MELSEC System Q
Programmable Logic Controllers
User’s Manual
High Performance Model QCPU
Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU,
Q25HCPU
Art. no.: 130000 01 10 2002 SH (NA)-080037-F

When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in this manual. Also pay careful attention to safety and handle the module properly. These SAFETY PRECAUTIONS classify the safety precautions into two categories: "DANGER" and "CAUTION".

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Depending on circumstances, procedures indicated by ! CAUTION may also be linked to serious results. In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.
! DANGER
Install a safety circuit external to the PLC that keeps the entire system safe even when there
are problems with the external power supply or the PLC module. Otherwise, trouble could result from erroneous output or erroneous operation. (1) Outside the PLC, construct mechanical damage preventing interlock circuits such as
emergency stop, protective circuits, positioning upper and lower limits switches and interlocking forward/reverse operations. (2) When the PLC detects the following problems, it will stop calculation and turn off all output
in the case of (a). In the case of (b), it will stop calculation and hold or turn off all output according to the parameter setting. Note that the AnS series module will turn off the output in either of cases (a) and (b).
(a) The power supply module has over current protection equipment and over voltage
protection equipment. (b) The PLC CPUs self-diagnosis functions, such as the watch dog timer error, detect
problems. In addition, all output will be turned on when there are problems that the PLC CPU cannot detect, such as in the I/O controller. Build a fail safe circuit exterior to the PLC that will make sure the equipment operates safely at such times. See section 9.1 of this manual for example fail safe circuits. (3) Output could be left on or off when there is trouble in the outputs module relay or transistor.
So build an external monitoring circuit that will monitor any single outputs that could cause serious trouble.

! DANGER
When overcurrent which exceeds the rating or caused by short-circuited load flows in the output
module for a long time, it may cause smoke or fire. To prevent this, configure an external safety circuit, such as fuse. Build a circuit that turns on the external power supply when the PLC main module power is
turned on. If the external power supply is turned on first, it could result in erroneous output or erroneous operation. When there are communication problems with the data link, refer to the corresponding data link
manual for the operating status of each station. Not doing so could result in erroneous output or erroneous operation. When connecting a peripheral device to the CPU module or connecting a personal computer or
the like to the intelligent function module to exercise control (data change) on the running PLC, configure up an interlock circuit in the sequence program to ensure that the whole system will always operate safely. Also before exercising other control (program change, operating status change (status control)) on the running PLC, read the manual carefully and fully confirm safety. Especially for the above control on the remote PLC from an external device, an immediate action may not be taken for PLC trouble due to a data communication fault. In addition to configuring up the interlock circuit in the sequence program, corrective and other actions to be taken as a system for the occurrence of a data communication fault should be predetermined between the external device and PLC CPU.
Do not bunch the control wires or communication cables with the main circuit or power wires, or
install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that would cause erroneous operation.
When controlling items like lamp load, heater or solenoid valve using an output module, large
current (approximately ten times greater than that present in normal circumstances) may flow when the output is turned OFF to ON. Take measures such as replacing the module with one having sufficient rated current.

! CAUTION
Use the PLC in an environment that meets the general specifications contained in this manual.
Using this PLC in an environment outside the range of the general specifications could result in electric shock, fire, erroneous operation, and damage to or deterioration of the product.
Hold down the module loading lever at the module bottom, and securely insert the module
fixing latch into the fixing hole in the base unit. Incorrect loading of the module can cause a malfunction, failure or drop. When using the PLC in the environment of much vibration, tighten the module with a screw. Tighten the screw in the specified torque range. Undertightening can cause a drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to damage to the screw or module.
When installing extension cables, be sure that the connectors of base unit are installed
correctly. After installation, check them for looseness. Poor connections could cause an input or output failure.
Securely load the memory card into the memory card loading connector. After loading, check
for lifting. Lifting can cause a malfunction due to a contact fault.
Completely turn off the external power supply before loading or unloading the module. Not
doing so could result in electric shock or damage to the product.
Do not directly touch the module's conductive parts or electronic components. Touching the
conductive parts could cause an operation failure or give damage to the module.
! DANGER
Completely turn off the external power supply when installing or placing wiring. Not completely
turning off all power could result in electric shock or damage to the product.
When turning on the power supply or operating the module after installation or wiring work, be
sure that the module's terminal covers are correctly attached. Not attaching the terminal cover could result in electric shock.

! CAUTION
Be sure to ground the FG terminals and LG terminals to the protective ground conductor. Not
doing so could result in electric shock or erroneous operation.
When wiring in the PLC, be sure that it is done correctly by checking the product's rated voltage
and the terminal layout. Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or damage.
External connections shall be crimped or pressure welded with the specified tools, or correctly
soldered. Imperfect connections could result in short circuit, fires, or erroneous operation.
Tighten the terminal screws with the specified torque. If the terminal screws are loose, it could
result in short circuits, fire, or erroneous operation. Tightening the terminal screws too far may cause damages to the screws and/or the module, resulting in fallout, short circuits, or malfunction.
Be sure there are no foreign substances such as sawdust or wiring debris inside the module.
Such debris could cause fires, damage, or erroneous operation.
The module has an ingress prevention label on its top to prevent foreign matter, such as wire
offcuts, from entering the module during wiring. Do not peel this label during wiring. Before starting system operation, be sure to peel this label because of heat dissipation.
! DANGER
Do not touch the terminals while power is on.
Doing so could cause shock or erroneous operation.
Correctly connect the battery.
Also, do not charge, disassemble, heat, place in fire, short circuit, or solder the battery. Mishandling of battery can cause overheating or cracks which could result in injury and fires.
Switch all phases of the external power supply off when cleaning the module or retightening the
terminal or module mounting screws. Not doing so could result in electric shock. Undertightening of terminal screws can cause a short circuit or malfunction. Overtightening of screws can cause damages to the screws and/or the module, resulting in fallout, short circuits, or malfunction.

! DANGER
The online operations conducted for the CPU module being operated, connecting the peripheral
device (especially, when changing data or operation status), shall be conducted after the manual has been carefully read and a sufficient check of safety has been conducted. Operation mistakes could cause damage or problems with of the module.
Do not disassemble or modify the modules.
Doing so could cause trouble, erroneous operation, injury, or fire.
Use any radio communication device such as a cellular phone or a PHS phone more than 25cm
(9.85 inch) away from the PLC. Not doing so can cause a malfunction.
Switch all phases of the external power supply off before mounting or removing the module.
If you do not switch off the external power supply, it will cause failure or malfunction of the module.
Do not drop or give an impact to the battery installed in the module.
Otherwise the battery will be broken, possibly causing internal leakage of electrolyte. Do not use but dispose of the battery if it has fallen or an impact is given to it.
! CAUTION
When disposing of this product, treat it as industrial waste.

The manual number is given on the bottom left of the back cover. Print Date Manual Number Revision Dec., 1999 SH(NA)-080037-A First edition Sep., 2000 SH(NA)-080037-B Addition model
Q33B, Q63B, Q63P Addition Section 2.3, 4.5, 11.2.3, 11.2.10, 11.2.11 Partial correction Section 1.2, 2.2, 4.1, 4.2, 5.1.1, 5.2, 8.1.5, 11.2.1, 11.3.2, 11.5.1, 11.6, 11.7 Jun., 2001 SH(NA)-080037-C Addition model
Q62P, Q52B, Q55B, QC05B Addition Section 6.6 Partial correction Section 2.1, 2.2, 4.1, 4.2, 5.1.5, 6.1, 6.2, 6.3, 8.1.5, 11.2.4, 11.7 Sep., 2001 SH(NA)-080037-D Addition model
Q64P Partial correction CONTENTS, Section 4.1, 5.1.1, 5.1.2, 5.2, 6.1, 6.2, 8.1.5, 11.5.1, Appendix1.2, 2.2 Apr., 2002 SH(NA)-080037-E Partial correction
Chapter 1, Section 1.1, 2.1, 2.2, 2.3, 4.1, 5.1.1, 7.1, 7.2, 7.3, 10.3.1, 10.3.2 Oct., 2002 SH(NA)-080037-F Complete review
Japanese Manual Version SH-080019-I
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
A - 6 A - 6


The following manuals are related to this product.
Referring to this list, please request the necessary manuals.
Manual Name Manual Number
(Model Code)
High Performance model QCPU (Q Mode) User's Manual (Function Explanation, Program Fundamentals)
SH-080038
This manual explains the functions, programming methods, devices and so on necessary to create
programs with the High Performance model QCPU. (sold separately)
SH-080039
This manual describes how to use the sequence instructions, basic instructions and application
instructions. (sold separately)
SH-080040
(13JF59)
This manual describes the dedicated instructions used to exercise PID control. (sold separately)
SH-080041
This manual explains the system configuration, performance specifications, functions, programming,
debugging, error codes and others of MELSAP3. (sold separately)
SH-080076
This manual describes the programming methods, specifications, functions, and so on that are
necessary to create the MELSAP-L type SFC programs. (sold separately)

This manual is prepared for users to understand the hardware specifications of those modules such as the CPU modules, power supply modules, and base units, maintenance and inspections of the system, and troubleshooting required when you use MELSEC-Q series PLCs.
The manual is classified roughly into three sections as shown below.
This manual does not explain the functions of the CPU module. For these functions, refer to the manual shown below. • High Performance model QCPU (Q Mode) User's Manual (Function Explanation, Program Fundamentals)

This manual uses the following general names and abbreviations in the descriptions of the High Performance model QCPU unless otherwise specified.
General name for Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU modules. Q Series Abbreviation for Mitsubishi MELSEC-Q Series Programmable Logic Controller.
AnS Series Abbreviation for small types of Mitsubishi MELSEC-A Series Programmable Logic Controller. GX Developer General name for GX Developer Version 4 or later.
General name for Q33B, Q35B, Q38B, Q312B type main base unit with High Performance model QCPU and Q Series power supply module, I/O module and intelligent function module attachable.
General name for Q32SB, Q33SB, Q35SB slim type main base unit with High Performance model QCPU and slim type power supply module, I/O module and intelligent function module attachable.
Q5 B General name for Q52B and Q55B type extension base unit with Q Series I/O module and intelligent function module attachable.
Q6 B General name for Q63B, Q65B, Q68B and Q612B type extension base unit with Q Series power supply module, I/O module and intelligent function module attachable.
QA1S6 B General name for QA1S65B and QA1S68B type extension base unit with AnS Series power supply module, I/O module and special function module attachable.
General name for Q33B, Q35B, Q38B, Q312B type main base unit with High Performance model QCPU and Q Series power supply module, I/O module and intelligent function module attachable.
General name for Q32SB, Q33SB, Q35SB slim type main base unit with High Performance model QCPU and slim type power supply module, I/O module and intelligent function module attachable. Extension base unit General name for Q5 B, Q6 B and QA1S6 B. SRAM card Abbreviation for Q2MEM-1MBS, Q2MEM-2MBS type SRAM card. Flash card General name for Q2MEM-2MBF and Q2MEM-4MBF types Flash card.
ATA card General name for Q2MEM-8MBA, Q2MEM-16MBA and Q2MEM-32MBA types ATA card. Memory card General name for SRAM card, Flash card and ATA card.
Power supply module General name for Q61P-A1, Q61P-A2, Q62P, Q63P, Q64P, A1S61PN, A1S62P and A1S63P types power supply module. Slim type power supply module General name for Q61SP slim type power supply module
Battery General name for battery for Q6BAT type CPU module and Q2MEM-BAT type SRAM card.
Extension cable General name for QC05B, QC06B, QC12B, QC30B, QC50B, QC100B type extension cable.

1 OVERVIEW
This Manual describes the hardware specifications and handling methods of the High Performance model QCPU. The Manual also describes those items related to the specifications of the power supply module, main base unit, extension base unit, extension cable, memory card and battery. Functions are added when the High Performance model QCPU is updated. The added functions can be discriminated by the function version/serial number of the CPU module. Table 1.1 gives the added functions and the corresponding GX Developer versions. When using the added function, confirm the function version/serial number and the GX Developer version. Table 1.1 List of Functions Added to High Performance Model QCPU and Function
Update Details of High Performance Model QCPU Function
Corresponding
GX Developer
version Serial No. Added functions
Version 6 or later
— • Compatibility with the multiple CPU system Version 6 or later
"03051" or later • Installation of PC CPU module into the
Version 7.10L or later
" 04012 " or later
POINT (1) For the details of the added functions in Table 1.1, refer to the High
Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals). (2) Refer to Section 2.3 for the serial No. and function version of the High
Performance model QCPU.

1.1 Features
High Performance model QCPU has the following new features: (1) Controllable multiple I/O points
All High Performance model QCPUs support 4096 points (X/Y0 to FFF) as the number of actual I/O points capable of getting access to the I/O module installed on the base unit. They also support 8192 points max. (X/YO to 1FFF) as the number of I/O devices which can be used in the remote I/O stations such as MELSECNET/H remote I/O NET, CC-Link data link and MELSECNET/MINI-S3 data link.
The optimum CPU module for the program capacity to be used can be selected. Q02CPU, Q02HCPU : 28k step Q06HCPU : 60k step Q12HCPU : 124k step Q25HCPU : 252k step
Depending on the type of the sequencer, high speed processing has been realized.(Example: when LD instruction is used) Q02CPU : 0.079 s Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU : 0.034 s In addition, an access to the intelligent function module or an increase in speed of the link refresh of the network have been realized by the connection system (System bus connection) of the newly developed base unit. Access to the intelligent function module : 20 s /word (approx. 7 times) 1 MELSECNET/H link refresh processing : 4.6ms/8k word (approx. 4.3 times) 1 1: Where Q02HCPU is compared with Q2ASHCPU-S1.
communication with GX Developer In the High Performance model QCPU, a time required for writing/reading of a program or monitoring has been reduced through the high speed communication at a speed of 115.2kbps max. by the RS-232, and a communication time efficiency at the time of debugging has been increased. In the Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU, a high speed communication at a speed of 12Mbps is allowed through the USB.
Q25HCPU(RS-232)
Q2ASHCPU
A2USHCPU-S1
(Unit:s) 90 100
0 10 20 30 40 50 60 70 80
(5) AnS series I/O module or special function module are available.
For Q series, if an appropriate module is not available, the AnS series I/O module or special function module can also be used for the High Performance model QCPU through the use of the QA1S65B/QA1S68B extension base unit.

(6) Saved space by a reduction in size
The installation space for Q series has been reduced by approx. 60 % of the space for AnS series.
Comparison of installation space

98mm (3.86 inch)
(7) Connection of up to seven extension base units.
units (eight base units including the main) and accept up to 64 modules.
(b) The overall distance of the extension cables is up to 13.2m to ensure high
degree of extension base unit arrangement.
The High Performance model QCPU is provided with a memory card installation connector to which a memory card of 32 Mbyte max. can be connected (32 Mbyte is available when a ATA card is used). When a memory card of large capacity is installed, a large capacity of file can be controlled, comments to all data devices can be set up, and the programs in the past can be stored in the memory as they are in the form of the corrected histories. If a memory card is not installed, a program can be stored onto the standard ROM built in the CPU module, and file registers can be handled by the standard RAM.
CPU Module Type Number of File Registers Q02CPU 32k points First 5 digits of serial number are "04011" or earlier 32k points Q02HCPU Q06HCPU First 5 digits of serial number are "04012" or later 64k points First 5 digits of serial number are "02091" or earlier 32k points Q12HCPU Q25HCPU First 5 digits of serial number are "02092" or later 128k points

Refer to Section 2.3 to confirm the function version and serial number of the High Performance model QCPU.

(9) Data can be written automatically to standard ROM
You need not use GX Developer to write parameters/programs on a memory card to the standard ROM of the High Performance model QCPU. When the standard ROM is used to perform ROM operation, you can load a memory card into the High Performance model QCPU and write parameters/programs on the memory card to the standard ROM. Hence, you need not carry GX Developer (personal computer) to rewrite the parameters/programs.
If the High Performance model QCPU is in the RUN mode, you can operate GX Developer to turn external inputs/outputs ON/OFF forcibly, independently of the program execution status. You need not put the High Performance model QCPU in the STOP mode to perform wiring/operation tests by forced ON/OFF of outputs.
When access to an Ethernet module or serial communication module is made externally, whether access to the High Performance model QCPU can be made or not can be selected with a remote password.
You can load the remote master station of the MELSECNET/H to configure an MELSECNET/H remote I/O system.
the High Performance model QCPU (b) Protection of the memory card by setting the write protect switch of the memory
card (c) File-by-file protection using password • The MELSECNET/H remote I/O network facility can be executed when the MELSECNET/H network module of function version B and GX Developer (Version 6 or later) are used.

2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM
This section describes the system configuration of the High Performance model QCPU, cautions on use of the system, and configured equipment. 2.1 System Configuration
The outline of the equipment configuration, configuration with peripheral devices, and system configuration in the High Performance model QCPU system is described below.
(a) If the main base unit (Q3 B) is used
MITSUBISHI LITHIUM BATTERY
High Performance model QCPU (Q02CPU,Q02HCPU,Q06HCPU,
Q12HCPU,Q25HCPU)
Q2MEM-32MBA)
Power supply module , I/O module , Intelligent function
Main base unit (Q33B, Q35B,Q38B,Q312B)
module of the Q Series
Extension of the AnS Series module Extension of the Q Series module
Q5 B extension base unit
Extension cable (QC05B,QC06B,QC12B, QC30B, QC50B,QC100B)
QA1S6 extension base unit
(Q52B, Q55B) Q6 B extension base unit (Q63B, Q65B,Q68B,Q612B)
Power supply module , I/O module , Intelligent function
Power supply module , I/O module , Intelligent function
module of the AnS Series
module of the Q Series
POINTS 1: The number of memory cards to be installed is one sheet. The memory card must be selected from SRAM card, Flash card, and ATA card according to the application and capacity. With commercial memory cards, the Operation is not assured. 2: QA1S65B and QA1S68B extension base units are used for the power supply module, I/O module, and special function module of the AnS series. 3: The Q series power supply module is not required for the Q5 B type extension base unit. 4: Q61SP cannot be used for the power supply module. Use Q61P-A1, Q61P-A2, Q62P, or Q64P for the power supply module.
Memory card (Q2MEM-1MBS,Q2MEM-2MBS, · Battery (Q6BAT)

(b) If the slim type main base unit (Q3SB) is used

POINTS 1: The number of memory cards to be installed is one sheet. The memory card must be selected from SRAM card, Flash card, and ATA card according to the application and capacity. With commercial memory cards, the Operation is not assured. 2: The slim type main base unit does not have an extension cable connector. The extension base unit and GOT cannot be connected. 3: Q61P-A1, Q61P-A2, Q62P, or Q64P cannot be used for the power supply module. Use Q61SP for the power supply module.

(2) Configuration of peripheral devices

Only Q02HCPU, Q06HCPU Q12HCPU and Q25HCPU can be used.

(3) Outline of system configuration
(a) If the main base unit (Q3 B) is used
0 1 2 3 4 5 6 7 8 9 10 11
Slot No.
E0
OUT
1F
3F
5F
7F
9F
BF
DF
FF
11F
13F
15F
17F
The figure shows the configuration when 32-I/O modules are loaded to each slot. OUT IN
22 21 20 19 18 17 16 15 14 13 12 2A0
1E0
2E0
19F
1BF
1DF
1FF
21F
23F
25F
27F
29F
2BF
2DF
2FF
31 30 29 28 27 26 25 24 3E0
52 51 50 49 48 47 46 45 680
5A0
5E0
OUT IN
OUT IN
System configuration
31F
33F
35F
37F
39F
3BF
3DF
3FF
5BF
5DF
5FF
61F
63F
65F
67F
69F
39 38 37 36 35 34 33 32 4E0
60 59 58 57 56 55 54 53 780
6A0
6E0
OUT IN
OUT IN
41F
43F
45F
47F
49F
4BF
4DF
4FF
6BF
6DF
6FF
71F
73F
75F
77F
79F
44 43 42 41 40 580
7A0
OUT IN
OUT IN
51F
53F
55F
57F
59F
7BF
7DF
7FF
When module is installed, an error occurs.
Maximum number of I/O modules to be installed
64 modules
Maximum number of occupied I/O points 4096
Main base unit Q33B, Q35B, Q38B, Q312B Extension base unit Q52B, Q55B, Q63B, Q65B, Q68B, Q612B, QA1S65B, QA1S68B Extension cable QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
(1) Extension bases unit of up to seven stages can be used. (2) Do not use extension cable longer than an overall extension length of 13.2m(43.31ft.). (3) When using an extension cable, do not bind it together with the main circuit (high voltage and
heavy current) line or do not lay down them closely to each other. (4) When setting the No. of the expansion stages, set it in the ascending order so that the same
No. is not set simultaneously by two extension base units. (5) When Q5 B, Q6 B and QA1S6 B types of extension base units are mixed, first connect the Q5 B, Q6 B type and then connect the QA1S6 B type. When setting the No. of the extension stages, set it from Q5 B/Q6 B in order. Although there are no particular restrictions in the order of the installation of the Q5 B and Q6 B, refer to Section 6.6 for usability. (6) Connect the extension cable from OUT of the extension cable connector of the base unit to IN
of the extension base unit on the next stage. (7) If 65 or more modules are installed, an error will occur. (8) When the GOT is bus-connected, it occupies one extension stage and one slot. (9) The High Performance model QCPU processes the GOT as a 16-point intelligent function
module. Hence, connecting one GOT decreases 16 points available for the base unit. (10) Q61SP cannot be used for the power supply module.
Use Q61P-A1, Q61P-A2, Q62P, or Q64P for the power supply module.

(b) If the slim type main base unit (Q3SB) is used
0 1 2 3 4 Slot No. Slim type main base unit (Q35SB)
3F
5F
7F
9F
The above system assumes that each slot is loading with a 32-point module.
Maximum number of I/O modules to be installed
5 modules
Maximum number of occupied I/O points 4096
Main base unit Q32SB, Q33SB, Q35SB Extension base unit Cannot be connected. Extension cable Cannot be connected.
(1) Q61P-A1, Q61P-A2, Q62P, or Q64P cannot be used for the power supply module.
Use Q61SP for the power supply module. (2) The slim type main base unit does not have an extension cable connector.
The extension base unit and GOT cannot be connected.
Power supply · CPU module · module

2.2 Precaution on System Configuration
This section describes hardware and software packages compatible with QCPU. (1) Hardware
(a) The number of modules to be installed and functions are limited depending on
the type of the modules.
to be installed
Up to 4 in total of inter-PLC network and remote I/O network modules
No limit (setting of automatic refresh function not allowed)
MELSECNET/MINI-S3 data link module
Total of 6 units
Input (X), Output (Y) X/Y0 to 7FF
Internal relay (M), Latch relay (L) M0 to 8191
Link relay (B) B0 to FFF
Timer (T) T0 to 2047
Counter (C) C0 to 1023
Data register (D) D0 to 6143
Link register (W) W0 to FFF
Annunciator (F) F0 to 2047
(c) A graphic operation terminal can be used only for the GOT900 series (Basic
OS matching Q mode and communication driver must be installed). The GOT800 series, A77GOT, and A64GOT cannot be used.

(d) The modules shown below cannot be used.

(e) A dedicated instruction for the next module which was present in the QnA/A
series program instruction cannot be used for the High Performance model QCPU. Re-writing using FROM/TO instruction is required.

parameter of the "High speed interrupt fixed scan interval" setting. Refer to the following manual for the restrictions when the parameter of the "High speed interrupt fixed scan interval" setting has been written. • High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals) Note that the above restrictions do not apply to the High Performance model QCPU of serial number "04011" or earlier since it ignores the "High speed interrupt fixed scan interval" setting.
GX Developer that can use the functions added to the High Performance model QCPU changes depending on the function version/serial number of the CPU module.

Refer to Section 2.3 to confirm the function version and serial number of the High Performance model QCPU.

2.3 Confirming the Serial Number and Function Version
The CPU module serial No. can be confirmed on the rated plate and GX Developer's system monitor. (1) Confirming the serial No. on the rated plate
The serial No. and function version can be confirmed on the rating plate.

Serial No. (First five digits)
information) The CPU module serial No. and function version can be confirmed with the list of product information on the GX Developer (Version 6 or later) system monitor. Serial Nos. and function versions of the intelligent function module and CPU module can also be confirmed.
Serial number Function version

Function version

3 GENERAL SPECIFICATIONS

Shock resistance Conforming to JIS B 3502, IEC 61131-2 (147 m/s2, 3 times in each of 3 directions X, Y, Z)
1 : This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V. 2 : This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected occasionally. 3 : The storage ambient temperature is -20 to 75°C if the system includes the AnS series modules. 4 : The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system includes the AnS series modules. 5 : Do not use or store the PLC under pressure higher than the atmospheric pressure of altitude 0m. Doing so can cause a malfunction. When using the PLC under pressure, please contact your sales representative.

MEMO

4 HARDWARE SPECIFICATION OF THE CPU MODULE
4.1 Performance Specification
The table below shows the performance specifications of the CPU module.
Control method Repetitive operation of stored program
Direct I/O is possible by direct I/O specification (DX , DY ) Programming language (Sequence control dedicated language)
I/O control mode Refresh mode
Relay symbol language, logic symbolic language,
LD X0 0.079 s 0.034 s —— Processing speed (Sequence instruction) MOV D0 D1 0.237 s 0.102 s ——
Constant scan (Function for setting the scan timer to fixed settings)
0.5 to 2000 ms (configurable in increments of 0.5 ms) Set parameter values to
Program memory (Drive 0) 28k step 60k step 124k step 252k step ——
Program memory (Drive 0) 112 kbyte 240 kbyte 496 kbyte 1008 kbyte ——
Memory card (RAM) (Drive 1) Capacity of loading memory cards(2Mbyte max.)
For memory capacity, refer to Section 7.1.
Memory card (ROM) (Drive 2)
Installed memory card capacity (Flash card: 4 Mbyte max., ATA card: 32 Mbyte max.)
Standard ROM (Drive 4) 112 kbyte 240 kbyte 496 kbyte 1008 kbyte ——
Program memory 28 60 124 252 1 —— Memory card (RAM) 256 —— Flash card 288 —— Memory card (ROM) ATA card 512 ——
Maximum number of stored files
Standard RAM 2 Only one file register and one local device
Standard ROM 28 60 124 252 —— Standard ROM number of writings Max. 100000 times ——
Number of I/O device points 8192 points (X/Y0 to 1FFF) Number of devices usable on program
Number of occupied I/O points 4096 points (X/Y0 to FFF) Number of points accesible to actual I/O modules 1:124 is the maximum number of programs that can be executed on High Performance model QCPU. 2: The maximum number of sequence steps that can be executed for one program by the High Performance model QCPU with the parameters stored in another drive is calculated with the following expression. (Program size) - (File header size (default: 34 steps)) Refer to the High Performance model QCPU User's Manual (Function Explanation, Program Fundamentals) for details on the program size and file. 3: The memory capacity of the Q12HCPU or Q25HCPU whose first five digits of serial No. are "02091" or earlier is 64K bytes. (Refer to Section 2.3 for the way to confirm the serial No.) 4:The CPU shared memory is not latched. The CPU shared memory is cleared when the power is turned on to the PLC or when the CPU module is reset. 5:The memory capacity of the Q02HCPU or Q06HCPU whose first five digits of serial No. are "04011" or earlier is 64K bytes. (Refer to Section 2.3 for the way to confirm the serial No.)
![Page 36 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — [ZR]](/cdn/reader/23/23ace0389574f80b15b64d444ff08c69b0306e29c3549a9ddef814782e5e0cba/images/page-36.webp?w=400)
Performance Specifications (continued)
Internal relay [M] Default 8192 points (M0 to 8191)
Latch relay [L] Default 8192 points (L0 to 8191)
Link relay [B] Default 8192points (B0 to 1FFF)
Default 2048 points (T0 to 2047) (for low / high speed timer) Select between low / high speed timer by instructions. The measurement unit of the low / high speed timer is set with parameters. (Low speed timer : 1 to 1000ms, 1ms/unit, default 100ms) (High speed timer : 0.1 to 100ms, 0.1ms/unit, default 10ms)
Default 0 point(for low / high speed retentive timer) Switchover between the low / high speed retentive timer is set by instructions. The measurement unit of the low /high speed retentive timer is set with parameters. (Low speed retentive timer : 1 to 1000ms, 1ms/unit, default 100ms) (High speed retentive timer : 0.1 to 100ms, 0.1ms/unit, default 10ms)
Number of use points
is set with parameters.
Data register [D] Default 12288 points (D0 to 12287)
Link register [W] Default 8192 points (W0 to 1FFF)
Annunciator [F] Default 2048 points (F0 to 2047)
Edge relay [V] Default 2048 points (V0 to 2047)
Number of device points
can be used by block conversion in increments of 32768 points (R0 to 32767) Q12HCPU, Q25HCPU The number of points of up to 131072
When a Flash card is
used, read only is
possible.
The ATA card cannot
be used.
conversion necessary. Q12HCPU, Q25HCPU 131072 points (ZR0 to 131071), No block
4 - 2 4 - 2

Performance Specifications (continued)

Link special relay [SB] 2048 points (SB0 to 7FF)
Link special register [SW] 2048 points (SW0 to 7FF)
4096 points (P0 to 4095), set parameter values to select usable range
The specified intervals of the system interrupt pointers I28 to I31 can
Device having a direct access to the buffer memory of the intelligent
(Latch range can be set for B, F, V, T, ST, C, D, and W.)
RUN and PAUSE contacts can be set from among X0 to 1FFF,
Year, month, day, hour, minute, second, day of the week
Accuracy -3.18 to +5.25s (TYP. +2.12s) /d at 0°C
Allowable momentary power failure period Varies according to the type of power supply module. ——
4 - 3 4 - 3

4.2 Part Names and Settings
This section explains the part names and settings of the module.
With front cover open


When opening the front cover, put your finger here.


No. Name Application 1) Module fixing hook Hook used to fix the module to the base unit. (Single-motion installation)
Indicates the mode of the CPU module. ON (green) : Q mode ON (orange) : A mode Flicker (green) : Enforced ON/OFF for external I/O registered
Indicates the operating status of the CPU module. ON : During operation in "RUN" status. OFF : During a stop in "STOP" status or detection of error whose occurrence stops
changed from "STOP" to "RUN". To turn ON the RUN LED after writing the program, carry out the following steps. y Set the RUN/STOP switch from "RUN" → "STOP" → "RUN". y Reset with the RESET/L.CLR switch. y Restart the PLC power. To turn ON the RUN LED after writing the parameters, carry out the following steps. y Reset with the RESET/L.CLR switch. y Restart the PLC power. (If the RUN/STOP switch is set from "RUN" → "STOP" → "RUN" after changing the parameters, the parameters related to the intelligent function module, such as the network parameters, will not be reflected.)
error. (When operation continued at error detection is set in the parameter.) OFF : Normal Flicker : Detection of error whose occurrence stops operation.
When automatic write to standard ROM is completed normally. ("BOOT" LED also flickers.)
ON : Start of boot operation OFF : Non-execution of boot operation Flicker : When automatic write to standard ROM is completed normally. ("ERR." LED
also flickers.) 8) Module loading lever Used to load the module to the base unit.

No. Name Application 9) Memory card EJECT button Used to eject the memory card from the CPU module.
CPU module. (Shipped in OFF position) OFF : No protection ON : Protection SW2, SW3: Used to specify parameter-valid drive.
13)
(Both SW2 and SW3 are shipped in OFF position)
SW2 SW3 Parameter Drive
OFF OFF Program memory (Drive 0) ON OFF SRAM card (Drive 1) OFF ON Flash card/ATA card (Drive 2)
etc. If this switch is left in the RESET position, the whole system will be reset and the system will not operate properly. After performing reset, always return this switch to the neutral position. L.CLR : Used to turn "OFF" or "zero" all data in the parameter-set latch area.
Used to clear the sampling trace and status latch registration. 16) Module fixing screw hole Hole for the screw used to fix to the base unit. (M3 12 screw) 17) Module fixing latch Hook used to fix to the base unit.
Q6HLD-R2
RS-232 cable
4 - 6 4 - 6

4.3 Switch Operation After Writing in Program
When writing a program into the CPU module, do not turn off the system protect set switch SW1 in advance (When the switch is turned off, the system will not be protected).
When a program is written while the CPU module is stopped, operate the switch in the order shown below. 1) RUN / STOP switch : STOP "RUN" LED: Turns off CPU module in stop status Write a program.
When a program is written while the CPU module is running, the switch need not be operated.
POINTS (1) Even if the RUN/STOP switch is set to RUN immediately after a program is
written when the CPU module is in the stop status, CPU module will not come into RUN status. When the CPU module is reset with the RESET / L.CLR switch and the RUN/STOP switch is set to RUN after a program has been written, the CPU module can be brought into RUN status. (2) If the CPU module is desired to be brought into RUN status without resetting it,
operate the RUN/STOP switch from STOP to RUN, RUN to STOP, and STOP to RUN in that order. After the seconds STOP to RUN switch operation, the CPU module is brought into RUN status. (3) When a program is written while the CPU module is running in boot operation,
the program written during the running is written into the program memory. After a program has been written while the CPU module is running, write the program also into the boot original memory. Failure to write a program into the boot original memory will run an old program at the time of the next boot operation. (For details of the boot operation, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals) ).

4.4 Latch Clear Operation
To perform latch clear, operate the RESET/L.CLR switch in the following procedure.
POINTS (1) The ineffective range for latch clear can be set for each device by the device
setting parameter. (2) In addition to the way of using the RESET/L.CLR switch for latch clear, remote
latch clear may be performed from GX Developer. For details of the remote latch clear operation using GX Developer, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals). 4.5 Executing Automatic Write to Standard ROM.
Automatic write to the standard ROM is carried out with the following procedures. (a) Operation with GX Developer (setting automatic write to standard ROM)

Check "Auto Download all
Data from Memory card to
Standard ROM ".
Set the "Transfer from" to "Standard ROM".

(c) The parameters and programs will be booted from the standard ROM to the
program memory when the PLC is switched on to enable actual operations.

5 POWER SUPPLY MODULE
5.1 Specification
This section gives the specifications of the power supply modules.
Performance Specifications Item Q61P-A1 Q61P-A2 Q62P Q63P Base loading position Power supply module loading slot Applicable base unit Q3B, Q6B
100 to 120VAC +10% -15% 200 to 240VAC +10% -15% 100 to 240VAC +10% -15% 24VDC +30% -35% Input power supply
(85 to 132VAC) (170 to 264VAC) (85 to 264VAC) (15.6 to 31.2VDC) Input frequency 50/60Hz ±5% —— Input voltage distortion factor Within 5% (refer to section 5.1.3) —— Max. input apparent power 105VA —— Max. input power —— 45W Inrush current 20A within 8ms 100A within 1ms 5VDC 6A 3A 6A Rated output current 24VDC —— 0.6A —— External output voltage —— 24VDC ±10% —— 5VDC 6.6A or more 3.3A or more 6.6A or more Overcurrent protection 1 24VDC —— 0.66A or more —— 5VDC 5.5 to 6.5V Overvoltage protection 2 24VDC —— Efficiency 70% or more 65% or more 70% or more Allowable momentary power failure period 3 Within 20ms Within 10ms (at 24VDC input)
Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.)) 500VAC across primary and 5VDC
Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester
10M or more by insulation resistance
By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency Operation indication LED indication (lit at 5VDC output) Fuse Built-in (Unchangeable by user)
Application ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU module), for CPU module operating status output Rated switching voltage, current 24VDC, 0.5A
Minimum switching load 5VDC, 1mA Response time OFF to ON: 10ms max. ON to OFF: 12ms max.
Life Mechanical : More than 2 million times Electrical : More than 100 thousand times at rated switching voltage, current Surge suppressor No
Fuse No Terminal screw size M3.5 × 7 Applicable wire size 0.75 to 2mm2 Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5 Applicable tightening torque 66 to 89N•cm H 98mm (3.86inch) W 55.2mm (2.33inch) External dimensions D 90mm (3.55inch) Weight 0.31kg 0.39kg 0.33kg

Base loading position Power supply module loading slot
Applicable base unit Q3B, Q6B
100 to 120VAC/200 to 240VAC +10% -15% Input power supply
(85V to 132VAC/170 to 264VAC)
Input frequency 50/60Hz ±5%
Input voltage distortion factor Within 5% (refer to section 5.1.3)
Max. input apparent power 160VA
Inrush current 20A within 8ms
5VDC 8.5A Rated output current 24VDC ——
5VDC 9.9A or more Overcurrent protection*1 24VDC ——
5VDC 5.5 to 6.5V Overvoltage protection*2 24VDC ——
Efficiency 70% or more
Allowable momentary power failure period*3 Within 20ms
Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.))
Insulation resistance Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester
Operation indication LED indication (lit at 5VDC output)
Fuse Built-in (Unchangeable by user)
Application ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU
module), for CPU module operating status output
Rated switching voltage, current 24VDC, 0.5A
Minimum switching load 5VDC, 1mA
Response time OFF to ON: 10ms max. ON to OFF: 12ms max.
Life Mechanical : More than 2 million times Electrical : More than 100 thousand times at rated switching voltage, current
Terminal screw size M3.5 × 7
Applicable wire size 0.75 to 2mm2
Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5
Applicable tightening torque 66 to 89N•cm
H 98mm (3.86inch)
W 55.2mm (2.33inch) External dimensions
D 115mm (4.53inch)
Weight 0.40kg

Base loading position Slim type power supply module loading slot
Applicable base unit Q3SB
100 to 240VAC +10% -15% Input power supply
Input frequency 50/60Hz ±5%
Input voltage distortion factor Within 5% (refer to section 4.3.1)
Max. input apparent power 40VA
Inrush current 20A within 8ms
5VDC 2A Rated output current 24VDC ——
5VDC 2.2A or more Overcurrent protection*1 24VDC ——
5VDC 5.5 to 6.5V Overvoltage protection*2 24VDC ——
Efficiency 70% or more
Allowable momentary power failure period*3 Within 20ms
Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.))
Insulation resistance Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester
Operation indication LED indication (lit at 5VDC output)
Fuse Built-in (Unchangeable by user)
Application ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU
module), for CPU module operating status output
Rated switching voltage, current 24VDC, 0.5A
Minimum switching load 5VDC, 1mA
Response time OFF to ON: 10ms max. ON to OFF: 12ms max.
Life Mechanical : More than 20 million times Electrical : More than 100 thousand times at rated switching voltage, current
Terminal screw size M3.5 × 7
Applicable wire size 0.75 to 2mm2
Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5
Applicable tightening torque 66 to 89N•cm
H 98mm (3.86inch)
W 27.4mm (1.08inch) External dimensions
D 104mm (4.09inch)
Weight 0.18kg

Base loading position Power supply module loading slot
Applicable base unit QA1S65B, QA1S68B
100 to 240VAC +10% -15% 24VDC +30% -35% Input power supply
(85 to 264VAC) (15.6 to 31.2VDC)
Input frequency 50/60Hz ±5% ——
Input voltage distortion factor Within 5%
Max. input apparent power 105VA ——
Max. input power —— 41W
Inrush current 20A within 8ms 81A within 1ms
5VDC 5A 3A 5A Rated output current 24VDC —— 0.6A ——
5VDC 5.5A or more 3.3A or more 5.5A or more Overcurrent protection 1 24VDC —— 0.66A or more ——
5VDC 5.5 to 6.5V Overvoltage protection 2 24VDC ——
Efficiency 65% or more
Allowable momentary power failure period 3 Within 20ms Within 10ms (at 24VDC input)
Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.)) 500VAC across primary and 5VDC
Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester
5M or more by insulation resistance tester
By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency
Operation indication LED indication (lit at 5VDC output)
Fuse Built-in (Unchangeable by user)
Contact output section No
Terminal screw size M3.5 × 7
Applicable wire size 0.75 to 2mm2
Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5
Applicable tightening torque 66 to 89N•cm
H 130mm (5.12inch)
W 55mm (2.17inch) External dimensions
D 93.6mm (3.69inch)
Weight 0.60kg 0.50kg
Performance Specifications Item · Insulation resistance · Noise durability

POINTS 1 : Overcurrent protection The overcurrent protection device shuts off the 5 V, 24 VDC circuit and stops
the system if the current flowing in the circuit exceeds the specified value. The LED of the power supply module is unlit or lit dimly upon a voltage drop. If this device is activated, switch the input power supply off and eliminate the cause such as insufficient current capacity or short. Then, a few minutes later, switch it on to restart the system. The initial start for the system takes place when the current value becomes normal. 2 : Overvoltage protection The overvoltage protection device shuts off the 5 VDC circuit and stops the system if a voltage of 5.5 VDC is applied to the circuit. When this device is activated, the power supply module LED is switched OFF. If this happens, switch the input power OFF, then a few minutes later ON. This causes the initial start for the system to take place. The power supply module must be changed if the system is not booted and the LED remains OFF. 3 : Allowable momentary power failure period (1) For AC input power supply
down to be detected, but operation will continue. y An instantaneous power failure lasting more than 20ms may cause the
operation to continue or initial start to take place depending on the power supply load. Furthermore, by using the same AC power supply for the AC input module and the power supply module, it is possible to prevent the sensor, to which the AC input module is connected, from turning OFF when it is ON when the power is turned OFF. However, if only the AC input module is connected to the AC line, which is connected to the power suppludetection of the AC down for the power supply module may be delayed by the capacitor in the AC input module. Thus, connect a load of approx. 30mA per QX10 unit to the AC line. (2) For DC input power supply
24VDC down to be detected, but operation will continue. y An instantaneous power failure lasting more than 10ms (*4) may cause
the operation to continue or initial start to take place depending on the power supply load. ( 4: This is for a 24VDC input. This is 10ms or less for 24VDC or less.)

5.1.2 Selecting the power supply module
The power supply module is selected according to the total of current consumption of the base units, I/O modules, intelligent function module, special function module, and peripheral devices supplied by its power supply module. For the internal current consumption of 5 VDC of the base unit, refer to Chapter 6. For the internal current consumption of 5 VDC of the I/O modules, intelligent function module, special function module, and peripheral devices, refer to the Manuals of their respective modules. For the devices obtained by a user, see the manual for the respective device.
(1) When the base unit is of Q3B or Q6B:

Peripheral devices, converter, cables, etc. (for connection between CPU module and PC)
(a) Selection of power supply module for use of Q52B or Q55B extension base
unit Using the Q52B or Q55B supplies 5VDC power from the power supply module of the main base unit through the extension cable. Therefore, note the following when using the Q52B or Q55B.
5VDC Rated output current Type
8.5A Q64P

The following methods are effective to reduce voltage drops at the extension cables.

Peripheral devices, converter, cables, etc. (for connection between CPU module and PC)
(a) To use the slim type main base unit and slim type power supply module, pay
5VDC Rated output current Type
5 - 7 5 - 7

(3) When the base unit is of QA1S6 B:
Power supply module A1S61PN, A1S62PN, A1S63P
Base unit QA1S65B and QA1S68B
I/O module A1SX10, A1SY10, etc.
Special function module A1SD61, A1SD75P1-S3, etc.
peripheral devices AD75TU 2
Be sure of the following terms when connecting the High Performance model QCPU system to the uninterruptive power supply (abbreviated as UPS hereafter): Use a UPS which employs the constant inverter power supply method with 5 % or less voltage fluctuation. Do not use a UPS with the constant commercial power supply method.

5.2 Names of Parts and Settings
The names of the parts of each power supply module are described below.


Q61P-A2


Q63P


Q64P
5 - 9 5 - 9

1) POWER LED 5VDC power indicator LED
any of the CPU modules.
Normally off when loaded in an extension base unit.
7) Terminal cover Protective cover of the terminal block

POINTS (1) The Q61P-A1 is dedicated for inputting a voltage of 100 VAC.
Do not input a voltage of 200 VAC into it or trouble may occur on the Q61P-A1.
Power supply module does not cause trouble. CPU module cannot be operated.
Therefore, it is not compatible with the intermediate voltage (133 to 169VAC). The CPU module may not work normally if the above intermediate voltage is applied. (3) Ensure that the earth terminals LG and FG are grounded.

(2) A1S61PN, A1S62PN and A1S63P
MELSECA 1S62PN
MELSECA 1S63P
POWER
POWER
POWER
MITSUBISHI
MITSUBISHI
MITSUBISHI
INPUT 100-240VAC 105VA 50 / 60Hz
INPUT 100-240VAC 105VA 50 / 60Hz
INPUT DC15.6 31.2V
OUTPUT DC 5V 5A
NC
+24V
NC
NC
24G
NC
FG
(FG)
(FG)
NC
NC
(LG)
(LG)
LG
INPUT
INPUT
INPUT +24V
100-240VAC
100-240VAC
24G
A1S61PN
A1S62PN
A1S62PN
A1S63P
No. Name Application 1) POWER LED 5VDC power indicator LED 2) +24V, 24G terminals Used to supply 24VDC power to inside the output module (using external wiring). 3) FG terminals Ground terminal connected to the shield pattern of the printed circuit board.
POINTS (1) Do not wire to those terminals for which NC is stamped on the terminal block. (2) Ensure that the earth terminals LG and FG are grounded.

6 BASE UNIT AND EXTENSION CABLE
This section describes the specifications of the extension cables for the base units (main, slim type and extension base unit) used in the PLC system and the specification standards of the extension base unit. 6.1 Base Unit Specification Table

Possibility of extension Extendable Applicable module Q series modules 5 VDC internal current consumption 0.105A 0.110A 0.114A 0.121A
W 189mm (7.44inch) 245mm (9.65inch) 328mm (12.92inch) 439mm (17.30inch) External dimensions
Weight 0.21kg 0.25 kg 0.35 kg 0.45 kg Attachment Mounting screw M4 14 4 pieces (DIN rail mounting adapter to be sold separately) DIN rail mounting Adapter type Q6DIN3 Q6DIN2 Q6DIN1

Possibility of extension Cannot connect extension modules. Applicable module Q series modules 5 VDC internal current consumption 0.086A 0.086A 0.091A
W 114mm (4.49inch) 142mm (5.59inch) 198mm (7.80inch) External dimensions
Weight 0.12kg 0.15 kg 0.21 kg Attachment Mounting screw M4 12 4 pieces (DIN rail mounting adapter to be sold separately) DIN rail mounting Adapter type Q6DIN3

(3) Extension base unit specifications (Type not requiring power supply
module)
Number of I/O modules installed 2 5
Possibility of extension Extendable
Applicable module Q series modules
5 VDC internal current consumption 0.080A 0.100A
Mounting hole size M4 screw hole or 4.5 hole (for M4 screw)
H 98mm (3.86inch)
W 106mm (4.17inch) 189mm (7.44inch) External dimensions
D 44.1mm (1.74inch)
Weight 0.14kg 0.23kg
Attachment Mounting screw M4 14 4 pieces (DIN rail mounting adapter to be sold separately)
(4) Extension base unit specifications (Power supply loaded type)
Type
Item Q63B Q65B Q68B Q612B QA1S65B QA1S68B
Number of I/O modules installed 3 5 8 12 5 8
Possibility of extension Extendable
Applicable module Q series modules AnS series modules 5 VDC internal current consumption 0.105A 0.110A 0.114A 0.121A 0.117A 0.118A
M5 screw hole or 5.5 hole (for M5 screw)
H 98mm (3.86inch) 130mm (5.12inch)
420mm (16.55inch) External dimensions
W 189mm (7.44inch)
245mm (9.65inch)
328mm (12.92inch)
439mm (17.30inch)
315mm (12.41inch)
Weight 0.23kg 0.25 kg 0.35 kg 0.45 kg 0.75 kg 1.00 kg
Attachment Mounting screw M4 14 , 4 pieces (DIN rail mounting adapter sold separately)
Mounting screw M5 25 4 pieces DIN rail mounting Adapter type Q6DIN3 Q6DIN2 Q6DIN1 ——— ———

6.2 Extension Cable Specification Table
The list below shows the specifications of the extension cables which can be used for the High Performance model QCPU system.

Cable length 0.45m (1.48ft.) 0.6m (1.97ft.) 1.2m (3.93ft.) 3.0m (9.84ft.) 5.0m (16.39ft.) 10.0m (32.79ft.)
Application Connection across the main base unit and extension base unit or across the extension base units.
Weight 0.15 kg 0.16 kg 0.22 kg 0.40 kg 0.60 kg 1.11 kg
POINT When the extension cables are used in combination, limit the overall distance of the combined cable to 13.2 m(43.28 ft.).
The names of the parts of the base unit are described below.
I/11 I/10 I/09 I/08 I/07 I/06 I/05 I/04 I/03 I/02 I/01 I/00 CPU POWER
1) Extension cable
Connector for sending and receiving signals from the extension base unit, to which the
extension cables are connected.
2) Base cover
the area of the base cover surrounded by the groove under the word "OUT" on the base
cover must be removed with a tool such as nippers.
intelligent function module.
To the connectors located in the spare space where these modules are not installed, attach
the supplied connector cover or the blank cover module (QG60) to prevent entry of dirt.
mounting hole Hole for mounting DIN rail adapter
6 - 3 6 - 3
1) · 2)

(2) Slim type main base unit(Q32SB, Q33SB, Q35SB)

To the connectors located in the spare space where these modules are not installed, attach
the supplied connector cover or the blank cover module (QG60) to prevent entry of dirt.

(3) Extension base unit (Q5 B, Q6 B, QA1S6 B)
I/O2 I/O1 I/O0 I/O3 I/O4
I/11 I/10 I/09 I/08 I/07 I/06 I/05 I/04 I/03 I/02 I/01 I/00 POWER
SG
FG
I/O0 I/O7 I/O6 I/O5 I/O4 I/O3 I/O2 I/O1
POWER
QA1S68B
No. Name Application
Connectors for sending and receiving signals from the main base unit or the other extension base units, to which the extension cables are connected. Do not remove the supplied connector cover. 2) Base cover Protective cover of extension cable connector.
3) Stage No. setting connector
Connector for setting the number of stages of the extension base unit. For setting method, refer to Section 6.4.
Connectors for installing the power supply module, I/O modules, and intelligent function module/ special function module. To those connectors located in the spare space where these modules are not installed, apply the supplied connector cover or the blank cover module to prevent entry of dirt. Blank cover module applicable to Q52B, Q55B, Q63B,Q65B, Q68B and Q612B :QG60 Blank cover module applicable to QA1S65B and QA1S68B :A1SG60

6.4 Setting the Extension Base Unit
The number of stages setting method of each extension base unit to be used when extension base units are installed is described below.


1st stage 2nd stage 3rd stage 4th stage 5th stage 6th stage 7th stage

POINTS To set the stages No. setting connector, set a number from 1 to 7 according to the number of extension stages. Do not set the same stage number at two or more positions or do not fail to set a number. A miss-input or miss-output may occur.

6.5 I/O Number Allocation
The I/O numbers are automatically allocated in the system loading status.
0 1 2 3 4

6 7 8 9 10 11 12 5 X/Y
X/Y 100 X/Y 120 X/Y 140 X/Y 160 X/Y 180
14 15 16 17 18 19 20 13 X/Y 1A0
X/Y 1C0 X/Y 1E0 X/Y 200 X/Y 220 X/Y 240 X/Y 260 X/Y 280
3rd extension stage In this system, 32-point modules are loaded on slots 0 to 25.
For the I/O number setting method using GX Developer, refer to the Operating Manual of GX Developer. For details of I/O number allocation, refer to the following manual. • High Performance Model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals)

POINT For the extension using the Q5 B, Q6B B and QA1S6 B, allocate the I/O numbers on the modules starting from the Q series module installed on the Q5 B, Q6 B base unit. Where 32 modules are installed in all slots with the configuration
1st extension stage · 2nd extension stage

6.6 Guideline for Use of Extension Base Units (Q5 B)
Since the Q5B is supplied with 5VDC from the power supply module on the main base unit, a voltage drop occurs at extension cables. Improper I/O may be provided if the specified voltage (4.75VDC or higher) is not supplied to the "IN" connector of the Q5B. When using the Q5B, make sure that the "IN" connector of the Q5B is supplied with 4.75VDC or higher. And it is recommend to connect it with the shortest possible extension cable right after connecting the main base unit, so as to minimize the effects of voltage drop. (1) When only the Q5B is connected to the extension base unit
4.75VDC or higher should be supplied to the "IN" connector of the Q5B in the final extension stage. (b) How to calculate voltage to "IN" connector
The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC. Therefore, the Q5B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).
Main base unit (Q3 B)
Extension Cable
Conductor
Type
Resistance ( )
QC05B 0.044
Extension base unit (Q5 B)
QC12B 0.082
QC30B 0.172
Extension base unit (Q5 B)
QC100B 0.530
R7
Extension base unit (Q5 B)
V1 Voltage drop at the extension cable between the main base unit and extension base unit
Vn Voltage drop at the extension cable between the extension base unit (extension stage n-1) and extension base
R1 Cable resistance between the main base unit and extension base unit
Rn Cable resistance between the extension base unit (extension stage n-1) and extension base unit (extension
l1 to l7 5VDC current consumption among extension stage 1 to 7 1
Q5B.
The symbols including "I" (I1 to I7) vary with the modules loaded on the extension base unit. For details of the symbol,
refer to the user's manuals of the module used.

List for Calculating Voltage Drops Occurring at Extension Cables in System Consisting of Extensions 1 to 7

Voltage Drop at Extension Cable on Corresponding Extension Unit Q5B Loading Position V1 V2 V3 V4 V5 V6 V7
of Q5B (V) Extension stage 1 R1 • I1 V=V1
Extension stage 2 R1(I1+I2) R2 • I2 V=V1+V2
Extension stage 3 R1(I1+I2+I3) R2(I2+I3) R3 • I3 V=V1+V2+V3
Extension stage 4 R1(I1+I2+I3+I4) R2(I2+I3+I4) R3(I3+I4) R4 • I4 V=V1+V2+V3+V4
+I5) R2(I2+I3+I4+I5) R3(I3+I4+I5) R4(I4+I5) R5 • I5 V=V1+V2+V3+V4+V5
+I6) R3(I3+I4+I5+I6) R4(I4+I5+I6) R5(I5+I6) R6 • I6 V=V1+V2+V3+V4+V5+
The voltage supplied to "IN" connector of the Q5B in the final extension reaches 4.75 VDC or higher on the condition that the sum total of voltage drop to "IN" connector of Q5B (V) is 0.15V or lower.
(2) When the Q6 B is connected between the Q3 B and the Q5 B (a) Selection condition
4.75VDC or higher should be supplied to the "IN" connector of the Q5B in the final extension. (b) How to calculate voltage to "IN" connector
The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC. Therefore, the Q5B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).

[When the Q5 B is connected to Extension stage 2.]
V Voltage drop at the extension cable between the main base unit and extension base unit (Q5B)
5VDC current consumption when the Q5B is used as Extension n+1, n = 1 to 6, n: Extension No. of Q6B
(Sum total of current consumed by Q5B and currents consumed by the I/O, intelligent function modules
Extension cable resistance between the main base unit or the extension base unit (Q6B) and the extension
Rn+1 Extension cable resistance between the extension base unit (Q6B) and extension base unit (Q5B)

List for Calculating Voltage Drops Occurring at Extension Cables when connecting Q6B between Q3B and Q5B

Voltage drop caused by extension cable from the main base unit to the
Extension stage 1 to 4 Extension stage 5 V=(R1+R2+R3+R4+R5)I1
Extension stage 1 to 5 Extension stage 6 V=(R1+R2+R3+R4+R5+R6)I1
Extension stage 1 to 6 Extension stage 7 V=(R1+R2+R3+R4+R5+R6+R7)I1 The voltage supplied to the "IN" connector of the Q5B reaches 4.75 VDC or higher on the condition that the voltage drop (V) at the extension cable between the main base unit and Q5B is 0.15 VDC or lower.
(a) Selection condition
4.75VDC or higher should be supplied to the "IN" connector of the Q5B. (b) How to calculate voltage to "IN" connector
The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC. Therefore, the Q5B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).
Main base unit (Q3 B)
Extension Cable
Conductor
Type
Resistance ( )
Extension base unit (Q5 B)
QC06B 0.051
QC12B 0.082
QC30B 0.172
GOT
QC50B 0.273
QC100B 0.530
Symbol Description
V Voltage drop at the extension cable between the main base unit and extension base unit (Q5B)
5VDC current consumption when the Q5B is used as Extension n+1, n = 1 to 5, n: Extension No. of the Q6B connected (Sum total of current consumed by Q5B and currents consumed by I/O, intelligent function modules loaded on the Q5B)
Im 5VDC current consumption of the GOT (current consumption per GOT is 254mA) • Im = 254 c (c: Number of GOTs connected (c: 1 to 5))
Rn Extension cable resistance between the main base unit or the extension base unit (Q6B) and extension base unit (Q6B)
Rn+1 Extension cable resistance between the extension base unit (Q6B) and extension base unit (Q5B)
Power supply module

POINT When connecting GOT by extension cable that is 13.2 m (43.31ft) or longer, the bus extension connector box A9GT-QCNB is required. Since the A9GT-QCNB is supplied with 5VDC from the power supply module loaded on the main base unit, 29mA must be added to "Im" as the current consumption of the A9GT-QCNB. For details of the GOT-bus connection, refer to the GOT-A900 Series User's Manual (Connection).

7 MEMORY CARD AND BATTERY
This section describes the specifications and handling of the memory card and battery which can be used on the High Performance model QCPU. The memory card is necessary for sampling tracing. The memory card is also used to handle file registers of more than the number of points that can be stored in the standard RAM. (Refer to Section 4.1) 7.1 Memory Card Specifications
The specifications of the memory card which can be used on the High Performance model QCPU adheres to the PCMCIA small PC card. On the High Performance model QCPU, only one memory card can be installed.

Memory capacity after format 7940 kbyte 15932 kbyte 31854 kbyte

7.2 Battery Specifications (For CPU Module and SRAM Card)
(1) For CPU module
Item Q6BAT
Classification Manganese dioxide lithium primary
battery
Initial voltage 3.0V
Nominal current 1800mAh
Storage life 10 years (room temperature)
Total power failure time Refer to Section 10.3.1.
Application
memory, standard RAM and latch
devices
(2) For SRAM card
Type
Item Q2MEM-BAT
Classification Graphite fluoride primary battery
Initial voltage 3.0V
Nominal current 48mAh
Storage life 5 years (room temperature)
Total power failure time Refer to Section 10.3.1.
REMARK
Refer to Section 10.3.1 for the battery life.

7.3 Handling the Memory Card
(1) Formatting of memory card
Any SRAM or ATA card must have been formatted to use on the High Performance model QCPU. Since the SRAM or ATA card purchased is not yet formatted, format it using GX Developer before use. (The Flash card need not be formatted.) For the formatting procedure, refer to the Operating Manual of the GX Developer. (2) Installation of SRAM card battery
A power interrupt hold-on battery is furnished with the SRAM card you purchased. Before using the SRAM card, install the battery.
POINTS Even if the battery is installed on the CPU module, if a battery is not installed on the SRAM card, the memory of the SRAM card will not be backed up. Ensure to install the battery on the SRAM card. Also, if the battery is installed on the SRAM card but the CPU module has no battery, the program memory, standard RAM and latch devices of the CPU module are not backed up. Similarly ensure to install the battery on the CPU module.
Please refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals) of section 6.1 for the kind of the file which can be stored on each memory card.

7.4 The Names of The Parts of The Memory Card
The names of the parts of the memory card are described below.

Used to set write inhibit in the memory. At the time of shipping, it is
: The battery holder fixing switch is returned automatically from RELEASE to LOCK
when the battery holder is disconnected.

7.5 Memory Card Loading/Unloading Procedures
(1) To install the memory card
Install the memory card into the CPU module, while paying attention to the orientation of the memory card. Insert the memory card securely into the connector until the height of the memory card reaches that of the memory card EJECT button.
Memory card EJECT button
"Precautions" on this side Insert it in this direction.
To remove the memory card from the CPU module, press the memory card EJECT button to push out the card.
Memory card EJECT button
Remove the card in this direction.
card is ready for use by user. SM604 (memory card use flag) : The system is turned on when the CPU
module uses a memory card. SM605 (memory card detach inhibit flag) : This is turned on by the user to disable
the memory card from being detached.
POINTS Install and remove the memory card while the power is turned on, paying attention to the following. (1) If the procedures specified above are not followed, the data stored in the
memory card may be destroyed. When the CPU module operation at the time of occurrence of a parameter error is set to STOP, the CPU module operation is stopped by the occurrence of "ICM.OPE.ERROR." (2) When the memory card is installed, its mount processing is performed again.
As a result, the scanning time is increased by several 10 ms max.

7.6 Installation of Battery (for CPU Module and Memory Card)
(1) The battery for the CPU module is shipped with its connector disconnected.
Connect the connector as follows. Refer to Section 10.3 for the service life of the battery and how to replace the battery.

Side of the CPU module Open the cover at the CPU module's bottom.

Insert the battery connector into the connector pin on the case. Be sure that the insertion direction is correct.
(2) The battery for the SRAM card is shipped separately from the battery holder.
Before installing the SRAM card into the CPU module, set the battery holder in the following procedure.
Battery holder's locking switch "Model name" on this side

Set the battery holder's locking switch to the "RELEASE" position.
Set the battery onto the battery holder with the "plus" face up.
Insert the battery holder with which the battery is installed firmly, into the SRAM card.
Confirm that the battery holder's locking switch is set to the "LOCK" position.
"LOCK" position The battery holder's locking switch is set automatically to the "LOCK" position when the battery holder is removed. In its position, insert the battery holder firmly.
'+' sign · Battery holder

8 EMC AND LOW VOLTAGE DIRECTIVE
For the products sold in European countries, the conformance to the EMC Directive, which is one of the European Directive, has been a legal obligation since 1996. Also, conformance to the Low Voltage Directive, another European Directive, has been a legal obligation since 1997. Manufacturers who recognize their products must conform to the EMC and Low Voltage Directive required to declare that their products conform to these Directives and put a "CE mark" on their products. 8.1 Requirements for Conformance to EMC Directive
The EMC Directive specifies that products placed on the market must "be so constructed that they do not cause excessive electromagnetic interference (emissions) and are not unduly affected by electromagnetic interference (immunity)". The applicable products are requested to meet these requirements. The sections 8.1.1 through 8.1.6 summarize the precautions on conformance to the EMC Directive of the machinery constructed using the MELSEC-Q series PLCs. The details of these precautions has been prepared based on the control requirements and the applicable standards control. However, we will not assure that the overall machinery manufactured according to these details conforms to the above-mentioned directives. The method of conformance to the EMC Directive and the judgment on whether or not the machinery conforms to the EMC Directive must be determined finally by the manufacturer of the machinery. 8.1.1 Standards applicable to the EMC Directive
The standards applicable to the EMC Directive are listed below.
Specification Test item Test details Standard value
30 M-230 MHz QP : 30 dB V/m (30 m in measurement range) 1 230 M-1000 MHz QP : 37 dB V/m (30 m in measurement range) EN50081-2 : 1995 EN55011 Conducted noise
EN55011 Radiated noise 2 Electromagnetic emissions from the product are measured.
Electromagnetic emissions from the product to the power line is measured.
150 k-500 kHz QP : 79 dB, Mean : 66 dB 1 500 k-30 MHz QP : 73 dB, Mean : 60 dB
Immunity test in which static electricity is applied to the cabinet of the equipment.
EN61000-4-2 Electrostatic immunity 2
15 k V Aerial discharge
Power line : 2 kV Digital I/O (24 V or higher) : 1 kV (Digital I/O (24 V or less)) > 250 V (Analog I/O, signal lines) > 250 V EN61000-4-3 Radiated field AM modulation 2
Immunity test in which burst noise is applied to the power line and signal lines.
EN61000-4-4 Fast transient burst noise 2
Immunity test in which field is irradiated to the product.
10 V/m, 26-1000 MHz, 80%AM modulation@1 kHz
EN61000-4-12 Damped oscillatory wave immunity
Immunity test in which a damped oscillatory wave is superimposed on the power line.
Power line : 1 kV Digital I/O (24 V or higher) : 1 kV ( 1) QP : Quasi-peak value, Mean : Average value ( 2) The PLC is an open type device (device installed to another device) and must be installed in a conductive control panel. The tests for the corresponding items were performed while the PLC was installed inside a control panel.

8.1.2 Installation instructions for EMC Directive
The PLC is open equipment and must be installed within a control cabinet for use. This not only ensures safety but also ensures effective shielding of PLC-generated electromagnetic noise. (1) Control cabinet
(a) Use a conductive control cabinet.
(b) When attaching the control cabinet's top plate or base plate, mask painting
and weld so that good surface contact can be made between the cabinet and plate.
(c) To ensure good electrical contact with the control cabinet, mask the paint on
the installation bolts of the inner plate in the control cabinet so that contact between surfaces can be ensured over the widest possible area.
(d) Earth the control cabinet with a thick wire so that a low impedance
connection to ground can be ensured even at high frequencies.
(e) Holes made in the control cabinet must be 10 cm (3.94 inch) diameter or
less. If the holes are 10 cm (3.94 inch) or larger, radio frequency noise may be emitted. In addition, because radio waves leak through a clearance between the control panel door and the main unit, reduce the clearance as much as practicable. The leakage of radio waves can be suppressed by the direct application of an EMI gasket on the paint surface. Our tests have been carried out on a panel having the damping characteristics of 37 dB max. and 30 dB mean (measured by 3 m method with 30 to 300 MHz). (2) Connection of power and earth wires
Earthing and power supply wires for the PLC system must be connected as described below. (a) Provide an earthing point near the power supply module. Earth the power
supply's LG and FG terminals (LG : Line Ground, FG : Frame Ground) with the thickest and shortest wire possible. (The wire length must be 30 cm (11.81 inch) or shorter.) The LG and FG terminals function is to pass the noise generated in the PLC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.
(b) The earth wire led from the earthing point must be twisted with the power
supply wires. By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.

8.1.3 Cables
The cables extracted from the control panel contain a high frequency noise component. On the outside of the control panel, therefore, they serve as antennas to emit noise. To prevent noise emission, use shielded cable for the cables which are connected to the I/O modules and intelligent function modules and may be extracted to the outside of the control panel. The use of a shielded cable also increases noise resistance. The signal lines connected to the PLC I/O modules and intelligent function modules use shielded cables to assure noise resistance under the conditions where the shield is earthed. If a shielded cable is not used or not earthed correctly, the noise resistance will not meet the specified requirements.
When the shield of a shielded cable is earthed to the cabinet body, please ensure that the shield contact with the body is over a large surface area. If the cabinet body is painted it will be necessary to remove paint from the contact area. All fastenings must be metallic and the shield and earthing contact must be made over the largest available surface area. If the contact surfaces are too uneven for optimal contact to be made either use washers to correct for surface inconsistencies or use an abrasive to level the surfaces. The following diagrams show examples of how to provide good surface contact of shield earthing by use of a cable clamp.
(a) Earth the shield of the shielded cable as near the module as possible taking
care so that the earthed cables are not induced electromagnetically by the cable to be earthed. (b) Take an appropriate measures so that the shield section of the shielded
cable from which the outer cover was partly removed for exposure is earthed to the control panel on an increased contact surface. A clamp may also be used as shown in the figure below. In this case, however, apply a cover to the painted inner wall surface of the control panel which comes in contact with the clamp.
shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.
8 - 3 8 - 3

(2) MELSECNET/H module
Always use a double-shielded coaxial cable (MITSUBISHI CABLE INDUSTRIES, LTD.: 5C-2V-CCY) for the coaxial cables MELSECNET/H module. Radiated noise in the range of 30MHz or higher can be suppressed by use of the double- shielded coaxial cables. Earth the double-shielded coaxial cable by connecting its outer shield to the ground.
Refer to (1) for the earthing of the shield.
Precautions for using AUI cables, twisted pair cables and coaxial cables are described below. (a) Always earth the AUI cables connected to the 10BASE5 connectors.
Because the AUI cable is of the shielded type, strip part of the outer cover and earth the exposed shield section to the ground on the widest contact surface as shown below.
Refer to (1) for the earthing of the shield.
(b) Use shielded twisted pair cables as the twisted pair cables connected to the
10BASE-T/100BASE-TX connectors. For the shielded twisted pair cables, strip part of the outer cover and earth the exposed shield section to the ground on the widest contact surface as shown below.
Shielded twisted pair cables
Refer to (1) for the earthing of the shield.
to the 10BASE2 connectors. Earth the double-shielded coaxial cable by connecting its outer shield to the ground.
Refer to (1) for the earthing of the shield.
Ethernet is the registered trademark of XEROX, Co., LTD.
For the I/O signal lines and other communication cables lines (RS-232, RS-422, CC- Link, etc.), if extracted to the outside of the control panel, also ensure to earth the shield section of these lines and cables in the same manner as in item (1) above.

8.1.4 Power supply module
Always ground the LG and FG terminals after short-circuiting them. 8.1.5 When using QA1S6 B type base unit
(a) Earthing of shielded cable
shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.
8 - 5 8 - 5

(b) Positioning modules
External wiring cable (within 2 m (6.56 ft.))
External wiring cable (2 m to 10 m (6.56 ft. to 32.79 ft.))
Required Qty Cable length Prepared part 1 axis 2 axes 3 axes Within 2 m (6.56 ft.) AD75CK 1 1 1 AD75CK 1 1 1 2 m (6.56 ft.) to 10m (32.79ft.) ZCAT3035-1330 1 2 3

(c) CC-Link module
CC-Link dedicated cable Shield
Master station Remote I/O station Local station
DA DB DG SLD
DA DB DG SLD
FG
FG
FG
(d) I/O signal lines
For the I/O signal lines, if extracted to the outside of the control panel, also ensure to earth the shield section of these lines and cables in the same manner as in item (1) above.
The precautions required for each power supply module are described below. Always observe the items noted as precautions.
A1S63P ( 1) Use the CE marked 24VDC panel power equipment. A1S61PEU A1S62PEU A1S61PN A1S62PN
Always ground the LG and FG terminals after short-circuiting them.
( 1) If sufficient filter circuitry is built into the 24VDC external power supply module, the noise generated by A1S63P will be absorbed by that filter circuit, so a line filter may not be required. Filtering circuitry of version F or later of A1S63P is improved so that a external line filter is not required.

8.1.6 Others
(1) Ferrite core
A ferrite core has the effect of reducing radiated noise in the 30MHz to 100MHz band. It is not required to fit ferrite cores to cables, but it is recommended to fit ferrite cores if shield cables pulled out of the enclosure do not provide sufficient shielding effects. It should be noted that the ferrite cores should be fitted to the cables in the position immediately before they are pulled out of the enclosure. If the fitting position is improper, the ferrite will not produce any effect. In the CC-Link system, however, ferrite cores cannot be fitted to cables. (2) Noise filter (power supply line filter)
A noise filter is a component which has an effect on conducted noise. It is not required to fit the noise filter to the power supply line, but fitting it can further suppress noise. (The noise filter has the effect of reducing conducted noise of 10 MHz or less.) The precautions required when installing a noise filter are described below.
(a) Do not bundle the wires on the input side and output side of the noise filter.
When bundled, the output side noise will be induced into the input side wires from which the noise was filtered.
Input side (power supply side)
Input side (power supply side)
Output side (device side)
Output side (device side)
(b) Earth the noise filter earthing terminal to the control cabinet with the shortest
wire possible (approx. 10 cm (3.94 inch)).
Noise Filter Model Name FN343-3/01 FN660-6/06 ZHC2203-11
Manufacturer SCHAFFNER SCHAFFNER TDK Rated current 3 A 6 A 3 A Rated voltage 250 V
Introduction · Filter · Filter

8.2 Requirement to Conform to the Low Voltage Directive
The Low Voltage Directive requires each device that operates with the power supply ranging from 50 to 1000VAC and 75 to 1500VDC to satisfy the safety requirements. In Sections 8.2.1 to 8.2.6, cautions on installation and wiring of the MELSEC-Q series PLC to conform to the Low Voltage Directive are described. We have put the maximum effort to develop this material based on the requirements and standards of the regulation that we have collected. However, compatibility of the devices which are fabricated according to the contents of this manual to the above regulation is not guaranteed. Each manufacturer who fabricates such device should make the final judgement about the application method of the Low Voltage Directive and the product compatibility. 8.2.1 Standard applied for MELSEC-Q series PLC
The standard applied for MELSEC-Q series PLC is EN61010-1 safety of devices used in measurement rooms, control rooms, or laboratories. The MELSEC-Q series PLC modules which operate at the rated voltage of 50VAC/75VDC or above are also developed to conform to the above standard. The modules which operate at the rated voltage of less than 50VAC/75VDC are out of the Low Voltage Directive application range. 8.2.2 MELSEC-Q series PLC selection
There are dangerous voltages (voltages higher than 42.4V peak) inside the power supply modules of the 100/200VAC rated I/O voltages. Therefore, the CE marked models are enhanced in insulation internally between the primary and secondary.
There are dangerous voltages (voltages higher than 42.4V peak) inside the I/O modules of the 100/200VAC rated I/O voltages. Therefore, the CE marked models are enhanced in insulation internally between the primary and secondary. The I/O modules of 24VDC or less rating are out of the Low Voltage Directive application range.
Using 5VDC circuits inside, the above modules are out of the Low Voltage Directive application range.
The intelligent function modules (special function modules) such as the analog, network and positioning modules are 24VDC or less in rated voltage and are therefore out of the Low Voltage Directive application range.
Use the CE marked display device.

8.2.3 Power supply
The insulation specification of the power supply module was designed assuming installation category II. Be sure to use the installation category II power supply to the PLC. The installation category indicates the durability level against surge voltage generated by a thunderbolt. Category I has the lowest durability; category IV has the highest durability.
Category III Category II Category I Category IV
Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution. 8.2.4 Control box
Because the PLC is an open device (a device designed to be stored within another module), be sure to use it after storing in the control box.
In order to prevent persons who are not familiar with the electric facility such as the operators from electric shocks, the control box must have the following functions : (a) The control box must be equipped with a lock so that only the personnel who
has studied about the electric facility and have enough knowledge can open it. (b) The control box must have a structure which automatically stops the power
supply when the box is opened.
The control box also has the dustproof and waterproof functions. Insufficient dustproof and waterproof features lower the insulation withstand voltage, resulting in insulation destruction. The insulation in our PLC is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or below.
Pollution level 1 : An environment where the air is dry and conductive dust does not exist. Pollution level 2 : An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust. Generally, this is the level for inside the control box equivalent to IP54 in a control room or on the floor of a typical factory. Pollution level 3 : An environment where conductive dust exits and conductivity may be generated due to the accumulated dust. An environment for a typical factory floor. Pollution level 4 : Continuous conductivity may occur due to rain, snow, etc. An outdoor environment. As shown above, the PLC can realize the pollution level 2 when stored in a control box equivalent to IP54.

8.2.5 Grounding
There are the following two different grounding terminals. Use either grounding terminal in an earthed status.
noise resistance.
Functional grounding : Improves the noise resistance.
(1) 24VDC external power supply
For the MELSEC-Q series PLC 24VDC I/O modules and the intelligent function modules (special function modules) which require external supply power, use a model whose 24VDC circuit is intensively insulated from the hazardous voltage circuit. (2) External devices
When a device with a hazardous voltage circuit is externally connected to the PLC, use a model whose circuit section of the interface to the PLC is intensively insulated from the hazardous voltage circuit. (3) Intensive insulation
Intensive insulation refers to the insulation with the dielectric withstand voltage shown in Table 8.1.
(Installation Category II, source : IEC664)
Rated voltage of hazardous voltage area Surge withstand voltage (1.2/50 s)
150VAC or below 2500 V 300VAC or below 4000 V
8 - 11 8 - 11

9 LOADING AND INSTALLATION
In order to increase the reliability of the system and exploit the maximum performance of its functions, this section describes the methods and precautions for the mounting and installation of the system. 9.1 General Safety Requirements
! DANGER Install a safety circuit external to the PLC that keeps the entire
system safe even when there are problems with the external power supply or the PLC module. Otherwise, trouble could result from erroneous output or erroneous operation. (1) Outside the PLC, construct mechanical damage preventing
interlock circuits such as emergency stop, protective circuits, positioning upper and lower limits switches and interlocking forward/reverse operations. (2) When the PLC detects the following problems, it will stop
calculation and turn off all output in the case of (a). In the case of (b), it will stop calculation and hold or turn off all output according to the parameter setting. Note that the A1S series module will turn off the output in either of cases (a) and (b). All outputs of AnS Series Module will be switched off in the following cases:
equipment and over voltage protection equipment. (b) The PLC CPUs self-diagnosis functions, such as the watch
dog timer error, detect problems. In addition, all output will be turned on when there are problems that the PLC CPU cannot detect, such as in the I/O controller. (3) Output could be left on or off when there is trouble in the outputs
module relay or transistor. So build an external monitoring circuit that will monitor any single outputs that could cause serious trouble. When overcurrent which exceeds the rating or caused by short-
circuited load flows in the output module for a long time, it may cause smoke or fire. To prevent this, configure an external safety circuit, such as fuse. Build a circuit that turns on the external power supply when the PLC
main module power is turned on. If the external power supply is turned on first, it could result in erroneous output or erroneous operation. When there are communication problems with the data link, refer to
the corresponding data link manual for the operating status of each station. Not doing so could result in erroneous output or erroneous operation.operating status of each station. Not doing so could result in erroneous output or erroneous operation.

! DANGER When connecting a peripheral device to the CPU module or connecting
a personal computer or the like to the special function module to exercise control (data change) on the running PLC, configure up an interlock circuit in the sequence program to ensure that the whole system will always operate safely. Also before exercising other control (program change, operating status change (status control)) on the running PLC, read the manual carefully and fully confirm safety. Especially for the above control on the remote PLC from an external device, an immediate action may not be taken for PLC trouble due to a data communication fault. In addition to configuring up the interlock circuit in the sequence program, corrective and other actions to be taken as a system for the occurrence of a data communication fault should be predetermined between the external device and PLC CPU.
! CAUTION Do not bunch the control wires or communication cables with the main
circuit or power wires, or install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that would cause erroneous operation. When controlling items like lamp load, heater or solenoid valve using an
output module, large current (approximately ten times greater than that present in normal circumstances) may flow when the output is turned OFF to ON. Take measures such as replacing the module with one having sufficient rated current.
When the PLC power supply is switched ON-OFF, correct control output may not be performed temporarily due to differences in delay time and starting time between the PLC power supply and the external power supply for the controlled object (especially DC). For example, if the external power supply for the controlled object is switched on in a DC output module and then the PLC power supply is switched on, the DC output module may provide false output instantaneously at power-on of the PLC. Therefore, it is necessary to make up a circuit that can switch on the PLC power supply first. Also, an abnormal operation may be performed if an external power supply fault or PLC failure takes place. To prevent any of these abnormal operations from leading to the abnormal operation of the whole system and in a fail-safe viewpoint, areas which can result in machine breakdown and accidents due to abnormal operations (e.g. emergency stop, protective and interlock circuits) should be constructed outside the PLC. The following page gives examples of system designing in the above viewpoint.

(1) System design circuit example (when not using ERR contact of
power supply module)

Set time for DC power supply to be established.
Voltage relay is recommended
Low battery alarm (Lamp or buzzer)
Power to output equipment switched OFF when the STOP signal is given.
ON when run by SM403
In the case of an emergency stop or a stop caused by a limit switch.
Interlock circuits as necessary.Provide external interlock circuits for conflicting operations, such as forward rotation and reverse rotation, and for parts that could damage the machine or cause accidents if no interlock were used.
Power to output equipment switched OFF when the STOP signal is given.
In the case of an emergency stop or a stop caused by a limit switch.
For AC For AC/DC 1) Switch power ON. 2) Set CPU to RUN. 3) Turn ON the start switch. 4) When the magnetic contactor (MC) comes on, the output equipment is powered and may be driven by the program.
1) Switch power ON. 2) Set CPU to RUN. 3) When DC power is established, RA2 goes ON. 4) Timer (TM) times out after the DC power reaches 100%. (The TM set value should be the period of time from when RA2 goes ON to the establishment of 100% DC voltage. Set this value to approximately 0.5 seconds.) 5) Turn ON the start switch. 6) When the magnetic contactor (MC) comes on, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.)

(2) System design circuit example (when using ERR contact of power
supply module)
FOR AC/DC

Set time for DC power supply to be established.
OFF at stop error from ERR POWER SUPPLY MODULE
MC MC Interlock circuits asnecessary. Provide external interlock circuits for conflicting operations, such as forward rotation and reverse rotation, and for parts that could damage the machine or cause accidents if no interlock were used.
Power to output equipment switched OFF when ERR contact turns OFF.
In the case of an emergency stop or a stop caused by a limit switch.
The power-ON procedure is as follows: For AC/DC 1) Switch power ON. 2) Set CPU to RUN. 3) When DC power is established, RA2 goes ON. 4) Timer (TM) times out after the DC power reaches 100%. (The TM set value should be the period of time from when RA2 goes ON to the establishment of 100% DC voltage. Set this value to approximately 0.5s.) 5) Turn ON the start switch. 6) When the magnetic contactor (MC) comes on, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.)

(3) Fail-safe measures against failure of the PLC
Failure of a CPU module or memory can be detected by the self-diagnosis function. However, failure of I/O control area may not be detected by the CPU module. In such cases, all I/O points turn ON or OFF depending on a condition of problem, and normal operating conditions and operating safety cannot sometimes be maintained. Though Mitsubishi PLCs are manufactured under strict quality control, they may cause failure or abnormal operations due to unspecific reasons. To prevent the abnormal operation of the whole system, machine breakdown, and accidents, fail-safe circuitry against failure of the PLC must be constructed outside the PLC. Examples of a system and its fail-safe circuitry are described below:

Output module for fail-safe purpose 1

ON delay timer

9.2 Calculating Heat Generation by PLC
The ambient temperature inside the board storing the PLC must be suppressed to a PLC usable ambient temperature of 55°C. For the design of radiation from the storing board, it is necessary to know the average power consumption (heating value) of the devices and instruments stored in the board. Here the method of obtaining the average power consumption of the PLC system is described. From the power consumption, calculate a rise in ambient temperature inside the board.
The power consuming parts of the PLC are roughly classified into six blocks as shown below.
The power conversion efficiency of the power supply module is approx. 70 %, i.e., 30 % of the output power is consumed by heating. As a result, 3/7 of the output power becomes the power consumption. Therefore the calculation formula is as follows.
(2) Power consumption of a total of 5 VDC logic section of each
module The power consumption of the 5 VDC output circuit section of the power supply module is the power consumption of each module (including the current consumption of the base unit).
(3) A total of 24 VDC average power consumption of the output module
(power consumption for simultaneous ON points) The average power of the external 24 VDC power is the total power consumption of each module.
(4) Average power consumption due to voltage drop in the output
section of the output module (Power consumption for simultaneous ON points)
WOUT = IOUT Vdrop Number of outputs Simultaneous ON rate (W)
IOUT : Output current (Current in actual use) (A) Vdrop : Voltage drop in each output module (V)
module(Power consumption for simultaneous ON points)
WIN = IIN E Number of input points Simultaneous ON rate (W)
IIN : Input current (Effective value for AC) (A) E : Input voltage (Voltage in actual use) (V)

(6) Power consumption of the power supply section of the intelligent
function module
WS = I5V 5 + I24V 24 + I100V 100 (W) The total of the power consumption values calculated for each block becomes the power consumption of the overall sequencer system.
W = WPW + W5V + W24V + WOUT + WIN + WS (W) From this overall power consumption (W), calculate the heating value and a rise in ambient temperature inside the board. The outline of the calculation formula for a rise in ambient temperature inside the board is shown below.
UA (°C)
W : Power consumption of overall sequencer system (value obtained above) A : Surface area inside the board U : When the ambient temperature inside the board is uniformed by a fan 6
POINT When a rise in ambient temperature inside the board exceeds the specified limit, it is recommended that you install a heat exchanger in the board to lower the ambient temperature inside the board. If a normal ventilating fan is used, dust will be sucked into the PLC together with the external air, and it may affect the performance of the PLC.
Q35B
Q61P-A1
Q02HCPU
QX40
QX40
QY10
(b) 5 VDC current consumption of each module
Q02HCPU : 0.64 (A) QX40 : 0.05 (A) QY10 : 0.43 (A) QJ71LP21-25 : 0.55 (A) Q35B : 0.074 (A) (c) Power consumption of power supply module
WPW = 3/7 (0.64+0.05+0.05+0.43+0.55+0.074) 5) = 3.84 (W) (d) Power consumption of a total of 5 VDC logic section of each module
W5V = (0.64+0.05+0.05+0.43+0.55+0.074) 5) = 8.97 (W) (e) A total of 24 VDC average power consumption of the output module
9 - 7 9 - 7
Vacant

(f) Average power consumption due to voltage drop in the output section of the
W OUT = 0 (W)
(g) Average power consumption of the input section of the input module
W IN = 0.004 24 32 1 = 3.07 (W)
(h) Power consumption of the power supply section of the intelligent function
module W S = 0 (W)
(i) Power consumption of overall system.
W = 3.84 + 8.97 + 0 + 0 + 3.07 + 0 = 15.88 (W)

9.3 Module Installation 9.3.1 Precaution on installation
! CAUTION Use the PLC in an environment that meets the general specifications
contained in this manual. Using this PLC in an environment outside the range of the general specifications could result in electric shock, fire, erroneous operation, and damage to or deterioration of the product. Hold down the module loading lever at the module bottom, and
securely insert the module fixing latch into the fixing hole in the base unit. Incorrect loading of the module can cause a malfunction, failure or drop.When using the PLC in the environment of much vibration, tighten the module with a screw. Tighten the screw in the specified torque range. Undertightening can cause a drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to damage to the screw or module. When installing more cables, be sure that the base unit and the module
connectors are installed correctly. After installation, check them for looseness. Poor connections could cause an input or output failure. Securely load the memory card by pushing it into the memory card
loading slot. Check for insecure loading after loading the memory card. Not doing so can cause a malfunction due to a contact fault. Completely turn off the external power supply before loading or
unloading the module. Not doing so could result in electric shock or damage to the product. Do not directly touch the module's conductive parts or electronic
components. Touching the conductive parts could cause an operation failure or give damage to the module.
This section gives instructions for handling the CPU, I/O, intelligent function and power supply modules, base units and so on.
(1) Module enclosure, terminal block connectors and pin connectors are made of resin;
do not drop them or subject them to strong impact.
(2) Do not remove modules' printed circuit boards from the enclosure in order to avoid
changes in operation.
(3) Tighten the module fixing screws and terminal block screws within the tightening
torque range specified below.

I/O module terminal block screw (M3 screw) 42 to 58 N • cm
I/O module terminal block fixing screw (M3.5 screw) 66 to 89 N • cm
Power supply module terminal screw (M3.5 screw) 66 to 89 N • cm
(4) Be sure to install the power supply module in the Q3 B, Q6 B and QA1S6 B. Even if the power supply module is not installed, when the I/O modules and intelligent function module installed on the base units are of light load type, the modules may be operated. In this case, because a voltage becomes unstable, we cannot guarantee the operation.
(5) When an extension cable is used, do not bind the cable together with the main
circuit (high voltage, heavy current) line or lay them close to each other.

(6) Install the main base unit (by screwing) in the following procedure.
slot. Remove the base unit after unloading the module from the right-end slot. Note2 : The mounting screws that included with the slim type main base unit differ
from those included with other types of the base unit. When ordering mounting screws for the slim type main base unit, specify "cross recessed head bind screw M4 x 12 (black)."
Panel · Panel · Panel

(7) Note the following points when mounting a DIN rail.
Mounting a DIN rail needs special adaptors (optional), which are to be user- prepared. (a) Applicable adaptor types
For Q38B, Q312B, Q68B, Q612B : Q6DIN1 For Q35B, Q65B : Q6DIN2 For Q33B, Q52B, Q55B, Q63B, Q32SB, Q33SB, Q35SB : Q6DIN3
The way to install the adaptors for mounting a DIN rail to the base unit is given below.

Place the hook of the adaptor (small) in the lower hole.
Push the top of the adaptor (small) far enough until it "clicks".
Insert the adaptor (large) into the grooves of the base unit from below.
Push the bottom of the adaptor (large) far enough until it "clicks". (c) Applicable DIN rail types (JIS C 2812)
(d) DIN rail mounting screw intervals
When using a TH35-7.5Fe or TH35-7.5Al DIN rail, rail mounting screws should be tightened at a pitch of 200 mm (7.88 inch) or less in order to ensure that the rail has sufficient strength.
DIN rail DIN rail mounting screw

35mm (1.38 inch)
P=200mm (7.88 inch) or less
Base unit rear

9.3.2 Instructions for mounting the base unit
When mounting the PLC to an enclosure or similar, fully consider its operability, maintainability and environmental resistance.
For enhanced ventilation and ease of module replacement, leave the following clearances between the module top/bottom and structure/parts. (a) In case of main base unit or extension base unit
Indicates the panel top, wiring duct or any part position.


30mm (1.18 inch) or more 1
30mm (1.18 inch) or more
5mm (0.20 inch) or more 2 5mm (0.20 inch) or more

Indicates the panel top, wiring duct or any part position.

30 mm (1.18 inch) or more 1

30 mm (1.18 inch) or more
1 : For wiring duct with 50 (1.97 inch) mm or less height. 40 mm (1.58 inch) or more for other cases. 2 : The cable of the power supply module of the slim type main base unit protrudes out of the left end of the module. Install the module while reserving 17 mm (0.67 inch) or more wiring space. If the cable sheath is susceptible to damage caused by a structural object or part on the left side of the module, take a protective measure with spiral tube or a similar insulator. 3 : 80 mm (3.15 inch) mm or more for the connector type.
Panel · Door

(2) Module mounting orientation
(a) Since the PLC generates heat, it should be mounted on a well ventilated
location in the orientation shown below.
(b) Do not mount it in either of the orientations shown below.
Mount the base unit on a flat surface. If the mounting surface is not even, this may strain the printed circuit boards and cause malfunctions. (4) Installation of unit in an area where the other devices are installed
Avoid mounting base unit in proximity to vibration sources such as large magnetic contractors and no-fuse circuit breakers; mount these on a separate panel or at a distance. (5) Distances from the other devices



9.3.3 Installation and removal of module
This section explains how to install and remove a power supply, CPU, I/O, intelligent function or another module to and from the base unit.
(1) Installation and removal of the module from Q3 B, ,Q5 B and
Q6 B The installation and removal of the module from Q3 B/Q6 B base unit are described below. (a) Installation of module on Q3 B, Q5 B and Q6 B

Insert the module fixing latch into the module fixing hole of the base unit.
Push the module in the direction of arrow to load it into the base unit.
Make sure that the module is inserted in the base unit securely.
POINTS (1) Always insert the module fixing latch of the module into the module fixing hole.
Forcing the hook into the hole will damage the module connector and module. (2) When using the PLC in a place where there is large vibration or impact, screw
the CPU module to the base unit. Module fixing screw : M3 12 (user-prepared)
Base unit


Hold the module with both hands, and push the unit fixing hook on the top of the module with a finger until it stops.

While pushing the unit fixing hook, and using the bottom of the module as a support, pull the module toward you.
Lift the module upwards and remove the module fixing latch from the module fixing hole.

POINT When the module fixing screw is used, always remove the module by removing the module fixing screw and then taking the module fixing latch off the module fixing hole of the base unit. Do not try to remove the module forcibly since this may damage the module.
Module connector

(2) Installation and removal of the module from QA1S6 B
The procedure for installing and removing the module from the QA1S6 B base unit is described below. (a) Installation of module on QA1S6 B


Insert the module fixing projections into the module fixing hole in the base unit.
Install the module onto the base unit by pushing the top forward.
Make sure that the module is firmly inserted in the base unit. Then, secure it with the module mounting screw.

POINT Make sure to install the module, with the module fixing projection inserted into the module fixing hole, using the module fixing screws. Do not try to forcibly install the module without inserting the projection into the hole, since this may damage the module connector and the module.



Remove the module mounting screw, and using the bottom of the module as a support, pull the top of the module toward you.
Lift the module upwards and remove the module fixing projections from the module fixing hole.

POINT To remove the module, make sure to remove the module fixing screws, and then disengage the module fixing projection from the module fixing hole. Do not try to remove the module forcibly since this may damage the module fixing projection.
Base unit · Module connector · Module fixing hole

9.4 How to Set Stage Numbers for the Extension Base Unit
When using two or more extension base units, their stage numbers must be set with their stage number setting connectors. Extension 1 need not be set since the extension number is factory-set to 1. Make this setting in the following procedure.
(1) The stage number setting connector of the extension base unit is located under the
IN side base cover. (Refer to Section 6.4 for the setting of the extension number setting connector.) First, loosen the upper and lower screws in the IN side base cover and remove the base cover from the extension base unit.

(2) Insert the connector pin in the required stage number location of the connector
(PIN1) existing between the IN and OUT sides of the extension cable connector.
(3) Install the base cover to the extension base unit and tighten the base cover screw.


9.5 Connection and Disconnection of Extension Cable
(1) Instructions for handling an extension cable
Holding the ferrite core may cause the cable to open within the connector. Also, if the ferrite core is shifted, the characteristic will change. When handling the cable, take care not to shift the ferrite core positions. (2) Connection of extension cable
POINT When connecting an extension base unit to the main base unit with an extension cable, always plug the OUT side connector of the main base unit and the IN side connector of the extension base unit with an extension cable. The system will not operate properly if the extension cable is connected in the form of IN to IN, OUT to OUT or IN to OUT. When connecting two or more extension base units, plug the OUT side connector of the first extension base unit and the IN side connector of the second extension base unit with an extension cable.

(a) To connect an extension cable to the main base unit, remove the portion
under the OUT characters on the base cover with a tool such as a flat-blade screwdriver (5.5 75, 6 100). This also applies to a case where an extension cable is connected to the OUT side connector of the extension base unit.


(b) To connect the extension cable to the next extension base unit, remove the
seal applied under the IN characters on the base cover.
IN side of extension base unit
(c) When plugging the extension cable to any base unit, hold the connector part
of the extension cable.
fixing screws. (Tightening torque: 20N • cm)

Base cover · Seal

(3) Disconnection of extension cable
When unplugging the extension cable, hold and pull the connector part of the extension cable after making sure that the fixing screws have been removed completely.

9.6 Wiring
9.6.1 The precautions on the wiring
! DANGER Completely turn off the external power supply when installing or
placing wiring. Not completely turning off all power could result in electric shock or damage to the product. When turning on the power supply or operating the module after
installation or wiring work, be sure that the module's terminal covers are correctly attached. Not attaching the terminal cover could result in electric shock.
! CAUTION Be sure to ground the FG terminals and LG terminals to the
protective ground conductor. Not doing so could result in electric shock or erroneous operation. When wiring in the PLC, be sure that it is done correctly by checking
the product's rated voltage and the terminal layout. Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or damage. External connections shall be crimped or pressure welded with the
specified tools, or correctly soldered. Imperfect connections could result in short circuit, fires, or erroneous operation. Tighten the terminal screws with the specified torque. If the terminal screws
are loose, it could result in short circuits, fire, or erroneous operation. Tightening the terminal screws too far may cause damages to the screws and/or the module, resulting in fallout, short circuits, or malfunction. Be sure there are no foreign substances such as sawdust or wiring
debris inside the module. Such debris could cause fires, damage, or erroneous operation. The module has an ingress prevention label on its top to prevent
foreign matter, such as wire offcuts, from entering the module during wiring. Do not peel this label during wiring. Before starting system operation, be sure to peel this label because of heat dissipation.
The precautions on the connection of the power cables are described below. (1) Power supply wiring
(a) Separate the PLC's power supply line from the lines for I/O devices and
power devices as shown below. When there is much noise, connect an insulation transformer.
PLC power supply Main power supply
PLC
T1
9 - 23 9 - 23

(b) Do not connect the 24VDC outputs of two or more power supply modules in
parallel to supply power to one I/O module. Parallel connection will damage the power supply modules.
24VDC 24VDC
(c) 100VAC, 200VAC and 24VDC wires should be twisted as dense as possible.
Connect the modules with the shortest distance. Also, to reduce the voltage drop to the minimum, use the thickest wires possible (maximum 2mm2). (d) Do not bundle the 100VAC and 24VDC wires with, or run them close to, the
main circuit (high voltage, large current) and I/O signal lines. Reserve a distance of at least 100 mm from adjacent wires. (e) As a countermeasure to power surge due to lightening, connect a surge
absorber for lightening as shown below.
PLC
E2
E1
Surge absorber for lightening
POINT (1) Separate the ground of the surge absorber for lightening (E1) from that of the
PLC (E2). (2) Select a surge absorber for lightening whose power supply voltage does no
exceed the maximum allowable circuit voltage even at the time of maximum power supply voltage elevation.

(2) Wiring of I/O equipment
(a) Insulation-sleeved crimping terminals cannot be used with the terminal block.
It is recommended to cover the wire connections of the crimping terminals with mark or insulation tubes. (b) The wires used for connection to the terminal block should be 0.3 to 0.75mm2
in core and 2.8mm (0.11 inch) max. in outside diameter. (c) Run the input and output lines away from each other. (d) When the wiring cannot be run away from the main circuit and power lines,
use a batch-shielded cable and ground it on the PLC side. In some cases, ground it in the opposite side.
DC
(e) Where wiring runs through piping, ground the piping without fail. (f) Run the 24VDC input line away from the 100VAC and 200VAC lines. (g) Wiring of 200m (686.67 ft.) or longer distance will give rise to leakage currents
due to the line capacity, resulting in a fault. Refer to Section 11.5 for details. (3) Grounding
To ground the cable, follow the steps (a) to (c) shown below. (a) Use the dedicated grounding as far as possible.
Grounding shown below.
PLC Another equipment PLC Another equipment
(1) Independent grounding Best (2) Common grounding Good (3) Joint grounding Not allowed
(c) For grounding a cable, use the cable of 2 mm2 or more.
Position the ground-contact point as closely to the sequencer as possible, and reduce the length of the grounding cable as much as possible.

9.6.2 Connecting to the power supply module
The following diagram shows the wiring example of power lines, grounding lines, etc. to the main and extension base units.

Connect to 24VDC terminals of I/O module that requires 24VDC internally.
POINTS (1) Use the thickest possible (max. 2 mm2 (14 AWG)) wires for the 100/200 VAC
and 24 VDC power cables. Be sure to twist these wires starting at the connection terminals. To prevent a short-circuit should any screws loosen, use solderless terminals with insulation sleeves. (2) When the LG terminals and FG terminals are connected, be sure to ground the
wires. Do not connect the LG terminals and FG terminals to anything other than ground. If LG terminals and FG terminals are connected without grounding the wires, the PLC may be susceptible to noise. In addition, since the LG terminals have potential, the operator may receive an electric shock when touching metal parts. (3) 1 An error cannot be output from the ERR terminal of the power supply module loaded on the extension base. To output an error, use the ERR terminal of the power supply module loaded on the main base unit.
Main base unit

10 MAINTENANCE AND INSPECTION
! DANGER Do not touch the terminals while power is on.
Doing so could cause shock. Correctly connect the battery. Also, do not charge, disassemble,
heat, place in fire, short circuit, or solder the battery. Mishandling of a battery can cause overheating or cracks which could result in injury and fires. Turn the power off when cleaning the module or tightening the
terminal screws or module mounting screws. Conducting these operations when the power is on could result in electric shock. Loose terminal screws may cause short circuits or malfunctions. Failure to mount the module properly will result in short circuit, malfunction or in the module falling.
! CAUTION In order to ensure safe operation, read the manual carefully to
acquaint yourself with procedures for program change, forced outputs, RUN, STOP, and PAUSE operations, etc., while operation is in progress. Operation mistakes could cause damage to the equipment and other problems. Never try to disassemble of modify module. It may cause product
failure, malfunction, fire or cause injury. When using any radio communication device such as a cellular
phone or a PHS phone, keep them away from the controller at least 25 cm (9.85 inch) or it may cause a malfunction. Turn the power off when installing or removing the modules.
Trying to install or remove the module while the power is on could damage the module or result in erroneous operation.
In order that you can use the PLC in normal and optimal condition at all times, this section describes those items that must be maintained or inspected daily or at regular intervals.

10.1 Daily Inspection
The items that must be inspected daily are listed below.
Item Inspection Item Inspection Judgment Criteria Remedy
Check that fixing screws are not loose and the cover is not dislocated.
The screws and cover must be installed securely.
Further tighten the screws.
Check that the module is not dislocated and the unit fixing hook is engaged securely.
The unit fixing hook must be engaged and installed securely.
Securely engaged the unit fixing hook.
Check for loose terminal screws. Screws should not be loose. Retighten terminal screws Check distance between Solderless terminals.
The proper clearance should be provided between Solderless terminals Correct. 3 Connecting conditions
Check connectors of extension cable. Connections should no be loose. Retighten connector mounting screws. Power supply "POWER" LED Check that the LED is ON. The LED must be ON. (Abnormal if the
The LED must be ON. (Abnormal if the LED is OFF.) CPU "ERR." LED
Check that the LED is ON in RUN status.
The LED must be OFF. (Abnormal if the LED is ON or flickering.) CPU "BAT." LED
Check that the LED is OFF.
Check that the LED is OFF.
The LED must be ON when the input power is turned ON. The LED must be extinguished when the input power is turned OFF. (Abnormal if the LED does not turn ON or turn OFF as indicated above.)
Follow Section 10.2.
Input LED Check that the LED turns ON and OFF.
The LED turns ON when the output power is turned ON. The LED must be extinguished when the output power is turned OFF. (Abnormal if the LED does not turn ON or turn OFF as indicated above.)
Output LED Check that the LED turns ON and OFF.

10.2 Periodic Inspection
The items that must be inspected one or two times every 6 months to 1 year are listed below. When the equipment is moved or modified, or layout of the wiring is changed, also perform this inspection.
Item Inspection Item Inspection Judgment Criteria Remedy
Ambient environment
Ambient temperature 0 to 55 °C
When the sequencer is used in the board, the ambient temperature in the board becomes the ambient temperature.
Measure with a thermometer and a hygrometer. Measure corrosive gas.
Corrosive gas must not be present.
85 to 132VAC 170 to 264VAC 2 Power voltage
Measure a voltage across the terminals of 100/200VAC and 24VDC. 15.6 to 31.2VDC
Change the power supply.
Further tighten screws. If the CPU, I/O, or power supply module is loose, fix it with screws. 3
Looseness, rattling Move the module to check for looseness and rattling.
The module must be installed fixedly.
Adhesion of dirt and foreign matter Check visually. Dirt and foreign matter must not be present. Remove and clean.
Try to further tighten screws with a screwdriver. Screws must not be loose. Further tighten.
Proximity of solderless terminals to each other
Check visually. Solderless terminals must be positioned at proper intervals. Correct. 4
Looseness of connectors Check visually. Connectors must not be loose. Further tighten connector
fixing screws.
Even if the lowering of a battery capacity is not shown, replace the battery with a new one if a specified service life of the battery is exceeded.
check on the monitor mode of the GX Developer that SM51 or SM52 is turned OFF.
(Preventive maintenance)
1 When AnS Series Module is included in the system, the judgement criteria will be from 10 to 90 % RH.

10.3 Battery Replacement
When the voltage of the program and power interrupt hold-on function backup battery is lowered, the special relays SM51 and SM52 are energized. Even if these special relays are energized, the contents of the program and power interrupt hold-on function are not erased immediately. If the energization of these relays is recognized, however, these contents may be deleted unintentionally. While a total of the power interrupt hold-on time after the SM51 is energized is within a specified time, replace the battery with a new one.
POINTS The SM51 is used to give an alarm when the capacity of the battery is lowered. Even after it is energized, the data is held for a specified time. For safety, however, replace the battery with a new one as early as possible. The SM52 is energized when the battery causes a complete discharge error. Immediately after the relay has been energized, replace the battery with a new one. Whichever voltage of the battery of the CPU module and SRAM card is lowered, the SM51 and SM52 are energized. To identify the specific battery of the memory of which voltage is lowered, check the contents of the special resisters SD51 and SD52. When the voltage of the battery of each memory is lowered, the bit corresponding to each of SD51 and SD52 memories is turned on.

Bit 0 CPU module
Bit 1, 2 SRAM card

POINTS The relation between the backups of the memories preformed by the batteries which are installed on the CPU module and SRAM card is described below. The items that must be considered are the following two points. 1) The battery installed on the CPU module cannot backup the memory of the SRAM card. 2) The battery installed on the SRAM card cannot backup the memory of the CPU module.
The standard service life and replacement procedures of the battery is described on the next page.

10.3.1 Battery life
(1) CPU module battery (Q6BAT) life
(a) The CPU module battery life is given below.

alarm occurrence) 0% 5433hr 13120hr 120hr 30% 7761hr 18742hr 120hr 50% 10866hr 26240hr 120hr 70% 18110hr 43733hr 120hr Q02CPU
100% 10years 10years 120hr 0% 2341hr 6435hr 120hr 30% 3344hr 9192hr 120hr 50% 4682hr 12870hr 120hr 70% 7803hr 21450hr 120hr
100% 10years 10years 120hr 0% 1260hr 4228hr 48hr 30% 1800hr 6040hr 48hr 50% 2520hr 8456hr 48hr 70% 4200hr 14093hr 48hr
(b) The Q6BAT life is 10 years when it is used without connecting to the CPU
module.
The SRAM card battery life changes depending on the combination of the serial number (first 5 digits) of the CPU module and the manufacturing control number of the memory card. The SRAM card battery life is indicated below.
(a) CPU module whose serial number's first 5 digits are "04012" or later

0% 2400hr 2.7years 20hr 30% 2880hr 3.6years 20hr 50% 4320hr 4.5years 20hr 70% 6480hr 5.0years 20hr
2 100% 5.0years 5.0years 50hr 0% 2400hr 2.7years 20hr 30% 2880hr 3.6years 20hr 50% 4320hr 4.5years 20hr 70% 6480hr 5.0years 20hr Q2MEM-2MBS

(b) CPU module whose serial number's first 5 digits are "04011" or earlier

50%.) 2: The manufacturing control number is given on the SRAM card rear label (see below).
Manufacturing control number
Do not subject to mechanical shock!
Do not expose to extreme temperrature,
POINT Remember that the SRAM card consumes battery power even when the battery is connected to the CPU module and the power is turned ON.
If the special relay SM51 (battery low latch) turns on, immediately replace the battery. If an alarm has not yet occurred, it is recommended to replace the battery periodically according to the conditions of use.

10.3.2 Battery replacement procedure
(1) CPU module battery replacement procedure
When the CPU module battery has been exhausted, replace the battery with a new one according to the procedure shown below. The PLC power must be on for 10 minutes or longer before dismounting the battery. Even when the battery is dismounted, the memories are backed up by the capacitor for a while. However, if the replacement time exceeds the guaranteed value specified in the table below, the contents stored in the memories may be erased. To prevent this trouble, replace the battery speedily.
Backup time by capacitor[min]

Insert a new battery into the holder in the correct direction. Connect the lead to the connector.

(2) SRAM card CPU module battery replacement procedure
Replace the SRAM card battery in the following procedure.
POINTS Replace the battery while paying attention to the following. (a) To back up the data, replace the SRAM card battery with the PLC power supply
ON and the SRAM card installed. (b) Start replacement after backing up the CPU module data using GX Developer. (c) Since replacement is made with the PLC power supply ON, take extreme care
not to get an electric shock. (d) When dismounting or mounting the battery holder on the SRAM card, take care
so that the battery does not come out of the battery holder. (e) When replacing the battery with the PLC power supply OFF, always back up the
data before starting replacement. [Battery replacement procedure] 1) Back up the SRAM card data using GX Developer. 2) Replace the battery. 3) Write the backed up data from GX Developer to the memory card.
Open the front cover while the PLC power supply is on.
Using a flat screw-driver, slide the battery holder's locking switch away from the "LOCK" position.
Remove the battery holder from the SRAM card.
Remove the old battery from its holder.
Insert a new battery into the holder in the correct direction.
Push the battery holder all the way into the memory card, and confirm that the battery holder's locking switch is set to the "LOCK" position.
Monitor SM52 to verify on/off.
ON
Monitor SD52 to verify the bit number
Bit 0 is on.
that is on.
A bit other than 0 is on
The CPU module battery is faulty.
Bit 1 or 2 on: Memory card A battery is faulty.
Refer to Section 10.3.2 (1).

This section describes the various types of trouble that occur when the system is operated, and causes and remedies of these troubles. 11.1 Troubleshooting Basics
In order to increase the reliability of the system, not only highly reliable devices are used but also the speedy startup of the system after the occurrence of trouble becomes an important factor. To start up the system speedily, the cause of the trouble must be located and eliminated correctly. The basic three points that must be followed in the troubleshooting are as follows.
Visually check the following. 1) Movement of sequencer (stopped condition, operating condition) 2) Power supply on/off 3) Status of input/output devices 4) Power supply module, CPU module, I/O module, intelligent function module, installation condition of extension cable 5) Status of wiring (I/O cables, cables) 6) Display status of various types of indicators ("POWER" LED, "RUN" LED, "ERR." LED, I/O LED) 7) Status of setting of various types of set switches (Setting of No. of stages of extension base unit, power interrupt hold-on status)
After confirming items 1) to 7), connect the GX Developer, and check the operating conditions of the PLC and the contents of the program.
Check to see how the operating condition of the PLC varies while the PLC is operated as follows. 1) Set the RUN/STOP switch to STOP. 2) Reset the trouble with the RESET/L.CLR switch. 3) Turn ON and OFF the power supply.
Estimate the troubled part in accordance with items (1) and (2) above. 1) PLC or external devices 2) I/O module or others 3) Sequence program

The trouble investigating methods, contents of troubles for the error codes, and remedies of the troubles are described below. 11.2.1 Troubleshooting flowchart
The following shows the contents of the troubles classified into a variety of groups according to the types of events.
Proceed to Section 11.2.2, "Flowchart for when the "MODE" LED is not turned on."
Proceed to Section 11.2.3, "Flowchart for when the "MODE" LED is flickering."
Proceed to Section 11.2.4, "Flowchart for when the "POWER" LED is turned off."
"RUN" LED off Proceed to Section 11.2.5, "Flowchart for when the "RUN" LED is turned off."
Proceed to Section 11.2.6, "When the "RUN" LED is flickering."
Proceed to Section 11.2.7, "Flowchart for when the "ERR." LED is on/flickering."
"ERR." LED on/flickering
Proceed to Section 11.2.8, "When the "USER" LED is turned on."
Proceed to Section 11.2.9, "When the "BAT. " LED is turned on."
"BAT. " LED on
Proceed to Section 11.2.10, "Flowchart for when the "BOOT" LED is flickering."
Proceed to Section 11.2.11, "Flowchart for when output module LED is not turned on" Output module LED not turned on
Proceed to Section 11.2.12 "Flowchart for when output load of output module dose not turn on."
I/O module not operating properly
Proceed to Section 11.2.13, "Flowchart for when unable to read a program."
Unable to read a program
Proceed to Section 11.2.14, "Flowchart for when unable to write a program."
Unable to write a program
Proceed to Section 11.2.15, "Flowchart for when unable to perform boot operation from memory card."
Unable to perform boot operation from memory card
Proceed to Section 11.2.16, "Flowchart for when UNIT. VERIFY ERR. occurs."
UNIT. VERIFY ERR. occurs.
Proceed to Section 11.2.17, "Flowchart for when CONTROL BUS ERR. occurs."
CONTROL BUS ERR. occurs.

The following shows the flowchart to be followed when the "MODE" LED of the CPU module does not turn on at PLC power-on.
"MODE" LED is not turned on.
Is the power supply for all the power supply modules turned on? Is the wiring of the power supply
Check the wire and turn on the power supply.
Is the "POWER" LED for the power supply module
Exchange the power supply module, and confirm if "POWER" LED is turned on.
NO
YES
Is the extension cable connected properly?(Isn't IN
connected to IN or OUT
Connect the extension cable properly.
YES
NO YES
Is the CPU module RESET/L. CLR switch in
Set the RESET/L. CLR switch in the neutral position.
Hardware fault Check operations in the order starting from the minimum system. If the module will not work, please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

The following shows the flowchart to be followed when the "MODE" LED of the CPU module flickers at PLC power-on, at operation start or during operation.
"MODE" LED is flickering
Did you make forced
Cancel forced ON/OFF.
NO
YES
Is the "MODE" LED turned on?
Is the RESET/L.CLR switch of the CPU module in
Move the RESET/L.CLR switch to the neutral position.
YES
Is the "MODE" LED turned on?
Hardware fault Check operations in the order starting from the minimum system. If the module will not work, please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

The following shows the flowchart to be followed when the "POWER" LED of the power supply module turns off at PLC power-on or during operation.
"POWER" LED is turned off.
Is there a power supply? Supply power.
NO YES
Is the power supply voltage within the voltage range given in the
The supply voltage should be within the rated range.
Properly fix the power supply module. Is the power supply
YES
NO YES
Is overcurrent protection and overvoltage
NO
NO YES
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

The following shows the flowchart to be followed when the "RUN" LED of the CPU module turns off during PLC operation.
"RUN" LED is turned off.
Is the "POWER" LED of the power supply module lit?
Proceed to Section 11.2.4, "Flowchart for when the "POWER" LED is turned off."
YES
Proceed to Section 11.2.7, "Flowchart for when the "ERR." LED is on/flickering."
Is "ERR." LED
NO
"RUN" LED is on.
(1) PLC part/connection fault (2) By excessive noise
Reset the CPU module RESET/L. CLR switch.
"RUN" LED is off.
For the case of (1) For the case of (2)
Set the CPU module's RUN/STOP switch to STOP and write END to address 0 with the GX Developer.
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
Set the RUN/STOP switch to RUN and enter to the monitor mode with the GX Developer to be operated.
"RUN" LED does not turn on.
"RUN" LED is on.
Considered to be a sequence program error.
Check the program and modify the program error location.
Connect a surge protector circuit such as CR to the noise source.
YES
11 - 6 11 - 6

If the "RUN" LED flickers, follow the steps below. The High Performance model QCPU flickers the "RUN" LED when the RUN/STOP switch is set from STOP to RUN after the programs or parameters are written in the CPU module during the stoppage. Though this is not the trouble with the CPU module, the operation of the CPU module is stopped. To bring the CPU module into RUN status, reset the CPU module with the RESET/L.CLR or set the RUN/STOP switch again from STOP to RUN. The "RUN" LED turns on. 11.2.7 Flowchart for when the "ERR." LED is on/flickering
The following shows the flowchart to be followed when the "ERR." LED of the CPU module turns on or flickers at PLC power-on, at operation start or during operation.
"ERR." LED is on/flickering.
Confirm details of error by GX Developer. (Refer to Section 11.3.)
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
Set the RUN/STOP switch to STOP.
Modify error details. (Refer to Section 11.3.)
Reset by the RESET/L. CLR switch.
Set the RUN/STOP switch to RUN.
Can the "ERR." LED
YES
11 - 7 11 - 7
Hardware fault · be turned off? · Completion

When the RESET/L.CLR switch is tilted to L.CLR several times for latch clear operation, the "USER" LED flickers to indicate that the latch clear processing is under operation. When the RESET/L.CLR switch is further tilted to L.CLR while the "USER" LED flickers, the "USER" LED turns off and terminates the latch clear processing. 11.2.9 When the "BAT." LED is turned on
If the "BAT." LED turns on, follow the steps described below. The "BAT." LED turns on when a low battery capacity is detected. If the "BAT." LED is on, monitor the special relays and special registers in the monitor mode of GX Developer to check which of the CPU module and SRAM card batteries was lowered in capacity. (SM51 to SM52, SD51 to SD52) After confirmation, replace the battery with a new one, and reset the CPU module with the RESET/L.CLR switch or run the LEDR instruction, and the "BAT. " LED will turns off.

The following shows the flowchart to be followed when the "BOOT" LED of the CPU module flickers at PLC power-on, at operation start or during operation.
Power off the PLC.
Remove the memory card.
Move the DIP switches SW2 and SW3 of the CPU module to ON.
Power on the PLC.
Completion of automatic write from memory card to standard ROM
Is the "BOOT" LED turned on?
Perform boot operation from standard ROM.
CPU module hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
"BOOT" LED flickering

The following shows the flowchart to be followed when the output module LED does not turn on during PLC operation.
Output module LED not turned on
Is the "MODE" LED on? Refer to Section 11.2.3.
Is the LED on when it is monitored on GX Developer?
Reexamine the program.
Check the input/output number on the GX Developer system monitor.
Does the output number match?
Change the output number.
Is the LED turned on when another output module
is forcibly turned on?
Is the LED turned on when the output module is changed for another output module,
CPU module, base unit, extension cable hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
Output module hardware fault Consult your local system service, agency or branch office.
which is then forcibly
Output module hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
NO (Flickering) · turned on?

11.2.12 Flowchart for when output load of output module does not turn on
The following shows the flowchart to be followed when the output load of the output module does not turn on during PLC operation.
The output load does not turn on.
Is the operation indicator of output module
Check output conditions with the monitor mode of the GX Developer.
Is voltage for the power supply load
Is the operation indicator of input module
Voltage measurement among the modules input and COM terminals.
What is the voltage among the various output
Set the GX Developer in the monitor mode and check that the input signal is OFF.
COM terminals of the
Is it reaching the supply voltage value?
Output module failure Replace the output module.
Check the external wiring and external input devices.
Check the power supply load wire and recover the power supply.
Check the load wire and load, and recover the power supply.
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
Confirm rush current when the load is at the maximum simultaneous on.
Change the output relay number and let the load maximum simultaneous on current to within the specification.
POINT For the trouble that the input signal to the input module is not turned off, troubleshoot referring to Section 11.5 Examples of I/O Modules Troubleshooting.

The following shows the flowchart to be followed when communication with GX Developer cannot be made during PLC power-on.
The CPU cannot communicate with the GX Developer.
Is the memory to be
Select the correct memory.
Can the CPU communicate
with the GX Developer?
Is the connection cable
Connect the connection cable properly.
Can the CPU communicate
with the GX Developer?
Can the CPU communicate with the GX Developer by replacing the
NO
USB Is the connection type RS-232?
Is the USB driver installed in the personal
NO Install the USB driver into the personal computer.
NO
Can the CPU communicate
with the GX Developer?
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
YES Can the CPU communicate with GX Developer by
lowering the baud rate?
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

The following shows the flowchart to be followed when programs cannot be written in the CPU module.
Unable to write a program
Is the DIP switch SW1 set to OFF?
Turn the DIP switch SW1 (system protect) to OFF.
Is it able to write a program?
Cancel the password using the GX Developer.
Is the password registered?
NO YES
Is it able to write a program?
Perform the following. Confirm whether the write-protect switch is off or not. Confirm if it is formatted. Confirm the writing destination specification.
Is the memory program
Perform the following. Organize file. Confirm memory space. Confirm the writing destination specification.
Is it able to write a program?
NO
YES
Is it able to write a program?

Format program memory.
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
1) · Completion

11.2.15 Flowchart for when it is unable to perform boot operation from memory card
The following shows the flowchart that must be followed when the boot operation of the CPU module cannot be performed using the memory card.

Is there CPU module error? Remove the cause of the error.
Is the drive that stores the parameter file specified?
Set the DIP switch 2 and 3 to the drive in which the parameter file is stored.
Set a file to boot file setup. Is a file set with parameter
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

The following shows the flowchart to be followed when UNIT VERIFY ERR. occurs at PLC power-on or during operation.
UNIT. VERIFY ERR. occurs.
Check the slot where error occurred with the GX Developer.
Is the module of the applicable slot installed
Install the module properly.
NO YES
Is the "ERR." LED
Are all the extension cables of the base module connected
Install the extension cable properly.
NO YES
Is the "ERR." LED
Replace the applicable module.
Replace the CPU module.
base unit.
Hardware fault Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

The following shows the flowchart to be followed when CONTROL BUS ERR. occurs at PLC power-on or during operation. This flow chart can be confirmed only when a specific slot/base unit can be detected by the error code.
CONTROL BUS ERR. occurs.
Check the slot base unit where error occurred with the GX Developer.
Is the module of the applicable slot installed properly?
Install the module and cable properly.
Is the extension cable of the
Is the "ERR." LED
Are all the extension cables of the base unit
Install the extension cable properly.
NO YES
Is the "ERR." LED
Replace the applicable module.
Replace the CPU module.
base unit.
Hardware fault Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

If a fault occurs when the PLC power supply is switched on, when the CPU is switched from STOP to RUN or during RUN, the High Performance model QCPU displays an error (on the LED) using the self-diagnostic function and stores the error information into the special relays SM and special registers SD.
For the error code (4000H to 4FFFH) developed upon a request for general data processing from the GX Developer, intelligent function module or network system, refer to Appendix 1. 11.3.1 Procedure for reading error codes
When an error occurs, the error code and error message can be read by the GX Developer Version 4 or later. The procedure for reading error codes by the GX Developer is as follows.
1) Start the GX Developer. 2) Connect the CPU module to the personal computer. 3) Select [Online] - [Read from PLC] Menu by the GX Developer, and also read the project from the High Performance model QCPU. 4) Select the [Diagnostics] - [Diagnostics PLC] Menu. 5) Click the "Error Jump" button in the PLC diagnostics dialog box to display the error code and error message. 6) Select the [Help] - [PLC error] Menu, and confirm the content of the applicable error code. For details of the GX Developer operating method, refer to the applicable the GX Developer Operating Manual.

The following information deals with error codes and the meanings, causes, and corrective measures of error messages. " " in the Corresponding CPU column indicates that the error is applied to all types of CPU modules. "Rem" indicates compatibility with the remote I/O module. A CPU type name in the column indicates that the error is applied only to the specific CPU module type.

1000 Off Flicker/On Stop Always 1001 1002 1003 1004
MAIN CPU DOWN ——— ——— Off Flicker Stop Always
1012 END NOT EXECUTE ——— ——— Off Flicker Stop When an END instruction is executed.
RAM ERROR ——— ——— Off Flicker Stop At power ON/At reset
1300 FUSE BREAK OFF Unit/moule No. ——— Off/ON Flicker/On
1310 I/O INT ERROR Unit/module No. ——— Off Flicker Stop During interrupt
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU MODULE operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

QCPU
Run mode suspended or failure of main CPU module (1) Malfunctioning due to noise or other reason (2) Hardware fault
(1) Measure noise level. (2) Reset and establish the RUN status again.
If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.
Rem 1006 1007 1008
1009 Failure of the power supply module, CPU module, main base unit, extension base unit or extension cable is detected.
Entire program was executed without the execution of an END instruction. (1) When the END instruction is executed it is read as another
(1) Measure noise level. (2) Reset and establish the RUN status again.
If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.
instruction code, e.g. due to noise. (2) The END instruction has been changed to another instruction
code somehow.
1101 Error in internal RAM/program memory where CPU module sequence program is stored. 1102 Error in RAM used as CPU module work area. 1103 Internal CPU module device error. 1104 RAM Address error in CPU module.
This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.
(1) Measure noise level. (2) Reset and establish the RUN status again.
1105 CPU shared memory fault
If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.
Ver. B or later
1200 The circuit that performs CPU internal index modification is not operating properly. 1201 Internal CPU module hardware (logic) does not operate normally. 1202 The circuit that executes sequence processing in the CPU module does not operate properly.
This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.
1203 The operation circuit that conducts index modification in the CPU module is not operating properly. 1204 The hardware (logic) in the CPU us not operating properly. 1205 The operation circuit that conducts sequence processing in the CPU in not operating properly. 1206 The DSP operation circuit in the CPU is not operating properly.
This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. Q4AR
(1) Check ERR. LED of the output modules and replace the module
whose LED is lit. (2) Read the common error information with the peripheral device
and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1".
There is an output module with a blown fuse.
(1) Check ERR. LED of the output modules and replace the fuse of
the module whose LED is lit. (2) Read the common error information with the peripheral device
There is an output module with a blown fuse.
and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1".
(1) Check ERR. LED of the output modules and replace the module
whose LED is lit. (2) Read the common error information with the peripheral device
and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1". (3) Check whether the external power supply for output load is ON
(1) There is an output module with a blown fuse. (2) External power supply for output load is turned off or
disconnected.
or OFF.
One of the individual modules is experiencing hardware problems, so check the modules. Contact your nearest Mitsubishi representative and explain the problem with the defective module.
1310 An interruption has occurred although there is no interrupt module.
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 RUN ERROR
LED Status Error Code
(SD0) 1 Error Messages
1401 SP. UNIT DOWN Unit/module No. ——— Off/On Flicker/On
At power ON/At reset/ When intelligent function module is accessed.
When an intelligent function module access instruction is executed.
3 At power ON/At reset
1402 Program error location
SP. UNIT DOWN Unit/module No.
During execution of FROM/TO instruction set.
When an END instruction is executed.
1411 At power ON/At reset
CONTROL-BUS ERR. Unit/module No. Program error location Off Flicker Stop
During execution of FROM/TO instruction set.
1413 CONTROL-BUS. ERR. ——— ——— off Flicker Stop Always
CONTROL-BUS. ERR. Unit/module No. ——— Off Flicker Stop When an END instruction is executed.
——— off Flicker Stop When an END instruction is executed
1415 Base No. When an END instruction is executed
CONTROL-BUS. ERR.
Unit/module No.
At power ON/At reset
1421 SYS. UNIT DOWN 3 ——— ——— off Flicker Stop Always
1500 AC DOWN ——— ——— On Off Continue Always
1510 DUAL DC DOWN 5V 4 ——— ——— on on Continue Always
1520 DC DOWN 5V 5 ——— ——— off Flicker Stop Always
1530 DC DOWN 24V 3 ——— ——— on on Continue Always
BATTERY ERROR Drive Name ———
BAT.ALM LED On
When an END instruction is executed.
2000 UNIT VERIFY ERR. Unit/module No. ——— Off/On Flicker/On
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.) 3 This can only be detected in redundant systems. Detection is possible in either the control system or the standby system. 4 This can only be detected in the redundant system control system. 5 This can be detected in either a standalone system or a redundant system. However, in a redundant system it can only be detected in the control system. 6 Stop/continue operation is selectable for each module by setting parameters.

The CPU module is experiencing hardware problems. Contact your nearest Mitsubishi representative.
1401 When parameter I/O allocation was being made, there was no return signal from the special function module during initial processing stage. When error is generated, the initial I/O number of the special function module that corresponds to the common information is stored.
The special function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative.
The intelligent function module was accessed in the program, but there was no response.
This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.
1402 The special function module was accessed during the execution of a FROM/TO instruction set, but there was no response. When an error is generated, the program error location corresponding to the individual information is stored.
The special function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative.
The intelligent function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative.
When performing a parameter I/O allocation a special function module could not be accessed during initial communications. On error occurring, the head I/O number of the corresponding special function module is stored in the common information.
A special function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.
The FROM/TO instruction set could not be executed, due to a system bus error with a special function module. On error occurring, the program error location is stored in the individual information.
(1) Change the High Performance model QCPU of function version
A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is
The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.
experiencing problems. Contact your nearest Mitsubishi representative.
Ver. B or later
An error is detected on the system bus. • Wait-length time-out, arbitration time-out.
An intelligent function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.
(1) Change the High Performance model QCPU of function version
Fault of the loaded module was detected. The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.
A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is
Ver. B or later
experiencing problems. Contact your nearest Mitsubishi representative.
An intelligent function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.
An error is detected on the system bus.
1415 Fault of the main or extension base unit was detected.
An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.
Ver. B or later 1421 Hardware fault at the system management module AS92R. This is experiencing hardware problems. Contact your nearest Mitsubishi representative. Q4AR
1416 System bus fault was detected at PLC power-on or CPU module reset.
1500 A momentary power supply interruption has occurred. The power supply went off. Check the power supply. Rem
1510 The 5 VDC supplied to one of the two power-supply modules in the redundant system extension base unit has dropped below 85% of the rated voltage. 1520 The 5 VDC supplied to the power-supply modules in the extension base unit has dropped below 80% of the rated voltage.
Check the supply voltage of the power supply module. If the voltage is abnormal then replace the power supply module.
1530 The 24 VDC power supplied to the system management module AS92R has dropped below 85% of the rated voltage. Check the power supply.
(1) Change the battery. (2) If the battery is for program memory, standard RAM or for the
1600 (1) Voltage in the CPU module battery. (2) The CPU module battery is not connected.
back-up power function, install a lead connector.
1601 Voltage of the battery on memory card 1 has dropped below stipulated level. Change the battery.
1602 Voltage of the battery on memory card 2 has dropped below stipulated level. Change the battery. QnA
Read the error common information at the peripheral device, and check and/or change the module that corresponds to the numerical value (module number) there. Alternatively, monitor the special registers SD1400 to SD1431 at a peripheral device, and change the fuse at the output module whose bit has a value of "1".
I/O module information power ON is changed. I/O module (or special function module) not installed properly or installed on the base unit.
The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.
Change the High Performance model QCPU of function version A for the High Performance model QCPU of function version B.
Ver. B or later
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.


SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
2106 SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 6 This can only be detected in the redundant system standby system.

Slot loaded with the QI60 is set to other than the Inteli (intelligent function module) or Interrupt (interrupt module) in the parameter I/O assignment.
Make setting again to match the parameter I/O assignment with the actual loading status.
Ver. B or later
(1) In the parameter I/O allocation settings, an Inteli (intelligent
function module) was allocated to a location reserved for an I/O module or vice versa. (2) In the parameter I/O allocation settings, a module other than
(1) Reset the parameter I/O allocation setting to conform to the
actual status of the intelligent function module and the CPU module. (2) Delete the general-purpose switch settings.
CPU (or nothing) was allocated to a location reserved for a CPU module or vice versa. (3) A general-purpose switch was set to the module with no
general-purpose switches.
In parameter I/O allocation settings, a special function module was allocated to a location reserved for an I/O module. Or, the opposite has happened.
Reset the parameter I/O allocation setting to conform with the actual status of the special function modules. QnA
Keep the number of A-series special function modules that can initiate an interrupt (except for the QI60, A1SI61) to 12 or fewer. QCPU
13 or more A-series special function modules (except for the QI60, A1SI61) that can initiate an interrupt to the CPU module have been installed.
2101 13 or more special function modules (not counting the AI61) capable of sending an interrupt to the CPU module have been installed.
Keep the number of special function modules that can initiate an interrupt (with the exception of the AI61 module) to 12 or fewer. QnA
7 or more A1SD51S have been installed. Keep the number of A1SD51S to 6 or fewer. QCPU
2102 7 or more computer link modules (excludes A (1S) J71QC24) have been installed.
Keep the number of computer link modules (excludes A (1S) J71QU24) installed to 6 or fewer.
(1) Reduce the number of QI60/A1SI61 modules loaded in the
single-PLC system to one. (2) Change the number of QI60/A1SI61 modules set to the same
(1) Two or more QI60/A1SI61 modules are loaded in a single-PLC
system. (2) Two or more QI60/A1SI61 modules are set to the same control
control PLC to only one in the multiple CPU system. (3) Reduce the number of A1SI61 modules to only one in the
PLC in a multiple CPU system. (3) Two or more A1SI61 modules are loaded in a multiple CPU
Ver. B or later
multiple CPU system. When using an interrupt module with each QCPU in a multiple CPU system, change it for the QI60. (Use one A1SI61 module + max. three QI60 modules or only the QI60 modules.)
system.
Two or more QI60, A1SI61 interrupt modules have been installed. Install only 1 QI60, A(1S)I61 module. QCPU The QI60 is loaded. Remove the QI60. Rem
Two or more AIS61 interrupt modules have been installed. Install only 1 AI61 module. QnA
2104 At the MELSECNET/MINI auto refresh parameter settings, the module allocation that was set is different from the actual module models at the station numbers in the link system.
Reset the parameter MELSECNET/MINI auto refresh unit module allocation setting so that it conforms to the station number of the module that is actually linked.
There are too many special function modules that can use dedicated instructions allocated (number of modules installed). (The total of the figures indicated below is above 1344.) (Number of AD59 modules installed × 5) (Number of AD57 (S1)/AD58 modules installed × 8) (Number of AJ71C24 (S3/S6/S8) modules installed × 10) (Number of AJ71UC24 modules installed × 10) (Number of AJ71C21 (S1) modules installed × 29) (Number of AJ71PT32-S3/AJ71T32-S3 modules installed × 125) (Number of AJ71QC24 (R2, R4) modules installed × 29) (Number of AJ71ID1 (2)-R4 modules installed × 18) (Number of AD75 modules installed × 12) Total > 1344
Reduce the number of special function modules installed.
: When the expansion mode is used. QnA
Reduce the number of modules to four or less in the whole multiple CPU system.
Ver. B or later (1) 5 or more MELSECNET/H modules have been installed. (2) 5 or more Q series Ethernet interface modules have been
(1) Keep the number to 4 or fewer. (2) Keep the number to 4 or fewer. (3) Check the network numbers and station numbers.
installed. (3) Identical network numbers or station numbers exist in the
2106 (1) 5 or more AJ71QLP21 & AJ71QBR11 modules are installed. (2) 3 or more AJ71AP21/R21 & AJ71AT21B modules are installed. (3) The total number of installed AJ71QLP21, AJ71QBR11,
MELSECNET/10 network system.
(1) Install 4 or fewer modules. (2) Install 2 or fewer modules. (3) Reduce the total number of modulees to 4 or less. (4) Check the network Nos. and station Nos. (5) Check the station Nos.
AJ71AP21/R21, and AJ71AT21B modules exceeds 5. (4) Identical network Nos. or identical station Nos. exist at the
MELSECNET/10 network system. (5) 2 or more master or load stations exist simultaneously at the
MELSECNET(II) or MELSECNET/B data link system.
2107 Head X/Y set in the parameter I/O allocation settings is also the head X/Y for another module.
Reset the parameter I/O allocation setting to conform with the actual status of the special function modules.
(1) Network module A1SJ71LP21, A1SJ71BR11, A1SJ71AP21 , A1SJ71AR21, or A1SJ71AT2B dedicated for the A2USCPU has been installed. (2) Network module A1SJ71QLP21 or A1SJ71QBR11 dedicated for
Change network module to QJ71LP21 or QJ71BR11. QCPU
the Q2AS has been installed.
A(1s)J71LP21 or A(1s)J71BR11 for use with the AnUCPU network module has been installed. Change network module to A(1s)J71QLP21 or A(1s)J71QBR11. QnA
2109 6 The control system and standby system module configurations are different when a redundant system is in the backup mode. Check the module configuration of the standby system. Q4AR
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 6 This can only be detected in the redundant system standby system.

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 RUN ERROR
LED Status Error Code
(SD0) 1 Error Messages
SP. UNIT ERROR Unit/module No. Program error location Off/On Flicker/On
2 When instruction executed.
2112 Unit/module No.
Program error location Off/On Flicker/On
When instruction executed/ STOP RUN
SP. UNIT ERROR Unit/module No. Program error location Flicker/On Flicker/On Continue/
Stop When instruction is executed
SP. UNIT LAY ERR. ——— ——— Off Flicker Stop At power ON/At reset
2126 SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
2150 SP. UNIT VER. ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
2200 MISSING PARA. Drive Name ——— Off Flicker Stop At power ON/At reset
2210 BOOT ERROR Drive Name ——— Off Flicker Stop At power ON/At reset
ICM. OPE. ERROR Drive Name ——— Off/On Flicker/On
When memory card is inserted or removed
2400 FILE SET ERROR File name Parameter number Off Flicker Stop At power ON/At reset
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

Station not loaded was specified using the instruction whose target was the PLC share memory.
Read the individual information of the error, check the program corresponding that value (program error location), and make correction.
Ver. B or later 2110 (1) The location designated by the FROM/TO instruction set is not a
(1) Read error individual information, then check and edit the
special function module. (2) The special function module, Network module being accessed is
FROM/TO instruction set that corresponds to the numerical value there (Program error location). (2) The special function module that is being accessed has a
faulty. 2111 The location designated by a link direct device (J \ ) is not a network module.
hardware error. Consult the nearest service center, agent or our branch office and describe the symptom.
(1) The location designated by a special function module dedicated
instruction is not a special function module. (2) The network number specified by the network dedicated
Read error individual information, then check and edit the special function module (Network module) dedicated instruction that corresponds to the numerical value there (program error location).
instruction does not exist, or the network module is not the corresponding one. (3) Alternatively, it is not the relevant special function module.
2113 The one specified in the network-dedicated instruction is not a network module, or a relay target network does not exist.
2114 An instruction, which on execution specifies other stations, has been used for specifying the host station. (An instruction that does not allow the host station to be specified).
2115 An instruction, which on execution specifies the host station, has been used for specifying other stations. (An instruction that does not allow other stations to be specified).
Read the individual information of the error, check the program corresponding that value (program error location), and make correction.
Ver. B or later
2120 The location of Q B and QA1S B is improper. Check the location of the base unit. 2121 The CPU module is installed at other than the CPU slot or slots 0 to 2. Check the loading position of the CPU module and reinstall it at the correct slot. 2122 QA1S B is used to the main base unit. Use Q3 B as the main base unit.
(1) Remove the module installed at 65th or later slot. (2) Remove the module installed at the slot later than the number of
(1) A module is installed at 65th or higher slot. (2) A module is installed at the slot later than the number of slots
specified with base allocation setting. (3) A module is installed at the I/O points later than the 4,096th
slots specified with base allocation setting. (3) Remove the module installed at the I/O points later than the
4,096th point. (4) Change the last module to a module which does not exceed the
point. (4) A module installed at the 4,096th point occupies higher points.
4,096th point.
2125 (1) A module which the QCPU cannot recognise has been installed. (2) There was no response form the intelligent function module.
(1) Install a module which can be used with the CPU. (2) The intelligent function module is experiencing hardware
problems. Contact your nearest Mitsubishi representative.
CPU module locations in a multiple CPU system are either of the following. (1) There are empty slots between the QCPU and QCPU/motion
(1) Eliminate empty slots between the CPU modules. (Set empty
slots on the right side of the CPU modules.) (2) Remove the modules, which are not the QCPU modules, loaded
between the QCPU modules, and fit the slots with the QCPUs. Load the motion controller modules on the right side of the QCPUs.
controller. (2) Modules other than the QCPU (including the motion controller)
modules are loaded between the QCPU modules.
Ver. B or later
(1) Change the intelligent function module for the one compatible
2150 In a multiple CPU system, the control PLC of the intelligent function module incompatible with the multiple CPU system is set to other than station 1.
with the multiple CPU system (function version B). (2) Change the setting of the control CPU of the intelligent function
module incompatible with the multiple CPU system to station 1.
Check and correct the setting of the parameter enabled drive switch. Put a parameter file in the drive designated by the parameter enabled drive switch.
2200 There is no parameter file at the drive designated by DIP switches as a valid drive.
The contents of the boot file are incorrect. Check the boot setting. QCPU
Check and correct the setting of the parameter enabled drive switch. Put a boot file in the drive designated by the parameter enabled drive switch.
2210 There is no boot file in the drive designated by the parameter enabled drive switch even though the Boot DIP switch is ON.
(1) A memory card was removed without switching the memory
card in/out switch OFF. (2) The memory card in/out switch is turned ON although a memory
(1) Remove memory card after placing the memory card in/out
switch OFF. (2) Turn on the card insert switch after inserting a memory card.
card is not actually installed.
2301 (1) The memory card has not been formatted. (2) Memory card format status is incorrect. 2302 A memory card that cannot be used with the CPU module has been installed.
(1) Format memory card. (2) Reformat memory card.
Check memory card.
(1) Execute automatic write to standard ROM on the CPU module
Automatic write to standard ROM was performed on the CPU module that is incompatible with automatic write to standard ROM. (Memory card where automatic write to standard ROM was selected in the boot file was fitted and the parameter enable drive was set to the memory card.)
which is compatible with automatic write to standard ROM. (2) Using GX Developer, perform write of parameters and programs
QCPU function Ver. B or later
to standard ROM. (3) Change the memory card for the one where automatic write to
standard ROM has not been set, and perform boot operation from the memory card.
Read the error individual information at the peripheral device, check to be sure that the parameter drive name and file name correspond to the numerical values there (parameter number), and correct. Create a file created using parameters, and load it to the CPU module.
The file designated at the PLC file settings in the parameters cannot be found.
The Ethernet parameter that was added for QnACPU, with the function version "B," has been set to QnACPU without the function version "B."
Change to QnACPU with the function version "B." Delete the Ethernet parameter. QnA
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 RUN ERROR
LED Status Error Code
(SD0) 1 Error Messages
2401 FILE SET ERROR File name Parameter number Off Flicker Stop At power ON/At reset
FILE OPE. ERROR File name Program error location Off/On Flicker/ON
2 When instruction is executed
CAN'T EXE. PRG. File name ——— Off Flicker Stop At power ON/At reset
PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
PARAMETER ERROR File name/drive name Parameter number Off Flicker Stop When an END instruction is executed.
PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
3004 PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
3006 PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
PARAMETER ERROR File name/drive name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

(1) Check and correct the parameters (boot setting). (2) Delete unnecessary files in the program memory. (3) Choose "Clear program memory" for boot in the parameter so
Program memory capacity was exceeded by performing boot operation or automatic write to standard ROM.
Ver. B or later 2401
that boot is started after the program memory is cleared.
Read the error individual information at the peripheral device, check to be sure that the parameter drive name and file name correspond to the numerical values there (parameter number), and correct. Check the space remaining in the memory card.
The file designated at the parameter PLC RAS settings fault history area has not been created.
Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Create a file created using parameters, and load it to the CPU module. 2411 The sequence program designated a file that cannot be designated by the sequence program (comment file, etc.). 2412 The SFC program file is one that cannot be designated by the sequence program.
2410 The file designated by the sequence program cannot be found.
Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct.
Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Check to ensure that the designated file has not been write protected.
2413 No data has been written to the file designated by the sequence program.
Read the error common information at the peripheral device, check to be sure that the parameter device allocation setting and the program file device allocation correspond to the numerical values there (file name), and correct if necessary. 2501 There are multiple program files although "none" has been set at the parameter program settings.
2500 There is a program file that uses a device that exceeds the device allocation range designated by the parameter device settings.
Edit the parameter program setting to "yes". Alternatively, delete unneeded programs.
2502 The program file is incorrect. Alternatively, the file contents are not those of a sequence program.
Check whether the program version is .QPG, and check the file contents to be sure they are for a sequence program. 2503 2504
There are no program files at all. Two or more SFC normal programs or control programs have been designated.
Check program configuration. Check parameters and program configuration.
In a multiple CPU system, the intelligent function module under control of another station is specified in the interrupt pointer setting of the parameter.
(1) Specify the first I/O number of the intelligent function module
under control of the host station. (2) Delete the interrupt pointer setting of the parameter.
Ver. B or later
3000 The parameter settings for timer time limit setting, the RUN-PAUSE contact, the common pointer number, the general data processing, number of vacant slots, or system interrupt settings are outside the range that can be used by the CPU module. 3001 Parameter contents have been destroyed.
(1) Read the error detailed information at the peripheral device,
check the parameter items corresponding to the numerical values (parameter numbers) there, and correct when necessary. (2) If the error is still generated following the correction of the
parameter settings, it is likely that there is a memory error, either in the internal CPU RAM/program memory or on the memory card. Contact your nearest Mitsubishi representative.
3002 When "use the following files" is selected for the file registers in the PLC file setting parameter, the specified file does not exist though the file register capacity has been set.
The automatic refresh range of the multiple CPU system exceeded the file register capacity.
Change the file register file for the one refresh-enabled in the whole range.
Ver. B or later
(1) Read the error detailed information at the peripheral device,
check the parameter items corresponding to the numerical values (parameter numbers) there, and correct when necessary. (2) If the error is still generated following the correction of the
The number of devices set at the parameter device settings exceeds the possible CPU module range.
parameter settings, it is likely that there is a memory error, either in the internal CPU RAM/program memory or on the memory card. Contact your nearest Mitsubishi representative. 3004 The parameter file is incorrect. Alternatively, the contents of the file are not parameters.
Check whether the parameter file version is .QPA, and check the file contents to be sure they are parameters.
(1) Delete the setting of the Q02CPU’s high speed interrupt
parameter. To use high speed interrupts, change the CPU module to one of the Q02H/Q06H/Q12H/Q25HCPU. (2) To use a multiple CPU system, delete the setting of the high-
(1) The high speed interrupt parameter is set in a Q02CPU. (2) The high speed parameter is set in a multiple CPU system. (3) The high speed interrupt parameter is set when a QA1S B or
speed interrupt parameter. To use high speed interrupts, change the system to a single PLC system. (3) To use either the QA1S B or QA B, delete the setting of the
QA B is used. (4) No module is installed at the I/O address designated by the high
No. 04012 or later
speed interrupt parameter.
high speed interrupt parameter. To use high speed interrupts, do not use the QA1S B/QA B. (4) Re-examine the I/O address designated by the high speed
interrupt parameter.
Re-set the parameter I/O assignment to control them under one QCPU. (Change the parameters of all stations in the multiple CPU system.) 3010 The parameter-set number of CPU modules differs from the actual number in a multiple CPU system.
3009 A modules are set to control PLCs in a multiple CPU system.
Match (preset count of multiple PLC setting) - (CPU (empty) setting in I/O assignment) with the actual number of CPUs loaded. 3012 Multiple CPU setting or control PLC setting differs from that of the reference station in a multiple CPU system.
Match the multiple PLC setting or control CPU setting in the parameter with that of the reference station (station 1).
Multiple CPU automatic refresh setting is any of the followings in a multiple CPU system. (1) When a bit device is specified as a refresh device, a number
Ver. B or later
Check the following in the multiple CPU automatic refresh parameters and make correction. (1) When specifying the bit device, specify a multiple of 16 for the
other than a multiple of 16 is specified for the refresh-starting device. (2) The device specified is other than the one that may be specified. (3) The number of send points is an odd number.
refresh starting device. (2) Specify the device that may be specified for the refresh device. (3) Set the number of send points to an even number.
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 RUN ERROR
LED Status Error Code
(SD0) 1 Error Messages
3100 LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
LINK PARA. ERROR File name/drive name Parameter number Off Flicker Stop When an END instruction is executed.
LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
LINK PARA. ERROR File name/drive name Parameter number Off Flicker Stop When an END instruction is executed.
LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
3107 LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
SFC PARA. ERROR File name Parameter number Off Flicker Stop STOP RUN
3300 SP. PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
Operating Statuses of · Diagnostic Timing · 3200 3201

(1) Delete the MELSECNET/H network parameter of the
In a multiple CPU system, the MELSECNET/H under control of another station is specified as the first I/O number in the network setting parameter of the MELSECNET/H.
MELSECNET/H under control of another station. (2) Change the setting to the first I/O number of the MELSECNET/H
under control of the host station. The network parameters of the MELSECNET/H operating in the ordinary station were rewritten to the control station, or the network parameters of the MELSECNET/H operating in the control station were rewritten to the ordinary station. (The network parameters are reflected on the module side by making a reset.)
Ver. B or later
Reset the CPU module.
(1) The number of actually installed modules is different from that
(1) Check the network parameters and the installation state. If
designated in the number of modules setting parameter of MELSECNET/H. (2) The head I/O number of actually installed modules is different
inconsistency is found, arrange consistency between network parameters and the installation state. If network parameters are changed, write the new network parameters to the CPU module. (2) Check the number of extension stages of the extension base unit. (3) Check the state of connection of the extension base unit and
from that designated in the network parameter of MELSECNET/H. (3) Some data in the parameter cannot be handled. (4) The station type of MELSECNET/H has been changed while the
connector. If the display unit is connected to the main base unit or extension base unit, check the state of connection. (4) If the error persists after the above items (1) through (3) are
power is on. (RESET RUN is required to change the station type.)
checked, the hardware is faulty. Contact your nearest Mitsubishi representative and explain the symptom.
(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact
Network parameters have not been written although the QnACPU is the control station, or the master station.
your nearest Mitsubishi representative.
Correct the type or station number of the MELSECNET/H module in the parameter to meet the used system.
Ver. B or later
(1) Check the network parameters and the installation state. If
inconsistency is found, arrange consistency between network parameters and the installation state. If network parameters are changed, write the new network parameters to the CPU module. (2) Check the number of extension stages of the extension base unit. (3) Check the state of connection of the extension base unit and
3101 The network No. specified by a parameter is different from that of the actually mounted network. The head I/O No. specified by a parameter is different from that of the actually mounted I/O unit. The network class specified by a parameter is different from that of the actually mounted network. The network refresh parameter of the MELSECNET/10(H) is out of the specified area.
connector. If the display unit is connected to the main base unit or extension base unit, check the state of connection. (4) If the error persists after the above items (1) through (3) are
checked, the hardware is faulty. Contact your nearest Mitsubishi representative and explain the symptom.
3102 An error was discovered when the network parameter check was made at the network module.
(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact
your nearest Mitsubishi representative.
In a multiple CPU system, the Q series Ethernet interface module under control of another station is specified as the first I/O number of the Ethernet setting parameter.
(1) Delete the Ethernet setting parameter of the Q series Ethernet
interface module under control of another station. (2) Change the setting to the first I/O number of the Q series
Ver. B or later
Ethernet interface module under control of the host station.
(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact
your nearest Mitsubishi representative.
AJ71QE71 does not exist in the position of I/O number set by the parameter. I/O number designation is overlapping. Numbers of the parameter and loaded AJ71QE71 are different. Ethernet (parameter + dedicated instruction) is set to more than 5.
(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact
your nearest Mitsubishi representative.
3104 Ethernet and MELSECNET/10 use the same network number. Network number, station number or group number set by the parameter is out of range. I/O number is out of range.
(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact
your nearest Mitsubishi representative.
(1) Delete the CC-Link setting parameter of the Q series CC-Link
In a multiple CPU system, the Q series CC-Link module under control of another station is specified as the first I/O number of the CC-Link setting parameter.
module under control of another station. (2) Change the setting to the first I/O number of the Q series CC-
Ver. B or later (1) Though the number of CC-Link module set in the network
Link module under control of the host station.
parameters is one or more, the actually mounted number of units is zero. (2) The head I/O number in the common parameters is different
(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact
from that of the actually mounted module. (3) The station class for the CC-Link module quantity set
your nearest Mitsubishi representative.
parameters is different from that of the actually mounted station.
The contents of the Ethernet parameter are incorrect. Write after correcting parameters. QnA
The CC-Link link refresh range exceeded the file register capacity. Change the file register file for the one refresh-enabled in the whole range.
Ver. B or later 3106
The network refresh parameter for CC-Link is out of range. Check the parameter setting. QCPU
3107 The contents of the CC-Link parameter are incorrect. Check the parameter setting. Rem 3200 The parameter contents are incorrect. 3201 The contents of the SFC block attribute information are incorrect. 3202 The number of step relays designated in the parameters is less than the number used by the program. 3203 The execution type set for an SFC program in the parameters is other than the scan execution type.
Write after correcting parameters.
3300 The first I/O number in the intelligent function module parameter set on GX Configurator differs from the actual I/O number. Check the parameter setting. QCPU
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 RUN ERROR
LED Status Error Code
(SD0) 1 Error Messages
When an END instruction is executed.
SP. PARA. ERROR File name Parameter number Off Flicker Stop
3303 SP. PARA. ERROR File name/drive name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN
REMOTE PASS. ERROR ——— ——— Off Flicker Stop At power ON/Reset/ STOP RUN
INSTRCT CODE ERR. Program error location ——— Off Flicker Stop At power ON/Reset/ STOP RUN
4010 MISSING END INS. Program error location ——— Off Flicker Stop
4021 CAN'T SET (P) Program error location ——— Off Flicker Stop
At power ON/Reset/ STOP RUN
4030 CAN'T SET (I) Program error location ——— Off Flicker Stop
4101 Program error location ———
Program Program error location
Program error location ———
When instruction is executed
Program Program error location
Program error location ———
4200 FOR NEXT ERROR Program error location ——— Off Flicker Stop When instruction is executed 4201 FOR NEXT ERROR Program error location ——— Off Flicker Stop When instruction is executed
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

The refresh setting of the intelligent function module exceeded the file register capacity.
Change the file register file for the one which allows refresh in the whole range.
Ver. B or later
The intelligent function module's refresh parameter setting is outside the available range. Check the parameter setting. QCPU
Rem 3302 The intelligent function module's refresh parameter are abnormal. Check the parameter setting. QCPU
(1) Delete the automatic refresh setting or similar parameter setting
of the intelligent function module under control of another station. (2) Change the setting to the automatic refresh setting or similar
3303 In a multiple CPU system, automatic refresh setting or similar parameter setting was made to the intelligent function module under control of another station.
parameter setting of the intelligent function module under control of the host station. 3400 The first I/O number of the target module in the remote password file is set to other than 0H to 0FF0H.
Ver. B or later
Load the QJ71C24(-R2) or Q series Ethernet interface module of function version B in the position specified as the first I/O number of the remote password file.
(1) Change the setting to the QJ71C24(-R2) or Q series Ethernet
QJ71C24(-R2) or Q series Ethernet interface module of function version B under control of another station is specified in a multiple CPU system.
interface module of function version B under control of the host station. (2) Delete the remote password setting.
4000 The program contains an instruction code that cannot be decoded. An unusable instruction is included in the program.
4001 The program contains a dedicated instruction for SFC program although it is not an SFC program.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4002 The extension instruction designated by the program has an incorrect instruction name. 4003 The extension instruction designated by the program has an incorrect number of devices.
4004 The extension instruction designated by the program a device which cannot be used.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4010 There is no END (FEND) instruction in the program. 4020 The total number of internal file pointers used by the program exceeds the number of internal file pointers set in the parameters. 4021 The common pointer numbers used by individual files overlap.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4030 The allocation pointer numbers used by individual files are overlap.
4100 The instruction cannot process the contained data.
The designated device number for data processed by the instruction exceeds the usable range. Alternatively, the stored data or constants for the devices designated by the instruction exceeds the usable range.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
(1) Delete from the program the link direct device which specifies
In a multiple CPU system, the link direct device (J \G ) was specified for the network module under control of another station.
the network module under control of another station. (2) Using the link direct device, specify the network module under
Ver. B or later
control of the host station.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4103 The configuration of the PID dedicated instruction is incorrect.
Using the multiple CPU dedicated instruction completion bit, provide interlocks to prevent one CPU module from executing 32 or more multiple CPU dedicated instructions.
33 or more multiple CPU dedicated instructions were executed from one CPU module.
Ver. B or later
Numbers of execution to the CC-Link instruction are beyond 64. Set the numbers of execution to the CC-Link instruction to 64 or less. 4108 The CC-Link parameter is not set when the CC-Link instruction is executed.
Execute the CC-Link instruction after setting the CC-Link parameter.
4109 With high speed interrupt setting execute PR/PRC,UDCNT1/2,PWM,SPD,PLOADP,PUNLOADP,PAWPP instruction.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
No. 04012 or later No NEXT instruction was executed following the execution of a FOR instruction.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4200 Alternatively, there are fewer NEXT instructions than FOR instructions.
A NEXT instruction was executed although no FOR instruction has been executed.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4201 Alternatively, there are more NEXT instructions than FOR instructions.
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 RUN ERROR
LED Status Error Code
(SD0) 1 Error Messages
4203 FOR NEXT ERROR Program error location ——— Off Flicker Stop When instruction is executed
CAN'T EXECUTE (P) Program error location ——— Off Flicker Stop When instruction is executed
CAN'T EXECUTE (I) Program error location ——— Off Flicker Stop When instruction is executed
4235 INST. FORMAT ERR. Program error location ——— Off Flicker Stop When instruction is executed
4300 4301 EXTEND INST. ERR. Program error location ——— Off/On Flicker/On
2 When instruction is executed
4400 SFCP. CODE ERROR Program error location ——— Off Flicker Stop STOP RUN
4410 4411 CAN'T SET (BL) Program error location ——— Off Flicker Stop STOP RUN
4422 CAN'T SET (S) Program error location ——— Off Flicker Stop STOP RUN
SFCP. FORMAT ERR. Program error location ——— Off Flicker Stop STOP RUN
4602 SFCP. OPE. ERROR Program error location ——— Off/On Flicker/On
2 When instruction is executed
4611 SFCP. EXE. ERROR Program error location ——— On On Continue STOP RUN
4621 BLOCK EXE. ERROR Program error location ——— Off Flicker Stop When instruction is executed
STEP EXE. ERROR Program error location ——— Off Flicker Stop When instruction is executed
WDT ERROR Time (value set) Time (value actually
measured) Off Flicker Stop Always
PRG. TIME OVER Time (value set) Time (value actually
measured) On On Continue Always
6000 PRG. VERIFY ERR. 5 File name ——— off Flicker Stop Always
6010 MODE VERIFY ERR. 5 ——— ——— on on Continue Always
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.) 5 Can only be detected in the standby system of a redundant system.

CPU 4202 More than 16 nesting levels are programmed. Keep nesting levels at 16 or under.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4203 A BREAK instruction was executed although no FOR instruction has been executed prior to that.
4210 The CALL instruction is executed, but there is no subroutine at the specified pointer. 4211 There was no RET instruction in the executed sub-routine program. 4212 The RET instruction was before the FEND instruction in the main program.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4213 More than 16 nesting levels are programmed. Keep nesting levels at 16 or under.
4220 Interrupt input was generated, but no corresponding interrupt pointer was found. 4221 There was no IRET instruction in the executed interrupt program. 4223 The IRET instruction was before the FEND instruction in the main program. 4230 The number of CHK and CHKEND instructions is not equal. 4231 The number of IX and IXEND instructions is not equal.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
The configuration of the check conditions for the CHK instruction is incorrect. Alternatively, a CHK instruction has been used in a low speed execution type program.
4300 The designation of a MELSECNET/MINI-S3 master module control instruction was wrong. 4301 The designation of an AD57/AD58 control instruction was wrong.
Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4400 No SFCP or SFCPEND instruction in SFC program. 4410 The block number designated by the SFC program exceeds the range. 4411 Block number designations overlap in SFC program. 4420 A step number designated in an SFC program exceeds 511.
Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4421 Total number of steps in all SFC programs exceed the range Reduce total number of steps to below the maximum.
Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4422 Step number designations overlap in SFC program.
4500 The numbers of BLOCK and BEND instructions in an SFC program are not equal.
4501 The configuration of the STEP to TRAN to TSET to SEND instructions in the SFC program is incorrect. 4502 There was no STEPI instruction in SFC program block.
Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4503 The step designated by the TSET instruction in the SFC program does not exist.
4504 The step designated by the TAND instruction in the SFC program does not exist.
4600 The SFC program contains data that cannot be processed. 4601 Exceeds device range that can be designated by the SFC program. 4602 The START instruction in an SFC program is proceeded by an END instruction.
Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. The program is automatically subjected to an initial start. 4610 The active step information at presumptive start of an SFC program is incorrect. 4611 Key-switch was reset during RUN when presumptive start was designated for SFC program. 4620 Startup was executed at a block in the SFC program that was already started up. 4621 Startup was attempted at a block that does not exist in the SFC program.
Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.
4630 Startup was executed at a block in the SFC program that was already started up. 4631 Startup was attempted at a block that does not exist in an SFC program. 4632 There were too many simultaneous active steps in blocks that can be designated by the SFC program. 4633 There were too many simultaneous active steps in all blocks that can be designated.
5000 Program scan time for initial execution type programs exceeds the initial execution WDT time setting designated in the PLC RAS parameter. 5001 The program scan time goes over the WDT value set in the parameter PLC RAS parameter.
Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary.
(1) The scan time of the program exceeded the constant scan
(1) Review the constant scan setting time. (2) Review the constant scan time and low speed program
setting time specified in the PC RAS setting parameter. (2) The low speed program execution time specified in the PC RAS
execution time in the parameter so that the margin time of constant scan may be fully reserved.
setting parameter exceeded the margin time of constant scan.
5011 Low speed scan type program scan time goes over the low speed execution WDT set in the parameter PC RAS settings.
Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary.
6000 The control system and standby system in the redundant system do not have the same programs and parameters.
Synchronise the programs and parameters of the control system and standby system. 6010 The operational status of the control system and standby system in the redundant system is not the same.
Synchronise the operation statuses of the control system and standby system.
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
Corres- ponding · Error Code · QnA

Common Information (SD5 to 15) 1
Individual Information (SD16 to 26) 1 LED Status
(SD0) 1 Error Messages
6100 At power on/ Reset/STOP RUN
TRK. MEMORY ERR. 3 ——— ——— on on Continue
When END instruction executed
6200 CONTROL EXE. 4 Cause of switch ——— on off Continue Always
6210 CONTROL WAIT. 5 Cause of switch ——— on off Continue Always
4 Cause of switch ——— on on Continue Always
MULT CPU DOWN Unit/module No. ——— Off Flicker Stop
7010 MULTI EXE. ERROR Unit/module No. ——— Off Flicker Stop At power ON/Reset
On Off 9000 F∗∗∗∗ 6 Program error location Annunciator number
7020 MULTI CPU ERROR Unit/module No. ——— On On Continue Always
Continue When instruction is executed
On Off 9010 ERR ∗∗∗-∗∗∗ 7 Program error location Failure No.
Continue When instruction is executed
9020 BOOT OK ——— ——— Off Flicker Stop At power ON/Reset
10000 CONT. UNIT ERROR ———
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 3 Can only be detected in a redundant system. Can be detected either in the control system or the standby system. 4 Can only be detected in the control system of a redundant system. 5 Can only be detected in the standby system of a redundant system. 6 ∗∗∗∗ indicates detected annunciator number. 7 ∗∗∗ indicates detected contact and coil number.

Because this is a CPU module hardware error, contact your nearest Mitsubishi representative. To replace the module, replace the standby system CPU first, then the control system CPU. 6101 The CPU module detected an error during the handshake for tracking. Check the condition of the other stations.
6100 A CPU module tracking memory error was detected during initial.
6200 The standby system in a redundant system is switched to the control system. Check the control system condition.
6210 The control system in a redundant system is switched to the standby system. Check the control system condition.
6220 The standby system in a redundant system could not be switched from the control system to the standby system because of an error status or other reason.
Check the standby system condition.
6221 Switching is disabled because of a bus switching module error. Because this is a bus switching module hardware error, contact your nearest Mitsubishi representative. 6222 Switching is disabled because a multiplexed master station of a remote I/O network was installed in the standby station during initial. Check the remote I/O network setting.
(1) In a multiple CPU system, at CPU module fault occurred at a
(1) Read the error individual information at a peripheral device,
station where "all station stop by stop error of PLC " was selected in the operating mode. (2) High Performance model QCPU of function version A was
check the error of the PLC resulting in CPU module fault, and remove the error. (2) Remove the High Performance model QCPU of function version
A from the main base unit.
loaded in a multiple CPU system.
Read the error individual information at a peripheral device, check the error of the CPU module resulting in CPU module fault, and remove the error.
In a multiple CPU system, station 1 resulted in stop error at power- on and the other stations cannot start. (This error occurred at stations 2 to 4)
(1) There is no response from the target station in a multiple CPU
(1) Reset the High Performance model QCPU and run it again. If
Ver. B or later
the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative. (2) Remove the High Performance model QCPU of function version
system at initial communication stage. (2) High Performance model QCPU of function version A was
A from the main base unit.
loaded in a multiple CPU system configuration.
7003 There is no response from the target station in a multiple CPU system at initial communication stage.
Reset the High Performance model QCPU and run it again. If the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative.
(1) Faulty CPU is loaded in a multiple CPU system. (2) High Performance model QCPU of function version A is loaded
(1) Read the error individual information at a peripheral device, and
in a multiple CPU system configuration. (An error is detected at the High Performance model QCPU of function version B.) (3) In a multiple CPU system, any of stations 2 to 4 was reset during
change the faulty station. (2) Change the station of function version A for function version B. (3) Do not reset the CPU modules of PLC No.2 to 4. Reset the High
Performance model QCPU of PLC No.1 and restart the multiple CPU system.
power-on. (This error occurs at only the station which was reset.)
Ver. B or later
In a multiple CPU system, a PLC fault occurred at a station where "all station stop by stop error of PLC" was not selected in the operation mode. (The error is detected at the High Performance model QCPU of other than the station where the CPU module fault occurred.)
Read the error individual information at a peripheral device, check the error of the CPU module resulting in CPU module fault, and remove the error.
Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (annunciator number).
9000 Annunciator F was set ON
Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (error number) there.
9010 Error detected by the CHK instruction.
9020 Storage of data onto ROM was completed normally in automatic write to standard ROM. (BOOT LED also flickers.)
Set the parameter enable drive to standard ROM, switch power on again, and perform boot operation from standard ROM.
Ver. B or later
10000 In the multiple CPU system, an error occurred in the CPU module other than the Process CPU/High Performance model QCPU.
Use the software package of the corresponding CPU module to check the details of the error that occurred.
Ver. B or later
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

The High Performance model QCPU can perform the cancel operation for errors only when the errors allow the CPU module to continue its operation. To cancel the errors, follow the steps shown below. 1) Eliminate the cause of the error. 2) Store the error code to be canceled in the special register SD50. 3) Energize the special relay SM50 (OFF ON). 4) The error to be canceled is canceled. After the CPU module is reset by the canceling of the error, the special relays, special registers, and LEDs associated with the error are returned to the status under which the error occurred. If the same error occurs again after the cancellation of the error, it will be registered again in the error history. When multiple enunciators(F) detected are canceled, the first one with No. F only is canceled.
POINT (1) When the error is canceled with the error code to be canceled stored in the
SD50, the lower one digit of the code is neglected. (Example) If error codes 2100 and 2101 occur, and error code 2100 to cancel error code 2101. If error codes 2100 and 2111 occur, error code 2111 is not canceled even if error code 2100 is canceled.
(2) Errors developed due to trouble in other than the CPU module are not canceled
even if the special relay (SM50) and special register (SD50) are used to cancel the error. (Example) The cause of "SP. UNIT DOWN" error cannot be removed even by using the special relay (SM50) and special register (SD50), because the error is developed on the Q bus. Refer to the error code list in Section 11.3.2 to remove the cause of the error.

This chapter explains possible problems with I/O circuits and their corrective actions. 11.5.1 Input circuit troubleshooting
This section describes possible problems with input circuits and their corrective actions.
Condition Cause Corrective Action
Input signal does not turn OFF.
Leakage current Input module
It is recommended to use 0.1 to 47 F + 47 to 120 (1/2W) for the CR constant.
Input signal does not turn OFF.
Input signal does not turn OFF.
DC input (plus common)
DC input (plus common)
Input signal does not turn OFF.
connected resistor is given on the following page.


Change response time setting. Example : 1ms 5ms (Setting of a shorter response time may produce a higher effect on periodic excessive noise.)If no effects are produced by the above, take basic actions to prevent excessive noise form entering, e.g. avoid bundling the power and I/O cables, and suppress noise by adding surge absorbers to such noise sources as relays and conductors used with the same power supply.)
Depending on response time setting, noise is imported as input.


If a switch with an LED display is connected to QX40 and current of 2.33 mA is leaked. 4.7k
Voltage VTB across the terminal and common base is: VTB = 2.33[mA] 5.6[k ] = 13[V] (Ignore the voltage drop caused by the LED.) Because the condition for the OFF voltage ( 11 [V]) is not satisfied, the input does not turn off. To correct this, connect a resistor as shown below.

The voltage of QX40 across the terminals must be reduced to 11 [V] or less. The required current
(24-11[V]) ÷ 4.7[k ] = 2.77[mA] Therefore resistor R of flowing current I of 2.77 [mA] or more must be connected.
11[V] R > 2.77[mA] - 5.6[k ] 11[V] 11[V] ÷ R > 2.77-1.96[mA] 11[V] ÷ 0.81[mA] > R 13.6[k ] > R Resistance of the connected resistor R is obtained in the above equations.
Suppose that the resistance R is 12 [kW]. The power capacity W of the resistor during activation of the switch is: W = (Applied voltage)2 / R W = (28.8[V])2/12[k ]=0.069[W]
Because the resistance is selected so that the power capacity is three to five times
the actual power consumption, a third to a half [W] should be selected. In this case, a resistor of 12 [k ] and a third to a half [W] should be connected across the terminal and COM.

This section explains trouble examples and troubleshooting methods in the output circuit.
Condition Cause Corrective Action
D1
Excessive voltage is applied to load when output turns off.
Example 2
Load does not turn off. (Triac output)
11 - 41 11 - 41

Special relays, SM, are internal relays whose applications are fixed in the PLC. For this reason, they cannot be used by sequence programs in the same way as the normal internal relays. However, they can be turned ON or OFF as needed in order to control the CPU module and remote I/O modules. The headings in the table that follows have the following meanings.
S : Set by system U : Set by user (in sequence program or test operation at a GX Developer) S/U : Set by both system and user
Indicated only if setting is done by system. Each END : Set during each END processing Initial : Set only during initial processing
Set by (When set)
(when power supply is turned ON, or when going from STOP to RUN) Status change : Set only when there is a change in status Error : Set when error is generated Instruction execution : Set when instruction is executed Request : Set only when there is a user request
(through SM, etc.)

POINT (1) SM1200 to SM1255 are used for QnACPU.
These relays are vacant with QCPU. (2) Special relays SM1500 and later are dedicated for Q4ARCPU.
Corresponding ACPU M9 · Corresponding CPU

(1) Diagnostic Information
Number Name Meaning Explanation Set by (When Set)
SM5 Error common information
SM16 Error individual information
QCPU SM53 AC/DC DOWN detection
detected • Comes ON if a momentary power interruption of less than 1ms occurred during use of the DC power supply module, and reset by turning power OFF, then ON.
S (Error) M9004 QnA
SM60 Blown fuse detection
SM61 I/O module verification error
OFF : Not detected ON : Detected • Goes ON if even one annunciator F goes ON. S (Instruction
SM90 Corresponds to SD90 M9108 SM91 Corresponds to SD91 M9109 SM92 Corresponds to SD92 M9110 SM93 Corresponds to SD93 M9111 SM94 Corresponds to SD94 M9112 SM95 Corresponds to SD95 M9113 SM96 Corresponds to SD96 M9114 SM97 Corresponds to SD97 New SM98 Corresponds to SD98 New SM99
Startup of watchdog timer for step transition (Enabled only when SFC program exists)
11 - 43 11 - 43

(2) System information
Number Name Meaning Explanation Set by (When Set)
SM202 LED OFF
command OFF ON : LED OFF • When this relay goes from OFF to ON, the LEDs corresponding to the individual bits at SD202 go off U New
SM203 STOP contact STOP status • Goes ON at STOP status S (Status
SM204 PAUSE contact PAUSE status • Goes ON at PAUSE status S (Status
contact STEP-RUN status • Goes ON at STEP-RUN status S (Status
SM210 Clock data set
SM213 Clock data read
SM240 No. 1 CPU reset
SM241 No. 2 CPU reset
SM242 No. 3 CPU reset
SM243 No. 4 CPU reset
Ver. B
SM244 No. 1 CPU error
SM245 No. 2 CPU error
SM246 No. 3 CPU error
SM247 No. 4 CPU error

Number Name Meaning Explanation Set by (When Set)
SM250 Max. loaded I/O
U (END) M9094
Q3A Q4A Q4AR
SM252 I/O change OK OFF : Replacement prohibited ON : Replacement enabled • Goes ON when I/O replacement is OK. S (END) New
MELSECNET/10 module 1 information
MELSECNET/10 module 2 information
MELSECNET/10 module 3 information
MELSECNET/10 module 4 information
change) New QCPU Remote SM280 CC-Link error OFF : Normal ON : Error • Goes ON when a CC-Link error is detected in any of the installed A(1S)J61QBT11. Stays ON even after normal operation is restored.
S (Error) New QnA
Presence/absenc e of SFC program
11 - 45 11 - 45

Number Name Meaning Explanation Set by (When Set)
Presence/absenc e of continuous transition for entire block
Continuous transition prevention flag
SM325 Output mode at
Selects the device status when the stopped CPU is run after the sequence program or SFC program has been modified when the SFC program exists.
SM326 SFC device clear
Output during end step execution
Operation mode for low speed execution type program
Low speed execution type program ON for 1 scan only after RUN U (END) New
When ON, access to the intelligent function module is completed

(3) System clocks/counters
Number Name Meaning Explanation Set by (When Set)
SM400 Always ON ON OFF
SM401 Always OFF ON OFF
S (Every END processing)
SM402 ON for 1 scan
M9038
SM403 After RUN, OFF
ON OFF 1 scan
S (Every END processing)
for 1 scan only
Low speed execution type program ON for 1 scan only after RUN
ON OFF 1 scan
S (Every END processing)
Low speed execution type program After RUN, OFF for 1 scan only
ON OFF 1 scan
S (Every END processing)
SM409 0.01 second
0.005 sec. 0.005 sec.
SM410 0.1 second clock 0.05 sec. 0.05 sec. M9030
SM411 0.2 second clock 0.1sec. 0.1sec. M9031
SM412 1 second clock 0.5 sec. 0.5 sec. M9032
SM413 2 second clock 1 sec. 1 sec.
SM414 2n second clock n sec. n sec.
SM415 2n (ms) clock n(ms) n(ms)
SM420 User timing clock
No.0 M9020
SM421 User timing clock
No.1 M9021
S (Every END processing)
SM422 User timing clock
No.2 M9022
SM423 User timing clock
No.3 M9023
SM424 User timing clock
n2 scan n2 scan
No.4
SM430 User timing clock
No.5
SM431 User timing clock
No.6
SM432 User timing clock
No.7
SM433 User timing clock
No.8
SM434 User timing clock
No.9

(4) Scan information

Number Name Meaning Explanation Set by (When Set)
OFF : Unusable ON : Use enabled • ON when memory card is ready for use by user S (Initial) New
OFF : No protect ON : Protect • Goes ON when memory card protect switch is ON S (Initial) New
SM602 Drive 1 flag OFF : No drive 1 ON : Drive 1 present • Goes ON when loaded memory card is RAM. S (Initial) New
SM603 Drive 2 flag OFF : No drive 2 ON : Drive 2 present • Goes ON when loaded memory card is ROM. S (Initial) New
OFF : Not used ON : In use • Goes ON when memory card is in use S (Initial) New
Memory card remove/insert prohibit flag
Memory card remove/insert enable flag
SM620 Memory card B
OFF : Unusable ON : Use enabled • ON when memory card B is ready for use by user S (Initial) New
Q3A Q4A Q4AR • Always ON S (Initial) New QCPU
SM621 Memory card B
OFF : No protect ON : Protect • Goes ON when memory card B protect switch is ON S (Initial) New
Q3A Q4A Q4AR • Always ON S (Initial) New QCPU
SM622 Drive 3 flag OFF : No drive 3 ON : Drive 3 present • Goes ON when drive 3 (card 2 RAM area) is present S (Initial) New
SM624 Memory card B
OFF : Not used ON : In use • Goes ON when memory card B is in use S (Initial) New
Q3A Q4A Q4AR
Memory card B remove/insert prohibit flag
SM640 File register use OFF : File register not used ON : File register in use • Goes ON when file register is in use S (Status
SM650 Comment use OFF : File register not used ON : File register in use • Goes ON when comment file is in use S (Status
Memory card A file register access range flag
11 - 48 11 - 48


Number Name Meaning Explanation Set by (When Set)
SM700 Carry flag OFF : Carry OFF ON : Carry ON • Carry flag used in application instruction S (Instruction
Number of output characters selection
Selection of real number instruction processing type
CHK instruction priority ranking flag
M9065
M9066
request to remote terminal module enabled ON : Communication
Communication request registration area BUSY signal
M9081
request to remote terminal module disabled
SM715 EI flag OFF : During DI ON : During EI • ON when EI instruction is being executed. S (Instruction
BIN/DBIN instruction error disabling flag
communication with intelligent device station enabled ON : Request for
BUSY signal for CC-Link communication request registration area
communication with intelligent device station disabled

Number Name Meaning Explanation Set by (When Set)
PKEY instruction execution in progress flag
Keyboard input reception flag for PKEY instruction
Selection of link refresh processing during COM instruction execution
Enable/disable local device at CALL
Enable/disable local device in interrupt program
CC-Link dedicated instruction executable
(7) Debug
Number Name Meaning Explanation Set by (When Set)
ACPU M9
Trace preparation • Switches ON when the trace preparation is completed. S (Status
change) New QCPU SM800 Sampling trace
OFF : Not ready ON : Ready • Goes ON when sampling trace is ready S (Status
Trace execution in progress • Switches ON during execution of trace. S (Status
Trace trigger • Trace is triggered when this relay switches from OFF to ON. (Identical to TRACE instruction execution status) U M9044 QCPU
OFF ON: Start • Sampling trace trigger goes ON when this goes from OFF to ON (Identical to STRA instruction execution status)
After trace trigger • Switches ON after trace is triggered. S (Status
change) New QCPU SM804 After sampling
OFF : Not after trigger ON : After trigger • Goes ON after sampling trace trigger S (Status
change) 9043 QCPU SM805 Sampling trace
Trace completed • Switches ON at completion of trace. S (Status
OFF : Not completed ON : End • Goes ON at completion of sampling trace S (Status

Number Name Meaning Explanation Set by (When Set)
OFF : Not ready ON : Ready • Goes ON when status latch is ready S (Status
OFF : Latch not completed ON : Latch completed • Comes ON when status latch is completed. S (Status
SM809 Status latch clear OFF ON: Clear • Enable next status latch U New
OFF : Not ready ON : Ready • Goes ON when program trace is ready S (Status
Program trace execution under way
trigger OFF ON: Start • Program trace trigger goes ON when this goes from OFF to ON (Identical to PTRA instruction execution status)
OFF : Not after trigger ON : After trigger • Goes ON after program trace trigger S (Status
OFF : Not completed ON : End • Goes ON at completion of program trace S (Status
OFF : Not ready ON : Ready • Goes ON after program trace registration, at ready. U New
Step trace execution underway
SM823 After step trace
SM824 After Step trace
change) New QCPU SM826 Sampling trace
Trace error • Switches ON if error occurs during execution of trace. S (Status
OFF : Normal ON : Errors • Goes ON if error occurs during execution of sampling trace.


Special relays SM1000 to SM1255 are the relays which correspond to ACPU special relays M9000 to M9255 after A to Q/QnA conversion. All of these special relays are controlled by the system so that users cannot turn them ON/OFF in the program. If users want to turn these relays ON/OFF, the program should be modified to use QCPU/QnACPU special relays. For SM1084 and SM1200 through SM1255, however, if a user can turn ON/OFF some of special relays M9084 and M9200 through M9255 before conversion, the user can also turn ON/OFF the corresponding relays among SM1084 and SM1200 through SM1255 after the conversion. For details on the ACPU special relays, see the user's manuals for the individual CPUs, and MELSECNET or MELSECNET/B Data Link System Reference Manuals.

POINT The processing time may be longer when converted special relays are used with QCPU. Uncheck "A-series CPU compatibility setting" within the PC system setting in GX Developer PC parameters when converted special relays are not used.
The following are additional explanations about the Special Relay for Modification column.
1 When a special relay for modification is provided, the device number should be changed to the provided QCPU/QnACPU special relay.
2 When is provided, the converted special relay can be used for the device number.
3 When is provided, the device number does not work with QCPU/QnACPU.
Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
I/O module verification error
M9004 SM1004 NIMI link error OFF : Normal ON : Error
ACPU Special · QnA · AC DOWN detection

Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
M9007 SM1007 Battery low latch OFF : Normal ON : Battery low
M9008 SM1008 SM1 Self-diagnosis error
M9009 SM1009 SM62 Annunciator detection
M9011 SM1011 SM56 Operation error flag
M9012 SM1012 SM700 Carry flag OFF : Carry OFF ON : Carry ON • Carry flag used in application instruction.
M9016 SM1016 Data memory clear flag
M9017 SM1017 Data memory clear flag
User timing clock No.0
User timing clock No.1
User timing clock No.2
M9023 SM1023
User timing clock No.3
DUTY n1 n2 M9020
User timing clock No.4
Clock data set request
M9026 SM1026 Clock data error OFF : No error ON : Error • Switched on by clock data (SD1025 to SD1028) error
Clock data read request
Batch processing of data communications requests
0.05 seconds 0.05 seconds
M9030 SM1030 0.1 second clock
0.1 seconds 0.1 seconds
M9031 SM1031 0.2 second clock
0.5 seconds 0.5 seconds
M9032 SM1032 1 second clock
1 seconds 1 seconds
M9033 SM1033 2 second clock
2n minute clock (1 minute clock)
n seconds n seconds
: 1 minute clock indicates the name of the special relay (M9034) of the ACPU.

Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
M9036 SM1036 Always ON
M9037 SM1037 Always OFF
ON for 1 scan only after RUN
ON OFF 1 scan
RUN flag(After RUN, OFF for 1 scan only)
ON OFF 1 scan
M9040 SM1040 SM206 PAUSE enable coil
M9041 SM1041 SM204 USE status contact
M9042 SM1042 SM203 STOP status contact
M9043 SM1043 SM805 Sampling trace completed
Same as execution ON OFF STRAR
M9044 SM1044 SM803 Sampling trace
The value stored in SD1044 is used as the condition for the sampling trace. At scanning, at time → Time (10 ms unit)
M9045 SM1045 Watchdog timer (WDT) reset
M9046 SM1046 SM802 Sampling trace OFF : Trace not in progress ON : Trace in progress • Switched on during sampling trace.
M9047 SM1047 SM801 Sampling trace preparations
Selection of number of characters output
M9051 SM1051 CHG instruction execution disable
M9052 SM1052 SEG instruction switch
M9054 SM1054 SM205 STEP RUN flag OFF : STEP RUN not in effect ON : STEP RUN in effect
M9055 SM1055 SM808 Status latch completion flag
M9056 SM1056 Main side P, I set request
M9057 SM1057 Sub side P, I set request
M9058 SM1058 Main side P, I set completion
Momentarily ON at P, I set completion
M9059 SM1059 Sub program P, I set completion
Momentarily ON at P, I set completion
M9060 SM1060 Sub program 2 P, I set request

Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
M9061 SM1061 Sub program 3 P, I set request
Divided processing execution detection
Divided processing request flag
A8UPU/A8PUJre quired search time
The A8UPU/A8PUJ cannot be used in the QCPU/QnACPU special relays.
Communication request registration area BUSY signal
communication request registration area ON : No empty spaces in
communication request registration area
M9091 SM1091 Instruction error flag
M9094 SM1094 SM251 I/O change flag OFF : Replacement ON : No replacement
Presence/absenc e of SFC program
M9101 SM1101 SM321 Start/stop SFC program
M9102 SM1102 SM322 SFC program start status
Presence/absenc e of continuous transition

Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
Continuous transition suspension flag
Step transition watchdog timer start (equivalent of D9108)
Step transition watchdog timer start (equivalent of D9109)
Step transition watchdog timer start (equivalent of D9110)
Step transition watchdog timer start (equivalent of D9111)
Step transition watchdog timer start (equivalent of D9112)
Step transition watchdog timer start (equivalent of D9113)
Step transition watchdog timer start (equivalent of D9114)
Active step sampling trace completion flag
Active step sampling trace execution flag
Active step sampling trace permission
M9196 SM1196 SM325 Operation output at block stop
I/O numbers to be displayed
OFF OFF X/Y 0 to 7F0 M9197 SM1197
Switch between blown fuse and I/O verification error display
Switches I/O numbers in the fuse blow module storage registers (SD1100 to SD1107) and I/O module verify error storage registers (SD1116 to SD1123) according to the combination of ON/OFF of the SM1197 and SM1198.
ON OFF X/Y 800 to FF0
OFF ON X/Y 1000 to 17F0 M9198 SM1198
ON ON X/Y 1800 to 1FF0
Data recovery of online sampling trace/status latch
11 - 56 11 - 56
ACPU Special · start · way

Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
ZNRD instruction (LRDP instruction for ACPU) reception (for master station)
ZNRD instruction (LRDP instruction for ACPU) completion (for master station)
ZNWR instruction (LWTP instruction for ACPU) reception (for master station)
ZNWR instruction (LWTP instruction for ACPU) completion (for master station)
ZNRD instruction (LRDP instruction for ACPU) reception (for local station)
On indicates that the ZNRD instruction is complete at the local station.
ZNWR instruction (LWTP instruction for ACPU) recep-tion (for local station)
On indicates that the ZNWR instruction is complete at the local station.
Host station link parameter error
Depends on whether or not the link parameter setting of the host is valid.
Depends on whether or not the link parameter setting of the master station in tier two matches that of the master station in tier three in a three-tier system. (Valid only for the master stations in a three-tier system.)
Link parameter check results
Sets master station B and W transmission range (for lower link master stations only)
Link parameter check command (for lower link master stations only)
Link card error (for master station)
Depends on presence or absence of the link card hardware error. Judged by the CPU.
Link module error (for local station use)
Depends on presence or absence of the link card hardware error. Judged by the CPU.
Depends on whether the master station is online or offline or is in station-to-station test or self-loopback test mode.
M9224 SM1224 Link status
test, or self-loopback test
M9225 SM1225 Forward loop error OFF : Normal
ON : Abnormal Depends on the error condition of the forward loop line.
M9226 SM1226 Reverse loop error OFF : Normal
ON : Abnormal Depends on the error condition of the reverse loop line.
Depends on whether or not the master station is executing a forward or a reverse loop test.
M9227 SM1227 Loop test status
Local station operation status
Depends on whether or not a local station is in STOP or PAUSE mode.
ACPU Special · QnA · test execution underway

Special Relay after Conversion
Special Relay for Modification
Name Meaning Details Applicable
Relay
Local station error detect status
Depends on whether or not a local station has detected an error in another station.
Local station, remote I/O station parameter error detect status
Depends on whether or not a local or a remote I/O station has detected any link parameter error in the master station
Local station, remote I/O station initial communications status
Depends on the results of initial communication between a local or remote I/O station and the master station.
Local station, remote I/O station error
Depends on the error condition of a local or remote I/O station.
Local station, remote I/O station forward or reverse loop error
Depends on the error condition of the forward and reverse loop lines of a local or a remote I/O station.
Depends on whether the local station is online or offline, or is in station-to-station test or self-loopback test mode.
M9240 SM1240 Link status
stationtest, or self- loopback test
Forward loop line error
OFF : Normal ON : Abnormal Depends on the error condition of the forward loop line.
Reverse loop line error
OFF : Normal ON : Abnormal Depends on the error condition of the reverse loop line.
Depends on whether or not loopback is occurring at the local station.
M9246 SM1246 Data not received OFF : Reception
Depends on whether or not data has been received from the master station.
M9247 SM1247 Data not received OFF : Reception
Depends on whether or not a tier three station has received data from its master station in a three-tier system.
Depends on whether or not link parameters have been received from the master station.
M9251 SM1251 Link relay OFF : Normal ON : Abnormal Depands on the data link condition at the local station.
Depends on whether or not the local station is executing a forward or a reverse loop test.
M9252 SM1252 Loop test status
Master station operation status
Depends on whether or not the master station is in STOP or PAUSE mode.
Local station other than host station operation status
Depends on whether or not a local station other than the host is in STOP or PAUSE mode.
Local station other than host station error
Depends on whether or not a local station other than the host is in error.
11 - 58 11 - 58

(10) For redundant systems (Host system CPU information 1) for Q4AR only SM1510 to SM1599 are only valid for redundant systems. All off for standalone systems.
system backup mode, independent system ON : Redundant
S (Each END) New
SM1511 Start mode when
power supply is on
SM1512 Start mode when CPU
SM1513 Operation status when
SM1514 Operation mode when
S (Each END) New
S (Status change) /U New
SM1517 CPU startup status
SM1520 SM1520 Block 1 SM1521 SM1521 Block 2 SM1522 SM1522 Block 3 SM1523 SM1523 Block 4 SM1524 SM1524 Block 5 SM1525 SM1525 Block 6 SM1526 SM1526 Block 7 SM1527 SM1527 Block 8 SM1528 SM1528 Block 9 SM1529 SM1529 Block 10 SM1530 SM1530 Block 11 SM1531 SM1531 Block 12 SM1532 SM1532 Block 13 SM1533 SM1533 Block 14 SM1534 SM1534 Block 15 SM1535 SM1535 Block 16 SM1536 SM1536 Block 17 SM1537 SM1537 Block 18 SM1538 SM1538 Block 19 SM1539 SM1539 Block 20 SM1540 SM1540 Block 21 SM1541 SM1541 Block 22 SM1542 SM1542 Block 23 SM1543 SM1543 Block 24 SM1544 SM1544 Block 25 SM1545
Data tracking transmission link specification
1 Host system CPU information is stored.

Number Name Meaning Explanation Set by (When Set)
CPU SM1546 SM1546 Block 27 SM1547 SM1547 Block 28 SM1548 SM1548 Block 29 SM1549 SM1549 Block 30 SM1550 SM1550 Block 31 SM1551 SM1551 Block 32 SM1552 SM1552 Block 33 SM1553 SM1553 Block 34 SM1554 SM1554 Block 35 SM1555 SM1555 Block 36 SM1556 SM1556 Block 37 SM1557 SM1557 Block 38 SM1558 SM1558 Block 39 SM1559 SM1559 Block 40 SM1560 SM1560 Block 41 SM1561 SM1561 Block 42 SM1562 SM1562 Block 43 SM1563 SM1563 Block 44 SM1564 SM1564 Block 45 SM1565 SM1565 Block 46 SM1566 SM1566 Block 47 SM1567 SM1567 Block 48 SM1568 SM1568 Block 49 SM1569 SM1569 Block 50 SM1570 SM1570 Block 51 SM1571 SM1571 Block 52 SM1572 SM1572 Block 53 SM1573 SM1573 Block 54 SM1574 SM1574 Block 55 SM1575 SM1575 Block 56 SM1576 SM1576 Block 57 SM1577 SM1577 Block 58 SM1578 SM1578 Block 59 SM1579 SM1579 Block 60 SM1580 SM1580 Block 61 SM1581 SM1581 Block 62 SM1582 SM1582 Block 63 SM1583
Data tracking transmission link specification
SM1590 Switching status from

(11) For redundant system (Other system CPU information 1) for Q4AR only SM1600 to SM1650 only valid for the CPU redundant system backup mode, so they cannot be refreshed during the separate mode. Either the backup mode or the separate mode is valid for the SM4651 to SM1699. SM1600 to SM1699 are all turned off for standalone system.
ACPU M9 2
Number Name Meaning Explanation
S (Each END) New
S (Each END) New
SM1601 Self diagnosis error
S (Each END) New
S (Each END) New
SM1653 STOP contact STOP status • Turns on when in the STOP status. S (Each END) New
SM1654 PAUSE contact PAUSE status • Turns on when in the PAUSE status. S (Each END) New
SM1655 STEP-RUN contact STEP-RUN status • Turns on when in the STEP-RUN status. S (Each END) New
1 Stores other system CPU diagnostic information and system information. 2 This shows the special relay(SM ) for the host system CPU.

Either the backup mode or the second mode is valid for SM1700 to SM1799. All is turned off for standalone system.
SM1712 SM1712 Block 1 SM1713 SM1713 Block 2 SM1714 SM1714 Block 3 SM1715 SM1715 Block 4 SM1716 SM1716 Block 5 SM1717 SM1717 Block 6 SM1718 SM1718 Block 7 SM1719 SM1719 Block 8 SM1720 SM1720 Block 9 SM1721 SM1721 Block 10 SM1722 SM1722 Block 11 SM1723 SM1723 Block 12 SM1724 SM1724 Block 13 SM1725 SM1725 Block 14 SM1726 SM1726 Block 15 SM1727 SM1727 Block 16 SM1728 SM1728 Block 17 SM1729 SM1729 Block 18 SM1730 SM1730 Block 19 SM1731 SM1731 Block 20 SM1732 SM1732 Block 21 SM1733 SM1733 Block 22 SM1734 SM1734 Block 23 SM1735 SM1735 Block 24 SM1736 SM1736 Block 25 SM1737 SM1737 Block 26 SM1738 SM1738 Block 27 SM1739 SM1739 Block 28 SM1740 SM1740 Block 29 SM1741 SM1741 Block 30 SM1742 SM1742 Block 31 SM1743 SM1743 Block 32 SM1744 SM1744 Block 33 SM1745 SM1745 Block 34 SM1746 SM1746 Block 35 SM1747 SM1747 Block 36 SM1748 SM1748 Block 37 SM1749 SM1749 Block 38 SM1750 SM1750 Block 39 SM1751 SM1751 Block 40 SM1752 SM1752 Block 41 SM1753 SM1753 Block 42 SM1754 SM1754 Block 43 SM1755 SM1755 Block 44 SM1756 SM1756 Block 45 SM1757 SM1757 Block 46 SM1758 SM1758 Block 47 SM1759
Transmission trigger end flag


CPU SM1760 SM1760 Block 49 SM1761 SM1761 Block 50 SM1762 SM1762 Block 51 SM1763 SM1763 Block 52 SM1764 SM1764 Block 53 SM1765 SM1765 Block 54 SM1766 SM1766 Block 55 SM1767 SM1767 Block 56 SM1768 SM1768 Block 57 SM1769 SM1769 Block 58 SM1770 SM1770 Block 59 SM1771 SM1771 Block 60 SM1772 SM1772 Block 61 SM1773 SM1773 Block 62 SM1774 SM1774 Block 63 SM1775

The special registers, SD, are internal registers with fixed applications in the PLC. For this reason, it is not possible to use these registers in sequence programs in the same way that normal registers are used. However, data can be written as needed in order to control the CPU modules and remote I/O modules. Data stored in the special registers are stored as BIN values if no special designation has been made to the contrary. The headings in the table that follows have the following meanings.
S : Set by system U : Set by user (sequence programs or test operations from GX Developer) S/U : Set by both system and user
Set by (When set)
Indicated only for registers set by system Each END : Set during each END processing Initial : Set only during initial processing (when power supply is turned
ON, or when going from STOP to RUN) Status change : Set only when there is a change in status Error : Set when error occurs Instruction execution : Set when instruction is executed Request : Set only when there is a user request (through SM, etc.)

POINT (1) SD1200 to SD1255 are used for QnACPU.
These relays are vacant with QCPU. (2) Special register SD1500 and later are dedicated for Q4ARCPU.
Corresponding ACPU D9 · Corresponding CPU

(1) Diagnostic Information
Number Name Meaning Explanation
B15 B7 B0 B8 to to (Example) : October, 1995 H9510
Year (0 to 99) Month (1 to 12)
Clock time for diagnosis error occurrence
Clock time for diagnosis error occurrence
B15 B7 B0 B8 to to (Example) : 10 a.m. on 25th H2510
Day (1 to 31) Hour (0 to 23)
B15 B7 B0 B8 to to (Example) : 35 min. 48 sec. (past the hour) H3548
Minutes (0 to 59)
Seconds (0 to 59)
Category codes which help indicate what type of information is being stored in the common information areas (SD5 through SD15) and the individual information areas (SD16 through SD26) are stored here.
B15 B7 B0 B8 to to
Error information category code
number is stored depending on the error that occurred. (Refer to the corresponding error code for which number has been stored.) PLC No. 1: 1, PLC No. 2: 2, PLC No. 3: 3, PLC No. 4: 4 • The individual information category codes store the following codes: 0 : No error 1 : (Open) 2 : File name/Drive name 3 : Time (value actually measured) 4 : Program error location 5 : Parameter number 6 : Annunciator number 7 : Check instruction malfunction number

Number Name Meaning Explanation
1 Slot No.
Meaning Slot No./PLC No./Base No. 1 2
SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15
I/O No.
SD8
*1: For a multiple PLC system, the slot number or PLC number is stored depending on the error that occurred. Slot 0 in the multiple PLC system is the one on the slot on the right of the rightmost CPU module. (Refer to the corresponding error code for which number has been stored.) PLC No. 1: 1, PLC No. 2: 2, PLC No. 3: 3, PLC No. 4: 4 *2: If a fuse blown or I/O verify error occurred in the module loaded in the MELSECNET/H remote I/O station, the network number is stored into the upper 8 bits and the station number into the lower 8 bits. Use the I/O No. to check the module where the fuse blown or I/O verify error occurred.
SD10
S (Error) New +Rem
SD12
2 File name/Drive name
File name= ABCDEFGH. IJK
SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15
B15 to B8 B7 to B0
42H(B) 41H(A) 44H(D) 43H(C) 46H(F) 45H(E) 48H(H) 47H(G) 49H(I) 2EH(.) 4BH(K) 4AH(J)
SD14
(Continued to next page)

SD10 SD11 Higher8 bits Lower8 bits Higher8 bits Extension name File type
51H 50H 41H QPA Parameters 51H 50H 47H QPG Sequence program/SFC program 51H 43H 44H QCD Device comment 51H 44H 49H QDI Device initial value 51H 44H 52H QDR File register 51H 44H 53H QDS Simulation data 51H 44H 4CH QDL Local device 51H 54H 53H QTS Sampling trace data (For QnA) 51H 54H 4CH QTL Status latch data (For QnA) 51H 54H 50H QTP Program trace data (For QnA) 51H 54H 52H QTR SFC trace file 51H 46H 44H QFD Trouble history data

Number Name Meaning Explanation
3 Time (value set)
SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15
SD7
4 Program error location
SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15
S (Error) New +Rem
2E H (.)
Pattern Block No. Step No./transition No. Sequence step No. (L) Sequence step No. (H)
4 Contents of pattern data
0 1 2 3 4 15 14 to
0 to
SFC block designation present (1)/absent (0)
SFC step designation present (1)/absent (0) SFC transition designation present (1)/absent (0)
SD12
Switch direction (0:standby system to control system/ 1: control system to standby system)
SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15
S (Error) New Q4AR
5 Tracking flag contents Shows whether or not the tracking data is valid.
0 1 2 3 4 15 14 to
0 to
Invalid work data invalid (0) /valid (1)
System data (SFC active step information) invalid (0)/ valid (1) Switching cause invalid (0)/ valid (1)
11 - 67 11 - 67

Number Name Meaning Explanation
1 File name/Drive name
File name= ABCDEFGH. IJK
SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26
B15 to B8 B7 to B0
42H(B) 41H(A) 44H(D) 43H(C) 46H(F) 45H(E) 48H(H) 47H(G) 49H(I) 2EH(.) 4BH(K) 4AH(J)
2 Time (value actually measured)
SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26
SD20
3 Program error location
SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26
2E H (.)
S (Error) New +Rem
Pattern Block No. Step No./transition No.
Sequence step No. (L) Sequence step No. (H)
Contents of pattern data
0 1 2 3 4 15 14 to
0 to
SFC block designation present (1)/absent (0)
SFC step designation present (1)/absent (0) SFC transition designation present (1)/absent (0)
5 Annunciator number / CHK instruction malfunction number
6 Intelligent function module parameter error (for QCPU only)
SD24 4 Parameter number
Meaning Parameter No.
SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26
SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26
No.
Parameter No. Error code for intelligent function module
SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26
6 For details of the parameter numbers, refer to the user's manual of the CPU module used.
11 - 68 11 - 68

Number Name Meaning Explanation Set by (When set)
SD50 Error reset Error code that performs error reset • Stores error code that performs error reset U New +Rem
Bit pattern indicating where battery voltage drop occurred
CPU module battery error
SD51 Battery low latch
Memory card A alarm Memory card A error Memory card B alarm Memory card B error
Bit pattern indicating where battery voltage drop occurred
Number of times for AC/DC DOWN
S (Error) D9005 +Rem
1 The relevant station bit goes ON when any of the Installed MINI (-S3) X(n+0)/X(n+20), X(n+6)/(n+26), X(n+7)/(n+27) or X(n+8)/X(n+28) goes ON.
2 Goes ON when communications between the installed MINI (-S3) and the CPU are not possible. B15 B8 B9 B0
SD54 MINI link errors
S (Error) D9004 format
module
Information on Information on 1 2
SD60 Blown fuse number
Number of module with blown fuse
I/O module verification error number
I/O module verification error module number
Annunciator number • The first annunciator number to be detected is stored here. S (Instruction
Number of annunciators • Stores the number of annunciators searched. S (Instruction
SD63 Number of annunciators
11 - 69 11 - 69

Number Name Meaning Explanation Set by (When set)
When F goes ON due to OUT F or SET F , the F numbers which
go progressively ON from SD64 through SD79 are registered. F numbers turned OFF by RST F are deleted from SD64 to SD79,
and are shifted to the data register following the data register where the deleted F numbers had been stored. Execution of the LEDR instruction shifts the contents of SD64 to
SD67 D9128
SD79 up by one. (This can also be done by using the INDICATOR RESET switch on the of the Q3A/Q4ACPU.) After 16 annunciators have been detected, detection of the 17th will not be stored from SD64 through SD79.
SD69 D9130
SET
SET
SET F99
RST
SET F15
SET
SET F65
SET
SET F110
SET F151
SET F210LEDR
SD70 D9131
F50
F25
F25
F70
F38
Table of detected annunciator numbers
SD62 0 50 99 ...(Number detected)
SD63 0 1 2 3 2 3 4 5 6 7 8 9 8
...(Number of annunciators detected)
0 50 99 SD64
0 0 25 25 99 15
0 0 0 99 0 15 70
0 70 65
0 65 38
0 38 110
0 110 110 110 151
0 151 210
0 210
0
0
0
0
0
0
0
SD80 CHK number CHK number • Error codes detected by the CHK instruction are stored as BCD code.
SD90 Corresponds to SM90 D9108
SD91 Corresponds to SM91 D9109
SD92 Corresponds to SM92 D9110
Step transition watchdog timer setting value (Enabled only when SFC program exists)
SD93 Corresponds to SM93 D9111
F number for timer set value and time over error
Timer time limit setting (1 to 255 s: (1-s units)) • Timer is started by turning SM90 through SM99 ON during active step, and if the transition conditions for the relevant steps are not met within the timer limits, the designated annunciator (F) will go ON.
F number setting (0 to 255)
SD94 Corresponds to SM94 D9112
SD95 Corresponds to SM95 D9113
SD96 Corresponds to SM96 D9114
SD97 Corresponds to SM97 New
SD98 Corresponds to SM98 New
Stores the preset transmission speed when GX Developer is used.
CH1 transmission speed setting (RS-232)
11 - 70 11 - 70

Number Name Meaning Explanation Set by (When set)
S (Always) New Remote
1 Vacant 1 Remote I/O module switch status Always 1: STOP
Vacant 3 2 1
SD200 Status of switch
Status of CPU switch
Vacant 3 2 1

Number Name Meaning Explanation Set by (When set)
8 3 2 1 4 5 6 7
5 : BOOT
2 : ERROR
SD201 LED status Status of CPU-LED
8 3 2 1 4 5 6 7
1 : RUN
2 : ERROR
Bit pattern of LED that is turned off
S (Always) New Remote
1 Vacant 1 Remote I/O module operating status Always 2: STOP
Operating status of CPU
Operating status of CPU
Device test execution type
11 - 72 11 - 72

Number Name Meaning Explanation Set by (When set)
SD207 Priorities 1 to 4 D9038
SD208 Priorities 5 to 8 D3039 format
Priority 8 Priority 7 Priority 6 Priority 5 SD208
LED display priority ranking Priorities 9 to 10
Priority 10 Priority 9 SD209 Default Value SD207=H4321 SD208=H8765 SD207=H00A9 • No display is made if "0" is set. However, even if "0" has been set, information concerning CPU module operation stop (including parameter settings) errors will be indicated by the LEDs without conditions.
SD209
Example :
SD210 Clock data Clock data (year, month)
to
to
Example :
SD211 Clock data Clock data (day, hour)
31st, 10 a.m. H3110
Clock data (minute, second)
35 min., 48 sec. (after the hour) H3548
B15 B12B11 B8 B7 B4 B3 B0 to
Example :
Clock data (higher digits of year, day of week)
S/U (Request) D9028 QCPU Remote
Higher digits of year (0 to 99)
to
Example :
Clock data (day of week)
S/U (Request) D9028 QnA

Number Name Meaning Explanation Set by (When set)
SD220
to B15 B8 to B7 B0
SD220
15th character from the right
16th character from the right
SD221
13th character from the right
14th character from the right
SD222
11th character from the right
12th character from the right
S (When changed) New
SD223
9th character from the right
10th character from the right
7th character from the right
8th character from the right
SD225
5th character from the right
6th character from the right
SD226
3rd character from the right
4th character from the right
1st character from the right
2nd character from the right
No. of extension bases
B1 B2 B7
B0
SD242 A/Q base differentiation
When no expansion base is installed, the value is fixed to 0.
SD243
SD243 Expansion 3 Expansion 2 Expansion 1 Main
No. of base slots No. of base slots
Expansion 7 Expansion 6 Expansion 5 Expansion 4 SD244
SD250 Loaded maximum I/O
Loaded maximum I/O No.
Head I/O number for replacement
Head I/O No. for module replacement
SD251
SD253 RS-422 baud rate RS-422 baud rate • Stores baud rate of RS-422.
SD254 Number of modules installed • Indicates the number of modules installed on MELSECNET/10 (H).
SD255 I/O No. • MELSECNET/10 (H) I/O number of first module installed
SD256 Network No. • MELSECNET/10 (H) network number of first module installed
Informa- tion from 1st module
SD257 Group number • MELSECNET/10 (H) group number of first module installed
SD258 Station No. • MELSECNET/10 (H) station number of first module installed
MELSECNET /10 (H) information
Information from 2nd module • Configuration is identical to that for the first module.
Information from 3rd module • Configuration is identical to that for the first module.
Information from 4th module • Configuration is identical to that for the first module.

Number Name Meaning Explanation Set by (When set)
1 When Xn0 of the installed CC-Link goes ON, the bit corresponding to the station switches ON. 2 When either Xn1 or XnF of the installed CC-Link switch OFF, the bit corresponding to the station switches ON. 3 Switches ON when the CPU module cannot communicate with the installed CC-Link.
Information of 1 Information of 2 Information of 3
S (Error) New QCPU Remote
B0
SD280 CC-Link error Error detection status
The above module numbers n are in order of the head I/O Nos. (However, the modules without parameter setting are not counted in.)
1 When Xn0 of the installed CC-Link goes ON, the bit corresponding to the station switches ON. 2 When either Xn1 or XnF of the installed CC-Link switch OFF, the bit corresponding to the station switches ON. 3 Switches ON when the CPU module cannot communicate with the installed CC-Link.
S (Error) New QnA
module ...
Information of 1 Information of 2
Number of points allocated for X
Number of points allocated for Y
Number of points allocated for M
Number of points allocated for L
Number of points allocated for B
Number of points allocated for F
Device allocation (Same as parameter contents)
Number of points allocated for SB
Number of points allocated for V
Number of points allocated for S
Number of points allocated for T
Number of points allocated for ST
Number of points allocated for C

Number Name Meaning Explanation Set by (When set)
SD302 Number of points allocated for D • Stores the number of points currently set for D devices
Device allocation (Same as parameter contents) Number of points allocated for SW • Stores the number of points currently set for SW devices
SD303 Number of points allocated for W • Stores the number of points currently set for W devices
S (Initial) New +Rem
Reserves the designated time for communication processing with GX Developer or other units. The greater the value is designated, the shorter the response time for communication with other devices (GX Developer, serial communication units) becomes. Setting range: 1 to 100 ms If the designated value is out of the range above, it is assumed to no setting.
Time reserved for communicat ion processing
Time reserved for communication processing
SD340 No. of modules installed • Indicates the number of modules installed on Ethernet.
SD341 I/O No. • Ethernet I/O No. of the 1st module installed.
SD342 Network No. • Ethernet network No. of the 1st module installed.
SD343 Group No. • Ethernet group No. of the 1st module installed.
SD344 Station No. • Ethernet station No. of the 1st module installed.
Informa- tion of 1st module
SD345 to SD346 Vacant
Information from 2nd module • Configuration is identical to that for the first module.
Information from 3rd module • Configuration is identical to that for the first module.
Information from 4th module • Configuration is identical to that for the first module.
SD340 No. of modules installed • Indicates the number of modules installed on Ethernet.
SD341 I/O No. • Ethernet I/O No. of the 1st module installed.
SD342 Network No. • Ethernet network No. of the 1st module installed.
SD343 Group No. • Ethernet group No. of the 1st module installed.
Informa- tion of 1st module
SD344 Station No. • Ethernet station No. of the 1st module installed.
SD345 to SD346 IP address • Ethernet IP address of the 1st module installed.
Error code • Ethernet error code of the 1st module installed.
Information from 2nd module • Configuration is identical to that for the first module.
Information from 3rd module • Configuration is identical to that for the first module.
Information from 4th module • Configuration is identical to that for the first module. S (Initial) New
B1 B2 B3 B4 B5 B6 B7 B8 B15
Instruction reception status of channel 1 Instruction reception status of channel 2
Ethernet instruction reception status
Instruction reception status of channel 3 Instruction reception status of channel 4 Instruction reception status of channel 5 Instruction reception status of channel 6 Instruction reception status of channel 7 Instruction reception status of channel 8
Instruction reception status of 1st module

Number Name Meaning Explanation Set by (When set)
SD381 Information from 2nd module • Configuration is identical to that for the first module.
Ethernet instruction reception status Information from 4th module • Configuration is identical to that for the first module.
SD382 Information from 3rd module • Configuration is identical to that for the first module.
The software version is stored in the lower byte position. The data in the higher byte position is indefinite.
Higher byte Lower byte
Internal system software version
For version "A", for example, "41H" is stored.
version indicated by the version symbol printed on the case.
SD395 Multiple PLC number
S (Initial) New QCPU function
Ver. B or later
Number Name Meaning Explanation Set by (When set)
SD412 1 second counter
Number of counts in 1-second units
S (Status change) D9022
2n second clock setting
2n second clock units
Number of counts in each scan
Low speed scan counter
Number of counts in each scan
: Not counted by the scan in an initial execution type program.

Number Name Meaning Explanation Set by (When set)
SD500 Execution program No.
Execution type of program being executed
File name of low speed execution in progress
SD510 Low speed program No.
SD520 Current scan time (ms unit)
Current scan time (µs unit)
below. SD520 = 23 SD521 = 600
SD522 Initial scan time (ms unit)
Initial scan time Initial scan time (µs unit)
SD524 Minimum scan time (ms unit)
Minimum scan time (µs unit)
SD526 Maximum scan time (ms unit)
Maximum scan time Maximum scan time (µs unit)
SD528 Current scan time (ms unit)
Current scan time for low speed execution type programs
Current scan time (µs unit)
SD532 Minimum scan time (ms unit)
Minimum scan time for low speed execution type programs
Minimum scan time (µs unit)
SD534 Maximum scan time (ms unit)
Maximum scan time for low speed execution type programs
Maximum scan time (µs unit)
SD540 END processing time (ms unit)
END processing time END processing time (µs unit)
11 - 78 11 - 78

Number Name Meaning Explanation Set by (When set)
SD542 Constant scan waiting time (ms unit)
Constant scan wait time Constant scan waiting time (µs unit)
Cumulative execution time for low speed execution type programs
Low speed program cumulative execution time (ms unit)
Low speed program cumulative execution time (µs unit)
Low speed program execution time (ms unit)
Execution time for low speed execution type programs
Low speed program execution time (µs unit)
Scan program execution time (ms unit)
Scan program execution time Scan program
execution time (µs unit)
Service interval measurement module
Unit/module No. • Sets I/O number for module that measures service interval U New
SD551 Module service intervals (ms unit)
Service interval time Module service intervals (µs unit)
11 - 79 11 - 79

Number Name Meaning Explanation Set by (When set)
S (Initial and card
Memory card A models
Memory card A models • Indicates memory card A model installed B4 B3 B0
SD600
S (Initial and card
S (Initial and card
removal) New QCPU SD602
Drive 1 (RAM) capacity
Drive 1 capacity • Drive 1 capacity is stored in 1 kbyte units S (Initial and card
S (Initial and card
removal) New QCPU SD603
Drive 2 (ROM) capacity
Drive 2 capacity • Drive 2 capacity is stored in 1 kbyte units S (Initial and card
B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File register R (QDR) B5: Trace (QTS) B6: Not used B7: Not used
B8: Not used B9: CPU fault history (QFD) BA: SFC trace (QTS) BB: Local device (QDL) BC: Not used BD: Not used BE: Not used BF: Not used
S (Status change) New QCPU
Memory card A use conditions
Memory card A use conditions
B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File register R (QDR) B5: Sampling trace (QTS) B6: Status latch (QTL) B7: Program trace (QTP)
B8: Simulation data (QDS) B9: CPU fault history (QFD) B10: SFC trace (QTS) B11: Local device (QDL) B12: Not used B13: Not used B14: Not used B15: Not used
S (Status change) New QnA
Memory card B models
Memory card B models
1: SRAM
S (Initial) New QCPU
2 Drive 4 is fixed to "3" because it has built-in Flash ROM.

Number Name Meaning Explanation
Q2A (S1)
SD620 Memory card B models
Memory card B models
1: SRAM
Drive 3 (RAM) capacity
Drive 3 capacity • Drive 3 capacity is stored in 1 kbyte units S (Initial) New
Q3A Q4A Q4AR
Drive 4 (ROM) capacity
SD623
Drive 4 capacity • Drive 4 capacity is stored in 1 kbyte units S (Initial) New
B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File R (QDR) B5: Trace (QTS) B6: Not used B7: Not used
B8: Not used B9: CPU fault history (QFD) B10: SFC trace (QTS) B11: Local device (QDL) B12: Not used B13: Not used B14: Not used B15: Not used
Drive 3/4 use conditions
Drive 3/4 use conditions
B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File R (QDR) B5: Sampling trace (QTS) B6: Status latch (QTL) B7: Program trace (QTP)
B8: Simulation data (QDS) B9: CPU fault history (QFD) B10: SFC trace (QTS) B11: Local device (QDL) B12: Not used B13: Not used B14: Not used B15: Not used
Memory card B use conditions
Memory card B use conditions
SD640 File register drive Drive number: • Stores drive number being used by file register S (Initial) New
B15 to B8 B7 to B0
SD644
SD641 SD642 SD643 SD644 SD645
First character Third character
File register file name
File register file name
Sixth character Eighth character First character of extension
Fifth character Seventh character
SD646
SD646
Third character of extension
SD647 File register capacity
SD648 File register block number
File register block number • Stores the currently selected file register block number. S (Status


Number Name Meaning Explanation
Mask pattern Mask pattern
Number of vacant communicati on request registration areas
0 to 32 • Stores the number of vacant blocks in the communications request area for remote terminal modules connected to the AJ71PT32-S3.
S (During execution) D9081 QnA
B15 B0 B1 to
IMASK instruction mask pattern
S (During execution) New
SD716
SD717
SD717
SD718
SD719
Accumulator Accumulator • For use as replacement for accumulators used in A-series programs. S/U New
Program No. designation for PLOAD instruction
Program No. designation for PLOAD instruction
No. of vacant registration area for CC- Link communicati on request
0 to 32 • Stores the number of vacant registration area for the request for communication with the intelligent device station connected to A(1S)J61QBT61.
S (During execution) New QnA
SD736 PKEY input PKEY input • Special register that temporarily stores keyboard data input by means of the PKEY instruction.
S (During execution) New QnA

Number Name Meaning Explanation
SD738
1st character B15 B8 B7 B0
SD738 SD739 SD740 SD741 SD742 SD743
2nd character 3rd character 4th character 5th character 6th character 7th character 8th character 9th character 10th character 11th character 12th character 13th character 14th character 15th character 16th character 17th character 18th character 19th character 20th character 21st character 22nd character 23rd character 24th character 25th character 26th character 27th character 28th character 29th character 30th character 31st character 32nd character 33rd character 34th character 35th character 36th character 37th character 38th character 39th character 40th character 41st character 42nd character 43rd character 44th character 45th character 46th character 47th character 48th character 49th character 50th character 51st character 52nd character 53rd character 54th character 55th character 56th character 57th character 58th character 59th character 60th character 61st character 62nd character 63rd character
SD742
SD743
SD744
SD745
SD744 SD745 SD746 SD747 SD748 SD749 SD750 SD751 SD752 SD753 SD754 SD755 SD756 SD757 SD758 SD759 SD760 SD761 SD762 SD763 SD764 SD765 SD766 SD767 SD768 SD769 64th character
SD747
SD748
SD749
SD750
SD751
SD752
SD753
S (During execution) New
SD755
SD756
SD757
SD758
SD759
SD760
SD761
SD762
SD763
SD764
SD765
SD766
SD767
SD768
SD769
B15 B1 B0 Loop16
SD775
Selects whether or not the data is refreshed when the COM instruction
is executed.
Refresh processing selection when the COM instruction is executed
SD778 0 1/0 b14 b5 to b4 b3 b2 b1 b0 b15
QCPU Serial number 04012 or later
I/O refresh CC-Link refresh MELSECNET/H refresh Automatic refresh of intelligent function modules Automatic refresh of multi-CPU shared memory General data processing
11 - 83 11 - 83


Remaining No. of simultaneous execution of CC-Link dedicated instruction
0 to 32 • Stores the remaining number of simultaneous execution of the CC- Link dedicated instructions. U New QnA
SD812 • Stores step number from point in time when status latch was conducted.
0 1 2 3 4 15 14
(Not in use) SFC block designation present (1)/absent (0)

Number Name Meaning Explanation
Access file drive number during power loss
Drive where power was interrupted
B15 B8 B7 B0 1st character 2nd character 3rd character 4th character 5th character 6th character 7th character 8th character
SD901 SD902 SD903 SD904
SD903
File name active during power loss
Access file name during power loss
SD905
1st character of extension 2EH(.)
2nd character of extension 3rd character of extension
SD906
SD910
SD911
SD910 SD911 SD912 SD913 SD914 SD915
1st character 2nd character 3rd character 4th character 5th character 6th character 7th character 8th character 9th character 10th character 11th character 12th character 13th character 14th character 15th character 16th character 17th character 18th character 19th character 20th character 21st character 22nd character 23rd character 24th character 25th character 26th character 27th character 28th character 29th character 30th character 31st character 32nd character
SD913
SD914
SD915
SD916
SD916 SD917 SD918 SD919 SD920 SD921 SD922 SD923 SD924 SD925
RKEY input RKEY input
S (During execution) New
SD919
SD920
SD921
SD922
SD923
SD924
SD925
11 - 85 11 - 85

ACPU special registers D9000 to D9255 correspond to the special registers SD1000 to SD1255 after A-series to the Q/QnA-series conversion. These special registers are all set by the system, and users cannot use them to set program data. Users who need to set data with these registers should edit the special registers for the Q/QnA. However, before conversion users could set data at special registers D9200 to D9255 only, and after conversion users can also set data at registers 1200 to 1255. For more detailed information concerning the contents of the ACPU special registers, see the individual CPU users manual, and the MELSECNET and MELSECNET/B data link system reference manual.
1 For the device numbers for which a special register for modification is specified, modify it to the special register for QCPU/QnACPU.
2 For the device numbers for which is specified, special register after conversion can be used.
3 Device numbers for which is specified do not function for QCPU/QnACPU.
Special Register for Modification
Name Meaning Details Corresponding
Number of module with blown fuse
D9000 SD1000 Fuse blown
I/O module for A0J2 Extension base unit
switch Stored data Base unit
slot No. Stored data
0 1 0 5
Number of module with blown fuse
1 2 1 6
D9001 SD1001 Fuse blown
2 3 2 7
3 4 3 8

Name Meaning Details Corresponding
entered, are detected when the power is turned on,
the first I/O number of the lowest number unit among
the detected units is stored in hexadecimal. (Storing
method is the same as that of SD1000.) To monitor
the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of SD1116 to SD1123 are
reset to 0.)
modules of remote I/O terminals.
mounted MELSECNET/MINI-S3 master module. B15 B8 B7 B0
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
On the PLC CPU and A(1S)J71PT32(S3) side, the bit corresponding to the A(1S)J71PT32(S3) that cannot make data communication turns ON.
Bits which correspond to the signals of A(1S)J71PT32(S3), shown below, are turned on as the signals are turned on. · Hardware error (X0/X20)
· MINI(S3) link error datection (X6/X26)
· MINI(S3) link communication error (X7/X27)
20ms occurs when AC power supply module is used,
and reset when power is switched OFF, then ON.
Number of times for
10ms occurs when DC power supply module is used,
and reset when power is switched OFF, then ON.
1ms occurs when DC power supply module is used,
and reset when power is switched OFF, then ON.
D9008 SD1008 SD0 Self-diagnosis
code is stored in BIN code.
SET F , the F number, which has been detected
earliest among the F numbers which have turned on,
is stored in BIN code. • SD62 can be cleared by RST F or LEDR
instruction.
If another F number has been detected, the clearing of
F number at which
SD62 causes the next number to be stored in SD62.
D9009 SD1009 SD62 Annunciator
SET F , the F number, which has been detected
earliest among the F numbers which have turned on,
is stored in BIN code. • SD62 can be cleared by executing RST F or
LEDR instruction or moving INDICATOR RESET
switch on CPU front to ON position. If another F
number has been detected, the clearing of SD62
causes the nest number to be stored in SD62.
of application instruction, the step number, at which
D9010 SD1010 Error step
the error has occurred, is stored in BIN code.
error has occurred.
Thereafter, each time operation error occurs, the
contents of SD1010 are renewed.

Special Register for Modification
Name Meaning Details Corresponding
Step number at which operation error has occurred.
D9011 SD1011 Error step
D9014 SD1014 I/O control mode I/O control mode

to
Remote RUN/STOP by computer
0 RUN
1 STOP
1 STOP
D9015 SD1015 SD203 Operating status of CPU
Operating status of CPU
PAUSE 1
3 STEP RUN
Remains the same in remote RUN/STOP mode.
Remote RUN/STOP by parameter setting
0 RUN
1 STOP
2 PAUSE 1
1 When the CPU module is in RUN mode and SM1040 is off, the CPU remains in RUN mode if changed to PAUSE mode.
D9016 SD1016 Program number
D9017 SD1017 SD520 Scan time Minimum scan time (10 ms units)
D9018 SD1018 SD524 Scan time Scan time (10 ms units)

Special Register for Modification
Name Meaning Details Corresponding
D9019 SD1019 SD526 Scan time Maximum scan time (10 ms units)
Constant scan time (User sets in 10 ms units)
D9020 SD1020 Constant scan
D9021 SD1021 Scan time Scan time (1 ms units)
D9022 SD1022 SD412 1 second counter
Count in units of 1sec.
D9025 SD1025 Clock data Clock data (year, month)

to
D9026 SD1026 Clock data Clock data (day, hour)
to
Example 31th, 10 o'clock H3110
D9027 SD1027 Clock data Clock data (minute, second)
to
B15 B12 B11 B8 B7 B4 B3 B0 Example: Friday H0005
to

0 must be set. Day of the week
D9028 SD1028 Clock data Clock data (day of week)
0 1 2 3
Sunday Monday Tuesday Wednesday
D9035 SD1035 SD648 Extension file register Use block No. • Stores the block No. of the extension file register being used in BCD code.
Device number when individual devices from extension file register are directly accessed
Extension file registerfor designation of device number
Block No.1 area
16383 16384 Block No.2 area
D9037 SD1037
Device No. (BIN data)
D9038 SD1038 SD207 Priorities 1 to 4
LED display priority ranking Priorities 5 to 7
B15 B12B11 B8 B7 B4 B3 B0 Priority 4 Priority 3 Priority 2 Priority 1
to
SD207
SD208
Priority 5 Priority 6 Priority 7

Special Register for Modification
Name Meaning Details Corresponding
D9044 SD1044 For sampling trace
Step or time during sampling trace
stored in SD1044 is used as sampling trace condition.
For scan 0 For time Time (10ms increments) Value is stored into SD1044 in BIN code.
Extension file register block No. used as SFC program execution work area
D9049 SD1049 Work area for SFC
Error code generated by SFC program
D9050 SD1050 SFC program error number
Block number where error occurred
D9051 SD1051 Error block
D9052 SD1052 Error step Step number where error occurred
Transition condition number where error occurred
D9053 SD1053 Error transition
Sequence step number where error occurred
D9054 SD1054 Error sequence step
Status latch execution step No.
Status latch execution step No.
Block No.
Step No.
(BIN)
Higher 8 bits Lower 8 bits
The data in the lower byte position is indefinite. The software version is stored in the higher byte position.
Higher byte Lower byte
D9060 SD1060 SD392 Software version Software version of
For version "A", for example, "41H" is stored. Note: The software version of the initial system may
differ from the version indicated by the version information printed on the rear of the case.
Data check of serial communication module
Number of empty blocks in communications request registrtion area
11 - 90 11 - 90

Special Register for Modification
Name Meaning Details Corresponding
Register for setting time check value
Microcomputer subroutine input data area head device No.
According to corresponding microcomputer package
D9091 SD1091 Detailed error code
Self-diagnosis detailed error code • Stores the detail code of cause of an instruction error.
Head I/O number for replacement
Head I/O number for replacement
D9100 SD1100
D9102 SD1102
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 1 (Y80) 0
Bit pattern in units of 16 points, indicating the modules whose fuses have blown
SD1101
0
0 1 Y7 B0
D9104 SD1104
SD1107
Indicates fuse blow.
D9106 SD1106
D9107 SD1107
D9108 SD1108
b15 b8 b7 b0 to to

Step transfer monitoring timer setting
Timer setting valve and the F number at time out
Timer setting (1 to 255 s in seconds)
D9112 SD1112
(By turning on any of SM1108 to SM1114, the
monitoring timer starts. If the transfer condition following a step which corresponds to the timer is not established within set time, set annunciator (F) is tuned on.)
D9114 SD1114
D9116 SD1116
D9118 SD1118
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit pattern, in units of 16 points, indicating the modules with verification errors.
0
D9119 SD1119
0 1 XY 100
I/O module verification error
0
0 1 XY 100
SD1123
Indicates I/O module verify error. • I/O module verify check is executed also to remote I/O station modules. (If normal status is restored, clear is not performed. Therefore, it is required to perform clear by user program.)
D9122 SD1122
D9123 SD1123
11 - 91 11 - 91

Special Register for Modification
Name Meaning Details Corresponding
instruction is executed, 1 is subtracted from the contents of SD63. (If the INDICATOR RESET switch is provided to the CPU, pressing the switch can execute the same processing.) • Quantity, which has been turned on by SET F is
stored into SD63 in BIN code. The value of SD63 is maximum 8.
numbers turned ON sequentially are registered into D9125 - D9132. F numbers turned OFF by RST F are deleted from
D9125 - D9132, and move to data registers subsequent to the ones that stored deleted F numbers. Execution of LEDR instruction shifts up
SD64 - SD71 contents one place. (When CPU has INDICATOR RESET switch, pressing that switch performs the same processing.) When there are eight annunciator numbers detected, the ninth number is not stored into SD64 - SD71 if detected.
D9128 SD1128 SD67
SET F50
SET F25
SET F99
RST F25
SET F15
SET F70
SET F65
SET F38
SET F110
SET F151
SET F210 LEDR
SD62
0 50 99
SD63
1 2 3 2 3 4 5 6 7 8 8 8
0 50 99
0 25 25 99 15
SD66
0 99 15 70
0 70 65 0
0 65 38 0
SD69
0 38 110
0 110 110 110 151 0
0 151 151 210
11 - 92 11 - 92

Special Register for Modification
Name Meaning Details Corresponding
Stores the execution result of the ZNRD (word device read) instruction
ZNRD (LRDP for ACPU) processing results
The specified station is a remote I/O station.
Stores the execution result of the ZNWR (word device write) instruction.
ZNWR (LWTP for ACPU) processing results
The specified station is a remote I/O station.
Stores conditions for up to numbers 1 to 16
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
Local station link type
L32 L31 L30 L29 L28 L27
SD1241
L48 L47 L46 L45 L44 L43
L64 L63 L62 L61 L60 L59
Stores conditions for up to numbers 17 to 32
Stores the present path status of the data link. • Data link in forward loop

Master station Station 1 Station 2 Station n
D9204 SD1204 Link status
Forward loop Reverse loop • Data link in reverse loop

Master station Station 1 Station 2 Station n
Forward loop Reverse loop

Special Register for Modification
Name Meaning Details Corresponding

Master station Station 1 Station 2 Station 3 Station n
Forward loopback Reverse loopback • Loopback in forward loop only

Master station Station 1 Station 2 Station 3 Station n
D9204 SD1204 Link status
Forward loopback • Loopback in reverse loop only

Master station Station 1 Station 2 Station 3 Station n
Stores the local or remote I/O station number at which loopback is being executed.
Station that implemented forward loopback

Master station Station 1 Station 2 Station 3 Station n
Forward loopback Reverse loopback In the example of above figure, "1" is stored into SD1205 and "3" into SD1206. If data link returns to normal status (data link in forward loop), values stored into SD1205, SD1206 do not return to "0". To return them to "0", therefore, sequence program must be used or reset operation performed.
Station that implemented reverse loopback
Stores the number of retry times due to transmission error. Count stops at maximum of "FFFFH" . RESET to return the count to 0.
Stored as cumulative value
Stores the number of times the loop line has been switched to reverse loop or loopback. Count stops at maximum of "FFFFH". RESET to return the count to 0.
Number of times loop selected
Stored as cumulative value
Stores conditions for up to numbers 1 to 16
Stores the local station numbers which are in STOP or PAUSE mode.
Local station operation status
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Stores conditions for up to numbers 17 to 32
Local station operation status
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
SD1213
L32 L31 L30 L29 L28 L27
SD1214
L48 L47 L46 L45 L44 L43
When a local station is switched to STOP or PAUSE mode, the bit corresponding to the station number in the register becomes "1". Example: When station 7 switches to STOP mode,
L64 L63 L62 L61 L60 L59
Stores conditions for up to numbers 33 to 48
Local station operation status
Stores conditions for up to numbers 49 to 64
Local station operation status
bit 6 in SD1212 becomes "1" , and when SD1212 is monitored, its value is "64 (40H)".
11 - 94 11 - 94

Special Register for Modification
Name Meaning Details Corresponding
Stores conditions for up to numbers 1 to 16
Station numbers of local stations that have detected errors are stored into corresponding data register bits as indicated below.
Stores conditions for up to numbers 17 to 32
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SD1216
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
Local station error detect status
L32 L31 L30 L29 L28 L27
Stores conditions for up to numbers 33 to 48
L48 L47 L46 L45 L44 L43
If a local station detects an error, the bit corresponding to the station number becomes "1". Example: When station 6 and 12 detect an error, bits 5
L64 L63 L62 L61 L60 L59
D9218 SD1218
Stores conditions for up to numbers 49 to 64
and 11 in SD1216 become "1", and when SD1216 is monitored, its value is "2080 (820H)".
Stores conditions for up to numbers 1 to 16
Stores the local station numbers that have mismatches between the parameters of the master station of tier three and those of the master station in tier two in the three tier system or the remote I/O station numbers that have incorrect I/O assignment, as shown below in correspondence with the data register bits.
Stores conditions for up to numbers 17 to 32
Local station parameters non-conforming; remote I/O station I/O allocation error
Stores conditions for up to numbers 33 to 48
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
L32 L31 L30 L29 L28 L27
SD1222
L48 L47 L46 L45 L44 L43
If a local station acting as the master station of tier three detects a parameter error or a remote station contains an invalid I/O assignment, the bit corresponding to the station number becomes "1". Example: When local station 5 and remote I/O station
L64 L63 L62 L61 L60 L59
Stores conditions for up to numbers 49 to 64
14 detect an error, bits 4 and 13 in SD1220 become "1" , and when SD1220 is monitored, its value is "8208 (2010H) " .
Stores conditions for up to numbers 1 to 16
Stores the local or remote station numbers while they are communicating the initial data with their relevant master station.
Stores conditions for up to numbers 17 to 32
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 L/R
1 L/R
16 L/R
15 L/R
14 L/R
13 L/R
12 L/R
11 L/R
10 L/R
9 L/R
8 L/R
7 L/R
6 L/R
5 L/R
4 L/R
3 L/R
2 L/R
Local station and remote I/O station initial communications underway
17 L/R
32 L/R
31 L/R
30 L/R
29 L/R
28 L/R
27 L/R
26 L/R
25 L/R
24 L/R
23 L/R
22 L/R
21 L/R
20 L/R
19 L/R
18 L/R
SD1226
48 L/R
47 L/R
46 L/R
45 L/R
44 L/R
43 L/R
42 L/R
41 L/R
40 L/R
39 L/R
38 L/R
37 L/R
36 L/R
35 L/R
34 L/R
Stores conditions for up to numbers 33 to 48
The bit corresponding to the station number which is currently communicating the initial settings becomes "1" . Example: When stations 23 and 45 are communicating,
64 L/R
63 L/R
62 L/R
61 L/R
60 L/R
59 L/R
58 L/R
57 L/R
56 L/R
55 L/R
54 L/R
53 L/R
52 L/R
51 L/R
50 L/R
D9226 SD1226
SD1227
Stores conditions for up to numbers 49 to 64
bit 6 of SD1225 and bit 12 of SD1226 become "1", and when SD1225 is monitored, its value is "64 (40H)", and when SD1226 is monitored, its value is "4096 (1000H)"
Stores conditions for up to numbers 1 to 16
Stores the local or remote station numbers which are in error.
Stores conditions for up to numbers 17 to 32
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 L/R
1 L/R
16 L/R
15 L/R
14 L/R
13 L/R
12 L/R
11 L/R
10 L/R
9 L/R
8 L/R
7 L/R
6 L/R
5 L/R
4 L/R
3 L/R
2 L/R
D9229 SD1229
SD1229
17 L/R
32 L/R
31 L/R
30 L/R
29 L/R
28 L/R
27 L/R
26 L/R
25 L/R
24 L/R
23 L/R
22 L/R
21 L/R
20 L/R
19 L/R
18 L/R
Local station and remote I/O station error
48 L/R
47 L/R
46 L/R
45 L/R
44 L/R
43 L/R
42 L/R
41 L/R
40 L/R
39 L/R
38 L/R
37 L/R
36 L/R
35 L/R
34 L/R
The bit corresponding to the station number with the error becomes "1" . Example: When local station 3 and remote I/O station
64 L/R
63 L/R
62 L/R
61 L/R
60 L/R
59 L/R
58 L/R
57 L/R
56 L/R
55 L/R
54 L/R
53 L/R
52 L/R
51 L/R
50 L/R
Stores conditions for up to numbers 33 to 48
D9230 SD1230
Stores conditions for up to numbers 49 to 64
14 have an error, bits 2 and 13 of SD1228 become "1", and when SD1228 is monitored, its value is "8196 (2004H)".
11 - 95 11 - 95

Special Register for Modification
Name Meaning Details Corresponding
Stores conditions for up to numbers 1 to 8
Stores the local or remote station number at which a forward or reverse loop error has occurred
Stores conditions for up to numbers 9 to 16
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
R F R F R F R F R F R F R F R F
L/R8 L/R7 L/R6 L/R5 L/R4 L/R3 L/R2 L/R1
R F R F R F R F R F R F R F R F
Stores conditions for up to numbers 17 to 24
L/R16 L/R15 L/R14 L/R13 L/R12 L/R11 L/R10 L/R9
D9234 SD1234
R F R F R F R F R F R F R F R F
L/R24 L/R23 L/R22 L/R21 L/R20 L/R19 L/R18 L/R17
R F R F R F R F R F R F R F R F
Stores conditions for up to numbers 25 to 32
L/R32 L/R31 L/R30 L/R29 L/R28 L/R27 L/R26 L/R25
D9235 SD1235
R F R F R F R F R F R F R F R F
Local station and remote I/O station loop error
L/R40 L/R39 L/R38 L/R37 L/R36 L/R35 L/R34 L/R33
Stores conditions for up to numbers 33 to 40
R F R F R F R F R F R F R F R F
D9236 SD1236
R F R F R F R F R F R F R F R F
L/R56 L/R55 L/R54 L/R53 L/R52 L/R51 L/R50 L/R49
Stores conditions for up to numbers 41 to 48
In the above table, "F" indicates a forward loop line and "R" a reverse loop line .The bit corresponding to the station number at which the forward or reverse loop error has occurred, becomes "1". Example: When the forward loop line of station 5 has an
R F R F R F R F R F R F R F R F
D9237 SD1237
Stores conditions for up to numbers 49 to 56
Stores conditions for up to numbers 57 to 64
error, bit 8 of SD1232 become "1", and when SD1232 is monitored, its value is "256 (100H)".
Stores the number of times the following transmission errors have been detected: CRC, OVER, AB. IF Count is made to a maximum of FFFFH. RESET to return the count to 0.
Number of times communications errors detected
Stores cumulative total of receive errors
Stores conditions for up to numbers 33 to 48
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
Local station link type
L32 L31 L30 L29 L28 L27
SD1241
L48 L47 L46 L45 L44 L43
L64 L63 L62 L61 L60 L59
Stores conditions for up to numbers 49 to 64
Station number information for host station
Stores station number (0 to 64) Allows a local station to confirm its own station number
D9244 SD1244
Number of link device stations
Stores number of slave stations Indicates the number of slave stations in one loop.
Stores the number of times the following transmission errors have been detected: CRC, OVER, AB. IF Count is made to a maximum of FFFFH. RESET to return the count to 0.
Number of times communications errors detected
Stores cumulative total of receive errors
11 - 96 11 - 96

Special Register for Modification
Name Meaning Details Corresponding
Stores conditions for up to numbers 1 to 16
Stores the local station number which is in STOP or PAUSE mode.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Stores conditions for up to numbers 17 to 32
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
SD1249
L32 L31 L30 L29 L28 L27
Local station operation status
L48 L47 L46 L45 L44 L43
The bit corresponding to the station number which is in STOP or PAUSE mode, becomes "1". Example: When local stations 7 and 15 are in STOP mode,
L64 L63 L62 L61 L60 L59
Stores conditions for up to numbers 33 to 48
Stores conditions for up to numbers 49 to 64
bits 6 and 14 of SD1248 become "1", and when SD1248 is monitored, its value is "16448 (4040H)".
Stores conditions for up to numbers 1 to 16
Stores the local station number other than the host, which is in error.
Stores conditions for up to numbers 17 to 32
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L16 L15 L14 L13 L12 L11
L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
SD1253
L32 L31 L30 L29 L28 L27
Local station error conditions
L48 L47 L46 L45 L44 L43
Stores conditions for up to numbers 33 to 48
The bit corresponding to the station number which is in error, becomes "1". Example: When local station 12 is in error, bit 11 of SD1252
L64 L63 L62 L61 L60 L59
D9254 SD1254
Stores conditions for up to numbers 49 to 64
becomes "1", and when SD1252 is monitored, its value is "2048 (800H) ".
Number Name Meaning Explanation
SD1300 D9100
SD1302 D9102
SD1303 D9103
Bit pattern in units of 16 points, indicating the modules whose fuses have blown 0: No blown fuse 1: Blown fuse present
SD1305 D9105
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 1 (YC0) 0 1 (Y80) SD1300
0 0 1 (Y1F0) 0 1 (Y1A) SD1301 0 0
0 0 1 (Y1F B0) 0 SD1331 0 0 0 1 (Y1F 30) 0
Indicates a blown fuse • Not cleared even if the blown fuse is replaced with a new one. This flag is cleared by error resetting operation.
Bit pattern in units of 16 points, indicating the modules whose external power supply has been disconnected 0: External power supply disconnected 1: External power supply is not disconnected
The module number (in units of 16 points) whose external power supply has been disconnected is input as a bit pattern. (If the module numbers are set by parameter, the parameter-set numbers are used.)
External power supply disconnected module (For future expansion)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 1 0 1
S (Error) New QCPU Remote
0 0 1 0 1 0 0
SD1381 0 0 1 0 1 0
Indicates a blown fuse

Number Name Meaning Explanation
SD1400 D9116
SD1402 D9118
Bit pattern, in units of 16 points, indicating the modules with verification errors. 0: No I/O verification errors 1: I/O verification error present
SD1404 D9120
SD1405 D9121
I/O module verification error
1 ( ) 1 ( )
0 D9116
SD1407 D9123
0 D9117 0 0
0 0 1 ( )
0 D9123 0
Indicates an I/O module verification error • Not cleared even if the blown fuse is replaced with a new one. This flag is cleared by error resetting operation.
(13) For redundant systems (Host system CPU information 1) for Q4AR only SD1510 to SD1599 are only valid for redundant systems. They are all set to 0 for standalone systems.

1 Host system CPU information is stored.

Special Register List (Continue) (14) For redundant systems (Other system CPU information 1) for Q4AR only SD1600 to SD1659 is only valid during the back up mode for redundant systems, and refresh cannot be done when in the separate mode. When a standalone system SD1600 to SD1699 are all 0.
Number Name Meaning Explanation Set by (When set)
SD1600 Diagnosis error Diagnosis error
code.
Diagnosis error occurrence time
Diagnosis error occurrence time
SD1605
SD1606
SD1607
SD1608
SD1610
SD1611
SD1612
SD1613
SD1614
Q4AR
SD1615
SD1616
SD1617
SD1618
SD1619
SD1621
SD1622
SD1623
SD1624
SD1625
SD1626
SD1650 Switch status CPU switch status
SD1651 LED status CPU-LED status
SD1653 CPU operation status
1 Stores other system CPU self-diagnosis information and system information. 2 Shows the special register (SD ) for the host system CPU.
SD1700 to SD1799 is valid only for redundant systems. These are all 0 for standalone systems.

Trucking error detection count • Make it the trucking error detection +1. S (Error occurrence) New Q4AR
2 Shows the special register (SD ) for the host system CPU.

APPENDICES
APPENDIX 1 Error Code Return to Origin During General Data Processing
The CPU module returns an error code to the general data processing request origin when an error occurs and there is a general data processing request form the peripheral equipment, intelligent function module, or network system. If an error occurs when a general data processing is requested from the peripheral devices, intelligent function module, and network system.
POINT This error code is not an error that is detected by the CPU module self-diagnosis function, so it is not stored in the special relay (SD0). When the request origin is a GX Developer, a message or an error code is displayed. When the request origin is an intelligent function module or network system, an error is returned to the process that was requested.
These error codes differs depending on the error No. of the location the error was detected. The following table shows the relationship between the error detection location and the error code.
CPU module 4000H to 4FFFH Refer to Appendix 1.2.
module 7000 H to 7FFF H User's manuals of intelligent function module
Network system F000 H to FFFF H Q Corresponding MELSECNET/H Network System
Reference Manual
App - 1 App - 1

APPENDIX 1.2 Description of the errors of the error codes (4000H to 4FFFH)
The error contents of the error codes (4000H to 4FFFH) detected by the CPU module and the messages displayed by the GX Developer are shown below.
item Error description Countermeasure
4000H Sum check error Check the connection status of the connection cable with the CPU module
4001H Remote request that is not handled was executed. Check the requested remote operation.
Command for which a global request cannot be performed was executed. Check the requested command.
4004H CPU module cannot execute the request contents because it is in system protect Turn off the CPU module system protect switch.
4005H The volume of data handled according to the specified request is too large.
Reduce the volume of data to that which can be processed at the specified request.
4006H The password cannot be deleted. Delete the set password.
The CPU module is not BUSY (The buffer is not vacant). After the free time has passed, reexecute the request.
4010H The CPU module is running to the request contents cannot be executed. Execute after setting the CPU module to STOP status.
CPU mode error The CPU module is not in the STEP-RUN status so the request contents cannot be executed.
Execute after setting the CPU module to STEP-RUN status.
App - 2 App - 2
Error code (hexadecimal) · Error · CPU related error

item Error description Countermeasure
4021H The specified drive memory does not exist or there is an error. Check the specified drive memory status.
4022H The file with the specified file name or file No. does not exist. Check the specified file name and file No.
4023H The file name and file No. of the specified file do not match. Delete the file and then recreate the file.
4024H The specified file cannot be handled by a user. Do not access the specified file.
Forcefully execute the request forcibly. Or reexecute the request after the processing from the other location has ended.
4025H The specified file is processing the request from a different location.
4026H The keyword specification set in the corresponding drive memory is required.
Access by specifying the keyword set in the corresponding drive memory. 4027H The specified range exceeds the file range. Check the specified range and access within that range.
CPU file related error
4028H The same file already exists. Forcefully execute the request forcibly. Or reexecute after changing the file name.
Revise the specified file contents. Or reexecute after cleaning up and reorganizing the specified drive memory.
4029H The specified file capacity cannot be obtained.
402BH The request contents cannot be executed in the specified drive memory.
Do not execute a request for a specified drive memory in which an error has occurred.
Currently the request contents cannot be executed. Reexecute after the free wait time has passed.
4030H The specified device name cannot be handled. Check the specified device name. 4031H The specified device No. is outside the range. Check the specified device No.
CPU device specified error
4032H There is a mistake in the specified device qualification. Check the specified device qualification method.
Writing cannot be done because the specified device is for system use.
Do not write the data in the specified device, and do not turn on or off.
4040H The request contents cannot be executed in the specified intelligent function module.
Do not conduct a request for a specified intelligent function module in which an error has occurred.
4041H The access range exceeds the buffer memory range of the specified intelligent function module.
Check the header address and access number of points and access using a range that exists in the intelligent function module.
Intelligent function module specification error
4042H The specified intelligent function module cannot be accessed.
Check that the specified intelligent function module is operating normally.
4043H The intelligent function module does not exist in the specified position.
Check the header I/O No. of the specified intelligent function module.
4044H A control bus error has occurred. Check that there is no error in the intelligent function module or in the hardware of another module.
4045H The setting required to conduct simulation has not been made. Conduct a simulation setting.
The device header or number of points in the simulation is not in 16point unit.
Check the device header No. or number of points and correct them to 16 point units.
Error code (hexadecimal) · Error

item Error description Countermeasure
4050H The request contents cannot be executed because the memory card write protect switch is on.
Turn off the memory card write protect switch.
4051H The specified device memory cannot be accessed.
4052H The specified file attribute is read only so the data cannot be written.
Do not write data in the specified file. Or change the file attribute.
Check the specified drive memory. Or reexecute write after changing the corresponding drive memory.
4053H An error occurred when writing data to the specified drive memory.
Check the specified drive memory. Or re-erase after replacing the corresponding drive memory.
An error occurred when deleting the data in the specified drive memory.
4060H The monitor condition registration CPU module system area is already being used by another piece of equipment.
Reexecute monitor after the monitor by the other equipment has completed. Or increase the system area of the program memory using the format with option. 4061H Communication failed. Execute a re-communication.
Do not conduct monitor detail condi-tions from the specified equipment. Or reexecute monitoring after deleting the monitor detail conditions of the other equipment.
4062H The monitor detail condition is already being used and monitored by another piece of equipment.
4063H The number of the file lock registrations exceeds 16. Reduce the number of registrations to 16 or less.
4064H There is a problem with the specified contents. Check the specified contents.
4065H The device allocation information differs from the parameter.
Check the parameter. Or check the data.
4066H A keyword that differs from the keyword set in the specified driver memory has been specified. Check the specified keyword.
4067H The specified monitor file cannot be obtained. Conduct monitor after obtaining the monitor file.
4068H Registration/deletion cannot be conducted because the specified command is being executed.
Reexecute the command after the request from the other equipment has been completed.
4069H The conditions have already been reached by the device match.
Check the monitor conditions. Or reconduct monitor registration and execute monitor.
A drive other than Nos. 1 to 3 has been specified. Check the specified drive and specify the correct drive.
4070H Circuit inquiry Program before correction and the registration program differ.
Check the registration program and make the programs match. 4080H Data error Check the requested data contents. 4081H The sort subject cannot be detected. Check the data to be searched.
4082H The specified command is executing and therefore cannot be executed.
Reexecute the command after the request from the other equipment is completed.
Trying to execute a program that is not registered in the parameter. Register the program to be executed in the parameter.
App - 4 App - 4

item Error description Countermeasure
4084H The specified pointer P, I cannot be detected. Check the data to be searched.
4085H Pointer P, I cannot be specified because the program is not specified in the parameter.
Specify pointer P, I after registering the program to be executed in the parameter. 4086H Pointer P, I has already been added. Check the pointer No. to be added and make correction. 4087H Trying to specify too many pointers. Check the specified pointer and make a correction.
4088H The specified step No. was not in the instruction header. Check the specified step No. and make a correction.
4089H An END instruction was inserted/deleted while the CPU module was running.
Conduct Insert/removal after the CPU module has stopped.
408AH The file capacity was exceeded by the write during Run. Write the program after the CPU module has stopped.
The remote request cannot be executed. Reexecute after the CPU module is in a status where the mode request can be executed. 4090H The block breakpoint number was exceeded. Check the number of settings and make a correction.
4091H There is a mistake in the block breakpoint registration number.
Check the number of registrations and make a correction.
4092H The step breakpoint number has been exceeded.
Check the number of registrations and make a correction.
4093H There is a mistake in the step breakpoint registration number.
Check the number of registrations and make a correction.
4094H Tried to execute a request during block continuous processing. Reconduct the request after the processing has ended.
4095H Tried to execute a request during block forced execution processing. Reconduct the request after the processing has ended.
4096H Tried to execute a request during step continuous processing. Reconduct the request after the processing has ended.
4097H Tried to execute a request during step forced execution processing. Reconduct the request after the processing has ended.
Online registration errors during SFC STEP- RUN
4098H Tried to execute a request during one step continuous processing. Reconduct the request after the processing has ended.
4099H Tried to execute a request during one step forced execution processing. Reconduct the request after the processing has ended.
409AH Tried to execute a request during block forced end processing. Reconduct the request after the processing has ended.
409BH Tried to execute a request during step forced end processing. Reconduct the request after the processing has ended.
409CH Tried to execute a request during hold step reset processing. Reconduct the request after the processing has ended.
409DH A block No. that has not been created or that exceeds the range has been specified. Check the setting contents and make a correction.
409EH A step No. that was not created was specified. Check the setting contents and make a correction.
The specified number of cycles is outside the range.
Check the number of registrations and make a correction.
App - 5 App - 5
Error code (hexadecimal) · Error · Other errors

item Error description Countermeasure
40A0H A block No. outside the range was specified. Check the setting contents and make a correction.
40A1H A number of blocks that exceeds the range was specified. Check the number of settings and make a correction.
40A2H A step No. that is outside the range was specified. Check the setting contents and make a correction.
SFC device specification error
40A3H A number of steps that exceeds the range was specified. Check the number of settings and make a correction.
40A4H A sequence step No. outside the range was specified. Check the setting contents and make a correction.
40A5H The specified device was outside the range. Check the number of settings and make a correction.
There is a mistake in the block specification pattern or the step specification pattern. Check the setting contents and make a correction.
40B0H The wrong drive was specified. Check the setting contents and make a correction. 40B1H The specified program does not exist. Check the specified file name and make a correction.
40B2H The specified program was not an SFC program. Check the specified file name and make a correction.
SFC file related error
There was an SFC dedicated instruction in the write during run area. Check the setting contents and make a correction.
Increase the free space of the specified drive. Optimize the specified drive to increase continuous free areas. 41D1H The file pointer is insufficient. Specify the correct file pointer. 41D5H The file of the same name exists. Change the file name.
41D0H The route directory has no free space.
41DFH The disk is write-protected. Cancel the write protection of the disk and execute again. 41E0H The drive does not respond. Check for the specified drive. If it exists, check its status. 41E1H The address or sector is not found. Check if the target is a ROM drive or not. 41E4H The file cannot be accessed properly. Execute again after resetting the CPU module. 41E8H The drive format information is illegal. Format the target drive.
41E9H At the time of file access, time-out occurred during waiting for access. Execute again after some time.
41EBH The path name is too long. Check the length of the path name. 41ECH The disk is logically broken. Change the specified drive.
41EDH An attempt to make a file continuous failed. (There are enough free file areas, which cannot be taken continuously.)
Optimize the specified drive to increase continuous free areas.
41F2H The specified drive is ROM. Check the specified drive. (Format it for RAM.)
41FBH The same starting source has already opened the specified file. Check if it is being processed by another application.
41FCH An attempt was made to erase the mounted drive. Execute again after dismounting the drive.
41FDH The Flash ROM is not formatted. Erase the specified drive. 41FEH The memory card is not inserted. Insert or reinsert the memory card. 41FFH
The memory card type differs. Check the memory card type.
(1) The specified station could not be accessed
because a routing parameter was not set in the related station. (2) Though routing via the multiple CPU system
(1) Set the routing parameter for accessing the specified
station in the related station. (2) Try after a while. Or check if the system relaying the
is attempted, the control CPU of the network module that relays the data is not active.
data is active, then start communication.
4A01H The network with the No. set in the routing parameter does not exist.
Check the routing parameter set in the related station and make a correction.
Cannot access the specified station. Check if an error has occurred in the network module and if the module is offline.
Check if an error has occurred in the specified access destination or in a relay station to the access station and if so take countermeasures.
4B00H Object related error
An error occurred in the access destination or in a relay station.

APPENDIX 2 External Dimensions
APPENDIX 2.1 CPU module


(1) Power Supply Module (Q61P-A1, Q61P-A2, Q62P, Q63P)


App - 7 App - 7

(2) Power Supply Module (Q64P)


(3) Power Supply Module (Q61SP)

POWER
INPUT
Q61SP
OUTPUT 5VDC 2A
ERR. 24VDC 0.5A
(FG)
(LG)
INPUT
100240V AC
MITSUBISHI
Unit: mm (inch)
App - 8 App - 8
50/60Hz 40VA 100-240VAC

(4) Power Supply Module (A1S61PN, A1S62PN, A1S63P)


(0.26)
App - 9 App - 9

APPENDIX 2.3 Main base unit
(1) Main Base Unit (Q33B)

(0.30)
44.1 (1.74)
(2) Main Base Unit (Q35B)

(0.30)
44.1 (1.74)
(3) Main Base Unit (Q38B)

I/O1 I/O0 CPU I/O5 I/O4 I/O3 I/O2 I/O6 I/O7
(0.30)
44.1 (1.74)
App - 10 App - 10

(4) Main Base Unit (Q312B)

I/11 I/10 I/09 I/08 I/07 I/06 I/05 I/04 I/03 I/02 I/01 I/00 CPU POWER
App - 11 App - 11

APPENDIX 2.4 Slim type main base unit
(1) Main Base Unit (Q32SB)

(0.30)
(0.33) (1.74)

(0.30)
(1.74) (0.33)

(0.30)
App - 12 App - 12

APPENDIX 2.5 Extension base unit
(1) Extension Base Unit (Q52B)
4-mounting screws (M4 14)



App - 13 App - 13

(4) Extension Base Unit (Q65B)


(6) Extension Base Unit (Q612B)

I/O11 I/O10 I/O9 I/O8 I/O7 I/O6 I/O5 I/O4 I/O3 I/O2 I/O1 I/O0
App - 14 App - 14

(7) Extension Base Unit (QA1S65B)


App - 15 App - 15

APPENDIX 3 Upgraded Functions of High Performance Model QCPU
The High Performance model QCPU is upgraded to add functions and change the specifications. The functions and specifications that can be used by the High Performance model QCPU change depending on the function version/serial number. APPENDIX 3.1 Specification comparison

: Available, : N/A APPENDIX 3.2 Function comparison
Serial No. of CPU Module Function Version A Function Version B
: Available, : N/A
For function details, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals).

APPENDIX 3.3 Added functions and the corresponding GX Developer versions

: Available, : N/A, — : Function not related to GX Developer
App - 17 App - 17

Please confirm the following product warranty details before starting use. 1. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the dealer or Mitsubishi Service Company. Note that if repairs are required at a site overseas, on a detached island or remote place, expenses to dispatch an engineer shall be charged for. [Gratis Warranty Term]
The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range]
(1) The range shall be limited to normal use within the usage status, usage methods and usage environment, etc.,
which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product. (2) Even within the gratis warranty term, repairs shall be charged for in the following cases.
1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design. 2. Failure caused by unapproved modifications, etc., to the product by the user. 3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided. 4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced. 5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage. 6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi. 7. Any other failure found not to be the responsibility of Mitsubishi or the user. 2. Onerous repair term after discontinuation of production (1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.
Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc. (2) Product supply (including repair parts) is not possible after production is discontinued. 3. Overseas service Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ. 4. Exclusion of chance loss and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to damages caused by any cause found not to be the responsibility of Mitsubishi, chance losses, lost profits incurred to the user by Failures of Mitsubishi products, damages and secondary damages caused from special reasons regardless of Mitsubishi's expectations, compensation for accidents, and compensation for damages to products other than Mitsubishi products and other duties. 5. Changes in product specifications The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice. 6. Product application (1) In using the Mitsubishi MELSEC programmable logic controller, the usage conditions shall be that the application will
not lead to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault. (2) The Mitsubishi general-purpose programmable logic controller has been designed and manufactured for applications
in general industries, etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or National Defense purposes shall be excluded from the programmable logic controller applications. Note that even with these applications, if the user approves that the application is to be limited and a special quality is not required, application shall be possible. When considering use in aircraft, medical applications, railways, incineration and fuel devices, manned transport devices, equipment for recreation and amusement, and safety devices, in which human life or assets could be greatly affected and for which a particularly high reliability is required in terms of safety and control system, please consult with Mitsubishi and discuss the required specifications.

EUROPEAN REPRESENTATIVES
EUROPEAN REPRESENTATIVES
EUROPEAN REPRESENTATIVES
MITSUBISHI ELECTRIC EUROPE EUROPE B.V. Gothaer Straße 8 D-40880 Ratingen Phone: +49 (0) 21 02 / 486-0 Fax: +49 (0) 21 02 / 4 86-11 20 e mail: megfamail@meg.mee.com MITSUBISHI ELECTRIC FRANCE EUROPE B.V. 25, Boulevard des Bouvets F-92741 Nanterre Cedex Phone: +33 1 55 68 55 68 Fax: +33 1 55 68 56 85 e mail: factory.automation@fra.mee.com MITSUBISHI ELECTRIC UK EUROPE B.V. Travellers Lane GB-Hatfield Herts. AL10 8 XB Phone: +44 (0) 1707 / 27 61 00 Fax: +44 (0) 1707 / 27 86 95 MITSUBISHI ELECTRIC ITALY EUROPE B.V. Via Paracelso 12 I-20041 Agrate Brianza (MI) Phone: +39 039 6053 1 Fax: +39 039 6053 312 e mail: factory.automation@it.mee.com MITSUBISHI ELECTRIC SPAIN EUROPE B.V. Carretera de Rubí 76-80 E-08190 Sant Cugat del Vallés Phone: +34 9 3 / 565 3131 Fax: +34 9 3 / 589 2948 e mail: industrial@sp.mee.com MITSUBISHI ELECTRIC JAPAN CORPORATION Office Tower “Z” 14 F 8-12,1 chome, Harumi Chuo-Ku Tokyo 104-6212 Phone: +81 3 6221 6060 Fax: +81 3 6221 6075 MITSUBISHI ELECTRIC USA AUTOMATION 500 Corporate Woods Parkway Vernon Hills, IL 60061 Phone: +1 847 / 478 21 00 Fax: +1 847 / 478 22 83
GEVA AUSTRIA Wiener Straße 89 A-2500 Baden Phone: +43 (0) 2252 / 85 55 20 Fax: +43 (0) 2252 / 488 60 e mail: [email protected] TEHNIKON BELARUS Oktjabrskaya 16/5, Ap 704 BY-220030 Minsk Phone: +375 (0) 17 / 22 75 704 Fax: +375 (0) 17 / 22 76 669 e mail: tehnikon@belsonet.net Getronics b.v. BELGIUM Control Systems Pontbeeklaan 43 B-1731 Asse-Zellik Phone: +32 (0) 2 / 467 17 51 Fax: +32 (0) 2 / 467 17 45 e mail: infoautomation@getronics.com TELECON CO. BULGARIA 4, A. Ljapchev Blvd. BG-1756 Sofia Phone: +359 (0) 2 / 97 44 05 8 Fax: +359 (0) 2 / 97 44 06 1 e mail: — INEA CR d.o.o. CROATIA Drvinje 63 HR-10000 Zagreb Phone: +385 (0) 1 / 36 67 140 Fax: +385 (0) 1 / 36 67 140 e mail: — AutoCont CZECHIA Control Systems s.r.o. Nemocnicni 12 CZ-702 00 Ostrava 2 Phone: +420 59 / 6152 111 Fax: +420 59 / 6152 562 e mail: [email protected] louis poulsen DENMARK industri & automation Geminivej 32 DK-2670 Greve Phone: +45 (0) 43 / 95 95 95 Fax: +45 (0) 43 / 95 95 91 e mail: lpia@lpmail.com UTU Elektrotehnika AS ESTONIA Pärnu mnt.160i EE-11317 Tallinn Phone: +372 (0) 6 / 51 72 80 Fax: +372 (0) 6 / 51 72 88 e mail: [email protected] Beijer Electronics OY FINLAND Ansatie 6a FIN-01740 Vantaa Phone: +358 (0) 9 / 886 77 500 Fax: +358 (0) 9 / 886 77 555 e mail: [email protected] PROVENDOR OY FINLAND Teljänkatu 8 A 3 FIN-28130 Pori Phone: +358 (0) 2 / 522 3300 Fax: +358 (0) 2 / 522 3322 e mail: — UTECO A.B.E.E. GREECE 5, Mavrogenous Str. GR-18542 Piraeus Phone: +302 (0) 10 / 42 10 050 Fax: +302 (0) 10 / 42 12 033 e mail: [email protected] Meltrade Automatika Kft. HUNGARY 55, Harmat St. H-1105 Budapest Phone: +36 (0)1 / 2605 602 Fax: +36 (0)1 / 2605 602 e mail: [email protected]
MITSUBISHI ELECTRIC IRELAND EUROPE B.V. – Irish Branch Westgate Business Park IRL-Dublin 24 Phone: +353 (0) 1 / 419 88 00 Fax: +353 (0) 1 / 419 88 90 e mail: sales.info@meir.mee.com SIA POWEL LATVIA Lienes iela 28 LV-1009 Riga Phone: +371 784 / 22 80 Fax: +371 784 / 22 81 e mail: [email protected] UAB UTU POWEL LITHUANIA Savanoriu pr. 187 LT-2053 Vilnius Phone: +370 (0) 52323-101 Fax: +370 (0) 52322-980 e mail: [email protected] INTEHSIS SRL MOLDOVA, REPUBLIC OF Cuza-Voda 36/1-81 MD-2061 Chisinau Phone: +373 (0)2 / 562 263 Fax: +373 (0)2 / 562 263 e mail: intehsis@mdl.net Getronics b.v. NETHERLANDS Control Systems Donauweg 2 B NL-1043 AJ Amsterdam Phone: +31 (0) 20 / 587 67 00 Fax: +31 (0) 20 / 587 68 39 e mail: info.gia@getronics.com Beijer Electronics AS NORWAY Teglverksveien 1 N-3002 Drammen Phone: +47 (0) 32 / 24 30 00 Fax: +47 (0) 32 / 84 85 77 e mail: [email protected] MPL Technology Sp. z o.o. POLAND ul. Sliczna 36 PL-31-444 Kraków Phone: +48 (0) 12 / 632 28 85 Fax: +48 (0) 12 / 632 47 82 e mail: [email protected] SiriusTrading&Servicessrl ROMANIA Bd. Lacul Tei nr. 1 B RO-72301 Bucuresti 2 Phone: +40 (0) 21 / 201 7147 Fax: +40 (0) 21 / 201 7148 e mail: [email protected]
GTS TURKEY Darülaceze Cad. No. 43 KAT: 2 TR-80270 Okmeydani-Istanbul Phone: +90 (0) 212 / 320 1640 Fax: +90 (0) 212 / 320 1649 e mail: gts@turk.net CSC Automation Ltd. UKRAINE 15, M. Raskova St., Fl. 10, Office 1010 UA-02002 Kiev Phone: +380 (0) 44 / 238-83-16 Fax: +380 (0) 44 / 238-83-17 e mail: [email protected]
CBI Ltd SOUTH AFRICA Private Bag 2016 ZA-1600 Isando Phone: +27 (0) 11/ 928 2000 Fax: +27 (0) 11/ 392 2354 e mail: cbi@cbi.co.za
TEXEL Electronics LTD. ISRAEL Box 6272 IL-42160 Netanya Phone: +972 (0) 9 / 863 08 91 Fax: +972 (0) 9 / 885 24 30 e mail: texel_me@netvision.net.il
AVTOMATIKA SEVER RUSSIA Krapivnij Per. 5, Of. 402 RU-194044 St Petersburg Phone: +7 812 / 1183 238 Fax: +7 812 / 3039 648 e mail: [email protected] CONSYS RUSSIA Promyshlennaya St. 42 RU-198099 St Petersburg Phone: +7 812 / 325 36 53 Fax: +7 812 / 325 36 53 e mail: [email protected] ELEKTROSTYLE RUSSIA Ul Garschina 11 RU-140070 Moscowskaja Oblast Phone: +7 095/ 261 3808 Fax: +7 095/ 261 3808 e mail: — ICOS RUSSIA Industrial Computer Systems Zao Ryazanskij Prospekt 8a, Office 100 RU-109428 Moscow Phone: +7 095 / 232 - 0207 Fax: +7 095 / 232 - 0327 e mail: [email protected] NPP Uralelektra RUSSIA Sverdlova 11a RU-620027 Ekaterinburg Phone: +7 34 32 / 53 27 45 Fax: +7 34 32 / 53 27 45 e mail: [email protected] STC Drive Technique RUSSIA Poslannikov Per. 9, str.1 RU-107005 Moscow Phone: +7 095 / 786 21 00 Fax: +7 095 / 786 21 01 e mail: [email protected]
ACP Autocomp a.s. SLOVAKIA Chalupkova 7 SK-81109 Bratislava Phone: +421 (02) / 5292-22 54, 55 Fax: +421 (02) / 5292-22 48 e mail: [email protected]
INEA d.o.o. SLOVENIA Stegne 11 SI-1000 Ljubljana Phone: +386 (0) 1-513 8100 Fax: +386 (0) 1-513 8170 e mail: [email protected]
Beijer Electronics AB SWEDEN Box 426 S-20124 Malmö Phone: +46 (0) 40 / 35 86 00 Fax: +46 (0) 40 / 35 86 02 e mail: [email protected]
ECONOTEC AG SWITZERLAND Postfach 282 CH-8309 Nürensdorf Phone: +41 (0) 1 / 838 48 11 Fax: +41 (0) 1 / 838 48 12 e mail: [email protected]
MITSUBISHI ELECTRIC Gothaer Straße 8 Phone: +49 2102 486-0 Fax: +49 2102 486-7170 www.mitsubishi-automation.de D-40880 Ratingen Hotline: +49 1805 000-765 megfa-mail@meg.mee.com www.mitsubishi-automation.com
Pages referenced in this manual — manufacturer, support and downloads.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| 1000 | Run mode suspended or failure of main CPU module (1) Malfunctioning due to noise or other reason (2) Hardware fault | (1) Measure noise level. (2) Reset and establish the RUN status again. If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.136 |
| 1009 | Failure of the power supply module, CPU module, main base unit, extension base unit or extension cable is detected. | p.136 | |
| 1010 | Entire program was executed without the execution of an END instruction. (1) When the END instruction is executed it is read as another instruction code, e.g. due to noise. (2) The END instruction has been changed to another instruction code somehow. | (1) Measure noise level. (2) Reset and establish the RUN status again. If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.136 |
| 1101 | Error in internal RAM/program memory where CPU module sequence program is stored. | This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.136 |
| 1102 | Error in RAM used as CPU module work area. | p.136 | |
| 1103 | Internal CPU module device error. | p.136 | |
| 1104 | RAM Address error in CPU module. | p.136 | |
| 1105 | CPU shared memory fault | (1) Measure noise level. (2) Reset and establish the RUN status again. If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.136 |
| 1200 | The circuit that performs CPU internal index modification is not operating properly. | This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.136 |
| 1201 | Internal CPU module hardware (logic) does not operate normally. | p.136 | |
| 1202 | The circuit that executes sequence processing in the CPU module does not operate properly. | p.136 | |
| 1203 | The operation circuit that conducts index modification in the CPU module is not operating properly. | This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.136 |
| 1204 | The hardware (logic) in the CPU us not operating properly. | p.136 | |
| 1205 | The operation circuit that conducts sequence processing in the CPU in not operating properly. | p.136 | |
| 1206 | The DSP operation circuit in the CPU is not operating properly. | p.136 | |
| 1300 | There is an output module with a blown fuse. | (1) Check ERR. LED of the output modules and replace the module whose LED is lit. (2) Read the common error information with the peripheral device and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1". | p.136 |
| 1310 | An interruption has occurred although there is no interrupt module. | One of the individual modules is experiencing hardware problems, so check the modules. Contact your nearest Mitsubishi representative and explain the problem with the defective module. | p.136 |
| 1401 | • There was no response from the intelligent function module during initial communication stage. • The size of the buffer memory of the intelligent function module is wrong. | The CPU module is experiencing hardware problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1402 | The intelligent function module was accessed in the program, but there was no response. | This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. | p.138 |
| 1403 | • There was no response from the intelligent function module when the END instruction is executed. • An error is detected at the intelligent function module. | The intelligent function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1411 | When performing a parameter I/O allocation a special function module could not be accessed during initial communications. On error occurring, the head I/O number of the corresponding special function module is stored in the common information. | A special function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1412 | The FROM/TO instruction set could not be executed, due to a system bus error with a special function module. On error occurring, the program error location is stored in the individual information. | p.138 | |
| 1413 | The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration. | (1) Change the High Performance model QCPU of function version A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1414 | Fault of the loaded module was detected. The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration. | (1) Change the High Performance model QCPU of function version A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1415 | Fault of the main or extension base unit was detected. | An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1416 | System bus fault was detected at PLC power-on or CPU module reset. | p.138 | |
| 1421 | Hardware fault at the system management module AS92R. | This is experiencing hardware problems. Contact your nearest Mitsubishi representative. | p.138 |
| 1500 | A momentary power supply interruption has occurred. The power supply went off. | Check the power supply. | p.138 |
| 1510 | The 5 VDC supplied to one of the two power-supply modules in the redundant system extension base unit has dropped below 85% of the rated voltage. | Check the supply voltage of the power supply module. If the voltage is abnormal then replace the power supply module. | p.138 |
| 1520 | The 5 VDC supplied to the power-supply modules in the extension base unit has dropped below 80% of the rated voltage. | p.138 | |
| 1530 | The 24 VDC power supplied to the system management module AS92R has dropped below 85% of the rated voltage. | Check the power supply. | p.138 |
| 1600 | (1) Voltage in the CPU module battery. (2) The CPU module battery is not connected. | (1) Change the battery. (2) If the battery is for program memory, standard RAM or for the back-up power function, install a lead connector. | p.138 |
| 1601 | Voltage of the battery on memory card 1 has dropped below stipulated level. | Change the battery. | p.138 |
| 1602 | Voltage of the battery on memory card 2 has dropped below stipulated level. | Change the battery. | p.138 |
| 2000 | I/O module information power ON is changed. I/O module (or special function module) not installed properly or installed on the base unit. | Read the error common information at the peripheral device, and check and/or change the module that corresponds to the numerical value (module number) there. Alternatively, monitor the special registers SD1400 to SD1431 at a peripheral device, and change the fuse at the output module whose bit has a value of "1". | p.138 |
| 2100 | Slot loaded with the QI60 is set to other than the Inteli (intelligent function module) or Interrupt (interrupt module) in the parameter I/O assignment. | Make setting again to match the parameter I/O assignment with the actual loading status. | p.140 |
| 2101 | 13 or more A-series special function modules (except for the QI60, A1SI61) that can initiate an interrupt to the CPU module have been installed. | Keep the number of A-series special function modules that can initiate an interrupt (except for the QI60, A1SI61) to 12 or fewer. | p.140 |
| 2102 | 7 or more A1SD51S have been installed. | Keep the number of A1SD51S to 6 or fewer. | p.140 |
| 2103 | (1) Two or more QI60/A1SI61 modules are loaded in a single-PLC system. (2) Two or more QI60/A1SI61 modules are set to the same control PLC in a multiple CPU system. (3) Two or more A1SI61 modules are loaded in a multiple CPU system. | (1) Reduce the number of QI60/A1SI61 modules loaded in the single-PLC system to one. (2) Change the number of QI60/A1SI61 modules set to the same control PLC to only one in the multiple CPU system. (3) Reduce the number of A1SI61 modules to only one in the multiple CPU system. When using an interrupt module with each QCPU in a multiple CPU system, change it for the QI60. (Use one A1SI61 module + max. three QI60 modules or only the QI60 modules.) | p.140 |
| 2104 | At the MELSECNET/MINI auto refresh parameter settings, the module allocation that was set is different from the actual module models at the station numbers in the link system. | Reset the parameter MELSECNET/MINI auto refresh unit module allocation setting so that it conforms to the station number of the module that is actually linked. | p.140 |
| 2105 | There are too many special function modules that can use dedicated instructions allocated (number of modules installed). (The total of the figures indicated below is above 1344.) (Number of AD59 modules installed × 5) (Number of AD57 (S1)/AD58 modules installed × 8) (Number of AJ71C24 (S3/S6/S8) modules installed × 10) (Number of AJ71UC24 modules installed × 10) (Number of AJ71C21 (S1) modules installed × 29) (Number of AJ71PT32-S3/AJ71T32-S3 modules installed × 125) (Number of AJ71QC24 (R2, R4) modules installed × 29) (Number of AJ71ID1 (2)-R4 modules installed × 18) (Number of AD75 modules installed × 12) Total > 1344 | Reduce the number of special function modules installed. : When the expansion mode is used. | p.140 |
| 2106 | • Five or more MELSECNET/H modules are loaded in a whole multiple CPU system. • Five or more Q series Ethernet interface modules are loaded in a whole multiple CPU system. | Reduce the number of modules to four or less in the whole multiple CPU system. | p.140 |
| 2107 | Head X/Y set in the parameter I/O allocation settings is also the head X/Y for another module. | Reset the parameter I/O allocation setting to conform with the actual status of the special function modules. | p.140 |
| 2108 | (1) Network module A1SJ71LP21, A1SJ71BR11, A1SJ71AP21 , A1SJ71AR21, or A1SJ71AT2B dedicated for the A2USCPU has been installed. (2) Network module A1SJ71QLP21 or A1SJ71QBR11 dedicated for the Q2AS has been installed. | Change network module to QJ71LP21 or QJ71BR11. | p.140 |
| 2109 6 | The control system and standby system module configurations are different when a redundant system is in the backup mode. | Check the module configuration of the standby system. | p.140 |
| 2110 | Station not loaded was specified using the instruction whose target was the PLC share memory. | Read the individual information of the error, check the program corresponding that value (program error location), and make correction. | p.142 |
| 2111 | The location designated by a link direct device (J \ ) is not a network module. | p.142 | |
| 2112 | (1) The location designated by a special function module dedicated instruction is not a special function module. (2) The network number specified by the network dedicated instruction does not exist, or the network module is not the corresponding one. (3) Alternatively, it is not the relevant special function module. | Read error individual information, then check and edit the special function module (Network module) dedicated instruction that corresponds to the numerical value there (program error location). | p.142 |
| 2113 | The one specified in the network-dedicated instruction is not a network module, or a relay target network does not exist. | p.142 | |
| 2114 | An instruction, which on execution specifies other stations, has been used for specifying the host station. (An instruction that does not allow the host station to be specified). | Read the individual information of the error, check the program corresponding that value (program error location), and make correction. | p.142 |
| 2115 | An instruction, which on execution specifies the host station, has been used for specifying other stations. (An instruction that does not allow other stations to be specified). | p.142 | |
| 2116 | • An instruction that does not allow the module under the control of another station to be specified is being used for a similar task. • Instruction was executed for the A or QnA module under control of another station. | p.142 | |
| 2117 | A CPU module that cannot be specified in the instruction dedicated to the multiple CPU system was specified. | p.142 | |
| 2120 | The location of Q | Check the location of the base unit. | p.142 |
| 2121 | The CPU module is installed at other than the CPU slot or slots 0 to 2. | Check the loading position of the CPU module and reinstall it at the correct slot. | p.142 |
| 2126 | CPU module locations in a multiple CPU system are either of the following. (1) There are empty slots between the QCPU and QCPU/motion controller. (2) Modules other than the QCPU (including the motion controller) modules are loaded between the QCPU modules. | (1) Eliminate empty slots between the CPU modules. (Set empty slots on the right side of the CPU modules.) (2) Remove the modules, which are not the QCPU modules, loaded between the QCPU modules, and fit the slots with the QCPUs. Load the motion controller modules on the right side of the QCPUs. | p.142 |
| 2150 | In a multiple CPU system, the control PLC of the intelligent function module incompatible with the multiple CPU system is set to other than station 1. | (1) Change the intelligent function module for the one compatible with the multiple CPU system (function version B). (2) Change the setting of the control CPU of the intelligent function module incompatible with the multiple CPU system to station 1. | p.142 |
| 2200 | There is no parameter file at the drive designated by DIP switches as a valid drive. | Check and correct the setting of the parameter enabled drive switch. Put a parameter file in the drive designated by the parameter enabled drive switch. | p.142 |
| 2210 | The contents of the boot file are incorrect. | Check the boot setting. | p.142 |
| 2301 | (1) The memory card has not been formatted. (2) Memory card format status is incorrect. | (1) Format memory card. (2) Reformat memory card. Check memory card. | p.142 |
| 2302 | A memory card that cannot be used with the CPU module has been installed. | p.142 | |
| 2400 | Automatic write to standard ROM was performed on the CPU module that is incompatible with automatic write to standard ROM. (Memory card where automatic write to standard ROM was selected in the boot file was fitted and the parameter enable drive was set to the memory card.) | (1) Execute automatic write to standard ROM on the CPU module which is compatible with automatic write to standard ROM. (2) Using GX Developer, perform write of parameters and programs to standard ROM. (3) Change the memory card for the one where automatic write to standard ROM has not been set, and perform boot operation from the memory card. | p.142 |
| 2401 | Program memory capacity was exceeded by performing boot operation or automatic write to standard ROM. | (1) Check and correct the parameters (boot setting). (2) Delete unnecessary files in the program memory. (3) Choose "Clear program memory" for boot in the parameter so that boot is started after the program memory is cleared. | p.144 |
| 2410 | The file designated by the sequence program cannot be found. | Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Create a file created using parameters, and load it to the CPU module. | p.144 |
| 2411 | The sequence program designated a file that cannot be designated by the sequence program (comment file, etc.). | Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. | p.144 |
| 2412 | The SFC program file is one that cannot be designated by the sequence program. | p.144 | |
| 2413 | No data has been written to the file designated by the sequence program. | Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Check to ensure that the designated file has not been write protected. | p.144 |
| 2500 | There is a program file that uses a device that exceeds the device allocation range designated by the parameter device settings. | Read the error common information at the peripheral device, check to be sure that the parameter device allocation setting and the program file device allocation correspond to the numerical values there (file name), and correct if necessary. | p.144 |
| 2501 | There are multiple program files although "none" has been set at the parameter program settings. | Edit the parameter program setting to "yes". Alternatively, delete unneeded programs. | p.144 |
| 2502 | The program file is incorrect. Alternatively, the file contents are not those of a sequence program. | Check whether the program version is .QPG, and check the file contents to be sure they are for a sequence program. | p.144 |
| 2503 | There are no program files at all. Two or more SFC normal programs or control programs have been designated. | Check program configuration. Check parameters and program configuration. | p.144 |
| 3000 | In a multiple CPU system, the intelligent function module under control of another station is specified in the interrupt pointer setting of the parameter. | (1) Specify the first I/O number of the intelligent function module under control of the host station. (2) Delete the interrupt pointer setting of the parameter. | p.144 |
| 3001 | Parameter contents have been destroyed. | p.144 | |
| 3002 | When "use the following files" is selected for the file registers in the PLC file setting parameter, the specified file does not exist though the file register capacity has been set. | p.144 | |
| 3003 | The automatic refresh range of the multiple CPU system exceeded the file register capacity. | Change the file register file for the one refresh-enabled in the whole range. | p.144 |
| 3004 | The parameter file is incorrect. Alternatively, the contents of the file are not parameters. | Check whether the parameter file version is .QPA, and check the file contents to be sure they are parameters. | p.144 |
| 3006 | (1) The high speed interrupt parameter is set in a Q02CPU. (2) The high speed parameter is set in a multiple CPU system. (3) The high speed interrupt parameter is set when a QA1S B or QA B is used. (4) No module is installed at the I/O address designated by the high speed interrupt parameter. | (1) Delete the setting of the Q02CPU’s high speed interrupt parameter. To use high speed interrupts, change the CPU module to one of the Q02H/Q06H/Q12H/Q25HCPU. (2) To use a multiple CPU system, delete the setting of the high- speed interrupt parameter. To use high speed interrupts, change the system to a single PLC system. (3) To use either the QA1S B or QA B, delete the setting of the high speed interrupt parameter. To use high speed interrupts, do not use the QA1S B/QA B. (4) Re-examine the I/O address designated by the high speed interrupt parameter. | p.144 |
| 3009 | A modules are set to control PLCs in a multiple CPU system. | Re-set the parameter I/O assignment to control them under one QCPU. (Change the parameters of all stations in the multiple CPU system.) | p.144 |
| 3010 | The parameter-set number of CPU modules differs from the actual number in a multiple CPU system. | Match (preset count of multiple PLC setting) - (CPU (empty) setting in I/O assignment) with the actual number of CPUs loaded. | p.144 |
| 3012 | Multiple CPU setting or control PLC setting differs from that of the reference station in a multiple CPU system. | Match the multiple PLC setting or control CPU setting in the parameter with that of the reference station (station 1). | p.144 |
| 3013 | Multiple CPU automatic refresh setting is any of the followings in a multiple CPU system. (1) When a bit device is specified as a refresh device, a number other than a multiple of 16 is specified for the refresh-starting device. (2) The device specified is other than the one that may be specified. (3) The number of send points is an odd number. | Check the following in the multiple CPU automatic refresh parameters and make correction. (1) When specifying the bit device, specify a multiple of 16 for the refresh starting device. (2) Specify the device that may be specified for the refresh device. (3) Set the number of send points to an even number. | p.144 |
| 3100 | In a multiple CPU system, the MELSECNET/H under control of another station is specified as the first I/O number in the network setting parameter of the MELSECNET/H. | (1) Delete the MELSECNET/H network parameter of the MELSECNET/H under control of another station. (2) Change the setting to the first I/O number of the MELSECNET/H under control of the host station. | p.146 |
| 3101 | The link refresh range exceeded the file register capacity. | Change the file register file for the one refresh-enabled in the whole range. | p.146 |
| 3102 | An error was discovered when the network parameter check was made at the network module. | (1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact your nearest Mitsubishi representative. | p.146 |
| 3103 | In a multiple CPU system, the Q series Ethernet interface module under control of another station is specified as the first I/O number of the Ethernet setting parameter. | (1) Delete the Ethernet setting parameter of the Q series Ethernet interface module under control of another station. (2) Change the setting to the first I/O number of the Q series Ethernet interface module under control of the host station. | p.146 |
| 3104 | Ethernet and MELSECNET/10 use the same network number. Network number, station number or group number set by the parameter is out of range. I/O number is out of range. | (1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact your nearest Mitsubishi representative. | p.146 |
| 3105 | In a multiple CPU system, the Q series CC-Link module under control of another station is specified as the first I/O number of the CC-Link setting parameter. | (1) Delete the CC-Link setting parameter of the Q series CC-Link module under control of another station. (2) Change the setting to the first I/O number of the Q series CC- Link module under control of the host station. | p.146 |
| 3106 | The CC-Link link refresh range exceeded the file register capacity. | Change the file register file for the one refresh-enabled in the whole range. | p.146 |
| 3107 | The contents of the CC-Link parameter are incorrect. | Check the parameter setting. | p.146 |
| 3200 | The parameter contents are incorrect. | Write after correcting parameters. | p.146 |
| 3201 | The contents of the SFC block attribute information are incorrect. | p.146 | |
| 3202 | The number of step relays designated in the parameters is less than the number used by the program. | p.146 | |
| 3203 | The execution type set for an SFC program in the parameters is other than the scan execution type. | p.146 | |
| 3300 | The first I/O number in the intelligent function module parameter set on GX Configurator differs from the actual I/O number. | Check the parameter setting. | p.146 |
| 3301 | The refresh setting of the intelligent function module exceeded the file register capacity. | Change the file register file for the one which allows refresh in the whole range. | p.148 |
| 3302 | The intelligent function module's refresh parameter are abnormal. | Check the parameter setting. | p.148 |
| 3303 | In a multiple CPU system, automatic refresh setting or similar parameter setting was made to the intelligent function module under control of another station. | (1) Delete the automatic refresh setting or similar parameter setting of the intelligent function module under control of another station. (2) Change the setting to the automatic refresh setting or similar parameter setting of the intelligent function module under control of the host station. | p.148 |
| 3400 | The first I/O number of the target module in the remote password file is set to other than 0H to 0FF0H. | Change the first I/O number of the target module to within the 0H to 0FF0H range. | p.148 |
| 3401 | Position specified as the first I/O number of the remote password file is incorrect due to one of the following reasons: • Module is not loaded. • Other than a Q-compatible intelligent function module (I/O, A, QnA module) • Intelligent function module other than QJ71C24(-R2) or Q series Ethernet interface module • QJ71C24(-R2) or Q series Ethernet interface module of function version A | Load the QJ71C24(-R2) or Q series Ethernet interface module of function version B in the position specified as the first I/O number of the remote password file. | p.148 |
| 4000 | The program contains an instruction code that cannot be decoded. An unusable instruction is included in the program. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4001 | The program contains a dedicated instruction for SFC program although it is not an SFC program. | p.148 | |
| 4002 | The extension instruction designated by the program has an incorrect instruction name. | p.148 | |
| 4003 | The extension instruction designated by the program has an incorrect number of devices. | p.148 | |
| 4004 | The extension instruction designated by the program a device which cannot be used. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4010 | There is no END (FEND) instruction in the program. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4020 | The total number of internal file pointers used by the program exceeds the number of internal file pointers set in the parameters. | p.148 | |
| 4021 | The common pointer numbers used by individual files overlap. | p.148 | |
| 4030 | The allocation pointer numbers used by individual files are overlap. | p.148 | |
| 4100 | The instruction cannot process the contained data. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4101 | The designated device number for data processed by the instruction exceeds the usable range. Alternatively, the stored data or constants for the devices designated by the instruction exceeds the usable range. | p.148 | |
| 4102 | In a multiple CPU system, the link direct device (J \G ) was specified for the network module under control of another station. | (1) Delete from the program the link direct device which specifies the network module under control of another station. (2) Using the link direct device, specify the network module under control of the host station. | p.148 |
| 4103 | The configuration of the PID dedicated instruction is incorrect. | p.148 | |
| 4107 | 33 or more multiple CPU dedicated instructions were executed from one CPU module. | Using the multiple CPU dedicated instruction completion bit, provide interlocks to prevent one CPU module from executing 32 or more multiple CPU dedicated instructions. | p.148 |
| 4108 | The CC-Link parameter is not set when the CC-Link instruction is executed. | Execute the CC-Link instruction after setting the CC-Link parameter. | p.148 |
| 4109 | With high speed interrupt setting execute PR/PRC,UDCNT1/2,PWM,SPD,PLOADP,PUNLOADP,PAWPP instruction. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4200 | No NEXT instruction was executed following the execution of a FOR instruction. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4201 | A NEXT instruction was executed although no FOR instruction has been executed. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.148 |
| 4202 | More than 16 nesting levels are programmed. | Keep nesting levels at 16 or under. | p.150 |
| 4203 | A BREAK instruction was executed although no FOR instruction has been executed prior to that. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4210 | The CALL instruction is executed, but there is no subroutine at the specified pointer. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4211 | There was no RET instruction in the executed sub-routine program. | p.150 | |
| 4212 | The RET instruction was before the FEND instruction in the main program. | p.150 | |
| 4213 | More than 16 nesting levels are programmed. | Keep nesting levels at 16 or under. | p.150 |
| 4220 | Interrupt input was generated, but no corresponding interrupt pointer was found. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4221 | There was no IRET instruction in the executed interrupt program. | p.150 | |
| 4223 | The IRET instruction was before the FEND instruction in the main program. | p.150 | |
| 4230 | The number of CHK and CHKEND instructions is not equal. | p.150 | |
| 4231 | The number of IX and IXEND instructions is not equal. | p.150 | |
| 4235 | The configuration of the check conditions for the CHK instruction is incorrect. Alternatively, a CHK instruction has been used in a low speed execution type program. | p.150 | |
| 4300 | The designation of a MELSECNET/MINI-S3 master module control instruction was wrong. | Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4301 | The designation of an AD57/AD58 control instruction was wrong. | p.150 | |
| 4400 | No SFCP or SFCPEND instruction in SFC program. | Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4410 | The block number designated by the SFC program exceeds the range. | p.150 | |
| 4411 | Block number designations overlap in SFC program. | p.150 | |
| 4420 | A step number designated in an SFC program exceeds 511. | p.150 | |
| 4421 | Total number of steps in all SFC programs exceed the range | Reduce total number of steps to below the maximum. | p.150 |
| 4422 | Step number designations overlap in SFC program. | Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4500 | The numbers of BLOCK and BEND instructions in an SFC program are not equal. | Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4501 | The configuration of the STEP to TRAN to TSET to SEND instructions in the SFC program is incorrect. | p.150 | |
| 4502 | There was no STEPI | p.150 | |
| 4503 | The step designated by the TSET instruction in the SFC program does not exist. | p.150 | |
| 4504 | The step designated by the TAND instruction in the SFC program does not exist. | p.150 | |
| 4600 | The SFC program contains data that cannot be processed. | Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. The program is automatically subjected to an initial start. | p.150 |
| 4601 | Exceeds device range that can be designated by the SFC program. | p.150 | |
| 4602 | The START instruction in an SFC program is proceeded by an END instruction. | p.150 | |
| 4610 | The active step information at presumptive start of an SFC program is incorrect. | Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. | p.150 |
| 4611 | Key-switch was reset during RUN when presumptive start was designated for SFC program. | p.150 | |
| 4620 | Startup was executed at a block in the SFC program that was already started up. | p.150 | |
| 4621 | Startup was attempted at a block that does not exist in the SFC program. | p.150 | |
| 4630 | Startup was executed at a block in the SFC program that was already started up. | p.150 | |
| 4631 | Startup was attempted at a block that does not exist in an SFC program. | p.150 | |
| 4632 | There were too many simultaneous active steps in blocks that can be designated by the SFC program. | p.150 | |
| 4633 | There were too many simultaneous active steps in all blocks that can be designated. | p.150 | |
| 5000 | Program scan time for initial execution type programs exceeds the initial execution WDT time setting designated in the PLC RAS parameter. | Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary. | p.150 |
| 5001 | The program scan time goes over the WDT value set in the parameter PLC RAS parameter. | p.150 | |
| 5010 | (1) The scan time of the program exceeded the constant scan setting time specified in the PC RAS setting parameter. (2) The low speed program execution time specified in the PC RAS setting parameter exceeded the margin time of constant scan. | (1) Review the constant scan setting time. (2) Review the constant scan time and low speed program execution time in the parameter so that the margin time of constant scan may be fully reserved. | p.150 |
| 5011 | Low speed scan type program scan time goes over the low speed execution WDT set in the parameter PC RAS settings. | Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary. | p.150 |
| 6000 | The control system and standby system in the redundant system do not have the same programs and parameters. | Synchronise the programs and parameters of the control system and standby system. | p.150 |
| 6010 | The operational status of the control system and standby system in the redundant system is not the same. | Synchronise the operation statuses of the control system and standby system. | p.150 |
| 6100 | A CPU module tracking memory error was detected during initial. | Because this is a CPU module hardware error, contact your nearest Mitsubishi representative. To replace the module, replace the standby system CPU first, then the control system CPU. | p.152 |
| 6101 | The CPU module detected an error during the handshake for tracking. | Check the condition of the other stations. | p.152 |
| 6200 | The standby system in a redundant system is switched to the control system. | Check the control system condition. | p.152 |
| 6210 | The control system in a redundant system is switched to the standby system. | Check the control system condition. | p.152 |
| 6220 | The standby system in a redundant system could not be switched from the control system to the standby system because of an error status or other reason. | Check the standby system condition. | p.152 |
| 6221 | Switching is disabled because of a bus switching module error. | Because this is a bus switching module hardware error, contact your nearest Mitsubishi representative. | p.152 |
| 6222 | Switching is disabled because a multiplexed master station of a remote I/O network was installed in the standby station during initial. | Check the remote I/O network setting. | p.152 |
| 7000 | (1) In a multiple CPU system, at CPU module fault occurred at a station where "all station stop by stop error of PLC " was selected in the operating mode. (2) High Performance model QCPU of function version A was loaded in a multiple CPU system. | (1) Read the error individual information at a peripheral device, check the error of the PLC resulting in CPU module fault, and remove the error. (2) Remove the High Performance model QCPU of function version A from the main base unit. | p.152 |
| 7002 | (1) There is no response from the target station in a multiple CPU system at initial communication stage. (2) High Performance model QCPU of function version A was loaded in a multiple CPU system configuration. | (1) Reset the High Performance model QCPU and run it again. If the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative. (2) Remove the High Performance model QCPU of function version A from the main base unit. | p.152 |
| 7003 | There is no response from the target station in a multiple CPU system at initial communication stage. | Reset the High Performance model QCPU and run it again. If the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative. | p.152 |
| 7010 | (1) Faulty CPU is loaded in a multiple CPU system. (2) High Performance model QCPU of function version A is loaded in a multiple CPU system configuration. (An error is detected at the High Performance model QCPU of function version B.) (3) In a multiple CPU system, any of stations 2 to 4 was reset during power-on. (This error occurs at only the station which was reset.) | (1) Read the error individual information at a peripheral device, and change the faulty station. (2) Change the station of function version A for function version B. (3) Do not reset the CPU modules of PLC No.2 to 4. Reset the High Performance model QCPU of PLC No.1 and restart the multiple CPU system. | p.152 |
| 7020 | In a multiple CPU system, a PLC fault occurred at a station where "all station stop by stop error of PLC" was not selected in the operation mode. (The error is detected at the High Performance model QCPU of other than the station where the CPU module fault occurred.) | Read the error individual information at a peripheral device, check the error of the CPU module resulting in CPU module fault, and remove the error. | p.152 |
| 9000 | Annunciator F was set ON | Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (annunciator number). | p.152 |
| 9010 | Error detected by the CHK instruction. | Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (error number) there. | p.152 |
| 9020 | Storage of data onto ROM was completed normally in automatic write to standard ROM. (BOOT LED also flickers.) | Set the parameter enable drive to standard ROM, switch power on again, and perform boot operation from standard ROM. | p.152 |
| 10000 | In the multiple CPU system, an error occurred in the CPU module other than the Process CPU/High Performance model QCPU. | Use the software package of the corresponding CPU module to check the details of the error that occurred. | p.152 |
| SD213 | value, and OFF if no error is detected. | p.160 | |
| SD520 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD521 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD523 | (Measurement is made in 100µs increments.) | p.194 | |
| SD522 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD524 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD525 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD526 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD527 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD528 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD529 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD532 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD533 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD534 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD535 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD540 | Place of ms is stored (storage range: 0 to 65535) | p.194 | |
| SD541 | Place of µs is stored (storage range: 0 to 900) | p.194 | |
| SD542 | Place of ms is stored (storage range: 0 to 65535) | p.195 | |
| SD543 | Place of µs is stored (storage range: 0 to 900) | p.195 | |
| SD544 | Place of ms is stored (storage range: 0 to 65535) | p.195 | |
| SD545 | Place of µs is stored (storage range: 0 to 900) | p.195 | |
| SD546 | Place of ms is stored (storage range: 0 to 65535) | p.195 | |
| SD547 | Place of µs is stored (storage range: 0 to 900) | p.195 | |
| SD548 | Place of ms is stored (storage range: 0 to 65535) | p.195 | |
| SD549 | Place of µs is stored (storage range: 0 to 900) | p.195 | |
| SD551 | Place of ms is stored (storage range: 0 to 65535) | p.195 | |
| SD552 | Place of µs is stored (storage range: 0 to 900) | p.195 | |
| B0 | Boot operation (QBT) | p.196 | |
| B1 | Parameters (QPA) | p.196 | |
| B2 | Device comments (QCD) | p.196 | |
| B3 | Device initial value (QDI) | p.196 | |
| B7 | Not used | p.196 | |
| B8 | Not used | p.196 | |
| B9 | CPU fault history (QFD) | p.196 | |
| B10 | SFC trace (QTS) | p.196 | |
| B11 | Local device (QDL) | p.196 | |
| B13 | Not used | p.196 | |
| B14 | Not used | p.196 | |
| B15 | Not used | p.196 | |
| D9125 | D9132. | p.208 | |
| SD64 | SD71 contents one place. (When CPU has | p.208 | |
| 4000H | Sum check error | Check the connection status of the connection cable with the CPU module | p.217 |
| 4001H | Remote request that is not handled was executed. | Check the requested remote operation. | p.217 |
| 4002H | Command for which a global request cannot be performed was executed. | Check the requested command. | p.217 |
| 4004H | CPU module cannot execute the request contents because it is in system protect | Turn off the CPU module system protect switch. | p.217 |
| 4005H | The volume of data handled according to the specified request is too large. | Reduce the volume of data to that which can be processed at the specified request. | p.217 |
| 4006H | The password cannot be deleted. | Delete the set password. | p.217 |
| 4008H | The CPU module is not BUSY (The buffer is not vacant). | After the free time has passed, reexecute the request. | p.217 |
| 4010H | The CPU module is running to the request contents cannot be executed. | Execute after setting the CPU module to STOP status. | p.217 |
| 4011H | The CPU module is not in the STEP-RUN status so the request contents cannot be executed. | Execute after setting the CPU module to STEP-RUN status. | p.217 |
| 4021H | The specified drive memory does not exist or there is an error. | Check the specified drive memory status. | p.218 |
| 4022H | The file with the specified file name or file No. does not exist. | Check the specified file name and file No. | p.218 |
| 4023H | The file name and file No. of the specified file do not match. | Delete the file and then recreate the file. | p.218 |
| 4024H | The specified file cannot be handled by a user. | Do not access the specified file. | p.218 |
| 4025H | The specified file is processing the request from a different location. | Forcefully execute the request forcibly. Or reexecute the request after the processing from the other location has ended. | p.218 |
| 4026H | The keyword specification set in the corresponding drive memory is required. | Access by specifying the keyword set in the corresponding drive memory. | p.218 |
| 4027H | The specified range exceeds the file range. | Check the specified range and access within that range. | p.218 |
| 4028H | The same file already exists. | Forcefully execute the request forcibly. Or reexecute after changing the file name. | p.218 |
| 4029H | The specified file capacity cannot be obtained. | Revise the specified file contents. Or reexecute after cleaning up and reorganizing the specified drive memory. | p.218 |
| 402BH | The request contents cannot be executed in the specified drive memory. | Do not execute a request for a specified drive memory in which an error has occurred. | p.218 |
| 402CH | Currently the request contents cannot be executed. | Reexecute after the free wait time has passed. | p.218 |
| 4030H | The specified device name cannot be handled. | Check the specified device name. | p.218 |
| 4031H | The specified device No. is outside the range. | Check the specified device No. | p.218 |
| 4032H | There is a mistake in the specified device qualification. | Check the specified device qualification method. | p.218 |
| 4033H | Writing cannot be done because the specified device is for system use. | Do not write the data in the specified device, and do not turn on or off. | p.218 |
| 4040H | The request contents cannot be executed in the specified intelligent function module. | Do not conduct a request for a specified intelligent function module in which an error has occurred. | p.218 |
| 4041H | The access range exceeds the buffer memory range of the specified intelligent function module. | Check the header address and access number of points and access using a range that exists in the intelligent function module. | p.218 |
| 4042H | The specified intelligent function module cannot be accessed. | Check that the specified intelligent function module is operating normally. | p.218 |
| 4043H | The intelligent function module does not exist in the specified position. | Check the header I/O No. of the specified intelligent function module. | p.218 |
| 4044H | A control bus error has occurred. | Check that there is no error in the intelligent function module or in the hardware of another module. | p.218 |
| 4045H | The setting required to conduct simulation has not been made. | Conduct a simulation setting. | p.218 |
| 4046H | The device header or number of points in the simulation is not in 16point unit. | Check the device header No. or number of points and correct them to 16 point units. | p.218 |
| 4050H | The request contents cannot be executed because the memory card write protect switch is on. | Turn off the memory card write protect switch. | p.219 |
| 4051H | The specified device memory cannot be accessed. | Check the following and make it countermeasures. • Is the memory one that can be used? • Is the specified drive memory correctly installed? | p.219 |
| 4052H | The specified file attribute is read only so the data cannot be written. | Do not write data in the specified file. Or change the file attribute. | p.219 |
| 4053H | An error occurred when writing data to the specified drive memory. | Check the specified drive memory. Or reexecute write after changing the corresponding drive memory. | p.219 |
| 4054H | An error occurred when deleting the data in the specified drive memory. | Check the specified drive memory. Or re-erase after replacing the corresponding drive memory. | p.219 |
| 4060H | The monitor condition registration CPU module system area is already being used by another piece of equipment. | Reexecute monitor after the monitor by the other equipment has completed. Or increase the system area of the program memory using the format with option. | p.219 |
| 4061H | Communication failed. | Execute a re-communication. | p.219 |
| 4062H | The monitor detail condition is already being used and monitored by another piece of equipment. | Do not conduct monitor detail condi-tions from the specified equipment. Or reexecute monitoring after deleting the monitor detail conditions of the other equipment. | p.219 |
| 4063H | The number of the file lock registrations exceeds 16. | Reduce the number of registrations to 16 or less. | p.219 |
| 4064H | There is a problem with the specified contents. | Check the specified contents. | p.219 |
| 4065H | The device allocation information differs from the parameter. | Check the parameter. Or check the data. | p.219 |
| 4066H | A keyword that differs from the keyword set in the specified driver memory has been specified. | Check the specified keyword. | p.219 |
| 4067H | The specified monitor file cannot be obtained. | Conduct monitor after obtaining the monitor file. | p.219 |
| 4068H | Registration/deletion cannot be conducted because the specified command is being executed. | Reexecute the command after the request from the other equipment has been completed. | p.219 |
| 4069H | The conditions have already been reached by the device match. | Check the monitor conditions. Or reconduct monitor registration and execute monitor. | p.219 |
| 406AH | A drive other than Nos. 1 to 3 has been specified. | Check the specified drive and specify the correct drive. | p.219 |
| 4070H | Program before correction and the registration program differ. | Check the registration program and make the programs match. | p.219 |
| 4080H | Data error | Check the requested data contents. | p.219 |
| 4081H | The sort subject cannot be detected. | Check the data to be searched. | p.219 |
| 4082H | The specified command is executing and therefore cannot be executed. | Reexecute the command after the request from the other equipment is completed. | p.219 |
| 4083H | Trying to execute a program that is not registered in the parameter. | Register the program to be executed in the parameter. | p.219 |
| 4084H | The specified pointer P, I cannot be detected. | Check the data to be searched. | p.220 |
| 4085H | Pointer P, I cannot be specified because the program is not specified in the parameter. | Specify pointer P, I after registering the program to be executed in the parameter. | p.220 |
| 4086H | Pointer P, I has already been added. | Check the pointer No. to be added and make correction. | p.220 |
| 4087H | Trying to specify too many pointers. | Check the specified pointer and make a correction. | p.220 |
| 4088H | The specified step No. was not in the instruction header. | Check the specified step No. and make a correction. | p.220 |
| 4089H | An END instruction was inserted/deleted while the CPU module was running. | Conduct Insert/removal after the CPU module has stopped. | p.220 |
| 408AH | The file capacity was exceeded by the write during Run. | Write the program after the CPU module has stopped. | p.220 |
| 408BH | The remote request cannot be executed. | Reexecute after the CPU module is in a status where the mode request can be executed. | p.220 |
| 4090H | The block breakpoint number was exceeded. | Check the number of settings and make a correction. | p.220 |
| 4091H | There is a mistake in the block breakpoint registration number. | Check the number of registrations and make a correction. | p.220 |
| 4092H | The step breakpoint number has been exceeded. | Check the number of registrations and make a correction. | p.220 |
| 4093H | There is a mistake in the step breakpoint registration number. | Check the number of registrations and make a correction. | p.220 |
| 4094H | Tried to execute a request during block continuous processing. | Reconduct the request after the processing has ended. | p.220 |
| 4095H | Tried to execute a request during block forced execution processing. | Reconduct the request after the processing has ended. | p.220 |
| 4096H | Tried to execute a request during step continuous processing. | Reconduct the request after the processing has ended. | p.220 |
| 4097H | Tried to execute a request during step forced execution processing. | Reconduct the request after the processing has ended. | p.220 |
| 4098H | Tried to execute a request during one step continuous processing. | Reconduct the request after the processing has ended. | p.220 |
| 4099H | Tried to execute a request during one step forced execution processing. | Reconduct the request after the processing has ended. | p.220 |
| 409AH | Tried to execute a request during block forced end processing. | Reconduct the request after the processing has ended. | p.220 |
| 409BH | Tried to execute a request during step forced end processing. | Reconduct the request after the processing has ended. | p.220 |
| 409CH | Tried to execute a request during hold step reset processing. | Reconduct the request after the processing has ended. | p.220 |
| 409DH | A block No. that has not been created or that exceeds the range has been specified. | Check the setting contents and make a correction. | p.220 |
| 409EH | A step No. that was not created was specified. | Check the setting contents and make a correction. | p.220 |
| 409FH | The specified number of cycles is outside the range. | Check the number of registrations and make a correction. | p.220 |
| 40A0H | A block No. outside the range was specified. | Check the setting contents and make a correction. | p.221 |
| 40A1H | A number of blocks that exceeds the range was specified. | Check the number of settings and make a correction. | p.221 |
| 40A2H | A step No. that is outside the range was specified. | Check the setting contents and make a correction. | p.221 |
| 40A3H | A number of steps that exceeds the range was specified. | Check the number of settings and make a correction. | p.221 |
| 40A4H | A sequence step No. outside the range was specified. | Check the setting contents and make a correction. | p.221 |
| 40A5H | The specified device was outside the range. | Check the number of settings and make a correction. | p.221 |
| 40A6H | There is a mistake in the block specification pattern or the step specification pattern. | Check the setting contents and make a correction. | p.221 |
| 40B0H | The wrong drive was specified. | Check the setting contents and make a correction. | p.221 |
| 40B1H | The specified program does not exist. | Check the specified file name and make a correction. | p.221 |
| 40B2H | The specified program was not an SFC program. | Check the specified file name and make a correction. | p.221 |
| 40B3H | There was an SFC dedicated instruction in the write during run area. | Check the setting contents and make a correction. | p.221 |
| 41D0H | The route directory has no free space. | Increase the free space of the specified drive. Optimize the specified drive to increase continuous free areas. | p.221 |
| 41D1H | The file pointer is insufficient. | Specify the correct file pointer. | p.221 |
| 41D5H | The file of the same name exists. | Change the file name. | p.221 |
| 41DFH | The disk is write-protected. | Cancel the write protection of the disk and execute again. | p.221 |
| 41E0H | The drive does not respond. | Check for the specified drive. If it exists, check its status. | p.221 |
| 41E1H | The address or sector is not found. | Check if the target is a ROM drive or not. | p.221 |
| 41E4H | The file cannot be accessed properly. | Execute again after resetting the CPU module. | p.221 |
| 41E8H | The drive format information is illegal. | Format the target drive. | p.221 |
| 41E9H | At the time of file access, time-out occurred during waiting for access. | Execute again after some time. | p.221 |
| 41EBH | The path name is too long. | Check the length of the path name. | p.221 |
| 41ECH | The disk is logically broken. | Change the specified drive. | p.221 |
| 41EDH | An attempt to make a file continuous failed. (There are enough free file areas, which cannot be taken continuously.) | Optimize the specified drive to increase continuous free areas. | p.221 |
| 41F2H | The specified drive is ROM. | Check the specified drive. (Format it for RAM.) | p.221 |
| 41FBH | The same starting source has already opened the specified file. | Check if it is being processed by another application. | p.221 |
| 41FCH | An attempt was made to erase the mounted drive. | Execute again after dismounting the drive. | p.221 |
| 41FDH | The Flash ROM is not formatted. | Erase the specified drive. | p.221 |
| 41FEH | The memory card is not inserted. | Insert or reinsert the memory card. | p.221 |
| 41FFH | The memory card type differs. | Check the memory card type. | p.221 |
| 4A00H | (1) The specified station could not be accessed because a routing parameter was not set in the related station. (2) Though routing via the multiple CPU system is attempted, the control CPU of the network module that relays the data is not active. | (1) Set the routing parameter for accessing the specified station in the related station. (2) Try after a while. Or check if the system relaying the data is active, then start communication. | p.221 |
| 4A01H | The network with the No. set in the routing parameter does not exist. | Check the routing parameter set in the related station and make a correction. | p.221 |
| 4A02H | Cannot access the specified station. | Check if an error has occurred in the network module and if the module is offline. | p.221 |
| 4B00H | An error occurred in the access destination or in a relay station. | Check if an error has occurred in the specified access destination or in a relay station to the access station and if so take countermeasures. | p.221 |
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Input signal does not turn OFF. | • Leakage current of input switch (e.g. drive by non-contact switch). AC input Leakage Input module current Power supply | • Connect an appropriate resistor which will make the voltage across the terminals of the input module lower than the OFF voltage value. AC input Input module It is recommended to use 0.1 to 47 F + 47 to 120 (1/2W) for the CR constant. | p.154 |
| Input signal does not turn OFF. | • Drive by a limit switch with neon lamp. AC input Leakage Input module current Power supply | • Same as Example 1. • Or make up another independent display circuit. | p.154 |
| Input signal does not turn OFF. | • Leakage current due to line capacity of wiring cable. (Line capacity C of twisted pair wire is approx. 100 pF/m). AC input Leakage Input module current Power supply | • Same as Example 1. • However, leakage current is not generated when the power supply is located in the input equipment side as shown below. AC input Input module Power supply | p.154 |
| Input signal does not turn OFF. | • Drive by switch with LED indicator. DC input (plus common) Leakage current Input module | • Connect a register which will make the voltage between the input module terminal and common lower than the OFF voltage, as shown below. DC input (plus common) Resistor Input module A calculation example of a value for a connected resistor is given on the following page. | p.154 |
| Input signal does not turn OFF. | • Sneak path due to the use of two power supplies. E1 E2 Input module E1>E2 | • Use only one power supply. • Connect a sneak path prevention diode. (Figure below) E1 E2 Input module | p.155 |
| False input due to noise | Depending on response time setting, noise is imported as input. | Change response time setting. Example : 1ms 5ms (Setting of a shorter response time may produce a higher effect on periodic excessive noise.)If no effects are produced by the above, take basic actions to prevent excessive noise form entering, e.g. avoid bundling the power and I/O cables, and suppress noise by adding surge absorbers to such noise sources as relays and conductors used with the same power supply.) | p.155 |
| Excessive voltage is applied to load when output turns off. | • When load is half-wave rectified inside (This is typical of some solenoids.) QY22 [1] Output module D1 C Load [2] • When the polarity of the power supply is [1], the capacitor C is charged. When the polarity is [2], the voltage charged in C plus the power supply voltage is applied to across D1. The maximum value of the voltage is approx. 2.2E. (This usage does not pose problems to the output components but may deteriorate the diode built in the load, causing burnout, etc.) | • Connect a resistor of several ten K to several hundred K across the load. Resistor Load | p.157 |
| Load does not turn off. (Triac output) | • Leakage current due to the built-in surge suppressor QY22 Output module Load Leakage current | • Connect a resistor across the load. (If the wiring from the output module to the load is long, be careful since there may be a leakage current due to the line capacity.) Resistor Load | p.157 |