387 pages·21.6 MB·Air Conditioner·PDF·ENDEFRITNLJA
Mitsubishi Electronics P96
Table of Contents 80 sections Safety Precautions · WARNING · CAUTION · i HWE0803A GB · … ShowHide
Safety Precautionsp.2WARNINGp.2CAUTIONp.2i HWE0803A GBp.2ii HWE0803A GBp.3Precautions for handling units for use with R410Ap.4iiiiii HWE0803A GBp.4Before installing the unitp.5iv HWE0803A GBp.5v HWE0803A GBp.6Before the test runp.7vi HWE0803A GBp.7I Read Before Servicingp.10I Read Before Servicing [1] Read Before Servicingp.12[2] Necessary Tools and Materialsp.134. Tools and materials that must not be used with R410Ap.13[3] Piping Materialsp.14Do not use the existing piping!p.141. Copper pipe materialsp.142. Types of copper pipesp.14R410A R22, R407Cp.15ø12.7 [1/2"] 26.0 24.0p.15ø15.88 [5/8"] 29.0 27.0p.15[4] Storage of Pipingp.161. Storage locationp.162. Sealing the pipe endsp.16[5] Pipe Processingp.16[6] Brazingp.17[7] Air Tightness Testp.18[8] Vacuum Drying (Evacuation)p.19[9] Refrigerant Chargingp.21[10] Remedies to be taken in case of a Refrigerant Leakp.21[11] Characteristics of the Conventional and the New Refrigerantsp.22R410A R407C R22p.22Ozone Depletion Coefficient (ODP) *1 0 0 0.055p.22[12] Notes on Refrigerating Machine Oilp.231. Refrigerating machine oil in the HFC refrigerant systemp.232. Effects of contaminants *1p.23II Restrictionsp.24II Restrictions [1] System configurationp.26[2] Types and Maximum allowable Length of Cablesp.27(2) Control wiringp.27[3] Switch Settings and Address Settingsp.282. M-NET Address settings (1) Address settings tablep.29BS1 BS2p.29GR SCp.29SR SCp.29AN SCp.29ST SCp.29TR SCp.29(2) Power supply switch connector connection on the outdoor unitp.30ONp.30(5) Various start-stop controls (Indoor unit settings)p.31OFF ONp.31ON OFFp.31CN3Sp.31(1) CN51 (2) CN3Sp.325 4 3 X Yp.32CN51p.32(3) CN3Np.32CN3N Xp.32OFFp.32(4) CN3Dp.32CN3Dp.32CN3D 1-2Pp.33[4] Sample System Connectionp.34GB HWE0803Ap.35(5) Address setting methodp.36(2) Cautionsp.41Shielded cable connectionp.42[8] Restrictions on Pipe Lengthp.52troller>p.52H H'p.52below.>p.54above.>p.56G Fp.56[PURY-P144, P168TSHMU-A] [PURY-P144, P168YSHMU-A]p.58[PURY-P192TSHMU-A] [PURY-P192YSHMU-A]p.58[PURY-P216, P240TSHMU-A] [PURY-P216, P240YSHMU-A]p.58P24, P27, P30p.59
Page 1 of the Mitsubishi Electronics P96 user manual
Page 1 · click to enlarge
Page 1
Mitsubishi Electronics P96 diagram (page 1)
Fig. 1
Mitsubishi Electronics P96 diagram (page 1)
Fig. 2
Mitsubishi Electronics P96 diagram (page 1)
Fig. 3
Page 2 of the Mitsubishi Electronics P96 user manual — i HWE0803A GB
Page 2 · click to enlarge
Page 2

Safety Precautions

ŒBefore installing the unit, thoroughly read the following safety precautions. ŒObserve these safety precautions for your safety.

WARNING

This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid

the risk of serious injury or death.

CAUTION

This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid

the risk of serious injury or damage to the unit.

ŒAfter reading this manual, give it to the user to retain for future reference. ŒKeep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these

services. When the user changes, make sure that the new user receives this manual.

WARNING

Ask your dealer or a qualified technician to install the unit.

In the event of a refrigerant leak, thoroughly ventilate the room.

Improper installation by the user may result in water leak- age, electric shock, smoke, and/or fire.

If refrigerant gas leaks and comes in contact with an open flame, poisonous gases will be produced.

Properly install the unit on a surface that can with- stand the weight of the unit.

When installing the All-Fresh type units, take it into consideration that the outside air may be discharged directly into the room when the thermo is turned off.

Unit installed on an unstable surface may fall and cause in- jury.

Direct exposure to outdoor air may have an adverse effect on health. It may also result in food spoilage.

Only use specified cables. Securely connect each ca- ble so that the terminals do not carry the weight of the cable.

Properly install the unit according to the instructions in the installation manual.

Improperly connected or fixed cables may produce heat and start a fire.

Improper installation may result in water leakage, electric shock, smoke, and/or fire.

Take appropriate safety measures against strong winds and earthquakes to prevent the unit from falling.

Have all electrical work performed by an authorized electrician according to the local regulations and in- structions in this manual, and a dedicated circuit must be used.

If the unit is not installed properly, the unit may fall and cause serious injury to the person or damage to the unit.

Insufficient capacity of the power supply circuit or improper installation may result in malfunctions of the unit, electric shock, smoke, and/or fire.

Do not make any modifications or alterations to the unit. Consult your dealer for repair.

Improper repair may result in water leakage, electric shock, smoke, and/or fire.

Do not touch the heat exchanger fins.

The fins are sharp and dangerous.

i HWE0803A GB

Page 3 of the Mitsubishi Electronics P96 user manual — ii HWE0803A GB
Page 3 · click to enlarge
Page 3

WARNING

Securely attach the terminal block cover (panel) to the unit.

After completing the service work, check for a gas leak.

If the terminal block cover (panel) is not installed properly, dust and/or water may infiltrate and pose a risk of electric shock, smoke, and/or fire.

If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, poisonous gases may be produced.

Only use the type of refrigerant that is indicated on the unit when installing or reinstalling the unit.

Do not try to defeat the safety features of the unit.

Forced operation of the pressure switch or the temperature switch by defeating the safety features of these devices, or the use of accessories other than the ones that are recom- mended by MITSUBISHI may result in smoke, fire, and/or explosion.

Infiltration of any other type of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.

When installing the unit in a small room, exercise cau- tion and take measures against leaked refrigerant reaching the limiting concentration.

Only use accessories recommended by MITSUBISHI.

Ask a qualified technician to install the unit. Improper instal- lation by the user may result in water leakage, electric shock, smoke, and/or fire.

Consult your dealer with any questions regarding limiting concentrations and for precautionary measures before in- stalling the unit. Leaked refrigerant gas exceeding the lim- iting concentration causes oxygen deficiency.

Control box houses high-voltage parts.

Consult your dealer or a specialist when moving or re- installing the unit.

When opening or closing the front panel of the control box, do not let it come into contact with any of the internal com- ponents. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)

Improper installation may result in water leakage, electric shock, and/or fire.

ii HWE0803A GB

Page 4 of the Mitsubishi Electronics P96 user manual — iiiiii HWE0803A GB
Page 4 · click to enlarge
Page 4

Precautions for handling units for use with R410A

CAUTION

Do not use the existing refrigerant piping.

Use a vacuum pump with a reverse-flow check valve.

ŒA large amount of chlorine that is contained in the residual

If a vacuum pump that is not equipped with a reverse-flow check valve is used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerating machine oil to deteriorate.

refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate. ŒR410A is a high-pressure refrigerant and can cause the

existing pipes to burst.

Prepare tools for exclusive use with R410A. Do not use the following tools if they have been used with the con- ventional refrigerant (gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.).

Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.

These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.

ŒIf the refrigerant or the refrigerating machine oil left on

these tools are mixed in with R410A, it may cause the re- frigerating machine oil to deteriorate. ŒInfiltration of water may cause the refrigerating machine

Store the pipes to be installed indoors, and keep both ends of the pipes sealed until immediately before braz- ing. (Keep elbows and other joints wrapped in plastic.)

oil to deteriorate. ŒGas leak detectors for conventional refrigerants will not

Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate or cause the unit to malfunction.

detect an R410A leak because R410A is free of chlorine.

Do not use a charging cylinder.

Use a small amount of ester oil, ether oil, or alkylben- zene to coat flares and flanges.

If a charging cylinder is used, the composition of the refrig- erant will change, and the unit may experience power loss.

Infiltration of a large amount of mineral oil may cause the re- frigerating machine oil to deteriorate.

Exercise special care when handling the tools for use with R410A.

Charge liquid refrigerant (as opposed to gaseous re- frigerant) into the system.

Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate.

If gaseous refrigerant is charged into the system, the com- position of the refrigerant in the cylinder will change and may result in performance loss.

Only use refrigerant R410A.

The use of other types of refrigerant that contain chlorine (i.e. R22) may cause the refrigerating machine oil to deteri- orate.

iiiiii HWE0803A GB

Page 5 of the Mitsubishi Electronics P96 user manual — iv HWE0803A GB
Page 5 · click to enlarge
Page 5

Before installing the unit

WARNING

Do not install the unit where a gas leak may occur.

When installing the unit in a hospital, take appropriate measures to reduce noise interference.

If gaseous refrigerant leaks and piles up around the unit, it may be ignited.

High-frequency medical equipment may interfere with the normal operation of the air conditioner or vice versa.

Do not use the unit to keep food items, animals, plants, artifacts, or for other special purposes.

Do not install the unit on or over things that cannot get wet.

The unit is not designed to preserve food products.

When the humidity level exceeds 80% or if the drainage system is clogged, the indoor unit may drip water. Drain wa- ter is also discharged from the outdoor unit. Install a central- ized drainage system if necessary.

Do not use the unit in an unusual environment.

ŒDo not install the unit where a large amount of oil or steam

is present or where acidic or alkaline solutions or chemical sprays are used frequently. Doing so may lead to a re- markable drop in performance, electric shock, malfunc- tions, smoke, and/or fire. ŒThe presence of organic solvents or corrosive gas (i.e.

ammonia, sulfur compounds, and acid) may cause gas leakage or water leakage.

iv HWE0803A GB

Page 6 of the Mitsubishi Electronics P96 user manual — v HWE0803A GB
Page 6 · click to enlarge
Page 6

Before installing the unit (moving and reinstalling the unit) and performing electrical work

CAUTION

Properly ground the unit.

Periodically check the installation base for damage.

Do not connect the grounding wire to a gas pipe, water pipe, lightning rod, or grounding wire from a telephone pole. Im- proper grounding may result in electric shock, smoke, fire, and/or malfunction due to noise interference.

If the unit is left on a damaged platform, it may fall and cause injury.

Properly install the drain pipes according to the in- structions in the installation manual. Keep them insu- lated to avoid dew condensation.

Do not put tension on the power supply wires.

If tension is put on the wires, they may break and result in excessive heat, smoke, and/or fire.

Improper plumbing work may result in water leakage and damage to the furnishings.

Install an earth leakage breaker to avoid the risk of electric shock.

Exercise caution when transporting products.

ŒProducts weighing more than 20 kg should not be carried

Failure to install an earth leakage breaker may result in electric shock, smoke, and/or fire.

alone. ŒDo not carry the product by the PP bands that are used on

some products. ŒDo not touch the heat exchanger fins. They are sharp and

Use the kind of power supply wires that are specified in the installation manual.

The use of wrong kind of power supply wires may result in current leak, electric shock, and/or fire.

to prevent the unit from falling.

Properly dispose of the packing materials.

Use breakers and fuses (current breaker, remote switch <switch + Type-B fuse>, moulded case circuit breaker) with the proper current capacity.

ŒNails and wood pieces in the package may pose a risk of

injury. ŒPlastic bags may pose a risk of choking hazard to chil-

The use of wrong capacity fuses, steel wires, or copper wires may result in malfunctions, smoke, and/or fire.

dren. Tear plastic bags into pieces before disposing of them.

Do not spray water on the air conditioner or immerse the air conditioner in water.

Otherwise, electric shock and/or fire may result.

When handling units, always wear protective gloves to protect your hands from metal parts and high-tempera- ture parts.

v HWE0803A GB

Page 7 of the Mitsubishi Electronics P96 user manual — vi HWE0803A GB
Page 7 · click to enlarge
Page 7

Before the test run

CAUTION

Turn on the unit at least 12 hours before the test run.

Do not operate the unit without panels and safety guards.

Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc- tions.

Rotating, high-temperature, or high-voltage parts on the unit pose a risk of burns and/or electric shock.

To avoid the risk of electric shock or malfunction of the unit, do not operate switches with wet hands.

Do not turn off the power immediately after stopping the operation.

Keep the unit on for at least five minutes before turning off the power to prevent water leakage or malfunction.

Do not touch the refrigerant pipes with bare hands dur- ing and immediately after operation.

During or immediately after operation, certain parts of the unit such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frost bites and burns, do not touch these parts with bare hands.

Do not operate the unit without the air filter.

Dust particles may build up in the system and cause mal- functions.

vi HWE0803A GB

Page 8 of the Mitsubishi Electronics P96 user manual — Before the test run
Page 8 · click to enlarge
Page 8
Page 8 of the Mitsubishi Electronics P96 user manual — Before the test run
Page 9 of the Mitsubishi Electronics P96 user manual — Before the test run
Page 9 · click to enlarge
Page 9
Page 9 of the Mitsubishi Electronics P96 user manual — Before the test run
Page 10 of the Mitsubishi Electronics P96 user manual — I Read Before Servicing
Page 10 · click to enlarge
Page 10

I Read Before Servicing

[1] Read Before Servicing 3 [2] Necessary Tools and Materials 4 [3] Piping Materials 5 [4] Storage of Piping 7 [5] Pipe Processing 7 [6] Brazing 8 [7] Air Tightness Test 9 [8] Vacuum Drying (Evacuation) 10 [9] Refrigerant Charging 12 [10] Remedies to be taken in case of a Refrigerant Leak 12 [11] Characteristics of the Conventional and the New Refrigerants 13 [12] Notes on Refrigerating Machine Oil 14

Page 11 of the Mitsubishi Electronics P96 user manual — I Read Before Servicing
Page 11 · click to enlarge
Page 11
Page 11 of the Mitsubishi Electronics P96 user manual — I Read Before Servicing
Page 12 of the Mitsubishi Electronics P96 user manual — I Read Before Servicing [1] Read Before Servicing
Page 12 · click to enlarge
Page 12

[ I Read Before Servicing ]

I Read Before Servicing [1] Read Before Servicing

1. Check the type of refrigerant used in the system to be serviced. Refrigerant Type Multi air conditioner for building application CITY MULTI R2 THMU-A, YHMU-A series R410A
2. Check the symptoms exhibited by the unit to be serviced. Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant. Refer to "Necessary Tools and Materials" for information on the use of tools.(page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced. Œ Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free

of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water. ŒThese types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.

6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas hydrofluoric acid may form. Keep workplace well ventilated.
Page 13 of the Mitsubishi Electronics P96 user manual — 4. Tools and materials that must not be used with R410A
Page 13 · click to enlarge
Page 13

[ I Read Before Servicing ]

[2] Necessary Tools and Materials

Prepare the following tools and materials necessary for installing and servicing the unit.

Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)

1. To be used exclusively with R410A (not to be used if used with R22 or R407C)

Gauge Manifold Evacuation and refrigerant charging Higher than 5.09MPa[738psi] on the high-pressure side

Charging Hose Evacuation and refrigerant charging The hose diameter is larger than the conventional model.

Refrigerant Recovery Cylinder Refrigerant recovery

Refrigerant Cylinder Refrigerant charging The refrigerant type is indicated. The cylinder is pink.

Charging Port on the Refrigerant Cylinder Refrigerant charging The charge port diameter is larger than that of the current port.

Flare Nut Connection of the unit with the pipes Use Type-2 Flare nuts.

2. Tools and materials that may be used with R410A with some restrictions

Gas Leak Detector Gas leak detection The ones for use with HFC refrigerant may be used.

Vacuum Pump Vacuum drying May be used if a check valve adapter is attached.

Flare Tool Flare processing Flare processing dimensions for the piping in the system using the new re- frigerant differ from those of R22. Re- fer to I [3] Piping Materials.

Refrigerant Recovery Equipment Refrigerant recovery May be used if compatible with R410A.

3. Tools and materials that are used with R22 or R407C that may also be used with R410A

Vacuum Pump with a Check Valve Vacuum drying

Torque Wrench Tightening flare nuts Only the flare processing dimensions for pipes that have a diameter of ø12.70 (1/2") and ø15.88 (5/8") have been changed.

Pipe Cutter Cutting pipes

Welder and Nitrogen Cylinder Welding pipes

Refrigerant Charging Meter Refrigerant charging

Vacuum Gauge Vacuum level check

4. Tools and materials that must not be used with R410A

Charging Cylinder Refrigerant charging Prohibited to use

Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.

Show 5 more labels / short text on this page
Tools/Materials Use Notes · Tools/Materials Use Notes · Tools/Materials Use Notes · Bender Bending pipes · Tools/Materials Use Notes
Page 14 of the Mitsubishi Electronics P96 user manual — 2. Types of copper pipes
Page 14 · click to enlarge
Page 14

[ I Read Before Servicing ]

[3] Piping Materials

Do not use the existing piping!

1. Copper pipe materials

O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands.

1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed) at the same radial thickness.

ŒThe distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-

selves.

2. Types of copper pipes

Maximum working pressure Refrigerant type

3.45 MPa [500psi] R22, R407C etc.

4.30 MPa [624psi] R410A etc.

3. Piping materials/Radial thickness Use refrigerant pipes made of phosphorus deoxidized copper. The operation pressure of the units that use R410A is higher than that of the units that use R22. Use pipes that have at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7 mm [28mil] or less may not be used.)

Pipe size (mm[in.]) Radial thickness (mm [mil]) Type

ø6.35 [1/4"] 0.8t [32t]

O-material (Annealed) ø9.52 [3/8"] 0.8t [32t]

ø12.7 [1/2"] 0.8t [32t]

ø15.88 [5/8"] 1.0t [40t]

ø19.05 [3/4"] 1.0t [40t]

ø22.2 [7/8"] 1.0t [40t]

ø25.4 [1"] 1.0t [40t]

ø28.58 [1-1/8"] 1.0t [40t]

ø31.75 [1-1/4"] 1.1t [44t]

ø34.93 [1-3/8"] 1.2t [48t]

ø41.28 [1-5/8"] 1.4t [56t]

ŒThe pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the

pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn) unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t. ŒThe figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes

that meet the local standards.

1/2H-material, H-material (Drawn)

Page 15 of the Mitsubishi Electronics P96 user manual — ø12.7 [1/2"] 26.0 24.0
Page 15 · click to enlarge
Page 15

[ I Read Before Servicing ]

4. Thickness and refrigerant type indicated on the piping materials Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only) The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.

Flare processing dimensions (mm[in.])

Pipe size (mm[in.])

R410A R22, R407C

ø6.35 [1/4"] 9.1 9.0

ø9.52 [3/8"] 13.2 13.0

ø12.7 [1/2"] 16.6 16.2

ø15.88 [5/8"] 19.7 19.4

ø19.05 [3/4"] 24.0 23.3

(ø19.05 pipes should have a radial thickness of 1.2 t and be made of annealed materials.) If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0 and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.

6. Flare nut The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.

Flare nut dimensions (mm[in.])

Pipe size (mm[in.])

R410A R22, R407C

ø6.35 [1/4"] 17.0 17.0

ø9.52 [3/8"] 22.0 22.0

ø12.7 [1/2"] 26.0 24.0

ø15.88 [5/8"] 29.0 27.0

ø19.05 [3/4"] 36.0 36.0

The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.

Show 4 more labels / short text on this page
A dimension (mm) · Dimension A · B dimension (mm) · Dimension B
Page 16 of the Mitsubishi Electronics P96 user manual — [5] Pipe Processing
Page 16 · click to enlarge
Page 16

[ I Read Before Servicing ]

[4] Storage of Piping

1. Storage location

Mitsubishi Electronics P96 — 1. Storage location diagram (page 16)
Fig. 4 · 1. Storage location
Mitsubishi Electronics P96 — 1. Storage location diagram (page 16)
Fig. 5 · 1. Storage location
Mitsubishi Electronics P96 — 1. Storage location diagram (page 16)
Fig. 6 · 1. Storage location
Mitsubishi Electronics P96 — 1. Storage location diagram (page 16)
Fig. 7 · 1. Storage location
Mitsubishi Electronics P96 — 1. Storage location diagram (page 16)
Fig. 8 · 1. Storage location

Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.

2. Sealing the pipe ends

Mitsubishi Electronics P96 — 2. Sealing the pipe ends diagram (page 16)
Fig. 9 · 2. Sealing the pipe ends
Mitsubishi Electronics P96 — 2. Sealing the pipe ends diagram (page 16)
Fig. 10 · 2. Sealing the pipe ends
Mitsubishi Electronics P96 — 2. Sealing the pipe ends diagram (page 16)
Fig. 11 · 2. Sealing the pipe ends
Mitsubishi Electronics P96 — 2. Sealing the pipe ends diagram (page 16)
Fig. 12 · 2. Sealing the pipe ends
Mitsubishi Electronics P96 — 2. Sealing the pipe ends diagram (page 16)
Fig. 13 · 2. Sealing the pipe ends

Both ends of the pipes should be sealed until just before brazing. Keep elbow pipes and T-joints in plastic bags.

The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to deteriorate and cause a compressor failure.

[5] Pipe Processing

Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.

ŒUse a minimum amount of oil. ŒUse only ester oil, ether oil, and alkylbenzene.

Page 17 of the Mitsubishi Electronics P96 user manual — [6] Brazing
Page 17 · click to enlarge
Page 17

[ I Read Before Servicing ]

[6] Brazing

No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system.

ExampleInside the brazed connection

Use of oxidized solder for brazing Use of non-oxidized solder for brazing

Mitsubishi Electronics P96 — [6] Brazing diagram (page 17)
Fig. 14 · [6] Brazing
Mitsubishi Electronics P96 — [6] Brazing diagram (page 17)
Fig. 15 · [6] Brazing
1. Items to be strictly observed Œ Do not conduct refrigerant piping work outdoors if raining. Œ Use non-oxidized solder. Œ Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and

copper coupling. ŒIf installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.

2. Reasons Œ The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if

water infiltrates into the system. ŒFlux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.

3. Notes Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to deteriorate.
Page 18 of the Mitsubishi Electronics P96 user manual — [7] Air Tightness Test
Page 18 · click to enlarge
Page 18

[ I Read Before Servicing ]

[7] Air Tightness Test

No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.

Halide torch R22 leakage detector

1. Items to be strictly observed Œ Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-

ness, taking temperature variations into account. ŒRefrigerant R410A must be charged in its liquid state (vs. gaseous state).

2. Reasons Œ Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.) Œ Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition

of the remaining refrigerant in the cylinder will change and become unsuitable for use.

3. Notes Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an HFC(R410A) leak.
Page 19 of the Mitsubishi Electronics P96 user manual — [8] Vacuum Drying (Evacuation)
Page 19 · click to enlarge
Page 19

[ I Read Before Servicing ]

[8] Vacuum Drying (Evacuation)

Mitsubishi Electronics P96 — [8] Vacuum Drying (Evacuation) diagram (page 19)
Fig. 16 · [8] Vacuum Drying (Evacuation)
Mitsubishi Electronics P96 — [8] Vacuum Drying (Evacuation) diagram (page 19)
Fig. 17 · [8] Vacuum Drying (Evacuation)

(Photo1) 15010H (Photo2) 14010

Recommended vacuum gaugeROBINAIR 14010 Thermistor Vacuum Gauge
1. Vacuum pump with a reverse-flow check valve (Photo1) To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum pump with a reverse-flow check valve. A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2) Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recommended vacuum gauge is shown in Photo2.) Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time Œ After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-

moves moisture in the pipes.) ŒVerify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than

1Torr(130Pa) is acceptable. ŒIf the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum

drying.

5. Procedures for stopping vacuum pump To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening the charge hose, and then stop the operation. The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying Œ When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-

etrated the system or that there is a leak. ŒIf water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to

0.5kgf/cm2G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac- uum below 5Torr(650Pa) is attained or until the pressure stops rising. ŒOnly use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)

Page 20 of the Mitsubishi Electronics P96 user manual — [8] Vacuum Drying (Evacuation)
Page 20 · click to enlarge
Page 20

[ I Read Before Servicing ]

7. Notes Œ To evacuate air from the entire system

Applying a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) is not enough to attain the desired vacuum pressure. Be sure to apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2). ŒTo evacuate air only from the outdoor units

Apply a vacuum through the check joints on the high and low pressure sides (CJ1, and 2). ŒTo evacuate air from the indoor units and extension pipes

Apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2).

Page 21 of the Mitsubishi Electronics P96 user manual — [10] Remedies to be taken in case of a Refrigerant Leak
Page 21 · click to enlarge
Page 21

[ I Read Before Servicing ]

[9] Refrigerant Charging

Cylinder with a siphon

Cylinder without a siphon

Mitsubishi Electronics P96 — [9] Refrigerant Charging diagram (page 21)
Fig. 18 · [9] Refrigerant Charging
Mitsubishi Electronics P96 — [9] Refrigerant Charging diagram (page 21)
Fig. 19 · [9] Refrigerant Charging

Cylinder color R410A is pink. Refrigerant charging in the liquid state

1. Reasons R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use.
2. Notes When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check the type of the cylinder on the label before use.

[10] Remedies to be taken in case of a Refrigerant Leak

If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the liquid state.) Refer to "IX [5] Refrigerant Leak".(page 314)

Show 5 more labels / short text on this page
Cylin- der · Cylin- der · Valve Valve · liquid · liquid
Page 22 of the Mitsubishi Electronics P96 user manual — R410A R407C R22
Page 22 · click to enlarge
Page 22

[ I Read Before Servicing ]

[11] Characteristics of the Conventional and the New Refrigerants

1. Chemical property As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant. However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia. If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a confined area.

New Refrigerant (HFC type) Conventional Refriger-

R410A R407C R22

Composition (wt%) (50/50) (23/25/52) (100)

Type of Refrigerant Pseudo-azeotropic

Chloride Not included Not included Included

Safety Class A1/A1 A1/A1 A1

Molecular Weight 72.6 86.2 86.5

Boiling Point (°C/°F) -51.4/-60.5 -43.6/-46.4 -40.8/-41.4

Steam Pressure (25°C,MPa/77°F,psi) (gauge)

1.557/226 0.9177/133 0.94/136

Saturated Steam Density (25°C,kg/m3/77°F,psi)

64.0 42.5 44.4

Flammability Nonflammable Nonflammable Nonflammable

Ozone Depletion Coefficient (ODP) *1 0 0 0.055

Global Warming Coefficient (GWP)*2 1730 1530 1700

Refrigerant Charging Method Refrigerant charging in

Replenishment of Refrigerant after a Refrigerant Leak

*1 When CFC11 is used as a reference *2 When CO2 is used as a reference

2. Refrigerant composition R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use. If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics The pressure in the system using R410A is 1.6 times as great as that in the system using R22.

R410A R407C R22

-20/-4 0.30/44 0.18/26 0.14/20

0/32 0.70/102 0.47/68 0.40/58

20/68 1.34/194 0.94/136 0.81/117

40/104 2.31/335 1.44/209 1.44/209

60/140 3.73/541 2.44/354 2.33/338

65/149 4.17/605 2.75/399 2.60/377

Show 15 more labels / short text on this page
ant (HCFC type) · R32/R125 R32/R125/R134a R22 · Non-azeotropic · Single Refrigerant · Refrigerant · Refrigerant · Refrigerant charging in · Refrigerant charging in · the liquid state · the liquid state · the gaseous state · Available Available Available · Pressure (gauge) · Temperature (°C/°F) · MPa/psi MPa/psi MPa/psi
Page 23 of the Mitsubishi Electronics P96 user manual — 2. Effects of contaminants *1
Page 23 · click to enlarge
Page 23

[ I Read Before Servicing ]

[12] Notes on Refrigerating Machine Oil

1. Refrigerating machine oil in the HFC refrigerant system

HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil.

Refrigerant Refrigerating machine oil

2. Effects of contaminants *1

Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out. The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.

3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.

Cause Symptoms Effects on the refrigerant cycle

Water infiltration Frozen expansion valve and capillary tubes

Clogged expansion valve and capillary tubes Poor cooling performance Compressor overheat Motor insulation failure Burnt motor Coppering of the orbiting scroll Lock Burn-in on the orbiting scroll

Sludge formation and ad- hesion Acid generation Oxidization Oil degradation Air infiltration Oxidization

Adhesion to expansion valve and capillary tubes

Clogged expansion valve, capillary tubes, and drier Poor cooling performance Compressor overheat

Infiltration of contaminants into the com- pressor

Burn-in on the orbiting scroll

Sludge formation and adhesion Clogged expansion valve and capillary tubes Poor cooling performance Compressor overheat

Mineral oil etc.

Oil degradation Burn-in on the orbiting scroll

*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.

Show 6 more labels / short text on this page
R22 Mineral oil · R407C Ester oil · R410A Ester oil · Hydrolysis · Dust, dirt · Infiltration of contaminants
Page 24 of the Mitsubishi Electronics P96 user manual — II Restrictions
Page 24 · click to enlarge
Page 24

II Restrictions

[1] System configuration 17 [2] Types and Maximum allowable Length of Cables 18 [3] Switch Settings and Address Settings 19 [4] Sample System Connection 25 [5] An Example of a System to which an MA Remote Controller is connected 26 [6] An Example of a System to which an M-NET Remote Controller is connected 38 [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected 40 [8] Restrictions on Pipe Length 43

Page 25 of the Mitsubishi Electronics P96 user manual — II Restrictions
Page 25 · click to enlarge
Page 25
Page 25 of the Mitsubishi Electronics P96 user manual — II Restrictions
Page 26 of the Mitsubishi Electronics P96 user manual — II Restrictions [1] System configuration
Page 26 · click to enlarge
Page 26

[ II Restrictions ]

II Restrictions [1] System configuration

1. Table of compatible indoor units The table below summarizes the types of indoor units that are compatible with different types of outdoor units.

Composing units Maximum total capacity

Maximum number of connectable in-

Types of connectable in-

72. - 36 - 108 18 P06 - P96 models R410A series indoor units 96 - - 48 - 144 24
120. - 60 - 180 30

144 72 72 72 - 216 36

168 96 72 84 - 252 42

192 96 96 96 - 288 48

216 120 96 108 - 324 50

240 120 120 120 - 360 50

1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names. 2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.

Show 6 more labels / short text on this page
Outdoor · units · of connectable indoor · door units · units · door units
Page 27 of the Mitsubishi Electronics P96 user manual — (2) Control wiring
Page 27 · click to enlarge
Page 27

[ II Restrictions ]

[2] Types and Maximum allowable Length of Cables

1. Wiring work (1) Notes 1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man- ual. 2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.) 3) Provide grounding for the outdoor unit as required. 4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing. 5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic compo- nents on the terminal block. 6) Use 2-core shielded cables as transmission cables. Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and malfunctions.

Mitsubishi Electronics P96 — [2] Types and Maximum allowable Length of Cables diagram (page 27)
Fig. 20 · [2] Types and Maximum allowable Length of Cables
TB3Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control

(2) Control wiring

Different types of control wiring are used for different systems. Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.

Types and maximum allowable length of cables Control lines are categorized into 2 types: transmission line and remote controller line. Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce noise interference.

1. M-NET transmission line
Mitsubishi Electronics P96 — (2) Control wiring diagram (page 27)
Fig. 21 · (2) Control wiring

Maximum transmission line distance between the outdoor unit and the far- thest indoor unit

Maximum transmission line distance for central- ized control and Indoor/ outdoor transmission line (Maximum line distance via outdoor unit)

500 m [1640ft] max. *The maximum overall line length from the power supply unit on the transmission lines for centralized control to each outdoor unit or to the system controller is 200m [656ft] max.

Page 28 of the Mitsubishi Electronics P96 user manual — [3] Switch Settings and Address Settings
Page 28 · click to enlarge
Page 28

[ II Restrictions ]

2. Remote controller wiring

MA remote controller*1 M-NET remote controller*2

Type VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT Shielded cable MVVS

Number of cores 2-core cable 2-core cable

0.3 to 1.25mm2 *3

0.3 to 1.25mm2 *3

[AWG22 to 16] (0.75 to 1.25mm2 ) *4

[AWG22 to 16] (0.75 to 1.25mm2 ) *4

Maximum overall line length 200 m [656ft] max. The section of the cable that exceeds 10m [32ft] must be included in the maximum in- door-outdoor transmission line distance.

*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wireless remote controller. *2 M-NET remote controller refers to ME remote controller and ME simple remote controller. *3 The use of cables that are smaller than 0.75mm2 [AWG18] is recommended for easy handling. *4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi- cations shown in the parenthesis.

[3] Switch Settings and Address Settings

1. Switch setting Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work. Set the switches while the power is turned off. If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not function properly.

Units on which to set the switches Symbol Units to which the power must be shut off

CITY MULTI indoor unit Main/sub unit IC Outdoor units *3 and Indoor units

LOSSNAY, OA processing unit *1 LC Outdoor units *3 and LOSSNAY

M-NET remote controller Main/sub remote controller

RC Outdoor units *3

MA remote controller Main/sub remote controller

CITY MULTI outdoor unit*2 OC,OS Outdoor units *3

BC controller Main BC Outdoor units *3 and BC controller

Sub1, 2 BS1, BS2 Outdoor units *3 and BC controller

*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line. *2. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). *3. Turn off the power to all the outdoor units in the same refrigerant circuit.

Show 5 more labels / short text on this page
Cable type · Cable size · [AWG18 to 16] · [AWG18 to 16] · MA Indoor units
Page 29 of the Mitsubishi Electronics P96 user manual — TR SC
Page 29 · click to enlarge
Page 29

[ II Restrictions ]

2. M-NET Address settings (1) Address settings table

The need for address settings and the range of address setting depend on the configuration of the system.

Unit or controller Sym- bol

Setting method Factory address

CITY MULTI indoor unit

Main/sub unit IC 0, 01 to 50*1 *4 *6 Assign the smallest address to the main indoor unit in the group, and assign sequential address numbers to the rest of the indoor units in the same group. In an R2 system with a sub BC controller, make the set- tings for the indoor units in the following order. (i) Indoor unit to be connected to the main BC controller (ii) Indoor unit to be connected to sub BC controller 1 (iii) Indoor unit to be connected to sub BC controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

LOSSNAY, OA processing unit LC 0, 01 to 50*1 *4 *6 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.

RC 101 to 150 Add 100 to the smallest address of all the indoor units in the same group.

RC 151 to 200*3 Add 150 to the smallest address of all the indoor units in the same group.

MA remote controller MA No address settings required. (The main/sub setting must be made if 2 remote controllers are connected to the system.) Main

CITY MULTI outdoor unit OC OS

0, 51 to 100*1 *2 *6

ŒAssign an address that equals the lowest address of the in-

door units in the same refrigerant circuit plus 50. ŒAssign sequential addresses to the outdoor units in the

same refrigerant circuit. The outdoor units in the same re- frigerant circuit are automatically designated as OC and OS. *5

BC 0, 51 to 100*1 *2 *6

ŒAssign an address that equals the address of the outdoor

unit in the same refrigerant system plus 1. ŒIf a given address overlaps any of the addresses that are

assigned to the outdoor units or to the sub BC controller, use a different, unused address within the setting range.

BC controller (sub1, 2)

BS1 BS2

51 to 100 *2 ŒAssign an address to both the sub BC controller 1 and 2

that equals the lowest address of the indoor units that are connected to each of them plus 50. ŒIf a sub BC controller is connected, the automatic startup

function is not available.

GR SC

201 to 250 Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.

SR SC

Assign an arbitrary but unique address within the range listed on the left to each unit.

AN SC

Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.

Schedule timer (com- patible with M-NET)

ST SC

Assign an arbitrary but unique address within the range listed on the left to each unit.

TR SC

0, 201 to 250 Assign an arbitrary but unique address within the range listed on the left to each unit. The address must be set to "0" to control the K-control unit.

LM adapter SC 201 to 250 Assign an arbitrary but unique address within the range listed on the left to each unit.

*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting range. *2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50." *3. To set the M-NET remote controller address to "200," set the rotary switches to "00." *4. Some models of indoor units have two or three control boards. Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2. *5. The outdoor units in the same refrigerant circuit are automatically designated as OC, and OS. They are designated as OC, and OS in the descending order of capacity (ascending order of address if the capacities are the same). *6. No address settings are required for units in a system with a single outdoor unit (with some exceptions). Address setting is required if a sub BC controller is connected.

Show 15 more labels / short text on this page
Address setting range · setting · M-NET adapter · M-NET con- trol interface · Free Plan adapter · M-NET re- mote con- troller · Main remote controller · Sub remote controller · Auxiliary outdoor unit · BC controller (main) · System controller · Group remote con- troller · System remote con- troller · ON/OFF remote con- troller · Central controller G(B)-50A
Page 30 of the Mitsubishi Electronics P96 user manual — ON
Page 30 · click to enlarge
Page 30

[ II Restrictions ]

(2) Power supply switch connector connection on the outdoor unit

(Factory setting: The male power supply switch connector is connected to CN41.) There are limitations on the total number of units that are connectable to each refrigerant system. Refer to the System Design Manual for details.

Connection to the system con- troller

Power supply unit for transmission lines

Group operation of units in a sys- tem with multiple outdoor units

Power supply switch connector connection

System with one outdoor unit

_ _ _ Leave CN41 as it is (Factory setting)

System with multi- ple outdoor units

Not connected _ Not grouped

Grouped Disconnect the male connector from the fe- male power supply switch connector (CN41) and connect it to the female power supply switch connector (CN40) on only one of the outdoor units.*2

With connection to the indoor unit system

Not required Grouped/not grouped

With connection to the central- ized control sys- tem

*Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor unit whose CN41 was replaced with CN40 to the ground terminal ( ) on the electric box.

(Powered from the outdoor unit)

Required *1 Grouped/not grouped

Leave CN41 as it is (Factory setting)

*1 The need for a power supply unit for transmission lines depends on the system configuration. *2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the system. (3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)

System configuration Centralized control switch settings *1

Connection to the system controller Not connected Leave it to OFF. (Factory setting)

Connection to the system controller Connected*2

ON

*1. Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting.

*2. When only the LM adapter is connected, leave SW2-1 to OFF (as it is).

(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)

To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor on the remote controller or an optional thermistor. 1) To use the built-in sensor on the remote controller, set the SW1-1 to ON. ŒSome models of remote controllers are not equipped with a built-in temperature sensor.

Use the built-in temperature sensor on the indoor unit instead. ŒWhen using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.

(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON. 2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON. ŒWhen using an optional temperature sensor, install it where room temperature can be detected.

System configura- tion · Not required*1 · Grouped/not grouped

Page 31 of the Mitsubishi Electronics P96 user manual — CN3S
Page 31 · click to enlarge
Page 31

[ II Restrictions ]

(5) Various start-stop controls (Indoor unit settings)

Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.

Setting (SW1)*4 *5

Function Operation of the indoor unit when the operation is resumed after the unit

Power ON/OFF by the plug*1,*2,*3 Indoor unit will go into operation regardless of its operation status before power off (power failure). (In approx. 5 minutes)

OFF ON

Automatic restoration after power failure

Indoor unit will go into operation if it was in operation when the power was turned off (or cut off due to power failure). (In approx. 5 minutes)

ON OFF

Indoor unit will remain stopped regardless of its operation status before power off (power failure).

OFF ON

*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the crankcase heater and may cause the compressor to malfunction when the unit is put back into operation. *2. Not applicable to units with a built-in drain pump or humidifier. *3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir- cuits will be turned on or off by the plug. *4. Requires that the dipswitch settings for all the units in the group be made. *5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To use the auto recovery function after power failure while these settings are made, set SW1-5 to ON. (6) Miscellaneous settings

Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.") When using indoor unit as a cooling-only unit, set SW3-1 to ON. (7) Various types of control using input-output signal connector on the outdoor unit (various connection options)

to be used*1

DEMAND (level) CN3D*2

Input Prohibiting cooling/heating operation (thermo OFF) by an external input to the outdoor unit.

Adapter for external input (PAC- SC36NA-E) Performs a low level noise operation of the outdoor unit by an ex- ternal input to the outdoor unit. * It can be used as the silent operation device for each refrigerant system.

Low-noise mode (level)*3 *4

Forces the outdoor unit to perform a fan operation by receiving sig- nals from the snow sensor. *5 Snow sensor signal input (level)

CN3S

Cooling/heating operation can be changed by an external input to the outdoor unit.

How to extract signals from the outdoor unit

Operation status of the compressor *5 CN51 Adapter for external out- put (PAC- SC37SA-E) Error status*6

*It can be used as an operation status display device. *It can be used for an interlock operation with external devices.

*1. For detailed drawing, refer to "Example of wiring connection".

*2. For details, refer to 1) through 4) shown below.

*3. Low-noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2 or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible.

*4. By setting Dip SW5-5, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri- ority mode. When SW5-5 is set to ON: The low-noise mode always remains effective. When SW5-5 is set to OFF: The low noise mode is cancelled when certain outside temperature or pressure criteria are met, and the unit goes into normal operation (capacity priority mode).

Low-noise mod is effective. Capacity priority mode becomes effective.

Cooling Heating Cooling Heating

TH74.6kg/cm2 TH7>35°C[95°F] or 63HS1>35kg/cm2 TH7

*5. Each outdoor unit in the system with multiple outdoor units requires the signal input/output setting to be made. *6. Take out signals from the outdoor unit (OC) if multiple outdoor units exist in a single system.

Show 7 more labels / short text on this page
was stopped · Terminal · Type Usage Function · Option · Auto-changeover CN3N · Out- · put
Page 32 of the Mitsubishi Electronics P96 user manual — CN3D
Page 32 · click to enlarge
Page 32

[ II Restrictions ]

(1) CN51 (2) CN3S

Adapter 2 Outdoor unit control board

Distant control board Relay circuit Adapter 1 Outdoor unit control board

CN3S

e cru o s re w o p p m a L

Y

5 4 3 X Y

CN51

Maximum cable length is 10m

in the field Maximum cable length is 10m

XRelay

Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC

L1 : Outdoor unit error display lamp L2 : Compressor operation lamp (compressor running state) X, Y : Relay (coil =

Snow sensorThe outdoor fan runs when X is closed
1. Optional part : PAC-SC37SA-E or field supply. 2. Optional part : PAC-SC36NA-E or field supply.

in stop mode or thermostat mode.

(3) CN3N

Relay circuit Adapter 2 Outdoor unit control board

CN3N X

OFF

ON

Y

ON

XCooling / Heating Y : Validity / Invalidity of X X,Y : Relay

Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC

Maximum cable length is 10m

2. Optional part : PAC-SC36NA-E or field supply.

(4) CN3D

Adapter 2 Outdoor unit control board

Adapter 2 Outdoor unit control board

CN3D

CN3D

Y

Maximum cable length is 10m

Maximum cable length is 10m

XLow-noise mode
XLow-noise mode
XRelay

Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC

YCompressor ON/OFF X,Y : Relay Contact rating voltage >= DC15V

Contact rating current >= 0.1A Minimum appicable load =< 1mA at DC

2. Optional part : PAC-SC36NA-E or field supply.
Low-noise modeThe noise level is reduced by controlling the maximum
2. Optional part : PAC-SC36NA-E or field supply.

fan frequency and maximum compressor frequency.

Show 15 more labels / short text on this page
Relay circuit · Preparations · in the field · Preparations · Normal Y OFF · Cooling · Heating · Preparations · in the field · Relay circuit · Relay circuit · Preparations · Preparations · in the field · in the field
Page 33 of the Mitsubishi Electronics P96 user manual — CN3D 1-2P
Page 33 · click to enlarge
Page 33

[ II Restrictions ]

1. SW4-4: OFF (Compressor ON/OFF, Low-noise mode)

CN3D 1-3P Compressor ON/OFF *1

CN3D 1-2P Low-noise mode*2

*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON , this function cannot be used. *2. This function can be enabled when the 4-step demand control is enabled. Input the order to CN3D 1-2P on the outdoor unit whose SW4-4 is set to OFF.

2. When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND) (*3)

CN3D 1-2P

CN3D 1-3P Open Short-circuit

Open 100% (No DEMAND) 75%

Short-circuit 0% (Compressor OFF) 50%

*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.

(Example) When switching from 100% to 50%

If the step listed as the wrong example above is taken, thermo may go off. The percentage of the demand listed in the table above is an approximate value based on the compressor volume and does not necessarily correspond with the capacity. When this function is enabled, the night mode cannot be enabled.

3. When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND) (*3, *4)

8 levels of on-DEMAND No.2 CN3D

No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit

Open Open 100% 50% 88% 75%

Short-circuit 50% 0% 38% 25%

Short-circuit Open 88% 38% 75% 63%

Short-circuit 75% 25% 63% 50%

*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON. *4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.

Show 15 more labels / short text on this page
Open Compressor ON · Short-circuit Compressor OFF · Open OFF · Short-circuit ON · Demand control · (Wrong) · 100% · 0% · 50% · steps · (Correct) · 100% · 75% · 50% · 1-2P Open Short-circuit
Page 34 of the Mitsubishi Electronics P96 user manual — [4] Sample System Connection
Page 34 · click to enlarge
Page 34

[ II Restrictions ]

[4] Sample System Connection

Examples of typical system connection are shown on pages [5] to [7]. Refer to the Installation Manual that came with each device or controller for details.

(1) An example of a system to which an MA remote controller is connected

System configuration Connection to the system controller Address start up for in- door and outdoor units Notes

1 System with one out-

door unit NO Automatic address setup

Connection of multiple LOSS- NAY units

2 System with one out-

door unit NO Manual address setup

3 Grouping of units in a

NO Manual address setup

4 System with one out-

With connection to transmission line

5 System with one out-

With connection to indoor-outdoor

Connection of multiple LOSS- NAY units

6 System with one out-

With connection to transmission line

(2) An example of a system to which an M-NET remote controller is connected

System configuration Connection to the system controller Address start up for indoor

and outdoor units Notes

1 System with one out-

With connection to transmission line

(3) An example of a system to which both MA remote controller and M-NET remote controller are connected

System configuration Connection to the system controller Address start up for in- door and outdoor units Notes

1 System with one out-

With connection to transmission

line for centralized control

Show 16 more labels / short text on this page
system with multiple · outdoor units · Manual address setup · door unit · for centralized control · Manual address setup · door unit · transmission line · Manual address setup · door unit · for centralized control · Manual address setup · door unit · for centralized control · Manual address setup · door unit
Page 35 of the Mitsubishi Electronics P96 user manual — GB HWE0803A
Page 35 · click to enlarge
Page 35

[ II Restrictions ]

[5] An Example of a System to which an MA Remote Controller is connected

1. System with one outdoor unit (automatic address setup for both indoor and outdoor units) (1) Sample control wiring
Mitsubishi Electronics P96 — GB HWE0803A diagram (page 35)
Fig. 22

Leave the male connector on CN41 as it is. SW2-1 OFF

Leave the male connector on CN41 as it is. SW2-1 OFF

TB7 M1 M2 M1 M2 M1 M2 S TB3 TB02 M1 M2 S

*1. When BS is connected to the system, automatic address setup is not available.

(2) Cautions 1) M-NET remote controller and MA remote controller can- not both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

4. Automatic address setup is not available if start-stop input(CN32, CN51, CN41) is used for a group operation of indoor units. Refer to "[5] 2. Manual address setup for both indoor and outdoor units" 5) To connect more than 2 LOSSNAY units to indoor units in the same system, refer to the next section "[5] 2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected".

(3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L1 +L2+L3+L4+L5 200m[656ft] L1 +L2+L3+L11+L12+L13 200m[656ft] 2) Transmission line for centralized control No connection is required. 3) MA remote controller wiring Maximum overall line length (0.3 to 1.25mm2 [AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft] m4+m5 200m [656ft]

Mitsubishi Electronics P96 — GB HWE0803A diagram (page 35)
Fig. 23

When the P72 and P96 models are not included in the connect- ed indoor units

When the P72 and P96 models are included in the connected indoor units

ŒThe table above shows the number of transmission

boosters that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.

GB HWE0803A

Page 36 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 36 · click to enlarge
Page 36

[ II Restrictions ]

(4) Wiring method 1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block for indoor-outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-out- door transmission line (TB02) on the main BC controller (BC), and of the terminal block for indoor-outdoor trans- mission line (TB5) on each indoor unit (IC). (Non-polar- ized two-wire) ŒOnly use shielded cables.

ŒSet one of the MA remote controllers as a sub controller.

(Refer to the Instruction Manual for the MA remote con- troller for the setting method.) Group operation of indoor units To perform a group operation of indoor units (IC), daisy- chain terminals 1 and 2 on the terminal block (TB15) on all indoor units (IC) in the same group, and then connect terminals 1 and 2 on the terminal block (TB15) on the in- door unit on one end to the terminal block on the MA re- motecontroller. (Non-polarized two-wire) ŒWhen performing a group operation of indoor units that

have different functions, "Automatic indoor/outdoor ad- dresssetup" is not available. 4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block(TB5) on the indoor unit (IC) to the appropriate ter- minals on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire) ŒInterlock operation setting with all the indoor units in the

The outdoor units in the same refrigerant circuit are au- tomatically designated as OC and OS in the order of ca- pacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC controller (BC), and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable. 2) Transmission line for centralized control No connection is required. 3) MA remote controller wiring Connect terminals 1 and 2 on the terminal block for MA remote controller line (TB15) on the indoor unit (IC) to the terminal block on the MA remote controller (MA). (Non-polarized two-wire) When 2 remote controllers are connected to the sys- tem When 2 remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15) on the indoor unit (IC) to the terminal block on the two MA remote controllers.

same system will automatically be made. (It is required that the Lossnay unit be turned on before the outdoo- runit.) ŒWhen performing an interlocked operation of part of the

indoor units in the system with a LOSSNAY unit, using a LOSSNAY unit alone without interlocking it with any units, performing an interlock operation of more than 16 indoor units with a LOSSNAY unit, or connecting two or more LOSSNAY units to the same refrigerant system, the automatic IC/OC address setup function is not avail- able. 5) Switch setting No address settings required.

(5) Address setting method

dures Unit or controller Address set-

ting range Setting method Notes Factory

1 Indoor unit Main unit IC No settings required.

- Port number setting is re- quired To perform a group opera- tion of indoor units that fea- ture different functions, the automatic IC/OC address setup function is not avail- able.

2 LOSSNAY LC No settings required.

3 MA remote con- troller

MA No settings required.

MA Sub remote con- troller

Settings to be made with the Sub/Main switch

4 Outdoor unit OC OS

No settings required.

5 Auxiliary outdoor unit

BC No settings required.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 7 more labels / short text on this page
Proce- · setting · Sub unit IC · Main remote con- troller · - Main · Sub remote con- troller · BC controller
Page 37 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 37 · click to enlarge
Page 37

[ II Restrictions ]

2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and outdoor units) (1) Sample control wiring
Mitsubishi Electronics P96 — (5) Address setting method diagram (page 37)
Fig. 24 · (5) Address setting method

Leave the male connector on CN41 as it is. SW2-1 OFF

Leave the male connector on CN41 as it is. SW2-1 OFF

TB7 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2

* If the BC address overlaps any of the addresses that are assigned to either the OC, OS, or BS, use a different, unused address. OC, OS, and BS addresses (lowest indoor unit address in the group plus +50) have higher priority than the BS address.

(2) Cautions 1) M-NET remote controller and MA remote controller can- not both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

ŒThe table above shows the number of transmission

boosters that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected. (3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 1. 2) Transmission line for centralized control No connection is required. 3) MA remote controller wiring Same as [5] 1.

Mitsubishi Electronics P96 — (5) Address setting method diagram (page 37)
Fig. 25 · (5) Address setting method

When the P72 and P96 models are not in- cluded in the connected indoor units

When the P72 and P96 models are includ- ed in the connected indoor units

Page 38 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 38 · click to enlarge
Page 38

[ II Restrictions ]

2. Transmission line for centralized control No connection is required.

(4) Wiring method 1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block for indoor-outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-out- door transmission line (TB02) on the main and sub BC controllers (BC and BS), and of the terminal block for in- door-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire) ŒOnly use shielded cables.

3. MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the system Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block (TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire) Œ Interlock setting between the indoor units and LOSS-

The outdoor units in the same refrigerant circuit are au- tomatically designated as OC and OS in the order of ca- pacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on BC and BS, and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.

NAY units must be entered on the remote controller. (Re- fer to "IV [3] Interlock Settings via the MA Remote Controller" or the installation manual for the MA remote controller for the setting method.) 5) Switch setting Address setting is required as follows.

(5) Address setting method

dures Unit or controller

Main unit IC 01 to 50 ŒAssign the smallest address to the main

ŒPort number setting is

unit in the group. ŒIn a system with a sub BC controller,

required ŒTo perform a group op-

make the settings for the indoor units in the following order. (i) Indoor unit to be connected to the main

eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.

BC controller (ii) Indoor unit to be connected to sub BC

controller 1 (iii) Indoor unit to be connected to sub BC

controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an ad- dress to all indoor units.

None of these addresses may overlap any of the indoor unit addresses.

3 MA remote controller

MA No set- tings re- quired.

MA Sub remote controller

Settings to be made with the Sub/ Main switch

4 Outdoor unit OC OS

51 to 100 ŒAssign sequential address to the outdoor

ŒTo set the address to 100,

units in the same refrigerant circuit. ŒThe outdoor units are automatically des-

set the rotary switches to 50. ŒIf the addresses that is as-

ignated as OC and OS.(Note)

signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. ŒThe use of a sub BC control-

5 Auxiliary outdoor unit

BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

BC control- ler (Main) BC OC (or OS if it exists) +1

ler requires the connection of a main BC controller.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 11 more labels / short text on this page
Fac- · Address · Proce- · setting · Setting method Notes · tory set- ting · range · 1 Indoor unit · Main remote controller · - Main · Sub remote controller
Page 39 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 39 · click to enlarge
Page 39

[ II Restrictions ]

3. Group operation of units in a system with multiple outdoor units (1) Sample control wiring
Mitsubishi Electronics P96 — (5) Address setting method diagram (page 39)
Fig. 26 · (5) Address setting method

CN41 CN40 Replace SW2-1 OFF Leave the male connector on CN41 as it is. SW2-1 OFF

M1 M2 M1 M2 M1 M2 M1 M2 M1 M2

Leave the male connector on CN41 as it is. SW2-1 OFF

Leave the male connector on CN41 as it is. SW2-1 OFF

M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2

(2) Cautions 1) M-NET remote controller and MA remote controller can- not both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units. 5) Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

ŒThe left table shows the number of transmission boost-

ers that is required by the system with three BC control- lers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.

(3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L12+L31+L22 500m [1640ft] L11+L31+L21 500m [1640ft] 3) MA remote controller wiring Same as [5] 1.

Mitsubishi Electronics P96 — (5) Address setting method diagram (page 39)
Fig. 27 · (5) Address setting method

When the P72 and P96 mod- els are not included in the connected indoor units

When the P72 and P96 mod- els are included in the con- nected indoor units

Page 40 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 40 · click to enlarge
Page 40

[ II Restrictions ]

(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 2. Shielded cable connection Same as [5] 2. 2) Transmission line for centralized control Daisy-chain terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC and OS in the same refrigerant circuit If a power supply unit is not connected to the transmis- sion line for centralized control, replace the power jump- er connector on the control board from CN41 to CN40 on only one of the outdoor units.

Shielded cable connection Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the sys- tem Same as [5] 1. Group operation of indoor units Same as [5] 2. 4) LOSSNAY connection Same as [5] 2. 5) Switch setting Address setting is required as follows.

The outdoor units in the same refrigerant circuit are au- tomatically designated as OC and OS in the order of ca- pacity from large to small (if two or more units have the same capacity, in the order of address from small to large). ŒOnly use shielded cables.

(5) Address setting method

dures Unit or controller

Main unit IC 01 to 50 ŒAssign the smallest address to the main

ŒPort number setting is

unit in the group. ŒIn a system with a sub BC controller,

required ŒTo perform a group op-

make the settings for the indoor units in the following order. (i) Indoor unit to be connected to the main

eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.

BC controller (ii) Indoor unit to be connected to sub BC

controller 1 (iii) Indoor unit to be connected to sub BC

controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an ad- dress to all indoor units.

None of these addresses may overlap any of the indoor unit addresses.

3 MA remote controller

MA No set- tings re- quired.

MA Sub remote controller

Settings to be made with the Sub/ Main switch

4 Outdoor unit OC OS

51 to 100 ŒAssign sequential address to the outdoor

ŒTo set the address to 100,

units in the same refrigerant circuit. ŒThe outdoor units are automatically des-

set the rotary switches to 50. ŒIf the addresses that is as-

ignated as OC and OS.(Note)

signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. ŒThe use of a sub BC control-

5 Auxiliary outdoor unit

BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

BC control- ler (Main) BC OC (or OS if it exists) +1

ler requires the connection of a main BC controller.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 11 more labels / short text on this page
Address · Fac- · Proce- · tory set- ting · setting · Setting method Notes · range · 1 Indoor unit · Main remote controller · - Main · Sub remote controller
Page 41 of the Mitsubishi Electronics P96 user manual — (2) Cautions
Page 41 · click to enlarge
Page 41

[ II Restrictions ]

4. A system in which a system controller is connected to the transmission line for centralized control and which is powered from an outdoor unit (1) Sample control wiring
Mitsubishi Electronics P96 — (2) Cautions diagram (page 41)
Fig. 28 · (2) Cautions

CN41 CN40 Replace SW2-1 OFF Leave the male connector on CN41 as it is. SW2-1 OFF

Leave the male connector on CN41 as it is. SW2-1 OFF

Leave the male connector on CN41 as it is. SW2-1 OFF

(2) Cautions

ŒThe left table shows the number of transmission boosters

1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be per- formed only on one of the outdoor units. 5) Short-circuit the shield terminal (S terminal) and the earth terminal ( ) on the terminal block for transmission line for centralized control (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-men- tioned system, two additional indoor units can be connected. 7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec- tor on CN41 as it is (factory setting).

(3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 3. 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft] 3) MA remote controller wiring Same as [5] 1.

Mitsubishi Electronics P96 — (2) Cautions diagram (page 41)
Fig. 29 · (2) Cautions

When the P72 and P96 models are not included in the connected in- door units

When the P72 and P96 models are included in the connected indoor units

Page 42 of the Mitsubishi Electronics P96 user manual — Shielded cable connection
Page 42 · click to enlarge
Page 42

[ II Restrictions ]

Daisy-chain the S terminal of the terminal block (TB7) on the system controller, OC, and OS with the shield of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the sys- tem Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block (TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-polarized two-wire) ŒIndoor units must be interlocked with the LOSSNAY unit

(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 2. Only use shielded cables. Shielded cable connection Same as [5] 2. 2) Transmission line for centralized control Daisy-chain terminals A and B on the system controller, ter- minals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in dif- ferent refrigerant circuits and on the outdoor units (OC and OS) in the same refrigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper con- nector on the control board from CN41 to CN40 on only one of the outdoor units. If a system controller is connected, set the central control switch (SW2-1) on the control board of all outdoor units to "ON."

using the system controller. (Refer to the operation man- ual for the system controller for the setting method.) In- terlock setting from the remote controller is required if the ON/OFF remote controller alone or the LM adapter alone is connected. 5) Switch setting Address setting is required as follows.

The outdoor units in the same refrigerant circuit are au- tomatically designated as OC, OS1, and OS2 in the or- der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). ŒOnly use shielded cables.

Shielded cable connection

(5) Address setting method

dures Unit or controller

Main unit IC 01 to 50 ŒAssign the smallest address to the main unit

ŒPort number setting is

in the group. ŒIn a system with a sub BC controller, make

required ŒTo perform a group op-

the settings for the indoor units in the fol- lowing order. (i) Indoor unit to be connected to the main BC

eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.

controller (ii) Indoor unit to be connected to sub BC

controller 1 (iii) Indoor unit to be connected to sub BC

controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.

None of these addresses may overlap any of the indoor unit addresses.

3 MA remote controller

MA No set- tings re- quired.

- Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.

MA Sub remote controller

Settings to be made with the Sub/ Main switch

4 Outdoor unit (Note) OC OS

51 to 100 ŒAssign sequential address to the outdoor

ŒTo set the address to 100,

units in the same refrigerant circuit. ŒThe outdoor units are automatically desig-

set the rotary switches to 50. ŒIf the addresses that is as-

nated as OC and OS.(Note)

signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. ŒThe use of a sub BC control-

5 Auxiliary outdoor unit

BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

BC control- ler (Main) BC OC (or OS if it exists) +1

ler requires the connection of a main BC controller.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 10 more labels / short text on this page
Ad- dress setting · Fac- · Proce- · tory set- ting · Setting method Notes · range · 1 Indoor unit · Main remote con- troller · Main · Sub remote con- troller
Page 43 of the Mitsubishi Electronics P96 user manual — GB HWE0803A
Page 43 · click to enlarge
Page 43

[ II Restrictions ]

5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter) (1) Sample control wiring
Mitsubishi Electronics P96 — Shielded cable connection diagram (page 43)
Fig. 30 · Shielded cable connection

Leave the male connector on CN41 as it is.

M2 M1 M2 M1 M2 M1 M2 M1 M2 M1

Leave the male connector on CN41 as it is.

Leave the male connector on CN41 as it is.

M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1

(2) Cautions

1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be per- formed only on one of the outdoor units. 5) Provide grounding to S terminal on the terminal block for transmis- sion line for centralized control (TB7) on only one of the outdoor units. 6) A maximum of 3 system controllers can be connected to the indoor- outdoor transmission line, with the exception that only one G(B)-50A may be connected. 7) When the total number of indoor units exceeds 20 (12 if one or more indoor units of the 72 model or above is connected), it may not be possible to connect a system controller to the indoor-outdoor trans- mission line. 8) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

Mitsubishi Electronics P96 — (2) Cautions diagram (page 43)
Fig. 31 · (2) Cautions

When the P72 and P96 models are not in- cluded in the connected indoor units

When the P72 and P96 models are includ- ed in the connected indoor units

ŒThe table above shows the number of transmission boosters that is

required by the system with three BC controllers. For each BC con- troller that is subtracted from the above-mentioned system, two ad- ditional indoor units can be connected. (3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] L25 200m [656ft] 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L25+L31+L12(L11) 500m [1640ft] L12(L11)+L31+L22(L21) 500m [1640ft] 3) MA remote controller wiring Same as [5] 1.

GB HWE0803A

Page 44 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 44 · click to enlarge
Page 44

[ II Restrictions ]

ŒOnly use shielded cables.

(4) Wiring method 1) Indoor/outdoor transmission line

Shielded cable connection Daisy-chain the S terminal on the terminal block (TB7) on the out- door units (OC, OS) with the shield wire of the shielded cable. Short- circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the sys- tem Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection

Daisy-chain terminals M1 and M2 of the terminal block for indoor- outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC controllers (BC and BS), of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC), and the S terminal of the system controller.(Non-polarized two-wire) ŒOnly use shielded cables.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC and BS, and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable. 2) Transmission line for centralized control

Connect terminals M1 and M2 on the terminal block (TB5) on the in- door units (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po- larized two-wire) ŒIndoor units must be interlocked with the LOSSNAY unit using the

Daisy-chain terminals M1 and M2 on the terminal block for transmis- sion line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC and OS in the same re- frigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the con- trol board from CN41 to CN40 on only one of the outdoor units. Set the central control switch (SW2-1) on the control board of all out- door units to "ON."

system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock setting from the remote controller is required if the ON/OFF remote controller alone is con- nected. 5) Switch setting Address setting is required as follows.

(5) Address setting method

dures Unit or controller

Main unit IC 01 to 50 ŒAssign the smallest address to the main unit

ŒPort number setting is

in the group. ŒIn a system with a sub BC controller, make

required ŒTo perform a group op-

the settings for the indoor units in the fol- lowing order. (i) Indoor unit to be connected to the main BC

eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.

controller (ii) Indoor unit to be connected to sub BC

controller 1 (iii) Indoor unit to be connected to sub BC

controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.

None of these addresses may overlap any of the indoor unit addresses.

3 MA remote controller

MA No set- tings re- quired.

- Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.

MA Sub remote controller

Settings to be made with the Sub/ Main switch

4 Outdoor unit OC OS

51 to 100 ŒAssign sequential address to the outdoor

ŒTo set the address to 100,

units in the same refrigerant circuit. ŒThe outdoor units are automatically desig-

set the rotary switches to 50. ŒIf the addresses that is as-

nated as OC and OS.(Note)

signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. ŒThe use of a sub BC control-

5 Auxiliary outdoor unit

BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

BC control- ler (Main) BC OC (or OS if it exists) +1

ler requires the connection of a main BC controller.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 10 more labels / short text on this page
Ad- dress setting · Fac- · Proce- · tory set- ting · Setting method Notes · range · 1 Indoor unit · Main remote con- troller · Main · Sub remote con- troller
Page 45 of the Mitsubishi Electronics P96 user manual — GB HWE0803A
Page 45 · click to enlarge
Page 45

[ II Restrictions ]

6. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter) (1) Sample control wiring
Mitsubishi Electronics P96 — Shielded cable connection diagram (page 45)
Fig. 32 · Shielded cable connection

Leave the male connector on CN41 as it is.

1 1 2 1 2 2 2 1 2 57

M1M2

Leave the male connector on CN41 as it is.

Leave the male connector on CN41 as it is.

*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.

(2) Cautions

(3) Maximum allowable length 1) Indoor/outdoor transmission line Maximum distance (1.25mm2 [AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] 2) Transmission line for centralized control Maximum line distance via outdoor unit (1.25mm2 [AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft] 3) MA remote controller wiring Maximum overall line length (0.3 to 1.25mm2 [AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft]

1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 2 MA remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replacement of male power jumper connector (CN41) must be per- formed only on one of the outdoor units. 5) Short-circuit the S (shield) terminal of the terminal block for the cen- tral control unit (TB7) and the ground terminal ( ) on the outdoor unit whose power jumper was moved from CN41 to CN40. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

Mitsubishi Electronics P96 — (2) Cautions diagram (page 45)
Fig. 33 · (2) Cautions

When the P72 and P96 models are not in- cluded in the connected indoor units

When the P72 and P96 models are includ- ed in the connected indoor units

ŒThe table above shows the number of transmission boost-

ers that is required by the system with three BC controllers. For each BC controller that is subtracted from the above- mentioned system, two additional indoor units can be con- nected. 7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec- tor on CN41 as it is (factory setting).

GB HWE0803A

Page 46 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 46 · click to enlarge
Page 46

[ II Restrictions ]

door units to "ON." ŒOnly use shielded cables.

(4) Wiring method 1) Indoor/outdoor transmission line

Shielded cable connection Daisy-chain the S terminal of the terminal block (TB7) on the system controller, OC, and OS with the shield of the shielded cable. Short- circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40. 3) MA remote controller wiring Same as [5] 1. When 2 remote controllers are connected to the system Same as [5] 1. Group operation of indoor units Same as [5] 1. 4) LOSSNAY connection

Daisy-chain terminals M1 and M2 of the terminal block for indoor- outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC controllers (BC and BS), and of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire) Shielded cable connection Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC (BS), and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.

The outdoor units in the same refrigerant circuit are auto- matically designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). ŒOnly use shielded cables. 2) Transmission line for centralized control

Connect terminals M1 and M2 on the terminal block (TB5) on the in- door unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po- larized two-wire) ŒIndoor units must be interlocked with the LOSSNAY unit us-

ing the system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock set- ting from the remote controller is required if the ON/OFF re- mote controller alone or the LM adapter alone is connected. 5) Switch setting Address setting is required as follows.

Daisy-chain terminals A and B on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in differ- ent refrigerant circuits and on the OC and OS in the same refrigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the con- trol board from CN41 to CN40 on only one of the outdoor units. Set the central control switch (SW2-1) on the control board of all out-

(5) Address setting method

Main unit IC 01 to 50 ŒAssign the smallest address to the main unit in the

ŒPort number setting is

group. ŒIn a system with a sub BC controller, make the set-

required ŒTo perform a group op-

tings for the indoor units in the following order. (i) Indoor unit to be connected to the main BC con-

eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.

troller (ii) Indoor unit to be connected to sub BC controller 1 (iii) Indoor unit to be connected to sub BC controller 2

Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit ad- dress +1, main unit address +2, main unit address +3, etc.)

2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.

None of these addresses may overlap any of the indoor unit addresses.

3 MA remote controller

Main remote controller MA No settings required. - Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.

Sub remote controller MA Sub re- mote con- troller

Settings to be made with the Sub/Main switch

4 Outdoor unit OC OS

51 to 100 ŒThe sum of the smallest address of the indoor units

ŒTo set the address to 100,

set the rotary switches to 50. 00

in the same system and 50. ŒAssign sequential address to the outdoor units in

the same refrigerant circuit. ŒThe outdoor units are automatically designated as

OC and OS.(Note)

5 Auxiliary outdoor unit

BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

ŒTo set the address to 100,

set the rotary switches to 50. ŒIf the addresses that is as-

signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. ŒThe use of a sub BC control-

BC control- ler (Main) BC 51 to 100 OC (or OS if it exists) +1

ler requires the connection of a main BC controller.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 13 more labels / short text on this page
Pro · Fact · Address · ce- du- res · Unit or controller · setting · Setting method Notes · ory set- ting · range · 1 Indoor unit · Mai · n · BC controller (Sub)
Page 47 of the Mitsubishi Electronics P96 user manual — Shielded cable connection
Page 47 · click to enlarge
Page 47

[ II Restrictions ]

[6] An Example of a System to which an M-NET Remote Controller is connected

Mitsubishi Electronics P96 — Shielded cable connection diagram (page 47)
Fig. 34 · Shielded cable connection

Leave the male connector on CN41 as it is.

Leave the male connector on CN41 as it is.

Leave the male connector on CN41 as it is.

*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.

(2) Cautions 1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 2) No more than 3 M-NET remote controllers can be connected to a group of indoor units. 3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 4) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units. 5) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the out- door units. 6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in par- allel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

ŒThe left table shows the number of transmission boosters

that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-men- tioned system, two additional indoor units can be connected. 7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec- tor on CN41 as it is (factory setting). (3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 3. 2) Transmission line for centralized control Same as [5] 4. 3) M-NET remote controller wiring Maximum overall line length (0.3 to 1.25mm2 [AWG22 to 16]) m1 10m [32ft] m2+m3 10m [32ft] If the standard-supplied cable must be extended, use a cable with a diameter of 1.25mm2 [AWG16]. The section of the cable that exceeds 10m [32ft] must be included in the maximum indoor-outdoor transmission line distance described in (1). When connected to the terminal block on the Simple re- mote controller, use cables that meet the following cable size specifications: 0.75 - 1.25 mm2 [AWG18-16].

Mitsubishi Electronics P96 — Shielded cable connection diagram (page 47)
Fig. 35 · Shielded cable connection

When the P72 and P96 models are not included in the connected indoor units

When the P72 and P96 models are included in the connected in- door units

Page 48 of the Mitsubishi Electronics P96 user manual — (5) Address setting method
Page 48 · click to enlarge
Page 48

[ II Restrictions ]

When 2 remote controllers are connected to the sys- tem Refer to the section on Switch Setting. Performing a group operation (including the group operation of units in different refrigerant circuits). Refer to the section on Switch Setting. 4) LOSSNAY connection Same as [5] 4. 5) Switch setting Address setting is required as follows.

(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 3. Shielded cable connection Same as [5] 1. 2) Transmission line for centralized control Same as [5] 4. Shielded cable connection Same as [5] 4. 3) M-NET remote controller wiring M-NET remote controller is connectable anywhere on the indoor-outdoor transmission line.

(5) Address setting method

dures Unit or controller

Main unit IC 01 to 50 ŒAssign the smallest address to the main unit

ŒPort number setting is

in the group. ŒIn a system with a sub BC controller, make

required ŒTo perform a group op-

the settings for the indoor units in the fol- lowing order. (i) Indoor unit to be connected to the main BC

eration of indoor units that have different func- tions, set the indoor unit in the group with the greatest number of functions as the main unit.

controller (ii) Indoor unit to be connected to sub BC

controller 1 (iii) Indoor unit to be connected to sub BC

controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

Sub unit Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

2 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.

None of these addresses may overlap any of the indoor unit addresses.

3 M-NET remote controller

RC 101 to 150 Add 100 to the main unit address in the group

ŒIt is not necessary to set the

100s digit. ŒTo set the address to 200,

set the rotary switches to 00.

RC 151 to 200 Add 150 to the main unit address in the group

4 Outdoor unit OC OS

51 to 100 ŒAssign sequential address to the outdoor

ŒTo set the address to 100,

units in the same refrigerant circuit. ŒThe outdoor units are automatically desig-

set the rotary switches to 50. ŒIf the addresses that is as-

nated as OC and OS.(Note)

signed to the main BC con- troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif- ferent, unused address with- in the setting range. ŒThe use of a sub BC control-

5 Auxiliary outdoor unit

BCcon- troller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

BC control- ler (Main) BC OC (or OS if it exists) +1

ler requires the connection of a main BC controller.

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

Show 9 more labels / short text on this page
Ad- dress setting · Fac- · Proce- · tory set- ting · Setting method Notes · range · 1 Indoor unit · Main remote con- troller · Sub remote con- troller
Page 49 of the Mitsubishi Electronics P96 user manual — GB HWE0803A
Page 49 · click to enlarge
Page 49

[ II Restrictions ]

[7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected

Mitsubishi Electronics P96 — Shielded cable connection diagram (page 49)
Fig. 36 · Shielded cable connection

Leave the male connector on CN41 as it is.

Leave the male connector on CN41 as it is.

Leave the male connector on CN41 as it is.

M1M2 M1M2 M1M2 M1 M2 M1 M2 M1 M2

*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.

(2) Cautions

ŒThe left table shows the number of transmission boost-

1) Be sure to connect a system controller. 2) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. 3) Assign to the indoor units connected to the MA remote controller ad- dresses that are smaller than those of the indoor units that are con- nected to the M-NET remote controller. 4) No more than 2 M-NET remote controllers can be connected to a group of indoor units. 5) No more than 2 MA remote controllers can be connected to a group of indoor units. 6) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other. 7) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units. 8) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the outdoor units. 9) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)

ers that is required by the system with three BC control- lers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected. 10) When a power supply unit is connected to the transmis- sion line for centralized control, leave the power jumper connector on CN41 as it is (factory setting). (3) Maximum allowable length 1) Indoor/outdoor transmission line Same as [5] 3. 2) Transmission line for centralized control Same as [5] 4. 3) MA remote controller wiring Same as [5] 1. 4) M-NET remote controller wiring Same as [6]

Mitsubishi Electronics P96 — (2) Cautions diagram (page 49)
Fig. 37 · (2) Cautions

When the P72 and P96 models are not included in the connected indoor units

When the P72and P96 models are included in the connected in- door units

GB HWE0803A

Page 50 of the Mitsubishi Electronics P96 user manual — Shielded cable connection
Page 50 · click to enlarge
Page 50

[ II Restrictions ]

Group operation of indoor units Same as [5] 1. 4) M-NET remote controller wiring When 2 remote controllers are connected to the sys- tem Group operation of indoor units Same as [6] 5) LOSSNAY connection Same as [5] 4. 6) Switch setting Address setting is required as follows.

(4) Wiring method 1) Indoor/outdoor transmission line Same as [5] 3. Shielded cable connection Same as [5] 1. 2) Transmission line for centralized control Same as [5] 4. Shielded cable connection Same as [5] 4. 3) MA remote controller wiring When 2 remote controllers are connected to the sys- tem

Page 51 of the Mitsubishi Electronics P96 user manual — GB HWE0803A
Page 51 · click to enlarge
Page 51

[ II Restrictions ]

(5) Address setting method

1 Opera- tion with the MA re- mote controller

IC 01 to 50 ŒAssign the smallest address to

ŒAssign an address smaller than that of

the main unit in the group. ŒIn a system with a sub BC con-

the indoor unit that is connected to the M-NET remote controller. ŒEnter the same indoor unit group set-

troller, make the settings for the indoor units in the following or- der. (i) Indoor unit to be connected to

tings on the system controller as the ones that were entered on the MA re- mote controller. ŒTo perform a group operation of indoor

the main BC controller (ii) Indoor unit to be connected to

units that have different functions, des- ignate the indoor unit in the group with the greatest number of ŒPort number setting is required

sub BC controller 1 (iii) Indoor unit to be connected to

sub BC controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.

IC 01 to 50 Assign sequential numbers start- ing with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

MA No set- tings re- quired.

MA Sub remote control- ler

Settings to be made according to the remote controller func- tion selection

2 Opera- tion with the M-NET remote controller

IC 01 to 50 Assign the smallest address to the main unit in the group.

ŒAssign an address higher than those of

the indoor units that are connected to the MA remote controller. ŒMake the initial settings for the indoor

IC 01 to 50 Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)

unit group settings via the system con- troller. ŒTo perform a group operation of indoor

units that have different functions, des- ignate the indoor unit in the group with the greatest number of functions as the main unit. ŒPort number setting is required. ŒAddresses that are assigned to the in-

door units that are connected to the sub BC controller should be higher than the addresses that are assigned to the in- door units that are connected to the main BC controller.

RC 101 to 150 Add 100 to the main unit ad- dress in the group.

ŒIt is not necessary to set the 100s

digit. ŒTo set the address to 200, set it to

RC 151 to 200 Add 150 to the main unit ad- dress in the group.

3 LOSSNAY LC 01 to 50 Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.

None of these addresses may over- lap any of the indoor unit addresses.

4 Outdoor unit OC OS

51 to 100 ŒAssign sequential address to the

ŒTo set the address to 100, set it to 50. ŒIf the addresses that is assigned to the

outdoor units in the same refrig- erant circuit. ŒThe outdoor units are automati-

main BC controller overlaps any of the addresses that are assigned to the out- door units or to the sub BC controller, use a different, unused address within the setting range. ŒThe use of a sub BC controller requires

cally designated as OC and OS.(Note)

5 Auxiliary outdoor unit

BCcontroller (Sub) BS 51 to 100 Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.

the connection of a main BC controller.

BC controller (Main) BC OC (or OS if it exists) +1

The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).

GB HWE0803A

Show 22 more labels / short text on this page
Ad- dress · Pro- · Facto- ry set- · ce- dure · Unit or controller · set- ting range · Setting method Notes · ting · s · In- door unit · Main unit · Sub unit · MA re- mote con- troller · Main re- mote control- ler · - Main · Sub remote control- ler · In- door unit · Main unit · Sub unit · M- NET re- mote con- troller · Main re- mote control- ler · Sub remote control- ler
Page 52 of the Mitsubishi Electronics P96 user manual — B
Page 52 · click to enlarge
Page 52

[ II Restrictions ]

[8] Restrictions on Pipe Length

(1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con-

troller>

A

*Use a main BC controller when connecting the outdoor units of P144 model or above.

H H'

Reducer (P06 - P18 models) (Supplied with the BC Controller)

B

c Junction pipe (CMY-R160-J)

(P06 - P54 models) (P72 or P96 models) Maximum of 3 units per port Total capacity of P54 or below

Unitm [ft]

Operation Pipe sections Allowable length of pipes

Length Total pipe length A+B+a+b+c+d Refer to the restrictions on the total piping

length in the graph on the next page.

Total pipe length from the outdoor unit to the farthest indoor unit

A+B+d 165 [541] or less (Equivalent length 190 [623] or less)

Between outdoor unit and BC control- ler

A 110 [360] or less

Between BC controller and indoor unit B+d 40 [131] or less*1

Height difference Between indoor and outdoor units

Outdoor unit above indoor unit

H 50 [164] or less

Outdoor unit be- low indoor unit

H' 40 [131] or less

Between indoor unit and BC controller h1 15[49](10[32]) or less*2

Between indoor units h2 15[49](10[32]) or less *2

*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)

*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.

1) To connect the P72 or P96 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J). 2) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port. 3) Note the following when connecting multiple indoor units to a single port. ŒThose indoor units connected to the same port must be installed in the same room. ŒSet the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure

these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.

Show 9 more labels / short text on this page
Outdoor unit · BC controller · Indoor · Branch joint (CMY-Y102S-G2) · d · h1 · h2 · a b · Indoor Indoor Indoor
Page 53 of the Mitsubishi Electronics P96 user manual — [8] Restrictions on Pipe Length
Page 53 · click to enlarge
Page 53

[ II Restrictions ]

The height difference and the pipe length between BC controller and indoor units Restrictions on pipe length [PURY-P72, P96THMU-A, PURY-P72, P96YHMU-A]

Aggregate length of all pipes(m[ft])

controller and farthest indoor unit (m[ft])

Pipe length between main BC

200 10 20 30 40 50 60 70 80 90 100 110

0 5 10 15

[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]

Pipe length between outdoor unit and BC controller (m[ft])

Height difference between main BC controller and farthest indoor unit (m[ft])

Show 17 more labels / short text on this page
[3280] · [229] · [2952] · [196] · [2624] · [164] · [2296] · [131] · [1968] · [98] · [1640] · [64] · [1312] · [984] · [32] · [656] · [16] [32] [49]
Page 54 of the Mitsubishi Electronics P96 user manual — E
Page 54 · click to enlarge
Page 54

[ II Restrictions ]

(2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P120 model or

below.>

Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2)

D

H H'

Branch joint (CMY-Y102S-G2)

Reducer (P06 - P18 models) (Supplied with the BC Controller)

E

B

Indoor

(P06 - P54 models) (P72 or P96 models) Maximum of 3 units per port Total capacity of P54 or below

Unitm [ft]

Operation Pipe sections Allowable length of pipes

Length Total pipe length A+B+C+D+E+a+b+c+d+e+f Refer to the restrictions on the total pip- ing length in the graphon the next page.

Total pipe length from the out- door unit to the farthest indoor unit

A+C+E+f 165 [541] or less (Equivalent length 190 [623] or less)

Between outdoor unit and BC controller

A 110 [360] or less

40 [131] or less*1

Between BC controller and in- door unit

Height differ- ence Between indoor and outdoor units

Outdoor unit above in- door unit

H 50 [164] or less

Outdoor unit below in- door unit

H' 40 [131] or less

h1 15 [49](10[32]) or less*2

Between indoor unit and BC controller

Between indoor units h2 15 [49](10[32]) or less *2

Between the BC controller (main or sub) and the sub BC controller

h3 15 [49] or less

*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)

*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.

Show 16 more labels / short text on this page
Outdoor unit · Indoor · A e h1 · BC controller (sub) · BC controller (main) · h3 · BC controller (sub) · h2 · Junction pipe (CMY-R160-J) · h1 h1 · a · b · c d f · Indoor · B+d or C+D+e · or C+E+f
Page 55 of the Mitsubishi Electronics P96 user manual — below.>
Page 55 · click to enlarge
Page 55

[ II Restrictions ]

1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel. 4) To connect the P36 through P54 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J) and merge the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.) It is also possible to connect the P36 through P54 models of units to a port, although the cooling performance will somewhat decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.) (The factory setting for DIP SW4-6 is OFF. ) 5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port. 6) Note the following when connecting multiple indoor units to a single port. ŒThose indoor units connected to the same port must be installed in the same room. ŒSet the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure

these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode. 7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or below (when two GB type controllers are connected P126 or below for both combined). The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below. If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with two sub controllers is P168 or below.

The height difference and the pipe length between BC controller and indoor units Restrictions on pipe length [PURY-P120THMU-A, PURY-P120YHMU-A]

Aggregate length of all pipes(m[ft])

controller and farthest indoor unit (m[ft])

Pipe length between main BC

200 10 20 30 40 50 60 70 80 90 100 110

0 5 10 15

[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]

Pipe length between outdoor unit and BC controller (m[ft])

Height difference between main BC controller and farthest indoor unit (m[ft])

Show 17 more labels / short text on this page
[3280] · [229] · [2952] · [196] · [2624] · [164] · [2296] · [131] · [1968] · [98] · [1640] · [1312] · [64] · [984] · [32] · [656] · [16] [32] [49]
Page 56 of the Mitsubishi Electronics P96 user manual — E
Page 56 · click to enlarge
Page 56

[ II Restrictions ]

(3) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144 model or

above.>

Branch joint (CMY-R100VBK) The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity index of the two, regardless of the relative positions of the outdoor units or their addresses. If the distributor is placed in the outdoor unit that has a smaller capacity, refrigerant will not be properly distributed and compressor failure may result. (If outdoor units that have the same capacity are used in combination, the distributor can be placed in either outdoor unit.)

Outdoor unit 1 Outdoor unit 2

Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2)

G F

A

D

H H'

Branch joint (CMY-Y102S-G2)

Reducer (P06 - P18 models) (Supplied with the BC Controller)

E

B

Indoor

(P06 - P54 models) (P72 - P96 models) Maximum of 3 units per port Total capacity of P54 or below

Unitm [ft]
Mitsubishi Electronics P96 — E diagram (page 56)
Fig. 38

Refer to the restrictions on the total pip- ing length in the graph on the next page.

Total pipe length from the out- door unit to the farthest indoor unit

F(G)+A+C+E+f 165 [541] or less (Equivalent length 190 [623] or less)

Between indoor units h2 15 [49](10[32]) or less *2

Between the BC controller (main or sub) and the sub BC controller

*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)

*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.

Show 17 more labels / short text on this page
h4 · Indoor · e · h1 · BC controller (sub) · BC controller (main) · h3 · BC controller (sub) · h2 · h1 · a · Junction pipe (CMY-R160-J) · b · c d · f · h1 · Indoor
Page 57 of the Mitsubishi Electronics P96 user manual — above.>
Page 57 · click to enlarge
Page 57

[ II Restrictions ]

1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel. 4) To connect the P36 through P54 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J) and merge the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.) It is also possible to connect the P36 through P54 models of units to a port, although the cooling performance will somewhat decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.) (The factory setting for DIP SW4-6 is OFF.) 5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port. 6) Note the following when connecting multiple indoor units to a single port. ŒThose indoor units connected to the same port must be installed in the same room. ŒSet the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure

these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode. 7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or below (when two GB type controllers are connected P126 or below for both combined) . The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below. If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with two sub controllers is P168 or below.

Page 58 of the Mitsubishi Electronics P96 user manual — [PURY-P216, P240TSHMU-A] [PURY-P216, P240YSHMU-A]
Page 58 · click to enlarge
Page 58

[ II Restrictions ]

Restrictions on pipe length

[PURY-P144, P168TSHMU-A] [PURY-P144, P168YSHMU-A]

[PURY-P192TSHMU-A] [PURY-P192YSHMU-A]

Aggregate length of all pipes(m[ft])

Aggregate length of all pipes(m[ft])

200 10 20 30 40 50 60 70 80 90 100

200 10 20 30 40 50 60 70 80 90 100

[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]

[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]

Pipe length between outdoor unit and BC controller (m[ft])

Pipe length between outdoor unit and BC controller (m[ft])

[PURY-P216, P240TSHMU-A] [PURY-P216, P240YSHMU-A]

Aggregate length of all pipes(m[ft]) Pipe length between main BC

200 10 20 30 40 50 60 70 80 90 100

[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]

Pipe length between outdoor unit and BC controller (m[ft])

The height difference and the pipe length between BC controller and indoor units

controller and farthest indoor unit (m[ft])

0 5 10 15

Height difference between main BC controller and farthest indoor unit (m[ft])

Show 35 more labels / short text on this page
[3280] · [3280] · [2952] · [2952] · [2624] · [2624] · [2296] · [2296] · [1968] · [1968] · [1640] · [1640] · [1312] · [1312] · [984] · [984] · [656] 110 · [656] · [3280] · [2952] · [2624] · [2296] · [1968] · [1640] · [1312] · [984] · [656] · [229] · [196] · [164] · [131] · [98] · [64] · [32] · [16] [32] [49]
Page 59 of the Mitsubishi Electronics P96 user manual — P109 - P126
Page 59 · click to enlarge
Page 59

[ II Restrictions ]

1. Refrigerant pipe size (1) Between outdoor unit and the first twinning pipe (Part A)
Unitmm [inch]

Refrigerant pipe size Connection to outdoor unit and BC controller

Low-pressure pipe High-pressure pipe Low-pressure pipe High-pressure pipe

72 ø19.05 [3/4"] ø15.88 [5/8"] ø19.05 [3/4"] ø15.88 [5/8"]

96 ø22.2 [7/8"]

ø22.2 [7/8"]

ø19.05 [3/4"] 120

ø19.05 [3/4"]

ø22.2[7/8"] ø22.2 [7/8"] 168

ø28.58 [1-1/8"] ø28.58 [1-1/8"]

216 ø28.58 [1-1/8"] ø28.58 [1-1/8"] 240

(2) Between BC controller and indoor unit (Sections a, b, c, d, e, and f )

Unitmm [inch]

Refrigerant pipe size Indoor unit connection (Flare connection for all models)

Liquid pipe Gas pipe Liquid pipe Gas pipe

P06, P08, P12, P15, P18 ø6.35 [1/4"] ø12.7 [1/2"] ø6.35 [1/4"] ø12.7 [1/2"]

P24, P27, P30

ø9.52 [3/8"] ø15.88 [5/8"] ø9.52 [3/8"] ø15.88 [5/8"] P36, P48, P54

P72

ø19.05 [3/4"]

ø19.05 [3/4"]

ø12.7 [1/2"]

ø12.7 [1/2"]

P96 ø22.2

ø22.2

(3) Between the main and sub BC controllers (Section C)

Unitmm [inch]

Refrigerant pipe size (Brazed connection on all models )

Liquid pipe High-pressure gas pipe Low-pressure gas pipe

- P72

ø15.88 [5/8"] ø19.05 [3/4"]

ø9.52 [3/8"]

P73 - P108

ø22.2 [7/8"]

ø19.05 [3/4"]

P109 - P126

ø12.7 [1/2"]

ø28.58 [1-1/8"] P127 - P144

ø22.2 [7/8"] P145 - P168 ø15.88 [5/8"]

Select the proper size pipes for the main unit based on the total capacity of the indoor units that are connected to both sub BC controllers. Select the proper size pipes for the sub controller side based on the total capacity of the indoor units that are connected to the sub controller.

Show 5 more labels / short text on this page
Outdoor units · Indoor unit · [7/8"] · [7/8"] · Indoor unit
Page 60 of the Mitsubishi Electronics P96 user manual — PURY-P120THMU-A PURY-P120YHMU-A
Page 60 · click to enlarge
Page 60

[ II Restrictions ]

2. Connecting the BC controller (1) Size of the pipe that fits the standard BC controller ports

P72 - P120 models

ConnectionBrazed connection

*1 Reducer (Standard supplied parts)

*2 Junction pipe kit (Model name: CMY-R160-J) (Optional accessory)

Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)

A B

Indoor

P18 model or below P24 - P54 models P72 or P96 models

Maximum of 3 units per port Total capacity of P30 or below (All units connected to the same port must be in the same operating mode.)

The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.

Unitmm [inch]

High-pressure side (gas) Low-pressure side (gas)

Outdoor unit side PURY-P72THMU-A PURY-P72YHMU-A

ø15.88 [5/8"] (Brazed connection)

ø19.05 [3/4"] (Brazed connection)

PURY-P96THMU-A PURY-P96YHMU-A ø19.05 [3/4"] (Brazed connection)

ø22.2 [7/8"] (Brazed connection)

PURY-P120THMU-A PURY-P120YHMU-A

ø28.58 [1-1/8"] (Brazed connection)

Indoor unit side ø9.52 [3/8"] (Flare connection) ø15.88 [5/8"] (Flare connection)

* BC controllers can only be connected to P72 - P120 models of outdoor units.

Show 5 more labels / short text on this page
To outdoor unit · BC controller · 3* · Pipe sections · Operation
Page 61 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 61 · click to enlarge
Page 61

[ II Restrictions ]

1. To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2. To connect P36 - P96 models of indoor units (or when the total capacity of indoor units exceeds P31), use a junction pipe kit and merge the two nozzles.

Liquid pipe side:3/8F (Flare connection)

Liquid pipe side:3/8F (Flare connection) Gas pipe side:5/8F (Flare connection)

Liquid pipe side9.52[3/8”]ID
Liquid pipe side6.35[1/4"]ID
Gas pipe side19.05[3/4”]ID(*1)

Gas pipe side:5/8F (Flare connection)

Gas pipe side12.7[1/2"]ID

Supplied with a thermal insulation cover

3. To connect multiple indoor units to a port (or to a junction pipe) Œ Maximum total capacity of connected indoor units: P30 or below (in a system with a junction pipe: P96 or below) Œ Maximum number of connectable indoor units: 3 units Œ Branch joint: Use CMY-Y102S-G2 (optional accessory). Œ Refrigerant pipe selection (size of the pipes A and B in the previous page) : Select the proper size pipes based

on the total capacity of the downstream indoor units, using the table below as a reference.

Unitmm [inch]

Total capacity of indoor units Liquid pipe Gas pipe

P54 or below ø9.52 [3/8"] ø15.88 [5/8"]

P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]

P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]

50 [1-31/32"] · 234 [9-7/32"]

Page 62 of the Mitsubishi Electronics P96 user manual — PURY-P192TSHMU-A PURY-P192YSHMU-A
Page 62 · click to enlarge
Page 62

[ II Restrictions ]

(2) Size of the pipe that fits the main BC controller ports

P72 - P240 models

Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)

BC controller (main) To outdoor unit Connection: Brazed connection

*1 Reducer (Standard supplied parts)

A B

*2 Junction pipe kit (Model name:CMY-R160-J) (Optional accessory)

Indoor Indoor Indoor

Indoor Indoor Indoor

P18 model or below P24 - P54 models P72 or P96 models

Maximum of 3 units per port Total capacity of P54 or below (All units connected to the same port must be in the same operating mode.)

The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.

1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller. 2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use a junction pipe kit and merge the two nozzles. 3) To connect multiple indoor units to a port (or to a junction pipe) ŒMaximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below) ŒMaximum number of connectable indoor units: 3 units ŒBranch joint: Use CMY-Y102S-G2 (optional accessory). ŒRefrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total

capacity of the downstream indoor units, using the table below as a reference.

Unitmm [inch]

Total capacity of indoor units Liquid pipe Gas pipe

P54 or below ø9.52 [3/8"] ø15.88 [5/8"]

P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]

P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]

Unitmm [inch]

High pressure side (Liquid) Low-pressure side (Gas)

PURY-P72THMU-A PURY-P72YHMU-A

ø15.88 [5/8"] (Brazed connection)

ø19.05 [3/4"] (Brazed connection)

PURY-P96THMU-A PURY-P96YHMU-A ø19.05 [3/4"] (Brazed connection)

ø22.2 [7/8"] (Brazed connection)

PURY-P120THMU-A PURY-P120YHMU-A

PURY-P144TSHMU-A PURY-P144YSHMU-A

ø22.2 [7/8"] (Brazed connection) PURY-P168TSHMU-A PURY-P168YSHMU-A

ø28.58 [1-1/8"] (Brazed connection)

PURY-P192TSHMU-A PURY-P192YSHMU-A

PURY-P216TSHMU-A PURY-P216YSHMU-A ø28.58 [1-1/8"] (Brazed connection) PURY-P240TSHMU-A PURY-P240YSHMU-A

Indoor unit side ø9.52 [3/8"] (Flare connection) ø15.88 [5/8"] (Flare connection)

Show 4 more labels / short text on this page
3* · Pipe sections · Operation · Outdoor unit side
Page 63 of the Mitsubishi Electronics P96 user manual — P109 - P126
Page 63 · click to enlarge
Page 63

[ II Restrictions ]

(3) Size of the pipe that fits the sub BC controller ports

Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)

ConnectionBrazed connection

BC controller (sub) To Main BC controller

*2 Junction pipe kit (Model name: CMY-R160-J) (Optional accessory)

*1 Reducer (Standard supplied parts)

A B

Indoor Indoor Indoor

Indoor Indoor Indoor

P18 model or below P24 - P54 models P72 or P96 models

Maximum of 3 units per port Total capacity of P54 or below (All units connected to the same port must be in the same operating mode.)

The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.

1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller. 2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use a junction pipe kit and merge the two nozzles. 3) To connect multiple indoor units to a port (or to a junction pipe) ŒMaximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below) ŒMaximum number of connectable indoor units: 3 units ŒBranch joint: Use CMY-Y102S-G2 (optional accessory). ŒRefrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total

capacity of the downstream indoor units, using the table below as a reference.

Unitmm [inch]

Total capacity of indoor units Liquid pipe Gas pipe

P54 or below ø9.52 [3/8"] ø15.88 [5/8"]

P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]

P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]

Unitmm [inch]

Total capacity of the in- door units that are con- nected to the BC controller

(gas) Liquid pipe side

On the BC controller side P72 model or below ø15.88 [5/8"] (Brazed connection)

ø19.05 [3/4"] (Brazed connection) ø9.52 [3/8"] (Brazed connection) P73 - P108 ø19.05 [3/4"] (Brazed connection)

ø22.2 [7/8"] (Brazed connection)

P109 - P126

ø12.7 [1/2"] (Brazed connection) P127 - P144

ø28.58 [1-1/8"] (Brazed connection)

ø22.2 [7/8"] (Brazed connection) P145 - P168 ø15.88 [5/8"] (Brazed connection)

Show 5 more labels / short text on this page
3* · Operation Pipe sections · High-pressure side · Low-pressure side · (liquid)
Page 64 of the Mitsubishi Electronics P96 user manual — III Outdoor Unit Components
Page 64 · click to enlarge
Page 64

III Outdoor Unit Components

[1] Outdoor Unit Components and Refrigerant Circuit 57 [2] Control Box of the Outdoor Unit 60 [3] Outdoor Unit Circuit Board 64 [4] BC Controller Components 74 [5] Control Box of the BC Controller 77 [6] BC Controller Circuit Board 78

Page 65 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 65 · click to enlarge
Page 65
Page 65 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 66 of the Mitsubishi Electronics P96 user manual — 1. Front view of a outdoor unit (1) PURY-P72, P96, P120THMU-A
Page 66 · click to enlarge
Page 66

[ III Outdoor Unit Components ]

III Outdoor Unit Components [1] Outdoor Unit Components and Refrigerant Circuit

1. Front view of a outdoor unit (1) PURY-P72, P96, P120THMU-A

PURY-P72, P96, P120YHMU-A

Mitsubishi Electronics P96 — 1. Front view of a outdoor unit (1) PURY-P72, P96, P120THMU-A diagram (page 66)
Fig. 39 · 1. Front view of a outdoor unit (1) PURY-P72, P96, P…
Show 6 more labels / short text on this page
Fan guard · Fan · Control Box · Heat exchanger · Front panel · Fin guard
Page 67 of the Mitsubishi Electronics P96 user manual — 2. Refrigerant circuit (1) PURY-P72THMU-A
Page 67 · click to enlarge
Page 67

[ III Outdoor Unit Components ]

2. Refrigerant circuit (1) PURY-P72THMU-A

PURY-P72YHMU-A

Mitsubishi Electronics P96 — 2. Refrigerant circuit (1) PURY-P72THMU-A diagram (page 67)
Fig. 40 · 2. Refrigerant circuit (1) PURY-P72THMU-A

Refrigerant service valve on the low pressure side (BV1) Solenoid valve(SV5c) Refrigerant service valve on the high pressure side(BV2)

Page 68 of the Mitsubishi Electronics P96 user manual — (2) PURY-P96, P120THMU-A
Page 68 · click to enlarge
Page 68

[ III Outdoor Unit Components ]

(2) PURY-P96, P120THMU-A

PURY-P96, P120YHMU-A

Mitsubishi Electronics P96 — (2) PURY-P96, P120THMU-A diagram (page 68)
Fig. 41

Low pressure check joint(CJ2) Refrigerant service valve on the low pressure side(BV1)

Refrigerant service valve on the high pressure side (BV2)

Page 69 of the Mitsubishi Electronics P96 user manual — (TB1)
Page 69 · click to enlarge
Page 69

[ III Outdoor Unit Components ]

[2] Control Box of the Outdoor Unit

<HIGH VOLTAGE WARNING>

Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and Check that the voltage across terminals FT-P and FT-N (YHMU) on the INV board or the voltage at both ends of the main capacitor (C1) (THMU) is 20VDC or below. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)

1. PURY-P72THMU-A

DC reactor (DCL) Fan board

Mitsubishi Electronics P96 — 1. PURY-P72THMU-A diagram (page 69)
Fig. 42
Mitsubishi Electronics P96 — 1. PURY-P72THMU-A diagram (page 69)
Fig. 43

Rush current protection resistor (R1) Note.2

(TB1)

INV board Terminal block for transmission line (TB3, TB7)

1. Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components. 2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
Show 8 more labels / short text on this page
Control board · Electromagnetic relay(72C) · Noise filter · M-NET board · Terminal block for · power supply · Ground terminal · Smoothing capacitor(C1)
Page 70 of the Mitsubishi Electronics P96 user manual — (72C)
Page 70 · click to enlarge
Page 70

[ III Outdoor Unit Components ]

2. PURY-P96, P120THMU-A

Mitsubishi Electronics P96 — 2. PURY-P96, P120THMU-A diagram (page 70)
Fig. 44

(72C)

(ACCT3)

(DCCT1)

(TB1)

IPM

Terminal block for transmission line (TB3, TB7)

1. Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components. 2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
Show 11 more labels / short text on this page
DC reactor (DCL) · Electromagnetic relay · Diode stack · Noise filter · Current sensor · M-NET board · Current sensor · Terminal block for · power supply · Ground terminal · Smoothing capacitor(C1)
Page 71 of the Mitsubishi Electronics P96 user manual — 3. PURY-P72, P96, P120YHMU-A
Page 71 · click to enlarge
Page 71

[ III Outdoor Unit Components ]

3. PURY-P72, P96, P120YHMU-A

Capacitor(C100) Rush current protection resistor (R1,R5) Note.2

Fan board Control board

Mitsubishi Electronics P96 — 3. PURY-P72, P96, P120YHMU-A diagram (page 71)
Fig. 45

Terminal block for power supply (TB1)

Terminal block for transmission line (TB3, TB7) Note.1

1. Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components. 2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
Show 7 more labels / short text on this page
Electromagnetic relay(72C) · DC reactor (DCL) · Noise filter · M-NET board · Fuse(F4) · Fuse(F5) Ground terminal · INV board
Page 72 of the Mitsubishi Electronics P96 user manual — 4. Transformer Box (PURY-P72, P96, P120Y(T)HMU-A)
Page 72 · click to enlarge
Page 72

[ III Outdoor Unit Components ]

4. Transformer Box (PURY-P72, P96, P120Y(T)HMU-A)

Mitsubishi Electronics P96 — 4. Transformer Box (PURY-P72, P96, P120Y(T)HMU-A) diagram (page 72)
Fig. 46 · 4. Transformer Box (PURY-P72, P96, P120Y(T)HMU-A)

Transformer (T03) · Transformer (T02)

Page 73 of the Mitsubishi Electronics P96 user manual — CNAC L1 L2
Page 73 · click to enlarge
Page 73

[ III Outdoor Unit Components ]

[3] Outdoor Unit Circuit Board

1. Outdoor unit control board

CN2

CNDC Bus voltage input P N

CN332 Output 18VDC GND (Fan board)

Serial communication signal input GND INV board Output 17VDC

CN801 Pressure switch connection

CN4 GND Serial communication signal output

CNAC2 L1 L2

CN505 72C driving output (THMU)

CN51

Output 12VDC Compressor ON/OFF output Error output

CN72 72C driving output (YHMU)

LED3 Lit when powered

LED2 Lit during normal CPU operation

LED3 Lit when powered

CNVCC2 Output 12VDC Output 5VDC GND CNIT Output 12VDC GND Output 5VDC Power supply detection input

CN41 Power supply for centralized control OFF CN40 Power supply for centralized control ON CN102

CNAC L1 L2

External signal input (contact input) F01 Fuse 250V AC/3.15A

Indoor/outdoor transmission line input/output (30VDC) Power supply input for centralized control system (30VDC)

Power supply ON/OFF signal output CNS2 Transmission line input/output for centralized control system (30VDC)

Show 6 more labels / short text on this page
LEV driving output · LED1 Service LED · SWU1,2 Address switch · SW1-5 Dip switch · Actuator driving output · Sensor input
Page 74 of the Mitsubishi Electronics P96 user manual — 2. M-NET board
Page 74 · click to enlarge
Page 74

[ III Outdoor Unit Components ]

2. M-NET board

CN04 Bus voltage input (YHMU only) Bus voltage output (THMU only) P N

CN102 CNS2 Transmission line input/output for centralized control system (30VDC)

CNIT Input 12VDC GND Input 5VDC Power supply detection output Power supply ON/OFF signal input

CN03(THMU only) Bus voltage input P N

Power supply output for centralized control system (30VDC) Indoor/outdoor transmission line input/output (30VDC)

(THMU only) F01 250V 3.15A Grounding

LED1 Power supply for indoor transmission line

TP1,2 Check pins for indoor/outdoor transmission line

Ground terminal for transmission line Grounding Grounding

TB7 Terminal block for transmission line for centralized control TB3 Indoor/outdoor transmission block

Page 75 of the Mitsubishi Electronics P96 user manual — 3. INV board (1) PURY-P72THMU-A
Page 75 · click to enlarge
Page 75

[ III Outdoor Unit Components ]

3. INV board (1) PURY-P72THMU-A

Mitsubishi Electronics P96 — 3. INV board (1) PURY-P72THMU-A diagram (page 75)
Fig. 47 · 3. INV board (1) PURY-P72THMU-A
CN6 OpenNo-load operation setting Short-circuited: Normal setting CN5V GND Output 5VDC
LED1 LitInverter in normal operation Blink: Inverter error

Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

Page 76 of the Mitsubishi Electronics P96 user manual — CNIPM
Page 76 · click to enlarge
Page 76

[ III Outdoor Unit Components ]

(2) PURY-P96, P120THMU-A

CNTH Thermistor input (THHS) CNTYP Function setting input (Z26)

CNCT3 Current (AC) sensor input (ACCT3)

CNCT2 Current (AC) sensor input ACCT1 ACCT2

LED1 Inverter in normal operation

LED4 Lit during normal CPU operation

SW1 ONNo-load operation setting OFF: Normal setting : Fixed to OFF

CN5V GND Output 5VDC

CNCT Current (DC) sensor input

FT-N(Note) BUS voltage output(N)

CN4 GND (Fan board) Serial communication

LED3 Lit while charging

SC-P1 Bus voltage input/output(P)

CNIPM

IPM-P BUS voltage output(P) (IPM input)

CNDC1 BUS voltage output P N

IPM driving power supply output and signal output

F02 Fuse 250VAC 3.15A

IPM error signal input (IPM output)

IPM-N BUS voltage input/output(N) (IPM input)

CNDC2 BUS voltage input P N

CNDC3 BUS voltage output P N

Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

Show 6 more labels / short text on this page
LED2 Inverter error · CN2 Serial communication · signal output · GND Output 17VDC · signal input · CNFG Functional earth
Page 77 of the Mitsubishi Electronics P96 user manual — CN2
Page 77 · click to enlarge
Page 77

[ III Outdoor Unit Components ]

(3) PURY-P72, P96, P120YHMU-A

SC-P1 Rectifier diode output (P)

CN6 OpenNo-load operation setting Short-circuited: Normal setting

CN5V GND Output 5VDC

RSH1 Overcurrent detection resistor

SC-P2 Bus voltage Input(P)

LED1 LitInverter in normal operation Blink: Inverter error

CN4 GND(INV Board)

Serial communication signal output

Bus voltage check terminal (P) Note

CN2

Serial communication signal output GND Input 17VDC

CN1 Bus voltage output N P

CNTYP Inverter board type

Bus voltage check terminal (N) Note 1

CT22 Current sensor(W) CT12 Current sensor(U)

C30 C37 Smoothing capacitor

1. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
Show 8 more labels / short text on this page
IGBT (Rear) · SC-V Inverter output(V) · SC-L1 Input(L1) · SC-W Inverter output(W) · SC-U Inverter output(U) · SC-L2 Input(L2) · SC-L3 Input(L3) · CT3 Current sensor(L3)
Page 78 of the Mitsubishi Electronics P96 user manual — 4. Fan board (1) PURY-P72, P96, P120THMU-A
Page 78 · click to enlarge
Page 78

[ III Outdoor Unit Components ]

4. Fan board (1) PURY-P72, P96, P120THMU-A

CN4 GND Serial communication signal output GND(Control board) Serial communication signal output

CNVDC Bus voltage input N P

F01 Fuse 250VAC 15A

LED3 Lit during normal CPU operation

CN18V Input 18VDC GND

CN22 GND(INV board) Input 5VDC Serial communication signal input GND(INV board) Input 17VDC

CN21 Serial communication signal output GND(INV board) Input 17VDC

THBOX Thermistor (Control box internal temperature detection)

LED1 Inverter in normal operation

R630 Overcurrent detection resistor

DIP IPM(Rear) CNINV Inverter output W V U

LED2 Inverter error

Page 79 of the Mitsubishi Electronics P96 user manual — CN5
Page 79 · click to enlarge
Page 79

[ III Outdoor Unit Components ]

(2) PURY-P72, P96, P120YHMU-A

CN18V Input 18VDC GND

LED3 Lit during normal CPU operation

CN4 GND Serial communication signal output

CN5

GND(Control board) Serial communication signal output

CN21 Serial communication signal output GND(INV board) Input 17VDC

CNVDC Bus voltage input N P

CN22 GND(INV board) Input 5VDC Serial communication signal input GND(INV board) Output 17VDC

CNINV Inverter output W V U

THBOX Thermistor (Control box internal temperature detection)

LED1 Inverter in normal operation LED2 Inverter error

R630,R631 Overcurrent detection resistor

DIP IPM Rear

Page 80 of the Mitsubishi Electronics P96 user manual — 5. Noise Filter (1) PURY-P72THMU-A
Page 80 · click to enlarge
Page 80

[ III Outdoor Unit Components ]

5. Noise Filter (1) PURY-P72THMU-A

Mitsubishi Electronics P96 — 5. Noise Filter (1) PURY-P72THMU-A diagram (page 80)
Fig. 48 · 5. Noise Filter (1) PURY-P72THMU-A
Page 81 of the Mitsubishi Electronics P96 user manual — (2) PURY-P96, P120THMU-A
Page 81 · click to enlarge
Page 81

[ III Outdoor Unit Components ]

(2) PURY-P96, P120THMU-A

R1,2 Rush current protection resistor

TB42 Bus voltage output(N)

TB31 Bus voltage output(P)

CN03 72C drive input

Electromagnetic relay (72C)

F3 Fuse 250VAC 6.3A

Diode stack rectified voltage input (Diode stack output)

Output (Diode stack input)

CN02 Output L1 L2

TB23 Input (L3)

TB22 Input (L2)

F1 Fuse 250VAC 6.3A

TB21 Input (L1)

F2 Fuse 250VAC 6.3A

CN01 Input L3 L2 L1

Grounding

Page 82 of the Mitsubishi Electronics P96 user manual — (3) PURY-P72, P96, P120YHMU-A
Page 82 · click to enlarge
Page 82

[ III Outdoor Unit Components ]

(3) PURY-P72, P96, P120YHMU-A

Mitsubishi Electronics P96 — (3) PURY-P72, P96, P120YHMU-A diagram (page 82)
Fig. 49

CN2 Surge absorber circuit Surge absorber circuit Short circuit Short circuit

Page 83 of the Mitsubishi Electronics P96 user manual — TH12
Page 83 · click to enlarge
Page 83

[ III Outdoor Unit Components ]

[4] BC Controller Components

1. CMB-P NU-G, GA (1) Front

Mitsubishi Electronics P96 — 1. CMB-P NU-G, GA (1) Front diagram (page 83)
Fig. 50 · 1. CMB-P NU-G, GA (1) Front

Liquid pipe (Indoor unit side)

Gas pipe (Indoor unit side)

(2) Rear view <G type>

PS1

TH11

Mitsubishi Electronics P96 — (2) Rear view <G type> diagram (page 83)
Fig. 51 · (2) Rear view <G type>

SVM1

LEV1 LEV3

PS3

TH16

Tube in tube heat exchanger

TH12

TH15

Gas/Liquid separator

Page 84 of the Mitsubishi Electronics P96 user manual — SVM1
Page 84 · click to enlarge
Page 84

[ III Outdoor Unit Components ]

(3) Rear view <GA type>

LEV2 PS1 PS3

TH16

Mitsubishi Electronics P96 — (3) Rear view <GA type> diagram (page 84)
Fig. 52 · (3) Rear view <GA type>

LEV3

TH11

LEV1

SVM2

Tube in tube heat exchanger

SVM1

TH12 TH15

Gas/Liquid separator

Page 85 of the Mitsubishi Electronics P96 user manual — LEV3
Page 85 · click to enlarge
Page 85

[ III Outdoor Unit Components ]

2. CMB-P NU-GB, HB (1) Front

Mitsubishi Electronics P96 — 2. CMB-P NU-GB, HB (1) Front diagram (page 85)
Fig. 53 · 2. CMB-P NU-GB, HB (1) Front

Liquid pipe (Indoor unit side)

Gas pipe (Indoor unit side)

(2) Rear view

TH12

Mitsubishi Electronics P96 — (2) Rear view diagram (page 85)
Fig. 54 · (2) Rear view

LEV3

TH15

Page 86 of the Mitsubishi Electronics P96 user manual — 1. CMB-P1016NU-G, GA
Page 86 · click to enlarge
Page 86

[ III Outdoor Unit Components ]

[5] Control Box of the BC Controller

1. CMB-P1016NU-G, GA

Mitsubishi Electronics P96 — 1. CMB-P1016NU-G, GA diagram (page 86)
Fig. 55

Terminal block for power supply

Terminal block for transmission line

Transformer · Relay board · BC controller board

Page 87 of the Mitsubishi Electronics P96 user manual — 1. BC controller circuit board (BC board)
Page 87 · click to enlarge
Page 87

[ III Outdoor Unit Components ]

[6] BC Controller Circuit Board

1. BC controller circuit board (BC board)

SW1 SW2 SW5 SW6 SW4

Page 88 of the Mitsubishi Electronics P96 user manual — 2. RELAY BOARD (RELAY 4 board)
Page 88 · click to enlarge
Page 88

[ III Outdoor Unit Components ]

2. RELAY BOARD (RELAY 4 board)

3. RELAY BOARD (RELAY 10 board)

Page 89 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 89 · click to enlarge
Page 89
Page 89 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 90 of the Mitsubishi Electronics P96 user manual — IV Remote Controller
Page 90 · click to enlarge
Page 90

IV Remote Controller

[1] Functions and Specifications of MA and ME Remote Controllers 83 [2] Group Settings and Interlock Settings via the ME Remote Controller 84 [3] Interlock Settings via the MA Remote Controller 88 [4] Using the built-in Temperature Sensor on the Remote Controller 89

Page 91 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 91 · click to enlarge
Page 91
Page 91 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 92 of the Mitsubishi Electronics P96 user manual — 1. Comparison of functions and specifications between MA and ME remote controllers
Page 92 · click to enlarge
Page 92

[ IV Remote Controller ]

IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers

There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor-outdoor transmission line, and MA remote controller, which is connected to each indoor unit.

1. Comparison of functions and specifications between MA and ME remote controllers

Mitsubishi Electronics P96 — 1. Comparison of functions and specifications between MA and ME remote controllers diagram (page 92)
Fig. 56 · 1. Comparison of functions and specifications betwee…

Not required (required only by a system with one outdoor unit)*4

Remote controller connection Connectable to any indoor unit in the group

Interlock with the ventilation unit Each indoor unit can individually be in- terlocked with a ventilation unit. (Set up via remote controller in the group.)

Each indoor unit can individually be inter- locked with a ventilation unit. (Set up via remote controller.)

MA remote controller wiring between in- door units requires rewiring.

Either the indoor unit address and remote controller address must both be changed, or the registration information must be changed via MELANS.

*1. MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wire- less remote controller.

*2. Either the MA remote controller or the M-NET remote controller can be connected when a group operation of units in a system with multiple outdoor units is conducted or when a system controller is connected.

*3. M-NET remote controller refers to ME remote controller and ME simple remote controller.

*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.

2. Remote controller selection criteria MA remote controller and M-NET remote controller have different functions and characteristics. Choose the one that better suits the requirements of a given system. Use the following criteria as a reference.
Mitsubishi Electronics P96 — 1. Comparison of functions and specifications between MA and ME remote controllers diagram (page 92)
Fig. 57 · 1. Comparison of functions and specifications betwee…

MA remote controller*1*2 M-NET (ME) remote controller*1*2

ŒThere is little likelihood of system expansion and group-

ŒThere is a likelihood of centralized installation of remote

ing changes. ŒGrouping (floor plan) has been set at the time of instal-

controllers, system expansion, and grouping changes. ŒGrouping (floor plan) has not been set at the time of in-

stallation. ŒTo connect the remote controller directly to the OA pro-

*1. M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.

*2. A system controller must be connected to a system to which both MA remote controller and M-NET remote controller are connected.

Mitsubishi Electronics P96 — 1. Comparison of functions and specifications between MA and ME remote controllers diagram (page 92)
Fig. 58 · 1. Comparison of functions and specifications betwee…
Page 93 of the Mitsubishi Electronics P96 user manual — D
Page 93 · click to enlarge
Page 93

[ IV Remote Controller ]

[2] Group Settings and Interlock Settings via the ME Remote Controller

1. Group settings/interlock settings

Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the indoor/outdoor unit address. (A) Group settings Registration of the indoor units to be controlled with the remote controller, and search and deletion of registered information. (B) Interlock settings Registration of LOSSNAY units to be interlocked with the indoor units, and search and deletion of registered information [Operation Procedures] (1) Address settings Register the indoor unit to be controlled with the remote controller.

CENTRALLY CONTROLLED

˚C 1Hr.

DAILY AUTO OFF

CLOCK

ON OFF

Bring up either the blinking display of HO by turning on the unit or the normal display by pressing the ON/OFF button. The display window must look like one of the two figures below to proceed to the next step.

REMAINDER

CHECK MODE

FILTER

NOT AVAILABLE STAND BY DEFROST

˚C

TEST RUN

LIMIT TEMP.

TEMP.

ON/OFF

A F

CLOCK → ON → OFF

FILTER

G

CHECK TEST

PAR-F27MEA

TIMER SET

E

D

B H

[Blinking display of HO ]

(B) Interlock Settings (A) Group Settings

2 Bring up the Group Setting window. -Press and hold buttons [FILTER] and [ ]

Bring up the Interlock Setting window. -Press button [ ] to bring up the following display. Press again to go back to the Group Setting window as shown under step .

A

B

G

simultaneously for 2 seconds to bring up the display as shown below.

Both the indoor unit address and interlocked unit address will be displayed together.

Indoor unit address display window Indoor unit address display window

Interlocked unit address display window

To search for an address, go to section (2) Address Search.

Select the unit address.

- Select the address of the indoor unit to be registered by pressing button [TEMP. ( ) or ( )] to advance or go back through the addresses. Register the indoor unit whose address appears on the display.

Bring up the address of the indoor unit and the address of the LOSSNAY to be interlocked on the display. - Select the address of the indoor unit to be registered by pressing button [TEMP. ( ) or ( )] to advance or go back through the addresses. - Select the address of the LOSSNAY unit to be interlocked by pressing button [TIMER SET ( ) or ( )] to advance or go back through the interlocked unit addresses.

- Press button [TEST] to register the indoor unit address whose address appears on the display.

D

- If registration is successfully completed, unit type will appear on the display as shown in the figure below.

H

- If the selected address does not have a corresponding indoor unit, an error message will appear on the display. Check the address, and try again.

Make the settings to interlock LOSSNAY units with indoor units. - Press button [TEST] while both the indoor unit address and the address of the LOSSNAY units to be interlocked are displayed to enter the interlock setting. - Interlock setting can also be made by bringing up the LOSSNAY address in the indoor unit address display window and the indoor unit address in the interlocked unit address display window.

D

Unit type (Indoor unit in this case)

If registration is successfully completed, the two displays as shown on the left will appear alternately. If the registration fails, will blink on the display. (Indicates that the selected address does not have a corresponding unit.)

blinks to indicate a registration error. (Indicates that selected address does not have a corresponding unit.)

To register the addresses for multiple indoor units, repeat steps and above. 3 4

To search for an address, go to section (2) Address Search.

To next page.

Show 4 more labels / short text on this page
? · [Normal display] · <Deletion error> · (Displayed alternately)
Page 94 of the Mitsubishi Electronics P96 user manual — F
Page 94 · click to enlarge
Page 94

[ IV Remote Controller ]

Repeat steps and in the previous page to interlock all the indoor units in a group with the LOSSNAY unit.

(C) To return to the normal display When all the group settings and interlock settings are made, take the following step to go back to the normal display. Press and hold buttons [FILTER] and [ ] simultaneously for 2 seconds to go back to the window as shown in step .

To go back to the normal display, follow step .

To search for an address, go to section (2) Address Search.

10 A B

To search for the address of indoor units that have been entered into the remote controller, follow steps and .

(A) To search group settings

(B) Interlock setting search

After performing step , proceed as follows:

Bring up the Group Setting window. - Each pressing of button [ ] will bring up the address of a registered indoor unit and its unit type on the display.

E

Bring up the address of the indoor unit to be searched on the display. - Select the address of the indoor unit to be searched by pressing button [TIMER SET ( ) or ( )] to advance or go back through the interlocked addresses.

H

Unit type (Indoor unit in this case)

LOSSNAY can be searched in the same manner by bringing up the LOSSNAY address in the Interlocked unit address display window.

Bring up on the display the address of the LOSSNAY unit that was interlocked with the indoor unit in step . - With each pressing of button [ ], the address of the LOSSNAY and indoor unit that is interlocked with it will be displayed alternately.

E

- When only one unit address is registered, the same address will remain on the display regardless of how many times the button is pressed. - When the address of multiple units are registered (i.e. 011, 012, 013 ), they will be displayed one at a time in an ascending order with each pressing of button [ ] .

E

Address of an interlocked LOSSNAY unit

To delete an address, go to section (3) Address Deletion.

Bring up the address of another registered unit on the display. - After completing step , a subsequent pressing of button [ ] will bring up the address of another registered unit. (The display method is the same as the one in step .)

E

To go back to the normal display, follow step .

Address of another interlocked unit

To delete an address, go to section (3) Address Deletion .

The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings. The interlock settings between units can be deleted by deleting the interlock settings. Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the display window. To delete an address, the address must first be bought up on the display.

Delete the registered indoor unit address or the interlock setting between units. - Press button ? [CLOCK ON OFF] twice while either the indoor unit address or the address of the interlocked unit is displayed on the display to delete the interlock setting.

F

Show 6 more labels / short text on this page
(2) Address search · <Entry found> · <No entries found> · (Displayed alternately) · (Displayed alternately) · (3) Address deletion
Page 95 of the Mitsubishi Electronics P96 user manual — PAR-F27MEA
Page 95 · click to enlarge
Page 95

[ IV Remote Controller ]

(A) To delete group settings (B) To delete interlock settings

If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will appear in the unit type display window. In this case, repeat the steps above.

will be displayed in the room temperature display window. - If a transmission error occurs, the selected setting will not be deleted, and the display will appear as shown below. In this case, repeat the steps above.

will be displayed in the room temperature display window.

To go back to the normal display, follow step . 10

(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controller

(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller. Refer to (B) Interlock Settings under section 1 Group Settings/Interlock Settings for operation procedures. Set the address as shown below.

(A) To make group settings Interlocked unit address display window...Remote controller address Indoor unit address display window The address of the indoor unit to be controlled with the remote controller

(B) To make interlock settings Interlocked unit address display window...LOSSNAY address Indoor unit address display window The address of the indoor unit to be interlocked with the LOSSNAY

2. Remote controller function selection via the ME remote controller

In the remote controller function selection mode, the settings for four types of functions can be made or changed as necessary.

1. Skip-Auto-Mode setting The automatic operation mode that is supported by some simultaneous cooling/heating type units can be made unselectable via the ME remote controller.
2. Operation mode display selection mode (Display or non-display of COOL/HEAT during automatic operation mode) When the automatic operation mode is selected, the indoor unit will automatically perform a cooling or heating operation based on the room temperature. In this case, or will appear on the remote controller display. This setting can be changed so that only will appear on the display.
3. Room temperature display selection mode (Display or non-display of room temperature) Although the suction temperature is normally displayed on the remote controller, the setting can be changed so that it will not appear on the remote controller.
4. Narrowed preset temperature range mode The default temperature ranges are 19 C to 30 C in the cooling/dry mode and 17 C to 28 C in the heating mode and 19 C to 28 C in the auto mode. By changing these ranges (raising the lower limit for the cooling/dry mode and lowering the upper limit for the heating mode), energy can be saved.

NOTE

When making the temperature range setting on the simultaneous cooling/heating type units that supports the automatic operation mode to save on energy consumption, enable the Skip-Auto-Mode setting to make the automatic operation mode unselectable. If the automatic operation mode is selected, the energy-saving function may not work properly.

When connected to the air conditioning units that do not support the automatic operation mode, the setting for the Skip-Auto-Mode, restricted preset temperature range mode (AUTO), and operation mode display selection mode are invalid. If an attempt is made to change the preset temperature range, “LIMIT TEMP.” appears on the display.

[Function selection mode sequence on the remote controller] Normal display

Remote controller function selection mode

*2 Temperature range setting mode (AUTO)

TEMP.

ON/OFF

: Press and hold the [CHECK] and [ ] buttons simultaneously for two seconds. : [SET TEMP. ( ) ] button : [SET TEMP. ( ) ] button

Operation mode display selection mode (Display or non-display of the automatic mode)

CLOCKĺONĺOFF

FILTER

CHECK TEST

Restricted preset temperature range mode (Cooling)

PAR-F27MEA

TIMER SET

Restricted preset temperature range mode (Heating)

Room temperature display selection mode *1 : Skip-Auto-Mode is enabled *2 : Skip-Auto-Mode is disabled

Show 6 more labels / short text on this page
(Displayed alternately) · <Deletion error> · Skip-Auto-Mode setting · [Normal display] · *1 *1 · *2
Page 96 of the Mitsubishi Electronics P96 user manual — ˚C ˚C
Page 96 · click to enlarge
Page 96

[ IV Remote Controller ]

[Operation Procedures] 1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display). 2. Press buttons [CHECK] and [ ] simultaneously for 2 seconds to go into the “Skip-Auto-Mode setting.” under the remote controller function selection mode. Press button [SET TEMP. ( )] or [SET TEMP. ( )] to go into the other four modes under the remote controller function selection mode.

Skip-Auto-Mode setting (Making the automatic operation mode unselectable)

This setting is valid only when the controller is connected to the simultaneous cooling/heating type air conditioning units that support the automatic operation mode.

“ ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches between “ON” and “OFF.”

[TIMER SET ( ) (( ))] button

When set to “ON,” the automatic operation mode is available for selection in the function selection mode. When set to “OFF,” the automatic operation mode is not available for selection in the function selection mode, and an automatic operation cannot be performed. (The automatic operation mode is skipped in the function selection mode sequence.)

Operation mode display selection mode (Changing the type of display that appears during the automatic mode operation)

When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.

will blink, and either “ON”or “OFF” will light up. Press button [TIMER SET ( ) or ( )] in this state to switch between “ON” and “OFF.”

[TIMER SET ( ) (( ))] button

When it is set to ON, will appear on the display during automatic operation mode. When it is set to OFF, only will appear on the display during automatic operation mode.

Restricted preset temperature range mode (The range of preset temperature can be changed.)

1. Temperature range setting for the cooling/dry mode

will light up in the display window, and the temperature range for the cooling/dry mode will appear on the display.

[Lower limit temperature]: Appears in the preset temperature display window [Upper limit temperature: Appears in the time display window

Switch between the Lower and Upper limit temperature setting by pressing the [CLOCK-ON-OFF] button. The selected temperature setting blinks.

[TIMER SET ( ) (( ))] button

[The left figure shows the display that appears when the current temperature range setting is between 19 C and 30 C in the Cool/Dry mode, and the lower limit temperature is selected to be set.]

Press button [TIMER SET ( ) or ( )] to set the lower limit temperature to the desired temperature. 4

[Settable range for the lower limit temperature] : 19 C 30 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 30 C 19 C (Settable up to the lower limit temperature that is shown on the display)

2. Temperature range setting for heating

“ ” and the settable temperature range for heating appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.

[Settable range for the lower limit temperature] : 17 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 17 C (Settable up to the lower limit temperature that is shown on the display)

3. Temperature range setting for the automatic mode

When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.

“ ” and the temperature range for the automatic operation mode appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range. 5 4

[Settable range for the lower limit temperature] : 19 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 19 C (Settable up to the lower limit temperature that is shown on the display)

Room temperature display selection mode (Switching between the display or non-display of room temperature on the controller)

“ 88 C ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches between “ON” and “OFF.”

˚C ˚C

[TIMER SET ( ) (( ))] button

When set to “ON,” room temperature always appears on the display during operation. When set to “OFF,” room temperature does not appear on the display during operation.

Page 97 of the Mitsubishi Electronics P96 user manual — [3] Interlock Settings via the MA Remote Controller
Page 97 · click to enlarge
Page 97

[ IV Remote Controller ]

[3] Interlock Settings via the MA Remote Controller

1. LOSSNAY interlock setting (Make this setting only when making an interlock settings between the LOSSNAY units and the Freeplan model of units.)

Make this setting only when necessary.

Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to search and delete registered information.

In the following example, the address of the indoor unit is 05 and the address of the LOSSNAY unit is 30.

Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display window on the remote controller must look like the figure below to proceed to step .

2 Press and hold the [FILTER] and [ ] buttons simultaneously for two seconds to perform a search for the LOSSNAY that is interlocked with the indoor unit to which the remote controller is connected.

Search result - The indoor unit address and the interlocked LOSSNAY address will appear alternately.

- Without interlocked LOSSNAY settings

If no settings are necessary, exit the window by pressing and holding the [FILTER] and [ ] buttons simultaneously for 2 seconds. Go to step 1. Registration Procedures to make the interlock settings with LOSSNAY units, or go to step 2. Search Procedures to search for a particular LOSSNAY unit. Go to step 3. Deletion Procedures to delete any LOSSNAY settings.

< 1. Registration Procedures >

To interlock an indoor unit with a LOSSNAY unit, press the [ TEMP. ( ) or ( )] button on the remote controller that is connected to the indoor unit, and select its address (01 to 50). Press the [ CLOCK ( ) or ( )] button to select the address of the LOSSNAY to be interlocked (01 to 50).

Indoor unit address LOSSNAY address

Press the [TEST] button to register the address of the selected indoor unit and the interlocked LOSSNAY unit. - Registration completed The registered indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.

- Registration error If the registration fails, the indoor unit address and the LOSSNAY address will be displayed alternately.

Registration cannot be completed: The selected unit address does not have a corresponding indoor unit or a LOSSNAY unit. Registration cannot be completed: Another LOSSNAY has already been interlocked with the selected indoor unit.

[Operation Procedures]

Page 98 of the Mitsubishi Electronics P96 user manual — [4] Using the built-in Temperature Sensor on the Remote Controller
Page 98 · click to enlarge
Page 98

[ IV Remote Controller ]

< 2. Search Procedures >

To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it.

Press the [ MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit. - Search completed (With a LOSSNAY connection) The indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.

- Search completed (No interlocked settings with a LOSSNAY exist.)

- The selected address does not have a corresponding indoor unit.

< 3. Deletion Procedures >

Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller that is connected to the indoor unit. Find the address of the LOSSNAY to be deleted (See section 2. Search Procedures. ), and bring up the result of the search for both the indoor unit and LOSSNAY on the display.

Press the [ ON/OFF] button twice to delete the address of the LOSSNAY unit that is interlocked with the selected indoor unit. - Registration completed The indoor unit address and , and the interlocked LOSSNAY address and will appear alternately.

-Deletion error If the deletion fails

[4] Using the built-in Temperature Sensor on the Remote Controller

1. Selecting the position of temperature detection (Factory setting: SW1-1 on the controller board on the indoor unit is set to OFF.) To use the built-in sensor on the remote controller, set the SW1-1 on the controller board on the indoor unit to ON. Œ Some models of remote controllers are not equipped with a built-in temperature sensor. Use the built-in temperature sensor

on the indoor unit instead. ŒWhen using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.

Page 99 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 99 · click to enlarge
Page 99
Page 99 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 100 of the Mitsubishi Electronics P96 user manual — V Electrical Wiring Diagram
Page 100 · click to enlarge
Page 100

V Electrical Wiring Diagram

[1] Electrical Wiring Diagram of the Outdoor Unit 93 [2] Electrical Wiring Diagram of the BC Controller 96 [3] Electrical Wiring Diagram of Transmission Booster 105

Page 101 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 101 · click to enlarge
Page 101
Page 101 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 102 of the Mitsubishi Electronics P96 user manual — (1) PURY-P72THMU-A
Page 102 · click to enlarge
Page 102

[ V Electrical Wiring Diagram ]

V Electrical Wiring Diagram [1] Electrical Wiring Diagram of the Outdoor Unit

(1) PURY-P72THMU-A

Mitsubishi Electronics P96 — (1) PURY-P72THMU-A diagram (page 102)
Fig. 59

4 5 2 1 OFF 4 3 2 1 1 2 4 3 1

*3.Refer to the Data book for connecting input/output signal connectors.

*4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant

*1.Single-dotted lines indicate wiring not supplied with the unit.

*5.Faston terminals have a locking function.Make sure the terminals

Crankcase heater(for heating the compressor) Current sensor(AC) Magnetic relay(inverter main circuit) Low pressure Discharge pressure

Page 103 of the Mitsubishi Electronics P96 user manual — (2) PURY-P96, P120THMU-A
Page 103 · click to enlarge
Page 103

[ V Electrical Wiring Diagram ]

(2) PURY-P96, P120THMU-A

Mitsubishi Electronics P96 — (2) PURY-P96, P120THMU-A diagram (page 103)
Fig. 60

2 1 1 1 3 1 1 2 4 3 2

*3.Refer to the Data book for connecting input/output signal connectors.

*4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant

*1.Single-dotted lines indicate wiring not supplied with the unit.

*5.Faston terminals have a locking function.Make sure the terminals

Crankcase heater(for heating the compressor) Current sensor(AC) Magnetic relay(inverter main circuit) Low pressure

Page 104 of the Mitsubishi Electronics P96 user manual — CT12,22,3
Page 104 · click to enlarge
Page 104

[ V Electrical Wiring Diagram ]

(3) PURY-P72, P96, P120YHMU-A

TH6

TH7

TH3

TH5

63LS

63HS1

TH4

Z25

Z24

TP2

1 CNTYP2

CNTYP5

CNTYP4

CN213

CN212

CN990

CN202

CN201

CN211

CNIT

LED1:Power supply to

TP1

S

TB7

M2

P 63H1

CNS2

M1

LED1

M2

ON OFF

SW1 10

CNS2

TB3

M1

ON

OFF

CN102

ON

OFF

SW2 10

1 SWU2

ON

SW3 10

CN40

CN41

3 2 1 1 2 2

CN4

LED1

OFF

ON OFF

SW4 10

CN102

CN332

CN2

LED2:CPU in operation

CN04

ON

OFF

SW5

LED3:Lit when powered

1 1 CN3D

CNT02

CN3S

CN801

SWU1

CN3N

G

CN3K

CNT01

AC250V

3.15A T

CPU power supply circuit

F01

ZNR01

CNDC

CN72

U

CNAC

CNAC2

CN502

CN503

CN504

CN506

CN507

CN508

CN509

CN510

CH11

SV9

SV2

CNTYP

SC-W

CT22

CN4 3 CN6

LED1:Normal operation(Lit)

C1 CN2

SC-V

W

2 CN5

CN21

CN22

THBOX

LED1:Normal

CN5V

RSH1

3~ MS

LED2:Error

U

1 CN4

LED3:CPU in

SC-U

CT12

THHS

SC-L2

CN18V

ZNR1

IPM

U

SC-L3

R5

SC-P1

IGBT

SC-L1

R630

R631

CT3

R1

FT-P

FT-N

R31

R33 R30

R34 R35

DC700V

DCL

SC-P2

P

N

+ - + +

+

8 CNTR1

F01

4A T

CNVDC

CNINV

CN1

R32

U

W

M

F5

600V 3A F

CNTR2

CNTR3

AC250V

6.3A T

Z5

600V 3A F

CN5

D1 R5

U

CN6

F4

TB23

T02

T03

R4

R6 C17

TB22

L3 L2 L1

*1.Single-dotted lines indicate wiring not supplied with the unit. *2.Dot-dash lines indicate the control box boundaries. *3.Refer to the Data book for connecting input/output signal connectors. *4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant system together.

CN4

TB21

CN06

CN07

TB1

CN1B

G G

Z4

U

F3

F2

F1

DSA

R3

R2

R1

CN2

F1,F2,F3

AC250V

6.3A T

Z3

U

Z2

U

Z1

U

CN1A

*5.Faston terminals have a locking function. Make sure the terminals are securely locked

FT-P and FT-N on INV Board has dropped

High pressure protection for the

For opening/closing the bypass

Heat exchanger capacity control

For opening/closing the bypass

For opening/closing the bypass

Control box internal temperature

Crankcase heater(for heating the compressor) Current sensor(AC) Magnetic relay(inverter main circuit) Low pressure Discharge pressure

Heat exchanger low pressure

ACC inlet pipe temperature

in place after insertion. Press the tab

*6.Control box houses high-voltage parts. Before inspecting the inside of the

and confirm that the voltage between

Heat exchanger inlet pipe

on the terminals to removed them.

control box,turn off the power,keep

circuit under the O/S

Liquid pipe temperature Thermistor

the unit off for at least 10 minutes,

*7.Difference of appliance

P72 *7 do not exist

to DC20V or less.

CT12,22,3

72C 63LS 63HS1

THBOX

Z24,25 THHS

63H1

CH11

DCL

SV2

SV9

TB3 TB1

TB7

TH6 TH5 TH4 TH3

TH7

Show 159 more labels / short text on this page
t° · t° · t° · t° · t° · red · Indoor/Outdoor · transmission line · Central control · transmission · black · green · green F4 · red · red · cable · red · CNIT yellow · yellow · Display · setting CN51 12V · TB7 Power · connector · selecting · Indoor/Outdoor · transmission · *4 · cable · Function · setting · Compressor ON/OFF output · M-NET Board · Error detection output · red · M-NET power · supply circuit · blue · Control Board · red · yellow · Unit address · blue · 1's digit · setting · *3 · 1 Power failure · detection circuit · 10's digit · yellow · *3 · pink · red · red · black · blue · green · red · black · blue · yellow · SV1a · 21S4a · SV5b · SV4a · SV4c · SV5c · SV4b · *7 · SV4d · 3 Noise · black · black · black · white · white · (Compressor) · blue · t° · operation · yellow · / Error(Blink) · Motor · operation · red · INV Board red · red · red · blue · t° · *5 · black · black · FAN Board · red · *6 · red · white · black · red · (Heat exchanger) · Fan motor · 3~ · white · black · Ground · Diode · Bridge · red · black white red · (Transformer) · (Transformer) · red · yellow · Power Source · Transformer Box · Filter · 60Hz · blue · + · 3~ · purple · purple · black · white · red · Indoor/Outdoor transmission · Central control transmission · Discharge pipe temperature · Discharge suction bypass · 4-way valve(Cooling/Heating switching) · IGBT temperature · Explanation · OA temperature · outdoor unit Pressure · Power supply · temperature · Function setting connector · bypass · Model name Appliance · <Symbol explanation> · circuit · circuit · cable · cable · P96/P120 *7 exist · DC reactor · switch · Pressure · sensor · Solenoid · Terminal · valve · block · Symbol · SV4a,b,c,d · 21S4a · SV1a · SV5b · SV5c
Page 105 of the Mitsubishi Electronics P96 user manual — 1 ON
Page 105 · click to enlarge
Page 105

[ V Electrical Wiring Diagram ]

[2] Electrical Wiring Diagram of the BC Controller

(1) CMB-P104NU-G model

Fuse AC250V 6.3A F F01 Terminal T1~4

Expansion valve Thermistor sensor Transformer Name Symbol

Terminal block (for power source) TB01

Terminal block (for Transmission) TB02

of switch on CONT.B

2.The initial set values

terminal block.

are as follows.

TH11,12,15,16

line to it.

SW1:0

SW2:0

CONT.B

LEV1,3

TR

BREAKER(15A)

SV1B

SV1A

SV1C

SV2B

SV2A

SV2C

SV3B

SV3A

SV3C

SV4B 11

SV4A

SV4C

SVM1

TO NEXT INDOOR UNIT

PULL BOX

FUSE(15A)

~208V-230V 60Hz POWER SUPPLY

T1

T3

T4

T2 1

1

TB02 TR

M1 M2 S(SHIELD)

G

TB01

G

CN26

ZNR02 ZNR01

3 5 1 CN12

250VAC 6.3A F

F01

DSA

CN05

1 2 3 4 5 6

LEV1

3 CN02

1 2 3 2 1

SW1 SW2

SW5

CN03

SW4

1 2 3 4 5 6

1 ON

ON

OFF

CN07

OFF

LEV3

CNP3

CN13

CN10

CN11

CONT.B

CNP1

PS1

PS3

TH11

TH12

TH15

TH16

Show 19 more labels / short text on this page
BC controller · PS1,3 Pressure sensor · Solenoid valve SV1~4A,B,C · SVM1 Solenoid valve · Never connect power · Circuit · board · (Symbol explanation) · Indoor/outdoor (heat source) · Transmission Line · CN29(Green) · X21 CN36(Green) · CN27(Red) · CN28(Blue) · (Red) CNTR · (Red) (Yellow) · (Yellow) · (Red) · (Black)
Page 106 of the Mitsubishi Electronics P96 user manual — CONT.B
Page 106 · click to enlarge
Page 106

[ V Electrical Wiring Diagram ]

(2) CMB-P105,106NU-G models

F01 Fuse AC250V 6.3A F

2.The initial set values

of switch on CONT.B

terminal block.

are as follows.

TH11,12,15,16

line to it.

SW1:0

SW2:0

LEV1,3

CONT.B

PS1,3

TR

CMB-P106NU-G ONLY F01

SV1C SV1A SV1B

SV2B

SV2C SV2A

SV3A SV3B

SV3C

SV4B

SV4C SV4A

SV5B

SV5A

SV5C

SV6C SV6A SV6B

SVM1

T1

T3

T4

T5

T6

1 T2

1

TB02

S(SHIELD)

M1 M2

TO NEXT INDOOR UNIT

BREAKER(15A)

3 CNTR

CN26

FUSE(15A)

PULL BOX

ZNR02

G G

POWER SUPPLY

TB01

1 5 3 6 5 4 3 2 1

250VAC 6.3A F

ZNR01

CN12

TR

CN02 3

1 2 3 2 1 CN03

DSA

SW2 SW1

SW5

SW4

CN05 CN07

LEV3 LEV1

ON

OFF

ON

OFF

3 CNP3

CN13

CN10

CN11

6 5 4 3 2 1

CONT.B

CNP1

PS1

PS3

TH11

TH12

TH15

TH16

Show 31 more labels / short text on this page
BC controller · Thermistor sensor · (for power source) · (for Transmission) · Expansion valve · Pressure sensor · SV1~6A,B,C Solenoid valve · Solenoid valve SVM1 · TB01 Terminal block · TB02 Terminal block · Symbol Name · Transformer · T1~6 Terminal · Never connect power · Circuit · board · (Symbol explanation) · Indoor/outdoor (heat source) · Transmission line · CN28(Blue) · CN29(Green) · CN30(Black) · CN31(Yellow) · CN36(Green) · CN27(Red) · (Red) · ~208V-230V 60Hz · (Yellow) · (Red) (Yellow) · (Red) · (Black)
Page 107 of the Mitsubishi Electronics P96 user manual — ON
Page 107 · click to enlarge
Page 107

[ V Electrical Wiring Diagram ]

(3) CMB-P108,1010NU-G models

REL.B

4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

CN52

SV7B

4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

3 3 3 1 5 7 1 3 5 7 1 3 5 7 1 3 7 5

SV7A

T10 T9 T8 T7

16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13

SV7C

7 6 5 4 3 2 1

CN32

SV8B

SV8A

SV8C

CMB-P1010NU-G ONLY

CMB-P1010NU-G ONLY

6 5 4 3 2 1

SV9B

SV9A

SV9C

CN53

SV10B

SV10A

SV10C

POWER SUPPLY

SVM1

CN39

FUSE(15A) BREAKER(15A)

SV1B

SV1A

SV1C

SV2C SV2A SV2B

SV3C SV3A SV3B

SV4C SV4A SV4B

SV5B

SV5A

SV5C

SV6C SV6A SV6B

TO NEXT INDOOR UNIT

PULL BOX

T1

T3

T4

T5

T6

T2

TB02

S(SHIELD)

M1 M2

G G

L1 TB01

of switch on CONT.B

1 CNTR

1 3 CN38 CN26

2.The initial set values

are as follows.

ZNR01 ZNR02

SW1:0

SW2:0

250VAC 6.3A F

CN12

CN50

F01

DSA

7 6 5 4 3 2 1 2 3 4 5 6 7

terminal block.

6 5 4 3 2 1 2 3 4 5 6

line to it.

CN51

CN05 CN07

6 5 4 3 2 1 6 5 4 3 2 1

TR

1 2 3 2 1 CN03 CN02

LEV3 LEV1

SW1 SW2

1 8 ON

SW4

SW5

board BC controller REL.B Relay

Fuse AC250V 6.3A F F01

ON

OFF

OFF

3 CNP3

CN13

CN10

CN11

CONT.B

CNP1

TH11,12,15,16

TH11

TH12

TH15

TH16

SV1~10A,B,C

PS1

PS3

LEV1,3

CONT.B

PS1,3

TR

Show 32 more labels / short text on this page
CN33(Red) · CN34(Black) · CN35(Blue) · ~208V-230V 60Hz · Indoor/outdoor (heat source) · Transmission line · CN27(Red) · CN28(Blue) · CN29(Green) · CN30(Black) · CN31(Yellow) · 1 CN36(Green) · (Red) · Never connect power · (Red) (Yellow) · (Yellow) · (for power source) · Thermistor sensor · Expansion valve · Pressure sensor · (for Transmission) · TB01 Terminal block · TB02 Terminal block · Solenoid valve · Solenoid valve SVM1 · (Red) · Symbol Name · Transformer · (Black) · T1~10 Terminal · (Symbol explanation) · Circuit
Page 108 of the Mitsubishi Electronics P96 user manual — SW1:0
Page 108 · click to enlarge
Page 108

[ V Electrical Wiring Diagram ]

(4) CMB-P1013,1016NU-G models

F01 Fuse AC250V 6.3A F

CMB-P1016NU-G ONLY

Expansion valve Thermistor sensor Transformer Name Symbol

(for power source) TB01

Terminal block (for Transmission) TB02

SV11B

SV11A

SV11C

SV12B

SV12A

SV12C

SV13B

SV13A

SV13C

SV14B

SV14A

SV14C

SV15B

SV15A

SV15C

SV16B

SV16A

SV16C

SVM1 2

Relay REL.B

T11

T12

T13

T14

T15

T16

TH11,12,15,16

SV1~16A,B,C

REL.B

LEV1,3

CONT.B

TR

3 X41 1

7 5 3 1 7 5 3 1 7 5 3 1 CN40

CN42

CNVCC2 3 1 2

CN39

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

SV7A SV7B

7 5 3 1 3 3

T10 T9 T8 T7

16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13

SV7C

CN32

SV8B SV8A SV8C

SV9B SV9A SV9C

SV10B

CNOUT2

CNOUT4

SV10A

SV10C

8 7 6 5 4 3 2 1

POWER SUPPLY

SV1B

SV1A

SV1C

SV2C SV2A SV2B

SV3C SV3A SV3B

SV4C SV4A SV4B

SV5B

SV5A

SV5C

SV6B

SV6A

SV6C

~208V-230V

FUSE(15A) BREAKER(15A)

T1

T2

T3

T4

T5

T6

1

INDOOR UNIT

PULL BOX

TO NEXT

TB01

G G

TB02

S(SHIELD)

M1 M2

1 CNTR

CN38 CN26

ZNR01 ZNR02

1 3 5 CN12

CNOUT1

CNOUT3

F01

250VAC 6.3A F

DSA

1 2 3 2 1 CN03 CN02

TR

SW1 SW2

SW4

SW5

2.The initial set values

of switch on CONT.B

CN07 CN05

6 5 4 3 2 1 6 5 4 3 2 1

LEV1 LEV3

1 ON

OFF

ON

OFF

terminal block.

are as follows.

2 1 CNVCC1

3 CNP3

CN13

CN10

CN11

line to it.

SW1:0

SW2:0

CONT.B

CNP1

TH11

TH12

TH15

TH16

PS1

PS3

Show 32 more labels / short text on this page
BC controller Circuit · PS1,3 Pressure sensor · Terminal block · Solenoid valve · Solenoid valve SVM1 · Terminal T1~16 · (Symbol explanation) · board · (Yellow) · CN41(Green) · CN43(Red) · CN44(Yellow) · CN45(Green) · (Blue) · CN33(Red) · CN34(Black) · CN35(Blue) · Indoor/outdoor (heat source) · 60Hz · Transmission line · CN27(Red) · CN28(Blue) · CN29(Green) · CN30(Black) · CN31(Yellow) · CN36(Green) · (Red) · Never connect power · (Blue) (Yellow) · (Yellow) (Red) · (Red) · (Black)
Page 109 of the Mitsubishi Electronics P96 user manual — SW4
Page 109 · click to enlarge
Page 109

[ V Electrical Wiring Diagram ]

(5) CMB-P108,1010NU-GA models

REL.B

SV7B

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

5 7 1 7 5 1 7 5 3 1 7 5 1 3 3 3

2.The initial set values

of switch on CONT.B

SV7A

T7 T8 T9 T10

13 14 15 10 11 12 9 7 8 6 5 4 4 8 7 6 5 12 11 10 9 15 14 13 16 16

terminal block.

are as follows.

SV7C

CN32

CN52

line to it.

SV8B

SW1:0

SW2:0

SV8A

1 2 3 4 5 6 7

SV8C

CMB-P1010NU-GA ONLY

SV9B

SV9A

F01 Fuse AC250V 6.3A F T1~10 Terminal Solenoid valve SVM1,2

SV9C

6 5 4 3 2 1 CN53

Expansion valve Thermistor sensor Transformer Name Symbol

(for power source) TB01

SV10B

Relay REL.B

SV10A

SV10C

TH11,12,15,16

CN39

SV1~10A,B,C

1 2 3 4 4 1 2 3

SVM1 SVM2

LEV1~3

CONT.B

60Hz ~208V-230V POWER SUPPLY

TR

BREAKER(15A)

SV1C SV1A SV1B

SV2B

SV2A

SV2C

SV3B

SV3A

SV3C

SV4B

SV4A

SV4C

SV5A SV5B

SV5C

SV6B

SV6A

SV6C

TO NEXT INDOOR UNIT

PULL BOX

FUSE(15A)

T1

T2

T3

T4

T5

T6

TB02

S(SHIELD)

M1 M2

G

TB01

G

CN26 CN38

ZNR01 ZNR02

250VAC 6.3A F

7 6 5 4 3 2 1 2 3 4 5 6 7 CN50

F01

DSA

CN12

6 5 4 3 2 1 2 3 4 5 6 CN51

1 2 3 4 5 6 1 2 3 4 5 6

CN06 CN05 CN07

LEV1 LEV3

TR

1 2 3 2 1

CN02

SW2 SW1

1 2 3 4 5 6

SW4

SW5

LEV2

ON

OFF

ON

OFF

CNP3

CN13

CN10

CN11

CONT.B

CNP1

TH11

TH12

TH15

TH16

PS1

PS3

Show 26 more labels / short text on this page
Never connect power · CN33(Red) · BC controller Circuit · CN34(Black) · (for Transmission) TB02 · PS1,3 Pressure sensor · Solenoid valve · Terminal block · Terminal block · CN35(Blue) · (Symbol explanation) · board · Indoor/outdoor (heat source) · Transmission line · CN27(Red) · CN28(Blue) · CN29(Green) · CN30(Black) · CN31(Yellow) · CN36(Green) · CN46(Yellow) · (Red) CNTR · (Blue) (Red) (Yellow) · (Yellow) CN03 · (Red) · (Black)
Page 110 of the Mitsubishi Electronics P96 user manual — LEV3
Page 110 · click to enlarge
Page 110

[ V Electrical Wiring Diagram ]

(6) CMB-P1013,1016NU-GA models

F01 Fuse AC250V 6.3A F

Expansion valve Thermistor sensor Transformer Name Symbol

(for power source) TB01

Relay REL.B

T1~16 Terminal Solenoid valve

SV11B

SV11A

SV11C

SV12B

SV12A

SV12C

SV13B

SV13A

SV13C

SV14B

SV14A

SV14C

SV15B

SV15A

SV15C

SV16B

SV16A

SV16C

SVM1

SVM2

T11

T12

T13

T14

T15

T16

TH11,12,15,16

SV1~16A,B,C

LEV1~3

CONT.B

SVM1,2

TR

REL.B

CNVCC2 3 1 2

CN42

CN39

SV7A SV7B

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

7 5 3 1 3 3

T10 T9 T8 T7

16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13

SV7C

CN32

7 5 3 1 7 5 3 1 7 5 3 1

SV8B SV8A SV8C

SV9B SV9A SV9C

SV10B SV10A SV10C

CNOUT2

CNOUT4

8 7 6 5 4 3 2 1

POWER SUPPLY

~208V-230V

SV1B

SV1A

SV1C

SV2C SV2A SV2B

SV3C SV3A SV3B

SV4C SV4A SV4B

SV5B

SV5A

SV5C

SV6B

SV6A

SV6C

FUSE(15A) BREAKER(15A)

T1

T2

T3

T4

T5

T6

1

PULL BOX

INDOOR UNIT TO NEXT

TB02

S(SHIELD)

M1 M2

G G

L2 L1 TB01 1 3 5 CN12

CN38 CN26

CNTR

ZNR01 ZNR02 CN06

CNOUT1

CNOUT3

F01

250VAC 6.3A F

block.Never connect power line

2.The initial set values of switch

on CONT.B are as follows.

TR

1 2 3 2 1 CN02

SW1 SW2

SW4

SW5

1 ON

OFF

ON

OFF

6 5 4 3 2 1

3 CNP3

CN13

CN10

CN11

CN07

CN05

LEV1

SW1:0

SW2:0

CONT.B

6 5 4 3 2 1

5 4 3 2 1

to it.

LEV3

LEV2

TH11

TH12

TH15

TH16

PS1

PS3

Show 35 more labels / short text on this page
BC controller Circuit · (for Transmission) TB02 · PS1,3 Pressure sensor · Terminal block · Terminal block · Solenoid valve · CMB-P1016NU-GA ONLY (Red) · (Symbol explanation) · board · (Blue) · CN41(Green) · CN45(Green) · CN40 (Yellow) · CN43(Red) · CN44(Yellow) · CN33(Red) · CN34(Black) · CN35(Blue) · Indoor/outdoor (heat source) · 60Hz · Transmission line · CN29(Green) · CN30(Black) · CN31(Yellow) · 1 CN36(Green) · 1 CN46(Yellow) · CN27(Red) · CN28(Blue) · (Red) · DSA (Blue) · (Yellow) CN03 · CNP1 (Blue) CNVCC1 · (Yellow) · (Red) · (Black)
Page 111 of the Mitsubishi Electronics P96 user manual — OFF
Page 111 · click to enlarge
Page 111

[ V Electrical Wiring Diagram ]

(7) CMB-P104NU-GB model

Fuse AC250V 6.3A F F01 Terminal T1~4

Expansion valve Thermistor sensor Transformer Name Symbol

(for power source) TB01

2.The initial set values

of switch on CONT.B

terminal block.

are as follows.

line to it.

SW1:0

SW2:0

TH12,15

CONT.B

LEV3

TR

BREAKER(15A)

SV1B

SV1A

SV1C

SV2B

SV2A

SV2C

SV3B

SV3A

SV3C

SV4B 11

SV4A

SV4C

TO NEXT INDOOR UNIT

PULL BOX

G G FUSE(15A)

POWER SUPPLY

T1

T2

T3

T4

~208V-230V

1

M1 M2 S(SHIELD) TB02

TB01

CN26

CNTR

ZNR02 ZNR01

3 5 1 CN12

250VAC 6.3A F

F01

DSA

TR

CN02

1 2 3 2 1

SW1 SW2

CN03

SW4

SW5

1 ON

1 2 3 4 5 6

OFF

ON

OFF

CN07

LEV3

CN13

CN10

CN11

CONT.B

TH12

TH15

Show 19 more labels / short text on this page
BC controller · (for Transmission) TB02 · Terminal block · Terminal block · Solenoid valve SV1~4A,B,C · (Symbol explanation) · Circuit · board · Never connect power · Indoor/outdoor (heat source) · Transmission Line · 60Hz · CN27(Red) · CN29(Green) · CN28(Blue) · (Red) · (Yellow) · (Yellow) · (Red)
Page 112 of the Mitsubishi Electronics P96 user manual — CN13
Page 112 · click to enlarge
Page 112

[ V Electrical Wiring Diagram ]

(8) CMB-P108NU-GB model

F01 Fuse AC250V 6.3A F Terminal T1~8

Expansion valve Thermistor sensor Transformer Name Symbol

(for power source) TB01

Relay REL.B

SV1~8A,B,C

REL.B

TH12,15

CONT.B

LEV3

TR

SV7B

4 3 2 1 4 3 2 1

4 3 2 1 4 3 2 1

3 1 5 7 1 3 5 7 1 3 5 7 1 3 7 5

SV7A

16 16 13 14 15 9 10 11 12 5 6 7 8 4 4 5 6 8 7 9 12 11 10 15 14 13

T8 T7

SV7C

CN32

CN52

SV8B

SV8A

7 6 5 4 3 2 1 CN39

SV8C

2.The initial set values

of switch on CONT.B

terminal block.

are as follows.

line to it.

SW1:0

SW2:0

G 60Hz ~208V-230V POWER SUPPLY

BREAKER(15A) FUSE(15A)

SV1B

SV1A

SV1C

SV2C SV2A SV2B

SV3C SV3A SV3B

SV4C SV4A SV4B

SV5B

SV5A

SV5C

SV6C SV6A SV6B

TO NEXT INDOOR UNIT

PULL BOX

T1

T2

T3

T4

T5

T6

M1 M2 S(SHIELD) TB02

G

TB01

1 CNTR

1 3 CN38 CN26

ZNR02 ZNR01

F01

250VAC 6.3A F

CN12

CN50

DSA

7 6 5 4 3 2 1

1 2 3 2 1 CN03 CN02

TR

SW1 SW2

1 8 ON

SW4

SW5

ON

OFF

OFF

CN07

6 5 4 3 2 1

CN13

CN10

CN11

LEV3

CONT.B

TH12

TH15

Show 21 more labels / short text on this page
BC controller Circuit · (for Transmission) TB02 · Terminal block · Terminal block · Solenoid valve · (Symbol explanation) · board · CN33(Red) · Never connect power · CN34(Black) · CN35(Blue) · Indoor/outdoor (heat source) · Transmission line · CN27(Red) · CN28(Blue) · CN29(Green) · CN31(Yellow) · CN30(Black) · (Red) · (Yellow) · (Red)
Page 113 of the Mitsubishi Electronics P96 user manual — M
Page 113 · click to enlarge
Page 113

[ V Electrical Wiring Diagram ]

(9) CMB-P1016NU-HB model

(for power source) TB01

Fuse AC250V 6.3A F F01

Terminal T1~T16 Solenoid valve SV1~16A,B,C TB02 Terminal block

SV12B

SV12A

SV12C

SV13B

SV13A

SV13C

SV14B

SV14A

SV14C

SV15B

SV15A

SV15C

SV16B

SV16A

SV16C

SV11B

SV11A

SV11C

(Symbol explanation)

T11

T12

T13

T14

T15

T16

TH12,15

CONT.B REL.B

LEV3

TR

3 1 2 3 CNVCC2

CN40

CN42

4 3 2 1 4 3 2 1

CN39

SV7B

1 2 3 4

7 5 3 1

SV7A

T10 T9 T8 T7

5 4 4 5 16 16 13 14 15 9 10 11 12 6 7 8 6 8 7 9 12 11 10 15 14 13

SV7C

CN32

SV8B

1 2 3 4

1 3 5 7

SV8A

SV8C

REL.B

SV9B

1 2 3 4

4 3 2 1

1 3 5 7

SV9A

SV9C

1 2 3 4

4 3 2 1

1 3 5 7

CNOUT2

CNOUT4

SV10B

SV10A

SV10C

8 7 6 5 4 3 2 1

POWER SUPPLY

~208V-230V

FUSE(15A) BREAKER(15A)

SV1C

SV2C

SV3C

SV4C

SV5C

SV6C

SV1B

SV1A

SV2B

SV2A

SV3B

SV3A

SV4B

SV4A

SV5B

SV5A

SV6B

SV6A

T1

T2

T3

T4

T5

T6

PULL BOX

INDOOR UNIT

TO NEXT

G G

TB01

2.The initial set values of swith on CONT.B are as follows.

M1 M2

CN26

SW1:0

SW2:0

ZNR01 ZNR02

3 1 CN38

U U

250VAC 6.3A F

LD1:CPU in

CNOUT1

CNOUT3

F01

CONT.B

DSA

CN12

block.Never connect power line

TR

1 1 1 3 2 3 2 2 CN02 CN03

8 1 SW1 SW2

1 8 SW5

SW4

SW6

ON

OFF

ON

OFF

ON

OFF

CN10 4

CN11

CN07

TH15 1

to it.

M

TH12

LEV3

Show 33 more labels / short text on this page
Thermister sensor · BC controller · (for Transmission) · Expansion valve · board Relay · Terminal block · Symbol Name · Transformer · Circuit · (Blue) · (Yellow) · CN41(Green) · CN43(Red) · CN44(Yellow) · CN45(Green) · CN33(Red) · CN34(Black) · CN35(Blue) · Transmission line · S(SHIELD)TB02 Indoor/outdoor · 3 CNTR(Red) · 1 CN27(Red) · CN28(Blue) · CN29(Green) · CN30(Black) · CN31(Yellow) · operation · (Yellow) CNVCC1 · (Yellow) · (Blue) · 2 (Red) CN13 · t° · t°
Page 114 of the Mitsubishi Electronics P96 user manual — B
Page 114 · click to enlarge
Page 114

[ V Electrical Wiring Diagram ]

[3] Electrical Wiring Diagram of Transmission Booster

Terminal block for power supply (TB1)

L Red Red Red

250V 5A

100V/200VAC

E

U

U

DSA

CN2 CN1

White Blue Red Red

CN2

1 2 1 2

S

Terminal block 2 for transmission line (TB3) Expanded (indoor unit) side

CN3

CN4

B

CN1 Electronic control board

A

S

Terminal block 1 for transmission line (TB2) Expanded (outdoor unit) side

B

A

Show 31 more labels / short text on this page
Red Red · White · White · Black · Varistor · Green/Yellow · Noise filter · White · White White · White · Black · Red · Varistor · Green · Red · Black · Red · Blue · Stabilized power supply · Black · Grounding · White · Choke coil · White · White · Red · Red · Black · Black · Red · Red
Page 115 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 115 · click to enlarge
Page 115

- 106 -

Page 116 of the Mitsubishi Electronics P96 user manual — [1] Refrigerant Circuit Diagram ...........................................................................................109 [2] Principal Parts and Functions ........................................................................................116
Page 116 · click to enlarge
Page 116

VI Refrigerant Circuit

[1] Refrigerant Circuit Diagram 109 [2] Principal Parts and Functions 116

Page 117 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 117 · click to enlarge
Page 117

- 108 -

Page 118 of the Mitsubishi Electronics P96 user manual — (2) PURY-P96, P120 models
Page 118 · click to enlarge
Page 118

[ VI Refrigerant Circuit ]

VI Refrigerant Circuit [1] Refrigerant Circuit Diagram

1. Outdoor unit (1) PURY-P72 model

Mitsubishi Electronics P96 — 1. Outdoor unit (1) PURY-P72 model diagram (page 118)
Fig. 61 · 1. Outdoor unit (1) PURY-P72 model

(2) PURY-P96, P120 models

Mitsubishi Electronics P96 — (2) PURY-P96, P120 models diagram (page 118)
Fig. 62 · (2) PURY-P96, P120 models
Page 119 of the Mitsubishi Electronics P96 user manual — (3) PURY-P144 model
Page 119 · click to enlarge
Page 119

[ VI Refrigerant Circuit ]

(3) PURY-P144 model

Mitsubishi Electronics P96 — (3) PURY-P144 model diagram (page 119)
Fig. 63 · (3) PURY-P144 model
Page 120 of the Mitsubishi Electronics P96 user manual — (4) PURY-P168 model
Page 120 · click to enlarge
Page 120

[ VI Refrigerant Circuit ]

(4) PURY-P168 model

Mitsubishi Electronics P96 — (4) PURY-P168 model diagram (page 120)
Fig. 64 · (4) PURY-P168 model
Page 121 of the Mitsubishi Electronics P96 user manual — (5) PURY-P192, P216, P240 models
Page 121 · click to enlarge
Page 121

[ VI Refrigerant Circuit ]

(5) PURY-P192, P216, P240 models

Mitsubishi Electronics P96 — (5) PURY-P192, P216, P240 models diagram (page 121)
Fig. 65 · (5) PURY-P192, P216, P240 models
Page 122 of the Mitsubishi Electronics P96 user manual — 2. BC controller (1) CMB-P104 - P1016NU-G
Page 122 · click to enlarge
Page 122

[ VI Refrigerant Circuit ]

2. BC controller (1) CMB-P104 - P1016NU-G

Mitsubishi Electronics P96 — 2. BC controller (1) CMB-P104 - P1016NU-G diagram (page 122)
Fig. 66 · 2. BC controller (1) CMB-P104 - P1016NU-G
Page 123 of the Mitsubishi Electronics P96 user manual — (3) CMB-P104, P108NU-GB (sub)
Page 123 · click to enlarge
Page 123

[ VI Refrigerant Circuit ]

(2) CMB-P108, P1013, P1016NU-GA (main)

Mitsubishi Electronics P96 — (2) CMB-P108, P1013, P1016NU-GA (main) diagram (page 123)
Fig. 67 · (2) CMB-P108, P1013, P1016NU-GA (main)

(3) CMB-P104, P108NU-GB (sub)

Mitsubishi Electronics P96 — (3) CMB-P104, P108NU-GB (sub) diagram (page 123)
Fig. 68 · (3) CMB-P104, P108NU-GB (sub)
Page 124 of the Mitsubishi Electronics P96 user manual — (4) CMB-P1016NU-HB (sub)
Page 124 · click to enlarge
Page 124

[ VI Refrigerant Circuit ]

(4) CMB-P1016NU-HB (sub)

Mitsubishi Electronics P96 — (4) CMB-P1016NU-HB (sub) diagram (page 124)
Fig. 69 · (4) CMB-P1016NU-HB (sub)
Page 125 of the Mitsubishi Electronics P96 user manual — 63LS
Page 125 · click to enlarge
Page 125

[ VI Refrigerant Circuit ]

[2] Principal Parts and Functions

1. Outdoor unit

Symbols (functions) Notes Usage Specifications Check method

Adjusts the amount of circulating refrigerant by adjusting the operat- ing frequency based on the oper- ating pressure data

P72 model Low-pressure shell scroll compressor Wirewound resistance 20°C[68°F] : 0.268ohm (THMU) 0.981ohm (YHMU) P96, P120 models Low-pressure shell scroll compressor Wirewound resistance 20°C[68°F] : 0.161ohm (THMU) 0.583ohm (YHMU)

63HS1 1) Detects high pressure 2) Regulates frequency and pro- vides high-pressure protec- tion

Pressure 0~4.15 MPa [601psi] Vout 0.5~3.5V 0.071V/0.098 MPa [14psi] Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145

63HS1

GND (Black) Vout (White) Vcc (DC5V) (Red)

63LS 1) Detects low pressure 2) Provides low-pressure pro- tection

Pressure 0~1.7 MPa [247psi] Vout 0.5~3.5V 0.173V/0.098 MPa [14psi] Pressure [MPa] =0.566 x Vout [V] - 0.283 Pressure [psi] =(0.566 x Vout [V] - 0.283) x 145

63LS

GND (Black) Vout (White) Vcc (DC5V) (Red)

63H1 1) Detects high pressure 2) Provides high-pressure pro- tection

4.15MPa[601psi] OFF setting

1. Detects discharge air temperature 2) Provides high-pressure protection

Degrees Celsius Resistance check

R = 7.465k 120 R = 4057 R = 7.465

4057 273 t 1 393 1 exp

0°C[32°F] :698kohm 10°C[50°F] :413kohm 20°C[68°F] :250kohm 30°C[86°F] :160kohm 40°C[104°F] :104kohm 50°C[122°F] : 70kohm 60°C[140°F] : 48kohm 70°C[158°F] : 34kohm 80°C[176°F] : 24kohm 90°C[194°F] :17.5kohm 100°C[212°F] :13.0kohm 110°C[230°F] : 9.8kohm

Show 12 more labels / short text on this page
Part name · Com- pressor · MC1 (Comp1) · High pres- sure sensor · Con- nector · Low pres- sure sensor · Con- nector · Pres- sure switch · Thermis- tor · TH4 (Discharge) · 25/120 · t
Page 126 of the Mitsubishi Electronics P96 user manual — SV2
Page 126 · click to enlarge
Page 126

[ VI Refrigerant Circuit ]

Symbols (functions) Notes Usage Specifications Check method

Controls defrosting during heating operation

R = 15k 0 R = 3460 R = 15

t 3460 273 t 1 273 1 exp

1. Detects outdoor air temperature 2) Controls fan operation

0°C[32°F] :15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm

TH5 Fan operated on the 63LS and TH5 values.

TH6 Controls defrosting during heating operation

THHS Inverter heat sink tem- perature

Controls inverter cooling fan based on THHS temperature

R = 17k 50 R = 4016 R = 17

t 4016 273 t 1 323 1 exp

THBOX Control box in- ternal tempera- ture detection

0°C[32°F] :161kohm 10°C[50°F] :97kohm 20°C[68°F] :60kohm 25°C[77°F] :48kohm 30°C[86°F] :39kohm 40°C[104°F] :25kohm

1. High/low pressure bypass at start-up and stopping, and capacity control during lowload operation 2) High-pressure-rise prevention

AC208 - 230V Open while being powered/ closed while not being pow- ered

Continuity check with a tester

SV2

SV4a - SV4d Heat exchanger capacity control

Controls outdoor unit heat ex- changer capacity

SV5b Heat exchanger capacity control

Prevents high-pressure-rise Controls defrost cycle

AC208 - 230V Closed while being powered/ open while not being powered

SV5c Allows the refrigerant to pass through the bypass pipe to pre- vent an accumulation of liquid re- frigerant

AC208 - 230V Open while being powered/ closed while not being pow- ered

SV9 High-pressure-rise prevention AC208 - 230V Open while being powered/ closed while not being pow- ered

Heater CH11 Heats the refrigerant in the com- pressor

Cord heater P72 model 1035 ohm 51W P96, P120 models 928 ohm 57W

21S4a Changeover between heating and cooling

AC208-230V Deadcooling cycle Live: heating cycle

Continuity check with a tester

Show 13 more labels / short text on this page
Part name · Thermis- tor · TH3 (Pipe temperature) · Degrees Celsius · Resistance check · 0/80 · TH7 (Outdoor tem- perature) · Degrees Celsius · 25/120 · Sole- noid valve · SV1a Discharge-suc- tion bypass · Resistance check · 4-way valve
Page 127 of the Mitsubishi Electronics P96 user manual — M
Page 127 · click to enlarge
Page 127

[ VI Refrigerant Circuit ]

2. Indoor Unit

Symbol (functions) Notes Usage Specification Check method

LEV 1) Adjusts superheat at the indoor heat exchanger outlet during cooling 2) Adjusts subcool at the heat exchanger outlet of the indoor unit during cooling

DC12V Opening of stepping motor driving valve 0-(1400) puls- es

Refer to the section "Continuity Test with a Tester". Continuity between white, red, and or- ange. Continuity between yellow, brown, and blue.

M

TH1 (Suction air temperature)

Indoor unit control (Thermo)

R0=15k R0/80=3460 Rt = 15exp{3460( - )} 1 273

1. Indoor unit control (Frost prevention, Hot adjust) 2) LEV control during heating operation (subcool detection).

0°C [32°F]:15kohm 10°C [50°F] :9.7kohm 20°C [68°F]:6.4kohm 25°C [77°F] :5.3kohm 30°C [86°F] :4.3kohm 40°C [104°F] :3.1kohm

TH3 (Gas pipe temperature)

LEV control during cooling op- eration (superheat detection)

TH4 Outdoor air temperature)

Indoor unit control (Thermo)

Temperature sensor (In- door air tem- perature)

Indoor unit control (Thermo)

Show 11 more labels / short text on this page
Part Name · Linear expan- sion valve · White · Red · Orange · Yellow · Brown Blue · Thermis- tor · Resistance check · 1 273+t · TH2 (Pipe temper- ature)
Page 128 of the Mitsubishi Electronics P96 user manual — PS1
Page 128 · click to enlarge
Page 128

[ VI Refrigerant Circuit ]

3. BC controller (1) G type

Part name Symbols (functions)

Part code Usage Specifications Check method

PS1 (High pres- sure side)

1. Detects high pressure 2) LEV control

Pressure 0~4.15 MPa [601psi] Vout 0.5~3.5V 0.071V/0.098 MPa [14psi] Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145

PS1

1. Detects intermediate pressure 2) LEV control

GND (Black) Vout (White) Vcc (DC5V) (Red)

Thermistor TH11 (Liquid inlet tempera- ture)

LEV control (Liquid level control)

R = 15k 0 R = 3460 R = 15

t 3460 273 t 1 273 1 exp

TH12 (Bypass outlet tem- perature)

0°C[32°F]15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm

TH15 (Bypass in- let tempera- ture)

TH16 (Liquid re- frigerant tempera- ture)

SVM1 Opens during cooling and de- frost modes

Continuity check with a tester SV A Provides refrigerant to indoor unit in cooling operation

AC208-230V Open while being powered/ closed while not being pow- ered

SV B Provides refrigerant to indoor unit in heating operation

SV C Provides refrigerant to indoor unit in cooling operation

LEV LEV1 1) Liquid level control 2) Pressure differential con- trol

Same as indoor LEV LEV3

DC12V Opening of a valve driven by a stepping motor 0-2000 pulses

Show 8 more labels / short text on this page
Pressure sensor · Con- nector · PS3 (Intermedi- ate pres- sure) · 0/80 · LEV control (Superheat) · LEV control (Superheat) · LEV control (Subcool) · Solenoid valve
Page 129 of the Mitsubishi Electronics P96 user manual — LEV LEV1 LEV2
Page 129 · click to enlarge
Page 129

[ VI Refrigerant Circuit ]

(2) GA type

Part name Symbols (functions)

Part code Usage Specifications Check method

PS1 (High pres- sure side)

1. Detects high pressure 2) LEV control

Pressure 0~4.15 MPa [601psi] Vout 0.5~3.5V 0.071V/0.098 MPa [14psi] Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145

PS1

1. Detects intermediate pressure 2) LEV control

GND (Black) Vout (White) Vcc (DC5V) (Red)

Thermistor TH11 (Liquid inlet tempera- ture)

LEV control (Liquid level control)

R = 15k 0 R = 3460 R = 15

t 3460 273 t 1 273 1 exp

TH12 (Bypass outlet tem- perature)

0°C[32°F]15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm

TH15 (Bypass in- let tempera- ture)

TH16 (Liquid re- frigerant tempera- ture)

SVM1 Opens during cooling and de- frost modes

Continuity check with a tester SVM2 Pressure differential control

AC208-230V Open while being powered/ closed while not being pow- ered

SV A Provides refrigerant to indoor unit in cooling operation

SV B Provides refrigerant to indoor unit in heating operation

SV C Provides refrigerant to indoor unit in cooling operation

LEV LEV1 LEV2

1. Liquid level control 2) Pressure differential control

DC12V Opening of a valve driven by a stepping motor 0-2000 pulses

Same as indoor LEV

Show 9 more labels / short text on this page
Pressure sensor · Con- nector · PS3 (Intermedi- ate pres- sure) · 0/80 · LEV control (Superheat) · LEV control (Superheat) · LEV control (Subcool) · Solenoid valve · LEV3 Subcool control
Page 130 of the Mitsubishi Electronics P96 user manual — (3) GB type
Page 130 · click to enlarge
Page 130

[ VI Refrigerant Circuit ]

(3) GB type

Part name Symbols (functions)

Part code Usage Specifications Check method

Thermistor TH12 (Bypass outlet tem- perature)

R = 15k 0 R = 3460 R = 15

t 3460 273 t 1 273 1 exp

TH15 (Bypass in- let tempera- ture)

0°C[32°F]15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm

SV A Provides refrigerant to indoor unit in cooling operation

Continuity check with a tester SV B Provides refrigerant to indoor unit in heating operation

AC208-230V Open while being powered/ closed while not being pow- ered

SV C Provides refrigerant to indoor unit in cooling operation

LEV LEV3 Pressure differential control DC12V Opening of a valve driven by a stepping motor 0-2000 pulses

Same as indoor LEV

Show 4 more labels / short text on this page
LEV control (Superheat) · 0/80 · LEV control (Superheat) · Solenoid valve
Page 131 of the Mitsubishi Electronics P96 user manual — (4) HB type
Page 131 · click to enlarge
Page 131

[ VI Refrigerant Circuit ]

(4) HB type

Part name Symbols (functions)

Part code Usage Specifications Check method

Thermistor TH12 (Bypass outlet tem- perature)

R = 15k 0 R = 3460 R = 15

t 3460 273 t 1 273 1 exp

TH15 (Bypass in- let tempera- ture)

0°C[32°F]15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm

SV A Provides refrigerant to indoor unit in cooling operation

Continuity check with a tester SV B Provides refrigerant to indoor unit in heating operation

AC208-230V Open while being powered/ closed while not being pow- ered

SV C Provides refrigerant to indoor unit in cooling operation

LEV LEV3 Pressure differential control DC12V Opening of a valve driven by a stepping motor 0-2000 pulses

Same as indoor LEV

Show 4 more labels / short text on this page
LEV control (Superheat) · 0/80 · LEV control (Superheat) · Solenoid valve
Page 132 of the Mitsubishi Electronics P96 user manual — VII Control
Page 132 · click to enlarge
Page 132

VII Control

[1] Functions and Factory Settings of the Dipswitches 125 [2] Controlling the Outdoor Unit 132 [3] Controlling BC Controller 145 [4] Operation Flow Chart 146

Page 133 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 133 · click to enlarge
Page 133

- 124 -

Page 134 of the Mitsubishi Electronics P96 user manual — A -
Page 134 · click to enlarge
Page 134

[ VII Control ]

VII Control [1] Functions and Factory Settings of the Dipswitches

1. Outdoor unit (1) Control board

Function according to switch setting Switch setting timing

setting Note.2

OFF ON OFF ON OC OS

SWU 1-2 Unit address setting Set to 00 or 51-100 with the dial switch Before power on C C

SW1 1-10 For self-diagnosis/ operation monitoring

Refer to the LED monitor display on the outdoor unit board. Anytime after power on C C

Without connection to the centralized controller

With connection to the centralized con- troller

B B

1 Centralized control switch

2 Deletion of connec- tion information Normal control Deletion Before power on A -

(OC) Storage of IC/ OC error history

(OC) Deletion of IC/ OC error history Anytime after power on (When switched from OFF to ON)

3 Deletion of error his- tory SW

(OS) Storage of OS error history

(OS) Deletion of OS error history

After being energized and while the compressor is stopped

A -

4 Pump down mode Normal control Pump down mode

SW2

5. - 6 -

Anytime af- ter power on (When switched from OFF to ON)

A A

10 minutes after com- pressor startup

7 Forced defrost (Note 3) Normal control Forced defrost starts

8 Defrost timer setting (Note 3) 50 minutes 90 minutes Anytime after power on (When switched from OFF to ON)

B B

9 Target evaporating temperature setting 0°C [32°F] -2°C [28°F] /-4°C [25°F] /-6°C [21°F]

Anytime after power on (When switched from OFF to ON)

A -

10. -

1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made. 3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 132) 4) Target evaporating temperature will change as shown in the table below each time SW2-9 is turned ON and OFF.

SW2-9 OFF → ON → OFF → ON → OFF → ON

0 [32 ] [32 ] [32 ] [25 ] -2 [28 ]

Show 6 more labels / short text on this page
Units that re- · quire switch · Switch Function · Before power on · Target evaporating temperature · [21 ]
Page 135 of the Mitsubishi Electronics P96 user manual — SW4
Page 135 · click to enlarge
Page 135

[ VII Control ]

Function according to switch setting Switch setting timing

setting Note.2

OFF ON OFF ON OC OS

1 Test run modeenabled/disabled SW3-2 disabled SW3-2 enabled Anytime after power on A -
2 Test run modeON/ OFF Stops all ICs Sends a test-run signal to all IC

After power on and when SW3-1 is on.

A -

-10°C [14°F] -5°C [23°F] Anytime after power on

B B

3 Defrost start temper- ature

<P96, P120> -8°C [18°F]

10°C [50°F] 15°C [59°F] Anytime after power on (except during defrost op- eration)

B B

4 Defrost end temper- ature

<P96, P120> 7°C [45°F] <P96, P120> 12°C [54°F]

SW3

5. -

6 Temperature unit setting Centigrade Fahrenheit Anytime after power on C C

7 Target condensing temperature setting for heating

A -

49°C [120°F] 53°C [127°F] -

8. -

9 Model setting (To change the ex- ternal static pressure setting)

Outdoor standard static pressure

Outdoor high static pressure Before being energized

10 Model setting (To change the ex- ternal static pressure setting)

High static pressure 60Pa High static pressure 30Pa Before being energized

1 Enable/disenable high sensible opera- tion

High sensible heat operation mode Before being energized A -

2. -

Anytime after being ener- gized (except during ini- tial startup mode. Automatically cancelled 90 minutes after com- pressor startup)

A -

3 Refrigerant amount adjustment

Refrigerant amount adjust mode

4 Low-noise mode/ step demand switch- ing

Low-noise mode (Note 3) Step demand mode Before being energized

SW4

5. -

Cumulative com- pressor operation time data is re- tained.

Cumulative com- pressor operation time data is delet- ed.

6 Cumulative com- pressor operation time data deletion

Anytime after power on (when the unit is turned on)

7. - 8 - 9 - 10 -

1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made. 3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed A setting of CN3D is required.(page 23)

Show 5 more labels / short text on this page
Units that re- · quire switch · Switch Function · Normal operation mode · Normal operation mode
Page 136 of the Mitsubishi Electronics P96 user manual — SW5
Page 136 · click to enlarge
Page 136

[ VII Control ]

Function according to switch setting Switch setting timing

setting Note.2

OFF ON OFF ON OC OS

1. - 2 - 3 - 4 -

5 Low-noise mode selection

Capacity priority mode(Note 3) Low-noise mode Before being energized A -

SW5

6. - 7 -
8. - 9 - 10 Backup heating Disabled Enabled Anytime after power on A -

1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made. 3) When set to the capacity priority mode and if the following conditions are met, the quiet mode will terminate, and the unit will go back into the normal operation mode. Cooling-only/Cooling-main: Outside temperature is high or high pressure is high. Heating-only/Heating-main: Outside temperature is low or low pressure is low. (page 22)

(2) INV board 1) PURY-P72, P96, P120YHMU-A, PURY-P72THMU-A Functions are switched with the following connector.

Function according to connec-

Enabled Disabled Enabled Disabled

Enabling/disabling the following error detection functions; ACCT sensor failure (5301 Detail No. 115) ACCT sensor circuit failure (5301 Detail No.117) IPM open/ACCT erroneous wiring (5301 Detail No. 119) Detection of ACCT erroneous wiring (5301 Detail No.120)

Error detec- tion disable (No load op- eration is pos- sible.)

Anytime after power on

ŒCN6 short-circuit connector is mated with the mating connector. ŒLeave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the

equipment from damage.

Show 8 more labels / short text on this page
Units that re- · quire switch · Switch Function · tor Setting timing · Connector Function · CN6 short- circuit con- · Error detec- tion enabled · nector
Page 137 of the Mitsubishi Electronics P96 user manual — OFF ON OFF ON
Page 137 · click to enlarge
Page 137

[ VII Control ]

2) PURY-P96, P120THMU-A

Function according to switch

setting Switch setting timing

OFF ON OFF ON

SW1 1 Enabling/disabling the following error detection functions; ACCT/DCCT sensor failure (5301 Detail No. 115, 116) ACCT/DCCT sensor circuit failure (5301 Detail No.117,118) IPM open/Disconnected CNCT2 (5301 Detail No. 119) Detection of erroneous wiring (5301 Detail No.120)

Error detec- tion disable (No load op- eration is pos- sible.)

Anytime after power on

2. -
3. -
4. -
5. -
6. -

ŒAll are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where indicated by "-," which may

be set to a certain setting for a reason. ŒLeave SW1-1 to OFF during normal operation. If it is set to ON, errors cannot be detected and the unit may be damaged.

Switch Function · Error detec- tion enabled

Page 138 of the Mitsubishi Electronics P96 user manual — SW3-1
Page 138 · click to enlarge
Page 138

[ VII Control ]

2. Function of the switch (Indoor unit) (1) Dipswitches 1) SW1,3

Switch Function Function according to switch setting

OFF ON

OFF ON

Room temperature detection position

Built-in sensor on the remote controller

Set to ON (built-in sensor on the remote controller) on All Fresh (PEFY-VMH-F) model units

Filter check reminder time setting

Always set to OFF on PKFY-AM model units

SW1

Always on while in the heating mode

Fan speed setting for Heating Thermo-OFF Very Low Low

Forced heating operation at OA temp of 5 C or below

Applicable to All Fresh model units (PEFY-VMH-F) only

According to the SW1-7 setting

Fan speed setting for Heating Thermo-OFF

Applicable to All Fresh model units (PEFY-VMH-F) only

While the unit is stopped (Remote controller OFF)

Self-recovery after power failure

Always set to OFF on PKFY-VAM model units

SW3

Vane angle limit setting for cooling operation

Always set to Downblow B or C on PKFY-VAM model units

Automatic LEV value conversion function

Heating 4 C[7.2 F] up

Set to OFF on floor-standing (PFFY) type units

SHm setting 2 The setting depends on the model and type.

The setting depends on the model and type.

SCm setting 10 15

Note 2. If both SW1-7 and SW1-8 are set to ON, the fan remains stopped during heating Thermo-OFF. To prevent incorrect temperature detection due to a build-up of warm air around the indoor unit, use the built-in temperature sensor on the remote controller (SW1-1) instead of the one on the indoor unit inlet thermistor. Note 3. By setting SW3-1, SW1-7, and SW1-8 to a certain configuration, the fan can be set to remain stopped during cooling Thermo-OFF. See the table below for details.

Fan speed during Thermo-OFF

SW1-7 SW1-8 Heating Cooling Cooling-only/heat pump

SW3-1

OFF OFF

OFF

ON

OFF

ON

ON

OFF

OFF

ON

ON

OFF

ON

ON

Show 55 more labels / short text on this page
Switch setting timing · Indoor unit inlet · Clogged filter detection · Not available · Available · 100h · 2500h · Outside air intake · Disabled · Enabled · Remote display option · Fan output · Thermo-ON signal · Humidifier control · During heating operation · Available Not available · Preset speed · Disabled · Enabled · Power source start-stop · Disabled Enabled · Unit model selection · Heat pump · Cooling only · Louver · Not available · Available · Vane · Not available Available · Vane swing function · Not available Available · Downblow B,C Horizontal · Initial vane position · Enabled · Disabled · PLFY-VLMD model only · Not available Available · Enabled · Disabled · Switch setting · Very Low · Low · Preset speed · Heat pump · Preset speed · Stop · - · Preset speed · Cooling-only · - · - · Stop · Stop · Stop · Heat pump
Page 139 of the Mitsubishi Electronics P96 user manual — ON
Page 139 · click to enlarge
Page 139

[ VII Control ]

(2) Address switch

Actual indoor unit address setting varies in different systems. Refer to the installation manual for the outdoor unit for details on how to make the address setting. Each address is set with a combination of the settings for the 10's digit and 1's digit. (Example) When setting the address to "3", set the 1's digit to 3, and the 10's digit to 0. When setting the address to "25", set the 1's digit to 5, and the 10's digit to 2.

3. Function of the switch <Remote controller> (1) MA remote controller (PAR-20MAA)

The SW is located at the bottom of the remote controller under the cover. Operate the switches to perform the remote con- troller main/sub setting or other function settings. Normally, do not change the settings of switches other than the SW1 (main/ sub switching switch). (All the switches are set to "ON" at factory setting.)

ON

Remote controller Switching switch

Operation by switch settings Switch setting timing ON OFF

Remote controller main/sub setting

Before power on When two remote controllers are connected to one group, set either of the remote controllers to "Sub".

When the program timer (only few stock products are available) is connected, set to "Timer mode startup" to resume the operation with timer mode after power is restored.

At power on of the remote controller

When the automatic mode is set and the "Cooling"/"Heating" display is not necessary, set to "Not displayed".

3 Cooling/heating display set by automatic setting Displayed Not displayed

When the suction temperature (discharge temperature) display is not necessary, set to "Not displayed".

4 Suction temperature display (discharge temperature display) Displayed Not displayed

The MA remote controller (PAR-21MAA) does not have the switches listed above. Refer to the installation manual for the func- tion setting.

Show 10 more labels / short text on this page
Switch · Function · Main Sub · Normal · Timer mode · Before power on · startup · startup · Before power on · Before power on
Page 140 of the Mitsubishi Electronics P96 user manual — SW5
Page 140 · click to enlarge
Page 140

[ VII Control ]

(2) ME remote controller (PAR-F27MEA)

Set the address of the remote controller with the rotary switch.

10's digit 1's digit (left) (right)

ExampleIn case of address 108

Address setting range Setting method

Main remote controller 101-150 Add 100 to the smallest address of all the indoor units in the same group.

Sub remote controller 151-200 Add 150 to the smallest address of all the indoor units in the same group.

Setting of rotary switch Address No.

01-99*1 101-199 with the 100's digit automatically being set to 1*2

*1. At factory shipment, the rotary switch is set to 01.

*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is automatically set to [2].

To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (w)], and do not apply than 19.6N. The use of any other tool or applying too much load may damage the switch.

4. Switch functions <BC controller> (Control board)

Function according to switch setting

Switch setting timing OFF ON

1 Model setting R410A - Always leave this switch to OFF.

2. 5 -

SW4

6 No. of ports *1

1 2 Before being energized

7, 8 -

1. 6 -

SW5

7. - - -
8. - - -

*1. When a junction pipe kit was used to merge two ports to connect the indoor units with a total capacity of between P31 and P54, turn DIP SW4-6 to ON. When connecting a main and a sub BC controller, change the SW setting on only the main BC controller. (It is not necessary to change the SW setting on the sub BC controller. )

Rotary switch · Remote controller unit · Switch Function

Page 141 of the Mitsubishi Electronics P96 user manual — -4Control at Start-up
Page 141 · click to enlarge
Page 141

[ VII Control ]

[2] Controlling the Outdoor Unit

-1Outline of Control Method

ŒThe outdoor units are designated as OC and OS in the order of capacity from large to small (if two or more units have the

same capacity, in the order of address from small to large). ŒThe setting of outdoor unit can be verified by using the self-diagnosis switch (SW1).

Display SW1

1 2 3 5 4 6 7 8 9 10 The unit is designated as the OC: “oc” appears on the display. The unit is designated as OS: “oS” appears on the display

ON

ŒThe OC determines the operation mode and the control mode, and it also communicates with the indoor units. ŒThe OS exercises autonomous distributed control (over defrost, error detection, and actuator control etc.) according to the

operation/control mode signals that are sent from the OC.

-2Startup sequence rotation

ŒAt the initial startup, outdoor units start up in the order of "OC and OS." ŒStartup sequence rotation is performed while all the indoor units are stopped. (Even after two hours of operation, startup se-

quence rotation is not performed while the compressor is in operation.) In a system with multiple outdoor units (OC and OS), when the integrated operation time of the unit in operation (either OC or OS) reaches one hour during a cooling operation at low outside temperature, that unit will stop and the other unit will go into operation. ŒRefer to [-10-Control at Initial Start-up] for the initial startup. ŒPerforming startup sequence rotation does not change the basic operation of OC and OS. Only startup sequence is changed. ŒStartup sequence of the outdoor units can be checked with the self-diagnosis switch (SW1) on the OC.

Display SW1

1 2 3 5 4 6 7 8 9 10

OC→OS: “oc” and the “OC” address appear alternately on the display. OS→OC: “oS” and the “OS” address appear alternately on the display. ON

-3Initial Control

ŒWhen the power is turned on, the initial processing of the microcomputer is given top priority. ŒDuring the initial processing, control processing of the operation signal is suspended. (The control processing is resumed after

the initial processing is completed. Initial processing involves data processing in the microcomputer and initial setting of each of the LEV opening. This process will take up to 5 minutes.) ŒDuring the initial processing, the LED monitor on the outdoor unit's control board displays S/W version -> refrigerant type

-> heat pump -> cooling only and capacity -> and communication address in turn every second.

-4Control at Start-up

ŒThe upper limit of frequency during the first 3 minutes of the operation is 50 Hz. ŒWhen the power is turned on, normal operation will start after the initial start-up mode (to be described later) has been com-

pleted (with a restriction on the frequency).

Page 142 of the Mitsubishi Electronics P96 user manual — (4) Bypass solenoid valve (SV5b) (ON = Open)
Page 142 · click to enlarge
Page 142

[ VII Control ]

-5Bypass Control

Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions.

(1) Bypass solenoid valve (SV1a) (ON = Open)

ON OFF

When each indoor unit compressor startup ON for 4 minutes.

After the restoration of thermo or 3 minutes after restart

ON for 4 minutes.

During cooling or heating operation with the compressor stopped

Always ON. ExceptionOFF when 63HS1-63LS is 0.2MPa[29psi] or less

After the operation has stopped ON for 3 minutes. Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less

During defrost operation ON

While the compressor is operating at the minimum frequency and when the low pres- sure (63LS) drops (3 or more minutes after compressor startup)

When low pressure (63LS) drops below 0.23MPa[33psi].

When low pressure (63LS) ex- ceeds 0.38MPa[55psi].

When high pressure (63HS1) rises When 63HS1 exceeds 3.62MPa[525psi] When 63HS1 is or below 3.43MPa[497psi] and 30 seconds have passed

(2) Bypass solenoid valve (SV9) (ON = Open)

ON OFF

When high pressure (63HS1) rises during the heating operation

When 63HS1 exceeds 3.50MPa

When SV5b is ON and the pressure

is 2.70MPa[391psi]or below

(3) Bypass solenoid valve (SV2) (ON = Open)

ON OFF

When high pressure (63HS1) rises during the heating operation

When SV5b is OFF and the pres- sure is 3.50MPa[507psi]or below

When 63HS1 exceeds 2.70MPa [391psi]

When startup or resuming operation after a defrost cycle

OFF

During defrost cycle ON

(4) Bypass solenoid valve (SV5b) (ON = Open)

ON OFF

When high pressure (63HS1) rises during the heating operation

When SV2 is OFF and the pressure is 2.70MPa[391psi]or below

When SV9 is ON and the pressure is 3.50MPa[507psi]or below

During defrost cycle ON (open)

When returning to normal operation after completion of the defrost cycle

ON for 5 minutes and goes OFF

Show 9 more labels / short text on this page
Operation SV1a · Operation SV9 · [507psi] · Others Always OFF · Operation SV2 · Others Always OFF · Operation SV5b · At startup ON · Others Always OFF
Page 143 of the Mitsubishi Electronics P96 user manual — (3) Periodic frequency control
Page 143 · click to enlarge
Page 143

[ VII Control ]

(5) Bypass solenoid valve (SV5b) (ON = Open)

ON OFF

While the unit is stopped Always ON

Cooling mode When one or more of the following valves is turned OFF: SV4a through SV4c.

When the condition on the left is not met

-6Compressor Frequency Control

ŒDepending on the capacity required, the frequency of the compressor is controlled to keep constant evaporation temperature

(0°C [32°F] = 0.71 MPa [103 psi]) during cooling operation, and condensing temperature (49°C [120°F] = 2.88 MPa [418 psi]) during heating operation. ŒThe table below summarizes the operating frequency ranges of the inverter compressor during normal operation. ŒThe OS in the multiple-outdoor-unit system operates at the actual compressor frequency value that is calculated by the OS

based on the preliminary compressor frequency value that the OC determines.

Frequency/cooling (Hz) Frequency/heating (Hz)

Max Min Max Min

P72 model 43 14 48 19

P96 model 65 18 71 15

P120 model 75 18 85 15

The maximum frequency during heating operation is affected by the outdoor air temperature to a certain extent.

(1) Pressure limit

The upper limit of high pressure (63HS1) is preset, and when it exceeds the upper limit, the frequency is decreased every 15 seconds. ŒThe actuation pressure is when the high-pressure reading on 63HS1 is 3.58MPa[519psi].

(2) Discharge temperature limit

Discharge temperature (TH4) of the compressor in operation is monitored, and when it exceeds the upper limit, the frequency is decreased every minute. ŒOperating temperature is 115°C [239°F].

(3) Periodic frequency control

Frequency control other than the ones performed at start-up, upon status change, and for protection is called periodic frequen- cy control (convergent control) and is performed in the following manner. Periodic control cycle Periodic control is performed after the following time has passed Œ30 seconds after either compressor start-up or the completion of defrost operation Œ30 seconds after frequency control based on discharge temperature or pressure limit

The amount of frequency change The amount of frequency change is controlled to approximate the target value based on the evaporation temperature (Te) and condensing temperature (Tc).

Operation SV5c · Others Always OFF · Model

Page 144 of the Mitsubishi Electronics P96 user manual — SVM1 ON
Page 144 · click to enlarge
Page 144

[ VII Control ]

-7Defrost Operation Control

(1) Starting the defrost operation

ŒThe defrost cycle starts when the pipe temperature (TH6), in the following table, or below has continuously been detected for

3 minutes after the integrated compressor operation time of 50 minutes have passed. ŒIf 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced defrost operation

will start by turning on the forced defrost switch (DIP SW2-7). ŒEven if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation will be 50 minutes

if defrosting took 12 minutes. ŒIn the multiple-outdoor-unit system, all of the outdoor units that are in operation go into the defrost mode simultaneously. The

unit(s) that is stopped at the time defrost operation starts remains stopped.

TH6

SW3 - 3 OFF SW3 - 3 ON

P72 model - 10°C [14°F] - 5°C [23°F]

P96 model - 8°C [18°F] - 5°C [23°F]

P120 model - 8°C [18°F] - 5°C [23°F]

(2) Defrost operation

Outdoou unit Compressor frequency Model Compressor frequency

P72 model 60 Hz

P96 model 65 Hz

P120 model 65 Hz

Outdoor unit fan Stopped

BC controller LEV1 G type4000, GA type: 6000
LEV3 G type1000, GA type: 2000 GB, HB type: 60 (full closed)

SVM1 ON

SVM2 OFF

SV B OFF

SV A Ports that are connected to the indoor units in cooling Thermo-ON

Other portsOFF
Show 6 more labels / short text on this page
Model · SV1a ON (open) · SV2 ON (open) · SV5b ON (open) · 21S4a OFF · SV9 OFF (closed)
Page 145 of the Mitsubishi Electronics P96 user manual — (2) Control
Page 145 · click to enlarge
Page 145

[ VII Control ]

(3) Stopping the defrost operation

ŒThe defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperature (TH3

and TH6) has been continuously detected for 2 minutes that exceeds the values in the table below ŒDefrost operation will not stop its operation for 4 minutes once started. ŒIn the multiple-outdoor-unit system, defrosting is stopped on all units at the same time.

TH3

SW3 - 3 OFF SW3 - 3 ON

P72 model 10°C [50°F] 15°C [59°F]

P96 model 7°C [45°F] 12°C [54°F]

P120 model 7°C [45°F] 12°C [54°F]

(4) Problems during defrost operation

ŒIf a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on the

integrated compressor operation time will be set to 20 minutes.

(5) Change in the number of operating indoor units during defrost operation

ŒEven when there is a change in the number of operating indoor units during defrost operation, the operation will continue, and

an adjustment will be made after the completion of the defrost operation. ŒDefrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its course.

-8Refrigerant Recovery Control

Refrigerant recovery is performed for each BC port during heating operation to prevent the refrigerant from accumulating in- side the units that are stopped (in the fan mode), in the cooling mode, or in the heating Thermo-OFF mode. It is also performed during cooling operation to prevent an excessive amount of refrigerant from accumulating in the outdoor heat exchanger.

Starting criteria for the refrigerant recovery cycle (during Cooling-only, Cooling-main, Heating-only, or Heating-main mode) The refrigerant recovery mode starts when all of the following conditions are met: 1) When 5 minutes have passed in the Heating-only or Heating-main mode or 30 seconds have passed in the Cooling-only or Cooling-main mode since the completion of the previous refrigerant recovery cycle AND the when following conditions are met. TH4 > 105°C [221°F] 2) When the port is not in the 4-minute restart delay mode

Starting criteria for the refrigerant recovery cycle (during Cooling-only, Cooling-main, Heating-only, or Heating-main mode) 1) When the port is in the cooling Thermo-OFF, fan, or stop mode SV C at the port turns on for 30 seconds. ( indicates port No.)

2. The opening of LEV1 and LEV3 is increased.

-9Capacity Control of Outdoor Fan and Heat Exchanger

(1) Control method

ŒDepending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter to keep a constant

condensing temperature of (outside temperature +10°C [50°F]) during cooling operation and a constant evaporation temper- ature of (0°C [32°F] =0.71

based on the preliminary outdoor unit fan control value that the OC determines.

(2) Control

ŒOutdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor). ŒThe fan operates at full speed for 5 seconds after start-up.(Only when TH7

Model

Page 146 of the Mitsubishi Electronics P96 user manual — 1 ON ON ON ON OFF
Page 146 · click to enlarge
Page 146

[ VII Control ]

(3) Outdoor unit heat exchanger capacity control patterns

SV4a SV4b SV4c SV4d SV5c

P72 model Cooling- only Cooling- main

1 OFF OFF - ON ON

2 OFF OFF - OFF ON

3 OFF ON - OFF ON

4 ON OFF - OFF ON

5 ON ON - OFF OFF

Heating- only 1 ON ON - OFF OFF

1 ON ON - ON OFF

2 ON ON - OFF OFF

Defrost 1 ON ON - OFF OFF

P96, P120 models Cooling- only Cooling- main

1 OFF OFF OFF ON ON

2 OFF OFF OFF OFF ON

3 OFF OFF ON OFF ON

4 OFF ON ON OFF ON

5 ON ON ON OFF OFF

Heating- only 1 ON ON ON OFF OFF

1 ON OFF

2 ON ON ON OFF OFF

Defrost 1 ON ON ON OFF OFF

Show 7 more labels / short text on this page
Solenoid valve · Model Operation · Operation · mode · patterns · Heating- main · Heating- main
Page 147 of the Mitsubishi Electronics P96 user manual — (2) P144, P168, P192, P216, P240 models
Page 147 · click to enlarge
Page 147

[ VII Control ]

-10Control at Initial Start-up

ŒWhen started up for the first time before 12 hours have elapsed after power on, the unit goes into the initial startup mode. ŒAt the completion of the initial operation mode on the OC and OS, they will go into the normal control mode.

1. Flowchart of initial operation (1) P72, P96, P120 models

Initial startup mode starts.

Completed in the integrated operation time of 35 minutes.

or F < 50Hz

Completed in the integrated operation time of 90 minutes.

Initial startup mode complete

(2) P144, P168, P192, P216, P240 models

Initial startup mode starts.

The compressor on the OC starts up.

*1 Qj:Total capacity (models) code

The total operating load of the indoor unit after 5 minutes of operation is P96 or above.

(*1 Qj 50)

The compressor on the OC starts up.

The compressor on the OC remains in operation, and the compressor on the OS starts up.

50 F 60Hz (OC)

50 F 60Hz (both OC and OS)

or F < 50Hz (OC) Completed in the integrated operation time of 35 minutes.

or F < 50Hz (both OC and OS) Completed in the integrated operation time of 35 minutes.

Completed in the integrated operation time of 90 minutes.

Completed in the integrated operation time of 90 minutes.

Both the OC and OS stop.

The startup sequence of the OC and OS is rotated.

The compressor on the OS starts up.

50 F 60Hz (OS)

or F < 50Hz (OS) Completed in the integrated operation time of 35 minutes.

Completed in the integrated operation time of 90 minutes.

*2 The air conditioning load is too small for both the OC and the OS to simultaneously stay in operation.

Initial startup mode complete

*3 The air conditioning load is high enough for both OC and OS to simultaneously stay in operation.

Show 6 more labels / short text on this page
50 F 60Hz · F 60Hz · No · Yes · *2 · *3
Page 148 of the Mitsubishi Electronics P96 user manual — OC
Page 148 · click to enlarge
Page 148

[ VII Control ]

-11Emergency Operation Mode

1. Problems with the outdoor unit Œ The P144 through P240 models of unit have a mode that allows the outdoor unit to perform an emergency operation when

the other outdoor unit in the system malfunctions. ŒThis mode can be started by performing an error reset via the remote controller.

(1) Starting the emergency operation 1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller. 2) The error is reset using the remote controller. 3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation starts. 4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting the error via the remote controller.

Error codes that permit an emergency operation (Applicable to both OC and OS)

Trouble source Error codes that permit an emergency operation Error code description

0403 4220, 4225 4230 4240 4250, 4255 5110 5301 5102 5103 5104 5105 5106 5107

Serial communication error Bus voltage drop Heatsink overheat protection Overload protection Overcurrent relay trip Heatsink temperature sensor failure (THHS) Current sensor/circuit failure Subcool heat exchanger bypass outlet temperature sensor failure Pipe temperature sensor failure Discharge temperature sensor failure Accumulator inlet temperature sensor failure Subcool heat exchanger liquid outlet sensor failure Outside air temperature sensor failure

Compressor Fan motor Inverter

TH2 TH3 TH4 TH5 TH6 TH7

Power supply sync signal abnormality

Emergency operation pattern (2 outdoor units)

OC failure pattern Trouble Normal

OC

OS

Maximum total capacity of indoor units (Note 1)

1. If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable capacity, some of the indoor units will go into the same condition as Thermo-OFF.

(2) Ending the emergency operation 1) End conditions When one of the following conditions is met, emergency operation stops, and the unit makes an error stop. ŒWhen the integrated operation time of compressor in cooling mode has reached four hours. ŒWhen the integrated operation time of compressor in heating mode has reached two hours. ŒWhen an error is detected that does not permit the unit to perform an emergency operation.

2. Control at or after the completion of emergency operation Œ At or after the completion of emergency operation, the compressor stops, and the error code reappears on the remote con-

troller. ŒIf another error reset is performed at the completion of an emergency mode, the unit repeats the procedures in section (1)

above. ŒTo stop the emergency mode and perform a current-carrying operation after correcting the error, perform a power reset.

Show 10 more labels / short text on this page
Thermistor · Open phase · Power · OS failure pattern · Normal Trouble · Emergency operation · Cooling Heating · Permitted Permitted · Permitted Permitted · 60%
Page 149 of the Mitsubishi Electronics P96 user manual — (3) Ending the emergency operation
Page 149 · click to enlarge
Page 149

[ VII Control ]

2. Communication circuit failure or when some of the outdoor units are turned off This is a temporary operation mode in which the outdoor unit that is not in trouble operates when communication circuit failure occurs or when some of the outdoor units are turned off.

(1) Starting the emergency operation (When the OC is in trouble) 1) When an error occurs, the error source and the error code appear on the display on the remote controller. 2) Reset the error via the remote controller to start an emergency operation. Precautions before servicing the unit ŒWhen the OC is in trouble, the OS temporarily takes over the OC's function and performs an emergency operation. When this

happens, the indoor unit connection information are changed. ŒIn a system that has a billing function, a message indicating that the billing system information has an error may appear on

the TG-2000A. Even if this message appears, do not change (or set) the refrigerant system information on the TG-2000A. After the completion of an emergency operation, the correct connection information will be restored.

(2) Starting the emergency operation (When the OS is in trouble) 1) A communication error occurs. -> An emergency operation starts in approximately six minutes.

Error codes that permit an emergency operation (Applicable to both OC and OS)

Error codes that permit an emergency operation Error code description

Circuit board failure or the power to the outdoor units is off

6607 6608 No acknowledgement error No response error

Emergency operation pattern (2 outdoor units)

OC failure pattern Trouble Normal

OC

OS

Maximum total capacity of indoor units (Note 1)

Capacity that matches the total capacity of the operable outdoor units

1. If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable capacity, some of the indoor units will go into the same condition as Thermo-OFF.

(3) Ending the emergency operation

When communication is restored, the emergency mode is cancelled, and the units go into the normal operation mode.

Show 7 more labels / short text on this page
Trouble source · OS failure pattern · Normal Trouble · Emergency operation · Cooling Heating · Permitted Permitted · Permitted Permitted
Page 150 of the Mitsubishi Electronics P96 user manual — *
Page 150 · click to enlarge
Page 150

[ VII Control ]

-12Control Method

The control system configuration for the PURY models is shown in the chart below.

Data signal exchange between system equipment

Non-polar 2-wire serial communication method

Daisy-chained non-polar 2-wire transmission line

16-bit CPU microcomputer operation processing

*

System control Adjustment of refrigerant flow rate Adjustment of rotation speed of compressor or fan

Autonomous distributed control system (F2-VPM control)

Rotation speed control of compressor or fan depending on the refrigerant pressure value and the changing speed

Self-contained capacity control depending on the load

Refrigerant distribution control depending on the operation mode

Autonomous distributed control systemA system that consists of three independent sub control systems,

instead of a single centralized control system, that work together to maintain the overall control of the entire system.

Show 5 more labels / short text on this page
Control method · Calculation, processing · Outdoor unit · Indoor unit · BC controller
Page 151 of the Mitsubishi Electronics P96 user manual — -13Cooling/heating Circuit Control and General Function of System Equipment
Page 151 · click to enlarge
Page 151

[ VII Control ]

-13Cooling/heating Circuit Control and General Function of System Equipment

Mitsubishi Electronics P96 — -13Cooling/heating Circuit Control and General Function of System Equipment diagram (page 151)
Fig. 70 · -13Cooling/heating Circuit Control and General Funct…
Page 152 of the Mitsubishi Electronics P96 user manual — (3) Operation pattern for automatic cooling/heating mode
Page 152 · click to enlarge
Page 152

[ VII Control ]

-14Operation Mode

(1) Indoor unit operation mode

The operation mode can be selected from the following 6 modes using the remote controller.

4 Automatic cooling/heating mode

(2) Outdoor unit operation mode

Mitsubishi Electronics P96 — (2) Outdoor unit operation mode diagram (page 152)
Fig. 71 · (2) Outdoor unit operation mode

1 Cooling only mode All indoor units in operation are in cooling mode.

2 Heating only mode All indoor units in operation are in heating mode.

3 Cooling main mode Coexistence of units in cooling and heating modes.

4 Heating main mode Coexistence of units in cooling and heating modes.

5 Stopping mode All indoor units are in fan mode or stopping mode.

When units in cooing and heating coexist, the operation mode (cooling main mode or heating main mode) will be determined, based on the refrigerant pressure in the R2 refrigerant circuit and speed variation data.

(3) Operation pattern for automatic cooling/heating mode

When the automatic cooling/heating mode is selected from remote controller functions, the indoor temperature will be detect- ed in pattern as shown in the figure below, and the operation mode (cooling or heating) will automatically be selected.

Mitsubishi Electronics P96 — (3) Operation pattern for automatic cooling/heating mode diagram (page 152)
Fig. 72 · (3) Operation pattern for automatic cooling/heating…

Cooling operation under Thermo-ON conditions Set temperature (Variable between 19 C and 28 C [ 67 F and 83 F]) Heating operation under Thermo-ON conditions

(4) Relationship between the operation mode and the load capacity (kW) (within a system)

Mitsubishi Electronics P96 — (3) Operation pattern for automatic cooling/heating mode diagram (page 152)
Fig. 73 · (3) Operation pattern for automatic cooling/heating…
Show 5 more labels / short text on this page
1 Cooling mode · 2 Heating mode · 3 Dry mode · 5 Fan mode · 6 Stopping mode
Page 153 of the Mitsubishi Electronics P96 user manual — -15DEMAND Control
Page 153 · click to enlarge
Page 153

[ VII Control ]

-15DEMAND Control

Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units.

When DIP SW4-4 is set to ON, the 4-step DEMAND control is enabled. Eight-step demand control is possible in the system with two outdoor units.

Refer to Chapter II [3] 2. (7) "Various types of control using input-output signal connector on the outdoor unit (various connec- tion options)" for details.(page 22)

Page 154 of the Mitsubishi Electronics P96 user manual — 4. Control of SVM2
Page 154 · click to enlarge
Page 154

[ VII Control ]

[3] Controlling BC Controller

1. Control of SV A, SV B, and SV C SV A, SV B, and SV C turn on or off depending on the operation mode of the branch.

Cooling Heating Stopped Defrost

SV A ON OFF OFF OFF

SV B OFF ON OFF OFF

SV C ON OFF OFF OFF

2. Control of SVM1 SVM turns on or off depending on the operation mode.

mode Cooling only Cooling main Heating only Heating main Defrost Stopped

Pressure dif- ferential con- trol*1

SVM1 ON

OFF OFF ON OFF

*1. Pressure differential control: The detected differential pressure (PS1 and P3) is controlle every minute so as to be within a certain range.

3. Control of LEV LEV opening (sj) is controlled as follows depending on the operation mode.

Operation mode Cooling only Cooling

main Heating only Heating

LEV1

2000 1200 LEV2 (only GA type)

2000 Liquid level control*1dif- ferential control*2

G,GA

Pressure dif- ferential con- trol*2

Pressure dif- ferential con- trol*2

G:1000 GA:2000 60

GB,HB

control*4 60

*1. Liquid level control: The liquid level detected by the liquid inlet temperature (TH11 sensor) is controlled so as to be within a certain range.

*2. Pressure differential control: The detected differential pressure (PS1 and P3) is controlle every minute so as to be within a certain range.

*3. Can be 110 or more due to pressure rise on the liquid side (PS1).

*4. Superheat control: The amound of superheat that is calculated on the bypass inlet and outlet temperature (G, GA, H:TH12,TH15, GB, HB: TH12, TH15) is controlled every minute so as to be within a certain range.

4. Control of SVM2

mode Cooling only Cooling main Heating only Heating main Defrost Stopped

SVM2 OFF OFF Pressure differ-

ential control*1 OFF OFF

*1. Pressure differential control: The detected differential pressure (PS1 and P3) is controlled every minute so as to be with- in a certain range.

Show 13 more labels / short text on this page
Mode · Port · Operation · main Defrost Stopped · 110 110*3 · type · LEV3 Superheat · control*4 · type LEV3 Superheat · control*4 Superheat · Operation · Pressure differ- · ential control*1
Page 155 of the Mitsubishi Electronics P96 user manual — YES YES YES
Page 155 · click to enlarge
Page 155

[ VII Control ]

[4] Operation Flow Chart

1. Mode determination flowchart (1) Indoor unit (cooling, heating, dry, fan mode)

NO

YES

YES

NO

1. Protection function self-holding cancelled. 2. Indoor unit LEV fully closed.

NO

display lit off Error mode

YES

YES

ON

NO

Dry mode Heating mode Fan mode

1. Auxiliary heater OFF 2. Low fan speed for 1 minute

Self-holding of protection function

Dry display Heating display Cooling display

*Note 3 *Note 3 *Note 3

YES YES YES

YES

ON

NO NO NO NO NO

Indoor unit LEV fully closed.

Refer to 2-(1) for cooling operation.

Refer to 2-(2) for heating operation.

Refer to 2-(3) for

dry operation.

Prohibition "Blinking display on the remote controller"

*Note 1. Indoor unit LEV fully closed : Opening 41. *Note 2. The system may go into the error mode on either the indoor unit side or the BC controller or outdoor unit side. If some of the indoor units are experiencing a problem, only those indoor units that are experiencing the problem will stop. If the BC controller or the outdoor unit is experiencing a problem, all the connected units will stop.

*Note 3. If multiple indoor units are connected to a port and there is a discrepancy in the operation mode between the indoor unit and the port, the operation will be prohibited. (Operation mode blinks on the remote controller, the Fan stops, indoor unit LEV becomes fully closed.)

Show 30 more labels / short text on this page
Start · Normal operation · Error Stop · Breaker turned on · Operation SW · turned on · *Note 1 · *Note 2 · Remote controller · Operation mode · Auxiliary heater · Error stop · Automatic cooling/heating mode · Error display · Cooling mode · FAN stop · Auto COOL/HEAT · Fan display · display · *Note 3 YES · Error command · to outdoor unit · Drain pump · Prohibition Prohibition Prohibition · Prohibition · 3-minute drain · pump ON · *Note 1 · Auto cooling/heating mode · Fan operations
Page 156 of the Mitsubishi Electronics P96 user manual — YES
Page 156 · click to enlarge
Page 156

[ VII Control ]

(2) Outdoor unit (cooling only, heating only, cooling main and heating main modes)

NO

Unit in the stopped state

"HO" / "PLEASE WAIT" blinks

YES

on the remote controller

Indoor units registered to the remote controller

NO

YES

NO

Protection function self-holding cancelled.

YES

Cooling only, Heating only Mixture of units in cooling and heating

1. 52C1 4-way valve OFF 2. Inverter output 0Hz 3. Fan stop 4. All solenoid valves OFF

YES

NO

52C1 ON

Mixture of units in cooling and heating

Error display on the outdoor unit LED

Self-holding of protection function

Cooling Only Heating Only

to the BC controller

Operation command to the BC controller

*Note 1. For about 3 minutes after power on, search for the indoor unit address, for the remote controller address, and for the group information will start. During this, "HO"/ "PLEASE WAIT" blinks on the display of the remote controller. When the indoor unit to be controlled by the remote controller is missing, "HO"/ "PLEASE WAIT" keeps blinking on the display of the remote controller even after 3 or more minutes after power on.

*Note 2. The system may go into the error mode on either the indoor unit or the outdoor unit side. The outdoor stops only when all of the connected indoor units are experiencing problems. The operation of even a single indoor unit will keep the outdoor unit running. The error will be indicated on the LED display.

*Note 3. The units will follow the operation mode commands from the BC controller *Note 4. When the operation mode commands from the BC controllers are mixed (both cooling and heating), the actual operation mode is determined by the outdoor unit.

Show 22 more labels / short text on this page
Start · Normal operation · Error · Breaker turned on · *Note 1 · Operation · command · fan · Operation · mode · *Note 2 · Error mode · Error stop · *Note 3 · Operation · mode · *Note 4 · Operation · mode · Operation command · Cooling Main · Heating Main
Page 157 of the Mitsubishi Electronics P96 user manual — YES
Page 157 · click to enlarge
Page 157

[ VII Control ]

(3) BC controller (cooling only, heating only, cooling main and heating main modes)

NO

Unit in the stopped state

YES

NO

YES

Protection function self-holding cancelled.

1. Determination of operation mode (Cooling only, Heating only, Mixture of units in cooling and heating) 2. Transmitted to the outdoor unit

Reception of operation mode command from the outdoor unit

YES

NO

Mixture of units in cooling and heating

All units in the same mode Solenoid valves OFF LEV Fully closed

Self-holding of protection function

Cooling Only Heating Only Cooling Main Heating Main

Note 1. The system may go into the error mode on either the indoor unit side or the BC controller or outdoor unit side. If some of the indoor units are experiencing a problem, only those indoor units that are experiencing the problem will stop. If the BC controller or the outdoor unit is experiencing a problem, all the connected units will stop.

Show 19 more labels / short text on this page
Start · Normal operation · Error · Breaker turned on · Operation · command · *Note 1 · Error mode · Fan · Error command to · Operation · mode · outdoor unit · Operation · Error stop · mode Operation · mode · Error command to · indoor unit
Page 158 of the Mitsubishi Electronics P96 user manual — YES
Page 158 · click to enlarge
Page 158

[ VII Control ]

2. Operations in each mode (1) Cooling operation

During test run mode

Unit in the stopped state

Indoor unit fan operation

YES

ON

NO

NO

ON

YES

YES

NO

1. Inverter output 0Hz 2. Indoor unit LEV, Oil return LEV fully closed 3. Solenoid valves OFF 4. Outdoor unit fan stop 5. BC controller solenoid valves OFF 6. BC controller LEV fully closed
1. Inverter frequency control 2. Indoor unit LEV, Oil returnLEV control 3. Solenoid valve control 4. Outdoor unit fan control 5. BC controller solenoid valve control 6. BC controller control

*Note 1. The indoor fan operates at the set notch under cooling mode regardless of the ON/OFF state of the thermostat.

Show 8 more labels / short text on this page
Cooling operation · Normal operation · 4-way valve OFF · *Note 1 · Test run mode · Thermostat · 3-minute restart · prevention
Page 159 of the Mitsubishi Electronics P96 user manual — YES
Page 159 · click to enlarge
Page 159

[ VII Control ]

(2) Heating operation

Unit in the stopped state

During test run mode

NO

YES

ON

NO

1. Indoor unit fan stop 2. Inverter defrost frequency control 3. Indoor unit LEV fully open 4. Solenoid valve control 5. Outdoor unit fan stop 6. BC controller solenoid valve control 7. BC controller LEV control

NO

ON

YES

YES

NO

NO

Stopping the defrost operation

1. Indoor unit fan operation at Very Low speed 2. Inverter output 0Hz 3. Indoor unit LEV fully open 4. Solenoid valve OFF 5. Outdoor unit fan stop 6. BC controller solenoid valve control 7. BC controller LEV control
1. Indoor/outdoor unit fan control 2. Inverter frequency control 3. Indoor unit LEV fully open 4. Solenoid valve control 5. BC controller solenoid valve control 6. BC controller LEV control

YES

Stopping the defrost operation

*Note 1. When the outdoor unit goes into the defrost mode, defrost command is sent to the BC controller and indoor units. Upon reception of the command, the indoor units will go into the defrost mode. When defrosting is completed and upon receiving the signal that indicates the completion of defrosting, indoor units will resume the heating operation. *Note 2. Defrost end condition: 10 or more minutes must pass after defrost operation. or Outdoor unit piping temperature : refer to "-7-. Defrost operation control" of [2] Controlling the Outdoor Unit.

Show 11 more labels / short text on this page
Normal operation · Heating operation · Defrost operation · *Note 1,2 · Defrost operation · 4-way valve ON · 4-way valve OFF · Test run mode · Thermostat · 3-minute restart prevention · *Note 1,2
Page 160 of the Mitsubishi Electronics P96 user manual — YES
Page 160 · click to enlarge
Page 160

[ VII Control ]

(3) Dry operation

Unit in the stopped state

YES

ON

NO

NO

18 C[64 F]

YES

1. Indoor unit fan stop 2. Inverter output 0Hz 3. Indoor unit LEV fully closed. 4. Solenoid valve OFF 5. Outdoor unit fan stop 6. BC controller Solenoid valve OFF 7. BC controller LEV fully closed
1. Outdoor unit (compressor) intermittent operation 2. Indoor unit fan intermittent operations (Synchronized with the compressor: low speed, OFF operations)

*Note 1.When the indoor unit inlet temperature exceeds 18 C [64 F], the outdoor unit (compressor) and the indoor unit fan start the intermittent operation simultaneously. When the indoor unit inlet temperature becomes 18 C [64 F],or less, the fan always runs (at low speed). The outdoor unit, the indoor unit, and the solenoid valve operate in the same way as they do in the cooling operation when the compressor is turned on.

*Note 2.Thermostat is always kept on during test run mode, and indoor and outdoor unit intermittent operation (ON) time is a little longer than that of normal operation.

Show 9 more labels / short text on this page
Dry operation · Normal operation · Thermostat ON · 4-way valve OFF · Test run mode · *Note 2 · Thermostat ON · Suction temperature · *Note 1
Page 161 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 161 · click to enlarge
Page 161

- 152 -

Page 162 of the Mitsubishi Electronics P96 user manual — VIII Test Run Mode
Page 162 · click to enlarge
Page 162

VIII Test Run Mode

[1] Items to be checked before a Test Run 155 [2] Test Run Method 156 [3] Operating Characteristic and Refrigerant Amount 157 [4] Adjusting the Refrigerant Amount 157 [5] Refrigerant Amount Adjust Mode 160 [6] The following symptoms are normal 162 [7] Standard Operation Data (Reference Data) 163

Page 163 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 163 · click to enlarge
Page 163

- 154 -

Page 164 of the Mitsubishi Electronics P96 user manual — (5) [When a transmission booster is connected]
Page 164 · click to enlarge
Page 164

[ VIII Test Run Mode ]

VIII Test Run Mode [1] Items to be checked before a Test Run

(1) Check for refrigerant leak and loose cables and connectors.

(2) Measure the insulation resistance between the power supply terminal block and the ground with a 500V megger and

make sure it reads at least 1.0Mohm.

ŒDo not operate the unit if the insulation resistance is below 1.0Mohm. ŒDo not apply megger voltage to the terminal block for transmission line. Doing so will damage the controller board. ŒThe insulation resistance between the power supply terminal block and the ground could go down to close to 1Mohm imme-

diately after installation or when the power is kept off for an extended period of time because of the accumulation of refrigerant in the compressor. ŒIf insulation resistance reads at least 1Mohm, by turning on the main power and powering the crankcase heater for at least

12 hours, the refrigerant in the compressor will evaporate and the insulation resistance will go up. ŒDo not measure the insulation resistance of the terminal block for transmission line for the unit remote controller.

(3) Check that the valve on the gas pipe and liquid pipe are fully open.

Securely tighten the cap.

(4) Check the phase sequence and the voltage of the power supply.

(5) [When a transmission booster is connected]

Turn on the transmission booster before turning on the outdoor units.

ŒIf the outdoor units are turned on first, the connection information for the refrigerant circuit may not be properly recognized. ŒIn case the outdoor units are turned on before the transmission booster is turned on, perform a power reset on the outdoor

units after turning on the power booster.

(6) Turn on the main power to the unit at least 12 hours before test run to power the crankcase heater.

Insufficient powering time may result in compressor damage.

(7) When a power supply unit is connected to the transmission line for centralized control, perform a test run with the

power supply unit being energized. Leave the power jumper connector on CN41 as it is (factory setting).

Page 165 of the Mitsubishi Electronics P96 user manual — PAR-21MAA
Page 165 · click to enlarge
Page 165

[ VIII Test Run Mode ]

[2] Test Run Method

The figure shows an MA remote controller (PAR-21MAA).

TIME SUN MON TUE WED THU FRI SAT

TIMER

ON

ERROR CODE AFTER

AFTER

OFF

F C F C

FILTER FUNCTION

SIMPLE AUTO OFF

WEEKLY

ONLY1Hr.

TEMP.

ON/OFF

MENU

ON/OFF

FILTER

BACK DAY MONITOR/SET

CHECK

TEST

Vertical Air Direction button Louver button ( Operation button)

PAR-21MAA

CLOCK

OPERATION CLEAR

To preceding operation number.

Ventilation button ( Operation button)

To next operation number.

Turn on the main power. "PLEASE WAIT" appears on the LCD for up to five minutes. Leave the power on for 12 hours. (Energize the crankcase heater.)

Press the Test button twice. Operation mode display "TEST RUN" and OPERATION MODE are displayed alternately.

Press the Operation Mode button.

Make sure that the air is blowing out.

Switch to cooling (or heating) operation by pressing the Operation Mode button.

Make sure that cold (or warm) air blows out.

Press the Fan Speed button.

Make sure that the fan speed changes with each pressing of the button.

Change the air flow direction by pressing the Vertical Air Direction button or the Louver button.

Make sure that the air flow direction changes with each pressing of the button.

Confirm the operation of outdoor unit fan.

Confirm the operation of all interlocked equipment, such as ventilation equipment.

Cancel the test run by pressing the ON/OFF button.

2: The OFF timer will automatically stop the test run after 2 hours. 3: The remaining time for the test run will be displayed in the time display during test run. 4: The temperature of the liquid pipe on the indoor unit will be displayed in the room temperature display window on the remote controller during test run. 5: On some models, "NOT AVAILABLE" may appear on the display when the Vane Control button is pressed. This is normal. 6: If an external input is connected, perform a test run using the external input signal.

Show 10 more labels / short text on this page
Set Temperature buttons · ON/OFF button · Down · Fan Speed button · Up · Hr · Operation Mode button · Test Run button · Operation procedures · Stop
Page 166 of the Mitsubishi Electronics P96 user manual — 2. Amount of refrigerant (1) To be checked during operation
Page 166 · click to enlarge
Page 166

[ VIII Test Run Mode ]

[3] Operating Characteristic and Refrigerant Amount

It is important to have a clear understanding of the characteristics of refrigerant and the operating characteristics of air conditioners before attempting to adjust the refrigerant amount in a given system.

1. Operating characteristic and refrigerant amount The following table shows items of particular importance. 1) During cooling operation, the amount of refrigerant in the accumulator is the smallest when all indoor units are in operation. 2) During heating operation, the amount of refrigerant in the accumulator is the largest when all indoor units are in operation. 3) General tendency of discharge temperature ŒDischarge temperature tends to rise when the system is short on refrigerant. ŒChanging the amount of refrigerant in the system while there is refrigerant in the accumulator has little effect on the discharge

temperature. ŒThe higher the pressure, the more likely it is for the discharge temperature to rise. ŒThe lower the pressure, the more likely it is for the discharge temperature to rise. 4) When the amount of refrigerant in the system is adequate, the compressor shell temperature is 10 to 60°C [18 to 108°F] higher than the low pressure saturation temperature (Te). -> If the temperature difference between the compressor shell temperature and low pressure saturation temperature (Te) is smaller than 5°C [9°F], an overcharging of refrigerant is suspected.

[4] Adjusting the Refrigerant Amount

1. Symptoms Overcharging or undercharging of refrigerant can cause the following symptoms: Before attempting to adjust the amount of refrigerant in the system, thoroughly check the operating conditions of the system. Then, adjust the refrigerant amount by running the unit in the refrigerant amount adjust mode.

The system comes to an abnormal stop, displaying 1500 (overcharged refrigerant) on the controller.

The operating frequency does not reach the set frequency, and there is a problem with performance.

The system comes to an abnormal stop, displaying 1102 (abnormal discharge temper- ature) on the controller.

2. Amount of refrigerant (1) To be checked during operation

Operate all indoor units in either cooling-only or heating-only mode, and check such items as discharge temperature, subcool- ing, low pressure, suction temperature, and shell bottom temperature to estimate the amount of refrigerant in the system.

Discharge temperature is high. (Normal discharge temperature is below 95°C [203°F].) Slightly under- charged refrigerant Low pressure is unusually low.

Suction superheat is large. (Normal suction superheat is less than 20°C [36°F].)

Compressor shell bottom temperature is high. (The difference between the compressor shell bottom temperature and low pressure saturation temperature (Te) is greater than 60°C [108°F].)

Discharge superheat is small. (Normal discharge superheat is greater than 10°C [18°F].) Slightly overcharged refrigerant Compressor shell bottom temperature is low. (The difference between the compressor shell bot- tom temperature and low pressure saturation temperature (Te) is less than 5°C [9°F].)

Overcharged refrigerant · Insufficient refrigerant amount · Symptoms Conclusion

Page 167 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 167 · click to enlarge
Page 167

[ VIII Test Run Mode ]

3. Amount of refrigerant to be added The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units. The amount necessary for extended pipe (field piping) is not included and must be added on site.

Outdoor unit model P72 P96 P120

Amount of pre-charged refrigerant in the outdoor unit (kg) 10.5 11.8 11.8

Amount of pre-charged refrigerant in the outdoor unit [lbs-oz] 23-2 26-1 26-1

The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])

Amount of added refrigerant (kg) = (0.36 x L1) + (0.23 x L2) + (0.16 x L3) + (0.11 x L4)+ (0.2 x L5)

+ (0.12 x L6) + (0.06 x L7) + (0.024 x L8) + ǩ1+ ǩ3 + ǩ4

Amount of added refrigerant (oz) = (3.88 x L1' ) + (2.48 x L2' ) + (1.73 x L3' ) + (1.19 x L4' )+ (2.16 x L5' )

+ (1.30 x L6' ) + (0.65 x L7' ) + (0.26 x L8' ) + ǩ1' + ǩ3' + ǩ4'

L1 : Length of ø28.58[1-1/8"] high pressure pipe (m) L2 : Length of ø22.2[7/8"] high pressure pipe (m) L3 : Length of ø19.05[3/4"] high pressure pipe (m) L4 : Length of ø15.88[5/8"] high pressure pipeŠ (m) L5 : Length of ø15.88[5/8"] liquid pipe (m) L6 : Length of ø12.7[1/2"] liquid pipe (m) L7 : Length of ø9.52[3/8"] liquid pipe (m) L8 : Length of ø6.35[1/4"] liquid pipe (m) ǩ1,ǩ3,ǩ4, ǩ1' , ǩ3' , ǩ4' : Refer to the table below.

L1' : Length of ø28.58[1-1/8"] high pressure pipe [ft] L2' : Length of ø22.2[7/8"] high pressure pipe [ft] L3' : Length of ø19.05[3/4"] high pressure pipe [ft] L4' : Length of ø15.88[5/8"] high pressure pipe [ft] L5' : Length of ø15.88[5/8"] liquid pipe [ft] L6' : Length of ø12.7[1/2"] liquid pipe [ft] L7' : Length of ø9.52[3/8"] liquid pipe [ft] L8' : Length of ø6.35[1/4"] liquid pipe [ft]

Amount for the BC controllers (main/sub) BC controller (sub)

Total capacity of connected indoor

Amount for the Indoor

ǩ1(kg) ǩ1' (oz) ǩ4(kg) ǩ4' (oz)

P72 model 3.0 106 Total number of BC ǩ3(kg) ǩ3' (oz) - 27 2.0 71

4.5 159 1 1.0 35 28 - 54 2.5 89

P120 model 2 2.0 71 55 - 126 3.0 106

P144 model 6.0 212 127 - 144 3.5 124

P168 model 7.5 265 145 - 180 4.5 159

181. 234 5.0 177

P216 model 235 - 273 6.0 212

9.0 318

P240 model 274 - 307 8.0 283

308. 342 9.0 318
343. 411 10.0 353
412. 12.0 424

Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg) Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz. (Example: 78.21oz to 79oz)

Show 7 more labels / short text on this page
(1) Calculation formula · Outdoor unit total · unit · index · units · P96 model · P192 model
Page 168 of the Mitsubishi Electronics P96 user manual — When
Page 168 · click to enlarge
Page 168

[ VIII Test Run Mode ]

(2) Example

Outdoor unit 1 Outdoor unit 2

F

G

Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2)

D

H H′

Reducer (P06 - P18 models) (Supplied with the BC Controller)

E

Junction pipe kit (CMY-R160-J) (Optional accessory)

B

(P06 - P30)

(P36 - P96)

Maximum of 3 units per port Total capacity of P30 or below

(3) Sample calculation

Indoor unit1:30 model Indoor unit2:96 model Indoor unit3:12 model Indoor unit4:15 model Indoor unit5:12 model Indoor unit6:24 model

A : 28.58 B : 9.52 C : 9.52 D : 9.52 E : 9.52 F : 22.2 G : 19.05

[1-1/8"] [3/8"] [7/8"] [3/4"]

40m 10m 20m 5m 5m 3m 1m

[131ft] [32ft] [65ft] [16ft] [16ft] [9ft] [3ft]

a : 9.52 b : 9.52 c : 6.35 d : 6.35 e : 6.35 f : 9.52

[3/8"] [3/8"] [1/4"] [1/4"] [1/4"] [3/8"]

10m 5m 5m 10m 5m 5m

[32ft] [16ft] [16ft] [32ft] [16ft] [16ft]

When

The aggregate length of each liquid pipe type.

28.58 A = 40m[131ft] 22.2 F = 30m[98ft] 19.05 G = 1m[3ft] 9.52 C+D+E+a+b+f = 50m[164ft] 6.35 c+d+e = 20m[65ft]

The final result will be as follows: Amount of refrigerant to be charged = 40×0.36+3×0.23+1×0.16+50×0.06+20×0.024+7.5+2+2+5

= 35.3kg

Show 18 more labels / short text on this page
h4 · Branch joint kit · Indoor · A e h1 · BC controller(HB) · BC controller(HA) · h3 · Branch joint (CMY-Y102S-G2) · BC controller(HB) · h2 · h1 · a · b · c d f · h1 · Indoor Indoor Indoor · Indoor · Indoor
Page 169 of the Mitsubishi Electronics P96 user manual — [5] Refrigerant Amount Adjust Mode
Page 169 · click to enlarge
Page 169

[ VIII Test Run Mode ]

[5] Refrigerant Amount Adjust Mode

1. Procedures Follow the procedures below to add or extract refrigerant as necessary depending on the operation mode.

When the function switch (SW4-3) on the main board on the outdoor unit (OC only) is turned to ON, the unit goes into the refrigerant amount adjust mode, and the following sequence is followed.

SW4-3 on the OS is invalid, and the unit will not go into the refrigerant amount adjust mode.

Operation When the unit is in the refrigerant amount adjust mode, the LEV on the indoor unit does not open as fully as it nor- mally does during cooling operation to secure subcooling.

1) Adjust the refrigerant amount based on the values of TH4, TH3, TH6, and Tc, following the flowchart below. Check the TH4, TH3, TH6, and Tc values on the OC, OS by following the flowchart. The TH4, TH3, TH6, and Tc values can be displayed by setting the self-diagnosis switch (SW1) on the main board on the OC, OS. 2) There may be cases when the refrigerant amount may seem adequate for a short while after starting the unit in the refrigerant amount adjust mode but turn out to be inadequate later on (when the refrigerant system stabilizes). When the amount of refrigerant is truly adequate. TH3-TH6 on the indoor unit is 5°C [9°F] or above and SH on the indoor unit is between 5 and 15°C [9 and 27°F]. The refrigerant amount may seem adequate at the moment, but may turn out to be inadequate later on. TH3-TH6 on the indoor unit is 5°C [9°F] or less and SH on the indoor unit is 5°C [9°F] or less. Wait until the TH3-TH6 reaches 5°C [9°F] or above and the SH of the indoor unit is between 5 and 15°C [9 and 27°F] to determine that the refrigerant amount is adequate. 3) High pressure must be at least 2.0MPa [290psi] to enable a proper adjustment of refrigerant amount to be made. 4) Refrigerant amount adjust mode automatically ends 90 minutes after beginning. When this happens, by turning off the SW4- 3 and turning them back on, the unit will go back into the refrigerant amount adjust mode.

Self-diagnosis swithes on TH4

Self-diagnosis swithes on TH3

1 2 3 4 5 6 7 8 9 10 ON

1 2 3 4 5 6 7 8 9 10 ON

Self-diagnosis swithes on TH6

Self-diagnosis swithes on Tc

1 2 3 4 5 6 7 8 9 10 ON

1 2 3 4 5 6 7 8 9 10 ON

Page 170 of the Mitsubishi Electronics P96 user manual — YES
Page 170 · click to enlarge
Page 170

[ VIII Test Run Mode ]

Turn on SW4-3 on the OC.

YES

NO

Put all indoor units in the test run mode and run the units in cooling mode.

*Refer to the previous page for *Notes 1-4 in the chart.

NO

Has the initial start-up mode been completed?

YES

Has it been at least

NO

30 minutes since start up?

YES

NO

Gradually add refrigerant from the service port on the low- pressure side.

Is the TH4 value of the OC, OS

at or below 100°C [212°F]?

YES

Has the operating frequency of the compressor on the OC, OS

NO

YES

Keep the unit running for 5 minutes after adjusting the refrigerant amount to determine its adequacy.

NO

Does 8°C [14.4°F] Tc-TH3 12°C [21.6°F] hold true?

(Use the largest “Tc - TH3” value of the

OC, OS.)

YES

Keep the unit running for 5 minutes after adjusting the refrigerant amount and check(Tc-TH3)

Gradually add refrigerant from the service port on the low pressure side.

NO

NO

Does Tc-TH6 20°C [36°F] hold true?

Does the following hold true?

(Check this item on the unit whose “Tc – TH3” value was

used in the step above.)

Tc-TH3 8°C [14.4°F]

YES

YES

Keep the unit running for 5 minutes after adjusting the refrigerant amount to determine its adequacy.

Gradually add refrigerant from the service port on the low pressure side.

NO

Is the TH4 value of the OC, OS

Gradually add refrigerant from the service port on the low pressure side.

Gradually draw out refrigerant from the service port on the low pressure side.

at or below 95°C [203°F]

YES

Turn off SW4-3 on the OC.

result in performance loss.

Show 4 more labels / short text on this page
Start · Note 1 · become stable? · Adjustment complete
Page 171 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 171 · click to enlarge
Page 171

[ VIII Test Run Mode ]

[6] The following symptoms are normal.

The indoor unit does not start after starting cooling (heating) operation.

The unit cannot perform a heating (cooling) operation when other indoor units are performing a cooling (heating) operation.

icon blinks on the

display.

The auto vane adjusts its posi- tion by itself.

After an hour of cooling operation with the auto vane in the vertical posi- tion, the vane may automatically move into the horizontal position. Louver blades will automatically move into the horizontal position while the unit is in the defrost mode, pre-heating stand-by mode, or when the thermostat triggers unit off.

The fan stops during heating operation. Defrost The fan remains stopped during defrost operation.

The fan keeps running after the unit has stopped. Unlit When the auxiliary heater is turned on, the fan operates for one minute after stopping to dissipate heat.

The fan speed does not reach the set speed when operation switch is turned on. STAND BY

The fan operates at extra low speed for 5 minutes after it is turned on or until the pipe temperature reaches 35°C[95°F], then it operates at low speed for 2 minutes, and finally it operates at the set speed. (Pre-heating stand-by)

When the main power is turned on, the display shown on the right appears on the in- door unit remote controller for 5 minutes.

The system is starting up. Wait until the blinking display of "HO" or "PLEASE WAIT" go off.

"HO" or "PLEASE WAIT" icons blink

on the display.

The drain pump keeps run- ning after the unit has stopped.

The drain pump stays in operation for three minutes after the unit in the cooling mode is stopped.

The drain pump is running while the unit is stopped.

When drain water is detected, the drain pump goes into operation even while the unit is stopped.

Indoor unit and BC controller make noise during cooling/ heating changeover.

This noise is made when the refrigerant circuit is reversed and is normal.

Sound of the refrigerant flow is heard from the indoor unit im- mediately after starting opera- tion.

This is caused by the transient instability of the refrigerant flow and is nor- mal.

Warm air sometimes comes out of the indoor units that are not in the heating mode. Normal display

This is due to the fact that the LEVs on some of the indoor units are kept slightly open to prevent the refrigerant in the indoor units that are not op- erating in the heating mode from liquefying and accumulating in the com- pressor. It is part of a normal operation.

Show 7 more labels / short text on this page
Symptoms Remote controller · display Cause · "Cooling (heating)" · Normal display · Unlit · Normal display · Normal display
Page 172 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 172 · click to enlarge
Page 172

[ VIII Test Run Mode ]

[7] Standard Operation Data (Reference Data)

1. Single unit (1) Cooling only operation

PURY-P72THMU-A PURY-P96THMU-A

Model name of BC controller CMB-P104NU-G CMB-P104NU-G

26.7°C/19.4°C [80 °F/67 °F]

26.7°C/19.4°C [80 °F/67 °F]

DB/WB

Outdoor 35°C/- [95 °F/-]

35°C/- [95°F/-]

No. of connected units

No. of units in operation 3 2

Model - 24/24/24 48/48

5 [16-3/8"] 5 [16-3/8"]

Branch pipe 10 [32-3/4"] 10 [32-3/4"]

Total pipe length 35 [114-13/16"] 25 [82]

Fan speed - Hi Hi

Amount of refrigerant kg [lbs-oz] 19.1 [42] 21.3 [47]

Electric current A 15.4 23.2

Voltage V 230 230

Compressor frequency Hz 43 65

BC controller (1/2/3) 2000/-/180 2000/-/170

High pressure(63HS1)/ Low pressure(63LS) MPa

2.65/0.90 [384/130]

2.66/0.93 [385/134]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.59/2.59 [375/375]

2.58/2.58 [374/374]

76 [169] 85 [185]

Heat exchanger outlet (TH3) 41 [106] 39 [102]

Accumulator inlet 14 [57] 8 [46]

Temp. of each sec- tion

Accumulator outlet 14 [57] 8 [46]

°C [°F]

Compressor inlet 23 [73] 19 [66]

Compressor shell bottom 34 [93] 40 [104]

LEV inlet 24 [75] 19 [66]

Heat exchanger inlet 12 [54] 6 [43]

Show 20 more labels / short text on this page
Outdoor unit model · Operation · Indoor · Ambient tempera- ture · Unit · Indoor unit · Operating conditions · Main pipe · m [ft] · Piping · Outdoor unit · LEV open- ing · Indoor unit · 180/200/220 387/387 · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 173 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 173 · click to enlarge
Page 173

[ VIII Test Run Mode ]

PURY-P120THMU-A

Model name of BC controller CMB-P104NU-G

26.7°C/19.4°C [80°F/67°F]

DB/WB

No. of connected units

No. of units in operation 4

Branch pipe 10 [32-3/4"]

Total pipe length 45 [147-5/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 22.5 [50]

Electric current A 29.5

Compressor frequency Hz 75

BC controller (1/2/3) 2000/-/210

High pressure(63HS1)/ Low pressure(63LS) MPa

2.82/0.89 [409/129]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.73/2.72 [395/394]

Heat exchanger outlet (TH3) 43 [109]

Accumulator inlet 8 [46]

Temp. of each sec- tion

Accumulator outlet 8 [46]

°C [°F]

Compressor inlet 20 [68]

Compressor shell bottom 42 [108]

LEV inlet 22 [72]

Heat exchanger inlet 11 [52]

Show 25 more labels / short text on this page
Outdoor unit model · Operation · Indoor · Ambient tempera- ture · Outdoor 35°C/- [95°F/-] · Unit · Indoor unit · Operating conditions · Model - 30/30/30/30 · Main pipe · 5 [16-3/8"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 230/230/230/230 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · 82 [180] · Outdoor unit · Indoor unit
Page 174 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 174 · click to enlarge
Page 174

[ VIII Test Run Mode ]

(2) Heating only operation

PURY-P72THMU-A PURY-P96THMU-A

Model name of BC controller CMB-P104NU-G CMB-P104NU-G

21.1°C/- [70°F/-]

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 3 2

Model - 24/24/24 48/48

5 [16-3/8"] 5 [16-3/8"]

Branch pipe 10 [32-3/4"] 10 [32-3/4"]

Total pipe length 35 [114-13/16"] 25 [82]

Fan speed - Hi Hi

Amount of refrigerant kg [lbs-oz] 19.1 [42] 21.3 [47]

Electric current A 16.8 24.1

Voltage V 230 230

Compressor frequency Hz 48 71

BC controller (1/2/3) 110/-/520 110/-/590

High pressure(63HS1)/ Low pressure(63LS) MPa

2.61/0.69 [378/100]

2.67/0.68 [387/98]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.54/2.22 [368/321]

2.63/2.31 [381/335]

69 [156] 80 [176]

Heat exchanger outlet (TH6) 0 [32] 0 [32]

Accumulator inlet 1 [34] -2 [28]

Temp. of each sec- tion

°C [°F]

Accumulator outlet 1 [34] -3 [27]

Compressor inlet 1 [34] -3 [27]

Compressor shell bottom 40 [104] 40 [104]

LEV inlet 30 [86] 38 [100]

Heat exchanger inlet 63 [145] 70 [158]

Show 20 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Unit · Indoor unit · Operating conditions · Main pipe · m [ft] · Piping · Outdoor unit · Indoor unit · 205/203/200 406/406 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 175 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 175 · click to enlarge
Page 175

[ VIII Test Run Mode ]

PURY-P120THMU-A

Model name of BC controller CMB-P104NU-G

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 4

Branch pipe 10 [32-3/4"]

Total pipe length 45 [147-5/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 22.5 [50]

Electric current A 28.3

Compressor frequency Hz 81

BC controller (1/2/3) 110/-/660

High pressure(63HS1)/ Low pressure(63LS) MPa

2.57/0.64 [372/92]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.54/2.22 [368/321]

Heat exchanger outlet (TH6) 2 [36]

Accumulator inlet -1 [30]

Temp. of each sec- tion

Accumulator outlet -1 [30]

°C [°F]

Compressor inlet -1 [30]

Compressor shell bottom 40 [104]

LEV inlet 28 [82]

Heat exchanger inlet 67 [153]

Show 24 more labels / short text on this page
Outdoor unit model · Operation · Indoor · Ambient tempera- ture · Unit · Indoor unit · Operating conditions · Model - 30/30/30/30 · Main pipe · 5 [16-3/8"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 295/295/295/295 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · 73 [163] · Outdoor unit · Indoor unit
Page 176 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 176 · click to enlarge
Page 176

[ VIII Test Run Mode ]

2. 2-unit combination (1) Cooling only operation

PURY-P144TSHMU-A

PURY-P72THMU-A PURY-P72THMU-A

Model name of BC controller CMB-P108NU-GA

26.7°C/19.4°C [80°F/67°F]

DB/WB

No. of connected units

No. of units in operation 4

Branch pipe 10 [32-3/4"]

Total pipe length 45 [147-5/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 34.1 [75]

Electric current A 31.5

Compressor frequency Hz 43 43

BC controller (1/2/3) 2000/2000/250

High pressure(63HS1)/ Low pressure(63LS) MPa

2.65/0.90 [384/130]

2.65/0.90 [384/130]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.59/2.59 [375/375]

76 [169] 76 [169]

Heat exchanger outlet (TH3) 41 [106] 41 [106]

Accumulator inlet 14 [57] 14 [57]

Temp. of each sec- tion

°C [°F]

Accumulator outlet 14 [57] 14 [57]

Compressor inlet 23 [73] 23 [73]

Compressor shell bottom 34 [93] 34 [93]

LEV inlet 24 [75]

Heat exchanger inlet 12 [54]

Show 24 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Outdoor 35°C/- [95°F/-] · Unit · Indoor unit · Model - 36/36/36/36 · Operating conditions · Main pipe · 5 [16-3/8"] · m [ft] · Piping · Outdoor unit · Voltage V 230 · Indoor unit · 275/275/275/275 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 177 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 177 · click to enlarge
Page 177

[ VIII Test Run Mode ]

PURY-P168TSHMU-A

PURY-P96THMU-A PURY-P72THMU-A

Model name of BC controller CMB-P108NU-GA

26.7°C/19.4°C [80°F/67°F]

DB/WB

No. of connected units

No. of units in operation 5

Branch pipe 10 [32-3/4"]

Total pipe length 55 [180-1/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 38.5 [85]

Electric current A 39.5

Compressor frequency Hz 65 43

BC controller (1/2/3) 2000/2000/260

High pressure(63HS1)/ Low pressure(63LS) MPa

2.66/0.91 [385/131]

2.65/0.91 [384/131]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.59/2.59 [375/375]

85 [185] 76 [169]

Heat exchanger outlet (TH3) 39 [102] 41 [106]

Accumulator inlet 8 [46] 14 [57]

Temp. of each sec- tion

Accumulator outlet 8 [46] 14 [57]

°C [°F]

Compressor inlet 19 [66] 23 [73]

Compressor shell bottom 40 [104] 34 [93]

LEV inlet 22 [72]

Heat exchanger inlet 9 [48]

Show 24 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Outdoor 35°C/- [95°F/-] · Unit · Indoor unit · Model - 30/30/36/36/36 · Operating conditions · Main pipe · 5 [16-3/8"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 230/230/230/275/275 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 178 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 178 · click to enlarge
Page 178

[ VIII Test Run Mode ]

PURY-P192TSHMU-A

PURY-P96THMU-A PURY-P96THMU-A

Model name of BC controller CMB-P108NU-GA

26.7°C/19.4°C [80°F/67°F]

DB/WB

No. of connected units

No. of units in operation 6

Branch pipe 10 [32-3/4"]

Total pipe length 65 [213-1/4"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 42.4 [93]

Electric current A 47.5

Compressor frequency Hz 65 65

BC controller (1/2/3) 2000/2000/270

High pressure(63HS1)/ Low pressure(63LS) MPa

2.66/0.93 [385/134]

2.66/0.93 [385/134]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.59/2.59 [375/375]

85 [185] 85 [185]

Heat exchanger outlet (TH3) 39 [102] 39 [102]

Accumulator inlet 8 [46] 8 [46]

Temp. of each sec- tion

Accumulator outlet 8 [46] 8 [46]

°C [°F]

Compressor inlet 19 [66] 19 [66]

Compressor shell bottom 42 [108] 40 [104]

LEV inlet 19 [66]

Heat exchanger inlet 6 [43]

Show 24 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Outdoor 35°C/- [95°F/-] · Unit · Indoor unit · Model - 30/30/30/30/36/36 · Operating conditions · Main pipe · 5 [16-3/8"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 230/230/230/230/275/275 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 179 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 179 · click to enlarge
Page 179

[ VIII Test Run Mode ]

PURY-P216TSHMU-A

PURY-P120THMU-A PURY-P96THMU-A

Model name of BC controller CMB-P1013NU-GA

26.7°C/19.4°C [80°F/67°F]

DB/WB

No. of connected units

No. of units in operation 6

Branch pipe 10 [32-3/4"]

Total pipe length 65 [213-1/4"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 43.0 [95]

Electric current A 53.8

Compressor frequency Hz 75 65

BC controller (1/2/3) 2000/2000/280

High pressure(63HS1)/ Low pressure(63LS) MPa

2.82/0.91 [409/131]

2.66/0.91 [385/131]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.66/2.66 [385/385]

82 [180] 85 [185]

Heat exchanger outlet (TH3) 43 [109] 39 [102]

Accumulator inlet 8 [46] 8 [46]

Temp. of each sec- tion

Accumulator outlet 8 [46] 8 [46]

°C [°F]

Compressor inlet 20 [68] 19 [66]

Compressor shell bottom 42 [108] 40 [104]

LEV inlet 22 [72]

Heat exchanger inlet 9 [48]

Show 24 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Outdoor 35°C/- [95°F/-] · Unit · Indoor unit · Model - 36/36/36/36/36/36 · Operating conditions · Main pipe · 5 [16-3/8"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 275/275/275/275/275/275 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 180 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 180 · click to enlarge
Page 180

[ VIII Test Run Mode ]

PURY-P240TSHMU-A

PURY-P120THMU-A PURY-P120THMU-A

Model name of BC controller CMB-P1013NU-GA

26.7°C/19.4°C [80°F/67°F]

DB/WB

No. of connected units

No. of units in operation 7

Branch pipe 10 [32-3/4"]

Total pipe length 75 [229-5/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 44.6 [98]

Electric current A 60.2

Compressor frequency Hz 75 75

BC controller (1/2/3) 2000/2000/290

High pressure(63HS1)/ Low pressure(63LS) MPa

2.82/0.89 [409/129]

2.82/0.89 [409/129]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.73/2.73 [395/395]

82 [180] 82 [180]

Heat exchanger outlet (TH3) 43 [109] 43 [109]

Accumulator inlet 8 [46] 8 [46]

Temp. of each sec- tion

Accumulator outlet 8 [46] 8 [46]

°C [°F]

Compressor inlet 20 [68] 20 [68]

Compressor shell bottom 42 [108] 42 [108]

LEV inlet 22 [72]

Heat exchanger inlet 11 [52]

Show 24 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Outdoor 35°C/- [95°F/-] · Unit · Indoor unit · Model - 24/36/36/36/36/36/36 · Operating conditions · Main pipe · 5 [16-3/8"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 200/275/275/275/275/275/275 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 181 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 181 · click to enlarge
Page 181

[ VIII Test Run Mode ]

(2) Heating only operation

PURY-P144TSHMU-A

PURY-P72THMU-A PURY-P72THMU-A

Model name of BC controller CMB-P108NU-A

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 4

Branch pipe 10 [32-3/4"]

Total pipe length 45 [147-5/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 34.1 [75]

Electric current A 34.6

Compressor frequency Hz 48 48

BC controller (1/2/3) 110/110/870

High pressure(63HS1)/ Low pressure(63LS) MPa

2.61/0.69 [378/100]

2.61/0.69 [378/100]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.54/2.22 [368/321]

69 [156] 69 [156]

Heat exchanger outlet (TH6) 0 [32] 0 [32]

Accumulator inlet 1 [34] 1 [34]

Temp. of each sec- tion

°C [°F]

Accumulator outlet 1 [34] 1 [34]

Compressor inlet 1 [34] 1 [34]

Compressor shell bottom 40 [104] 40 [104]

LEV inlet 30 [86]

Heat exchanger inlet 63 [145]

Show 23 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Unit · Indoor unit · Model - 36/36/36/36 · Operating conditions · Main pipe · 5 [16-3/18"] · m [ft] · Piping · Outdoor unit · Voltage V 230 · Indoor unit · 350/350/350/350 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 182 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 182 · click to enlarge
Page 182

[ VIII Test Run Mode ]

PURY-P168TSHMU-A

PURY-P96THMU-A PURY-P72THMU-A

Model name of BC controller CMB-P108NU-GA

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 5

Branch pipe 10 [32-3/4"]

Total pipe length 55 [180-1/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 38.5 [85]

Electric current A 42.2

Compressor frequency Hz 71 48

BC controller (1/2/3) 110/110/980

High pressure(63HS1)/ Low pressure(63LS) MPa

2.64/0.68 [382/98]

2.64/0.69 [382/335]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.60/2.27 [377/329]

80 [176] 69 [156]

Heat exchanger outlet (TH6) 0 [32] 0 [32]

Accumulator inlet -2 [28] 1 [34]

Temp. of each sec- tion

Accumulator outlet -3 [27] 1 [34]

°C [°F]

Compressor inlet -3 [27] 1 [34]

Compressor shell bottom 40 [104] 40 [104]

LEV inlet 34 [93]

Heat exchanger inlet 67 [153]

Show 23 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Unit · Indoor unit · Model - 30/30/36/36/36 · Operating conditions · Main pipe · 5 [16-3/18"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 295/295/350/350 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 183 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 183 · click to enlarge
Page 183

[ VIII Test Run Mode ]

PURY-P192TSHMU-A

PURY-P96THMU-A PURY-P96THMU-A

Model name of BC controller CMB-P108NU-GA

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 6

Branch pipe 10 [32-3/4"]

Total pipe length 65 [213-1/4"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 42.4 [93]

Electric current A 44.2

Compressor frequency Hz 71 71

BC controller (1/2/3) 110/110/1050

High pressure(63HS1)/ Low pressure(63LS) MPa

2.67/0.68 [387/98]

2.79/0.58 [405/81]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.63/2.31 [381/335]

80 [176] 80 [176]

Heat exchanger outlet (TH6) 0 [32] 0 [32]

Accumulator inlet -2 [28] -2 [28]

Temp. of each sec- tion

Accumulator outlet -3 [27] -3 [27]

°C [°F]

Compressor inlet -3 [27] -3 [27]

Compressor shell bottom 40 [104] 40 [104]

LEV inlet 38 [100]

Heat exchanger inlet 70 [158]

Show 23 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Unit · Indoor unit · Model - 30/30/30/30/36/36 · Operating conditions · Main pipe · 5 [16-3/18"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 295/295/295/295/350/350 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 184 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 184 · click to enlarge
Page 184

[ VIII Test Run Mode ]

PURY-P216TSHMU-A

PURY-P120THMU-A PURY-P96THMU-A

Model name of BC controller CMB-P1013NU-GA

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 6

Branch pipe 10 [32-3/4"]

Total pipe length 65 [213-1/4"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 43.0 [95]

Electric current A 54.0

Compressor frequency Hz 81 71

BC controller (1/2/3) 110/110/1120

High pressure(63HS1)/ Low pressure(63LS) MPa

2.62/0.64 [380/92]

2.62/0.68 [380/98]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.60/2.27 [377/329]

73 [163] 80 [176]

Heat exchanger outlet (TH6) 2 [36] 0 [32]

Accumulator inlet -1 [30] -2 [28]

Temp. of each sec- tion

Accumulator outlet -1 [30] -3 [27]

°C [°F]

Compressor inlet -1 [30] -3 [27]

Compressor shell bottom 40 [104] 40 [104]

LEV inlet 33 [91]

Heat exchanger inlet 68 [154]

Show 23 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Unit · Indoor unit · Model - 36/36/36/36/36/36 · Operating conditions · Main pipe · 5 [16-3/18"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 350/350/350/350/350/350 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 185 of the Mitsubishi Electronics P96 user manual — °C [°F]
Page 185 · click to enlarge
Page 185

[ VIII Test Run Mode ]

PURY-P240TSHMU-A

PURY-P120THMU-A PURY-P120THMU-A

Model name of BC controller CMB-P1013NU-GA

21.1°C/- [70°F/-]

DB/WB

Outdoor 8.3°C/6.1°C [47°F/43°F]

No. of connected units

No. of units in operation 7

Branch pipe 10 [32-3/4"]

Total pipe length 75 [229-5/8"]

Fan speed - Hi

Amount of refrigerant kg [lbs-oz] 44.6 [98]

Electric current A 58.3

Compressor frequency Hz 81 81

BC controller (1/2/3) 110/110/1190

High pressure(63HS1)/ Low pressure(63LS) MPa

2.57/0.64 [372/92]

2.57/0.64 [372/92]

BC controller on the liquid side(PS1)/ Intermediate part(PS3)

2.54/2.22 [368/321]

73 [163] 73 [163]

Heat exchanger outlet (TH6) 2 [36] 2 [36]

Accumulator inlet -1 [30] -1 [30]

Temp. of each sec- tion

Accumulator outlet -1 [30] -1 [30]

°C [°F]

Compressor inlet -1 [30] -1 [30]

Compressor shell bottom 40 [104] 40 [104]

LEV inlet 28 [82]

Heat exchanger inlet 67 [153]

Show 23 more labels / short text on this page
Outdoor unit model · Operation · Ambient tempera- ture · Indoor · Unit · Indoor unit · Model - 24/36/36/36/36/36/36 · Operating conditions · Main pipe · 5 [16-3/18"] · Piping · m [ft] · Outdoor unit · Voltage V 230 · Indoor unit · 203/350/350/350/350/350/350 · LEV open- ing · Pulse · Pressure · [psi] · Discharge (TH4) · Outdoor unit · Indoor unit
Page 186 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 186 · click to enlarge
Page 186

[1] Error Code Lists 179 [2] Responding to Error Display on the Remote Controller 182 [3] Investigation of Transmission Wave Shape/Noise 270 [4] Troubleshooting Principal Parts 273 [5] Refrigerant Leak 314 [6] Compressor Replacement Instructions 316 [7] Servicing the BC controller 327 [8] Troubleshooting Using the Outdoor Unit LED Error Display 330

Page 187 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 187 · click to enlarge
Page 187

- 178 -

Page 188 of the Mitsubishi Electronics P96 user manual — LOSSNAY
Page 188 · click to enlarge
Page 188

IX Troubleshooting [1] Error Code Lists

LOSSNAY

Serial communication error O

1102 1202 - Discharge temperature fault O

1301 - - Low pressure fault O

1302 1402 - High pressure fault O

1500 1600 - Refrigerant overcharge O

- 1605 - Preliminary suction pressure fault O

2500 - - Drain sensor submergence O

2502 - - Drain pump fault O O

2503 - - Drain sensor (Thd) fault O O

2600 - - Water leakage O

2601 - - Water supply cutoff O

3121 - - Out-of-range outside air temperature O

4102 4152 - Open phase O

4106 - - Transmission power supply fault O

4115 - - Power supply signal sync error O

4116 - - RPM error/Motor error O O

[108] Abnormal bus voltage drop O

[109] Abnormal bus voltage rise O

[111] Logic error O

[131] Low bus voltage at startup O

4230 4330 - Heatsink overheat protection O

4240 4340 - Overload protection O

[101] IPM error O

[102] ACCT overcurrent (H/W detection) O

[103] DCCT overcurrent (H/W detection) O

[104] Short-circuited IPM/Ground fault O

[105] Overcurrent error due to short-circuited motor O

[106] Instantaneous overcurrent O

4260 - - Heatsink overheat protection at startup O

Return air temperature (TH21) O

5101 1202 - Temperature sensor fault

OA processing unit inlet temperature (TH4) O

Show 19 more labels / short text on this page
Searched unit · Prelimi- · Error (prelim- · Remote controller · Error Code · nary error code · Outdoor unit · BC controller · inary) detail · Error code definition · Indoor unit · code · 01 05 (Note) · 0403 4300 4305 · 4220 4225 (Note) · 4320 4325 (Note) · 4250 4255 (Note) · 4350 4355 (Note) · [107] Overcurrent O
Page 189 of the Mitsubishi Electronics P96 user manual — O
Page 189 · click to enlarge
Page 189

LOSSNAY

Indoor unit pipe tempera- ture (TH22) O

5102 1217 - Temperature sensor fault

OA processing unit pipe temperature (TH2) O

Indoor unit gas-side pipe temperature (TH23) O

OA processing unit gas- side pipe temperature (TH3)

5103 1205 00 Temperature sensor fault

O

Pipe temperature at heat exchanger outlet (TH3) O

OA processing unit intake air temperature (TH1) O

Detectable only by the All- Fresh type in- door units

5104 1202 - Temperature sensor fault

Outside temperature (TH24) O

Outdoor unit discharge temperature (TH4) O

5105 1204 - Temperature sensor fault

Accumulator inlet tempera- ture (TH5) O

5106 1216 - Temperature sensor fault

Heat exchanger inlet tem- perature (TH6) O

5107 1221 - Temperature sensor fault Outside temperature (TH7) O

5110 1214 01 Temperature sensor fault

Heatsink temperature (THHS) O

Liquid inlet temperature (TH11) O

5112 - - Bypass outlet temperature (TH12) O

Temperature sensor fault (BC controller)

5115 - - LEV3 outlet temperature (TH15) O

5116 - - LEV3 inlet temperature (TH16) O

5201 - - High-pressure sensor fault (63HS1) O

5201 1402 - High-pressure sensor fault (Outdoor unit HPS/BC controller PS1) O O

5203 - - Intermediate pressure sensor fault (BC controller PS3) O

[115] ACCT sensor fault O

[117] ACCT sensor circuit fault O

[119] Open-circuited IPM/Loose ACCT connector O

[120] Faulty ACCT wiring O

5401 - - Temperature sensor fault O

5701 - - Loose float switch connector O

Show 14 more labels / short text on this page
Searched unit · Error (prelim- · Prelimi- · Remote controller · Error Code · nary error code · BC controller · inary) detail · Error code definition · Outdoor unit · Indoor unit · code · 5111 - - · 5301 4300
Page 190 of the Mitsubishi Electronics P96 user manual — LOSSNAY
Page 190 · click to enlarge
Page 190

LOSSNAY

6201 - - Remote controller board fault (nonvolatile memory error) O

6202 - - Remote controller board fault (clock IC error) O

6600 - - Address overlaps O

6601 - - Polarity setting error O

6602 - - Transmission processor hardware error O

6603 - - Transmission line bus busy error O

6606 - - Communication error between device and trans- mission processors O

6607 - - No ACK error O

6608 - - No response error O

6831 - - MA controller signal reception error (No signal re- ception) O O

6832 - - MA remote controller signal transmission error (Synchronization error) O O

6833 - - MA remote controller signal transmission error (H/ W error) O O

6834 - - MA controller signal reception error (Start bit de- tection error) O O

7100 - - Total capacity error O

7101 - - Capacity code setting error O O O

7102 - - Wrong number of connected units O O

7105 - - Address setting error O

7106 - - Attribute setting error O

7107 - - Port setting error O

7110 - - Connection information signal transmission/recep- tion error O

7111 - - Remote controller sensor fault O O

7113 - - Function setting error O

7117 - - Model setting error O

7130 - - Incompatible unit combination O

The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to inverter on fan inverter. Example Code 4225 (detail code 108): Bus voltage drop in the fan inverter system Code 4230 : Heatsink overheat protection in the inverter system

The last digit Inverter system

0 or 1 Compressor inverter system

5 Fan inverter system

Show 12 more labels / short text on this page
Searched unit · Error (prelim- · Prelimi- · Remote controller · Error Code · nary error code · BC controller · inary) detail · Error code definition · Outdoor unit · Indoor unit · code
Page 191 of the Mitsubishi Electronics P96 user manual — CN22 CN2
Page 191 · click to enlarge
Page 191

[2] Responding to Error Display on the Remote Controller

1. Error Code

0403 (THMU-A)

Serial communication error

2. Error definition and error detection method Serial communication error between the control board and the INV board on the compressor, and between the control board and the Fan board Detail code 01: Between the control board and the INV board Detail code 05: Between the control board and the Fan board

3. Cause, check method and remedy (1) Faulty wiring

Check the following wiring connections. 1) Between Control board and Fan board

Control board FAN board

CN2 CN21 CN4 CN4 CN332 CN18V

2. Between Fan board and INV board

FAN board INV board

CN22 CN2

CN5V

CN4 CN4

(2) INV board failure, Fan board failure and Control board failure

Replace the INV board or the Fan board or control board when the power turns on automatically, even if the power source is reset.

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 192 of the Mitsubishi Electronics P96 user manual — CN22 CN2
Page 192 · click to enlarge
Page 192

1. Error Code

0403 (YHMU-A)

Serial communication error

2. Error definition and error detection method Serial communication error between the control board and the INV board on the compressor, and between the control board and the Fan board Detail code 01: Between the control board and the INV board Detail code 05: Between the control board and the Fan board

3. Cause, check method and remedy (1) Faulty wiring

Check the following wiring connections. 1) Between Control board and Fan board

Control board FAN board

CN2 CN21 CN4 CN5 CN332 CN18V

2. Between Fan board and INV board

FAN board INV board

CN22 CN2

CN5V

CN4 CN4

(2) INV board failure, Fan board failure and Control board failure

Replace the INV board or the Fan board or control board when the power turns on automatically, even if the power source is reset.

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 193 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 193 · click to enlarge
Page 193

1. Error Code

Discharge temperature fault

2. Error definition and error detection method 1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically. 2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the second stop of the outdoor unit described above, the mode will be changed to 3 - minute restart mode, then the outdoor unit will restart in 3 minutes. 3) If the discharge temperature of 120°C [248°F] or more is detected (the third detection) within 30 minutes after the stop of the outdoor unit described above (regardless of the first or the second stop), the outdoor unit will make an error stop, and the error code "1102" will be displayed. 4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor unit, the detection is regarded as the first detection, and the operation described in step 1 above will start. 5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the LED display.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Gas leak, gas shortage Refer to the page on refrigerant amount evaluation.(page 157)

(2) Overload operation Check operating conditions and operation status of indoor/ outdoor units.

(3) LEV failure on the indoor unit Perform a heating operation and check the operation. Cooling: LEV on the indoor unit LEV1,2,3 SVM1,2 SVA,C Heating: LEV on the indoor unit LEV3 SVB SV4a - 4d Refer to the page on troubleshooting LEV.(page 279)

(4) BC controller LEV malfunction Cooling only : LEV3 Cooling main : LEV1,2,3 Heating only or heating main : LEV3 Defrost : LEV3

(5) BC controller SVM1 and 2 malfunction -> Cooling only or defrost

(6) BC controller SVA malfunction -> Cooling only or cooling main

(7) BC controller SVB malfunction -> Heating only or heating main

(8) Solenoid valve SV malfunction (4a-4c (P72 model) ,4a-4d (P96 and P120 models)) :heating only, heating main

(9) Port address setting error. Confirm the port address of the indoor unit.

(10) Closed ball valve Confirm that the ball valve is fully open.

(11) Outdoor fan (including fan parts) failure, mo- tor failure, or fan controller malfunction Rise in discharge temp. by low pressure drawing for (3) - (11).

Check the fan on the outdoor unit. Refer to the section on troubleshooting the outdoor unit fan.(page 279)

(12) Gas leak between low and high pressures (4-way valve failure, Compressor failure, So- lenoid valve (SV1a) failure)

Perform a cooling or heating operation and check the opera- tion.

(13) Thermistor failure (TH4)

Check the thermistor resistor.(page 217)

(14) Input circuit failure on the controller board thermistor

Check the inlet air temperature on the LED monitor.

Page 194 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 194 · click to enlarge
Page 194

1. Error Code

Low pressure fault

2. Error definition and error detection method When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before start-up, the operation immediately stops.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inner pressure drop due to a leakage. Refer to the section on troubleshooting the low pressure sensor.(page 274) (2) Low pressure sensor failure

(3) Short-circuited pressure sensor cable due to torn outer rubber

(4) A pin on the male connector is missing.

(6) Failure of the low pressure input circuit on the controller board

(5) Disconnected wire

Page 195 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 195 · click to enlarge
Page 195

1. Error Code

High pressure fault 1 (Outdoor unit) 2. Error definition and error detection method 1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out- door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically. 2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 min- utes after the first stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically. 3) If the pressure of 3.87MPa [561psi] or higher is detected by the pressure sensor (the third detection) within 30 minutes of the second stop of the outdoor unit, the outdoor unit will make an error stop, and the error code "1302" will be displayed. 4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection is regarded as the first detection, and the operation described in step 1 above will start. 5) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display. 6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects 4.15+0,-0.15 MPa [601+0,-22 psi] 7) Open phase due to unstable power supply voltage may cause the pressure switch to malfunction or cause the units to come to an abnormal stop. 3. Cause, check method and remedy

Cause Check method and remedy (1) Indoor unit LEV actuation failure Perform a heating operation and check the op- eration. Cooling: LEV on the indoor unit LEV1,2,3 SVM1,1b,2,2b SVA Heating: LEV on the indoor unit LEV3 SVM2,2b SVB,SV4a - 4d Refer to the page on troubleshooting for LEV and solenoid valve.(page 279)

(2) BC controller LEV malfunction Heating only or heating main : Indoor LEV 3 Defrost : LEV3

(3) BC controller SVM1 and 2 malfunction ->Cooling only or defrost (4) BC controller SVA and SVC malfunction ->Cooling only or cooling main (5) BC controller SVB malfunction ->Heating only or heating main Solenoid valve SV malfunction(4a-4c (P72 model) ,4a-4d(P96 and P120 models)) ->Cooling only or cooling main

(6) Port address setting error. Confirm the port address of the indoor unit. (7) Refrigerant service valve actuation failure Confirm that the refrigerant service valve is fully (8) Short cycle on the indoor unit side Check the indoor units for problems and correct them, if any. (9) Clogged filter on the indoor unit

(10) Reduced air flow due to dirty fan on the indoor unit fan

(11) Dirty heat exchanger of the indoor unit

(12) Indoor fan (including fan parts) failure or motor failure Items (7) through (12) above reduce the condensing capability of the unit, resulting in high-pressure rise during heating oper- ation.

(13) Short cycle on the outdoor unit Check the outdoor units for problems and cor- rect them, if any. (14) Dirty heat exchanger of the outdoor unit

(15) Outdoor fan (including fan parts) failure, motor failure, or fan controller malfunction Items (13) through (15) above reduce the condensing capabil- ity of the unit, resulting in high-pressure rise during cooling op- eration.

Check the fan on the outdoor unit. Refer to the section on troubleshooting the out- door unit fan.(page 279)

(16) Solenoid valve (SV1a) malfunction The by-pass valve (SV1a) can not control rise in high pressure.

Refer to the section on troubleshooting the sole- noid valve.(page 275)

(17) Thermistor failure (TH3, TH7) Check the thermistor resistor.(page 217) (18) Pressure sensor failure Refer to the page on the troubleshooting of the high pressure sensor. (page 273) (19) Failure of the thermistor input circuit and pressure sensor input circuit on the controller board

Check the sensor temperature/pressure on the LED monitor. (20) Thermistor mounting problem (TH3, TH7) Check the sensor temperature/pressure on the LED monitor. (21) Disconnected male connector on the pressure switch (63HS1) or disconnected wire (22) Voltage drop caused by unstable power supply voltage Check the input voltage at the power supply ter- minal block (TB1).

Page 196 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 196 · click to enlarge
Page 196

1. Error Code

High pressure fault 2 (Outdoor unit)

2. Error definition and error detection method If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an abnormal stop, and error code "1302" will be displayed.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inner pressure drop due to a leakage. Refer to the page on the troubleshooting of the high pressure sensor.(page 273) (2) Pressure sensor failure

(3) Shorted-circuited pressure sensor cable due to torn outer rubber

(4) A pin on the male connector on the pressure sensor is missing or contact failure

(5) Disconnected pressure sensor cable

(6) Failure of the pressure sensor input circuit on the controller board

1. Error Code

Refrigerant overcharge

2. Error definition and error detection method An error can be detected by the discharge temperature superheat. 1) If the formula "TdSH 10°C [18°F]" is satisfied during operation (first detection), the outdoor unit stops, goes into the 3-minute restart mode, and starts up in three minutes. 2) If the formula "TdSH 10°C [18°F]" is satisfied again within 30 minutes of the first stoppage of the outdoor unit (second de- tection), the unit comes to an abnormal stop, and the error code "1500" appears. 3) If the formula "TdSH 10°C [18°F]" is satisfied 30 minutes or more after the first stoppage of the outdoor unit, the same se- quence as Item "1 above (first detection) is followed. 4) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Overcharged refrigerant Refer to the page on refrigerant amount evaluation.(page 157)

(2) Thermistor input circuit failure on the control board Check the temperature and pressure readings on the sen- sor that are displayed on the LED monitor.

(3) Faulty mounting of thermistor (TH4) Check the temperature and pressure readings on the thermistor that are displayed on the LED monitor.

Page 197 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 197 · click to enlarge
Page 197

1. Error Code

Drain sensor submergence (Models with a drain sensor)

2. Error definition and error detection method 1) If an immersion of the drain sensor in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being detected, humidifier output cannot be turned on.(Applicable to the units manufactured in or after October 1996) 2) If the immersion of the sensor in the water is detected four consecutive times at an hour interval, this is considered water leak- age, and "2500" appears on the monitor. 3) Detection of water leakage is also performed while the unit is stopped. 4) Preliminary water leakage is cancelled when the following conditions are met: One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON. The operation mode is changed to Cool/Dry. Liquid pipe temperature - inlet temperature is -10°C[ -18°F]

3. Cause, check method and remedy

Cause Check method and remedy

(1) Drain water drainage problem

Check for proper drainage.

ŒClogged drain pump ŒClogged drain piping ŒBackflow of drain water from other units

(2) Adhesion of water drops to the drain sensor

1. Check for proper lead wire installation.

ŒTrickling of water along the lead wire ŒRippling of drain water caused by filter clogging

2. Check for clogged filter.

(3) Failure of the relay circuit for the solenoid valve Replace the relay.

(4) Indoor unit control board failure

If the above item checks out OK, replace the indoor unit control board.

ŒDrain sensor circuit failure

Page 198 of the Mitsubishi Electronics P96 user manual — ON
Page 198 · click to enlarge
Page 198

1. Error Code

Drain sensor submergence (Models with a float switch)

2. Error definition and error detection method 1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being detected, humidifier output cannot be turned on. 2) If the drain pump turns on within one hour after preliminary water leakage is detected and the above-mentioned condition is detected two consecutive times, water leakage error water leakage is detected, and "2500" appears on the monitor. 3) Detection of water leakage is also performed while the unit is stopped. 4) Preliminary water leakage is cancelled when the following conditions are met: One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON. The operation mode is changed to Cool/Dry. Liquid pipe temperature - inlet temperature - 10°C[-18°F]

3. Cause, check method and remedy

Cause Check method and remedy

(1) Drain water drainage problem

Check for proper drainage.

ŒClogged drain pump ŒClogged drain piping ŒBackflow of drain water from other units

(2) Stuck float switch Check for slime in the moving parts of the float switch.

Check for normal operation of the float switch.

(3) Float switch failure Check the resistance with the float switch turned on and turned off.

Drain pump operation triggered by a submergence of the liquid level sensor (except during the Cooing/Dry mode)

6 minutes 6 minutes

ON

OFF

ON

OFF

15 seconds 15 seconds

Submergence of the sensor Submergence of the sensor Preliminary water leakage

Sensor in the air Sensor in the air

Submergence of the sensor Water leakage

Within 1-hour period Within 1-hour period

Show 6 more labels / short text on this page
<Reference> · Drain pump output · Float switch input · 15 seconds · 15 seconds · 15 seconds
Page 199 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 199 · click to enlarge
Page 199

1. Error Code

Drain pump fault (Models with a drain sensor)

2. Error definition and error detection method 1) Make the drain sensor thermistor self-heat. If the temperature rise is small, it is interpreted that the sensor is immersed in water. This condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode. 2) If another episode of the above condition is detected during the preliminary error, this is considered a drain pump error, and "2502" appears on the monitor. 3) This error is always detected while the drain pump is in operation. 4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met. "Liquid pipe temperature - inlet temperature - 10 °C [ -18°F] " has been detected for 30 minutes. The immersion of drain sensor is detected 10 consecutive times. The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage

of the outdoor unit. 5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant circuit that are in any mode other than Fan or Stop to an error stop. "2502" appears on the monitor of the units that came to an error stop. 6) Forced stoppage of the outdoor unit Detection timing: The error is detected whether the unit is in operation or stopped. 7) Ending criteria for the forced stoppage of outdoor unit Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig- erant circuit. Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller. (Note) Items 1) - 3) and 4) - 7) are detected independently from each other.

The address and attribute that appear on the remote controller are those of the indoor unit (or OA processing unit) that caused the error.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Drain pump failure Check for proper functioning of the drain pump.

(2) Drain water drainage problem

Check for proper drainage.

ŒClogged drain pump ŒClogged drain piping

(3) Adhesion of water drops to the drain sensor

1. Check for proper lead wire installation.

ŒTrickling of water along the lead wire ŒRippling of drain water caused by filter clogging

2. Check for clogged filter.

(4) Indoor unit control board failure

If the above item checks out OK, replace the indoor unit control board.

ŒDrain pump drive circuit failure ŒDrain heater output circuit failure

(5) Items (1) through (4) above and an indoor unit elec- tronic valve closure failure (leaky valve) occurred si- multaneously.

Check the solenoid valves on the indoor unit for leaks.

Page 200 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 200 · click to enlarge
Page 200

1. Error Code

Drain pump fault (Models with a float switch)

2. Error definition and error detection method 1) The immersion of sensor tip in water is detected by the ON/OFF signal from the float switch. Submergence of the sensor

When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in water. Sensor in the air

When it is detected that the float switch has been OFF for 15 seconds, it is interpreted that the sensor tip is not immersed in water. 2) If it is detected that the float switch has been ON for 3 minutes after the immersion of the sensor tip was detected, this is con- sidered a drain pump failure, and "2502" appears on the monitor.

The total time it takes for this error to be detected is 3 minutes and 15 seconds, including the time it takes for the first im-

mersion of the sensor tip to be detected. 3) Detection of drain pump failure is performed while the unit is stopped. 4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met. "Liquid pipe temperature - inlet temperature - 10°C [ -18°F] " has been detected for 30 minutes. It is detected by the float switch that the sensor tip has been immersed in water for 15 minutes or more. The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage

of the outdoor unit. 5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant circuit that are in any mode other than Fan or Stop to an error stop. 6) Forced stoppage of the outdoor unit Detection timing: The error is detected whether the unit is in operation or stopped. This error is detected whether the unit is in operation or stopped. 7) Ending criteria for the forced stoppage of outdoor unit Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig- erant circuit. Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller. (Note) Items 1) - 3) and 4) - 7) are detected independently from each other.

The address and attribute that appear on the remote controller are those of the indoor unit (or OA processing unit) that caused the error.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Drain pump failure Check for proper functioning of the drain pump mechanism

(2) Drain water drainage problem

Check for proper drainage.

ŒClogged drain pump ŒClogged drain piping

(3) Stuck float switch Check for slime in the moving parts of the float switch.

Check for normal operation of the float switch.

(4) Float switch failure Check the resistance with the float switch turned on and turned off.

(5) Indoor unit control board failure

Replace indoor unit control board.

ŒDrain pump drive circuit failure ŒFloat switch input circuit failure

(6) Items (1) through (5) above and an indoor unit electronic valve closure failure (leaky valve) occurred simultane- ously.

Check the solenoid valves on the indoor unit for leaks.

Page 201 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 201 · click to enlarge
Page 201

1. Error Code

Drain sensor (Thd) fault

2. Error definition and error detection method Œ If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary

error, and the unit goes into the 3-minute restart delay mode. ŒIf another episode of the above condition is detected during the preliminary error, this is considered a drain sensor error.(If

the short or open circuit of the thermistor is no longer detected, normal operation will be restored in 3 minutes.) ŒThis error is detected when one of the following conditions are met.

During Cool/Dry operation Liquid pipe temperature minus inlet temperature is equal to or smaller than - 10°C[ -18°F] (except during the defrost cycle) When the liquid temperature thermistor or suction temperature thermistor or short or open circuited. Drain pump is in operation. One hour has elapsed since the drain sensor went off.

Short90 °C [194 °F] or above Open: - 20 °C [-4 °F] or below

3. Cause, check method and remedy

Cause Check method and remedy

(1) Faulty connector (CN31) insertion. 1) Check for connector connection failure. Reinsert the connector, restart the operation, and check for proper operation.

(2) Broken or semi-broken thermistor wire 2) Check for a broken thermistor wire.

(3) Thermistor failure 3) Check the resistance of the thermistor. 0°C[32 °F]:6.0k 10°C[50 °F]:3.9k 20°C[68°F]:2.6k 30°C[86°F]:1.8k 40°C[104 °F]:1.3k

(4) Indoor unit control board (error detection circuit) failure

4. Replace the indoor unit control board if the problem recurs when the unit is operated with the No.-1 and No.-2 pins on the drain sensor connector (CN31) being short-circuited. If the above item checks out OK, there are no problems with the drain sensor. Turn off the power and turn it back on.
Page 202 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 202 · click to enlarge
Page 202

1. Error Code

Water leakage

2. Cause, check method and remedy Check that water does not leak from the pipes in such as the humidifier.

1. Error Code

Water supply cutoff

2. Cause, check method and remedy

Cause Check method and remedy

(1) The water tank of the humidifier is empty. Check the amount of supply water. Check for the solenoid valve and for the connection.

(2) The solenoid valve for humidification is OFF. Check the connector.

(3) Disconnected float switch Check the connecting part.

(4) Poor operation of float switch Check for the float switch.

(5) Frozen water tank Turn off the power source of the water tank to defrost, and turn it on again.

Page 203 of the Mitsubishi Electronics P96 user manual — TH7
Page 203 · click to enlarge
Page 203

1. Error Code

Out-of-range outside air temperature

2. Error definition and error detection method Œ When the thermistor temperature of -28°C[-18°F] or below has continuously been detected for 3 minutes during heating op-

eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm- istor temperature to determine when two outdoor units are in operation.) ŒThe compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop. (The

error display needs to be canceled by setting the remote controller.) ŒOutdoor temperature error is canceled if the units stop during error stop. (The error display needs to be canceled by setting

the remote controller.)

3. Cause, check method and remedy Check the following factors if an error is detected, without drop in the outdoor temperature.

Cause Check method and remedy

(1) Thermistor failure Check thermistor resistance.

(2) Pinched lead wire Check for pinched lead wire.

(3) Torn wire coating Check for wire coating.

(4) A pin on the male connector is missing or contact failure

Check connector.

(5) Disconnected wire Check for wire.

(6) Thermistor input circuit failure on the control board

Check the intake temperature of the sensor with the LED monitor. When the temperature is far different from the actual temper- ature, replace the control board.

-40 C [ -40 F ] and below (130 k ) Short detection 110 C [230 F ] and above (0.4 k )

TH7

· Open detection

Page 204 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 204 · click to enlarge
Page 204

1. Error Code

4102 (THMU-A)

Open phase

2. Error definition and error detection method Œ An open phase of the power supply (L1 phase, L2 phase) was detected at power on. Œ The L3 phase current is outside of the specified range.

The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Power supply problem

Check the input voltage to the power supply terminal block TB1.

ŒOpen phase voltage of the power supply ŒPower supply voltage drop

(2) Noise filter problem

ŒCheck the coil connections. ŒCheck for coil burnout. ŒConfirm that the voltage at the CN02 connector is 188 V or

ŒCoil problem ŒCircuit board failure

above.

(3) Wiring failure Confirm that the voltage at the control board connector CNAC is 188 V or above. If the voltage is below 188V, check the wiring connection between the noise filter board CN02 and control board CNAC. P72 model Confirm that the wiring between TB23 and INV board SC-T is put through CT3. P96 and P120 models Confirm that the wiring between the coil L3 and TB23 is put through ACCT3.

(4) Blown fuse Check F01 on the control board, F4, and F5 for a blown fuse. ->If a blown fuse is found, check for a short-circuiting or earth fault of the actuator.

(5) CT3 failure P72 model Replace the inverter if this problem is detected after the compres- sor has gone into operation. P96 and P120 models Replace the ACCT3 if this problem is detected after the compres- sor has gone into operation.

(6) Control board failure Replace the control board if none of the above is causing the problem.

Page 205 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 205 · click to enlarge
Page 205

1. Error Code

4102 (YHMU-A)

Open phase

2. Error definition and error detection method Œ An open phase of the power supply (L1 phase, L2 phase) was detected at power on. Œ The L3 phase current is outside of the specified range.

The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Power supply problem

Check the input voltage to the power supply terminal block TB1.

ŒOpen phase voltage of the power supply ŒPower supply voltage drop

(2) Noise filter problem

ŒCheck the coil connections. ŒCheck for coil burnout. ŒCheck that the voltage across TB21 and TB22 on the noise filter

ŒCoil problem ŒCircuit board failure

board is 414V or above.

(3) Wiring failure Confirm that the voltage at the control board connector CNAC is 190 V or above. If the voltage is below 190, check the wiring between noise filter CN6, noise filter CN2, transformer box, and control board CNAC. Confirm that the wiring between noise filter TB23 and INV board SC-L3 is put through CT3.

(4) Blown fuse Check F01 on the control board, F4, and F5 for a blown fuse. ->If a blown fuse is found, check for a short-circuiting or earth fault of the actuator.

(5) CT3 failure Replace the inverter if this problem is detected after the compres- sor has gone into operation.

(6) Control board failure Replace the control board if none of the above is causing the problem.

Page 206 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 206 · click to enlarge
Page 206

1. Error Code

<Transmission power supply fault error detail FF (Outdoor unit)> 2. Error definition and error detection method Transmission power output failure

3. Cause 1) Wiring failure 2) Transmission power supply cannot output voltage because overcurrent was detected. 3) Voltage cannot be output due to transmission power supply problem. 4) Transmission voltage detection circuit failure
4. Check method and remedy Check the items in IX [4] -8- (2) on all outdoor units in the same refrigerant circuit.

<Transmission power supply fault other than error detail code FF (Outdoor unit)> 2. Error definition and error detection method Transmission power reception failure

3. Cause One of the outdoor units stopped supplying power, but no other outdoor units start supplying power.
4. Check method and remedy Check the items in IX [4] -8- (2) on all outdoor units in the same refrigerant circuit.
Page 207 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 207 · click to enlarge
Page 207

1. Error Code

4115 (THMU-A)

Power supply signal sync error

2. Error definition and error detection method The frequency cannot be determined when the power is switched on.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Power supply error Check the voltage of the power supply terminal block (TB1).

(2) Noise filter problem

ŒCheck the coil connections. ŒCheck for coil burnout. ŒConfirm that the voltage at the CN02 connector is

ŒCoil problem ŒCircuit board failure

188 V or above.

(3) Faulty wiring Check fuse F01 on the control board (or F1, F2).

(4) Wiring failure Between noise filter board CN02 and control board CNAC

Confirm that the voltage at the control board con- nector CNAC is 188 V or above.

(5) Control board failure If none of the items described above is applicable, and if the trouble reappears even after the power is switched on again, replace the control board.

1. Error Code

4115 (YHMU-A)

Power supply signal sync error

2. Error definition and error detection method The frequency cannot be determined when the power is switched on.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Power supply error Check the voltage of the power supply terminal block (TB1).

(2) Noise filter problem

ŒCheck the coil connections. ŒCheck for coil burnout. ŒCheck that the voltage across TB21 and TB22 on

ŒCoil problem ŒCircuit board failure

the noise filter board is 414V or above.

(3) Faulty wiring Check F01 on the control board, F4, and F5 for a blown fuse.

(4) Wiring failure Between noise filter CN3, noise filter CN2, transformer box, and control board CNAC

Confirm that the voltage at the control board con- nector CNAC is 190 V or above.

(5) Control board failure If none of the items described above is applicable, and if the trouble reappears even after the power is switched on again, replace the control board.

Page 208 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 208 · click to enlarge
Page 208

1. Error Code

RPM error/Motor error

2. Error definition and error detection method Œ LOSSNAY

The motor keep running even if the power is OFF. The thermal overload relay is ON. (Only for the three-phase model) ŒIndoor unit

If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected again, the display will appear.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Board failure Replace the board.

(2) Motor malfunction Check for the motor and the solenoid switch.

(3) Solenoid switch malfunction

Page 209 of the Mitsubishi Electronics P96 user manual — (3) Control board failure
Page 209 · click to enlarge
Page 209

1. Error Code

4220 4225 (THMU-A)

Abnormal bus voltage drop (Detail code 108)

2. Error definition and error detection method If Vdc 160V or less is detected during Inverter operation. (S/W detection)

3. Cause, check method and remedy (1) Power supply environment

Check whether the unit makes an instantaneousstop when the detection result is abnormal or a power failure occurs. Check whether the power voltage is 188V or less across all phases. (2) Voltage drop detected

4220 P72 model ŒCheck the voltage between the tab terminal TB-P and TB-N on the INV board while the inverter is stopped. -> Check the fol-

lowing items if it is 253V or above.

1) Confirm on the LED monitor that the bus voltage is above 160 V. Replace the INV board if it is below 160 V. 2) Check the voltage at CN505 on the control board. ->Go to (3). 3) Check the coil connections (L1 - L3) and for coil burnout. 4) Check the wiring connections between the following sections Between the noise filter board and INV board. Between the INV board and DCL. Between the INV board and C1. Replace 72C if no problems are found.-> Check the following items if the voltage is below 253V. 1) Check the coil connections (L1 - L3) and for coil burnout. 2) Check the wiring between the noise filter board and INV board. 3) Check the connection to SC-P1 and SC-P2 on the INV board. 4) Check the in-rush current resistor value. Replace the INV board if no problems are found.

P96 and P120 models ŒCheck the voltage between SC-P1 and IPM N terminals on the INV board while the inverter is stopped.

-> Check the following items if it is 253V or above.

1) Confirm on the LED monitor that the bus voltage is above 160 V. Replace the INV board if it is below 160 V. 2) Check the voltage at CN505 on the control board. ->Go to (3). 3) Check the coil connections (L1 - L3) and coil burnout. 4) Check the resistance of the diode stack. ->Refer to IX [4] -7- (6). 5) Check the wiring connections between the following sections: Between the noise filter board and INV board. Between the INV board and C1. Replace the noise filter board if no problems are found. -> Check the following items if the voltage is below 253 V. 1) Check the connection to SC-P1 and IPM N on the INV board. 2) Check the wiring between the noise filter board and INV board. 3) Check the resistance of the diode stack. ->Refer to IX [4] -7- (6). 4) Check the in-rush current resistor value. ->Refer to IX [4] -7- (4). 5) Replace the noise filter board.

4225 ŒCheck the voltage at CNVDC on the Fan board while the inverter is stopped.

->Check the following items if it is 253 V or above.

1. Check the voltage at CN505 on the control board. ->Go to 3). 2) Check the coil connections (L1 - L3) and for coil burnout. 3) Check the wiring connections. Replace 72C if no problems are found. (P96 and P120 models: Replace the noise filter board.) If the problem recurs after replacing 72C, replace the Fan board. -> Check the following items if the voltage is below 253V. 1) Check the CNVDC connector connection.

(3) Control board failure

Confirm that a voltage of 208-230 VAC is applied to the connector CN505 on the control board during inverter operation. ->If voltage is absent, check the control board, fuse F01, or (F1, F2). If no problems are found, replace the control board.

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 210 of the Mitsubishi Electronics P96 user manual — (3) Control board failure
Page 210 · click to enlarge
Page 210

1. Error Code

4220 4225 (YHMU-A)

Abnormal bus voltage drop (Detail code 108)

2. Error definition and error detection method If Vdc 289V or less is detected during Inverter operation. (S/W detection)

3. Cause, check method and remedy (1) Power supply environment

Check whether the unit makes an instantaneous stop when the detection result is abnormal or a power failure occurs. Check whether the power voltage (Between L1 and L2, L2 and L3, and L1 and L3) is 414V or less across all phases. (2) Voltage drop detected

4220 ŒCheck the voltage between the FT-P and FT-N terminals on the INV board while the inverter is stopped and if it is 420 V or

above, check the following items.

1) Confirm on the LED monitor that the bus voltage is above 289V. Replace the INV board if it is below 289 V. 2) Check the voltage at CN72 on the control board. ->Go to (3). 3) Check the noise filter coil connections and for coil burnout. 4) Check the wiring connections between the following sections Between the noise filter board and INV board. Between the INV board and DCL. Replace 72C if no problems are found. 5) Check the IGBT module resistance on the INV board (Refer to the Trouble shooting for IGBT module). ŒCheck the voltage between the FT-P and FT-N terminals on the INV board while the inverter is stopped and if it is less than

420 V, check the following items. 1) Check the coil connections and for coil burnout on the noise filter. 2) Check the wiring between the noise filter board and INV board. 3) Check the connection to SCP1 and SC-P2 on the INV board. 4) Check the in-rush current resistor value. 5) Check the 72C resistance value. 6) Check the DCL resistance value. Replace the INV board if no problems are found.

4225 ŒCheck the voltage at CNVDC on the Fan board while the inverter is stopped and if it is 420 V or above, check the following

items.

1. Check the voltage at CN72 on the control board. ->Go to 3). 2) Check the noise filter coil connections and for coil burnout. 3) Check the wiring connections between the following sections Between the INV board and the Fan board. 4) Check contents 4220 Replace the Fan board if no problems are found. Œ Check the voltage at CNVDC on the Fan board while the inverter is stopped and if it is less than 420 V, check the following

items.

1. Check the state of the wiring connections between the INV board and the Fan board. 2) Check contents 4220 Replace the Fan board if no problems are found.

(3) Control board failure

Check that 12VDC is applied to connector CN72 on the control board while the inverter is operating. If voltage is absent or the wrong voltage is applied, check the fuse F01. Replace the control board if no problems are found with the fuse.

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 211 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy (1) Different voltage connection
Page 211 · click to enlarge
Page 211

1. Error Code

4220 4225 (THMU-A)

Abnormal bus voltage rise (Detail code 109)

2. Error definition and error detection method If Vdc 400V is detected during inverter operation.

3. Cause, check method and remedy (1) Different voltage connection

Check the power supply voltage on the power supply terminal block (TB1). (2) INV board failure

If the problem recurs, replace the INV board. In the case of 4220: INV board In the case of 4225: Fan board

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

1. Error Code

4220 4225 (YHMU-A)

Abnormal bus voltage rise (Detail code 109)

2. Error definition and error detection method If Vdc 830V is detected during inverter operation.

3. Cause, check method and remedy (1) Different voltage connection

Check the power supply voltage on the power supply terminal block (TB1). (2) INV board failure

If the problem recurs, replace the INV board. In the case of 4220: INV board In the case of 4225: Fan board

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 212 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 212 · click to enlarge
Page 212

1. Error Code

4220 4225 (THMU-A) (P96 and P120 models)

VDC error (Detail code 110)

2. Error definition and error detection method Bus voltage abnormality If Vdc 400V or Vdc 160V is detected. (H/W detection)
3. Cause, check method and remedy Same as detail code No.108 and 109 of 4220 error

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 213 of the Mitsubishi Electronics P96 user manual — In the case of 4225
Page 213 · click to enlarge
Page 213

1. Error Code

4220 4225 (THMU-A)

Logic error (Detail code 111)

2. Error definition and error detection method H/W error If only the H/W error logic circuit operates, and no identifiable error is detected.

3. Cause, Check method and remedy In the case of 4220

Cause Check method and remedy

(2) INV board failure Refer to IX [4] -7- (2) [1].(page 295)

(3) IPM failure (P96 and P120 models only) Replace the IPM.

(4) DCCT failure (P96 and P120 models only) Replace the DCCT.

In the case of 4225

Cause Check method and remedy

(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 296)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

(1) External noise · (1) External noise

Page 214 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy (1) Inverter main circuit failure
Page 214 · click to enlarge
Page 214

1. Error Code

4220 4225 (YHMU-A)

Logic error (Detail code 111)

2. Error definition and error detection method H/W error If only the H/W error logic circuit operates, and no identifiable error is detected.

3. Cause, Check method and remedy In the case of 4220

Cause Check method and remedy

(2) INV board failure Refer to IX [4] -7- (2) [1].(page 303)

In the case of 4225

Cause Check method and remedy

(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 304)

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

1. Error Code

4220 4225 (YHMU-A)

Low bus voltage at startup (Detail code 131)

2. Error definition and error detection method When Vdc 160 V is detected just before the inverter operation.

3. Cause, check method and remedy (1) Inverter main circuit failure

Same as detail code 108 of 4220 error

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

(1) External noise · (1) External noise

Page 215 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 215 · click to enlarge
Page 215

1. Error Code

4230 (THMU-A)

Heatsink overheat protection

2. Error definition and error detection method When the heat sink temperature (THHS) remains at or above TOH is detected.

P72 model 100°C [212°F]

P96, P120 models 90°C [194°F]

3. Cause, check method and remedy

Cause Check method and remedy

(1) Fan board failure Refer to IX [4] -7- (2) [6].(page 296)

(2) Outdoor unit fan failure Check the outdoor unit fan operation. If any problem is found with the fan operation, check the fan motor. ->Refer to IX [4] -7- (2) [5].(page 296)

(3) Air passage blockage Check that the heat sink cooling air passage is not blocked

(4) THHS failure P72 model

1. Check for proper installation of the INV board IGBT. (Check for proper installation of the IGBT heatsink.)
2. Check for proper installation of the INV board IGBT. ->If an abnormal value appears, replace the INV board.
3. Check the THHS sensor reading on the LED monitor. ->If an abnormal value appears, check the sensor resistance, and replace the sensor as necessary.

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Model TOH · P96 andP120 models

Page 216 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 216 · click to enlarge
Page 216

1. Error Code

4230 (YHMU-A)

Heatsink overheat protection

2. Error definition and error detection method When the heat sink temperature (THHS) remains at or above 100°C [212°F] is detected.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Fan board failure Refer to IX [4] -7- (2) [6].(page 304)

(2) Outdoor unit fan failure Check the outdoor unit fan operation. If any problem is found with the fan operation, check the fan motor. ->Refer to IX [4] -7- (2) [5].(page 304)

(3) Air passage blockage Check that the heat sink cooling air passage is not blocked

(4) THHS failure 1) Check for proper installation of the INV board IGBT. (Check for proper instal- lation of the IGBT heatsink.)

2. Check the THHS sensor reading on the LED monitor. ->If an abnormal value appears, replace the INV board.

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 217 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 217 · click to enlarge
Page 217

1. Error Code

4240 (THMU-A)

Overload protection

2. Error definition and error detection method If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes or more during inverter operation.

P96, P120 model 53

P72 model 95°C [203°F]

P96, P120 model 80°C [175°F]

3. Cause, check method and remedy

Cause Check method and remedy

(1) Air passage blockage Check that the heat sink cooling air passage is not blocked

(2) Power supply environment Power supply voltage is 188 V or above.

(3) Inverter failure Refer to IX [4] -7-.(page 293)

(4) Current sensor (ACCT) failure Refer to IX [4] -7- (4).

(5) Compressor failure Check that the compressor has not overheated during operation. -> Check the refrigerant circuit (oil return section). Refer to IX [4] -7- (2) [2].(page 295)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Model Imax(Arms) · P72 model 35 · Model TOL

Page 218 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 218 · click to enlarge
Page 218

1. Error Code

4240 (YHMU-A)

Overload protection

2. Error definition and error detection method If the output current of "(Iac) >Imax (Arms)" or "THHS > 95°C [203°F] " is continuously detected for 10 minutes or more during inverter operation.

P96 , P120 model 27

3. Cause, check method and remedy

Cause Check method and remedy

(1) Air passage blockage Check that the heat sink cooling air passage is not blocked

(2) Power supply environment Power supply voltage is 414 V or above.

(3) Inverter failure Refer to IX [4] -7-.(page 301)

(4) Compressor failure Check that the compressor has not overheated during operation. -> Check the refrigerant circuit (oil return section). Refer to IX [4] -7- (2) [2].(page 303)

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Model Imax(Arms) · P72 model 19

Page 219 of the Mitsubishi Electronics P96 user manual — In the case of 4255
Page 219 · click to enlarge
Page 219

1. Error Code

4250 4255 (THMU-A)

IPM error (Detail code 101)

2. Error definition and error detection method In the case of 4250 P72 model Overcurrent is detected by the overcurrent detection resistor (RSH) on the INVboard. P96 and P120 models IPM error signal is detected. In the case of 4255 IPM error signal is detected.
3. Cause, check method and remedy In the case of 4250 P72 model

Cause Check method and remedy

(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 295)

P96 and P120 models

Cause Check method and remedy

(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 295)

(2) Same as 4230 error Same as 4230 error

In the case of 4255

Cause Check method and remedy

(1) Fan motor abnormality Refer to IX [4] -7- (2) [5].(page 296)

(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 296)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 220 of the Mitsubishi Electronics P96 user manual — In the case of 4255
Page 220 · click to enlarge
Page 220

1. Error Code

4250 4255 (YHMU-A)

IPM error (Detail code 101)

2. Error definition and error detection method In the case of 4250 Overcurrent is detected by the overcurrent detection resistor (RSH) on the INV board. In the case of 4255 IPM error signal is detected.

3. Cause, check method and remedy In the case of 4250

Cause Check method and remedy

(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 303)

Check the IGBT module resistance value of the INV board, if no problems are found. (Refer to the Trouble shooting for IGBT module)

In the case of 4255

Cause Check method and remedy

(1) Fan motor abnormality Refer to IX [4] -7- (2) [5].(page 304)

(2) Fan board failure Refer to IX [4] -7- (2) [6].(page 304)

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 221 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 221 · click to enlarge
Page 221

1. Error Code

4250 (THMU-A)

ACCT overcurrent (H/W detection) (Detail code 102) DCCT overcurrent (H/W detection) (Detail code 103) Instantaneous overcurrent (Detail code 106) Overcurrent (Detail code 107)

2. Error definition and error detection method P72 model Overcurrent 88 Apeak or 42 Arms and above is detected by the current sensor. P96 and P120 models Overcurrent 128 Apeak or 60 Arms and above is detected by the current sensor.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4].(page 295)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 222 of the Mitsubishi Electronics P96 user manual — In the case of 4255
Page 222 · click to enlarge
Page 222

1. Error Code

4250 (YHMU-A)

Instantaneous overcurrent (Detail code 106) Overcurrent (Detail code 107)

2. Error definition and error detection method P72 model Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor. P96 andP120 models Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inverter output related Refer to IX [4] -7- (2) [1] - [4]. (page 303)

Check the IGBT module resistance value of the INV board, if no problems are found. (Refer to the Trouble shooting for IGBT module)

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

1. Error Code

4250 4255

Short-circuited IPM/Ground fault (Detail code 104)

2. Error definition and error detection method When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.

3. Cause, check method and remedy In the case of 4250

Cause Check method and remedy

(1) Grounding fault compressor Refer to IX [4] -7- (2) [2].

(2) Inverter output related Refer to IX [4] -7- (2) [1] - [4].

In the case of 4255

Cause Check method and remedy

(1) Grounding fault of fan motor Refer to IX [4] -7- (2) [5].

(2) Fan board failure Refer to IX [4] -7- (2) [6].

Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.

Page 223 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 223 · click to enlarge
Page 223

1. Error Code

4250 4255

Overcurrent error due to short-circuited motor (Detail code 105)

2. Error definition and error detection method When a short is detected on the load side just before starting the inverter operation.

3. Cause, Check method and remedy In the case of 4250

Cause Check method and remedy

(1) Short - circuited compressor Refer to IX [4] -7- (2) [2].

(2) Output wiring Check for a short circuit.

In the case of 4255

Cause Check method and remedy

(1) Short - circuited fan motor Refer to IX [4] -7- (2) [5].

(2) Output wiring Check for a short circuit.

Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.

1. Error Code

4260 (THMU-A)

Heatsink overheat protection at startup

2. Error definition and error detection method The heatsink temperature (THHS) remains at or above TOH for 10 minutes or more at inverter startup.

P72 model 100°C [212°F]

P96, P120 models 90°C [194°F]

3. Cause, check method and remedy Same as 4230 error

Model TOH

Page 224 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 224 · click to enlarge
Page 224

1. Error Code

4260 (YHMU-A)

Heatsink overheat protection at startup

2. Error definition and error detection method The heatsink temperature (THHS) remains at or above 100°C [212°F] for 10 minutes or more at inverter startup.
3. Cause, check method and remedy Same as 4230 error
Page 225 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 225 · click to enlarge
Page 225

1. Error Code

Return air temperature sensor (TH21) fault (Indoor unit) Return air temperature sensor (TH4) fault (OA processing unit)

Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit)

Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit)

Intake air temperature sensor (TH1) fault (OA processing unit) Intake air temperature sensor (TH24) fault (All-fresh (100% outdoor air) type indoor unit)

2. Error definition and error detection method Œ If a short or an open is detected during thermostat ON, the outdoor unit turns to anti-restart mode for 3 minutes. When the

error is not restored after 3 minutes (if restored, the outdoor unit runs normally), the outdoor unit makes an error stop. Short: detectable at 90°C [194°F] or higher Open: detectable at -40°C [-40°F] or lower ŒSensor error at gas-side cannot be detected under the following conditions.

During heating operation During cooling operation for 3 minutes after the compressor turns on.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Thermistor failure Check the thermistor resistor. 0°C [32°F]: 15 kohm 10°C [50°F]: 9.7 kohm 20°C [68°F] : 6.4 kohm 30°C [86°F] : 4.3 kohm 40°C [104°F] : 3.1 kohm

(2) Connector contact failure

(3) Disconnected wire or partial disconnected thermistor wire

(4) Unattached thermistor or contact failure

(5) Indoor board (detection circuit) failure Check the connector contact. When no fault is found, the indoor board is a failure.

Page 226 of the Mitsubishi Electronics P96 user manual — TH3 TH4 TH5 TH6 TH7
Page 226 · click to enlarge
Page 226

1. Error Code

Heat exchanger outlet temperature sensor (TH3) fault (Outdoor unit)

Discharge temperature sensor (TH4) fault (Outdoor unit)

Accumulator inlet temperature sensor (TH5) fault (Outdoor unit)

Heat exchanger inlet temperature sensor (TH6) fault (Outdoor unit)

Outside temperature sensor (TH7) fault (Outdoor unit)

2. Error definition and error detection method Œ When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection),

the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. ŒWhen a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit

stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within the normal range. ŒWhen a short or an open is detected again (the third detection) after the previous restart of the outdoor unit, the outdoor unit

makes an error stop. ŒWhen a short or an open of the thermistor is detected just before the restart of the outdoor unit, the outdoor unit makes an

error stop, and the error code "5102", "5103", 5104", "5105", "5106"or "5107" will appear. ŒDuring 3-minute antirestart mode, preliminary errors will be displayed on the LED display. ŒA short or an open described above is not detected for 10 minutes after the compressor start, during defrost mode, or for 3

minutes after defrost mode.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Thermistor failure Check thermistor resistance.

(2) Pinched lead wire Check for pinched lead wire.

(3) Torn wire coating Check for wire coating.

(4) A pin on the male connector is missing or contact failure

Check connector.

(5) Disconnected wire Check for wire.

(6) Thermistor input circuit failure on the control board

Check the intake temperature of the sensor with the LED monitor. When the temperature is far different from the actual temper- ature, replace the control board.

TH3 TH4 TH5 TH6 TH7

110 C [230 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

240 C [464 F ] and above (0.57 k )

0 C [ 32 F ] and below (698 k )

70 C [158 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

70 C [158 F ] and above (1.14 k )

-40 C [ -40 F ] and below (130 k )

110 C [230 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

· Short detection · Open detection

Page 227 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 227 · click to enlarge
Page 227

1. Error Code

5110 (THMU-A)

Heatsink temperature sensor (THHS) fault (Detail code 01)

2. Error definition and error detection method When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy P72 model

Cause Check method and remedy

(1) INV board failure If the problem recurs when the unit is put into operation, replace the INV board.

P96 and P120 models

Cause Check method and remedy

(1) THHS sensor failure Check the THHS sensor reading on the LED monitor. Replace the sensor if it reads below - 30°C[ -22°F] or above 150°C[302°F].

(2) Contact failure Check the connector connection (CNTH) on the INV board.

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

1. Error Code

5110 (YHMU-A)

Heatsink temperature sensor (THHS) fault (Detail code 01)

2. Error definition and error detection method When a short or an open of THHS is detected just before or during the inverter operation.

3. Cause, check method and remedy

Cause Check method and remedy

(1) INV board failure If the problem recurs when the unit is put into operation, replace the INV board.

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 228 of the Mitsubishi Electronics P96 user manual — TH11 TH12 TH15 TH16
Page 228 · click to enlarge
Page 228

1. Error Code

Liquid inlet temperature sensor (TH11) fault (BC controller)

Bypass outlet temperature sensor (TH12) fault (BC controller)

LEV3 outlet temperature sensor (TH15) fault (BC controller)

LEV3 inlet temperature sensor (TH16) fault (BC controller)

2. Error definition and error detection method Œ If a shorted (high temperature intake) or open (low temperature intake) thermistor (TH11, TH12, TH15, or TH16) is detected

during operation, the unit makes an error stop, and an error code "5111," "5112," "5115," or "5116" appears on the display. ŒDetection of a short- or open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the

operation mode is changed.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Thermistor failure Check thermistor resistance.

(2) Pinched lead wire Check for pinched lead wire.

(3) Torn wire coating Check for wire coating.

(4) A pin on the male connector is missing or contact failure

Check connector.

(5) Disconnected wire Check for wire.

(6) Thermistor input circuit failure on the control board

Check the intake temperature of the sensor with the LED monitor. When the temperature is far different from the actual temper- ature, replace the control board.

TH11 TH12 TH15 TH16

110 C [230 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

110 C [230 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

70 C [158 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

110 C [230 F ] and above (0.4 k )

-40 C [ -40 F ] and below (130 k )

· Short detection · Open detection

Page 229 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 229 · click to enlarge
Page 229

1. Error Code

High-pressure sensor fault (63HS1)

2. Error definition and error detection method Œ If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to anti-

restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more. ŒIf the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and

the error code "5201" will appear. ŒDuring 3-minute antirestart mode, preliminary errors will be displayed on the LED display. ŒA error is not detected for 3 minutes after the compressor start, during defrost operation, or 3 minutes after defrost operation.

3. Cause, check method and remedy

Cause Check method and remedy

(1) High pressure sensor failure Refer to the page on the troubleshooting of the high pressure sensor. (IX [4] -1- (page 273))

(2) Pressure drop due to refrigerant leak

(3) Torn wire coating

(4) A pin on the male connector is missing or contact failure

(6) High pressure sensor input circuit failure on the control board

(5) Disconnected wire

Page 230 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 230 · click to enlarge
Page 230

1. Error Code

High-pressure sensor fault (Outdoor unit HPS/BC controller PS1)

Intermediate pressure sensor fault (BC controller PS3)

2. Error definition and error detection method When a pressure sensor reading of 4.06 MPa [589 psi] or above is detected, error codes "5201" and "5203" will appear. The unit will continue its operation by using other sensors as a backup.

3. Cause, check method and remedy

Cause Check method and remedy

(1) High pressure sensor failure Refer to the page on the troubleshooting of the high pressure sensor. (IX [4] -1-(page 273))

(2) Pressure drop due to refrigerant leak

(3) Torn wire coating

(4) A pin on the male connector is missing or contact failure

(6) High pressure sensor input circuit failure on the control board

(5) Disconnected wire

Page 231 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 231 · click to enlarge
Page 231

1. Error Code

5301 (THMU-A)

ACCT sensor fault (Detail code 115)

2. Error definition and error detection method When the formula "output current < 2 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy P72 model

Cause Check method and remedy

(1) Inverter open output phase Check the output wiring connections.

(2) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

(3) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 295)

P96 and P120 models

Cause Check method and remedy

(1) Inverter open output phase Check the output wiring connections.

(2) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

(3) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 295)

(4) Contact failure Check the connection of the connector (CNCT2) on the INV board- INV board.

(5) ACCT sensor failure Refer to IX [4] -7- (4).

Refer to section -7-"Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

1. Error Code

5301 (YHMU-A)

ACCT sensor fault (Detail code 115)

2. Error definition and error detection method When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inverter open output phase Check the output wiring connections.

(2) Compressor failure Refer to IX [4] -7- (2) [2].(page 303)

(3) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 303)

Refer to section -7-"Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 232 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 232 · click to enlarge
Page 232

1. Error Code

5301 (THMU-A) (P96 and P120 models only)

DCCT sensor fault (Detail code116)

2. Error definition and error detection method When the bus current less than 18 Apeak is detected at startup (6Hz)

3. Cause, check method and remedy

Cause Check method and remedy

(1) Contact failure Check the contact of the connector (CNCT) on the INV board, and the contact the connector on DCCT side.

(2) Misorientation Check the installation direction of DCCT.

(3) DCCT sensor failure Replace the DCCT sensor.

(4) INV board failure Replace the INV board.

Refer to section -7-"Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 233 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 233 · click to enlarge
Page 233

1. Error Code

ACCT sensor circuit fault (Detail code 117)

2. Error definition and error detection method When an error value is detected with the ACCT detection circuit just before the inverter starts

3. Cause, check method and remedy

Cause Check method and remedy

(1) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].

(2) Compressor failure Refer to IX [4] -7- (2) [2].

Refer to section -7-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.

Page 234 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 234 · click to enlarge
Page 234

1. Error Code

5301 (THMU-A) (P96 and P120 model only)

DCCT sensor circuit fault (Detail code118)

2. Error definition and error detection method When an error value is detected with the DCCT detection circuit just before the inverter starts

3. Cause, check method and remedy

Cause Check method and remedy

(1) Contact failure Check for good contact of the INV board connector CNCT and the connec- tor on the DCCT side.

(2) INV board failure Refer to IX [4] -7- (2) [1], [3], [4].(page 295)

(3) DCCT sensor failure Replace the DCCT sensor.

(4) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

(5) Inverter failure Refer to IX [4] -7-.(page 293)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 235 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 235 · click to enlarge
Page 235

1. Error Code

5301 (THMU-A)

Open-circuited IPM/Loose ACCT connector (Detail code 119)

2. Error definition and error detection method Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.
3. Cause, check method and remedy P72 model

Cause Check method and remedy

(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.

(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)

(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

P96 and P120 models

Cause Check method and remedy

(1) ACCT sensor disconnection Check the connection of the connector (CNCT2) on the INV board. Check for proper mounting of ACCT.

(2) ACCT sensor failure Refer to IX [4] -7- (4).

(3) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)

(4) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 236 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 236 · click to enlarge
Page 236

1. Error Code

5301 (YHMU-A)

Open-circuited IPM/Loose ACCT connector (Detail code 119)

2. Error definition and error detection method Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.

(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 304)

(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 303)

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

1. Error Code

5301 (THMU-A)

Faulty ACCT wiring (Detail code 120)

2. Error definition and error detection method Presence of target current cannot be detected during the self-diagnostic operation immediately before startup. (Detection of improperly mounted ACCT sensor)
3. Cause, check method and remedy P72 model

Cause Check method and remedy

(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.

(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)

(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

(4) INV board failure Replace the INV board.

P96 and P120 models

Cause Check method and remedy

(1) Wrongly mounted ACCT sensor Check for proper mounting of ACCT. Refer to IX [4] -7- (4).

(2) ACCT sensor failure Refer to IX [4] -7- (4).

(3) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 296)

(4) Compressor failure Refer to IX [4] -7- (2) [2].(page 295)

Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 293)

Page 237 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 237 · click to enlarge
Page 237

1. Error Code

5301 (YHMU-A)

Faulty ACCT wiring (Detail code 120)

2. Error definition and error detection method Presence of target current cannot be detected during the self-diagnostic operation immediately before startup.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Inverter output wiring problem Check output wiring connections. Confirm that the U- and W-phase output cables are put through CT12 and CT22 on the INV board respectively.

(2) Inverter failure Refer to IX [4] -7- (2) [3], [4].(page 304)

(3) Compressor failure Refer to IX [4] -7- (2) [2].(page 303)

Refer to section -7- "Inverter (YHMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 301)

Page 238 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 238 · click to enlarge
Page 238

1. Error Code

Temperature sensor fault

2. Error definition and error detection method Œ A short-circuit or an open-circuit of the humidity sensor is detected during operation.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Connector contact failure (CN30) (Loose con- nector)

1. Check the connector for proper contact. Reconnect the connector, and operate the unit to check for proper operation.

(2) Broken or partially broken humidity sensor wire 2) Check for broken humidity sensor wire.

(3) Humidity sensor fault 3) Check the output voltage across No. 1 and No. 3 pins of connector CN30 with the connector being connected to the indoor unit control board.

30% : 1.25V 40% : 1.52V 50% : 1.88V 60% : 2.19V 70% : 2.48V 80% : 2.79V

(4) Indoor unit control board (detection circuit) fault 4) If the above items check out okay, replace the indoor unit control board.

Page 239 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy (1) Remote controller failure
Page 239 · click to enlarge
Page 239

1. Error Code

Loose float switch connector

2. Error definition and error detection method Detection of the disconnected float switch (open-phase condition) during operation

3. Cause, check method and remedy (1) CN4F disconnection or contact failure

Check for disconnection of the connector (CN4F) on the indoor unit control board.

1. Error Code

Remote controller board fault (nonvolatile memory error)

2. Error definition and error detection method This error is detected when the data cannot be read out from the built-in nonvolatile memory on the remote controller.

3. Cause, check method and remedy (1) Remote controller failure

Replace the remote controller.

1. Error Code

Remote controller board fault (clock IC error)

2. Error definition and error detection method This error is detected when the built-in clock on the remote controller is not properly functioning.

3. Cause, check method and remedy (1) Remote controller failure

Replace the remote controller.

Page 240 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 240 · click to enlarge
Page 240

1. Error Code

Address overlaps

2. Error definition and error detection method An error in which signals from more than one indoor units with the same address are received

The address and attribute that appear on the remote controller indicate the controller that detected the error.

3. Cause, check method and remedy

Cause Check method and remedy

Two or more of the following have the same address: Outdoor units, indoor units, LOSSNAY units, control- lers such as M-NET remote controllers. 6600 "01" appears on the remote controller Unit #01 detected the error. Two or more units in the system have 01 as their ad- dress.

Find the unit that has the same address as that of the error source. Once the unit is found, correct the address. Then, turn off the outdoor units, indoor units, and LOSS- NAY units, keep them all turned off for at least five minutes, and turn them back on.

1. Error Code

Polarity setting error

2. Error definition and error detection method The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.

3. Cause, check method and remedy

Cause Check method and remedy

(1) No voltage is applied to the M-NET transmission line that G(B)-50A is connected to.

Check if power is supplied to the M-NET transmission line of the G(B)-50A, and correct any problem found.

(2) M-NET transmission line to which G(B)-50A is con- nected is short-circuited.

Page 241 of the Mitsubishi Electronics P96 user manual — NO
Page 241 · click to enlarge
Page 241

1. Error Code

Transmission processor hardware error

2. Error definition and error detection method Although "0" was surely transmitted by the transmission processor, "1" is displayed on the transmission line.

The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.

3. Cause 1) When the wiring work of or the polarity of either the indoor or outdoor transmission line is performed or is changed while the power is on, the transmitted data will collide, the wave shape will be changed, and an error will be detected. 2) Grounding fault of the transmission line 3) When grouping the indoor units that are connected to different outdoor units, the male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector (CN40). 4) When the power supply unit for transmission lines is used in the system connected with MELANS, the male power supply connector is connected to the female power supply switch connector (CN40) on the outdoor unit. 5) Controller failure of the source of the error 6) When the transmission data is changed due to the noise on the transmission line 7) Voltage is not applied on the transmission line for centralized control (in case of grouped indoor units connected to different outdoor units or in case of the system connected with MELANS)

4. Check method and remedy

Is the transmission line work performed while the power is on?

YES

Turn off the power source of outdoor/indoor units, and turn them on again.

NO

Check the power source of the indoor unit.

188 / 253V?

NO

Faulty power source work

YES

Check the transmission line work is performed and the shielded wire is treated properly.

Grounding fault or does the shielded wire contact with the transmission line?

YES

Improper transmission line work

NO

Single-outdoor-unit system Multiple-outdoor-unit system

System with the power supply unit for transmission lines

Confirm that the power supply connector on the outdoor unit is not plugged into CN40.

Confirm that the power supply connector on the outdoor unit is not plugged into CN40.

Is the male power supply connector connected to the female power supply switch connector (CN40) on only one of the outdoor unit?

YES

NO

Is the male power supply connector connected to the female power supply switch connector (CN40) ?

NO

YES

Tightly reconnect the male power supply connector to the female power supply switch connector (CN40).

Disconnect the male power supply on CN40 and connect it to CN41

Investigation into the transmission line noise

*For the investigation method, follow

YES

Investigation into the cause of the noise

NO

Controller failure of the source of the error

Correct the error.

System ? · Noise exist?

Page 242 of the Mitsubishi Electronics P96 user manual — 3. Cause, check method and remedy
Page 242 · click to enlarge
Page 242

1. Error Code

Transmission line bus busy error

2. Error definition and error detection method Œ Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busy Œ Generated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise

The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.

3. Cause, check method and remedy

Cause Check method and remedy

(1) The transmission processor cannot be transmit- ted as the short-wavelength voltage like noise ex- ists consecutively on the transmission line.

No noise indicates that the error source controller is a fail- ure. If noise exists, investigate the noise.

-> No noise indicates that the error source controller is a

failure. -> If noise exists, investigate the noise.

(2) Error source controller failure

1. Error Code

Communication error between device and transmission processors

2. Error definition and error detection method Communication error between the main microcomputer on the indoor unit board and the microcomputer for transmission

The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.

3. Cause, check method and remedy

Cause Check method and remedy

(1) Data is not properly transmitted due to accidental erroneous operation of the controller of the error source.

Turn off the power source of the outdoor and the indoor units.(When the power source is turned off separately, the microcomputer will not be reset, and the error will not be corrected.)

(2) Error source controller failure

-> If the same error occurs, the error source controller is

a failure.

Page 243 of the Mitsubishi Electronics P96 user manual — LOSSNAY (LC)
Page 243 · click to enlarge
Page 243

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (1) System with one outdoor unit

method Cause Check method and remedy

M-NET remote controller (RC) MA re- mote con- troller (MA)

No ac- knowl- edgement (ACK) at IC trans- mission to OC

(1) Contact failure of transmission line of OC or IC Turn off the power source of the outdoor unit, and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (4).

(2) Decrease of transmission line voltage/signal by ex- ceeding acceptable range of transmission wiring. Farthest:200 m [656ft] or less Remote controller wiring: 10m [32ft] or less

(3) Erroneous sizing of transmission line (Not within the range below). Wire diameter: 1.25mm2 [AWG16] or more

(4) Indoor unit control board failure

M-NET remote controller (RC) MA re- mote con- troller (MA)

No ac- knowl- edgement (ACK) at IC trans- mission to BC

(1) When BC controller address is changed or modified during operation.

Turn off the outdoor/in- door units for 5 or more minutes, and turn them on again. If the error is accidental, they will run normally. If not, check the causes (1) - (4).

(2) Faulty or disconnected transmission wiring of BC controller

(3) Disconnected connector of BC controller (CN02)

(4) Faulty control board of BC controller

M-NET remote controller (RC) MA re- mote con- troller (MA)

No ac- knowl- edgement (ACK) at RC trans- mission to IC

(1) When IC unit address is changed or modified during operation.

Turn off the outdoor/in- door units for 5 or more minutes, and turn them on again. If the error is accidental, they will run normally. If not, check the causes (1) - (5).

(2) Faulty or disconnected IC transmission wiring

(3) Disconnected IC connector (CN2M)

(4) Indoor unit controller failure

(5) M-NET remote controller failure

LOSSNAY (LC)

M-NET remote controller (RC) MA re- mote con- troller (MA)

No ac- knowl- edgement (ACK) at IC trans- mission to LC

(1) The power source of LOSSNAY has been shut off. Turn off the power source of LOSSNAY and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (5).

(2) When the address of LOSSNAY is changed in the middle of the operation

(3) Faulty or disconnected transmission wiring of LOSSNAY

(4) Disconnected connector (CN1) on LOSSNAY

(5) Controller failure of LOSSNAY

M-NET remote control- ler (RC)

M-NET remote controller (RC) MA re- mote con- troller (MA)

No ac- knowl- edgement (ACK) at IC trans- mission to RC

(1) Faulty transmission wiring at IC unit side. Turn off the power source of the outdoor unit for 5 minutes or more, and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (4).

(2) Faulty wiring of the transmission line for M-NET re- mote controller

(3) When the address of M-NET remote controller is changed in the middle of the operation

(4) M-NET remote controller failure

Show 7 more labels / short text on this page
Error source address · Error dis- · Detection · play · Outdoor unit (OC) · BC con- troller (BC) · Indoor unit (IC)
Page 244 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 244 · click to enlarge
Page 244

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (2) Grouping of units in a system with multiple outdoor units

method Cause Check method and remedy

M-NET re- mote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmission to OC

Same cause as that for system with one outdoor unit

Same remedy as that for sys- tem with one outdoor unit

M-NET re- mote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmission to BC

Same cause as that for system with one outdoor unit

Same remedy as that for sys- tem with one outdoor unit

M-NET re- mote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at RC transmission to IC

(1) Same causes as (1) - (5) for sys- tem with one outdoor unit

1. Turn off the power sources of the outdoor and indoor units for 5 or more minutes, and turn them on again. If the error is accidental, the will run normally.If not, check the cause 2).

(2) Disconnection or short circuit of the transmission line for the out- door unit on the terminal block for centralized control line connection (TB7)

2. Check the causes of (1) - (5). If the cause is found, correct it. If no cause is found, check 3).

(3) When multiple outdoor units are connected and the power source of one of the outdoor units has been shut off.

3. Check the LED displays for troubleshooting on other remote controllers whether an error occurs.

(4) The male power supply connector of the outdoor unit is not connect- ed to the female power supply switch connector (CN40).

If an error is found, -> If an error is found, check the check code definition, and correct the error. If no error is found, -> Indoor unit board failure (5) The male power supply connec- tors on 2 or more outdoor units are connected to the female pow- er supply switch connector (CN40) for centralized control.

If an error occurs, after the unit runs normally once, the following causes may be considered.

ŒTotal capacity error (7100) ŒCapacity code error (7101) ŒError in the number of con-

nected units (7102) ŒAddress setting error (7105)

Show 5 more labels / short text on this page
Error source address · Error display Detection · Outdoor unit (OC) · BC con- troller (BC) · Indoor unit (IC)
Page 245 of the Mitsubishi Electronics P96 user manual — LOSSNAY (LC)
Page 245 · click to enlarge
Page 245

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (2) Grouping of units in a system with multiple outdoor units

method Cause Check method and remedy

LOSSNAY (LC)

M-NET re- mote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmission to LC

(1) Factors (1) through (5) in the "Factors in system with one outdoor unit" (When perform- ing an interlocked operation of the LOSSNAY unit and the indoor units that are connect- ed to different outdoor units.)

1. Turn off the power source of LOSSNAY for 5 or more minutes, and turn it on again. If the error is accidental, it will run normally.If not, check the cause 2).

(2) Disconnection or short circuit of the transmission line for the outdoor unit on the termi- nal block for centralized con- trol line connection (TB7)

2. Check the causes of (1) - (5). If the cause is found, correct it. If no cause is found, check 3).

(3) When multiple outdoor units are connected and the power source of one of the outdoor units has been shut off.

3. Same cause as that for indoor unit described in 3)

(4) The male power supply con- nector of the outdoor unit is not connected to the female power supply switch connec- tor (CN40).

(5) The male power supply con- nectors on 2 or more outdoor units are connected to the fe- male power supply switch connector (CN40) for central- ized control.

If an error occurs, after the unit runs normally once, the following causes may be con- sidered.

ŒTotal capacity error

(7100) ŒCapacity code error

(7101) ŒError in the number of

connected units (7102) ŒAddress setting error

Error source address · Error display Detection · (7105)

Page 246 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 246 · click to enlarge
Page 246

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (2) Grouping of units in a system with multiple outdoor units

method Cause Check method and remedy

M-NET re- mote con- troller (RC)

M-NET re- mote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmission to RC

(1) Same causes as (1) - (4) for system with one outdoor unit

1. Turn off the power source of LOSSNAY for 5 or more minutes, and turn it on again. If the error is accidental, it will run normally.If not, check the cause 2).

(2) Disconnection or short circuit of the transmission line for the outdoor unit on the termi- nal block for centralized con- trol line connection (TB7)

2. Check the causes of (1) - (5). If the cause is found, correct it. If no cause is found, check 3).

(3) When multiple outdoor units are connected and the power source of one of the outdoor units has been shut off.

3. Same cause as that for indoor unit described in 3)

(4) The male power supply con- nector of the outdoor unit is not connected to the female power supply switch connec- tor (CN40).

(5) The male power supply con- nectors on 2 or more outdoor units are connected to the fe- male power supply switch connector (CN40) for central- ized control.

If the problem recurs after normal operation is restored, the problem is caused by one of the following factors:

ŒTotal capacity error

(7100) ŒCapacity code setting

error (7101) ŒError in the number of

connected units (7102) ŒAddress setting error

Error source address · Error display Detection · (7105)

Page 247 of the Mitsubishi Electronics P96 user manual — 3. System configuration (3) System connected to the system controllers (MELANS)
Page 247 · click to enlarge
Page 247

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (3) System connected to the system controllers (MELANS)

method Cause Check method and remedy

M-NET remote controller (RC) System control- ler (SC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmis- sion to OC

Same cause as that for system with one outdoor unit

Same remedy as that for system with one outdoor unit

M-NET remote controller (RC) system control- ler (SC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmis- sion to BC

Same cause as that for system with one outdoor unit

Same remedy as that for system with one outdoor unit

Show 4 more labels / short text on this page
Error source address · Error display Detection · Out- door unit (OC) · BC con- troller (BC)
Page 248 of the Mitsubishi Electronics P96 user manual — 3. System configuration (3) System connected to the system controllers (MELANS)
Page 248 · click to enlarge
Page 248

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (3) System connected to the system controllers (MELANS)

method Cause Check method and remedy

M-NET remote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at RC transmis- sion to IC

Same as grouping of units in a system with multiple outdoor units

Same remedy as that for grouping of units in a sys- tem with multiple outdoor units

No acknowl- edgement (ACK) at SC transmis- sion to IC

1. Error occurrence on some IC Same remedy as that for system with one outdoor unit (1) Same cause as that for system with one outdoor unit
2. Error occurrence on all IC in the system with one outdoor unit
1. Check the LED display for troubleshooting on the outdoor unit.

(1) Total capacity error (7100) ŒIf an error is found,

check the check code definition, and correct the error. ŒIf no error is found,

(2) Capacity code error (7101)

(3) Error in the number of connected units (7102)

check 2).

(4) Address setting error (7105)

(5) Disconnection or short circuit of the trans- mission line for the outdoor unit on the ter- minal block for centralized control line connection (TB7)

2. Check (5) - (7) on the left.

(6) Turn off the power source of the outdoor unit

(7) Malfunction of electrical system for the outdoor unit

3. Error occurrence on all IC Check voltage of the transmission line for centralized control.

(1) Same causes as (1) - (7) described in 2.

(2) The male power supply connectors on 2 or more outdoor units are connected to the female power supply switch connector (CN40) for the transmission line for cen- tralized control.

Œ 20V or moreCheck (1)

and (2) on the left. ŒLess than 20V: Check

(3) on the left.

(3) Disconnection or shutdown of the power source of the power supply unit for trans- mission line

(4) System controller (MELANS) malfunction

Show 4 more labels / short text on this page
Error source address · Error display Detection · Indoor unit (IC) · System control- ler (SC)
Page 249 of the Mitsubishi Electronics P96 user manual — 3. System configuration (3) System connected to the system controllers (MELANS)
Page 249 · click to enlarge
Page 249

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (3) System connected to the system controllers (MELANS)

method Cause Check method and remedy

M-NET re- mote con- troller (RC)

M-NET re- mote controller (RC) System con- troller (SC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmission to RC

Same as grouping of units in a sys- tem with multiple outdoor units

Same remedy as that for grouping of units in a system with multiple outdoor units

No acknowl- edgement (ACK) at MELANS transmission to RC

1. Error occurrence on some IC Same remedy as that for system with one outdoor unit (1) Same cause as that for system with one outdoor unit
2. Error occurrence on all IC in the system with one outdoor unit
1. Check the LED display for troubleshooting on the outdoor unit.

(1) An error is found by the outdoor unit. Total capacity error (7100) Capacity code error (7101) Error in the number of connected units (7102) Address setting error (7105)

Œ If an error is found, check

the check code definition, and correct the error. ŒIf no error is found, check

the cause 2).

(2) Disconnection or short circuit of the transmission line for the outdoor unit on the terminal block for cen- tralized control line connection (TB7)

2. Check (2) - (4) on the left.

(3) Turn off the power source of the outdoor unit

(4) Malfunction of electrical system for the outdoor unit

3. Error occurrence on all IC Check (1) - (4) on the left.

(1) Same causes as (1) - (4) described in 2.

(2) When the power supply unit for transmission lines is used and the male power supply connector is connected to the female power supply switch connector (CN40) for the transmission line for central- ized control

(3) Disconnection or shutdown of the power source of the power supply unit for transmission line

(4) System controller (MELANS) mal- function

Error source address · Error display Detection · System con- troller (SC)

Page 250 of the Mitsubishi Electronics P96 user manual — 3. System configuration (3) System connected to the system controllers (MELANS)
Page 250 · click to enlarge
Page 250

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (3) System connected to the system controllers (MELANS)

method Cause Check method and remedy

M-NET re- mote controller (RC) MA remote controller (MA)

No acknowl- edgement (ACK) at IC transmission to SC

1. Error display on some displays on M-NET remote controllers

Check (1) - (3) on the left.

(1) Faulty wiring of the transmission line for M-NET remote controller

(2) Disconnection or contact failure of the transmission connector for M- NET remote controller

(3) M-NET remote controller failure

2. Error occurrence on all IC in the system with one outdoor unit
1. Check the LED display for troubleshooting on the outdoor unit.

(1) An error is found by the outdoor unit. Total capacity error (7100) Capacity code error (7101) Error in the number of connected units (7102) Address setting error (7105)

Œ If an error is found, check

the check code definition, and correct the error. ŒIf no error is found, check

(2) Disconnection or short circuit of the transmission line for the outdoor unit on the terminal block for cen- tralized control line connection (TB7)

2. Check (2) - (4) on the left.

(3) Turn off the power source of the outdoor unit

(4) Malfunction of electrical system for the outdoor unit

3. Error display on all displays on MNET remote controllers

Check (1) - (4) on the left

(1) Same causes as (1) - (4) described in 2.

(2) When the power supply unit for transmission lines is used and the male power supply connector is connected to the female power sup- ply switch connector (CN40) for the transmission line for centralized control

(3) Disconnection or shutdown of the power source of the power supply unit for transmission line

(4) System controller (MELANS) mal- function

Show 4 more labels / short text on this page
Error source address · Error display Detection · System controller (SC) · the cause 2)
Page 251 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 251 · click to enlarge
Page 251

1. Error Code

No ACK error

2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is transmitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)

The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).

3. System configuration (4) Errors that are not limited to a particular system

method Cause Check method and remedy

Address which should not be existed

- - (1) Although the address of M- NET remote controller has been changed after the group is set using M-NET remote controller, the indoor unit is keeping the memory of the previous address. The same symptom will appear for the registration with SC.

Delete unnecessary informa- tion of non-existing address which some indoor units have. Use either of the following two methods for deletion.

(2) Although the address of LOSSNAY has been changed after the interlock registration of LOSSNAY is made using M- NET remote controller, the in- door unit is keeping the mem- ory of the previous address.

1. Address deletion by M-NET remote controller Delete unnecessary address information using the manual setting function of M-NET remote controller. Refer to this service handbook "IV [2] Group Settings and Interlock Settings via the ME Remote Controller 1. (3) Address deletion".
2. Deletion of connection information of the outdoor unit by the deleting switch

ŒTurn off the power source of

the outdoor unit, and wait for 5 minutes. ŒTurn on the dip switch (SW2-

2. on the outdoor unit control board. Œ Turn on the power source of

the outdoor unit, and wait for 5 minutes. ŒTurn off the power source of

the outdoor unit, and wait for 5 minutes. ŒTurn off the dip switch (SW2-

2. on the outdoor unit control board. Œ Turn on the power source of

the outdoor unit.

Show 5 more labels / short text on this page
Error source ad- · Error dis- · Detection · play · dress
Page 252 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 252 · click to enlarge
Page 252

1. Error Code

No response error

2. Error definition and error detection method Œ When no response command is returned although acknowledgement (ACK) is received after transmission, an error is detect-

ed. ŒWhen the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side.

The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.

3. Cause 1) The transmission line work is performed while the power is on, the transmitted data will collide, and the wave shape will be changed. 2) The transmission is sent and received repeatedly due to noise. 3) Decrease of transmission line voltage/signal by exceeding acceptable range of transmission wiring. Farthest:200m [656ft] or less Remote controller wiring:12m [39ft] or less 4) The transmission line voltage/signal is decreased due to erroneous sizing of transmission line. Wire diameter: 1.25mm2[AWG16] or more

4. Check method and remedy 1) When an error occurs during commissioning, turn off the power sources for the outdoor unit, indoor unit, BC controller, and LOSSNAY for 5 or more minutes, and then turn them on again. Œ When they return to normal operation, the cause of the error is the transmission line work performed with the power on. ŒIf an error occurs again, check the cause 2). 2) Check 3) and 4) above. ŒIf the cause is found, correct it. Œ If no cause is found, check 3). 3) Check transmission wave shape/ noise on trans-mission line by following "IX [3] Investigation of Transmission Wave Shape/ Noise" (page 270). Noise is the most possible cause of the error "6608".

Page 253 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 253 · click to enlarge
Page 253

1. Error Code

MA controller signal reception error (No signal reception)

2. Error definition and error detection method Œ Communication between the MA remote controller and the indoor unit is not done properly. Œ No proper data has been received for 3 minutes.

3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit. 2) All the remote controllers are set to SUB. 3) Failure to meet wiring regulations ŒWire length ŒWire size ŒNumber of remote controllers ŒNumber of indoor units 4) The remote controller is removed after the installation without turning the power source off. 5) Noise interference on the remote controller transmission lines 6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller 7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller

4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.

ŒIf LED1 is lit, the main power source of the indoor unit is turned on. ŒIf LED2 is lit, the MA remote controller line is being powered.

Page 254 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 254 · click to enlarge
Page 254

1. Error Code

MA remote controller signal transmission error (Synchronization error)

2. Error definition and error detection method Œ MA remote controller and the indoor unit is not done properly. Œ Failure to detect opening in the transmission path and unable to send signals
Indoor unit3 minutes Remote controller : 6 seconds

3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit 2) 2 or more remote controllers are set to MAIN 3) Overlapped indoor unit address 4) Noise interference on the remote controller lines 5) Failure to meet wiring regulations ŒWire length ŒWire size ŒNumber of remote controllers ŒNumber of indoor units 6) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller

4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.

ŒIf LED1 is lit, the main power source of the indoor unit is turned on. ŒIf LED2 is lit, the MA remote controller line is being powered.

Page 255 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 255 · click to enlarge
Page 255

1. Error Code

MA remote controller signal transmission error (Hardware error)

2. Error definition and error detection method Œ Communication between the MA remote controller and the indoor unit is not done properly. Œ An error occurs when the transmitted data and the received data differ for 30 times in a row.

3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit 2) 2 or more remote controllers are set to MAIN 3) Overlapped indoor unit address 4) Noise interference on the remote controller lines 5) Failure to meet wiring regulations ŒWire length ŒWire size ŒNumber of remote controllers ŒNumber of indoor units 6) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller

4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.

ŒIf LED1 is lit, the main power source of the indoor unit is turned on. ŒIf LED2 is lit, the MA remote controller line is being powered.

Page 256 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 256 · click to enlarge
Page 256

1. Error Code

MA controller signal reception error (Start bit detection error)

2. Error definition and error detection method Œ Communication between the MA remote controller and the indoor unit is not done properly. Œ No proper data has been received for 2 minutes.

3. Cause 1) Contact failure of the remote controller lines of MA remote controller or the indoor unit. 2) All the remote controllers are set to SUB. 3) Failure to meet wiring regulations ŒWire length ŒWire size ŒNumber of remote controllers ŒNumber of indoor units 4) The remote controller is removed after the installation without turning the power source off. 5) Noise interference on the remote controller transmission lines 6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller 7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller

4. Check method and remedy 1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers. 2) Confirm that the power is supplied to the main power source and the remote controller line. 3) Confirm that MA remote controller's capacity limit is not exceeded. 4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN. 5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations) [NO]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference 6) Check wave shape/noise on MA remote controller line by following "IX [3] Investigation of Transmission Wave Shape/ Noise".(page 270) 7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.

ŒIf LED1 is lit, the main power source of the indoor unit is turned on ŒIf LED2 is lit, the MA remote controller line is being powered.

Page 257 of the Mitsubishi Electronics P96 user manual — OFF ON OFF OFF
Page 257 · click to enlarge
Page 257

1. Error Code

Total capacity error

2. Error definition and error detection method The model total of indoor units in the system with one outdoor unit exceeds limitations.

3. Error source, cause, check method and remedy,

Error source Cause Check method and remedy

Outdoor unit (1) The model total of indoor units in the sys- tem with one outdoor unit exceeds the fol- lowing table.

1. Check the model total (capacity code total) of indoor units connected.
2. Check the model name (capacity code) of the connected indoor unit set by the switch (SW2 on indoor unit board).

When the model name set by the switch is differ- ent from that of the unit connected, turn off the power source of the outdoor and the indoor units, and change the setting of the model name (ca- pacity code).

(2) The model selection switches (SW5-1 - 5- 4) on the outdoor unit are set incorrectly. Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-1 - 5-4 on the outdoor unit control board).

SW5

1 2 3 4 Model

OFF ON OFF OFF

ON ON OFF OFF

OFF OFF ON OFF

(3) The outdoor unit and the auxiliary unit (OS) that is connected to the same system are not properly connected.

Confirm that the TB3 on the OC and OS are properly connected.

Show 12 more labels / short text on this page
Model Capacity total · P72 model · P96 model · P120 model · P144 model · P168 model · P192 model · P216 model · P240 model · 72 model · 96 model · 120 model
Page 258 of the Mitsubishi Electronics P96 user manual — SW5
Page 258 · click to enlarge
Page 258

1. Error Code

Capacity code setting error

2. Error definition and error detection method Connection of incompatible (wrong capacity code) indoor unit or outdoor unit

3. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit Indoor unit

(1) The model name (capacity code) set by the switch (SW2) is wrong.

1. Check the model name (capacity code) of the indoor unit which has the error source address set by the switch (SW2 on indoor unit board). When the model name set by the switch is different from that of the unit connected, turn off the power source of the outdoor and the indoor units, and change the setting of the capacity code.

*The capacity of the indoor unit can be confirmed by the self-diagnosis function (SW1 operation) of the outdoor unit.

Outdoor unit (2) The model selection switches (SW5-1 - 5-4) on the outdoor unit are set incor- rectly.

Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-1 - 5-4 on the outdoor unit control board).

1 2 3 4 Model

SW5

OFF ON OFF OFF

ON ON OFF OFF

OFF OFF ON OFF

72 model · 96 model · 120 model

Page 259 of the Mitsubishi Electronics P96 user manual — 3. Error source, cause, check method and remedy
Page 259 · click to enlarge
Page 259

1. Error Code

Wrong number of connected units

2. Error definition and error detection method The number of connected indoor units is "0" or exceeds the allowable value.

3. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit (1) Number of indoor units connected to the outdoor terminal block (TB3) for indoor/ outdoor transmis- sion lines exceeds limitations described below.

1. Check whether the number of units connected to the outdoor terminal block (TB3) for indoor/ outdoor transmission lines does not exceed the limitation. (See (1) and (2) on the left.)
2. Check (2) - (3) on the left.

Restriction on the number of units Number of units

3. Check whether the transmission line for the terminal block for centralized control (TB7) is not connected to the terminal block for the indoor/outdoor transmission line (TB3).

Total number of indoor units

1. 18 : P72 model
1. 24 : P96 model
1. 30 : P120 model
1. 36 : P144 model
1. 42 : P168 model
4. Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-7 on the outdoor unit control board).
1. 48 : P192 model
2. 50 : P216 model
2. 50 : P240 model

Number of BC controllers

1 (P72- P120 models only)

Number of Main BC controllers

Number of Sub BC controllers

Total number of LOSSNAY units (During auto address start-up only)

Total number of outdoor units

1. P72 - P120 models
2. P144 - P240 models

(2) Disconnected transmission line from the outdoor unit or BC controller

(3) Short-circuited transmission line When (2) and (3) apply, the following display will appear.

ŒM-NET remote controller

Nothing appears on the remote controller be- cause it is not powered. ŒMA remote controller

"HO" or "PLEASE WAIT" blinks.

(4) The model selection switch (SW5-7) on the out- door unit is set to OFF. (Normally set to ON)

(5) Outdoor unit address setting error The outdoor units in the same refrigerant circuit do not have sequential address numbers.

(6) In a system with the P700 models of units or larger, a BC controller other than the HA-type is used as the main BC controller.

0 or 1 · 0,1 or 2 · 0 or 1

Page 260 of the Mitsubishi Electronics P96 user manual — ON
Page 260 · click to enlarge
Page 260

1. Error Code

Address setting error

2. Error definition and error detection method Erroneous setting of OC unit address Erroneous setting of BC controller address

3. Cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit BC controller

Erroneous setting of OC unit address The address of outdoor unit is not being set to 51 - 100. The address of BC controller is not set to 51 - 100.

Check that the outdoor unit and BC controller addresses are set to 00 or a number between 51 and 100. If the outdoor unit address is out of the valid range, reset the address with the power to the outdoor unit turned off. If the BC controller address is out of the valid range, reset the address with the power to both the outdoor unit and BC controller turned off.

1. Error Code

Attribute setting error

2. Error definition and error detection method

Error source Cause Check method and remedy

- A remote controller for use with indoor units, such as the MA remote controller, is connected to the OA processing unit whose attribute is FU.

To operate the OA processing unit directly via a re- mote controller for use with indoor units, such as the MA remote controller, set the DIP SW 3-1 on the OA processing unit to ON.

SW3-1

Interlocked operation with the indoor unit

OFF

Direct operation via the MA remote controller

ON

Operation Method

Page 261 of the Mitsubishi Electronics P96 user manual — YES
Page 261 · click to enlarge
Page 261

1. Error Code

Port setting error

2. Error definition and error detection method The port with wrong number is connected to the indoor unit.The model total connected to the port is greater than the specification.

3. Cause, check method and remedy

Error source Cause Check method and remedy

BC controller (1) Model total of indoor units per each port or per each port merge is greater than the specification.

Before resetting the port number using the port number setting switch or the model using the model (capacity code) setting switch, turn off the power of the outdoor unit, the BC controller and the indoor unit.

Model total Total port number

2 branches merge 54

(2) 4 or more indoor units are connected to the same port.

(3) When two ports are used, the port with the smaller number is not connected to the indoor unit.

(4) For the address of the BC controller (Sub 1 or 2), 50 is not added to the smallest indoor unit address, which is connected to the BC controller (Sub1 or 2).

(5) In the system to which multiple BC controllers are connected, the indoor unit address connected to the BC controller is not set as shown below. (i) The indoor unit address which is connected to

the BC controller (main) (ii) The indoor unit address which is connected to

the BC controller (Sub1) (iii) he indoor unit address which is connected to

the BC controller (Sub2) Address setting

(i)

For the address of the BC controller (Sub), is 50 added to the smallest indoor unit address,

Is there a BC controller (Sub)?

YES

NO Change the BC controller (Sub) address.

which is connected to the

NO

YES

Are 4 or more indoor units connected to the same port?

YES

YES

Port No. setting error?

Change the port No.

NO

NO

Is the address of the indoor

Is the model total of indoor units connected to the same port

Adjust the piping connection to the port.

unit, which is connected to the the

YES

BC controller (Main) ,smaller than

NO

Change the indoor unit address or change the BC controller address

that of the indoor, which is

greater than the item (1)?

connected to the BC controller

NO

(Sub 1 or 2)?

YES

When two ports are used,

YES

is the port with the smallest number

Port No. setting error?

Change the port No.

connected to the indoor unit?

NO

NO

Is the address of the indoor

The wrong model (capacity code) is set.

YES Change the set indoor unit model (capacity code).

unit, which is connected to the the

BC controller (Main), smaller than

NO

that of the indoor, which is

NO

connected to the BC controller

(Sub 1 or 2)?

Adjust the piping connection to the port.

Change the port No.

YES

Single branching · BC controller (Sub)?

Page 262 of the Mitsubishi Electronics P96 user manual — 3. Error source, cause, check method and remedy
Page 262 · click to enlarge
Page 262

1. Error Code

Connection information signal transmission/reception error

2. Error definition and error detection method The given indoor unit is inoperable because it is not properly connected to the outdoor unit in the same system.

3. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit (1) Power to the transmission booster is cut off. 1) Confirm that the power to the transmission booster is not cut off by the booster being connected to the switch on the indoor unit. (The unit will not function properly unless the transmission booster is turned on.)

(2) Power resetting of the transmission booster and outdoor unit.

->Reset the power to the outdoor unit.

(3) Wiring failure between OC and OS 2) Confirm that the TB3 on the OC and OS are properly connected.

(4) Broken wire between OC and OS. 3) Check the model selection switch on the out- door unit (Dipswitch SW5-7 on the control board.). (5) The model selection switch (SW5-7) on the outdoor unit is set to OFF. (Normally set to ON)

1. Error Code

Remote controller sensor fault

2. Error definition and error detection method This error occurs when the temperature data is not sent although the remote controller sensor is specified.

3. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Indoor unit OA process- ing unit

The remote controller without the temperature sensor (the wireless remote controller or the M-NET compact remote controller (mounted type)) is used and the remote controller sen- sor for the indoor unit is specified. (SW1-1 is ON.)

Replace the remote controller with the one with built-in temperature sensor.

Page 263 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 263 · click to enlarge
Page 263

1. Error Code

Function setting error (incorrect resistor connection)

2. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit (1) Wiring fault (Detail code 15)

(2) Loose connectors, short-circuit, con- tact failure

1. Check the connector CNTYP5 on the control board for proper connection.

(3) Incompatible control board and INV board (replacement with a wrong cir- cuit board)

1. Check the connector CNTYP4 on the control board for proper connection.
2. Check the connector CNTYP5 on the control board for proper connection.

(4) DIP SW setting error on the control board

3. Check the settings of SW5-1 through SW5-4 on the control board.
1. Check the connector CNTYP2 on the control board for proper connection.
2. Check the connector CNTYP5 on the control board for proper connection.
3. Check the connector CNTYP4 on the control board for proper connection.
4. Check the settings of SW5-1 through SW5-4 on the control board.
1. Check the connector CNTYP on the INV board for proper connection.
2. Check the connector CNTYP5 on the control board for proper connection.
3. Check the connector CNTYP4 on the control board for proper connection.
4. Check the settings of SW5-1 through SW5-4 on the control board.
5. Check the wiring between the control board and INV board. (Refer to the section on Error code 0403.)

(Detail code 00, 01, 05)

1. Check the wiring between the control board and INV board. (Refer to the section on Error code 0403.)
2. Check the settings of SW5-1 through SW5-4 on the control board.
3. Check the connector CNTYP5 on the control board for proper connection.
4. Check the connector CNTYP4 on the control board for proper connection.

*If a set-model-name identification error occurs, check the detail code on the unit on which the error occurred. The detail code that appears on other units will be dif- ferent from the ones shown above.

Show 4 more labels / short text on this page
(Detail code 14) · (Detail code 12) · (Detail code 16) · (Detail code Miscellaneous)
Page 264 of the Mitsubishi Electronics P96 user manual — 1. Error Code
Page 264 · click to enlarge
Page 264

1. Error Code

Model setting error

2. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit (1) Wiring fault (Detail code 15)

(2) Loose connectors, short-circuit, con- tact failure

1. Check the connector CNTYP5 on the control board for proper connection.
1. Check the connector CNTYP4 on the control board for proper connection.
1. Check the connector CNTYP2 on the control board for proper connection.
2. Check the connector CNTYP5 on the control board for proper connection.
1. Check the connector CNTYP on the INV board for proper connection.
2. Check the connector CNTYP5 on the control board for proper connection.
3. Check the connector CNTYP4 on the control board for proper connection.
4. Check the wiring between the control board and INV board. (Refer to the section on Error code 0403.)

(Detail code 00, 01, 05)

1. Check the wiring between the control board and INV board. (Refer to the section on Error code 0403.)
2. Check the settings of SW5-1 through SW5-4 on the control board.
3. Check the connector CNTYP5 on the control board for proper connection.
4. Check the connector CNTYP4 on the control board for proper connection.

*If a set-model-name identification error occurs, check the detail code on the unit on which the error occurred. The detail code that appears on other units will be dif- ferent from the ones shown above.

Show 4 more labels / short text on this page
(Detail code 14) · (Detail code 12) · (Detail code 16) · (Detail code Miscellaneous)
Page 265 of the Mitsubishi Electronics P96 user manual — 3. Error source, cause, check method and remedy
Page 265 · click to enlarge
Page 265

1. Error Code

Incompatible unit combination

2. Error definition and error detection method The check code will appear when the indoor units with different refrigerant systems are connected.

3. Error source, cause, check method and remedy

Error source Cause Check method and remedy

Outdoor unit The connected indoor unit or BC controller is exclusively for use with R22 or R407C. An in- compatible indoor unit or BC controller is con- nected. The M-NET connection adapter is connected to the indoor unit system in a system in which the Slim Model (A control) of units are con- nected to the M-NET.

Check the model names of the connected in- door unit and the BC controller. Check whether the connecting adapter for M-NET is not connected to the indoor unit. (Connect the connecting adapter for M-NET to the outdoor unit.)

Page 266 of the Mitsubishi Electronics P96 user manual — -1Troubleshooting according to the remote controller malfunction or the external input error
Page 266 · click to enlarge
Page 266

-1Troubleshooting according to the remote controller malfunction or the external input error

In the case of MA remote controller

1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start running.(Power indicator does not appear on the screen.)

(1) Cause 1) The power is not supplied to the indoor unit. ŒThe main power of the indoor unit is not on. ŒThe connector on the indoor unit board has come off. ŒThe fuse on the indoor unit board has melted. ŒTransformer failure and disconnected wire of the indoor unit. 2) Incorrect wiring for the MA remote controller ŒDisconnected wire for the MA remote controller or disconnected line to the terminal block. ŒShort-circuited MA remote controller wiring ŒIncorrect wiring of the MA remote controller cables ŒIncorrect connection of the MA remote wiring to the terminal block for transmission line (TB5) on the indoor unit ŒWiring mixup between the MA remote controller cable and power supply cable ŒReversed connection of the wire for the MA remote controller and the M-NET transmission line on the indoor unit 3) The number of the MA remote controllers that are connected to an indoor unit exceeds the allowable range (2 units). 4) The length or the diameter of the wire for the MA remote controller are out of specification. 5) Short circuit of the wire for the remote display output of the outdoor unit or reversed polarity connection of the relay. 6) The indoor unit board failure 7) MA remote controller failure

(2) Check method and remedy 1) Measure voltages of the MA remote controller terminal (among 1 to 3). ŒIf the voltage is between DC 9 and 12V, the remote controller is a failure. ŒIf no voltage is applied, check the causes 1) and 3) and if the cause is found, correct it.

If no cause is found, refer to 2). 2) Remove the wire for the remote controller from the terminal block (TB13) on the MA remote controller for the indoor unit, and check voltage among 1 to 3. ŒIf the voltage is between DC 9 and 12 V, check the causes 2) and 4) and if the cause is found, correct it. ŒIf no voltage is applied, check the cause 1) and if the cause is found, correct it.

If no cause is found, check the wire for the remote display output (relay polarity). If no further cause is found, replace the indoor unit board.

Page 267 of the Mitsubishi Electronics P96 user manual — NO
Page 267 · click to enlarge
Page 267

In the case of MA remote controller

2. Phenomena When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off, and the display lights out immediately, and the unit stops.

(1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit. 2) Short circuit of the transmission line. 3) Incorrect wiring of the M-NETtransmission line on the outdoorunit. ŒDisconnected wire for the MA remote controller or disconnected line to the terminal block. ŒThe indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7). ŒThe male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector

(CN40). In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect- ed to the female power supply switch connector (CN40) on the outdoor unit. 4) Disconnected M-NET transmission line on the indoor unit side. 5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or disconnected connector.

(2) Check method and remedy 1) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.

NO

Same symptom for all units in a system with one outdoor unit?

Measure voltages of the terminal block for transmission line (TB5) on the indoor unit.

YES

Check the self-diagnosis LED

NO

Check 4.

17 - 30V?

YES

Check for 2 and 3.

Is the error code 7102

YES

Check 5.

NO

Check 1).

YES

Correct the error.

NO

Indoor unit board or MA remote controller failure

Correct the error.

Refer to section IX [4] -8- (2) for Troubleshooting transmission power circuit of outdoor unit.

displayed? · Error found?

Page 268 of the Mitsubishi Electronics P96 user manual — NO
Page 268 · click to enlarge
Page 268

In the case of MA remote controller

3. Phenomena "HO" or "PLEASE WAIT" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. ("HO" or "PLEASE WAIT" display will normally turn off 5 minutes later after the power on.)

(1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit. 2) Short-circuited transmission line 3) Incorrect wiring of the M-NET transmission line on the outdoor unit. ŒDisconnected wire for the MA remote controller or disconnected line to the terminal block. ŒThe indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7). ŒThe male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector

(CN40). In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect- ed to the female power supply switch connector (CN40) on the outdoor unit 4) Disconnected M-NET transmission line on the indoor unit. 5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or disconnected connector. 6) Incorrect wiring for the MA remote controller ŒShort-circuited wire for the MA remote controller ŒDisconnected wire for the MA remote controller (No.2) and disconnected line to the terminal block. ŒReversed daisy-chain connection between groups ŒIncorrect wiring for the MA remote controller to the terminal block for transmission line connection (TB5) on the indoor unit ŒThe M-NET transmission line is connected incorrectly to the terminal block (TB13) for the MA remote controller. 7) The sub/main setting of the MA remote controller is set to sub. 8) 2 or more main MA remote controllers are connected. 9) Indoor unit board failure (MA remote controller communication circuit) 10) Remote controller failure 11) Outdoor unit failure (Refer to IX [8] Troubleshooting Using the Outdoor Unit LED Error Display.)(page 330)

(2) Check method and remedy 1) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.

NO

Same symptom for all units in a system with one outdoor unit?

YES

Measure voltages of the terminal block for transmission line (TB5) on the indoor unit.

Check the self-diagnosis LED

NO

17 - 30V?

Check 4.

YES

Check 2 and 3.

Is the error code 7102

YES

Check for 5 and 6.

NO

YES

Correct the error.

YES

Replace the M-NET remote controller with the MA remote controller

NO

NO

Indoor unit board or MA remote controller failure

Check (1).

Correct the error.

Refer to section IX [4] -8- (2) for Troubleshooting transmission power circuit of outdoor unit.

displayed? · Error found? · Error found?

Page 269 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 269 · click to enlarge
Page 269

Flow chart Even if the operation button on the remote controller is pressed, the indoor and the outdoor units do not start running.

Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 269)
Fig. 74

After the main power on, start the MA remote

indoor unit turn turned on again? DEMAND by MELANS?

Check that no error occurs in other indoor units.

9-13VDC if the voltage is applied and 0V if no voltage

*After correcting the error, daisy-chain the wire for the MA remote controller again.

9-13VDC if the voltage is applied and 0V if no voltage is applied.

Page 270 of the Mitsubishi Electronics P96 user manual — In case of M-NET remote controller
Page 270 · click to enlarge
Page 270

In case of M-NET remote controller

1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start running. (Power indicator does not appear on the screen.)

(1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit. 2) Short circuit of the transmission line. 3) Incorrect wiring of the M-NET transmission line on the outdoor unit. ŒDisconnected wire for the MA remote controller or disconnected line to the terminal block. ŒThe indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7). 4) Disconnected transmission line on the remote controller. 5) Remote controller failure 6) Outdoor unit failure (Refer to IX [8] Troubleshooting Using the Outdoor Unit LED Error Display.)(page 330)

(2) Check method and remedy 1) Check voltage of the transmission terminal block for of the M-NET remote controller. ŒIf voltage between is 17V and 30V -> M-NET remote controller failure Œ When voltage is 17V or less -> Refer to IX [4] -8- (2) . 2) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.

Page 271 of the Mitsubishi Electronics P96 user manual — (2) Check method and remedy
Page 271 · click to enlarge
Page 271

In case of M-NET remote controller

2. Phenomena When the remote controller operation SW is turned on, a temporary operation display is indicated, and the display lights out immediately.

(1) Cause 1) The power is not supplied to the indoor unit.

ŒThe main power of the indoor unit (AC208/230V) is not on. ŒThe connector on the indoor unit board has come off. ŒThe fuse on the indoor unit board has melted. ŒTransformer failure and disconnected wire of the indoor unit ŒThe indoor unit board failure 2) The outdoor control board failure As the indoor unit does not interact with the outdoor unit, the outdoor unit model cannot be recognized.

(2) Check method and remedy

Mitsubishi Electronics P96 — (2) Check method and remedy diagram (page 271)
Fig. 75 · (2) Check method and remedy

Check voltage of the power supply terminal on the indoor unit.

Check the main power of the power supply wire Turn on the power again.

Melted? Check 200V circuit for short circuit and ground fault

Check the cause of the disconnected transformer. Ground fault on the circuit board

Check for the change of LED display by operating dip switch SW1 for self-diagnosis.

Check self-diagnosis function of outdoor unit after the power on.

Page 272 of the Mitsubishi Electronics P96 user manual — YES
Page 272 · click to enlarge
Page 272

In case of M-NET remote controller

3. Phenomena "HO" display on the remote controller does not disappear, and no operation is performed even if the button is pressed.

(1) Cause Without using MELANS 1) Outdoor unit address is set to "00" 2) A wrong address is set. ŒThe address of the indoor unit that is connected to the remote controller is incorrect. (It should equal the M-NET remote con-

troller address plus 100.) ŒA wrong address is set to the M-NET remote controller. (100 must be added to the address of the indoor unit.) 3) Faulty wiring of the terminal block for transmission line (TB5) of the indoor unit in the same group with the remote controller. 4) The centralized control switch (SW2-1) on the outdoor unit is set to ON. 5) Disconnection or faulty wiring of indoor unit transmission line. 6) Disconnection between the terminal block for M-NET line connection (TB5) of the indoor unit and the male connector (CN2M) 7) The male power supply connectors on 2 or more outdoor units are connected to the female power supply switch connector (CN40) for the transmission line for centralized control. 8) Outdoor unit control board failure 9) Outdoor unit control board failure 10) Remote controller failure Interlocking control with MELANS 1) No group registration is made using MELANS. (The indoor unit and the M-NET remote controller are not grouped.) 2) Disconnected transmission line for centralized control (TB7) of the outdoor unit 3) The male power supply connector is connected to CN40 on more than one outdoor unit, or the connector is connected to CN40 on the outdoor unit in the system to which a power supply unit for transmission line is connected. Using MELANS 1) When MELANS is used, "HO" display on the remote controller will disappear when the indoor unit and the local remote con- troller (M-NET remote controller) are grouped. If "HO" does not disappear after the registration, check the causes (2) 1) - 3).

(2) Check method and remedy

NO

Are all the units in the system experiencing the same problem?

YES

Check the address of the M-NET remote controller on which "HO" is displayed.

Check the address of the outdoor unit.

NO

NO *1

A wrong address is set to the M-NET remote controller.

Indoor unit + 100?

51. 100?

A wrong address is set to the outdoor unit.

YES

YES

Check the address of the indoor unit to be coupled.

Check the centralized centralized switch (SW2-1) on the outdoor unit.

NO

A wrong address is set to the indoor unit.

ON?

YES

Wrong switch setting Change it from ON to OFF.

NO

YES

Measure voltages of the terminal block for M-NET transmission line on the indoor unit.

Indoor unit control board failure

Wrong wiring of the M-NET transmission line of the indoor unit

NO

17 - 30V?

YES

Check connection between indoor M-NET transmission terminal block (TB5) and the male connector (CN2M)

YES

NO

Indoor unit board or remote controller failure

Correct the error.

*1. When the indoor unit address is set to 1 - 50, the address will be forcibly set to 100.

Show 5 more labels / short text on this page
Without using MELANS · M-NET remote controller · - 100? · Disconnected connector (CN2M) · Disconnected?
Page 273 of the Mitsubishi Electronics P96 user manual — Generates at interlocking registration between LOSSNAY and the indoor unit
Page 273 · click to enlarge
Page 273

In case of M-NET remote controller

4. Phenomena "88" appears on the remote controller when the address is registered or confirmed.

(1) Cause, check method and remedy

Cause Check method and remedy

An error occurs when the address is registered or confirmed. (common)

1. A wrong address is set to the unit to be coupled. (1) Confirm the address of unit to be coupled.
2. The transmission line of the unit to be coupled is disconnected or is not connected.

(2) Check the connection of transmission line.

3. Circuit board failure of the unit to be coupled (3) Check voltage of the terminal block for transmission line of the unit to be coupled.
1. Normal if voltage is between DC17 and 30V.
4. Improper transmission line work 2) Check (5) in case other than 1).

Generates at interlocking registration between LOSSNAY and the indoor unit

5. The power of LOSSNAY is OFF. (4) Check for the main power of LOSSNAY.

Generates at confirmation of controllers used in the system in which the indoor units connected to differ- ent outdoor units are grouped

6. The power of the outdoor unit to be confirmed has been cut off.

(5) Check the power supply of the outdoor unit which is coupled with the unit to be confirmed.

7. Transmission line is disconnected from the terminal block for central control system connection (TB7) on the outdoor unit.

(6) Check that the transmission line for centralized control (TB7) of the outdoor unit is not disconnect- ed.

8. When the indoor units connected to different outdoor units are grouped without MELANS, the male power supply connector is not connected to the female power supply switch connector (CN40) for the transmission line for centralized control.

(7) Check voltage of the transmission line for central- ized control.

9. The male power supply connectors on 2 or more outdoor units are connected to the female power supply switch connector (CN40) for the transmission line for centralized control.
1. Normal when voltage is between 10V and 30V
10. In the system to which MELANS is connected, the male power supply connector is connected to the female power supply switch connector (CN40) for the transmission line for centralized control.
2. Check 8 - 11 described on the left in case other than 1).
11. Short circuit of the transmission line for centralized control
Page 274 of the Mitsubishi Electronics P96 user manual — ON
Page 274 · click to enlarge
Page 274

Both for MA remote controller and M-NET remote controller

1. Phenomena Although cooling operation starts with the normal remote controller display, the capacity is not enough

(1) Cause, check method and remedy

Cause Check method and remedy

1. Compressor frequency does not rise sufficiently.

(1) Check pressure difference between the detected pressure by the pressure sensor and the actual pressure with self-diagnosis LED. -> If the accurate pressure is not detected, check the pressure sensor. (Refer to the page on Trouble- shooting of Pressure Sensor).

ŒFaulty detection of pressure sensor. ŒProtection works and compressor frequency does

not rise due to high discharge temperature ŒProtection works and compressor frequency does

not rise due to high pressure ŒPressure drops excessively.

SW1

1 2 3 4 5 6 7 8 9 10

ON

SW1

1 2 3 4 5 6 7 8 9 10

ON

(2) Check temperature difference between the evapo- rating temperature (Te) and the target evaporating temperature (Tem) with self-diagnosis LED.

SW1

1 2 3 4 5 6 7 8 9 10

ON

Target evaporating temperature Tem

SW1

1 2 3 4 5 6 7 8 9 10

ON

2. Indoor unit LEV malfunction Refer to the page of LEV troubleshooting ([4] -5- ).(page 279) Œ Insufficient refrigerant flows due to LEV malfunc-

tion (not enough opening) or protection works and compressor frequency does not rise due to pres- sure drop. ŒRefrigerant leak from LEV on the stopping unit

causes refrigerant shortage on the running unit.

3. RPM error of the outdoor unit FAN Refer to the page on troubleshooting of the outdoor unit fan. Refer to 5106.(page 217) Refer to 1302.(page 186) Œ Motor failure or board failure, or airflow rate de-

crease due to clogging of the heat exchanger ŒThe fan is not properly controlled as the outdoor

temperature cannot be precisely detected by the temperature sensor. ŒThe fan is not properly controlled as the pressure

cannot be precisely detected by the pressure sen- sor.

High pressure sensor · Low pressure sensor · Evaporating temperature Te

Page 275 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 275 · click to enlarge
Page 275

Cause Check method and remedy

4. Long piping length The cooling capacity varies greatly depending on the pressure loss. (When the pressure loss is large, the cooling capacity drops.)

Check the piping length to determine if it is contrib- uting to performance loss. Piping pressure loss can be estimated from the temperature difference between the indoor unit heat exchanger outlet temperature and the satura- tion temperature (Te) of 63LS. ->Correct the piping. 5. Piping size is not proper (thin)

6. Insufficient refrigerant amount Protection works and compressor frequency does not rise due to high discharge temperature.

Refer to 1-1. (Compressor frequency does not rise sufficiently.)(page 265)Refer to the page on refrig- erant amount adjustment(page 157)

7. Clogging by foreign object Check the temperature difference between in front of and behind the place where the foreign object is clogging the pipe (upstream side and downstream side). When the temperature drops significantly, the foreign object may clog the pipe. -> Remove the foreign object inside the pipe.
8. The indoor unit inlet temperature is excessively. (Less than 15°C [59°F] WB)

Check the inlet air temperature and for short cy- cling. Change the environment where the indoor unit is used.

9. Compressor failure The amount of circulating refrigerant decreases due to refrigerant leak in the compressor.

Check the discharge temperature to determine if the refrigerant leaks, as it rises if there is a leak.

10. LEV3 malfunction Sufficient liquid refrigerant is not be supplied to the indoor unit as sufficient sub cool cannot be secured due to LEV3 malfunction.

Refer to the page of LEV troubleshooting ( [4] -5- ).(page 279) It most likely happens when there is little difference or no difference between TH12 and TH15.

11. TH12, TH15 and 63HS1 sensor failure or faulty wiring LEV3 is not controlled normally.

ŒCheck the thermistor. ŒCheck wiring.

Page 276 of the Mitsubishi Electronics P96 user manual — ON
Page 276 · click to enlarge
Page 276
2. Phenomena Although heating operation starts with the normal remote controller display, the capacity is not enough.

(1) Cause, check method and remedy

Cause Check method and remedy

1. Compressor frequency does not rise sufficiently.

(1) Check pressure difference between the detected pressure by the pressure sensor and the actual pressure with self-diagnosis LED. -> If the accurate pressure is not detected, check the pressure sensor.(Refer to the page on Trouble- shooting of Pressure Sensor)

ŒFaulty detection of pressure sensor. ŒProtection works and compressor frequency does

not rise due to high discharge temperature ŒProtection works and compressor frequency does

not rise due to high pressure.

SW1

1 2 3 4 5 6 7 8 9 10

ON

SW1

1 2 3 4 5 6 7 8 9 10

ON

(2) Check the difference between the condensing tem- perature (Tc) and the target condensing tempera- ture (Tcm) with self-diagnosis LED.

SW1

1 2 3 4 5 6 7 8 9 10

ON

Target condensing temperature Tcm

SW1

1 2 3 4 5 6 7 8 9 10

ON

High pressure sensor · Low pressure sensor · Condensing temperature Tc

Page 277 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 277 · click to enlarge
Page 277

Cause Check method and remedy

2. Indoor unit LEV malfunction Insufficient refrigerant flows due to LEV malfunction (not enough opening).

Refer to the page of LEV troubleshooting ( [4] -5- ).(page 279)

3. Temperature reading error on the indoor unit piping temperature sensor If the temperature reading on the sensor is higher than the actual temperature, it makes the subcool seem smaller than it is, and the LEV opening decreases too much.

Check the thermistor.

4 RPM error of the outdoor unit FAN Refer to the page on outdoor unit fan ([4] -4- ).(page 279) ŒMotor failure or board failure, or airflow rate de-

crease, pressure drop due to clogging of the heat exchanger leading to high discharge temperature ŒThe fan is not properly controlled as the tempera-

ture cannot be precisely detected with the piping sensor.

5. Insulation failure of the refrigerant piping
6. Long piping length Excessively long piping on the high pressure side causes pressure loss leading to increase in the high pressure.

Confirm that the characteristic of capacity drop due to piping length. -> Change the pipe

7. Piping size is not proper (thin)
8. Clogging by foreign object Check the temperature difference between the upstream and the downstream of the pipe section that is blocked. Since blockage in the extended section is difficult to locate, operate the unit in the cooling cycle, and follow the same procedures that are used to locate the blockage of pipe during cooling operation. ->Remove the blockage in the pipe.
9. The indoor unit inlet temperature is excessively high.(exceeding 28°C [82°F])

Check the inlet air temperature and for short cy- cling. Change the environment where the indoor unit is used.

10. Insufficient refrigerant amount Protection works and compressor frequency does not rise due to low discharge temperature Refrigerant recovery operation is likely to start.

Refer to 2 - 1. (Compressor frequency does not rise sufficiently.)(page 265) Refer to the page on refrigerant amount adjustment.(page 157)

11. Compressor failure (same as in case of cooling) Check the discharge temperature.
12. LEV3 actuation failure A drop in the low pressure that is caused either by a blockage of liquid pipe or by a pressure loss and the resultant slowing of refrigerant flow causes a tendency for the discharge temperature to rise.

Refer to the page on troubleshooting the LEV ([4] - 5-).(page 279)

Page 278 of the Mitsubishi Electronics P96 user manual — (1) Cause, check method and remedy
Page 278 · click to enlarge
Page 278
3. Phenomena Outdoor unit stops at times during operation.

(1) Cause, check method and remedy

Cause Check method and remedy

The first stop is not considered as an error, as the unit turns to anti-restart mode for 3 minutes as a pre- liminary error.

(1) Check the mode operated in the past by displaying preliminary error history on LED display with SW1.

Error mode (2) Reoperate the unit to find the mode that stops the unit by displaying preliminary error history on LED display with SW1. -> Refer to the reference page for each error mode. 1) Abnormal high pressure

2. Abnormal discharge air temperature
3. Heatsink thermistor failure *Display the indoor piping temperature table with SW1 to check whether the freeze proof operation runs properly, and check the temperature. 4) Thermistor failure
5. Pressure sensor failure
6. Over-current break
7. Refrigerant overcharge
Page 279 of the Mitsubishi Electronics P96 user manual — Wave shape check
Page 279 · click to enlarge
Page 279

[3] Investigation of Transmission Wave Shape/Noise

1. M-NET transmission Control is performed by exchanging signals between the outdoor unit and the indoor unit (M-NET remote controller) through M-NET transmission. Noise interference on the transmission line will interrupt the normal transmission, leading to erroneous operation. (1) Symptoms caused by noise interference on the transmission line

Cause Erroneous operation Error code Error code definition

Signal is transformed and will be misjudged as the signal of another address.

Transmission wave pattern is transformed due to the noise creating a new signal

6602 Transmission pro- cessor hardware er- ror

Transmission wave pattern is transformed due to the noise, and will not be received normally leading to no acknowledgement (ACK).

6607 No ACK error

Transmission cannot be performed due to the fine noise.

6603 Transmission line bus busy error

Transmission is successful; however, the acknowl- edgement (ACK) or the response cannot be re- ceived normally due to the noise.

6607 6608 No ACK error No response error

(2) Wave shape check

V HL

V BN

52

[With transmission]

Logic "0" Logic "1"

No fine noise allowed

Wave shape check

Check the wave pattern of the transmission line with an oscilloscope. The following conditions must be met. 1) Small wave pattern (noise) must not exist on the transmission signal. (Minute noise (approximately 1V) can be generated by DC-DC converter or the inverter operation; however, such noise is not a problem when the shield of the transmission line is grounded.) 2) The sectional voltage level of transmission signal should be as follows.

Logic Voltage level of the transmission line

0 VHL = 2.5V or higher

1 VBN = 1.3V or below

Show 6 more labels / short text on this page
6600 Address overlap · Noise interference on · the transmission line · No fine noise · allowed · [Without transmission]
Page 280 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 280 · click to enlarge
Page 280

(3) Check method and remedy 1) Measures against noise Check the followings when noise exists on the wave or the errors described in (1) occur.

Error code definition Remedy

Check that the wiring work is performed ac- cording to wiring specifications.

1. The transmission line and the power line are not wired too closely.

Isolate the transmission line from the power line (5cm [1-31/32"] or more). Do not insert them in the same conduit.

2. The transmission line is not bundled with that for another systems.

The transmission line must be isolated from another transmission line. When they are bundled, erroneous operation may be caused.

3. The specified wire is used for the transmission line.

Use the specified transmission line. Type: Shielded wire CVVS/CPEVS/MVVS (For M-NET remote controller) Diameter: 1.25mm2 [AWG16] or more (Remote controller wire: 0.3 - 1.25mm2 [AWG22-16])

4. When the transmission line is daisy-chained on the indoor unit terminals, are the shields daisychained on the terminals, too?

The transmission is two-wire daisy-chained. The shielded wire must be also daisy-chained. When the shielded cable is not daisy-chained, the noise cannot be reduced enough.

Check that the grounding work is performed according to grounding specifi- cations.

5. Is the shield of the indooroutdoor transmission cable grounded to the earth terminal on the outdoor unit?

Connect the shield of the indoor-outdoor transmission cable to the earth terminal ( ) on the outdoor unit. If no grounding is provided, the noise on the transmission line can- not escape leading to change of the transmission signal.

6. Check the treatment method of the shield of the transmission line (for centralized control).

The transmission cable for centralized control is less subject to noise interference if it is grounded to the outdoor unit whose power jumper cable was moved from CN41 to CN40 or to the power sup- ply unit. The environment against noise varies depending on the distance of the transmission lines, the number of the connected units, the type of the controllers to be connected, or the environment of the installation site. Therefore, the transmission line work for central- ized control must be performed as follows.

1. When no grounding is provided: Ground the shield of the transmission cable by connecting to the outdoor unit whose power jumper connector was moved from CN41 to CN40 or to the power supply unit.
2. When an error occurs even though one point grounding is provided: Ground the shield on all outdoor units.
2. Check the followings when the error "6607" occurs, or "HO" appears on the display on the remote controller.

Error code definition Remedy

7. The farthest distance of transmission line is 200m [656ft] or longer. Check that the farthest distance from the outdoor unit to the indoor unit and to the remote controller is within 200m [656ft].
8. The types of transmission lines are different. Use the specified transmission line. Type: Shielded wire CVVS/CPEVS/MVVS (For M-NET remote controller) Diameter: 1.25mm 2 [AWG16] or more (Remote controller wire: 0.3-1.25mm 2 [AWG22-16])
9. Outdoor unit circuit board failure Replace the outdoor unit control board or the power supply board for the transmission line.
10. Indoor unit circuit board failure or remote controller failure

Replace the indoor unit circuit board or the remote controller.

11. The MA remote controller is connected to the MNET transmission line.

Connect the MA remote controller to the terminal block for MA re- mote controller (TB15).

Page 281 of the Mitsubishi Electronics P96 user manual — DC9~12V
Page 281 · click to enlarge
Page 281
2. MA remote controller transmission The communication between the MA remote controller and the indoor unit is performed with current tone burst.

(1) Symptoms caused by noise interference on the transmission line

If noise is generated on the transmission line, and the communication between the MA remote controller and the indoor unit is interrupted for 3 minutes in a row, MA transmission error (6831) will occur.

(2) Confirmation of transmission specifications and wave pattern

TB15 A B

A, BNo polarity

Across terminal No. 1-2

: Power supply (9V to 12VDC)

Transmission waveform (Across terminal No.1 - 2)

DC9~12V

Voltage among terminals must

Logic 1 Logic 0 Logic 1 Logic 1

be between DC9 and 12 V.

12msec

Show 4 more labels / short text on this page
Indoor unit · MA remote controller · Satisfies the formula · 12 msec/bit 5%
Page 282 of the Mitsubishi Electronics P96 user manual — 63HS1 1 2 3
Page 282 · click to enlarge
Page 282

[4] Troubleshooting Principal Parts

-1High-Pressure Sensor (63HS1, PS1, PS3)

1. Compare the pressure that is detected by the high pressure sensor, and the high-pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the highpressure sensor appears on the LED1 on the control board.

SW1

1 2 3 4 5 6 7 8 9 10 ON

(1) While the sensor is stopped, compare the gauge pressure and the pressure displayed on self-diagnosis LED1. 1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal pressure is caused due to gas leak. 2) When the pressure displayed on self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the connector may be defective or be disconnected. Check the connector and go to (4). 3) When the pressure displayed on self-diagnosis LED1 exceeds 4.15MPa [601psi], go to (3). 4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2). (2) Compare the gauge pressure and the pressure displayed on self-diagnosis LED1 while the sensor is running. (Com-

pare them by MPa [psi] unit.) 1) When the difference between both pressures is within 0.098MPa [14psi], both the high pressure sensor and the control board are normal. 2) When the difference between both pressures exceeds 0.098MPa [14psi], the high pressure sensor has a problem. (perfor- mance deterioration) 3) When the pressure displayed on self-diagnosis LED1 does not change, the high pressure sensor has a problem. (3) Remove the high pressure sensor from the control board to check the pressure on the self-diagnosis LED1. 1) When the pressure displayed on self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the high pressure sensor has a problem. 2) When the pressure displayed on self-diagnosis LED1 is approximately 4.15MPa [601psi], the control board has a problem. (4) Remove the high pressure sensor from the control board, and short-circuit between the No.2 and 3 connectors

(63HS1, PS1, PS3) to check the pressure with self-diagnosis LED1. 1) When the pressure displayed on the self-diagnosis LED1 exceeds 4.15MPa [601psi], the high pressure sensor has a problem. 2) If other than 1), the control board has a problem.

2. Pressure sensor configuration The high pressure sensor consists of the circuit shown in the figure below. If DC 5V is applied between the red and the black wires, voltage corresponding to the pressure between the white and the black wires will be output, and the value of this voltage will be converted by the microcomputer. The output voltage is 0.071V per 0.098MPa [14psi].

The pressure sensor on the body side is designed to connect to the connector. The connector pin number on the body side is different from that on the control board side.

Body side Control board side

Vcc Pin 1 Pin 3

Vout Pin 2 Pin 2

GND Pin 3 Pin 1

4.5 [653]

63HS1 1 2 3

Pressure (MPa [psi])

4.0 [580]

Pressure 0 ~ 4.15 MPa [601psi] Vout 0.5 ~ 3.5 V 0.071 V / 0.098 MPa [14 psi]

3.5 [508]

3.0 [435]

2.5 [363]

2.0 [290]

1.5 [218]

1.0 [145]

0.5 [73]

Vcc (DC 5 V)(Red)

0 0.5 1 1.5 2 2.5 3 3.5

Output voltage (V)

Connector · GND (Black) · Vout (White)

Page 283 of the Mitsubishi Electronics P96 user manual — 63LS 1 2 3
Page 283 · click to enlarge
Page 283

-2Low-Pressure Sensor (63LS)

1. Compare the pressure that is detected by the low pressure sensor, and the low pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the lowpressure sensor appears on the LED1 on the control board.

SW1

1 2 3 4 5 6 7 8 9 10 ON

(1) While the sensor is stopped, compare the gauge pressure and the pressure displayed on self-diagnosis LED1. 1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal pressure is caused due to gas leak. 2) When the pressure displayed on self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the connector may be defective or be disconnected. Check the connector and go to (4). 3) When the pressure displayed on self-diagnosis LED1 exceeds 1.7MPa [247psi], go to (3). 4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2). (2) Compare the gauge pressure and the pressure displayed on self-diagnosis LED1 while the sensor is running.(Com-

pare them by MPa [psi] unit.) 1) When the difference between both pressures is within 0.03MPa [4psi], both the low pressure sensor and the control board are normal. 2) When the difference between both pressures exceeds 0.03MPa [4psi], the low pressure sensor has a problem. (performance deterioration) 3) When the pressure displayed on the self-diagnosis LED1 does not change, the low pressure sensor has a problem. (3) Remove the low pressure sensor from the control board to check the pressure with the self-diagnosis LED1 display. 1) When the pressure displayed on the self-diagnosis LED1 is between 0 and 0.098MPa [14psi], the low pressure sensor has a problem. 2) When the pressure displayed on self-diagnosis LED1 is approximately 1.7MPa [247psi], the control board has a problem. ŒWhen the outdoor temperature is 30°C [86°F] or less, the control board has a problem. ŒWhen the outdoor temperature exceeds 30°C [86°F], go to (5). (4) Remove the low pressure sensor from the control board, and short-circuit between the No.2 and 3 connectors

(63LS:CN202) to check the pressure with the self-diagnosis LED1. 1) When the pressure displayed on the self-diagnosis LED1 exceeds 1.7MPa [247psi], the low pressure sensor has a problem. 2) If other than 1), the control board has a problem. (5) Remove the high pressure sensor (63HS1) from the control board, and insert it into the connector for the low pres-

sure sensor (63LS) to check the pressure with the self-diagnosis LED1. 1) When the pressure displayed on the self-diagnosis LED1 exceeds 1.7MPa [247psi], the control board has a problem. 2) If other than 1), the control board has a problem. 2. Low-pressure sensor configuration The low pressure sensor consists of the circuit shown in the figure below. If DC5V is applied between the red and the black wires, voltage corresponding to the pressure between the white and the black wires will be output, and the value of this voltage will be converted by the microcomputer. The output voltage is 0.173V per 0.098MPa [14psi].

The pressure sensor on the body side is designed to connect to the connector. The connector pin number on the body side is different from that on the control board side.

Body side Control board side

Vcc Pin 1 Pin 3

Vout Pin 2 Pin 2

GND Pin 3 Pin 1

1.8 [261]

1.6 [232]

63LS 1 2 3

Pressure (MPa [psi])

Pressure 0 ~ 1.7 MPa [247psi] Vout 0.5 ~ 3.5 V 0.173 V / 0.098 MPa [14 psi]

1.4 [203]

1.2 [174]

1.0 [145]

0.8 [116]

0.6 [87]

0.4 [58]

0.2 [29]

Vcc (DC 5 V)(Red)

0 0.5 1 1.5 2 2.5 3 3.5

Output voltage (V)

Connector · GND (Black) · Vout (White)

Page 284 of the Mitsubishi Electronics P96 user manual — (2) In case of SV1a (Bypass valve)
Page 284 · click to enlarge
Page 284

-3Solenoid Valve

Check whether the output signal from the control board and the operation of the solenoid valve match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED's. Each LED shows whether the relays for the following parts are ON or OFF. LEDs light up when relays are on.

The circuits on some parts are closed when the relays are ON. Refer to the following instructions.

SW1

LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8

Upper 21S4a CH11 SV1a SV2

SW1

1 2 3 4 5 6 7 8 9 10 ON

Upper SV4a SV4b SV4c SV5c SV4d SV9

SW1

1 2 3 4 5 6 7 8 9 10 ON

When a valve malfunctions, check if the wrong solenoid valve coil is not attached the lead wire of the coil is not disconnected, the connector on the board is not inserted wrongly, or the wire for the connector is not disconnected.

(1) In case of 21S4a (4-way switching valve)

About this 4-way valve When not powered: Conducts electricity between the oil separator outlet and heat exchanger AND the gas ball valve (BV1) and the accumulator to complete the circuit for the cooling cycle. When powered: The electricity runs between the oil separator and the gas ball valve, and between the heat exchanger and the accumulator. This circulation is for heating.

Check the LED display and the intake and the discharge temperature for the 4-way valve to check whether the valve has no faults and the electricity runs between where and where.Do not touch the pipe when checking the temperature, as the pipe on the oil separator side will be hot.

Do not give an impact from outside, as the outer hull will be deformed leading to the malfunction of the inner valve.

(2) In case of SV1a (Bypass valve)

This solenoid valve opens when powered (Relay ON). 1) At compressor start-up, the SV1a turns on for 4 minutes, and the operation can be checked by the self-diagnosis LED display and the closing sound. 2) To check whether the valve is open or closed, check the change of the SV1a downstream piping temperature while the valve is being powered.Even when the valve is closed, high-temperature refrigerant flows inside the capillary next to the valve. (Therefore, temperature of the downstream piping will not be low with the valve closed.) (3) In case of SV2 (Bypass valve)

This solenoid valve opens when powered (Relay ON). This valve turns on when low-pressure (LPS) drops to 0.25 MPa [36 psi] or below during Heating-only or Heating-main oper- ation AND after 5 minutes have passed after compressor startup; OR when 63HS1 is above 3.5 MPa [507psi] with the SV9 turned on and SV5b turned off AND the frequency drops to the minimum. To check whether the valve is open or closed, check the change of the SV1a downstream piping temperature while the valve is being powered.Even when the valve is closed, high-temperature refrigerant flows inside the capillary next to the valve.

Display · Lower SV5b · Lower

Page 285 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 285 · click to enlarge
Page 285

(4) SV4a, 4b and 4d (P72 model), SV4a - 4d (P96 and P120 models)(Controls heat exchanger capacity) 1) Depending on the conditions during Cooling-only operation, at least one of the solenoid valves among SV4a through 4d turns on. Check for proper operation on the LED and by listening for the operation sound of the solenoid valve. 2) During Heating-only operation, SV4a through 4d all turn on. Check for proper operation on the LED and by listening for the operation sound of the solenoid valves. 3) Depending on the conditions during Cooling-main or Heating-main operation, at least one of the solenoid valves among SV4a through 4d turns on. Check for proper operation on the LED and by listening for the operation sound of the solenoid valve. 4) The diagram on the next page shows the refrigerant flow. This diagram shows the flow of the high-temperature (high-pressure) gas refrigerant in the Cooling-only and Cooling-main modes and the flow of the low-temperature gas/liquid refrigerant in the Heating-only and Heating-main modes. Refer to the refrigerant circuit diagram. Solenoid valves turns on and off according to such factors as the capacity of the indoor units in operation and outside temperature. Check the LED. Remove the SV coil, open the lid, and check the plunger. The type of pin face wrench that is listed in the service parts list is required to perform this task.

Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 285)
Fig. 76
Page 286 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 286 · click to enlarge
Page 286
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 286)
Fig. 77

Solenoid valve block (four compartments) P96 and P120 models

Tightening torque150N . m [1500kg . cm]
Page 287 of the Mitsubishi Electronics P96 user manual — (7) In the case of SV9 (Bypass valve)
Page 287 · click to enlarge
Page 287

(5) In the case of SV5b (Bypass valve)

This solenoid valve closes when energized (when the relay is on). This valve turns off for five minutes after the completion of the defrost cycle, or when SV9 is on turned ON and the value of 63HS1 is greater than 3.5 MPa [507psi] during Heating-only or Heating-main operation at the minimum frequency. The valve position can be determined by measuring and monitoring the changes in the pipe temperature on the downstream of SV5b while the unit is de-energized. When the valve is open, high-temperature gas refrigerant passes through the pipe. Do not at- tempt to check the pipe temperature by touching the pipe.

(6) In the case of SV5c (Bypass valve)

This solenoid valve opens when energized (when the relay is on). This valve turns on, depending on the conditions during Cooling-only or Cooling-main operation. Check for proper operation on the LED and by listening for the operation sound of the solenoid valve.

(7) In the case of SV9 (Bypass valve)

This solenoid valve opens when energized (when the relay is on) This valve turns on when the value of 63HS1 is greater than 3.5 MPa [507psi] during Heating-only or Heating-main operation at the minimum frequency. The valve position can be determined by measuring and monitoring the changes in the pipe tem- perature on the downstream of SV9 while the unit is energized. When the valve is open, high-temperature gas refrigerant passes through the pipe. Do not attempt to check the pipe temperature by touching the pipe.

Page 288 of the Mitsubishi Electronics P96 user manual — (1) Indoor LEV and BC controller LEV
Page 288 · click to enlarge
Page 288

-4Outdoor Unit Fan

ŒTo check the revolution of the fan, check the inverter output state on the self-diagnosis LED, as the inverter on the outdoor

fan controls the revolutions of the fan.The revolution of the fan is approximately 680rpm(P72 model),790rpm(P96 and P120 models) at full speed. ŒWhen starting the fan, the fan runs at full speed for 5 seconds. ŒWhen setting the DIP SW1 as shown in the figure below, the inverter output [%] will appear. 100% indicates the full speed

and 0% indicates the stopping.

SW1

1 2 3 4 5 6 7 8 9 10 ON

ŒAs the revolution of the fan changes under control, at the interphase or when the indoor unit operation capacity is low, the

revolution of the fan may change. ŒIf the fan does not move or it vibrates, fan inverter board problem or fan motor problem is suspected. Refer to IX [4] -7- (2) [5]

"Check the fan motor ground fault or the winding." and IX [4] -7- (2) [6] "Check the FAN board failure."

-5LEV

LEV operation LEV are stepping-motor-driven valves that operate by receiving the pulse signals from the indoor and outdoor unit control boards.

(1) Indoor LEV and BC controller LEV

The valve opening changes according to the number of pulses. 1) Control boards and the LEV

Mitsubishi Electronics P96 — (1) Indoor LEV and BC controller LEV diagram (page 288)
Fig. 78 · (1) Indoor LEV and BC controller LEV
2. Pulse signal output and valve operation
Mitsubishi Electronics P96 — (1) Indoor LEV and BC controller LEV diagram (page 288)
Fig. 79 · (1) Indoor LEV and BC controller LEV

Output pulses change in the following orders when the Valve is closed; 1 2 3 4 1 Valve is open; 4 3 2 1 4

number 1 2 3 4 1 ON OFF OFF ON

2 ON ON OFF OFF 3 OFF ON ON OFF

*1. When the LEV opening angle does not change, all the output phases will be off. *2. When the output is open phase or remains ON, the motor cannot run smoothly, and rattles and vibrates.

3. LEV valve closing and opening operation
Page 289 of the Mitsubishi Electronics P96 user manual — E
Page 289 · click to enlarge
Page 289

C D

*When the power is turned on, the valve closing signal of 2200 pulses will be output from the indoor board to LEV to fix the valve position. It must be fixed at point A.

Valve opening (refrigerant flow rate)

When the valve operates smoothly, no sound from LEV or no vibration occurs, however, when the pulses change from E to A in the chart or the valve is locked, a big sound occurs.

*Whether a sound is generated or not can be determined by holding a screwdriver against it, then placing your ear against the handle.

Fully open1400 pulses A

E

B

80. 100 pulses

Valve closed · Valve open · Pulses

Page 290 of the Mitsubishi Electronics P96 user manual — (2) Judgment methods and possible failure mode
Page 290 · click to enlarge
Page 290

(2) Judgment methods and possible failure mode

Microcomputer driver circuit fail- ure

Disconnect the control board connector and connect the check LED as shown in the figure below.

When the drive circuit has a problem, replace the control board.

1 1 k LED

resistance : 0.25W 1k LED : DC15V 20mA or more When the main power is turned on, the indoor unit cir- cuit board outputs pulse signals to the indoor unit LEV for 10 seconds. If any of the LED remains lit or unlit, the drive circuit is faulty.

LEV mechanism is locked

If the LEV is locked, the drive motor runs idle, and makes a small clicking sound. When the valve makes a closing and opening sound, the valve has a problem.

Replace the LEV.

Disconnected or short-circuited LEV motor coil

Measure resistance between the coils (red - white, red -orange, brown - yellow, brown - blue) using a tester. They are normal if resistance is 150ohm 10%.

Replace the LEV coils.

Incomple sealing (leak from the valve)

When checking the refrigerant leak from the indoor LEV, run the target indoor unit in the fan mode, and the other indoor units in the cooling mode. Then, check the liquid temperature (TH22) with the self-diagnosis LED. When the unit is running in the fan mode, the LEV is ful- ly closed, and the temperature detected by the thermis- tor is not low. If there is a leak, however, the temperature will be low. If the temperature is extremely low compared with the inlet temperature displayed on the remote controller, the LEV is not properly sealed, however, if there is a little leak, it is not necessary to re- place the LEV when there are no effects to other parts.

If there is a large amount of leakage, replace the LEV.

Thermistor (liquid piping temperature detection)

Faulty wire con- nections in the connector or faulty contact

1. Check for loose pins on the connector and check the colors of the lead wires visually

Check the continuity at the points where an error occurs.

2. Disconnect the control board's connector and conduct a continuity check using a tester.
Show 4 more labels / short text on this page
Malfunction · Judgment method Remedy · mode · Linear Expansion Valve
Page 291 of the Mitsubishi Electronics P96 user manual — NO
Page 291 · click to enlarge
Page 291

-6Troubleshooting Principal Parts of BC Controller

1. Pressure sensor Troubleshooting flow chart for pressure sensor

START

Check whether the pressure sensor or the connectors of P1 and P3 are connected, properly

OK?

Repair the fault.

NO

Operating at the moment?

On the self-diagnosis monitor, measure Outdoor high-pressure 63HS1 Outdoor low-pressure 63LS BC controller pressure P1 (liquid side) and P3 (intermediate part) Check whether the result is 63HS1 P1 P3 63LS

Check whether the refrigerant pipe and the transmission line are connected correctly between the indoor unit and the BC controller.

NO

OK?

YES

All the compressors of the outdoor units to which the BC controller is connected are stopped.

NO

Fix the relation between the refrigerant piping and the transmission line.

OK?

YES

10 minutes or longer after the operation stops?

NO

Check P1 and P3 on the self-diagnosis LED, and check that the detected pressure is 0.098MPa [14psi] or less.

NO

Check whether the contact of the pressure sensor connector in trouble is not faulty.

OK?

Check that the difference between each detected pressure is 0.098MPa [14psi] or less.

OK?

NO

YES

NO

Restore contact failure.

OK? Is Pd P1 P3 Ps? Remove the pressure sensor connector from the board, and check the pressure.

NO

YES

YES

Both the board and the pressure sensor are normal.

NO

YES

Short-circuit between connecter pins #2 and #3 on the circuit board, and check the pressure.

Check whether the refrigerant pipe and the transmission line are connected correctly between the indoor unit and the BC controller.

NO

6MPa [870psi] pressure or more is displayed.

NO

Fix the relation between the refrigerant piping and the transmission line.

OK?

YES

YES

Replace the pressure sensor, which detects less than 6MPa [870psi] pressure, with the pressure sensor, which detects 6MPa [870psi] or more pressure, check the pressure, and check whether the detected pressure is displayed normally.

NO

OK?

YES

Replace the pressure sensor. Replace the board.

YES Note 2 · Pressure 0MPa [0psi]

Page 292 of the Mitsubishi Electronics P96 user manual — PS3
Page 292 · click to enlarge
Page 292
1. BC controller: Phenomena when the pressure sensor is connected wrongly (reverse connection of P1 and P3) to the board.

Cooling-only Heating only Heating main

Non-cooling Normal SC11 large SC16 small PHM large

Indoor heating SC small

SC11 large SC16 small PHM large

Non-cooling Indoor heating SC small

SC11 large SC16 small PHM large

Heating indoor Thermo ON Especially noise is large.

Heating indoor Thermo ON Especially noise is large.

2. Check the self-diagnosis switch (Outdoor control board SW1).

Measurement data SW1 setting value

1 2 3 4 5 6 7 8 9 10 ON

63HS1

1 2 3 4 5 6 7 8 9 10 ON

63LS

1 2 3 4 5 6 7 8 9 10 ON

BC controller pressure (liquid side)

PS1

1 2 3 4 5 6 7 8 9 10 ON

BC controller pressure (intermediate part)

PS3

3. Check whether CNP1 (liquid side) connector on the BC controller control board and the connector CNP2 (intermediate part) are not disconnected or not loose. 4) Check the pressure value on the self-diagnosis switch (same as note 2) with the connector of the applied pressure sensor is disconnected from the board.
Show 5 more labels / short text on this page
Symptoms · Cooling-main · Symbol · Outdoor high pressure · Outdoor low pressure
Page 293 of the Mitsubishi Electronics P96 user manual — NO
Page 293 · click to enlarge
Page 293

2. Temperature sensor

Troubleshooting instructions for thermistor

START

Pull out the thermistor connector in trouble from the board.

Measure the temperature of the thermistor in trouble. (actual measurement value)

Check the thermistor resistor.

Compare the temperature corresponding to the resistance measured by the thermistor and the temperature measured by a commercially available thermometer, and check whether there is no difference between them.

YES

Replace the thermistor Temperature difference

NO

Insert the connector of the thermistor in trouble into the board, check the sensor inlet temperature on the LED monitor, and check the temperature difference.

YES

Temperature difference Check for contact failure.

NO

Replace the control board.

Normal

Page 294 of the Mitsubishi Electronics P96 user manual — TH15
Page 294 · click to enlarge
Page 294

1) For the connectors on the board, TH11 and TH12 are connected to CN10, and TH15 and TH16 are connected to CN11. Dis- connect the connector in trouble, and check the sensor of each number. 2) ŒPull out the sensor connector from the I/O board, Do not pull the sensor by holding the lead wire. ŒMeasure the resistance with such as a tester. ŒCompare the measured value with that of shown in the figure below. When the result is 10%, it is normal. 3) Check the self-diagnosis switch (Outdoor control board SW1).

Measurement data SW1 setting value Symbol

1 2 3 4 5 6 7 8 9 10 ON

TH11

1 2 3 4 5 6 7 8 9 10 ON

G, GA (Standard / main)

TH12

1 2 3 4 5 6 7 8 9 10 ON

TH15

1 2 3 4 5 6 7 8 9 10 ON

TH16

1 2 3 4 5 6 7 8 9 10 ON

TH12

GB, HB (Sub 1)

1 2 3 4 5 6 7 8 9 10 ON

TH15

1 2 3 4 5 6 7 8 9 10 ON

TH12

GB, HB (Sub 2)

1 2 3 4 5 6 7 8 9 10 ON

TH15

Show 8 more labels / short text on this page
Liquid inlet temperature · Bypass outlet temperature · Bypass inlet temperature · Bypass inlet temperature · Bypass outlet temperature · Bypass inlet temperature · Bypass outlet temperature · Bypass inlet temperature
Page 295 of the Mitsubishi Electronics P96 user manual — NO
Page 295 · click to enlarge
Page 295

3. Troubleshooting flow chart for LEV Solenoid valve (1) LEV

No cooling capacity No heating capacity

Check whether the electric expansion valve and the solenoid valve connector are not disconnected or not loose.

NO

Repair the fault. Fault is found.

Run the cooling operation or the heating operation in the system in trouble (only in one system).

Cooling or heating operation

Check that LEV1 is fully open. Check that LEV1 is fully open.

NO

NO

LEV1 is fully open.

LEV1 is fully open.

Check LEV1.

YES

Check whether LEV3 is controlling superheat.

Check whether LEV 3 is controlled by the value of the differential pressure.

NO

NO

Superheat control OK Differential pressure OK

YES

YES

Check LEV3.

Check that SVA and SVC are ON. Check that SVA and SVC are OFF.

NO

NO

SVA, SVC ON SVA, SVC OFF

YES

YES

Check SVA and SVC.

Check that SVB is OFF. Check that SVB is ON.

NO

NO

SVB OFF SVB ON

YES

YES

Check SVB.

Heating operation · Cooling operation · Completed

Page 296 of the Mitsubishi Electronics P96 user manual — GB, HB
Page 296 · click to enlarge
Page 296
1. BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3) to the board.

Cooling-only Cooling-main Heating only Heating main

Non-cooling SH12 small, SC11 small SC16 small, branch pipe SC small BC controller sound

Non-cooling and non-heating SH12 small, SC11 small SC16 large, but branch pipe SC small BC controller sound PHM large

Indoor heating SC small PHM large

Non-cooling Indoor heating SC small PHM large

2. Check method of fully open state or fully closed state of LEV Œ Check LEV opening (pulse) on the self-diagnosis LED (Outdoor control board SW1).

Full open: 2000 pulses Fully closed: 110 pulses (In the case of heating-only mode, however, the pulse may become 110 or more.) ŒWhen LEV is fully open, measure the temperature at the upstream and downstream pipes of LEV, and make sure that there

is no temperature difference. ŒWhen LEV is fully closed, check that there is no refrigerant flowing sound. 3) Refer to the chart below to judge LEV opening controlled by the values of the differential pressure and of the superheat. (BC controller LEV basic operation characteristic)

mode Content Standards of judgment on

Difference between high pressure (P1) and interme- diate pressure (P3) is large.

0.3 to 0.4MPa [44 to 58psi] Inclined to

LEV1

Difference between high pressure (P1) and interme- diate pressure (P3) is small.

SH12 is large. SH12 < 20°C [36°F]

Difference between high pressure (P1) and interme- diate pressure (P3) is small.

0.3 to 0.4MPa [44 to 58psi]

LEV3

SC16 and SH12 are small. SC16 > 3°C [5.4°F] SH12 > 3°C [5.4°F]

Difference between high pressure (P1) and interme- diate pressure (P3) is large.

0.3 to 0.4MPa [44 to 58psi]

SH22 is large. SH22 < 20°C [36°F]

GB, HB

SH22 is small. SH22 > 3°C [5.4°F]

Show 39 more labels / short text on this page
Phenomena · Part Malfunction · Operation · mode · unit stable operation · Inclined to · close Heating only · Heating- · main Cooling- · main · open · Cooling-only · Cooling- · main · G, GA type · Inclined to · close · Heating only · Heating- · main · Cooling-only · Cooling- · main · Inclined to · open · Heating only · Heating- · main · Inclined to · Cooling-only · Cooling- · close · main · type) LEV3 · Cooling-only · Inclined to · Cooling- · open · main
Page 297 of the Mitsubishi Electronics P96 user manual — SC16
Page 297 · click to enlarge
Page 297

Self-diagnosis LED

Measurement data SW1 setting value Symbol

1 2 3 4 5 6 7 8 9 10 ON

1 2 3 4 5 6 7 8 9 10 ON

G, GA (Standard / main)

1 2 3 4 5 6 7 8 9 10 ON

BC controller bypass outlet superheat

1 2 3 4 5 6 7 8 9 10 ON

SH12

1 2 3 4 5 6 7 8 9 10 ON

BC controller intermediate part subcool

SC16

1 2 3 4 5 6 7 8 9 10 ON

BC controller liquid-side subcool SC11

GB, HB (Sub 1)

1 2 3 4 5 6 7 8 9 10 ON

1 2 3 4 5 6 7 8 9 10 ON

GB, HB (Sub 2)

Show 5 more labels / short text on this page
LEV1 opening · LEV2 opening · LEV3 opening · LEV3 opening · LEV3 opening
Page 298 of the Mitsubishi Electronics P96 user manual — Completed
Page 298 · click to enlarge
Page 298

Troubleshooting flow chart for solenoid valve body

Start

Check for pins not fully inserted on the connector and check the colors of the lead wires visually.

Intermediate connector Control board

When LEV is fully closed : tick sound When LEV is fully open : no sound Check the above.

2 5 1 3 4 6

5 4 3 2 1

OK? NO

YES

Replace LEV.

NO

Check that no refrigerant leaks from LEV.

OK?

YES

Repair the fault.

YES

OK? NO

Pull out the connector from the board, and check that the electricity runs with a tester. The wiring side of CN05 and 07: Among 1, 3 and 5, and among 2, 4 and 6

Replace LEV.

NO

Connect the LED for check, which is as shown in the right figure, to the board connector, and check that the LED keeps lighting for 10 seconds.

OK?

5 4 3 2 1

YES

Repair the fault.

Check the resistance between each coil with a tester (between red and white, red and orange, brown and yellow and brown and blue), and check that the resistance is 150 within 10%.

OK? NO

OK? NO

YES Replace LEV.

YES Replace the board in trouble.

Completed

Show 10 more labels / short text on this page
Brown · Brown · Red Blue Orange · Red Blue Orange · To LEV · Yellow · Yellow · White · White · LED 10 k
Page 299 of the Mitsubishi Electronics P96 user manual — YES
Page 299 · click to enlarge
Page 299

(2) Solenoid valve (SVA, SVB, SVC)

Faulty judgment of solenoid valve

Stop the operation of the applied BC remote controller system.

NO

YES

Check whether the wire to the solenoid valve is not connected wrongly, or the connector is not loose.

NO

Repair the fault.

YES

Run the cooling or heating operation of the refrigerant system of the solenoid valve in trouble.

Check the operation sound of the solenoid valve to be magnetized at the time of turning on the remote controller.

NO

Makes a tick sound.

YES

Remove the solenoid valve coil, and check that there is a suction force.

NO

There is a suction force.

YES

Stop the unit with the remote controller.

Measure the temperature at the upstream and downstream pipes of the solenoid valve, and compare them. There is no temperature difference. : OK There is a temperature difference. : NO

Remove the solenoid valve connector, and check that the electricity runs through the solenoid valve coil.

Check the relay output with the self-diagnosis LED, and check whether the operation corresponds with the operation mode.

NO NO

The electricity runs.

OK

YES

YES

Turn on the remote controller with the connector of the solenoid valve in trouble disconnected, and check that the control board outputs 200V.

Replace the control board.

YES

Measure the temperature at the upstream and downstream pipes of the solenoid valve. When the solenoid valve is ON : There is no temperature difference. When the solenoid valve is OFF : There is a temperature difference.

YES

NO

OK

Replace the control board. Replace the solenoid valve coil.

YES

Faulty judgment of solenoid valve Solenoid valve failure

Show 4 more labels / short text on this page
Stop the operation · No fault · Corresponds · Output 200V
Page 300 of the Mitsubishi Electronics P96 user manual — SVM1 ON
Page 300 · click to enlarge
Page 300

Check whether the BC board output signal corresponds with the solenoid valve operation correspond.

1. SVA, SVB, SVC SVA, SVB, and SVC turn on or off according to the indoor unit operation mode.

Cooling Heating Stopped Defrost Fan

SVA ON OFF

SVB OFF ON OFF OFF OFF

SVC ON OFF OFF OFF ON

SVM1 and SVM2 SVM1 and SVM2 turn on or off according to the indoor unit operation mode.

mode Cooling only Cooling main Heating only Heating main Defrost Stopped

SVM1 ON

OFF OFF ON OFF

ON

SVM2 OFF OFF

OFF OFF

ON

ON

2. SVA, SVB, SVC Measure the temperature at the upstream and downstream pipes and of SVA. Measure the temperature at the upstream and downstream pipes and of SVA.
Mitsubishi Electronics P96 — SVM1 ON diagram (page 300)
Fig. 80
Show 9 more labels / short text on this page
Mode · Port · Operation · Pressure dif- ferential con- · trol OFF or · Pressure dif- ferential con- · Pressure dif- ferential con- · trol OFF or · trol OFF or
Page 301 of the Mitsubishi Electronics P96 user manual — 4. BC controller transformer
Page 301 · click to enlarge
Page 301

4. BC controller transformer

CNTR CN03 BC controller control board

Red White Red Red

CNTR(1)-(3) about 58 ohm.

Open-phase or shorting CN03(1)-(3) about 16 ohm.

* Before measuring the resistance, pull out the connector.

Normal Abnormal

Page 302 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 302 · click to enlarge
Page 302

[THMU-A]

-7Inverter (THMU-A)

ŒReplace only the compressor if only the compressor is found to be defective. (Overcurrent will flow through the inverter if the

compressor is damaged, however, the power supply is automatically cut when overcurrent is detected, protecting the inverter from damage.) ŒReplace only the fan motor if only the fan motor is found to be defective. (Overcurrent will flow through the inverter if the fan

motor is damaged, however, the power supply is automatically cut when overcurrrent is detected, protecting the inverter from damage.) ŒReplace the defective components if the inverter is found to be defective. ŒIf both the compressor and the inverter are found to be defective, replace the defective component(s) of both devices.

(1) Inverter-related problems: Troubleshooting and remedies 1) The INV board has a large-capacity electrolytic capacitor, in which residual voltage remains even after the main power is turned off, posing a risk of electric shock. Before inspecting the inverter-related items, turn off the main power, wait for 5 to 10 minutes, and confirm that the voltage at both ends of the electrolytic capacitor has dropped to a sufficiently low level. 2) The IPM on the inverter becomes damaged if there are loose screws are connectors. If a problem occurs after replacing some of the parts, mixed up wiring is often the cause of the problem. Check for proper connection of the wiring, screws, connectors, and Faston terminals. 3) To avoid damage to the circuit board, do not connect or disconnect the inverter-related connectors with the main power turned on. 4) Current sensors become damaged if electricity is passed through without them being connected to the circuit board. Connect the current sensor to the appropriate connectors on the circuit board before operating the inverter. 5) Faston terminals have a locking function. Make sure the terminals are securely locked in place after insertion.

Press the tab on the terminals to remove them.

6. When the IPM, diode stack, or IGBT is replaced, apply a thin layer of heat radiation grease that is supplied evenly to these parts. Wipe off any grease that may get on the wiring terminal to avoid terminal contact failure. 7) Faulty wiring to the compressor damages the compressor. Connect the wiring in the correct phase sequence.
Page 303 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 303 · click to enlarge
Page 303

[THMU-A]

Error display/failure condition Measure/inspection item

[1] Inverter related errors 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Check the details of the inverter error in the error log at 10.[1] Table of LED codes. Take appropriate measures to the error code and the error details in ac- cordance with 9. [2] Self-diagnosis on the basis of Error Display on Re- mote Controller and Remedy for Error.

[2] Main power breaker trip Check the breaker capacity.

Check whether the electrical system is short-circuited or ground-

faulted.

If items cause is not or are not the causes of the problem,

see (3)-[1].

[3] Main power earth leakage breaker trip Check the earth leakage breaker capacity and the sensitivity cur-

rent.

Meg failure for electrical system other than the inverter

If the cause is not or , see (3)-[1]

[4] Only the compressor does not operate. Check the inverter frequency on the LED monitor and proceed to (2) - [4] if the compressor is in operation.

[5] The compressor vibrates violently at all times or makes an abnor- mal sound.

See (2)-[4].

[6] Only the fan motor does not operate. Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.

[7] The fan motor shakes violently at all times or makes an abnormal sound.

Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.

[8] Noise is picked up by the peripheral device Check that power supply wiring of the peripheral device does not

run close to the power supply wiring of the outdoor unit.

Check that the inverter output wiring is not in close contact with the

power supply wiring and the transmission lines.

Check that the shielded wire is used as the transmission line when

it is required, and check that the grounding work is performed prop- erly on the shielded wire.

Meg failure for electrical system other than the inverter

Attach a ferrite core to the inverter output wiring. (Contact the fac-

tory for details of the service part settings.)

Provide separate power supply to the air conditioner and other

electric appliances.

If the error occurred suddenly, a ground fault of the inverter output

can be considered. See (2)-[4].

*Contact the factory for cases other than those listed above.

[9] Sudden malfunction (as a result of external noise.) Check that the grounding work is performed properly.

Check that the shielded wire is used as the transmission line when

it is required, and check that the grounding work is performed prop- erly on the shielded wire.

Check that neither the transmission line nor the external connec-

tion wiring does not run close to another power supply system or does not run through the same conduit pipe.

* Contact the factory for cases other than those listed above.

Page 304 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 304 · click to enlarge
Page 304

[THMU-A]

(2) Inverter output related troubles

Items to be checked Phenomena Remedy

[1] Check the INV board error detection cir- cuit.

1) IPM/overcurrent breaker trip (4250 Detail code No. 101, 104, 105, 106, and 107)

Replace the INV board.

(1) Disconnect the invert- er output wire from the terminals of the INV board (SC-U, SC-V, SC-W).

2. Logic error (4220 Detail code No. 111)

Replace the INV board.

(2) Put the outdoor unit into operation.

3. ACCT sensor circuit failure (5301 Detail code No.117)

Replace the INV board.

4. IPM open (5301 Detail code No.119)

1) IPM/overcurrent breaker trip (4250 Detail code No. 101, 102, 103, 104, 105, 106, and 107)

See the section "Troubleshooting the IPM" ( Refer to - 7 - (5) ). Replace the IPM, and put the out- door unit back into operation. If the problem persists, replace the INV board.

(1) Disconnect the invert- er output wire from the output terminals (U, V, W) of the IPM.

2. Logic error (4220 Detail code No. 111)

See the section "Troubleshooting the IPM" ( Refer to - 7 - (5) ). Replace the IPM, and put the out- door unit back into operation. If the problem persists, replace the INV board. Replace the INV board, and put the outdoor unit back into opera- tion. If the problem persists, replace the DCCT.

(2) Put the outdoor unit into operation.

3. ACCT sensor circuit failure (5301 Detail code No.117)

Replace the INV board.

4. DCCT sensor circuit failure (5301 Detail code No.118)

Replace the DCCT board. Replace the DCCT, and put the outdoor unit back into operation. If the problem persists, replace the INV board.

5. IPM open (5301 Detail code No.119)

[2] Check for compressor ground fault or coil error.

Disconnect the compres- sor wiring, and check the compressor Meg, and coil resistance.

1. Compressor Meg failure Error if less than 1 Mohm. When no liquid refrigerant in the compressor

Replace the compressor Check that no liquid refrigerant in the compressor.

2. Compressor coil resistance failure Coil resistance value of 0.3 ohm (20°C [68°F]) : -P96 models Coil resistance value of 0.3 ohm (20°C [68°F]) :P120 model

Normal · Normal

Page 305 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 305 · click to enlarge
Page 305

[THMU-A]

Items to be checked Phenomena Remedy

[3] Check whether the inverter is damaged. (No load)

1) Inverter-related problems are de- tected.

Connect the short-circuit con- nector to CN6, and go to sec- tion [1].

(1) Disconnect the inverter output wire from the ter- minals of the INV board (SC-U, SC-V, SC-W).

2. Inverter voltage is not output. Replace the INV board.

(2) Disconnect the short-cir- cuit connector from CN6 on the INV board.

3. There is an voltage imbalance between the wires. Greater than 5% imbalance or 5V

Replace the INV board.

(3) Put the outdoor unit into operation. Check the inverter output voltage after the inverter output frequency has sta- bilized.

4. There is no voltage imbalance between the wires.

Normal *Reconnect the short-circuit connector to CN6 after check- ing the voltage.

1) Inverter-related problems are de- tected.

Turn off SW1-1 and go to [1]

(1) Disconnect the inverter output wire from the out- put terminals (U, V, W) of the IPM.

2. Inverter voltage is not output. Check the connection between the IPM and the CNIPM on the INV board. Replace the IPM. If the problem persists, replace the INV board.

(2) Turn on SW1-1 on the INV board.

3. There is an voltage imbalance between the wires. Greater than 5% imbalance or 5V

Replace the IPM. If the problem persists, re- place the INV board.

(3) Put the outdoor unit into operation.

4. There is no voltage imbalance between the wires.

Normal *Turn off SW1-1

[4] Check whether the inverter is damaged. (During com- pressor opera- tion)

Put the outdoor unit into oper- ation. Check the inverter output volt- age after the inverter output frequency has stabilized.

1. There is an voltage imbalance between the wires. Greater than 5% imbalance or 5V

Replace the INV board. Replace the IPM. If the problem persists, re- place the INV board. If the problem persists after replacing the above parts, go to section [2].

[5] Check the fan motor ground fault or the winding.

Remove the wire for the out- door fan motor, and check the fan motor megger and the winding resistance.

1. Fan motor megger failure Failure when the megger is 1Mohm or less.

Replace the fan motor.

2. Fan motor disconnection Standard: The winding resistance is approximately several ohm. (It varies depending on the temperature, or while the inner thermo is operating, it will be ohm)

[6] Check the FAN board failure.

(1) Check the fan output wir- ing.

Connect the connector.

ŒBoard side (CNINV) ŒFan motor side

(2) Check the connector CN- VDC connection.

Cnnector contact failure Connect the connector.

(3) Check the FAN board failure.

1. The voltage imbalance among each motor wiring during operation (The voltage imbalance is greater than the larger of the values represented by 5% or 5 V.)

Replace the FAN board.

2. The same error occurs even after the operation is restarted.

Connector contact failure

Page 306 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 306 · click to enlarge
Page 306

[THMU-A]

(3) Trouble treatment when the main power breaker is tripped.

Items to be checked Phenomena Remedy

[1] Perform Meg check between the terminals on the power terminal block TB1.

Zero to several ohm, or Meg failure Check each part in the main inverter circuit. *Refer to "Simple checking Proce- dures for individual components of main inverter circuit".

[2] Turn on the power again and check again.

1. Main power breaker trip
2. No remote control display

ŒDiode stack ŒIPM ŒRush current protection resistor ŒElectromagnetic relay ŒDC reactor

[3] Turn on the outdoor unit and check that it operates normally.

1. Operates normally without tripping the main breaker.

a) The wiring may have been short-

circuited. Search for the wire that short-circuited, and repair it. b) If item a) above is not the cause of

the problem, the compressor may have a problem.

2. Main power breaker trip A compressor ground fault can be considered. Go to (2)-[2].
Page 307 of the Mitsubishi Electronics P96 user manual — U V IPM
Page 307 · click to enlarge
Page 307

[THMU-A]

(4) Simple checking procedure for individual components of main inverter circuit

Before checking, turn the power off and remove the parts to be checked from the control box.

Part name Judgment method

Diode stack Refer to "Diode stack" ( IX [4] - 7 - (6) )

IPM (Intelligent power module)

Refer to "Intelligent power module (IPM)" ( IX [4] - 7 - (5) )

Rush current protection resis- tor R1(R2)

Measure the resistance between terminals: 22 ohm 10% Measure the resistance between the + terminal on the diode stack and terminal TB31. (*Can be mea- sured without the need to remove the noise filter board): 22 ohm 10%

Electromagnetic relay 72C This electromagnetic relay is rated at 200VAC and is driven by a coil. The resistance between the coils in row A cannot be measured with a tester.Check only for shorting.

Row A Not to be short-circuited

E A2 44 34 24 14

A

B

D

With the test button turned off : With the test button turned on : 0

Row B to Row E

43 33 23 13 A1

Between No. 1 pin and No. 3 pin of the CN03 on the noise filter board

Not to be short-circuited

+ terminal on the diode stack and terminal TB31 on the noise filter

With the test button turned off :

With the test button turned on : 0

DC reactor DCL Measure the resistance between terminals: 1ohm or lower (almost 0 ohm) Measure the resistance between terminals and the chassis:

Disconnect the CNCT2 connector and measure the resistance between terminals: 280 ohm 30 ohm 1 - 2 PIN (U-phase),3 - 4 PIN (W-phase)

U V IPM

W

W ACCT-W

U

ACCT-U

*Check the ACCT connection phase and the direction of the connection

Show 17 more labels / short text on this page
<P72 model> · Installation direction · Check point · Checking criteria · Row · Row · Row · Row · Row · Coil · Contact · Test button · Check point · Checking criteria · Coil · Contact · Current sensor ACCT
Page 308 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 308 · click to enlarge
Page 308

[THMU-A]

(5) Intelligent power module (P96 and P120 models)

Measure resistances between each pair of terminals on the IPM with a tester, and use the results for troubleshooting.

1) Notes on measurement ŒCheck the polarity before measuring. (On the tester, black normally indicates plus.) ŒCheck that the resistance is not open ( ohm) or not shorted (to 0 ohm). ŒThe values are for reference, and the margin of errors is allowed. ŒThe result that is more than double or half of the result that is measured at the same measurement point is not allowed. 2) Tester restriction ŒUse the tester whose internal electrical power source is 1.5V or greater ŒUse the dry-battery-powered tester.

(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt- age is low.) ŒUse a low-range tester if possible. A more accurate resistance can be measured.

Mitsubishi Electronics P96 — [THMU-A] diagram (page 308)
Fig. 81

P - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm

External view Internal circuit diagram

Mitsubishi Electronics P96 — [THMU-A] diagram (page 308)
Fig. 82

Judgment value (reference)

Page 309 of the Mitsubishi Electronics P96 user manual — - (N) - -
Page 309 · click to enlarge
Page 309

[THMU-A]

(6) Diode stack (P96 and P120 models)

Measure resistances between each pair of terminals on the diode stack with a tester, and use the results for troubleshoot- ing.Refer to (5) " Intelligent power module (IPM) " for notes on measurement and tester selection.

Black ( + ) External view

+ (P) - (N) to (L1) to (L2) to (L3)

+ (P) - - 5 - 200 ohm

5. 200 ohm
5. 200 ohm

- (N) - -

L1 L2 L3

to (L1) 5 - 200 ohm

to (L2) 5 - 200 ohm

to (L3) 5 - 200 ohm

Show 4 more labels / short text on this page
Judgment value (reference) · Internal circuit diagram · Red (-) · +
Page 310 of the Mitsubishi Electronics P96 user manual — [YHMU-A]
Page 310 · click to enlarge
Page 310

[YHMU-A]

-7Inverter (YHMU-A)

ŒReplace only the compressor if only the compressor is found to be defective. ŒReplace only the fan motor if only the fan motor is found to be defective. ŒReplace the defective components if the inverter is found to be defective. ŒIf both the compressor and the inverter are found to be defective, replace the defective component(s) of both devices.

(1) Inverter-related problems: Troubleshooting and remedies 1) The inverter board has a large-capacity electrolytic capacitor, in which residual voltage remains even after the main power is turned off, posing a risk of electric shock. Turn off the unit, leave it turned off for at least 10 minutes, and check that the voltage across FT-P and FT-N terminals on the INV board or the terminals at both ends of the electrolytic capacitor is 20V or below before checking inside the control box. (It takes about 10 minutes to discharge electricity after the power supply is turn off.) 2) The IPM on the inverter becomes damaged if there are loose screws are connectors. If a problem occurs after replacing some of the parts, mixed up wiring is often the cause of the problem. Check for proper connection of the wiring, screws, connectors, and Faston terminals. 3) To avoid damage to the circuit board, do not connect or disconnect the inverter-related connectors with the main power turned on. 4) Faston terminals have a locking function. Make sure the terminals are securely locked in place after insertion.

Press the tab on the terminals to remove them.

5. When the IPM or IGBT is replaced, apply a thin layer of heat radiation grease that is supplied evenly to these parts. Wipe off any grease that may get on the wiring terminal to avoid terminal contact failure. 6) Faulty wiring to the compressor damages the compressor. Connect the wiring in the correct phase sequence.
Page 311 of the Mitsubishi Electronics P96 user manual — [YHMU-A]
Page 311 · click to enlarge
Page 311

[YHMU-A]

Error display/failure condition Measure/inspection item

[1] Inverter related errors 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Check the details of the inverter error in the error log at 10.[1] Table of LED codes. Take appropriate measures to the error code and the error details in ac- cordance with 9. [2] Self-diagnosis on the basis of Error Display on Re- mote Controller and Remedy for Error.

[2] Main power breaker trip Refer to "(3) Trouble treatment when the main power breaker is tripped".

[3] Main power earth leakage breaker trip Refer to "(4) Trouble treatment when the main power earth leakage breaker is tripped".

[4] Only the compressor does not operate. Check the inverter frequency on the LED monitor and proceed to (2) - [4] if the compressor is in operation.

[5] The compressor vibrates violently at all times or makes an abnor- mal sound.

See (2)-[4].

[6] Only the fan motor does not operate. Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.

[7] The fan motor shakes violently at all times or makes an abnormal sound.

Check the inverter frequency on the LED monitor and proceed to (2)- [6] if the fan motor is in operation.

[8] Noise is picked up by the peripheral device Check that power supply wiring of the peripheral device does not

run close to the power supply wiring of the outdoor unit.

Check if the inverter output wiring is not running parallel to the

power supply wiring and the transmission lines.

Check that the shielded wire is used as the transmission line when

it is required, and check that the grounding work is performed prop- erly on the shielded wire.

Meg failure for electrical system other than the inverter

Attach a ferrite core to the inverter output wiring. (Contact the fac-

tory for details of the service part settings.)

Provide separate power supply to the air conditioner and other

electric appliances.

If the error occurred suddenly, a ground fault of the inverter output

can be considered. See (2)-[4].

*Contact the factory for cases other than those listed above.

[9] Sudden malfunction (as a result of external noise.) Check that the grounding work is performed properly.

Check that the shielded wire is used as the transmission line when

it is required, and check that the grounding work is performed prop- erly on the shielded wire.

Check that neither the transmission line nor the external connec-

tion wiring does not run close to another power supply system or does not run through the same conduit pipe.

* Contact the factory for cases other than those listed above.

Page 312 of the Mitsubishi Electronics P96 user manual — [YHMU-A]
Page 312 · click to enlarge
Page 312

[YHMU-A]

(2) Inverter output related troubles

Items to be checked Phenomena Remedy

[1] Check the INV board er- ror detection circuit.

(1) Disconnect the invert- er output wire from the terminals of the inverter board (SC-U, SC-V, SC-W).

1. Overcurrent error (4250 Detail code No. 101, 104, 105, 106, and 107)

Replace the INV board.

(2) Put the outdoor unit into operation.

2. Logic error (4220 Detail code No. 111)

Replace the INV board.

3. ACCT sensor circuit failure (5301 Detail code No.117)

Replace the INV board.

4. IPM open (5301 Detail code No.119)

[2] Check for compressor ground fault or coil error.

Disconnect the compressor wiring, and check the com- pressor Meg, and coil resis- tance.

1. Compressor Meg failure Error if less than 1 Mohm.

Check that there is no liquid re- frigerant in the compressor. If there is none, replace the com- pressor.

2. Compressor coil resistance failure Coil resistance value of 1 ohm (20°C [68°F]): - P96 models Coil resistance value of 0.6 ohm (20°C [68°F]): P120 model

Replace the compressor.

Normal

Page 313 of the Mitsubishi Electronics P96 user manual — [YHMU-A]
Page 313 · click to enlarge
Page 313

[YHMU-A]

Items to be checked Phenomena Remedy

[3] Check whether the inverter is damaged. (No load)

(1) Disconnect the inverter output wire from the ter- minals of the inverter board (SC-U, SC-V, SC- W).

1. Inverter-related problems are detected.

Connect the short-circuit con- nector to CN6, and go to sec- tion [1].

(2) Disconnect the short-cir- cuit connector from CN6 on the inverter board.

2. Inverter voltage is not output at the terminals (SC-U, SC-V, and SC-W)

Replace the INV board.

(3) Put the outdoor unit into operation. Check the inverter output voltage after the inverter output frequency has sta- bilized.

3. There is an voltage imbalance between the wires. Greater than 5% imbalance or 5V

Replace the INV board.

4. There is no voltage imbalance between the wires.

Normal *Reconnect the short-circuit connector to CN6 after check- ing the voltage.

[4] Check whether the inverter is damaged. (During com- pressor opera- tion)

Put the outdoor unit into oper- ation. Check the inverter output volt- age after the inverter output frequency has stabilized.

1. There is an voltage imbalance between the wires. Greater than 5% imbalance or 5V

Replace the INV board.

[5] Check the fan motor ground fault or the winding.

Remove the wire for the out- door fan motor, and check the fan motor megger and the winding resistance.

1. Fan motor megger failure Failure when the megger is 1Mohm or less.

Replace the fan motor.

2. Fan motor disconnection Standard: The winding resistance is approximately several ohm. (It varies depending on the temperature, or while the inner thermo is operating, it will be ohm)

[6] Check the FAN board failure.

(1) Check the fan output wir- ing.

Connect the connector.

ŒBoard side (CNINV) ŒFan motor side

(2) Check the connector CN- VDC connection.

Cnnector contact failure Connect the connector.

(3) Check the FAN board failure.

1. The voltage imbalance among each motor wiring during operation (The voltage imbalance is greater than the larger of the values represented by 5% or 5 V.)

Replace the FAN board.

2. The same error occurs even after the operation is restarted.

Connector contact failure

Page 314 of the Mitsubishi Electronics P96 user manual — (4) Trouble treatment when the main power earth leakage breaker is tripped
Page 314 · click to enlarge
Page 314

[YHMU-A]

(3) Trouble treatment when the main power breaker is tripped

Items to be checked Phenomena Remedy

[1] Check the breaker capacity. Use of a non-specified break- er

Replace it with a specified breaker.

[2] Perform Meg check between the terminals on the power terminal block TB1.

Zero to several ohm, or Meg failure

Check each part and wiring. *Refer to (5) "Simple checking procedure for individual components of main inverter circuit".

[3] Turn on the power again and check again.

1. Main power breaker trip

ŒIGBT module ŒRush current protection resistor ŒElectromagnetic relay ŒDC reactor

2. No remote control display

[4] Turn on the outdoor unit and check that it operates normally.

1. Operates normally without tripping the main breaker.

a) The wiring may have been short-circuit-

ed. Search for the wire that short-circuit- ed, and repair it. b) If item a) above is not the cause of the

problem, refer to (2)-[1]-[6]. 2) Main power breaker trip

(4) Trouble treatment when the main power earth leakage breaker is tripped

Items to be checked Phenomena Remedy

[1] Check the earth leakage breaker capacity and the sensitivity cur- rent.

Use of a non-specified earth leakage breaker

Replace with a regulation earth leakage breaker.

[2] Check the resistance at the power supply terminal block (TB1) with a megger.

Failure resistance value Check each part and wiring. *Refer to (5) "Simple checking Procedures for individual components of main inverter circuit".

ŒIGBT module ŒRush current protection resistor ŒElectromagnetic relay ŒDC reactor

[3] Disconnect the compressor wir- ings and check the resistance of the compressor with a megger.

Failure compressor if the insu- lating resistance value is not in specified range. Failure when the insulating re- sistance value is 1 Mohm or less.

Check that there is no liquid refrigerant in the compressor. If there is none, replace the compressor.

[4] Disconnect the fan motor wirings and check the resistance of the fan motor with a megger.

Failure fan motor if the insulat- ing resistance value is not in specified range. Failure when the insulating re- sistance value is 1 Mohm or less.

Replace the fan motor.

The insulation resistance could go down to close to 1Mohm after installation or when the power is kept off for an extended period of time because of the accumulation of refrigerant in the compressor. If the earth leakage breaker is triggered, please use the following procedure to take care of this. ŒDisconnect the wires from the compressor's terminal block. ŒIf the resistance is less than 1 Mohm, switch on the power for the outdoor unit with the wires still disconnected. ŒLeave the power on for at least 12 hours. ŒCheck that the resistance has recovered to 1 Mohm or greater. Earth leakage current measurement method

ŒFor easy on-site measurement of the earth leakage current, enable the filter with a measurement instrument that has filter

functions as below, clamp all the power supply wires, and measure. Recommended measurement instrument: CLAMP ON LEAK HiTESTER 3283 made by HIOKI E.E. CORPORATION ŒWhen measuring one device alone, measure near the device's power supply terminal block.

Page 315 of the Mitsubishi Electronics P96 user manual — (6) Troubleshooting for IGBT Module
Page 315 · click to enlarge
Page 315

[YHMU-A]

(5) Simple checking procedure for individual components of main inverter circuit

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.

Part name Judgment method

IGBT module See "Troubleshooting for IGBT Module ". ( IX [4] - 7 - (6) )

Rush current pro- tection resistor R1, R5

Measure the resistance between terminals R1 and R5: 22 ohm 10%

Electromagnetic relay 72C This electromagnetic relay is rated at DC12V and is driven by a coil. Check the resistance between terminals

Check point Checking criteria( ) W

(Center value 75 ohm) Coil

Between Terminals 5 and 6

Not to be short-circuited

Between Terminals 1 and 2 Between Terminals 3 and 4

DC reactor DCL Measure the resistance between terminals: 1ohm or lower (almost 0 ohm) Measure the resistance between terminals and the chassis:

(6) Troubleshooting for IGBT Module

Measure the resistances between each pair of terminals on the IGBT with a tester, and use the results for troubleshooting. The terminals on the inverter board are used for the measurement.

1) Notes on measurement ŒCheck the polarity before measuring. (On the tester, black normally indicates plus.) ŒCheck that the resistance is not open ( ohm) or not shorted (to 0 ohm). ŒThe values are for reference, and the margin of errors is allowed. ŒThe result that is more than double or half of the result that is measured at the same measurement point is not allowed. ŒDisconnect all the wiring connected the INV board, and make the measurement.

2. Tester restriction Œ Use the tester whose internal electrical power source is 1.5V or greater Œ Use the dry-battery-powered tester.

(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt- age is low.) ŒUse a low-range tester if possible. A more accurate resistance can be measured.

Upper · Installation direction · Contact

Page 316 of the Mitsubishi Electronics P96 user manual — SC-P1 SC-P2
Page 316 · click to enlarge
Page 316

[YHMU-A]

Black ( + )

SC-P1 FT-N SC-L1 SC-L2 SC-L3

SC-P1 - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm

FT-N - -

SC-L1 5 - 200 ohm - - -

SC-L2 5 - 200 ohm - - -

SC-L3 5 - 200 ohm - - -

Black ( + )

SC-P2 FT-N SC-U SC-V SC-W

SC-P2 - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm

FT-N - -

SC-U 5 - 200 ohm - - -

SC-V 5 - 200 ohm - - -

SC-W 5 - 200 ohm - - -

INV board external diagram

SC-P1 SC-P2

FT-N

SC-V

SC-L1 SC-L2

SC-W

SC-L3

SC-U

Judgment value (reference) · Red (-) · Red (-)

Page 317 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 317 · click to enlarge
Page 317

[THMU-A]

-8Control Circuit (THMU-A)

(1) Control power source function block 1) PURY-P72THMU-A

Mitsubishi Electronics P96 — [THMU-A] diagram (page 317)
Fig. 83

Power source system (AC 208 / 230 V) Control system (DC 5 ~ 30 V)

AC 208 / 230 V Terminal block for power source

Detection circuit for the power supply to the transmission line

CN40 Terminal block for transmission line for centralized control (DC 24 ~ 30 V)

Terminal block for transmission line connection DC 17 ~ 30 V

* MA remote controllers and M-NET remote controllers cannot be used together.

(Both the M-NET and MA remote controller can be connected to a system with a system controller.)

Page 318 of the Mitsubishi Electronics P96 user manual — [THMU-A]
Page 318 · click to enlarge
Page 318

[THMU-A]

2) PURY-P96, P120THMU-A

Mitsubishi Electronics P96 — [THMU-A] diagram (page 318)
Fig. 84

Power source system (AC 208 / 230 V) Control system (DC 5 ~ 30 V)

AC 208 / 230 V Terminal block for power source

Detection circuit for the power supply to the transmission line

Terminal block for transmission line for centralized control (DC 24 ~ 30 V)

Terminal block for transmission line connection DC 17 ~ 30 V

* MA remote controllers and M-NET remote controllers cannot be used together.

(Both the M-NET and MA remote controller can be connected to a system with a system controller.)

Page 319 of the Mitsubishi Electronics P96 user manual — NO
Page 319 · click to enlarge
Page 319

[THMU-A]

(2) Troubleshooting transmission power circuit of outdoor unit 1) PURY-P72THMU-A

Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit.

DC 24 ~ 30 V

YES

Check whether the transmission line is disconnected, check for contact failure, and repair the problem.

NO

Check the voltage at TB3 after removing transmission line from TB3.

DC 24 ~ 30 V

YES

Check if the indoor/outdoor transmission line is not short-circuited, and repair the problem.

NO

Check whether the male connector is connected to the female power supply connector (CN40).

NO

YES

Check voltage of terminal block for centralized control (TB7).

YES

Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.

DC24 ~ 30V

NO NO

YES

Is there a wiring error or a connector

Fix the wiring and connector disconnection.

Check voltage of TB7 by removing transmission line from TB7.

DC24 ~ 30V

YES

Check for shorted transmission line for centralized control.

NO

Check the voltage between No.1 and No.2 pins of the CNS2 on the control board.

YES

DC24 ~ 30V

Replace the control board.

NO

Check the voltage between No.1 and No.2 pins of the CN102 on the power supply board for the transmission line.

YES

Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.

DC24 ~ 30V

NO

Is there a connector

YES

disconnection? Fix the connector disconnection.

NO

Check the voltage between No.5 and No.2 pins of the CNIT on the control board.

Check the voltage between No.1 and No.3 pins of the CNDC on the INV board.

YES

NO

Is the voltage measurement between

Replace the M-NET board

4.5 and 5.2 VDC?

YES

DC265 ~ 357V

Replace the M-NET board

NO

Check the voltage between SC-P1 and TB-N on the INV board.

DC265 ~ 357V

YES

Check the inrush current resistance (R1).

NO

Replace the inrush current limiting resistor.

Check the voltages among SC-R, SC-S, and SC-T on the INV board.

NO

YES

Replace the INV board.

YES

AC188 ~ 253V

Replace the INV board.

NO

Check the voltages among TB21, TB22, and TB23 on the noise filter.

YES

Check the wiring between the noise filter and the INV board as well as screw tightness, and fix any problems found.

AC188 ~ 253V

NO

Check the voltage at the power supply terminal block TB1.

YES

AC188 ~ 253V

Replace the noise filter.

NO

Check and fix any power supply wiring and main power supply problems found.

Turn on the power again.

Connected · disconnection? · 22 10%

Page 320 of the Mitsubishi Electronics P96 user manual — NO
Page 320 · click to enlarge
Page 320

[THMU-A]

2) PURY-P96, P120THMU-A

Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit.

YES

DC 24 ~ 30 V

Check whether the transmission line is disconnected, check for contact failure, and repair the problem.

NO

Check the voltage at TB3 after removing transmission line from TB3.

YES

DC 24 ~ 30 V

Check if the indoor/outdoor transmission line is not short-circuited, and repair the problem.

NO

Check whether the male connector is connected to the female power supply connector (CN40).

NO

YES

Check voltage of terminal block for centralized control (TB7).

YES

Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.

DC24 ~ 30V

NO

YES Is there a wiring error or a connector

NO

Fix the wiring and connector disconnection.

Check voltage of TB7 by removing transmission line from TB7.

YES

Check for shorted transmission line for centralized control.

DC24 ~ 30V

NO

Check the voltage between No.1 and No.2 pins of the CNS2 on the control board.

YES

DC24 ~ 30V

Replace the control board.

NO

Check the voltage between No.1 and No.2 pins of the CN102 on the power supply board for the transmission line.

Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.

YES

DC24 ~ 30V

NO

Is there a connector

YES

disconnection? Fix the connector disconnection.

NO

Check the voltage between No.5 and No.2 pins of the CNIT on the control board.

Check the voltage between No.1 and No.3 pins of the CNDC3 on the INV board.

NO

YES

Is the voltage measurement between

Replace the M-NET board

4.5 and 5.2 VDC?

YES

DC265 ~ 357V

Replace the M-NET board

NO

Check the voltage between TB31 and TB42 on the noise filter.

DC265 ~ 357V

YES

Replace the INV board.

NO

Check the voltage between the + and – terminals on the diode stack.

DC265 ~ 357V

YES

Replace the noise filter.

NO

Check the voltages among TB21, TB22, and TB23 on the noise filter.

YES

AC188 ~ 253V

Replace the diode stack.

NO

Check the voltage at the power supply terminal block TB1.

AC188 ~ 253V

YES

Replace the noise filter.

NO

Check and fix any power supply wiring and main power supply problems found.

Turn on the power again.

Connected · disconnection?

Page 321 of the Mitsubishi Electronics P96 user manual — A, B
Page 321 · click to enlarge
Page 321

[YHMU-A]

- 8 - Control Circuit (YHMU-A)

(1) Control power source function block 1) PURY-P72, P96, P120YHMU-A

Power source system (AC 230 / 460 V) Control system (DC 5 ~ 30 V)

TB1

72C DCL

AC 460V Terminal block for power source

5 V Power supply

Solenoid valve 4-way valve CH11

63H1

Relay, LEV Drive circuit

18 V Power supply

72C, LEV

5 V Power supply

5 V Power supply

DC / DC converter

Detection circuit for the power supply to the transmission line

TB7

Terminal block for transmission line for centralized control (DC 24 ~ 30 V)

DC / DC converter

CN40

TB3

30 V Power supply

Indoor/outdoor transmission block (DC 24 ~ 30 V)

M-NET transmission line (Non-polar 2 wire)

TB2

AC 220 / 240 V AC Power source

Terminal block for power source

TB15

Terminal block for MA remote controller

To next unit (Indoor unit)

TB5

Terminal block for transmission line connection DC 17 ~ 30 V

MA remote controller wiring

A, B

DC 17 ~ 30 V

A, B

DC 9 ~ 12 V

* MA remote controllers and M-NET remote controllers cannot be used together.

(Both the M-NET and MA remote controller can be connected to a system with a system controller.)

Show 36 more labels / short text on this page
Noise filter · INV board · Noise filter · Rectifier Compressor · Smoothing capacitor Inverter · Fuse · Inverter drive circuit · 17V Power supply · Surge protection · Rectifier · Fuse · Microcomputer · Trans Box · Fan board · Control board · Inverter · Heat exchanger · fan · Fuse · Inverter reset circuit · Fuse · Oudoor unit · Outdoor unit · Inverter drive circuit · Microcomputer · Microcomputer · 12V Power supply · M-NET board · Relay drive circuit · Relay · Indoor unit · (Non-polar 2 wire) · M-NET remote · controller · MA remote · controller
Page 322 of the Mitsubishi Electronics P96 user manual — NO
Page 322 · click to enlarge
Page 322

[YHMU-A]

(2) Troubleshooting transmission power circuit of outdoor unit 1) PURY-P72, P96, P120YHMU-A

Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit.

YES

DC 24 ~ 30 V

Check whether the transmission line is disconnected, check for contact failure, and repair the problem.

NO

Check the voltage at TB3 after removing transmission line from TB3.

YES

DC 24 ~ 30 V

Check if the indoor/outdoor transmission line is not short-circuited, and repair the problem.

NO

Check whether the male connector is connected to the female power supply connector (CN40).

NO

YES

Check voltage of terminal block for centralized control (TB7).

DC 24 ~ 30 V

YES

Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.

NO

YES

Check voltage of TB7 by removing transmission line from TB7.

NO

Is there a wiring error or a connector

Fix the wiring and connector disconnection.

YES

Check for shorted transmission line or power feed collision for centralized control.

DC 24 ~ 30 V

NO

Check the voltage between No.1 and No.2 pins of the CNS2 on the control board.

YES

DC 24 ~ 30 V

Replace the control board.

NO

Check the voltage between No.1 and No.2 pins of the CN102 on the power supply board for the transmission line.

YES

Check the wiring between the control board and power supply board for the transmission line (CN102 and CNIT), and check for proper connection of connectors.

DC 24 ~ 30 V

NO

YES

Is there a connector

Fix the connector disconnection.

NO

Check the voltage between No.5 and No.2 pins of the CNIT on the control board.

NO

Is the voltage measurement between

YES

Check the voltage between No.1 and No.3 pins of the noise filter CN4.

Replace the M-NET board

4.5 and 5.2 VDC?

YES

DC270 ~ 356V

Replace the control board.

NO

Check the voltage between No.1 and No.3 pins of the noise filter CN5.

YES

DC270 ~ 356V

Replace the M-NET board

NO

Check the noise filter fuse F4 .

YES

Fuse F4 on the noise filter board is blown.

Disconnect the noise filters CN4 and CN5, and then replace fuse F4 on the noise filter board, then turn the power on.

NO

YES

Fuse F4 on the noise filter board is blown.

Replace the noise filter.

NO

Connect the noise filter CN4, and then turn the power on.

YES

Fuse F4 on the noise filter board is blown.

Replace the control board.

NO

Check fuse F5.

Replace the M-NET board

YES

Fuse F5 is blown.

Pull out CN4 and CN5 on the noise filter, replace fuse F5, and turn on the power.

NO

YES

Check the voltages among TB22 and TB23 on the noise filter

Fuse F5 is blown.

Replace the noise filter.

NO

Connect the noise filter CN4, and then turn the power on.

YES

Fuse F5 is blown.

Replace the control board.

NO

Replace the M-NET board

YES

AC41 4 ~ 506V

Replace the noise filter.

NO

Check the voltage between L2 and L3 at the power supply terminal block TB1.

YES

AC414 ~ 506V

Replace the noise filter.

NO

Check and fix any power supply wiring and main power supply problems found.

Turn on the power again.

Connected · disconnection? · disconnection?

Page 323 of the Mitsubishi Electronics P96 user manual — [5] Refrigerant Leak
Page 323 · click to enlarge
Page 323

[5] Refrigerant Leak

1. Leak spot: In the case of extension pipe for indoor unit (Cooling season) 1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side. 2) Stop all the indoor units, and close the high-pressure side refrigerant service valve (BV2) on the outdoor unit while the com- pressor is being stopped. 3) Stop all the indoor units; turn on SW2-4 on the outdoor unit control board while the compressor is being stopped.(Pump down mode will start, and all the indoor units will run in cooling test run mode.) 4) In the pump down mode (SW2-4 is ON), all the indoor units will automatically stop when the low pressure (63LS) reaches 0.383MPa [55psi] or less or 15 minutes have passed after the pump mode started. Stop all the indoor units and compressors when the pressure indicated by the pressure gauge, which is on the check joint (CJ2) for low-pressure service, reaches 0.383MPa [55psi] or 20 minutes pass after the pump down operation is started. 5) Close the service ball valve (BV1) on the low-pressure pipe on the outdoor unit. 6) Collect the refrigerant that remains in the extended pipe for the indoor unit. Do not discharge refrigerant into the atmosphere when it is collected. 7) Repair the leak. 8) After repairing the leak, vacuum*1 the extension pipe and the indoor unit. 9) To adjust refrigerant amount, open the ball valves (BV1 and BV2) inside the outdoor unit and turn off SW2-4.

2. Leak spot: In the case of outdoor unit (Cooling season) (1) Run all the indoor units in the cooling test run mode. 1) To run the indoor unit in test run mode, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Change the setting of the remote controller for all the indoor units to the cooling mode. 3) Check that all the indoor units are performing a cooling operation.

(2) Check the SC16 value.

(This valve can be displayed on the LED by setting the self-diagnosis switch (SW1) on the outdoor unit control board.) 1) When SC16 is 10°C [18°F] or above: Go to the next item (3). 2) When the SC16 value is below 10°C [18°F] : After the compressor has stopped, extract the refrigerant in the system, repair the leak, evacuate the air from the system *1, and charge the system with refrigerant. (If the leak is in the outdoor unit, follow the same procedure as listed under "heating season.")

1 2 3 4 5 6 7 8 10 9 ON

(3) Stop all the indoor units, and stop the compressor. 1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Check that all the indoor units are being stopped.

(4) Close the ball valves (BV1 and BV2). (5) Collect the refrigerant that remains inside the outdoor unit.Do not discharge refrigerant into air into the atmosphere

when it is collected. (6) Repair the leak. (7) After repairing the leak, replace the dryer with the new one, and perform evacuation *1 inside the outdoor unit. (8) To adjust refrigerant amount, open the ball valves (BV1 and BV2) inside the outdoor unit.

*1. Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

SC16 self-diagnosis switch

Page 324 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 324 · click to enlarge
Page 324
3. Leak spot: In the case of extension pipe for indoor unit (Heating season) (1) Run all the indoor units in heating test run mode. 1) To run the indoor unit in test run mode, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Change the setting of the remote controller for all the indoor units to the heating mode. 3) Check that all the indoor units are performing a heating operation.

(2) Stop all the indoor units, and stop the compressor. 1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Check that all the indoor units are stopped.

(3) Close the ball valves (BV1 and BV2). (4) Collect the refrigerant that remains inside the indoor unit. Do not discharge refrigerant into air into the atmosphere

when it is collected. (5) Repair the leak. (6) After repairing the leak, perform evacuation of the extension pipe*1 for the indoor unit, and open the ball valves (BV1

and BV2) to adjust refrigerant.

4. Leak spot: In the case of outdoor unit (Heating season) 1) Collect the refrigerant in the entire system (outdoor unit, extended pipe and indoor unit).Do not discharge refrigerant into the atmosphere when it is collected. 2) Repair the leak. 3) Repair the leak, and evacuate the air from the entire system *1 . Then, calculate the proper amount of refrigerant to be added (outdoor unit + extension pipe + indoor unit), and charge the system with that amount. Refer to Chapter VIII [4] 3. for the proper amount of refrigerant charge.

*1. Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

Page 325 of the Mitsubishi Electronics P96 user manual — 1. Compressor Replacement Instructions
Page 325 · click to enlarge
Page 325

[6] Compressor Replacement Instructions

1. Compressor Replacement Instructions

[Compressor replacement procedures]

Follow the procedures below (Steps 1 through 6) to remove the compressor components and replace the compressor. Reassemble them in the reverse order after replacing the compressor.

Mitsubishi Electronics P96 — 1. Compressor Replacement Instructions diagram (page 325)
Fig. 85 · 1. Compressor Replacement Instructions
Mitsubishi Electronics P96 — 1. Compressor Replacement Instructions diagram (page 325)
Fig. 86 · 1. Compressor Replacement Instructions

Service panel Control box

1. Remove both the top and bottom service panels (front panels).
2. Remove the control box and the compressor cover (front).
Mitsubishi Electronics P96 — 1. Compressor Replacement Instructions diagram (page 325)
Fig. 87 · 1. Compressor Replacement Instructions
3. Remove the wires that are secured to the frame, and remove the frame.

*1 Remove the transformer box from the P72, P96, and P120YHMU-A models.

Show 5 more labels / short text on this page
Compressor cover (front) · *1 · Transformer box · Frame · Electric wiring
Page 326 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 326 · click to enlarge
Page 326
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 326)
Fig. 88
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 326)
Fig. 89

Compressor covers (right and left) (The inside of the compressor cover is lined with sound insulation material.)

4. Remove the compressor cover (top). 5. Remove the compressor wires, compressor covers (right and left), and crankcase heater.
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 326)
Fig. 90

Protection for the sealing material

Protection for the compressor cover

6. Place protective materials on the insulation lining of the compressor cover and on the sealing material on the compressor suction pipe to protect them from the torch flame, debraze the pipe, and replace the compressor.

Compressor cover (top) · Crankcase heater · Suction piping

Page 327 of the Mitsubishi Electronics P96 user manual — inside. (*1)
Page 327 · click to enlarge
Page 327
1. Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement instruc-

tions

* Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b,

SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures.

1. Applicable models

  • PURY-P72THMU-A (-BS), PURY-P72YHMU-A (-BS)

2. Parts to be serviced, Set-content

Following instructions are applicable to 1-3 service parts on the table below.

Things required for replacing Item

NO. Parts to be serviced

Numbers

  • Solenoid valve block service parts set [Set-content]
  • Replacement instructions
  • Solenoid valve block ASSY
  • Connecting pipe ( φ 9.52 [3/8"])

1 Solenoid valve block ASSY (SV4a, SV4b, SV4d)

2 Check valve (CV4a)

  • Service parts replacement instructions set [Set-content]
  • Replacement instructions
  • Connecting pipe ( φ 9.52 [3/8"])

3 Check valve (CV6a, CV8a, CV9a, CV10a)

3. Procedures

* Precautions for starting replacement

  • Check that the main power supply is OFF.
  • Check that no refrigerant is in the outdoor unit.

Remove each part according to the 1)-3) procedures on the next page before replacing service parts. Mount the removed parts back in place in a reversed procedures of 1)-3) on the next page after replacing service parts.

(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement procedures

  • To remove Solenoid valve block ASSY ① Remove the solenoid valve block coil cover, solenoid valve coil, and peripheral cables. ② Remove the screw (M5) that fixes the solenoid valve block and the supporting plate for solenoid valve block. ③ Cut the pipe at the position indicated on the next page with a pipe cutter. Remove the pipe from the brazed A part. ④ Debraze B-G parts (total 6 places). ⑤ Do not damage heat exchanger fins and peripheral piping devices when removing the Solenoid valve block ASSY.
  • To install Solenoid valve block ASSY ⑥ Mount the Solenoid valve block ASSY replacement to the unit with care not to damage heat exchanger fins and

peripheral piping devices. Fix the Solenoid valve block ASSY and the supporting plate with the fixing screw (M5). ⑦ Braze B-G part (total 6 places), and connect the solenoid valve block and the heat exchanger header with the connect-

ing pipe (φ9.52 [3/8"]) that comes with the service parts set. ⑧ Mount the solenoid valve block coil cover, solenoid valve coil, and peripheral cables back in place.

* Precautions for replacing Solenoid valve block ASSY

  • Be sure to perform no-oxidation brazing when brazing.
  • After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air

inside. (*1)

  • Perform brazing with care of the flame direction so that it does not burn cables and plates etc. in the unit.
  • Remove the brazing part protecting heat exchanger fins from burning, and replace the service parts.

*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

Page 328 of the Mitsubishi Electronics P96 user manual — Brazing (Solenoid valve block side)
Page 328 · click to enlarge
Page 328
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 328)
Fig. 91
2. Remove the control box.
1. Remove the upper and lower service panels (Panel FU and FB).
3. Remove the cable that is fixed to the Frame ASSY MU (upper) and MB (lower), and remove the Frame ASSY MU and MB.

④⑦ Brazing or debrazing pipes D (φ28.6 [1-1/8"]), E (φ9.52 [3/8"]), F (φ9.52 [3/8"])

Solenoid valve block ASSY

④⑦B (φ15.88 [5/8"])

④⑦C (φ19.05 [3/8"])

Solenoid valve coil (SV4a,SV4b,SV4d)

Mitsubishi Electronics P96 — Solenoid valve block ASSY diagram (page 328)
Fig. 92 · Solenoid valve block ASSY

D C

Mitsubishi Electronics P96 — D C diagram (page 328)
Fig. 93
Mitsubishi Electronics P96 — D C diagram (page 328)
Fig. 94

B E

F G

Removed Solenoid valve block ASSY

G (φ15.88 [5/8"])

* This figure does not show heat exchanger.

②⑥ Removing or installing

solenoid valve block Solenoid valve block

Cutting pipes positions Cut the pipe at 40mm ahead from the Bending R end with a pipe cutter.

40 A (φ12.7

[1/2"]) Bending R end

Supporting plate for solenoid valve block

After cutting pipe, remove the pipe from the brazed A.

⑦ Brazing connecting pipe (φ9.52 [3/8"])

Mitsubishi Electronics P96 — B E diagram (page 328)
Fig. 95

Brazing (Solenoid valve block side)

Brazing (heat exchanger header side)

Service patrs set supplied connecting pipe ( φ 9.52 [3/8"])

Heat exchanger ③⑦A (φ12.7 [1/2"])

* Refer to the next page for Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures.

Show 4 more labels / short text on this page
⑤ Removing · ①Coil cover, · ③ Cutting pipes · Screw (M5)
Page 329 of the Mitsubishi Electronics P96 user manual — inside. (*1)
Page 329 · click to enlarge
Page 329

(2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures

① Remove the Solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement

procedures" on the front page.

② Debraze H-M parts (total 6 places), and remove the Check valve ASSY.

③ Replace the Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) to be serviced while it is removed from the unit.

Braze the pipes as they were according to the angle of the pipes on the next page (Figure as viewed from point Q).

④ Mount the solenoid valve block ASSY, coil cover, and peripheral cables back in place according to "(1) Solenoid valve

block ASSY (SV4a, SV4b, SV4d) replacement procedures" on the front page.

Part A (Refer to the next page.)

Mitsubishi Electronics P96 — Part A (Refer to the next page.) diagram (page 329)
Fig. 96 · Part A (Refer to the next page.)

②③ H (φ19.05 [3/4"])

②③ I (φ15.88 [5/8"])

Heat exchanger

②③ J (φ12.7 [1/2"]) ②③ K (φ6.35 [1/4"])

* After removing Solenoid valve block ASSY

* Precautions for replacing Check valve

  • Be sure to perform no-oxidation brazing when brazing.
  • Place a wet towel on the check valve when heating pipes to keep the temperature of the valve from exceed-

ing 120°C [248°F].

  • After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air

inside. (*1)

  • Perform carefully with the flame direction so that it does not burn cables and plates etc. in the unit.
  • Remove the brazing part protecting heat exchanger fins not to be burn, and replace the service parts.

*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

Page 330 of the Mitsubishi Electronics P96 user manual — Q Check valve ASSY
Page 330 · click to enlarge
Page 330

Detailed View of Part A

②③ Brazing or debrazing pipes

③ Check valve replacement

L (φ15.88 [5/8"])

M (φ28.6 [1-1/8"])

M

Mitsubishi Electronics P96 — M diagram (page 330)
Fig. 97

CV4a 2 (φ15.88 [5/8"])

When replacing CV4a:

Mitsubishi Electronics P96 — When replacing CV4a: diagram (page 330)
Fig. 98 · When replacing CV4a:

H 1 (φ28.6 [1-1/8"])

Remove the brazing 1.

7 (φ15.88 [5/8"])

When replacing CV6a:

Remove the brazing 2.

3 (φ15.88

5 (φ15.88 [5/8"])

When replacing CV8a:

Remove the brazing 3 and 4.

CV9a 8 (φ15.88 [5/8"])

When replacing CV9a:

Remove the brazing 5 and 6.

6 (φ15.88 [5/8"])

4 (φ15.88 [5/8"])

When replacing CV10a:

J

Remove the brazing 7 and 8.

Q Check valve ASSY

* This figure does not show heat exchanger.

③ Angle of the pipes when replacing CV8a,CV9a,CV10a

(Figure as viewed from point Q)

Mitsubishi Electronics P96 — Q Check valve ASSY diagram (page 330)
Fig. 99 · Q Check valve ASSY
Show 4 more labels / short text on this page
CV6a · [5/8"]) · CV10a · CV8a K G
Page 331 of the Mitsubishi Electronics P96 user manual — (1) Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d) replacement procedures
Page 331 · click to enlarge
Page 331
2. Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement

instructions

* Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b,

SV4c, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures.

1. Applicable models

  • PURY-P96, P120THMU-A (-BS), PURY-P96, P120YHMU-A (-BS)

2. Parts to be serviced, Set-content

Following instructions are applicable to 1-4 service parts on the table below.

NO. Parts to be serviced

Things required for replacing Item

Numbers

  • Solenoid valve block service parts set [Set-content]
  • Replacement instructions
  • Solenoid valve block ASSY
  • Connecting pipe ( φ 9.52 [3/8"])

1 Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d)

2 Check valve (CV4a, CV8a)

  • Service parts replacement instructions set [Set-content]
  • Replacement instructions
  • Connecting pipe ( φ 9.52 [3/8"])

3 Check valve (CV9a)

4 Check valve (CV6a, CV10a)

3. Procedures

  • * Precautions for starting replacement
  • Check that the main power supply is OFF.
  • Check that no refrigerant is in the outdoor unit.

Remove each part according to the 1)-3) procedures on the next page before replacing service parts. Mount the removed parts back in place in a reversed procedures of 1)-3) on the next page after replacing service parts.

(1) Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d) replacement procedures

  • To remove Solenoid valve block ASSY ① Remove the solenoid valve block coil cover, solenoid valve coil, and peripheral cables. ② Remove the screw (M5) that fixes the solenoid valve block and the supporting plate for solenoid valve block. ③ Cut the pipe at the position indicated on the next page with a pipe cutter. Remove the pipe from the brazed A part. ④ Debraze B-H parts (total 7 places). ⑤ Do not damage heat exchanger fins and peripheral piping devices when removing the Solenoid valve block ASSY.
  • To install Solenoid valve block ASSY ⑥ Mount the Solenoid valve block ASSY replacement to the unit with care not to damage heat exchanger fins and

peripheral piping devices. Fix the Solenoid valve block ASSY and the supporting plate with the fixing screw (M5). ⑦ Braze B-H part (total 7 places), and connect the solenoid valve block and the heat exchanger header with the connect-

ing pipe (φ9.52 [3/8"]) that comes with the service parts set. ⑧ Mount the solenoid valve block coil cover, solenoid valve coil, and peripheral cables back in place.

  • * Precautions for replacing Solenoid valve block ASSY
  • Be sure to perform no-oxidation brazing when brazing.
  • After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air inside. (*1)
  • Perform carefully with the flame direction so that it does not burn cables and plates etc. in the unit.
  • Remove the brazing part protecting heat exchanger fins from burning, and replace the service parts. *1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.
Page 332 of the Mitsubishi Electronics P96 user manual — Brazing (Solenoid valve block side)
Page 332 · click to enlarge
Page 332
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 332)
Fig. 100
2. Remove the control box and the partition plate.
1. Remove the upper and lower service panels (Panel FU and FB).
3. Remove the cable that is fixed to the Frame ASSY MU (upper) and MB (lower), and remove the Frame ASSY MU and MB.

④⑦ Brazing or debrazing pipes ⑤ Removing Solenoid

④⑦B (φ19.05 [3/4"])

①Coil cover, Solenoid valve coil

Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 332)
Fig. 101

valve block ASSY E (φ28.6 [1-1/8"])

F (φ9.52 [3/8"])

Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 332)
Fig. 102

B

Mitsubishi Electronics P96 — B diagram (page 332)
Fig. 103

④⑦C (φ15.88

E

F

D

H (φ9.52 [3/8"])

H G Removed Solenoid valve block ASSY

G (φ15.88 [5/8"]) * This figure does not show heat exchanger.

②⑥ Removing or installing

③ Cutting pipes Cutting pipes positions Cut the pipe at 60mm ahead from the Bending R end with a pipe cutter.

solenoid valve block

④⑦D (φ15.88

Supporting plate for solenoid valve block

A (φ12.7

After cutting pipe, remove the pipe from the brazed A.

⑦ Brazing connecting pipe (φ9.52 [3/8"])

Mitsubishi Electronics P96 — solenoid valve block diagram (page 332)
Fig. 104 · solenoid valve block

Brazing (Solenoid valve block side)

Brazing (heat exchanger header side)

Service parts set supplied connecting pipe ( φ 9.52 [3/8"])

Heat exchanger ③⑦A (φ12.7 [1/2"])

* Refer to the next page for Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures.

Show 7 more labels / short text on this page
(SV4a,SV4b,SV4c,SV4d) · [5/8"]) · Solenoid valve block · [5/8"]) · Screw (M5) · 60 Bending R · [1/2"])
Page 333 of the Mitsubishi Electronics P96 user manual — inside. (*1)
Page 333 · click to enlarge
Page 333

(2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures

① Remove the solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d)

replacement procedures" on the front page.

② Debraze I-O parts (total 7 places), and remove the Check valve ASSY.

③ Replace the Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) to be serviced while it is removed from the unit.

Braze the pipes as they were according to the angle of the pipes on the figure below (Figure as viewed from point Q).

④ Mount the solenoid valve block ASSY, coil cover, and peripheral cables back in place according to "(1) Solenoid valve

block ASSY (SV4a, SV4b, SV4c, SV4d) replacement procedures" on the front page.

Part A (Refer to the next page.)

Mitsubishi Electronics P96 — Part A (Refer to the next page.) diagram (page 333)
Fig. 105 · Part A (Refer to the next page.)

②③ I (φ19.05 [3/4"])

②③ J (φ15.88 [5/8"])

②③ K (φ15.88 [5/8"])

Heat exchanger

②③ L (φ6.35 [1/4"])

②③ M (φ12.7 [1/2"])

* After removing Solenoid valve block ASSY

* Precautions for replacing Check valve

  • Be sure to perform no-oxidation brazing when brazing.
  • Place a wet towel on the check valve when heating pipes to keep the temperature of the valve from exceed-

ing 120°C [248°F].

  • After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air

inside. (*1)

  • Perform carefully with the flame direction so that it does not burn cables and plates etc. in the unit.
  • Remove the brazing part protecting heat exchanger fins not to be burn, and replace the service parts.

*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.

Page 334 of the Mitsubishi Electronics P96 user manual — Q
Page 334 · click to enlarge
Page 334

Detailed View of Part A

②③Brazing or debrazing pipes

③Check valve replacement

N (φ15.88 [5/8"])

O (φ28.6 [1-1/8"])

Mitsubishi Electronics P96 — Detailed View of Part A diagram (page 334)
Fig. 106 · Detailed View of Part A

When replacing CV4a:

Mitsubishi Electronics P96 — When replacing CV4a: diagram (page 334)
Fig. 107 · When replacing CV4a:

Remove the brazing 1.

O

N CV6a CV4a 2 (φ15.88 [5/8"])

When replacing CV6a:

1 (φ28.6 [1-1/8"])

Remove the brazing 2.

5 (φ25.4 [1"])

J

When replacing CV8a:

7 (φ15.88 [5/8"])

3 (φ28.6 [1-1/8"])

Remove the brazing 3 and 4.

When replacing CV9a:

K

Remove the brazing 5 and 6.

8 (φ15.88 [5/8"]) 6 (φ25.4 [1"]) 4 (φ28.6 [1-1/8"])

When replacing CV10a:

M G

Remove the brazing 7 and 8.

* This figure does not show heat exchanger.

Q

③Angle of the pipes when replacing CV8a,CV9a,CV10a (Figure as viewed from point Q)

Mitsubishi Electronics P96 — Q diagram (page 334)
Fig. 108
Show 4 more labels / short text on this page
CV8a · CV10a · CV9a · Check valve ASSY
Page 335 of the Mitsubishi Electronics P96 user manual — B
Page 335 · click to enlarge
Page 335

3. Solenoid valve (SV1a), Capillary tube ASSY (CP1) replacement instructions

1. Applicable models

PURY-P72THMU-A(-BS), PURY-P72YHMU-A(-BS)

……Low pressure twinning kit (optional accessory) is built in.

* The parts can be replaced without removing the Solenoid valve ASSY on the unit for the units that do not have

built-in low pressure twinning kit (optional accessory).

2. Parts to be serviced

NO. Item Applicable models

PURY-P72THMU-A(-BS) PURY-P72YHMU-A(-BS) Capillary tube ASSY (CP1)

3. Procedures

Removing the Solenoid valve (SV1a) and the Capillary tube ASSY (CP1) individually is difficult when the low

pressure twinning kit (optional accessory) is built in. Refer to the procedures Ԙԙ below and replace the parts.

  • * Precautions for starting replacement
  • Check that the main power supply is OFF.
  • Check that no refrigerant is in the outdoor unit.

Heat exchanger A (φ9.52 [3/8"])

Mitsubishi Electronics P96 — 3. Procedures diagram (page 335)
Fig. 109 · 3. Procedures
Mitsubishi Electronics P96 — 3. Procedures diagram (page 335)
Fig. 110 · 3. Procedures

Compressor cover

A

Low pressure twinning kit (optional accessory)

NO.1 Solenoid valve (SV1a)

NO.2 Capillary tube ASSY (CP1)

B (φ6.35 [1/4"])

B

Solenoid valve ASSY

ԘDebraze A and B, and remove solenoid valve ASSY

ԙReplace Solenoid valve (SV1a) or Capillary tube ASSY

from the unit.

(CP1), and mount them again.

  • * Precautions for brazing
  • Be sure to perform no-oxidation brazing when brazing.
  • After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air inside. (*1)
  • Braze carefully with the flame direction so that it does not burn cables and plates etc. in the unit. *1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed proced

Solenoid valve (SV1a)

Page 336 of the Mitsubishi Electronics P96 user manual — CMB-1016NU-G, GA
Page 336 · click to enlarge
Page 336

[7] Servicing the BC controller

1. Service panel

*Special care must be taken when replacing heavy parts.

Work procedure Explanatory figure

1. Remove the two lock nuts on the control box, loosen the other two, and remove the control box. 2) Remove the three fixing screws on the service panel, and remove the service panel. 3) Remove the nine machine screws on the ceiling panel, and remove the ceiling panel.

2. Control box

Work procedure Explanatory figure

(1) To check the inside of the control box, remove the

two lock nuts on the control box cover. 1) Check the terminal connection of the power wire or of the transmission line. 2) Check the transformer. 3) Check the address switch. (2) When the control board is replaced, the followings

Mitsubishi Electronics P96 — (1) To check the inside of the control box, remove the diagram (page 336)
Fig. 111 · (1) To check the inside of the control box, remove t…

must be noted. (1) Check that the board type is G,GA, or GB(HB). (2) Check that the wire and the connector are properly con-

nected.

CMB-1016NU-G, GA

It is not required to remove the two fixing screws on the control box when checking the inside.

Loosen Service panel · Ceiling panel · Control Box

Page 337 of the Mitsubishi Electronics P96 user manual — SVM1
Page 337 · click to enlarge
Page 337

3. Thermistor (liquid pipe/gas pipe temperature detection)

*Special care must be taken when replacing heavy parts.

Work procedure Explanatory figure

(1) Remove the service panel. 1) For TH11, TH12, and TH15, refer to 1. 1)-2). 2) For TH16, refer to (1)-1.2.3. (GA type only) (2) Remove the lead wire of the piping sensor from the

Mitsubishi Electronics P96 — 3. Thermistor (liquid pipe/gas pipe temperature detection) diagram (page 337)
Fig. 112 · 3. Thermistor (liquid pipe/gas pipe temperature dete…

control board. 1) TH11,TH12 (CN10) 2) TH15,TH16 (CN11) (3) Pull out the temperature sensor from the tempera-

TH16

ture sensor housing, and replace the temperature sensor with the new one. (4) Connect the lead wire of the temperature sensor se-

TH11

curely on the control board.

Mitsubishi Electronics P96 — TH11 diagram (page 337)
Fig. 113

TH15 TH12

CMB-1016NU-GA

4. Pressure sensor

Work procedure Explanatory figure

(1) Remove the service panel. 1) For the pressure sensors PS1 and PS3, refer to 1. 1)-2). (2) Remove the pressure sensor connector in trouble

PS1

from the control board, and insulate the connector. 1) Liquid-side pressure sensor (CNP1) 2) Intermediate-part pressure sensor (CNP3) (3) Attach a new pressure sensor to the place which is

Mitsubishi Electronics P96 — PS1 diagram (page 337)
Fig. 114

shown in the figure, and insert the connector to the control board.

PS3

When gas leaks from the pressure sensor, repair the leak, and follow the instructions above if required.

SVM1

Page 338 of the Mitsubishi Electronics P96 user manual — CMB-1016NU-GA
Page 338 · click to enlarge
Page 338

5. LEV

Work procedure Explanatory figure

(1) Remove the service panel.(Refer to (1)-1.2.3.) (2) Replace the LEV in trouble.

Mitsubishi Electronics P96 — 5. LEV diagram (page 338)
Fig. 115

LEV3

Secure enough service space in the ceiling for welding operation, and conduct the work carefully.If required, dismount the unit from the ceiling, and conduct the work.

LEV1

LEV2

SVM2

6. Solenoid valve

*Special care must be taken when replacing heavy parts.

Work procedure Explanatory figure

(1) Remove the service panel.(Refer to (1)-1.2.3.) (2) Remove the connector of the solenoid valve in trou-

ble. (3) Remove the solenoid valve coil. 1) The coils on the solenoid valves SVA, SVB, SVM1 and SVM2 can be serviced through the inspection door. SVC is accessible for replacement by removing the four mounting screws on the rear panel and removing the panel (if enough space is available on the back). (SVM1 is present only on the G and GA types, SVM2 on the GA type.)

Mitsubishi Electronics P96 — LEV1 diagram (page 338)
Fig. 116

CMB-1016NU-G

Mitsubishi Electronics P96 — CMB-1016NU-G diagram (page 338)
Fig. 117

CMB-1016NU-GA

SVM2b · Double-pipe heat exchanger · Solenoid valve

Page 339 of the Mitsubishi Electronics P96 user manual — [8] Troubleshooting Using the Outdoor Unit LED Error Display
Page 339 · click to enlarge
Page 339

[8] Troubleshooting Using the Outdoor Unit LED Error Display

If the LED error display appear as follows while all the SW1 switches are set to OFF, check the items under the applicable item numbers below.

1. Error code appears on the LED display. Refer to IX [2] Responding to Error Display on the Remote Controller.
2. LED is blank. Take the following troubleshooting steps. (1) If the voltage between pins 1 and 3 of CNDC on the control board is outside the range between 220 VDC and 380 VDC,

refer to IX [4] -8- (2) Troubleshooting transmission power circuit of outdoor unit. (2) If the LED error display becomes lit when the power is turned on with all the connectors on the control board except

CNDC disconnected, there is a problem with the wiring to those connectors or with the connectors themselves. (3) If nothing appears on the display under item (2) above AND the voltage between pins 1 and 3 of CNDC is within the

range between 220 VDC and 380 VDC, control board failure is suspected.

3. Only the software version appears on the LED display. (1) Only the software version appears while the transmission cables to TB3 and TB7 are disconnected. 1) Wiring failure between the control board and the transmission line power supply board.(CNIT, CNS2, CN102) 2) If item 1) checks out OK, the transmission line power supply board failure is suspected. 3) If items 1) and 2) check out OK, control board failure is suspected.

(2) If the LED display appears as noted in "X [1] 2. LED display at Initial setting" (page 333) while the transmission cables

to TB3 and TB7 are disconnected, failure with the transmission cable or the connected equipment is suspected.

Page 340 of the Mitsubishi Electronics P96 user manual — [1] How to Read the LED on the Service Monitor ...............................................................333
Page 340 · click to enlarge
Page 340

X LED Monitor Display on the Outdoor Unit Board

[1] How to Read the LED on the Service Monitor 333

Page 341 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 341 · click to enlarge
Page 341

- 332 -

Page 342 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 342 · click to enlarge
Page 342

[ X LED Monitor Display on the Outdoor Unit Board ]

X LED Monitor Display on the Outdoor Unit Board [1] How to Read the LED on the Service Monitor

1. How to read the LED By setting the DIP SW 1-1 through 1-10 (Switch number 10 is represented by 0), the operating condition of the unit can be monitored on the service monitor. (Refer to the table on the following pages for DIP SW settings.) The service monitor uses 4-digit 7-segment LED to display numerical values and other types of information.
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 342)
Fig. 118

Pressure and temperature are examples of numerical values, and operating conditions and the on-off status of solenoid valve are examples of flag display.

1. Display of numerical values Example: When the pressure data sensor reads 18.8kg/cm 2 (Item No. 58) Œ The unit of pressure is in kg/cm 2
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 342)
Fig. 119

Œ Use the following conversion formula to convert the displayed value into

a value in SI unit. Value in SI unit (MPa) = Displayed value (kg/cm2) x 0.098

2. Flag display Example: When 21S4a, 21S4b, SV1a are ON. (Item No. 3)
Example3-minutes restart mode (Item No. 14)
2. LED display at initial setting From power on until the completion of initial settings, the following information will be displayed on the monitor screen. (Displays No. 1 through No. 4 in order repeatedly.)
Mitsubishi Electronics P96 — P24, P27, P30 diagram (page 342)
Fig. 120

Model and capacity [H-20] : Cooling/Heating 20 HP For the first few minutes after power on, the capacity of each outdoor unit is displayed. Thereafter, the com- bined capacity is displayed.

After the initial settings have been completed, the information on these items can be checked by making the switch setting that corresponds to No. 517 in the LED display table.

Only item No. 1 "Software Version" appears on the display if there is a wiring failure between the control board and the trans- mission line power supply board or if the circuit board has failed.

Page 343 of the Mitsubishi Electronics P96 user manual — 3. Time data storage function
Page 343 · click to enlarge
Page 343

[ X LED Monitor Display on the Outdoor Unit Board ]

3. Time data storage function

The outdoor unit has a simple clock function that enables the unit to calculate the current time with an internal timer by receiv- ing the time set by the system controller, such as G(B)-50A. If an error (including a preliminary error) occurs, the error history data and the error detection time are stored into the service memory. The error detection time stored in the service memory and the current time can be seen on the service LED.

1) Use the time displayed on the service LED as a reference. 2) The date and the time are set to "00" by default. If a system controller that sets the time, such as G(B)-50A is not connected, the elapsed time and days since the first power on will be displayed. If the time set on a system controller is received, the count will start from the set date and the time. 3) The time is not updated while the power of the indoor unit is turned off. When the power is turned off and then on again, the count will resume from the time before the power was turned off. Thus, the time that differs the actual time will be displayed. (This also applies when a power failure occurs.) The system controller, such as G(B)-50A, adjusts the time once a day. When the system controller is connected, the time will be automatically updated to the correct current time after the time set by the system controller is received. (The data stored into the memory before the set time is received will not be updated.)

(1) Reading the time data1) Time display Example: 12 past 9
Mitsubishi Electronics P96 — 3. Time data storage function diagram (page 343)
Fig. 121 · 3. Time data storage function

* Disappears if the time data is deviated due to a power failure, or if a system controller that sets the time is not connected.

2. Date display Œ When the main controller that can set the time is connected
ExampleMay 10, 2003
Mitsubishi Electronics P96 — 3. Time data storage function diagram (page 343)
Fig. 122 · 3. Time data storage function

* Appears between the year and the month, and nothing appears when the date is displayed.

ŒWhen the main controller that can set the time is not connected

Example52 days after power was turned on
Mitsubishi Electronics P96 — 3. Time data storage function diagram (page 343)
Fig. 123 · 3. Time data storage function

* Appears between the year and the month, and nothing appears when the date is displayed.

Page 344 of the Mitsubishi Electronics P96 user manual — Current data
Page 344 · click to enlarge
Page 344

[ X LED monitor display on the outdoor unit board ]

Display of the latest pre-

(Including IC and BC) 0000 to 9999 (Address and error codes highlighted) B If no errors are detected,

" " appears on the dis-

If no preliminary errors

are detected, " " ap-

trolled, " " [ % ] ap-

trolled, " " [ % ] ap-

pears on the display.

mand capacity 0000 to 9999 B If not demanded con-

pears on the display.

capacity 0000 to 9999 B If not demanded con-

pears on the display.

play.

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

OC/OS error 0000 to 9999 (Address and error codes highlighted) B B

0000 to 9999 (Address and error codes highlighted) A A

A A

sion line A A

B B

eration 72C OC CPU in oper-

Top 21S4a CH11 SV1a SV2

SV4a SV4b SV4c SV5c SV4d SV9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Lighting Comp in op-

Check (error) display 1

Check (error) display 2

2 0100000000 Check (error) display 3

Relay output display 1

10 0101000000 Contact point demand

9 1001000000 Communication de-

3 1100000000 Relay out-

XLED monitor display on the outdoor unit board LED monitor display

No. SW1

Current data

- 335 - HWE0803A

Show 33 more labels / short text on this page
Remarks · liminary error · ation A A · Item Display Unit · ply for indoor · Communica- · Power sup- · transmis- · tion error · 3-minute re- start delay · mode · Communica- · tion error be- · tween the · OC and OS · Bottom SV5b · tion Emergency · operation · Retry opera- · Bottom · Top · Special control · OC/OS error · put display · Relay out- · put display · 0 0000000000 · 1 1000000000 · 4 0010000000 · 5 1010000000 · 6 0110000000 · 7 1110000000 · 8 0001000000
Page 345 of the Mitsubishi Electronics P96 user manual — Current data
Page 345 · click to enlarge
Page 345

[ X LED monitor display on the outdoor unit board ]

came to an abnormal stop

The lamp goes off when

Each unit that comes to

an abnormal unit will be

given a sequential num-

sponds to the unit that

ber in ascending order

check Top Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 B The lamp that corre-

Unlit while the unit is

stopped or in the fan

the error is reset.

Top Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 B Lit during cooling

starting with 1.

lights.

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

A A

A A

sure error A A

15 1111000000 OC/OS identification OC/OS A A

Bottom Unit No. 9 Unit No. 10 Unit No. 11 Unit No. 12 Unit No. 13 Unit No. 14 Unit No. 15 Unit No. 16

17 1000100000 Top Unit No. 17 Unit No. 18 Unit No. 19 Unit No. 20 Unit No. 21 Unit No. 22 Unit No. 23 Unit No. 24

Bottom Unit No. 25 Unit No. 26 Unit No. 27 Unit No. 28 Unit No. 29 Unit No. 30 Unit No. 31 Unit No. 32

18 0100100000 Top Unit No. 33 Unit No. 34 Unit No. 35 Unit No. 36 Unit No. 37 Unit No. 38 Unit No. 39 Unit No. 40

Bottom Unit No. 41 Unit No. 42 Unit No.43 Unit No. 44 Unit No. 45 Unit No. 46 Unit No47 Unit No. 48

Bottom Unit No. 9 Unit No. 10 Unit No. 11 Unit No. 12 Unit No. 13 Unit No. 14 Unit No. 15 Unit No. 16

21 1010100000 Top Unit No. 17 Unit No. 18 Unit No. 19 Unit No. 20 Unit No. 21 Unit No. 22 Unit No. 23 Unit No. 24

Bottom Unit No. 25 Unit No. 26 Unit No. 27 Unit No. 28 Unit No. 29 Unit No. 30 Unit No. 31 Unit No. 32

22 0110100000 Top Unit No. 33 Unit No. 34 Unit No. 35 Unit No. 36 Unit No. 37 Unit No. 38 Unit No. 39 Unit No. 40

Bottom Unit No. 41 Unit No. 42 Unit No.43 Unit No. 44 Unit No. 45 Unit No. 46 Unit No47 Unit No. 48

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

tion signal 3-minutes restart mode Compressor

19 1100100000 Top Unit No. 49 Unit No. 50

23 1110100000 Top Unit No. 49 Unit No. 50

16 0000100000 Indoor unit

20 0010100000 Indoor unit

No. SW1

Current data

- 336 - HWE0803A

Show 48 more labels / short text on this page
Lit during heating · Remarks · mode · Item Display Unit · (Quiet priori- · Preliminary · Low-noise · low pres- · mode · ty) · 3-minutes restart after · neous power · instanta- · failure · error Error · in operation Preliminary · heating · changeover · (Heating) · Cooling- · heating · changeover · (Cooling) · Cooling- · Snow sensor · Low-noise · (Capacity · priority ) · mode · status BC opera- · point de- · Contact · mand · Outdoor unit operation · (Open input contact · (Open input contact · Bottom · Bottom · External signal · External signal · Operation · point) · point) · mode · 11 1101000000 · 12 0011000000 · 13 1011000000 · 14 0111000000
Page 346 of the Mitsubishi Electronics P96 user manual — Current data
Page 346 · click to enlarge
Page 346

[ X LED monitor display on the outdoor unit board ]

Top Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 B Lit when thermostat is on

Unlit when thermostat is

off Bottom Unit No. 9 Unit No. 10 Unit No. 11 Unit No. 12 Unit No. 13 Unit No. 14 Unit No. 15 Unit No. 16

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

OFF Fan Stop B

25 1001100000 Top Unit No. 17 Unit No. 18 Unit No. 19 Unit No. 20 Unit No. 21 Unit No. 22 Unit No. 23 Unit No. 24

Bottom Unit No. 25 Unit No. 26 Unit No. 27 Unit No. 28 Unit No. 29 Unit No. 30 Unit No. 31 Unit No. 32

26 0101100000 Top Unit No. 33 Unit No. 34 Unit No. 35 Unit No. 36 Unit No. 37 Unit No. 38 Unit No. 39 Unit No. 40

Bottom Unit No. 41 Unit No. 42 Unit No.43 Unit No. 44 Unit No. 45 Unit No. 46 Unit No47 Unit No. 48

up Defrost Oil balance Low fre-

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

stop Standby Cooling Cooling-

mode Stop Thermo OFF Abnormal

27 1101100000 Top Unit No. 49 Unit No. 50

37 1010010000 BC operation mode Cooling-only

39 1110010000 Outdoor unit Operation

42 0101010000 Outdoor unit control

24 0001100000 Indoor unit

No. SW1

Current data

- 337 - HWE0803A

Show 32 more labels / short text on this page
Remarks · main A A · recovery A A · recovery A A · Item Display Unit · quency oil · ON Mixed-mode · main Heating Heating- · OFF Mixed-mode · control Initial start · ON Heating-only · stop Scheduled · OFF Heating-only · ON Cooling-only · 43 1101010000 Refrigerant · mode Permissible · Bottom · thermo- · stat · 28 0011100000 · 29 1011100000 · 30 0111100000 · 31 1111100000 · 32 0000010000 · 33 1000010000 · 34 0100010000 · 35 1100010000 · 36 0010010000 · 38 0110010000 · 40 0001010000 · 41 1001010000 · 44 0011010000
Page 347 of the Mitsubishi Electronics P96 user manual — Current data
Page 347 · click to enlarge
Page 347

[ X LED monitor display on the outdoor unit board ]

data -99.9 to 999.9 A A The unit is [kgf/cm2]

45 1011010000 TH4 -99.9 to 999.9 A A The unit is [°C]

56 0001110000 THHS1 -99.9 to 999.9 A A The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

46 0111010000 TH3 -99.9 to 999.9 A A

47 1111010000 TH7 -99.9 to 999.9 A A

48 0000110000 TH6 -99.9 to 999.9 A A

50 0100110000 TH5 -99.9 to 999.9 A A

57 1001110000 THBOX -99.9 to 999.9 A A

data -99.9 to 999.9 A A

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

58 0101110000 High-pressure sensor

59 1101110000 Low-pressure sensor

No. SW1

Current data

- 338 - HWE0803A

Show 20 more labels / short text on this page
Remarks · Item Display Unit · 49 1000110000 · 51 1100110000 · 52 0010110000 · 53 1010110000 · 54 0110110000 · 55 1110110000 · 60 0011110000 · 61 1011110000 · 62 0111110000 · 63 1111110000 · 64 0000001000 · 65 1000001000 · 66 0100001000 · 67 1100001000 · 68 0010001000 · 69 1010001000 · 70 0110001000 · 71 1110001000
Page 348 of the Mitsubishi Electronics P96 user manual — Current data
Page 348 · click to enlarge
Page 348

[ X LED monitor display on the outdoor unit board ]

frequency of the inverter

depends on the type of

the integer multiples (x1,

x2 etc.) of the operating

The unit is [rps]Output

frequency of the com-

(OC+OS) 0000 to 9999 B Control data [ Hz ]

81 1000101000 Target Tc -99.9 to 999.9 B The unit is [°C]

pressor.

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

78 0111001000 Qj 0000 to 9999 B B

79 1111001000 Qjc 0000 to 9999 B B

80 0000101000 Qjh 0000 to 9999 B B

83 1100101000 Tc -99.9 to 999.9 A A

84 0010101000 Te -99.9 to 999.9 A A

unit 0000 to 9999 A A

88 0001101000 COMP frequency 0000 to 9999 A A

0000 to 9999 A A

82 0100101000 Target Te -99.9 to 999.9 B

93 1011101000 All AK (OC+OS) 0000 to 9999 B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

87 1110101000 Total frequency of each

86 0110101000 Total frequencies

No. SW1

Current data

- 339 - HWE0803A

Show 16 more labels / short text on this page
compressor and equals · Remarks · Item Display Unit · COMP operating fre- · quency · 72 0001001000 · 73 1001001000 · 74 0101001000 · 75 1101001000 · 76 0011001000 · 77 1011001000 · 85 1010101000 · 89 1001101000 · 90 0101101000 · 91 1101101000 · 92 0011101000
Page 349 of the Mitsubishi Electronics P96 user manual — Current data
Page 349 · click to enlarge
Page 349

[ X LED monitor display on the outdoor unit board ]

quency 0000 to 9999 A A Twice the actual output

95 1111101000 FAN 0000 to 9999 A A Fan output [ % ]

rent (DC) 00.0 to 999.9 A A Peak value[A]

111 1111011000 COMP bus voltage 00.0 to 999.9 A A The unit is

[ V ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

94 0111101000 AK 0000 to 9999 A A

0000 to 9999 B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

unit went into the mode

96 0000011000 Fan inverter output fre-

108 0011011000 COMP operating cur-

Number of times the

to remedy wet vapor

No. SW1

Current data

- 340 - HWE0803A

Show 22 more labels / short text on this page
Remarks · frequency · Item Display Unit · suction · 97 1000011000 · 98 0100011000 · 99 1100011000 · 100 0010011000 · 101 1010011000 · 102 0110011000 · 103 1110011000 · 104 0001011000 · 105 1001011000 · 106 0101011000 · 107 1101011000 · 109 1011011000 · 110 0111011000 · 112 0000111000 · 113 1000111000 · 114 0100111000 · 115 1100111000 · 116 0010111000
Page 350 of the Mitsubishi Electronics P96 user manual — Current data
Page 350 · click to enlarge
Page 350

[ X LED monitor display on the outdoor unit board ]

rise A A Stays lit for 90 seconds

after the completion of

Upper 4 digits 0000 to 9999 A A Count-up at start-up

The unit is [Time]

rotation purpose) 0000 to 9999 B The unit is [ h ]

Upper 4 digits 0000 to 9999 A A The unit is

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

Lower 4 digits 0000 to 9999 A A

Lower 4 digits 0000 to 9999 A A

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

sure drop Abnormal Td

121 1001111000 Backup mode Abnormal

123 1101111000 COMP number of start-

124 0011111000 COMP number of start-

time of compressor (for

117 1010111000 COMP Operation time

118 0110111000 COMP Operation time

129 1000000100 Integrated operation

No. SW1

Current data

- 341 - HWE0803A

Show 23 more labels / short text on this page
Remarks · backup control · [ h ] · Item Display Unit · Control box · temperature · sure during · defrost cycle · High-pres- · rise · sure drop Low-pres- · pressure rise High-pres- · stop events · stop events · 119 1110111000 · 120 0001111000 · 122 0101111000 · 125 1011111000 · 126 0111111000 · 127 1111111000 · 128 0000000100 · 130 0100000100 · 131 1100000100
Page 351 of the Mitsubishi Electronics P96 user manual — Current data
Page 351 · click to enlarge
Page 351

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

B

B

B

B

B

B

B

B

B

133 1010000100 Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2

Bottom SVA3 SVB3 SVC3 SVA4 SVB4 SVC4

134 0110000100 Top SVA5 SVB5 SVC5 SVA6 SVB6 SVC6

Bottom SVA7 SVB7 SVC7 SVA8 SVB8 SVC8

135 1110000100 Top SVA9 SVB9 SVC9 SVA10 SVB10 SVC10

Bottom SVA11 SVB11 SVC11 SVA12 SVB12 SVC12

136 0001000100 Top SVA13 SVB13 SVC13 SVA14 SVB14 SVC14

Bottom SVA15 SVB15 SVC15 SVA16 SVB16 SVC16

Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2

Bottom SVA3 SVB3 SVC3 SVA4 SVB4 SVC4

139 1101000100 Top SVA5 SVB5 SVC5 SVA6 SVB6 SVC6

Bottom SVA7 SVB7 SVC7 SVA8 SVB8 SVC8

140 0011000100 Top SVA9 SVB9 SVC9 SVA10 SVB10 SVC10

Bottom SVA11 SVB11 SVC11 SVA12 SVB12 SVC12

141 1011000100 Top SVA13 SVB13 SVC13 SVA14 SVB14 SVC14

Bottom SVA15 SVB15 SVC15 SVA16 SVB16 SVC16

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Top SVM1 SVM2 SVM1b SVM2b

132 0010000100 Relay out-

138 0101000100 Relay out-

No. SW1

Current data

- 342 - HWE0803A

Show 9 more labels / short text on this page
Remarks · Item Display Unit · Bottom · put display · put display · BC(Sub1) · BC(Main) · 137 1001000100 · 142 0111000100
Page 352 of the Mitsubishi Electronics P96 user manual — Current data
Page 352 · click to enlarge
Page 352

[ X LED monitor display on the outdoor unit board ]

(Fully open:2000)

(Fully open:2000)

(Fully open:2000)

159 1111100100 BC(Main)LEV1 0000 to 2000 B LEV1 opening

160 0000010100 BC(Main)LEV3 0000 to 2000 B LEV3 opening

163 1100010100 BC(Sub1)LEV3 0000 to 2000 B LEV3 opening

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

B

B

B

B

TH11 -99.9 to 999.9 B

150 0110100100 BC(Main)TH12 -99.9 to 999.9 B

151 1110100100 BC(Main)TH15 -99.9 to 999.9 B

152 0001100100 BC(Main)TH16 -99.9 to 999.9 B

153 1001100100 BC(Main)63HS1 -99.9 to 999.9 B

154 0101100100 BC(Main)63HS3 -99.9 to 999.9 B

155 1101100100 BC(Main)SC11 -99.9 to 999.9 B

156 0011100100 BC(Main)SH12 -99.9 to 999.9 B

157 1011100100 BC(Main)SH13 -99.9 to 999.9 B

158 0111100100 BC(Main)SC16 -99.9 to 999.9 B

161 1000010100 BC(Sub1)TH12 -99.9 to 999.9 B

162 0100010100 BC(Sub1)TH15 -99.9 to 999.9 B

Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2

Bottom SVA3 SVB3 SVC3 SVA4 SVB4 SVC4

144 0000100100 Top SVA5 SVB5 SVC5 SVA6 SVB6 SVC6

Bottom SVA7 SVB7 SVC7 SVA8 SVB8 SVC8

145 1000100100 Top SVA9 SVB9 SVC9 SVA10 SVB10 SVC10

Bottom SVA11 SVB11 SVC11 SVA12 SVB12 SVC12

146 0100100100 Top SVA13 SVB13 SVC13 SVA14 SVB14 SVC14

Bottom SVA15 SVB15 SVC15 SVA16 SVB16 SVC16

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

149 1010100100 BC(Main or standard)

143 1111000100 Relay out-

No. SW1

Current data

- 343 - HWE0803A

Show 6 more labels / short text on this page
Remarks · Item Display Unit · put display · BC(Sub2) · 147 1100100100 · 148 0010100100
Page 353 of the Mitsubishi Electronics P96 user manual — Current data
Page 353 · click to enlarge
Page 353

[ X LED monitor display on the outdoor unit board ]

(Fully open:2000)

(Fully open:2000)

166 0110010100 BC(Sub2)LEV3 0000 to 2000 B LEV3a opening

167 1110010100 BC(Main)LEV2 0000 to 2000 B LEV2 opening

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

164 0010010100 BC(Sub2)TH12 -99.9 to 999.9 B

165 1010010100 BC(Sub2)TH25 -99.9 to 999.9 B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

No. SW1

Current data

- 344 - HWE0803A

Show 12 more labels / short text on this page
Remarks · Item Display Unit · 168 0001010100 · 169 1001010100 · 170 0101010100 · 171 1101010100 · 172 0011010100 · 173 1011010100 · 174 0111010100 · 175 1111010100 · 176 0000110100 · 177 1000110100
Page 354 of the Mitsubishi Electronics P96 user manual — Current data
Page 354 · click to enlarge
Page 354

[ X LED monitor display on the outdoor unit board ]

information of the OC nor

error information of the IC

178 0100110100 Error history 1 0000 to 9999 B B Address and error codes

If no errors are detected,

" " appears on the dis-

tion of the OS does not

appear on the OC.

appears on the OS.

play.

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

179 1100110100 Error details of inverter Error details of inverter (0001-0120) A A

180 0010110100 Error history 2 0000 to 9999 B B

181 1010110100 Error details of inverter Error details of inverter (0001-0120) A A

182 0110110100 Error history 3 0000 to 9999 B B

183 1110110100 Error details of inverter Error details of inverter (0001-0120) A A

184 0001110100 Error history 4 0000 to 9999 B B

185 1001110100 Error details of inverter Error details of inverter (0001-0120) A A

186 0101110100 Error history 5 0000 to 9999 B B

187 1101110100 Error details of inverter Error details of inverter (0001-0120) A A

188 0011110100 Error history 6 0000 to 9999 B B

189 1011110100 Error details of inverter Error details of inverter (0001-0120) A A

190 0111110100 Error history 7 0000 to 9999 B B

191 1111110100 Error details of inverter Error details of inverter (0001-0120) A A

192 0000001100 Error history 8 0000 to 9999 B B

193 1000001100 Error details of inverter Error details of inverter (0001-0120) A A

194 0100001100 Error history 9 0000 to 9999 B B

195 1100001100 Error details of inverter Error details of inverter (0001-0120) A A

196 0010001100 Error history 10 0000 to 9999 B B

197 1010001100 Error details of inverter Error details of inverter (0001-0120) A A

backup before error) 0000 to 9999 B B

199 1110001100 Error details of inverter Error details of inverter (0001-0120) A A

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

(At the time of last data

198 0110001100 Error history of inverter

No. SW1

Current data

- 345 - HWE0803A

Show 6 more labels / short text on this page
Preliminary error informa- · Neither preliminary error · Remarks · highlighted · Item Display Unit · 200 0001001100
Page 355 of the Mitsubishi Electronics P96 user manual — Error history
Page 355 · click to enlarge
Page 355

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

sure error A A

202 0101001100 OC/OS identification OC/OS A A

OFF Fan Stop A A

eration 72C OC Always lit A A

A A

up Defrost Oil balance Low fre-

Top 21S4a CH11 SV1a SV2

SV4a SV4b SV4c SV5c SV4d SV9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

tion signal 3-minutes restart mode Compressor

stop Standby Cooling Cooling-

mode Stop Thermo OFF Abnormal

203 1101001100 BC operation mode Cooling-only

Lighting Comp in op-

205 1011001100 Outdoor unit Operation

211 1100101100 Relay output display 1

208 0000101100 Outdoor unit control

No. SW1

Error history

- 346 - HWE0803A

Show 50 more labels / short text on this page
Remarks · main A A · recovery A A · recovery A A · A A Bottom · Item Display Unit · Preliminary · power to the · indoor units · is being sup- · low pres- · quency oil · Lit while · plied · 3-minutes restart after · neous power · instanta- · failure · ON Mixed-mode · main Heating Heating- · error Error · in operation Preliminary · OFF Mixed-mode · control Initial start · ON Heating-only · stop Scheduled · SV5b · OFF Heating-only · ON Cooling-only · 209 1000101100 Refrigerant · mode Permissible · status BC opera- · Outdoor unit operation · Bottom · Top · Relay out- · put display · Relay out- · put display · 2 Lighting · 3 Lighting · 201 1001001100 · 204 0011001100 · 206 0111001100 · 207 1111001100 · 210 0100101100 · 212 0010101100 · 213 1010101100 · 214 0110101100 · 215 1110101100
Page 356 of the Mitsubishi Electronics P96 user manual — Error history
Page 356 · click to enlarge
Page 356

[ X LED monitor display on the outdoor unit board ]

data -99.9 to 999.9 A A The unit is [kgf/cm2]

216 0001101100 TH4 -99.9 to 999.9 A A The unit is [°C]

227 1100011100 THHS1 -99.9 to 999.9 A A The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

217 1001101100 TH3 -99.9 to 999.9 A A

218 0101101100 TH7 -99.9 to 999.9 A A

219 1101101100 TH6 -99.9 to 999.9 A A

221 1011101100 TH5 -99.9 to 999.9 A A

228 0010011100 THBOX -99.9 to 999.9 A A

data -99.9 to 999.9 A A

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

229 1010011100 High-pressure sensor

230 0110011100 Low-pressure sensor

No. SW1

Error history

- 347 - HWE0803A

Show 20 more labels / short text on this page
Remarks · Item Display Unit · 220 0011101100 · 222 0111101100 · 223 1111101100 · 224 0000011100 · 225 1000011100 · 226 0100011100 · 231 1110011100 · 232 0001011100 · 233 1001011100 · 234 0101011100 · 235 1101011100 · 236 0011011100 · 237 1011011100 · 238 0111011100 · 239 1111011100 · 240 0000111100 · 241 1000111100 · 242 0100111100
Page 357 of the Mitsubishi Electronics P96 user manual — Error history
Page 357 · click to enlarge
Page 357

[ X LED monitor display on the outdoor unit board ]

quency 0000 to 9999 A A Twice the actual output

266 0101000010 FAN 0000 to 9999 A A Fan inverter output

254 0111111100 Tc -99.9 to 999.9 A A The unit is [°C]

252 0011111100 Target Tc -99.9 to 999.9 B The unit is [°C]

(OC+OS) 0000 to 9999 B Control data

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

249 1001111100 Qj 0000 to 9999 B B

250 0101111100 Qjc 0000 to 9999 B B

251 1101111100 Qjh 0000 to 9999 B B

255 1111111100 Te -99.9 to 999.9 A A

unit 0000 to 9999 A A

259 1100000010 COMP frequency 0000 to 9999 A A

265 1001000010 AK 0000 to 9999 A A

253 1011111100 Target Te -99.9 to 999.9 B

264 0001000010 All AK (OC+OS) 0000 to 9999 B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

258 0100000010 Total frequency of each

267 1101000010 Fan inverter output fre-

257 1000000010 Total frequencies

No. SW1

Error history

- 348 - HWE0803A

Show 16 more labels / short text on this page
Remarks · frequency · [ Hz ] · [ % ] · Item Display Unit · 243 1100111100 · 244 0010111100 · 245 1010111100 · 246 0110111100 · 247 1110111100 · 248 0001111100 · 256 0000000010 · 260 0010000010 · 261 1010000010 · 262 0110000010 · 263 1110000010
Page 358 of the Mitsubishi Electronics P96 user manual — Error history
Page 358 · click to enlarge
Page 358

[ X LED monitor display on the outdoor unit board ]

rent (DC) 00.0 to 999.9 A A Peak value[A]

282 0101100010 COMP bus voltage 00.0 to 999.9 A A The unit is [ V ]

Upper 4 digits 0000 to 9999 A A The unit is [ h ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

Lower 4 digits 0000 to 9999 A A

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

288 0000010010 COMP Operation time

289 1000010010 COMP Operation time

279 1110100010 COMP operating cur-

No. SW1

Error history

- 349 - HWE0803A

Show 24 more labels / short text on this page
Remarks · Item Display Unit · 268 0011000010 · 269 1011000010 · 270 0111000010 · 271 1111000010 · 272 0000100010 · 273 1000100010 · 274 0100100010 · 275 1100100010 · 276 0010100010 · 277 1010100010 · 278 0110100010 · 280 0001100010 · 281 1001100010 · 283 1101100010 · 284 0011100010 · 285 1011100010 · 286 0111100010 · 287 1111100010 · 290 0100010010 · 291 1100010010 · 292 0010010010 · 293 1010010010
Page 359 of the Mitsubishi Electronics P96 user manual — Error history
Page 359 · click to enlarge
Page 359

[ X LED monitor display on the outdoor unit board ]

Upper 4 digits 0000 to 9999 A A Count-up at start-up

The unit is [Time]

rotation purpose) 0000 to 9999 B The unit is [ h ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

Lower 4 digits 0000 to 9999 A A

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

294 0110010010 COMP number of start-

295 1110010010 COMP number of start-

time of compressor (for

300 0011010010 Integrated operation

No. SW1

Error history

- 350 - HWE0803A

Show 8 more labels / short text on this page
Remarks · Item Display Unit · stop events · stop events · 296 0001010010 · 297 1001010010 · 298 0101010010 · 299 1101010010
Page 360 of the Mitsubishi Electronics P96 user manual — Current data
Page 360 · click to enlarge
Page 360

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

301 1011010010 Power supply unit OC/OS Address B

302 0111010010 Start-up unit OC/OS Address B

320 0000001010 BC(Main)TH11 -99.9 to 999.9 B

321 1000001010 BC(Main)TH12 -99.9 to 999.9 B

322 0100001010 BC(Main)TH15 -99.9 to 999.9 B

323 1100001010 BC(Main)TH16 -99.9 to 999.9 B

324 0010001010 BC(Main)PS1 -99.9 to 999.9 B

325 1010001010 BC(Main)PS3 -99.9 to 999.9 B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

No. SW1

Current data

- 351 - HWE0803A

Show 21 more labels / short text on this page
Remarks · Item Display Unit · 309 1010110010 · 310 0110110010 · 311 1110110010 · 312 0001110010 · 313 1001110010 · 314 0101110010 · 315 1101110010 · 316 0011110010 · 317 1011110010 · 318 0111110010 · 319 1111110010 · 326 0110001010 · 327 1110001010 · 303 1111010010 · 304 0000110010 · 305 1000110010 · 306 0100110010 · 307 1100110010 · 308 0010110010
Page 361 of the Mitsubishi Electronics P96 user manual — Current data
Page 361 · click to enlarge
Page 361

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

330 0101001010 BC(Main)LEV1 0000 to 2000 B

331 1101001010 BC(Main)LEV3 0000 to 2000 B

332 0011001010 BC(Sub1)TH12 -99.9 to 999.9 B

333 1011001010 BC(Sub1)TH15 -99.9 to 999.9 B

334 0111001010 BC(Sub1)LEV3 0000 to 2000 B

335 1111001010 BC(Sub2)TH12 -99.9 to 999.9 B

336 0000101010 BC(Sub2)TH25 -99.9 to 999.9 B

337 1000101010 BC(Sub2)LEV3 0000 to 2000 B

338 0100101010 BC(Main)LEV2 0000 to 2000 B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

No. SW1

Current data

- 352 - HWE0803A

Show 16 more labels / short text on this page
Remarks · Item Display Unit · 328 0001001010 · 329 1001001010 · 339 1100101010 · 340 0010101010 · 341 1010101010 · 342 0110101010 · 343 1110101010 · 344 0001101010 · 345 1001101010 · 346 0101101010 · 347 1101101010 · 348 0011101010 · 349 1011101010 · 350 0111101010
Page 362 of the Mitsubishi Electronics P96 user manual — - 353 - HWE0803A
Page 362 · click to enlarge
Page 362

[ X LED monitor display on the outdoor unit board ]

351 1111101010 IC1 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alternately ev-

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

352 0000011010 IC2 Address/capacity code 0000 to 9999 0000 to 9999

353 1000011010 IC3 Address/capacity code 0000 to 9999 0000 to 9999

354 0100011010 IC4 Address/capacity code 0000 to 9999 0000 to 9999

355 1100011010 IC5 Address/capacity code 0000 to 9999 0000 to 9999

356 0010011010 IC6 Address/capacity code 0000 to 9999 0000 to 9999

357 1010011010 IC7 Address/capacity code 0000 to 9999 0000 to 9999

358 0110011010 IC8 Address/capacity code 0000 to 9999 0000 to 9999

359 1110011010 IC9 Address/capacity code 0000 to 9999 0000 to 9999

360 0001011010 IC10 Address/capacity code 0000 to 9999 0000 to 9999

361 1001011010 IC11 Address/capacity code 0000 to 9999 0000 to 9999

362 0101011010 IC12 Address/capacity code 0000 to 9999 0000 to 9999

363 1101011010 IC13 Address/capacity code 0000 to 9999 0000 to 9999

364 0011011010 IC14 Address/capacity code 0000 to 9999 0000 to 9999

365 1011011010 IC15 Address/capacity code 0000 to 9999 0000 to 9999

366 0111011010 IC16 Address/capacity code 0000 to 9999 0000 to 9999

367 1111011010 IC17 Address/capacity code 0000 to 9999 0000 to 9999

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 353 - HWE0803A

Remarks · ery 5 seconds · Item Display Unit

Page 363 of the Mitsubishi Electronics P96 user manual — - 354 - HWE0803A
Page 363 · click to enlarge
Page 363

[ X LED monitor display on the outdoor unit board ]

368 0000111010 IC18 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alternately ev-

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

369 1000111010 IC19 Address/capacity code 0000 to 9999 0000 to 9999

370 0100111010 IC20 Address/capacity code 0000 to 9999 0000 to 9999

371 1100111010 IC21 Address/capacity code 0000 to 9999 0000 to 9999

372 0010111010 IC22 Address/capacity code 0000 to 9999 0000 to 9999

373 1010111010 IC23 Address/capacity code 0000 to 9999 0000 to 9999

374 0110111010 IC24 Address/capacity code 0000 to 9999 0000 to 9999

375 1110111010 IC25 Address/capacity code 0000 to 9999 0000 to 9999

376 0001111010 IC26 Address/capacity code 0000 to 9999 0000 to 9999

377 1001111010 IC27 Address/capacity code 0000 to 9999 0000 to 9999

378 0101111010 IC28 Address/capacity code 0000 to 9999 0000 to 9999

379 1101111010 IC29 Address/capacity code 0000 to 9999 0000 to 9999

380 0011111010 IC30 Address/capacity code 0000 to 9999 0000 to 9999

381 1011111010 IC31 Address/capacity code 0000 to 9999 0000 to 9999

382 0111111010 IC32 Address/capacity code 0000 to 9999 0000 to 9999

383 1111111010 IC33 Address/capacity code 0000 to 9999 0000 to 9999

384 0000000110 IC34 Address/capacity code 0000 to 9999 0000 to 9999

385 1000000110 IC35 Address/capacity code 0000 to 9999 0000 to 9999

386 0100000110 IC36 Address/capacity code 0000 to 9999 0000 to 9999

387 1100000110 IC37 Address/capacity code 0000 to 9999 0000 to 9999

388 0010000110 IC38 Address/capacity code 0000 to 9999 0000 to 9999

389 1010000110 IC39 Address/capacity code 0000 to 9999 0000 to 9999

390 0110000110 IC40 Address/capacity code 0000 to 9999 0000 to 9999

391 1110000110 IC41 Address/capacity code 0000 to 9999 0000 to 9999

392 0001000110 IC42 Address/capacity code 0000 to 9999 0000 to 9999

393 1001000110 IC43 Address/capacity code 0000 to 9999 0000 to 9999

394 0101000110 IC44 Address/capacity code 0000 to 9999 0000 to 9999

395 1101000110 IC45 Address/capacity code 0000 to 9999 0000 to 9999

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 354 - HWE0803A

Remarks · ery 5 seconds · Item Display Unit

Page 364 of the Mitsubishi Electronics P96 user manual — - 355 - HWE0803A
Page 364 · click to enlarge
Page 364

[ X LED monitor display on the outdoor unit board ]

396 0011000110 IC46 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alternately ev-

408 0001100110 IC1 Suction temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

397 1011000110 IC47 Address/capacity code 0000 to 9999 0000 to 9999

398 0111000110 IC48 Address/capacity code 0000 to 9999 0000 to 9999

399 1111000110 IC49 Address/capacity code 0000 to 9999 0000 to 9999

400 0000100110 IC50 Address/capacity code 0000 to 9999 0000 to 9999

409 1001100110 IC2 Suction temperature -99.9 to 999.9

410 0101100110 IC3 Suction temperature -99.9 to 999.9

411 1101100110 IC4 Suction temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 355 - HWE0803A

Show 10 more labels / short text on this page
Remarks · ery 5 seconds · Item Display Unit · 401 1000100110 · 402 0100100110 · 403 1100100110 · 404 0010100110 · 405 1010100110 · 406 0110100110 · 407 1110100110
Page 365 of the Mitsubishi Electronics P96 user manual — - 356 - HWE0803A
Page 365 · click to enlarge
Page 365

[ X LED monitor display on the outdoor unit board ]

412 0011100110 IC5 Suction temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

413 1011100110 IC6 Suction temperature -99.9 to 999.9

414 0111100110 IC7 Suction temperature -99.9 to 999.9

415 1111100110 IC8 Suction temperature -99.9 to 999.9

416 0000010110 IC9 Suction temperature -99.9 to 999.9

417 1000010110 IC10 Suction temperature -99.9 to 999.9

418 0100010110 IC11 Suction temperature -99.9 to 999.9

419 1100010110 IC12 Suction temperature -99.9 to 999.9

420 0010010110 IC13 Suction temperature -99.9 to 999.9

421 1010010110 IC14 Suction temperature -99.9 to 999.9

422 0110010110 IC15 Suction temperature -99.9 to 999.9

423 1110010110 IC16 Suction temperature -99.9 to 999.9

424 0001010110 IC17 Suction temperature -99.9 to 999.9

425 1001010110 IC18 Suction temperature -99.9 to 999.9

426 0101010110 IC19 Suction temperature -99.9 to 999.9

427 1101010110 IC20 Suction temperature -99.9 to 999.9

428 0011010110 IC21 Suction temperature -99.9 to 999.9

429 1011010110 IC22 Suction temperature -99.9 to 999.9

430 0111010110 IC23 Suction temperature -99.9 to 999.9

431 1111010110 IC24 Suction temperature -99.9 to 999.9

432 0000110110 IC25 Suction temperature -99.9 to 999.9

433 1000110110 IC26 Suction temperature -99.9 to 999.9

434 0100110110 IC27 Suction temperature -99.9 to 999.9

435 1100110110 IC28 Suction temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 356 - HWE0803A

Remarks · Item Display Unit

Page 366 of the Mitsubishi Electronics P96 user manual — - 357 - HWE0803A
Page 366 · click to enlarge
Page 366

[ X LED monitor display on the outdoor unit board ]

436 0010110110 IC29 Suction temperature -99.9 to 999.9 B The unit is [°C]

458 0101001110 IC1 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

437 1010110110 IC30 Suction temperature -99.9 to 999.9

438 0110110110 IC31 Suction temperature -99.9 to 999.9

439 1110110110 IC32 Suction temperature -99.9 to 999.9

440 0001110110 IC33 Suction temperature -99.9 to 999.9

441 1001110110 IC34 Suction temperature -99.9 to 999.9

442 0101110110 IC35 Suction temperature -99.9 to 999.9

443 1101110110 IC36 Suction temperature -99.9 to 999.9

444 0011110110 IC37 Suction temperature -99.9 to 999.9

445 1011110110 IC38 Suction temperature -99.9 to 999.9

446 0111110110 IC39 Suction temperature -99.9 to 999.9

447 1111110110 IC40 Suction temperature -99.9 to 999.9

448 0000001110 IC41 Suction temperature -99.9 to 999.9

449 1000001110 IC42 Suction temperature -99.9 to 999.9

450 0100001110 IC43 Suction temperature -99.9 to 999.9

451 1100001110 IC44 Suction temperature -99.9 to 999.9

452 0010001110 IC45 Suction temperature -99.9 to 999.9

453 1010001110 IC46 Suction temperature -99.9 to 999.9

454 0110001110 IC47 Suction temperature -99.9 to 999.9

455 1110001110 IC48 Suction temperature -99.9 to 999.9

456 0001001110 IC49 Suction temperature -99.9 to 999.9

457 1001001110 IC50 Suction temperature -99.9 to 999.9

459 1101001110 IC2 Liquid pipe temperature -99.9 to 999.9

460 0011001110 IC3 Liquid pipe temperature -99.9 to 999.9

461 1011001110 IC4 Liquid pipe temperature -99.9 to 999.9

462 0111001110 IC5 Liquid pipe temperature -99.9 to 999.9

463 1111001110 IC6 Liquid pipe temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 357 - HWE0803A

Remarks · Item Display Unit

Page 367 of the Mitsubishi Electronics P96 user manual — - 358 - HWE0803A
Page 367 · click to enlarge
Page 367

[ X LED monitor display on the outdoor unit board ]

464 0000101110 IC7 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

465 1000101110 IC8 Liquid pipe temperature -99.9 to 999.9

466 0100101110 IC9 Liquid pipe temperature -99.9 to 999.9

467 1100101110 IC10 Liquid pipe temperature -99.9 to 999.9

468 0010101110 IC11 Liquid pipe temperature -99.9 to 999.9

469 1010101110 IC12 Liquid pipe temperature -99.9 to 999.9

470 0110101110 IC13 Liquid pipe temperature -99.9 to 999.9

471 1110101110 IC14 Liquid pipe temperature -99.9 to 999.9

472 0001101110 IC15 Liquid pipe temperature -99.9 to 999.9

473 1001101110 IC16 Liquid pipe temperature -99.9 to 999.9

474 0101101110 IC17 Liquid pipe temperature -99.9 to 999.9

475 1101101110 IC18 Liquid pipe temperature -99.9 to 999.9

476 0011101110 IC19 Liquid pipe temperature -99.9 to 999.9

477 1011101110 IC20 Liquid pipe temperature -99.9 to 999.9

478 0111101110 IC21 Liquid pipe temperature -99.9 to 999.9

479 1111101110 IC22 Liquid pipe temperature -99.9 to 999.9

480 0000011110 IC23 Liquid pipe temperature -99.9 to 999.9

481 1000011110 IC24 Liquid pipe temperature -99.9 to 999.9

482 0100011110 IC25 Liquid pipe temperature -99.9 to 999.9

483 1100011110 IC26 Liquid pipe temperature -99.9 to 999.9

484 0010011110 IC27 Liquid pipe temperature -99.9 to 999.9

485 1010011110 IC28 Liquid pipe temperature -99.9 to 999.9

486 0110011110 IC29 Liquid pipe temperature -99.9 to 999.9

487 1110011110 IC30 Liquid pipe temperature -99.9 to 999.9

488 0001011110 IC31 Liquid pipe temperature -99.9 to 999.9

489 1001011110 IC32 Liquid pipe temperature -99.9 to 999.9

490 0101011110 IC33 Liquid pipe temperature -99.9 to 999.9

491 1101011110 IC34 Liquid pipe temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 358 - HWE0803A

Remarks · Item Display Unit

Page 368 of the Mitsubishi Electronics P96 user manual — - 359 - HWE0803A
Page 368 · click to enlarge
Page 368

[ X LED monitor display on the outdoor unit board ]

492 0011011110 IC35 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

493 1011011110 IC36 Liquid pipe temperature -99.9 to 999.9

494 0111011110 IC37 Liquid pipe temperature -99.9 to 999.9

495 1111011110 IC38 Liquid pipe temperature -99.9 to 999.9

496 0000111110 IC39 Liquid pipe temperature -99.9 to 999.9

497 1000111110 IC40 Liquid pipe temperature -99.9 to 999.9

498 0100111110 IC41 Liquid pipe temperature -99.9 to 999.9

499 1100111110 IC42 Liquid pipe temperature -99.9 to 999.9

500 0010111110 IC43 Liquid pipe temperature -99.9 to 999.9

501 1010111110 IC44 Liquid pipe temperature -99.9 to 999.9

502 0110111110 IC45 Liquid pipe temperature -99.9 to 999.9

503 1110111110 IC46 Liquid pipe temperature -99.9 to 999.9

504 0001111110 IC47 Liquid pipe temperature -99.9 to 999.9

505 1001111110 IC48 Liquid pipe temperature -99.9 to 999.9

506 0101111110 IC49 Liquid pipe temperature -99.9 to 999.9

507 1101111110 IC50 Liquid pipe temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 359 - HWE0803A

Show 6 more labels / short text on this page
Remarks · Item Display Unit · 508 0011111110 · 509 1011111110 · 510 0111111110 · 511 1111111110
Page 369 of the Mitsubishi Electronics P96 user manual — Setting data
Page 369 · click to enlarge
Page 369

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

512 0000000001 Self-address Alternate display of self address and unit model A A

517 1010000001 Version/Capacity S/W version -> Refrigerant type -> Model and capacity -> Communication address A A

518 0110000001 OC address OC address display B

(A, B) *1

513 1000000001 IC/FU address Count-up display of number of connected units B

514 0100000001 RC address Count-up display of number of connected units B

515 1100000001 BC/BS/TU address Count-up display of number of connected units B

516 0010000001 OS address Count-up display of number of connected units B

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

No. SW1

Setting data

- 360 - HWE0803A

Show 6 more labels / short text on this page
Remarks · Item Display Unit · 519 1110000001 · 520 0001000001 · 521 1001000001 · 522 0101000001
Page 370 of the Mitsubishi Electronics P96 user manual — - 361 - HWE0803A
Page 370 · click to enlarge
Page 370

[ X LED monitor display on the outdoor unit board ]

523 1101000001 IC1 Gas pipe temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

524 0011000001 IC2 Gas pipe temperature -99.9 to 999.9

525 1011000001 IC3 Gas pipe temperature -99.9 to 999.9

526 0111000001 IC4 Gas pipe temperature -99.9 to 999.9

527 1111000001 IC5 Gas pipe temperature -99.9 to 999.9

528 0000100001 IC6 Gas pipe temperature -99.9 to 999.9

529 1000100001 IC7 Gas pipe temperature -99.9 to 999.9

530 0100100001 IC8 Gas pipe temperature -99.9 to 999.9

531 1100100001 IC9 Gas pipe temperature -99.9 to 999.9

532 0010100001 IC10 Gas pipe temperature -99.9 to 999.9

533 1010100001 IC11 Gas pipe temperature -99.9 to 999.9

534 0110100001 IC12 Gas pipe temperature -99.9 to 999.9

535 1110100001 IC13 Gas pipe temperature -99.9 to 999.9

536 0001100001 IC14 Gas pipe temperature -99.9 to 999.9

537 1001100001 IC15 Gas pipe temperature -99.9 to 999.9

538 0101100001 IC16 Gas pipe temperature -99.9 to 999.9

539 1101100001 IC17 Gas pipe temperature -99.9 to 999.9

540 0011100001 IC18 Gas pipe temperature -99.9 to 999.9

541 1011100001 IC19 Gas pipe temperature -99.9 to 999.9

542 0111100001 IC20 Gas pipe temperature -99.9 to 999.9

543 1111100001 IC21 Gas pipe temperature -99.9 to 999.9

544 0000010001 IC22 Gas pipe temperature -99.9 to 999.9

545 1000010001 IC23 Gas pipe temperature -99.9 to 999.9

546 0100010001 IC24 Gas pipe temperature -99.9 to 999.9

547 1100010001 IC25 Gas pipe temperature -99.9 to 999.9

548 0010010001 IC26 Gas pipe temperature -99.9 to 999.9

549 1010010001 IC27 Gas pipe temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 361 - HWE0803A

Remarks · Item Display Unit

Page 371 of the Mitsubishi Electronics P96 user manual — - 362 - HWE0803A
Page 371 · click to enlarge
Page 371

[ X LED monitor display on the outdoor unit board ]

(A, B) *1 Remarks

550 0110010001 IC28 Gas pipe temperature -99.9 to 999.9 B The unit is [°C]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

551 1110010001 IC29 Gas pipe temperature -99.9 to 999.9

552 0001010001 IC30 Gas pipe temperature -99.9 to 999.9

553 1001010001 IC31 Gas pipe temperature -99.9 to 999.9

554 0101010001 IC32 Gas pipe temperature -99.9 to 999.9

555 1101010001 IC33 Gas pipe temperature -99.9 to 999.9

556 0011010001 IC34 Gas pipe temperature -99.9 to 999.9

557 1011010001 IC35 Gas pipe temperature -99.9 to 999.9

558 0111010001 IC36 Gas pipe temperature -99.9 to 999.9

559 1111010001 IC37 Gas pipe temperature -99.9 to 999.9

560 0000110001 IC38 Gas pipe temperature -99.9 to 999.9

561 1000110001 IC39 Gas pipe temperature -99.9 to 999.9

562 0100110001 IC40 Gas pipe temperature -99.9 to 999.9

563 1100110001 IC41 Gas pipe temperature -99.9 to 999.9

564 0010110001 IC42 Gas pipe temperature -99.9 to 999.9

565 1010110001 IC43 Gas pipe temperature -99.9 to 999.9

566 0110110001 IC44 Gas pipe temperature -99.9 to 999.9

567 1110110001 IC45 Gas pipe temperature -99.9 to 999.9

568 0001110001 IC46 Gas pipe temperature -99.9 to 999.9

569 1001110001 IC47 Gas pipe temperature -99.9 to 999.9

570 0101110001 IC48 Gas pipe temperature -99.9 to 999.9

571 1101110001 IC49 Gas pipe temperature -99.9 to 999.9

572 0011110001 IC50 Gas pipe temperature -99.9 to 999.9

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Data on indoor unit system

No. SW1

- 362 - HWE0803A

Item Display Unit

Page 372 of the Mitsubishi Electronics P96 user manual — - 363 - HWE0803A
Page 372 · click to enlarge
Page 372

[ X LED monitor display on the outdoor unit board ]

573 1011110001 IC1SH -99.9 to 999.9 B The unit is [ °C ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

574 0111110001 IC2SH -99.9 to 999.9

575 1111110001 IC3SH -99.9 to 999.9

576 0000001001 IC4SH -99.9 to 999.9

577 1000001001 IC5SH -99.9 to 999.9

578 0100001001 IC6SH -99.9 to 999.9

579 1100001001 IC7SH -99.9 to 999.9

580 0010001001 IC8SH -99.9 to 999.9

581 1010001001 IC9SH -99.9 to 999.9

582 0110001001 IC10SH -99.9 to 999.9

583 1110001001 IC11SH -99.9 to 999.9

584 0001001001 IC12SH -99.9 to 999.9

585 1001001001 IC13SH -99.9 to 999.9

586 0101001001 IC14SH -99.9 to 999.9

587 1101001001 IC15SH -99.9 to 999.9

588 0011001001 IC16SH -99.9 to 999.9

589 1011001001 IC17SH -99.9 to 999.9

590 0111001001 IC18SH -99.9 to 999.9

591 1111001001 IC19SH -99.9 to 999.9

592 0000101001 IC20SH -99.9 to 999.9

593 1000101001 IC21SH -99.9 to 999.9

594 0100101001 IC22SH -99.9 to 999.9

595 1100101001 IC23SH -99.9 to 999.9

596 0010101001 IC24SH -99.9 to 999.9

597 1010101001 IC25SH -99.9 to 999.9

598 0110101001 IC26SH -99.9 to 999.9

599 1110101001 IC27SH -99.9 to 999.9

Data on indoor unit system

No. SW1

- 363 - HWE0803A

Remarks · Item Display Unit

Page 373 of the Mitsubishi Electronics P96 user manual — - 364 - HWE0803A
Page 373 · click to enlarge
Page 373

[ X LED monitor display on the outdoor unit board ]

600 0001101001 IC28SH -99.9 to 999.9 B The unit is [ °C ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

601 1001101001 IC29SH -99.9 to 999.9

602 0101101001 IC30SH -99.9 to 999.9

603 1101101001 IC31SH -99.9 to 999.9

604 0011101001 IC32SH -99.9 to 999.9

605 1011101001 IC33SH -99.9 to 999.9

606 0111101001 IC34SH -99.9 to 999.9

607 1111101001 IC35SH -99.9 to 999.9

608 0000011001 IC36SH -99.9 to 999.9

609 1000011001 IC37SH -99.9 to 999.9

610 0100011001 IC38SH -99.9 to 999.9

611 1100011001 IC39SH -99.9 to 999.9

612 0010011001 IC40SH -99.9 to 999.9

613 1010011001 IC41SH -99.9 to 999.9

614 0110011001 IC42SH -99.9 to 999.9

615 1110011001 IC43SH -99.9 to 999.9

616 0001011001 IC44SH -99.9 to 999.9

617 1001011001 IC45SH -99.9 to 999.9

618 0101011001 IC46SH -99.9 to 999.9

619 1101011001 IC47SH -99.9 to 999.9

620 0011011001 IC48SH -99.9 to 999.9

621 1011011001 IC49SH -99.9 to 999.9

622 0111011001 IC50SH -99.9 to 999.9

Data on indoor unit system

No. SW1

- 364 - HWE0803A

Remarks · Item Display Unit

Page 374 of the Mitsubishi Electronics P96 user manual — - 365 - HWE0803A
Page 374 · click to enlarge
Page 374

[ X LED monitor display on the outdoor unit board ]

623 1111011001 IC1SC -99.9 to 999.9 B The unit is [ °C ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

624 0000111001 IC2SC -99.9 to 999.9

625 1000111001 IC3SC -99.9 to 999.9

626 0100111001 IC4SC -99.9 to 999.9

627 1100111001 IC5SC -99.9 to 999.9

628 0010111001 IC6SC -99.9 to 999.9

629 1010111001 IC7SC -99.9 to 999.9

630 0110111001 IC8SC -99.9 to 999.9

631 1110111001 IC9SC -99.9 to 999.9

632 0001111001 IC10SC -99.9 to 999.9

633 1001111001 IC11SC -99.9 to 999.9

634 0101111001 IC12SC -99.9 to 999.9

635 1101111001 IC13SC -99.9 to 999.9

636 0011111001 IC14SC -99.9 to 999.9

637 1011111001 IC15SC -99.9 to 999.9

638 0111111001 IC16SC -99.9 to 999.9

639 1111111001 IC17SC -99.9 to 999.9

640 0000000101 IC18SC -99.9 to 999.9

641 1000000101 IC19SC -99.9 to 999.9

642 0100000101 IC20SC -99.9 to 999.9

643 1100000101 IC21SC -99.9 to 999.9

644 0010000101 IC22SC -99.9 to 999.9

645 1010000101 IC23SC -99.9 to 999.9

646 0110000101 IC24SC -99.9 to 999.9

647 1110000101 IC25SC -99.9 to 999.9

648 0001000101 IC26SC -99.9 to 999.9

649 1001000101 IC27SC -99.9 to 999.9

Data on indoor unit system

No. SW1

- 365 - HWE0803A

Remarks · Item Display Unit

Page 375 of the Mitsubishi Electronics P96 user manual — - 366 - HWE0803A
Page 375 · click to enlarge
Page 375

[ X LED monitor display on the outdoor unit board ]

650 0101000101 IC28SC -99.9 to 999.9 B The unit is [ °C ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

651 1101000101 IC29SC -99.9 to 999.9

652 0011000101 IC30SC -99.9 to 999.9

653 1011000101 IC31SC -99.9 to 999.9

654 0111000101 IC32SC -99.9 to 999.9

655 1111000101 IC33SC -99.9 to 999.9

656 0000100101 IC34SC -99.9 to 999.9

657 1000100101 IC35SC -99.9 to 999.9

658 0100100101 IC36SC -99.9 to 999.9

659 1100100101 IC37SC -99.9 to 999.9

660 0010100101 IC38SC -99.9 to 999.9

661 1010100101 IC39SC -99.9 to 999.9

662 0110100101 IC40SC -99.9 to 999.9

663 1110100101 IC41SC -99.9 to 999.9

664 0001100101 IC42SC -99.9 to 999.9

665 1001100101 IC43SC -99.9 to 999.9

666 0101100101 IC44SC -99.9 to 999.9

667 1101100101 IC45SC -99.9 to 999.9

668 0011100101 IC46SC -99.9 to 999.9

669 1011100101 IC47SC -99.9 to 999.9

670 0111100101 IC48SC -99.9 to 999.9

671 1111100101 IC49SC -99.9 to 999.9

672 0000010101 IC50SC -99.9 to 999.9

Data on indoor unit system

No. SW1

- 366 - HWE0803A

Show 5 more labels / short text on this page
Remarks · Item Display Unit · 673 1000010101 · 674 0100010101 · 675 1100010101
Page 376 of the Mitsubishi Electronics P96 user manual — Setting data
Page 376 · click to enlarge
Page 376

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

676 0010010101 INV board S/W version 0.00 to 99.99 A A

679 1110010101 Fan board S/W version 0.00 to 99.99 A A

(A, B) * 1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

No. SW1

Setting data

- 367 - HWE0803A

Show 12 more labels / short text on this page
Remarks · Item Display Unit · 677 1010010101 · 678 0110010101 · 680 0001010101 · 681 1001010101 · 682 0101010101 · 683 1101010101 · 684 0011010101 · 685 1011010101 · 686 0111010101 · 687 1111010101
Page 377 of the Mitsubishi Electronics P96 user manual — Setting data
Page 377 · click to enlarge
Page 377

[ X LED monitor display on the outdoor unit board ]

689 1000110101 Current time -2 00.00 to 99.12/1 to 31 Year and month, and date

691 1100110101 Time of error detection 1-2 00.00 to 99.12/1 to 31 Year and month, and date

693 1010110101 Time of error detection 2-2 00.00 to 99.12/1 to 31 Year and month, and date

695 1110110101 Time of error detection 3-2 00.00 to 99.12/1 to 31 Year and month, and date

697 1001110101 Time of error detection 4-2 00.00 to 99.12/1 to 31 Year and month, and date

699 1101110101 Time of error detection 5-2 00.00 to 99.12/1 to 31 Year and month, and date

701 1011110101 Time of error detection 6-2 00.00 to 99.12/1 to 31 Year and month, and date

688 0000110101 Current time 00:00 to 23:59 A A Hour: minute

690 0100110101 Time of error detection 1 00:00 to 23:59 Hour: minute

692 0010110101 Time of error detection 2 00:00 to 23:59 Hour: minute

694 0110110101 Time of error detection 3 00:00 to 23:59 Hour: minute

696 0001110101 Time of error detection 4 00:00 to 23:59 Hour: minute

698 0101110101 Time of error detection 5 00:00 to 23:59 Hour: minute

700 0011110101 Time of error detection 6 00:00 to 23:59 Hour: minute

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

No. SW1

Setting data

- 368 - HWE0803A

Show 9 more labels / short text on this page
Remarks · alternate display · alternate display · alternate display · alternate display · alternate display · alternate display · alternate display · Item Display Unit
Page 378 of the Mitsubishi Electronics P96 user manual — Setting data
Page 378 · click to enlarge
Page 378

[ X LED monitor display on the outdoor unit board ]

703 1111110101 Time of error detection 7-2 00.00 to 99.12/1 to 31 Year and month, and date

705 1000001101 Time of error detection 8-2 00.00 to 99.12/1 to 31 Year and month, and date

707 1100001101 Time of error detection 9-2 00.00 to 99.12/1 to 31 Year and month, and date

709 1010001101 Time of error detection 10-2 00.00 to 99.12/1 to 31 Year and month, and date

fore error -2 00.00 to 99.12/1 to 31 Year and month, and date

702 0111110101 Time of error detection 7 00:00 to 23:59 A A Hour: minute

704 0000001101 Time of error detection 8 00:00 to 23:59 Hour: minute

706 0100001101 Time of error detection 9 00:00 to 23:59 Hour: minute

708 0010001101 Time of error detection 10 00:00 to 23:59 Hour: minute

fore error 00:00 to 23:59 Hour: minute

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

710 0110001101 Time of last data backup be-

711 1110001101 Time of last data backup be-

No. SW1

Setting data

- 369 - HWE0803A

Show 9 more labels / short text on this page
Remarks · alternate display · alternate display · alternate display · alternate display · alternate display · Item Display Unit · 712 0001001101 · 713 1001001101
Page 379 of the Mitsubishi Electronics P96 user manual — - 370 - HWE0803A
Page 379 · click to enlarge
Page 379

[ X LED monitor display on the outdoor unit board ]

714 0101001101 IC1 LEV opening 0000 to 9999 B Fully open: 2000

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

715 1101001101 IC2 LEV opening 0000 to 9999

716 0011001101 IC3 LEV opening 0000 to 9999

717 1011001101 IC4 LEV opening 0000 to 9999

718 0111001101 IC5 LEV opening 0000 to 9999

719 1111001101 IC6 LEV opening 0000 to 9999

720 0000101101 IC7 LEV opening 0000 to 9999

721 1000101101 IC8 LEV opening 0000 to 9999

722 0100101101 IC9 LEV opening 0000 to 9999

723 1100101101 IC10 LEV opening 0000 to 9999

724 0010101101 IC11 LEV opening 0000 to 9999

725 1010101101 IC12 LEV opening 0000 to 9999

726 0110101101 IC13 LEV opening 0000 to 9999

727 1110101101 IC14 LEV opening 0000 to 9999

728 0001101101 IC15 LEV opening 0000 to 9999

729 1001101101 IC16 LEV opening 0000 to 9999

730 0101101101 IC17 LEV opening 0000 to 9999

731 1101101101 IC18 LEV opening 0000 to 9999

732 0011101101 IC19 LEV opening 0000 to 9999

733 1011101101 IC20 LEV opening 0000 to 9999

734 0111101101 IC21 LEV opening 0000 to 9999

735 1111101101 IC22 LEV opening 0000 to 9999

736 0000011101 IC23 LEV opening 0000 to 9999

737 1000011101 IC24 LEV opening 0000 to 9999

738 0100011101 IC25 LEV opening 0000 to 9999

739 1100011101 IC26 LEV opening 0000 to 9999

740 0010011101 IC27 LEV opening 0000 to 9999

Data on indoor unit system

No. SW1

- 370 - HWE0803A

Remarks · Item Display Unit

Page 380 of the Mitsubishi Electronics P96 user manual — - 371 - HWE0803A
Page 380 · click to enlarge
Page 380

[ X LED monitor display on the outdoor unit board ]

B The four LDs on the left

mode, and the four LDs

on the right (LD5-LD8)

display port address.

741 1010011101 IC28 LEV opening 0000 to 9999 B Fully open: 2000

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

0000Stop 0001 : Ventilation 0002 : Cooling 0003 : Heating 0004 : Dry

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

742 0110011101 IC29 LEV opening 0000 to 9999

743 1110011101 IC30 LEV opening 0000 to 9999

744 0001011101 IC31 LEV opening 0000 to 9999

745 1001011101 IC32 LEV opening 0000 to 9999

746 0101011101 IC33 LEV opening 0000 to 9999

747 1101011101 IC34 LEV opening 0000 to 9999

748 0011011101 IC35 LEV opening 0000 to 9999

749 1011011101 IC36 LEV opening 0000 to 9999

750 0111011101 IC37 LEV opening 0000 to 9999

751 1111011101 IC38 LEV opening 0000 to 9999

752 0000111101 IC39 LEV opening 0000 to 9999

753 1000111101 IC40 LEV opening 0000 to 9999

754 0100111101 IC41 LEV opening 0000 to 9999

755 1100111101 IC42 LEV opening 0000 to 9999

756 0010111101 IC43 LEV opening 0000 to 9999

757 1010111101 IC44 LEV opening 0000 to 9999

758 0110111101 IC45 LEV opening 0000 to 9999

759 1110111101 IC46 LEV opening 0000 to 9999

760 0001111101 IC47 LEV opening 0000 to 9999

761 1001111101 IC48 LEV opening 0000 to 9999

762 0101111101 IC49 LEV opening 0000 to 9999

763 1101111101 IC50 LEV opening 0000 to 9999

764 0011111101 IC1 Operation mode

765 1011111101 IC2 Operation mode

766 0111111101 IC3Operation mode

767 1111111101 IC4 Operation mode

768 0000000011 IC5 Operation mode

Data on indoor unit system

No. SW1

- 371 - HWE0803A

Show 5 more labels / short text on this page
(LD1-4) display operation · (Displayed alternately ev- · Remarks · ery five seconds) · Item Display Unit
Page 381 of the Mitsubishi Electronics P96 user manual — - 372 - HWE0803A
Page 381 · click to enlarge
Page 381

[ X LED monitor display on the outdoor unit board ]

B The four LDs on the left

tion mode, and the four

LDs on the right (LD5-

LD8) display port ad-

dress.

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

0000Stop 0001 : Ventilation 0002 : Cooling 0003 : Heating 0004 : Dry

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

773 1010000011 IC10 Operation mode

774 0110000011 IC11 Operation mode

775 1110000011 IC12 Operation mode

776 0001000011 IC13 Operation mode

777 1001000011 IC14 Operation mode

778 0101000011 IC15 Operation mode

779 1101000011 IC16 Operation mode

780 0011000011 IC17 Operation mode

781 1011000011 IC18 Operation mode

782 0111000011 IC19 Operation mode

783 1111000011 IC20 Operation mode

784 0000100011 IC21 Operation mode

785 1000100011 IC22 Operation mode

786 0100100011 IC23 Operation mode

787 1100100011 IC24 Operation mode

788 0010100011 IC25 Operation mode

789 1010100011 IC26 Operation mode

790 0110100011 IC27 Operation mode

791 1110100011 IC28 Operation mode

792 0001100011 IC29 Operation mode

793 1001100011 IC30 Operation mode

794 0101100011 IC31 Operation mode

795 1101100011 IC32 Operation mode

796 0011100011 IC33 Operation mode

769 1000000011 IC6 Operation mode

770 0100000011 IC7 Operation mode

771 1100000011 IC8 Operation mode

772 0010000011 IC9 Operation mode

Data on indoor unit system

No. SW1

- 372 - HWE0803A

Show 5 more labels / short text on this page
(LD1-4) display opera- · (Displayed alternately · every five seconds) · Remarks · Item Display Unit
Page 382 of the Mitsubishi Electronics P96 user manual — - 373 - HWE0803A
Page 382 · click to enlarge
Page 382

[ X LED monitor display on the outdoor unit board ]

B The four LDs on the left

tion mode, and the four

LDs on the right (LD5-

814 0111010011 IC1 filter 0000 to 9999 B Hours since last mainte-

LD8) display port ad-

nance [ h ]

dress.

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

0000Stop 0001 : Ventilation 0002 : Cooling 0003 : Heating 0004 : Dry

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

815 1111010011 IC2 filter 0000 to 9999

816 0000110011 IC3 filter 0000 to 9999

817 1000110011 IC4 filter 0000 to 9999

818 0100110011 IC5 filter 0000 to 9999

819 1100110011 IC6 filter 0000 to 9999

820 0010110011 IC7 filter 0000 to 9999

821 1010110011 IC8 filter 0000 to 9999

822 0110110011 IC9 filter 0000 to 9999

823 1110110011 IC10 filter 0000 to 9999

824 0001110011 IC11 filter 0000 to 9999

797 1011100011 IC34 Operation mode

798 0111100011 IC35 Operation mode

799 1111100011 IC36 Operation mode

800 0000010011 IC37 Operation mode

801 1000010011 IC38 Operation mode

802 0100010011 IC39 Operation mode

803 1100010011 IC40 Operation mode

804 0010010011 IC41 Operation mode

805 1010010011 IC42 Operation mode

806 0110010011 IC43 Operation mode

807 1110010011 IC44 Operation mode

808 0001010011 IC45 Operation mode

809 1001010011 IC46 Operation mode

810 0101010011 IC47 Operation mode

811 1101010011 IC48 Operation mode

812 0011010011 IC49 Operation mode

813 1011010011 IC50 Operation mode

Data on indoor unit system

No. SW1

- 373 - HWE0803A

Show 5 more labels / short text on this page
(LD1-4) display opera- · (Displayed alternately · every five seconds) · Remarks · Item Display Unit
Page 383 of the Mitsubishi Electronics P96 user manual — - 374 - HWE0803A
Page 383 · click to enlarge
Page 383

[ X LED monitor display on the outdoor unit board ]

825 1001110011 IC12 filter 0000 to 9999 B Hours since last mainte-

nance [ h ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

826 0101110011 IC13 filter 0000 to 9999

827 1101110011 IC14 filter 0000 to 9999

828 0011110011 IC15 filter 0000 to 9999

829 1011110011 IC16 filter 0000 to 9999

830 0111110011 IC17 filter 0000 to 9999

831 1111110011 IC18 filter 0000 to 9999

832 0000001011 IC19 filter 0000 to 9999

833 1000001011 IC20 filter 0000 to 9999

834 0100001011 IC21 filter 0000 to 9999

835 1100001011 IC22 filter 0000 to 9999

836 0010001011 IC23 filter 0000 to 9999

837 1010001011 IC24 filter 0000 to 9999

838 0110001011 IC25 filter 0000 to 9999

839 1110001011 IC26 filter 0000 to 9999

840 0001001011 IC27 filter 0000 to 9999

841 1001001011 IC28 filter 0000 to 9999

842 0101001011 IC29 filter 0000 to 9999

843 1101001011 IC30 filter 0000 to 9999

844 0011001011 IC31 filter 0000 to 9999

845 1011001011 IC32 filter 0000 to 9999

846 0111001001 IC33 filter 0000 to 9999

847 1111001011 IC34 filter 0000 to 9999

848 0000101011 IC35 filter 0000 to 9999

849 1000101011 IC36 filter 0000 to 9999

850 0100101011 IC37 filter 0000 to 9999

851 1100101011 IC38 filter 0000 to 9999

852 0010101011 IC39 filter 0000 to 9999

Data on indoor unit system

No. SW1

- 374 - HWE0803A

Remarks · Item Display Unit

Page 384 of the Mitsubishi Electronics P96 user manual — - 375 - HWE0803A
Page 384 · click to enlarge
Page 384

[ X LED monitor display on the outdoor unit board ]

853 1010101011 IC40 filter 0000 to 9999 B Hours since last mainte-

nance [ h ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) * 1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

854 0110101011 IC41 filter 0000 to 9999

855 1110101011 IC42 filter 0000 to 9999

856 0001101011 IC43 filter 0000 to 9999

857 1001101011 IC44 filter 0000 to 9999

858 0101101011 IC45 filter 0000 to 9999

859 1101101011 IC46 filter 0000 to 9999

860 0011101011 IC47 filter 0000 to 9999

861 1011101011 IC48 filter 0000 to 9999

862 0111101011 IC49 filter 0000 to 9999

863 1111101011 IC50 filter 0000 to 9999

Data on indoor unit system

No. SW1

- 375 - HWE0803A

Remarks · Item Display Unit

Page 385 of the Mitsubishi Electronics P96 user manual — - 376 - HWE0803A
Page 385 · click to enlarge
Page 385

[ X LED monitor display on the outdoor unit board ]

gle 1 -99.9 to 999.9 A A The unit is [ deg ]

Reset counter 0 to 254 A A The unit is [ time ]

Reset counter 0 to 254 A A The unit is [ time ]

tive value 1 -99.9 to 999.9 A A The unit is [ A ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

tive value 1 -99.9 to 999.9 A A

Reset counter 0 to 254 A A

(A, B) *1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

873 1001011011 Power factor phase an-

871 1110011011 U-phase current effec-

872 0001011011 W-phase current effec-

880 0000111011 Control board

881 1000111011 INV board

884 0010111011 Fan board

Other types of data

No. SW1

- 376 - HWE0803A

Show 19 more labels / short text on this page
Remarks · Item Display Unit · 864 0000011011 · 865 1000011011 · 866 0100011011 · 867 1100011011 · 868 0010011011 · 869 1010011011 · 870 0110011011 · 874 0101011011 · 875 1101011011 · 876 0011011011 · 877 1011011011 · 878 0111011011 · 879 1111011011 · 882 0100111011 · 883 1100111011 · 885 1010111011 · 886 0110111011
Page 386 of the Mitsubishi Electronics P96 user manual — - 377 - HWE0803A
Page 386 · click to enlarge
Page 386

[ X LED monitor display on the outdoor unit board ]

1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS

(A, B) *1

*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Other types of data

No. SW1

- 377 - HWE0803A

Show 27 more labels / short text on this page
Remarks · Item Display Unit · 887 1110111011 · 888 0001111011 · 889 1001111011 · 890 0101111011 · 891 1101111011 · 892 0011111011 · 893 1011111011 · 894 0111111011 · 895 1111111011 · 896 0000000111 · 897 1000000111 · 898 0100000111 · 899 1100000111 · 900 0010000111 · 901 1010000111 · 902 0110000111 · 903 1110000111 · 904 0001000111 · 905 1001000111 · 906 0101000111 · 907 1101000111 · 1020 0011111111 · 1021 1011111111 · 1022 0111111111 · 1023 1111111111
Page 387 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Page 387 · click to enlarge
Page 387
Page 387 of the Mitsubishi Electronics P96 user manual — P24, P27, P30
Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
TB3Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control p.27
0403Serial communication error p.148
4220, 4225Bus voltage drop p.148
4230Heatsink overheat protection p.148
4240Overload protection p.148
4250, 4255Overcurrent relay trip p.148
5110Heatsink temperature sensor failure (THHS) p.148
5301Current sensor/circuit failure p.148
5102Subcool heat exchanger bypass outlet temperature sensor failure p.148
5103Pipe temperature sensor failure p.148
5104Discharge temperature sensor failure p.148
5105Accumulator inlet temperature sensor failure p.148
5106Subcool heat exchanger liquid outlet sensor failure p.148
5107Outside air temperature sensor failure p.148
4102Open phase p.148
4115Power supply sync signal abnormality p.148
6607No acknowledgement error p.149
6608No response error p.149
6600Noise interference on the transmission line p.279
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Water infiltration p.23
Hydrolysis p.23
OxidizationAir infiltration p.23
Adhesion to expansion valve and capillary tubesInfiltration of contaminants p.23
Infiltration of contaminants into the com- pressor p.23
Sludge formation and adhesion p.23
Oil degradation p.23
The indoor unit does not start after starting cooling (heating) operation.The unit cannot perform a heating (cooling) operation when other indoor units are performing a cooling (heating) operation. p.171
The auto vane adjusts its posi- tion by itself.After an hour of cooling operation with the auto vane in the vertical posi- tion, the vane may automatically move into the horizontal position. Louver blades will automatically move into the horizontal position while the unit is in the defrost mode, pre-heating stand-by mode, or when the thermostat triggers unit off. p.171
The fan stops during heating operation.The fan remains stopped during defrost operation. p.171
The fan keeps running after the unit has stopped.When the auxiliary heater is turned on, the fan operates for one minute after stopping to dissipate heat. p.171
The fan speed does not reach the set speed when operation switch is turned on.The fan operates at extra low speed for 5 minutes after it is turned on or until the pipe temperature reaches 35°C[95°F], then it operates at low speed for 2 minutes, and finally it operates at the set speed. (Pre-heating stand-by) p.171
When the main power is turned on, the display shown on the right appears on the in- door unit remote controller for 5 minutes.The system is starting up. Wait until the blinking display of "HO" or "PLEASE WAIT" go off. p.171
The drain pump keeps run- ning after the unit has stopped.The drain pump stays in operation for three minutes after the unit in the cooling mode is stopped. p.171
The drain pump is running while the unit is stopped.When drain water is detected, the drain pump goes into operation even while the unit is stopped. p.171
Indoor unit and BC controller make noise during cooling/ heating changeover.This noise is made when the refrigerant circuit is reversed and is normal. p.171
Sound of the refrigerant flow is heard from the indoor unit im- mediately after starting opera- tion.This is caused by the transient instability of the refrigerant flow and is nor- mal. p.171
Warm air sometimes comes out of the indoor units that are not in the heating mode.This is due to the fact that the LEVs on some of the indoor units are kept slightly open to prevent the refrigerant in the indoor units that are not op- erating in the heating mode from liquefying and accumulating in the com- pressor. It is part of a normal operation. p.171
Microcomputer driver circuit fail- ureWhen the drive circuit has a problem, replace the control board. p.290
LEV mechanism is lockedReplace the LEV. p.290
Disconnected or short-circuited LEV motor coilReplace the LEV coils. p.290
Incomple sealing (leak from the valve)If there is a large amount of leakage, replace the LEV. p.290
Faulty wire con- nections in the connector or faulty contactCheck the continuity at the points where an error occurs. p.290

Ask about the Mitsubishi Electronics P96

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics P96

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics P96 manual PDF

387 pages·21.6 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…