Before installing the unit, thoroughly read the following safety precautions. Observe these safety precautions for your safety.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or death.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or damage to the unit.
After reading this manual, give it to the user to retain for future reference. Keep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these
services. When the user changes, make sure that the new user receives this manual.
Ask your dealer or a qualified technician to install the unit.
In the event of a refrigerant leak, thoroughly ventilate the room.
Improper installation by the user may result in water leak- age, electric shock, smoke, and/or fire.
If refrigerant gas leaks and comes in contact with an open flame, poisonous gases will be produced.
Properly install the unit on a surface that can with- stand the weight of the unit.
When installing the All-Fresh type units, take it into consideration that the outside air may be discharged directly into the room when the thermo is turned off.
Unit installed on an unstable surface may fall and cause in- jury.
Direct exposure to outdoor air may have an adverse effect on health. It may also result in food spoilage.
Only use specified cables. Securely connect each ca- ble so that the terminals do not carry the weight of the cable.
Properly install the unit according to the instructions in the installation manual.
Improperly connected or fixed cables may produce heat and start a fire.
Improper installation may result in water leakage, electric shock, smoke, and/or fire.
Take appropriate safety measures against strong winds and earthquakes to prevent the unit from falling.
Have all electrical work performed by an authorized electrician according to the local regulations and in- structions in this manual, and a dedicated circuit must be used.
If the unit is not installed properly, the unit may fall and cause serious injury to the person or damage to the unit.
Insufficient capacity of the power supply circuit or improper installation may result in malfunctions of the unit, electric shock, smoke, and/or fire.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, smoke, and/or fire.
Do not touch the heat exchanger fins.
The fins are sharp and dangerous.

Securely attach the terminal block cover (panel) to the unit.
After completing the service work, check for a gas leak.
If the terminal block cover (panel) is not installed properly, dust and/or water may infiltrate and pose a risk of electric shock, smoke, and/or fire.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, poisonous gases may be produced.
Only use the type of refrigerant that is indicated on the unit when installing or reinstalling the unit.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features of these devices, or the use of accessories other than the ones that are recom- mended by MITSUBISHI may result in smoke, fire, and/or explosion.
Infiltration of any other type of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small room, exercise cau- tion and take measures against leaked refrigerant reaching the limiting concentration.
Only use accessories recommended by MITSUBISHI.
Ask a qualified technician to install the unit. Improper instal- lation by the user may result in water leakage, electric shock, smoke, and/or fire.
Consult your dealer with any questions regarding limiting concentrations and for precautionary measures before in- stalling the unit. Leaked refrigerant gas exceeding the lim- iting concentration causes oxygen deficiency.
Control box houses high-voltage parts.
Consult your dealer or a specialist when moving or re- installing the unit.
When opening or closing the front panel of the control box, do not let it come into contact with any of the internal com- ponents. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
Improper installation may result in water leakage, electric shock, and/or fire.

Do not use the existing refrigerant piping.
Use a vacuum pump with a reverse-flow check valve.
A large amount of chlorine that is contained in the residual
If a vacuum pump that is not equipped with a reverse-flow check valve is used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerating machine oil to deteriorate.
refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate. R410A is a high-pressure refrigerant and can cause the
existing pipes to burst.
Prepare tools for exclusive use with R410A. Do not use the following tools if they have been used with the con- ventional refrigerant (gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.).
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
If the refrigerant or the refrigerating machine oil left on
these tools are mixed in with R410A, it may cause the re- frigerating machine oil to deteriorate. Infiltration of water may cause the refrigerating machine
Store the pipes to be installed indoors, and keep both ends of the pipes sealed until immediately before braz- ing. (Keep elbows and other joints wrapped in plastic.)
oil to deteriorate. Gas leak detectors for conventional refrigerants will not
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate or cause the unit to malfunction.
detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
Use a small amount of ester oil, ether oil, or alkylben- zene to coat flares and flanges.
If a charging cylinder is used, the composition of the refrig- erant will change, and the unit may experience power loss.
Infiltration of a large amount of mineral oil may cause the re- frigerating machine oil to deteriorate.
Exercise special care when handling the tools for use with R410A.
Charge liquid refrigerant (as opposed to gaseous re- frigerant) into the system.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate.
If gaseous refrigerant is charged into the system, the com- position of the refrigerant in the cylinder will change and may result in performance loss.
Only use refrigerant R410A.
The use of other types of refrigerant that contain chlorine (i.e. R22) may cause the refrigerating machine oil to deteri- orate.

Do not install the unit where a gas leak may occur.
When installing the unit in a hospital, take appropriate measures to reduce noise interference.
If gaseous refrigerant leaks and piles up around the unit, it may be ignited.
High-frequency medical equipment may interfere with the normal operation of the air conditioner or vice versa.
Do not use the unit to keep food items, animals, plants, artifacts, or for other special purposes.
Do not install the unit on or over things that cannot get wet.
The unit is not designed to preserve food products.
When the humidity level exceeds 80% or if the drainage system is clogged, the indoor unit may drip water. Drain wa- ter is also discharged from the outdoor unit. Install a central- ized drainage system if necessary.
Do not use the unit in an unusual environment.
Do not install the unit where a large amount of oil or steam
is present or where acidic or alkaline solutions or chemical sprays are used frequently. Doing so may lead to a re- markable drop in performance, electric shock, malfunc- tions, smoke, and/or fire. The presence of organic solvents or corrosive gas (i.e.
ammonia, sulfur compounds, and acid) may cause gas leakage or water leakage.

Before installing the unit (moving and reinstalling the unit) and performing electrical work
Properly ground the unit.
Periodically check the installation base for damage.
Do not connect the grounding wire to a gas pipe, water pipe, lightning rod, or grounding wire from a telephone pole. Im- proper grounding may result in electric shock, smoke, fire, and/or malfunction due to noise interference.
If the unit is left on a damaged platform, it may fall and cause injury.
Properly install the drain pipes according to the in- structions in the installation manual. Keep them insu- lated to avoid dew condensation.
Do not put tension on the power supply wires.
If tension is put on the wires, they may break and result in excessive heat, smoke, and/or fire.
Improper plumbing work may result in water leakage and damage to the furnishings.
Install an earth leakage breaker to avoid the risk of electric shock.
Exercise caution when transporting products.
Products weighing more than 20 kg should not be carried
Failure to install an earth leakage breaker may result in electric shock, smoke, and/or fire.
alone. Do not carry the product by the PP bands that are used on
some products. Do not touch the heat exchanger fins. They are sharp and
Use the kind of power supply wires that are specified in the installation manual.
The use of wrong kind of power supply wires may result in current leak, electric shock, and/or fire.
to prevent the unit from falling.
Properly dispose of the packing materials.
Use breakers and fuses (current breaker, remote switch <switch + Type-B fuse>, moulded case circuit breaker) with the proper current capacity.
Nails and wood pieces in the package may pose a risk of
injury. Plastic bags may pose a risk of choking hazard to chil-
The use of wrong capacity fuses, steel wires, or copper wires may result in malfunctions, smoke, and/or fire.
dren. Tear plastic bags into pieces before disposing of them.
Do not spray water on the air conditioner or immerse the air conditioner in water.
Otherwise, electric shock and/or fire may result.
When handling units, always wear protective gloves to protect your hands from metal parts and high-tempera- ture parts.

Turn on the unit at least 12 hours before the test run.
Do not operate the unit without panels and safety guards.
Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc- tions.
Rotating, high-temperature, or high-voltage parts on the unit pose a risk of burns and/or electric shock.
To avoid the risk of electric shock or malfunction of the unit, do not operate switches with wet hands.
Do not turn off the power immediately after stopping the operation.
Keep the unit on for at least five minutes before turning off the power to prevent water leakage or malfunction.
Do not touch the refrigerant pipes with bare hands dur- ing and immediately after operation.
During or immediately after operation, certain parts of the unit such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frost bites and burns, do not touch these parts with bare hands.
Do not operate the unit without the air filter.
Dust particles may build up in the system and cause mal- functions.





[1] Read Before Servicing 3 [2] Necessary Tools and Materials 4 [3] Piping Materials 5 [4] Storage of Piping 7 [5] Pipe Processing 7 [6] Brazing 8 [7] Air Tightness Test 9 [8] Vacuum Drying (Evacuation) 10 [9] Refrigerant Charging 12 [10] Remedies to be taken in case of a Refrigerant Leak 12 [11] Characteristics of the Conventional and the New Refrigerants 13 [12] Notes on Refrigerating Machine Oil 14


![Page 12 of the Mitsubishi Electronics P96 user manual — I Read Before Servicing [1] Read Before Servicing](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-12.webp?w=400)
[ I Read Before Servicing ]
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water. These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.

[ I Read Before Servicing ]
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
Gauge Manifold Evacuation and refrigerant charging Higher than 5.09MPa[738psi] on the high-pressure side
Charging Hose Evacuation and refrigerant charging The hose diameter is larger than the conventional model.
Refrigerant Recovery Cylinder Refrigerant recovery
Refrigerant Cylinder Refrigerant charging The refrigerant type is indicated. The cylinder is pink.
Charging Port on the Refrigerant Cylinder Refrigerant charging The charge port diameter is larger than that of the current port.
Flare Nut Connection of the unit with the pipes Use Type-2 Flare nuts.
Gas Leak Detector Gas leak detection The ones for use with HFC refrigerant may be used.
Vacuum Pump Vacuum drying May be used if a check valve adapter is attached.
Flare Tool Flare processing Flare processing dimensions for the piping in the system using the new re- frigerant differ from those of R22. Re- fer to I [3] Piping Materials.
Refrigerant Recovery Equipment Refrigerant recovery May be used if compatible with R410A.
Vacuum Pump with a Check Valve Vacuum drying
Torque Wrench Tightening flare nuts Only the flare processing dimensions for pipes that have a diameter of ø12.70 (1/2") and ø15.88 (5/8") have been changed.
Pipe Cutter Cutting pipes
Welder and Nitrogen Cylinder Welding pipes
Refrigerant Charging Meter Refrigerant charging
Vacuum Gauge Vacuum level check
Charging Cylinder Refrigerant charging Prohibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.

[ I Read Before Servicing ]
Do not use the existing piping!
O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed) at the same radial thickness.
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
Maximum working pressure Refrigerant type
3.45 MPa [500psi] R22, R407C etc.
4.30 MPa [624psi] R410A etc.
Pipe size (mm[in.]) Radial thickness (mm [mil]) Type
ø6.35 [1/4"] 0.8t [32t]
O-material (Annealed) ø9.52 [3/8"] 0.8t [32t]
ø12.7 [1/2"] 0.8t [32t]
ø15.88 [5/8"] 1.0t [40t]
ø19.05 [3/4"] 1.0t [40t]
ø22.2 [7/8"] 1.0t [40t]
ø25.4 [1"] 1.0t [40t]
ø28.58 [1-1/8"] 1.0t [40t]
ø31.75 [1-1/4"] 1.1t [44t]
ø34.93 [1-3/8"] 1.2t [48t]
ø41.28 [1-5/8"] 1.4t [56t]
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn) unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t. The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
1/2H-material, H-material (Drawn)
![Page 15 of the Mitsubishi Electronics P96 user manual — ø12.7 [1/2"] 26.0 24.0](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-15.webp?w=400)
[ I Read Before Servicing ]
Flare processing dimensions (mm[in.])
Pipe size (mm[in.])
ø6.35 [1/4"] 9.1 9.0
ø9.52 [3/8"] 13.2 13.0
ø12.7 [1/2"] 16.6 16.2
ø15.88 [5/8"] 19.7 19.4
ø19.05 [3/4"] 24.0 23.3
(ø19.05 pipes should have a radial thickness of 1.2 t and be made of annealed materials.) If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0 and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
Flare nut dimensions (mm[in.])
Pipe size (mm[in.])
ø6.35 [1/4"] 17.0 17.0
ø9.52 [3/8"] 22.0 22.0
ø15.88 [5/8"] 29.0 27.0
ø19.05 [3/4"] 36.0 36.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.
![Page 16 of the Mitsubishi Electronics P96 user manual — [5] Pipe Processing](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-16.webp?w=400)
[ I Read Before Servicing ]





Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.





Both ends of the pipes should be sealed until just before brazing. Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to deteriorate and cause a compressor failure.
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil. Use only ester oil, ether oil, and alkylbenzene.
![Page 17 of the Mitsubishi Electronics P96 user manual — [6] Brazing](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-17.webp?w=400)
[ I Read Before Servicing ]
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system.
Use of oxidized solder for brazing Use of non-oxidized solder for brazing
![Mitsubishi Electronics P96 — [6] Brazing diagram (page 17)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/rimg-11.webp)
![Mitsubishi Electronics P96 — [6] Brazing diagram (page 17)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/rimg-12.webp)
copper coupling. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
water infiltrates into the system. Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
![Page 18 of the Mitsubishi Electronics P96 user manual — [7] Air Tightness Test](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-18.webp?w=400)
[ I Read Before Servicing ]
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
ness, taking temperature variations into account. Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
![Page 19 of the Mitsubishi Electronics P96 user manual — [8] Vacuum Drying (Evacuation)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-19.webp?w=400)
[ I Read Before Servicing ]
![Mitsubishi Electronics P96 — [8] Vacuum Drying (Evacuation) diagram (page 19)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/rimg-13.webp)
![Mitsubishi Electronics P96 — [8] Vacuum Drying (Evacuation) diagram (page 19)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/rimg-14.webp)
(Photo1) 15010H (Photo2) 14010
moves moisture in the pipes.) Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable. If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
etrated the system or that there is a leak. If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm2G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac- uum below 5Torr(650Pa) is attained or until the pressure stops rising. Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
![Page 20 of the Mitsubishi Electronics P96 user manual — [8] Vacuum Drying (Evacuation)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-20.webp?w=400)
[ I Read Before Servicing ]
Applying a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) is not enough to attain the desired vacuum pressure. Be sure to apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2). To evacuate air only from the outdoor units
Apply a vacuum through the check joints on the high and low pressure sides (CJ1, and 2). To evacuate air from the indoor units and extension pipes
Apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2).
![Page 21 of the Mitsubishi Electronics P96 user manual — [10] Remedies to be taken in case of a Refrigerant Leak](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-21.webp?w=400)
[ I Read Before Servicing ]
Cylinder with a siphon
Cylinder without a siphon
![Mitsubishi Electronics P96 — [9] Refrigerant Charging diagram (page 21)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/rimg-15.webp)
![Mitsubishi Electronics P96 — [9] Refrigerant Charging diagram (page 21)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/rimg-16.webp)
Cylinder color R410A is pink. Refrigerant charging in the liquid state
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the liquid state.) Refer to "IX [5] Refrigerant Leak".(page 314)

[ I Read Before Servicing ]
New Refrigerant (HFC type) Conventional Refriger-
Composition (wt%) (50/50) (23/25/52) (100)
Type of Refrigerant Pseudo-azeotropic
Chloride Not included Not included Included
Safety Class A1/A1 A1/A1 A1
Molecular Weight 72.6 86.2 86.5
Boiling Point (°C/°F) -51.4/-60.5 -43.6/-46.4 -40.8/-41.4
Steam Pressure (25°C,MPa/77°F,psi) (gauge)
1.557/226 0.9177/133 0.94/136
Saturated Steam Density (25°C,kg/m3/77°F,psi)
64.0 42.5 44.4
Flammability Nonflammable Nonflammable Nonflammable
Global Warming Coefficient (GWP)*2 1730 1530 1700
Refrigerant Charging Method Refrigerant charging in
Replenishment of Refrigerant after a Refrigerant Leak
*1 When CFC11 is used as a reference *2 When CO2 is used as a reference
-20/-4 0.30/44 0.18/26 0.14/20
0/32 0.70/102 0.47/68 0.40/58
20/68 1.34/194 0.94/136 0.81/117
40/104 2.31/335 1.44/209 1.44/209
60/140 3.73/541 2.44/354 2.33/338
65/149 4.17/605 2.75/399 2.60/377

[ I Read Before Servicing ]
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil.
Refrigerant Refrigerating machine oil
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out. The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
Cause Symptoms Effects on the refrigerant cycle
Water infiltration Frozen expansion valve and capillary tubes
Clogged expansion valve and capillary tubes Poor cooling performance Compressor overheat Motor insulation failure Burnt motor Coppering of the orbiting scroll Lock Burn-in on the orbiting scroll
Sludge formation and ad- hesion Acid generation Oxidization Oil degradation Air infiltration Oxidization
Adhesion to expansion valve and capillary tubes
Clogged expansion valve, capillary tubes, and drier Poor cooling performance Compressor overheat
Infiltration of contaminants into the com- pressor
Burn-in on the orbiting scroll
Sludge formation and adhesion Clogged expansion valve and capillary tubes Poor cooling performance Compressor overheat
Mineral oil etc.
Oil degradation Burn-in on the orbiting scroll
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.

[1] System configuration 17 [2] Types and Maximum allowable Length of Cables 18 [3] Switch Settings and Address Settings 19 [4] Sample System Connection 25 [5] An Example of a System to which an MA Remote Controller is connected 26 [6] An Example of a System to which an M-NET Remote Controller is connected 38 [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected 40 [8] Restrictions on Pipe Length 43


![Page 26 of the Mitsubishi Electronics P96 user manual — II Restrictions [1] System configuration](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-26.webp?w=400)
[ II Restrictions ]
Composing units Maximum total capacity
Maximum number of connectable in-
Types of connectable in-
144 72 72 72 - 216 36
168 96 72 84 - 252 42
192 96 96 96 - 288 48
216 120 96 108 - 324 50
240 120 120 120 - 360 50
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names. 2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.

[ II Restrictions ]
1. Wiring work (1) Notes 1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man- ual. 2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.) 3) Provide grounding for the outdoor unit as required. 4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing. 5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic compo- nents on the terminal block. 6) Use 2-core shielded cables as transmission cables. Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and malfunctions.
![Mitsubishi Electronics P96 — [2] Types and Maximum allowable Length of Cables diagram (page 27)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/fig-27-1.webp)
Different types of control wiring are used for different systems. Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
Types and maximum allowable length of cables Control lines are categorized into 2 types: transmission line and remote controller line. Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce noise interference.

Maximum transmission line distance between the outdoor unit and the far- thest indoor unit
Maximum transmission line distance for central- ized control and Indoor/ outdoor transmission line (Maximum line distance via outdoor unit)
500 m [1640ft] max. *The maximum overall line length from the power supply unit on the transmission lines for centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
![Page 28 of the Mitsubishi Electronics P96 user manual — [3] Switch Settings and Address Settings](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-28.webp?w=400)
[ II Restrictions ]
MA remote controller*1 M-NET remote controller*2
Type VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT Shielded cable MVVS
Number of cores 2-core cable 2-core cable
0.3 to 1.25mm2 *3
0.3 to 1.25mm2 *3
[AWG22 to 16] (0.75 to 1.25mm2 ) *4
[AWG22 to 16] (0.75 to 1.25mm2 ) *4
Maximum overall line length 200 m [656ft] max. The section of the cable that exceeds 10m [32ft] must be included in the maximum in- door-outdoor transmission line distance.
*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wireless remote controller. *2 M-NET remote controller refers to ME remote controller and ME simple remote controller. *3 The use of cables that are smaller than 0.75mm2 [AWG18] is recommended for easy handling. *4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi- cations shown in the parenthesis.
Units on which to set the switches Symbol Units to which the power must be shut off
CITY MULTI indoor unit Main/sub unit IC Outdoor units *3 and Indoor units
LOSSNAY, OA processing unit *1 LC Outdoor units *3 and LOSSNAY
M-NET remote controller Main/sub remote controller
RC Outdoor units *3
MA remote controller Main/sub remote controller
CITY MULTI outdoor unit*2 OC,OS Outdoor units *3
BC controller Main BC Outdoor units *3 and BC controller
Sub1, 2 BS1, BS2 Outdoor units *3 and BC controller
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line. *2. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). *3. Turn off the power to all the outdoor units in the same refrigerant circuit.

[ II Restrictions ]
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controller Sym- bol
Setting method Factory address
CITY MULTI indoor unit
Main/sub unit IC 0, 01 to 50*1 *4 *6 Assign the smallest address to the main indoor unit in the group, and assign sequential address numbers to the rest of the indoor units in the same group. In an R2 system with a sub BC controller, make the set- tings for the indoor units in the following order. (i) Indoor unit to be connected to the main BC controller (ii) Indoor unit to be connected to sub BC controller 1 (iii) Indoor unit to be connected to sub BC controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
LOSSNAY, OA processing unit LC 0, 01 to 50*1 *4 *6 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
RC 101 to 150 Add 100 to the smallest address of all the indoor units in the same group.
RC 151 to 200*3 Add 150 to the smallest address of all the indoor units in the same group.
MA remote controller MA No address settings required. (The main/sub setting must be made if 2 remote controllers are connected to the system.) Main
CITY MULTI outdoor unit OC OS
0, 51 to 100*1 *2 *6
Assign an address that equals the lowest address of the in-
door units in the same refrigerant circuit plus 50. Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same re- frigerant circuit are automatically designated as OC and OS. *5
BC 0, 51 to 100*1 *2 *6
Assign an address that equals the address of the outdoor
unit in the same refrigerant system plus 1. If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub BC controller, use a different, unused address within the setting range.
BC controller (sub1, 2)
51 to 100 *2 Assign an address to both the sub BC controller 1 and 2
that equals the lowest address of the indoor units that are connected to each of them plus 50. If a sub BC controller is connected, the automatic startup
function is not available.
201 to 250 Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range listed on the left to each unit.
Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.
Schedule timer (com- patible with M-NET)
Assign an arbitrary but unique address within the range listed on the left to each unit.
0, 201 to 250 Assign an arbitrary but unique address within the range listed on the left to each unit. The address must be set to "0" to control the K-control unit.
LM adapter SC 201 to 250 Assign an arbitrary but unique address within the range listed on the left to each unit.
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting range. *2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50." *3. To set the M-NET remote controller address to "200," set the rotary switches to "00." *4. Some models of indoor units have two or three control boards. Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2. *5. The outdoor units in the same refrigerant circuit are automatically designated as OC, and OS. They are designated as OC, and OS in the descending order of capacity (ascending order of address if the capacities are the same). *6. No address settings are required for units in a system with a single outdoor unit (with some exceptions). Address setting is required if a sub BC controller is connected.

[ II Restrictions ]
(Factory setting: The male power supply switch connector is connected to CN41.) There are limitations on the total number of units that are connectable to each refrigerant system. Refer to the System Design Manual for details.
Connection to the system con- troller
Power supply unit for transmission lines
Group operation of units in a sys- tem with multiple outdoor units
Power supply switch connector connection
System with one outdoor unit
_ _ _ Leave CN41 as it is (Factory setting)
System with multi- ple outdoor units
Not connected _ Not grouped
Grouped Disconnect the male connector from the fe- male power supply switch connector (CN41) and connect it to the female power supply switch connector (CN40) on only one of the outdoor units.*2
With connection to the indoor unit system
Not required Grouped/not grouped
With connection to the central- ized control sys- tem
*Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor unit whose CN41 was replaced with CN40 to the ground terminal ( ) on the electric box.
(Powered from the outdoor unit)
Required *1 Grouped/not grouped
Leave CN41 as it is (Factory setting)
*1 The need for a power supply unit for transmission lines depends on the system configuration. *2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the system. (3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)
System configuration Centralized control switch settings *1
Connection to the system controller Not connected Leave it to OFF. (Factory setting)
Connection to the system controller Connected*2
*1. Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting.
*2. When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor on the remote controller or an optional thermistor. 1) To use the built-in sensor on the remote controller, set the SW1-1 to ON. Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead. When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON. 2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON. When using an optional temperature sensor, install it where room temperature can be detected.
System configura- tion · Not required*1 · Grouped/not grouped

[ II Restrictions ]
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Setting (SW1)*4 *5
Function Operation of the indoor unit when the operation is resumed after the unit
Power ON/OFF by the plug*1,*2,*3 Indoor unit will go into operation regardless of its operation status before power off (power failure). (In approx. 5 minutes)
Automatic restoration after power failure
Indoor unit will go into operation if it was in operation when the power was turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before power off (power failure).
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the crankcase heater and may cause the compressor to malfunction when the unit is put back into operation. *2. Not applicable to units with a built-in drain pump or humidifier. *3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir- cuits will be turned on or off by the plug. *4. Requires that the dipswitch settings for all the units in the group be made. *5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To use the auto recovery function after power failure while these settings are made, set SW1-5 to ON. (6) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.") When using indoor unit as a cooling-only unit, set SW3-1 to ON. (7) Various types of control using input-output signal connector on the outdoor unit (various connection options)
to be used*1
DEMAND (level) CN3D*2
Input Prohibiting cooling/heating operation (thermo OFF) by an external input to the outdoor unit.
Adapter for external input (PAC- SC36NA-E) Performs a low level noise operation of the outdoor unit by an ex- ternal input to the outdoor unit. * It can be used as the silent operation device for each refrigerant system.
Low-noise mode (level)*3 *4
Forces the outdoor unit to perform a fan operation by receiving sig- nals from the snow sensor. *5 Snow sensor signal input (level)
Cooling/heating operation can be changed by an external input to the outdoor unit.
How to extract signals from the outdoor unit
Operation status of the compressor *5 CN51 Adapter for external out- put (PAC- SC37SA-E) Error status*6
*It can be used as an operation status display device. *It can be used for an interlock operation with external devices.
*1. For detailed drawing, refer to "Example of wiring connection".
*2. For details, refer to 1) through 4) shown below.
*3. Low-noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2 or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible.
*4. By setting Dip SW5-5, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri- ority mode. When SW5-5 is set to ON: The low-noise mode always remains effective. When SW5-5 is set to OFF: The low noise mode is cancelled when certain outside temperature or pressure criteria are met, and the unit goes into normal operation (capacity priority mode).
Low-noise mod is effective. Capacity priority mode becomes effective.
Cooling Heating Cooling Heating
TH74.6kg/cm2 TH7>35°C[95°F] or 63HS1>35kg/cm2 TH7
*5. Each outdoor unit in the system with multiple outdoor units requires the signal input/output setting to be made. *6. Take out signals from the outdoor unit (OC) if multiple outdoor units exist in a single system.

[ II Restrictions ]
Adapter 2 Outdoor unit control board
Distant control board Relay circuit Adapter 1 Outdoor unit control board
e cru o s re w o p p m a L
5 4 3 X Y
CN51
Maximum cable length is 10m
in the field Maximum cable length is 10m
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
L1 : Outdoor unit error display lamp L2 : Compressor operation lamp (compressor running state) X, Y : Relay (coil =
in stop mode or thermostat mode.
Relay circuit Adapter 2 Outdoor unit control board
OFF
ON
Y
ON
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
Maximum cable length is 10m
Adapter 2 Outdoor unit control board
Adapter 2 Outdoor unit control board
CN3D
Y
Maximum cable length is 10m
Maximum cable length is 10m
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
Contact rating current >= 0.1A Minimum appicable load =< 1mA at DC
fan frequency and maximum compressor frequency.

[ II Restrictions ]
CN3D 1-3P Compressor ON/OFF *1
CN3D 1-2P Low-noise mode*2
*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON , this function cannot be used. *2. This function can be enabled when the 4-step demand control is enabled. Input the order to CN3D 1-2P on the outdoor unit whose SW4-4 is set to OFF.
CN3D 1-3P Open Short-circuit
Open 100% (No DEMAND) 75%
Short-circuit 0% (Compressor OFF) 50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
(Example) When switching from 100% to 50%
If the step listed as the wrong example above is taken, thermo may go off. The percentage of the demand listed in the table above is an approximate value based on the compressor volume and does not necessarily correspond with the capacity. When this function is enabled, the night mode cannot be enabled.
8 levels of on-DEMAND No.2 CN3D
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit
Open Open 100% 50% 88% 75%
Short-circuit 50% 0% 38% 25%
Short-circuit Open 88% 38% 75% 63%
Short-circuit 75% 25% 63% 50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON. *4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
![Page 34 of the Mitsubishi Electronics P96 user manual — [4] Sample System Connection](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-34.webp?w=400)
[ II Restrictions ]
Examples of typical system connection are shown on pages [5] to [7]. Refer to the Installation Manual that came with each device or controller for details.
(1) An example of a system to which an MA remote controller is connected
System configuration Connection to the system controller Address start up for in- door and outdoor units Notes
1 System with one out-
door unit NO Automatic address setup
Connection of multiple LOSS- NAY units
2 System with one out-
door unit NO Manual address setup
3 Grouping of units in a
NO Manual address setup
4 System with one out-
With connection to transmission line
5 System with one out-
With connection to indoor-outdoor
Connection of multiple LOSS- NAY units
6 System with one out-
With connection to transmission line
(2) An example of a system to which an M-NET remote controller is connected
System configuration Connection to the system controller Address start up for indoor
and outdoor units Notes
1 System with one out-
With connection to transmission line
(3) An example of a system to which both MA remote controller and M-NET remote controller are connected
System configuration Connection to the system controller Address start up for in- door and outdoor units Notes
1 System with one out-
With connection to transmission
line for centralized control

[ II Restrictions ]
[5] An Example of a System to which an MA Remote Controller is connected

Leave the male connector on CN41 as it is. SW2-1 OFF
Leave the male connector on CN41 as it is. SW2-1 OFF
TB7 M1 M2 M1 M2 M1 M2 S TB3 TB02 M1 M2 S
*1. When BS is connected to the system, automatic address setup is not available.
(2) Cautions 1) M-NET remote controller and MA remote controller can- not both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
(3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L1 +L2+L3+L4+L5 200m[656ft] L1 +L2+L3+L11+L12+L13 200m[656ft] 2) Transmission line for centralized control No connection is required. 3) MA remote controller wiring Maximum overall line length (0.3 to 1.25mm2 [AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft] m4+m5 200m [656ft]

When the P72 and P96 models are not included in the connect- ed indoor units
When the P72 and P96 models are included in the connected indoor units
The table above shows the number of transmission
boosters that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.

[ II Restrictions ]
(4) Wiring method 1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block for indoor-outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-out- door transmission line (TB02) on the main BC controller (BC), and of the terminal block for indoor-outdoor trans- mission line (TB5) on each indoor unit (IC). (Non-polar- ized two-wire) Only use shielded cables.
Set one of the MA remote controllers as a sub controller.
(Refer to the Instruction Manual for the MA remote con- troller for the setting method.) Group operation of indoor units To perform a group operation of indoor units (IC), daisy- chain terminals 1 and 2 on the terminal block (TB15) on all indoor units (IC) in the same group, and then connect terminals 1 and 2 on the terminal block (TB15) on the in- door unit on one end to the terminal block on the MA re- motecontroller. (Non-polarized two-wire) When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor ad- dresssetup" is not available. 4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block(TB5) on the indoor unit (IC) to the appropriate ter- minals on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire) Interlock operation setting with all the indoor units in the
The outdoor units in the same refrigerant circuit are au- tomatically designated as OC and OS in the order of ca- pacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC controller (BC), and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable. 2) Transmission line for centralized control No connection is required. 3) MA remote controller wiring Connect terminals 1 and 2 on the terminal block for MA remote controller line (TB15) on the indoor unit (IC) to the terminal block on the MA remote controller (MA). (Non-polarized two-wire) When 2 remote controllers are connected to the sys- tem When 2 remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15) on the indoor unit (IC) to the terminal block on the two MA remote controllers.
same system will automatically be made. (It is required that the Lossnay unit be turned on before the outdoo- runit.) When performing an interlocked operation of part of the
indoor units in the system with a LOSSNAY unit, using a LOSSNAY unit alone without interlocking it with any units, performing an interlock operation of more than 16 indoor units with a LOSSNAY unit, or connecting two or more LOSSNAY units to the same refrigerant system, the automatic IC/OC address setup function is not avail- able. 5) Switch setting No address settings required.
dures Unit or controller Address set-
ting range Setting method Notes Factory
1 Indoor unit Main unit IC No settings required.
- Port number setting is re- quired To perform a group opera- tion of indoor units that fea- ture different functions, the automatic IC/OC address setup function is not avail- able.
2 LOSSNAY LC No settings required.
3 MA remote con- troller
MA No settings required.
MA Sub remote con- troller
Settings to be made with the Sub/Main switch
4 Outdoor unit OC OS
No settings required.
5 Auxiliary outdoor unit
BC No settings required.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]

Leave the male connector on CN41 as it is. SW2-1 OFF
Leave the male connector on CN41 as it is. SW2-1 OFF
TB7 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
* If the BC address overlaps any of the addresses that are assigned to either the OC, OS, or BS, use a different, unused address. OC, OS, and BS addresses (lowest indoor unit address in the group plus +50) have higher priority than the BS address.
(2) Cautions 1) M-NET remote controller and MA remote controller can- not both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
The table above shows the number of transmission
boosters that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected. (3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 1. 2) Transmission line for centralized control No connection is required. 3) MA remote controller wiring Same as [5] 1.

When the P72 and P96 models are not in- cluded in the connected indoor units
When the P72 and P96 models are includ- ed in the connected indoor units

[ II Restrictions ]
(4) Wiring method 1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block for indoor-outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-out- door transmission line (TB02) on the main and sub BC controllers (BC and BS), and of the terminal block for in- door-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire) Only use shielded cables.
The outdoor units in the same refrigerant circuit are au- tomatically designated as OC and OS in the order of ca- pacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on BC and BS, and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.
NAY units must be entered on the remote controller. (Re- fer to "IV [3] Interlock Settings via the MA Remote Controller" or the installation manual for the MA remote controller for the setting method.) 5) Switch setting Address setting is required as follows.
dures Unit or controller
Main unit IC 01 to 50 Assign the smallest address to the main
Port number setting is
unit in the group. In a system with a sub BC controller,
required To perform a group op-
make the settings for the indoor units in the following order. (i) Indoor unit to be connected to the main
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
BC controller (ii) Indoor unit to be connected to sub BC
controller 1 (iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an ad- dress to all indoor units.
None of these addresses may overlap any of the indoor unit addresses.
3 MA remote controller
MA No set- tings re- quired.
MA Sub remote controller
Settings to be made with the Sub/ Main switch
4 Outdoor unit OC OS
51 to 100 Assign sequential address to the outdoor
To set the address to 100,
units in the same refrigerant circuit. The outdoor units are automatically des-
set the rotary switches to 50. If the addresses that is as-
ignated as OC and OS.(Note)
signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. The use of a sub BC control-
5 Auxiliary outdoor unit
BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
BC control- ler (Main) BC OC (or OS if it exists) +1
ler requires the connection of a main BC controller.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]

CN41 CN40 Replace SW2-1 OFF Leave the male connector on CN41 as it is. SW2-1 OFF
M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is. SW2-1 OFF
Leave the male connector on CN41 as it is. SW2-1 OFF
M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
(2) Cautions 1) M-NET remote controller and MA remote controller can- not both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units. 5) Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
The left table shows the number of transmission boost-
ers that is required by the system with three BC control- lers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
(3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L12+L31+L22 500m [1640ft] L11+L31+L21 500m [1640ft] 3) MA remote controller wiring Same as [5] 1.

When the P72 and P96 mod- els are not included in the connected indoor units
When the P72 and P96 mod- els are included in the con- nected indoor units

[ II Restrictions ]
(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 2. Shielded cable connection Same as [5] 2. 2) Transmission line for centralized control Daisy-chain terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC and OS in the same refrigerant circuit If a power supply unit is not connected to the transmis- sion line for centralized control, replace the power jump- er connector on the control board from CN41 to CN40 on only one of the outdoor units.
Shielded cable connection Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the sys- tem Same as [5] 1. Group operation of indoor units Same as [5] 2. 4) LOSSNAY connection Same as [5] 2. 5) Switch setting Address setting is required as follows.
The outdoor units in the same refrigerant circuit are au- tomatically designated as OC and OS in the order of ca- pacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Only use shielded cables.
dures Unit or controller
Main unit IC 01 to 50 Assign the smallest address to the main
Port number setting is
unit in the group. In a system with a sub BC controller,
required To perform a group op-
make the settings for the indoor units in the following order. (i) Indoor unit to be connected to the main
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
BC controller (ii) Indoor unit to be connected to sub BC
controller 1 (iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an ad- dress to all indoor units.
None of these addresses may overlap any of the indoor unit addresses.
3 MA remote controller
MA No set- tings re- quired.
MA Sub remote controller
Settings to be made with the Sub/ Main switch
4 Outdoor unit OC OS
51 to 100 Assign sequential address to the outdoor
To set the address to 100,
units in the same refrigerant circuit. The outdoor units are automatically des-
set the rotary switches to 50. If the addresses that is as-
ignated as OC and OS.(Note)
signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. The use of a sub BC control-
5 Auxiliary outdoor unit
BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
BC control- ler (Main) BC OC (or OS if it exists) +1
ler requires the connection of a main BC controller.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]

CN41 CN40 Replace SW2-1 OFF Leave the male connector on CN41 as it is. SW2-1 OFF
Leave the male connector on CN41 as it is. SW2-1 OFF
Leave the male connector on CN41 as it is. SW2-1 OFF
The left table shows the number of transmission boosters
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be per- formed only on one of the outdoor units. 5) Short-circuit the shield terminal (S terminal) and the earth terminal ( ) on the terminal block for transmission line for centralized control (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-men- tioned system, two additional indoor units can be connected. 7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec- tor on CN41 as it is (factory setting).
(3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 3. 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft] 3) MA remote controller wiring Same as [5] 1.

When the P72 and P96 models are not included in the connected in- door units
When the P72 and P96 models are included in the connected indoor units

[ II Restrictions ]
Daisy-chain the S terminal of the terminal block (TB7) on the system controller, OC, and OS with the shield of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the sys- tem Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block (TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-polarized two-wire) Indoor units must be interlocked with the LOSSNAY unit
(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 2. Only use shielded cables. Shielded cable connection Same as [5] 2. 2) Transmission line for centralized control Daisy-chain terminals A and B on the system controller, ter- minals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in dif- ferent refrigerant circuits and on the outdoor units (OC and OS) in the same refrigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper con- nector on the control board from CN41 to CN40 on only one of the outdoor units. If a system controller is connected, set the central control switch (SW2-1) on the control board of all outdoor units to "ON."
using the system controller. (Refer to the operation man- ual for the system controller for the setting method.) In- terlock setting from the remote controller is required if the ON/OFF remote controller alone or the LM adapter alone is connected. 5) Switch setting Address setting is required as follows.
The outdoor units in the same refrigerant circuit are au- tomatically designated as OC, OS1, and OS2 in the or- der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Only use shielded cables.
(5) Address setting method
dures Unit or controller
Main unit IC 01 to 50 Assign the smallest address to the main unit
Port number setting is
in the group. In a system with a sub BC controller, make
required To perform a group op-
the settings for the indoor units in the fol- lowing order. (i) Indoor unit to be connected to the main BC
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
controller (ii) Indoor unit to be connected to sub BC
controller 1 (iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
None of these addresses may overlap any of the indoor unit addresses.
3 MA remote controller
MA No set- tings re- quired.
- Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.
MA Sub remote controller
Settings to be made with the Sub/ Main switch
4 Outdoor unit (Note) OC OS
51 to 100 Assign sequential address to the outdoor
To set the address to 100,
units in the same refrigerant circuit. The outdoor units are automatically desig-
set the rotary switches to 50. If the addresses that is as-
nated as OC and OS.(Note)
signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. The use of a sub BC control-
5 Auxiliary outdoor unit
BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
BC control- ler (Main) BC OC (or OS if it exists) +1
ler requires the connection of a main BC controller.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]

Leave the male connector on CN41 as it is.
M2 M1 M2 M1 M2 M1 M2 M1 M2 M1
Leave the male connector on CN41 as it is.
Leave the male connector on CN41 as it is.
M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be per- formed only on one of the outdoor units. 5) Provide grounding to S terminal on the terminal block for transmis- sion line for centralized control (TB7) on only one of the outdoor units. 6) A maximum of 3 system controllers can be connected to the indoor- outdoor transmission line, with the exception that only one G(B)-50A may be connected. 7) When the total number of indoor units exceeds 20 (12 if one or more indoor units of the 72 model or above is connected), it may not be possible to connect a system controller to the indoor-outdoor trans- mission line. 8) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

When the P72 and P96 models are not in- cluded in the connected indoor units
When the P72 and P96 models are includ- ed in the connected indoor units
The table above shows the number of transmission boosters that is
required by the system with three BC controllers. For each BC con- troller that is subtracted from the above-mentioned system, two ad- ditional indoor units can be connected. (3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] L25 200m [656ft] 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L25+L31+L12(L11) 500m [1640ft] L12(L11)+L31+L22(L21) 500m [1640ft] 3) MA remote controller wiring Same as [5] 1.

[ II Restrictions ]
Only use shielded cables.
(4) Wiring method 1) Indoor/outdoor transmission line
Shielded cable connection Daisy-chain the S terminal on the terminal block (TB7) on the out- door units (OC, OS) with the shield wire of the shielded cable. Short- circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the sys- tem Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection
Daisy-chain terminals M1 and M2 of the terminal block for indoor- outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC controllers (BC and BS), of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC), and the S terminal of the system controller.(Non-polarized two-wire) Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC and BS, and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable. 2) Transmission line for centralized control
Connect terminals M1 and M2 on the terminal block (TB5) on the in- door units (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po- larized two-wire) Indoor units must be interlocked with the LOSSNAY unit using the
Daisy-chain terminals M1 and M2 on the terminal block for transmis- sion line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC and OS in the same re- frigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the con- trol board from CN41 to CN40 on only one of the outdoor units. Set the central control switch (SW2-1) on the control board of all out- door units to "ON."
system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock setting from the remote controller is required if the ON/OFF remote controller alone is con- nected. 5) Switch setting Address setting is required as follows.
dures Unit or controller
Main unit IC 01 to 50 Assign the smallest address to the main unit
Port number setting is
in the group. In a system with a sub BC controller, make
required To perform a group op-
the settings for the indoor units in the fol- lowing order. (i) Indoor unit to be connected to the main BC
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
controller (ii) Indoor unit to be connected to sub BC
controller 1 (iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
None of these addresses may overlap any of the indoor unit addresses.
3 MA remote controller
MA No set- tings re- quired.
- Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.
MA Sub remote controller
Settings to be made with the Sub/ Main switch
4 Outdoor unit OC OS
51 to 100 Assign sequential address to the outdoor
To set the address to 100,
units in the same refrigerant circuit. The outdoor units are automatically desig-
set the rotary switches to 50. If the addresses that is as-
nated as OC and OS.(Note)
signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. The use of a sub BC control-
5 Auxiliary outdoor unit
BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
BC control- ler (Main) BC OC (or OS if it exists) +1
ler requires the connection of a main BC controller.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]

Leave the male connector on CN41 as it is.
1 1 2 1 2 2 2 1 2 57
M1M2
Leave the male connector on CN41 as it is.
Leave the male connector on CN41 as it is.
*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
(3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft] 3) MA remote controller wiring Maximum overall line length (0.3 to 1.25mm2 [AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft]
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be per- formed only on one of the outdoor units. 5) Short-circuit the S (shield) terminal of the terminal block for the cen- tral control unit (TB7) and the ground terminal ( ) on the outdoor unit whose power jumper was moved from CN41 to CN40. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

When the P72 and P96 models are not in- cluded in the connected indoor units
When the P72 and P96 models are includ- ed in the connected indoor units
The table above shows the number of transmission boost-
ers that is required by the system with three BC controllers. For each BC controller that is subtracted from the above- mentioned system, two additional indoor units can be con- nected. 7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec- tor on CN41 as it is (factory setting).

[ II Restrictions ]
door units to "ON." Only use shielded cables.
(4) Wiring method 1) Indoor/outdoor transmission line
Shielded cable connection Daisy-chain the S terminal of the terminal block (TB7) on the system controller, OC, and OS with the shield of the shielded cable. Short- circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the system Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection
Daisy-chain terminals M1 and M2 of the terminal block for indoor- outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC controllers (BC and BS), and of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire) Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC (BS), and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.
The outdoor units in the same refrigerant circuit are auto- matically designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Only use shielded cables. 2) Transmission line for centralized control
Connect terminals M1 and M2 on the terminal block (TB5) on the in- door unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po- larized two-wire) Indoor units must be interlocked with the LOSSNAY unit us-
ing the system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock set- ting from the remote controller is required if the ON/OFF re- mote controller alone or the LM adapter alone is connected. 5) Switch setting Address setting is required as follows.
Daisy-chain terminals A and B on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in differ- ent refrigerant circuits and on the OC and OS in the same refrigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the con- trol board from CN41 to CN40 on only one of the outdoor units. Set the central control switch (SW2-1) on the control board of all out-
Main unit IC 01 to 50 Assign the smallest address to the main unit in the
Port number setting is
group. In a system with a sub BC controller, make the set-
required To perform a group op-
tings for the indoor units in the following order. (i) Indoor unit to be connected to the main BC con-
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
troller (ii) Indoor unit to be connected to sub BC controller 1 (iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit ad- dress +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
None of these addresses may overlap any of the indoor unit addresses.
3 MA remote controller
Main remote controller MA No settings required. - Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.
Sub remote controller MA Sub re- mote con- troller
Settings to be made with the Sub/Main switch
4 Outdoor unit OC OS
51 to 100 The sum of the smallest address of the indoor units
To set the address to 100,
set the rotary switches to 50. 00
in the same system and 50. Assign sequential address to the outdoor units in
the same refrigerant circuit. The outdoor units are automatically designated as
OC and OS.(Note)
5 Auxiliary outdoor unit
BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
To set the address to 100,
set the rotary switches to 50. If the addresses that is as-
signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. The use of a sub BC control-
BC control- ler (Main) BC 51 to 100 OC (or OS if it exists) +1
ler requires the connection of a main BC controller.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]
[6] An Example of a System to which an M-NET Remote Controller is connected

Leave the male connector on CN41 as it is.
Leave the male connector on CN41 as it is.
Leave the male connector on CN41 as it is.
*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
(2) Cautions 1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 3 M-NET remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units. 5) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the out- door units. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in par- allel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
The left table shows the number of transmission boosters
that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-men- tioned system, two additional indoor units can be connected. 7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec- tor on CN41 as it is (factory setting). (3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 3. 2) Transmission line for centralized control Same as [5] 4. 3) M-NET remote controller wiring Maximum overall line length (0.3 to 1.25mm2 [AWG22 to 16]) m1 10m [32ft] m2+m3 10m [32ft] If the standard-supplied cable must be extended, use a cable with a diameter of 1.25mm2 [AWG16]. The section of the cable that exceeds 10m [32ft] must be included in the maximum indoor-outdoor transmission line distance described in (1). When connected to the terminal block on the Simple re- mote controller, use cables that meet the following cable size specifications: 0.75 - 1.25 mm2 [AWG18-16].

When the P72 and P96 models are not included in the connected indoor units
When the P72 and P96 models are included in the connected in- door units

[ II Restrictions ]
When 2 remote controllers are connected to the sys- tem Refer to the section on Switch Setting. Performing a group operation (including the group operation of units in different refrigerant circuits). Refer to the section on Switch Setting. 4) LOSSNAY connection Same as [5] 4. 5) Switch setting Address setting is required as follows.
(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 3. Shielded cable connection Same as [5] 1. 2) Transmission line for centralized control Same as [5] 4. Shielded cable connection Same as [5] 4. 3) M-NET remote controller wiring M-NET remote controller is connectable anywhere on the indoor-outdoor transmission line.
dures Unit or controller
Main unit IC 01 to 50 Assign the smallest address to the main unit
Port number setting is
in the group. In a system with a sub BC controller, make
required To perform a group op-
the settings for the indoor units in the fol- lowing order. (i) Indoor unit to be connected to the main BC
eration of indoor units that have different func- tions, set the indoor unit in the group with the greatest number of functions as the main unit.
controller (ii) Indoor unit to be connected to sub BC
controller 1 (iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
None of these addresses may overlap any of the indoor unit addresses.
3 M-NET remote controller
RC 101 to 150 Add 100 to the main unit address in the group
It is not necessary to set the
100s digit. To set the address to 200,
set the rotary switches to 00.
RC 151 to 200 Add 150 to the main unit address in the group
4 Outdoor unit OC OS
51 to 100 Assign sequential address to the outdoor
To set the address to 100,
units in the same refrigerant circuit. The outdoor units are automatically desig-
set the rotary switches to 50. If the addresses that is as-
nated as OC and OS.(Note)
signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. The use of a sub BC control-
5 Auxiliary outdoor unit
BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
BC control- ler (Main) BC OC (or OS if it exists) +1
ler requires the connection of a main BC controller.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]
[7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected

Leave the male connector on CN41 as it is.
Leave the male connector on CN41 as it is.
Leave the male connector on CN41 as it is.
M1M2 M1M2 M1M2 M1 M2 M1 M2 M1 M2
*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
The left table shows the number of transmission boost-
1) Be sure to connect a system controller. 2) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 3) Assign to the indoor units connected to the MA remote controller ad- dresses that are smaller than those of the indoor units that are con- nected to the M-NET remote controller. 4) No more than 2 M-NET remote controllers can be connected to a group of indoor units. 5) No more than 2 MA remote controllers can be connected to a group of indoor units. 6) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 7) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units. 8) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the outdoor units. 9) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
ers that is required by the system with three BC control- lers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected. 10) When a power supply unit is connected to the transmis- sion line for centralized control, leave the power jumper connector on CN41 as it is (factory setting). (3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 3. 2) Transmission line for centralized control Same as [5] 4. 3) MA remote controller wiring Same as [5] 1. 4) M-NET remote controller wiring Same as [6]

When the P72 and P96 models are not included in the connected indoor units
When the P72and P96 models are included in the connected in- door units

[ II Restrictions ]
Group operation of indoor units Same as [5] 1. 4) M-NET remote controller wiring When 2 remote controllers are connected to the sys- tem Group operation of indoor units Same as [6] 5) LOSSNAY connection Same as [5] 4. 6) Switch setting Address setting is required as follows.
(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 3. Shielded cable connection Same as [5] 1. 2) Transmission line for centralized control Same as [5] 4. Shielded cable connection Same as [5] 4. 3) MA remote controller wiring When 2 remote controllers are connected to the sys- tem

[ II Restrictions ]
1 Opera- tion with the MA re- mote controller
IC 01 to 50 Assign the smallest address to
Assign an address smaller than that of
the main unit in the group. In a system with a sub BC con-
the indoor unit that is connected to the M-NET remote controller. Enter the same indoor unit group set-
troller, make the settings for the indoor units in the following or- der. (i) Indoor unit to be connected to
tings on the system controller as the ones that were entered on the MA re- mote controller. To perform a group operation of indoor
the main BC controller (ii) Indoor unit to be connected to
units that have different functions, des- ignate the indoor unit in the group with the greatest number of Port number setting is required
sub BC controller 1 (iii) Indoor unit to be connected to
sub BC controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
IC 01 to 50 Assign sequential numbers start- ing with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
MA No set- tings re- quired.
MA Sub remote control- ler
Settings to be made according to the remote controller func- tion selection
2 Opera- tion with the M-NET remote controller
IC 01 to 50 Assign the smallest address to the main unit in the group.
Assign an address higher than those of
the indoor units that are connected to the MA remote controller. Make the initial settings for the indoor
IC 01 to 50 Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
unit group settings via the system con- troller. To perform a group operation of indoor
units that have different functions, des- ignate the indoor unit in the group with the greatest number of functions as the main unit. Port number setting is required. Addresses that are assigned to the in-
door units that are connected to the sub BC controller should be higher than the addresses that are assigned to the in- door units that are connected to the main BC controller.
RC 101 to 150 Add 100 to the main unit ad- dress in the group.
It is not necessary to set the 100s
digit. To set the address to 200, set it to
RC 151 to 200 Add 150 to the main unit ad- dress in the group.
3 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
None of these addresses may over- lap any of the indoor unit addresses.
4 Outdoor unit OC OS
51 to 100 Assign sequential address to the
To set the address to 100, set it to 50. If the addresses that is assigned to the
outdoor units in the same refrig- erant circuit. The outdoor units are automati-
main BC controller overlaps any of the addresses that are assigned to the out- door units or to the sub BC controller, use a different, unused address within the setting range. The use of a sub BC controller requires
cally designated as OC and OS.(Note)
5 Auxiliary outdoor unit
BCcontroller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
the connection of a main BC controller.
BC controller (Main) BC OC (or OS if it exists) +1
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

[ II Restrictions ]
(1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con-
A
*Use a main BC controller when connecting the outdoor units of P144 model or above.
Reducer (P06 - P18 models) (Supplied with the BC Controller)
c Junction pipe (CMY-R160-J)
(P06 - P54 models) (P72 or P96 models) Maximum of 3 units per port Total capacity of P54 or below
Operation Pipe sections Allowable length of pipes
Length Total pipe length A+B+a+b+c+d Refer to the restrictions on the total piping
length in the graph on the next page.
Total pipe length from the outdoor unit to the farthest indoor unit
A+B+d 165 [541] or less (Equivalent length 190 [623] or less)
Between outdoor unit and BC control- ler
A 110 [360] or less
Between BC controller and indoor unit B+d 40 [131] or less*1
Height difference Between indoor and outdoor units
Outdoor unit above indoor unit
H 50 [164] or less
Outdoor unit be- low indoor unit
H' 40 [131] or less
Between indoor unit and BC controller h1 15[49](10[32]) or less*2
Between indoor units h2 15[49](10[32]) or less *2
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
1) To connect the P72 or P96 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J). 2) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port. 3) Note the following when connecting multiple indoor units to a single port. Those indoor units connected to the same port must be installed in the same room. Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
![Page 53 of the Mitsubishi Electronics P96 user manual — [8] Restrictions on Pipe Length](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-53.webp?w=400)
[ II Restrictions ]
The height difference and the pipe length between BC controller and indoor units Restrictions on pipe length [PURY-P72, P96THMU-A, PURY-P72, P96YHMU-A]
Aggregate length of all pipes(m[ft])
controller and farthest indoor unit (m[ft])
Pipe length between main BC
200 10 20 30 40 50 60 70 80 90 100 110
0 5 10 15
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
Height difference between main BC controller and farthest indoor unit (m[ft])

[ II Restrictions ]
(2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P120 model or
Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2)
H H'
Branch joint (CMY-Y102S-G2)
Reducer (P06 - P18 models) (Supplied with the BC Controller)
B
Indoor
(P06 - P54 models) (P72 or P96 models) Maximum of 3 units per port Total capacity of P54 or below
Operation Pipe sections Allowable length of pipes
Length Total pipe length A+B+C+D+E+a+b+c+d+e+f Refer to the restrictions on the total pip- ing length in the graphon the next page.
Total pipe length from the out- door unit to the farthest indoor unit
A+C+E+f 165 [541] or less (Equivalent length 190 [623] or less)
Between outdoor unit and BC controller
A 110 [360] or less
40 [131] or less*1
Between BC controller and in- door unit
Height differ- ence Between indoor and outdoor units
Outdoor unit above in- door unit
H 50 [164] or less
Outdoor unit below in- door unit
H' 40 [131] or less
h1 15 [49](10[32]) or less*2
Between indoor unit and BC controller
Between indoor units h2 15 [49](10[32]) or less *2
Between the BC controller (main or sub) and the sub BC controller
h3 15 [49] or less
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.

[ II Restrictions ]
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel. 4) To connect the P36 through P54 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J) and merge the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.) It is also possible to connect the P36 through P54 models of units to a port, although the cooling performance will somewhat decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.) (The factory setting for DIP SW4-6 is OFF. ) 5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port. 6) Note the following when connecting multiple indoor units to a single port. Those indoor units connected to the same port must be installed in the same room. Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode. 7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or below (when two GB type controllers are connected P126 or below for both combined). The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below. If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with two sub controllers is P168 or below.
The height difference and the pipe length between BC controller and indoor units Restrictions on pipe length [PURY-P120THMU-A, PURY-P120YHMU-A]
Aggregate length of all pipes(m[ft])
controller and farthest indoor unit (m[ft])
Pipe length between main BC
200 10 20 30 40 50 60 70 80 90 100 110
0 5 10 15
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
Height difference between main BC controller and farthest indoor unit (m[ft])

[ II Restrictions ]
(3) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144 model or
Branch joint (CMY-R100VBK) The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity index of the two, regardless of the relative positions of the outdoor units or their addresses. If the distributor is placed in the outdoor unit that has a smaller capacity, refrigerant will not be properly distributed and compressor failure may result. (If outdoor units that have the same capacity are used in combination, the distributor can be placed in either outdoor unit.)
Outdoor unit 1 Outdoor unit 2
Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2)
A
D
H H'
Branch joint (CMY-Y102S-G2)
Reducer (P06 - P18 models) (Supplied with the BC Controller)
B
Indoor
(P06 - P54 models) (P72 - P96 models) Maximum of 3 units per port Total capacity of P54 or below

Refer to the restrictions on the total pip- ing length in the graph on the next page.
Total pipe length from the out- door unit to the farthest indoor unit
F(G)+A+C+E+f 165 [541] or less (Equivalent length 190 [623] or less)
Between indoor units h2 15 [49](10[32]) or less *2
Between the BC controller (main or sub) and the sub BC controller
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.

[ II Restrictions ]
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel. 4) To connect the P36 through P54 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J) and merge the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.) It is also possible to connect the P36 through P54 models of units to a port, although the cooling performance will somewhat decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.) (The factory setting for DIP SW4-6 is OFF.) 5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port. 6) Note the following when connecting multiple indoor units to a single port. Those indoor units connected to the same port must be installed in the same room. Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode. 7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or below (when two GB type controllers are connected P126 or below for both combined) . The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below. If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with two sub controllers is P168 or below.
![Page 58 of the Mitsubishi Electronics P96 user manual — [PURY-P216, P240TSHMU-A] [PURY-P216, P240YSHMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-58.webp?w=400)
[ II Restrictions ]
Restrictions on pipe length
[PURY-P192TSHMU-A] [PURY-P192YSHMU-A]
Aggregate length of all pipes(m[ft])
Aggregate length of all pipes(m[ft])
200 10 20 30 40 50 60 70 80 90 100
200 10 20 30 40 50 60 70 80 90 100
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
Pipe length between outdoor unit and BC controller (m[ft])
Aggregate length of all pipes(m[ft]) Pipe length between main BC
200 10 20 30 40 50 60 70 80 90 100
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
The height difference and the pipe length between BC controller and indoor units
controller and farthest indoor unit (m[ft])
0 5 10 15
Height difference between main BC controller and farthest indoor unit (m[ft])

[ II Restrictions ]
Refrigerant pipe size Connection to outdoor unit and BC controller
Low-pressure pipe High-pressure pipe Low-pressure pipe High-pressure pipe
72 ø19.05 [3/4"] ø15.88 [5/8"] ø19.05 [3/4"] ø15.88 [5/8"]
96 ø22.2 [7/8"]
ø22.2 [7/8"]
ø19.05 [3/4"] 120
ø19.05 [3/4"]
ø22.2[7/8"] ø22.2 [7/8"] 168
ø28.58 [1-1/8"] ø28.58 [1-1/8"]
216 ø28.58 [1-1/8"] ø28.58 [1-1/8"] 240
(2) Between BC controller and indoor unit (Sections a, b, c, d, e, and f )
Refrigerant pipe size Indoor unit connection (Flare connection for all models)
Liquid pipe Gas pipe Liquid pipe Gas pipe
P06, P08, P12, P15, P18 ø6.35 [1/4"] ø12.7 [1/2"] ø6.35 [1/4"] ø12.7 [1/2"]
ø9.52 [3/8"] ø15.88 [5/8"] ø9.52 [3/8"] ø15.88 [5/8"] P36, P48, P54
ø19.05 [3/4"]
ø19.05 [3/4"]
ø12.7 [1/2"]
ø12.7 [1/2"]
P96 ø22.2
ø22.2
Refrigerant pipe size (Brazed connection on all models )
Liquid pipe High-pressure gas pipe Low-pressure gas pipe
ø15.88 [5/8"] ø19.05 [3/4"]
ø9.52 [3/8"]
ø22.2 [7/8"]
ø19.05 [3/4"]
ø12.7 [1/2"]
ø28.58 [1-1/8"] P127 - P144
ø22.2 [7/8"] P145 - P168 ø15.88 [5/8"]
Select the proper size pipes for the main unit based on the total capacity of the indoor units that are connected to both sub BC controllers. Select the proper size pipes for the sub controller side based on the total capacity of the indoor units that are connected to the sub controller.

[ II Restrictions ]
P72 - P120 models
*1 Reducer (Standard supplied parts)
*2 Junction pipe kit (Model name: CMY-R160-J) (Optional accessory)
Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)
Indoor
P18 model or below P24 - P54 models P72 or P96 models
Maximum of 3 units per port Total capacity of P30 or below (All units connected to the same port must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.
High-pressure side (gas) Low-pressure side (gas)
Outdoor unit side PURY-P72THMU-A PURY-P72YHMU-A
ø15.88 [5/8"] (Brazed connection)
ø19.05 [3/4"] (Brazed connection)
PURY-P96THMU-A PURY-P96YHMU-A ø19.05 [3/4"] (Brazed connection)
ø22.2 [7/8"] (Brazed connection)
ø28.58 [1-1/8"] (Brazed connection)
Indoor unit side ø9.52 [3/8"] (Flare connection) ø15.88 [5/8"] (Flare connection)
* BC controllers can only be connected to P72 - P120 models of outdoor units.

[ II Restrictions ]
Liquid pipe side:3/8F (Flare connection)
Liquid pipe side:3/8F (Flare connection) Gas pipe side:5/8F (Flare connection)
Gas pipe side:5/8F (Flare connection)
Supplied with a thermal insulation cover
on the total capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units Liquid pipe Gas pipe
P54 or below ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]
50 [1-31/32"] · 234 [9-7/32"]

[ II Restrictions ]
P72 - P240 models
Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)
BC controller (main) To outdoor unit Connection: Brazed connection
*1 Reducer (Standard supplied parts)
*2 Junction pipe kit (Model name:CMY-R160-J) (Optional accessory)
Indoor Indoor Indoor
P18 model or below P24 - P54 models P72 or P96 models
Maximum of 3 units per port Total capacity of P54 or below (All units connected to the same port must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller. 2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use a junction pipe kit and merge the two nozzles. 3) To connect multiple indoor units to a port (or to a junction pipe) Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below) Maximum number of connectable indoor units: 3 units Branch joint: Use CMY-Y102S-G2 (optional accessory). Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units Liquid pipe Gas pipe
P54 or below ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]
High pressure side (Liquid) Low-pressure side (Gas)
ø15.88 [5/8"] (Brazed connection)
ø19.05 [3/4"] (Brazed connection)
PURY-P96THMU-A PURY-P96YHMU-A ø19.05 [3/4"] (Brazed connection)
ø22.2 [7/8"] (Brazed connection)
PURY-P144TSHMU-A PURY-P144YSHMU-A
ø22.2 [7/8"] (Brazed connection) PURY-P168TSHMU-A PURY-P168YSHMU-A
ø28.58 [1-1/8"] (Brazed connection)
PURY-P216TSHMU-A PURY-P216YSHMU-A ø28.58 [1-1/8"] (Brazed connection) PURY-P240TSHMU-A PURY-P240YSHMU-A
Indoor unit side ø9.52 [3/8"] (Flare connection) ø15.88 [5/8"] (Flare connection)

[ II Restrictions ]
Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)
BC controller (sub) To Main BC controller
*2 Junction pipe kit (Model name: CMY-R160-J) (Optional accessory)
*1 Reducer (Standard supplied parts)
Indoor Indoor Indoor
Indoor Indoor Indoor
P18 model or below P24 - P54 models P72 or P96 models
Maximum of 3 units per port Total capacity of P54 or below (All units connected to the same port must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller. 2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use a junction pipe kit and merge the two nozzles. 3) To connect multiple indoor units to a port (or to a junction pipe) Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below) Maximum number of connectable indoor units: 3 units Branch joint: Use CMY-Y102S-G2 (optional accessory). Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units Liquid pipe Gas pipe
P54 or below ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]
Total capacity of the in- door units that are con- nected to the BC controller
(gas) Liquid pipe side
On the BC controller side P72 model or below ø15.88 [5/8"] (Brazed connection)
ø19.05 [3/4"] (Brazed connection) ø9.52 [3/8"] (Brazed connection) P73 - P108 ø19.05 [3/4"] (Brazed connection)
ø22.2 [7/8"] (Brazed connection)
ø12.7 [1/2"] (Brazed connection) P127 - P144
ø28.58 [1-1/8"] (Brazed connection)
ø22.2 [7/8"] (Brazed connection) P145 - P168 ø15.88 [5/8"] (Brazed connection)

[1] Outdoor Unit Components and Refrigerant Circuit 57 [2] Control Box of the Outdoor Unit 60 [3] Outdoor Unit Circuit Board 64 [4] BC Controller Components 74 [5] Control Box of the BC Controller 77 [6] BC Controller Circuit Board 78



[ III Outdoor Unit Components ]
PURY-P72, P96, P120YHMU-A


[ III Outdoor Unit Components ]
PURY-P72YHMU-A

Refrigerant service valve on the low pressure side (BV1) Solenoid valve(SV5c) Refrigerant service valve on the high pressure side(BV2)

[ III Outdoor Unit Components ]
PURY-P96, P120YHMU-A

Low pressure check joint(CJ2) Refrigerant service valve on the low pressure side(BV1)
Refrigerant service valve on the high pressure side (BV2)

[ III Outdoor Unit Components ]
<HIGH VOLTAGE WARNING>
Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and Check that the voltage across terminals FT-P and FT-N (YHMU) on the INV board or the voltage at both ends of the main capacitor (C1) (THMU) is 20VDC or below. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
DC reactor (DCL) Fan board


Rush current protection resistor (R1) Note.2
INV board Terminal block for transmission line (TB3, TB7)

[ III Outdoor Unit Components ]

(ACCT3)
(DCCT1)
(TB1)
IPM
Terminal block for transmission line (TB3, TB7)

[ III Outdoor Unit Components ]
Capacitor(C100) Rush current protection resistor (R1,R5) Note.2
Fan board Control board

Terminal block for power supply (TB1)
Terminal block for transmission line (TB3, TB7) Note.1

[ III Outdoor Unit Components ]

Transformer (T03) · Transformer (T02)

[ III Outdoor Unit Components ]
CN2
CNDC Bus voltage input P N
CN332 Output 18VDC GND (Fan board)
Serial communication signal input GND INV board Output 17VDC
CN801 Pressure switch connection
CN4 GND Serial communication signal output
CN505 72C driving output (THMU)
Output 12VDC Compressor ON/OFF output Error output
CN72 72C driving output (YHMU)
LED3 Lit when powered
LED2 Lit during normal CPU operation
LED3 Lit when powered
CNVCC2 Output 12VDC Output 5VDC GND CNIT Output 12VDC GND Output 5VDC Power supply detection input
CN41 Power supply for centralized control OFF CN40 Power supply for centralized control ON CN102
External signal input (contact input) F01 Fuse 250V AC/3.15A
Indoor/outdoor transmission line input/output (30VDC) Power supply input for centralized control system (30VDC)
Power supply ON/OFF signal output CNS2 Transmission line input/output for centralized control system (30VDC)

[ III Outdoor Unit Components ]
CN04 Bus voltage input (YHMU only) Bus voltage output (THMU only) P N
CN102 CNS2 Transmission line input/output for centralized control system (30VDC)
CNIT Input 12VDC GND Input 5VDC Power supply detection output Power supply ON/OFF signal input
CN03(THMU only) Bus voltage input P N
Power supply output for centralized control system (30VDC) Indoor/outdoor transmission line input/output (30VDC)
(THMU only) F01 250V 3.15A Grounding
LED1 Power supply for indoor transmission line
TP1,2 Check pins for indoor/outdoor transmission line
Ground terminal for transmission line Grounding Grounding
TB7 Terminal block for transmission line for centralized control TB3 Indoor/outdoor transmission block

[ III Outdoor Unit Components ]

Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

[ III Outdoor Unit Components ]
CNTH Thermistor input (THHS) CNTYP Function setting input (Z26)
CNCT3 Current (AC) sensor input (ACCT3)
CNCT2 Current (AC) sensor input ACCT1 ACCT2
LED1 Inverter in normal operation
LED4 Lit during normal CPU operation
CN5V GND Output 5VDC
CNCT Current (DC) sensor input
FT-N(Note) BUS voltage output(N)
CN4 GND (Fan board) Serial communication
LED3 Lit while charging
SC-P1 Bus voltage input/output(P)
IPM-P BUS voltage output(P) (IPM input)
CNDC1 BUS voltage output P N
IPM driving power supply output and signal output
F02 Fuse 250VAC 3.15A
IPM error signal input (IPM output)
IPM-N BUS voltage input/output(N) (IPM input)
CNDC2 BUS voltage input P N
CNDC3 BUS voltage output P N
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

[ III Outdoor Unit Components ]
SC-P1 Rectifier diode output (P)
CN5V GND Output 5VDC
RSH1 Overcurrent detection resistor
SC-P2 Bus voltage Input(P)
CN4 GND(INV Board)
Serial communication signal output
Bus voltage check terminal (P) Note
Serial communication signal output GND Input 17VDC
CN1 Bus voltage output N P
CNTYP Inverter board type
Bus voltage check terminal (N) Note 1
CT22 Current sensor(W) CT12 Current sensor(U)
C30 C37 Smoothing capacitor

[ III Outdoor Unit Components ]
CN4 GND Serial communication signal output GND(Control board) Serial communication signal output
CNVDC Bus voltage input N P
F01 Fuse 250VAC 15A
LED3 Lit during normal CPU operation
CN18V Input 18VDC GND
CN22 GND(INV board) Input 5VDC Serial communication signal input GND(INV board) Input 17VDC
CN21 Serial communication signal output GND(INV board) Input 17VDC
THBOX Thermistor (Control box internal temperature detection)
LED1 Inverter in normal operation
R630 Overcurrent detection resistor
DIP IPM(Rear) CNINV Inverter output W V U
LED2 Inverter error

[ III Outdoor Unit Components ]
CN18V Input 18VDC GND
LED3 Lit during normal CPU operation
CN4 GND Serial communication signal output
GND(Control board) Serial communication signal output
CN21 Serial communication signal output GND(INV board) Input 17VDC
CNVDC Bus voltage input N P
CN22 GND(INV board) Input 5VDC Serial communication signal input GND(INV board) Output 17VDC
CNINV Inverter output W V U
THBOX Thermistor (Control box internal temperature detection)
LED1 Inverter in normal operation LED2 Inverter error
R630,R631 Overcurrent detection resistor
DIP IPM Rear

[ III Outdoor Unit Components ]


[ III Outdoor Unit Components ]
R1,2 Rush current protection resistor
TB42 Bus voltage output(N)
TB31 Bus voltage output(P)
CN03 72C drive input
Electromagnetic relay (72C)
F3 Fuse 250VAC 6.3A
Diode stack rectified voltage input (Diode stack output)
Output (Diode stack input)
CN02 Output L1 L2
TB23 Input (L3)
TB22 Input (L2)
F1 Fuse 250VAC 6.3A
TB21 Input (L1)
F2 Fuse 250VAC 6.3A
CN01 Input L3 L2 L1
Grounding

[ III Outdoor Unit Components ]

CN2 Surge absorber circuit Surge absorber circuit Short circuit Short circuit

[ III Outdoor Unit Components ]

Liquid pipe (Indoor unit side)
Gas pipe (Indoor unit side)
PS1
TH11

LEV1 LEV3
PS3
TH16
Tube in tube heat exchanger
TH15
Gas/Liquid separator

[ III Outdoor Unit Components ]
LEV2 PS1 PS3
TH16

TH11
LEV1
SVM2
Tube in tube heat exchanger
TH12 TH15
Gas/Liquid separator

[ III Outdoor Unit Components ]

Liquid pipe (Indoor unit side)
Gas pipe (Indoor unit side)
TH12

TH15

[ III Outdoor Unit Components ]

Terminal block for power supply
Terminal block for transmission line
Transformer · Relay board · BC controller board

[ III Outdoor Unit Components ]
SW1 SW2 SW5 SW6 SW4

[ III Outdoor Unit Components ]
3. RELAY BOARD (RELAY 10 board)



[1] Functions and Specifications of MA and ME Remote Controllers 83 [2] Group Settings and Interlock Settings via the ME Remote Controller 84 [3] Interlock Settings via the MA Remote Controller 88 [4] Using the built-in Temperature Sensor on the Remote Controller 89



[ IV Remote Controller ]
IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor-outdoor transmission line, and MA remote controller, which is connected to each indoor unit.

Not required (required only by a system with one outdoor unit)*4
Remote controller connection Connectable to any indoor unit in the group
Interlock with the ventilation unit Each indoor unit can individually be in- terlocked with a ventilation unit. (Set up via remote controller in the group.)
Each indoor unit can individually be inter- locked with a ventilation unit. (Set up via remote controller.)
MA remote controller wiring between in- door units requires rewiring.
Either the indoor unit address and remote controller address must both be changed, or the registration information must be changed via MELANS.
*1. MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wire- less remote controller.
*2. Either the MA remote controller or the M-NET remote controller can be connected when a group operation of units in a system with multiple outdoor units is conducted or when a system controller is connected.
*3. M-NET remote controller refers to ME remote controller and ME simple remote controller.
*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.

MA remote controller*1*2 M-NET (ME) remote controller*1*2
There is little likelihood of system expansion and group-
There is a likelihood of centralized installation of remote
ing changes. Grouping (floor plan) has been set at the time of instal-
controllers, system expansion, and grouping changes. Grouping (floor plan) has not been set at the time of in-
stallation. To connect the remote controller directly to the OA pro-
*1. M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and M-NET remote controller are connected.


[ IV Remote Controller ]
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the indoor/outdoor unit address. (A) Group settings Registration of the indoor units to be controlled with the remote controller, and search and deletion of registered information. (B) Interlock settings Registration of LOSSNAY units to be interlocked with the indoor units, and search and deletion of registered information [Operation Procedures] (1) Address settings Register the indoor unit to be controlled with the remote controller.
˚C 1Hr.
CLOCK
ON OFF
Bring up either the blinking display of HO by turning on the unit or the normal display by pressing the ON/OFF button. The display window must look like one of the two figures below to proceed to the next step.
CHECK MODE
FILTER
NOT AVAILABLE STAND BY DEFROST
˚C
TEST RUN
LIMIT TEMP.
TEMP.
A F
CLOCK → ON → OFF
FILTER
G
CHECK TEST
PAR-F27MEA
TIMER SET
E
D
B H
[Blinking display of HO ]
(B) Interlock Settings (A) Group Settings
2 Bring up the Group Setting window. -Press and hold buttons [FILTER] and [ ]
Bring up the Interlock Setting window. -Press button [ ] to bring up the following display. Press again to go back to the Group Setting window as shown under step .
B
G
simultaneously for 2 seconds to bring up the display as shown below.
Both the indoor unit address and interlocked unit address will be displayed together.
Indoor unit address display window Indoor unit address display window
Interlocked unit address display window
To search for an address, go to section (2) Address Search.
Select the unit address.
- Select the address of the indoor unit to be registered by pressing button [TEMP. ( ) or ( )] to advance or go back through the addresses. Register the indoor unit whose address appears on the display.
Bring up the address of the indoor unit and the address of the LOSSNAY to be interlocked on the display. - Select the address of the indoor unit to be registered by pressing button [TEMP. ( ) or ( )] to advance or go back through the addresses. - Select the address of the LOSSNAY unit to be interlocked by pressing button [TIMER SET ( ) or ( )] to advance or go back through the interlocked unit addresses.
- Press button [TEST] to register the indoor unit address whose address appears on the display.
- If registration is successfully completed, unit type will appear on the display as shown in the figure below.
- If the selected address does not have a corresponding indoor unit, an error message will appear on the display. Check the address, and try again.
Make the settings to interlock LOSSNAY units with indoor units. - Press button [TEST] while both the indoor unit address and the address of the LOSSNAY units to be interlocked are displayed to enter the interlock setting. - Interlock setting can also be made by bringing up the LOSSNAY address in the indoor unit address display window and the indoor unit address in the interlocked unit address display window.
Unit type (Indoor unit in this case)
If registration is successfully completed, the two displays as shown on the left will appear alternately. If the registration fails, will blink on the display. (Indicates that the selected address does not have a corresponding unit.)
blinks to indicate a registration error. (Indicates that selected address does not have a corresponding unit.)
To register the addresses for multiple indoor units, repeat steps and above. 3 4
To search for an address, go to section (2) Address Search.
To next page.

[ IV Remote Controller ]
Repeat steps and in the previous page to interlock all the indoor units in a group with the LOSSNAY unit.
(C) To return to the normal display When all the group settings and interlock settings are made, take the following step to go back to the normal display. Press and hold buttons [FILTER] and [ ] simultaneously for 2 seconds to go back to the window as shown in step .
To go back to the normal display, follow step .
To search for an address, go to section (2) Address Search.
To search for the address of indoor units that have been entered into the remote controller, follow steps and .
(A) To search group settings
(B) Interlock setting search
After performing step , proceed as follows:
Bring up the Group Setting window. - Each pressing of button [ ] will bring up the address of a registered indoor unit and its unit type on the display.
Bring up the address of the indoor unit to be searched on the display. - Select the address of the indoor unit to be searched by pressing button [TIMER SET ( ) or ( )] to advance or go back through the interlocked addresses.
Unit type (Indoor unit in this case)
LOSSNAY can be searched in the same manner by bringing up the LOSSNAY address in the Interlocked unit address display window.
Bring up on the display the address of the LOSSNAY unit that was interlocked with the indoor unit in step . - With each pressing of button [ ], the address of the LOSSNAY and indoor unit that is interlocked with it will be displayed alternately.
- When only one unit address is registered, the same address will remain on the display regardless of how many times the button is pressed. - When the address of multiple units are registered (i.e. 011, 012, 013 ), they will be displayed one at a time in an ascending order with each pressing of button [ ] .
Address of an interlocked LOSSNAY unit
To delete an address, go to section (3) Address Deletion.
Bring up the address of another registered unit on the display. - After completing step , a subsequent pressing of button [ ] will bring up the address of another registered unit. (The display method is the same as the one in step .)
To go back to the normal display, follow step .
Address of another interlocked unit
To delete an address, go to section (3) Address Deletion .
The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings. The interlock settings between units can be deleted by deleting the interlock settings. Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the display window. To delete an address, the address must first be bought up on the display.
Delete the registered indoor unit address or the interlock setting between units. - Press button ? [CLOCK ON OFF] twice while either the indoor unit address or the address of the interlocked unit is displayed on the display to delete the interlock setting.

[ IV Remote Controller ]
(A) To delete group settings (B) To delete interlock settings
If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will appear in the unit type display window. In this case, repeat the steps above.
will be displayed in the room temperature display window. - If a transmission error occurs, the selected setting will not be deleted, and the display will appear as shown below. In this case, repeat the steps above.
will be displayed in the room temperature display window.
To go back to the normal display, follow step . 10
(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controller
(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller. Refer to (B) Interlock Settings under section 1 Group Settings/Interlock Settings for operation procedures. Set the address as shown below.
(A) To make group settings Interlocked unit address display window...Remote controller address Indoor unit address display window The address of the indoor unit to be controlled with the remote controller
(B) To make interlock settings Interlocked unit address display window...LOSSNAY address Indoor unit address display window The address of the indoor unit to be interlocked with the LOSSNAY
In the remote controller function selection mode, the settings for four types of functions can be made or changed as necessary.
When making the temperature range setting on the simultaneous cooling/heating type units that supports the automatic operation mode to save on energy consumption, enable the Skip-Auto-Mode setting to make the automatic operation mode unselectable. If the automatic operation mode is selected, the energy-saving function may not work properly.
When connected to the air conditioning units that do not support the automatic operation mode, the setting for the Skip-Auto-Mode, restricted preset temperature range mode (AUTO), and operation mode display selection mode are invalid. If an attempt is made to change the preset temperature range, “LIMIT TEMP.” appears on the display.
[Function selection mode sequence on the remote controller] Normal display
Remote controller function selection mode
*2 Temperature range setting mode (AUTO)
TEMP.
: Press and hold the [CHECK] and [ ] buttons simultaneously for two seconds. : [SET TEMP. ( ) ] button : [SET TEMP. ( ) ] button
Operation mode display selection mode (Display or non-display of the automatic mode)
CLOCKĺONĺOFF
CHECK TEST
Restricted preset temperature range mode (Cooling)
TIMER SET
Restricted preset temperature range mode (Heating)
Room temperature display selection mode *1 : Skip-Auto-Mode is enabled *2 : Skip-Auto-Mode is disabled

[ IV Remote Controller ]
[Operation Procedures] 1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display). 2. Press buttons [CHECK] and [ ] simultaneously for 2 seconds to go into the “Skip-Auto-Mode setting.” under the remote controller function selection mode. Press button [SET TEMP. ( )] or [SET TEMP. ( )] to go into the other four modes under the remote controller function selection mode.
Skip-Auto-Mode setting (Making the automatic operation mode unselectable)
This setting is valid only when the controller is connected to the simultaneous cooling/heating type air conditioning units that support the automatic operation mode.
“ ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches between “ON” and “OFF.”
[TIMER SET ( ) (( ))] button
When set to “ON,” the automatic operation mode is available for selection in the function selection mode. When set to “OFF,” the automatic operation mode is not available for selection in the function selection mode, and an automatic operation cannot be performed. (The automatic operation mode is skipped in the function selection mode sequence.)
Operation mode display selection mode (Changing the type of display that appears during the automatic mode operation)
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
will blink, and either “ON”or “OFF” will light up. Press button [TIMER SET ( ) or ( )] in this state to switch between “ON” and “OFF.”
[TIMER SET ( ) (( ))] button
When it is set to ON, will appear on the display during automatic operation mode. When it is set to OFF, only will appear on the display during automatic operation mode.
Restricted preset temperature range mode (The range of preset temperature can be changed.)
will light up in the display window, and the temperature range for the cooling/dry mode will appear on the display.
[Lower limit temperature]: Appears in the preset temperature display window [Upper limit temperature: Appears in the time display window
Switch between the Lower and Upper limit temperature setting by pressing the [CLOCK-ON-OFF] button. The selected temperature setting blinks.
[TIMER SET ( ) (( ))] button
[The left figure shows the display that appears when the current temperature range setting is between 19 C and 30 C in the Cool/Dry mode, and the lower limit temperature is selected to be set.]
Press button [TIMER SET ( ) or ( )] to set the lower limit temperature to the desired temperature. 4
[Settable range for the lower limit temperature] : 19 C 30 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 30 C 19 C (Settable up to the lower limit temperature that is shown on the display)
“ ” and the settable temperature range for heating appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.
[Settable range for the lower limit temperature] : 17 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 17 C (Settable up to the lower limit temperature that is shown on the display)
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
“ ” and the temperature range for the automatic operation mode appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range. 5 4
[Settable range for the lower limit temperature] : 19 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 19 C (Settable up to the lower limit temperature that is shown on the display)
Room temperature display selection mode (Switching between the display or non-display of room temperature on the controller)
“ 88 C ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches between “ON” and “OFF.”
[TIMER SET ( ) (( ))] button
When set to “ON,” room temperature always appears on the display during operation. When set to “OFF,” room temperature does not appear on the display during operation.
![Page 97 of the Mitsubishi Electronics P96 user manual — [3] Interlock Settings via the MA Remote Controller](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-97.webp?w=400)
[ IV Remote Controller ]
Make this setting only when necessary.
Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to search and delete registered information.
In the following example, the address of the indoor unit is 05 and the address of the LOSSNAY unit is 30.
Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display window on the remote controller must look like the figure below to proceed to step .
2 Press and hold the [FILTER] and [ ] buttons simultaneously for two seconds to perform a search for the LOSSNAY that is interlocked with the indoor unit to which the remote controller is connected.
Search result - The indoor unit address and the interlocked LOSSNAY address will appear alternately.
- Without interlocked LOSSNAY settings
If no settings are necessary, exit the window by pressing and holding the [FILTER] and [ ] buttons simultaneously for 2 seconds. Go to step 1. Registration Procedures to make the interlock settings with LOSSNAY units, or go to step 2. Search Procedures to search for a particular LOSSNAY unit. Go to step 3. Deletion Procedures to delete any LOSSNAY settings.
< 1. Registration Procedures >
To interlock an indoor unit with a LOSSNAY unit, press the [ TEMP. ( ) or ( )] button on the remote controller that is connected to the indoor unit, and select its address (01 to 50). Press the [ CLOCK ( ) or ( )] button to select the address of the LOSSNAY to be interlocked (01 to 50).
Indoor unit address LOSSNAY address
Press the [TEST] button to register the address of the selected indoor unit and the interlocked LOSSNAY unit. - Registration completed The registered indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Registration error If the registration fails, the indoor unit address and the LOSSNAY address will be displayed alternately.
Registration cannot be completed: The selected unit address does not have a corresponding indoor unit or a LOSSNAY unit. Registration cannot be completed: Another LOSSNAY has already been interlocked with the selected indoor unit.
[Operation Procedures]
![Page 98 of the Mitsubishi Electronics P96 user manual — [4] Using the built-in Temperature Sensor on the Remote Controller](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-98.webp?w=400)
[ IV Remote Controller ]
< 2. Search Procedures >
To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it.
Press the [ MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit. - Search completed (With a LOSSNAY connection) The indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Search completed (No interlocked settings with a LOSSNAY exist.)
- The selected address does not have a corresponding indoor unit.
< 3. Deletion Procedures >
Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller that is connected to the indoor unit. Find the address of the LOSSNAY to be deleted (See section 2. Search Procedures. ), and bring up the result of the search for both the indoor unit and LOSSNAY on the display.
Press the [ ON/OFF] button twice to delete the address of the LOSSNAY unit that is interlocked with the selected indoor unit. - Registration completed The indoor unit address and , and the interlocked LOSSNAY address and will appear alternately.
-Deletion error If the deletion fails
on the indoor unit instead. When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.



[1] Electrical Wiring Diagram of the Outdoor Unit 93 [2] Electrical Wiring Diagram of the BC Controller 96 [3] Electrical Wiring Diagram of Transmission Booster 105



[ V Electrical Wiring Diagram ]

4 5 2 1 OFF 4 3 2 1 1 2 4 3 1
*3.Refer to the Data book for connecting input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant
*1.Single-dotted lines indicate wiring not supplied with the unit.
*5.Faston terminals have a locking function.Make sure the terminals
Crankcase heater(for heating the compressor) Current sensor(AC) Magnetic relay(inverter main circuit) Low pressure Discharge pressure

[ V Electrical Wiring Diagram ]

2 1 1 1 3 1 1 2 4 3 2
*3.Refer to the Data book for connecting input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant
*1.Single-dotted lines indicate wiring not supplied with the unit.
*5.Faston terminals have a locking function.Make sure the terminals
Crankcase heater(for heating the compressor) Current sensor(AC) Magnetic relay(inverter main circuit) Low pressure

[ V Electrical Wiring Diagram ]
TH6
TH7
TH3
TH5
63LS
63HS1
TH4
Z25
Z24
TP2
1 CNTYP2
CNTYP5
CNTYP4
CN213
CN212
CN990
CN202
CN201
CN211
CNIT
LED1:Power supply to
S
TB7
M2
P 63H1
CNS2
M1
LED1
M2
ON OFF
SW1 10
CNS2
TB3
M1
ON
OFF
CN102
ON
OFF
SW2 10
1 SWU2
ON
SW3 10
CN40
CN41
3 2 1 1 2 2
LED1
OFF
ON OFF
SW4 10
CN102
CN332
CN2
LED2:CPU in operation
ON
OFF
SW5
LED3:Lit when powered
CNT02
CN3S
CN801
SWU1
CN3N
G
CN3K
CNT01
AC250V
3.15A T
CPU power supply circuit
ZNR01
CNDC
CN72
U
CNAC
CNAC2
CN502
CN503
CN504
CN506
CN507
CN508
CN509
CN510
CH11
SV9
SV2
CNTYP
SC-W
CT22
CN4 3 CN6
LED1:Normal operation(Lit)
SC-V
W
2 CN5
CN21
CN22
THBOX
LED1:Normal
RSH1
3~ MS
LED2:Error
1 CN4
LED3:CPU in
CT12
THHS
SC-L2
CN18V
ZNR1
IPM
U
SC-L3
R5
SC-P1
IGBT
SC-L1
R630
R631
CT3
R1
FT-P
FT-N
R31
R33 R30
R34 R35
DC700V
DCL
SC-P2
P
N
+ - + +
+
F01
4A T
CNVDC
CNINV
CN1
R32
U
W
M
F5
600V 3A F
CNTR2
CNTR3
AC250V
6.3A T
Z5
600V 3A F
CN5
D1 R5
U
CN6
F4
TB23
T02
T03
R4
R6 C17
TB22
L3 L2 L1
*1.Single-dotted lines indicate wiring not supplied with the unit. *2.Dot-dash lines indicate the control box boundaries. *3.Refer to the Data book for connecting input/output signal connectors. *4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant system together.
TB21
CN06
CN07
TB1
CN1B
G G
Z4
U
F3
F2
F1
DSA
R3
R2
R1
CN2
F1,F2,F3
AC250V
6.3A T
Z3
U
Z2
U
Z1
U
CN1A
*5.Faston terminals have a locking function. Make sure the terminals are securely locked
FT-P and FT-N on INV Board has dropped
High pressure protection for the
For opening/closing the bypass
Heat exchanger capacity control
For opening/closing the bypass
For opening/closing the bypass
Control box internal temperature
Crankcase heater(for heating the compressor) Current sensor(AC) Magnetic relay(inverter main circuit) Low pressure Discharge pressure
Heat exchanger low pressure
ACC inlet pipe temperature
in place after insertion. Press the tab
*6.Control box houses high-voltage parts. Before inspecting the inside of the
and confirm that the voltage between
Heat exchanger inlet pipe
on the terminals to removed them.
control box,turn off the power,keep
circuit under the O/S
Liquid pipe temperature Thermistor
the unit off for at least 10 minutes,
*7.Difference of appliance
P72 *7 do not exist
to DC20V or less.
72C 63LS 63HS1
THBOX
Z24,25 THHS
63H1
CH11
DCL
SV2
SV9
TB3 TB1
TB7
TH6 TH5 TH4 TH3
TH7

[ V Electrical Wiring Diagram ]
Fuse AC250V 6.3A F F01 Terminal T1~4
Expansion valve Thermistor sensor Transformer Name Symbol
Terminal block (for power source) TB01
Terminal block (for Transmission) TB02
of switch on CONT.B
2.The initial set values
terminal block.
are as follows.
line to it.
SW2:0
CONT.B
LEV1,3
TR
BREAKER(15A)
SV1B
SV1A
SV1C
SV2B
SV2A
SV2C
SV3B
SV3A
SV3C
SV4B 11
SV4A
SV4C
SVM1
TO NEXT INDOOR UNIT
PULL BOX
FUSE(15A)
~208V-230V 60Hz POWER SUPPLY
T3
T4
T2 1
1
M1 M2 S(SHIELD)
G
TB01
G
CN26
ZNR02 ZNR01
3 5 1 CN12
250VAC 6.3A F
F01
DSA
CN05
1 2 3 4 5 6
3 CN02
1 2 3 2 1
SW5
CN03
SW4
1 2 3 4 5 6
ON
OFF
CN07
OFF
LEV3
CNP3
CN13
CN10
CN11
CONT.B
CNP1
PS1
PS3
TH11
TH12
TH15
TH16

[ V Electrical Wiring Diagram ]
F01 Fuse AC250V 6.3A F
2.The initial set values
of switch on CONT.B
terminal block.
are as follows.
line to it.
SW2:0
LEV1,3
CONT.B
PS1,3
TR
CMB-P106NU-G ONLY F01
SV1C SV1A SV1B
SV2B
SV2C SV2A
SV3A SV3B
SV3C
SV4B
SV4C SV4A
SV5B
SV5A
SV5C
SV6C SV6A SV6B
SVM1
T1
T3
T4
T5
T6
1 T2
1
S(SHIELD)
M1 M2
TO NEXT INDOOR UNIT
BREAKER(15A)
3 CNTR
CN26
FUSE(15A)
PULL BOX
ZNR02
G G
POWER SUPPLY
TB01
1 5 3 6 5 4 3 2 1
ZNR01
CN12
TR
CN02 3
1 2 3 2 1 CN03
DSA
SW2 SW1
SW5
SW4
CN05 CN07
LEV3 LEV1
ON
OFF
ON
OFF
3 CNP3
CN13
CN10
CN11
6 5 4 3 2 1
CNP1
PS1
PS3
TH11
TH12
TH15
TH16

[ V Electrical Wiring Diagram ]
REL.B
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
SV7B
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
3 3 3 1 5 7 1 3 5 7 1 3 5 7 1 3 7 5
T10 T9 T8 T7
16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13
7 6 5 4 3 2 1
SV8B
SV8A
SV8C
CMB-P1010NU-G ONLY
CMB-P1010NU-G ONLY
6 5 4 3 2 1
SV9A
SV9C
CN53
SV10B
SV10A
SV10C
POWER SUPPLY
SVM1
CN39
FUSE(15A) BREAKER(15A)
SV1B
SV1A
SV1C
SV2C SV2A SV2B
SV3C SV3A SV3B
SV4C SV4A SV4B
SV5B
SV5A
SV5C
SV6C SV6A SV6B
TO NEXT INDOOR UNIT
PULL BOX
T1
T3
T4
T5
T6
T2
TB02
S(SHIELD)
M1 M2
G G
L1 TB01
of switch on CONT.B
1 3 CN38 CN26
2.The initial set values
are as follows.
SW1:0
SW2:0
250VAC 6.3A F
CN12
CN50
F01
DSA
7 6 5 4 3 2 1 2 3 4 5 6 7
terminal block.
6 5 4 3 2 1 2 3 4 5 6
line to it.
CN05 CN07
6 5 4 3 2 1 6 5 4 3 2 1
1 2 3 2 1 CN03 CN02
LEV3 LEV1
SW1 SW2
1 8 ON
SW4
SW5
board BC controller REL.B Relay
Fuse AC250V 6.3A F F01
OFF
OFF
3 CNP3
CN13
CN10
CN11
CONT.B
CNP1
TH11,12,15,16
TH11
TH12
TH15
TH16
SV1~10A,B,C
PS1
PS3
LEV1,3
CONT.B
PS1,3
TR

[ V Electrical Wiring Diagram ]
F01 Fuse AC250V 6.3A F
Expansion valve Thermistor sensor Transformer Name Symbol
(for power source) TB01
Terminal block (for Transmission) TB02
SV11A
SV11C
SV12B
SV12A
SV12C
SV13B
SV13A
SV13C
SV14B
SV14A
SV14C
SV15B
SV15A
SV15C
SV16B
SV16A
SV16C
SVM1 2
Relay REL.B
T12
T13
T14
T15
T16
TH11,12,15,16
SV1~16A,B,C
REL.B
LEV1,3
CONT.B
TR
3 X41 1
7 5 3 1 7 5 3 1 7 5 3 1 CN40
CNVCC2 3 1 2
CN39
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
7 5 3 1 3 3
16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13
CN32
SV8B SV8A SV8C
SV9B SV9A SV9C
SV10B
CNOUT2
CNOUT4
SV10A
SV10C
8 7 6 5 4 3 2 1
SV1B
SV1A
SV1C
SV2C SV2A SV2B
SV3C SV3A SV3B
SV4C SV4A SV4B
SV5B
SV5A
SV5C
SV6B
SV6A
SV6C
~208V-230V
FUSE(15A) BREAKER(15A)
T1
T2
T3
T4
T5
T6
1
PULL BOX
TO NEXT
TB01
G G
TB02
S(SHIELD)
M1 M2
1 CNTR
CN38 CN26
ZNR01 ZNR02
1 3 5 CN12
CNOUT1
CNOUT3
F01
250VAC 6.3A F
DSA
1 2 3 2 1 CN03 CN02
TR
SW1 SW2
SW4
SW5
2.The initial set values
of switch on CONT.B
6 5 4 3 2 1 6 5 4 3 2 1
1 ON
OFF
ON
OFF
terminal block.
are as follows.
3 CNP3
CN13
CN10
CN11
line to it.
SW2:0
CONT.B
CNP1
TH11
TH12
TH15
TH16
PS1
PS3

[ V Electrical Wiring Diagram ]
REL.B
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
5 7 1 7 5 1 7 5 3 1 7 5 1 3 3 3
2.The initial set values
of switch on CONT.B
T7 T8 T9 T10
13 14 15 10 11 12 9 7 8 6 5 4 4 8 7 6 5 12 11 10 9 15 14 13 16 16
terminal block.
are as follows.
CN32
CN52
line to it.
SW1:0
SW2:0
SV8A
1 2 3 4 5 6 7
CMB-P1010NU-GA ONLY
SV9B
SV9A
F01 Fuse AC250V 6.3A F T1~10 Terminal Solenoid valve SVM1,2
6 5 4 3 2 1 CN53
Expansion valve Thermistor sensor Transformer Name Symbol
(for power source) TB01
Relay REL.B
SV10C
TH11,12,15,16
CN39
SV1~10A,B,C
1 2 3 4 4 1 2 3
LEV1~3
CONT.B
60Hz ~208V-230V POWER SUPPLY
BREAKER(15A)
SV1C SV1A SV1B
SV2B
SV2A
SV2C
SV3B
SV3A
SV3C
SV4B
SV4A
SV4C
SV5A SV5B
SV5C
SV6B
SV6A
SV6C
TO NEXT INDOOR UNIT
PULL BOX
FUSE(15A)
T1
T2
T3
T4
T5
T6
TB02
S(SHIELD)
M1 M2
G
TB01
G
CN26 CN38
ZNR01 ZNR02
250VAC 6.3A F
7 6 5 4 3 2 1 2 3 4 5 6 7 CN50
DSA
CN12
6 5 4 3 2 1 2 3 4 5 6 CN51
1 2 3 4 5 6 1 2 3 4 5 6
LEV1 LEV3
TR
1 2 3 2 1
SW2 SW1
1 2 3 4 5 6
SW5
LEV2
ON
OFF
ON
OFF
CNP3
CN13
CN10
CN11
CONT.B
CNP1
TH11
TH12
TH15
TH16
PS1
PS3

[ V Electrical Wiring Diagram ]
F01 Fuse AC250V 6.3A F
Expansion valve Thermistor sensor Transformer Name Symbol
(for power source) TB01
Relay REL.B
T1~16 Terminal Solenoid valve
SV11A
SV11C
SV12B
SV12A
SV12C
SV13B
SV13A
SV13C
SV14B
SV14A
SV14C
SV15B
SV15A
SV15C
SV16B
SV16A
SV16C
SVM1
SVM2
T11
T12
T13
T14
T15
T16
TH11,12,15,16
SV1~16A,B,C
LEV1~3
CONT.B
SVM1,2
TR
REL.B
CNVCC2 3 1 2
CN42
CN39
SV7A SV7B
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
7 5 3 1 3 3
16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13
CN32
7 5 3 1 7 5 3 1 7 5 3 1
SV9B SV9A SV9C
SV10B SV10A SV10C
CNOUT2
CNOUT4
8 7 6 5 4 3 2 1
~208V-230V
SV1B
SV1A
SV1C
SV2C SV2A SV2B
SV3C SV3A SV3B
SV4C SV4A SV4B
SV5B
SV5A
SV5C
SV6B
SV6A
SV6C
FUSE(15A) BREAKER(15A)
T1
T2
T3
T4
T5
T6
1
INDOOR UNIT TO NEXT
TB02
S(SHIELD)
M1 M2
G G
L2 L1 TB01 1 3 5 CN12
CN38 CN26
CNTR
ZNR01 ZNR02 CN06
CNOUT1
CNOUT3
F01
250VAC 6.3A F
block.Never connect power line
2.The initial set values of switch
on CONT.B are as follows.
1 2 3 2 1 CN02
SW1 SW2
SW4
SW5
1 ON
OFF
ON
OFF
6 5 4 3 2 1
CN13
CN10
CN11
CN07
CN05
LEV1
SW1:0
SW2:0
CONT.B
6 5 4 3 2 1
5 4 3 2 1
to it.
LEV2
TH11
TH12
TH15
TH16
PS1
PS3

[ V Electrical Wiring Diagram ]
Fuse AC250V 6.3A F F01 Terminal T1~4
Expansion valve Thermistor sensor Transformer Name Symbol
(for power source) TB01
2.The initial set values
of switch on CONT.B
terminal block.
are as follows.
line to it.
SW2:0
TH12,15
CONT.B
LEV3
TR
BREAKER(15A)
SV1B
SV1A
SV1C
SV2B
SV2A
SV2C
SV3B
SV3A
SV3C
SV4B 11
SV4A
SV4C
TO NEXT INDOOR UNIT
PULL BOX
G G FUSE(15A)
POWER SUPPLY
T1
T2
T3
T4
~208V-230V
1
TB01
CN26
CNTR
ZNR02 ZNR01
3 5 1 CN12
250VAC 6.3A F
F01
DSA
TR
CN02
1 2 3 2 1
CN03
SW4
SW5
1 ON
1 2 3 4 5 6
ON
OFF
CN07
LEV3
CN13
CN10
CN11
CONT.B
TH12
TH15

[ V Electrical Wiring Diagram ]
F01 Fuse AC250V 6.3A F Terminal T1~8
Expansion valve Thermistor sensor Transformer Name Symbol
(for power source) TB01
Relay REL.B
REL.B
TH12,15
CONT.B
LEV3
TR
SV7B
4 3 2 1 4 3 2 1
4 3 2 1 4 3 2 1
3 1 5 7 1 3 5 7 1 3 5 7 1 3 7 5
16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13
SV7C
CN32
CN52
SV8B
SV8A
7 6 5 4 3 2 1 CN39
SV8C
2.The initial set values
of switch on CONT.B
terminal block.
are as follows.
line to it.
SW2:0
G 60Hz ~208V-230V POWER SUPPLY
SV1B
SV1A
SV1C
SV2C SV2A SV2B
SV3C SV3A SV3B
SV4C SV4A SV4B
SV5B
SV5A
SV5C
SV6C SV6A SV6B
TO NEXT INDOOR UNIT
PULL BOX
T1
T2
T3
T4
T5
T6
M1 M2 S(SHIELD) TB02
G
TB01
1 CNTR
1 3 CN38 CN26
ZNR02 ZNR01
F01
250VAC 6.3A F
CN12
CN50
DSA
7 6 5 4 3 2 1
TR
SW1 SW2
1 8 ON
SW4
SW5
ON
OFF
OFF
CN07
6 5 4 3 2 1
CN10
CN11
LEV3
CONT.B
TH12
TH15

[ V Electrical Wiring Diagram ]
(for power source) TB01
Fuse AC250V 6.3A F F01
Terminal T1~T16 Solenoid valve SV1~16A,B,C TB02 Terminal block
SV12A
SV12C
SV13B
SV13A
SV13C
SV14B
SV14A
SV14C
SV15B
SV15A
SV15C
SV16B
SV16A
SV16C
SV11B
SV11A
SV11C
(Symbol explanation)
T12
T13
T14
T15
T16
TH12,15
CONT.B REL.B
LEV3
TR
3 1 2 3 CNVCC2
CN40
CN42
4 3 2 1 4 3 2 1
SV7B
1 2 3 4
7 5 3 1
T10 T9 T8 T7
5 4 4 5 16 16 13 14 15 9 10 11 12 6 7 8 6 8 7 9 12 11 10 15 14 13
CN32
SV8B
1 2 3 4
1 3 5 7
SV8C
REL.B
SV9B
1 2 3 4
4 3 2 1
1 3 5 7
SV9C
1 2 3 4
4 3 2 1
1 3 5 7
CNOUT4
SV10B
SV10A
SV10C
8 7 6 5 4 3 2 1
~208V-230V
FUSE(15A) BREAKER(15A)
SV1C
SV2C
SV3C
SV4C
SV5C
SV6C
SV1B
SV1A
SV2B
SV2A
SV3B
SV3A
SV4B
SV4A
SV5B
SV5A
SV6B
SV6A
T1
T2
T3
T4
T5
T6
PULL BOX
INDOOR UNIT
TO NEXT
G G
TB01
2.The initial set values of swith on CONT.B are as follows.
CN26
SW1:0
SW2:0
ZNR01 ZNR02
3 1 CN38
U U
250VAC 6.3A F
LD1:CPU in
CNOUT3
F01
CONT.B
DSA
CN12
block.Never connect power line
1 1 1 3 2 3 2 2 CN02 CN03
1 8 SW5
SW4
SW6
ON
OFF
ON
OFF
ON
OFF
CN10 4
CN11
CN07
TH15 1
to it.
TH12
LEV3

[ V Electrical Wiring Diagram ]
Terminal block for power supply (TB1)
L Red Red Red
100V/200VAC
E
U
U
DSA
CN2 CN1
White Blue Red Red
1 2 1 2
Terminal block 2 for transmission line (TB3) Expanded (indoor unit) side
CN4
B
CN1 Electronic control board
S
Terminal block 1 for transmission line (TB2) Expanded (outdoor unit) side
A

- 106 -
![Page 116 of the Mitsubishi Electronics P96 user manual — [1] Refrigerant Circuit Diagram ...........................................................................................109 [2] Principal Parts and Functions ........................................................................................116](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-116.webp?w=400)

- 108 -

[ VI Refrigerant Circuit ]



[ VI Refrigerant Circuit ]


[ VI Refrigerant Circuit ]


[ VI Refrigerant Circuit ]


[ VI Refrigerant Circuit ]


[ VI Refrigerant Circuit ]



[ VI Refrigerant Circuit ]


[ VI Refrigerant Circuit ]
Symbols (functions) Notes Usage Specifications Check method
Adjusts the amount of circulating refrigerant by adjusting the operat- ing frequency based on the oper- ating pressure data
P72 model Low-pressure shell scroll compressor Wirewound resistance 20°C[68°F] : 0.268ohm (THMU) 0.981ohm (YHMU) P96, P120 models Low-pressure shell scroll compressor Wirewound resistance 20°C[68°F] : 0.161ohm (THMU) 0.583ohm (YHMU)
63HS1 1) Detects high pressure 2) Regulates frequency and pro- vides high-pressure protec- tion
Pressure 0~4.15 MPa [601psi] Vout 0.5~3.5V 0.071V/0.098 MPa [14psi] Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145
GND (Black) Vout (White) Vcc (DC5V) (Red)
63LS 1) Detects low pressure 2) Provides low-pressure pro- tection
Pressure 0~1.7 MPa [247psi] Vout 0.5~3.5V 0.173V/0.098 MPa [14psi] Pressure [MPa] =0.566 x Vout [V] - 0.283 Pressure [psi] =(0.566 x Vout [V] - 0.283) x 145
GND (Black) Vout (White) Vcc (DC5V) (Red)
63H1 1) Detects high pressure 2) Provides high-pressure pro- tection
4.15MPa[601psi] OFF setting
Degrees Celsius Resistance check
R = 7.465k 120 R = 4057 R = 7.465
4057 273 t 1 393 1 exp
0°C[32°F] :698kohm 10°C[50°F] :413kohm 20°C[68°F] :250kohm 30°C[86°F] :160kohm 40°C[104°F] :104kohm 50°C[122°F] : 70kohm 60°C[140°F] : 48kohm 70°C[158°F] : 34kohm 80°C[176°F] : 24kohm 90°C[194°F] :17.5kohm 100°C[212°F] :13.0kohm 110°C[230°F] : 9.8kohm

[ VI Refrigerant Circuit ]
Symbols (functions) Notes Usage Specifications Check method
Controls defrosting during heating operation
R = 15k 0 R = 3460 R = 15
t 3460 273 t 1 273 1 exp
0°C[32°F] :15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm
TH5 Fan operated on the 63LS and TH5 values.
TH6 Controls defrosting during heating operation
THHS Inverter heat sink tem- perature
Controls inverter cooling fan based on THHS temperature
R = 17k 50 R = 4016 R = 17
t 4016 273 t 1 323 1 exp
THBOX Control box in- ternal tempera- ture detection
0°C[32°F] :161kohm 10°C[50°F] :97kohm 20°C[68°F] :60kohm 25°C[77°F] :48kohm 30°C[86°F] :39kohm 40°C[104°F] :25kohm
AC208 - 230V Open while being powered/ closed while not being pow- ered
Continuity check with a tester
SV4a - SV4d Heat exchanger capacity control
Controls outdoor unit heat ex- changer capacity
SV5b Heat exchanger capacity control
Prevents high-pressure-rise Controls defrost cycle
AC208 - 230V Closed while being powered/ open while not being powered
SV5c Allows the refrigerant to pass through the bypass pipe to pre- vent an accumulation of liquid re- frigerant
AC208 - 230V Open while being powered/ closed while not being pow- ered
SV9 High-pressure-rise prevention AC208 - 230V Open while being powered/ closed while not being pow- ered
Heater CH11 Heats the refrigerant in the com- pressor
Cord heater P72 model 1035 ohm 51W P96, P120 models 928 ohm 57W
21S4a Changeover between heating and cooling
Continuity check with a tester

[ VI Refrigerant Circuit ]
Symbol (functions) Notes Usage Specification Check method
LEV 1) Adjusts superheat at the indoor heat exchanger outlet during cooling 2) Adjusts subcool at the heat exchanger outlet of the indoor unit during cooling
DC12V Opening of stepping motor driving valve 0-(1400) puls- es
Refer to the section "Continuity Test with a Tester". Continuity between white, red, and or- ange. Continuity between yellow, brown, and blue.
TH1 (Suction air temperature)
Indoor unit control (Thermo)
R0=15k R0/80=3460 Rt = 15exp{3460( - )} 1 273
0°C [32°F]:15kohm 10°C [50°F] :9.7kohm 20°C [68°F]:6.4kohm 25°C [77°F] :5.3kohm 30°C [86°F] :4.3kohm 40°C [104°F] :3.1kohm
TH3 (Gas pipe temperature)
LEV control during cooling op- eration (superheat detection)
TH4 Outdoor air temperature)
Indoor unit control (Thermo)
Temperature sensor (In- door air tem- perature)
Indoor unit control (Thermo)

[ VI Refrigerant Circuit ]
Part name Symbols (functions)
Part code Usage Specifications Check method
PS1 (High pres- sure side)
Pressure 0~4.15 MPa [601psi] Vout 0.5~3.5V 0.071V/0.098 MPa [14psi] Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145
GND (Black) Vout (White) Vcc (DC5V) (Red)
Thermistor TH11 (Liquid inlet tempera- ture)
LEV control (Liquid level control)
R = 15k 0 R = 3460 R = 15
t 3460 273 t 1 273 1 exp
TH12 (Bypass outlet tem- perature)
TH15 (Bypass in- let tempera- ture)
TH16 (Liquid re- frigerant tempera- ture)
SVM1 Opens during cooling and de- frost modes
Continuity check with a tester SV A Provides refrigerant to indoor unit in cooling operation
AC208-230V Open while being powered/ closed while not being pow- ered
SV B Provides refrigerant to indoor unit in heating operation
SV C Provides refrigerant to indoor unit in cooling operation
LEV LEV1 1) Liquid level control 2) Pressure differential con- trol
Same as indoor LEV LEV3
DC12V Opening of a valve driven by a stepping motor 0-2000 pulses

[ VI Refrigerant Circuit ]
Part name Symbols (functions)
Part code Usage Specifications Check method
PS1 (High pres- sure side)
Pressure 0~4.15 MPa [601psi] Vout 0.5~3.5V 0.071V/0.098 MPa [14psi] Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145
GND (Black) Vout (White) Vcc (DC5V) (Red)
Thermistor TH11 (Liquid inlet tempera- ture)
LEV control (Liquid level control)
R = 15k 0 R = 3460 R = 15
t 3460 273 t 1 273 1 exp
TH12 (Bypass outlet tem- perature)
TH15 (Bypass in- let tempera- ture)
TH16 (Liquid re- frigerant tempera- ture)
SVM1 Opens during cooling and de- frost modes
Continuity check with a tester SVM2 Pressure differential control
AC208-230V Open while being powered/ closed while not being pow- ered
SV A Provides refrigerant to indoor unit in cooling operation
SV B Provides refrigerant to indoor unit in heating operation
SV C Provides refrigerant to indoor unit in cooling operation
DC12V Opening of a valve driven by a stepping motor 0-2000 pulses
Same as indoor LEV

[ VI Refrigerant Circuit ]
Part name Symbols (functions)
Part code Usage Specifications Check method
Thermistor TH12 (Bypass outlet tem- perature)
R = 15k 0 R = 3460 R = 15
t 3460 273 t 1 273 1 exp
TH15 (Bypass in- let tempera- ture)
SV A Provides refrigerant to indoor unit in cooling operation
Continuity check with a tester SV B Provides refrigerant to indoor unit in heating operation
AC208-230V Open while being powered/ closed while not being pow- ered
SV C Provides refrigerant to indoor unit in cooling operation
LEV LEV3 Pressure differential control DC12V Opening of a valve driven by a stepping motor 0-2000 pulses
Same as indoor LEV

[ VI Refrigerant Circuit ]
Part name Symbols (functions)
Part code Usage Specifications Check method
Thermistor TH12 (Bypass outlet tem- perature)
R = 15k 0 R = 3460 R = 15
t 3460 273 t 1 273 1 exp
TH15 (Bypass in- let tempera- ture)
SV A Provides refrigerant to indoor unit in cooling operation
Continuity check with a tester SV B Provides refrigerant to indoor unit in heating operation
AC208-230V Open while being powered/ closed while not being pow- ered
SV C Provides refrigerant to indoor unit in cooling operation
LEV LEV3 Pressure differential control DC12V Opening of a valve driven by a stepping motor 0-2000 pulses
Same as indoor LEV

[1] Functions and Factory Settings of the Dipswitches 125 [2] Controlling the Outdoor Unit 132 [3] Controlling BC Controller 145 [4] Operation Flow Chart 146

- 124 -

[ VII Control ]
Function according to switch setting Switch setting timing
setting Note.2
SWU 1-2 Unit address setting Set to 00 or 51-100 with the dial switch Before power on C C
SW1 1-10 For self-diagnosis/ operation monitoring
Refer to the LED monitor display on the outdoor unit board. Anytime after power on C C
Without connection to the centralized controller
With connection to the centralized con- troller
1 Centralized control switch
2 Deletion of connec- tion information Normal control Deletion Before power on A -
(OC) Storage of IC/ OC error history
(OC) Deletion of IC/ OC error history Anytime after power on (When switched from OFF to ON)
3 Deletion of error his- tory SW
(OS) Storage of OS error history
(OS) Deletion of OS error history
After being energized and while the compressor is stopped
4 Pump down mode Normal control Pump down mode
Anytime af- ter power on (When switched from OFF to ON)
10 minutes after com- pressor startup
7 Forced defrost (Note 3) Normal control Forced defrost starts
8 Defrost timer setting (Note 3) 50 minutes 90 minutes Anytime after power on (When switched from OFF to ON)
9 Target evaporating temperature setting 0°C [32°F] -2°C [28°F] /-4°C [25°F] /-6°C [21°F]
Anytime after power on (When switched from OFF to ON)
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made. 3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 132) 4) Target evaporating temperature will change as shown in the table below each time SW2-9 is turned ON and OFF.
SW2-9 OFF → ON → OFF → ON → OFF → ON
0 [32 ] [32 ] [32 ] [25 ] -2 [28 ]

[ VII Control ]
Function according to switch setting Switch setting timing
setting Note.2
After power on and when SW3-1 is on.
-10°C [14°F] -5°C [23°F] Anytime after power on
3 Defrost start temper- ature
10°C [50°F] 15°C [59°F] Anytime after power on (except during defrost op- eration)
4 Defrost end temper- ature
SW3
6 Temperature unit setting Centigrade Fahrenheit Anytime after power on C C
7 Target condensing temperature setting for heating
49°C [120°F] 53°C [127°F] -
9 Model setting (To change the ex- ternal static pressure setting)
Outdoor standard static pressure
Outdoor high static pressure Before being energized
10 Model setting (To change the ex- ternal static pressure setting)
High static pressure 60Pa High static pressure 30Pa Before being energized
1 Enable/disenable high sensible opera- tion
High sensible heat operation mode Before being energized A -
Anytime after being ener- gized (except during ini- tial startup mode. Automatically cancelled 90 minutes after com- pressor startup)
3 Refrigerant amount adjustment
Refrigerant amount adjust mode
4 Low-noise mode/ step demand switch- ing
Low-noise mode (Note 3) Step demand mode Before being energized
Cumulative com- pressor operation time data is re- tained.
Cumulative com- pressor operation time data is delet- ed.
6 Cumulative com- pressor operation time data deletion
Anytime after power on (when the unit is turned on)
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made. 3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed A setting of CN3D is required.(page 23)

[ VII Control ]
Function according to switch setting Switch setting timing
setting Note.2
5 Low-noise mode selection
Capacity priority mode(Note 3) Low-noise mode Before being energized A -
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made. 3) When set to the capacity priority mode and if the following conditions are met, the quiet mode will terminate, and the unit will go back into the normal operation mode. Cooling-only/Cooling-main: Outside temperature is high or high pressure is high. Heating-only/Heating-main: Outside temperature is low or low pressure is low. (page 22)
(2) INV board 1) PURY-P72, P96, P120YHMU-A, PURY-P72THMU-A Functions are switched with the following connector.
Function according to connec-
Enabled Disabled Enabled Disabled
Enabling/disabling the following error detection functions; ACCT sensor failure (5301 Detail No. 115) ACCT sensor circuit failure (5301 Detail No.117) IPM open/ACCT erroneous wiring (5301 Detail No. 119) Detection of ACCT erroneous wiring (5301 Detail No.120)
Error detec- tion disable (No load op- eration is pos- sible.)
Anytime after power on
CN6 short-circuit connector is mated with the mating connector. Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.

[ VII Control ]
Function according to switch
setting Switch setting timing
SW1 1 Enabling/disabling the following error detection functions; ACCT/DCCT sensor failure (5301 Detail No. 115, 116) ACCT/DCCT sensor circuit failure (5301 Detail No.117,118) IPM open/Disconnected CNCT2 (5301 Detail No. 119) Detection of erroneous wiring (5301 Detail No.120)
Error detec- tion disable (No load op- eration is pos- sible.)
Anytime after power on
All are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where indicated by "-," which may
be set to a certain setting for a reason. Leave SW1-1 to OFF during normal operation. If it is set to ON, errors cannot be detected and the unit may be damaged.
Switch Function · Error detec- tion enabled

[ VII Control ]
Switch Function Function according to switch setting
OFF ON
Room temperature detection position
Built-in sensor on the remote controller
Set to ON (built-in sensor on the remote controller) on All Fresh (PEFY-VMH-F) model units
Filter check reminder time setting
Always set to OFF on PKFY-AM model units
Always on while in the heating mode
Fan speed setting for Heating Thermo-OFF Very Low Low
Forced heating operation at OA temp of 5 C or below
Applicable to All Fresh model units (PEFY-VMH-F) only
According to the SW1-7 setting
Fan speed setting for Heating Thermo-OFF
Applicable to All Fresh model units (PEFY-VMH-F) only
While the unit is stopped (Remote controller OFF)
Self-recovery after power failure
Always set to OFF on PKFY-VAM model units
Vane angle limit setting for cooling operation
Always set to Downblow B or C on PKFY-VAM model units
Automatic LEV value conversion function
Heating 4 C[7.2 F] up
Set to OFF on floor-standing (PFFY) type units
SHm setting 2 The setting depends on the model and type.
The setting depends on the model and type.
SCm setting 10 15
Note 2. If both SW1-7 and SW1-8 are set to ON, the fan remains stopped during heating Thermo-OFF. To prevent incorrect temperature detection due to a build-up of warm air around the indoor unit, use the built-in temperature sensor on the remote controller (SW1-1) instead of the one on the indoor unit inlet thermistor. Note 3. By setting SW3-1, SW1-7, and SW1-8 to a certain configuration, the fan can be set to remain stopped during cooling Thermo-OFF. See the table below for details.
Fan speed during Thermo-OFF
SW1-7 SW1-8 Heating Cooling Cooling-only/heat pump
OFF OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON

[ VII Control ]
Actual indoor unit address setting varies in different systems. Refer to the installation manual for the outdoor unit for details on how to make the address setting. Each address is set with a combination of the settings for the 10's digit and 1's digit. (Example) When setting the address to "3", set the 1's digit to 3, and the 10's digit to 0. When setting the address to "25", set the 1's digit to 5, and the 10's digit to 2.
The SW is located at the bottom of the remote controller under the cover. Operate the switches to perform the remote con- troller main/sub setting or other function settings. Normally, do not change the settings of switches other than the SW1 (main/ sub switching switch). (All the switches are set to "ON" at factory setting.)
Remote controller Switching switch
Operation by switch settings Switch setting timing ON OFF
Remote controller main/sub setting
Before power on When two remote controllers are connected to one group, set either of the remote controllers to "Sub".
When the program timer (only few stock products are available) is connected, set to "Timer mode startup" to resume the operation with timer mode after power is restored.
At power on of the remote controller
When the automatic mode is set and the "Cooling"/"Heating" display is not necessary, set to "Not displayed".
3 Cooling/heating display set by automatic setting Displayed Not displayed
When the suction temperature (discharge temperature) display is not necessary, set to "Not displayed".
4 Suction temperature display (discharge temperature display) Displayed Not displayed
The MA remote controller (PAR-21MAA) does not have the switches listed above. Refer to the installation manual for the func- tion setting.

[ VII Control ]
Set the address of the remote controller with the rotary switch.
10's digit 1's digit (left) (right)
Address setting range Setting method
Main remote controller 101-150 Add 100 to the smallest address of all the indoor units in the same group.
Sub remote controller 151-200 Add 150 to the smallest address of all the indoor units in the same group.
Setting of rotary switch Address No.
01-99*1 101-199 with the 100's digit automatically being set to 1*2
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is automatically set to [2].
To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (w)], and do not apply than 19.6N. The use of any other tool or applying too much load may damage the switch.
Function according to switch setting
Switch setting timing OFF ON
1 Model setting R410A - Always leave this switch to OFF.
6 No. of ports *1
1 2 Before being energized
7, 8 -
*1. When a junction pipe kit was used to merge two ports to connect the indoor units with a total capacity of between P31 and P54, turn DIP SW4-6 to ON. When connecting a main and a sub BC controller, change the SW setting on only the main BC controller. (It is not necessary to change the SW setting on the sub BC controller. )
Rotary switch · Remote controller unit · Switch Function

[ VII Control ]
-1Outline of Control Method
The outdoor units are designated as OC and OS in the order of capacity from large to small (if two or more units have the
same capacity, in the order of address from small to large). The setting of outdoor unit can be verified by using the self-diagnosis switch (SW1).
1 2 3 5 4 6 7 8 9 10 The unit is designated as the OC: “oc” appears on the display. The unit is designated as OS: “oS” appears on the display
The OC determines the operation mode and the control mode, and it also communicates with the indoor units. The OS exercises autonomous distributed control (over defrost, error detection, and actuator control etc.) according to the
operation/control mode signals that are sent from the OC.
At the initial startup, outdoor units start up in the order of "OC and OS." Startup sequence rotation is performed while all the indoor units are stopped. (Even after two hours of operation, startup se-
quence rotation is not performed while the compressor is in operation.) In a system with multiple outdoor units (OC and OS), when the integrated operation time of the unit in operation (either OC or OS) reaches one hour during a cooling operation at low outside temperature, that unit will stop and the other unit will go into operation. Refer to [-10-Control at Initial Start-up] for the initial startup. Performing startup sequence rotation does not change the basic operation of OC and OS. Only startup sequence is changed. Startup sequence of the outdoor units can be checked with the self-diagnosis switch (SW1) on the OC.
1 2 3 5 4 6 7 8 9 10
OC→OS: “oc” and the “OC” address appear alternately on the display. OS→OC: “oS” and the “OS” address appear alternately on the display. ON
When the power is turned on, the initial processing of the microcomputer is given top priority. During the initial processing, control processing of the operation signal is suspended. (The control processing is resumed after
the initial processing is completed. Initial processing involves data processing in the microcomputer and initial setting of each of the LEV opening. This process will take up to 5 minutes.) During the initial processing, the LED monitor on the outdoor unit's control board displays S/W version -> refrigerant type
-> heat pump -> cooling only and capacity -> and communication address in turn every second.
The upper limit of frequency during the first 3 minutes of the operation is 50 Hz. When the power is turned on, normal operation will start after the initial start-up mode (to be described later) has been com-
pleted (with a restriction on the frequency).

[ VII Control ]
Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions.
ON OFF
When each indoor unit compressor startup ON for 4 minutes.
After the restoration of thermo or 3 minutes after restart
ON for 4 minutes.
During cooling or heating operation with the compressor stopped
After the operation has stopped ON for 3 minutes. Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
During defrost operation ON
While the compressor is operating at the minimum frequency and when the low pres- sure (63LS) drops (3 or more minutes after compressor startup)
When low pressure (63LS) drops below 0.23MPa[33psi].
When low pressure (63LS) ex- ceeds 0.38MPa[55psi].
When high pressure (63HS1) rises When 63HS1 exceeds 3.62MPa[525psi] When 63HS1 is or below 3.43MPa[497psi] and 30 seconds have passed
ON OFF
When high pressure (63HS1) rises during the heating operation
When 63HS1 exceeds 3.50MPa
When SV5b is ON and the pressure
is 2.70MPa[391psi]or below
ON OFF
When high pressure (63HS1) rises during the heating operation
When SV5b is OFF and the pres- sure is 3.50MPa[507psi]or below
When 63HS1 exceeds 2.70MPa [391psi]
When startup or resuming operation after a defrost cycle
During defrost cycle ON
ON OFF
When high pressure (63HS1) rises during the heating operation
When SV2 is OFF and the pressure is 2.70MPa[391psi]or below
When SV9 is ON and the pressure is 3.50MPa[507psi]or below
During defrost cycle ON (open)
When returning to normal operation after completion of the defrost cycle
ON for 5 minutes and goes OFF

[ VII Control ]
ON OFF
While the unit is stopped Always ON
Cooling mode When one or more of the following valves is turned OFF: SV4a through SV4c.
When the condition on the left is not met
Depending on the capacity required, the frequency of the compressor is controlled to keep constant evaporation temperature
(0°C [32°F] = 0.71 MPa [103 psi]) during cooling operation, and condensing temperature (49°C [120°F] = 2.88 MPa [418 psi]) during heating operation. The table below summarizes the operating frequency ranges of the inverter compressor during normal operation. The OS in the multiple-outdoor-unit system operates at the actual compressor frequency value that is calculated by the OS
based on the preliminary compressor frequency value that the OC determines.
Frequency/cooling (Hz) Frequency/heating (Hz)
Max Min Max Min
P72 model 43 14 48 19
P96 model 65 18 71 15
P120 model 75 18 85 15
The maximum frequency during heating operation is affected by the outdoor air temperature to a certain extent.
The upper limit of high pressure (63HS1) is preset, and when it exceeds the upper limit, the frequency is decreased every 15 seconds. The actuation pressure is when the high-pressure reading on 63HS1 is 3.58MPa[519psi].
Discharge temperature (TH4) of the compressor in operation is monitored, and when it exceeds the upper limit, the frequency is decreased every minute. Operating temperature is 115°C [239°F].
Frequency control other than the ones performed at start-up, upon status change, and for protection is called periodic frequen- cy control (convergent control) and is performed in the following manner. Periodic control cycle Periodic control is performed after the following time has passed 30 seconds after either compressor start-up or the completion of defrost operation 30 seconds after frequency control based on discharge temperature or pressure limit
The amount of frequency change The amount of frequency change is controlled to approximate the target value based on the evaporation temperature (Te) and condensing temperature (Tc).
Operation SV5c · Others Always OFF · Model

[ VII Control ]
The defrost cycle starts when the pipe temperature (TH6), in the following table, or below has continuously been detected for
3 minutes after the integrated compressor operation time of 50 minutes have passed. If 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced defrost operation
will start by turning on the forced defrost switch (DIP SW2-7). Even if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation will be 50 minutes
if defrosting took 12 minutes. In the multiple-outdoor-unit system, all of the outdoor units that are in operation go into the defrost mode simultaneously. The
unit(s) that is stopped at the time defrost operation starts remains stopped.
SW3 - 3 OFF SW3 - 3 ON
P72 model - 10°C [14°F] - 5°C [23°F]
P96 model - 8°C [18°F] - 5°C [23°F]
P120 model - 8°C [18°F] - 5°C [23°F]
Outdoou unit Compressor frequency Model Compressor frequency
P72 model 60 Hz
P96 model 65 Hz
P120 model 65 Hz
Outdoor unit fan Stopped
SVM2 OFF
SV B OFF
SV A Ports that are connected to the indoor units in cooling Thermo-ON

[ VII Control ]
The defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperature (TH3
and TH6) has been continuously detected for 2 minutes that exceeds the values in the table below Defrost operation will not stop its operation for 4 minutes once started. In the multiple-outdoor-unit system, defrosting is stopped on all units at the same time.
SW3 - 3 OFF SW3 - 3 ON
P72 model 10°C [50°F] 15°C [59°F]
P96 model 7°C [45°F] 12°C [54°F]
P120 model 7°C [45°F] 12°C [54°F]
If a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on the
integrated compressor operation time will be set to 20 minutes.
Even when there is a change in the number of operating indoor units during defrost operation, the operation will continue, and
an adjustment will be made after the completion of the defrost operation. Defrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its course.
Refrigerant recovery is performed for each BC port during heating operation to prevent the refrigerant from accumulating in- side the units that are stopped (in the fan mode), in the cooling mode, or in the heating Thermo-OFF mode. It is also performed during cooling operation to prevent an excessive amount of refrigerant from accumulating in the outdoor heat exchanger.
Starting criteria for the refrigerant recovery cycle (during Cooling-only, Cooling-main, Heating-only, or Heating-main mode) The refrigerant recovery mode starts when all of the following conditions are met: 1) When 5 minutes have passed in the Heating-only or Heating-main mode or 30 seconds have passed in the Cooling-only or Cooling-main mode since the completion of the previous refrigerant recovery cycle AND the when following conditions are met. TH4 > 105°C [221°F] 2) When the port is not in the 4-minute restart delay mode
Starting criteria for the refrigerant recovery cycle (during Cooling-only, Cooling-main, Heating-only, or Heating-main mode) 1) When the port is in the cooling Thermo-OFF, fan, or stop mode SV C at the port turns on for 30 seconds. ( indicates port No.)
Depending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter to keep a constant
condensing temperature of (outside temperature +10°C [50°F]) during cooling operation and a constant evaporation temper- ature of (0°C [32°F] =0.71
based on the preliminary outdoor unit fan control value that the OC determines.
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor). The fan operates at full speed for 5 seconds after start-up.(Only when TH7
Model

[ VII Control ]
SV4a SV4b SV4c SV4d SV5c
P72 model Cooling- only Cooling- main
2 OFF OFF - OFF ON
3 OFF ON - OFF ON
4 ON OFF - OFF ON
5 ON ON - OFF OFF
Heating- only 1 ON ON - OFF OFF
2 ON ON - OFF OFF
Defrost 1 ON ON - OFF OFF
P96, P120 models Cooling- only Cooling- main
2 OFF OFF OFF OFF ON
3 OFF OFF ON OFF ON
4 OFF ON ON OFF ON
5 ON ON ON OFF OFF
Heating- only 1 ON ON ON OFF OFF
2 ON ON ON OFF OFF
Defrost 1 ON ON ON OFF OFF

[ VII Control ]
When started up for the first time before 12 hours have elapsed after power on, the unit goes into the initial startup mode. At the completion of the initial operation mode on the OC and OS, they will go into the normal control mode.
Initial startup mode starts.
Completed in the integrated operation time of 35 minutes.
or F < 50Hz
Completed in the integrated operation time of 90 minutes.
Initial startup mode complete
Initial startup mode starts.
The compressor on the OC starts up.
*1 Qj:Total capacity (models) code
The total operating load of the indoor unit after 5 minutes of operation is P96 or above.
(*1 Qj 50)
The compressor on the OC starts up.
The compressor on the OC remains in operation, and the compressor on the OS starts up.
50 F 60Hz (OC)
50 F 60Hz (both OC and OS)
or F < 50Hz (OC) Completed in the integrated operation time of 35 minutes.
or F < 50Hz (both OC and OS) Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
Completed in the integrated operation time of 90 minutes.
Both the OC and OS stop.
The startup sequence of the OC and OS is rotated.
The compressor on the OS starts up.
50 F 60Hz (OS)
or F < 50Hz (OS) Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
*2 The air conditioning load is too small for both the OC and the OS to simultaneously stay in operation.
Initial startup mode complete
*3 The air conditioning load is high enough for both OC and OS to simultaneously stay in operation.

[ VII Control ]
the other outdoor unit in the system malfunctions. This mode can be started by performing an error reset via the remote controller.
(1) Starting the emergency operation 1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller. 2) The error is reset using the remote controller. 3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation starts. 4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting the error via the remote controller.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Trouble source Error codes that permit an emergency operation Error code description
0403 4220, 4225 4230 4240 4250, 4255 5110 5301 5102 5103 5104 5105 5106 5107
Serial communication error Bus voltage drop Heatsink overheat protection Overload protection Overcurrent relay trip Heatsink temperature sensor failure (THHS) Current sensor/circuit failure Subcool heat exchanger bypass outlet temperature sensor failure Pipe temperature sensor failure Discharge temperature sensor failure Accumulator inlet temperature sensor failure Subcool heat exchanger liquid outlet sensor failure Outside air temperature sensor failure
Compressor Fan motor Inverter
Power supply sync signal abnormality
Emergency operation pattern (2 outdoor units)
OC failure pattern Trouble Normal
OS
Maximum total capacity of indoor units (Note 1)
(2) Ending the emergency operation 1) End conditions When one of the following conditions is met, emergency operation stops, and the unit makes an error stop. When the integrated operation time of compressor in cooling mode has reached four hours. When the integrated operation time of compressor in heating mode has reached two hours. When an error is detected that does not permit the unit to perform an emergency operation.
troller. If another error reset is performed at the completion of an emergency mode, the unit repeats the procedures in section (1)
above. To stop the emergency mode and perform a current-carrying operation after correcting the error, perform a power reset.

[ VII Control ]
(1) Starting the emergency operation (When the OC is in trouble) 1) When an error occurs, the error source and the error code appear on the display on the remote controller. 2) Reset the error via the remote controller to start an emergency operation. Precautions before servicing the unit When the OC is in trouble, the OS temporarily takes over the OC's function and performs an emergency operation. When this
happens, the indoor unit connection information are changed. In a system that has a billing function, a message indicating that the billing system information has an error may appear on
the TG-2000A. Even if this message appears, do not change (or set) the refrigerant system information on the TG-2000A. After the completion of an emergency operation, the correct connection information will be restored.
(2) Starting the emergency operation (When the OS is in trouble) 1) A communication error occurs. -> An emergency operation starts in approximately six minutes.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Error codes that permit an emergency operation Error code description
Circuit board failure or the power to the outdoor units is off
6607 6608 No acknowledgement error No response error
Emergency operation pattern (2 outdoor units)
OC failure pattern Trouble Normal
OS
Maximum total capacity of indoor units (Note 1)
Capacity that matches the total capacity of the operable outdoor units
When communication is restored, the emergency mode is cancelled, and the units go into the normal operation mode.

[ VII Control ]
The control system configuration for the PURY models is shown in the chart below.
Data signal exchange between system equipment
Non-polar 2-wire serial communication method
Daisy-chained non-polar 2-wire transmission line
16-bit CPU microcomputer operation processing
System control Adjustment of refrigerant flow rate Adjustment of rotation speed of compressor or fan
Autonomous distributed control system (F2-VPM control)
Rotation speed control of compressor or fan depending on the refrigerant pressure value and the changing speed
Self-contained capacity control depending on the load
Refrigerant distribution control depending on the operation mode
instead of a single centralized control system, that work together to maintain the overall control of the entire system.

[ VII Control ]


[ VII Control ]
The operation mode can be selected from the following 6 modes using the remote controller.
4 Automatic cooling/heating mode

1 Cooling only mode All indoor units in operation are in cooling mode.
2 Heating only mode All indoor units in operation are in heating mode.
3 Cooling main mode Coexistence of units in cooling and heating modes.
4 Heating main mode Coexistence of units in cooling and heating modes.
5 Stopping mode All indoor units are in fan mode or stopping mode.
When units in cooing and heating coexist, the operation mode (cooling main mode or heating main mode) will be determined, based on the refrigerant pressure in the R2 refrigerant circuit and speed variation data.
When the automatic cooling/heating mode is selected from remote controller functions, the indoor temperature will be detect- ed in pattern as shown in the figure below, and the operation mode (cooling or heating) will automatically be selected.

Cooling operation under Thermo-ON conditions Set temperature (Variable between 19 C and 28 C [ 67 F and 83 F]) Heating operation under Thermo-ON conditions
(4) Relationship between the operation mode and the load capacity (kW) (within a system)


[ VII Control ]
Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units.
When DIP SW4-4 is set to ON, the 4-step DEMAND control is enabled. Eight-step demand control is possible in the system with two outdoor units.
Refer to Chapter II [3] 2. (7) "Various types of control using input-output signal connector on the outdoor unit (various connec- tion options)" for details.(page 22)

[ VII Control ]
Cooling Heating Stopped Defrost
SV B OFF ON OFF OFF
SV C ON OFF OFF OFF
mode Cooling only Cooling main Heating only Heating main Defrost Stopped
Pressure dif- ferential con- trol*1
OFF OFF ON OFF
*1. Pressure differential control: The detected differential pressure (PS1 and P3) is controlle every minute so as to be within a certain range.
Operation mode Cooling only Cooling
main Heating only Heating
2000 1200 LEV2 (only GA type)
2000 Liquid level control*1dif- ferential control*2
Pressure dif- ferential con- trol*2
Pressure dif- ferential con- trol*2
GB,HB
control*4 60
*1. Liquid level control: The liquid level detected by the liquid inlet temperature (TH11 sensor) is controlled so as to be within a certain range.
*2. Pressure differential control: The detected differential pressure (PS1 and P3) is controlle every minute so as to be within a certain range.
*3. Can be 110 or more due to pressure rise on the liquid side (PS1).
*4. Superheat control: The amound of superheat that is calculated on the bypass inlet and outlet temperature (G, GA, H:TH12,TH15, GB, HB: TH12, TH15) is controlled every minute so as to be within a certain range.
mode Cooling only Cooling main Heating only Heating main Defrost Stopped
SVM2 OFF OFF Pressure differ-
ential control*1 OFF OFF
*1. Pressure differential control: The detected differential pressure (PS1 and P3) is controlled every minute so as to be with- in a certain range.

[ VII Control ]
NO
YES
YES
NO
display lit off Error mode
YES
ON
NO
Dry mode Heating mode Fan mode
Self-holding of protection function
Dry display Heating display Cooling display
*Note 3 *Note 3 *Note 3
YES
ON
NO NO NO NO NO
Indoor unit LEV fully closed.
Refer to 2-(1) for cooling operation.
Refer to 2-(2) for heating operation.
Refer to 2-(3) for
dry operation.
Prohibition "Blinking display on the remote controller"
*Note 1. Indoor unit LEV fully closed : Opening 41. *Note 2. The system may go into the error mode on either the indoor unit side or the BC controller or outdoor unit side. If some of the indoor units are experiencing a problem, only those indoor units that are experiencing the problem will stop. If the BC controller or the outdoor unit is experiencing a problem, all the connected units will stop.
*Note 3. If multiple indoor units are connected to a port and there is a discrepancy in the operation mode between the indoor unit and the port, the operation will be prohibited. (Operation mode blinks on the remote controller, the Fan stops, indoor unit LEV becomes fully closed.)

[ VII Control ]
(2) Outdoor unit (cooling only, heating only, cooling main and heating main modes)
Unit in the stopped state
"HO" / "PLEASE WAIT" blinks
on the remote controller
Indoor units registered to the remote controller
YES
NO
Protection function self-holding cancelled.
Cooling only, Heating only Mixture of units in cooling and heating
NO
52C1 ON
Mixture of units in cooling and heating
Error display on the outdoor unit LED
Self-holding of protection function
Cooling Only Heating Only
to the BC controller
Operation command to the BC controller
*Note 1. For about 3 minutes after power on, search for the indoor unit address, for the remote controller address, and for the group information will start. During this, "HO"/ "PLEASE WAIT" blinks on the display of the remote controller. When the indoor unit to be controlled by the remote controller is missing, "HO"/ "PLEASE WAIT" keeps blinking on the display of the remote controller even after 3 or more minutes after power on.
*Note 2. The system may go into the error mode on either the indoor unit or the outdoor unit side. The outdoor stops only when all of the connected indoor units are experiencing problems. The operation of even a single indoor unit will keep the outdoor unit running. The error will be indicated on the LED display.
*Note 3. The units will follow the operation mode commands from the BC controller *Note 4. When the operation mode commands from the BC controllers are mixed (both cooling and heating), the actual operation mode is determined by the outdoor unit.

[ VII Control ]
(3) BC controller (cooling only, heating only, cooling main and heating main modes)
Unit in the stopped state
NO
YES
Protection function self-holding cancelled.
Reception of operation mode command from the outdoor unit
NO
Mixture of units in cooling and heating
All units in the same mode Solenoid valves OFF LEV Fully closed
Self-holding of protection function
Cooling Only Heating Only Cooling Main Heating Main
Note 1. The system may go into the error mode on either the indoor unit side or the BC controller or outdoor unit side. If some of the indoor units are experiencing a problem, only those indoor units that are experiencing the problem will stop. If the BC controller or the outdoor unit is experiencing a problem, all the connected units will stop.

[ VII Control ]
During test run mode
Unit in the stopped state
Indoor unit fan operation
ON
NO
NO
ON
YES
YES
NO
*Note 1. The indoor fan operates at the set notch under cooling mode regardless of the ON/OFF state of the thermostat.

[ VII Control ]
Unit in the stopped state
During test run mode
YES
ON
NO
ON
YES
YES
NO
NO
Stopping the defrost operation
Stopping the defrost operation
*Note 1. When the outdoor unit goes into the defrost mode, defrost command is sent to the BC controller and indoor units. Upon reception of the command, the indoor units will go into the defrost mode. When defrosting is completed and upon receiving the signal that indicates the completion of defrosting, indoor units will resume the heating operation. *Note 2. Defrost end condition: 10 or more minutes must pass after defrost operation. or Outdoor unit piping temperature : refer to "-7-. Defrost operation control" of [2] Controlling the Outdoor Unit.

[ VII Control ]
Unit in the stopped state
ON
NO
NO
18 C[64 F]
YES
*Note 1.When the indoor unit inlet temperature exceeds 18 C [64 F], the outdoor unit (compressor) and the indoor unit fan start the intermittent operation simultaneously. When the indoor unit inlet temperature becomes 18 C [64 F],or less, the fan always runs (at low speed). The outdoor unit, the indoor unit, and the solenoid valve operate in the same way as they do in the cooling operation when the compressor is turned on.
*Note 2.Thermostat is always kept on during test run mode, and indoor and outdoor unit intermittent operation (ON) time is a little longer than that of normal operation.

- 152 -

[1] Items to be checked before a Test Run 155 [2] Test Run Method 156 [3] Operating Characteristic and Refrigerant Amount 157 [4] Adjusting the Refrigerant Amount 157 [5] Refrigerant Amount Adjust Mode 160 [6] The following symptoms are normal 162 [7] Standard Operation Data (Reference Data) 163

- 154 -
![Page 164 of the Mitsubishi Electronics P96 user manual — (5) [When a transmission booster is connected]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-164.webp?w=400)
[ VIII Test Run Mode ]
VIII Test Run Mode [1] Items to be checked before a Test Run
(1) Check for refrigerant leak and loose cables and connectors.
(2) Measure the insulation resistance between the power supply terminal block and the ground with a 500V megger and
make sure it reads at least 1.0Mohm.
Do not operate the unit if the insulation resistance is below 1.0Mohm. Do not apply megger voltage to the terminal block for transmission line. Doing so will damage the controller board. The insulation resistance between the power supply terminal block and the ground could go down to close to 1Mohm imme-
diately after installation or when the power is kept off for an extended period of time because of the accumulation of refrigerant in the compressor. If insulation resistance reads at least 1Mohm, by turning on the main power and powering the crankcase heater for at least
12 hours, the refrigerant in the compressor will evaporate and the insulation resistance will go up. Do not measure the insulation resistance of the terminal block for transmission line for the unit remote controller.
(3) Check that the valve on the gas pipe and liquid pipe are fully open.
Securely tighten the cap.
(4) Check the phase sequence and the voltage of the power supply.
Turn on the transmission booster before turning on the outdoor units.
If the outdoor units are turned on first, the connection information for the refrigerant circuit may not be properly recognized. In case the outdoor units are turned on before the transmission booster is turned on, perform a power reset on the outdoor
units after turning on the power booster.
(6) Turn on the main power to the unit at least 12 hours before test run to power the crankcase heater.
Insufficient powering time may result in compressor damage.
(7) When a power supply unit is connected to the transmission line for centralized control, perform a test run with the
power supply unit being energized. Leave the power jumper connector on CN41 as it is (factory setting).

[ VIII Test Run Mode ]
The figure shows an MA remote controller (PAR-21MAA).
TIMER
ON
ERROR CODE AFTER
AFTER
OFF
F C F C
FILTER FUNCTION
SIMPLE AUTO OFF
WEEKLY
ONLY1Hr.
TEMP.
MENU
ON/OFF
FILTER
BACK DAY MONITOR/SET
CHECK
TEST
Vertical Air Direction button Louver button ( Operation button)
CLOCK
OPERATION CLEAR
To preceding operation number.
Ventilation button ( Operation button)
To next operation number.
Turn on the main power. "PLEASE WAIT" appears on the LCD for up to five minutes. Leave the power on for 12 hours. (Energize the crankcase heater.)
Press the Test button twice. Operation mode display "TEST RUN" and OPERATION MODE are displayed alternately.
Press the Operation Mode button.
Make sure that the air is blowing out.
Switch to cooling (or heating) operation by pressing the Operation Mode button.
Make sure that cold (or warm) air blows out.
Press the Fan Speed button.
Make sure that the fan speed changes with each pressing of the button.
Change the air flow direction by pressing the Vertical Air Direction button or the Louver button.
Make sure that the air flow direction changes with each pressing of the button.
Confirm the operation of outdoor unit fan.
Confirm the operation of all interlocked equipment, such as ventilation equipment.
Cancel the test run by pressing the ON/OFF button.
2: The OFF timer will automatically stop the test run after 2 hours. 3: The remaining time for the test run will be displayed in the time display during test run. 4: The temperature of the liquid pipe on the indoor unit will be displayed in the room temperature display window on the remote controller during test run. 5: On some models, "NOT AVAILABLE" may appear on the display when the Vane Control button is pressed. This is normal. 6: If an external input is connected, perform a test run using the external input signal.

[ VIII Test Run Mode ]
It is important to have a clear understanding of the characteristics of refrigerant and the operating characteristics of air conditioners before attempting to adjust the refrigerant amount in a given system.
1. Operating characteristic and refrigerant amount The following table shows items of particular importance. 1) During cooling operation, the amount of refrigerant in the accumulator is the smallest when all indoor units are in operation. 2) During heating operation, the amount of refrigerant in the accumulator is the largest when all indoor units are in operation. 3) General tendency of discharge temperature Discharge temperature tends to rise when the system is short on refrigerant. Changing the amount of refrigerant in the system while there is refrigerant in the accumulator has little effect on the discharge
temperature. The higher the pressure, the more likely it is for the discharge temperature to rise. The lower the pressure, the more likely it is for the discharge temperature to rise. 4) When the amount of refrigerant in the system is adequate, the compressor shell temperature is 10 to 60°C [18 to 108°F] higher than the low pressure saturation temperature (Te). -> If the temperature difference between the compressor shell temperature and low pressure saturation temperature (Te) is smaller than 5°C [9°F], an overcharging of refrigerant is suspected.
The system comes to an abnormal stop, displaying 1500 (overcharged refrigerant) on the controller.
The operating frequency does not reach the set frequency, and there is a problem with performance.
The system comes to an abnormal stop, displaying 1102 (abnormal discharge temper- ature) on the controller.
Operate all indoor units in either cooling-only or heating-only mode, and check such items as discharge temperature, subcool- ing, low pressure, suction temperature, and shell bottom temperature to estimate the amount of refrigerant in the system.
Discharge temperature is high. (Normal discharge temperature is below 95°C [203°F].) Slightly under- charged refrigerant Low pressure is unusually low.
Suction superheat is large. (Normal suction superheat is less than 20°C [36°F].)
Compressor shell bottom temperature is high. (The difference between the compressor shell bottom temperature and low pressure saturation temperature (Te) is greater than 60°C [108°F].)
Discharge superheat is small. (Normal discharge superheat is greater than 10°C [18°F].) Slightly overcharged refrigerant Compressor shell bottom temperature is low. (The difference between the compressor shell bot- tom temperature and low pressure saturation temperature (Te) is less than 5°C [9°F].)
Overcharged refrigerant · Insufficient refrigerant amount · Symptoms Conclusion

[ VIII Test Run Mode ]
Outdoor unit model P72 P96 P120
Amount of pre-charged refrigerant in the outdoor unit (kg) 10.5 11.8 11.8
Amount of pre-charged refrigerant in the outdoor unit [lbs-oz] 23-2 26-1 26-1
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Amount of added refrigerant (kg) = (0.36 x L1) + (0.23 x L2) + (0.16 x L3) + (0.11 x L4)+ (0.2 x L5)
+ (0.12 x L6) + (0.06 x L7) + (0.024 x L8) + ǩ1+ ǩ3 + ǩ4
Amount of added refrigerant (oz) = (3.88 x L1' ) + (2.48 x L2' ) + (1.73 x L3' ) + (1.19 x L4' )+ (2.16 x L5' )
+ (1.30 x L6' ) + (0.65 x L7' ) + (0.26 x L8' ) + ǩ1' + ǩ3' + ǩ4'
L1 : Length of ø28.58[1-1/8"] high pressure pipe (m) L2 : Length of ø22.2[7/8"] high pressure pipe (m) L3 : Length of ø19.05[3/4"] high pressure pipe (m) L4 : Length of ø15.88[5/8"] high pressure pipeŠ (m) L5 : Length of ø15.88[5/8"] liquid pipe (m) L6 : Length of ø12.7[1/2"] liquid pipe (m) L7 : Length of ø9.52[3/8"] liquid pipe (m) L8 : Length of ø6.35[1/4"] liquid pipe (m) ǩ1,ǩ3,ǩ4, ǩ1' , ǩ3' , ǩ4' : Refer to the table below.
L1' : Length of ø28.58[1-1/8"] high pressure pipe [ft] L2' : Length of ø22.2[7/8"] high pressure pipe [ft] L3' : Length of ø19.05[3/4"] high pressure pipe [ft] L4' : Length of ø15.88[5/8"] high pressure pipe [ft] L5' : Length of ø15.88[5/8"] liquid pipe [ft] L6' : Length of ø12.7[1/2"] liquid pipe [ft] L7' : Length of ø9.52[3/8"] liquid pipe [ft] L8' : Length of ø6.35[1/4"] liquid pipe [ft]
Amount for the BC controllers (main/sub) BC controller (sub)
Total capacity of connected indoor
Amount for the Indoor
ǩ1(kg) ǩ1' (oz) ǩ4(kg) ǩ4' (oz)
P72 model 3.0 106 Total number of BC ǩ3(kg) ǩ3' (oz) - 27 2.0 71
4.5 159 1 1.0 35 28 - 54 2.5 89
P120 model 2 2.0 71 55 - 126 3.0 106
P144 model 6.0 212 127 - 144 3.5 124
P168 model 7.5 265 145 - 180 4.5 159
P216 model 235 - 273 6.0 212
9.0 318
P240 model 274 - 307 8.0 283
Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg) Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz. (Example: 78.21oz to 79oz)

[ VIII Test Run Mode ]
Outdoor unit 1 Outdoor unit 2
G
Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2)
H H′
Reducer (P06 - P18 models) (Supplied with the BC Controller)
Junction pipe kit (CMY-R160-J) (Optional accessory)
(P06 - P30)
(P36 - P96)
Maximum of 3 units per port Total capacity of P30 or below
Indoor unit1:30 model Indoor unit2:96 model Indoor unit3:12 model Indoor unit4:15 model Indoor unit5:12 model Indoor unit6:24 model
A : 28.58 B : 9.52 C : 9.52 D : 9.52 E : 9.52 F : 22.2 G : 19.05
[1-1/8"] [3/8"] [7/8"] [3/4"]
40m 10m 20m 5m 5m 3m 1m
[131ft] [32ft] [65ft] [16ft] [16ft] [9ft] [3ft]
a : 9.52 b : 9.52 c : 6.35 d : 6.35 e : 6.35 f : 9.52
[3/8"] [3/8"] [1/4"] [1/4"] [1/4"] [3/8"]
10m 5m 5m 10m 5m 5m
[32ft] [16ft] [16ft] [32ft] [16ft] [16ft]
The aggregate length of each liquid pipe type.
28.58 A = 40m[131ft] 22.2 F = 30m[98ft] 19.05 G = 1m[3ft] 9.52 C+D+E+a+b+f = 50m[164ft] 6.35 c+d+e = 20m[65ft]
The final result will be as follows: Amount of refrigerant to be charged = 40×0.36+3×0.23+1×0.16+50×0.06+20×0.024+7.5+2+2+5
= 35.3kg
![Page 169 of the Mitsubishi Electronics P96 user manual — [5] Refrigerant Amount Adjust Mode](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-169.webp?w=400)
[ VIII Test Run Mode ]
When the function switch (SW4-3) on the main board on the outdoor unit (OC only) is turned to ON, the unit goes into the refrigerant amount adjust mode, and the following sequence is followed.
SW4-3 on the OS is invalid, and the unit will not go into the refrigerant amount adjust mode.
Operation When the unit is in the refrigerant amount adjust mode, the LEV on the indoor unit does not open as fully as it nor- mally does during cooling operation to secure subcooling.
1) Adjust the refrigerant amount based on the values of TH4, TH3, TH6, and Tc, following the flowchart below. Check the TH4, TH3, TH6, and Tc values on the OC, OS by following the flowchart. The TH4, TH3, TH6, and Tc values can be displayed by setting the self-diagnosis switch (SW1) on the main board on the OC, OS. 2) There may be cases when the refrigerant amount may seem adequate for a short while after starting the unit in the refrigerant amount adjust mode but turn out to be inadequate later on (when the refrigerant system stabilizes). When the amount of refrigerant is truly adequate. TH3-TH6 on the indoor unit is 5°C [9°F] or above and SH on the indoor unit is between 5 and 15°C [9 and 27°F]. The refrigerant amount may seem adequate at the moment, but may turn out to be inadequate later on. TH3-TH6 on the indoor unit is 5°C [9°F] or less and SH on the indoor unit is 5°C [9°F] or less. Wait until the TH3-TH6 reaches 5°C [9°F] or above and the SH of the indoor unit is between 5 and 15°C [9 and 27°F] to determine that the refrigerant amount is adequate. 3) High pressure must be at least 2.0MPa [290psi] to enable a proper adjustment of refrigerant amount to be made. 4) Refrigerant amount adjust mode automatically ends 90 minutes after beginning. When this happens, by turning off the SW4- 3 and turning them back on, the unit will go back into the refrigerant amount adjust mode.
Self-diagnosis swithes on TH4
Self-diagnosis swithes on TH3
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
Self-diagnosis swithes on TH6
Self-diagnosis swithes on Tc
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON

[ VIII Test Run Mode ]
Turn on SW4-3 on the OC.
NO
Put all indoor units in the test run mode and run the units in cooling mode.
*Refer to the previous page for *Notes 1-4 in the chart.
Has the initial start-up mode been completed?
Has it been at least
30 minutes since start up?
NO
Gradually add refrigerant from the service port on the low- pressure side.
Is the TH4 value of the OC, OS
at or below 100°C [212°F]?
Has the operating frequency of the compressor on the OC, OS
Keep the unit running for 5 minutes after adjusting the refrigerant amount to determine its adequacy.
Does 8°C [14.4°F] Tc-TH3 12°C [21.6°F] hold true?
(Use the largest “Tc - TH3” value of the
Keep the unit running for 5 minutes after adjusting the refrigerant amount and check(Tc-TH3)
Gradually add refrigerant from the service port on the low pressure side.
NO
Does Tc-TH6 20°C [36°F] hold true?
Does the following hold true?
(Check this item on the unit whose “Tc – TH3” value was
used in the step above.)
Tc-TH3 8°C [14.4°F]
YES
Keep the unit running for 5 minutes after adjusting the refrigerant amount to determine its adequacy.
Gradually add refrigerant from the service port on the low pressure side.
Is the TH4 value of the OC, OS
Gradually add refrigerant from the service port on the low pressure side.
Gradually draw out refrigerant from the service port on the low pressure side.
at or below 95°C [203°F]
Turn off SW4-3 on the OC.
result in performance loss.

[ VIII Test Run Mode ]
[6] The following symptoms are normal.
The indoor unit does not start after starting cooling (heating) operation.
The unit cannot perform a heating (cooling) operation when other indoor units are performing a cooling (heating) operation.
icon blinks on the
display.
The auto vane adjusts its posi- tion by itself.
After an hour of cooling operation with the auto vane in the vertical posi- tion, the vane may automatically move into the horizontal position. Louver blades will automatically move into the horizontal position while the unit is in the defrost mode, pre-heating stand-by mode, or when the thermostat triggers unit off.
The fan stops during heating operation. Defrost The fan remains stopped during defrost operation.
The fan keeps running after the unit has stopped. Unlit When the auxiliary heater is turned on, the fan operates for one minute after stopping to dissipate heat.
The fan speed does not reach the set speed when operation switch is turned on. STAND BY
The fan operates at extra low speed for 5 minutes after it is turned on or until the pipe temperature reaches 35°C[95°F], then it operates at low speed for 2 minutes, and finally it operates at the set speed. (Pre-heating stand-by)
When the main power is turned on, the display shown on the right appears on the in- door unit remote controller for 5 minutes.
The system is starting up. Wait until the blinking display of "HO" or "PLEASE WAIT" go off.
"HO" or "PLEASE WAIT" icons blink
on the display.
The drain pump keeps run- ning after the unit has stopped.
The drain pump stays in operation for three minutes after the unit in the cooling mode is stopped.
The drain pump is running while the unit is stopped.
When drain water is detected, the drain pump goes into operation even while the unit is stopped.
Indoor unit and BC controller make noise during cooling/ heating changeover.
This noise is made when the refrigerant circuit is reversed and is normal.
Sound of the refrigerant flow is heard from the indoor unit im- mediately after starting opera- tion.
This is caused by the transient instability of the refrigerant flow and is nor- mal.
Warm air sometimes comes out of the indoor units that are not in the heating mode. Normal display
This is due to the fact that the LEVs on some of the indoor units are kept slightly open to prevent the refrigerant in the indoor units that are not op- erating in the heating mode from liquefying and accumulating in the com- pressor. It is part of a normal operation.
![Page 172 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-172.webp?w=400)
[ VIII Test Run Mode ]
Model name of BC controller CMB-P104NU-G CMB-P104NU-G
26.7°C/19.4°C [80 °F/67 °F]
DB/WB
Outdoor 35°C/- [95 °F/-]
No. of connected units
No. of units in operation 3 2
Model - 24/24/24 48/48
5 [16-3/8"] 5 [16-3/8"]
Branch pipe 10 [32-3/4"] 10 [32-3/4"]
Total pipe length 35 [114-13/16"] 25 [82]
Fan speed - Hi Hi
Amount of refrigerant kg [lbs-oz] 19.1 [42] 21.3 [47]
Electric current A 15.4 23.2
Voltage V 230 230
Compressor frequency Hz 43 65
BC controller (1/2/3) 2000/-/180 2000/-/170
High pressure(63HS1)/ Low pressure(63LS) MPa
2.65/0.90 [384/130]
2.66/0.93 [385/134]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.59/2.59 [375/375]
2.58/2.58 [374/374]
76 [169] 85 [185]
Heat exchanger outlet (TH3) 41 [106] 39 [102]
Accumulator inlet 14 [57] 8 [46]
Temp. of each sec- tion
Accumulator outlet 14 [57] 8 [46]
Compressor inlet 23 [73] 19 [66]
Compressor shell bottom 34 [93] 40 [104]
LEV inlet 24 [75] 19 [66]
Heat exchanger inlet 12 [54] 6 [43]
![Page 173 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-173.webp?w=400)
[ VIII Test Run Mode ]
Model name of BC controller CMB-P104NU-G
DB/WB
No. of connected units
No. of units in operation 4
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 22.5 [50]
Electric current A 29.5
Compressor frequency Hz 75
BC controller (1/2/3) 2000/-/210
High pressure(63HS1)/ Low pressure(63LS) MPa
2.82/0.89 [409/129]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.73/2.72 [395/394]
Heat exchanger outlet (TH3) 43 [109]
Accumulator inlet 8 [46]
Temp. of each sec- tion
Accumulator outlet 8 [46]
Compressor inlet 20 [68]
Compressor shell bottom 42 [108]
LEV inlet 22 [72]
Heat exchanger inlet 11 [52]
![Page 174 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-174.webp?w=400)
[ VIII Test Run Mode ]
(2) Heating only operation
Model name of BC controller CMB-P104NU-G CMB-P104NU-G
21.1°C/- [70°F/-]
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 3 2
Model - 24/24/24 48/48
5 [16-3/8"] 5 [16-3/8"]
Branch pipe 10 [32-3/4"] 10 [32-3/4"]
Total pipe length 35 [114-13/16"] 25 [82]
Fan speed - Hi Hi
Amount of refrigerant kg [lbs-oz] 19.1 [42] 21.3 [47]
Electric current A 16.8 24.1
Voltage V 230 230
Compressor frequency Hz 48 71
BC controller (1/2/3) 110/-/520 110/-/590
High pressure(63HS1)/ Low pressure(63LS) MPa
2.61/0.69 [378/100]
2.67/0.68 [387/98]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.54/2.22 [368/321]
2.63/2.31 [381/335]
69 [156] 80 [176]
Heat exchanger outlet (TH6) 0 [32] 0 [32]
Accumulator inlet 1 [34] -2 [28]
Temp. of each sec- tion
Accumulator outlet 1 [34] -3 [27]
Compressor inlet 1 [34] -3 [27]
Compressor shell bottom 40 [104] 40 [104]
LEV inlet 30 [86] 38 [100]
Heat exchanger inlet 63 [145] 70 [158]
![Page 175 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-175.webp?w=400)
[ VIII Test Run Mode ]
Model name of BC controller CMB-P104NU-G
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 4
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 22.5 [50]
Electric current A 28.3
Compressor frequency Hz 81
BC controller (1/2/3) 110/-/660
High pressure(63HS1)/ Low pressure(63LS) MPa
2.57/0.64 [372/92]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.54/2.22 [368/321]
Heat exchanger outlet (TH6) 2 [36]
Accumulator inlet -1 [30]
Temp. of each sec- tion
Accumulator outlet -1 [30]
Compressor inlet -1 [30]
Compressor shell bottom 40 [104]
LEV inlet 28 [82]
Heat exchanger inlet 67 [153]
![Page 176 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-176.webp?w=400)
[ VIII Test Run Mode ]
PURY-P72THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-GA
DB/WB
No. of connected units
No. of units in operation 4
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 34.1 [75]
Electric current A 31.5
Compressor frequency Hz 43 43
BC controller (1/2/3) 2000/2000/250
High pressure(63HS1)/ Low pressure(63LS) MPa
2.65/0.90 [384/130]
2.65/0.90 [384/130]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.59/2.59 [375/375]
76 [169] 76 [169]
Heat exchanger outlet (TH3) 41 [106] 41 [106]
Accumulator inlet 14 [57] 14 [57]
Temp. of each sec- tion
Accumulator outlet 14 [57] 14 [57]
Compressor inlet 23 [73] 23 [73]
Compressor shell bottom 34 [93] 34 [93]
LEV inlet 24 [75]
Heat exchanger inlet 12 [54]
![Page 177 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-177.webp?w=400)
[ VIII Test Run Mode ]
PURY-P96THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-GA
DB/WB
No. of connected units
No. of units in operation 5
Branch pipe 10 [32-3/4"]
Total pipe length 55 [180-1/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 38.5 [85]
Electric current A 39.5
Compressor frequency Hz 65 43
BC controller (1/2/3) 2000/2000/260
High pressure(63HS1)/ Low pressure(63LS) MPa
2.66/0.91 [385/131]
2.65/0.91 [384/131]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.59/2.59 [375/375]
85 [185] 76 [169]
Heat exchanger outlet (TH3) 39 [102] 41 [106]
Accumulator inlet 8 [46] 14 [57]
Temp. of each sec- tion
Accumulator outlet 8 [46] 14 [57]
Compressor inlet 19 [66] 23 [73]
Compressor shell bottom 40 [104] 34 [93]
LEV inlet 22 [72]
Heat exchanger inlet 9 [48]
![Page 178 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-178.webp?w=400)
[ VIII Test Run Mode ]
PURY-P96THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P108NU-GA
DB/WB
No. of connected units
No. of units in operation 6
Branch pipe 10 [32-3/4"]
Total pipe length 65 [213-1/4"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 42.4 [93]
Electric current A 47.5
Compressor frequency Hz 65 65
BC controller (1/2/3) 2000/2000/270
High pressure(63HS1)/ Low pressure(63LS) MPa
2.66/0.93 [385/134]
2.66/0.93 [385/134]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.59/2.59 [375/375]
85 [185] 85 [185]
Heat exchanger outlet (TH3) 39 [102] 39 [102]
Accumulator inlet 8 [46] 8 [46]
Temp. of each sec- tion
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 42 [108] 40 [104]
LEV inlet 19 [66]
Heat exchanger inlet 6 [43]
![Page 179 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-179.webp?w=400)
[ VIII Test Run Mode ]
PURY-P120THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P1013NU-GA
DB/WB
No. of connected units
No. of units in operation 6
Branch pipe 10 [32-3/4"]
Total pipe length 65 [213-1/4"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 43.0 [95]
Electric current A 53.8
Compressor frequency Hz 75 65
BC controller (1/2/3) 2000/2000/280
High pressure(63HS1)/ Low pressure(63LS) MPa
2.82/0.91 [409/131]
2.66/0.91 [385/131]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.66/2.66 [385/385]
82 [180] 85 [185]
Heat exchanger outlet (TH3) 43 [109] 39 [102]
Accumulator inlet 8 [46] 8 [46]
Temp. of each sec- tion
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 20 [68] 19 [66]
Compressor shell bottom 42 [108] 40 [104]
LEV inlet 22 [72]
Heat exchanger inlet 9 [48]
![Page 180 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-180.webp?w=400)
[ VIII Test Run Mode ]
PURY-P120THMU-A PURY-P120THMU-A
Model name of BC controller CMB-P1013NU-GA
DB/WB
No. of connected units
No. of units in operation 7
Branch pipe 10 [32-3/4"]
Total pipe length 75 [229-5/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 44.6 [98]
Electric current A 60.2
Compressor frequency Hz 75 75
BC controller (1/2/3) 2000/2000/290
High pressure(63HS1)/ Low pressure(63LS) MPa
2.82/0.89 [409/129]
2.82/0.89 [409/129]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.73/2.73 [395/395]
82 [180] 82 [180]
Heat exchanger outlet (TH3) 43 [109] 43 [109]
Accumulator inlet 8 [46] 8 [46]
Temp. of each sec- tion
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 20 [68] 20 [68]
Compressor shell bottom 42 [108] 42 [108]
LEV inlet 22 [72]
Heat exchanger inlet 11 [52]
![Page 181 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-181.webp?w=400)
[ VIII Test Run Mode ]
(2) Heating only operation
PURY-P72THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-A
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 4
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 34.1 [75]
Electric current A 34.6
Compressor frequency Hz 48 48
BC controller (1/2/3) 110/110/870
High pressure(63HS1)/ Low pressure(63LS) MPa
2.61/0.69 [378/100]
2.61/0.69 [378/100]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.54/2.22 [368/321]
69 [156] 69 [156]
Heat exchanger outlet (TH6) 0 [32] 0 [32]
Accumulator inlet 1 [34] 1 [34]
Temp. of each sec- tion
Accumulator outlet 1 [34] 1 [34]
Compressor inlet 1 [34] 1 [34]
Compressor shell bottom 40 [104] 40 [104]
LEV inlet 30 [86]
Heat exchanger inlet 63 [145]
![Page 182 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-182.webp?w=400)
[ VIII Test Run Mode ]
PURY-P96THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-GA
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 5
Branch pipe 10 [32-3/4"]
Total pipe length 55 [180-1/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 38.5 [85]
Electric current A 42.2
Compressor frequency Hz 71 48
BC controller (1/2/3) 110/110/980
High pressure(63HS1)/ Low pressure(63LS) MPa
2.64/0.68 [382/98]
2.64/0.69 [382/335]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.60/2.27 [377/329]
80 [176] 69 [156]
Heat exchanger outlet (TH6) 0 [32] 0 [32]
Accumulator inlet -2 [28] 1 [34]
Temp. of each sec- tion
Accumulator outlet -3 [27] 1 [34]
Compressor inlet -3 [27] 1 [34]
Compressor shell bottom 40 [104] 40 [104]
LEV inlet 34 [93]
Heat exchanger inlet 67 [153]
![Page 183 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-183.webp?w=400)
[ VIII Test Run Mode ]
PURY-P96THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P108NU-GA
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 6
Branch pipe 10 [32-3/4"]
Total pipe length 65 [213-1/4"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 42.4 [93]
Electric current A 44.2
Compressor frequency Hz 71 71
BC controller (1/2/3) 110/110/1050
High pressure(63HS1)/ Low pressure(63LS) MPa
2.67/0.68 [387/98]
2.79/0.58 [405/81]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.63/2.31 [381/335]
80 [176] 80 [176]
Heat exchanger outlet (TH6) 0 [32] 0 [32]
Accumulator inlet -2 [28] -2 [28]
Temp. of each sec- tion
Accumulator outlet -3 [27] -3 [27]
Compressor inlet -3 [27] -3 [27]
Compressor shell bottom 40 [104] 40 [104]
LEV inlet 38 [100]
Heat exchanger inlet 70 [158]
![Page 184 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-184.webp?w=400)
[ VIII Test Run Mode ]
PURY-P120THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P1013NU-GA
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 6
Branch pipe 10 [32-3/4"]
Total pipe length 65 [213-1/4"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 43.0 [95]
Electric current A 54.0
Compressor frequency Hz 81 71
BC controller (1/2/3) 110/110/1120
High pressure(63HS1)/ Low pressure(63LS) MPa
2.62/0.64 [380/92]
2.62/0.68 [380/98]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.60/2.27 [377/329]
73 [163] 80 [176]
Heat exchanger outlet (TH6) 2 [36] 0 [32]
Accumulator inlet -1 [30] -2 [28]
Temp. of each sec- tion
Accumulator outlet -1 [30] -3 [27]
Compressor inlet -1 [30] -3 [27]
Compressor shell bottom 40 [104] 40 [104]
LEV inlet 33 [91]
Heat exchanger inlet 68 [154]
![Page 185 of the Mitsubishi Electronics P96 user manual — °C [°F]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-185.webp?w=400)
[ VIII Test Run Mode ]
PURY-P120THMU-A PURY-P120THMU-A
Model name of BC controller CMB-P1013NU-GA
DB/WB
Outdoor 8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation 7
Branch pipe 10 [32-3/4"]
Total pipe length 75 [229-5/8"]
Fan speed - Hi
Amount of refrigerant kg [lbs-oz] 44.6 [98]
Electric current A 58.3
Compressor frequency Hz 81 81
BC controller (1/2/3) 110/110/1190
High pressure(63HS1)/ Low pressure(63LS) MPa
2.57/0.64 [372/92]
2.57/0.64 [372/92]
BC controller on the liquid side(PS1)/ Intermediate part(PS3)
2.54/2.22 [368/321]
73 [163] 73 [163]
Heat exchanger outlet (TH6) 2 [36] 2 [36]
Accumulator inlet -1 [30] -1 [30]
Temp. of each sec- tion
Accumulator outlet -1 [30] -1 [30]
Compressor inlet -1 [30] -1 [30]
Compressor shell bottom 40 [104] 40 [104]
LEV inlet 28 [82]
Heat exchanger inlet 67 [153]

[1] Error Code Lists 179 [2] Responding to Error Display on the Remote Controller 182 [3] Investigation of Transmission Wave Shape/Noise 270 [4] Troubleshooting Principal Parts 273 [5] Refrigerant Leak 314 [6] Compressor Replacement Instructions 316 [7] Servicing the BC controller 327 [8] Troubleshooting Using the Outdoor Unit LED Error Display 330

- 178 -

Serial communication error O
1102 1202 - Discharge temperature fault O
1301 - - Low pressure fault O
1302 1402 - High pressure fault O
1500 1600 - Refrigerant overcharge O
- 1605 - Preliminary suction pressure fault O
2500 - - Drain sensor submergence O
2502 - - Drain pump fault O O
2503 - - Drain sensor (Thd) fault O O
2600 - - Water leakage O
2601 - - Water supply cutoff O
3121 - - Out-of-range outside air temperature O
4102 4152 - Open phase O
4106 - - Transmission power supply fault O
4115 - - Power supply signal sync error O
4116 - - RPM error/Motor error O O
[108] Abnormal bus voltage drop O
[109] Abnormal bus voltage rise O
[111] Logic error O
[131] Low bus voltage at startup O
4230 4330 - Heatsink overheat protection O
4240 4340 - Overload protection O
[101] IPM error O
[102] ACCT overcurrent (H/W detection) O
[103] DCCT overcurrent (H/W detection) O
[104] Short-circuited IPM/Ground fault O
[105] Overcurrent error due to short-circuited motor O
[106] Instantaneous overcurrent O
4260 - - Heatsink overheat protection at startup O
Return air temperature (TH21) O
5101 1202 - Temperature sensor fault
OA processing unit inlet temperature (TH4) O

Indoor unit pipe tempera- ture (TH22) O
5102 1217 - Temperature sensor fault
OA processing unit pipe temperature (TH2) O
Indoor unit gas-side pipe temperature (TH23) O
OA processing unit gas- side pipe temperature (TH3)
5103 1205 00 Temperature sensor fault
Pipe temperature at heat exchanger outlet (TH3) O
OA processing unit intake air temperature (TH1) O
Detectable only by the All- Fresh type in- door units
5104 1202 - Temperature sensor fault
Outside temperature (TH24) O
Outdoor unit discharge temperature (TH4) O
5105 1204 - Temperature sensor fault
Accumulator inlet tempera- ture (TH5) O
5106 1216 - Temperature sensor fault
Heat exchanger inlet tem- perature (TH6) O
5107 1221 - Temperature sensor fault Outside temperature (TH7) O
5110 1214 01 Temperature sensor fault
Heatsink temperature (THHS) O
Liquid inlet temperature (TH11) O
5112 - - Bypass outlet temperature (TH12) O
Temperature sensor fault (BC controller)
5115 - - LEV3 outlet temperature (TH15) O
5116 - - LEV3 inlet temperature (TH16) O
5201 - - High-pressure sensor fault (63HS1) O
5201 1402 - High-pressure sensor fault (Outdoor unit HPS/BC controller PS1) O O
5203 - - Intermediate pressure sensor fault (BC controller PS3) O
[115] ACCT sensor fault O
[117] ACCT sensor circuit fault O
[119] Open-circuited IPM/Loose ACCT connector O
[120] Faulty ACCT wiring O
5401 - - Temperature sensor fault O
5701 - - Loose float switch connector O

6201 - - Remote controller board fault (nonvolatile memory error) O
6202 - - Remote controller board fault (clock IC error) O
6600 - - Address overlaps O
6601 - - Polarity setting error O
6602 - - Transmission processor hardware error O
6603 - - Transmission line bus busy error O
6606 - - Communication error between device and trans- mission processors O
6607 - - No ACK error O
6608 - - No response error O
6831 - - MA controller signal reception error (No signal re- ception) O O
6832 - - MA remote controller signal transmission error (Synchronization error) O O
6833 - - MA remote controller signal transmission error (H/ W error) O O
6834 - - MA controller signal reception error (Start bit de- tection error) O O
7100 - - Total capacity error O
7101 - - Capacity code setting error O O O
7102 - - Wrong number of connected units O O
7105 - - Address setting error O
7106 - - Attribute setting error O
7107 - - Port setting error O
7110 - - Connection information signal transmission/recep- tion error O
7111 - - Remote controller sensor fault O O
7113 - - Function setting error O
7117 - - Model setting error O
7130 - - Incompatible unit combination O
The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to inverter on fan inverter. Example Code 4225 (detail code 108): Bus voltage drop in the fan inverter system Code 4230 : Heatsink overheat protection in the inverter system
The last digit Inverter system
0 or 1 Compressor inverter system
5 Fan inverter system

0403 (THMU-A)
Serial communication error
Check the following wiring connections. 1) Between Control board and Fan board
Control board FAN board
FAN board INV board
CN5V
CN4 CN4
(2) INV board failure, Fan board failure and Control board failure
Replace the INV board or the Fan board or control board when the power turns on automatically, even if the power source is reset.
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

0403 (YHMU-A)
Serial communication error
Check the following wiring connections. 1) Between Control board and Fan board
Control board FAN board
FAN board INV board
CN5V
CN4 CN4
(2) INV board failure, Fan board failure and Control board failure
Replace the INV board or the Fan board or control board when the power turns on automatically, even if the power source is reset.
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Discharge temperature fault
2. Error definition and error detection method 1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically. 2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the second stop of the outdoor unit described above, the mode will be changed to 3 - minute restart mode, then the outdoor unit will restart in 3 minutes. 3) If the discharge temperature of 120°C [248°F] or more is detected (the third detection) within 30 minutes after the stop of the outdoor unit described above (regardless of the first or the second stop), the outdoor unit will make an error stop, and the error code "1102" will be displayed. 4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor unit, the detection is regarded as the first detection, and the operation described in step 1 above will start. 5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the LED display.
Cause Check method and remedy
(1) Gas leak, gas shortage Refer to the page on refrigerant amount evaluation.(page 157)
(2) Overload operation Check operating conditions and operation status of indoor/ outdoor units.
(3) LEV failure on the indoor unit Perform a heating operation and check the operation. Cooling: LEV on the indoor unit LEV1,2,3 SVM1,2 SVA,C Heating: LEV on the indoor unit LEV3 SVB SV4a - 4d Refer to the page on troubleshooting LEV.(page 279)
(4) BC controller LEV malfunction Cooling only : LEV3 Cooling main : LEV1,2,3 Heating only or heating main : LEV3 Defrost : LEV3
(5) BC controller SVM1 and 2 malfunction -> Cooling only or defrost
(6) BC controller SVA malfunction -> Cooling only or cooling main
(7) BC controller SVB malfunction -> Heating only or heating main
(8) Solenoid valve SV malfunction (4a-4c (P72 model) ,4a-4d (P96 and P120 models)) :heating only, heating main
(9) Port address setting error. Confirm the port address of the indoor unit.
(10) Closed ball valve Confirm that the ball valve is fully open.
(11) Outdoor fan (including fan parts) failure, mo- tor failure, or fan controller malfunction Rise in discharge temp. by low pressure drawing for (3) - (11).
Check the fan on the outdoor unit. Refer to the section on troubleshooting the outdoor unit fan.(page 279)
(12) Gas leak between low and high pressures (4-way valve failure, Compressor failure, So- lenoid valve (SV1a) failure)
Perform a cooling or heating operation and check the opera- tion.
(13) Thermistor failure (TH4)
Check the thermistor resistor.(page 217)
(14) Input circuit failure on the controller board thermistor
Check the inlet air temperature on the LED monitor.

Low pressure fault
Cause Check method and remedy
(1) Inner pressure drop due to a leakage. Refer to the section on troubleshooting the low pressure sensor.(page 274) (2) Low pressure sensor failure
(3) Short-circuited pressure sensor cable due to torn outer rubber
(4) A pin on the male connector is missing.
(6) Failure of the low pressure input circuit on the controller board
(5) Disconnected wire

High pressure fault 1 (Outdoor unit) 2. Error definition and error detection method 1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out- door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically. 2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 min- utes after the first stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically. 3) If the pressure of 3.87MPa [561psi] or higher is detected by the pressure sensor (the third detection) within 30 minutes of the second stop of the outdoor unit, the outdoor unit will make an error stop, and the error code "1302" will be displayed. 4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection is regarded as the first detection, and the operation described in step 1 above will start. 5) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display. 6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects 4.15+0,-0.15 MPa [601+0,-22 psi] 7) Open phase due to unstable power supply voltage may cause the pressure switch to malfunction or cause the units to come to an abnormal stop. 3. Cause, check method and remedy
Cause Check method and remedy (1) Indoor unit LEV actuation failure Perform a heating operation and check the op- eration. Cooling: LEV on the indoor unit LEV1,2,3 SVM1,1b,2,2b SVA Heating: LEV on the indoor unit LEV3 SVM2,2b SVB,SV4a - 4d Refer to the page on troubleshooting for LEV and solenoid valve.(page 279)
(2) BC controller LEV malfunction Heating only or heating main : Indoor LEV 3 Defrost : LEV3
(3) BC controller SVM1 and 2 malfunction ->Cooling only or defrost (4) BC controller SVA and SVC malfunction ->Cooling only or cooling main (5) BC controller SVB malfunction ->Heating only or heating main Solenoid valve SV malfunction(4a-4c (P72 model) ,4a-4d(P96 and P120 models)) ->Cooling only or cooling main
(6) Port address setting error. Confirm the port address of the indoor unit. (7) Refrigerant service valve actuation failure Confirm that the refrigerant service valve is fully (8) Short cycle on the indoor unit side Check the indoor units for problems and correct them, if any. (9) Clogged filter on the indoor unit
(10) Reduced air flow due to dirty fan on the indoor unit fan
(11) Dirty heat exchanger of the indoor unit
(12) Indoor fan (including fan parts) failure or motor failure Items (7) through (12) above reduce the condensing capability of the unit, resulting in high-pressure rise during heating oper- ation.
(13) Short cycle on the outdoor unit Check the outdoor units for problems and cor- rect them, if any. (14) Dirty heat exchanger of the outdoor unit
(15) Outdoor fan (including fan parts) failure, motor failure, or fan controller malfunction Items (13) through (15) above reduce the condensing capabil- ity of the unit, resulting in high-pressure rise during cooling op- eration.
Check the fan on the outdoor unit. Refer to the section on troubleshooting the out- door unit fan.(page 279)
(16) Solenoid valve (SV1a) malfunction The by-pass valve (SV1a) can not control rise in high pressure.
Refer to the section on troubleshooting the sole- noid valve.(page 275)
(17) Thermistor failure (TH3, TH7) Check the thermistor resistor.(page 217) (18) Pressure sensor failure Refer to the page on the troubleshooting of the high pressure sensor. (page 273) (19) Failure of the thermistor input circuit and pressure sensor input circuit on the controller board
Check the sensor temperature/pressure on the LED monitor. (20) Thermistor mounting problem (TH3, TH7) Check the sensor temperature/pressure on the LED monitor. (21) Disconnected male connector on the pressure switch (63HS1) or disconnected wire (22) Voltage drop caused by unstable power supply voltage Check the input voltage at the power supply ter- minal block (TB1).

High pressure fault 2 (Outdoor unit)
Cause Check method and remedy
(1) Inner pressure drop due to a leakage. Refer to the page on the troubleshooting of the high pressure sensor.(page 273) (2) Pressure sensor failure
(3) Shorted-circuited pressure sensor cable due to torn outer rubber
(4) A pin on the male connector on the pressure sensor is missing or contact failure
(5) Disconnected pressure sensor cable
(6) Failure of the pressure sensor input circuit on the controller board
Refrigerant overcharge
2. Error definition and error detection method An error can be detected by the discharge temperature superheat. 1) If the formula "TdSH 10°C [18°F]" is satisfied during operation (first detection), the outdoor unit stops, goes into the 3-minute restart mode, and starts up in three minutes. 2) If the formula "TdSH 10°C [18°F]" is satisfied again within 30 minutes of the first stoppage of the outdoor unit (second de- tection), the unit comes to an abnormal stop, and the error code "1500" appears. 3) If the formula "TdSH 10°C [18°F]" is satisfied 30 minutes or more after the first stoppage of the outdoor unit, the same se- quence as Item "1 above (first detection) is followed. 4) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
Cause Check method and remedy
(1) Overcharged refrigerant Refer to the page on refrigerant amount evaluation.(page 157)
(2) Thermistor input circuit failure on the control board Check the temperature and pressure readings on the sen- sor that are displayed on the LED monitor.
(3) Faulty mounting of thermistor (TH4) Check the temperature and pressure readings on the thermistor that are displayed on the LED monitor.

Drain sensor submergence (Models with a drain sensor)
2. Error definition and error detection method 1) If an immersion of the drain sensor in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being detected, humidifier output cannot be turned on.(Applicable to the units manufactured in or after October 1996) 2) If the immersion of the sensor in the water is detected four consecutive times at an hour interval, this is considered water leak- age, and "2500" appears on the monitor. 3) Detection of water leakage is also performed while the unit is stopped. 4) Preliminary water leakage is cancelled when the following conditions are met: One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON. The operation mode is changed to Cool/Dry. Liquid pipe temperature - inlet temperature is -10°C[ -18°F]
Cause Check method and remedy
(1) Drain water drainage problem
Check for proper drainage.
Clogged drain pump Clogged drain piping Backflow of drain water from other units
(2) Adhesion of water drops to the drain sensor
Trickling of water along the lead wire Rippling of drain water caused by filter clogging
(3) Failure of the relay circuit for the solenoid valve Replace the relay.
(4) Indoor unit control board failure
If the above item checks out OK, replace the indoor unit control board.
Drain sensor circuit failure

Drain sensor submergence (Models with a float switch)
2. Error definition and error detection method 1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being detected, humidifier output cannot be turned on. 2) If the drain pump turns on within one hour after preliminary water leakage is detected and the above-mentioned condition is detected two consecutive times, water leakage error water leakage is detected, and "2500" appears on the monitor. 3) Detection of water leakage is also performed while the unit is stopped. 4) Preliminary water leakage is cancelled when the following conditions are met: One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON. The operation mode is changed to Cool/Dry. Liquid pipe temperature - inlet temperature - 10°C[-18°F]
Cause Check method and remedy
(1) Drain water drainage problem
Check for proper drainage.
Clogged drain pump Clogged drain piping Backflow of drain water from other units
(2) Stuck float switch Check for slime in the moving parts of the float switch.
Check for normal operation of the float switch.
(3) Float switch failure Check the resistance with the float switch turned on and turned off.
Drain pump operation triggered by a submergence of the liquid level sensor (except during the Cooing/Dry mode)
6 minutes 6 minutes
OFF
ON
OFF
15 seconds 15 seconds
Submergence of the sensor Submergence of the sensor Preliminary water leakage
Sensor in the air Sensor in the air
Submergence of the sensor Water leakage
Within 1-hour period Within 1-hour period

Drain pump fault (Models with a drain sensor)
2. Error definition and error detection method 1) Make the drain sensor thermistor self-heat. If the temperature rise is small, it is interpreted that the sensor is immersed in water. This condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode. 2) If another episode of the above condition is detected during the preliminary error, this is considered a drain pump error, and "2502" appears on the monitor. 3) This error is always detected while the drain pump is in operation. 4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met. "Liquid pipe temperature - inlet temperature - 10 °C [ -18°F] " has been detected for 30 minutes. The immersion of drain sensor is detected 10 consecutive times. The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage
of the outdoor unit. 5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant circuit that are in any mode other than Fan or Stop to an error stop. "2502" appears on the monitor of the units that came to an error stop. 6) Forced stoppage of the outdoor unit Detection timing: The error is detected whether the unit is in operation or stopped. 7) Ending criteria for the forced stoppage of outdoor unit Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig- erant circuit. Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller. (Note) Items 1) - 3) and 4) - 7) are detected independently from each other.
The address and attribute that appear on the remote controller are those of the indoor unit (or OA processing unit) that caused the error.
Cause Check method and remedy
(1) Drain pump failure Check for proper functioning of the drain pump.
(2) Drain water drainage problem
Check for proper drainage.
Clogged drain pump Clogged drain piping
(3) Adhesion of water drops to the drain sensor
Trickling of water along the lead wire Rippling of drain water caused by filter clogging
(4) Indoor unit control board failure
If the above item checks out OK, replace the indoor unit control board.
Drain pump drive circuit failure Drain heater output circuit failure
(5) Items (1) through (4) above and an indoor unit elec- tronic valve closure failure (leaky valve) occurred si- multaneously.
Check the solenoid valves on the indoor unit for leaks.

Drain pump fault (Models with a float switch)
When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in water. Sensor in the air
When it is detected that the float switch has been OFF for 15 seconds, it is interpreted that the sensor tip is not immersed in water. 2) If it is detected that the float switch has been ON for 3 minutes after the immersion of the sensor tip was detected, this is con- sidered a drain pump failure, and "2502" appears on the monitor.
The total time it takes for this error to be detected is 3 minutes and 15 seconds, including the time it takes for the first im-
mersion of the sensor tip to be detected. 3) Detection of drain pump failure is performed while the unit is stopped. 4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met. "Liquid pipe temperature - inlet temperature - 10°C [ -18°F] " has been detected for 30 minutes. It is detected by the float switch that the sensor tip has been immersed in water for 15 minutes or more. The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage
of the outdoor unit. 5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant circuit that are in any mode other than Fan or Stop to an error stop. 6) Forced stoppage of the outdoor unit Detection timing: The error is detected whether the unit is in operation or stopped. This error is detected whether the unit is in operation or stopped. 7) Ending criteria for the forced stoppage of outdoor unit Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig- erant circuit. Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller. (Note) Items 1) - 3) and 4) - 7) are detected independently from each other.
The address and attribute that appear on the remote controller are those of the indoor unit (or OA processing unit) that caused the error.
Cause Check method and remedy
(1) Drain pump failure Check for proper functioning of the drain pump mechanism
(2) Drain water drainage problem
Check for proper drainage.
Clogged drain pump Clogged drain piping
(3) Stuck float switch Check for slime in the moving parts of the float switch.
Check for normal operation of the float switch.
(4) Float switch failure Check the resistance with the float switch turned on and turned off.
(5) Indoor unit control board failure
Replace indoor unit control board.
Drain pump drive circuit failure Float switch input circuit failure
(6) Items (1) through (5) above and an indoor unit electronic valve closure failure (leaky valve) occurred simultane- ously.
Check the solenoid valves on the indoor unit for leaks.

Drain sensor (Thd) fault
error, and the unit goes into the 3-minute restart delay mode. If another episode of the above condition is detected during the preliminary error, this is considered a drain sensor error.(If
the short or open circuit of the thermistor is no longer detected, normal operation will be restored in 3 minutes.) This error is detected when one of the following conditions are met.
During Cool/Dry operation Liquid pipe temperature minus inlet temperature is equal to or smaller than - 10°C[ -18°F] (except during the defrost cycle) When the liquid temperature thermistor or suction temperature thermistor or short or open circuited. Drain pump is in operation. One hour has elapsed since the drain sensor went off.
Cause Check method and remedy
(1) Faulty connector (CN31) insertion. 1) Check for connector connection failure. Reinsert the connector, restart the operation, and check for proper operation.
(2) Broken or semi-broken thermistor wire 2) Check for a broken thermistor wire.
(3) Thermistor failure 3) Check the resistance of the thermistor. 0°C[32 °F]:6.0k 10°C[50 °F]:3.9k 20°C[68°F]:2.6k 30°C[86°F]:1.8k 40°C[104 °F]:1.3k
(4) Indoor unit control board (error detection circuit) failure

Water leakage
Water supply cutoff
2. Cause, check method and remedy
Cause Check method and remedy
(1) The water tank of the humidifier is empty. Check the amount of supply water. Check for the solenoid valve and for the connection.
(2) The solenoid valve for humidification is OFF. Check the connector.
(3) Disconnected float switch Check the connecting part.
(4) Poor operation of float switch Check for the float switch.
(5) Frozen water tank Turn off the power source of the water tank to defrost, and turn it on again.

Out-of-range outside air temperature
eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm- istor temperature to determine when two outdoor units are in operation.) The compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop. (The
error display needs to be canceled by setting the remote controller.) Outdoor temperature error is canceled if the units stop during error stop. (The error display needs to be canceled by setting
the remote controller.)
Cause Check method and remedy
(1) Thermistor failure Check thermistor resistance.
(2) Pinched lead wire Check for pinched lead wire.
(3) Torn wire coating Check for wire coating.
(4) A pin on the male connector is missing or contact failure
Check connector.
(5) Disconnected wire Check for wire.
(6) Thermistor input circuit failure on the control board
Check the intake temperature of the sensor with the LED monitor. When the temperature is far different from the actual temper- ature, replace the control board.
-40 C [ -40 F ] and below (130 k ) Short detection 110 C [230 F ] and above (0.4 k )
· Open detection

4102 (THMU-A)
Open phase
The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
Cause Check method and remedy
(1) Power supply problem
Check the input voltage to the power supply terminal block TB1.
Open phase voltage of the power supply Power supply voltage drop
(2) Noise filter problem
Check the coil connections. Check for coil burnout. Confirm that the voltage at the CN02 connector is 188 V or
Coil problem Circuit board failure
above.
(3) Wiring failure Confirm that the voltage at the control board connector CNAC is 188 V or above. If the voltage is below 188V, check the wiring connection between the noise filter board CN02 and control board CNAC. P72 model Confirm that the wiring between TB23 and INV board SC-T is put through CT3. P96 and P120 models Confirm that the wiring between the coil L3 and TB23 is put through ACCT3.
(4) Blown fuse Check F01 on the control board, F4, and F5 for a blown fuse. ->If a blown fuse is found, check for a short-circuiting or earth fault of the actuator.
(5) CT3 failure P72 model Replace the inverter if this problem is detected after the compres- sor has gone into operation. P96 and P120 models Replace the ACCT3 if this problem is detected after the compres- sor has gone into operation.
(6) Control board failure Replace the control board if none of the above is causing the problem.

4102 (YHMU-A)
Open phase
The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
Cause Check method and remedy
(1) Power supply problem
Check the input voltage to the power supply terminal block TB1.
Open phase voltage of the power supply Power supply voltage drop
(2) Noise filter problem
Check the coil connections. Check for coil burnout. Check that the voltage across TB21 and TB22 on the noise filter
Coil problem Circuit board failure
board is 414V or above.
(3) Wiring failure Confirm that the voltage at the control board connector CNAC is 190 V or above. If the voltage is below 190, check the wiring between noise filter CN6, noise filter CN2, transformer box, and control board CNAC. Confirm that the wiring between noise filter TB23 and INV board SC-L3 is put through CT3.
(4) Blown fuse Check F01 on the control board, F4, and F5 for a blown fuse. ->If a blown fuse is found, check for a short-circuiting or earth fault of the actuator.
(5) CT3 failure Replace the inverter if this problem is detected after the compres- sor has gone into operation.
(6) Control board failure Replace the control board if none of the above is causing the problem.

<Transmission power supply fault error detail FF (Outdoor unit)> 2. Error definition and error detection method Transmission power output failure
<Transmission power supply fault other than error detail code FF (Outdoor unit)> 2. Error definition and error detection method Transmission power reception failure

4115 (THMU-A)
Power supply signal sync error
Cause Check method and remedy
(1) Power supply error Check the voltage of the power supply terminal block (TB1).
(2) Noise filter problem
Check the coil connections. Check for coil burnout. Confirm that the voltage at the CN02 connector is
Coil problem Circuit board failure
188 V or above.
(3) Faulty wiring Check fuse F01 on the control board (or F1, F2).
(4) Wiring failure Between noise filter board CN02 and control board CNAC
Confirm that the voltage at the control board con- nector CNAC is 188 V or above.
(5) Control board failure If none of the items described above is applicable, and if the trouble reappears even after the power is switched on again, replace the control board.
4115 (YHMU-A)
Power supply signal sync error
Cause Check method and remedy
(1) Power supply error Check the voltage of the power supply terminal block (TB1).
(2) Noise filter problem
Check the coil connections. Check for coil burnout. Check that the voltage across TB21 and TB22 on
Coil problem Circuit board failure
the noise filter board is 414V or above.
(3) Faulty wiring Check F01 on the control board, F4, and F5 for a blown fuse.
(4) Wiring failure Between noise filter CN3, noise filter CN2, transformer box, and control board CNAC
Confirm that the voltage at the control board con- nector CNAC is 190 V or above.
(5) Control board failure If none of the items described above is applicable, and if the trouble reappears even after the power is switched on again, replace the control board.

RPM error/Motor error
The motor keep running even if the power is OFF. The thermal overload relay is ON. (Only for the three-phase model) Indoor unit
If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected again, the display will appear.
Cause Check method and remedy
(1) Board failure Replace the board.
(2) Motor malfunction Check for the motor and the solenoid switch.
(3) Solenoid switch malfunction

4220 4225 (THMU-A)
Abnormal bus voltage drop (Detail code 108)
Check whether the unit makes an instantaneousstop when the detection result is abnormal or a power failure occurs. Check whether the power voltage is 188V or less across all phases. (2) Voltage drop detected
4220 P72 model Check the voltage between the tab terminal TB-P and TB-N on the INV board while the inverter is stopped. -> Check the fol-
lowing items if it is 253V or above.
1) Confirm on the LED monitor that the bus voltage is above 160 V. Replace the INV board if it is below 160 V. 2) Check the voltage at CN505 on the control board. ->Go to (3). 3) Check the coil connections (L1 - L3) and for coil burnout. 4) Check the wiring connections between the following sections Between the noise filter board and INV board. Between the INV board and DCL. Between the INV board and C1. Replace 72C if no problems are found.-> Check the following items if the voltage is below 253V. 1) Check the coil connections (L1 - L3) and for coil burnout. 2) Check the wiring between the noise filter board and INV board. 3) Check the connection to SC-P1 and SC-P2 on the INV board. 4) Check the in-rush current resistor value. Replace the INV board if no problems are found.
P96 and P120 models Check the voltage between SC-P1 and IPM N terminals on the INV board while the inverter is stopped.
-> Check the following items if it is 253V or above.
1) Confirm on the LED monitor that the bus voltage is above 160 V. Replace the INV board if it is below 160 V. 2) Check the voltage at CN505 on the control board. ->Go to (3). 3) Check the coil connections (L1 - L3) and coil burnout. 4) Check the resistance of the diode stack. ->Refer to IX [4] -7- (6). 5) Check the wiring connections between the following sections: Between the noise filter board and INV board. Between the INV board and C1. Replace the noise filter board if no problems are found. -> Check the following items if the voltage is below 253 V. 1) Check the connection to SC-P1 and IPM N on the INV board. 2) Check the wiring between the noise filter board and INV board. 3) Check the resistance of the diode stack. ->Refer to IX [4] -7- (6). 4) Check the in-rush current resistor value. ->Refer to IX [4] -7- (4). 5) Replace the noise filter board.
4225 Check the voltage at CNVDC on the Fan board while the inverter is stopped.
->Check the following items if it is 253 V or above.
Confirm that a voltage of 208-230 VAC is applied to the connector CN505 on the control board during inverter operation. ->If voltage is absent, check the control board, fuse F01, or (F1, F2). If no problems are found, replace the control board.
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

4220 4225 (YHMU-A)
Abnormal bus voltage drop (Detail code 108)
Check whether the unit makes an instantaneous stop when the detection result is abnormal or a power failure occurs. Check whether the power voltage (Between L1 and L2, L2 and L3, and L1 and L3) is 414V or less across all phases. (2) Voltage drop detected
4220 Check the voltage between the FT-P and FT-N terminals on the INV board while the inverter is stopped and if it is 420 V or
above, check the following items.
1) Confirm on the LED monitor that the bus voltage is above 289V. Replace the INV board if it is below 289 V. 2) Check the voltage at CN72 on the control board. ->Go to (3). 3) Check the noise filter coil connections and for coil burnout. 4) Check the wiring connections between the following sections Between the noise filter board and INV board. Between the INV board and DCL. Replace 72C if no problems are found. 5) Check the IGBT module resistance on the INV board (Refer to the Trouble shooting for IGBT module). Check the voltage between the FT-P and FT-N terminals on the INV board while the inverter is stopped and if it is less than
420 V, check the following items. 1) Check the coil connections and for coil burnout on the noise filter. 2) Check the wiring between the noise filter board and INV board. 3) Check the connection to SCP1 and SC-P2 on the INV board. 4) Check the in-rush current resistor value. 5) Check the 72C resistance value. 6) Check the DCL resistance value. Replace the INV board if no problems are found.
4225 Check the voltage at CNVDC on the Fan board while the inverter is stopped and if it is 420 V or above, check the following
items.
items.
Check that 12VDC is applied to connector CN72 on the control board while the inverter is operating. If voltage is absent or the wrong voltage is applied, check the fuse F01. Replace the control board if no problems are found with the fuse.
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

4220 4225 (THMU-A)
Abnormal bus voltage rise (Detail code 109)
Check the power supply voltage on the power supply terminal block (TB1). (2) INV board failure
If the problem recurs, replace the INV board. In the case of 4220: INV board In the case of 4225: Fan board
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)
4220 4225 (YHMU-A)
Abnormal bus voltage rise (Detail code 109)
Check the power supply voltage on the power supply terminal block (TB1). (2) INV board failure
If the problem recurs, replace the INV board. In the case of 4220: INV board In the case of 4225: Fan board
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

4220 4225 (THMU-A) (P96 and P120 models)
VDC error (Detail code 110)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

4220 4225 (THMU-A)
Logic error (Detail code 111)
Cause Check method and remedy
(2) INV board failure Refer to IX [4] -7- (2) [1].(page 295)
(3) IPM failure (P96 and P120 models only) Replace the IPM.
(4) DCCT failure (P96 and P120 models only) Replace the DCCT.
Cause Check method and remedy
(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 296)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)
(1) External noise · (1) External noise

4220 4225 (YHMU-A)
Logic error (Detail code 111)
Cause Check method and remedy
(2) INV board failure Refer to IX [4] -7- (2) [1].(page 303)
Cause Check method and remedy
(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 304)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)
4220 4225 (YHMU-A)
Low bus voltage at startup (Detail code 131)
Same as detail code 108 of 4220 error
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)
(1) External noise · (1) External noise

4230 (THMU-A)
Heatsink overheat protection
P72 model 100°C [212°F]
P96, P120 models 90°C [194°F]
Cause Check method and remedy
(1) Fan board failure Refer to IX [4] -7- (2) [6].(page 296)
(2) Outdoor unit fan failure Check the outdoor unit fan operation. If any problem is found with the fan operation, check the fan motor. ->Refer to IX [4] -7- (2) [5].(page 296)
(3) Air passage blockage Check that the heat sink cooling air passage is not blocked
(4) THHS failure P72 model
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)
Model TOH · P96 andP120 models

4230 (YHMU-A)
Heatsink overheat protection
Cause Check method and remedy
(1) Fan board failure Refer to IX [4] -7- (2) [6].(page 304)
(2) Outdoor unit fan failure Check the outdoor unit fan operation. If any problem is found with the fan operation, check the fan motor. ->Refer to IX [4] -7- (2) [5].(page 304)
(3) Air passage blockage Check that the heat sink cooling air passage is not blocked
(4) THHS failure 1) Check for proper installation of the INV board IGBT. (Check for proper instal- lation of the IGBT heatsink.)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

4240 (THMU-A)
Overload protection
P96, P120 model 53
P72 model 95°C [203°F]
P96, P120 model 80°C [175°F]
Cause Check method and remedy
(1) Air passage blockage Check that the heat sink cooling air passage is not blocked
(2) Power supply environment Power supply voltage is 188 V or above.
(3) Inverter failure Refer to IX [4] -7-.(page 293)
(4) Current sensor (ACCT) failure Refer to IX [4] -7- (4).
(5) Compressor failure Check that the compressor has not overheated during operation. -> Check the refrigerant circuit (oil return section). Refer to IX [4] -7- (2) [2].(page 295)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)
Model Imax(Arms) · P72 model 35 · Model TOL

4240 (YHMU-A)
Overload protection
P96 , P120 model 27
Cause Check method and remedy
(1) Air passage blockage Check that the heat sink cooling air passage is not blocked
(2) Power supply environment Power supply voltage is 414 V or above.
(3) Inverter failure Refer to IX [4] -7-.(page 301)
(4) Compressor failure Check that the compressor has not overheated during operation. -> Check the refrigerant circuit (oil return section). Refer to IX [4] -7- (2) [2].(page 303)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)
Model Imax(Arms) · P72 model 19

4250 4255 (THMU-A)
IPM error (Detail code 101)
Cause Check method and remedy
(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 295)
P96 and P120 models
Cause Check method and remedy
(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 295)
(2) Same as 4230 error Same as 4230 error
Cause Check method and remedy
(1) Fan motor abnormality Refer to IX [4] -7- (2) [5].(page 296)
(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 296)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

4250 4255 (YHMU-A)
IPM error (Detail code 101)
Cause Check method and remedy
(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 303)
Check the IGBT module resistance value of the INV board, if no problems are found. (Refer to the Trouble shooting for IGBT module)
Cause Check method and remedy
(1) Fan motor abnormality Refer to IX [4] -7- (2) [5].(page 304)
(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 304)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

4250 (THMU-A)
ACCT overcurrent (H/W detection) (Detail code 102) DCCT overcurrent (H/W detection) (Detail code 103) Instantaneous overcurrent (Detail code 106) Overcurrent (Detail code 107)
Cause Check method and remedy
(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 295)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

4250 (YHMU-A)
Instantaneous overcurrent (Detail code 106) Overcurrent (Detail code 107)
Cause Check method and remedy
(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4]. (page 303)
Check the IGBT module resistance value of the INV board, if no problems are found. (Refer to the Trouble shooting for IGBT module)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)
4250 4255
Short-circuited IPM/Ground fault (Detail code 104)
Cause Check method and remedy
(1) Grounding fault compressor Refer to IX [4] -7- (2) [2].
(2) Inverter output related Refer to IX [4] -7- (2) [1] - [4].
Cause Check method and remedy
(1) Grounding fault of fan motor Refer to IX [4] -7- (2) [5].
(2) Fan board failure Refer to IX [4] -7- (2) [6].
Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.

4250 4255
Overcurrent error due to short-circuited motor (Detail code 105)
Cause Check method and remedy
(1) Short - circuited compressor Refer to IX [4] -7- (2) [2].
(2) Output wiring Check for a short circuit.
Cause Check method and remedy
(1) Short - circuited fan motor Refer to IX [4] -7- (2) [5].
(2) Output wiring Check for a short circuit.
Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.
4260 (THMU-A)
Heatsink overheat protection at startup
P72 model 100°C [212°F]
P96, P120 models 90°C [194°F]
Model TOH

4260 (YHMU-A)
Heatsink overheat protection at startup

Return air temperature sensor (TH21) fault (Indoor unit) Return air temperature sensor (TH4) fault (OA processing unit)
Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit)
Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit)
Intake air temperature sensor (TH1) fault (OA processing unit) Intake air temperature sensor (TH24) fault (All-fresh (100% outdoor air) type indoor unit)
error is not restored after 3 minutes (if restored, the outdoor unit runs normally), the outdoor unit makes an error stop. Short: detectable at 90°C [194°F] or higher Open: detectable at -40°C [-40°F] or lower Sensor error at gas-side cannot be detected under the following conditions.
During heating operation During cooling operation for 3 minutes after the compressor turns on.
Cause Check method and remedy
(1) Thermistor failure Check the thermistor resistor. 0°C [32°F]: 15 kohm 10°C [50°F]: 9.7 kohm 20°C [68°F] : 6.4 kohm 30°C [86°F] : 4.3 kohm 40°C [104°F] : 3.1 kohm
(2) Connector contact failure
(3) Disconnected wire or partial disconnected thermistor wire
(4) Unattached thermistor or contact failure
(5) Indoor board (detection circuit) failure Check the connector contact. When no fault is found, the indoor board is a failure.

Heat exchanger outlet temperature sensor (TH3) fault (Outdoor unit)
Discharge temperature sensor (TH4) fault (Outdoor unit)
Accumulator inlet temperature sensor (TH5) fault (Outdoor unit)
Heat exchanger inlet temperature sensor (TH6) fault (Outdoor unit)
Outside temperature sensor (TH7) fault (Outdoor unit)
the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit
stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within the normal range. When a short or an open is detected again (the third detection) after the previous restart of the outdoor unit, the outdoor unit
makes an error stop. When a short or an open of the thermistor is detected just before the restart of the outdoor unit, the outdoor unit makes an
error stop, and the error code "5102", "5103", 5104", "5105", "5106"or "5107" will appear. During 3-minute antirestart mode, preliminary errors will be displayed on the LED display. A short or an open described above is not detected for 10 minutes after the compressor start, during defrost mode, or for 3
minutes after defrost mode.
Cause Check method and remedy
(1) Thermistor failure Check thermistor resistance.
(2) Pinched lead wire Check for pinched lead wire.
(3) Torn wire coating Check for wire coating.
(4) A pin on the male connector is missing or contact failure
Check connector.
(5) Disconnected wire Check for wire.
(6) Thermistor input circuit failure on the control board
Check the intake temperature of the sensor with the LED monitor. When the temperature is far different from the actual temper- ature, replace the control board.
110 C [230 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
240 C [464 F ] and above (0.57 k )
0 C [ 32 F ] and below (698 k )
70 C [158 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
70 C [158 F ] and above (1.14 k )
-40 C [ -40 F ] and below (130 k )
110 C [230 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
· Short detection · Open detection

5110 (THMU-A)
Heatsink temperature sensor (THHS) fault (Detail code 01)
Cause Check method and remedy
(1) INV board failure If the problem recurs when the unit is put into operation, replace the INV board.
P96 and P120 models
Cause Check method and remedy
(1) THHS sensor failure Check the THHS sensor reading on the LED monitor. Replace the sensor if it reads below - 30°C[ -22°F] or above 150°C[302°F].
(2) Contact failure Check the connector connection (CNTH) on the INV board.
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)
5110 (YHMU-A)
Heatsink temperature sensor (THHS) fault (Detail code 01)
Cause Check method and remedy
(1) INV board failure If the problem recurs when the unit is put into operation, replace the INV board.
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Liquid inlet temperature sensor (TH11) fault (BC controller)
Bypass outlet temperature sensor (TH12) fault (BC controller)
LEV3 outlet temperature sensor (TH15) fault (BC controller)
LEV3 inlet temperature sensor (TH16) fault (BC controller)
during operation, the unit makes an error stop, and an error code "5111," "5112," "5115," or "5116" appears on the display. Detection of a short- or open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the
operation mode is changed.
Cause Check method and remedy
(1) Thermistor failure Check thermistor resistance.
(2) Pinched lead wire Check for pinched lead wire.
(3) Torn wire coating Check for wire coating.
(4) A pin on the male connector is missing or contact failure
Check connector.
(5) Disconnected wire Check for wire.
(6) Thermistor input circuit failure on the control board
Check the intake temperature of the sensor with the LED monitor. When the temperature is far different from the actual temper- ature, replace the control board.
110 C [230 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
110 C [230 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
70 C [158 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
110 C [230 F ] and above (0.4 k )
-40 C [ -40 F ] and below (130 k )
· Short detection · Open detection

High-pressure sensor fault (63HS1)
restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more. If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and
the error code "5201" will appear. During 3-minute antirestart mode, preliminary errors will be displayed on the LED display. A error is not detected for 3 minutes after the compressor start, during defrost operation, or 3 minutes after defrost operation.
Cause Check method and remedy
(1) High pressure sensor failure Refer to the page on the troubleshooting of the high pressure sensor. (IX [4] -1- (page 273))
(2) Pressure drop due to refrigerant leak
(3) Torn wire coating
(4) A pin on the male connector is missing or contact failure
(6) High pressure sensor input circuit failure on the control board
(5) Disconnected wire

High-pressure sensor fault (Outdoor unit HPS/BC controller PS1)
Intermediate pressure sensor fault (BC controller PS3)
Cause Check method and remedy
(1) High pressure sensor failure Refer to the page on the troubleshooting of the high pressure sensor. (IX [4] -1-(page 273))
(2) Pressure drop due to refrigerant leak
(3) Torn wire coating
(4) A pin on the male connector is missing or contact failure
(6) High pressure sensor input circuit failure on the control board
(5) Disconnected wire

5301 (THMU-A)
ACCT sensor fault (Detail code 115)
Cause Check method and remedy
(1) Inverter open output phase Check the output wiring connections.
(2) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
(3) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 295)
P96 and P120 models
Cause Check method and remedy
(1) Inverter open output phase Check the output wiring connections.
(2) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
(3) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 295)
(4) Contact failure Check the connection of the connector (CNCT2) on the INV board- INV board.
(5) ACCT sensor failure Refer to IX [4] -7- (4).
Refer to section -7-"Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)
5301 (YHMU-A)
ACCT sensor fault (Detail code 115)
Cause Check method and remedy
(1) Inverter open output phase Check the output wiring connections.
(2) Compressor failure Refer to IX [4] -7- (2) [2].(page 303)
(3) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 303)
Refer to section -7-"Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

5301 (THMU-A) (P96 and P120 models only)
DCCT sensor fault (Detail code116)
Cause Check method and remedy
(1) Contact failure Check the contact of the connector (CNCT) on the INV board, and the contact the connector on DCCT side.
(2) Misorientation Check the installation direction of DCCT.
(3) DCCT sensor failure Replace the DCCT sensor.
(4) INV board failure Replace the INV board.
Refer to section -7-"Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

ACCT sensor circuit fault (Detail code 117)
Cause Check method and remedy
(1) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].
(2) Compressor failure Refer to IX [4] -7- (2) [2].
Refer to section -7-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.

5301 (THMU-A) (P96 and P120 model only)
DCCT sensor circuit fault (Detail code118)
Cause Check method and remedy
(1) Contact failure Check for good contact of the INV board connector CNCT and the connec- tor on the DCCT side.
(2) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 295)
(3) DCCT sensor failure Replace the DCCT sensor.
(4) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
(5) Inverter failure Refer to IX [4] -7-.(page 293)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

5301 (THMU-A)
Open-circuited IPM/Loose ACCT connector (Detail code 119)
Cause Check method and remedy
(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.
(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)
(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
P96 and P120 models
Cause Check method and remedy
(1) ACCT sensor disconnection Check the connection of the connector (CNCT2) on the INV board. Check for proper mounting of ACCT.
(2) ACCT sensor failure Refer to IX [4] -7- (4).
(3) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)
(4) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

5301 (YHMU-A)
Open-circuited IPM/Loose ACCT connector (Detail code 119)
Cause Check method and remedy
(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.
(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 304)
(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 303)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)
5301 (THMU-A)
Faulty ACCT wiring (Detail code 120)
Cause Check method and remedy
(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.
(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)
(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
(4) INV board failure Replace the INV board.
P96 and P120 models
Cause Check method and remedy
(1) Wrongly mounted ACCT sensor Check for proper mounting of ACCT. Refer to IX [4] -7- (4).
(2) ACCT sensor failure Refer to IX [4] -7- (4).
(3) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)
(4) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

5301 (YHMU-A)
Faulty ACCT wiring (Detail code 120)
Cause Check method and remedy
(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.
(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 304)
(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 303)
Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Temperature sensor fault
Cause Check method and remedy
(1) Connector contact failure (CN30) (Loose con- nector)
(2) Broken or partially broken humidity sensor wire 2) Check for broken humidity sensor wire.
(3) Humidity sensor fault 3) Check the output voltage across No. 1 and No. 3 pins of connector CN30 with the connector being connected to the indoor unit control board.
30% : 1.25V 40% : 1.52V 50% : 1.88V 60% : 2.19V 70% : 2.48V 80% : 2.79V
(4) Indoor unit control board (detection circuit) fault 4) If the above items check out okay, replace the indoor unit control board.

Loose float switch connector
Check for disconnection of the connector (CN4F) on the indoor unit control board.
Remote controller board fault (nonvolatile memory error)
Replace the remote controller.
Remote controller board fault (clock IC error)
Replace the remote controller.

Address overlaps
The address and attribute that appear on the remote controller indicate the controller that detected the error.
Cause Check method and remedy
Two or more of the following have the same address: Outdoor units, indoor units, LOSSNAY units, control- lers such as M-NET remote controllers. 6600 "01" appears on the remote controller Unit #01 detected the error. Two or more units in the system have 01 as their ad- dress.
Find the unit that has the same address as that of the error source. Once the unit is found, correct the address. Then, turn off the outdoor units, indoor units, and LOSS- NAY units, keep them all turned off for at least five minutes, and turn them back on.
Polarity setting error
Cause Check method and remedy
(1) No voltage is applied to the M-NET transmission line that G(B)-50A is connected to.
Check if power is supplied to the M-NET transmission line of the G(B)-50A, and correct any problem found.
(2) M-NET transmission line to which G(B)-50A is con- nected is short-circuited.

Transmission processor hardware error
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
3. Cause 1) When the wiring work of or the polarity of either the indoor or outdoor transmission line is performed or is changed while the power is on, the transmitted data will collide, the wave shape will be changed, and an error will be detected. 2) Grounding fault of the transmission line 3) When grouping the indoor units that are connected to different outdoor units, the male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector (CN40). 4) When the power supply unit for transmission lines is used in the system connected with MELANS, the male power supply connector is connected to the female power supply switch connector (CN40) on the outdoor unit. 5) Controller failure of the source of the error 6) When the transmission data is changed due to the noise on the transmission line 7) Voltage is not applied on the transmission line for centralized control (in case of grouped indoor units connected to different outdoor units or in case of the system connected with MELANS)
Is the transmission line work performed while the power is on?
Turn off the power source of outdoor/indoor units, and turn them on again.
Check the power source of the indoor unit.
NO
Faulty power source work
Check the transmission line work is performed and the shielded wire is treated properly.
Grounding fault or does the shielded wire contact with the transmission line?
Improper transmission line work
Single-outdoor-unit system Multiple-outdoor-unit system
System with the power supply unit for transmission lines
Confirm that the power supply connector on the outdoor unit is not plugged into CN40.
Confirm that the power supply connector on the outdoor unit is not plugged into CN40.
Is the male power supply connector connected to the female power supply switch connector (CN40) on only one of the outdoor unit?
NO
Is the male power supply connector connected to the female power supply switch connector (CN40) ?
YES
Tightly reconnect the male power supply connector to the female power supply switch connector (CN40).
Disconnect the male power supply on CN40 and connect it to CN41
Investigation into the transmission line noise
*For the investigation method, follow
Investigation into the cause of the noise
Controller failure of the source of the error
Correct the error.
System ? · Noise exist?

Transmission line bus busy error
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Cause Check method and remedy
(1) The transmission processor cannot be transmit- ted as the short-wavelength voltage like noise ex- ists consecutively on the transmission line.
No noise indicates that the error source controller is a fail- ure. If noise exists, investigate the noise.
-> No noise indicates that the error source controller is a
failure. -> If noise exists, investigate the noise.
(2) Error source controller failure
Communication error between device and transmission processors
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Cause Check method and remedy
(1) Data is not properly transmitted due to accidental erroneous operation of the controller of the error source.
Turn off the power source of the outdoor and the indoor units.(When the power source is turned off separately, the microcomputer will not be reset, and the error will not be corrected.)
(2) Error source controller failure
-> If the same error occurs, the error source controller is
a failure.

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET remote controller (RC) MA re- mote con- troller (MA)
No ac- knowl- edgement (ACK) at IC trans- mission to OC
(1) Contact failure of transmission line of OC or IC Turn off the power source of the outdoor unit, and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (4).
(2) Decrease of transmission line voltage/signal by ex- ceeding acceptable range of transmission wiring. Farthest:200 m [656ft] or less Remote controller wiring: 10m [32ft] or less
(3) Erroneous sizing of transmission line (Not within the range below). Wire diameter: 1.25mm2 [AWG16] or more
(4) Indoor unit control board failure
M-NET remote controller (RC) MA re- mote con- troller (MA)
No ac- knowl- edgement (ACK) at IC trans- mission to BC
(1) When BC controller address is changed or modified during operation.
Turn off the outdoor/in- door units for 5 or more minutes, and turn them on again. If the error is accidental, they will run normally. If not, check the causes (1) - (4).
(2) Faulty or disconnected transmission wiring of BC controller
(3) Disconnected connector of BC controller (CN02)
(4) Faulty control board of BC controller
M-NET remote controller (RC) MA re- mote con- troller (MA)
No ac- knowl- edgement (ACK) at RC trans- mission to IC
(1) When IC unit address is changed or modified during operation.
Turn off the outdoor/in- door units for 5 or more minutes, and turn them on again. If the error is accidental, they will run normally. If not, check the causes (1) - (5).
(2) Faulty or disconnected IC transmission wiring
(3) Disconnected IC connector (CN2M)
(4) Indoor unit controller failure
(5) M-NET remote controller failure
M-NET remote controller (RC) MA re- mote con- troller (MA)
No ac- knowl- edgement (ACK) at IC trans- mission to LC
(1) The power source of LOSSNAY has been shut off. Turn off the power source of LOSSNAY and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (5).
(2) When the address of LOSSNAY is changed in the middle of the operation
(3) Faulty or disconnected transmission wiring of LOSSNAY
(4) Disconnected connector (CN1) on LOSSNAY
(5) Controller failure of LOSSNAY
M-NET remote control- ler (RC)
M-NET remote controller (RC) MA re- mote con- troller (MA)
No ac- knowl- edgement (ACK) at IC trans- mission to RC
(1) Faulty transmission wiring at IC unit side. Turn off the power source of the outdoor unit for 5 minutes or more, and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (4).
(2) Faulty wiring of the transmission line for M-NET re- mote controller
(3) When the address of M-NET remote controller is changed in the middle of the operation
(4) M-NET remote controller failure

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET re- mote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmission to OC
Same cause as that for system with one outdoor unit
Same remedy as that for sys- tem with one outdoor unit
M-NET re- mote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmission to BC
Same cause as that for system with one outdoor unit
Same remedy as that for sys- tem with one outdoor unit
M-NET re- mote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at RC transmission to IC
(1) Same causes as (1) - (5) for sys- tem with one outdoor unit
(2) Disconnection or short circuit of the transmission line for the out- door unit on the terminal block for centralized control line connection (TB7)
(3) When multiple outdoor units are connected and the power source of one of the outdoor units has been shut off.
(4) The male power supply connector of the outdoor unit is not connect- ed to the female power supply switch connector (CN40).
If an error is found, -> If an error is found, check the check code definition, and correct the error. If no error is found, -> Indoor unit board failure (5) The male power supply connec- tors on 2 or more outdoor units are connected to the female pow- er supply switch connector (CN40) for centralized control.
If an error occurs, after the unit runs normally once, the following causes may be considered.
Total capacity error (7100) Capacity code error (7101) Error in the number of con-
nected units (7102) Address setting error (7105)

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET re- mote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmission to LC
(1) Factors (1) through (5) in the "Factors in system with one outdoor unit" (When perform- ing an interlocked operation of the LOSSNAY unit and the indoor units that are connect- ed to different outdoor units.)
(2) Disconnection or short circuit of the transmission line for the outdoor unit on the termi- nal block for centralized con- trol line connection (TB7)
(3) When multiple outdoor units are connected and the power source of one of the outdoor units has been shut off.
(4) The male power supply con- nector of the outdoor unit is not connected to the female power supply switch connec- tor (CN40).
(5) The male power supply con- nectors on 2 or more outdoor units are connected to the fe- male power supply switch connector (CN40) for central- ized control.
If an error occurs, after the unit runs normally once, the following causes may be con- sidered.
Total capacity error
(7100) Capacity code error
(7101) Error in the number of
connected units (7102) Address setting error
Error source address · Error display Detection · (7105)

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET re- mote con- troller (RC)
M-NET re- mote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmission to RC
(1) Same causes as (1) - (4) for system with one outdoor unit
(2) Disconnection or short circuit of the transmission line for the outdoor unit on the termi- nal block for centralized con- trol line connection (TB7)
(3) When multiple outdoor units are connected and the power source of one of the outdoor units has been shut off.
(4) The male power supply con- nector of the outdoor unit is not connected to the female power supply switch connec- tor (CN40).
(5) The male power supply con- nectors on 2 or more outdoor units are connected to the fe- male power supply switch connector (CN40) for central- ized control.
If the problem recurs after normal operation is restored, the problem is caused by one of the following factors:
Total capacity error
(7100) Capacity code setting
error (7101) Error in the number of
connected units (7102) Address setting error
Error source address · Error display Detection · (7105)

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET remote controller (RC) System control- ler (SC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmis- sion to OC
Same cause as that for system with one outdoor unit
Same remedy as that for system with one outdoor unit
M-NET remote controller (RC) system control- ler (SC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmis- sion to BC
Same cause as that for system with one outdoor unit
Same remedy as that for system with one outdoor unit

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET remote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at RC transmis- sion to IC
Same as grouping of units in a system with multiple outdoor units
Same remedy as that for grouping of units in a sys- tem with multiple outdoor units
No acknowl- edgement (ACK) at SC transmis- sion to IC
(1) Total capacity error (7100) If an error is found,
check the check code definition, and correct the error. If no error is found,
(2) Capacity code error (7101)
(3) Error in the number of connected units (7102)
check 2).
(4) Address setting error (7105)
(5) Disconnection or short circuit of the trans- mission line for the outdoor unit on the ter- minal block for centralized control line connection (TB7)
(6) Turn off the power source of the outdoor unit
(7) Malfunction of electrical system for the outdoor unit
(1) Same causes as (1) - (7) described in 2.
(2) The male power supply connectors on 2 or more outdoor units are connected to the female power supply switch connector (CN40) for the transmission line for cen- tralized control.
and (2) on the left. Less than 20V: Check
(3) on the left.
(3) Disconnection or shutdown of the power source of the power supply unit for trans- mission line
(4) System controller (MELANS) malfunction

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET re- mote con- troller (RC)
M-NET re- mote controller (RC) System con- troller (SC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmission to RC
Same as grouping of units in a sys- tem with multiple outdoor units
Same remedy as that for grouping of units in a system with multiple outdoor units
No acknowl- edgement (ACK) at MELANS transmission to RC
(1) An error is found by the outdoor unit. Total capacity error (7100) Capacity code error (7101) Error in the number of connected units (7102) Address setting error (7105)
If an error is found, check
the check code definition, and correct the error. If no error is found, check
the cause 2).
(2) Disconnection or short circuit of the transmission line for the outdoor unit on the terminal block for cen- tralized control line connection (TB7)
(3) Turn off the power source of the outdoor unit
(4) Malfunction of electrical system for the outdoor unit
(1) Same causes as (1) - (4) described in 2.
(2) When the power supply unit for transmission lines is used and the male power supply connector is connected to the female power supply switch connector (CN40) for the transmission line for central- ized control
(3) Disconnection or shutdown of the power source of the power supply unit for transmission line
(4) System controller (MELANS) mal- function
Error source address · Error display Detection · System con- troller (SC)

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
M-NET re- mote controller (RC) MA remote controller (MA)
No acknowl- edgement (ACK) at IC transmission to SC
Check (1) - (3) on the left.
(1) Faulty wiring of the transmission line for M-NET remote controller
(2) Disconnection or contact failure of the transmission connector for M- NET remote controller
(3) M-NET remote controller failure
(1) An error is found by the outdoor unit. Total capacity error (7100) Capacity code error (7101) Error in the number of connected units (7102) Address setting error (7105)
If an error is found, check
the check code definition, and correct the error. If no error is found, check
(2) Disconnection or short circuit of the transmission line for the outdoor unit on the terminal block for cen- tralized control line connection (TB7)
(3) Turn off the power source of the outdoor unit
(4) Malfunction of electrical system for the outdoor unit
Check (1) - (4) on the left
(1) Same causes as (1) - (4) described in 2.
(2) When the power supply unit for transmission lines is used and the male power supply connector is connected to the female power sup- ply switch connector (CN40) for the transmission line for centralized control
(3) Disconnection or shutdown of the power source of the power supply unit for transmission line
(4) System controller (MELANS) mal- function

No ACK error
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
method Cause Check method and remedy
Address which should not be existed
- - (1) Although the address of M- NET remote controller has been changed after the group is set using M-NET remote controller, the indoor unit is keeping the memory of the previous address. The same symptom will appear for the registration with SC.
Delete unnecessary informa- tion of non-existing address which some indoor units have. Use either of the following two methods for deletion.
(2) Although the address of LOSSNAY has been changed after the interlock registration of LOSSNAY is made using M- NET remote controller, the in- door unit is keeping the mem- ory of the previous address.
Turn off the power source of
the outdoor unit, and wait for 5 minutes. Turn on the dip switch (SW2-
the outdoor unit, and wait for 5 minutes. Turn off the power source of
the outdoor unit, and wait for 5 minutes. Turn off the dip switch (SW2-
the outdoor unit.

No response error
ed. When the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side.
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
3. Cause 1) The transmission line work is performed while the power is on, the transmitted data will collide, and the wave shape will be changed. 2) The transmission is sent and received repeatedly due to noise. 3) Decrease of transmission line voltage/signal by exceeding acceptable range of transmission wiring. Farthest:200m [656ft] or less Remote controller wiring:12m [39ft] or less 4) The transmission line voltage/signal is decreased due to erroneous sizing of transmission line. Wire diameter: 1.25mm2[AWG16] or more
4. Check method and remedy 1) When an error occurs during commissioning, turn off the power sources for the outdoor unit, indoor unit, BC controller, and LOSSNAY for 5 or more minutes, and then turn them on again. When they return to normal operation, the cause of the error is the transmission line work performed with the power on. If an error occurs again, check the cause 2). 2) Check 3) and 4) above. If the cause is found, correct it. If no cause is found, check 3). 3) Check transmission wave shape/ noise on trans-mission line by following "IX [3] Investigation of Transmission Wave Shape/ Noise" (page 270). Noise is the most possible cause of the error "6608".

MA controller signal reception error (No signal reception)
3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit. 2) All the remote controllers are set to SUB. 3) Failure to meet wiring regulations Wire length Wire size Number of remote controllers Number of indoor units 4) The remote controller is removed after the installation without turning the power source off. 5) Noise interference on the remote controller transmission lines 6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller 7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on. If LED2 is lit, the MA remote controller line is being powered.

MA remote controller signal transmission error (Synchronization error)
3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit 2) 2 or more remote controllers are set to MAIN 3) Overlapped indoor unit address 4) Noise interference on the remote controller lines 5) Failure to meet wiring regulations Wire length Wire size Number of remote controllers Number of indoor units 6) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on. If LED2 is lit, the MA remote controller line is being powered.

MA remote controller signal transmission error (Hardware error)
3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit 2) 2 or more remote controllers are set to MAIN 3) Overlapped indoor unit address 4) Noise interference on the remote controller lines 5) Failure to meet wiring regulations Wire length Wire size Number of remote controllers Number of indoor units 6) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on. If LED2 is lit, the MA remote controller line is being powered.

MA controller signal reception error (Start bit detection error)
3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit. 2) All the remote controllers are set to SUB. 3) Failure to meet wiring regulations Wire length Wire size Number of remote controllers Number of indoor units 4) The remote controller is removed after the installation without turning the power source off. 5) Noise interference on the remote controller transmission lines 6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller 7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on If LED2 is lit, the MA remote controller line is being powered.

Total capacity error
Error source Cause Check method and remedy
Outdoor unit (1) The model total of indoor units in the sys- tem with one outdoor unit exceeds the fol- lowing table.
When the model name set by the switch is differ- ent from that of the unit connected, turn off the power source of the outdoor and the indoor units, and change the setting of the model name (ca- pacity code).
(2) The model selection switches (SW5-1 - 5- 4) on the outdoor unit are set incorrectly. Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-1 - 5-4 on the outdoor unit control board).
1 2 3 4 Model
ON ON OFF OFF
OFF OFF ON OFF
(3) The outdoor unit and the auxiliary unit (OS) that is connected to the same system are not properly connected.
Confirm that the TB3 on the OC and OS are properly connected.

Capacity code setting error
Error source Cause Check method and remedy
Outdoor unit Indoor unit
(1) The model name (capacity code) set by the switch (SW2) is wrong.
*The capacity of the indoor unit can be confirmed by the self-diagnosis function (SW1 operation) of the outdoor unit.
Outdoor unit (2) The model selection switches (SW5-1 - 5-4) on the outdoor unit are set incor- rectly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-1 - 5-4 on the outdoor unit control board).
1 2 3 4 Model
OFF ON OFF OFF
ON ON OFF OFF
OFF OFF ON OFF
72 model · 96 model · 120 model

Wrong number of connected units
Error source Cause Check method and remedy
Outdoor unit (1) Number of indoor units connected to the outdoor terminal block (TB3) for indoor/ outdoor transmis- sion lines exceeds limitations described below.
Restriction on the number of units Number of units
Total number of indoor units
Number of BC controllers
1 (P72- P120 models only)
Number of Main BC controllers
Number of Sub BC controllers
Total number of LOSSNAY units (During auto address start-up only)
Total number of outdoor units
(2) Disconnected transmission line from the outdoor unit or BC controller
(3) Short-circuited transmission line When (2) and (3) apply, the following display will appear.
M-NET remote controller
Nothing appears on the remote controller be- cause it is not powered. MA remote controller
"HO" or "PLEASE WAIT" blinks.
(4) The model selection switch (SW5-7) on the out- door unit is set to OFF. (Normally set to ON)
(5) Outdoor unit address setting error The outdoor units in the same refrigerant circuit do not have sequential address numbers.
(6) In a system with the P700 models of units or larger, a BC controller other than the HA-type is used as the main BC controller.
0 or 1 · 0,1 or 2 · 0 or 1

Address setting error
Error source Cause Check method and remedy
Outdoor unit BC controller
Erroneous setting of OC unit address The address of outdoor unit is not being set to 51 - 100. The address of BC controller is not set to 51 - 100.
Check that the outdoor unit and BC controller addresses are set to 00 or a number between 51 and 100. If the outdoor unit address is out of the valid range, reset the address with the power to the outdoor unit turned off. If the BC controller address is out of the valid range, reset the address with the power to both the outdoor unit and BC controller turned off.
Attribute setting error
2. Error definition and error detection method
Error source Cause Check method and remedy
- A remote controller for use with indoor units, such as the MA remote controller, is connected to the OA processing unit whose attribute is FU.
To operate the OA processing unit directly via a re- mote controller for use with indoor units, such as the MA remote controller, set the DIP SW 3-1 on the OA processing unit to ON.
Interlocked operation with the indoor unit
Direct operation via the MA remote controller
Operation Method

Port setting error
Error source Cause Check method and remedy
BC controller (1) Model total of indoor units per each port or per each port merge is greater than the specification.
Before resetting the port number using the port number setting switch or the model using the model (capacity code) setting switch, turn off the power of the outdoor unit, the BC controller and the indoor unit.
Model total Total port number
2 branches merge 54
(2) 4 or more indoor units are connected to the same port.
(3) When two ports are used, the port with the smaller number is not connected to the indoor unit.
(4) For the address of the BC controller (Sub 1 or 2), 50 is not added to the smallest indoor unit address, which is connected to the BC controller (Sub1 or 2).
(5) In the system to which multiple BC controllers are connected, the indoor unit address connected to the BC controller is not set as shown below. (i) The indoor unit address which is connected to
the BC controller (main) (ii) The indoor unit address which is connected to
the BC controller (Sub1) (iii) he indoor unit address which is connected to
the BC controller (Sub2) Address setting
(i)
For the address of the BC controller (Sub), is 50 added to the smallest indoor unit address,
Is there a BC controller (Sub)?
NO Change the BC controller (Sub) address.
which is connected to the
YES
Are 4 or more indoor units connected to the same port?
YES
Port No. setting error?
Change the port No.
NO
Is the address of the indoor
Is the model total of indoor units connected to the same port
Adjust the piping connection to the port.
unit, which is connected to the the
BC controller (Main) ,smaller than
Change the indoor unit address or change the BC controller address
that of the indoor, which is
greater than the item (1)?
connected to the BC controller
(Sub 1 or 2)?
When two ports are used,
is the port with the smallest number
Port No. setting error?
Change the port No.
connected to the indoor unit?
NO
Is the address of the indoor
The wrong model (capacity code) is set.
YES Change the set indoor unit model (capacity code).
unit, which is connected to the the
BC controller (Main), smaller than
that of the indoor, which is
connected to the BC controller
(Sub 1 or 2)?
Adjust the piping connection to the port.
Change the port No.
Single branching · BC controller (Sub)?

Connection information signal transmission/reception error
Error source Cause Check method and remedy
Outdoor unit (1) Power to the transmission booster is cut off. 1) Confirm that the power to the transmission booster is not cut off by the booster being connected to the switch on the indoor unit. (The unit will not function properly unless the transmission booster is turned on.)
(2) Power resetting of the transmission booster and outdoor unit.
->Reset the power to the outdoor unit.
(3) Wiring failure between OC and OS 2) Confirm that the TB3 on the OC and OS are properly connected.
(4) Broken wire between OC and OS. 3) Check the model selection switch on the out- door unit (Dipswitch SW5-7 on the control board.). (5) The model selection switch (SW5-7) on the outdoor unit is set to OFF. (Normally set to ON)
Remote controller sensor fault
Error source Cause Check method and remedy
Indoor unit OA process- ing unit
The remote controller without the temperature sensor (the wireless remote controller or the M-NET compact remote controller (mounted type)) is used and the remote controller sen- sor for the indoor unit is specified. (SW1-1 is ON.)
Replace the remote controller with the one with built-in temperature sensor.

Function setting error (incorrect resistor connection)
2. Error source, cause, check method and remedy
Error source Cause Check method and remedy
Outdoor unit (1) Wiring fault (Detail code 15)
(2) Loose connectors, short-circuit, con- tact failure
(3) Incompatible control board and INV board (replacement with a wrong cir- cuit board)
(4) DIP SW setting error on the control board
(Detail code 00, 01, 05)
*If a set-model-name identification error occurs, check the detail code on the unit on which the error occurred. The detail code that appears on other units will be dif- ferent from the ones shown above.

Model setting error
2. Error source, cause, check method and remedy
Error source Cause Check method and remedy
Outdoor unit (1) Wiring fault (Detail code 15)
(2) Loose connectors, short-circuit, con- tact failure
(Detail code 00, 01, 05)
*If a set-model-name identification error occurs, check the detail code on the unit on which the error occurred. The detail code that appears on other units will be dif- ferent from the ones shown above.

Incompatible unit combination
Error source Cause Check method and remedy
Outdoor unit The connected indoor unit or BC controller is exclusively for use with R22 or R407C. An in- compatible indoor unit or BC controller is con- nected. The M-NET connection adapter is connected to the indoor unit system in a system in which the Slim Model (A control) of units are con- nected to the M-NET.
Check the model names of the connected in- door unit and the BC controller. Check whether the connecting adapter for M-NET is not connected to the indoor unit. (Connect the connecting adapter for M-NET to the outdoor unit.)

In the case of MA remote controller
(1) Cause 1) The power is not supplied to the indoor unit. The main power of the indoor unit is not on. The connector on the indoor unit board has come off. The fuse on the indoor unit board has melted. Transformer failure and disconnected wire of the indoor unit. 2) Incorrect wiring for the MA remote controller Disconnected wire for the MA remote controller or disconnected line to the terminal block. Short-circuited MA remote controller wiring Incorrect wiring of the MA remote controller cables Incorrect connection of the MA remote wiring to the terminal block for transmission line (TB5) on the indoor unit Wiring mixup between the MA remote controller cable and power supply cable Reversed connection of the wire for the MA remote controller and the M-NET transmission line on the indoor unit 3) The number of the MA remote controllers that are connected to an indoor unit exceeds the allowable range (2 units). 4) The length or the diameter of the wire for the MA remote controller are out of specification. 5) Short circuit of the wire for the remote display output of the outdoor unit or reversed polarity connection of the relay. 6) The indoor unit board failure 7) MA remote controller failure
(2) Check method and remedy 1) Measure voltages of the MA remote controller terminal (among 1 to 3). If the voltage is between DC 9 and 12V, the remote controller is a failure. If no voltage is applied, check the causes 1) and 3) and if the cause is found, correct it.
If no cause is found, refer to 2). 2) Remove the wire for the remote controller from the terminal block (TB13) on the MA remote controller for the indoor unit, and check voltage among 1 to 3. If the voltage is between DC 9 and 12 V, check the causes 2) and 4) and if the cause is found, correct it. If no voltage is applied, check the cause 1) and if the cause is found, correct it.
If no cause is found, check the wire for the remote display output (relay polarity). If no further cause is found, replace the indoor unit board.

(1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit. 2) Short circuit of the transmission line. 3) Incorrect wiring of the M-NETtransmission line on the outdoorunit. Disconnected wire for the MA remote controller or disconnected line to the terminal block. The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7). The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40). In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect- ed to the female power supply switch connector (CN40) on the outdoor unit. 4) Disconnected M-NET transmission line on the indoor unit side. 5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or disconnected connector.
(2) Check method and remedy 1) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
Same symptom for all units in a system with one outdoor unit?
Measure voltages of the terminal block for transmission line (TB5) on the indoor unit.
Check the self-diagnosis LED
Check 4.
YES
Check for 2 and 3.
Is the error code 7102
Check 5.
Check 1).
Correct the error.
Indoor unit board or MA remote controller failure
Correct the error.
Refer to section IX [4] -8- (2) for Troubleshooting transmission power circuit of outdoor unit.
displayed? · Error found?

(1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit. 2) Short-circuited transmission line 3) Incorrect wiring of the M-NET transmission line on the outdoor unit. Disconnected wire for the MA remote controller or disconnected line to the terminal block. The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7). The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40). In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect- ed to the female power supply switch connector (CN40) on the outdoor unit 4) Disconnected M-NET transmission line on the indoor unit. 5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or disconnected connector. 6) Incorrect wiring for the MA remote controller Short-circuited wire for the MA remote controller Disconnected wire for the MA remote controller (No.2) and disconnected line to the terminal block. Reversed daisy-chain connection between groups Incorrect wiring for the MA remote controller to the terminal block for transmission line connection (TB5) on the indoor unit The M-NET transmission line is connected incorrectly to the terminal block (TB13) for the MA remote controller. 7) The sub/main setting of the MA remote controller is set to sub. 8) 2 or more main MA remote controllers are connected. 9) Indoor unit board failure (MA remote controller communication circuit) 10) Remote controller failure 11) Outdoor unit failure (Refer to IX [8] Troubleshooting Using the Outdoor Unit LED Error Display.)(page 330)
(2) Check method and remedy 1) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
Same symptom for all units in a system with one outdoor unit?
Measure voltages of the terminal block for transmission line (TB5) on the indoor unit.
Check the self-diagnosis LED
17 - 30V?
Check 4.
Check 2 and 3.
Is the error code 7102
Check for 5 and 6.
YES
Correct the error.
Replace the M-NET remote controller with the MA remote controller
NO
Indoor unit board or MA remote controller failure
Check (1).
Correct the error.
Refer to section IX [4] -8- (2) for Troubleshooting transmission power circuit of outdoor unit.
displayed? · Error found? · Error found?

Flow chart Even if the operation button on the remote controller is pressed, the indoor and the outdoor units do not start running.

After the main power on, start the MA remote
indoor unit turn turned on again? DEMAND by MELANS?
Check that no error occurs in other indoor units.
9-13VDC if the voltage is applied and 0V if no voltage
*After correcting the error, daisy-chain the wire for the MA remote controller again.
9-13VDC if the voltage is applied and 0V if no voltage is applied.

(1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit. 2) Short circuit of the transmission line. 3) Incorrect wiring of the M-NET transmission line on the outdoor unit. Disconnected wire for the MA remote controller or disconnected line to the terminal block. The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7). 4) Disconnected transmission line on the remote controller. 5) Remote controller failure 6) Outdoor unit failure (Refer to IX [8] Troubleshooting Using the Outdoor Unit LED Error Display.)(page 330)
(2) Check method and remedy 1) Check voltage of the transmission terminal block for of the M-NET remote controller. If voltage between is 17V and 30V -> M-NET remote controller failure When voltage is 17V or less -> Refer to IX [4] -8- (2) . 2) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.

(1) Cause 1) The power is not supplied to the indoor unit.
The main power of the indoor unit (AC208/230V) is not on. The connector on the indoor unit board has come off. The fuse on the indoor unit board has melted. Transformer failure and disconnected wire of the indoor unit The indoor unit board failure 2) The outdoor control board failure As the indoor unit does not interact with the outdoor unit, the outdoor unit model cannot be recognized.

Check voltage of the power supply terminal on the indoor unit.
Check the main power of the power supply wire Turn on the power again.
Melted? Check 200V circuit for short circuit and ground fault
Check the cause of the disconnected transformer. Ground fault on the circuit board
Check for the change of LED display by operating dip switch SW1 for self-diagnosis.
Check self-diagnosis function of outdoor unit after the power on.

(1) Cause Without using MELANS 1) Outdoor unit address is set to "00" 2) A wrong address is set. The address of the indoor unit that is connected to the remote controller is incorrect. (It should equal the M-NET remote con-
troller address plus 100.) A wrong address is set to the M-NET remote controller. (100 must be added to the address of the indoor unit.) 3) Faulty wiring of the terminal block for transmission line (TB5) of the indoor unit in the same group with the remote controller. 4) The centralized control switch (SW2-1) on the outdoor unit is set to ON. 5) Disconnection or faulty wiring of indoor unit transmission line. 6) Disconnection between the terminal block for M-NET line connection (TB5) of the indoor unit and the male connector (CN2M) 7) The male power supply connectors on 2 or more outdoor units are connected to the female power supply switch connector (CN40) for the transmission line for centralized control. 8) Outdoor unit control board failure 9) Outdoor unit control board failure 10) Remote controller failure Interlocking control with MELANS 1) No group registration is made using MELANS. (The indoor unit and the M-NET remote controller are not grouped.) 2) Disconnected transmission line for centralized control (TB7) of the outdoor unit 3) The male power supply connector is connected to CN40 on more than one outdoor unit, or the connector is connected to CN40 on the outdoor unit in the system to which a power supply unit for transmission line is connected. Using MELANS 1) When MELANS is used, "HO" display on the remote controller will disappear when the indoor unit and the local remote con- troller (M-NET remote controller) are grouped. If "HO" does not disappear after the registration, check the causes (2) 1) - 3).
NO
Are all the units in the system experiencing the same problem?
Check the address of the M-NET remote controller on which "HO" is displayed.
Check the address of the outdoor unit.
NO *1
A wrong address is set to the M-NET remote controller.
Indoor unit + 100?
A wrong address is set to the outdoor unit.
YES
Check the address of the indoor unit to be coupled.
Check the centralized centralized switch (SW2-1) on the outdoor unit.
A wrong address is set to the indoor unit.
YES
Wrong switch setting Change it from ON to OFF.
YES
Measure voltages of the terminal block for M-NET transmission line on the indoor unit.
Indoor unit control board failure
Wrong wiring of the M-NET transmission line of the indoor unit
17 - 30V?
YES
Check connection between indoor M-NET transmission terminal block (TB5) and the male connector (CN2M)
NO
Indoor unit board or remote controller failure
Correct the error.
*1. When the indoor unit address is set to 1 - 50, the address will be forcibly set to 100.

Cause Check method and remedy
(2) Check the connection of transmission line.
Generates at confirmation of controllers used in the system in which the indoor units connected to differ- ent outdoor units are grouped
(5) Check the power supply of the outdoor unit which is coupled with the unit to be confirmed.
(6) Check that the transmission line for centralized control (TB7) of the outdoor unit is not disconnect- ed.
(7) Check voltage of the transmission line for central- ized control.

Cause Check method and remedy
(1) Check pressure difference between the detected pressure by the pressure sensor and the actual pressure with self-diagnosis LED. -> If the accurate pressure is not detected, check the pressure sensor. (Refer to the page on Trouble- shooting of Pressure Sensor).
Faulty detection of pressure sensor. Protection works and compressor frequency does
not rise due to high discharge temperature Protection works and compressor frequency does
not rise due to high pressure Pressure drops excessively.
1 2 3 4 5 6 7 8 9 10
SW1
1 2 3 4 5 6 7 8 9 10
(2) Check temperature difference between the evapo- rating temperature (Te) and the target evaporating temperature (Tem) with self-diagnosis LED.
1 2 3 4 5 6 7 8 9 10
Target evaporating temperature Tem
1 2 3 4 5 6 7 8 9 10
tion (not enough opening) or protection works and compressor frequency does not rise due to pres- sure drop. Refrigerant leak from LEV on the stopping unit
causes refrigerant shortage on the running unit.
crease due to clogging of the heat exchanger The fan is not properly controlled as the outdoor
temperature cannot be precisely detected by the temperature sensor. The fan is not properly controlled as the pressure
cannot be precisely detected by the pressure sen- sor.
High pressure sensor · Low pressure sensor · Evaporating temperature Te

Cause Check method and remedy
Check the piping length to determine if it is contrib- uting to performance loss. Piping pressure loss can be estimated from the temperature difference between the indoor unit heat exchanger outlet temperature and the satura- tion temperature (Te) of 63LS. ->Correct the piping. 5. Piping size is not proper (thin)
Refer to 1-1. (Compressor frequency does not rise sufficiently.)(page 265)Refer to the page on refrig- erant amount adjustment(page 157)
Check the inlet air temperature and for short cy- cling. Change the environment where the indoor unit is used.
Check the discharge temperature to determine if the refrigerant leaks, as it rises if there is a leak.
Refer to the page of LEV troubleshooting ( [4] -5- ).(page 279) It most likely happens when there is little difference or no difference between TH12 and TH15.
Check the thermistor. Check wiring.

Cause Check method and remedy
(1) Check pressure difference between the detected pressure by the pressure sensor and the actual pressure with self-diagnosis LED. -> If the accurate pressure is not detected, check the pressure sensor.(Refer to the page on Trouble- shooting of Pressure Sensor)
Faulty detection of pressure sensor. Protection works and compressor frequency does
not rise due to high discharge temperature Protection works and compressor frequency does
not rise due to high pressure.
1 2 3 4 5 6 7 8 9 10
SW1
1 2 3 4 5 6 7 8 9 10
(2) Check the difference between the condensing tem- perature (Tc) and the target condensing tempera- ture (Tcm) with self-diagnosis LED.
1 2 3 4 5 6 7 8 9 10
Target condensing temperature Tcm
1 2 3 4 5 6 7 8 9 10
High pressure sensor · Low pressure sensor · Condensing temperature Tc

Cause Check method and remedy
Refer to the page of LEV troubleshooting ( [4] -5- ).(page 279)
Check the thermistor.
4 RPM error of the outdoor unit FAN Refer to the page on outdoor unit fan ([4] -4- ).(page 279) Motor failure or board failure, or airflow rate de-
crease, pressure drop due to clogging of the heat exchanger leading to high discharge temperature The fan is not properly controlled as the tempera-
ture cannot be precisely detected with the piping sensor.
Confirm that the characteristic of capacity drop due to piping length. -> Change the pipe
Check the inlet air temperature and for short cy- cling. Change the environment where the indoor unit is used.
Refer to 2 - 1. (Compressor frequency does not rise sufficiently.)(page 265) Refer to the page on refrigerant amount adjustment.(page 157)
Refer to the page on troubleshooting the LEV ([4] - 5-).(page 279)

Cause Check method and remedy
The first stop is not considered as an error, as the unit turns to anti-restart mode for 3 minutes as a pre- liminary error.
(1) Check the mode operated in the past by displaying preliminary error history on LED display with SW1.
Error mode (2) Reoperate the unit to find the mode that stops the unit by displaying preliminary error history on LED display with SW1. -> Refer to the reference page for each error mode. 1) Abnormal high pressure

Cause Erroneous operation Error code Error code definition
Signal is transformed and will be misjudged as the signal of another address.
Transmission wave pattern is transformed due to the noise creating a new signal
6602 Transmission pro- cessor hardware er- ror
Transmission wave pattern is transformed due to the noise, and will not be received normally leading to no acknowledgement (ACK).
6607 No ACK error
Transmission cannot be performed due to the fine noise.
6603 Transmission line bus busy error
Transmission is successful; however, the acknowl- edgement (ACK) or the response cannot be re- ceived normally due to the noise.
6607 6608 No ACK error No response error
V HL
V BN
52
Logic "0" Logic "1"
No fine noise allowed
Check the wave pattern of the transmission line with an oscilloscope. The following conditions must be met. 1) Small wave pattern (noise) must not exist on the transmission signal. (Minute noise (approximately 1V) can be generated by DC-DC converter or the inverter operation; however, such noise is not a problem when the shield of the transmission line is grounded.) 2) The sectional voltage level of transmission signal should be as follows.
Logic Voltage level of the transmission line
0 VHL = 2.5V or higher
1 VBN = 1.3V or below

(3) Check method and remedy 1) Measures against noise Check the followings when noise exists on the wave or the errors described in (1) occur.
Error code definition Remedy
Check that the wiring work is performed ac- cording to wiring specifications.
Isolate the transmission line from the power line (5cm [1-31/32"] or more). Do not insert them in the same conduit.
The transmission line must be isolated from another transmission line. When they are bundled, erroneous operation may be caused.
Use the specified transmission line. Type: Shielded wire CVVS/CPEVS/MVVS (For M-NET remote controller) Diameter: 1.25mm2 [AWG16] or more (Remote controller wire: 0.3 - 1.25mm2 [AWG22-16])
The transmission is two-wire daisy-chained. The shielded wire must be also daisy-chained. When the shielded cable is not daisy-chained, the noise cannot be reduced enough.
Check that the grounding work is performed according to grounding specifi- cations.
Connect the shield of the indoor-outdoor transmission cable to the earth terminal ( ) on the outdoor unit. If no grounding is provided, the noise on the transmission line can- not escape leading to change of the transmission signal.
The transmission cable for centralized control is less subject to noise interference if it is grounded to the outdoor unit whose power jumper cable was moved from CN41 to CN40 or to the power sup- ply unit. The environment against noise varies depending on the distance of the transmission lines, the number of the connected units, the type of the controllers to be connected, or the environment of the installation site. Therefore, the transmission line work for central- ized control must be performed as follows.
Error code definition Remedy
Replace the indoor unit circuit board or the remote controller.
Connect the MA remote controller to the terminal block for MA re- mote controller (TB15).

If noise is generated on the transmission line, and the communication between the MA remote controller and the indoor unit is interrupted for 3 minutes in a row, MA transmission error (6831) will occur.
TB15 A B
Across terminal No. 1-2
: Power supply (9V to 12VDC)
Transmission waveform (Across terminal No.1 - 2)
Voltage among terminals must
Logic 1 Logic 0 Logic 1 Logic 1
be between DC9 and 12 V.
12msec

-1High-Pressure Sensor (63HS1, PS1, PS3)
1 2 3 4 5 6 7 8 9 10 ON
(1) While the sensor is stopped, compare the gauge pressure and the pressure displayed on self-diagnosis LED1. 1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal pressure is caused due to gas leak. 2) When the pressure displayed on self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the connector may be defective or be disconnected. Check the connector and go to (4). 3) When the pressure displayed on self-diagnosis LED1 exceeds 4.15MPa [601psi], go to (3). 4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2). (2) Compare the gauge pressure and the pressure displayed on self-diagnosis LED1 while the sensor is running. (Com-
pare them by MPa [psi] unit.) 1) When the difference between both pressures is within 0.098MPa [14psi], both the high pressure sensor and the control board are normal. 2) When the difference between both pressures exceeds 0.098MPa [14psi], the high pressure sensor has a problem. (perfor- mance deterioration) 3) When the pressure displayed on self-diagnosis LED1 does not change, the high pressure sensor has a problem. (3) Remove the high pressure sensor from the control board to check the pressure on the self-diagnosis LED1. 1) When the pressure displayed on self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the high pressure sensor has a problem. 2) When the pressure displayed on self-diagnosis LED1 is approximately 4.15MPa [601psi], the control board has a problem. (4) Remove the high pressure sensor from the control board, and short-circuit between the No.2 and 3 connectors
(63HS1, PS1, PS3) to check the pressure with self-diagnosis LED1. 1) When the pressure displayed on the self-diagnosis LED1 exceeds 4.15MPa [601psi], the high pressure sensor has a problem. 2) If other than 1), the control board has a problem.
The pressure sensor on the body side is designed to connect to the connector. The connector pin number on the body side is different from that on the control board side.
Body side Control board side
Vcc Pin 1 Pin 3
Vout Pin 2 Pin 2
GND Pin 3 Pin 1
4.5 [653]
Pressure (MPa [psi])
4.0 [580]
Pressure 0 ~ 4.15 MPa [601psi] Vout 0.5 ~ 3.5 V 0.071 V / 0.098 MPa [14 psi]
3.5 [508]
3.0 [435]
2.5 [363]
2.0 [290]
1.5 [218]
1.0 [145]
0.5 [73]
Vcc (DC 5 V)(Red)
0 0.5 1 1.5 2 2.5 3 3.5
Output voltage (V)
Connector · GND (Black) · Vout (White)

1 2 3 4 5 6 7 8 9 10 ON
(1) While the sensor is stopped, compare the gauge pressure and the pressure displayed on self-diagnosis LED1. 1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal pressure is caused due to gas leak. 2) When the pressure displayed on self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the connector may be defective or be disconnected. Check the connector and go to (4). 3) When the pressure displayed on self-diagnosis LED1 exceeds 1.7MPa [247psi], go to (3). 4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2). (2) Compare the gauge pressure and the pressure displayed on self-diagnosis LED1 while the sensor is running.(Com-
pare them by MPa [psi] unit.) 1) When the difference between both pressures is within 0.03MPa [4psi], both the low pressure sensor and the control board are normal. 2) When the difference between both pressures exceeds 0.03MPa [4psi], the low pressure sensor has a problem. (performance deterioration) 3) When the pressure displayed on the self-diagnosis LED1 does not change, the low pressure sensor has a problem. (3) Remove the low pressure sensor from the control board to check the pressure with the self-diagnosis LED1 display. 1) When the pressure displayed on the self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the low pressure sensor has a problem. 2) When the pressure displayed on self-diagnosis LED1 is approximately 1.7MPa [247psi], the control board has a problem. When the outdoor temperature is 30°C [86°F] or less, the control board has a problem. When the outdoor temperature exceeds 30°C [86°F], go to (5). (4) Remove the low pressure sensor from the control board, and short-circuit between the No.2 and 3 connectors
(63LS:CN202) to check the pressure with the self-diagnosis LED1. 1) When the pressure displayed on the self-diagnosis LED1 exceeds 1.7MPa [247psi], the low pressure sensor has a problem. 2) If other than 1), the control board has a problem. (5) Remove the high pressure sensor (63HS1) from the control board, and insert it into the connector for the low pres-
sure sensor (63LS) to check the pressure with the self-diagnosis LED1. 1) When the pressure displayed on the self-diagnosis LED1 exceeds 1.7MPa [247psi], the control board has a problem. 2) If other than 1), the control board has a problem. 2. Low-pressure sensor configuration The low pressure sensor consists of the circuit shown in the figure below. If DC5V is applied between the red and the black wires, voltage corresponding to the pressure between the white and the black wires will be output, and the value of this voltage will be converted by the microcomputer. The output voltage is 0.173V per 0.098MPa [14psi].
The pressure sensor on the body side is designed to connect to the connector. The connector pin number on the body side is different from that on the control board side.
Body side Control board side
Vcc Pin 1 Pin 3
Vout Pin 2 Pin 2
GND Pin 3 Pin 1
1.8 [261]
1.6 [232]
Pressure (MPa [psi])
Pressure 0 ~ 1.7 MPa [247psi] Vout 0.5 ~ 3.5 V 0.173 V / 0.098 MPa [14 psi]
1.4 [203]
1.2 [174]
1.0 [145]
0.8 [116]
0.6 [87]
0.4 [58]
0.2 [29]
Vcc (DC 5 V)(Red)
0 0.5 1 1.5 2 2.5 3 3.5
Output voltage (V)
Connector · GND (Black) · Vout (White)

Check whether the output signal from the control board and the operation of the solenoid valve match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED's. Each LED shows whether the relays for the following parts are ON or OFF. LEDs light up when relays are on.
The circuits on some parts are closed when the relays are ON. Refer to the following instructions.
LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Upper 21S4a CH11 SV1a SV2
1 2 3 4 5 6 7 8 9 10 ON
Upper SV4a SV4b SV4c SV5c SV4d SV9
1 2 3 4 5 6 7 8 9 10 ON
When a valve malfunctions, check if the wrong solenoid valve coil is not attached the lead wire of the coil is not disconnected, the connector on the board is not inserted wrongly, or the wire for the connector is not disconnected.
About this 4-way valve When not powered: Conducts electricity between the oil separator outlet and heat exchanger AND the gas ball valve (BV1) and the accumulator to complete the circuit for the cooling cycle. When powered: The electricity runs between the oil separator and the gas ball valve, and between the heat exchanger and the accumulator. This circulation is for heating.
Check the LED display and the intake and the discharge temperature for the 4-way valve to check whether the valve has no faults and the electricity runs between where and where.Do not touch the pipe when checking the temperature, as the pipe on the oil separator side will be hot.
Do not give an impact from outside, as the outer hull will be deformed leading to the malfunction of the inner valve.
This solenoid valve opens when powered (Relay ON). 1) At compressor start-up, the SV1a turns on for 4 minutes, and the operation can be checked by the self-diagnosis LED display and the closing sound. 2) To check whether the valve is open or closed, check the change of the SV1a downstream piping temperature while the valve is being powered.Even when the valve is closed, high-temperature refrigerant flows inside the capillary next to the valve. (Therefore, temperature of the downstream piping will not be low with the valve closed.) (3) In case of SV2 (Bypass valve)
This solenoid valve opens when powered (Relay ON). This valve turns on when low-pressure (LPS) drops to 0.25 MPa [36 psi] or below during Heating-only or Heating-main oper- ation AND after 5 minutes have passed after compressor startup; OR when 63HS1 is above 3.5 MPa [507psi] with the SV9 turned on and SV5b turned off AND the frequency drops to the minimum. To check whether the valve is open or closed, check the change of the SV1a downstream piping temperature while the valve is being powered.Even when the valve is closed, high-temperature refrigerant flows inside the capillary next to the valve.
Display · Lower SV5b · Lower

(4) SV4a, 4b and 4d (P72 model), SV4a - 4d (P96 and P120 models)(Controls heat exchanger capacity) 1) Depending on the conditions during Cooling-only operation, at least one of the solenoid valves among SV4a through 4d turns on. Check for proper operation on the LED and by listening for the operation sound of the solenoid valve. 2) During Heating-only operation, SV4a through 4d all turn on. Check for proper operation on the LED and by listening for the operation sound of the solenoid valves. 3) Depending on the conditions during Cooling-main or Heating-main operation, at least one of the solenoid valves among SV4a through 4d turns on. Check for proper operation on the LED and by listening for the operation sound of the solenoid valve. 4) The diagram on the next page shows the refrigerant flow. This diagram shows the flow of the high-temperature (high-pressure) gas refrigerant in the Cooling-only and Cooling-main modes and the flow of the low-temperature gas/liquid refrigerant in the Heating-only and Heating-main modes. Refer to the refrigerant circuit diagram. Solenoid valves turns on and off according to such factors as the capacity of the indoor units in operation and outside temperature. Check the LED. Remove the SV coil, open the lid, and check the plunger. The type of pin face wrench that is listed in the service parts list is required to perform this task.



Solenoid valve block (four compartments) P96 and P120 models

This solenoid valve closes when energized (when the relay is on). This valve turns off for five minutes after the completion of the defrost cycle, or when SV9 is on turned ON and the value of 63HS1 is greater than 3.5 MPa [507psi] during Heating-only or Heating-main operation at the minimum frequency. The valve position can be determined by measuring and monitoring the changes in the pipe temperature on the downstream of SV5b while the unit is de-energized. When the valve is open, high-temperature gas refrigerant passes through the pipe. Do not at- tempt to check the pipe temperature by touching the pipe.
This solenoid valve opens when energized (when the relay is on). This valve turns on, depending on the conditions during Cooling-only or Cooling-main operation. Check for proper operation on the LED and by listening for the operation sound of the solenoid valve.
This solenoid valve opens when energized (when the relay is on) This valve turns on when the value of 63HS1 is greater than 3.5 MPa [507psi] during Heating-only or Heating-main operation at the minimum frequency. The valve position can be determined by measuring and monitoring the changes in the pipe tem- perature on the downstream of SV9 while the unit is energized. When the valve is open, high-temperature gas refrigerant passes through the pipe. Do not attempt to check the pipe temperature by touching the pipe.

To check the revolution of the fan, check the inverter output state on the self-diagnosis LED, as the inverter on the outdoor
fan controls the revolutions of the fan.The revolution of the fan is approximately 680rpm(P72 model),790rpm(P96 and P120 models) at full speed. When starting the fan, the fan runs at full speed for 5 seconds. When setting the DIP SW1 as shown in the figure below, the inverter output [%] will appear. 100% indicates the full speed
and 0% indicates the stopping.
1 2 3 4 5 6 7 8 9 10 ON
As the revolution of the fan changes under control, at the interphase or when the indoor unit operation capacity is low, the
revolution of the fan may change. If the fan does not move or it vibrates, fan inverter board problem or fan motor problem is suspected. Refer to IX [4] -7- (2) [5]
"Check the fan motor ground fault or the winding." and IX [4] -7- (2) [6] "Check the FAN board failure."
LEV operation LEV are stepping-motor-driven valves that operate by receiving the pulse signals from the indoor and outdoor unit control boards.
The valve opening changes according to the number of pulses. 1) Control boards and the LEV


Output pulses change in the following orders when the Valve is closed; 1 2 3 4 1 Valve is open; 4 3 2 1 4
number 1 2 3 4 1 ON OFF OFF ON
2 ON ON OFF OFF 3 OFF ON ON OFF
*1. When the LEV opening angle does not change, all the output phases will be off. *2. When the output is open phase or remains ON, the motor cannot run smoothly, and rattles and vibrates.

*When the power is turned on, the valve closing signal of 2200 pulses will be output from the indoor board to LEV to fix the valve position. It must be fixed at point A.
Valve opening (refrigerant flow rate)
When the valve operates smoothly, no sound from LEV or no vibration occurs, however, when the pulses change from E to A in the chart or the valve is locked, a big sound occurs.
*Whether a sound is generated or not can be determined by holding a screwdriver against it, then placing your ear against the handle.
B
Valve closed · Valve open · Pulses

Microcomputer driver circuit fail- ure
Disconnect the control board connector and connect the check LED as shown in the figure below.
When the drive circuit has a problem, replace the control board.
1 1 k LED
resistance : 0.25W 1k LED : DC15V 20mA or more When the main power is turned on, the indoor unit cir- cuit board outputs pulse signals to the indoor unit LEV for 10 seconds. If any of the LED remains lit or unlit, the drive circuit is faulty.
LEV mechanism is locked
If the LEV is locked, the drive motor runs idle, and makes a small clicking sound. When the valve makes a closing and opening sound, the valve has a problem.
Replace the LEV.
Disconnected or short-circuited LEV motor coil
Measure resistance between the coils (red - white, red -orange, brown - yellow, brown - blue) using a tester. They are normal if resistance is 150ohm 10%.
Replace the LEV coils.
Incomple sealing (leak from the valve)
When checking the refrigerant leak from the indoor LEV, run the target indoor unit in the fan mode, and the other indoor units in the cooling mode. Then, check the liquid temperature (TH22) with the self-diagnosis LED. When the unit is running in the fan mode, the LEV is ful- ly closed, and the temperature detected by the thermis- tor is not low. If there is a leak, however, the temperature will be low. If the temperature is extremely low compared with the inlet temperature displayed on the remote controller, the LEV is not properly sealed, however, if there is a little leak, it is not necessary to re- place the LEV when there are no effects to other parts.
If there is a large amount of leakage, replace the LEV.
Thermistor (liquid piping temperature detection)
Faulty wire con- nections in the connector or faulty contact
Check the continuity at the points where an error occurs.

Check whether the pressure sensor or the connectors of P1 and P3 are connected, properly
Repair the fault.
Operating at the moment?
On the self-diagnosis monitor, measure Outdoor high-pressure 63HS1 Outdoor low-pressure 63LS BC controller pressure P1 (liquid side) and P3 (intermediate part) Check whether the result is 63HS1 P1 P3 63LS
Check whether the refrigerant pipe and the transmission line are connected correctly between the indoor unit and the BC controller.
OK?
YES
All the compressors of the outdoor units to which the BC controller is connected are stopped.
Fix the relation between the refrigerant piping and the transmission line.
YES
10 minutes or longer after the operation stops?
Check P1 and P3 on the self-diagnosis LED, and check that the detected pressure is 0.098MPa [14psi] or less.
Check whether the contact of the pressure sensor connector in trouble is not faulty.
Check that the difference between each detected pressure is 0.098MPa [14psi] or less.
NO
YES
Restore contact failure.
OK? Is Pd P1 P3 Ps? Remove the pressure sensor connector from the board, and check the pressure.
YES
YES
Both the board and the pressure sensor are normal.
YES
Short-circuit between connecter pins #2 and #3 on the circuit board, and check the pressure.
Check whether the refrigerant pipe and the transmission line are connected correctly between the indoor unit and the BC controller.
6MPa [870psi] pressure or more is displayed.
Fix the relation between the refrigerant piping and the transmission line.
YES
YES
Replace the pressure sensor, which detects less than 6MPa [870psi] pressure, with the pressure sensor, which detects 6MPa [870psi] or more pressure, check the pressure, and check whether the detected pressure is displayed normally.
OK?
YES
Replace the pressure sensor. Replace the board.
YES Note 2 · Pressure 0MPa [0psi]

Cooling-only Heating only Heating main
Non-cooling Normal SC11 large SC16 small PHM large
Indoor heating SC small
SC11 large SC16 small PHM large
Non-cooling Indoor heating SC small
SC11 large SC16 small PHM large
Heating indoor Thermo ON Especially noise is large.
Heating indoor Thermo ON Especially noise is large.
Measurement data SW1 setting value
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
BC controller pressure (liquid side)
1 2 3 4 5 6 7 8 9 10 ON
BC controller pressure (intermediate part)

Troubleshooting instructions for thermistor
START
Pull out the thermistor connector in trouble from the board.
Measure the temperature of the thermistor in trouble. (actual measurement value)
Check the thermistor resistor.
Compare the temperature corresponding to the resistance measured by the thermistor and the temperature measured by a commercially available thermometer, and check whether there is no difference between them.
Replace the thermistor Temperature difference
Insert the connector of the thermistor in trouble into the board, check the sensor inlet temperature on the LED monitor, and check the temperature difference.
Temperature difference Check for contact failure.
Replace the control board.
Normal

1) For the connectors on the board, TH11 and TH12 are connected to CN10, and TH15 and TH16 are connected to CN11. Dis- connect the connector in trouble, and check the sensor of each number. 2) Pull out the sensor connector from the I/O board, Do not pull the sensor by holding the lead wire. Measure the resistance with such as a tester. Compare the measured value with that of shown in the figure below. When the result is 10%, it is normal. 3) Check the self-diagnosis switch (Outdoor control board SW1).
Measurement data SW1 setting value Symbol
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
G, GA (Standard / main)
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
GB, HB (Sub 1)
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
GB, HB (Sub 2)
1 2 3 4 5 6 7 8 9 10 ON

No cooling capacity No heating capacity
Check whether the electric expansion valve and the solenoid valve connector are not disconnected or not loose.
Repair the fault. Fault is found.
Run the cooling operation or the heating operation in the system in trouble (only in one system).
Cooling or heating operation
Check that LEV1 is fully open. Check that LEV1 is fully open.
NO
LEV1 is fully open.
LEV1 is fully open.
Check LEV1.
Check whether LEV3 is controlling superheat.
Check whether LEV 3 is controlled by the value of the differential pressure.
NO
Superheat control OK Differential pressure OK
YES
Check LEV3.
Check that SVA and SVC are ON. Check that SVA and SVC are OFF.
NO
SVA, SVC ON SVA, SVC OFF
YES
YES
Check SVA and SVC.
Check that SVB is OFF. Check that SVB is ON.
NO
SVB OFF SVB ON
YES
YES
Check SVB.
Heating operation · Cooling operation · Completed

Cooling-only Cooling-main Heating only Heating main
Non-cooling SH12 small, SC11 small SC16 small, branch pipe SC small BC controller sound
Non-cooling and non-heating SH12 small, SC11 small SC16 large, but branch pipe SC small BC controller sound PHM large
Indoor heating SC small PHM large
Non-cooling Indoor heating SC small PHM large
Full open: 2000 pulses Fully closed: 110 pulses (In the case of heating-only mode, however, the pulse may become 110 or more.) When LEV is fully open, measure the temperature at the upstream and downstream pipes of LEV, and make sure that there
is no temperature difference. When LEV is fully closed, check that there is no refrigerant flowing sound. 3) Refer to the chart below to judge LEV opening controlled by the values of the differential pressure and of the superheat. (BC controller LEV basic operation characteristic)
mode Content Standards of judgment on
Difference between high pressure (P1) and interme- diate pressure (P3) is large.
0.3 to 0.4MPa [44 to 58psi] Inclined to
Difference between high pressure (P1) and interme- diate pressure (P3) is small.
SH12 is large. SH12 < 20°C [36°F]
Difference between high pressure (P1) and interme- diate pressure (P3) is small.
0.3 to 0.4MPa [44 to 58psi]
SC16 and SH12 are small. SC16 > 3°C [5.4°F] SH12 > 3°C [5.4°F]
Difference between high pressure (P1) and interme- diate pressure (P3) is large.
0.3 to 0.4MPa [44 to 58psi]
SH22 is large. SH22 < 20°C [36°F]
SH22 is small. SH22 > 3°C [5.4°F]

Measurement data SW1 setting value Symbol
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
G, GA (Standard / main)
1 2 3 4 5 6 7 8 9 10 ON
BC controller bypass outlet superheat
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
BC controller intermediate part subcool
1 2 3 4 5 6 7 8 9 10 ON
BC controller liquid-side subcool SC11
GB, HB (Sub 1)
1 2 3 4 5 6 7 8 9 10 ON
1 2 3 4 5 6 7 8 9 10 ON
GB, HB (Sub 2)

Start
Check for pins not fully inserted on the connector and check the colors of the lead wires visually.
Intermediate connector Control board
When LEV is fully closed : tick sound When LEV is fully open : no sound Check the above.
5 4 3 2 1
OK? NO
YES
Replace LEV.
Check that no refrigerant leaks from LEV.
YES
Repair the fault.
OK? NO
Pull out the connector from the board, and check that the electricity runs with a tester. The wiring side of CN05 and 07: Among 1, 3 and 5, and among 2, 4 and 6
Replace LEV.
Connect the LED for check, which is as shown in the right figure, to the board connector, and check that the LED keeps lighting for 10 seconds.
5 4 3 2 1
YES
Repair the fault.
Check the resistance between each coil with a tester (between red and white, red and orange, brown and yellow and brown and blue), and check that the resistance is 150 within 10%.
OK? NO
YES Replace LEV.
YES Replace the board in trouble.

Faulty judgment of solenoid valve
Stop the operation of the applied BC remote controller system.
YES
Check whether the wire to the solenoid valve is not connected wrongly, or the connector is not loose.
Repair the fault.
Run the cooling or heating operation of the refrigerant system of the solenoid valve in trouble.
Check the operation sound of the solenoid valve to be magnetized at the time of turning on the remote controller.
Makes a tick sound.
Remove the solenoid valve coil, and check that there is a suction force.
There is a suction force.
Stop the unit with the remote controller.
Measure the temperature at the upstream and downstream pipes of the solenoid valve, and compare them. There is no temperature difference. : OK There is a temperature difference. : NO
Remove the solenoid valve connector, and check that the electricity runs through the solenoid valve coil.
Check the relay output with the self-diagnosis LED, and check whether the operation corresponds with the operation mode.
The electricity runs.
YES
YES
Turn on the remote controller with the connector of the solenoid valve in trouble disconnected, and check that the control board outputs 200V.
Replace the control board.
Measure the temperature at the upstream and downstream pipes of the solenoid valve. When the solenoid valve is ON : There is no temperature difference. When the solenoid valve is OFF : There is a temperature difference.
NO
OK
Replace the control board. Replace the solenoid valve coil.
Faulty judgment of solenoid valve Solenoid valve failure

Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
Cooling Heating Stopped Defrost Fan
SVB OFF ON OFF OFF OFF
SVC ON OFF OFF OFF ON
SVM1 and SVM2 SVM1 and SVM2 turn on or off according to the indoor unit operation mode.
mode Cooling only Cooling main Heating only Heating main Defrost Stopped
OFF OFF ON OFF
ON
SVM2 OFF OFF
OFF OFF
ON
ON


CNTR CN03 BC controller control board
Red White Red Red
CNTR(1)-(3) about 58 ohm.
Open-phase or shorting CN03(1)-(3) about 16 ohm.
* Before measuring the resistance, pull out the connector.
Normal Abnormal
![Page 302 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-302.webp?w=400)
-7Inverter (THMU-A)
Replace only the compressor if only the compressor is found to be defective. (Overcurrent will flow through the inverter if the
compressor is damaged, however, the power supply is automatically cut when overcurrent is detected, protecting the inverter from damage.) Replace only the fan motor if only the fan motor is found to be defective. (Overcurrent will flow through the inverter if the fan
motor is damaged, however, the power supply is automatically cut when overcurrrent is detected, protecting the inverter from damage.) Replace the defective components if the inverter is found to be defective. If both the compressor and the inverter are found to be defective, replace the defective component(s) of both devices.
(1) Inverter-related problems: Troubleshooting and remedies 1) The INV board has a large-capacity electrolytic capacitor, in which residual voltage remains even after the main power is turned off, posing a risk of electric shock. Before inspecting the inverter-related items, turn off the main power, wait for 5 to 10 minutes, and confirm that the voltage at both ends of the electrolytic capacitor has dropped to a sufficiently low level. 2) The IPM on the inverter becomes damaged if there are loose screws are connectors. If a problem occurs after replacing some of the parts, mixed up wiring is often the cause of the problem. Check for proper connection of the wiring, screws, connectors, and Faston terminals. 3) To avoid damage to the circuit board, do not connect or disconnect the inverter-related connectors with the main power turned on. 4) Current sensors become damaged if electricity is passed through without them being connected to the circuit board. Connect the current sensor to the appropriate connectors on the circuit board before operating the inverter. 5) Faston terminals have a locking function. Make sure the terminals are securely locked in place after insertion.
Press the tab on the terminals to remove them.
![Page 303 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-303.webp?w=400)
Error display/failure condition Measure/inspection item
[1] Inverter related errors 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Check the details of the inverter error in the error log at 10.[1] Table of LED codes. Take appropriate measures to the error code and the error details in ac- cordance with 9. [2] Self-diagnosis on the basis of Error Display on Re- mote Controller and Remedy for Error.
[2] Main power breaker trip Check the breaker capacity.
Check whether the electrical system is short-circuited or ground-
faulted.
If items cause is not or are not the causes of the problem,
see (3)-[1].
[3] Main power earth leakage breaker trip Check the earth leakage breaker capacity and the sensitivity cur-
rent.
Meg failure for electrical system other than the inverter
If the cause is not or , see (3)-[1]
[4] Only the compressor does not operate. Check the inverter frequency on the LED monitor and proceed to (2) - [4] if the compressor is in operation.
[5] The compressor vibrates violently at all times or makes an abnor- mal sound.
See (2)-[4].
[6] Only the fan motor does not operate. Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.
[7] The fan motor shakes violently at all times or makes an abnormal sound.
Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.
[8] Noise is picked up by the peripheral device Check that power supply wiring of the peripheral device does not
run close to the power supply wiring of the outdoor unit.
Check that the inverter output wiring is not in close contact with the
power supply wiring and the transmission lines.
Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop- erly on the shielded wire.
Meg failure for electrical system other than the inverter
Attach a ferrite core to the inverter output wiring. (Contact the fac-
tory for details of the service part settings.)
Provide separate power supply to the air conditioner and other
electric appliances.
If the error occurred suddenly, a ground fault of the inverter output
can be considered. See (2)-[4].
*Contact the factory for cases other than those listed above.
[9] Sudden malfunction (as a result of external noise.) Check that the grounding work is performed properly.
Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop- erly on the shielded wire.
Check that neither the transmission line nor the external connec-
tion wiring does not run close to another power supply system or does not run through the same conduit pipe.
* Contact the factory for cases other than those listed above.
![Page 304 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-304.webp?w=400)
(2) Inverter output related troubles
Items to be checked Phenomena Remedy
[1] Check the INV board error detection cir- cuit.
1) IPM/overcurrent breaker trip (4250 Detail code No. 101, 104, 105, 106, and 107)
Replace the INV board.
(1) Disconnect the invert- er output wire from the terminals of the INV board (SC-U, SC-V, SC-W).
Replace the INV board.
(2) Put the outdoor unit into operation.
Replace the INV board.
1) IPM/overcurrent breaker trip (4250 Detail code No. 101, 102, 103, 104, 105, 106, and 107)
See the section "Troubleshooting the IPM" ( Refer to - 7 - (5) ). Replace the IPM, and put the out- door unit back into operation. If the problem persists, replace the INV board.
(1) Disconnect the invert- er output wire from the output terminals (U, V, W) of the IPM.
See the section "Troubleshooting the IPM" ( Refer to - 7 - (5) ). Replace the IPM, and put the out- door unit back into operation. If the problem persists, replace the INV board. Replace the INV board, and put the outdoor unit back into opera- tion. If the problem persists, replace the DCCT.
(2) Put the outdoor unit into operation.
Replace the INV board.
Replace the DCCT board. Replace the DCCT, and put the outdoor unit back into operation. If the problem persists, replace the INV board.
[2] Check for compressor ground fault or coil error.
Disconnect the compres- sor wiring, and check the compressor Meg, and coil resistance.
Replace the compressor Check that no liquid refrigerant in the compressor.
Normal · Normal
![Page 305 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-305.webp?w=400)
Items to be checked Phenomena Remedy
[3] Check whether the inverter is damaged. (No load)
1) Inverter-related problems are de- tected.
Connect the short-circuit con- nector to CN6, and go to sec- tion [1].
(1) Disconnect the inverter output wire from the ter- minals of the INV board (SC-U, SC-V, SC-W).
(2) Disconnect the short-cir- cuit connector from CN6 on the INV board.
Replace the INV board.
(3) Put the outdoor unit into operation. Check the inverter output voltage after the inverter output frequency has sta- bilized.
Normal *Reconnect the short-circuit connector to CN6 after check- ing the voltage.
1) Inverter-related problems are de- tected.
Turn off SW1-1 and go to [1]
(1) Disconnect the inverter output wire from the out- put terminals (U, V, W) of the IPM.
(2) Turn on SW1-1 on the INV board.
Replace the IPM. If the problem persists, re- place the INV board.
(3) Put the outdoor unit into operation.
Normal *Turn off SW1-1
[4] Check whether the inverter is damaged. (During com- pressor opera- tion)
Put the outdoor unit into oper- ation. Check the inverter output volt- age after the inverter output frequency has stabilized.
Replace the INV board. Replace the IPM. If the problem persists, re- place the INV board. If the problem persists after replacing the above parts, go to section [2].
[5] Check the fan motor ground fault or the winding.
Remove the wire for the out- door fan motor, and check the fan motor megger and the winding resistance.
Replace the fan motor.
[6] Check the FAN board failure.
(1) Check the fan output wir- ing.
Connect the connector.
Board side (CNINV) Fan motor side
(2) Check the connector CN- VDC connection.
Cnnector contact failure Connect the connector.
(3) Check the FAN board failure.
Replace the FAN board.
Connector contact failure
![Page 306 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-306.webp?w=400)
(3) Trouble treatment when the main power breaker is tripped.
Items to be checked Phenomena Remedy
[1] Perform Meg check between the terminals on the power terminal block TB1.
Zero to several ohm, or Meg failure Check each part in the main inverter circuit. *Refer to "Simple checking Proce- dures for individual components of main inverter circuit".
[2] Turn on the power again and check again.
Diode stack IPM Rush current protection resistor Electromagnetic relay DC reactor
[3] Turn on the outdoor unit and check that it operates normally.
a) The wiring may have been short-
circuited. Search for the wire that short-circuited, and repair it. b) If item a) above is not the cause of
the problem, the compressor may have a problem.

(4) Simple checking procedure for individual components of main inverter circuit
Before checking, turn the power off and remove the parts to be checked from the control box.
Part name Judgment method
Diode stack Refer to "Diode stack" ( IX [4] - 7 - (6) )
IPM (Intelligent power module)
Refer to "Intelligent power module (IPM)" ( IX [4] - 7 - (5) )
Rush current protection resis- tor R1(R2)
Measure the resistance between terminals: 22 ohm 10% Measure the resistance between the + terminal on the diode stack and terminal TB31. (*Can be mea- sured without the need to remove the noise filter board): 22 ohm 10%
Electromagnetic relay 72C This electromagnetic relay is rated at 200VAC and is driven by a coil. The resistance between the coils in row A cannot be measured with a tester.Check only for shorting.
Row A Not to be short-circuited
A
B
D
With the test button turned off : With the test button turned on : 0
Row B to Row E
Between No. 1 pin and No. 3 pin of the CN03 on the noise filter board
Not to be short-circuited
+ terminal on the diode stack and terminal TB31 on the noise filter
With the test button turned off :
With the test button turned on : 0
DC reactor DCL Measure the resistance between terminals: 1ohm or lower (almost 0 ohm) Measure the resistance between terminals and the chassis:
Disconnect the CNCT2 connector and measure the resistance between terminals: 280 ohm 30 ohm 1 - 2 PIN (U-phase),3 - 4 PIN (W-phase)
W
W ACCT-W
U
ACCT-U
*Check the ACCT connection phase and the direction of the connection
![Page 308 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-308.webp?w=400)
(5) Intelligent power module (P96 and P120 models)
Measure resistances between each pair of terminals on the IPM with a tester, and use the results for troubleshooting.
1) Notes on measurement Check the polarity before measuring. (On the tester, black normally indicates plus.) Check that the resistance is not open ( ohm) or not shorted (to 0 ohm). The values are for reference, and the margin of errors is allowed. The result that is more than double or half of the result that is measured at the same measurement point is not allowed. 2) Tester restriction Use the tester whose internal electrical power source is 1.5V or greater Use the dry-battery-powered tester.
(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt- age is low.) Use a low-range tester if possible. A more accurate resistance can be measured.
![Mitsubishi Electronics P96 — [THMU-A] diagram (page 308)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/fig-308-1.webp)
P - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm
External view Internal circuit diagram
![Mitsubishi Electronics P96 — [THMU-A] diagram (page 308)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/fig-308-2.webp)
Judgment value (reference)

(6) Diode stack (P96 and P120 models)
Measure resistances between each pair of terminals on the diode stack with a tester, and use the results for troubleshoot- ing.Refer to (5) " Intelligent power module (IPM) " for notes on measurement and tester selection.
Black ( + ) External view
+ (P) - (N) to (L1) to (L2) to (L3)
+ (P) - - 5 - 200 ohm
L1 L2 L3
to (L1) 5 - 200 ohm
to (L2) 5 - 200 ohm
to (L3) 5 - 200 ohm
![Page 310 of the Mitsubishi Electronics P96 user manual — [YHMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-310.webp?w=400)
-7Inverter (YHMU-A)
Replace only the compressor if only the compressor is found to be defective. Replace only the fan motor if only the fan motor is found to be defective. Replace the defective components if the inverter is found to be defective. If both the compressor and the inverter are found to be defective, replace the defective component(s) of both devices.
(1) Inverter-related problems: Troubleshooting and remedies 1) The inverter board has a large-capacity electrolytic capacitor, in which residual voltage remains even after the main power is turned off, posing a risk of electric shock. Turn off the unit, leave it turned off for at least 10 minutes, and check that the voltage across FT-P and FT-N terminals on the INV board or the terminals at both ends of the electrolytic capacitor is 20V or below before checking inside the control box. (It takes about 10 minutes to discharge electricity after the power supply is turn off.) 2) The IPM on the inverter becomes damaged if there are loose screws are connectors. If a problem occurs after replacing some of the parts, mixed up wiring is often the cause of the problem. Check for proper connection of the wiring, screws, connectors, and Faston terminals. 3) To avoid damage to the circuit board, do not connect or disconnect the inverter-related connectors with the main power turned on. 4) Faston terminals have a locking function. Make sure the terminals are securely locked in place after insertion.
Press the tab on the terminals to remove them.
![Page 311 of the Mitsubishi Electronics P96 user manual — [YHMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-311.webp?w=400)
Error display/failure condition Measure/inspection item
[1] Inverter related errors 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Check the details of the inverter error in the error log at 10.[1] Table of LED codes. Take appropriate measures to the error code and the error details in ac- cordance with 9. [2] Self-diagnosis on the basis of Error Display on Re- mote Controller and Remedy for Error.
[2] Main power breaker trip Refer to "(3) Trouble treatment when the main power breaker is tripped".
[3] Main power earth leakage breaker trip Refer to "(4) Trouble treatment when the main power earth leakage breaker is tripped".
[4] Only the compressor does not operate. Check the inverter frequency on the LED monitor and proceed to (2) - [4] if the compressor is in operation.
[5] The compressor vibrates violently at all times or makes an abnor- mal sound.
See (2)-[4].
[6] Only the fan motor does not operate. Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.
[7] The fan motor shakes violently at all times or makes an abnormal sound.
Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.
[8] Noise is picked up by the peripheral device Check that power supply wiring of the peripheral device does not
run close to the power supply wiring of the outdoor unit.
Check if the inverter output wiring is not running parallel to the
power supply wiring and the transmission lines.
Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop- erly on the shielded wire.
Meg failure for electrical system other than the inverter
Attach a ferrite core to the inverter output wiring. (Contact the fac-
tory for details of the service part settings.)
Provide separate power supply to the air conditioner and other
electric appliances.
If the error occurred suddenly, a ground fault of the inverter output
can be considered. See (2)-[4].
*Contact the factory for cases other than those listed above.
[9] Sudden malfunction (as a result of external noise.) Check that the grounding work is performed properly.
Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop- erly on the shielded wire.
Check that neither the transmission line nor the external connec-
tion wiring does not run close to another power supply system or does not run through the same conduit pipe.
* Contact the factory for cases other than those listed above.
![Page 312 of the Mitsubishi Electronics P96 user manual — [YHMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-312.webp?w=400)
(2) Inverter output related troubles
Items to be checked Phenomena Remedy
[1] Check the INV board er- ror detection circuit.
(1) Disconnect the invert- er output wire from the terminals of the inverter board (SC-U, SC-V, SC-W).
Replace the INV board.
(2) Put the outdoor unit into operation.
Replace the INV board.
Replace the INV board.
[2] Check for compressor ground fault or coil error.
Disconnect the compressor wiring, and check the com- pressor Meg, and coil resis- tance.
Check that there is no liquid re- frigerant in the compressor. If there is none, replace the com- pressor.
Replace the compressor.
Normal
![Page 313 of the Mitsubishi Electronics P96 user manual — [YHMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-313.webp?w=400)
Items to be checked Phenomena Remedy
[3] Check whether the inverter is damaged. (No load)
(1) Disconnect the inverter output wire from the ter- minals of the inverter board (SC-U, SC-V, SC- W).
Connect the short-circuit con- nector to CN6, and go to sec- tion [1].
(2) Disconnect the short-cir- cuit connector from CN6 on the inverter board.
Replace the INV board.
(3) Put the outdoor unit into operation. Check the inverter output voltage after the inverter output frequency has sta- bilized.
Replace the INV board.
Normal *Reconnect the short-circuit connector to CN6 after check- ing the voltage.
[4] Check whether the inverter is damaged. (During com- pressor opera- tion)
Put the outdoor unit into oper- ation. Check the inverter output volt- age after the inverter output frequency has stabilized.
Replace the INV board.
[5] Check the fan motor ground fault or the winding.
Remove the wire for the out- door fan motor, and check the fan motor megger and the winding resistance.
Replace the fan motor.
[6] Check the FAN board failure.
(1) Check the fan output wir- ing.
Connect the connector.
Board side (CNINV) Fan motor side
(2) Check the connector CN- VDC connection.
Cnnector contact failure Connect the connector.
(3) Check the FAN board failure.
Replace the FAN board.
Connector contact failure

(3) Trouble treatment when the main power breaker is tripped
Items to be checked Phenomena Remedy
[1] Check the breaker capacity. Use of a non-specified break- er
Replace it with a specified breaker.
[2] Perform Meg check between the terminals on the power terminal block TB1.
Zero to several ohm, or Meg failure
Check each part and wiring. *Refer to (5) "Simple checking procedure for individual components of main inverter circuit".
[3] Turn on the power again and check again.
IGBT module Rush current protection resistor Electromagnetic relay DC reactor
[4] Turn on the outdoor unit and check that it operates normally.
a) The wiring may have been short-circuit-
ed. Search for the wire that short-circuit- ed, and repair it. b) If item a) above is not the cause of the
problem, refer to (2)-[1]-[6]. 2) Main power breaker trip
Items to be checked Phenomena Remedy
[1] Check the earth leakage breaker capacity and the sensitivity cur- rent.
Use of a non-specified earth leakage breaker
Replace with a regulation earth leakage breaker.
[2] Check the resistance at the power supply terminal block (TB1) with a megger.
Failure resistance value Check each part and wiring. *Refer to (5) "Simple checking Procedures for individual components of main inverter circuit".
IGBT module Rush current protection resistor Electromagnetic relay DC reactor
[3] Disconnect the compressor wir- ings and check the resistance of the compressor with a megger.
Failure compressor if the insu- lating resistance value is not in specified range. Failure when the insulating re- sistance value is 1 Mohm or less.
Check that there is no liquid refrigerant in the compressor. If there is none, replace the compressor.
[4] Disconnect the fan motor wirings and check the resistance of the fan motor with a megger.
Failure fan motor if the insulat- ing resistance value is not in specified range. Failure when the insulating re- sistance value is 1 Mohm or less.
Replace the fan motor.
The insulation resistance could go down to close to 1Mohm after installation or when the power is kept off for an extended period of time because of the accumulation of refrigerant in the compressor. If the earth leakage breaker is triggered, please use the following procedure to take care of this. Disconnect the wires from the compressor's terminal block. If the resistance is less than 1 Mohm, switch on the power for the outdoor unit with the wires still disconnected. Leave the power on for at least 12 hours. Check that the resistance has recovered to 1 Mohm or greater. Earth leakage current measurement method
For easy on-site measurement of the earth leakage current, enable the filter with a measurement instrument that has filter
functions as below, clamp all the power supply wires, and measure. Recommended measurement instrument: CLAMP ON LEAK HiTESTER 3283 made by HIOKI E.E. CORPORATION When measuring one device alone, measure near the device's power supply terminal block.

(5) Simple checking procedure for individual components of main inverter circuit
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
Part name Judgment method
IGBT module See "Troubleshooting for IGBT Module ". ( IX [4] - 7 - (6) )
Rush current pro- tection resistor R1, R5
Measure the resistance between terminals R1 and R5: 22 ohm 10%
Electromagnetic relay 72C This electromagnetic relay is rated at DC12V and is driven by a coil. Check the resistance between terminals
Check point Checking criteria( ) W
(Center value 75 ohm) Coil
Between Terminals 5 and 6
Not to be short-circuited
Between Terminals 1 and 2 Between Terminals 3 and 4
DC reactor DCL Measure the resistance between terminals: 1ohm or lower (almost 0 ohm) Measure the resistance between terminals and the chassis:
Measure the resistances between each pair of terminals on the IGBT with a tester, and use the results for troubleshooting. The terminals on the inverter board are used for the measurement.
1) Notes on measurement Check the polarity before measuring. (On the tester, black normally indicates plus.) Check that the resistance is not open ( ohm) or not shorted (to 0 ohm). The values are for reference, and the margin of errors is allowed. The result that is more than double or half of the result that is measured at the same measurement point is not allowed. Disconnect all the wiring connected the INV board, and make the measurement.
(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt- age is low.) Use a low-range tester if possible. A more accurate resistance can be measured.
Upper · Installation direction · Contact

Black ( + )
SC-P1 - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm
SC-L1 5 - 200 ohm - - -
SC-L2 5 - 200 ohm - - -
SC-L3 5 - 200 ohm - - -
Black ( + )
SC-P2 - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm
SC-U 5 - 200 ohm - - -
SC-V 5 - 200 ohm - - -
SC-W 5 - 200 ohm - - -
INV board external diagram
FT-N
SC-V
SC-L1 SC-L2
SC-W
SC-L3
SC-U
Judgment value (reference) · Red (-) · Red (-)
![Page 317 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-317.webp?w=400)
-8Control Circuit (THMU-A)
(1) Control power source function block 1) PURY-P72THMU-A
![Mitsubishi Electronics P96 — [THMU-A] diagram (page 317)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/fig-317-1.webp)
Power source system (AC 208 / 230 V) Control system (DC 5 ~ 30 V)
AC 208 / 230 V Terminal block for power source
Detection circuit for the power supply to the transmission line
CN40 Terminal block for transmission line for centralized control (DC 24 ~ 30 V)
Terminal block for transmission line connection DC 17 ~ 30 V
* MA remote controllers and M-NET remote controllers cannot be used together.
(Both the M-NET and MA remote controller can be connected to a system with a system controller.)
![Page 318 of the Mitsubishi Electronics P96 user manual — [THMU-A]](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-318.webp?w=400)
2) PURY-P96, P120THMU-A
![Mitsubishi Electronics P96 — [THMU-A] diagram (page 318)](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/fig-318-1.webp)
Power source system (AC 208 / 230 V) Control system (DC 5 ~ 30 V)
AC 208 / 230 V Terminal block for power source
Detection circuit for the power supply to the transmission line
Terminal block for transmission line for centralized control (DC 24 ~ 30 V)
Terminal block for transmission line connection DC 17 ~ 30 V
* MA remote controllers and M-NET remote controllers cannot be used together.
(Both the M-NET and MA remote controller can be connected to a system with a system controller.)

(2) Troubleshooting transmission power circuit of outdoor unit 1) PURY-P72THMU-A
Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit.
YES
Check whether the transmission line is disconnected, check for contact failure, and repair the problem.
Check the voltage at TB3 after removing transmission line from TB3.
YES
Check if the indoor/outdoor transmission line is not short-circuited, and repair the problem.
Check whether the male connector is connected to the female power supply connector (CN40).
YES
Check voltage of terminal block for centralized control (TB7).
Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.
NO NO
YES
Is there a wiring error or a connector
Fix the wiring and connector disconnection.
Check voltage of TB7 by removing transmission line from TB7.
YES
Check for shorted transmission line for centralized control.
Check the voltage between No.1 and No.2 pins of the CNS2 on the control board.
DC24 ~ 30V
Replace the control board.
Check the voltage between No.1 and No.2 pins of the CN102 on the power supply board for the transmission line.
Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.
NO
Is there a connector
disconnection? Fix the connector disconnection.
Check the voltage between No.5 and No.2 pins of the CNIT on the control board.
Check the voltage between No.1 and No.3 pins of the CNDC on the INV board.
NO
Is the voltage measurement between
Replace the M-NET board
4.5 and 5.2 VDC?
DC265 ~ 357V
Replace the M-NET board
Check the voltage between SC-P1 and TB-N on the INV board.
YES
Check the inrush current resistance (R1).
Replace the inrush current limiting resistor.
Check the voltages among SC-R, SC-S, and SC-T on the INV board.
YES
Replace the INV board.
AC188 ~ 253V
Replace the INV board.
Check the voltages among TB21, TB22, and TB23 on the noise filter.
Check the wiring between the noise filter and the INV board as well as screw tightness, and fix any problems found.
NO
Check the voltage at the power supply terminal block TB1.
AC188 ~ 253V
Replace the noise filter.
Check and fix any power supply wiring and main power supply problems found.
Turn on the power again.
Connected · disconnection? · 22 10%

2) PURY-P96, P120THMU-A
Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit.
DC 24 ~ 30 V
Check whether the transmission line is disconnected, check for contact failure, and repair the problem.
Check the voltage at TB3 after removing transmission line from TB3.
DC 24 ~ 30 V
Check if the indoor/outdoor transmission line is not short-circuited, and repair the problem.
Check whether the male connector is connected to the female power supply connector (CN40).
YES
Check voltage of terminal block for centralized control (TB7).
Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.
NO
YES Is there a wiring error or a connector
Fix the wiring and connector disconnection.
Check voltage of TB7 by removing transmission line from TB7.
Check for shorted transmission line for centralized control.
NO
Check the voltage between No.1 and No.2 pins of the CNS2 on the control board.
DC24 ~ 30V
Replace the control board.
Check the voltage between No.1 and No.2 pins of the CN102 on the power supply board for the transmission line.
Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.
DC24 ~ 30V
NO
Is there a connector
disconnection? Fix the connector disconnection.
Check the voltage between No.5 and No.2 pins of the CNIT on the control board.
Check the voltage between No.1 and No.3 pins of the CNDC3 on the INV board.
YES
Is the voltage measurement between
Replace the M-NET board
4.5 and 5.2 VDC?
DC265 ~ 357V
Replace the M-NET board
Check the voltage between TB31 and TB42 on the noise filter.
YES
Replace the INV board.
Check the voltage between the + and – terminals on the diode stack.
YES
Replace the noise filter.
Check the voltages among TB21, TB22, and TB23 on the noise filter.
AC188 ~ 253V
Replace the diode stack.
Check the voltage at the power supply terminal block TB1.
YES
Replace the noise filter.
Check and fix any power supply wiring and main power supply problems found.
Turn on the power again.
Connected · disconnection?

- 8 - Control Circuit (YHMU-A)
(1) Control power source function block 1) PURY-P72, P96, P120YHMU-A
Power source system (AC 230 / 460 V) Control system (DC 5 ~ 30 V)
72C DCL
AC 460V Terminal block for power source
5 V Power supply
Solenoid valve 4-way valve CH11
Relay, LEV Drive circuit
18 V Power supply
5 V Power supply
5 V Power supply
DC / DC converter
Detection circuit for the power supply to the transmission line
Terminal block for transmission line for centralized control (DC 24 ~ 30 V)
DC / DC converter
TB3
30 V Power supply
Indoor/outdoor transmission block (DC 24 ~ 30 V)
M-NET transmission line (Non-polar 2 wire)
AC 220 / 240 V AC Power source
Terminal block for power source
Terminal block for MA remote controller
To next unit (Indoor unit)
Terminal block for transmission line connection DC 17 ~ 30 V
MA remote controller wiring
DC 17 ~ 30 V
A, B
DC 9 ~ 12 V
* MA remote controllers and M-NET remote controllers cannot be used together.
(Both the M-NET and MA remote controller can be connected to a system with a system controller.)

(2) Troubleshooting transmission power circuit of outdoor unit 1) PURY-P72, P96, P120YHMU-A
Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit.
DC 24 ~ 30 V
Check whether the transmission line is disconnected, check for contact failure, and repair the problem.
Check the voltage at TB3 after removing transmission line from TB3.
DC 24 ~ 30 V
Check if the indoor/outdoor transmission line is not short-circuited, and repair the problem.
Check whether the male connector is connected to the female power supply connector (CN40).
YES
Check voltage of terminal block for centralized control (TB7).
YES
Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.
YES
Check voltage of TB7 by removing transmission line from TB7.
Is there a wiring error or a connector
Fix the wiring and connector disconnection.
Check for shorted transmission line or power feed collision for centralized control.
NO
Check the voltage between No.1 and No.2 pins of the CNS2 on the control board.
DC 24 ~ 30 V
Replace the control board.
Check the voltage between No.1 and No.2 pins of the CN102 on the power supply board for the transmission line.
Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.
NO
YES
Is there a connector
Fix the connector disconnection.
Check the voltage between No.5 and No.2 pins of the CNIT on the control board.
Is the voltage measurement between
Check the voltage between No.1 and No.3 pins of the noise filter CN4.
Replace the M-NET board
4.5 and 5.2 VDC?
DC270 ~ 356V
Replace the control board.
Check the voltage between No.1 and No.3 pins of the noise filter CN5.
DC270 ~ 356V
Replace the M-NET board
Check the noise filter fuse F4 .
Fuse F4 on the noise filter board is blown.
Disconnect the noise filters CN4 and CN5, and then replace fuse F4 on the noise filter board, then turn the power on.
YES
Fuse F4 on the noise filter board is blown.
Replace the noise filter.
Connect the noise filter CN4, and then turn the power on.
Fuse F4 on the noise filter board is blown.
Replace the control board.
Check fuse F5.
Replace the M-NET board
Fuse F5 is blown.
Pull out CN4 and CN5 on the noise filter, replace fuse F5, and turn on the power.
YES
Check the voltages among TB22 and TB23 on the noise filter
Fuse F5 is blown.
Replace the noise filter.
Connect the noise filter CN4, and then turn the power on.
Fuse F5 is blown.
Replace the control board.
Replace the M-NET board
AC41 4 ~ 506V
Replace the noise filter.
Check the voltage between L2 and L3 at the power supply terminal block TB1.
AC414 ~ 506V
Replace the noise filter.
Check and fix any power supply wiring and main power supply problems found.
Turn on the power again.
Connected · disconnection? · disconnection?
![Page 323 of the Mitsubishi Electronics P96 user manual — [5] Refrigerant Leak](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-323.webp?w=400)
1. Leak spot: In the case of extension pipe for indoor unit (Cooling season) 1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side. 2) Stop all the indoor units, and close the high-pressure side refrigerant service valve (BV2) on the outdoor unit while the com- pressor is being stopped. 3) Stop all the indoor units; turn on SW2-4 on the outdoor unit control board while the compressor is being stopped.(Pump down mode will start, and all the indoor units will run in cooling test run mode.) 4) In the pump down mode (SW2-4 is ON), all the indoor units will automatically stop when the low pressure (63LS) reaches 0.383MPa [55psi] or less or 15 minutes have passed after the pump mode started. Stop all the indoor units and compressors when the pressure indicated by the pressure gauge, which is on the check joint (CJ2) for low-pressure service, reaches 0.383MPa [55psi] or 20 minutes pass after the pump down operation is started. 5) Close the service ball valve (BV1) on the low-pressure pipe on the outdoor unit. 6) Collect the refrigerant that remains in the extended pipe for the indoor unit. Do not discharge refrigerant into the atmosphere when it is collected. 7) Repair the leak. 8) After repairing the leak, vacuum*1 the extension pipe and the indoor unit. 9) To adjust refrigerant amount, open the ball valves (BV1 and BV2) inside the outdoor unit and turn off SW2-4.
(2) Check the SC16 value.
(This valve can be displayed on the LED by setting the self-diagnosis switch (SW1) on the outdoor unit control board.) 1) When SC16 is 10°C [18°F] or above: Go to the next item (3). 2) When the SC16 value is below 10°C [18°F] : After the compressor has stopped, extract the refrigerant in the system, repair the leak, evacuate the air from the system *1, and charge the system with refrigerant. (If the leak is in the outdoor unit, follow the same procedure as listed under "heating season.")
1 2 3 4 5 6 7 8 10 9 ON
(3) Stop all the indoor units, and stop the compressor. 1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Check that all the indoor units are being stopped.
(4) Close the ball valves (BV1 and BV2). (5) Collect the refrigerant that remains inside the outdoor unit.Do not discharge refrigerant into air into the atmosphere
when it is collected. (6) Repair the leak. (7) After repairing the leak, replace the dryer with the new one, and perform evacuation *1 inside the outdoor unit. (8) To adjust refrigerant amount, open the ball valves (BV1 and BV2) inside the outdoor unit.
*1. Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.
SC16 self-diagnosis switch

(2) Stop all the indoor units, and stop the compressor. 1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Check that all the indoor units are stopped.
(3) Close the ball valves (BV1 and BV2). (4) Collect the refrigerant that remains inside the indoor unit. Do not discharge refrigerant into air into the atmosphere
when it is collected. (5) Repair the leak. (6) After repairing the leak, perform evacuation of the extension pipe*1 for the indoor unit, and open the ball valves (BV1
and BV2) to adjust refrigerant.
4. Leak spot: In the case of outdoor unit (Heating season) 1) Collect the refrigerant in the entire system (outdoor unit, extended pipe and indoor unit).Do not discharge refrigerant into the atmosphere when it is collected. 2) Repair the leak. 3) Repair the leak, and evacuate the air from the entire system *1 . Then, calculate the proper amount of refrigerant to be added (outdoor unit + extension pipe + indoor unit), and charge the system with that amount. Refer to Chapter VIII [4] 3. for the proper amount of refrigerant charge.
*1. Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

[Compressor replacement procedures]
Follow the procedures below (Steps 1 through 6) to remove the compressor components and replace the compressor. Reassemble them in the reverse order after replacing the compressor.


Service panel Control box

*1 Remove the transformer box from the P72, P96, and P120YHMU-A models.



Compressor covers (right and left) (The inside of the compressor cover is lined with sound insulation material.)

Protection for the sealing material
Protection for the compressor cover
Compressor cover (top) · Crankcase heater · Suction piping

* Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b,
SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures.
Following instructions are applicable to 1-3 service parts on the table below.
NO. Parts to be serviced
Numbers
2 Check valve (CV4a)
3. Procedures
* Precautions for starting replacement
Remove each part according to the 1)-3) procedures on the next page before replacing service parts. Mount the removed parts back in place in a reversed procedures of 1)-3) on the next page after replacing service parts.
peripheral piping devices. Fix the Solenoid valve block ASSY and the supporting plate with the fixing screw (M5). ⑦ Braze B-G part (total 6 places), and connect the solenoid valve block and the heat exchanger header with the connect-
ing pipe (φ9.52 [3/8"]) that comes with the service parts set. ⑧ Mount the solenoid valve block coil cover, solenoid valve coil, and peripheral cables back in place.
* Precautions for replacing Solenoid valve block ASSY
*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.


④⑦ Brazing or debrazing pipes D (φ28.6 [1-1/8"]), E (φ9.52 [3/8"]), F (φ9.52 [3/8"])
④⑦B (φ15.88 [5/8"])
④⑦C (φ19.05 [3/8"])
Solenoid valve coil (SV4a,SV4b,SV4d)



F G
Removed Solenoid valve block ASSY
G (φ15.88 [5/8"])
* This figure does not show heat exchanger.
②⑥ Removing or installing
solenoid valve block Solenoid valve block
Cutting pipes positions Cut the pipe at 40mm ahead from the Bending R end with a pipe cutter.
40 A (φ12.7
[1/2"]) Bending R end
Supporting plate for solenoid valve block
After cutting pipe, remove the pipe from the brazed A.
⑦ Brazing connecting pipe (φ9.52 [3/8"])

Brazing (heat exchanger header side)
Service patrs set supplied connecting pipe ( φ 9.52 [3/8"])
Heat exchanger ③⑦A (φ12.7 [1/2"])
* Refer to the next page for Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures.

① Remove the Solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement
procedures" on the front page.
② Debraze H-M parts (total 6 places), and remove the Check valve ASSY.
③ Replace the Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) to be serviced while it is removed from the unit.
Braze the pipes as they were according to the angle of the pipes on the next page (Figure as viewed from point Q).
④ Mount the solenoid valve block ASSY, coil cover, and peripheral cables back in place according to "(1) Solenoid valve
block ASSY (SV4a, SV4b, SV4d) replacement procedures" on the front page.

②③ H (φ19.05 [3/4"])
②③ I (φ15.88 [5/8"])
②③ J (φ12.7 [1/2"]) ②③ K (φ6.35 [1/4"])
* Precautions for replacing Check valve
ing 120°C [248°F].
*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

②③ Brazing or debrazing pipes
③ Check valve replacement
L (φ15.88 [5/8"])
M (φ28.6 [1-1/8"])

CV4a 2 (φ15.88 [5/8"])

H 1 (φ28.6 [1-1/8"])
Remove the brazing 1.
7 (φ15.88 [5/8"])
Remove the brazing 2.
3 (φ15.88
5 (φ15.88 [5/8"])
Remove the brazing 3 and 4.
CV9a 8 (φ15.88 [5/8"])
Remove the brazing 5 and 6.
6 (φ15.88 [5/8"])
4 (φ15.88 [5/8"])
J
Remove the brazing 7 and 8.
* This figure does not show heat exchanger.
③ Angle of the pipes when replacing CV8a,CV9a,CV10a
(Figure as viewed from point Q)


* Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b,
SV4c, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures.
Following instructions are applicable to 1-4 service parts on the table below.
Things required for replacing Item
Numbers
2 Check valve (CV4a, CV8a)
4 Check valve (CV6a, CV10a)
3. Procedures
Remove each part according to the 1)-3) procedures on the next page before replacing service parts. Mount the removed parts back in place in a reversed procedures of 1)-3) on the next page after replacing service parts.
peripheral piping devices. Fix the Solenoid valve block ASSY and the supporting plate with the fixing screw (M5). ⑦ Braze B-H part (total 7 places), and connect the solenoid valve block and the heat exchanger header with the connect-
ing pipe (φ9.52 [3/8"]) that comes with the service parts set. ⑧ Mount the solenoid valve block coil cover, solenoid valve coil, and peripheral cables back in place.


④⑦ Brazing or debrazing pipes ⑤ Removing Solenoid
④⑦B (φ19.05 [3/4"])
①Coil cover, Solenoid valve coil

valve block ASSY E (φ28.6 [1-1/8"])
F (φ9.52 [3/8"])


④⑦C (φ15.88
F
D
H (φ9.52 [3/8"])
H G Removed Solenoid valve block ASSY
G (φ15.88 [5/8"]) * This figure does not show heat exchanger.
②⑥ Removing or installing
③ Cutting pipes Cutting pipes positions Cut the pipe at 60mm ahead from the Bending R end with a pipe cutter.
④⑦D (φ15.88
Supporting plate for solenoid valve block
A (φ12.7
After cutting pipe, remove the pipe from the brazed A.
⑦ Brazing connecting pipe (φ9.52 [3/8"])

Brazing (heat exchanger header side)
Service parts set supplied connecting pipe ( φ 9.52 [3/8"])
Heat exchanger ③⑦A (φ12.7 [1/2"])
* Refer to the next page for Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures.

① Remove the solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d)
replacement procedures" on the front page.
② Debraze I-O parts (total 7 places), and remove the Check valve ASSY.
③ Replace the Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) to be serviced while it is removed from the unit.
Braze the pipes as they were according to the angle of the pipes on the figure below (Figure as viewed from point Q).
④ Mount the solenoid valve block ASSY, coil cover, and peripheral cables back in place according to "(1) Solenoid valve
block ASSY (SV4a, SV4b, SV4c, SV4d) replacement procedures" on the front page.

②③ I (φ19.05 [3/4"])
②③ J (φ15.88 [5/8"])
②③ K (φ15.88 [5/8"])
②③ L (φ6.35 [1/4"])
②③ M (φ12.7 [1/2"])
* Precautions for replacing Check valve
ing 120°C [248°F].
*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

②③Brazing or debrazing pipes
③Check valve replacement
N (φ15.88 [5/8"])
O (φ28.6 [1-1/8"])


Remove the brazing 1.
N CV6a CV4a 2 (φ15.88 [5/8"])
1 (φ28.6 [1-1/8"])
Remove the brazing 2.
5 (φ25.4 [1"])
When replacing CV8a:
7 (φ15.88 [5/8"])
3 (φ28.6 [1-1/8"])
Remove the brazing 3 and 4.
K
Remove the brazing 5 and 6.
8 (φ15.88 [5/8"]) 6 (φ25.4 [1"]) 4 (φ28.6 [1-1/8"])
M G
Remove the brazing 7 and 8.
* This figure does not show heat exchanger.
③Angle of the pipes when replacing CV8a,CV9a,CV10a (Figure as viewed from point Q)


1. Applicable models
PURY-P72THMU-A(-BS), PURY-P72YHMU-A(-BS)
……Low pressure twinning kit (optional accessory) is built in.
* The parts can be replaced without removing the Solenoid valve ASSY on the unit for the units that do not have
built-in low pressure twinning kit (optional accessory).
NO. Item Applicable models
PURY-P72THMU-A(-BS) PURY-P72YHMU-A(-BS) Capillary tube ASSY (CP1)
Removing the Solenoid valve (SV1a) and the Capillary tube ASSY (CP1) individually is difficult when the low
pressure twinning kit (optional accessory) is built in. Refer to the procedures Ԙԙ below and replace the parts.
Heat exchanger A (φ9.52 [3/8"])


A
Low pressure twinning kit (optional accessory)
NO.1 Solenoid valve (SV1a)
NO.2 Capillary tube ASSY (CP1)
B (φ6.35 [1/4"])
Solenoid valve ASSY
ԘDebraze A and B, and remove solenoid valve ASSY
ԙReplace Solenoid valve (SV1a) or Capillary tube ASSY
from the unit.
(CP1), and mount them again.
Solenoid valve (SV1a)

*Special care must be taken when replacing heavy parts.
Work procedure Explanatory figure
Work procedure Explanatory figure
two lock nuts on the control box cover. 1) Check the terminal connection of the power wire or of the transmission line. 2) Check the transformer. 3) Check the address switch. (2) When the control board is replaced, the followings

must be noted. (1) Check that the board type is G,GA, or GB(HB). (2) Check that the wire and the connector are properly con-
nected.
It is not required to remove the two fixing screws on the control box when checking the inside.
Loosen Service panel · Ceiling panel · Control Box

*Special care must be taken when replacing heavy parts.
Work procedure Explanatory figure
(1) Remove the service panel. 1) For TH11, TH12, and TH15, refer to 1. 1)-2). 2) For TH16, refer to (1)-1.2.3. (GA type only) (2) Remove the lead wire of the piping sensor from the

control board. 1) TH11,TH12 (CN10) 2) TH15,TH16 (CN11) (3) Pull out the temperature sensor from the tempera-
ture sensor housing, and replace the temperature sensor with the new one. (4) Connect the lead wire of the temperature sensor se-
curely on the control board.

CMB-1016NU-GA
4. Pressure sensor
Work procedure Explanatory figure
(1) Remove the service panel. 1) For the pressure sensors PS1 and PS3, refer to 1. 1)-2). (2) Remove the pressure sensor connector in trouble
from the control board, and insulate the connector. 1) Liquid-side pressure sensor (CNP1) 2) Intermediate-part pressure sensor (CNP3) (3) Attach a new pressure sensor to the place which is

shown in the figure, and insert the connector to the control board.
When gas leaks from the pressure sensor, repair the leak, and follow the instructions above if required.

Work procedure Explanatory figure
(1) Remove the service panel.(Refer to (1)-1.2.3.) (2) Replace the LEV in trouble.

Secure enough service space in the ceiling for welding operation, and conduct the work carefully.If required, dismount the unit from the ceiling, and conduct the work.
LEV2
SVM2
6. Solenoid valve
*Special care must be taken when replacing heavy parts.
Work procedure Explanatory figure
(1) Remove the service panel.(Refer to (1)-1.2.3.) (2) Remove the connector of the solenoid valve in trou-
ble. (3) Remove the solenoid valve coil. 1) The coils on the solenoid valves SVA, SVB, SVM1 and SVM2 can be serviced through the inspection door. SVC is accessible for replacement by removing the four mounting screws on the rear panel and removing the panel (if enough space is available on the back). (SVM1 is present only on the G and GA types, SVM2 on the GA type.)


SVM2b · Double-pipe heat exchanger · Solenoid valve
![Page 339 of the Mitsubishi Electronics P96 user manual — [8] Troubleshooting Using the Outdoor Unit LED Error Display](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-339.webp?w=400)
If the LED error display appear as follows while all the SW1 switches are set to OFF, check the items under the applicable item numbers below.
refer to IX [4] -8- (2) Troubleshooting transmission power circuit of outdoor unit. (2) If the LED error display becomes lit when the power is turned on with all the connectors on the control board except
CNDC disconnected, there is a problem with the wiring to those connectors or with the connectors themselves. (3) If nothing appears on the display under item (2) above AND the voltage between pins 1 and 3 of CNDC is within the
range between 220 VDC and 380 VDC, control board failure is suspected.
(2) If the LED display appears as noted in "X [1] 2. LED display at Initial setting" (page 333) while the transmission cables
to TB3 and TB7 are disconnected, failure with the transmission cable or the connected equipment is suspected.
![Page 340 of the Mitsubishi Electronics P96 user manual — [1] How to Read the LED on the Service Monitor ...............................................................333](/cdn/reader/51/514963dd01e98a15c07b4b4b7212774289d8593141b627220a19e6af65fda393/images/page-340.webp?w=400)

- 332 -

[ X LED Monitor Display on the Outdoor Unit Board ]
X LED Monitor Display on the Outdoor Unit Board [1] How to Read the LED on the Service Monitor

Pressure and temperature are examples of numerical values, and operating conditions and the on-off status of solenoid valve are examples of flag display.

Use the following conversion formula to convert the displayed value into
a value in SI unit. Value in SI unit (MPa) = Displayed value (kg/cm2) x 0.098

Model and capacity [H-20] : Cooling/Heating 20 HP For the first few minutes after power on, the capacity of each outdoor unit is displayed. Thereafter, the com- bined capacity is displayed.
After the initial settings have been completed, the information on these items can be checked by making the switch setting that corresponds to No. 517 in the LED display table.
Only item No. 1 "Software Version" appears on the display if there is a wiring failure between the control board and the trans- mission line power supply board or if the circuit board has failed.

[ X LED Monitor Display on the Outdoor Unit Board ]
The outdoor unit has a simple clock function that enables the unit to calculate the current time with an internal timer by receiv- ing the time set by the system controller, such as G(B)-50A. If an error (including a preliminary error) occurs, the error history data and the error detection time are stored into the service memory. The error detection time stored in the service memory and the current time can be seen on the service LED.
1) Use the time displayed on the service LED as a reference. 2) The date and the time are set to "00" by default. If a system controller that sets the time, such as G(B)-50A is not connected, the elapsed time and days since the first power on will be displayed. If the time set on a system controller is received, the count will start from the set date and the time. 3) The time is not updated while the power of the indoor unit is turned off. When the power is turned off and then on again, the count will resume from the time before the power was turned off. Thus, the time that differs the actual time will be displayed. (This also applies when a power failure occurs.) The system controller, such as G(B)-50A, adjusts the time once a day. When the system controller is connected, the time will be automatically updated to the correct current time after the time set by the system controller is received. (The data stored into the memory before the set time is received will not be updated.)

* Disappears if the time data is deviated due to a power failure, or if a system controller that sets the time is not connected.

* Appears between the year and the month, and nothing appears when the date is displayed.
When the main controller that can set the time is not connected

* Appears between the year and the month, and nothing appears when the date is displayed.

[ X LED monitor display on the outdoor unit board ]
Display of the latest pre-
(Including IC and BC) 0000 to 9999 (Address and error codes highlighted) B If no errors are detected,
" " appears on the dis-
If no preliminary errors
are detected, " " ap-
trolled, " " [ % ] ap-
trolled, " " [ % ] ap-
pears on the display.
mand capacity 0000 to 9999 B If not demanded con-
pears on the display.
capacity 0000 to 9999 B If not demanded con-
pears on the display.
play.
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
OC/OS error 0000 to 9999 (Address and error codes highlighted) B B
0000 to 9999 (Address and error codes highlighted) A A
sion line A A
eration 72C OC CPU in oper-
Top 21S4a CH11 SV1a SV2
SV4a SV4b SV4c SV5c SV4d SV9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
Lighting Comp in op-
Check (error) display 1
Check (error) display 2
2 0100000000 Check (error) display 3
Relay output display 1
10 0101000000 Contact point demand
9 1001000000 Communication de-
3 1100000000 Relay out-
XLED monitor display on the outdoor unit board LED monitor display
No. SW1
- 335 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
came to an abnormal stop
The lamp goes off when
Each unit that comes to
an abnormal unit will be
given a sequential num-
sponds to the unit that
ber in ascending order
check Top Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 B The lamp that corre-
Unlit while the unit is
stopped or in the fan
the error is reset.
Top Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 B Lit during cooling
starting with 1.
lights.
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
A A
A A
sure error A A
15 1111000000 OC/OS identification OC/OS A A
Bottom Unit No. 9 Unit No. 10 Unit No. 11 Unit No. 12 Unit No. 13 Unit No. 14 Unit No. 15 Unit No. 16
17 1000100000 Top Unit No. 17 Unit No. 18 Unit No. 19 Unit No. 20 Unit No. 21 Unit No. 22 Unit No. 23 Unit No. 24
Bottom Unit No. 25 Unit No. 26 Unit No. 27 Unit No. 28 Unit No. 29 Unit No. 30 Unit No. 31 Unit No. 32
18 0100100000 Top Unit No. 33 Unit No. 34 Unit No. 35 Unit No. 36 Unit No. 37 Unit No. 38 Unit No. 39 Unit No. 40
Bottom Unit No. 41 Unit No. 42 Unit No.43 Unit No. 44 Unit No. 45 Unit No. 46 Unit No47 Unit No. 48
Bottom Unit No. 9 Unit No. 10 Unit No. 11 Unit No. 12 Unit No. 13 Unit No. 14 Unit No. 15 Unit No. 16
21 1010100000 Top Unit No. 17 Unit No. 18 Unit No. 19 Unit No. 20 Unit No. 21 Unit No. 22 Unit No. 23 Unit No. 24
Bottom Unit No. 25 Unit No. 26 Unit No. 27 Unit No. 28 Unit No. 29 Unit No. 30 Unit No. 31 Unit No. 32
22 0110100000 Top Unit No. 33 Unit No. 34 Unit No. 35 Unit No. 36 Unit No. 37 Unit No. 38 Unit No. 39 Unit No. 40
Bottom Unit No. 41 Unit No. 42 Unit No.43 Unit No. 44 Unit No. 45 Unit No. 46 Unit No47 Unit No. 48
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
tion signal 3-minutes restart mode Compressor
19 1100100000 Top Unit No. 49 Unit No. 50
23 1110100000 Top Unit No. 49 Unit No. 50
16 0000100000 Indoor unit
20 0010100000 Indoor unit
No. SW1
- 336 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
Top Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 B Lit when thermostat is on
Unlit when thermostat is
off Bottom Unit No. 9 Unit No. 10 Unit No. 11 Unit No. 12 Unit No. 13 Unit No. 14 Unit No. 15 Unit No. 16
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
OFF Fan Stop B
25 1001100000 Top Unit No. 17 Unit No. 18 Unit No. 19 Unit No. 20 Unit No. 21 Unit No. 22 Unit No. 23 Unit No. 24
Bottom Unit No. 25 Unit No. 26 Unit No. 27 Unit No. 28 Unit No. 29 Unit No. 30 Unit No. 31 Unit No. 32
26 0101100000 Top Unit No. 33 Unit No. 34 Unit No. 35 Unit No. 36 Unit No. 37 Unit No. 38 Unit No. 39 Unit No. 40
Bottom Unit No. 41 Unit No. 42 Unit No.43 Unit No. 44 Unit No. 45 Unit No. 46 Unit No47 Unit No. 48
up Defrost Oil balance Low fre-
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
stop Standby Cooling Cooling-
mode Stop Thermo OFF Abnormal
27 1101100000 Top Unit No. 49 Unit No. 50
37 1010010000 BC operation mode Cooling-only
39 1110010000 Outdoor unit Operation
42 0101010000 Outdoor unit control
24 0001100000 Indoor unit
No. SW1
- 337 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
data -99.9 to 999.9 A A The unit is [kgf/cm2]
45 1011010000 TH4 -99.9 to 999.9 A A The unit is [°C]
56 0001110000 THHS1 -99.9 to 999.9 A A The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
46 0111010000 TH3 -99.9 to 999.9 A A
47 1111010000 TH7 -99.9 to 999.9 A A
48 0000110000 TH6 -99.9 to 999.9 A A
50 0100110000 TH5 -99.9 to 999.9 A A
57 1001110000 THBOX -99.9 to 999.9 A A
data -99.9 to 999.9 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
58 0101110000 High-pressure sensor
59 1101110000 Low-pressure sensor
No. SW1
- 338 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
frequency of the inverter
depends on the type of
the integer multiples (x1,
x2 etc.) of the operating
The unit is [rps]Output
frequency of the com-
(OC+OS) 0000 to 9999 B Control data [ Hz ]
81 1000101000 Target Tc -99.9 to 999.9 B The unit is [°C]
pressor.
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
78 0111001000 Qj 0000 to 9999 B B
79 1111001000 Qjc 0000 to 9999 B B
80 0000101000 Qjh 0000 to 9999 B B
83 1100101000 Tc -99.9 to 999.9 A A
84 0010101000 Te -99.9 to 999.9 A A
unit 0000 to 9999 A A
88 0001101000 COMP frequency 0000 to 9999 A A
0000 to 9999 A A
82 0100101000 Target Te -99.9 to 999.9 B
93 1011101000 All AK (OC+OS) 0000 to 9999 B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
87 1110101000 Total frequency of each
86 0110101000 Total frequencies
No. SW1
- 339 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
quency 0000 to 9999 A A Twice the actual output
95 1111101000 FAN 0000 to 9999 A A Fan output [ % ]
rent (DC) 00.0 to 999.9 A A Peak value[A]
111 1111011000 COMP bus voltage 00.0 to 999.9 A A The unit is
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
94 0111101000 AK 0000 to 9999 A A
0000 to 9999 B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
unit went into the mode
96 0000011000 Fan inverter output fre-
108 0011011000 COMP operating cur-
Number of times the
to remedy wet vapor
No. SW1
- 340 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
rise A A Stays lit for 90 seconds
after the completion of
Upper 4 digits 0000 to 9999 A A Count-up at start-up
The unit is [Time]
rotation purpose) 0000 to 9999 B The unit is [ h ]
Upper 4 digits 0000 to 9999 A A The unit is
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
Lower 4 digits 0000 to 9999 A A
Lower 4 digits 0000 to 9999 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
sure drop Abnormal Td
121 1001111000 Backup mode Abnormal
123 1101111000 COMP number of start-
124 0011111000 COMP number of start-
time of compressor (for
117 1010111000 COMP Operation time
118 0110111000 COMP Operation time
129 1000000100 Integrated operation
No. SW1
- 341 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
B
B
B
B
B
B
B
B
B
133 1010000100 Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2
Bottom SVA3 SVB3 SVC3 SVA4 SVB4 SVC4
134 0110000100 Top SVA5 SVB5 SVC5 SVA6 SVB6 SVC6
Bottom SVA7 SVB7 SVC7 SVA8 SVB8 SVC8
135 1110000100 Top SVA9 SVB9 SVC9 SVA10 SVB10 SVC10
Bottom SVA11 SVB11 SVC11 SVA12 SVB12 SVC12
136 0001000100 Top SVA13 SVB13 SVC13 SVA14 SVB14 SVC14
Bottom SVA15 SVB15 SVC15 SVA16 SVB16 SVC16
Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2
Bottom SVA3 SVB3 SVC3 SVA4 SVB4 SVC4
139 1101000100 Top SVA5 SVB5 SVC5 SVA6 SVB6 SVC6
Bottom SVA7 SVB7 SVC7 SVA8 SVB8 SVC8
140 0011000100 Top SVA9 SVB9 SVC9 SVA10 SVB10 SVC10
Bottom SVA11 SVB11 SVC11 SVA12 SVB12 SVC12
141 1011000100 Top SVA13 SVB13 SVC13 SVA14 SVB14 SVC14
Bottom SVA15 SVB15 SVC15 SVA16 SVB16 SVC16
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
Top SVM1 SVM2 SVM1b SVM2b
132 0010000100 Relay out-
138 0101000100 Relay out-
No. SW1
- 342 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
(Fully open:2000)
(Fully open:2000)
(Fully open:2000)
159 1111100100 BC(Main)LEV1 0000 to 2000 B LEV1 opening
160 0000010100 BC(Main)LEV3 0000 to 2000 B LEV3 opening
163 1100010100 BC(Sub1)LEV3 0000 to 2000 B LEV3 opening
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
B
B
B
B
TH11 -99.9 to 999.9 B
150 0110100100 BC(Main)TH12 -99.9 to 999.9 B
151 1110100100 BC(Main)TH15 -99.9 to 999.9 B
152 0001100100 BC(Main)TH16 -99.9 to 999.9 B
153 1001100100 BC(Main)63HS1 -99.9 to 999.9 B
154 0101100100 BC(Main)63HS3 -99.9 to 999.9 B
155 1101100100 BC(Main)SC11 -99.9 to 999.9 B
156 0011100100 BC(Main)SH12 -99.9 to 999.9 B
157 1011100100 BC(Main)SH13 -99.9 to 999.9 B
158 0111100100 BC(Main)SC16 -99.9 to 999.9 B
161 1000010100 BC(Sub1)TH12 -99.9 to 999.9 B
162 0100010100 BC(Sub1)TH15 -99.9 to 999.9 B
Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2
Bottom SVA3 SVB3 SVC3 SVA4 SVB4 SVC4
144 0000100100 Top SVA5 SVB5 SVC5 SVA6 SVB6 SVC6
Bottom SVA7 SVB7 SVC7 SVA8 SVB8 SVC8
145 1000100100 Top SVA9 SVB9 SVC9 SVA10 SVB10 SVC10
Bottom SVA11 SVB11 SVC11 SVA12 SVB12 SVC12
146 0100100100 Top SVA13 SVB13 SVC13 SVA14 SVB14 SVC14
Bottom SVA15 SVB15 SVC15 SVA16 SVB16 SVC16
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
149 1010100100 BC(Main or standard)
143 1111000100 Relay out-
No. SW1
- 343 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
(Fully open:2000)
(Fully open:2000)
166 0110010100 BC(Sub2)LEV3 0000 to 2000 B LEV3a opening
167 1110010100 BC(Main)LEV2 0000 to 2000 B LEV2 opening
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
164 0010010100 BC(Sub2)TH12 -99.9 to 999.9 B
165 1010010100 BC(Sub2)TH25 -99.9 to 999.9 B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
- 344 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
information of the OC nor
error information of the IC
178 0100110100 Error history 1 0000 to 9999 B B Address and error codes
If no errors are detected,
" " appears on the dis-
tion of the OS does not
appear on the OC.
appears on the OS.
play.
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
179 1100110100 Error details of inverter Error details of inverter (0001-0120) A A
180 0010110100 Error history 2 0000 to 9999 B B
181 1010110100 Error details of inverter Error details of inverter (0001-0120) A A
182 0110110100 Error history 3 0000 to 9999 B B
183 1110110100 Error details of inverter Error details of inverter (0001-0120) A A
184 0001110100 Error history 4 0000 to 9999 B B
185 1001110100 Error details of inverter Error details of inverter (0001-0120) A A
186 0101110100 Error history 5 0000 to 9999 B B
187 1101110100 Error details of inverter Error details of inverter (0001-0120) A A
188 0011110100 Error history 6 0000 to 9999 B B
189 1011110100 Error details of inverter Error details of inverter (0001-0120) A A
190 0111110100 Error history 7 0000 to 9999 B B
191 1111110100 Error details of inverter Error details of inverter (0001-0120) A A
192 0000001100 Error history 8 0000 to 9999 B B
193 1000001100 Error details of inverter Error details of inverter (0001-0120) A A
194 0100001100 Error history 9 0000 to 9999 B B
195 1100001100 Error details of inverter Error details of inverter (0001-0120) A A
196 0010001100 Error history 10 0000 to 9999 B B
197 1010001100 Error details of inverter Error details of inverter (0001-0120) A A
backup before error) 0000 to 9999 B B
199 1110001100 Error details of inverter Error details of inverter (0001-0120) A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
(At the time of last data
198 0110001100 Error history of inverter
No. SW1
- 345 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
sure error A A
202 0101001100 OC/OS identification OC/OS A A
OFF Fan Stop A A
eration 72C OC Always lit A A
up Defrost Oil balance Low fre-
Top 21S4a CH11 SV1a SV2
SV4a SV4b SV4c SV5c SV4d SV9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
tion signal 3-minutes restart mode Compressor
stop Standby Cooling Cooling-
mode Stop Thermo OFF Abnormal
203 1101001100 BC operation mode Cooling-only
Lighting Comp in op-
205 1011001100 Outdoor unit Operation
211 1100101100 Relay output display 1
208 0000101100 Outdoor unit control
No. SW1
- 346 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
data -99.9 to 999.9 A A The unit is [kgf/cm2]
216 0001101100 TH4 -99.9 to 999.9 A A The unit is [°C]
227 1100011100 THHS1 -99.9 to 999.9 A A The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
217 1001101100 TH3 -99.9 to 999.9 A A
218 0101101100 TH7 -99.9 to 999.9 A A
219 1101101100 TH6 -99.9 to 999.9 A A
221 1011101100 TH5 -99.9 to 999.9 A A
228 0010011100 THBOX -99.9 to 999.9 A A
data -99.9 to 999.9 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
229 1010011100 High-pressure sensor
230 0110011100 Low-pressure sensor
No. SW1
- 347 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
quency 0000 to 9999 A A Twice the actual output
266 0101000010 FAN 0000 to 9999 A A Fan inverter output
254 0111111100 Tc -99.9 to 999.9 A A The unit is [°C]
252 0011111100 Target Tc -99.9 to 999.9 B The unit is [°C]
(OC+OS) 0000 to 9999 B Control data
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
249 1001111100 Qj 0000 to 9999 B B
250 0101111100 Qjc 0000 to 9999 B B
251 1101111100 Qjh 0000 to 9999 B B
255 1111111100 Te -99.9 to 999.9 A A
unit 0000 to 9999 A A
259 1100000010 COMP frequency 0000 to 9999 A A
265 1001000010 AK 0000 to 9999 A A
253 1011111100 Target Te -99.9 to 999.9 B
264 0001000010 All AK (OC+OS) 0000 to 9999 B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
258 0100000010 Total frequency of each
267 1101000010 Fan inverter output fre-
257 1000000010 Total frequencies
No. SW1
- 348 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
rent (DC) 00.0 to 999.9 A A Peak value[A]
282 0101100010 COMP bus voltage 00.0 to 999.9 A A The unit is [ V ]
Upper 4 digits 0000 to 9999 A A The unit is [ h ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
Lower 4 digits 0000 to 9999 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
288 0000010010 COMP Operation time
289 1000010010 COMP Operation time
279 1110100010 COMP operating cur-
No. SW1
- 349 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
Upper 4 digits 0000 to 9999 A A Count-up at start-up
The unit is [Time]
rotation purpose) 0000 to 9999 B The unit is [ h ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
Lower 4 digits 0000 to 9999 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
294 0110010010 COMP number of start-
295 1110010010 COMP number of start-
time of compressor (for
300 0011010010 Integrated operation
No. SW1
- 350 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
301 1011010010 Power supply unit OC/OS Address B
302 0111010010 Start-up unit OC/OS Address B
320 0000001010 BC(Main)TH11 -99.9 to 999.9 B
321 1000001010 BC(Main)TH12 -99.9 to 999.9 B
322 0100001010 BC(Main)TH15 -99.9 to 999.9 B
323 1100001010 BC(Main)TH16 -99.9 to 999.9 B
324 0010001010 BC(Main)PS1 -99.9 to 999.9 B
325 1010001010 BC(Main)PS3 -99.9 to 999.9 B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
- 351 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
330 0101001010 BC(Main)LEV1 0000 to 2000 B
331 1101001010 BC(Main)LEV3 0000 to 2000 B
332 0011001010 BC(Sub1)TH12 -99.9 to 999.9 B
333 1011001010 BC(Sub1)TH15 -99.9 to 999.9 B
334 0111001010 BC(Sub1)LEV3 0000 to 2000 B
335 1111001010 BC(Sub2)TH12 -99.9 to 999.9 B
336 0000101010 BC(Sub2)TH25 -99.9 to 999.9 B
337 1000101010 BC(Sub2)LEV3 0000 to 2000 B
338 0100101010 BC(Main)LEV2 0000 to 2000 B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
- 352 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
351 1111101010 IC1 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alternately ev-
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
352 0000011010 IC2 Address/capacity code 0000 to 9999 0000 to 9999
353 1000011010 IC3 Address/capacity code 0000 to 9999 0000 to 9999
354 0100011010 IC4 Address/capacity code 0000 to 9999 0000 to 9999
355 1100011010 IC5 Address/capacity code 0000 to 9999 0000 to 9999
356 0010011010 IC6 Address/capacity code 0000 to 9999 0000 to 9999
357 1010011010 IC7 Address/capacity code 0000 to 9999 0000 to 9999
358 0110011010 IC8 Address/capacity code 0000 to 9999 0000 to 9999
359 1110011010 IC9 Address/capacity code 0000 to 9999 0000 to 9999
360 0001011010 IC10 Address/capacity code 0000 to 9999 0000 to 9999
361 1001011010 IC11 Address/capacity code 0000 to 9999 0000 to 9999
362 0101011010 IC12 Address/capacity code 0000 to 9999 0000 to 9999
363 1101011010 IC13 Address/capacity code 0000 to 9999 0000 to 9999
364 0011011010 IC14 Address/capacity code 0000 to 9999 0000 to 9999
365 1011011010 IC15 Address/capacity code 0000 to 9999 0000 to 9999
366 0111011010 IC16 Address/capacity code 0000 to 9999 0000 to 9999
367 1111011010 IC17 Address/capacity code 0000 to 9999 0000 to 9999
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Remarks · ery 5 seconds · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
368 0000111010 IC18 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alternately ev-
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
369 1000111010 IC19 Address/capacity code 0000 to 9999 0000 to 9999
370 0100111010 IC20 Address/capacity code 0000 to 9999 0000 to 9999
371 1100111010 IC21 Address/capacity code 0000 to 9999 0000 to 9999
372 0010111010 IC22 Address/capacity code 0000 to 9999 0000 to 9999
373 1010111010 IC23 Address/capacity code 0000 to 9999 0000 to 9999
374 0110111010 IC24 Address/capacity code 0000 to 9999 0000 to 9999
375 1110111010 IC25 Address/capacity code 0000 to 9999 0000 to 9999
376 0001111010 IC26 Address/capacity code 0000 to 9999 0000 to 9999
377 1001111010 IC27 Address/capacity code 0000 to 9999 0000 to 9999
378 0101111010 IC28 Address/capacity code 0000 to 9999 0000 to 9999
379 1101111010 IC29 Address/capacity code 0000 to 9999 0000 to 9999
380 0011111010 IC30 Address/capacity code 0000 to 9999 0000 to 9999
381 1011111010 IC31 Address/capacity code 0000 to 9999 0000 to 9999
382 0111111010 IC32 Address/capacity code 0000 to 9999 0000 to 9999
383 1111111010 IC33 Address/capacity code 0000 to 9999 0000 to 9999
384 0000000110 IC34 Address/capacity code 0000 to 9999 0000 to 9999
385 1000000110 IC35 Address/capacity code 0000 to 9999 0000 to 9999
386 0100000110 IC36 Address/capacity code 0000 to 9999 0000 to 9999
387 1100000110 IC37 Address/capacity code 0000 to 9999 0000 to 9999
388 0010000110 IC38 Address/capacity code 0000 to 9999 0000 to 9999
389 1010000110 IC39 Address/capacity code 0000 to 9999 0000 to 9999
390 0110000110 IC40 Address/capacity code 0000 to 9999 0000 to 9999
391 1110000110 IC41 Address/capacity code 0000 to 9999 0000 to 9999
392 0001000110 IC42 Address/capacity code 0000 to 9999 0000 to 9999
393 1001000110 IC43 Address/capacity code 0000 to 9999 0000 to 9999
394 0101000110 IC44 Address/capacity code 0000 to 9999 0000 to 9999
395 1101000110 IC45 Address/capacity code 0000 to 9999 0000 to 9999
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Remarks · ery 5 seconds · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
396 0011000110 IC46 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alternately ev-
408 0001100110 IC1 Suction temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
397 1011000110 IC47 Address/capacity code 0000 to 9999 0000 to 9999
398 0111000110 IC48 Address/capacity code 0000 to 9999 0000 to 9999
399 1111000110 IC49 Address/capacity code 0000 to 9999 0000 to 9999
400 0000100110 IC50 Address/capacity code 0000 to 9999 0000 to 9999
409 1001100110 IC2 Suction temperature -99.9 to 999.9
410 0101100110 IC3 Suction temperature -99.9 to 999.9
411 1101100110 IC4 Suction temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1

[ X LED monitor display on the outdoor unit board ]
412 0011100110 IC5 Suction temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
413 1011100110 IC6 Suction temperature -99.9 to 999.9
414 0111100110 IC7 Suction temperature -99.9 to 999.9
415 1111100110 IC8 Suction temperature -99.9 to 999.9
416 0000010110 IC9 Suction temperature -99.9 to 999.9
417 1000010110 IC10 Suction temperature -99.9 to 999.9
418 0100010110 IC11 Suction temperature -99.9 to 999.9
419 1100010110 IC12 Suction temperature -99.9 to 999.9
420 0010010110 IC13 Suction temperature -99.9 to 999.9
421 1010010110 IC14 Suction temperature -99.9 to 999.9
422 0110010110 IC15 Suction temperature -99.9 to 999.9
423 1110010110 IC16 Suction temperature -99.9 to 999.9
424 0001010110 IC17 Suction temperature -99.9 to 999.9
425 1001010110 IC18 Suction temperature -99.9 to 999.9
426 0101010110 IC19 Suction temperature -99.9 to 999.9
427 1101010110 IC20 Suction temperature -99.9 to 999.9
428 0011010110 IC21 Suction temperature -99.9 to 999.9
429 1011010110 IC22 Suction temperature -99.9 to 999.9
430 0111010110 IC23 Suction temperature -99.9 to 999.9
431 1111010110 IC24 Suction temperature -99.9 to 999.9
432 0000110110 IC25 Suction temperature -99.9 to 999.9
433 1000110110 IC26 Suction temperature -99.9 to 999.9
434 0100110110 IC27 Suction temperature -99.9 to 999.9
435 1100110110 IC28 Suction temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
436 0010110110 IC29 Suction temperature -99.9 to 999.9 B The unit is [°C]
458 0101001110 IC1 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
437 1010110110 IC30 Suction temperature -99.9 to 999.9
438 0110110110 IC31 Suction temperature -99.9 to 999.9
439 1110110110 IC32 Suction temperature -99.9 to 999.9
440 0001110110 IC33 Suction temperature -99.9 to 999.9
441 1001110110 IC34 Suction temperature -99.9 to 999.9
442 0101110110 IC35 Suction temperature -99.9 to 999.9
443 1101110110 IC36 Suction temperature -99.9 to 999.9
444 0011110110 IC37 Suction temperature -99.9 to 999.9
445 1011110110 IC38 Suction temperature -99.9 to 999.9
446 0111110110 IC39 Suction temperature -99.9 to 999.9
447 1111110110 IC40 Suction temperature -99.9 to 999.9
448 0000001110 IC41 Suction temperature -99.9 to 999.9
449 1000001110 IC42 Suction temperature -99.9 to 999.9
450 0100001110 IC43 Suction temperature -99.9 to 999.9
451 1100001110 IC44 Suction temperature -99.9 to 999.9
452 0010001110 IC45 Suction temperature -99.9 to 999.9
453 1010001110 IC46 Suction temperature -99.9 to 999.9
454 0110001110 IC47 Suction temperature -99.9 to 999.9
455 1110001110 IC48 Suction temperature -99.9 to 999.9
456 0001001110 IC49 Suction temperature -99.9 to 999.9
457 1001001110 IC50 Suction temperature -99.9 to 999.9
459 1101001110 IC2 Liquid pipe temperature -99.9 to 999.9
460 0011001110 IC3 Liquid pipe temperature -99.9 to 999.9
461 1011001110 IC4 Liquid pipe temperature -99.9 to 999.9
462 0111001110 IC5 Liquid pipe temperature -99.9 to 999.9
463 1111001110 IC6 Liquid pipe temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
464 0000101110 IC7 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
465 1000101110 IC8 Liquid pipe temperature -99.9 to 999.9
466 0100101110 IC9 Liquid pipe temperature -99.9 to 999.9
467 1100101110 IC10 Liquid pipe temperature -99.9 to 999.9
468 0010101110 IC11 Liquid pipe temperature -99.9 to 999.9
469 1010101110 IC12 Liquid pipe temperature -99.9 to 999.9
470 0110101110 IC13 Liquid pipe temperature -99.9 to 999.9
471 1110101110 IC14 Liquid pipe temperature -99.9 to 999.9
472 0001101110 IC15 Liquid pipe temperature -99.9 to 999.9
473 1001101110 IC16 Liquid pipe temperature -99.9 to 999.9
474 0101101110 IC17 Liquid pipe temperature -99.9 to 999.9
475 1101101110 IC18 Liquid pipe temperature -99.9 to 999.9
476 0011101110 IC19 Liquid pipe temperature -99.9 to 999.9
477 1011101110 IC20 Liquid pipe temperature -99.9 to 999.9
478 0111101110 IC21 Liquid pipe temperature -99.9 to 999.9
479 1111101110 IC22 Liquid pipe temperature -99.9 to 999.9
480 0000011110 IC23 Liquid pipe temperature -99.9 to 999.9
481 1000011110 IC24 Liquid pipe temperature -99.9 to 999.9
482 0100011110 IC25 Liquid pipe temperature -99.9 to 999.9
483 1100011110 IC26 Liquid pipe temperature -99.9 to 999.9
484 0010011110 IC27 Liquid pipe temperature -99.9 to 999.9
485 1010011110 IC28 Liquid pipe temperature -99.9 to 999.9
486 0110011110 IC29 Liquid pipe temperature -99.9 to 999.9
487 1110011110 IC30 Liquid pipe temperature -99.9 to 999.9
488 0001011110 IC31 Liquid pipe temperature -99.9 to 999.9
489 1001011110 IC32 Liquid pipe temperature -99.9 to 999.9
490 0101011110 IC33 Liquid pipe temperature -99.9 to 999.9
491 1101011110 IC34 Liquid pipe temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
492 0011011110 IC35 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
493 1011011110 IC36 Liquid pipe temperature -99.9 to 999.9
494 0111011110 IC37 Liquid pipe temperature -99.9 to 999.9
495 1111011110 IC38 Liquid pipe temperature -99.9 to 999.9
496 0000111110 IC39 Liquid pipe temperature -99.9 to 999.9
497 1000111110 IC40 Liquid pipe temperature -99.9 to 999.9
498 0100111110 IC41 Liquid pipe temperature -99.9 to 999.9
499 1100111110 IC42 Liquid pipe temperature -99.9 to 999.9
500 0010111110 IC43 Liquid pipe temperature -99.9 to 999.9
501 1010111110 IC44 Liquid pipe temperature -99.9 to 999.9
502 0110111110 IC45 Liquid pipe temperature -99.9 to 999.9
503 1110111110 IC46 Liquid pipe temperature -99.9 to 999.9
504 0001111110 IC47 Liquid pipe temperature -99.9 to 999.9
505 1001111110 IC48 Liquid pipe temperature -99.9 to 999.9
506 0101111110 IC49 Liquid pipe temperature -99.9 to 999.9
507 1101111110 IC50 Liquid pipe temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
512 0000000001 Self-address Alternate display of self address and unit model A A
517 1010000001 Version/Capacity S/W version -> Refrigerant type -> Model and capacity -> Communication address A A
518 0110000001 OC address OC address display B
513 1000000001 IC/FU address Count-up display of number of connected units B
514 0100000001 RC address Count-up display of number of connected units B
515 1100000001 BC/BS/TU address Count-up display of number of connected units B
516 0010000001 OS address Count-up display of number of connected units B
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
- 360 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
523 1101000001 IC1 Gas pipe temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
524 0011000001 IC2 Gas pipe temperature -99.9 to 999.9
525 1011000001 IC3 Gas pipe temperature -99.9 to 999.9
526 0111000001 IC4 Gas pipe temperature -99.9 to 999.9
527 1111000001 IC5 Gas pipe temperature -99.9 to 999.9
528 0000100001 IC6 Gas pipe temperature -99.9 to 999.9
529 1000100001 IC7 Gas pipe temperature -99.9 to 999.9
530 0100100001 IC8 Gas pipe temperature -99.9 to 999.9
531 1100100001 IC9 Gas pipe temperature -99.9 to 999.9
532 0010100001 IC10 Gas pipe temperature -99.9 to 999.9
533 1010100001 IC11 Gas pipe temperature -99.9 to 999.9
534 0110100001 IC12 Gas pipe temperature -99.9 to 999.9
535 1110100001 IC13 Gas pipe temperature -99.9 to 999.9
536 0001100001 IC14 Gas pipe temperature -99.9 to 999.9
537 1001100001 IC15 Gas pipe temperature -99.9 to 999.9
538 0101100001 IC16 Gas pipe temperature -99.9 to 999.9
539 1101100001 IC17 Gas pipe temperature -99.9 to 999.9
540 0011100001 IC18 Gas pipe temperature -99.9 to 999.9
541 1011100001 IC19 Gas pipe temperature -99.9 to 999.9
542 0111100001 IC20 Gas pipe temperature -99.9 to 999.9
543 1111100001 IC21 Gas pipe temperature -99.9 to 999.9
544 0000010001 IC22 Gas pipe temperature -99.9 to 999.9
545 1000010001 IC23 Gas pipe temperature -99.9 to 999.9
546 0100010001 IC24 Gas pipe temperature -99.9 to 999.9
547 1100010001 IC25 Gas pipe temperature -99.9 to 999.9
548 0010010001 IC26 Gas pipe temperature -99.9 to 999.9
549 1010010001 IC27 Gas pipe temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
(A, B) *1 Remarks
550 0110010001 IC28 Gas pipe temperature -99.9 to 999.9 B The unit is [°C]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
551 1110010001 IC29 Gas pipe temperature -99.9 to 999.9
552 0001010001 IC30 Gas pipe temperature -99.9 to 999.9
553 1001010001 IC31 Gas pipe temperature -99.9 to 999.9
554 0101010001 IC32 Gas pipe temperature -99.9 to 999.9
555 1101010001 IC33 Gas pipe temperature -99.9 to 999.9
556 0011010001 IC34 Gas pipe temperature -99.9 to 999.9
557 1011010001 IC35 Gas pipe temperature -99.9 to 999.9
558 0111010001 IC36 Gas pipe temperature -99.9 to 999.9
559 1111010001 IC37 Gas pipe temperature -99.9 to 999.9
560 0000110001 IC38 Gas pipe temperature -99.9 to 999.9
561 1000110001 IC39 Gas pipe temperature -99.9 to 999.9
562 0100110001 IC40 Gas pipe temperature -99.9 to 999.9
563 1100110001 IC41 Gas pipe temperature -99.9 to 999.9
564 0010110001 IC42 Gas pipe temperature -99.9 to 999.9
565 1010110001 IC43 Gas pipe temperature -99.9 to 999.9
566 0110110001 IC44 Gas pipe temperature -99.9 to 999.9
567 1110110001 IC45 Gas pipe temperature -99.9 to 999.9
568 0001110001 IC46 Gas pipe temperature -99.9 to 999.9
569 1001110001 IC47 Gas pipe temperature -99.9 to 999.9
570 0101110001 IC48 Gas pipe temperature -99.9 to 999.9
571 1101110001 IC49 Gas pipe temperature -99.9 to 999.9
572 0011110001 IC50 Gas pipe temperature -99.9 to 999.9
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
Item Display Unit

[ X LED monitor display on the outdoor unit board ]
573 1011110001 IC1SH -99.9 to 999.9 B The unit is [ °C ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
574 0111110001 IC2SH -99.9 to 999.9
575 1111110001 IC3SH -99.9 to 999.9
576 0000001001 IC4SH -99.9 to 999.9
577 1000001001 IC5SH -99.9 to 999.9
578 0100001001 IC6SH -99.9 to 999.9
579 1100001001 IC7SH -99.9 to 999.9
580 0010001001 IC8SH -99.9 to 999.9
581 1010001001 IC9SH -99.9 to 999.9
582 0110001001 IC10SH -99.9 to 999.9
583 1110001001 IC11SH -99.9 to 999.9
584 0001001001 IC12SH -99.9 to 999.9
585 1001001001 IC13SH -99.9 to 999.9
586 0101001001 IC14SH -99.9 to 999.9
587 1101001001 IC15SH -99.9 to 999.9
588 0011001001 IC16SH -99.9 to 999.9
589 1011001001 IC17SH -99.9 to 999.9
590 0111001001 IC18SH -99.9 to 999.9
591 1111001001 IC19SH -99.9 to 999.9
592 0000101001 IC20SH -99.9 to 999.9
593 1000101001 IC21SH -99.9 to 999.9
594 0100101001 IC22SH -99.9 to 999.9
595 1100101001 IC23SH -99.9 to 999.9
596 0010101001 IC24SH -99.9 to 999.9
597 1010101001 IC25SH -99.9 to 999.9
598 0110101001 IC26SH -99.9 to 999.9
599 1110101001 IC27SH -99.9 to 999.9
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
600 0001101001 IC28SH -99.9 to 999.9 B The unit is [ °C ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
601 1001101001 IC29SH -99.9 to 999.9
602 0101101001 IC30SH -99.9 to 999.9
603 1101101001 IC31SH -99.9 to 999.9
604 0011101001 IC32SH -99.9 to 999.9
605 1011101001 IC33SH -99.9 to 999.9
606 0111101001 IC34SH -99.9 to 999.9
607 1111101001 IC35SH -99.9 to 999.9
608 0000011001 IC36SH -99.9 to 999.9
609 1000011001 IC37SH -99.9 to 999.9
610 0100011001 IC38SH -99.9 to 999.9
611 1100011001 IC39SH -99.9 to 999.9
612 0010011001 IC40SH -99.9 to 999.9
613 1010011001 IC41SH -99.9 to 999.9
614 0110011001 IC42SH -99.9 to 999.9
615 1110011001 IC43SH -99.9 to 999.9
616 0001011001 IC44SH -99.9 to 999.9
617 1001011001 IC45SH -99.9 to 999.9
618 0101011001 IC46SH -99.9 to 999.9
619 1101011001 IC47SH -99.9 to 999.9
620 0011011001 IC48SH -99.9 to 999.9
621 1011011001 IC49SH -99.9 to 999.9
622 0111011001 IC50SH -99.9 to 999.9
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
623 1111011001 IC1SC -99.9 to 999.9 B The unit is [ °C ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
624 0000111001 IC2SC -99.9 to 999.9
625 1000111001 IC3SC -99.9 to 999.9
626 0100111001 IC4SC -99.9 to 999.9
627 1100111001 IC5SC -99.9 to 999.9
628 0010111001 IC6SC -99.9 to 999.9
629 1010111001 IC7SC -99.9 to 999.9
630 0110111001 IC8SC -99.9 to 999.9
631 1110111001 IC9SC -99.9 to 999.9
632 0001111001 IC10SC -99.9 to 999.9
633 1001111001 IC11SC -99.9 to 999.9
634 0101111001 IC12SC -99.9 to 999.9
635 1101111001 IC13SC -99.9 to 999.9
636 0011111001 IC14SC -99.9 to 999.9
637 1011111001 IC15SC -99.9 to 999.9
638 0111111001 IC16SC -99.9 to 999.9
639 1111111001 IC17SC -99.9 to 999.9
640 0000000101 IC18SC -99.9 to 999.9
641 1000000101 IC19SC -99.9 to 999.9
642 0100000101 IC20SC -99.9 to 999.9
643 1100000101 IC21SC -99.9 to 999.9
644 0010000101 IC22SC -99.9 to 999.9
645 1010000101 IC23SC -99.9 to 999.9
646 0110000101 IC24SC -99.9 to 999.9
647 1110000101 IC25SC -99.9 to 999.9
648 0001000101 IC26SC -99.9 to 999.9
649 1001000101 IC27SC -99.9 to 999.9
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
650 0101000101 IC28SC -99.9 to 999.9 B The unit is [ °C ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
651 1101000101 IC29SC -99.9 to 999.9
652 0011000101 IC30SC -99.9 to 999.9
653 1011000101 IC31SC -99.9 to 999.9
654 0111000101 IC32SC -99.9 to 999.9
655 1111000101 IC33SC -99.9 to 999.9
656 0000100101 IC34SC -99.9 to 999.9
657 1000100101 IC35SC -99.9 to 999.9
658 0100100101 IC36SC -99.9 to 999.9
659 1100100101 IC37SC -99.9 to 999.9
660 0010100101 IC38SC -99.9 to 999.9
661 1010100101 IC39SC -99.9 to 999.9
662 0110100101 IC40SC -99.9 to 999.9
663 1110100101 IC41SC -99.9 to 999.9
664 0001100101 IC42SC -99.9 to 999.9
665 1001100101 IC43SC -99.9 to 999.9
666 0101100101 IC44SC -99.9 to 999.9
667 1101100101 IC45SC -99.9 to 999.9
668 0011100101 IC46SC -99.9 to 999.9
669 1011100101 IC47SC -99.9 to 999.9
670 0111100101 IC48SC -99.9 to 999.9
671 1111100101 IC49SC -99.9 to 999.9
672 0000010101 IC50SC -99.9 to 999.9
No. SW1

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
676 0010010101 INV board S/W version 0.00 to 99.99 A A
679 1110010101 Fan board S/W version 0.00 to 99.99 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
- 367 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
689 1000110101 Current time -2 00.00 to 99.12/1 to 31 Year and month, and date
691 1100110101 Time of error detection 1-2 00.00 to 99.12/1 to 31 Year and month, and date
693 1010110101 Time of error detection 2-2 00.00 to 99.12/1 to 31 Year and month, and date
695 1110110101 Time of error detection 3-2 00.00 to 99.12/1 to 31 Year and month, and date
697 1001110101 Time of error detection 4-2 00.00 to 99.12/1 to 31 Year and month, and date
699 1101110101 Time of error detection 5-2 00.00 to 99.12/1 to 31 Year and month, and date
701 1011110101 Time of error detection 6-2 00.00 to 99.12/1 to 31 Year and month, and date
688 0000110101 Current time 00:00 to 23:59 A A Hour: minute
690 0100110101 Time of error detection 1 00:00 to 23:59 Hour: minute
692 0010110101 Time of error detection 2 00:00 to 23:59 Hour: minute
694 0110110101 Time of error detection 3 00:00 to 23:59 Hour: minute
696 0001110101 Time of error detection 4 00:00 to 23:59 Hour: minute
698 0101110101 Time of error detection 5 00:00 to 23:59 Hour: minute
700 0011110101 Time of error detection 6 00:00 to 23:59 Hour: minute
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1
- 368 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
703 1111110101 Time of error detection 7-2 00.00 to 99.12/1 to 31 Year and month, and date
705 1000001101 Time of error detection 8-2 00.00 to 99.12/1 to 31 Year and month, and date
707 1100001101 Time of error detection 9-2 00.00 to 99.12/1 to 31 Year and month, and date
709 1010001101 Time of error detection 10-2 00.00 to 99.12/1 to 31 Year and month, and date
fore error -2 00.00 to 99.12/1 to 31 Year and month, and date
702 0111110101 Time of error detection 7 00:00 to 23:59 A A Hour: minute
704 0000001101 Time of error detection 8 00:00 to 23:59 Hour: minute
706 0100001101 Time of error detection 9 00:00 to 23:59 Hour: minute
708 0010001101 Time of error detection 10 00:00 to 23:59 Hour: minute
fore error 00:00 to 23:59 Hour: minute
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
710 0110001101 Time of last data backup be-
711 1110001101 Time of last data backup be-
No. SW1
- 369 - HWE0803A

[ X LED monitor display on the outdoor unit board ]
714 0101001101 IC1 LEV opening 0000 to 9999 B Fully open: 2000
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
715 1101001101 IC2 LEV opening 0000 to 9999
716 0011001101 IC3 LEV opening 0000 to 9999
717 1011001101 IC4 LEV opening 0000 to 9999
718 0111001101 IC5 LEV opening 0000 to 9999
719 1111001101 IC6 LEV opening 0000 to 9999
720 0000101101 IC7 LEV opening 0000 to 9999
721 1000101101 IC8 LEV opening 0000 to 9999
722 0100101101 IC9 LEV opening 0000 to 9999
723 1100101101 IC10 LEV opening 0000 to 9999
724 0010101101 IC11 LEV opening 0000 to 9999
725 1010101101 IC12 LEV opening 0000 to 9999
726 0110101101 IC13 LEV opening 0000 to 9999
727 1110101101 IC14 LEV opening 0000 to 9999
728 0001101101 IC15 LEV opening 0000 to 9999
729 1001101101 IC16 LEV opening 0000 to 9999
730 0101101101 IC17 LEV opening 0000 to 9999
731 1101101101 IC18 LEV opening 0000 to 9999
732 0011101101 IC19 LEV opening 0000 to 9999
733 1011101101 IC20 LEV opening 0000 to 9999
734 0111101101 IC21 LEV opening 0000 to 9999
735 1111101101 IC22 LEV opening 0000 to 9999
736 0000011101 IC23 LEV opening 0000 to 9999
737 1000011101 IC24 LEV opening 0000 to 9999
738 0100011101 IC25 LEV opening 0000 to 9999
739 1100011101 IC26 LEV opening 0000 to 9999
740 0010011101 IC27 LEV opening 0000 to 9999
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
B The four LDs on the left
mode, and the four LDs
on the right (LD5-LD8)
display port address.
741 1010011101 IC28 LEV opening 0000 to 9999 B Fully open: 2000
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
742 0110011101 IC29 LEV opening 0000 to 9999
743 1110011101 IC30 LEV opening 0000 to 9999
744 0001011101 IC31 LEV opening 0000 to 9999
745 1001011101 IC32 LEV opening 0000 to 9999
746 0101011101 IC33 LEV opening 0000 to 9999
747 1101011101 IC34 LEV opening 0000 to 9999
748 0011011101 IC35 LEV opening 0000 to 9999
749 1011011101 IC36 LEV opening 0000 to 9999
750 0111011101 IC37 LEV opening 0000 to 9999
751 1111011101 IC38 LEV opening 0000 to 9999
752 0000111101 IC39 LEV opening 0000 to 9999
753 1000111101 IC40 LEV opening 0000 to 9999
754 0100111101 IC41 LEV opening 0000 to 9999
755 1100111101 IC42 LEV opening 0000 to 9999
756 0010111101 IC43 LEV opening 0000 to 9999
757 1010111101 IC44 LEV opening 0000 to 9999
758 0110111101 IC45 LEV opening 0000 to 9999
759 1110111101 IC46 LEV opening 0000 to 9999
760 0001111101 IC47 LEV opening 0000 to 9999
761 1001111101 IC48 LEV opening 0000 to 9999
762 0101111101 IC49 LEV opening 0000 to 9999
763 1101111101 IC50 LEV opening 0000 to 9999
764 0011111101 IC1 Operation mode
765 1011111101 IC2 Operation mode
766 0111111101 IC3Operation mode
767 1111111101 IC4 Operation mode
768 0000000011 IC5 Operation mode
No. SW1

[ X LED monitor display on the outdoor unit board ]
B The four LDs on the left
tion mode, and the four
LDs on the right (LD5-
LD8) display port ad-
dress.
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
773 1010000011 IC10 Operation mode
774 0110000011 IC11 Operation mode
775 1110000011 IC12 Operation mode
776 0001000011 IC13 Operation mode
777 1001000011 IC14 Operation mode
778 0101000011 IC15 Operation mode
779 1101000011 IC16 Operation mode
780 0011000011 IC17 Operation mode
781 1011000011 IC18 Operation mode
782 0111000011 IC19 Operation mode
783 1111000011 IC20 Operation mode
784 0000100011 IC21 Operation mode
785 1000100011 IC22 Operation mode
786 0100100011 IC23 Operation mode
787 1100100011 IC24 Operation mode
788 0010100011 IC25 Operation mode
789 1010100011 IC26 Operation mode
790 0110100011 IC27 Operation mode
791 1110100011 IC28 Operation mode
792 0001100011 IC29 Operation mode
793 1001100011 IC30 Operation mode
794 0101100011 IC31 Operation mode
795 1101100011 IC32 Operation mode
796 0011100011 IC33 Operation mode
769 1000000011 IC6 Operation mode
770 0100000011 IC7 Operation mode
771 1100000011 IC8 Operation mode
772 0010000011 IC9 Operation mode
No. SW1

[ X LED monitor display on the outdoor unit board ]
B The four LDs on the left
tion mode, and the four
LDs on the right (LD5-
814 0111010011 IC1 filter 0000 to 9999 B Hours since last mainte-
LD8) display port ad-
nance [ h ]
dress.
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
815 1111010011 IC2 filter 0000 to 9999
816 0000110011 IC3 filter 0000 to 9999
817 1000110011 IC4 filter 0000 to 9999
818 0100110011 IC5 filter 0000 to 9999
819 1100110011 IC6 filter 0000 to 9999
820 0010110011 IC7 filter 0000 to 9999
821 1010110011 IC8 filter 0000 to 9999
822 0110110011 IC9 filter 0000 to 9999
823 1110110011 IC10 filter 0000 to 9999
824 0001110011 IC11 filter 0000 to 9999
797 1011100011 IC34 Operation mode
798 0111100011 IC35 Operation mode
799 1111100011 IC36 Operation mode
800 0000010011 IC37 Operation mode
801 1000010011 IC38 Operation mode
802 0100010011 IC39 Operation mode
803 1100010011 IC40 Operation mode
804 0010010011 IC41 Operation mode
805 1010010011 IC42 Operation mode
806 0110010011 IC43 Operation mode
807 1110010011 IC44 Operation mode
808 0001010011 IC45 Operation mode
809 1001010011 IC46 Operation mode
810 0101010011 IC47 Operation mode
811 1101010011 IC48 Operation mode
812 0011010011 IC49 Operation mode
813 1011010011 IC50 Operation mode
No. SW1

[ X LED monitor display on the outdoor unit board ]
825 1001110011 IC12 filter 0000 to 9999 B Hours since last mainte-
nance [ h ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
826 0101110011 IC13 filter 0000 to 9999
827 1101110011 IC14 filter 0000 to 9999
828 0011110011 IC15 filter 0000 to 9999
829 1011110011 IC16 filter 0000 to 9999
830 0111110011 IC17 filter 0000 to 9999
831 1111110011 IC18 filter 0000 to 9999
832 0000001011 IC19 filter 0000 to 9999
833 1000001011 IC20 filter 0000 to 9999
834 0100001011 IC21 filter 0000 to 9999
835 1100001011 IC22 filter 0000 to 9999
836 0010001011 IC23 filter 0000 to 9999
837 1010001011 IC24 filter 0000 to 9999
838 0110001011 IC25 filter 0000 to 9999
839 1110001011 IC26 filter 0000 to 9999
840 0001001011 IC27 filter 0000 to 9999
841 1001001011 IC28 filter 0000 to 9999
842 0101001011 IC29 filter 0000 to 9999
843 1101001011 IC30 filter 0000 to 9999
844 0011001011 IC31 filter 0000 to 9999
845 1011001011 IC32 filter 0000 to 9999
846 0111001001 IC33 filter 0000 to 9999
847 1111001011 IC34 filter 0000 to 9999
848 0000101011 IC35 filter 0000 to 9999
849 1000101011 IC36 filter 0000 to 9999
850 0100101011 IC37 filter 0000 to 9999
851 1100101011 IC38 filter 0000 to 9999
852 0010101011 IC39 filter 0000 to 9999
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
853 1010101011 IC40 filter 0000 to 9999 B Hours since last mainte-
nance [ h ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
854 0110101011 IC41 filter 0000 to 9999
855 1110101011 IC42 filter 0000 to 9999
856 0001101011 IC43 filter 0000 to 9999
857 1001101011 IC44 filter 0000 to 9999
858 0101101011 IC45 filter 0000 to 9999
859 1101101011 IC46 filter 0000 to 9999
860 0011101011 IC47 filter 0000 to 9999
861 1011101011 IC48 filter 0000 to 9999
862 0111101011 IC49 filter 0000 to 9999
863 1111101011 IC50 filter 0000 to 9999
No. SW1
Remarks · Item Display Unit

[ X LED monitor display on the outdoor unit board ]
gle 1 -99.9 to 999.9 A A The unit is [ deg ]
Reset counter 0 to 254 A A The unit is [ time ]
Reset counter 0 to 254 A A The unit is [ time ]
tive value 1 -99.9 to 999.9 A A The unit is [ A ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
tive value 1 -99.9 to 999.9 A A
Reset counter 0 to 254 A A
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
873 1001011011 Power factor phase an-
871 1110011011 U-phase current effec-
872 0001011011 W-phase current effec-
880 0000111011 Control board
881 1000111011 INV board
884 0010111011 Fan board
No. SW1

[ X LED monitor display on the outdoor unit board ]
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.
No. SW1


What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| TB3 | Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control | p.27 | |
| 0403 | Serial communication error | p.148 | |
| 4220, 4225 | Bus voltage drop | p.148 | |
| 4230 | Heatsink overheat protection | p.148 | |
| 4240 | Overload protection | p.148 | |
| 4250, 4255 | Overcurrent relay trip | p.148 | |
| 5110 | Heatsink temperature sensor failure (THHS) | p.148 | |
| 5301 | Current sensor/circuit failure | p.148 | |
| 5102 | Subcool heat exchanger bypass outlet temperature sensor failure | p.148 | |
| 5103 | Pipe temperature sensor failure | p.148 | |
| 5104 | Discharge temperature sensor failure | p.148 | |
| 5105 | Accumulator inlet temperature sensor failure | p.148 | |
| 5106 | Subcool heat exchanger liquid outlet sensor failure | p.148 | |
| 5107 | Outside air temperature sensor failure | p.148 | |
| 4102 | Open phase | p.148 | |
| 4115 | Power supply sync signal abnormality | p.148 | |
| 6607 | No acknowledgement error | p.149 | |
| 6608 | No response error | p.149 | |
| 6600 | Noise interference on the transmission line | p.279 |
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Water infiltration | p.23 | ||
| Hydrolysis | p.23 | ||
| Oxidization | Air infiltration | p.23 | |
| Adhesion to expansion valve and capillary tubes | Infiltration of contaminants | p.23 | |
| Infiltration of contaminants into the com- pressor | p.23 | ||
| Sludge formation and adhesion | p.23 | ||
| Oil degradation | p.23 | ||
| The indoor unit does not start after starting cooling (heating) operation. | The unit cannot perform a heating (cooling) operation when other indoor units are performing a cooling (heating) operation. | p.171 | |
| The auto vane adjusts its posi- tion by itself. | After an hour of cooling operation with the auto vane in the vertical posi- tion, the vane may automatically move into the horizontal position. Louver blades will automatically move into the horizontal position while the unit is in the defrost mode, pre-heating stand-by mode, or when the thermostat triggers unit off. | p.171 | |
| The fan stops during heating operation. | The fan remains stopped during defrost operation. | p.171 | |
| The fan keeps running after the unit has stopped. | When the auxiliary heater is turned on, the fan operates for one minute after stopping to dissipate heat. | p.171 | |
| The fan speed does not reach the set speed when operation switch is turned on. | The fan operates at extra low speed for 5 minutes after it is turned on or until the pipe temperature reaches 35°C[95°F], then it operates at low speed for 2 minutes, and finally it operates at the set speed. (Pre-heating stand-by) | p.171 | |
| When the main power is turned on, the display shown on the right appears on the in- door unit remote controller for 5 minutes. | The system is starting up. Wait until the blinking display of "HO" or "PLEASE WAIT" go off. | p.171 | |
| The drain pump keeps run- ning after the unit has stopped. | The drain pump stays in operation for three minutes after the unit in the cooling mode is stopped. | p.171 | |
| The drain pump is running while the unit is stopped. | When drain water is detected, the drain pump goes into operation even while the unit is stopped. | p.171 | |
| Indoor unit and BC controller make noise during cooling/ heating changeover. | This noise is made when the refrigerant circuit is reversed and is normal. | p.171 | |
| Sound of the refrigerant flow is heard from the indoor unit im- mediately after starting opera- tion. | This is caused by the transient instability of the refrigerant flow and is nor- mal. | p.171 | |
| Warm air sometimes comes out of the indoor units that are not in the heating mode. | This is due to the fact that the LEVs on some of the indoor units are kept slightly open to prevent the refrigerant in the indoor units that are not op- erating in the heating mode from liquefying and accumulating in the com- pressor. It is part of a normal operation. | p.171 | |
| Microcomputer driver circuit fail- ure | When the drive circuit has a problem, replace the control board. | p.290 | |
| LEV mechanism is locked | Replace the LEV. | p.290 | |
| Disconnected or short-circuited LEV motor coil | Replace the LEV coils. | p.290 | |
| Incomple sealing (leak from the valve) | If there is a large amount of leakage, replace the LEV. | p.290 | |
| Faulty wire con- nections in the connector or faulty contact | Check the continuity at the points where an error occurs. | p.290 |