This installation manual is only for the outdoor unit installation. In installing the indoor units, refer to the installation manual attached to each indoor unit. Any structural alternations necessary for the installation must comply with the local building code require- ments.
I Do not install the unit by yourself (customer).
I Perform electrical work according to the in-
Incomplete installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you pur- chased the unit or special installer. I Install the unit securely in a place which can
stallation manual and be sure to use an ex- clusive circuit. If the capacity of the power circuit is insufficient or there is insufficient electrical work, it could re- sult in a fire or an electric shock. I Attach the electrical cover to the indoor unit
K
bear the weight of the unit. When installed in an insufficient strong place, the unit could fall causing injury. I Use the specified wires to connect the indoor
and the service panel to the outdoor unit se- curely. If the electrical cover in the indoor unit and/or the service panel in the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust water, etc. I Be sure to use the part provided or specified
and outdoor units securely and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not ap- plied to the sections. Incomplete connecting and fixing could cause fire. I Do not use intermediate connection of the
parts for the installation work. The use of defective parts could cause an injury due to a fire, an electric shock, the unit falling, leakage of water, etc. I Be sure to cut off the main power in case of
power cord or the extension cord and do not connect many devices to one AC outlet. It could cause a fire or an electric shock due to defective contact, defective insulation, exceed- ing the permissible current, etc. I Check that the refrigerant gas due not leak
Open as a rule More than 500 mm if the front and both sides are open
setting up the indoor electronic control P.C. board or wiring works. It could cause an electric shock. I The appliance shall be installed in accordance
after installation has completed. If refrigerant gas leaks indoors, and comes into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated. I Perform the installation securely referring to
with national wiring regulations. I When installing or relocating the unit, make
More than 100 mm More than 200 mm if there are obstacles to both sides
sure that no substance other than the speci- fied refrigerant (R410A) enters the refrigerant circuit. Any presence of foreign substance such as air can cause abnormal pressure rise or an explo- sion.
the installation manual. Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water.
More than 100 mm
CAUTION
I Perform earthing.
I Install an earth leakage breaker depending on
Do not connect the earth wire to a gas pipe, wa- ter pipe, lightning rod or telephone earth wire. Defective earthing could cause an electric shock. I Do not install the unit in a place where an in-
the installation place (Where it is humid). If a earth leakage breaker is not installed, it could cause an electric shock. I Perform the drainage/piping work securely
Open as a rule More than 500 mm if the back, both sides and top are open More than 350 mm
flammable gas leaks. If gas leak and accumulate in the area surround- ing the unit, it could cause an explosion. I Fasten a flare nut with a torque wrench as
according to the installation manual. If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
specified in this manual. When fastened too tight, a flare nut may broken after a long period and cause a leakage of refrig- erant.

Parts to be locally procured
2-U-shape notched holes (Base bolt M10)
2-12 × 36 Oval holes (Base bolt M10) (Unit: mm)
You should note that indoor unit that can be connected to this outdoor unit have the following constraints on them. • Indoor units with model numbers 22, 25, 35, 50, 60 and 71 can be connected. Refer to the table below for possible two-room, three-room and four-room indoor unit combinations.
Air in · Air in · Air out


100 or more 200 or more

Fix here with M10 bolts.
350 or more 100 or more
Make the setting depth deeper.
Make with wider.

25 mm or less
Anchor both length Anchor both pitch
Please perform the drain piping work only when draining from one place.
350 or more 500 or more
1Please choose one hole to discharge drain and install the drain socket to the hole. 2Please close the rest of the holes with the drain caps. 3Please connect a vinyl hose of 25 mm in the inside diameter on the market with the drain socket and lead drain.

Power cable terminal block
Indoor/Outdoor connecting terminal block
Power supply cord Specification Cable 3-core 2.5 mm2, in conformity with Design 245 IEC 57. Indoor and Outdoor connecting wire Specification Cable 4-core 1.0/1.5 mm2, in conformity with Design 245 IEC 57.
Opening for power cable and indoor/out- door connecting wire
This installation manual is only for the outdoor unit installation. In installing the indoor units, refer to the installation manual attached to each indoor unit.
Liquid Ç UNIT GAS
Indoor/outdoor unit connecting wire
Liquid ı UNIT GAS
4-4 INDOOR/OUTDOOR WIRE CONNECTION AND OUTDOOR POWER SUPPLY CORD CONNECTION
POWER SUPPLY ~/N 230 V 50 Hz
WARNING: Be sure to comply with “Technical Standards for Electrical Installation”, follow this manual and use special circuits for electrical work. If there is a lack of circuit capacity or some deficiency in installation, it may cause a risk of fire or electric shock. Overcurrent that might be produced may include DC substances. Be careful to choose the correct type of overcurrent protection switch.
Power supply cord A
Rated Voltage Breaker capacity 230 V 25 A
Connect to the supply terminals and leave a contact separation of at least 3 mm at each pole to disconnect the source power pole. (When the power switch is shut off, it must disconnect all poles.)
Indoor/Outdoor unit connecting wire B

Refrigerant adjustment If pipe length exceeds 40 m, additional refrigerant (R410A) charge is required. (The outdoor unit is charged with refrigerant for total pipe length up to 40 m.)
1If you use commercially available copper pipes, use the following table for pipe specifications.
Outside diameter Wall thickness Liquid pipe ø6.35 mm 0.8 mm Gas pipe ø9.52 mm 0.8 mm Gas pipe ø12.7 mm 1.0 mm Gas pipe ø15.88 mm 1.0 mm
2For insulation material, use 8 mm-thick heat-insulating expended polyethylene with a specific gravity of 0.045. 3Ensure that the 2 refrigerant pipes are insulated to prevent condensation. 4Refrigerant pipe bending radius must be 100 mm or more.
The diameter of connection pipes differs according to the type and capacity of indoor units. Match the diameters of connection pipes for indoor and outdoor units according to the following table.

Wing nut type Clutch type
Connect the refrigerant pipes (both liquid pipe and gas pipe) between the indoor and the outdoor unit.
Remove the service port cap of the stop valve on the gas pipe side of the outdoor unit. (The stop valve will not work in it initial state fresh out of the factory [totally closed with cap on].)
Firmly hold copper pipe in a die in the dimension shown in the table above.
Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit.
Inside is shining without any scratches
Run the vacuum pump. (Vacuumize for more than 15 minutes.)
Check the vacuum with the gauge manifold valve, then close the gauge manifold valve and stop the vacuum pump.
Even length all around
Leave it as is for one or two minutes. Make sure the pointer of the gauge manifold valve remains in the same position. Confirm that the pressure gauge shows –0.101 MPa [Gauge] (–760 mmHg).
Compound pressure gauge (for R410A) -0.101MPa (-760 mmHg)
Pressure gauge (for R410A)
Stop valve (gas side)
Gauge manifold valve (for R410A)
Charge hose (for R410A)
hand. - For tightening the union part of the indoor unit side, use the table below as a standard and tighten
(or the vacuum pump with the function to prevent the back flow)
the flare nut with two wrenches. Excessive tightening damages the flared section.
Adapter for preventing the back flow

Charge hose (for R410A)
Remove the gauge manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and liquid pipe. Operating without fully opening lowers the performance and this causes trouble.
Pipe length up to 40 m No gas charge is needed.
Pipe length exceeding 40 m Charge the prescribed amount of gas. (refer to 5-1)
torque wrench or spanner.
Tighten the cap to the service port to obtain the initial status.
Retighten the cap.
![Page 8 of the Mitsubishi Electronics MXZ-4A80VA user manual — [How to lock the operation mode]](/cdn/reader/ef/ef8b2ddb181c9a8e11cc3503b544412dfd9e69771f76b71b8c7a13682424d90f/images/page-8.webp?w=400)


Tightening torque N·m kgf·cm Cap for service port 13.7 to 17.7 140 to 180 Cap for stop valve 19.6 to 29.4 200 to 300
* Initial setting is required to activate this function. Please ex- plain about this function to your customers and ask them whether they want to use it.
Put the earth circuit to the ground in accordance with “Technical Standards for Electrical Installation”.
1Be sure to turn off the main power for the air conditioner before making the setting. 2Set the 3rd Dip Switch of SW1 on the outdoor controller board to ON to enable this function. 3Turn on the main power for the air conditioner.
Lower the operating noise
The product incorporates a frequency inverter and so requires earthing in order to observe electric charge and noise caused by static electricity.
5-6 LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
After finishing the installation, check the following items again by marking .
Have special circuits been provided? Is power supply voltage as specified? Has indoor/outdoor connecting wire been inserted into terminal block? Has indoor/outdoor connecting wire been secured firmly? Has intermediary connection between power cable and indoor/outdoor connecting wire been carried out? Is combination of connection pipes and indoor/outdoor connecting wire correct (Room A, Room B, Room C, Room D)? Is earth cable connection correct? Has leak test been carried out? Has air purge been carried out? Is stop valve fully open? Has drain discharge been checked? Is insulation over connection pipe joints correct? Is strength of installation location well enough? Have all of WARNING and CAUTION items in “1. THE FOLLOWING SHOULD ALWAYS BE OB- SERVED FOR SAFETY” been checked?
* Initial setting is required to activate this function. Please ex- plain about this function to your customers and ask them whether they want to use it.
1Be sure to turn off the main power for the air conditioner before making the setting. 2Set the 2nd Dip Switch of SW1 on the outdoor controller board to ON to enable this function. 3To lock the operation mode in COOL/DRY mode, set the 1st Dip Switch of SW1 on the outdoor controller board to OFF. To lock the operation in HEAT mode, set the same switch to ON. 4Turn on the main power for the air conditioner.

5-10 TEST RUN
Perform gas charge to unit.
1Connect gas cylinder to the service port of stop valve. 2Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder. 3Replenish specified amount of the refrigerant, while operating the air conditioner for cooling.
If the customer (user) is absent, explain to the purchaser (owner, building’s controller, etc) about those points.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 40°C) during cold season. But never use naked fire or steam.


Refrigerant gas cylinder operating valve (for R410A)
Gauge manifold valve (for R410A) Charge hose (for R410A)
Refrigerant gas cylinder for R410A with siphon
Electronic scale for refrigerant charging
Indoor · unit · Refrigerant (liquid)