunction. Excessive tightening may damage the screw and/or the module, resulting in a drop, short circuit or malfunction.
Before handling the module, touch a grounded metal object to discharge the static electricity from the human body. Not doing so may result in a failure or malfunction of the module.
CAUTION
When disposing of this product, treat it as industrial waste.

(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident; and ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general
industries. MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT. ("Prohibited Application") Prohibited Applications include, but not limited to, the use of the PRODUCT in; • Nuclear Power Plants and any other power plants operated by Power companies, and/or any
other cases in which the public could be affected if any problem or fault occurs in the PRODUCT. • Railway companies or Public service purposes, and/or any other cases in which establishment of
a special quality assurance system is required by the Purchaser or End User. • Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as
Elevator and Escalator, Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other applications where there is a significant risk of injury to the public or property.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are required. For details, please contact the Mitsubishi representative in your region.

* The manual number is given on the bottom left of the back cover.
Japanese Manual Version SH-080725-D
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any licenses. Mitsubishi
Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a
result of using the contents noted in this manual.
A - 5


Compliance with the EMC and Low Voltage Directives
To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller (EMC and Low Voltage Directives compliant) into other machinery or equipment, refer to Chapter 9 "EMC AND LOW VOLTAGE DIRECTIVES" of the QCPU User's Manual (Hardware Design, Maintenance and Inspection). The CE mark, indicating compliance with the EMC and Low Voltage Directives, is printed on the rating plate of the programmable controller.
For the compliance of this product with the EMC and Low Voltage Directives, refer to Section 4.4.1 Wiring precautions.

This manual describes the type QD64D2 4Mpps capable high-speed counter module using the following generic terms and abbreviations, unless otherwise specified.
The following are included in the package.

This User's Manual describes the specifications, handling, and programming methods for the type QD64D2 4Mpps capable high-speed counter module used together with the MELSEC-Q series CPU module.
The QD64D2 has the following input methods.
For details of the input methods, refer to Section 5.1.
Figure 1.1 shows the general operation of the QD64D2.
Reading/writing I/O signal and buffer memory
CH1
Coincidence signal output (2 points)
Coincidence signal output (2 points)
1) Pulses to be input to the QD64D2 are counted. 2) Preset value and count value can be latched with external control signal. 3) Status of the I/O signal and buffer memory of the QD64D2 can be checked with the sequence program. Also, start/stop of a count, preset, and coincidence output can be performed. 4) When a counter value matches with the set value, an interrupt request can be issued to the programmable controller CPU. 5) The present value is compared with comparison point setting value and the coincidence signal can be output.
Figure 1.1 General operation of the QD64D2

This section describes the features of the QD64D2.
(1) Counting at the maximum counting speed of 4Mpps is possible. (In 4
multiples of 2 phases) Since the QD64D2 can be used for high-resolution encoder (e.g. linear scale), the equipment can improve position detection accuracy and a workpiece can be moved at high-speed.
Count values can be stored in 32-bit signed binary.
Pulse input can be selected from 1 multiple of 1 phase, 2 multiples of 1 phase, 1 multiple of 2 phases, 2 multiples of 2 phases, 4 multiples of 2 phases, and CW/CCW.
Either of the following counter formats can be selected.
(a) Linear counter format
From -2147483648 to 2147483647 can be counted and an overflow can be detected when the count range is overrun.
(b) Ring counter format
Counts are repeatedly executed between the ring counter upper limit value and ring counter lower limit value.
The QD64D2 can compare the present value and comparison point, notify the comparison result with input signal, and start an interrupt program when they match. It also mounts 2-point external coincidence output for each channel, which permits controlling external devices at high-speed.
According to application, select the coincidence output function or continuous comparison function.
(a) Coincidence output function
Set 1 as the coincidence detection point for each point to compare it with the present value. Reset the coincidence output signal or change the coincidence detection point with the sequence program. Controlling equipment according to the operating status, such as change of the coincidence detection point according to condition, is possible.

(b) Continuous comparison function
Set from 1 to 16 as the coincidence detection point for each point to compare it with the present value (Only 1 point can be compared simultaneously). Whenever a coincidence is detected, the coincidence output signal is reset or the coincidence detection point is changed automatically. If this function is used when the coincidence detection point is predetermined, the sequence program can be reduced, which brings improvement in takt time.
continuous comparison function) By using the coincidence output test function, wiring of the coincidence output terminals (EQU1, EQU2) and operations can be checked without count operation.
The present value when the preset command (Y04) is input or the preset input terminal (PRST) is turned ON can be overwritten to preset value.
The present value when the latch counter execution command (Y07) is input or the latch counter input terminal (LATCH) is turned ON can be latched.
control signal Since the QD64D2 is independent of scan time of the programmable controller CPU, disparity in a span before executing the preset function/latch counter function can be lessen.
(10)Fuse blown at external output part is detectable.
The QD64D2 can detect fuse blown at external output part and notify it with the blown fuse detection flag (X1F) and LED display on it.
The QD64D2 setting can be performed on screen by using GX Configurator-CT sold separately. Thus, the number of sequence programs results in decreasing and checking a setting status or operation status of modules easily.

CHAPTER2 SYSTEM CONFIGURATION
This chapter describes system configurations for the QD64D2.
This section describes the applicable systems.
(a) When mounted with a CPU module
The table below shows the CPU modules and base units applicable to the QD64D2 and quantities for each CPU model. Depending on the combination with other modules or the number of mounted modules, power supply capacity may be insufficient. Pay attention to the power supply capacity before mounting modules, and if the power supply capacity is insufficient, change the combination of the modules.
Table 2.1 Applicable modules and the number of mountable modules

CPU type CPU model Main base unit Extension base
Q00JCPU Up to 8 Q00CPU Up to 24 Q01CPU


Table 2.1 Applicable modules and the number of mountable modules (Continued)
CPU type CPU model Main base unit Extension base
* 1 Limited within the range of I/O points for the CPU module. * 2 Can be installed to any I/O slot of a base unit. * 3 For the coincidence detection interrupt function, use the Basic model QCPU of function version B
or later. * 4 The coincidence detection interrupt function is not supported. * 5 Connection of extension base units is not available with any safety CPU.
For the use of the C Controller module, refer to C Controller Module User's Manual.

(b) Mounting to a MELSECNET/H remote I/O station
The following table shows network modules that can be mounted to the QD64D2, the number of mountable network modules, and applicable base units.
The QD64D2 module can be mounted into any I/O slots*1 on the applicable base unit. However, the power capacity may be insufficient depending on the combination with the other mounted modules and the number of mounted modules. Be sure to check the power capacity when mounting the modules.
Table 2.2 Mountable network modules, No. of mountable modules, and mountable base unit

* 1 Limited within the range of I/O points for the network module. * 2 Can be installed to any I/O slot of a base unit. * 3 The coincidence detection interrupt function is not supported.
The Basic model QCPU or C Controller module cannot create the MELSECNET/ H remote I/O network.

The QD64D2 of first released version to function version B supports multiple CPU system. When using the QD64D2 in a multiple CPU system, refer to the following manual first.
QCPU User's Manual (Multiple CPU System)
(a) Intelligent function module parameters
Write intelligent function module parameters to only the control CPU of the QD64D2.
Relation between the system using the QD64D2 and software package is shown in the following table. GX Developer is necessary when using the QD64D2.
Table 2.3 Software package version
GX Developer GX Configurator-CT GX Works2
Q00J/Q00/Q01CPU Single CPU system Version 7 or later
Version 1.10N or later Multiple CPU system Version 8 or later Q02/Q02H/Q06H/
Single CPU system Version 4 or later Version 1.08J or later Multiple CPU system Version 6 or later
Q02H/Q06HCPU Single CPU system Version 8.68W or later
Q12PH/Q25PHCPU Single CPU system Version 7.10L or later Multiple CPU system Q12PRH/
Q25PRHCPU Redundant system Version 8.45X or later
Single CPU system Version 8.76E or later
Version 1.28AE or later
Q04UDH/
Version 8.48A or later Multiple CPU system
Q10UDH/
Single CPU system Version 8.76E or later Multiple CPU system
Version 1.08J or later
Single CPU system Version 8.62Q or later Multiple CPU system
Q03UDE/Q04UDEH/
Q06UDEH/Q13UDEH/
Version 8.68W or later Multiple CPU system
Q10UDEH/
Single CPU system Version 8.76E or later Multiple CPU system
Q50UDEH/
Single CPU system Use prohibited Use prohibited Version 1.31H or later Multiple CPU system
When mounted to the MELSECNET/H remote I/
O station Version 6 or later Version 1.28AE or later Use prohibited
The connector is not included with the QD64D2. Purchase it with reference to Section 4.3.

2.2 About Use of the QD64D2 with Redundant CPU
This section explains how to use the QD64D2 with the Redundant CPU.
GX Configurator-CT cannot be used when accessing the Redundant CPU via an intelligent function module on an extension base unit from GX Developer. Connect a personal computer with a communication path indicated below.

2 Connecting to a programmable controller CPU via an intelligent function module (Ethernet module, MELSECNET/H module, or CC-Link module) on the main base unit
Figure 2.1 Communication path which GX Configrator-CT can use
The coincidence detection interrupt function is not available.

2.3 About Use of the QD64D2 on the MELSECNET/H Remote I/O Station
This section explains how to use the QD64D2 on the MELSECNET/H remote I/O station.
(1) Number of QD64D2 that can be installed when the remote I/O station is
used Refer to Section 2.1 concerning the number of the QD64D2 that can be installed when the remote I/O station is used.
(a) The coincidence detection interrupt function cannot be used.
(b) When the QD64D2 is used on the MELSECNET/H remote I/O station, a delay will
occur due to the link scan time. Therefore, fully verify that there will be no problem with controllability in the target system.
(Example) When processing is executed using the counter value input by a sequence program, variations will occur due to a delay in the link scan time.
2.3 About Use of the QD64D2 on the MELSECNET/H Remote I/O Station 2 - 6

2.4 How to Check the Function Version/Serial No./Software Version
The rating plate is situated on the side face of the QD64D2.

Figure 2.2 Checking the serial No. and function version (rating plate)
The serial No. on the rating plate is also indicated on the front of the module (lower part).

Figure 2.3 Display on the front of the module
The serial number is displayed on the front of the module from August 2008 production. Products manufactured during switching period may not have the serial number on the front of the module.

Information List) To display the screen for checking the serial number and function version, select
[Diagnostics] [System monitor] and click the Product Inf. List button in GX Developer.

Figure 2.4 System monitor
(a) Production number display
Since the QD64D2 does not support the production number display, "-" is displayed.
The serial No. displayed in the Product Information List of GX Developer may be different from the one on the rating plate and the front of the module.
management information of the product. • The serial No. in the Product Information List of GX Developer indicates
the functional information on the product, which is updated when a new function is added.
Serial number · Function · version

The software version of GX Configurator-CT can be checked GX Developer's "Product information" screen.
GX Developer [Help] [Product information]

(In the case of GX Developer Version 8)
Figure 2.5 [Product information] screen of GX Developer
[Operating procedure] · Software version

This chapter describes the performance specifications of the QD64D2, I/O signals to the programmable controller CPU, specifications of the buffer memory. For general specifications of the QD64D2, refer to the User's Manual for the CPU module.
The following table shows the performance specifications of the QD64D2.
Table 3.1 Performance specifications of the QD64D2
Number of channels 2 channels
Phase 1-phase input, 2-phase input
EIA Standard RS-422-A Differential line driver level
Signal level ( A, B)
(AM26LS31 (manufactured by Texas Instruments Incorporated) or equivalent)
Counting speed (max.)
2 multiples of 1 phase, 2 multiples of 2 phases: 2Mpps
1 multiple of 1 phase, 1 multiple of 2 phases, CW/CCW: 1Mpps
Counting range 32-bit signed binary (-2147483648 to 2147483647)
Addition method, subtraction method
linear counter format, ring counter format
preset counter function, latch counter function
0.5 0.5
(Duty ratio 50 %)
(Minimum phase difference for 2-phase input: 0.25 s)
For details, refer to Section 3.1.1
Comparison range 32-bit signed binary
Setting value < Count value
Setting value = Count value
Setting value > Count value
Interrupt With coincidence detection interrupt function
24VDC 2 to 5mA Count value latch
Coincidence output Transistor (sinking type) output: 2 points/channel
12/24VDC 0.5 A/point 2 A/common
Derating Applied (refer to Section 3.1.2 )
Number of occupied I/O points 32 points (I/O assignment: Intelligent 32 points)
5VDC internal current consumption 0.53 A
Weight 0.16 kg
* 1 Note that counting a pulse whose phase difference between phase A and phase B is small may
result in a count error. For the relation of phase difference between phase A and phase B, refer to Section 3.3.1. * 2 The maximum counting speed is determined in the pulse input mode.
Counting speed cannot be changed.

The relation indicated below is for each pulse input mode at the maximum counting speed. Pulse input waveform that does not reach to the maximum counting speed is also applicable.
(a) At 1-phase input
Pulse input waveform at 1-phase input input needs to satisfy the following conditions (duty ratio of 50%).
t (=tH+tL) = 1.0 s tH, tL = 0.5 s (= 0.5 t)
tH tL
Figure 3.1 Pulse input waveform at 1-phase input
(b) At 2-phase input
Pulse input waveform at 2-phase input needs to satisfy both the condition at 1- phase input and the condition below. t1, t2, t3, t4 = 0.25 s (= 0.25 t)
0.1V -0.1V
L level Differential voltage
0.1V 0.1V -0.1V
Figure 3.2 Pulse input waveform at 2-phase input 1
0.1V -0.1V
L level Differential voltage
B
Figure 3.3 Pulse input waveform at 2-phase input 2

0 10 20 30 40 50
Figure 3.4 Derating chart
This section explains conditions for each counter value comparison function selection.
Take care so that the ratio of the number of points that external coincidence output (ON) is executed to the number of external coincidence output points of the module (4 points) does not exceed the ON ratio in Figure 3.4.
The number of points that external coincidence output
100 [%] ON ratio [%]
Take care so that the ratio of continuous comparison No. m ON time setting (Un\G52, Un\G102) (t1) to the time from start of coincidence output to the next coincidence output (t2) in Figure 3.5 may not exceed the ON ratio in Figure 3.4. (For interval of the continuous comparison No. m point n setting that decides t2, refer to Section 5.3.2.)
ON ratio [%] 100 [%] t1[ms]
Coincidence output No. m terminal
Figure 3.5 Relationship between ON time setting in the case of the continuous comparison function (t1) and the time from start of
coincidence output to the next coincidence output (t2)
![Page 28 of the Mitsubishi Electronics MELSEC-Q Counter Module (QD64D2) user manual — t2[ms] (](/cdn/reader/92/92b7e7cbdd0998367f9879cdb7e62a6fcd0990ef3093e1ce0c853520a461033d/images/page-28.webp?w=400)
(3) When (CH1 or CH2) is the coincidence output function and (CH2 or CH1)
is the continuous comparison function Take care so that the addition of the ratio of above (1) "When all channels are the coincidence output function" in the CH where the coincidence output function is set and a value when the ratio of above (2) "When all channels are the continuous comparison function" in the CH where the continuous comparison function is set is divided by 2 may not exceed the ON ratio in Figure 3.4
Ratio of above (2) "When all channels are the continuous comparison function" [%]
Ratio of above (1) "When all channels are the coincidence output function" [%]
The number of points that external coincidence output (ON) is executed
(
+ 100 [%] (
(
3 - 4 3.1 Performance Specifications 3.1.2 Derating chart

The following table shows the functions of the QD64D2. I/O numbers (X/Y) and buffer memory addresses in Description describe only for channel 1. For I/O numbers (X/Y) of channel 2 and buffer memory addresses, refer to Section 3.3.1.
Table 3.2 Function list of the QD64D2
Function *1 Description Reference
Linear counter function Counts within the range from -2147483648 to 2147483647.
An overflow occurs when a count exceeds the count range. Section 5.2.1
Ring counter function Repeats a count between the ring counter upper limit value
and the lower limit value. Section 5.2.2
Compares preset coincidence detection point of an arbitrary
channel with the present counter value and outputs the
Section 5.3.1
counter value coincidence.
Compares any of preset coincidence detection points of an
arbitrary channel with the present counter value and
Section 5.3.2
outputs the counter value coincidence during the set time
after the coincidence.
Checks wiring of coincidence output.
This function can be used only when the continuous
Section 5.3.3
comparison function is selected.
Generates an interrupt signal to the programmable
controller CPU when a coincidence is detected, and starts
Section 5.3.4
an interrupt program.
Preset function Overwrites present value to an arbitrary value. Section 5.4
Latch counter function Latches the present value. Section 5.5
* 1 The functions can be used in combination.

The following table shows the I/O signals from the QD64D2 to the programmable controller CPU. Note that I/O numbers (X/Y) mentioned in this and the subsequent chapters are assumed when the QD64D2 is mounted to the null I/O slot on the main base unit.
Table 3.3 List of input signals

X02 Counter value coincidence No.1 X12 Counter value coincidence No.1
X03 Counter value small No.1 X13 Counter value small No.1
X04 Counter value large No.2 X14 Counter value large No.2
X05 Counter value coincidence No.2 X15 Counter value coincidence No.2
X06 Counter value small No.2 X16 Counter value small No.2
X08 External preset request detection X18 External preset request detection
* 1 The signals are used only for the continuous comparison function.
The reserved signals above are for system use, not for users. If used (turning ON/ OFF) by a user, the functions of the QD64D2 are not guaranteed.

Table 3.4 List of output signals
number Signal name Operation
number Signal name Operation
Y00 Reserved --- Y10 Reserved ---
Coincidence signal No.1 reset
Coincidence signal No.1 reset
Coincidence signal No.2 reset
Coincidence signal No.2 reset
Y03
Y04 Preset command Y14 Preset command
Y05 Subtraction count command Y15 Subtraction count command
Y06 Count enable command Y16 Count enable command
Y07 Latch counter execution
command Y17 Latch counter execution
CH2
Y08 External preset request
detection reset command Y18 External preset request
Continuous comparison No.1
Continuous comparison No.1
execution command *2 Y19
Continuous comparison No.2
Continuous comparison No.2
execution command *2 Y1A
Coincidence output No.1 test
Coincidence output No.1 test
Coincidence output No.2 test
Coincidence output No.2 test
Y0D Error reset command Y1D Error reset command
Y1E
Reserved --- Y0F Y1F
* 1 The signal is only used for the coincidence output function. * 2 The signal is only used for the continuous comparison function.
(1) The reserved signals above are for system use, not for users. If used (turning
ON/OFF) by a user, the functions of the QD64D2 are not guaranteed. (2) Definitions of the expression in Operation timing are as follows.
3.3 I/O Signals to the Programmable Controller CPU 3.3.1 List of I/O signals 3 - 7

The following indicates the details of I/O signals of the QD64D2.
In this section, I/O numbers (X/Y) and buffer memory addresses are listed only for channel 1. For I/O numbers and buffer memory addresses used for channel 2, refer to Section 3.3.1 and Section 3.4.1.
QD64D2 is ready for counting, and the counting process is executed.
(Error code: 810 to 860) occurs.
Operation by the QD64D2 Operation by the sequence program
In preparation Ready Watchdog timer error or an error that affects the system
OFF
(X00)
Figure 3.6 Operation of the module READY (X00)
QD64D2 status · Module READY

counter value small No.1 (X03) counter value large No.2 (X04), counter value coincidence No.2 (X05), counter value small No.2 (X06) The signals notify a comparison result in the counter value comparison function (coincidence output function, continuous comparison function). In (a) and (b) below, operations of the counter value large No.1 (X01), the counter value coincidence No.1 (X02) and the counter value small No.1 (X03) are explained. For the counter value large No.2 (X04), the counter value coincidence No.2 (X05), and the counter value small No.2 (X06), operations are the same except that I/O numbers (X/Y) and buffer memory addresses of the point used for comparison are different.
(a) Operation when used for the coincidence output function (Refer to Section 5.3.1.)
large No.1(X01)
small No.1(X03)
No.1(X02)
Coincidence output No.1 point
Present value (Un\G12 and 13)
setting (Un\G6 and 7)
Present value (Un\G12 and 13) =
Coincidence output No.1 point
setting (Un\G6 and 7)
Coincidence output No.1 point
Present value (Un\G12 and 13) >
setting (Un\G6 and 7)
* The counter value coincidence No.1 (X02) remains ON until the coincidence signal No.1 reset command (Y01) is turned ON.
Operation by the QD64D2 Operation by the sequence program
Immediately after power-on or reset of the programmable controller CPU
No.1 point setting
Present value (Un\G12 and 13)
100 101 102 99 98
ON
No.1 (X01)
ON
OFF
No.1 (X02)
OFF
ON
No.1 (X03)
ON
ON
Coincidence signal No.1
OFF
(Y01)
Figure 3.7 Operation of the counter value large No.1 (X01), the counter value coincidence No.1 (X02) and the counter value small
No.1 (X03) when using the coincidence output function
3.3 I/O Signals to the Programmable Controller CPU 3.3.2 Functions of I/O signals 3 - 9

(b) Operation when used for the continuous comparison function (Refer to Section
5.3.2.)

* The counter value coincidence No.1 (X02) remains ON for the preset time of the continuous comparison No.1 ON time setting (Un\G52).

Usage condition of the following operation diagram Continuous comparison No.1 start point setting (Un\G50): 1 (point 1) Continuous comparison No.1 repeat point setting (Un\G51): 3 (point 3) Continuous comparison No.1 point 1 setting (Un\G54 and 55): 100 Continuous comparison No.1 point 2 setting (Un\G56 and 57): 10000 Continuous comparison No.1 point 3 setting (Un\G58 and 59): 20000
Operation by the QD64D2 Operation by the sequence program
99 100 101 102 10000 10001 10002 19998 19999 20000 20001 20002
*1 t1 = Continuous comparison No.1 ON time setting (Un\G52)
Figure 3.8 Operation of the counter value large No.1 (X01), the counter value coincidence No.1 (X02) and the counter value small
No.1 (X03) when using the continuous comparison function

preset request detection reset command (Y08). • The preset cannot be executed while the external preset request detection (X08)
is ON.
Operation by the QD64D2 Operation by the sequence program
(PRST)
OFF
ON
External preset request detection
(X08)
ON
External preset request detection reset command
(Y08)
Present value (Un\G12 and 13)
Figure 3.9 Operation of the external preset request detection (X08)
comparison No.2 execution (X0A)
Section 5.3.2.)
ON the error reset command (Y0D).
Operation by the QD64D2 Operation by the sequence program
(Y0D)
OFF
ON
(X0D)
OFF
Figure 3.10 Operation of the error occurrence (X0D)
turn ON the error reset command (Y0D).
Operation by the QD64D2 Operation by the sequence program
(Y0D)
OFF
OFF
Figure 3.11 Operation of the warning occurrence (X0E)
3.3 I/O Signals to the Programmable Controller CPU 3.3.2 Functions of I/O signals 3 - 11

to the external coincidence output power supply terminal.
Operation by the QD64D2
OFF
ON
Blown fuse detection flag
(X1F)
ON
(X0D)
Figure 3.12 Operation of the blown fuse detection flag (X1F)
reset command (Y02)
value coincidence No.1 (X02).
value coincidence No.2 (X05).
the coincidence output No.1 terminal (EQU1) and the coincidence output No.2 terminal (EQU2) of the external device connector when the count value coincides with the comparison point.
Operation by the QD64D2
Counter value coincidence No.1
(X02)
ON
Counter value coincidence No.2
ON
Coincidence output enable command
(Y03)
ON
Coincidence output No.1 terminal
OFF
ON
Coincidence output No.2 terminal
OFF
Figure 3.13 Operation of the coincidence output enable command (Y03)

Section 5.4).
the preset command (Y04).
executed by the preset command (Y04).
Operation by the QD64D2
(Y04)
OFF
Present value (Un\G12 and 13)
Figure 3.14 Operation of the preset command (Y04)
phase B pulse or the subtraction count command (Y05) is turned ON.
shown below.
command (Y05) are turned OFF.
ON ON
B
OFF
ON
(Y05)
Present value (Un\G12 and 13)
99 98 97 100 99
Figure 3.15 Operation of the subtraction count command (Y05) (when the pulse input mode is 1 multiple of 1 phase)
shown below.
B
ON
(Y06)
Present value (Un\G12 and 13)
Figure 3.16 Operation of the count enable command (Y06) (when the pulse input mode is 1 multiple of 1 phase)
3.3 I/O Signals to the Programmable Controller CPU 3.3.2 Functions of I/O signals 3 - 13

present value (Un\G12 and 13) is stored in the latch count value (Un\G14 and 15).
(Un\G12 and 13) is stored in the latch count value (Un\G14 and 15).
Operation by the QD64D2
Present value (Un\G12 and 13)
0 4 1 2 3
ON
Latch counter execution command
OFF
Figure 3.17 Operation of the latch counter execution command (Y07)
comparison No.2 execution command (Y0A)
test command (Y0C)
errors can be checked.

The following table shows the buffer memory assignment of the QD64D2. For details of each buffer memory, refer to Section 3.4.2.
Table 3.5 List of buffer memory assignment
CH1 CH2 0 200 Ring counter lower limit value *2
Only used for the ring counter function. 1 201 (H) 2 202 Ring counter upper limit value *2 (L) 3 203 (H) 4 204 Preset value setting *2 (L) 5 205 (H) 6 206 Coincidence output No.1 point setting *2 (L)
enabled.
7 207 (H) 8 208 Coincidence output No.2 point setting *2 (L) 9 209 (H) 10 210 Coincidence output No.1 point change request 11 211 Coincidence output No.2 point change request 12 212 Present value *2 (L)
Only used for the coincidence output
function.
13 213 (H) 14 214 Latch count value *2 (L) 15 215 (H)
16 216 Overflow detection flag Only used for the linear counter
function. 17 217 External I/O status monitor
18 218 Error code 19 219 Warning code 20 220 Reserved to to 49 249 50 250 Continuous comparison No.1 start point setting
comparison function. 51 251 Continuous comparison No.1 repeat point
Only used for the continuous
setting 52 252 Continuous comparison No.1 ON time setting 53 253 Reserved 54 254 Continuous comparison No.1 point 1
enabled.
55 255 (H)
56 256 Continuous comparison No.1 point 2
Only used for the continuous
comparison function.
enabled.
58 258 Continuous comparison No.1 point 3
59 259 (H)
* 1 Initial value which is set when the module is powered on or the programmable controller CPU is
reset. * 2 Read and write a value in 32-bit signed binary format. (Make sure to use a value in units of 2
words.)
3.4 Buffer Memory Assignment 3.4.1 List of buffer memory assignment 3 - 15

Table 3.5 List of buffer memory assignment (Continued)

CH1 CH2 60 260 Continuous comparison No.1 point 4
Reserved to to 99 299 100 300 Continuous comparison No.2 start point setting
comparison function. 101 301 Continuous comparison No.2 repeat point setting 102 302 Continuous comparison No.2 ON time setting 103 303 Reserved 104 304 Continuous comparison No.2 point 1
* 1 Initial value which is set when the module is powered on or the programmable controller CPU is
reset. * 2 Read and write a value in 32-bit signed binary format. (Make sure to use a value in units of 2
words.)

Table 3.5 List of buffer memory assignment (Continued)
CH1 CH2 108 308 Continuous comparison No.2 point 3
109 309 (H)
110 310 Continuous comparison No.2 point 4
111 311 (H)
112 312 Continuous comparison No.2 point 5 setting *2
(L) 113 313 (H) 114 314 Continuous comparison No.2 point 6 setting *2
(L) 115 315 (H) 116 316 Continuous comparison No.2 point 7 setting *2
(L) 117 317 (H) 118 318 Continuous comparison No.2 point 8 setting *2
(L) 119 319 (H) 120 320 Continuous comparison No.2 point 9 setting *2
(L) 121 321 (H) 122 322 Continuous comparison No.2 point 10 setting *2
are enabled. Only used for the continuous
(L) 123 323 (H) 124 324 Continuous comparison No.2 point 11 setting *2
comparison function.
(L) 125 325 (H) 126 326 Continuous comparison No.2 point 12 setting *2
(L) 127 327 (H) 128 328 Continuous comparison No.2 point 13 setting *2
(L) 129 329 (H) 130 330 Continuous comparison No.2 point 14 setting *2
(L) 131 331 (H) 132 332 Continuous comparison No.2 point 15 setting *2
(L) 133 333 (H) 134 334 Continuous comparison No.2 point 16 setting *2
136 336 Continuous comparison No.2 point monitor
137 337 Reserved to to 199 399
* 1 Initial value which is set when the module is powered on or the programmable controller CPU is
reset. * 2 Read and write a value in 32-bit signed binary format. (Make sure to use a value in units of 2
words.)
3.4 Buffer Memory Assignment 3.4.1 List of buffer memory assignment 3 - 17

table are for system use, not for users. If written by a user, the functions of the QD64D2 are not guaranteed. • All data in the buffer memory of the QD64D2 are initialized when the
module is powered on or the programmable controller CPU is reset. To save the necessary data, use the FROM/DFRO/TO/DTO instructions in the sequence program or make setting with the utility package for writing/ reading of the buffer memory data. • Since the buffer memory contents are automatically updated by count
operation, the latest count value can be read from the buffer memory.

This section describes details of the QD64D2 buffer memory. In this section, I/O numbers (X/Y) and buffer memory addresses are listed for channel 1 and coincidence output No.1. For I/O numbers and buffer memory addresses used for channel 2 and coincidence output No.2, refer to Section 3.3.1 and Section 3.4.1.
Ring counter upper limit value (Un\G2 and 3)
Operation by the QD64D2
(Y06)
Ring counter lower limit value
Ring counter upper limit value
*1 Setting value of the ring counter upper limit value (Un\G2 and 3) and the ring counter lower limit value (Un\G0 and 1) becomes effective when the count enable command (Y06) is turned from OFF to ON. *2 It does not become effective until the count enable command (Y06) is turned from OFF to ON.
Figure 3.18 Timing chart for the ring counter lower limit value (Un\G0 and 1) and ring counter upper limit value (Un\G2 and 3)
preset input terminal (PRST) is turned from OFF to ON.
Operation by the QD64D2
OFF
(Y04)
Present value (Un\G12 and 13)
Figure 3.19 Timing chart for the preset value setting (Un\G4 and 5)
3.4 Buffer Memory Assignment 3.4.2 Details of the buffer memory 3 - 19

Coincidence output No.1 point change request (Un\G10) Coincidence output No.2 point setting (Un\G8 and 9) Coincidence output No.2 point change request (Un\G11)
with the present value) used for the coincidence output function.
change request, the comparison point written to the coincidence output No.1 point setting does not become effective. For the comparison point, a value previously set in the coincidence output No.1 point setting is used.
For example, the default value of the coincidence output No.1 point setting is "0". If "10000" is written to the coincidence output No.1 point setting, the default value of "0" is used for the comparison point unless "1" is written to the coincidence output No.1 point change request.
To set the coincidence output No.2, replace the coincidence output No.1 setting (Un\G6 and 7) and the coincidence output No.1 point change request (Un\G10) with the coincidence output No.2 point setting (Un\G8 and 9) and the coincidence output No.2 point change request (Un\G11).
Operation by the QD64D2
Coincidence output No.1 point change request
0 0 1 0
Coincidence output No.1 point 1 setting
*1 When the coincidence output No.1 point setting (Un\G6 and 7) becomes effective, the QD64D2 writes "0" to the coincidence output No.1 point change request (Un\G10).
Figure 3.20 Timing chart for the coincidence output No.1 point setting (Un\G6 and 7) and the coincidence output No.1 point change
request (Un\G10) • For details of the operation, refer to Section 5.3.1.

B
ON
(Y06)
Present value (Un\G12 and 13)
Figure 3.21 Timing chart of the present value (Un\G12 and 13)
(Refer to Section 5.5.) • When one of the following conditions is satisfied, the present value (Un\G12 and
Operation by the QD64D2
Present value (Un\G12 and 13)
0 4 1 2 3
Latch counter execution command
Figure 3.22 Timing chart for the latch count value (Un\G14 and 15)
3.4 Buffer Memory Assignment 3.4.2 Details of the buffer memory 3 - 21

5.2.1.) 0: No detection 1: Overflow occurred • Overflow occurs when the count value exceeds the range of -2147483648 to
2147483647. • The overflow detection flag (Un\G16) can be cleared by the preset command
(Y04) or the preset input terminal (PRST).
Operation by the QD64D2
B
Present value (Un\G12 and 13)
(Y04)
Figure 3.23 Timing chart for the overflow detection flag (Un\G16) (when the pulse input mode is 1 multiple of 1 phase)
b15 b8 b7 b0
0
Latch counter input status
Phase A input status
Phase B input status
Coincidence output No.1 output status *1
Coincidence output No.2 output status *1
Figure 3.24 Storage contents of the external I/O status monitor (Un\G17)
to the external coincidence output power supply terminal. • It takes up to 2ms until actual I/O status is reflected to the external I/O status
monitor (Un\G17).

8.11.1.
Section 8.11.2.
Continuous comparison No.2 start point setting (Un\G100)
Continuous comparison No.2 repeat point setting (Un\G101)
Continuous comparison No.2 ON time setting (Un\G102)
Continuous comparison No.2 point n setting (Un\G104 to 135)
Continuous comparison No.2 point monitor during comparison (Un\G136)
stored in this area. • For details of setting and operation, refer to Section 5.3.2.
3.4 Buffer Memory Assignment 3.4.2 Details of the buffer memory 3 - 23

Table 3.6 Input specifications of the QD64D2
Phase A pulse input
(AM26C32 (manufactured by Texas Instruments Incorporated) or equivalent)
VIT+ differential input ON voltage (H level threshold voltage) 0.1V
VIT- differential input OFF voltage (L level threshold voltage) -0.1V
Phase B pulse input
Vhys Hysteresis voltage (VIT+ - VIT-) 60mV
(A current type line driver cannot be used.)
0.5ms or
/5mA 21.6 to 26.4VDC 21.6 to 26.4VDC
Approx.
/0.1mA or less
1.0ms or
0.5ms or
Latch counter input 24VDC
/5mA 21.6 to 26.4VDC 21.6 to 26.4VDC
Approx.
/0.1mA or less
1.0ms or
Approx.
10.2 to 30VDC
3.9k
(TYP 24VDC)
(2) Output specifications
Table 3.7 Output specifications of the QD64D2
Signal name Rated load
OFF ON
0.05ms or
No.1
12/24VDC 10.2 to 30VDC 0.5A/point
2A/common 1.5VDC 0.1mA
0.1ms or
No.2


The specifications of the connector section, which is the I/O interface for the QD64D2 and external device, are shown below.
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A09 A08 A07 A06 A05 A04 A03 A02 A01
3.5 Specifications of I/O Interfaces with External Device 3.5.2 Signal layout for external device connector 3 - 25

The details of each signal for the QD64D2 external device connector are shown below.
Table 3.9 Details of each signal for external device connector
number Symbol Signal details
Pulse input common B15 A15 PULSE
Preset input common B13 A13 PRST
Preset input 24V B12 A12 PRST
value (Un\G12 and 13) is changed to the preset value setting (Un\G4
and 5). Latch counter input
common B09 A09 LATCH
signal.
present value (Un\G12 and 13) is latched and stored in the latch
count value (Un\G14 and 15).
No.1 B05 A05 EQU1 Executes the coincidence output when a coincidence of the count
value is detected while using the coincidence output function or the
continuous comparison function. Coincidence output
No.2 B04 A04 EQU2
B03 A03 12V/24V •Supplies 12V or 24V when executing the external coincidence output.


The following table shows the list of external device interface of the QD64D2.
Table 3.10 List of external device interface of the QD64D2
3.5 Specifications of I/O Interfaces with External Device 3.5.4 Interface for external device 3 - 27

The encoders connectable to the QD64D2 are described below. • Line driver output type encoders (Check that the encoder output voltage meets the specifications of the QD64D2.)

CHAPTER4 PROCEDURES AND SETTINGS BEFORE OPERATION
This chapter describes the operating procedures before operation, part names, settings, and wiring of the QD64D2.
This section describes precautions on handling the QD64D2.
(1) Do not drop the module case and/or connector or apply a strong impact
to it.
(2) Do not remove the printed-circuit board of the module from the case.
Doing so will cause a failure.
(3) Be careful to prevent foreign matter such as dust or wire chips from
entering the module. Failure to do may cause a fire, failure or malfunction.
(4) A protective film is attached to the module top to prevent foreign matter
such as wire chips from entering the module during wiring. Do not remove the film during wiring. Be sure to remove it for heat dissipation before system operation.
ranges.
Table 4.1 Tightening torque range of module fixing screw
Screw Tightening torque range
Module fixing screw (M3)*1 0.36 to 0.48 N•m
Connector screw of module (M2.6) 0.20 to 0.29 N•m
* 1 The module can be easily fixed onto the base unit using the hook at the top of the module.
However, it is recommended to secure the module with the module fixing screw if the module is subject to significant vibration.
(6) When mounting the module to the base unit, insert the module fixing
projection into the fixing hole in the base unit, and mount the module with using the hole as a supporting point. Incorrect module mounting may cause a malfunction, failure, or drop of the module.

4.2 Procedures before Operation
The following flowchart shows the procedures for operating the QD64D2.
Module mounting Mount the QD64D2 to the specified slot.
Wiring Wire external devices to the QD64D2.
Intelligent function module switch setting Set the switches with GX Developer (refer to Section 4.5).
Section 4.5
Use GX Configurator-CT? Yes
Make the initial setting?
Make the initial setting?
Initial setting Create a sequence program for writing initial values with the FROM/TO instruction.
Initial setting Make initial settings with GX Configurator-CT (refer to Section 6.4).
Section 6.4
Make the auto refresh setting? No
Auto refresh setting Make the auto refresh setting with GX Configurator-CT (refer to Section 6.5).
Section 6.5
Programming Create and a program for counter processing with the FROM/TO instruction and check it.
Programming Create and a program for counter processing without the FROM/TO instruction and check it.
Figure 4.1 Procedures before operation


The following explains the part names of the QD64D2.

POINT
Even if the fuse of the external coincidence output part is blown, the FUSE LED does not turn ON unless a voltage is applied to the external coincidence output power supply terminal.
Purchase the connector for the QD64D2 separately. The following tables show the recommended connector types and crimp tool.
Table 4.3 Connector types
Type Model Soldering type, straight out A6CON1
Crimp type, straight out A6CON2 Soldering type, usable for both straight out and
* The A6CON3 connector (pressure welding type, straight out) cannot be used for the QD64D2.
(b) Connector crimp tool
Table 4.4 Connector crimp tool
Type Model Applicable wire size Contact
Crimp tool FCN-363T-T005/H AWG28 to 24 FUJITSU COMPONENT
4 - 4 4.3 Part Names
(a) Connector types · diagonal out A6CON4

4.4 Wiring
This section describes wiring an encoder and controller to the QD64D2.
One of the conditions to maximize the QD64D2 functions and make the system high- reliable, the external wiring has to be laid so that the QD64D2 becomes less subject to noise. This section describes the precautions on external wiring.
(1) Inputting a signal of different voltage may result in a malfunction or
mechanical failure.
(2) For 1-phase input, always perform pulse input wiring on the phase A
side.
(3) When pulse status noise is input, the QD64D2 may miscount.
(4) Take the following measures against noise for high-speed pulse input.
(a) Always use a shielded twisted pair cable and ground it on the QD64D2 side.
(b) Wire the shielded twisted pair cables so as not to be in parallel with wires causing
much noise such as power lines or I/O wires while keeping a distance of at least 150 mm (5.91 inch) between such wires. Also install the shielded twisted pair cables as short as possible.
noise.
Ground the shielded twisted pair cable on the QD64D2 side, and install the cable as short as possible.
Avoid using a solenoid valve and inductive load together in the same metallic pipe. If a sufficient distance cannot be secured with high voltage cable due to such as duct wiring, use CVVS or other shielded cable for the high voltage cable.
Install I/O wires at least 150 mm (5.91 inch) away from the high voltage equipment such as relay and inverter. (Apply this wiring in a control panel as well.)
Make the distance between the encoder and relay box as short as possible. If the distance is long, a voltage drop may occur. Therefore, check that the voltages while the encoder is in operation/stop are within the rated voltage at the terminal block of the relay box using the measure such as a synchronoscope.
Figure 4.3 Example of wiring for measures against noise

(6) Take the following measures to conform the wiring to the EMC and Low
Voltage Directives.
(a) Ground the shielded twisted pair cables to a control panel with the AD75CK cable
clamp (manufactured by Mitsubishi Electric Corporation)

Figure 4.4 AD75CK cable clamp
For the AD75CK, refer to the following manual.
AD75CK-type Cable Clamping Instruction Manual
(b) The power supply line connecting to the external coincidence output power supply
module should be 10m or less long.
(c) Keep the length of the cable connected to the external devices of the QD64D2 to
30m or less.


Alphanumeric characters in parentheses of QD64D2 terminal parts indicate CH2 terminal numbers.
Figure 4.5 Example of wiring with a line driver (AM26LS31 equivalent) encoder
4.4 Wiring 4.4.2 Example of wiring the module and an encoder 4 - 7

Alphanumeric characters in parentheses of QD64D2 terminal parts indicate CH2 terminal numbers.

Figure 4.6 Example of wiring with a controller (sink loading type)

Figure 4.7 Example of wiring with a controller (source loading type)


When using coincidence output No. 1 terminal (EQU1) and coincidence output No. 2 terminal (EQU2), external power supply of 10.2 to 30VDC is required. Figure 4.8 shows wiring example. Alphanumeric characters in parentheses of QD64D2 terminal parts indicate CH2 terminal numbers.
Figure 4.8 Example of wiring with an external output terminal (sink output type)
4.4 Wiring 4.4.4 Example of wiring with an external output terminal 4 - 9

4.5 Intelligent Function Module Switch Setting
This section describes the intelligent function module switch setting. The switch setting is made on the [I/O assignment] screen of GX Developer.
The switch has five switches and is set at 16-bit data. When the switch setting is not made, the default values of the switches from 1 to 5 are 0.
Table 4.5 Intelligent function module switches
Setting item Setting value Default
0000H 2) Counter format
(CH2) Same as for the switch 1 0000H

(Example) Target channel: channel 1, pulse input mode setting: 1 multiple of 2 phases, counter format: ring counter, and counter value comparison function selection: continuous comparison function
Set the switch 1 = 1103H.
The reserved bits in Table 4.5 are for system use, not for users. Therefore, always fix them to 0. If used (changed from 0 to 1) by a user, the functions of the QD64D2 are not guaranteed.
Table 4.6 Details of the intelligent function module switch setting
Setting item Description Reference
Set the pulse input mode for each channel.
When setting 6H to FH, a switch setting error (error code:
Section 5.1.1
Counter format Set the counter format for each channel. Section 5.2.1
Section 5.2.2
Set the counter value comparison function for each
Section 5.3.1
channel.
Section 5.3.2
Pulse input mode · Counter value comparison · function selection

Set the switches on the [I/O assignment] screen of GX Developer.
(a) [I/O assignment] screen
Make the following settings to the slot to which the QD64D2 is mounted. [Type]: Select [Intelli]. [Model name]: Input the model of the module. [Points]: Select [32points]. [Start XY]: Input the start I/O number of the QD64D2.

Figure 4.9 Setting example of [I/O assignment]
(b) [Switch setting for I/O and intelligent function module] screen
Click the on the [I/O assignment] screen to display the screen below and
set the switches from 1 to 5. Entering the values in hexadecimal make the setting easier. Change [Input format] to [HEX.] and enter values.

Figure 4.10 [Switch setting for I/O and intelligent function module] screen
Since [Error time output mode] and [H/W error time PLC operation mode] on the [Switch setting for I/O and intelligent function module] screen are disabled to the QD64D2, the settings are unnecessary.

This chapter describes functions of the QD64D2.
The pulse input method has six types as shown on Table 5.1. This chapter describes I/O numbers (X/Y) of channel 1 only. For I/O numbers (X/Y) of channel 2, refer to Section 3.3.1. Set the count method with the intelligent function module switch setting of GX Developer (refer to Section 4.5).
Table 5.1 Types of the pulse input method
For addition count Counts on the rising edge ( ) of A.
B (and subtraction count
B and the subtraction count command (Y05) are OFF.
1 multiple of 1 phase
Counts on the falling edge ( ) of A.
B (or subtraction count
B or the subtraction count command (Y05) is ON.
For addition count Counts on the rising ( ) and falling ( ) edges of A.
B (and subtraction count
B and the subtraction count command (Y05) are OFF.
2 multiples of 1
Counts on the rising ( ) and falling ( ) edges of A.
B (or subtraction count
B or the subtraction count command (Y05) is ON.
For addition count Counts on the rising edge ( ) of A.
B is OFF.
CW/CCW
A
A is OFF.
Counts on the rising edge ( ) of B.
A
For addition count When B is OFF, counts on the rising edge ( ) of A.
1 multiple of 2
A
count When B is OFF, counts on the falling edge ( ) of A.
5.1 Pulse Input and Count Methods 5.1.1 Types of the pulse input method 5 - 1

Table 5.1 Types of the pulse input method (continued)
For addition count When B is OFF, counts on the rising edge ( ) of A.
When B is ON, counts on the falling edge ( ) of A.
2 multiples of 2
When B is ON, counts on the rising edge ( ) of A.
When B is OFF, counts on the falling edge ( ) of A.
When B is OFF, counts on the rising edge ( ) of A.
When B is ON, counts on the falling edge ( ) of A.
When A is ON, counts on the rising edge ( ) of B.
4 multiples of 2
When A is OFF, counts on the falling edge ( ) of B.
When B is ON, counts on the rising edge ( ) of A.
When B is OFF, counts on the falling edge ( ) of A.
When A is OFF, counts on the rising edge ( ) of B.
When A is ON, counts on the falling edge ( ) of B.
When performing control with phase B pulse input or the subtraction count command (Y05) at 1-phase pulse input, always turn OFF the unused signals. If either of phase B pulse input or the subtraction count command (Y05) is ON, subtraction count is performed at phase A pulse input.

The counter format has the following two types. Select a counter format using the intelligent function module switch setting of GX Developer. (Refer to Section 4.5.)
5.2 Selecting a Counter Format 5.1.1 Types of the pulse input method 5 - 3

(a) For the linear counter, the counting is executed within the range of -2147483648
to 2147483647.
Figure 5.1 Operation image of the linear counter
(b) The following functions can be used in combination.
(a) If the present value (Un\G12 and 13) exceeds the range of -2147483648 to
2147483647, an overflow error occurs.
(b) The following are processed at the overflow error.
error code (Un\G18).
(c) The overflow error can be cleared by setting the present value (Un\12 and 13)
within the range of -2147483648 to 2147483647 using the preset function. When the overflow error is cleared, "0" is stored in the overflow detection flag (Un\G16) and the counting can be restarted. However, the error occurrence (X0D) remains ON and the stored value of the error code (Un\G18) is held even after presetting. Turn ON the error reset command (Y0D) to reset the error.

(a) For the ring counter, the counting is executed repeatedly within the range set by
the ring counter lower limit value (Un\G0 and 1) and the ring counter upper limit value (Un\G2 and 3). Overflow error does not occur.
Ring counter upper limit value (Un\G2 and 3)
Ring counter lower limit value (Un\G0 and 1)
Figure 5.2 Operation image of the ring counter
(b) The following functions can be used in combination.
5.2 Selecting a Counter Format 5.2.2 Selecting the ring counter 5 - 5

(a) Count range is the following three types shown in Table 5.2
1), the ring counter upper limit value (Un\G2 and 3) and the present value (Un\G12 and 13). • Range 1 and 2 in Table 5.2 are examples with the following setting.
Ring counter lower limit value (Un\G0 and 1) = -50000 Ring counter upper limit value (Un\G2 and 3) = 100000
Table 5.2 Count range of the ring counter
Count range Setting condition
Present value (Un\G12 and 13)
limit value (Un\G0 and 1)
limit value (Un\G2 and 3)
)
limit value (Un\G0 and 1)
limit value (Un\G2 and 3)
( )
Present value (Un\G12 and 13)
limit value (Un\G0 and 1)
Present value (Un\G12 and 13)
limit value (Un\G2 and 3)
-2147483648 to -50000 100001 to 2147483647
limit value Ring counter lower
( )
limit value (Un\G0 and 1)
limit value (Un\G2 and 3)
The present value (Un\G12 and 13) is not included in the setting condition.

(b) Setting method of the count range
input terminal (PRST) for external input.
upper limit value (Un\G2 and 3). • Turn from OFF to ON the count enable command (Y06).
(c) When the ring counter lower limit value (Un\G0 and 1) and the ring counter upper
limit value (Un\G2 and 3) are set as shown below and turn from OFF to ON the count enable command (Y06), a ring counter upper/lower limit value setting error (Error code: 500) occurs.
Ring counter lower limit value
Ring counter upper limit value
( )
POINT
However, the changes for the ring counter lower limit value (Un\G0 and 1) and the ring counter upper limit value (Un\G2 and 3) become valid only after turning from OFF to ON the count enable command (Y06). • When changing the count range by the preset, to avoid miss-counting,
always turn OFF the count enable command (Y06) before changing it.
5.2 Selecting a Counter Format 5.2.2 Selecting the ring counter 5 - 7
(Un\G0 and 1)

The counter value comparison function compares the present value (Un\G12 and 13) to a comparison point, and outputs the comparison result by the input signal (X01 to X06) or the external output (EQU1 and EQU2).
The counter value comparison function has the following two types. Select a counter value comparison function using the intelligent function module switch setting. (Refer to Section 4.5.)

Each channel has No.1 and No.2 comparison points. Each point individually compares to the present value (Un\G12 and 13) and outputs the comparison result. (Refer to Table 5.3.) One comparison point can be set for each No.1 and No.2.
Table 5.3 Coincidence output function
Signal and external output terminal used to output the
Input signal (X) External output
No.1 Coincidence output No.1 point setting (Un\G6
Coincidence output No.1
No.1 (X02)
No.2 Coincidence output No.1 point setting (Un\G8
Coincidence output No.2
No.2 (X05)
In this section, I/O numbers (X/Y) and buffer memory addresses are listed for channel 1 and coincidence output No.1. For I/O numbers and buffer memory addresses used for channel 2 and coincidence output No.2, refer to Section 3.3.1 and Section 3.4.1.
ON OFF
(Y06)
ON OFF
(Y03)
At the point where the coincidence output No.1 point change request (Un\G10) changes from "1" (Change request) to "0" (No change request), the comparison between the value set in the coincidence output No.1 point setting (Un\G6 and 7) (1000) and the present value (Un\G12 and 13) starts.
Coincidence output No.1
No.1 point setting
Counter value small No.1
(X03)
Counter value coincidence No.1
(X02)
ON OFF
No.1 terminal
Coincidence signal No.1 reset command
(Y01)
Counter value large No.1
(X01)
Present value (Un\G12 and 13)
1001 1000 999 1
Figure 5.3 Operation example of the coincidence output function
5.3 Using the Counter Value Comparison Function 5.3.1 Using the coincidence output function 5 - 9

Table 5.4 Details of operation example of the coincidence output function
With the following procedures, start the coincidence detection using the value
set in the coincidence output No.1 point setting (Un\G6 and 7).
(1) Write "1000" for the coincidence output No.1 point setting (Un\G6 and 7).
(2) Write "1" (Change request) for the coincidence output No.1 point change
request (Un\G10).
(3) The setting value becomes valid when "1" (Change requet) turns to "0" (No
change request).
No.1 point setting (Un\G6 and 7), the counter value small No.1 (X03) turns ON.
When outputting from the coincidence output No.1 terminal (EQU1) of external
device connector, turn ON the coincidence output enable command (Y03).
At the time, the coincidence output No.2 terminal (EQU2) is also enabled.
When the present value (Un\G12 and 13) is equal to the coincidence output
No.1 point setting (Un\G6 and 7), the counter value small No.1 (X03) turns OFF
and the counter value coincidence No.1 (X02) turns ON.
When the present value (Un\G12 and 13) is larger than the coincidence output
No.1 point setting (Un\G6 and 7), the counter value large No.1 (X01) turns ON.
The counter value coincidence No.1 (X02) remains ON until resetting it.
Turn ON the coincidence signal No.1 reset command (Y01) to reset the counter
value coincidence No.1 (X02). If the counter value coincidence No.1 (X02)
remains ON, the counter value coincidence No.1 (X02) cannot be output next
time.
* 1 If the operation in 1) is not executed, comparison with the values stored in the coincidence output
No.1 point setting (Un\G6 and 7) and the coincidence output No.2 point setting (Un\G8 and 9) is not executed.

(1) At immediately after the power-on or resetting the programmable controller
CPU, the relation of the present value and the coincidence output point setting is the following: "Present value = Coincidence output point setting = 0". Therefore, the counter value coincidence (X02, X05, X12, and X15) of channels that use the coincidence output function turns ON. For channels that use the coincidence output function, always execute the following procedures from 1 to 3. For the programming method of the following procedures, refer to Section 7.3 and Section 7.4.
Procedure 1: Set the following buffer memories and make sure that the coincidence output point settings are other than "0"
Buffer memory address to be set Setting value
CH1 coincidence output No.1 point setting (Un\G6 and 7)
Other than "0" CH1 coincidence output No.2 point setting (Un\G8 and 9)
CH2 coincidence output No.1 point setting (Un\G206 and 207)
CH2 coincidence output No.2 point setting (Un\G208 and 209)
CH1 coincidence output No.1 point change request (Un\G10)
1 CH1 coincidence output No.2 point change request (Un\G11)
CH2 coincidence output No.1 point change request (Un\G210)
CH2 coincidence output No.2 point change request (Un\G211)
Procedure 2: Turn from OFF to ON then OFF the following signals to turn OFF the counter value coincidence (X02, X05, X12, and X15).
Signals to be turned OFF ON OFF*1
CH1 coincidence signal No.1 reset command (Y01)
CH1 coincidence signal No.2 reset command (Y02)
CH2 coincidence signal No.1 reset command (Y11)
CH2 coincidence signal No.2 reset command (Y12)
*1 Make sure that ON time is longer than 2ms.
Procedure 3 (Only for external output): After checking that the counter value coincidence (X02, X05, X12, and X15) is OFF, turn ON the coincidence output enable (Y03 and Y13).
(2) Even if the coincidence signal No.1 reset command (Y01) is turned from ON
to OFF while the present value is equal to the coincidence output point setting, the counter value coincidence (X02) and the coincidence output No.1 terminal (EQU1) turn ON again.
(3) When the counter value coincidence No.1 (X02) is turned from OFF to ON by
the coincidence detection process of the QD64D2, there may be cases where the counter value large No.1 (X01) or the counter value small No.1 (X03) turns ON.
5.3 Using the Counter Value Comparison Function 5.3.1 Using the coincidence output function 5 - 11

coincidence output No.2 terminal (EQU2) For the coincidence output function, the wiring cannot be checked with the coincidence output test function (refer to Section 5.3.3). Check the wiring referring to the following procedures. Wiring check for the coincidence output No.1 terminal (EQU1) of channel 1 is indicated below.

Each channel has No.1 and No.2 comparison points. Each point individually compares to the present value (Un\G12 and 13) and outputs the comparison result (refer to Table 5.5). 16 comparison points can be set for each No.1 and No.2. Without rewriting the comparison point in the middle of the control, multiple coincidence detections can be executed easily.
Table 5.5 Continuous comparison function
Signal and external output terminal used to output the
Input signal (X) External output
Continuous comparison No.1 point 1 setting
(Un\G54 and 55) •Counter value large No.1 (X01)
Coincidence output No.1
No.1
No.1 (X02)
Continuous comparison No.1 point 16 setting
Continuous comparison No.2 point 1 setting
(Un\G104 and 105) •Counter value large No.2 (X04)
Coincidence output No.2
No.2
No.2 (X05)
Continuous comparison No.2 point 16 setting
In this section, I/O numbers (X/Y) and buffer memory addresses are listed for channel 1 and continuous comparison No.1. For I/O numbers and buffer memory addresses used for channel 2 and continuous comparison No.2, refer to Section 3.3.1 and Section 3.4.1.
(Un\G54 to 85) and the continuous comparison No.2 point n setting (Un\G104 to 135) By the magnitude correlation of the following buffer memories, an order and range of the continuous comparison points as comparison targets can be specified. A: Continuous comparison No.1 start point setting (Un\G50) B: Continuous comparison No.1 repeat point setting (Un\G51)
(a) When A < B
(b) When A > B
5.3 Using the Counter Value Comparison Function 5.3.2 Using the continuous comparison function 5 - 13

(c) When A = B
After coincidence detection with the continuous comparison No.1 point 16 setting (Un\G84 and 85) is completed, the comparison target returns to the continuous comparison No.1 point 1 setting (Un\G54 and 55) again. When temporarily stopping the continuous comparison, turn OFF the count enable command (Y06) and so on, so that the present value (Un\G12 and 13) does not change.
When restarting the continuous comparison function after stopping the function, the comparison starts from the point set by the continuous comparison No.1 start point setting (Un\G50).

Setting example for comparing between point 1 (1000) and point 2 (21000) repeatedly using the continuous comparison No.1 is indicated below.
Write the following values beforehand. *1 Continuous comparison No.1 start point setting (Un\G50) = 1 Continuous comparison No.1 repeat point setting (Un\G51) = 2 Continuous comparison No.1 ON time setting (Un\G52) = 1ms Continuous comparison No.1 point 1 setting (Un\G54 and 55) = 1000 Continuous comparison No.1 point 2 setting (Un\G56 and 57) = 21000
* 1 The continuous comparison point can be set up to 16 points each. Beforehand, set all points to be
used. (Refer to Section 3.4.1) If the settings of buffer memories for the continuous comparison No.1 start point setting (Un\G50) and so on are improper, an error (Error code 201 to 222) occurs and the continuous comparison cannot be started.
(Y06)
OFF
Continuous comparison No.1 execution command
(Y09) During continuous comparison No.1 execution
ON
OFF
(X09)
Continuous comparison No.1 point monitor during comparison
1 0 2 1
Counter value small No.1
(X03)
OFF
ON
Coincidence output No.1 terminal
OFF
Counter value coincidence No.1
OFF
Counter value large No.1
(X01)
OFF
Present value (Un\G12 and 13)
999 1000 1001 20999 21000
*1 t1 = Continuous comparison No.1 ON time setting (Un\G52)
Figure 5.4 Operation example of the continuous comparison function
5.3 Using the Counter Value Comparison Function 5.3.2 Using the continuous comparison function 5 - 15

Table 5.6 Details of operation example of the continuous comparison function
Turn ON the continuous comparison No.1 execution command (Y09).
When the continuous comparison is ready, first comparison target will be the
continuous comparison No.1 point 1 setting (Un\G54 and 55) because "1" is set
in the continuous comparison No.1 start point setting (Un\G50).
When "1" is stored in the continuous comparison No.1 point monitor during
comparison (Un\G86), the during continuous comparison No.1 execution (X09)
turns ON and the continuous comparison starts.
[At counter value coincidence]
When the present value (Un\G12 and 13) is equal to the continuous comparison
No.1 point 1 setting, the following are processed.
coincidence No.1 (X02) and the coincidence output No.1 terminal (EQU1)
turn ON.
generated.
[Process after the continuous comparison ON time setting]
After a set time of the continuous comparison No.1 ON time setting (Un\G52)
elapses, the coincidence output No.1 terminal (EQU1) turns OFF.
(Un\G56 and 57).
comparison (Un\G86).
When OFF of the coincidence output No.1 terminal (EQU1) is detected, the
following are processed.
(After that, the comparison is repeated with the continuous comparison No.1
point 2 setting (Un\G56 and 57) and the continuous comparison No.1 point 1
setting (Un\G54 and 55) until the continuous comparison No.1 execution
command (Y09) is turned OFF. )
(Un\G54 and 55).
comparison (Un\G86).
When the coninuous comparison No.1 execution command (Y09) is turned OFF,
the following are processed and the during continuous comparison No.1
execution (X09) turns OFF.
The continuous comparison No.1 point monitor during comparison (Un\G86) is
held until the during continuous comparison No.1 execution (X09) turns ON.

(1) When the count value coincides with the comparison point, an external output
is performed. Therefore, do not connect anything to the unused coincidence output terminal (EQU). (2) When the counter value coincidence No.1 (X02) is turned from OFF to ON by
the coincidence detection process of the QD64D2, there may be cases where the counter value large No.1 (X01) or the counter value small No.1 (X03) turns ON. (3) If the continuous comparison No.1 execution command (Y09) is turned OFF
while outputting from the coincidence output No.1 terminal (EQU1), the output stops regardless of the set time of the continuous comparison No.1 ON time setting (Un\G52).
5.3 Using the Counter Value Comparison Function 5.3.2 Using the continuous comparison function 5 - 17

point setting For the QD64D2, settable continuous comparison No.1 point n setting (Un\G54 to 85) is up to 16 points each. Therefore, when comparing with 17 points or more, execute the following procedures.
Set the following and turn from OFF to ON the continuous comparison No.1 execution command (Y09).
following buffer memories. Continuous comparison No.1 point 1 setting (Un\G54 and 55) to Continuous comparison No.1 point 16 setting (Un\G84 and 85)
* 1 When starting from point 2 or later, set a value that is "Start point setting -1" for the repeat point
setting. Example) When start point = 6, repeat point = 5 When starting from point 16, set the following. Start point = 16, Repeat point = 1
(b) Rewriting data during comparison
Set the following when the continuous comparison No.1 point monitor during comparison (Un\G86) becomes "2".
comparison point setting for the 17th point After that, rewrite the data at every point change.
No.1 point monitor during comparison
After that, repeat setting until the end point.
continuous comparison No.1 point 1 setting (Un\G54 and 55) to
continuous comparison No.1 point 2 setting (Un\G56 and 57) to
continuous comparison No.1 point 3 setting (Un\G58 and 59) to
the setting for the 17th point.
the setting for the
the setting for the 19th point.
18th point.
Figure 5.5 Rewriting data during comparison
When the point monitor is "1", rewrite the point 16 setting.
No.1 point monitor during comparison
continuous comparison No.1 point 14 setting
continuous comparison No.1 point 15 setting
continuous comparison No.1 point 16 setting
continuous comparison No.1 point 1 setting
(Un\G80 and 81).
(Un\G82 and 83).
(Un\G84 and 85).
(Un\G54 and 55).
Figure 5.6 When the point monitor is "1"

(c) Process after completion of comparison at end point
(Continuous comparison No.1 point monitor during comparison (Un\G86) -1) = Continuous comparison point setting of the 1st point and later Figure 5.7 is the example when comparing with 19 points.
No.1 point monitor during comparison
After that, repeat setting until the end point.
continuous comparison No.1 point 2 setting (Un\G56 and 57) to
continuous comparison No.1 point 3 setting (Un\G58 and 59) to
continuous comparison No.1 point 4 setting (Un\G60 and 61) to
continuous comparison No.1 point 5 setting (Un\G62 and 63) to
the setting for the
the setting for the
the setting for the
the setting for the
18th point.
19th point.
1st point.
2nd point.
Figure 5.7 When repeatedly comparing from the 1st point
-1) = Comparison end point Figure 5.8 is the example when comparing with 19 points.
Comparison end point Comparison end point + 1
No.1 point monitor during comparison
continuous comparison No.1 point 2 setting (Un\G56 and 57) to
continuous comparison No.1 point 3 setting (Un\G58 and 59) to
Turn from OFF to ON
the continuous comparison No.1 execution command
the setting for the
the setting for the
18th point.
19th point.
*1 When the present value may coincide with the comparison point of the (comparison end point + 1) before stopping the continuous comparison, store a value which does not perform a coincidence output (for example: -1) to the (comparison end point + 1) before completing the coincidence detection at the comparison end point. *2 In the case of the comparison end point is 16, turn from ON to OFF the execution command when the point monitor changes to 1.
Figure 5.8 When stopping the continuous comparison
5.3 Using the Counter Value Comparison Function 5.3.2 Using the continuous comparison function 5 - 19

Table 5.7 shows the example of continuous comparison point setting for 19 points.
Table 5.7 Example of continuous comparison point setting
Target continuous comparison No.1 point n setting
1 100 Continuous comparison No.1 point 1 setting
2 110 Continuous comparison No.1 point 2 setting 3 120 Continuous comparison No.1 point 3 setting
4 130 Continuous comparison No.1 point 4 setting 5 140 Continuous comparison No.1 point 5 setting
6 150 Continuous comparison No.1 point 6 setting 7 160 Continuous comparison No.1 point 7 setting
8 170 Continuous comparison No.1 point 8 setting 9 180 Continuous comparison No.1 point 9 setting
10 190 Continuous comparison No.1 point 10 setting 11 200 Continuous comparison No.1 point 11 setting
12 210 Continuous comparison No.1 point 12 setting 13 220 Continuous comparison No.1 point 13 setting
14 230 Continuous comparison No.1 point 14 setting 15 240 Continuous comparison No.1 point 15 setting
16 250 Continuous comparison No.1 point 16 setting 17 260 Continuous comparison No.1 point 1 setting
18 270 Continuous comparison No.1 point 2 setting 19 280 Continuous comparison No.1 point 3 setting
Continuous comparison No.1 point 4 setting
(Set "-1" so that the coincidence output is not performed
when the continuous comparison function is stopped. )

For the interval of the continuous comparison No.m point n setting, set the values to satisfy the following conditions 1 and 2.
(a) Condition 1:
Interval of (Continuous comparison
No.m point n setting)
Input pulse speed [pps]
(Continuous comparison No.m
ON time setting [ms])
(b) Condition 2 (Applies only when the derating of external coincidence output is less
than 100% (Refer to Section 3.1.2)):
Interval of (Continuous comparison
No.m point n setting)
Input pulse speed [pps]
Continuous comparison No.m
ON time setting [ms] ON ratio [%]
For example, when "Continuous comparison No.1 ON time setting" = 10[ms], "ON ratio" = 50[%], "Input pulse speed" = 4[Mpps] = 4000000[pps], interval of the continuous comparison No.1 point n setting (Un\G54 to 85) is the following.
Condition 1:
Interval of (Continuous comparison No.1 point n setting (Un\G54 to 85))
Condition 2:
Interval of (Continuous comparison No.1 point n setting (Un\G54 to 85))
(To satisfy the conditions 1 and 2, set the value of condition 2.)
Interval of the continuous comparison No.1 point n setting (Un\G54 to 85) 80000
"1ms" in the above condition 1 is a time for the comparison target change in the QD64D2. Always set the sequence program to satisfy the condition 1. When the count value is coincided within the time, the QD64D2 may not detect the coincidence depending on the timing of the count value coincidence and the comparison target change.
5.3 Using the Counter Value Comparison Function 5.3.2 Using the continuous comparison function 5 - 21

Use the coincidence output test function to check the wiring of the coincidence output No.1 terminal (EQU1) and the coincidence output No.2 terminal (EQU2) when selecting the continuous comparison function.
When using the continuous comparison function, the coincidence output No.1 terminal (EQU1) and the coincidence output No.2 terminal (EQU2) automatically turn OFF. Therefore, check the wiring using the coincidence output test function.
Coincidence output No.1 test command
(Y0B)
OFF
Coincidence output No.1 terminal
(EQU1)
OFF
External I/O status monitor. b4
OFF
Figure 5.9 Operation example of the coincidence output test function
Table 5.8 Details of operation example of coincidence output test function
When the coincidence output No.1 test command (Y0B) is turned ON, the
following are executed.
(Un\G17) turns ON.
When the coincidence output No.1 test command (Y0B) is turned OFF, the
following are executed.
(Un\G17) turns OFF.
(a) Before executing the coincidence output test function, check that the following
signals are all OFF.
(b) Counting cannot be started while the coincidence output test command is ON.
Do not turn ON the count enable command (Y06). If it is turned ON, a count enable execution not possible error (Error code: 300) occurs.

(c) Do not turn ON the continuous comparison execution command while the
coincidence output test command is ON. If the continuous comparison execution command is turned ON while the test command is ON, a continuous comparison No.m execution not possible error (Error code: 311 and 312) occurs.
coincidence output No.2 test command (Y0C) are turned ON, the counter value coincidence No.1 (X02) and the counter value coincidence No.2 (X05) do not turn ON/OFF. (Coincidence detection interrupt also does not occur.) • The coincidence output test function cannot be used when selecting the
coincidence output function.
5.3 Using the Counter Value Comparison Function 5.3.3 Using the coincidence output test function 5 - 23

Use the coincidence detection interrupt function to request an interrupt to the programmable controller CPU when a coincidence is detected, and start up the interrupt program.
(a) Up to 16-point interrupt factors (SI) are allowed for a single MELSEC-Q series
intelligent function module. As shown in Table 5.9, the QD64D2 has 4-point interrupt factors (SI) for coincidence detection.
Table 5.9 List of interrupt factors
SI No. Interrupt factor
comparison No.1 point m setting
comparison No.2 point m setting
comparison No.1 point m setting
comparison No.2 point m setting 4 to 15 Reserved
Timing of interrupt signal generation
Counter value coincidence No.1
Coincidence signal No.1 reset command
Internal processing of the programmable
Program processing in the programmable controller CPU Interrupt program processing
*1 The coincidence signal No.1 reset command (Y01) is only used for the coincidence output function. For the continuous comparison function, the counter value coincidence No.1 (X02) automatically turns OFF after elapsing the set time of the continuous comparison No.1 ON time setting (Un\G52).
Figure 5.10 Timing of interrupt signal generation
(b) It takes approximately 150 s from when the QD64D2 detects a coincidence until
it requests an interrupt to the programmable controller CPU.
(c) Select [PLC parameter] - [PLC system] - [Intelligent function module setting] -
[Interrupt pointer settings] to set the interrupt factors (SI) of the QD64D2 and interrupt pointers of the programmable controller CPU.


Figure 5.11 Interrupt pointer setting example (GX Developer screen)
(d) The following two methods are available for using particular SI numbers only.
1) Using the interrupt pointer setting with parameters According to the setting in the [Intelligent function module interrupt pointer setting] dialog box, only the interrupt factors starting from the [Start SI No.] and equivalent to the number set at [Interrupt pointer No. of module] are used. For example, if the [Start SI No.] and [Interrupt pointer No. of module] are set to 1 and 2 respectively, only SI 1 and 2 will be used. The interrupt function is not used if the interrupt pointer setting with parameters has not been made.
MELSEC-Q/L Programming Manual (Common Instruction)
5.3 Using the Counter Value Comparison Function 5.3.4 Coincidence detection interrupt function 5 - 25

coincidence No.1 (X02) and the counter value coincidence No.2 (X05) turns ON immediately after the power-on or resetting the programmable controller CPU; however, a coincidence detection interrupt does not occur. For resetting method of the counter value coincidence No.1 (X02) and the counter value coincidence No.2 (X05), refer to Section 5.3.1.

Use the preset function to rewrite the present value (Un\G12 and 13) to any value (preset value) and start counting pulses from the value.
The following two methods are available for presetting.
In (1) and (2) below, I/O numbers (X/Y) and buffer memory addresses are listed for channel 1. For I/O numbers and buffer memory addresses used for channel 2 , refer to Section 3.3.1 and Section 3.4.1.
program Turn ON the preset command (Y04) by the sequence program to execute preset.
(Y06)
Present value (Un\G12 and 13) to
2001 2000 0 1067 1066 1065 1002 1001 1000
2002 2003 2004 2005
Figure 5.12 Operation example of the preset function by the sequence program
Table 5.10 Details of operation example of the preset function by the sequence program
bit binary format.
At the rising edge (OFF ON) of the preset command (Y04), the preset value
setting (Un\G4 and 5) is stored in the present value (Un\G12 and 13).
The preset can be executed regardless of the ON/OFF status of the count
enable command (Y06).

Apply ON voltage to the preset input terminal (PRST) for external input to execute preset. Operation example is indicated in Figure 5.13.

2001 2000 0 1067 1066 1065 1002 1001 1000
Figure 5.13 Operation example of the preset function by external control signal
Table 5.11 Details of operation example of the preset function by external control signal
bit binary format.
When the preset input terminal (PRST) is turned from OFF to ON, the preset
value setting (Un\G4 and 5) is stored in the present value (Un\G12 and 13).
The preset can be executed regardless of ON/OFF status of the count enable
command (Y06).
While the external preset request detection (X08) is ON, the preset cannot be
executed by turning ON the preset command (Y04) or the preset input terminal
(PRST).
When the external preset request detection reset command (Y08) is turned ON
and the external preset request detection (X08) turns OFF, the preset can be
executed.
When the external preset request detection (X08) is OFF, both the preset command (Y04) and the preset input terminal (PRST) are valid.

The latch counter function latches the present value (Un\G12 and 13) to the latch count value (Un\G14 and 15).
The following two methods are available for latch operation.
In (1) below, I/O numbers (X/Y) and buffer memory addresses are listed for channel 1. For I/O numbers and buffer memory addresses used for channel 2 , refer to Section 3.3.1 and Section 3.4.1.
ON OFF
(Y06)
Present value (Un\G12 and 13)
Latch counter execution command
(Y07)
Latch counter input terminal
(LATCH)
Figure 5.14 Operation example of the latch counter function

Table 5.12 Details of operation example of the latch counter function
When the latch counter execution command (Y07) is turned from OFF to ON,
the present value (Un\G12 and 13) is stored in the latch count value (Un\G14
and 15).
When the latch counter input terminal (LATCH) is turned from OFF to ON, the
present value (Un\G12 and 13) is stored in the latch count value (Un\G14 and
15).
terminal (LATCH) is ON, the latch counter function cannot be executed.
count enable command (Y06).
Number Description · 1) · 2)

In the QD64D2, a response delays due to the cause indicated in (a) and (b) below.
(a) Scan time of the sequence program
It affects the delay of I/O signal. Use the direct access input (DX) or the direct access output (DY) to minimize the delay.
(b) Control cycle (1ms) of the QD64D2
Up to 2ms (1 control cycle 2) of delay occurs until the QD64D2 reads out the output signal and buffer memory updated by the sequence program and completes processing. Update timing of the I/O signal and buffer memory varies within the range of a control cycle.
For example, the following is the maximum delay time until the QD64D2 executes the latch counter function and updates the latch count value after the latch counter execution command (Y07) is turned ON by the sequence program.
Maximum delay time [ms] = [Time of (a)] + [Maximum time of (b)]
= Sequence program scan time + 2 [ms]

CHAPTER6 UTILITY PACKAGE (GX Configurator-CT)
6.1 Utility Package Functions
Table 6.1 shows the functions of the utility package.
Table 6.1 Utility package (GX Configurator-CT) functions list
(1) Make the initial settings for each channel to operate the QD64D2.
Section 6.4
(2) Data with initial settings are registered to programmable controller CPU parameters and are
automatically written to the QD64D2 when the programmable controller CPU is in RUN.
(1) Set the buffer memory of the QD64D2 to which auto refresh is to be performed for each
Section 6.5
(2) The values stored in the QD64D2 buffer memory with auto refresh setting are automatically
read when the programmable controller CPU executes the END instruction.
Function Description Reference · Initial setting · Auto refresh

Table 6.1 Utility package (GX Configurator-CT) functions list
Section 6.6
Function Description Reference · Monitor/Test

6.2 Installing and Uninstalling the Utility Package
For how to install or uninstall the utility package, refer to "Method of installing the MELSOFT Series" included in the utility package.
The following explains the precautions on using the utility package.
Since the utility is add-in software for GX Developer, read "SAFETY PRECAUTIONS" and the basic operating procedures in the GX Developer Operating Manual.
GX Configurator-CT is add-in software for GX Developer Version 4 or later. Therefore, GX Configurator-CT must be installed on the personal computer that has already GX Developer Version 4 or later installed.
Insufficient system resource may cause the screen to be displayed inappropriately while using the Intelligent function module utility. If this occurs, close the Intelligent function module utility, GX Developer (program, comments, etc.), and other applications, and then start GX Developer and Intelligent function module utility again.
(a) In GX Developer, select "QCPU (Q mode)" for [PLC series] and specify a project.
If any other than "QCPU (Q mode)" is selected for [PLC series], or if no project is specified, the [Intelligent function module utility] will not start.
(b) Multiple [Intelligent function module utility] can be started.
However, [Open parameters] and [Save parameters] operations under [Intelligent function module parameter] are allowed for one [Intelligent function module utility] only. Only the [Monitor/test] operation is allowed for the other utilities.
When two or more Intelligent function module utility screens cannot be displayed side by side, select a screen to be displayed on the top of others using the task bar.

When multiple intelligent function modules are mounted, set the parameters within the maximum number of settable parameters shown on the next page.

Table 6.2 Maximum number of settable parameters using GX Configurator
When intelligent function modules
Maximum number of parameter settings
are mounted to:
Initial setting Auto refresh setting
Q02PH/Q06PH/Q12PH/Q25PHCPU 512 256 Q12PRH/Q25PRHCPU 512 256
Q00UJ/Q00U/Q01UCPU 512 256 Q02UCPU 2048 1024
Q03UD/Q04UDH/Q06UDH/Q10UDH/
Q13UDH/Q20UDH/Q26UDH/
Q03UDE/Q04UDEH/Q06UDEH/
Q10UDEH/Q13UDEH/Q20UDEH/
Q26UDEHCPU
Q50UDEH/Q100UDEHCPU Use prohibited Use prohibited MELSECNET/H remote I/O station 512 256
For example, if multiple intelligent function modules are mounted to the remote I/O station, configure the settings in GX Configurator so that the number of parameters set for all the intelligent function modules does not exceed the limit of the remote I/O station. Calculate the total number of parameter settings separately for the initial setting and for the auto refresh setting. The number of parameters that can be set for one module in GX Configurator-CT is as shown below.
Table 6.3 Number of settable parameters per module
Target module Initial setting Auto refresh setting
QD64D2 6 (fixed) 16 (Max.)
Example) Counting the number of parameter settings in Auto refresh setting

This one row is counted as one setting. Blank rows are not counted. Count up all the setting items on this screen, and add the total to the number of settings for other intelligent function modules to get a grand total.
Figure 6.1 Numeration for the number of parameters set in Auto refresh setting
6.2 Installing and Uninstalling the Utility Package 6.2.1 Handling precautions 6 - 4
4096 2048

This section explains the operating environment of the personal computer that runs GX Configurator-CT.
Table 6.4 Operating environment of the personal computer

Installation (Add-in) target*1 Add-in to GX Developer Version 4 (English version) or later.*2
CPU Refer to Table 6.5 "Operating system and performance required for personal
Microsoft Windows NT Workstation Operating System Version 4.0 (English
Microsoft Windows XP Home Edition Operating System (English version)
Microsoft Windows Vista Home Basic Operating System (English version)
Microsoft Windows Vista Home Premium Operating System (English version)
* 1 Install GX Configurator-CT in GX Developer Version 4 or higher in the same language.
GX Developer (English version) and GX Configurator-CT (Japanese version) cannot be used in combination, and GX Developer (Japanese version) and GX Configurator-CT (English version) cannot be used in combination. * 2 GX Configurator-CT is not applicable to GX Developer Version 3 or earlier.
* 3 At least 15GB is required for Windows Vista .
* 4 Resolution of 1024 X 768 dots or more is recommended for Windows Vista .

Table 6.5 Operating system and performance required for personal computer
Operating system Performance required for personal computer
Windows 95 Pentium 133 MHz or more 32 MB or more
Windows 98 Pentium 133 MHz or more 32 MB or more
Windows Me Pentium 150 MHz or more 32 MB or more
Windows NT Workstation 4.0 Pentium 133 MHz or more 32 MB or more
Windows 2000 Professional Pentium 133 MHz or more 64 MB or more
Windows XP Professional (Service Pack1 or later) Pentium 300 MHz or more 128 MB or more
Windows XP Home Edition (Service Pack1 or later) Pentium 300 MHz or more 128 MB or more
Windows Vista Home Basic Pentium 1GHz or more 1GB or more
Windows Vista Home Premium Pentium 1GHz or more 1GB or more
Windows Vista Business Pentium 1GHz or more 1GB or more
Windows Vista Ultimate Pentium 1GHz or more 1GB or more
Windows Vista Enterprise Pentium 1GHz or more 1GB or more
(1) The functions shown below are not available for Windows XP and Windows
Vista . If any of the following functions is attempted, this product may not operate normally.
Also, 64-bit version Windows XP and Windows Vista are not supported.
(2) Use a USER authorization or higher in Windows Vista .
6.2 Installing and Uninstalling the Utility Package 6.2.2 Operating environment 6 - 6
CPU Memory

6.3 Utility Package Operation
Table 6.6 shows the special keys that can be used in operations of the utility package and their applications.
Table 6.6 Control keys
Cancels the current entry in a cell.
Closes the window.
Moves between controls in the window.
Used in combination with the mouse operation to select
multiple cells for test execution. Deletes the character where the cursor is positioned.
When a cell is selected, clears all of the setting contents in
the cell.
Deletes the character where the cursor is positioned.
Moves the cursor.
Moves the cursor one page up.
Moves the cursor one page down.
Completes the entry in the cell.
The following data or files that are created with the utility package can be also handled in GX Developer. Figure 6.3 shows respective data or files are handled in which operation.
(a) This represents the data created in Auto refresh setting, and they are stored in an
intelligent function module parameter file in a project created by GX Developer.
Intelligent function module parameter
Figure 6.2 Project structure

(b) Steps 1) to 3) shown in Figure 6.3 are performed as follows:
[Project] [Open project]/[Save]/[Save as].
[Intelligent function module parameter] [Open parameters]/[Save parameters].
[Online] [Read from PLC]/[Write to PLC] "Intelligent function module parameters". Or, from the module selection screen of the utility, select:
[Online] [Read from PLC]/[Write to PLC].
(a) A text file can be created by clicking the button on the initial setting, Auto refresh setting, or Monitor/Test screen. The text files can be utilized to create user documents.
(b) Text files can be saved in any directory. However, a path (folder where the file is to
be saved) cannot be created during operation of . Therefore, create the
folder beforehand using Windows Explorer.
GX Developer/ GX Configurator-CT
A
B
QCPU
A: Intelligent function module parameters B: Data saved by "Make text file"
Figure 6.3 Correlation chart for data created with the utility package


[Tools] - [Intelligent function utility] - [Start]
Screen for selecting a target

Section 6.3.3.
Enter "Start I/O No.", and select "Module type" and "Module model name".
Initial setting Auto refresh
[Auto refresh setting] screen

Refer to Refer to
Section 6.4. Section 6.5.
Figure 6.4 General operation

[Select monitor/test module] screen

Select a module to be monitored/tested.

Section 6.6.
Figure 6.4 General operation (continued)

Start the utility from GX Developer to display the [Intelligent function module utility] screen. From this screen, [Initial setting], [Auto refresh setting], and [Select monitor/test module] (selection of the module which performs monitor/test) screens for the QD64D2 can be started. [Operating procedure]
[Tools] [Intelligent function utility] [Start] [Setting screen]

Figure 6.5 [Intelligent function module utility] screen
(a) [Initial setting] screen
[Start I/O No.*] [Module type] [Module model name]
(b) [Auto refresh setting] screen
[Start I/O No.*] [Module type] [Module model name]
(c) Monitor/test module selection screen
* Enter the [Start I/O No.] in hexadecimal.
[Purpose] · [Explanation of items] · [Online] [Monitor/Test]

Deletes the [Initial setting] and [Auto refresh setting] of the selected module.
Closes this screen.

Intelligent function module parameters of the project opened by GX Developer are handled.
[Open parameters] : Reads a parameter file.
modified, a dialog asking for file saving will appear.
[Save parameters] : Saves the parameter file.
[Delete parameters] : Deletes the parameter file.
[Open FB support parameter...] : Opens a FB support parameter file.
[Save as FB support parameter...] : Saves a FB support parameter.
[Exit] : Exits the [Intelligent function module utility].
screen.
parameters from the CPU module.
parameters to the CPU module.
6.3 Utility Package Operation 6.3.3 Starting the Intelligent function module utility 6 - 12
(a) File menu · (b) Online menu

POINT
(1) Saving intelligent function module parameters in a file
Since intelligent function module parameters cannot be saved in a file by the project saving operation of GX Developer, save them on the shown module selection screen. (2) Reading/writing intelligent function module parameters from/to a
programmable controller using GX Developer
a programmable controller after having been saved in a file. • Set a target programmable controller CPU in GX Developer:
[Online] - [Transfer setup]. • When mounting the QD64D2 to the remote I/O station, use [Read from
PLC]/[Write to PLC] of GX Developer. (3) Checking the required utility
While the start I/O is displayed on the Intelligent function module utility setting screen, " * " may be displayed for the model name. This means that the required utility has not been installed or the utility cannot be started from GX Developer. Check the required utility, selecting [Tools] - [Intelligent function utility] - [Utility list...] in GX Developer.

6.4 Initial Setting
Make [Initial setting] for each channel to operate the QD64D2. For parameter types of [Initial setting], refer to Section 6.1. This setting allows skipping sequence program setting. By making the initial settings, the sequence program settings become unnecessary. [Operating procedure]
"Start I/O No.*" "Module type" "Module model name"
* Enter the [Start I/O No.] in hexadecimal. [Setting screen]


Figure 6.6 [Initial setting] screen
[Purpose] · Channel 1 · Channel 2

Creates a file containing the screen data in text file format.
Saves the set data and ends the operation.
Cancels the setting and ends the operation.
Initial settings are stored to the intelligent function module parameters. The initial settings become effective after writing them to the CPU module and executing (1) or (2). (1) Change RUN/STOP switch on the CPU module STOP, RUN, STOP, and RUN
again. (2) After changing the switch to RUN, power OFF and then ON the CPU module
or reset it. When the initial setting contents are written with the sequence program, the initial settings are executed when the RUN/STOP switch is changed to STOP and RUN again, and initial setting values are written. When the CPU module is switched to STOP and RUN again, execute the initial settings with the sequence program again.
[Explanation of items]

6.5 Auto Refresh
Set the buffer memory of the QD64D2 to which auto refresh is to be performed for each channel. For parameter types of [Auto refresh setting], refer to Section 6.1. This auto refresh setting eliminates the need for reading by sequence programs. [Operating procedure]
"Start I/O No.*" "Module type" "Module model name"
* Enter the [Start I/O No.] in hexadecimal. [Setting screen]

Figure 6.7 [Auto refresh setting] screen
[Purpose]

Module side Buffer size : Displays the buffer memory size of the setting item.
Module side Transfer word count
: Displays the number of words to be transferred.
Transfer direction : " " indicates that data are written from the programmable controller CPU to the buffer memory.
" " indicates that data are loaded from the buffer memory to the programmable controller CPU. PLC side Device : Enter a CPU module side device that is to be
automatically refreshed. Applicable devices are X, Y, M, L, B, T, C, ST, D, W, R, and ZR. When using bit devices X, Y, M, L or B, set a number that can be divided by 16 points (examples: X10, Y120, M16, etc.) Also, buffer memory data are stored in a 16-point area, starting from the specified device number. For example, if X10 is entered, data are stored in X10 to X1F.
Creates a file containing the screen data in text file format.
Saves the set data and ends the operation.
Cancels the setting and ends the operation.
parameter file. The auto refresh settings become effective by turning the power OFF and then ON or resetting the CPU module after writing the intelligent function module parameters to the CPU module. • The auto refresh settings cannot be changed from sequence programs.
However, processing equivalent to auto refresh can be added using the FROM/TO instruction in the sequence program.
[Explanation of items]

6.6 Monitoring/Test
Start buffer memory monitor/test and I/O signal monitor/test from this screen. [Operating procedure]
"Select monitor/test module" screen "Start I/O No.*" "Module type" "Module
model name" .
* Enter the [Start I/O No.] in hexadecimal. The screen can also be started from System monitor of GX Developer Version 6 or later. Refer to the GX Developer Operating Manual for details. [Setting screen]

Selecting these buttons displays the following screens.
Preset function X/Y Monitor/Test


Figure 6.8 [Monitor/Test] screen
[Purpose] · 1)



Coincidence output function 1)
Ring counter function Latch counter function


Figure 6.8 [Monitor/Test] screen (continued)
Continuous comparison function

Setting item : Displays I/O signals and buffer memory names.
Current value : Monitors the I/O signal status and present buffer memory values. Setting value : Enter or select values to be written into the buffer memory for test
Displays the current value of the item selected. (This is used to check the text that cannot be displayed in the current value field. However, in this utility package, all items can be displayed in the display fields). Creates a file containing the screen data in text file format. / Selects whether or not to monitor current values.
Performs a test on the selected items. To select more than one item, select them while holding down the
key. Closes the screen that is currently open and returns to the previous screen.
The following describes a method for using [Execute test] by an example when setting "3000" at [CH1 Preset value setting] and writing it to the QD64D2. (1) Click the [Preset function] button in [Setting value] field to display the [Preset
function] screen. (2) Click [Setting value] field on [CH1 Preset value setting], enter "3000", and
press the key.
At this point, the value has not been written to the QD64D2 yet. (3) Click [Setting value] field on [CH1 Preset command (Y04)] and select [ON].
At this point, the value has not been written to the QD64D2 yet. (4) Select [Setting value] fields entered by operations (2) and (3) while pressing
the key. Multiple items can be selected by dragging operation.
(Selected [Setting value] fields are inverted.)
(5) Click the button and write setting values of the items selected at
(4) to the QD64D2. After writing, the values entered at (2) and (3) are displayed at [Current value] fields.

This chapter describes the programs of the QD64D2. When applying any of the program examples introduced in this chapter to the actual system, verify the applicability and confirm that no problems will occur in the system control. 7.1 Programming Procedure
Create a program activating a count by the QD64D2 by the following procedures.
with sequence program.
with GX Configurator-CT.
Ring counter setting program
Preset value setting program
Coincidence output function setting program
Continuous comparison function setting program
*1: Created according to the functions used.
Turn OFF the counter value coincidence
No.m when using the
*2: Turn OFF the coincidence signal No. m reset command with coincidence output function program.
Coincidence signal No. m
Turn ON the initial setting
*3: If unnecessary on a program, the signal needs not to be created.
complete signal (any given device). *3
To the next page
Figure 7.1 Program creation procedures

From the previous page
(1) Count control program
(a) Count operation program
(b) Preset execution program
Use the latch counter function?
(c) Latch counter function
(2) Counter value comparison program
*4: Required to use the counter value comparison function.
Setting of the counter value comparison function selection is
(a) Coincidence output function
*5: Added according to contents of the control (created when necessary).
Counter format setting is
(a) Overflow detection processing
Figure 7.1 Program creation procedures (continued)

This section describes a program example under the following system configuration and use conditions.

Figure 7.2 System configuration
Table 7.1 Conditions for the intelligent function module switch setting
Channel Pulse input mode Counter format Counter value comparison function selection
CH1 CW/CCW Linear counter Coincidence output function
CH2 CW/CCW Ring counter Continuous comparison function
(a) Preset the following values to each channel.
(b) CH1 uses the coincidence output function (refer to Section 5.3.1).*1
No.2 (X05) turns ON at default.
(c) CH2 uses the continuous comparison function (refer to Section 5.3.2).*2
* 2: This program example does not use the continuous comparison No.2.
(d) CH2 uses the ring counter function (refer to Section 5.2.2).


Mount the QD64D2 on the base unit and connect the external devices.
7.2 For Use in Normal System Configuration 7.2.1 Before creating a program 7 - 4

Based on the setting conditions given in Section 7.2 (2), make the intelligent function module switch settings.
(a) Each switch setting

Counter value comparison function selection CH1: 0 (Coincidence output function)

Counter value comparison function selection CH2: 1 (Continuous comparison function)
0
* If any other than 0 is set to the switches from 1 to 5 where 0 is fixed, the functions of the QD64D2 are not guaranteed.
(b) Write the settings in (a) to the QD64D2.
On GX Developer's "Parameter setting" screen, select the "I/O assignment" tab, click "Switch setting", and make settings of Switch 1 to 5 on the screen shown below.

Fixed at 0


X02 CH1 counter value coincidence No.1 X0D CH1 error occurrence
Y06 CH1 count enable command Y07 CH1 latch counter execution command
Y0D CH1 error reset command X12 CH2 counter value coincidence No.1
Y14 CH2 preset command Y16 CH2 count enable command
X28 CH1 error/warning reset command signal X2A CH2 count operation start signal
X2B CH2 count operation stop signal X2D CH2 preset command signal

Table 7.2 List of devices (continued)
Device Function Y30 CH1 coincidence confirmation LED signal
QY40P (Y30 to Y3F) Y31*2 CH1 overflow occurrence confirmation LED signal
Y32 CH2 coincidence confirmation LED signal
* 1 Set this only when using the latch counter function. * 2 Set this only when using the linear counter function. * 3 Stores last occurred error and holds it even after error reset. * 4 Stores last occurred warning and holds it even after error reset. * 5 Set this only when using the coincidence output function. * 6 Set this only when using the continuous comparison function.
Set the initial settings of CH1 and 2. Refer to Section 7.2 for the settings. For Initial setting in GX Configurator-CT, refer to Section 6.4.

Figure 7.4 [Initial setting] screen
(a) Initial setting

Table 7.3 Item on the [Initial setting] screen
Setting item Description Setting
Preset value setting Set preset value. 0
Set these only when
No.1 point setting
No.1 point change
Section 4.5) is the
function.
Ring counter lower limit
Set these only when
using the ring counter
Ring counter upper limit
function.
Preset value setting Set preset value. -50000
No.1 start point setting
Set these only when
No.1 repeat point
comparison No.1 setting
No.1 ON time setting 10
Section 4.5) is the
No.1 point 1 setting 20000
function.
No.1 point 2 setting 40000
(b) Auto refresh setting
Set devices storing the present values, latch count values, overflow detection flags, error codes, and warning codes of CH1 and CH2. For Auto refresh setting in GX Configurator-CT, refer to Section 6.5.
Figure 7.5 Auto refresh setting screen

Table 7.4 Auto refresh setting
Description Setting value CH1 Present value D0
CH1 Latch count value*1 D2
CH1 Overflow detection flag*2 D4
CH2 Present value D8 CH1 Error code D118
CH1 Warning code D119 CH2 Error code D120
CH2 Warning code D121
* 1 Set this only when using the latch counter function. * 2 Set this only when using the linear counter function.
(c) Writing the intelligent function module parameters
Write the intelligent function module parameters to the CPU module. This operation is performed using the parameter setting module selection screen. For writing of intelligent function module parameters with GX Configurator-CT, refer to Section 6.3.3.


CH1 coincidence signal No.1 reset command (Y01) ON
CH1 count enable command (Y06) ON
CH1 count enable command (Y06) OFF
CH1 preset command (Y04) ON
CH1 latch counter execution command (Y07) ON
CH1 coincidence output enable command (Y03) ON
CH1 coincidence confirmation LED signal ON
CH1 counter value coincidence No.1 (X02) OFF
CH1 overflow occurrence confirmation LED signal ON
Stores CH1 error code to D5.
Stores CH1 warning code to D6.
CH1 error reset command (YD0) ON


CH2 count enable command (Y16) ON
CH2 count enable command (Y16) OFF
CH2 preset command (Y14) ON
CH2 continuous comparison No.1 execution command (Y19) ON CH2 coincidence confirmation LED signal ON
Stores CH2 error code to D10.
Stores CH2 warning code to D11.
CH2 error reset command (Y1D) ON


D119 CH1 warning code D8,D9 CH2 present value storage
X02 CH1 counter value coincidence No.1 X0D CH1 error occurrence
Y06 CH1 count enable command Y07 CH1 latch counter execution command
Y0D CH1 error reset command X12 CH2 counter value coincidence No.1
Y14 CH2 preset command Y16 CH2 count enable command

Table 7.5 List of devices (continued)
X20 CH1 count operation start signal
X21 CH1 count operation stop signal
X22 CH1 present value read signal X23 CH1 preset command signal
X24*1 CH1 latch execution command signal
X25*1 CH1 latch count data read signal
X26*5 CH1 coincidence output enable signal
QX40 (X20 to X2F)
X27*5 CH1 coincidence LED clear signal
X28 CH1 error/warning reset command signal X2A CH2 count operation start signal
X2B CH2 count operation stop signal X2C CH2 present value read signal
X2D CH2 preset command signal
X2E*6 CH2 continuous comparison execution signal
X2F CH2 error/warning reset command signal Y30 CH1 coincidence confirmation LED signal
QY40P (Y30 to Y3F) Y31*2 CH1 overflow occurrence confirmation LED signal
Y32 CH2 coincidence confirmation LED signal
* 1 Set this only when using the latch counter function. * 2 Set this only when using the linear counter function. * 3 Stores last occurred error and holds it even after error reset. * 4 Stores last occurred warning and holds it even after error reset. * 5 Set this only when using the coincidence output function. * 6 Set this only when using the continuous comparison function.
Device Function


CH1 preset value setting
CH1 coincidence output No.1 point setting
CH1 coincidence output No.1 point change request
CH1 coincidence signal No.1 reset command (Y01) ON
CH2 ring counter lower limit value setting
CH2 ring counter upper/lower limit value setting
CH2 preset value setting
CH2 continuous comparison No.1 start point setting
CH2 continuous comparison No.1 repeat point setting
CH2 continuous comparison No.1 ON time setting
CH2 continuous comparison No.1 point 1 setting
CH2 continuous comparison No.1 point 2 setting
CH1 count enable command (Y06) ON
CH1 count enable command (Y06) OFF
Stores CH1 present value to D0.
CH1 preset command (Y04) ON
CH1 latch counter execution command (Y07) ON
Stores CH1 latch count value to D2.


CH1 coincidence output enable command (Y03) ON
CH1 coincidence confirmation LED signal ON
CH1 counter value coincidence No.1 (X02) OFF
Stores CH1 overflow status to D4.
CH1 overflow occurrence confirmation LED signal ON
Stores CH1 error code to D118.
Stores a value of D118 to D5 when error code is stored in D118. Stores CH1 warning code to D119. Stores a value of D119 to D6 when warning code is stored in D119. CH1 error reset command (YD0) ON
CH2 count enable command (Y16) ON
CH2 count enable command (Y16) OFF
Stores CH2 present value to D8.
CH2 preset command (Y14) ON
CH2 continuous comparison No.1 execution command (Y19) ON
CH2 coincidence confirmation LED signal ON


Stores CH2 error code to D120.
Stores a value of D120 to D10 when error code is stored in D120. Stores CH2 warning code to D121. Stores a value of D121 to D11 when warning code is stored in D121. CH2 error reset command (Y1D) ON

This section describes a program example to start an interrupt program upon detecting coincidence of comparison point of channel 1.
QD64D2 (X/Y00 to X/Y1F)
Figure 7.6 System configuration when the coincidence detection interrupt function is used
(a) Interrupt pointer setting
Set the values at [PLC parameter] - [PLC system] - [Intelligent function module setting] - [Interrupt pointer setting] in the [Project data list] on GX Developer. Set the values for this program example as shown below.

Figure 7.7 Intelligent function module interrupt pointer setting
(b) Devices used by users
Table 7.6 Devices used by users
Interrupt enabled flag storage for the IMASK instruction D20 to D35
Description Setting value

An interrupt must be enabled using the IMASK instruction before using an interrupt pointer.

program is execution-enabled and other interrupt programs are execution-disabled. When executing interrupt programs other than I50, set the corresponding bit for interrupt program to be executed to 1 (enabled). • For details of the IMASK instruction, refer to the following manual.
MELSEC-Q/L Programming Manual (Common Instruction)
7.5 Program Example when the Coincidence Detection Interrupt Function is Used 7 - 18
QD64D2 program · Interrupt program

This chapter describes the troubleshooting, error code and warning code of the QD64D2. Before performing a troubleshooting for the QD64D2, check that the CPU module does not have any errors. For error details of the CPU module, refer to the following manual.
QCPU User's Manual(Hardware Design, Maintenance and Inspection)
Error codes can be checked by selecting [Module's Detailed Information...] on the [System Monitor] screen of GX Developer.
Select [Diagnostics] [System Monitor] [QD64D2]
Error code that is stored in the error code (Un\G18) is displayed in the [Present Error] field.(Either one of channels 1 and 2)
(By clicking the button, error code of the present error on each channel
is displayed in order of channel 1 to 2. Note that this is not a history.)

The error codes in Section 8.11.1 "Error code list" are shown in decimal notation. Select [DEC] because the initial value is set to [HEX].
Section 8.11.1
Indicates error code 500 "ring counter upper/lower limit value setting error".
Error code of the channel
Channel number that has an error
[2500] indicates that the error code 500 is occurring on CH2.
Figure 8.1 [Module's Detailed Information] screen
[Display format] · [Display contents] · [Present Error]

Check the status of LEDs and intelligent function module switch setting, and module information in [H/W status] on the [Module's Detailed Information] screen which can be displayed from [System Monitor] of GX Developer.
Select [Diagnostics] [System monitor...] [QD64D2]
[Module's Detailed Information...]

Figure 8.2 [H/W Information] screen
[H/W LED Information] The following information is displayed on the [H/W LED Information] screen.
Table 8.1 H/W LED Information
Item Signal Value RUN "RUN" LED on the QD64D2 0: The LED is OFF.
[H/W SW Information] The setting status of the intelligent function module switches is displayed.
Table 8.2 H/W SW Information
CH1 CH1 setting Switch 1
CH2 CH2 setting Switch 2 NOP1 Switch 3
For details, refer to Section 4.5
Intelligent Function Module Switch
NOP2 Switch 4 NOP3 Switch 5
Setting.
8.1 Error Processing and Recovery Methods 8.1.1 Checking error description using System Monitor of GX Developer 8 - 2
[Setting procedure] · Item Signal Corresponding · switch Value

Table 8.3 When the RUN LED turns OFF
Check item Action Reference
Is the power supplied? Check if the service voltage of the power supply
module is within the rated range.
Calculate the consumption current of the modules
Is the capacity of the power supply module
mounted to the base unit such as CPU module, I/O
module, and intelligent function module, and check
that the current capacity is sufficient.
Reset the programmable controller CPU and check
that the RUN LED turns ON. If the RUN LED
remains OFF even doing so, the QD64D2 is at
Is there a watchdog timer error?
Section 4.3
fault. Please consult your local Mitsubishi
representative, explaining a detailed description of
the problem.
Are the modules correctly mounted to the base
unit? Check the module mounting status. Section 4.1
Table 8.4 When the RUN LED and ERR.LED turn ON
Check item Action Reference
Is there any errors? Check the error code (Un\G18) of channels in use
and take action described in Error Code List. Section 8.11.1
Table 8.5 When the RUN LED and FUSE LED turn ON
Check item Action Reference
Please consult your local Mitsubishi
Is the fuse of the external coincidence output part
representative, explaining a detailed description of
Section 4.3
the problem.
Even if the fuse of the external coincidence output part is blown, the FUSE LED does not turn ON unless a voltage is applied to the external coincidence output power supply terminal.
sufficient? · blown?


Table 8.6 When the QD64D2 does not start counting
If they turn ON, check the external wiring, encoder
Do the LEDs of A and B turn ON by directly
applying a voltage to the pulse input terminals of
If they remain OFF, it is a hardware failure. Please
A and B using such as a voltage stabilizer?
Is the external wiring of A and B correct? Check the external wiring and correct the error.
Is the count enable command (Y06) turned ON? Turn ON the count enable command (Y06) by the
Are the pulse input method and pulse input mode
Match the pulse input method with the pulse input
Table 8.7 When the QD64D2 does not normally count
When the count value that is same with another
If they differ, it is a hardware failure. Please consult
Use the shielded twisted pair cables for pulse input
Bundle the pulse input lines and put them in a
single tube, and keep a distance of 150mm (5.91
inch) or more with the power line even inside the
Separate the ground cable of the QD64D2 from the
If the QD64D2 case touches to the ground part,
Are the count value data treated in 32-bit binary in
Is the preset performed out of the count range of
Perform the preset within the count range of the

8.4 When the Counter Value Coincidence No.1 (X02) or Counter Value Coincidence No.2 (X05) does not Turn ON/OFF
Table 8.8 When the counter value coincidence does not turn ON (when selecting the coincidence output function)
Check item Action Reference
After changing the coincidence output No.m point
Has the coincidence output No.m point change
setting (Un\G6 and 7, and Un\G8 and 9), set the
request (Un\G10 and 11) been set to "1" (Change
Section 3.4
coincidence output No.m point change request to
"1".
Is the coincidence signal No.m reset command
Turn OFF the coincidence signal No.m reset
command. Section 3.3
(Y01 and Y02) ON?
Has the coincidence output No.m point setting
(Un\G6 and 7, and Un\G8 and 9) been set to out
Set the coincidence output No.m point setting
value to within the count range of the ring counter. Section 3.4
of the count range of the ring counter?
(Only for the ring counter)
"m" indicates the coincidence output number.
Table 8.9 When the counter value coincidence does not turn OFF (when selecting the coincidence output function)
Check item Action Reference Is the ON time of the coincidence signal No.m
Set the ON time of the coincidence signal No.m
reset command to 2ms or longer. Section 3.3
reset command (Y01 and Y02) 2ms or longer?
"m" indicates the coincidence output number.
Table 8.10 When the counter value coincidence does not turn ON/OFF (when selecting the continuous comparison function)
Check item Action Reference Does the present value (Un\G12 and 13) coincide
Change the setting so that the present value
with the continuous comparison No.m point n
coincides with the continuous comparison No.m
setting (Un\G54 to 85, and 104 to 135) after an
Section 5.3.2
point n setting after an elapse of (continuous
elapse of (continuous comparison No.m ON time
comparison No.m ON time setting + 1ms).
setting (Un\G52 and 102) + 1ms)?
Has the continuous comparison No.m point n
Set the continuous comparison No.m point n
setting been set to out of the count range of the
Section 5.2.1
setting value to within the count range of the ring
Section 5.3.2
counter.
(Only for the ring counter function)
Does the relation of the scan time in the
Use the direct access input (DX) and so on to read
sequence program fall under the following
out the counter value coincidence No.m (X02 and
Section 5.3.2
X05) within the time set by the continuous
Scan time > continuous comparison No.m ON
comparison No.m ON time setting (Un\G52 and
time setting (Un\G52 and 102)
102).
"m" indicates the continuous comparison number.
request)? · ring counter? · condition?

8.5 When the Counter Value Coincidence No.1 (X02) or Counter Value Coincidence No.2 (X05) are Turned ON, but the Coincidence Output No.1 Terminal (EQU1) and Coincidence Output No.2 Terminal (EQU2) do not Turn ON
Table 8.11 When the counter value coincidence No.1 (X02) or counter value coincidence No.2 (X05) are turned ON but the
coincidence output No.1 terminal (EQU1) and coincidence output No.2 terminal (EQU2) do not turn ON
Check item Action Reference
Is the coincidence output enable command (Y03)
Turn ON the coincidence output enable command
Section 3.3
(Y03).
(Only for the coincidence output function)
Is a voltage applied to the external coincidence
Apply a voltage to the external coincidence output
output power supply terminal.
power supply terminal.
If the FUSE LED is ON, the fuse is blown.
Please consult your local Mitsubishi
Is the fuse blown?
Section 3.5
representative, explaining a detailed description of
Section 4.4
the problem. Is the external wiring of the coincidence output
No.1 terminal (EQU1) and coincidence output
Check the external wiring and correct the error.
No.2 terminal (EQU2) correct?
Table 8.12 When the coincidence detection interrupt does not occur
Check item Action Reference
Change the CPU module to the one which
Does the CPU module support the coincidence
supports the intelligent function module event
Section 2.1 (1)
interrupt.
If the setting made on [Interrupt pointer setting] of
Check the intelligent function module interrupt
[Intelligent function module setting ] in [PLC
pointer setting. Section 5.3
Is the way to use the program execution control
instruction, such as IMASK, correct? Check the sequence program. Section 5.3
Reset (OFF) the counter value coincidence No.m
Is the counter value coincidence (X02 and X05)
(X02 and X05) by the coincidence signal No.m
Section 3.3.2
reset command (Y01 and Y02) for the
(Only for the coincidence output function)
corresponding number.
8.5 When the Counter Value Coincidence No.1 (X02) or Counter Value Coincidence No.2 (X05) are Turned ON, but the Coincidence Output No.1 Terminal (EQU1) and Coincidence Output No.2 Terminal (EQU2) do 8 - 6

Table 8.13 When the coincidence output function cannot be executed
Check item Action Reference
While selecting the coincidence output function,
Has the counter value comparison function
the coincidence output test function cannot be
selection been set to the coincidence output
used. To perform wiring check while selecting a
Section 5.3.1 (2)
coincidence output function, refer to procedure in
Section 5.3.1 (2).
function?

Table 8.14 When the preset cannot be executed by the preset command (Y04)
Check item Action Reference
Is the ON and OFF time of the preset command
(Y04) 2ms or longer? Set the ON and OFF time 2ms or longer.
Turn ON the external preset request detection
reset command (Y08), and reset (OFF) the
Section 3.3 Is the external preset request detection (X08)
external preset request detection (X08).
At the time, set the ON and OFF time of the
external preset request detection reset command
(Y08) 2ms or longer.
8.8.2 When the preset cannot be executed by the preset input terminal (PRST)
Table 8.15 When the preset cannot be executed by the preset input terminal (PRST)
Check item Action Reference
Is the external wiring of the preset input terminal
(PRST) correct? Check the external wiring and correct the error. Section 3.5
Is the interval after changing the preset value
setting (Un\G4 and 5) until turning ON the preset
Set the interval 2ms or longer. Section 3.4
input terminal (PRST) 2ms or longer?
Turn ON the external preset request detection
reset command (Y08), and reset (OFF) the
Is the external preset request detection (X08)
external preset request detection (X08).
Section 3.3
At the time, set the ON and OFF time of the
external preset request detection reset command
(Y08) longer than 2ms.
8.8 When the Preset Cannot be Executed 8.8.1 When the preset cannot be executed by the preset command (Y04) 8 - 8

8.9.1 When the latch counter function cannot be executed by the latch counter execution command (Y07)
Table 8.16 When the latch counter function cannot be executed by the latch counter execution command (Y07)
Check item Action Reference
Is the ON and OFF time of the latch counter
execution command (Y07) longer than 2ms? Set the ON and OFF time 2ms or longer. Section 3.3
Is the latch counter input terminal (LATCH) ON? Turn OFF the latch counter input terminal
(LATCH). Section 5.5
8.9.2 When the latch counter function cannot be executed by the latch counter input terminal (LATCH)
Table 8.17 When the latch counter function cannot be executed by the latch counter input terminal (LATCH)
Check item Action Reference
Is the external wiring of the latch counter input
terminal (LATCH) correct? Check the external wiring and correct the error. Section 3.5
Is the latch counter execution command (Y07)
Turn OFF the latch counter execution command
(Y07). Section 5.5
8.10 When the Error Code (Un\G18)/Warning Code (Un\G19) Cannot be Reset
Table 8.18 When the error code (Un\G18)/warning code (Un\G19) cannot be reset
Check item Action Reference
Is the cause of the error/warning fixed? Refer to the description and action columns in error
code and warning code list, and fix the cause. Section 8.11
Is the ON and OFF time of the error reset
command (Y0D) 2ms or longer. Set the ON and OFF time 2ms or longer. Section 3.3

This section describes the descriptions and corrective actions for the errors detected by the QD64D2.
Table 8.19 Error code list
code Description Action Operation at error
Error channel Other channels
0 (Normal)
The present value (Un\G12 and 13) exceeded the
Perform the preset.
following range.
(Refer to Section 5.4.)
counting.
(Only for the linear counter function)
[Continuous comparison No.m start point setting error]
The continuous comparison No.m start point setting
Set a value from 1 to 16.
(Un\G50 and 100) is set to other than 1 to 16.
"m" indicates the continuous comparison number
where the error occurred.
[Continuous comparison No.m repeat point setting
be started. (The
Set a value from 1 to 16. The continuous comparison No.m repeat point setting
(Un\G51 and 101) is set to other than 1 to 16.
channels.
"m" indicates the continuous comparison number
where the error occurred.
[Continuous comparison No.m ON time setting error]
number.)
Set a value from 1 to 10. The continuous comparison No.m ON time setting
(Un\G52 and 102) is set to other than 1 to 10.
"m" indicates the continuous comparison number
where the error occurred.
[Count enable execution not possible error]
The count enable command (Y06) is turned ON while
Turn OFF the coincidence
one of the following is ON.
output test command which is
ON.
counting.
8.11 Action and Handling of Errors 8.11.1 Error code list 8 - 10
![Page 144 of the Mitsubishi Electronics MELSEC-Q Counter Module (QD64D2) user manual — CPU]](/cdn/reader/92/92b7e7cbdd0998367f9879cdb7e62a6fcd0990ef3093e1ce0c853520a461033d/images/page-144.webp?w=400)
Table 8.19 Error code list (continued)
code Description Action Operation at error
Error channel Other channels
[Continuous comparison No.m execution not possible
The continuous comparison No.m execution
Turn OFF the coincidence
be started. (The
command (Y09 and Y0A) is turned ON while one of
output test command, then turn
the following is ON.
ON the continuous comparison
execution command.
"m" indicates the continuous comparison number
number.)
where the error occurred.
channels.
[Ring counter upper/lower limit value setting error]
The count enable command (Y06) is turned ON
Set a value as follows.
under the following condition.
(Lower limit value Upper limit
(Ring counter lower limit value (Un\G0 and 1)) >
start counting.
(Ring counter upper limit value (Un\G2 and 3))
(Only for the ring counter function)
Set a correct value in GX
Developer and perform [Write to
An invalid value is set in the switch setting for
PLC]. After that, power OFF
intelligent function module in GX Developer.
then ON the programmable
controller CPU or reset it. (Refer
to Section 4.5.)
[Programmable controller CPU error]
An error occurred in the programmable controller
CPU.
Power OFF then ON the
[Watchdog timer error of programmable controller
programmable controller CPU or
reset it.
A watchdog timer error occurred in the programmable
controller CPU.
Power OFF then ON the
stopped.
programmable controller CPU or
An error occurred in the module.
reset it.
monitor is stopped.
If an error occurs again, replace
the module.
OFF.
850 [Hardware error] Replace the module. A hardware error occurred.
consult your local Mitsubishi
representative.
The fuse of the external coincidence output part is
module with a blown fuse, do
blown.
not apply a voltage to the
power supply terminal and
power OFF then ON or reset
CPU.

(1) When another error occurs during error occurrence, take the following action.
ignored and the error code stored before the latest error code is held. • When an error code from 810 to 860 occurs, the error code is overwritten
as the latest one. (2) The error code 810 is stored for each channel, and the error code from 820 to
860 is stored for all channels. (3) After fixing the cause of the error, reset the error by the error reset command
(Y0D). If the cause of the error is not fixed, the error is detected again.
8.11 Action and Handling of Errors 8.11.1 Error code list 8 - 12

This section describes the descriptions and corrective actions for the warnings detected by the QD64D2.
Table 8.20 Warning code list
code Description Action Operation at warning
0 (Normal)
[Coincidence output No.m test output not possible]
The coincidence output No.m test command (Y0B
and Y0C) is turned ON while one of the following is
ON.
be started.
Turn OFF the all signals listed
on the left.
not affect the other
other channels.
number.)
"m" indicates the continuous comparison number
where the warning occurred.
code is overwritten as the latest one. • After fixing the cause of the warning, reset the warning by the error reset
command (Y0D). If the cause of the warning is not fixed, the warning is detected again.



Memo
App - 2 Appendix 2 Difference with the QD62D

Please confirm the following product warranty details before using this product.
If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company. However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module. [Gratis Warranty Term] The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range] (1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc.,
which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product. (2) Even within the gratis warranty term, repairs shall be charged for in the following cases. 1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design. 2. Failure caused by unapproved modifications, etc., to the product by the user. 3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided. 4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced. 5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage. 6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi. 7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.
(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is
discontinued. Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc. (2) Product supply (including repair parts) is not available after production is discontinued.
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ.
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation of damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not , compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.

Microsoft, Windows, Windows NT, and Windows Vista are registered trademarks of Microsoft Corporation in the United States and other countries. Pentium is a trademark of Intel Corporation in the United States and other countries. Ethernet is a trademark of Xerox Corporation. All other company names and product names used in this manual are trademarks or registered trademarks of their respective companies. SPREAD Copyright (C) 1996 Farpoint Technologies, Inc.



HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN NAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| X05 | within the time set by the continuous | p.138 | |
| 0 | (Normal) | ---- | p.143 |
| 100 | [Overflow error] The present value (Un\G12 and 13) exceeded the following range. -2147483648 to 2147483647 (Only for the linear counter function) | Perform the preset. (Refer to Section 5.4.) | p.143 |
| 20m | [Continuous comparison No.m start point setting error] The continuous comparison No.m start point setting (Un\G50 and 100) is set to other than 1 to 16. "m" indicates the continuous comparison number where the error occurred. | Set a value from 1 to 16. | p.143 |
| 21m | [Continuous comparison No.m repeat point setting error] The continuous comparison No.m repeat point setting (Un\G51 and 101) is set to other than 1 to 16. "m" indicates the continuous comparison number where the error occurred. | Set a value from 1 to 16. | p.143 |
| 22m | [Continuous comparison No.m ON time setting error] The continuous comparison No.m ON time setting (Un\G52 and 102) is set to other than 1 to 10. "m" indicates the continuous comparison number where the error occurred. | Set a value from 1 to 10. | p.143 |
| 300 | [Count enable execution not possible error] The count enable command (Y06) is turned ON while one of the following is ON. •Coincidence output No.1 test command (Y0B) •Coincidence output No.2 test command (Y0C) | Turn OFF the coincidence output test command which is ON. | p.143 |
| 31m | [Continuous comparison No.m execution not possible error] The continuous comparison No.m execution command (Y09 and Y0A) is turned ON while one of the following is ON. •Coincidence output No.1 test command (Y0B) •Coincidence output No.2 test command (Y0C) "m" indicates the continuous comparison number where the error occurred. | Turn OFF the coincidence output test command, then turn ON the continuous comparison execution command. | p.144 |
| 500 | [Ring counter upper/lower limit value setting error] The count enable command (Y06) is turned ON under the following condition. (Ring counter lower limit value (Un\G0 and 1)) > (Ring counter upper limit value (Un\G2 and 3)) (Only for the ring counter function) | Set a value as follows. (Lower limit value Upper limit value) | p.144 |
| 810 | [Switch setting error] An invalid value is set in the switch setting for intelligent function module in GX Developer. | Set a correct value in GX Developer and perform [Write to PLC]. After that, power OFF then ON the programmable controller CPU or reset it. (Refer to Section 4.5.) | p.144 |
| 820 | [Programmable controller CPU error] An error occurred in the programmable controller CPU. | Power OFF then ON the programmable controller CPU or reset it. | p.144 |
| 830 | [Watchdog timer error of programmable controller CPU] A watchdog timer error occurred in the programmable controller CPU. | p.144 | |
| 840 | [Module error] An error occurred in the module. | Power OFF then ON the programmable controller CPU or reset it. If an error occurs again, replace the module. | p.144 |
| 850 | [Hardware error] A hardware error occurred. | Replace the module. | p.144 |
| 860 | [Blown fuse error] The fuse of the external coincidence output part is blown. | •For replacement of fuse, please consult your local Mitsubishi representative. •When temporarily using the module with a blown fuse, do not apply a voltage to the external coincidence output power supply terminal and power OFF then ON or reset the programmable controller CPU. | p.144 |