HFC utilizedp.1SPLIT-TYPE, HEAT PUMP AIR CONDITIONERSp.1R410Ap.1December 2010p.1No. OC366 REVISED EDITION-Fp.1TECHNICAL & SERVICE MANUALp.1[Model name] (Standard type) PUMY-P36NHMUp.1[Service Ref.]p.1PUMY-P48NHMUp.1(Salt proof type) PUMY-P36NHMU-BSp.1PUMY-P48NHMU-BSp.1Revision:p.21 TECHNICAL CHANGESp.3PUMY-P48NHMU 1 PUMY-P48NHMU 2 PUMY-P48NHMU 1 -BS PUMY-P48NHMU 2 -BSp.3PUMY-P48NHMU PUMY-P48NHMU 1 PUMY-P48NHMU-BS PUMY-P48NHMU 1 -BSp.31-1. PRIMARY HEATING ON/OFF CONTROL SET-UPp.3(2) Outdoor unit DIPSW4-4 for Primary Heating Control:p.3(3) Determine required Indoor Fans Speed during defrost mode:p.4(4) Determine Fan Airflow setting during Indoor Thermo OFF conditions:p.4(6) Locally procured wiringp.5CN24p.5CN22 X +p.5H1 88Hp.5FS1p.5FS2 FS1p.5H2 88Hp.5FS2p.526H 88Hp.52 SAFETY PRECAUTIONp.6Cautions for units utilizing refrigerant R410A 2-1. CAUTIONS RELATED TO NEW REFRIGERANTp.6[1] Cautions for servicep.6[2] Additional refrigerant chargep.6Unitp.7Gravimeterp.73 OVERVIEW OF UNITSp.93-1. UNIT CONSTRUCTIONp.93-2. UNIT SPECIFICATIONSp.10(1) Method for identifying MULTI-S modelp.10MULTI-Sp.10(2) Operating temperature rangep.10(3) Guaranteed voltage 198~253V, 60Hzp.104 SPECIFICATIONSp.115 DATAp.135-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICSp.13(1) Capacity of indoor unitp.13A 48,900 B 54,500 5.01 4.71 21.9 20.6p.13(2) Sample calculation (using the system described above in 5-1-1. (2) ):p.13During cooling: During heating:p.135-2-1. PUMY-P36NHMU(-BS)/ PUMY-P36NHMUR1(-BS)p.14Capacity(Btu/h) Power Consumption(kW) Current(A)/230V Current(A)/208Vp.145-2-2. PUMY-P48NHMU/NHMU 1 /NHMU 2 /NHMUR3(-BS)p.155-3. CORRECTING COOLING AND HEATING CAPACITYp.16Figure 2. Heating performance curvep.16Figure 1. Cooling performance curvep.16: DB(°FDB)p.16: WB(°FWB)p.16INDOORp.16°C DB °F DBp.16OUTDOORp.16(1) Capacity CORRECTION CURVE (Figure 3) Coolingp.17(2) Method for Obtaining the Equivalent Piping Lengthp.175-4. NOISE CRITERION CURVESp.17LINE PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) COOLINGp.17MODEp.17LINEp.17PUMY-P48NHMU(-BS) PUMY-P48NHMU 1 (-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)p.17COOLINGp.17HEATINGp.17MICROPHONEp.17GROUNDp.176 OUTLINES AND DIMENSIONSp.187 WIRING DIAGRAMp.20PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BSp.20DCLp.2021S4p.20SV1p.20(SV2)p.20TH7TH6 TH3 TH4 63HS 63H 63Lp.21SW4 < + 1 MODEL SELECT>p.21MODELSp.21
Page 1 of the Mitsubishi Electronics OC366 user manual — PUMY-P48NHMU-BS
Page 1 · click to enlarge
Page 1

HFC utilized

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

R410A

December 2010

No. OC366 REVISED EDITION-F

TECHNICAL & SERVICE MANUAL

[Model name] (Standard type) PUMY-P36NHMU

[Service Ref.]

  • Revision:
  • 14. RoHS PARTS LIST has been modified in REVISED EDITION-F.
  • Some descriptions have been modified.

PUMY-P36NHMU PUMY-P36NHMUR1 PUMY-P48NHMU PUMY-P48NHMU1 PUMY-P48NHMU2 PUMY-P48NHMUR3 PUMY-P36NHMU-BS PUMY-P36NHMUR1-BS PUMY-P48NHMU-BS PUMY-P48NHMU1-BS PUMY-P48NHMU2-BS PUMY-P48NHMUR3-BS

PUMY-P48NHMU

  • Please void OC366 REVISED EDITION-E.

(Salt proof type) PUMY-P36NHMU-BS

service manual. • RoHS compliant products have mark on the spec name plate.

PUMY-P48NHMU-BS

Mitsubishi Electronics OC366 — PUMY-P48NHMU-BS diagram (page 1)
Fig. 1

CONTENTS 1. TECHNICAL CHANGES 3 2. SAFETY PRECAUTION 6 3. OVERVIEW OF UNITS 9 4. SPECIFICATIONS 11 5. DATA 13 6. OUTLINES AND DIMENSIONS 18 7. WIRING DIAGRAM 20 8. NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION 24 9. TROUBLESHOOTING 34 10. ELECTRICAL WIRING 81 11. REFRIGERANT PIPING TASKS 84 12. DISASSEMBLY PROCEDURE 88 13. PARTS LIST 93 14. RoHS PARTS LIST 96 15. OPTIONAL PARTS 99 OUTDOOR UNIT

Mitsubishi Electronics OC366 — PUMY-P48NHMU-BS diagram (page 1)
Fig. 2
Page 2 of the Mitsubishi Electronics OC366 user manual — Revision:
Page 2 · click to enlarge
Page 2

Revision:

"14. RoHS PARTS LIST " has been modifi ed on page 98.

PageRevising pointService Ref.IncorrectCorrect 98STRUCTURAL PARTS No. 1 SIDE PANEL(L)PUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)T7W E03 662T7W E06 662 98STRUCTURAL PARTS No. 4 BASE ASSYPUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)R01 E31 686R01 E26 686 98STRUCTURAL PARTS No. 5 MOTOR SUPPORTPUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)R01 E27 130R01 E19 130 98STRUCTURAL PARTS No. 7 COVER PANEL (FRONT)PUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)R01 E13 658R01 E14 658 98STRUCTURAL PARTS No. 8 COVER PANEL (REAR)PUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)R01 E11 658R01 E24 658 98STRUCTURAL PARTS No. 11 SERVICE PANELPUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)T7W E08 668T7W E06 668 98STRUCTURAL PARTS No. 13 TOP PANELPUMY-P36NHMU(-BS) PUMY-P48NHMU2(-BS)R01 E14 641R01 E29 641
Page 3 of the Mitsubishi Electronics OC366 user manual — (2) Outdoor unit DIPSW4-4 for Primary Heating Control:
Page 3 · click to enlarge
Page 3

1 TECHNICAL CHANGES

PUMY-P36NHMU PUMY-P36NHMUR1 PUMY-P36NHMU-BS PUMY-P36NHMUR1-BS PUMY-P48NHMU 2 PUMY-P48NHMUR3 PUMY-P48NHMU 2 -BS PUMY-P48NHMUR3-BS

  • THERMISTOR has been changed. (Discharge thermistor → Compressor thermistor)
  • Compressor has been changed.

PUMY-P48NHMU 1 PUMY-P48NHMU 2 PUMY-P48NHMU 1 -BS PUMY-P48NHMU 2 -BS

· Compressor (MC) and oil have been changed. ANB33FDCMT (Ester oil: MEL56) ANB33FDHMT(Ether oil: FV50S) · Electrical parts have been changed. Multi controller board (MULTI. → C.B.) Noise filter circuit board (N.F.) Active filter module (ACTM) Relay (52C) , Resister (RS) (including N.F.)

PUMY-P48NHMU PUMY-P48NHMU 1 PUMY-P48NHMU-BS PUMY-P48NHMU 1 -BS

  • Primary heating ON/OFF control has been added.

1-1. PRIMARY HEATING ON/OFF CONTROL SET-UP

(1) Primary heating operation controls another heat source that depends on the main system's operations,

which means the interlock operation shown in "c)" will be possible. a) b)

Service ref. PUMY-P48NHMU(-BS) does not have this function. Indoor unit must be R410A UL model for this function to operate.

PMFY-P06NBMU PMFY-P12NBMU PKFY-P06NAMU PMFY-P08NBMU PMFY-P15NBMU PKFY-P08NAMU c) Different Indoor unit applications that can be applied:

Mitsubishi Electronics OC366 — 1-1. PRIMARY HEATING ON/OFF CONTROL SET-UP diagram (page 3)
Fig. 3

(2) Outdoor unit DIPSW4-4 for Primary Heating Control:

Set DIPSW4-4 when power is turned off at unit.

OFFDisable Primary Heating Function (Initial setting) ON : Enable Primary Heating Function
Page 4 of the Mitsubishi Electronics OC366 user manual — (4) Determine Fan Airflow setting during Indoor Thermo OFF conditions:
Page 4 · click to enlarge
Page 4

(3) Determine required Indoor Fans Speed during defrost mode:

a) With no Primary heating output the Indoor fan normally goes off to prevent cold drafts during the defrost cycles. b) With Primary heating control the auxiliary heat will be on during defrost mode, thus cold drafts will not be present. (Ducted units only) c) For models PEFY and PDFY (Ducted) recommended to use "Black" (20K) connector. d) For models PLFY, PCFY, PKFY and PFFY (Ductless) recommended "None", no connector required. e) To set the fan airflow rate to be used during defrost operation, insert the resistance that is packed within the optional adaptor cable kit (PAC-YU24HT-F) into the CN22 sensor input. You can choose at what speed the indoor fan operates during defrost cycles bases on chart below.

Fan airflow rate setting During defrost operationOFFONWiring CN22 input resistance ()020k27k39k62KCN22 CN22 input (cable color)NoneBlackBlueWhiteRed FAN SPEED SETTINGStoppedSetting on remote controllerVery LowLowHigh
Mitsubishi Electronics OC366 — (3) Determine required Indoor Fans Speed during defrost mode: diagram (page 4)
Fig. 4 · (3) Determine required Indoor Fans Speed during defr…

(4) Determine Fan Airflow setting during Indoor Thermo OFF conditions:

a) These settings are done within Indoor DIPSW1-7 and DIPSW1-8, see chart below for options. b) Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on "Setting on the remote controller".

Auxiliary Heating SignalFan speed settingFan speed setting Thermo ConditionOFFON SW1-7SW1-8 OFFOFFVery lowSetting on remote controller ONOFFLow OFFONSetting on remote controller ONONStopped
Mitsubishi Electronics OC366 — (4) Determine Fan Airflow setting during Indoor Thermo OFF conditions: diagram (page 4)
Fig. 5 · (4) Determine Fan Airflow setting during Indoor Ther…

(5) Setting Outdoor unit and Auxiliary heat switch over temperatures.

When the DIPSW 4-4 is set to "ON", the outdoor unit and the contact output operates as shown below.

a) Outdoor default setting and operations are shown below:

Stage 1 Amb. Decreasing - Outdoor unit HP operation Amb. Increasing - Defrost : Heater contact ON signal

- Other than defrostContact OFF

- Outdoor unit HP operation - Heater contact ON signal

- Outdoor unit OFF (Standby)

- Heater contact ON signal

TH7 = Outdoor Temperature a -12: [10 F]

b 0[32 F]
c 10[50 F]
d 20[68 F]

Stage 2 · Stage 3

Page 5 of the Mitsubishi Electronics OC366 user manual — CN24
Page 5 · click to enlarge
Page 5

When the set temperature ranges overlap, the previously set pattern (1,2 or 3) has a priority. The stage 1 has the highest priority, 2 the second and then 3.

b) Based on above chart listed the sequence of operation on "On Ambient Decrease"

Stage 1 :(TH7 = > 10 :) : the Outdoor unit runs in HP mode. Stage 2 :(TH7 = 10: to -12:) : the Outdoor unit runs in HP mode with Auxiliary heating. Stage 3 :(TH7 = < -12:) : Auxiliary heating only (Outdoor unit is OFF).

c) Based on above chart listed the sequence of operation on " On Ambient Increase"

Stage 3 :(TH7 = < 0 :) : Auxiliary heating only (Outdoor unit is OFF). Stage 2 :(TH7 = > 0: to 20:) : Auxiliary heating with Outdoor unit in HP mode. Stage 1 :(TH7 = > 20:) : Outdoor unit in HP mode only.

(6) Locally procured wiring

A basic connection method is shown.

(i.e. interlocked operation with the electric heater with the fan speed setting on high

Indoor unit control board

Outdoor unit control board

Remote control Board Relay circuit Adapter

Dip switch SW4-4 "ON"

CN24

CN22 X +

Preparations in the field Maximum cable length is 10 m (32ft)

For relay X use the specifications given below Operation coil

Rated voltage : 12VDC Power consumption : 0.9W or less *Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.

The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)

To extend this length, use sheathed 2-core cable.

Control cable type : CVV, CVS, CPEV or equivalent.

Cable size : 0.5 mm2 ~ 1.25 mm2 (AWG22 to AWG16) Don`t extend the cable more than 10 meters (32ft).

H1 88H

R

FS1

S

FS2 FS1

H2 88H

R

FS1, 2 Thermal fuse

S

FS2

H1, H2 Heater

26H 88H

26H Overheat protection thermostat

88H Electromagnetic contactor

CN24

Show 13 more labels / short text on this page
Electric Heater · power source · Red 1 · Yellow Green · White 2 · Red 1 · Electric Heater · Red 2 · Recommended circuit · 1-phase power supply · 208V, 230V/60Hz · Wiring diagram · Control board
Page 6 of the Mitsubishi Electronics OC366 user manual — [2] Additional refrigerant charge
Page 6 · click to enlarge
Page 6

2 SAFETY PRECAUTION

Cautions for units utilizing refrigerant R410A 2-1. CAUTIONS RELATED TO NEW REFRIGERANT

Use new refrigerant pipes.

Do not use refrigerant other than R410A.

Avoid using thin pipes.

If other refrigerant (R22 etc.) is used, chlorine in refrige- rant can cause deterioration of refrigerant oil etc.

Make sure that the inside and outside of refrige- rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazards to refrigerant cycle. In addition, use pipes with specified thickness.

Use a vacuum pump with a reverse flow check valve.

Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.

Use the following tools specifically designed for use with R410A refrigerant.

Contamination inside refrigerant piping can cause deterio- ration of refrigerant oil etc.

The following tools are necessary to use R410A refrigerant.

Store the piping to be used indoors during installation, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)

Tools for R410A Gauge manifoldFlare tool Charge hoseSize adjustment gauge Gas leak detectorVacuum pump adaptor Torque wrenchElectronic refrigerant charging scale

If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com- pressor.

Handle tools with care.

The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbezene oil in a small amount.

If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com- pressor.

If large amount of mineral oil enters, that can cause deterio- ration of refrigerant oil etc.

Do not use a charging cylinder.

Charge refrigerant from liquid phase of gas cylinder.

If a charging cylinder is used, the composition of refrigera- nt will change and the efficiency will be lowered.

If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.

Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.

[1] Cautions for service

(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.

Be sure to use a filter drier for new refrigerant.

[2] Additional refrigerant charge

When charging directly from cylinder · Check that cylinder for R410A on the market is syphon type. · Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

Page 7 of the Mitsubishi Electronics OC366 user manual — Unit
Page 7 · click to enlarge
Page 7

Unit

Gravimeter

[3] Service tools Use the below service tools as exclusive tools for R410A refrigerant.

No.Tool nameSpecifications 1Gauge manifold· Only for R410A · Use the existing fitting specifications. · Use high-tension side pressure of 5.3MPa·G or over. 2Charge hose· Only for R410A · Use pressure performance of 5.09MPa·G or over. 3Electronic scale— 4· Use the detector for R134a, R407C or R410A. 5Gas leak detector· Attach on vacuum pump. 6Adaptor for reverse flow check— 7Refrigerant charge base· Only for R410A · Top of cylinder (Pink) · Cylinder with syphon 8Refrigerant recovery equipment—

2-2. PRECAUTIONS FOR SALT PROOF TYPE "-BS" MODEL Although "-BS" model has been designed to be resistant to salt damage, observe the following precautions to maintain the performance of the unit. 1. Avoid installing the unit in a location where it will be exposed directly to seawater or sea breeze. 2. If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away by rainwater. (If a sunshade is installed, rainwater may not clean the panel.) 3. To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust. 4. If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up. 5. If the unit is damaged during installation or maintenance, be sure to repair it. 6. Be sure to check the condition of the unit regularly. 7. Be sure to install the unit in a location with good drainage.

Page 8 of the Mitsubishi Electronics OC366 user manual — Unit
Page 8 · click to enlarge
Page 8

2-3. Cautions for refrigerant piping work New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.

1 Thickness of pipes Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 0.7 mm [7/256 inch] or below.)

Diagram belowPiping diameter and thickness
Nominal dimensions[inch]Outside diameter (mm)Thickness (mm) [inch] R410AR22 1/46.350.8 [1/32]0.8 [1/32] 3/89.520.8 [1/32]0.8 [1/32] 1/212.700.8 [1/32]0.8 [1/32] 5/815.881.0 [5/128]1.0 [5/128] 3/419.05—1.0 [5/128]

2 Dimensions of flare cutting and flare nut The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A has been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to increase intensity as shown below. Set copper pipe correctly referring to cop- per pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes. Use torque wrench corresponding to each dimension.

Mitsubishi Electronics OC366 — Unit diagram (page 8)
Fig. 6 · Unit
Mitsubishi Electronics OC366 — Unit diagram (page 8)
Fig. 7 · Unit
Nominal dimensions[inch]Outside diameterDimension A ( + 0 ) -0.4 R410AR22 1/46.359.1 [11/32-23/64]9.0 3/89.5213.2 [1/2-33/64]13.0 1/212.7016.6 [41/64-21/32]16.2 5/815.8819.7 [49/64-25/32]19.4 3/419.05—23.3
Nominal dimensions[inch]Outside diameter[inch]Dimension B R410AR22 1/46.3517.0 [43/64]17.0 3/89.5222.0 [7/8]22.0 1/212.7026.0 [1-3/64]24.0 5/815.8829.0 [1-9/64]27.0 3/419.05—36.0

3 Tools for R410A (The following table shows whether conventional tools can be used or not.)

Tools and materialsUseR410A toolsCan R22 tools be used?Can R407C tools be used? Gauge manifoldAir purge, refrigerant charge and operation checkTool exclusive for R410A Charge hoseTool exclusive for R410A Gas leak detectorGas leak checkTool for HFC refrigerant Refrigerant recovery equipmentRefrigerant recoveryTool exclusive for R410A Refrigerant cylinderRefrigerant chargeTool exclusive for R410A Applied oilApply to flared sectionEster oil, ether oil and alkylbenzene oil (minimum amount)Ester oil, ether oil: Alkylbenzene oil: minimum amount Safety chargerPrevent compressor malfunction when charging refrigerant by spraying liquid refrigerantTool exclusive for R410A Charge valvePrevent gas from blowing out when detaching charge hoseTool exclusive for R410A Vacuum pumpVacuum drying and air purgeTools for other refrigerants can be used if equipped with adopter for reverse flow check(Usable if equipped with adopter for reverse flow)(Usable if equipped with adopter for reverse flow) Flare toolFlaring work of pipingTools for other refrigerants can be used by adjusting flaring dimension(Usable by adjusting flaring dimension)(Usable by adjusting flaring dimension) BenderBend the pipesTools for other refrigerants can be used Pipe cutterCut the pipesTools for other refrigerants can be used Welder and nitrogen gas cylinderWeld the pipesTools for other refrigerants can be used Refrigerant charging scaleRefrigerant chargeTools for other refrigerants can be used Vacuum gauge or thermistor vacuum gauge and vacuum valveCheck the degree of vacuum. (Vacuum valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)Tools for other refrigerants can be used Charging cylinderRefrigerant chargeTool exclusive for R410A : Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
Show 5 more labels / short text on this page
Dimension A · Dimension B · Flare cutting dimensions · Flare nut dimensions · (mm) [inch]
Page 9 of the Mitsubishi Electronics OC366 user manual — 3-1. UNIT CONSTRUCTION
Page 9 · click to enlarge
Page 9

3 OVERVIEW OF UNITS

3-1. UNIT CONSTRUCTION

Outdoor unitP36P48 Indoor unit that can be connectedCapacityType 06 ~ Type 36Type 06 ~ Type 54 Number of units1~ 6 unit1~ 8 unit Total system wide capacity50% ~130% of outdoor unit capacity
CMY-Y62-G-ECMY-Y64-G-ECMY-Y68-G-E Branching pipe componentsBranch header (2 branches)Branch header (4 branches)Branch header (8 branches)

Model Ceiling Ceiling Ceiling Concealed mounted Wall Mounted Concealed 4-way flow 2-way flow 1-way flow built-in Exposed Concealed (Fresh Air)*1 PLFY-P PLFY-P PMFY-P PEFY-P PDFY-P PKFY-P PCFY-P PFFY-P PEFY-P Capacity NCMU-E NBMU-E NLMU-E NBMU-E NMLU-E NMHU-E NMSU-E NMU-E NAMU-E NGMU-E NFMU-E NGMU-E NEMU-E NRMU-E NMHU-E-F 06 08 12 15 18 24 27 30 36 48 54

Ceiling Cassette Ceiling Suspended

Remote controllerNameM-NET remote controllerMA remote controller Model numberPAR-F27MEA-USPAR-21MAA Functions• A handy remote controller for use in conjunction with the Melans centralized management system. • Addresses must be set.• Address setting is not necessary.

*1. It is possible only by 1:1 system. (1 indoor unit of Fresh Air type is connected with 1 outdoor unit.) Operating temperature range (outdoor temperature) for fresh air type indoor units differ from other indoor units. Refer to 3-2(2).

Floor Standing · Decorative panel

Page 10 of the Mitsubishi Electronics OC366 user manual — (3) Guaranteed voltage 198~253V, 60Hz
Page 10 · click to enlarge
Page 10

3-2. UNIT SPECIFICATIONS

(1) Method for identifying MULTI-S model

  • Indoor unit < When using Model 30 >
  • Outdoor unit <When using model 48 >

P L F Y - P 30 N B M U - E PU M Y - P 48 N H M U -BS

L : Ceiling cassette K : Wall-mounted type E : Hidden skylight type C : Ceiling suspended type M : Ceiling cassette type F : Floor standing type

Outdoor unit model type

MULTI-S

Salt proof type Frequency conversion controller

N: Single phase 208/230V 60Hz

Indicates equivalent to Cooling capacity

NEW frequency converter one-to-many air conditioners (flexible design type)

Power supply NSingle phase 208/230V 60Hz

Indicates equivalent to Cooling capacity

(2) Operating temperature range

CoolingHeating Indoor-side intake air temperatureW.B. 15~24°C [59~75°F]D.B. 15~27°C [59~81°F] Outdoor-side intake air temperatureD.B. -5~46°C [23~115°F]*1W.B. -18~15°C [0~60°F]
  • In case of connecting fresh air type indoor unit
Capacity of Fresh air type indoorCoolingHeating Indoor-side and Outdoor-side intake air temperatureP30D.B.21~43[70~109°F] *2 W.B.15.5~35[60~95°F]D.B.-10~20[14~68°F] *3 P54D.B.21~43[70~109°F] *2 W.B.15.5~35[60~95°F]D.B.-5~20[23~68°F] *3

*2.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is lower than 21D.B.[70°FD.B.]. *3.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is higher than 20D.B.[68°FD.B.].

(3) Guaranteed voltage 198~253V, 60Hz

Show 12 more labels / short text on this page
Outdoor unit · UL model · PAC type · Refrigerant R410A/R22 commonness · Refrigerant R410A · Sub-number · M-NET control · Frequency conversion controller · Power supply · UL model · M-NET control · Unit model type
Page 11 of the Mitsubishi Electronics OC366 user manual — 4 SPECIFICATIONS
Page 11 · click to enlarge
Page 11

4 SPECIFICATIONS

Item Service Ref.PUMY-P36NHMU(-BS)PUMY-P36NHMUR1(-BS) Cooling CapacityBtu/h36,000 Heating CapacityBtu/h40,000 Input (Cool) *3kW3.22 Input Current (Cool) *3A14.23/15.74 Power factor (Cool) *3%98.4 Input (Heat) *3kW2.93 Input Current (Heat) *3A12.88/14.24 Power factor (Heat) *3%98.9 EER (Cool) *3Btu/h/W11.18 COP (Heat) *3W/W4.00 Connectable indoor units (Max.)6 Max. Connectable CapacityBtu/h46,800(130%) Power SupplySingle phase , 60Hz , 208/230V Breaker Size30A Max. fuse size40A Min.Circuit.Ampacity26A Sound level (Cool/Heat)dB49 / 51 External finishMunsell 3Y 7.8/1.1 Refrigerant controlLinear Expansion Valve Compressor Model Motor output kW Starting methodHermetic ModelANB33FDHMTANB33FDSMT Motor outputkW2.2 Starting methodInverter Crankcase heaterW— Heat exchangerPlate fin coil (Anti corrosion fin treatment) FanFan(drive) % No.Propeller fan % 2 Fan motor outputkW0.086 + 0.086 Airflowm3/min [CFM]100 [3,530] Dimensions (H%W%D)Wmm [in.]950 [37-13/32] Dmm [in.]330+30 [13+1-3/16) Hmm [in.]1,350 [53-5/32] Weightkg [lbs]130 [287] Refrigerant Charge kg [lbs] Oil (Model) L [oz]R410A Chargekg [lbs]8.5 [18.7] Oil (Model)L [oz]2.3 [73] (FV50S) Protection devicesHigh pressure protectionHP switch Compressor protectionDischarge thermo, Over current detectionCompressor thermo, Over current detection Fan motor protectionOverheating/Voltage protection Total Piping length (Max.)m [ft]120 [394] Farthestm [ft]80 [262] Max Height differencem [ft]50 [164]*1 Chargeless lengthm [ft]50 [164] Piping diameterLiquid:mm[inch]9.52 [3/8] Gas:mm[inch]15.88 [5/8] Guaranteed operation range(cool)-5~ 46 DB [23~115°F DB]*2 (heat)-18~ 15 WB [0~60°F WB]

Rating conditions Cooling Indoor : D.B. 26.7°C / W.B. 19.4°C [D.B. 80°F / W.B. 67°F] Outdoor : D.B. 35°C[D.B. 95°F] Heating Indoor : D.B. 21.1°C[D.B. 70°F] Outdoor : D.B. 8.3°C / W.B. 6.1°C [D.B. 47°F / W.B. 43°F]

Note.*1. 20m [70ft] : In case of installing outdoor unit lower than indoor unit. *2. 10~46°C [50~115°F]DB : In case of connecting PKFY-P06/P08 type indoor unit. *3. Electrical data is for only outdoor unit. (In case of connecting 2 indoor units of PLFY-P18BM type) Btu/h=kW × 3,412 CFM=K/min × 35.31 lbs=kg/ 0.4536 *Above specification data is subject to rounding variation.

Page 12 of the Mitsubishi Electronics OC366 user manual — 4 SPECIFICATIONS
Page 12 · click to enlarge
Page 12
Item Service Ref.PUMY-P48NHMU/NHMU/NHMU/NHMUR3(-BS) 1 2 Cooling CapacityBtu/h48,000 Heating CapacityBtu/h54,000 Input (Cool) *3kW4.97 Input Current (Cool) *3A24.0/21.7 Power factor (Cool) *3%99.5 Input (Heat) *3kW4.88 Input Current (Heat) *3A23.6/21.3 Power factor (Heat) *3%99.5 EER (Cool) *3Btu/h/W9.66 COP (Heat) *3W/W3.24 Connectable indoor units (Max.)8 Max. Connectable CapacityBtu/h62,400 (130%) Power SupplySingle phase , 60Hz , 208/230V Breaker Size30A Max. fuse size40A Min.Circuit.Ampacity26A Sound level (Cool/Heat)dB50 / 52 External finishMunsell 3Y 7.8/1.1 Refrigerant controlLinear Expansion Valve Compressor Model Motor output kW Starting methodHermetic ModelANB33FDCMT(NHMU(1)), ANB33FDHMT(NHMU2), ANB33FDSMT(NHMUR3) Motor outputkW2.4 Starting methodInverter Crankcase heaterW— Heat exchangerPlate fin coil (Anti corrosion fin treatment) FanFan(drive) % No.Propeller fan % 2 Fan motor outputkW0.086 + 0.086 Airflowm3/min [CFM]100 [3,530] Dimensions (H%W%D)Wmm [in.]950 [37-13/32] Dmm [in.]330+30 [13+1-3/16) Hmm [in.]1,350 [53-5/32] Weightkg [lbs]130 [287] Refrigerant Charge kg [lbs] Oil (Model) L [oz]R410A Chargekg [lbs]8.5 [18.7] Oil (Model)L [oz]2.3 [73] (MEL56/NHMU , FV50S/NHMU, NHMUR3) (1) 2 Protection devicesHigh pressure protectionHP switch Compressor protectionDischarge thermo, Over current detection(NHMU/NHMU/NHMU) 1 2 Compressor thermo, Over current detection(NHMUR3) Fan motor protectionOverheating/Voltage protection Total Piping length (Max.)m [ft]120 [394] Farthestm [ft]80 [262] Max Height differencem [ft]50 [164]*1 Chargeless lengthm [ft]50 [164] Piping diameterLiquid:mm[inch]9.52 [3/8] Gas:mm[inch]15.88 [5/8] Guaranteed operation range(cool)-5~ 46 DB [23~115°F DB]*2 (heat)-18~ 15 WB [0~60°F WB]

Rating conditions Cooling Indoor : D.B. 26.7°C / W.B. 19.4°C [D.B. 80°F / W.B. 67°F] Outdoor : D.B. 35°C[D.B. 95°F] Heating Indoor : D.B. 21.1°C[D.B. 70°F] Outdoor : D.B. 8.3°C / W.B. 6.1°C [D.B. 47°F / W.B. 43°F]

Page 13 of the Mitsubishi Electronics OC366 user manual — (2) Sample calculation (using the system described above in 5-1-1. (2) ):
Page 13 · click to enlarge
Page 13

5 DATA

5-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS

5-1-1. Method for obtaining system cooling and heating capacity: To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with the help of the tables on 5-2. STANDARD CAPACITY DIAGRAM.

(1) Capacity of indoor unit

Model number for indoor unit Model 06 Model 08 Model 12 Model 15 Model 18 Model 24 Model 27 Model 30 Model 36 Model 48 Model 54

Model Capacity 6 8 12 15 18 24 27 30 36 48 54

  • (2) Sample calculation 1 System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of the outdoor unit)
  • Outdoor unit PUMY-P48NHMU
  • Indoor unit PKFY-P08NAMU-E o 2 , PLFY-P18NLMU-E o 2 2 According to the conditions in 1 , the total capacity of the indoor unit will be: 8 o 2 + 18 o 2 = 52 3 The following figures are obtained from the 52 total capacity row of the standard capacity table (5-2.):

Capacity (Btu/h) Outdoor unit power consumption (kW) Outdoor unit current (A)/230V

Cooling Heating Cooling Heating Cooling Heating

A 48,900 B 54,500 5.01 4.71 21.9 20.6

5-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:

model capacity total model capacity of all indoor units

(1) The capacity of each indoor unit (Btu/h) = the capacity A (or B) o

(2) Sample calculation (using the system described above in 5-1-1. (2) ):

During cooling: During heating:

  • The total model capacity of the indoor unit is: 8000 o 2 + 18000 o 2 = 52000Btu/h Therefore, the capacity of PKFY-P08NAMU-E and PLFY-P18NLMU-E will be calculated as follows by using the formula in 5-1-2. (1):
  • The total model capacity of indoor unit is: 9000 o 2 + 20000 o 2 = 58000 Btu/h Therefore, the capacity of PKFY-P08NAMU-E and PLFY-P18NLMU-E will be calculated as follows by using the formula in 5-1-2. (1):

9000 58000 20000 58000

Model 08= 48,900 o = 7,520 Btu/h

Model 08=54,500 o = 8,460 Btu/h

Model 18= 48,900 o = 16,930 Btu/h

Model 18= 54,500 o = 18,790 Btu/h

8000 52000 · 18000 52000

Page 14 of the Mitsubishi Electronics OC366 user manual — Capacity(Btu/h) Power Consumption(kW) Current(A)/230V Current(A)/208V
Page 14 · click to enlarge
Page 14

5-2. STANDARD CAPACITY DIAGRAM * Before calculating the sum of total capacity of indoor units, please convert the value following the formula on 5-1-1.

5-2-1. PUMY-P36NHMU(-BS)/ PUMY-P36NHMUR1(-BS)

Total capacity of Indoor units* Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Capacity(Btu/h) Power Consumption(kW) Current(A)/230V Current(A)/208V

18 18,000 20,200 1.38 1.45 6.1 6.4 6.8 7.1 19 19,000 21,300 1.45 1.52 6.4 6.7 7.1 7.4 20 20,000 22,400 1.52 1.60 6.7 7.0 7.4 7.8 21 21,000 23,500 1.60 1.67 7.1 7.4 7.8 8.1 22 22,000 24,700 1.68 1.75 7.4 7.7 8.2 8.5 23 23,000 25,800 1.76 1.83 7.8 8.0 8.6 8.9 24 24,000 26,900 1.85 1.91 8.2 8.4 9.0 9.3 25 25,000 28,000 1.94 1.98 8.6 8.7 9.5 9.6 26 26,000 29,200 2.04 2.06 9.0 9.1 9.9 10.0 27 27,000 30,300 2.14 2.15 9.4 9.4 10.4 10.4 28 28,000 31,400 2.24 2.23 9.9 9.8 10.9 10.8 29 29,000 32,500 2.35 2.31 10.4 10.2 11.5 11.2 30 30,000 33,700 2.46 2.40 10.9 10.5 12.0 11.7 31 31,000 34,800 2.58 2.48 11.4 10.9 12.6 12.1 32 32,000 35,900 2.70 2.57 11.9 11.3 13.2 12.5 33 33,000 37,000 2.82 2.66 12.5 11.7 13.8 12.9 34 34,000 38,200 2.95 2.75 13.0 12.1 14.4 13.4 35 35,000 39,300 3.08 2.84 13.6 12.5 15.1 13.8 36 36,000 40,000 3.22 2.93 14.2 12.9 15.7 14.2 37 36,200 40,200 3.23 2.92 14.3 12.9 15.8 14.2 38 36,400 40,400 3.25 2.89 14.3 12.7 15.9 14.1 39 36,600 40,700 3.26 2.86 14.4 12.6 15.9 13.9 40 36,900 40,900 3.27 2.84 14.5 12.5 16.0 13.8 41 37,100 41,100 3.28 2.81 14.5 12.3 16.0 13.6 42 37,300 41,300 3.30 2.78 14.6 12.2 16.1 13.5 43 37,500 41,600 3.31 2.75 14.6 12.1 16.2 13.4 44 37,700 41,800 3.32 2.72 14.7 11.9 16.2 13.2 45 37,900 42,000 3.34 2.69 14.7 11.8 16.3 13.1 46 38,100 42,200 3.35 2.66 14.8 11.7 16.4 12.9

(CAPACITYabout several hundred Btu/h)
Page 15 of the Mitsubishi Electronics OC366 user manual — Capacity(Btu/h) Power Consumption(kW) Current(A)/230V Current(A)/208V
Page 15 · click to enlarge
Page 15

5-2-2. PUMY-P48NHMU/NHMU 1 /NHMU 2 /NHMUR3(-BS)

Total capacity of Indoor units* Cooling Heating Cooling Heating Cooling Heating Cooling Heating 24 24,000 26,900 2.11 2.32 9.2 10.2 10.2 11.2 25 25,000 28,000 2.20 2.41 9.6 10.5 10.6 11.6 26 26,000 29,200 2.29 2.50 10.0 10.9 11.1 12.1 27 27,000 30,300 2.38 2.59 10.4 11.3 11.5 12.5 28 28,000 31,400 2.48 2.68 10.8 11.7 12.0 13.0 29 29,000 32,500 2.58 2.78 11.3 12.1 12.4 13.4 30 30,000 33,700 2.68 2.87 11.7 12.6 12.9 13.9 31 31,000 34,800 2.78 2.97 12.2 13.0 13.4 14.4 32 32,000 35,900 2.89 3.07 12.6 13.4 14.0 14.8 33 33,000 37,000 3.00 3.17 13.1 13.9 14.5 15.3 34 34,000 38,200 3.11 3.28 13.6 14.3 15.0 15.8 35 35,000 39,300 3.23 3.38 14.1 14.8 15.6 16.3 36 36,000 40,400 3.35 3.49 14.6 15.2 16.2 16.9 37 37,000 41,500 3.47 3.60 15.2 15.7 16.8 17.4 38 38,000 42,700 3.60 3.71 15.7 16.2 17.4 17.9 39 39,000 43,800 3.72 3.82 16.3 16.7 18.0 18.5 40 40,000 44,900 3.85 3.93 16.8 17.2 18.6 19.0 41 41,000 46,000 3.99 4.05 17.4 17.7 19.3 19.6 42 42,000 47,200 4.12 4.17 18.0 18.2 19.9 20.1 43 43,000 48,300 4.26 4.28 18.6 18.7 20.6 20.7 44 44,000 49,400 4.41 4.41 19.3 19.3 21.3 21.3 45 45,000 50,500 4.55 4.53 19.9 19.8 22.0 21.9 46 46,000 51,700 4.70 4.65 20.5 20.3 22.7 22.5 47 47,000 52,800 4.85 4.78 21.2 20.9 23.4 23.1 48 48,000 54,000 4.97 4.88 21.7 21.3 24.0 23.6 49 48,300 54,200 4.98 4.83 21.8 21.1 24.1 23.3 50 48,500 54,300 4.99 4.79 21.8 20.9 24.1 23.2 51 48,700 54,400 5.00 4.75 21.8 20.8 24.1 23.0 52 48,900 54,500 5.01 4.71 21.9 20.6 24.2 22.8 53 49,100 54,600 5.01 4.67 21.9 20.4 24.2 22.6 54 49,300 54,800 5.02 4.63 21.9 20.2 24.3 22.4 55 49,600 54,900 5.03 4.59 22.0 20.1 24.3 22.2 56 49,800 55,000 5.04 4.55 22.0 19.9 24.3 22.0 57 50,000 55,100 5.04 4.51 22.0 19.7 24.4 21.8 58 50,200 55,200 5.05 4.47 22.1 19.5 24.4 21.6 59 50,400 55,300 5.06 4.43 22.1 19.4 24.4 21.4 60 50,600 55,500 5.07 4.39 22.1 19.2 24.5 21.2 61 50,800 55,600 5.07 4.35 22.2 19.0 24.5 21.0 62 51,100 55,700 5.08 4.31 22.2 18.8 24.6 20.8

Capacity(Btu/h) Power Consumption(kW) Current(A)/230V Current(A)/208V

(CAPACITYabout several hundred Btu/h)
Page 16 of the Mitsubishi Electronics OC366 user manual — OUTDOOR
Page 16 · click to enlarge
Page 16

5-3. CORRECTING COOLING AND HEATING CAPACITY

5-3-1. Correcting Changes in Air Conditions (1) The performance curve charts (Figure 1, 2) show the ratio by the temperature condition change when the rated capacity (total

capacity) and the rated input are presumed 1, under standard length (7.6 m [25 ft]) and standard temperature condition. • Standard conditions:

Indoor D.B. 26.7°C / W.B. 19.4°C [D.B.80°F / W.B.67°F] Outdoor D.B. 35°C [D.B.95°F] Indoor D.B. 21.1°C [D.B.70°F] Outdoor D.B. 8.3°C / W.B. 6.1°C [D.B.47°F / W.B.43°F]

  • Use the rated input and rated power values given in the characteristics table for each indoor unit.
  • The input is the single value of the outdoor unit; the input of each indoor unit must be added to obtain the total input.

(2) The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the

individual capacity at the rated time and the total capacity at the rated time.

individual capacity at the rated time Individual capacity under stated conditions = total capacity under the stated conditions o

total capacity at the rated time

(3) Capacity correction factor curve

Figure 2. Heating performance curve

Figure 1. Cooling performance curve

: DB(°FDB)

: WB(°FWB)

21.1 (70)

22 (71.6) 20 (68) 18 (64.4) 16 (60.8)

INDOOR

INDOOR

: WB(°FWB)

22 (71.6) 20 (68) 18 (64.4) 16 (60.8)

: DB(°FDB)

21.1 (70)

INDOOR

INDOOR

Cooling power consumption (ratio)

Heating power consumption (ratio)

0.4 -5 0 10 20 30 40 46 23 32 50 68 86 104 115

°C DB °F DB

14 -5 23 0 32 5 41 10 50 15 59 °C WB °F WB

OUTDOOR

OUTDOOR

  • 5-3-2. Correcting Capacity for Changes in the Length of Refrigerant Piping
  • During cooling, to obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total in-use indoor capacity, first find the capacity ratio corresponding to the standard piping length from Figure 3 at first, and then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
  • During heating, to find the equivalent piping length, first find the capacity ratio corresponding to standard piping length from Figure 3, and then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
Show 8 more labels / short text on this page
Rated cooling capacity · Rated heating capacity · Cooling capacity (ratio) · Heating capacity (ratio) · 15 (59) · 25 (77) · 15 (59) · 25 (77)
Page 17 of the Mitsubishi Electronics OC366 user manual — GROUND
Page 17 · click to enlarge
Page 17

(1) Capacity CORRECTION CURVE (Figure 3) Cooling

Mitsubishi Electronics OC366 — (1) Capacity CORRECTION CURVE (Figure 3) Cooling diagram (page 17)
Fig. 8 · (1) Capacity CORRECTION CURVE (Figure 3) Cooling

Heating P36, 48 models

70 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80[m]

[16] [33] [50] [70] [80] [100] [115] [130] [150] [165] [180] [195] [215] [230] [245] [260][ft]

(2) Method for Obtaining the Equivalent Piping Length

Equivalent length for type P48 = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m) Length of piping to farthest indoor unit: 80 m [262 ft]

5-3-3. Correction of Heating Capacity for Frost and Defrosting If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction factor from the following table to obtain the actual heating capacity. Correction factor diagram

Outdoor Intake temperature (W.B.°F) 43 39 36 32 28 25 21 18 14 Outdoor Intake temperature (W.B.°C) 6 4 2 0 -2 -4 -6 -8 -10 Correction factor 1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95

5-4. NOISE CRITERION CURVES

LINE PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) COOLING

MODE

LINE

PUMY-P48NHMU(-BS) PUMY-P48NHMU 1 (-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

MODE

COOLING

HEATING

HEATING

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)

Mitsubishi Electronics OC366 — LINE PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) COOLING diagram (page 17)
Fig. 9
Mitsubishi Electronics OC366 — LINE PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) COOLING diagram (page 17)
Fig. 10

10 63 125 250 500 1000 2000 4000 8000

10 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

MICROPHONE

1m [3.3ft]

UNIT

1.5m [4.9ft]

GROUND

Show 7 more labels / short text on this page
Heating 100 · Capacity ratio [%] · Cooling P36 model · Cooling P48 model · Corrected pipe length · 49 SPL(dB) · 50 SPL(dB)
Page 18 of the Mitsubishi Electronics OC366 user manual — 6 OUTLINES AND DIMENSIONS
Page 18 · click to enlarge
Page 18

6 OUTLINES AND DIMENSIONS

Mitsubishi Electronics OC366 — 6 OUTLINES AND DIMENSIONS diagram (page 18)
Fig. 11

1 FREE SPACE (Around the unit) 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS

……Refrigerant LIQUID pipe connection (FLARE): 9.52 (3/8 inch)

……Refrigerant GAS pipe connection (FLARE):15.88 (5/8 inch)

Page 19 of the Mitsubishi Electronics OC366 user manual — 6 OUTLINES AND DIMENSIONS
Page 19 · click to enlarge
Page 19
Mitsubishi Electronics OC366 — 6 OUTLINES AND DIMENSIONS diagram (page 19)
Fig. 12

1 FREE SPACE (Around the unit) 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS

……Refrigerant LIQUID pipe connection (FLARE):9.52 (3/8 inch)

……Refrigerant GAS pipe connection (FLARE):15.88 (5/8 inch)

Page 20 of the Mitsubishi Electronics OC366 user manual — 21S4
Page 20 · click to enlarge
Page 20

7 WIRING DIAGRAM

PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS

SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 Terminal Block TB3 Terminal Block TB7 Terminal Block MC Motor for Compressor MF1,MF2 Fan Motor 21S4 Solenoid Valve SV1 Solenoid Valve TH3 Thermistor TH4 Thermistor TH6 Thermistor TH7 Thermistor TH8 Thermistor 63HS High Pressure Sensor 63H High Pressure Switch 63L Low Pressure Switch CB Main Smoothing Capacitor ACTM

MULTI.B. Multi Controller Board Fuse F1,F2

N.F. Noise Filter Circuit Board Connection Lead LI/LO

M-P.B.

Connector Transmission Power Board CN1

Connector CN2

Switch SWU1

Switch SWU2

Digital Indicator LED1,2

LED LED3

Active filter Module RS Rush Current Protect Resistor

DCL

Connector CNAC

P.B. Power Circuit Board Connection Terminal U/V/W

Connector CNDC

Connector CN2

Connector CN4

Connector CN40

Connector CN41

Connector 63HS Connector 63H Connector 63L Connector CNF1,CNF2

Light Emitting Diodes LED1

Connector 21S4 Connector SV1

Use copper supply wires.

! WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2 minutes (input voltage: 240 V).

When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then wait for at least 1 minute. Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual. Do not replace the outdoor board without checking.

During normal operation The LED indicates the drive state of the controller in the outdoor unit.

[Example] When the compressor and SV1 are turned during cooling operation.

1 2 3 4 5 6 7 8

21S4

SV1

(SV2)

When faults requiring inspection occurs The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.

Show 37 more labels / short text on this page
Fuse<3A> F500 · Connection Lead<N-Phase> NI/NO · Switch<Display Selection> SW1 · Connection Terminal<Ground> EI · Switch<Function Selection> SW2 · Connector CNAC1/2 · Switch<Test Run> SW3 · Connector CN5 · Switch<Model Selection> SW4 · Switch<Function Selection> SW5 · Switch<Function Selection> SW6 · Switch<Function Selection> SW7 · Switch<Function Selection> SW8 · Transformer TRANS · Connector<Multi System> CNS1 · Connector<Centralized Control> CNS2 · Reactor · Terminal<L/N-Phase> TAB-S/T · Terminal<DCVoltage> TAB-P/P1/P2 · Terminal<DCVoltage> TAB-N/N1/N2 · Connector CN2~5 · Connector<Thermistor> TH3 · Connector CNDC · Connector<Thermistor> TH4 · Connector CNAF · Connector<Thermistor> TH7/6 · Inverter IPM · Connector<For Option> SS · Connector<For Option> CN3D · Connector<For Option> CN3S · Connector<For Option> CN3N · Connector<For Option> CN51 · Relay X501~505 · Bit · Compressor operated · Indication · Always lit
Page 21 of the Mitsubishi Electronics OC366 user manual — SW4 < + 1 MODEL SELECT>
Page 21 · click to enlarge
Page 21

TH7TH6 TH3 TH4 63HS 63H 63L

Mitsubishi Electronics OC366 — TH7TH6 TH3 TH4 63HS 63H 63L diagram (page 21)
Fig. 13

1 2 1 2 1 2 3 4 CN3D (WHT) 1 2 3

SS (WHT) 2 1 2 1 2 1 2 1 3 1

1 2 1 2 1 2 1 2 3 4 5 6 7

SW4 < + 1 MODEL SELECT>

MODELS

PUMY-P48NHMU

ON OFF 1 2 3 4 5 6

indicates a switch position. The black square ( )

(NoteOnly PUMY-P48NHMU 1 and PUMY-P48NHMU 1 -BS)

DIP SW4-4 for primary heating control : Set DIP SW4-4 when power is turned off at unit. DIP SW4-4 OFF : Disable primary heating function (Initial setting) DIP SW4-4 ON : Enable primary heating function

Page 22 of the Mitsubishi Electronics OC366 user manual — 21S4
Page 22 · click to enlarge
Page 22

PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 Terminal Block TB3 Terminal Block TB7 Terminal Block MC Motor For Compressor MF1,MF2 Fan Motor 21S4 Solenoid Valve

P.B. Power Circuit Board

Connection Terminal TABP1/P2/P

Switch SWU1

Connection Terminal Diode Bridge TABN1/N2/N

Switch SWU2

IPM DS2,DS3

Connector (Symbol of Board is CNLVB) CNLVB

63H High Pressure Switch 63L Low Pressure Switch

N.F. Noise Filter Circuit Board Connection Terminal LI/LO

Connector SS

63HS High Pressure Sensor

Connector CN3D

SV1 Solenoid Valve TH3 Thermistor TH4 Thermistor TH6 Thermistor TH7 TH8

Connector CN3S

Connector CN3N

Connector CN51

C.B.

LED LED3 Controller Circuit Board

LED LED1,LED2

Fuse F1,F2 Switch SW1

CE Main Smoothing Capacitor ACTM DCL

Relay X501~505 M-NET P.B.

ConnectionTerminal M-NET Power Circuit Board TP1

  • Use copper supply wires.
  • WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2 minutes (input voltage: 230 V). When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then wait for at least 1 minute.
  • Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual. Do not replace the outdoor board without checking.

[Example] When the compressor and SV1 are turned during cooling operation.

  • During normal operation
  • The LED indicates the drive state of the controller in the outdoor unit.

1 2 3 4 5 6 7 8

21S4

SV1

(SV2)

  • When faults requiring inspection occurs The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
Show 20 more labels / short text on this page
Switch<Function Selection> SW6 · Connection Terminal<U/V/W-Phase> TABU/V/W · Switch<Function Selection> SW7 · Connection Terminal<L/N-Phase> TABS/T · Switch<Function Selection> SW8 · Power Module · Connection Terminal<N-Phase> NI/NO · Connection Terminal<Ground> EI,E2 · 52C Relay 52C · Thermistor<Outdoor> Thermistor<Heatsink> · Switch<Function Selection> SW2 · Reactor · Switch<Test Run> SW3 · Active Filter Module · Switch<Model Selection> SW4 · Switch<Function Selection> SW5 · Bit · Compressor operated · Indication · Always lit
Page 23 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 23 · click to enlarge
Page 23
Mitsubishi Electronics OC366 — TH7TH6 TH3 TH4 63HS 63H 63L diagram (page 23)
Fig. 14

1 2 3 4 5 6 0 1 1 0 1 0 0 1 1 0 0 1

Page 24 of the Mitsubishi Electronics OC366 user manual — 1 1 1 1
Page 24 · click to enlarge
Page 24

8 NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION

8-1. TRANSMISSION SYSTEM SETUP

Address SW Address SW Address SW Address SW Address SW

Address SW Address SW Address SW Address SW Address SW

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

Address SW Address SW Address SW Address SW Address SW

1

Address SW Address SW

PUMY has no 100ths digit switch.

The address automatically become

connected to each refrigerant

Outdoor unit 051-100

Indoor unit 001-050

Remote controller 101-200

A transmission wire must be

system (outdoor and indoor).

"100" if it is set as "01~50".

Set addresses:

Show 22 more labels / short text on this page
controller 105 Remote · controller · 102 104 154 · 157 Remote · controller Remote · controller 107 Remote · controller Remote · controller · controller Remote · Transmission wire · Remote · Piping · For remote · For remote · controller · controller · Outdoor unit · Outdoor unit · For centralized · For centralized · management · management
Page 25 of the Mitsubishi Electronics OC366 user manual — P36, P48
Page 25 · click to enlarge
Page 25

8-2. REFRIGERANT SYSTEM DIAGRAM PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)

Refrigerant flow in cooling Refrigerant flow in heating

Pressure sensor (63HS) High pressure switch(63H)

Thermistor(TH6)

Check valve

Thermistor(TH3) (Pipe temperature) Oil separator

Discharge thermistor(TH4) Compressor thermistor(TH4) (P36NHMUR1,P48NHMUR3)

Capillary tube (for oil separator) : :2.5 % :0.8 % L1000(mm) [:(3/32) % :(1/32) % L(39-1/2)] inch

Refrigerant piping specifications <dimensions of flared connector> Unit:mm<inch>

Capacity Item Liquid piping Gas pipng

P06, P08, P12, P15, P18

:6.35

:12.7

P24, P30, P36, P48, P54

:9.52

:15.88

P36, P48

:9.52

:15.88

Show 24 more labels / short text on this page
Service port · Thermistor(TH7) (Outdoor temperature) · Stop valve · 4-way valve · Refrigerant Gas pipe · <5/8 inch> · Solenoid valve(SV1) · Strainer · Capillary tube · Distributor · Strainer · Check valve<Low pressure> · Strainer · Accumulator · Low pressure switch(63L) · Compressor · Heatsink thermistor(TH8) · Stop valve · Refrigerant Liquid pipe · <3/8 inch> · Strainer · Service port · Indoor unit · Outdoor unit
Page 26 of the Mitsubishi Electronics OC366 user manual — RC
Page 26 · click to enlarge
Page 26

8-3. SYSTEM CONTROL 8-3-1. Example for the System • Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed in the standard system with detailed explanation. The explanation for the system in this section : Use one single outdoor unit and multiple outdoor units for M-NET remote control system.

Use one single outdoor unit and multiple indoor units in the multiple outdoor units for the M-NET remote control system.

A. Example of a M-NET remote controller system (address setting is necessary.)

Example of wiring control cables Wiring Method and Address Setting

1. Standard operation

a. Use feed wiring to connect terminals M1 and M2 on

transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non- polarized 2 wire. b. Connect terminals M1 and M2 on transmission cable

OC

terminal block (TB5) for each indoor unit with the terminal block (TB6) for the remote controller (RC). c. Set the address setting switch (on outdoor unit P.C.B)

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S A B

S M1M2

M1M2

as shown below.

A B

Unit Indoor unit (IC)

Range 001 to 050

A B

  • 1 remote controller for each indoor unit.
  • There is no need for setting the 100 position on the remote controller.

RC

— Use the smallest address of all the indoor unit plus 50. Indoor unit address plus 100.

RC

(OC)

2. Operation using 2 remote controllers

a. Same as above. b. Same as above. c. Set address switch (on outdoor unit P.C.B) as

OC

shown below.

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

Unit Indoor Unit (IC)

Range 001 to 050

M1M2

S A B

S M1M2

M1M2

— Use the smallest address of all the indoor units plus 50. Indoor unit address plus 100. Indoor unit address plus 150.

(OC)

Main Remote Controller (RC)

A B A B A B A B

  • Using 2 remote controllers for each indoor unit.

Sub Remote Controller (RC)

a. Same as above. b. Connect terminals M1 and M2 on transmission cable

3. Group operation

terminal block (TB5) of the IC main unit with the most recent address within the same indoor unit (IC) group to terminal block (TB6) on the remote controller. c. Set the address setting switch (on outdoor unit P.C.B)

OC

as shown below.

Range 001 to 050

Setting Method Use the smallest address within the same group of indoor units. Use an address, other than that of the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main).

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S A B

S M1M2

M1M2

Use the smallest address of all the indoor units plus 50. Set at an IC (Main) address within the same group plus 100. Set at an IC (Main) address within the same group plus 150. d. Use the indoor unit (IC) within the group with the

A B

  • Multiple indoor units operated together by 1 remote controller

RC

most functions as the IC (Main) unit.

Combinations of 1 through 3 above are possible.

Show 26 more labels / short text on this page
Setting Method · Outdoor unit · 051 to 100 · Remote controller (RC) · 101 to 150 · Setting Method · Outdoor unit · 051 to 100 · 101 to 150 · RC (Main) · RC (Sub) · RC (Main) · RC (Sub) · 151 to 200 · IC(Main) · IC(Sub) · Unit IC (Main) · IC (Sub) · 001 to 050 · Outdoor Unit · 051 to 100 · Main Remote · 101 to 150 · Controller Sub Remote · 151 to 200 · Controller
Page 27 of the Mitsubishi Electronics OC366 user manual — A B
Page 27 · click to enlarge
Page 27
  • Name, Symbol and the Maximum Remote controller Units for Connection

Name Symbol Maximum units for connection Outdoor unit OC — Indoor unit IC One OC unit can be connected to 1-6 (P36)/1-8 (P48) IC units M-NET remote controller RC Maximum 2 RC for 1 indoor unit, Maximum 16 RC for 1 OC

Permissible Lengths Prohibited items

Longest transmission cable length (1.25 mm2 [AWG16]) L1 + L2, L2 + L3, L3 + L1 [ 200m [656ft] Remote controller cable length 1. If 0.5 to 1.25 mm2

  • M-NET remote controller (RC) and MA remote controller (MA) cannot be used together.
  • Do not connect anything with TB15 of indoor unit(IC).

OC

[AWG20 to AWG16] R1, R2 [10m [33ft] 2. If the length exceeds 10 meters [33ft], the exceeding section should be 1.25 mm2 [AWG16] and that section should be a value within the total extension length of the transmission cable and maximum transmission cable length. (L3)

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S A B

S M1M2

M1M2

A B

A B

TB15

MA

RC

OC

  • Use the indoor unit (IC) address plus 150 as the sub remote controller address. In this case, it should be 152.
  • Three or more remote controller (RC) cannot be connected to 1 indoor unit.

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S A B

S M1M2

M1M2

A B A B A B A B A B

RC

OC

TB3

TB7

TB5

TB15

TB5

TB15

M1M2

S A B

S M1M2

M1M2

S 1 2

S 1 2

  • The remote controller address is the indoor unit main address plus 100. In this case, it should be 101.

A B

RC

Show 8 more labels / short text on this page
Same as above · RC (Main) · RC (Sub) · RC (Main) · RC (Sub) · Same as above · IC(Main) · IC(Sub)
Page 28 of the Mitsubishi Electronics OC366 user manual — A B A B A B
Page 28 · click to enlarge
Page 28

B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller. (Shielding wires and address settings are necessary.)

OC

TB3

TB5

TB5

TB5

TB5

M1M2 S M1 M2 S

TB7

M1 M2 S

M1 M2 S

M1 M2 S

M1 M2 S

N

N

N

Examples of Transmission Cable Wiring

A B A B A B

RC

RC

RC

OC

TB3

TB5

TB5

TB5

M1 M2 S

M1M2 S

M1 M2 S

M1 M2 S

M1 M2 S

TB7

L 6 L 7

M1M2S

N

DV 12V

G-50A

A B

M1M2S

RC

: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address

a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well

for all OC-OC, and IC-IC wiring intervals. b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)

of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC). c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most

recent address within the same group to the terminal block on the remote controller (RC). d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit

Wiring Method Address Settings

(OC). e. DO NOT change the jumper connector CN41 on MULTI controller board. f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary.

Connect the terminal S on the power supply unit with the earth. g. Set the address setting switch as follows.

Unit Range Setting Method IC (Main) 01 to 00 Use the smallest address within the same group of indoor units.

IC (Sub) 01 to 50 Use an address, other than that of the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main).

Outdoor Unit 51 to 100 Use the smallest address of all the indoor units plus 50. *The address automatically becomes “100” if it is set as “01 - 50”. Main Remote Controller 101 to 150 Set at an IC (Main) address within the same group plus 100. Sub Remote Controller 151 to 200 Set at an IC (Main) address within the same group plus 150. MA Remote Controller — Unnecessary address setting (Necessary main/ sub setting)

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical

power has been turned on.

Show 20 more labels / short text on this page
· · (51) · (01) · (02) · (05) · (06) · · (101) · (105) · (155) · · (53) · (04) · (07) · (03) · Power Supply · Unit · (104) ·
Page 29 of the Mitsubishi Electronics OC366 user manual — OC
Page 29 · click to enlarge
Page 29
  • Name, Symbol, and the Maximum Units for Connection
  • Longest length via outdoor units : L 1 +L 2 +L 3 +L 4, L 1 +L 2 +L 3+ L 5, L 1 +L 2 +L 6 +L 7 [ 500 meters [1640 ft] (1.25 mm 2 [AWG16])
  • Longest transmission cable length : L 1, L 3 +L 4 , L 3+ L 5 , L 6, L 2 +L 6 , L 7 [ 200 meters (1.25 mm 2 [AWG16])
  • Remote controller cable length : R 1 , R 2 , R 2 + R 3 , R 4 [ 10 meters [33 ft] (0.5 to 1.25 mm 2 [AWG20 to AWG16]) If the length exceeds 10 meters [33 ft], use a 1.25 mm 2 [AWG16] shielded wire. The length of this section (L 5 ) should be included in the calculation of the maximum length and overall length.

Permissible Length Prohibited items

OC

TB3

M1M2 S M1 M2 S

M1 M2 S

TB5

M1 M2 S

TB5

M1 M2 S

TB5

M1 M2 S

TB5

TB7

A B A B A B

RC

RC

RC

OC

TB3

M1M2 S

TB5

TB5

TB5

M1 M2 S

TB7

M1 M2 S

M1 M2 S

M1 M2 S

M1M2S

DV 12V

A B

G-50A

M1M2S

RC

: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address

  • Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC).
  • Set all addresses to ensure that they are not overlapped.
  • M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wiring together.
Show 20 more labels / short text on this page
· · (51) · (01) · (02) · (05) · (06) · · (101) · (105) · (155) · · (53) · (03) · (04) · (07) · Power Supply · Unit · (104) ·
Page 30 of the Mitsubishi Electronics OC366 user manual — MA
Page 30 · click to enlarge
Page 30

C. Example of a MA remote controller system (address setting is not necessary.) NOTE : In the case of same group operation, need to set the address that is only main indoor unit.

Example of wiring control cables Wiring Method and Address Setting

1. Standard operation

a. Use feed wiring to connect terminals M1 and M2 on

transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non- polarized 2 wire. b. Connect terminals 1 and 2 on transmission cable

L 1 L 2

OC

terminal block (TB15) for each indoor unit with the terminal block for the MA remote controller (MA).

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S M1M2

S M1M2

M1M2

N 2

N 1

A B

A B

MA MA

  • 1 remote controller for each indoor unit.
2. Operation using 2 remote controllers

a. The same as above. b. The same as above. c. In the case of using 2 remote controllers, connect

OC

terminals 1 and 2 on transmission cable terminal block (TB15) for each indoor unit with the terminal block for 2 remote controllers. · Set the sub remote controller position for one of MA remote controller’s main switch. Refer to the installation manual of MA remote con-

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S M1M2

S M1M2

M1M2

N 4

N 6

N 3

N 5

A B

A B A B

A B

  • Using 2 remote controllers for each indoor unit.

MA

MA

MA MA

3. Group operation

a. The same as above. b. The same as above. c. Connect terminals 1 and 2 on transmission cable ter-

OC

minal block (TB15) of each indoor unit, which is doing group operation with the terminal block the MA remote controller. Use non-polarized tow wire. d. In the case of same group operation, need to set the

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S M1M2

S M1M2

M1M2

address that is only main indoor unit. Please set the address of the indoor unit with the most functions in the same group in the number that 01-50 is young.

N 7

A B

  • Multiple indoor units operated together by 1 remote controller

MA

N 8

Combinations of 1 through 3 above are possible.

troller

Page 31 of the Mitsubishi Electronics OC366 user manual — OC
Page 31 · click to enlarge
Page 31
  • Name, Symbol, and the Maximum Units for Connection

Permissible Lengths Prohibited items

Longest transmission cable length L1 + L2 [ 200 m [656 ft] (1.25 mm2 [AWG16]) MA remote controller cable length R1, R2 [ 200 m [656 ft]

The MA remote controller and the M-NET remote controller cannot be used together with the indoor unit of the same group.

OC

(0.3 – 1.25 mm2 [AWG22 to AWG16])

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S M1M2

S M1M2

M1M2

A B

A B

A B

RC

MA MA

Longest transmission cable length The same as above. MA remote controller cable length R3 +R4, R5 +R6 [ 200 m [656 ft]

Three MA remote controller or more cannot be connect with the indoor unit of the same group.

OC

(0.3 – 1.25 mm2 [AWG22 to AWG16])

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S M1M2

S M1M2

M1M2

A B A B

A B

A B A B

MA MA MA

MA

MA

Longest transmission cable length The same as above. MA remote controller cable length R7 +R8 [ 200 m [656 ft]

The second MA remote controller is connected with the terminal block (TB15) for the MA remote controller of the same indoor unit (IC) as the first remote control.

(0.3 – 1.25 mm2 [AWG22 to AWG16])

OC

TB3

TB7

TB5

S 1 2 TB15

TB5

S 1 2 TB15

M1M2

S M1M2

S

M1M2

M1M2

A B

A B

MA

MA

Page 32 of the Mitsubishi Electronics OC366 user manual — A B A B A B
Page 32 · click to enlarge
Page 32

D. Example of a group operation with 2 or more outdoor units and a MA remote controller.

(Shielding wires and address settings are necessary.)

OC

TB3

M1 M2 1 2 S TB5 TB15

TB5

1 2 TB15

TB5

1 2 TB15

TB5

1 2 TB15

M1 M2 S

M1M2 S

M1 M2 S

M1 M2 S

M1 M2 S

TB7

Examples of Transmission Cable Wiring

A B A B A B

MA

MA

MA

OC

TB3

TB5

1 2 TB15 1 2 TB15

TB5

1 2 TB15

TB5

M1 M2 S

M1M2 S

M1 M2 S

M1 M2 S

M1 M2 S

TB7

L 6 L 7

M1M2

S

DV 12V

A B

G-50A

M1M2

S

MA

: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address

a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well

for all OC-OC, and IC-IC wiring intervals. b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)

of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC). c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most

recent address within the same group to the terminal block on the remote controller (RC). d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit

Wiring Method Address Settings

(OC). e. DO NOT change the jumper connector CN41 on MULTI controller board. f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary.

Connect the terminal S on the power supply unit with the earth. g. Set the address setting switch as follows.

Unit Range Setting Method IC (Main) 01 to 00 Use the smallest address within the same group of indoor units.

IC (Sub) 01 to 50 Use an address, other than that of the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main).

Outdoor Unit 51 to 100 Use the smallest address of all the indoor units plus 50. *The address automatically becomes “100” if it is set as “01 - 50”. Main Remote Controller 101 to 150 Set at an IC (Main) address within the same group plus 100. Sub Remote Controller 151 to 200 Set at an IC (Main) address within the same group plus 150. MA Remote Controller — Unnecessary address setting (Necessary main/ sub setting)

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical

power has been turned on.

Show 23 more labels / short text on this page
· · (51) · m m · (01) · (02) · (05) · (06) · m4 · m · m · · m3 · m · · (53) · (03) · (04) · (07) · Power Supply · Unit · m ·
Page 33 of the Mitsubishi Electronics OC366 user manual — TB3
Page 33 · click to enlarge
Page 33
  • Name, Symbol, and the Maximum Units for Connection

Permissible Length Prohibited items

Longest length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6+L7 500 m [1640ft] (1.25 mm2

[AWG16] or more) Longest transmission cable length (M-NET cable): L1 and L3+L4 and L6 and L2+L6 and L7 200 m [656ft] (1.25 mm2 [AWG16] or more) Remote controller cable length: m1 and m1+m2+m3 and m1+m2+m3+m4 200 m [656ft] (0.3 to 1.25 mm2

[AWG20 to AWG16] )

TB3

M1 M2 1 2 S TB5 TB15

TB5

1 2 TB15

TB5

1 2 TB15

TB5

1 2 TB15

M1 M2 S

M1M2 S

M1 M2 S

M1 M2 S

M1 M2 S

TB7

A B A B A B

MA

MA

MA

OC

TB3

TB5

1 2 TB15 1 2 TB15

TB5

1 2 TB15

TB5

M1 M2 S

M1M2 S

M1 M2 S

M1 M2 S

M1 M2 S

TB7

M1M2

S

DV 12V

G-50A

A B

M1M2

S

MA

: Group 1 : Group 3 : Group 5 : Shielded Wire : Sub Remote Controller ( ): Address

  • Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC).
  • M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wiring together.
Show 14 more labels / short text on this page
(51) · (01) · (02) · (05) · (06) · · · (53) · (03) · (04) · (07) · Power Supply · Unit ·
Page 34 of the Mitsubishi Electronics OC366 user manual — CHECK TEST
Page 34 · click to enlarge
Page 34

9 TROUBLESHOOTING

9-1. CHECK POINTS FOR TEST RUN 9-1-1. Procedures of test run

(1) Before test run, make sure that following work is completed.

  • Installation related : Make sure that the panel of cassette type and electrical wiring are done. Otherwise electrical functions like auto vane will not operate normally.
  • Piping related : Perform leakage test of refrigerant and drain piping. Make sure that all joints are perfectly insulated. Check stop valves on both liquid and gas side for full open.
  • Electrical wiring related : Check ground wire, transmission cable, remote controller cable, and power supply cable for secure connection. Make sure that all switch settings of address or adjustments for special specification systems are correctly settled. (2) Safety check :

With the insulation tester of 500V, inspect the insulation resistance. Do not touch the transmission cable and remote controller cable with the tester. The resistance should be over 1.0 MΩ. Do not proceed inspection if the resistance in under 1.0 MΩ. Inspect between the outdoor unit power supply terminal block and ground first, metallic parts like refrigerant pipes or the electrical box next, then inspect all electrical wiring of outdoor unit, indoor unit, and all linked equipment . (3) Before operation :

a) Turn the power supply switch of the outdoor unit to on for compressor protection.For a test run, wait at least 12 hours from this point. b) Register control systems into remote controller(s). Never touch the on/ off switch of the remote controller(s). Refer to “ 9-1-2. Special

Function Operation and Settings (for M-NET Remote Controller)” as for settings . In MA remote controller(s), this registration is unneces- sary. (4) More than 12 hours later from power supply to the outdoor unit, turn all power switch to on for test run. Perform test run according to the

“Operation procedure” table of the bottom of this page. While test running, make test run reports . (5) When you deliver the unit after test run, instruct the end user for proper usage of the system using owners’ manual and the test run report

you made to certificate normal operation. If abnormalities are detected during test run, refer to “ 9-1-3. Countermeasures for Error During Test Run”. As for DIP switch setting of outdoor unit, refer to” 9-5. INTERNAL SWITCH FUNCTION TABLE”.

Check code indicator (see NOTE 1) Test run remaining time indicator (see NOTE 2)

Indoor unit liquid pipe temperature indicator

°C 1Hr.

TEST RUN

TEMP.

ON/OFF button ON/OFF LED (Lights up in operation)

(Cooling/Heating) OPERATION SWITCH button ,

ON/OFF

FILTER

AIR DIRECTION button

CHECK TEST

TIMER SET

AIR SPEED button

Operation procedure 1 Turn on the main power supply of all units at least 12 hours before test run. ”HO” appears on display panel for 3 min. 2 12 hours later, press TEST RUN button twice to perform test run. “TEST RUN “ appears on display panel. 3 Press OPERATION SWITCH button to make sure that air blows out. 4 Select Cooling (or Heating) by OPERATION SWITCH button to make sure that cool (or warm) air blow out. 5 Press Fan speed button to make sure that fan speed is changed by the button. 6 Press AIR DIRECTION button or LOUVER button to make sure that air direction is adjustable (horizontal, downward, upward, and each angle). 7 Check outdoor fans for normal operation 8 Check interlocked devices (like ventilator) for normal operation, if any. This is the end of test run operation. 9 Press ON/OFF button to stop and cancel test run.

NOTE 1 : If error code appears on remote controller or remote controller malfunction , refer to “ 9-1-3. Countermeasures for Error During Run”. NOTE 2 : During test run operation 2-hours off timer activates automatically and remaining time is on remote controller and test run stops 2 hours later. NOTE 3 : During test run, the indoor liquid pipe temperature is displayed on remote controller instead of room temperature. NOTE 4 : Depend on a model, “This function is not available” appears when air direction button is pressed, however, this is not malfunction.

Show 7 more labels / short text on this page
(M-NET Remote controller) · (see NOTE 3) · Display panel · TEST RUN indicator · TEST RUN button · LOUVER button · Control panel
Page 35 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 35 · click to enlarge
Page 35

9-1-2. Special Function Operation and Settings (for M-NET Remote Controller) • It is necessary to perform “group settings” and “paired settings” at making group settings of different refrigerant systems (multiple outdoor unit). (A) Group settings: Enter the indoor unit controlled by the remote controller, check the content of entries, and clear entries, etc. (B) Paired settings: Used to set the linked operation of a Lossnay unit. (1) Entering address: Follow the steps below to enter the addresses of the indoor unit using the remote controller.

  • a) Group settings
  • Turning off the remote controller: Press the ON/OFF button to stop operation (the indicator light will go off).
  • Changing to indoor unit address display mode: If the FILTER and k buttons on the remote controller are pressed simultaneously and held for 2 seconds, the display shown in Figure 1 will appear.
  • Changing address: Press the temperature adjustment buttons to change the displayed address to the address to be entered.
  • Entering the displayed address: Press the TEST RUN button to enter the indoor unit with the displayed address. The type of the unit will be displayed as shown in Figure 2 if entry is completed normally. If a selected indoor unit does not exist, an error signal will be displayed as shown in Figure 3. When this happens, check whether the indoor unit actually exists and perform entry again.
  • Returning to the normal mode after completing entry: Press the FILTER and k buttons simultaneously and hold for 2 seconds to return to the normal mode.

Figure 1. (A) Group setting display Figure 2. Normal completion of entry Figure 3. Entry error signal

Flashing “88” indicates entry error. Type of unit is displayed.

  • b) Paired Settings
  • Turn off the remote controller: Press the remote controller’s ON/OFF button to turn it off (the indicator light will go off).
  • Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds. * The above steps are the same as when making group settings (A).
  • Changing to the linked operation unit address display state: The display shown in Figure 4 will appear when the a button on the remote control is pressed.
  • Displaying the address of the Lossnay unit and linked indoor unit: In this situation, the indoor unit number will be the lowest address of the group. The Lossnay unit will not operate if this setting is incorrect. * If the temperature adjustment buttons are pressed, the address may be changed to the indoor unit that are to be linked. * If the time setting buttons are pressed, the address of the linked units may be changed to the address where it is desired to enter the Lossnay .
  • Linking the Lossnay and the indoor unit: The display shown in Figure 5 will appear when the TEST RUN button is pressed. The indoor unit whose address is displayed and the Lossnay unit with a linked address will operate in a linked manner. * If it is desired to display the address of the Lossnay in the indoor unit address, display the indoor unit address in the linked unit address, and the above content will also be recorded. * Apart from the indoor unit with the lowest address in the group, display and enter the addresses of the other indoor unit that are to be linked with the Lossnay unit.
  • Returning to the normal mode after completing entry: Press the FILTER and k buttons on the remote controller simultaneously and hold for 2 seconds to return to the normal mode.

Figure 4. (B) Making paired settings Figure 5. Completing normal entry

These alternating IC or LC displays will appear when entry is completed normally.

The addresses of indoor unit and linked units are displayed simultaneously.

A flashing “88” will appear if there is a problem with the entry (indicating that the unit does not exist).

(alternating display)

Page 36 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 36 · click to enlarge
Page 36

(2) Address check: Refer to section (1) regarding address entry.

  • a) In making group settings:
  • Turn off the remote controller: Press the remote controller's ON/OFF button to stop operation (the indicator light will go off).
  • Locate the indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for 2 seconds.
  • Display indoor unit address: The entered indoor units address and type will be displayed each time the button is pressed. * When one entry is made, only 1 address will be displayed no matter how many times the w button is pressed.
  • Returning to the normal mode after completing check: Simultaneously press the FILTER and k buttons on the remote controller and hold for 2 seconds to return to the normal mode.
  • b) In making paired settings:
  • Turn off the remote controller: Press the remote controller's ON/OFF button to stop operation (the indicator light will go off).
  • Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for 2 seconds.
  • Changing to the linked operation unit address display state: Press the a button on the remote control.
  • Displaying the address of the indoor unit to be checked: Change the address to that of the indoor unit to be checked by pressing the temperature adjustment buttons .
  • Displaying the address of the linked Lossnay unit: Press the w button to display the addresses of the linked Lossnay and indoor unit in alternation.
  • Displaying the addresses of other entered units: The addresses of the other entered units will be displayed in alternating fashion after resting the w button again.
  • Returning to the normal mode after completing the check: Simultaneously press the FILTER and k buttons on the remote controller and hold for 2 seconds to return to the normal mode.

(3) Clearing an address: Refer to section (1) regarding the address entry and section (2) regarding checking addresses. a) In making group settings:

  • Turn off the remote controller: The procedure is same as a) in (2) Address check.
  • Put in the indoor unit address display mode: The procedure is same as a) in (2) Address check.
  • Displaying the indoor unit address to be cleared: The procedure is same as a) in (2) Address check.
  • Clearing indoor unit address : Pressing the q button on the remote controller twice will clear the address entry of the displayed indoor unit, resulting in the display shown in Figure 6. The display shown in Figure 7 will appear if an abnormality occurs and the entry is not cleared. Please repeat the clearing procedure.
  • Returning to the normal mode after clearing an address: The procedure is same as a) in (2) Address check.

Figure 7. Display when an abnormality has

occurred during clearing Figure 6. Display after address has been

"88" will appear in the room temperature display location. "--" will appear in the room temperature display location.

  • b) In making paired settings:
  • Turn off the remote controller: The procedure is same as b) in (2) Address check.
  • Put into the indoor unit address display mode: The procedure is same as b) in (2) Address check.
  • Put into the linked unit address display mode: The procedure is same as b) in (2) Address check.
  • Display the address of the Lossnay unit or the indoor unit to be cleared.
  • Deleting the address of a linked indoor unit: Pressing the q button on the remote controller twice will clear the address entry of the displayed indoor unit, resulting in the display shown in Figure 8.
  • Returning to the normal mode after clearing an address: The procedure is same as b) in (2) Address check.

Figure 8. Display after address has been cleared normally

"--" will appear in the unit type display location when an address has been cleared normally.

"88" will appear in the unit type display location when an abnormality has occurred during clearing.

cleared normally · (altenating display)

Page 37 of the Mitsubishi Electronics OC366 user manual — 21S4
Page 37 · click to enlarge
Page 37

9-1-3. Countermeasures for Error During Test Run

  • If a problems occurs during test run, a code number will appear in the temperature display area on the remote controller (or LED on the outdoor unit), and the air conditioning system will automatically cease operating. Determine the nature of the abnormality and apply corrective measures.

Trouble Remarks Detected unit

Outdoor unit Multi controller board ~ Power board communiation trouble Check delay code 1202 Check delay code 1400 Check delay code 1402 Check delay code 1600 Check delay code 1601

Discharge/Compressor temperature trouble Low pressure trouble High pressure trouble Excessive refrigerant replenishment Insufficient refrigerant trouble Vacuum operation protection Water leakage Drain pump trouble Drain sensor trouble (THd) Overcurrent trouble (Overload, compressor lock) Power synchronization signal trouble Inverter trouble Overheat protection of radiator panel Power module trouble or Overcurrent trouble Fan controller trouble (Outdoor) Air inlet sensor trouble (TH21) or Discharge/Compressor temperature sensor trouble (TH4) Liquid pipe temp.sensor trouble (TH22) or Low pressure saturated temp.sensor trouble (TH6) Gas pipe temperature sensor trouble (TH23) Piping temperature sensor trouble (TH3) Outdoor temperature sensor trouble (TH7) Heatsink temperature sensor trouble (TH8) Pressure sensor trouble (63HS) Curnent sensor trouble Contact failure of drain float switch Dupricated unit address setting Transmission error (Transmission processor hardware error) Transmission error (Transmission route BUSY) Transmission and reception error (Communication trouble with transmission processor) Transmission and reception error (No ACK error) Transmission and reception error (No responsive frame error) MA communication receive signal error (no receive signal) MA commnication send signal error (starting bit derection error) MA commnication send error (H/W error) MA commnication receive error (Synchronous recovery error) Total capacity error Capacity code error Connecting unit number error Address set error Remote controller sensor trouble

1302 1500 1501 1505

Check delay code 4350 Check delay code 4165 Check delay code 4320 Check delay code 4330 Check delay code 4350 Check delay code 4500

4115 4220 4230 4250

Check delay code 1202

Check delay code 1211

5103 5105 5106 5110 5201

Check delay code 1205 Check delay code 1221 Check delay code 1214 Check delay code 1402 Check delay code 4310

Only M-NET Remote controller is detected.

Only M-NET Remote controller is detected.

Only M-NET Remote controller is detected.

Only M-NET Remote controller is detected.

Only M-NET Remote controller is detected. +

Only M-NET Remote controller is detected. +

Only MA Remote controller is detected.

Only MA Remote controller is detected.

Only MA Remote controller is detected.

Only MA Remote controller is detected.

7100 7101 7102 7105 7111

NOTE ) w

When the outdoor unit detects No ACK error/ No responsive frame error, an object indoor unit is treated

as a stop, and not assumed to be abnormal.

Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF. During normal operation The LED indicates the drive state of the controller in the outdoor unit.

[Example] When the compressor and SV1 are turned during cooling operation.

1 2 3 4 5 6 7 8

21S4

SV1

(SV2)

Show 10 more labels / short text on this page
Check code · Indoor Outdoor Remote · controller · Serial transmission trouble · 2502 2500 · 5300 5701 · Bit · Compressor operated · Indication · Always lit
Page 38 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 38 · click to enlarge
Page 38

Display Abnormal point and detecting method Causes Check points

High discharging/compressor temperature Abnormal if discharge/compressor temperature thermistor (TH4) exceeds 125 [257°F] or 110 [230°F] continuously for 5 minutes. Abnormal if pressure detected by high pressure sensor and converted to saturation temperature exceeds 40 [104°F] during defrosting and discharge/compressor temperature thermistor (TH4) exceeds 110 [230°F] .

Over-heated compressor operation caused by shortage of refrigerant Defective operation of stop valve Defective thermistor Defective outdoor controller board Defective action of linear expansion valve

Check intake super heat. Check leakage of refrigerant. Charge additional refrigerant. Check if stop valve is fully open. Turn the power off and check if 5101 is displayed when the power is turned again. When 5101 is displayed, refer to “Check points” for 5101. Check linear expansion valve.

Low pressure (63L operated) Abnormal if 63L is operated (under- 0.03MPa [-4.35PSIG]) during compressor operation. 63L: Low-pressure switch

Stop valve of outdoor unit is closed during operation. Disconnection or loose connection of connector (63L) on outdoor controller board Disconnection or loose connection of 63L Defective outdoor controller board Leakage or shortage of refrigerant Malfunction of linear expansion valve Short cycle of indoor unit Clogged filter of indoor unit Decreased airflow caused by dirt of indoor fan Dirt of indoor heat exchanger Locked indoor fan motor Malfunction of indoor fan motor Defective operation of stop valve (Not fully open) Clogged or broken pipe Locked outdoor fan motor Malfunction of outdoor fan motor Short cycle of outdoor unit Dirt of outdoor heat exchanger Decreased airflow caused by defective inspection of outside temperature thermistor (It detects lower temperature than actual temperature.) Disconnection or contact failure of connector (63H) on outdoor controller board Disconnection or contact failure of 63H connection Defective outdoor controller board Defective action of linear expansion valve Malfunction of fan driving circuit Solenoid valve (SV1) performance failure (High-pressure cannot be controlled by SV1.) High-pressure sensor defective High-pressure sensor input circuit defective in multi controller board

Check stop valve.

~ Check the connector (63L) on outdoor controller board.

Correct to proper amount of refrigerant. Check linear expansion valve. ~ Check indoor unit and repair defectives.

(1) High pressure (High-pressure switch 63H operated) Abnormal if high-pressure switch 63H operated ( + ) during compressor operation. + 4.15 MPa [602PSIG]

63HHigh-pressure switch

Check if stop valve is fully open.

(2) High pressure (High - pressure sensor 63HS detect) Abnormal if high-pressure sensor detects 4.31MPa [625PSIG] or more (or over 4.15MPa [602PSIG] for 3 minutes) during the compressor operation.

Check piping and repair defectives. ~ Check outdoor unit and repair defectives.

Check the inspected temperature of outside temperature thermistor on LED display.

~ Check the connector (63H) on outdoor controller board.

Check linear expansion valve.

Replace outdoor controller board. Check the solenoid valve performance.

Check the high-pressure sensor. Check the high-pressure sensor.

Superheat due to low discharge temperature

Disconnection or loose connection of discharge/compressor temperature thermistor (TH4) Defective holder of discharge temperature thermistor

Check the compressor installation conditions of discharge temperature thermistor (TH4).

Abnormal if discharge superheat is continuously detected less than or equal to -15 [-27°F] even though linear expansion valve has minimum open pulse after compressor starts operating for 10 minutes.

Page 39 of the Mitsubishi Electronics OC366 user manual — ON
Page 39 · click to enlarge
Page 39

Display Abnormal point and detecting method Causes Check points

Refrigerant shortage When the conditions of below detecting mode or are satisfied during the compressor operation.

Gas leakage, Gas shortage When heating operation, refrigerant shortage feeling operation (When heating, airflow or thermo OFF are mixed-operation, it causes a refrigerant shortage operation.) Ball valve performance failure (not full opened.) Error detection of discharge superheat 1) High-pressure sensor defective 2) Discharge temperature thermistor defective 3) Thermistor input circuit defective and high-pressure sensor defective in multi controller board

Check the refrigerant amount.

Check the operation condition and refrigerant amount.

When the below conditions are satisfied completely. 1. Compressor is operating in HEAT mode. 2. Discharge superheat is 80 [144°F] or more. 3. Difference of outer temperature thermistor (TH7) and outdoor piping temp. thermistor (TH3) applies to the formula of (TH7-TH3)

Check the ball valve is fully open.

1. Check the ball valve is fully open. 2) Check the resistance of discharge temperature thermistor. 3) According to “Outdoor unit functions”, set the SW2 and check the highpressure sensor level.

According to “Outdoor unit functions”, check the discharge temp. thermistor level. When the high-pressure sensor and discharge temp. thermistor are normal, if the above mentioned detecting pressure level and temp. are big different from the actual pressure and temp. replace the multi controller board. 1) Check the resistance of thermistor.

Error detection of TH7/TH3 1) Thermistor defective

2. Thermistor input circuit defective in multi controller board
2. According to “Outdoor unit functions”, check the outdoor pipe temp. thermistor level. 3) According to “Outdoor unit functions”, check the outer temp. thermistor level.

Check the drain function.

2500 (Float switch model)

Water leakage 1. Suspensive Abnormality when float switch detects to be in the water and drain pump turns on and off except during cooling or dry mode. 2. Abnormal when detecting that the drain pump turns on and off again within 1 hour after the detection of water leakage suspensive abnormality, and repeats the detection twice. is displayed. 3. The unit continues to detect abnormality while turned off. 4. To release water leakage suspensive abnormality · When not detecting that the drain pump turns off and on within 1 hour after detecting suspensive abnormality. · When turning to cooling operation or dry operation. · Detected that [liquid pipe temperature – room temperature] -10deg[-18°F]

Defective drain Clogged drain pump Clogged drain pipe Adverse flow of drain in other units Defective moving part of float switch Foreign matter on the moving part of float switch(ex. sludge etc.) Defective float switch

Check moving part of float switch.

Check the value of resistance with the float switch ON/OFF.

Operation mode: When drain pump turns on as float switch detects to be in the water except during cooling/dry mode

6 min. 6 min.

ON

OFF

OFF

15 sec.

15 sec.

15 sec. 15 sec. 15 sec.

In the water Water leakage suspensive abnormality

In the water Water leakage abnormality In the air In the water In the air

Within 1 hour Within 1 hour

Drain pump · Float switch ON

Page 40 of the Mitsubishi Electronics OC366 user manual — ( )
Page 40 · click to enlarge
Page 40

Display Abnormal point and detecting method Causes Check points

2502 (Drain sensor model)

Drain pump (DP) Drain sensor thermistor is heated, and when

  • Malfunction of drain pump Defective drain Clogged drain pump Clogged drain pipe Water drops on drain sensor
  • Drops of drain trickles from lead wire.
  • Clogged filter is causing wave of drain. Defective indoor controller board

Check if drain pump works. Check drain function.

only a fraction of the temperature rise is detected, the system determines abnormality to defer the error to stop operation and changes to protection mode to restart the system in 3 minutes. Drain pump is abnormal if the condition above is detected during suspensive abnormality. is displayed. Malfunction of drain pipe is constantly detected during drain pump operation.

Check the setting of lead wire of drain sensor and check clogs of the filter.

Replace indoor controller board when there is no problem in the above mentioned ~ .

Both of above mentioned ~ and the indoor linear expansion valve full-closed failure (leakage) happens synchronistically.

Check whether the indoor linear expansion valve leaks or not.

The unit enters to forced outdoor unit stop when following conditions, a) and b), are satisfied (while the above mentioned detection is performed). a) The drain sensor detects to be soaked in the water 10 times in a row. b) The room teperature subtracted with liquid pipe temperature is detected to be less than -10[-18°F] continuously for 30 minutes. When the drain sensor detects to be NOT soaked in the water, the detection record of a) and b) will be cleared.) + Drain pump abnormality (above ~ ) is detected before it becomes an outdoor unit forced stop condition. When indoor unit detects above condition, outdoor unit in same refrigerant sytem stops. Also, indoor unit except for Fan or OFF mode unit stop. 2502 is displayed on stopped unit. Detection timing of forced outdoor unit stop

(Note) Address/Attribute displayed on the remote controller shows the indoor unit which is cause of trouble.

( )

Constantly detected during unit operation and stop Releasing of forced outdoor unit stop Reset power supply of both abnormal indoor unit and its outdoor unit in same refrigerant system. Forced outdoor unit stop cannot be released by remote controller OFF. NOTE ) Above-mentioned ~ and ~ are detected independently.

Page 41 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 41 · click to enlarge
Page 41

Display Abnormal point and detecting method Causes Check points

2502 (Float switch model)

Drain pump (DP) Judge whether the sensor is in the water or in the air by turning the float switch ON/OFF. In the water: Detected that the float switch is ON for 15 seconds. In the air:Detected that the float switch is OFF for 15 seconds. When the float switch remains to be turned ON for 3 minutes after detected to be in the water, the drain pump is judged to be abnormal and will be displayed. *It takes 3 minutes and 15 seconds to detect abnormality including the time to judge to be in the water.

Malfunction of drain pump Defective drain Clogged drain pump Clogged drain pipe Defective moving part of float switch Foreign matter on the moving part of float switch(ex. sludge etc.) Defective float switch

Check if drain pump works. Check drain function.

Check moving part of float switch.

Check the value of resistance with the float switch ON/OFF. Change the indoor controller board.

Defective indoor controller board Defective driving circuit of drain pump Defective input circuit of float switch

The unit continue to detect abnormality while turned off. When the conditions below 1, 2 and forced

Check whether the indoor linear expansion valve leaks or not. Both of above mentioned ~ and the indoor linear expansion valve full-closed failure (leakage) happens synchronistically.

outdoor unit stop condition are met 1. Detected that [liquid pipe temperature – room temperature] -10deg[-18°F] for 30 minutes constantly. 2. Float switch detects to be in the water for 15 minutes constantly. *Before Forced outdoor unit stop Condition is met, the unit always detects - above. The indoor unit detecting above stops due to detecting abnormality the outdoor unit in same refrigerant system (compressor is inhibited to operate). The unit which stops due to detecting abnormality displays . Detection timing of forced outdoor unit stop Constantly detected during unit operation and stop Releasing of forced outdoor unit stop Reset power supply of both abnormal indoor unit and its outdoor unit in same refrigerant system. Forced outdoor unit stop cannot be released by remote controller OFF.

(Note) Address/Attribute displayed on the remote controller shows the indoor unit which is cause of trouble.

Drain sensor (THd, DS) When the drain sensor detects short/open while the operation.

Connector (CN31) contact failure (insertion failure)

Check whether the indoor controller board connector (CN31) is disconnected or not. Check whether the thermistor wiring is disconnected or not. Check the resistance of thermistor. If abnormality is not found in the method of the above-mentioned from to , it is defective of the indoor controller board.

Thermistor wiring disconnection or half disconnection Thermistor defective Indoor controller board (detecting circuit) failure

Compressor overcurrent interruption (When compressor locked) Abnormal if overcurrent of DC bus or compressor is detected within 30 seconds after compressor starts operating.

Open stop valve. Check facility of power supply. Correct the wiring (U·V·W phase) to compressor. Check compressor. Replace outdoor power circuit board.

Stop valve is closed. Decrease of power supply voltage Looseness, disconnection or converse of compressor wiring connection Defective compressor Defective outdoor power board

Over current27.5A
Page 42 of the Mitsubishi Electronics OC366 user manual —  Notes in case of 4220 error (Over voltage or voltage shortage)
Page 42 · click to enlarge
Page 42

Display Abnormal point and detecting method Causes Check points

4220 Decrease of power supply voltage Disconnection of compressor wiring Defective 52C Defective ACT module Disconnection or loose connection of CN5 on the outdoor power circuit board Defective 52C drive circuit of outdoor power circuit board Disconnection or loose connection of CN2 on the outdoor power circuit board Defective ACT module drive circuit of outdoor controller circuit board Disconnection or loose connection of CNAF

Overvoltage or voltage shortage

Check the facility of power supply. Correct the wiring (U·V·W phase) to

Abnormal if any of followings are detected during compressor operation;

compressor. (Outdoor power circuit board). P48NHMU(1)(-BS) : Replace 52C.

  • Decrease of DC bus voltage to 310V
  • Instantaneous decrease of DC bus voltage to 200V.
  • Increase of DC bus voltage to 400V.
  • Decrease of input current of outdoor unit to 0.5A only if operation frequency is more than or equal to 40Hz or compressor current is more than or equal to 5A.

P36NHMU(-BS)/NHMUR1(-BS) P48NHMU 2 (-BS)/MHMUR3(-BS) :

Replace noise filter circuit board

(Including 52C) Replace ACT module.

(Refer to 9-9. Test point ; the item of ACTM) Check CN5 wiring on the outdoor power

circuit board. Replace outdoor power circuit board.

Check CN2 wiring on the outdoor power

circuit board. Replace outdoor power circuit board. Check CNAF wiring. The 4220 error history can be confirmed

2 1 3 4 5 6 7 8

with SW1 No.189.

(Refer to 9-9. Test point ; the item of ACTM)

Notes in case of 4220 error (Over voltage or voltage shortage)

In PUMY models, bus voltage is controlled using ACTM. If ACTM is failed, bus voltage becomes uncontrollable and stops abnormally. To check the normality of operation, see DC bus voltage SW1 9-10. No.45, or determine DC bus voltage of the both sides of condenser C510 or CNDC connector which is on Multi controller board using a tester.

1. Check point
Self check switch No.45 SW110110100

Tester check The voltage (DC) of the condenser C510 or CNDC connector which is on Multi controller board

2. Check the voltage

ACTM condition DC bus voltage

Normal Target voltage 340-350V (DC)

Failure / no operation Less than 310V (DC) or over 400V (DC)

stopping (Including constraint electric continuity) and for 10 seconds after the compressor start to operate. When bus voltage is abnormal, see the table above (1.Check point) and check such as input voltage, wiring, 52C relay. To check ACTM itsef, see 9-9. Test point ; the item of ACTM. In case of ACTM failure, also check if there is the breaking of a wire in rush current protect resistor. As for PUMY-P48NHMU(1)(-BS), rush current protect resistor is resistor RS (not mounted on the board). For PUMY-

P36NHMU/NHMUR1(-BS), P48NHMU2,/NHMUR3(-BS) resistor RS1 is mounted on noise filter circuit board.

Temperature of heatsink Abnormal if heat sink thermistor(TH8) detects temperature indicated below 85 [185°F]

The outdoor fan motor is locked. Failure of outdoor fan motor Airflow path is clogged. Rise of ambient temperature

Check outdoor fan.

Check air flow path for cooling. Check if there is something which causes temperature rise around outdoor unit.

(Upper limit of ambient temperature is 46 [115°F].) Turn off power, and on again to check if 4230 is displayed within 30 minutes. Check thermistor temperature by microprocessor. Replace outdoor power circuit board.

Defective input circuit of outdoor power circuit board Failure of outdoor fan drive circuit

Replace outdoor controller circuit board.

(1) Power module Check abnormality by driving power module in case overcurrent is detected.

Outdoor stop valve is closed. Decrease of power supply voltage Looseness, disconnection or converse of compressor wiring connection

Open stop valve. Check facility of power supply. Correct the wiring (U·V·W phase) to compressor. (Outdoor power circuit board). Check compressor. Replace outdoor power circuit board.

Defective compressor Defective outdoor power circuit board

Contimued on the next page.

on · Defective thermistor

Page 43 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 43 · click to enlarge
Page 43

From the previous page.

Display Abnormal point and detecting method Causes Check points

(2) Compressor overcurrent interruption Abnormal if overcurrent DC bus or compressor is detected after compressor starts operating for 30 seconds.

Stop valve of outdoor unit is closed. Decrease of power supply voltage Looseness, disconnection or converse of compressor wiring connection Defective fan of indoor/outdoor units Short cycle of indoor/outdoor units Defective input circuit of outdoor controller board

Open stop valve. Check facility of power supply. Correct the wiring (U·V·W phase) to

compressor. (Outdoor power circuit board) Check indoor/outdoor fan. Solve short cycle. Replace outdoor controller circuit board.

Over current27.5A

Check compressor Before the replacement of the outdoor controller circuit board, disconnect the wiring to compressor from the outdoor

power circuit board and check the output voltage among phases, U, V, W, during test run (SW7-1 ON). No defect on board if voltage among phases (U-V, V-W and W-U) is same. Make sure to perform the voltage check with same performing frequency.

Outdoor fan motor Abnormal if rotational frequency of the fan motor is not detected during DC fan motor operation. Fan motor rotational frequency is abnormal if; • 100 rpm or below detected continuously

Failure in the operation of the DC fan motor

Check or replace the DC fan motor.

Failure in the outdoor circuit controller board

Check the voltage of the outdoor circuit controller board during operation.

for 15 seconds at 20 [68°F]: or more

Replace the outdoor circuit contrlooer board. (when the failure is still indicated even after performing the remedy 1 above.)

outside air temperature • 50 rpm or below or 1500 rpm or more

detected continuously for 1 minute.

Room temperature thermistor (TH21) When controller detects short (high temp.)/open (low temp.) in thermistor during the operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. In this time, is displayed. Then, if the thermistor recover in 3 minutes, it operates normally.

Check whether the connector (CN20) in the indoor controller board is connected or not.

Connector (CN20) contact failure

Check whether the thermistor wiring is disconnected or not.

Thermistor wiring disconnection or half disconnection

Check the resistance of thermistor;

0 [32°F] 15k 10 [50°F] 9.6k 20 [68°F] 6.3k 30 [86°F] 4.3k 40 [104°F]··· 3.0k

ShortDetected 90 [194°F] or more

When there is no problem in above mentioned , replace the indoor controller board.

Detecting circuit failure in the indoor controller board

OpenDetected –40 [-40°F] or less

Discharge/Compressor temperature thermistor (TH4)

When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.

Connector (TH4) contact failure Check whether the connector (TH4) in the multi controller board is connected or not.

When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.

Thermistor wiring disconnection or half disconnection

Check whether the thermistor wiring is disconnected or not.

For 10 minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, above-mentioned short/open are not detected.

Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor. 0 [32°F] about 700k 10 [50°F] about 410k 20 [68°F] about 250k 30 [86°F] about 160k 40 [104°F]··· about 104k

Short: 216 [421°F] or more (1k) Open: 0 [32°F] or less (700k)

2 1 3 4 5 6 7 8

Set the SW1 to

When the temperature in multi controller board is not an actual temperature, replace the multi controller board.

1.3Open 219.4: Short

Defective compressor · Thermistor failure · on

Page 44 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 44 · click to enlarge
Page 44

Display Abnormal point and detecting method Causes Check points

5102 Liquid pipe temperature thermistor (TH22)

When the thermistor detects short/open during the operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. In this time, is displayed. Then, if the thermistor recover in 3 minutes, it operates normally.

Connector (CN21 or CN44) contact failure

Check whether the connector (CN21 or CN44) in the indoor controller board is connected or not.

Thermistor wiring disconnection or half disconnection

Check whether the thermistor wiring is disconnected or not.

ShortDetected 90 [194°F] or more Thermistor failure

Check the resistance of thermistor;

OpenDetected -40 [-40°F] or less

0 [32°F] 15k

10 [50°F] 9.6k

20 [68°F] 6.3k

30 [86°F] 4.3k

40 [104°F] ···3.0k

Detecting circuit failure in the indoor controller board

When there is no problem in above mentioned , replace the indoor controller board.

Low pressure saturation temperature thermistor (TH6)

When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.

Connector (TH6) contact failure Check whether the connector (TH6) in the multi controller board is connected or not.

When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.

Thermistor wiring disconnection or half disconnection

Check whether the thermistor wiring is disconnected or not.

For 10 minutes after starting compressor, heating mode, above-mentioned short/open are not detected.

Thermistor failure Check the resistance of thermistor;

0 [32°F] 15k

Short90 [194°F] or more

10 [50°F] 9.6k

20 [68°F] 6.3k

Open-40 [-40°F] or less

30 [86°F] 4.3k

40 [104°F]···3.0k

2 1 3 4 5 6 7 8

Multi controller board input circuit failure

Set the SW1 to

When the temperature in multi controller board is not an actual temperature, replace the multi controller board.

-42.5Open
91.9Short

on

Page 45 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 45 · click to enlarge
Page 45

Display Abnormal point and detecting method Causes Check points

5103 Gas pipe temperature thermistor (TH23)

When the thermistor detects short/open after 3minutes-continuous thermo ON during cooling or dry operation, the operation stops and the operation changes to protect mode of restarting in 3 minutes. If the thermistor does not recover in 3 minutes, the operation stops due to detecting abnormality. In this time, is displayed. Then, if the thermistor recovers in 3 minutes, it operates normally.

Connector (CN29 or CN44) contact failure

Check whether the connector (CN29 or CN44) in the indoor controller board is connected or not.

Thermistor wiring disconnection or half disconnection

Check whether the thermistor wiring is disconnected or not.

Thermistor failure Check the resistance of thermistor;

ShortDetected 90 [194°F] or more

0 [32°F] 15k

10 [50°F] 9.6k

OpenDetected -40 [-40°F] or less

20 [68°F] 6.3k

30 [86°F] 4.3k

40 [104°F]···3.0k

Detecting circuit failure in the indoor controller board

When there is no problem in above mentioned , replace the indoor controller board.

5105 Pipe temperature / judging defrost thermistor (TH3)

When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.

Connector (TH3) contact failure Check whether the connector (TH3) in the multi controller board is connected or not.

When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.

Thermistor wiring disconnection or half disconnection

Check whether the thermistor wiring is disconnected or not.

Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.

For 10 minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, above-mentioned short/open are not detected.

0 [32°F] 15k

Short88 [190°F] or more (0.4k )

10 [50°F] 9.6k

Open-39 [-38°F] or less (115k )

20 [68°F] 6.3k

30 [86°F] 4.3k

40 [104°F]···3.0k

2 1 3 4 5 6 7 8

Multi controller board input circuit failure

Set the SW1 to When the temperature in multi controller board is not an actual temperature, replace the multi controller board.

-42.5Open
91.9Short

on

Page 46 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 46 · click to enlarge
Page 46

Display Abnormal point and detecting method Causes Check points

5106 Outdoor temperature thermistor (TH7)

Connector (TH7) contact failure Check whether the connector (TH7)

in the multi controller board is connected or not. When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3 minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.

Thermistor wiring disconnection or half disconnection

Check whether the thermistor wiring is disconnected or not.

When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.

Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.

0 [32°F] 15k 10 [50°F] 9.6k 20 [68°F] 6.3k 30 [86°F] 4.3k 40 [104°F]···3.0k

For 10 minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, above-mentioned short/open are not detected. Short: 90 [194°F] or more Open: -40 [-40°F] or less

2 1 3 4 5 6 7 8

Multi controller board input circuit failure

Set the SW1 to When the temperature in multi controller board is not an actual temperature, replace the multi controller board.

-42.5Open
91.9Short

5110 Heatsink temperature thermistor (TH8) (internal thermistor of power module)

Connector (TH8) contact failure.

Check whether the connector (TH8) in the power circuit board.

When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.

Thermistor wiring disconnection or half disconnection.

Check whether the thermistor wiring is disconnected or not.

Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.

When controller detects short/open in thermistor at just before of restarting, the unit stops due to detecting abnormality. In this time, is displayed.

0 [32°F] 180k 10[50°F] 105k 20 [68°F] 63k 30 [86°F] 39k 40 [104°F]···25k

For 10 minutes after starting compressor, for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.

2 1 3 4 5 6 7 8

Short:102 [216°F] or more Open: -27 [-17°F] or less

Power board input circuit failure Set the SW1 to When the temperature in multi controller board is not an actual temperature, replace the power board.

-81.0Open 999.9: Short

Wrong setting of model setting switch (SW4)

See 9-5. SWITCH FUNCTION TABLE

; SW4 model switching, then set correctly. *When SW4-1 is on, it will be 5110 error. Set correctly.

on · Thermistor failure · on

Page 47 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 47 · click to enlarge
Page 47

Display Abnormal point and detecting method Causes Check points

When detected pressure in high-pressure sensor is 1 MPa [145PSIG] or less during the operation, the compressor stops and restarts operation in 3 minutes.

High-pressure sensor failure Check the high-pressure sensor.

When the detected pressure is 1 MPa [145PSIG] or less at just before of restarting, the compressor stops due to detecting abnormality. In this time, is displayed.

Internal pressure decrease by gas leakage

Check the internal pressure.

For 3minutes after starting compressor, for defrosting or for 3 minutes after recover of defrosting, abnormality is not determined as abnormality.

Connector contact failure, disconnection

Check the high-pressure sensor.

Multi controller board input circuit failure

Check the high-pressure sensor.

Current sensor error Abnormal if current sensor detects –1.5A to 1.5A during compressor operation.

Disconnection of compressor wiring Defective circuit of current sensor on outdoor power circuit board

Correct the wiring (U·V·W phase) to compressor. (Outdoor power circuit board). Replace outdoor power circuit board.

(This error is ignored in case of SW7-1 ON.)

Abnormal if input current exceeds 38A or 34A continuously 10 seconds. (Current sensor on noise filter board detects input current.)

Decrease of power supply voltage Check the facility of power supply.

5701 Disconnected float switch connector Abnormal if detected that the float switch connector is disconnected(open) during operation

1. Disconnection of connecor(CN4F) Check the disconnetion of connector(CN4F) on the indoor controller board.

6600 Duplex address error

There are 2 units or more with the same address among the outdoor unit or indoor unit or lossnay controller, remote controller.

Look for the unit, which is source of abnormality with the same address. When the same address is found, correct the address and turn off power supply of outdoor unit, indoor unit, and lossnay for 2 minutes or more as the same time. Then, turn on power supply.

Detected error when transmission of unit with the same address is confirmed.

When noise has occurred in the transmission signal, and the signal

Check the transmitted wave and the noise on the transmission line.

has changed.

6602 Transmission processor H/W error

When the transmission line is constructed with the current flowed, turn off power supply of outdoor unit, indoor unit and lossnay for 2 minutes or more as the same time. Then, turn on power supply. Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.

When the wiring for either of the indoor unit, the outdoor unit or lossnay transmission line is constructed or polarity is changed with the power supply turned on, the transmission waves change in case that the transmission data collides mutually. It causes to detect error.

'' 1 '' shows on the transmission line though the transmission processor transmitted '' 0''.

Transmission processor circuit failure

Check the transmitted wave and the noise on the transmission line. When the transmission data has changed by the noise.

Pressure sensor (63HS)

Page 48 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 48 · click to enlarge
Page 48

Display Abnormal point and detecting method Causes Check points

6603 Transmission bus busy error

Over error by collision The transmission processor cannot be transmitted since a short cycle voltage of the noise etc. mixes on the transmission line consecutively.

Check whether the transmission line of the indoor unit, fresh master, lossnay and remote controller is connected to the outdoor unit terminal board (TB7) for centralized controller or not.

Abnormality when the state, which cannot be transmitted by collision of transmission, is consecutive for 8 to 10minutes.

The transmission volume increases and cannot be transmitted since the wiring method is mistaken and the routing technique to the terminal board (TB3) for the transmission line of the outdoor unit and the terminal board (TB7) for centralized control cannot be transmitted.

Check whether the transmission line with the other refrigerant system of the indoor unit and lossnay is connected to the outdoor unit terminal board (TB3) for transmission or not.

The state that data cannot to be output to the transmission line by the noise happens for 8 to 10minutes consecutively.

The share becomes high since the data exists together to other transmitted data by a defective repeater (function which connects and intercepts the transmission of controlling system and centralized control system), and it causes abnormal detection.

Check whether the outdoor unit terminal board for transmission line (TB3) and for centralized controller (TB7) are connected or not.

Check the transmitted wave and the noise on the transmission line.

Signal communication error with transmission processor 6606

The data of the unit/transmission processor was not normally transmitted due to accidental disturbance such as noise and lightening surge.

Turn off power supply of outdoor unit, indoor unit, and lossnay for 2 minutes or more at the same time. Then, turn on power supply. It normally recovers from the malfunction that happens by chance. When same abnormality occurs again, it is defective of the controller.

Signal communication error between unit processor and transmission processor

The address transmission from the unit processor was not normally transmitted by the hardware of transmission processor defective.

Page 49 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 49 · click to enlarge
Page 49

Display Abnormal point and detecting method Causes Check points

6607 No ACK (Acknowledgement) Abnormality which controller of the sending side detects when there is no answer (ACK) from other side though data was transmitted once. It is detected 6 times every 30seconds continuously.

Factor that does not related to origin Turn off power supply of outdoor unit, indoor unit fresh master and lossnay for 2 minutes or more at the same time. Then, turn on power supply. It recovers normally at the malfunction that happens by chance.

Since the address switch was changed with the current passed, the unit in the last address does not exist.

Check the address switch in the address, which occurs abnormality. Decline of transmission voltage and signal by transmission line tolerance over

· The furthest point···200m

· Remote controller line···(12m) (Refer to 8-3.)

Check whether the transmission line is connected / loosen or not at origin. (Terminal board or connector)

Decline of transmission line voltage and signal by unmatched kind of line.

Line diameter···1.25 Aor more

Check whether the transmission line tolerance is over or not.

Decline of transmission line voltage and signal by a number of over-connected units.

Check whether the kind of transmission line is mistaken or not.

Miss operation of origin controller, which happens by chance.

When there is any trouble from above -, turn off power supply of outdoor unit, indoor unit and lossnay for 2 minutes or more at the same time. Then, turn on power supply.

When there is not any trouble in single refrigerant system (1 outdoor unit) from above -, controller defective in displayed address and attribute. When there is not any trouble in different refrigerant system (2 outdoor unit or more) from above -, determine it after . When the address, which should not exist, is an origin, since there is the indoor unit which memorizes the address data, cancel the unnecessary address data by the manual setting function of remote controller.

When the cause of displayed address and attribute is on the outdoor unit side.

Contact failure of outdoor unit or indoor unit transmission line (The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the outdoor unit.)

However, they are limited to the system, which sets the group between different refrigerant systems, or which fresh master /lossnay are connected.

Indoor unit transmission connector (CN2M) disconnection

Sending/receiving signal circuit failure in the indoor/outdoor unit

When there is not any trouble from above -, replace the displayed address/attribute controller board.

When operating with multi refrigerant system indoor units, the remote controller transmits the signal to the indoor unit after the other refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality.

When the cause of displayed address and attribute is on the indoor unit side.

In this time, when the error does not recover to normal, the outdoor unit multi controller board (repeater circuit) defective is expected.

Check the recovery by replacing the multi controller board one by one.

Contact failure of remote controller or indoor unit transmission line.

Indoor unit transmission connector (CN2M) disconnection.

(The remote controller detects when there is no reply (ACK) on transmitting from the remote controller to the indoor unit.)

Sending/receiving signal circuit failure in the indoor unit or remote controller.

Continued on the next page.

Show 6 more labels / short text on this page
· Shield line-CVVS,CPEVS · · · · Original controller defective ·
Page 50 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 50 · click to enlarge
Page 50

From the previous page.

Display Abnormal point and detecting method Causes Check points

When the cause of displayed address and attribute is on the remote controller side.

When operating with multi refrigerant system indoor units, the indoor units transmits the signal to the remote controller after the other refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality.

(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the remote controller unit.)

Contact failure of remote controller or indoor unit transmission line

Indoor unit transmission connector (CN2M) disconnection Sending/receiving signal circuit failure in the indoor unit or remote controller

When the cause of displayed address and attribute is on the fresh master side.

When synchronized operating with other refrigerant system fresh master, the indoor units transmits the signal to the fresh master after the fresh master and same refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality.

(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the fresh master.)

Contact failure of fresh master or indoor unit transmission line

Indoor unit or fresh master transmission connector (CN2M) disconnection

Sending/receiving signal circuit failure in the indoor unit or fresh master

When the cause of displayed address and attribute is on the lossnay side.

When the lossnay power supply is Off, the indoor unit detects abnormality at signal transmitting to the lossnay.

(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the lossnay.)

When synchronized operating with other refrigerant system lossnay, the indoor units transmits the signal to the lossnay after the lossnay and same refrigerant system outdoor unit is turned off or turned on again in 2 minutes, and detects abnormality

Contact failure of lossnay or indoor unit transmission line

Indoor unit transmission connector (CN2M) disconnection

Sending/receiving signal circuit failure in the indoor unit or lossnay

When the controller of displayed address and attribute is not recognized

Since the address switch was changed with the current passed, the unit in the last address does not exist.

Since the fresh master/lossnay address are changed after synchronized setting of fresh master / lossnay by the remote controller, abnormality is detected at transmitting from the indoor unit.

· ·

Page 51 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 51 · click to enlarge
Page 51

Display Abnormal point and detecting method Causes Check points

Transmission repeats the failure by the noise etc. 6608 No response

Check the transmission wave and noise on the transmission line. Though there was a replay (ACK) of having received signal from the other side, it is the abnormality when the response command does not return. The sending side detects the abnormality continuously six times every 30 seconds. Note) Address/Attribute displayed on the remote controller shows the controller, which did not response.

Decline of transmission voltage and signal by transmission line tolerance over

Turn off power supply of outdoor unit, indoor unit and lossnay for 2 minutes or more at the same time. Then, turn on power supply again. It recovers normally at the malfunction that happens by chance. When same abnormality occurs again, it is defective of displayed address and attribute.

· The furthest point···200 m [656 ft]

· Remote controller line···(12 m [39 ft]) (Refer to 8-3.)

Decline of transmission line voltage and signal by unmatched kind of line

Wire diameter···1.25 A [AWG16] or more

Mis-operation of origin controller, which happens by chance

Signal reception(Remote controller) Following symptoms are regarded as abnormality.

Defect of the transmission and reception circuit of the remote controller

  • ~ Perform a check of the remote controller. According to the results, perform the following disposals.
  • When "RC OK" is displayed The remote controller is normal. Turn off the power supply and turn it on again. If "HO" or "PLEASE WAIT" is displayed for 4 minutes or more, replace the indoor controller board.
  • When "RC NG" is displayed Replace the remote controller.
  • When "RC 6832 or 6833" or "ERC 00-66" is displayed These displays may be due to noise, etc. Set one remote controller to main remote controller and the other to sub-remote controller.

Defect of the transmission and reception circuit of the indoor controller board

1. When the remote controller cannot receive the signal from indoor controller normally even once for 3 minutes.

Noise occurs on the transmission line of the remote controller.

2. When the remote controller cannot receive the signal even once for 2 minutes

All remote controllers are set as sub-remote controller.

Signal transmission(Remote controller) Following symptoms are regarded as abnormality.

Defect of the transmission and reception circuit of the remote controller

Noise occurs on the transmission line of the remote controller.

1. When sub-remote controller cannot transmit the signal to the transmission path for 6 minutes.

There are 2 main remote controllers.

2. When the remote controller cannot finish transmitting the signal for 30 times on end.

7100 Connecting total models of the indoor unit exceed the specified level.

Check the total models of connected indoor unit. Total capacity When connected total models of the indoor units exceed the specified level (130% of the outdoor unit models), error code is displayed.

· PUMY-P36NHMU/NHMUR1 ( ~ code 26) · PUMY-P48NHMU(1) ( ~ code 34) · PUMY-P48NHMU2/NHMUR3 ( ~ code 35)

Check the model code registration switch (indoor controller board SW2) of connected indoor unit.

There is a mistake in the registration of model name code of the outdoor unit.

Check the model code registration switch (outdoor multi controller board SW4) of the outdoor unit.

· Shield wire-CVVS,CPEVS · 6831 6834 · 6832 6833

Page 52 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 52 · click to enlarge
Page 52

Display Abnormal point and detecting method Causes Check points

7101 Capacity code error When the connected indoor unit models cannot be connected, is displayed.

The indoor unit models is not possible to connect.

Check the model code registration switch (indoor controller board SW2) in the connected indoor unit. The indoor unit of 06-54 (code 4-28) is possible to connect. The outdoor unit SW1 operation can check model code of the connected indoor units.

2 1 3 4 5 6 7 8

Code of indoor unit No.1

2 1 3 4 5 6 7 8

Code of indoor unit No.2

2 1 3 4 5 6 7 8

Code of indoor unit No.3

2 1 3 4 5 6 7 8

Code of indoor unit No.4

2 1 3 4 5 6 7 8

Code of indoor unit No.5

2 1 3 4 5 6 7 8

Code of indoor unit No.6

2 1 3 4 5 6 7 8

Code of indoor unit No.7

2 1 3 4 5 6 7 8

Code of indoor unit No.8

7102 Number of connecting unit over

When the connecting unit exceeds a number of limitations, error code is displayed.

Connecting unit exceeds a number of limitations. It is assumed abnormality excluding the following cases;

Check whether the connecting unit exceeds a number of limitations or not.

The indoor unit can be totally connected up to 6(P36)/8(P48) units. The indoor unit can be connected up to 8 units.

Even if the indoor unit is not connected, becomes is display.

Ventilation unit connecting is only 1unit.

7105 Address setting error

Addresses miss setting of the outdoor unit.

Check the address setting of the outdoor unit. The address should be set in 000 or 51-100. The outdoor unit is not set in 000 or in the range of 51-100. When the setting is out of the range, reset it, turn off power supply of the outdoor unit, indoor unit and lossnay for 2minutes or more at the same time, and turn on power supply again.

Address setting of the outdoor unit is wrong.

7111 When an old type M-NET remote controller is used, and the remote controller sensor is specified (SW1-1 is ON).

Replace the remote controller to M-NET remote controller. In the case of network remote controller, it is an abnormality when incapable response returns from the M-NET remote controller during the operation.

0403 Serial communication error Abnormal if serial communication between outdoor multi board and outdoor power board is defective.

Breaking of wire or contact failure of connector CN2 Breaking of wire or contact failure of connector CN4 Defective communication circuit of outdoor power board Defective communication circuit of outdoor multi board for power board

Check connection of each connector CN2, CN4.

Replace outdoor power board.

Replace outdoor multi board.

Show 9 more labels / short text on this page
on · on · on · on · on · on · on · on · Remote controller sensor
Page 53 of the Mitsubishi Electronics OC366 user manual — · MA remote controller is equipped with the diagnosis function
Page 53 · click to enlarge
Page 53

9-2. REMOTE CONTROLLER DIAGNOSIS

· MA remote controller is equipped with the diagnosis function

If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.

Mitsubishi Electronics OC366 — · MA remote controller is equipped with the diagnosis function diagram (page 53)
Fig. 15 · · MA remote controller is equipped with the diagnosi…

If the correct voltage (DC12 V) is not supplied to the remote controller, the indicator will not light. If this occurs, check the remote controller's wiring and the indoor unit.

Press the CHECK button for 5 seconds or more. The display content will

change as shown below.

Remote controller self-diagnosis result

[When the remote controller is functioning correctly]

[When the remote controller malfunctions] (Error display 1) "NG" blinks. → The remote controller's transmitting-receiv- ing circuit is defective.

Check for other possible causes, as there is no problem with the remote controller.

The remote controller must be replaced with a new one.

[Where the remote controller is not defective, but cannot be operated.] (Error display 2) [E3], [6833] or [6832] blinks. → Transmission is not possible.

(Error display 3) "ERC" and the number of data errors are displayed. → Data error has occurred.

There might be noise or interference on the transmission path, or the indoor unit or other remote controllers are defective. Check the transmission path and other controllers.

The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmis- sion path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.

When the number of data errors is "02":

Transmission data from remote controller Transmission data on transmission path

To cancel remote controller diagnosis

Press the CHECK button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After approximately 30 seconds, the state in effect before the diagnosis will be restored.

Page 54 of the Mitsubishi Electronics OC366 user manual — (2) For MA remote controller systems
Page 54 · click to enlarge
Page 54

9-3. REMOTE CONTROLLER TROUBLE

Mitsubishi Electronics OC366 — 9-3. REMOTE CONTROLLER TROUBLE diagram (page 54)
Fig. 16

“ ” indicator: Appears when current is carried.

(1) For M-NET remote controller systems

Symptom or inspection code Cause Inspection method and solution

Though the content of operation is displayed on the remote controller, some indoor units do not operate.

  • The power supply of the indoor unit is not on.
  • The address of the indoor units in same group or the remote controller is not set correctly.
  • The group setting between outdoor units is not registered to the remote controller.
  • The fuse on the indoor unit controller board is blown.
  • Check the part where the abnormality occurs. The entire system In the entire refrigerant system In same group only 1 indoor unit only

Though the indoor unit operates, the display of the remote controller goes out soon.

  • The power supply of the indoor unit is not on.
  • The fuse on the indoor unit controller board is blown.
  • <In case of the entire system or in the entire refrigerant system>
  • Check the self-diagnosis LED of the outdoor unit.
  • Check the items shown in the left that are related to the outdoor unit.

( ) is not displayed on the remote controller. (M-NET remote controller is not fed.)

  • The power supply of the outdoor unit is not on.
  • The connector of transmission outdoor power board is not connected.
  • The number of connected indoor unit in the refrigeration system is over the limit or the number of connected remote controller is over the limit.
  • M-NET remote controller is connected to MA remote controller cable.
  • The transmission line of the indoor/outdoor unit is shorted or down.
  • M-NET remote controller cable is shorted or down.
  • Transmission outdoor power board failure. "HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed about 3 minutes after the power supply of the outdoor unit is on.)

• Check the items shown in the left that are related to the indoor unit.

  • The power supply for the feeding expansion unit for the transmission line is not on.
  • The address of the outdoor unit remains "00".
  • The address of the indoor unit or the remote controller is not set correctly.
  • MA remote controller is connected to the transmission line of the indoor/outdoor unit. The remote controller does not operate though ( ) is displayed.
  • The transmission line of the indoor/outdoor unit is connected to TB15.
  • The transmission line of the indoor/outdoor unit is shorted, down or badly contacted.

(2) For MA remote controller systems

Symptom or inspection code Cause Inspection method and solution

Though the content of operation is displayed on the remote controller, some indoor units do not operate.

  • The power supply of the indoor unit is not on.
  • Wiring between indoor units in same group is not finished.
  • The indoor unit and Slim model are connected to same group.
  • The fuse on the indoor unit controller board is blown.
  • Check the part where the abnormality occurs. The entire system In the entire refrigerant system In same group only 1 indoor unit only

Though the indoor unit operates, the display of the remote controller goes out soon.

  • The power supply of the indoor unit (Master) is not on.
  • In case of connecting the system controller, the setting of the system controller does not correspond to that of MA remote controller.
  • The fuse on the indoor unit (Master) controller board is blown. The remote controller is not fed until the power supply of both indoor unit and outdoor unit is on and the start-up of both units is finished normally.
  • The power supply of the indoor unit is not on.
  • The power supply of the outdoor unit is not on.
  • The number of connected remote controller is over the limit (Maximum: 2 units) or the number of connected indoor unit that is over the limit (Maximum: 16 units).
  • The address of the indoor unit is "00" and the address for the outdoor unit is the one other than "00".
  • The transmission line of the indoor/outdoor unit is connected to TB15.
  • MA remote controller is connected to the transmission line of the indoor/outdoor unit .
  • The remote controller cable is shorted or down.
  • The power supply cable or the transmission line is shorted or down.
  • The fuse on the indoor unit controller board is blown.
  • The power supply of the outdoor unit is not on.
  • The power supply of the feeding expansion unit for the transmission line is not on.
  • The setting of MA remote controller is not main remote controller, but sub-remote controller.
  • MA remote controller is connected to the transmission line of the indoor/outdoor unit.
  • The power supply of the indoor unit (Master) is not on.
  • The transmission line of the indoor/outdoor unit is connected to TB15.
  • The transmission line of the indoor/outdoor unit is shorted, down or badly contacted.
  • The fuse on the indoor unit controller board is blown.
  • <In case of the entire system or in the entire refrigerant system>
  • Check the self-diagnosis LED of the outdoor unit.
  • Check the items shown in the left that are related to the outdoor unit.

( ) is not displayed on the remote controller. (MA remote controller is not fed.)

• Check the items shown in the left that are related to the indoor unit.

"PLEASE WAIT" keeps being dis- played or it is displayed periodically. ("PLEASE WAIT" is usually dis- played about 3 minutes after the power supply of the outdoor unit is on.)

The remote controller does not operate though ( ) is displayed.

(M-NET Remote controller)

Page 55 of the Mitsubishi Electronics OC366 user manual — STAND BY
Page 55 · click to enlarge
Page 55

9-4. THE FOLLOWING SYMPTOM DO NOT REPRESENT TROUBLE (EMERGENCY)

Symptom Display of remote controller CAUSE

Even the cooling (heating) operation selection button is pressed, the indoor unit cannot be operated. The auto vane runs freely.

The indoor unit can not cool (heat) if other indoor units are heating (cooling).

Because of the control operation of auto vane, it may change over to horizontal blow automatically from the downward blow in cooling in cause the downward blow operation has been continued for one hour. At defrosting in heating, hot adjusting and thermostat OFF, it automatically changes over to horizontal blow. Ultra-low speed operation is commenced at thermostat OFF. Light air automatically change over to set value by time or piping temperature at thermostat ON. The fan is to stop during defrosting.

Fan setting changes during heating.

Fan stops during heating operation. Fan does not stop while operation has been stopped. No setting of fan while start SW has been turned on.

Fan is to run for 1 minute after stopping to exhaust residual heat (only in heating). Ultra-low speed operation for 5 minutes after SW ON or until piping temperature becomes 35C. There low speed operate for 2 minutes, and then set notch is commenced. (Hot adjust control) System is being driven. Operate remote controller again after “HO” or “PLEASE WAIT” disappears.

STAND BY

Indoor unit remote controller shows “HO” or “PLEASE WAIT ” indicator for about 2 minutes when turning ON power supply. Drain pump does not stop while unit has been stopped. Drain pump continues to operate while unit has been stopped.

“HO” blinks “PLEASE WAIT” blinks

After a stop of cooling operation, unit continues to operate drain pump for 3 minutes and then stops it. Unit continues to operate drain pump if drainage is generated, even during a stop.

Show 6 more labels / short text on this page
"Cooling (Heating)" blinks · Normal display · Normal display · "Defrost " · Light out · Light out
Page 56 of the Mitsubishi Electronics OC366 user manual — ON OFF
Page 56 · click to enlarge
Page 56

9-5. INTERNAL SWITCH FUNCTION TABLE PUMY-P36NHMU/NHMUR1(-BS) PUMY-P48NHMU/NHMU 1 /NHMU 2 /NHMUR3(-BS)

The black square (■) indicates a switch position.

Operation in Each Switch Setting

ON OFF When to Set

SW U1 1s digit

Before turning the power on

SW U2 10ths digit

Can be set either during operation or not

SW1 Digital Display Switching

ON OFF

ON OFF

2 3 4 5 6 7 8

2 3 4 5 6 7 8

Selects operating system startup

Start up Does not start up

Before turning the power on

Connection Information Clear Switch

Clear Do not clear

OFF to ON any time after the power is turned on During compressor running

ON OFF

Abnormal data clear switch input

2 3 4 5 6

Auto change over from Remote controller

Before turning the power on

ON/ OFF from outdoor unit

ON

OFF

Any time after the power is turned on

ON OFF

<MODEL SELECT>

Set for each capacity.

MODELS

SW4

Before the power is turned on

PUMY-P36NHMU ON OFF 1 2 3 4 5 6

ON OFF 1 2 3 4 5 6

PUMY-P48NHMU

Pressure limitation value change

Change the indoor unit's LEV opening at start

Can be set when off or during operation

ON OFF

Fixing the indoor units linear expansion valve opening

2 3 4 5 6 7 8

Fix the operation frequency

OFF to ON during com- pressor running

Change the indoor unit's LEV opening at defrost

Switching the target sub cool

Can be set when off or during operation

During the FAN or COOL mode,and thermo-OFF or OFF in heating operation, set the opening of linear expansion valve on indoor unit +1

During the FAN or COOL mode,and thermo-OFF in heating operation, set the opening of linear ex- pansion valve on indoor unit +2

+1 SW5-7 Refrigerant shortage amount is measured during heating operation (Refrigerant piping is long etc.) +2 SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.

+ 3 (NoteThis model switching is available for PUMY-P48NHMU 1 (-BS) and PUMY-P48NHMU 2 (-BS), PUMY-P48NHMUR3(-BS)

but not available for PUMY-P48NHMU(-BS) since it does not have the auxiliary heater function.) DIP SW4-4 for primary heating control : Set DIP SW4-4 when power is turned off at unit DIP SW4-4 OFF : Disable primary heating function (Initial setting) DIP SW4-4 ON : Enable primary heating function

Show 45 more labels / short text on this page
Switch · Step · Function · Remarks · <Initial settings> · Rotary switch · SWU2 (10ths digit) · SWU1 (1s digit) · SWU2 (10ths digit) · SWU1 (1s digit) · <Initial settings> · 1~8 · <Initial settings> · SW2 Function Switching · Clear abnormal data · Normal · Pump down · Run adjustment mode · Normal · Enable · Disable · SW3 Test run · <Initial settings> · Outdoor unit · Mode setting · Heating · Cooling · +3 · SW4 Model Switching · 1~6 · Enable · Normal · <Initial settings> · Enable · Normal · SW5 Function switching · Fix Normal · Fix Normal · Enable · Normal · Enable · Normal · Active · Inactive · Active Inactive
Page 57 of the Mitsubishi Electronics OC366 user manual — ON OFF
Page 57 · click to enlarge
Page 57

The black square (■) indicates a switch position.

Operation in Each Switch Setting

ON OFF When to Set

—

Normal Switch of current limitation reading in a different way

Before turning the power on

—

ON OFF

Normal Restriction of maximum frequency

Can be set when off or during operation

2 3 4 5 6 7 8

Enable Normal Ignore refrigerant filling abnormality

Switching the target discharge pressure (Pdm)

Switching (1) the target evaporation temperature (ETm) Switching (2) the target evaporation temperature (ETm)

Enable Normal Ignore current sensor abnormality

Before turning the power on

ON OFF

2 3 4 5 6

During compressor running in heating mode

Silent mode/ Demand Control Selection (see next page)

Demand Control Enable (For high humidity)

Can be set when off or during operation

ON OFF

Change of defrosting control

Show 20 more labels / short text on this page
Switch · Step · Function · Remarks · <Initial settings> · Enable · SW6 Function switching · Enable · Enable Normal · Outdoor unit · Enable Normal · Enable Normal · <Initial settings> · SW7 Function switching · Forced defrost · Forced defrost Normal · SW8 Function switching · Silent mode · <Initial settings> · Normal
Page 58 of the Mitsubishi Electronics OC366 user manual — ON ON
Page 58 · click to enlarge
Page 58

9-6. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR State (CN51)

Lamp power supply Procure locally Max. 10m[33ft] ~

Distant control board Relay circuit External output adapter (PAC-SA88HA-E) Outdoor unit control board

Y

CN51

Y

L1 : Error display lamp L2 : Compressor operation lamp X, Y : Relay (Coil standard of 0.9W or less for DC 12V)

X, YRelay (DC1mA)

Auto change over (CN3N)

Remote control panel Relay circuit External input adapter (PAC-SC36NA) Outdoor unit control board

Relay power supply Procure locally Max. 10m[33ft]

SW1

CN3N X

SW2

Y

ON Heating Validity of SW1

OFF Cooling Invalidity of SW1

Y

SW1 SW2

Silent Mode / Demand Control (CN3D)

Remote control panel Relay circuit External input adapter (PAC-SC36NA) Outdoor unit control board

Relay power supply Procure locally Max. 10m[33ft]

SW1

CN3D X

SW2

Y

ON Heating Validity of SW1

OFF Cooling Invalidity of SW1

Y

SW1 SW2

The silent mode and the demand control are selected by switching the Dip switch 8-1 on outdoor controller board. It is possible to set it to the following power sonsumption (compared with ratings) by setting SW1,2

Outdoor controller board DIP SW8-1 SW1 SW2 Function

Silent mode Silent mode operation

OFF ON

ON OFF ON

— OFF OFF ON OFF

100% 75% 50% 0%

ON ON

Show 19 more labels / short text on this page
· · · · · · · · · ~ · · · · · ~ · · Demand control · (Normal) · (Stop)
Page 59 of the Mitsubishi Electronics OC366 user manual — L3 L2 L1
Page 59 · click to enlarge
Page 59

9-7. HOW TO CHECK THE PARTS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)

Parts name Check points

Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 10~30 [50°F~86°F]) Thermistor (TH3) Thermistor (TH4) Thermistor (TH6) Thermistor (TH7)

TH4

160k~410k

TH3

TH6

4.3k~9.6k

TH7

TH8

39k~105k

Refer to next page. Fan motor(MF1,MF2)

Measure the resistance between the terminals with a tester. (At the ambient temperature 20 [68°F]) Solenoid valve coil (21S4)

1190 ± 100

Motor for compressor (MC)

Measure the resistance between the terminals with a tester. (Winding temperature 20 [68°F])

U

Open or short W

0.188

Measure the resistance between the terminals with a tester. (Surrounding temperature 20 [68°F])

Solenoid valve coil (SV1)

Normal 1183 ± 100 Abnormal Open or short

Note : As for P36NHMU/NHMUR1(-BS) and P48NHMU2/NHMUR3(-BS), rush current protect resistor is mounted on noise filter curcuit board. (20 ± 5% /10W)

Measure the resistance between the terminals with a tester.

Rush current protect resistor (RS) only PUMY-P48NHMU(1)(-BS)

Normal 5.6± 5% Abnormal Open* or short

*In case of open failure, check ACTM with a tester as well. (Refer to 9-9. Test point ; the item of ACTM)

Measure the resistance between the terminals with a tester.

L3 L2 L1

A1

T3 T2 T1

A2

Reference value1.45k

only PUMY-P48NHMU(1)(-BS)

Measure the resistance between the terminals with a tester.

Normal Reference value0.04

Abnormal Open or short*

*Because the resistor of the reactor is little, it is difficult to determine if it is short or normal with an ordinary tester.

Show 12 more labels / short text on this page
Normal · Abnormal · Open or short · Thermistor (TH8) <Heatsink> · Normal Abnormal · Open or short · Normal Abnormal · 52C relay (52C) · Normal Abnormal · Coil (A1-A2) · Open or short · Reactor (DCL)
Page 60 of the Mitsubishi Electronics OC366 user manual — 㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞
Page 60 · click to enlarge
Page 60

Check method of DC fan motor (fan motor / outdoor controller circuit board)

Fuse check Check the fuse (F500) on outdoor controller board.

Replace outdoor controller board (MULTI.B.) (C.B) and fan motor (MF1, 2).

Did the fuse blow?

Wiring contact check Contact of fan motor connector (CNF1, 2)

Is there contact failure? Yes

Recover wiring.

Power supply check(Remove the connector (CNF1, 2)) Measure the voltage in the outdoor controller circuit board. TEST POINT : VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC280-340V (When ACTM stops), DC350V (When ACTM is operating) TEST POINT : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V

Is the voltage normal?

Replace the fan motor.

Check the operation of fan. END

controller board.

NG

Replace outdoor controller board.

OK

Check the operation. END

NG

Replace the fan motor.

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇

㪤㫌㫃㫋㫀㩷㪺㫆㫅㫋㫉㫆㫃㫃㪼㫉㩷㪹㫆㪸㫉㪻

㪝㪘㪥㩷㪤㪦㪫㪦㪩䇭㩿㪤㪝㪈㪀

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪄㪕㩷㩷㫉㫆㫋㪸㫋㫀㫆㫅㩷㫊㫀㪾㫅㪸㫃 㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㪺㫆㫅㫋㫉㫆㫃㩷㫍㫆㫃㫋㪸㪾㪼

㪎 㪍 㪌 㪋 㪄 㪄 㪈

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇 㪧㪚㪌㪈㪈

㪛㪚㪈㪌㪭 㪛㪚㪇㪄㪍㪅㪌㪭 㪛㪚㪇㪄㪈㪌㪭㩷㫇㫌㫃㫊㪼

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞

㪠㫅㫍㪼㫉㫋㪼㫉

㪚㪌㪈㪌

㪻㫉㫀㫍㪼㫉

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㪾㪸㫋㪼㩷㪻㫉㫀㫍㪼㪀

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪞㫉㫆㫌㫅㪻

㪚㪏㪉㪘

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽳㩷㪭㪺㪺

㪤㫆㫋㫆㫉

㪊 㪄 㪈

㪊 㪄 㪈

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽳㩷㪭㪺㪺

㪂 㪛㪚㪉㪏㪇㪄㪊㪌㪇㪭

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㫀㫅㫍㪼㫉㫋㪼㫉㩷㪻㫉㫀㫍㪼㪀

㪚㪥㪝㪈 㪚㪥㪛㪚 㪝㪌㪇㪇

㪚㪌㪈㪇

㪚㪥㪛㪚

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽲㩷㪭 㪛㪚

㪧㫆㫎㪼㫉㩷㪹㫆㪸㫉㪻

㪚㪟㪜㪚㪢㩷㪧㪦㪠㪥㪫

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞

㪚㪟㪜㪚㪢㩷㪧㪦㪠㪥㪫

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇

㪝㪘㪥㩷㪤㪦㪫㪦㪩䇭㩿㪤㪝㪉㪀

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪄㪕㩷㩷㫉㫆㫋㪸㫋㫀㫆㫅㩷㫊㫀㪾㫅㪸㫃 㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㪺㫆㫅㫋㫉㫆㫃㩷㫍㫆㫃㫋㪸㪾㪼

㪎 㪍 㪌 㪋 㪄 㪄 㪈

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽴㩷㪭㫊㫇 㪧㪚㪌㪈㪉

㪛㪚㪇㪄㪍㪅㪌㪭 㪛㪚㪇㪄㪈㪌㪭㩷㫇㫌㫃㫊㪼

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽵㩷㪭 㪝㪞

㪠㫅㫍㪼㫉㫋㪼㫉

㪻㫉㫀㫍㪼㫉

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㪾㪸㫋㪼㩷㪻㫉㫀㫍㪼㪀

㪚㪌㪈㪍

㪤㫆㫋㫆㫉

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪞㫉㫆㫌㫅㪻

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽳㩷㪭㪺㪺

㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㩷㪓㪄㩷㫇㫆㫎㪼㫉㩷㫊㫌㫇㫇㫃㫐㩷㩿㫀㫅㫍㪼㫉㫋㪼㫉㩷㪻㫉㫀㫍㪼㪀

㪚㪥㪝㪉

㪫㪜㪪㪫㪪㩷㪧㪦㪠㪥㪫㩷㽲㩷㪭 㪛㪚

㪚㪟㪜㪚㪢㩷㪧㪦㪠㪥㪫

· The inverter control P.C. board is built in the fan motor of this outdoor unit. · When F500 that is on controller board is blown, change the fan motor and multi controller board at the same time (F500 is impossisble to changae). · For outdoor unit, there are 2 fan motors (up and down; MF1/MF2), it is possible to connect to either CNF1 or CNF2 on the board. · It is abnormal when the abnormlity is detected from either both fan motors or only one side.

Show 7 more labels / short text on this page
Yes · No · No · Yes · Yes OK · No · Replace outdoor
Page 61 of the Mitsubishi Electronics OC366 user manual — 208/230V ±10% AC
Page 61 · click to enlarge
Page 61

Check method of multi controller board

Multi controller board check

Fuse check Check the fuse on Multi controller board

Did the fuse (F500) blow? Replace Multi board and fan motor.

*See DC fan check

Did the fuse (F1 and F2) blow? Check the SV1 and 21S4 and wiring.

7seg LED is lit? (SW1all off)

Check the voltage from the power board to CNDC(PNK) connector.

LED1 LED2

280V to 350V DC?

*Check the breaker and main incoming power *Check noise filter board *Check wiring

*Check wiring *Replace multi controller board

CNDC (PNK)

Multi controller board

Mitsubishi Electronics OC366 — CNDC (PNK) diagram (page 61)
Fig. 17

280-350V DC

conv. circuit

CNDC (PNK)

NO LO

F500

208/230V ±10% AC

CNAC (RED) F1 F2

208/230V ±10% AC

Noise filter circuit board CNAC2(RED) 208/230V ±10% AC

208/230V ±10% AC

LO

NO

NI

TB1

Show 10 more labels / short text on this page
Yes (blow) · No · Yes (blow) · No · No (No lit) · Yes (lit) · No · Yes · Normal · Power circuit board
Page 62 of the Mitsubishi Electronics OC366 user manual — W
Page 62 · click to enlarge
Page 62

Check method of power board

*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.

Is the voltage of main incoming power

208/230V AC ? *Check the breaker and power supply

*Check wiring *Check power board *Check noise filter board

Is the voltage of CNDC(PNK) on multi

*Check wiring *Check model setting switch SW4 on the multi controller board. *Replace power board

Is the voltage to the compressor (U-V,U-W and V-W) balanced ?

Noise filter circuit board 208/230V ±10% AC

52C P36NHMU P48NHMU 2

208/230V ±10% AC

LO

NI

NO

208/230V ±10% AC

TB1

Power board

Mitsubishi Electronics OC366 — 52C P36NHMU P48NHMU 2 diagram (page 62)
Fig. 18

U-V 10V-180V AC U-W 10V-180V AC V-W 10V-180V AC

280-350V DC

W V U Circuit diagram

COMP

conv. circuit

CNDC (PNK)

W

Mitsubishi Electronics OC366 — CNDC (PNK) diagram (page 62)
Fig. 19

W

W

7 6 5 4 3 2 1 CN2 (WHT)

Show 11 more labels / short text on this page
Power board check · No · Yes · No · board 280-350V DC? · Yes · No · Yes · Normal · Multi controller board · *See test point
Page 63 of the Mitsubishi Electronics OC366 user manual — CNAC1(WHT)
Page 63 · click to enlarge
Page 63

Check method of noise fi lter circuit board

Noise filter circuit board check

*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.

Is the voltage of main incoming power

208/230V±10% AC ? *Check the breaker and power supply

Is the voltage of CNAC (RED) on multi

*Check wiring *Replace noise filter board

208/230V±10% AC?

*Check wiring *Check M-NET power board *Check noise filter board

Is the voltage between M1 and M2 on TB3 (M-NET transmission) 24-30V DC?

Turn off the incoming power supply and check the resistance of RS1 on

Is the voltage of CNDC(PNK) on multi

*1 As for P48NHMU(1), 52C-relay and RS are not mounted on noise filter circuit board.

the Noise filter board. *1

*Check wiring *Check power board,

RS1 = open ?

*Replace Noise filter board and check 52C-relay,wiring,power board and ACTM.

Circuit diagram

Mitsubishi Electronics OC366 — Circuit diagram diagram (page 63)
Fig. 20 · Circuit diagram

12V DC from multi board CNLVB

*1 As for P48NHMU(1), 52C-relay and RS are not mounted on noise filter circuit board.

208/230V ±10% AC

Noise filter circuit board

Mitsubishi Electronics OC366 — 208/230V ±10% AC diagram (page 63)
Fig. 21

NO LO

208/230V ±10% AC

conv. circuit

TB1

CNDC (PNK)

280-350V DC

208/230V ±10% AC 208/230V ±10% AC To multi controller board CNDC(PNK)

CNAC1(WHT)

CNAC2(RED) 2 1

Show 18 more labels / short text on this page
No · Yes · No · board CNAC (RED) · Yes · No · Yes · No · board 280-350V DC? · Yes Yes · No (normal) · Yes (open) · Normal · 52C(relay) *1 · RS1(resistor) *1 · Power circuit board · M-NET power board · Multi controller board
Page 64 of the Mitsubishi Electronics OC366 user manual — W
Page 64 · click to enlarge
Page 64

Check method of ACTM

ACTM check (Active Filter Module)

*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.

Is the voltage of main incoming power

208/230V ± -10% AC? *Check the breaker and power supply

Is the voltage of CNDC(PNK) on multi board 330 - 350V DC during cooling or

Is the voltage between 3pin and

4pin of CN2 on multi controller board 18V DC?

*Check wiring *Check 52C relay *Check ACTM

*Replace multi controller board

TIME CHART

ON

208/230V

OFF

ON

OFF

ex. 48Hz

290/325V 330-350V

290/325V

Bus bar voltage (DC)

ON

ACTM OFF

OFF

power on starts stop

208/230V ±10% AC

operate:330-350V DC stop :290-325V DC

Noise filter circuit board

P36NHMU P48NHMU 2 52C

conv. circuit 208/230V ±10% AC

3 - 1 CNDC (PNK)

LO

NO

NI

208/230V ±10% AC

TB1

7 6 5 4 3 2 1 CN2 (WHT)

CN2 3-4pin18V DC

ACTM gate drive power supply

U-V 10V-180V AC U-W 10V-180V AC V-W 10V-180V AC

P48NHMU (1)

AC TM

DCL

W V U

COMP

Mitsubishi Electronics OC366 — P48NHMU (1) diagram (page 64)
Fig. 22

Circuit giagram

W

W

Mitsubishi Electronics OC366 — Circuit giagram diagram (page 64)
Fig. 23 · Circuit giagram

W

operate:330-350V DC stop :290-325V DC

Show 15 more labels / short text on this page
No · Yes · No · heating operation? · Yes · Yes · No · Normal · Power supply · 52C relay · COMP (Hz) · 0Hz · min Hz · Multi controller board · Power board
Page 65 of the Mitsubishi Electronics OC366 user manual — 4 3 2 1 208/230V ±10% AC
Page 65 · click to enlarge
Page 65

Check method of M-NET transmission power board

M-NET transmission power board check

*To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited.

Check the voltage between M1 and M2 on the

transmission terminal block TB3

24-30V DC ?

Yes (24-30V DC ) No

Is the incoming main voltage 208/230V ±10% AC ?

*Check breaker and incoming power supply *Check noise filter board *Check wiring

Yes (208-230V AC )

Disconnect the indoor - outdoor transmission wiring from the terminal block TB3 , and check the voltage

between M1 and M2 on TB3 again.

24-30V DC ?

Yes (24-30V DC )

*Check wiring *Replace M-NET transmission power board

*Correct the short circuit point on the M-NET transmission line.

24V-30V DC

M-NET transmission power board

CN2

Mitsubishi Electronics OC366 — 24V-30V DC diagram (page 65)
Fig. 24

4 3 2 1 208/230V ±10% AC

NI

2 1 CN102 (WHT)

CNS1 (RED)

CNAC1(WHT)

TB1

CN1

208/230V ±10% AC

TB3

M1 M2

Show 8 more labels / short text on this page
No · No · Normal · Multi controller board · Noise filter · circuit board · 24V-30V DC (Non-polar) · To Indoor Unit
Page 66 of the Mitsubishi Electronics OC366 user manual — High temperature thermistor
Page 66 · click to enlarge
Page 66

9-8. HOW TO CHECK THE COMPONENTS

<HIGH PRESSURE SENSOR>

MULTI CONTROLLER BOARD

5V DC

WHT

SENSOR

BLU

BLK

GND 63HS

-5V (DC) - : Output Vout (DC)

2.5 5 363 725 MPa PSIG

PRESSURE

<Thermistor feature chart>

Low temperature thermistors

  • Thermistor <Outdoor pipe> (TH3)
  • Thermistor <Low pressure saturated temperature> (TH6)
  • Thermistor <Outdoor> (TH7)

Resistance (k)

Thermistor R0 = 15k' ± 3% B constant = 3480 ± 2%

Rt =15exp{3480( 273+t – 273 )} 1 1 t : :=(°F-32)/1.8

0. [32°F] 15k ' 10 : [50°F] 9.6k ' 20 : [68°F] 6.3k ' 25 : [77°F] 5.2k ' 30 : [86°F] 4.3k ' 40 : [104°F] 3.0k '

-20 -10 0 10 20 30 40 50 -4 -14 32 50 68 86 104122

Medium temperature thermistor

Heatsink temperature thermistor (TH8)

Thermistor R50 = 17k' ± 2% B constant = 4170 ± 3%

Resistance (k)

Rt =17exp{4170( 273+t – 323)} 1 1

t: =(°F-32)/1.8
0. [32°F] 180k ' 25 : [77°F] 50k ' 50 : [122°F] 17k ' 70 : [158°F] 8k ' 90 : [194°F] 4k '

0 25 50 75 100 110 125 77 122 167 212 230 257 ºF Temperature

High temperature thermistor

  • Thermistor <Discharge/Compressor> (TH4)

Thermistor R120 = 7.465k' ± 2% B constant = 4057 ± 2%

Resistance (k)

Rt =7.465exp{4057( 273+t – 393)} 1 1

t: =(°F-32)/1.8
20. [68°F] 250k ' 30 : [86°F] 160k ' 40 : [104°F] 104k ' 50 : [122°F] 70k ' 60 : [140°F] 48k '
70. [158°F] 34k ' 80 : [176°F] 24k ' 90 : [194°F] 17.5k ' 100 : [212°F] 13.0k ' 110 : [230°F] 9.8k '

0 25 50 75 100 120 77 122 167 212 248 °F Temperature

Vout (V) · Vout MICRO COMPUTER · °F Temperature

Page 67 of the Mitsubishi Electronics OC366 user manual — CNDC DC290V–350V ( 1 (+)– 3 (-))
Page 67 · click to enlarge
Page 67

9-9. TEST POINT DIAGRAM Outdoor multi controller board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)

SW4 Model select SW7 Forced defrost SW3 Test run

CN51 External signal output

CN102 Connect to the M-P.B (Transmission power board)

SW8 Demand/ Silent selection

Mitsubishi Electronics OC366 — TH7TH6 TH3 TH4 63HS 63H 63L diagram (page 67)
Fig. 25

CN40,CN41 Centralized control power supply/ For storing jumper connector selection

SW1 Display selection (Self diagnosis)

CNS2 Transmission wire of centrallized control

SWU2, SWU1 Address setting

CNS1 Indoor/ outdoor unit connecting wire

CNLVB (only P36/P48NHMU2) Connect to the oudoor noise filter circuit board(CN52C) 1–6 : DC12V

CN2 Connect to the outdoor power circuit board 1-5: Power circuit board → Transmitting signal to the multi controller board (0-5V DC) 2-5: Zero cross signal (0-5V DC) 3-4: 18VDC (ACTM power supply) 6-5: 16V DC (Inverter drive power supply) 7-5: 16V DC (Inverter drive power supply)

63L Low pressure switch

63H High presser switch

CN3D Input of demand control

CNAC Power supply for multi controller board

TH3 Thermistor

TH7/ 6 Thermistor

63HS High presser sensor

VFG (TEST POINT4) (voltage between left pins of PC511 and PC512, pin1 and pin2) : (Same as CNF1,2 7(+)–4(-))

VCC (TEST POINT2) (Voltage between pins of C82A) : DC15V (Same as CNF1,2 5(+)–4(-))

52C 52C relay signal

VSP (TEST POINT3) (voltage between pins of C515 and C516) : DC0V (when stopped) DC1–6.5V (when operated) (Same as CNF1,2 6(+)–4(-))

CNF1, 2 Connect to fan motors 1–4 : DC290V–350V 5–4 : DC15V 6–4 : DC0–6.5V 7–4 : DC15V (when stopped) DC0–15V pulse (when operated)

VDC (TEST POINT1) (Voltage between pins of C510) : DC290V–350V (Same as CNF1,2 1(+)–4(-))

CNDC DC290V–350V ( 1 (+)– 3 (-))

CNDC and C510 have the same voltage. Also possible to check at self check No. 45 SW1 : 10110100

Show 4 more labels / short text on this page
SW2 pump down · TH4 Thermistor <Discharge/Compressor> · SV1 Bypass valve · 21S4 Four-way valve
Page 68 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 68 · click to enlarge
Page 68

Outdoor power circuit board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)

Brief Check of POWER MODULE W Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken. 1. Check of POWER MODULE 1.Check of DIODE circuit S - P1 , T - P1 , S - N1 , T - N1 2.Check of IGBT circuit P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W

in the diagram are not actually printed on the board.

CN2 Connect to the outdoor controller circuit board (CN2) 1-5:Transmitting signal to the outdoor controller circuit board (0~5V DC) 2-5:Zero cross signal (0~5V DC) 3-4:18V DC 6-5:16V DC 7-5:16V DC

CNDC 310V DC (1+, 3–) Connect to the outdoor con- troller circuit board

Mitsubishi Electronics OC366 — TH7TH6 TH3 TH4 63HS 63H 63L diagram (page 68)
Fig. 26

TABS/T Connect to the outdoor noise filter circuit board Voltage among phases: 208/230V AC

TABN1/SC-N1 Connect to the ACTM(-)

CN3 Thermistor (TH8)

CN5 Detection of primary current Connect to the outdoor noise filter circuit board (CN5)

TABP1/SC-P1 Connect to 52C (P48NHMU) Connect to ACTM (+) (P36NHMU, P48NHMU2)

CN4 Connect to the outdoor controller circuit board (CN4)

TABP2/SC-P2 Connect to the ACTM(P)

TABU/V/W Connect to the compressor (MC) Voltage among phases: 10V~180V AC

TABN2/SC-N2 Connect to the ACTM (N2)

Page 69 of the Mitsubishi Electronics OC366 user manual — TABS
Page 69 · click to enlarge
Page 69

Outdoor noise filter circuit board PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS

LO, NO Voltage of 208-230V AC is output (Connect to the outdoor power circuit board)

TABS

TABT

Mitsubishi Electronics OC366 — TABS diagram (page 69)
Fig. 27

CNAC2 208/230V AC (Connect to the outdoor control- ler circuit board (CNAC))

CN5 Primary current (Connect to the outdoor power circuit board (CN5))

CNAC1 208/230V AC (Connect to the M-NET power cir- cuit board (M-P.B.)) Current transformer (Primary current)

EI Connect to the earth

LI, NI Voltage of 208/230V AC is input (Connect to the terminal block (TB1))

Page 70 of the Mitsubishi Electronics OC366 user manual — Outdoor noise filter circuit board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)
Page 70 · click to enlarge
Page 70

Outdoor noise filter circuit board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

52C Relay (Coil resistance 155" (typ))

Mitsubishi Electronics OC366 — Outdoor noise filter circuit board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS) diagram (page 70)
Fig. 28 · Outdoor noise filter circuit board PUMY-P36NHMU(-BS)…

CN5 52C driving signal (Connect to the outdoor controller circuit board (CNLVB))

RS1 Rush current protect resistor 20" ± 5% / 10W

LO, NO Voltage of 208/230V AC is out- put (Connect to the outdoor power circuit board)

CNAC2 208/230V AC (Connect to the outdoor control- ler circuit board (CNAC))

CNAC1 208/230V AC (Connect to the M-NET power circuit board (M-P.B.))

E2 Connect to the earth

Current transformer (Primary current)

CN5 Primary current (Connect to the outdoor power circuit board (CN5))

EI Connect to the earth

LI, NI Voltage of 208/230V AC is input (Connect to the terminal block (TB1))

Page 71 of the Mitsubishi Electronics OC366 user manual — TH7TH6 TH3 TH4 63HS 63H 63L
Page 71 · click to enlarge
Page 71

Transmission power board PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU1(-BS) PUMY-P48NHMU2(-BS) PUMY-P48NHMUR3(-BS)

Mitsubishi Electronics OC366 — TH7TH6 TH3 TH4 63HS 63H 63L diagram (page 71)
Fig. 29

CN2 Connect to the outdoor multi controller board 1-2: 24–30V DC 3-4: 24–30V DC

CN1 Connect to the outdoor noise filter circuit board 1–3 : 208/230V AC

Page 72 of the Mitsubishi Electronics OC366 user manual — Connection and internal circuit diagram
Page 72 · click to enlarge
Page 72

Active filter module PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS

P Connect to the out- door power circuit board (TABP2)

L1, L2 Connect to the DCL(Reactor)

Mitsubishi Electronics OC366 — Active filter module PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS diagram (page 72)
Fig. 30 · Active filter module PUMY-P48NHMU PUMY-P48NHMU-BS PU…

+ –

Connect to the outdoor power circuit board (CNAF) 1 : GND 2-1 : 15V DC 3-1 : Control signal 4, 5 : Not used 6-1 : Control signal

I Not used N2 Connect to the outdoor power circuit board (TABN2)

Connect to the 52C Connect to the outdoor power circuit board (TABN1)

Connection and internal circuit diagram

DCL

L1 L2 ACTM

P

N1 N2

Tester check points of Active fi lter module

Error condition Normal value (reference) Symptom when the unit is in trouble

(–) and N1 / N2 / I open less than 1" 1 The unit does not operate (can not be switched ON)

(–) and L2 short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

P and L2 short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

P and N1 / N2 / I short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

L2 and N1 / N2 / I short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

W The symptom when the unit is in open error condition is described to determine open error by tester check.

Show 5 more labels / short text on this page
N1 Non-connect · (+) · + · Load · (- )
Page 73 of the Mitsubishi Electronics OC366 user manual — Connection and internal circuit diagram
Page 73 · click to enlarge
Page 73

Active filter module PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

P Connect to the outdoor power circuit board (TABP2)

Mitsubishi Electronics OC366 — Active filter module PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS) diagram (page 73)
Fig. 31 · Active filter module PUMY-P36NHMU(-BS) PUMY-P36NHMUR…

L1, L2 Connect to the DCL (Reactor)

Upper side

Lower side

+

Connect to the outdoor power circuit board (TABP1)

Connect to the outdoor power circuit board (CNAF) 1 : GND 2-1 : 15V DC 3-1 : Control signal 4, 5 : Not used 6-1 : Control signal

lo Connect to the outdoor power circuit board (TABN2)

Connect to the outdoor power circuit board (TABN1)

Connection and internal circuit diagram

DCL

L1 L2 ACTM

P

N1 N2

Tester check points of Active fi lter module

Error condition Normal value (reference) Symptom when the unit is in trouble

(–) and Io open less than 1" 1 The unit does not operate (can not be switched ON)

(–) and L2 short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

P and L2 short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

P and Io short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

L2 and Io short 100k" ~ 1M" 1 The breaker operates

open W 1 The unit does not operate (can not be switched ON) 24220 Abnormal stop (9-10. No.189 "ACTM error" display)

W The symptom when the unit is in open error condition is described to determine open error by tester check.

Show 7 more labels / short text on this page
N1 Non-connect · N2 Non-connect · (+) · + · Load · (- ) · Io
Page 74 of the Mitsubishi Electronics OC366 user manual — SV1
Page 74 · click to enlarge
Page 74

9-10. OUTDOOR UNIT FUNCTIONS SW:setting

0 OFF 1 ON

latest; records become older

  • When abnormality occurs, check display.
Checklight on Normal: light off
  • Display abnormalities up to

in sequence; history record

Coolinglight on Heating: light blinking
Thermo ONlight on Thermo OFF : light off
  • The No. 1 unit will start from

the address with the lowest

ONlight on OFF: light off
  • History record in 1 is the
  • Display of indoor unit

in 10 is the oldest.

Stop fanlight off

No.8 unit check

start over current inter-

start over current inter-

start over current inter-

No.8 unit mode

No.8 unit operation

start over current inter-

Pressure sensor (63HS) abnormality

Over charge refrigerant abnormality

frequency abnormalityTH7 abnormality

No.7 unit mode

No.7 unit check

63HS abnormality Current sensor

No.7 unit operation

No.6 unit mode

No.6 unit check

TH4 abnormality TH3 abnormality Outdoor fan rotantial

Outdoor fan rotantial fre-

No.6 unit operation

address error Outdoor unit

Display mode Display on the LED1, 2 (display data)

Outdoor pipe temperature sensor (TH3) abnormality

Outside air temperature sensor (TH7) abnormality

Discharge/Comp. temperature abnormality

Discharge/Comp. temperature sensor (TH4) abnormality

Radiator panel thermistor (TH8) abnormality

Saturation temperature of suction pressure

No.5 unit mode

No.5 unit check

No.5 unit operation

(SV2)

0000~9999 (Alternating display of addresses and error code)

No.4 unit mode

No.4 unit check

No.4 unit operation

SV1

TH4

Discharge/Comp. temperature

Discharge/Comp. temperature

No.3 unit mode

No.3 unit operation

Discharge/Comp.

(including abnormality delay code)

0000-9999 and abnormality code

Alternating display of addresses

No.2 unit check

overheating Over current interception

Restart after 3 minutes

No.2 unit mode

No.2 unit operation

0~9999(unit::10-hour)

0~9999(unit::1-hour)

number of indoor units

No.1 unit mode

No.1 unit operation

No.1 unit check

Indoor unit check status

Abnormality delay display 1

Abnormality delay display 2

Abnormality delay display 3

Abnormality delay history 1

Abnormality delay history 2

Abnormality delay history 3

Abnormality code history 1

Abnormality code history 10

Outdoor unit operation display

Indoor unit operation mode

Indoor unit operation display

Capacity code (No. 1 indoor unit)

Capacity code (No. 2 indoor unit)

Capacity code (No. 3 indoor unit)

Capacity code (No. 4 indoor unit)

Capacity code (No. 5 indoor unit)

Abnormality code history 2

Abnormality code history 3

Abnormality code history 4

Abnormality code history 5

Abnormality code history 6

Abnormality code history 7

Abnormality code history 8

Abnormality code history 9

No.

Show 170 more labels / short text on this page
Display input microprocessor · present (including abnormality · compressor operating time · Display all abnormalities · remaining in abnormality · Display all abnormalities · remaining in abnormality · protection (abnormality) · Display of cumulative · capacity code · delay history · terminals) · number · delay · TH8 abnormality · Lighting always · interception abnormality · ception abnormality delay · ception abnormality delay · communication(POWER · BOARD)abormality delay · ception abnormality delay · ception abnormality delay · communication(POWER · BOARD)abormality delay · serial communication · Insufficient refrigerant abnormality · Heatsink temperature abnormality · start over current · High-pressure abnormality · Frequency converter insufficient · Power module abnormality · abormality · Abnormality delay · wiring voltage abnormality · 63HS abnormality delay · open/short delay · 63HS abnormality delay · open/short delay · TH7 abnormality · Current sensor · TH7 abnormality · Current sensor · open/short · delay · delay · frequency abnormality delay · abnormality delay · quency abnormality delay · abnormality delay · Outdoor fan rotantial · TH6 abnormality delay · Low-pressure · address error · Low-pressure · TH6 abnormality · Low-pressure · Delay code · abnormality · delay · Current sensor · abnormality delay · abnormality delay · TH3 abnormality · abnormality delay · abnormaliy delay · TH3 abnormality · Current sensor · Current sensor · Power module · Abnormality delay · abnormality · Indoor unit · Power module · delay · delay · sensor (TH6) abnormality · amount abnormality delay · Frozen protection delay · amount abnormality delay · Frozen protection delay · Abnormality(detection) · Insufficient refigerant · amount abnormality · Over capacity · TH4 abnormality delay · abnormality delay · Insufficient refigerant · Insufficient refigerant · temperature abnormality · Voltage abnormality · Delay code · Voltage abnormality · Voltage abnormality · Compressor operation · capacity error · Indoor unit · abnormality delay · delay · abnormality delay · delay · SHd(low discharge temperature) · setting abnormality · SHd(low discharge temperature) · abnormality delay · Over current interception · SHd(low discharge temperature) · abnormality delay · Address double · interception delay · abnormality · delay · Over current · Compressor operation · abnormality delay · overheating delay · abnormality delay · overheating delay · Excitation Current · High-pressure · Abnormality in the · High-pressure · High-pressure · abnormality · 0~255 · Heatsink · Heatsink · Heatsink · Cumulative time · Cumulative time · Relay output display · Check display · Protection input · Protection input · Protection input · (the oldest) · (the latest) · SW1 setting · 12345678 · 00000000 · 10000000 · 01000000 · 11000000 · 00100000 · 10100000 · 01100000 · 11100000 · 00010000 · 10010000 · 01010000 · 11010000 · 00110000 · 10110000 · 01110000 · 11110000 · 00001000 · 10001000 · 01001000 · 11001000 · 00101000 · 10101000 · 01101000 · 11101000 · 00011000 · 10011000 · 01011000 · 11011000 · 00111000 · 10111000 · 01111000
Page 75 of the Mitsubishi Electronics OC366 user manual — 0~999.9 (A)
Page 75 · click to enlarge
Page 75
Inputlight off No input: light on

Display of communication demand capacity

  • Display of indoor unit

1 2 3 4 7 5 6 8

3-min.delay/no

ON/OFF Heating/Cooling Abnormal/Normal DEFROST/NO Refrigerant pull back/no Excitation current/no

Max. Hz

Frozen protection TH6 abnormality Power module

Abnormal rise of Pd control Control that restrains abnormal rise of discharge pressure

Hz restrain of receipt voltage change Max.Hz correction control due to receipt voltage change

OFF

Display mode Display on the LED1, 2 (display data)

Hz correction of receipt voltage decrease prevention Max.Hz correction control due to voltage decrease

Discharge/Comp. temperature control Hz control by discharge temperature limitation

CN3D1-3 input P93:Silent

Max.Hz control Max.Hz limitation when power supply on

ON

Heatsink over heat prevention control Heatsink over heat prevention control

temp.(heating)

Discharge pressure control Hz control by pressure limitation

CN3S1-2 input P94:Demand

OFF

Hz control by bypass valve

Secondary current control Secondary current control

-99.9~999.9(Short/Open:-99.9 or 999.9)

Input current contol Input current contol

P95:Undefined

Max. Hz

ON

Min.Sj

State of compressor frequency(Hz) control (Words) Content

Discharge/Comp.

P96:Autochange

0000~9999 (unito10)
0000~9999 (unito10)

0~255 (Max. 8 unit)

0~999.9[Arms]

P97:Autochange

0~999.9 (A)

0~999.9 (A)

0~999.9 (V)

OFF

Number of compressor ON/OFF

Input current of outdoor unit

Thermo ON operating time

Total capacity of thermo on

when microprocessor of POWER

Number of indoor units

The second current value when

BOARD abnormality is deteced

The radiator panel temperature

BOARD abnormality is deteced

State of LEV control

No.

Show 98 more labels / short text on this page
operating mode · Light on/light off · prevention · Freeze · control · high compression · Heating · ratio prevention · thermo · Correction of · control · abnormality · LEV opening · depends on Td · pressure(heating) · control Frequency restrain · CN3D1-2 input · of receipt voltage · Heating · thermo · correction · Discharge · Backup · change · LEV opening · depends on Pd · Cooling · correction · thermo · Discharge · Backup · depends on Td · Input current · Cooling · thermo · correction · control · over fixed mode · SHd declease · current control · CN3N1-2 input · Secondary · prevention · temperature · Fan · control · over permission · Td over heat · over heat pre- · vention control · CN3N1-3 input · prevention · Discharge · pressure · Heatsink · 0~255 · 0~255 · control · Communication demand capacity · Compressor operating current · External connection status · State of compressor · State of compressor · IC1 operation mode · IC2 operation mode · IC3 operation mode · IC4 operation mode · IC5 operation mode · OC operation mode · frequency control 1 · frequency control 2 · microprocessor of POWER · DC bus voltage · Protection input · SV control · SW1 setting · 12345678 · 11111000 · 00000100 · 10000100 · 01000100 · 11000100 · 00100100 · 10100100 · 01100100 · 11100100 · 00010100 · 10010100 · 01010100 · 11010100 · 00110100 · 10110100 · 01110100 · 11110100 · 00001100 · 10001100 · 01001100 · 11001100
Page 76 of the Mitsubishi Electronics OC366 user manual — TH6(ET) °C
Page 76 · click to enlarge
Page 76

Display of actual operating frequency

Display of number of outdoor

outdoor SLEV and indoor LEV

from high-pressure sensor and

Display of target frequency

Display of opening pulse of

(SC) data and detection data

fan control steps (target)

Display of outdoor subcool

1 2 3 4 7 5 6 8

Display mode Display on the LED1, 2 (display data)

(When the indoor unit is not connected,it is displayed as"0".)

-99.9 ~ 999.9

-99.9 ~ 999.9

-99.9 ~ 999.9

Outdoor fan control step number

IC1 LEV Opening pulse

IC2 LEV Opening pulse

IC3 LEV Opening pulse

IC4 LEV Opening pulse

IC5 LEV Opening pulse

TH7(Outdoor-temp.) °C

Outdoor SC (cooling) °C

EER fan control step number (cooling)

High-pressure sensor (Pd) kgf/cm2

IC4 TH22 (Liquid) °C

IC5 TH22 (Liquid) °C

IC2 TH21 (Intake) °C

IC3 TH21 (Intake) °C

IC4 TH21 (Intake) °C

IC5 TH21 (Intake) °C

TH6(ET) °C

No.

Show 52 more labels / short text on this page
each thermistor · 0~FF(16 progressive) · 0~2000 · 0~255 · 0~15 · TH8(Power module) °C · Operational frequency · TH3(Outdoor pipe) °C · IC1 TH22(Liquid) °C · IC2 TH22(Liquid) °C · IC3 TH22(Liquid) °C · IC1 TH21(Intake) °C · IC1 TH23(Gas) °C · IC2 TH23(Gas) °C · IC3 TH23(Gas) °C · IC4 TH23(Gas) °C · IC5 TH23(Gas) °C · Target frequency · TH4(Td) °C · 12345678 · 00000010 · 10000010 · 01000010 · 11000010 · 10100010 · 01100010 · 11100010 · 00010010 · 10010010 · 01010010 · 11010010 · 00110010 · 10110010 · 01110010 · 00001010 · 10001010 · 01001010 · 11001010 · 00101010 · 10101010 · 01101010 · 11101010 · 00011010 · 10011010 · 01011010 · 11011010 · 00111010 · 10111010 · 00000110 · SW1 setting · 01111010 · 11111010
Page 77 of the Mitsubishi Electronics OC366 user manual — IC1 SC/SH °C
Page 77 · click to enlarge
Page 77

Display of actual frequency at time of abnormality delay

Display of fan step number at time of abnormality delay

Display of opening pulse outdoor SLEV

and indoor LEV at time of abnormality

Display of all control target data

high-pressure sensor and each

Display of detection data from

Display of indoor SC/SH data

Display of discharge superheat data

Display of target subcool step data

1 2 3 4 5 6 7 8 Display mode No. Notes SW1 setting

during heatingsubcool (SC)/during cooling: superheat (SH)

Display on the LED1, 2 (display data)

SCm/SHm(0.0~20.0)

0.0~711.0 [PSIG]

ETm(-2.0~23.0)

-99.9~999.9 [°F]

-99.9~999.9 [°F]

Pdm(0.0~30.0)

SCm(0.0~20.0)

-99.9 ~ 999.9

-99.9~999.9

Fan step number at time of abnormality delay

IC1 LEV opening pulse abnormality delay

IC2 LEV opening pulse abnormality delay

IC3 LEV opening pulse abnormality delay

IC4 LEV opening pulse abnormality delay

IC5 LEV opening pulse abnormality delay

Target Pd display (heating) kgf/%

Actual frequency of abnormality delay

Discharge superheat (SHd) °C

Target ET display (cooling) °C

Target outdoor SC (cooling) °C

Target indoor SC/SH (IC1) °C

Target indoor SC/SH (IC2) °C

Target indoor SC/SH (IC3) °C

Target indoor SC/SH (IC4) °C

Target indoor SC/SH (IC5) °C

High pressure sensor (Pd) PSIG

TH3 (Outdoor pipe) °F

TH7 (Outdoor temp.) °F

TH8 (Power module) °F

IC1 SC/SH °C

IC2 SC/SH °C

IC3 SC/SH °C

IC4 SC/SH °C

IC5 SC/SH °C

TH6 (ET) °F

Show 37 more labels / short text on this page
thermistor · delay · 0~FF(16 progressive) · 0~2000 · -2~4 · 0~15 · Target subcool step · TH4 (Td) °F · 12345678 · 10000110 · 01000110 · 11000110 · 00100110 · 10100110 · 01100110 · 11100110 · 10010110 · 01010110 · 11010110 · 00110110 · 10110110 · 01110110 · 11110110 · 00001110 · 10011110 · 01011110 · 11011110 · 00111110 · 10111110 · 01111110 · 00000001 · 10000001 · 11000001 · 00100001 · 10100001 · 01100001 · 11100001
Page 78 of the Mitsubishi Electronics OC366 user manual — -99.9 ~ 999.9 [°F]
Page 78 · click to enlarge
Page 78

Display of data from high-pressure sensor,

all thermistors, and SC/SH at time of

Display of detection data from each

Display of check sum code of ROM

Display of detection data from each

Display of version data of ROM

indoor liquid pipe thermistor

No. Display mode Notes

Display of ROM type

(When the indoor unit is not connected,it is displayed as"32".)

(When the indoor unit is not connected,it is displayed as"32".)

1 2 3 4 5 6 7 8

Display on the LED1, 2 (display data)

-99.9 ~ 999.9 [°F]

-99.9 ~ 999.9 [°F]

-99.9 ~ 999.9

High-pressure sensor data at time of abnormality delay kgf/%

TH4 sensor data at time of abnormality delay °C

TH6 sensor data at time of abnormality delay °C

TH3 sensor data at time of abnormality delay °C

TH8 sensor data at time of abnormality delay °C

OC SC (cooling) at time of abnormality delay °C

IC1 SC/SH at time of abnormality delay °C

IC2 SC/SH at time of abnormality delay °C

IC3 SC/SH at time of abnormality delay °C

IC4 SC/SH at time of abnormality delay °C

IC5 SC/SH at time of abnormality delay °C

IC1 TH21 Intake °F

IC2 TH21 Intake °F

IC3 TH21 Intake °F

IC4 TH21 Intake °F

IC5 TH21 Intake °F

IC6 TH21 Intake °F

IC7 TH21 Intake °F

IC8 TH21 Intake °F

IC1 TH22 Liquid °F

IC2 TH22 Liquid °F

IC1 TH23 Gas °F

IC2 TH23 Gas °F

IC3 TH23 Gas °F

IC4 TH23 Gas °F

IC5 TH23 Gas °F

IC6 TH23 Gas °F

IC7 TH23 Gas °F

IC8 TH23 Gas °F

Show 39 more labels / short text on this page
abnormality delay · indoor thermistor · ROM version monitor · Check Sum code · ROM type · SW1 setting · 12345678 · 00010001 · 10010001 · 01010001 · 11010001 · 00110001 · 10110001 · 01110001 · 11110001 · 00001001 · 10001001 · 01001001 · 11001001 · 00101001 · 10101001 · 01101001 · 11101001 · 00011001 · 10011001 · 01011001 · 11011001 · 00111001 · 10111001 · 01111001 · 11111001 · 00000101 · 10000101 · 01000101 · 01010101 · 11010101 · 00110101 · 10110101 · 01110101
Page 79 of the Mitsubishi Electronics OC366 user manual — -99.9 ~ 999.9 [°F]
Page 79 · click to enlarge
Page 79

Except Service Ref. PUMY-P48NHMU(-BS)

Display of actual frequency at time of abnormality

Display of fan step number at time of abnormality

Display of opening pulse of outdoor SLEV

Display of data from high-pressure sensor

and all thermistors at time of abnormality

op2,op3=a op4,op5=b op6, op7=c op8,op9=d

SET05 18 00 80 05 00 05 00 15 00 25

and indoor LEV at time of abnormality

a b c d a=c b=d

Display of detection data from each

HD=05, CM=18 op1=00()/01(°F)

Display of data from SC/SH and all

Primary heating controlSW4-4 ON

Ex. a=-5, b=5, c=15, d=25

thermistors at time of abnormality

indoor liquid pipe thermistor

No. Display mode Notes

MONI : 25 18 00

(When the indoor unit is not connected,it is displayed as"32".)

1 2 3 4 5 6 7 8

Initial value a=10.4°F, b=32°F, c=50.0°F, d=68.0°F

Display on the LED1, 2 (display data)

Initial value a= -12, b=0, c=10, d=20

— — ACTM error — — CT sensor

a=c and b=d, 10.4°F a

a=c and b=d, -12 a

10.4°F a

-12 a

-99.9 ~ 999.9 [°F]

-99.9 ~ 999.9

High-pressure sensor data at abnormality kgf/%

TH4 sensor data at time of abnormality °C

TH6 sensor data at time of abnormality °C

TH3 sensor data at time of abnormality °C

TH8 sensor data at time of abnormality °C

IC1 SC/SH at time of abnormality °C

IC2 SC/SH at time of abnormality °C

IC3 SC/SH at time of abnormality °C

IC4 SC/SH at time of abnormality °C

IC5 SC/SH at time of abnormality °C

IC1 LEV opening pulse at time of abnormality

IC2 LEV opening pulse at time of abnormality

IC3 LEV opening pulse at time of abnormality

IC4 LEV opening pulse at time of abnormality

IC5 LEV opening pulse at time of abnormality

Primary heating control setting temp. a

Primary heating control setting temp. b

Primary heating control setting temp. c

Primary heating control setting temp. d

Primary heating control setting temp. a°F

Primary heating control setting temp. b°F

Primary heating control setting temp. c°F

Primary heating control setting temp. d°F

Actual frequency at time of abnormality

Fan step number at time of abnormality

IC3 TH22 Liquid °F

IC4 TH22 Liquid °F

IC5 TH22 Liquid °F

IC6 TH22 Liquid °F

IC7 TH22 Liquid °F

IC8 TH22 Liquid °F

Show 41 more labels / short text on this page
voltage · voltage Over · disconnection Under · 0~FF(16progressive) · 0~2000 · 0~20 · 4220 Error history · SW1 setting · 12345678 · 11110101 · 00001101 · 10001101 · 01001101 · 11001101 · 00101101 · 10101101 · 01101101 · 11101101 · 00011101 · 10011101 · 01011101 · 11011101 · 00111101 · 10111101 · 00000011 · 10000011 · 11000011 · 00100011 · 10100011 · 01100011 · 11100011 · 00010011 · 10010011 · 01010011 · 11010011 · 00110011 · 01110011 · 11110011 · 00001011 · 10001011 · 01001011
Page 80 of the Mitsubishi Electronics OC366 user manual — IC6 SC/SH °C
Page 80 · click to enlarge
Page 80

Display of data from high-pressure sensor,

Display of opening pulse of indoor LEV

Display of opening pulse of indoor LEV

Display of indoor unit operating mode

Display of indoor unit capacity mode

Display of opening pulse of outdoor

Display of SC/ SH data at time of

Display of SC/ SH data at time of

all thermistors, and outdoor SC

Display of all control target data

Display of indoor SC/SH data

No. Display mode Notes

SLEV and indoor LEV

at time of abnormality

at time of abnormality

(When the indoor unit is not connected,it is displayed as"0".)

1 2 3 4 5 6 7 8

during heating:subcool (SC)/during cooling:superheat (SH)

Display on the LED1, 2 (display data)

OFF

ON

OFF

SCm/SHm (0.0~14.0)

ON

-99.9 ~ 999.9

-99.9 ~ 999.9

-99.9 ~ 999.9

-99.9 ~ 999.9

IC6 LEV opening pulse at abnormality delay

IC7 LEV opening pulse at abnormality delay

IC8 LEV opening pulse at abnormality delay

IC6 LEV opening pulse at time of abnormality

IC7 LEV opening pulse at time of abnormality

IC8 LEV opening pulse at time of abnormality

IC6 SC/SH at abnormality delay °C

IC7 SC/SH at abnormality delay °C

IC8 SC/SH at abnormality delay °C

IC6 SC/SH at abnormality °C

IC7 SC/SH at abnormality °C

IC8 SC/SH at abnormality °C

IC6 target SC/SH °C

IC7 target SC/SH °C

IC8 target SC/SH °C

IC6 LEV opening pulse

IC7 LEV opening pulse

IC8 LEV opening pulse

IC6 SC/SH °C

IC7 SC/SH °C

IC8 SC/SH °C

12345678 11001011 00101011 10101011 01101011 11101011 00011011 10011011 01011011 11011011 00111011 10111011 01111011 11111011 00000111 10000111 01000111 11000111 00100111 10100111 01100111 11100111 00010111 10010111 01010111 11010111 00110111 10110111 01110111 11110111 00001111 10001111 01001111 11001111 00101111 10101111 01101111

211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246

Show 30 more labels / short text on this page
abnormality · abnormality · Heating · thermo · Heating · thermo · Cooling · thermo · OFF Fan Cooling · thermo · 0~2000 · 0~2000 · 0~2000 · 0~255 · IC6 operation mode · IC7 operation mode · IC8 operation mode · IC6 TH22(Liquid) °C · IC7 TH22(Liquid) °C · IC8 TH22(Liquid) °C · IC6 TH21(Intake) °C · IC7 TH21(Intake) °C · IC8 TH21(Intake) °C · IC6 Capacity code · IC7 Capacity code · IC8 Capacity code · IC6 TH23(Gas) °C · IC7 TH23(Gas) °C · IC8 TH23(Gas) °C · SW1 setting
Page 81 of the Mitsubishi Electronics OC366 user manual — 10-2-2. Power supply wire diameter and capacity
Page 81 · click to enlarge
Page 81

10 ELECTRICAL WIRING

This chapter provides an introduction to electrical wiring for the CITY MULTI-S series, together with notes concerning power wiring, wiring for control (transmission wires and remote controller wires), and the frequency converter.

10-1. OVERVIEW OF POWER WIRING

(1) Use a separate power supply for the outdoor unit and indoor unit.

(2) Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water,etc.) when proceeding with the wiring and connections.

(3) The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.

Make sure the power-supply voltage does not drop more than 10 %. (4) Specific wiring requirements should adhere to the wiring regulations of the region. (5) Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord.

For example, use wiring such as YZW. (6) Install an earth longer than other cables. (7) Use copper supply wires. Use electric wires over the rating voltage 300V.

10-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY 10-2-1. Wiring diagram for main power supply

Breaker for Wiring and Current Leakage Power supply (Single phase 60Hz 208/230V)

Breaker for Wiring and Current Leakage Power supply (single phase 60Hz 208/230V)

10-2-2. Power supply wire diameter and capacity

of over current protector device Model

for Wiring*1 Ground ~/N (single), 60Hz 208/230V ~/N (single), 60Hz 208/230V

(mm2[AWG]) Breaker for Current

Outdoor Unit P36, P48 5.3 [AWG10] 5.3 [AWG10]

30 A 30 mA 0.1 sec. or less 30 A 26 A 40 A Indoor Unit

Refer to installation manual of indoor unit.

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV). *2. Use copper supply wires. Use the electric wires over the rating voltage 300V.

Show 13 more labels / short text on this page
Outdoor unit · Grounded · Pull box · Indoor unit · Grounded · Minimum Wire Thickness · Breaker · Minimum · Maximum rating · circuit ampacity · Power Supply · Leakage · Main Cable*2
Page 82 of the Mitsubishi Electronics OC366 user manual — 10-3-4. MA Remote control cables
Page 82 · click to enlarge
Page 82

10-3. DESIGN FOR CONTROL WIRING Please note that the types and numbers of control wires needed by the CITY MULTI-S series will depend on the remote con- trollers and whether they are linked with the system.

10-3-1. Selection number of control wires

  • Remote controller used in system control operations.
  • Group operation involving different refrigerant systems.
  • Linked operation with upper control system.

Remote controller → indoor unit

Wires connecting → indoor units

Wires connecting → indoor units with outdoor unit

Wires connecting → outdoor units

  • 10-3-2. Control signal wires Transmission wires
  • Types of transmission cables : Shielding wire CVVS or CPEVS.
  • Cable diameter : More than 1.25 E [AWG 16]
  • Maximum wiring length : Within 200 m [656 ft]

10-3-3. M-NET Remote controller wiring

Kind of remote control cable Shielding wire MVVS

Cable diameter 0.5 to 1.25 E [AWG 20 to AWG 16]

Remarks When 10 m is exceeded, use cable with the same

specifications as 10-3-2. Transmission line wiring

10-3-4. MA Remote control cables

Kind of remote control cable 2-core cable (unshielded)

Cable diameter 0.3 to 1.25 E [AWG 22 to AWG 16]

10-4. SYSTEM SWITCH SETTING In order to identify the destinations of signals to the outdoor units, indoor units, and remote controller of the MULTI-S series, each microprocessor must be assigned an identification number (address). The addresses of outdoor units, indoor units, and remote controller must be set using their settings switches. Please consult the installation manual that comes with each unit for detailed information on setting procedures.

10-5. EXAMPLE EXTERNAL WIRING DIAGRAM FOR A BASIC SYSTEM 10-5-1. Example using a M-NET remote controller

Breaker for Wiring and Current Leakage

Outdoor unit Power supply Single phase 2 wire 60Hz 208/230V

15A Breaker for Wiring and Current Leakage

Power supply Single phase 60Hz 208/230V

1.25mm2 × 2 [AWG16]

:1.6mm × 2 [AWG14]

:1.6mm × 2 [AWG14]

0.5~1.25mm2 × 2 [AWG20 ~ AWG16]

Show 10 more labels / short text on this page
M-NET remote controller · Use · Transmission · 2 wires (non-polar) · wires · Grounded · Pull box · Indoor unit · Group operation · Remote controller wire
Page 83 of the Mitsubishi Electronics OC366 user manual — (2) Method of obtaining total current
Page 83 · click to enlarge
Page 83

10-6. METHOD FOR OBTAINING ELECTRICAL CHARACTERISTICS WHEN A CAPACITY AGREEMENT IS TO BE SIGNED WITH AN ELECTRIC POWER COMPANY The electrical characteristics of connected indoor unit system for air conditioning systems, including the MULTI-S series, will depend on the arrangement of the indoor and outdoor units. First read the data on the selected indoor and outdoor units and then use the following formulas to calculate the electrical char- acteristics before applying for a capacity agreement with the local electric power company.

10-6-1. Obtaining the electrical characteristics of a CITY MULTI-S series system (1) Procedure for obtaining total power consumption

Page numbers in this technical manual Power consumption

Total power consumption of each indoor unit See the technical manual of each indoor unit 1

*1 power consumption of outdoor unit Standard capacity table— Refer to 5-2. 2

Total power consumption of system See the technical manual of each indoor unit 1+2

*1 Please note that the power consumption of the outdoor unit will vary depending on the total capacity of the selected indoor units.

(2) Method of obtaining total current

Page numbers in this technical manual Subtotal

Total current through each indoor unit See the technical manual of each indoor unit 1

*2 current through outdoor unit Standard capacity table— Refer to 5-2. 2

Total current through system See the technical manual of each indoor unit 1+2

*2 Please note that the current through the outdoor unit will vary depending on the total capacity of the selected indoor units.

(3) Method of obtaining system power factor Use the following formula and the total power and current obtained in parts 1 and 2 in the above table to calculate the system power factor.

(Total system power consumption)

System power factor =

(Total system current x voltage) o 100%

10-6-2. Applying to an electric power company for power and total current Calculations should be performed separately for heating and cooling employing the same methods; use the largest resulting value in your application to the electric power company.

Page 84 of the Mitsubishi Electronics OC366 user manual — W 15.88 [5/8] W 9.52 [3/8]
Page 84 · click to enlarge
Page 84

11 REFRIGERANT PIPING TASKS

11-1. REFRIGERANT PIPING SYSTEM

A

Line-Branch Method Connection Examples (Connecting to 4 Indoor Units)

H

B C

b c

A B C

Outdoor Unit First Branch Indoor unit

Total Piping Length Farthest Piping Length

A+B+C+a+b+c+d 120m [394ft] A+B+C+d 80m [262ft] B+C+d 30m [100ft] 50 meters [164ft] or less (If the outdoor unit is lower, 20 meters [70ft] or less) 12 meters [39ft] or less Use an optional branch piping kit (CMY-Y62-G-E).

(L) ( 1 )

Farthest Piping Length After First Branch

High/Low Difference in Indoor/Outdoor Section

(H)

  • (h)
  • Selecting the Refrigerant Branch Kit
  • Select Each Section of Refrigerant Piping

High/Low Difference in Indoor/Indoor Section

(1) Refrigerant Piping Diameter In Section From Outdoor Unit to First Branch (Outdoor Unit Piping Diameter) (1) Section From Oudoor Unit to First Branch (A) (2) Sections From Branch to Indoor Unit (a,b,c,d) (3) Section From Branch to Branch (B,C)

(2) Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)

Piping Diameter (mm [inch]) Model

Piping Diameter (mm [inch]) Model number

W 9.52 [3/8] W 15.88 [5/8]

W6.35 [1/4] W12.7 [1/2] W9.52 [3/8] W15.88 [5/8]

PUMY-P36,48

Gas Line Liquid Line

Select the size from the right table.

(3) Refrigerant Piping Diameter In Section From Branch to Branch

Liquid Line (mm [inch]) Gas Line (mm [inch])

W 15.88 [5/8] W 9.52 [3/8]

  • Additional refrigerant charge
  • Refrigerant of 3kg [6.6 lbs] equivalent to 50m [165 ft] total extended piping length is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m [165 ft] or less, there is no need to charge with additional refrigerant.
  • If the total extended piping length exceeds 50m [165 ft], calculate the required additional refrigerant charge using the procedure shown on the right.
  • If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.

Liquid pipe size Total length of W9.52 × 0.06 kg [3/8" × 0.041 lbs] =

Liquid pipe size Total length of W6.35 × 0.024 kg [1/4" × 0.016 lbs]

Refrigerant amount for outdoor unit

(m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]

(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]

3.0kg [6.6 lbs]

Outdoor model : P48 Indoor 1 : P24 A : W9.52 [3/8"] 10 m [33 ft] a : W9.52 [3/8"] 15m [49 ft] 2 : P15 B : W9.52 [3/8"] 10 m [33 ft] b : W6.35 [1/4"] 10m [33 ft] 3 : P08 C : W9.52 [3/8"] 10 m [33 ft] c : W6.35 [1/4"] 10m [33 ft] 4 : P06 d : W6.35 [1/4"] 20m [66 ft] The total length of each liquid line is as follows; W9.52 [3/8"] : A + B + C + a = 10 m + 10 m + 10 m + 15 m = 45 m [33 ft + 33 ft + 33 ft + 49 ft = 148 ft] W6.35 [1/4"] : b + c + d = 10 m +10 m + 20 m = 40 m [33 ft + 33 ft + 66 ft = 132 ft] Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7kg (rounded up) = [148 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.58 lbs]

At the conditions below:

Show 18 more labels / short text on this page
d · a · h · Permissible · Length · Permissible High/ · Low Difference · Liquid Line · Liquid Line · 18 or lower · Gas Line · 24 to 54 · Gas Line · <Additional Charge> · Additional refrigerant charge · + · (kg) · [lbs]
Page 85 of the Mitsubishi Electronics OC366 user manual — (m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]
Page 85 · click to enlarge
Page 85

A

Header-Branch Method Connection Examples (Connecting to 4 Indoor Units)

N

H

1

A B C

Outdoor Unit First Branch Indoor unit

Total Piping Length Farthest Piping Length

A+a+b+c+d 120m [394 ft] A+d 80m [262 ft] d is 30 meters[100 ft] or less 50 meters [164 ft] or less (If the outdoor unit is lower, 20 meters [70 ft] or less) 12 meters [39 ft] or less Please select branching kit, which is sold separately, from the table below. (The kit comprises sets for use with liquid pipes and for use with gas pipes.)

(L) ( 1 )

Farthest Piping Length After First Branch

High/Low Difference in Indoor/Outdoor Section

(H)

High/Low Difference in Indoor/Indoor Section

  • Selecting the Refrigerant Branch Kit

Branch header (4 branches)

Branch header (8 branches)

CMY-Y64-G-E

CMY-Y68-G-E

  • Select Each Section of Refrigerant Piping

(1) Refrigerant Piping Diameter In Section From Outdoor Unit to First Branch (Out- door Unit Piping Diameter) (1) Section From Outdoor Unit to First Branch (A) (2) Sections From Branch to Indoor Unit (a,b,c,d)

(2) Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)

Piping Diameter (mm [inch]) Model

Piping Diameter (mm [inch]) Model number

PUMY-P36,48

W 9.52 [3/8] W 15.88 [5/8]

W6.35 [1/4] W12.7 [1/2] W9.52 [3/8] W15.88 [5/8]

Gas Line Liquid Line

Select the size from the right table.

  • Additional refrigerant charge
  • Refrigerant of 3kg [6.6 lbs] equivalent to 50m [165 ft] total extended piping length is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m [165 ft] or less, there is no need to charge with additional refrigerant.
  • If the total extended piping length exceeds 50m [165 ft], calculate the required additional refrigerant charge using the procedure shown on the right.
  • If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.

Liquid pipe size Total length of W9.52 × 0.06 kg [3/8" × 0.041 lbs]

Liquid pipe size Total length of W6.35 × 0.024 kg [1/4" × 0.016 lbs]

Refrigerant amount for outdoor unit

(m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]

(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]

3.0kg [6.6 lbs]

Outdoor model : P48 Indoor 1 : P24 A : W9.52 [3/8"] 30 m [98ft] a : W9.52 [3/8"] 15m [49ft] 2 : P15 b : W6.35 [1/4"] 10m [33 ft] 3 : P08 c : W6.35 [1/4"] 10m [33 ft] 4 : P06 d : W6.35 [1/4"] 20m [66 ft] The total length of each liquid line is as follows; W9.52 : A + a = 30 m + 15 m = 45 m [98 ft + 49 ft = 147 ft] W6.35 : b + c + d = 10 m + 10 m + 20 m = 40 m [33 ft + 33 ft + 66 ft = 132 ft] Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7kg (rounded up) = [147 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.54 lbs]

At the conditions below:

Show 19 more labels / short text on this page
a b c · d · h · Permissible · Length · Permissible High/ · Low Difference · (h) · Liquid Line · 18 or lower · Liquid Line · Gas Line · 24 to 54 · Gas Line · <Additional Charge> · Additional refrigerant charge · = · + · (kg) [lbs]
Page 86 of the Mitsubishi Electronics OC366 user manual — W 15.88 [5/8] W 9.52 [3/8]
Page 86 · click to enlarge
Page 86

A

A

Method of Combined Branching of Lines and Headers Connection Examples (Connecting to 5 Indoor Units)

F

E

A

G

B

B 3

H

D D D

A B

Outdoor unit First branching (branching joint) Branching joint Indoor unit Branching header To downstream unit Blind caps

C D E F G

C D

D

Total Piping Length Farthest Piping Length

A+B+C+a+b+c+d+e is 120 meters [394 ft] or less A+B+b is 80 meters [262 ft] or less B+b is 30 meters [100 ft] or less 50 meters [164 ft] or less (If the outdoor unit is lower, 20 meters [70 ft] or less) 12 meters [39 ft] or less Please select branching kit, which is sold separately, from the table below. (The kit comprises sets for use with liquid pipes and for use with gas pipes.)

(L) ( 1 )

Farthest Piping Length After First Branch

High/Low Difference in Indoor/Outdoor Section

(H)

(h) ■ Selecting the Refrigerant Branch Kit

High/Low Difference in Indoor/Indoor Section

Branch Header (4 branches)

Branch Header (8 branches)

CMY-Y64-G-E

CMY-Y68-G-E

  • Select Each Section of Refrigerant Piping

(2) Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)

(1) Refrigerant Piping Diameter In Section From Outdoor Unit to First Branch (Out- door Unit Piping Diameter) (1) Section From Outdoor Unit to First Branch (A) (2) Sections From Branch to Indoor Unit (a,b,c,d,e) (3) Section From Branch to Branch (B,C)

Piping Diameter (mm [inch]) Model

Piping Diameter (mm [inch]) Model number

W 9.52 [3/8] W 15.88 [5/8]

W6.35 [1/4] W12.7 [1/2] W9.52 [3/8] W15.88 [5/8]

PUMY-P36, 48

Gas Line Liquid Line

Select the size from the right table.

(3) Refrigerant Piping Diameter In Section From Branch to Branch

Liquid Line (mm [inch]) Gas Line (mm [inch])

W 15.88 [5/8] W 9.52 [3/8]

  • Additional refrigerant charge
  • Refrigerant of 3kg [6.6 lbs] equivalent to 50m [165 ft] total extended piping length is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m [165 ft] or less, there is no need to charge with additional refrigerant.
  • If the total extended piping length exceeds 50m [165 ft], calculate the required additional refrigerant charge using the procedure

Liquid pipe size Total length of W9.52 × 0.06 kg [3/8" × 0.041 lbs]

Liquid pipe size Total length of W6.35 × 0.024 kg [1/4" × 0.016 lbs]

Refrigerant amount for outdoor unit

(m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]

(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]

3.0kg [6.6 lbs]

Outdoor model : P48 Indoor 1 : P24 A : W9.52 [3/8"] 10 m [33 ft] a : W9.52 [3/8"] 15m [49 ft] 2 : P15 B : W9.52 [3/8"] 10 m [33 ft] b : W6.35 [1/4"] 10m [33 ft] 3 : P08 C : W9.52 [3/8"] 10 m [33 ft] c : W6.35 [1/4"] 10m [33 ft] 4 : P06 d : W6.35 [1/4"] 10m [33 ft] 5 : P06 e : W6.35 [1/4"] 10m [33 ft] The total length of each liquid line is as follows; W9.52 : A + B + C + a = 10 m + 10 m + 10 m + 15 m = 45 m [33 ft + 33 ft + 33 ft + 49 ft = 148 ft] W6.35 : b + c + d + e = 10 m + 10 m + 10 m + 10 m = 40 m [33 ft + 33 ft + 33 ft + 33 ft = 132 ft] Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7kg (rounded up) = [148 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.58 lbs]

shown on the right. • If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.

At the conditions below:

Show 20 more labels / short text on this page
c d e · h · b · a · Permissible · Length · Permissible High/ · Low Difference · Branch Joint CMY-Y62-G-E · Liquid Line · Liquid Line · 18 or lower · Gas Line · 24 to 54 · Gas Line · <Additional Charge> · Additional refrigerant charge · = · + · (kg) [lbs]
Page 87 of the Mitsubishi Electronics OC366 user manual — (1) Calculate total refrigerant amount by each refrig-
Page 87 · click to enlarge
Page 87

11-2. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.

11-2-1. Introduction R410A refrigerant of this air conditioner is non-toxic and non- flammable but leaking of large amount from an indoor unit into the room where the unit is installed may be deleterious. To prevent possible injury, the rooms should be large enough to keep the R410A concentration specified by KHK : (a high pressure gas safety association) installation guidelines S0010 as follows.

(2) Calculate room volumes ( K [ft

3. ) and find the room with the smallest volume The part with represents the room with the smallest volume. (a) Situation in which there are no partitions

* Maximum concentration Maximum refrigerant concentration of R410A of a room is 0.30 kg/K accordance with the installation guidelines. To facilitate calculation, the maximum concentration is expressed in units of O/K ( kg of R410A per K)

Maximum concentration of R410A : 0.3 O / K [0.019lbs/ft 3 ]

(KHK installation guidelines S0010)

(b) There are partitions, but there are openings that allow

the effective mixing of air.

Direction of refrigerant flow

(Situation in which there are no door openings or in which there are open- ings above and blow doors that occupy at least 0.15% of the floor area)

All refrigerant of this system will leak out to this room if there is leakage at this indoor unit.

11-2-2. Confirming procedure of R410A concentration

(c) If the smallest room has mechanical ventilation apparatus that is linked to a household gas detection

Follow (1) to (3) to confirm the R410A concentration and take appropriate treatment, if necessary.

and alarm device, the calculations should be performed for the second smallest room.

(1) Calculate total refrigerant amount by each refrig-

erant system. Total refrigerant amount is precharged refriger- ant amount at ex-factory plus additional charged amount at field installation.

Outdoor unit Ventilation apparatus

The second smallest room

(3) Use the results of calculations (1) and (2) to calculate the refrigerant concentration:

Total refrigerant in the refrigerating unit (O[lbs]) [ maximum concentration The smallest room in which an indoor (O/K[lbs/ft3]) unit has been installed (K[ft3]) Maximum concentration of R410A:0.3O/K[0.019lbs/ft3]

If the calculation results do not exceed the maximum concen- tration, perform the same calculations for the larger second and third room, etc., until it has been determined that nowhere will the maximum concentration be exceeded.

Show 10 more labels / short text on this page
Outdoor unit · Indoor unit · Outdoor unit · Outdoor unit · Indoor unit · Indoor unit · Opening · Wall · Indoor unit · The smallest room
Page 88 of the Mitsubishi Electronics OC366 user manual — Photo 1 Fan motor
Page 88 · click to enlarge
Page 88

12 DISASSEMBLY PROCEDURE

OUTDOOR UNITPUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU(-BS) PUMY-P48NHMU 1 (-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

OPERATING PROCEDURE PHOTOS & ILLUSTRATION

1. Removing the service panel and top panel (1) Remove 3 service panel fixing screws (5 × 12) and slide

Figure 1 Top panel fixing screws Top panel

Mitsubishi Electronics OC366 — Figure 1 Top panel fixing screws Top panel diagram (page 88)
Fig. 32 · Figure 1 Top panel fixing screws Top panel

the hook on the right downward to remove the service panel. (2) Remove screws (3 for front, 3 for rear/5 × 12) of the top

panel and remove it.

Service panel fixing screws

Photo 1 Fan motor

Photo 2

2. Removing the fan motor (MF1, MF2) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove 5 fan grille fixing screws (5 × 12) to detach the

Fan motor fixing screws

Mitsubishi Electronics OC366 — Photo 1 Fan motor diagram (page 88)
Fig. 33 · Photo 1 Fan motor
Mitsubishi Electronics OC366 — Photo 1 Fan motor diagram (page 88)
Fig. 34 · Photo 1 Fan motor

fan grille. (See Figure 1) (4) Remove a nut (for right handed screw of M6) to detach the

propeller. (See Photo 1.) (5) Disconnect the connectors, CNF1 and CNF2 on Multi con-

troller board in electrical parts box. (6) Remove 4 fan motor fixing screws (5 × 25) to detach the

fan motor. (See Photo 2)

Fan motor fixing screws

Photo 3 3. Removing the electrical parts box (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connecting wire from terminal block. (4) Remove all the following connectors from Multi controller board;

Mitsubishi Electronics OC366 — Photo 1 Fan motor diagram (page 88)
Fig. 35 · Photo 1 Fan motor
  • fan motor, thermistor <Outdoor pipe>, thermistor <Discharge/Compressor>, thermistor <Low pressure saturated temp>, thermistor <Outdoor>, high pressure switch, high pressure sensor, low pressure switch, 4-way valve coil and bypass valve coil. Pull out the disconnected wire from the electrical parts box. <Diagram symbol in the connector housing>
  • Fan motor (CNF1, CNF2)
  • Thermistor <Outdoor pipe> (TH3)
  • Thermistor <Discharge/Compressor> (TH4)
  • Thermistor <Low pressure saturated temp, Outdoor> (TH6/7)
  • High pressure switch (63H)
  • High pressure sensor (63HS)
  • Low pressure switch (63L)
  • Solenoid valve coil <Four-way valve> (21S4)
  • Solenoid valve coil <Bypass valve> (SV1) (5) Remove the terminal cover and disconnect the compres-

Multi controller board (MULTI.B)

Terminal block (TB3) (TB7)

sor lead wire.

Cover panel fixing screws

Continued to the next page.

Show 14 more labels / short text on this page
Service panel · Grille fixing screws · Slide · Fan grille · Grille fixing screws · Front panel · Propeller · Nut · Electrical parts box · Terminal block (TB1) · Valve bed · Compressor (MC) · Terminal cover · Cover panel (Front)
Page 89 of the Mitsubishi Electronics OC366 user manual — PUMY-P36NHMU(R1)/P48NHMU (2) ,(R3)
Page 89 · click to enlarge
Page 89

From the previous page.

OPERATING PROCEDURE PHOTOS & ILLUSTRATION

Photo 4 (6) Remove electrical parts box fixing screw (4 × 10) and

detach the electrical parts box by pulling it upward. The electrical parts box is fixed with 2 hooks on the left and 1 hook on the right.

Mitsubishi Electronics OC366 — OPERATING PROCEDURE PHOTOS & ILLUSTRATION diagram (page 89)
Fig. 36

Electrical parts box fixing screw

Photo 5 4. Removing the thermistor <Low pressure saturated temp.> (TH6) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connector, TH6 and TH7 (red), on the Multi

Mitsubishi Electronics OC366 — OPERATING PROCEDURE PHOTOS & ILLUSTRATION diagram (page 89)
Fig. 37

controller board in the electrical parts box. (4) Loosen the wire clamps on top of the electrical parts box. (5) Pull out the thermistor

(TH6) from the sensor holder.

Note: In case of replacing thermistor <Low pressure satu-

rated temp.> (TH6), replace it together with thermistor <Outdoor> (TH7) since they are combined together. Refer to No.5 below to remove thermistor <Outdoor>.

Thermistor Electrical parts box

5. Removing the thermistor (TH7) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connector TH6 and TH7 (red) on the Multi

Photo 6

PUMY-P48NHMU (1)

Mitsubishi Electronics OC366 — Photo 6 diagram (page 89)
Fig. 38 · Photo 6

controller board in the electrical parts box. (4) Loosen the wire clamps on top of the electrical parts box.

(See Photo 4) (5) Pull out the thermistor (TH7) from the sensor

holder.

Note: In case of replacing thermistor <Outdoor> (TH7),

replace it together with thermistor <Low pressure saturated temp> (TH6), since they are combined together. Refer to No.4 above to remove thermistor <Low pres- sure saturated temp>.

Lead wire of thermistor (TH7)

PUMY-P36NHMU(R1)/P48NHMU (2) ,(R3)

Mitsubishi Electronics OC366 — PUMY-P36NHMU(R1)/P48NHMU (2) ,(R3) diagram (page 89)
Fig. 39

Lead wire of thermistor (TH7) Sensor holder

Electrical parts box · Sensor holder

Page 90 of the Mitsubishi Electronics OC366 user manual — Photo 8
Page 90 · click to enlarge
Page 90

OPERATING PROCEDURE PHOTOS

Photo 7 6. Removing the thermistor <Outdoor pipe> (TH3) and ther- mistor <Discharge/Compressor> (TH4) (1) Remove the service panel. (See Figure 1) (2) Disconnect the connectors, TH3 (white) and TH4 (white),

Thermistor (TH3)

Mitsubishi Electronics OC366 — OPERATING PROCEDURE PHOTOS diagram (page 90)
Fig. 40

on the Multi controller board in the electrical parts box. (3) Loosen the clamp for the lead wire in the rear of the elec-

trical parts box. (4) Pull out the thermistor (TH3) and ther-

mistor (TH4) from the sensor holder.

7. Removing the 4-way valve coil (21S4) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1)

Photo 8

4-way valve coil (21S4)

[Removing the 4-way valve coil] (3) Remove 4-way valve solenoid coil fixing screw (M4 × 6). (4) Remove the 4-way valve coil by sliding the coil toward you. (5) Disconnect the connector 21S4 (green) on the Multi con-

Mitsubishi Electronics OC366 — Photo 8 diagram (page 90)
Fig. 41 · Photo 8

troller board in the electrical parts box.

8. Removing the 4-way valve (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove 3 valve bed fixing screws (4 × 10) and 4 ball

Thermistor (TH6)

valve and stop valve fixing screws (5 × 16) and then remove the valve bed. (4) Remove 5 right side panel fixing screws (5 × 12) in the

4-way valve coil fixing screw

rear of the unit and then remove the right side panel. (5) Remove the 4-way valve coil. (See Photo 8) (6) Recover refrigerant. (7) Remove the welded part of 4-way valve. Note 1: Recover refrigerant without spreading it in the air. Note 2: The welded part can be removed easily by remov-

ing the right side panel. Note 3: When installing the 4-way valve, cover it with a wet

cloth to prevent it from heating (120 °C [248 °F] or more), then braze the pipes so that the inside of pipes are not oxidized.

Show 4 more labels / short text on this page
Thermistor <Compressor> (TH4) · Compressor (MC) · Thermistor <Discharge> (TH4) · 4-way valve
Page 91 of the Mitsubishi Electronics OC366 user manual — Photo 10
Page 91 · click to enlarge
Page 91

OPERATING PROCEDURE PHOTOS

9. Removing bypass valve coil (SV1) and bypass valve (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove 5 right side panel fixing screws (5 × 12) in the

Photo 9

Mitsubishi Electronics OC366 — Photo 9 diagram (page 91)
Fig. 42 · Photo 9

rear of the unit and remove the right side panel. (4) Remove the bypass valve coil fixing screw (M4 × 6). (5) Remove the bypass valve coil by sliding the coil upward. (6) Disconnect the connector SV1 (white) on the Multi control-

ler circuit board in the electrical parts box. (7) Recover refrigerant. (8) Remove the welded part of bypass valve.

High pressure switch (63H)

ing the right side panel.

Bypass valve coil fixing screw

Bypass valve coil (SV1)

10. Removing the high pressure switch (63H) and low pressure switch (63L) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the electrical parts box. (See Photo 4) (4) Remove 5 right side panel fixing screws (5 o 12) in the

High pressure sensor (63HS)

rear of the unit and remove the right side panel. (5) Pull out the lead wire of high pressure switch and low

pressure switch. (6) Recover refrigerant. (7) Remove the welded part of high pressure switch and low

pressure switch.

the right side panel. Note 3: When installing the high pressure switch and low

Photo 10

pressure switch, cover them with a wet cloth to pre- vent them from heating (100 °C [212 °F] or more), then braze the pipes so that the inside of pipes are not oxidized.

Mitsubishi Electronics OC366 — Photo 10 diagram (page 91)
Fig. 43 · Photo 10
11. Removing the high pressure sensor (63HS) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the electrical parts box. (See Photo 4) (4) Remove 5 right side panel fixing screws (5 o 12) in the

rear of the unit and remove the right side panel. (5) Pull out the lead wire of high pressure sensor. (6) Recover refrigerant. (7) Remove the welded part of high pressure sensor.

the right side panel. Note 3: When installing the high pressure sensor, cover it

with a wet cloth to prevent it from heating (100 °C [212 °F] or more), then braze the pipes so that the inside of pipes are not oxidized.

High pressure sensor (63HS)

Low pressure switch (63L)

Bypass valve

Page 92 of the Mitsubishi Electronics OC366 user manual — Photo 13
Page 92 · click to enlarge
Page 92

OPERATING PROCEDURE PHOTOS

12. Removing the compressor (MC) (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove 2 front cover panel fixing screws (5 × 12) and

Photo 11

Mitsubishi Electronics OC366 — Photo 11 diagram (page 92)
Fig. 44 · Photo 11

remove the front cover panel. (See Photo 3) (4) Remove 2 back cover panel fixing screws (5 × 12) and

remove the back cover panel. (5) Remove the electrical parts box. (See Photo 3) (6) Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve

and stop valve fixing screws (5 × 16) and then remove the valve bed. (7) Remove 4 right side panel fixing screws (5 × 12) in the

Valve bed fixing screws

Valve bed fixing screw

rear of the unit and then remove the right side panel. (8) Remove 3 separator fixing screws (4 × 10) and remove

the separator. (9) Recover refrigerant. (10) Remove the 3 points of the motor for compressor fixing nut

using a spanner or a monkey wrench. (11) Remove the welded pipe of motor for compressor inlet and

outlet and then remove the compressor.

13. Removing the accumulator (1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove 2 front cover panel fixing screws (5 × 12) and

Photo 12

Mitsubishi Electronics OC366 — Photo 12 diagram (page 92)
Fig. 45 · Photo 12

remove the front cover panel. (See Photo 3) (4) Remove 2 back cover panel fixing screws (5 × 12) and

remove the back cover panel. (5) Remove the electrical parts box. (See Photo 3) (6) Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve

and stop valve fixing screws (5 × 16) and then remove the valve bed. (7) Remove 4 right side panel fixing screws (5 × 12) in the

rear of the unit and then remove the right side panel. (8) Recover refrigerant. (9) Remove 4 welded pipes of power receiver inlet and outlet. (10) Remove 2 receiver leg fixing screws (4 × 10). (See Photo 13)

Photo 13

Mitsubishi Electronics OC366 — Photo 13 diagram (page 92)
Fig. 46 · Photo 13

Accumulator leg fixing screws

Show 11 more labels / short text on this page
Valve bed · Compressor (MC) · Accumulator · Separator · Compressor fixing nut · Separator fixing screw · Inlet · Outlet · Accumulator · Accumulator · Accumulator leg
Page 93 of the Mitsubishi Electronics OC366 user manual — PUMY-P48 NHMU 1 (-BS)
Page 93 · click to enlarge
Page 93

13 PARTS LIST

13-1. STRUCTURAL PARTS PUMY-P48NHMU PUMY-P48NHMU-BS PUMY-P48NHMU 1 PUMY-P48NHMU 1 -BS

3 4 5 6

w Parts of PUMY-P48NHMU are set as the same service parts as PUMY-P48NHMU-BS.

Q , ty/set

Remarks (Drawing No.)

Part No. Part Name Specification No.

Q,ty PUMY-P48 NHMU(-BS)

PUMY-P48 NHMU 1 (-BS)

R01 E04 662

SIDE PANEL (L)

T7W E02 691

FAN GRILLE

T7W E04 667

FRONT PANEL

R01 E18 686

BASE ASSY

R01 E26 686

BASE ASSY

R01 E19 130

MOTOR SUPPORT

R01 30L 655

HANDLE

T7W E01 658

COVER PANEL (FRONT)

R01 E14 658

COVER PANEL (FRONT)

T7W E00 658

COVER PANEL (REAR)

R01 E05 658

COVER PANEL (REAR)

T7W E16 661

SIDE PANEL (R)

T7W E06 668

SERVICE PANEL

R01 E01 698

REAR GUARD

R01 E06 641

TOP PANEL

R01 E00 655

HANDLE

Show 7 more labels / short text on this page
Wiring Diagram · Recom- mended · Symbol · Including CONDUIT PLATE · Including CONDUIT PLATE · Including CONDUIT PLATE · Including CONDUIT PLATE
Page 94 of the Mitsubishi Electronics OC366 user manual — 13-2. FUNCTIONAL PARTS PUMY-P48NHMU PUMY-P48NHMU 1 PUMY-P48NHMU-BS PUMY-P48NHMU 1 -BS
Page 94 · click to enlarge
Page 94

13-2. FUNCTIONAL PARTS PUMY-P48NHMU PUMY-P48NHMU 1 PUMY-P48NHMU-BS PUMY-P48NHMU 1 -BS

24 23 22

13 14 15

Page 95 of the Mitsubishi Electronics OC366 user manual — T7W E01 233
Page 95 · click to enlarge
Page 95

Part numbers that are circled are not shown in the figure.

Q , ty/set

Remarks (Drawing No.)

Part No. Part Name Specification No.

PUMY-P48NHMU (1) PUMY-P48NHMU (1) -BS

R01 E44 221

FAN MOTOR

MF1,2

R01 E01 115

PROPELLER FAN

R01 E02 097

NUT

T7W E07 413

CHARGE PLUG

ANB33FDCMT Including RUBBER MOUNT

T97 410 742

COMPRESSOR

MC

T7W E04 410

STOP VALVE

3/8

T7W E06 411

BALL VALVE

5/8

R01 E03 450

STRAINER

R01 E35 440

ACCUMULATOR

T7W E02 490

OIL SEPARATOR

:2.5:0.81000mm

R01 E22 425

CAPILLARY TUBE

[(3/32) % : (1/32) % L(39-1/2)]inch

T7W E04 208

H.P SENSOR

63HS

R01 25T 209

LOW PRESSURE SWITCH

T7W E03 428

BYPASS VALVE

T7W E17 242

SOLENOID COIL <BYPASS VALVE>

SV1

T7W E18 242

SOLENOID COIL <4-WAY VALVE>

21S4

T7W E05 403

4-WAY VALVE

R01 E75 202

THERMISTOR

TH6,7

T7W E05 208

HIGH PRESSURE SWITCH

63H

T7W E29 408

HEAT EXCHANGER

T7W E02 259

CONTACTOR

T7W 850 716

TERMINAL BLOCK

3P (L1,L2,GR)

TB1

T7W E14 346

NOISE FILTER CIRCUIT BOARD

N.F.

R01 H76 310

MULTI CONTROLLER CIRCUIT BOARD

MULTI.B.

T7W E17 716

TERMINAL BLOCK

3P (M1, M2, S)

TB3, TB7

R01 E01 311

TRANSMISSION POWER BOARD

M-P.B.

T7W E01 234

RESISTOR

RS

T7W E09 259

REACTOR

DCL

T7W E26 313

POWER CIRCUIT BOARD

P.B.

T7W E01 233

ACT MODULE

ACTM

T7W E09 254

MAIN SMOOTHING CAPACITOR

CB

R01 E66 202

THERMISTOR (OUTDOOR PIPE)

TH3

R01 E00 201

THERMISTOR (DISCHARGE)

TH4

R01 E65 202

THERMISTOR (HEATSINK)

TH8

Show 4 more labels / short text on this page
Wining Diagram · Recom- mended · Q,ty · Symbol
Page 96 of the Mitsubishi Electronics OC366 user manual — 14-1. FUNCTIONAL PARTS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)
Page 96 · click to enlarge
Page 96

14 RoHS PARTS LIST

14-1. FUNCTIONAL PARTS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

Mitsubishi Electronics OC366 — 14-1. FUNCTIONAL PARTS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS) diagram (page 96)
Fig. 47
Page 97 of the Mitsubishi Electronics OC366 user manual — G
Page 97 · click to enlarge
Page 97

Part numbers that are circled are not shown in the figure.

Q'ty/set

RoHS

PUMY-P·(-BS)

Remarks (Drawing No.)

Part No. Part Name Specification No.

36NHMU 48NHMU 2 2

36NHMUR1 48NHMUR3

G

T7W E27 763

FAN MOTOR

MF1,2

G

R01 E08 115

PROPELLER FAN

G

R01 E12 115

PROPELLER FAN

G

R01 E09 097

NUT

G

T7W E07 413

CHARGE PLUG

G

T7W E12 413

CHARGE PLUG

ANB33FDHMT Including RUBBER MOUNT ANB33FDSMT Including RUBBER MOUNT

G

T97 415 755

COMPRESSOR

MC

G

T97 415 779

COMPRESSOR

MC

G

T7W E04 410

STOP VALVE

3/8

G

T7W E06 411

BALL VALVE

5/8

G

R01 E28 201

THERMISTOR(COMPRESSOR)

TH4

G

R01 E44 440

ACCUMULATOR

G

T7W E02 490

OIL SEPARATOR

G

R01 E26 425

CAPILLARY TUBE

:2.5:0.81000mm [:(3/32) % :(1/32) % L(39-1/2)]inch

G

R01 E07 208

H.P SENSOR

63HS

G

R01 E00 209

LOW PRESSURE SWITCH

G

T7W E03 428

BYPASS VALVE

G

T7W E17 242

SOLENOID COIL <BYPASS VALVE>

SV1

G

T7W E18 242

SOLENOID COIL <4-WAY VALVE>

21S4

G

T7W E05 403

4-WAY VALVE

G

R01 H01 202

THERMISTOR

TH6,7

G

T7W E07 208

HIGH PRESSURE SWITCH

63H

G

T7W E41 408

HEAT EXCHANGER

G

R01 V03 310

CONTROLLER CIRCUIT BOARD

C.B.

G

R01 V14 310

CONTROLLER CIRCUIT BOARD

C.B.

G

R01 E27 246

TERMINAL BLOCK

3P (M1, M2, S)

TB3, TB7

G

R01 E02 311

M-POWER BOARD

M-NET.P.B.

G

R01 E04 311

M-POWER BOARD

M-NET.P.B.

G

R01 E20 259

REACTOR

DCL

G

T7W E17 259

REACTOR

DCL

G

R01 E64 313

POWER CIRCUIT BOARD

P.B.

G

R01 E65 313

POWER CIRCUIT BOARD

P.B.

G

R01 E07 233

ACT MODULE

ACTM

G

T7W E45 716

TERMINAL BLOCK

3P (L1,L2,GR)

TB1

G

R01 E18 346

NOISE FILTER CIRCUIT BOARD

N.F.

G

R01 E99 202

THERMISTOR (HEATSINK)

TH8

G

R01 E22 255

MAIN SMOOTHING CAPACITOR

CE

G

R01 H00 202

THERMISTOR (OUTDOOR PIPE)

TH3

G

R01 E12 201

THERMISTOR (DISCHARGE)

TH4

G

R01 E06 239

FUSE

250V, 6.3A

F1, 2

Show 4 more labels / short text on this page
Wining Diagram · Recom- mended · Symbol · Q'ty
Page 98 of the Mitsubishi Electronics OC366 user manual — Part No. Part Name
Page 98 · click to enlarge
Page 98

14-2. STRUCTURAL PARTS PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS) PUMY-P48NHMU 2 (-BS) PUMY-P48NHMUR3(-BS)

3 4 5 6

w Parts of PUMY-P36/48NHMU are set as the same service parts as

PUMY-P36/48NHMU-BS.

Q , ty/set

Speci- fication No.

RoHS

Remarks (Drawing No.)

Part No. Part Name

PUMY-P36 NHMUR1(-BS) PUMY-P48 NHMU 2 (-BS)

PUMY-P48 NHMUR3(-BS)

G

T7W E06 662

SIDE PANEL (L)

G

T7W E03 691

FAN GRILLE

G

T7W E06 667

FRONT PANEL

G

R01 E26 686

BASE ASSY

G

R01 E19 130

MOTOR SUPPORT

G

R01 E01 655

HANDLE

G

R01 E14 658

COVER PANEL (FRONT)

G

R01 E24 658

COVER PANEL (REAR)

G

T7W E01 617

CONDUIT PLATE

G

T7W E19 661

SIDE PANEL (R)

G

T7W E06 668

SERVICE PANEL

G

R01 E07 698

REAR GUARD

G

R01 E29 641

TOP PANEL

G

R01 E02 655

HANDLE

Show 4 more labels / short text on this page
Wiring Diagram · Recom- mended · Q’ty PUMY-P36 NHMU(-BS) · Symbol
Page 99 of the Mitsubishi Electronics OC366 user manual — NUMBER OF BRANCHING POINTS
Page 99 · click to enlarge
Page 99

15 OPTIONAL PARTS

DRAIN SOCKET

Part No. PAC-SG61DS-E

AIR OUTLET GUIDE

Part No. PAC-SG59SG-E

w Need 2 pieces.

AIR GUIDE

Part No. PAC-SH63AG-E

w Need 2 pieces.

DRAIN PAN

Part No. PAC-SG64DP-E

BRANCH PIPE (Joint)

Part No.

NUMBER OF BRANCHING POINTS

CMY-Y62-G-E CMY-Y64-G-E

2 4 CMY-Y68-G-E 8

Page 100 of the Mitsubishi Electronics OC366 user manual — TM
Page 100 · click to enlarge
Page 100

TM

HEAD OFFICETOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN

cCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Dec. 2010 No. OC366 REVISED EDITION-F Distributed in Sep. 2010 No. OC366 REVISED EDITION-E PDF 5 Distributed in Nov. 2009 No. OC366 REVISED EDITION-D PDF 7 Distributed in Jul. 2008 No. OC366 REVISED EDITION-C PDF 7 Distributed in Dec. 2007 No. OC366 REVISED EDITION-B PDF 9 Distributed in Apr. 2006 No. OC366 REVISED EDITION-A PDF 10 Distributed in Jan. 2006 No. OC366 PDF 10 Made in Japan

New publication, effective Dec. 2010 Specifications subject to change without notice

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
SW4of the outdoor unit. p.51
C82A: DC15V p.67
C510: DC290V–350V p.67
SW110110100 p.67
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Though the content of operation is displayed on the remote controller, some indoor units do not operate.• The power supply of the indoor unit is not on. • The address of the indoor units in same group or the remote controller is not set correctly. • The group setting between outdoor units is not registered to the remote controller. • The fuse on the indoor unit controller board is blown.• Check the part where the abnormality occurs. The entire system In the entire refrigerant system In same group only 1 indoor unit only <In case of the entire system or in the entire refrigerant system> • Check the self-diagnosis LED of the outdoor unit. • Check the items shown in the left that are related to the outdoor unit. <In case of in same group only or 1 indoor unit only> • Check the items shown in the left that are related to the indoor unit. p.54
Though the indoor unit operates, the display of the remote controller goes out soon.• The power supply of the indoor unit is not on. • The fuse on the indoor unit controller board is blown. p.54
( ) is not displayed on the remote controller. (M-NET remote controller is not fed.)• The power supply of the outdoor unit is not on. • The connector of transmission outdoor power board is not connected. • The number of connected indoor unit in the refrigeration system is over the limit or the number of connected remote controller is over the limit. • M-NET remote controller is connected to MA remote controller cable. • The transmission line of the indoor/outdoor unit is shorted or down. • M-NET remote controller cable is shorted or down. • Transmission outdoor power board failure. p.54
"HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed about 3 minutes after the power supply of the outdoor unit is on.)• The power supply for the feeding expansion unit for the transmission line is not on. • The address of the outdoor unit remains "00". • The address of the indoor unit or the remote controller is not set correctly. • MA remote controller is connected to the transmission line of the indoor/outdoor unit. p.54
The remote controller does not operate though ( ) is displayed.• The transmission line of the indoor/outdoor unit is connected to TB15. • The transmission line of the indoor/outdoor unit is shorted, down or badly contacted. p.54
Though the indoor unit operates, the display of the remote controller goes out soon.• The power supply of the indoor unit (Master) is not on. • In case of connecting the system controller, the setting of the system controller does not correspond to that of MA remote controller. • The fuse on the indoor unit (Master) controller board is blown. p.54
( ) is not displayed on the remote controller. (MA remote controller is not fed.)The remote controller is not fed until the power supply of both indoor unit and outdoor unit is on and the start-up of both units is finished normally. • The power supply of the indoor unit is not on. • The power supply of the outdoor unit is not on. • The number of connected remote controller is over the limit (Maximum: 2 units) or the number of connected indoor unit that is over the limit (Maximum: 16 units). • The address of the indoor unit is "00" and the address for the outdoor unit is the one other than "00". • The transmission line of the indoor/outdoor unit is connected to TB15. • MA remote controller is connected to the transmission line of the indoor/outdoor unit . • The remote controller cable is shorted or down. • The power supply cable or the transmission line is shorted or down. • The fuse on the indoor unit controller board is blown. p.54
"PLEASE WAIT" keeps being dis- played or it is displayed periodically. ("PLEASE WAIT" is usually dis- played about 3 minutes after the power supply of the outdoor unit is on.)• The power supply of the outdoor unit is not on. • The power supply of the feeding expansion unit for the transmission line is not on. • The setting of MA remote controller is not main remote controller, but sub-remote controller. • MA remote controller is connected to the transmission line of the indoor/outdoor unit. p.54
The remote controller does not operate though ( ) is displayed.• The power supply of the indoor unit (Master) is not on. • The transmission line of the indoor/outdoor unit is connected to TB15. • The transmission line of the indoor/outdoor unit is shorted, down or badly contacted. •The fuse on the indoor unit controller board is blown. p.54

Ask about the Mitsubishi Electronics OC366

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics OC366

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics OC366 manual PDF

100 pages·11.3 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…