Motion Controllers
Programming Manual
Common
Q173DCPU Q172DCPU
01 01 2008 B(NA)-0300134 Version A
MITSUBISHI ELECTRIC

Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. These precautions apply only to this product. Refer to the Q173DCPU/Q172DCPU Users manual for a description of the Motion controller safety precautions. In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Depending on circumstances, procedures indicated by CAUTION may also be linked to serious results. In any case, it is important to follow the directions for usage.
Please save this manual to make it accessible when required and always forward it to the end user.

Never open the front case or terminal covers while the power is ON or the unit is running, as this
may lead to electric shocks. Never run the unit with the front case or terminal cover removed. The high voltage terminal and
charged sections will be exposed and may lead to electric shocks. Never open the front case or terminal cover at times other than wiring work or periodic
inspections even if the power is OFF. The insides of the Motion controller and servo amplifier are charged and may lead to electric shocks.
Completely turn off the externally supplied power used in the system before mounting or removing the
module, performing wiring work, or inspections. Failing to do so may lead to electric shocks. When performing wiring work or inspections, turn the power OFF, wait at least ten minutes, and
then check the voltage with a tester, etc.. Failing to do so may lead to electric shocks. Be sure to ground the Motion controller, servo amplifier and servomotor. (Ground resistance :
100 or less) Do not ground commonly with other devices. The wiring work and inspections must be done by a qualified technician. Wire the units after installing the Motion controller, servo amplifier and servomotor. Failing to do
so may lead to electric shocks or damage. Never operate the switches with wet hands, as this may lead to electric shocks. Do not damage, apply excessive stress, place heavy things on or sandwich the cables, as this
may lead to electric shocks. Do not touch the Motion controller, servo amplifier or servomotor terminal blocks while the power
is ON, as this may lead to electric shocks. Do not touch the built-in power supply, built-in grounding or signal wires of the Motion controller
and servo amplifier, as this may lead to electric shocks.
incombustible. Installing them directly or close to combustibles will lead to fire. If a fault occurs in the Motion controller or servo amplifier, shut the power OFF at the servo
amplifier’s power source. If a large current continues to flow, fire may occur. When using a regenerative resistor, shut the power OFF with an error signal. The regenerative
resistor may abnormally overheat due to a fault in the regenerative transistor, etc., and may lead to fire. Always take heat measures such as flame proofing for the inside of the control panel where the
servo amplifier or regenerative resistor is installed and for the wires used. Failing to do so may lead to fire. Do not damage, apply excessive stress, place heavy things on or sandwich the cables, as this may
lead to fire.

Do not apply a voltage other than that specified in the instruction manual on any terminal.
Doing so may lead to destruction or damage. Do not mistake the terminal connections, as this may lead to destruction or damage. Do not mistake the polarity ( + / - ), as this may lead to destruction or damage. Do not touch the heat radiating fins of controller or servo amplifier, regenerative resistor and
servomotor, etc., while the power is ON and for a short time after the power is turned OFF. In this timing, these parts become very hot and may lead to burns. Always turn the power OFF before touching the servomotor shaft or coupled machines, as these
parts may lead to injuries. Do not go near the machine during test operations or during operations such as teaching.
Doing so may lead to injuries.
Strictly observe the following precautions.
Mistaken handling of the unit may lead to faults, injuries or electric shocks. (1) System structure
Always install a leakage breaker on the Motion controller and servo amplifier power source. If installation of an electromagnetic contactor for power shut off during an error, etc., is specified in
the instruction manual for the servo amplifier, etc., always install the electromagnetic contactor. Install the emergency stop circuit externally so that the operation can be stopped immediately and
the power shut off. Use the Motion controller, servo amplifier, servomotor and regenerative resistor with the correct
combinations listed in the instruction manual. Other combinations may lead to fire or faults. Use the CPU module, base unit and motion module with the correct combinations listed in the
instruction manual. Other combinations may lead to faults. If safety standards (ex., robot safety rules, etc.,) apply to the system using the Motion controller,
servo amplifier and servomotor, make sure that the safety standards are satisfied. Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in the system. In systems where coasting of the servomotor will be a problem during the forced stop, emergency
stop, servo OFF or power supply OFF, use dynamic brakes. Make sure that the system considers the coasting amount even when using dynamic brakes. In systems where perpendicular shaft dropping may be a problem during the forced stop,
emergency stop, servo OFF or power supply OFF, use both dynamic brakes and electromagnetic brakes.

The dynamic brakes must be used only on errors that cause the forced stop, emergency stop, or
servo OFF. These brakes must not be used for normal braking. The brakes (electromagnetic brakes) assembled into the servomotor are for holding applications,
and must not be used for normal braking. The system must have a mechanical allowance so that the machine itself can stop even if the
stroke limits switch is passed through at the max. speed. Use wires and cables that have a wire diameter, heat resistance and bending resistance
compatible with the system. Use wires and cables within the length of the range described in the instruction manual. The ratings and characteristics of the parts (other than Motion controller, servo amplifier and
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and servomotor. Install a cover on the shaft so that the rotary parts of the servomotor are not touched during
operation. There may be some cases where holding by the electromagnetic brakes is not possible due to the
life or mechanical structure (when the ball screw and servomotor are connected with a timing belt, etc.). Install a stopping device to ensure safety on the machine side.
CAUTION
Set the parameter values to those that are compatible with the Motion controller, servo amplifier,
servomotor and regenerative resistor model and the system application. The protective functions may not function if the settings are incorrect. The regenerative resistor model and capacity parameters must be set to values that conform to
the operation mode, servo amplifier and servo power supply module. The protective functions may not function if the settings are incorrect. Set the mechanical brake output and dynamic brake output validity parameters to values that are
compatible with the system application. The protective functions may not function if the settings are incorrect. Set the stroke limit input validity parameter to a value that is compatible with the system
application. The protective functions may not function if the setting is incorrect. Set the servomotor encoder type (increment, absolute position type, etc.) parameter to a value
that is compatible with the system application. The protective functions may not function if the setting is incorrect. Set the servomotor capacity and type (standard, low-inertia, flat, etc.) parameter to values that
are compatible with the system application. The protective functions may not function if the settings are incorrect. Set the servo amplifier capacity and type parameters to values that are compatible with the
system application. The protective functions may not function if the settings are incorrect.

Use the program commands for the program with the conditions specified in the instruction
manual. Set the sequence function program capacity setting, device capacity, latch validity range, I/O
assignment setting, and validity of continuous operation during error detection to values that are compatible with the system application. The protective functions may not function if the settings are incorrect. Some devices used in the program have fixed applications, so use these with the conditions
specified in the instruction manual. The input devices and data registers assigned to the link will hold the data previous to when
communication is terminated by an error, etc. Thus, an error correspondence interlock program specified in the instruction manual must be used. Use the interlock program specified in the intelligent function module's instruction manual for the
program corresponding to the intelligent function module.
CAUTION
Transport the product with the correct method according to the mass. Use the servomotor suspension bolts only for the transportation of the servomotor. Do not
transport the servomotor with machine installed on it. Do not stack products past the limit. When transporting the Motion controller or servo amplifier, never hold the connected wires or
cables. When transporting the servomotor, never hold the cables, shaft or detector. When transporting the Motion controller or servo amplifier, never hold the front case as it may fall
off. When transporting, installing or removing the Motion controller or servo amplifier, never hold the
edges. Install the unit according to the instruction manual in a place where the mass can be withstood. Do not get on or place heavy objects on the product. Always observe the installation direction. Keep the designated clearance between the Motion controller or servo amplifier and control panel
inner surface or the Motion controller and servo amplifier, Motion controller or servo amplifier and other devices. Do not install or operate Motion controller, servo amplifiers or servomotors that are damaged or
that have missing parts. Do not block the intake/outtake ports of the Motion controller, servo amplifier and servomotor with
cooling fan. Do not allow conductive matter such as screw or cutting chips or combustible matter such as oil
enter the Motion controller, servo amplifier or servomotor.

The Motion controller, servo amplifier and servomotor are precision machines, so do not drop or
apply strong impacts on them. Securely fix the Motion controller, servo amplifier and servomotor to the machine according to
the instruction manual. If the fixing is insufficient, these may come off during operation. Always install the servomotor with reduction gears in the designated direction. Failing to do so
may lead to oil leaks. Store and use the unit in the following environmental conditions.
When coupling with the synchronous encoder or servomotor shaft end, do not apply impact such
as by hitting with a hammer. Doing so may lead to detector damage. Do not apply a load larger than the tolerable load onto the synchronous encoder and servomotor
shaft. Doing so may lead to shaft breakage. When not using the module for a long time, disconnect the power line from the Motion controller
or servo amplifier. Place the Motion controller and servo amplifier in static electricity preventing vinyl bags and store. When storing for a long time, please contact with our sales representative.
Also, execute a trial operation.

CAUTION
Correctly and securely wire the wires. Reconfirm the connections for mistakes and the terminal
screws for tightness after wiring. Failing to do so may lead to run away of the servomotor. After wiring, install the protective covers such as the terminal covers to the original positions. Do not install a phase advancing capacitor, surge absorber or radio noise filter (option FR-BIF)
on the output side of the servo amplifier. Correctly connect the output side (terminal U, V, W). Incorrect connections will lead the
servomotor to operate abnormally. Do not connect a commercial power supply to the servomotor, as this may lead to trouble. Do not mistake the direction of the surge absorbing diode
installed on the DC relay for the control signal output of brake signals, etc. Incorrect installation may lead to signals not being output when trouble occurs or the protective functions not functioning. Do not connect or disconnect the connection cables between
Control output signal RA
each unit, the encoder cable or PLC expansion cable while the power is ON.
Securely tighten the cable connector fixing screws and fixing mechanisms. Insufficient fixing may
lead to the cables combing off during operation. Do not bundle the power line or cables.
CAUTION
Confirm and adjust the program and each parameter before operation. Unpredictable
movements may occur depending on the machine. Extreme adjustments and changes may lead to unstable operation, so never make them. When using the absolute position system function, on starting up, and when the Motion
controller or absolute value motor has been replaced, always perform a home position return.
Servo amplifier

CAUTION
Immediately turn OFF the power if smoke, abnormal sounds or odors are emitted from the Motion
controller, servo amplifier or servomotor. Always execute a test operation before starting actual operations after the program or
parameters have been changed or after maintenance and inspection. Do not attempt to disassemble and repair the units excluding a qualified technician whom our
company recognized. Do not make any modifications to the unit. Keep the effect or electromagnetic obstacles to a minimum by installing a noise filter or by using
wire shields, etc. Electromagnetic obstacles may affect the electronic devices used near the Motion controller or servo amplifier. When using the CE Mark-compliant equipment, refer to the "EMC Installation Guidelines" (data
number IB(NA)-67339) for the Motion controllers and refer to the corresponding EMC guideline information for the servo amplifiers, inverters and other equipment. Use the units with the following conditions.

CAUTION
If an error occurs in the self diagnosis of the Motion controller or servo amplifier, confirm the
check details according to the instruction manual, and restore the operation. If a dangerous state is predicted in case of a power failure or product failure, use a servomotor
with electromagnetic brakes or install a brake mechanism externally. Use a double circuit construction so that the electromagnetic brake operation circuit can be
operated by emergency stop signals set externally.
Shut off with the emergency stop signal(EMG).
Shut off with servo ON signal OFF, alarm, electromagnetic brake signal.
24VDC
If an error occurs, remove the cause, secure the safety and then resume operation after alarm
release. The unit may suddenly resume operation after a power failure is restored, so do not go near the
machine. (Design the machine so that personal safety can be ensured even if the machine restarts suddenly.)
CAUTION
Perform the daily and periodic inspections according to the instruction manual. Perform maintenance and inspection after backing up the program and parameters for the Motion
controller and servo amplifier. Do not place fingers or hands in the clearance when opening or closing any opening. Periodically replace consumable parts such as batteries according to the instruction manual. Do not touch the lead sections such as ICs or the connector contacts.
Before touching the module, always touch grounded metal, etc. to discharge static electricity from
human body. Failure to do so may cause the module to fail or malfunction. Do not directly touch the module's conductive parts and electronic components.
Touching them could cause an operation failure or give damage to the module. Do not place the Motion controller or servo amplifier on metal that may cause a power leakage
or wood, plastic or vinyl that may cause static electricity buildup.
Do not perform a megger test (insulation resistance measurement) during inspection.
Servomotor · Electro- magnetic brakes

When replacing the Motion controller or servo amplifier, always set the new module settings
correctly. When the Motion controller or absolute value motor has been replaced, carry out a home position
return operation using one of the following methods, otherwise position displacement could occur.
absolute position detector function is correct.
Do not drop or impact the battery installed to the module.
Doing so may damage the battery, causing battery liquid to leak in the battery. Do not use the dropped or impacted battery, but dispose of it. Do not short circuit, charge, overheat, incinerate or disassemble the batteries. The electrolytic capacitor will generate gas during a fault, so do not place your face near the
Motion controller or servo amplifier. The electrolytic capacitor and fan will deteriorate. Periodically replace these to prevent secondary
damage from faults. Replacements can be made by our sales representative.
When you discard Motion controller, servo amplifier, a battery (primary battery) and other option articles, please follow the law of each country (area).
This product is not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life. When considering this product for operation in special applications such as machinery or systems
used in passenger transportation, medical, aerospace, atomic power, electric power, or submarine repeating applications, please contact your nearest Mitsubishi sales representative. Although this product was manufactured under conditions of strict quality control, you are strongly
advised to install safety devices to forestall serious accidents when it is used in facilities where a breakdown in the product is likely to cause a serious accident.
CAUTION
All drawings provided in the instruction manual show the state with the covers and safety partitions removed to explain detailed sections. When operating the product, always return the covers and partitions to the designated positions, and operate according to the instruction manual.

The manual number is given on the bottom left of the back cover. Print Date Manual Number Revision Jan., 2008 IB(NA)-0300134-A First edition
Japanese Manual Number IB(NA)-0300126
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
A - 11


The following manuals are also related to this product.
In necessary, order them by quoting the details in the tables below.
Related Manuals (1) Motion controller
Manual Name Manual Number
Q173DCPU/Q172DCPU Motion controller User's Manual
This manual explains specifications of the Motion CPU modules, Q172DLX Servo external signal interface
module, Q172DEX Synchronous encoder interface module, Q173DPX Manual pulse generator interface
module, Power supply modules, Servo amplifiers, SSCNET cables, Synchronous encoder cables and
others.
Q173DCPU/Q172DCPU Motion controller (SV13/SV22) Programming Manual (Motion SFC)
This manual explains the functions, programming, debugging, error lists and others for Motion SFC.
Q173DCPU/Q172DCPU Motion controller (SV13/SV22) Programming Manual (REAL MODE)
This manual explains the servo parameters, positioning instructions, device lists, error lists and others.
Q173DCPU/Q172DCPU Motion controller (SV22) Programming Manual (VIRTUAL MODE)
This manual explains the dedicated instructions to use the synchronous control by virtual main shaft,
mechanical system program create mechanical module, servo parameters, positioning instructions, device
lists, error lists and others.

Manual Name Manual Number
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
This manual explains the specifications of the QCPU modules, power supply modules, base modules,
(13JR73)
extension cables, memory card battery and others.
QCPU User's Manual (Function Explanation, Program Fundamentals)
This manual explains the functions, programming methods and devices and others to create programs
(13JR74)
with the QCPU.
QCPU User's Manual (Multiple CPU System)
This manual explains the functions, programming methods and cautions and others to construct the
(13JR75)
Multiple CPU system with the QCPU.
QCPU (Q Mode)/QnACPU Programming Manual (Common Instructions)
This manual explains how to use the sequence instructions, basic instructions, application instructions and
(13JF58)
micro computer program.
QCPU (Q Mode)/QnACPU Programming Manual (PID Control Instructions)
This manual explains the dedicated instructions used to exercise PID control.
QCPU (Q Mode)/QnACPU Programming Manual (SFC)
This manual explains the system configuration, performance specifications, functions, programming,
debugging, error codes and others of MELSAP3.
I/O Module Type Building Block User's Manual
This manual explains the specifications of the I/O modules, connector, connector/terminal block
(13JL99)
conversion modules and others.
Manual Name Manual Number
MR-J3- B Servo amplifier Instruction Manual
This manual explains the I/O signals, parts names, parameters, start-up procedure and others for
MR-J3- B Servo amplifier.
Fully Closed Loop Control MR-J3- B-RJ006 Servo amplifier Instruction Manual
This manual explains the I/O signals, parts names, parameters, start-up procedure and others for Fully
(1CW304)
Closed Loop Control MR-J3- B-RJ006 Servo amplifier.


1. OVERVIEW
1.1 Overview
This programming manual describes the common items of each operating system software, such as the Multiple CPU system of the operating system software packages "SW8DNC-SV Q " for Motion CPU module (Q173DCPU/Q172DCPU).
In this manual, the following abbreviations are used.
Q173DCPU/Q172DCPU or Motion CPU (module) Q173DCPU/Q172DCPU Motion CPU module
Q172DLX Servo external signals interface module/ Q172DEX Serial Synchronous encoder interface module(Note-1)/ Q173DPX Manual pulse generator interface module
Q172DLX/Q172DEX/Q173DPX or Motion module
MR-J3- B Servo amplifier model MR-J3- B
AMP or Servo amplifier General name for "Servo amplifier model MR-J3- B"
QCPU, PLC CPU or PLC CPU module QnUD(H)CPU
Multiple CPU system or Motion system Abbreviation for "Multiple PLC system of the Q series"
CPUn Abbreviation for "CPU No.n (n= 1 to 4) of the CPU module for the Multiple CPU system"
Self CPU Motion CPU being programmed by the currently open MT Developer project
Programming software package General name for MT Developer/GX Developer/MR Configurator
Operating system software General name for "SW8DNC-SV Q "
SV13 Operating system software for conveyor assembly use (Motion SFC) : SW8DNC -SV13Q
SV22 Operating system software for automatic machinery use (Motion SFC) : SW8DNC -SV22Q
MT Developer Abbreviation for "Motion controller programming software MT Developer2 (Version 1.00A or later)"
GX Developer Abbreviation for "MELSEC PLC programming software package GX Developer (Version 8.48A or later)"
MR Configurator Abbreviation for "Servo setup software package MR Configurator (Version C0 or later)"
Manual pulse generator or MR-HDP01 Abbreviation for "Manual pulse generator (MR-HDP01)"
Serial absolute synchronous encoder or Q170ENC Abbreviation for "Serial absolute synchronous encoder (Q170ENC)"
SSCNET (Note-2) High speed synchronous network between Motion controller and servo amplifier
Absolute position system General name for "system using the servomotor and servo amplifier for absolute position"
Battery holder unit Battery holder unit (Q170DBATC)
External battery General name for "Q170DBATC" and "Q6BAT"
Intelligent function module Abbreviation for "MELSECNET/H module/Ethernet module/CC-Link module/ Serial communication module"
(Note-1) : Q172DEX can be used in SV22.
Generic term/Abbreviation Description

REMARK
For information about the each module, design method for program and parameter, refer to the following manuals relevant to each module.
Motion CPU module/Motion unit Q173DCPU/Q172DCPU User’s Manual
PLC CPU, peripheral devices for PLC program design, I/O
modules and intelligent function module Manual relevant to each module
Operation method for MT Developer Help of each software
Q173DCPU/Q172DCPU Motion controller (SV13/SV22)
Programming Manual (Motion SFC)
SV13/SV22 • Design method for positioning control
program in the real mode
Q173DCPU/Q172DCPU Motion controller (SV13/SV22)
Programming Manual (REAL MODE)
Q173DCPU/Q172DCPU Motion controller (SV22)
Programming Manual (VIRTUAL MODE)

1.2 Features
The Motion CPU and Multiple CPU system have the following features. 1.2.1 Features of Motion CPU
(a) Load distribution of processing can be performed by controlling the
complicated servo control with Motion CPU and the machine control or information control with PLC CPU. Therefore, the flexible system configuration can be realized.
(b) The Motion CPU and PLC CPU are selected flexibly, and the Multiple CPU
system up to 4 CPU modules can be realized. The Motion CPU module for the number of axis to be used can be selected.
The PLC CPU module for the program capacity to be used can be selected. (One or more PLC CPU is necessary with the Multiple CPU system.)
(c) The device data access of the Motion CPU and the Motion SFC program
start can be executed from PLC CPU by the Motion dedicated PLC instruction.
(a) The minimum operation cycle of the Motion CPU is made 0.44[ms], and it
correspond with high frequency operation.
(b) High speed PLC control is possible by the universal model QCPU.
(For LD instruction)

(3) Connection between the Motion controller and servo amplifier with
high speed synchronous network by SSCNET (a) High speed synchronous network by SSCNET connect between the
Motion controller and servo amplifier, and batch control the charge of servo parameter, servo monitor and test operation, etc. It is also realised reduce the number of wires.
(b) The maximum distance between the Motion CPU and servo amplifier, servo
amplifier and servo amplifier of the SSCNET cable on the same bus was set to 50(164.04)[m(ft.)], and the flexibility improved at the Motion system design.
By installing the operating system software for applications in the internal flash memory of the Motion CPU, the Motion controller suitable for the machine can be realized. And, it also can correspond with the function improvement of the software package.
(a) Conveyor assembly use (SV13)
Offer liner interpolation, circular interpolation, helical interpolation, constant- speed control, speed control, fixed-pitch feed and etc. by the dedicated servo instruction. Ideal for use in conveyors and assembly machines.
(b) Automatic machinery use (SV22)
Provides synchronous control and offers electronic cam control by mechanical support language. Ideal for use in automatic machinery.

1.2.2 Basic specifications of Q173DCPU/Q172DCPU
(1) Module specifications

Exterior dimensions [mm(inch)] 98 (3.85)(H) 27.4 (1.08)(W) 119.3 (4.69)(D)
specifications (a) Motion control specifications

Number of control axes Up to 32 axes Up to 8 axes
Interpolation functions Linear interpolation (Up to 4 axes), Circular interpolation (2 axes),
PTP(Point to Point) control, Speed control, Speed-position control, Fixed-pitch feed,
Constant speed control, Position follow-up control, Speed control with fixed position stop,
Speed switching control, High-speed oscillation control, Synchronous control (SV22)
Programming language Motion SFC, Dedicated instruction, Mechanical support language (SV22)
Proximity dog type (2 types), Count type (3 types), Data set type (2 types), Dog cradle type,
(Home position return re-try function provided, home position shift function provided)
operation function Possible to connect 12 modules Possible to connect 8 modules

Motion control specifications (continued)
Absolute position system Made compatible by setting battery to servo amplifier.
(Possible to select the absolute data method or incremental method for each axis)
(Note-1) 2 systems 1 system
(Note-1) : The servo amplifiers for SSCNET cannot be used.
(Note-2) : When using the incremental synchronous encoder (SV22 use), you can use above number of modules.
When connecting the manual pulse generator, you can use only 1 module.

(b) Motion SFC Performance Specifications
Code total (Motion SFC chart + Operation control + Transition)
543k bytes Motion SFC program capacity
Text total (Operation control + Transition) 484k bytes
Number of Motion SFC programs 256 (No.0 to 255)
Motion SFC chart size/program Up to 64k bytes (Included Motion SFC chart comments)
Number of Motion SFC steps/program Up to 4094 steps
Number of selective branches/branch 255
Number of parallel branches/branch 255
Parallel branch nesting Up to 4 levels
Number of operation control programs 4096 with F(Once execution type) and FS(Scan execution type) combined. (F/FS0 to F/FS4095)
Number of transition programs 4096(G0 to G4095)
Operation control program (F/FS) / Transition program (G)
Code size/program Up to approx. 64k bytes (32766 steps)
Number of blocks(line)/program Up to 8192 blocks (in the case of 4 steps(min)/blocks)
Number of characters/block Up to 128 (comment included)
Number of operand/block Up to 64 (operand: constants, word device, bit devices)
( ) nesting/block Up to 32 levels
Operation control program Calculation expression/bit conditional expression
Descriptive expression Transition program Calculation expression/bit conditional expression/
Number of multi execute programs Up to 256
Number of multi active steps Up to 256 steps/all programs
Normal task Execute in main cycle of Motion CPU
Fixed cycle Execute in fixed cycle (0.88ms, 1.77ms, 3.55ms, 7.11ms, 14.2ms)
Event task (Execution can be masked.)
Execute when input ON is set among interrupt module QI60
(16 points).
PLC interrupt Execute with interrupt instruction (D(P).GINT) from PLC CPU.
NMI task Execute when input ON is set among interrupt module QI60
(16 points).
Internal relays (M) 8192 points
Link relays (B) 8192 points
Annunciators (F) 2048 points
Number of devices (Device In the Motion CPU only) (Included the positioning dedicated device)
Special relays (SM) 2256 points
Data registers (D) 8192 points
Link registers (W) 8192 points
Special registers (SD) 2256 points
Motion registers (#) 8736 points
Coasting timers (FT) 1 point (888µs)
Multiple CPU area devices (U \G) Up to 14336 points usable
(Note): Usable number of points changes according to the system settings.

1.3 Hardware Configuration
This section describes the Q173DCPU/Q172DCPU system configuration, precautions on use of system, and configured equipments. 1.3.1 Motion system configuration
This section describes the equipment configuration, configuration with peripheral devices and system configuration in the Q173DCPU/Q172DCPU system.
Extension of the Q series module

Q6 B extension base unit (Q63B, Q65B, Q68B, Q612B)
It is possible to select the best according to the system.
(Note-1) : Be sure to install the Battery (Q6BAT) to the Battery holder unit (Q170DBATC). It is packed together with Q173DCPU/Q172DCPU.
(Note-2) : Q172DEX cannot be used in the extension base unit. Mount it to the main base unit.

(2) Peripheral device configuration for the Q173DCPU/Q172DCPU
The following (a)(b) can be used.
(b) RS-232 configuration



1.3.2 Q173DCPU System overall configuration
Motion CPU control module

: Stop signal : Lower stroke limit : Upper stroke limit
MR-J3- B model Servo amplifier, Up to 32 axes (Up to 16 axes/system)

CAUTION
Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in the system. The ratings and characteristics of the parts (other than Motion controller, servo amplifier and
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and servomotor. Set the parameter values to those that are compatible with the Motion controller, servo amplifier,
servomotor and regenerative resistor model and the system application. The protective functions may not function if the settings are incorrect.

1.3.3 Q172DCPU System overall configuration
Motion CPU control module

(Up to 6 modules) (Q170ENC) E Serial absolute synchronous encoder 2/module
: Stop signal : Lower stroke limit : Upper stroke limit

CAUTION
Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in the system. The ratings and characteristics of the parts (other than Motion controller, servo amplifier and
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and servomotor. Set the parameter values to those that are compatible with the Motion controller, servo amplifier,
servomotor and regenerative resistor model and the system application. The protective functions may not function if the settings are incorrect.

1.3.4 Software packages
(1) Software packages
(a) Operating system software


English version only.
R2000 English version operates normally.
R XP/Windows

R XP Home Edition (Service Pack 2 or later)
Corporation in the United States and/or other countries.
(Note-2) : Intel, Celeron and Pentium are trademarks of Intel Corporation in the U.S. and other countries.

(3) Operating system type/version
(a) Confirmation method in the operating system (CD)

Example) When using Q173DCPU, SV22 and version 00A.
The operating system(OS) type/version of connected CPU is displayed on the installation screen of MT Developer.
S V 2 2 Q A V E R 3 (OS software)
(a) PLC software package
Model name Software package
Model name Software package

POINTS (1) When the operation of Windows is not unclear in the operation of this software,
refer to the manual of Windows or guide-book from the other supplier. (2) The following functions cannot be used when the computer is running under
R 2000. This product may not perform properly, when these functions are used.
R Vista, Windows
R XP or Windows
< Windows
R 2000> • Large fonts

1.3.5 Restrictions on motion systems
(1) Combination of Multiple CPU system
(a) Motion CPU module cannot be used as standalone module.
Be sure to install the universal model PLC CPU module (Q03UDCPU/ Q04UDHCPU/Q06UDHCPU) to CPU No.1. For Universal model PLC CPU module, "Multiple CPU high speed taransmission function" must be set in the Multiple CPU settings.
(b) Only Multiple CPU high speed main base unit (Q38DB/Q312DB) can be
used.
(c) The combination of Q173DCPU/Q172DCPU and Q173HCPU(-T)/
Q172HCPU(-T)/Q173CPUN(-T)/Q172CPUN(-T) cannot be used.
(d) Up to four modules of PLC CPU modules (Q03UDCPU/Q04UDHCPU/
Q06UDHCPU/Motion CPU modules can be installed from the CPU slot (the slot on the right side of power supply module) to slot 2 of the main base unit. CPU modules called as CPU No.1 to CPU No.4 from the left sequentially. There is no restriction on the installation order of CPU No.2 to No.4. For CPU module except CPU No.1, an empty slot can be reserved for addition of CPU module. An empty slot can be set between CPU modules. However, the mounting condition when combining with the High performance PLC CPU module/Process CPU module/PC CPU module/C controller module is different depending on the specification of CPU modules, refer to the Manuals of each CPU modules.
(e) It takes about 10 seconds to startup (state that can be controlled) of Motion
CPU. Make a Multiple CPU synchronous startup setting suitable for the system.
(f) Execute the automatic refresh of the Motion CPU modules and PLC CPU
modules (Q03UDCPU/Q04UDHCPU/Q06UDHCPU) by using the automatic refresh of Multiple CPU high speed transmission area setting. When the High performance PLC CPU module/Process CPU module/PC CPU module/C controller module is mounted in the combination of Multiple CPU system, the Motion CPU module cannot be execute the automatic refresh with these modules.
(g) Use the Motion dedicated PLC instructions that starts by "D(P).". The Motion
dedicated PLC instructions that starts by "S(P)." cannot be used. When the High performance PLC CPU module/Process CPU module/PC CPU module/C controller module is mounted in the combination of Multiple CPU system, the Motion dedicated PLC instruction from these modules cannot be executed.

(2) Motion modules
(a) Installation position of Q172DEX(Note-1) is only the main base unit.
It cannot be used on the extension base unit.
(b) Q172DLX/Q173DPX can be installed on any of the main base unit/
extension base unit.
(c) Q172DLX/Q172DEX(Note-1)/Q173DPX cannot be installed in CPU slot and I/O
slot 0 to 2 of the main base unit. Wrong installation might damage the main base unit.
(d) Q172EX(-S1/-S2/-S3)/Q172LX/Q173PX(-S1) for Q173HCPU(-T)/
Q172HCPU(-T)/Q173CPUN(-T)/Q172CPUN(-T)/Q173CPU/Q172CPU cannot be used.
(e) Be sure to use the Motion CPU as the control CPU of Motion modules
(Q172DLX, Q172DEX(Note-1), Q173DPX, etc.) for Motion CPU. They will not operate correctly if PLC CPU is set and installed as the control CPU by mistake. Motion CPU is treated as a 32-point intelligent module by PLC CPU of other CPU. (Note-1) : Q172DEX can be used in SV22. It cannot be used in SV13.

(3) Other restrictions
(a) Motion CPU module cannot be set as the control CPU of intelligent function
module (except some modules) or Graphic Operation Terminal(GOT).
(b) Be sure to use the external battery.
(c) There are following methods to execute the forced stop input.
(d) Forced stop input for EMI terminal of Motion CPU module cannot be
invalidated by the parameter. When the device set in the forced stop input setting is used without use of EMI terminal of Motion CPU module, apply 24VDC voltage on EMI terminal and invalidate the forced stop input of EMI terminal.
(e) Be sure to use the cable for forced stop input (sold separately). The forced
stop cannot be released without using it.
(f) When the operation cycle is 0.4[ms], set the system setting as the axis select
switch of servo amplifier "0 to 7". If the axis select switch of servo amplifier "8 to F" is set, the servo amplifiers are not recognized.
(g) It is impossible to mount the main base unit by DIN rail when using the
Motion CPU module. Doing so could result in vibration that may cause erroneous operation.
(h) The module name displayed by "System monitor" - "Product information list"
of GX Developer is different depending on the function version of Motion modules (Q172DLX, Q172DEX, Q173DPX).
to the online module change.
Model display Module name
Function version "B" Function version "C"
Q172DEX MOTION-UNIT Q172DEX
Q173DPX MOTION-UNIT Q173DPX

MEMO

2. MULTIPLE CPU SYSTEM
2.1 Multiple CPU System
2.1.1 Overview
(1) What is Multiple CPU system ?
A Multiple CPU system is a system in which more than one PLC CPU module and Motion CPU module (up to 4 modules) are mounted on several main base unit in order to control the I/O modules and intelligent function modules. Each Motion CPU controls the servo amplifiers connected by SSCNET cable.
(a) By distributing such tasks as servo control, machine control and information
control among multiple processors, the flexible system configuration can be realized.
(b) You can increase the number of control axes by using a multiple Motion
CPU modules. It is possible to control up to 96 axes by using the three CPU modules (Q173DCPU).
(c) By distributing the high-load processing performed on a single PLC CPU
over several CPU modules, it is possible to reduce the overall system PLC scan time.
(a) Since device data of other CPUs can be automatically read by the automatic
refresh function, the self CPU can also use them as those of self CPU.
module/PC CPU module/C controller module is mounted in the combination of Multiple CPU system, the Motion dedicated PLC instruction from these modules cannot be executed.
(b) Motion dedicated PLC instructions can be used to access device data from
the PLC CPU to Motion CPU and start Motion SFC program.

2.1.2 Installation position of CPU module
Up to four PLC CPUs and Motion CPUs can be installed from the CPU slot (the right side slot of the power supply module) to slots 2 of the main base unit. The Motion CPU module cannot be installed in the CPU slot. The PLC CPU module must be installed in the CPU slot (CPU No.1) in the Multiple CPU system. There is no restriction on the installation order for CPU modules (CPU No.2 to 4). (Note): Refer to the manual for each CPU module when the High performance PLC
CPU module, Process CPU module, PC CPU module and C controller module is mounted in the combination of Multiple CPU.

An empty slot can be reserved for future addition of a CPU module. Set the number of CPU modules including empty slots in the Multiple CPU setting, and set the type of the slots to be emptied to "PLC (Empty)" in the CPU setting.
CPU 0 1 2
CPU 0 1 2
Q17 D
CPU Q17 D
Q17 D
CPU
CPU
CPU
CPU No.2 CPU No.1
CPU No.3
CPU No.4
CPU No.2 CPU No.1
CPU No.3
CPU No.4
CPU No.2 CPU No.1
CPU No.3
CPU No.4

2.1.3 Precautions for using I/O modules and intelligent function modules
(1) Modules controllable by the Motion CPU
The intelligent function modules of function version "B" or later support the Multiple CPU system. Be sure to use the PLC CPU as a control CPU because of the intelligent function modules cannot be controlled by the Motion CPU.
(a) The Motion CPU can access only the modules controlled by the self CPU. It
cannot access the modules controlled by other CPUs.
(b) Access range from non-controlled PLC CPU for the modules controlled by
the Motion CPU are shown below.

: Accessible : Inaccessible

2.1.4 Modules subject to installation restrictions
(1) Modules subject to install restrictions for the Motion CPU are sown below. Use
within the restrictions listed below.

(Note-1) : When the Manual pulse generator and the serial encoder are used at the same time with the SV22, the
Q173DPX installed in the slot of the smallest number is used for manual pulse generator input.
(Note-2) : SV22 only.
(2) A total of eight base units including one main base unit and seven extension base
units can be used. However, the usable slots (number of modules) are limited to 64 per system including empty slots. If a module is installed in slot 65 or subsequent slot, an error (SP. UNIT LAY ERROR) will occur. Make sure all modules are installed in slots 1 to 64. (Even when the total number of slots provided by the main base unit and extension base units exceeds 65 (such as when six 12-slot base units are used), an error does not occur as long as the modules are installed within slots 1 to 64.)

POINT (1) Q172DLX/Q172DEX/Q173DPX cannot be installed in CPU slot and I/O slot 0
to 2 of the main base unit. Wrong installation might damage the main base unit. (2) Q172DEX can be installed in the main base unit only. It cannot be used in the

2.1.5 How to reset the Multiple CPU system
The entire Multiple CPU system can be reset by resetting CPU No.1. The CPU modules of No.2 to No.4, I/O modules and intelligent function modules will be reset when PLC CPU No.1 is reset. If a stop error occurs in any of the CPUs on the Multiple CPU system, either reset CPU No.1 or restart the Multiple CPU system (power supply ON OFF ON) for recovery. (Recovery is not allowed by resetting the error-stopped CPU modules other than CPU No.1.)
POINT (1) It is not possible to reset the CPU modules of No.2 to No.4 individually in the
Multiple CPU system. If an attempt to reset any of those PLC CPU modules during operation of the Multiple CPU system, a "MULTI CPU DOWN (error code: 7000)" error will occur for the other CPUs, and the entire Multiple CPU system will be halted. However, depending on the timing in which any of PLC CPU modules other than No.1 has been reset, an error other than the "MULTI CPU DOWN" may halt the other PLC CPUs/Motion CPUs. (2) A "MULTI CPU DOWN (error code: 7000)" error will occur regardless of the
operation mode(All stop by stop error of CPU "n"/continue) set at the "Multiple CPU setting" screen when any of PLC CPU modules of No.2 to No.4 is reset. (Refer to Section 2.1.6.)

2.1.6 Operation for CPU module stop error
The entire system will behaves differently depending whether a stop error occurs in CPU No.1 or any of CPU No.2 to No.4 in the Multiple CPU system.
(a) A "MULTI CPU DOWN (error code: 7000)" error occurs at the other CPUs
and the Multiple CPU system will be halted when a stop error occurs at the PLC CPU No.1. (Note-1)
(b) The following procedure to restore the system is shown below.
All CPUs on the entire Multiple CPU system will be reset and the system will be restored when PLC CPU No. 1 is reset or the Multiple CPU system is reapplied.
Whether the entire system is halted or not is determined by the Multiple CPU setting's "Operating Mode" setting when a stop error occurs in a PLC CPU module/Motion CPU module other than CPU No.1. The default is set for all CPUs to be stopped with a stop error. When you do not want to stop all CPUs at occurrence of a stop error in a PLC CPU module/Motion CPU module, remove the check mark that corresponds to the CPU No. so that its error will not stop all CPUs. (See arrow A.)

(a) When a stop error occurs in the CPU module for which "All station stop by
stop error of CPU 'n' " has been set, a "MULTI CPU DOWN (error code: 7000)" error occurs for the other PLC CPU module/Motion CPU modules and the Multiple CPU system will be halted. (Note-1)

(b) When a stop error occurs in the CPU module for which " All station stop by
stop error of CPU 'n' " has not been set, a "MULTI EXE. ERROR (error code: 7010)" error occurs in all other CPUs but operations will continue. POINT (Note-1) : When a stop error occurs, a "MULTI CPU DOWN (error code : 7000)"
stop error will occur at the CPU on which the error was detected. Depending on the timing of error detection, a "MULTI CPU DOWN" error may be detected in a CPU of "MULTI CPU DOWN" status, not the first CPU on which a stop error occurs. Because of this, CPU No. different from the one of initial error CPU may be stored in the error data's common information category. To restore the system, remove the error cause on the CPU that is stopped by an error other than "MULTI CPU DOWN". In the screen below, the cause of the CPU No.2 error that did not cause the "MULTI CPU DOWN" error is to be removed.

(c) Observe the following procedures to restore the system.
All CPUs on the entire Multiple CPU system will be reset and the system will be restored when PLC CPU No.1 is reset or the power to the Multiple CPU system is reapplied.

(3) Operation at a Motion CPU error
Operations at a Motion CPU error are shown below.
Category Type of error Operation Remark
System setting error Does not operate from the
beginning (does not run).
No effect on other CPUs.
WDT error Varies depending on the error.
Other CPUs may also stop depending on
the parameter setting. Operation
Self-diagnosis error Stops at a CPU DOWN error.
STOP (M2000 OFF). Depends on
Other CPU DOWN error
the "Operation mode upon CPU
stop error" setting.
Self-diagnosis error Operation continues when the
continuous error occurred.
Processing stops for each
program may continue depending on the
program or axis instead of the
type of error).
Motion CPU stopping all the
processing.

2.2 Starting Up the Multiple CPU System
This section describes a standard procedure to start up the Multiple CPU system. 2.2.1 Startup Flow of the Multiple CPU System
Definition of functions with Multiple CPU system
Control and function executed in each CPU module are defined.
Application and assignment of device
Refer to Section 2.3
When automatic refresh of the CPU shared memory is performed, the number of refresh points is continuously obtained.
Refer to the "Q173DCPU/Q172DCPU User's Manual"
Select the module to achieve the function with the Multiple CPU system.
PLC CPU Motion CPU
Refer to the "Q173DCPU/Q172DCPU User's Manual"
Install the selected module on the main base unit and extension base unit.
Start-up of GX Developer
Refer to the GX Developer Manual.
Start-up GX Developer (Ver. 8.48A or later).
Creation of parameters, etc.
Create the parameters for CPU No. 1 to 4 and PLC programs.
Create the parameter such as Multiple CPU setting and control CPU setting, and the PLC program.
Refer to the "QCPU User's Manual" (Function Explanation/Program Fundamentals)".
Connection of PC to the PLC CPU module of CPU No. 1
Connect the PC that started GX Developer to the PLC CPU module of CPU No. 1 with the RS-232 cable/ USB cable.
Multiple CPU system power ON
Turn ON the power of Multiple CPU system in the following state of PLC CPU module of CPU No.1. RUN/STOP/RESET switch : STOP
Write of parameter and program
Write parameter and PLC program in the PLC CPU of CPU No. 1. For PLC CPU other than CPU No. 1, select the applicable PLC CPU by specifying the connection.
Selection of module · Installation of module · 1)

Start-up of MT Developer Refer to the help for operation of MT Developer.
Start-up MT Developer.
Creation of system settings and
Refer to Section 3.1 for system settings.
program, etc.
Refer to the Programming Manual of each operating system software for details of program.
Create the system settings, servo data and Motion SFC program.
Write to the Motion CPU
Write the system settings, servo data and Motion SFC program.
Switch setting for all CPUs
PLC CPU Motion CPU
Set RUN/STOP/RESET switch of PLC CPU modules and RUN/STOP switch of Motion CPU modules in CPU No.1 to 4 to RUN.
Reset PLC CPU module of CPU No.1
Set RUN/STOP/RESET switch of PLC CPU module in CPU No.1 to RESET to reset the entire system.
Status check in all CPU modules
Check if all CPUs of the Multiple CPU system are RUN status/error by resetting the CPU module of CPU No. 1.
Check and correction of errors
An error is checked with the PC diagnosis function of GX Developer and Motion CPU error batch monitor of MT Developer for correction.
PLC CPU Motion CPU
Debug of each CPU module
Multiple CPU system is debugged for each PLC CPU/Motion CPU.
Check in the automatic operation.
(Note) : Installation of the operating system software is required to the Motion CPU module before start of
the Multiple CPU system. Refer to Chapter 5 of the "Q173DCPU/Q172DCPU User's Manual" for installation of the Motion CPU operating system software.
1) · Motion CPU · Actual operation

2.3 Communication between the PLC CPU and the Motion CPU in the Multiple CPU System
(1) Structure of CPU shared memory
The CPU shared memory configuration and the availability of the communication from the self CPU using the CPU shared memory by program are shown below.

(1FFH)
(200H)
(7FFH)
(800H)
(FFFH) (1000H)
(270FH) (2710H)
Multiple CPU high speed transmission area (Variable size in 0 to 14k[points]: 1k words in unit)
: Communication allowed : Communication not allowed
CPU in the Motion CPU. Use the S. TO instruction to write to the user setting area of the self CPU in the PLC CPU. (Note-2) : Use the MULTR instruction to read the shared memory of self CPU and
other CPU in the Motion CPU. Use the FROM instruction/Multiple CPU area device (U \G ) to read the shared memory of the Motion CPU from the PLC CPU. (Note-3) : Refer to Section 2.3.2(1) for the access method of Multiple CPU high
speed transmission area.

(a) Self CPU operation information area (0H to 1FFH)
Name Detail Description (Note) Corresponding special register
0H Information availability Information availability flag
1H Diagnostic error Diagnostic error number An error No. identified during diagnosis is stored in BIN. SD0
2H The year and month that the error number was stored in the CPU shared memory's 1H address is stored with two digits of the BCD code.
3H The date and time that the error number was stored in the CPU shared memory's 1H address is stored with two digits of the BCD code.
Time the diagnostic error occurred
Time the diagnostic error occurred
The minutes and seconds that the error number was stored in the CPU shared memory's 1H address is stored with two digits of the BCD code.
SD3
Stores an identification code to determine what error information has been stored in the common error information and individual error information.
5H Error information identification code
Error information identification code
6H to 10H Common error information Common error information The common information corresponding to the error number identified during diagnosis is stored. SD5 to SD15
11H to 1BH Individual error information
The individual information corresponding to the error number identified during diagnostic is stored. SD16 to SD26
1CH Empty — Cannot be used —
1DH Switch status CPU switch status Stores the CPU module switch status. SD200
1EH Empty — Cannot be used —
1FH CPU operation status CPU operation status Stores the CPU module's operation status. SD203
(Note) : Refer to the corresponding special register for details.
The area used by the operating systems (OS) of the PLC CPU/Motion CPU.
(c) User setting area
The area for communication between CPU modules in the Multiple CPU system by MULTR/MULTW instruction of Motion CPU. (PLC CPU use FROM/S.TO instruction or Multiple CPU area devices to communicate between CPU modules.) Refer to the Programming Manual of operating system software for MULTR/MULTW instruction.

(d) Multiple CPU high speed transmission area
The area corresponding to the Multiple CPU high speed main base unit (Q3 DB) and Multiple CPU high speed transmission that uses the drive system controllers including QnUD(H)CPU and Motion CPU. The image chart of Multiple CPU high speed transmission area is shown below. Refer to Section 2.3.2(1) for access to the Multiple CPU high speed transmission area of self CPU and other CPU.
CPU No.1
CPU No.2
CPU No.3 CPU No.4
CPU No.1 Multiple CPU high speed transmission area (Transmission)
CPU No.1 Multiple CPU high speed transmission area (Reception)
CPU No.1 Multiple CPU high speed transmission area (Reception)
CPU No.1 Multiple CPU high speed transmission area (Reception)
CPU No.2 Multiple CPU high speed transmission area (Reception)
CPU No.2 Multiple CPU high speed transmission area (Transmission)
CPU No.2 Multiple CPU high speed transmission area (Reception)
CPU No.2 Multiple CPU high speed transmission area (Reception)
U3E2\G10000
CPU No.3 Multiple CPU high speed transmission area (Reception)
CPU No.3 Multiple CPU high speed transmission area (Reception)
CPU No.3 Multiple CPU high speed transmission area (Transmission)
CPU No.3 Multiple CPU high speed transmission area (Reception)
U3E3\G10000 CPU No.4 Multiple CPU high speed transmission area (Reception)
CPU No.4 Multiple CPU high speed transmission area (Reception)
CPU No.4 Multiple CPU high speed transmission area (Reception)
CPU No.4 Multiple CPU high speed transmission area (Transmission)
(Note-1) : The final device is "10000+(A 1024-B-1)". A : Data transmission size of each CPU (1k words in unit) B : Size used in the automatic refresh of each CPU. Refer to Section "2.3.2 Multiple CPU high speed transmission" for the size setting of A and B. (Note-2) : Transmission area to write/read in the self CPU. Reception area from the other CPU can be read only.
It is updated every 0.88ms.

2.3.2 Multiple CPU high speed transmission
(1) Multiple CPU high speed transmission
Multiple CPU high speed transmission is a function for fixed cycle data transmission between Multiple CPUs (Multiple CPU high speed transmission cycle is 0.88ms.). Secure data transmission is possible without effecting the PLC CPU scan time or Motion CPU main cycle because the data transmission and execution of PLC program and Motion SFC program can be executed with parallel processing. High speed response between multiple CPUs is realized by synchronizing the Multiple CPU high speed transmission cycle with Motion CPU operation cycle.
(a) Multiple CPU area device method

CPU shared memory (User setting area (Note-1)) PLC program Motion SFC program
1), 4) : Write data in the user setting area (Note-1) by the instruction that uses the Multiple CPU area device. 3), 6) : Read data from the user setting area (Note-1) by the instruction that uses the Multiple CPU area device. 2), 5) : Transmit the contents of user setting area (Note-1) to the other CPU with by Multiple CPU high speed transmission in 0.88ms cycle. Note-1: The area composed in the Multiple CPU high speed transmission area. (Refer to Section "(3) Memory configuration of Multiple CPU high speed transmission area".)

CPU shared memory address (decimal) (10000 to up to 24335)
First I/O number of CPU module
CPU No. First I/O number 3E0(H) CPU No.1
3E1(H) CPU No.2
3E2(H) CPU No.3
3E3(H) CPU No.4
: U \ G . Bit device
CPU shared memory address (decimal) (10000 to up to 24335)
First I/O number CPU module
CPU No. First I/O number 3E0(H) CPU No.1
3E1(H) CPU No.2
3E2(H) CPU No.3
3E3(H) CPU No.4
• Program which executes the positioning for Axis 1 to position set in the Multiple CPU high speed transmission memory 10400, 10401 of CPU No.1 at the speed set in the 10402, 10403 of CPU No.1, and uses bit 1 of CPU No.1 Multiple CPU high speed transmission memory 10404 of CPU No.1 as a cancel signal.
ABS-1 Axis 1, U3E0\G10400 Speed U3E0\G10402 Cancel U3E0\G10404.1
POINT This method can be used to access only the Multiple CPU high speed transmission area of CPU shared memory. It cannot be used to access the CPU shared memory (0 to 4095).
Word device

(b) Example of using automatic refresh method

Refresh at the timing of Motion CPU main cycle
1) Transmit the content of D0 to the automatic refresh area (Note-1) at the time of END processing by parameter setting. 2) Transmit the content of automatic refresh area (Note-1) to the other CPU by Multiple CPU high speed transmission at 0.88ms cycle. 3) Read the content of automatic refresh area (Note-1) at the time of Motion CPU main cycle and transmit it to D2000 by parameter setting. . Note-1: The area composed in the Multiple CPU high speed transmission area. (Refer to Section "(3) Memory configuration of Multiple CPU high speed transmission area".)
Multiple CPU high speed transmission can be used only between CPU modules for the Multiple CPU high speed transmission installed in the Multiple CPU high speed main base unit (Q3 DB). The system configuration specification is shown in Table 2.4. Table 2.4 System configuration to use Multiple CPU high speed

Base unit Multiple CPU high speed main base unit (Q3 DB) is used.
CPU module Q173DCPU/Q172DCPU and QnUD(H)CPU are used for CPU No. 2 to
"MULTI EXE. ERROR (error code: 7011) will occur if the power supply of Multiple CPU system is turned on without matching the system configuration shown in Table 2.4.

(3) Memory configuration of Multiple CPU high speed transmission
area Memory configuration of Multiple CPU high speed transmission area is shown below.

User setting area Multiple CPU high speed transmission area [Variable in 0 to 14k[points] (Note-1)] Automatic refresh area 7)
(Note-1): Multiple CPU high speed transmission area; 14k[points]: Maximum value when constituted with two CPUs 13k[points]: Maximum value when constituted with three CPUs 12k[points]: Maximum value when constituted with four CPUs


(4) Parameter setting
The parameter setting list for use with the Multiple CPU high speed transmission is shown in Table 2.6. Table 2.6 Multiple CPU high speed transmission parameter list
Name Description Target CPU
Set the size of the Multiple CPU high speed
transmission area allocated in each CPU module
which composes the Multiple CPU system.
Set the range to execute the data transmission by
the automatic refresh function among the user area
in the Multiple CPU high speed transmission area.
(a) Multiple CPU high speed transmission area setting
Multiple CPU high speed transmission area setting screen and setting range are shown below.

Table 2.7 Parameter setting items of Multiple CPU high speed transmission area setting
Item Setting description Setting/display value Restriction Consistency
CPU CPU No. corresponding to displayed parameters. CPU No.1 to No.4 — —
Set the number of points of data that each CPU module sends. Default value assigned to each CPU is shown below.
Default value of CPU specific
CPU specific send range
CPUs CPU No.1
CPU No.2
CPU No.3
CPU No.4
2 7k 7k — —
3 7k 3k 3k —
4 3k
Number of points used in the automatic refresh function is displayed. Number of points that is set by the "automatic refresh setting" is displayed.
Do not exceed the CPU specific send range [points]. —
Area size specified directly by program is displayed. The value where the "number of points set in the automatic refresh" is subtracted from the "CPU specific send range setting" is displayed.

POINT Selecting "Advanced setting" enables the ability to change the number of points from 1k to 2k in the system area used for Motion dedicated PLC instructions. Changing the number of points in the system area to 2k increases the number of Motion dedicated PLC instructions that can be executed concurrently in a scan. The screen where "Advanced setting" is selected is shown below. Refer to the "Q173DCPU/Q172DCPU Motion controller (SV13/SV22) Programming Manual (Motion SFC) " for the Motion dedicated PLC instruction.

Item Setting description Setting/display value (Points: Word in units) Restriction
be the following points or
lower.
When constituted with two
CPU specific send range
Set the number of points of data that each CPU module sends.
When constituted with four
Set the number of points for a system area to be assigned for each CPU module. (Default value of system area size is 1k [point].)
Display the total of number of points of the self CPU send area and the system area that are assigned to the each CPU module.
Set the total of all CPUs to 16.0k points or lower. —

(b) Automatic refresh setting
Setting for use of the automatic refresh function in the Multiple CPU high speed transmission area. Up to 32 setting ranges can be set for each CPU module. Automatic refresh setting screen and setting range are shown below.

Item Setting description Setting range Restriction
Select the CPU module for editing of the CPU specific send range setting. CPU No.1 to No.4
The setting No. for transmission of each CPU module is displayed. Automatic refresh is executed between devices set to the same setting No. for all CPUs that constitute the Multiple CPU system.
Setting No.
1 to 32 — —
Points Set the number of points for data communication.
Specifies the device which performs the data communication (automatic refresh). Specifies the device sent by the self CPU when the "Send source CPU selection" is the self CPU, and specifies the device received by the self CPU when the CPU specific send range setting is the other CPU.
Usable device ( X, Y, M, B, D, W, #, SM, SD) Note) Set "blank" when
automatic refresh is not executed.

POINT The processing performance of automatic refresh improves when devices are transmitted in 2 word sets. Therefore, it is recommended to set the start device as 2 word unit by inputting an even device number.
The example of setting automatic refresh is shown below.


Set the device received from CPU No.2.
Set the device transmitted to CPU No.1.


(Note) : The operation example of automatic refresh is shown on the next page.


POINT Set the following operation for automatic refresh setting using GX Developer. 1) Select tab "Multiple CPU high speed communication area setting". 2) Set "Use Multiple CPU high speed communication ".
The example of operating automatic refresh is shown below.
PLC CPU (CPU No.1) Motion CPU (CPU No.2)

(c) Data size consistency check
Whether the Multiple CPU setting parameters are the same for all CPUs or not is automatically checked. A "PARAMETER ERROR (error code: 3012, 3015) " will occur if they do not match.
b) Operation example

(5) Precautions
(a) Assurance of data sent between CPUs
Due to the timing of data sent from the self CPU and automatic refresh in any of the other CPUs, old data and new data may become mixed (data separation). The following shows the methods for avoiding data separation at communications by automatic refresh. 1) Data consistency for 32 bit data Transfer data with automatic refresh method is in units of 32 bits. Since automatic refresh is set in units of 32 bits, 32-bit data does not separate. • For word data 2 words data can be prevented from separating by using an even number to set the first number of each device in automatic refresh setting. 2) Data consistency for data exceeding 32 bits In automatic refresh method, data is read in descending order of the setting number in automatic refresh setting parameter. Transfer data separation can be avoided by using a transfer number lower than the transfer data as an interlock device.

2.3.3 Multiple CPU high speed refresh function
This function is used to update the data between internal devices of Motion CPU and the Multiple CPU high speed transmission area. This occurs every operation cycle as defined in the device setting of automatic refresh in the self CPU.
Classification Item Description Setting/display value Restriction
Setting No. Setting No. which executes high speed refresh is displayed.
1 to 128 (Up to 128)
CPU No. set in the automatic refresh setting is automatically displayed by setting devices. Self CPU : Refresh from the internal device
of Motion CPU to Multiple CPU high speed transmission area. Other CPU : Refresh form the Multiple CPU
CPU No. 1 to No.4
high speed transmission area to internal device of Motion CPU.
Set the device No. of Motion CPU to execute the high speed refreshes.
Set the number of points to refresh data of each data in word unit. (Note) Refresh is not executed when not set.
Refresh cycle Operation cycle (fixed) — —
(Note-1) : Point in word unit.

Multiple CPU high speed refresh function is used as in the following applications. 1) Read the data such as the real current value and synchronous encoder current value with PLC CPU at high speed. 2) Exchange the FIN waiting signal at high speed.

(2) Operation example of Multiple CPU high speed refresh function
The automatic refresh setting of Multiple CPU high speed refresh is shown below.

Set the device received from CPU No.2.
Set the device transmitted to CPU No.1.
Set the device to executed the Multiple CPU high speed refresh.

in "(b) Operation example".
(a) Parameter setting

POINT Set the following operation for automatic refresh setting using GX Developer. 1) Select tab "Multiple CPU high speed communication area setting". 2) Set "Use Multiple CPU high speed communication ".

1) · 2)

The example of operating Multiple CPU high speed refresh function is shown below.
PLC CPU (CPU No.1)
Motion CPU (CPU No.2)

(b) Operation example

2.3.4 Clock synchronization between Multiple CPU
The clock of each CPU is synchronized with the clock of CPU No. 1. The clock data used for synchronization in a Multiple CPU system can be edited.
Set the clock of CPU No.1. The Motion CPU module operates automatically by the clock of CPU No.1.
POINT The clock data of CPU No.1 is automatically set even if the clocks of CPU No. 2 to 4 are set independently.
All clocks are synchronized with CPU No.1 immediately after turning ON/resetting power and every 1-second interval thereafter.
The clock data that CPU No. 1 transmits is year, month, day, day of week, hour, minute and second.
Since CPU No.1 sets the clock data at 1-second intervals, an error of up to 1 second may occur to the clock of CPU No.2 to 4.

2.3.5 Multiple CPU synchronous startup
Multiple CPU synchronous startup function synchronizes the startups of CPU No.1 to CPU No.4. (It takes about ten seconds to startup for Motion CPU.) Since this function monitors the startup of each CPU module, when other CPU is accessed by a user program, an interlock program which checks the CPU module startup is unnecessary. With the Multiple CPU synchronous startup function, the startup is synchronized with the slowest CPU module to startup; therefore, the system startup may be slow.
POINT Multiple CPU synchronous startup function is for accessing each CPU module in a Multiple CPU system without needing an interlock. This function is not for starting an operation simultaneously among CPU modules after startup.
To use the Multiple CPU synchronous startup function, check No.1 to No.4 of target CPU in Multiple CPU settings in system setting of MT Developer. (Set it in the Multiple CPU setting of PLC parameter setting of GX Developer for QnUD(H)CPU.) "Set Sync. startup setting of CPU " is set for No.1 to 4 at default.

Set the same Multiple CPU synchronous startup for all CPUs that constitute the Multiple CPU system. The self-diagnosis error "PARAMETER ERROR (error code: 3015)" will occur if all CPU modules that constitute the Multiple CPU system do not have the same setting. When this function is not used (each CPU startup without synchronization), startup of each CPU module can be confirmed by using special relays SM220 to SM223 (CPU No.1 to 4 READY complete flag).

2.3.6 Control Instruction from PLC CPU to Motion CPU
Control can be instructed from the PLC CPU to the Motion CPU using the Motion dedicated PLC instructions listed in the table below. Refer to the "Q173DCPU/Q172DCPU Motion controller (SV13/SV22) Programming Manual (Motion SFC)" for the details of each instruction. (Control may not be instructed from one Motion CPU to another Motion CPU.)

D(P).SFCS Start request of the Motion SFC program (Program No. may be specified.)
D(P).CHGA Current value change request of the specified axis
D(P).CHGT Torque control value change request of the specified axis
D(P).GINT Execute request of an event task to the other CPU (Motion CPU)
D(P).DDWR Write device data of the self CPU (PLC CPU) to the device of other CPU
D(P).DDRD Read device data of other CPU (Motion CPU) to the device of self CPU
For example, by using the D(P).SFCS instruction of Motion dedicated PLC instruction, the Motion SFC of the Motion CPU can be started from the PLC CPU.


MEMO

3. COMMON PARAMETERS
3.1 System Settings
In the Multiple CPU system, the common system parameters and individual parameters are set for each CPU and written to each CPU. (1) The base settings, Multiple CPU settings and Motion slot settings are set in the
common system parameter setting.
(2) The system basic setting, self CPU installation position setting, servo
amplifier setting, high-speed read setting and optional data monitor setting are set in the individual parameter setting.
(3) The data setting and correction can be performed in dialog form using MT
Developer.

3.1.1 System data settings
The table below lists the system data items to be set.
Item Setting range Initial value Remark
Main base 8/12 slots Main base: 8 slots Base setting
Set the number of slots in the main base or extension base.
Extension base None/2/3/5/8/10/12 slots None
No. of CPU 2/3/4 modules 2 modules Set the total number of Multiple CPUs including PLC CPU(s).
Stop/do not stop all CPUs upon an error in CPU No. 1 to 4. (The setting range varies depending on the number of Multiple CPUs.)
Set whether or not to stop the entire system when a CPU stop error occurs in each CPU.
Error operation mode at the stop of CPU
Stop all CPUs upon error in CPU Nos. 1 to 4
CPU specific send range
0 to 14k points Varies depending on the number of CPUs.
Multiple CPU high speed transmission area setting Automatic refresh setting
System area 1 to 2k points 1
Refer to Section 2.3.2.
automatic refresh.
Set/do not set CPU No. 1 to 4 as the synchronized startup. (The setting range varies depending on the number of Multiple CPUs.)
Multiple CPU synchronous startup setting
Set CPU No. 1 to 4 as the synchronized startup. Refer to Section 2.3.5.
Install the modules controlled by the self CPU in the main base and/or extension base(s).
Module arrangement Within the main base and extension base slots None
Individual module Varies depending on the module. Varies depending on the module.
Set detailed items for each module controlled by the self CPU.
Operation cycle 0.4ms/0.8ms/1.7ms/3.5ms/7.1 ms/ 14.2ms/Auto Auto Set the operation cycle of motion control.
M2000 is turned on by switching from STOP to RUN./M2000 is turned on by switching from STOP to RUN and setting 1 in the set register.
M2000 is turned on by switching from STOP to RUN.
Operation at STOP to RUN
Set the condition in which the PLC ready flag (M2000) turns on.
Set the bit device to use forced stop in the program. However, the forced stop input by EMI terminal of Motion CPU module cannot be invalidated using parameter setting.
Forced stop (Note-1) None/X(PX) (0 to 1FFF)/ M (0 to 8191) None
M (0 to 8191)/B (0 to 1FFF)/ F (0 to 2047)/D (0 to 8191)/ W (0 to 1FFF)
None Set the latch range of device memory.
Set self CPU/other CPU/CPU (empty) for slots 0/1/2. (The setting range varies depending on the number of Multiple CPUs installed.)
None Set the installation position of the self CPU in the main base.
Self CPU installation position setting

Item Setting range Initial value Remark
None Set the model name, axis No. and other details for the servo amplifiers.
Amplifier input invalid Amplifier setting
External signal input setting Amplifier input invalid/Amplifier input valid
Input filter setting None/0.8ms/1.7ms/2.6ms/3.5ms 3.5ms
High-speed data read setting One Q172DEX/Q173DPX module and one input module. None Set the high-speed read data. Refer to Section 4.3.
Set 1 to 3 for each axis. Q173DCPU: Up to 32 axes Q172DCPU: Up to 8 axes
None Set the optional data monitor. Refer to Section 4.10.
Optional data monitor setting
(Note-1) : The forced stop can also be executed by the EMI forced stop terminal of Motion CPU module or forced stop terminal of
servo amplifier besides the forced stop input setting.
Individual parameters

3.1.2 Common system parameters
(1) Parameters for operating the Multiple CPU system
In the Multiple CPU system, the common system parameters and individual parameter for each CPU are set and written into each CPU. Regarding the Motion CPU, the items in System Settings related to the entire Multiple CPU system must be identical to the parameter settings in the PLC CPU.
Q173D CPU QnUD(H) CPU

(2) Parameters common throughout the Multiple CPU system
In the Motion CPU, during initialization the parameters in the table below are verified against the parameters in the PLC CPU of CPU No. 1. Unmatched parameters generate a PARAMETER ERROR (error code: 3012, 3015), so the parameters show below must be set identically between Motion CPUs and the PLC CPU of CPU No.1. (If the system settings are changed in a Motion CPU, it is necessary to reset. Therefore, the parameters are checked only during initialization.) The parameter No. of unmatched parameter is set in the error individual information (SD16) by this error occurrence. PLC CPUs can use the parameters of the other CPUs via "Multiple CPU parameter utilization" of GX Developer. Since Motion CPUs don't have this function, however, the common parameters must be set for each Motion CPU. Table of Parameters cross-Multiple CPU system
Name in Motion CPU Name in PLC CPU
No. of CPU No. of PLC Number of CPUs 0E00H
Operating mode Operating mode Operation mode for CPU stop error 0E01H
CPU specific send range
CPU specific send range
Points of CPU specific send range E008H Refer to Section 2.3.2.
Refer to Section 2.3.2. This parameter can be set when "Advanced setting" is selected.
Multiple CPU high speed transmission area setting
Multiple CPU high speed transmission area setting
System area System area System area size E008H
Refer to Section 2.3.2. (Automatic refresh using Multiple CPU high speed transmission area)
Points of automatic refresh E009H
Multiple CPU synchronous startup setting
Multiple CPU synchronous startup setting
Synchronize Multiple CPU startup or not E00BH Refer to Section 2.3.5.
Motion slot setting Detailed settings Control PLC Control CPU No. 0406H Verify module only set in the system settings in the Motion CPU side.
Total number of bases
0401H Not verified if base settings are omitted in the PLC CPU side.
Base No. Base setting
Base Number of base

(a) Multiple CPU settings

Number of CPU modules
Error operation mode at the stop of CPU
Multiple CPU high speed transmission area setting

Multiple CPU synchronous startup setting

Select tab "Multiple CPU high speed communication area setting"
Set "Use multiple CPU high speed communication".

(b) Motion slot settings
Set the modules controlled by the self CPU by the Motion Slot Settings (Motion CPU) in MT Developer. In GX Developer, set the slot for Motion CPU control as the CPU number of Motion CPU in I/O Assignment Settings (PLC CPU).

Control CPU No.

(Note): Motion slot setting items are different depending on the operating system software.

Set the total number of bases and number of slots in each base identically between Base Settings (Motion CPU) in MT Developer and I/O Assignment Settings (PLC CPU) in GX Developer. In GX Developer, the detailed settings may be omitted by setting the base mode "Automatic".

Total number of bases and number of slots in each base

(Note) : Only the Motion CPU may be set without setting the PLC CPU.
(c) Base settings

POINT GOT is recognized as an intelligent function modules "16 points 10 slots" on the base (number of extension bases and slot No. are set in the GOT parameter.) for bus connection with GOT. Set the one extension base (16 points 10 slots) for connection with GOT, then set "10 slots" as number of extension bases for connection with GOT in the system setting (base setting).
When the "2nd stage" of extension base is set as connection with GOT. (Set "10" slot as "2nd stage" of extension base in the base setting.)


3.1.3 Individual parameters
(1) System basic setting
The following explains each item to be set in system basic setting.

Operating system Number of axes Operation cycle setting
1 to 6 axes 0.4 ms
7 to 18 axes 0.8 ms SV13
19 to 32 axes 1.7 ms
1 to 4 axes 0.4 ms
5 to 12 axes 0.8 ms
13 to 28 axes 1.7 ms SV22
29 to 32 axes 3.5 ms
(a) Operation cycle

3) If the duration of motion operation has exceeded the operation cycle, the operation cycle over flag (M2054) turns ON. Even when "Automatic setting" is selected, the duration of motion operation may exceed the operation cycle depending on the control conditions. The actual duration of motion operation (unit:μs) is stored in SD522, and the current setting of operation cycle (unit:μs) is stored in SD523. Monitor these special registers and adjust the set value of operation cycle so that the actual duration of motion operation will not exceed the set operation cycle. (A WDT or other error may occur in the Motion CPU.)
(b) Operation at STOP to RUN
Set the condition in which the "PLC ready" flag (M2000) turns ON. Select any one of the followings. 1) M2000 is turned on by switching from STOP to RUN. Condition in which the M2000 turns from OFF to ON
Condition in which the M2000 turns from ON to OFF
(M2000 turns ON when the switch is set to RUN and 1 is set in the setting register.)
Condition in which the M2000 turns from OFF to ON
Condition in which the M2000 turns from ON to OFF
(c) Forced stop

The setting items for each module are shown below.

Number of usable modules Module name Item Setting range Initial value
External signal setting Set the number of axes for which the 8 axes input is used. Unused
DOG Valid on leading edge/ Valid on trailing edge
QI60 Interrupt module Input response time 0.1/0.2/0.4/0.6/1 ms 0.2 ms 1 1
(d) Latch range

Setting items for each module (Continued)
Number of usable modules Module name Item Setting range Initial value
First I/O No. 00 to FF0 (in units of 16 points) 0
High-speed data read setting Used/Unused Unused QX Input module
I/O response time (setting for high-speed input module in parentheses)
1/5/10/20/70 ms (0.1/0.2/0.4/0.6/1 ms)
10 ms (0.2 ms)
First I/O No. 00 to FF0 (in units of 16 points) 0 QY Output module
First I/O No. 00 to FF0 (in units of 16 points) 0
Input/Output composite module High-speed data read setting Used/Unused Unused
I/O response time 1/5/10/20/70 ms 10 ms QH / QX Y
First I/O No. 00 to FF0 (in units of 16 points) 0
Input range 4 to 20mA/0 to 20mA/1 to 5V/0 to 5V/-10 to 10V/0 to 10V/User range 4 to 20mA
Total 256 points or less
Total 256 points or less
Temperature drift compensation Used/None Used
Resolution mode Normal/High Normal
Operation mode Normal (A/D conversion)/Offset gain setting
(A/D conversion) First I/O No. 00 to FF0 (in units of 16 points) 0
Output range 4 to 20mA/0 to 20mA/1 to 5V/0 to 5V/-10 to 10V/User range 4 to 20mA
HOLD/CLEAR function CLEAR only CLEAR
Output mode Normal (Asynchronous)/ Synchronous output
(Asyn- chronous) Resolution mode Normal/High Normal
Operation mode Normal (D/A conversion)/ Offset gain setting

(3) External signal input
Servo external signal (Upper stroke limit/Lower stroke limit/Stop signal/Proximity dog) can be selected for every axis from the following two methods.
(a) Q172DLX Servo external signals interface module use
Set the servo external signals interface module, and set axis No. as the "External signal setting" in the system setting.
(b) Servo amplifier input device use (MR-J3-B use only)
The correspondence of external signal and input device is shown below.
External signals Input device (CN3) (Note)
Upper stroke limit (FLS) DI1
Lower stroke limit (RLS) DI2
Proximity dog (DOG) DI3
(Note): Refer to the "MR-J3-B Servo Amplifier Instruction Manual" for pin configurations.
Set the external signal setting in the "Input Filter Setting".

3.2 I/O number assignment
In the Multiple CPU system, I/O numbers are used for interactive transmission between the Motion CPU and I/O modules and intelligent function modules, or between PLC CPU and Motion CPU. 3.2.1 I/O number assignment of each module
The Multiple CPU system is different from the Single CPU system in the position (slot) of I/O number "0H" for PLC CPU. However, I/O number of control module can be assigned independently for each CPU for Motion CPU.
(a) The number of slots set with the Multiple CPU settings are occupied by the
PLC CPU/Motion CPU on the Multiple CPU system.
(b) I/O modules and intelligent function modules are installed from the right of the
slots occupied by PLC CPU/Motion CPU.
(c) I/O number of Motion CPU control module can be assigned independently for
each CPU. The I/O number of PLC CPU control module for an I/O module or intelligent function module mounted to the next slot to those occupied by CPU modules is set as "0H" and consecutive numbers are then allocated sequentially to the right.
(d) Notation of I/O number

(2) I/O number assignment of Motion CPU control module
Mitsubishi recommends that I/O No. assignment be set as common consecutive No. throughout all CPUs. However, the I/O number of the input modules, output modules and input/output composite modules controlled with the Motion CPU can also be set regardless as the I/O number of PLC CPU. (I/O number of the Motion CPU control modules is indicated as PX/PY.) I/O number of the Motion CPU control modules cannot be assigned by I/O assignment settings of PLC CPU.

CPU No. 1 CPU No. 2 CPU No. 2
CPU No. 2
CPU No. 1
CPU No. 1
Follow the table below when Motion CPU control modules are set in I/O Assignment Settings of the PLC CPU. (The PLC CPU handles the Q172DLX, Q172DEX and Q173DPX as intelligent function modules having 32 occupied points.) Type and number of points may be left unset.


POINT (1) Set the I/O device of the Motion CPU within the range from PX/PY000 to
PX/PYFFF. Set the number of real I/O points within 256 points. (I/O No. may not be consecutive.) (2) As for the Motion CPU, the Q172DLX, Q172DEX, Q173DPX and QI60 are not

3.2.2 I/O number of each CPU modules
In the Multiple CPU system, I/O numbers are assigned to each CPU module to specify installed CPU modules. The I/O number for each CPU module is fixed to the corresponding slot and cannot be changed. The I/O number allocated to each CPU module in the Multiple CPU system is shown below.
CPU module installation position CPU slot Slot 0 Slot 1 Slot 2
First I/O number 3E00H 3E10H 3E20H 3E30H

3.2.3 I/O number setting
Set the I/O No. of modules controlled with the Motion CPU module set in the system structure screen of MT Developer. The setting procedure of I/O No. is shown below.
(Example) For set the output module



(Note): Display of system setting and motion slot setting are different depending on the operating system
software.
POINT I/O No.s cannot be assigned automatically, unlike a PLC CPU for which I/O No. are assigned automatically if such setting is omitted in the Motion CPU. In the Motion CPU, be sure to set the first I/O No. in System Settings for each module used.
· ·

3.3 Servo Parameters
The servo parameters control the data fixed by the specifications of the servo amplifier and servomotor controlled in the parameter set for each axis and the control of the servomotor. The servo parameters are set by the Setup software (MR Configurator). Refer to the "Servo amplifier Instruction Manual" for details of the servo parameters. Refer to the help for handling of MR Configurator. Instruction Manual list is shown below.

MR-J3- B-RJ006 Fully closed loop control MR-J3- B-RJ006 Servo Amplifier Instruction Manual (SH-030056)

POINTS (1) When the items marked " " in the above table has changed, make the Multiple CPU system reset or power supply OFF to ON. And, once turn OFF the servo amplifier power supply and then turn ON it again.


(2) Gain/filter parameters
No. Symbol Name Initial value Unit
PB01 FILT Adaptive tuning mode (Adaptive filter ) 0000h —
PB02 VRFT Vibration suppression control tuning mode (Advanced vibration suppression control) 0000h —
PB03 — For manufacturer setting 0 —
PB04 FFC Feed forward gain 0 %
PB05 — For manufacturer setting 500 —
PB06 GD2 Ratio of load inertia moment to servomotor inertia moment 7.0 times
PB07 PG1 Model loop gain 24 rad/s
PB08 PG2 Position loop gain 37 rad/s
PB09 VG2 Speed loop gain 823 rad/s
PB10 VIC Speed integral compensation 33.7 ms
PB11 VDC Speed differential compensation 980 —
PB12 — For manufacturer setting 0 —
PB13 NH1 Machine resonance suppression filter 1 4500 Hz
PB14 NHQ1 Notch shape selection 1 0000h —
PB15 NH2 Machine resonance suppression filter 2 4500 Hz
PB16 NHQ2 Notch shape selection 2 0000h —
PB17 — Automatic setting parameter — —
PB18 LPF Low pass filter setting 3141 rad/s
PB19 VRF1 Vibration suppression control - vibration frequency setting 100.0 Hz
PB20 VRF2 Vibration suppression control - resonance frequency setting 100.0 Hz
— For manufacturer setting
PB23 VFBF Low pass filter selection 0000h —
PB24 MVS Slight vibration suppression control selection 0000h —
PB25 — For manufacturer setting 0000h —
PB26 CDP Gain changing selection 0000h —
PB27 CDL Gain changing condition 10 —
PB28 CDT Gain changing time constant 1 ms
PB29 GD2B Gain changing - ratio of load inertia moment to servo motor inertia moment 7.0 times
PB30 PG2B Gain changing - position loop gain 37 rad/s
PB31 VG2B Gain changing - speed loop gain 823 rad/s
PB32 VICB Gain changing - speed integral compensation 33.7 ms
PB33 VRF1B Gain changing - vibration suppression control - vibration frequency setting 100.0 Hz
PB34 VRF2B Gain changing - vibration suppression control - resonance frequency setting 100.0 Hz
PB36 0.00
PB37 100
PB38 0.0
PB39 0.0
PB40 0.0
— For manufacturer setting
PB42 1125
PB44 0.0
PB45
POINTS (1) When the items marked " " in the above table has changed, make the Multiple CPU system reset or power supply OFF to ON. And, once turn OFF the servo amplifier power supply and then turn ON it again.
PB43 0004h · 0000h

(3) Extension setting parameters

PC13 MOSDL Analog monitor feedback position output standard data Low 0 PLS
PC14 MOSDH Analog monitor feedback position output standard data High 0 10000PLS
POINTS (1) When the items marked " " in the above table has changed, make the Multiple CPU system reset or power supply OFF to ON. And, once turn OFF the servo amplifier power supply and then turn ON it again.


(4) I/O Setting Parameters

PD07 DO1 Output signal device selection 1 (CN3-13) 0005h —
PD08 DO2 Output signal device selection 2 (CN3-9) 0004h —
PD09 DO3 Output signal device selection 3 (CN3-15) 0003h —
POINTS (1) When the items marked " " in the above table has changed, make the Multiple CPU system reset or power supply OFF to ON. And, once turn OFF the servo amplifier power supply and then turn ON it again.


4. AUXILIARY AND APPLIED FUNCTIONS
4.1 Limit Switch Output Function
This function is used to output the ON/OFF signal corresponding to the data range of the watch data set per output device. Motion control data or optional word data can be used as watch data. (Refer to Section "4.1.2 Limit output setting data" for details.) A maximum output device for 32 points can be set regardless of the number of axes. 4.1.1 Operations
(1) ON output to an output device is made while the watch data value is in the ON
output region set with (ON Value) and (OFF Value) in this function. (a) (ON Value), (OFF Value) and watch data value are handled as signed data.
ON output region where an ON output is made to the output device is governed by the magnitude relationship between (ON Value) and (OFF Value) as indicated below.
Relationship between (ON Value) and
(OFF Value) ON output region
(ON Value) < (OFF Value) (ON Value)
(ON Value) > (OFF Value) (ON Value)
(Watch data value) < (OFF Value)
(ON Value) = (OFF Value) Output OFF in whole region
OFF
OFF
(ON Value) (Watch data value) (OFF Value)
ON
OFF
(Watch data value) (OFF Value) (ON Value) (Watch data value)

OFF in whole region
ON Value OFF Value
(b) The limit switch outputs are controlled based on the each watch data during
the PCPU ready status (SM500: ON) by the PLC ready flag (M2000) from OFF to ON. When the PCPU ready flag (SM500) turns OFF by turning the PLC ready flag (M2000) from ON to OFF, all points turn OFF. When (ON Value) and (OFF Value) are specified with word devices, the word device contents are input to the internal area when the PLC ready flag (M2000) turns from OFF to ON. After that, the word device contents are input per motion operation cycle, and limit switch outputs are controlled.
(c) Multiple outputs (Up to 32 points) can be also set to one watch data. In each
setting, the output device may be the same. If multiple ON region settings have been made to the same output device, the logical add of the output results in the regions is output.
ON
OFF
OFF
ON region setting No.2
ON region setting No.1
(2) Output enable/disable bit can be set and executed enable/disable of the limit
switch outputs point-by-point. Limit switch output control is executed when the output enable/disable bit is ON, and the output is OFF when it is OFF. If there is no setting, the outputs are always enabled.
(3) Forced output bit can be set and turned the forcibly output of the limit switch
outputs point-by-point ON. The output is ON when the forced output bit is ON. Priority is given to control of this setting over off (disable) of the "output enable/disable bit". If there is no setting, no forced outputs are not always made.

(4) When the multiple watch data, ON region, output enable/disable bit and forced
output bit are set to the same output device, the logical add of output results of the settings is output.

Output ON (Forced output) Output control based on ON Value and OFF Value
Output control based on ON Value and OFF Value Output OFF

4.1.2 Limit output setting data
Limit output data list are shown below. Up to 32 points of output devices can be set. (The following items of No.1 to No.5 are set together as one point.)

1 Output device Bit device (X, Y, M, B, U \G) — Operation
ON Value Word device (D, W, #, U \G)/constant (K, H) 3 ON region
setting OFF Value Word device (D, W, #, U \G)/constant (K, H)
Bit device (X, Y, M, B, F, SM, U \G)/ none
5 Forced output bit Bit device (X, Y, M, B, F, SM, U \G)/ none
(a) Set the bit device which outputs the ON/OFF signal toward the preset watch
data.
(b) As the output device, the following devices can be used.

Input relay (Note-1) X0 to X1FFF Output relay (Note-2) Y0 to Y1FFF Internal relay (Note-3) M0 to M8191
Multiple CPU area device U \G10000.0 to U \G (10000+p-1).F (Note-4), (Note-5)
(Note-1) : PX is write-disabled and it cannot be used as the output device.
For X, only the free No. of the input card non-loading can be used.
(Note-2) : The real output device range (PY) is also included.
(Note-3) : M2001 to M2032 cannot be used to the output device.
Be careful because it affect a positioning operation, when the positioning
dedicated devices are set.
transmission area for the each CPU.
(Note-5) : Only device of the self CPU can be used.

(2) Watch data
(a) This data is used to perform the limit switch output function. This data is
comparison data to output the ON/OFF signal. The output device is ON/OFF-controlled according to the ON region setting.
(b) As the watch data, motion control data or optional word device data can be
used.


Multiple CPU area device U \G10000 to U \G (10000+p-1) (Note-1)
transmission area for the each CPU.

64-bit floating-point type Set the device No. as an even No..

(3) ON region setting
(a) The data range which makes the output device turn ON/OFF toward the
watch data.
(b) The following devices can be used as the ON Value and OFF Value of the
data range. The data type of device/constant to be set is the same as the type of watch data.

Multiple CPU area device U \G10000 to U \G (10000+p-1) (Note-1)
transmission area for the each CPU.
(a) Set the status of output enable/disable bit when the limit switch output is
forbidden during operation.

Limit switch output is turned ON/OFF based on the ON

Multiple CPU area device U \G10000.0 to U \G (10000+p-1).F (Note-3)
(Note-1) : The real input range(PX) is included.
(Note-2) : The real input range(PY) is included.
transmission area for the each CPU.
(b) Usable devices

(5) Forced output bit
(a) Set the "forced output bit" when you want to forcibly provide the limit switch
outputs during operation.
Output enable/disable bit Control description
Limit switch outputs are turned ON/OFF on the basis of
the "output enable/disable bit" and ON region setting
(ON Value, OFF Value). With setting
ON Limit switch outputs are turned ON.
Item Device No. setting range
Input relay X0 to X1FFF
Output relay Y0 to Y1FFF
Internal relay M0 to M8191
Link relay B0 to B1FFF
Annunciator F0 to F2047
Special relay SM0 to SM1999
Multiple CPU area device U \G10000.0 to U \G (10000+p-1).F (Note-1)
transmission area for the each CPU.
POINT Refer to Chapter 2 for the user setting area points of the Multiple CPU high speed
transmission area.
Without setting · (b) Usable devices

4.2 Absolute Position System
The positioning control for absolute position system can be performed using the absolute-position-compatible servomotors and servo amplifiers. If the machine position is set at the system starting, home position return is not necessary because the absolute position is detected at the power on. The machine position is set with the home position return using the Motion SFC program or MT Developer. (1) Conditions of the absolute position system start
Perform a home position return after machine adjustment at the absolute position system start.
(2) In the absolute positioning system, the absolute position may be lost in the
following cases: Set the absolute position with a home position return. (a) The battery unit is removed or replaced.
(b) The battery error of the servo amplifier occurs. (It is detected at the servo
amplifier power on).
(c) The machine system is disturbed by a shock.
(d) The cable between servo amplifier and encoder is removed, or the servo
amplifier or encoder is replaced.
(3) The current value history can be monitored using of the "System setting mode-
allowable travel during power off" or "Monitor mode" using a MT Developer. (Refer to the help of MT Developer to be used "Allowable travel during power off" and "Monitor mode".)
After removing or replacing the battery unit, correctly install the new unit and set the absolute
position.
After a servo battery error occurs, eliminate the cause of the error and ensure operation is safe
before setting the absolute position.
After the mechanical system is disturbed by a shock, make the necessary checks and repairs,
and ensure operation is safe before setting the absolute position.

POINT (1) The address setting range of absolute position system is 2147483648 to
2147483647. It is not possible to restore position commands that exceed this limit, or current values after a power interruption. Correspond by the [degree] setting for an infinite feed operation. (2) Even when the current value address is changed by a current value change
instruction, the restored data for the current value after a power interruption is the value based on the status prior to execution of the current value change instruction. (3) When home position return has not been completed (home position return
request is ON), restoration of the current value after a power interruption is not possible.

4.2.1 Current value control
The current value when using the ABS encoder is controlled by following functions. (1) The validity of an encoder data during operation is checked.
(a) Checks that the amount of change of the encoder in a 3.5[ms] is within 180
degrees at the motor axis. (An error is displayed at the abnormal.)
(b) Checks that adjustment of the encoder data and feed-back positions
controlled with the servo amplifier. (An error is displayed at the abnormal.)
(2) The following values can be monitored by the current value history monitor of
MT Developer.
Monitor conditions Monitor value
Multiple CPU system power ON/OFF
Encoder current value, Servo command value, Monitor current value
Home position return completion
(a) Current value history monitor
The time such as at the completion of home position return and servo amplifier power supply ON/OFF is indicated. In order to indicate the time correctly, turn on SM801 (clock data read request) in the Motion SFC program after setting the clock data of special register.
(b) Encoder current value
When using the MR-J3- B, the multiple revolution data and within-one- revolution data read from the encoder is indicated. (Note) : For the encoder current value in the home position data area, the
encoder current value when the motor is within the in-position range at the completion of home position return is displayed (not encoder value of home position).
(c) Servo command value
The command value issued to the servo amplifier is indicated.
(d) Monitor current value
The current value controlled in the Motion CPU is indicated. (Note) : A value near the feed current value is indicated. However, because
the monitor current value and feed current value are different data, it is not abnormal even if a different value is indicated.
When an error for current value restoration occurs at the servo amplifier power on, an error code is indicated.
(3) By setting of the "Allowable travel during power off", if the encoder data changes
exceeding the setting range during power-off, it checks at servo amplifier power- on. (An error is displayed at the abnormal.) "Allowable travel during power off" cannot be set for the Linear servo amplifier.
Month/day/hour/minute · (e) Alarms

4.3 High-Speed Reading of Specified Data
This function is used to store the specified positioning data in the specified device (D, W, U \G). The signal from input module controlled in the Motion CPU is used as a trigger. It can be set in the system setting of MT Developer. (1) Positioning data that can be set

Position command (Feed current value) 2 10-1[µm], 10-5[inch], 10-5[degree], [PLS]
Actual current value 2 10-1[µm], 10-5[inch], 10-5[degree], [PLS]
Virtual servo M-code 1 Current value after main shaft differential gear 2 [PLS]
Current value within one revolution of cam axis 2 [PLS]
Execute cam No. 1 Execute stroke amount 2 10-1[µm], 10-5[inch] [PLS]

Input module Signal Read timing Number of settable points
(Note) : Only one PLC input module can be used.

U \G 10000 to (10000 + p-1) (Note-1), (Note-2)
transmission area for the each CPU. (Note-2): Only device of the self CPU can be used.

POINT (1) Set an even number as device setting in the two word data. (2) Refer to Chapter 2 for the user setting area points of the Multiple CPU high

4.4 ROM Operation Function
This function is used to operate based on the data in the FLASH ROM built-in Motion CPU module that the user programs and parameters have been stored. 4.4.1 Specifications of 7-segment LED/Switches


"Operation mode" of the Motion CPU is set by the rotary switch setting of Motion CPU module at the power supply ON of the Multiple CPU system. The rotary switch setting, operation mode and operation mode overview are shown below.
(a) Rotary switch setting and operation mode

(Note-1) : Do not set except the above setting. (Note-2) : The programs, parameters, absolute position data, and latch data in the
SRAM built-in Motion CPU module are cleared.
1)

(b) Operation mode overview
Operation mode 7-segment LED Operation overview
built-in Motion CPU module.
the FLASH ROM built-in Motion CPU module.
digit of 7-segment LED.
ROM built-in Motion CPU module are read to the SRAM built-in Motion CPU
module at power supply on or reset of the Multiple CPU system.
If the ROM writing is not executed, even if the user programs and parameters
are changed using the MT Developer during mode operated by ROM,
operation starts with the contents of the FLASH ROM at next power supply on
or reset.
Also, If the ROM writing is not executed, even if the auto tuning data are
reflected on the servo parameter of Motion CPU by operation in the auto-tuning
setting, operation starts with the contents of the FLASH ROM at next power
supply on or reset.
POINT Do not change the rotary switch setting during operation. Be sure to turn OFF the power supply before the rotary switch setting change.

4.4.2 Outline of ROM operation
When the ROM writing is requested to the Motion CPU module using the MT Developer, the programs and parameters stored in the SRAM built-in Motion CPU module are batch-written to the FLASH ROM, after the data of FLASH ROM built-in Motion CPU are erased. When the Motion CPU starts in the "Mode operated by ROM", a normal operation starts, after the data written in the FLASH ROM is read to the SRAM.
The data batch written to the FLASH ROM built-in Motion CPU module by ROM writing are shown below. Backup data except the followings (current position of servomotor in absolute position system, home position and latch device.) cannot be written to the FLASH ROM.
Each parameter for servo control
— Mechanical system program
POINT (1) "Backup • load" operation of the MT Developer targets the SRAM built-in
Motion CPU module. (The FLASH ROM built-in Motion CPU module is not targeted.) Set to "Mode operated by ROM" after ROM writing to execute the ROM operation after "Backup • load" operation at the Motion CPU module exchange. (2) The FLASH ROM built-in Motion CPU module serves as a life in 100000 times
writing. Make the ROM writing within 100000 times. If it passes over a life, "writing error" will occur, replace the Motion CPU module. (3) The online change of Motion SFC program executes the Motion SFC program
performed the online change from the next scanning at the mode operated by ROM. Operation starts with the contents of the Motion SFC program written in the FLASH ROM built-in Motion CPU module at next power supply on or reset. (4) It needs to meet the following conditions for the ROM writing.
(a) PLC ready flag (M2000) OFF (b) Not installation mode

(1) Write the programs and parameters written in the SRAM built-in Motion CPU
module to the FLASH ROM built-in Motion CPU module for the ROM operation.
Mode operated by RAM/Mode operated by ROM
Be sure to write the programs and parameters beforehand to the SRAM built-in Motion CPU module at the ROM operation.
IBM PC/AT
Programs Parameters, etc.
Programs Parameters, etc.
Mode operated by RAM/Mode operated by ROM
Programs Parameters, etc.
Programs Parameters, etc.

Write the data of SRAM built-in Motion CPU module to the ROM.
The operating procedure for ROM writing using the MT Developer is shown below.


Be sure to write the all data beforehand to SRAM built-in Motion CPU module at the ROM writing.
Operating procedure

(2) Write the programs and parameters of the MT Developer to the SRAM built-in
Motion CPU module, and then write them to the FLASH ROM built-in Motion CPU module for the ROM operation.
Mode operated by RAM/Mode operated by ROM
SRAM
Programs Parameters, etc.
Programs Parameters, etc.
Programs Parameters, etc.
Mode operated by RAM/Mode operated by ROM
Programs Parameters, etc.
Programs Parameters, etc.

Write the data of MT Developer to the ROM.
The operating procedure for ROM writing using the MT Developer is shown below.


(Note): Mechanical system program and cam data (converted data) cannot be displayed when using OS type "SW8DNC-SV13".
Be sure to write the all data beforehand to SRAM built-in Motion CPU module at the ROM writing.
Operating procedure

4.4.3 Operating procedure of the ROM operation function
The outline procedure of ROM operation function is shown below. 1) Turn on or reset the power supply of Multiple CPU system in the "Mode operated by RAM". 2) Create the system setting, programs and parameters using the MT Developer, and execute a trial run and adjustment. 3) Write the system setting, programs and parameters of SRAM built-in Motion CPU module to the FLASH ROM built-in Motion CPU module by the ROM writing request using the MT Developer. 4) By starting the Motion CPU in the "Mode operated by ROM", a normal operation starts after the system setting, programs and parameters written in the FLASH ROM built-in Motion CPU module are read to the SRAM built-in Motion CPU module.
The ROM operation procedure is shown below.
Preparation for ROM operation
Set the "Mode operated by RAM" by setting the rotary switch 1 (SW1) and 2 (SW2) to "0".
Turn ON the power supply of Multiple CPU system.
Create or correct the system setting, parameters and programs using the MT Developer, and write them to the Motion CPU module.
Execute the trial run and adjustment.
Is the operation normal ?
Mode operated by RAM (ROM writing)
Execute the "ROM writing" of the programs and parameters in a lump using the MT Developer.
Turn OFF the power supply of Multiple CPU system.
Set the "Mode operated by ROM" by setting the rotary switch 1 (SW1) to "0" and rotary switch 2 (SW2) to "6".
Turn ON the power supply of Multiple CPU system.
Mode operated by ROM
ROM operation start

(2) Operation at the "Mode operated by ROM"
Mode operated by ROM start
(Data (programs, parameters and absolute position data) is not written to the FLASH ROM built-in Motion CPU module.)
Is the data write to the FLASH ROM built-in
Motion CPU module ?
Read the followings of the FLASH ROM built-in Motion CPU module to the SRAM built-in Motion CPU module. System setting data Parameter for servo control Servo program Motion SFC parameter Motion SFC program Mechanical system program (SV22) Cam data (SV22)
The system setting error (" AL" flashes 3 times steady "L01" display) in the 7- segment LED at the front side of Motion CPU module.
Wait the restart of Multiple CPU system.
After that, it cannot be operated because of stop state. Retry the operation for "ROM writing" "Mode operated by ROM" after confirm the contents for programs and parameters of the SRAM built-in Motion CPU module.
After that, it is same operation at the RAM operation.
POINT (1) Change the operation mode using the rotary switch of Motion CPU module. (2) Confirm the operation mode by the 7-segment LED of Motion CPU module.
Normal operation start

4.5 Security Function
This function is used to protect the user data of Motion CPU by registering a password. The illegal reading or writing of the user data are prevented by setting a password. Registered password can be changed and deleted. [Register/Change Password] or [Delete Password] screen is used to register/ change/delete a password. Select from a menu bar to display these screen.

The user data protected in this function are shown below. "Write Protection" or "Read/Write Protection" can be set every user data.
system software User data Protected contents
Motion SFC program Motion SFC programs (Control code, text) SV13/SV22
Servo program Servo programs and program allocation
Mechanical system program Mechanical system programs SV22
Cam data Cam data
Select menu [Online] [Register Password] [Register/Change] to register/change a password.
(a) Enter initial registration password in password column, and select
registration condition (Write Protection, Read/Write Protection). It leaves in blank for the user data that does not register a password.
(b) Click on [Execute] button to register a password in the Motion CPU.
(c) Select menu [Project] [Save] to save a password after registration in a project. Refer to Section 4.5.4 for password save.
(a) Status of password registered in the Motion CPU are displayed.
Operating

(b) Enter new password in password column, and select registration condition
(Write Protection, Read/Write Protection). It leaves in blank for the user data that does not change a password.
(c) Click on [Execute] button to display [Check Password] screen for old
password confirmation. Click on [Execute] button after old password input. New password will be registered in the Motion CPU by success of old password check. When the new password is the same as old password (change for only registration condition), [Check Password] screen is not displayed.
(d) Select menu [Project] [Save] to save a password after change in a project. Refer to Section 4.5.4 for password save.
POINT (1) If an user has forgotten a registration password, clear a password of Motion
CPU by the all clear function. However, the all password data and user data are cleared by the all clear function. Re-write the user data to the Motion CPU. (Refer to Section 4.6 for details.) (2) ROM operation can be executed by user data registered a password.
The password setting is also included in the ROM writing/reading data. (3) The password data is not save in a project without password save.
Therefore, be sure to save a password. (4) If an operation stops by reset or power OFF of the Multiple CPU system while
a password registration/change, the user data may not be registered. Register/change a password again to restore the user data.

Type Type of user data
Registration " " is displayed when a password is registered in the Motion CPU.
Enter initial registration/change password.
Alphanumeric character (ASCII) of 6 or less
Match case (Not full-size character)
A registration condition set in the Motion CPU is displayed.
New registration condition can be selected by password input.
Items Details · Password · Registration condition

4.5.2 Password delete
Select menu [Online] [Register Password] [Delete] to delete a password.
(a) Status of password registered in the Motion CPU are displayed.
(b) Enter old password and click on [Execute] button to delete password. It
leaves in blank for the user data that does not delete a password.
(c) A password will be deleted by success of password check. (" " displayed in registration column disappears.)
(d) Select menu [Project] [Save] to save a password after delete in a project. Refer to Section 4.5.4 for password save.
POINT (1) The password data is not save in a project without password save.
Therefore, be sure to save a password.
(2) If an operation stops by reset or power OFF of the Multiple CPU system while
delete of password, the data may not be deleted. Delete a password again to restore the user data.

Type Type of user data
Registration " " is displayed when a password is registered in the Motion CPU.
Password Enter old password.
Items Details

4.5.3 Password check
When operating the user data that sets password, the check password screen is displayed automatically.
(a) Enter old password in password column, and click on [Execute] button.
(b) Protection by the password temporarily released by success of password
check. After that it can be operated the user data.
(c) A password is memorized until MT Developer ends. (Since protection by
password is automatically released temporarily at the user data operation, a check password screen is not displayed.)

Type Type of user data
Password Enter old password.
Items Details

4.5.4 Password save
Registered/changed/deleted password or password read with user data from "Read from CPU" screen displayed by menu [Online] [Read from CPU] can be saved in a project data. A password saved in a project data can be registered with user data, when the user data are written in the Motion CPU that does not set password from "Write to CPU" screen displayed by menu [Online] [Write to CPU].
Select menu [Project] [Save] to save the updated password data in a project.
Operation Status of password data
Read When a password is set in the call source Motion CPU, the password contents are called and the password data in a project are updated.
Write When a password data is set in a project, if a password is not set in the write designation Motion CPU, the password contents are also written.
Verification Password data in a project are not updated.
ROM writing Password contents registered in the write designation Motion CPU are written in ROM.
Online change Password contents of write designation Motion CPU are not updated.
Backup It is saved in backup data including also the password contents registered in the call source Motion CPU. The password data in a project is not updated.
Load Password contents in backup data are written in the write designation Motion CPU.
New password contents are written in the write designation Motion CPU. Password data in a project is also updated to new password contents.
Delete password A password is deleted from the write designation Motion CPU. A password is deleted also from the password data in a project.
Project diversion The password data in diverting source project is not diverted.
POINT (1) The password data is not save in a project without project save. (2) Save a project after delete of password to delete the password data in a
project. Or, create a project without password data by creating new project and diverting user data from a project with password data.
Register/change password

4.6 All clear function
This function is used to clear the all user data, password setting, backup area and user data area of FLASH ROM in the Motion CPU module. (1) Procedure for clear all
(a) Set the Motion CPU module to installation mode (Set a rotary switch 1
(SW1) to "A".)
(b) Select [Execute] button of "Clear CPU Memory" screen displayed by menu
[Online] [Clear CPU Memory]".

POINT (1) Set the Motion CPU module to installation mode to clear all.
Be sure to set a rotary switch after power supply OFF. (2) The user data area of FLASH ROM built-in Motion CPU module is also
cleared. (3) All user data and password setting are cleared at the "Clear all".
It is recommended to be backup them in advance using MT Developer.

4.7 Communication via Network
The communication between the personal computer and the Motion CPU is possible via Q series Network module (MELSECNET/10(H), Ethernet, CC-Link and etc.) in the Motion CPU (Q173DCPU/Q172DCPU). Refer to the PLC manuals for the specifications of each network modules of MELSECNET/10(H), Ethernet, CC-Link and Serial communication, the handling method. 4.7.1 Specifications of the communications via network
(1) Communications via network enables using MT Developer in the Motion CPU.
(2) Access range of the communications via network of the Motion CPU is an access
range equivalent to QnUD(H)CPU. (Refer to Section "4.7.2 Access range of the communications via network".)
(3) By setting the routing parameter to the control CPU of the network module and the
CPU which connected the peripheral devices in the network by MELSECNET/10(H) and Ethernet, it is possible to relay to 8 network points and communicate.
(4) Because the Motion CPU cannot become the control CPU of the network module,
there is not setting item of the network module and network parameter. However, when connecting with the CPU on the other network from the peripheral device which connected the Motion CPU, it needs to the setting of the routing parameter.
(5) It can operate by remote control the monitor or program editing of the Motion CPU
via the intranet using the Ethernet module.

Personal Computer · Personal Computer

4.7.2 Access range of the communications via network
(1) Network configuration via the MELSECNET/10(H) or the Ethernet
(a) It can access the other CPU via the network from the programming software
packages (GX Developer, MT Developer, etc.) of the personal computer connected with the CPU or serial communication module in USB/RS-232.
(b) It can access the other CPU via the network from the programming software
packages in the personal computer by connecting the personal computer equipped with Ethernet to MELSECNET/10(H) or Ethernet board to the Ethernet to MELSECNET/10(H) or Ethernet.
(c) The access range of above (1) and (2) can be accessed to 8 network points
by setting the routing parameter to the control CPU of the network module and the CPU which connected the personal computer.

Network No.2
Network No.6
Network No.10
: Communication is possible : Communication is possible (Setting of the routing parameter is necessary.) : Communication is impossible

(2) Network configuration via the CC-Link
(a) It can access the other CPU via the CC-link from the programming software
packages (GX Developer, MT Developer, etc.) of the personal computer connected with the CPU or serial communication module in USB/RS-232.
(b) It can access the other CPU via the CC-Link from the programming software
packages in the personal computer by connecting the personal computer equipped with CC-Link board to the CC-Link.
(c) The access range of above (1) is only the CPU on the CC-Link which a
system connects it to, and it can select a CC-Link network to connect by specifying the I/O No. of the CC-Link module.
(d) The access range of above (2) is only the CPU of the connected the CC-
Link.

Network No.2

Network No.2

(3) Network configuration via the RS-422/485
(a) It can access the other CPU via the RS-422/485 from the programming
software packages (GX Developer, MT Developer, etc.) of the personal computer connected with the CPU or serial communication module in USB/RS-232.
(b) The access range of above (1) is only the CPU on the RS-422/485 which a
system connects it to, and it can select RS-422/485 network to connect by specifying the I/O No. of the C24 module.

<Example 2>

Q173D CPU QnUD(H) CPU Q173D CPU QnUD(H) CPU Q173D CPU QnUD(H) CPU

(4) Network configuration which MELSECNET/10(H), Ethernet, CC-
Link, RS-422/485 were mixed (a) When the MELSECNET/10(H) or Ethernet is defined as "Network" and CC-
Link or RS-422/485 is defined as "Link", combination of whether to be able to access from the programming software packages (GX Developer, MT Developer, etc.) is shown below.

Programming software package CPU (C24) Network Link CPU Programming software package CPU (C24) Link Network CPU Programming software package Network Link CPU Programming software package Link Network CPU Programming software package CPU (C24) Network Link Network CPU Programming software package CPU (C24) Link Network Link CPU Programming software package Network Link Network CPU Programming software package Link Network Link CPU
: Usable : Unusable
(b) It can be accessed to 8 network points by setting the routing parameter in
the "Network".
(c) Because routing cannot access, it can access only the connected network.
The connected network can be selected by specifying the I/O No. of the module.

: Communication is possible : Communication is possible (Setting of the routing parameter is necessary.) : Communication is impossible


Network No.1

Network No.1
: Communication is possible : Communication is possible (Setting of the routing parameter is necessary.) : Communication is impossible

4.8 Monitor Function of the Main Cycle
(1) Information for main cycle of the Motion CPU (process cycle executed at free time
except for motion control) is stored to the special register.
(2) Since the automatic refresh of CPU shared memory and normal task of Motion
SFC program are executed in the main cycle, make it reference for process time, etc. to program.
(3) There are following methods to shorten a main cycle.
(a) Lengthen an operation cycle setting. (b) Reduce the number of event task programs to execute in the Motion SFC
program. (c) Reduce the number of normal task programs to execute simultaneously in
the Motion SFC program. (d) Reduce the number of automatic refresh points of CPU shared memory.
(4) When a main cycle is lengthened (more than 1.0[s]), a WDT error may occur in
the Motion CPU.
(5) Details of main cycle monitor register is shown below.
No. Name Meaning Details
SD520 Scan time Current scan time (1ms units)
SD521 Maximum scan time Maximum scan time (1ms units)

4.9 Servo Parameter Reading Function
(1) When the servo parameters are changed, the Motion CPU will be automatically
read the servo parameters and reflected them to the servo parameter storage area in the Motion CPU. Therefore, an operation to read servo parameters is unnecessary in the following cases.
(a) The parameters are changed by auto tuning. (b) The parameters are changed by connecting directly MR Configurator to the
servo amplifier.
POINT If the power supply of Multiple CPU system is turned off/reset or the power supply of servo amplifier is turned off immediately after change, it may not be reflected.
(2) After executing the servo parameter reading function, when it needs to reflect the
servo parameters changed to the MT Developer, read the servo parameters from the Motion CPU and save data.

4.10 Optional Data Monitor Function
This function is used to store the data (refer to following table) up to three points per axis to the specified devices (D, W, #, U \G) and monitor them. It can be set by the system setting of MT Developer. (1) Data that can be set


(Note-1): "p" indicates the user setting area points of the Multiple CPU high speed transmission area
for the each CPU. (Note-2): Only device of the self CPU can be used.

POINT (1) The updating cycle of data is every operation cycle. (2) Set an even number as device setting in the two word data. (3) Refer to Chapter 2 for the user setting area points of the Multiple CPU high

4.11 Connect/Disconnect Function
This function is used to temporarily suspend SSCNET communication while servo amplifiers and/or SSCNET cables after Axis 1 are exchanged with the power supply ON in a Multiple CPU system. SD803 is required for connect/disconnect and SD508 stores the command status for "accept waiting" or "execute waiting" during this process. If a servo amplifier was previously removed using the connect/disconnect function, it must be used again to reconnect the servo amplifier. This function is only required when there is a desire to maintain communication to all axes in front of the one being removed. No connect/disconnect processing is required if the power supply to Axis 1 is shutdown.

Connect command or disconnect command is in the status that can be accepted
SD508 is waiting for connect/disconnect execute command after accepting a connect command or disconnect command.

0 None This value is set if there is no command.
1 to 32 Disconnect command Set axis No. "1 to 32" to be disconnected.
-10 Connect command Set to connect axis while disconnecting.
Connect/disconnect processing is executed by setting this value in the status of a connect/disconnect execute waiting.

POINT (1) After completion of SSCNET communication disconnect processing, be sure to
check the LED display of the servo amplifier for "AA" before turning OFF its the power supply. (2) When a "1 to 32 : Disconnect command" and/or "-10 : Connect command"
are set to the "Connect/disconnect command device (SD803)", the status of the SD508 changes to the "-1: Connect/disconnect waiting" state. In order to complete connect/disconnect processing, "-2 : Connect/disconnect execute command" must be set to SD803 to execute the prior connect/disconnect command. (3) When "1 to 32 : Disconnect command" is set to axis not disconnect, the
connect/disconnect status device (SD508) returns "0" without entering the status of "-1 : Connect/disconnect execute waiting". (4) Operation failure may occur in some axes if the power supply of servo
amplifiers connected after them on the SSCNET system is turned OFF. Be sure to use the disconnect function before turning OFF the power supply of any servo amplifiers connected after an amplifier whose power remains on.
(3) Procedure for connect/disconnect function to exchange the servo amplifier or
SSCNET cable is shown below.
(a) Operation procedure to disconnect

(b) Operation procedure to connect
(4) Flow for device value at connect/disconnect operation is shown below.
Disconnect command (Axis No. of servo amplifier to disconnect)



(1) Self CPU program which connects/disconnects servo amplifiers from Axis 5 on
checking its LED display for "AA". Connect procedure: Resume operation of servo amplifier after verifying
that the servo ready (M2415+20n) is ON.

Set "5" (Disconnect from Axis 5 on) as disconnect command in SD803.

(2) PLC CPU program which connects/disconnects servo amplifiers from Axis 5 on
which is connected to the Motion CPU (CPU No.2).
supply of servo amplifier after checking the LED display "AA" of servo amplifier. Connect procedure: Turn X1 OFF to ON, and then resume operation of
servo amplifier after checking the servo ready (M2415+20n) of servo amplifier.
QY40 QY40 Q172D LX
QY40
Disconnection (From Axis 5 on)
AMP
AMP
AMP
AMP
AMP
M
M
M
M
M
M
0 SM400
K1 D51 MOV
Set "-2" as disconnect execute command in D104.
5 M101 M100 M102 X0
K5 D102 MOV
Set "5" (Disconnect afrom Axis 5 on) as disconnect command in D102.
Set "-10" as connect command in D102.
M100 SET
M10 M100
DP.DDRD H3E1 D100 M10 SD508 D50
Read the data of SD508 for Multiple CPU system (CPU No.2) by turning M100 ON, and store it to data area (D100) of self CPU.
M100 RST
SET
M101
M12 M101
DP.DDWR H3E1 SD803 M12 D102 D50
Write the data of SD803 for Multiple CPU system (CPU No.2) to D102 by turning M101 ON. (Disconnect command/Connect command)
M101 RST
M102 SET
M10 M102
DP.DDRD H3E1 D100 M10 SD508 D50 57
Read the data of SD508 for Multiple CPU system (CPU No.2) by turning M102 ON, and store it to data area (D100) of self CPU.
M102 RST
M103 SET
M12 M103
DP.DDWR H3E1 SD803 M12 D104 D50
Write the data of SD803 for Multiple CPU system (CPU No.2) to D104 by turning M103 ON. (Disconnect execute command)
M103 RST
M104 SET
M10 M104
DP.DDRD H3E1 D100 M10 SD508 D50 96
Read the data of SD508 for Multiple CPU system (CPU No.2) by turning M104 ON, and store it to data area (D100) of self CPU.
M104 RST

4.12 Remote operation
POINT Latch clear can be executed only using the remote control of MT Developer. 4.12.1 Remote RUN/STOP
The PLC ready flag (M2000) is turned ON/OFF by MT Developer with RUN/STOP switch of Motion CPU module set to RUN.
Select [RUN] on "CPU remote operation" screen displayed by menu [Online] – [Remote Operation], and click [Execute] button.
Select [STOP] on "CPU remote operation" screen displayed by menu [Online] – [Remote Operation], and click [Execute] button.

(a) Remote RUN · (b) Remote STOP

POINT (1) Remote RUN cannot be executed if RUN/STOP switch sets to STOP.
Operation after remote operation by RUN/STOP switch is shown below.
Position of RUN/STOP switch RUN STOP
Execute remote RUN RUN STOP
Execute remote STOP STOP STOP
(2) The following parameters are read by turning on the PLC ready flag (M2000).
The PLC ready flag (M2000) can also be turned ON/OFF (PCPU READY complete flag (SM500) ON/OFF) in the following methods.
Remote operation

4.12.2 Remote latch clear
Device data of Motion CPU that latched are cleared by MT Developer at PLC ready flag (M2000) OFF (PCPU READY complete flag (SM500) OFF). Operation for remote latch clear is combined with remote RUN/STOP.
(a) Turn OFF the PLC ready flag (M2000) (PCPU READY complete flag
(SM500) OFF) by remote STOP.
(b) Select [Latch clear (1)] or [Latch clear (1)(2)] on "CPU remote operation"
screen displayed by menu [Online] – [Remote Operation], and click [Execute] button.
remote latch clear.
POINT (1) Remote latch clear cannot be operated while the PLC ready flag (M2000) is ON
(PCPU READY complete flag (SM500) is ON) or test mode. (2) The following latch area are cleared in the remote latch clear operation.
latch clear. (4) All of the user device not latched are cleared by the remote latch clear operation of
latch area (1) and (2). (5) Set the range of latch area (1) and (2) in the system basic setting of system setting.
(Refer to Section 3.1.3.)

MEMO

APPENDICES
APPENDIX 1 Special relays/Special registers
APPENDIX 1.1 Special relays
Special relays are internal relays whose applications are fixed in the Motion CPU. For this reason, they cannot be used in the same way as the normal internal relays by the Motion SFC programs. However, they can be turned ON/OFF as needed in order to control the Motion CPU.
The headings in the table that follows have the following meanings.
No. • Indicates the device No. of the special relay.
Name • Indicates the name of the special relay.
Meaning • Indicates the nature of the special relay.
Details • Indicates detailed information about the nature of the special relay.
setting is performed.
APP.
S: Set by system (Motion CPU)
U: Set by user (Motion SFC program or test operation using MT Developer)
Indicated only if setting is done by system (Motion CPU).
when executed the reset)
Error : Set when error is occurred.
Operation cycle : Set during each operation cycle of the Motion CPU.

Table 1.1 Special relay list
No. Name Meaning Details Set by (When set) Remark
S (Occur an error)
SM58 Battery low warning latch
(Note-1) CPU No.1 READY
CPU No.2 READY complete
CPU No.3 READY complete
CPU No.4 READY complete
SM240 No.1 CPU resetting OFF : CPU No.1 reset cancel ON : CPU No.1 resetting • Goes OFF when reset of the CPU No.1 is cancelled.
SM241 No.2 CPU resetting OFF : CPU No.2 reset cancel ON : CPU No.2 resetting • Goes OFF when reset of the CPU No.2 is cancelled.
SM242 No.3 CPU resetting OFF : CPU No.3 reset cancel ON : CPU No.3 resetting • Goes OFF when reset of the CPU No.3 is cancelled.

Table 1.1 Special relay list (Continued)
No. Name Meaning Details Set by (When set) Remark
SM243 No.4 CPU resetting OFF : CPU No.4 reset cancel ON : CPU No.4 resetting • Goes OFF when reset of the CPU No.4 is cancelled.
SM244 No.1 CPU error
SM245 No.2 CPU error
SM246 No.3 CPU error
SM247 No.4 CPU error
ON OFF • Normally is ON.
ON OFF • Normally is OFF. S (Main processing)
SM500 PCPU READY
SM502 External forced stop
ON : Forced stop OFF OFF : Forced stop ON • Confirm forced stop ON/OFF. S (Operation cycle)
SM510 TEST mode request
SM512 Motion CPU WDT
Manual pulse generator axis setting error
S (Occur an error)
settings are normal.
SM526 Over heat warning

Table 1.1 Special relay list (Continued)
No. Name Meaning Details Set by (When set) Remark
SM528 No.1 CPU MULTR
OFF to ON :
CPU No.1 read completion
SM529 No.2 CPU MULTR
OFF to ON :
CPU No.2 read completion
SM530 No.3 CPU MULTR
OFF to ON :
CPU No.3 read completion
SM531 No.4 CPU MULTR
OFF to ON :
CPU No.4 read completion
SM801 Clock data read
(Note-1) : It is used for interlock condition of Multiple CPU high speed bus dedicated instruction when a synchronous system
set in Multiple CPU synchronous startup setting of system setting. (Note-2) : The CPU No.1 is reset after the factor of the stop error is removed to cancel a stop error → Resetting is cancelled.

APPENDIX 1.2 Special registers
Special registers are internal registers whose applications are fixed in the Motion CPU. For this reason, it is not possible to use these registers in Motion SFC programs in the same way that normal registers are used. However, data can be written as needed in order to control the Motion CPU. Data stored in the special registers are stored as BIN values if no special designation has been made to the contrary.
The headings in the table that follows have the following meanings.
Number • Indicates the No. of the special register.
Name • Indicates the name of the special register.
Meaning • Indicates the nature of the special register.
Details • Indicates detailed information about the nature of the special register.
when setting is performed.
S: Set by system (Motion CPU)
U: Set by user (Motion SFC program or test operation using MT Developer)
Indicated only if setting is done by system (Motion CPU).
when executed the reset)
Error : Set when error is occurred.
Operation cycle : Set during each operation cycle of the Motion CPU.

Table 1.2 Special register list
No. Name Meaning Details Set by (When set) Remark
SD0 Diagnostic errors Diagnostic error
Example : January 2006 H0601 B15 B7 B0 B8 to to Month(1 to 12) Year(0 to 99)
Clock time for diagnostic error occurrence
Clock time for diagnostic error occurrence
Example : 25st, 10 a.m H2510 B15 B7 B0 B8 to to Day(1 to 31) Hour(0 to 23)
Second(0 to 59) B15 B7 B0 B8 to to Example : 35min., 48 sec. H3548 Minute(0 to 59)
B15 B7 B8 to to B0
S (Occur an error)
SD4 Error information categories
Error information category code
SD7
SD8
SD9
SD10
SD11
SD12
SD13
SD14 No. Meaning
SD5 Module No./CPU No./Base No.
SD6 I/O No.
SD15
APP - 6

Table 1.2 Special register list (Continued)
No. Name Meaning Details Set by (When set) Remark
SD18
SD19
SD20 No. Meaning
SD21 SD16 Parameter No.
SD17
SD23
SD24
SD25 0401H :Base setting
0406H :Motion slot setting
0E00H :Multiple CPU setting (Number of Multiple CPU's)
0E01H :Multiple CPU setting (Operation mode/Multiple CPU
E008H :Multiple CPU high speed transmission area setting
(CPU specific send range setting/ (System area))
S (Occur an error)
E009H/E00AH :Multiple CPU high speed transmission area setting
E00BH :Synchronous setting
No. Meaning
SD16 Parameter No.
SD17 CPU No.(1 to 4)
SD53 AC/DC DOWN counter No.
Number of times for AC/DC DOWN
SD60 Fuse blown No. Module No. with blown fuse • The lowest station I/O No. of the module with the blown fuse is stored.
SD200 Status of switch Status of CPU switch
Operating status of CPU
(Note) Priority is earliest first

Table 1.2 Special register list (Continued)
No. Name Meaning Details Set by (When set) Remark
B15 B12 to B11 B8 to B7 B4 to B3 B0 to
SD210 Clock data (Year, Month)
B15 B12 to B11 B8 to B7 B4 to B3 B0 to
SD211 Clock data (Day, Hour)
B15 B12 to B11 B8 to B7 B4 to B3 B0 to
SD212 Clock data (Minute, Second)
B15 B12 to B11 B8 to B7 B4 to B3 B0 to
Clock data (Day of week)
Always set to "0".
SD290 Number of points assigned for X • Stores the number of points currently set for X devices.
SD291 Number of points assigned for Y • Stores the number of points currently set for Y devices.
SD292 Number of points assigned for M • Stores the number of points currently set for M devices.
SD293 Number of points assigned for L • Stores the number of points currently set for L devices.
SD294 Number of points assigned for B • Stores the number of points currently set for B devices.
SD295 Number of points assigned for F • Stores the number of points currently set for F devices.
SD296 Number of points assigned for SB • Stores the number of points currently set for SB devices.
SD297 Number of points assigned for V • Stores the number of points currently set for V devices.
SD298 Number of points assigned for S • Stores the number of points currently set for S devices.
SD299 Number of points assigned for T • Stores the number of points currently set for T devices.
SD300 Number of points assigned for ST • Stores the number of points currently set for ST devices.
SD301 Number of points assigned for C • Stores the number of points currently set for C devices.
SD302 Number of points assigned for D • Stores the number of points currently set for D devices.
SD303 Number of points assigned for W • Stores the number of points currently set for W devices.
Number of points assigned for SW • Stores the number of points currently set for SW devices.
APP - 8

Table 1.2 Special register list (Continued)
No. Name Meaning Details Set by (When set) Remark
SD395 Multiple CPU No. Multiple CPU No. • CPU No. of the self CPU is stored. S (Initial processing)
Real mode axis information register
Real mode axis information register
S (At virtual mode
Servo amplifier loading information
Servo amplifier loading information
Real mode/virtual mode switching error information
Real mode /virtual mode switching error code
S (Occur an error)
Connect/ disconnect of SSCNET
It is operating in requirement error occurrence of the test mode, axis information
Test mode request error
Error meaning of WDT error occurs
S (Occur an error)
Manual pulse generator axis setting error information
Manual pulse generator axis setting error
(P1 to P3). The smoothing magnification setting is stored in b3 to b5 (P1 to P3). SD514 : One pulse input magnification setting error is stored in b0 to b15
(axis 1 to axis 16). SD515 : One pulse input magnification setting error is stored in b0 to b15
(axis 17 to axis 32).
Error program No. of servo program
No.
Error code of servo program
SD520 Scan time Scan time (1ms units)
Maximum scan time (1ms units)

Table 1.2 Special register list (Continued)

No. Name Meaning Details Set by (When set) Remark

APPENDIX 1.3 Replacement of special relays/special registers
When a project for Q173HCPU(-T)/Q172HCPU(-T)/Q173CPUN(-T)/Q172CPUN(-T)/ Q173CPU/Q172CPU is converted into a project for Q173DCPU/Q172DCPU using the "Project management - File diversion" in MT Developer, special relays (M9000 to M9255) and special registers (D9000 to D9255) are automatically converted into new special relays (SM2000 to SM2255) and special registers (SD2000 to SD2255) respectively. However, in order to maintain the same functionality the user must manually convert them to the special relays and special registers shown in Table 1.3 and Table 1.4 below for Q173DCPU/Q172DCPU.

M9060 SM2060 — Diagnostic error reset Use M2039 for error reset operation.
M9077 SM2077 SM513 Manual pulse generator axis setting error

Table 1.4 Replacement of special registers

D9010 SD2010 SD1 Clock time for diagnostic error occurrence (Year, month)
D9011 SD2011 SD2 Clock time for diagnostic error occurrence (Day, hour)
D9012 SD2012 SD3 Clock time for diagnostic error occurrence (Minute, second)
D9060 SD2060 — Diagnostic error reset error No. Use M2039 for error reset operation.
D9197 SD2197 SD523 Operation cycle of the Motion CPU setting

APPENDIX 2 System Setting Errors
Motion CPUs generate a system configuration error under the following conditions.
Error name 7-segment LED (Note-1)
AXIS No. MULTIDEF
AMP No. SETTING • Not a single axis is set in system settings.
AXIS No. ERROR • System setting data is not written.
I/O POINTS OVER • The number of actual I/O points set in system settings exceeds 256.
ROM ERROR1 • Type of the operating system software of data written to ROM is different.
ROM ERROR2 • Data is not written to ROM.
Cannot be started. (Motion CPU system setting error)
Power supply ON/ Reset
to the Motion modules (Q172DLX, Q173DPX, Q172DEX).
(Note-1) : "" AL" flashes 3-times "L01" display"" (Repetition) Error code is not displayed. (Note-2) : Error code stored in self-diagnostic error (SD0) (Note-3) : When the error code 10014 occurs, the system setting error flag (M2041) turns ON and the error name is displayed on the error
list monitor of MT Developer.

MEMO

APPENDIX 3 Self-diagnosis error code
Multiple CPU related errors are stored in the CPU shared memory "self CPU operation information area (1H to 1CH)" of each module and self diagnostic error information (SD0 to SD26) of the special register (SD) as the self diagnostic errors. Error codes (1000 to 9999) of Multiple CPU related errors are common to each CPU module. The error code (10000 to 10999) is stored as required at Motion CPU-specific error occurrence. Confirm the error codes and contents by "Motion error history" on Motion CPU error batch monitor of MT Developer and remove the error cause if an error occurs.

Confirm operation status and error occurrence of each CPU used in the Multiple CPU system by PLC diagnosis of GX Developer.


(1) Multiple CPU related errors which occurs in Motion CPU
Each digit of error code has been described as follows.
Major division 1 2 3 4 5 6 7 8 9
Tens digit Hundreds digit
:
Table 3.1 Multiple CPU related errors which occurs in Motion CPU (1000 to 9999)

(SD16 to SD26) 7-segment LED display CPU operation status
1150 RAM ERROR — — Stop At power ON/
1300 FUSE BREAK OFF Module No. — Stop (Note-3) Always
4 digits error code is displayed in two flashes
(Note-1) : CPU No. is stored in slot No. of common information classification. (Note-2) : Base No. stored in "common information classification code" of "error information classification code" "0 : Main base, 1 to 7 : Number of extension bases. (Note-3) : CPU operation status at error occurrence can be set in the parameters. (LED display varies in conjunction with operation.)

(SD0) Error contents and cause Corrective action
Runaway or failure of CPU module. (1) Malfunctioning due to noise or other reason (2) Hardware fault
(1) Take noise reduction measures. (2) Reset the CPU module and RUN it again. If the same error is
displayed again, this suggests a CPU module hardware fault. Explain the error symptom and get advice from our sales representative.
1105 The CPU shared memory in the CPU module is faulty.
1150 The memory of the CPU module in the Multiple CPU high speed transmission area is faulty.
1300 There is an output module with a blown fuse. Check FUSE. LED of the output modules and replace the module whose LED is lit.
Set the Motion module/intelligent function module used in the Motion CPU in the system setting. This suggests a Motion module, intelligent function module, CPU module and/or base unit is expecting a hardware fault. Explain the error symptom and get advice from our sales representative.
1401 There was no response from the Motion module/intelligent function module in the initial processing.
1403 (1) An error is detected at the intelligent function module. (2) The I/O module (including intelligent function module) is nearly
The CPU module, base unit and/or the intelligent function module that was accessed is experiencing a hardware fault. Explain the error symptom and get advice from our sales representative.
removed or completely removed/mounted during running.
1414 An error is detected on the system bus.
Reset the CPU module and RUN it again. If the same error is displayed again, the intelligent function module, CPU module or base unit is faulty. Explain the error symptom and get advice from our sales representative.
1415 Fault of the main or extension base unit was detected.
1416 System bus fault was detected at power-on or reset.
Error code

Table 3.1 Multiple CPU related errors which occurs in Motion CPU (1000 to 9999)

(SD16 to SD26) 7-segment LED display CPU operation status
4 digits error code is displayed in two flashes
Power supply 1500 AC/DC DOWN — — None Continue Always
Steady "BT1" Battery 1600 BATTERY ERROR Drive name —
4 digits error code is displayed in two flashes

(SD0) Error contents and cause Corrective action
Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module hardware fault. Explain the error symptom and get advice from our sales representative.
1430 The error of self CPU is detected in the Multiple CPU high speed bus.
(1) Take noise reduction measures. (2) Check the main base unit mounting status of the CPU module. (3) Reset the CPU module and RUN it again. If the same error is
1431 The communication error with other CPU is detected in the Multiple CPU high speed bus.
displayed again, this suggests a CPU module or base unit hardware fault. Explain the error symptom and get advice from our sales representative.
Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module hardware fault. Explain the error symptom and get advice from our sales representative.
1432 The communication time out with other CPU is detected in the Multiple CPU high speed bus.
(1) Take noise reduction measures. (2) Check the main base unit mounting status of the CPU module. (3) Reset the CPU module and RUN it again. If the same error is displayed
The communication error with other CPU is detected in the Multiple CPU high speed bus.
again, this suggests a CPU module or base unit hardware fault. Explain the error symptom and get advice from our sales representative.
1500 A momentary power supply interruption has occurred. The power supply went off. Check the power supply.
(1) The battery voltage in the CPU module has dropped below
stipulated level. (2) The battery holder unit that install the battery is not mounted to the
(1) Change the battery. (2) Mount the battery holder unit that installs the battery.
CPU module.
Make the PLC parameter's I/O assignment setting again so it is consistent with the actual status of the intelligent function module and the CPU module.
2100 In the I/O assignment setting of PLC CPU, the intelligent function module was allocated to an I/O module or vice versa.
2107 The first I/O No. set in the system settings is overlapped with the one for another module.
Make the I/O No. setting again so it is consistent with the actual status of the modules.
2124 (1) A module is mounted on the 65th or higher slot. (2) The extension base unit set to "None" is mounted.
(1) Remove the module mounted on the 65th or later slot. (2) Remove the extension base unit set to "None".
(1) Install an usable module. (2) The intelligent function module is experiencing a hardware fault.
2125 (1) A module which the CPU cannot recognise has been mounted. (2) There was no response form the intelligent function module.
Explain the error symptom and get advice from our sales representative.
2140 The motion modules (Q172DLX, Q172DEX, Q173DPX, Q172LX, Q172EX (-S1/-S2/-S3), Q173PX (-S1)) are installed in CPU slot or I/O 0 to 2 slot.
Remove the Motion modules installed CPU slot or I/O 0 to 2 slot.
(1) Change to the intelligent function module (function version B or later)
2150 In a Multiple CPU system, the control CPU of intelligent function module incompatible with the Multiple CPU system is set to other than CPU No.1.
compatible with the Multiple CPU system. (2) Change the control CPU of intelligent function module incompatible with
the Multiple CPU system to CPU No.1.
Error code

Table 3.1 Multiple CPU related errors which occurs in Motion CPU (1000 to 9999)

(SD16 to SD26) 7-segment LED display CPU operation status
4 digits error code is displayed in two flashes
(Note-1) : CPU No. is stored in slot No. of common information classification. (Note-4) : Because a stop error or CPU No. except CPU No. that it was reset becomes MULTI CPU DOWN simultaneously, a stop error or CPU No. except CPU
No. that it was reset may store in the classification of common error information depending on timing.

(SD0) Error contents and cause Corrective action
(1) Check the parameter item corresponding the numerical value
(parameter No.), and correct it. (2) Rewrite corrected parameters to the CPU module, reload or reset the
3001 The parameter settings are corrupted.
Multiple CPU system power supply. (3) If the same error occurs, it is thought to be a hardware error.
Explain the error symptom and get advice from our sales representative.
3012 Multiple CPU setting of Multiple CPU setting parameter or control CPU setting of system setting differs from that of the reference CPU settings.
Match the Multiple CPU setting of Multiple CPU setting parameter or control CPU setting of system setting with that of the reference CPU (CPU No.1) settings.
Check the following in the Multiple CPU automatic refresh setting and make correction. (1) When specifying the bit device, specify a multiple of 16 for the refresh
Multiple CPU automatic refresh setting is any of the following. (1) When a bit device is specified as a refresh device, a number other
than a multiple of 16 is specified for the refresh start device. (2) The device specified is other than the one that may be specified. (3) The number of send points is an odd number. (4) The total number of send points is greater than the maximum
start device. (2) Specify the device that may be specified for the refresh device. (3) Set the number of send points to an even number. (4) Set the total number of send points is within the range of the maximum
number of refresh points.
number of refresh points.
(1) Set "Use multiple CPU high speed transmission " in the Universal
(1) "Use multiple CPU high speed transmission " is not set in the
module QCPU. (2) Check the parameter item corresponding to the numerical value
Multiple CPU setting of Universal module QCPU. (2) In a Multiple CPU system, the CPU verified is different from the
(parameter No./CPU No.) and parameter of target CPU, and correct them.
one set in the parameter setting.
In the operating mode of a Multiple CPU system, a CPU error occurred at the CPU where "All station stop by stop error of CPU" was selected.
Check the error of the CPU resulting in CPU module fault, and remove the errors.
7000 In a Multiple CPU system, CPU No.1 resulted in stop error at power- on and the other CPU cannot start. (This error occurred at CPU No.2 to 4)
Reset the CPU module and RUN it again. If the same error is displayed again, this suggests the hardware fault of any of the CPU modules. Explain the error symptom and get advice from our sales representative.
7002 There is no response from the target CPU module in a Multiple CPU system during initial communication.
7010 In a Multiple CPU system, a faulty CPU module was mounted. Replace the faulty CPU module.
Either of the following settings was made in a Multiple CPU system. (1) Multiple CPU automatic refresh setting was made for the
(1) Correct the Multiple CPU automatic refresh setting. (2) Correct the "I/O sharing when using multiple CPUs" setting.
inapplicable CPU module. (2) "I/O sharing when using multiple CPUs" setting was made for the
inapplicable CPU module.
7011 The system configuration for using the Multiple CPU high speed transmission function is not met. (1) The QnUD(H)CPU is not used for the CPU No.1. (2) The Multiple CPU high speed main base unit (Q3 DB) is not used.
Change to the system configuration to meet the conditions for using the Multiple CPU high speed transmission function.
7013 (1) CPU module which cannot be mounted in OnCPU(H)CPU is
mounted. (The module may break down.) (2) Q173HCPU,Q172HCPU,Q173CPUN,Q172CPUN is mounted.
Remove Q173HCPU,Q172HCPU,Q173CPUN,Q172CPUN.
7020 In the operating mode of a Multiple CPU system, an error occurred in the CPU where "system stop" was not selected. (The CPU module where no error occurred was used to detect an error.)
Check the error of the CPU resulting in CPU module fault, and remove the error.
7030 An assignment error occurred in the CPU-mountable slot (CPU slot, I/O slot 0 to 2) in excess of the number of CPU slot (with in the range of CPU number setting parameter).
(1) Set the same value to the number of CPU modules specified in the
Multiple CPU setting of the PLC parameter and the number of mounted CPU modules (including CPU (empty)). (2) Make the same as the state of the installation of CPU module set in the
7031 An assignment error occurred in the CPU slot (within the range of the CPU number setting parameter).
system setting.
7035 The CPU module has been mounted on the inapplicable slot. Mount the CPU module on the applicable slot.
Error code

(2) Motion CPU-specific errors
Each digit of error code has been described as follows. Refer to programming manuals for error details.
Details code 1 0

003 004 005 006 007 008 009 010 011 014 016 020 021 022 023 030
Minor/major error (Virtual servomoter axis)(SV22) Minor/major error (Synchronous encoder axis)(SV22)
Tens digit Hundreds digit
:
: Positioning CPU division (0 : Motion CPU)
WDT error System setting error Motion slot fault Motion SFC control error (F/FS)
Motion SFC control error (G) Motion SFC control error (K or others (Not F/FS, G)) Motion SFC control error (Motion SFC chart)

(SD16 to SD26) 7-segment LED display CPU status operation
Digit · Thousands digit

(SD0) Error contents and cause Corrective action
10003 Minor/major errors had occurred.
Check the Motion error history of MT Developer and the minor/major error codes of minor/major error code of minor/major error code storage device, and remove the error cause. Refer to the error codes for error details of minor/major errors.
10004 Minor/major errors had occurred in virtual servomotor axis. (SV22)
10005 Minor/major errors had occurred in synchronous encoder axis. (SV22)
Check the Motion error history of MT Developer and the servo error codes of servo error code storage device, and remove the error cause of servo amplifier. Refer to the servo error code for details of servo errors.
10006 The servo errors had occurred in the servo amplifier connected to the Motion CPU.
Check the Motion error history of MT Developer and the servo program setting error storage device (error program No., error item information), and remove the error cause. Refer to the servo program setting error codes for details of servo program setting errors.
10007 Servo program setting error occurred.
Check the Motion error history of MT Developer and the real mode/virtual mode switching error storage device, and remove the error cause. Refer to the real mode/virtual mode switching error codes for details of real mode/virtual mode switching errors.
10008 Real mode/virtual mode switching error occurred. (SV22)
Check the Motion error history of MT Developer and the manual pulse generator axis setting error storage device, and remove the error cause. Refer to the manual pulse generator axis setting error codes for details of manual pulse generator axis setting errors.
10009 Manual pulse generator axis setting error occurred.
10010 Test mode request error occurred. Check the Motion error history of MT Developer and the test mode request error storage device, and remove the error cause.
10011 WDT error occurred at Motion CPU. Check the Motion error history of MT Developer and the Motion CPU WDT error factors, and remove the error cause.
10014 System setting error occurred at Motion CPU.
Check the error message on error monitor screen of MT Developer, and remove the error cause. And then, turn on the power supply again or reset the Multiple CPU system.
10016 Motion slot fault occurred at Motion CPU.
Check the Motion error history of MT Developer, and remove the error cause. Refer to the Motion SFC error code for details of errors.
Motion SFC error occurred at Motion SFC program.
10030 Motion CPU internal bus error occurred. Motion CPU module hardware fault. Explain the error symptom and get advice from our sales representative.
Error code

(3) Self-diagnostic error information
No. Name Meaning Details
SD0 Diagnostic errors Diagnostic error
code • Error codes for errors found by diagnosis are stored as BIN data.
Example : January 2006 H0601 B15 B7 B0 B8 to to Month(1 to 12) Year(0 to 99)
Clock time for diagnostic error occurrence
Clock time for diagnostic error occurrence
Example : 25st, 10 a.m H2510 B15 B7 B0 B8 to to Day(1 to 31) Hour(0 to 23)
Second(0 to 59) B15 B7 B0 B8 to to Example : 35min., 48 sec. H3548 Minute(0 to 59)
B15 B7 B8 to to B0
SD4 Error information categories
Error information category code
No. Meaning
SD5 Module No./CPU No./Base No.
SD6 I/O No.
No. Meaning
SD16 Parameter No.
0401H :Base setting
0406H :Motion slot setting
0E00H :Multiple CPU setting (Number of Multiple CPU's)
0E01H :Multiple CPU setting (Operation mode/ Multiple CPU synchronous startup)
E008H :Multiple CPU high speed transmission area setting
(CPU specific send range setting / (System area))
E00BH :Synchronous setting
No. Meaning
SD16 Parameter No.
SD17 CPU No.(1 to 4)
APP - 24

(4) Release of Multiple CPU related error
The release operation of errors that continues operation for CPU can be executed. Release the errors in the following procedure. 1) Remove the error cause. 2) Turn off the Motion error detection flag (M2039).
The special relays, special registers and 7-segment LED for the errors are returned to the status before error occurs after release of errors. If the same error is displayed again after release of errors, an error is set again, and the Motion error detection flag (M2039) turns on.

APPENDIX 4 Differences Between Q173DCPU/Q172DCPU and Q173HCPU/Q172HCPU
APPENDIX 4.1 Differences Between Q173DCPU/Q172DCPU and Q173HCPU/Q172HCPU
Common differences to each mode are shown in Table 4.1. Refer to "APPENDIX 4.3 Differences of each mode" for characteristic differences to each mode. And, refer to "APPENDIX 4.2 Comparison of devices " for detailed differences of devices. Table 4.1 Differences Between Q173DCPU/Q172DCPU and Q173HCPU/Q172HCPU
Peripheral I/F Via PLC CPU (USB/RS-232) USB/SSCNET
External battery Demand Add Q6BAT at continuous power failure for 1 month or more.
Multiple CPU high speed transmission memory for data transfer between CPU modules
Internal relays (M) 8192 points
Latch relays (L) None (Latch for M is possible by latch setting)
Special relays (M) — 256 points
Special relays (SM) 2256 points —
Special registers (D) — 256 points
Special registers (SD) 2256 points —
Motion registers (#) 8736 points 8192 points
Multiple CPU area devices (U \G) Up to 14336 points —
S(P).DDRD, S(P).DDWR, S(P).SFCS, S(P).SVST, S(P).CHGT, S(P).CHGV, S(P).CHGA, S(P).GINT
Motion dedicated PLC instructions
Multiple instructions are executable continuously without interlock condition by the self CPU high speed interrupt accept flag from CPU . :CPU No.
Interlock condition by the to self CPU high speed interrupt accept flag from CPU is necessary.
Motion modules Q172DLX, Q172DEX, Q173DPX Q172LX, Q172EX, Q173PX
Latch clear Remote operation L.CLR switch
RUN/STOP Remote operation, RUN/STOP switch RUN/STOP switch
Rom writing is executed with installation mode/ mode written in ROM.

Table 4.1 Differences Between Q173DCPU/Q172DCPU and Q173HCPU/Q172HCPU
(Continued)
Medium of operating system software CD-ROM (1 disk) FD (2 disks)
Model of operating system software SW8DNC-SV Q SW6RN-SV Q
CPU module No.1 QnUD(H)CPU Qn(H)CPU
Installation orders CPU No.2 or later No restriction Install Motion CPU module on the right-hand side of PLC CPU module.
Combination of Motion CPU modules Q173DCPU/Q172DCPU only Combination with Q173CPUN(-T)/Q172CPUN(-T).
CPU empty slot Settable between CPU modules Not settable between CPU modules
Multiple CPU high speed transmission area
Provided None CPU shared memory
Access by Multiple CPU shared memory Possible Impossible
Memory Multiple CPU high speed transmission area in CPU shared memory Automatic refresh area in CPU shared memory
Automatic refresh setting 32 range possible 4 range possible Automatic refresh
Multiple CPU high speed refresh function
LED display 7-segment LED display Each LED of MODE, RUN, ERR, M.RUN, BAT
Range which can be cleared with the latch clear key. Latch range setting
Latch (1) It is possible to clear with latch clear(1) and latch clear (1)(2) of remote latch clear.
Latch (2) It is possible to clear with lath clear(1)(2) of remote latch clear.
Range which cannot be cleared with the latch clear key.
All clear function Execute with installation mode Turn off the PLC ready flag (M2000) and test mode ON flag (M9075) to execute all clear.
Store the error code to be released in the special register D9060 and turn off to on the special relay M9060.
Release of Multiple CPU related error Turn off M2039.
Item Q173DCPU/Q172DCPU Q173HCPU/Q172HCPU · Provided None · and BOOT

APPENDIX 4.2 Comparison of devices
(1) Motion registers
Table 4.2 Motion registers (Monitor devices) list

#8000 to #8019 #8064 to #8067 Axis 1 monitor device
#8020 to #8039 #8068 to #8071 Axis 2 monitor device
#8040 to #8059 #8072 to #8075 Axis 3 monitor device
#8060 to #8079 #8076 to #8079 Axis 4 monitor device
#8080 to #8099 #8080 to #8083 Axis 5 monitor device
#8100 to #8119 #8084 to #8087 Axis 6 monitor device
#8120 to #8139 #8088 to #8091 Axis 7 monitor device
#8140 to #8159 #8092 to #8095 Axis 8 monitor device
#8160 to #8179 #8096 to #8099 Axis 9 monitor device
#8180 to #8199 #8100 to #8103 Axis 10 monitor device
#8200 to #8219 #8104 to #8107 Axis 11 monitor device
#8220 to #8239 #8108 to #8111 Axis 12 monitor device
#8240 to #8259 #8112 to #8115 Axis 13 monitor device
#8260 to #8279 #8116 to #8119 Axis 14 monitor device
#8280 to #8299 #8120 to #8123 Axis 15 monitor device
#8300 to #8319 #8124 to #8127 Axis 16 monitor device
#8320 to #8339 #8128 to #8131 Axis 17 monitor device
#8340 to #8359 #8132 to #8135 Axis 18 monitor device
#8360 to #8379 #8136 to #8139 Axis 19 monitor device
#8380 to #8399 #8140 to #8143 Axis 20 monitor device
#8400 to #8419 #8144 to #8147 Axis 21 monitor device
#8420 to #8439 #8148 to #8151 Axis 22 monitor device
#8440 to #8459 #8152 to #8155 Axis 23 monitor device
#8460 to #8479 #8156 to #8159 Axis 24 monitor device
#8480 to #8499 #8160 to #8163 Axis 25 monitor device
#8500 to #8519 #8164 to #8167 Axis 26 monitor device
#8520 to #8539 #8168 to #8171 Axis 27 monitor device
#8540 to #8559 #8172 to #8175 Axis 28 monitor device
#8560 to #8579 #8176 to #8179 Axis 29 monitor device
#8580 to #8599 #8180 to #8183 Axis 30 monitor device
#8600 to #8619 #8184 to #8187 Axis 31 monitor device
#8620 to #8639 #8188 to #8191 Axis 32 monitor device
(a) Monitor devices

Table 4.3 Monitor devices list

#8000 + 20n #8064 + 4n Servo amplifier type
#8004 + 20n #8005 + 20n — Command speed
#8006 + 20n #8007 + 20n — Home position return re-travel value
(Note-1) : "n" in the above device No. indicates the numerical value which correspond to axis No.
(b) Motion error history

#8640 to #8651 #8000 to #8007 Seventh error information in past (Oldest error information)
#8652 to #8663 #8008 to #8015 Sixth error information in past
#8664 to #8675 #8016 to #8023 Fifth error information in past
#8676 to #8687 #8024 to #8031 Fourth error information in past
#8688 to #8699 #8032 to #8039 Third error information in past
#8700 to #8711 #8040 to #8047 Second error information in past
#8712 to #8723 #8048 to #8055 First error information in past
#8724 to #8735 #8056 to #8063 Latest error information

#8640 + 12n #8000 + 8n Error Motion SFC program No.
#8642 + 12n #8002 + 8n Error program No.
#8643 + 12n #8003 + 8n Error block No./Motion SFC list/Line No./Axis No.
#8645 + 12n #8005 + 8n Error occurrence time (Year/month
#8646 + 12n #8006 + 8n Error occurrence time (Day/hour)
#8647 + 12n #8007 + 8n Error occurrence time (Minute/second)
#8650 + 12n #8651 + 12n — Error setting data
(Note-1) : "n" in the above device No. indicates the numerical value which correspond to axis No.

(2) Special relays
Table 4.6 Special relay list

— M9060/M3138 Diagnostic error reset Use M2039 for error reset operation.

(3) Special registers
Table 4.7 Special registers list

SD1 D9010 Clock time for diagnostic error occurrence (Year, month)
SD2 D9011 Clock time for diagnostic error occurrence (Day, hour)
SD3 D9012 Clock time for diagnostic error occurrence (Minute, second)
— D9060 Diagnostic error reset error No. Use M2039 for error reset operation.

Table 4.7 Special registers list (Continued)

SD523 D9197 Operation cycle of the Motion CPU setting
— D9201 State of LED Use 7-segment LED in Q173DCPU/Q172DCPU.

(4) Other devices
Table 4.8 Other devices list
M2320 to M2399 Unusable Special relay allocated devices (Status)
M2400 to M3039 Device area of 9 axes or more is usable as user devices in Q172DCPU.
Device area of 9 axes or more is unusable as user devices in Q172HCPU.
Internal relays/ Data registers
M3136 to M3199 Unusable Special relay allocated devices (Command signal)
Device area of 9 axes or more is usable as user devices in Q172DCPU.
Device area of 9 axes or more is unusable in Q172HCPU.
Personal computer link communication error flag — M2034
PCPU READY complete SM500 D759
D9 + 20n (Data shortened to 1 word) (Note-1)
D9 + 20n (Note-1)
Home position return re-travel value #8006 + 20n, #8007 + 20n (Referring at monitoring) (Note-1)
Optional device (Set for D16 + 20n, D17 + 20n are also usable.)
Travel value change registers
D16 + 20n, D17 + 20n (Note-1)
D0 to D8191 D800 to D8191
Indirect setting devices (Word devices)
W0 to W1FFF W0 to W1FFF
#0 to #7999 #0 to #7999
U \G10000 to U \G(10000 + p – 1) (Note-2) —
X0 to X1FFF X0 to X1FFFF
Y0 to Y1FFF Y0 to Y1FFF
M0 to M8191 M/L0 to M/L8191
Indirect setting devices (Bit devices)
— M9000 to M9255
B0 to B1FFF B0 to B1FFF
F0 to F2047 F0 to F2047
U \G10000.0 to U \G(10000 + p – 1).F (Note-2) —
D0 to D8191 D800 to D3069, D3080 to D8191
High-speed reading function settable devices
W0 to W1FFF W0 to W1FFF
U \G10000 to U \G(10000 + p – 1) (Note-2) —
D0 to D8191 D0 to D8191
W0 to W1FFF W0 to W1FFF
Optional data monitor function settable devices
#0 to #7999 #0 to #7999
U \G10000 to U \G(10000 + p – 1) (Note-2) —
(Note-1) : "n" in the above device No. indicates the numerical value which correspond to axis No. (Note-2) : "p" indicates the user setting area points of Multiple CPU high speed transmission area in each CPU.

Table 4.8 Other devices list (Continued)

U \G10000.0 to U \G(10000 + p –1).F (Note-2) —
U \G10000 to U \G(10000 + p –1) (Note-2) —
U \G10000 to U \G(10000 + p – 1) (Note-2) —
U \G10000.0 to U \G(10000 + p – 1).F (Note-2) —
(Note-2) : "p" indicates the user setting area points of Multiple CPU high speed transmission area in each CPU. (Note-3) : Setting range varies depending on the setting units.

POINT Refer to Chapter 2 for number of user setting area points of Multiple CPU high speed transmission area.

APPENDIX 4.3 Differences of each mode
(1) Motion SFC
Table 4.9 Differences in Motion SFC mode

Motion SFC program executing flag X, Y, M, B, U \G —
Operation control/transition control usable device (Word device) D, W, U \G, SD, #, FT D, W, Special D, #, FT
Operation control/transition control usable device (Bit device) X, PX, Y, PY, M, U \G . , B, F, SM X, PX, Y, PY, M, L, B, F, Special M
Table 4.10 Differences in Virtual mode
M5440 to M5487 Internal relay/ Data register
Device area of 9 axes or more is usable as user devices in the Q172DCPU.
Device area of 9 axes or more is unusable in the Q172HCPU.
Clutch status Optional device (Set for M2160 to M2223 are also usable.) M2160 to M2223
Cam axis command signals (Cam/ball screw switching command)
Optional device (Set for M5488 to M5519 are also usable.) M5488 to M5519
Smoothing clutch complete signals Optional device (Set for M5520 to M5583 are also usable.) M5520 to M5583
Real mode axis information register SD500, SD501 D790, D791
D0 to D8191 D800 to D3069, D3080 to D8191
Indirect setting devices of mechanical system program (Word device)
W0 to W1FFF W0 to W1FFF
#0 to #7999 —
U \G10000 to U \G(10000 + p –1 ) (Note-1) —
X0 to X1FFF X0 to X1FFF
Y0 to Y1FFF Y0 to Y1FFF
Indirect setting devices of mechanical system program (Bit device)
M0 to M8191 M/L0 to M/L8191
— M9000 to M9255
B0 to B1FFF B0 to B1FFF
F0 to F2047 F0 to F2047
U \G10000.0 to U \G(10000 + p –1 ).F (Note-1) —
Speed change ratio of speed change gear
Permissible droop pulse value of output module 1 to 1073741824 [PLS] 1 to 65535[∗100PLS]
(Note-1) : "p" indicates user setting area points of Multiple CPU high speed transmission area in each CPU.

POINT Refer to Chapter 2 for number of user setting area points of Multiple CPU high speed transmission area.
Item Q173DCPU/Q172DCPU Q173HCPU/Q172HCPU · M4640 to M4687 · D1120 to D1239
![Page 171 of the Mitsubishi Electronics Q172DCPU user manual — [ Gratis Warranty Term]](/cdn/reader/ff/ff79c707ba6e0c6fccf2d339d546c863431b91850597ac25598199bd366ce101/images/page-171.webp?w=400)
Please confirm the following product warranty details before using this product. 1. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company. However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module.
(1) Diagnosis of failure
As a general rule, diagnosis of failure is done on site by the customer. However, Mitsubishi or Mitsubishi service network can perform this service for an agreed upon fee upon the customer’s request. There will be no charges if the cause of the breakdown is found to be the fault of Mitsubishi.
There will be a charge for breakdown repairs, exchange replacements and on site visits for the following four conditions, otherwise there will be a charge. 1) Breakdowns due to improper storage, handling, careless accident, software or hardware design by the customer 2) Breakdowns due to modifications of the product without the consent of the manufacturer 3) Breakdowns resulting from using the product outside the specified specifications of the product 4) Breakdowns that are outside the terms of warranty
Since the above services are limited to Japan, diagnosis of failures, etc. are not performed abroad. If you desire the after service abroad, please register with Mitsubishi. For details, consult us in advance. 2. Exclusion of Loss in Opportunity and Secondary Loss from Warranty Liability Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties. 3. Onerous Repair Term after Discontinuation of Production Mitsubishi shall accept onerous product repairs for seven years after production of the product is discontinued. 4. Delivery Term In regard to the standard product, Mitsubishi shall deliver the standard product without application settings or adjustments to the customer and Mitsubishi is not liable for on site adjustment or test run of the product. 5. Precautions for Choosing the Products (1) These products have been manufactured as a general-purpose part for general industries, and have not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life. (2) Before using the products for special purposes such as nuclear power, electric power, aerospace, medicine,
passenger movement vehicles or under water relays, contact Mitsubishi. (3) These products have been manufactured under strict quality control. However, when installing the product where
major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system. (4) When exporting any of the products or related technologies described in this catalogue, you must obtain an
export license if it is subject to Japanese Export Control Law.
(2) Breakdown repairs


Q173D-P-COM-E
MODEL
1XB928
CODE
IB(NA)-0300134-A(0801)MEE
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.



EUROPEAN REPRESENTATIVES
EUROPEAN REPRESENTATIVES
EURASIAN REPRESENTATIVES
EUROPE MITSUBISHI ELECTRIC EUROPE B.V. German Branch GothaerStraße 8 D-40880 Ratingen Phone: +49 (0)2102 / 486-0 Fax: +49 (0)2102 / 486-1120
AUSTRIA GEVA Wiener Straße 89 AT-2500 Baden Phone: +43 (0)2252 / 85 55 20 Fax: +43 (0)2252 / 488 60
MALTA ALFATRADE Ltd. 99, Paola Hill Malta- Paola PLA 1702 Phone: +356 (0)21 / 697 816 Fax: +356 (0)21 / 697 817
KAZAKHSTAN Kazpromautomatics Ltd. Mustafina Str. 7/2 KAZ-470046 Karaganda Phone: +7 7212 / 50 11 50 Fax: +7 7212 / 50 11 50
BELARUS TEHNIKON Oktyabrskaya 16/5, Off. 703-711 BY-220030 Minsk Phone: +375 (0)17 / 210 46 26 Fax: +375 (0)17 / 210 46 26
MOLDOVA INTEHSIS srl bld. Traian 23/1 MD-2060 Kishinev Phone: +373 (0)22 / 66 4242 Fax: +373 (0)22 / 66 4280
CZECH REPUBLIC MITSUBISHIELECTRICEUROPEB.V. Czech Branch Avenir Business Park, Radlická 714/113a CZ-158 00 Praha 5 Phone: +420 (0)251 551 470 Fax: +420 (0)251-551-471
ISRAEL ILAN & GAVISH Ltd. 24 Shenkar St., Kiryat Arie IL-49001 Petah-Tiqva Phone: +972 (0)3 / 922 18 24 Fax: +972 (0)3 / 924 0761
BELGIUM Koning & Hartman b.v. Woluwelaan 31 BE-1800 Vilvoorde Phone: +32 (0)2 / 257 02 40 Fax: +32 (0)2 / 257 02 49
NETHERLANDS Koning & Hartman b.v. Haarlerbergweg 21-23 NL-1101 CH Amsterdam Phone: +31 (0)20 / 587 76 00 Fax: +31 (0)20 / 587 76 05
FRANCE MITSUBISHI ELECTRIC EUROPE B.V. French Branch 25, Boulevard des Bouvets F-92741 NanterreCedex Phone: +33 (0)1 / 55 68 55 68 Fax: +33 (0)1 / 55 68 57 57
BOSNIA AND HERZEGOVINA INEA BH d.o.o. Aleja Lipa 56 BA-71000 Sarajevo Phone: +387 (0)33 / 921 164 Fax: +387 (0)33/ 524 539
NORWAY Beijer Electronics AS Postboks 487 NO-3002 Drammen Phone: +47 (0)32 / 24 30 00 Fax: +47 (0)32 / 84 85 77
ISRAEL TEXEL ELECTRONICS Ltd. 2 Ha´umanut, P.O.B. 6272 IL-42160 Netanya Phone: +972 (0)9 / 863 39 80 Fax: +972 (0)9 / 885 24 30
IRELAND MITSUBISHI ELECTRIC EUROPE B.V. Irish Branch Westgate Business Park, Ballymount IRL-Dublin 24 Phone: +353 (0)1 4198800 Fax: +353 (0)1 4198890
LEBANON CEG INTERNATIONAL Cebaco Center/Block A Autostrade DORA Lebanon - Beirut Phone: +961 (0)1 / 240 430 Fax: +961 (0)1 / 240 438
BULGARIA AKHNATON 4 Andrej Ljapchev Blvd. Pb 21 BG-1756 Sofia Phone: +359 (0)2 / 817 6004 Fax: +359 (0)2 / 97 44 06 1
POLAND MPL Technology Sp. z o.o. Ul. Krakowska 50 PL-32-083 Balice Phone: +48 (0)12 / 630 47 00 Fax: +48 (0)12 / 630 47 01
ITALY MITSUBISHI ELECTRIC EUROPE B.V. Italian Branch Viale Colleoni 7 I-20041 Agrate Brianza (MI) Phone: +39 039 / 60 53 1 Fax: +39 039 / 60 53 312
CROATIA INEA CR d.o.o. Losinjska 4 a HR-10000 Zagreb Phone:+385(0)1/36940-01/-02/-03 Fax: +385 (0)1 / 36 940 - 03
ROMANIA Sirius Trading & Services srl Aleea Lacul Morii Nr. 3 RO-060841 Bucuresti, Sector 6 Phone: +40 (0)21 / 430 40 06 Fax: +40 (0)21 / 430 40 02
SOUTH AFRICA CBI Ltd. Private Bag 2016 ZA-1600 Isando Phone: + 27 (0)11 / 928 2000 Fax: + 27 (0)11 / 392 2354
SPAIN MITSUBISHI ELECTRIC EUROPE B.V. Spanish Branch Carretera de Rubí 76-80 E-08190 Sant Cugat del Vallés (Barcelona) Phone: 902 131121 // +34 935653131 Fax: +34 935891579
CZECH REPUBLIC AutoCont C.S. s.r.o. Technologická 374/6 CZ-708 00 Ostrava-Pustkovec Phone: +420 595 691 150 Fax: +420 595 691 199
SERBIA Craft Con. & Engineering d.o.o. Bulevar Svetog Cara Konstantina 80-86 SER-18106 Nis Phone:+381 (0)18 / 292-24-4/5 Fax: +381 (0)18 / 292-24-4/5
UK MITSUBISHI ELECTRIC EUROPE B.V. UK Branch Travellers Lane UK-Hatfield, Herts. AL10 8XB Phone: +44 (0)1707 / 27 61 00 Fax: +44 (0)1707 / 27 86 95
CZECH REPUBLIC B:TECH A.S. U Borové 69 CZ-58001 Havlíčkův Brod Phone: +420 (0)569 777 777 Fax: +420 (0)569-777 778
SERBIA INEA SR d.o.o. Izletnicka 10 SER-113000 Smederevo Phone: +381 (0)26 / 617 163 Fax: +381 (0)26 / 617 163
DENMARK Beijer Electronics A/S Lykkegårdsvej 17, 1. DK-4000 Roskilde Phone: +45 (0)46/ 75 76 66 Fax: +45 (0)46 / 75 56 26
SLOVAKIA AutoCont Control s.r.o. Radlinského 47 SK-02601 Dolny Kubin Phone: +421 (0)43 / 5868210 Fax: +421 (0)43 / 5868210
JAPAN MITSUBISHI ELECTRIC CORPORATION Office Tower “Z” 14 F 8-12,1 chome, Harumi Chuo-Ku Tokyo 104-6212 Phone: +81 3 622 160 60 Fax: +81 3 622 160 75
ESTONIA Beijer Electronics Eesti OÜ Pärnu mnt.160i EE-11317 Tallinn Phone: +372 (0)6 / 51 81 40 Fax: +372 (0)6 / 51 81 49
SLOVAKIA CS MTrade Slovensko, s.r.o. Vajanskeho 58 SK-92101 Piestany Phone: +421 (0)33 / 7742 760 Fax: +421 (0)33 / 7735 144
USA MITSUBISHI ELECTRIC AUTOMATION, Inc. 500 Corporate Woods Parkway Vernon Hills, IL 60061 Phone: +1 847 478 21 00 Fax: +1 847 478 22 53
FINLAND Beijer Electronics OY Jaakonkatu 2 FIN-01620 Vantaa Phone: +358 (0)207 / 463 500 Fax: +358 (0)207 / 463 501
SLOVENIA INEA d.o.o. Stegne 11 SI-1000 Ljubljana Phone: +386 (0)1 / 513 8100 Fax: +386 (0)1 / 513 8170
GREECE UTECO A.B.E.E. 5, Mavrogenous Str. GR-18542 Piraeus Phone: +30 211 / 1206 900 Fax: +30 211 / 1206 999
SWEDEN Beijer Electronics AB Box 426 SE-20124 Malmö Phone: +46 (0)40 / 35 86 00 Fax: +46 (0)40 / 35 86 02
HUNGARY MELTRADE Ltd. Fertő utca 14. HU-1107 Budapest Phone: +36 (0)1 / 431-9726 Fax: +36 (0)1 / 431-9727
SWITZERLAND Econotec AG Hinterdorfstr. 12 CH-8309 Nürensdorf Phone: +41 (0)44 / 838 48 11 Fax: +41 (0)44 / 838 48 12
LATVIA Beijer Electronics SIA Vestienas iela 2 LV-1035 Riga Phone: +371 (0)784 / 2280 Fax: +371 (0)784 / 2281
TURKEY GTS Darülaceze Cad. No. 43 KAT. 2 TR-34384 Okmeydanı-Istanbul Phone: +90 (0)212 / 320 1640 Fax: +90 (0)212 / 320 1649
LITHUANIA Beijer Electronics UAB Savanoriu Pr. 187 LT-02300 Vilnius Phone: +370 (0)5 / 232 3101 Fax: +370 (0)5 / 232 2980
UKRAINE CSC Automation Ltd. 4-B, M. Raskovoyi St. UA-02660 Kiev Phone: +380 (0)44 / 494 33 55 Fax: +380 (0)44 / 494-33-66
Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Straße 8 /// D-40880 Ratingen /// Germany Tel.: +49(0)2102-4860/// Fax: +49(0)2102-4861120/// info@mitsubishi-automation.com /// www.mitsubishi-automation.com
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| SD500 | b0 to b15 (Axis 1 to 16) | p.144 | |
| SD501 | b0 to b15 (Axis 17 to 32) | p.144 | |
| SD502 | b0 to b15 (Axis 1 to 16) | p.144 | |
| SD503 | b0 to b15 (Axis 17 to 32) | p.144 | |
| SD510 | b0 to b15 (Axis 1 to Axis 16) | p.144 | |
| SD511 | b0 to b15 (Axis 17 to Axis 32) | p.144 | |
| SD513 | The manual pulse generator axis setting error is stored in b0 to b2 | p.144 | |
| SD514 | One pulse input magnification setting error is stored in b0 to b15 | p.144 | |
| SD515 | One pulse input magnification setting error is stored in b0 to b15 | p.144 | |
| M9255 | and special registers (D9000 to D9255) are automatically converted into new | p.146 | |
| ROM ERROR1 | • Type of the operating system software of data written to ROM is different. | p.148 | |
| ROM ERROR2 | • Data is not written to ROM. | p.148 | |
| 1000 | Runaway or failure of CPU module. (1) Malfunctioning due to noise or other reason (2) Hardware fault | (1) Take noise reduction measures. (2) Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module hardware fault. Explain the error symptom and get advice from our sales representative. | p.152 |
| 1105 | The CPU shared memory in the CPU module is faulty. | p.152 | |
| 1150 | The memory of the CPU module in the Multiple CPU high speed transmission area is faulty. | p.152 | |
| 1300 | There is an output module with a blown fuse. | Check FUSE. LED of the output modules and replace the module whose LED is lit. | p.152 |
| 1401 | There was no response from the Motion module/intelligent function module in the initial processing. | Set the Motion module/intelligent function module used in the Motion CPU in the system setting. This suggests a Motion module, intelligent function module, CPU module and/or base unit is expecting a hardware fault. Explain the error symptom and get advice from our sales representative. | p.152 |
| 1403 | (1) An error is detected at the intelligent function module. (2) The I/O module (including intelligent function module) is nearly removed or completely removed/mounted during running. | The CPU module, base unit and/or the intelligent function module that was accessed is experiencing a hardware fault. Explain the error symptom and get advice from our sales representative. | p.152 |
| 1413 | An error is detected on the system bus. | Reset the CPU module and RUN it again. If the same error is displayed again, the intelligent function module, CPU module or base unit is faulty. Explain the error symptom and get advice from our sales representative. | p.152 |
| 1415 | Fault of the main or extension base unit was detected. | p.152 | |
| 1416 | System bus fault was detected at power-on or reset. | p.152 | |
| 1430 | The error of self CPU is detected in the Multiple CPU high speed bus. | Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module hardware fault. Explain the error symptom and get advice from our sales representative. | p.154 |
| 1431 | The communication error with other CPU is detected in the Multiple CPU high speed bus. | (1) Take noise reduction measures. (2) Check the main base unit mounting status of the CPU module. (3) Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module or base unit hardware fault. Explain the error symptom and get advice from our sales representative. | p.154 |
| 1432 | The communication time out with other CPU is detected in the Multiple CPU high speed bus. | Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module hardware fault. Explain the error symptom and get advice from our sales representative. | p.154 |
| 1433 | The communication error with other CPU is detected in the Multiple CPU high speed bus. | (1) Take noise reduction measures. (2) Check the main base unit mounting status of the CPU module. (3) Reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module or base unit hardware fault. Explain the error symptom and get advice from our sales representative. | p.154 |
| 1500 | A momentary power supply interruption has occurred. The power supply went off. | Check the power supply. | p.154 |
| 1600 | (1) The battery voltage in the CPU module has dropped below stipulated level. (2) The battery holder unit that install the battery is not mounted to the CPU module. | (1) Change the battery. (2) Mount the battery holder unit that installs the battery. | p.154 |
| 2100 | In the I/O assignment setting of PLC CPU, the intelligent function module was allocated to an I/O module or vice versa. | Make the PLC parameter's I/O assignment setting again so it is consistent with the actual status of the intelligent function module and the CPU module. | p.154 |
| 2107 | The first I/O No. set in the system settings is overlapped with the one for another module. | Make the I/O No. setting again so it is consistent with the actual status of the modules. | p.154 |
| 2140 | The motion modules (Q172DLX, Q172DEX, Q173DPX, Q172LX, Q172EX (-S1/-S2/-S3), Q173PX (-S1)) are installed in CPU slot or I/O 0 to 2 slot. | Remove the Motion modules installed CPU slot or I/O 0 to 2 slot. | p.154 |
| 2150 | In a Multiple CPU system, the control CPU of intelligent function module incompatible with the Multiple CPU system is set to other than CPU No.1. | (1) Change to the intelligent function module (function version B or later) compatible with the Multiple CPU system. (2) Change the control CPU of intelligent function module incompatible with the Multiple CPU system to CPU No.1. | p.154 |
| 3001 | The parameter settings are corrupted. | (1) Check the parameter item corresponding the numerical value (parameter No.), and correct it. (2) Rewrite corrected parameters to the CPU module, reload or reset the Multiple CPU system power supply. (3) If the same error occurs, it is thought to be a hardware error. Explain the error symptom and get advice from our sales representative. | p.156 |
| 3012 | Multiple CPU setting of Multiple CPU setting parameter or control CPU setting of system setting differs from that of the reference CPU settings. | Match the Multiple CPU setting of Multiple CPU setting parameter or control CPU setting of system setting with that of the reference CPU (CPU No.1) settings. | p.156 |
| 3013 | Multiple CPU automatic refresh setting is any of the following. (1) When a bit device is specified as a refresh device, a number other than a multiple of 16 is specified for the refresh start device. (2) The device specified is other than the one that may be specified. (3) The number of send points is an odd number. (4) The total number of send points is greater than the maximum number of refresh points. | Check the following in the Multiple CPU automatic refresh setting and make correction. (1) When specifying the bit device, specify a multiple of 16 for the refresh start device. (2) Specify the device that may be specified for the refresh device. (3) Set the number of send points to an even number. (4) Set the total number of send points is within the range of the maximum number of refresh points. | p.156 |
| 3015 | (1) "Use multiple CPU high speed transmission " is not set in the Multiple CPU setting of Universal module QCPU. (2) In a Multiple CPU system, the CPU verified is different from the one set in the parameter setting. | (1) Set "Use multiple CPU high speed transmission " in the Universal module QCPU. (2) Check the parameter item corresponding to the numerical value (parameter No./CPU No.) and parameter of target CPU, and correct them. | p.156 |
| 7000 | In the operating mode of a Multiple CPU system, a CPU error occurred at the CPU where "All station stop by stop error of CPU" was selected. | Check the error of the CPU resulting in CPU module fault, and remove the errors. | p.156 |
| 7002 | There is no response from the target CPU module in a Multiple CPU system during initial communication. | Reset the CPU module and RUN it again. If the same error is displayed again, this suggests the hardware fault of any of the CPU modules. Explain the error symptom and get advice from our sales representative. | p.156 |
| 7010 | In a Multiple CPU system, a faulty CPU module was mounted. | Replace the faulty CPU module. | p.156 |
| 7011 | Either of the following settings was made in a Multiple CPU system. (1) Multiple CPU automatic refresh setting was made for the inapplicable CPU module. (2) "I/O sharing when using multiple CPUs" setting was made for the inapplicable CPU module. | (1) Correct the Multiple CPU automatic refresh setting. (2) Correct the "I/O sharing when using multiple CPUs" setting. | p.156 |
| 7013 | (1) CPU module which cannot be mounted in OnCPU(H)CPU is mounted. (The module may break down.) (2) Q173HCPU,Q172HCPU,Q173CPUN,Q172CPUN is mounted. | Remove Q173HCPU,Q172HCPU,Q173CPUN,Q172CPUN. | p.156 |
| 7020 | In the operating mode of a Multiple CPU system, an error occurred in the CPU where "system stop" was not selected. (The CPU module where no error occurred was used to detect an error.) | Check the error of the CPU resulting in CPU module fault, and remove the error. | p.156 |
| 7030 | An assignment error occurred in the CPU-mountable slot (CPU slot, I/O slot 0 to 2) in excess of the number of CPU slot (with in the range of CPU number setting parameter). | (1) Set the same value to the number of CPU modules specified in the Multiple CPU setting of the PLC parameter and the number of mounted CPU modules (including CPU (empty)). (2) Make the same as the state of the installation of CPU module set in the system setting. | p.156 |
| 7031 | An assignment error occurred in the CPU slot (within the range of the CPU number setting parameter). | p.156 | |
| 7035 | The CPU module has been mounted on the inapplicable slot. | Mount the CPU module on the applicable slot. | p.156 |
| 10003 | Minor/major errors had occurred. | Check the Motion error history of MT Developer and the minor/major error codes of minor/major error code of minor/major error code storage device, and remove the error cause. Refer to the error codes for error details of minor/major errors. | p.158 |
| 10004 | Minor/major errors had occurred in virtual servomotor axis. (SV22) | p.158 | |
| 10005 | Minor/major errors had occurred in synchronous encoder axis. (SV22) | p.158 | |
| 10006 | The servo errors had occurred in the servo amplifier connected to the Motion CPU. | Check the Motion error history of MT Developer and the servo error codes of servo error code storage device, and remove the error cause of servo amplifier. Refer to the servo error code for details of servo errors. | p.158 |
| 10007 | Servo program setting error occurred. | Check the Motion error history of MT Developer and the servo program setting error storage device (error program No., error item information), and remove the error cause. Refer to the servo program setting error codes for details of servo program setting errors. | p.158 |
| 10008 | Real mode/virtual mode switching error occurred. (SV22) | Check the Motion error history of MT Developer and the real mode/virtual mode switching error storage device, and remove the error cause. Refer to the real mode/virtual mode switching error codes for details of real mode/virtual mode switching errors. | p.158 |
| 10009 | Manual pulse generator axis setting error occurred. | Check the Motion error history of MT Developer and the manual pulse generator axis setting error storage device, and remove the error cause. Refer to the manual pulse generator axis setting error codes for details of manual pulse generator axis setting errors. | p.158 |
| 10010 | Test mode request error occurred. | Check the Motion error history of MT Developer and the test mode request error storage device, and remove the error cause. | p.158 |
| 10011 | WDT error occurred at Motion CPU. | Check the Motion error history of MT Developer and the Motion CPU WDT error factors, and remove the error cause. | p.158 |
| 10014 | System setting error occurred at Motion CPU. | Check the error message on error monitor screen of MT Developer, and remove the error cause. And then, turn on the power supply again or reset the Multiple CPU system. | p.158 |
| 10016 | Motion slot fault occurred at Motion CPU. | p.158 | |
| 10020 | Motion SFC error occurred at Motion SFC program. | Check the Motion error history of MT Developer, and remove the error cause. Refer to the Motion SFC error code for details of errors. | p.158 |
| 10030 | Motion CPU internal bus error occurred. | Motion CPU module hardware fault. Explain the error symptom and get advice from our sales representative. | p.158 |