Air-Conditioners PCA-A • KA4

INSTALLATION MANUAL For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil exté- rieur pour une utilisation sûre et correct. MANUAL DE INSTALACIÓN Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.

FOR INSTALLER

English

POUR L’INSTALLATEUR

Français

PARA EL INSTALADOR

Español

Page 3 of the Mitsubishi Electronics PCA-A.KA4 user manual — 3.2.3. Selection of suspension bolts and tubing positions (Fig. 3-3)
Page 3 · click to enlarge
Page 3

2. Installation location

2.1. Outline dimensions (Indoor unit) (Fig. 2-1) Select a proper position allowing the following clearances for installation and main- tenance. (inch)

Mitsubishi Electronics PCA-A.KA4 — 2. Installation location diagram (page 3)
Fig. 1 · 2. Installation location
ModelsW A24, 3050-3/8 A36, 4263

2.2. Outline dimensions (Outdoor unit) Refer to the outdoor unit installation manual.

3. Installing the indoor unit

Mitsubishi Electronics PCA-A.KA4 — 3. Installing the indoor unit diagram (page 3)
Fig. 2 · 3. Installing the indoor unit

3.1. Check the indoor unit accessories (Fig. 3-1) The indoor unit should be supplied with the following accessories (contained in the inside of the intake grille).

Accessory nameQ’ty Washer4 pcs Pipe cover1 pc Large size (For gas tubing) Pipe cover1 pc Small size (For liquid tubing) Band4 pcs Joint socket1 pc Marked with “UNIT” Socket cover1 pc Drain tubing cover1 pc
Mitsubishi Electronics PCA-A.KA4 — 3. Installing the indoor unit diagram (page 3)
Fig. 3 · 3. Installing the indoor unit
163-1/8 12-5/8 B 1/16

3.2. Preparation for installation (Fig. 3-2) 3.2.1. Suspension bolt installing spacing (inch)

A24,3048-11/1650-3/8 A36,4261-5/1663

3.2.2. Refrigerant and drain tubing location

Front side outlet Left drain tubing Left side outlet Gas tubing Right side outlet Liquid tubing Independent piece (Removable) Rubber plug Right drain tubing with Joint socket

In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position. (The heat exchanger might be clogged because of dust)

3.2.3. Selection of suspension bolts and tubing positions (Fig. 3-3)

Using the pattern paper provided for installation, select proper positions for suspen- sion bolts and tubing and prepare relative holes.

Pattern paper Suspension bolt hole Indoor unit width Secure the suspension bolts or use angle stock braces or square timbers for bolt installation.

Mitsubishi Electronics PCA-A.KA4 — 3.2.3. Selection of suspension bolts and tubing positions (Fig. 3-3) diagram (page 3)
Fig. 4 · 3.2.3. Selection of suspension bolts and tubing posi…

Use inserts of 220-230 lbs. each. Use suspension bolts of W 3/8 or M10 in size.

·

Page 4 of the Mitsubishi Electronics PCA-A.KA4 user manual —
Page 4 · click to enlarge
Page 4

3. Installing the indoor unit

Mitsubishi Electronics PCA-A.KA4 — 3. Installing the indoor unit diagram (page 4)
Fig. 5 · 3. Installing the indoor unit

3.2.4. Fresh air intake hole (Fig. 3-4) At the time of installation, use the duct holes (knock out) located at the positions shown in following diagram, as and when required. Indoor unit Fresh air intake hole (knock out hole) Filter in. (mm)

ABC 10-3/16 (259.5)ø 3-15/16 (ø 100)4-5/16 (109)

3.2.5. Indoor unit preparation (Fig. 3-5) 1. Install the suspending bolts. (Procure the W 3/8 or M10 bolts locally.) Predetermine the length from the ceiling ( within 3-15/16 in. (100 mm)). Ceiling surface Suspending bolt Suspending bracket 2. Remove the intake grille. Slide the intake grille holding knobs (at 2 or 3 locations) backward to open the intake grille. 3. Remove the side panel. Remove the side panel holding screws (1 in each side, right and left) then slide the side panel forward for removal.

Mitsubishi Electronics PCA-A.KA4 —  diagram (page 4)
Fig. 6

Intake grille Slide the side panel forward. Intake grille holding knob Side panel Slide Remove the side panel holding screws. Hinge Remove the protective vinyl of vane. Pushing the hinge, pull out the intake grille. Forcing open the intake grille or opening it to an angle of more than 120° may

damage the hinges.

3.3. Installing the indoor unit (Fig. 3-6) Use a proper suspending method depending on the presence or absence of ceiling materials as follows.

In the presence of ceiling materials 1 Ceiling In the absence of ceiling materials 2 Suspending bolt / Suspending bracket 3 Washer 0 Unit 4 Washer (Local procurement) 5 Double nuts

Mitsubishi Electronics PCA-A.KA4 —  diagram (page 4)
Fig. 7
1. Directly suspending the unit Installing procedures
  • 1. Install the washer (supplied with the unit) and the nuts (to be locally procured). 2. Set (hook) the unit through the suspending bolts. 3. Tighten the nuts. Check the unit installing condition.
  • Check that the unit is horizontal between the right and left sides.
  • Check that the front and the rear of suspending brackets are horizontal. (To keep drainage, the unit is inclined to the suspending brackets. The unit slopes continuously downward from the front to the rear is the right installation position.)

2) Installing the suspending bracket first onto the ceiling (Fig. 3-7) Installing procedures 1. Remove the suspending brackets and U-shaped washers from the unit. 2. Adjust the suspending bracket holding bolts on the unit. 3. Attach the suspending brackets to the suspending bolts. 4. Check that the suspending brackets are horizontal (front and rear/right and left). 5. Set (hook) the unit to the suspending brackets. 6. Tighten fixed bolts of the suspending brackets. + Be sure to install the U-shaped washers.

Mitsubishi Electronics PCA-A.KA4 —  diagram (page 4)
Fig. 8

Suspending bracket holding bolt Unit U-shaped washer Suspending bolt Washer Double nuts

A24,30 47 - 5/10 A36,42 59 - 7/8

Show 8 more labels / short text on this page
· · / · / 5 3 · (inch) · 25/64-25/32 · · (inch)
Page 5 of the Mitsubishi Electronics PCA-A.KA4 user manual —
Page 5 · click to enlarge
Page 5

4. Installing the refrigerant piping

Mitsubishi Electronics PCA-A.KA4 — 4. Installing the refrigerant piping diagram (page 5)
Fig. 9 · 4. Installing the refrigerant piping
  • 4.1. Precautions For devices that use R410A refrigerant
  • Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections.
  • Use C1220 copper phosphorus for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses specified in the table below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust.

Flare cutting dimensions in. (mm)

Copper pipe O.D.Flare dimensions øA dimensions 1/4” (ø6.35)11/32-23/64 (8.7 - 9.1) 3/8" (ø9.52)1/2-33/64 (12.8 - 13.2) 1/2" (ø12.7)41/64-21/32 (16.2 - 16.6) 5/8" (ø15.88)49/64-25/32 (19.3 - 19.7) 3/4" (ø19.05)29/32-59/64 (22.9 - 23.3)

in. (mm)

A24, 30, 36, 42 Liquid pipe3/8" (ø9.52) thickness 1/32" (0.8) Gas pipe5/8" (ø15.88) thickness 3/64" (1.0)
  • Do not use pipes thinner than those specified above.
  • 4.2. Connecting pipes (Fig. 4-1)
  • When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 212 °F (100 °C) or more, thickness of 1/2 in. (12 mm) or more).
  • The indoor parts of the drain pipe should be wrapped with polyethylene foam insulation materials (specific gravity of 0.03, thickness of 23/64 in. (9 mm) or more).
  • Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut.
  • Use 2 wrenches to tighten piping connections.
  • Use refrigerant piping insulation provided to insulate indoor unit connections. Insulate carefully.

Die Copper pipe

Flare nut tightening torque

Copper pipe O.D. (mm, inch)Flare nut O.D. (mm, inch)Tightening torque (N-m, ft.lbs) ø6.35, 1/417, 43/6414-18, 10-13 ø6.35, 1/422, 7/834-42, 25-30 ø9.52, 3/822, 7/834-42, 25-30 ø12.7, 1/226, 1-3/6449-61, 35-44 ø12.7, 1/229, 1-9/6468-82, 49-59 ø15.88, 5/829, 1-9/6468-82, 49-59 ø15.88, 5/836, 1-27/64100-120, 71-86 ø19.05, 3/436, 1-27/64100-120, 71-86
Mitsubishi Electronics PCA-A.KA4 — 4. Installing the refrigerant piping diagram (page 5)
Fig. 10 · 4. Installing the refrigerant piping

in. (mm)

Copper pipe O.D.B Flare tool for R410A Clutch type 1/4” (ø6.35)0-1/64 (0 - 0.5) 3/8" (ø9.52)0-1/64 (0 - 0.5) 1/2" (ø12.7)0-1/64 (0 - 0.5) 5/8" (ø15.88)0-1/64 (0 - 0.5) 3/4" (ø19.05)0-1/64 (0 - 0.5)

Apply refrigerating machine oil over the entire flare seat surface. Use correct flare nuts meeting the pipe size of the outdoor unit.

Mitsubishi Electronics PCA-A.KA4 — 4. Installing the refrigerant piping diagram (page 5)
Fig. 11 · 4. Installing the refrigerant piping

4.3. Indoor unit (Fig. 4-3) Installing procedures 1. Slide the supplied pipe cover over the gas tubing until it is pressed against the sheet metal inside the unit. 2. Slide the provided pipe cover over the liquid tubing until it is pressed against the sheet metal inside the unit. 3. Tighten the pipe covers and at the both ends 3/4 in. (20 mm) with the sup- plied bands .

Mitsubishi Electronics PCA-A.KA4 — 4. Installing the refrigerant piping diagram (page 5)
Fig. 12 · 4. Installing the refrigerant piping

Gas tubing Pipe cover Liquid tubing Press the pipe cover against the sheet metal. Band Refrigerant tubing heat insulating material Pipe cover

4.4. For twin combination Refer to the outdoor unit installation manual.

·

Page 6 of the Mitsubishi Electronics PCA-A.KA4 user manual — CN105
Page 6 · click to enlarge
Page 6

5. Drainage piping work

  • For left side tubing, be sure to insert the rubber plug into the right drain port. (Fig. 5-1)
  • Use VP-20 (O.D. ø26 (1”) PVC TUBE) for drain piping and provide 1/100 or more downward slope.
  • After completion of work, check that correct drain is available from the outfl ow port of the drain tubing.

Drain pan Plug Insert the driver etc.in the plug deeply.

Mitsubishi Electronics PCA-A.KA4 — 5. Drainage piping work diagram (page 6)
Fig. 13 · 5. Drainage piping work

Installing procedures (Fig. 5-2) 1. Attach the joint socket supplied with the unit to the drain port on the unit with a vinyl chloride adhesive. 2. Fasten the socket cover supplied with the unit to the joint socket . 3. Attach the fi eld drain tubing (VP-20) to the joint socket with a vinyl chloride adhesive. 4. Wrap the drain tubing cover supplied with the unit. (Seam taping)

Drain pan Drain tubing Socket cover Joint socket Drain tubing cover Insertion length 1-15/32 in. (37mm)

Mitsubishi Electronics PCA-A.KA4 — 5. Drainage piping work diagram (page 6)
Fig. 14 · 5. Drainage piping work
5. Check for correct drainage. (Fig. 5-3) * Fill the drain pan with water of about 1/4 gal (1 L) from the air outlet.
Mitsubishi Electronics PCA-A.KA4 — 5. Drainage piping work diagram (page 6)
Fig. 15 · 5. Drainage piping work

6.1. Electric wiring Wiring procedures 1. Remove the tapping screw then remove the beam. 2. Remove the (2) tapping screws then remove the electric part cover . 3. For radio frequency interface. Connect the electric cord of radio frequency interface securely to CN105 (RED) on indoor controller board. For wired remote controller Connect the electric wires securely to the corresponding terminals (Fig. 6-1) 4. Replace the removed parts. 5. Tie the electric wires with the local wiring clamp located in the right side of the junction box.

Mitsubishi Electronics PCA-A.KA4 —     diagram (page 6)
Fig. 16
Mitsubishi Electronics PCA-A.KA4 —     diagram (page 6)
Fig. 17

Cover Grounding cable connector Set screws (2 pcs) Terminal block for wired remote controller Set screws (Beam) 7 Secure with the wiring clamp. Wiring clamp Indoor controller board Wire service entrance Terminal block for indoor and outdoor units connection

Mitsubishi Electronics PCA-A.KA4 —  diagram (page 6)
Fig. 18

CN105

(RED)

Show 6 more labels / short text on this page
· · · · ·
Page 7 of the Mitsubishi Electronics PCA-A.KA4 user manual — CN105 (RED)
Page 7 · click to enlarge
Page 7

6.1.1. Indoor unit power supplied from outdoor unit The following connection patterns are available. The outdoor unit power supply patterns vary on models.1 System

1:1 System

Outdoor unit power supply Wiring circuit breaker or isolating switch Outdoor unit Indoor unit/outdoor unit connecting cords Wired remote controller Indoor unit Indoor unit earth Indoor controller board Radio frequency interface for RF thermostat * Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.

CN105 (RED)

GR

S1

S1

S2

S2

S3 S3

Mitsubishi Electronics PCA-A.KA4 — CN105 (RED) diagram (page 7)
Fig. 19
Indoor unit modelPCA-A24,30PCA-A36, 42 Minimum circuit ampacity1A2A Maximum rating of overcurrent protective device15A Wiring Wire No. × sizeIndoor unit-Outdoor unit *13 × AWG16 (polar) Indoor unit earth1 × Min. AWG16 Wired remote controller-Indoor unit *22 × AWG22 (Non-polar, unshielded) Circuit ratingIndoor unit-Outdoor unit S1-S2 *3AC 208/230 V Indoor unit-Outdoor unit S2-S3 *3DC24 V Wired remote controller-Indoor unit *3DC12 V

*1. Max. 50 m, 165 ft *2. The 10 m, 30 ft wire is attached in the wired remote controller accessory. Max. 500 m, 1500 ft *3. The figures are NOT always against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.

6.2. Remote controller 6.2.1. For wired remote controller 1) 2 wired remote controllers setting If 2 wired remote controllers are connected, set one to “Main” and the other to “Sub”. For setting procedures, refer to “Function selection of remote controller” in the operation manual for the indoor unit.

Show 7 more labels / short text on this page
· · · · · ·
Page 8 of the Mitsubishi Electronics PCA-A.KA4 user manual — RESET SET CLOCK
Page 8 · click to enlarge
Page 8
  • 6.2.2. For IR wireless remote controller 1) Installation area
  • Area in which the IR wireless remote controller is not exposed to direct sunshine.
  • Area in which there is no nearby heating source.
  • Area in which the IR wireless remote controller is not exposed to cold (or hot) winds.
  • Area in which the IR wireless remote controller can be operated easily.
  • Area in which the IR wireless remote controller is beyond the reach of children.

MODEL SELECT

ON/OFF TEMP

2. Setting (Fig. 6-3) Insert batteries. Press the SET button with something sharp at the end. MODEL SELECT blinks and Model No. is lighted. Press the temp buttons to set the Model No. If you mistook the operation, press the ON/OFF button and operate again from procedure . Press the SET button with something sharp at the end. MODEL SELECT and Model No. are lighted for 3 seconds, then turned off.

FAN

AUTO STOP

MODE

VANE

AUTO START

CHECK

LOUVER

RESET SET CLOCK

Indoor Outdoor Model No.

PCAPUZ001 PUY033
3. Assigning a IR wireless remote controller to each unit Each unit can be operated only by the assigned IR wireless remote controller. Make sure each pair of an indoor unit PC board and a IR wireless remote controller is assigned to the same pair No.
4. IR wireless remote controller pair number setting operation (Fig. 6-4) Press the SET button with something sharp at the end. Start this operation from the status of IR wireless remote controller display turned off.

MODEL SELECT

MODEL SELECT blinks and Model No. is lighted.

ON/OFF TEMP

min button twice continuously. Pair No. “0” blinks.

Press the temp buttons to set the pair number you want to set. If you mistook the operation, press the ON/OFF button and operate again from procedure . Press the SET button with something sharp at the end. Set pair number is lighted for 3 seconds then turned off.

FAN

AUTO STOP

MODE

VANE

AUTO START

CHECK

LOUVER

Pair No. of IR wireless remote controllerIndoor PC board 0Initial setting 1Cut J41 2Cut J42 3-9Cut J41, J42

RESET SET CLOCK

Mitsubishi Electronics PCA-A.KA4 — RESET SET CLOCK diagram (page 8)
Fig. 20

6.3. Function settings 6.3.1 Function setting on the unit (Selecting the unit functions)

1. For wired remote controller (Fig. 6-5) Changing the power voltage setting • Be sure to change the power voltage setting depending on the voltage used. Go to the function setting mode.

Switch OFF the wired remote controller. Press the and buttons simultaneously and hold them for at least 2 seconds. FUNCTION will start to flash. Use the button to set the refrigerant address ( ) to 00. Press and [--] will start to flash in the unit number () display. Use the button to set the unit number () to 00. Press the MODE button to designate the refrigerant address/unit number. [--]

will flash in the mode number ( ) display momentarily. Press the buttons to set the mode number ( ) to 04. Press the button and the current set setting number ( ) will flash. Use the button to switch the setting number in response to the power supply voltage to be used. Power supply voltage 230 V : setting number = 1 208 V : setting number = 2 Press the MODE button and mode and the setting number ( ) and ( ) will

change to being on constantly and the contents of the setting can be confirmed. Press the FILTER and TEST RUN buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air conditioner OFF display will appear.

Show 5 more labels / short text on this page
· h · · Press the · h
Page 9 of the Mitsubishi Electronics PCA-A.KA4 user manual — MODEL SELECT
Page 9 · click to enlarge
Page 9
Mitsubishi Electronics PCA-A.KA4 — MODEL SELECT diagram (page 9)
Fig. 21
2. For IR wireless remote controller (Fig. 6-6) Changing the power voltage setting • Be sure to change the power voltage setting depending on the voltage used. Go to the function select mode

Press the CHECK button twice continuously. (Start this operation from the status of IR wireless remote controller display turned off.)

CHECK is lighted and “00” blinks. Press the temp button once to set “50”. Direct the IR wireless remote

controller toward the receiver of the indoor unit and press the h button . Setting the unit number

Press the temp button and to set the unit number “00”. Direct the IR wireless remote controller toward the receiver of the indoor unit and press the

min button . Selecting a mode

Enter 04 to change the power voltage setting using the and buttons. Direct the IR wireless remote controller toward the receiver of the indoor unit

and press the h button . Current setting number: 1 = 1 beep (one second) 2 = 2 beeps (one second each) 3 = 3 beeps (one second each) Selecting the setting number

Use the and buttons to change the power voltage setting to 01 (230 V). Direct the IR wireless remote controller toward the sensor of the indoor unit and press the h button . To select multiple functions continuously

Repeat steps and to change multiple function settings continuously. Complete function selection

Direct the IR wireless remote controller toward the sensor of the indoor unit and press the button .

or maintenance, be sure to record the changes with a mark in the “Setting” column of the Function table.

6.3.2 Function setting on the remote controller For details on how to operate the remote controller, refer to the appropriate opera- tion manual included with each remote controller.

Function table Select unit number 00

ModeSettingsMode no.Setting no.Initial settingsetting Wired remote controller (RF thermostat) Power failure automatic recoveryNot available01 (101)1 Available +2Ο Indoor temperature detectingIndoor unit operating average02 (—)1Ο Set by indoor unit’s remote controller2 Wired remote controller’s internal sensor3 LOSSNAY connectivityNot Supported03 (103)1Ο Supported (indoor unit is not equipped with outdoor-air intake)2 Supported (indoor unit is equipped with outdoor-air intake)3 Power voltage230 V04 (104)1 208 V2Ο
Mitsubishi Electronics PCA-A.KA4 — MODEL SELECT diagram (page 9)
Fig. 22

Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])

ModeSettingsMode no.Setting no.Initial settingsetting Wired remote controller (RF thermostat) Filter sign100Hr07 (107)1 2500Hr2Ο No filter sign indicator3 Fan speedSilent08 (108)1 Standard2Ο High ceiling3 Up/down vane settingNo vanes11 (111)1 Equipped with vanes (vanes angle setup )2Ο Equipped with vanes (vanes angle setup )3
Mitsubishi Electronics PCA-A.KA4 — MODEL SELECT diagram (page 9)
Fig. 23

+ When the power supply returns, the air conditioner will start 3 minutes later.

Page 10 of the Mitsubishi Electronics PCA-A.KA4 user manual — 7.3. Self-check
Page 10 · click to enlarge
Page 10

7.1. Before test run ► After completing installation and the wiring and piping of the indoor and

► Do not carry out this test on the control wiring (low voltage circuit) termi-

outdoor units, check for refrigerant leakage, looseness in the power sup- ply or control wiring, wrong polarity, and no disconnection of one phase in the supply. ► Use a 500-volt megohmmeter to check that the resistance between the

nals. Warning: Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.

power supply terminals and ground is at least 1.0 MΩ.

Refer to the installation manual that comes with each remote controller for details.

7.3. Self-check

Refer to the installation manual that comes with each remote controller for details. RF thermostat is not established.

  • Refer to the following tables for details on the check codes. (IR wireless remote controller) [Output pattern A]

Beep

OPERATION INDICATOR lamp blinking pattern

th 1 st 2 nd 3 rd 1 st 2 nd

· · · Repeated

Off Approx. 2.5 sec.

On 0.5 sec. On 0.5 sec. On 0.5 sec. On 0.5 sec. Off Approx. 2.5 sec.

On 0.5 sec. On 0.5 sec.

Self-check starts (Start signal received)

Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)

Number of blinks/beeps in pattern indicates the check code in the following table

Beep

th 1 st 2 nd 3 rd 1 st 2 nd

OPERATION INDICATOR lamp blinking pattern

· · · Repeated

Off Approx. 2.5 sec.

On Approx. 3 sec.

On 0.5 sec. On 0.5 sec. On 0.5 sec. On 0.5 sec. Off Approx. 2.5 sec.

On Approx. 3 sec.

On 0.5 sec. On 0.5 sec.

Self-check starts (Start signal received)

Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)

Number of blinks/beeps in pattern indicates the check code in the following table

[Output pattern A] Errors detected by indoor unit

Mitsubishi Electronics PCA-A.KA4 — 7.3. Self-check diagram (page 10)
Fig. 24 · 7.3. Self-check
IR wireless remote controllerWired remote controller RF thermostatSymptomRemark Beeper sounds/OPERATION INDICATOR lamp blinks (Number of times)Check code 1P1Intake sensor error 2P2Pipe (TH2) sensor error P9Pipe (TH5) sensor error 3E6, E7Indoor/outdoor unit communication error 4P4Drain sensor error / Float switch connector open 5P5Drain pump error PAForced compressor error 6P6Freezing/Overheating protection operation 7EECommunication error between indoor and outdoor units 8P8Pipe temperature error 9E4Remote controller signal receiving error 10—— 11—— 12FbIndoor unit control system error (memory error, etc.) No soundE0, E3Remote controller transmission error No soundE1, E2Remote controller control board error No sound–No corresponding
Show 5 more labels / short text on this page
Beeper sounds · n · [Output pattern B] · Beeper sounds · n
Page 11 of the Mitsubishi Electronics PCA-A.KA4 user manual — 7.3. Self-check
Page 11 · click to enlarge
Page 11

[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)

IR wireless remote controllerWired remote controller RF thermostatSymptomRemark Beeper sounds/OPERATION INDICATOR lamp blinks (Number of times)Check code 1E9Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)For details, check the LED display of the outdoor controller board. 2UPCompressor overcurrent interruption 3U3, U4Open/short of outdoor unit thermistors 4UFCompressor overcurrent interruption (When compressor locked) 5U2Abnormal high discharging temperature/49C worked/insufficient refrigerant 6U1, UdAbnormal high pressure (63H worked)/Overheating protection operation 7U5Abnormal temperature of heat sink 8U8Outdoor unit fan protection stop 9U6Compressor overcurrent interruption/Abnormal of power module 10U7Abnormality of super heat due to low discharge temperature 11U9, UHAbnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error 12—— 13—— 14OthersOther errors (Refer to the technical manual for the outdoor unit.)
Mitsubishi Electronics PCA-A.KA4 — 7.3. Self-check diagram (page 11)
Fig. 25 · 7.3. Self-check
  • *1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on, there are no error records. *2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
  • On IR wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
  • On wired remote controller Check code displayed in the LCD.
  • If the unit cannot be operated properly after test run, refer to the following table to find the cause.
SymptomCause Wired remote controllerLED 1, 2 (PCB in outdoor unit PLEASE WAITFor about 2 minutes after power-onAfter LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)•For about 2 minutes after power-on, operation of the remote controller is not possible due to system start-up. (Correct operation) PLEASE WAIT → Error codeSubsequent to about 2 minutes after power-onOnly LED 1 is lighted. → LED 1, 2 blink.•Connector for the outdoor unit’s protection device is not connected. Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR) Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).Only LED 1 is lighted. → LED 1 blinks twice, LED 2 blinks once.•Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3) •Remote controller wire short
  • On the IR wireless remote controller with condition above, following phenomena take place.
  • No signals from the remote controller are accepted.
  • Operation lamp is blinking.
  • The buzzer makes a short ping sound. Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

LED 1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is always lit. LED 2 (power for remote controller)Indicates whether power is supplied to the remote controller. This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address “0”. LED 3 (communication between indoor and outdoor units)Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.
Mitsubishi Electronics PCA-A.KA4 — 7.3. Self-check diagram (page 11)
Fig. 26 · 7.3. Self-check
Page 12 of the Mitsubishi Electronics PCA-A.KA4 user manual — D
Page 12 · click to enlarge
Page 12

8. Easy maintenance function (For wired remote controller only)

Display example (Comp discharge temperature 147˚F)

By using the maintenance mode, you can display many types of maintenance data on the wired remote controller such as the heat exchanger temperature and com- pressor current consumption for the indoor and outdoor units. This function can be used whether the air conditioner is operating or not. During air conditioner operation, data can be checked during either normal opera- tion or maintenance mode stable operation. * This function cannot be used during the test run. * The availability of this function depends on the connecting outdoor unit. Refer to the brochures.

D

PAR-21MAA

Maintenance mode operation procedures

(1) Press the TEST button for 3 seconds to activate the maintenance mode.

MAINTENANCE

(2) Press the TEMP. buttons to set the refrigerant address.

(3) Select the data you want to display.

MENU

COMP ON x10 HOURS

COMP ON x100 TIMES

COMP ON CURRENT (A)

OUTDOOR UNIT H•EXC. TEMP

OUTDOOR UNIT OUTLET TEMP

OUTDOOR UNIT OUTDOOR TEMP

ON/OFF

Stable operation Using the maintenance mode, the operation frequency can be fixed and the op- eration can be stabilized. If the air conditioner is stopped, use the following pro- cedure to start this operation.

INDOOR UNIT INLET TEMP

INDOOR UNIT H•EXC. TEMP

INDOOR UNIT FILTER USE H

* The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed.

Press the MODE button to select the operation mode.

(4) Press the FILTER button.

COOL STABLE MODE

HEAT STABLE MODE

STABLE MODE CANCEL

(5) The data is displayed in . (Airflow temperature display example)

Press the FILTER button.

Approx.

10 sec. 147˚F

Waiting for stable operation

* Repeat steps (2) to (5) to check another data.

D

(6) Press the TEST button for 3 seconds or press the ON/OFF button to deactivate the maintenance mode.

* You can check the data using steps (3) to (5) of the maintenance mode opera- tion procedures while waiting for the stable operation.

Show 26 more labels / short text on this page
Display · Display · Compressor information · Cumulative operation time · ON/OFF number · Operation current · Display · Heat exchanger temperature · Comp discharge temperature · Outdoor ambient temperature · Outdoor unit information · Display · Indoor room temperature · Heat exchanger temperature · Filter operation time · Indoor unit information · Display · Stable cooling operation · Stable heating operation · Stable operation cancellation · Display · Blinking · Display · Waiting for response · Stable operation · Display
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Wired remote controller p.11
PLEASE WAIT•For about 2 minutes after power-on, operation of the remote controller is not possible due to system start-up. (Correct operation) p.11
PLEASE WAIT → Error code•Connector for the outdoor unit’s protection device is not con- nected. Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR) p.11
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).•Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3) •Remote controller wire short p.11

Ask about the Mitsubishi Electronics PCA-A.KA4

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics PCA-A.KA4

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics PCA-A.KA4 manual PDF

36 pages·1.2 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…