SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
December 2010
No. OC366 REVISED EDITION-F
TECHNICAL & SERVICE MANUAL
[Model name] (Standard type) PUMY-P36NHMU
[Service Ref.]
PUMY-P36NHMU PUMY-P36NHMUR1 PUMY-P48NHMU PUMY-P48NHMU1 PUMY-P48NHMU2 PUMY-P48NHMUR3 PUMY-P36NHMU-BS PUMY-P36NHMUR1-BS PUMY-P48NHMU-BS PUMY-P48NHMU1-BS PUMY-P48NHMU2-BS PUMY-P48NHMUR3-BS
service manual. • RoHS compliant products have mark on the spec name plate.

CONTENTS 1. TECHNICAL CHANGES 3 2. SAFETY PRECAUTION 6 3. OVERVIEW OF UNITS 9 4. SPECIFICATIONS 11 5. DATA 13 6. OUTLINES AND DIMENSIONS 18 7. WIRING DIAGRAM 20 8. NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION 24 9. TROUBLESHOOTING 34 10. ELECTRICAL WIRING 81 11. REFRIGERANT PIPING TASKS 84 12. DISASSEMBLY PROCEDURE 88 13. PARTS LIST 93 14. RoHS PARTS LIST 96 15. OPTIONAL PARTS 99 OUTDOOR UNIT


"14. RoHS PARTS LIST " has been modifi ed on page 98.

· Compressor (MC) and oil have been changed. ANB33FDCMT (Ester oil: MEL56) ANB33FDHMT(Ether oil: FV50S) · Electrical parts have been changed. Multi controller board (MULTI. → C.B.) Noise filter circuit board (N.F.) Active filter module (ACTM) Relay (52C) , Resister (RS) (including N.F.)
(1) Primary heating operation controls another heat source that depends on the main system's operations,
which means the interlock operation shown in "c)" will be possible. a) b)
Service ref. PUMY-P48NHMU(-BS) does not have this function. Indoor unit must be R410A UL model for this function to operate.
PMFY-P06NBMU PMFY-P12NBMU PKFY-P06NAMU PMFY-P08NBMU PMFY-P15NBMU PKFY-P08NAMU c) Different Indoor unit applications that can be applied:

Set DIPSW4-4 when power is turned off at unit.

a) With no Primary heating output the Indoor fan normally goes off to prevent cold drafts during the defrost cycles. b) With Primary heating control the auxiliary heat will be on during defrost mode, thus cold drafts will not be present. (Ducted units only) c) For models PEFY and PDFY (Ducted) recommended to use "Black" (20K) connector. d) For models PLFY, PCFY, PKFY and PFFY (Ductless) recommended "None", no connector required. e) To set the fan airflow rate to be used during defrost operation, insert the resistance that is packed within the optional adaptor cable kit (PAC-YU24HT-F) into the CN22 sensor input. You can choose at what speed the indoor fan operates during defrost cycles bases on chart below.

a) These settings are done within Indoor DIPSW1-7 and DIPSW1-8, see chart below for options. b) Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on "Setting on the remote controller".

(5) Setting Outdoor unit and Auxiliary heat switch over temperatures.
When the DIPSW 4-4 is set to "ON", the outdoor unit and the contact output operates as shown below.
a) Outdoor default setting and operations are shown below:
Stage 1 Amb. Decreasing - Outdoor unit HP operation Amb. Increasing - Defrost : Heater contact ON signal
- Outdoor unit HP operation - Heater contact ON signal
- Outdoor unit OFF (Standby)
- Heater contact ON signal
TH7 = Outdoor Temperature a -12: [10 F]
Stage 2 · Stage 3

When the set temperature ranges overlap, the previously set pattern (1,2 or 3) has a priority. The stage 1 has the highest priority, 2 the second and then 3.
b) Based on above chart listed the sequence of operation on "On Ambient Decrease"
Stage 1 :(TH7 = > 10 :) : the Outdoor unit runs in HP mode. Stage 2 :(TH7 = 10: to -12:) : the Outdoor unit runs in HP mode with Auxiliary heating. Stage 3 :(TH7 = < -12:) : Auxiliary heating only (Outdoor unit is OFF).
c) Based on above chart listed the sequence of operation on " On Ambient Increase"
Stage 3 :(TH7 = < 0 :) : Auxiliary heating only (Outdoor unit is OFF). Stage 2 :(TH7 = > 0: to 20:) : Auxiliary heating with Outdoor unit in HP mode. Stage 1 :(TH7 = > 20:) : Outdoor unit in HP mode only.
A basic connection method is shown.
(i.e. interlocked operation with the electric heater with the fan speed setting on high
Indoor unit control board
Outdoor unit control board
Remote control Board Relay circuit Adapter
Dip switch SW4-4 "ON"
CN22 X +
Preparations in the field Maximum cable length is 10 m (32ft)
For relay X use the specifications given below Operation coil
Rated voltage : 12VDC Power consumption : 0.9W or less *Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (AWG22 to AWG16) Don`t extend the cable more than 10 meters (32ft).
R
FS1
S
FS2 FS1
H2 88H
R
FS1, 2 Thermal fuse
FS2
H1, H2 Heater
26H Overheat protection thermostat
88H Electromagnetic contactor
![Page 6 of the Mitsubishi Electronics OC366 user manual — [2] Additional refrigerant charge](/cdn/reader/57/5735c9b311c410314a037792b147e95b4d42b7c077cd08d0794115b0e3ae5593/images/page-6.webp?w=400)
Use new refrigerant pipes.
Do not use refrigerant other than R410A.
Avoid using thin pipes.
If other refrigerant (R22 etc.) is used, chlorine in refrige- rant can cause deterioration of refrigerant oil etc.
Make sure that the inside and outside of refrige- rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazards to refrigerant cycle. In addition, use pipes with specified thickness.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
Contamination inside refrigerant piping can cause deterio- ration of refrigerant oil etc.
The following tools are necessary to use R410A refrigerant.
Store the piping to be used indoors during installation, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com- pressor.
Handle tools with care.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbezene oil in a small amount.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com- pressor.
If large amount of mineral oil enters, that can cause deterio- ration of refrigerant oil etc.
Do not use a charging cylinder.
Charge refrigerant from liquid phase of gas cylinder.
If a charging cylinder is used, the composition of refrigera- nt will change and the efficiency will be lowered.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
When charging directly from cylinder · Check that cylinder for R410A on the market is syphon type. · Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

Gravimeter
[3] Service tools Use the below service tools as exclusive tools for R410A refrigerant.
2-2. PRECAUTIONS FOR SALT PROOF TYPE "-BS" MODEL Although "-BS" model has been designed to be resistant to salt damage, observe the following precautions to maintain the performance of the unit. 1. Avoid installing the unit in a location where it will be exposed directly to seawater or sea breeze. 2. If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away by rainwater. (If a sunshade is installed, rainwater may not clean the panel.) 3. To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust. 4. If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up. 5. If the unit is damaged during installation or maintenance, be sure to repair it. 6. Be sure to check the condition of the unit regularly. 7. Be sure to install the unit in a location with good drainage.

2-3. Cautions for refrigerant piping work New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
1 Thickness of pipes Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 0.7 mm [7/256 inch] or below.)
2 Dimensions of flare cutting and flare nut The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A has been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to increase intensity as shown below. Set copper pipe correctly referring to cop- per pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes. Use torque wrench corresponding to each dimension.


3 Tools for R410A (The following table shows whether conventional tools can be used or not.)

Model Ceiling Ceiling Ceiling Concealed mounted Wall Mounted Concealed 4-way flow 2-way flow 1-way flow built-in Exposed Concealed (Fresh Air)*1 PLFY-P PLFY-P PMFY-P PEFY-P PDFY-P PKFY-P PCFY-P PFFY-P PEFY-P Capacity NCMU-E NBMU-E NLMU-E NBMU-E NMLU-E NMHU-E NMSU-E NMU-E NAMU-E NGMU-E NFMU-E NGMU-E NEMU-E NRMU-E NMHU-E-F 06 08 12 15 18 24 27 30 36 48 54
Ceiling Cassette Ceiling Suspended
*1. It is possible only by 1:1 system. (1 indoor unit of Fresh Air type is connected with 1 outdoor unit.) Operating temperature range (outdoor temperature) for fresh air type indoor units differ from other indoor units. Refer to 3-2(2).
Floor Standing · Decorative panel

P L F Y - P 30 N B M U - E PU M Y - P 48 N H M U -BS
L : Ceiling cassette K : Wall-mounted type E : Hidden skylight type C : Ceiling suspended type M : Ceiling cassette type F : Floor standing type
Outdoor unit model type
Salt proof type Frequency conversion controller
N: Single phase 208/230V 60Hz
Indicates equivalent to Cooling capacity
NEW frequency converter one-to-many air conditioners (flexible design type)
Indicates equivalent to Cooling capacity
*2.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is lower than 21D.B.[70°FD.B.]. *3.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is higher than 20D.B.[68°FD.B.].

Rating conditions Cooling Indoor : D.B. 26.7°C / W.B. 19.4°C [D.B. 80°F / W.B. 67°F] Outdoor : D.B. 35°C[D.B. 95°F] Heating Indoor : D.B. 21.1°C[D.B. 70°F] Outdoor : D.B. 8.3°C / W.B. 6.1°C [D.B. 47°F / W.B. 43°F]
Note.*1. 20m [70ft] : In case of installing outdoor unit lower than indoor unit. *2. 10~46°C [50~115°F]DB : In case of connecting PKFY-P06/P08 type indoor unit. *3. Electrical data is for only outdoor unit. (In case of connecting 2 indoor units of PLFY-P18BM type) Btu/h=kW × 3,412 CFM=K/min × 35.31 lbs=kg/ 0.4536 *Above specification data is subject to rounding variation.

Rating conditions Cooling Indoor : D.B. 26.7°C / W.B. 19.4°C [D.B. 80°F / W.B. 67°F] Outdoor : D.B. 35°C[D.B. 95°F] Heating Indoor : D.B. 21.1°C[D.B. 70°F] Outdoor : D.B. 8.3°C / W.B. 6.1°C [D.B. 47°F / W.B. 43°F]

5-1-1. Method for obtaining system cooling and heating capacity: To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with the help of the tables on 5-2. STANDARD CAPACITY DIAGRAM.
Model number for indoor unit Model 06 Model 08 Model 12 Model 15 Model 18 Model 24 Model 27 Model 30 Model 36 Model 48 Model 54
Model Capacity 6 8 12 15 18 24 27 30 36 48 54
Capacity (Btu/h) Outdoor unit power consumption (kW) Outdoor unit current (A)/230V
Cooling Heating Cooling Heating Cooling Heating
5-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
model capacity total model capacity of all indoor units
(1) The capacity of each indoor unit (Btu/h) = the capacity A (or B) o
During cooling: During heating:
9000 58000 20000 58000
Model 08= 48,900 o = 7,520 Btu/h
Model 08=54,500 o = 8,460 Btu/h
Model 18= 48,900 o = 16,930 Btu/h
Model 18= 54,500 o = 18,790 Btu/h
8000 52000 · 18000 52000

5-2. STANDARD CAPACITY DIAGRAM * Before calculating the sum of total capacity of indoor units, please convert the value following the formula on 5-1-1.
Total capacity of Indoor units* Cooling Heating Cooling Heating Cooling Heating Cooling Heating
18 18,000 20,200 1.38 1.45 6.1 6.4 6.8 7.1 19 19,000 21,300 1.45 1.52 6.4 6.7 7.1 7.4 20 20,000 22,400 1.52 1.60 6.7 7.0 7.4 7.8 21 21,000 23,500 1.60 1.67 7.1 7.4 7.8 8.1 22 22,000 24,700 1.68 1.75 7.4 7.7 8.2 8.5 23 23,000 25,800 1.76 1.83 7.8 8.0 8.6 8.9 24 24,000 26,900 1.85 1.91 8.2 8.4 9.0 9.3 25 25,000 28,000 1.94 1.98 8.6 8.7 9.5 9.6 26 26,000 29,200 2.04 2.06 9.0 9.1 9.9 10.0 27 27,000 30,300 2.14 2.15 9.4 9.4 10.4 10.4 28 28,000 31,400 2.24 2.23 9.9 9.8 10.9 10.8 29 29,000 32,500 2.35 2.31 10.4 10.2 11.5 11.2 30 30,000 33,700 2.46 2.40 10.9 10.5 12.0 11.7 31 31,000 34,800 2.58 2.48 11.4 10.9 12.6 12.1 32 32,000 35,900 2.70 2.57 11.9 11.3 13.2 12.5 33 33,000 37,000 2.82 2.66 12.5 11.7 13.8 12.9 34 34,000 38,200 2.95 2.75 13.0 12.1 14.4 13.4 35 35,000 39,300 3.08 2.84 13.6 12.5 15.1 13.8 36 36,000 40,000 3.22 2.93 14.2 12.9 15.7 14.2 37 36,200 40,200 3.23 2.92 14.3 12.9 15.8 14.2 38 36,400 40,400 3.25 2.89 14.3 12.7 15.9 14.1 39 36,600 40,700 3.26 2.86 14.4 12.6 15.9 13.9 40 36,900 40,900 3.27 2.84 14.5 12.5 16.0 13.8 41 37,100 41,100 3.28 2.81 14.5 12.3 16.0 13.6 42 37,300 41,300 3.30 2.78 14.6 12.2 16.1 13.5 43 37,500 41,600 3.31 2.75 14.6 12.1 16.2 13.4 44 37,700 41,800 3.32 2.72 14.7 11.9 16.2 13.2 45 37,900 42,000 3.34 2.69 14.7 11.8 16.3 13.1 46 38,100 42,200 3.35 2.66 14.8 11.7 16.4 12.9

Total capacity of Indoor units* Cooling Heating Cooling Heating Cooling Heating Cooling Heating 24 24,000 26,900 2.11 2.32 9.2 10.2 10.2 11.2 25 25,000 28,000 2.20 2.41 9.6 10.5 10.6 11.6 26 26,000 29,200 2.29 2.50 10.0 10.9 11.1 12.1 27 27,000 30,300 2.38 2.59 10.4 11.3 11.5 12.5 28 28,000 31,400 2.48 2.68 10.8 11.7 12.0 13.0 29 29,000 32,500 2.58 2.78 11.3 12.1 12.4 13.4 30 30,000 33,700 2.68 2.87 11.7 12.6 12.9 13.9 31 31,000 34,800 2.78 2.97 12.2 13.0 13.4 14.4 32 32,000 35,900 2.89 3.07 12.6 13.4 14.0 14.8 33 33,000 37,000 3.00 3.17 13.1 13.9 14.5 15.3 34 34,000 38,200 3.11 3.28 13.6 14.3 15.0 15.8 35 35,000 39,300 3.23 3.38 14.1 14.8 15.6 16.3 36 36,000 40,400 3.35 3.49 14.6 15.2 16.2 16.9 37 37,000 41,500 3.47 3.60 15.2 15.7 16.8 17.4 38 38,000 42,700 3.60 3.71 15.7 16.2 17.4 17.9 39 39,000 43,800 3.72 3.82 16.3 16.7 18.0 18.5 40 40,000 44,900 3.85 3.93 16.8 17.2 18.6 19.0 41 41,000 46,000 3.99 4.05 17.4 17.7 19.3 19.6 42 42,000 47,200 4.12 4.17 18.0 18.2 19.9 20.1 43 43,000 48,300 4.26 4.28 18.6 18.7 20.6 20.7 44 44,000 49,400 4.41 4.41 19.3 19.3 21.3 21.3 45 45,000 50,500 4.55 4.53 19.9 19.8 22.0 21.9 46 46,000 51,700 4.70 4.65 20.5 20.3 22.7 22.5 47 47,000 52,800 4.85 4.78 21.2 20.9 23.4 23.1 48 48,000 54,000 4.97 4.88 21.7 21.3 24.0 23.6 49 48,300 54,200 4.98 4.83 21.8 21.1 24.1 23.3 50 48,500 54,300 4.99 4.79 21.8 20.9 24.1 23.2 51 48,700 54,400 5.00 4.75 21.8 20.8 24.1 23.0 52 48,900 54,500 5.01 4.71 21.9 20.6 24.2 22.8 53 49,100 54,600 5.01 4.67 21.9 20.4 24.2 22.6 54 49,300 54,800 5.02 4.63 21.9 20.2 24.3 22.4 55 49,600 54,900 5.03 4.59 22.0 20.1 24.3 22.2 56 49,800 55,000 5.04 4.55 22.0 19.9 24.3 22.0 57 50,000 55,100 5.04 4.51 22.0 19.7 24.4 21.8 58 50,200 55,200 5.05 4.47 22.1 19.5 24.4 21.6 59 50,400 55,300 5.06 4.43 22.1 19.4 24.4 21.4 60 50,600 55,500 5.07 4.39 22.1 19.2 24.5 21.2 61 50,800 55,600 5.07 4.35 22.2 19.0 24.5 21.0 62 51,100 55,700 5.08 4.31 22.2 18.8 24.6 20.8

5-3-1. Correcting Changes in Air Conditions (1) The performance curve charts (Figure 1, 2) show the ratio by the temperature condition change when the rated capacity (total
capacity) and the rated input are presumed 1, under standard length (7.6 m [25 ft]) and standard temperature condition. • Standard conditions:
Indoor D.B. 26.7°C / W.B. 19.4°C [D.B.80°F / W.B.67°F] Outdoor D.B. 35°C [D.B.95°F] Indoor D.B. 21.1°C [D.B.70°F] Outdoor D.B. 8.3°C / W.B. 6.1°C [D.B.47°F / W.B.43°F]
(2) The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
individual capacity at the rated time Individual capacity under stated conditions = total capacity under the stated conditions o
total capacity at the rated time
(3) Capacity correction factor curve
Figure 1. Cooling performance curve
: DB(°FDB)
: WB(°FWB)
21.1 (70)
22 (71.6) 20 (68) 18 (64.4) 16 (60.8)
INDOOR
: WB(°FWB)
22 (71.6) 20 (68) 18 (64.4) 16 (60.8)
21.1 (70)
INDOOR
Cooling power consumption (ratio)
Heating power consumption (ratio)
0.4 -5 0 10 20 30 40 46 23 32 50 68 86 104 115
14 -5 23 0 32 5 41 10 50 15 59 °C WB °F WB
OUTDOOR


Heating P36, 48 models
70 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80[m]
[16] [33] [50] [70] [80] [100] [115] [130] [150] [165] [180] [195] [215] [230] [245] [260][ft]
Equivalent length for type P48 = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m) Length of piping to farthest indoor unit: 80 m [262 ft]
5-3-3. Correction of Heating Capacity for Frost and Defrosting If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction factor from the following table to obtain the actual heating capacity. Correction factor diagram
Outdoor Intake temperature (W.B.°F) 43 39 36 32 28 25 21 18 14 Outdoor Intake temperature (W.B.°C) 6 4 2 0 -2 -4 -6 -8 -10 Correction factor 1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95
MODE
LINE
PUMY-P48NHMU(-BS) PUMY-P48NHMU 1 (-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)
MODE
COOLING
HEATING
HEATING
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)


10 63 125 250 500 1000 2000 4000 8000
10 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
1m [3.3ft]
1.5m [4.9ft]


1 FREE SPACE (Around the unit) 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS
……Refrigerant LIQUID pipe connection (FLARE): 9.52 (3/8 inch)
……Refrigerant GAS pipe connection (FLARE):15.88 (5/8 inch)


1 FREE SPACE (Around the unit) 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS
……Refrigerant LIQUID pipe connection (FLARE):9.52 (3/8 inch)
……Refrigerant GAS pipe connection (FLARE):15.88 (5/8 inch)

SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 Terminal Block TB3 Terminal Block TB7 Terminal Block MC Motor for Compressor MF1,MF2 Fan Motor 21S4 Solenoid Valve SV1 Solenoid Valve TH3 Thermistor TH4 Thermistor TH6 Thermistor TH7 Thermistor TH8 Thermistor 63HS High Pressure Sensor 63H High Pressure Switch 63L Low Pressure Switch CB Main Smoothing Capacitor ACTM
MULTI.B. Multi Controller Board Fuse F1,F2
N.F. Noise Filter Circuit Board Connection Lead LI/LO
M-P.B.
Connector Transmission Power Board CN1
Connector CN2
Switch SWU1
Switch SWU2
Digital Indicator LED1,2
LED LED3
Active filter Module RS Rush Current Protect Resistor
Connector CNAC
P.B. Power Circuit Board Connection Terminal U/V/W
Connector CNDC
Connector CN2
Connector CN4
Connector CN40
Connector CN41
Connector 63HS Connector 63H Connector 63L Connector CNF1,CNF2
Light Emitting Diodes LED1
Connector 21S4 Connector SV1
Use copper supply wires.
! WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2 minutes (input voltage: 240 V).
When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then wait for at least 1 minute. Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual. Do not replace the outdoor board without checking.
During normal operation The LED indicates the drive state of the controller in the outdoor unit.
[Example] When the compressor and SV1 are turned during cooling operation.
1 2 3 4 5 6 7 8
SV1
(SV2)
When faults requiring inspection occurs The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.


1 2 1 2 1 2 3 4 CN3D (WHT) 1 2 3
SS (WHT) 2 1 2 1 2 1 2 1 3 1
1 2 1 2 1 2 1 2 3 4 5 6 7
MODELS
PUMY-P48NHMU
ON OFF 1 2 3 4 5 6
indicates a switch position. The black square ( )
DIP SW4-4 for primary heating control : Set DIP SW4-4 when power is turned off at unit. DIP SW4-4 OFF : Disable primary heating function (Initial setting) DIP SW4-4 ON : Enable primary heating function

SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 Terminal Block TB3 Terminal Block TB7 Terminal Block MC Motor For Compressor MF1,MF2 Fan Motor 21S4 Solenoid Valve
P.B. Power Circuit Board
Connection Terminal TABP1/P2/P
Switch SWU1
Connection Terminal Diode Bridge TABN1/N2/N
Switch SWU2
Connector (Symbol of Board is CNLVB) CNLVB
63H High Pressure Switch 63L Low Pressure Switch
N.F. Noise Filter Circuit Board Connection Terminal LI/LO
Connector SS
63HS High Pressure Sensor
Connector CN3D
SV1 Solenoid Valve TH3 Thermistor TH4 Thermistor TH6 Thermistor TH7 TH8
Connector CN3S
Connector CN3N
Connector CN51
C.B.
LED LED3 Controller Circuit Board
LED LED1,LED2
Fuse F1,F2 Switch SW1
CE Main Smoothing Capacitor ACTM DCL
Relay X501~505 M-NET P.B.
ConnectionTerminal M-NET Power Circuit Board TP1
[Example] When the compressor and SV1 are turned during cooling operation.
1 2 3 4 5 6 7 8
SV1
(SV2)


1 2 3 4 5 6 0 1 1 0 1 0 0 1 1 0 0 1

Address SW Address SW Address SW Address SW Address SW
Address SW Address SW Address SW Address SW Address SW
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Address SW Address SW Address SW Address SW Address SW
Address SW Address SW
PUMY has no 100ths digit switch.
The address automatically become
connected to each refrigerant
Outdoor unit 051-100
Indoor unit 001-050
Remote controller 101-200
A transmission wire must be
system (outdoor and indoor).
"100" if it is set as "01~50".
Set addresses:

8-2. REFRIGERANT SYSTEM DIAGRAM PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)
Refrigerant flow in cooling Refrigerant flow in heating
Pressure sensor (63HS) High pressure switch(63H)
Thermistor(TH6)
Check valve
Thermistor(TH3) (Pipe temperature) Oil separator
Discharge thermistor(TH4) Compressor thermistor(TH4) (P36NHMUR1,P48NHMUR3)
Capillary tube (for oil separator) : :2.5 % :0.8 % L1000(mm) [:(3/32) % :(1/32) % L(39-1/2)] inch
Capacity Item Liquid piping Gas pipng
:6.35
:12.7
:9.52
:15.88
:9.52
:15.88

8-3. SYSTEM CONTROL 8-3-1. Example for the System • Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed in the standard system with detailed explanation. The explanation for the system in this section : Use one single outdoor unit and multiple outdoor units for M-NET remote control system.
Use one single outdoor unit and multiple indoor units in the multiple outdoor units for the M-NET remote control system.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cables Wiring Method and Address Setting
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non- polarized 2 wire. b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) for each indoor unit with the terminal block (TB6) for the remote controller (RC). c. Set the address setting switch (on outdoor unit P.C.B)
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S A B
S M1M2
M1M2
as shown below.
Unit Indoor unit (IC)
Range 001 to 050
— Use the smallest address of all the indoor unit plus 50. Indoor unit address plus 100.
(OC)
a. Same as above. b. Same as above. c. Set address switch (on outdoor unit P.C.B) as
shown below.
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
Unit Indoor Unit (IC)
Range 001 to 050
S A B
S M1M2
M1M2
— Use the smallest address of all the indoor units plus 50. Indoor unit address plus 100. Indoor unit address plus 150.
Main Remote Controller (RC)
Sub Remote Controller (RC)
a. Same as above. b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most recent address within the same indoor unit (IC) group to terminal block (TB6) on the remote controller. c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Range 001 to 050
Setting Method Use the smallest address within the same group of indoor units. Use an address, other than that of the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main).
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S A B
S M1M2
M1M2
Use the smallest address of all the indoor units plus 50. Set at an IC (Main) address within the same group plus 100. Set at an IC (Main) address within the same group plus 150. d. Use the indoor unit (IC) within the group with the
most functions as the IC (Main) unit.
Combinations of 1 through 3 above are possible.

Name Symbol Maximum units for connection Outdoor unit OC — Indoor unit IC One OC unit can be connected to 1-6 (P36)/1-8 (P48) IC units M-NET remote controller RC Maximum 2 RC for 1 indoor unit, Maximum 16 RC for 1 OC
Permissible Lengths Prohibited items
Longest transmission cable length (1.25 mm2 [AWG16]) L1 + L2, L2 + L3, L3 + L1 [ 200m [656ft] Remote controller cable length 1. If 0.5 to 1.25 mm2
[AWG20 to AWG16] R1, R2 [10m [33ft] 2. If the length exceeds 10 meters [33ft], the exceeding section should be 1.25 mm2 [AWG16] and that section should be a value within the total extension length of the transmission cable and maximum transmission cable length. (L3)
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S A B
S M1M2
M1M2
A B
A B
TB15
MA
RC
OC
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S A B
S M1M2
M1M2
A B A B A B A B A B
OC
TB3
TB7
TB5
TB15
TB5
TB15
M1M2
S A B
S M1M2
M1M2
S 1 2
S 1 2
RC

B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller. (Shielding wires and address settings are necessary.)
TB3
TB5
TB5
TB5
TB5
M1M2 S M1 M2 S
TB7
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
N
N
N
Examples of Transmission Cable Wiring
RC
RC
RC
OC
TB3
TB5
TB5
TB5
M1 M2 S
M1M2 S
M1 M2 S
M1 M2 S
M1 M2 S
TB7
L 6 L 7
M1M2S
N
DV 12V
G-50A
A B
M1M2S
RC
: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals. b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC). c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC). d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit
Wiring Method Address Settings
(OC). e. DO NOT change the jumper connector CN41 on MULTI controller board. f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary.
Connect the terminal S on the power supply unit with the earth. g. Set the address setting switch as follows.
Unit Range Setting Method IC (Main) 01 to 00 Use the smallest address within the same group of indoor units.
IC (Sub) 01 to 50 Use an address, other than that of the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main).
Outdoor Unit 51 to 100 Use the smallest address of all the indoor units plus 50. *The address automatically becomes “100” if it is set as “01 - 50”. Main Remote Controller 101 to 150 Set at an IC (Main) address within the same group plus 100. Sub Remote Controller 151 to 200 Set at an IC (Main) address within the same group plus 150. MA Remote Controller — Unnecessary address setting (Necessary main/ sub setting)
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical
power has been turned on.

Permissible Length Prohibited items
TB3
M1M2 S M1 M2 S
M1 M2 S
TB5
M1 M2 S
TB5
M1 M2 S
TB5
M1 M2 S
TB5
TB7
A B A B A B
RC
RC
RC
OC
TB3
M1M2 S
TB5
TB5
TB5
M1 M2 S
TB7
M1 M2 S
M1 M2 S
M1 M2 S
M1M2S
DV 12V
A B
G-50A
M1M2S
RC
: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address

C. Example of a MA remote controller system (address setting is not necessary.) NOTE : In the case of same group operation, need to set the address that is only main indoor unit.
Example of wiring control cables Wiring Method and Address Setting
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non- polarized 2 wire. b. Connect terminals 1 and 2 on transmission cable
OC
terminal block (TB15) for each indoor unit with the terminal block for the MA remote controller (MA).
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S M1M2
S M1M2
M1M2
N 2
N 1
A B
A B
MA MA
a. The same as above. b. The same as above. c. In the case of using 2 remote controllers, connect
terminals 1 and 2 on transmission cable terminal block (TB15) for each indoor unit with the terminal block for 2 remote controllers. · Set the sub remote controller position for one of MA remote controller’s main switch. Refer to the installation manual of MA remote con-
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S M1M2
S M1M2
M1M2
N 4
N 6
N 3
N 5
A B
A B A B
A B
MA
MA MA
a. The same as above. b. The same as above. c. Connect terminals 1 and 2 on transmission cable ter-
minal block (TB15) of each indoor unit, which is doing group operation with the terminal block the MA remote controller. Use non-polarized tow wire. d. In the case of same group operation, need to set the
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S M1M2
S M1M2
M1M2
address that is only main indoor unit. Please set the address of the indoor unit with the most functions in the same group in the number that 01-50 is young.
A B
N 8
Combinations of 1 through 3 above are possible.
troller

Permissible Lengths Prohibited items
Longest transmission cable length L1 + L2 [ 200 m [656 ft] (1.25 mm2 [AWG16]) MA remote controller cable length R1, R2 [ 200 m [656 ft]
The MA remote controller and the M-NET remote controller cannot be used together with the indoor unit of the same group.
(0.3 – 1.25 mm2 [AWG22 to AWG16])
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S M1M2
S M1M2
M1M2
A B
A B
A B
RC
MA MA
Longest transmission cable length The same as above. MA remote controller cable length R3 +R4, R5 +R6 [ 200 m [656 ft]
Three MA remote controller or more cannot be connect with the indoor unit of the same group.
(0.3 – 1.25 mm2 [AWG22 to AWG16])
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S M1M2
S M1M2
M1M2
A B A B
A B
A B A B
MA MA MA
MA
MA
Longest transmission cable length The same as above. MA remote controller cable length R7 +R8 [ 200 m [656 ft]
The second MA remote controller is connected with the terminal block (TB15) for the MA remote controller of the same indoor unit (IC) as the first remote control.
(0.3 – 1.25 mm2 [AWG22 to AWG16])
TB3
TB7
TB5
S 1 2 TB15
TB5
S 1 2 TB15
M1M2
S M1M2
S
M1M2
M1M2
A B
A B
MA
MA

D. Example of a group operation with 2 or more outdoor units and a MA remote controller.
(Shielding wires and address settings are necessary.)
TB3
M1 M2 1 2 S TB5 TB15
TB5
1 2 TB15
TB5
1 2 TB15
TB5
1 2 TB15
M1 M2 S
M1M2 S
M1 M2 S
M1 M2 S
M1 M2 S
TB7
Examples of Transmission Cable Wiring
MA
MA
MA
OC
TB3
TB5
1 2 TB15 1 2 TB15
TB5
1 2 TB15
TB5
M1 M2 S
M1M2 S
M1 M2 S
M1 M2 S
M1 M2 S
TB7
L 6 L 7
M1M2
S
DV 12V
A B
G-50A
M1M2
S
MA
: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals. b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC). c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC). d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit
Wiring Method Address Settings
(OC). e. DO NOT change the jumper connector CN41 on MULTI controller board. f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary.
Connect the terminal S on the power supply unit with the earth. g. Set the address setting switch as follows.
Unit Range Setting Method IC (Main) 01 to 00 Use the smallest address within the same group of indoor units.
IC (Sub) 01 to 50 Use an address, other than that of the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main).
Outdoor Unit 51 to 100 Use the smallest address of all the indoor units plus 50. *The address automatically becomes “100” if it is set as “01 - 50”. Main Remote Controller 101 to 150 Set at an IC (Main) address within the same group plus 100. Sub Remote Controller 151 to 200 Set at an IC (Main) address within the same group plus 150. MA Remote Controller — Unnecessary address setting (Necessary main/ sub setting)
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical
power has been turned on.

Permissible Length Prohibited items
Longest length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6+L7 500 m [1640ft] (1.25 mm2
[AWG16] or more) Longest transmission cable length (M-NET cable): L1 and L3+L4 and L6 and L2+L6 and L7 200 m [656ft] (1.25 mm2 [AWG16] or more) Remote controller cable length: m1 and m1+m2+m3 and m1+m2+m3+m4 200 m [656ft] (0.3 to 1.25 mm2
[AWG20 to AWG16] )
M1 M2 1 2 S TB5 TB15
TB5
1 2 TB15
TB5
1 2 TB15
TB5
1 2 TB15
M1 M2 S
M1M2 S
M1 M2 S
M1 M2 S
M1 M2 S
TB7
A B A B A B
MA
MA
MA
OC
TB3
TB5
1 2 TB15 1 2 TB15
TB5
1 2 TB15
TB5
M1 M2 S
M1M2 S
M1 M2 S
M1 M2 S
M1 M2 S
TB7
M1M2
S
DV 12V
G-50A
A B
M1M2
S
MA
: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address

(1) Before test run, make sure that following work is completed.
With the insulation tester of 500V, inspect the insulation resistance. Do not touch the transmission cable and remote controller cable with the tester. The resistance should be over 1.0 MΩ. Do not proceed inspection if the resistance in under 1.0 MΩ. Inspect between the outdoor unit power supply terminal block and ground first, metallic parts like refrigerant pipes or the electrical box next, then inspect all electrical wiring of outdoor unit, indoor unit, and all linked equipment . (3) Before operation :
a) Turn the power supply switch of the outdoor unit to on for compressor protection.For a test run, wait at least 12 hours from this point. b) Register control systems into remote controller(s). Never touch the on/ off switch of the remote controller(s). Refer to “ 9-1-2. Special
Function Operation and Settings (for M-NET Remote Controller)” as for settings . In MA remote controller(s), this registration is unneces- sary. (4) More than 12 hours later from power supply to the outdoor unit, turn all power switch to on for test run. Perform test run according to the
“Operation procedure” table of the bottom of this page. While test running, make test run reports . (5) When you deliver the unit after test run, instruct the end user for proper usage of the system using owners’ manual and the test run report
you made to certificate normal operation. If abnormalities are detected during test run, refer to “ 9-1-3. Countermeasures for Error During Test Run”. As for DIP switch setting of outdoor unit, refer to” 9-5. INTERNAL SWITCH FUNCTION TABLE”.
Check code indicator (see NOTE 1) Test run remaining time indicator (see NOTE 2)
Indoor unit liquid pipe temperature indicator
°C 1Hr.
TEMP.
ON/OFF button ON/OFF LED (Lights up in operation)
(Cooling/Heating) OPERATION SWITCH button ,
FILTER
AIR DIRECTION button
TIMER SET
AIR SPEED button
Operation procedure 1 Turn on the main power supply of all units at least 12 hours before test run. ”HO” appears on display panel for 3 min. 2 12 hours later, press TEST RUN button twice to perform test run. “TEST RUN “ appears on display panel. 3 Press OPERATION SWITCH button to make sure that air blows out. 4 Select Cooling (or Heating) by OPERATION SWITCH button to make sure that cool (or warm) air blow out. 5 Press Fan speed button to make sure that fan speed is changed by the button. 6 Press AIR DIRECTION button or LOUVER button to make sure that air direction is adjustable (horizontal, downward, upward, and each angle). 7 Check outdoor fans for normal operation 8 Check interlocked devices (like ventilator) for normal operation, if any. This is the end of test run operation. 9 Press ON/OFF button to stop and cancel test run.
NOTE 1 : If error code appears on remote controller or remote controller malfunction , refer to “ 9-1-3. Countermeasures for Error During Run”. NOTE 2 : During test run operation 2-hours off timer activates automatically and remaining time is on remote controller and test run stops 2 hours later. NOTE 3 : During test run, the indoor liquid pipe temperature is displayed on remote controller instead of room temperature. NOTE 4 : Depend on a model, “This function is not available” appears when air direction button is pressed, however, this is not malfunction.

9-1-2. Special Function Operation and Settings (for M-NET Remote Controller) • It is necessary to perform “group settings” and “paired settings” at making group settings of different refrigerant systems (multiple outdoor unit). (A) Group settings: Enter the indoor unit controlled by the remote controller, check the content of entries, and clear entries, etc. (B) Paired settings: Used to set the linked operation of a Lossnay unit. (1) Entering address: Follow the steps below to enter the addresses of the indoor unit using the remote controller.
Figure 1. (A) Group setting display Figure 2. Normal completion of entry Figure 3. Entry error signal
Flashing “88” indicates entry error. Type of unit is displayed.
Figure 4. (B) Making paired settings Figure 5. Completing normal entry
These alternating IC or LC displays will appear when entry is completed normally.
The addresses of indoor unit and linked units are displayed simultaneously.
A flashing “88” will appear if there is a problem with the entry (indicating that the unit does not exist).
(alternating display)

(2) Address check: Refer to section (1) regarding address entry.
(3) Clearing an address: Refer to section (1) regarding the address entry and section (2) regarding checking addresses. a) In making group settings:
Figure 7. Display when an abnormality has
occurred during clearing Figure 6. Display after address has been
"88" will appear in the room temperature display location. "--" will appear in the room temperature display location.
Figure 8. Display after address has been cleared normally
"--" will appear in the unit type display location when an address has been cleared normally.
"88" will appear in the unit type display location when an abnormality has occurred during clearing.
cleared normally · (altenating display)

Trouble Remarks Detected unit
Outdoor unit Multi controller board ~ Power board communiation trouble Check delay code 1202 Check delay code 1400 Check delay code 1402 Check delay code 1600 Check delay code 1601
Discharge/Compressor temperature trouble Low pressure trouble High pressure trouble Excessive refrigerant replenishment Insufficient refrigerant trouble Vacuum operation protection Water leakage Drain pump trouble Drain sensor trouble (THd) Overcurrent trouble (Overload, compressor lock) Power synchronization signal trouble Inverter trouble Overheat protection of radiator panel Power module trouble or Overcurrent trouble Fan controller trouble (Outdoor) Air inlet sensor trouble (TH21) or Discharge/Compressor temperature sensor trouble (TH4) Liquid pipe temp.sensor trouble (TH22) or Low pressure saturated temp.sensor trouble (TH6) Gas pipe temperature sensor trouble (TH23) Piping temperature sensor trouble (TH3) Outdoor temperature sensor trouble (TH7) Heatsink temperature sensor trouble (TH8) Pressure sensor trouble (63HS) Curnent sensor trouble Contact failure of drain float switch Dupricated unit address setting Transmission error (Transmission processor hardware error) Transmission error (Transmission route BUSY) Transmission and reception error (Communication trouble with transmission processor) Transmission and reception error (No ACK error) Transmission and reception error (No responsive frame error) MA communication receive signal error (no receive signal) MA commnication send signal error (starting bit derection error) MA commnication send error (H/W error) MA commnication receive error (Synchronous recovery error) Total capacity error Capacity code error Connecting unit number error Address set error Remote controller sensor trouble
1302 1500 1501 1505
Check delay code 4350 Check delay code 4165 Check delay code 4320 Check delay code 4330 Check delay code 4350 Check delay code 4500
4115 4220 4230 4250
Check delay code 1202
Check delay code 1211
5103 5105 5106 5110 5201
Check delay code 1205 Check delay code 1221 Check delay code 1214 Check delay code 1402 Check delay code 4310
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected. +
Only M-NET Remote controller is detected. +
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
7100 7101 7102 7105 7111
When the outdoor unit detects No ACK error/ No responsive frame error, an object indoor unit is treated
as a stop, and not assumed to be abnormal.
Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF. During normal operation The LED indicates the drive state of the controller in the outdoor unit.
[Example] When the compressor and SV1 are turned during cooling operation.
1 2 3 4 5 6 7 8
SV1
(SV2)

Display Abnormal point and detecting method Causes Check points
High discharging/compressor temperature Abnormal if discharge/compressor temperature thermistor (TH4) exceeds 125 [257°F] or 110 [230°F] continuously for 5 minutes. Abnormal if pressure detected by high pressure sensor and converted to saturation temperature exceeds 40 [104°F] during defrosting and discharge/compressor temperature thermistor (TH4) exceeds 110 [230°F] .
Over-heated compressor operation caused by shortage of refrigerant Defective operation of stop valve Defective thermistor Defective outdoor controller board Defective action of linear expansion valve
Check intake super heat. Check leakage of refrigerant. Charge additional refrigerant. Check if stop valve is fully open. Turn the power off and check if 5101 is displayed when the power is turned again. When 5101 is displayed, refer to “Check points” for 5101. Check linear expansion valve.
Low pressure (63L operated) Abnormal if 63L is operated (under- 0.03MPa [-4.35PSIG]) during compressor operation. 63L: Low-pressure switch
Stop valve of outdoor unit is closed during operation. Disconnection or loose connection of connector (63L) on outdoor controller board Disconnection or loose connection of 63L Defective outdoor controller board Leakage or shortage of refrigerant Malfunction of linear expansion valve Short cycle of indoor unit Clogged filter of indoor unit Decreased airflow caused by dirt of indoor fan Dirt of indoor heat exchanger Locked indoor fan motor Malfunction of indoor fan motor Defective operation of stop valve (Not fully open) Clogged or broken pipe Locked outdoor fan motor Malfunction of outdoor fan motor Short cycle of outdoor unit Dirt of outdoor heat exchanger Decreased airflow caused by defective inspection of outside temperature thermistor (It detects lower temperature than actual temperature.) Disconnection or contact failure of connector (63H) on outdoor controller board Disconnection or contact failure of 63H connection Defective outdoor controller board Defective action of linear expansion valve Malfunction of fan driving circuit Solenoid valve (SV1) performance failure (High-pressure cannot be controlled by SV1.) High-pressure sensor defective High-pressure sensor input circuit defective in multi controller board
Check stop valve.
~ Check the connector (63L) on outdoor controller board.
Correct to proper amount of refrigerant. Check linear expansion valve. ~ Check indoor unit and repair defectives.
(1) High pressure (High-pressure switch 63H operated) Abnormal if high-pressure switch 63H operated ( + ) during compressor operation. + 4.15 MPa [602PSIG]
Check if stop valve is fully open.
(2) High pressure (High - pressure sensor 63HS detect) Abnormal if high-pressure sensor detects 4.31MPa [625PSIG] or more (or over 4.15MPa [602PSIG] for 3 minutes) during the compressor operation.
Check piping and repair defectives. ~ Check outdoor unit and repair defectives.
Check the inspected temperature of outside temperature thermistor on LED display.
~ Check the connector (63H) on outdoor controller board.
Check linear expansion valve.
Replace outdoor controller board. Check the solenoid valve performance.
Check the high-pressure sensor. Check the high-pressure sensor.
Superheat due to low discharge temperature
Disconnection or loose connection of discharge/compressor temperature thermistor (TH4) Defective holder of discharge temperature thermistor
Check the compressor installation conditions of discharge temperature thermistor (TH4).
Abnormal if discharge superheat is continuously detected less than or equal to -15 [-27°F] even though linear expansion valve has minimum open pulse after compressor starts operating for 10 minutes.

Display Abnormal point and detecting method Causes Check points
Refrigerant shortage When the conditions of below detecting mode or are satisfied during the compressor operation.
Gas leakage, Gas shortage When heating operation, refrigerant shortage feeling operation (When heating, airflow or thermo OFF are mixed-operation, it causes a refrigerant shortage operation.) Ball valve performance failure (not full opened.) Error detection of discharge superheat 1) High-pressure sensor defective 2) Discharge temperature thermistor defective 3) Thermistor input circuit defective and high-pressure sensor defective in multi controller board
Check the refrigerant amount.
Check the operation condition and refrigerant amount.
When the below conditions are satisfied completely. 1. Compressor is operating in HEAT mode. 2. Discharge superheat is 80 [144°F] or more. 3. Difference of outer temperature thermistor (TH7) and outdoor piping temp. thermistor (TH3) applies to the formula of (TH7-TH3)
Check the ball valve is fully open.
According to “Outdoor unit functions”, check the discharge temp. thermistor level. When the high-pressure sensor and discharge temp. thermistor are normal, if the above mentioned detecting pressure level and temp. are big different from the actual pressure and temp. replace the multi controller board. 1) Check the resistance of thermistor.
Error detection of TH7/TH3 1) Thermistor defective
Check the drain function.
2500 (Float switch model)
Water leakage 1. Suspensive Abnormality when float switch detects to be in the water and drain pump turns on and off except during cooling or dry mode. 2. Abnormal when detecting that the drain pump turns on and off again within 1 hour after the detection of water leakage suspensive abnormality, and repeats the detection twice. is displayed. 3. The unit continues to detect abnormality while turned off. 4. To release water leakage suspensive abnormality · When not detecting that the drain pump turns off and on within 1 hour after detecting suspensive abnormality. · When turning to cooling operation or dry operation. · Detected that [liquid pipe temperature – room temperature] -10deg[-18°F]
Defective drain Clogged drain pump Clogged drain pipe Adverse flow of drain in other units Defective moving part of float switch Foreign matter on the moving part of float switch(ex. sludge etc.) Defective float switch
Check moving part of float switch.
Check the value of resistance with the float switch ON/OFF.
Operation mode: When drain pump turns on as float switch detects to be in the water except during cooling/dry mode
6 min. 6 min.
OFF
OFF
15 sec.
15 sec.
15 sec. 15 sec. 15 sec.
In the water Water leakage suspensive abnormality
In the water Water leakage abnormality In the air In the water In the air
Within 1 hour Within 1 hour
Drain pump · Float switch ON

Display Abnormal point and detecting method Causes Check points
2502 (Drain sensor model)
Drain pump (DP) Drain sensor thermistor is heated, and when
Check if drain pump works. Check drain function.
only a fraction of the temperature rise is detected, the system determines abnormality to defer the error to stop operation and changes to protection mode to restart the system in 3 minutes. Drain pump is abnormal if the condition above is detected during suspensive abnormality. is displayed. Malfunction of drain pipe is constantly detected during drain pump operation.
Check the setting of lead wire of drain sensor and check clogs of the filter.
Replace indoor controller board when there is no problem in the above mentioned ~ .
Both of above mentioned ~ and the indoor linear expansion valve full-closed failure (leakage) happens synchronistically.
Check whether the indoor linear expansion valve leaks or not.
The unit enters to forced outdoor unit stop when following conditions, a) and b), are satisfied (while the above mentioned detection is performed). a) The drain sensor detects to be soaked in the water 10 times in a row. b) The room teperature subtracted with liquid pipe temperature is detected to be less than -10[-18°F] continuously for 30 minutes. When the drain sensor detects to be NOT soaked in the water, the detection record of a) and b) will be cleared.) + Drain pump abnormality (above ~ ) is detected before it becomes an outdoor unit forced stop condition. When indoor unit detects above condition, outdoor unit in same refrigerant sytem stops. Also, indoor unit except for Fan or OFF mode unit stop. 2502 is displayed on stopped unit. Detection timing of forced outdoor unit stop
(Note) Address/Attribute displayed on the remote controller shows the indoor unit which is cause of trouble.
Constantly detected during unit operation and stop Releasing of forced outdoor unit stop Reset power supply of both abnormal indoor unit and its outdoor unit in same refrigerant system. Forced outdoor unit stop cannot be released by remote controller OFF. NOTE ) Above-mentioned ~ and ~ are detected independently.

Display Abnormal point and detecting method Causes Check points
2502 (Float switch model)
Drain pump (DP) Judge whether the sensor is in the water or in the air by turning the float switch ON/OFF. In the water: Detected that the float switch is ON for 15 seconds. In the air:Detected that the float switch is OFF for 15 seconds. When the float switch remains to be turned ON for 3 minutes after detected to be in the water, the drain pump is judged to be abnormal and will be displayed. *It takes 3 minutes and 15 seconds to detect abnormality including the time to judge to be in the water.
Malfunction of drain pump Defective drain Clogged drain pump Clogged drain pipe Defective moving part of float switch Foreign matter on the moving part of float switch(ex. sludge etc.) Defective float switch
Check if drain pump works. Check drain function.
Check moving part of float switch.
Check the value of resistance with the float switch ON/OFF. Change the indoor controller board.
Defective indoor controller board Defective driving circuit of drain pump Defective input circuit of float switch
The unit continue to detect abnormality while turned off. When the conditions below 1, 2 and forced
Check whether the indoor linear expansion valve leaks or not. Both of above mentioned ~ and the indoor linear expansion valve full-closed failure (leakage) happens synchronistically.
outdoor unit stop condition are met 1. Detected that [liquid pipe temperature – room temperature] -10deg[-18°F] for 30 minutes constantly. 2. Float switch detects to be in the water for 15 minutes constantly. *Before Forced outdoor unit stop Condition is met, the unit always detects - above. The indoor unit detecting above stops due to detecting abnormality the outdoor unit in same refrigerant system (compressor is inhibited to operate). The unit which stops due to detecting abnormality displays . Detection timing of forced outdoor unit stop Constantly detected during unit operation and stop Releasing of forced outdoor unit stop Reset power supply of both abnormal indoor unit and its outdoor unit in same refrigerant system. Forced outdoor unit stop cannot be released by remote controller OFF.
(Note) Address/Attribute displayed on the remote controller shows the indoor unit which is cause of trouble.
Drain sensor (THd, DS) When the drain sensor detects short/open while the operation.
Connector (CN31) contact failure (insertion failure)
Check whether the indoor controller board connector (CN31) is disconnected or not. Check whether the thermistor wiring is disconnected or not. Check the resistance of thermistor. If abnormality is not found in the method of the above-mentioned from to , it is defective of the indoor controller board.
Thermistor wiring disconnection or half disconnection Thermistor defective Indoor controller board (detecting circuit) failure
Compressor overcurrent interruption (When compressor locked) Abnormal if overcurrent of DC bus or compressor is detected within 30 seconds after compressor starts operating.
Open stop valve. Check facility of power supply. Correct the wiring (U·V·W phase) to compressor. Check compressor. Replace outdoor power circuit board.
Stop valve is closed. Decrease of power supply voltage Looseness, disconnection or converse of compressor wiring connection Defective compressor Defective outdoor power board

Display Abnormal point and detecting method Causes Check points
4220 Decrease of power supply voltage Disconnection of compressor wiring Defective 52C Defective ACT module Disconnection or loose connection of CN5 on the outdoor power circuit board Defective 52C drive circuit of outdoor power circuit board Disconnection or loose connection of CN2 on the outdoor power circuit board Defective ACT module drive circuit of outdoor controller circuit board Disconnection or loose connection of CNAF
Overvoltage or voltage shortage
Check the facility of power supply. Correct the wiring (U·V·W phase) to
Abnormal if any of followings are detected during compressor operation;
compressor. (Outdoor power circuit board). P48NHMU(1)(-BS) : Replace 52C.
Replace noise filter circuit board
(Including 52C) Replace ACT module.
(Refer to 9-9. Test point ; the item of ACTM) Check CN5 wiring on the outdoor power
circuit board. Replace outdoor power circuit board.
Check CN2 wiring on the outdoor power
circuit board. Replace outdoor power circuit board. Check CNAF wiring. The 4220 error history can be confirmed
2 1 3 4 5 6 7 8
with SW1 No.189.
(Refer to 9-9. Test point ; the item of ACTM)
In PUMY models, bus voltage is controlled using ACTM. If ACTM is failed, bus voltage becomes uncontrollable and stops abnormally. To check the normality of operation, see DC bus voltage SW1 9-10. No.45, or determine DC bus voltage of the both sides of condenser C510 or CNDC connector which is on Multi controller board using a tester.
Tester check The voltage (DC) of the condenser C510 or CNDC connector which is on Multi controller board
ACTM condition DC bus voltage
Normal Target voltage 340-350V (DC)
Failure / no operation Less than 310V (DC) or over 400V (DC)
stopping (Including constraint electric continuity) and for 10 seconds after the compressor start to operate. When bus voltage is abnormal, see the table above (1.Check point) and check such as input voltage, wiring, 52C relay. To check ACTM itsef, see 9-9. Test point ; the item of ACTM. In case of ACTM failure, also check if there is the breaking of a wire in rush current protect resistor. As for PUMY-P48NHMU(1)(-BS), rush current protect resistor is resistor RS (not mounted on the board). For PUMY-
P36NHMU/NHMUR1(-BS), P48NHMU2,/NHMUR3(-BS) resistor RS1 is mounted on noise filter circuit board.
Temperature of heatsink Abnormal if heat sink thermistor(TH8) detects temperature indicated below 85 [185°F]
The outdoor fan motor is locked. Failure of outdoor fan motor Airflow path is clogged. Rise of ambient temperature
Check outdoor fan.
Check air flow path for cooling. Check if there is something which causes temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46 [115°F].) Turn off power, and on again to check if 4230 is displayed within 30 minutes. Check thermistor temperature by microprocessor. Replace outdoor power circuit board.
Defective input circuit of outdoor power circuit board Failure of outdoor fan drive circuit
Replace outdoor controller circuit board.
(1) Power module Check abnormality by driving power module in case overcurrent is detected.
Outdoor stop valve is closed. Decrease of power supply voltage Looseness, disconnection or converse of compressor wiring connection
Open stop valve. Check facility of power supply. Correct the wiring (U·V·W phase) to compressor. (Outdoor power circuit board). Check compressor. Replace outdoor power circuit board.
Defective compressor Defective outdoor power circuit board
Contimued on the next page.
on · Defective thermistor

From the previous page.
Display Abnormal point and detecting method Causes Check points
(2) Compressor overcurrent interruption Abnormal if overcurrent DC bus or compressor is detected after compressor starts operating for 30 seconds.
Stop valve of outdoor unit is closed. Decrease of power supply voltage Looseness, disconnection or converse of compressor wiring connection Defective fan of indoor/outdoor units Short cycle of indoor/outdoor units Defective input circuit of outdoor controller board
Open stop valve. Check facility of power supply. Correct the wiring (U·V·W phase) to
compressor. (Outdoor power circuit board) Check indoor/outdoor fan. Solve short cycle. Replace outdoor controller circuit board.
Check compressor Before the replacement of the outdoor controller circuit board, disconnect the wiring to compressor from the outdoor
power circuit board and check the output voltage among phases, U, V, W, during test run (SW7-1 ON). No defect on board if voltage among phases (U-V, V-W and W-U) is same. Make sure to perform the voltage check with same performing frequency.
Outdoor fan motor Abnormal if rotational frequency of the fan motor is not detected during DC fan motor operation. Fan motor rotational frequency is abnormal if; • 100 rpm or below detected continuously
Failure in the operation of the DC fan motor
Check or replace the DC fan motor.
Failure in the outdoor circuit controller board
Check the voltage of the outdoor circuit controller board during operation.
for 15 seconds at 20 [68°F]: or more
Replace the outdoor circuit contrlooer board. (when the failure is still indicated even after performing the remedy 1 above.)
outside air temperature • 50 rpm or below or 1500 rpm or more
detected continuously for 1 minute.
Room temperature thermistor (TH21) When controller detects short (high temp.)/open (low temp.) in thermistor during the operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. In this time, is displayed. Then, if the thermistor recover in 3 minutes, it operates normally.
Check whether the connector (CN20) in the indoor controller board is connected or not.
Connector (CN20) contact failure
Check whether the thermistor wiring is disconnected or not.
Thermistor wiring disconnection or half disconnection
Check the resistance of thermistor;
0 [32°F] 15k 10 [50°F] 9.6k 20 [68°F] 6.3k 30 [86°F] 4.3k 40 [104°F]··· 3.0k
When there is no problem in above mentioned , replace the indoor controller board.
Detecting circuit failure in the indoor controller board
Discharge/Compressor temperature thermistor (TH4)
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
Connector (TH4) contact failure Check whether the connector (TH4) in the multi controller board is connected or not.
When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.
Thermistor wiring disconnection or half disconnection
Check whether the thermistor wiring is disconnected or not.
For 10 minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, above-mentioned short/open are not detected.
Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor. 0 [32°F] about 700k 10 [50°F] about 410k 20 [68°F] about 250k 30 [86°F] about 160k 40 [104°F]··· about 104k
Short: 216 [421°F] or more (1k) Open: 0 [32°F] or less (700k)
2 1 3 4 5 6 7 8
Set the SW1 to
When the temperature in multi controller board is not an actual temperature, replace the multi controller board.
Defective compressor · Thermistor failure · on

Display Abnormal point and detecting method Causes Check points
5102 Liquid pipe temperature thermistor (TH22)
When the thermistor detects short/open during the operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. In this time, is displayed. Then, if the thermistor recover in 3 minutes, it operates normally.
Connector (CN21 or CN44) contact failure
Check whether the connector (CN21 or CN44) in the indoor controller board is connected or not.
Thermistor wiring disconnection or half disconnection
Check whether the thermistor wiring is disconnected or not.
Check the resistance of thermistor;
0 [32°F] 15k
10 [50°F] 9.6k
20 [68°F] 6.3k
30 [86°F] 4.3k
40 [104°F] ···3.0k
Detecting circuit failure in the indoor controller board
When there is no problem in above mentioned , replace the indoor controller board.
Low pressure saturation temperature thermistor (TH6)
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
Connector (TH6) contact failure Check whether the connector (TH6) in the multi controller board is connected or not.
When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.
Thermistor wiring disconnection or half disconnection
Check whether the thermistor wiring is disconnected or not.
For 10 minutes after starting compressor, heating mode, above-mentioned short/open are not detected.
Thermistor failure Check the resistance of thermistor;
0 [32°F] 15k
10 [50°F] 9.6k
20 [68°F] 6.3k
30 [86°F] 4.3k
40 [104°F]···3.0k
2 1 3 4 5 6 7 8
Multi controller board input circuit failure
Set the SW1 to
When the temperature in multi controller board is not an actual temperature, replace the multi controller board.
on

Display Abnormal point and detecting method Causes Check points
5103 Gas pipe temperature thermistor (TH23)
When the thermistor detects short/open after 3minutes-continuous thermo ON during cooling or dry operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. In this time, is displayed. Then, if the thermistor recovers in 3 minutes, it operates normally.
Connector (CN29 or CN44) contact failure
Check whether the connector (CN29 or CN44) in the indoor controller board is connected or not.
Thermistor wiring disconnection or half disconnection
Check whether the thermistor wiring is disconnected or not.
Thermistor failure Check the resistance of thermistor;
0 [32°F] 15k
10 [50°F] 9.6k
20 [68°F] 6.3k
30 [86°F] 4.3k
40 [104°F]···3.0k
Detecting circuit failure in the indoor controller board
When there is no problem in above mentioned , replace the indoor controller board.
5105 Pipe temperature / judging defrost thermistor (TH3)
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
Connector (TH3) contact failure Check whether the connector (TH3) in the multi controller board is connected or not.
When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.
Thermistor wiring disconnection or half disconnection
Check whether the thermistor wiring is disconnected or not.
Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.
For 10 minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, above-mentioned short/open are not detected.
0 [32°F] 15k
10 [50°F] 9.6k
20 [68°F] 6.3k
30 [86°F] 4.3k
40 [104°F]···3.0k
2 1 3 4 5 6 7 8
Multi controller board input circuit failure
Set the SW1 to When the temperature in multi controller board is not an actual temperature, replace the multi controller board.
on

Display Abnormal point and detecting method Causes Check points
5106 Outdoor temperature thermistor (TH7)
Connector (TH7) contact failure Check whether the connector (TH7)
in the multi controller board is connected or not. When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
Thermistor wiring disconnection or half disconnection
Check whether the thermistor wiring is disconnected or not.
When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.
Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.
0 [32°F] 15k 10 [50°F] 9.6k 20 [68°F] 6.3k 30 [86°F] 4.3k 40 [104°F]···3.0k
For 10 minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, above-mentioned short/open are not detected. Short: 90 [194°F] or more Open: -40 [-40°F] or less
2 1 3 4 5 6 7 8
Multi controller board input circuit failure
Set the SW1 to When the temperature in multi controller board is not an actual temperature, replace the multi controller board.
5110 Heatsink temperature thermistor (TH8) (internal thermistor of power module)
Connector (TH8) contact failure.
Check whether the connector (TH8) in the power circuit board.
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
Thermistor wiring disconnection or half disconnection.
Check whether the thermistor wiring is disconnected or not.
Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.
When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.
0 [32°F] 180k 10[50°F] 105k 20 [68°F] 63k 30 [86°F] 39k 40 [104°F]···25k
For 10 minutes after starting compressor, for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
2 1 3 4 5 6 7 8
Short:102 [216°F] or more Open: -27 [-17°F] or less
Power board input circuit failure Set the SW1 to When the temperature in multi controller board is not an actual temperature, replace the power board.
Wrong setting of model setting switch (SW4)
See 9-5. SWITCH FUNCTION TABLE
; SW4 model switching, then set correctly. *When SW4-1 is on, it will be 5110 error. Set correctly.
on · Thermistor failure · on

Display Abnormal point and detecting method Causes Check points
When detected pressure in high-pressure sensor is 1 MPa [145PSIG] or less during the operation, the compressor stops and restarts operation in 3 minutes.
High-pressure sensor failure Check the high-pressure sensor.
When the detected pressure is 1 MPa [145PSIG] or less at just before of restarting, the compressor stops due to detecting abnormality. In this time, is displayed.
Internal pressure decrease by gas leakage
Check the internal pressure.
For 3minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, abnormality is not determined as abnormality.
Connector contact failure, disconnection
Check the high-pressure sensor.
Multi controller board input circuit failure
Check the high-pressure sensor.
Current sensor error Abnormal if current sensor detects –1.5A to 1.5A during compressor operation.
Disconnection of compressor wiring Defective circuit of current sensor on outdoor power circuit board
Correct the wiring (U·V·W phase) to compressor. (Outdoor power circuit board). Replace outdoor power circuit board.
(This error is ignored in case of SW7-1 ON.)
Abnormal if input current exceeds 38A or 34A continuously 10 seconds. (Current sensor on noise filter board detects input current.)
Decrease of power supply voltage Check the facility of power supply.
5701 Disconnected float switch connector Abnormal if detected that the float switch connector is disconnected(open) during operation
6600 Duplex address error
There are 2 units or more with the same address among the outdoor unit or indoor unit or lossnay controller, remote controller.
Look for the unit, which is source of abnormality with the same address. When the same address is found, correct the address and turn off power supply of outdoor unit, indoor unit, and lossnay for 2 minutes or more as the same time. Then, turn on power supply.
Detected error when transmission of unit with the same address is confirmed.
When noise has occurred in the transmission signal, and the signal
Check the transmitted wave and the noise on the transmission line.
has changed.
6602 Transmission processor H/W error
When the transmission line is constructed with the current flowed, turn off power supply of outdoor unit, indoor unit and lossnay for 2 minutes or more as the same time. Then, turn on power supply. Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
When the wiring for either of the indoor unit, the outdoor unit or lossnay transmission line is constructed or polarity is changed with the power supply turned on, the transmission waves change in case that the transmission data collides mutually. It causes to detect error.
'' 1 '' shows on the transmission line though the transmission processor transmitted '' 0''.
Transmission processor circuit failure
Check the transmitted wave and the noise on the transmission line. When the transmission data has changed by the noise.
Pressure sensor (63HS)

Display Abnormal point and detecting method Causes Check points
6603 Transmission bus busy error
Over error by collision The transmission processor cannot be transmitted since a short cycle voltage of the noise etc. mixes on the transmission line consecutively.
Check whether the transmission line of the indoor unit, fresh master, lossnay and remote controller is connected to the outdoor unit terminal board (TB7) for centralized controller or not.
Abnormality when the state, which cannot be transmitted by collision of transmission, is consecutive for 8 to 10minutes.
The transmission volume increases and cannot be transmitted since the wiring method is mistaken and the routing technique to the terminal board (TB3) for the transmission line of the outdoor unit and the terminal board (TB7) for centralized control cannot be transmitted.
Check whether the transmission line with the other refrigerant system of the indoor unit and lossnay is connected to the outdoor unit terminal board (TB3) for transmission or not.
The state that data cannot to be output to the transmission line by the noise happens for 8 to 10minutes consecutively.
The share becomes high since the data exists together to other transmitted data by a defective repeater (function which connects and intercepts the transmission of controlling system and centralized control system), and it causes abnormal detection.
Check whether the outdoor unit terminal board for transmission line (TB3) and for centralized controller (TB7) are connected or not.
Check the transmitted wave and the noise on the transmission line.
Signal communication error with transmission processor 6606
The data of the unit/transmission processor was not normally transmitted due to accidental disturbance such as noise and lightening surge.
Turn off power supply of outdoor unit, indoor unit, and lossnay for 2 minutes or more at the same time. Then, turn on power supply. It normally recovers from the malfunction that happens by chance. When same abnormality occurs again, it is defective of the controller.
Signal communication error between unit processor and transmission processor
The address transmission from the unit processor was not normally transmitted by the hardware of transmission processor defective.

Display Abnormal point and detecting method Causes Check points
6607 No ACK (Acknowledgement) Abnormality which controller of the sending side detects when there is no answer (ACK) from other side though data was transmitted once. It is detected 6 times every 30seconds continuously.
Factor that does not related to origin Turn off power supply of outdoor unit, indoor unit fresh master and lossnay for 2 minutes or more at the same time. Then, turn on power supply. It recovers normally at the malfunction that happens by chance.
Since the address switch was changed with the current passed, the unit in the last address does not exist.
Check the address switch in the address, which occurs abnormality. Decline of transmission voltage and signal by transmission line tolerance over
· The furthest point···200m
· Remote controller line···(12m) (Refer to 8-3.)
Check whether the transmission line is connected / loosen or not at origin. (Terminal board or connector)
Decline of transmission line voltage and signal by unmatched kind of line.
Line diameter···1.25 Aor more
Check whether the transmission line tolerance is over or not.
Decline of transmission line voltage and signal by a number of over-connected units.
Check whether the kind of transmission line is mistaken or not.
Miss operation of origin controller, which happens by chance.
When there is any trouble from above -, turn off power supply of outdoor unit, indoor unit and lossnay for 2 minutes or more at the same time. Then, turn on power supply.
When there is not any trouble in single refrigerant system (1 outdoor unit) from above -, controller defective in displayed address and attribute. When there is not any trouble in different refrigerant system (2 outdoor unit or more) from above -, determine it after . When the address, which should not exist, is an origin, since there is the indoor unit which memorizes the address data, cancel the unnecessary address data by the manual setting function of remote controller.
When the cause of displayed address and attribute is on the outdoor unit side.
Contact failure of outdoor unit or indoor unit transmission line (The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the outdoor unit.)
However, they are limited to the system, which sets the group between different refrigerant systems, or which fresh master /lossnay are connected.
Indoor unit transmission connector (CN2M) disconnection
Sending/receiving signal circuit failure in the indoor/outdoor unit
When there is not any trouble from above -, replace the displayed address/attribute controller board.
When operating with multi refrigerant system indoor units, the remote controller transmits the signal to the indoor unit after the other refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality.
When the cause of displayed address and attribute is on the indoor unit side.
In this time, when the error does not recover to normal, the outdoor unit multi controller board (repeater circuit) defective is expected.
Check the recovery by replacing the multi controller board one by one.
Contact failure of remote controller or indoor unit transmission line.
Indoor unit transmission connector (CN2M) disconnection.
(The remote controller detects when there is no reply (ACK) on transmitting from the remote controller to the indoor unit.)
Sending/receiving signal circuit failure in the indoor unit or remote controller.
Continued on the next page.

From the previous page.
Display Abnormal point and detecting method Causes Check points
When the cause of displayed address and attribute is on the remote controller side.
When operating with multi refrigerant system indoor units, the indoor units transmits the signal to the remote controller after the other refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality.
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the remote controller unit.)
Contact failure of remote controller or indoor unit transmission line
Indoor unit transmission connector (CN2M) disconnection Sending/receiving signal circuit failure in the indoor unit or remote controller
When the cause of displayed address and attribute is on the fresh master side.
When synchronized operating with other refrigerant system fresh master, the indoor units transmits the signal to the fresh master after the fresh master and same refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality.
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the fresh master.)
Contact failure of fresh master or indoor unit transmission line
Indoor unit or fresh master transmission connector (CN2M) disconnection
Sending/receiving signal circuit failure in the indoor unit or fresh master
When the cause of displayed address and attribute is on the lossnay side.
When the lossnay power supply is Off, the indoor unit detects abnormality at signal transmitting to the lossnay.
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the lossnay.)
When synchronized operating with other refrigerant system lossnay, the indoor units transmits the signal to the lossnay after the lossnay and same refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality
Contact failure of lossnay or indoor unit transmission line
Indoor unit transmission connector (CN2M) disconnection
Sending/receiving signal circuit failure in the indoor unit or lossnay
When the controller of displayed address and attribute is not recognized
Since the address switch was changed with the current passed, the unit in the last address does not exist.
Since the fresh master/lossnay address are changed after synchronized setting of fresh master / lossnay by the remote controller, abnormality is detected at transmitting from the indoor unit.
· ·

Display Abnormal point and detecting method Causes Check points
Transmission repeats the failure by the noise etc. 6608 No response
Check the transmission wave and noise on the transmission line. Though there was a replay (ACK) of having received signal from the other side, it is the abnormality when the response command does not return. The sending side detects the abnormality continuously six times every 30 seconds. Note) Address/Attribute displayed on the remote controller shows the controller, which did not response.
Decline of transmission voltage and signal by transmission line tolerance over
Turn off power supply of outdoor unit, indoor unit and lossnay for 2 minutes or more at the same time. Then, turn on power supply again. It recovers normally at the malfunction that happens by chance. When same abnormality occurs again, it is defective of displayed address and attribute.
· The furthest point···200 m [656 ft]
· Remote controller line···(12 m [39 ft]) (Refer to 8-3.)
Decline of transmission line voltage and signal by unmatched kind of line
Wire diameter···1.25 A [AWG16] or more
Mis-operation of origin controller, which happens by chance
Signal reception(Remote controller) Following symptoms are regarded as abnormality.
Defect of the transmission and reception circuit of the remote controller
Defect of the transmission and reception circuit of the indoor controller board
Noise occurs on the transmission line of the remote controller.
All remote controllers are set as sub-remote controller.
Signal transmission(Remote controller) Following symptoms are regarded as abnormality.
Defect of the transmission and reception circuit of the remote controller
Noise occurs on the transmission line of the remote controller.
There are 2 main remote controllers.
7100 Connecting total models of the indoor unit exceed the specified level.
Check the total models of connected indoor unit. Total capacity When connected total models of the indoor units exceed the specified level (130% of the outdoor unit models), error code is displayed.
· PUMY-P36NHMU/NHMUR1 ( ~ code 26) · PUMY-P48NHMU(1) ( ~ code 34) · PUMY-P48NHMU2/NHMUR3 ( ~ code 35)
Check the model code registration switch (indoor controller board SW2) of connected indoor unit.
There is a mistake in the registration of model name code of the outdoor unit.
Check the model code registration switch (outdoor multi controller board SW4) of the outdoor unit.
· Shield wire-CVVS,CPEVS · 6831 6834 · 6832 6833

Display Abnormal point and detecting method Causes Check points
7101 Capacity code error When the connected indoor unit models cannot be connected, is displayed.
The indoor unit models is not possible to connect.
Check the model code registration switch (indoor controller board SW2) in the connected indoor unit. The indoor unit of 06-54 (code 4-28) is possible to connect. The outdoor unit SW1 operation can check model code of the connected indoor units.
2 1 3 4 5 6 7 8
Code of indoor unit No.1
2 1 3 4 5 6 7 8
Code of indoor unit No.2
2 1 3 4 5 6 7 8
Code of indoor unit No.3
2 1 3 4 5 6 7 8
Code of indoor unit No.4
2 1 3 4 5 6 7 8
Code of indoor unit No.5
2 1 3 4 5 6 7 8
Code of indoor unit No.6
2 1 3 4 5 6 7 8
Code of indoor unit No.7
2 1 3 4 5 6 7 8
Code of indoor unit No.8
7102 Number of connecting unit over
When the connecting unit exceeds a number of limitations, error code is displayed.
Connecting unit exceeds a number of limitations. It is assumed abnormality excluding the following cases;
Check whether the connecting unit exceeds a number of limitations or not.
The indoor unit can be totally connected up to 6(P36)/8(P48) units. The indoor unit can be connected up to 8 units.
Even if the indoor unit is not connected, becomes is display.
Ventilation unit connecting is only 1unit.
7105 Address setting error
Addresses miss setting of the outdoor unit.
Check the address setting of the outdoor unit. The address should be set in 000 or 51-100. The outdoor unit is not set in 000 or in the range of 51-100. When the setting is out of the range, reset it, turn off power supply of the outdoor unit, indoor unit and lossnay for 2minutes or more at the same time, and turn on power supply again.
Address setting of the outdoor unit is wrong.
7111 When an old type M-NET remote controller is used, and the remote controller sensor is specified (SW1-1 is ON).
Replace the remote controller to M-NET remote controller. In the case of network remote controller, it is an abnormality when incapable response returns from the M-NET remote controller during the operation.
0403 Serial communication error Abnormal if serial communication between outdoor multi board and outdoor power board is defective.
Breaking of wire or contact failure of connector CN2 Breaking of wire or contact failure of connector CN4 Defective communication circuit of outdoor power board Defective communication circuit of outdoor multi board for power board
Check connection of each connector CN2, CN4.
Replace outdoor power board.
Replace outdoor multi board.

If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.

If the correct voltage (DC12 V) is not supplied to the remote controller, the indicator will not light. If this occurs, check the remote controller's wiring and the indoor unit.
Press the CHECK button for 5 seconds or more. The display content will
change as shown below.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
[When the remote controller malfunctions] (Error display 1) "NG" blinks. → The remote controller's transmitting-receiv- ing circuit is defective.
Check for other possible causes, as there is no problem with the remote controller.
The remote controller must be replaced with a new one.
[Where the remote controller is not defective, but cannot be operated.] (Error display 2) [E3], [6833] or [6832] blinks. → Transmission is not possible.
(Error display 3) "ERC" and the number of data errors are displayed. → Data error has occurred.
There might be noise or interference on the transmission path, or the indoor unit or other remote controllers are defective. Check the transmission path and other controllers.
The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmis- sion path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.
When the number of data errors is "02":
Transmission data from remote controller Transmission data on transmission path
To cancel remote controller diagnosis
Press the CHECK button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After approximately 30 seconds, the state in effect before the diagnosis will be restored.


“ ” indicator: Appears when current is carried.
Symptom or inspection code Cause Inspection method and solution
Though the content of operation is displayed on the remote controller, some indoor units do not operate.
Though the indoor unit operates, the display of the remote controller goes out soon.
( ) is not displayed on the remote controller. (M-NET remote controller is not fed.)
• Check the items shown in the left that are related to the indoor unit.
Symptom or inspection code Cause Inspection method and solution
Though the content of operation is displayed on the remote controller, some indoor units do not operate.
Though the indoor unit operates, the display of the remote controller goes out soon.
( ) is not displayed on the remote controller. (MA remote controller is not fed.)
• Check the items shown in the left that are related to the indoor unit.
"PLEASE WAIT" keeps being dis- played or it is displayed periodically. ("PLEASE WAIT" is usually dis- played about 3 minutes after the power supply of the outdoor unit is on.)
The remote controller does not operate though ( ) is displayed.
(M-NET Remote controller)

Symptom Display of remote controller CAUSE
Even the cooling (heating) operation selection button is pressed, the indoor unit cannot be operated. The auto vane runs freely.
The indoor unit can not cool (heat) if other indoor units are heating (cooling).
Because of the control operation of auto vane, it may change over to horizontal blow automatically from the downward blow in cooling in cause the downward blow operation has been continued for one hour. At defrosting in heating, hot adjusting and thermostat OFF, it automatically changes over to horizontal blow. Ultra-low speed operation is commenced at thermostat OFF. Light air automatically change over to set value by time or piping temperature at thermostat ON. The fan is to stop during defrosting.
Fan setting changes during heating.
Fan stops during heating operation. Fan does not stop while operation has been stopped. No setting of fan while start SW has been turned on.
Fan is to run for 1 minute after stopping to exhaust residual heat (only in heating). Ultra-low speed operation for 5 minutes after SW ON or until piping temperature becomes 35C. There low speed operate for 2 minutes, and then set notch is commenced. (Hot adjust control) System is being driven. Operate remote controller again after “HO” or “PLEASE WAIT” disappears.
Indoor unit remote controller shows “HO” or “PLEASE WAIT ” indicator for about 2 minutes when turning ON power supply. Drain pump does not stop while unit has been stopped. Drain pump continues to operate while unit has been stopped.
“HO” blinks “PLEASE WAIT” blinks
After a stop of cooling operation, unit continues to operate drain pump for 3 minutes and then stops it. Unit continues to operate drain pump if drainage is generated, even during a stop.

The black square (■) indicates a switch position.
Operation in Each Switch Setting
ON OFF When to Set
SW U1 1s digit
Before turning the power on
SW U2 10ths digit
Can be set either during operation or not
SW1 Digital Display Switching
ON OFF
2 3 4 5 6 7 8
2 3 4 5 6 7 8
Selects operating system startup
Start up Does not start up
Before turning the power on
Connection Information Clear Switch
Clear Do not clear
OFF to ON any time after the power is turned on During compressor running
Abnormal data clear switch input
2 3 4 5 6
Auto change over from Remote controller
Before turning the power on
ON/ OFF from outdoor unit
OFF
Any time after the power is turned on
<MODEL SELECT>
Set for each capacity.
SW4
Before the power is turned on
PUMY-P36NHMU ON OFF 1 2 3 4 5 6
PUMY-P48NHMU
Pressure limitation value change
Change the indoor unit's LEV opening at start
Can be set when off or during operation
Fixing the indoor units linear expansion valve opening
2 3 4 5 6 7 8
Fix the operation frequency
OFF to ON during com- pressor running
Change the indoor unit's LEV opening at defrost
Switching the target sub cool
Can be set when off or during operation
During the FAN or COOL mode,and thermo-OFF or OFF in heating operation, set the opening of linear expansion valve on indoor unit +1
During the FAN or COOL mode,and thermo-OFF in heating operation, set the opening of linear ex- pansion valve on indoor unit +2
+1 SW5-7 Refrigerant shortage amount is measured during heating operation (Refrigerant piping is long etc.) +2 SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.
but not available for PUMY-P48NHMU(-BS) since it does not have the auxiliary heater function.) DIP SW4-4 for primary heating control : Set DIP SW4-4 when power is turned off at unit DIP SW4-4 OFF : Disable primary heating function (Initial setting) DIP SW4-4 ON : Enable primary heating function

The black square (■) indicates a switch position.
Operation in Each Switch Setting
ON OFF When to Set
—
Normal Switch of current limitation reading in a different way
Before turning the power on
—
Normal Restriction of maximum frequency
Can be set when off or during operation
2 3 4 5 6 7 8
Enable Normal Ignore refrigerant filling abnormality
Switching the target discharge pressure (Pdm)
Switching (1) the target evaporation temperature (ETm) Switching (2) the target evaporation temperature (ETm)
Enable Normal Ignore current sensor abnormality
Before turning the power on
2 3 4 5 6
During compressor running in heating mode
Silent mode/ Demand Control Selection (see next page)
Demand Control Enable (For high humidity)
Can be set when off or during operation
Change of defrosting control

Lamp power supply Procure locally Max. 10m[33ft] ~
Distant control board Relay circuit External output adapter (PAC-SA88HA-E) Outdoor unit control board
CN51
Y
L1 : Error display lamp L2 : Compressor operation lamp X, Y : Relay (Coil standard of 0.9W or less for DC 12V)
Remote control panel Relay circuit External input adapter (PAC-SC36NA) Outdoor unit control board
Relay power supply Procure locally Max. 10m[33ft]
CN3N X
SW2
Y
ON Heating Validity of SW1
OFF Cooling Invalidity of SW1
SW1 SW2
Silent Mode / Demand Control (CN3D)
Remote control panel Relay circuit External input adapter (PAC-SC36NA) Outdoor unit control board
Relay power supply Procure locally Max. 10m[33ft]
CN3D X
SW2
Y
ON Heating Validity of SW1
OFF Cooling Invalidity of SW1
SW1 SW2
The silent mode and the demand control are selected by switching the Dip switch 8-1 on outdoor controller board. It is possible to set it to the following power sonsumption (compared with ratings) by setting SW1,2
Outdoor controller board DIP SW8-1 SW1 SW2 Function
Silent mode Silent mode operation
ON OFF ON
— OFF OFF ON OFF
100% 75% 50% 0%

9-7. HOW TO CHECK THE PARTS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)
Parts name Check points
Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 10~30 [50°F~86°F]) Thermistor (TH3) Thermistor (TH4) Thermistor (TH6) Thermistor (TH7)
160k~410k
TH6
4.3k~9.6k
TH8
39k~105k
Refer to next page. Fan motor(MF1,MF2)
Measure the resistance between the terminals with a tester. (At the ambient temperature 20 [68°F]) Solenoid valve coil (21S4)
1190 ± 100
Motor for compressor (MC)
Measure the resistance between the terminals with a tester. (Winding temperature 20 [68°F])
Open or short W
0.188
Measure the resistance between the terminals with a tester. (Surrounding temperature 20 [68°F])
Solenoid valve coil (SV1)
Normal 1183 ± 100 Abnormal Open or short
Note : As for P36NHMU/NHMUR1(-BS) and P48NHMU2/NHMUR3(-BS), rush current protect resistor is mounted on noise filter curcuit board. (20 ± 5% /10W)
Measure the resistance between the terminals with a tester.
Rush current protect resistor (RS) only PUMY-P48NHMU(1)(-BS)
Normal 5.6± 5% Abnormal Open* or short
*In case of open failure, check ACTM with a tester as well. (Refer to 9-9. Test point ; the item of ACTM)
Measure the resistance between the terminals with a tester.
A1
T3 T2 T1
A2
only PUMY-P48NHMU(1)(-BS)
Measure the resistance between the terminals with a tester.
Abnormal Open or short*
*Because the resistor of the reactor is little, it is difficult to determine if it is short or normal with an ordinary tester.

Check method of DC fan motor (fan motor / outdoor controller circuit board)
Fuse check Check the fuse (F500) on outdoor controller board.
Replace outdoor controller board (MULTI.B.) (C.B) and fan motor (MF1, 2).
Did the fuse blow?
Wiring contact check Contact of fan motor connector (CNF1, 2)
Is there contact failure? Yes
Recover wiring.
Power supply check(Remove the connector (CNF1, 2)) Measure the voltage in the outdoor controller circuit board. TEST POINT : VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC280-340V (When ACTM stops), DC350V (When ACTM is operating) TEST POINT : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V
Is the voltage normal?
Replace the fan motor.
Check the operation of fan. END
controller board.
Replace outdoor controller board.
Check the operation. END
Replace the fan motor.
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇
㪤㫌㫃㫋㫀㩷㪺㫆㫅㫋㫉㫆㫃㫃㪼㫉㩷㪹㫆㪸㫉㪻
㪝㪘㪥㩷㪤㪦㪫㪦㪩䇭㩿㪤㪝㪈㪀
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪄㪕㩷㩷㫉㫆㫋㪸㫋㫀㫆㫅㩷㫊㫀㪾㫅㪸㫃 㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㪺㫆㫅㫋㫉㫆㫃㩷㫍㫆㫃㫋㪸㪾㪼
㪎 㪍 㪌 㪋 㪄 㪄 㪈
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇 㪧㪚㪌㪈㪈
㪛㪚㪈㪌㪭 㪛㪚㪇㪄㪍㪅㪌㪭 㪛㪚㪇㪄㪈㪌㪭㩷㫇㫌㫃㫊㪼
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞
㪠㫅㫍㪼㫉㫋㪼㫉
㪚㪌㪈㪌
㪻㫉㫀㫍㪼㫉
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㪾㪸㫋㪼㩷㪻㫉㫀㫍㪼㪀
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪞㫉㫆㫌㫅㪻
㪚㪏㪉㪘
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽳㩷㪭㪺㪺
㪤㫆㫋㫆㫉
㪊 㪄 㪈
㪊 㪄 㪈
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽳㩷㪭㪺㪺
㪂 㪛㪚㪉㪏㪇㪄㪊㪌㪇㪭
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㫀㫅㫍㪼㫉㫋㪼㫉㩷㪻㫉㫀㫍㪼㪀
㪚㪥㪝㪈 㪚㪥㪛㪚 㪝㪌㪇㪇
㪚㪌㪈㪇
㪚㪥㪛㪚
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽲㩷㪭 㪛㪚
㪧㫆㫎㪼㫉㩷㪹㫆㪸㫉㪻
㪚㪟㪜㪚㪢㩷㪧㪦㪠㪥㪫
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞
㪚㪟㪜㪚㪢㩷㪧㪦㪠㪥㪫
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇
㪝㪘㪥㩷㪤㪦㪫㪦㪩䇭㩿㪤㪝㪉㪀
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪄㪕㩷㩷㫉㫆㫋㪸㫋㫀㫆㫅㩷㫊㫀㪾㫅㪸㫃 㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㪺㫆㫅㫋㫉㫆㫃㩷㫍㫆㫃㫋㪸㪾㪼
㪎 㪍 㪌 㪋 㪄 㪄 㪈
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇 㪧㪚㪌㪈㪉
㪛㪚㪇㪄㪍㪅㪌㪭 㪛㪚㪇㪄㪈㪌㪭㩷㫇㫌㫃㫊㪼
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞
㪠㫅㫍㪼㫉㫋㪼㫉
㪻㫉㫀㫍㪼㫉
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㪾㪸㫋㪼㩷㪻㫉㫀㫍㪼㪀
㪚㪌㪈㪍
㪤㫆㫋㫆㫉
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪞㫉㫆㫌㫅㪻
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽳㩷㪭㪺㪺
㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㫀㫅㫍㪼㫉㫋㪼㫉㩷㪻㫉㫀㫍㪼㪀
㪚㪥㪝㪉
㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽲㩷㪭 㪛㪚
㪚㪟㪜㪚㪢㩷㪧㪦㪠㪥㪫
· The inverter control P.C. board is built in the fan motor of this outdoor unit. · When F500 that is on controller board is blown, change the fan motor and multi controller board at the same time (F500 is impossisble to changae). · For outdoor unit, there are 2 fan motors (up and down; MF1/MF2), it is possible to connect to either CNF1 or CNF2 on the board. · It is abnormal when the abnormlity is detected from either both fan motors or only one side.

Multi controller board check
Fuse check Check the fuse on Multi controller board
Did the fuse (F500) blow? Replace Multi board and fan motor.
*See DC fan check
Did the fuse (F1 and F2) blow? Check the SV1 and 21S4 and wiring.
Check the voltage from the power board to CNDC(PNK) connector.
280V to 350V DC?
*Check the breaker and main incoming power *Check noise filter board *Check wiring
*Check wiring *Replace multi controller board
Multi controller board

conv. circuit
NO LO
F500
208/230V ±10% AC
CNAC (RED) F1 F2
208/230V ±10% AC
Noise filter circuit board CNAC2(RED) 208/230V ±10% AC
LO
NO
NI
TB1

*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.
Is the voltage of main incoming power
208/230V AC ? *Check the breaker and power supply
*Check wiring *Check power board *Check noise filter board
Is the voltage of CNDC(PNK) on multi
*Check wiring *Check model setting switch SW4 on the multi controller board. *Replace power board
Is the voltage to the compressor (U-V,U-W and V-W) balanced ?
Noise filter circuit board 208/230V ±10% AC
208/230V ±10% AC
LO
NI
NO
208/230V ±10% AC
TB1
Power board

U-V 10V-180V AC U-W 10V-180V AC V-W 10V-180V AC
W V U Circuit diagram
COMP
conv. circuit
W

W
7 6 5 4 3 2 1 CN2 (WHT)

Noise filter circuit board check
*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.
Is the voltage of main incoming power
208/230V±10% AC ? *Check the breaker and power supply
Is the voltage of CNAC (RED) on multi
*Check wiring *Replace noise filter board
*Check wiring *Check M-NET power board *Check noise filter board
Is the voltage between M1 and M2 on TB3 (M-NET transmission) 24-30V DC?
Turn off the incoming power supply and check the resistance of RS1 on
Is the voltage of CNDC(PNK) on multi
*1 As for P48NHMU(1), 52C-relay and RS are not mounted on noise filter circuit board.
the Noise filter board. *1
*Check wiring *Check power board,
RS1 = open ?
*Replace Noise filter board and check 52C-relay,wiring,power board and ACTM.

12V DC from multi board CNLVB
*1 As for P48NHMU(1), 52C-relay and RS are not mounted on noise filter circuit board.
Noise filter circuit board

208/230V ±10% AC
conv. circuit
CNDC (PNK)
280-350V DC
208/230V ±10% AC 208/230V ±10% AC To multi controller board CNDC(PNK)
CNAC2(RED) 2 1

ACTM check (Active Filter Module)
*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.
Is the voltage of main incoming power
208/230V ± -10% AC? *Check the breaker and power supply
Is the voltage of CNDC(PNK) on multi board 330 - 350V DC during cooling or
Is the voltage between 3pin and
4pin of CN2 on multi controller board 18V DC?
*Check wiring *Check 52C relay *Check ACTM
*Replace multi controller board
ON
208/230V
OFF
ON
OFF
ex. 48Hz
290/325V
Bus bar voltage (DC)
ACTM OFF
OFF
power on starts stop
operate:330-350V DC stop :290-325V DC
Noise filter circuit board
conv. circuit 208/230V ±10% AC
LO
NO
NI
208/230V ±10% AC
TB1
7 6 5 4 3 2 1 CN2 (WHT)
ACTM gate drive power supply
U-V 10V-180V AC U-W 10V-180V AC V-W 10V-180V AC
AC TM
DCL
W V U
COMP

W
W

operate:330-350V DC stop :290-325V DC

M-NET transmission power board check
*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.
Check the voltage between M1 and M2 on the
transmission terminal block TB3
Yes (24-30V DC ) No
Is the incoming main voltage 208/230V ±10% AC ?
*Check breaker and incoming power supply *Check noise filter board *Check wiring
Yes (208-230V AC )
Disconnect the indoor - outdoor transmission wiring from the terminal block TB3 , and check the voltage
between M1 and M2 on TB3 again.
Yes (24-30V DC )
*Check wiring *Replace M-NET transmission power board
*Correct the short circuit point on the M-NET transmission line.
M-NET transmission power board
CN2

NI
2 1 CN102 (WHT)
CNS1 (RED)
CNAC1(WHT)
TB1
CN1
208/230V ±10% AC
TB3
M1 M2

MULTI CONTROLLER BOARD
5V DC
WHT
SENSOR
BLU
BLK
GND 63HS
2.5 5 363 725 MPa PSIG
<Thermistor feature chart>
Low temperature thermistors
Resistance (k)
Thermistor R0 = 15k' ± 3% B constant = 3480 ± 2%
Rt =15exp{3480( 273+t – 273 )} 1 1 t : :=(°F-32)/1.8
-20 -10 0 10 20 30 40 50 -4 -14 32 50 68 86 104122
Heatsink temperature thermistor (TH8)
Thermistor R50 = 17k' ± 2% B constant = 4170 ± 3%
Resistance (k)
Rt =17exp{4170( 273+t – 323)} 1 1
0 25 50 75 100 110 125 77 122 167 212 230 257 ºF Temperature
Thermistor R120 = 7.465k' ± 2% B constant = 4057 ± 2%
Resistance (k)
Rt =7.465exp{4057( 273+t – 393)} 1 1
0 25 50 75 100 120 77 122 167 212 248 °F Temperature
Vout (V) · Vout MICRO COMPUTER · °F Temperature

9-9. TEST POINT DIAGRAM Outdoor multi controller board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)
SW4 Model select SW7 Forced defrost SW3 Test run
CN51 External signal output
CN102 Connect to the M-P.B (Transmission power board)
SW8 Demand/ Silent selection

CN40,CN41 Centralized control power supply/ For storing jumper connector selection
SW1 Display selection (Self diagnosis)
CNS2 Transmission wire of centrallized control
SWU2, SWU1 Address setting
CNS1 Indoor/ outdoor unit connecting wire
CNLVB (only P36/P48NHMU2) Connect to the oudoor noise filter circuit board(CN52C) 1–6 : DC12V
CN2 Connect to the outdoor power circuit board 1-5: Power circuit board → Transmitting signal to the multi controller board (0-5V DC) 2-5: Zero cross signal (0-5V DC) 3-4: 18VDC (ACTM power supply) 6-5: 16V DC (Inverter drive power supply) 7-5: 16V DC (Inverter drive power supply)
63L Low pressure switch
63H High presser switch
CN3D Input of demand control
CNAC Power supply for multi controller board
TH3 Thermistor
TH7/ 6 Thermistor
63HS High presser sensor
VFG (TEST POINT4) (voltage between left pins of PC511 and PC512, pin1 and pin2) : (Same as CNF1,2 7(+)–4(-))
VCC (TEST POINT2) (Voltage between pins of C82A) : DC15V (Same as CNF1,2 5(+)–4(-))
52C 52C relay signal
VSP (TEST POINT3) (voltage between pins of C515 and C516) : DC0V (when stopped) DC1–6.5V (when operated) (Same as CNF1,2 6(+)–4(-))
CNF1, 2 Connect to fan motors 1–4 : DC290V–350V 5–4 : DC15V 6–4 : DC0–6.5V 7–4 : DC15V (when stopped) DC0–15V pulse (when operated)
VDC (TEST POINT1) (Voltage between pins of C510) : DC290V–350V (Same as CNF1,2 1(+)–4(-))
CNDC and C510 have the same voltage. Also possible to check at self check No. 45 SW1 : 10110100

Outdoor power circuit board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)
Brief Check of POWER MODULE W Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken. 1. Check of POWER MODULE 1.Check of DIODE circuit S - P1 , T - P1 , S - N1 , T - N1 2.Check of IGBT circuit P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
in the diagram are not actually printed on the board.
CN2 Connect to the outdoor controller circuit board (CN2) 1-5:Transmitting signal to the outdoor controller circuit board (0~5V DC) 2-5:Zero cross signal (0~5V DC) 3-4:18V DC 6-5:16V DC 7-5:16V DC
CNDC 310V DC (1+, 3–) Connect to the outdoor con- troller circuit board

TABS/T Connect to the outdoor noise filter circuit board Voltage among phases: 208/230V AC
TABN1/SC-N1 Connect to the ACTM(-)
CN3 Thermistor (TH8)
CN5 Detection of primary current Connect to the outdoor noise filter circuit board (CN5)
TABP1/SC-P1 Connect to 52C (P48NHMU) Connect to ACTM (+) (P36NHMU, P48NHMU2)
CN4 Connect to the outdoor controller circuit board (CN4)
TABP2/SC-P2 Connect to the ACTM(P)
TABU/V/W Connect to the compressor (MC) Voltage among phases: 10V~180V AC
TABN2/SC-N2 Connect to the ACTM (N2)

LO, NO Voltage of 208-230V AC is output (Connect to the outdoor power circuit board)
TABT

CNAC2 208/230V AC (Connect to the outdoor control- ler circuit board (CNAC))
CN5 Primary current (Connect to the outdoor power circuit board (CN5))
CNAC1 208/230V AC (Connect to the M-NET power cir- cuit board (M-P.B.)) Current transformer (Primary current)
EI Connect to the earth
LI, NI Voltage of 208/230V AC is input (Connect to the terminal block (TB1))

52C Relay (Coil resistance 155" (typ))

CN5 52C driving signal (Connect to the outdoor controller circuit board (CNLVB))
RS1 Rush current protect resistor 20" ± 5% / 10W
LO, NO Voltage of 208/230V AC is out- put (Connect to the outdoor power circuit board)
CNAC2 208/230V AC (Connect to the outdoor control- ler circuit board (CNAC))
CNAC1 208/230V AC (Connect to the M-NET power circuit board (M-P.B.))
E2 Connect to the earth
Current transformer (Primary current)
CN5 Primary current (Connect to the outdoor power circuit board (CN5))
EI Connect to the earth
LI, NI Voltage of 208/230V AC is input (Connect to the terminal block (TB1))

Transmission power board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)

CN2 Connect to the outdoor multi controller board 1-2: 24–30V DC 3-4: 24–30V DC
CN1 Connect to the outdoor noise filter circuit board 1–3 : 208/230V AC

P Connect to the out- door power circuit board (TABP2)
L1, L2 Connect to the DCL(Reactor)

Connect to the outdoor power circuit board (CNAF) 1 : GND 2-1 : 15V DC 3-1 : Control signal 4, 5 : Not used 6-1 : Control signal
I Not used N2 Connect to the outdoor power circuit board (TABN2)
Connect to the 52C Connect to the outdoor power circuit board (TABN1)
DCL
L1 L2 ACTM
P
N1 N2
Tester check points of Active fi lter module
Error condition Normal value (reference) Symptom when the unit is in trouble
(–) and N1 / N2 / I open less than 1" 1 The unit does not operate (can not be switched ON)
(–) and L2 short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
P and L2 short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
P and N1 / N2 / I short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
L2 and N1 / N2 / I short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
W The symptom when the unit is in open error condition is described to determine open error by tester check.

P Connect to the outdoor power circuit board (TABP2)

L1, L2 Connect to the DCL (Reactor)
Lower side
+
Connect to the outdoor power circuit board (TABP1)
Connect to the outdoor power circuit board (CNAF) 1 : GND 2-1 : 15V DC 3-1 : Control signal 4, 5 : Not used 6-1 : Control signal
lo Connect to the outdoor power circuit board (TABN2)
Connect to the outdoor power circuit board (TABN1)
DCL
L1 L2 ACTM
P
N1 N2
Tester check points of Active fi lter module
Error condition Normal value (reference) Symptom when the unit is in trouble
(–) and Io open less than 1" 1 The unit does not operate (can not be switched ON)
(–) and L2 short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
P and L2 short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
P and Io short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
L2 and Io short 100k" ~ 1M" 1 The breaker operates
open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)
W The symptom when the unit is in open error condition is described to determine open error by tester check.

latest; records become older
in sequence; history record
the address with the lowest
in 10 is the oldest.
No.8 unit check
start over current inter-
start over current inter-
start over current inter-
No.8 unit mode
No.8 unit operation
start over current inter-
Pressure sensor (63HS) abnormality
Over charge refrigerant abnormality
frequency abnormalityTH7 abnormality
No.7 unit mode
No.7 unit check
63HS abnormality Current sensor
No.7 unit operation
No.6 unit mode
No.6 unit check
TH4 abnormality TH3 abnormality Outdoor fan rotantial
Outdoor fan rotantial fre-
No.6 unit operation
address error Outdoor unit
Display mode Display on the LED1, 2 (display data)
Outdoor pipe temperature sensor (TH3) abnormality
Outside air temperature sensor (TH7) abnormality
Discharge/Comp. temperature abnormality
Discharge/Comp. temperature sensor (TH4) abnormality
Radiator panel thermistor (TH8) abnormality
Saturation temperature of suction pressure
No.5 unit mode
No.5 unit check
No.5 unit operation
0000~9999 (Alternating display of addresses and error code)
No.4 unit mode
No.4 unit check
No.4 unit operation
TH4
Discharge/Comp. temperature
Discharge/Comp. temperature
No.3 unit mode
No.3 unit operation
Discharge/Comp.
(including abnormality delay code)
0000-9999 and abnormality code
Alternating display of addresses
No.2 unit check
overheating Over current interception
Restart after 3 minutes
No.2 unit mode
No.2 unit operation
0~9999(unit::10-hour)
0~9999(unit::1-hour)
number of indoor units
No.1 unit mode
No.1 unit operation
No.1 unit check
Indoor unit check status
Abnormality delay display 1
Abnormality delay display 2
Abnormality delay display 3
Abnormality delay history 1
Abnormality delay history 2
Abnormality delay history 3
Abnormality code history 1
Abnormality code history 10
Outdoor unit operation display
Indoor unit operation mode
Indoor unit operation display
Capacity code (No. 1 indoor unit)
Capacity code (No. 2 indoor unit)
Capacity code (No. 3 indoor unit)
Capacity code (No. 4 indoor unit)
Capacity code (No. 5 indoor unit)
Abnormality code history 2
Abnormality code history 3
Abnormality code history 4
Abnormality code history 5
Abnormality code history 6
Abnormality code history 7
Abnormality code history 8
Abnormality code history 9
No.

Display of communication demand capacity
1 2 3 4 7 5 6 8
3-min.delay/no
ON/OFF Heating/Cooling Abnormal/Normal DEFROST/NO Refrigerant pull back/no Excitation current/no
Max. Hz
Frozen protection TH6 abnormality Power module
Abnormal rise of Pd control Control that restrains abnormal rise of discharge pressure
Hz restrain of receipt voltage change Max.Hz correction control due to receipt voltage change
Display mode Display on the LED1, 2 (display data)
Hz correction of receipt voltage decrease prevention Max.Hz correction control due to voltage decrease
Discharge/Comp. temperature control Hz control by discharge temperature limitation
CN3D1-3 input P93:Silent
Max.Hz control Max.Hz limitation when power supply on
Heatsink over heat prevention control Heatsink over heat prevention control
temp.(heating)
Discharge pressure control Hz control by pressure limitation
CN3S1-2 input P94:Demand
Hz control by bypass valve
Secondary current control Secondary current control
-99.9~999.9(Short/Open:-99.9 or 999.9)
Input current contol Input current contol
P95:Undefined
Max. Hz
Min.Sj
State of compressor frequency(Hz) control (Words) Content
Discharge/Comp.
P96:Autochange
0~255 (Max. 8 unit)
0~999.9[Arms]
P97:Autochange
0~999.9 (A)
0~999.9 (V)
OFF
Number of compressor ON/OFF
Input current of outdoor unit
Thermo ON operating time
Total capacity of thermo on
when microprocessor of POWER
Number of indoor units
The second current value when
BOARD abnormality is deteced
The radiator panel temperature
BOARD abnormality is deteced
State of LEV control
No.

Display of actual operating frequency
Display of number of outdoor
outdoor SLEV and indoor LEV
from high-pressure sensor and
Display of target frequency
Display of opening pulse of
(SC) data and detection data
fan control steps (target)
Display of outdoor subcool
1 2 3 4 7 5 6 8
Display mode Display on the LED1, 2 (display data)
(When the indoor unit is not connected,it is displayed as"0".)
-99.9 ~ 999.9
-99.9 ~ 999.9
-99.9 ~ 999.9
Outdoor fan control step number
IC1 LEV Opening pulse
IC2 LEV Opening pulse
IC3 LEV Opening pulse
IC4 LEV Opening pulse
IC5 LEV Opening pulse
TH7(Outdoor-temp.) °C
Outdoor SC (cooling) °C
EER fan control step number (cooling)
High-pressure sensor (Pd) kgf/cm2
IC4 TH22 (Liquid) °C
IC5 TH22 (Liquid) °C
IC2 TH21 (Intake) °C
IC3 TH21 (Intake) °C
IC4 TH21 (Intake) °C
IC5 TH21 (Intake) °C
No.

Display of actual frequency at time of abnormality delay
Display of fan step number at time of abnormality delay
Display of opening pulse outdoor SLEV
and indoor LEV at time of abnormality
Display of all control target data
high-pressure sensor and each
Display of detection data from
Display of indoor SC/SH data
Display of discharge superheat data
Display of target subcool step data
1 2 3 4 5 6 7 8 Display mode No. Notes SW1 setting
Display on the LED1, 2 (display data)
SCm/SHm(0.0~20.0)
ETm(-2.0~23.0)
-99.9~999.9 [°F]
Pdm(0.0~30.0)
SCm(0.0~20.0)
-99.9 ~ 999.9
-99.9~999.9
Fan step number at time of abnormality delay
IC1 LEV opening pulse abnormality delay
IC2 LEV opening pulse abnormality delay
IC3 LEV opening pulse abnormality delay
IC4 LEV opening pulse abnormality delay
IC5 LEV opening pulse abnormality delay
Target Pd display (heating) kgf/%
Actual frequency of abnormality delay
Discharge superheat (SHd) °C
Target ET display (cooling) °C
Target outdoor SC (cooling) °C
Target indoor SC/SH (IC1) °C
Target indoor SC/SH (IC2) °C
Target indoor SC/SH (IC3) °C
Target indoor SC/SH (IC4) °C
Target indoor SC/SH (IC5) °C
High pressure sensor (Pd) PSIG
TH3 (Outdoor pipe) °F
TH7 (Outdoor temp.) °F
TH8 (Power module) °F
IC2 SC/SH °C
IC3 SC/SH °C
IC4 SC/SH °C
IC5 SC/SH °C
TH6 (ET) °F
![Page 78 of the Mitsubishi Electronics OC366 user manual — -99.9 ~ 999.9 [°F]](/cdn/reader/57/5735c9b311c410314a037792b147e95b4d42b7c077cd08d0794115b0e3ae5593/images/page-78.webp?w=400)
Display of data from high-pressure sensor,
all thermistors, and SC/SH at time of
Display of detection data from each
Display of check sum code of ROM
Display of detection data from each
Display of version data of ROM
indoor liquid pipe thermistor
No. Display mode Notes
Display of ROM type
(When the indoor unit is not connected,it is displayed as"32".)
(When the indoor unit is not connected,it is displayed as"32".)
1 2 3 4 5 6 7 8
Display on the LED1, 2 (display data)
-99.9 ~ 999.9 [°F]
-99.9 ~ 999.9
High-pressure sensor data at time of abnormality delay kgf/%
TH4 sensor data at time of abnormality delay °C
TH6 sensor data at time of abnormality delay °C
TH3 sensor data at time of abnormality delay °C
TH8 sensor data at time of abnormality delay °C
OC SC (cooling) at time of abnormality delay °C
IC1 SC/SH at time of abnormality delay °C
IC2 SC/SH at time of abnormality delay °C
IC3 SC/SH at time of abnormality delay °C
IC4 SC/SH at time of abnormality delay °C
IC5 SC/SH at time of abnormality delay °C
IC1 TH21 Intake °F
IC2 TH21 Intake °F
IC3 TH21 Intake °F
IC4 TH21 Intake °F
IC5 TH21 Intake °F
IC6 TH21 Intake °F
IC7 TH21 Intake °F
IC8 TH21 Intake °F
IC1 TH22 Liquid °F
IC2 TH22 Liquid °F
IC1 TH23 Gas °F
IC2 TH23 Gas °F
IC3 TH23 Gas °F
IC4 TH23 Gas °F
IC5 TH23 Gas °F
IC6 TH23 Gas °F
IC7 TH23 Gas °F
IC8 TH23 Gas °F
![Page 79 of the Mitsubishi Electronics OC366 user manual — -99.9 ~ 999.9 [°F]](/cdn/reader/57/5735c9b311c410314a037792b147e95b4d42b7c077cd08d0794115b0e3ae5593/images/page-79.webp?w=400)
Except Service Ref. PUMY-P48NHMU(-BS)
Display of actual frequency at time of abnormality
Display of fan step number at time of abnormality
Display of opening pulse of outdoor SLEV
Display of data from high-pressure sensor
and all thermistors at time of abnormality
op2,op3=a op4,op5=b op6, op7=c op8,op9=d
and indoor LEV at time of abnormality
a b c d a=c b=d
Display of detection data from each
HD=05, CM=18 op1=00()/01(°F)
Display of data from SC/SH and all
Ex. a=-5, b=5, c=15, d=25
thermistors at time of abnormality
indoor liquid pipe thermistor
No. Display mode Notes
(When the indoor unit is not connected,it is displayed as"32".)
1 2 3 4 5 6 7 8
Initial value a=10.4°F, b=32°F, c=50.0°F, d=68.0°F
Display on the LED1, 2 (display data)
Initial value a= -12, b=0, c=10, d=20
— — ACTM error — — CT sensor
a=c and b=d, 10.4°F a
a=c and b=d, -12 a
10.4°F a
-12 a
-99.9 ~ 999.9
High-pressure sensor data at abnormality kgf/%
TH4 sensor data at time of abnormality °C
TH6 sensor data at time of abnormality °C
TH3 sensor data at time of abnormality °C
TH8 sensor data at time of abnormality °C
IC1 SC/SH at time of abnormality °C
IC2 SC/SH at time of abnormality °C
IC3 SC/SH at time of abnormality °C
IC4 SC/SH at time of abnormality °C
IC5 SC/SH at time of abnormality °C
IC1 LEV opening pulse at time of abnormality
IC2 LEV opening pulse at time of abnormality
IC3 LEV opening pulse at time of abnormality
IC4 LEV opening pulse at time of abnormality
IC5 LEV opening pulse at time of abnormality
Primary heating control setting temp. a
Primary heating control setting temp. b
Primary heating control setting temp. c
Primary heating control setting temp. d
Primary heating control setting temp. a°F
Primary heating control setting temp. b°F
Primary heating control setting temp. c°F
Primary heating control setting temp. d°F
Actual frequency at time of abnormality
Fan step number at time of abnormality
IC3 TH22 Liquid °F
IC4 TH22 Liquid °F
IC5 TH22 Liquid °F
IC6 TH22 Liquid °F
IC7 TH22 Liquid °F
IC8 TH22 Liquid °F

Display of data from high-pressure sensor,
Display of opening pulse of indoor LEV
Display of opening pulse of indoor LEV
Display of indoor unit operating mode
Display of indoor unit capacity mode
Display of opening pulse of outdoor
Display of SC/ SH data at time of
Display of SC/ SH data at time of
all thermistors, and outdoor SC
Display of all control target data
Display of indoor SC/SH data
No. Display mode Notes
SLEV and indoor LEV
at time of abnormality
at time of abnormality
(When the indoor unit is not connected,it is displayed as"0".)
1 2 3 4 5 6 7 8
during heating:subcool (SC)/during cooling:superheat (SH)
Display on the LED1, 2 (display data)
ON
OFF
SCm/SHm (0.0~14.0)
-99.9 ~ 999.9
-99.9 ~ 999.9
-99.9 ~ 999.9
-99.9 ~ 999.9
IC6 LEV opening pulse at abnormality delay
IC7 LEV opening pulse at abnormality delay
IC8 LEV opening pulse at abnormality delay
IC6 LEV opening pulse at time of abnormality
IC7 LEV opening pulse at time of abnormality
IC8 LEV opening pulse at time of abnormality
IC6 SC/SH at abnormality delay °C
IC7 SC/SH at abnormality delay °C
IC8 SC/SH at abnormality delay °C
IC6 SC/SH at abnormality °C
IC7 SC/SH at abnormality °C
IC8 SC/SH at abnormality °C
IC6 target SC/SH °C
IC7 target SC/SH °C
IC8 target SC/SH °C
IC6 LEV opening pulse
IC7 LEV opening pulse
IC8 LEV opening pulse
IC7 SC/SH °C
IC8 SC/SH °C
12345678 11001011 00101011 10101011 01101011 11101011 00011011 10011011 01011011 11011011 00111011 10111011 01111011 11111011 00000111 10000111 01000111 11000111 00100111 10100111 01100111 11100111 00010111 10010111 01010111 11010111 00110111 10110111 01110111 11110111 00001111 10001111 01001111 11001111 00101111 10101111 01101111
211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246

This chapter provides an introduction to electrical wiring for the CITY MULTI-S series, together with notes concerning power wiring, wiring for control (transmission wires and remote controller wires), and the frequency converter.
(1) Use a separate power supply for the outdoor unit and indoor unit.
(2) Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
(3) The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %. (4) Specific wiring requirements should adhere to the wiring regulations of the region. (5) Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord.
For example, use wiring such as YZW. (6) Install an earth longer than other cables. (7) Use copper supply wires. Use electric wires over the rating voltage 300V.
10-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY 10-2-1. Wiring diagram for main power supply
Breaker for Wiring and Current Leakage Power supply (Single phase 60Hz 208/230V)
Breaker for Wiring and Current Leakage Power supply (single phase 60Hz 208/230V)
of over current protector device Model
for Wiring*1 Ground ~/N (single), 60Hz 208/230V ~/N (single), 60Hz 208/230V
(mm2[AWG]) Breaker for Current
Outdoor Unit P36, P48 5.3 [AWG10] 5.3 [AWG10]
30 A 30 mA 0.1 sec. or less 30 A 26 A 40 A Indoor Unit
Refer to installation manual of indoor unit.
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV). *2. Use copper supply wires. Use the electric wires over the rating voltage 300V.

10-3. DESIGN FOR CONTROL WIRING Please note that the types and numbers of control wires needed by the CITY MULTI-S series will depend on the remote con- trollers and whether they are linked with the system.
Remote controller → indoor unit
Wires connecting → indoor units
Wires connecting → indoor units with outdoor unit
Wires connecting → outdoor units
Kind of remote control cable Shielding wire MVVS
Cable diameter 0.5 to 1.25 E [AWG 20 to AWG 16]
Remarks When 10 m is exceeded, use cable with the same
specifications as 10-3-2. Transmission line wiring
Kind of remote control cable 2-core cable (unshielded)
Cable diameter 0.3 to 1.25 E [AWG 22 to AWG 16]
10-4. SYSTEM SWITCH SETTING In order to identify the destinations of signals to the outdoor units, indoor units, and remote controller of the MULTI-S series, each microprocessor must be assigned an identification number (address). The addresses of outdoor units, indoor units, and remote controller must be set using their settings switches. Please consult the installation manual that comes with each unit for detailed information on setting procedures.
10-5. EXAMPLE EXTERNAL WIRING DIAGRAM FOR A BASIC SYSTEM 10-5-1. Example using a M-NET remote controller
Breaker for Wiring and Current Leakage
Outdoor unit Power supply Single phase 2 wire 60Hz 208/230V
15A Breaker for Wiring and Current Leakage
Power supply Single phase 60Hz 208/230V
1.25mm2 × 2 [AWG16]
:1.6mm × 2 [AWG14]
:1.6mm × 2 [AWG14]
0.5~1.25mm2 × 2 [AWG20 ~ AWG16]

10-6. METHOD FOR OBTAINING ELECTRICAL CHARACTERISTICS WHEN A CAPACITY AGREEMENT IS TO BE SIGNED WITH AN ELECTRIC POWER COMPANY The electrical characteristics of connected indoor unit system for air conditioning systems, including the MULTI-S series, will depend on the arrangement of the indoor and outdoor units. First read the data on the selected indoor and outdoor units and then use the following formulas to calculate the electrical char- acteristics before applying for a capacity agreement with the local electric power company.
10-6-1. Obtaining the electrical characteristics of a CITY MULTI-S series system (1) Procedure for obtaining total power consumption
Page numbers in this technical manual Power consumption
Total power consumption of each indoor unit See the technical manual of each indoor unit 1
*1 power consumption of outdoor unit Standard capacity table— Refer to 5-2. 2
Total power consumption of system See the technical manual of each indoor unit 1+2
*1 Please note that the power consumption of the outdoor unit will vary depending on the total capacity of the selected indoor units.
Page numbers in this technical manual Subtotal
Total current through each indoor unit See the technical manual of each indoor unit 1
*2 current through outdoor unit Standard capacity table— Refer to 5-2. 2
Total current through system See the technical manual of each indoor unit 1+2
*2 Please note that the current through the outdoor unit will vary depending on the total capacity of the selected indoor units.
(3) Method of obtaining system power factor Use the following formula and the total power and current obtained in parts 1 and 2 in the above table to calculate the system power factor.
(Total system power consumption)
System power factor =
(Total system current x voltage) o 100%
10-6-2. Applying to an electric power company for power and total current Calculations should be performed separately for heating and cooling employing the same methods; use the largest resulting value in your application to the electric power company.
![Page 84 of the Mitsubishi Electronics OC366 user manual — W 15.88 [5/8] W 9.52 [3/8]](/cdn/reader/57/5735c9b311c410314a037792b147e95b4d42b7c077cd08d0794115b0e3ae5593/images/page-84.webp?w=400)
Line-Branch Method Connection Examples (Connecting to 4 Indoor Units)
B C
b c
A B C
Outdoor Unit First Branch Indoor unit
Total Piping Length Farthest Piping Length
A+B+C+a+b+c+d 120m [394ft] A+B+C+d 80m [262ft] B+C+d 30m [100ft] 50 meters [164ft] or less (If the outdoor unit is lower, 20 meters [70ft] or less) 12 meters [39ft] or less Use an optional branch piping kit (CMY-Y62-G-E).
Farthest Piping Length After First Branch
High/Low Difference in Indoor/Outdoor Section
High/Low Difference in Indoor/Indoor Section
(1) Refrigerant Piping Diameter In Section From Outdoor Unit to First Branch (Outdoor Unit Piping Diameter) (1) Section From Oudoor Unit to First Branch (A) (2) Sections From Branch to Indoor Unit (a,b,c,d) (3) Section From Branch to Branch (B,C)
(2) Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Piping Diameter (mm [inch]) Model
Piping Diameter (mm [inch]) Model number
W6.35 [1/4] W12.7 [1/2] W9.52 [3/8] W15.88 [5/8]
Gas Line Liquid Line
Select the size from the right table.
(3) Refrigerant Piping Diameter In Section From Branch to Branch
Liquid Line (mm [inch]) Gas Line (mm [inch])
Liquid pipe size Total length of W9.52 × 0.06 kg [3/8" × 0.041 lbs] =
Liquid pipe size Total length of W6.35 × 0.024 kg [1/4" × 0.016 lbs]
Refrigerant amount for outdoor unit
(m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]
(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]
3.0kg [6.6 lbs]
Outdoor model : P48 Indoor 1 : P24 A : W9.52 [3/8"] 10 m [33 ft] a : W9.52 [3/8"] 15m [49 ft] 2 : P15 B : W9.52 [3/8"] 10 m [33 ft] b : W6.35 [1/4"] 10m [33 ft] 3 : P08 C : W9.52 [3/8"] 10 m [33 ft] c : W6.35 [1/4"] 10m [33 ft] 4 : P06 d : W6.35 [1/4"] 20m [66 ft] The total length of each liquid line is as follows; W9.52 [3/8"] : A + B + C + a = 10 m + 10 m + 10 m + 15 m = 45 m [33 ft + 33 ft + 33 ft + 49 ft = 148 ft] W6.35 [1/4"] : b + c + d = 10 m +10 m + 20 m = 40 m [33 ft + 33 ft + 66 ft = 132 ft] Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7kg (rounded up) = [148 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.58 lbs]
At the conditions below:
![Page 85 of the Mitsubishi Electronics OC366 user manual — (m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]](/cdn/reader/57/5735c9b311c410314a037792b147e95b4d42b7c077cd08d0794115b0e3ae5593/images/page-85.webp?w=400)
Header-Branch Method Connection Examples (Connecting to 4 Indoor Units)
H
1
A B C
Outdoor Unit First Branch Indoor unit
Total Piping Length Farthest Piping Length
A+a+b+c+d 120m [394 ft] A+d 80m [262 ft] d is 30 meters[100 ft] or less 50 meters [164 ft] or less (If the outdoor unit is lower, 20 meters [70 ft] or less) 12 meters [39 ft] or less Please select branching kit, which is sold separately, from the table below. (The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Farthest Piping Length After First Branch
High/Low Difference in Indoor/Outdoor Section
High/Low Difference in Indoor/Indoor Section
Branch header (4 branches)
Branch header (8 branches)
CMY-Y68-G-E
(1) Refrigerant Piping Diameter In Section From Outdoor Unit to First Branch (Out- door Unit Piping Diameter) (1) Section From Outdoor Unit to First Branch (A) (2) Sections From Branch to Indoor Unit (a,b,c,d)
(2) Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Piping Diameter (mm [inch]) Model
Piping Diameter (mm [inch]) Model number
W 9.52 [3/8] W 15.88 [5/8]
W6.35 [1/4] W12.7 [1/2] W9.52 [3/8] W15.88 [5/8]
Gas Line Liquid Line
Select the size from the right table.
Liquid pipe size Total length of W9.52 × 0.06 kg [3/8" × 0.041 lbs]
Liquid pipe size Total length of W6.35 × 0.024 kg [1/4" × 0.016 lbs]
Refrigerant amount for outdoor unit
(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]
3.0kg [6.6 lbs]
Outdoor model : P48 Indoor 1 : P24 A : W9.52 [3/8"] 30 m [98ft] a : W9.52 [3/8"] 15m [49ft] 2 : P15 b : W6.35 [1/4"] 10m [33 ft] 3 : P08 c : W6.35 [1/4"] 10m [33 ft] 4 : P06 d : W6.35 [1/4"] 20m [66 ft] The total length of each liquid line is as follows; W9.52 : A + a = 30 m + 15 m = 45 m [98 ft + 49 ft = 147 ft] W6.35 : b + c + d = 10 m + 10 m + 20 m = 40 m [33 ft + 33 ft + 66 ft = 132 ft] Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7kg (rounded up) = [147 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.54 lbs]
At the conditions below:
![Page 86 of the Mitsubishi Electronics OC366 user manual — W 15.88 [5/8] W 9.52 [3/8]](/cdn/reader/57/5735c9b311c410314a037792b147e95b4d42b7c077cd08d0794115b0e3ae5593/images/page-86.webp?w=400)
Method of Combined Branching of Lines and Headers Connection Examples (Connecting to 5 Indoor Units)
E
A
G
B
B 3
H
D D D
A B
Outdoor unit First branching (branching joint) Branching joint Indoor unit Branching header To downstream unit Blind caps
C D
D
Total Piping Length Farthest Piping Length
A+B+C+a+b+c+d+e is 120 meters [394 ft] or less A+B+b is 80 meters [262 ft] or less B+b is 30 meters [100 ft] or less 50 meters [164 ft] or less (If the outdoor unit is lower, 20 meters [70 ft] or less) 12 meters [39 ft] or less Please select branching kit, which is sold separately, from the table below. (The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Farthest Piping Length After First Branch
High/Low Difference in Indoor/Outdoor Section
(h) ■ Selecting the Refrigerant Branch Kit
High/Low Difference in Indoor/Indoor Section
Branch Header (4 branches)
Branch Header (8 branches)
CMY-Y68-G-E
(2) Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)
(1) Refrigerant Piping Diameter In Section From Outdoor Unit to First Branch (Out- door Unit Piping Diameter) (1) Section From Outdoor Unit to First Branch (A) (2) Sections From Branch to Indoor Unit (a,b,c,d,e) (3) Section From Branch to Branch (B,C)
Piping Diameter (mm [inch]) Model
Piping Diameter (mm [inch]) Model number
W6.35 [1/4] W12.7 [1/2] W9.52 [3/8] W15.88 [5/8]
Gas Line Liquid Line
Select the size from the right table.
(3) Refrigerant Piping Diameter In Section From Branch to Branch
Liquid Line (mm [inch]) Gas Line (mm [inch])
Liquid pipe size Total length of W9.52 × 0.06 kg [3/8" × 0.041 lbs]
Liquid pipe size Total length of W6.35 × 0.024 kg [1/4" × 0.016 lbs]
Refrigerant amount for outdoor unit
(m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]
(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]
3.0kg [6.6 lbs]
Outdoor model : P48 Indoor 1 : P24 A : W9.52 [3/8"] 10 m [33 ft] a : W9.52 [3/8"] 15m [49 ft] 2 : P15 B : W9.52 [3/8"] 10 m [33 ft] b : W6.35 [1/4"] 10m [33 ft] 3 : P08 C : W9.52 [3/8"] 10 m [33 ft] c : W6.35 [1/4"] 10m [33 ft] 4 : P06 d : W6.35 [1/4"] 10m [33 ft] 5 : P06 e : W6.35 [1/4"] 10m [33 ft] The total length of each liquid line is as follows; W9.52 : A + B + C + a = 10 m + 10 m + 10 m + 15 m = 45 m [33 ft + 33 ft + 33 ft + 49 ft = 148 ft] W6.35 : b + c + d + e = 10 m + 10 m + 10 m + 10 m = 40 m [33 ft + 33 ft + 33 ft + 33 ft = 132 ft] Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7kg (rounded up) = [148 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.58 lbs]
shown on the right. • If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
At the conditions below:

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.
11-2-1. Introduction R410A refrigerant of this air conditioner is non-toxic and non- flammable but leaking of large amount from an indoor unit into the room where the unit is installed may be deleterious. To prevent possible injury, the rooms should be large enough to keep the R410A concentration specified by KHK : (a high pressure gas safety association) installation guidelines S0010 as follows.
* Maximum concentration Maximum refrigerant concentration of R410A of a room is 0.30 kg/K accordance with the installation guidelines. To facilitate calculation, the maximum concentration is expressed in units of O/K ( kg of R410A per K)
(KHK installation guidelines S0010)
the effective mixing of air.
Direction of refrigerant flow
(Situation in which there are no door openings or in which there are open- ings above and blow doors that occupy at least 0.15% of the floor area)
All refrigerant of this system will leak out to this room if there is leakage at this indoor unit.
(c) If the smallest room has mechanical ventilation apparatus that is linked to a household gas detection
Follow (1) to (3) to confirm the R410A concentration and take appropriate treatment, if necessary.
and alarm device, the calculations should be performed for the second smallest room.
erant system. Total refrigerant amount is precharged refriger- ant amount at ex-factory plus additional charged amount at field installation.
Outdoor unit Ventilation apparatus
The second smallest room
(3) Use the results of calculations (1) and (2) to calculate the refrigerant concentration:
Total refrigerant in the refrigerating unit (O[lbs]) [ maximum concentration The smallest room in which an indoor (O/K[lbs/ft3]) unit has been installed (K[ft3]) Maximum concentration of R410A:0.3O/K[0.019lbs/ft3]
If the calculation results do not exceed the maximum concen- tration, perform the same calculations for the larger second and third room, etc., until it has been determined that nowhere will the maximum concentration be exceeded.


the hook on the right downward to remove the service panel. (2) Remove screws (3 for front, 3 for rear/5 × 12) of the top
panel and remove it.
Service panel fixing screws
Photo 2
Fan motor fixing screws


fan grille. (See Figure 1) (4) Remove a nut (for right handed screw of M6) to detach the
propeller. (See Photo 1.) (5) Disconnect the connectors, CNF1 and CNF2 on Multi con-
troller board in electrical parts box. (6) Remove 4 fan motor fixing screws (5 × 25) to detach the
fan motor. (See Photo 2)
Fan motor fixing screws
Photo 3 3. Removing the electrical parts box (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connecting wire from terminal block. (4) Remove all the following connectors from Multi controller board;

Multi controller board (MULTI.B)
Terminal block (TB3) (TB7)
sor lead wire.
Cover panel fixing screws
Continued to the next page.

From the previous page.
Photo 4 (6) Remove electrical parts box fixing screw (4 × 10) and
detach the electrical parts box by pulling it upward. The electrical parts box is fixed with 2 hooks on the left and 1 hook on the right.

Electrical parts box fixing screw
Photo 5 4. Removing the thermistor <Low pressure saturated temp.> (TH6) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connector, TH6 and TH7 (red), on the Multi

controller board in the electrical parts box. (4) Loosen the wire clamps on top of the electrical parts box. (5) Pull out the thermistor
(TH6) from the sensor holder.
rated temp.> (TH6), replace it together with thermistor <Outdoor> (TH7) since they are combined together. Refer to No.5 below to remove thermistor <Outdoor>.
Thermistor Electrical parts box
PUMY-P48NHMU (1)

controller board in the electrical parts box. (4) Loosen the wire clamps on top of the electrical parts box.
(See Photo 4) (5) Pull out the thermistor (TH7) from the sensor
holder.
replace it together with thermistor <Low pressure saturated temp> (TH6), since they are combined together. Refer to No.4 above to remove thermistor <Low pres- sure saturated temp>.
Lead wire of thermistor (TH7)

Lead wire of thermistor (TH7) Sensor holder
Electrical parts box · Sensor holder

Photo 7 6. Removing the thermistor <Outdoor pipe> (TH3) and ther- mistor <Discharge/Compressor> (TH4) (1) Remove the service panel. (See Figure 1) (2) Disconnect the connectors, TH3 (white) and TH4 (white),
Thermistor (TH3)

on the Multi controller board in the electrical parts box. (3) Loosen the clamp for the lead wire in the rear of the elec-
trical parts box. (4) Pull out the thermistor (TH3) and ther-
mistor (TH4) from the sensor holder.
4-way valve coil (21S4)
[Removing the 4-way valve coil] (3) Remove 4-way valve solenoid coil fixing screw (M4 × 6). (4) Remove the 4-way valve coil by sliding the coil toward you. (5) Disconnect the connector 21S4 (green) on the Multi con-

troller board in the electrical parts box.
Thermistor (TH6)
valve and stop valve fixing screws (5 × 16) and then remove the valve bed. (4) Remove 5 right side panel fixing screws (5 × 12) in the
4-way valve coil fixing screw
rear of the unit and then remove the right side panel. (5) Remove the 4-way valve coil. (See Photo 8) (6) Recover refrigerant. (7) Remove the welded part of 4-way valve. Note 1: Recover refrigerant without spreading it in the air. Note 2: The welded part can be removed easily by remov-
ing the right side panel. Note 3: When installing the 4-way valve, cover it with a wet
cloth to prevent it from heating (120 °C [248 °F] or more), then braze the pipes so that the inside of pipes are not oxidized.


rear of the unit and remove the right side panel. (4) Remove the bypass valve coil fixing screw (M4 × 6). (5) Remove the bypass valve coil by sliding the coil upward. (6) Disconnect the connector SV1 (white) on the Multi control-
ler circuit board in the electrical parts box. (7) Recover refrigerant. (8) Remove the welded part of bypass valve.
High pressure switch (63H)
ing the right side panel.
Bypass valve coil fixing screw
Bypass valve coil (SV1)
High pressure sensor (63HS)
rear of the unit and remove the right side panel. (5) Pull out the lead wire of high pressure switch and low
pressure switch. (6) Recover refrigerant. (7) Remove the welded part of high pressure switch and low
pressure switch.
the right side panel. Note 3: When installing the high pressure switch and low
pressure switch, cover them with a wet cloth to pre- vent them from heating (100 °C [212 °F] or more), then braze the pipes so that the inside of pipes are not oxidized.

rear of the unit and remove the right side panel. (5) Pull out the lead wire of high pressure sensor. (6) Recover refrigerant. (7) Remove the welded part of high pressure sensor.
the right side panel. Note 3: When installing the high pressure sensor, cover it
with a wet cloth to prevent it from heating (100 °C [212 °F] or more), then braze the pipes so that the inside of pipes are not oxidized.
High pressure sensor (63HS)
Low pressure switch (63L)
Bypass valve


remove the front cover panel. (See Photo 3) (4) Remove 2 back cover panel fixing screws (5 × 12) and
remove the back cover panel. (5) Remove the electrical parts box. (See Photo 3) (6) Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve
and stop valve fixing screws (5 × 16) and then remove the valve bed. (7) Remove 4 right side panel fixing screws (5 × 12) in the
Valve bed fixing screws
Valve bed fixing screw
rear of the unit and then remove the right side panel. (8) Remove 3 separator fixing screws (4 × 10) and remove
the separator. (9) Recover refrigerant. (10) Remove the 3 points of the motor for compressor fixing nut
using a spanner or a monkey wrench. (11) Remove the welded pipe of motor for compressor inlet and
outlet and then remove the compressor.

remove the front cover panel. (See Photo 3) (4) Remove 2 back cover panel fixing screws (5 × 12) and
remove the back cover panel. (5) Remove the electrical parts box. (See Photo 3) (6) Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve
and stop valve fixing screws (5 × 16) and then remove the valve bed. (7) Remove 4 right side panel fixing screws (5 × 12) in the
rear of the unit and then remove the right side panel. (8) Recover refrigerant. (9) Remove 4 welded pipes of power receiver inlet and outlet. (10) Remove 2 receiver leg fixing screws (4 × 10). (See Photo 13)

Accumulator leg fixing screws

w Parts of PUMY-P48NHMU are set as the same service parts as PUMY-P48NHMU-BS.
Remarks (Drawing No.)
Part No. Part Name Specification No.
Q,ty PUMY-P48 NHMU(-BS)
R01 E04 662
SIDE PANEL (L)
T7W E02 691
FAN GRILLE
T7W E04 667
FRONT PANEL
R01 E18 686
BASE ASSY
R01 E26 686
BASE ASSY
R01 E19 130
MOTOR SUPPORT
R01 30L 655
HANDLE
T7W E01 658
COVER PANEL (FRONT)
R01 E14 658
COVER PANEL (FRONT)
T7W E00 658
COVER PANEL (REAR)
R01 E05 658
COVER PANEL (REAR)
T7W E16 661
SIDE PANEL (R)
T7W E06 668
SERVICE PANEL
R01 E01 698
REAR GUARD
R01 E06 641
TOP PANEL
R01 E00 655
HANDLE

24 23 22
13 14 15

Part numbers that are circled are not shown in the figure.
Remarks (Drawing No.)
Part No. Part Name Specification No.
R01 E44 221
FAN MOTOR
MF1,2
R01 E01 115
PROPELLER FAN
R01 E02 097
NUT
T7W E07 413
CHARGE PLUG
ANB33FDCMT Including RUBBER MOUNT
T97 410 742
COMPRESSOR
MC
T7W E04 410
STOP VALVE
3/8
T7W E06 411
BALL VALVE
5/8
R01 E03 450
STRAINER
R01 E35 440
ACCUMULATOR
T7W E02 490
OIL SEPARATOR
:2.5:0.81000mm
CAPILLARY TUBE
H.P SENSOR
63HS
R01 25T 209
LOW PRESSURE SWITCH
T7W E03 428
BYPASS VALVE
T7W E17 242
SOLENOID COIL <BYPASS VALVE>
SV1
T7W E18 242
SOLENOID COIL <4-WAY VALVE>
21S4
T7W E05 403
4-WAY VALVE
R01 E75 202
THERMISTOR
TH6,7
T7W E05 208
HIGH PRESSURE SWITCH
63H
T7W E29 408
HEAT EXCHANGER
T7W E02 259
CONTACTOR
T7W 850 716
TERMINAL BLOCK
3P (L1,L2,GR)
TB1
T7W E14 346
NOISE FILTER CIRCUIT BOARD
N.F.
MULTI CONTROLLER CIRCUIT BOARD
MULTI.B.
TERMINAL BLOCK
3P (M1, M2, S)
TB3, TB7
R01 E01 311
TRANSMISSION POWER BOARD
M-P.B.
RESISTOR
RS
T7W E09 259
REACTOR
DCL
T7W E26 313
POWER CIRCUIT BOARD
P.B.
ACT MODULE
ACTM
T7W E09 254
MAIN SMOOTHING CAPACITOR
CB
R01 E66 202
THERMISTOR (OUTDOOR PIPE)
TH3
R01 E00 201
THERMISTOR (DISCHARGE)
TH4
R01 E65 202
THERMISTOR (HEATSINK)
TH8



Part numbers that are circled are not shown in the figure.
RoHS
PUMY-P·(-BS)
Remarks (Drawing No.)
Part No. Part Name Specification No.
36NHMUR1 48NHMUR3
G
T7W E27 763
FAN MOTOR
MF1,2
G
R01 E08 115
PROPELLER FAN
G
R01 E12 115
PROPELLER FAN
G
R01 E09 097
NUT
G
T7W E07 413
CHARGE PLUG
G
T7W E12 413
CHARGE PLUG
ANB33FDHMT Including RUBBER MOUNT ANB33FDSMT Including RUBBER MOUNT
G
T97 415 755
COMPRESSOR
MC
G
T97 415 779
COMPRESSOR
MC
G
T7W E04 410
STOP VALVE
3/8
G
T7W E06 411
BALL VALVE
5/8
G
R01 E28 201
THERMISTOR(COMPRESSOR)
TH4
G
R01 E44 440
ACCUMULATOR
G
T7W E02 490
OIL SEPARATOR
G
R01 E26 425
CAPILLARY TUBE
:2.5:0.81000mm [:(3/32) % :(1/32) % L(39-1/2)]inch
R01 E07 208
H.P SENSOR
63HS
G
R01 E00 209
LOW PRESSURE SWITCH
G
T7W E03 428
BYPASS VALVE
G
T7W E17 242
SOLENOID COIL <BYPASS VALVE>
SV1
G
T7W E18 242
SOLENOID COIL <4-WAY VALVE>
21S4
G
T7W E05 403
4-WAY VALVE
G
R01 H01 202
THERMISTOR
TH6,7
G
T7W E07 208
HIGH PRESSURE SWITCH
63H
G
T7W E41 408
HEAT EXCHANGER
G
R01 V03 310
CONTROLLER CIRCUIT BOARD
C.B.
R01 V14 310
CONTROLLER CIRCUIT BOARD
C.B.
R01 E27 246
TERMINAL BLOCK
3P (M1, M2, S)
TB3, TB7
G
R01 E02 311
M-POWER BOARD
M-NET.P.B.
R01 E04 311
M-POWER BOARD
M-NET.P.B.
R01 E20 259
REACTOR
DCL
G
T7W E17 259
REACTOR
DCL
G
R01 E64 313
POWER CIRCUIT BOARD
P.B.
R01 E65 313
POWER CIRCUIT BOARD
P.B.
R01 E07 233
ACT MODULE
ACTM
G
T7W E45 716
TERMINAL BLOCK
3P (L1,L2,GR)
TB1
G
R01 E18 346
NOISE FILTER CIRCUIT BOARD
N.F.
R01 E99 202
THERMISTOR (HEATSINK)
TH8
G
R01 E22 255
MAIN SMOOTHING CAPACITOR
CE
G
R01 H00 202
THERMISTOR (OUTDOOR PIPE)
TH3
G
R01 E12 201
THERMISTOR (DISCHARGE)
TH4
G
R01 E06 239
FUSE
250V, 6.3A
F1, 2

w Parts of PUMY-P36/48NHMU are set as the same service parts as
PUMY-P36/48NHMU-BS.
Speci- fication No.
Remarks (Drawing No.)
PUMY-P36 NHMUR1(-BS) PUMY-P48 NHMU 2 (-BS)
PUMY-P48 NHMUR3(-BS)
G
T7W E06 662
SIDE PANEL (L)
G
T7W E03 691
FAN GRILLE
G
T7W E06 667
FRONT PANEL
G
R01 E26 686
BASE ASSY
G
R01 E19 130
MOTOR SUPPORT
G
R01 E01 655
HANDLE
G
R01 E14 658
COVER PANEL (FRONT)
G
R01 E24 658
COVER PANEL (REAR)
G
T7W E01 617
CONDUIT PLATE
G
T7W E19 661
SIDE PANEL (R)
G
T7W E06 668
SERVICE PANEL
G
R01 E07 698
REAR GUARD
G
R01 E29 641
TOP PANEL
G
R01 E02 655
HANDLE

Part No. PAC-SG61DS-E
Part No. PAC-SG59SG-E
w Need 2 pieces.
Part No. PAC-SH63AG-E
w Need 2 pieces.
Part No. PAC-SG64DP-E
Part No.
CMY-Y62-G-E CMY-Y64-G-E
2 4 CMY-Y68-G-E 8

cCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Dec. 2010 No. OC366 REVISED EDITION-F Distributed in Sep. 2010 No. OC366 REVISED EDITION-E PDF 5 Distributed in Nov. 2009 No. OC366 REVISED EDITION-D PDF 7 Distributed in Jul. 2008 No. OC366 REVISED EDITION-C PDF 7 Distributed in Dec. 2007 No. OC366 REVISED EDITION-B PDF 9 Distributed in Apr. 2006 No. OC366 REVISED EDITION-A PDF 10 Distributed in Jan. 2006 No. OC366 PDF 10 Made in Japan
New publication, effective Dec. 2010 Specifications subject to change without notice
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Though the content of operation is displayed on the remote controller, some indoor units do not operate. | • The power supply of the indoor unit is not on. • The address of the indoor units in same group or the remote controller is not set correctly. • The group setting between outdoor units is not registered to the remote controller. • The fuse on the indoor unit controller board is blown. | • Check the part where the abnormality occurs. The entire system In the entire refrigerant system In same group only 1 indoor unit only <In case of the entire system or in the entire refrigerant system> • Check the self-diagnosis LED of the outdoor unit. • Check the items shown in the left that are related to the outdoor unit. <In case of in same group only or 1 indoor unit only> • Check the items shown in the left that are related to the indoor unit. | p.54 |
| Though the indoor unit operates, the display of the remote controller goes out soon. | • The power supply of the indoor unit is not on. • The fuse on the indoor unit controller board is blown. | p.54 | |
| ( ) is not displayed on the remote controller. (M-NET remote controller is not fed.) | • The power supply of the outdoor unit is not on. • The connector of transmission outdoor power board is not connected. • The number of connected indoor unit in the refrigeration system is over the limit or the number of connected remote controller is over the limit. • M-NET remote controller is connected to MA remote controller cable. • The transmission line of the indoor/outdoor unit is shorted or down. • M-NET remote controller cable is shorted or down. • Transmission outdoor power board failure. | p.54 | |
| "HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed about 3 minutes after the power supply of the outdoor unit is on.) | • The power supply for the feeding expansion unit for the transmission line is not on. • The address of the outdoor unit remains "00". • The address of the indoor unit or the remote controller is not set correctly. • MA remote controller is connected to the transmission line of the indoor/outdoor unit. | p.54 | |
| The remote controller does not operate though ( ) is displayed. | • The transmission line of the indoor/outdoor unit is connected to TB15. • The transmission line of the indoor/outdoor unit is shorted, down or badly contacted. | p.54 | |
| Though the indoor unit operates, the display of the remote controller goes out soon. | • The power supply of the indoor unit (Master) is not on. • In case of connecting the system controller, the setting of the system controller does not correspond to that of MA remote controller. • The fuse on the indoor unit (Master) controller board is blown. | p.54 | |
| ( ) is not displayed on the remote controller. (MA remote controller is not fed.) | The remote controller is not fed until the power supply of both indoor unit and outdoor unit is on and the start-up of both units is finished normally. • The power supply of the indoor unit is not on. • The power supply of the outdoor unit is not on. • The number of connected remote controller is over the limit (Maximum: 2 units) or the number of connected indoor unit that is over the limit (Maximum: 16 units). • The address of the indoor unit is "00" and the address for the outdoor unit is the one other than "00". • The transmission line of the indoor/outdoor unit is connected to TB15. • MA remote controller is connected to the transmission line of the indoor/outdoor unit . • The remote controller cable is shorted or down. • The power supply cable or the transmission line is shorted or down. • The fuse on the indoor unit controller board is blown. | p.54 | |
| "PLEASE WAIT" keeps being dis- played or it is displayed periodically. ("PLEASE WAIT" is usually dis- played about 3 minutes after the power supply of the outdoor unit is on.) | • The power supply of the outdoor unit is not on. • The power supply of the feeding expansion unit for the transmission line is not on. • The setting of MA remote controller is not main remote controller, but sub-remote controller. • MA remote controller is connected to the transmission line of the indoor/outdoor unit. | p.54 | |
| The remote controller does not operate though ( ) is displayed. | • The power supply of the indoor unit (Master) is not on. • The transmission line of the indoor/outdoor unit is connected to TB15. • The transmission line of the indoor/outdoor unit is shorted, down or badly contacted. •The fuse on the indoor unit controller board is blown. | p.54 |