Instruction/ maintenance manual of the product MSZ-FA35VA Mitsubishi Electronics
Go to page of 40
SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ····································2 2. P ART NAMES AND FUNCTIONS ······················3 3. SPECIFICA TION·················································5 4.
2 1 TECHNICAL CHANGES MSZ-A09YV - ➔ MSZ-F A25V A - MSZ-A12YV - ➔ MSZ-F A35V A - E1 E1 E1 E1 12. PLASMA DEODORIZING/AIR PURIFYING filter units have been added. 13. i-see Sensor has been added. (i-see control operation and AREA setting have been added.
3 P ART NAMES AND FUNCTIONS 2 INDOOR UNIT MSZ-F A25V A - MSZ-F A35V A - E1 E1 Line flow fan Air outlet Vertical vane Air inlet Display section Front panel PLASMA DEODORIZING filter Panel Heat exchange.
4 ACCESSORIES 1 2 3 4 5 6 7 Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless r.
5 SPECIFICA TION 3 T3.15AL250V NSEJ001DA1 12V DC 100 " (at 25˚C) MP20Z 12V DC 300 " (at 25˚C) MSBPC20M16 12V DC 250 " (at 25˚C) MSBPC20M1 1 12V DC 300 " (at 25˚C) ERZV14D471 A2.
6 4 NOISE CRITERIA CUR VES 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, dB re 0.
7 OUTLINES AND DIMENSIONS 5 MSZ-F A25V A - E1 Unit : mm INDOOR UNIT 780 155 155 335 320 41.5 215 42.5 214 3 287.5 70 55 55 55 225 225 298 90 106 or more 7 100 198 5 53.
8 6 WIRING DIAGRAM REFRIGERANT SYSTEM DIAGRAM 7 MSZ-F A25V A - E1 Indoor heat e xchanger Flared connection Room temperature thermistor R T11 Indoor coil thermistor R T13(sub) Flared connection Refrigerant flow in cooling Refrigerant flow in heating Refrigerant pipe [ 9.
9 SER VICE FUNCTIONS 8 8-2. P .C. BOARD MODIFICA TION FOR INDIVIDUAL OPERA TION A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller , P .C.
10 NOTE: • The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller . • If main power is turned OFF or a power failure occurs while AUT O ST AR T/ST OP timer is active, the timer setting is cancelled.
2 1 Stopper Lock. Left Insert this end first. 11 TROUBLESHOOTING 9 3. T roubleshooting procedure 1) First, check if the OPERA TION INDICA TOR lamp on the indoor unit is flashing on and of f to indicate an abnormality . T o make sure, check how many times the abnormality indication is flashing on and off before starting service work.
12 If PLASMA/W ASH lamp on the indoor unit blinks, clean the filters as soon as possible. The lamp will start blinking when accumulated operating time exceeds 330 hours. <Remove> (1) Switch the indoor unit OFF with the remote controller and disconnect the power supply plug and/ or turn OFF the breaker .
13 INFORMA TION FOR MUL TI SYSTEM AIR CONDITIONER OUTDOOR UNIT : MXZ series Multi system air conditioner can connect two or more indoor units with one outdoor unit. •Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units.
14 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur .
15 2. Flow chart of PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode recall function Operational procedure Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
16 4. Indoor unit failure mode table NOTE: Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.). 5. PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode table 12-time flash 2.5-second OFF Replace the indoor electronic control P.
17 Start Indoor unit operates. Outdoor unit doesn't operate. Indoor unit doesn't receive the signal from remote controller . OPERA TION INDICA T OR lamp on the indoor unit is flashing on and off. OPERA TION INDICA T OR lamp on the indoor unit stays off.
18 NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P .C. board turns OFF the indoor fan motor with OPERA TION INDICA TOR lamp flashing.
19 Lighted Blinking Not lighted Lighted Blinking Not lighted Lighted Blinking Not lighted · Flashing of AREA lamp(left-hand side lamp) indicates abnormality . NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P .
20 9-5. T rouble criterion of main parts MSZ-F A25V A - MSZ-F A35V A - E1 E1 Part name Figure Check method and criterion Measure the resistance with a tester .
21 Check of indoor fan motor A When POWER lamp flashes 3-time. Indoor fan does not operate. w If 12 seconds or more passes after EMERGENCY OPERATION switch is pressed, the voltage mentioned above 2 goes 0V DC although the indoor electric control P.C. board is normal.
22 Check of remote controller and receiver P .C. board B Indoor unit operates by pressing EMERGENCY OPERA TION switch, but does not operate with the remote controller . w Check if the remote controller is exclusive for this air conditioner . Y es Replace the batteries.
23 The unit does not operate with the remote controller . Also, POWER lamp does not light up by pressing EMERGENCY OPERA TION switch. Check of indoor electronic control P .C. board and indoor fan motor C Yes No w 1. The fan motor connector's 1 lead wire is red, whereas 3 is black.
24 How to check mis-wiring and serial signal error D When POWER lamp flashes ON and OFF in every 0.5-second. Outdoor unit does not operate. Is there rated voltage of 230V AC in the power supply? In 3 minutes after turning ON the power supply of the outdoor unit, does the LED on the inverter P.
25 Check of installation of the horizontal vane E Start Replace the indoor electronic control P .C. board. Replace the interlock switch(Fan). Is the stopper of the horizontal vane locked to the indoor unit correctly? Y es No Is there resistance 0 " ? Relock the stopper of the horizontal vane to the indoor unit.
26 Check of PLASMA DEODORIZING power F When PLASMA/W ASH lamp flashes 2-time. w w The power failure mode for PLASMA DEODORIZING power is memorized when the failure mode is called. After performing the check, make sure to release the failure mode recall function.
27 Check of PLASMA AIR PURIFYING power G When PLASMA/W ASH lamp flashes 2-time. w w The power failure mode for PLASMA AIR PURIFYING power is memorized when the failure mode is called. PLASMA AIR PURIFYING operation Make sure that the front panel is firmly closed.
28 Check of auto front panel H Is the connector of the front panel driving motor unit or the indoor electric control P .C. board unplugged? Front panel is normal.
29 Electromagnetic noise enters into TV sets or radios I Replace the antennas. Replace the coaxial cable. No No No Yes Yes No No Yes Yes Yes Is the distance between the antennas and the indoor unit wi.
30 Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT1 1) T emperature ( : ) Resistance (k " ) MSZ-F A25V A - MSZ-F A35V A - Indoor electronic control P .C. board E1 E1 Release of Auto restart function Solder the Jumper wire to JR07.
31 DISASSEMBL Y INSTRUCTIONS 10 (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. 1 Slide the sleeve. 2 Pull the terminal while pushing the locking lever . 1 Hold the sleeve, and pull out the terminal slowly .
32 2. Removing the electronic control P .C. board, the power monitor receiver P .C. board, i-see Sensor , SW P .C. board and the terminal block (1) Remove the horizontal vane, the panel (Refer to 1.) and the corner box. (2) Remove the screw of the V .
33 OPERA TING PROCEDURE PHOTOS Photo 8 Photo 10 Screws of the left side of the heat exchanger 5. Removing the vertical vane motor unit (1) Remove the horizontal vane, the panel (Refer to 1.) and the corner box. (2) Pull out the drain hose from the nozzle assembly , and remove the nozzle assembly .
34 OPERA TING PROCEDURE PHOTOS Photo 13 Photo 1 1 Photo 12 Front panel driving motor Screw of the plasma element holder 7. Removing the plasma power P .C. board (1) Remove the horizontal vane, the panel (Refer to 1.) and the corner box. (2) Remove the switch holder and the electrical cover .
35 P ARTS LIST 1 1 MSZ-F A25V A - (WH) MSZ-F A35V A - (WH) 1 1-1. INDOOR UNIT STRUCTURAL P ARTS E1 E1 No. Part No. Part name Remarks Symbol in Wiring Diagram Q'ty/unit 1 2 3 4 5 6 7 8 MSZ-FA25VA .
36 1 1-3. INDOOR UNIT ELECTRICAL P ARTS AND FUNCTIONAL P ARTS MSZ-F A25V A - (WH) MSZ-F A35V A - (WH) E1 E1 4 2 5 3 9 SLEEVE BEARING ROOM TEMPERA TURE THERMISTOR FUSE V ARISTOR NR1 1 1 6 33 1 1-4. INDOOR UNIT HEA T EXCHANGER 10 8 7 18 1 1 12 13 POWER MONITOR RECEIVER P .
37 BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBL Y V ANE MOT OR UNIT (HORIZONT AL) INTERLOCK SWITCH(F AN) V ANE MOT OR UNIT (VERTICAL) HORIZONT AL V ANE FUSE V ARIST OR POWER MONITOR RECEIVER P .C. BOARD HOLDER i-see Sensor i-see Sensor MOTOR V A CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P .
38 12 OPTIONAL P ARTS DEODORIZING CERAMIC FIL TER Replacement of the deodorizing ceramic filter(about once every 6 years) Deodorizing ceramic filter is installed inside PLASMA DEODORIZING filter unit.
39 OB371_--2qxp 05.1.17 12:49 Page 39.
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, T OKYO100-8310, JAP AN C C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Jan. 2005. No. OB371 6 Made in Japan New publication, effective Jan. 2005 Specifications subject to change without notice.
An important point after buying a device Mitsubishi Electronics MSZ-FA35VA (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Mitsubishi Electronics MSZ-FA35VA yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Mitsubishi Electronics MSZ-FA35VA - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Mitsubishi Electronics MSZ-FA35VA you will learn all the available features of the product, as well as information on its operation. The information that you get Mitsubishi Electronics MSZ-FA35VA will certainly help you make a decision on the purchase.
If you already are a holder of Mitsubishi Electronics MSZ-FA35VA, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Mitsubishi Electronics MSZ-FA35VA.
However, one of the most important roles played by the user manual is to help in solving problems with Mitsubishi Electronics MSZ-FA35VA. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Mitsubishi Electronics MSZ-FA35VA along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center