COVERp.1SAFETY PRECAUTIONSp.2REVISIONSp.7INTRODUCTIONp.8CONTENTSp.8About Manualsp.18How to Use This Manualp.19About the Generic Terms and Abbreviationsp.201 OVERVIEWp.211.1 Featuresp.222 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEMp.252.1 System Configurationp.252.2 Precaution on System Configurationp.302.3 Confirming the Serial Number and Function Versionp.323 GENERAL SPECIFICATIONSp.334 HARDWARE SPECIFICATION OF THE CPU MODULEp.354.1 Performance Specificationp.354.2 Part Names and Settingsp.384.3 Switch Operation After Writing in Programp.414.4 Latch Clear Operationp.424.5 Executing Automatic Write to Standard ROM.p.425 POWER SUPPLY MODULEp.445.1 Specificationp.445.1.1 Power supply module specificationsp.445.1.2 Selecting the power supply modulep.495.1.3 Precaution when connecting the uninterruptive power supplyp.515.2 Names of Parts and Settingsp.526 BASE UNIT AND EXTENSION CABLEp.556.1 Base Unit Specification Tablep.556.2 Extension Cable Specification Tablep.576.3 Parts Names of Base Unitp.576.4 Setting the Extension Base Unitp.606.5 I/O Number Allocationp.616.6 Guideline for Use of Extension Base Units (Q5[ ] B)p.627 MEMORY CARD AND BATTERYp.667.1 Memory Card Specificationsp.667.2 Battery Specifications (For CPU Module and SRAM Card)p.677.3 Handling the Memory Cardp.687.4 The Names of The Parts of The Memory Cardp.697.5 Memory Card Loading/Unloading Proceduresp.707.6 Installation of Battery (for CPU Module and Memory Card)p.718 EMC AND LOW VOLTAGE DIRECTIVEp.728.1 Requirements for Conformance to EMC Directivep.728.1.1 Standards applicable to the EMC Directivep.728.1.2 Installation instructions for EMC Directivep.738.1.3 Cablesp.748.1.4 Power supply modulep.768.1.5 When using QA1S6[ ] B type base unitp.768.1.6 Othersp.798.2 Requirement to Conform to the Low Voltage Directivep.808.2.1 Standard applied for MELSEC-Q series PLCp.808.2.2 MELSEC-Q series PLC selectionp.808.2.3 Power supplyp.818.2.4 Control boxp.818.2.5 Groundingp.828.2.6 External wiringp.829 LOADING AND INSTALLATIONp.839.1 General Safety Requirementsp.839.2 Calculating Heat Generation by PLCp.889.3 Module Installationp.919.3.1 Precaution on installationp.919.3.2 Instructions for mounting the base unitp.949.3.3 Installation and removal of modulep.979.4 How to Set Stage Numbers for the Extension Base Unitp.1019.5 Connection and Disconnection of Extension Cablep.1029.6 Wiringp.1059.6.1 The precautions on the wiringp.1059.6.2 Connecting to the power supply modulep.10810 MAINTENANCE AND INSPECTIONp.10910.1 Daily Inspectionp.11010.2 Periodic Inspectionp.11110.3 Battery Replacementp.11210.3.1 Battery lifep.11310.3.2 Battery replacement procedurep.11511 TROUBLESHOOTINGp.11711.1 Troubleshooting Basicsp.11711.2 Troubleshootingp.11811.2.1 Troubleshooting flowchartp.11811.2.2 Flowchart for when the "MODE" LED is not turned onp.11911.2.3 Flowchart for when the "MODE" LED is flickeringp.12011.2.4 Flowchart for when the "POWER" LED is turned offp.12111.2.5 Flowchart for when the "RUN" LED is turned offp.12211.2.6 When the "RUN" LED is flickeringp.12311.2.7 Flowchart for when the "ERR." LED is on/flickeringp.12311.2.8 When the "USER" LED is turned onp.12411.2.9 When the "BAT." LED is turned onp.12411.2.10 Flowchart for when the "BOOT" LED is flickeringp.12511.2.11 Flowchart for when output module LED is not turned onp.12611.2.12 Flowchart for when output load of output module does not turn onp.12711.2.13 Flowchart for when unable to read a programp.12811.2.14 Flowchart for when unable to write a programp.12911.2.15 Flowchart for when it is unable to perform boot operation from memory cardp.13111.2.16 Flowchart for when UNIT VERIFY ERR. occursp.13211.2.17 Flowchart for when CONTROL BUS ERR. occursp.13311.3 Error Code Listp.13411.3.1 Procedure for reading error codesp.13411.3.2 Error Code Listp.13511.4 Canceling of Errorsp.15311.5 I/O Module Troubleshootingp.15411.5.1 Input circuit troubleshootingp.15411.5.2 Output Circuit Troubleshootingp.15711.6 Special Relay Listp.15811.7 Special Register Listp.180APPENDICESp.216APPENDIX 1 Error Code Return to Origin During General Data Processingp.216APPENDIX 1.1 Error code overall explanationp.216APPENDIX 1.2 Description of the errors of the error codes (4000H to 4FFFH)p.217APPENDIX 2 External Dimensionsp.222APPENDIX 2.1 CPU modulep.222APPENDIX 2.2 Power supply modulep.222APPENDIX 2.3 Main base unitp.225APPENDIX 2.4 Slim type main base unitp.227APPENDIX 2.5 Extension base unitp.228APPENDIX 3 Upgraded Functions of High Performance Model QCPUp.231APPENDIX 3.1 Specification comparisonp.231APPENDIX 3.2 Function comparisonp.231APPENDIX 3.3 Added functions and the corresponding GX Developer versionsp.232INDEXp.233WARRANTYp.235
Page 1 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC
Page 1 · click to enlarge
Page 1

MITSUBISHI ELECTRIC

MELSEC System Q

Programmable Logic Controllers

User’s Manual

High Performance Model QCPU

Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU,

Q25HCPU

Art. no.: 130000 01 10 2002 SH (NA)-080037-F

INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC

Page 2 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 1 A - 1
Page 2 · click to enlarge
Page 2

SAFETY PRECAUTIONS

(Read these precautions before using.)

When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in this manual. Also pay careful attention to safety and handle the module properly. These SAFETY PRECAUTIONS classify the safety precautions into two categories: "DANGER" and "CAUTION".

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (Read these precautions before using.) diagram (page 2)
Fig. 1 · (Read these precautions before using.)

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.

Depending on circumstances, procedures indicated by ! CAUTION may also be linked to serious results. In any case, it is important to follow the directions for usage.

Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.

[DESIGN PRECAUTIONS]

! DANGER

Install a safety circuit external to the PLC that keeps the entire system safe even when there

are problems with the external power supply or the PLC module. Otherwise, trouble could result from erroneous output or erroneous operation. (1) Outside the PLC, construct mechanical damage preventing interlock circuits such as

emergency stop, protective circuits, positioning upper and lower limits switches and interlocking forward/reverse operations. (2) When the PLC detects the following problems, it will stop calculation and turn off all output

in the case of (a). In the case of (b), it will stop calculation and hold or turn off all output according to the parameter setting. Note that the AnS series module will turn off the output in either of cases (a) and (b).

(a) The power supply module has over current protection equipment and over voltage

protection equipment. (b) The PLC CPUs self-diagnosis functions, such as the watch dog timer error, detect

problems. In addition, all output will be turned on when there are problems that the PLC CPU cannot detect, such as in the I/O controller. Build a fail safe circuit exterior to the PLC that will make sure the equipment operates safely at such times. See section 9.1 of this manual for example fail safe circuits. (3) Output could be left on or off when there is trouble in the outputs module relay or transistor.

So build an external monitoring circuit that will monitor any single outputs that could cause serious trouble.

A - 1 A - 1

Page 3 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 2 A - 2
Page 3 · click to enlarge
Page 3

[DESIGN PRECAUTIONS]

! DANGER

When overcurrent which exceeds the rating or caused by short-circuited load flows in the output

module for a long time, it may cause smoke or fire. To prevent this, configure an external safety circuit, such as fuse. Build a circuit that turns on the external power supply when the PLC main module power is

turned on. If the external power supply is turned on first, it could result in erroneous output or erroneous operation. When there are communication problems with the data link, refer to the corresponding data link

manual for the operating status of each station. Not doing so could result in erroneous output or erroneous operation. When connecting a peripheral device to the CPU module or connecting a personal computer or

the like to the intelligent function module to exercise control (data change) on the running PLC, configure up an interlock circuit in the sequence program to ensure that the whole system will always operate safely. Also before exercising other control (program change, operating status change (status control)) on the running PLC, read the manual carefully and fully confirm safety. Especially for the above control on the remote PLC from an external device, an immediate action may not be taken for PLC trouble due to a data communication fault. In addition to configuring up the interlock circuit in the sequence program, corrective and other actions to be taken as a system for the occurrence of a data communication fault should be predetermined between the external device and PLC CPU.

! CAUTION

Do not bunch the control wires or communication cables with the main circuit or power wires, or

install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that would cause erroneous operation.

When controlling items like lamp load, heater or solenoid valve using an output module, large

current (approximately ten times greater than that present in normal circumstances) may flow when the output is turned OFF to ON. Take measures such as replacing the module with one having sufficient rated current.

A - 2 A - 2

Page 4 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 3 A - 3
Page 4 · click to enlarge
Page 4

[INSTALLATION PRECAUTIONS]

! CAUTION

Use the PLC in an environment that meets the general specifications contained in this manual.

Using this PLC in an environment outside the range of the general specifications could result in electric shock, fire, erroneous operation, and damage to or deterioration of the product.

Hold down the module loading lever at the module bottom, and securely insert the module

fixing latch into the fixing hole in the base unit. Incorrect loading of the module can cause a malfunction, failure or drop. When using the PLC in the environment of much vibration, tighten the module with a screw. Tighten the screw in the specified torque range. Undertightening can cause a drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to damage to the screw or module.

When installing extension cables, be sure that the connectors of base unit are installed

correctly. After installation, check them for looseness. Poor connections could cause an input or output failure.

Securely load the memory card into the memory card loading connector. After loading, check

for lifting. Lifting can cause a malfunction due to a contact fault.

Completely turn off the external power supply before loading or unloading the module. Not

doing so could result in electric shock or damage to the product.

Do not directly touch the module's conductive parts or electronic components. Touching the

conductive parts could cause an operation failure or give damage to the module.

[WIRING PRECAUTIONS]

! DANGER

Completely turn off the external power supply when installing or placing wiring. Not completely

turning off all power could result in electric shock or damage to the product.

When turning on the power supply or operating the module after installation or wiring work, be

sure that the module's terminal covers are correctly attached. Not attaching the terminal cover could result in electric shock.

A - 3 A - 3

Page 5 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 4 A - 4
Page 5 · click to enlarge
Page 5

[WIRING PRECAUTIONS]

! CAUTION

Be sure to ground the FG terminals and LG terminals to the protective ground conductor. Not

doing so could result in electric shock or erroneous operation.

When wiring in the PLC, be sure that it is done correctly by checking the product's rated voltage

and the terminal layout. Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or damage.

External connections shall be crimped or pressure welded with the specified tools, or correctly

soldered. Imperfect connections could result in short circuit, fires, or erroneous operation.

Tighten the terminal screws with the specified torque. If the terminal screws are loose, it could

result in short circuits, fire, or erroneous operation. Tightening the terminal screws too far may cause damages to the screws and/or the module, resulting in fallout, short circuits, or malfunction.

Be sure there are no foreign substances such as sawdust or wiring debris inside the module.

Such debris could cause fires, damage, or erroneous operation.

The module has an ingress prevention label on its top to prevent foreign matter, such as wire

offcuts, from entering the module during wiring. Do not peel this label during wiring. Before starting system operation, be sure to peel this label because of heat dissipation.

[STARTUP AND MAINTENANCE PRECAUTIONS]

! DANGER

Do not touch the terminals while power is on.

Doing so could cause shock or erroneous operation.

Correctly connect the battery.

Also, do not charge, disassemble, heat, place in fire, short circuit, or solder the battery. Mishandling of battery can cause overheating or cracks which could result in injury and fires.

Switch all phases of the external power supply off when cleaning the module or retightening the

terminal or module mounting screws. Not doing so could result in electric shock. Undertightening of terminal screws can cause a short circuit or malfunction. Overtightening of screws can cause damages to the screws and/or the module, resulting in fallout, short circuits, or malfunction.

A - 4 A - 4

Page 6 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 5 A - 5
Page 6 · click to enlarge
Page 6

[STARTUP AND MAINTENANCE PRECAUTIONS]

! DANGER

The online operations conducted for the CPU module being operated, connecting the peripheral

device (especially, when changing data or operation status), shall be conducted after the manual has been carefully read and a sufficient check of safety has been conducted. Operation mistakes could cause damage or problems with of the module.

Do not disassemble or modify the modules.

Doing so could cause trouble, erroneous operation, injury, or fire.

Use any radio communication device such as a cellular phone or a PHS phone more than 25cm

(9.85 inch) away from the PLC. Not doing so can cause a malfunction.

Switch all phases of the external power supply off before mounting or removing the module.

If you do not switch off the external power supply, it will cause failure or malfunction of the module.

Do not drop or give an impact to the battery installed in the module.

Otherwise the battery will be broken, possibly causing internal leakage of electrolyte. Do not use but dispose of the battery if it has fallen or an impact is given to it.

[DISPOSAL PRECAUTIONS]

! CAUTION

When disposing of this product, treat it as industrial waste.

A - 5 A - 5

Page 7 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 1999 MITSUBISHI ELECTRIC CORPORATION
Page 7 · click to enlarge
Page 7

REVISIONS

The manual number is given on the bottom left of the back cover. Print Date Manual Number Revision Dec., 1999 SH(NA)-080037-A First edition Sep., 2000 SH(NA)-080037-B Addition model

Q33B, Q63B, Q63P Addition Section 2.3, 4.5, 11.2.3, 11.2.10, 11.2.11 Partial correction Section 1.2, 2.2, 4.1, 4.2, 5.1.1, 5.2, 8.1.5, 11.2.1, 11.3.2, 11.5.1, 11.6, 11.7 Jun., 2001 SH(NA)-080037-C Addition model

Q62P, Q52B, Q55B, QC05B Addition Section 6.6 Partial correction Section 2.1, 2.2, 4.1, 4.2, 5.1.5, 6.1, 6.2, 6.3, 8.1.5, 11.2.4, 11.7 Sep., 2001 SH(NA)-080037-D Addition model

Q64P Partial correction CONTENTS, Section 4.1, 5.1.1, 5.1.2, 5.2, 6.1, 6.2, 8.1.5, 11.5.1, Appendix1.2, 2.2 Apr., 2002 SH(NA)-080037-E Partial correction

Chapter 1, Section 1.1, 2.1, 2.2, 2.3, 4.1, 5.1.1, 7.1, 7.2, 7.3, 10.3.1, 10.3.2 Oct., 2002 SH(NA)-080037-F Complete review

Addition model Q32SB, Q33SB, Q35SB, Q61SP

Japanese Manual Version SH-080019-I

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

1999 MITSUBISHI ELECTRIC CORPORATION

A - 6 A - 6

Page 8 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Table of Contents
Page 8 · Contents
Contents

Contents

COVERp.1SAFETY PRECAUTIONSp.2REVISIONSp.7INTRODUCTIONp.8CONTENTSp.8About Manualsp.18How to Use This Manualp.19About the Generic Terms and Abbreviationsp.201 OVERVIEWp.211.1 Featuresp.222 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEMp.252.1 System Configurationp.252.2 Precaution on System Configurationp.302.3 Confirming the Serial Number and Function Versionp.323 GENERAL SPECIFICATIONSp.334 HARDWARE SPECIFICATION OF THE CPU MODULEp.354.1 Performance Specificationp.354.2 Part Names and Settingsp.384.3 Switch Operation After Writing in Programp.414.4 Latch Clear Operationp.424.5 Executing Automatic Write to Standard ROM.p.425 POWER SUPPLY MODULEp.445.1 Specificationp.445.1.1 Power supply module specificationsp.445.1.2 Selecting the power supply modulep.495.1.3 Precaution when connecting the uninterruptive power supplyp.515.2 Names of Parts and Settingsp.526 BASE UNIT AND EXTENSION CABLEp.556.1 Base Unit Specification Tablep.556.2 Extension Cable Specification Tablep.576.3 Parts Names of Base Unitp.576.4 Setting the Extension Base Unitp.606.5 I/O Number Allocationp.616.6 Guideline for Use of Extension Base Units (Q5[ ] B)p.627 MEMORY CARD AND BATTERYp.667.1 Memory Card Specificationsp.667.2 Battery Specifications (For CPU Module and SRAM Card)p.677.3 Handling the Memory Cardp.687.4 The Names of The Parts of The Memory Cardp.697.5 Memory Card Loading/Unloading Proceduresp.707.6 Installation of Battery (for CPU Module and Memory Card)p.718 EMC AND LOW VOLTAGE DIRECTIVEp.728.1 Requirements for Conformance to EMC Directivep.728.1.1 Standards applicable to the EMC Directivep.728.1.2 Installation instructions for EMC Directivep.738.1.3 Cablesp.748.1.4 Power supply modulep.768.1.5 When using QA1S6[ ] B type base unitp.768.1.6 Othersp.798.2 Requirement to Conform to the Low Voltage Directivep.808.2.1 Standard applied for MELSEC-Q series PLCp.808.2.2 MELSEC-Q series PLC selectionp.808.2.3 Power supplyp.818.2.4 Control boxp.818.2.5 Groundingp.828.2.6 External wiringp.829 LOADING AND INSTALLATIONp.839.1 General Safety Requirementsp.839.2 Calculating Heat Generation by PLCp.889.3 Module Installationp.919.3.1 Precaution on installationp.919.3.2 Instructions for mounting the base unitp.949.3.3 Installation and removal of modulep.979.4 How to Set Stage Numbers for the Extension Base Unitp.1019.5 Connection and Disconnection of Extension Cablep.1029.6 Wiringp.1059.6.1 The precautions on the wiringp.1059.6.2 Connecting to the power supply modulep.10810 MAINTENANCE AND INSPECTIONp.10910.1 Daily Inspectionp.11010.2 Periodic Inspectionp.11110.3 Battery Replacementp.11210.3.1 Battery lifep.11310.3.2 Battery replacement procedurep.11511 TROUBLESHOOTINGp.11711.1 Troubleshooting Basicsp.11711.2 Troubleshootingp.11811.2.1 Troubleshooting flowchartp.11811.2.2 Flowchart for when the "MODE" LED is not turned onp.11911.2.3 Flowchart for when the "MODE" LED is flickeringp.12011.2.4 Flowchart for when the "POWER" LED is turned offp.12111.2.5 Flowchart for when the "RUN" LED is turned offp.12211.2.6 When the "RUN" LED is flickeringp.12311.2.7 Flowchart for when the "ERR." LED is on/flickeringp.12311.2.8 When the "USER" LED is turned onp.12411.2.9 When the "BAT." LED is turned onp.12411.2.10 Flowchart for when the "BOOT" LED is flickeringp.12511.2.11 Flowchart for when output module LED is not turned onp.12611.2.12 Flowchart for when output load of output module does not turn onp.12711.2.13 Flowchart for when unable to read a programp.12811.2.14 Flowchart for when unable to write a programp.12911.2.15 Flowchart for when it is unable to perform boot operation from memory cardp.13111.2.16 Flowchart for when UNIT VERIFY ERR. occursp.13211.2.17 Flowchart for when CONTROL BUS ERR. occursp.13311.3 Error Code Listp.13411.3.1 Procedure for reading error codesp.13411.3.2 Error Code Listp.13511.4 Canceling of Errorsp.15311.5 I/O Module Troubleshootingp.15411.5.1 Input circuit troubleshootingp.15411.5.2 Output Circuit Troubleshootingp.15711.6 Special Relay Listp.15811.7 Special Register Listp.180APPENDICESp.216APPENDIX 1 Error Code Return to Origin During General Data Processingp.216APPENDIX 1.1 Error code overall explanationp.216APPENDIX 1.2 Description of the errors of the error codes (4000H to 4FFFH)p.217APPENDIX 2 External Dimensionsp.222APPENDIX 2.1 CPU modulep.222APPENDIX 2.2 Power supply modulep.222APPENDIX 2.3 Main base unitp.225APPENDIX 2.4 Slim type main base unitp.227APPENDIX 2.5 Extension base unitp.228APPENDIX 3 Upgraded Functions of High Performance Model QCPUp.231APPENDIX 3.1 Specification comparisonp.231APPENDIX 3.2 Function comparisonp.231APPENDIX 3.3 Added functions and the corresponding GX Developer versionsp.232INDEXp.233WARRANTYp.235
Page 18 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 17 A - 17
Page 18 · click to enlarge
Page 18

About Manuals

The following manuals are related to this product.

Referring to this list, please request the necessary manuals.

Related Manuals

Manual Name Manual Number

(Model Code)

High Performance model QCPU (Q Mode) User's Manual (Function Explanation, Program Fundamentals)

SH-080038

This manual explains the functions, programming methods, devices and so on necessary to create

(13JL98)

programs with the High Performance model QCPU. (sold separately)

QCPU (Q Mode)/QnACPU Programming Manual (Common Instructions)

SH-080039

This manual describes how to use the sequence instructions, basic instructions and application

(13JF58)

instructions. (sold separately)

QCPU (Q Mode)/QnACPU Programming Manual (PID Control Instructions)

SH-080040

(13JF59)

This manual describes the dedicated instructions used to exercise PID control. (sold separately)

QCPU (Q Mode)/QnACPU Programming Manual (SFC)

SH-080041

This manual explains the system configuration, performance specifications, functions, programming,

(13JF60)

debugging, error codes and others of MELSAP3. (sold separately)

QCPU (Q Mode) Programming Manual (MELSAP-L)

SH-080076

This manual describes the programming methods, specifications, functions, and so on that are

(13JF61)

necessary to create the MELSAP-L type SFC programs. (sold separately)

A - 17 A - 17

Page 19 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 18 A - 18
Page 19 · click to enlarge
Page 19

How to Use This Manual

This manual is prepared for users to understand the hardware specifications of those modules such as the CPU modules, power supply modules, and base units, maintenance and inspections of the system, and troubleshooting required when you use MELSEC-Q series PLCs.

The manual is classified roughly into three sections as shown below.

1. Chapters 1 and 2 Describe the outline of the CPU module and the system configuration. The basics of the system configuration of CPU module are described.
2. Chapters 3 to 7 Describe the general specifications indicating the operating environments of the CPU module, power supply module, and base units, and the performance specifications of these modules.
3. Chapters 8 to 10 Describe the overall maintenance such as the installation of the CPU module, daily inspections, and troubleshooting.

REMARK

This manual does not explain the functions of the CPU module. For these functions, refer to the manual shown below. • High Performance model QCPU (Q Mode) User's Manual (Function Explanation, Program Fundamentals)

A - 18 A - 18

Page 20 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — A - 19 A - 19
Page 20 · click to enlarge
Page 20

About the Generic Terms and Abbreviations

This manual uses the following general names and abbreviations in the descriptions of the High Performance model QCPU unless otherwise specified.

Generic Term/Abbreviation Description High Performance model QCPU

General name for Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU modules. Q Series Abbreviation for Mitsubishi MELSEC-Q Series Programmable Logic Controller.

AnS Series Abbreviation for small types of Mitsubishi MELSEC-A Series Programmable Logic Controller. GX Developer General name for GX Developer Version 4 or later.

General name for Q33B, Q35B, Q38B, Q312B type main base unit with High Performance model QCPU and Q Series power supply module, I/O module and intelligent function module attachable.

Q3 B

General name for Q32SB, Q33SB, Q35SB slim type main base unit with High Performance model QCPU and slim type power supply module, I/O module and intelligent function module attachable.

Q3 SB

Q5 B General name for Q52B and Q55B type extension base unit with Q Series I/O module and intelligent function module attachable.

Q6 B General name for Q63B, Q65B, Q68B and Q612B type extension base unit with Q Series power supply module, I/O module and intelligent function module attachable.

QA1S6 B General name for QA1S65B and QA1S68B type extension base unit with AnS Series power supply module, I/O module and special function module attachable.

General name for Q33B, Q35B, Q38B, Q312B type main base unit with High Performance model QCPU and Q Series power supply module, I/O module and intelligent function module attachable.

Main base unit

General name for Q32SB, Q33SB, Q35SB slim type main base unit with High Performance model QCPU and slim type power supply module, I/O module and intelligent function module attachable. Extension base unit General name for Q5 B, Q6 B and QA1S6 B. SRAM card Abbreviation for Q2MEM-1MBS, Q2MEM-2MBS type SRAM card. Flash card General name for Q2MEM-2MBF and Q2MEM-4MBF types Flash card.

Slim type main base unit

ATA card General name for Q2MEM-8MBA, Q2MEM-16MBA and Q2MEM-32MBA types ATA card. Memory card General name for SRAM card, Flash card and ATA card.

Power supply module General name for Q61P-A1, Q61P-A2, Q62P, Q63P, Q64P, A1S61PN, A1S62P and A1S63P types power supply module. Slim type power supply module General name for Q61SP slim type power supply module

Battery General name for battery for Q6BAT type CPU module and Q2MEM-BAT type SRAM card.

Extension cable General name for QC05B, QC06B, QC12B, QC30B, QC50B, QC100B type extension cable.

A - 19 A - 19

Page 21 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 1 - 1 1 - 1
Page 21 · click to enlarge
Page 21

MELSEC-Q 1 OVERVIEW

1 OVERVIEW

This Manual describes the hardware specifications and handling methods of the High Performance model QCPU. The Manual also describes those items related to the specifications of the power supply module, main base unit, extension base unit, extension cable, memory card and battery. Functions are added when the High Performance model QCPU is updated. The added functions can be discriminated by the function version/serial number of the CPU module. Table 1.1 gives the added functions and the corresponding GX Developer versions. When using the added function, confirm the function version/serial number and the GX Developer version. Table 1.1 List of Functions Added to High Performance Model QCPU and Function

Versions/Serial Numbers

Update Details of High Performance Model QCPU Function

Corresponding

GX Developer

version Serial No. Added functions

  • Automatic write to standard ROM
  • Enforced ON/OFF for external I/O
  • Remote password setting
  • Increased standard RAM capacity of Q12HCPU, Q25HCPU
  • Compatibility with MELSECNET/H remote I/O network
  • Interrupt module (QI60) compatibility

A " 02092 " or later

Version 6 or later

— • Compatibility with the multiple CPU system Version 6 or later

"03051" or later • Installation of PC CPU module into the

multiple CPU system Version 7 or later

  • High speed interrupt function
  • Compatibility with index modification for module designation of dedicated instruction
  • Selection of refresh item for COM instruction
  • Extended life battery of SRAM card
  • Compatibility with 2Mbyte SRAM card
  • Increased standard RAM capacity of Q02HCPU, Q06HCPU

B

Version 7.10L or later

" 04012 " or later

POINT (1) For the details of the added functions in Table 1.1, refer to the High

Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals). (2) Refer to Section 2.3 for the serial No. and function version of the High

Performance model QCPU.

1 - 1 1 - 1

Page 22 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 1 - 2 1 - 2
Page 22 · click to enlarge
Page 22

MELSEC-Q 1 OVERVIEW

1.1 Features

High Performance model QCPU has the following new features: (1) Controllable multiple I/O points

All High Performance model QCPUs support 4096 points (X/Y0 to FFF) as the number of actual I/O points capable of getting access to the I/O module installed on the base unit. They also support 8192 points max. (X/YO to 1FFF) as the number of I/O devices which can be used in the remote I/O stations such as MELSECNET/H remote I/O NET, CC-Link data link and MELSECNET/MINI-S3 data link.

(2) Lineup according to program capacity

The optimum CPU module for the program capacity to be used can be selected. Q02CPU, Q02HCPU : 28k step Q06HCPU : 60k step Q12HCPU : 124k step Q25HCPU : 252k step

(3) Realised high speed processing

Depending on the type of the sequencer, high speed processing has been realized.(Example: when LD instruction is used) Q02CPU : 0.079 s Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU : 0.034 s In addition, an access to the intelligent function module or an increase in speed of the link refresh of the network have been realized by the connection system (System bus connection) of the newly developed base unit. Access to the intelligent function module : 20 s /word (approx. 7 times) 1 MELSECNET/H link refresh processing : 4.6ms/8k word (approx. 4.3 times) 1 1: Where Q02HCPU is compared with Q2ASHCPU-S1.

(4) Increase in debugging efficiency through high speed

communication with GX Developer In the High Performance model QCPU, a time required for writing/reading of a program or monitoring has been reduced through the high speed communication at a speed of 115.2kbps max. by the RS-232, and a communication time efficiency at the time of debugging has been increased. In the Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU, a high speed communication at a speed of 12Mbps is allowed through the USB.

26k step program transfer time

Q25HCPU(USB)

Q25HCPU(RS-232)

Q2ASHCPU

A2USHCPU-S1

(Unit:s) 90 100

0 10 20 30 40 50 60 70 80

(5) AnS series I/O module or special function module are available.

For Q series, if an appropriate module is not available, the AnS series I/O module or special function module can also be used for the High Performance model QCPU through the use of the QA1S65B/QA1S68B extension base unit.

1 - 2 1 - 2

Page 23 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 1 - 3 1 - 3
Page 23 · click to enlarge
Page 23

MELSEC-Q 1 OVERVIEW

(6) Saved space by a reduction in size

The installation space for Q series has been reduced by approx. 60 % of the space for AnS series.

Comparison of installation space

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 1 OVERVIEW diagram (page 23)
Fig. 2

98mm (3.86 inch)

(7) Connection of up to seven extension base units.

(a) The High Performance model QCPU can connect to seven extension base

units (eight base units including the main) and accept up to 64 modules.

(b) The overall distance of the extension cables is up to 13.2m to ensure high

degree of extension base unit arrangement.

(8) Memory extension by memory card

The High Performance model QCPU is provided with a memory card installation connector to which a memory card of 32 Mbyte max. can be connected (32 Mbyte is available when a ATA card is used). When a memory card of large capacity is installed, a large capacity of file can be controlled, comments to all data devices can be set up, and the programs in the past can be stored in the memory as they are in the form of the corrected histories. If a memory card is not installed, a program can be stored onto the standard ROM built in the CPU module, and file registers can be handled by the standard RAM.

REMARK

  • The number of file registers that can be handled changes depending on the function version/serial number of the CPU module used.

CPU Module Type Number of File Registers Q02CPU 32k points First 5 digits of serial number are "04011" or earlier 32k points Q02HCPU Q06HCPU First 5 digits of serial number are "04012" or later 64k points First 5 digits of serial number are "02091" or earlier 32k points Q12HCPU Q25HCPU First 5 digits of serial number are "02092" or later 128k points

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — REMARK diagram (page 23)
Fig. 3

Refer to Section 2.3 to confirm the function version and serial number of the High Performance model QCPU.

1 - 3 1 - 3

Page 24 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 1 - 4 1 - 4
Page 24 · click to enlarge
Page 24

MELSEC-Q 1 OVERVIEW

(9) Data can be written automatically to standard ROM

You need not use GX Developer to write parameters/programs on a memory card to the standard ROM of the High Performance model QCPU. When the standard ROM is used to perform ROM operation, you can load a memory card into the High Performance model QCPU and write parameters/programs on the memory card to the standard ROM. Hence, you need not carry GX Developer (personal computer) to rewrite the parameters/programs.

(10) External I/O can be turned ON/OFF forcibly

If the High Performance model QCPU is in the RUN mode, you can operate GX Developer to turn external inputs/outputs ON/OFF forcibly, independently of the program execution status. You need not put the High Performance model QCPU in the STOP mode to perform wiring/operation tests by forced ON/OFF of outputs.

(11) Remote password can be set

When access to an Ethernet module or serial communication module is made externally, whether access to the High Performance model QCPU can be made or not can be selected with a remote password.

(12) Remote I/O network of MELSECNET/H can be configured

You can load the remote master station of the MELSECNET/H to configure an MELSECNET/H remote I/O system.

REMARK

  • Features (9) to (12) are functions added to the High Performance model QCPU whose serial number is "02092" or later in its upper 5 digits.
  • The remote password facility can be executed when the Ethernet module or serial communication module of function version B and GX Developer Version 6 or later are used.
  • In addition to the remote password, there are the following protection facilities for the High Performance model QCPU. (a) Protection of the whole CPU module by making system protection settings of

the High Performance model QCPU (b) Protection of the memory card by setting the write protect switch of the memory

card (c) File-by-file protection using password • The MELSECNET/H remote I/O network facility can be executed when the MELSECNET/H network module of function version B and GX Developer (Version 6 or later) are used.

1 - 4 1 - 4

Page 25 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 1 2 - 1
Page 25 · click to enlarge
Page 25

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

This section describes the system configuration of the High Performance model QCPU, cautions on use of the system, and configured equipment. 2.1 System Configuration

The outline of the equipment configuration, configuration with peripheral devices, and system configuration in the High Performance model QCPU system is described below.

(1) Equipment configuration

(a) If the main base unit (Q3 † B) is used

MITSUBISHI

MITSUBISHI LITHIUM BATTERY

High Performance model QCPU (Q02CPU,Q02HCPU,Q06HCPU,

Q2MEM-2MBF,Q2MEM-4MBF, Q2MEM-8MBA,Q2MEM-16MBA,

Q12HCPU,Q25HCPU)

Q2MEM-32MBA)

Power supply module , I/O module , Intelligent function

Main base unit (Q33B, Q35B,Q38B,Q312B)

module of the Q Series

Extension of the AnS Series module Extension of the Q Series module

Q5 B extension base unit

Extension cable (QC05B,QC06B,QC12B, QC30B, QC50B,QC100B)

QA1S6 extension base unit

(Q52B, Q55B) Q6 B extension base unit (Q63B, Q65B,Q68B,Q612B)

(QA1S65B,QA1S68B)

Power supply module , I/O module , Intelligent function

Power supply module , I/O module , Intelligent function

module of the AnS Series

module of the Q Series

POINTS 1: The number of memory cards to be installed is one sheet. The memory card must be selected from SRAM card, Flash card, and ATA card according to the application and capacity. With commercial memory cards, the Operation is not assured. 2: QA1S65B and QA1S68B extension base units are used for the power supply module, I/O module, and special function module of the AnS series. 3: The Q series power supply module is not required for the Q5 B type extension base unit. 4: Q61SP cannot be used for the power supply module. Use Q61P-A1, Q61P-A2, Q62P, or Q64P for the power supply module.

2 - 1 2 - 1

Memory card (Q2MEM-1MBS,Q2MEM-2MBS, · Battery (Q6BAT)

Page 26 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 2 2 - 2
Page 26 · click to enlarge
Page 26

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

(b) If the slim type main base unit (Q3†SB) is used

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM diagram (page 26)
Fig. 4

POINTS 1: The number of memory cards to be installed is one sheet. The memory card must be selected from SRAM card, Flash card, and ATA card according to the application and capacity. With commercial memory cards, the Operation is not assured. 2: The slim type main base unit does not have an extension cable connector. The extension base unit and GOT cannot be connected. 3: Q61P-A1, Q61P-A2, Q62P, or Q64P cannot be used for the power supply module. Use Q61SP for the power supply module.

2 - 2 2 - 2

Page 27 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 3 2 - 3
Page 27 · click to enlarge
Page 27

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

(2) Configuration of peripheral devices

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM diagram (page 27)
Fig. 5

Only Q02HCPU, Q06HCPU Q12HCPU and Q25HCPU can be used.

1. For how to write data to the memory card and the details of the USB cable, refer to the GX Developer Operating Manual.

2 - 3 2 - 3

Page 28 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 4 2 - 4
Page 28 · click to enlarge
Page 28

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

(3) Outline of system configuration

(a) If the main base unit (Q3 † B) is used

0 1 2 3 4 5 6 7 8 9 10 11

Slot No.

A0

E0

OUT

1F

3F

5F

7F

9F

BF

DF

FF

11F

13F

15F

17F

The figure shows the configuration when 32-I/O modules are loaded to each slot. OUT IN

22 21 20 19 18 17 16 15 14 13 12 2A0

1A0

1E0

2E0

19F

1BF

1DF

1FF

21F

23F

25F

27F

29F

2BF

2DF

2FF

31 30 29 28 27 26 25 24 3E0

52 51 50 49 48 47 46 45 680

3A0

5A0

5E0

OUT IN

OUT IN

System configuration

31F

33F

35F

37F

39F

3BF

3DF

3FF

5BF

5DF

5FF

61F

63F

65F

67F

69F

39 38 37 36 35 34 33 32 4E0

60 59 58 57 56 55 54 53 780

4A0

6A0

6E0

OUT IN

OUT IN

41F

43F

45F

47F

49F

4BF

4DF

4FF

6BF

6DF

6FF

71F

73F

75F

77F

79F

44 43 42 41 40 580

63 62 61 7E0

7A0

OUT IN

OUT IN

51F

53F

55F

57F

59F

7BF

7DF

7FF

When module is installed, an error occurs.

Maximum number of Extension Stages Seven Extension Stages

Maximum number of I/O modules to be installed

64 modules

Maximum number of occupied I/O points 4096

Main base unit Q33B, Q35B, Q38B, Q312B Extension base unit Q52B, Q55B, Q63B, Q65B, Q68B, Q612B, QA1S65B, QA1S68B Extension cable QC05B, QC06B, QC12B, QC30B, QC50B, QC100B

(1) Extension bases unit of up to seven stages can be used. (2) Do not use extension cable longer than an overall extension length of 13.2m(43.31ft.). (3) When using an extension cable, do not bind it together with the main circuit (high voltage and

heavy current) line or do not lay down them closely to each other. (4) When setting the No. of the expansion stages, set it in the ascending order so that the same

No. is not set simultaneously by two extension base units. (5) When Q5 B, Q6 B and QA1S6 B types of extension base units are mixed, first connect the Q5 B, Q6 B type and then connect the QA1S6 B type. When setting the No. of the extension stages, set it from Q5 B/Q6 B in order. Although there are no particular restrictions in the order of the installation of the Q5 B and Q6 B, refer to Section 6.6 for usability. (6) Connect the extension cable from OUT of the extension cable connector of the base unit to IN

Notes

of the extension base unit on the next stage. (7) If 65 or more modules are installed, an error will occur. (8) When the GOT is bus-connected, it occupies one extension stage and one slot. (9) The High Performance model QCPU processes the GOT as a 16-point intelligent function

module. Hence, connecting one GOT decreases 16 points available for the base unit. (10) Q61SP cannot be used for the power supply module.

Use Q61P-A1, Q61P-A2, Q62P, or Q64P for the power supply module.

2 - 4 2 - 4

Show 27 more labels / short text on this page
Main base unit(Q312B) · Power supply module · CPU module · Extension cable · Extension base unit(Q612B) · 1st extension stage · Power supply module · Extension base unit(Q68B) · Extension base unit(QA1S68B) · Power supply module · Power supply module · 2nd extension stage · 5th extension stage · Extension base unit(Q68B) · Extension base unit(QA1S68B) · Power supply module · Power supply module · 3rd extension stage · 6th extension stage · Extension base unit(Q65B) · Extension base unit(QA1S65B) · Power supply module · 7th extension stage · Power supply module · 4th extension stage · Prohibit · Prohibit
Page 29 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 5 2 - 5
Page 29 · click to enlarge
Page 29

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

(b) If the slim type main base unit (Q3†SB) is used

0 1 2 3 4 Slot No. Slim type main base unit (Q35SB)

System configuration

1F

3F

5F

7F

9F

The above system assumes that each slot is loading with a 32-point module.

Maximum number of Extension Stages No extension allowed

Maximum number of I/O modules to be installed

5 modules

Maximum number of occupied I/O points 4096

Main base unit Q32SB, Q33SB, Q35SB Extension base unit Cannot be connected. Extension cable Cannot be connected.

(1) Q61P-A1, Q61P-A2, Q62P, or Q64P cannot be used for the power supply module.

Use Q61SP for the power supply module. (2) The slim type main base unit does not have an extension cable connector.

Notes

The extension base unit and GOT cannot be connected.

2 - 5 2 - 5

Power supply · CPU module · module

Page 30 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 6 2 - 6
Page 30 · click to enlarge
Page 30

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

2.2 Precaution on System Configuration

This section describes hardware and software packages compatible with QCPU. (1) Hardware

(a) The number of modules to be installed and functions are limited depending on

the type of the modules.

Applicable Module Type Limit of number of modules

to be installed

  • QJ71LP21
  • QJ71BR11
  • QJ71LP21-25
  • QJ71LP21G
  • QJ71LP21GE

Q Series MELSECNET/H network module

Up to 4 in total of inter-PLC network and remote I/O network modules

Q series Ethernet interface module

  • QJ71E71
  • QJ71E71-B2
  • QJ71E71-100 Up to 4 units

Q series CC-Link system master local module • QJ61BT11 No limit 1

No limit (setting of automatic refresh function not allowed)

MELSECNET/MINI-S3 data link module

  • A1SJ71PT32-S3
  • A1SJ71T32-S3
  • A1SD51S
  • A1SD21-S1
  • A1SJ71J92-S3 (When GET/PUT service is used)

AnS series special function module shown on the right

Total of 6 units

  • Interrupt module
  • A1SI61
  • QI60 One unit only
1. A maximum of 4 modules if the network parameters for CC-Link are set and controlled by the GX Developer. There is no restriction in the number of modules when the parameters are set by the special-purpose instructions for the CC-Link. For details on the CC-Link System Master Local Unit that can set parameters with the special-purpose instructions, refer to the user's manual for the CC-Link Master Local module.

(b) When the AnS series special-function modules shown below are used, a

  • limitation is given to an accessible device range.
  • A1SJ71J92-S3 type JEMANET interface module
  • A1SD51S type intelligent communication

Device Accessible device range

Input (X), Output (Y) X/Y0 to 7FF

Internal relay (M), Latch relay (L) M0 to 8191

Link relay (B) B0 to FFF

Timer (T) T0 to 2047

Counter (C) C0 to 1023

Data register (D) D0 to 6143

Link register (W) W0 to FFF

Annunciator (F) F0 to 2047

(c) A graphic operation terminal can be used only for the GOT900 series (Basic

OS matching Q mode and communication driver must be installed). The GOT800 series, A77GOT, and A64GOT cannot be used.

2 - 6 2 - 6

Page 31 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 7 2 - 7
Page 31 · click to enlarge
Page 31

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

(d) The modules shown below cannot be used.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM diagram (page 31)
Fig. 6

(e) A dedicated instruction for the next module which was present in the QnA/A

series program instruction cannot be used for the High Performance model QCPU. Re-writing using FROM/TO instruction is required.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM diagram (page 31)
Fig. 7

(f) Some system configurations and functions are restricted when writing the

parameter of the "High speed interrupt fixed scan interval" setting. Refer to the following manual for the restrictions when the parameter of the "High speed interrupt fixed scan interval" setting has been written. • High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals) Note that the above restrictions do not apply to the High Performance model QCPU of serial number "04011" or earlier since it ignores the "High speed interrupt fixed scan interval" setting.

(2) Software package

GX Developer that can use the functions added to the High Performance model QCPU changes depending on the function version/serial number of the CPU module.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (2) Software package diagram (page 31)
Fig. 8 · (2) Software package

— Functions added to "03052" Version 7 (SW7D5C-GPPW-E) or later

Refer to Section 2.3 to confirm the function version and serial number of the High Performance model QCPU.

2 - 7 2 - 7

Page 32 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2 - 8 2 - 8
Page 32 · click to enlarge
Page 32

MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

2.3 Confirming the Serial Number and Function Version

The CPU module serial No. can be confirmed on the rated plate and GX Developer's system monitor. (1) Confirming the serial No. on the rated plate

The serial No. and function version can be confirmed on the rating plate.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM diagram (page 32)
Fig. 9

Serial No. (First five digits)

(2) Confirming the serial No. on the system monitor (list of product

information) The CPU module serial No. and function version can be confirmed with the list of product information on the GX Developer (Version 6 or later) system monitor. Serial Nos. and function versions of the intelligent function module and CPU module can also be confirmed.

Serial number Function version

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (2) Confirming the serial No. on the system monitor (list of product diagram (page 32)
Fig. 10 · (2) Confirming the serial No. on the system monitor…

2 - 8 2 - 8

Function version

Page 33 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 3 - 1 3 - 1
Page 33 · click to enlarge
Page 33

MELSEC-Q 3 GENERAL SPECIFICATIONS

3 GENERAL SPECIFICATIONS

Performance specification of PLC is as follows:

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Performance specification of PLC is as follows: diagram (page 33)
Fig. 11 · Performance specification of PLC is as follows:

Shock resistance Conforming to JIS B 3502, IEC 61131-2 (147 m/s2, 3 times in each of 3 directions X, Y, Z)

1 : This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V. 2 : This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected occasionally. 3 : The storage ambient temperature is -20 to 75°C if the system includes the AnS series modules. 4 : The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system includes the AnS series modules. 5 : Do not use or store the PLC under pressure higher than the atmospheric pressure of altitude 0m. Doing so can cause a malfunction. When using the PLC under pressure, please contact your sales representative.

3 - 1 3 - 1

Page 34 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 3 - 2 3 - 2
Page 34 · click to enlarge
Page 34

MELSEC-Q 3 GENERAL SPECIFICATIONS

MEMO

3 - 2 3 - 2

Page 35 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4 - 1 4 - 1
Page 35 · click to enlarge
Page 35

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

4 HARDWARE SPECIFICATION OF THE CPU MODULE

4.1 Performance Specification

The table below shows the performance specifications of the CPU module.

Performance Specifications

Q02CPU Q02HCPU Q06HCPU Q12HCPU Q25HCPU

Control method Repetitive operation of stored program

Direct I/O is possible by direct I/O specification (DX , DY ) Programming language (Sequence control dedicated language)

I/O control mode Refresh mode

Relay symbol language, logic symbolic language,

MELSAP3 (SFC), MELSAP-L, Function block ——

LD X0 0.079 s 0.034 s —— Processing speed (Sequence instruction) MOV D0 D1 0.237 s 0.102 s ——

Total number of instructions 360 (excluding intelligent function module dedicated instructions) ——

Constant scan (Function for setting the scan timer to fixed settings)

0.5 to 2000 ms (configurable in increments of 0.5 ms) Set parameter values to

Program memory (Drive 0) 28k step 60k step 124k step 252k step ——

Program memory (Drive 0) 112 kbyte 240 kbyte 496 kbyte 1008 kbyte ——

Memory card (RAM) (Drive 1) Capacity of loading memory cards(2Mbyte max.)

For memory capacity, refer to Section 7.1.

Memory card (ROM) (Drive 2)

Installed memory card capacity (Flash card: 4 Mbyte max., ATA card: 32 Mbyte max.)

Standard RAM (Drive 3) 64kbyte 128kbyte 5 256kbyte 3 ——

Standard ROM (Drive 4) 112 kbyte 240 kbyte 496 kbyte 1008 kbyte ——

4 8 kbyte ——

Program memory 28 60 124 252 1 —— Memory card (RAM) 256 —— Flash card 288 —— Memory card (ROM) ATA card 512 ——

Maximum number of stored files

Standard RAM 2 Only one file register and one local device

Standard ROM 28 60 124 252 —— Standard ROM number of writings Max. 100000 times ——

Number of I/O device points 8192 points (X/Y0 to 1FFF) Number of devices usable on program

Number of occupied I/O points 4096 points (X/Y0 to FFF) Number of points accesible to actual I/O modules 1:124 is the maximum number of programs that can be executed on High Performance model QCPU. 2: The maximum number of sequence steps that can be executed for one program by the High Performance model QCPU with the parameters stored in another drive is calculated with the following expression. (Program size) - (File header size (default: 34 steps)) Refer to the High Performance model QCPU User's Manual (Function Explanation, Program Fundamentals) for details on the program size and file. 3: The memory capacity of the Q12HCPU or Q25HCPU whose first five digits of serial No. are "02091" or earlier is 64K bytes. (Refer to Section 2.3 for the way to confirm the serial No.) 4:The CPU shared memory is not latched. The CPU shared memory is cleared when the power is turned on to the PLC or when the CPU module is reset. 5:The memory capacity of the Q02HCPU or Q06HCPU whose first five digits of serial No. are "04011" or earlier is 64K bytes. (Refer to Section 2.3 for the way to confirm the serial No.)

4 - 1 4 - 1

Show 6 more labels / short text on this page
Model Item · Remark · specify · Program 2 capacity · Memory capacity · CPU shared memory
Page 36 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — [ZR]
Page 36 · click to enlarge
Page 36

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

Performance Specifications (continued)

Q02CPU Q02HCPU Q06HCPU Q12HCPU Q25HCPU

Internal relay [M] Default 8192 points (M0 to 8191)

Latch relay [L] Default 8192 points (L0 to 8191)

Link relay [B] Default 8192points (B0 to 1FFF)

Default 2048 points (T0 to 2047) (for low / high speed timer) Select between low / high speed timer by instructions. The measurement unit of the low / high speed timer is set with parameters. (Low speed timer : 1 to 1000ms, 1ms/unit, default 100ms) (High speed timer : 0.1 to 100ms, 0.1ms/unit, default 10ms)

Default 0 point(for low / high speed retentive timer) Switchover between the low / high speed retentive timer is set by instructions. The measurement unit of the low /high speed retentive timer is set with parameters. (Low speed retentive timer : 1 to 1000ms, 1ms/unit, default 100ms) (High speed retentive timer : 0.1 to 100ms, 0.1ms/unit, default 10ms)

Number of use points

is set with parameters.

  • Normal counter default 1024 points (C0 to 1023)
  • Interrupt counter maximum 256 points (default 0 point, set with parameters)

Data register [D] Default 12288 points (D0 to 12287)

Link register [W] Default 8192 points (W0 to 1FFF)

Annunciator [F] Default 2048 points (F0 to 2047)

Edge relay [V] Default 2048 points (V0 to 2047)

Number of device points

  • When a standard RAM is used: Q02CPU ..........................32768 points (R0 to 32767) Q02HCPU, Q06HCPU.....The number of points of up to 65536 points

can be used by block conversion in increments of 32768 points (R0 to 32767) Q12HCPU, Q25HCPU The number of points of up to 131072

  • points can be used by block conversion in increments of 32768 points (R0 to 32767)
  • When a SRAM card (1Mbyte) is used: The number of points of up to 517120 points can be used by block conversion in increments of 32768 points (R0 to 32767).
  • When a SRAM card (2Mbyte) is used: The number of points of up to 1041408 points can be used by block conversion in increments of 32768 points (R0 to 32767).
  • When a Flash card (2Mbyte) is used: The number of points of up to 1041408 points can be used by block conversion in increments of 32768 points (R0 to 32767).
  • When a Flash card (4Mbyte) is used: The number of points of up to 1042432 points can be used by block conversion in increments of 32768 points (R0 to 32767).

[R]

When a Flash card is

used, read only is

possible.

The ATA card cannot

be used.

  • When a standard RAM is used: Q02CPU ..........................32768 points (ZR0 to 32767) Q02HCPU, Q06HCPU.....65536 points (ZR0 to 65535), No block

conversion necessary. Q12HCPU, Q25HCPU 131072 points (ZR0 to 131071), No block

  • conversion necessary.
  • When a SRAM card (1Mbyte) is used: 517120 points (ZR0 to 517119) , No block conversion necessary.
  • When a SRAM card (2Mbyte) is used: 1041408 points (ZR0 to 1041407), No block conversion necessary.
  • When a Flash card (2Mbyte) is used: 1041408 points (ZR0 to 1041407), No block conversion necessary.
  • When a Flash card (4Mbyte) is used: 1042432 points (ZR0 to 1042431), No block conversion necessary.

[ZR]

4 - 2 4 - 2

Show 6 more labels / short text on this page
Model Item · Remark · Timer [T] · Retentive timer [ST] · Counter [C] · File register
Page 37 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5VDC internal current consumption 0.60A 0.64A 0.64A 0.64A 0.64A ——
Page 37 · click to enlarge
Page 37

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

Performance Specifications (continued)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE diagram (page 37)
Fig. 12

Link special relay [SB] 2048 points (SB0 to 7FF)

Link special register [SW] 2048 points (SW0 to 7FF)

4096 points (P0 to 4095), set parameter values to select usable range

The specified intervals of the system interrupt pointers I28 to I31 can

be set with parameters.(0.5 to 1000ms, 0.5 ms /unit )

Default I28100ms I29 : 40ms I30 : 20ms I31 : 10ms
Specified formJ \X , J \Y , J \W ,

Device having a direct access to the buffer memory of the intelligent

(Latch range can be set for B, F, V, T, ST, C, D, and W.)

RUN and PAUSE contacts can be set from among X0 to 1FFF,

Year, month, day, hour, minute, second, day of the week

Accuracy -3.18 to +5.25s (TYP. +2.12s) /d at 0°C

Allowable momentary power failure period Varies according to the type of power supply module. ——

5VDC internal current consumption 0.60A 0.64A ——

4 - 3 4 - 3

Page 38 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4 - 4 4 - 4
Page 38 · click to enlarge
Page 38

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

4.2 Part Names and Settings

This section explains the part names and settings of the module.

Front face

With front cover open

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Front face diagram (page 38)
Fig. 13 · Front face
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Front face diagram (page 38)
Fig. 14 · Front face
11. 1

When opening the front cover, put your finger here.

Side face

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Side face diagram (page 38)
Fig. 15 · Side face
1. Not provided for Q02CPU.

4 - 4 4 - 4

Show 12 more labels / short text on this page
2) · 3) · 4) · 5) · 6) · 13) · 7) · 14) · 15) · 16) · 17) · 19)
Page 39 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4 - 5 4 - 5
Page 39 · click to enlarge
Page 39

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

No. Name Application 1) Module fixing hook Hook used to fix the module to the base unit. (Single-motion installation)

Indicates the mode of the CPU module. ON (green) : Q mode ON (orange) : A mode Flicker (green) : Enforced ON/OFF for external I/O registered

2) "Mode" LED

Indicates the operating status of the CPU module. ON : During operation in "RUN" status. OFF : During a stop in "STOP" status or detection of error whose occurrence stops

operation. FlickerWhen parameter/program is written at STOP and RUN/STOP switch is

changed from "STOP" to "RUN". To turn ON the RUN LED after writing the program, carry out the following steps. y Set the RUN/STOP switch from "RUN" → "STOP" → "RUN". y Reset with the RESET/L.CLR switch. y Restart the PLC power. To turn ON the RUN LED after writing the parameters, carry out the following steps. y Reset with the RESET/L.CLR switch. y Restart the PLC power. (If the RUN/STOP switch is set from "RUN" → "STOP" → "RUN" after changing the parameters, the parameters related to the intelligent function module, such as the network parameters, will not be reflected.)

3) "RUN" LED

ONDetection of self-diagnosis error which will not stop operation, except battery

error. (When operation continued at error detection is set in the parameter.) OFF : Normal Flicker : Detection of error whose occurrence stops operation.

4) "ERR." LED

When automatic write to standard ROM is completed normally. ("BOOT" LED also flickers.)

5. "USER" LED ON : Error detected by CHK instruction or annunciator ON OFF : Normal Flicker : Execution of latch clear
6. "BAT." LED ON : Occurrence of battery error due to reduction in battery voltages of CPU module

or memory card. OFF : Normal

ON : Start of boot operation OFF : Non-execution of boot operation Flicker : When automatic write to standard ROM is completed normally. ("ERR." LED

7) "BOOT" LED

also flickers.) 8) Module loading lever Used to load the module to the base unit.

4 - 5 4 - 5

Page 40 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — CPU module
Page 40 · click to enlarge
Page 40

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

No. Name Application 9) Memory card EJECT button Used to eject the memory card from the CPU module.

10. Memory card loading connector Connector used to load the memory card to the CPU module.
11. USB connector 1 Connector for connection with USB-compatible peripheral device. (Connector type B) Can be connected by USB-dedicated cable. Not available for Q02CPU.
12. RS-232 connector 1 Connector for RS-232 connection Can be connected by RS-232 connection cable (QC30R2). Used to set the items for operation of the CPU module. For system protection and parameter-valid drive functions, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals). SW1 : Used to set system protection. Batch-inhibits write and control directives to the

DIP switches

CPU module. (Shipped in OFF position) OFF : No protection ON : Protection SW2, SW3: Used to specify parameter-valid drive.

ON SW

13)

(Both SW2 and SW3 are shipped in OFF position)

SW2 SW3 Parameter Drive

OFF OFF Program memory (Drive 0) ON OFF SRAM card (Drive 1) OFF ON Flash card/ATA card (Drive 2)

ON ON Standard ROM (Drive 4)

SW5 : Must not be used. Normally OFF. (Shipped in OFF position)

14. RUN/STOP switch RUN : Executes sequence program operation. STOP : Stops sequence program operation.

RESET : Used to perform hardware reset, operation fault rest, operation initialization,

etc. If this switch is left in the RESET position, the whole system will be reset and the system will not operate properly. After performing reset, always return this switch to the neutral position. L.CLR : Used to turn "OFF" or "zero" all data in the parameter-set latch area.

15) RESET/L.CLR switch

Used to clear the sampling trace and status latch registration. 16) Module fixing screw hole Hole for the screw used to fix to the base unit. (M3 12 screw) 17) Module fixing latch Hook used to fix to the base unit.

18. Battery connector pin For connection of battery lead wires. (When shipped from the factory, the lead wires are disconnected from the connector to prevent the battery from consuming.)
19. Battery Backup battery for use of program memory, standard RAM and power failure compensation function.
1. When normally connecting a cable to the USB connector or RS-232 connector, clamp the cable to prevent it from coming off due to the dangling, moving or carelessly pulling of the cable. Q6HLD-R2 type RS-232 Connector Disconnection Prevention Holder is available as a clamp for RS-232 connector.

CPU module

Q6HLD-R2

RS-232 cable

4 - 6 4 - 6

Page 41 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4 - 7 4 - 7
Page 41 · click to enlarge
Page 41

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

4.3 Switch Operation After Writing in Program

When writing a program into the CPU module, do not turn off the system protect set switch SW1 in advance (When the switch is turned off, the system will not be protected).

(1) When a program is written while CPU module is stopped:

When a program is written while the CPU module is stopped, operate the switch in the order shown below. 1) RUN / STOP switch : STOP "RUN" LED: Turns off CPU module in stop status Write a program.

2. RESET / L.CLR switch : Tilt this switch to RESET once, and return it to the original center position.
3. RUN / STOP switch : STOP RUN "RUN" LED: Turns on CPU module in running status

(2) When a program is written while CPU module is running:

When a program is written while the CPU module is running, the switch need not be operated.

POINTS (1) Even if the RUN/STOP switch is set to RUN immediately after a program is

written when the CPU module is in the stop status, CPU module will not come into RUN status. When the CPU module is reset with the RESET / L.CLR switch and the RUN/STOP switch is set to RUN after a program has been written, the CPU module can be brought into RUN status. (2) If the CPU module is desired to be brought into RUN status without resetting it,

operate the RUN/STOP switch from STOP to RUN, RUN to STOP, and STOP to RUN in that order. After the seconds STOP to RUN switch operation, the CPU module is brought into RUN status. (3) When a program is written while the CPU module is running in boot operation,

the program written during the running is written into the program memory. After a program has been written while the CPU module is running, write the program also into the boot original memory. Failure to write a program into the boot original memory will run an old program at the time of the next boot operation. (For details of the boot operation, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals) ).

4 - 7 4 - 7

Page 42 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4 - 8 4 - 8
Page 42 · click to enlarge
Page 42

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

4.4 Latch Clear Operation

To perform latch clear, operate the RESET/L.CLR switch in the following procedure.

1) RUN/STOP switch : STOP

2. RESET/L.CLR switch : Move the switch to L.CLR several times until the USER LED flickers. "USER" LED: Flicker Ready for latch clear.
3. RESET/L.CLR switch : Move the switch to L.CLR once more. "USER" LED: OFF Latch clear complete.

POINTS (1) The ineffective range for latch clear can be set for each device by the device

setting parameter. (2) In addition to the way of using the RESET/L.CLR switch for latch clear, remote

latch clear may be performed from GX Developer. For details of the remote latch clear operation using GX Developer, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals). 4.5 Executing Automatic Write to Standard ROM.

(1) Order of execution for automatic write to standard ROM

Automatic write to the standard ROM is carried out with the following procedures. (a) Operation with GX Developer (setting automatic write to standard ROM)

1. Check the " Auto Download all Data from Memory card to Standard ROM " item in the PLC parameter boot file setting. Set the parameter and program to be booted at the "Boot file setting" section. (Set the "Transfer from" to "Standard ROM".)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) Order of execution for automatic write to standard ROM diagram (page 42)
Fig. 16 · (1) Order of execution for automatic write to standa…

Check "Auto Download all

Data from Memory card to

Standard ROM ".

Set the "Transfer from" to "Standard ROM".

2. Store the set parameters and programs to be booted in the memory card.

4 - 8 4 - 8

Page 43 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4 - 9 4 - 9
Page 43 · click to enlarge
Page 43

MELSEC-Q 4 HARDWARE SPECIFICATION OF THE CPU MODULE

(b) Operations with CPU module (automatic write to standard ROM)

1. Switch OFF the power supply to the PLC.
2. Mount the memory card that contains the parameters and programs to be booted onto the CPU module.
  • 3) Set the parameter's valid drive in the mounted memory card with the CPU module's dip switches.
  • When a SRAM card is mounted: SW2 : ON, SW3 : OFF
  • When a Flash card/ATA card is mounted: SW2 : OFF, SW3 : ON
4. Switch on the power supply to the PLC.
5. "BOOT" LED will flicker when automatic write to standard ROM has been completed, and the CPU module will assume a suspension error status.
6. Switch OFF the power supply to the PLC.
7. Remove the memory card, and then set the parameter's valid drive in the standard ROM with the CPU module's dip switches. • Standard ROM: SW2 : ON, SW3 : ON

(c) The parameters and programs will be booted from the standard ROM to the

program memory when the PLC is switched on to enable actual operations.

4 - 9 4 - 9

Page 44 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 1 5 - 1
Page 44 · click to enlarge
Page 44

MELSEC-Q 5 POWER SUPPLY MODULE

5 POWER SUPPLY MODULE

5.1 Specification

5.1.1 Power supply module specifications

This section gives the specifications of the power supply modules.

Performance Specifications Item Q61P-A1 Q61P-A2 Q62P Q63P Base loading position Power supply module loading slot Applicable base unit Q3†B, Q6†B

100 to 120VAC +10% -15% 200 to 240VAC +10% -15% 100 to 240VAC +10% -15% 24VDC +30% -35% Input power supply

(85 to 132VAC) (170 to 264VAC) (85 to 264VAC) (15.6 to 31.2VDC) Input frequency 50/60Hz ±5% —— Input voltage distortion factor Within 5% (refer to section 5.1.3) —— Max. input apparent power 105VA —— Max. input power —— 45W Inrush current 20A within 8ms 100A within 1ms 5VDC 6A 3A 6A Rated output current 24VDC —— 0.6A —— External output voltage —— 24VDC ±10% —— 5VDC 6.6A or more 3.3A or more 6.6A or more Overcurrent protection 1 24VDC —— 0.66A or more —— 5VDC 5.5 to 6.5V Overvoltage protection 2 24VDC —— Efficiency 70% or more 65% or more 70% or more Allowable momentary power failure period 3 Within 20ms Within 10ms (at 24VDC input)

Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.)) 500VAC across primary and 5VDC

Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester

10M or more by insulation resistance

By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency Operation indication LED indication (lit at 5VDC output) Fuse Built-in (Unchangeable by user)

  • By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency
  • Noise voltage IEC61000-4-4, 2kV

Application ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU module), for CPU module operating status output Rated switching voltage, current 24VDC, 0.5A

Minimum switching load 5VDC, 1mA Response time OFF to ON: 10ms max. ON to OFF: 12ms max.

Life Mechanical : More than 2 million times Electrical : More than 100 thousand times at rated switching voltage, current Surge suppressor No

Fuse No Terminal screw size M3.5 × 7 Applicable wire size 0.75 to 2mm2 Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5 Applicable tightening torque 66 to 89N•cm H 98mm (3.86inch) W 55.2mm (2.33inch) External dimensions D 90mm (3.55inch) Weight 0.31kg 0.39kg 0.33kg

5 - 1 5 - 1

Show 4 more labels / short text on this page
Insulation resistance · tester · Noise durability · Contact output section
Page 45 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 2 5 - 2
Page 45 · click to enlarge
Page 45

MELSEC-Q 5 POWER SUPPLY MODULE

Power Supply Module Specifications (Continued)

Q64P

Base loading position Power supply module loading slot

Applicable base unit Q3†B, Q6†B

100 to 120VAC/200 to 240VAC +10% -15% Input power supply

(85V to 132VAC/170 to 264VAC)

Input frequency 50/60Hz ±5%

Input voltage distortion factor Within 5% (refer to section 5.1.3)

Max. input apparent power 160VA

Inrush current 20A within 8ms

5VDC 8.5A Rated output current 24VDC ——

5VDC 9.9A or more Overcurrent protection*1 24VDC ——

5VDC 5.5 to 6.5V Overvoltage protection*2 24VDC ——

Efficiency 70% or more

Allowable momentary power failure period*3 Within 20ms

Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.))

Insulation resistance Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester

  • By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency
  • Noise voltage IEC61000-4-4, 2kV

Operation indication LED indication (lit at 5VDC output)

Fuse Built-in (Unchangeable by user)

Application ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU

module), for CPU module operating status output

Rated switching voltage, current 24VDC, 0.5A

Minimum switching load 5VDC, 1mA

Response time OFF to ON: 10ms max. ON to OFF: 12ms max.

Life Mechanical : More than 2 million times Electrical : More than 100 thousand times at rated switching voltage, current

Terminal screw size M3.5 × 7

Applicable wire size 0.75 to 2mm2

Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5

Applicable tightening torque 66 to 89N•cm

H 98mm (3.86inch)

W 55.2mm (2.33inch) External dimensions

D 115mm (4.53inch)

Weight 0.40kg

5 - 2 5 - 2

Show 5 more labels / short text on this page
Performance Specifications Item · Noise durability · Contact output section · Surge suppressor No · Fuse No
Page 46 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 3 5 - 3
Page 46 · click to enlarge
Page 46

MELSEC-Q 5 POWER SUPPLY MODULE

Q61SP

Base loading position Slim type power supply module loading slot

Applicable base unit Q3†SB

100 to 240VAC +10% -15% Input power supply

Input frequency 50/60Hz ±5%

Input voltage distortion factor Within 5% (refer to section 4.3.1)

Max. input apparent power 40VA

Inrush current 20A within 8ms

5VDC 2A Rated output current 24VDC ——

5VDC 2.2A or more Overcurrent protection*1 24VDC ——

5VDC 5.5 to 6.5V Overvoltage protection*2 24VDC ——

Efficiency 70% or more

Allowable momentary power failure period*3 Within 20ms

Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.))

Insulation resistance Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester

  • By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency
  • Noise voltage IEC61000-4-4, 2kV

Operation indication LED indication (lit at 5VDC output)

Fuse Built-in (Unchangeable by user)

Application ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU

module), for CPU module operating status output

Rated switching voltage, current 24VDC, 0.5A

Minimum switching load 5VDC, 1mA

Response time OFF to ON: 10ms max. ON to OFF: 12ms max.

Life Mechanical : More than 20 million times Electrical : More than 100 thousand times at rated switching voltage, current

Terminal screw size M3.5 × 7

Applicable wire size 0.75 to 2mm2

Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5

Applicable tightening torque 66 to 89N•cm

H 98mm (3.86inch)

W 27.4mm (1.08inch) External dimensions

D 104mm (4.09inch)

Weight 0.18kg

5 - 3 5 - 3

Show 6 more labels / short text on this page
Performance Specifications Item · (85 to 264VAC) · Noise durability · Contact output section · Surge suppressor No · Fuse No
Page 47 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 4 5 - 4
Page 47 · click to enlarge
Page 47

MELSEC-Q 5 POWER SUPPLY MODULE

Power Supply Module Specifications (Continued)

A1S61PN A1S62PN A1S63P

Base loading position Power supply module loading slot

Applicable base unit QA1S65B, QA1S68B

100 to 240VAC +10% -15% 24VDC +30% -35% Input power supply

(85 to 264VAC) (15.6 to 31.2VDC)

Input frequency 50/60Hz ±5% ——

Input voltage distortion factor Within 5%

Max. input apparent power 105VA ——

Max. input power —— 41W

Inrush current 20A within 8ms 81A within 1ms

5VDC 5A 3A 5A Rated output current 24VDC —— 0.6A ——

5VDC 5.5A or more 3.3A or more 5.5A or more Overcurrent protection 1 24VDC —— 0.66A or more ——

5VDC 5.5 to 6.5V Overvoltage protection 2 24VDC ——

Efficiency 65% or more

Allowable momentary power failure period 3 Within 20ms Within 10ms (at 24VDC input)

Dielectric withstand voltage Across inputs/LG and outputs/FG 2830VAC rms/3 cycles (2000 m (6562 ft.)) 500VAC across primary and 5VDC

Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs and FG/LG 10M or more by insulation resistance tester

5M or more by insulation resistance tester

By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency

  • By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency
  • Noise voltage IEC61000-4-4, 2kV

Operation indication LED indication (lit at 5VDC output)

Fuse Built-in (Unchangeable by user)

Contact output section No

Terminal screw size M3.5 × 7

Applicable wire size 0.75 to 2mm2

Applicable solderless terminal RAV1.25 to 3.5, RAV2 to 3.5

Applicable tightening torque 66 to 89N•cm

H 130mm (5.12inch)

W 55mm (2.17inch) External dimensions

D 93.6mm (3.69inch)

Weight 0.60kg 0.50kg

5 - 4 5 - 4

Performance Specifications Item · Insulation resistance · Noise durability

Page 48 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 5 5 - 5
Page 48 · click to enlarge
Page 48

MELSEC-Q 5 POWER SUPPLY MODULE

POINTS 1 : Overcurrent protection The overcurrent protection device shuts off the 5 V, 24 VDC circuit and stops

the system if the current flowing in the circuit exceeds the specified value. The LED of the power supply module is unlit or lit dimly upon a voltage drop. If this device is activated, switch the input power supply off and eliminate the cause such as insufficient current capacity or short. Then, a few minutes later, switch it on to restart the system. The initial start for the system takes place when the current value becomes normal. 2 : Overvoltage protection The overvoltage protection device shuts off the 5 VDC circuit and stops the system if a voltage of 5.5 VDC is applied to the circuit. When this device is activated, the power supply module LED is switched OFF. If this happens, switch the input power OFF, then a few minutes later ON. This causes the initial start for the system to take place. The power supply module must be changed if the system is not booted and the LED remains OFF. 3 : Allowable momentary power failure period (1) For AC input power supply

y An instantaneous power failure lasting less than 20ms will cause AC

down to be detected, but operation will continue. y An instantaneous power failure lasting more than 20ms may cause the

operation to continue or initial start to take place depending on the power supply load. Furthermore, by using the same AC power supply for the AC input module and the power supply module, it is possible to prevent the sensor, to which the AC input module is connected, from turning OFF when it is ON when the power is turned OFF. However, if only the AC input module is connected to the AC line, which is connected to the power suppludetection of the AC down for the power supply module may be delayed by the capacitor in the AC input module. Thus, connect a load of approx. 30mA per QX10 unit to the AC line. (2) For DC input power supply

y An instantaneous power failure lasting less than 10ms (*4) will cause

24VDC down to be detected, but operation will continue. y An instantaneous power failure lasting more than 10ms (*4) may cause

the operation to continue or initial start to take place depending on the power supply load. ( 4: This is for a 24VDC input. This is 10ms or less for 24VDC or less.)

5 - 5 5 - 5

Page 49 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 6 5 - 6
Page 49 · click to enlarge
Page 49

MELSEC-Q 5 POWER SUPPLY MODULE

5.1.2 Selecting the power supply module

The power supply module is selected according to the total of current consumption of the base units, I/O modules, intelligent function module, special function module, and peripheral devices supplied by its power supply module. For the internal current consumption of 5 VDC of the base unit, refer to Chapter 6. For the internal current consumption of 5 VDC of the I/O modules, intelligent function module, special function module, and peripheral devices, refer to the Manuals of their respective modules. For the devices obtained by a user, see the manual for the respective device.

(1) When the base unit is of Q3†B or Q6†B:

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 5 POWER SUPPLY MODULE diagram (page 49)
Fig. 17

Peripheral devices, converter, cables, etc. (for connection between CPU module and PC)

1. The CPU module is loaded on the Q3 B main base unit.

(a) Selection of power supply module for use of Q52B or Q55B extension base

unit Using the Q52B or Q55B supplies 5VDC power from the power supply module of the main base unit through the extension cable. Therefore, note the following when using the Q52B or Q55B.

1. The power supply module to be loaded on the main base unit should be selected to cover also the 5VDC used on the Q52B or Q55B. For example, either of the following power supply modules must be mounted on the main base unit, when the current consumption on the main base unit is 3A and that on the Q52B or Q55B is 1A.

5VDC Rated output current Type

6A Q61P-A1, Q61P-A2, Q63P

8.5A Q64P

2. Since 5VDC is supplied to the Q52B or Q55B through the extension cable, a voltage drop occurs at the extension cable. You must select the power supply module and extension cable length to ensure that the "IN" connector voltage of the Q52B or Q55B is 4.75VDC or more. For details of a voltage drop, refer to Section 6.6.

5 - 6 5 - 6

Page 50 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 2.0A Q61SP
Page 50 · click to enlarge
Page 50

MELSEC-Q 5 POWER SUPPLY MODULE

(b) Ideas for reducing voltage drops

The following methods are effective to reduce voltage drops at the extension cables.

1. Changing the module loading positions Load large current consumption modules on the main base unit. Load small current consumption modules on the extension base unit. 2) Using short extension cables The shorter the extension cable is, the smaller the resistance and voltage drops are. Use the shortest possible extension cables.

(2) When the base unit is of Q3 † SB:

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (2) When the base unit is of Q3 † SB: diagram (page 50)
Fig. 18 · (2) When the base unit is of Q3 † SB:

Peripheral devices, converter, cables, etc. (for connection between CPU module and PC)

1. The CPU module is loaded on the Q3 SB slim type main base unit.

(a) To use the slim type main base unit and slim type power supply module, pay

1. The capacity of the 5VDC power supply of the power supply module (Q61SP) installed to the slim type main base unit is 2A. Choose modules with total capacity of 2A or less.

5VDC Rated output current Type

2.0A Q61SP

5 - 7 5 - 7

Page 51 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 8 5 - 8
Page 51 · click to enlarge
Page 51

MELSEC-Q 5 POWER SUPPLY MODULE

(3) When the base unit is of QA1S6 † B:

Power supply module A1S61PN, A1S62PN, A1S63P

Base unit QA1S65B and QA1S68B

I/O module A1SX10, A1SY10, etc.

Special function module A1SD61, A1SD75P1-S3, etc.

peripheral devices AD75TU 2

2. Select the power supply module also in consideration of the current consumption of the peripheral devices connected to the special function module. For example, when the AD75TU is connected to the A1SD75P1-S3, the current consumption of the AD75TU must also be taken into account. 5.1.3 Precaution when connecting the uninterruptive power supply

Be sure of the following terms when connecting the High Performance model QCPU system to the uninterruptive power supply (abbreviated as UPS hereafter): Use a UPS which employs the constant inverter power supply method with 5 % or less voltage fluctuation. Do not use a UPS with the constant commercial power supply method.

5 - 8 5 - 8

Page 52 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Q61SP
Page 52 · click to enlarge
Page 52

MELSEC-Q 5 POWER SUPPLY MODULE

5.2 Names of Parts and Settings

The names of the parts of each power supply module are described below.

(1) Q61P-A1, Q61P-A2, Q62P, Q63P, Q64P, Q61SP

8. 1)
8. 1)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) Q61P-A1, Q61P-A2, Q62P, Q63P, Q64P, Q61SP diagram (page 52)
Fig. 19
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) Q61P-A1, Q61P-A2, Q62P, Q63P, Q64P, Q61SP diagram (page 52)
Fig. 20
4. 10)

Q61P-A1

Q61P-A2

8. 1)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Q61P-A1 diagram (page 52)
Fig. 21
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Q61P-A1 diagram (page 52)
Fig. 22
4. 12)
4. 13)

Q62P

Q63P

8. 1)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Q62P diagram (page 52)
Fig. 23
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Q62P diagram (page 52)
Fig. 24
4. 14)

Q61SP

Q64P

5 - 9 5 - 9

Show 24 more labels / short text on this page
7) · 7) · 2) · 2) · 3) · 3) · 4) · 11) · 9) · 7) · 7) · 2) · 2) · 3) · 3) · 7) · 2) · 2) · 3) · 3) · 4) · 12) · 9) · 6)
Page 53 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 10 5 - 10
Page 53 · click to enlarge
Page 53

MELSEC-Q 5 POWER SUPPLY MODULE

No. Name Application

1) POWER LED 5VDC power indicator LED

1. Turned ON when the whole system operates normally.
2. Turned OFF (opened) when a stop error occurs in the CPU module.

2) ERR terminals

3. In a multiple CPU system configuration, turned OFF when a stop error occurs in

any of the CPU modules.

Normally off when loaded in an extension base unit.

3. FG terminal Ground terminal connected to the shield pattern of the printed circuit board.
4. LG terminal Grounding for the power supply filter. The potential of Q61P-A1, Q61P-A2, Q62P,

Q64P and Q61SP terminal is 1/2 of the input voltage

5. +24V, 24G terminals Used to supply 24VDC power to inside the output module (using external wiring).

6) Terminal screw M3.5 × 7 screw

7) Terminal cover Protective cover of the terminal block

8. Module fixing screw hole Used to fix the module to the base unit. M3 × 12 screw (user-prepared)

(Tightening torque : 36 to 48N•cm)

9. Module loading lever Used to load the module into the base unit.
10. Power input terminals Used to connect a 100VAC power supply.
11. Power input terminals Used to connect a 200VAC power supply.
12. Power input terminals Used to connect a 100VAC to 200VAC power supply.
13. Power input terminals Used to connect a 24VAC power supply.
14. Power input terminals Used to connect a 100VAC/200VAC power supply.
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (Tightening torque : 36 to 48N•cm) diagram (page 53)
Fig. 25 · (Tightening torque : 36 to 48N•cm)

POINTS (1) The Q61P-A1 is dedicated for inputting a voltage of 100 VAC.

Do not input a voltage of 200 VAC into it or trouble may occur on the Q61P-A1.

Power supply module does not cause trouble. CPU module cannot be operated.

Therefore, it is not compatible with the intermediate voltage (133 to 169VAC). The CPU module may not work normally if the above intermediate voltage is applied. (3) Ensure that the earth terminals LG and FG are grounded.

5 - 10 5 - 10

Page 54 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 5 - 11 5 - 11
Page 54 · click to enlarge
Page 54

MELSEC-Q 5 POWER SUPPLY MODULE

(2) A1S61PN, A1S62PN and A1S63P

MELSECA 1S61PN

MELSECA 1S62PN

MELSECA 1S63P

POWER

POWER

POWER

MITSUBISHI

MITSUBISHI

MITSUBISHI

INPUT 100-240VAC 105VA 50 / 60Hz

OUTPUT 5VDC 5A

INPUT 100-240VAC 105VA 50 / 60Hz

OUTPUT 5VDC 3A 24VDC 0.6A

INPUT DC15.6 31.2V

OUTPUT DC 5V 5A

NC

+24V

NC

NC

24G

NC

FG

(FG)

(FG)

NC

NC

(LG)

(LG)

LG

INPUT

INPUT

INPUT +24V

100-240VAC

100-240VAC

24G

A1S61PN

A1S62PN

3. 4) 5) 7)
3. 4) 5) 7) 2)
3. 4) 6) 7)

A1S61PN

A1S62PN

A1S63P

No. Name Application 1) POWER LED 5VDC power indicator LED 2) +24V, 24G terminals Used to supply 24VDC power to inside the output module (using external wiring). 3) FG terminals Ground terminal connected to the shield pattern of the printed circuit board.

4. LG terminals Grounding for the power supply filter. The potential of A1S61PN or A1S62PN terminal is 1/2 of the input voltage. 5) Power input terminals Used to connect a 100VAC to 200VAC power supply. 6) Power input terminals Used to connect a 24 VDC power supply. 7) Terminal screw M3.5 7 screw 8) Terminal cover Protective cover of the terminal block
9. Module fixing screw Used to fix the module to the base unit. (M4 screw, tightening torque : 66 to 89N•cm)

POINTS (1) Do not wire to those terminals for which NC is stamped on the terminal block. (2) Ensure that the earth terminals LG and FG are grounded.

5 - 11 5 - 11

Show 9 more labels / short text on this page
9) · 9) · 9) · 1) · 1) · 1) · 8) · 8) · 8)
Page 55 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 1 6 - 1
Page 55 · click to enlarge
Page 55

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

6 BASE UNIT AND EXTENSION CABLE

This section describes the specifications of the extension cables for the base units (main, slim type and extension base unit) used in the PLC system and the specification standards of the extension base unit. 6.1 Base Unit Specification Table

(1) Main base unit specifications

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) Main base unit specifications diagram (page 55)
Fig. 26 · (1) Main base unit specifications

Number of I/O modules installed 3 5 8 12

Possibility of extension Extendable Applicable module Q series modules 5 VDC internal current consumption 0.105A 0.110A 0.114A 0.121A

Mounting hole size M4 screw hole or 4.5 hole (for M4 screw)

W 189mm (7.44inch) 245mm (9.65inch) 328mm (12.92inch) 439mm (17.30inch) External dimensions

Weight 0.21kg 0.25 kg 0.35 kg 0.45 kg Attachment Mounting screw M4 14 4 pieces (DIN rail mounting adapter to be sold separately) DIN rail mounting Adapter type Q6DIN3 Q6DIN2 Q6DIN1

(2) Slim type main base unit specifications

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (2) Slim type main base unit specifications diagram (page 55)
Fig. 27 · (2) Slim type main base unit specifications

Possibility of extension Cannot connect extension modules. Applicable module Q series modules 5 VDC internal current consumption 0.086A 0.086A 0.091A

Mounting hole size M4 screw hole or 4.5 hole (for M4 screw)

W 114mm (4.49inch) 142mm (5.59inch) 198mm (7.80inch) External dimensions

Weight 0.12kg 0.15 kg 0.21 kg Attachment Mounting screw M4 12 4 pieces (DIN rail mounting adapter to be sold separately) DIN rail mounting Adapter type Q6DIN3

6 - 1 6 - 1

Page 56 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 2 6 - 2
Page 56 · click to enlarge
Page 56

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

(3) Extension base unit specifications (Type not requiring power supply

module)

Type Item Q52B Q55B

Number of I/O modules installed 2 5

Possibility of extension Extendable

Applicable module Q series modules

5 VDC internal current consumption 0.080A 0.100A

Mounting hole size M4 screw hole or 4.5 hole (for M4 screw)

H 98mm (3.86inch)

W 106mm (4.17inch) 189mm (7.44inch) External dimensions

D 44.1mm (1.74inch)

Weight 0.14kg 0.23kg

Attachment Mounting screw M4 14 4 pieces (DIN rail mounting adapter to be sold separately)

DIN rail mounting Adapter type Q6DIN3

(4) Extension base unit specifications (Power supply loaded type)

Type

Item Q63B Q65B Q68B Q612B QA1S65B QA1S68B

Number of I/O modules installed 3 5 8 12 5 8

Possibility of extension Extendable

Applicable module Q series modules AnS series modules 5 VDC internal current consumption 0.105A 0.110A 0.114A 0.121A 0.117A 0.118A

Mounting hole size M4 screw hole or 4.5 hole (for M4 screw)

M5 screw hole or 5.5 hole (for M5 screw)

H 98mm (3.86inch) 130mm (5.12inch)

420mm (16.55inch) External dimensions

W 189mm (7.44inch)

245mm (9.65inch)

328mm (12.92inch)

439mm (17.30inch)

315mm (12.41inch)

D 44.1mm (1.74inch) 51.2mm (2.02inch)

Weight 0.23kg 0.25 kg 0.35 kg 0.45 kg 0.75 kg 1.00 kg

Attachment Mounting screw M4 14 , 4 pieces (DIN rail mounting adapter sold separately)

Mounting screw M5 25 4 pieces DIN rail mounting Adapter type Q6DIN3 Q6DIN2 Q6DIN1 ——— ———

6 - 2 6 - 2

Page 57 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6) DIN rail adapter
Page 57 · click to enlarge
Page 57

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

6.2 Extension Cable Specification Table

The list below shows the specifications of the extension cables which can be used for the High Performance model QCPU system.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 57)
Fig. 28

Cable length 0.45m (1.48ft.) 0.6m (1.97ft.) 1.2m (3.93ft.) 3.0m (9.84ft.) 5.0m (16.39ft.) 10.0m (32.79ft.)

Application Connection across the main base unit and extension base unit or across the extension base units.

Weight 0.15 kg 0.16 kg 0.22 kg 0.40 kg 0.60 kg 1.11 kg

POINT When the extension cables are used in combination, limit the overall distance of the combined cable to 13.2 m(43.28 ft.).

6.3 Parts Names of Base Unit

The names of the parts of the base unit are described below.

(1) Main base unit(Q33B, Q35B, Q38B, Q312B)

5. 4)

I/11 I/10 I/09 I/08 I/07 I/06 I/05 I/04 I/03 I/02 I/01 I/00 CPU POWER

F6

3. 6)

No. Name Application

1) Extension cable

Connector for sending and receiving signals from the extension base unit, to which the

connector

extension cables are connected.

Protective cover of extension cable connector. Before an extension cable is connected,

2) Base cover

the area of the base cover surrounded by the groove under the word "OUT" on the base

cover must be removed with a tool such as nippers.

Connector for installing the power supply module, CPU module, I/O modules, and

intelligent function module.

3) Module connector

To the connectors located in the spare space where these modules are not installed, attach

the supplied connector cover or the blank cover module (QG60) to prevent entry of dirt.

4. Module fixing screw hole Screw hole for fixing the module to the base unit. Screw size:M3 12
5. Base mounting hole Hole for mounting this base unit onto the panel of the control panel (for M4 screw)

6) DIN rail adapter

mounting hole Hole for mounting DIN rail adapter

6 - 3 6 - 3

1) · 2)

Page 58 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 4 6 - 4
Page 58 · click to enlarge
Page 58

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

(2) Slim type main base unit(Q32SB, Q33SB, Q35SB)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 58)
Fig. 29

Connector for installing the power supply module, CPU module, I/O modules, and

To the connectors located in the spare space where these modules are not installed, attach

the supplied connector cover or the blank cover module (QG60) to prevent entry of dirt.

2. Module fixing screw hole Screw hole for fixing the module to the base unit. Screw size:M3 12
3. Base mounting hole Hole for mounting this base unit onto the panel of the control panel (for M4 screw)

6 - 4 6 - 4

Page 59 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 5 6 - 5
Page 59 · click to enlarge
Page 59

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

(3) Extension base unit (Q5 B, Q6 B, QA1S6 B)

Q52B, Q55B

OUT IN 6)

I/O2 I/O1 I/O0 I/O3 I/O4

7. 4)

Q63B,Q65B, Q68B, Q612B

OUT IN

I/11 I/10 I/09 I/08 I/07 I/06 I/05 I/04 I/03 I/02 I/01 I/00 POWER

4. 7)

QA1S65B, QA1S68B

IN OUT

SG

FG

I/O0 I/O7 I/O6 I/O5 I/O4 I/O3 I/O2 I/O1

POWER

QA1S68B

No. Name Application

Connectors for sending and receiving signals from the main base unit or the other extension base units, to which the extension cables are connected. Do not remove the supplied connector cover. 2) Base cover Protective cover of extension cable connector.

1) Extension cable connector

3) Stage No. setting connector

Connector for setting the number of stages of the extension base unit. For setting method, refer to Section 6.4.

Connectors for installing the power supply module, I/O modules, and intelligent function module/ special function module. To those connectors located in the spare space where these modules are not installed, apply the supplied connector cover or the blank cover module to prevent entry of dirt. Blank cover module applicable to Q52B, Q55B, Q63B,Q65B, Q68B and Q612B :QG60 Blank cover module applicable to QA1S65B and QA1S68B :A1SG60

4) Module connector

5. Module fixing screw hole Screw hole for fixing the module to the base unit. Q52B, Q55B, Q63B,Q65B,Q68B and Q612B Screw size: M3 12 QA1S65B and QA1S68B Screw size: M4 12
6. Base mounting hole Hole for mounting this base unit on the panel of the control panel. Q52B, Q55B, Q65B,Q68B and Q612B For M4 screw QA1S65B and QA1S68B For M5 screw
7. DIN rail adapter mounting hole DIN rail adapter mounting hole.

6 - 5 6 - 5

Show 15 more labels / short text on this page
5) · 3) · 2) · 1) · 5) · 6) · 3) · 2) · 1) · 5) · 6) · 3) · 2) · 1) · 4)
Page 60 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 6 6 - 6
Page 60 · click to enlarge
Page 60

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

6.4 Setting the Extension Base Unit

The number of stages setting method of each extension base unit to be used when extension base units are installed is described below.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 60)
Fig. 30

Setting of Stage Number for Extension Base Units

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Setting of Stage Number for Extension Base Units diagram (page 60)
Fig. 31 · Setting of Stage Number for Extension Base Units

1st stage 2nd stage 3rd stage 4th stage 5th stage 6th stage 7th stage

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Setting of Stage Number for Extension Base Units diagram (page 60)
Fig. 32 · Setting of Stage Number for Extension Base Units

POINTS To set the stages No. setting connector, set a number from 1 to 7 according to the number of extension stages. Do not set the same stage number at two or more positions or do not fail to set a number. A miss-input or miss-output may occur.

6 - 6 6 - 6

Page 61 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 7 6 - 7
Page 61 · click to enlarge
Page 61

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

6.5 I/O Number Allocation

The I/O numbers are automatically allocated in the system loading status.

0 1 2 3 4

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 61)
Fig. 33

6 7 8 9 10 11 12 5 X/Y

X/Y 100 X/Y 120 X/Y 140 X/Y 160 X/Y 180

14 15 16 17 18 19 20 13 X/Y 1A0

X/Y 1C0 X/Y 1E0 X/Y 200 X/Y 220 X/Y 240 X/Y 260 X/Y 280

3rd extension stage In this system, 32-point modules are loaded on slots 0 to 25.

For the I/O number setting method using GX Developer, refer to the Operating Manual of GX Developer. For details of I/O number allocation, refer to the following manual. • High Performance Model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 61)
Fig. 34

POINT For the extension using the Q5 B, Q6B B and QA1S6 B, allocate the I/O numbers on the modules starting from the Q series module installed on the Q5 B, Q6 B base unit. Where 32 modules are installed in all slots with the configuration

6 - 7 6 - 7

1st extension stage · 2nd extension stage

Page 62 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 8 6 - 8
Page 62 · click to enlarge
Page 62

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

6.6 Guideline for Use of Extension Base Units (Q5 † B)

Since the Q5†B is supplied with 5VDC from the power supply module on the main base unit, a voltage drop occurs at extension cables. Improper I/O may be provided if the specified voltage (4.75VDC or higher) is not supplied to the "IN" connector of the Q5†B. When using the Q5†B, make sure that the "IN" connector of the Q5†B is supplied with 4.75VDC or higher. And it is recommend to connect it with the shortest possible extension cable right after connecting the main base unit, so as to minimize the effects of voltage drop. (1) When only the Q5†B is connected to the extension base unit

(a) Selection condition

4.75VDC or higher should be supplied to the "IN" connector of the Q5†B in the final extension stage. (b) How to calculate voltage to "IN" connector

The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC. Therefore, the Q5†B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).

Main base unit (Q3 B)

Extension Cable

Extension Cable

Conductor

Type

Resistance ( )

R1

QC05B 0.044

Extension base unit (Q5 B)

QC06B 0.051

QC12B 0.082

QC30B 0.172

R2

Extension base unit (Q5 B)

QC50B 0.273

QC100B 0.530

R7

R7

Extension base unit (Q5 B)

Symbol Description

V1 Voltage drop at the extension cable between the main base unit and extension base unit

Vn Voltage drop at the extension cable between the extension base unit (extension stage n-1) and extension base

unit (extension stage n)

R1 Cable resistance between the main base unit and extension base unit

Rn Cable resistance between the extension base unit (extension stage n-1) and extension base unit (extension

stage n)

l1 to l7 5VDC current consumption among extension stage 1 to 7 1

1. Sum total of current consumed by Q5 † B and currents consumed by the I/O, intelligent function modules loaded on the

Q5†B.

The symbols including "I" (I1 to I7) vary with the modules loaded on the extension base unit. For details of the symbol,

refer to the user's manuals of the module used.

6 - 8 6 - 8

Show 4 more labels / short text on this page
Power supply module · Extension stage 1 · Extension stage 2 · Extension stage 7
Page 63 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 9 6 - 9
Page 63 · click to enlarge
Page 63

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

List for Calculating Voltage Drops Occurring at Extension Cables in System Consisting of Extensions 1 to 7

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 63)
Fig. 35

Voltage Drop at Extension Cable on Corresponding Extension Unit Q5†B Loading Position V1 V2 V3 V4 V5 V6 V7

of Q5†B (V) Extension stage 1 R1 • I1 V=V1

Extension stage 2 R1(I1+I2) R2 • I2 V=V1+V2

Extension stage 3 R1(I1+I2+I3) R2(I2+I3) R3 • I3 V=V1+V2+V3

Extension stage 4 R1(I1+I2+I3+I4) R2(I2+I3+I4) R3(I3+I4) R4 • I4 V=V1+V2+V3+V4

+I5) R2(I2+I3+I4+I5) R3(I3+I4+I5) R4(I4+I5) R5 • I5 V=V1+V2+V3+V4+V5

+I6) R3(I3+I4+I5+I6) R4(I4+I5+I6) R5(I5+I6) R6 • I6 V=V1+V2+V3+V4+V5+

The voltage supplied to "IN" connector of the Q5†B in the final extension reaches 4.75 VDC or higher on the condition that the sum total of voltage drop to "IN" connector of Q5†B (V) is 0.15V or lower.

(2) When the Q6 B is connected between the Q3 B and the Q5 B (a) Selection condition

4.75VDC or higher should be supplied to the "IN" connector of the Q5†B in the final extension. (b) How to calculate voltage to "IN" connector

The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC. Therefore, the Q5†B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 63)
Fig. 36

[When the Q5 B is connected to Extension stage 2.]

V Voltage drop at the extension cable between the main base unit and extension base unit (Q5†B)

5VDC current consumption when the Q5†B is used as Extension n+1, n = 1 to 6, n: Extension No. of Q6†B

(Sum total of current consumed by Q5†B and currents consumed by the I/O, intelligent function modules

Extension cable resistance between the main base unit or the extension base unit (Q6†B) and the extension

Rn+1 Extension cable resistance between the extension base unit (Q6†B) and extension base unit (Q5†B)

6 - 9 6 - 9

Page 64 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 10 6 - 10
Page 64 · click to enlarge
Page 64

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

List for Calculating Voltage Drops Occurring at Extension Cables when connecting Q6†B between Q3†B and Q5†B

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE diagram (page 64)
Fig. 37

Voltage drop caused by extension cable from the main base unit to the

Extension stage 1 to 3 Extension stage 4 V=(R1+R2+R3+R4)I1

Extension stage 1 to 4 Extension stage 5 V=(R1+R2+R3+R4+R5)I1

Extension stage 1 to 5 Extension stage 6 V=(R1+R2+R3+R4+R5+R6)I1

Extension stage 1 to 6 Extension stage 7 V=(R1+R2+R3+R4+R5+R6+R7)I1 The voltage supplied to the "IN" connector of the Q5†B reaches 4.75 VDC or higher on the condition that the voltage drop (V) at the extension cable between the main base unit and Q5†B is 0.15 VDC or lower.

(3) When the GOT is bus-connected

(a) Selection condition

4.75VDC or higher should be supplied to the "IN" connector of the Q5†B. (b) How to calculate voltage to "IN" connector

The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC. Therefore, the Q5†B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).

Main base unit (Q3 B)

Extension Cable

Extension Cable

Conductor

Type

Resistance ( )

Extension base unit (Q5 B)

QC05B 0.044

R1

QC06B 0.051

QC12B 0.082

QC30B 0.172

GOT

QC50B 0.273

QC100B 0.530

Number of GOTs connectedMax. 5 units

GOT

Symbol Description

V Voltage drop at the extension cable between the main base unit and extension base unit (Q5†B)

5VDC current consumption when the Q5†B is used as Extension n+1, n = 1 to 5, n: Extension No. of the Q6†B connected (Sum total of current consumed by Q5†B and currents consumed by I/O, intelligent function modules loaded on the Q5†B)

In

Im 5VDC current consumption of the GOT (current consumption per GOT is 254mA) • Im = 254 c (c: Number of GOTs connected (c: 1 to 5))

Rn Extension cable resistance between the main base unit or the extension base unit (Q6†B) and extension base unit (Q6†B)

Rn+1 Extension cable resistance between the extension base unit (Q6†B) and extension base unit (Q5†B)

6 - 10 6 - 10

Power supply module

Page 65 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 6 - 11 6 - 11
Page 65 · click to enlarge
Page 65

MELSEC-Q 6 BASE UNIT AND EXTENSION CABLE

POINT When connecting GOT by extension cable that is 13.2 m (43.31ft) or longer, the bus extension connector box A9GT-QCNB is required. Since the A9GT-QCNB is supplied with 5VDC from the power supply module loaded on the main base unit, 29mA must be added to "Im" as the current consumption of the A9GT-QCNB. For details of the GOT-bus connection, refer to the GOT-A900 Series User's Manual (Connection).

6 - 11 6 - 11

Page 66 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 7 - 1 7 - 1
Page 66 · click to enlarge
Page 66

MELSEC-Q 7 MEMORY CARD AND BATTERY

7 MEMORY CARD AND BATTERY

This section describes the specifications and handling of the memory card and battery which can be used on the High Performance model QCPU. The memory card is necessary for sampling tracing. The memory card is also used to handle file registers of more than the number of points that can be stored in the standard RAM. (Refer to Section 4.1) 7.1 Memory Card Specifications

The specifications of the memory card which can be used on the High Performance model QCPU adheres to the PCMCIA small PC card. On the High Performance model QCPU, only one memory card can be installed.

(1) SRAM card

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) SRAM card diagram (page 66)
Fig. 38 · (1) SRAM card

Memory capacity after format 7940 kbyte 15932 kbyte 31854 kbyte

7 - 1 7 - 1

Page 67 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 7 - 2 7 - 2
Page 67 · click to enlarge
Page 67

MELSEC-Q 7 MEMORY CARD AND BATTERY

7.2 Battery Specifications (For CPU Module and SRAM Card)

(1) For CPU module

Type

Item Q6BAT

Classification Manganese dioxide lithium primary

battery

Initial voltage 3.0V

Nominal current 1800mAh

Storage life 10 years (room temperature)

Total power failure time Refer to Section 10.3.1.

Power failure backup for program

Application

memory, standard RAM and latch

devices

(2) For SRAM card

Type

Item Q2MEM-BAT

Classification Graphite fluoride primary battery

Initial voltage 3.0V

Nominal current 48mAh

Storage life 5 years (room temperature)

Total power failure time Refer to Section 10.3.1.

Application Power failure backup for SRAM card

REMARK

Refer to Section 10.3.1 for the battery life.

7 - 2 7 - 2

Page 68 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 7 - 3 7 - 3
Page 68 · click to enlarge
Page 68

MELSEC-Q 7 MEMORY CARD AND BATTERY

7.3 Handling the Memory Card

(1) Formatting of memory card

Any SRAM or ATA card must have been formatted to use on the High Performance model QCPU. Since the SRAM or ATA card purchased is not yet formatted, format it using GX Developer before use. (The Flash card need not be formatted.) For the formatting procedure, refer to the Operating Manual of the GX Developer. (2) Installation of SRAM card battery

A power interrupt hold-on battery is furnished with the SRAM card you purchased. Before using the SRAM card, install the battery.

POINTS Even if the battery is installed on the CPU module, if a battery is not installed on the SRAM card, the memory of the SRAM card will not be backed up. Ensure to install the battery on the SRAM card. Also, if the battery is installed on the SRAM card but the CPU module has no battery, the program memory, standard RAM and latch devices of the CPU module are not backed up. Similarly ensure to install the battery on the CPU module.

(3) Kind of file which can be stored on memory card

Please refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals) of section 6.1 for the kind of the file which can be stored on each memory card.

7 - 3 7 - 3

Page 69 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 7 - 4 7 - 4
Page 69 · click to enlarge
Page 69

MELSEC-Q 7 MEMORY CARD AND BATTERY

7.4 The Names of The Parts of The Memory Card

The names of the parts of the memory card are described below.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 7 MEMORY CARD AND BATTERY diagram (page 69)
Fig. 39

1) Connector area Connector area connected to the CPU module

2. Battery holder Used to set the lithium battery for data backup of the SRAM memory

Switch for fixing the battery holder to the memory card main module

Used to set write inhibit in the memory. At the time of shipping, it is

: The battery holder fixing switch is returned automatically from RELEASE to LOCK

when the battery holder is disconnected.

7 - 4 7 - 4

Page 70 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 7 - 5 7 - 5
Page 70 · click to enlarge
Page 70

MELSEC-Q 7 MEMORY CARD AND BATTERY

7.5 Memory Card Loading/Unloading Procedures

(1) To install the memory card

Install the memory card into the CPU module, while paying attention to the orientation of the memory card. Insert the memory card securely into the connector until the height of the memory card reaches that of the memory card EJECT button.

Memory card EJECT button

"Precautions" on this side Insert it in this direction.

(2) To remove the memory card

To remove the memory card from the CPU module, press the memory card EJECT button to push out the card.

Memory card EJECT button

Remove the card in this direction.

(3) To extract the memory card while the power is turned on

  • Before removing the memory card, make sure that the special relays "SM604", "SM605" are OFF.
  • When "SM604" is ON, the memory card cannot be removed since the CPU module is using the memory card.
  • When "SM605" is ON, turn it OFF. When "SM604" and "SM605" are OFF, remove the memory card in the following procedure.
1. Turn on the special relay "SM609" using the sequence program or by the device test of GX Developer etc. 2) By monitoring GX Developer etc., check that the special relays "SM600" is turned off. 3) Extract the memory card. SM600 (Memory card usable flag) : The system is turned on when memory

card is ready for use by user. SM604 (memory card use flag) : The system is turned on when the CPU

module uses a memory card. SM605 (memory card detach inhibit flag) : This is turned on by the user to disable

the memory card from being detached.

(4) To install the memory card while the power is turned on

1. Install the memory card.\ 2) By monitoring GX Developer etc., check that the special relays "SM600" is turned on.

POINTS Install and remove the memory card while the power is turned on, paying attention to the following. (1) If the procedures specified above are not followed, the data stored in the

memory card may be destroyed. When the CPU module operation at the time of occurrence of a parameter error is set to STOP, the CPU module operation is stopped by the occurrence of "ICM.OPE.ERROR." (2) When the memory card is installed, its mount processing is performed again.

As a result, the scanning time is increased by several 10 ms max.

7 - 5 7 - 5

Show 5 more labels / short text on this page
CPU module · Memory card · Push · CPU module · Memory card
Page 71 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 7 - 6 7 - 6
Page 71 · click to enlarge
Page 71

MELSEC-Q 7 MEMORY CARD AND BATTERY

7.6 Installation of Battery (for CPU Module and Memory Card)

(1) The battery for the CPU module is shipped with its connector disconnected.

Connect the connector as follows. Refer to Section 10.3 for the service life of the battery and how to replace the battery.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 7 MEMORY CARD AND BATTERY diagram (page 71)
Fig. 40

Side of the CPU module Open the cover at the CPU module's bottom.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 7 MEMORY CARD AND BATTERY diagram (page 71)
Fig. 41

Insert the battery connector into the connector pin on the case. Be sure that the insertion direction is correct.

(2) The battery for the SRAM card is shipped separately from the battery holder.

Before installing the SRAM card into the CPU module, set the battery holder in the following procedure.

Battery holder's locking switch "Model name" on this side

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 7 MEMORY CARD AND BATTERY diagram (page 71)
Fig. 42

Set the battery holder's locking switch to the "RELEASE" position.

Set the battery onto the battery holder with the "plus" face up.

Insert the battery holder with which the battery is installed firmly, into the SRAM card.

Confirm that the battery holder's locking switch is set to the "LOCK" position.

"LOCK" position The battery holder's locking switch is set automatically to the "LOCK" position when the battery holder is removed. In its position, insert the battery holder firmly.

7 - 6 7 - 6

'+' sign · Battery holder

Page 72 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 1 8 - 1
Page 72 · click to enlarge
Page 72

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8 EMC AND LOW VOLTAGE DIRECTIVE

For the products sold in European countries, the conformance to the EMC Directive, which is one of the European Directive, has been a legal obligation since 1996. Also, conformance to the Low Voltage Directive, another European Directive, has been a legal obligation since 1997. Manufacturers who recognize their products must conform to the EMC and Low Voltage Directive required to declare that their products conform to these Directives and put a "CE mark" on their products. 8.1 Requirements for Conformance to EMC Directive

The EMC Directive specifies that products placed on the market must "be so constructed that they do not cause excessive electromagnetic interference (emissions) and are not unduly affected by electromagnetic interference (immunity)". The applicable products are requested to meet these requirements. The sections 8.1.1 through 8.1.6 summarize the precautions on conformance to the EMC Directive of the machinery constructed using the MELSEC-Q series PLCs. The details of these precautions has been prepared based on the control requirements and the applicable standards control. However, we will not assure that the overall machinery manufactured according to these details conforms to the above-mentioned directives. The method of conformance to the EMC Directive and the judgment on whether or not the machinery conforms to the EMC Directive must be determined finally by the manufacturer of the machinery. 8.1.1 Standards applicable to the EMC Directive

The standards applicable to the EMC Directive are listed below.

Specification Test item Test details Standard value

30 M-230 MHz QP : 30 dB V/m (30 m in measurement range) 1 230 M-1000 MHz QP : 37 dB V/m (30 m in measurement range) EN50081-2 : 1995 EN55011 Conducted noise

EN55011 Radiated noise 2 Electromagnetic emissions from the product are measured.

Electromagnetic emissions from the product to the power line is measured.

150 k-500 kHz QP : 79 dB, Mean : 66 dB 1 500 k-30 MHz QP : 73 dB, Mean : 60 dB

Immunity test in which static electricity is applied to the cabinet of the equipment.

EN61000-4-2 Electrostatic immunity 2

15 k V Aerial discharge

Power line : 2 kV Digital I/O (24 V or higher) : 1 kV (Digital I/O (24 V or less)) > 250 V (Analog I/O, signal lines) > 250 V EN61000-4-3 Radiated field AM modulation 2

Immunity test in which burst noise is applied to the power line and signal lines.

EN61000-4-4 Fast transient burst noise 2

EN61131-2 : 1996

Immunity test in which field is irradiated to the product.

10 V/m, 26-1000 MHz, 80%AM modulation@1 kHz

EN61000-4-12 Damped oscillatory wave immunity

Immunity test in which a damped oscillatory wave is superimposed on the power line.

Power line : 1 kV Digital I/O (24 V or higher) : 1 kV ( 1) QP : Quasi-peak value, Mean : Average value ( 2) The PLC is an open type device (device installed to another device) and must be installed in a conductive control panel. The tests for the corresponding items were performed while the PLC was installed inside a control panel.

8 - 1 8 - 1

Page 73 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 2 8 - 2
Page 73 · click to enlarge
Page 73

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.1.2 Installation instructions for EMC Directive

The PLC is open equipment and must be installed within a control cabinet for use. This not only ensures safety but also ensures effective shielding of PLC-generated electromagnetic noise. (1) Control cabinet

(a) Use a conductive control cabinet.

(b) When attaching the control cabinet's top plate or base plate, mask painting

and weld so that good surface contact can be made between the cabinet and plate.

(c) To ensure good electrical contact with the control cabinet, mask the paint on

the installation bolts of the inner plate in the control cabinet so that contact between surfaces can be ensured over the widest possible area.

(d) Earth the control cabinet with a thick wire so that a low impedance

connection to ground can be ensured even at high frequencies.

(e) Holes made in the control cabinet must be 10 cm (3.94 inch) diameter or

less. If the holes are 10 cm (3.94 inch) or larger, radio frequency noise may be emitted. In addition, because radio waves leak through a clearance between the control panel door and the main unit, reduce the clearance as much as practicable. The leakage of radio waves can be suppressed by the direct application of an EMI gasket on the paint surface. Our tests have been carried out on a panel having the damping characteristics of 37 dB max. and 30 dB mean (measured by 3 m method with 30 to 300 MHz). (2) Connection of power and earth wires

Earthing and power supply wires for the PLC system must be connected as described below. (a) Provide an earthing point near the power supply module. Earth the power

supply's LG and FG terminals (LG : Line Ground, FG : Frame Ground) with the thickest and shortest wire possible. (The wire length must be 30 cm (11.81 inch) or shorter.) The LG and FG terminals function is to pass the noise generated in the PLC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.

(b) The earth wire led from the earthing point must be twisted with the power

supply wires. By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.

8 - 2 8 - 2

Page 74 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Crimp terminal
Page 74 · click to enlarge
Page 74

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.1.3 Cables

The cables extracted from the control panel contain a high frequency noise component. On the outside of the control panel, therefore, they serve as antennas to emit noise. To prevent noise emission, use shielded cable for the cables which are connected to the I/O modules and intelligent function modules and may be extracted to the outside of the control panel. The use of a shielded cable also increases noise resistance. The signal lines connected to the PLC I/O modules and intelligent function modules use shielded cables to assure noise resistance under the conditions where the shield is earthed. If a shielded cable is not used or not earthed correctly, the noise resistance will not meet the specified requirements.

When the shield of a shielded cable is earthed to the cabinet body, please ensure that the shield contact with the body is over a large surface area. If the cabinet body is painted it will be necessary to remove paint from the contact area. All fastenings must be metallic and the shield and earthing contact must be made over the largest available surface area. If the contact surfaces are too uneven for optimal contact to be made either use washers to correct for surface inconsistencies or use an abrasive to level the surfaces. The following diagrams show examples of how to provide good surface contact of shield earthing by use of a cable clamp.

(1) Earthing of shielded of shield cable

(a) Earth the shield of the shielded cable as near the module as possible taking

care so that the earthed cables are not induced electromagnetically by the cable to be earthed. (b) Take an appropriate measures so that the shield section of the shielded

cable from which the outer cover was partly removed for exposure is earthed to the control panel on an increased contact surface. A clamp may also be used as shown in the figure below. In this case, however, apply a cover to the painted inner wall surface of the control panel which comes in contact with the clamp.

shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.

Crimp terminal

8 - 3 8 - 3

Show 6 more labels / short text on this page
Screw · Shield section · Clamp fitting · Paint mask · Shielded cable · Shielded cable Wire
Page 75 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 4 8 - 4
Page 75 · click to enlarge
Page 75

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

(2) MELSECNET/H module

Always use a double-shielded coaxial cable (MITSUBISHI CABLE INDUSTRIES, LTD.: 5C-2V-CCY) for the coaxial cables MELSECNET/H module. Radiated noise in the range of 30MHz or higher can be suppressed by use of the double- shielded coaxial cables. Earth the double-shielded coaxial cable by connecting its outer shield to the ground.

Refer to (1) for the earthing of the shield.

(3) Ethernet module, Web server module

Precautions for using AUI cables, twisted pair cables and coaxial cables are described below. (a) Always earth the AUI cables connected to the 10BASE5 connectors.

Because the AUI cable is of the shielded type, strip part of the outer cover and earth the exposed shield section to the ground on the widest contact surface as shown below.

Refer to (1) for the earthing of the shield.

(b) Use shielded twisted pair cables as the twisted pair cables connected to the

10BASE-T/100BASE-TX connectors. For the shielded twisted pair cables, strip part of the outer cover and earth the exposed shield section to the ground on the widest contact surface as shown below.

Shielded twisted pair cables

Refer to (1) for the earthing of the shield.

(c) Always use double-shielded coaxial cables as the coaxial cables connected

to the 10BASE2 connectors. Earth the double-shielded coaxial cable by connecting its outer shield to the ground.

Refer to (1) for the earthing of the shield.

Ethernet is the registered trademark of XEROX, Co., LTD.

(4) I/O signal lines and other communication cables

For the I/O signal lines and other communication cables lines (RS-232, RS-422, CC- Link, etc.), if extracted to the outside of the control panel, also ensure to earth the shield section of these lines and cables in the same manner as in item (1) above.

8 - 4 8 - 4

Show 5 more labels / short text on this page
Earth here Shield · AUI cable · Shield · Shield · Earth here Shield
Page 76 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Crimp terminal
Page 76 · click to enlarge
Page 76

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.1.4 Power supply module

Always ground the LG and FG terminals after short-circuiting them. 8.1.5 When using QA1S6 B type base unit

(1) Cable

(a) Earthing of shielded cable

  • Earth the shield of the shielded cable as near the unit as possible taking care so that the earthed cables are not induced electromagnetically by the cable to be earthed.
  • Take appropriate measures so the shield that was partly removed for exposure is earthed to the control panel over a large contact surface area. A clamp may also be used as shown in the figure below. In this case, however, apply a cover to the painted inner wall surface of the control panel which comes in contact with the clamp.

shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.

Crimp terminal

8 - 5 8 - 5

Show 6 more labels / short text on this page
Screw · Shield section · Clamp fitting · Paint mask · Shielded cable · Shielded cable Wire
Page 77 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 6 8 - 6
Page 77 · click to enlarge
Page 77

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

(b) Positioning modules

  • Precautions to be followed when the machinery conforming to the EMC Directive is configured using the A1SD75P1-S3/A1SD75P2-S3/A1SD75P3S3 (hereafter referred to as the A1SD75) are described below. 1) When wiring with a 2 m (6.56 ft.) or less cable
  • Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.)
  • Wire the external wiring cable to the drive unit and external device with the shortest practicable length of cable.
  • Install the drive unit in the same panel.

A1SD75

External wiring cable (within 2 m (6.56 ft.))

  • 2) When wiring with cable that exceeds 2 m (6.56 ft.), but is 10 m (32.79 ft.) or less
  • Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.)
  • Install a ferrite core.
  • Wire the external wiring cable to the drive unit and external device with the shortest practicable length of cable.

A1SD75

External wiring cable (2 m to 10 m (6.56 ft. to 32.79 ft.))

  • 3) Ferrite core and cable clamp types and required quantities
  • Cable clamp Type : AD75CK (Mitsubishi Electric)
  • Ferrite core Type : ZCAT3035-1330 (TDK ferrite core)
  • Required quantity

Required Qty Cable length Prepared part 1 axis 2 axes 3 axes Within 2 m (6.56 ft.) AD75CK 1 1 1 AD75CK 1 1 1 2 m (6.56 ft.) to 10m (32.79ft.) ZCAT3035-1330 1 2 3

8 - 6 8 - 6

Show 13 more labels / short text on this page
External wiring connector · module · Power supply · module · Cable clamp · Drive unit · External wiring connector · Power supply · module · module · Ferrite core · Cable clamp · Drive unit
Page 78 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 7 8 - 7
Page 78 · click to enlarge
Page 78

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

(c) CC-Link module

1. Be sure to ground the cable shield that is connected to the CC-Link module close to the exit of control panel or to any of the CC-Link stations within 30 cm (11.81 inch) from the module or stations. The CC-Link dedicated cable is a shielded cable. As shown in the illustration below, remove a portion of the outer covering and ground as large a surface area of the exposed shield part as possible.

CC-Link dedicated cable Shield

2. Always use the specified CC-Link dedicated cable. 3) Do not use a ferrite core for the CC-Link module or CC-Link stations. 4) The CC-Link module, the CC-Link stations and the FG line inside the control panel should be connected at both the FG terminal and the SLD terminal as shown in the diagram below.

Master station Remote I/O station Local station

DA DB DG SLD

DA DB DG SLD

DA DB DG SLD

FG

FG

FG

(d) I/O signal lines

For the I/O signal lines, if extracted to the outside of the control panel, also ensure to earth the shield section of these lines and cables in the same manner as in item (1) above.

(2) Power supply module

The precautions required for each power supply module are described below. Always observe the items noted as precautions.

Model Precautions A1S61P A1S62P Not usable

A1S63P ( 1) Use the CE marked 24VDC panel power equipment. A1S61PEU A1S62PEU A1S61PN A1S62PN

Always ground the LG and FG terminals after short-circuiting them.

( 1) If sufficient filter circuitry is built into the 24VDC external power supply module, the noise generated by A1S63P will be absorbed by that filter circuit, so a line filter may not be required. Filtering circuitry of version F or later of A1S63P is improved so that a external line filter is not required.

8 - 7 8 - 7

Show 8 more labels / short text on this page
[Simplified diagram] · (Blue) (White) (Yellow) · Terminal resistor · Terminal resistor · CC-Link dedicated · CC-Link dedicated · cable · cable
Page 79 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 8 8 - 8
Page 79 · click to enlarge
Page 79

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.1.6 Others

(1) Ferrite core

A ferrite core has the effect of reducing radiated noise in the 30MHz to 100MHz band. It is not required to fit ferrite cores to cables, but it is recommended to fit ferrite cores if shield cables pulled out of the enclosure do not provide sufficient shielding effects. It should be noted that the ferrite cores should be fitted to the cables in the position immediately before they are pulled out of the enclosure. If the fitting position is improper, the ferrite will not produce any effect. In the CC-Link system, however, ferrite cores cannot be fitted to cables. (2) Noise filter (power supply line filter)

A noise filter is a component which has an effect on conducted noise. It is not required to fit the noise filter to the power supply line, but fitting it can further suppress noise. (The noise filter has the effect of reducing conducted noise of 10 MHz or less.) The precautions required when installing a noise filter are described below.

(a) Do not bundle the wires on the input side and output side of the noise filter.

When bundled, the output side noise will be induced into the input side wires from which the noise was filtered.

Input side (power supply side)

Input side (power supply side)

Output side (device side)

Output side (device side)

2. Separate and lay the input and output wires.
1. The noise will be included when the input and output wires are bundled.

(b) Earth the noise filter earthing terminal to the control cabinet with the shortest

wire possible (approx. 10 cm (3.94 inch)).

Reference

Noise Filter Model Name FN343-3/01 FN660-6/06 ZHC2203-11

Manufacturer SCHAFFNER SCHAFFNER TDK Rated current 3 A 6 A 3 A Rated voltage 250 V

8 - 8 8 - 8

Introduction · Filter · Filter

Page 80 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 9 8 - 9
Page 80 · click to enlarge
Page 80

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.2 Requirement to Conform to the Low Voltage Directive

The Low Voltage Directive requires each device that operates with the power supply ranging from 50 to 1000VAC and 75 to 1500VDC to satisfy the safety requirements. In Sections 8.2.1 to 8.2.6, cautions on installation and wiring of the MELSEC-Q series PLC to conform to the Low Voltage Directive are described. We have put the maximum effort to develop this material based on the requirements and standards of the regulation that we have collected. However, compatibility of the devices which are fabricated according to the contents of this manual to the above regulation is not guaranteed. Each manufacturer who fabricates such device should make the final judgement about the application method of the Low Voltage Directive and the product compatibility. 8.2.1 Standard applied for MELSEC-Q series PLC

The standard applied for MELSEC-Q series PLC is EN61010-1 safety of devices used in measurement rooms, control rooms, or laboratories. The MELSEC-Q series PLC modules which operate at the rated voltage of 50VAC/75VDC or above are also developed to conform to the above standard. The modules which operate at the rated voltage of less than 50VAC/75VDC are out of the Low Voltage Directive application range. 8.2.2 MELSEC-Q series PLC selection

(1) Power supply module

There are dangerous voltages (voltages higher than 42.4V peak) inside the power supply modules of the 100/200VAC rated I/O voltages. Therefore, the CE marked models are enhanced in insulation internally between the primary and secondary.

(2) I/O module

There are dangerous voltages (voltages higher than 42.4V peak) inside the I/O modules of the 100/200VAC rated I/O voltages. Therefore, the CE marked models are enhanced in insulation internally between the primary and secondary. The I/O modules of 24VDC or less rating are out of the Low Voltage Directive application range.

(3) CPU module, memory card, base unit

Using 5VDC circuits inside, the above modules are out of the Low Voltage Directive application range.

(4) Intelligent function modules (special function modules)

The intelligent function modules (special function modules) such as the analog, network and positioning modules are 24VDC or less in rated voltage and are therefore out of the Low Voltage Directive application range.

(5) Display device

Use the CE marked display device.

8 - 9 8 - 9

Page 81 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 8 - 10 8 - 10
Page 81 · click to enlarge
Page 81

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.2.3 Power supply

The insulation specification of the power supply module was designed assuming installation category II. Be sure to use the installation category II power supply to the PLC. The installation category indicates the durability level against surge voltage generated by a thunderbolt. Category I has the lowest durability; category IV has the highest durability.

Category III Category II Category I Category IV

Figure 8.1: Installation Category

Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution. 8.2.4 Control box

Because the PLC is an open device (a device designed to be stored within another module), be sure to use it after storing in the control box.

(1) Electrical shock prevention

In order to prevent persons who are not familiar with the electric facility such as the operators from electric shocks, the control box must have the following functions : (a) The control box must be equipped with a lock so that only the personnel who

has studied about the electric facility and have enough knowledge can open it. (b) The control box must have a structure which automatically stops the power

supply when the box is opened.

(2) Dustproof and waterproof features

The control box also has the dustproof and waterproof functions. Insufficient dustproof and waterproof features lower the insulation withstand voltage, resulting in insulation destruction. The insulation in our PLC is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or below.

Pollution level 1 : An environment where the air is dry and conductive dust does not exist. Pollution level 2 : An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust. Generally, this is the level for inside the control box equivalent to IP54 in a control room or on the floor of a typical factory. Pollution level 3 : An environment where conductive dust exits and conductivity may be generated due to the accumulated dust. An environment for a typical factory floor. Pollution level 4 : Continuous conductivity may occur due to rain, snow, etc. An outdoor environment. As shown above, the PLC can realize the pollution level 2 when stored in a control box equivalent to IP54.

8 - 10 8 - 10

Page 82 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Table 8.1 : Intensive Insulation Withstand Voltage
Page 82 · click to enlarge
Page 82

MELSEC-Q 8 EMC AND LOW VOLTAGE DIRECTIVE

8.2.5 Grounding

There are the following two different grounding terminals. Use either grounding terminal in an earthed status.

Protective grounding : Maintains the safety of the PLC and improves the

noise resistance.

Functional grounding : Improves the noise resistance.

8.2.6 External wiring

(1) 24VDC external power supply

For the MELSEC-Q series PLC 24VDC I/O modules and the intelligent function modules (special function modules) which require external supply power, use a model whose 24VDC circuit is intensively insulated from the hazardous voltage circuit. (2) External devices

When a device with a hazardous voltage circuit is externally connected to the PLC, use a model whose circuit section of the interface to the PLC is intensively insulated from the hazardous voltage circuit. (3) Intensive insulation

Intensive insulation refers to the insulation with the dielectric withstand voltage shown in Table 8.1.

Table 8.1 : Intensive Insulation Withstand Voltage

(Installation Category II, source : IEC664)

Rated voltage of hazardous voltage area Surge withstand voltage (1.2/50 s)

150VAC or below 2500 V 300VAC or below 4000 V

8 - 11 8 - 11

Page 83 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 1 9 - 1
Page 83 · click to enlarge
Page 83

MELSEC-Q 9 LOADING AND INSTALLATION

9 LOADING AND INSTALLATION

In order to increase the reliability of the system and exploit the maximum performance of its functions, this section describes the methods and precautions for the mounting and installation of the system. 9.1 General Safety Requirements

! DANGER Install a safety circuit external to the PLC that keeps the entire

system safe even when there are problems with the external power supply or the PLC module. Otherwise, trouble could result from erroneous output or erroneous operation. (1) Outside the PLC, construct mechanical damage preventing

interlock circuits such as emergency stop, protective circuits, positioning upper and lower limits switches and interlocking forward/reverse operations. (2) When the PLC detects the following problems, it will stop

calculation and turn off all output in the case of (a). In the case of (b), it will stop calculation and hold or turn off all output according to the parameter setting. Note that the A1S series module will turn off the output in either of cases (a) and (b). All outputs of AnS Series Module will be switched off in the following cases:

(a) The power supply module has over current protection

equipment and over voltage protection equipment. (b) The PLC CPUs self-diagnosis functions, such as the watch

dog timer error, detect problems. In addition, all output will be turned on when there are problems that the PLC CPU cannot detect, such as in the I/O controller. (3) Output could be left on or off when there is trouble in the outputs

module relay or transistor. So build an external monitoring circuit that will monitor any single outputs that could cause serious trouble. When overcurrent which exceeds the rating or caused by short-

circuited load flows in the output module for a long time, it may cause smoke or fire. To prevent this, configure an external safety circuit, such as fuse. Build a circuit that turns on the external power supply when the PLC

main module power is turned on. If the external power supply is turned on first, it could result in erroneous output or erroneous operation. When there are communication problems with the data link, refer to

the corresponding data link manual for the operating status of each station. Not doing so could result in erroneous output or erroneous operation.operating status of each station. Not doing so could result in erroneous output or erroneous operation.

9 - 1 9 - 1

Page 84 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 2 9 - 2
Page 84 · click to enlarge
Page 84

MELSEC-Q 9 LOADING AND INSTALLATION

! DANGER When connecting a peripheral device to the CPU module or connecting

a personal computer or the like to the special function module to exercise control (data change) on the running PLC, configure up an interlock circuit in the sequence program to ensure that the whole system will always operate safely. Also before exercising other control (program change, operating status change (status control)) on the running PLC, read the manual carefully and fully confirm safety. Especially for the above control on the remote PLC from an external device, an immediate action may not be taken for PLC trouble due to a data communication fault. In addition to configuring up the interlock circuit in the sequence program, corrective and other actions to be taken as a system for the occurrence of a data communication fault should be predetermined between the external device and PLC CPU.

! CAUTION Do not bunch the control wires or communication cables with the main

circuit or power wires, or install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that would cause erroneous operation. When controlling items like lamp load, heater or solenoid valve using an

output module, large current (approximately ten times greater than that present in normal circumstances) may flow when the output is turned OFF to ON. Take measures such as replacing the module with one having sufficient rated current.

When the PLC power supply is switched ON-OFF, correct control output may not be performed temporarily due to differences in delay time and starting time between the PLC power supply and the external power supply for the controlled object (especially DC). For example, if the external power supply for the controlled object is switched on in a DC output module and then the PLC power supply is switched on, the DC output module may provide false output instantaneously at power-on of the PLC. Therefore, it is necessary to make up a circuit that can switch on the PLC power supply first. Also, an abnormal operation may be performed if an external power supply fault or PLC failure takes place. To prevent any of these abnormal operations from leading to the abnormal operation of the whole system and in a fail-safe viewpoint, areas which can result in machine breakdown and accidents due to abnormal operations (e.g. emergency stop, protective and interlock circuits) should be constructed outside the PLC. The following page gives examples of system designing in the above viewpoint.

9 - 2 9 - 2

Page 85 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 3 9 - 3
Page 85 · click to enlarge
Page 85

MELSEC-Q 9 LOADING AND INSTALLATION

(1) System design circuit example (when not using ERR contact of

power supply module)

POWER SUPPLY POWER SUPPLY

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — POWER SUPPLY POWER SUPPLY diagram (page 85)
Fig. 43

TRANSFORMER

Set time for DC power supply to be established.

Voltage relay is recommended

Low battery alarm (Lamp or buzzer)

Power to output equipment switched OFF when the STOP signal is given.

ON when run by SM403

MC

In the case of an emergency stop or a stop caused by a limit switch.

Interlock circuits as necessary.Provide external interlock circuits for conflicting operations, such as forward rotation and reverse rotation, and for parts that could damage the machine or cause accidents if no interlock were used.

Power to output equipment switched OFF when the STOP signal is given.

In the case of an emergency stop or a stop caused by a limit switch.

The power-ON procedure is as follows:

For AC For AC/DC 1) Switch power ON. 2) Set CPU to RUN. 3) Turn ON the start switch. 4) When the magnetic contactor (MC) comes on, the output equipment is powered and may be driven by the program.

1) Switch power ON. 2) Set CPU to RUN. 3) When DC power is established, RA2 goes ON. 4) Timer (TM) times out after the DC power reaches 100%. (The TM set value should be the period of time from when RA2 goes ON to the establishment of 100% DC voltage. Set this value to approximately 0.5 seconds.) 5) Turn ON the start switch. 6) When the magnetic contactor (MC) comes on, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.)

9 - 3 9 - 3

Page 86 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 4 9 - 4
Page 86 · click to enlarge
Page 86

MELSEC-Q 9 LOADING AND INSTALLATION

(2) System design circuit example (when using ERR contact of power

supply module)

POWER SUPPLY

FOR AC/DC

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — POWER SUPPLY diagram (page 86)
Fig. 44

Set time for DC power supply to be established.

OFF at stop error from ERR POWER SUPPLY MODULE

MC MC Interlock circuits asnecessary. Provide external interlock circuits for conflicting operations, such as forward rotation and reverse rotation, and for parts that could damage the machine or cause accidents if no interlock were used.

Power to output equipment switched OFF when ERR contact turns OFF.

In the case of an emergency stop or a stop caused by a limit switch.

The power-ON procedure is as follows: For AC/DC 1) Switch power ON. 2) Set CPU to RUN. 3) When DC power is established, RA2 goes ON. 4) Timer (TM) times out after the DC power reaches 100%. (The TM set value should be the period of time from when RA2 goes ON to the establishment of 100% DC voltage. Set this value to approximately 0.5s.) 5) Turn ON the start switch. 6) When the magnetic contactor (MC) comes on, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.)

9 - 4 9 - 4

Page 87 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 5 9 - 5
Page 87 · click to enlarge
Page 87

MELSEC-Q 9 LOADING AND INSTALLATION

(3) Fail-safe measures against failure of the PLC

Failure of a CPU module or memory can be detected by the self-diagnosis function. However, failure of I/O control area may not be detected by the CPU module. In such cases, all I/O points turn ON or OFF depending on a condition of problem, and normal operating conditions and operating safety cannot sometimes be maintained. Though Mitsubishi PLCs are manufactured under strict quality control, they may cause failure or abnormal operations due to unspecific reasons. To prevent the abnormal operation of the whole system, machine breakdown, and accidents, fail-safe circuitry against failure of the PLC must be constructed outside the PLC. Examples of a system and its fail-safe circuitry are described below:

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 87)
Fig. 45

Output module for fail-safe purpose 1

1. The output module for fail-safe purpose should be loaded in the last slot of the system. (Y80 to Y8F in the above system.)

<Fail-safe circuit example>

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — <Fail-safe circuit example> diagram (page 87)
Fig. 46 · <Fail-safe circuit example>
2. Y80 repeats turning ON and then OFF at 0.5s intervals. Use a no-contact output module (transistor in the example shown above).

9 - 5 9 - 5

ON delay timer

Page 88 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 6 9 - 6
Page 88 · click to enlarge
Page 88

MELSEC-Q 9 LOADING AND INSTALLATION

9.2 Calculating Heat Generation by PLC

The ambient temperature inside the board storing the PLC must be suppressed to a PLC usable ambient temperature of 55°C. For the design of radiation from the storing board, it is necessary to know the average power consumption (heating value) of the devices and instruments stored in the board. Here the method of obtaining the average power consumption of the PLC system is described. From the power consumption, calculate a rise in ambient temperature inside the board.

How to calculate average power consumption

The power consuming parts of the PLC are roughly classified into six blocks as shown below.

(1) Power consumption of power supply module

The power conversion efficiency of the power supply module is approx. 70 %, i.e., 30 % of the output power is consumed by heating. As a result, 3/7 of the output power becomes the power consumption. Therefore the calculation formula is as follows.

Wpw = (I 5 v 5) (W) 3 7

I 5VCurrent consumption of logic 5 VDC circuit of each module

(2) Power consumption of a total of 5 VDC logic section of each

module The power consumption of the 5 VDC output circuit section of the power supply module is the power consumption of each module (including the current consumption of the base unit).

W 5V = I 5V 5 (W)

(3) A total of 24 VDC average power consumption of the output module

(power consumption for simultaneous ON points) The average power of the external 24 VDC power is the total power consumption of each module.

W 24V = I 24V 24 (W)

(4) Average power consumption due to voltage drop in the output

section of the output module (Power consumption for simultaneous ON points)

WOUT = IOUT Vdrop Number of outputs Simultaneous ON rate (W)

IOUT : Output current (Current in actual use) (A) Vdrop : Voltage drop in each output module (V)

(5) Average power consumption of the input section of the input

module(Power consumption for simultaneous ON points)

WIN = IIN E Number of input points Simultaneous ON rate (W)

IIN : Input current (Effective value for AC) (A) E : Input voltage (Voltage in actual use) (V)

9 - 6 9 - 6

Page 89 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — W 24V = 0 (W)
Page 89 · click to enlarge
Page 89

MELSEC-Q 9 LOADING AND INSTALLATION

(6) Power consumption of the power supply section of the intelligent

function module

WS = I5V 5 + I24V 24 + I100V 100 (W) The total of the power consumption values calculated for each block becomes the power consumption of the overall sequencer system.

W = WPW + W5V + W24V + WOUT + WIN + WS (W) From this overall power consumption (W), calculate the heating value and a rise in ambient temperature inside the board. The outline of the calculation formula for a rise in ambient temperature inside the board is shown below.

T = W

UA (°C)

W : Power consumption of overall sequencer system (value obtained above) A : Surface area inside the board U : When the ambient temperature inside the board is uniformed by a fan 6

When air inside the board is not circulated 4

POINT When a rise in ambient temperature inside the board exceeds the specified limit, it is recommended that you install a heat exchanger in the board to lower the ambient temperature inside the board. If a normal ventilating fan is used, dust will be sucked into the PLC together with the external air, and it may affect the performance of the PLC.

(7) Example of calculation of average power consumption

(a) System configuration

QJ71LP21-25

Q35B

Q61P-A1

Q02HCPU

QX40

QX40

QY10

(b) 5 VDC current consumption of each module

Q02HCPU : 0.64 (A) QX40 : 0.05 (A) QY10 : 0.43 (A) QJ71LP21-25 : 0.55 (A) Q35B : 0.074 (A) (c) Power consumption of power supply module

WPW = 3/7 (0.64+0.05+0.05+0.43+0.55+0.074) 5) = 3.84 (W) (d) Power consumption of a total of 5 VDC logic section of each module

W5V = (0.64+0.05+0.05+0.43+0.55+0.074) 5) = 8.97 (W) (e) A total of 24 VDC average power consumption of the output module

W 24V = 0 (W)

9 - 7 9 - 7

Vacant

Page 90 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 8 9 - 8
Page 90 · click to enlarge
Page 90

MELSEC-Q 9 LOADING AND INSTALLATION

(f) Average power consumption due to voltage drop in the output section of the

output module

W OUT = 0 (W)

(g) Average power consumption of the input section of the input module

W IN = 0.004 24 32 1 = 3.07 (W)

(h) Power consumption of the power supply section of the intelligent function

module W S = 0 (W)

(i) Power consumption of overall system.

W = 3.84 + 8.97 + 0 + 0 + 3.07 + 0 = 15.88 (W)

9 - 8 9 - 8

Page 91 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 9 9 - 9
Page 91 · click to enlarge
Page 91

MELSEC-Q 9 LOADING AND INSTALLATION

9.3 Module Installation 9.3.1 Precaution on installation

! CAUTION Use the PLC in an environment that meets the general specifications

contained in this manual. Using this PLC in an environment outside the range of the general specifications could result in electric shock, fire, erroneous operation, and damage to or deterioration of the product. Hold down the module loading lever at the module bottom, and

securely insert the module fixing latch into the fixing hole in the base unit. Incorrect loading of the module can cause a malfunction, failure or drop.When using the PLC in the environment of much vibration, tighten the module with a screw. Tighten the screw in the specified torque range. Undertightening can cause a drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to damage to the screw or module. When installing more cables, be sure that the base unit and the module

connectors are installed correctly. After installation, check them for looseness. Poor connections could cause an input or output failure. Securely load the memory card by pushing it into the memory card

loading slot. Check for insecure loading after loading the memory card. Not doing so can cause a malfunction due to a contact fault. Completely turn off the external power supply before loading or

unloading the module. Not doing so could result in electric shock or damage to the product. Do not directly touch the module's conductive parts or electronic

components. Touching the conductive parts could cause an operation failure or give damage to the module.

This section gives instructions for handling the CPU, I/O, intelligent function and power supply modules, base units and so on.

(1) Module enclosure, terminal block connectors and pin connectors are made of resin;

do not drop them or subject them to strong impact.

(2) Do not remove modules' printed circuit boards from the enclosure in order to avoid

changes in operation.

(3) Tighten the module fixing screws and terminal block screws within the tightening

torque range specified below.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 91)
Fig. 47

Module fixing screw (M3 12 screw) 36 to 48 N • cm

I/O module terminal block screw (M3 screw) 42 to 58 N • cm

I/O module terminal block fixing screw (M3.5 screw) 66 to 89 N • cm

Power supply module terminal screw (M3.5 screw) 66 to 89 N • cm

(4) Be sure to install the power supply module in the Q3 B, Q6 B and QA1S6 B. Even if the power supply module is not installed, when the I/O modules and intelligent function module installed on the base units are of light load type, the modules may be operated. In this case, because a voltage becomes unstable, we cannot guarantee the operation.

(5) When an extension cable is used, do not bind the cable together with the main

circuit (high voltage, heavy current) line or lay them close to each other.

9 - 9 9 - 9

Page 92 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 10 9 - 10
Page 92 · click to enlarge
Page 92

MELSEC-Q 9 LOADING AND INSTALLATION

(6) Install the main base unit (by screwing) in the following procedure.

1. Fit the two base unit top mounting screws into the enclosure.
2. Place the right-hand side notch of the base unit onto the right-hand side screw.
3. Place the left-hand side pear-shaped hole onto the left-hand side screw.
4. Fit the mounting screws into the mounting screw holes in the base unit bottom and retighten the four mounting screws. Note1 : Install the main base unit to a panel, with no module loaded in the right-end

slot. Remove the base unit after unloading the module from the right-end slot. Note2 : The mounting screws that included with the slim type main base unit differ

from those included with other types of the base unit. When ordering mounting screws for the slim type main base unit, specify "cross recessed head bind screw M4 x 12 (black)."

9 - 10 9 - 10

Panel · Panel · Panel

Page 93 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 11 9 - 11
Page 93 · click to enlarge
Page 93

MELSEC-Q 9 LOADING AND INSTALLATION

(7) Note the following points when mounting a DIN rail.

Mounting a DIN rail needs special adaptors (optional), which are to be user- prepared. (a) Applicable adaptor types

For Q38B, Q312B, Q68B, Q612B : Q6DIN1 For Q35B, Q65B : Q6DIN2 For Q33B, Q52B, Q55B, Q63B, Q32SB, Q33SB, Q35SB : Q6DIN3

(b) Adaptor installation method

The way to install the adaptors for mounting a DIN rail to the base unit is given below.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Adaptor installation method diagram (page 93)
Fig. 48 · (b) Adaptor installation method

Place the hook of the adaptor (small) in the lower hole.

Push the top of the adaptor (small) far enough until it "clicks".

Insert the adaptor (large) into the grooves of the base unit from below.

Push the bottom of the adaptor (large) far enough until it "clicks". (c) Applicable DIN rail types (JIS C 2812)

TH35-7.5Fe TH35-7.5Al TH35-15Fe

(d) DIN rail mounting screw intervals

When using a TH35-7.5Fe or TH35-7.5Al DIN rail, rail mounting screws should be tightened at a pitch of 200 mm (7.88 inch) or less in order to ensure that the rail has sufficient strength.

DIN rail DIN rail mounting screw

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — TH35-7.5Fe TH35-7.5Al TH35-15Fe diagram (page 93)
Fig. 49 · TH35-7.5Fe TH35-7.5Al TH35-15Fe

35mm (1.38 inch)

P=200mm (7.88 inch) or less

9 - 11 9 - 11

Base unit rear

Page 94 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 12 9 - 12
Page 94 · click to enlarge
Page 94

MELSEC-Q 9 LOADING AND INSTALLATION

9.3.2 Instructions for mounting the base unit

When mounting the PLC to an enclosure or similar, fully consider its operability, maintainability and environmental resistance.

(1) Module mounting position

For enhanced ventilation and ease of module replacement, leave the following clearances between the module top/bottom and structure/parts. (a) In case of main base unit or extension base unit

Indicates the panel top, wiring duct or any part position.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) Module mounting position diagram (page 94)
Fig. 50 · (1) Module mounting position
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (1) Module mounting position diagram (page 94)
Fig. 51 · (1) Module mounting position

30mm (1.18 inch) or more 1

30mm (1.18 inch) or more

5mm (0.20 inch) or more 2 5mm (0.20 inch) or more

1. For wiring duct with 50mm (1.97 inch) or less height. 40mm (1.58 inch) or more for other cases. 2 : 20mm (0.79 inch) or more when the adjacent module is not removed and the extension cable is connected. 3 : 80mm (3.15 inch) or more for the connector type.

9 - 12 9 - 12

Page 95 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 13 9 - 13
Page 95 · click to enlarge
Page 95

MELSEC-Q 9 LOADING AND INSTALLATION

(b) In case of slim type main base unit

Indicates the panel top, wiring duct or any part position.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) In case of slim type main base unit diagram (page 95)
Fig. 52 · (b) In case of slim type main base unit

30 mm (1.18 inch) or more 1

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) In case of slim type main base unit diagram (page 95)
Fig. 53 · (b) In case of slim type main base unit

30 mm (1.18 inch) or more

1 : For wiring duct with 50 (1.97 inch) mm or less height. 40 mm (1.58 inch) or more for other cases. 2 : The cable of the power supply module of the slim type main base unit protrudes out of the left end of the module. Install the module while reserving 17 mm (0.67 inch) or more wiring space. If the cable sheath is susceptible to damage caused by a structural object or part on the left side of the module, take a protective measure with spiral tube or a similar insulator. 3 : 80 mm (3.15 inch) mm or more for the connector type.

9 - 13 9 - 13

Panel · Door

Page 96 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 14 9 - 14
Page 96 · click to enlarge
Page 96

MELSEC-Q 9 LOADING AND INSTALLATION

(2) Module mounting orientation

(a) Since the PLC generates heat, it should be mounted on a well ventilated

location in the orientation shown below.

(b) Do not mount it in either of the orientations shown below.

Vertical Flat (3) Installation surface

Mount the base unit on a flat surface. If the mounting surface is not even, this may strain the printed circuit boards and cause malfunctions. (4) Installation of unit in an area where the other devices are installed

Avoid mounting base unit in proximity to vibration sources such as large magnetic contractors and no-fuse circuit breakers; mount these on a separate panel or at a distance. (5) Distances from the other devices

  • In order to avoid the effects of radiated noise and heat, provide the clearances indicated below between the PLC and devices that generate noise or heat (contactors and relays).
  • Required clearance in front of PLC : at least 100 mm (3.94 inch)
  • Required clearance on the right and left of PLC : at least 50 mm (1.97 inch)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Vertical Flat (3) Installation surface diagram (page 96)
Fig. 54 · Vertical Flat (3) Installation surface
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Vertical Flat (3) Installation surface diagram (page 96)
Fig. 55 · Vertical Flat (3) Installation surface

9 - 14 9 - 14

Page 97 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 15 9 - 15
Page 97 · click to enlarge
Page 97

MELSEC-Q 9 LOADING AND INSTALLATION

9.3.3 Installation and removal of module

This section explains how to install and remove a power supply, CPU, I/O, intelligent function or another module to and from the base unit.

(1) Installation and removal of the module from Q3 B, ,Q5 B and

Q6 B The installation and removal of the module from Q3 B/Q6 B base unit are described below. (a) Installation of module on Q3 B, Q5 B and Q6 B

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 97)
Fig. 56

Insert the module fixing latch into the module fixing hole of the base unit.

Push the module in the direction of arrow to load it into the base unit.

Make sure that the module is inserted in the base unit securely.

POINTS (1) Always insert the module fixing latch of the module into the module fixing hole.

Forcing the hook into the hole will damage the module connector and module. (2) When using the PLC in a place where there is large vibration or impact, screw

the CPU module to the base unit. Module fixing screw : M3 12 (user-prepared)

9 - 15 9 - 15

Base unit

Page 98 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 16 9 - 16
Page 98 · click to enlarge
Page 98

MELSEC-Q 9 LOADING AND INSTALLATION

(b) Removal from Q3 B, Q5 B and Q6 B

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Removal from Q3 B, Q5 B and Q6 B diagram (page 98)
Fig. 57 · (b) Removal from Q3 B, Q5 B and Q6 B

Hold the module with both hands, and push the unit fixing hook on the top of the module with a finger until it stops.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Removal from Q3 B, Q5 B and Q6 B diagram (page 98)
Fig. 58 · (b) Removal from Q3 B, Q5 B and Q6 B

While pushing the unit fixing hook, and using the bottom of the module as a support, pull the module toward you.

Lift the module upwards and remove the module fixing latch from the module fixing hole.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Removal from Q3 B, Q5 B and Q6 B diagram (page 98)
Fig. 59 · (b) Removal from Q3 B, Q5 B and Q6 B

POINT When the module fixing screw is used, always remove the module by removing the module fixing screw and then taking the module fixing latch off the module fixing hole of the base unit. Do not try to remove the module forcibly since this may damage the module.

9 - 16 9 - 16

Module connector

Page 99 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 17 9 - 17
Page 99 · click to enlarge
Page 99

MELSEC-Q 9 LOADING AND INSTALLATION

(2) Installation and removal of the module from QA1S6 B

The procedure for installing and removing the module from the QA1S6 B base unit is described below. (a) Installation of module on QA1S6 B

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 99)
Fig. 60
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 99)
Fig. 61

Insert the module fixing projections into the module fixing hole in the base unit.

Install the module onto the base unit by pushing the top forward.

Make sure that the module is firmly inserted in the base unit. Then, secure it with the module mounting screw.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 99)
Fig. 62

POINT Make sure to install the module, with the module fixing projection inserted into the module fixing hole, using the module fixing screws. Do not try to forcibly install the module without inserting the projection into the hole, since this may damage the module connector and the module.

9 - 17 9 - 17

Show 6 more labels / short text on this page
Base unit · Module connector · Module fixing hole · Module mounting screw · Base unit · Module
Page 100 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 18 9 - 18
Page 100 · click to enlarge
Page 100

MELSEC-Q 9 LOADING AND INSTALLATION

(b) Removal from QA1S6 B

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Removal from QA1S6 B diagram (page 100)
Fig. 63 · (b) Removal from QA1S6 B
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Removal from QA1S6 B diagram (page 100)
Fig. 64 · (b) Removal from QA1S6 B

Remove the module mounting screw, and using the bottom of the module as a support, pull the top of the module toward you.

Lift the module upwards and remove the module fixing projections from the module fixing hole.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (b) Removal from QA1S6 B diagram (page 100)
Fig. 65 · (b) Removal from QA1S6 B

POINT To remove the module, make sure to remove the module fixing screws, and then disengage the module fixing projection from the module fixing hole. Do not try to remove the module forcibly since this may damage the module fixing projection.

9 - 18 9 - 18

Base unit · Module connector · Module fixing hole

Page 101 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 19 9 - 19
Page 101 · click to enlarge
Page 101

MELSEC-Q 9 LOADING AND INSTALLATION

9.4 How to Set Stage Numbers for the Extension Base Unit

When using two or more extension base units, their stage numbers must be set with their stage number setting connectors. Extension 1 need not be set since the extension number is factory-set to 1. Make this setting in the following procedure.

(1) The stage number setting connector of the extension base unit is located under the

IN side base cover. (Refer to Section 6.4 for the setting of the extension number setting connector.) First, loosen the upper and lower screws in the IN side base cover and remove the base cover from the extension base unit.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 101)
Fig. 66

(2) Insert the connector pin in the required stage number location of the connector

(PIN1) existing between the IN and OUT sides of the extension cable connector.

OUT

(3) Install the base cover to the extension base unit and tighten the base cover screw.

(Tightening torque: 36 to 48N • cm)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (Tightening torque: 36 to 48N • cm) diagram (page 101)
Fig. 67 · (Tightening torque: 36 to 48N • cm)

9 - 19 9 - 19

Page 102 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 20 9 - 20
Page 102 · click to enlarge
Page 102

MELSEC-Q 9 LOADING AND INSTALLATION

9.5 Connection and Disconnection of Extension Cable

(1) Instructions for handling an extension cable

  • Do not stamp an extension cable.
  • An extension cable must be connected to the base unit when the base cover has been installed. (After you have set the extension number to the extension base unit, reinstall and screw the base cover.)
  • When running an extension cable, the minimum bending radius of the cable should be 55mm (2.17 inch) or more. If it is less than 55mm (2.17 inch), a malfunction may occur due to characteristic deterioration, open cable or the like.
  • When connecting or disconnecting an extension cable, do not hold the ferrite cores mounted at both ends of the cable. Hold the connector part of the cable for connection or disconnection.

Holding the ferrite core may cause the cable to open within the connector. Also, if the ferrite core is shifted, the characteristic will change. When handling the cable, take care not to shift the ferrite core positions. (2) Connection of extension cable

POINT When connecting an extension base unit to the main base unit with an extension cable, always plug the OUT side connector of the main base unit and the IN side connector of the extension base unit with an extension cable. The system will not operate properly if the extension cable is connected in the form of IN to IN, OUT to OUT or IN to OUT. When connecting two or more extension base units, plug the OUT side connector of the first extension base unit and the IN side connector of the second extension base unit with an extension cable.

9 - 20 9 - 20

Page 103 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 21 9 - 21
Page 103 · click to enlarge
Page 103

MELSEC-Q 9 LOADING AND INSTALLATION

(a) To connect an extension cable to the main base unit, remove the portion

under the OUT characters on the base cover with a tool such as a flat-blade screwdriver (5.5 75, 6 100). This also applies to a case where an extension cable is connected to the OUT side connector of the extension base unit.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 103)
Fig. 68
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 9 LOADING AND INSTALLATION diagram (page 103)
Fig. 69

(b) To connect the extension cable to the next extension base unit, remove the

seal applied under the IN characters on the base cover.

IN side of extension base unit

OUT IN

(c) When plugging the extension cable to any base unit, hold the connector part

of the extension cable.

(d) After fitting the extension cable, always tighten the extension cable connector

fixing screws. (Tightening torque: 20N • cm)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (d) After fitting the extension cable, always tighten the extension cable connector diagram (page 103)
Fig. 70 · (d) After fitting the extension cable, always tighte…

9 - 21 9 - 21

Base cover · Seal

Page 104 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 22 9 - 22
Page 104 · click to enlarge
Page 104

MELSEC-Q 9 LOADING AND INSTALLATION

(3) Disconnection of extension cable

When unplugging the extension cable, hold and pull the connector part of the extension cable after making sure that the fixing screws have been removed completely.

9 - 22 9 - 22

Page 105 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 200VAC
Page 105 · click to enlarge
Page 105

MELSEC-Q 9 LOADING AND INSTALLATION

9.6 Wiring

9.6.1 The precautions on the wiring

! DANGER Completely turn off the external power supply when installing or

placing wiring. Not completely turning off all power could result in electric shock or damage to the product. When turning on the power supply or operating the module after

installation or wiring work, be sure that the module's terminal covers are correctly attached. Not attaching the terminal cover could result in electric shock.

! CAUTION Be sure to ground the FG terminals and LG terminals to the

protective ground conductor. Not doing so could result in electric shock or erroneous operation. When wiring in the PLC, be sure that it is done correctly by checking

the product's rated voltage and the terminal layout. Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or damage. External connections shall be crimped or pressure welded with the

specified tools, or correctly soldered. Imperfect connections could result in short circuit, fires, or erroneous operation. Tighten the terminal screws with the specified torque. If the terminal screws

are loose, it could result in short circuits, fire, or erroneous operation. Tightening the terminal screws too far may cause damages to the screws and/or the module, resulting in fallout, short circuits, or malfunction. Be sure there are no foreign substances such as sawdust or wiring

debris inside the module. Such debris could cause fires, damage, or erroneous operation. The module has an ingress prevention label on its top to prevent

foreign matter, such as wire offcuts, from entering the module during wiring. Do not peel this label during wiring. Before starting system operation, be sure to peel this label because of heat dissipation.

The precautions on the connection of the power cables are described below. (1) Power supply wiring

(a) Separate the PLC's power supply line from the lines for I/O devices and

power devices as shown below. When there is much noise, connect an insulation transformer.

PLC power supply Main power supply

200VAC

PLC

T1

9 - 23 9 - 23

Show 5 more labels / short text on this page
Insulation transformer · I/O power supply · I/O devices · Main circuit device · Main circuit device
Page 106 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 24 9 - 24
Page 106 · click to enlarge
Page 106

MELSEC-Q 9 LOADING AND INSTALLATION

(b) Do not connect the 24VDC outputs of two or more power supply modules in

parallel to supply power to one I/O module. Parallel connection will damage the power supply modules.

24VDC

24VDC 24VDC

(c) 100VAC, 200VAC and 24VDC wires should be twisted as dense as possible.

Connect the modules with the shortest distance. Also, to reduce the voltage drop to the minimum, use the thickest wires possible (maximum 2mm2). (d) Do not bundle the 100VAC and 24VDC wires with, or run them close to, the

main circuit (high voltage, large current) and I/O signal lines. Reserve a distance of at least 100 mm from adjacent wires. (e) As a countermeasure to power surge due to lightening, connect a surge

absorber for lightening as shown below.

AC

PLC

E2

E1

Surge absorber for lightening

POINT (1) Separate the ground of the surge absorber for lightening (E1) from that of the

PLC (E2). (2) Select a surge absorber for lightening whose power supply voltage does no

exceed the maximum allowable circuit voltage even at the time of maximum power supply voltage elevation.

9 - 24 9 - 24

Show 8 more labels / short text on this page
Power supply · module Power supply · I/O module · Power supply · I/O module · module · module · External power supply
Page 107 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 25 9 - 25
Page 107 · click to enlarge
Page 107

MELSEC-Q 9 LOADING AND INSTALLATION

(2) Wiring of I/O equipment

(a) Insulation-sleeved crimping terminals cannot be used with the terminal block.

It is recommended to cover the wire connections of the crimping terminals with mark or insulation tubes. (b) The wires used for connection to the terminal block should be 0.3 to 0.75mm2

in core and 2.8mm (0.11 inch) max. in outside diameter. (c) Run the input and output lines away from each other. (d) When the wiring cannot be run away from the main circuit and power lines,

use a batch-shielded cable and ground it on the PLC side. In some cases, ground it in the opposite side.

RA

DC

(e) Where wiring runs through piping, ground the piping without fail. (f) Run the 24VDC input line away from the 100VAC and 200VAC lines. (g) Wiring of 200m (686.67 ft.) or longer distance will give rise to leakage currents

due to the line capacity, resulting in a fault. Refer to Section 11.5 for details. (3) Grounding

To ground the cable, follow the steps (a) to (c) shown below. (a) Use the dedicated grounding as far as possible.

(b) When a dedicated grounding cannot be performed, use (2) Common

Grounding shown below.

PLC Another equipment PLC Another equipment

(1) Independent grounding Best (2) Common grounding Good (3) Joint grounding Not allowed

(c) For grounding a cable, use the cable of 2 mm2 or more.

Position the ground-contact point as closely to the sequencer as possible, and reduce the length of the grounding cable as much as possible.

9 - 25 9 - 25

Show 7 more labels / short text on this page
PLC Shielded cable · Input · Output · Shield · PLC Another equipment · grounding · grounding
Page 108 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 9 - 26 9 - 26
Page 108 · click to enlarge
Page 108

MELSEC-Q 9 LOADING AND INSTALLATION

9.6.2 Connecting to the power supply module

The following diagram shows the wiring example of power lines, grounding lines, etc. to the main and extension base units.

100/110VAC

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — 100/110VAC diagram (page 108)
Fig. 71

Connect to 24VDC terminals of I/O module that requires 24VDC internally.

POINTS (1) Use the thickest possible (max. 2 mm2 (14 AWG)) wires for the 100/200 VAC

and 24 VDC power cables. Be sure to twist these wires starting at the connection terminals. To prevent a short-circuit should any screws loosen, use solderless terminals with insulation sleeves. (2) When the LG terminals and FG terminals are connected, be sure to ground the

wires. Do not connect the LG terminals and FG terminals to anything other than ground. If LG terminals and FG terminals are connected without grounding the wires, the PLC may be susceptible to noise. In addition, since the LG terminals have potential, the operator may receive an electric shock when touching metal parts. (3) 1 An error cannot be output from the ERR terminal of the power supply module loaded on the extension base. To output an error, use the ERR terminal of the power supply module loaded on the main base unit.

9 - 26 9 - 26

Main base unit

Page 109 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 1 10 - 1
Page 109 · click to enlarge
Page 109

MELSEC-Q 10 MAINTENANCE AND INSPECTION

10 MAINTENANCE AND INSPECTION

! DANGER Do not touch the terminals while power is on.

Doing so could cause shock. Correctly connect the battery. Also, do not charge, disassemble,

heat, place in fire, short circuit, or solder the battery. Mishandling of a battery can cause overheating or cracks which could result in injury and fires. Turn the power off when cleaning the module or tightening the

terminal screws or module mounting screws. Conducting these operations when the power is on could result in electric shock. Loose terminal screws may cause short circuits or malfunctions. Failure to mount the module properly will result in short circuit, malfunction or in the module falling.

! CAUTION In order to ensure safe operation, read the manual carefully to

acquaint yourself with procedures for program change, forced outputs, RUN, STOP, and PAUSE operations, etc., while operation is in progress. Operation mistakes could cause damage to the equipment and other problems. Never try to disassemble of modify module. It may cause product

failure, malfunction, fire or cause injury. When using any radio communication device such as a cellular

phone or a PHS phone, keep them away from the controller at least 25 cm (9.85 inch) or it may cause a malfunction. Turn the power off when installing or removing the modules.

Trying to install or remove the module while the power is on could damage the module or result in erroneous operation.

In order that you can use the PLC in normal and optimal condition at all times, this section describes those items that must be maintained or inspected daily or at regular intervals.

10 - 1 10 - 1

Page 110 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 2 10 - 2
Page 110 · click to enlarge
Page 110

MELSEC-Q 10 MAINTENANCE AND INSPECTION

10.1 Daily Inspection

The items that must be inspected daily are listed below.

Daily inspection

Item Inspection Item Inspection Judgment Criteria Remedy

Check that fixing screws are not loose and the cover is not dislocated.

The screws and cover must be installed securely.

Further tighten the screws.

1 Installation of base unit

Check that the module is not dislocated and the unit fixing hook is engaged securely.

2 Installation of I/O module

The unit fixing hook must be engaged and installed securely.

Securely engaged the unit fixing hook.

Check for loose terminal screws. Screws should not be loose. Retighten terminal screws Check distance between Solderless terminals.

The proper clearance should be provided between Solderless terminals Correct. 3 Connecting conditions

Check connectors of extension cable. Connections should no be loose. Retighten connector mounting screws. Power supply "POWER" LED Check that the LED is ON. The LED must be ON. (Abnormal if the

LED is OFF.) CPU " RUN " LED

The LED must be ON. (Abnormal if the LED is OFF.) CPU "ERR." LED

Check that the LED is ON in RUN status.

The LED must be OFF. (Abnormal if the LED is ON or flickering.) CPU "BAT." LED

Check that the LED is OFF.

Module indication LED

Check that the LED is OFF.

The LED must be OFF. (Abnormal if the LED is ON.)

The LED must be ON when the input power is turned ON. The LED must be extinguished when the input power is turned OFF. (Abnormal if the LED does not turn ON or turn OFF as indicated above.)

Follow Section 10.2.

Input LED Check that the LED turns ON and OFF.

The LED turns ON when the output power is turned ON. The LED must be extinguished when the output power is turned OFF. (Abnormal if the LED does not turn ON or turn OFF as indicated above.)

Output LED Check that the LED turns ON and OFF.

10 - 2 10 - 2

Page 111 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 3 10 - 3
Page 111 · click to enlarge
Page 111

MELSEC-Q 10 MAINTENANCE AND INSPECTION

10.2 Periodic Inspection

The items that must be inspected one or two times every 6 months to 1 year are listed below. When the equipment is moved or modified, or layout of the wiring is changed, also perform this inspection.

Periodic Inspection

Item Inspection Item Inspection Judgment Criteria Remedy

Ambient environment

Ambient temperature 0 to 55 °C

When the sequencer is used in the board, the ambient temperature in the board becomes the ambient temperature.

Measure with a thermometer and a hygrometer. Measure corrosive gas.

Ambient humidity 5 to 95 %RH 1 1

Corrosive gas must not be present.

Atmosphere

85 to 132VAC 170 to 264VAC 2 Power voltage

Measure a voltage across the terminals of 100/200VAC and 24VDC. 15.6 to 31.2VDC

Change the power supply.

Further tighten screws. If the CPU, I/O, or power supply module is loose, fix it with screws. 3

Looseness, rattling Move the module to check for looseness and rattling.

The module must be installed fixedly.

Installation

Adhesion of dirt and foreign matter Check visually. Dirt and foreign matter must not be present. Remove and clean.

Looseness of terminal screws

Try to further tighten screws with a screwdriver. Screws must not be loose. Further tighten.

Connection

Proximity of solderless terminals to each other

Check visually. Solderless terminals must be positioned at proper intervals. Correct. 4

Looseness of connectors Check visually. Connectors must not be loose. Further tighten connector

fixing screws.

Even if the lowering of a battery capacity is not shown, replace the battery with a new one if a specified service life of the battery is exceeded.

check on the monitor mode of the GX Developer that SM51 or SM52 is turned OFF.

5 Battery

(Preventive maintenance)

1 When AnS Series Module is included in the system, the judgement criteria will be from 10 to 90 % RH.

10 - 3 10 - 3

Page 112 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 4 10 - 4
Page 112 · click to enlarge
Page 112

MELSEC-Q 10 MAINTENANCE AND INSPECTION

10.3 Battery Replacement

When the voltage of the program and power interrupt hold-on function backup battery is lowered, the special relays SM51 and SM52 are energized. Even if these special relays are energized, the contents of the program and power interrupt hold-on function are not erased immediately. If the energization of these relays is recognized, however, these contents may be deleted unintentionally. While a total of the power interrupt hold-on time after the SM51 is energized is within a specified time, replace the battery with a new one.

POINTS The SM51 is used to give an alarm when the capacity of the battery is lowered. Even after it is energized, the data is held for a specified time. For safety, however, replace the battery with a new one as early as possible. The SM52 is energized when the battery causes a complete discharge error. Immediately after the relay has been energized, replace the battery with a new one. Whichever voltage of the battery of the CPU module and SRAM card is lowered, the SM51 and SM52 are energized. To identify the specific battery of the memory of which voltage is lowered, check the contents of the special resisters SD51 and SD52. When the voltage of the battery of each memory is lowered, the bit corresponding to each of SD51 and SD52 memories is turned on.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 10 MAINTENANCE AND INSPECTION diagram (page 112)
Fig. 72

Bit No. of SD51 and SD52 Object

Bit 0 CPU module

Bit 1, 2 SRAM card

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Bit No. of SD51 and SD52 Object diagram (page 112)
Fig. 73 · Bit No. of SD51 and SD52 Object

POINTS The relation between the backups of the memories preformed by the batteries which are installed on the CPU module and SRAM card is described below. The items that must be considered are the following two points. 1) The battery installed on the CPU module cannot backup the memory of the SRAM card. 2) The battery installed on the SRAM card cannot backup the memory of the CPU module.

Memory of SRAM Card ON Connection OFF ON ON

The standard service life and replacement procedures of the battery is described on the next page.

10 - 4 10 - 4

Page 113 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 5 10 - 5
Page 113 · click to enlarge
Page 113

MELSEC-Q 10 MAINTENANCE AND INSPECTION

10.3.1 Battery life

(1) CPU module battery (Q6BAT) life

(a) The CPU module battery life is given below.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 10 MAINTENANCE AND INSPECTION diagram (page 113)
Fig. 74

alarm occurrence) 0% 5433hr 13120hr 120hr 30% 7761hr 18742hr 120hr 50% 10866hr 26240hr 120hr 70% 18110hr 43733hr 120hr Q02CPU

100% 10years 10years 120hr 0% 2341hr 6435hr 120hr 30% 3344hr 9192hr 120hr 50% 4682hr 12870hr 120hr 70% 7803hr 21450hr 120hr

100% 10years 10years 120hr 0% 1260hr 4228hr 48hr 30% 1800hr 6040hr 48hr 50% 2520hr 8456hr 48hr 70% 4200hr 14093hr 48hr

1. The energization time ratio denotes the ratio of power-on time in a day (24 hours). (When power is on for 12 hours and off for 12 hours, the energization time ratio is 50%.)

(b) The Q6BAT life is 10 years when it is used without connecting to the CPU

module.

(2) SRAM card battery life

The SRAM card battery life changes depending on the combination of the serial number (first 5 digits) of the CPU module and the manufacturing control number of the memory card. The SRAM card battery life is indicated below.

(a) CPU module whose serial number's first 5 digits are "04012" or later

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (2) SRAM card battery life diagram (page 113)
Fig. 75 · (2) SRAM card battery life

0% 2400hr 2.7years 20hr 30% 2880hr 3.6years 20hr 50% 4320hr 4.5years 20hr 70% 6480hr 5.0years 20hr

2 100% 5.0years 5.0years 50hr 0% 2400hr 2.7years 20hr 30% 2880hr 3.6years 20hr 50% 4320hr 4.5years 20hr 70% 6480hr 5.0years 20hr Q2MEM-2MBS

10 - 5 10 - 5

Page 114 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 6 10 - 6
Page 114 · click to enlarge
Page 114

MELSEC-Q 10 MAINTENANCE AND INSPECTION

(b) CPU module whose serial number's first 5 digits are "04011" or earlier

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q 10 MAINTENANCE AND INSPECTION diagram (page 114)
Fig. 76
1. The energization time ratio denotes the ratio of power-on time in a day (24 hours) . (When power is on for 12 hours and off for 12 hours, the energization time ratio is

50%.) 2: The manufacturing control number is given on the SRAM card rear label (see below).

CAUTION

Manufacturing control number

Do not subject to mechanical shock!

Do not expose to extreme temperrature,

POINT Remember that the SRAM card consumes battery power even when the battery is connected to the CPU module and the power is turned ON.

If the special relay SM51 (battery low latch) turns on, immediately replace the battery. If an alarm has not yet occurred, it is recommended to replace the battery periodically according to the conditions of use.

10 - 6 10 - 6

Page 115 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 7 10 - 7
Page 115 · click to enlarge
Page 115

MELSEC-Q 10 MAINTENANCE AND INSPECTION

10.3.2 Battery replacement procedure

(1) CPU module battery replacement procedure

When the CPU module battery has been exhausted, replace the battery with a new one according to the procedure shown below. The PLC power must be on for 10 minutes or longer before dismounting the battery. Even when the battery is dismounted, the memories are backed up by the capacitor for a while. However, if the replacement time exceeds the guaranteed value specified in the table below, the contents stored in the memories may be erased. To prevent this trouble, replace the battery speedily.

Backup time by capacitor

Backup time by capacitor[min]

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Backup time by capacitor diagram (page 115)
Fig. 77 · Backup time by capacitor

Insert a new battery into the holder in the correct direction. Connect the lead to the connector.

10 - 7 10 - 7

Page 116 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 10 - 8 10 - 8
Page 116 · click to enlarge
Page 116

MELSEC-Q 10 MAINTENANCE AND INSPECTION

(2) SRAM card CPU module battery replacement procedure

Replace the SRAM card battery in the following procedure.

POINTS Replace the battery while paying attention to the following. (a) To back up the data, replace the SRAM card battery with the PLC power supply

ON and the SRAM card installed. (b) Start replacement after backing up the CPU module data using GX Developer. (c) Since replacement is made with the PLC power supply ON, take extreme care

not to get an electric shock. (d) When dismounting or mounting the battery holder on the SRAM card, take care

so that the battery does not come out of the battery holder. (e) When replacing the battery with the PLC power supply OFF, always back up the

data before starting replacement. [Battery replacement procedure] 1) Back up the SRAM card data using GX Developer. 2) Replace the battery. 3) Write the backed up data from GX Developer to the memory card.

Open the front cover while the PLC power supply is on.

Using a flat screw-driver, slide the battery holder's locking switch away from the "LOCK" position.

Remove the battery holder from the SRAM card.

Remove the old battery from its holder.

Insert a new battery into the holder in the correct direction.

Push the battery holder all the way into the memory card, and confirm that the battery holder's locking switch is set to the "LOCK" position.

Monitor SM52 to verify on/off.

OFF

ON

Monitor SD52 to verify the bit number

Bit 0 is on.

that is on.

A bit other than 0 is on

The CPU module battery is faulty.

Bit 1 or 2 on: Memory card A battery is faulty.

Refer to Section 10.3.2 (1).

10 - 8 10 - 8

Show 5 more labels / short text on this page
Replacing battery · "RELEASE" position · Battery holder · '+' sign · Completion
Page 117 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 1 11 - 1
Page 117 · click to enlarge
Page 117

11 TROUBLESHOOTING

This section describes the various types of trouble that occur when the system is operated, and causes and remedies of these troubles. 11.1 Troubleshooting Basics

In order to increase the reliability of the system, not only highly reliable devices are used but also the speedy startup of the system after the occurrence of trouble becomes an important factor. To start up the system speedily, the cause of the trouble must be located and eliminated correctly. The basic three points that must be followed in the troubleshooting are as follows.

(1) Visual inspection

Visually check the following. 1) Movement of sequencer (stopped condition, operating condition) 2) Power supply on/off 3) Status of input/output devices 4) Power supply module, CPU module, I/O module, intelligent function module, installation condition of extension cable 5) Status of wiring (I/O cables, cables) 6) Display status of various types of indicators ("POWER" LED, "RUN" LED, "ERR." LED, I/O LED) 7) Status of setting of various types of set switches (Setting of No. of stages of extension base unit, power interrupt hold-on status)

After confirming items 1) to 7), connect the GX Developer, and check the operating conditions of the PLC and the contents of the program.

(2) Check of trouble

Check to see how the operating condition of the PLC varies while the PLC is operated as follows. 1) Set the RUN/STOP switch to STOP. 2) Reset the trouble with the RESET/L.CLR switch. 3) Turn ON and OFF the power supply.

(3) Reduction in area

Estimate the troubled part in accordance with items (1) and (2) above. 1) PLC or external devices 2) I/O module or others 3) Sequence program

11 - 1 11 - 1

Page 118 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 2 11 - 2
Page 118 · click to enlarge
Page 118

11.2 Troubleshooting

The trouble investigating methods, contents of troubles for the error codes, and remedies of the troubles are described below. 11.2.1 Troubleshooting flowchart

The following shows the contents of the troubles classified into a variety of groups according to the types of events.

Proceed to Section 11.2.2, "Flowchart for when the "MODE" LED is not turned on."

Proceed to Section 11.2.3, "Flowchart for when the "MODE" LED is flickering."

Proceed to Section 11.2.4, "Flowchart for when the "POWER" LED is turned off."

"RUN" LED off Proceed to Section 11.2.5, "Flowchart for when the "RUN" LED is turned off."

Proceed to Section 11.2.6, "When the "RUN" LED is flickering."

Proceed to Section 11.2.7, "Flowchart for when the "ERR." LED is on/flickering."

"ERR." LED on/flickering

Proceed to Section 11.2.8, "When the "USER" LED is turned on."

Proceed to Section 11.2.9, "When the "BAT. " LED is turned on."

"BAT. " LED on

Proceed to Section 11.2.10, "Flowchart for when the "BOOT" LED is flickering."

Proceed to Section 11.2.11, "Flowchart for when output module LED is not turned on" Output module LED not turned on

Proceed to Section 11.2.12 "Flowchart for when output load of output module dose not turn on."

I/O module not operating properly

Proceed to Section 11.2.13, "Flowchart for when unable to read a program."

Unable to read a program

Proceed to Section 11.2.14, "Flowchart for when unable to write a program."

Unable to write a program

Proceed to Section 11.2.15, "Flowchart for when unable to perform boot operation from memory card."

Unable to perform boot operation from memory card

Proceed to Section 11.2.16, "Flowchart for when UNIT. VERIFY ERR. occurs."

UNIT. VERIFY ERR. occurs.

Proceed to Section 11.2.17, "Flowchart for when CONTROL BUS ERR. occurs."

CONTROL BUS ERR. occurs.

11 - 2 11 - 2

Show 7 more labels / short text on this page
Error-occurrence description · "MODE" LED off · "MODE" LED flickering · "POWER" LED off · "RUN" LED flickering · "USER" LED on · "BOOT" LED flickering
Page 119 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 3 11 - 3
Page 119 · click to enlarge
Page 119

11.2.2 Flowchart for when the "MODE" LED is not turned on

The following shows the flowchart to be followed when the "MODE" LED of the CPU module does not turn on at PLC power-on.

"MODE" LED is not turned on.

Is the power supply for all the power supply modules turned on? Is the wiring of the power supply

NO

Check the wire and turn on the power supply.

YES NO YES

Is the "POWER" LED for the power supply module

NO

Exchange the power supply module, and confirm if "POWER" LED is turned on.

YES

NO

YES

Is the extension cable connected properly?(Isn't IN

NO

connected to IN or OUT

Connect the extension cable properly.

OUT?)

YES

NO YES

Is the CPU module RESET/L. CLR switch in

Set the RESET/L. CLR switch in the neutral position.

NO YES

Hardware fault Check operations in the order starting from the minimum system. If the module will not work, please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 3 11 - 3

Show 15 more labels / short text on this page
module correct? · Can "MODE" LED · be turned on? · turned on? · Can "MODE" LED · be turned on? · connected to · Can "MODE" LED · be turned on? · "RESET" position · the neutral position? · Neutral position · Can "MODE" LED · be turned on? · Completion
Page 120 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 4 11 - 4
Page 120 · click to enlarge
Page 120

11.2.3 Flowchart for when the "MODE" LED is flickering

The following shows the flowchart to be followed when the "MODE" LED of the CPU module flickers at PLC power-on, at operation start or during operation.

"MODE" LED is flickering

Did you make forced

YES

Cancel forced ON/OFF.

NO

NO

YES

Is the "MODE" LED turned on?

Is the RESET/L.CLR switch of the CPU module in

Move the RESET/L.CLR switch to the neutral position.

NO

YES

Is the "MODE" LED turned on?

Hardware fault Check operations in the order starting from the minimum system. If the module will not work, please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 4 11 - 4

Show 5 more labels / short text on this page
ON/OFF setting? · RESET position · the neutral position? · Neutral position · Completion
Page 121 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 5 11 - 5
Page 121 · click to enlarge
Page 121

11.2.4 Flowchart for when the "POWER" LED is turned off

The following shows the flowchart to be followed when the "POWER" LED of the power supply module turns off at PLC power-on or during operation.

"POWER" LED is turned off.

NO

Is there a power supply? Supply power.

YES

NO YES

Is the power supply voltage within the voltage range given in the

NO

The supply voltage should be within the rated range.

YES NO YES

Properly fix the power supply module. Is the power supply

NO

YES

NO YES

1. Check the electric-current capacity and reduce the amount of overcurrent. 2) Turn OFF the input power and wait several minutes before turning it ON again.

Is overcurrent protection and overvoltage

YES

NO

NO YES

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 5 11 - 5

Show 12 more labels / short text on this page
Can "POWER" LED · be turned on? · specifications? · Can "POWER" LED · be turned on? · module fixed? · Can "POWER" LED · be turned on? · protection working? · Can "POWER" LED · be turned on? · Completion
Page 122 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — NO
Page 122 · click to enlarge
Page 122

11.2.5 Flowchart for when the "RUN" LED is turned off

The following shows the flowchart to be followed when the "RUN" LED of the CPU module turns off during PLC operation.

"RUN" LED is turned off.

Is the "POWER" LED of the power supply module lit?

Proceed to Section 11.2.4, "Flowchart for when the "POWER" LED is turned off."

NO

YES

Proceed to Section 11.2.7, "Flowchart for when the "ERR." LED is on/flickering."

Is "ERR." LED

YES

NO

"RUN" LED is on.

(1) PLC part/connection fault (2) By excessive noise

Reset the CPU module RESET/L. CLR switch.

"RUN" LED is off.

For the case of (1) For the case of (2)

Set the CPU module's RUN/STOP switch to STOP and write END to address 0 with the GX Developer.

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

Set the RUN/STOP switch to RUN and enter to the monitor mode with the GX Developer to be operated.

"RUN" LED does not turn on.

"RUN" LED is on.

Considered to be a sequence program error.

Check the program and modify the program error location.

Connect a surge protector circuit such as CR to the noise source.

NO

YES

11 - 6 11 - 6

Show 4 more labels / short text on this page
on/flickering? · Can "RUN" LED · be turned on? · Completion
Page 123 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — NO
Page 123 · click to enlarge
Page 123

11.2.6 When the "RUN" LED is flickering

If the "RUN" LED flickers, follow the steps below. The High Performance model QCPU flickers the "RUN" LED when the RUN/STOP switch is set from STOP to RUN after the programs or parameters are written in the CPU module during the stoppage. Though this is not the trouble with the CPU module, the operation of the CPU module is stopped. To bring the CPU module into RUN status, reset the CPU module with the RESET/L.CLR or set the RUN/STOP switch again from STOP to RUN. The "RUN" LED turns on. 11.2.7 Flowchart for when the "ERR." LED is on/flickering

The following shows the flowchart to be followed when the "ERR." LED of the CPU module turns on or flickers at PLC power-on, at operation start or during operation.

"ERR." LED is on/flickering.

Confirm details of error by GX Developer. (Refer to Section 11.3.)

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

Set the RUN/STOP switch to STOP.

Modify error details. (Refer to Section 11.3.)

Reset by the RESET/L. CLR switch.

Set the RUN/STOP switch to RUN.

Can the "ERR." LED

NO

YES

11 - 7 11 - 7

Hardware fault · be turned off? · Completion

Page 124 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 8 11 - 8
Page 124 · click to enlarge
Page 124

11.2.8 When the "USER" LED is turned on

  • If the "USER" LED turns on, follow the steps described below. The "USER" LED turns on when an error is detected by the CHK instruction or the annunciator (F) turns on. If the "USER" LED is on, monitor the special relays SM62 and SM80 in the monitor mode of GX Developer.
  • When M62 has turned ON The annunciator (F) is ON. Using SD62 to SD79, check the error cause.
  • When SM80 has turned ON The "USER" LED was on by the execution of the CHK instruction. Using SD80, check the error cause. Eliminate the error cause after confirming it. The "USER" LED can be turned off by:
  • Making a reset with the RESET/L.CLR switch; or
  • Executing the LEDR instruction in the sequence program.

REMARK

When the RESET/L.CLR switch is tilted to L.CLR several times for latch clear operation, the "USER" LED flickers to indicate that the latch clear processing is under operation. When the RESET/L.CLR switch is further tilted to L.CLR while the "USER" LED flickers, the "USER" LED turns off and terminates the latch clear processing. 11.2.9 When the "BAT." LED is turned on

If the "BAT." LED turns on, follow the steps described below. The "BAT." LED turns on when a low battery capacity is detected. If the "BAT." LED is on, monitor the special relays and special registers in the monitor mode of GX Developer to check which of the CPU module and SRAM card batteries was lowered in capacity. (SM51 to SM52, SD51 to SD52) After confirmation, replace the battery with a new one, and reset the CPU module with the RESET/L.CLR switch or run the LEDR instruction, and the "BAT. " LED will turns off.

11 - 8 11 - 8

Page 125 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 9 11 - 9
Page 125 · click to enlarge
Page 125

11.2.10 Flowchart for when the "BOOT" LED is flickering

The following shows the flowchart to be followed when the "BOOT" LED of the CPU module flickers at PLC power-on, at operation start or during operation.

Power off the PLC.

Remove the memory card.

Move the DIP switches SW2 and SW3 of the CPU module to ON.

Power on the PLC.

YES

Completion of automatic write from memory card to standard ROM

Is the "BOOT" LED turned on?

NO

Perform boot operation from standard ROM.

CPU module hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 9 11 - 9

"BOOT" LED flickering

Page 126 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 10 11 - 10
Page 126 · click to enlarge
Page 126

11.2.11 Flowchart for when output module LED is not turned on

The following shows the flowchart to be followed when the output module LED does not turn on during PLC operation.

Output module LED not turned on

Is the "MODE" LED on? Refer to Section 11.2.3.

YES

Is the LED on when it is monitored on GX Developer?

NO

Reexamine the program.

YES

Check the input/output number on the GX Developer system monitor.

NO

Does the output number match?

Change the output number.

YES

Is the LED turned on when another output module

NO

is forcibly turned on?

YES

Is the LED turned on when the output module is changed for another output module,

CPU module, base unit, extension cable hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

Output module hardware fault Consult your local system service, agency or branch office.

NO

which is then forcibly

YES

Output module hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 10 11 - 10

NO (Flickering) · turned on?

Page 127 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 11 11 - 11
Page 127 · click to enlarge
Page 127

11.2.12 Flowchart for when output load of output module does not turn on

The following shows the flowchart to be followed when the output load of the output module does not turn on during PLC operation.

The output load does not turn on.

Is the operation indicator of output module

NO

Check output conditions with the monitor mode of the GX Developer.

YES

Is voltage for the power supply load

NO

Is the operation indicator of input module

Voltage measurement among the modules input and COM terminals.

YES

What is the voltage among the various output

Set the GX Developer in the monitor mode and check that the input signal is OFF.

COM terminals of the

Is it reaching the supply voltage value?

Output module failure Replace the output module.

Check the external wiring and external input devices.

Check the power supply load wire and recover the power supply.

Check the load wire and load, and recover the power supply.

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

Confirm rush current when the load is at the maximum simultaneous on.

NG

Change the output relay number and let the load maximum simultaneous on current to within the specification.

OK

POINT For the trouble that the input signal to the input module is not turned off, troubleshoot referring to Section 11.5 Examples of I/O Modules Troubleshooting.

11 - 11 11 - 11

Show 8 more labels / short text on this page
turned on? · Off · added? · turned on? · On · Supply voltage · output module? · (Monitor signal off)
Page 128 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 12 11 - 12
Page 128 · click to enlarge
Page 128

11.2.13 Flowchart for when unable to read a program

The following shows the flowchart to be followed when communication with GX Developer cannot be made during PLC power-on.

The CPU cannot communicate with the GX Developer.

NO

Is the memory to be

Select the correct memory.

YES NO YES

Can the CPU communicate

with the GX Developer?

Is the connection cable

NO

Connect the connection cable properly.

YES NO YES

Can the CPU communicate

with the GX Developer?

Can the CPU communicate with the GX Developer by replacing the

YES

NO

USB Is the connection type RS-232?

Is the USB driver installed in the personal

NO Install the USB driver into the personal computer.

RS-232 YES

NO

Can the CPU communicate

YES

with the GX Developer?

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

YES Can the CPU communicate with GX Developer by

lowering the baud rate?

NO

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 12 11 - 12

Show 5 more labels / short text on this page
read correct? · connected properly? · connection cable? · computer? · Completion
Page 129 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 13 11 - 13
Page 129 · click to enlarge
Page 129

11.2.14 Flowchart for when unable to write a program

The following shows the flowchart to be followed when programs cannot be written in the CPU module.

Unable to write a program

Is the DIP switch SW1 set to OFF?

ON

Turn the DIP switch SW1 (system protect) to OFF.

OFF NO YES

Is it able to write a program?

Cancel the password using the GX Developer.

YES

Is the password registered?

NO

NO YES

Is it able to write a program?

Perform the following. Confirm whether the write-protect switch is off or not. Confirm if it is formatted. Confirm the writing destination specification.

Is the memory program

Perform the following. Organize file. Confirm memory space. Confirm the writing destination specification.

Is it able to write a program?

YES

NO

YES

Is it able to write a program?

NO

2. 3)

11 - 13 11 - 13

Show 6 more labels / short text on this page
Memory · card · memory? · Program memory · 1) · 3)
Page 130 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 14 11 - 14
Page 130 · click to enlarge
Page 130
2. 3)

Format program memory.

YES

3. Is it able to write a program?

NO

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 14 11 - 14

1) · Completion

Page 131 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 15 11 - 15
Page 131 · click to enlarge
Page 131

11.2.15 Flowchart for when it is unable to perform boot operation from memory card

The following shows the flowchart that must be followed when the boot operation of the CPU module cannot be performed using the memory card.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — 11.2.15 Flowchart for when it is unable to perform boot operation from memory card diagram (page 131)
Fig. 78 · 11.2.15 Flowchart for when it is unable to perform b…

Is there CPU module error? Remove the cause of the error.

Is the drive that stores the parameter file specified?

Set the DIP switch 2 and 3 to the drive in which the parameter file is stored.

Set a file to boot file setup. Is a file set with parameter

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 15 11 - 15

Page 132 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 16 11 - 16
Page 132 · click to enlarge
Page 132

11.2.16 Flowchart for when UNIT VERIFY ERR. occurs

The following shows the flowchart to be followed when UNIT VERIFY ERR. occurs at PLC power-on or during operation.

UNIT. VERIFY ERR. occurs.

Check the slot where error occurred with the GX Developer.

Is the module of the applicable slot installed

NO

Install the module properly.

YES

NO YES

Is the "ERR." LED

Are all the extension cables of the base module connected

NO

Install the extension cable properly.

YES

NO YES

Is the "ERR." LED

Replace the applicable module.

Replace the CPU module.

base unit.

Hardware fault Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 16 11 - 16

Show 12 more labels / short text on this page
properly? · turned off? · properly? · turned off? · Proper operation · Error detection · Proper operation · Error detection · Proper operation · Replace the applicable · Error detection · Completion
Page 133 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 17 11 - 17
Page 133 · click to enlarge
Page 133

11.2.17 Flowchart for when CONTROL BUS ERR. occurs

The following shows the flowchart to be followed when CONTROL BUS ERR. occurs at PLC power-on or during operation. This flow chart can be confirmed only when a specific slot/base unit can be detected by the error code.

CONTROL BUS ERR. occurs.

Check the slot base unit where error occurred with the GX Developer.

Is the module of the applicable slot installed properly?

NO

Install the module and cable properly.

Is the extension cable of the

YES NO YES

Is the "ERR." LED

Are all the extension cables of the base unit

NO

Install the extension cable properly.

YES

NO YES

Is the "ERR." LED

Replace the applicable module.

Replace the CPU module.

base unit.

Hardware fault Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

11 - 17 11 - 17

Show 13 more labels / short text on this page
applicable base unit · installed properly? · turned off? · connected properly? · turned off? · Proper operation · Error detection · Proper operation · Error detection · Replace the applicable · Proper operation · Error detection · Completion
Page 134 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 18 11 - 18
Page 134 · click to enlarge
Page 134

11.3 Error Code List

If a fault occurs when the PLC power supply is switched on, when the CPU is switched from STOP to RUN or during RUN, the High Performance model QCPU displays an error (on the LED) using the self-diagnostic function and stores the error information into the special relays SM and special registers SD.

REMARK

For the error code (4000H to 4FFFH) developed upon a request for general data processing from the GX Developer, intelligent function module or network system, refer to Appendix 1. 11.3.1 Procedure for reading error codes

When an error occurs, the error code and error message can be read by the GX Developer Version 4 or later. The procedure for reading error codes by the GX Developer is as follows.

1) Start the GX Developer. 2) Connect the CPU module to the personal computer. 3) Select [Online] - [Read from PLC] Menu by the GX Developer, and also read the project from the High Performance model QCPU. 4) Select the [Diagnostics] - [Diagnostics PLC] Menu. 5) Click the "Error Jump" button in the PLC diagnostics dialog box to display the error code and error message. 6) Select the [Help] - [PLC error] Menu, and confirm the content of the applicable error code. For details of the GX Developer operating method, refer to the applicable the GX Developer Operating Manual.

11 - 18 11 - 18

Page 135 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 19 11 - 19
Page 135 · click to enlarge
Page 135

11.3.2 Error Code List

The following information deals with error codes and the meanings, causes, and corrective measures of error messages. " " in the Corresponding CPU column indicates that the error is applied to all types of CPU modules. "Rem" indicates compatibility with the remote I/O module. A CPU type name in the column indicates that the error is applied only to the specific CPU module type.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — 11.3.2 Error Code List diagram (page 135)
Fig. 79 · 11.3.2 Error Code List

1000 Off Flicker/On Stop Always 1001 1002 1003 1004

MAIN CPU DOWN ——— ——— Off Flicker Stop Always

1012 END NOT EXECUTE ——— ——— Off Flicker Stop When an END instruction is executed.

RAM ERROR ——— ——— Off Flicker Stop At power ON/At reset

1300 FUSE BREAK OFF Unit/moule No. ——— Off/ON Flicker/On

1310 I/O INT ERROR Unit/module No. ——— Off Flicker Stop During interrupt

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU MODULE operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

11 - 19 11 - 19

Page 136 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 20 11 - 20
Page 136 · click to enlarge
Page 136

(SD0) 1 Error Contents and Cause Corrective Action

QCPU

Run mode suspended or failure of main CPU module (1) Malfunctioning due to noise or other reason (2) Hardware fault

(1) Measure noise level. (2) Reset and establish the RUN status again.

1005 QCPU

If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.

Rem 1006 1007 1008

QCPU

1009 Failure of the power supply module, CPU module, main base unit, extension base unit or extension cable is detected.

Entire program was executed without the execution of an END instruction. (1) When the END instruction is executed it is read as another

(1) Measure noise level. (2) Reset and establish the RUN status again.

If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.

instruction code, e.g. due to noise. (2) The END instruction has been changed to another instruction

code somehow.

1101 Error in internal RAM/program memory where CPU module sequence program is stored. 1102 Error in RAM used as CPU module work area. 1103 Internal CPU module device error. 1104 RAM Address error in CPU module.

This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.

(1) Measure noise level. (2) Reset and establish the RUN status again.

1105 CPU shared memory fault

If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.

Ver. B or later

1200 The circuit that performs CPU internal index modification is not operating properly. 1201 Internal CPU module hardware (logic) does not operate normally. 1202 The circuit that executes sequence processing in the CPU module does not operate properly.

This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.

1203 The operation circuit that conducts index modification in the CPU module is not operating properly. 1204 The hardware (logic) in the CPU us not operating properly. 1205 The operation circuit that conducts sequence processing in the CPU in not operating properly. 1206 The DSP operation circuit in the CPU is not operating properly.

This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. Q4AR

(1) Check ERR. LED of the output modules and replace the module

whose LED is lit. (2) Read the common error information with the peripheral device

and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1".

QCPU

There is an output module with a blown fuse.

(1) Check ERR. LED of the output modules and replace the fuse of

the module whose LED is lit. (2) Read the common error information with the peripheral device

There is an output module with a blown fuse.

and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1".

(1) Check ERR. LED of the output modules and replace the module

whose LED is lit. (2) Read the common error information with the peripheral device

and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1". (3) Check whether the external power supply for output load is ON

(1) There is an output module with a blown fuse. (2) External power supply for output load is turned off or

Q2AS

disconnected.

or OFF.

One of the individual modules is experiencing hardware problems, so check the modules. Contact your nearest Mitsubishi representative and explain the problem with the defective module.

1310 An interruption has occurred although there is no interrupt module.

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 20 11 - 20

Show 6 more labels / short text on this page
Error Code · Corres- ponding · 1010 1011 · QCPU function · Rem · QnA Q4AR
Page 137 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 21 11 - 21
Page 137 · click to enlarge
Page 137

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 RUN ERROR

LED Status Error Code

(SD0) 1 Error Messages

1401 SP. UNIT DOWN Unit/module No. ——— Off/On Flicker/On

At power ON/At reset/ When intelligent function module is accessed.

When an intelligent function module access instruction is executed.

3 At power ON/At reset

1402 Program error location

SP. UNIT DOWN Unit/module No.

During execution of FROM/TO instruction set.

When an END instruction is executed.

1411 At power ON/At reset

CONTROL-BUS ERR. Unit/module No. Program error location Off Flicker Stop

During execution of FROM/TO instruction set.

1413 CONTROL-BUS. ERR. ——— ——— off Flicker Stop Always

CONTROL-BUS. ERR. Unit/module No. ——— Off Flicker Stop When an END instruction is executed.

——— off Flicker Stop When an END instruction is executed

1415 Base No. When an END instruction is executed

CONTROL-BUS. ERR.

Unit/module No.

At power ON/At reset

1421 SYS. UNIT DOWN 3 ——— ——— off Flicker Stop Always

1500 AC DOWN ——— ——— On Off Continue Always

1510 DUAL DC DOWN 5V 4 ——— ——— on on Continue Always

1520 DC DOWN 5V 5 ——— ——— off Flicker Stop Always

1530 DC DOWN 24V 3 ——— ——— on on Continue Always

BATTERY ERROR Drive Name ———

BAT.ALM LED On

When an END instruction is executed.

2000 UNIT VERIFY ERR. Unit/module No. ——— Off/On Flicker/On

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.) 3 This can only be detected in redundant systems. Detection is possible in either the control system or the standby system. 4 This can only be detected in the redundant system control system. 5 This can be detected in either a standalone system or a redundant system. However, in a redundant system it can only be detected in the control system. 6 Stop/continue operation is selectable for each module by setting parameters.

11 - 21 11 - 21

Show 9 more labels / short text on this page
Operating Statuses of · Diagnostic Timing · Stop/ Continue · Stop/ Continue · Off/On Flicker/On · Off Flicker Stop · 1600 ON On · Continue Always · Stop/ Continue
Page 138 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 22 11 - 22
Page 138 · click to enlarge
Page 138

(SD0) 1 Error Contents and Cause Corrective Action

  • CPU
  • There was no response from the intelligent function module during initial communication stage.
  • The size of the buffer memory of the intelligent function module is wrong.

The CPU module is experiencing hardware problems. Contact your nearest Mitsubishi representative.

QCPU

1401 When parameter I/O allocation was being made, there was no return signal from the special function module during initial processing stage. When error is generated, the initial I/O number of the special function module that corresponds to the common information is stored.

The special function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative.

The intelligent function module was accessed in the program, but there was no response.

This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative.

QCPU

1402 The special function module was accessed during the execution of a FROM/TO instruction set, but there was no response. When an error is generated, the program error location corresponding to the individual information is stored.

The special function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative.

  • 1403
  • There was no response from the intelligent function module when the END instruction is executed.
  • An error is detected at the intelligent function module.

The intelligent function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative.

QCPU

When performing a parameter I/O allocation a special function module could not be accessed during initial communications. On error occurring, the head I/O number of the corresponding special function module is stored in the common information.

A special function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.

The FROM/TO instruction set could not be executed, due to a system bus error with a special function module. On error occurring, the program error location is stored in the individual information.

(1) Change the High Performance model QCPU of function version

A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is

The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.

experiencing problems. Contact your nearest Mitsubishi representative.

Ver. B or later

An error is detected on the system bus. • Wait-length time-out, arbitration time-out.

An intelligent function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.

QCPU

(1) Change the High Performance model QCPU of function version

Fault of the loaded module was detected. The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.

A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is

Ver. B or later

experiencing problems. Contact your nearest Mitsubishi representative.

An intelligent function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.

QCPU

An error is detected on the system bus.

1415 Fault of the main or extension base unit was detected.

An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative.

Ver. B or later 1421 Hardware fault at the system management module AS92R. This is experiencing hardware problems. Contact your nearest Mitsubishi representative. Q4AR

1416 System bus fault was detected at PLC power-on or CPU module reset.

1500 A momentary power supply interruption has occurred. The power supply went off. Check the power supply. Rem

1510 The 5 VDC supplied to one of the two power-supply modules in the redundant system extension base unit has dropped below 85% of the rated voltage. 1520 The 5 VDC supplied to the power-supply modules in the extension base unit has dropped below 80% of the rated voltage.

Check the supply voltage of the power supply module. If the voltage is abnormal then replace the power supply module.

Q4AR

1530 The 24 VDC power supplied to the system management module AS92R has dropped below 85% of the rated voltage. Check the power supply.

(1) Change the battery. (2) If the battery is for program memory, standard RAM or for the

1600 (1) Voltage in the CPU module battery. (2) The CPU module battery is not connected.

back-up power function, install a lead connector.

1601 Voltage of the battery on memory card 1 has dropped below stipulated level. Change the battery.

1602 Voltage of the battery on memory card 2 has dropped below stipulated level. Change the battery. QnA

Read the error common information at the peripheral device, and check and/or change the module that corresponds to the numerical value (module number) there. Alternatively, monitor the special registers SD1400 to SD1431 at a peripheral device, and change the fuse at the output module whose bit has a value of "1".

I/O module information power ON is changed. I/O module (or special function module) not installed properly or installed on the base unit.

The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.

Change the High Performance model QCPU of function version A for the High Performance model QCPU of function version B.

Ver. B or later

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 22 11 - 22

Show 15 more labels / short text on this page
Error Code · Corres- ponding · Rem · QnA · Rem · QnA · Rem · Rem · QCPU function · Rem · QCPU function · Rem · QCPU function · Rem · QCPU function
Page 139 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 23 11 - 23
Page 139 · click to enlarge
Page 139

Error Code List (Continued)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Error Code List (Continued) diagram (page 139)
Fig. 80 · Error Code List (Continued)

SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset

SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset

2106 SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset

SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 6 This can only be detected in the redundant system standby system.

11 - 23 11 - 23

Page 140 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 24 11 - 24
Page 140 · click to enlarge
Page 140

(SD0) 1 Error Contents and Cause Corrective Action

Slot loaded with the QI60 is set to other than the Inteli (intelligent function module) or Interrupt (interrupt module) in the parameter I/O assignment.

Make setting again to match the parameter I/O assignment with the actual loading status.

Ver. B or later

(1) In the parameter I/O allocation settings, an Inteli (intelligent

function module) was allocated to a location reserved for an I/O module or vice versa. (2) In the parameter I/O allocation settings, a module other than

(1) Reset the parameter I/O allocation setting to conform to the

actual status of the intelligent function module and the CPU module. (2) Delete the general-purpose switch settings.

QCPU

CPU (or nothing) was allocated to a location reserved for a CPU module or vice versa. (3) A general-purpose switch was set to the module with no

general-purpose switches.

In parameter I/O allocation settings, a special function module was allocated to a location reserved for an I/O module. Or, the opposite has happened.

Reset the parameter I/O allocation setting to conform with the actual status of the special function modules. QnA

Keep the number of A-series special function modules that can initiate an interrupt (except for the QI60, A1SI61) to 12 or fewer. QCPU

13 or more A-series special function modules (except for the QI60, A1SI61) that can initiate an interrupt to the CPU module have been installed.

2101 13 or more special function modules (not counting the AI61) capable of sending an interrupt to the CPU module have been installed.

Keep the number of special function modules that can initiate an interrupt (with the exception of the AI61 module) to 12 or fewer. QnA

7 or more A1SD51S have been installed. Keep the number of A1SD51S to 6 or fewer. QCPU

2102 7 or more computer link modules (excludes A (1S) J71QC24) have been installed.

Keep the number of computer link modules (excludes A (1S) J71QU24) installed to 6 or fewer.

(1) Reduce the number of QI60/A1SI61 modules loaded in the

single-PLC system to one. (2) Change the number of QI60/A1SI61 modules set to the same

(1) Two or more QI60/A1SI61 modules are loaded in a single-PLC

system. (2) Two or more QI60/A1SI61 modules are set to the same control

control PLC to only one in the multiple CPU system. (3) Reduce the number of A1SI61 modules to only one in the

PLC in a multiple CPU system. (3) Two or more A1SI61 modules are loaded in a multiple CPU

Ver. B or later

multiple CPU system. When using an interrupt module with each QCPU in a multiple CPU system, change it for the QI60. (Use one A1SI61 module + max. three QI60 modules or only the QI60 modules.)

system.

Two or more QI60, A1SI61 interrupt modules have been installed. Install only 1 QI60, A(1S)I61 module. QCPU The QI60 is loaded. Remove the QI60. Rem

Two or more AIS61 interrupt modules have been installed. Install only 1 AI61 module. QnA

2104 At the MELSECNET/MINI auto refresh parameter settings, the module allocation that was set is different from the actual module models at the station numbers in the link system.

Reset the parameter MELSECNET/MINI auto refresh unit module allocation setting so that it conforms to the station number of the module that is actually linked.

There are too many special function modules that can use dedicated instructions allocated (number of modules installed). (The total of the figures indicated below is above 1344.) (Number of AD59 modules installed × 5) (Number of AD57 (S1)/AD58 modules installed × 8) (Number of AJ71C24 (S3/S6/S8) modules installed × 10) (Number of AJ71UC24 modules installed × 10) (Number of AJ71C21 (S1) modules installed × 29) (Number of AJ71PT32-S3/AJ71T32-S3 modules installed × 125) (Number of AJ71QC24 (R2, R4) modules installed × 29) (Number of AJ71ID1 (2)-R4 modules installed × 18) (Number of AD75 modules installed × 12) Total > 1344

Reduce the number of special function modules installed.

: When the expansion mode is used. QnA

  • Five or more MELSECNET/H modules are loaded in a whole multiple CPU system.
  • Five or more Q series Ethernet interface modules are loaded in a whole multiple CPU system.

Reduce the number of modules to four or less in the whole multiple CPU system.

Ver. B or later (1) 5 or more MELSECNET/H modules have been installed. (2) 5 or more Q series Ethernet interface modules have been

(1) Keep the number to 4 or fewer. (2) Keep the number to 4 or fewer. (3) Check the network numbers and station numbers.

installed. (3) Identical network numbers or station numbers exist in the

QCPU

2106 (1) 5 or more AJ71QLP21 & AJ71QBR11 modules are installed. (2) 3 or more AJ71AP21/R21 & AJ71AT21B modules are installed. (3) The total number of installed AJ71QLP21, AJ71QBR11,

MELSECNET/10 network system.

(1) Install 4 or fewer modules. (2) Install 2 or fewer modules. (3) Reduce the total number of modulees to 4 or less. (4) Check the network Nos. and station Nos. (5) Check the station Nos.

AJ71AP21/R21, and AJ71AT21B modules exceeds 5. (4) Identical network Nos. or identical station Nos. exist at the

MELSECNET/10 network system. (5) 2 or more master or load stations exist simultaneously at the

MELSECNET(II) or MELSECNET/B data link system.

2107 Head X/Y set in the parameter I/O allocation settings is also the head X/Y for another module.

Reset the parameter I/O allocation setting to conform with the actual status of the special function modules.

(1) Network module A1SJ71LP21, A1SJ71BR11, A1SJ71AP21 , A1SJ71AR21, or A1SJ71AT2B dedicated for the A2USCPU has been installed. (2) Network module A1SJ71QLP21 or A1SJ71QBR11 dedicated for

Change network module to QJ71LP21 or QJ71BR11. QCPU

the Q2AS has been installed.

A(1s)J71LP21 or A(1s)J71BR11 for use with the AnUCPU network module has been installed. Change network module to A(1s)J71QLP21 or A(1s)J71QBR11. QnA

2109 6 The control system and standby system module configurations are different when a redundant system is in the backup mode. Check the module configuration of the standby system. Q4AR

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 6 This can only be detected in the redundant system standby system.

11 - 24 11 - 24

Show 11 more labels / short text on this page
Corres- ponding · Error Code · QCPU function · Rem · QnA Rem · QCPU function · QnA · QCPU function · Rem · QnA · Rem
Page 141 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 25 11 - 25
Page 141 · click to enlarge
Page 141

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 RUN ERROR

LED Status Error Code

(SD0) 1 Error Messages

SP. UNIT ERROR Unit/module No. Program error location Off/On Flicker/On

2 When instruction executed.

2112 Unit/module No.

SP. UNIT ERROR

Program error location Off/On Flicker/On

When instruction executed/ STOP RUN

SP. UNIT ERROR Unit/module No. Program error location Flicker/On Flicker/On Continue/

Stop When instruction is executed

SP. UNIT LAY ERR. ——— ——— Off Flicker Stop At power ON/At reset

2126 SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset

2150 SP. UNIT VER. ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset

2200 MISSING PARA. Drive Name ——— Off Flicker Stop At power ON/At reset

2210 BOOT ERROR Drive Name ——— Off Flicker Stop At power ON/At reset

ICM. OPE. ERROR Drive Name ——— Off/On Flicker/On

When memory card is inserted or removed

2400 FILE SET ERROR File name Parameter number Off Flicker Stop At power ON/At reset

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

11 - 25 11 - 25

Show 7 more labels / short text on this page
Operating Statuses of · Diagnostic Timing · Stop/ Continue · Stop/ Continue · FFFFH (fixed) · 2121 2122 · Stop/ Continue
Page 142 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 26 11 - 26
Page 142 · click to enlarge
Page 142

(SD0) 1 Error Contents and Cause Corrective Action

Station not loaded was specified using the instruction whose target was the PLC share memory.

Read the individual information of the error, check the program corresponding that value (program error location), and make correction.

Ver. B or later 2110 (1) The location designated by the FROM/TO instruction set is not a

(1) Read error individual information, then check and edit the

special function module. (2) The special function module, Network module being accessed is

FROM/TO instruction set that corresponds to the numerical value there (Program error location). (2) The special function module that is being accessed has a

faulty. 2111 The location designated by a link direct device (J \ ) is not a network module.

hardware error. Consult the nearest service center, agent or our branch office and describe the symptom.

(1) The location designated by a special function module dedicated

instruction is not a special function module. (2) The network number specified by the network dedicated

Read error individual information, then check and edit the special function module (Network module) dedicated instruction that corresponds to the numerical value there (program error location).

instruction does not exist, or the network module is not the corresponding one. (3) Alternatively, it is not the relevant special function module.

2113 The one specified in the network-dedicated instruction is not a network module, or a relay target network does not exist.

2114 An instruction, which on execution specifies other stations, has been used for specifying the host station. (An instruction that does not allow the host station to be specified).

2115 An instruction, which on execution specifies the host station, has been used for specifying other stations. (An instruction that does not allow other stations to be specified).

Read the individual information of the error, check the program corresponding that value (program error location), and make correction.

  • An instruction that does not allow the module under the control of another station to be specified is being used for a similar task.
  • Instruction was executed for the A or QnA module under control of another station. 2117 A CPU module that cannot be specified in the instruction dedicated to the multiple CPU system was specified.

Ver. B or later

2120 The location of Q B and QA1S B is improper. Check the location of the base unit. 2121 The CPU module is installed at other than the CPU slot or slots 0 to 2. Check the loading position of the CPU module and reinstall it at the correct slot. 2122 QA1S B is used to the main base unit. Use Q3 B as the main base unit.

(1) Remove the module installed at 65th or later slot. (2) Remove the module installed at the slot later than the number of

(1) A module is installed at 65th or higher slot. (2) A module is installed at the slot later than the number of slots

QCPU

specified with base allocation setting. (3) A module is installed at the I/O points later than the 4,096th

slots specified with base allocation setting. (3) Remove the module installed at the I/O points later than the

4,096th point. (4) Change the last module to a module which does not exceed the

point. (4) A module installed at the 4,096th point occupies higher points.

4,096th point.

2125 (1) A module which the QCPU cannot recognise has been installed. (2) There was no response form the intelligent function module.

(1) Install a module which can be used with the CPU. (2) The intelligent function module is experiencing hardware

problems. Contact your nearest Mitsubishi representative.

CPU module locations in a multiple CPU system are either of the following. (1) There are empty slots between the QCPU and QCPU/motion

(1) Eliminate empty slots between the CPU modules. (Set empty

slots on the right side of the CPU modules.) (2) Remove the modules, which are not the QCPU modules, loaded

between the QCPU modules, and fit the slots with the QCPUs. Load the motion controller modules on the right side of the QCPUs.

controller. (2) Modules other than the QCPU (including the motion controller)

modules are loaded between the QCPU modules.

Ver. B or later

(1) Change the intelligent function module for the one compatible

2150 In a multiple CPU system, the control PLC of the intelligent function module incompatible with the multiple CPU system is set to other than station 1.

with the multiple CPU system (function version B). (2) Change the setting of the control CPU of the intelligent function

module incompatible with the multiple CPU system to station 1.

Check and correct the setting of the parameter enabled drive switch. Put a parameter file in the drive designated by the parameter enabled drive switch.

2200 There is no parameter file at the drive designated by DIP switches as a valid drive.

The contents of the boot file are incorrect. Check the boot setting. QCPU

Check and correct the setting of the parameter enabled drive switch. Put a boot file in the drive designated by the parameter enabled drive switch.

2210 There is no boot file in the drive designated by the parameter enabled drive switch even though the Boot DIP switch is ON.

(1) A memory card was removed without switching the memory

card in/out switch OFF. (2) The memory card in/out switch is turned ON although a memory

(1) Remove memory card after placing the memory card in/out

switch OFF. (2) Turn on the card insert switch after inserting a memory card.

card is not actually installed.

2301 (1) The memory card has not been formatted. (2) Memory card format status is incorrect. 2302 A memory card that cannot be used with the CPU module has been installed.

(1) Format memory card. (2) Reformat memory card.

Check memory card.

(1) Execute automatic write to standard ROM on the CPU module

Automatic write to standard ROM was performed on the CPU module that is incompatible with automatic write to standard ROM. (Memory card where automatic write to standard ROM was selected in the boot file was fitted and the parameter enable drive was set to the memory card.)

which is compatible with automatic write to standard ROM. (2) Using GX Developer, perform write of parameters and programs

QCPU function Ver. B or later

to standard ROM. (3) Change the memory card for the one where automatic write to

standard ROM has not been set, and perform boot operation from the memory card.

Read the error individual information at the peripheral device, check to be sure that the parameter drive name and file name correspond to the numerical values there (parameter number), and correct. Create a file created using parameters, and load it to the CPU module.

The file designated at the PLC file settings in the parameters cannot be found.

The Ethernet parameter that was added for QnACPU, with the function version "B," has been set to QnACPU without the function version "B."

Change to QnACPU with the function version "B." Delete the Ethernet parameter. QnA

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 26 11 - 26

Show 8 more labels / short text on this page
Corres- ponding · Error Code · QCPU function · Rem · QCPU function · Rem · QCPU function · QnA
Page 143 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 27 11 - 27
Page 143 · click to enlarge
Page 143

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 RUN ERROR

LED Status Error Code

(SD0) 1 Error Messages

2401 FILE SET ERROR File name Parameter number Off Flicker Stop At power ON/At reset

FILE OPE. ERROR File name Program error location Off/On Flicker/ON

2 When instruction is executed

CAN'T EXE. PRG. File name ——— Off Flicker Stop At power ON/At reset

PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

PARAMETER ERROR File name/drive name Parameter number Off Flicker Stop When an END instruction is executed.

PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

3004 PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

3006 PARAMETER ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

PARAMETER ERROR File name/drive name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

11 - 27 11 - 27

Show 4 more labels / short text on this page
Operating Statuses of · Diagnostic Timing · Stop/ Continue · 2502 2503
Page 144 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 28 11 - 28
Page 144 · click to enlarge
Page 144

(SD0) 1 Error Contents and Cause Corrective Action

(1) Check and correct the parameters (boot setting). (2) Delete unnecessary files in the program memory. (3) Choose "Clear program memory" for boot in the parameter so

Program memory capacity was exceeded by performing boot operation or automatic write to standard ROM.

Ver. B or later 2401

that boot is started after the program memory is cleared.

Read the error individual information at the peripheral device, check to be sure that the parameter drive name and file name correspond to the numerical values there (parameter number), and correct. Check the space remaining in the memory card.

The file designated at the parameter PLC RAS settings fault history area has not been created.

Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Create a file created using parameters, and load it to the CPU module. 2411 The sequence program designated a file that cannot be designated by the sequence program (comment file, etc.). 2412 The SFC program file is one that cannot be designated by the sequence program.

2410 The file designated by the sequence program cannot be found.

Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct.

Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Check to ensure that the designated file has not been write protected.

2413 No data has been written to the file designated by the sequence program.

Read the error common information at the peripheral device, check to be sure that the parameter device allocation setting and the program file device allocation correspond to the numerical values there (file name), and correct if necessary. 2501 There are multiple program files although "none" has been set at the parameter program settings.

2500 There is a program file that uses a device that exceeds the device allocation range designated by the parameter device settings.

Edit the parameter program setting to "yes". Alternatively, delete unneeded programs.

2502 The program file is incorrect. Alternatively, the file contents are not those of a sequence program.

Check whether the program version is .QPG, and check the file contents to be sure they are for a sequence program. 2503 2504

There are no program files at all. Two or more SFC normal programs or control programs have been designated.

Check program configuration. Check parameters and program configuration.

In a multiple CPU system, the intelligent function module under control of another station is specified in the interrupt pointer setting of the parameter.

(1) Specify the first I/O number of the intelligent function module

under control of the host station. (2) Delete the interrupt pointer setting of the parameter.

Ver. B or later

3000 The parameter settings for timer time limit setting, the RUN-PAUSE contact, the common pointer number, the general data processing, number of vacant slots, or system interrupt settings are outside the range that can be used by the CPU module. 3001 Parameter contents have been destroyed.

(1) Read the error detailed information at the peripheral device,

check the parameter items corresponding to the numerical values (parameter numbers) there, and correct when necessary. (2) If the error is still generated following the correction of the

parameter settings, it is likely that there is a memory error, either in the internal CPU RAM/program memory or on the memory card. Contact your nearest Mitsubishi representative.

3002 When "use the following files" is selected for the file registers in the PLC file setting parameter, the specified file does not exist though the file register capacity has been set.

The automatic refresh range of the multiple CPU system exceeded the file register capacity.

Change the file register file for the one refresh-enabled in the whole range.

Ver. B or later

(1) Read the error detailed information at the peripheral device,

check the parameter items corresponding to the numerical values (parameter numbers) there, and correct when necessary. (2) If the error is still generated following the correction of the

The number of devices set at the parameter device settings exceeds the possible CPU module range.

parameter settings, it is likely that there is a memory error, either in the internal CPU RAM/program memory or on the memory card. Contact your nearest Mitsubishi representative. 3004 The parameter file is incorrect. Alternatively, the contents of the file are not parameters.

Check whether the parameter file version is .QPA, and check the file contents to be sure they are parameters.

(1) Delete the setting of the Q02CPU’s high speed interrupt

parameter. To use high speed interrupts, change the CPU module to one of the Q02H/Q06H/Q12H/Q25HCPU. (2) To use a multiple CPU system, delete the setting of the high-

(1) The high speed interrupt parameter is set in a Q02CPU. (2) The high speed parameter is set in a multiple CPU system. (3) The high speed interrupt parameter is set when a QA1S B or

QCPU

speed interrupt parameter. To use high speed interrupts, change the system to a single PLC system. (3) To use either the QA1S B or QA B, delete the setting of the

QA B is used. (4) No module is installed at the I/O address designated by the high

No. 04012 or later

speed interrupt parameter.

high speed interrupt parameter. To use high speed interrupts, do not use the QA1S B/QA B. (4) Re-examine the I/O address designated by the high speed

interrupt parameter.

Re-set the parameter I/O assignment to control them under one QCPU. (Change the parameters of all stations in the multiple CPU system.) 3010 The parameter-set number of CPU modules differs from the actual number in a multiple CPU system.

3009 A modules are set to control PLCs in a multiple CPU system.

Match (preset count of multiple PLC setting) - (CPU (empty) setting in I/O assignment) with the actual number of CPUs loaded. 3012 Multiple CPU setting or control PLC setting differs from that of the reference station in a multiple CPU system.

Match the multiple PLC setting or control CPU setting in the parameter with that of the reference station (station 1).

Multiple CPU automatic refresh setting is any of the followings in a multiple CPU system. (1) When a bit device is specified as a refresh device, a number

Ver. B or later

Check the following in the multiple CPU automatic refresh parameters and make correction. (1) When specifying the bit device, specify a multiple of 16 for the

other than a multiple of 16 is specified for the refresh-starting device. (2) The device specified is other than the one that may be specified. (3) The number of send points is an odd number.

refresh starting device. (2) Specify the device that may be specified for the refresh device. (3) Set the number of send points to an even number.

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 28 11 - 28

Show 8 more labels / short text on this page
Corres- ponding · Error Code · QCPU function · QCPU function · Rem · QCPU function · serial · QCPU function
Page 145 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 29 11 - 29
Page 145 · click to enlarge
Page 145

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 RUN ERROR

LED Status Error Code

(SD0) 1 Error Messages

3100 LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

LINK PARA. ERROR File name/drive name Parameter number Off Flicker Stop When an END instruction is executed.

LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

LINK PARA. ERROR File name/drive name Parameter number Off Flicker Stop When an END instruction is executed.

LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

3107 LINK PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

SFC PARA. ERROR File name Parameter number Off Flicker Stop STOP RUN

3300 SP. PARA. ERROR File name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 29 11 - 29

Operating Statuses of · Diagnostic Timing · 3200 3201

Page 146 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 30 11 - 30
Page 146 · click to enlarge
Page 146

(SD0) 1 Error Contents and Cause Corrective Action

(1) Delete the MELSECNET/H network parameter of the

In a multiple CPU system, the MELSECNET/H under control of another station is specified as the first I/O number in the network setting parameter of the MELSECNET/H.

MELSECNET/H under control of another station. (2) Change the setting to the first I/O number of the MELSECNET/H

under control of the host station. The network parameters of the MELSECNET/H operating in the ordinary station were rewritten to the control station, or the network parameters of the MELSECNET/H operating in the control station were rewritten to the ordinary station. (The network parameters are reflected on the module side by making a reset.)

Ver. B or later

Reset the CPU module.

(1) The number of actually installed modules is different from that

(1) Check the network parameters and the installation state. If

designated in the number of modules setting parameter of MELSECNET/H. (2) The head I/O number of actually installed modules is different

inconsistency is found, arrange consistency between network parameters and the installation state. If network parameters are changed, write the new network parameters to the CPU module. (2) Check the number of extension stages of the extension base unit. (3) Check the state of connection of the extension base unit and

from that designated in the network parameter of MELSECNET/H. (3) Some data in the parameter cannot be handled. (4) The station type of MELSECNET/H has been changed while the

QCPU

connector. If the display unit is connected to the main base unit or extension base unit, check the state of connection. (4) If the error persists after the above items (1) through (3) are

power is on. (RESET RUN is required to change the station type.)

checked, the hardware is faulty. Contact your nearest Mitsubishi representative and explain the symptom.

(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact

Network parameters have not been written although the QnACPU is the control station, or the master station.

your nearest Mitsubishi representative.

  • The link refresh range exceeded the file register capacity. Change the file register file for the one refresh-enabled in the whole range.
  • When the station number of the MELSECNET/H module is 0, the inter-PLC network parameter setting has been made.
  • When the station number of the MELSECNET/H module is other than 0, the remote master parameter setting has been made.

Correct the type or station number of the MELSECNET/H module in the parameter to meet the used system.

Ver. B or later

(1) Check the network parameters and the installation state. If

inconsistency is found, arrange consistency between network parameters and the installation state. If network parameters are changed, write the new network parameters to the CPU module. (2) Check the number of extension stages of the extension base unit. (3) Check the state of connection of the extension base unit and

3101 The network No. specified by a parameter is different from that of the actually mounted network. The head I/O No. specified by a parameter is different from that of the actually mounted I/O unit. The network class specified by a parameter is different from that of the actually mounted network. The network refresh parameter of the MELSECNET/10(H) is out of the specified area.

connector. If the display unit is connected to the main base unit or extension base unit, check the state of connection. (4) If the error persists after the above items (1) through (3) are

checked, the hardware is faulty. Contact your nearest Mitsubishi representative and explain the symptom.

3102 An error was discovered when the network parameter check was made at the network module.

(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact

your nearest Mitsubishi representative.

In a multiple CPU system, the Q series Ethernet interface module under control of another station is specified as the first I/O number of the Ethernet setting parameter.

(1) Delete the Ethernet setting parameter of the Q series Ethernet

interface module under control of another station. (2) Change the setting to the first I/O number of the Q series

Ver. B or later

Ethernet interface module under control of the host station.

  • Though the number of Ethernet module is set to one or more in the parameter, the actually mounted number of units is zero.
  • The head I/O number for the Ethernet module set parameter is different from that of the actually mounted module.

(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact

your nearest Mitsubishi representative.

AJ71QE71 does not exist in the position of I/O number set by the parameter. I/O number designation is overlapping. Numbers of the parameter and loaded AJ71QE71 are different. Ethernet (parameter + dedicated instruction) is set to more than 5.

(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact

your nearest Mitsubishi representative.

3104 Ethernet and MELSECNET/10 use the same network number. Network number, station number or group number set by the parameter is out of range. I/O number is out of range.

(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact

your nearest Mitsubishi representative.

(1) Delete the CC-Link setting parameter of the Q series CC-Link

In a multiple CPU system, the Q series CC-Link module under control of another station is specified as the first I/O number of the CC-Link setting parameter.

module under control of another station. (2) Change the setting to the first I/O number of the Q series CC-

Ver. B or later (1) Though the number of CC-Link module set in the network

Link module under control of the host station.

parameters is one or more, the actually mounted number of units is zero. (2) The head I/O number in the common parameters is different

(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact

from that of the actually mounted module. (3) The station class for the CC-Link module quantity set

your nearest Mitsubishi representative.

parameters is different from that of the actually mounted station.

The contents of the Ethernet parameter are incorrect. Write after correcting parameters. QnA

The CC-Link link refresh range exceeded the file register capacity. Change the file register file for the one refresh-enabled in the whole range.

Ver. B or later 3106

The network refresh parameter for CC-Link is out of range. Check the parameter setting. QCPU

3107 The contents of the CC-Link parameter are incorrect. Check the parameter setting. Rem 3200 The parameter contents are incorrect. 3201 The contents of the SFC block attribute information are incorrect. 3202 The number of step relays designated in the parameters is less than the number used by the program. 3203 The execution type set for an SFC program in the parameters is other than the scan execution type.

Write after correcting parameters.

3300 The first I/O number in the intelligent function module parameter set on GX Configurator differs from the actual I/O number. Check the parameter setting. QCPU

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 30 11 - 30

Show 14 more labels / short text on this page
Corres- ponding · Error Code · QCPU function · QnA · QCPU function · QCPU function · Rem · QnA · Rem · QCPU function · Rem · QCPU function · Rem · Rem
Page 147 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 31 11 - 31
Page 147 · click to enlarge
Page 147

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 RUN ERROR

LED Status Error Code

(SD0) 1 Error Messages

When an END instruction is executed.

SP. PARA. ERROR File name Parameter number Off Flicker Stop

STOP RUN

3303 SP. PARA. ERROR File name/drive name Parameter number Off Flicker Stop At power ON/Reset/ STOP RUN

REMOTE PASS. ERROR ——— ——— Off Flicker Stop At power ON/Reset/ STOP RUN

INSTRCT CODE ERR. Program error location ——— Off Flicker Stop At power ON/Reset/ STOP RUN

4010 MISSING END INS. Program error location ——— Off Flicker Stop

4021 CAN'T SET (P) Program error location ——— Off Flicker Stop

At power ON/Reset/ STOP RUN

4030 CAN'T SET (I) Program error location ——— Off Flicker Stop

4101 Program error location ———

Program Program error location

Program error location ———

OPERATION ERROR

When instruction is executed

Program Program error location

Program error location ———

4200 FOR NEXT ERROR Program error location ——— Off Flicker Stop When instruction is executed 4201 FOR NEXT ERROR Program error location ——— Off Flicker Stop When instruction is executed

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)

11 - 31 11 - 31

Show 10 more labels / short text on this page
Operating Statuses of · Diagnostic Timing · At power ON/Reset/ · Stop/ continue · Stop/ Continue · 4102 4103 · Stop/ continue · Off/On Flicker/On · Stop/ Continue · Stop/ continue
Page 148 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 32 11 - 32
Page 148 · click to enlarge
Page 148

(SD0) 1 Error Contents and Cause Corrective Action

The refresh setting of the intelligent function module exceeded the file register capacity.

Change the file register file for the one which allows refresh in the whole range.

Ver. B or later

The intelligent function module's refresh parameter setting is outside the available range. Check the parameter setting. QCPU

Rem 3302 The intelligent function module's refresh parameter are abnormal. Check the parameter setting. QCPU

(1) Delete the automatic refresh setting or similar parameter setting

of the intelligent function module under control of another station. (2) Change the setting to the automatic refresh setting or similar

3303 In a multiple CPU system, automatic refresh setting or similar parameter setting was made to the intelligent function module under control of another station.

parameter setting of the intelligent function module under control of the host station. 3400 The first I/O number of the target module in the remote password file is set to other than 0H to 0FF0H.

  • Change the first I/O number of the target module to within the 0 H to 0FF0 H range. Position specified as the first I/O number of the remote password file is incorrect due to one of the following reasons:
  • Module is not loaded.
  • Other than a Q-compatible intelligent function module (I/O, A, QnA module)
  • Intelligent function module other than QJ71C24(-R2) or Q series Ethernet interface module
  • QJ71C24(-R2) or Q series Ethernet interface module of function version A

Ver. B or later

Load the QJ71C24(-R2) or Q series Ethernet interface module of function version B in the position specified as the first I/O number of the remote password file.

(1) Change the setting to the QJ71C24(-R2) or Q series Ethernet

QJ71C24(-R2) or Q series Ethernet interface module of function version B under control of another station is specified in a multiple CPU system.

interface module of function version B under control of the host station. (2) Delete the remote password setting.

4000 The program contains an instruction code that cannot be decoded. An unusable instruction is included in the program.

4001 The program contains a dedicated instruction for SFC program although it is not an SFC program.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4002 The extension instruction designated by the program has an incorrect instruction name. 4003 The extension instruction designated by the program has an incorrect number of devices.

4004 The extension instruction designated by the program a device which cannot be used.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4010 There is no END (FEND) instruction in the program. 4020 The total number of internal file pointers used by the program exceeds the number of internal file pointers set in the parameters. 4021 The common pointer numbers used by individual files overlap.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4030 The allocation pointer numbers used by individual files are overlap.

4100 The instruction cannot process the contained data.

The designated device number for data processed by the instruction exceeds the usable range. Alternatively, the stored data or constants for the devices designated by the instruction exceeds the usable range.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

(1) Delete from the program the link direct device which specifies

In a multiple CPU system, the link direct device (J \G ) was specified for the network module under control of another station.

the network module under control of another station. (2) Using the link direct device, specify the network module under

Ver. B or later

control of the host station.

  • 4102 The network number and station number designated with a dedicated network instruction are not correct. The link direct device (J \W ) is not set correctly.
  • The module No./network No./character string count specified by the extension instruction is outside the setting range.
  • The character string (" ") specified by the extension instruction is unusable.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4103 The configuration of the PID dedicated instruction is incorrect.

Using the multiple CPU dedicated instruction completion bit, provide interlocks to prevent one CPU module from executing 32 or more multiple CPU dedicated instructions.

33 or more multiple CPU dedicated instructions were executed from one CPU module.

Ver. B or later

Numbers of execution to the CC-Link instruction are beyond 64. Set the numbers of execution to the CC-Link instruction to 64 or less. 4108 The CC-Link parameter is not set when the CC-Link instruction is executed.

Execute the CC-Link instruction after setting the CC-Link parameter.

QCPU

4109 With high speed interrupt setting execute PR/PRC,UDCNT1/2,PWM,SPD,PLOADP,PUNLOADP,PAWPP instruction.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

No. 04012 or later No NEXT instruction was executed following the execution of a FOR instruction.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4200 Alternatively, there are fewer NEXT instructions than FOR instructions.

A NEXT instruction was executed although no FOR instruction has been executed.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4201 Alternatively, there are more NEXT instructions than FOR instructions.

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 32 11 - 32

Show 10 more labels / short text on this page
Corres- ponding · Error Code · QCPU function · QCPU function · Rem · QCPU function · Rem · QCPU function · QnA · serial
Page 149 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 33 11 - 33
Page 149 · click to enlarge
Page 149

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 RUN ERROR

LED Status Error Code

(SD0) 1 Error Messages

4203 FOR NEXT ERROR Program error location ——— Off Flicker Stop When instruction is executed

CAN'T EXECUTE (P) Program error location ——— Off Flicker Stop When instruction is executed

CAN'T EXECUTE (I) Program error location ——— Off Flicker Stop When instruction is executed

4235 INST. FORMAT ERR. Program error location ——— Off Flicker Stop When instruction is executed

4300 4301 EXTEND INST. ERR. Program error location ——— Off/On Flicker/On

2 When instruction is executed

4400 SFCP. CODE ERROR Program error location ——— Off Flicker Stop STOP RUN

4410 4411 CAN'T SET (BL) Program error location ——— Off Flicker Stop STOP RUN

4422 CAN'T SET (S) Program error location ——— Off Flicker Stop STOP RUN

SFCP. FORMAT ERR. Program error location ——— Off Flicker Stop STOP RUN

4602 SFCP. OPE. ERROR Program error location ——— Off/On Flicker/On

2 When instruction is executed

4611 SFCP. EXE. ERROR Program error location ——— On On Continue STOP RUN

4621 BLOCK EXE. ERROR Program error location ——— Off Flicker Stop When instruction is executed

STEP EXE. ERROR Program error location ——— Off Flicker Stop When instruction is executed

WDT ERROR Time (value set) Time (value actually

measured) Off Flicker Stop Always

PRG. TIME OVER Time (value set) Time (value actually

measured) On On Continue Always

6000 PRG. VERIFY ERR. 5 File name ——— off Flicker Stop Always

6010 MODE VERIFY ERR. 5 ——— ——— on on Continue Always

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.) 5 Can only be detected in the standby system of a redundant system.

11 - 33 11 - 33

Show 11 more labels / short text on this page
Operating Statuses of · Diagnostic Timing · 4210 4211 · 4212 4213 · 4220 4221 · 4230 4231 · Stop/ continue · 4420 4421 · 4501 4502 · 4600 4601 · Stop/ Continue
Page 150 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 34 11 - 34
Page 150 · click to enlarge
Page 150

(SD0) 1 Error Contents and Cause Corrective Action

CPU 4202 More than 16 nesting levels are programmed. Keep nesting levels at 16 or under.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4203 A BREAK instruction was executed although no FOR instruction has been executed prior to that.

4210 The CALL instruction is executed, but there is no subroutine at the specified pointer. 4211 There was no RET instruction in the executed sub-routine program. 4212 The RET instruction was before the FEND instruction in the main program.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4213 More than 16 nesting levels are programmed. Keep nesting levels at 16 or under.

4220 Interrupt input was generated, but no corresponding interrupt pointer was found. 4221 There was no IRET instruction in the executed interrupt program. 4223 The IRET instruction was before the FEND instruction in the main program. 4230 The number of CHK and CHKEND instructions is not equal. 4231 The number of IX and IXEND instructions is not equal.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

The configuration of the check conditions for the CHK instruction is incorrect. Alternatively, a CHK instruction has been used in a low speed execution type program.

4300 The designation of a MELSECNET/MINI-S3 master module control instruction was wrong. 4301 The designation of an AD57/AD58 control instruction was wrong.

Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4400 No SFCP or SFCPEND instruction in SFC program. 4410 The block number designated by the SFC program exceeds the range. 4411 Block number designations overlap in SFC program. 4420 A step number designated in an SFC program exceeds 511.

Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4421 Total number of steps in all SFC programs exceed the range Reduce total number of steps to below the maximum.

Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4422 Step number designations overlap in SFC program.

4500 The numbers of BLOCK and BEND instructions in an SFC program are not equal.

4501 The configuration of the STEP to TRAN to TSET to SEND instructions in the SFC program is incorrect. 4502 There was no STEPI instruction in SFC program block.

Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4503 The step designated by the TSET instruction in the SFC program does not exist.

4504 The step designated by the TAND instruction in the SFC program does not exist.

4600 The SFC program contains data that cannot be processed. 4601 Exceeds device range that can be designated by the SFC program. 4602 The START instruction in an SFC program is proceeded by an END instruction.

Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. The program is automatically subjected to an initial start. 4610 The active step information at presumptive start of an SFC program is incorrect. 4611 Key-switch was reset during RUN when presumptive start was designated for SFC program. 4620 Startup was executed at a block in the SFC program that was already started up. 4621 Startup was attempted at a block that does not exist in the SFC program.

Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem.

4630 Startup was executed at a block in the SFC program that was already started up. 4631 Startup was attempted at a block that does not exist in an SFC program. 4632 There were too many simultaneous active steps in blocks that can be designated by the SFC program. 4633 There were too many simultaneous active steps in all blocks that can be designated.

5000 Program scan time for initial execution type programs exceeds the initial execution WDT time setting designated in the PLC RAS parameter. 5001 The program scan time goes over the WDT value set in the parameter PLC RAS parameter.

Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary.

(1) The scan time of the program exceeded the constant scan

(1) Review the constant scan setting time. (2) Review the constant scan time and low speed program

setting time specified in the PC RAS setting parameter. (2) The low speed program execution time specified in the PC RAS

execution time in the parameter so that the margin time of constant scan may be fully reserved.

setting parameter exceeded the margin time of constant scan.

5011 Low speed scan type program scan time goes over the low speed execution WDT set in the parameter PC RAS settings.

Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary.

6000 The control system and standby system in the redundant system do not have the same programs and parameters.

Synchronise the programs and parameters of the control system and standby system. 6010 The operational status of the control system and standby system in the redundant system is not the same.

Q4AR

Synchronise the operation statuses of the control system and standby system.

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 34 11 - 34

Corres- ponding · Error Code · QnA

Page 151 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 35 11 - 35
Page 151 · click to enlarge
Page 151

Error Code List (Continued)

Common Information (SD5 to 15) 1

Individual Information (SD16 to 26) 1 LED Status

(SD0) 1 Error Messages

6100 At power on/ Reset/STOP RUN

TRK. MEMORY ERR. 3 ——— ——— on on Continue

When END instruction executed

6200 CONTROL EXE. 4 Cause of switch ——— on off Continue Always

6210 CONTROL WAIT. 5 Cause of switch ——— on off Continue Always

CAN'T EXE CHANGE

4 Cause of switch ——— on on Continue Always

MULT CPU DOWN Unit/module No. ——— Off Flicker Stop

7010 MULTI EXE. ERROR Unit/module No. ——— Off Flicker Stop At power ON/Reset

On Off 9000 F∗∗∗∗ 6 Program error location Annunciator number

7020 MULTI CPU ERROR Unit/module No. ——— On On Continue Always

Continue When instruction is executed

On Off 9010 ERR ∗∗∗-∗∗∗ 7 Program error location Failure No.

Continue When instruction is executed

9020 BOOT OK ——— ——— Off Flicker Stop At power ON/Reset

10000 CONT. UNIT ERROR ———

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored. 3 Can only be detected in a redundant system. Can be detected either in the control system or the standby system. 4 Can only be detected in the control system of a redundant system. 5 Can only be detected in the standby system of a redundant system. 6 ∗∗∗∗ indicates detected annunciator number. 7 ∗∗∗ indicates detected contact and coil number.

11 - 35 11 - 35

Show 7 more labels / short text on this page
Error Code · Operating Statuses of · Diagnostic Timing · 7000 Always · At power ON/Reset · USER LED On · USER LED On
Page 152 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 36 11 - 36
Page 152 · click to enlarge
Page 152

(SD0) 1 Error Contents and Cause Corrective Action

Because this is a CPU module hardware error, contact your nearest Mitsubishi representative. To replace the module, replace the standby system CPU first, then the control system CPU. 6101 The CPU module detected an error during the handshake for tracking. Check the condition of the other stations.

6100 A CPU module tracking memory error was detected during initial.

Q4AR

6200 The standby system in a redundant system is switched to the control system. Check the control system condition.

6210 The control system in a redundant system is switched to the standby system. Check the control system condition.

Q4AR

6220 The standby system in a redundant system could not be switched from the control system to the standby system because of an error status or other reason.

Check the standby system condition.

6221 Switching is disabled because of a bus switching module error. Because this is a bus switching module hardware error, contact your nearest Mitsubishi representative. 6222 Switching is disabled because a multiplexed master station of a remote I/O network was installed in the standby station during initial. Check the remote I/O network setting.

(1) In a multiple CPU system, at CPU module fault occurred at a

(1) Read the error individual information at a peripheral device,

station where "all station stop by stop error of PLC " was selected in the operating mode. (2) High Performance model QCPU of function version A was

check the error of the PLC resulting in CPU module fault, and remove the error. (2) Remove the High Performance model QCPU of function version

A from the main base unit.

loaded in a multiple CPU system.

Read the error individual information at a peripheral device, check the error of the CPU module resulting in CPU module fault, and remove the error.

In a multiple CPU system, station 1 resulted in stop error at power- on and the other stations cannot start. (This error occurred at stations 2 to 4)

(1) There is no response from the target station in a multiple CPU

(1) Reset the High Performance model QCPU and run it again. If

Ver. B or later

the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative. (2) Remove the High Performance model QCPU of function version

system at initial communication stage. (2) High Performance model QCPU of function version A was

A from the main base unit.

loaded in a multiple CPU system configuration.

7003 There is no response from the target station in a multiple CPU system at initial communication stage.

Reset the High Performance model QCPU and run it again. If the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative.

(1) Faulty CPU is loaded in a multiple CPU system. (2) High Performance model QCPU of function version A is loaded

(1) Read the error individual information at a peripheral device, and

in a multiple CPU system configuration. (An error is detected at the High Performance model QCPU of function version B.) (3) In a multiple CPU system, any of stations 2 to 4 was reset during

change the faulty station. (2) Change the station of function version A for function version B. (3) Do not reset the CPU modules of PLC No.2 to 4. Reset the High

Performance model QCPU of PLC No.1 and restart the multiple CPU system.

power-on. (This error occurs at only the station which was reset.)

Ver. B or later

In a multiple CPU system, a PLC fault occurred at a station where "all station stop by stop error of PLC" was not selected in the operation mode. (The error is detected at the High Performance model QCPU of other than the station where the CPU module fault occurred.)

Read the error individual information at a peripheral device, check the error of the CPU module resulting in CPU module fault, and remove the error.

Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (annunciator number).

9000 Annunciator F was set ON

Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (error number) there.

9010 Error detected by the CHK instruction.

9020 Storage of data onto ROM was completed normally in automatic write to standard ROM. (BOOT LED also flickers.)

Set the parameter enable drive to standard ROM, switch power on again, and perform boot operation from standard ROM.

Ver. B or later

10000 In the multiple CPU system, an error occurred in the CPU module other than the Process CPU/High Performance model QCPU.

Use the software package of the corresponding CPU module to check the details of the error that occurred.

Ver. B or later

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 36 11 - 36

Show 6 more labels / short text on this page
Error Code · Corres- ponding · QCPU function · QCPU function · QCPU function · QCPU function
Page 153 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 37 11 - 37
Page 153 · click to enlarge
Page 153

11.4 Canceling of Errors

The High Performance model QCPU can perform the cancel operation for errors only when the errors allow the CPU module to continue its operation. To cancel the errors, follow the steps shown below. 1) Eliminate the cause of the error. 2) Store the error code to be canceled in the special register SD50. 3) Energize the special relay SM50 (OFF ON). 4) The error to be canceled is canceled. After the CPU module is reset by the canceling of the error, the special relays, special registers, and LEDs associated with the error are returned to the status under which the error occurred. If the same error occurs again after the cancellation of the error, it will be registered again in the error history. When multiple enunciators(F) detected are canceled, the first one with No. F only is canceled.

POINT (1) When the error is canceled with the error code to be canceled stored in the

SD50, the lower one digit of the code is neglected. (Example) If error codes 2100 and 2101 occur, and error code 2100 to cancel error code 2101. If error codes 2100 and 2111 occur, error code 2111 is not canceled even if error code 2100 is canceled.

(2) Errors developed due to trouble in other than the CPU module are not canceled

even if the special relay (SM50) and special register (SD50) are used to cancel the error. (Example) The cause of "SP. UNIT DOWN" error cannot be removed even by using the special relay (SM50) and special register (SD50), because the error is developed on the Q bus. Refer to the error code list in Section 11.3.2 to remove the cause of the error.

11 - 37 11 - 37

Page 154 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 38 11 - 38
Page 154 · click to enlarge
Page 154

11.5 I/O Module Troubleshooting

This chapter explains possible problems with I/O circuits and their corrective actions. 11.5.1 Input circuit troubleshooting

This section describes possible problems with input circuits and their corrective actions.

Input Circuit Problems and Corrective Actions

Condition Cause Corrective Action

  • Leakage current of input switch (e.g. drive by non-contact switch).
  • Connect an appropriate resistor which will make the voltage across the terminals of the input module lower than the OFF voltage value.

Example 1

Input signal does not turn OFF.

Leakage current Input module

It is recommended to use 0.1 to 47 F + 47 to 120 (1/2W) for the CR constant.

  • Drive by a limit switch with neon lamp.
  • Same as Example 1.
  • Or make up another independent display circuit.

Example 2

Input signal does not turn OFF.

  • Leakage current due to line capacity of wiring cable. (Line capacity C of twisted pair wire is approx. 100 pF/m).
  • Same as Example 1.
  • However, leakage current is not generated when the power supply is located in the input equipment side as shown below.

Example 3

Input signal does not turn OFF.

  • Drive by switch with LED indicator.
  • Connect a register which will make the voltage between the input module terminal and common lower than the OFF voltage, as shown below.

DC input (plus common)

DC input (plus common)

Example 4

Input signal does not turn OFF.

A calculation example of a value for a

connected resistor is given on the following page.

11 - 38 11 - 38

Show 18 more labels / short text on this page
AC input · AC input · Power supply · Input module · AC input · Leakage current · Input module · Power supply · AC input · AC input · Leakage current · Input module · Input module · Power supply · Power supply · Leakage current · Input module · Input module Resistor
Page 155 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 39 11 - 39
Page 155 · click to enlarge
Page 155

Input Circuit Problems and Corrective Actions (Continued)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Input Circuit Problems and Corrective Actions (Continued) diagram (page 155)
Fig. 81 · Input Circuit Problems and Corrective Actions (Conti…
  • Sneak path due to the use of two power supplies.
  • Use only one power supply.
  • Connect a sneak path prevention diode. (Figure below)

Change response time setting. Example : 1ms 5ms (Setting of a shorter response time may produce a higher effect on periodic excessive noise.)If no effects are produced by the above, take basic actions to prevent excessive noise form entering, e.g. avoid bundling the power and I/O cables, and suppress noise by adding surge absorbers to such noise sources as relays and conductors used with the same power supply.)

Depending on response time setting, noise is imported as input.

11 - 39 11 - 39

Page 156 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 40 11 - 40
Page 156 · click to enlarge
Page 156

<Calculation example of Example 4>

QX40

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — QX40 diagram (page 156)
Fig. 82

If a switch with an LED display is connected to QX40 and current of 2.33 mA is leaked. 4.7k

Voltage VTB across the terminal and common base is: VTB = 2.33[mA] 5.6[k ] = 13[V] (Ignore the voltage drop caused by the LED.) Because the condition for the OFF voltage ( 11 [V]) is not satisfied, the input does not turn off. To correct this, connect a resistor as shown below.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — QX40 diagram (page 156)
Fig. 83

The voltage of QX40 across the terminals must be reduced to 11 [V] or less. The required current

(24-11[V]) ÷ 4.7[k ] = 2.77[mA] Therefore resistor R of flowing current I of 2.77 [mA] or more must be connected.

Calculation of resistance of connected resistor R

11[V] R > 2.77[mA] - 5.6[k ] 11[V] 11[V] ÷ R > 2.77-1.96[mA] 11[V] ÷ 0.81[mA] > R 13.6[k ] > R Resistance of the connected resistor R is obtained in the above equations.

Suppose that the resistance R is 12 [kW]. The power capacity W of the resistor during activation of the switch is: W = (Applied voltage)2 / R W = (28.8[V])2/12[k ]=0.069[W]

Because the resistance is selected so that the power capacity is three to five times

the actual power consumption, a third to a half [W] should be selected. In this case, a resistor of 12 [k ] and a third to a half [W] should be connected across the terminal and COM.

11 - 40 11 - 40

Page 157 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — QY22
Page 157 · click to enlarge
Page 157

11.5.2 Output Circuit Troubleshooting

This section explains trouble examples and troubleshooting methods in the output circuit.

Output Circuit Troubleshooting

Condition Cause Corrective Action

  • When load is half-wave rectified inside (This is typical of some solenoids.)
  • Connect a resistor of several ten K to several hundred K across the load.

QY22

D1

Excessive voltage is applied to load when output turns off.

Example 1

  • When the polarity of the power supply is [1], the capacitor C is charged. When the polarity is [2], the voltage charged in C plus the power supply voltage is applied to across D1. The maximum value of the voltage is approx. 2.2E. (This usage does not pose problems to the output components but may deteriorate the diode built in the load, causing burnout, etc.)
  • Leakage current due to the built-in surge suppressor
  • Connect a resistor across the load. (If the wiring from the output module to the load is long, be careful since there may be a leakage current due to the line capacity.)

QY22

Example 2

Load does not turn off. (Triac output)

11 - 41 11 - 41

Show 10 more labels / short text on this page
[1] · Output module · Resistor · Load · Load · [2] · Output module Load · Resistor · Leakage current · Load
Page 158 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 42 11 - 42
Page 158 · click to enlarge
Page 158

11.6 Special Relay List

Special relays, SM, are internal relays whose applications are fixed in the PLC. For this reason, they cannot be used by sequence programs in the same way as the normal internal relays. However, they can be turned ON or OFF as needed in order to control the CPU module and remote I/O modules. The headings in the table that follows have the following meanings.

  • Item Function of Item Number
  • Indicates the number of the special relay. Name
  • Indicates the name of the special relay. Meaning
  • Indicates the nature of the special relay. Explanation
  • Contains detailed information about the nature of the special relay.
  • Indicates whether the relay is set by the system or user, and, if it is set by the system, when setting is performed. <Set by>

S : Set by system U : Set by user (in sequence program or test operation at a GX Developer) S/U : Set by both system and user

Indicated only if setting is done by system. Each END : Set during each END processing Initial : Set only during initial processing

Set by (When set)

(when power supply is turned ON, or when going from STOP to RUN) Status change : Set only when there is a change in status Error : Set when error is generated Instruction execution : Set when instruction is executed Request : Set only when there is a user request

(through SM, etc.)

  • Indicates special relay M9 corresponding to the ACPU. (Change and notation when there has been a change in contents)
  • Items indicated as "New" have been newly added for High performance model QCPU/QnACPU.
  • Indicates the corresponding CPU module type name. +Rem: Can be applied to all CPU module types and MELSECNET/H remote I/O modules. : Can be applied to all types of CPU module QCPU: Can be applied to High Performance model QCPU QnA: Can be applied to QnA series and Q2ASCPU Series Remote: Can be applied to the MELSECNET/H remote I/O modules. Each CPU type name: Can be applied only to the specific CPU module. (e.g. Q4ARCPU, Q3ACPU)
  • For details on the following items, refer to the following manuals:
  • Networks
  • For Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)
  • For Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)
  • For QnA/Q4AR MELSECNET/10 Network System Reference Manual
  • SFC QCPU(Q Mode)/QnACPU Programming Manual (SFC)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — 11.6 Special Relay List diagram (page 158)
Fig. 84 · 11.6 Special Relay List

POINT (1) SM1200 to SM1255 are used for QnACPU.

These relays are vacant with QCPU. (2) Special relays SM1500 and later are dedicated for Q4ARCPU.

11 - 42 11 - 42

Corresponding ACPU M9 · Corresponding CPU

Page 159 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — U
Page 159 · click to enlarge
Page 159

Special Relay List

(1) Diagnostic Information

Number Name Meaning Explanation Set by (When Set)

ACPU M9

  • ON if diagnosis results show error occurrence (Includes when an annunciator is ON, and when an error is detected with CHK instruction)
  • Stays ON subsequently even if normal operations restored
SM0 Diagnostic errors OFFNo error
ONError
  • Comes ON when an error occurs as a result of selfdiagnosis. (Does not include when annunciator is ON or when error is detected by CHK instruction.)
  • Stays ON subsequently even if normal operations restored
OFFNo self-diagnosis
errors ONSelf-diagnosis
OFFNo error common

SM5 Error common information

information ONError common
  • When SM0 is ON, ON if there is error common information S (Error) New
OFFNo error common

SM16 Error individual information

information ONError common
  • When SM0 is ON, ON if there is error individual information S (Error) New
SM50 Error reset OFF ONError reset • Conducts error reset operation U New
  • ON if battery voltage at CPU module or memory card drops below rated value. Stays ON subsequently even after normal operation is restored
  • Synchronous with BAT. ALA/BAT. LED
SM51 Battery low latch OFFNormal ON : Battery low
SM52 Battery low OFFNormal ON : Battery low
  • Same as SM51, but goes OFF subsequently when battery voltage returns to normal. S (Error) M9006
  • Comes ON it a momentary power interruption of less than 20ms occurred during use of the AC power supply module, and reset by turning the power OFF, then ON.
OFFAC/DC DOWN not
  • Comes ON if a momentary power interruption of less than 10ms occurred during use of the DC power supply module, and reset by turning power OFF, then ON.

QCPU SM53 AC/DC DOWN detection

detected ONAC/DC DOWN

detected • Comes ON if a momentary power interruption of less than 1ms occurred during use of the DC power supply module, and reset by turning power OFF, then ON.

  • Goes ON if MINI (S3) link error is detected at even one of the installed MELSECNET/MINI master modules. Stays ON subsequently even after normal operation is restored.
SM54 MINI link errors OFFNormal ON : Error

S (Error) M9004 QnA

  • ON when operation error is generated
  • Stays ON subsequently even if normal operations restored
SM56 Operation Errors OFFNormal ON : Operation error
  • Comes ON even if there is only one output module with a blown fuse, and remains ON even after return to normal
  • Blown fuse status is checked even for remote I/O station output modules.

SM60 Blown fuse detection

OFFNormal ON : Module with blown fuse
  • Comes ON if there is a discrepancy between the actual I/O modules and the registered information when the power is turned on
  • I/O module verification is also conducted for remote I/O station modules.

SM61 I/O module verification error

OFFNormal ON : Error

OFF : Not detected ON : Detected • Goes ON if even one annunciator F goes ON. S (Instruction

M9009

  • Goes ON if error is detected by CHK instruction.
  • Stays ON subsequently even after normal operation is restored.
SM80 CHK detection OFFNot detected ON : Detected

SM90 Corresponds to SD90 M9108 SM91 Corresponds to SD91 M9109 SM92 Corresponds to SD92 M9110 SM93 Corresponds to SD93 M9111 SM94 Corresponds to SD94 M9112 SM95 Corresponds to SD95 M9113 SM96 Corresponds to SD96 M9114 SM97 Corresponds to SD97 New SM98 Corresponds to SD98 New SM99

Startup of watchdog timer for step transition (Enabled only when SFC program exists)

OFFNot started
  • Goes ON when measurement of step transition watchdog timer is commenced.
  • Resets watchdog timer when it goes OFF.
(watchdog timer reset) ONStarted

U

11 - 43 11 - 43

Show 23 more labels / short text on this page
Corresponding · Applicable · S (Error) New · SM1 Self-diagnosis error · S (Error) M9008 · +Rem · information · information · S (Error) M9007 · S (Error) M9005 · QnA · S (Error) M9011 · S (Error) M9000 · +Rem · S (Error) M9002 · SM62 Annunciator detection · execution) · S (Instruction · New · execution) · (watchdog timer started) · Corresponds to SD99 · New
Page 160 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 44 11 - 44
Page 160 · click to enlarge
Page 160

Special Relay List

(2) System information

Number Name Meaning Explanation Set by (When Set)

ACPU M9

SM202 LED OFF

command OFF ON : LED OFF • When this relay goes from OFF to ON, the LEDs corresponding to the individual bits at SD202 go off U New

SM203 STOP contact STOP status • Goes ON at STOP status S (Status

SM204 PAUSE contact PAUSE status • Goes ON at PAUSE status S (Status

SM205 STEP-RUN

contact STEP-RUN status • Goes ON at STEP-RUN status S (Status

OFFPAUSE disabled ON : PAUSE enabled
  • PAUSE status is entered if this relay is ON when the remote PAUSE contact goes ON U M9040
OFFDevice test not yet executed ON : Device test executed
  • Comes ON when the device test mode is executed on GX Developer. S (Request) New Remote

SM210 Clock data set

OFFIgnored ON : Set request
  • When this relay goes from OFF to ON, clock data being stored from SD210 to SD213 after execution of END instruction for changed scan is written to the clock device.

U M9025

SM211 Clock data error OFFNo error ON : Error
  • ON when error is generated in clock data (SD210 to SD213) value, and OFF if no error is detected. S (Request) M9026

Q3A Q4A Q4AR

OFFIgnored ON : Display
  • Displays clock data as month, day, hour, minute, and second at the LED display at front of CPU module. U M9027

SM213 Clock data read

OFFIgnored ON : Read request
  • When this relay is ON, clock data is read to SD210 to SD213 as BCD values. U M9028 +Rem
  • Goes OFF when reset of the PLC No. 1 is canceled.
  • Comes ON when the PLC No. 1 is resetting (including the case where the PLC is removed from the base unit). The other PLCs are also put in reset status.

SM240 No. 1 CPU reset

OFFPLC No. 1 reset cancel ON : PLC No. 1 resetting
  • Goes OFF when reset of the PLC No. 2 is canceled.
  • Comes ON when the PLC No. 2 is resetting (including the case where the PLC is removed from the base unit). The other PLCs result in "MULTI CPU DOWN" (error code: 7000).

SM241 No. 2 CPU reset

OFFPLC No. 2 reset cancel ON : PLC No. 2 resetting
  • Goes OFF when reset of the PLC No. 3 is canceled.
  • Comes ON when the PLC No. 3 is resetting (including the case where the PLC is removed from the base unit). The other PLCs result in "MULTI CPU DOWN" (error code: 7000).

SM242 No. 3 CPU reset

OFFPLC No. 3 reset cancel ON : PLC No. 3 resetting
  • Goes OFF when reset of the PLC No. 4 is canceled.
  • Comes ON when the PLC No. 4 is resetting (including the case where the PLC is removed from the base unit). The other PLCs result in "MULTI CPU DOWN" (error code: 7000).

SM243 No. 4 CPU reset

OFFPLC No. 4 reset cancel ON : PLC No. 4 resetting

Ver. B

OFFPLC No. 1 normal ON : PLC No. 1 during stop error
  • Goes OFF when the PLC No. 1 is normal (including a continuation error).
  • Comes ON when the PLC No. 1 is during a stop error.

SM244 No. 1 CPU error

OFFPLC No. 2 normal ON : PLC No. 2 during stop error
  • Goes OFF when the PLC No. 2 is normal (including a continuation error).
  • Comes ON when the PLC No. 2 is during a stop error.

SM245 No. 2 CPU error

SM246 No. 3 CPU error

OFFPLC No. 3 normal ON : PLC No. 3 during stop error
  • Goes OFF when the PLC No. 3 is normal (including a continuation error).
  • Comes ON when the PLC No. 3 is during a stop error.
OFFPLC No. 4 normal ON : PLC No. 4 during stop error
  • Goes OFF when the PLC No. 4 is normal (including a continuation error).
  • Comes ON when the PLC No. 4 is during a stop error.

SM247 No. 4 CPU error

11 - 44 11 - 44

Show 23 more labels / short text on this page
Corresponding · Applicable · change) M9042 · change) M9041 · change) M9054 · PAUSE enable coil · SM206 Device test · request acceptance status · request · SM212 Clock data · display · request · flag · flag · flag · S (Status · QCPU function · change) New · flag · flag · flag · flag · flag
Page 161 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — U
Page 161 · click to enlarge
Page 161

Special Relay List (Continued)

Number Name Meaning Explanation Set by (When Set)

ACPU M9

SM250 Max. loaded I/O

OFFIgnored ON : Read
  • When this relay goes from OFF to ON, maximum loaded I/O number is read to SD250. U New +Rem
  • After the head I/O number of the I/O module being replaced is set in SD251 is set, on-line I/O module replace ment is enabled when this relay is ON. (Only one module can be replaced at each setting.)
  • To replace an I/O module in the RUN status, use the program or a peripheral device to turn this relay ON; to replace an I/O module in the STOP status, turn this relay ON in the test mode of a peripheral device.
  • Do not switch between RUN and STOP status until I/O module replacement is completed.
SM251 I/O change flag OFFNo replacement ON : Replacement

Q2A (S1)

U (END) M9094

Q3A Q4A Q4AR

SM252 I/O change OK OFF : Replacement prohibited ON : Replacement enabled • Goes ON when I/O replacement is OK. S (END) New

  • Effective for the batch refresh (also effective for the low speed cyclic)
  • Designate whether to receive arrival stations only or to receive all slave stations.
OFFRefresh arrival station ON : Refresh all stations
  • Goes ON for standby network (If no designation has been made concerning active or standby, active is assumed.)
SM255 OFFOperative network ON : Standby network

MELSECNET/10 module 1 information

SM256 OFFReads ON : Does not read
  • For refresh from link to CPU (B, W, etc.) indicate whether to read from the link module. U New
OFFWrites ON : Does not write
  • For refresh from CPU to link (B, W, etc.), designate whether to write to the link module. U New

SM257

  • Goes ON for standby network (If no designation has been made concerning active or standby, active is assumed.)
SM260 OFFOperative network ON : Standby network

MELSECNET/10 module 2 information

SM261 OFFReads ON : Does not read
  • For refresh from link to CPU (B, W, etc.) indicate whether to read from the link module. U New
OFFWrites ON : Does not write
  • For refresh from CPU to link (B, W, etc.), designate whether to write to the link module. U New

SM262

  • Goes ON for standby network (If no designation has been made concerning active or standby, active is assumed.)
SM265 OFFOperative network ON : Standby network

MELSECNET/10 module 3 information

SM266 OFFReads ON : Does not read
  • For refresh from link to CPU (B, W, etc.) indicate whether to read from the link module. U New

SM267

OFFWrites ON : Does not write
  • For refresh from CPU to link (B, W, etc.), designate whether to write to the link module. U New
  • Goes ON for standby network (If no designation has been made concerning active or standby, active is assumed.)
SM270 OFFOperative network ON : Standby network

MELSECNET/10 module 4 information

SM271 OFFReads ON : Does not read
  • For refresh from link to CPU (B, W, etc.) indicate whether to read from the link module. U New

SM272

OFFWrites ON : Does not write
  • For refresh from CPU to link (B, W, etc.), designate whether to write to the link module. U New

change) New QCPU Remote SM280 CC-Link error OFF : Normal ON : Error • Goes ON when a CC-Link error is detected in any of the installed A(1S)J61QBT11. Stays ON even after normal operation is restored.

  • Goes ON when a CC-Link error is detected in any of the installed QJ61QBT11. Goes OFF when normal operation is restored.

S (Error) New QnA

Presence/absenc e of SFC program

  • ON if SFC program is correctly registered, and OFF if not registered.
  • Goes OFF if SFC dedicated instruction is not correct. S (Initial) M9100

SM320

OFFSFC program absent ON : SFC program present
  • Initial value is set at the same value as SM320. (Goes ON automatically if SFC program is present.)
  • SFC program will not execute if this goes OFF prior to SFC program processing
  • Starts SFC program when this relay goes from OFF to ON.
  • Stops SFC program when this relay goes from ON to OFF.
OFFSFC program stop ON : SFC program start

U

11 - 45 11 - 45

Show 16 more labels / short text on this page
Corresponding · Applicable · read · SM254 All stations · U (Every · END) New QCPU · refresh command · S (Initial) New · S (Initial) New · S (Initial) New · S (Initial) New · S (Status · SM321 Start/stop SFC · S (Initial) · M9101 format change · program
Page 162 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 46 11 - 46
Page 162 · click to enlarge
Page 162

Special Relay List (Continued)

Number Name Meaning Explanation Set by (When Set)

ACPU M9

  • Initial value is set at ON or OFF depending on parameters.
  • When this relay is OFF, all execution status are cleared from time SFC program was stopped; starts from the initial step of block where the start request was made.
  • When this relay is ON, starts from execution block and execution step active at time SFC program was stopped. (ON is enabled only when resumptive start has been designated at parameters.)
  • SM902 is not automatically designated for latch.
OFFInitial start ON : Restart

U

  • When this relay is OFF, transition occurs at one scan/one step, for all blocks.
  • When this relay is ON, transition occurs continuously for all blocks in one scan.
  • In designation of individual blocks, priority is given to the continuous transition bit of the block. (Designation is checked when block starts.)

Presence/absenc e of continuous transition for entire block

OFFContinuous transition

SM323

not effective ONContinuous transition

U M9103

Continuous transition prevention flag

OFFWhen transition is
  • When continuous transition is effective, goes ON when continuous transition is not being executed; goes OFF when continuous transition is being executed.
  • Normally ON when continuous transition is not effective.

SM324

executed ONWhen no transition

M9104

SM325 Output mode at

OFFOFF ON : Preserves
  • When block stops, selects active step operation output.
  • All coil outputs go OFF when this relay is OFF.
  • Coil outputs are preserved when this relay is ON.

U M9196

Selects the device status when the stopped CPU is run after the sequence program or SFC program has been modified when the SFC program exists.

SM326 SFC device clear

OFFClear device ON : Preserves device
  • Selects the output action of the step being held when a block is ended by executing the end step.
  • All coil outputs go OFF when this relay is OFF.
  • Coil outputs are preserved when this relay is ON.

Output during end step execution

OFFOFF ON : Preserves

SM327

Operation mode for low speed execution type program

SM330

OFFAsynchronous mode ON : Synchronous mode

Low speed execution type program ON for 1 scan only after RUN U (END) New

  • Stores the status of the intelligent function module access instruction executed immediately before. (This information will be overwritten when the intelligent function module access instruction is executed again.)
  • This flag is used by the user in a program as the completion bit.

When ON, access to the intelligent function module is completed

11 - 46 11 - 46

Show 19 more labels / short text on this page
Corresponding · Applicable · SM322 SFC program · S (Initial) · M9102 format change · start status · effective · S (Instruction · execution) · S (Initial) · block stop · U New · mode · S (Initial) · U New · SM390 Access execution · S (Status · change) New QCPU · flag
Page 163 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 47 11 - 47
Page 163 · click to enlarge
Page 163

Special Relay List

(3) System clocks/counters

Number Name Meaning Explanation Set by (When Set)

ACPU M9

SM400 Always ON ON OFF

  • Normally is ON S (Every END processing)

M9036

SM401 Always OFF ON OFF

  • Normally is OFF S (Every END processing)

M9037

  • After RUN, ON for 1 scan only.
  • This connection can be used for scan execution type programs only.

S (Every END processing)

SM402 ON for 1 scan

ON OFF

M9038

SM403 After RUN, OFF

ON OFF 1 scan

  • After RUN, OFF for 1 scan only.
  • This connection can be used for scan execution type programs only.

S (Every END processing)

M9039

for 1 scan only

Low speed execution type program ON for 1 scan only after RUN

ON OFF 1 scan

  • After RUN, ON for 1 scan only.
  • This connection can be used for low speed execution type programs only.

S (Every END processing)

SM404

Low speed execution type program After RUN, OFF for 1 scan only

ON OFF 1 scan

  • After RUN, OFF for 1 scan only.
  • This connection can be used for low speed execution type programs only.

S (Every END processing)

SM405

  • Repeatedly changes between ON and OFF at 5-ms interval.
  • When PLC power supply is turned OFF or a CPU module reset is performed, goes from OFF to start.
  • Note that the ON-OFF status changes when the designated time has elapsed during the execution of the program.

SM409 0.01 second

0.005 sec. 0.005 sec.

SM410 0.1 second clock 0.05 sec. 0.05 sec. M9030

  • Repeatedly changes between ON and OFF at each designated time interval.
  • When PLC power supply is turned OFF or a CPU module reset is performed, goes from OFF to start.
  • Note that the ON-OFF status changes when the designated time has elapsed during the execution of the program.

SM411 0.2 second clock 0.1sec. 0.1sec. M9031

SM412 1 second clock 0.5 sec. 0.5 sec. M9032

SM413 2 second clock 1 sec. 1 sec.

M9033

  • Goes between ON and OFF in accordance with the number of seconds designated by SD414.
  • When PLC power supply is turned OFF or a CPU module reset is performed, goes from OFF to start.
  • Note that the ON-OFF status changes when the designated time has elapsed during the execution of the program.

SM414 2n second clock n sec. n sec.

  • Switches between ON and OFF in accordance with the number of milliseconds designated by SD415.
  • When PLC power supply is turned OFF or a CPU module reset is performed, goes from OFF to start.
  • Note that the ON-OFF status changes when the designated time has elapsed during the execution of the program.

SM415 2n (ms) clock n(ms) n(ms)

SM420 User timing clock

No.0 M9020

SM421 User timing clock

No.1 M9021

  • Relay repeats ON/OFF switching at fixed scan intervals.
  • When PLC power supply is turned OFF or a CPU module reset is performed, goes from OFF to start.
  • The ON/OFF intervals are set with the DUTY instruction. DUTY n1 n2 SM420

S (Every END processing)

SM422 User timing clock

No.2 M9022

SM423 User timing clock

No.3 M9023

SM424 User timing clock

n2 scan n2 scan

M9024

No.4

SM430 User timing clock

No.5

SM431 User timing clock

No.6

  • For use with SM420 to SM424 low speed programs. S (Every END processing)

SM432 User timing clock

No.7

SM433 User timing clock

No.8

SM434 User timing clock

No.9

11 - 47 11 - 47

Show 19 more labels / short text on this page
Corresponding · Applicable · 1 scan · only after RUN · New · New · S (Status · change) New QCPU · clock · S (Status · change) · S (Status · M9034 format · change) · change · S (Status · change) New QCPU · n1 scan · New
Page 164 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SM672
Page 164 · click to enlarge
Page 164

Special Relay List

(4) Scan information

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Relay List diagram (page 164)
Fig. 85 · Special Relay List
  • Goes ON when low speed execution type program is executed.
  • When this relay goes from OFF to ON, the module service interval designated by SD550 is read to SD551 to SD552.

(5) Memory cards

Number Name Meaning Explanation Set by (When Set)

ACPU M9

OFF : Unusable ON : Use enabled • ON when memory card is ready for use by user S (Initial) New

OFF : No protect ON : Protect • Goes ON when memory card protect switch is ON S (Initial) New

SM602 Drive 1 flag OFF : No drive 1 ON : Drive 1 present • Goes ON when loaded memory card is RAM. S (Initial) New

SM603 Drive 2 flag OFF : No drive 2 ON : Drive 2 present • Goes ON when loaded memory card is ROM. S (Initial) New

OFF : Not used ON : In use • Goes ON when memory card is in use S (Initial) New

Memory card remove/insert prohibit flag

OFFRemove/insert enabled ON : Remove/insert
  • Goes ON when memory card cannot be inserted or removed U New

SM605

  • Turned ON by user to enable the removal/insertion of memory card.
  • Turned OFF by the system after the memory card is removed.

Memory card remove/insert enable flag

OFFRemove/insert

SM609

prohibited ONRemove/insert enabled
  • Always ON S (Initial) New QCPU

SM620 Memory card B

OFF : Unusable ON : Use enabled • ON when memory card B is ready for use by user S (Initial) New

Q2A (S1)

Q3A Q4A Q4AR • Always ON S (Initial) New QCPU

Q2A (S1)

SM621 Memory card B

OFF : No protect ON : Protect • Goes ON when memory card B protect switch is ON S (Initial) New

Q3A Q4A Q4AR • Always ON S (Initial) New QCPU

Q2A (S1)

SM622 Drive 3 flag OFF : No drive 3 ON : Drive 3 present • Goes ON when drive 3 (card 2 RAM area) is present S (Initial) New

  • Q3A Q4A Q4AR
  • Always ON S (Initial) New QCPU SM623 Drive 4 flag OFF : No drive 4 ON : Drive 4 present
  • Goes ON when drive 4 (card 2 ROM area) is present S (Initial) New

SM624 Memory card B

OFF : Not used ON : In use • Goes ON when memory card B is in use S (Initial) New

Q2A (S1)

Q3A Q4A Q4AR

Memory card B remove/insert prohibit flag

OFFRemove/insert enabled ON : Remove/insert
  • Goes ON when memory card B cannot be inserted or removed U New

SM625

SM640 File register use OFF : File register not used ON : File register in use • Goes ON when file register is in use S (Status

SM650 Comment use OFF : File register not used ON : File register in use • Goes ON when comment file is in use S (Status

OFFInternal memory
execution ONBoot operation in
  • Goes ON while boot operation is in process
  • Goes OFF if boot designation switch is OFF S (Status

Memory card A file register access range flag

  • Goes ON when access is made to area outside the range of file register R of memory card A (Set within END processing.)
  • Reset at user program
OFFWithin access range ON : Outside access range

SM672

11 - 48 11 - 48

Show 20 more labels / short text on this page
Corresponding · Applicable · SM600 Memory card · usable flags · SM601 Memory card · protect flag · SM604 Memory card · in-use flag · prohibited · U/S New · usable flags · protect flag · in-use flag · prohibited · change) New · change) New · SM660 Boot operation · change) New · progress · S/U New
Page 165 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 49 11 - 49
Page 165 · click to enlarge
Page 165

Special Relay List (Continued)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Relay List (Continued) diagram (page 165)
Fig. 86 · Special Relay List (Continued)
  • Goes ON when access is made outside the range of file registers, R. of memory card B. (Set within END processing.)
  • Reset at user program
OFFWithin access range ON : Outside access range

(6) Instruction-Related Special Relays

Number Name Meaning Explanation Set by (When Set)

ACPU M9

SM700 Carry flag OFF : Carry OFF ON : Carry ON • Carry flag used in application instruction S (Instruction

M9012

  • When SM701 is OFF, 16 characters of ASCII code are output.
  • When SM701 is ON, output conducted until NUL (00H) code of ASCII code is encountered.

Number of output characters selection

SM701

OFF16 characters output ON : Outputs until NUL

U M9049

SM702 Search method OFFSearch next ON : 2-part search
  • Designates method to be used by search instruction.
  • Data must be arranged for 2-part search. U New
  • The sort instruction is used to designate whether data should be sorted in ascending order or in descending order.
SM703 Sort order OFFAscending order ON : Descending order
SM704 Block comparison OFFNon-match found
  • Goes ON when all data conditions have been met for the BKCMP instruction.
ONAll match

Selection of real number instruction processing type

  • When SM707 is OFF, real number instructions are processed at high speed.
  • When it is ON, real number instructions are processed with high accuracy.
OFFSpeed oriented ON : Accuracy oriented

SM707

CHK instruction priority ranking flag

SM710

OFFConditions priority ON : Pattern priority
  • Remains as originally set when OFF.
  • CHK priorities updated when ON.
OFFOther than during
  • In processing of AD57(S1), goes ON when screen is split for transfer, and goes OFF when split processing is completed
divided processing ONDuring divided

SM711

M9065

OFFBatch processing ON : Divided processing
  • In processing of AD57(S1), goes ON when canvas screen is divided for transfer.

SM712

M9066

OFFCommunication

request to remote terminal module enabled ON : Communication

Communication request registration area BUSY signal

  • Used to determine whether communications requests to remote terminal modules connected to the AJ71PT32-S3 can be executed or not.

SM714

M9081

request to remote terminal module disabled

SM715 EI flag OFF : During DI ON : During EI • ON when EI instruction is being executed. S (Instruction

OFFComment read not
completed ONComment read
  • Switches ON for only one scan when COMRD or PRC instruction is completed.
  • Switches ON while a file is being accessed by the S.FWRITE, S.FREAD, COMRD, PRC, or LEDC instruction.
OFFFile not accessed ON : File being accessed

QCPU

BIN/DBIN instruction error disabling flag

OFFError detection
performed ONError detection not
  • Turned ON when "OPERATION ERROR" is suppressed for BIN or DBIN instruction. U New

SM722

OFFRequest for

communication with intelligent device station enabled ON : Request for

BUSY signal for CC-Link communication request registration area

  • Used for determination whether to enable or disable the communication request for the intelligent device station connected with A(1S)J61QBT11.

SM730

communication with intelligent device station disabled

11 - 49 11 - 49

Show 36 more labels / short text on this page
Corresponding · Applicable · execution) · U New · S (Instruction · New · execution) · U New Q4AR · S (Instruction · New · execution) · Divided transmission status · S (Instruction · execution) · processing · Transmission processing selection · S (Instruction · execution) · QnA · S (Instruction · execution) · New · execution) · SM720 Comment read · S (Status · change) New · completion flag · completed · SM721 File being · S (Status · accessed · change) New · performed · S (Instruction · New QnA · execution)
Page 166 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 50 11 - 50
Page 166 · click to enlarge
Page 166

Special Relay List (Continued)

Number Name Meaning Explanation Set by (When Set)

ACPU M9

PKEY instruction execution in progress flag

OFFInstruction not
  • ON when PKEY instruction is being executed. Goes OFF when CR is input, or when input character string reaches 32 characters.

SM736

executed ONInstruction execution

Keyboard input reception flag for PKEY instruction

OFFKeyboard input
reception enabled ONKeyboard input
  • Goes ON when keyboard input is being conducted. Goes when keyboard input has been stored at the CPU.

SM737

OFFInstruction not
  • Goes ON when MSG instruction is executed. S (Instruction
executed ONInstruction execution
OFFForces match ON : Does not force match
  • In manual mode, designates whether or not to force the SV value to match the PV value. U New
OFFPerforms link refresh ON : Performs no link
  • Selects whether only the general data process is performed for the execution of the COM instruction or the link refresh process is also performed.

Selection of link refresh processing during COM instruction execution

SM775

OFFPerforms all refresh

QCPU

processes ONPerforms the refresh
  • Selects whether all refresh process or the refresh set with SD778 is performed when COM instruction is executed. U New

Enable/disable local device at CALL

OFFLocal device disabled ON : Local device enabled
  • Determines whether to enable/disable the local device in the program CALLED at CALL.

SM776

Enable/disable local device in interrupt program

OFFLocal device disabled ON : Local device enabled
  • Determines whether to enable/disable the local device at the execution of interrupt programs.

SM777

OFFCC-Link dedicated

CC-Link dedicated instruction executable

instruction executable ONCC-Link dedicated
  • Switches ON when the number of the CC-Link dedicated instructions that can be executed simultaneously reaches 32. Switches OFF when the number goes below 32.

SM780

(7) Debug

Number Name Meaning Explanation Set by (When Set)

ACPU M9

Trace preparation • Switches ON when the trace preparation is completed. S (Status

change) New QCPU SM800 Sampling trace

OFF : Not ready ON : Ready • Goes ON when sampling trace is ready S (Status

  • Trace start
  • Trace started when this goes ON.
  • Suspended when OFF (Related special M all OFF) U M9047 QCPU SM801 Sampling trace
  • OFF : Suspend ON : Start
  • Sampling trace started when this goes ON
  • Suspended when OFF (Related special M all OFF) U M9047 QnA

Trace execution in progress • Switches ON during execution of trace. S (Status

OFFSuspend ON : Start • Goes ON during execution of sampling trace S (Status

Trace trigger • Trace is triggered when this relay switches from OFF to ON. (Identical to TRACE instruction execution status) U M9044 QCPU

OFF ON: Start • Sampling trace trigger goes ON when this goes from OFF to ON (Identical to STRA instruction execution status)

After trace trigger • Switches ON after trace is triggered. S (Status

change) New QCPU SM804 After sampling

OFF : Not after trigger ON : After trigger • Goes ON after sampling trace trigger S (Status

change) 9043 QCPU SM805 Sampling trace

Trace completed • Switches ON at completion of trace. S (Status

OFF : Not completed ON : End • Goes ON at completion of sampling trace S (Status

11 - 50 11 - 50

Show 43 more labels / short text on this page
Corresponding · Applicable · S (Instruction · New · execution) · S (Instruction · New · execution) · reception disabled · SM738 MSG instruction · New · reception flag · execution) · SM774 PID bumpless · processing · U New · refresh · serial number ** · set the SD778 · or later · U (Status · change) New · U (Status · change) New · U (Status · change) New QnA · instruction not executable · Corresponding · Applicable · change) New QnA · preparation · start · change) M9046 QCPU · SM802 Sampling trace · execution in progress · change) M9046 QnA · SM803 Sampling trace · U M9044 QnA · trigger · change) New QnA · trace trigger · change) 9043 QnA · completed
Page 167 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 51 11 - 51
Page 167 · click to enlarge
Page 167

Special Relay List (Continued)

Number Name Meaning Explanation Set by (When Set)

ACPU M9

OFF : Not ready ON : Ready • Goes ON when status latch is ready S (Status

command OFF ONLatch • Runs status latch command U New

OFF : Latch not completed ON : Latch completed • Comes ON when status latch is completed. S (Status

SM809 Status latch clear OFF ON: Clear • Enable next status latch U New

OFF : Not ready ON : Ready • Goes ON when program trace is ready S (Status

OFFSuspend ON : Start
  • Program trace started when this goes ON
  • Suspended when OFF (Related special M all OFF) S (Status

Program trace execution under way

OFFSuspend ON : Start • ON when program trace execution is underway U New

SM812

trigger OFF ON: Start • Program trace trigger goes ON when this goes from OFF to ON (Identical to PTRA instruction execution status)

OFF : Not after trigger ON : After trigger • Goes ON after program trace trigger S (Status

OFF : Not completed ON : End • Goes ON at completion of program trace S (Status

OFF : Not ready ON : Ready • Goes ON after program trace registration, at ready. U New

SM821 Step trace starts OFFSuspend ON : Start
  • When this goes ON, step trace is started
  • Suspended when OFF (Related special M all OFF) S (Status

Step trace execution underway

OFFSuspend ON : Start
  • Goes ON when step trace execution is underway
  • Goes OFF at completion or suspension S (Status

SM822

  • Goes ON if even 1 block within the step trace being executed is triggered.
  • Goes OFF when step trace is commenced.

SM823 After step trace

OFFNot after trigger ON : Is after first trigger
  • Goes ON if all blocks within the step trace being executed are triggered.
  • Goes OFF when step trace is commenced.

SM824 After Step trace

OFFIs not after all triggers ON : Is after all triggers
OFFNot completed ON : End
  • Goes ON at step trace completion.
  • Goes OFF when step trace is commenced. S (Status

change) New QCPU SM826 Sampling trace

Trace error • Switches ON if error occurs during execution of trace. S (Status

OFF : Normal ON : Errors • Goes ON if error occurs during execution of sampling trace.

SM827 Status latch error OFFNormal
ONErrors • Goes ON if error occurs during execution of status latch. S (Status
OFFNormal ON : Errors
  • Goes ON if error occurs during execution of program trace.

(8) Latch area

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (8) Latch area diagram (page 167)
Fig. 87 · (8) Latch area
SM900 Power cut file OFFNo power cut file ON : Power cut file present
  • Goes ON if a file is present during access when power is interrupted.
  • Goes ON at registration of keyboard input. OFF if keyboard input is not registered.

11 - 51 11 - 51

Show 50 more labels / short text on this page
Corresponding · Applicable · SM806 Status latch · change) New · preparation · SM807 Status latch · QnA · SM808 Status latch · change) 9055 · completion · SM810 Program trace · change) New · preparation · SM811 Start program · change) New · trace · QnA · SM813 Program trace · S (Status · change) New · SM814 After program · change) New · trace trigger · SM815 Program trace · change) New · completion · SM820 Step trace · preparation · M9182 format · change) · change · change) M9181 · S (Status · trigger · change) New · S (Status · change) New · trigger · SM825 Step · change) M9180 · tracecompleted · S (Status · change) New · error · change) New · QnA · SM828 Program trace · S (Status · error · change) New
Page 168 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 52 11 - 52
Page 168 · click to enlarge
Page 168

(9) A to Q/QnA conversion correspondences

Special relays SM1000 to SM1255 are the relays which correspond to ACPU special relays M9000 to M9255 after A to Q/QnA conversion. All of these special relays are controlled by the system so that users cannot turn them ON/OFF in the program. If users want to turn these relays ON/OFF, the program should be modified to use QCPU/QnACPU special relays. For SM1084 and SM1200 through SM1255, however, if a user can turn ON/OFF some of special relays M9084 and M9200 through M9255 before conversion, the user can also turn ON/OFF the corresponding relays among SM1084 and SM1200 through SM1255 after the conversion. For details on the ACPU special relays, see the user's manuals for the individual CPUs, and MELSECNET or MELSECNET/B Data Link System Reference Manuals.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (9) A to Q/QnA conversion correspondences diagram (page 168)
Fig. 88 · (9) A to Q/QnA conversion correspondences

POINT The processing time may be longer when converted special relays are used with QCPU. Uncheck "A-series CPU compatibility setting" within the PC system setting in GX Developer PC parameters when converted special relays are not used.

REMARK

The following are additional explanations about the Special Relay for Modification column.

1 When a special relay for modification is provided, the device number should be changed to the provided QCPU/QnACPU special relay.

2 When is provided, the converted special relay can be used for the device number.

3 When is provided, the device number does not work with QCPU/QnACPU.

Special Relay List

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

  • Turned on when there is one or more output units of which fuse has been blown.Remains on if normal status is restored. Output modules of remote I/O stations are also checked fore fuse condition.
M9000 SM1000 Fuse blown OFFNormal ON : Module with blown fuse
  • Turned on if the status of I/O module is different form entered status when power is turned on. Remains on if normal status is restored. I/O module verification is done also to remote I/O station modules. (Reset is enabled only when special registers SD1116 to SD1123 are reset.)

I/O module verification error

OFFNormal ON : Error

M9002 SM1002

  • Turned on when the MINI(S3) link error is detected on even one of the MELSECNET/MINI master modules being loaded.Remains on if normal status is restored.

M9004 SM1004 NIMI link error OFF : Normal ON : Error

  • Comes ON it a momentary power interruption of less than 20ms occurred during use of the AC power supply module, and reset by turning power OFF, then ON.
  • Comes ON if a momentary power interruption of less than 10ms occurred during use of the DC power supply module, and reset by turning power OFF, then ON. M9005 SM1005
OFFAC DOWN not detected ON : AC DOWN detected
  • Comes ON if a momentary power interruption of less than 1ms occurred during use of the DC power supply module, and reset by turning power OFF, then ON.

11 - 52 11 - 52

ACPU Special · QnA · AC DOWN detection

Page 169 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 53 11 - 53
Page 169 · click to enlarge
Page 169

Special Relay List (Continued)

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

  • Turned on when battery voltage reduces to less than specified. Turned off when battery voltage becomes normal.
M9006 SM1006 Battery low OFFNormal ON : Battery low

M9007 SM1007 Battery low latch OFF : Normal ON : Battery low

  • Turned on when battery voltage reduces to less than specified. Remains on if battery voltage becomes normal.

M9008 SM1008 SM1 Self-diagnosis error

OFFNo error ON : Error
  • Turned on when error is found as a result of selfdiagnosis.

M9009 SM1009 SM62 Annunciator detection

OFFNo F number detected ON : F number detected
  • Turned on when OUT F of SET F instruction is executed. Switched off when SD1124 data is zeroed.
  • Turned on when operation error occurs during execution of application instruction. Remains on if normal status is restored.

M9011 SM1011 SM56 Operation error flag

OFFNo error ON : Error

M9012 SM1012 SM700 Carry flag OFF : Carry OFF ON : Carry ON • Carry flag used in application instruction.

  • Clears the data memory including the latch range (other than special relays and special registers) in remote run mode from computer, etc. when SM1016 is on.

M9016 SM1016 Data memory clear flag

OFFlgnored ON : Output claered

M9017 SM1017 Data memory clear flag

OFFlgnored ON : Output claered
  • Clears the unlatched data memory (other than special relays and registers) in remote run mode from computer, etc. when SM1017 is on.

User timing clock No.0

M9020 SM1020

  • Relay which repeats on/off at intervals of predetermined scan.
  • When power is turned on or reset is per-formed, the clock starts with off.
  • Set the intervals of on/off by DUTY instruction.

User timing clock No.1

M9021 SM1021

User timing clock No.2

M9022 SM1022

M9023 SM1023

User timing clock No.3

DUTY n1 n2 M9020

M9024 SM1024

User timing clock No.4

  • Writes clock data from SD1025 to SD1028 to the clock element after the END instruction is executed during the scan in which SM1025 has changed from off to on.

M9025 SM1025

Clock data set request

OFFIgnored ON : Set request present used

M9026 SM1026 Clock data error OFF : No error ON : Error • Switched on by clock data (SD1025 to SD1028) error

OFFIgnored ON : Display
  • Clock data is read from SD1025 to SD1028 and month, day, hour, minute and minute are indicated on the CPU front LED display.

M9027 SM1027

Clock data read request

OFFIgnored ON : Read request
  • Reads clock data to SD1025 to SD1028 in BCD when SD1028 is on.

M9028 SM1028

  • The SM1029 relay is turned on using a sequence program to process all data communication requests accepted during one scan in the END processing of that scan.
  • The batch processing of the data communication requests can be turned on and off during running.
  • The default is OFF (processed one at a time for each END processing in the order in which data communication requests are accepted).

Batch processing of data communications requests

OFFBatch processing not

M9029 SM1029

conducted ONBatch processing

0.05 seconds 0.05 seconds

M9030 SM1030 0.1 second clock

0.1 seconds 0.1 seconds

  • 0.1 second, 0.2 second, 1 second and 2 second, clocks are generated.
  • Not turned on or off per scan but turned on and off even during scan if corresponding time has elapsed.
  • Starts with off when PLC power supply is turned on or CPU module reset is performed.

M9031 SM1031 0.2 second clock

0.5 seconds 0.5 seconds

M9032 SM1032 1 second clock

1 seconds 1 seconds

M9033 SM1033 2 second clock

  • Alternates between ON and OFF according to the seconds specified at SD414. (Default: n = 30)
  • Not turned on or off per scan but turned on and off even during scan if corresponding time has elapsed.
  • Starts with off when PLC power supply is turned on or CPU module reset is performed..

2n minute clock (1 minute clock)

n seconds n seconds

M9034 SM1034

: 1 minute clock indicates the name of the special relay (M9034) of the ACPU.

11 - 53 11 - 53

Show 6 more labels / short text on this page
ACPU Special · n2 scan · n2 scan · n1 scan · Clock data display · conducted
Page 170 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 54 11 - 54
Page 170 · click to enlarge
Page 170

Special Relay List (Continued)

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

ON OFF

M9036 SM1036 Always ON

  • Used as dummy contacts of initialization and application instruction in sequence program.
  • SM1038 and SM1037 are turned on and off without regard to position of key switch on CPU module front. SM1038 and SM1039 are under the same condition as RUN status except when the key switch is at STOP position, and turned off and on. Switched off if the key switch is in STOP position. SM1038 is on for one scan only and SM1039 is off for one scan only if the key switch is not in STOP position.

ON OFF

M9037 SM1037 Always OFF

ON for 1 scan only after RUN

ON OFF 1 scan

M9038 SM1038

RUN flag(After RUN, OFF for 1 scan only)

ON OFF 1 scan

M9039 SM1039

M9040 SM1040 SM206 PAUSE enable coil

OFFPAUSE disabled ON : PAUSE enabled
  • When RUN key switch is at PAUSE position or remote pause contact has turned on and if SM204 is on, PAUSE mode is set and SM206 is turned on.

M9041 SM1041 SM204 USE status contact

OFFPAUSE not in effect ON : PAUSE in effect

M9042 SM1042 SM203 STOP status contact

OFFSTOP not in effect ON : STOP in effect
  • Switched on when the RUN key switch or RUN/STOP switch is in STOP position.
OFFSampling trace in
  • Turned on upon completion of sampling trace performed the number of times preset by parameter after STRA instruction is executed. Reset when STRAR instruction is executed.

M9043 SM1043 SM805 Sampling trace completed

progress ONSampling trace
  • Turning on/off SM803 can execute STRA / STRAR instruction. (SM803 is forcibly turned on/off by a peripheral device.) When switched from OFF to ON: STRA instruction When switched from ON to OFF: STRAR instruction

OFF ON STRA

Same as execution ON OFF STRAR

M9044 SM1044 SM803 Sampling trace

The value stored in SD1044 is used as the condition for the sampling trace. At scanning, at time → Time (10 ms unit)

  • The SM1015 relay is turned on to reset the WDT when the ZCOM instruction and data communication request batch processing are executed (used when the scan time exceeds 200 ms).

M9045 SM1045 Watchdog timer (WDT) reset

OFFDoes not reset WDT ON : Resets WDT

M9046 SM1046 SM802 Sampling trace OFF : Trace not in progress ON : Trace in progress • Switched on during sampling trace.

OFFSampling trace
  • Sampling trace is not executed unless SM801 is turned ON.
  • Sampling trace is suspended when SM801 goes OFF.

M9047 SM1047 SM801 Sampling trace preparations

suspended ONSampling trace started

Selection of number of characters output

OFFOutput until NULL code
  • When SM701 is OFF, characters up to NUL (00H) code are output.
  • When SM701 is ON, ASCII codes of 16 characters are output.

M9049 SM1049 SM701

encountered ON16 characters output

M9051 SM1051 CHG instruction execution disable

OFFEnabled ON : Disable
  • Switched ON to disable the CHG instruction.
  • Switched ON when program transfer is requested. Automatically switched OFF when transfer is complete.
  • When SM1052 is ON, the SEG instruction is executed as an I/O partial refresh instruction.
  • When SM1052 is OFF, the SEG instruction is executed as a 7-SEG display instruction.

M9052 SM1052 SEG instruction switch

OFF7SEG segment display ON : I/O partial refresh

M9054 SM1054 SM205 STEP RUN flag OFF : STEP RUN not in effect ON : STEP RUN in effect

  • Switched on when the RUN key switch is in STEP RUN position.

M9055 SM1055 SM808 Status latch completion flag

OFFNot completed ON : Completed
  • Turned on when status latch is completed. Turned off by reset instruction.

M9056 SM1056 Main side P, I set request

OFFOther than when P, I set
being requested ONP, I set being requested
  • Provides P, I set request after transfer of the other program (for example subprogram when main program is being run) is complete during run. Automatically switched off when P, I setting is complete.
OFFOther than when P, I set

M9057 SM1057 Sub side P, I set request

being requested ONP, I set being requested

M9058 SM1058 Main side P, I set completion

Momentarily ON at P, I set completion

  • Turned ON once when the P, I set has been completed, and then turned OFF again.

M9059 SM1059 Sub program P, I set completion

Momentarily ON at P, I set completion

  • Provides P, I set request after transfer of the other program (for example subprogram when main program is being run) is complete during run. Automatically switched off when P, I setting is complete.
OFFOther than when P, I set

M9060 SM1060 Sub program 2 P, I set request

being requested ONP, I set being requested

11 - 54 11 - 54

Show 4 more labels / short text on this page
ACPU Special · completed · Same as execution · QnA
Page 171 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 55 11 - 55
Page 171 · click to enlarge
Page 171

Special Relay List (Continued)

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

  • Provides P, I set request after transfer of the other program (for example subprogram when main program is being run) is complete during run. Automatically switched off when P, I setting is complete.
OFFOther than when P, I set

M9061 SM1061 Sub program 3 P, I set request

being requested ONP, I set being requested

Divided processing execution detection

OFFDivided processing not
  • Turned on when canvas screen transfer to AD57(S1)/AD58 is done by divided processing, and turned off at completion of divided processing.

M9065 SM1065 SM711

underway ONDuring divided processing

Divided processing request flag

OFFBatch processing ON : Divided processing
  • Turned on when canvas screen transfer to AD57(S1)/AD58 is done by divided processing.

M9066 SM1066 SM712

  • Turned ON to shorten the search time in the A8UPU/A8PUJ. (In this case, the scan time is extended by 10 %.)

A8UPU/A8PUJre quired search time

OFFRead time not shortened ON : Read time shortened

M9070 SM1070

The A8UPU/A8PUJ cannot be used in the QCPU/QnACPU special relays.

OFFEmpty spaces in

Communication request registration area BUSY signal

communication request registration area ON : No empty spaces in

  • Indication of communication enable/disable to remote terminal modules connected to the MELSECNET/MINI master, A2C or A52G.

M9081 SM1081 SM714

communication request registration area

  • It is set whether the error checks below are performed or not when the END instruction is processed (to set the END instruction processing time).
M9084 SM1084 Error check OFFError check executed ON : No error check
  • Check for breakage of fuse.
  • Collation check of I/O unit
  • Check of battery

M9091 SM1091 Instruction error flag

OFFNo error ON : Error
  • Set when an operation error detail factor is stored at SD1091, and remains set after normal status is restored.
  • After the head address of the required I/O module is set to SD251, switching SM251 on allows the I/O module to be changed in online mode. (One module is only allowed to be changed by one setting.)
  • To be switched on in the program or peripheral device test mode to change the module during CPU RUN. To be switched on in peripheral device test mode to change the module during CPU STOP.
  • RUN/STOP mode must not be changed until I/O module change is complete.

M9094 SM1094 SM251 I/O change flag OFF : Replacement ON : No replacement

Presence/absenc e of SFC program

OFFSFC programs not used ON : SFC programs used
  • Turned on if the SFC program is registered, and turned off if it is not.

M9100 SM1100 SM320

  • Should be turned on by the program if the SFC program is to be started. If turned off, operation output of the execution step is turned off and the SFC program is stopped.

M9101 SM1101 SM321 Start/stop SFC program

OFFSFC programs stop ON : SFC programs start
  • Selects the starting step when the SFC program is restarted using SM322. ON: All execution conditions when the SFC program stopped are cleared, and the program is started with the initial step of block 0. OFF: Started with the step of the block being executed when the program stopped.
  • Once turned on, the program is latched in the system and remains on even if the power is turned off. Should be turned off by the sequence program when turning on the power, or when starting with the initial step of block 0.

M9102 SM1102 SM322 SFC program start status

OFFInitial Start ON : Continue
  • Selects consecutive or step-by-step transfer of steps of which transfer conditions are established when all of the transfer conditions of consecutive steps are established. ON: Consecutive transfer is executed. OFF: One step per one scan is transferred.
OFFContinuous transition not

Presence/absenc e of continuous transition

M9103 SM1103 SM323

effective ONContinuous transition

11 - 55 11 - 55

Show 5 more labels / short text on this page
ACPU Special · QnA · QnA · QnA · effective
Page 172 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — M9199 SM1199
Page 172 · click to enlarge
Page 172

Special Relay List (Continued)

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

  • Set when consecutive transfer is not executed with consecutive transfer enabled. Reset when transfer of one step is completed. Consecutive transfer of a step can be prevented by writing an AND condition to corresponding SM324.

Continuous transition suspension flag

OFFWhen transition is

M9104 SM1104 SM324

completed ONWhen no transition

Step transition watchdog timer start (equivalent of D9108)

M9108 SM1108 SM90

Step transition watchdog timer start (equivalent of D9109)

M9109 SM1109 SM91

Step transition watchdog timer start (equivalent of D9110)

M9110 SM1110 SM92

Step transition watchdog timer start (equivalent of D9111)

OFFWatchdog timer reset ON : Watchdog timer reset

M9111 SM1111 SM93

  • Turned on when the step transfer monitoring timer is started. Turned off when the monitoring timer is reset.

Step transition watchdog timer start (equivalent of D9112)

M9112 SM1112 SM94

Step transition watchdog timer start (equivalent of D9113)

M9113 SM1113 SM95

Step transition watchdog timer start (equivalent of D9114)

M9114 SM1114 SM96

Active step sampling trace completion flag

OFFTrace started ON : Trace completed
  • Set when sampling trace of all specified blocks is completed. Reset when sampling trace is started.

M9180 SM1180 SM825

Active step sampling trace execution flag

OFFTrace not being executed ON : Trace execution under
  • Set when sampling trace is being executed. Reset when sampling trace is completed or suspended.

M9181 SM1181 SM822

  • Selects sampling trace execution enable/disable. ON: Sampling trace execution is enabled. OFF: Sampling trace execution is disabled. If turned off during sampling trace execution, trace is suspended.

Active step sampling trace permission

OFFTrace disable/suspend ON : Trace enable

M9182 SM1182 SM821

  • Selects the operation output when block stop is executed. ON: Retains the ON/OFF status of the coil being used by using operation output of the step being executed at block stop. OFF: All coil outputs are turned off. (Operation output by the SET instruction is retained regardless of the ON/OFF status of M9196.)

M9196 SM1196 SM325 Operation output at block stop

OFFCoil output OFF ON : Coil output ON

I/O numbers to be displayed

SM1197 SM1198

OFF OFF X/Y 0 to 7F0 M9197 SM1197

Switch between blown fuse and I/O verification error display

Switches I/O numbers in the fuse blow module storage registers (SD1100 to SD1107) and I/O module verify error storage registers (SD1116 to SD1123) according to the combination of ON/OFF of the SM1197 and SM1198.

ON OFF X/Y 800 to FF0

OFF ON X/Y 1000 to 17F0 M9198 SM1198

ON ON X/Y 1800 to 1FF0

Data recovery of online sampling trace/status latch

  • Recovers the setting data stored in the CPU at restart when sampling trace/status latch is executed.
  • SM1199 should be ON to execute again. (Unnecessary when writing the data again from peripheral devices.)
OFFData recovery disabled ON : Data recovery enabled

M9199 SM1199

11 - 56 11 - 56

ACPU Special · start · way

Page 173 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 57 11 - 57
Page 173 · click to enlarge
Page 173

Special Relay List (Continued)

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

ZNRD instruction (LRDP instruction for ACPU) reception (for master station)

  • Depends on whether or not the ZNRD (word device read) instruction has been received.
  • Used in the program as an interlock for the ZNRD instruction.
  • Use the RST instruction to reset.
OFFNot accepted ON : Accepted

M9200 SM1200

ZNRD instruction (LRDP instruction for ACPU) completion (for master station)

  • Depends on whether or not the ZNRD (word device read) instruction execution is complete.
  • Used as a condition contact for resetting SM1202 and SM1203 after the ZNRD instruction is complete.
  • Use the RST instruction to reset.
OFFNot completed ON : End

M9201 SM1201

ZNWR instruction (LWTP instruction for ACPU) reception (for master station)

  • Depends on whether or not the ZNWR (word device write) instruction has been received.
  • Used in the program as an interlock for the ZNWR instruction.
  • Use the RST instruction to reset.
OFFNot accepted ON : Accepted

M9202 SM1202

ZNWR instruction (LWTP instruction for ACPU) completion (for master station)

  • Depends on whether or not the ZNWR (word device write) instruction execution is complete.
  • Used as a condition contact to reset SM1202 and SM1203 after the ZNWR instruction is complete.
  • Use the RST instruction to reset.
OFFNot completed ON : End

M9203 SM1203

ZNRD instruction (LRDP instruction for ACPU) reception (for local station)

OFFNot completed ON : End

On indicates that the ZNRD instruction is complete at the local station.

M9204 SM1204

ZNWR instruction (LWTP instruction for ACPU) recep-tion (for local station)

M9205 SM1205

OFFNot completed ON : End

On indicates that the ZNWR instruction is complete at the local station.

Host station link parameter error

OFFNormal ON : Abnormal

Depends on whether or not the link parameter setting of the host is valid.

M9206 SM1206

Depends on whether or not the link parameter setting of the master station in tier two matches that of the master station in tier three in a three-tier system. (Valid only for the master stations in a three-tier system.)

M9207 SM1207

Link parameter check results

OFF : YES ON : NO

  • Depends on whether or not the B and W data controlled by higher-link master station (host station) is sent to lower-link local stations (tertiary stations).
  • When SM1208 is OFF .......B and W of host station is sent to tertiary stations.
  • When SM1208 is ON.........B and W of host station is not sent to tertiary stations.

Sets master station B and W transmission range (for lower link master stations only)

OFFTransmits to tier2 and

M9208 SM1208

tier 3 ONTransmits to tier2 only

Link parameter check command (for lower link master stations only)

  • Set to ON not to match B and W of the higher and lower links. (When SM1209 is ON, the link parameters of the higher and lower links are not checked.)
  • When SM1209 is OFF, the link parameters of the higher and lower links are checked.
OFFExecuting the check

M9209 SM1209

function ONCheck non-execution

M9210 SM1210

Link card error (for master station)

OFFNormal ON : Abnormal

Depends on presence or absence of the link card hardware error. Judged by the CPU.

Link module error (for local station use)

OFFNormal ON : Abnormal

Depends on presence or absence of the link card hardware error. Judged by the CPU.

M9211 SM1211

OFFOnline ON : Offline,station-to-station

Depends on whether the master station is online or offline or is in station-to-station test or self-loopback test mode.

M9224 SM1224 Link status

test, or self-loopback test

M9225 SM1225 Forward loop error OFF : Normal

ON : Abnormal Depends on the error condition of the forward loop line.

M9226 SM1226 Reverse loop error OFF : Normal

ON : Abnormal Depends on the error condition of the reverse loop line.

OFFNot being executed ON : Forward or reverse loop

Depends on whether or not the master station is executing a forward or a reverse loop test.

M9227 SM1227 Loop test status

OFFRUN or STEP RUN

Local station operation status

Depends on whether or not a local station is in STOP or PAUSE mode.

M9232 SM1232

status ONSTOP or PAUSE status

11 - 57 11 - 57

ACPU Special · QnA · test execution underway

Page 174 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — M9255 SM1255
Page 174 · click to enlarge
Page 174

Special Relay List (Continued)

Special Relay after Conversion

Special Relay for Modification

Name Meaning Details Applicable

Relay

Local station error detect status

OFFNo errors ON : Error detection

Depends on whether or not a local station has detected an error in another station.

M9233 SM1233

Local station, remote I/O station parameter error detect status

OFFNo errors ON : Error detection

Depends on whether or not a local or a remote I/O station has detected any link parameter error in the master station

M9235 SM1235

Local station, remote I/O station initial communications status

OFFNo communications ON : Communications

M9236 SM1236

Depends on the results of initial communication between a local or remote I/O station and the master station.

Local station, remote I/O station error

M9237 SM1237

OFFNormal ON : Abnormal

Depends on the error condition of a local or remote I/O station.

Local station, remote I/O station forward or reverse loop error

OFFNormal ON : Abnormal

Depends on the error condition of the forward and reverse loop lines of a local or a remote I/O station.

M9238 SM1238

OFFOnline ON : Offline, station-to-

Depends on whether the local station is online or offline, or is in station-to-station test or self-loopback test mode.

M9240 SM1240 Link status

stationtest, or self- loopback test

Forward loop line error

OFF : Normal ON : Abnormal Depends on the error condition of the forward loop line.

M9241 SM1241

Reverse loop line error

OFF : Normal ON : Abnormal Depends on the error condition of the reverse loop line.

M9242 SM1242

OFFLoopback not being

Depends on whether or not loopback is occurring at the local station.

M9243 SM1243

conducted ONLoopback implementation

M9246 SM1246 Data not received OFF : Reception

Depends on whether or not data has been received from the master station.

ONNo reception

M9247 SM1247 Data not received OFF : Reception

Depends on whether or not a tier three station has received data from its master station in a three-tier system.

ONNo reception
OFFReception ON : No reception

Depends on whether or not link parameters have been received from the master station.

M9250 SM1250

M9251 SM1251 Link relay OFF : Normal ON : Abnormal Depands on the data link condition at the local station.

OFFNot being executed ON : Forward or reverse loop

Depends on whether or not the local station is executing a forward or a reverse loop test.

M9252 SM1252 Loop test status

OFFRUN or STEP RUN

M9253 SM1253

Master station operation status

status ONSTOP or PAUSE status

Depends on whether or not the master station is in STOP or PAUSE mode.

Local station other than host station operation status

OFFRUN or STEP RUN

Depends on whether or not a local station other than the host is in STOP or PAUSE mode.

M9254 SM1254

status ONSTOP or PAUSE status

Local station other than host station error

OFFNormal ON : Abnormal

Depends on whether or not a local station other than the host is in error.

M9255 SM1255

11 - 58 11 - 58

Show 6 more labels / short text on this page
ACPU Special · underway · QnA · Loopback implementation · Parameters not received · test execution underway
Page 175 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 59 11 - 59
Page 175 · click to enlarge
Page 175

Special Relay List

(10) For redundant systems (Host system CPU information 1) for Q4AR only SM1510 to SM1599 are only valid for redundant systems. All off for standalone systems.

Number Name Meaning Explanation Set by (When Set)

ACPU M9

SM1500 Hold mode OFFNo-hold ON : Hold
  • Specifies whether or not to hold the output value when a range over occurs for the S.IN instruction range check. U New
SM1501 Hold mode OFFNo-hold ON : Hold
  • Specifies whether or not the output value is held when a range over occurs for the S.OUT instruction range check. U New
OFFRedundant

system backup mode, independent system ON : Redundant

  • Turns on when the operating mode is redundant system separate.

S (Each END) New

OFFSystem A fixed
mode ONPrevious control
  • Turns on when the start mode for a redundant system when the power is turned on is the previous control system latch mode.

SM1511 Start mode when

power supply is on

SM1512 Start mode when CPU

OFFInitial start ON : Hot start
  • Turns on when the CPU operation mode is hot start when the redundant system is started up. S (Initial) New

SM1513 Operation status when

OFFInitial start ON : Hot start
  • Turns on when the CPU operation mode is hot start when the redundant system is actually start up. S (Initial) New

SM1514 Operation mode when

OFFInitial start ON : Hot start
  • Turns on when the operation is hot start when the CPU operation is switched for a redundant system. S (Initial) New
SM1515 Output hold mode OFFOutput reset ON : Output hold
  • Turns on when the output mode during a stop error is output hold.

S (Each END) New

OFFControl system ON : Standby system
  • Turns on when the CPU operation system status is the standby system.
OFFPower supply
on startup ONOperation
  • Turns on when the CPU is started up by the operation system switch.
  • Reset using the user program.

S (Status change) /U New

SM1517 CPU startup status

Q4AR

  • When turned off when the tracking memory is in use during END, standby is executed until execution is possible.
  • When turned on when the tracking memory is being usedduring END, this is repeatedly executed until the next END
OFFBatch operation
mode ONCarryover mode

SM1520 SM1520 Block 1 SM1521 SM1521 Block 2 SM1522 SM1522 Block 3 SM1523 SM1523 Block 4 SM1524 SM1524 Block 5 SM1525 SM1525 Block 6 SM1526 SM1526 Block 7 SM1527 SM1527 Block 8 SM1528 SM1528 Block 9 SM1529 SM1529 Block 10 SM1530 SM1530 Block 11 SM1531 SM1531 Block 12 SM1532 SM1532 Block 13 SM1533 SM1533 Block 14 SM1534 SM1534 Block 15 SM1535 SM1535 Block 16 SM1536 SM1536 Block 17 SM1537 SM1537 Block 18 SM1538 SM1538 Block 19 SM1539 SM1539 Block 20 SM1540 SM1540 Block 21 SM1541 SM1541 Block 22 SM1542 SM1542 Block 23 SM1543 SM1543 Block 24 SM1544 SM1544 Block 25 SM1545

Data tracking transmission link specification

  • Specified the blocks to trigger when the data is transmitted by the data tracking instruction S. TRUCK.
OFFNo trigger ON : Trigger

1 Host system CPU information is stored.

11 - 59 11 - 59

Show 18 more labels / short text on this page
Applicable · SM1510 Operation mode · system separate mode · S (Initial) New · system latch mode · is started · CPU is started · CPU is switched · SM1516 Operation system · S (Status · change) New · status · system switch starup · SM1518 Tracking execution · mode · U New · U New · SM1545 Block 26
Page 176 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 60 11 - 60
Page 176 · click to enlarge
Page 176

Special Relay List (Continued)

Number Name Meaning Explanation Set by (When Set)

ACPU M9

CPU SM1546 SM1546 Block 27 SM1547 SM1547 Block 28 SM1548 SM1548 Block 29 SM1549 SM1549 Block 30 SM1550 SM1550 Block 31 SM1551 SM1551 Block 32 SM1552 SM1552 Block 33 SM1553 SM1553 Block 34 SM1554 SM1554 Block 35 SM1555 SM1555 Block 36 SM1556 SM1556 Block 37 SM1557 SM1557 Block 38 SM1558 SM1558 Block 39 SM1559 SM1559 Block 40 SM1560 SM1560 Block 41 SM1561 SM1561 Block 42 SM1562 SM1562 Block 43 SM1563 SM1563 Block 44 SM1564 SM1564 Block 45 SM1565 SM1565 Block 46 SM1566 SM1566 Block 47 SM1567 SM1567 Block 48 SM1568 SM1568 Block 49 SM1569 SM1569 Block 50 SM1570 SM1570 Block 51 SM1571 SM1571 Block 52 SM1572 SM1572 Block 53 SM1573 SM1573 Block 54 SM1574 SM1574 Block 55 SM1575 SM1575 Block 56 SM1576 SM1576 Block 57 SM1577 SM1577 Block 58 SM1578 SM1578 Block 59 SM1579 SM1579 Block 60 SM1580 SM1580 Block 61 SM1581 SM1581 Block 62 SM1582 SM1582 Block 63 SM1583

  • Specified the blocks to trigger when the data is transmitted by the data tracking instruction S. TRUCK.

Data tracking transmission link specification

OFFNo trigger ON : Trigger

U

OFFNormal ON : Switching
  • Turns on when could not be executed normally when the network module detects a network error and issues a switching request to the host system CPU.

SM1590 Switching status from

11 - 60 11 - 60

Show 7 more labels / short text on this page
Applicable · New Q4AR · SM1583 Block 64 · S (Error · the network module · unsuccessful · ocurrs)
Page 177 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 61 11 - 61
Page 177 · click to enlarge
Page 177

Special Relay List

(11) For redundant system (Other system CPU information 1) for Q4AR only SM1600 to SM1650 only valid for the CPU redundant system backup mode, so they cannot be refreshed during the separate mode. Either the backup mode or the separate mode is valid for the SM4651 to SM1699. SM1600 to SM1699 are all turned off for standalone system.

Set by (When Set)

ACPU M9 2

Number Name Meaning Explanation

  • Turns on if a error occurs in the diagnosis results. (Including external diagnosis)
  • Remains on even if returns to normal thereafter.
SM1600 Diagnosis error OFFNo error ON : Error

S (Each END) New

OFFNo self
diagnosis error ONSelf diagnosis
  • Turns on when an error occurs in the self-diagnosis results.
  • Remains on even if returns to normal thereafter.

S (Each END) New

SM1601 Self diagnosis error

OFFNo error
common information ONError common
  • Turns on when there is error common information and the SM1600 is on.

S (Each END) New

Q4AR

OFFNo error
individual information ONError individual
  • Turns on when there is error individual information and the SM1600 is on.

S (Each END) New

SM1653 STOP contact STOP status • Turns on when in the STOP status. S (Each END) New

SM1654 PAUSE contact PAUSE status • Turns on when in the PAUSE status. S (Each END) New

SM1655 STEP-RUN contact STEP-RUN status • Turns on when in the STEP-RUN status. S (Each END) New

1 Stores other system CPU diagnostic information and system information. 2 This shows the special relay(SM ) for the host system CPU.

11 - 61 11 - 61

Show 8 more labels / short text on this page
Applicable · error · SM1605 Error common · information · information · SM1616 Error individual · information · information
Page 178 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 62 11 - 62
Page 178 · click to enlarge
Page 178

(12) For redundant system (tracking) for Q4AR only

Either the backup mode or the second mode is valid for SM1700 to SM1799. All is turned off for standalone system.

Number Name Meaning Explanation Set by (When Set)

ACPU M9

OFFExecution not
possible ONExecution
  • Turns on when tracking is executed normally. S (status

SM1712 SM1712 Block 1 SM1713 SM1713 Block 2 SM1714 SM1714 Block 3 SM1715 SM1715 Block 4 SM1716 SM1716 Block 5 SM1717 SM1717 Block 6 SM1718 SM1718 Block 7 SM1719 SM1719 Block 8 SM1720 SM1720 Block 9 SM1721 SM1721 Block 10 SM1722 SM1722 Block 11 SM1723 SM1723 Block 12 SM1724 SM1724 Block 13 SM1725 SM1725 Block 14 SM1726 SM1726 Block 15 SM1727 SM1727 Block 16 SM1728 SM1728 Block 17 SM1729 SM1729 Block 18 SM1730 SM1730 Block 19 SM1731 SM1731 Block 20 SM1732 SM1732 Block 21 SM1733 SM1733 Block 22 SM1734 SM1734 Block 23 SM1735 SM1735 Block 24 SM1736 SM1736 Block 25 SM1737 SM1737 Block 26 SM1738 SM1738 Block 27 SM1739 SM1739 Block 28 SM1740 SM1740 Block 29 SM1741 SM1741 Block 30 SM1742 SM1742 Block 31 SM1743 SM1743 Block 32 SM1744 SM1744 Block 33 SM1745 SM1745 Block 34 SM1746 SM1746 Block 35 SM1747 SM1747 Block 36 SM1748 SM1748 Block 37 SM1749 SM1749 Block 38 SM1750 SM1750 Block 39 SM1751 SM1751 Block 40 SM1752 SM1752 Block 41 SM1753 SM1753 Block 42 SM1754 SM1754 Block 43 SM1755 SM1755 Block 44 SM1756 SM1756 Block 45 SM1757 SM1757 Block 46 SM1758 SM1758 Block 47 SM1759

Q4AR

OFFTransmission
  • One scan turns on when the corresponding data transmission has been completed.

Transmission trigger end flag

uncompleted ONTransmission

11 - 62 11 - 62

Show 9 more labels / short text on this page
Applicable · SM1700 Tracking execution · change) New · flag · possible · S (status · change) New · end · SM1759 Block 48
Page 179 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 63 11 - 63
Page 179 · click to enlarge
Page 179
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — 11.6 Special Relay List diagram (page 179)
Fig. 89 · 11.6 Special Relay List

CPU SM1760 SM1760 Block 49 SM1761 SM1761 Block 50 SM1762 SM1762 Block 51 SM1763 SM1763 Block 52 SM1764 SM1764 Block 53 SM1765 SM1765 Block 54 SM1766 SM1766 Block 55 SM1767 SM1767 Block 56 SM1768 SM1768 Block 57 SM1769 SM1769 Block 58 SM1770 SM1770 Block 59 SM1771 SM1771 Block 60 SM1772 SM1772 Block 61 SM1773 SM1773 Block 62 SM1774 SM1774 Block 63 SM1775

  • One scan turns on when the corresponding data transmission has been completed.

11 - 63 11 - 63

Page 180 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 64 11 - 64
Page 180 · click to enlarge
Page 180

11.7 Special Register List

The special registers, SD, are internal registers with fixed applications in the PLC. For this reason, it is not possible to use these registers in sequence programs in the same way that normal registers are used. However, data can be written as needed in order to control the CPU modules and remote I/O modules. Data stored in the special registers are stored as BIN values if no special designation has been made to the contrary. The headings in the table that follows have the following meanings.

  • Item Function of Item Number
  • Indicates special register number Name
  • Indicates name of special register Meaning
  • Indicates contents of special register Explanation
  • Discusses contents of special register in more detail
  • Indicates whether the relay is set by the system or user, and, if it is set by the system, when setting is performed. <Set by>

S : Set by system U : Set by user (sequence programs or test operations from GX Developer) S/U : Set by both system and user

Set by (When set)

Indicated only for registers set by system Each END : Set during each END processing Initial : Set only during initial processing (when power supply is turned

ON, or when going from STOP to RUN) Status change : Set only when there is a change in status Error : Set when error occurs Instruction execution : Set when instruction is executed Request : Set only when there is a user request (through SM, etc.)

  • Indicates corresponding special register in ACPU (D9 )(Change and notation when there has been a change in contents)
  • Items indicated as "New" have been newly added for High Performance model QCPU/QnACPU
  • Indicates the corresponding CPU module type name. +Rem: Can be applied to all CPU module types and MELSECNET/H remote I/O modules. : Can be applied to all types of CPU module QCPU: Can be applied to High Performance model QCPU. QnA: Can be applied to QnA series and Q2ASCPU series Remote: Can be applied to the MELSECNET/H remote I/O modules. Each CPU type name: Can be applied only to the specific CPU module. (e.g. Q4ARCPU, Q3ACPU)
  • For details on the following items, refer to the following manuals:
  • Networks
  • For Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)
  • For Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)
  • For QnA/Q4AR MELSECNET/10 Network System Reference Manual
  • SFC QCPU(Q mode)/QnACPU Programming Manual (SFC)
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — 11.7 Special Register List diagram (page 180)
Fig. 90 · 11.7 Special Register List

POINT (1) SD1200 to SD1255 are used for QnACPU.

These relays are vacant with QCPU. (2) Special register SD1500 and later are dedicated for Q4ARCPU.

11 - 64 11 - 64

Corresponding ACPU D9 · Corresponding CPU

Page 181 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 65 11 - 65
Page 181 · click to enlarge
Page 181

Special Register List

(1) Diagnostic Information

Number Name Meaning Explanation

ACPU D9

  • Error codes for errors found by diagnosis are stored as BIN data.
  • Contents identical to latest fault history information. S (Error) D9008 format
  • Year (last two digits) and month that SD0 data was updated is stored as BCD 2-digit code.

SD1

B15 B7 B0 B8 to to (Example) : October, 1995 H9510

Year (0 to 99) Month (1 to 12)

  • The day and hour that SD0 was updated is stored as BCD 2-digit code.

Clock time for diagnosis error occurrence

Clock time for diagnosis error occurrence

B15 B7 B0 B8 to to (Example) : 10 a.m. on 25th H2510

SD2

Day (1 to 31) Hour (0 to 23)

  • The minute and second that SD0 data was updated is stored as BCD 2-digit code.

B15 B7 B0 B8 to to (Example) : 35 min. 48 sec. (past the hour) H3548

SD3

Minutes (0 to 59)

Seconds (0 to 59)

Category codes which help indicate what type of information is being stored in the common information areas (SD5 through SD15) and the individual information areas (SD16 through SD26) are stored here.

B15 B7 B0 B8 to to

  • The common information category codes store the following codes: 0 : No error 1 : Unit/module No./ PLC No./Base No. 2 : File name/Drive name 3 : Time (value set) 4 : Program error location 5 : Switch cause (for Q4AR only) : For a multiple PLC system, the module number or PLC

Error information category code

SD4

number is stored depending on the error that occurred. (Refer to the corresponding error code for which number has been stored.) PLC No. 1: 1, PLC No. 2: 2, PLC No. 3: 3, PLC No. 4: 4 • The individual information category codes store the following codes: 0 : No error 1 : (Open) 2 : File name/Drive name 3 : Time (value actually measured) 4 : Program error location 5 : Parameter number 6 : Annunciator number 7 : Check instruction malfunction number

11 - 65 11 - 65

Show 15 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · SD0 Diagnostic errors · Diagnosis error code · change · S (Error) New · Individual information · Common information · +Rem · category codes · category codes · Error information categories · S (Error) New
Page 182 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 66 11 - 66
Page 182 · click to enlarge
Page 182

Special Register List (Continued)

Number Name Meaning Explanation

ACPU D9

  • Common information corresponding to the error codes (SD0) is stored here.
  • The following five types of information are stored here:

SD5

1 Slot No.

Meaning Slot No./PLC No./Base No. 1 2

SD6

SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15

I/O No.

SD7

SD8

*1: For a multiple PLC system, the slot number or PLC number is stored depending on the error that occurred. Slot 0 in the multiple PLC system is the one on the slot on the right of the rightmost CPU module. (Refer to the corresponding error code for which number has been stored.) PLC No. 1: 1, PLC No. 2: 2, PLC No. 3: 3, PLC No. 4: 4 *2: If a fuse blown or I/O verify error occurred in the module loaded in the MELSECNET/H remote I/O station, the network number is stored into the upper 8 bits and the station number into the lower 8 bits. Use the I/O No. to check the module where the fuse blown or I/O verify error occurred.

SD9

SD10

S (Error) New +Rem

SD11

SD12

2 File name/Drive name

File name= ABCDEFGH. IJK

SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15

B15 to B8 B7 to B0

42H(B) 41H(A) 44H(D) 43H(C) 46H(F) 45H(E) 48H(H) 47H(G) 49H(I) 2EH(.) 4BH(K) 4AH(J)

SD13

File name (ASCII code8 characters)

2E H (.)

SD14

(ASCII code3 characters)

(Continued to next page)

SD15

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — SD15 diagram (page 182)
Fig. 91

SD10 SD11 Higher8 bits Lower8 bits Higher8 bits Extension name File type

51H 50H 41H QPA Parameters 51H 50H 47H QPG Sequence program/SFC program 51H 43H 44H QCD Device comment 51H 44H 49H QDI Device initial value 51H 44H 52H QDR File register 51H 44H 53H QDS Simulation data 51H 44H 4CH QDL Local device 51H 54H 53H QTS Sampling trace data (For QnA) 51H 54H 4CH QTL Status latch data (For QnA) 51H 54H 50H QTP Program trace data (For QnA) 51H 54H 52H QTR SFC trace file 51H 46H 44H QFD Trouble history data

11 - 66 11 - 66

Show 14 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · Number · (Vacant) · Error common information · Error common information · (Example) · Number · Meaning · Drive · Extension · (Vacant)
Page 183 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD15
Page 183 · click to enlarge
Page 183

Special Register List (Continued)

Number Name Meaning Explanation

ACPU D9

3 Time (value set)

SD5

Meaning Time1 µ s units (0 to 999 µ s)

SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15

Time1 ms units (0 to 65535 ms)

SD6

SD7

4 Program error location

SD5 SD6 SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15

S (Error) New +Rem

File name (ASCII code8 characters)

SD8

2E H (.)

(ASCII code3 characters)

Pattern Block No. Step No./transition No. Sequence step No. (L) Sequence step No. (H)

SD9

4 Contents of pattern data

0 1 2 3 4 15 14 to

SD10

0 to

SFC block designation present (1)/absent (0)

SFC step designation present (1)/absent (0) SFC transition designation present (1)/absent (0)

SD11

Meaning Switch cause (0automatic switch/ 1: manual switch)

SD5

SD12

Switch direction (0:standby system to control system/ 1: control system to standby system)

SD6

SD7 SD8 SD9 SD10 SD11 SD12 SD13 SD14 SD15

SD13

S (Error) New Q4AR

5 Tracking flag contents Shows whether or not the tracking data is valid.

SD14

0 1 2 3 4 15 14 to

0 to

Invalid work data invalid (0) /valid (1)

System data (SFC active step information) invalid (0)/ valid (1) Switching cause invalid (0)/ valid (1)

SD15

11 - 67 11 - 67

Show 20 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · (Continued) · Number · (Vacant) · Number · Meaning · Extension · (Bit number) · Error common information · Error common information · (Not used) · 5 Switch cause · Number · Tracking flag 5 · (Vacant) · (Bit number) · (Not used)
Page 184 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD26
Page 184 · click to enlarge
Page 184

Special Register List (Continued)

Number Name Meaning Explanation

ACPU D9

  • Individual information corresponding to error codes (SD0) is stored here.
  • There are the following six different types of stored information.

SD16

1 File name/Drive name

File name= ABCDEFGH. IJK

SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26

B15 to B8 B7 to B0

42H(B) 41H(A) 44H(D) 43H(C) 46H(F) 45H(E) 48H(H) 47H(G) 49H(I) 2EH(.) 4BH(K) 4AH(J)

SD17

File name (ASCII code8 characters)

2E H (.)

(ASCII code3 characters)

SD18

2 Time (value actually measured)

Meaning Time1 µ s units (0 to 999 µ s)

SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26

Time1 ms units (0 to 65535 ms)

SD19

SD20

3 Program error location

SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26

File name (ASCII code8 characters)

SD21

2E H (.)

S (Error) New +Rem

(ASCII code3 characters)

Pattern Block No. Step No./transition No.

Sequence step No. (L) Sequence step No. (H)

SD22

Contents of pattern data

0 1 2 3 4 15 14 to

0 to

SFC block designation present (1)/absent (0)

SFC step designation present (1)/absent (0) SFC transition designation present (1)/absent (0)

SD23

5 Annunciator number / CHK instruction malfunction number

6 Intelligent function module parameter error (for QCPU only)

SD24 4 Parameter number

Meaning Parameter No.

SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26

SD16 SD17 SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26

No.

SD16 SD17

Parameter No. Error code for intelligent function module

SD25

SD18 SD19 SD20 SD21 SD22 SD23 SD24 SD25 SD26

6 For details of the parameter numbers, refer to the user's manual of the CPU module used.

SD26

11 - 68 11 - 68

Show 27 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · (Example) · Number · Meaning · Drive · Extension · (Vacant) · Number · (Vacant) · Number · Meaning · Error individual information · Error individual information · Extension · (Bit number) · (Not used) · Number · Number · Meaning · Number · Meaning · (Vacant) · (Vacant) · (Vacant)
Page 185 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9124
Page 185 · click to enlarge
Page 185

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD50 Error reset Error code that performs error reset • Stores error code that performs error reset U New +Rem

  • All corresponding bits go ON when battery voltage drops.
  • Subsequently, these remain ON even after battery voltage has been returned to normal.

B4 B3 B0 B2 B1

Bit pattern indicating where battery voltage drop occurred

CPU module battery error

SD51 Battery low latch

Memory card A alarm Memory card A error Memory card B alarm Memory card B error

  • When High Performance model QCPU is used, this flag is always OFF because memory card B is used as standard memory.
  • Same configuration as SD51 above
  • Subsequently, goes OFF when battery voltage is restored to normal.
  • When High Performance model QCPU is used, this flag is always OFF because memory card B is used as standard memory.

Bit pattern indicating where battery voltage drop occurred

  • Every time the input voltage falls to or below 85% (AC power)/65% (DC power) of the rating during calculation of the CPU module, the value is incremented by 1 and stored in BIN code.

Number of times for AC/DC DOWN

SD53

S (Error) D9005 +Rem

1 The relevant station bit goes ON when any of the Installed MINI (-S3) X(n+0)/X(n+20), X(n+6)/(n+26), X(n+7)/(n+27) or X(n+8)/X(n+28) goes ON.

2 Goes ON when communications between the installed MINI (-S3) and the CPU are not possible. B15 B8 B9 B0

SD54 MINI link errors

S (Error) D9004 format

module

Information on Information on 1 2

SD60 Blown fuse number

Number of module with blown fuse

  • Value stored here is the lowest station I/O number of the module with the blown fuse. S (Error) D9000

I/O module verification error number

I/O module verification error module number

  • The lowest I/O number of the module where the I/O module verification number took place. S (Error) D9002

SD61

Annunciator number • The first annunciator number to be detected is stored here. S (Instruction

D9009

Number of annunciators • Stores the number of annunciators searched. S (Instruction

SD63 Number of annunciators

D9124

11 - 69 11 - 69

Show 20 more labels / short text on this page
Corresponding · Corresponding · 0< > ------------------- · S (Error) New · SD52 Battery low · S (Error) New · AC/DC DOWN detection · Error detection state · change QnA · 8th · 1st · 8th · 1st · module · module · module · +Rem · SD62 Annunciator number · execution) · execution)
Page 186 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD105
Page 186 · click to enlarge
Page 186

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

When F goes ON due to OUT F or SET F , the F numbers which

SD64 D9125

go progressively ON from SD64 through SD79 are registered. F numbers turned OFF by RST F are deleted from SD64 to SD79,

SD65 D9126

and are shifted to the data register following the data register where the deleted F numbers had been stored. Execution of the LEDR instruction shifts the contents of SD64 to

SD66 D9127

SD67 D9128

SD79 up by one. (This can also be done by using the INDICATOR RESET switch on the of the Q3A/Q4ACPU.) After 16 annunciators have been detected, detection of the 17th will not be stored from SD64 through SD79.

SD68 D9129

SD69 D9130

SET

SET

SET F99

RST

SET F15

SET

SET F65

SET

SET F110

SET F151

SET F210LEDR

SD70 D9131

F50

F25

F25

F70

F38

Table of detected annunciator numbers

SD71 D9132

SD62 0 50 99 ...(Number detected)

SD63 0 1 2 3 2 3 4 5 6 7 8 9 8

...(Number of annunciators detected)

0 50 99 SD64

SD65

0 0 25 25 99 15

SD66

0 0 0 99 0 15 70

SD67

0 70 65

SD68

0 65 38

SD69

0 38 110

SD70

0 110 110 110 151

SD71

0 151 210

SD72

0 210

SD73

0

SD74

0

SD75

0

SD76

0

SD77

0

SD78

0

SD79

0

SD79

SD80 CHK number CHK number • Error codes detected by the CHK instruction are stored as BCD code.

  • F numbers which go ON at step transition watchdog timer set value and watchdog timer over errors.

SD90 Corresponds to SM90 D9108

SD91 Corresponds to SM91 D9109

SD92 Corresponds to SM92 D9110

B15 B7 B0 B8

Step transition watchdog timer setting value (Enabled only when SFC program exists)

SD93 Corresponds to SM93 D9111

F number for timer set value and time over error

Timer time limit setting (1 to 255 s: (1-s units)) • Timer is started by turning SM90 through SM99 ON during active step, and if the transition conditions for the relevant steps are not met within the timer limits, the designated annunciator (F) will go ON.

F number setting (0 to 255)

SD94 Corresponds to SM94 D9112

U

SD95 Corresponds to SM95 D9113

SD96 Corresponds to SM96 D9114

SD97 Corresponds to SM97 New

SD98 Corresponds to SM98 New

SD99

Stores the preset transmission speed when GX Developer is used.

CH1 transmission speed setting (RS-232)

3. 300bps, 6 : 600bps, 24 : 2400bps, 48 : 4800bps 96 : 9600bps, 192 : 19.2kbps, 384 : 38.4kbps 576 : 57.6kbps, 1152 : 115.2kbps S New QCPU Remote

SD105

11 - 70 11 - 70

Show 20 more labels / short text on this page
Corresponding · Corresponding · Annunciator detection number · S (Instruction · SD72 New · execution) · SD73 New · SD74 New · SD75 New · 0 0 151 · (Number detected) · SD76 New · SD77 New · SD78 New · New · S (Instruction · New · execution) · Corresponds to SM99 · New
Page 187 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 71 11 - 71
Page 187 · click to enlarge
Page 187

Special Register List

(2) System information

Number Name Meaning Explanation Set by (When set)

ACPU D9

  • The switch status of the remote I/O module is stored in the following format.

B15 B4 B3 B0

S (Always) New Remote

1 Vacant 1 Remote I/O module switch status Always 1: STOP

  • The CPU module switch status is stored in the following format: B15 B12B11 B8 B7 B4 B3 B0

Vacant 3 2 1

1. CPU switch status 0: RUN 1: STOP 2: L.CLR
2. Memory card switch Always OFF
3. DIP switch B8 through BC correspond to SW1 through SW5 of system setting switch 1. 0: OFF, 1: ON BD through BF are vacant.

SD200 Status of switch

Status of CPU switch

  • The CPU module switch status is stored in the following format: B15 B12B11 B8 B7 B4 B3 B0

Vacant 3 2 1

1. CPU key Status of switch
0. RUN 1 : STOP 2 : L.CLR
2. Memory cards switch B4 corresponds to card A, and B5 corresponds to card B OFF at 0; ON at 1
3. DIP switch B8 through B12 correspond to SW1 through SW5 of system setting switch 1. B14 and B15 correspond to SW1 and SW2 of system setting switch 2, respectively. OFF at 0; ON at 1

11 - 71 11 - 71

Show 8 more labels / short text on this page
Corresponding · Corresponding · S(Every · END processing) · New QCPU · S(Every · END processing) · New QnA
Page 188 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD206
Page 188 · click to enlarge
Page 188

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

  • The following bit patterns are used to store the statuses of the LEDs on the CPU module:
  • 0 indicates OFF, 1 ON, and 2 flicker. B15 B12B11 B8 B7 B4 B3 B0

8 3 2 1 4 5 6 7

1 : RUN

5 : BOOT

2 : ERROR

6. Vacant

3 : USER

7. Vacant

4 : BAT.ALARM

8. MODE Bit patterns for MODE 0: OFF, 1: Green, 2: Orange

SD201 LED status Status of CPU-LED

  • Information concerning which of the following status the LEDs on the CPU module are in is stored in the following bit patterns:
  • 0 is off, 1 is on, and 2 is flicker B15 B12B11 B8 B7 B4 B3 B0

8 3 2 1 4 5 6 7

5 : BOOT

1 : RUN

2 : ERROR

6. CARD A (Memory card)

3 : USER

7. CARD B (Memory card)

4 : BAT.ALARM

8. Vacant

Bit pattern of LED that is turned off

  • Stores bit patterns of LEDs turned off (Only USER and BOOT enabled)
  • Turned off at 1, not turned off at 0 U New QnA
  • The operating status of the remote I/O module is stored in the following format.

B15 B4 B3 B0

S (Always) New Remote

1 Vacant 1 Remote I/O module operating status Always 2: STOP

  • The CPU module operating status is stored as indicated in the following figure:

B15 B12B11 B8 B7 B4 B3 B0

Operating status of CPU

Operating status of CPU

SD203

1. Operating status of CPU 0 :RUN 1 :STEP-RUN 2 :STOP 3 :PAUSE
2. STOP/PAUSE cause 0 :Switch 1 :Remote contact 2 : Remote operation from the GX Developer or Serial Communication. 3 :Internal program instruction
0. Test not yet executed 1: During X device test 2: During Y device test 3: During X/Y device test

Device test execution type

  • Set when the device test mode is executed on GX Developer. S (Request) New Remote

SD206

11 - 72 11 - 72

Show 11 more labels / short text on this page
Corresponding · Corresponding · S (Status · change) New QCPU · S (Status · change) New QnA · SD202 LED off · S (Every · D9015 format · END processing) · change
Page 189 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 73 11 - 73
Page 189 · click to enlarge
Page 189

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD207 Priorities 1 to 4 D9038

  • When error is generated, the LED display (flicker) is made according to the error number setting priorities.
  • The setting areas for priorities are as follows: B15 B12B11 B8 B7 B4 B3 B0 Priority 4 Priority 3 Priority 2 Priority 1 SD207

SD208 Priorities 5 to 8 D3039 format

Priority 8 Priority 7 Priority 6 Priority 5 SD208

LED display priority ranking Priorities 9 to 10

Priority 10 Priority 9 SD209 Default Value SD207=H4321 SD208=H8765 SD207=H00A9 • No display is made if "0" is set. However, even if "0" has been set, information concerning CPU module operation stop (including parameter settings) errors will be indicated by the LEDs without conditions.

U

SD209

  • The year (last two digits) and month are stored as BCD code at SD210 as shown below:

Example :

SD210 Clock data Clock data (year, month)

B15 B12B11 B8 B7 B4 B3 B0

to

D9025

  • The day and hour are stored as BCD code at SD211 as shown below:

B15 B12B11 B8 B7 B4 B3 B0

to

Example :

SD211 Clock data Clock data (day, hour)

D9026

31st, 10 a.m. H3110

  • The minutes and seconds (after the hour) are stored as BCD code at SD212 as shown below:

Clock data (minute, second)

ExampleB15 B12B11 B8 B7 B4 B3 B0 to to to to

35 min., 48 sec. (after the hour) H3548

D9027

  • Stores the year (two digits) and the day of the week in SD213 in the BCD code format as shown below.

B15 B12B11 B8 B7 B4 B3 B0 to

Example :

Clock data (higher digits of year, day of week)

S/U (Request) D9028 QCPU Remote

Higher digits of year (0 to 99)

  • The day of the week is stored as BCD code at SD213 as shown below:

B15 B12B11 B8 B7 B4 B3 B0

to

Example :

Clock data (day of week)

S/U (Request) D9028 QnA

11 - 73 11 - 73

Show 31 more labels / short text on this page
Corresponding · Corresponding · change · New · July 1993 H9307 · Year Month · S/U (Request) · +Rem · Day Hour · SD212 Clock data · Minute Second · Friday H0005 · Day of week · Sunday · Monday · Tuesday · Wednesday · Thursday · Friday · Saturday · SD213 Clock data · Friday H0005 · Day of week · Sunday · Always set "0" · Monday · Tuesday · Wednesday · Thursday · Friday · Saturday
Page 190 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 74 11 - 74
Page 190 · click to enlarge
Page 190

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD220

  • LED display ASCII data (16 characters) stored here.

to B15 B8 to B7 B0

SD221

SD220

15th character from the right

16th character from the right

SD222

SD221

13th character from the right

14th character from the right

SD223

SD222

11th character from the right

12th character from the right

S (When changed) New

SD224

SD223

9th character from the right

10th character from the right

SD224

7th character from the right

8th character from the right

SD225

SD225

5th character from the right

6th character from the right

SD226

SD226

3rd character from the right

4th character from the right

SD227

1st character from the right

2nd character from the right

SD227

SD240 Base mode 0Automatic mode 1: Detail mode • Stores the base mode. S (Initial) New

No. of extension bases

0. Main base only 1 to 7: No. of extension bases
  • Stores the maximum number of the extension bases unit being installed. S (Initial) New

SD241

B1 B2 B7

B0

Base type differentiation 0QA B is installed (A mode) 1: Q B is installed (Q mode)

SD242 A/Q base differentiation

When no expansion base is installed, the value is fixed to 0.

B15 B12 B11 B8 B7 B4 B3 B0

SD243

SD243 Expansion 3 Expansion 2 Expansion 1 Main

No. of base slots No. of base slots

  • As shown above, each area stores the number of slots being installed.

Expansion 7 Expansion 6 Expansion 5 Expansion 4 SD244

SD244

SD250 Loaded maximum I/O

Loaded maximum I/O No.

  • When SM250 goes from OFF to ON, the upper 2 digits of the final I/O number plus 1 of the modules loaded are stored as BIN values.

END)

Head I/O number for replacement

Head I/O No. for module replacement

Q2A (S1)

  • Stores the upper two digits of the first I/O number of an I/O module that is removed/replaced in the online status.(default value : 100 H ) U D9094

Q3A Q4A Q4AR

SD251

SD253 RS-422 baud rate RS-422 baud rate • Stores baud rate of RS-422.

0. 9600bps 1: 19.2kbps 2: 38.4kbps S (When changed) New QnA

SD254 Number of modules installed • Indicates the number of modules installed on MELSECNET/10 (H).

SD255 I/O No. • MELSECNET/10 (H) I/O number of first module installed

SD256 Network No. • MELSECNET/10 (H) network number of first module installed

Informa- tion from 1st module

SD257 Group number • MELSECNET/10 (H) group number of first module installed

SD258 Station No. • MELSECNET/10 (H) station number of first module installed

MELSECNET /10 (H) information

  • In the case of standby stations, the module number of the standby station is stored. (1 to 4)

SD259

Information from 2nd module • Configuration is identical to that for the first module.

Information from 3rd module • Configuration is identical to that for the first module.

Information from 4th module • Configuration is identical to that for the first module.

11 - 74 11 - 74

Show 21 more labels / short text on this page
Corresponding · Corresponding · LED display data · Display indicator data · Fixed to 0 · to · Main base unit · 1st expansion base · QCPU Remote · 2nd expansion base · S (Initial) New · to · 7th expansion base · S (Initial) New · S (Request · New +Rem · Standby informa- tion · S (Initial) New · SD260 to SD264 · SD265 to SD269 · SD270 to SD274
Page 191 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 75 11 - 75
Page 191 · click to enlarge
Page 191

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

1 When Xn0 of the installed CC-Link goes ON, the bit corresponding to the station switches ON. 2 When either Xn1 or XnF of the installed CC-Link switch OFF, the bit corresponding to the station switches ON. 3 Switches ON when the CPU module cannot communicate with the installed CC-Link.

Information of 1 Information of 2 Information of 3

S (Error) New QCPU Remote

B3 B4 B7 B8 B11 B12 B15

B0

SD280 CC-Link error Error detection status

The above module numbers n are in order of the head I/O Nos. (However, the modules without parameter setting are not counted in.)

1 When Xn0 of the installed CC-Link goes ON, the bit corresponding to the station switches ON. 2 When either Xn1 or XnF of the installed CC-Link switch OFF, the bit corresponding to the station switches ON. 3 Switches ON when the CPU module cannot communicate with the installed CC-Link.

S (Error) New QnA

B15 B8 B9 B0

module ...

Information of 1 Information of 2

Number of points allocated for X

SD290

  • Stores the number of points currently set for X devices

Number of points allocated for Y

SD291

  • Stores the number of points currently set for Y devices

Number of points allocated for M

SD292

  • Stores the number of points currently set for M devices

Number of points allocated for L

SD293

  • Stores the number of points currently set for L devices

Number of points allocated for B

SD294

  • Stores the number of points currently set for B devices +Rem

Number of points allocated for F

SD295

Device allocation (Same as parameter contents)

  • Stores the number of points currently set for F devices

Number of points allocated for SB

SD296

  • Stores the number of points currently set for SB devices +Rem

Number of points allocated for V

SD297

  • Stores the number of points currently set for V devices

Number of points allocated for S

SD298

  • Stores the number of points currently set for S devices

Number of points allocated for T

SD299

  • Stores the number of points currently set for T device

Number of points allocated for ST

SD300

  • Stores the number of points currently set for ST devices

Number of points allocated for C

SD301

  • Stores the number of points currently set for C devices

11 - 75 11 - 75

Show 17 more labels / short text on this page
Corresponding · Corresponding · Vacant · 1st module · 2nd module · 3rd module · 4th module · to to · 8th · 1st · 8th · 1st · module · module · module · +Rem · S (Initial) New
Page 192 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 76 11 - 76
Page 192 · click to enlarge
Page 192

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD302 Number of points allocated for D • Stores the number of points currently set for D devices

Device allocation (Same as parameter contents) Number of points allocated for SW • Stores the number of points currently set for SW devices

SD303 Number of points allocated for W • Stores the number of points currently set for W devices

S (Initial) New +Rem

SD304

Reserves the designated time for communication processing with GX Developer or other units. The greater the value is designated, the shorter the response time for communication with other devices (GX Developer, serial communication units) becomes. Setting range: 1 to 100 ms If the designated value is out of the range above, it is assumed to no setting.

Time reserved for communicat ion processing

Time reserved for communication processing

SD315

SD340 No. of modules installed • Indicates the number of modules installed on Ethernet.

SD341 I/O No. • Ethernet I/O No. of the 1st module installed.

SD342 Network No. • Ethernet network No. of the 1st module installed.

SD343 Group No. • Ethernet group No. of the 1st module installed.

SD344 Station No. • Ethernet station No. of the 1st module installed.

Informa- tion of 1st module

  • Vacant (With High Performance model QCPU, the Ethernet IP address of the 1st module is stored in buffer memory.)

SD345 to SD346 Vacant

  • Vacant (With High Performance model QCPU, the Ethernet error code of the 1st module is read with the ERRORRD instruction.)

SD347

Information from 2nd module • Configuration is identical to that for the first module.

Information from 3rd module • Configuration is identical to that for the first module.

Information from 4th module • Configuration is identical to that for the first module.

SD340 No. of modules installed • Indicates the number of modules installed on Ethernet.

SD341 I/O No. • Ethernet I/O No. of the 1st module installed.

SD342 Network No. • Ethernet network No. of the 1st module installed.

SD343 Group No. • Ethernet group No. of the 1st module installed.

Informa- tion of 1st module

SD344 Station No. • Ethernet station No. of the 1st module installed.

SD345 to SD346 IP address • Ethernet IP address of the 1st module installed.

SD347

Error code • Ethernet error code of the 1st module installed.

Information from 2nd module • Configuration is identical to that for the first module.

Information from 3rd module • Configuration is identical to that for the first module.

Information from 4th module • Configuration is identical to that for the first module. S (Initial) New

B1 B2 B3 B4 B5 B6 B7 B8 B15

B0

Instruction reception status of channel 1 Instruction reception status of channel 2

Ethernet instruction reception status

Instruction reception status of channel 3 Instruction reception status of channel 4 Instruction reception status of channel 5 Instruction reception status of channel 6 Instruction reception status of channel 7 Instruction reception status of channel 8

Instruction reception status of 1st module

SD380

ONReceived (Channel is used.) OFF: Not received (Channel is not used.)

11 - 76 11 - 76

Show 21 more labels / short text on this page
Corresponding · Corresponding · U (END processing) · New QCPU · S (Initial) New · Ethernet information · QCPU Remote · Vacant · SD348 to SD354 · SD355 to SD361 · S (Initial) New · SD362 to SD368 · S (Initial) New · Ethernet information · SD348 to SD354 · QnA · SD355 to SD361 · SD362 to SD368 · 0 0 to · Not used · S (Initial) New
Page 193 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 77 11 - 77
Page 193 · click to enlarge
Page 193

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD381 Information from 2nd module • Configuration is identical to that for the first module.

Ethernet instruction reception status Information from 4th module • Configuration is identical to that for the first module.

SD382 Information from 3rd module • Configuration is identical to that for the first module.

SD383

  • Stores the internal system software version in ASCII code.

The software version is stored in the lower byte position. The data in the higher byte position is indefinite.

Higher byte Lower byte

Internal system software version

For version "A", for example, "41H" is stored.

version indicated by the version symbol printed on the case.

SD395 Multiple PLC number

  • In a multiple PLC system configuration, the PLC number of the host CPU is stored. PLC No. 1: 1, PLC No. 2: 2, PLC No. 3: 3, PLC No. 4: 4

S (Initial) New QCPU function

Ver. B or later

(3) System clocks/counters

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD412 1 second counter

Number of counts in 1-second units

  • Following programmable controller CPU module RUN, 1 is added each second
  • Count repeats from 0 to 32767 to -32768 to 0

S (Status change) D9022

2n second clock setting

2n second clock units

  • Stores value n of 2n second clock (Default is 30)
  • Setting can be made between 1 and 32767 U New

SD414

  • SD415 2nms clock setting 2nms clock units
  • Stores value n of 2nms clock (Default is 30)
  • Setting can be made between 1 and 32767 U New QCPU
  • Incremented by 1 for each scan execution after the CPU module is set to RUN.
  • Count repeats from 0 to 32767 to -32768 to 0

Number of counts in each scan

  • Incremented by 1 for each scan execution after the CPU module is set to RUN.
  • Count repeats from 0 to 32767 to -32768 to 0
  • Used only for low speed execution type programs

Low speed scan counter

Number of counts in each scan

SD430

: Not counted by the scan in an initial execution type program.

11 - 77 11 - 77

Show 16 more labels / short text on this page
Corresponding · Corresponding · S (Initial) New · QnA · SD392 Software version · S (Initial) D9060 · Multiple PLC number · Corresponding · Corresponding · S(Every · SD420 Scan counter · END processing) · New · S(Every · END processing) · New
Page 194 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD541
Page 194 · click to enlarge
Page 194

Special Register List

(4) Scan information

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD500 Execution program No.

Execution type of program being executed

  • Program number of program currently being executed is stored as BIN value.

File name of low speed execution in progress

  • Program number of low speed program currently being executed is stored as BIN value.
  • Enabled only when SM510 is ON.

SD510 Low speed program No.

  • Current scan time is stored into SD520, SD521. (Measurement is made in 100 µ s increments.) SD520: Place of ms is stored (storage range: 0 to 65535) SD521: Place of µ s is stored (storage range: 0 to 900) Example: Current scan time 23.6ms is stored as indicated

SD520 Current scan time (ms unit)

Current scan time (µs unit)

SD521

below. SD520 = 23 SD521 = 600

SD522 Initial scan time (ms unit)

  • Scan time of initial execution program is stored into SD522, SD523. (Measurement is made in 100 µ s increments.) SD522: Place of ms is stored (storage range: 0 to 65535) SD523: Place of µ s is stored (storage range: 0 to 900)

Initial scan time Initial scan time (µs unit)

SD523

SD524 Minimum scan time (ms unit)

  • Minimum value of scan time with the exception of initial execution program scan time is stored into SD524, SD525. (Measurement is made in 100 µ s increments.) SD524: Place of ms is stored (storage range: 0 to 65535) SD525: Place of µ s is stored (storage range: 0 to 900)

Minimum scan time (µs unit)

SD525

SD526 Maximum scan time (ms unit)

  • Maximum value of scan time with the exception of initial execution program scan time is stored into SD526, SD527. (Measurement is made in 100 µ s increments.) SD526: Place of ms is stored (storage range: 0 to 65535) SD527: Place of µ s is stored (storage range: 0 to 900)

Maximum scan time Maximum scan time (µs unit)

SD527

SD528 Current scan time (ms unit)

Current scan time for low speed execution type programs

  • Current scan time of low speed program is stored into SD528, SD529. (Measurement is made in 100 µ s increments.) SD528: Place of ms is stored (storage range: 0 to 65535) SD529: Place of µ s is stored (storage range: 0 to 900)

Current scan time (µs unit)

SD529

SD532 Minimum scan time (ms unit)

Minimum scan time for low speed execution type programs

  • Minimum value of low speed program scan time is stored into SD532, SD533. (Measurement is made in 100 µ s increments.) SD532: Place of ms is stored (storage range: 0 to 65535) SD533: Place of µ s is stored (storage range: 0 to 900)

Minimum scan time (µs unit)

SD533

SD534 Maximum scan time (ms unit)

Maximum scan time for low speed execution type programs

  • Maximum value of low speed program scan time with the exception of the first scan is stored into SD534, SD535. (Measurement is made in 100 µ s increments.) SD534: Place of ms is stored (storage range: 0 to 65535) SD535: Place of µ s is stored (storage range: 0 to 900)

Maximum scan time (µs unit)

SD535

SD540 END processing time (ms unit)

  • Time from scan program end until next scan start is stored into SD540, SD541. (Measurement is made in 100 µ s increments.) SD540: Place of ms is stored (storage range: 0 to 65535) SD541: Place of µ s is stored (storage range: 0 to 900)

END processing time END processing time (µs unit)

SD541

11 - 78 11 - 78

Show 42 more labels / short text on this page
Corresponding · Corresponding · S (Status · change) New · S (Every · END processing) · New · S (Every · D9017 format · END processing) · change · Current scan time · S (Every · END processing) · New · S (First · END processing) · New · S (Every · D9018 format · END processing) · change · Minimum scan time · S (Every · END processing) · New · D9019 format · S (Every · change · END processing) New · S (Every · END processing) · New · S (Every · END processing) · New · S (Every · END processing) · New · S (Every · END processing) · New
Page 195 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD552
Page 195 · click to enlarge
Page 195

Special Register List (Continued)

Number Name Meaning Explanation Set by (When set)

ACPU D9

SD542 Constant scan waiting time (ms unit)

  • Waiting time at the time of constant scan setting is stored into SD542, SD543. (Measurement is made in 100 µ s increments.) SD542: Place of ms is stored (storage range: 0 to 65535) SD543: Place of µ s is stored (storage range: 0 to 900)

Constant scan wait time Constant scan waiting time (µs unit)

SD543

Cumulative execution time for low speed execution type programs

Low speed program cumulative execution time (ms unit)

  • Cumulative execution time of low speed program is stored into SD544, SD545. (Measurement is made in 100 µ s increments.) SD544: Place of ms is stored (storage range: 0 to 65535) SD545: Place of µ s is stored (storage range: 0 to 900)
  • Cleared to 0 after end of low speed one scan.

SD544

Low speed program cumulative execution time (µs unit)

SD545

Low speed program execution time (ms unit)

  • Execution time of low speed program during one scan is stored into SD546, SD547. (Measurement is made in 100 µ s increments.) SD546: Place of ms is stored (storage range: 0 to 65535) SD547: Place of µ s is stored (storage range: 0 to 900)
  • Stored every scan.

SD546

Execution time for low speed execution type programs

Low speed program execution time (µs unit)

SD547

Scan program execution time (ms unit)

  • Execution time of scan program during one scan is stored into SD548, SD549. (Measurement is made in 100 µ s increments.) SD548: Place of ms is stored (storage range: 0 to 65535) SD549: Place of µ s is stored (storage range: 0 to 900)
  • Stored every scan.

SD548

Scan program execution time Scan program

SD549

execution time (µs unit)

Service interval measurement module

SD550

Unit/module No. • Sets I/O number for module that measures service interval U New

SD551 Module service intervals (ms unit)

  • Service intervals for the module specified in SD550 are stored into SD551, SD552 when SM551 is turned ON. (Measurement is made in 100 µ s increments.) SD551: Place of ms is stored (storage range: 0 to 65535) SD552: Place of µ s is stored (storage range: 0 to 900)

Service interval time Module service intervals (µs unit)

SD552

11 - 79 11 - 79

Show 16 more labels / short text on this page
Corresponding · Corresponding · S (First · END processing) · New · S (Every · END processing) · New · S (Every · END processing) · New · S (Every · END processing) · New · +Rem · S (Request) New
Page 196 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 80 11 - 80
Page 196 · click to enlarge
Page 196

Special Register List (5) Memory card

Number Name Meaning Explanation Set by (When set)

ACPU D9

  • Indicates memory card A model installed

B4 B3 B0 B8 B7 B15

0. Does not exist

S (Initial and card

1: SRAM

0. Does not exist

(1: SRAM)

Memory card A models

Memory card A models • Indicates memory card A model installed B4 B3 B0

2: ATA FRASH

SD600

3. Flash ROM

B8 B7 B15

0. Does not exist

S (Initial and card

1: SRAM

0. Does not exist

2: E PROM

3. Flash ROM

S (Initial and card

removal) New QCPU SD602

Drive 1 (RAM) capacity

Drive 1 capacity • Drive 1 capacity is stored in 1 kbyte units S (Initial and card

S (Initial and card

removal) New QCPU SD603

Drive 2 (ROM) capacity

Drive 2 capacity • Drive 2 capacity is stored in 1 kbyte units S (Initial and card

  • The use conditions for memory card A are stored as bit patterns (In use when ON)
  • The significance of these bit patterns is indicated below:

B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File register R (QDR) B5: Trace (QTS) B6: Not used B7: Not used

B8: Not used B9: CPU fault history (QFD) BA: SFC trace (QTS) BB: Local device (QDL) BC: Not used BD: Not used BE: Not used BF: Not used

S (Status change) New QCPU

Memory card A use conditions

Memory card A use conditions

SD604

  • The use conditions for memory card A are stored as bit patterns (In use when ON)
  • The significance of these bit patterns is indicated below:

B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File register R (QDR) B5: Sampling trace (QTS) B6: Status latch (QTL) B7: Program trace (QTP)

B8: Simulation data (QDS) B9: CPU fault history (QFD) B10: SFC trace (QTS) B11: Local device (QDL) B12: Not used B13: Not used B14: Not used B15: Not used

S (Status change) New QnA

  • Indicates memory card B models installed

B4 B3 B0 B8 B7 B15

Memory card B models

Memory card B models

(0Does not exist)

SD620

1: SRAM

S (Initial) New QCPU

0. Does not exist

(1: SRAM)

2 Drive 4 is fixed to "3" because it has built-in Flash ROM.

(2: E PROM)

3. Flash ROM

11 - 80 11 - 80

Show 22 more labels / short text on this page
Corresponding · Corresponding · 0< >0 ----------- · Drive 1 · (RAM) model · removal) New QCPU · Drive 2 · (ROM) model · 0< >0 · ----------- · Drive 1 · (RAM) model · removal) New QnA · Drive 2 · (ROM) model · removal) New QnA · removal) New QnA · 0< >0 ----------- · Drive 3 · (RAM) model · Drive 4 · (ROM) model
Page 197 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 81 11 - 81
Page 197 · click to enlarge
Page 197

Special Register List (Continued)

Number Name Meaning Explanation

ACPU D9

  • Indicates memory card B models installed B4 B3 B0

B8 B7 B15

Q2A (S1)

SD620 Memory card B models

Memory card B models

0. Does not exist

Q3A Q4A Q4AR

1: SRAM

0. Does not exist

2: E 2 PROM

3. Flash ROM
  • Drive 3 capacity is stored in 1 kbyte units. S (Initial) New QCPU

Drive 3 (RAM) capacity

Q2A (S1)

Drive 3 capacity • Drive 3 capacity is stored in 1 kbyte units S (Initial) New

SD622

Q3A Q4A Q4AR

  • Drive 4 capacity is stored in 1 kbyte units. S (Initial) New QCPU

Drive 4 (ROM) capacity

Q2A (S1)

SD623

Drive 4 capacity • Drive 4 capacity is stored in 1 kbyte units S (Initial) New

Q3A Q4A Q4AR

  • The conditions for usage for drive 3/4 are stored as bit patterns. (In use when ON)
  • The significance of these bit patterns is indicated below:

B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File R (QDR) B5: Trace (QTS) B6: Not used B7: Not used

B8: Not used B9: CPU fault history (QFD) B10: SFC trace (QTS) B11: Local device (QDL) B12: Not used B13: Not used B14: Not used B15: Not used

Drive 3/4 use conditions

Drive 3/4 use conditions

SD624

  • The use conditions for memory card B are stored as bit patterns (In use when ON)
  • The significance of these bit patterns is indicated below:

B0: Boot operation (QBT) B1: Parameters (QPA) B2: Device comments (QCD) B3: Device initial value (QDI) B4: File R (QDR) B5: Sampling trace (QTS) B6: Status latch (QTL) B7: Program trace (QTP)

B8: Simulation data (QDS) B9: CPU fault history (QFD) B10: SFC trace (QTS) B11: Local device (QDL) B12: Not used B13: Not used B14: Not used B15: Not used

Q2A (S1)

Memory card B use conditions

Memory card B use conditions

Q3A Q4A Q4AR

SD640 File register drive Drive number: • Stores drive number being used by file register S (Initial) New

SD641

  • Stores file register file name (with extension) selected at parameters or by use of QDRSET instruction as ASCII code.

SD642

B15 to B8 B7 to B0

SD643

SD644

SD641 SD642 SD643 SD644 SD645

First character Third character

File register file name

File register file name

SD645

Sixth character Eighth character First character of extension

Fifth character Seventh character

2E H (.)

SD646

SD646

Third character of extension

SD647 File register capacity

  • Stores the data capacity of the currently selected file register in 1 k word units.

SD648 File register block number

File register block number • Stores the currently selected file register block number. S (Status

  • Stores the comment drive number selected at the parameters or by the QCDSET instruction.

11 - 81 11 - 81

Show 28 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · ----------- · 0< >0 · Drive 1 · (RAM) model · S (Initial) New · Drive 2 · (ROM) model · S (Status · change) New QCPU · S (Status · change) New · Second character · Fourth character · S (Initial) New · Second character of · extension · File register capacity · S (Status · change) New · change) D9035 · SD650 Comment drive · Comment drive number · S (Status · change) New
Page 198 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 82 11 - 82
Page 198 · click to enlarge
Page 198

Special Register List (Continued)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (Continued) diagram (page 198)
Fig. 92 · Special Register List (Continued)
  • Stores the comment file name (with extension) selected at the parameters or by the QCDSET instruction in ASCII code.
  • Stores the drive number where the boot designation file ( .QBT) is being stored. S (Initial) New
  • Stores the file name of the boot designation file ( .QBT).

(6) Instruction-Related Registers

Number Name Meaning Explanation

ACPU D9

  • During block operations, turning SM705 ON makes it possible to use the mask pattern being stored at SD705 (or at SD705 and SD706 if double words are being used) to operate on all data in the block with the masked values.

SD705

Mask pattern Mask pattern

SD706

Number of vacant communicati on request registration areas

0 to 32 • Stores the number of vacant blocks in the communications request area for remote terminal modules connected to the AJ71PT32-S3.

S (During execution) D9081 QnA

SD714

  • Patterns masked by use of the IMASK instruction are stored in the following manner:

SD715

B15 B0 B1 to

IMASK instruction mask pattern

SD715

S (During execution) New

SD716

SD716

SD717

SD717

SD718

SD719

Accumulator Accumulator • For use as replacement for accumulators used in A-series programs. S/U New

Program No. designation for PLOAD instruction

Program No. designation for PLOAD instruction

  • Stores the program number of the program to be loaded by the PLOAD instruction when designated.
  • Designation range: 1 to 124 U New QCPU

SD720

No. of vacant registration area for CC- Link communicati on request

0 to 32 • Stores the number of vacant registration area for the request for communication with the intelligent device station connected to A(1S)J61QBT61.

S (During execution) New QnA

SD730

SD736 PKEY input PKEY input • Special register that temporarily stores keyboard data input by means of the PKEY instruction.

S (During execution) New QnA

11 - 82 11 - 82

Show 9 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · U New · l15 l1 l0 · Mask pattern · to · to
Page 199 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD778
Page 199 · click to enlarge
Page 199

Special Register List (Continued)

Number Name Meaning Explanation

ACPU D9

SD738

  • Stores the message designated by the MSG instruction.

SD739

1st character B15 B8 B7 B0

SD740

SD738 SD739 SD740 SD741 SD742 SD743

2nd character 3rd character 4th character 5th character 6th character 7th character 8th character 9th character 10th character 11th character 12th character 13th character 14th character 15th character 16th character 17th character 18th character 19th character 20th character 21st character 22nd character 23rd character 24th character 25th character 26th character 27th character 28th character 29th character 30th character 31st character 32nd character 33rd character 34th character 35th character 36th character 37th character 38th character 39th character 40th character 41st character 42nd character 43rd character 44th character 45th character 46th character 47th character 48th character 49th character 50th character 51st character 52nd character 53rd character 54th character 55th character 56th character 57th character 58th character 59th character 60th character 61st character 62nd character 63rd character

SD741

SD742

SD743

SD744

SD745

SD744 SD745 SD746 SD747 SD748 SD749 SD750 SD751 SD752 SD753 SD754 SD755 SD756 SD757 SD758 SD759 SD760 SD761 SD762 SD763 SD764 SD765 SD766 SD767 SD768 SD769 64th character

SD746

SD747

SD748

SD749

SD750

SD751

SD752

SD753

S (During execution) New

SD754

SD755

SD756

SD757

SD758

SD759

SD760

SD761

SD762

SD763

SD764

SD765

SD766

SD767

SD768

SD769

  • Designate the limit for each PID loop as follows:

B15 B1 B0 Loop16

SD774 TO SD775

0. Limit set 1: Limit not set

SD774

SD775

Bits 0 to 40:Do not refresh 1:Refresh F bit 0:Refresh 1:Do not refresh

Selects whether or not the data is refreshed when the COM instruction

is executed.

Refresh processing selection when the COM instruction is executed

SD778 0 1/0 b14 b5 to b4 b3 b2 b1 b0 b15

QCPU Serial number 04012 or later

I/O refresh CC-Link refresh MELSECNET/H refresh Automatic refresh of intelligent function modules Automatic refresh of multi-CPU shared memory General data processing

SD778

11 - 83 11 - 83

Show 18 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · to to · Message storage · Message storage · PID limit setting · to · Loop2 · Loop1 · U New QCPU · to · Loop32 · Loop18 · Loop17 · 1/0 · U New
Page 200 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 84 11 - 84
Page 200 · click to enlarge
Page 200

Special Register List (7) Debug

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (7) Debug diagram (page 200)
Fig. 93 · Special Register List (7) Debug

Remaining No. of simultaneous execution of CC-Link dedicated instruction

0 to 32 • Stores the remaining number of simultaneous execution of the CC- Link dedicated instructions. U New QnA

  • Stores the mask patterns masked by the IMASK instruction as follows:
  • Stores file name (with extension) from point in time when status latch was conducted as ASCII code.

SD812 • Stores step number from point in time when status latch was conducted.

0 1 2 3 4 15 14

(Not in use) SFC block designation present (1)/absent (0)

11 - 84 11 - 84

Page 201 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — SD918
Page 201 · click to enlarge
Page 201

Special Register List (8) Latch area

Number Name Meaning Explanation

ACPU D9

Access file drive number during power loss

Drive where power was interrupted

  • Stores drive number if file was being accessed during power loss. S (Status

SD900

  • Stores file name (with extension) in ASCII code if file was being accessed during power loss.

SD901

B15 B8 B7 B0 1st character 2nd character 3rd character 4th character 5th character 6th character 7th character 8th character

SD902

SD901 SD902 SD903 SD904

SD903

File name active during power loss

Access file name during power loss

SD904

SD905

1st character of extension 2EH(.)

SD905

2nd character of extension 3rd character of extension

SD906

SD906

SD910

  • Stored in sequence that PU key code was entered.

B15 B8 B7 B0

SD911

SD910 SD911 SD912 SD913 SD914 SD915

1st character 2nd character 3rd character 4th character 5th character 6th character 7th character 8th character 9th character 10th character 11th character 12th character 13th character 14th character 15th character 16th character 17th character 18th character 19th character 20th character 21st character 22nd character 23rd character 24th character 25th character 26th character 27th character 28th character 29th character 30th character 31st character 32nd character

SD912

SD913

SD914

SD915

SD916

SD916 SD917 SD918 SD919 SD920 SD921 SD922 SD923 SD924 SD925

SD917

RKEY input RKEY input

S (During execution) New

SD918

SD919

SD920

SD921

SD922

SD923

SD924

SD925

11 - 85 11 - 85

Show 10 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · change) New · to to · S (Status · change) New · to to · QnA
Page 202 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 86 11 - 86
Page 202 · click to enlarge
Page 202

(9) A to Q/QnA conversion correspondences

ACPU special registers D9000 to D9255 correspond to the special registers SD1000 to SD1255 after A-series to the Q/QnA-series conversion. These special registers are all set by the system, and users cannot use them to set program data. Users who need to set data with these registers should edit the special registers for the Q/QnA. However, before conversion users could set data at special registers D9200 to D9255 only, and after conversion users can also set data at registers 1200 to 1255. For more detailed information concerning the contents of the ACPU special registers, see the individual CPU users manual, and the MELSECNET and MELSECNET/B data link system reference manual.

REMARK

Supplemental explanation on "Special Register for Modification" column

1 For the device numbers for which a special register for modification is specified, modify it to the special register for QCPU/QnACPU.

2 For the device numbers for which is specified, special register after conversion can be used.

3 Device numbers for which is specified do not function for QCPU/QnACPU.

Special Register List

Special Register for Modification

Name Meaning Details Corresponding

  • When fuse blown modules are detected, the lowest number of detected units is stored in hexadecimal. (Example: When fuses of Y50 to 6F output modules have blown, "50" is stored in hexadecimal) To monitor the number by peripheral devices, perform monitor operation given in hexadecimal. (Cleared when all contents of SD1100 to SD1107 are reset to 0.)
  • Fuse blow check is executed also to the output modules of remote I/O stations.

Number of module with blown fuse

D9000 SD1000 Fuse blown

  • Stores the module numbers corresponding to setting switch numbers or base unit slot numbers when fuse blow occurred.

I/O module for A0J2 Extension base unit

switch Stored data Base unit

slot No. Stored data

0 1 0 5

Number of module with blown fuse

1 2 1 6

D9001 SD1001 Fuse blown

2 3 2 7

3 4 3 8

  • For remote I/O station, value of (module I/O number/10H) + 1 is stored.

11 - 86 11 - 86

Show 4 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Setting
Page 203 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 87 11 - 87
Page 203 · click to enlarge
Page 203

Special Register List (Continued)

ACPU

Name Meaning Details Corresponding

  • If I/O modules, of which data are different from data

entered, are detected when the power is turned on,

the first I/O number of the lowest number unit among

the detected units is stored in hexadecimal. (Storing

method is the same as that of SD1000.) To monitor

D9002 SD1002

the number by peripheral devices, perform monitor

operation given in hexadecimal.

(Cleared when all contents of SD1116 to SD1123 are

reset to 0.)

  • I/O module verify check is executed also to the

modules of remote I/O terminals.

  • Stores the MINI(S3) link error detection status in the

mounted MELSECNET/MINI-S3 master module. B15 B8 B7 B0

8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1

D9004 SD1004

On the PLC CPU and A(1S)J71PT32(S3) side, the bit corresponding to the A(1S)J71PT32(S3) that cannot make data communication turns ON.

Bits which correspond to the signals of A(1S)J71PT32(S3), shown below, are turned on as the signals are turned on. · Hardware error (X0/X20)

· MINI(S3) link error datection (X6/X26)

· MINI(S3) link communication error (X7/X27)

  • Turned ON if instantaneous power failure of within

20ms occurs when AC power supply module is used,

and reset when power is switched OFF, then ON.

AC DOWN

Number of times for

  • Turned ON if instantaneous power failure of within

D9005 SD1005

10ms occurs when DC power supply module is used,

AC DOWN

and reset when power is switched OFF, then ON.

  • Turned ON if instantaneous power failure of within

1ms occurs when DC power supply module is used,

and reset when power is switched OFF, then ON.

D9008 SD1008 SD0 Self-diagnosis

  • When error is found as a result of self-diagnosis, error

code is stored in BIN code.

  • When one of F0 to 2047 is turned on by OUT F or

SET F , the F number, which has been detected

earliest among the F numbers which have turned on,

is stored in BIN code. • SD62 can be cleared by RST F or LEDR

instruction.

If another F number has been detected, the clearing of

F number at which

SD62 causes the next number to be stored in SD62.

D9009 SD1009 SD62 Annunciator

  • When one of F0 to 2047 is turned on by OUT F or

SET F , the F number, which has been detected

earliest among the F numbers which have turned on,

is stored in BIN code. • SD62 can be cleared by executing RST F or

LEDR instruction or moving INDICATOR RESET

switch on CPU front to ON position. If another F

number has been detected, the clearing of SD62

causes the nest number to be stored in SD62.

  • When operation error has occurred during execution

of application instruction, the step number, at which

D9010 SD1010 Error step

the error has occurred, is stored in BIN code.

error has occurred.

Thereafter, each time operation error occurs, the

contents of SD1010 are renewed.

11 - 87 11 - 87

Show 29 more labels / short text on this page
Special · Special · Special · Register after · Register for · Conversion · Conversion · Modification · I/O module · I/O module · verification error · verification error · module number · to to · MINI link master · Error detection · QnA · module errors · state · counter · QnA · Self-diagnosis error · error · code · external failure has · detection · occurred · Step number at · which operation
Page 204 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 88 11 - 88
Page 204 · click to enlarge
Page 204

Special Register List (Continued)

Special Register for Modification

Name Meaning Details Corresponding

  • When operation error has occurred during execution of application instruction, the step number, at which the error has occurred, is stored in BIN code. Since storage into SD1011 is made when SM1011 changes from off to on, the contents of SD1011 cannot be renewed unless SM1011 is cleared by user program.

Step number at which operation error has occurred.

D9011 SD1011 Error step

  • The I/O control mode set is returned in any of the following numbers:

D9014 SD1014 I/O control mode I/O control mode

0. Both input and output in direct mode 1. Input in refresh mode, output in direct mode 3. Both input and output in refresh mode
  • The operation status of CPU as shown below are stored in SD203.
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (Continued) diagram (page 204)
Fig. 94 · Special Register List (Continued)

B15 B12 B11 B8 B7 B4 B3 B0

to

Remote RUN/STOP by computer

0 RUN

0 RUN

1 STOP

1 STOP

D9015 SD1015 SD203 Operating status of CPU

Operating status of CPU

2 PAUSE 1

PAUSE 1

3 STEP RUN

Remains the same in remote RUN/STOP mode.

Remote RUN/STOP by parameter setting

STOP

0 RUN

1 STOP

2 PAUSE 1

1 When the CPU module is in RUN mode and SM1040 is off, the CPU remains in RUN mode if changed to PAUSE mode.

0. Main program (ROM) 1: Main program (RAM) 2: Subprogram 1 (RAM) 3: Subprogram 2 (RAM) 4: Subprogram 3 (RAM) 5: Subprogram 1 (ROM) 6: Subprogram 2 (ROM) 7: Subprogram 3 (ROM) 8: Main program (E 2 PROM) 9: Subprogram 1 (E 2 PROM) A: Subprogram 2

D9016 SD1016 Program number

  • Indicates which sequence program is run presently. One value of 0 to B is stored in BIN code.
(E 2 PROM) BSubprogram 3

(E 2 PROM)

  • If scan time is smaller than the content of SD520, the value is newly stored at each END. Namely, the minimum value of scan time is stored into SD520 in BIN code.

D9017 SD1017 SD520 Scan time Minimum scan time (10 ms units)

D9018 SD1018 SD524 Scan time Scan time (10 ms units)

  • Scan time is stored in BIN code at each END and always rewritten.

11 - 88 11 - 88

Show 8 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · number · CPU key switch · Status in program · Except below · instruction execution
Page 205 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 89 11 - 89
Page 205 · click to enlarge
Page 205

Special Register List (Continued)

Special Register for Modification

Name Meaning Details Corresponding

  • If scan time is larger than the content of SD526, the value is newly stored at each END. Namely, the maximum value of scan time is stored into SD526 in BIN code.

D9019 SD1019 SD526 Scan time Maximum scan time (10 ms units)

  • Sets the interval between consecutive program starts in multiples of 10 ms.

Constant scan time (User sets in 10 ms units)

D9020 SD1020 Constant scan

0. No setting 1 to 200: Set. Program is executed at intervals of (set value) × 10 ms.

D9021 SD1021 Scan time Scan time (1 ms units)

  • Scan time is stored and updated in BIN code after every END.
  • When the PC CPU starts running, it starts counting 1 every second.
  • Count repeats changing from 0 to 32767 to -32768 to 0.

D9022 SD1022 SD412 1 second counter

Count in units of 1sec.

  • Year (lower 2 digits) and month are stored into SD1025 in BCD code as shown below.

D9025 SD1025 Clock data Clock data (year, month)

B15 B12 B11 B8 B7 B4 B3 B0

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — B15 B12 B11 B8 B7 B4 B3 B0 diagram (page 205)
Fig. 95

to

Example1987, July H8707
  • Day and hour are stored into SD1026 in BCD code as shown below.

D9026 SD1026 Clock data Clock data (day, hour)

B15 B12 B11 B8 B7 B4 B3 B0

to

Example 31th, 10 o'clock H3110

  • Minute and second are stored into SD1027 in BCD code as shown below.

D9027 SD1027 Clock data Clock data (minute, second)

B15 B12 B11 B8 B7 B4 B3 B0

to

Example35 minutes, 48 seconds H3548
  • Day of week is stored into SD1028 in BCD code as shown below.

B15 B12 B11 B8 B7 B4 B3 B0 Example: Friday H0005

to

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — B15 B12 B11 B8 B7 B4 B3 B0 diagram (page 205)
Fig. 96

0 must be set. Day of the week

D9028 SD1028 Clock data Clock data (day of week)

0 1 2 3

Sunday Monday Tuesday Wednesday

D9035 SD1035 SD648 Extension file register Use block No. • Stores the block No. of the extension file register being used in BCD code.

  • Designate the device number for the extension file register for direct read and write in 2 words at SD1036 and SD1037 in BIN data. Use consecutive numbers beginning with R0 of block No. 1 to designate device numbers.

D9036 SD1036

Device number when individual devices from extension file register are directly accessed

Extension file registerfor designation of device number

Block No.1 area

16383 16384 Block No.2 area

SD1036,SD1037

D9037 SD1037

Device No. (BIN data)

D9038 SD1038 SD207 Priorities 1 to 4

  • Sets priority of ERROR LEDs which illuminate (or flicker) to indicate errors with error code numbers.
  • Configuration of the priority setting areas is as shown below.

LED display priority ranking Priorities 5 to 7

B15 B12B11 B8 B7 B4 B3 B0 Priority 4 Priority 3 Priority 2 Priority 1

to

D9039 SD1039 SD208

SD207

SD208

  • For details, refer to the applicable CPUs User’s Manual and the ACPU Programming manual (Fundamentals).

Priority 5 Priority 6 Priority 7

11 - 89 11 - 89

Show 12 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Year Month · Day Hour · Minute Second · Thursday · Friday Saturday · Exetension file register · to · to · to
Page 206 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9081 SD1081 SD714
Page 206 · click to enlarge
Page 206

Special Register List (Continued)

Special Register for Modification

Name Meaning Details Corresponding

  • When SM803 is turned ON/OFF by peripheral device to activate sampling trace STRA , STRAR , value

D9044 SD1044 For sampling trace

Step or time during sampling trace

stored in SD1044 is used as sampling trace condition.

For scan 0 For time Time (10ms increments) Value is stored into SD1044 in BIN code.

  • Stores the block number of the expansion file register which is used as the work area for the execution of a SFC program in a binary value.
  • Stores "0" if an empty area of 16K bytes or smaller, which cannot be expansion file register No. 1, is used or if SM320 is OFF.

Extension file register block No. used as SFC program execution work area

D9049 SD1049 Work area for SFC

  • Stores code numbers of errors occurred in the SFC program in BIN code.
0. No error 80: SFC program parameter error 81: SFC code error 82: Number of steps of simultaneous execution exceeded 83: Block start error 84: SFC program operation error

Error code generated by SFC program

D9050 SD1050 SFC program error number

  • Stores the block number in which an error occurred in the SFC program in BIN code. In the case of error 83 the starting block number is stored.

Block number where error occurred

D9051 SD1051 Error block

  • Stores the step number in which error 84 occurred in the SFC program in BIN code. Stores "0" when errors 80, 81 and 82 occurred. Stored the block starting step number when error 83 occurred.

D9052 SD1052 Error step Step number where error occurred

Transition condition number where error occurred

  • Stores the transfer condition number in which error 84 occurred in the SFC program in BIN code. Stored "0" when errors 80, 81, 82 and 83 occurred.

D9053 SD1053 Error transition

Sequence step number where error occurred

  • Stores the sequence step number of transfer condition and operation output in which error 84 occurred in the SFC program in BIN code.

D9054 SD1054 Error sequence step

  • Stores the step number when status latch is executed.
  • Stores the step number in a binary value if status latch is executed in a main sequence program.
  • Stores the block number and the step number if status latch is executed in a SFC program.

Status latch execution step No.

Status latch execution step No.

D9055 SD1055 SD812

Block No.

Step No.

(BIN)

(BIN)

Higher 8 bits Lower 8 bits

  • Stores the software version of the internal system in ASCII code.

The data in the lower byte position is indefinite. The software version is stored in the higher byte position.

Higher byte Lower byte

D9060 SD1060 SD392 Software version Software version of

For version "A", for example, "41H" is stored. Note: The software version of the initial system may

differ from the version indicated by the version information printed on the rear of the case.

Data check of serial communication module

  • In the self-loopback test of the serial communication module, the serial communication module writes/reads data automatically to make communication checks.

D9072 SD1072

Number of empty blocks in communications request registrtion area

  • Stores the number of empty blocks in the communication request registration area to the remote terminal module connected to the MELSECNET/MINIS3 master unit, A2C or A52G.

D9081 SD1081 SD714

11 - 90 11 - 90

Show 8 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · internal software · QnA · PLC communications check · 0 to 32 · QnA
Page 207 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9121 SD1121
Page 207 · click to enlarge
Page 207

Special Register List (Continued)

Special Register for Modification

Name Meaning Details Corresponding

  • Sets the time check time of the data link instructions (ZNRD, ZNWR) for the MELSECNET/10.
  • Setting range: 1 s to 65535 s (1 to 65535)
  • Setting unit: s
  • Default value: 10 s (If 0 has been set, default 10 s is applied)

Register for setting time check value

D9085 SD1085

Microcomputer subroutine input data area head device No.

According to corresponding microcomputer package

  • For details, refer to the manual of each microcomputer program package.

D9090 SD1090

D9091 SD1091 Detailed error code

Self-diagnosis detailed error code • Stores the detail code of cause of an instruction error.

  • Stores upper 2 digits of the head I/O address of I/O modules to be loaded or unloaded during online mode in BIN code. Example) Input module X2F0 → H2F

Head I/O number for replacement

Head I/O number for replacement

D9094 SD1094 SD251

D9100 SD1100

  • Output module numbers (in units of 16 points), of which fuses have blown, are entered in bit pattern. (Preset output unit numbers when parameter setting has been performed.)

D9101 SD1101

D9102 SD1102

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

SD1100

0 1 (Y80) 0

1 (YCO)

Bit pattern in units of 16 points, indicating the modules whose fuses have blown

D9103 SD1103

SD1101

0

0 1 Y7 B0

1 Y7 30

D9104 SD1104

SD1107

  • Fuse blow check is executed also to the output module of remote I/O station. (If normal status is restored, clear is not performed. Therefore, it is required to perform clear by user program.)

Indicates fuse blow.

D9105 SD1105

D9106 SD1106

D9107 SD1107

D9108 SD1108

  • Sets value for the step transfer monitoring timer and the number of F which turns on when the monitoring timer timed out.

D9109 SD1109

b15 b8 b7 b0 to to

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — D9109 SD1109 diagram (page 207)
Fig. 97

D9110 SD1110

Step transfer monitoring timer setting

Timer setting valve and the F number at time out

Timer setting (1 to 255 s in seconds)

D9111 SD1111

D9112 SD1112

(By turning on any of SM1108 to SM1114, the

monitoring timer starts. If the transfer condition following a step which corresponds to the timer is not established within set time, set annunciator (F) is tuned on.)

D9113 SD1113

D9114 SD1114

D9116 SD1116

  • When I/O modules, of which data are different from those entered at power-on, have been detected, the I/O unit numbers (in units of 16 points) are entered in bit pattern. (Preset I/O unit numbers when parameter setting has been performed.)

D9117 SD1117

D9118 SD1118

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Bit pattern, in units of 16 points, indicating the modules with verification errors.

SD1116

0

1 XY

D9119 SD1119

0 1 XY 100

I/O module verification error

SD1117

0

0 1 XY 100

D9120 SD1120

SD1123

Indicates I/O module verify error. • I/O module verify check is executed also to remote I/O station modules. (If normal status is restored, clear is not performed. Therefore, it is required to perform clear by user program.)

D9121 SD1121

D9122 SD1122

D9123 SD1123

11 - 91 11 - 91

Show 6 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · 1s to 65535s · Fuse blown module · F number setting
Page 208 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9132 SD1132 SD71
Page 208 · click to enlarge
Page 208

Special Register List (Continued)

Special Register for Modification

Name Meaning Details Corresponding

  • When one of F0 to 2047 (F0 to 2047 for AuA and AnU) is turned on by SET F 1 is added to the contents of SD63. When RST F or LEDR

instruction is executed, 1 is subtracted from the contents of SD63. (If the INDICATOR RESET switch is provided to the CPU, pressing the switch can execute the same processing.) • Quantity, which has been turned on by SET F is

D9124 SD1124 SD63

stored into SD63 in BIN code. The value of SD63 is maximum 8.

D9125 SD1125 SD64

  • When any of F0 to 2047 is turned ON by SET F , F

numbers turned ON sequentially are registered into D9125 - D9132. F numbers turned OFF by RST F are deleted from

D9126 SD1126 SD65

D9125 - D9132, and move to data registers subsequent to the ones that stored deleted F numbers. Execution of LEDR instruction shifts up

SD64 - SD71 contents one place. (When CPU has INDICATOR RESET switch, pressing that switch performs the same processing.) When there are eight annunciator numbers detected, the ninth number is not stored into SD64 - SD71 if detected.

D9127 SD1127 SD66

D9128 SD1128 SD67

SET F50

SET F25

SET F99

RST F25

SET F15

SET F70

SET F65

SET F38

SET F110

SET F151

SET F210 LEDR

SD62

0 50 99

D9129 SD1129 SD68

SD63

1 2 3 2 3 4 5 6 7 8 8 8

SD64

0 50 99

SD65

0 25 25 99 15

D9130 SD1130 SD69

SD66

0 99 15 70

SD67

0 70 65 0

SD68

0 65 38 0

D9131 SD1131 SD70

SD69

0 38 110

SD70

0 110 110 110 151 0

SD71

0 151 151 210

D9132 SD1132 SD71

11 - 92 11 - 92

Show 7 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Annunciator detection quantity · Annunciator detection quantity · Annunciator detection number · Annunciator detection number
Page 209 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 93 11 - 93
Page 209 · click to enlarge
Page 209

Special Register List (10) Special register list dedicated for QnA

Special Register for Modification

Name Meaning Details Corresponding

Stores the execution result of the ZNRD (word device read) instruction

0. Normal end 2: ZNRD instruction setting fault 3: Error at relevant station 4: Relevant station ZNRD execution disabled • ZNRD cannot be executed in the corresponding station:

ZNRD (LRDP for ACPU) processing results

  • ZNRD instruction setting fault: Faulty setting of the ZNRD instruction constant, source, and/or destination

D9200 SD1200

  • Corresponding station error: One of the stations is not communicating.

The specified station is a remote I/O station.

Stores the execution result of the ZNWR (word device write) instruction.

0. Normal end 2: ZNWR instruction setting fault 3: Error at relevant station 4: Relevant station ZNWR execution disabled • ZNWR cannot be executed in the corresponding station:

ZNWR (LWTP for ACPU) processing results

  • LWTP instruction setting fault: Faulty setting of the ZNWR instruction constant, source, and/or destination.

D9201 SD1201

  • Corresponding station error: One of the stations is not communicating.

The specified station is a remote I/O station.

  • Stores whether the slave station corresponds to MELSECNET or MELSECNET II.
  • Bits corresponding to the MELSECNET II stations become "1."
  • Bits corresponding to the MELSECNET stations or unconnected become "0."

Stores conditions for up to numbers 1 to 16

D9202 SD1202

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

SD1202

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

Local station link type

SD1203

L32 L31 L30 L29 L28 L27

SD1241

L48 L47 L46 L45 L44 L43

  • If a local station goes down during the operation, the contents before going down are retained. Contents of SD1224 to SD1227 and SD1228 to SD1231 are ORed. If the corresponding bit is "0", the corresponding bit of the special register above becomes valid.
  • If the own (master) station goes down, the contents before going down are also retained.

SD1242

L64 L63 L62 L61 L60 L59

Stores conditions for up to numbers 17 to 32

D9203 SD1203

0. Forward loop, during data link 1: Reverse loop, during data link 2: Loopback implemented in forward/reverse directions 3: Loopback implemented only in forward direction 4: Loopback implemented only inreverse direction 5: Data link disabled

Stores the present path status of the data link. • Data link in forward loop

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — D9203 SD1203 diagram (page 209)
Fig. 98

Master station Station 1 Station 2 Station n

D9204 SD1204 Link status

Forward loop Reverse loop • Data link in reverse loop

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — D9203 SD1203 diagram (page 209)
Fig. 99

Master station Station 1 Station 2 Station n

Forward loop Reverse loop

11 - 93 11 - 93

Show 6 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · QnA · Bit Device number · QnA
Page 210 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9215 SD1215
Page 210 · click to enlarge
Page 210

Special Register List (Continue)

Special Register for Modification

Name Meaning Details Corresponding

  • Loopback in forward/reverse loops
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (Continue) diagram (page 210)
Fig. 100 · Special Register List (Continue)

Master station Station 1 Station 2 Station 3 Station n

0. Forward loop, during data link 1: Reverse loop, during data link 2: Loopback implemented in forward/reverse directions 3: Loopback implemented only in forward direction 4: Loopback implemented only inreverse direction 5: Data link disabled

Forward loopback Reverse loopback • Loopback in forward loop only

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (Continue) diagram (page 210)
Fig. 101 · Special Register List (Continue)

Master station Station 1 Station 2 Station 3 Station n

D9204 SD1204 Link status

Forward loopback • Loopback in reverse loop only

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (Continue) diagram (page 210)
Fig. 102 · Special Register List (Continue)

Master station Station 1 Station 2 Station 3 Station n

Stores the local or remote I/O station number at which loopback is being executed.

Station that implemented forward loopback

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Special Register List (Continue) diagram (page 210)
Fig. 103 · Special Register List (Continue)

Master station Station 1 Station 2 Station 3 Station n

D9205 SD1205

Forward loopback Reverse loopback In the example of above figure, "1" is stored into SD1205 and "3" into SD1206. If data link returns to normal status (data link in forward loop), values stored into SD1205, SD1206 do not return to "0". To return them to "0", therefore, sequence program must be used or reset operation performed.

Station that implemented reverse loopback

D9206 SD1206

Stores the number of retry times due to transmission error. Count stops at maximum of "FFFFH" . RESET to return the count to 0.

Stored as cumulative value

D9210 SD1210

Stores the number of times the loop line has been switched to reverse loop or loopback. Count stops at maximum of "FFFFH". RESET to return the count to 0.

Number of times loop selected

Stored as cumulative value

D9211 SD1211

Stores conditions for up to numbers 1 to 16

Stores the local station numbers which are in STOP or PAUSE mode.

Local station operation status

D9212 SD1212

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

Stores conditions for up to numbers 17 to 32

Local station operation status

SD1212

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

D9213 SD1213

SD1213

L32 L31 L30 L29 L28 L27

SD1214

L48 L47 L46 L45 L44 L43

When a local station is switched to STOP or PAUSE mode, the bit corresponding to the station number in the register becomes "1". Example: When station 7 switches to STOP mode,

SD1215

L64 L63 L62 L61 L60 L59

Stores conditions for up to numbers 33 to 48

Local station operation status

D9214 SD1214

Stores conditions for up to numbers 49 to 64

Local station operation status

bit 6 in SD1212 becomes "1" , and when SD1212 is monitored, its value is "64 (40H)".

D9215 SD1215

11 - 94 11 - 94

Show 10 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Reverse loopback · QnA · Station implementing loopback · Station implementing loopback · Number of retries · Bit Device number · QnA
Page 211 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9231 SD1231
Page 211 · click to enlarge
Page 211

Special Register List (Continue)

Special Register for Modification

Name Meaning Details Corresponding

Stores conditions for up to numbers 1 to 16

Station numbers of local stations that have detected errors are stored into corresponding data register bits as indicated below.

D9216 SD1216

Stores conditions for up to numbers 17 to 32

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

D9217 SD1217

SD1216

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

Local station error detect status

SD1217

L32 L31 L30 L29 L28 L27

Stores conditions for up to numbers 33 to 48

SD1218

L48 L47 L46 L45 L44 L43

If a local station detects an error, the bit corresponding to the station number becomes "1". Example: When station 6 and 12 detect an error, bits 5

SD1219

L64 L63 L62 L61 L60 L59

D9218 SD1218

Stores conditions for up to numbers 49 to 64

and 11 in SD1216 become "1", and when SD1216 is monitored, its value is "2080 (820H)".

D9219 SD1219

Stores conditions for up to numbers 1 to 16

Stores the local station numbers that have mismatches between the parameters of the master station of tier three and those of the master station in tier two in the three tier system or the remote I/O station numbers that have incorrect I/O assignment, as shown below in correspondence with the data register bits.

D9220 SD1220

Stores conditions for up to numbers 17 to 32

D9221 SD1221

Local station parameters non-conforming; remote I/O station I/O allocation error

Stores conditions for up to numbers 33 to 48

D9222 SD1222

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

SD1220

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

SD1221

L32 L31 L30 L29 L28 L27

SD1222

L48 L47 L46 L45 L44 L43

If a local station acting as the master station of tier three detects a parameter error or a remote station contains an invalid I/O assignment, the bit corresponding to the station number becomes "1". Example: When local station 5 and remote I/O station

SD1223

L64 L63 L62 L61 L60 L59

Stores conditions for up to numbers 49 to 64

D9223 SD1223

14 detect an error, bits 4 and 13 in SD1220 become "1" , and when SD1220 is monitored, its value is "8208 (2010H) " .

Stores conditions for up to numbers 1 to 16

Stores the local or remote station numbers while they are communicating the initial data with their relevant master station.

D9224 SD1224

Stores conditions for up to numbers 17 to 32

D9225 SD1225

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 L/R

SD1224

1 L/R

16 L/R

15 L/R

14 L/R

13 L/R

12 L/R

11 L/R

10 L/R

9 L/R

8 L/R

7 L/R

6 L/R

5 L/R

4 L/R

3 L/R

2 L/R

Local station and remote I/O station initial communications underway

SD1225

17 L/R

32 L/R

31 L/R

30 L/R

29 L/R

28 L/R

27 L/R

26 L/R

25 L/R

24 L/R

23 L/R

22 L/R

21 L/R

20 L/R

19 L/R

18 L/R

SD1226

48 L/R

47 L/R

46 L/R

45 L/R

44 L/R

43 L/R

42 L/R

41 L/R

40 L/R

39 L/R

38 L/R

37 L/R

36 L/R

35 L/R

34 L/R

Stores conditions for up to numbers 33 to 48

The bit corresponding to the station number which is currently communicating the initial settings becomes "1" . Example: When stations 23 and 45 are communicating,

33 L/R

64 L/R

63 L/R

62 L/R

61 L/R

60 L/R

59 L/R

58 L/R

57 L/R

56 L/R

55 L/R

54 L/R

53 L/R

52 L/R

51 L/R

50 L/R

D9226 SD1226

SD1227

Stores conditions for up to numbers 49 to 64

bit 6 of SD1225 and bit 12 of SD1226 become "1", and when SD1225 is monitored, its value is "64 (40H)", and when SD1226 is monitored, its value is "4096 (1000H)"

D9227 SD1227

Stores conditions for up to numbers 1 to 16

Stores the local or remote station numbers which are in error.

D9228 SD1228

Stores conditions for up to numbers 17 to 32

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 L/R

SD1228

1 L/R

16 L/R

15 L/R

14 L/R

13 L/R

12 L/R

11 L/R

10 L/R

9 L/R

8 L/R

7 L/R

6 L/R

5 L/R

4 L/R

3 L/R

2 L/R

D9229 SD1229

SD1229

17 L/R

32 L/R

31 L/R

30 L/R

29 L/R

28 L/R

27 L/R

26 L/R

25 L/R

24 L/R

23 L/R

22 L/R

21 L/R

20 L/R

19 L/R

18 L/R

Local station and remote I/O station error

SD1230

48 L/R

47 L/R

46 L/R

45 L/R

44 L/R

43 L/R

42 L/R

41 L/R

40 L/R

39 L/R

38 L/R

37 L/R

36 L/R

35 L/R

34 L/R

The bit corresponding to the station number with the error becomes "1" . Example: When local station 3 and remote I/O station

33 L/R

64 L/R

63 L/R

62 L/R

61 L/R

60 L/R

59 L/R

58 L/R

57 L/R

56 L/R

55 L/R

54 L/R

53 L/R

52 L/R

51 L/R

50 L/R

Stores conditions for up to numbers 33 to 48

SD1231

D9230 SD1230

Stores conditions for up to numbers 49 to 64

14 have an error, bits 2 and 13 of SD1228 become "1", and when SD1228 is monitored, its value is "8196 (2004H)".

D9231 SD1231

11 - 95 11 - 95

Show 8 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Bit Device number · Bit Device number · QnA · Bit Device number · Bit Device number
Page 212 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — D9245 SD1245
Page 212 · click to enlarge
Page 212

Special Register List (Continue)

Special Register for Modification

Name Meaning Details Corresponding

Stores conditions for up to numbers 1 to 8

D9232 SD1232

Stores the local or remote station number at which a forward or reverse loop error has occurred

Stores conditions for up to numbers 9 to 16

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

D9233 SD1233

R F R F R F R F R F R F R F R F

SD1232

L/R8 L/R7 L/R6 L/R5 L/R4 L/R3 L/R2 L/R1

R F R F R F R F R F R F R F R F

Stores conditions for up to numbers 17 to 24

SD1233

L/R16 L/R15 L/R14 L/R13 L/R12 L/R11 L/R10 L/R9

D9234 SD1234

R F R F R F R F R F R F R F R F

SD1234

L/R24 L/R23 L/R22 L/R21 L/R20 L/R19 L/R18 L/R17

R F R F R F R F R F R F R F R F

Stores conditions for up to numbers 25 to 32

SD1235

L/R32 L/R31 L/R30 L/R29 L/R28 L/R27 L/R26 L/R25

D9235 SD1235

R F R F R F R F R F R F R F R F

Local station and remote I/O station loop error

SD1236

L/R40 L/R39 L/R38 L/R37 L/R36 L/R35 L/R34 L/R33

Stores conditions for up to numbers 33 to 40

SD1237

R F R F R F R F R F R F R F R F

L/R48 L/R47 L/R46 L/R45 L/R44 L/R43 L/R42 L/R41

D9236 SD1236

R F R F R F R F R F R F R F R F

SD1238

L/R56 L/R55 L/R54 L/R53 L/R52 L/R51 L/R50 L/R49

Stores conditions for up to numbers 41 to 48

In the above table, "F" indicates a forward loop line and "R" a reverse loop line .The bit corresponding to the station number at which the forward or reverse loop error has occurred, becomes "1". Example: When the forward loop line of station 5 has an

SD1239

R F R F R F R F R F R F R F R F

L/R64 L/R63 L/R62 L/R61 L/R60 L/R59 L/R58 L/R57

D9237 SD1237

Stores conditions for up to numbers 49 to 56

D9238 SD1238

Stores conditions for up to numbers 57 to 64

error, bit 8 of SD1232 become "1", and when SD1232 is monitored, its value is "256 (100H)".

D9239 SD1239

Stores the number of times the following transmission errors have been detected: CRC, OVER, AB. IF Count is made to a maximum of FFFFH. RESET to return the count to 0.

Number of times communications errors detected

Stores cumulative total of receive errors

D9240 SD1240

  • Stores whether the slave station corresponds to MELSECNET or MELSECNET II.
  • Bits corresponding to the MELSECNET II stations become "1."
  • Bits corresponding to the MELSECNET stations or unconnected become "0."

Stores conditions for up to numbers 33 to 48

D9241 SD1241

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

SD1202

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

Local station link type

SD1203

L32 L31 L30 L29 L28 L27

SD1241

L48 L47 L46 L45 L44 L43

  • If a local station goes down during the operation, the contents before going down are retained. Contents of SD1224 to SD1227 and SD1228 to SD1231 are ORed. If the corresponding bit is "0", the corresponding bit of the special register above becomes valid.
  • If the own (master) station goes down, the contents before going down are also retained.

SD1242

L64 L63 L62 L61 L60 L59

Stores conditions for up to numbers 49 to 64

D9242 SD1242

Station number information for host station

Stores station number (0 to 64) Allows a local station to confirm its own station number

D9243 SD1243

D9244 SD1244

Number of link device stations

Stores number of slave stations Indicates the number of slave stations in one loop.

Stores the number of times the following transmission errors have been detected: CRC, OVER, AB. IF Count is made to a maximum of FFFFH. RESET to return the count to 0.

Number of times communications errors detected

Stores cumulative total of receive errors

D9245 SD1245

11 - 96 11 - 96

Show 6 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Bit Device number · QnA · Bit Device number
Page 213 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 97 11 - 97
Page 213 · click to enlarge
Page 213

Special Register List (Continue)

Special Register for Modification

Name Meaning Details Corresponding

Stores conditions for up to numbers 1 to 16

Stores the local station number which is in STOP or PAUSE mode.

D9248 SD1248

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

Stores conditions for up to numbers 17 to 32

SD1248

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

D9249 SD1249

SD1249

L32 L31 L30 L29 L28 L27

Local station operation status

SD1250

L48 L47 L46 L45 L44 L43

The bit corresponding to the station number which is in STOP or PAUSE mode, becomes "1". Example: When local stations 7 and 15 are in STOP mode,

SD1251

L64 L63 L62 L61 L60 L59

Stores conditions for up to numbers 33 to 48

D9250 SD1250

Stores conditions for up to numbers 49 to 64

bits 6 and 14 of SD1248 become "1", and when SD1248 is monitored, its value is "16448 (4040H)".

D9251 SD1251

Stores conditions for up to numbers 1 to 16

Stores the local station number other than the host, which is in error.

D9252 SD1252

Stores conditions for up to numbers 17 to 32

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

SD1252

L16 L15 L14 L13 L12 L11

L10 L9 L8 L7 L6 L5 L4 L3 L2 L1

D9253 SD1253

SD1253

L32 L31 L30 L29 L28 L27

Local station error conditions

SD1254

L48 L47 L46 L45 L44 L43

Stores conditions for up to numbers 33 to 48

The bit corresponding to the station number which is in error, becomes "1". Example: When local station 12 is in error, bit 11 of SD1252

SD1255

L64 L63 L62 L61 L60 L59

D9254 SD1254

Stores conditions for up to numbers 49 to 64

D9255 SD1255

becomes "1", and when SD1252 is monitored, its value is "2048 (800H) ".

(11) Fuse blown module

Number Name Meaning Explanation

ACPU D9

SD1300 D9100

  • The numbers of output modules whose fuses have blown are input as a bit pattern (in units of 16 points). (If the module numbers are set by parameter, the parameter-set numbers are stored.)
  • Also detects blown fuse condition at remote station output modules

SD1301 D9101

SD1302 D9102

SD1303 D9103

Bit pattern in units of 16 points, indicating the modules whose fuses have blown 0: No blown fuse 1: Blown fuse present

SD1304 D9104

SD1305 D9105

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

SD1306 D9106

0 0 0 1 (YC0) 0 1 (Y80) SD1300

SD1307 D9107

0 0 1 (Y1F0) 0 1 (Y1A) SD1301 0 0

0 0 1 (Y1F B0) 0 SD1331 0 0 0 1 (Y1F 30) 0

Indicates a blown fuse • Not cleared even if the blown fuse is replaced with a new one. This flag is cleared by error resetting operation.

SD1331

Bit pattern in units of 16 points, indicating the modules whose external power supply has been disconnected 0: External power supply disconnected 1: External power supply is not disconnected

The module number (in units of 16 points) whose external power supply has been disconnected is input as a bit pattern. (If the module numbers are set by parameter, the parameter-set numbers are used.)

External power supply disconnected module (For future expansion)

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

SD1350

0 0 0 1 0 1

S (Error) New QCPU Remote

SD1351

0 0 1 0 1 0 0

SD1381 0 0 1 0 1 0

Indicates a blown fuse

11 - 97 11 - 97

Show 18 more labels / short text on this page
ACPU Special Conversion · Special Register after · Conversion · Bit Device number · QnA · Bit Device number · Set by (When · Corresponding · Corresponding · set) · Fuse blown module · S (Error) · +Rem · SD1308 New · SD1309 to SD1330 · New · New · SD1350 to SD1381
Page 214 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 98 11 - 98
Page 214 · click to enlarge
Page 214

Special Register List (Continue) (12) I/O module verification

Number Name Meaning Explanation

ACPU D9

SD1400 D9116

  • When the power is turned on, the module numbers of the I/O modules whose information differs from the registered I/O module information are set in this register (in units of 16 points). (If the I/O numbers are set by parameter, the parameter-set numbers are stored.)
  • Also detects I/O module information 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

SD1401 D9117

SD1402 D9118

Bit pattern, in units of 16 points, indicating the modules with verification errors. 0: No I/O verification errors 1: I/O verification error present

SD1403 D9119

SD1404 D9120

SD1405 D9121

I/O module verification error

SD1406 D9122

1 ( ) 1 ( )

0 D9116

X Y

SD1407 D9123

0 D9117 0 0

X Y 190

0 0 1 ( )

0 D9123 0

X Y 1FE0

Indicates an I/O module verification error • Not cleared even if the blown fuse is replaced with a new one. This flag is cleared by error resetting operation.

SD1431

(13) For redundant systems (Host system CPU information 1) for Q4AR only SD1510 to SD1599 are only valid for redundant systems. They are all set to 0 for standalone systems.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — SD1431 diagram (page 214)
Fig. 104
  • Set the basic period (1 second units) use for the process control instruction using floating point data.
  • Shows the detailed error contents for the error that occurred in the process control instruction
  • Shows the error process block that occurred in the process control instruction.
  • Shows the power out time (S) during the automatic switch from hot start to initial start in the operation mode when the CPU module is started up.
  • Stores the request origin at work No. when the SM1590 is turned on.

1 Host system CPU information is stored.

11 - 98 11 - 98

Show 10 more labels / short text on this page
Set by (When · Corresponding · Corresponding · set) · S (Error) · +Rem · SD1408 New · SD1409 to SD1430 · New to New · New
Page 215 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 11 - 99 11 - 99
Page 215 · click to enlarge
Page 215

Special Register List (Continue) (14) For redundant systems (Other system CPU information 1) for Q4AR only SD1600 to SD1659 is only valid during the back up mode for redundant systems, and refresh cannot be done when in the separate mode. When a standalone system SD1600 to SD1699 are all 0.

Number Name Meaning Explanation Set by (When set)

ACPU SD 2

  • Stores as BIN code the error code of the error that occurred during the other system CPU diagnosis.
  • Stores the latest error currently occurring.

SD1600 Diagnosis error Diagnosis error

code.

SD1601

  • SD1600 stores the updated date and time.
  • Stores each of the BCD two digits.
  • Refer to SD1 to SD3 for the storage status. (SD1 SD1601, SD2 SD1602, SD3 SD1603)

Diagnosis error occurrence time

SD1602

Diagnosis error occurrence time

SD1603

  • Stores the error comment information/individual information classification code.
  • Refer to SD4 for the storage status.

SD1604

SD1605

SD1606

SD1607

SD1608

  • Stores the common information for the error code.
  • Refer to SD5 to SD15 for the storage status. (SD5 SD1605, SD6 SD1606, SD7 SD1607, SD8 SD1608, SD9 SD1609, SD10 SD1610, SD11 SD1611, SD12 SD1612, SD13 SD1613, SD14 SD1614, SD15 SD1615)

SD1609

SD1610

SD1611

SD1612

SD1613

SD1614

Q4AR

SD1615

SD1616

SD1617

SD1618

SD1619

  • Stores the individual information for the error code Refer to SD16 to SD26 for the storage status. (SD16 SD1616, SD17 SD1617, SD18 SD1618, SD19 SD1619, SD20 SD1620, SD21 SD1621, SD22 SD1622, SD23 SD1623, SD24 SD1624, SD25 SD1625, SD26 SD1626)

SD1620

SD1621

SD1622

SD1623

SD1624

SD1625

SD1626

SD1650 Switch status CPU switch status

  • Stores the CPU module switch status.
  • Refer to SD200 for the storage status. (SD1650 SD200)
  • Stores the CPU module's LED status.
  • Shows 0 when turned off, 1 when turned on, and 2 when flicking.
  • Refer to SD201 for the storage status. (SD1651 SD201)

SD1651 LED status CPU-LED status

SD1653 CPU operation status

  • Stores the CPU module operation status. Refer to SD203 for the storage status. (SD1653 SD203)

1 Stores other system CPU self-diagnosis information and system information. 2 Shows the special register (SD ) for the host system CPU.

(15) For redundant systems (Trucking) for Q4AR only

SD1700 to SD1799 is valid only for redundant systems. These are all 0 for standalone systems.

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — (15) For redundant systems (Trucking) for Q4AR only diagram (page 215)
Fig. 105 · (15) For redundant systems (Trucking) for Q4AR only

Trucking error detection count • Make it the trucking error detection +1. S (Error occurrence) New Q4AR

2 Shows the special register (SD ) for the host system CPU.

11 - 99 11 - 99

Show 25 more labels / short text on this page
Corresponding · Corresponding · S (Each · END) New · S (Each · END) New · Error information classification · Error information classification · S (Each · END) New · Error common information · Error common information · S (Each · END) New · Error individual information · Error individual information · S (Each · END) New · S (Each · END) New · S (Each · END) New · CPU operation status · S (Each · END) New
Page 216 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Intelligent function
Page 216 · click to enlarge
Page 216

MELSEC-Q APPENDICES

APPENDICES

APPENDIX 1 Error Code Return to Origin During General Data Processing

The CPU module returns an error code to the general data processing request origin when an error occurs and there is a general data processing request form the peripheral equipment, intelligent function module, or network system. If an error occurs when a general data processing is requested from the peripheral devices, intelligent function module, and network system.

App

POINT This error code is not an error that is detected by the CPU module self-diagnosis function, so it is not stored in the special relay (SD0). When the request origin is a GX Developer, a message or an error code is displayed. When the request origin is an intelligent function module or network system, an error is returned to the process that was requested.

APPENDIX 1.1 Error code overall explanation

These error codes differs depending on the error No. of the location the error was detected. The following table shows the relationship between the error detection location and the error code.

Error detection location Error Code (hexadecimal) Error description reference destination

CPU module 4000H to 4FFFH Refer to Appendix 1.2.

Intelligent function

module 7000 H to 7FFF H User's manuals of intelligent function module

Network system F000 H to FFFF H Q Corresponding MELSECNET/H Network System

Reference Manual

App - 1 App - 1

Page 217 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4011 H
Page 217 · click to enlarge
Page 217

MELSEC-Q APPENDICES

APPENDIX 1.2 Description of the errors of the error codes (4000H to 4FFFH)

The error contents of the error codes (4000H to 4FFFH) detected by the CPU module and the messages displayed by the GX Developer are shown below.

App

item Error description Countermeasure

4000H Sum check error Check the connection status of the connection cable with the CPU module

4001H Remote request that is not handled was executed. Check the requested remote operation.

4002 H

Command for which a global request cannot be performed was executed. Check the requested command.

4003 H

4004H CPU module cannot execute the request contents because it is in system protect Turn off the CPU module system protect switch.

4005H The volume of data handled according to the specified request is too large.

Reduce the volume of data to that which can be processed at the specified request.

4006H The password cannot be deleted. Delete the set password.

The CPU module is not BUSY (The buffer is not vacant). After the free time has passed, reexecute the request.

4008 H

4010H The CPU module is running to the request contents cannot be executed. Execute after setting the CPU module to STOP status.

CPU mode error The CPU module is not in the STEP-RUN status so the request contents cannot be executed.

Execute after setting the CPU module to STEP-RUN status.

4011 H

App - 2 App - 2

Error code (hexadecimal) · Error · CPU related error

Page 218 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — App - 3 App - 3
Page 218 · click to enlarge
Page 218

MELSEC-Q APPENDICES

item Error description Countermeasure

4021H The specified drive memory does not exist or there is an error. Check the specified drive memory status.

4022H The file with the specified file name or file No. does not exist. Check the specified file name and file No.

4023H The file name and file No. of the specified file do not match. Delete the file and then recreate the file.

4024H The specified file cannot be handled by a user. Do not access the specified file.

Forcefully execute the request forcibly. Or reexecute the request after the processing from the other location has ended.

4025H The specified file is processing the request from a different location.

4026H The keyword specification set in the corresponding drive memory is required.

Access by specifying the keyword set in the corresponding drive memory. 4027H The specified range exceeds the file range. Check the specified range and access within that range.

CPU file related error

4028H The same file already exists. Forcefully execute the request forcibly. Or reexecute after changing the file name.

Revise the specified file contents. Or reexecute after cleaning up and reorganizing the specified drive memory.

4029H The specified file capacity cannot be obtained.

402BH The request contents cannot be executed in the specified drive memory.

Do not execute a request for a specified drive memory in which an error has occurred.

Currently the request contents cannot be executed. Reexecute after the free wait time has passed.

402C H

4030H The specified device name cannot be handled. Check the specified device name. 4031H The specified device No. is outside the range. Check the specified device No.

CPU device specified error

4032H There is a mistake in the specified device qualification. Check the specified device qualification method.

Writing cannot be done because the specified device is for system use.

Do not write the data in the specified device, and do not turn on or off.

4033 H

4040H The request contents cannot be executed in the specified intelligent function module.

Do not conduct a request for a specified intelligent function module in which an error has occurred.

4041H The access range exceeds the buffer memory range of the specified intelligent function module.

Check the header address and access number of points and access using a range that exists in the intelligent function module.

Intelligent function module specification error

4042H The specified intelligent function module cannot be accessed.

Check that the specified intelligent function module is operating normally.

4043H The intelligent function module does not exist in the specified position.

Check the header I/O No. of the specified intelligent function module.

4044H A control bus error has occurred. Check that there is no error in the intelligent function module or in the hardware of another module.

4045H The setting required to conduct simulation has not been made. Conduct a simulation setting.

4046 H

The device header or number of points in the simulation is not in 16point unit.

Check the device header No. or number of points and correct them to 16 point units.

App - 3 App - 3

Error code (hexadecimal) · Error

Page 219 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 4083 H
Page 219 · click to enlarge
Page 219

MELSEC-Q APPENDICES

item Error description Countermeasure

4050H The request contents cannot be executed because the memory card write protect switch is on.

Turn off the memory card write protect switch.

  • Check the following and make it countermeasures.
  • Is the memory one that can be used?
  • Is the specified drive memory correctly installed?

4051H The specified device memory cannot be accessed.

4052H The specified file attribute is read only so the data cannot be written.

Do not write data in the specified file. Or change the file attribute.

Check the specified drive memory. Or reexecute write after changing the corresponding drive memory.

4053H An error occurred when writing data to the specified drive memory.

Check the specified drive memory. Or re-erase after replacing the corresponding drive memory.

An error occurred when deleting the data in the specified drive memory.

4054 H

4060H The monitor condition registration CPU module system area is already being used by another piece of equipment.

Reexecute monitor after the monitor by the other equipment has completed. Or increase the system area of the program memory using the format with option. 4061H Communication failed. Execute a re-communication.

Do not conduct monitor detail condi-tions from the specified equipment. Or reexecute monitoring after deleting the monitor detail conditions of the other equipment.

4062H The monitor detail condition is already being used and monitored by another piece of equipment.

4063H The number of the file lock registrations exceeds 16. Reduce the number of registrations to 16 or less.

4064H There is a problem with the specified contents. Check the specified contents.

4065H The device allocation information differs from the parameter.

Check the parameter. Or check the data.

4066H A keyword that differs from the keyword set in the specified driver memory has been specified. Check the specified keyword.

4067H The specified monitor file cannot be obtained. Conduct monitor after obtaining the monitor file.

4068H Registration/deletion cannot be conducted because the specified command is being executed.

Reexecute the command after the request from the other equipment has been completed.

4069H The conditions have already been reached by the device match.

Check the monitor conditions. Or reconduct monitor registration and execute monitor.

A drive other than Nos. 1 to 3 has been specified. Check the specified drive and specify the correct drive.

406A H

4070H Circuit inquiry Program before correction and the registration program differ.

Check the registration program and make the programs match. 4080H Data error Check the requested data contents. 4081H The sort subject cannot be detected. Check the data to be searched.

4082H The specified command is executing and therefore cannot be executed.

Reexecute the command after the request from the other equipment is completed.

Trying to execute a program that is not registered in the parameter. Register the program to be executed in the parameter.

4083 H

App - 4 App - 4

Show 5 more labels / short text on this page
Error code (hexadecimal) · Error · Protect error · Online registration error · Other errors
Page 220 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — 409F H
Page 220 · click to enlarge
Page 220

MELSEC-Q APPENDICES

item Error description Countermeasure

4084H The specified pointer P, I cannot be detected. Check the data to be searched.

4085H Pointer P, I cannot be specified because the program is not specified in the parameter.

Specify pointer P, I after registering the program to be executed in the parameter. 4086H Pointer P, I has already been added. Check the pointer No. to be added and make correction. 4087H Trying to specify too many pointers. Check the specified pointer and make a correction.

4088H The specified step No. was not in the instruction header. Check the specified step No. and make a correction.

4089H An END instruction was inserted/deleted while the CPU module was running.

Conduct Insert/removal after the CPU module has stopped.

408AH The file capacity was exceeded by the write during Run. Write the program after the CPU module has stopped.

The remote request cannot be executed. Reexecute after the CPU module is in a status where the mode request can be executed. 4090H The block breakpoint number was exceeded. Check the number of settings and make a correction.

408B H

4091H There is a mistake in the block breakpoint registration number.

Check the number of registrations and make a correction.

4092H The step breakpoint number has been exceeded.

Check the number of registrations and make a correction.

4093H There is a mistake in the step breakpoint registration number.

Check the number of registrations and make a correction.

4094H Tried to execute a request during block continuous processing. Reconduct the request after the processing has ended.

4095H Tried to execute a request during block forced execution processing. Reconduct the request after the processing has ended.

4096H Tried to execute a request during step continuous processing. Reconduct the request after the processing has ended.

4097H Tried to execute a request during step forced execution processing. Reconduct the request after the processing has ended.

Online registration errors during SFC STEP- RUN

4098H Tried to execute a request during one step continuous processing. Reconduct the request after the processing has ended.

4099H Tried to execute a request during one step forced execution processing. Reconduct the request after the processing has ended.

409AH Tried to execute a request during block forced end processing. Reconduct the request after the processing has ended.

409BH Tried to execute a request during step forced end processing. Reconduct the request after the processing has ended.

409CH Tried to execute a request during hold step reset processing. Reconduct the request after the processing has ended.

409DH A block No. that has not been created or that exceeds the range has been specified. Check the setting contents and make a correction.

409EH A step No. that was not created was specified. Check the setting contents and make a correction.

The specified number of cycles is outside the range.

Check the number of registrations and make a correction.

409F H

App - 5 App - 5

Error code (hexadecimal) · Error · Other errors

Page 221 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — App - 6 App - 6
Page 221 · click to enlarge
Page 221

MELSEC-Q APPENDICES

item Error description Countermeasure

40A0H A block No. outside the range was specified. Check the setting contents and make a correction.

40A1H A number of blocks that exceeds the range was specified. Check the number of settings and make a correction.

40A2H A step No. that is outside the range was specified. Check the setting contents and make a correction.

SFC device specification error

40A3H A number of steps that exceeds the range was specified. Check the number of settings and make a correction.

40A4H A sequence step No. outside the range was specified. Check the setting contents and make a correction.

40A5H The specified device was outside the range. Check the number of settings and make a correction.

There is a mistake in the block specification pattern or the step specification pattern. Check the setting contents and make a correction.

40A6 H

40B0H The wrong drive was specified. Check the setting contents and make a correction. 40B1H The specified program does not exist. Check the specified file name and make a correction.

40B2H The specified program was not an SFC program. Check the specified file name and make a correction.

SFC file related error

40B3 H

There was an SFC dedicated instruction in the write during run area. Check the setting contents and make a correction.

Increase the free space of the specified drive. Optimize the specified drive to increase continuous free areas. 41D1H The file pointer is insufficient. Specify the correct file pointer. 41D5H The file of the same name exists. Change the file name.

41D0H The route directory has no free space.

41DFH The disk is write-protected. Cancel the write protection of the disk and execute again. 41E0H The drive does not respond. Check for the specified drive. If it exists, check its status. 41E1H The address or sector is not found. Check if the target is a ROM drive or not. 41E4H The file cannot be accessed properly. Execute again after resetting the CPU module. 41E8H The drive format information is illegal. Format the target drive.

41E9H At the time of file access, time-out occurred during waiting for access. Execute again after some time.

41EBH The path name is too long. Check the length of the path name. 41ECH The disk is logically broken. Change the specified drive.

41EDH An attempt to make a file continuous failed. (There are enough free file areas, which cannot be taken continuously.)

Optimize the specified drive to increase continuous free areas.

41F2H The specified drive is ROM. Check the specified drive. (Format it for RAM.)

41FBH The same starting source has already opened the specified file. Check if it is being processed by another application.

41FCH An attempt was made to erase the mounted drive. Execute again after dismounting the drive.

41FDH The Flash ROM is not formatted. Erase the specified drive. 41FEH The memory card is not inserted. Insert or reinsert the memory card. 41FFH

The memory card type differs. Check the memory card type.

(1) The specified station could not be accessed

because a routing parameter was not set in the related station. (2) Though routing via the multiple CPU system

(1) Set the routing parameter for accessing the specified

station in the related station. (2) Try after a while. Or check if the system relaying the

4A00 H

is attempted, the control CPU of the network module that relays the data is not active.

data is active, then start communication.

4A01H The network with the No. set in the routing parameter does not exist.

Check the routing parameter set in the related station and make a correction.

4A02 H

Cannot access the specified station. Check if an error has occurred in the network module and if the module is offline.

Check if an error has occurred in the specified access destination or in a relay station to the access station and if so take countermeasures.

4B00H Object related error

An error occurred in the access destination or in a relay station.

App - 6 App - 6

Show 4 more labels / short text on this page
Error code (hexadecimal) · Error · File-related errors · Link related error
Page 222 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 222 · click to enlarge
Page 222

MELSEC-Q APPENDICES

APPENDIX 2 External Dimensions

APPENDIX 2.1 CPU module

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 222)
Fig. 106
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 222)
Fig. 107

Unit: mm (inch) APPENDIX 2.2 Power supply module

(1) Power Supply Module (Q61P-A1, Q61P-A2, Q62P, Q63P)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) APPENDIX 2.2 Power supply module diagram (page 222)
Fig. 108 · Unit: mm (inch) APPENDIX 2.2 Power supply module
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) APPENDIX 2.2 Power supply module diagram (page 222)
Fig. 109 · Unit: mm (inch) APPENDIX 2.2 Power supply module

Unit: mm (inch)

App - 7 App - 7

Page 223 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Q61SP
Page 223 · click to enlarge
Page 223

MELSEC-Q APPENDICES

(2) Power Supply Module (Q64P)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 223)
Fig. 110
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 223)
Fig. 111

Unit: mm (inch)

(3) Power Supply Module (Q61SP)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) diagram (page 223)
Fig. 112 · Unit: mm (inch)

Q61SP

POWER

INPUT

Q61SP

OUTPUT 5VDC 2A

ERR. 24VDC 0.5A

(FG)

(LG)

INPUT

100240V AC

MITSUBISHI

Unit: mm (inch)

App - 8 App - 8

50/60Hz 40VA 100-240VAC

Page 224 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 224 · click to enlarge
Page 224

MELSEC-Q APPENDICES

(4) Power Supply Module (A1S61PN, A1S62PN, A1S63P)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 224)
Fig. 113
Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 224)
Fig. 114

(0.26)

Unit: mm (inch)

App - 9 App - 9

Page 225 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 225 · click to enlarge
Page 225

MELSEC-Q APPENDICES

APPENDIX 2.3 Main base unit

(1) Main Base Unit (Q33B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 225)
Fig. 115

(0.30)

44.1 (1.74)

Unit: mm (inch)

(2) Main Base Unit (Q35B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) diagram (page 225)
Fig. 116 · Unit: mm (inch)

(0.30)

44.1 (1.74)

Unit: mm (inch)

(3) Main Base Unit (Q38B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) diagram (page 225)
Fig. 117 · Unit: mm (inch)

I/O1 I/O0 CPU I/O5 I/O4 I/O3 I/O2 I/O6 I/O7

(0.30)

44.1 (1.74)

Unit: mm (inch)

App - 10 App - 10

Page 226 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 226 · click to enlarge
Page 226

MELSEC-Q APPENDICES

(4) Main Base Unit (Q312B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 226)
Fig. 118

I/11 I/10 I/09 I/08 I/07 I/06 I/05 I/04 I/03 I/02 I/01 I/00 CPU POWER

Unit: mm (inch)

App - 11 App - 11

Page 227 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 227 · click to enlarge
Page 227

MELSEC-Q APPENDICES

APPENDIX 2.4 Slim type main base unit

(1) Main Base Unit (Q32SB)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 227)
Fig. 119

(0.30)

(0.33) (1.74)

Unit: mm (inch) (2) Main Base Unit (Q33SB)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) (2) Main Base Unit (Q33SB) diagram (page 227)
Fig. 120 · Unit: mm (inch) (2) Main Base Unit (Q33SB)

(0.30)

(1.74) (0.33)

Unit: mm (inch) (3) Main Base Unit (Q35SB)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) (3) Main Base Unit (Q35SB) diagram (page 227)
Fig. 121 · Unit: mm (inch) (3) Main Base Unit (Q35SB)

(0.30)

Unit: mm (inch)

App - 12 App - 12

Page 228 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 228 · click to enlarge
Page 228

MELSEC-Q APPENDICES

APPENDIX 2.5 Extension base unit

(1) Extension Base Unit (Q52B)

4-mounting screws (M4 14)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 228)
Fig. 122

Unit: mm (inch) (2) Extension Base Unit (Q55B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) (2) Extension Base Unit (Q55B) diagram (page 228)
Fig. 123 · Unit: mm (inch) (2) Extension Base Unit (Q55B)

Unit: mm (inch) (3) Extension Base Unit (Q63B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) (3) Extension Base Unit (Q63B) diagram (page 228)
Fig. 124 · Unit: mm (inch) (3) Extension Base Unit (Q63B)

Unit: mm (inch)

App - 13 App - 13

Page 229 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 229 · click to enlarge
Page 229

MELSEC-Q APPENDICES

(4) Extension Base Unit (Q65B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 229)
Fig. 125

Unit: mm (inch) (5) Extension Base Unit (Q68B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) (5) Extension Base Unit (Q68B) diagram (page 229)
Fig. 126 · Unit: mm (inch) (5) Extension Base Unit (Q68B)

Unit: mm (inch)

(6) Extension Base Unit (Q612B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) diagram (page 229)
Fig. 127 · Unit: mm (inch)

I/O11 I/O10 I/O9 I/O8 I/O7 I/O6 I/O5 I/O4 I/O3 I/O2 I/O1 I/O0

Unit: mm (inch)

App - 14 App - 14

Page 230 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — Unit: mm (inch)
Page 230 · click to enlarge
Page 230

MELSEC-Q APPENDICES

(7) Extension Base Unit (QA1S65B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 230)
Fig. 128

Unit: mm (inch) (8) Extension Base Unit (QA1S68B)

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — Unit: mm (inch) (8) Extension Base Unit (QA1S68B) diagram (page 230)
Fig. 129 · Unit: mm (inch) (8) Extension Base Unit (QA1S68B)

Unit: mm (inch)

App - 15 App - 15

Page 231 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — App - 16 App - 16
Page 231 · click to enlarge
Page 231

MELSEC-Q APPENDICES

APPENDIX 3 Upgraded Functions of High Performance Model QCPU

The High Performance model QCPU is upgraded to add functions and change the specifications. The functions and specifications that can be used by the High Performance model QCPU change depending on the function version/serial number. APPENDIX 3.1 Specification comparison

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 231)
Fig. 130

Serial No. of CPU Module Function Version A Function Version B

: Available, : N/A APPENDIX 3.2 Function comparison

Serial No. of CPU Module Function Version A Function Version B

: Available, : N/A

For function details, refer to the High Performance model QCPU (Q mode) User's Manual (Function Explanation, Program Fundamentals).

App - 16 App - 16

Page 232 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — GX Developer Added Function SW4D5C-GPPW-E SW5D5C-GPPW-E Version 6 Version 7 Version 7.10L
Page 232 · click to enlarge
Page 232

MELSEC-Q APPENDICES

APPENDIX 3.3 Added functions and the corresponding GX Developer versions

Mitsubishi Electronics PLC CPU Module (Q25HCPU) — MELSEC-Q APPENDICES diagram (page 232)
Fig. 131

GX Developer Added Function SW4D5C-GPPW-E SW5D5C-GPPW-E Version 6 Version 7 Version 7.10L

: Available, : N/A, — : Function not related to GX Developer

App - 17 App - 17

Page 235 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — WARRANTY
Page 235 · click to enlarge
Page 235

WARRANTY

Please confirm the following product warranty details before starting use. 1. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the dealer or Mitsubishi Service Company. Note that if repairs are required at a site overseas, on a detached island or remote place, expenses to dispatch an engineer shall be charged for. [Gratis Warranty Term]

The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range]

(1) The range shall be limited to normal use within the usage status, usage methods and usage environment, etc.,

which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product. (2) Even within the gratis warranty term, repairs shall be charged for in the following cases.

1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design. 2. Failure caused by unapproved modifications, etc., to the product by the user. 3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided. 4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced. 5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage. 6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi. 7. Any other failure found not to be the responsibility of Mitsubishi or the user. 2. Onerous repair term after discontinuation of production (1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.

Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc. (2) Product supply (including repair parts) is not possible after production is discontinued. 3. Overseas service Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ. 4. Exclusion of chance loss and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to damages caused by any cause found not to be the responsibility of Mitsubishi, chance losses, lost profits incurred to the user by Failures of Mitsubishi products, damages and secondary damages caused from special reasons regardless of Mitsubishi's expectations, compensation for accidents, and compensation for damages to products other than Mitsubishi products and other duties. 5. Changes in product specifications The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice. 6. Product application (1) In using the Mitsubishi MELSEC programmable logic controller, the usage conditions shall be that the application will

not lead to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault. (2) The Mitsubishi general-purpose programmable logic controller has been designed and manufactured for applications

in general industries, etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or National Defense purposes shall be excluded from the programmable logic controller applications. Note that even with these applications, if the user approves that the application is to be limited and a special quality is not required, application shall be possible. When considering use in aircraft, medical applications, railways, incineration and fuel devices, manned transport devices, equipment for recreation and amusement, and safety devices, in which human life or assets could be greatly affected and for which a particularly high reliability is required in terms of safety and control system, please consult with Mitsubishi and discuss the required specifications.

Page 236 of the Mitsubishi Electronics PLC CPU Module (Q25HCPU) user manual — INDUSTRIAL AUTOMATION
Page 236 · click to enlarge
Page 236

MITSUBISHI ELECTRIC

HEADQUARTERS

EUROPEAN REPRESENTATIVES

EUROPEAN REPRESENTATIVES

EUROPEAN REPRESENTATIVES

MITSUBISHI ELECTRIC EUROPE EUROPE B.V. Gothaer Straße 8 D-40880 Ratingen Phone: +49 (0) 21 02 / 486-0 Fax: +49 (0) 21 02 / 4 86-11 20 e mail: megfamail@meg.mee.com MITSUBISHI ELECTRIC FRANCE EUROPE B.V. 25, Boulevard des Bouvets F-92741 Nanterre Cedex Phone: +33 1 55 68 55 68 Fax: +33 1 55 68 56 85 e mail: factory.automation@fra.mee.com MITSUBISHI ELECTRIC UK EUROPE B.V. Travellers Lane GB-Hatfield Herts. AL10 8 XB Phone: +44 (0) 1707 / 27 61 00 Fax: +44 (0) 1707 / 27 86 95 MITSUBISHI ELECTRIC ITALY EUROPE B.V. Via Paracelso 12 I-20041 Agrate Brianza (MI) Phone: +39 039 6053 1 Fax: +39 039 6053 312 e mail: factory.automation@it.mee.com MITSUBISHI ELECTRIC SPAIN EUROPE B.V. Carretera de Rubí 76-80 E-08190 Sant Cugat del Vallés Phone: +34 9 3 / 565 3131 Fax: +34 9 3 / 589 2948 e mail: industrial@sp.mee.com MITSUBISHI ELECTRIC JAPAN CORPORATION Office Tower “Z” 14 F 8-12,1 chome, Harumi Chuo-Ku Tokyo 104-6212 Phone: +81 3 6221 6060 Fax: +81 3 6221 6075 MITSUBISHI ELECTRIC USA AUTOMATION 500 Corporate Woods Parkway Vernon Hills, IL 60061 Phone: +1 847 / 478 21 00 Fax: +1 847 / 478 22 83

GEVA AUSTRIA Wiener Straße 89 A-2500 Baden Phone: +43 (0) 2252 / 85 55 20 Fax: +43 (0) 2252 / 488 60 e mail: [email protected] TEHNIKON BELARUS Oktjabrskaya 16/5, Ap 704 BY-220030 Minsk Phone: +375 (0) 17 / 22 75 704 Fax: +375 (0) 17 / 22 76 669 e mail: tehnikon@belsonet.net Getronics b.v. BELGIUM Control Systems Pontbeeklaan 43 B-1731 Asse-Zellik Phone: +32 (0) 2 / 467 17 51 Fax: +32 (0) 2 / 467 17 45 e mail: infoautomation@getronics.com TELECON CO. BULGARIA 4, A. Ljapchev Blvd. BG-1756 Sofia Phone: +359 (0) 2 / 97 44 05 8 Fax: +359 (0) 2 / 97 44 06 1 e mail: — INEA CR d.o.o. CROATIA Drvinje 63 HR-10000 Zagreb Phone: +385 (0) 1 / 36 67 140 Fax: +385 (0) 1 / 36 67 140 e mail: — AutoCont CZECHIA Control Systems s.r.o. Nemocnicni 12 CZ-702 00 Ostrava 2 Phone: +420 59 / 6152 111 Fax: +420 59 / 6152 562 e mail: [email protected] louis poulsen DENMARK industri & automation Geminivej 32 DK-2670 Greve Phone: +45 (0) 43 / 95 95 95 Fax: +45 (0) 43 / 95 95 91 e mail: lpia@lpmail.com UTU Elektrotehnika AS ESTONIA Pärnu mnt.160i EE-11317 Tallinn Phone: +372 (0) 6 / 51 72 80 Fax: +372 (0) 6 / 51 72 88 e mail: [email protected] Beijer Electronics OY FINLAND Ansatie 6a FIN-01740 Vantaa Phone: +358 (0) 9 / 886 77 500 Fax: +358 (0) 9 / 886 77 555 e mail: [email protected] PROVENDOR OY FINLAND Teljänkatu 8 A 3 FIN-28130 Pori Phone: +358 (0) 2 / 522 3300 Fax: +358 (0) 2 / 522 3322 e mail: — UTECO A.B.E.E. GREECE 5, Mavrogenous Str. GR-18542 Piraeus Phone: +302 (0) 10 / 42 10 050 Fax: +302 (0) 10 / 42 12 033 e mail: [email protected] Meltrade Automatika Kft. HUNGARY 55, Harmat St. H-1105 Budapest Phone: +36 (0)1 / 2605 602 Fax: +36 (0)1 / 2605 602 e mail: [email protected]

MITSUBISHI ELECTRIC IRELAND EUROPE B.V. – Irish Branch Westgate Business Park IRL-Dublin 24 Phone: +353 (0) 1 / 419 88 00 Fax: +353 (0) 1 / 419 88 90 e mail: sales.info@meir.mee.com SIA POWEL LATVIA Lienes iela 28 LV-1009 Riga Phone: +371 784 / 22 80 Fax: +371 784 / 22 81 e mail: [email protected] UAB UTU POWEL LITHUANIA Savanoriu pr. 187 LT-2053 Vilnius Phone: +370 (0) 52323-101 Fax: +370 (0) 52322-980 e mail: [email protected] INTEHSIS SRL MOLDOVA, REPUBLIC OF Cuza-Voda 36/1-81 MD-2061 Chisinau Phone: +373 (0)2 / 562 263 Fax: +373 (0)2 / 562 263 e mail: intehsis@mdl.net Getronics b.v. NETHERLANDS Control Systems Donauweg 2 B NL-1043 AJ Amsterdam Phone: +31 (0) 20 / 587 67 00 Fax: +31 (0) 20 / 587 68 39 e mail: info.gia@getronics.com Beijer Electronics AS NORWAY Teglverksveien 1 N-3002 Drammen Phone: +47 (0) 32 / 24 30 00 Fax: +47 (0) 32 / 84 85 77 e mail: [email protected] MPL Technology Sp. z o.o. POLAND ul. Sliczna 36 PL-31-444 Kraków Phone: +48 (0) 12 / 632 28 85 Fax: +48 (0) 12 / 632 47 82 e mail: [email protected] SiriusTrading&Servicessrl ROMANIA Bd. Lacul Tei nr. 1 B RO-72301 Bucuresti 2 Phone: +40 (0) 21 / 201 7147 Fax: +40 (0) 21 / 201 7148 e mail: [email protected]

GTS TURKEY Darülaceze Cad. No. 43 KAT: 2 TR-80270 Okmeydani-Istanbul Phone: +90 (0) 212 / 320 1640 Fax: +90 (0) 212 / 320 1649 e mail: gts@turk.net CSC Automation Ltd. UKRAINE 15, M. Raskova St., Fl. 10, Office 1010 UA-02002 Kiev Phone: +380 (0) 44 / 238-83-16 Fax: +380 (0) 44 / 238-83-17 e mail: [email protected]

AFRICAN REPRESENTATIVE

CBI Ltd SOUTH AFRICA Private Bag 2016 ZA-1600 Isando Phone: +27 (0) 11/ 928 2000 Fax: +27 (0) 11/ 392 2354 e mail: cbi@cbi.co.za

MIDDLE EAST REPRESENTATIVE

TEXEL Electronics LTD. ISRAEL Box 6272 IL-42160 Netanya Phone: +972 (0) 9 / 863 08 91 Fax: +972 (0) 9 / 885 24 30 e mail: texel_me@netvision.net.il

EURASIAN REPRESENTATIVE

AVTOMATIKA SEVER RUSSIA Krapivnij Per. 5, Of. 402 RU-194044 St Petersburg Phone: +7 812 / 1183 238 Fax: +7 812 / 3039 648 e mail: [email protected] CONSYS RUSSIA Promyshlennaya St. 42 RU-198099 St Petersburg Phone: +7 812 / 325 36 53 Fax: +7 812 / 325 36 53 e mail: [email protected] ELEKTROSTYLE RUSSIA Ul Garschina 11 RU-140070 Moscowskaja Oblast Phone: +7 095/ 261 3808 Fax: +7 095/ 261 3808 e mail: — ICOS RUSSIA Industrial Computer Systems Zao Ryazanskij Prospekt 8a, Office 100 RU-109428 Moscow Phone: +7 095 / 232 - 0207 Fax: +7 095 / 232 - 0327 e mail: [email protected] NPP Uralelektra RUSSIA Sverdlova 11a RU-620027 Ekaterinburg Phone: +7 34 32 / 53 27 45 Fax: +7 34 32 / 53 27 45 e mail: [email protected] STC Drive Technique RUSSIA Poslannikov Per. 9, str.1 RU-107005 Moscow Phone: +7 095 / 786 21 00 Fax: +7 095 / 786 21 01 e mail: [email protected]

ACP Autocomp a.s. SLOVAKIA Chalupkova 7 SK-81109 Bratislava Phone: +421 (02) / 5292-22 54, 55 Fax: +421 (02) / 5292-22 48 e mail: [email protected]

INEA d.o.o. SLOVENIA Stegne 11 SI-1000 Ljubljana Phone: +386 (0) 1-513 8100 Fax: +386 (0) 1-513 8170 e mail: [email protected]

Beijer Electronics AB SWEDEN Box 426 S-20124 Malmö Phone: +46 (0) 40 / 35 86 00 Fax: +46 (0) 40 / 35 86 02 e mail: [email protected]

ECONOTEC AG SWITZERLAND Postfach 282 CH-8309 Nürensdorf Phone: +41 (0) 1 / 838 48 11 Fax: +41 (0) 1 / 838 48 12 e mail: [email protected]

MITSUBISHI ELECTRIC Gothaer Straße 8 Phone: +49 2102 486-0 Fax: +49 2102 486-7170 www.mitsubishi-automation.de D-40880 Ratingen Hotline: +49 1805 000-765 megfa-mail@meg.mee.com www.mitsubishi-automation.com

INDUSTRIAL AUTOMATION

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
1000Run mode suspended or failure of main CPU module (1) Malfunctioning due to noise or other reason (2) Hardware fault(1) Measure noise level. (2) Reset and establish the RUN status again. If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.136
1009Failure of the power supply module, CPU module, main base unit, extension base unit or extension cable is detected. p.136
1010Entire program was executed without the execution of an END instruction. (1) When the END instruction is executed it is read as another instruction code, e.g. due to noise. (2) The END instruction has been changed to another instruction code somehow.(1) Measure noise level. (2) Reset and establish the RUN status again. If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.136
1101Error in internal RAM/program memory where CPU module sequence program is stored.This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.136
1102Error in RAM used as CPU module work area. p.136
1103Internal CPU module device error. p.136
1104RAM Address error in CPU module. p.136
1105CPU shared memory fault(1) Measure noise level. (2) Reset and establish the RUN status again. If the same error is displayed again, this suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.136
1200The circuit that performs CPU internal index modification is not operating properly.This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.136
1201Internal CPU module hardware (logic) does not operate normally. p.136
1202The circuit that executes sequence processing in the CPU module does not operate properly. p.136
1203The operation circuit that conducts index modification in the CPU module is not operating properly.This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.136
1204The hardware (logic) in the CPU us not operating properly. p.136
1205The operation circuit that conducts sequence processing in the CPU in not operating properly. p.136
1206The DSP operation circuit in the CPU is not operating properly. p.136
1300There is an output module with a blown fuse.(1) Check ERR. LED of the output modules and replace the module whose LED is lit. (2) Read the common error information with the peripheral device and replace the fuse at the output module corresponding to the numerical value (module No.) reading. Alternatively, monitor special registers SD1300 to SD1331 with the peripheral device and change the fuse of the output module whose bit has a value of "1". p.136
1310An interruption has occurred although there is no interrupt module.One of the individual modules is experiencing hardware problems, so check the modules. Contact your nearest Mitsubishi representative and explain the problem with the defective module. p.136
1401• There was no response from the intelligent function module during initial communication stage. • The size of the buffer memory of the intelligent function module is wrong.The CPU module is experiencing hardware problems. Contact your nearest Mitsubishi representative. p.138
1402The intelligent function module was accessed in the program, but there was no response.This suggests a CPU module hardware error. Contact your nearest Mitsubishi representative. p.138
1403• There was no response from the intelligent function module when the END instruction is executed. • An error is detected at the intelligent function module.The intelligent function module that was being accessed is experiencing hardware problems. Contact your nearest Mitsubishi representative. p.138
1411When performing a parameter I/O allocation a special function module could not be accessed during initial communications. On error occurring, the head I/O number of the corresponding special function module is stored in the common information.A special function module, the CPU module, or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. p.138
1412The FROM/TO instruction set could not be executed, due to a system bus error with a special function module. On error occurring, the program error location is stored in the individual information. p.138
1413The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.(1) Change the High Performance model QCPU of function version A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. p.138
1414Fault of the loaded module was detected. The High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.(1) Change the High Performance model QCPU of function version A for the High Performance model QCPU of function version B. (2) An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. p.138
1415Fault of the main or extension base unit was detected.An intelligent function module, CPU module or the base unit is experiencing problems. Contact your nearest Mitsubishi representative. p.138
1416System bus fault was detected at PLC power-on or CPU module reset. p.138
1421Hardware fault at the system management module AS92R.This is experiencing hardware problems. Contact your nearest Mitsubishi representative. p.138
1500A momentary power supply interruption has occurred. The power supply went off.Check the power supply. p.138
1510The 5 VDC supplied to one of the two power-supply modules in the redundant system extension base unit has dropped below 85% of the rated voltage.Check the supply voltage of the power supply module. If the voltage is abnormal then replace the power supply module. p.138
1520The 5 VDC supplied to the power-supply modules in the extension base unit has dropped below 80% of the rated voltage. p.138
1530The 24 VDC power supplied to the system management module AS92R has dropped below 85% of the rated voltage.Check the power supply. p.138
1600(1) Voltage in the CPU module battery. (2) The CPU module battery is not connected.(1) Change the battery. (2) If the battery is for program memory, standard RAM or for the back-up power function, install a lead connector. p.138
1601Voltage of the battery on memory card 1 has dropped below stipulated level.Change the battery. p.138
1602Voltage of the battery on memory card 2 has dropped below stipulated level.Change the battery. p.138
2000I/O module information power ON is changed. I/O module (or special function module) not installed properly or installed on the base unit.Read the error common information at the peripheral device, and check and/or change the module that corresponds to the numerical value (module number) there. Alternatively, monitor the special registers SD1400 to SD1431 at a peripheral device, and change the fuse at the output module whose bit has a value of "1". p.138
2100Slot loaded with the QI60 is set to other than the Inteli (intelligent function module) or Interrupt (interrupt module) in the parameter I/O assignment.Make setting again to match the parameter I/O assignment with the actual loading status. p.140
210113 or more A-series special function modules (except for the QI60, A1SI61) that can initiate an interrupt to the CPU module have been installed.Keep the number of A-series special function modules that can initiate an interrupt (except for the QI60, A1SI61) to 12 or fewer. p.140
21027 or more A1SD51S have been installed.Keep the number of A1SD51S to 6 or fewer. p.140
2103(1) Two or more QI60/A1SI61 modules are loaded in a single-PLC system. (2) Two or more QI60/A1SI61 modules are set to the same control PLC in a multiple CPU system. (3) Two or more A1SI61 modules are loaded in a multiple CPU system.(1) Reduce the number of QI60/A1SI61 modules loaded in the single-PLC system to one. (2) Change the number of QI60/A1SI61 modules set to the same control PLC to only one in the multiple CPU system. (3) Reduce the number of A1SI61 modules to only one in the multiple CPU system. When using an interrupt module with each QCPU in a multiple CPU system, change it for the QI60. (Use one A1SI61 module + max. three QI60 modules or only the QI60 modules.) p.140
2104At the MELSECNET/MINI auto refresh parameter settings, the module allocation that was set is different from the actual module models at the station numbers in the link system.Reset the parameter MELSECNET/MINI auto refresh unit module allocation setting so that it conforms to the station number of the module that is actually linked. p.140
2105There are too many special function modules that can use dedicated instructions allocated (number of modules installed). (The total of the figures indicated below is above 1344.) (Number of AD59 modules installed × 5) (Number of AD57 (S1)/AD58 modules installed × 8) (Number of AJ71C24 (S3/S6/S8) modules installed × 10) (Number of AJ71UC24 modules installed × 10) (Number of AJ71C21 (S1) modules installed × 29) (Number of AJ71PT32-S3/AJ71T32-S3 modules installed × 125) (Number of AJ71QC24 (R2, R4) modules installed × 29) (Number of AJ71ID1 (2)-R4 modules installed × 18) (Number of AD75 modules installed × 12) Total > 1344Reduce the number of special function modules installed. : When the expansion mode is used. p.140
2106• Five or more MELSECNET/H modules are loaded in a whole multiple CPU system. • Five or more Q series Ethernet interface modules are loaded in a whole multiple CPU system.Reduce the number of modules to four or less in the whole multiple CPU system. p.140
2107Head X/Y set in the parameter I/O allocation settings is also the head X/Y for another module.Reset the parameter I/O allocation setting to conform with the actual status of the special function modules. p.140
2108(1) Network module A1SJ71LP21, A1SJ71BR11, A1SJ71AP21 , A1SJ71AR21, or A1SJ71AT2B dedicated for the A2USCPU has been installed. (2) Network module A1SJ71QLP21 or A1SJ71QBR11 dedicated for the Q2AS has been installed.Change network module to QJ71LP21 or QJ71BR11. p.140
2109 6The control system and standby system module configurations are different when a redundant system is in the backup mode.Check the module configuration of the standby system. p.140
2110Station not loaded was specified using the instruction whose target was the PLC share memory.Read the individual information of the error, check the program corresponding that value (program error location), and make correction. p.142
2111The location designated by a link direct device (J \ ) is not a network module. p.142
2112(1) The location designated by a special function module dedicated instruction is not a special function module. (2) The network number specified by the network dedicated instruction does not exist, or the network module is not the corresponding one. (3) Alternatively, it is not the relevant special function module.Read error individual information, then check and edit the special function module (Network module) dedicated instruction that corresponds to the numerical value there (program error location). p.142
2113The one specified in the network-dedicated instruction is not a network module, or a relay target network does not exist. p.142
2114An instruction, which on execution specifies other stations, has been used for specifying the host station. (An instruction that does not allow the host station to be specified).Read the individual information of the error, check the program corresponding that value (program error location), and make correction. p.142
2115An instruction, which on execution specifies the host station, has been used for specifying other stations. (An instruction that does not allow other stations to be specified). p.142
2116• An instruction that does not allow the module under the control of another station to be specified is being used for a similar task. • Instruction was executed for the A or QnA module under control of another station. p.142
2117A CPU module that cannot be specified in the instruction dedicated to the multiple CPU system was specified. p.142
2120The location of QCheck the location of the base unit. p.142
2121The CPU module is installed at other than the CPU slot or slots 0 to 2.Check the loading position of the CPU module and reinstall it at the correct slot. p.142
2126CPU module locations in a multiple CPU system are either of the following. (1) There are empty slots between the QCPU and QCPU/motion controller. (2) Modules other than the QCPU (including the motion controller) modules are loaded between the QCPU modules.(1) Eliminate empty slots between the CPU modules. (Set empty slots on the right side of the CPU modules.) (2) Remove the modules, which are not the QCPU modules, loaded between the QCPU modules, and fit the slots with the QCPUs. Load the motion controller modules on the right side of the QCPUs. p.142
2150In a multiple CPU system, the control PLC of the intelligent function module incompatible with the multiple CPU system is set to other than station 1.(1) Change the intelligent function module for the one compatible with the multiple CPU system (function version B). (2) Change the setting of the control CPU of the intelligent function module incompatible with the multiple CPU system to station 1. p.142
2200There is no parameter file at the drive designated by DIP switches as a valid drive.Check and correct the setting of the parameter enabled drive switch. Put a parameter file in the drive designated by the parameter enabled drive switch. p.142
2210The contents of the boot file are incorrect.Check the boot setting. p.142
2301(1) The memory card has not been formatted. (2) Memory card format status is incorrect.(1) Format memory card. (2) Reformat memory card. Check memory card. p.142
2302A memory card that cannot be used with the CPU module has been installed. p.142
2400Automatic write to standard ROM was performed on the CPU module that is incompatible with automatic write to standard ROM. (Memory card where automatic write to standard ROM was selected in the boot file was fitted and the parameter enable drive was set to the memory card.)(1) Execute automatic write to standard ROM on the CPU module which is compatible with automatic write to standard ROM. (2) Using GX Developer, perform write of parameters and programs to standard ROM. (3) Change the memory card for the one where automatic write to standard ROM has not been set, and perform boot operation from the memory card. p.142
2401Program memory capacity was exceeded by performing boot operation or automatic write to standard ROM.(1) Check and correct the parameters (boot setting). (2) Delete unnecessary files in the program memory. (3) Choose "Clear program memory" for boot in the parameter so that boot is started after the program memory is cleared. p.144
2410The file designated by the sequence program cannot be found.Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Create a file created using parameters, and load it to the CPU module. p.144
2411The sequence program designated a file that cannot be designated by the sequence program (comment file, etc.).Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. p.144
2412The SFC program file is one that cannot be designated by the sequence program. p.144
2413No data has been written to the file designated by the sequence program.Read the error individual information at the peripheral device, check to be sure that the program corresponds to the numerical values there (program location), and correct. Check to ensure that the designated file has not been write protected. p.144
2500There is a program file that uses a device that exceeds the device allocation range designated by the parameter device settings.Read the error common information at the peripheral device, check to be sure that the parameter device allocation setting and the program file device allocation correspond to the numerical values there (file name), and correct if necessary. p.144
2501There are multiple program files although "none" has been set at the parameter program settings.Edit the parameter program setting to "yes". Alternatively, delete unneeded programs. p.144
2502The program file is incorrect. Alternatively, the file contents are not those of a sequence program.Check whether the program version is .QPG, and check the file contents to be sure they are for a sequence program. p.144
2503There are no program files at all. Two or more SFC normal programs or control programs have been designated.Check program configuration. Check parameters and program configuration. p.144
3000In a multiple CPU system, the intelligent function module under control of another station is specified in the interrupt pointer setting of the parameter.(1) Specify the first I/O number of the intelligent function module under control of the host station. (2) Delete the interrupt pointer setting of the parameter. p.144
3001Parameter contents have been destroyed. p.144
3002When "use the following files" is selected for the file registers in the PLC file setting parameter, the specified file does not exist though the file register capacity has been set. p.144
3003The automatic refresh range of the multiple CPU system exceeded the file register capacity.Change the file register file for the one refresh-enabled in the whole range. p.144
3004The parameter file is incorrect. Alternatively, the contents of the file are not parameters.Check whether the parameter file version is .QPA, and check the file contents to be sure they are parameters. p.144
3006(1) The high speed interrupt parameter is set in a Q02CPU. (2) The high speed parameter is set in a multiple CPU system. (3) The high speed interrupt parameter is set when a QA1S B or QA B is used. (4) No module is installed at the I/O address designated by the high speed interrupt parameter.(1) Delete the setting of the Q02CPU’s high speed interrupt parameter. To use high speed interrupts, change the CPU module to one of the Q02H/Q06H/Q12H/Q25HCPU. (2) To use a multiple CPU system, delete the setting of the high- speed interrupt parameter. To use high speed interrupts, change the system to a single PLC system. (3) To use either the QA1S B or QA B, delete the setting of the high speed interrupt parameter. To use high speed interrupts, do not use the QA1S B/QA B. (4) Re-examine the I/O address designated by the high speed interrupt parameter. p.144
3009A modules are set to control PLCs in a multiple CPU system.Re-set the parameter I/O assignment to control them under one QCPU. (Change the parameters of all stations in the multiple CPU system.) p.144
3010The parameter-set number of CPU modules differs from the actual number in a multiple CPU system.Match (preset count of multiple PLC setting) - (CPU (empty) setting in I/O assignment) with the actual number of CPUs loaded. p.144
3012Multiple CPU setting or control PLC setting differs from that of the reference station in a multiple CPU system.Match the multiple PLC setting or control CPU setting in the parameter with that of the reference station (station 1). p.144
3013Multiple CPU automatic refresh setting is any of the followings in a multiple CPU system. (1) When a bit device is specified as a refresh device, a number other than a multiple of 16 is specified for the refresh-starting device. (2) The device specified is other than the one that may be specified. (3) The number of send points is an odd number.Check the following in the multiple CPU automatic refresh parameters and make correction. (1) When specifying the bit device, specify a multiple of 16 for the refresh starting device. (2) Specify the device that may be specified for the refresh device. (3) Set the number of send points to an even number. p.144
3100In a multiple CPU system, the MELSECNET/H under control of another station is specified as the first I/O number in the network setting parameter of the MELSECNET/H.(1) Delete the MELSECNET/H network parameter of the MELSECNET/H under control of another station. (2) Change the setting to the first I/O number of the MELSECNET/H under control of the host station. p.146
3101The link refresh range exceeded the file register capacity.Change the file register file for the one refresh-enabled in the whole range. p.146
3102An error was discovered when the network parameter check was made at the network module.(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact your nearest Mitsubishi representative. p.146
3103In a multiple CPU system, the Q series Ethernet interface module under control of another station is specified as the first I/O number of the Ethernet setting parameter.(1) Delete the Ethernet setting parameter of the Q series Ethernet interface module under control of another station. (2) Change the setting to the first I/O number of the Q series Ethernet interface module under control of the host station. p.146
3104Ethernet and MELSECNET/10 use the same network number. Network number, station number or group number set by the parameter is out of range. I/O number is out of range.(1) Write after correcting network parameters. (2) If the error persists after corrections have been made, contact your nearest Mitsubishi representative. p.146
3105In a multiple CPU system, the Q series CC-Link module under control of another station is specified as the first I/O number of the CC-Link setting parameter.(1) Delete the CC-Link setting parameter of the Q series CC-Link module under control of another station. (2) Change the setting to the first I/O number of the Q series CC- Link module under control of the host station. p.146
3106The CC-Link link refresh range exceeded the file register capacity.Change the file register file for the one refresh-enabled in the whole range. p.146
3107The contents of the CC-Link parameter are incorrect.Check the parameter setting. p.146
3200The parameter contents are incorrect.Write after correcting parameters. p.146
3201The contents of the SFC block attribute information are incorrect. p.146
3202The number of step relays designated in the parameters is less than the number used by the program. p.146
3203The execution type set for an SFC program in the parameters is other than the scan execution type. p.146
3300The first I/O number in the intelligent function module parameter set on GX Configurator differs from the actual I/O number.Check the parameter setting. p.146
3301The refresh setting of the intelligent function module exceeded the file register capacity.Change the file register file for the one which allows refresh in the whole range. p.148
3302The intelligent function module's refresh parameter are abnormal.Check the parameter setting. p.148
3303In a multiple CPU system, automatic refresh setting or similar parameter setting was made to the intelligent function module under control of another station.(1) Delete the automatic refresh setting or similar parameter setting of the intelligent function module under control of another station. (2) Change the setting to the automatic refresh setting or similar parameter setting of the intelligent function module under control of the host station. p.148
3400The first I/O number of the target module in the remote password file is set to other than 0H to 0FF0H.Change the first I/O number of the target module to within the 0H to 0FF0H range. p.148
3401Position specified as the first I/O number of the remote password file is incorrect due to one of the following reasons: • Module is not loaded. • Other than a Q-compatible intelligent function module (I/O, A, QnA module) • Intelligent function module other than QJ71C24(-R2) or Q series Ethernet interface module • QJ71C24(-R2) or Q series Ethernet interface module of function version ALoad the QJ71C24(-R2) or Q series Ethernet interface module of function version B in the position specified as the first I/O number of the remote password file. p.148
4000The program contains an instruction code that cannot be decoded. An unusable instruction is included in the program.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4001The program contains a dedicated instruction for SFC program although it is not an SFC program. p.148
4002The extension instruction designated by the program has an incorrect instruction name. p.148
4003The extension instruction designated by the program has an incorrect number of devices. p.148
4004The extension instruction designated by the program a device which cannot be used.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4010There is no END (FEND) instruction in the program.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4020The total number of internal file pointers used by the program exceeds the number of internal file pointers set in the parameters. p.148
4021The common pointer numbers used by individual files overlap. p.148
4030The allocation pointer numbers used by individual files are overlap. p.148
4100The instruction cannot process the contained data.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4101The designated device number for data processed by the instruction exceeds the usable range. Alternatively, the stored data or constants for the devices designated by the instruction exceeds the usable range. p.148
4102In a multiple CPU system, the link direct device (J \G ) was specified for the network module under control of another station.(1) Delete from the program the link direct device which specifies the network module under control of another station. (2) Using the link direct device, specify the network module under control of the host station. p.148
4103The configuration of the PID dedicated instruction is incorrect. p.148
410733 or more multiple CPU dedicated instructions were executed from one CPU module.Using the multiple CPU dedicated instruction completion bit, provide interlocks to prevent one CPU module from executing 32 or more multiple CPU dedicated instructions. p.148
4108The CC-Link parameter is not set when the CC-Link instruction is executed.Execute the CC-Link instruction after setting the CC-Link parameter. p.148
4109With high speed interrupt setting execute PR/PRC,UDCNT1/2,PWM,SPD,PLOADP,PUNLOADP,PAWPP instruction.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4200No NEXT instruction was executed following the execution of a FOR instruction.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4201A NEXT instruction was executed although no FOR instruction has been executed.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.148
4202More than 16 nesting levels are programmed.Keep nesting levels at 16 or under. p.150
4203A BREAK instruction was executed although no FOR instruction has been executed prior to that.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4210The CALL instruction is executed, but there is no subroutine at the specified pointer.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4211There was no RET instruction in the executed sub-routine program. p.150
4212The RET instruction was before the FEND instruction in the main program. p.150
4213More than 16 nesting levels are programmed.Keep nesting levels at 16 or under. p.150
4220Interrupt input was generated, but no corresponding interrupt pointer was found.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4221There was no IRET instruction in the executed interrupt program. p.150
4223The IRET instruction was before the FEND instruction in the main program. p.150
4230The number of CHK and CHKEND instructions is not equal. p.150
4231The number of IX and IXEND instructions is not equal. p.150
4235The configuration of the check conditions for the CHK instruction is incorrect. Alternatively, a CHK instruction has been used in a low speed execution type program. p.150
4300The designation of a MELSECNET/MINI-S3 master module control instruction was wrong.Read the common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4301The designation of an AD57/AD58 control instruction was wrong. p.150
4400No SFCP or SFCPEND instruction in SFC program.Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4410The block number designated by the SFC program exceeds the range. p.150
4411Block number designations overlap in SFC program. p.150
4420A step number designated in an SFC program exceeds 511. p.150
4421Total number of steps in all SFC programs exceed the rangeReduce total number of steps to below the maximum. p.150
4422Step number designations overlap in SFC program.Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4500The numbers of BLOCK and BEND instructions in an SFC program are not equal.Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4501The configuration of the STEP to TRAN to TSET to SEND instructions in the SFC program is incorrect. p.150
4502There was no STEPI p.150
4503The step designated by the TSET instruction in the SFC program does not exist. p.150
4504The step designated by the TAND instruction in the SFC program does not exist. p.150
4600The SFC program contains data that cannot be processed.Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. The program is automatically subjected to an initial start. p.150
4601Exceeds device range that can be designated by the SFC program. p.150
4602The START instruction in an SFC program is proceeded by an END instruction. p.150
4610The active step information at presumptive start of an SFC program is incorrect.Read common error information at a peripheral device, check error step corresponding to its numerical value (program error location), and correct the problem. p.150
4611Key-switch was reset during RUN when presumptive start was designated for SFC program. p.150
4620Startup was executed at a block in the SFC program that was already started up. p.150
4621Startup was attempted at a block that does not exist in the SFC program. p.150
4630Startup was executed at a block in the SFC program that was already started up. p.150
4631Startup was attempted at a block that does not exist in an SFC program. p.150
4632There were too many simultaneous active steps in blocks that can be designated by the SFC program. p.150
4633There were too many simultaneous active steps in all blocks that can be designated. p.150
5000Program scan time for initial execution type programs exceeds the initial execution WDT time setting designated in the PLC RAS parameter.Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary. p.150
5001The program scan time goes over the WDT value set in the parameter PLC RAS parameter. p.150
5010(1) The scan time of the program exceeded the constant scan setting time specified in the PC RAS setting parameter. (2) The low speed program execution time specified in the PC RAS setting parameter exceeded the margin time of constant scan.(1) Review the constant scan setting time. (2) Review the constant scan time and low speed program execution time in the parameter so that the margin time of constant scan may be fully reserved. p.150
5011Low speed scan type program scan time goes over the low speed execution WDT set in the parameter PC RAS settings.Read the error individual information at a peripheral device, check the numerical value (time) there, and shorten scan time if necessary. p.150
6000The control system and standby system in the redundant system do not have the same programs and parameters.Synchronise the programs and parameters of the control system and standby system. p.150
6010The operational status of the control system and standby system in the redundant system is not the same.Synchronise the operation statuses of the control system and standby system. p.150
6100A CPU module tracking memory error was detected during initial.Because this is a CPU module hardware error, contact your nearest Mitsubishi representative. To replace the module, replace the standby system CPU first, then the control system CPU. p.152
6101The CPU module detected an error during the handshake for tracking.Check the condition of the other stations. p.152
6200The standby system in a redundant system is switched to the control system.Check the control system condition. p.152
6210The control system in a redundant system is switched to the standby system.Check the control system condition. p.152
6220The standby system in a redundant system could not be switched from the control system to the standby system because of an error status or other reason.Check the standby system condition. p.152
6221Switching is disabled because of a bus switching module error.Because this is a bus switching module hardware error, contact your nearest Mitsubishi representative. p.152
6222Switching is disabled because a multiplexed master station of a remote I/O network was installed in the standby station during initial.Check the remote I/O network setting. p.152
7000(1) In a multiple CPU system, at CPU module fault occurred at a station where "all station stop by stop error of PLC " was selected in the operating mode. (2) High Performance model QCPU of function version A was loaded in a multiple CPU system.(1) Read the error individual information at a peripheral device, check the error of the PLC resulting in CPU module fault, and remove the error. (2) Remove the High Performance model QCPU of function version A from the main base unit. p.152
7002(1) There is no response from the target station in a multiple CPU system at initial communication stage. (2) High Performance model QCPU of function version A was loaded in a multiple CPU system configuration.(1) Reset the High Performance model QCPU and run it again. If the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative. (2) Remove the High Performance model QCPU of function version A from the main base unit. p.152
7003There is no response from the target station in a multiple CPU system at initial communication stage.Reset the High Performance model QCPU and run it again. If the same error is displayed again, it is a hardware fault of any CPU module. Consult your sales representative. p.152
7010(1) Faulty CPU is loaded in a multiple CPU system. (2) High Performance model QCPU of function version A is loaded in a multiple CPU system configuration. (An error is detected at the High Performance model QCPU of function version B.) (3) In a multiple CPU system, any of stations 2 to 4 was reset during power-on. (This error occurs at only the station which was reset.)(1) Read the error individual information at a peripheral device, and change the faulty station. (2) Change the station of function version A for function version B. (3) Do not reset the CPU modules of PLC No.2 to 4. Reset the High Performance model QCPU of PLC No.1 and restart the multiple CPU system. p.152
7020In a multiple CPU system, a PLC fault occurred at a station where "all station stop by stop error of PLC" was not selected in the operation mode. (The error is detected at the High Performance model QCPU of other than the station where the CPU module fault occurred.)Read the error individual information at a peripheral device, check the error of the CPU module resulting in CPU module fault, and remove the error. p.152
9000Annunciator F was set ONRead the error individual information at a peripheral device, and check the program corresponding to the numerical value (annunciator number). p.152
9010Error detected by the CHK instruction.Read the error individual information at a peripheral device, and check the program corresponding to the numerical value (error number) there. p.152
9020Storage of data onto ROM was completed normally in automatic write to standard ROM. (BOOT LED also flickers.)Set the parameter enable drive to standard ROM, switch power on again, and perform boot operation from standard ROM. p.152
10000In the multiple CPU system, an error occurred in the CPU module other than the Process CPU/High Performance model QCPU.Use the software package of the corresponding CPU module to check the details of the error that occurred. p.152
SD213value, and OFF if no error is detected. p.160
SD520Place of ms is stored (storage range: 0 to 65535) p.194
SD521Place of µs is stored (storage range: 0 to 900) p.194
SD523(Measurement is made in 100µs increments.) p.194
SD522Place of ms is stored (storage range: 0 to 65535) p.194
SD524Place of ms is stored (storage range: 0 to 65535) p.194
SD525Place of µs is stored (storage range: 0 to 900) p.194
SD526Place of ms is stored (storage range: 0 to 65535) p.194
SD527Place of µs is stored (storage range: 0 to 900) p.194
SD528Place of ms is stored (storage range: 0 to 65535) p.194
SD529Place of µs is stored (storage range: 0 to 900) p.194
SD532Place of ms is stored (storage range: 0 to 65535) p.194
SD533Place of µs is stored (storage range: 0 to 900) p.194
SD534Place of ms is stored (storage range: 0 to 65535) p.194
SD535Place of µs is stored (storage range: 0 to 900) p.194
SD540Place of ms is stored (storage range: 0 to 65535) p.194
SD541Place of µs is stored (storage range: 0 to 900) p.194
SD542Place of ms is stored (storage range: 0 to 65535) p.195
SD543Place of µs is stored (storage range: 0 to 900) p.195
SD544Place of ms is stored (storage range: 0 to 65535) p.195
SD545Place of µs is stored (storage range: 0 to 900) p.195
SD546Place of ms is stored (storage range: 0 to 65535) p.195
SD547Place of µs is stored (storage range: 0 to 900) p.195
SD548Place of ms is stored (storage range: 0 to 65535) p.195
SD549Place of µs is stored (storage range: 0 to 900) p.195
SD551Place of ms is stored (storage range: 0 to 65535) p.195
SD552Place of µs is stored (storage range: 0 to 900) p.195
B0Boot operation (QBT) p.196
B1Parameters (QPA) p.196
B2Device comments (QCD) p.196
B3Device initial value (QDI) p.196
B7Not used p.196
B8Not used p.196
B9CPU fault history (QFD) p.196
B10SFC trace (QTS) p.196
B11Local device (QDL) p.196
B13Not used p.196
B14Not used p.196
B15Not used p.196
D9125D9132. p.208
SD64SD71 contents one place. (When CPU has p.208
4000HSum check errorCheck the connection status of the connection cable with the CPU module p.217
4001HRemote request that is not handled was executed.Check the requested remote operation. p.217
4002HCommand for which a global request cannot be performed was executed.Check the requested command. p.217
4004HCPU module cannot execute the request contents because it is in system protectTurn off the CPU module system protect switch. p.217
4005HThe volume of data handled according to the specified request is too large.Reduce the volume of data to that which can be processed at the specified request. p.217
4006HThe password cannot be deleted.Delete the set password. p.217
4008HThe CPU module is not BUSY (The buffer is not vacant).After the free time has passed, reexecute the request. p.217
4010HThe CPU module is running to the request contents cannot be executed.Execute after setting the CPU module to STOP status. p.217
4011HThe CPU module is not in the STEP-RUN status so the request contents cannot be executed.Execute after setting the CPU module to STEP-RUN status. p.217
4021HThe specified drive memory does not exist or there is an error.Check the specified drive memory status. p.218
4022HThe file with the specified file name or file No. does not exist.Check the specified file name and file No. p.218
4023HThe file name and file No. of the specified file do not match.Delete the file and then recreate the file. p.218
4024HThe specified file cannot be handled by a user.Do not access the specified file. p.218
4025HThe specified file is processing the request from a different location.Forcefully execute the request forcibly. Or reexecute the request after the processing from the other location has ended. p.218
4026HThe keyword specification set in the corresponding drive memory is required.Access by specifying the keyword set in the corresponding drive memory. p.218
4027HThe specified range exceeds the file range.Check the specified range and access within that range. p.218
4028HThe same file already exists.Forcefully execute the request forcibly. Or reexecute after changing the file name. p.218
4029HThe specified file capacity cannot be obtained.Revise the specified file contents. Or reexecute after cleaning up and reorganizing the specified drive memory. p.218
402BHThe request contents cannot be executed in the specified drive memory.Do not execute a request for a specified drive memory in which an error has occurred. p.218
402CHCurrently the request contents cannot be executed.Reexecute after the free wait time has passed. p.218
4030HThe specified device name cannot be handled.Check the specified device name. p.218
4031HThe specified device No. is outside the range.Check the specified device No. p.218
4032HThere is a mistake in the specified device qualification.Check the specified device qualification method. p.218
4033HWriting cannot be done because the specified device is for system use.Do not write the data in the specified device, and do not turn on or off. p.218
4040HThe request contents cannot be executed in the specified intelligent function module.Do not conduct a request for a specified intelligent function module in which an error has occurred. p.218
4041HThe access range exceeds the buffer memory range of the specified intelligent function module.Check the header address and access number of points and access using a range that exists in the intelligent function module. p.218
4042HThe specified intelligent function module cannot be accessed.Check that the specified intelligent function module is operating normally. p.218
4043HThe intelligent function module does not exist in the specified position.Check the header I/O No. of the specified intelligent function module. p.218
4044HA control bus error has occurred.Check that there is no error in the intelligent function module or in the hardware of another module. p.218
4045HThe setting required to conduct simulation has not been made.Conduct a simulation setting. p.218
4046HThe device header or number of points in the simulation is not in 16point unit.Check the device header No. or number of points and correct them to 16 point units. p.218
4050HThe request contents cannot be executed because the memory card write protect switch is on.Turn off the memory card write protect switch. p.219
4051HThe specified device memory cannot be accessed.Check the following and make it countermeasures. • Is the memory one that can be used? • Is the specified drive memory correctly installed? p.219
4052HThe specified file attribute is read only so the data cannot be written.Do not write data in the specified file. Or change the file attribute. p.219
4053HAn error occurred when writing data to the specified drive memory.Check the specified drive memory. Or reexecute write after changing the corresponding drive memory. p.219
4054HAn error occurred when deleting the data in the specified drive memory.Check the specified drive memory. Or re-erase after replacing the corresponding drive memory. p.219
4060HThe monitor condition registration CPU module system area is already being used by another piece of equipment.Reexecute monitor after the monitor by the other equipment has completed. Or increase the system area of the program memory using the format with option. p.219
4061HCommunication failed.Execute a re-communication. p.219
4062HThe monitor detail condition is already being used and monitored by another piece of equipment.Do not conduct monitor detail condi-tions from the specified equipment. Or reexecute monitoring after deleting the monitor detail conditions of the other equipment. p.219
4063HThe number of the file lock registrations exceeds 16.Reduce the number of registrations to 16 or less. p.219
4064HThere is a problem with the specified contents.Check the specified contents. p.219
4065HThe device allocation information differs from the parameter.Check the parameter. Or check the data. p.219
4066HA keyword that differs from the keyword set in the specified driver memory has been specified.Check the specified keyword. p.219
4067HThe specified monitor file cannot be obtained.Conduct monitor after obtaining the monitor file. p.219
4068HRegistration/deletion cannot be conducted because the specified command is being executed.Reexecute the command after the request from the other equipment has been completed. p.219
4069HThe conditions have already been reached by the device match.Check the monitor conditions. Or reconduct monitor registration and execute monitor. p.219
406AHA drive other than Nos. 1 to 3 has been specified.Check the specified drive and specify the correct drive. p.219
4070HProgram before correction and the registration program differ.Check the registration program and make the programs match. p.219
4080HData errorCheck the requested data contents. p.219
4081HThe sort subject cannot be detected.Check the data to be searched. p.219
4082HThe specified command is executing and therefore cannot be executed.Reexecute the command after the request from the other equipment is completed. p.219
4083HTrying to execute a program that is not registered in the parameter.Register the program to be executed in the parameter. p.219
4084HThe specified pointer P, I cannot be detected.Check the data to be searched. p.220
4085HPointer P, I cannot be specified because the program is not specified in the parameter.Specify pointer P, I after registering the program to be executed in the parameter. p.220
4086HPointer P, I has already been added.Check the pointer No. to be added and make correction. p.220
4087HTrying to specify too many pointers.Check the specified pointer and make a correction. p.220
4088HThe specified step No. was not in the instruction header.Check the specified step No. and make a correction. p.220
4089HAn END instruction was inserted/deleted while the CPU module was running.Conduct Insert/removal after the CPU module has stopped. p.220
408AHThe file capacity was exceeded by the write during Run.Write the program after the CPU module has stopped. p.220
408BHThe remote request cannot be executed.Reexecute after the CPU module is in a status where the mode request can be executed. p.220
4090HThe block breakpoint number was exceeded.Check the number of settings and make a correction. p.220
4091HThere is a mistake in the block breakpoint registration number.Check the number of registrations and make a correction. p.220
4092HThe step breakpoint number has been exceeded.Check the number of registrations and make a correction. p.220
4093HThere is a mistake in the step breakpoint registration number.Check the number of registrations and make a correction. p.220
4094HTried to execute a request during block continuous processing.Reconduct the request after the processing has ended. p.220
4095HTried to execute a request during block forced execution processing.Reconduct the request after the processing has ended. p.220
4096HTried to execute a request during step continuous processing.Reconduct the request after the processing has ended. p.220
4097HTried to execute a request during step forced execution processing.Reconduct the request after the processing has ended. p.220
4098HTried to execute a request during one step continuous processing.Reconduct the request after the processing has ended. p.220
4099HTried to execute a request during one step forced execution processing.Reconduct the request after the processing has ended. p.220
409AHTried to execute a request during block forced end processing.Reconduct the request after the processing has ended. p.220
409BHTried to execute a request during step forced end processing.Reconduct the request after the processing has ended. p.220
409CHTried to execute a request during hold step reset processing.Reconduct the request after the processing has ended. p.220
409DHA block No. that has not been created or that exceeds the range has been specified.Check the setting contents and make a correction. p.220
409EHA step No. that was not created was specified.Check the setting contents and make a correction. p.220
409FHThe specified number of cycles is outside the range.Check the number of registrations and make a correction. p.220
40A0HA block No. outside the range was specified.Check the setting contents and make a correction. p.221
40A1HA number of blocks that exceeds the range was specified.Check the number of settings and make a correction. p.221
40A2HA step No. that is outside the range was specified.Check the setting contents and make a correction. p.221
40A3HA number of steps that exceeds the range was specified.Check the number of settings and make a correction. p.221
40A4HA sequence step No. outside the range was specified.Check the setting contents and make a correction. p.221
40A5HThe specified device was outside the range.Check the number of settings and make a correction. p.221
40A6HThere is a mistake in the block specification pattern or the step specification pattern.Check the setting contents and make a correction. p.221
40B0HThe wrong drive was specified.Check the setting contents and make a correction. p.221
40B1HThe specified program does not exist.Check the specified file name and make a correction. p.221
40B2HThe specified program was not an SFC program.Check the specified file name and make a correction. p.221
40B3HThere was an SFC dedicated instruction in the write during run area.Check the setting contents and make a correction. p.221
41D0HThe route directory has no free space.Increase the free space of the specified drive. Optimize the specified drive to increase continuous free areas. p.221
41D1HThe file pointer is insufficient.Specify the correct file pointer. p.221
41D5HThe file of the same name exists.Change the file name. p.221
41DFHThe disk is write-protected.Cancel the write protection of the disk and execute again. p.221
41E0HThe drive does not respond.Check for the specified drive. If it exists, check its status. p.221
41E1HThe address or sector is not found.Check if the target is a ROM drive or not. p.221
41E4HThe file cannot be accessed properly.Execute again after resetting the CPU module. p.221
41E8HThe drive format information is illegal.Format the target drive. p.221
41E9HAt the time of file access, time-out occurred during waiting for access.Execute again after some time. p.221
41EBHThe path name is too long.Check the length of the path name. p.221
41ECHThe disk is logically broken.Change the specified drive. p.221
41EDHAn attempt to make a file continuous failed. (There are enough free file areas, which cannot be taken continuously.)Optimize the specified drive to increase continuous free areas. p.221
41F2HThe specified drive is ROM.Check the specified drive. (Format it for RAM.) p.221
41FBHThe same starting source has already opened the specified file.Check if it is being processed by another application. p.221
41FCHAn attempt was made to erase the mounted drive.Execute again after dismounting the drive. p.221
41FDHThe Flash ROM is not formatted.Erase the specified drive. p.221
41FEHThe memory card is not inserted.Insert or reinsert the memory card. p.221
41FFHThe memory card type differs.Check the memory card type. p.221
4A00H(1) The specified station could not be accessed because a routing parameter was not set in the related station. (2) Though routing via the multiple CPU system is attempted, the control CPU of the network module that relays the data is not active.(1) Set the routing parameter for accessing the specified station in the related station. (2) Try after a while. Or check if the system relaying the data is active, then start communication. p.221
4A01HThe network with the No. set in the routing parameter does not exist.Check the routing parameter set in the related station and make a correction. p.221
4A02HCannot access the specified station.Check if an error has occurred in the network module and if the module is offline. p.221
4B00HAn error occurred in the access destination or in a relay station.Check if an error has occurred in the specified access destination or in a relay station to the access station and if so take countermeasures. p.221
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Input signal does not turn OFF.• Leakage current of input switch (e.g. drive by non-contact switch). AC input Leakage Input module current Power supply• Connect an appropriate resistor which will make the voltage across the terminals of the input module lower than the OFF voltage value. AC input Input module It is recommended to use 0.1 to 47 F + 47 to 120 (1/2W) for the CR constant. p.154
Input signal does not turn OFF.• Drive by a limit switch with neon lamp. AC input Leakage Input module current Power supply• Same as Example 1. • Or make up another independent display circuit. p.154
Input signal does not turn OFF.• Leakage current due to line capacity of wiring cable. (Line capacity C of twisted pair wire is approx. 100 pF/m). AC input Leakage Input module current Power supply• Same as Example 1. • However, leakage current is not generated when the power supply is located in the input equipment side as shown below. AC input Input module Power supply p.154
Input signal does not turn OFF.• Drive by switch with LED indicator. DC input (plus common) Leakage current Input module• Connect a register which will make the voltage between the input module terminal and common lower than the OFF voltage, as shown below. DC input (plus common) Resistor Input module A calculation example of a value for a connected resistor is given on the following page. p.154
Input signal does not turn OFF.• Sneak path due to the use of two power supplies. E1 E2 Input module E1>E2• Use only one power supply. • Connect a sneak path prevention diode. (Figure below) E1 E2 Input module p.155
False input due to noiseDepending on response time setting, noise is imported as input.Change response time setting. Example : 1ms 5ms (Setting of a shorter response time may produce a higher effect on periodic excessive noise.)If no effects are produced by the above, take basic actions to prevent excessive noise form entering, e.g. avoid bundling the power and I/O cables, and suppress noise by adding surge absorbers to such noise sources as relays and conductors used with the same power supply.) p.155
Excessive voltage is applied to load when output turns off.• When load is half-wave rectified inside (This is typical of some solenoids.) QY22 [1] Output module D1 C Load [2] • When the polarity of the power supply is [1], the capacitor C is charged. When the polarity is [2], the voltage charged in C plus the power supply voltage is applied to across D1. The maximum value of the voltage is approx. 2.2E. (This usage does not pose problems to the output components but may deteriorate the diode built in the load, causing burnout, etc.)• Connect a resistor of several ten K to several hundred K across the load. Resistor Load p.157
Load does not turn off. (Triac output)• Leakage current due to the built-in surge suppressor QY22 Output module Load Leakage current• Connect a resistor across the load. (If the wiring from the output module to the load is long, be careful since there may be a leakage current due to the line capacity.) Resistor Load p.157

Ask about the Mitsubishi Electronics PLC CPU Module (Q25HCPU)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions