THE FX SERIES OF PROGRAMMABLE CONTROLLER (FX0, FX 0S, FX 0N, FX, FX 2C, FX2N, FX 2NC)




FX Series Programmable Controllers
Programming Manual

FX Series Programmable Controllers

FX Series Programmable Controllers
Mitsubishi has a world wide reputation for its efforts in continually developing and pushing back the frontiers of industrial automation. What is sometimes overlooked by the user is the care and attention to detail that is taken with the documentation. However,to continue this process of improvement, the comments of the Mitsubishi users are always welcomed. This page has been designed for you,the reader,to fill in your comments and fax them back to us. We look for- ward to hearing from you.
Please tick the box of your choice;
Fax numbers: Your name
Mitsubishi Electric
America (01) 847-478-2253 Your company
Australia (02) 638-7072
Germany (0 21 02) 4 86-1 12 Your location:
South Africa (0111) 444-8304
United Kingdom (01707) 278-695
What condition did the manual arrive in? Good Minor damage Unusable
Will you be using a folder to store the manual? Yes No
What do you think to the manual presentation? Tidy Un-friendly
Are the explanations understandable? Yes Not too bad Unusable
Which explanation was most difficult to understand:
Are there any diagrams which are not clear? Yes No
If so,which:
What do you think to the manual layout? Good Not too bad Un-helpful
If there one thing you would like to see improved,what is it?
Could you find the information you required easily using the index and/or the contents,if possi- ble please identify your experience:
Do you have any comments in general about the Mitsubishi manuals?
Thank you for taking the time to fill out this questionnaire. We hope you found both the product and this manual easy to use.

FX Series Programmable Controllers

FX Series Programmable Controllers
Guidelines for the Safety of the User and Protection of the Programmable Controller (PLC)
This manual provides information for the use of the FX family of PLC’s. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows;
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated with this manual should be of a competent nature, trained and qualified to the local and national standards required to fulfill that role. These engineers should be fully aware of all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers should also be trained in the use and maintenance of the completed product. This includes being completely familiar with all associated documentation for the said product. All maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment should be trained to use that product in a safe
and coordinated manner in compliance to established safety practices. The operators should also be familiar with documentation which is connected with the actual operation of the completed equipment.
contains or uses the product associated with this manual.
At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment. Whenever any of the following symbols are encountered its associated note must be read and understood. Each of the symbols used will now be listed with a brief description of its meaning.

FX Series Programmable Controllers

FX Series Programmable Controllers
2. Basic Program Instructions 2-1 2.1 What is a Program? 2-1 2.2 Outline of Basic Devices Used in Programming 2-1 2.3 How to Read Ladder Logic 2-2 2.4 Load, Load Inverse 2-3 2.5 Out 2-4 2.5.1 Timer and Counter Variations 2-4 2.5.2 Double Coil Designation 2-5 2.6 And, And Inverse 2-6 2.7 Or, Or Inverse 2-7 2.8 Load Pulse, Load Trailing Pulse 2-8 2.9 And Pulse, And Trailing Pulse 2-9 2.10 Or Pulse, Or Trailing Pulse 2-10 2.11 Or Block 2-11 2.12 And Block 2-12 2.13 MPS, MRD and MPP 2-13 2.14 Master Control and Reset 2-15 2.15 Set and Reset 2-17 2.16 Timer, Counter (Out & Reset) 2-18 2.16.1 Basic Timers, Retentive Timers And Counters 2-18 2.16.2 Normal 32 bit Counters 2-19 2.16.3 High Speed Counters 2-19 2.17 Leading and Trailing Pulse 2-20 2.18 Inverse 2-21 2.19 No Operation 2-22 2.20 End 2-23

FX Series Programmable Controllers
3. STL Programming 3-1 3.1 What is STL, SFC And IEC1131 Part 3? 3-1 3.2 How STL Operates 3-2 3.2.1 Each step is a program 3-2 3.3 How To Start And End An STL Program 3-3 3.3.1 Embedded STL programs 3-3 3.3.2 Activating new states 3-3 3.3.3 Terminating an STL Program 3-4 3.4 Moving Between STL Steps 3-5 3.4.1 Using SET to drive an STL coil 3-5 3.4.2 Using OUT to drive an STL coil 3-6 3.5 Rules and Techniques For STL programs 3-7 3.5.1 Basic Notes On The Behavior Of STL programs 3-7 3.5.2 Single Signal Step Control 3-9 3.6 Restrictions Of Some Instructions When Used With STL 3-10 3.7 Using STL To Select The Most Appropriate Program 3-11 3.8 Using STL To Activate Multiple Flows Simultaneously 3-12 3.9 General Rules For Successful STL Branching 3-14 3.10 General Precautions When Using The FX-PCS/AT-EE Software 3-15 3.11 Programming Examples 3-16 3.11.1 A Simple STL Flow 3-16 3.11.2 A Selective Branch/ First State Merge Example Program 3-18 3.12 Advanced STL Use 3-20
4. Devices in Detail 4-1 4.1 Inputs 4-1 4.2 Outputs 4-2 4.3 Auxiliary Relays 4-3 4.3.1 General Stable State Auxiliary Relays 4-3 4.3.2 Battery Backed/ Latched Auxiliary Relays 4-4 4.3.3 Special Diagnostic Auxiliary Relays 4-5 4.3.4 Special Single Operation Pulse Relays 4-5 4.4 State Relays 4-6 4.4.1 General Stable State - State Relays 4-6 4.4.2 Battery Backed/ Latched State Relays 4-7 4.4.3 STL Step Relays 4-8 4.4.4 Annunciator Flags 4-9 4.5 Pointers 4-10 4.6 Interrupt Pointers 4-11 4.6.1 Input Interrupts 4-12 4.6.2 Timer Interrupts 4-12 4.6.3 Disabling Individual Interrupts 4-13 4.6.4 Counter Interrupts 4-13 4.7 Constant K 4-14 4.8 Constant H 4-14 4.9 Timers 4-15 4.9.1 General timer operation 4-16 4.9.2 Selectable Timers 4-16 4.9.3 Retentive Timers 4-17 4.9.4 Timers Used in Interrupt and ‘CALL’ Subroutines 4-18 4.9.5 Timer Accuracy 4-18 4.10 Counters 4-19 4.10.1 General/ Latched 16bit UP Counters 4-20 4.10.2 General/ Latched 32bit Bi-directional Counters 4-21

FX Series Programmable Controllers
4.11 High Speed Counters 4-22 4.11.1 Basic High Speed Counter Operation 4-23 4.11.2 Availability of High Speed Counters on FX0, FX0S and FX0N PLC’s 4-24 4.11.3 Availability of High Speed Counters on FX, FX2C PLC’s 4-25 4.11.4 Availability of High Speed Counters on FX2N(C) PLC’s 4-28 4.11.5 1 Phase Counters - User Start and Reset (C235 - C240) 4-29 4.11.6 1 Phase Counters - Assigned Start and Reset (C241 to C245) 4-30 4.11.7 2 Phase Bi-directional Counters (C246 to C250) 4-31 4.11.8 A/B Phase Counters (C252 to C255) 4-32 4.12 Data Registers 4-33 4.12.1 General Use Registers 4-34 4.12.2 Battery Backed/ Latched Registers 4-35 4.12.3 Special Diagnostic Registers 4-35 4.12.4 File Registers 4-36 4.12.5Externally Adjusted Registers 4-37 4.13 Index Registers 4-38 4.13.1 Modifying a Constant 4-39 4.13.2 Misuse of the Modifiers 4-39 4.13.3 Using Multiple Index Registers 4-39 4.14 Bits, Words, BCD and Hexadecimal 4-40 4.14.1 Bit Devices, Individual and Grouped 4-40 4.14.2 Word Devices 4-42 4.14.3 Interpreting Word Data 4-42 4.14.4 Two’s Compliment 4-45 4.15 Floating Point And Scientific Notation 4-46 4.15.1 Scientific Notation 4-47 4.15.2 Floating Point Format 4-48 4.15.3 Summary Of The Scientific Notation and Floating Point Numbers 4-49

FX Series Programmable Controllers
5. Applied Instructions 5-1 5.1 Program Flow-Functions00 to 09 5-4 5.1.1 CJ (FNC 00) 5-5 5.1.2 CALL (FNC 01) 5-7 5.1.3 SRET (FNC 02) 5-8 5.1.4 IRET, EI, DI (FNC 03, 04, 05) 5-9 5.1.5 FEND (FNC 06) 5-11 5.1.6 WDT (FNC 07) 5-12 5.1.7 FOR, NEXT (FNC 08, 09) 5-13 5.2 Move And Compare - Functions 10 to 19 5-16 5.2.1 CMP (FNC 10) 5-17 5.2.2 ZCP (FNC 11) 5-17 5.2.3 MOV (FNC 12) 5-18 5.2.4 SMOV (FNC 13) 5-18 5.2.5 CML (FNC 14) 5-19 5.2.6 BMOV (FNC 15) 5-20 5.2.7 FMOV (FNC 16) 5-21 5.2.8 XCH (FNC 17) 5-21 5.2.9 BCD (FNC18) 5-22 5.2.10 BIN (FNC 19) 5-22 5.3 Arithmetic And Logical Operations -Functions 20 to 29 5-24 5.3.1 ADD (FNC 20) 5-25 5.3.2 SUB (FNC 21) 5-26 5.3.3 MUL (FNC 22) 5-27 5.3.4 DIV (FNC 23) 5-28 5.3.5 INC (FNC 24) 5-29 5.3.6 DEC (FNC 24) 5-29 5.3.7 WAND (FNC 26) 5-30 5.3.8 WOR (FNC 27) 5-30 5.3.9 WXOR (FNC 28) 5-31 5.3.10NEG (FNC 29) 5-31 5.4 Rotation And Shift - Functions 30 to 39 5-34 5.4.1 ROR (FNC 30) 5-35 5.4.2 ROL (FNC 31) 5-35 5.4.3 RCR (FNC 32) 5-36 5.4.4 RCL (FNC 33) 5-36 5.4.5 SFTR (FNC 34) 5-37 5.4.6 SFTL (FNC 35) 5-37 5.4.7 WSFR (FNC 36) 5-38 5.4.8 WSFL (FNC 37) 5-38 5.4.9 SFWR (FNC 38) 5-39 5.4.10 SFRD (FNC 39) 5-40 5.5 Data Operation - Functions 40 to 49 5-42 5.5.1 ZRST (FNC 40) 5-43 5.5.2 DECO (FNC 41) 5-43 5.5.3 ENCO (FNC 42) 5-44 5.5.4 SUM (FNC 43) 5-45 5.5.5 BON (FNC 44) 5-45 5.5.6 MEAN (FNC 45) 5-46 5.5.7 ANS (FNC 46) 5-47 5.5.8 ANR (FNC 47) 5-47 5.5.9 SQR (FNC 48) 5-48 5.5.10 FLT (FNC 49) 5-49

FX Series Programmable Controllers
5.6 High Speed Processing - Functions 50 to 59 5-52 5.6.1 REF (FNC 50) 5-53 5.6.2 REFF (FNC 51) 5-53 5.6.3 MTR (FNC 52) 5-54 5.6.4 HSCS (FNC 53) 5-55 5.6.5 HSCR (FNC 54) 5-56 5.6.6 HSZ (FNC 55) 5-57 5.6.7 SPD (FNC 56) 5-60 5.6.8 PLSY (FNC 57) 5-61 5.6.9 PWM (FNC 58) 5-62 5.6.10 PLSR (FNC 59) 5-63 5.7 Handy Instructions - Functions 60 to 69 5-66 5.7.1 IST (FNC 60) 5-67 5.7.2 SER (FNC 61) 5-69 5.7.3 ABSD (FNC 62) 5-70 5.7.4 INCD (FNC 63) 5-71 5.7.5 TTMR (FNC 64) 5-72 5.7.6 STMR (FNC 65) 5-72 5.7.7 ALT (FNC 66) 5-73 5.7.8 RAMP (FNC 67) 5-73 5.7.9 ROTC (FNC 68) 5-75 5.7.10 SORT (FNC 69) 5-77 5.8 External FX I/O Devices - Functions 70 to 79 5-80 5.8.1 TKY (FNC 70) 5-81 5.8.2 HKY (FNC 71) 5-82 5.8.3 DSW (FNC 72) 5-83 5.8.4 SEGD (FNC 73) 5-84 5.8.5 SEGL (FNC 74) 5-85 5.8.6 ARWS (FNC 75) 5-87 5.8.7 ASC (FNC 76) 5-88 5.8.8 PR (FNC 77) 5-89 5.8.9 FROM (FNC 78) 5-90 5.8.10 TO (FNC 77) 5-91 5.9 External FX Serial Devices - Functions 80 to 89 5-94 5.9.1 RS (FNC 80) 5-96 5.9.2 RUN (FNC 81) 5-97 5.9.3 ASCI (FNC 82) 5-99 5.9.4 HEX (FNC 83) 5-100 5.9.5 CCD (FNC 84) 5-101 5.9.6 VRRD (FNC 85) 5-102 5.9.7 VRSD (FNC 86) 5-102 5.9.8 PID (FNC 88) 5-103 5.10 External F2 Units - Functions 90 to 99 5-111 5.10.1 MNET (FNC 90) 5-112 5.10.2 ANRD (FNC 91) 5-112 5.10.3 ANWR (FNC 92) 5-113 5.10.4 RMST (FNC 93) 5-113 5.10.5 RMMR (FNC 94) 5-114 5.10.6 RMRD (FNC 95) 5-115 5.10.7 RMMN (FNC 96) 5-115 5.10.8 BLK (FNC 97) 5-116 5.10.9 MCDE (FNC 98) 5-117

FX Series Programmable Controllers
5.11 Floating Point 1 & 2 - Functions 110 to 129 5-119 5.11.1 ECMP (FNC 110) 5-121 5.11.2 EZCP (FNC 111) 5-121 5.11.3 EBCD (FNC 118) 5-122 5.11.4 EBIN (FNC 119) 5-122 5.11.5 EADD (FNC 120) 5-123 5.11.6 EAUB (FNC 121) 5-124 5.11.7 EMUL (FNC 122) 5-124 5.11.8 EDIV (FNC 123) 5-125 5.11.9 ESQR (FNC 127) 5-125 5.11.10INT (FNC 129) 5-126 5.12 Trigonometry - FNC 130 to FNC 139 5-128 5.12.1 SIN (FNC 130) 5-129 5.12.2 COS (FNC 131) 5-130 5.12.3 TAN (FNC 132) 5-130 5.13 Data Operations 2 - FNC 140 to FNC 149 5-132 5.13.1 SWAP (FNC 147) 5-133 5.14 Real Time Clock Control - FNC 160 to FNC 169 5-136 5.14.1 TCMP (FNC 160) 5-137 5.14.2 TZCP (FNC 161) 5-138 5.14.3 TADD (FNC 162) 5-139 5.14.4 TSUB (FNC 163) 5-140 5.14.5 TRD (FNC 166) 5-141 5.14.6 TWR (FNC 167) 5-142 5.15 Gray Codes - FNC 170 to FNC 179 5-144 5.15.1 GRY (FNC 170) 5-145 5.15.2 GBIN (FNC 171) 5-145 5.16 Inline Comparisons - FNC 220 to FNC 249 5-148 5.16.1 LD compare (FNC 224 to 230) 5-149 5.16.2 AND compare (FNC 232 to 238) 5-150 5.16.3 OR compare (FNC 240 to 246) 5-151
6. Diagnostic Devices 6-1 6.1 PLC Status (M8000 to M8009 and D8000 to D8009) 6-2 6.2 Clock Devices (M8010 to M8019 and D8010 to D8019) 6-3 6.3 Operation Flags 6-4 6.4 PLC Operation Mode (M8030 to M8039 and D8030 to D8039) 6-5 6.5 Step Ladder (STL) Flags (M8040 to M8049 and D8040 to D8049) 6-6 6.6 Interrupt Control Flags (M8050 to M8059 and D8050 to D8059) 6-7 6.7 Error Detection Devices (M8060 to M8069 and D8060 to D6069) 6-8 6.8 Link And Special Operation Devices (M8070 to M8099 and D8070 to D8099) .. 6-9 6.9 Miscellaneous Devices (M8100 to M8119 and D8100 to D8119) 6-10 6.10 Communication Adapter Devices, i.e. 232ADP, 485ADP 6-10 6.11 High Speed Zone Compare Table Comparison Flags 6-11 6.12 Miscellaneous Devices (M8160 to M8199) 6-12 6.13 Index Registers (D8180 to D8199) 6-13 6.14 Up/Down Counter Control (M8200 to M8234 and M8200 to D8234) 6-14 6.15 High Speed Counter Control (M8235 to M8255 and D8235 to D8255) 6-14 6.16 Error Code Tables 6-15

FX Series Programmable Controllers
(CPU versions from 3.07) And FX2C (all versions) 8-6 8.5 Performance Specification Of The FX2N(C) 8-8
10.Points Of Technique 10-1 10.1 Advanced Programming Points 10-1 10.2 Users of DC Powered FX Units 10-1 10.3 Using The Forced RUN/STOP Flags 10-2 10.3.1 A RUN/STOP push button configuration 10-2 10.3.2 Remote RUN/STOP control 10-3 10.4 Constant Scan Mode 10-4 10.5 Alternating ON/OFF States 10-4 10.6 Using Battery Backed Devices For Maximum Advantage 10-5 10.7 Indexing Through Multiple Display Data Values 10-5 10.8 Reading And Manipulating Thumbwheel Data 10-6 10.9 Measuring a High Speed Pulse Input 10-6 10.9.1 A 1 msec timer pulse measurement 10-6 10.9.2 A 0.1 msec timer pulse measurement 10-7 10.10Using The Execution Complete Flag, M8029 10-7 10.11Creating a User Defined MTR Instruction 10-8 10.12An Example System Application Using STL And IST Program Control 10-8 10.13Using The PWM Instruction For Motor Control 10-15 10.14Communication Format 10-18 10.14.1Specification of the communication parameters: 10-18 10.14.2Header and Terminator Characters 10-19 10.14.3Timing diagrams for communications: 10-20 10.14.48 bit or 16 bit communications 10-23

FX Series Programmable Controllers
10.15PID Programming Techniques 10-24 10.15.1Keeping MV within a set range 10-24 10.15.2Manual/Automatic change over 10-24 10.15.3Using the PID alarm signals 10-25 10.15.4Other tips for PID programming 10-25 10.16Additional PID functions 10-26 10.16.1Output Value range control (S3+1 b5) 10-26 10.17Pre-tuning operation 10-27 10.17.1Variable Constants 10-27 10.18Example Autotuning Program 10-28
11.Index 11-1 11.1 Index 11-1 11.2 ASCII Character Codes 11-9 11.3 Applied Instruction List 11-10

FX Series Programmable Controllers Introduction 1
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Introduction 1

Shaded boxes indicate the applicable PLC type
- “FX0(S)” - All FX0 and FX0S PLCs
- “FX0N” - All FX0N PLCs
- “FX” - All FX and FX2 PLCs (CPU ver 2.30 or earlier)
- “FX(2C)” - All FX and FX2 PLCs (CPU versions 3.07 or later)
- - All FX2C PLCs (see page 1-4)
- “FX2N(C)” - All FX2N and FX2NC PLCs
If an indicator box is half shaded, as shown to the left, this means that not all the functions described in the current section apply to that PLC. The text explains in further detail or makes an independent reference. If there are no indicator boxes then assume the section applies to all PLC types unless otherwise stated.
- Please refer to section 1.4 for details about version numbers and capabilities.
- Please refer to section 1.5 for details about peripheral support for each model.
Introduction 1

A Programmable Logic Controller (PLC or programmable controller) is a device that a user can program to perform a series or sequence of events. These events are triggered by stimuli (usually called inputs) received at the PLC or through delayed actions such as time delays or counted occur-rences. Once an event triggers, it actuates in the outside world by switching ON or OFF electronic control gear or the physical actuation of devices. A programmable controller will continually ‘loop’ through its internal ‘user defined’ program waiting for inputs and giving outputs at the programmed specific times.
The term programmable controller is a generic word used to bring all the elements making the control system under one descriptive name. Sometimes engineers use the term ‘Programmable Logic Controller’, ‘PLC’ or ‘programmable controller’ to describe the same control system. The construction of a programmable controller can be broken down into component parts. The element where the program is loaded, stored and processed is often known as the Main Processing Unit or MPU. Other terms commonly heard to describe this device are ‘base unit’, ‘controller’ and ‘CPU’. The term CPU is a little misleading as todays more advanced products may contain local CPU devices. A Main CPU (or more correctly a Main Processing Unit) controls these local CPUs through a communication network or bus.
A variety of tools are available to program the Mitsubishi FX family of PLCs. Each of these tools can use and access the instructions and devices listed in this manual for the identified PLC.

Introduction 1

Over time Mitsubishi adds newer and better features to develop and enhance the products. Because of the nature of PLCs, that can be likened to ‘industrial computers’, changes sometimes occur within the units main CPU (Central Processing Unit). These changes are similar to those experienced by office and home computer users, that is, going to a version up processor. The following lists identify the CPU versions that had significant upgrades or new functions and features added.
CPU Ver 1.20 The following features were added: Software control for protocol 1 and 4 communications with the FX0N-485ADP, 1:N network.
CPU Ver 1.40 The following features were added: Software control for communications using the FX0N-485ADP, peer to peer (N:N) network.
CPU Ver 3.07 The following instructions were added: ASCI (FNC82), CCD (FNC84), FLT (FNC49), HEX (FNC83), RS (FNC80), SER (FNC61), SORT (FNC69), SQR (FNC48)
The following instructions were upgraded: EI (FNC04), BMOV (FNC15), HSCS (FNC53), PLSY (FNC57), FMOV (FNC16), MEAN (FNC45), ABSD (FNC62), DSW (FNC72),SEGL (74), PR (FNC 77)
The following device ranges were added: Input and output devices are independently addressable upto 256 points in software. Total combined input and output points (hardware or software) is 256.
Auxiliary relays increased to 1536 points (M0-M1535) Data registers increased to 1000 points (D0-D999) Optional RAM File Registers added, 2000 points (D6000 -D7999) Pointers increased to 128 points (P0 - P127)
CPU Ver 3.11 The following instructions were added: PID (FNC88)
CPU Ver 3.2 The following features were added: Software control for protocol 4 communications with the FX-485ADP, 1:N network.
CPU Ver 3.30 The following features were added: Software control for protocol 1 communications with the FX-485ADP, 1:N network.
The following instructions were phased out (removed): ANRD (FNC91), ANWR (FNC92), BLK (FNC97), MCDE (FNC98), MNET (FNC90)
Introduction 1

1.5.1 FX CPU version 3.07 or later and FX 2C
Programming tools operating old system software can not access the new features added to
the FX CPU from version 3.07 (and available on all FX2C units). However, programming certain ‘standard’ applied instructions in conjunction with special auxiliary coils (M coils) can achieve the same ’effective instruction’ as the new instructions. The following tables identify which version of peripheral software will work directly with all of the ’new’ features and which peripheral software versions require use of modified instructions.
System software version which will
require the use of
program all instructions
Hand held programmer (HHP) FX-10P-E V 1.10 from V 2.00
HHP cassette FX-20P-MFXA-E V 1.20 from V 2.00
FX-PCS/AT-E-KIT V 1.01 from V 2.00
FX-A6GPP-E-KIT V 1.00 from V 2.00
FX-10DU-E V 1.10 from V 2.00
FX-20DU-E V 1.10 from V 2.00
Other DU units from V 1.00
Existing Instruction And Special M Coil Combination To Mimic The Operation Of The
Existing FX instruction used to mimic the operation of
Mnemonic FNC number Modifying M coil Mimicked instruction Mnemonic FNC Number
MOV 12 M8190 Square root SQR 48
MOV 12 M8191 Float FLT 49
RAMP 67 M8193 Data search SER 61
RAMP 67 M8194 RS232 instruction RS 80
FMOV 16 M8196 Hex to ASCII conversion ASCI 82
FMOV 16 M8197 ASCII to Hex conversion HEX 83
FMOV 16 M8195 Sum check CCD 84
This format is very important for the instruction to operate correctly.The user must program the ’mimic’ instruction with the modifying M coil in a SET instruction immediately before the instruction to be modified.
Using existing FX functions
MOV
D10 K36
to mimic

Using the new Interrupt Pointers:
Existing Instruction And Special M Coil
To program new Interrupt Pointers I010 through I060 in to the HSCS (FNC 53) instruction with older programming equipment, substitute the following special M codes for the appropriate Interrupt Pointer; see the table right.
Combination To Mimic The Operation
Of The Identified Interrupt pointer
Existing Auxiliary Coil used to replace the identi-
M8182 I020
M8183 I030
M8184 I040
M8185 I050
M8186 I060
Using M8198 with the BMOV instruction:
With old software and peripherals, file registers can not be used as a destination device in the BMOV (FNC 15) instruction. To BMOV data into file registers with old equipment set special M coil M8198 on. This switches the source and destination parameters; i.e., the source is then treated as the destination and the destination becomes the source.
General note:
Ignore the special programming techniques identified in this section if using updated programming software or peripherals; then normal operation, as identifiedin the following sections, will apply.
The introduction of this CPU provides the FX user with many new devices and instructions. To use the full features of the FX2N(C) units the user must upgrade older software and hardware programming tools. However, because of the downward compatibility of the FX2N(C), it is not necessary to upgrade existing programming tools for use with FX2N(C) units up to the equivalent functionality of FX CPU ver 3.30 units.
Description Model Number System software version with
full support for FX2N(c)
Hand held programmer (HHP) FX-10P-E from V 3.00
HHP cassette FX-20P-MFXA-E from V 3.00
FX-10DU-E from V 4.00
FX-20DU-E Supports up to FX devices only
FX-25DU-E from V 2.00
FX-30DU-E from V 3.00
FX-40DU-E(S) Supports up to FX devices only
FX-40DU-TK-ES from V 3.00
FX-50DU-TK(S)-E from V 2.10

Introduction 1

FX Series Programmable Controllers Basic Program Instructions 2
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Basic Program Instructions 2
2. Basic Program Instructions 2-1 2.1 What is a Program? 2-1 2.2 Outline of Basic Devices Used in Programming 2-1 2.3 How to Read Ladder Logic 2-2 2.4 Load, Load Inverse 2-3 2.5 Out 2-4 2.5.1 Timer and Counter Variations 2-4 2.5.2 Double Coil Designation 2-5 2.6 And, And Inverse 2-6 2.7 Or, Or Inverse 2-7 2.8 Load Pulse, Load Trailing Pulse 2-8 2.9 And Pulse, And Trailing Pulse 2-9 2.10 Or Pulse, Or Trailing Pulse 2-10 2.11 Or Block 2-11 2.12 And Block 2-12 2.13 MPS, MRD and MPP 2-13 2.14 Master Control and Reset 2-15 2.15 Set and Reset 2-17 2.16 Timer, Counter(Out & Reset) 2-18 2.16.1 Basic Timers, Retentive Timers And Counters 2-18 2.16.2 Normal 32 bit Counters 2-19 2.16.3 High Speed Counters 2-19 2.17 Leading and Trailing Pulse 2-20 2.18 Inverse 2-21 2.19 No Operation 2-22 2.20 End 2-23

FX Series Programmable Controllers
Basic Program Instructions 2
A program is a connected series of instructions written in a language that the PLC can understand. There are three forms of program format; instruction, ladder and SFC/STL. Not all programming tools can work in all programming forms. Generally hand held programming panels only work with instruction format while most graphic programming tools will work with both instruction and ladder format. Specialist programming software will also allow SFC style programming.
X10 Y7 M38 S5 X21 T01 K40
Instruction format Ladder Format SFC Format
There are six basic programming devices. Each device has its own unique use. To enable quick and easy identification each device is assigned a single reference letter;
- X: This is used to identify all direct, physical inputs to the PLC.
- Y: This is used to identify all direct, physical outputs from the PLC.
- T: This is used to identify a timing device which is contained within the PLC.
- C: This is used to identify a counting device which is contained within the PLC.
- M and S: These are used as internal operation flags within the PLC.
All of the devices mentioned above are known as ‘bit devices’. This is a descriptive title telling the user that these devices only have two states; ON or OFF, 1 or 0.

FX Series Programmable Controllers Basic Program Instructions 2
Ladder logic is very closely associated to basic relay logic. There are both contacts and coils that can be loaded and driven in different configurations. However, the basic principle remains the same.
A coil drives direct outputs of the PLC (ex. a Y device) or drives internal timers, counters or flags (ex. T, C, M and S devices). Each coil has associated contacts. These contacts are available in both “normally open” (NO) and “normally closed” (NC) configurations.
The term “normal(ly)” refers to the status of the contacts when the coil is not energized. Using a relay analogy, when the coil is OFF, a NO contact would have no current flow, that is, a load being supplied through a NO contact would not operate. However, a NC contact would allow current to flow, hence the connected load would be active.
Activating the coil reverses the contact status, that is, the current would flow in a NO contact and a NC contact would inhibit the flow.
Physical inputs to the PLC (X devices) have no programmable coil. These devices may only be used in a contact format (NO and NC types are available).
Because of the close relay association, ladder logic programs can be read as current flowing from the left vertical line to the right vertical line. This current must pass through a series of contact representations such as X0 and X1 in order to switch the output coil Y0 ON. Therefore, in the example shown, switching X0 ON causes the output Y0 to also switch ON. If however, the limit switch X1 is activates, the output Y0 turns OFF. This is because the connection between the left and the right vertical lines breaks so there is no current flow.
O U
PC Program I N
P U
Y0
T
COM (Y0)
T

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Initial logical operation contact type NO (normally open)
Initial logical operation contact type NC (normally closed)
Program example:
0 1 2 3 4
X Y X M T K T Y
0 0 1 100 0 19 0 1
M100
T0
K19 LDI
K
When using hand held programmers, the space key needs to be pressed to enable the constant to be entered.
Y1
Basic points to remember:
- Connect the LD and LDI instructions directly to the left hand bus bar.
- Or use LD and LDI instructions to define a new block of program when using the ORB and ANB instructions (see later sections).
LD (LoaD) · LDI (LoaD Inverse)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Y, M:1 S, special M coils: 2 T:3 C (16 bit): 3 C (32 bit): 5
Final logical operation type coil drive
Y, M, S, T, C
Basic points to remember:
- Connect the OUT instruction directly to the right hand bus bar.
- It is not possible to use the OUT instruction to drive ‘X’ type input devices.
- It is possible to connect multiple OUT instructions in parallel (for example see the previous page; M100/T0 configuration)
When configuring the OUT instruction for use as either a timer (T) or counter (C) a constant must also be entered. The constant is identified by the letter “K” (for example see previous page; T0 K19). In the case of a timer, the constant “K” holds the duration data for the timer to operate, i.e. if a 100 msec timer has a constant of “K100” it will be (1005 100 msec) 10 seconds before the timer coil activates. With counters, the constant identifies how many times the counter must be pulsed or triggered before the counter coil activates. For example, a counter with a constant of “8” must be triggered 8 times before the counter coil finally energizes. The following table identifies some basic parameter data for various timers and counters;
Timer/Counter Setting constant K Actual setting Program steps
0.001 to 32.767 sec
3 10 msec Timer 0.01 to 327.67 sec
100 msec Timer 0.1 to 3276.7 sec
16 bit Counter 1 to 32,767 1 to 32,767
32 bit Counter -2,147,483,648 to 2,147,483,647 -2,147,483,648 to 2,147,483,647 5
1 msec Timer · 1 to 32,767

FX Series Programmable Controllers Basic Program Instructions 2

Double or dual coiling is not a recommended practice. Using multiple output coils of the same device can cause the program operation to become unreliable. The example program shown opposite identifies a double coil situation; there are two Y3 outputs. The following sequence of events will occur when inputs X1 = ON and X2 = OFF;
1.The first Y3 tuns ON because X1 is ON. The contacts associated with Y3 also energize when the coil of output Y3 energizes. Hence, output Y4 turns ON.
2.The last and most important line in this program looks at the status of input X2.
If this is NOT ON then the second Y3 coil does NOT activate. Therefore the status of the Y3 coil updates to reflect this new situation, i.e. it turns OFF. The final outputs are then Y3 = OFF and Y4 = ON.
Input durations:

The ON or OFF duration of the PLC inputs must be longer than the operation cycle time of the PLC. Taking a 10 msec (standard input filter) response delay into account, the ON/OFF duration must be longer than 20 msec if the operation cycle (scan time) is 10 msec.
Therefore, in this example, input pulses of more than 25Hz (1sec/(20msec ON + 20msec OFF)) cannot be sensed. There are applied instructions provided to handle such high speed input requests.
: Input ON state NOT recognized : Input ON state recognized : Input OFF state NOT recognized : 1 program processing : Input processing : Output processing : A full program scan/operation cycle

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Serial connection of NO (normally open) contacts
X, Y, M, S, T, C 1
Serial connection of NC (normally closed) contacts
Program example:
0 1 2 3 4
X X Y Y X M T Y
2 0 3 3 3 101 1 4
Y3
M101
OUT AND
T1 ANI
OUT
Y4
AND
Basic points to remember:
- Use the AND and ANI instructions for serial connection of contacts. As many contacts as required can be connected in series (see following point headed “Peripheral limitations”).
- The output processing to a coil, through a contact, after writing the initial OUT instruction is called a “follow-on” output (for an example see the program above; OUT Y4). Follow- on outputs are permitted repeatedly as long as the output order is correct.
ANI (AND Inverse)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Parallel connection of NO (normally open) contacts
X, Y, M, S, T, C 1
Parallel connection of NC (normally closed) contacts
Program example:
0 1 2 3 4
X X M Y Y X M X M M
4 6 102 5 5
OR
M102
ORI
AND OR
ANI
Y5 X7 X10
8 9 OR OUT
M103
M103
M110
Basic points to remember:
- Use the OR and ORI instructions for parallel connection of contacts. To connect a block that contains more than one contact connected in series to another circuit block in parallel, use an ORB instruction.
- Connect one side of the OR/ORI instruction to the left hand bus bar.
ORI (OR Inverse) · 110 103

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Initial logical operation - Rising edge pulse
Initial logical operation Falling / trailing edge pulse
LDF (LoaD Falling pulse)
Program example:
M100
0 LDP X 0 2 OR X 1 3 OUT M 100 4 LDF X 0 6 OUT Y 0
Y0
Basic points to remember:
- Connect the LDP and LDF instructions directly to the left hand bus bar.
- Or use LDP and LDF instructions to define a new block of program when using the ORB and ANB instructions (see later sections).
- LDP is active for one program scan after the associated device switches from OFF to ON.
- LDF is active for one program scan after the associated device switches from ON to OFF.
For more details please see page 4-5.
LDP (LoaDPulse)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Serial connection of Rising edge pulse
Serial connection of Falling / trailing edge pulse
ANF (ANd Falling pulse)
Program example:
ANP
M40
T10
0 LD M 40 1 OR X 1 2 ANP T 10 4 OUT M 100 5 LDF X 0 6 ANF C 0 8 OUT Y 4
ANF
Y4
Basic points to remember:
- Use the ANDP and ANDF instructions for the serial connection of pulse contacts.
- Usage is the same as for AND and ANI; see earlier.
- ANP is active for one program scan after the associated device switches from OFF to ON.
- ANF is active for one program scan after the associated device switches from ON to OFF.
ANP (ANd Pulse)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Parallel connection of Rising edge pulse
Parallel connection of Falling / trailing edge pulse
ORF (OR Falling pulse)
Program example:
M40
SET M50
0 LD M 40 1 ORP X 1 3 SET M 50 4 LD X 0 5 AND M 24 6 LD Y 7 7 ORF X 1 9 ORB 10 OUT Y 4
M24
Y4
X1 Y7
ORF
Basic points to remember:
- Use the ORP and ORF instructions for the parallel connection of pulse contacts.
- Usage is the same as for OR and ORI; see earlier.
- ORP is active for one program scan after the associated device switches from OFF to ON.
- ORF is active for one program scan after the associated device switches from ON to OFF.
ORP (OR Pulse)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Parallel connection of multiple contact circuits
Program example:
Recommended sequential programming method
Non-preferred batch programming method
0 1 2 3 4
X X X X
0 1 2 3
0 1 2 3 4
X X X X
0 1 2 3
ORB
LDI AND
AND ORB
ORB
ORB
ORB
8 OUT
Y
8 OUT
Y 6
Basic points to remember:
- An ORB instruction is an independent instruction and is not associated with any device number.
- Use the ORB instruction to connect multi-contact circuits (usually serial circuit blocks) to the preceding circuit in parallel. Serial circuit blocks are those in which more than one contact connects in series or the ANB instruction is used.
- To declare the starting point of the circuit block use a LD or LDI instruction. After completing the serial circuit block, connect it to the preceding block in parallel using the ORB instruction.
ORB (OR Block)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Serial connection of multiple parallel circuits
Program example:
ANB LD
Recommended sequential programming method
0 1 2 3 4
X X X X X X
0 1 2 3 4
ORB
AND ORB
OR
8 ANB
9 10 OR OUT
X Y
Basic points to remember:
- An ANB instruction is an independent instruction and is not associated with any device number
- Use the ANB instruction to connect multi-contact circuits (usually parallel circuit blocks) to the preceding circuit in series. Parallel circuit blocks are those in which more than one contact connects in parallel or the ORB instruction is used.
- To declare the starting point of the circuit block, use a LD or LDI instruction. After completing the parallel circuit block, connect it to the preceding block in series using the ANB instruction.
ANB (ANd Block)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Stores the current result of the internal PLC operations
MPS
Reads the current result of the internal PLC operations
MRD
Pops (recalls and removes) the currently stored result
MPP
Basic points to remember:
- Use these instructions to connect output coils to the left hand side of a contact. Without these instructions connections can only be made to the right hand side of the last contact.
- MPS stores the connection point of the ladder circuit so that further coil branches can recall the value later.
- MRD recalls or reads the previously stored connection point data and forces the next contact to connect to it.
- MPP pops (recalls and removes) the stored connection point. First, it connects the next contact, then it removes the point from the temporary storage area.
- For every MPS instruction there MUST be a corresponding MPP instruction.
- The last contact or coil circuit must connect to an MPP instruction.
- At any programming step, the number of active MPS-MPP pairs must be no greater than 11.
MPS (Point Store) · MRD (Read) · MPP (PoP)

FX Series Programmable Controllers Basic Program Instructions 2

OUT MPP OUT MPP OUT MPP OUT MPP 17 OUT

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Y, M (no special M coils allowed) N denotes the nest level (N0 to N7)
Denotes the start of a master control block
MCR (Master Control Reset)
N denotes the nest level (N0 to N7) to be reset.
Denotes the end of a master control block
M100 N0 MC
M100 N0 X N M X Y X Y N
0 0 100 1 0 2 1 0
LD OUT
Y1
MCR
Basic points to remember:
- After the execution of an MC instruction, the bus line (LD, LDI point) shifts to a point after the MC instruction. An MCR instruction returns this to the original bus line.
- The MC instruction also includes a nest level pointer N. Nest levels are from the range N0 to N7 (8 points). The top nest level is ‘0’ and the deepest is ‘7’.
- The MCR instruction resets each nest level. When a nest level is reset, it also resets ALL deeper nest levels. For example, MCR N5 resets nest levels 5 to 7.
- When input X0=ON, all instructions between the MC and the MCR instruction execute.
- When input X0=OFF, none of the instruction between the MC and MCR instruction execute; this resets all devices except for retentive timers, counters and devices driven by SET/RST instructions.
- The MC instruction can be used as many times as necessary, by changing the device number Y and M. Using the same device number twice is processed as a double coil (see section 2.5.2). Nest levels can be duplicated but when the nest level resets, ALL occurrences of that level reset and not just the one specified in the local MC.
MC (Master Control)

FX Series Programmable Controllers Basic Program Instructions 2
A
M100 N0 MC
Level N0: Bus line (B) active when X0 is ON.
Y0
B
M101 N1 MC
Level N1: Bus line (C) active when both X0 and X2 are ON.
Y1
M102 N2 MC
Level N2: Bus line (D) active when X0,X2 and X4 are ON.
Y2
D
MCR
N2
Level N1: MCRN2 executes and restores bus line (C). If the MCR had reset N0 then the original bus bar (A) would now be active as all master controls below nest level 0 would reset.
MCR
N1
Level N0: MCRN1 executes and restores bus line (B).
B
MCR
N0
Initial state: MCR N0 executes and restores the initial bus line (A).
Output Y5 turns ON/OFF according to the ON/OFF state of X10, regardless of the ON/OFF status of inputs X0, X2 or X4.

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Y,M:1 S, special M coils:2
Sets a bit device permanently ON Y, M, S
Y, M, S, D, V, Z (see section 2.16 for timers and counters T,C)
Resets a bit device permanently OFF
D, special D registers, V and Z:3
LD SET LD RST LD
X Y X Y X M X M
SET Y0
RST Y0
0 2 0 3 0
SET LD
RST
RST M0
8 9 10 11 12
X S X S X D
4 0 5 0 6 0
RST S0
RST D0
Basic points to remember:
- Turning ON X0 causes Y0 to turn ON. Y0 remains ON even after X0 turns OFF.
- Turning ON X1 causes Y0 to turn OFF. Y0 remains OFF even after X1 turns OFF.
- SET and RST instructions can be used for the same device as many times as necessary. However, the last instruction activated determines the current status.
- It is also possible to use the RST instruction to reset the contents of data devices such as data registers, index registers etc. The effect is similar to moving ‘K0’ into the data device.
RST (ReSeT)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
32 bit counters:5 Others: 3
Driving timer or counter coils T, C
T, C (see section 2.15 for other resetable devices)
Resets timer and counter, coils contacts and current values
Program example:
2.16.1Basic Timers, Retentive Timers And Counters
RST T246
These devices can all be reset at any time by driving the RST instruction (with the number of the device to be reset). On resetting, all active contacts, coils and current value registers are reset for the selected device. In the example, T246, a 1msec retentive timer, is activate while X1 is ON. When the current value of T246 reaches the preset ‘K’ value, i.e. 1234, the timer coil for T246 will be activated. This drives the NO contact ON. Hence, Y0 is switched ON. Turning ON X0 will reset timer T246 in the manner described previously. Because the T246 contacts are reset, the output Y0 will be turned OFF.
K1234
T246
Y0
M8200
RST
D0
Y1
Retentive timers:
RST (ReSeT)

FX Series Programmable Controllers Basic Program Instructions 2
The 32 bit counter C200 counts (up-count, down-count) according to the ON/OFF state of M8200. In the example program shown on the previous page C200 is being used to count the number of OFF ~ ON cycles of input X4. The output contact is set or reset depending on the direction of the count, upon reaching a value equal (in this example) to the contents of data registers D1,D0 (32 bit setting data is required for a 32 bit counter). The output contact is reset and the current value of the counter is reset to ‘0’ when input X3 is turned ON.
High speed counters have selectable count directions. The directions are selected by driving the appropriate special auxiliary M coil. The example shown to the right works in the following manner; when X10 is ON, counting down takes place. When X10 is OFF counting up takes place. In the example the output contacts of counter C∆∆∆ and its associated current count values are reset to “0” when X11 is turned ON. When X12 is turned ON the driven counter is enabled. This means it will be able to start counting its assigned input signal (this will not be X12 - high speed counters are assigned special input signals, please see page 4-22).
RST
K/D
Y2
Availability of devices:

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Y, M (no special M coils allowed)
Y, M (no special M coils allowed)
Falling / trailing edge pulse
LD PLS LD SET LD
X M
PLS M0
M0
M Y X
SET Y0
0 1 1 1 0
PLF LD
M M Y
M1
RST Y0
RST
Basic points to remember:
- When a PLS instruction is executed, object devices Y and M operate for one operation cycle after the drive input signal has turned ON.
- When a PLF instruction is executed, object devices Y and M operate for one operation cycle after the drive input signal has turned OFF.
Y0
- When the PLC status is changed from RUN to STOP and back to RUN with the input signals still ON, PLS M0 is operated again. However, if an M coil which is battery backed (latched) was used instead of M0 it would not re-activate. For the battery backed device to be re-pulsed, its driving input (ex. X0) must be switched OFF during the RUN/STOP/RUN sequence before it will be pulsed once more.

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Invert the current result of the internal PLC operations
Program example:
PLS M0
LD PLS LD SET LD
X M
M0
M Y X
SET Y0
0 1 1 1 0
PLF LD
M M Y
M1
RST Y0
RST
Basic points to remember:
- The INV instruction is used to change (invert) the logical state of the current ladder network at the inserted position.
- Usage is the same as for AND and ANI; see earlier.
INV (Inverse)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
No operation or null step N/A N/A 1
Basic points to remember:
- Writing NOP instructions in the middle of a program minimizes step number changes when changing or editing a program.
- It is possible to change the operation of a circuit by replacing programmed instructions with NOP instructions.
- Changing a LD, LDI, ANB or an ORB instruction with a NOP instruction will change the circuit considerably; quite possibly resulting in an error being generated.
- After the program ‘all clear operation’ is executed, all of the instructions currently in the program are over written with NOP’s.
NOP (No Operation)

FX Series Programmable Controllers Basic Program Instructions 2
Mnemonic Function Format Devices Program steps
Forces the current program scan to end
END
N/A 1
Basic points to remember:
- Placing an END instruction in a program forces that program to end the current scan and carry out the updating processes for both inputs and outputs.
- Inserting END instructions in the middle of the program helps program debugging as the section after the END instruction is disabled and isolated from the area that is being checked. Remember to delete the END instructions from the blocks which have already been checked.
- When the END instruction is processed the PCs watchdog timer is automatically refreshed.

FX Series Programmable Controllers Basic Program Instructions 2

FX Series Programmable Controllers STL Programming 3
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers STL Programming 3
3. STL Programming 3-1 3.1 What is STL, SFC And IEC1131 Part 3? 3-1 3.2 How STL Operates 3-2 3.2.1 Each step is a program 3-2 3.3 How To Start And End An STL Program 3-3 3.3.1 Embedded STL programs 3-3 3.3.2 Activating new states 3-3 3.3.3 Terminating an STL Program 3-4 3.4 Moving Between STL Steps 3-5 3.4.1 Using SET to drive an STL coil 3-5 3.4.2 Using OUT to drive an STL coil 3-6 3.5 Rules and Techniques For STL programs 3-7 3.5.1 Basic Notes On The Behavior Of STL programs 3-7 3.5.2 Single Signal Step Control 3-9 3.6 Restrictions Of Some Instructions When Used With STL 3-10 3.7 Using STL To Select The Most Appropriate Program 3-11 3.8 Using STL To Activate Multiple Flows Simultaneously 3-12 3.9 General Rules For Successful STL Branching 3-14 3.10 General Precautions When Using The FX-PCS/AT-EE Software 3-15 3.11 Programming Examples 3-16 3.11.1 A Simple STL Flow 3-16 3.11.2 A Selective Branch/ First State Merge Example Program 3-18 3.12 Advanced STL Use 3-20

FX Series Programmable Controllers
This chapter differs from the rest of the contents in this manual as it has been written with a training aspect in mind. STL/SFC programming, although having been available for many years, is still misunderstood and misrepresented. We at Mitsubishi would like to take this opportunity to try to correct this oversight as we see STL/SFC programming becoming as important as ladder style programming.
The following explanation is very brief but is designed to quickly outline the differences and similarities between STL, SFC and IEC1131 part 3. In recent years Sequential Function Chart (or SFC) style programming (including other similar styles such as Grafcet and Funktionplan) have become very popular through out Europe and have prompted the creation of IEC1131 part 3. The IEC1131 SFC standard has been designed to become an interchangeable programming language. The idea being that a program written to IEC1131 SFC standards on one manufacturers PLC can be easily transferred (converted) for use on a second manufacturers PLC. STL programming is one of the basic programming instructions included in all FX PLC family members. The abbreviation STL actually means STep Ladder programming. STL programming is a very simple concept to understand yet can provide the user with one of the most powerful programming techniques possible. The key to STL lies in its ability to allow the programmer to create an operational program which ‘flows’ and works in almost exactly the same manner as SFC. This is not a coincidence as this programming technique has been developed deliberately to achieve an easy to program and monitor system. One of the key differences to Mitsubishi’s STL programming system is that it can be entered into a PLC in 3 formats. These are:
Ι) Instruction - a word/mnemonic entry system
ΙΙ) Ladder - a graphical program construction method using a relay logic symbols
ΙΙΙ) SFC - a flow chart style of STL program entry (similar to SFC)
Examples of these programming methods can be seen on page 2-1.
STL Programming 3

FX Series Programmable Controllers STL Programming 3
As previously mentioned, STL is a system which allows the user to write a program which functions in much the same way as a flow chart, this can be seen in the diagram opposite. STL derives its strength by organizing a larger program into smaller more manageable parts. Each of these parts can be referred to as either a state or a step. To help identify the states, each is given a unique identification number. These numbers are taken from the state relay devices (see page 4-6 for more details).
S 0
S 22
S 26
T0
S 27
T7
3.2.1 Each step is a program
Each state is completely isolated from all other states within the whole program. A good way to envisage this, is that each state is a separate program and the user puts each of those programs together in the order that they require to perform their task. Immediately this means that states can be reused many times and in different orders. This saves on programming time AND cuts down on the number of programming errors encountered.
On initial inspection the STL program looks as if it is a rather basic flow diagram. But to find out what is really happening the STL state needs to be put ‘under a microscope’ so to speak. When a single state is examined in more detail, the sub-program can be viewed.
With the exception of the STL instruction, it will be immediately seen that the STL sub-program looks just like ordinary programming.
The STL instruction is shown as a ‘fat’ normally
open contact. All programming after an STL instruction is only active when the associated state coil is active.
The transition condition is also written using
standard programming.
S 22
K20
This idea re-enforces the concept that STL is really a method of sequencing a series of events or as mentioned earlier ‘of joining lots of smaller programs together’.
SET S 27 T0

FX Series Programmable Controllers STL Programming 3
Sometimes STL programs will be written in hard copy as a combination of both flow diagram and internal sub-program. (example shown below). Identification of contact states
is used:
Y20
Normally Open contact Normally Closed contact
Common alternatives are ‘a’ and ‘b’ identifiers for Normally Open, Normally Closed states or often a line drawn over the top of the Normally Closed contact name is used, e.g. X000.
Y22
S 26
Y26
T0
K20
T0
S 27
Y27
T7
T7
K20
3.3 How To Start And End An STL Program
Before any complex programming can be undertaken the basics of how to start and more importantly how to finish an STL program need to be examined.
An STL style program does not have to entirely replace a standard ladder logic program. In fact it might be very difficult to do so. Instead small or even large section of STL program can be entered at any point in a program. Once the STL task has been completed the program must go back to processing standard program instructions until the next STL program block. Therefore, identifying the start and end of an STL program is very important.
LD OUT LD SET STL OUT LDI OUT RET LD OUT RST
X005 Y007 M080
3.3.2 Activating new states
Once an STL step has been selected, how is it used and how is the program ‘driven’? This is not so difficult, if it is considered that for an STL step to be active its associated state coil must be ON. Hence, to start an STL sequence all that has to be done is to drive the relevant state ON.
There are many different methods to drive a state, for example the initial state coils could be pulsed, SET or just included in an OUT instruction. However, within Mitsubishi’s STL programming language an STL coil which is SET has a different meaning than one that is included in an OUT instruction.
Y22
S 22
K20
T0
SET S 27 T0
STL
S 27
Normal Ladder Program · Embedded STL Program

FX Series Programmable Controllers STL Programming 3
For an STL program which is to be activated on the initial power up of the PLC, a trigger similar to that shown opposite could be used, i.e. using M8002 to drive the setting of the initial state. The STL step started in this manner is often referred to as the initial step. Similarly, the step activated first for any STL sequence is also called the initial step.
SET S005
STL
Y000
S005
Y011
Y014
3.3.3 Terminating an STL Program
Once an STL program has been started the programmable controllers CPU will process all fol- lowing instructions as being part of that STL program. This means that when a second pro- gram scan is started the normal instructions at the beginning of the program are considered to be within the STL program. This is obviously incorrect and the CPU will proceed to identify a programming error and disable the programmable controllers operation. This scenario may seem a little strange but it does make sense when it is considered that the STL program must return control to the ladder program after STL operation is complete. This means the last step in an STL program needs to be identified in some way.
This is achieved by placing a RET or RETurn instruction as the last instruction in the last STL step of an STL program block. This instruction then returns programming con- trol to the ladder sequence.
SET S005
STL
Y000
S005
Y011
Y014
RET
dard ladder between each STL program. For display of STL in SFC style format the RET instruction is used to indicate the end of a complete STL program.

FX Series Programmable Controllers STL Programming 3
To activate an STL step the user must first drive the state coil. Setting the coil has already been identified as a way to start an STL program, i.e. drive an initial state. It was also noted that using an OUT statement to driving a state coil has a different meaning to the SET instruction. These difference will now be explained:
However, if an STL state is driven by a series of standard ladder logic instructions, i.e. not a preceding STL state, then standard programming rules apply. In the example shown opposite S20 is not reset even after S30 or S21 have been driven. In addition, if S20 is turned OFF, S30 will also stop operating. This is because S20 has not been used as an STL state. The first instruction involving the status of S20 is a standard LoaD instruction and NOT an STL instruction.
S020
S020
S030
SET S021
RST S022
STL step, using the RST or ZRST (FNC 40) instructions would perform this task.

FX Series Programmable Controllers STL Programming 3
This has the same operational features as using SET. However, there is one major function which SET is not used. This is to make what is termed ‘distant jumps’.
If a user wishes to ‘jump’ back up a program, i.e. go back to a state which has already been processed, the OUT instruction would be used with the appropriate STL state number. Alternatively the user may wish to make a large ‘jump’ forwards skipping a whole section of STL programmed states.
S 0
S 20
S 20
OUT
S 21
S 22
S 21
OUT
S 22
S 23
S 23
Out is used for distant jumps
If a step in one STL program flow was required to trigger a step in a second, separate STL program flow the OUT instruction would be used.
S 1
S 20
S 40
S 21
S 41
OUT
S 42
S 22
S 43
S 23
S 44
display of STL in SFC like structured format.

FX Series Programmable Controllers STL Programming 3
It can be seen that there are a lot of advantages to using STL style programming but there are a few points a user must be aware of when writing the STL sub-programs. These are highlighted in this section.
1 Each STL step makes its own bus bar. This means that a user, cannot use an MPS instruction directly after the STL instruction (see ), i.e. There needs to be at least a single contact before the MPS instruction.
Y000
S005
Y011
RET
This is because the user can take advantage of the STL’s unique feature of isolating all STL steps except the active STL steps. This means in practice that there will be no conflict between dual coils. The example opposite shows M111 used twice in a single STL flow.
M112
S 32 M111

FX Series Programmable Controllers STL Programming 3
T001 S 30
T001
S 31
T001
K50
S 32
T001
Y11 S 30
Y11
S 31 Y10

FX Series Programmable Controllers STL Programming 3
Transferring between active STL steps can be controlled by a single signal. There are two methods the user can program to achieve this result.
In this example it is necessary to program separate locking devices, and the controlling signal must only pulse ON. This is to prevent the STL programs from running through. The example shown below identifies the general program required for this method.
- S30 is activated when M0 is first pulsed ON.
- The operation of M1 prevents the sequence from continuing because although M0 is ON, the transfer requirements, need M0 to be ON and M1 to be OFF.
S 30
M1 PLS
- After one scan the pulsed M0 and the ‘lock’ device M1 are reset.
M1
- On the next pulse of M0 the STL step will transfer program control from S31 to the next step in a similar manner. This time using M2 as the ‘lock’ device because dual coils in successive steps is not allowed.
M2 M0
- The reason for the use of the ‘lock’ devices M1 and M2 is because of the handshaking period when both states involved in the transfer of program control are ON for 1 program scan. Without the ‘locks’ it would be possible to immediately skip through all of the STL states in one go!
Using the pulse contacts (LDP, LDF, ANP, etc.) and a special range of M devices (M2800 to M3071) the FX2N(C) PLC’s achieves the same result as method 1. The special feature of these devices prevents run through of the states, as only the first occurrence of the LDP instruction will activate.
The example program below shows the necessary instructions.
- Assume S50 is already active.
- When X01 activates M2800, this in turn activates the LDP M2800 instruction in S50 and the flow moves on to step S51.
Do not use the step control device in a pulse contact within the main program body.
M2800
- The LDP M2800 instruction in the transition part of S51 does not execute because this is the second occurrence of M2800 in a pulse contact.
SET S51 M2800
M2800
- When X01 next activates M2800, the LDP instruction in S51 is the first occurrence because S50 is now inactive. Thus, control passes to the next step in the same manner.
M2800
SET Snn M2800

FX Series Programmable Controllers STL Programming 3
Although STL can operate with most basic and applied instructions there are a few exceptions. As a general rule STL and MC-MCR programming formats should not be combined. Other instruction restrictions are listed in the table below.

Other restrictions are as follows:
- FOR - NEXT structures can not contain STL program blocks.
- Subroutines and interrupts can not contain STL program blocks.
- STL program blocks can not be written after an FEND instruction.
- FOR - NEXT instructions are allowed within an STL program with a nesting of up to 4 levels.
For more details please see the operational compatibility listed in the two tables on pages 7-12,7-13.

FX Series Programmable Controllers STL Programming 3
So far STL has been considered as a simple flow charting programming language. One of STL’s exceptional features is the ability to create programs which can have several operating modes. For example certain machines require a selection of ‘manual’ and ‘automatic’ modes, other machines may need the ability to select the operation or manufacturing processes required to produce products ‘A’, ‘B’, ‘C’, or ‘D’. STL achieves this by allowing multiple program branches to originate from one STL state. Each branch is then programmed as an individual operating mode, and because each operating mode should act individually, i.e. there should be no other modes active; the selection of the program branch must be mutually exclusive. This type of program construction is called “Selective Branch Programming”. An example instruction program can be seen below, (this is the sub-program for STL state S20 only) notice how each branch is SET by a different contact.

A programming construction to split the program flow between different branches is very useful but it would be more useful if it could be used with a method to rejoin a set of individual branches.

This type of STL program construction is called a “First State Merge” simply because the first state (in the example S29, S39 or S49) to complete its operation will cause the merging state (S50) to be activated. It should be noticed how each of the final STL states on the different program branches call the same “joining” STL state.

FX Series Programmable Controllers STL Programming 3
In the previous branching technique, it was seen how a single flow could be selected from a group. The following methods describe how a group of individual flows can be activated simultaneously. Applications could include vending machines which have to perform several tasks at once, e.g. boiling water, adding different taste ingredients (coffee, tea, milk, sugar) etc. In the example below when state S20 is active and X0 is then switched ON, states S21, S31 and S41 are ALL SET ON as the next states. Hence, three separate, individual, branch flows are ‘set in motion’ from a single branch point. This programming technique is often called a ‘Parallel Branch’. To aid a quick visual distinction, parallel branches are marked with horizontal, parallel lines.
S Y X S
S 20
Y0
SET SET
31 41 S S
S 21 S 31 S 41

FX Series Programmable Controllers STL Programming 3
When a group of branch flows are activated, the user will often either;
a) ‘Race’ each flow against its counter parts. The flow which completes fastest would then
activate a joining function (“First State Merge” described in the previous section) OR
b) The STL flow will not continue until ALL branch flows have completed there tasks.
This is called a ‘Multiple State Merge”.
An explanation of Multiple State Merge now follows below. In the example below, states S29, S39 and S49 must all be active. If the instruction list is viewed it can be seen that each of the states has its own operating/processing instructions but that also additional STL instructions have been linked together (in a similar concept as the basic AND instruction). Before state S50 can be activated the trigger conditions must also be active, in this example these are X10, X11 and X12. Once all states and input conditions are made the merging or joining state can be SET ON. As is the general case, all of the states used in the setting procedure are reset automatically.
S Y
Y10 S 29 S 39 S 49 Y11 Y12
STL OUT
S Y
S 50
STL OUT
S Y
STL STL STL LD AND AND SET
S S S X X X S
29 39 49 10 11 12 50
Because more than one state is being simultaneously joined with further states (some times described as a parallel merge), a set of horizontal parallel lines are used to aid a quick visual recognition.

FX Series Programmable Controllers STL Programming 3
For each branch point 8 further branches may be programmed. There are no limits to the num- ber of states contained in a single STL flow. Hence, the possibility exists for a single initial state to branch to 8 branch flows which in turn could each branch to a further 8 branch flows etc. If the programmable controllers program is read/written using instruction or ladder formats the above rules are acceptable. However, users of the FX-PCS/AT-EE programming package who are utilizing the STL programming feature are constrained by further restrictions to enable automatic STL program conversions (please see page 3-15 for more details). When using branches, different types of branching /merging cannot be mixed at the same branch point. The item marked with a ‘S’ are transfer condition which are not permitted.

The following branch configurations/modifications are recommended:

STL LD SET STL LD SET STL LD SET STL LD AND SET LD AND SET
S X S S X S S X S S S X S S X S
20 0 100 30 1 100 40 2 100 100 100 3 50 100 4 60
STL STL STL LD SET STL LD SET SET
S S S X S
20 30 40 0 101 101 101 50 60
STL LD SET STL LD SET STL LD SET SET
S X S S X S
S S X S S S X S S X S
20 30 0 103 103 103 1 40 103 2 50

FX Series Programmable Controllers STL Programming 3

This software has the ability to program in SFC flow diagrams. As part of this ability it can read and convert existing STL programs back into SFC flows even if they were never originally programmed using the FX-PCS/AT-EE software. As an aid to allowing this automatic SFC flow generation the following rules and points should be noted:
3) The total number of branches which can be programmed with the STL programming mode are limited to a maximum of 16 circuits for an STL flow. Each branch point is limited to a maximum of 8 branching flows. This means two branch points both of 8 branch flows would equal the restriction. These restrictions are to ensure that the user can always view the STL flow diagram on the computer running the FX-PCS-AT/ EE software and that when it is needed, the STL program flow can be printed out clearly.

FX Series Programmable Controllers STL Programming 3
3.11.1 A Simple STL Flow
Y10 Y12
Y11
Y13
This simple example is an excerpt from a semi-automatic loading-unloading ore truck program. This example program has a built in, initialization routine which occurs only when the PLC is powered from OFF to ON. This is achieved by using the special auxiliary relay M8002.
This activates a Zone ReSeT (ZRST is applied instruction 40) instruction which ensures all of the operational STL states within the program are reset. The program example opposite shows an M8002/ZRST example.
ZRST S21 S25
The push button X0 acts as a start button and a mode selection button. The STL state S0 is initialized with the ZRST instruction. The system waits until inputs X0 and X2 are given and Y 13 is not active. In the scenario this means the ore truck is positioned at the ore discharge point, i.e. above the position sensor X2. The ore truck is not currently discharging its load, i.e. the signal to open the trucks unloading doors (Y13) is not active and the start button (X0) has been given. Once all of the points have been met the program steps on to state S21.
On this state the ore cart is moved (Y10) and positioned (X1) at the loading hopper. If the start button (X0) is pressed during this stage the ore cart will be set into a repeat mode (M2 is reset) where the ore truck is immediately returned to the loading hopper after discharging its current load. This repeat mode must be selected on every return to the loading station.
Once at the loading point the program steps onto state S22. This state opens the hoppers doors (Y11) and fills the truck with ore. After a timed duration, state S23 is activated and the truck returns (Y12) to the discharge point (X2).

FX Series Programmable Controllers STL Programming 3
Once at the discharge point the truck opens its bottom doors (Y13). After a timed duration in which the truck empties its contents, the program checks to see if the repeat mode was selected on the last cycle, i.e. M2 is reset. If M2 was reset (in state S21) the program ‘jumps’ to step S21 and the ore truck is returned for immediate refilling. If M2 is not reset, i.e. it is active, the program cycles back to STL state S0 where the ore truck will wait until the start push button is given. This is a simple program and is by no means complete but it identifies the way a series of tasks have been mapped to an STL flow.

1 22 22 11 1 70 1 23 23 12 2 24 24 13
2 50 2 2 25 2 2 0 25 2 2 21
K LD ANI SET LD AND OUT STL SET LD OUT RET END
T M S T M S S M M S
S S S X X Y S S Y X M
25 0 0 2 13 21 21 10 0 2
K LD SET STL OUT LD SET STL OUT
This example has used the line convention to identify normally closed contacts, for further variations and different methods used to perform this task please see the information note page 3-3.

FX Series Programmable Controllers STL Programming 3
The following example depicts an automatic sorting robot. The robot sorts two sizes of ball bearings from a mixed ‘source pool’ into individual storage buckets containing only one type of ball bearing.

The sequence of physical events (from initial power On) are:

FX Series Programmable Controllers STL Programming 3
Full STL flow diagram/program.
This example uses the dot notation to identify normally open and normally closed contacts.
Normally open contacts Normally closed contacts
S 21
Y0
K20
T0
T0
T0
Lower limit = small ball
Lower limit = large ball
S 25 SET Y1
K10
K10
T1
T1
T1
T1
S 23
Y2
S 26
Y2
S 24
Y3
S 27
Y3
Move to small ball bucket
Move to large ball bucket
Y0
S 31
RST Y1
K10
T2
T2
S 32 Y2
S 33 Y4 X1

FX Series Programmable Controllers STL Programming 3
STL programming can be enhanced by using the Initial State Applied Instruction. This instruction has a mnemonic abbreviation of IST and a special function number of 60. When the IST instruction is used an automatic assignment of state relays, special auxiliary relays (M coils) is made. The IST instruction provides the user with a pre-formatted way of creating a multi-mode program. The modes available are:
a) Automatic:
b) Manual:
More details on this instruction can be found on page 5-67.

FX Series Programmable Controllers Devices in Detail 4
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Devices in Detail 4
4. Devices in Detail 4-1 4.1 Inputs 4-1 4.2 Outputs 4-2 4.3 Auxiliary Relays 4-3 4.3.1 General Stable State Auxiliary Relays 4-3 4.3.2 Battery Backed/ Latched Auxiliary Relays 4-4 4.3.3 Special Diagnostic Auxiliary Relays 4-5 4.3.4 Special Single Operation Pulse Relays 4-5 4.4 State Relays 4-6 4.4.1 General Stable State - State Relays 4-6 4.4.2 Battery Backed/ Latched State Relays 4-7 4.4.3 STL Step Relays 4-8 4.4.4 Annunciator Flags 4-9 4.5 Pointers 4-10 4.6 Interrupt Pointers 4-11 4.6.1 Input Interrupts 4-12 4.6.2 Timer Interrupts 4-12 4.6.3 Disabling Individual Interrupts 4-13 4.6.4 Counter Interrupts 4-13 4.7 Constant K 4-14 4.8 Constant H 4-14 4.9 Timers 4-15 4.9.1 General timer operation 4-16 4.9.2 Selectable Timers 4-16 4.9.3 Retentive Timers 4-17 4.9.4 Timers Used in Interrupt and ‘CALL’ Subroutines 4-18 4.9.5 Timer Accuracy 4-18 4.10 Counters 4-19 4.10.1 General/ Latched 16bit UP Counters 4-20 4.10.2 General/ Latched 32bit Bi-directional Counters 4-21 4.11 High Speed Counters 4-22 4.11.1 Basic High Speed Counter Operation 4-23 4.11.2 Availability of High Speed Counters on FX0, FX0S and FX0N PCs 4-24 4.11.3 Availability of High Speed Counters on FX, FX2C PCs 4-25 4.11.4 Availability of High Speed Counters on FX2N PCs 4-28 4.11.5 1 Phase Counters - User Start and Reset (C235 - C240) 4-29 4.11.6 1 Phase Counters - Assigned Start and Reset (C246 to C250) 4-30 4.11.7 2 Phase Bi-directional Counters (C246 to C250) 4-31 4.11.8 A/B Phase Counters (C252 to C255) 4-32 4.12 Data Registers 4-33 4.12.1 General Use Registers 4-34 4.12.2 Battery Backed/ Latched Registers 4-35 4.12.3 Special Diagnostic Registers 4-35 4.12.4 File Registers 4-36 4.12.5 Externally Adjusted Registers 4-37 4.13 Index Registers 4-38 4.13.1 Modifying a Constant 4-39 4.13.2 Misuse of the Modifiers 4-39 4.13.3 Using Multiple Index Registers 4-39 4.14 Bits, Words, BCD and Hexadecimal 4-40 4.14.1 Bit Devices, Individual and Grouped 4-40 4.14.2 Word Devices 4-42 4.14.3 Interpreting Word Data 4-42 4.14.4 Two’s Compliment 4-45 4.15 Floating Point And Scientific Notation 4-46 4.15.1 Scientific Notation 4-47 4.15.2 Floating Point Format 4-48 4.15.3 Summary Of The Scientific Notation and Floating Point Numbers 4-49

FX Series Programmable Controllers
Devices in Detail 4
Inp (X) Input Input contact
(see example device usage for references)
Y10
Available devices:

FX Series Programmable Controllers Devices in Detail 4
Otp Out (Y) Output (Y) Output (coil/ relay/ contact)
(see example device usage for references)
Y10
Y10
Available devices:
PLC Maximum number of
FX0(S) Set by selected base unit 30
FX0N 84 Max. input config’ (40)
128 (60) 64 Max. output config’
FX(2C) 256 (addressable in software)
256 (Total addressed in software/hardware) FX2N(C)
256 (addressable in software)

FX Series Programmable Controllers Devices in Detail 4
M (coil/ relay/ contact /flag) M (bit) device
(see example device usage for references)
Further uses: General stable state auxiliary relays - see page 4-3 Battery backed/ latched auxiliary relays - see page 4-4 Special diagnostic auxiliary relays - see page 4-5
M507
M507
4.3.1 General Stable State Auxiliary Relays
PLC FX0(S) FX0N FX FX(2C) FX2N(C)
496 (M0 - 495)
384 (M0 - 383)
500 (M0 - 499)
500 (M0 - 499)
500 (M0 - 499)
524 (M500 - 1023)
1036 (M500 -
2572 (M500 -
Battery backed/ latched relays
128 (M384 - 511)
Total available 512 512 1024 1536 3072
General auxil- iary relays · 1535) · 3071)

FX Series Programmable Controllers Devices in Detail 4
There are a number of battery backed or latched relays whose status is retained in battery backed or EEPROM memory. If a power failure should occur all output and general purpose relays are switched off. When operation is resumed the previous status of these relays is restored. The circuit shown on page 4-3 is an example of a self retaining circuit. Relay M507 is activated when X0 is turned ON. If X0 is turned OFF after the activation of M507, the ON status of M507 is self retained, i.e. the NO contact M507 drives the coil M507. However, M507 is reset (turned OFF) when the input X1 is turned ON, i.e. the NC contact is broken. A SET and RST (reset) instruction can be used to retain the status of a relay being activated momentarily.
RST M507 X1
External loads:

FX Series Programmable Controllers Devices in Detail 4
A PLC has a number of special auxiliary relays. These relays all have specific functions and are classified into the following two types.
a) Using contacts of special auxiliary relays
- Coils are driven automatically by the PLC. Only the contacts of these coils may be used by a user defined program.
b) Driving coils of special auxiliary relays
- A PLC executes a predetermined specific operation when these coils are driven by the user.
When used with the pulse contacts LDP, LDF, etc., M devices in the range M2800 to M3072 have a special meaning. With these devices, only the next pulse contact instruction after the device coil is activated.


FX Series Programmable Controllers Devices in Detail 4
S (coil/ relay/ contact /flag) STL step (coil/ relay/ contact /flag) Annunciator flag
(see example device usage for references)
Further uses: General stable state - state relays - see page 4-6 Battery backed/ latched state relays - see page 4-7 STL step relays - see page 4-8 Annunciator flags - see page 4-9
S20
S20
4.4.1 General Stable State - State Relays
A number of state relays are used in the PLC. The coils of these relays are driven by device contacts in the PLC in the same manner that the output relays are driven in the program. All state relays have a number of electronic NO and NC contacts which can be used by the PLC as required. Note that these contacts cannot directly drive an external load. Only output relays can be used to do this.

FX Series Programmable Controllers Devices in Detail 4
There are a number of battery backed or latched relays whose status is retained in battery backed or EEPROM memory. If a power failure should occur all output and general purpose relays are switched off. When operation is resumed the previous status of these relays is restored.
PLC FX0(S) FX0N FX FX(2C) FX2N(C)
General state relays 64 (S0 - 63) N/A 500 (S0 - 499)
latched relays N/A 128 (S0 - 127)
Total available 64 128 1000
Battery backed/

FX Series Programmable Controllers Devices in Detail 4
States (S) are very important devices when programming step by step process control. They are used in combination with the basic instruction STL. When all STL style programming is used certain states have a pre-defined operation. The step identified as in the figure opposite is called an ‘initial state’. All other state steps are then used to build up the full STL function plan. It should be remembered that even though remaining state steps are used in an STL format, they still retain their general or latched operation status. The range of available devices is as specified in the information point of the previous section.
S20
Y0
S21
Y1
S22
Y2
Assigned states:
S0 : Manual operation initial state S1 : Zero return initial state S2 : Automatic operation initial state S10 to S19 : Allocated for the creation of the zero return program sequence

FX Series Programmable Controllers Devices in Detail 4
Some state flags can be used as outputs for external diagnosis (called annunciation) when certain applied instructions are used. These instructions are;
ANS function 46: ANnunciator Set - see page 5-47 ANR function 47: ANnunciator Reset - see page 5-47
When the annunciator function is used the controlled state flags are in the range S900 to S999 (100 points). By programming an external diagnosis circuit as shown below, and monitoring special data register D8049, the lowest activated state from the annunciator range will be displayed. Each of the states can be assigned to signify an error or fault condition. As a fault occurs the associated state is driven ON. If more than one fault occurs simultaneously, the lowest fault number will be displayed. When the active fault is cleared the next lowest fault will then be processed. This means that for a correctly prioritized diagnostic system the most dangerous or damaging faults should activate the lowest state flags, from the annunciator range. All state flags used for the annunciator function fall in the range of battery backed/ latched state registers.
Monitoring is enabled by driving special auxiliary relay M8049 ON. State S900 is activated if input X0 is not driven within one second after the output Y0 has been turned ON. State S901 is activated when both inputs X1 and X2 are OFF for more than two seconds. If the cycle time of the controlled machine is less than ten seconds, and input X3 stays ON, state S902 will be set ON if X4 is not activated within this machine cycle time. If any state from S900 to S999 is activated, i.e. ON, special auxiliary relay M8048 is activated to turn on failure indicator output Y10. The states activated by the users error / failure diagnosis detection program, are turned OFF by activating input X5. Each time X5 is activated, the active annunciator states are reset in ascending order of state numbers.
M8049
Y0 X0
FNC46
S900 K10 T0 ANS
FNC46
S901 K20 T1 ANS
FNC46
S902 K100 T2 ANS
M8048
Y10
FNC47
ANR (P)

FX Series Programmable Controllers Devices in Detail 4
Available forms: Label: appears on the left of the left hand bus bar when the program is
viewed in ladder mode.
Further uses: Can be used with conditional jump statements (CJ function 00) - see page 5-5 and item on the example device usage diagram. Can be used with call statements (CALL function 01 -not available on FX0 and FX0N PLC’s) - see page 5-7 and item on the example device usage diagram
CALL P1
CJ P0
1 P0
FEND
P1
SRET
Available devices:

FX Series Programmable Controllers Devices in Detail 4
High speed interrupt I
Available forms: Label: appears on the left of the left hand bus bar when the program is
viewed in ladder mode (see ¿ in the example device usage diagram).
Further uses: Input interrupts - see page 4-12 Timer interrupts - see page 4-12 Disabling interrupts - see page 4-13 Counter interrupts - see page 4-13
FEND
IRET
END
Additional applied instructions:
- IRET function 03: interrupt return - see page 5-9 - EI function 04: enable interrupt - see page 5-9 - DI function 05: disable interrupt - see page 5-9
triggering method

FX Series Programmable Controllers Devices in Detail 4
Identification of interrupt pointer number:
Input number; each input number can only be used once. FX0(S) and FX0N have 4 points (0 to 3 which map to X0 to X3) Other units have 6 points (0 to 5 which map to X0 to X5)
The sequence programmed after the label (indicated by the I001 pointer) is executed on the leading or rising edge of the input signal X0. The program sequence returns from the interruption program when an IRET instruction is encountered.
- Interrupt pointers cannot have the same number in the ‘100’s’ position, i.e. I100 and I101 are not allowed.
- The input used for the interrupt device must not coincide with inputs already allocated for use by other high speed instructions within the user program.
Identification of interrupt pointer number:
10 to 99 msec: the interrupt is repeatedly triggered at intervals of the specified time.
Timer interrupt number 3 points (6 to 8)
The sequence programmed after the label (indicated by the I610 pointer) is executed at intervals of 10msec. The program sequence returns from the interruption program when an IRET instruction is encountered.
- Interrupt pointers cannot have the same number in the ‘100’s’ position, i.e. I610 and I650 are not allowed.

FX Series Programmable Controllers Devices in Detail 4
Individual interrupt devices can be temporarily or permanently disabled by driving an associated special auxiliary relay. The relevant coils are identified in the tables of devices in chapter 6. However for all PLC types the head address is M8050, this will disable interrupt I0.
Identification of interrupt pointer number:
Counter interrupt number 6 points (1 to 6). Counter interrupts can be entered as the output devices for High Speed Counter Set (HSCS, FNC 53). To disable the Counter Interrupts Special Auxiliary Relay M8059 must be set ON.
Example:
The sequence programmed after the label (indicated by the I030 pointer) is executed once the value of High Speed Counter C255 reaches/equals the preset limit of K100 identified in the example HSCS.
C255 I030 K100 DHSCS
Additional notes:
- High Speed Counter Set, HSCS FNC 53 - see page 5-55

FX Series Programmable Controllers Devices in Detail 4
K (value/ constant) K
the range -32,768 to +32,767 For 32bit data, values from the range -2,147,483,648 to + 2,147,483,647 can be used.
Devices numbered in: N/A. This device is a method of local instruction data entry.
There is no limit to the number of times it can be used.
H (value/ constant) Hex (value/ constant) H
Available forms: Alpha-numeric data value, i.e. 0 to 9 and A to F (base 16).
When used for 16bit data, values can be selected from the range 0 to FFFF. For 32bit data, values from the range 0 to FFFFFFFF can be used.
Devices numbered in: N/A. This device is a method of local instruction data entry.
There is no limit to the number of times it can be used.

FX Series Programmable Controllers Devices in Detail 4
Available forms: A driven coil sets internal PLC contacts (NO and NC contacts available).
Various timer resolutions are possible, from 1 to 100 msec, but availability and quantity vary from PLC to PLC. The following variations are also available:- Selectable timer resolutions - see page 4-16 Retentive timers - see page 4-17 Timers used in interrupt and ‘CALL’ subroutines - see page 4-18
Devices numbered in: Decimal, i.e T0 to T9, T10 to T19.
T20
K123
Available devices:
Timer Resolution FX0(S) FX0N FX FX(2C) FX2N(C)
100 msec 56 (T0 - 55)
200 (T0 - 199)
10 msec \ 24 (T32 - 55)
46 (T200 - 245)
1 msec N/A 1 (T63) N/A
Retentive 1 msec N/A N/A 4 (T246 - 249)
Retentive 100 msec N/A N/A 6 (T250 - 255)
\ Selectable timers taken from the main range of 100 msec timers, see page 4-16.

FX Series Programmable Controllers Devices in Detail 4
Timers operate by counting clock pulses (1, 10 and 100 msec). The timer output contact is activated when the count data reaches the value set by the constant K. The overall duration or elapsed time, for a timers operation cycle, is calculated by multiplying the present value by the timer resolution, i.e.
A 10 msec timer with a present value of 567 has actually been operating for:
567× 10 msec 567× 0.01 sec = 5.67 seconds
Timers can either be set directly by using the constant K to specify the maximum duration or indirectly by using the data stored in a data register (ex. D). For the indirect setting, data registers which are battery backed/ latched are usually used; this ensures no loss of data during power down situations. If however, the voltage of the battery used to perform the battery backed service, reduces excessively, timer malfunctions may occur.
On certain programmable controllers, driving a special auxiliary coil redefines approximately half of the 100 msec timers as 10 msec resolution timers. The following PLC’s and timers are subject to this type of selection.
- FX0, FX0S driving M8028 ON, timers T32 to 55 (24 points) are changed to 10 msec resolution.
- FX0N driving M8028 ON, timers T32 to 62 (31 points) are changed to 10 msec resolution.

FX Series Programmable Controllers Devices in Detail 4
A retentive timer has the ability to retain the currently reached present value even after the drive contact has been removed. This means that when the drive contact is re-established a retentive timer will continue from where it last reached. Because the retentive timer is not reset when the drive contact is removed, a forced reset must be used. The following diagram shows this in a graphical format.
Non-retentive timer operation Retentive timer operation
T250
K123
K345
T20
T250
Y0 Y1
T250 RST
1.23 s t1 t2
t1 + t2 = 34.5s
Present value Present value
Y1
Using timers in interrupt or ‘CALL’ subroutines:

FX Series Programmable Controllers Devices in Detail 4
If timers T192 to T199 and T246 to T249 are used in a CALL subroutine or an interruption routine, the timing action is updated at the point when an END instruction is executed. The output contact is activated when a coil instruction or an END instruction is processed once the timers current value has reached the preset (maximum duration) value. Timers other than those specified above cannot function correctly within the specified circumstances. When an interrupt timer (1 msec resolution) is used in an interrupt routine or within a ‘CALL’ subroutine, the output contact is activated when the first coil instruction of that timer is executed after the timer has reached its preset (maximum duration) value.
Timer accuracy can be affected by the program configuration. That is to say, if a timer contact is used before its associated coil, then the timer accuracy is reduced. The following formulas give maximum and minimum errors for certain situations. However, an average expected error would be approximately;
1.5 × The program scan time
The timer contact appears after the timer coil.
T0
Y10
Maximum timing error:
2 × Scan time + The input filter time
Minimum timing error:
Input filter time - The timer resolution
T0
The timer contact appears before the timer coil.
T0
Maximum timing error:
3 × Scan time + The input filter time
Minimum timing error:
Input filter time- The timer resolution

FX Series Programmable Controllers Devices in Detail 4
Available forms: A driven coil sets internal PLC contacts (NO and NC contacts available).
Various counter resolutions are possible including; General/latched 16bit up counters - see page 4-20 General/latched 32bit bi-directional counters - see page 4-21 (The availability and use of all these counters is PLC specific - please check availability before use)
K345 X2
C12 RST
Available devices:
Counter Resolution FX0(S) FX0N FX FX(2C) FX2N(C)
16 (C0 - 15)
100 (C0 - 99)
2 (C14 - 15)
16 (C16 - 31)
100 (C100 - 199)
General 32bit bi-directional counter N/A N/A 20 (C200 - 219)
Latched 32bit bi-directional counter N/A N/A 15 (C220 - 234)

FX Series Programmable Controllers Devices in Detail 4
The current value of the counter increases each time coil C0 is turned ON by X11. The output contact is activated when the coil is turned ON for the tenth time (see diagram). After this, the counter data remains unchanged when X11 is turned ON. The counter current value is reset to ‘0’ (zero) when the RST instruction is executed by turning ON X10 in the example. The output contact Y0 is also reset at the same time. Counters can be set directly using constant K or indirectly by using data stored in a data register (ex. D). In an indirect setting, the designation of D10 for example, which contains the value “123” has the same effect as a setting of “K123”. If a value greater than the counter setting is written to a current value register, the counter counts up when the next input is turned ON. This is true for all types of counters. Generally, the count input frequency should be around several cycles per second.
K10
Y0
0 1 2 3 4 5 6 7 8 9 10
Battery backed/latched counters:

FX Series Programmable Controllers Devices in Detail 4
The counter shown in the example below, activates when its coil is driven, i.e. the C200 coil is driven. On every occasion the input X14 is turned from OFF to ON the current value or current count of C200 is incremented.

The output coil of C200 is set ON when the current value increases from “-6” to “-5”. However, if the counters value decreases from “-5” to “-6” the counter coil will reset. The counters current value increases or decreases independently of the output contact state (ON/OFF). Yet, if a counter counts beyond +2,147,483,647 the current value will automatically change to -2,147,483,648. Similarly, counting below -2,147,483,648 will result in the current value changing to +2,147,483,647. This type of counting technique is typical for “ring counters”. The current value of the active counter can be rest to "0" (zero) by forcibly resetting the counter coil; in the example program by switching the input X13 ON which drives the RST instruction. The counting direction is designated with special auxiliary relays M8200 to M8234.

FX Series Programmable Controllers Devices in Detail 4
C High speed counter (s) Phase counters
Available forms: A driven coil sets internal PLC contacts (NO and NC contacts available).
There are various types of high speed counter available but the quantity and function vary from PLC to PLC. Please check the following sections for device availability;
FX0,FX0S and FX0N - see page 4-24 FX, FX2C, FX2N(C) - see page 4-25
The following sections refer to counter types; 1 phase counters (user start and reset) - see page 4-29 1 phase counters (assigned start and reset) - see page 4-30 2 phase bi-directional counters - see page 4-31 A/B phase counters - see page 4-32
sections.

FX Series Programmable Controllers Devices in Detail 4
Although counters C235 to C255 (21 points) are all high speed counters, they share the same range of high speed inputs. Therefore, if an input is already being used by a high speed counter, it cannot be used for any other high speed counters or for any other purpose, i.e as an interrupt input. The selection of high speed counters are not free, they are directly dependent on the type of counter required and which inputs are available.
a) 1 phase with user start/reset: C235 to C240
b) 1 phase with assigned start/reset: C241 to C245
Please note ALL of these counters are 32bit devices. High speed counters operate by the principle of interrupts. This means they are event triggered and independent of cycle time. The coil of the selected counter should be driven continuously to indicate that this counter and its associated inputs are reserved and that other high speed processes must not coincide with them.
When X20 is ON, high speed counter C235 is selected. The counter C235 corresponds to count input X0. X20 is NOT the counted signal. This is the continuous drive mentioned earlier. X0 does not have to be included in the program. The input assignment is hardware related and cannot be changed by the user.
D4
When X20 is OFF, coil C235 is turned OFF and coil C236 is turned ON. Counter C236 has an assigned input of X1, again the input X20 is NOT the counted input. The assignment of counters and input devices is dependent upon the PLC selected. This is explained in the relevant, later sections.
D4
Available counter types;

FX Series Programmable Controllers Devices in Detail 4
4.11.2 Availability of High Speed Counters on FX0, FX0S and FX0N PLC’s
The following device table outlines the range of available high speed counters on both the FX0, FX0S and the FX0N;
1 Phase counter assigned start/reset
1 Phase counter user start/reset
2 Phase counter bi-directional A/B Phase counter
C235 C236 C237 C238 C241 C242 C244 C246 C247 C249 C251 C252 C254
X0 U/D U/D U/D U U U A A A
X1 U/D R R D D D B B B
X3 U/D R S S S
Key: U - up counter input D - down counter input R - reset counter (input) S - start counter (input) A - A phase counter input B - B phase counter input - Counter is backed up /latched on both FX0, FX0S and FX0N - Counter is backed up /latched on FX0N only (FX0, FX0S has no backup/latch on this device)
Sum of the speeds of the active 1 phase
Max. combined
Max. 1 phase
Max. 2 phase
Max. number of
sum of 1 and 2 phase counting
FX0, FX0N 5kHz ≤ 5kHz 2 kHz 1 1 phase and 2 phase counters cannot be mixed
FX0S 7kHz ≤ 14kHz 2 kHz 1 ≤ 14kHz see
This is calculated as follows:(2 phase counter speed x number of counted edges)
(the sum of the speeds of the active 1 phase counters).

FX Series Programmable Controllers Devices in Detail 4
The following device table outlines the range of available high speed counters on both the FX, FX2C.
1 Phase counter assigned start/reset
1 Phase counter user start/reset
2 Phase counter bi-directional A/B Phase counter
C235 C236 C237 C238 C239 C240 C241 C242 C243 C244 C245 C246 C247 C248 C249 C250 C251 C252 C253 C254 C255
U/D U/D U/D U U U A A A
p U/D R R D D D B B B
U/D R S R U S U A A
p U/D U/D D D B B
p U/D R
X7 S S S
Key: U - up counter input D - down counter input R - reset counter (input) S - start counter (input) A - A phase counter input B - B phase counter input - Counter is backed up / latched

FX Series Programmable Controllers Devices in Detail 4
No execution of high
(D)HSCS/R (1 to 6 instructions)
(1 to 2 instructions)
1 10 7 5
X0, X2, X3 (10 kHz inputs)
2 10 4 2.5 3 6.6 2.5
1 7 5 4
X0 to X5 (When X0, X2 and X3 are not
2 3.5 2.5
No execution of high
(D)HSCS/R (1 to 6 instructions)
(1 to 2 instructions)
2 1.5 1.5
A/B Phase Counters Used with Either a 1 or 2 Phase Counter
The frequency of the A/B phase counter must be kept below 1 kHz. The maximum frequency of the 1, 2 phase counter is listed in the following table:
No execution of high
(D)HSCS/R (1 to 6 instructions)
(1 to 2 instructions)
1 5 4 3
With 1 A/B phase counter
2 4 2 1 3 3

FX Series Programmable Controllers Devices in Detail 4
1 Phase counters Corresponding input Maximum signal frequency
C235 X0 4.2 kHz
C237 X2 4 kHz
C240 X3 6 kHz
Combined frequency 14.2kHz
The combined frequency of 14.2 kHz is lower than the maximum of 20 kHz, so this example is valid.
When calculating a combined frequency which includes an A/B phase counter, the maximum counting frequency should be multiplied by a factor of 4 before adding the maximum frequencies of the combining counters.
1 Phase counters Corresponding input Maximum signal frequency
1- Phase C237 X2 3 kHz
Bi-directional C246 X0, X1 4 kHz
A/B Phase C255 X3, X4 1 kHz × 4
Combined frequency 3 + 4 + (1 × 4) = 11kHz
The combined frequency of 11 kHz is lower than the maximum of 20 kHz, so this example is valid.

FX Series Programmable Controllers Devices in Detail 4
The following device table outlines the range of available high speed counters on FX2N(C).

X0 U/D U/D U/D U U U A A A
X1 U/D R R D D D B B B
X3 U/D R S R U U A A
Key: U - up counter input D - down counter input R - reset counter (input) S - start counter (input) A - A phase counter input B - B phase counter input - Counter is backed up/latched
- Single phase and bi-directional counters; up to 10 kHz. - A/B phase counters; up to 5 kHz. - Maximum total counting frequency; 20 kHz (A/B phase counter count twice).
- Single phase or bi-directional counting with C235, C236 or C246; up to 60 kHz. - Two phase counting with C251; up to 30 kHz.
If any high speed comparison instructions (FNC’s 53, 54, 55) are used, X0 and X1 must resort to software counting. In this case, please see the table below:
Max. Combined Signal Frequency
53 or 54 11 kHz
55 5.5 kHz
Function · Number

FX Series Programmable Controllers Devices in Detail 4
These counters only use one input each. When direction flag M8235 is ON, counter C235 counts down. When it is OFF, C235 counts up. When X11 is ON, C235 resets to 0 (zero). All contacts of the counter C235 are also reset. When X12 is ON, C235 is selected. From the previous counter tables, the corresponding counted input for C235 is X0. C235 therefore counts the number of times X0 switches from OFF to ON.
C235 RST
K1234
Device specification:

FX Series Programmable Controllers Devices in Detail 4
These counters have one countable input and 1 reset input each. Counters C244 and C245 also have a start input. When the direction flag M8245 is ON, C245 counts down. When it is OFF C245 will count up. When X14 is ON, C245 resets in the same manner as normal internal 32bit counters, but C245 can also be reset by input X3. This is assigned automatically when counter C245 is used (see previous counter tables). Counter C245 also has an external start contact, again automatically assigned. This is actually input X7. Once again this data can be found on the previous counter tables. When X7 is ON, C245 starts counting, conversely when X7 is OFF C245 stops counting. The input X15 selects and reserves the assigned inputs for the selected counter, i.e. in this case C245. The reason why these counters use assigned start (X7) and reset (X3) inputs is because they are not affected by the cycle (scan) time of the program. This means their operation is immediate and direct. In this example C245 actual counts the number of OFF to ON events of input X2. Note: Because C245 is a 32bit counter, its setting data, specified here by a data register also has to be of a 32bit format. This means that data registers D1 and D0 are used as a pair to provide the 32bit data format required.
C245 RST
D0
Device specification:
- When M8 is ON the counter counts down.
- When M8 is OFF the counter counts up.

FX Series Programmable Controllers Devices in Detail 4
These counters have one input for counting up and one input for counting down. Certain counters also have reset and start inputs as well.
When X10 is ON, C246 resets in the same way as standard 32bit counters.
Counter C246 uses inputs; X0 to count up and X1 to count down
For any counting to take place the drive input X11 must be ON to set and reserve the assigned inputs for the attached counter, i.e. C246.
X0 moving from OFF to ON will increment C246 by one X1 moving from ON to OFF will decrement C246 by one
Bi-directional counter C250 can be seen to have X5 as its reset input and X7 as its start input. Therefore, a reset operation can be made externally without the need for the RST C250 instruction. X13 must be ON to select C250. But start input X7 must be ON to allow C250 to actually count. If X7 goes OFF counting ceases. Counter C250 uses input X3 to count up and input X4 to count down.
Device size:
- When M8 is ON the counter counts down,
- When M8 is OFF the counter counts up.

FX Series Programmable Controllers Devices in Detail 4
With these counters only the input identified in the previous high speed counter tables can be used for counting. The counting performed by these devices is independent of the program cycle (scan) time. Depending on the counter used, start, reset and other associated inputs are automatically allocated.
The A phase, B phase input signal not only provide the counted signals but their relationship to each other will also dictate the counted direction.
While the wave form of the A phase is in the ON state and... the B phase moves from OFF to ON the counter will be counting up.
However, if... the B phase moves from ON to OFF the counter will be in a down configuration. One count is registered after both A and B phase inputs have been given and released in the correct order.
C251 counts the ON/OFF events of input X0 (the A phase input) and input X1 (the B phase input) while X11 is ON. C255 starts counting immediately when X7 is turned ON while X13 is ON. The counting inputs are X3 (A phase) and X4 (B phase). C255 is reset when X5 is turned ON. It can also be reset with X12 in the sequence.
C255 RST X12
K1234
D0
Device specification:

FX Series Programmable Controllers Devices in Detail 4
D (register) D Word
Available forms: General use registers - see page 4-34 Battery backed/latched registers - see page 4-35 Special diagnostic registers - see page 4-35 File registers - see page 4-36 RAM file registers - see page 4-36 Externally adjusted registers - see page 4-37
FX0 FX0N FX (CPU Ver. 2.3) FX(2C) FX2N(C)
128 (D0 - 127)
200 (D0 - 199)
2 (D30 - 31)
128 (D128 - 256)
312 (D200 - 512)
800 (D200 - 999)
7800 (D200 - 7999)
27 (D8000 - 8069)
39 (D8000 - 8255)
256 (D8000 - 8255)
File registers R N/A 1500 (D1000 - 2499)
7000 (D1000 - 7999)
RAM file registers M N/A 2000 (D6000 - 7999) N/A
2 (D8030 - 8031) N/A
R - These devices are allocated by the user at the expense of available program steps.
On FX2N(C) these devices are a subset of the latched registers.
F - These devices are also included under the count for diagnostic registers.
M - These devices are activated when special auxiliary relay M8074 is turned ON.
No program steps are occupied by RAM file registers.

FX Series Programmable Controllers Devices in Detail 4
Data registers, as the name suggests, store data. The stored data can be interpreted as a numerical value or as a series of bits, being either ON or OFF. A single data register contains 16bits or one word. However, two consecutive data registers can be used to form a 32bit device more commonly known as a double word. If the contents of the data register is being considered numerically then the Most Significant Bit (MSB) is used to indicate if the data has a positive or negative bias. As bit devices can only be ON or OFF, 1 or 0 the MSB convention used is, 0 is equal to a positive number and 1 is equal to a negative number.

The diagram above shows both single and double register configurations. In the diagram identified as ¡, it should be noted that the ‘lower’ register D0 no longer has a ‘Most Significant Bit’. This is because it is now being considered as part of a 32bit-double word. The MSB will always be found in the higher 16 bits, i.e. in this case D1. When specifying a 32 bit data register within a program instruction, the lower device is always used e.g. if the above example was to be written as a 32bit instructional operand it would be identified as D0. The second register, D1, would automatically be associated. Once the data is written to a general data register, it remains unchanged until it is overwritten. When the PLC is turned from RUN to STOP all of the general data registers have their current contents overwritten with a 0 (zero).

FX Series Programmable Controllers Devices in Detail 4
Once data is written to a battery backed register, it remains unchanged until it is overwritten. When the PLC’s status is changed from RUN to STOP, the data in these registers is retained. The range of devices that is battery backed can be changed by adjusting the parameters of the PLC. For details of how to do this please refer to the appropriate programming tools manual.
Communication between Master and Slave 100 points M800 to M899
10 points D490 to D499
Communication between Slave and Master 100 points M900 to M999
10 points D500 to D509
Special registers are used to control or monitor various modes or devices inside the PLC. Data written in these registers are set to the default values when the power supply to the PLC is turned ON.
- Note: When the power is turned ON, all registers are first cleared to 0 (zero) and then the default values are automatically written to the appropriate registers by the system software. For example, the watchdog timer data is written to D8000 by the system software. To change the setting, the user must write the required value over what is currently stored in D8000.
Data stored in the special diagnostic registers will remain unchanged when the PLC is switched from STOP mode into RUN.

FX Series Programmable Controllers Devices in Detail 4
File registers are available in two forms:
- Program memory registers - these occupy program steps in blocks of 500 and are avail- able on FX0N, FX, FX2C and FX2N(C) products
- RAM registers - these occupy a special data area and are available on all FX2C units and FX units with CPU version 3.07 or greater.
File registers can be secured in the program memory (RAM, EEPROM or EPROM) in units of 500 points. These registers can be accessed with a peripheral device. While the PLC is operating, data in the file registers can be read to the general-use/ battery backed/ latched registers by using the BMOV instruction. File registers are actually setup in the parameter area of the PLC. For every block of 500 file registers allocated and equivalent block of 500 program steps are lost.
RAM file registers are 2000 points which can be activated by driving a special auxiliary relay M8074 ON. These registers can then be accessed just like normal program file registers. RAM registers occupy no program steps but do occupy the sampling trace data register area when M8074 is active.

FX Series Programmable Controllers Devices in Detail 4
The FX0 and FX0N have built in “setting pots” which are used to adjust the contents of certain dedicated data registers. The contents of these registers can range from 0 to 255. This is a built in feature and requires no additional setup or programming. The FX, FX2C and FX2N(C) do not have this feature, however, an additional special function unit is available which provides the same function. For the FX and FX2C the unit is the FX-8AV. For FX2N(C) the unit is the FX2N-8AV-BD. To use this unit requires the applied instructions VRRD function 85 (Volume Read) and VRSC function 86 (Volume Scale).
5 Setting pot of an FX0
STOP
Number of setting pots 1 point 2 points 8 points: Supplied by using the additional special function block FX-8AV or FX2N-8AV-BD
Selected by the user when applied instructions
VRRD and VRSC are used.
Number of · controlled data registers

FX Series Programmable Controllers Devices in Detail 4
Purpose: To modify a specified device by stating an offset.
Index (register/ addressing/ modifier) Offset(s) (register/ addressing/ modifier) Indices Modifier
For 16bit data V or Z (2 devices) For 32bit data V and Z combined (1 device - Z is specified) Operation is similar to data registers.
16 Bit 16 Bit
V Z
Devices numbered in: N/A. FX0(S),FX0N, FX, FX2C there are two devices V and/ or Z.
For FX2N(C) there are 16 devices V0 - V7 and Z0 - Z7
Further uses: Can be used to modify the following devices under certain conditions; X, Y, M, S, P, T, C, D, K, H, KnX, KnY, KnM, KnS
The program shown right transfers data from D5V to D10Z. If the data contained in register V is equal to 8 and the data in register Z is equal to 14, then:
V = 8 D5V D5 +8 =13 Ì D13 Z = 14 D10Z D10 + 14 = 24 Ì D24
Hence, the actual devices used after the modifiers V and Z have been taken into account are; D13 and D24 and not D5 and D10 respectively.
32 Bit

FX Series Programmable Controllers Devices in Detail 4
Constants can be modified just as easily as data registers or bit devices. If, for example, the constant K20 was actually written K20V the final result would equal: K20 + the contents of V
Example:
If V = 3276 then K20V
Modifying Kn devices when Kn forms part of a device description such as KnY is not possible, i.e. while the following use of modifiers is permitted;
Statements of the form:
are not acceptable.
The use of multiple index registers is sometimes necessary in larger programs or programs which handle large quantities of data. There is no problem from the PLC’s point of view in using both V and Z registers many times through out a program. The point to be aware of is that it is sometimes confusing for the user or a maintenance person reading such programs, as it is not always clear what the current value of V or Z is.
MOV K20 Z
D40Z X2
ADD D 5V D 15Z
M8000
MOV K0 V
Example:
V = 10 (K10) Z = 20 (K20) D5V = D15 (D5 + V = D5 + 10 = D15) D15Z = D35 (D15 + Z = D15 + 20 = D35) D40Z = D60 (D40 + Z = D40 + 20 = D60)
DADD D 0 D 2
Both V and Z registers are initially set to K10 and K20 respectively. The contents of D15 is added to that of D35 and store in D60. V is then reset to 0 (zero) and both V and Z are used in the double word addition (DADD). The contents of D1, D0 are then added to D3, D2 and then finally stored in D25, D24.

FX Series Programmable Controllers Devices in Detail 4
The following section details general topics relating to good device understanding. The section is split into several smaller parts with each covering one topic or small group of topics. Some of the covered topics are;
Bit devices, individual and grouped - see page 4-40 Word devices - see page 4-42 Interpreting word data - see page 4-42 Two’s compliment - see page 4-45
Devices such as X, Y, M and S are bit devices. Bit devices are bi-stable, this means there are only two states, ON and OFF or 1 and 0. Bit devices can be grouped together to form bigger representations of data, for example 8 consecutive bit devices are some-times referred to as a byte. Further more, 16 consecutive bit devices are referred to as a word and 32 consecutive bit devices are a double word. The PLC identifies groups of bit devices which should be regarded as a single entity by looking for a range marker followed by a head address. This is of the form KnP where P represents the head address of the bit devices to be used. The Kn portion of the statement identifies the range of devices enclosed. “n” can be a number from the range 0 to 8. Each “n” digit actual represents 4 bit devices, i.e K1 = 4 bit devices and K8 = 32 bit devices. Hence all groups of bit devices are divisible by 4. The diagram and example on the following page explain this idea further

FX Series Programmable Controllers Devices in Detail 4
As already explained, bit devices can be grouped into 4 bit units. The “n” in KnM0 defines the number of groups of 4 bits to be combined for data operation. K1 to K4 are allowed for 16bit data operations but K1 to K8 are valid for 32bit operations. K2M0, for example identifies 2 groups of 4 bits; M0 to M3 and M4 to M7, giving a total of 8 bit devices or 1 byte. The diagram below identifies more examples of Kn use.
X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X31 X32 X33 X34 X35 X36 X30 X37
1 0 1 1 0 1 0 0 1 0 1 1 0 0 1 0 1 0
K3X0
K8X0
K1X0 : X0 to X3 4 bit devices with a head address of X0 K1X6 : X6 to X11 4 bit devices with a head address of X6 K3X0 : X0 to X13 12 bit devices with a head address of X0 K8X0 : X0 to X37 32 bit devices with a head address of X0

FX Series Programmable Controllers Devices in Detail 4
Word devices such as T, C, D, V and Z can store data about a particular event or action within the PLC. For the most part these devices are 16 bit registers. However, certain variations do have 32 bit capabilities, as can pairs of consecutive data registers or combined V and Z registers. It may seem strange to quote the size of a word device in bits. This is not so strange when it is considered that the bit is the smallest unit of data within the PLC. So by identifying every thing in bit format a common denomination is being used, hence comparison etc is much easier. Additional consequences of this bit interpretation is that the actual data can be interpreted differently. The physical pattern of the active bits may be the important feature or perhaps the numerical interpretation of the bit pattern may be the key to the program. It all comes down to how the information is read.
As word data can be read in many ways the significance of certain parts of the word data can change. PLC’s can read the word data as:
- A pure bit pattern
- A decimal number
- A hexadecimal number
- Or as a BCD (Binary Coded Decimal) number
The following examples will show how the same piece of data can become many different things depending wholly on the way the information is read or interpreted.
a) Considering a bit pattern
The following bit pattern means nothing - it is simply 16 devices which have two states. Some of the devices are randomly set to one of the states. However, if the header notation (base 2) is added to the 16 bit data the sum, decimal, total of the active bits can be calculated, e.g.,
1 0 0 1 0 0 1 1 1 0 1 0 1
20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 MSB
1 0 0 1 0 0 1 1 1 0 1 0 1
Decimal value = (20 x 1) + (22 x 1) + (24 x 1) + (25 x 1) +(25 x 1) + (29 x 1) + (210 x 1) + (211 x 1) + (212 x 1)
Decimal value = 7797
This is in fact incorrect! There is one bit device which has been shaded in. If its header notation is studied carefully it will be noted that it says MSB. This is the Most Significant Bit. This single bit device will determine if the data will be interpreted as a positive or negative number. In this example the MSB is equal to 1. This means the data is negative. The answer however, is not -7797.

FX Series Programmable Controllers Devices in Detail 4
The reason this is not -7797 is because a negative value is calculated using two’s compliment (described later) but can quickly be calculated in the following manner: Because this is a negative number, a base is set as -32768. This is the smallest number available with 16bit data. To this the positive sum of the active bits is added, i.e. -32768 + 7797. The correct answer is therefore -24971. Remember this is now a decimal representation of the original 16 bit - bit pattern. If the original pattern was re-assessed as a hexadecimal number the answer would be different.
b) A hexadecimal view
Taking the same original bit pattern used in point a) and now adding a hexadecimal notation instead of the binary (base 2) notation the bit patterns new meaning becomes:

1 0 0 1 0 0 1 1 1 0 1 0 1
8 4 2 1 8 4 2 1 8 4 2 1 8 4 2 1
1 0 0 1 0 0 1 1 1 0 1 0 1
Hexadecimal value = ((1 x 8) + (1 x 1)), ((1 x 8) + (1 x 4) + (1 x 2)),
((1 x 4) + (1 x 2) + (1 x 1)), ((1 x 4) + (1 x 1))
Hexadecimal value = 9E75
Two things become immediately obvious after a hexadecimal conversion. The first is that there is sign bit as hexadecimal numbers are always positive. The second is there is an "E" appearing in the calculated data. This is actually acceptable as hexadecimal counts from 0 to 15. But as there are only ten digits (0 to 9), substitutes need to be found for the remaining base 16 numbers, i.e. 10, 11, 12, 13, 14 and 15. The first six characters from the alphabet are used as the replacement indices, e.g. A to F respectively. As a result of base 16 counting, 4 binary bits are required to represent one base 16 or hexadecimal number. Hence, a 16 bit data word will have a 4 digit hexadecimal code. There is actually a forth interpretation for this bit sequence. This is a BCD or Binary Coded Decimal reading. The following section converts the original bit pattern into a BCD format.

FX Series Programmable Controllers Devices in Detail 4
Using the original bit pattern as a base but adding the following BCD headers allows the conversion of the binary data into a BCD format.

1 0 0 1 0 0 1 1 1 0 1 0 1
8 4 2 1 8 4 2 1 8 4 2 1 8 4 2 1
1 0 0 1 0 0 1 1 1 0 1 0 1
Binary Coded Decimal value= ERROR!!!!!
It will be noticed that this will produce an ERROR. The conversion will not be correct. This is because BCD numbers can only have values from 0 to 9, but the second block of 4 bit devices from the left would have a value of 14. Hence, the error. The conversion process is very similar to that of hexadecimal except for the mentioned limit on values of 0 to 9. If the other blocks were converted just as an example the following values would be found;
Extreme Left Hand Block= ((1 × 8) + (1 × 1)) = 9 Second Right Hand Block= ((1 × 4) + (1 × 2) + (1 × 1)) = 7 Extreme Right Hand Block= ((1 × 4) + (1 × 1)) = 5
BCD data is read from left to right as a normal number would be read. Therefore, in this example the “9” would actually represent “9000”. The second right hand block is actually “70” not “7”. The units are provided by the extreme right hand block, i.e. 5. The hundreds “100’s” would have been provided by the second left hand block (which is in error). It is also important to note that there is no sign with BCD converted data. The maximum number allowable for a single data word is “9999” and the minimum is “0000”.
In each of the previous cases the original bit pattern had a further meaning. To recap the three new readings and the original bit pattern,

1 0 0 1 0 0 1 1 1 0 1 0 1
Each meaning is radically different from the next yet they are all different ways of describing the same thing. They are in fact all equal to each other!
c) ABCD conversion

FX Series Programmable Controllers Devices in Detail 4
Programmable controllers, computers etc, use a format called 2’s compliment. This is a mathematical procedure which is more suited to the micro processors operational hardware requirements. It is used to represent negative numbers and to perform subtraction operations. The procedure is very simple, in the following example “15 - 7” is going to be solved:
15 = 00001111 7 = 00000111
7 = 00000111 Inverted 7 = 11111000
Inverted7 11111000 Additional1 00000001 Answer 11111001
This result is actually the same as the negative value for 7 i.e. -7.
Original value15 00001111 Answer found in step3 11111001 Solution (1)00001000
The “(1)” is a carried “1” and is ignored as this example is only dealing with 8 bits.
The answer is positive because the MSB (the most left hand bit) is a 0 (zero). If a quick mental check is made of the problem it is indeed found that “15-7 = 8”.
In fact no subtraction has taken place. Each of the steps has either converted some data or performed an addition. Yet the answer is correct 15 - 7 is 8. This example calculation was based on 8 bit numbers but it will work equally well on any other quantity of bits.

FX Series Programmable Controllers Devices in Detail 4
PLC’s can use many different systems and methods to store data. The most common have already been discussed in previous sections e.g. BCD, Binary, Decimal, Hex. These are what is known as ‘integer’ formats or ‘whole number formats’. As the titles suggest these formats use only whole numbers with no representation of fractional parts. However, there are two further formats which are becoming increasingly important and they are:
a) Floating point and
Both of these formats are in fact closely related. They both lend themselves to creating very large or very small numbers which can describe both whole and fractional components.
π 3.141 100
2π 6.283 100
π/4 7.853 10-1
π2 9.869 100
The speed of light 2.997 108 m/s Gravity, g 9.807 100 m/s2
e 2.718 100
Fixed points: Boiling point of liquid oxygen -1.8297 102 °C Melting point of ice 0.00 100 °C Triple point of water 1.00 10-2 °C Boiling point of water 1.00 102 °C
b) Scientific notation

FX Series Programmable Controllers Devices in Detail 4
This format could be called the step between the ‘integer’ formats and the full floating point formats. In basic terms Scientific Notation use two devices to store information about a number or value. One device contains a data string of the actual characters in the number (called the mantissa), while the second device contains information about the number of decimal places used in the number (called the exponent). Hence, Scientific Notation can accommodate values greater/smaller than the normal 32 bit limits, i.e. -2,147,483,648 to 2,147,483,647 where Scientific Notation limits are;
Maximums Minimums 9999 1035 9999 10-41
-9999 1035 -9999 10-41
Scientific Notation can be obtained by using the BCD, or EBCD in FX2N, instruction (FNC 18 or FNC 118) with the float flag M8023 set ON. In this situation floating point format numbers are converted by the BCD instruction into Scientific Notation - see page 5-22 for details. When using the FX2N the INT instruction (FNC 129) can be used. Scientific Notation can be converted back to floating point format by using the BIN instruction (FNC 19) with the float flag M8023 set ON - see page 5-22 for details.
The following points should be remembered about the use of Scientific Notation within appropriate FX units;
Data Register D+1 Data Register D
b0 b15 b15 b0
Sign bit (MSB) 1= Negative 0 = Positive
Sign bit (MSB) 1= Negative 0= Positive

FX Series Programmable Controllers Devices in Detail 4
Floating point format extends the abilities and ranges provided by Scientific Notation with the ability to represent fractional portions of whole numbers, for example; Performing and displaying the calculation of 22 divided by 7 would yield the following results:
a) Normal FX operation using decimal (integers) numbers would equal 3 remainder 1
b) In floating point it would equal 3.14285 (approximately)
c) In Scientific format this calculation would be equal to 3142 10 -3
So it can be seen that a greater degree of accuracy is provided by floating point numbers, i.e. through the use of larger numerical ranges and the availability of more calculable digits. Hence, calculations using floating point data have some significant advantages. Decimal data can be converted in to floating point by using the FLT, float instruction (FNC 49). When this same instruction is used with the float fag M8023 set ON, floating point numbers can be converted back to decimal. see page 5-49 for more details. The following points should be remembered about the use of Floating Point within appropriate FX units;
Additionally there is a single sign bit for the mantissa. The remaining bits of the 32 bit value, i.e. 23 bits, are used to ‘describe’ the mantissa value.
FX Data Register Contruction
b15 b0 Data register 'D+1' (16 bits) b15 b0 Data register 'D' (16 bits)
Valid ranges for floating point numbers as used in FX Main Processing Units:
Description Sign Exponent (bit pattern)
Mantissa (bit pattern) Remark
11111111111111111111111 11111111111111111111110 00000000000000000000001 00000000000000000000000
Largest number +/- 3.403 1038
Normal Float 0 or 1 11111110 00000001
Zero 0 or 1 00000000 00000000000000000000000 All digits are 0 (zero)

FX Series Programmable Controllers Devices in Detail 4
The instruction needed to convert between each number format are shown below in a diagrammatically format for quick and easy reference.
View as either integer of
Use to view the
mantissa and exponent of a floating
hexadecimal Perform all mathematical
Numbers (1 × 32 bit)
(M8023 OFF)
FLT (FNC 49)
FLT (FNC 49)
+ M8023 ON
BIN (FNC 19) + M8023 ON
Perform all mathematical operation with M8023 ON using double word functions (DADD, DSUB, DMUL, DDIV, DSQR, etc.)
Integers (16 or 32 bit) (Data registers)
Perform all mathematical operations using the special
floating point instructions using double word format
(DEADD, DESUB, DEMUL, DEDIV, DESQR, etc.)
EBCD (FNC 118)
EBIN (FNC 119)
INT (FNC 129)
Numbers (1 × 32 bit)
(C)

FX Series Programmable Controllers Devices in Detail 4

FX Series Programmable Controllers Applied Instructions 5
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Applied Instructions 5
Chapter Contents 5. Applied Instructions 5-1 5.1 Program Flow-Functions00 to 09 5-4 5.1.1 CJ (FNC 00) 5-5 5.1.2 CALL (FNC 01) 5-7 5.1.3 SRET (FNC 02) 5-8 5.1.4 IRET, EI, DI (FNC 03, 04, 05) 5-9 5.1.5 FEND (FNC 06) 5-11 5.1.6 WDT (FNC 07) 5-12 5.1.7 FOR, NEXT (FNC 08, 09) 5-13 5.2 Move And Compare - Functions 10 to 19 5-16 5.2.1 CMP (FNC 10) 5-17 5.2.2 ZCP (FNC 11) 5-17 5.2.3 MOV (FNC 12) 5-18 5.2.4 SMOV (FNC 13) 5-18 5.2.5 CML (FNC 14) 5-19 5.2.6 BMOV (FNC 15) 5-20 5.2.7 FMOV (FNC 16) 5-21 5.2.8 XCH (FNC 17) 5-21 5.2.9 BCD (FNC18) 5-22 5.2.10 BIN (FNC 19) 5-22 5.3 Arithmetic And Logical Operations -Functions 20 to 29 5-24 5.3.1 ADD (FNC 20) 5-25 5.3.2 SUB (FNC 21) 5-26 5.3.3 MUL (FNC 22) 5-27 5.3.4 DIV (FNC 23) 5-28 5.3.5 INC (FNC 24) 5-29 5.3.6 INC (FNC 24) 5-29 5.3.7 WAND (FNC 26) 5-30 5.3.8 WOR (FNC 27) 5-30 5.3.9 WXOR (FNC 28) 5-31 5.3.10 NEG (FNC 29) 5-31 5.4 Rotation And Shift - Functions 30 to 39 5-34 5.4.1 ROR (FNC 30) 5-35 5.4.2 ROR (FNC 31) 5-35 5.4.3 ROR (FNC 32) 5-36 5.4.4 ROR (FNC 33) 5-36 5.4.5 ROR (FNC 34) 5-37 5.4.6 ROR (FNC 35) 5-37 5.4.7 ROR (FNC 36) 5-38 5.4.8 ROR (FNC 37) 5-38 5.4.9 SFWR (FNC 38) 5-39 5.4.10 SFRD (FNC 39) 5-40 5.5 Data Operation - Functions 40 to 49 5-42 5.5.1 ZRST (FNC 40) 5-43 5.5.2 ROR (FNC 41) 5-43 5.5.3 ENCO (FNC 42) 5-44 5.5.4 SUM (FNC 43) 5-45 5.5.5 BON (FNC 44) 5-45 5.5.6 MEAN (FNC 45) 5-46 5.5.7 ANS (FNC 46) 5-47 5.5.8 ANR (FNC 47) 5-47 5.5.9 SQR (FNC 48) 5-48 5.5.10 FLT (FNC 49) 5-49 5.6 High Speed Processing - Functions 50 to 59 5-52 5.6.1 REF (FNC 50) 5-53 5.6.2 REFF (FNC 51) 5-53 5.6.3 MTR (FNC 52) 5-54 5.6.4 HSCS (FNC 53) 5-55 5.6.5 HSCR (FNC 54) 5-56 5.6.6 HSZ (FNC 55) 5-57 5.6.7 SPD (FNC 56) 5-60 5.6.8 SPD (FNC 56) 5-61 5.6.9 PWM (FNC 58) 5-62 5.6.10 PLSR (FNC 59) 5-63 5.7 Handy Instructions - Functions 60 to 69 5-66 5.7.1 IST (FNC 60) 5-67 5.7.2 SER (FNC 61) 5-69 5.7.3 ABSD (FNC 62) 5-70 5.7.4 INCD (FNC 63) 5-71 5.7.5 TTMR (FNC 64) 5-72 5.7.6 STMR (FNC 65) 5-72 5.7.7 TTMR (FNC 66) 5-73 5.7.8 RAMP (FNC 67) 5-73 5.7.9 ROTC (FNC 68) 5-75 5.7.10 SORT (FNC 69) 5-77 5.8 External FX I/O Devices - Functions 70 to 79 5-80 5.8.1 TKY (FNC 70) 5-81 5.8.2 HKY (FNC 71) 5-82 5.8.3 DSW (FNC 72) 5-83 5.8.4 SEGD (FNC 73) 5-84 5.8.5 SEGL (FNC 74) 5-85 5.8.6 SEGL (FNC 75) 5-87 5.8.7 SEGL (FNC 75) 5-88 5.8.8 PR (FNC 77) 5-89 5.8.9 PR (FNC 77) 5-90 5.8.10 PR (FNC 77) 5-91 5.9 External FX Serial Devices - Functions 80 to 89 5-94 5.9.1 RS (FNC 80) 5-96 5.9.2 RS (FNC 80) 5-97 5.9.3 ASCI (FNC 82) 5-99 5.9.4 HEX (FNC 83) 5-100 5.9.5 CCD (FNC 84) 5-101 5.9.6 VRRD (FNC 85) 5-102 5.9.7 VRSD (FNC 86) 5-102 5.9.8 PID (FNC 88) 5-103 5.10 External F2 Units - Functions 90 to 99 5-111 5.10.1 ANRD (FNC 91) 5-112 5.10.2 ANRD (FNC 91) 5-112 5.10.3 ANWR (FNC 92) 5-113 5.10.4 RMST (FNC 93) 5-113 5.10.5 RMMR (FNC 94) 5-114 5.10.6 RMRD (FNC 95) 5-115 5.10.7 RMMN (FNC 96) 5-115 5.10.8 BLK (FNC 97) 5-116 5.10.9 MCDE (FNC 98) 5-117 5.11 Floating Point 1 & 2 - Functions 110 to 129 5-119 5.11.1 ECMP (FNC 110) 5-121 5.11.2 ECMP (FNC 110) 5-121 5.11.3 EBCD (FNC 118) 5-122 5.11.4 EBCD (FNC 118) 5-122 5.11.5 EADD (FNC 120) 5-123 5.11.6 EAUB (FNC 121) 5-124 5.11.7 EMUL (FNC 122) 5-124 5.11.8 EDIV (FNC 123) 5-125 5.11.9 ESQR (FNC 127) 5-125 5.11.10 INT (FNC 129) 5-126 5.12 Trigonometry - FNC 130 to FNC 139 5-128 5.12.1 SIN (FNC 130) 5-129 5.12.2 COS (FNC 131) 5-130 5.12.3 TAN (FNC 132) 5-130 5.13 Data Operations 2 - FNC 140 to FNC 149 5-132 5.13.1 SWAP (FNC 147) 5-133 5.14 Real Time Clock Control - FNC 160 to FNC 169 5-136 5.14.1 TCMP (FNC 160) 5-137 5.14.2 TZCP (FNC 161) 5-138 5.14.3 TADD (FNC 162) 5-139 5.14.4 TSUB (FNC 163) 5-140 5.14.5 TRD (FNC 166) 5-141 5.14.6 TWR (FNC 167) 5-142 5.15 Gray Codes - FNC 170 to FNC 179 5-144 5.15.1 GRY (FNC 170) 5-145 5.15.2 GBIN (FNC 171) 5-145 5.16 Inline Comparisons - FNC 220 to FNC 249 5-148 5.16.1 LD compare (FNC 224 to 230) 5-149 5.16.2 AND compare (FNC 232 to 238) 5-150 5.16.3 OR compare (FNC 240 to 246) 5-151

FX Series Programmable Controllers
Applied Instructions are the ‘specialist’ instructions of the FX family of PLC’s. They allow the user to perform complex data manipulations, mathematical operations while still being very easy to program and monitor. Each applied instruction has unique mnemonics and special function numbers. Each applied instruction will be expressed using a table similar to that shown below:
CJ FNC 00 (Conditional Jump)
A method of jumping to an identified pointer position
Valid pointers from the range 0 to 63 CJ,CJP:3steps
Jump pointer P:1 step
The table will be found at the beginning of each new instruction description. The area identified as ‘Operands’ will list the various devices (operands) that can be used with the instruction. Various identification letters will be used to associate each operand with its function, i.e. D- destination, S- source, n, m- number of elements. Additional numeric suffixes will be attached if there are more than one operand with the same function.
Not all instructions and conditions apply to all PLC’s. Applicable CPU’s are identified by the boxes in the top right hand corner of the page. For more detailed instruction variations a second indicator box is used to identify the availability of pulse, single (16 bit) word and double (32 bit) word format and to show any flags that are set by the instruction.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
No modification of the instruction mnemonic is required for 16 bit operation. However, pulse operation requires a ‘P’ to be added directly after the mnemonic while 32 bit operation requires a ‘D’ to be added before the mnemonic. This means that if an instruction was being used with both pulse and 32 bit operation it would look like DP where was the basic mnemonic.
The ‘pulse’ function allows the associated instruction to be activated on the rising edge of the control input. The instruction is driven ON for the duration of one program scan. Thereafter, while the control input remains ON, the associated instruction is not active. To re-execute the instruction the control input must be turned from OFF to ON again. The FLAGS section identifies any flags that are used by the instruction. Details about the function of the flag are explained in the instructions text.


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
CJ - Conditional jump FNC 00 5-5
CALL - Call Subroutine FNC 01 5-7
SRET - Subroutine Return FNC 02 5-8
IRET - Interrupt Return FNC 03 5-9
EI - Enable Interrupt FNC 04 5-9
DI - Disable Interrupt FNC 05 5-9
FEND - First End FNC 06 5-11
WDT - Watchdog Timer FNC 07 5-12
FOR - Start of a For/Next Loop FNC 08 5-13
NEXT - End a For/Next Loop FNC 09 5-13
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

CJ FNC 00 (Conditional Jump)
Jumps to the identified pointer position
Valid pointers from the range 0 to 63 CJ, CJP:3steps Jump pointer PPP: 1 step
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
When the CJ instruction is active it forces the program to jump to an identified program marker. While the jump takes place the intervening pro-gram steps are skipped. This means they are not processed in any way. The resulting effect is to speed up the programs operational scan time.
P9 CJ
P9
Points to note:
a) Many CJ statements can reference a single pointer.
b) Each pointer must have a unique number. Using
pointer P63 is equivalent to jumping to the END instruction.
P 9
c) Any program area which is skipped, will not update
output statuses even if the input devices change. For example, the program opposite shows a situation which loads X1 to drive Y1. Assuming X1 is ON and the CJ instruction is activated the load X1, out Y1 is skipped. Now even if X1 is turned OFF Y1 will remain ON while the CJ instruction forces the program to skip to the pointer P0. The reverse situation will also apply, i.e. if X1 is OFF to begin with and the CJ instruction is driven, Y1 will not be turned ON if X1 is turned ON. Once the CJ instruction is deactivated X1 will drive Y1 in the normal manner. This situation applies to all types of outputs, e.g. SET, RST, OUT, Y, M and S devices
Y1
M8000
P0
Y0
END
d) The CJ instruction can jump to any point within the main program body or after an FEND

P10 e) A CJ instruction can be used to Jump forwards
through a program, i.e. to-wards the END instruction OR it can jump backwards towards step 0. If a backwards jump is used care must be taken not to overrun the watchdog timer setting otherwise the PLC will enter an error situation. For more information on the watchdog timer please see page 5-12.
f) Unconditional jumps can be entered by using special auxiliary coils such as M8000. In this
situation while the PLC is in RUN the program will ALWAYS execute the CJ instruction in an unconditional manner.
Using applied instructions:
Details of using CJ with other program flow instructions

CALL FNC 01 (Call sub- routine)
Executes the subroutine program starting at the identified pointer position
Valid pointers from the range 0 to 62
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ]
When the CALL instruction is active it forces the program to run the subroutine associated with the called pointer (area identified as subroutine P10). A CALL instruction must be used in conjunction with FEND (FNC 06) and SRET (FNC 02) instructions. The program jumps to the subroutine pointer (located after an FEND instruction) and processes the contents until an SRET instruction is encountered. This forces the program flow back to the line of ladder logic immediately following the original CALL instruction.
FEND
P10
SRET
Points to note:
a) Many CALL statements can reference a single subroutine.
b) Each subroutine must have a unique pointer number. Subroutine pointers can be selected
from the range P0 to P62. Subroutine pointers and the pointers used for CJ (FNC 00) instructions are NOT allowed to coincide.
c) Subroutines are not normally processed as they occur after an FEND instruction. When
they are called, care should be taken not to overrun the watchdog timer setting. For more information on watchdog timers please see page 5-12.
d) Subroutines can be nested for 5 levels including

the initial CALL instruction. As an example the program shown opposite shows a 2 level nest. When X1 is activated the program calls subroutine P11. Within this subroutine is a CALL to a second subroutine P12. When both subroutines P11 and P12 are active simultaneously, they are said to be nested. Once subroutine P12 reaches its SRET instruction it returns the program control to the program step immediately following its original CALL (see ). P11 then completes its operation, and once its SRET instruction is processed the program returns once again to the step following the CALL P11 statement (see ).

Special subroutine timers:
Details of using CALL with other program flow instructions
Mnemonic Function Operands Program steps D
SRET FNC 02 (Subroutine return)
Returns operation from a subroutine program
N/A Automatically returns to the step immediately following the CALL instruction which activated the subroutine.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
SRET signifies the end of the current subroutine and returns the program flow to the step immediately following the CALL instruction which activated the closing subroutine.
a) SRET can only be used with the CALL instruction.
b) SRET is always programmed after an FEND instruction - please see the CALL (FNC 01)
instruction for more details.

IRET FNC 03 (Interrupt return)
Forces the program to return from the active interrupt routine
N/A Automatically returns to the main program step which was being processed at the time of the interrupt call.
EI FNC 04 (Enable interrupts)
Enables interrupt inputs to be pro- cessed
N/A Any interrupt input being activated after an EI instruction and before FEND or DI instructions will be processed immediately unless it has been specifically disabled.
DI FNC 05 (Disable interrupts)
Disables the processing of interrupt routines
N/A Any interrupt input being activated after a DI instruction and before an EI instruction will be stored until the next sequential EI instruction is processed.
Identifies the beginning of an interrupt routine
A 3 digit numeric code relating to the interrupt type and operation.
An interrupt routine is a section of program which is, when triggered, operated immediately interrupting the main program flow. Once the interrupt has been processed the main program flow continues from where it was, just before the interrupt originally occurred.
Interrupts are triggered by different input conditions, sometimes a direct input such as X0 is used other times a timed interval e.g. 30 msec can be used. The availability of different interrupt types and the number operational points for each PLC type are detailed on page 4- 12, Interrupt Pointers. To program and operate interrupt routines requires up to 3 dedicated instructions (those detailed in this section) and an interrupt pointer.
An interrupt routine is specified between its own unique interrupt pointer and the first occurrence of an IRET instruction. Interrupt routines are ALWAYS programmed after an FEND instruction. The IRET instruction may only be used within interrupt routines.
IRET
IRET

The PLC has a default status of disabling interrupt operation. The EI instruction must be used to activate the interrupt facilities. All interrupts which physically occur during the program scan period from the EI instruction until the FEND or DI instructions will have their associated interrupt routines run. If these interrupts are triggered outside of the enclosed range (EI-FEND or EI-DI, see diagram below) they will be stored until the EI instruction is processed on the following scan. At this point the interrupt routine will be run.
EI
DI
FEND
FEND I301
IRET
IRET
If an individual interrupt is to be disabled its associated special M coil must be driven ON. While this coil is ON the interrupt routine will not be activated. For details about the disabling M coils see the PLC device tables in chapter 8.
Interrupts may be nested for two levels. This means that an interrupt may be interrupted during its operation. However, to achieve this, the interrupt routine which may be further interrupted must contain the EI and DI instructions; otherwise as under normal operation, when an interrupt routine is activated all other interrupts are disabled.
If more than one interrupt occurs sequentially, priority is given to the interrupt occurring first. If two or more interrupts occur simultaneously, the interrupt routine with the lower pointer number is given the higher priority.
FX PLC’s have a range of special timers which can be used within interrupt routines. For more information please see page 4-18, Timers Used in Interrupt and ‘CALL’ Subroutines.
Interrupt routines which are triggered directly by interrupt inputs, such as X0 etc., require a signal duration of approximately 200µsec, i.e. the input pulse width is equal or greater than 200µsec. When this type of interrupt is selected, the hardware input filters are automatically reset to 50µsec. (under normal operating circumstances the input filters are set to 10msec.).
Direct high speed inputs can be used to ‘catch’ short pulsed signals. When a pulse is received at an input a corresponding special M coil is set ON. This allows the ‘captured’ pulse to be used to trigger further actions, even if the original signal is now OFF. FX0, FX0S and FX0N units have this function permanently active for inputs X0 through X3 with special M coils storing the pulse data at M8056 to M8059. FX(2C) and FX2N units require the EI instruction (FNC 04) to activate pulse catch for inputs X0 through X5, with M8170 to M8175 indicating the caught pulse. Note that, if an input device is being used for another high speed function, then the pulse catch for that device is disabled.

Mnemonic Function Operands Program steps D
FEND FNC 06 (First end)
Used to indicate the end of the main program block
An FEND instruction indicates the first end of a main program and the start of the program area to be used for subroutines. Under normal operating circumstances the FEND instruction performs a similar action to the END instruction, i.e. output processing, input processing and watchdog timer refresh are all carried out on execution.
a) The FEND instruction is commonly used with CJ-P-FEND, CALL-P-SRET and I-IRET
program constructions (P refers to program pointer, I refers to interrupt pointer). Both CALL pointers/subroutines and interrupt pointers (I) subroutines are ALWAYS programmed after an FEND instruction, i.e. these program features NEVER appear in the body of a main program.
Main program Main program
X11 = ON
X11 = OFF
P 20 CJ
P 21 CJ
Main program Main program
FEND
P20 P21
X10 = ON
FEND
END END
b) Multiple occurrences of FEND instructions can be used to separate different subroutines
(see diagram above).
c) The program flow constructions are NOT allowed to be split by an FEND instruction.
d) FEND can never be used after an END instruction.


Used to refresh the watch dog timer during a program scan
N/A Can be driven at any time within the main program body
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The WDT instruction refreshes the PLC’s watchdog timer. The watchdog timer checks that the program scan (operation) time does not exceed an arbitrary time limit. It is assumed that if this time limit is exceeded there is an error at some point. The PLC will then cease operation to prevent any further errors from occurring. By causing the watchdog timer to refresh (driving the WDT instruction) the usable scan (program operation) time is effectively increased.

a) When the WDT instruction is used it will operate on every program scan so long as its input
condition has been made. To force the WDT instruction to operate for only ONE scan requires the user to program some form of interlock. FX users have the additional option of using the pulse (P) format of the WDT instruction, i.e. WDTP.

b) The watchdog timer has a default setting of 100
msec for FX PLC’s and 200 msec for FX0/FX0N/ FX2N PLC’s. This time limit may be customized to a users own requirement by editing the contents of data register D8000, the watchdog timer register.
MOV K150 D8000

FOR FNC 08 (Start of a FOR-NEXT loop)
Identifies the start position and the number of repeats for the loop
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
NEXT FNC 09 (End of a FOR-NEXT loop)
Identifies the end position for the loop
N/A Note: The FOR-NEXT loop can be nested for 5 lev- els, i.e. 5 FOR-NEXT loops are programmed within each other.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ]
The FOR and NEXT instructions allow the specification of an area of program, i.e. the program enclosed by the instructions, which is to be repeated S number of times.
NEXT
Points to note:
a) The FOR instruction operates in a 16 bit mode hence, the value of the operand S may be
within the range of 1 to 32,767. If a number between the range -32,768 and 0 (zero) is specified it is automatically replaced by the value 1, i.e. the FOR-NEXT loop would execute once.
b) The NEXT instruction has NO operand.
c) The FOR-NEXT instructions must be programmed as a pair e.g. for every FOR instruction
there MUST be an associated NEXT instruction. The same applies to the NEXT instructions, there MUST be an associated FOR instruction. The FOR-NEXT instructions must also be programmed in the correct order. This means that programming a loop as a NEXT-FOR (the paired NEXT instruction proceeds the associated FOR instruction) is NOT allowed. Inserting an FEND instruction between the FOR-NEXT instructions, i.e. FOR-FEND- NEXT, is NOT allowed. This would have the same effect as programming a FOR without a NEXT instruction, followed by the FEND instruction and a loop with a NEXT and no associated FOR instruction.
d) A FOR-NEXT loop operates for its set number of times before the main program is allowed
to finish the current program scan.
e) When using FOR-NEXT loops care should be taken not the exceed the PLC’s watchdog
timer setting. The use of the WDT instruction and/or increasing the watchdog timer value is recommended.
Operands · Mnemonic Function · Program steps S

FOR-NEXT instructions can be nested for 5 levels. This means that 5 FOR-NEXT loops can be sequentially programmed within each other. In the example a 3 level nest has been programmed. As each new FOR-NEXT nest level is encountered the number of times that loop is repeated is increased by the multiplication of all of the surrounding/previous loops.
For example, loop C operates 4 times. But within this loop there is a nested loop, B. For every completed cycle of loop C, loop B will be completely executed, i.e. it will loop D0Z times. This again applies between loops B and A.
FOR D 0Z
The total number of times that loop A will operate for ONE scan of the program will equal;
FOR K1X0
NEXT
If values were associated to loops A, B and C, e.g. 7, 6 and 4 respectively, the following number of operations would take place in ONE program scan:
Number of loop C operations = 4 times Number of loop B operations = 24 times (C × B, 4 × 6) Number of loop A operations = 168 times (C × B × A, 4 × 6 × 7)
The use of the CJ programming feature, causing the jump to P22 allows the ‘selection’ of which loop will be processed and when, i.e. if X10 was switched ON, loop A would no longer operate.

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
CMP - Compare FNC 10 5-17 ZCP - Zone Compare FNC 11 5-17 MOV - Move FNC 12 5-18 SMOV - Shift Move FNC 13 5-18 CML - Compliment FNC 14 5-19 BMOV - Block Move FNC 15 5-20 FMOV - Fill Move FNC 16 5-21 XCH - Exchange FNC 17 5-21 BCD - Binary Coded Decimal FNC 18 5-22 BIN - Binary FNC 19 5-22
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

Mnemonic Function Operands Program steps S1 S2 D CMP FNC 10 (Compare)
Compares two data values - results of are given.
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S2 ] [ D ] [ S1 ]
The data of S1 is compared to the data of S2. The result is indicated by 3 bit devices specified from the head address entered as D. The bit devices indicate: S2 is less than S1 - bit device D is ON S2 is equal to S1 - bit device D+1 is ON S2 is greater than S1 - bit device D+2 is ON
C 20 M 0
M0
C20>K100,M0=ON
M1
C20=K100,M1=ON
M2
C20>K100,M2=ON

Mnemonic Function Operands Program steps S1 S2 S3 D ZCP FNC 11 (Zone compare)
Compares a data value against a data range - results of are given.
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S2 ] [ D ] [ S1 ]
The operation is the same as the CMP instruction except a single data value (S3) is compared against a data range (S1-S2). S3 is less than S1and S2- bit device D is ON S3 is equal to or between S1 and S2 - bit device D+1 is ON S3 is greater than both S1 and S2 - bit device D+2 is ON


Moves data from one storage area to a new storage area
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation: The contents of the source device (S) is copied to the destination (D) device when the control input is active. If the MOV instruction is not driven, no operation takes place.

Program steps m1 m2 n S D
Takes elements of an existing 4 digit decimal number and inserts them into a new 4 digit number
Range 0 to 9,999 (deci- mal) or 0 to 9,999 (BCD) when M8168 is used - see note opposite

FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation 1: This instruction copies a specified number of digits from a 4 digit decimal source (S) and places them at a specified location within a destination (D) number (also a 4 digit decimal). The existing data in the destination is overwritten. The decimal manipulation mode is available to all FX and FX2C units. Key: m1 - The source position of the 1st digit to be moved m2 - The number of source digits to be moved n- The destination position for the first digit Note: The selected destination must NOT be smaller than the quantity of source data. Digit positions are referenced by number: 1= units, 2= tens, 3= hundreds, 4=thousands.

Operation 2: (Applicable units are FX units with CPU’s ver 3.07 or greater and FX2C‘s). This modification of the SMOV operation allows BCD numbers to be manipulated in exactly the same way as the ‘normal’ SMOV manipulates decimal numbers, i.e. This instruction copies a specified number of digits from a 4 digit BCD source (S) and places them at a specified location within a destination (D) number (also a 4 digit BCD number).
To select the BCD mode the SMOV instruction is coupled with special M coil M8168 which is driven ON. Please remember that this is a ‘mode’ setting operation and will be active, i.e. all SMOV instructions will operate in BCD format until the mode is reset, i.e. M8168 is forced OFF.
[ S ] [ D ]
SMOV D 1 K 4
K 2 D 2 K 3
M8000
M8168
General note:
For more information about ‘decimal’ and ‘Binary Coded Decimal’ (BCD) numbers please see the section titled ‘Interpreting Word Data’ on page 4-42 for more details.
Mnemonic Function Operands Program steps S D
CML FNC 14 (Compli- ment)
Copies and inverts the source bit pattern to a specified destination
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
A copy of each data bit within the source device (S) is inverted and then moved to a designated destination (D).
This means each occurrence of a ‘1’ in the source data will become a ‘0’ in the destination data while each source digit which is ‘0’ will become a ‘1’. If the destination area is smaller than the source data then only the directly mapping bit devices will be processed.
n m1 m2


Copies a specified block of multiple data elements to a new destination
KnX, KnY, KnM, KnS, T,C,D, V, Z (RAM) File registers,
KnY, KnM, KnS, T, C, D, V, Z (RAM) File registers, see note d)
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
BMOV D 5 D 7 K 3 [ S ] [ D ] n
A quantity of consecutively occurring data elements can be copied to a new destination. The source data is identified as a device head address (S) and a quantity of consecutive data elements (n). This is moved to the destination device (D) for the same number of elements (n).
a) If the quantity of source devices (n) exceeds the actual number of available source devices,
then only those devices which fall in the available range will be used.
b) If the number of source devices exceeds the available space at the destination location,
then only the available destination devices will be written to.
c) The BMOV instruction has a built in automatic feature to prevent overwriting errors from
occurring when the source (S - n) and destination (D -n) data ranges coincide. This is clearly identified in the following diagram: (Note: The numbered arrows indicate the order in which the BMOV is processed)

d) Using file registers as the destination devices [D]may only be performed on FX Main
Processing Units (MPUs) with a CPU version 3.07 or greater or on any FX2C or FX2N(C) MPU.


Copies a single data device to a range of destination devices
KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation: The data stored in the source device (S) is copied to every device within the destination range. The range is specified by a device head address (D) and a quantity of consecutive elements (n). If the specified number of destination devices (n) exceeds the available space at the destination location, then only the available destination devices will be written to. Please note that double word (32 bit) operation can only be performed by FX units with ver 3.07 CPU’s or greater and FX2C units.

KnY, KnM, KnS, T, C, D, V, Z Note: when using the byte XCH (i.e.M8160 is ON) D1 and D2 must be the same device other- wise a program error will occur and M8067 will be turned ON
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation 1: (Applicable units: FX and FX2C).The contents of the two destination devices D1 and D2are swapped, i.e. the complete word devices are exchanged. Ex.
Data register Before XCH After XCH
D1
XCH(P) D 1 D 17
D17
Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 147 SWAP The bytes within each word of the designated devices D1 are exchanged when ‘byte mode flag’ M8160 is ON. Please note that the mode will remain active until it is reset, i.e. M8160 is forced OFF. Ex.
![Mitsubishi Electronics FX — [ D1 ] [ D2 ] diagram (page 147)](/cdn/reader/25/2527b58be3669e56b81b7e01ffb0ac5a998fc57c23ecfe66c063198eed31d3d3/images/fig-147-3.webp)
Values are in Hex for clarity Before DXCH After DXCH
[ D1 ] [ D2 ]
DXCH(P) D 10 D 10
M8000
M8160

Mnemonic Function Operands Program steps S D BCD FNC 18 (Binary coded decimal)
Converts binary numbers to BCD equivalents / Converts floating point data to scientific format
KnX,KnY, KnM, KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D, V, Z
When using M8023 to convert data to scientific for- mat, only double word (32 bit) data registers (D) may be used. See page 4-46 for more details regarding floating point format.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation 1: (Applicable to all units) The binary source data (S) is converted into an equivalent BCD number and stored at the destination device (D). If the converted BCD number exceeds the operational ranges of 0 to 9,999 (16 bit operation) and 0 to 99,999,999 (32 bit operation) an error will occur.This instruction can be used to output data directly to a seven segment display.
BCD D 12 K2Y0
Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 118 EBCD Data (S)is converted from ‘floating point’ format to ‘scientific format’ (D). This instruction requires double word (32 bit) operation and data registers as devices (S)and (D)to operate correctly.
[ S ] [ D ]
DBCD D 42 D 20
M8000
M8023
5.2.10 BIN (FNC 19)
Mnemonic Function Operands Program steps S D BIN FNC 19 (Binary)
Converts BCD numbers to their binary equivalent / Converts scientific format data to float- ing point format
KnX, KnY, KnM, KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D, V, Z
When using M8023 to convert data to floating point format, only double word (32 bit) data reg- isters (D) may be used. See page 4-46 for more details regarding floating point format.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation 1: (Applicable to all units) The BCD source data (S) is converted into an equivalent binary number and stored at the destination device (D). If the source data is not provided in a BCD format an error will occur. This instruction can be used to read in data directly from thumbwheel switches.
BIN D 13 K2X0
Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 119 EBIN Data (S) is converted from ‘scientific format’ to ‘floating point’ format (D). This instruction requires double word (32 bit) operation and data registers as devices (S)and (D)to operate correctly.
[ S ] [ D ]
DBIN D 12 D 10
M8000
M8023

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
Page ADD - Addition FNC 20 5-25 SUB - Subtraction FNC 21 5-26 MUL - Multiplication FNC 22 5-27 DIV - Division FNC 23 5-28 INC - Increment FNC 24 5-29 DEC - Decrement FNC 25 5-29 WAND - Word AND FNC 26 5-30 WOR - Word OR FNC 27 5-30 WXOR - Word Exclusive OR FNC 28 5-31 NEG - Negation FNC 29 5-31
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.

Mnemonic Function Operands Program steps S1 S2 D
ADD FNC 20 (Addition)
The value of the two source devices is added and the result stored in the desti- nation device
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D, V, Z
When using M8023 to add floating point data, only double word (32 bit) data registers (D) or constants (K/H) may be used. See page 4-46 for more details regarding floating point format.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS
Zero M8020 Borrow M8021 Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S2 ]
The data contained within the source devices (S1,S2) is combined and the total is stored at the specified destination device (D).
D 14
Points to note:
a) All calculations are algebraically processed, i.e. 5 + (-8)= -3.
b) The same device may be used as a source (S1 or S2) and as the destination (D). If this is
the case then the ADD instruction would actually operate continuously. This means on every scan the instruction would add the result of the last scan to the second source device. To prevent this from happening the pulse modifier should be used or an interlock should be programmed.
c) If the result of a calculation is “0" then a special auxiliary flag, M8020 is set ON.
d) If the result of an operation exceeds 32,767 (16 bit limit) or 2,147,483,647 (32 bit limit) the
carry flag, M8022 is set ON. If the result of an operation exceeds -32,768 or -2,147,483,648 the borrow flag, M8021 is set ON. When a result exceeds either of the number limits, the appropriate flag is set ON (M8021 or M8022) and a portion of the carry/borrow is stored in the destination device. The mathematical sign of this stored data is reflective of the number limit which has been exceeded, i.e. when -32,768 is exceeded negative numbers are stored in the destination device but if 32,767 was exceeded positive numbers would be stored at D.
e) If the destination location is smaller than the obtained result, then only the portion of the
result which directly maps to the destination area will be written, i.e if 25 (decimal) was the result, and it was to be stored at K1Y4 then only Y4 and Y7 would be active. In binary terms this is equivalent to a decimal value of 9 a long way short of the real result of 25!
Continued over the page

Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 120 EADD. When ‘floating point mode flag’ M8023 is active, i.e. ON, DADD and DADDP instructions can be used to perform floating point additions. When M8023 is reset, i.e. OFF floating point manipulation will not occur. Constants (K/H) and floating point numbers (stored in double data registers D) can be added in any configuration. The constants (K/H) will automatically be converted to the ‘floating point format’ for the addition operation. Answers for an operation can only be stored in double (32 bit) data registers. Items a) and b) above are also valid for this operating mode.
[ S1 ] [ D ]
D 4 [ S2 ]
DADDP
H3F D 4
M8000
M8023
FX2N Support for floating point operations
- See section 5.11
Program steps S1 S2 D
SUB FNC 21 (Subtract)
One source device is subtracted from the other - the result is stored in the destination device
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D, V, Z
When using M8023 to subtract floating point data, only double word (32 bit) data registers (D) or constants (K/H) may be used. See page 4-46 for more details regarding floating point format.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS
Zero M8020 Borrow M8021 Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S2 ]
The data contained within the source device, S2 is subtracted from the contents of source device S1. The result or remainder of this calculation is stored in the destination device D. Note: the ‘Points to note’, under the ADD instruction (previous page) can also be similarly applied to the subtract instruction.
D 14
Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 121 ESUB. The information regarding ‘Operation2:’ of the ADD instruction apply similarly to this second operation of the SUB instruction (with the exception of a subtraction being performed instead of an addition). Again, only constants and double data words can be manipulated with only DSUB, DSUBP instruction formats being valid.
Operands · Mnemonic Function

Mnemonic Function Operands Program steps S1 S2 D
MUL FNC 22 (Multiplica -tion)
Multiplies the two source devices together the result is stored in the destination device
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
KnY,KnM,KnS, T, C, D, Z(V) Note: Z(V) may NOT be used for 32 bit oper- ation
See page 4-46 for more details regarding floating point format.
When using M8023 to subtract floating point data, only double word (32 bit) data registers (D) or constants (K/H) may be used.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation 1: (Applicable to all units) The contents of the two source devices (S1, S2) are multiplied together and the result is stored at the destination device (D). Note the normal rules of algebra apply.
[ S2 ]
MUL D 0 D 2
D 4
Points to note: a) When operating the MUL instruction in 16bit mode, two 16 bit data sources are multiplied
together. They produce a 32 bit result. The device identified as the destination address is the lower of the two devices used to store the 32 bit result. Using the above example with some test data: 5 (D0) × 7 (D2) = 35 - The value 35 is stored in (D4, D5) as a single 32 bit word. b) When operating the MUL instruction in 32 bit mode, two 32 bit data sources are multiplied
together. They produce a 64 bit result. The device identified as the destination address is the lower of the four devices used to store the 64 bit result. c) If the location of the destination device is smaller than the obtained result, then only the
portion of the result which directly maps to the destination area will be written, i.e if a result of 72 (decimal) is to be stored at K1Y4 then only Y7 would be active. In binary terms this is equivalent to a decimal value of 8, a long way short of the real result of 72!
Viewing 64 bit numbers
Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 122 EMUL. When ‘floating point mode flag’ M8023 is active, i.e. ON, DMUL and DMULP instructions can be used to perform floating point multiplications. When M8023 is reset, i.e. OFF floating point manipulation will not occur. Constants (K/H) and floating point numbers (stored in double data registers D) can be used in any configuration. The constants (K/H) will automatically be converted to the ‘floating point format’ for the operation. Answers for an operation are stored (completely) in one pair of double (32 bits) data registers and not 2 pairs (64 bits) as used in ‘Operation 1:’. The normal rules of algebra apply to floating point multiplication.
[ S1 ] [ D ] D 4 [ S2 ]
M8000
M8023

Mnemonic Function Operands Program steps S1 S2 D
DIV FNC 23 (Division)
Divides one source value by another the result is stored in the destination device
K, H, KnX, KnY, KnM, KnS,T, C, D, V, Z
KnY, KnM, KnS, T, C, D, Z(V)
See page 4-46 for more details regarding floating point format.
When using M8023 to subtract floating point data, only double word (32 bit) data registers (D) or constants (K/H) may be used.used to perform
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S2 ]
The primary source (S 1) is divided by the secondary source (S2). The result is stored in the destination (D). Note the normal rules of algebra apply.
D 4
Points to note:
a) When operating the DIV instruction in 16bit mode, two 16 bit data sources are divided into
each other. They produce two 16 bit results. The device identified as the destination address is the lower of the two devices used to store the these results. This storage device will actually contain a record of the number of whole times S2 will divide into S1 (the quotient). The second, following destination register contains the remained left after the last whole division (the remainder). Using the previous example with some test data:
51 (D0) ÷ 10 (D2) = 5(D4) 1(D5) This result is interpreted as 5 whole divisions with 1 left over (5 × 10 + 1 = 51).
b) When operating the DIV instruction in 32 bit mode, two 32 bit data sources are divided into
each other. They produce two 32 bit results. The device identified as the destination address is the lower of the two devices used to store the quotient and the following two devices are used to store the remainder, i.e. if D30 was selected as the destination of 32 bit division operation then D30, D31 would store the quotient and D32, D33 would store the remainder. If the location of the destination device is smaller than the obtained result, then only the portion of the result which directly maps to the destination area will be written. If bit devices are used as the destination area, no remainder value is calculated.
c) If the value of the source device S2 is 0 (zero) then an operation error is executed and the
operation of the DIV instruction is cancelled.
information regarding ‘Operation2:’ of the MUL instruction apply similarly to this second operation of the DIV instruction (with the exception of a division being performed instead of a multiplication). Again, only constants and double data words can be manipulated with only DDIV, DDIVP instruction formats being valid. Answers for an operation are stored (completely) in one pair of double (32 bits) data registers, i.e. answers are not split in to quotient and remainder as in ‘Operation 1:’. The normal rules of algebra apply to floating point division.


The designated device is incremented by 1 on every execution of the instruction
KnY, KnM, KnS, T, C, D, V, Z Standard V,Z rules apply for 32 bit operation
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
On every execution of the instruction the device specified as the destination D, has its current value incremented (increased) by a value of 1. In 16 bit operation, when +32,767 is reached, the next increment will write a value of -32,768 to the destination device. In 32 bit operation, when +2,147,483,647 is reached the next increment will write a value of - 2,147,483,648 to the destination device. In both cases there is no additional flag to identify this change in the counted value.

The designated device is decremented by 1 on every execution of the instruction
KnY, KnM, KnS, T, C, D, V, Z Standard V,Z rules apply for 32 bit operation
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
On every execution of the instruction the device specified as the destination D, has its current value decremented (decreased) by a value of 1. In 16 bit operation, when -32,768 is reached the next increment will write a value of +32,767 to the destination device. In 32 bit operation, when -2,147,483,648 is reached the next increment will write a value of +2,147,483,647 to the destination device. In both cases there is no additional flag to identify this change in the counted value.


A logical AND is performed on the source devices - result stored at destination
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ D ] [ S2 ]
The bit patterns of the two source devices are analyzed (the contents of S2is compared against the contents of S1). The result of the logical AND analysis is stored in the destination device (D). The following rules are used to determine the result of a logical AND operation. This takes place for every bit contained within the source devices: General rule: (S1) Bit n WAND (S2) Bit n = (D) Bit n 1 WAND 1 = 1 0 WAND 1 = 0 1 WAND 0 = 0 0 WAND 0 = 0

A logical OR is performed on the source devices - result stored at destination
K,H, KnX,KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ D ] [ S2 ]
The bit patterns of the two source devices are analyzed (the contents of S2is compared against the contents of S1). The result of the logical OR analysis is stored in the destination device (D). The following rules are used to determine the result of a logical OR operation. This takes place for every bit contained within the source devices: General rule: (S1) Bit n WOR (S2) Bit n = (D) Bit n 1 WOR 1 = 1 0 WOR 1 = 1 1 WOR 0 = 1 0 WOR 0 = 0


A logical XOR is performed on the source devices - result stored at destination
K, H KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ D ] [ S2 ]
The bit patterns of the two source devices are analyzed (the contents of S2 is compared against the contents of S1). The result of the logical XOR analysis is stored in the destination device (D). The following rules are used to determine the result of a logical XOR operation. This takes place for every bit contained within the source devices: General rule: (S1)Bit n WXOR (S2)Bit n = (D)Bit n 1 WXOR 1 = 0 0 WXOR 1 = 1 1 WXOR 0 = 1 0 WXOR 0 = 0

FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The bit pattern of the selected device is inverted. This means any occurrence of a ‘1’ becomes a ‘0’ and any occurrence of a ‘0’ will be written as a ‘1’. When this is complete, a further binary 1 is added to the bit pattern. The result is the total logical sign change of the selected devices contents, e.g. a positive number will become a negative number or a negative number will become a positive.


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
ROR - Rotation Right FNC 30 5-35
ROL - Rotation Left FNC 31 5-35
RCR - Rotation Right with Carry FNC 32 5-36
RCL - Rotation Left with Carry FNC 33 5-36
SFTR - (Bit) Shift Right FNC 34 5-37
SFTL - (Bit) Shift Left FNC 35 5-37
WSFR - Word Shift Right FNC 36 5-38
WSFL - Word Shift Left FNC 37 5-38
SFWR - Shift Register Write FNC 38 5-39
SFRD - Shift Register Read FNC 39 5-40
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

Mnemonic Function Operands Program steps D n
ROR FNC 30 (Rotation right)
The bit pattern of the destination device is rotated ‘n’ places to the right on every execution
KnY, KnM, KnS, T, C, D, V, Z Note: 16 bit operation Kn=K4, 32 bit operation Kn=K8
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ] [ n ] X0
The bit pattern of the destination device (D) is rotated n bit places to the right on every operation of the instruction. The status of the last bit rotated is copied to the carry flag M8022. The example shown left is based on the instruction noted above it, where the bit pattern represents the contents of D0.
1 0
After 1 rotation MSB
0 1 0
M8022
5.4.2 ROL (FNC 31)
Program steps S D
ROL FNC 31 (Rotation left)
The bit pattern of the destination device is rotated ‘n’ places to the left on every execution
KnY, KnM, KnS, T, C, D, V, Z Note: 16 bit operation Kn= K4, 32 bit operation Kn= K8
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
K 4 [ n ] ROL
The bit pattern of the destination device (D) is rotated n bit places to the left on every operation of the instruction. The status of the last bit rotated is copied to the carry flag M8022. The example shown left is based on the instruction noted above it, where the bit pattern represents the contents of D0.
1 0
MSB
1 0 1
M8022

Mnemonic Function Operands Program steps D n
RCR FNC 32 (Rotation right with carry)
The contents of the destination device are rotated right with 1 bit extracted to the carry flag
KnY, KnM, KnS, T, C, D, V, Z Note: 16 bit operation Kn= K4, 32 bit operation Kn=K8
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ] [ n ] X0
The bit pattern of the destination device (D)is rotated n bit places to the right on every operation of the instruction. The status of the last bit rotated is moved into the carry flag M8022. On the following operation of the instruction M8022 is the first bit to be moved back into the destination device. The example shown left is based on the instruction noted above it, where the bit pattern represents the contents of D0.
1 0
0 1 0 0 0
5.4.4 RCL (FNC 33)
Mnemonic Function Operands Program steps S D
RCL FNC 33 (Rotation left with carry)
The contents of the destination device are rotated left with 1 bit extracted to the carry flag
KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
K 4 [ n ] RCL
The bit pattern of the destination device (D)is rotated n bit places to the left on every operation of the instruction. The status of the last bit rotated is moved into the carry flag M8022. On the following operation of the instruction M8022 is the first bit to be moved back into the destination device. The example shown left is based on the instruction noted above it, where the bit pattern represents the contents of D0.
1 0
1 0 1 1 1
Carry · Carry

Program steps S D n1 n2
SFTR FNC 34 (Bit shift right)
The status of the source devices are copied to a controlled bit stack moving the existing data to the right
X, Y, M, S Y, M, S K,H, Note: FX users: n2 ≤ n1 ≤ 1024 FX0,FX0N users: n2 ≤ n1 ≤ 512
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[S] [D] [n1] [n2]
The instruction copies n2 source devices to a bit stack of length n1. For every new addition of n2 bits, the existing data within the bit stack is shifted n2 bits to the right. Any bit data moving to a position exceeding the n1 limit is diverted to an overflow area. The bit shifting operation will occur every time the instruction is processed unless it is modified with either the pulse suffix or a controlled interlock.
SFTR X 0 M 0 K 16 K 4
M15M14 M13M12 M11M10 M9 M8 M7 M6 M5 M4 M3 M2 M1 M0
Program steps S D n1 n2
SFTL FNC 35 (Bit shift left)
The status of the source devices are copied to a controlled bit stack moving the existing data to the left
X, Y, M, S Y, M, S K,H, Note: FX users: n2 ≤ n1 ≤ 1024 FX0,FX0N users: n2 ≤ n1 ≤ 512
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[S] [D] [n1] [n2]
The instruction copies n2 source devices to a bit stack of length n1. For every new addition of n2 bits, the existing data within the bit stack is shifted n2bits to the left. Any bit data moving to a position exceeding the n1 limit is diverted to an overflow area. The bit shifting operation will occur every time the instruction is processed unless it is modified with either the pulse suffix or a controlled interlock.
X12 X11 X10
Y5 Y4 Y3 Y10 Y7 Y6 Y13 Y12 Y11

Program steps S D n1 n2
WSFR FNC 36 (Word shift right)
The value of the source devices are copied to a controlled word stack moving the existing data to the right
KnX, KnY, KnM,KnS, T, C, D
KnY,KnM, KnS, T, C, D
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
[ n1 ] [ n2 ]
The instruction copies n2 source devices to a word stack of length n1. For each addition of n2words, the existing data within the word stack is shifted n2words to the right. Any word data moving to a position exceeding the n1limit is diverted to an overflow area. The word shifting operation will occur every time the instruction is processed unless it is modified with either the pulse suffix or a controlled interlock. Note: when using bit devices as source (S) and destination (D) the Kn value must be equal.
D 0
(1) (2) (3) (4) (5)
13 17 21 25 3
-
10 14 18 22 0
10 14 18 22 D 3 D 2 D 1 D 0
13 17 21 25
-
D25 D24 D23 D22 D18 D21 D14 D17 D13 D12 D11 D10
(1) (2) (3) (4)
Program steps S D n1 n2
WSFL FNC 37 (Word shift left)
The value of the source devices are copied to a controlled word stack moving the existing data to the left
KnX, KnY, KnM,KnS, T, C, D
KnY,KnM, KnS, T, C, D
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
[ n1 ] [ n2 ]
The instruction copies n2 source devices to a word stack of length n1. For each addition of n2words, the existing data within the word stack is shifted n2words to the left. Any word data moving to a position exceeding the n1 limit is diverted to an overflow area. The word shifting operation will occur every time the instruction is processed unless it is modified with either the pulse suffix or a controlled interlock. Note: when using bit devices as source (S) and destination (D) the Kn value must be equal.
D 0
(1) (2) (3) (4) (5)
25 21 17 13 3
-
22 18 14 10 0 D 3 D 2 D 1 D 0
25 21 17 13
-
22 18 14 10
D13 D12 D11 D10 D14 D17 D18 D21 D25 D24 D23 D22
(1) (2) (3) (4)

Mnemonic Function Operands Program steps S D N
SFWR FNC 38 (Shift register write)
This instruction creates and builds a FIFO stack n devices long -must be used with SFRD FNC 39
K, H, KnX, KnY, KnM,KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D,
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
The contents of the source device (S) are written to the FIFO stack. The position of insertion into the stack is automatically calculated by the PLC. The destination device (D) is the head address of the FIFO stack. The contents of D identify where the next record will be stored (as an offset from D+1).
D 0
D 0 D 10 D 9 D 8 D 7 D 6 D 5 D 4 D 3 D 2 D 1 [ S ] = 10
If the contents of D exceed the value “n-1” (n is the length of the FIFO stack) then insertion into
the FIFO stack is stopped. The carry flag M8022 is turned ON to identify this situation.
a) FIFO is an abbreviation for ‘First-In/ First-OUT’.
b) Although n devices are assigned for the FIFO stack, only n-1 pieces of information may be
written to that stack. This is because the head address device (D) takes the first available register to store the information regarding the next data insertion point into the FIFO stack.
c) Before starting to use a FIFO stack ensure that the contents of the head address register
(D) are equal to ‘0’ (zero).
d) This instruction should be used in conjunction with SFRD FNC 39. The n parameter in both
instructions should be equal.
[ n ] · [n] · (3) (2) (1)

Mnemonic Function Operands Program steps S D n
SFRD FNC 39 (Shift register read)
This instruction reads and reduces FIFO stack- must be used with SFWR FNC 38
KnY, KnM, KnS, T, C, D, KnY, KnM,KnS, T, C, D
KnY, KnM, KnS, T, C, D, KnY, KnM,KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
The source device (S) identifies the head address of the FIFO stack. Its contents reflect the last entry point of data on to the FIFO stack, i.e. where the end of the FIFO is (current position). This instruction reads the first piece of data from the FIFO stack (register S+1), moves all of the data within the stack ‘up’ one position to fill the read area and decrements the contents of the FIFO head address (S) by 1. The read data is written to the destination device (D). When the contents of the source device (S) are equal to ‘0’ (zero), i.e. the FIFO stack is empty, the flag M8020 is turned ON.
D 1
[D] = 10 [n]
D 20 D 10 D 9 D 8 D 7 D 6 D 5 D 4 D 3 D 2 D 1
a) FIFO is an abbreviation for ‘First-In/ First-OUT’.
b) Only n-1 pieces of data may be read from a FIFO stack. This is because the stack requires
that the first register, the head address (S) is used to contain information about the current length of the FIFO stack.
c) This instruction will always read the source data from the register S+1.
d) This instruction should be used in conjunction with SFWR FNC 38. The n parameter in both
instructions should be equal.
[ n ]

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
ZRST - Zone Reset FNC 40 5-43
DECO - Decode FNC 41 5-43
ENCO - Encode FNC 42 5-44
SUM - The Sum Of Active Bits FNC 43 5-45
BON - Check Specified Bit Status FNC 44 5-45
MEAN - Mean FNC 45 5-46
ANS - (Timed) Annunciator Set FNC 46 5-47
ANR - Annunciator Reset FNC 47 5-47
SQR - Square Root FNC 48 5-48
FLT - Float, (Floating Point) FNC 49 5-49
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function.
- An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page


Used to reset a range of like devices in one operation
Y, M,S, T, C, D Note: D1must be less than or equal ( ≤ ) to D2. Standard and High speed counters cannot be mixed.
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The range of devices, inclusive of those specified as the two destinations are reset, i.e. for data devices the current value is set to 0 (zero) and for bit elements, the devices are turned OFF, i.e. also set to 0 (zero).
The specified device range cannot contain mixed device types, i.e. C000 specified as the first destination device (D1) cannot be paired with T199 as the second destination device (D2). When resetting counters, standard and high speed counters cannot be reset as part of the same range. If D1is greater than (>) D2 then only device D1 is reset.
Program steps S D n
DECO FNC 41 (Decode)
Source data value Q identifies the Qth bit of the destination device which will be turned ON
K, H, X, Y, M,S, T, C, D, V, Z
K, H, Note: D= Y,M,S then n range = 1-8 D= T,C,D then n range = 1-4 n= 0, then no processing
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
Source data is provided by a combination of operands S and n. Where S specifies the head address of the data and n, the number of consecutive bits. The source data is read as a single number (binary to decimal conversion) Q. The source number Q is the location of a bit within the destination device (D) which will be turned ON (see example opposite). When the destination device is a data device n must be within the range 1 to 4 as there are only 16 available destination bits in a single data word. All unused data bits within the word are set to 0.
M 10 K 3
4 2 1 0 1 1 X 2 X 1 X 0
0 1 0 7. 6. 5. 4. 3. 2. 1. 0.

Program steps S D n
ENCO FNC 42 (Encode)
Then location of the highest active bit is stored as a numerical position from the head address
X, Y, M, S, T, C, D, V, Z
K, H, Note: S=X, Y, M, S then n range=1-8 S= T,C,D then n range = 1-4 n = 0, then no processing
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
The highest active bit within the readable range has its location noted as a numbered offset from the source head address (S). This is stored in the destination register (D).
M 10
D 10 K 3
0 1 0 7. 6. 5. 4. 3. 2. 1. 0.
0 1 1 D10
4 2 1 . .
a) The readable range is defined by the largest number storable in a binary format within the
number of destination storage bits specified by n, i.e. if n was equal to 4 bits a maximum number within the range 0 to 15 can be written to the destination device. Hence, if bit devices were being used as the source data, 16 bit devices would be used, i.e. the head bit device and 15 further, consecutive devices.
b) If the stored destination number is 0 (zero) then the source head address bit is ON, i.e. the
active bit has a 0 (zero) offset from the head address. However, if NO bits are ON within the source area, 0 (zero) is written to the destination device and an error is generated.
c) When the source device is a data or word device n must be taken from the range 1 to 4 as
there are only 16 source bits available within a single data word.

Program steps S D
SUM FNC 43 (Sum of active bits)
The number (quantity) of active bits in the source data is stored in the destination device
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
The number of active (ON) bits within the source device (S), i.e. bits which have a value of “1" are counted. The count is stored in the destination register (D). If a double word format is used, both the source and destination devices use 32 bit, double registers. The destination device will always have its upper 16 bits set to 0 (zero) as the counted value can never be more than 32. If no bits are ON then zero flag, M8020 is set.
D 2
D 0
0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 b15 b0
0 1 0 0 1
8 4 2 1 . .
Mnemonic Function Operands Program steps S D n
BON FNC 44 (Check specified bit status)
The status of the specified bit in the source device is indicated at the destination
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
Y, M, S K,H, Note: 16 bit operation n=0 to 15 32 bit operation n=0 to 31
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
A single bit position (n) is specified from within a source device/area (S). n could be regarded as a specified offset from the source head address (S), i.e. 0 (zero) being the first device (a 0 offset) where as an offset of 15 would actually be the 16th device. If the identified bit becomes active, i.e. ON, the destination device (D) is activated to “flag” the new status. The destination device could be said to act as a mirror to the status of the selected bit source.
D 10
M 0 K 15
D 10
1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 b15 b0
b15 = 1, M0 = 1
0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 b15 = 0, M0 = 0
Operands · Mnemonic Function · [ n ]

Mnemonic Function Operands Program steps S D n
MEAN FNC 45 (Mean)
Calculates the mean of a range of devices
KnX, KnY, KnM, KnS, T, C, D
KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
The range of source data is defined by operands Sand n. S is the head address of the source data and n specifies the number of consecutive source devices used. The value of all the devices within the source range is summed and then divided by the number of devices summed, i.e. n. This generates an integer mean value which is stored in the destination device (D). The remainder of the calculated mean is ignored.
D 0
D 10 K 3
D= = ( S0 + S1 + < + Sn )
n Σ S S0
D10= (D0) + (D1) + (Dn)
If the source area specified is actually smaller than the physically available area, then only the available devices are used. The actual value of n used to calculate the mean will reflect the used, available devices. However, the value for n which was entered into the instruction will still be displayed. This can cause confusion as the mean value calculated manually using this original n value will be different from that which is displayed. If the value of nis specified outside of the stated range (1 to 64) an error is generated.


This instruction starts a timer. Once timed out the selected annunciator flag is set ON
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction, when energized, starts a timer (S) for n,100 msec. When the timer completes its cycle the assigned annunciator (D) is set ON. If the instruction is switched OFF during or after completion of the timing cycle the timer is automatically reset. However, the current status of the annunciator coil remains unchanged.

The lowest active annunciator is reset on every operation of this instruction
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Annunciators which have been activated are sequentially reset one-by-one, each time the ANR instruction is operated. If the ANR instruction is driven continuously it will carry out its resetting operation on every program scan unless it is modified by the pulse, P prefix or by a user defined program interlock.

Mnemonic Function Operands Program steps S D
SQR FNC 48 (Square root)
Performs a mathematical square root e.g.:
When using M8023 in float mode, only double word (32bit) data can be processed. See page 4- 46 for more details regarding float- ing point.
PULSE-P
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020 Borrow M8021
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
This instruction performs a square root operation on source data (S) and stores the result at destination device (D). The operation is conducted entirely in whole integers rendering the square root answer rounded to the lowest whole number. For example, if (S) = 154, then (D) is calculated as being 12. M8020 is set ON when the square root operation result is equal to zero. Answers with rounded values will activate M8021.
D 2
M8023
D 30 D5 DSQR
M8000
M8023
Operation 2: This function is equivalent to FNC 127 ESQR This operation is similar to Operation 1. However, it is only activated when the mode setting float flag, M8023 is used. This then allows the SQR instruction to process answers in floating point format. The source data (S) must either be supplied in floating point format for data register use, or it can be supplied as a constant (K,H). When constants are used as a source, they are automatically converted to floating point format. Operation 2 is only valid for double word (32 bit) operation, hence both (S) and (D) will be 32 bit values and the SQR instruction will be entered as DSQR or DSQRP.
General note:
Performing any square root operation (even on a calculator) on a negative number will result in an error. This will be identified by special M coil M8067 being activated:
-168 = Error and M8067 will be set ON
This is true for both operating modes.

Mnemonic Function Operands Program steps S D
FLT FNC 49 (Floating point)
Used to convert data to and from floating point format
M8023 = OFF data is converted from decimal to floating point format
M8023 = ON data is converted from floating point format to decimal format
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
When the float instruction is used without the float flag (M8023 = OFF) the source data (S) is converted in to an equivalent value stored in float format at the destination device (D). Please note that two consecutive devices (D and D+1) will be used to store the converted float number. This is true regardless of the size of the source data (S), i.e. whether (S) is a single device (16 bits) or a double device (32 bits) has no effect on the number of destination devices (D) used to store the floating point number. Examples:
D 2
M8023
D120 D100 FLT
M8000
M8023
Floating point destination value (D)
-2.67 × 104
4.04 × 102
Operation 2: (Applicable units: FX(2C)) This function is equivalent to FNC 129 INT. When the float instruction is performed and the float flag M8023 is ON, the float operation will be conducted in reverse to Operation 1. Any floating point format number stored at source (S) will be converting to its decimal equivalent and stored at destination (D).
Continued over the page...
Decimal source data

a) When floating point numbers are used the zero, borrow and carry flags (M8020, M8021 and
M8022 respectively) operate at the following times; M8020, Zero: is activated when the result is Zero. M8021, Borrow: is activated when the result is smaller than the smallest possible number. The result is forced to equal the smallest number and the associated flag is set ON. M8022, Carry: is activated when the result is larger than the largest possible number. The result is forced to equal the largest number and the associated flag is set ON.
b) Floating point numbers always
occupy 32 consecutive bits, i.e. 2 consecutive data registers. When converting between float and decimal numbers please al-low enough destination devices, i.e.
Negative Value Very small
Borrow M8021 Carry M8022
Number of destination registers (D)
FLT
OFF 1 (S) 2 (D, D+1) Convert to floating point
FLT (INT) ON 2 (S, S+1) 1 (D) Convert to decimal
OFF 2 (S, S+1) 2 (D, D+1) Convert to floating point
DFLT (DINT) ON 2 (S, S+1) 2 (D, D+1) Convert to decimal
General note:
For more information about float and scientific notations please see Chapter 4, Advanced Devices, page 4-46

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
REF - Refresh FNC 50 5-53
REFF - Refresh and filter adjust FNC 51 5-53
MTR - Input matrix FNC 52 5-54
HSCS - High speed counter set FNC 53 5-55
HSCR - High speed counter reset FNC 54 5-56
HSZ - High speed counter
zone compare FNC 55 5-57
SPD - Speed detect FNC 56 5-60
PLSY - Pulse Y output FNC 57 5-61
PWM - Pulse width modulation FNC 58 5-62
PLSR - Ramp Pulse output FNC 59 5-63
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page


Forces an immediate update of inputs or outputs as specified
X, Y Note: D should always be a multiple of 10, i.e. 00, 10, 20, 30 etc.
K, H Note: n should always be a multiple of 8, i.e. 8, 16, 24, 32 etc.
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation: Standard PLC operation processes output and input status between the END instruction of one program scan and step 0 of the following program scan. If an immediate update of the I/O device status is required the REF instruction is used. The REF instruction can only be used to update or refresh blocks of 8 (n) consecutive devices. The head address of the refreshed devices should always have its last digit as a 0 (zero), i.e. in units of 10.
K 8 REF
a time equivalent to the filter setting, while outputs will delay for their set energized time.
![Mitsubishi Electronics FX — [ D ] diagram (page 179)](/cdn/reader/25/2527b58be3669e56b81b7e01ffb0ac5a998fc57c23ecfe66c063198eed31d3d3/images/fig-179-2.webp)
Inputs are refreshed, and their input filters are reset to the newly designated value
K, H, Note: n= 0 to 60 msec (0 = 50µs) X000 to X007 (X000 to X017 for FX2N) are automatically designated when using this instruction
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation: PLC’s are provided with input filters to overcome problems generated by mechanical switch gear. However, as this involves ensuring a steady input signal is received for a fixed time duration, the use of input filters slows down the PLC response times. For high speed applications, especially where solid state switching provides the input signal, input filter times may be reduced. The default setting for the input filters is approximately 10 msec. Using this instruction input filter times of 0 to 60 msec may be selected. The setting ‘0’ (zero) is actually 50 µsec. This is the minimum available setting. It is automatically selected when direct input, interrupts or high speed counting functions are used. The REFF instruction needs to be driven for each program scan if it is to be effective, otherwise, the standard 10 msec filter time is used.
[ n ] · [ n ]


Multiplexes a bank of inputs into a number of sets of devices. Can only be used ONCE
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction allows a selection of 8 consecutive input devices (head address S) to be used multiple (n) times, i.e. each physical input has more than one, separate and quite different (D1) signal being processed. The result is stored in a matrix-table (head address D2).
a) The MTR instruction involves high speed input/output switching. For this reason this
instruction is only recommended for use with transistor output modules.
b) For the MTR instruction to operate correctly, it must be driven continuously. It is
recommended that special auxiliary relay M8000, the PLC RUN status flag, is used. After the completion of the first full reading of the matrix, operation complete flag M8029 is turned ON. This flag is automatically reset when the MTR instruction is turned OFF.
c) Each set of 8 input signals are grouped into a ‘bank’ (there are n number of banks).
d) Each bank is triggered/selected by a dedicated output (head address D1). This means the
quantity of outputs from D1, used to achieve the matrix are equal to the number of banks n. As there are now additional inputs entering the PLC these will each have a status which needs recording. This is stored in a matrix-table. The matrix-table starts at the head address D2. The matrix construction mimics the same 8 signal by n bank configuration. Hence, when a certain input in a selected bank is read, its status is stored in an equivalent position within the result matrix-table.
e) The matrix instruction operates on an interrupt format, processing each bank of inputs
every 20msec. This time is based on the selected input filters being set at 10msec. This wouldresultinan8bankmatrix, i.e. 64inputs(8inputs´8banks) beingreadin160msec.
If high speed inputs (ex. X0) is specified for operand S, the reading time of each bank
becomes only 10msec, i.e. a halving of the reading speed. However, additional pull down resistors are required on the drive outputs to ensure the high speed reading does not detect any residual currents from the last operation. These should be placed in parallel to the input bank and should be of a value of approximately 3.3kΩ, 0.5W. For easier use, high speed inputs should not be specified at S.

X0 X1 X2 X3 X4 X5 X6 X7 24V 0V S/S

f) Because this instruction uses a series of
multiplexed signals it requires a certain amount of ‘hard wiring’ to operate. The example wiring diagram to the right depicts the circuit used if the previous example instruction was programmed. As a general precaution to aid successful operation diodes should be places after each input device (see diagram opposite). These should have a rating of 0.1A, 50V.

When output Y20 is ON only those inputs in the first bank are read. These results are then stored; in this example, auxiliary coils M30 to M37. The second step involves Y20 going OFF and Y21 coming ON. This time only inputs in the second bank are read. These results are stored in devices M40 to M47. The last step of this example has Y21 going OFF and Y22 coming ON. This then allows all of the inputs in the third bank to be read and stored in devices M50 to M57. The processing of this instruction example would take 20 × 3 = 60msec.

Sets the selected output when the specified high speed counter value equals the test value
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
Interrupt point- ers I010 to I060 can be set on FX units from CPU ver 3.07 and FX2C units
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The HSCS set, compares the current value of the selected high speed counter (S2)against a selected value (S1). When the counters current value changes to a value equal to S1the device specified as the destination (D)is set ON.The example above shows that Y10 would be set ON only when C255’s value stepped from 99-100 OR 101-100. If the counters current value was forced to equal 100, output Y10 would NOT be set ON.
a) It is recommended that the drive input used for the high speed counter functions; HSCS,
HSCR, HSCZ is the special auxiliary RUN contact M8000.
g) Example Operation

b) If more than one high speed counter function is used for a single counter the selected flag
devices (D) should be kept within 1 group of 8 devices, i.e. Y0-7, M10-17.
c) All high speed counter functions use an interrupt process, hence, all destination devices (D)
are updated immediately.
FX0,FX0N users - Max. 4 simultaneously active HSCS/R instructions. FX users Max. 6 simultaneously active HSCS/R and HSZ instructions. Please remember that the use of high speed counter functions has a direct impact on the maximum allowable counting speed! See page 4-22 for further details.
FX(2C) and FX2N MPUs can use interrupt pointers I010 through I060 (6 points) as destination devices (D). This enables interrupt routines to be triggered directly when the value of the specified high speed counter reaches the value in the HSCS instruction.
Program steps S1 S2 D
HSCR FNC 54 (High speed counter reset)
Resets the selected output when the specified high speed counter equals the test value
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ]
[ D ]
The HSCR, compares the current value of the selected high speed counter (S2) against a selected value (S1). When the counters current value changes to a value equal to S1, the device specified as the destination (D) is reset. In the example above, Y10 would be reset only when C255’s value stepped from 199 to 200 or from 201 to 200. If the current value of C255 was forced to equal 200 by test techniques, output Y10 would NOT reset. For further, general points, about using high speed counter functions, please see the subsection ‘Points to note’ under the HSCS (FNC 53). Relevant points are; a, b, and c. Please also reference the note about the number of high speed instructions allowable.
DHSCR
K200
C255 Y10
Operands · Mnemonic Function

Mnemonic Function Operands Program steps S1 S2 S3 D HSZ FNC 55 (High speed zone compare)
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
M8130 (only) This flag can only be used with one DHSZ instr’ at a time Operation 3: The designated range is held in a data table driving PLSY frequencies directly using D8132
D K,H Using values from 1 to 128 (deci- mal)
M8132 (only) This flag can only be used with one
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation 1 - Standard: (Applicable to all units) This instruction works in exactly the same way as the standard ZCP (FNC11). The only difference is that the device being compared is a high speed counter (specified as S3). Also, all of the outputs (D) are updated immediately due to the interrupt operation of the DHSZ. It should be remembered that when a device is specified in operand D it is in fact a head address for 3 consecutive devices. Each one is used to represent the status of the current comparison, i.e. using the above example as a basis, Y10 (D) C251 is less than S1, K1000 (S3< S1) Y11 (D+1) C251 is greater than S1, K1000 but less than S2, K1200 (S3> S1, S3< S2) Y12 (D+2) C251 is greater than S2, K1200 (S3> S2)
[ S1 ] [ S2 ] [ S3 ] [ D ]
C251 Y10 K1000 DHSZ K1200
For further, general points, about using high speed counter functions please see the
subsection ‘Points to note’ under the HSCS (FNC 52). Relevant points are; a, b, and c. Please also reference the note about the number of high speed instructions allowable.
Operation 2 - Using HSZ With A Data Table: (Applicable units: FX(2C) and FX2N) Operation 2 is selected when the destination device (D) is assigned special M coil M8130. This then allows devices (S1, S2) to be used to define a data table using (S1) as the head address and (S2) as the number of records in the table - maximum number of records is 128. Each record occupies 4 consecutive data registers proportioned in the following manner (for a single record of data registers D through D+3):
D, D+1 Used as a double (32 bit) data register to contain the comparison data
D+2 Stores the I/O device number, in HEX, of the ’Y’ Output device to be controlled, i.e. H10=Y10. Note: Hex digits A through F are not used.
D+3 Stores the action (SET/RESET) to be performed on the Output device D+2. Note: For a SET (ON) operation D+3 must equal 1, for a RESET (OFF) D+3 must equal 0.
Single Record · Data registers

The following points should be read while studying the example on the right of the page. Please note, all normal rules associated with high speed counters still apply.
The data table is processed one ‘record number’ at a time, i.e only 1 record is ever active as the comparison data. The currently active record number is stored in data register D8130. As the comparison value for the active record is ‘reached’, the assigned ‘Y’ device is SET or RESET and the active ‘Record number’ is incremented by 1. Once all records in a data table have been processed, the current record pointer (D8130) is reset to 0 (the table is then ready to process again) and the operation complete flag M8131 is set ON.

If the high speed counter is reset (by program or hardware input), when it resumes counting and reaches the first record’s comparison value, the M8131 flag will be reset. Both the status of M8131 and contents of D8130 are not editable by the user. If the DHSZ instruction is turned OFF then all associated flags are reset. Care should be exercised when resetting the high speed counter or turning OFF the DHSZ instruct as all associated ‘Y’ output devices will remain in their last state, i.e. if an output was ON it will remain ON until independently reset by the user. The data within inactive records can be changed during operation allowing data tables to be updated. Any change made is processed at the end of the current program scan. The HSZ instruction will continue to process only the active data record, i.e. it will not reset due to the updating of an inactive data record. When the DHSZ instruction is initially activated it will not process a comparison until the following program scan as the CPU requires a slight time delay to initialize the comparison table.


Operation 3 - Combined HSZ and PLSY Operation: (Applicable units: FX(2C) and FX2N(C)) Operation 3 allows the HSZ and PLSY instructions to be used together as a control loop. This operation is selected when the destination device (D) is assigned special M coil M8132. This then allows devices (S1, S2) to be used to define a data table using (S1) as the head address and (S2) as the number of records in the table - maximum number of records is 128. Each record occupies 4 consecutive data registers (D through D+3) proportioned in to two 32 bit data areas.
The first pair of data registers (D,D+1) contain the comparison value for use with the high speed counter. The second pair of data registers (D+2,D+3) contain a value (from 0 to 1000) which represents an output frequency in Hz. This value is loaded in to special data register D8132 when the comparison made by the DHSZ instruction gives a ‘TRUE’ output.
[D, D +1 ]
[D +2 , D +3 ]
[D180, D181]
[D182, D183]
K40 [D184, D185]
K100 [D186, D187]
K100 [D188, D189]
K600 [D190, D191]
K400 [D192, D193]
K550 [D194, D195]
Special data register D8132 can be used as the source data for a PLSY (FNC57) output enabling the output to be varied with relative count data.
K40 [D198, D199]
K0
K0
As with Operation 2 only one record in the data table is active at any one time. The current ‘Record number’ being processed is stored in data register D8131. To observe the current comparative value, data registers D8134 and D8135 should be monitored as a double word (32 bit) device.
M8132 C251 DHSZ D180 K5
PLS M10
M10
PLSY D8132 K0 Y7
Once the final entry in the data table has been processed, the operation complete flag M8133 is set ON and the record counter (D8131) cycles back to the first record.
C251 - count value
It is recommended that if the high speed counter and PLSY operations form a closed loop that the last record entry in the data table is set to K0 for the comparison value and K0 for the PLSY output frequency. This will bring the controlled system to a stop and the ‘Record number’ counter will not be able to cycle back to the start of the data table until the associated high speed counter is reset by either pro-gram or hardware methods. This situation can be easily monitored by checking the paired data registers D8134 and D8135 for the ‘0’ value.
0 1 3 2 4
1 3 2 1 3 2
in Hz for PLSY
PLSY Output Frequency in Hz
It is recommended that the operation of the PLSY instruction is delayed for 1 scan to allow the DHSZ data table to be constructed on initial operation. A suggested program using a pulsed flag is shown in the example on this page.

Program steps S1 S2 D
SPD FNC 56 (Speed detection)
Detects the number of ‘encoder’ pulses in a given time frame. Results can be used to calculate speed
X0 to X5 K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
T, C, D, Z (V) Note: 3 consecutive devices are used. In the case of D= Z monitor D8028, D8029 and D8030
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ D ]
The number of pulses received at S1 are counted and stored in D+1; this is the current count value. The counting takes place over a set time frame specified by S2 in msec. The time remaining on the current ‘timed count’, is displayed in device D+2. The number of counted pulses (of S1) from the last timed count are stored in D. The timing chart opposite shows the SPD operation in a graphical sense. Note: ¿: Current count value, device D+1 ¡: Accumulated/ last count value, device D ¬: Current time remaining in msec, device D+2
S1
S2
S2
Points to note:
a) When the timed count frame is completed the data stored in D+1 is immediately written to D.
D+1 is then reset and a new time frame is started.
b) Because this is both a high speed and an interrupt process only inputs X0 to X5 may be
used as the source device S1. However, the specified device for S1 must NOT coincide with any other high speed function which is operating, i.e. a high speed counter using the same input. The SPD instruction is considered to act as a single phase counter.
c) Multiple SPD instructions may be used, but the identified source devices S1 restrict this to a
maximum of 6 times.
d) Once values for timed counts have been collected, appropriate speeds can be calculated
using simple mathematics. These speeds could be radial speeds in rpm, linear speeds in M/ min it is entirely down to the mathematical manipulation placed on the SPD results. The following interpretations could be used;
Linear speed N (km/h) = 3600 × (D) n × S2 × 103
where n = the number of linear encoder divisions per kilometer.
Radial speed N (rpm) = 60 × (D)
n × S2 × 103
where n = the number of encoder pulses per revolution of the encoder disk.
Operands · Mnemonic Function

Program steps S1 S2 D
PLSY FNC 57 (Pulse Y output)
Outputs a specified number of pulses at a set frequency
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
Y Note: FX0(S)/FX0N users: Y000 only . FX users: any YPPP. FX2N(C) users: Y000 or Y001 only .
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ D ]
A specified quantity of pulses S2is output through device D at a specified frequency S1. This instruction is used in situations where the quantity of outputs is of primary concern.
Points to note:
a) Users of the FX PLC can specify output
frequencies (S1) of 1 to 1000Hz. Users of FX Version 2.2 or earlier will need to initialize the PLSY instruction. The program to the right can be used to achieve this. FX0/FX0N users may use frequencies of 10to 2000Hz. FX2N users may use frequencies of 2 to 20000Hz.
S2 D PLSY
S1
M8002
b) The maximum number of pulses: 16 bit operation:
1 to 32,767 pulses, 32 bit operation: 1 to 2,147,483,647 pulses. Note: special auxiliary coil M8029 is turned ON when the specified number of pulses has been completed. The pulse count and completion flag (M8029) are reset when the PLSY instruction is de-energized. If “0" (zero) is specified the PLSY instruction will continue generating pulses for as long as the instruction is energized.
c) A single pulse is described as having a 50% duty cycle. This means it is ON for 50% of the
pulse and consequently OFF for the remaining 50% of the pulse. The actual output is controlled by interrupt handling, i.e. the output cycle is NOT affected by the scan time of the program.
d) The data in operands S1 and S2 may be changed during execution. However, the new data
in S2 will not become effective until the current operation has been completed, i.e. the instruction has been reset by removal of the drive contact.
e) This instruction can only be used once within a program scan. Also, only one of either FNC
57 PLSY or FNC 59 PLSR can be in the active program at once.
It is possible to use subroutines or other such programming techniques to isolate different
instances of this instructions. In this case, the current instruction must be deactivated before changing to the new instance.
f) Because of the nature of the high speed output, transistor output units should be used with
this instruction. Relay outputs will suffer from a greatly reduced life and will cause false outputs to occur due to the mechanical ‘bounce’ of the contacts. To ensure a ‘clean’ output signal when using transistor units, the load current should be 200mA or higher. It may be found that ‘pull up’ resistors will be required.
Operands · Mnemonic Function

g) FX(2C) and FX2N(C) units can use the HSZ (FNC 55) instruction with the PLSY instruction
when source device S1 is set to D8132. Please see page 5-59 for more details.
h) FX units with CPU version 3.07 or greater and FX2C units can monitor the number of pulses
which have been output as a double word using devices D8136 and D8137.
FX2N(C) units can also monitor the number of pulses output to Y0 using devices D8140 and D8141 and the number of output pulses output to Y1 using devices D8142 and D8143. The total number of pulses output can be monitored using D8136 and D8137.
Program steps S1 S2 D
PWM FNC 58 (Pulse width modulation)
Generates a pulse train with defined pulse characteristics
Y Note: FX0(S)/FX0N users: Y001 only . FX users: any YPPP. FX2N(C) users: Y000 or Y001 only
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z Note: S1 S2
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ D ]
A continuous pulse train is output through device D when this instruction is driven. The characteristics of the pulse are defined as: The distance, in time (msec), between two identical parts of consecutive pulses (S2). And how long, also in time (msec), a single pulse will be active for (S1).
S1
D
S2
Points to note:
a) Because this is a 16 bit instruction, the available time ranges for S1 and S2 are 1 to 32,767.
b) A calculation of the duty cycle is easily made by dividing S1 by S2. Hence S1 cannot have a
value greater than S2 as this would mean the pulse is on for longer than the distance between two pulses, i.e. a second pulse would start before the first had finished. If this is programmed an error will occur. This instruction is used where the length of the pulse is the primary concern.
c) The PWM instruction may only be used once in a users program.
d) Because of the nature of the high speed output, transistor output units should be used with
this instruction. Relay outputs will suffer from a greatly reduced life and will cause false outputs to occur due to the mechanical ‘bounce’ of the contacts. To ensure a ‘clean’ output signal when using transistor units, the load current should be 200mA or higher. It may be found that ‘pull up’ resistors will be required.
Operands · Mnemonic Function


Program steps S1 S2 S3 D
Outputs a specified number of pulses, ramping up to a set frequency and back down to stop
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z Note: S1 S2
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
A specified quantity of pulses S2is output through device D. The output frequency is first ramped up in 10 steps to the maximum frequency S1 in acceleration time S3 ms, then ramped down to stop also in S3 ms. This instruction is used to generate simple acceleration/deceleration curves where the quantity of outputs is of primary concern.

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
a) FX2N users may use frequencies of 10 to 20,000Hz. The frequency should be set to a
multiple of 10. If not it will be rounded up to the next multiple of 10. The acceleration and deceleration steps are set to 1/10 of the maximum frequency. Take this in to consideration to prevent slipping, when using stepping motors.
b) The maximum number of pulses: 16 bit operation: 110 to 32,767 pulses, 32 bit operation: 110 to 2,147,483,647 pulses. Correct pulse output can not be guaranteed for a setting of 110.
c) The acceleration time must conform to the limitations described on the next page.

d) The output device is limited to Y0 or Y1 only and should be transistor type.
e) This instruction can only be used once within a program scan. Also, only one of either FNC
57 PLSY or FNC 59 PLSR can be in the active program at once.
It is possible to use subroutines or other such programming techniques to isolate differen instances of this instructions. In this case, the current instruction must be deactivated before changing to the new instance.
f) If the number of pulses is not enough to reach the maximum frequency then the frequency is
g) Special auxiliary coil M8029 turns ON when the specified number of pulses has been
completed. The pulse count and completion flag (M8029) are reset when the PLSR instruction is de-energized.
The acceleration time S3 has a maximum limit of 5000 ms. However, the actual limits of S3are determined by other parameters of the system according to the following 4 points.
If the parameters do not meet the above conditions, reduce the size of S1.
automatically cut · h)

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
IST - Initial State FNC 60 5-67
SER - Search FNC 61 5-69
ABSD - Absolute Drum FNC 62 5-70
INCD - Incremental Drum FNC 63 5-71
TTMR - Teaching Timer FNC 64 5-72
STMR - Special Timer - Definable FNC 65 5-72
ALT - Alternate State FNC 66 5-73
RAMP - Ramp - Variable Value FNC 67 5-73
ROTC - Rotary Table Control FNC 68 5-75
SORT - Sort Data FNC 69 5-77
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

Program steps S1 S2 S3
IST FNC 60 (Initial state)
Automatically sets up a multi-mode STL operating system
S, Note: FX0 users S20 to S63 FX0N users S20 to S127 FX users S20 to S899 D1must be lower than D2
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D1 ] [ D2 ]
This instruction automatically sets up a multi-mode STL operating system. This consists of variations of ‘manual’ and ‘automatic’ operation modes.
Points to note:
Assigned devices
a) The IST instruction automatically assigns
and uses many bit flags and word devices; these are listed in the boxed column on the right of this page.
Indirect user selected devices: S+0 Manual operation S+1 Zero return S+2 Step operation S+3 One cycle operation S+4 Cyclic operation S+5 Zero return start S+6 Automatic operation start S+7 Stop
b) The IST instruction may only be used
ONCE. It should be programmed close to the beginning of the program, before the controlled STL circuits.
c) The required operation mode is selected by
driving the devices associated with operands S+0through to S+4(5 inputs). None of the devices within this range should be ON at the same time. It is recommended that these ‘inputs’ are selected through use of a rotary switch. If the currently selected operating mode is changed before the ‘zero return complete’ flag (M8043) is set, all outputs will be turned OFF.
Special bit flags: M8040 = ON STL state transfer is inhibited M8041 = ON initial states are enabled M8042 = Start pulse given by start input M8043 = ON zero return completed M8044 = ON machine zero detected M8047 = ON STL monitor enabled
d) The ‘zero position’ is a term used to identify
a datum position from where the controlled device, starts from and returns too after it has completed its task. Hence, the operating mode ‘zero return’, causes the controlled system to return to this datum.
The ‘zero’ position is sometimes also referred to as a home position, safe position, neutral position or a datum position.
Operands · Mnemonic Function

e) The available operating modes are split into two main groups, manual and automatic. There
are sub-modes to these groups. Their operation is defined as:
Manual (selected by device S+0)- Power supply to individual loads is turned ON and OFF by using a separately provided means, often additional push buttons. Zero Return (selected by device S+1) -Actuators are returned to their initial positions when the Zero input (S+5) is given.
One Step (selected by device S+2)- The controlled sequence operates automatically but will only proceed to each new step when the start input (S+6) is given. One Cycle (selected by device S+3) - The controlled actuators are operated for one operation cycle. After the cycle has been completed, the actuators stop at their ‘zero’ positions. The cycle is started after a ‘start’ input (S+6) has been given. A cycle which is currently being processed can be stopped at any time by activating the ‘stop’ input (S+7). To restart the sequence from the currently ‘paused’ position the start input must be given once more. Automatic (selected by device S+4)-Fully automatic operation is possible in this mode. The programmed cycle is executed repeatedly when the ‘start’ input (S+6) is given. The currently operating cycle will not stop immediately when the ‘stop’ input (S+7)is given. The current operation will proceed to then end of the current cycle and then stop its operation. Note: Start, stop and zero inputs are often given by additional, manually operated push buttons. Please note that the ‘stop’ input is only a program stop signal. It cannot be used as a replacement for an ‘Emergency stop’ push button. All safety, ‘Emergency stop’ devices should be hardwired systems which will effectively isolate the machine from operation and external power supplies. Please refer to local and national standards for applicable safety practices.

Program steps S1 S2 D n
SER FNC 61 (Search a Data Stack)
Generates a list of statistics about a single data value located/found in a data stack
KnX, KnY, KnM, KnS, T, C, D
KnX, KnY, KnM, KnS,
KnY, KnM, KnS T, C, D Note: 5 consecutive devices are used
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ D ]
n [ S2 ]
The SER instruction searches a defined data stack from head address S1, with a stack length n. The data searched for is specified in parameter S2 and the results of the search are stored at destination device D for 5 consecutive devices.
D 35 K100
D Total number of occurrences of the searched value S2 (0 if no occurrences are found)
D+1 The position (within the searched data stack) of the first occurrence of the searched value S2
D+2 The position (within the searched data stack) of the last occurrence of the searched value S2
D+3 The position (within the searched data stack) of the smallest value found in the data stack (last occurrence is returned if there are multiple occurrences of the same value)
D+4 The position (within the searched data stack) of the largest value found in the data stack (last occurrence is returned if there are multiple occurrences of the same value)
a) Normal rules of algebra are used to determine the largest and smallest values, i.e. -30 is
smaller than 6 etc.
b) If no occurrence of the searched data can be found then destination devices D, D+1 and
D+2will equal 0 (zero).
c) When using data register s as the destination device D please remember that 16 bit
operation will occupy 5 consecutive, data registers but 32 bit operation will occupy 10 data registers in pairs forming 5 double words.
d) When multiple bit devices are used to store the result (regardless of 16 or 32 bit operation),
only the specified size of group is written to for 5 consecutive occurrences, i.e. K1Y0 would occupy 20 bit devices from Y0 (K1 = 4 bit devices and there will be 5 groups for the 5 results). As the maximum data stack is 256 (0 to 255) entries long, the optimum group of bit devices required is K2, i.e. 8 bit devices.

Program steps S1 S2 D n
ABSD FNC 62 (Absolute drum sequencer)
Generates multiple output patterns in response to counter data
KnX, KnY, KnM, KnS, (in groups of 8) T, C, D
K,H
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ D ]
This instruction generates a variety of output patterns (there are n number of addressed outputs) in response to the current value of a selected counter, S2.
C 0 D300 M 0
K 4
Points to note:
a) The current value of the selected counter (S2) is compared against a user defined data
table. This data table has a head address identified by operand S1. S1should always have an even device number.
b) For each destination bit (D) there are two consecutive values stored in the data table. The
first allocated value represents the event number when the destination device (D) will be turned ON. The second identifies the reset event. The data table values are allocated as a consecutive pair for each sequential element between D and D+n.
c) The data table has a length equal to 2 × n data entries. Depending on the format of the data
table, a single entry can be one data word such as D300 or a group of 16 bit devices e.g. K4X000.
d) Values from 0 to 32,767 may be used in the data table.
e) The ABSD instruction may only be used ONCE.
f) FX CPU’s ver 3.07 or greater and FX2C units have double word option on this instruction.
From the example instruction and the data table below, the following timing diagram for elements M0 to M3 can be constructed.
When counter S2 equals the value below, the destination
turned ON turned OFF
D301 - 140
M0
M 1
D302 - 100
D303 - 200
M1
M 2
D304 - 160
D305 - 60
M2
ON OFF
M 3
D306 - 240
D307 - 280
M3


Generates a single output sequence in response to counter data
KnX, KnY, KnM, KnS, (in groups of 8) T, C, D
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ D ]
This instruction generates a sequence of sequential output patterns (there are n number of addressed outputs) in response to the current value of a pair of selected counters (S2, S2+1).
a) This instruction uses a ‘data table’ which contains a single list of values which are to be
selected and compared by two consecutive counters (S2and S2+1). The data table is identified as having a head address S1and consists of n data elements.
b) Counter S2 is programmed in a conventional way. The set value for counter S2 MUST be
greater than any of the values entered into the data table. Counter S2 counts a user event and compares this to the value of the currently selected data element from the data table. When the counter and data value are equal, S2 increments the count of counter S2+1and resets its own current value to ‘0’ (zero). This new value of counter S2+1selects the new data element from the data table and counter S2now compares against the new data elements value.
c) The counter S2+1 may have values from 0 to n. Once the nth data element has been
processed, the operation complete flag M8029 is turned ON. This then automatically resets counter S2+1hence, the cycle starts again with data element S1+0.
d) Values from 0 to 32,767 may be used in the data table.
e) The INCD instruction may only be used
ONCE.

From the example instruction and the data table identified left, the following timing diagram for elements M0 to M3 can be constructed.


Program steps D n
TTMR FNC 64 (Teaching timer)
Monitors the duration of a signal and places the timed data into a data register
K, H Note: n= 0: (D) = (D+1) × 1 n= 1: (D) = (D+1) × 10 n= 2: (D) = (D+1) × 100
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation: The duration of time that the TTMR instruction is energized, is measured and stored in device D+1 (as a count of 100ms periods). The data value of D+1 (in secs), multiplied by the factor selected by the operand n, is moved in to register D. The contents of D could be used as the source data for an indirect timer setting or even as raw data for manipulation. When the TTMR instruction is de-energized D+1 is automatically reset (D is unchanged).
TTMR
D300
K 0
Equivalet time data (n duration D+1), is stored in D

Y, M, S Note:uses 4 consecutive devices D+0to D+3
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Operation: The designated timer Swill operate for the duration n with the operational effect being flagged by devices D+0to D+3. Device D+0is an off-delay timer, D+1is a one shot timer. When D+3is used in the configuration below, D+1and D+2act in a alternate flashing sequence.
Operands · Mnemonic Function · [ n ]


The status of the assigned device is inverted on every operation of the instruction
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The status of the destination device (D) is alternated on every operation of the ALT instruction.
This means the status of each bit device will flip- flop between ON and OFF. This will occur on every program scan unless a pulse modifier or a program interlock is used. The ALT instruction is ideal for switching between two modes of operation e.g. start and stop, on and off etc.
Program steps S1 S2 D n
Ramps a device from one value to another in the specified number of steps
D Note: Device D uses two consecutive registers identified as D and D+1 these are read only devices.
RAMP FNC 67 (Ramp vari- able value)
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ D ]
The RAMP instruction varies a current value (D) between the data limits set by the user (S1and S2). The ‘journey’ between these extreme limits takes n program scans. The current scan number is stored in device D+1. Once the current value of D equals the set value of S2the execution complete flag M8029 is set ON. The RAMP instruction can vary both increasing and decreasing differences between S1and S2.
D 2 D 1 D 3
K1000
[S2] [D]
[S1]
[D]
[S1]
[S2]
S1 < S2 S1 > S2
![Page 200 of the Mitsubishi Electronics FX user manual — [S2]](/cdn/reader/25/2527b58be3669e56b81b7e01ffb0ac5a998fc57c23ecfe66c063198eed31d3d3/images/page-200.webp?w=400)
a) FX users may set the operation mode of the
RAMP instruction by controlling the state of special auxiliary relay M8026. When M8026 is OFF, the RAMP instruction will be in repeat mode. This means when the current value of D equals S2the RAMP instruction will automatically reset and start again, i.e. the contents of D will be reset to that of S1 and the device D+1 (the number of current scans) will reset to ‘0’ (zero). This is shown in the diagram opposite. When M8026 is set ON, FX users will be operating the RAMP instruction in ‘Hold mode’. This means once the current value of D equals that of S2, the RAMP instruction will ‘freeze’ in this state. This means the M8029 will be set ON for as long as the instruction remains energized and the value of D will not reset until the instruction is re-initialized, i.e. the RAMP instruction is turned from OFF to ON again.
[D] [S1]
M8029
[S2]
[D]
[S1]
M8029
b) Users of FX0 and FX0N PLC’s cannot change the operating mode of the RAMP instruction.
For these PLC’s the mode is fixed as in the same case as FX PLC’s when M8026 has been set ON, i.e. HOLD mode.
c) If the RAMP instruction is interrupted before completion, then the current position within the
ramp is ‘frozen’ until the drive signal is re-established. Once the RAMP instruction is re- driven registers D and D+1 reset and the cycle starts from its beginning again.
d) If the RAMP instruction is operated with a constant scan mode, i.e. D8039 is written to with
the desired scan time (slightly longer than the current scan time) and M8039 is set ON. This would then allow the number of scans n (used to create the ramp between S1and S2) to be associated to a time. If 1 scan is equal to the contents of D8039 then the time to complete the ramp is equal to n × D8039.
The RAMP instruction may also be used with special M flags M8193 and M8194 to mimic the operation of the SER (FNC 61) and RS (FNC 80) respectively when being programmed on older versions of programming peripherals. See page 1-5 for more details.

Program steps S m1 m2 D
ROTC FNC 68 (Rotary table control)
Controls a rotary tables movement is response to a requested destination/ position
K, H Note: m2= 0 to 32,767
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ m1 ] [ D ]
The ROTC instruction is used to aid the tracking and positional movement of the rotary table as it moves to a specified destination.
K10 D200 K 2
fined devices. These are listed on the right of this page. b) The ROTC instruction may only be used
Indirect user selected devices: D+0 A-phase counter signal - input D+1 B-phase counter signal - input D+2 Zero point detection - input D+3 High speed forward - output D+4 Low speed forward - output D+5 Stop - output D+6 Low speed reverse - output D+7 High speed reverse - output
ONCE.
c) The ROTC instruction uses a built in 2-phase
counter to detect both movement direction and distance travelled. Devices D+0and D+1 are used to input the phase pulses, while device D+2is used to input the ‘zero position’ on the rotary table. These devices should be programmed as shown in the example below (where the physical termination takes place at the associated X inputs).
Rotary table constants: m1 Number of encoder pulses per table revolution m2 Distance to be travelled at low speed (in encoder pulses)
M 1
READ ONLY S+1 Destination position (selected
The movement direction is found by checking the relationship of the two phases of the 2 phase counter, e.g.
station to be moved to) relative to the ‘zero point’ - User defined S+2 Start position (selected station to
be moved) relative to the ‘zero point’ -User defined
A phase leads B phase
B phase leads A phase

d) When the ‘zero point’ input (D+2) is received the contents of device S+0is reset to ‘0’ (zero).
Before starting any new operation it is advisable to ensure the rotary table is initialized by moving the ‘zero point’ drive dog or marker around to the ‘zero point’ sensor. This could be considered as a calibration technique. The re-calibration of the rotary table should be carried out periodically to ensure a consistent/accurate operation.
e) Devices D+3 to D+7 are automatically set by the ROTC instruction during its operation.
These are used as flags to indicate the operation which should be carried out next.
f) All positions are entered in the form of the required encoder pulses. This can be seen in the
following example:
A rotary table has an encoder which outputs 400 (m1) pulses per revolution. There are 8 stations (0 to 7) on the rotary table. This means that when the rotary table moves from one station to its immediately following station, 50 encoder pulses are counted. The ‘zero position’ is station ‘0’ (zero). To move the item located at station 7 to station 3 the following values must be written to the ROTC
instruction: S+1=3 × 50 = 150 (station 3’s position in encoder pulses from the zero point) S+2=7 × 50 = 350 (station 7’s position in encoder pulses from the zero point) m1= 400 (total number of encoder pulses per rev) The rotary table is required approach the destination station at a slow speed starting from 1.5 stations before the destination. Therefor; m2= 1.5 × 50 = 75 slow speed distance either side of the destination station (in encoder pulses)


Program steps S m1 m2 D n
Data in a defined table can be sorted on selected fields while retaining record integrity
K, H D Note: n = 1 to m2
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction constructs a data table of m1 records with m2 fields having a start or head address of S. Then the data in field nis sorted in to numerical order while retaining each individual records integrity. The resulting (new) data table is stored from destination device D.
a) When a sort occurs each record is sorted in to ascending order based on the data in the
selected sort field n.
b) The source (S) and destination (D) areas can be the same BUT if the areas are chosen to
be different, there should be no overlap between the areas occupied by the tables.
c) Once the SORT operation has been completed the ‘Operation Complete Flag’ M8029 is
turned ON. For the complete sort of a data table the SORT instruction will be processed m1times.
d) During a SORT operation, the data in the SORT table must not be changed. If the data is
changed, this may result in an incorrectly sorted table.
e) The SORT instruction may only be used ONCE in a program.
From the example instruction and the ‘data table’ below left, the following data manipulation will occur when nis set to the identified field
Original Table1st table sort when n= 2 2nd table sort when n=1
(D104)
(D108)
(D100)
(D104)
(D108)
(D100)
(D104)
(D108)
R E C O R D (m1) 4
162 (D105)
4 (D109)
R E C O R D (m1) 4
6 (D105)
200 (D109)
R E C O R D (m1)
34 (D105)
6 (D109)
74 (D102)
6 (D106)
200 (D110)
7 (D102)
34 (D106)
6 (D110)
32 (D102)
162 (D106)
4 (D110)
100 (D103)
80 (D107)
62 (D111)
100 (D103)
80 (D107)
62 (D111)
74 (D103)
6 (D107)
200 (D111)
FIELD (m2) · FIELD (m2) · FIELD (m2)


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
TKY - Ten Key Input FNC 70 5-81
HKY - Hexadecimal Input FNC 71 5-82
DSW - Digital Switch
(Thumbwheel input) FNC 72 5-83
SEGD - Seven Segment Decoder FNC 73 5-84
SEGL - Seven Segment
With Latch FNC 74 5-85
ARWS - Arrow Switch FNC 75 5-87
ASC - ASCII Code FNC 76 5-88
PR- ‘Print’ To A Display FNC 77 5-89
FROM - Read From A Special
Function Block FNC 78 5-90
TO - Write To A Special
Function Block FNC 79 5-91
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page


Reads 10 devices with associated decimal values into a single number
KnY, KnM, KnS, T, C, D, V, Z Note: uses 2 consecutive devices for 32 bit operation
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction can read from 10 consecutive devices(S+0 to S+9) and will store an entered numeric string in device D1.
a) When a source device becomes active its associated destination (bit) device D2 also
becomes active. This destination device will remain active until another source device is operated. Each source device maps directly to its own D2 device, i.e. S+0 maps to D2+0, S+7 maps to D2+7 etc. These in turn, map directly to decimal values which are then stored in the destination data devices specified by D1.
b) One source device may be active at any one time. The destination device D2+10 is used to
signify that a key (one of the 10 source devices) has been pressed. D2+10 will remain active for as long as the key is held down. When the TKY instruction is active, every press of a key adds that digit to the stored number in D1. When the TKY is OFF, all of the D2 devices are reset, but the data value in D1 remains intact.
c) When the TKY instruction is used with 16 bit operation, D1 can store numbers from 0 to
9,999 i.e. max. 4 digits. When the DTKY instruction is used (32 bit operation) values of 0 to 99,999,999 (max. 8 digits) can be accommodated in two consecutive devices D1and D1+1. In both cases if the number to be stored exceeds the allowable ranges, the highest digits will overflow until an allowable number is reached. The overflowed digits are lost and can no longer be accessed by the user. Leading zero’s are not accommodated, i.e. 0127 will actually be stored as 127 only.
d) The TKY instruction may only be used ONCE.

e) Using the above instruction as a brief example: If the
‘keys’ identified (a) to (d) are pressed in that order the number 2,130 will be entered into D1. If the key identified as (e) is then pressed the value in D1 will become 1,309. The initial ‘2’ has been lost.

0 1 2 3 4 5 6 7 8 9
X11 X0 X1 X2 X3 X4 X5 24V 0V S/S X6 X7


Program steps S D1 D2 D3
Multiplexes inputs and outputs to create a numeric keyboard with 6 function keys
T, C, D, V, Z Note: uses 2 consecutive devices for 32 bit operation
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction creates a multiplex of 4 outputs (D1) and 4 inputs (S) to read in 16 different devices. Decimal values of 0 to 9 can be stored while 6 further function flags may be set.
a) Each of the first 10 multiplexed source devices (identified as 0 to 9) map directly to decimal
values 0 to 9. When entered, i.e. a source device is activated, then its associated decimal value is added to the data string currently stored in D2. Activation of any of these keys causes bit device D3+7 to turn ON for the duration of that key press.
b) The last 6 multiplexed source devices (identified as function keys A to F) are used to set bit
devices D3+0 to D3+5 respectively. These bit flags, once set ON, remain ON until the next function key has been activated. Activation of any of these keys causes bit device D3+6 to turn ON for the duration of that key press.
c) In all key entry cases, when two or more keys are pressed, only the key activated first is
effective. When the pressing of a key is sensed the M8029 (execution complete flag) is turned ON. When the HKY instruction is OFF, all D3 devices are reset but data value D2 remains intact.
d) When the HKY instruction is used with 16 bit

operation, D2 can store numbers from 0 to 9,999 i.e. max. 4 digits. When the DHKY instruction is used (32 bit operation) values of 0 to 99,999,999 (max. 8 digits) can be accommodated in two consecutive devices D2 and D2+1. In both cases if the number to be stored exceeds the allowable ranges, the highest digits will overflow until an allowable number is reached. The over-flowed digits are lost and can no longer be accessed by the user. Leading zero’s are not accommodated, i.e. 0127 will actually be stored as 127 only. This operation is similar to that of the TKY instruction.

e) The HKY instruction may only be used ONCE.

f) Normal operation requires 8 scans to read the key
inputs. To achieve a steady and repeatable performance, constant scan mode should be used, i.e. M8039 is set ON and a user defined scan time is written to register D8039. However, for a faster response the HKY instruction should be programmed in a timer interrupt routine as shown in the example opposite.
Y 0 D 0 M 0 HKY X 0
(Applicable units: FX(2C) and FX2N) When the HKY instruction is used with flag M8167 ON (as shown right), the operation of keys A through F allow actual entry of the Hexadecimal values of A through F respectively into the data device D2. This is in addition to the standard 0 through 9 keys. All other operation is as specified in ‘Operation 1 - Standard’. Maximum storage values for this operation become FFFF in 16 bit mode and FFFFFFFF in 32 bit (double word) mode.

Multiplexed reading of n sets of digital (BCD) thumbwheels
X Note: If n=2 then 8 devices else 4.
T, C, D, V, Z Note: If n=2 then 2 devices else 1.
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction multiplexes 4 outputs (D1) through 1 or 2(n) sets of switches. Each set of switches consists of 4 thumbwheels providing a single digit input.

a) When n = 1 only one set of switches are read. The
BCD digital switches (1st set) 2nd switch set inputs
multiplex is completed by wiring the thumbwheels in parallel back to 4 consecutive inputs from the head address specified in operand S. The (4 digit) data read is stored in data device D2.
X11 X12 X13 24V 0V S/S X14 X15 X16 X17
Continued on next page...

b) When n= 2, two sets of switches are read. This configuration requires 8 consecutive inputs
taken from the head address specified in operand S. The data from the first set of switches, i.e. those using the first 4 inputs, is read into data device D2. The data from the second set of switches (again 4 digits) is read into data device D2+1.
c) The outputs used for multiplexing (D1) are

cycled for as long as the DSW instruction is driven. After the completion of one reading, the execution complete flag M8029 is set. The number of outputs used does not depend on the number of switches n.
d) If the DSW instruction is suspended during mid-
operation, when it is restarted it will start from the beginning of its cycle and not from its last status achieved.
e) It is recommended that transistor output units
are used with this instruction. However, if the program technique at the right is used, relay output units can be successfully operated as the outputs will not be continually active.
Y 10 D 0 K 1 DSW X 10 M0
f) The DSW instruction may be used ONCE on
FX controllers with CPU versions lower than 3.07. FX units with CPU ver 3.07 or greater and all FX2C units can operate a maximum of TWO DSW instructions.
Mnemonic Function Operands Program steps S D
SEGD FNC 73 (Seven segment decoder)
Hex data is decoded into a format used to drive seven segment displays
K, H KnX, KnY, KnM, KnS, T, C, D, V, Z Note: Uses only the lower 4 bits
KnY, KnM, KnS, T, C, D, V, Z Note: The upper 8 bits remain unchanged
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ] [ S ]
A single hexadecimal digit (0 to 9, A to F) occupying the lower 4 bits of source device S is decoded into a data format used to drive a seven segment display. A representation of the hex digit is then displayed. The decoded data is stored in the lower 8 bits of destination device D. The upper 8 bits of the same device are not written to. The diagram opposite shows the bit control of the seven segment display. The active bits correspond to those set to 1 in the lower 8 bits of the destination device D.
It can be seen that B7 is NOT used. Hence B7 of the destination device D will always be OFF,
B5 B6
B1
B4
B2
B3


Writes data to multiplexed single digit displays - 4 digits per set, max. 2 sets
K, H KnX, KnY, KnM, KnS T, C, D, V, Z
Y Note: n = 0 to 3, 8 outputs are used n = 4 to 7, 12 outputs are used
K, H, Note: n= 0 to 3, 1 set of 7 Seg active n= 4 to 7, 2 sets of 7 Seg active
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ] [ S ] [ n ]
This instruction takes a source decimal value (S) and writes it to a set of 4 multiplexed, outputs (D). Because the logic used with latched seven segment displays varies between display manufactures, this instruction can be modified to suit most logic requirements. Configurations are selected depending on the value of n, see the following page.
a) Data is written to a set of multiplexed outputs (D+0 to D+7, 8 outputs) and hence seven
segment displays. A set of displays consists of 4 single digit seven segment units. A maximum of two sets of displays can be driven with this instruction. When two sets are used the displays share the same strobe outputs (D+4 to D+7 are the strobe outputs). An additional set of 4 output devices is required to supply the new data for the second set of displays (D+10 to D+13, this is an octal addition). The strobe outputs cause the written data to be latched at the seven segment display.
b) Source data within the range of 0 to 9,999 (decimal) is written to the multiplexed outputs.
When one set of displays are used this data is taken from the device specified as operand S. When two sets of displays are active the source device S+1 supplies the data for the second set of displays. This data must again be within the range 0 to 9,999. When using two sets of displays the data is treated as two separate numbers and is not combined to provide a single output of 0 to 99,999,999.
c) The SEGL instruction takes 12 program scans to complete one output cycle regardless of
the number of display sets used. On completion, the execution complete flag M8029 is set.

In this example it has been assumed that the seven segment displays accept data HIGH inputs and latch when a HIGH signal is received
Y2 Y3 +V0 Y0 Y1 Y6 Y7 +V1 Y4 Y5 Y12 Y13 +V2 Y10 Y11 1 2 4 8

d) If the SEGL instruction is suspended during mid-operation, when it is restarted it will start
from the beginning of its cycle and not from its last status achieved.
e) The SEGL instruction may be used ONCE on FX controllers with CPU versions lower than
3.07. FX units with CPU ver 3.07 or greater and all FX2C units can operate a maximum of TWO SEGL instructions.
The selection of parameter n depends on 4 factors; 1) The logic type used for the PLC output 2) The logic type used for the seven segment data lines 3) The logic type used for the seven segment strobe signal 4) How many sets of displays are to be used
Device considered Positive logic Negative logic
V+
HIGH
V+
Y
Y
0V LOW
COM
With a source output, when the output is HIGH the internal logic is ‘1’
With a sink output, when the output is LOW the internal logic is ‘1’
Seven segment Display logic
Data is latched and held when this signal is HIGH, i.e. its logic is ‘1’
Data is latched and held when this signal is LOW, i.e. its logic is ‘1’
Active data lines are held HIGH, i.e. they have a logic value of ‘1’
Active data lines are held LOW, i.e. they have a logic value of ‘1’
There are two types of logic system available, positive logic and negative logic. Depending on the type of system, i.e. which elements have positive or negative logic the value of n can be selected from the table below with the final reference to the number of sets of seven segment displays being used:
PLC Logic Seven segment display logic n
Data Logic Strobe logic 1 display set 2 display sets
Positive (Source) Positive (High) Positive (High)
0 4 Negative (Sink) Negative (Low) Negative (Low)
Positive (Source) Positive (High) Negative (Low)
1 5 Negative (Sink) Negative (Low) Positive (High)
Positive (Source) Positive (High) Negative (Low)
2 6 Negative (Sink) Negative (Low) Positive (High)
Positive (Source) Positive (High) Positive (High)
3 7 Negative (Sink) Negative (Low) Negative (Low)


Creates a user defined, (4 key) numeric data entry panel
T, C, D, V, Z Note: data is stored in a decimal format
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction displays the contents of a single data device D1on a set of 4 digit, seven segment displays. The data within D1is actually in a standard decimal format but is automatically converted to BCD for display on the seven segment units. Each digit of the displayed number can be selected and edited. The editing procedure directly changes the value of the device specified as D1.

a) The data stored in destination device D1can have a
value from the range 0 to 9,999 (decimal), i.e. 4 digit data. Each digits data value, can be incremented (S+1) or decremented (S+0) by pressing the associated control keys. The edited numbers automatically ‘wrap-around’ from 9 - 0 - 1 and 1 -0 - 9. The digit data is displayed by the lower 4 devices from D2, i.e. D2+0 to D2+3.
b) On initial activation of the ARWS instruction,
the digit in the numeric position 10 3 is currently selected. Each digit position can be sequentially ‘cursored through’ by moving to the left (S+2) or to the right (S+3). When the last digit is reached, the ARWS instruction automatically wraps the cursor position around, i.e. after position 10 3, position 10 0 is selected and vice-versa. Each digit is physically selected by a different ‘strobe’ output.
c) To aid the user of an operation panel controlled with the ARWS instruction, additional lamps
could be wired in parallel with the strobe outputs for each digit. This would indicate which digit was currently selected for editing.
d) The parameter n has the same function as parameter n of the SEGL instruction - please
seepage5-86, ‘Selectingthecorrectvalueforoperand n‘. Note: as the ARWS instruction only controls one set of displays only values of 0 to 3 are valid for n.
e) The ARWS instruction can be used ONCE. This instruction should only be used on
transistor output PLC’s.

Program steps S D1
ASC FNC 76 (ASCII code conversion)
An entered alphanumeric string can be converted to its ASCII codes
Alphanumeric data e.g. 0-9, A - Z and a - z etc. Note: Only one, 8 character string may be entered at any one time.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ] [ S ]
The source data string S consists of up to 8 characters taken from the printable ASCII character (Char) set. If less than 8 Char are used, the difference is made up with null Char (ASCII 00). The source data is converted to its associated ASCII codes. The codes are then stored in the destination devices D, see example shown below.
F X - 6 4 M R !
D
D300 58 (X) 46 (F)
D301 36 (6) 2D (-)
D302 4D (M) 34 (4)
D303 21 (!) 52 (R)


Outputs ASCII data to items such as display units
T, C, D Note: 8 byte mode (M8027=OFF) uses 4 consecutive devices 16 byte mode (M8027= ON) uses 8 consecutive devices
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Operation Complete M8029
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Source data (stored as ASCII values) is read byte by byte from the source data devices. Each byte is mapped directly to the first 8 consecutive destination devices D+0 to D+7). The final two destination bits provide a strobe signal (D+10, numbered in octal) and an execution/busy flag (D+11, in octal).
a) The source byte-data maps the lowest bit to the first destination device D+0. Consequently
the highest bit of the byte is sent to destination device D+7.
b) The PR instruction may be used ONCE on FX units fitted with CPU versions earlier than
3.07. FX units with CPU ver3.07 or later and all FX2C units can operate TWO PR instructions. This instruction should only be used on transistor output PLC’s. The PR instruction will not automatically repeat its operation unless the drive input has been turned OFF and ON again.
c) The operation of the PR instruction is program scan dependent. Under standard
circumstances it takes 3 program scans to send 1 byte. However, for a faster operation the PR instruction could be written into a timer interrupt routine similar to the one demonstrated for HKY on page 5-82.
d)8 byte operation has the following timing diagram. It should be noted that when the drive input (in the example X0) is switched OFF the PR instruction will cease operation. When it is restarted the PR instruction will start from the beginning of the message string. Once all 8 bytes have been sent the execution/busy flag is dropped and the PR instruction suspends operation.

e) 16 byte operation requires the special auxiliary flag
M8027 to be driven ON (it is recommended that M8000 is used as a drive input). In this operation mode the drive input (in the example X0) does not have to be active all of the time. Once the PR instruction is activated it will operate continuously until all 16 bytes of data have been sent or the value 00H (null) has been sent. Once the operation is complete the execution/busy flag (D+11, octal) is turned OFF and M8029 the execution complete flag is set.


Read data from the buffer memories of attached special function blocks
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The FROM instruction reads n words of data starting from the buffer memory address m2 of the special function block with the logical block position specified as m1, The read data is stored in the PLC at head address D for n word devices.
[ m1 ][ m2 ] [ D ] [ n ] X1
a) All special function blocks which are addressable with the FROM/TO instructions are
connected to the extension bus on the right hand side of the PLC. Each special function block can be inserted at any point within the chain of extended units (as long as the system configuration rules are not broken). Each special function block is consecutively addressed from 0 to 7 beginning with the one closest to the base unit.

b) Each special function unit has different buffer memory registers. These often have a
dedicated use for each individual unit. Before any reading or writing of data is undertaken ensure that the correct buffer memory allocations for the unit used are known. m2: This defines the head address of the (special function blocks) buffer memories being accessed. m2 may have a value from the range 0 to 31. n: This identifies the number of words which are to be transferred between the special function block and the PLC base unit. n may have a value of 1 to 31 for 16 bit operation but a range of 1 to 16 is available for 32 bit operation.
c) The destination head address for the data read FROM the special function block is
specified under the D operand; and will occupy n further devices.
d) This instruction will only operate when the drive input is energized.

e) Users of FX PLC’s have the option of allowing interrupts to occur immediately, i.e. during the
operation of the FROM/TO instructions or to wait until the completion of the current FROM/TO instruction. This is achieved by controlling the special auxiliary flag M8028. The following table identifies certain points associated with this control and operation.
Interruption Disabled Interruption Enabled
Jumps called by interrupt operation are delayed until the completion of the data transfer of the FROM/TO instruction
Jumps called by interrupt operation occur immediately
Data transfer will resume upon return from the interrupt program. This may not be desirable if a FROM/TO instruction has been programmed within the called interrupt
A small delay of (800m +200) µsec can be expected in the worst case. Note: m = the number of 32 bit words
Ensures that FROM/TO instructions included in an interrupt program will not interact with others elsewhere
M8028 should only be used when a very short delay is required in applications where timing and accuracy’s are important
Users of FX0N have no option for interruption of the FROM/TO instructions and hence always operate in a mode equivalent to having M8028 switched OFF.
Program steps m1 m2 S n
Writes data to the buffer memories of attached special function blocks
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ m1 ][ m2 ] [ S ] [ n ] X0
The TO instruction writes n words of data to the head buffer memory address m2 of the special function block with the logical block position specified in m1. The written data is taken from the PLC’s head address S for n word devices.
Points to note:
All points are the same as the FROM instruction (see previous page) except point c) which is replaced by the following:
a) The source head address for the data written TO the special function block is specified
under the S operand.
Operands · Mnemonic Function


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
RS - RS Communications FNC 80 5-95
PRUN - FX2-40AP Parallel Run FNC 81 5-96
ASCI - Hexadecimal to ASCII FNC 82 5-98
HEX - ASCII to Hexadecimal FNC 83 5-99
CCD - Check Code FNC 84 5-100
VRRD - FX-8AV Volume Read FNC 85 5-101
VRSC - FX-8AV Volume Scale FNC 86 5-101
- Not Available FNC 87
PID - PID Control Loop FNC 88 5-102
- Not Available FNC 89
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

Program steps S m D n
RS FNC 80 (Serial Com- munications instruction)
Used to control serial communications from/to the programmable controller
D (including file registers)
K, H, D m = 1 to 256, FX2N 1 to 4096.
D K, H, D m = 1 to 256, FX2N 1 to 4096
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS
Transmit Delay M8121 Trans Request M8122 Data Received M8123
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ] [ D ]
[ m ] [ n ]
This instruction performs the direct control of communications over FX and FX0N communication adapters which connect to the left hand port of the Main Processing Unit, i.e. FX0N-232ADP, FX- 232ADP etc.
K 5
Points to note:
Assigned devices Data devices:
a) This instruction has many automatically
defined devices. These are listed in the boxed column to the right of this page.
D8120 - Contains the configuration parameters for
communication, i.e. Baud rate,Stop bits etc. Full details over the page
b) The RS instruction has two parts, send
(or transmission) and receive. The first elements of the RS instruction specify the transmission data buffer (S) as a head address, which contains m number of elements in a sequential stack. The specification of the receive data area is contained in the last two parameters of the RS instruction. The destination (D) for received messages has a buffer or stack length of n data elements. The size of the send and receive buffers dictates how large a single message can be. Buffer sizes may be updated at the following times: 1) Transmit buffer - before transmission occurs, i.e. before M8122 is set ON 2) Receive buffer - after a message has been received and before M8123 is reset.
D8122 - Contains the current count of the number of
remaining bytes to be sent in the currently transmitting message.
D8123 - Contains the current count of the number of
received bytes in the ‘incoming’ message.
D8124 - Contains the ASCII code of the character used
to signify a message header - default is ‘STX’, 02 HEX.
D8125 - Contains the ASCII code of the character used
to signify a message terminator -default is ‘ETX’, 03 HEX. Operational flags:
M8121 - This flag is ON to indicate a transmission is
being delayed until the current receive operation is completed.
M8122 - This flag is used to trigger the transmission of
data when it is set ON.
M8123 - This flag is used to identify (when ON) that a
complete message has been received.
M8124 - Carrier detect flag. This flag is for use with FX
c) Data cannot be sent while a message is
and FX2C Main Processing Units. It is typically useful in modem communications
being received, the transmission will be delayed - see M8121.
M8161 - 8 or 16 bit operation mode ON = 8 bit mode
where only the lower 8 bits in each source or destination device are used, i.e. only one ASCII character is stored in one data register OFF = 16bit mode where all of the available source/ destination register is used, i.e. two ASCII characters are stored in each data register.
d) More than one RS instruction can be
programmed but only one may be active at any one time.
Operands · Mnemonic Function

Program steps S D
PRUN FNC 81 (Parallel run)
Used to control the FX parallel link adapters: FX2-40AW/AP
KnX, KnM KnY, KnY PRUN, PRUNP: 5 steps DPRUN, DPRUNP: 9 steps
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D ] [ S ]
This instruction is used with the FX parallel link adapters. It allows source data to be moved into the bit transmission area. The actual control of the parallel link communication is by special M flags.
K2M810
Points to note:
a) Parallel link communications automatically take
place when both systems are ‘linked’ and the Master station (M8070), Slave station flags (M8071) have been set ON (there is no need to have a PRUN instruction for communications). There can only be one of each type of station as this system connects only two FX PLC’s. The programs shown opposite should be inserted into the appropriate FX PLC’s programs.
M8070
Slave FX PC M8000
Once the station flags have been set, they can only be cleared by either forcibly resetting them when the FX PLC is in STOP mode or turning the power OFF and ON again.
b) During automatic communications the following data is ‘swapped’ between the Master and
Slave PLC’s.
Bit Data Bit Data
M800 to M899 (100 points) → M800 to M899 (100 points)
M900 to M999 (100 points) ← M900 to M999 (100 points)
Data words Data words
D490 to D499 (10 points) → D490 to D499 (10 points)
D500 to D509 (10 points) ← D500 to D509 (10 points)
Continued...

c) The PRUN instruction enables data to be moved into the bit transmission area or out of the
(bit) data received area. The PRUN instruction differs from the move statement in that it operates in octal. This means if K4X20 was moved using the PRUN instruction to K4M920, data would not be written to M928 and M929 as these devices fall outside of the octal counting system. This can be seen in the diagram below.
X37 X36 X35 X34 X33 X32 X31 X30 X27 X26 X25 X24 X23 X22 X21 X20 K4X20
M936 M935 M934 M933 M932 M931 M930 M927 M926 M925 M924 M923 M922 M921
These devices are not written to with the PRUN instruction
d) For more information please see page 9-6.


K, H, KnX, KnY, KnM, KnS T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction reads n hexadecimal data characters from head source address (S) and converts them in to the equivalent ASCII code. This is then stored at the destination (D) for n number of bytes.
Please note that data is converted ‘as read’, i.e. using the example above with the following data in (D9,D8) ABCDH,EF26H. Taking the first n hexadecimal characters (digits) from the right (in this case n= 6) and converting them to ASCI will store values in 6 consecutive bytes from D20, i.e. D20 = (67, 68), D21 = (69, 70) and D22 = (50, 54) respectively. In true characters symbols that would be read as CDEF26.
This can be shown graphically as in the table to the right. Please take special note that the source data (S) read from the most significant device to the least significant. While the destination data (D) is read in the opposite direction. The ASCI instruction can be used with the M8161, 8 bit/16bit mode flag. The effect of this flag is exactly the same as that detailed on page 10-20. The example to the right shows the effect when M8161 is OFF. If M8161 was set ON, then only the lower destination byte (b0-7) would be used to store data and hence 6 data registers would be required (D20 through D25).


The table below identifies the usable hexadecimal digits and their associated ASCII codes
HEX Character 0 1 2 3 4 5 6 7 8 9 A B C D E F
HEX 30 31 32 33 34 35 36 37 38 39 41 42 43 44 45 46
DEC 48 49 50 51 52 53 54 55 56 57 65 66 67 68 69 70
Symbol ’0’ ’1’ ’2’ ’3’ ’4’ ’5’ ’6’ ’7’ ’8’ ’9’ ’A’ ’B’ ’C’ ’D’ ’E’ ’F’


Converts a data value from ASCII in to a hexadecimal equivalent
K, H, KnX, KnY, KnM, KnS T, C, D
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction reads n ASCII data bytes from head source address (S) and converts them in to the equivalent Hexadecimal character. This is then stored at the destination (D) for n number of bytes.
Please note that this instruction ‘works in reverse’ to the ASCI instruction, i.e. ASCII data stored in bytes is converted into associated hexadecimal characters. The HEX instruction can be used with the M8161 8bit/16bit flag. In this case the source data (S)is read from either the lower byte (8bits) when M8161 is ON, or the whole word when M8161 is OFF i.e. using the example above with the following data in devices D50 and D51 respectively (43H,41H) (42H,31H) and assuming M8161 is ON.
The ASCII data is converted to its hexadecimal equivalent and stored sequentially digit by digit f r om the destination head address. If M8161 had been OFF, then the contents of D20 would read CAB1H.

For further details regarding the use of the HEX instruction and about the available ASCII data ranges, please see the following information point ‘ASCII Character Codes’ under the ASCI
instruction on the previous page.
If an attempt is made to access an ASCII Code (HEX or Decimal) which falls outside of the ranges specified in the table on previous page, the instruction is not executed. Error 8067 is flagged in data register D8004 and error 6706 is identified in D8067. Care should be taken when using the M8161 flag, and additional in the specification of the number of element ‘n‘ which are to be processed as these are the most likely places where this error will be caused.


FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction looks at a byte (8 bit) stack of data from head address (S)for n bytes and checks the vertical bit pattern for parity and sums the total data stack. These two pieces of data are then stored at the destination (D).
a) The SUM of the data stack is stored at destination D while the Parity for the data stack is
stored at D+1.
b) During the Parity check an even result is indicated by the use of a 0 (zero) while an odd
parity is indicated by a 1 (one).
c) This instruction can be used with the 8 bit/ 16 bit mode flag M8161. The following results will
occur under these circumstances. See page 10-20 for more details about M8161.


H L 1 FF FF
1 FF 1 00 0 1 0 1 F0 0F
1 FF 1 00
1 0 1 0
D101 L D102 L D103 L D104 L D105 L
1 0 1
It should be noted that when M8161 is OFF ‘n’ represents the number of consecutive bytes checked by the CCD instruction. When M8161 is ON only the lower bytes of ‘n’ consecutive words are used. The ‘SUM’ is quite simply a summation of the total quantity of data in the data stack. The Parity is checked vertically through the data stack as shown by the shaded areas.


Reads an analog value from 1 of 8 volume inputs on the FX-8AV
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The identified volume (S) on the FX-8AV is read as an analog input. The analog data is in an 8 bit format, i.e. values from 0 to 255 are readable. The read data is stored at the destination device identified under operand D.
The FX-8AV volume ‘inputs’ are able to be read in two formats, a) as an analog value and b) as an 11 (0 to 10) position rotary switch. The second use is described in the VRSC instruction (FNC 86).

Reads the set position value, 0 to 10, from volume inputs on the FX-8AV
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The identified volume (S) on the FX-8AV is read as a rotary switch with 11 set positions (0 to 10). The position data is stored at device D as an integer from the range 0 to 10.
The FX-8AV volume ‘inputs’ are able to be read in two formats, a) as a 11 (0 to 10) position rotary switch and b) as an analog value. The second use is described in the VRRD instruction (FNC 85).
![Page 228 of the Mitsubishi Electronics FX user manual — [ S3 ]](/cdn/reader/25/2527b58be3669e56b81b7e01ffb0ac5a998fc57c23ecfe66c063198eed31d3d3/images/page-228.webp?w=400)
Program steps S1 S2 S3 D
PID FNC 88 (PID control loop) register each
Receives a data input and calculates a corrective action to a specified level based on PID control
D
D
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction takes a current value (S2) and compares it to a predefined set value (S1). The difference or error between the two values is then processed through a PID loop to produce a correction factor which also takes into account previous iterations and trends of the calculated error. The PID process calculates a correction factor which is applied to the current output value and stored as a corrected output value in destination device (D). The setup parameters for the PID control loop are stored in 25 consecutive data registers S3+0 through S3+24.
[ S1 ] [ S2 ] [ D ]
D 19 D18 PID
D 20 D 46
Points to note:
a) Every PID application is different. There will be a certain amount of “trial and error”
necessary to set the variables at optimal levels.
b) The PID instruction is only available on FX and FX2C Main Processing Units fitted with CPU
versions 3.11 or greater.
c) On FX2N MPUs a Pre-tuning feature is available that can quickly provide initial values for the
PID process. Refer to page 10-28 for more details.
d) As 25 data register are required for the setup parameters for the PID loop, the head address
of this data stack cannot be greater than D975. The contents of this data stack are explained later in this section. Multiple PID instructions can be programmed, however each PID loop must not have conflicting data registers.
e) There are control limits in the PLC intended to help the PID controlled machines operate in
a safe manner. If it becomes necessary to reset the Set Point Value (S1) during operation, it is recommended to turn the PID command Off and restore the command after entering the new Set Point Value. This will prevent the safety control limits from stopping the operation of the PID instruction prematurely.
f) The PID instruction has a special set of error codes associated with it. Errors are identified
in the normal manner. The error codes associated with the PID loop will be flagged by M8067 with the appropriate error code being stored in D8067. These error devices are not exclusive to the PID instruction so care should be taken to investigate errors properly. Please see chapter 6, ‘Diagnostic Devices’ for more information.
g) A full PID iteration does not have to be performed. By manipulation of the setup parameters
P (proportional), I (Integral) or D (derivative) loops may be accessed individually or in a user defined/selected group. This is detailed later in this section.
Operands · Mnemonic Function

Forward PVnf > SV
∆MV KP EVn ( EV n 1 – ( ) – ) TS
TI EVn Dn + + =
EVn PVnf SV – =
TD TS KD TD ⋅ + 2PV – nf 1 – PVnf PVnf 2 – + + ( ) KD TD ⋅ TS KD TD ⋅ + Dn 1 – ⋅ + =
Reverse SV > PVnf
∆MV KP EVn EVn 1 – – ( ) TS
TI EVn + Dn + =
EVn SV PVnf – =
TD TS KD + TD ⋅ = 2PVnf 1 – PVnf – PVnf 2 – – ( ) KD TD ⋅ TS KD + TD ⋅ + Dn 1 – ⋅
PVnf = PVn + α(PVnf-1 - PVn)
EVn = the current Error Value Dn = the Derivative Value EVn-1 = the previous Error Value Dn-1 = the previous Derivative Value SV = the Set Point Value (S1) KP = the Proportion Constant PVn = the current Process Value (S2) α = the Input Filter PVnf = the calculated Process Value TS = the Sampling Time PVnf-1 = the previous Process Value TI = the Integral Time Constant PVnf-2 = the second previous Process Value TD = the Time Derivative Constant ∆MV = the change in the Output KD = the Derivative Filter Constant Manipulation Values MVn = the current Output Manipulation Value (D)
Please see the Parameter setup section for a more detailed description of the variable parameters and in which memory register they must be set.
Forward and Reverse operation (S3+1, b0) The Forward operation is the condition where the Process Value, PVnf, is greater than the Set Point, SV. An example is a building that requires air conditioning. Without air conditioning, the temperature of the room will be higher than the Set Point so work is required to lower PVnf.
The Reverse operation is the condition where the Set Point is higher than the Process Value. An example of this is an oven. The temperature of the oven will be too low unless some work is done to raise it, i.e. - the heating element is turned On.
The assumption is made with PID control that some work will need to be performed to bring the system into balance. Therefore, ∆MV will always have a value. Ideally, a system that is stable will require a constant amount of work to keep the Set Point and Process Value equal.
Dn · Dn

The PID setup parameters are contained in a 25 register data stack. Some of these devices require data input from the user, some are reserved for the internal operation and some return output data from the PID operation. Parameters S3+0 through S3+6 must be set by the user.
Parameter name/function Description Setting
ter S3 + P
S3+0 Sampling time
The time interval set between the reading the current Process Value of the system (PVnf) 1 to 32767 msec
b0 Forward operation(0), Reverse operation (1)
Not applicable b1 Process Value (PVnf) alarm enable, OFF(0)/ ON(1) b2 Output Value (MV) alarm enable, OFF(0)/ON(1) b3 - 15 Reserved S3+2 Input filter α Alters the effect of the input filter. 0 to 99%
direction and alarm control
This is a factor used to align the proportional output in a known magnitude to the change in the Process Value (PVnf). This is the P part of the PID loop.
S3+3 Proportional
This is the I part of the PID loop. This is the time taken for the corrective integral value to reach a magnitude equal to that applied by the proportional or P part of the loop. Selecting 0 (zero) for this parameter disables the I effect.
S3+4 Integral time
This is a factor used to align the derivative output in a known proportion to the change in the Process Value (PVnf) 1 to 100%
S3+5 Derivative
This is the D part of the PID loop. This is the time taken for the corrective derivative value to reach a magnitude equal to that applied by the proportional or P part of the loop. Selecting 0 (zero) for this parameter disables the D effect.
S3+6 Derivative time
S3+7 to
S3+19 Reserved for use for the internal processing
This is a user defined maximum limit for the Process Value (PVnf). If the Process Value (PVnf) exceeds the limit, S3+24, bit b0 is set On.
Active when S3+1, b1 is set ON.
This is a user defined lower limit for the Process Value. If the Process Value (PVnf) falls below the limit, S3+24, bit b1 is set On.
S3+21 Process Value, minimum value
This is a user defined maximum limit for the quantity of positive change which can occur in one PID scan. If the Output Value (MV) exceeds this, S3+24, bit b2 is set On.
maximum positive change Active when S3+1, b2 is set ON.
This is a user defined maximum limit for the quantity of negative change which can occur in one PID scan. If the Output Value (MV) falls below the lower limit, S3+24, bit b3 is set On.
Output Value, maximum negative change
b0 High limit exceeded in Process Value (PVnf)
b1 Below low limit for the Process Value (PVnf) b2 Excessive positive change in Output Value (MV) b3 Excessive negative change in Output Value (MV) b4 - 15 Reserved
S3+24 Alarm flags (Read Only)
See Initial values for PID loops for basic guidance on initial PID values; page 5-114. See page 10-24 for additional parameters available with FX2N MPUs.

The PID loop can be configured to offer variations on PID control. These are as follows:
Selection via setup registers
Description S3 +3 (KP) S3+ 4 (TI) S3 + 6 (TD)
P User value Set to 0 (zero) Set to 0 (zero) Proportional effect only
PI User value User value Set to 0 (zero) Proportional and integral effect
PD User value Set to 0 (zero) User value Proportional and derivative effect
PID User value User value User value Full PID
It should be noted that in all situations there must be a proportional or ‘P’ element to the loop.
When a proportional factor is applied, it calculates the difference between the Current Error Value, EVn, and the Previous Error Value, EVn-1. The Proportional Change is based upon how fast the Process Value is moving closer to (or further away from) the Set Point Value NOT upon the actual difference between the PVnf and SV.
Once a proportional change has been applied to an error situation, ‘fine tuning’ the correction can be performed with the I or integral element. Initially only a small change is applied but as time increases and the error is not corrected the integral effect is increased. It is important to note how TI actually effects how fast the total integral correction is applied. The smaller TI is, the bigger effect the integral will have.
The derivative function supplements the effects caused by the proportional response. The derivative effect is the result of a calculation involving elements TD, TS, and the calculated error. This causes the derivative to initially output a large corrective action which dissipates rapidly over time. The speed of this dissipation can be controlled by the value TD: If the value of TD is small then the effect of applying derivative control is increased.
Because the initial effect of the derivative can be quite severe there is a ‘softening’ effect which can be applied through the use of KD, the derivative gain. The action of KD could be considered as a filter allowing the derivative response to be scaled between 0 and 100%.
The phenomenon of chasing, or overcorrecting both too high and too low, is most often associated with the Derivative portion of the equation because of the large initial correction factor.
Control method

To prevent the PID instruction from reacting immediately and wildly to any errors on the Current Value, there is a filtering mechanism which allows the PID instruction to observe and account for any significant fluctuations over three samples. The quantitative effect of the input filter is to calculate a filtered Input Value to the PID instruction taken from a defined percentage of the Current Value and the previous two filtered Input Values. This type of filtering is often called first-order lag filter. It is particularly useful for removing the effects of high frequency noise which may appear on input signals received from sensors. The greater the filter percentage is set the longer the lag time. When the input filter is set to zero, this effectively removes all filtering and allows the Current Value to be used directly as the Input Value.
The PID instruction has many parameters which can be set and configured to the user’s needs. The difficulty is to find a good point from which to start the fine tuning of the PID loop to the system requirements. The following suggestions will not be ideal for all situations and applications but will at least give users of the PID instruction a reasonable points from which to start. A value should be given to all the variables listed below before turning the PID instruction ON. Values should be chosen so that the Output Manipulated Value does not exceed ± 32767. Recommended initial settings:
TS = Should be equal to the total program scan time or a multiple of that scan time, i.e. 2 times, 5 times, etc. α = 50% KP = This should be adjusted to a value dependent upon the maximum corrective action to reach the set point - values should be experimented with from an arbitrary 75% TI = This should ideally be 4 to 10 times greater than the TD time KD = 50% TD = This is set dependent upon the total system response, i.e. not only how fast the programmable controller reacts but also any valves, pumps or motors. For a fast system reaction TD will be set to a quick or small time, this should however never be less than TS. A slower reacting system will require the TD duration to be longer. A beginning value can be TD twice the value of TS.
Care should be taken when adjusting PID variables to ensure the safety of the operator and avoid damage to the equipment.
On FX2N MPUs pre-tuning feature is available that can quickly provide initial values for the PID process. Refer to page 10-28 for more details.
With ALL PID values there is a degree of experimentation required to tune the PID loop to the exact local conditions. A sensible approach to this is to adjust one parameter at a time by fixed percentages, i.e. say increasing (or decreasing) the KP value in steps of 10%. Selecting PID parameters without due consideration will result in a badly configured system which does not perform as required and will cause the user to become frustrated. Please remember the PID process is a purely mathematical calculation and as such has no regard for the ‘quality’ of the variable data supplied by the user/system - the PID will always process its PID mathematical function with the data available.

The partial program shown at below demonstrates which parameters must be set for the functioning of the FX2N. The first step sets the user values for S3+0 to S3+6. The PID instruction will be activated when M4 is On.
From the PID instruction at the bottom of the ladder, S1 = D200; S2 = D201; S3 = D500; and D or MV = D525.
D503: K P = 75%
K75 D503 FNC 12 MOV P
D505: K D = 50%
K50 D505 FNC 12 MOV P
M8002
K 1000 D200 FNC 12 MOV P
FNC 78 FROM K2 K5 D201 K4


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
MNET - F-16NP, Melsec Net Mini FNC 90 5-111
ANRD - F2-6A, Analog Read FNC 91 5-111
ANWR - F2-6A, Analog Write FNC 92 5-112
RMST - F2-32RM, RM Start FNC 93 5-112
RMWR - F2-32RM, RM Write FNC 94 5-113
RMRD - F2-32RM, RM Read FNC 95 5-114
RMMN - F2-32RM, RM Monitor FNC 96 5-114
BLK - F2-30GM, Block FNC 97 5-115
MCDE - F2-30GM, Machine Code FNC 98 5-116
- Not Available FNC 99
Please note: All of the instructions in this section reference chapter, Assigning System Devices for further information.
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page


Used to control the F series net mini module - use with an FX2-24EI
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The MNET instruction is used for communicating bit status signals between an FX PLC and an F- 16NP/NT Melsec Net Mini interface. The head address I/O numbers for both S and D are determined by the position of the FX2- 24EI (connected to the F-16NT/NP) within the FX PLC’s expansion chain. The devices specified for S and D can be used directly within the FX users program. For more information please see page 9-3.

Program steps S1 D2 D2 n
ANRD FNC 91 (F2-6A Analog read)
Used to read the F series analog module - use with an FX2-24EI
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The ANRD instruction is used to read input channel n of an F2-6A analog module. The read analog value is stored at destination device D2. The head address I/O numbers for both Sand D1 are determined by the position of the FX2- 24EI (connected to the F2-6A) within the FX PLC’s expansion chain. The analog data stored at the destination device D2 is in an 8 bit format. The operand nis used to specify which analog channel is being read, i.e. 10 to 13. For more information please see page 9-4.


Program steps S1 D2 D2 n
Used to write to the F series analog module - use with an FX2-24EI
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The ANWR instruction is used to write output data to channel n of an F2-6A analog module. The written analog value is stored in source device S1. The head address I/O numbers for both S2 and Dare determined by the position of the FX2- 24EI (connected to the F2-6A) within the expansion chain. The analog data to be written is stored at the source device S1 in an 8 bit format. The operand nis used to specify which analog channel is being written to, i.e. 0 or 1. For more information please see page 9-4.

Program steps S1 D1 D2 n
Used to start the F series CAM module - use with an FX2-24EI
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The RMST instruction is used to start the operation of an F2-32RM under FX control and to monitor the current status of the F2-32RM.
a) The head address I/O numbers for both S2 and Dare determined by the position of the FX2-
24EI (connected to the F2-6A) within the FX PLC’s expansion chain.
b) The operand nis used to specify which F2-32RM program is active, i.e. 0 or 1.

c) Operand D2 stores the F2-32RM status information.
Status of bit device D2+m
D2+0 BANK 1 (program 1) selected BANK 0 (program 0) selected
D2+1 - Normally OFF
D2+3 1.0 degree steps 0.5 degree steps
D2+4 Normally ON -
D2+5 Clockwise operation (CW) Counter-clockwise operation (CCW)
D2+6 Normal operation - No error Hardware Error
D2+7 Normal operation - No error Software Error
d) For more information please see page 9-4.
Program steps S1 S2 D
Disables outputs of the F series CAM module -use with an FX2-24EI
Y, M, S Note: 16 bit operation uses 16 devices, 32 bit mode uses 32 consecutive devices.
RMWR,RMWRP :7 steps DRMWR, DRMWRP: 13 steps
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ]
[ S2 ]
[ D ]
This instruction sends output disable data to an F2- 32RM programmable CAM switch from an FX PLC. The head address I/O numbers for both S2 and Dare determined by the position of the FX2- 24EI (connected to the F2-32RM) within the FX PLC’s expansion chain. The operand S1 is the head address of either 16 or 32 source bits. The source bits map directly over F2-32RM outputs Y0 to Y37 (numbered in octal) When a source device is turned ON at the FX PLC the F2-32RMs associated devices is disabled.
M500
X40 Y30
For more information please see page 9-4.
Operands · Mnemonic Function · RM write)


RMRD FNC 95 (F2-32RM RM read)
Reads output status of F series CAM module -use with an FX2-24EI
Y, M, S Note: 16 bit operation uses 16 devices, 32 bit mode uses 32 consecutive devices.
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction reads the current status of the outputs of an F2-32RM programmable CAM switch to an FX PLC. The head address I/O numbers for both Sand D1 are determined by the position of the FX2-24EI (connected to the F2-32RM) within the expansion chain. Output statuses of Y0-Y17 (16 bit operation) or Y0-Y37 (32 bit operation are read from the F2- 32RM. The read data is mapped directly over the FX destination devices (head address D2). The D2devices will retain their last status even when the RMRD instruction is turned OFF. For more information please see page 9-4.
Program steps S D1 D2
RMMN FNC 96 (F2-32RM RM monitor)
Monitors data states of F series CAM module -use with an FX2-24EI
KnY, YnM, YnS T, C, D, V, Z
Y Note: uses 8 consecutive devices
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ D2 ] RMMN
[ D1 ] X40
[ S ]
The RMMN instruction is used to read speed (r.p.m.) or current angular position from the F2- 32RM to an FX PLC. There it is stored at the device specified by operand D2. The decision for which data is read, i.e. speed or position is made by the F2-32RM through its hardware switch #4. The head address I/O numbers for both S and D1 are deter-mined by the position of the FX2-24EI (connected to the F2-32RM) within the FX PLC’s expansion chain. For more information please see page 9-4.
ON
D 2
OFF
speed (r.p.m)

Program steps S1 S2 D
BLK FNC 97 (F2-30GM Block)
Identifies a block number to the F2-30GM - use with an FX2-24EI
K, H KnX, KnY, KnM, KnS T, C, D, V, Z
Y Note: uses 8 consecutive devices
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ]
[ S2 ]
[ D ]
The BLK instruction is used to designate a block number (S1)to an F2-30GM pulse output unit through a controlling FX PLC.
K 0
X40 Y30
Points to note:
a) The head address I/O numbers for both Sand D1 are determined by the position of the FX2-
24EI (connected to the F2-30GM) within the FX PLC’s expansion chain.
b) Effective block numbers which can be specified for S1 are 0 to 31 (in decimal). Data which is
to be used for S1 cannot be in a BCD format, i.e data should not be read directly in (using KnX for example) from BCD thumbwheels.
c) When an F2-30GM is used and the BLK
instruction is not required, the program opposite is needed to ensure the FX2-24EI recognizes and operates correctly for the connected F2-30GM.
X40 Y30 BLK K 0
d) For more information please see page 9-5.
Operands · Mnemonic Function

Program steps S D1 D2
MCDE FNC 98 (F2-30GM Machine code)
Reads a set codes from the F2-30GM - use with an FX2-24EI
Y Note: uses 8 consecutive devices
Y, M, S Note: uses 64 consecutive (numbered in octal) devices
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ]
[ D1 ]
[ D2 ]
This instruction allows an FX PLC to read the machine codes of an F2-30GM. There are 64 machine code points in the F2-30GM. These are numbered in octal, i.e. 0 to 77 and are prefixed by M.
Y30 M500
Points to note:
a) The head address I/O number for both Sand D1 is determined by the position of the FX2-
24EI (connected to the F2-30GM) within the expansion chain.
b) When the F2-30GM operates a machine code (one of the M0 to M77 devices), an
associated destination device (D2) is activated. D2 devices directly map to the machine codes of the F2-30GM, i.e. when the F2-30GM activates M7, D2+7 (in octal) at the FX PLC also activates. If the data used in the sample instruction above is used and M77 at the F2- 30GM is ON - so will (D2+77 an octal addition) M577 at the FX PLC be ON (while the MCDE instruction is active).
c) To make the associate numbering easy between FX and F2-30GM it is recommended that
the lower two digits of the head address used to specify D2 are zero, i.e.’00’ when S or M devices are used in the FX PLC.
d) For more information please see page 9-5.
Operands · Mnemonic Function

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
Floating Point 1 Page
ECMP - Float Compare FNC 110 5-119
EZCP - Float Zone Compare FNC 111 5-119
- Not Available FNC 112 to 117
EBCD - Float to Scientific FNC 118 5-120
EBIN - Scientific to Float FNC 119 5-120
EADD - Float Add FNC 120 5-121
ESUB - Float Subtract FNC 121 5-122
EMUL - Float Multiplication FNC 122 5-122
EDIV - Float Division FNC 123 5-123
- Not Available FNC 124 to 126
ESQR - Float Square Root FNC 127 5-123
PPP - Not Available FNC 128
INT - Float to Integer FNC 129 5-124
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.

Program steps S1 S2 D
ECMP FNC 110 (Floating Point Compare)
Compares two floating point values - results of are given
K, H - integer value automati- cally converted to floating point
D - must be in floating point format (32bits).
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
DECMP M8000
[ S1 ] [ S2 ] [ D ]
The data of S1 is compared to the data of S2. The result is indicated by 3 bit devices specified with the head address entered as D. The bit devices indicate:
M16
D20 < D12
M17
S2 is less than < S1 - bit device D is ON S2 is equal to = S1 - bit device D+1 is ON S2 is greater than > S1 - bit device D+2 is ON
M18
D20 > D12
Points to note:
The status of the destination devices will be kept even if the ECMP instruction is deactivated. Full algebraic comparisons are used: i.e. -1.79 × 10 27 is smaller than 9.43 × 10 -15

Program steps S1 S2 S3 D
Compares a float range with a float value - results of are given
K, H - integer value automatically converted to floating point
D - must be in floating point format (32 bits). Note: S1 must be less than S2
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The operation is the same as the ECMP instruction except that a single data value (S3) is compared to a data range (S1 - S2). S3 is less than S1 and S2 - bit device D is ON S3 is between S1 and S2 - bit device D+1 is ON S3 is greater than S2 - bit device D+2 is ON
D50 D60 D100 M50 [ S1 ] [ S2 ] [ S3 ] [ D ]
Operands · Mnemonic Function


Converts floating point number format to scientific number format
D - must be in floating point format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Converts a floating point value at S into separate
mantissa and exponent parts at D and D+1
(scientific format).
a) The instruction must be double word format. The destinations D and D+1 represent the
mantissa and exponent of the floating point number respectively.
b) To provide maximum accuracy in the conversion the mantissa D will be in the range 1000 to
9999 (or 0) and the exponent D+1 corrected to an appropriate value.
c) E.g. S= 3.4567 × 10 -5 will become D= 3456, D+1 = -8

Converts scientific number format to floating point number format
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
Generates a floating point number at D from scientific format data at source S.
a) The instruction must be double word format. The source data Sand S+1 represent the
mantissa and exponent of the floating point number to be generated.
b) To provide maximum accuracy in the conversion the mantissa S must be in the range 1000
to 9999 (or 0) and the exponent S+1 corrected to an appropriate value.
c) E.g. S= 5432, S+1 = 12 will become D= 5.432 x 10 9

Program steps S1 S2 D
EADD FNC 120 (Floating Point Addition)
Adds two floating point numbers together
K, H - integer value automatically converted to floating point
D - a floating point value (32 bits).
D - must be in floating point format (32 bits).
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS
Zero M8020 Borrow M8021
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The floating point values stored in the source devices S1 and S2 are algebraically added and the result stored in the destination device D.
K52000 D106 D108
Points to note:
a) The instruction must use the double word format; i.e., DEADD or DEADDP. All source data
and destination data will be double word; i.e. uses two consecutive data registers to store the data (32 bits). Except for K or H, all source data will be regarded as being in floating point format and the result stored in the destination will also be in floating point format.
b) If a constant K or H is used as source data, the value is converted to floating point before
the addition operation.
c) The addition is mathematically correct: i.e., 2.3456 × 10 2 + (-5.6 × 10 -1) = 2.34 × 10 2
d) The same device may be used as a source and as the destination. If this is the case then,
on continuous operation of the DEADD instruction, the result of the previous operation will be used as a new source value and a new result calculated. This will happen every program scan unless the pulse modifier or an interlock program is used.
e) If the result of the calculation is zero “0” then the zero flag, M8020 is set ON.
If the result of the calculation is larger than the largest floating point number then the carry flag, M8021 is set ON and the result is set to the largest value. If the result of the calculation is smaller than the smallest floating point number then the borrow flag, M8022 is set ON and the result is set to the smallest value.
For more information about the format of floating point number refer to page 4-46.
Operands · Mnemonic Function · Carry M8022


K, H - integer value automati- cally converted to floating point D - must be in floating point number format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The floating point value of S2 is subtracted from the floating point value of S1and the result stored in destination device D.
All points of the EADD instruction apply, except that a subtraction is performed. See page 5-122.

K, H - integer value automati- cally converted to floating point
D - must be in floating point format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The floating point value of S1is multiplied with the floating point value of S2. The result of the multiplication is stored at D as a floating point value.
Point a, b, c and d of the EADD instruction apply, except that a multiplication is performed. See page 5-122.


K, H - integer value automati- cally converted to floating point
D - must be in floating point format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The floating point value of S1 is divided by the floating point value of S2. The result of the division is stored in D as a floating point value. No remainder is calculated.
Points a, b, c, d of the EADD instruction apply, except that a division is performed. See page 5-122.

Calculates the square root of a floating point value.
K, H - integer value automati- cally converted to floating point
D - must be in floating point number format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
A square root is performed on the floating point value of Sand the result is stored in D.
Points a, b, c, d of the EADD instruction apply, except that a square root is performed. See page 5-122.

Mnemonic Function Operands Program steps S D
INT FNC 129 (Float to Integer)
Converts a number from floating point format to decimal format
D - must be in floating point number format (always 32 bits).
D - decimal format
for INT, INTP - 16 bits
for DINT, DINTP - 32 bits
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS
Zero M8020 Borrow M8021
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
M25
The floating point value of S is rounded down to
D510 D254
the nearest integer value and stored in normal
binary format in D.
a) The source data is always a double (32 bit) word; a floating point value.
For single word (16 bit) operation the destination is a 16 bit value. For double word (32 bit) operation the destination is a 32 bit value.
b) This instruction is the inverse of the FLT instruction. (See page 5-49)
c) If the result is 0 then the zero flag M8020 is set ON.
If the source data is not a whole number it must be rounded down. In this case the borrow flag M8021 is set ON to indicate a rounded value. If the resulting integer value is outside the valid range for the destination device then an overflow occurs. In this case the carry flag M8022 is set on to indicate overflow. Note: If overflow occurs, the value in the destination device will not be valid.
Carry M8022

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
Floating point 3 Page
SIN - Sine FNC 130 5-127
COS - Cosine FNC 131 5-128
TAN - Tangent FNC 132 5-128
- Not Available FNC 133 to 139
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.


D - must be in floating point number format (32 bits).(radians)
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction performs the mathematical SIN operation on the floating point value in S. The result is stored in D.
a) The instruction must use the double word format: i.e., DSIN or DSINP. All source and
destination data will be double word; i.e., uses two consecutive data registers to store the data (32 bits). The source data is regarded as being in floating point format and the destination is also in floating point format.
b) The source value must be an angle between 0 to 360 degrees in radians; i.e.,
Radian Angles
Below is an program example of how to calculate angles in radians using floating point.

K45 degrees to D0
K90 degrees to D0
Convert D0 to float in D4,D5
Calculate π in radians (π/180) Store as a float in D20,D21 Calculate angle in radians in D30,D31 (deg° × π/180 = rads)
Calculate SIN of angle in D100


D - must be in floating point number format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction performs the mathematical COS operation on the floating point value in S. The result is stored in D.
All the points for the SIN instruction apply, except that COS is calculated. See page 5-127.

D - must be in floating point number format (32 bits).
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
This instruction performs the mathematical TAN operation on the floating point value in S. The result is stored in D.
All the points for the SIN instruction apply, except that COS is calculated. See page 5-127.

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
- Not Available FNC 140 to 146
SWAP - Float to Scientific FNC 147 5-131
- Not Available FNC 148 to 149
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

Mnemonic Function Operands Program steps S
SWAP FNC 147 (Byte Swap)
The high and low byte of the designated devices are exchanged
KnY, KnM, KnS, T, C, D, V, Z SWAP,SWAPP : 5 steps DSWAP, DSWAPP: 9 steps
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The upper byte and the lower byte of the source device are swapped. This instruction is equivalent to operation 2 of FNC 17 XCH (see page 5-21).
Points to note:
a) In single word (16 bit) operation the upper and lower byte of the source device are
exchanged.
b) In double word (32 bit) operation the upper and lower byte of each or the two 16 bit devices
are exchanged. Result of DSWAP(P) D10:
Values are in Hex for clarity
Before DSWAP After DSWAP
8B H
D10
8B H
1F H
C4 H
35 H
D11
35 H
C4 H
c) If the operation of this instruction is allowed to execute each scan, then the value of the
source device will swap back to its original value every other scan. The use of the pulse modifier or an interlock program is recommended.


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
TCMP - Time Compare FNC 160 5-135
TZCP - Time Zone Compare FNC 161 5-136
TADD - Time Add FNC 162 5-137
TSUB - Time Subtract FNC 163 5-138
- Not Available FNC 164 to 165
TRD - Read RTC data FNC 166 5-139
TWR - Set RTC data FNC 167 5-140
- Not Available FNC 168 to 169
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page

Program steps S1 S2 S3 S D
TCMP FNC 160 (Time Compare)
Compares two times - results of are given
K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
T, C, D Y, M, S TCMP, TCMPP: 11 steps Note: 3 consecutive devices are used.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ S ] [ S3 ] [ D ]
S1, S2 and S3 represent hours, minutes and seconds respectively. This time is compared to the time value in the 3 data devices specified by the head address S. The result is indicated in the 3 bit devices specified by the head address D.
M0
ON when D0,D1,D2 < 10:30:50
ON when D0,D1,D2 = 10:30:50
ON when D0,D1,D2 > 10:30:50
The bit devices in D indicate the following:
D+0 is set ON, when the time in S is less than the time in S1, S2 and S3. D+1 is set ON, when the time in S is equal to the time in S1, S2 and S3. D+2 is set ON, when the time in S is greater than the time in S1, S2 and S3.
a) The status of the destination devices is kept, even if the TCMP instruction is deactivated.
b) The comparison is based on the time value specified in the source devices.
- The valid range of values for S1and S+0 is 0 to 23 (Hours).
- The valid range of values for S2and S+1 is 0 to 59 (Minutes).
- The valid range of values for S3and S+2 is 0 to 59 (Seconds).
c) The current time of the real time clock can be compared by specifying D8015 (Hours),
D8014 (Minutes) and D8013 (Seconds) as the devices for S1, S2 and S3 respectively.
Operands · Mnemonic Function

Program steps S1 S2 S D
TZCP FNC 161 (Time Zone Compare)
Compares a time to a specified time range - results of are given
T, C, D S1 must be less than or equal to S2.
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] [ S ] [ D ]
S 1, S 2 and S represent time values. Each specifying the head address of 3 data devices. S is compared to the time period defined by S1 and S2. The result is indicated in the 3 bit devices specified by the head address D.
M0
ON when D0,D1,D2 < D20,D21,D22
ON when D20,D21,D22 £ D0,D1,D2 £ D30,D31,D32
ON when D30,D31,D32 < D0,D1,D2
The bit devices in D indicate the following:
D+0 is set ON, when the time in S is less than the times in S1 and S2. D+1 is set ON, when the time in S is between the times in S1 and S2. D+2 is set ON, when the time in S is greater than the times in S1 and S2.
a) The status of the destination devices is kept, even if the TCMP instruction is deactivated.
b) The comparison is based on the time value specified in the source devices.
- The valid range of values for S1and S+0 is 0 to 23 (Hours).
- The valid range of values for S2and S+1 is 0 to 59 (Minutes).
- The valid range of values for S3and S+2 is 0 to 59 (Seconds).
Operands · Mnemonic Function

Program steps S1 S2 D
TADD FNC 162 (Time Addition)
Adds two time values together to give a new time
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020 Carry M8022
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
D10 D20 D30 TSUB X13 [ S1 ] [ S2 ] [ D ]
Each of S1, S2 and D specify the head address of 3 data devices to be used a time value. The time value in S1 is added to the time value in S2, the result is stored to D as a new time value.
a) The addition is performed according to standard time values. Hours, minutes and seconds
are kept within correct limits. Any overflow is correctly processed.
S 2
D
10:30:29
03:10:49
13:41:16
b) If the addition of the two times results in a value greater than 24 hours, the value of the
result is the time remaining above 24 hours.
S 2
D
10:17:29
18:12:34
04:30:03
When this happens the carry flag M8022 is set ON.
c) If the addition of the two times results in a value of zero (0:00:00: 0 hours, 0 minutes, 0
seconds) then the zero flag M8020 is set ON.
d) The same device may be used as a source (S1 or S2) and destination device. In this case
the addition is continually executed; the destination value changing each program scan. To prevent this from happening, use the pulse modifier or an interlock program.

Program steps S1 S2 D
TSUB FNC 163 (Time Subtrac- tion)
Subtracts one time value from another to give a new time
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION FLAGS Zero M8020 Borrow M8021
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
D10 D20 D30 TSUB X13 [ S1 ] [ S2 ] [ D ]
Each of S1, S2 and D specify the head address of 3 data devices to be used a time value. The time value in S1 is subtracted from the time value in S2, the result is stored to D as a new time value.
a) The subtraction is performed according to standard time values. Hours, minutes and
seconds are kept within correct limits. Any underflow is correctly processed.
S 2
D
10:30:27
03:10:49
07:19:38
b) If the subtraction of the two times results in a value less than 00:00:00 hours, the value of
the result is the time remaining below 00:00:00 hours.
S 2
D
10:17:29
18:12:34
16:04:55
When this happens the borrow flag M8021 is set ON.
c) If the subtraction of the two times results in a value of zero (00:00:00 hours) then the zero
flag M8020 is set ON.
d) The same device may be used as a source (S1 or S2) and destination device. In this case
the subtraction is continually executed; the destination value changing each program scan. To prevent this from happening, use the pulse modifier or an interlock program.


Reads the current value of the real time clock to a group of registers
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The current time and date of the real time clock are read and stored in the 7 data devices specified by the head address D.
The 7 devices are set as follows:


The year is read as a two digit number. This can be change to a 4 digit number by setting D8018 to 2000 during the first program scan; see following program extract.
K2000 D8018 MOV
If this is done then the clock year should not be used during the first scan as it will be a two
digit number before the instruction and a value of 2000 after the instruction until the END instruction executes. After the first scan the year is read and written as a 4 digit number.
The FX-10DU-E, FX-20DU-E and FX-25DU-E only support a 2 digit year.

Mnemonic Function Operands Program steps S
TWR FNC 167 (Time Write)
Sets the real time clock to the value stored in a group of registers
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S ]
The 7 data devices specified with the head ad- dress S are used to set a new current value of the real time clock.
D20 TWR
The seven devices
Device Meaning Values Device Meaning
S+0 Year 00-99 ⇒ D8018 Year
S+1 Month 01-12 ⇒ D8017 Month
S+2 Date 01-31 ⇒ D8016 Date
S+3 Hours 00-23 ⇒ D8015 Hours
S+4 Minutes 00-59 ⇒ D8014 Minutes
S+5 Seconds 00-59 ⇒ D8013 Seconds
S+6 Day 0-6 (Sun-Sat) ⇒ D8019 Day
This instruction removes the need to use M8015 during real time clock setting. When setting the time it is a good idea to set the source data to a time a number of minutes ahead and then drive the instruction when the real time reaches this value.

Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
In-line Comparisons 5-146
FNC 220-249

Contents:
GRY - Decimal to Gray Code FNC 170 5-143
GBIN - Gray Code to Decimal FNC 171 5-143
- Not Available FNC 172 to 177
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
DP - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page


K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The binary integer value in S is converted to the GRAY CODE equivalent and stored at D.
The nature of gray code numbers allows numeric values to be quickly output without the need for a strobing signal. For example, if the source data is continually incremented, the new output data can be set each program scan.

K, H, KnX, KnY, KnM, KnS, T, C, D, V, Z
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The GRAY CODE value in S is converted to the normal binary equivalent and stored at D.
This instruction can be used to read the value from a gray code encoder. If the source is set to inputs X0 to X17 it is possible to speed up the reading time by adjusting the refresh filter with FNC 51 REFF.


Program Flow 5-4
Move And Compare 5-16
FNC 10 - 19
Arithmetic And Logical Operations (+, -, × , ÷ )
FNC 20 - 29
5-24 Rotation And Shift 5-34
FNC 30 - 39
Data Operation 5-42
FNC 40 - 49
High Speed Processing 5-52
FNC 50 - 59
Handy Instructions 5-66
FNC 60 - 69
External FX I/O Devices 5-80
FNC 70 - 79
External FX Serial Devices 5-94
FNC 80 - 89
External F2 Units 5-110
FNC 90 - 99
Floating Point 1 & 2 5-118
FNC 110-129
Trigonometry (Floating Point 3) 5-126
FNC 130-139
Data Operations 2 5-130
FNC 140-149
Real Time Clock Control 5-134
FNC 160-169
Gray Codes 5-142
FNC 170-179
16.
In-line Comparisons 5-146
FNC 220-249

Contents:
LD - LoaD compare FNC 224 to 230 5-119
AND - AND compare FNC 232 to 238 5-120
OR - OR compare FNC 240 to 246 5-120
D - Destination device. S - Source device. m, n- Number of active devices, bits or an operational constant. Additional numeric suffixes will be attached if there are more than one operand with the same function e.g. D1, S3 or for lists/tabled devices D3+0, S+9 etc. MSB - Most Significant Bit, sometimes used to indicate the mathematical sign of a number, i.e. positive = 0, and negative = 1. LSB - Least Significant Bit.
- An instruction operating in 16 bit mode, where identifies the instruction mnemonic.
P - A 16 bit mode instruction modified to use pulse (single) operation.
D - An instruction modified to operate in 32 bit operation.
D - A 32 bit mode instruction modified to use pulse (single) operation.
- A repetitive instruction which will change the destination value on every scan unless
modified by the pulse function. - An operand which cannot be indexed, i.e. The addition of V or Z is either invalid or will
have no effect to the value of the operand.
Page


Initial comparison contact. Active when the comparison S1 S2 is true.
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
where is =, >,

FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
The value of S1 and S2 are tested according to the comparison of the instruction. If the comparison is true then the LD contact is active. If the comparison is false then the LD contact is not active.
The LD comparison functions can be placed anywhere in a program that a standard LD instruction can be placed. I.e., it always starts a new block. (See page 2-3 for LD instruction)

224 LD = DLD = S1 = S2 S1 ≠ S2
225 LD > DLD > S1 > S2 S1 ≤ S2
226 LD < DLD < S1 < S2 S1 ≥ S2
228 LD DLD S1 ≠ S2 S1 = S2
229 LD ≤ DLD ≤ S1 ≤ S2 S1 > S2
230 LD ≥ DLD ≥ S1 ≥ S2 S1 < S2


Serial comparison contact. Active when the comparison S1 S2 is true.
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
where is =, >,

FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ] X000
The value of S1 and S2 are tested according to the comparison of the instruction. If the comparison is true then the AND contact is active. If the comparison is false then the AND contact is not active.
The AND comparison functions can be placed anywhere in a program that a standard AND instruction can be placed. I.e., it is a serial connection contact. (See page 2-6 for AND instruction)

232 AND = DAND = S1 = S2 S1 ≠ S2
233 AND > DAND > S1 > S2 S1 ≤ S2
234 AND < DAND < S1 < S2 S1 ≥ S2
236 AND DAND S1 ≠ S2 S1 = S2
237 AND ≤ DAND ≤ S1 ≤ S2 S1 > S2
238 AND ≥ DAND ≥ S1 ≥ S2 S1 < S2

Program steps S D
OR (OR compare)
Parallel comparison contact. Active when the comparison S1 S2 is true.
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
K,H, KnX, KnY, KnM, KnS, T, C, D, V, Z
where is =, >,
16 BIT OPERATION
FX FX0N FX0(s) FX(2C) FX2N(C) 32 BIT OPERATION
FX(2C) FX FX2N(C) FX0N FX0(s)
FX(2C) FX FX2N(C) FX0N FX0(s)
[ S1 ] [ S2 ]
K200 C10 OR =
X002 M30
M60
D100 K100000 OR £
Operation:
The value of S1 and S2 are tested according to the comparison of the instruction. If the comparison is true then the OR contact is active. If the comparison is false then the OR contact is not active.
The OR comparison functions can be placed anywhere in a program that a standard OR instruction can be placed. I.e., it is a parallel connection contact. (See page 2-7 for OR instruction)
FNC No.
when 16 bit 32 bit
240 OR = DOR = S1 = S2 S1 ≠ S2
241 OR > DOR > S1 > S2 S1 ≤ S2
242 OR < DOR < S1 < S2 S1 ≥ S2
244 OR DOR S1 ≠ S2 S1 = S2
245 OR ≤ DOR ≤ S1 ≤ S2 S1 > S2
246 OR ≥ DOR ≥ S1 ≥ S2 S1 < S2


FX Series Programmable Controllers Diagnostic Devices 6
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Diagnostic Devices 6
6. Diagnostic Devices 6-1 6.1 PC Status (M8000 to M8009 and D8000 to D8009) 6-2 6.2 Clock Devices (M8010 to M8019 and D8010 to D8019) 6-3 6.3 Operation Flags 6-4 6.4 PC Operation Mode (M8030 to M8039 and D8030 to D8039) 6-5 6.5 Step Ladder (STL) Flags (M8040 to M8049 and D8040 to D8049) 6-6 6.6 Interrupt Control Flags (M8050 to M8059 and D8050 to D8059) 6-7 6.7 Error Detection Devices (M8060 to M8069 and D8060 to D6069) 6-8 6.8 Link And Special Operation Devices (M8070 to M8099 and D8070 to D8099) .. 6-9 6.9 Miscellaneous Devices (M8100 to M8119 and D8100 to D8119) 6-10 6.10 Communication Adapter Devices, i.e. 232ADP, 485ADP (M8120 to M8129 and D8120 to D8129) 6-10 6.11 High Speed Zone Compare Table Comparison Flags (M8130 to M8139 and D8130 to D8139) 6-11 6.12 Miscellaneous Devices (M8160 to M8199) 6-12 6.13 Index Registers (D8180 to D8199) 6-13 6.14 Up/Down Counter Control (M8200 to M8234 and M8200 to D8234) 6-14 6.15 High Speed Counter Control (M8235 to M8255 and D8235 to D8255) 6-14 6.16 Error Code Tables 6-15

FX Series Programmable Controller
The following special devices are used by the PLC to highlight the current operational status and identify any faults or errors that may be occurring. There are some variations in the application of these devices to members of the FX PLC family, these are noted where appropriate. The Internal diagnostic devices consist of both auxiliary (M) coils and data (D) registers. Often there is a correlation between both M and D diagnostic devices for example M8039 identifies that the PLC is in constant scan mode but D8039 contains the value or length of the set constant scan.
Any device of type M or D that is marked with a “( )” cannot be set by a users program. In the case of M devices this means the associated coil cannot be driven BUT all contacts can be read. And for data devices (D) new values cannot be written to the register by a user BUT the register contents can be used in a data comparison.
Diagnostic Devices 6

FX Series Programmable Controller Diagnostic Devices 6
M8000 ( ) RUN monitor NO contact
D8000 () Watchdog timer
FX, FX2C: 100ms FX0, FX0S, FX0N, FX2N: 200ms See note 1
M8001 ( ) RUN monitor NC contact
D8001 ( ) PLC type and version
20Vvv FX0(S), FX0N, FX, FX2C version V.vv 24Vvv: FX2N version V.vv
M8002 ( ) Initial pulse NO contact
D8002 ( ) Memory capacity
M8003
00H = RAM, 01H = EPROM, 02H = EEPROM, 0AH = EEPROM (protected) 10H = MPU memory
M8003 ( ) Initial pulse NC contact
D8003 ( ) Memory type
The contents of this register identifies which error flag is active, i.e. if = 8060 identifies M8060
ON when one or more error flags from the range M8060 to M8067 are ON
M8004 ( ) Error occurrence
D8004 ( ) Error number M
M8005 Battery voltage Low
On when the battery voltage is below the value set in D8006
E.g. 36 = 3.6 volts
M8006 Battery error latch
D8006 Low battery voltage
Latches the battery Low error
The level at which a battery voltage low is detected
M8007 Momentary power failure
D8007 Power failure count
The number of time a momen- tary power failure has occurred since power ON.
D8008 Power failure detection
The time period before shut down when a power failure occurs (default 10ms)
M8008 Power failure Power loss has occurred
D8009 24V DC failed device
M8009 24V DC Down Power failure of 24V DC service supply
Lowest device affected by 24V DC power failure
For symbol key see page 6-1. Note 1:
Approx. 5msec
General note:
D8008 10msec (Power failure detection period)

FX Series Programmable Controller Diagnostic Devices 6
D8010 ( ) Present scan time
Current operation cycle / scan time in units of 0.1 msec
M8011 ( ) 10 msec clock pulse
D8011 ( ) Minimum scan time
Minimum cycle/ scan time in units of 0.1 msec
Oscillates in 10 msec cycles
Maximum cycle/ scan time in units of 0.1 msec (waiting time for constant scan mode is not included) M8013 ( ) 1 sec clock pulse
M8012 ( ) 100 msec clock pulse
D8012 ( ) Maximum scan time
Oscillates in 100 msec cycles
Oscillates in 1 sec cycles
M8014 ( ) 1 min clock pulse
Oscillates in 1 min cycles
The following devices apply to FX2N(C) PLC’s and to FX0N, FX and FX2C PLC’s when a
real time clock cassette is installed.
Seconds data for use with an RTC cassette (0 - 59) (FX0(S), FX0N see note 2)
Minute data for use with an RTC cassette (0-59)
When ON - clock stops, ON OFF restarts clock
Hour data for use with an RTC cassette (0-23)
When ON D8013 to 19 are frozen but clock continues
Day data for use with an RTC cassette (1-31)
M8017 Min. rounding
When pulsed ON set RTC to nearest minute
Month data for use with an RTC cassette (1-12)
M8018 ( ) RTC available
When ON Real Time Clock is installed
Year data for use with an RTC cassette (0-99)
Clock data has been set out of range
Weekday data for use with an RTC cassette (0-6)
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
Set when the result of an ADD (FNC 20) or SUB (FNC 21) is “0”
D8020 (FX0/FX0S/ FX0N only)
Input filter setting for devices X000 to X007 default is 10 msec, (0-15)
M8020 ( ) Zero
Set when the result of a SUB (FNC 21) is less than the min. negative number
Input filter setting for devices X000 to X017 default is 10 msec, (0-15)
M8021 ( ) Borrow
D8020 (FX2N(C) only)
Set when ‘carry’ occurs dur- ing an ADD (FNC 20) or when an overflow occurs as a result of a data shift opera- tion
M8022 () Carry
D8021 (FX0/FX0S only)
Input filter setting for devices X010 to X017 default is 10 msec, (0-15)
Set to enable floating point operations. This flag can be used with BCD, BIN, ADD, SUB, MUL,DIV, SQR and FLT applied instructions
M8023 () Float operation flag (FX2C only)
When ON HSC (FNC 53 - 55) instructions are processed even when the external HSC reset input is activated M8026 (Not FX0(S), FX0N)
M8025 (Not FX0(S), FX0N)
RAMP (FNC 67) hold mode
M8027 (Not FX0(S), FX0N)
PR (FNC 77) 16 element data string
FX0(S), FX0N: Change timers T32 to T55 to 10ms type FX, FX2C, FX2N: enable interrupts during FROM/ TO
D8028 ( ) Current value of the Z index register
M8029 ( ) Instruction execution complete
Set on the completion of operations such as DSW (FNC 72), RAMP (FNC 67) etc.
D8029 ( ) Current value of the V index register
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
M8030 () Battery LED OFF (Not FX0(S), FX0N)
Battery voltage is low but BATT.V LED not lit
D8030 ( ) (FX0N only)
Value read from first setting “pot” in msec, (0 to 255)
Current device settings are reset at next END, i.e. con- tacts, coils and current data values for Y, M, S, T, C and D devices respectively. Spe- cial devices which have default settings are refreshed with those defaults
This register is used as the 3rd storage device when Z or V has been selected as the destination for the SPD instruction (FNC 56)
M8031 () Non-latch memory all clear
D8030 (Not FX0(S), FX0N)
M8032 () Latch memory all clear
D8031 ( ) (FX0N only)
Value read from second set- ting “pot” in msec, (0 to 255)
The device statuses and set- tings are retained when the PLC changes from RUN to STOP and back into RUN
M8033 () Memory hold in ‘stop’ mode
All of the physical switch gear for activating outputs is disabled. However, the pro- gram still operates normally.
M8034 () All outputs disable
M8035 (S) Forced operation mode
By using forced operation mode, i.e.M8035 is turned ON, it is possible to perform remote RUN/STOP or pulsed RUN/ STOP opera- tion. Please see Chapter 10 for example operation
M8036 (S) Forced RUN signal
M8037 (S) Forced STOP signal
M8038() RAM file registers clear (FX(2C) only)
Used to clear the contents of the 2000 RAM file registers of any data
When ON the PLC executes the user program within a constant scan duration. The difference between the actual end of the program operation and the set con- stant scan duration causes the PLC to ‘pause’.
This register can be written to by the user to define the dura- tion of the constant scan. Res- olutions of 1msec are possible. This register has a default set- ting 0 msec which will be initi- ated during power ON.
M8039 () Constant scan mode
D8039 () Constant scan duration
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
M8040 () STL transfer disable
D8040 ( ) Lowest active STL step
When ON STL state trans- fer is disabled
When ON STL transfer from initial state is enabled dur- ing automatic operation (ref. IST FNC 60)
D8041 ( ) 2nd active STL state
M8041 (S) Transfer start
A pulse output is given in response to a start input (ref. IST FNC 60)
M8042 () Start pulse
D8042 ( ) 3rd active STL state
M8043 (S) Zero return complete
On during the last state of ZERO RETURN mode (ref. IST FNC 60)
D8043 ( ) 4th active STL state
Up to 8 active STL states, from the range S0 to S899, are stored in D8040 to D8047 in ascending numerical order. (Updated at END)
M8044 (S) Zero point condition
ON when the machine zero is detected (ref. IST FNC 60)
D8044 ( ) 5th active STL state
Disables the ‘all output reset’ function when the operation mode is changed (ref. IST FNC 60)
M8045 () All output reset disable
D8045 ( ) 6th active STL state
ON when STL monitoring has been enabled (M8047) and there is an active STL state
D8046 ( ) 7th active STL state
M8046 ( ) STL state ON
M8047 () Enable STL monitoring
When ON D8040 to D8047 are enabled for active STL step monitoring
D8047 ( ) 8th active STL state
M8048 ( ) Annunciator ON (Not FX0(S), FX0N)
ON when Annunciator moni- toring has been enabled (M8049) and there is an active Annunciator flag
M8049 () Enable Annunciator monitoring (Not FX0(S), FX0N)
D8049 ( ) Lowest active Annunciator (Not FX0(S), FX0N)
Stores the lowest currently active Annunciator from the range S900 to S999 (Updated at END)
When ON D8049 is enabled for active Annunciator state monitoring
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
M8050 () I00 disable
When the EI (FNC 04) instruction is driven in the user program, all interrupts are enabled unless the spe- cial M devices noted here are driven ON. In that case for each special M coil that is ON, the associated interrupt is disabled, i.e. will not oper- ate. Note denotes all types of that interrupt
D8050 -D8059 Reserved M8051 () I10 disable
M8052 () I20 disable
M8053 () I30 disable
The following assignments only refer to
The following assignments only refer to
FX, FX2C FX2N(C) PLC’s
FX0, FX0S and FX0N PLC’s
M8054 () I40 disable
M8055 () I50 disable M8055 Reserved
M8056 () I6 disable
When the EI (FNC 04) instruction is driven in the user program, all interrupts are enabled unless the spe- cial M devices noted here are driven ON. In that case for each special M coil that is ON, the associated interrupt is disabled, i.e. will not oper- ate. Note denotes all types of that interrupt
M8056 () X0 pulse catch
When the leading edge of a pulse is received at an input from the range X0 to X3 the associated M device detailed here is set ON. By resetting the same device within the user program the next pulse occurrence will again set the M coil ON. Hence, fast input pulses are 'caught' and stored. This operation contin- ues regardless of any EI (FNC04) and DI (FNC 5) instructions. For FX, FX2C, FX2N operation see page 6-12
M8057 () I7 disable
M8057 () X1 pulse catch
M8058 () I8 disable
M8058 () X2 pulse catch
M8059() I010 to I060 disabled as a single group (FX(2C), FX2N only)
M8059 () X3 pulse catch
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
PLC STATUS M8060 ( ) I/O configura- tion error (Not FX0(S), FX0N)
Device Operation Detection PROG.E
D8060 ( ) (Not FX0(S), FX0N)
The first I/O number of the unit or block causing the error - See note 3
While the PLC is in RUN
M8061 ( ) PLC hardware error
Error code for hardware error - See also appropriate PLC hardware manual
Flash STOP D8061 ( )
M8062 ( ) PC/HPP communication error (Not FX0(S), FX0N)
When a signal from the HPP is received
D8062 ( ) (Not FX0(S), FX0N)
Error code for PC/HPP Com- munications error -See appro- priate error code table
When paired sta- tions sig- nal is received or ADP com- munica- tions are in error
Error code for parallel link error - See also hardware manual. Also identification of ADP communication error - See also FX-485PC-IF users manual
M8063( )(R) Parallel link/ ADP error (Not FX0(S), FX0N)
D8063( )(-R) (Not FX0(S), FX0N)
M8064 ( ) Parameter error
Error code identifying parame- ter error - See appropriate error code table
When the program is changed (PLC in STOP) and when a program is transfer- red (PLC in STOP)
Error code identifying syntax error - See appropriate error code table
M8065 ( ) Syntax error D8065 ( )
Error code identifying program construction error See appropriate error code table
M8066 ( ) Program error
M8067( )(R) Operation error While in PLC is in RUN
Error code identifying opera- tion error. See appropriate error code table
OFF RUN
M8068 () Operation error latch
D8068 () Operation error step number latched
M8069 () I/O bus error (Not FX0(S), FX0N)
Step numbers for found errors corresponding to flags M8065 to M8067
See note 4 - - D8069()(R)

FX Series Programmable Controller Diagnostic Devices 6
For symbol key see page 6-1.
D8060
2 0 0 1
6.8 Link And Special Operation Devices (M8070 to M8099 and D8070 to D8099)
Driven when the PLC is a master station in a parallel link application
D8070 ( ) Parallel link watchdog time - 500 msec
Driven when the PLC is a slave station in a parallel link application
M8072 ( ) ON while the PLC is operat- ing in a parallel link
ON when M8070/ M8071 are incorrectly set during parallel link operations M8074 (FX(2C) only) Activate RAM file registers
D8071 - D8098 Reserved
Free ring timer, range: 0 to 32,767 in units of 0.1 msec (for use in measuring input pulse durations)
M8099 () High speed free timer oper- ation D8099
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
D8102 ( ) Memory Capacity
M8109 () Output refresh error D8109 ( ) Output refresh error device number; 0, 10, 20, etc.
6.10 Communication Adapter Devices, i.e. 232ADP, 485ADP (M8120 to M8129 and D8120 to D8129)
M8120 FX0N only setting data backup flag for 485 network D8120 Communications format
M8121( )(R) RS- Data transmission
delayed D8121 Local station number for 485 data network
M8122 (R) RS- Data transmission flag D8122( )(R) RS- Amount of remaining data
M8123 (R) Finished receiving data D8123( )(R) RS - Amount of data already
received M8124 (FX/FX2C only) RS- Carrier detection flag D8124 RS - Data header, default STX (02H)
M8125 Reserved D8125 232ADP - Data terminator, default ETX (03H) M8126 RS485 - global flag D8126 Reserved
M8127 RS485 - On Demand hand- shake flag D8127 RS485 - On Demand head device register
M8128 RS485 - On Demand error flag D8128 RS485 - On Demand data length register
RS485 - On Demand Byte/ Word flag, ON = Byte, OFF= Word
D8129 RS485 data network ‘time-out’ timer value

FX Series Programmable Controller Diagnostic Devices 6
6.11 High Speed Zone Compare Table Comparison Flags (M8130 to M8139 and D8130 to D8139)
Contains the number of the current record being pro- cessed in the HSZ compari- son table
Selects comparison tables to be used with the HSZ instruction
D8130 ( )( )
Contains the number of the current record being pro- cessed in the HSZ compari- son table when the PLSY operation has been enabled
Identifies when the HSZ comparison table has been processed.
D8131 ( )( )
Contains the source (output pulse frequency) data for the PLSY instruction when used with the HSZ comparison table
Selects the use of the PLSY instruction with the HSZ comparison tables
D8132 ( )( )
Identifies when the HSZ comparison table (when used with the PLSY instruc- tion) has been processed.
Contains a copy of the value for the current comparison when the HSZ comparison table and combined PLSY out- put are used. This data is only available in 32 bit or double word format.
Contains the total number of pulses that have been output using the PLSY (or PLSR) instruction. This data is only available in 32 bit or double word format D8138 - D8139 Reserved
Contains the total number of pulses that have been output to Y0 using the PLSY or PLSR instructions. This data is only available in 32 bit or double word format.
D8140 D8141 ( ) () (FX2N(C) only)
Contains the total number of pulses that have been output to Y1 using the PLSY or PLSR instructions. This data is only available in 32 bit or double word format.
D8142 D8143 ( ) () (FX2N(C) only)
For symbol key see page 6-1

FX Series Programmable Controller Diagnostic Devices 6
Selection of XCH operation to swap bytes in a single data word
Selection of 8 bit operations for applied instructions ASC, RS, ASCI, HEX, CCD
M8161
High speed mode for the PRUN instruction, 2 data words Read/write only
These special M coils can be entered into the HSCS (FNC 53) and HSCR (FNC 54)instructions instead of the associated Interrupt Pointers when using old version of pro- gramming software or hand held programmers. More details on this can be found in the ‘Introduction’ to this manual.
M8162
M8163 -M8166 Reserved M8183 (I030)
Selection of hexadecimal input mode for the HKY instruction
M8167
Selection of BCD mode for use with the SMOV instruc- tion
M8168
M8169 Reserved M8186 (I060) M8170 (R) X0 pulse catch
When the leading edge of a pulse is received at an input from the range X0 to X5 the associated M device detailed here is set ON. By resetting the same device within the user program the next pulse occurrence will again set the M coil ON. Hence, fast input pulses are ‘caught’ and stored. This operation requires the EI (FNC04) instruction to be active. For details of FX0,FX0S and FX0N operation see page 6-7
M8171 (R) X1 pulse catch
M8172 (R) X2 pulse catch
M8191 (+ MOV = FLT) M8173 (R) X3 pulse catch
These special M coils modify the instruction noted in the brackets as ‘+ ’ to per- form the same task as the instruction mnemonic identi- fied as ‘= ’. This is to allow old versions of program- ming software or hand held programmers to access the higher functions introduced on the FX CPU ver 3.07 and the FX2C units. More details on this can be found in the ‘Intro- duction’ to this manual.
M8192 (+SMOV=SORT) M8174 (R) X4 pulse catch
M8175 (R) X5 pulse catch
M8195 (+ FMOV = CCD) M8196 (+FMOV = ASCI) M8197 (+FMOV = HEX)
When this device is set ON it reverses the operation of the Source and Destination devices specified in the instruction. More details on this can be found in the ‘Introduction’ to this manual. M8199 Reserved
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
When M8 is operated, counter C functions as a down counter. When M8 is not operated the associated counter oper- ates as an up counter
For symbol key see page 6-1.
When M8 is operated, the 1 phase high speed counter C functions as a down counter. When M8 is not operated the associated counter oper- ates as an up counter. The available counters depends upon the PLC type. D8235 -D8255 Reserved
When M8 is operated, the 2 phase high speed counter C functions as a down counter. When M8 is not operated the associated counter oper- ates as an up counter. The available counters depends upon the PLC type.
For symbol key see page 6-1.

FX Series Programmable Controller Diagnostic Devices 6
Number Associated Meaning Action
Check the cable connec- tion between the pro- gramming device and the PLC
6101 RAM error 6102 Operation circuit error 6103 I/O bus error (M8069 = ON) 6104 Extension unit 24V failure (M8069=ON)
D8061 PLC Hardware error
Program execution time has exceeded the WDT time value set in D8000.
6105 Watch Dog Timer error
Number Associated Meaning Action
6201 Parity/ overrun/ framing error 6202 Communications character error 6203 Communication data sum check error 6204 Data format error 6205 Command error
D8062 PC/HPP communica- tions error
Check the cable connec- tion between the pro- gramming device and the PLC
Number Associated Meaning Note
6301 Parity/ overrun/ framing error 6302 Comms character error 6303 Comms data sum check error 6304 Comms data format error
Check both power and communications con- nections Special note regarding the 485 network: Because these errors are not transmitted through the network, they must be monitored by the unit acting as Master to the network
D8063 Serial communi- cation errors
Command error 485 Network - received command other than GW (global) when station number was FF 6306 Watchdog timer error 6312 Parallel link character error 6313 Parallel link data sum check error 6314 Parallel link data format error

FX Series Programmable Controller Diagnostic Devices 6
Number Associated Meaning Action
6401 Program sum check error 6402 Memory capacity setting error 6403 Latched device area setting error 6404 Comment area setting error 6405 File register area setting error 6406 - 6408 Reserved 6409 Other setting error
STOP the PLC, select the parameter mode, set the correct data
Number Associated Meaning Action
6501 Incorrect instruction/ device symbol/ device number combination
6502 No timer or counter coil before setting value
During programming, each instruction is checked as it is entered. If a syntax error is detected, re-enter the instruction correctly
6505 Device number is outside the allowable range 6506 Invalid applied instruction 6507 Invalid P assignment 6508 Invalid I assignment 6509 Other error 6510 MC nesting (N) number error
6511 Interrupt and high speed counter assigned inputs overlap

FX Series Programmable Controller Diagnostic Devices 6
Number Associated Meaning Action
6601 LD and LDI is used continuously 9 or more times in succession
6603 MPS is used continuously more than 12 times
6604 Unauthorized use of the MPS/ MRD/ MPP instructions
A circuit error occurs if a combination of instruc- tions is incorrect or badly specified. Select pro- gramming mode and correct the identified error.
Continued on next page...

FX Series Programmable Controller Diagnostic Devices 6
Number Associated Meaning Action
6610 LD, LDI is used continuously 9 or more times in succession
6611 Number of LD/LDI instructions is fewer than ANB/ORB instructions
6612 Number of LD/LDI instructions is more than ANB/ORB instructions
6613 MPS is used continuously more than 12 times 6614 MPS instruction missing 6515 MPP instruction missing
6616 Unauthorized use of the MPS/ MRD/ MPP instructions; possible coil missing
One of the following instructions is not connected to the active bus line: STL, RET, MCR, (P)ointer, (I)nterrupt, EI, DI, SRET, IRET, FOR, NEXT, FEND and END
6618 STL/ RET/ MC or MCR programmed within either a subroutine or an interrupt routine
A circuit error occurs if a combination of instruc- tions is incorrect or badly specified. Select programming mode and correct the identified error.
D8066 Circuit error (FX2N(C) only)
6619 Invalid instruction programmed within a FOR - NEXT loop: STL/ RET/ MC/ MCR/ I/ IRET/ SRET 6620 FOR - NEXT nesting exceeded
6621 Unmatched number of FOR and NEXT instructions 6622 NEXT instruction not found 6623 MC instruction not found 6624 MCR instruction not found
6625 A single STL branch drives 9 or more par- allel circuits
6626 Invalid instruction programmed within an STL - RET block: MC/ MCR/ I/ IRET/ SRET 6627 RET instruction not found
6628 I/ SRET/ IRET incorrectly programmed within main program body 6629 P or I label not found 6630 SRET or IRET not found 6631 SRET programmed in invalid location 6632 IRET programmed in invalid location
Error Detection · Stored Error · Device

FX Series Programmable Controller Diagnostic Devices 6
Number Associated Meaning Action
These error occur during the execution of an oper- ation. When an operation error occurs, STOP the PLC enter programming ode and correct the fault. Note: operation errors can occur even when the syntax or circuit design is correct, e.g. D500Z is a valid state- ment within an FX PLC. But if Z had a value of 100, the data register D600 would be attempted to be accessed. This will cause an operation error as there is no D600 device available.
6702 6 or more CALL instructions have been nested together
6703 3 or more interrupts have been nested together
6704 6 or more FOR - NEXT loops have been nested together
6705 An incompatible device has been speci- fied as an operand for an applied instruc- tion
6706 A device has been specified outside of the allowable range for an applied instruc- tion operand
6707 A file register has been accessed which is outside of the users specified range 6708 FROM/ TO instruction error
6709 Other error, i.e. missing IRE/ SRET, unau- thorized FOR - NEXT relationship
6730 Sampling time TS (TS32767) The identified parameter is specified outside of its allowable range Execution ceases PID instruction must be reset before execution will resume
6732 Input filter value α (α=101) 6733 Proportional gain KP (KP32767) 6734 Integral time constant TI (TI32767) 6735 Derivative gain KD (KD=101)
6736 Derivative time constant TD (TD32767)
TS is set to program scan time - Execution will continue. 6742 Current value ∆ exceeds its limits Data affected resets to the nearest limit value. For all errors except 6745, this will either be a minimum of -32768 or a maximum of +32767. Execution will continue., but user should reset PID instruction.
6740 Sampling time TS is less than the pro- gram scan time.
D8067 PID Operation error
6743 Calculated error ε exceeds its limits 6744 Integral result exceeds its limits
6745 Derivative gain over, or differential value exceeds allowable range 6746 Derivative result exceeds its limits
6747 Total PID result exceeds its limits
6750 SV - PVnf < 150, or system is unstable (SV - PVnf has wide, fast variations)
The error fluctuation is outside the normal oper- ation limits for the PID instruction. Execution ceases. PID instruction must be reset.
6751 Large Overshoot of the Set Value
6752 Large fluctuations during Autotuning Set Process

FX Series Programmable Controller Diagnostic Devices 6

FX Series Programmable Controllers Instruction Execution Times 7
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Instruction Execution Times 7

FX Series Programmable Controllers
Execution Times And Instructional Hierarchy 7
Execution Time in µsec
FX (> Ver 3.07),
Mnemonic Object Devices Steps
FX0, FX0S FX0N FX (< Ver 3.07)
FX 2C
ON OFF ON OFF ON OFF ON OFF ON OFF
3.4 3.4
AND
X,Y,M,S,T,C and special M 1
0.74 0.48 0.08
OR
ORI
LDP
43.2 LDF
ANP
X,Y,M,S,T,C 1 Function Not Available
ORP
ORF
ANB
2.2 2.2
MPS
0.74 0.48 0.08
MPP
INV Function Not Available
M,Y 3 17 18.2 19.2 20.4 42.8 47.8 27 30 24.8 27.5
MCR Nest level 2 6.0 6.2 40.4 19 20.8
Not applicable 1 1.6 1.6 0.74 0.48 0.08
STL S (see note 1) 1 4.2 + 8n 6.4 + 6.8n 39.1 + 21.1n 25 + 13.5n 27.3 + 12.6n
RET Not applicable 8.0 12.4 40.5 20 21.6
carried on over the page
Not applicable 1 · MC Nest level,

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec
FX (> Ver 3.07),
Mnemonic Object Devices Steps
FX0, FX0S FX0N FX (< Ver 3.07)
FX 2C
ON OFF ON OFF ON OFF ON OFF ON OFF
S 2 7.0 7.2 7.0 7.2 50.0 48.1 26 24 24.4 24.3
Special M 2 7.8 7.4 8.2 7.8 38.1 38.8 28 20 0.16
T-K 3 21.8 19.4 25.2 21.0 72.4 52.6 45 34 42.3 37.4
T-D 3 23.4 21.0 27.2 23.0 80.0 52.6 53 34 42.2 37.2
C-K (16 bit) 3 14.6 17.8 15.6 67.9 40.3 42 25 25.5 24.9
C-D (16 bit) 3 16.2 19.8 17.6 75.5 40.3 47 25 25.3 25.0
C-K (32 bit) 5 12.5 6.0 16.0 8.6 82.3 40.3 51 25 25.3 24.9
C-D (32 bit) 5 13.9 6.0 18.0 8.6 89.9 40.3 55 25 25.2 24.9
Y, M 1 3.6 2.0 3.6 2.0 0.74 0.48 0.08
6.8 2.6 7.0 2.8 39.0 25.5 24 16 23.7 17.2
S when used in
Function Not Available 45.2+ 14.2n 25.5 28 + 9n 16 27.3+ 12.6n 17.2
an STL step (see note 1)
Special M 2 7.4 2.4 7.8 2.6 41.9 28.5 26 18 0.16
Y, M 1 3.4 1.8 3.6 1.8 0.74 0.48 0.08
S 2 6.0 2.6 6.2 2.8 40.5 25.5 23 16 23.1 17.3
Special M 2 7.4 2.4 7.8 2.6 41.8 28.9 26 18 0.16
T, C 2 20.8 18.0 22.4 19.6 50.1 38.3 31 24 27 25
D, V, Z and
special D 3 10.0 2.8 9.2 3.0 35.5 25.5 22 16 21.9 17.1
PLS Y, M 2 19.4 21.8 41.9 41.5 27 26 0.32
PLF Y, M 2 42.7 40.6 26 25 0.32
P 0 TO 63 1 1.6 1.6 0.74 0.48 0.08 I Iooo 1

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
ON
00 CJ 16 19.4 9.6 20.0 10.0 46.6 27.4 29 8.8 - 29.0 6.4
01 CALL 16 Function Not Available
49.5 27.4 31 8.8 - 32.2 6.4
03 IRET 1 11.2 11.6 36.7 33 - 18.1
6.4 7.8 62.6 34 8.8 - 55.8
06 FEND 1 410 470 960 700 - 508
07 WDT 16 9.2 5.6 9.8 7.0 35.9 25.1 23 8.8 - 26.3 6.4
08 FOR 1 29.0 29.8 39.9 25 - 27.6
09 NEXT 1 12.4 12.4 29.1 19 - 5.2
16 122.6 22.0 112.2 22.6 161.8 33.3 49 8.8 - 87.6 6.4 32 129.2 30.4 118.6 31.6 189.0 39.9 57 12.2 - 91.9 6.4 11 ZCP
16 140.0 25.0 128.4 25.8 186.9 33.3 62 8.8 - 103.2 6.4 32 197.8 36.4 137.8 38.0 220.8 39.9 73 12.2 - 108.9 6.4 12 MOV
16 46.2 18.0 47.2 18.4 78.4 33.3 35 8.8 - 1.52 1.52 32 52.6 23.4 53.8 24.2 98.4 39.3 43 12.2 - 1.84 1.84 13 SMOV 16 Function Not Available
302.9 33.3 170 8.8 - 155.2 6.4
16 74.0 33.3 51 8.8 - 51.4 6.4 32 95.9 39.9 64 12.2 - 55.9 6.4 15 MOV
103.2 + 18.2n 20.8 180.5 + 17.1n 33.3 118+ 10.6n 8.8 - 97.0+
1.7n 6.4
69.1+ 2.8n 6.4 32 Function Not
107.6 +5.3n 33.3 73+ 3.3n 8.8 -
87+ 4.5n 12.2 - 73.2+ 5.2n 6.4
16 90.3 33.3 58 8.8 - 57.2 6.4 32 113.8 39.8 72 12.2 - 64.0 6.4 18 BCD
16 63.6 64.4 18.4 130.9 33.3 82 8.8 - 37.9 6.4 32 100.2 101.4 24.2 342.0 39.9 218 12.2 306 57.6 6.4 19 BIN
16 64.4 66.2 18.4 135.4 33.3 85 8.8 - 32.4 6.4 32 113.4 114.8 24.2 314.3 39.9 203 12.2 157 44.5 6.4
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
ON
20 ADD
16 69.4 70.8 21.6 115.5 33.3 51 8.8 - 27.6 6.4 32 81.2 82.8 31.8 114.5 39.9 63 12.2 224 28.9 6.4 21 SUB
16 69.8 71.6 21.6 116.6 33.3 52 8.8 - 27.6 6.4 32 81.4 83.0 31.6 146.5 39.9 65 12.2 232 28.9 6.4 22 MUL
16 89.4 91.0 21.6 113.4 33.3 54 8.8 - 25.2 6.4 32 104.6 106.4 31.2 185.0 39.9 81 12.2 162 31.4 6.4 23 DIV
16 119.2 120.8 21.6 139.5 33.3 56 8.8 - 32.0 6.4 32 230.0 232.4 31.0 804.8 39.9 451 12.2 197 36.4 6.4 24 INC
16 28.4 29.0 14.8 55.3 33.3 26 8.8 - 18.8 6.4 32 33.4 34.2 17.4 65.4 34.4 29 12.2 - 20.2 6.4 25 DEC
16 28.4 29.0 14.8 55.4 33.3 26 8.8 - 18.9 6.4 32 33.6 34.4 17.4 65.1 34.4 29 12.2 - 20.0 6.4 26 WAND
16 64.2 65.6 21.6 108.0 33.3 67 8.8 - 23.4 6.4 32 73.0 74.6 30.6 135.4 39.9 83 12.2 - 24.7 6.4 27 WOR
16 64.2 65.6 21.6 107.9 33.3 67 8.8 - 23.5 6.4 32 73.0 74.6 30.6 135.5 39.9 82 12.2 - 24.7 6.4 28 WXOR
16 64.2 65.6 21.6 106.5 33.3 67 8.8 - 23.5 6.4 32 73.0 74.6 30.5 133.9 39.9 82 12.2 - 25.0 6.4 29 NEG
55.1 33.3 34 8.8 - 35.3 6.4 32 65.5 34.4 41 12.2 - 38.4 6.4
16 91.9+ 3.0n 33.3
57+ 1.8n 8.8 -
61.7 6.4 32 113.8 +3.5n 39.9 70+ 2.1n 12.2 - 65.3 6.4
16 91.9+ 3.0n 33.3
57+ 1.8n 8.8 -
61.2 6.4 32 113.8 +3.5n 39.9 71+ 2.3n 12.2 - 65.2 6.4
16 99.0+ 1.4n 33.3
66.3+ 2.2n 6.4 32 120.8 +1.8n 39.9 75+ 1.2n 12.2 - 69.7+ 2.6n 6.4
61+ 0.9n 8.8 -
16 99.0+ 1.4n 33.3
65.8+ 2.2n 6.4 32 120.8 +1.8n 39.3 75+ 1.2n 12.2 - 69.5+ 2.6n 6.4
62+ 0.9n 8.8 -
34 SFTR
16 145.2 +5.1n 24.6 156.4 +4.8n 25.4 180.8 + 70.0n 33.3 172+ 42n 8.8 - 107+ 53.8n 6.4
16 150.6 +5.1n 24.2 162.4 +4.8n 25.0 180.8 + 70.0n 33.3 172+ 42n 8.8 - 105+ 53.8n 6.4
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
ON
36 WSFR
218.6 + 18.0n 33.3 147+ 11n 8.8 - 126+ 11.7n 6.4
16 218.6 + 18.0n 33.3 147+ 11n 8.8 - 125+ 11.7n 6.4
16 138.1 33.3 87 8.8 - 83.9 6.4
16 143.1 +6.8n 33.3 84 8.8 - 80.2 6.4
16(D) 57.2+ 1.6n
65.0+ 1.6n
161.3 +3.2n
77+ 1.7n
16(S) 127.0 +2.9n
131.5 +2.9n
161.3 + 16.5n
83+ 11.1n 16(C) 64.4+ 3.3n 70.7+ 3.3n -
121+ 10.5n
39.9
6.4
16(T) 65.2+ 3.3n 71.5+ 3.3n -
16(M) 127.0+ 0.08n 131.5 +3.5n 161.3+ 13.5n 121+ 8.7n
- 89.2+ 9.4n 16(Y) 127.0 +3.5n
131.5 +3.5n -
41 DECO 16 881.4 20.6 932.0 21.4 114.8 28.8 72 8.8 - 76.0 6.4
42 ENCO 16 618.3 20.6 692.4 21.4 125.6 28.8 79 8.8 - 81.8 6.4
133.5 33.3 84 8.8 - 72.8 6.4 32 196.6 39.9 123 12.2 - 94.6 6.4
44 BON
16 168.9 33.3 98 8.8 - 78.2 6.4 32 177.6 39.9 112 12.2 - 82.3 6.4
16 133.4+ 12.2n 33.3 84+ 7.7n 8.8 -
83.8+ 3.4n 6.4 32 Function Not
105+ 9.8n 12.1 - 90.9+ 6.7n 6.4
46 ANS 16 192.6 165.6 120 110 - 100.8 96.2
47 ANR 16 86.5 25.5 54 8.8 - 37.7 6.4
208 8.8 - 150.2 6.4 32 220 12.2 344 154.8 6.4
16 98 8.8 - 66.8 6.4 32 114 12.2 - 66.8 6.4 50 REF 8 16 53.6 12.8 65.4+ 3.1n 13.4 145.3 +3.6n 33.3 62+ 3.2n 8.8 - 99.6+
0.6n 6.4
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
ON
51 REFF
56.0+ 4.9n 33.3 35+ 3.5n 8.8 - 4 65.3+ 1.7n 6.4
16 Function Not Available
52 MTR 16 87.3 39.3 53 26 - 39.1 23.6
12.2 - 87.8 6.4
75.6 6.6 82.8 7.8 175.0 39.3 115
32 12.2 - 88.6 6.4
32 Function Not Available
240.3 39.3 142 12.2 - 100.6 6.4
56 SPD 1 164.4 163.0 102 101 - 80.2 80.2
16 189.4 10.0 212.4 21.4 154.5 173.6 101 136 - 85.0 73.3 32 223.4 31.4 115 136 - 86.6 75.8 58 PWM 16 42.5 7.8 44.2 18.6 139.8 171.0 86 101 - 70.4 73.3
16 Function Not Available 122.6 87.5 32 125.6 90.5 60 IST 16 766.0 322.4 212.4 21.4 272.9 33.3 153 8.8 - 114.3 6.4
129.2 +8.6n 22.9 32 168+ 17.4n 29 - 147+ 9.0n 22.9
147+ 12.5n 29 -
16 Function Not Available
141.4+ 61.4n 33.3 91+ 35n - 91.8+ 20.2n 6.4
110+ 43n - 97.5+ 21.5n 6.4
63 INCD 16 208.8 39.9 130 26 - 110.5 19.5
64 TTMR 16 81.3 69.6 48 43 - 54.9 44.9
65 STMR 16 176.6 167.8 106 104 - 84.4 84.4
66 ALT 16 61.0 9.8 62.8 10.0 105.6 33.3 66 8.8 - 4 50.1 6.4
67 RAMP 16 248.6 82.6 181.8 134.5 113 83 - 98.1 81.6
68 ROTC 16 Function Not Available 232.5 209.1 144 130 - 118.4 107.2
62+ 32.3 m1
16 Function Not Available
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
ON
70 TKY
245.7 33.3 153 23 - 97.2 22.2 32 229.1 39.9 145 23 - 98.7 22.2
16 318.8 39.9 189 29 - 92.2 27.4 32 338.0 45.5 205 29 - 65.0 6.4
16- 1 set 205.8 39.3 130 30 - 92.2 27.4
16- 2 sets 208.1 NA 30 - NA NA
142.1 33.3 87 8.8 - 4 65.0 6.4
16- 1 set 209.7 33.3 127 30 - 105.9 26.5
16- 2 sets 246.9 148 - NA NA
75 ARWS 16 285.0 163.0 169 8.8 - 134.4 22.1
76 ASC 16 130.9 33.3 104 8.8 - 49.5 6.4
16- printing 207.1 112.6 127 58 - 114.8 88.5 16- ready 112.1 68 - 88.0
97+ 487n 6.4 32 120+ 800n 26 200+ 800n 140+ 640n - 99+ 962n 6.4
120+ 400n 26 170+ 406n 45.0
120+ 325n 14 -
16 120+ 480n 38 151+ 480n 45.0
94+ 557n 6.4 32 120+ 950n 38 200+ 936n 140+ 749n - 96+ 1099n 6.4
106+ 384n 14 -
80 RS 16 Function Not
Available 125.5 20.5 Function Not
Available 132 20 - 117.6 18.0
16 Function Not Available
65.6+ 17.0n 6.4 32 154.5+ 49.3n 104+ 34n 12.2 - 67.0+ 17.7n 6.4
137.1+ 53.5n 33.3
91+ 32n 8.8 -
82 ASCI 16
115+ 9.7n 22.3
94+ 12n 8.8 - 4 88.2+ 10.8n 6.4
83 HEX 16 115+ 22.9 22.1 95+2 3n 8.8 - 4 89.7+ 20.0n 6.4
84 CCD 16 115+ 11.7n 24.4 96+ 8n 8.8 - 4 90.5+ 4.8n 6.4
85 VRRD 16 Function Not Available
308.1 33.3 209 21 - 4 209.7 27.3
86 VRSC 16 319.1 33.3 205 21 - 4 202.4 27.3
87 16 Function Not Available 32
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
ON
88 PID 16 Function Not Available 407 109 - 155.0 89.0
89 16 Function Not Available 32 90 MNET 16
643.9 25.5
Function Not Available 91 ANRD 16 1,137 33.3
93 RMST 16 948.8 950.0 691 692 -
94 RMWR
16 2,214 33.3 1,612 8.8 - 4 32 4,235 39.9 3,127 12.2 -
16 1,684 33.3 1,254 8.8 - 4 32 3,168 39.9 2,414 12.2 - 96 RMMN 16 1,589 33.3 1,195 8.8 - 4
97 BLK 16 672.4 669.3 Function Not Available 98 MCDE 16 740.3 33.3
99 16 Function Not Available 32
110 ECMP 32 Function Not Available
104.4 6.4
118 EBCD 32
106.9 6.4
120 EADD 32 117.4 6.4
121 ESUB 32 117.4 6.4
122 EMUL 32 96.4 6.4
123 EDIV 32 100.4 6.4
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7

Execution Time in µsec FX0, FX0S FX0N FX(< Ver 3.07) FX(> Ver 3.07), FX2C FX2N(C)
ON OFF ON OFF ON OFF P ON OFF
16 67.5 6.4 32 70.4 6.4 130 SIN 32
16 Function Not Available 36.1 6.4 32 41.2 6.4
See end of section for notes...

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
14:
15:

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
The following table identifies an 'inclusive relationship'. This means the secondary program construction is included within the complete operating boundaries of the primary program construction, e.g.:
EI DI
NEXT
MC-MCR CJ - P EI - DI FOR - NEXT
RET P - SRET I - IRET FEND -
- 8 nest lev-
- (6608) - (6608) - (6608)
CJ - P - (6701)
EI - DI
- 5 nest lev-
- (6607) - (6607) - (6607) - (6607)
- (within 1 STL step)
- (6605) - (6605) - (6605)
P - SRET - (6606) - (6606) - (6606) - (6606) - (6709)
I - IRET - (6606) - (6606) - (6606) - (6606) - (6606)
FEND - END
:Instruction combination is acceptable - for restrictions see appropriate note
: Instruction combination is not recommended for use even though there is no operational
The combination of instructions with an 'inclusive relationship' is allowable. However please be aware of the following exceptions:

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
The following table identifies an 'overlap-ping relationship'. This means the secondary program construction starts within the complete operating boundaries of the primary program construction but finishes outside of the primary construction, e.g.:
EI
NEXT
DI
MC-MCR CJ - P EI - DI FOR - NEXT
RET P - SRET I - IRET FEND -
MC - MCR - (6607) - (6605) - (6606) - (6606) - (6608)
CJ - P
EI - DI
FOR - NEXT - (6607) ¬ - (6601) - (6607) - (6607) - (6607)
STL - RET - (6605) - (6607) - (6606) - (6606) - (6605)
P - SRET - (6608) - (6607) - (6605) - (6606) - (6606) - (6709)
I - IRET - (6606) - (6607) - (6606) - (6606) - (6606) - (6606)
FEND - END - (6608) - (6601) - (6607) - (6605) - (6709) - (6709)
Enters a state as if the DI instruction was missing. An error is not generated.
The first occurrence of either an FEND or the END instruction takes priority. This would
then end the program scan prematurely.
The sequence will not process as expected, e.g.:
FOR
FOR
FOR
NEXT
NEXT
NEXT
NEXT

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
This is the system used by all members of the FX family of PLC’s. The basic concept is that there are three stages to any program scan. In other words, every time the program is processed form start to end the following sequence of events occurs:
All of the current input statuses are read in to a temporary memory area; sometimes called an image memory. The PLC is now ready for the next program processing
All of the updated inputs are checked as the program is processed. If the new input statuses change the status of driven outputs, then these are noted in the image memory for the
The new, current statuses of the outputs which have just be processed are physically updated, i.e relays are turned ON or OFF as required. The program scan starts again The system is known as 'Batch processing' because all of the inputs, program operation and finally the outputs are processed as batches.
The memory allocations of the programmable are very complex, but from a users point of view there are three main areas:
a) The Program Memory:
This memory area holds all of the data regarding: parameters, sequence program, constant values K and H, pointer information for P and I devices, nest level information, file register contents/allocations and also the program comment area.
- This memory area is latched either by battery backup or by use of EEPROM program management (dependent on the PLC being used). Any data stored in this area is kept even when the PLC is powered down. The duration and reliability of the data storage is dependent upon the condition of the battery or EEPROM being used to perform the backup process.
Input Processing · Program Processing · Output Processing

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
This memory area contains, as the title suggests, all of the data values associated with: data registers (normal and special), Index registers, current timer values, retentive timer values (if available) and current counter values.
- All of the devices which are designated as being latched (including retentive timers) are backed up in a similar method to the one mentioned under point a).
- Index registers and special data registers (D8000 to D8255) operate in the specified manner under the following circumstances:
PLC's power is turned OFF All data is cleared
PLC's power is turned ON Certain devices are reset to their defaults see chapter 6
PLC is switched from STOP to RUN
Certain devices are reset to their defaults see chapter 6 PLC is switched from RUN to STOP
- All other devices such as current values of non latched data registers, timers and counters behave in the following manner:
PLC's power is turned OFF All data is cleared PLC's power is turned ON
PLC is switched from STOP to RUN No change
PLC is switched from RUN to STOP Cleared (unless special M coil M8033 is active)
This memory area contains the contact status of all inputs, outputs, auxiliary relays, state coils, timers and counters.
- All of the devices which are designated as being latched (including retentive timers) are backed up in a similar method to the one mentioned under point a).
- Special auxiliary relays (M8000 to M8255) act in a similar way to the special data registers mentioned under point b).
- All other devices are subject to the same changes as the current values of data registers, timers and counter (see the last point and table under section b).
OFF OFF ON STOP RUN RUN STOP
All devices backed by battery Not changed
Special M and D devices (8000 to 8255) and index registers V and Z Cleared Default Not changed
All other devices Cleared Not changed Cleared
Not changed when M8033 is set

FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
7.6.1 Instructions Which Can Only Be Used Once In The Main Program Area
The following instructions can only be used once in the main program area. For PLC applicability please check either the detailed explanations of the instructions or the instruction execution tables list earlier.
FNC 52 MTR FNC 60 IST FNC 70 TKY FNC 57 PLSY FNC 61 SORT FNC 71 HKY FNC 58 PWM FNC 62 ABSD FNC 72 DSW FNC 59 PLSR FNC 63 INCD FNC 74 SEGL FNC 68 ROTC FNC 75 ARWS
7.6.2 Instructions Which Are Not Suitable For Use With 110V AC Input Units
When using 110V AC input units certain operations, functions and instructions are not recommended for use due to long energize/de-energize (ON/OFF) times of the 110V input devices.
- High speed counters
FNC 51 REFF FNC 68 ROTC FNC 72 DSW FNC 52 MTR FNC 70 TKY FNC 75 ARWS FNC 56 SPD FNC 71 HKY
above are not present in the CPU of the unit and hence cannot be used anyway
- Interrupt routines

FX Series Programmable Controllers PLC Device Tables 8
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers PLC Device Tables 8

FX Series Programmable Controllers
PLC Device Tables 8
Operation control method Cyclic operation by stored program
I/O control method Batch processing method (when
END instruction is executed) I/O refresh instruction is available
Operation processing time Basic instructions: 1.6 to 3.6 µs Applied instructions: several 10’s to 100 µs
Programming language Relay symbolic language + step
Step ladder can be used to pro-
duce an SFC style program
Program capacity 800 steps Provided by built in EEPROM
A Maximum 50 applied instructions
are available including all varia-
I/O configuration Max total I/O set by Main Processing Unit
General 512 points M0 to M511
Latched 16 points (subset) M496 to M511
Special 56 points From the range M8000 to M8255
General 64 points S0 to S63
Initial 10 points (subset) S0 to S9
56 points T0 to T55
24 points T32 to T55 when special M coil
M8028 is driven ON
16 points C0 to C13 Type: 16 bit up counter
Latched 2 points(subset) C14 to C15 Type: 16 bit up counter
1 phase Range: -2,147,483,648 to +2,147,483,647 counts FX0: Select upto four 1 phase counters with a combined counting frequency of 5kHz or less. Alternatively select one 2 phase or A/B phase counter with a counting frequency of 2kHz or less. FX0S: When multiple 1-phase counters are used the sum of the frequencies must be equal or less than 14kHz. Only 1, 2 phase high speed counter may be used at any one time. When 2 phase counters are in use the maximum counted speeds must be equal or less than 14kHz, calculated as (2 ph counter speed 5 number of counted edges) + 1 ph counter speeds.
C235 to C238 (note C235 is latched)
1 phase c/w start stop input
C241(latched), C242 and C244
2 phase C246, C247 and C249 (all latched)
High speed counters (C)
A/B phase C251, C252 and C254 (all latched)
continued over the page

FX Series Programmable Controllers PLC Device Tables 8
General 32 points D0 to D31 Type:16 bit data storage register
pair for 32 bit device
Latched 2 points (subset) D30 to D31 Type:16 bit data storage register
pair for 32 bit device
D8013 Data is entered indirectly through the external setting potentiometer
Special 27 points (inclusive of D8013) From the range D8000 to D8255 Type: 16 bit data storage register
Index 2 points V and Z Type: 16 bit data storage register
For use with CALL 64 points P0 to P63
4 points I00 to I30 (rising trigger = 1, falling trigger = 0)
Nest levels 8 points for use with MC and MCR N0 to N7
Operation control method Cyclic operation by stored program
I/O control method Batch processing method (when
END instruction is executed) I/O refresh instruction is available
Operation processing time Basic instructions: 1.6 to 3.6 µs Applied instructions: several 10's to 100 µs
Programming language Relay symbolic language + step
Step ladder can be used to pro-
duce an SFC style program
Program capacity 2000 steps Provided by built in EEPROM
A Maximum 59 applied instructions
are available including all varia-
I/O configuration Max hardware I/O configuration points 128, dependent on user selection
(Max. software addressable Inputs 128, Outputs 128)
General 512 points M0 to M511
Latched 128 points (subset) M384 to M511
Special 65 points From the range M8000 to M8255
continued over the page

FX Series Programmable Controllers PLC Device Tables 8
Latched 128 points S0 to S127
Initial 10 points (subset) S0 to S9
63 points T0 to T62
31 points T32 to T62 when special M coil
M8028 is driven ON
32 points C0 to C31 Type: 16 bit up counter
Latched 16 points (subset) C16 to C31 Type: 16 bit up counter
+2,147,483,647 counts Select upto four 1 phase counters
1 phase c/w start stop input
C241, C242 and C244
with a combined counting fre-
High speed counters (C)
quency of 5kHz or less. Alternatively select one 2 phase or A/B phase counter with a counting
2 phase C246, C247 and C249
frequency of 2kHz or less. Note all counters are latched
A/B phase C251, C252 and C254
General 256 points D0 to D255 Type: 16 bit data storage register
pair for 32 bit device
Latched 128 points (subset) D128 to D255 Type: 16 bit data storage register
pair for 32 bit device
File 1500 points D1000 to D2499 set by parameter
in 3 blocks of 500 program steps Type: 16 bit data storage register
Data is move from external setting
potentiometers to registers D8030 and D8031 ( D8013 is
used when no RTC is fitted)
Special 42 points (inclusive of D8013, D8030 and D8031)
From the range D8000 to D8255 Type: 16 bit data storage register
Index 2 points V and Z Type: 16 bit data storage register
For use with CALL 64 points P0 to P63
4 points I00 to I30 (rising trigger = 1, falling trigger = 0)
Nest levels 8 points for use with MC and MCR N0 to N7

FX Series Programmable Controllers PLC Device Tables 8
8.3 Performance Specification Of The FX (CPU versions 2.0 to 3.06)
Operation control method Cyclic operation by stored program
I/O control method Batch processing method (when
END instruction is executed) I/O refresh instruction is available
Operation processing time Basic instructions: 0.74 µs Applied instructions: several 10's to 100 µs
Programming language Relay symbolic language + step
Step ladder can be used to pro-
duce an SFC style program
Program capacity 2000 steps built in Expandable to 8000 steps using
A Maximum 119 applied instruc-
tions are available including all
I/O configuration Max hardware I/O configuration points 256, dependent on user selection
(Max. software addressable Inputs 128, Outputs 128)
General 1024 points M0 to M1023
Latched 524 points (subset) M500 to M1023
Special 256 points From the range M8000 to M8255
General 1000 points S0 to S999
Latched 500 points (subset) S500 to S999
Initial 10 points (subset) S0 to S9
Annunciator 100 points S900 to S999
200 points T0 to T199
46 points T200 to T245
4 points T246 to T249
6 points T250 to T255
200 points C0 to C199 Type: 16 bit up counter
16 bit 100 points (subset) C100 to C199 Type: 16 bit up counter
32 bit 15 points (subset) C219 to C234 Type: 16 bit up/down counter
continued over the page

FX Series Programmable Controllers PLC Device Tables 8
1 phase c/w start stop input
High speed counters (C)
2 phase C246 to C250
frequency of 20kHz or less. Note all counters are latched
A/B phase C251 to C255
General 512 points D0 to D511 Type: 16 bit data storage register
pair for 32 bit device
Latched 312 points (subset) D200 to D511 Type: 16 bit data storage register
pair for 32 bit device
File 2000 points D1000 to D2999 set by parameter
in 4 blocks of 500 program steps Type: 16 bit data storage register
Special 256 points From the range D8000 to D8255 Type: 16 bit data storage register
Index 2 points V and Z Type: 16 bit data storage register
For use with CALL 64 points P0 to P63
6 input points and 3 timers I00 to I50 and I6 to I8 (rising trigger =1, falling trigger =0,
=time in msec)
Nest levels 8 points for use with MC and MCR N0 to N7

FX Series Programmable Controllers PLC Device Tables 8
8.4 Performance Specification Of The FX (CPU versions from 3.07) And FX2C (all versions)
Operation control method Cyclic operation by stored program
I/O control method Batch processing method (when
END instruction is executed) I/O refresh instruction is available
Operation processing time Basic instructions: 0.48 µs Applied instructions: several 10's to 100 µs
Programming language Relay symbolic language + step
Step ladder can be used to pro-
duce an SFC style program
Program capacity 2000 steps built in Expandable to 8000 steps using
A Maximum 119 applied instruc-
tions are available including all
I/O configuration Max hardware I/O configuration points 255, dependent on user selection
(Max. software addressable Inputs 255, Outputs 255)
General 1536 points M0 to M1535
Latched 1024 points (subset) M500 to M1535
Special 256 points From the range M8000 to M8255
General 1000 points S0 to S999
Latched 500 points (subset) S500 to S999
Initial 10 points (subset) S0 to S9
Annunciator 100 points S900 to S999
200 points T0 to T199
46 points T200 to T245
4 points T246 to T249
6 points T250 to T255
200 points C0 to C199 Type: 16 bit up counter
16 bit 100 points (subset) C100 to C199 Type: 16 bit up counter
32 bit 15 points (subset) C219 to C234 Type: 16 bit up/down counter
continued over the page

FX Series Programmable Controllers PLC Device Tables 8
1 phase c/w start stop input
High speed counters (C)
2 phase C246 to C250
frequency of 20kHz or less. Note all counters are latched
A/B phase C251 to C255
General 1000 points D0 to D999 Type: 16 bit data storage register
pair for 32 bit device
Latched 800 points (subset) D200 to D999 Type: 16 bit data storage register
pair for 32 bit device
File registers 2000 points D1000 to D2999 set by parameter
in 4 blocks of 500 program steps Type: 16 bit data storage register
RAM file registers 2000 points D6000 to D7999 active when spe-
cial relay M8074 is active Type: 16 bit data storage register
Special 256 points From the range D8000 to D8255 Type: 16 bit data storage register
Index 2 points V and Z Type: 16 bit data storage register
For use with CALL 128 points P0 to P127
I00 to I50 and I6 to I8 (rising trigger =1, falling trigger =0,
6 input points, 3timers and 6 counters
=time in msec)
Nest levels 8 points for use with MC and MCR N0 to N7

FX Series Programmable Controllers PLC Device Tables 8
Operation control method Cyclic operation by stored program
I/O control method Batch processing method (when
END instruction is executed) I/O refresh instruction is available
Operation processing time Basic instructions: 0.08 µs Applied instructions: several 10's to 100 µs
Programming language Relay symbolic language + step
Step ladder can be used to pro-
duce an SFC style program
Program capacity 8000 steps built in Expandable to 16000 steps using
A Maximum 125 applied instruc-
I/O configuration Max hardware I/O configuration points 255, dependent on user selection
(Max. software addressable Inputs 255, Outputs 255)
General 3072 points M0 to M3071
Latched 2572 points (subset) M500 to M3071
Special 256 points From the range M8000 to M8255
General 1000 points S0 to S999
Latched 500 points (subset) S500 to S999
Initial 10 points (subset) S0 to S9
Annunciator 100 points S900 to S999
200 points T0 to T199
46 points T200 to T245
4 points T246 to T249
6 points T250 to T255
200 points C0 to C199 Type: 16 bit up counter
16 bit 100 points (subset) C100 to C199 Type: 16 bit up counter
32 bit 15 points (subset) C219 to C234 Type: 16 bit up/down counter
Continued over the page

FX Series Programmable Controllers PLC Device Tables 8
1 phase c/w start stop input
High speed counters (C)
2 phase C246 to C250
frequency of 20kHz or less. Note all counters are latched
A/B phase C251 to C255
General 8000 points D0 to D7999 Type: 16 bit data storage register
pair for 32 bit device
Latched 7800 points (subset) D200 to D7999 Type: 16 bit data storage register
pair for 32 bit device
File registers 7000 points D1000 to D7999 set by parameter in 14 blocks of 500 program steps
Special 256 points From the range D8000 to D8255 Type: 16 bit data storage register
Index 16 points V0 to V7 and Z0 to Z7 Type: 16 bit data storage register
For use with CALL 128 points P0 to P127
6 input points, 3 timers, 6 counters I00 to I50 and I6 to I8 (rising trigger =1, falling trigger =0,
=time in msec)
Nest levels 8 points for use with MC and MCR N0 to N7

FX Series Programmable Controllers PLC Device Tables 8

FX Series Programmable Controllers Assigning System Devices 9
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Assigning System Devices 9

FX Series Programmable Controllers
Assigning System Devices 9
Most of the FX family of PLC’s have the ability to connect additional discreet I/O and/or special function modules. To benefit from these additional units the user must address each block independently.
This type of I/O is the standard input and output modules. As each extension block or powered extension unit is added to the system they assume the next available ad-dresses. Hence, the units closest to the base unit will have the lowest I/O numbers or addresses. I/O numbers are always counted in octal. This means from 0 to 7 and 10 to 17 etc. Within a users program the additional addresses are used as normal. Discreet I/O can be added at the users discretion as long as the rules of system configuration for each PLC type are obeyed. This information can be found in the appropriate hardware manual. For easy use and identification, each additional I/O unit should be labeled with the appropriate I/O numbers using the provided number labels.
X0-27 X30-X37 X40-X57 X60-X67
POWER FX-8EYT
POWER FX-8EYR
POWER FX-16EX
POWER FX-8EX
Y0-Y27 Y30-Y37 Y40-Y47
Caution when using an FX system with FX-8ER, FX-24MR units
Special function blocks are allocated a logical ‘station/block number’ from 0 to 7. This is used by the FROM/TO instructions to directly access each independent special function module. The lower the ‘station/block number’ is, the closer to the base unit it can be found. Special function blocks can be added at the users discretion but the rules of configuration for each type of PLC must be obeyed at all times. The configuration notes can be found in the appropriate hardware manual for each programmable controller.

FX Series Programmable Controllers Assigning System Devices 9
The FX2-24EI allows an FX base unit to be directly connected to an one of the following F series special function blocks:
a) The F-16NT/NP, a Melsec Net Mini interface
b) The F2-6A, a combine analog 4 input and 2 output unit
c) The F2-32RM, a programmable CAM sequencer
d) The F2-30GM, a pulse train positioning unit
One 24EI unit can control one F series special function unit.

This is not the case. The FX2-24EI is really a communications module. It does not directly drive any discreet I/O. For the sake of power calculations it can be assumed that it only occupies 8 standard I/O points. This means that the configuration shown in the diagram actually occupies 32 points (three FX2-24EI’s and one FX-8EX) of I/O for the sake of power consumption calculations BUT actually occupies 80 points of addressable I/O.

FX Series Programmable Controllers Assigning System Devices 9
The F-16NP/NT’s operational I/O numbers (addresses) are based upon the position of the associated FX2-24EI within the users FX system. The diagram below shows how moving the position of the FX2-24EI used alters the addresses used by the F-16NP/NT, see EX. 1A to 1C. For installation, wiring and operational details of the F-16NP/NT please see the units dedicated manual. That manual will show examples of the F-16NP/NT being used and in each case the I/ O numbers used to address it are those fixed by the F series PLC’s. These I/O addresses will be replaced by those described in the previous paragraph, i.e. the FX devices assigned to the FX2-24EI being used.
The following tabular example identifies the correspondence between FX and F2 systems.
FX System Setup F2 System Setup Remark
X54 X414 Input data correct
X55 X415 Input data incorrect
X56 X416 Output data correct
X57 X417 Output data incorrect
X60 to X67 X420 to X427 Input to PLC
Y40 to Y47 Y440 to Y447 Output from PLC
The FX system used is similar to that shown in the diagram EX. 1C. The F2 system uses the second expansion port, i.e. the X400 port of the F series PLC.
Applicable FX Applied Instructions: (Not applicable to FX2C Main Processing Units or FX units with CPU’s greater than version 3.06)
PLC
EX. 1A EX. 1B EX. 1C EX. 2A EX. 2B EX. 2C
F2-30GM
F-16NP/NT
F2-6A
F2-32RM
X0 - X6 X¤14 -¤27
X34 - X47 Y30 - Y37
K000-001 K010-013
Y0-37 BANK 0,1
FX2-24EI
X30 Y30
Y¤40 -¤47 Y0 - Y6
F2-30GM
FX2-24EI
Y40 X50
F2-6A
F2-32RM
F-16NP/NT
X0 - X6 X¤14 -¤27
K000-001 K010-013
Y0-37 BANK 0,1
X54 - X67 Y40 - Y47
Y¤40 -¤47 Y0 - Y6
FX2-24EI
X70 Y50
F2-30GM X0 - X6 X¤14 - 27
F2-32RM
F-16NP/NT
F2-6A
Y0-37 BANK 0,1
X74 - X107 Y50 - Y57
K000-001 K010-013
Y0 - Y6
Y¤40 - 47
Example Configurations

FX Series Programmable Controllers Assigning System Devices 9
The F2-6A’s operational address is based upon the position of the associated FX2-24EI within the users FX system. However, the I/O channel numbers are not affected by this operational address. The I/O channel will always remain as K000 to K001 and K010 to K013. The diagram on the previous page shows how moving the position of the FX2-24EI used alters the operational address but NOT the channel number used by the F2-6A, see EX. 1A to 1C. For details on using the F2-6A see the units users manual. Please remember when reading the manual, that it has been written for use on an F2 system and hence all of the I/O addresses stated are for such an F2 setup.
F2-6A Channel identification:
Applicable FX Applied Instructions: (Not applicable to FX2C Main Processing Units or FX units with CPU’s greater than version 3.06)
The F2-32RM’s operational address is based upon the position of the associated FX2-24EI within the users FX system. However, the “32RM’s” I/O numbers are will always remain the same, i.e not be affected by the FX’s operational address. The 32RM’s I/O numbers would remain as Y0 to Y37, and Bank 0, 1. The diagram on the previous page shows how moving the position of the FX2-24EI used, alters the operational address but NOT the I/O numbers used by the F2-32RM, see EX. 1A to 1C. For details on using the F2-32RM see the units users manual. Please remember when reading the manual, that it has been written for use on an F2 system and hence all of the I/O addresses stated are for such an F2 setup.

FX Series Programmable Controllers Assigning System Devices 9
The F2-30GM’s operational address is based upon the position of the associated FX2-24EI within the users FX system. However, the I/O numbers are not directly affected by this operational address. The I/O numbers can be selected by the user. The diagram on the page 9-3 shows how moving the position of the FX2-24EI used alters the operational address but NOT the I/O numbers used by the F2-30GM, see EX. 2A to 2C. Where the symbol § is used in the diagram, this can be replaced by the numbers ‘0’, ‘4’ or ‘5’. It is recommended that for simplification the user favors ‘0’. For details on using the F2-30GM see the units users manual. Please remember when reading the manual, that it has been written for use on an F2 system and hence all of the I/O addresses stated are for such an F2 setup.
The following tabular example identifies the correspondence between FX and F2-30GM systems.
F2-30GM System Setup Comments FX System Setup
X 14 to X 27 Turn On − X54 to X67
Y 40 to Y 47 Are Turned On BY − Y40 to Y47
X0 to X6 No correspondence N/A
Y0 to Y6 No correspondence N/A
The FX system used is similar to that shown in the diagram EX. 2B from page 9-3.
Applicable FX Applied Instructions: (Not applicable to FX2C Main Processing Units or FX units with CPU’s greater than version 3.06)

FX Series Programmable Controllers Assigning System Devices 9
The FX parallel link adapters provide a means of direct communication between two FX PLC’s. There are two models of parallel link adapter providing two different communication mediums:
a) Fiber-optic link - FX2-40AP
Transmission distance: 50m (164 ft) Fiber-optic: F-OFC-M10 - length 10m (32.8 ft) F-OFC-M30 - length 30m (98.4 ft) F-OFC-M50 - length 50m (164 ft) Note all of the above fiber-optic cables come with connector CA9104AP fitted.
b) Wire link (twisted pair) - FX2-40AW
Transmission distance: 10m (32.8 ft) Connect like terminals together, i.e [SA] on unit 1 to [SA] on unit 2. Repeat for [SB] and [SG]. Finally also connect the [SG] terminal of each unit to the [SG] terminal of the local FX PLC.
Master Slave, Slave Master Bit devices -100 points Bit devices - 100 points (M800 to 899) (M900 to 999) Word devices - 10 points Word devices - 10 points (D490 to 499) (D500 to 509)
RUN T/R TXD RXD
RUN T/R TXD RXD
POWER FX -40AP 2
POWER MELSEC FX-48MR
POWER FX -40AP 2
POWER MELSEC FX-48MR
RUN BATT.V
RUN BATT.V
PROG-E CPU-E MITSUBISHI
PROG-E CPU-E MITSUBISHI
T R
T R

FX Series Programmable Controllers Assigning System Devices 9
When one of the real time clock (RTC) memory cassettes is used with either and FX or an FX0N, the real time clock function of that PLC is then automatically enabled. The time data of the RTC cassette is battery backed. This means when the PLC is turned OFF the time data and settings are not lost or corrupted. The duration or storage life of the time data is dependent upon the condition of the battery. The operation of the RTC clock circuits consumes negligible currents compared with the RAM memory (applicable to FX only). The real time clock cassettes have a worst case accuracy of ± 45 seconds per month at an ambient temperature of 25°C. The calendar function of the RTC cassettes caters for leap years during the period 1980 through 2079.
FX-RTC Real time clock function only
Real time clock function + 8K RAM (Note: the FX0N cannot use this cassette, because RAM program storage is not guaranteed)
FX-EEPROM-4C Real time clock function + 4K EEPROM (Note the FX0N can only use 2K of the EEPROM)
RTC Cassette Remark

FX Series Programmable Controllers Assigning System Devices 9
The RTC can be set using the special data registers and control flags as follows:
Device Number Function Range Device Number Comments
D8013 Seconds 0 to 59 M8015
Set ON to stop the clock. When the clock is stopped the time values can be reset. The clock restarts when the flag is reset to OFF.
D8014 Minutes 0 to 59
D8015 Hours 0 to 23
D8016 Date 1 to 31 (correct for current Month) M8016 Register
The clock data in the data regis- ters is held. The clock still runs. Use this to pause the data to read the current time. D8017 Month 1 to 12
D8018 Year 00 to 99 (1980 to 2079)
When on rounds the time up or down to the nearest minute.
0 to 6 (Sunday to Sat- urday
Automatically set to indicate the RTC is available.
ON when the values for the RTC are out of range.
These devices are used as shown in the program on the right.
The clock stops when X0 is ON. The new values are set when X0 turns OFF.
simplify the setting and use of the RTC. See section 5.14 for more details.
M0 PLF
M0
K30 D8013 MOV
K20 D8014 MOV
K10 D8015 MOV
K25 D8016 MOV
K4 D8017 MOV
K96 D8018 MOV
K4 D8019 MOV
M8017 X1
X1 is used to reset the clock to the nearest minute.

FX Series Programmable Controllers Points of Technique 10
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Controllers Points of Technique 10
10.Points Of Technique 10-1 10.1 Advanced Programming Points 10-1 10.2 Users of DC Powered FX Units 10-1 10.3 Using The Forced RUN/STOP Flags 10-2 10.3.1 A RUN/STOP push button configuration 10-2 10.3.2 Remote RUN/STOP control 10-3 10.4 Constant Scan Mode 10-4 10.5 Alternating ON/OFF States 10-4 10.6 Using Battery Backed Devices For Maximum Advantage 10-5 10.7 Indexing Through Multiple Display Data Values 10-5 10.8 Reading And Manipulating Thumbwheel Data 10-6 10.9 Measuring a High Speed Pulse Input 10-6 10.9.1 A 1 msec timer pulse measurement 10-6 10.9.2 A 0.1 msec timer pulse measurement 10-7 10.10Using The Execution Complete Flag, M8029 10-7 10.11Creating a User Defined MTR Instruction 10-8 10.12An Example System Application Using STL And IST Program Control 10-8 10.13Using The PWM Instruction For Motor Control 10-15 10.14Communication Format 10-18 10.14.1Specification of the communication parameters: 10-18 10.14.2Header and Terminator Characters 10-19 10.14.3Timing diagrams for communications: 10-20 10.14.48 bit or 16 bit communications 10-23 10.15PID programming techniques 10-24 10.15.1Keeping MV within a set range 10-24 10.15.2Manual / Automatic change over 10-24 10.15.3Using the PID alarm signals 10-25 10.15.4Other tips for PID programming 10-25 10.16Additional PID functions 10-26 10.16.1Output Value range control 10-26 10.17Pre-tuning operation 10-27 10.17.1Variable control 10-27 10.18Example Autotuning program 10-28

FX Series Programmable Controllers
Points Of Technique 10
The FX family of programmable controllers has a very easy to learn, easy to use instruction set which enables simple programs to perform complex functions. This chapter will point out one or two useful techniques while also providing the user with valuable reference programs.
If some of these techniques are applied to user programs the user must ensure that they will perform the task or operation that they require. Mitsubishi Electric can take no responsibility for user programs containing any of the examples within this manual.
Each program will include a brief explanation of the system. Please note that the method of 'how to program' and 'what parameters are available' for each instruction will not be discussed. For this information please see the relevant, previous chapters.
When using DC powered FX programmable controllers, it is necessary to add the following instructions to the beginning of the installed program:
MOV K -4 D8008 Step 0
Explanation:
With AC powered FX programmable controllers, the power break detection period can be adjusted by writing the desired detection period to the special data register D8008. However, in the case of DC powered units this detection period must be set to 5 msec.
This is achieved by moving the value of -4 into D8008. Failure to do this could result in inputs being missed during the DC power 'drop'.

FX Series Programmable Controllers Points Of Technique 10
10.3.1 A RUN/STOP push button configuration
The FX programmable controller has a single RUN terminal. When power is applied to this terminal the PLC changes into a RUN state, i.e. the program contained is executed. Consequently when there is no power 'on' the RUN terminal the PLC is in a STOP state. This feature can be utilized to provide the FX PLC with an external RUN/STOP - push button control. The following PLC wiring and program addition are required.
STOP
M8035
M8036
RUN
M8037
24V S/S 0V RUN X0 X1
FX base unit configured as source input (example only) Forced STOP command
Pressing the RUN push button sets the PLC into the RUN state. This means M8000 is ON. Following the program, M8000 activates both M8035 and M8036. These two special auxiliary devices set the PLC in to forced RUN mode. Releasing the RUN push button would normally return the PLC to the STOP state, but because the two auxiliary coils, M8035 and 36 are ON, the PLC remains in RUN. To stop the, PLC pressing the STOP push button drives an input ON and consequently M8037 turns ON. This then automatically forces OFF both M8035 and 36 and resets itself. Hence, the PLC is in its STOP status and awaits the cycle to begin again.
Forced RUN mode · Forced RUN command

FX Series Programmable Controllers Points Of Technique 10
The FX family of programmable controllers can be controlled, i.e. switched into RUN or STOP modes and have devices monitored by use of intelligent external control devices. These includes such items as computers, the Mitsubishi FX data access units and Graphic Operator Terminals. The following example utilizes a graphic FX-DU unit:
The programmable controller needs no special wiring or additional programming for this example.
SWITCH for...
The only condition required is that the PLC would not normally be in a RUN state, i.e., there is no connection to the RUN terminal and the RUN/STOP switch on PLC’s that have one is set in the STOP position.
POWER
The DU should be programmed with 'SWITCH' devices driving the three special M codes M8035,36 and 37. By activating the 'SWITCH' devices for M8035 and M8036 the PLC can be switched into a RUN state, while driving the 'SWITCH' device M8037 will put the PLC into a STOP state.
INPUT: 0
OUTPUT: PLC M8035
MODE: ALTERNATE
Example 'SWITCH' device setting opposite. Use an 'Alternate' switch for M8035 and M8036 and use a 'Momentary' switch for M8037. (see DU operation manual for SWITCH operation and programming)
FX-25DU-E - a 4 line text/graphic unit. FX-30DU-E - a 4 line text/graphics display unit with membrane style keypad. FX-40DU-TK-E - a 7 line, touch key, text/graphics display unit with numeric keypad. FX-50DU-TK(S)-E - a 15 line, touch key, color text/graphics display unit. F940GOT-SWD/LWD-E - a 15 line, touch key, color text/graphics advanced display unit.
With FX2N(C) units, even if the RUN terminal or RUN/STOP switch is in the RUN position, it is still possible to do a remote STOP by forcing M8037 ON.
Return to RUN by resetting M8037.

FX Series Programmable Controllers Points Of Technique 10
Some times the timing of operations can be a problem, especially if some co-ordination is being attempted with a second control system. In cases like this it is very useful to fix the PLC’s scan time. Under normal conditions the PLC’s scan time will vary from one scan to the next. This is simply because the natural PLC scan time is dependent on the number of and type of the active instructions. As these are continually changing between program scans the actual scan time is also a varying. Hence, by using the additional program function identified below, the PLC’s scan time can be fixed so that it will be the same duration on every program scan. The actual scan duration is set by writing a scan time in excess of the current longest scan duration to special data register D8039 (in the example the value K150 is used). If the PLC scans the program quicker than the set scan time, a 'pause' will occur until the set scan duration is reached. This program example should be placed at the beginning of a users program.
M8039
MOV K150 D8039
Newly set constant scan time = 150 msec
It is often useful to have a single input control or toggle a situation. A basic, yet typical example is the switching ON/OFF of a Light. This can be easily achieved by using standard ladder program to load an input and switch an output. However, this system requires an input which is latchable. If basic ladder steps are used to latch the program then it soon becomes complex and prone to mis-programming by the user. Using the ALT instruction to toggle the ON/OFF (SET/RESET, START/STOP, SLOW/FAST) state is much simpler, quicker and more efficient.
ALT Y 1
ALT M 0
M 0
Y 0
X 0 Y 1
Y 1 M 0
Program example 1 Program example 2
Pressing the momentary push button X1 once will switch the lamp ON. Pressing the push button for a second time will cause the lamp to turn OFF. And if the push button is again pressed for a third time, the lamp is turned ON again and so the toggled status continues. The second program shown identifies a possible motor interlock/control, possibly a start/stop situation.

FX Series Programmable Controllers Points Of Technique 10
Battery backed devices retain their status during a PLC power down. These devices can be used for maximum advantage by allowing the PLC to continue from its last operation status just before the power failure.
For example: A table traverse system is operating, moving alternatively between two limit switches. If a PLC power failure occurs during the traversing the machine will stop. Ideally, once the PLC regains its power the system should continue from where it left off, i.e. if the movement direction was to the left before the power down, it should continue to the left after the restoration of the power.

The status of the latched devices (in this example FX M coils M600 and M601) is retained during the power down. Once the power is restored the battery backed M coils latch themselves in again, i.e. the load M600 is used to drive M600.
Many users unwarily fall in to the trap of only using a single seven segment display to display only a single data value. This very simple combination of applied instructions shows how a user can 'page' through multiple data values displaying each in turn.
The contents of 10 counters are displayed in a sequential, 'paged' operation. The paging action occurs every time the input X11 is received. What actually hap-pens is that the index register Z is continually incremented until it equals 9. When this happens the comparison instruction drives M1 ON which in turn resets the current value of Z to 0 (zero). Hence, a loop effect is created with Z varying between fixed values of 0 and 9 (10 values). The Z value is used to select the next counter to be displayed on the seven segment display. This is because the Z index modifier is used to offset the counter being read by the BCD output instruction.
FX version of program FX0/FX0N version of program
PLS M10 C 0 C 1 C 2 C 3 C 4 C 5 C 6 C 7 C 8 C 9
Z=0 Z=1 Z=2 Z=3 Z=4 Z=5 Z=6 Z=7 Z=8 Z=9
PLS M11
BCDP
C 0 Z K4 Y0
M10
MOV K0 Z
M 1
INC P
Z
M11
CMPP K9 Z
M0
BCD
C 0 Z K4 Y0
INC
Z
K4 Y0
CMP K9 Z
M0
Right traverse · Left traverse · Operation

FX Series Programmable Controllers Points Of Technique 10
Data can be easily read into a programmable controller through the use of the BIN instruction. When data is read from multiple sources the data is often stored at different locations. It may be required that certain data values are combined or mixed to produce a new value. Alternatively, a certain data digit may need to be parsed from a larger data word. This kind of data handling and manipulation can be carried out by using the SMOV instruction. The example below shows how two data values (a single digit and a double digit number) are combined to make a final data value.
10 0 1 0 Digit
BIN
K2X20 D2
D2 = 65 D1=7
BIN K1X0 D1
X0 to X3 X20 to X27
K1
D2 K3
SMOV
D1D2 D2=765
Explanation:
The two BIN instructions each read in one of the data values. The first value, the single digit stored in D1, is combined with the second data value D2 (currently containing 2 digits). This is performed by the SMOV instruction. The result is that the contents of D1 is written to the third digit of the contents of D2. The result is then stored back into register D2.
10.9.1 A 1 msec timer pulse measurement
Some times due to system requirements or even as a result of maintenance activities it is necessary to 'find out' how long certain input pulses are lasting for. The following program utilizes two interrupt routines to capture a pulse width and measure it with a 1 msec timer. The timer used in the ample is one of the FX timers. However, T63 on the FX0N would be used for a similar situation on that PLC.
General wiring-pluse to be measured is connected to both X0 and X1
S (X0, X1)
Pulse to be measured
RST T246 X10
EI instruction MUST be included in main program
Explanation:
RST D 0
T246K32767
The 1 msec timer T246 is driven when interrupt I001 is activated. When the input to X1 is removed the current value of the timer T246 is moved to data register D0 by interrupt program I100. The operation complete flag M0 is then set ON.
1 msec timer- FX0N use T63
SET M 0 M0
Measured time stored inD0
RST T246 M8000
K1
Pulse has been measured
END
10 10 Digit · FX prpgrammable controller

FX Series Programmable Controllers Points Of Technique 10
This is a very accurate measuring process for pulse inputs. The use of a standard timer is not accurate enough in this case as the highest resolution is 1msec. Therefor, this example shows how the special high accuracy devices M8099 and D8099 are used to capture the 0.1 msec resolution pulse data.
General wiring-pluse to be measured is connected to both X0 and X1
Pulse to be measured
EI instruction MUST be included in main program
Explanation:
FEND
The incoming pulse is captured between two interrupt routines. These routines operate independently of each other, one on the rising edge of the pulse input and one on the falling edge of the same input. During the pulse input the contents of special register D8099 are continually moved into data register D0. Once the pulse has completed the contents of D0 can be viewed at leisure.
RST M 0
IRET X10
D 0 MOV D8099
Measured time stored inD0
IRET
Pulse has been measured
Please note for this high speed/accuracy mode to be active for D8099, the corresponding special auxiliary bit device M8099 must be driven ON in the main program.
Some of the applied instructions take more than one program scan to complete their operation. This makes identification of the current operating state difficult. As an aid to the programmer, certainappliedinstructionsidentify theircompletionbysettinganoperationcompleteflag, M8029. Because this flag can be used by several different instructions at the same time, a method similar to the following should be used to trap the M8029 status at each of the instructions using it:
The M8029 'trapping’ sequence takes advantage of the batch refresh of the FX family of PLC’s. As the program scan passes each instruction using M8029 the status of M8029 changes to reflect the current status of the instruction. Hence, by immediately resetting (or setting) the drive flag for the instruction the current operational status of the instruction is trapped. So when the batch refresh takes place only the completed instructions are reset. The example above uses a pulse to set the drive flags so that it is easy to monitor and see when each instruction finishes (if the instructions are continuously driven it will be difficult to see when they finish!).
D 0 MOV
K 0
D2 K 32766 MOV
M100 PLS M100
Y5 SET
K100 K10 PLSY Y0 Y5
M8029
Y5 RST
M101 PLS M101
Y6 SET Y6
D2 D0 RAMP D3 K8000 Trapped instruction
Y6 RST
Special device D8099 · Trapped instruction

FX Series Programmable Controllers Points Of Technique 10

For users who want to have the benefits of the MTR instruction for FX users who want to specify more than one MTR area, this user defined MTR function will be very useful.
The main control of this program rests in the timer interrupt I620. This interrupt triggers every 20msec regardless of what the main program is doing. On each interruption one bank of the user defined matrix is read. The program simply consists of reading the inputs triggered by each of the multiplexed outputs. The read data is then stored in sequential sets of auxiliary registers. Each MOV instruction reads a new bank of multiplexed inputs. The equivalent MTR instruction is shown immediately before the 'user defined' MTR. See the MTR instruction on page 5-54 for more details.
On each scan of this routine a differentinput block is read
This program area controls which input block will be read
X30-37 is refreshed at the start of the routine while Y30-37 are refreshed here
The following illustration shows a simple 'pick and place' system utilizing a small robotic arm. The zero point has been de-fined as the uppermost and left most position accessible by the robot arm.

A product is carried from point 'A' to point 'B' by the robot arm. To achieve this operation the following sequence of events takes place: Initial position: the robot arm is at its zero point.
- output Y0: ON, input X1: ON, output Y0: OFF.
- output Y1: ON.

FX Series Programmable Controllers Points Of Technique 10
- output Y2: ON, input X2: ON, output Y2: OFF.
- output Y3: ON, input X3: ON, output Y3: OFF.
- output Y0: ON, input X1: ON, output Y0: OFF.
- output Y1: OFF.
- output Y0: ON, input X2: ON, output Y0: OFF.
- output Y4: ON, input X4: ON, output Y4: OFF.
The cycle can then start again.
Left most arm position
Y3
Left most arm position Upper grip limit
Operation 1 Operation 3 Operation 5 Operation 7
Operation 2 Operation 6
Robot Arm Control Center
Press to continue P
CLEAR SET/- SHIFT ENTER

FX Series Programmable Controllers Points Of Technique 10
This example uses the IST instruction (FNC 60) to control the operation mode of the robot arm. The program shown opposite identifies how the IST instruction is written into the main program.
When all conditions are met robot grip is at zero point - M8044 = ON
M8044
M8000
IST M30 S27 S20
IST control - setup
When the IST instruction is used there are 5 selectable modes which access three separate programs. This example has the following programs associated with its modes. Each mode is selected through the FX-40DU-TK. The screen shown opposite is the initial mode menu. Each of the menu options causes a screen jump to the selected mode. Menu options 1 and 3 also set ON auxiliary devices M30 and M31 respectively. The active bits then trigger a screen change to the selected mode. Please note 'Automatic' has three further modes which are selected from a following screen/display.
An example DU screen design
In this mode ALL operations of the robot arm are controlled by the operator. An operation or movement is selected by pressing the corresponding option on the DUs screen (see below). These options then trigger DU SWITCH objects which drive associated auxiliary relays within the programmable controller. The SWITCH objects should be set to momentary so that they only operate when the key is pressed.
S0
SET Y1
M17
RSTY1
Clamp is not active
Y2
M20 Y2
Y0
Y3 M16 X2
Y4
Y4 M21 X2
The status of the clamping action could be identified by two INDICATOR (SCR) functions on the DU unit. They could be monitoring the ON and OFF status of the clamp output Y1. Hence, when the clamp was ON a single black box opposite the ON button could appear. When the clamp is OFF the box would appear in front of the OFF button. At any one time only one box would be active.
Key assignment for DU screen opposite:
Up = M15 Down = M20
Left = M16 Right = M21
Clamp ON = M22
Clamp OFF = M17
Menu = reset M30
ON
Once manual operation is completed the operator can return to the main mode selection screen by touching the 'Menu' key. This causes the manual mode bit flag, M30, to be reset. Once M30 is reset the DU screen then changes back to the desired mode selection screen.

FX Series Programmable Controllers Points Of Technique 10
This mode fulfills an initialization function by returning the robot arm to a known position. Once 'Z Return' has been selected from the mode selection screen the bit device M35 is ON. At this point the DU screen changes to the 'zero return' screen. The actual zero return operation will then start when the 'Return' push button is pressed (activating M25) and the robots grip is not active, i.e. Y1 is OFF (on the STL flow diagram opposite Y1 OFF is shown as Y1*).
Clamp is not activeand the return operation has been started
Ensure 'dowm' and 'clamp' options remain reset
RST Y1
RST Y0
Y2
S11
RST Y3
Ensure 'right' option is reset
S12 SETM8043
RST S12
The DU unit could be used to report back the status of the current returning operation. The example screen shown opposite uses 3 variable messages to indicate this status. The messages could be text strings stored in the PLC which are read and displayed by the DUs ASCII option.
Once the zero point has been returned to, the operator would also return to the mode selection screen. This is achieved by pressing the 'Menu' touch key. This then resets the zero return bit device M31 which allows the DU screen change to take place.
Key assignment for DU screen above: Return = M25 Menu = reset M31
Under this option there are three further mode selections. The available modes are:
Step Mode:
- The automatic program is stepped through - operation by operation, on command by the user pressing the 'Start' button.
Cycle Mode:
- The automatic program is processed for one complete operational cycle. Each cycle is initiated by pressing the 'Start' button. If the 'Stop' button is pressed, the program is stopped immediately. To resume the cycle, the 'Start' button is pressed again.
Automatic Mode:
- A fully automatic, continuously cycling mode. The modes operation can be stopped by pressing the 'stop' button. However, this will only take effect after completion of the current cycle.

FX Series Programmable Controllers Points Of Technique 10
In this example these three modes are selected by an external rotary switch. The rotary switch is not connected to the PLC but to the I/O bus on the rear of the DU unit. The use of the rotary switch means that the selected modes are mutually exclusive in their operation. For an operator friendly environment the currently selected mode is displayed on the DU screen (again this could be by use of the DUs ASCII function). The start/ stop controls are touch keys on the DU screen. When a mode is selected the input received at the DU unit momentarily activates one of the following auxiliary relays: Rotary switch: position 1 'Step' - Step operation: DU input I0, controls bit device M32 position 2 'Cycle' - Single cycle operation: DU input I1, controls bit device M33 position 3 'Auto' - Automatic operation: DU input I2, controls bit device M34
CYCLE
AUTO STEP
Rotary switch input to DU through I/O bus (used to select mode).
M8041 M8044
S 20
Y0
Key assignment for DU screen above: Start = M36 Stop = M37
SET Y1
K10
T0
T0
The program run in all three mode choices is shown opposite. As noted earlier, the 'Step' mode will require an operator to press the 'Start' key to start each new STL block. This could be viewed as an additional transfer condition between each state. However, the user is not required to program this as the IST instruction controls this operation automatically.
Y2
S 23
Y3
Y0 S 24
The 'Cycle' mode will process the program from STL step S2, all the way through until STL step S2 is encountered again. Once more the IST instruction ensures that only one cycle is completed for each initial activation of the 'Start' input.
RST Y1
Clamp is not active
T1
T1
Y2 S 26
S 27
Y4
Finally as suggested by the name, 'Auto' mode will continuously cycle through the program until the 'Stop' button is pressed. The actual halting of the program cycling will occur when the currently active cycle is completed.

FX Series Programmable Controllers Points Of Technique 10
a) Users of the IST instruction will be aware that only one of the operation modes should be
active at one time. In this example program the isolation of 'Manual' and 'Zero return' modes by the use of separate DU control screens, and the use of a rotary switch to isolate the three automatic modes achieves this objective. Alternatively all of the operation modes could be selected by a rotary switch.
b) For users who would like to test this example using simulator switches (i.e., without using
a data access unit) the appropriate program changes are noted next to the full program listing later in this section. Alternatively, the original program could be used with all of the input conditions being given by forcing ON the contacts with a programming device e.g. a hand held programmer, Medoc etc.
c) Special flags used in this program are:
- Manual mode: Always ON. Zero return and Cycle modes: Once the 'Stop' input is given the current state is retained until the 'Start' input is received. Step mode: This flag is OFF when the 'Start' input is ON. At all other times M8040 is ON, this enables the single STL step operation to be achieved. Auto mode: M8040 is ON initially when the PLC is switched into RUN. It is reset when the 'Start' input is given.
- Manual and Zero return modes: This flag is not used. Step and Cycle modes: This flag is only active while the 'Start' input is received. Auto mode: The flag is set ON after the 'Start' input is received. It is reset after the 'Stop' input is received.
- This is momentarily active after the 'Start' input is received.
- This is a user activated device which should be controlled within the users program.
- This is a user activated device which should be controlled within the users program.

FX Series Programmable Controllers Points Of Technique 10
0 LD X 4 35 STL S 1 72 STL S 21
1 AND X 2 36 LD M 35 73 SET Y 1
2 ANI Y 1 37 RST M 8043 74 OUT T 0
3 OUT M 8044 39 ANI Y 1 K 10
5 LD M 8000 40 SET S 10 77 LD T 0
6 IST 60 42 STL S 10 78 SET S 22
M 30 43 RST Y 1 80 STL S 22
S 20 44 RST Y 0 81 OUT Y 2
S 27 45 OUT Y 2 82 LD X 2
13 STL S 0 46 LD X 2 83 SET S 23
14 LD M 8044 47 SET S 11 85 STL S 23
15 OUT M 8043 49 STL S 11 86 OUT Y 3
17 LD M 22 50 RST Y 3 87 LD X 3
18 SET Y 1 51 OUT Y 4 88 SET S 24
19 LD M 17 52 LD X 4 90 STL S 24
20 RST Y 1 53 SET S 12 91 OUT Y 0
21 LD M 15 55 STL S 12 92 LD X 1
22 ANI Y 0 56 SET M 8043 93 SET S 25
23 OUT Y 2 58 RST S 12 95 STL S 25
24 LD M 20 (RET)* 96 RST Y 1
25 ANI Y 2 60 STL S 2 97 OUT T 1
26 OUT Y 0 61 LD M 8041 K 10
27 LD M 16 62 RST M 8043 100 LD T 1
28 AND X 2 64 AND M 8044 101 SET S 26
29 ANI Y 3 65 SET S 20 103 STL S 26
30 OUT Y 4 67 STL S 20 104 OUT Y 2
31 LD M 21 68 OUT Y 0 105 LD X 2
32 AND X 2 69 LD X 1 106 SET S 27
33 ANI Y 4 70 SET S 21 108 STL S 27
(RET)* 110 LD X 4 ↑ This instruction returns the program flow to STL step S2. → 111 OUT S 2
*: Instructions in ( ) are not necessary 113 RET

6 IST 60 17 LD X 12 27 LD X 6
X 20 19 LD X 7 31 LD X 11
S 20 21 LD X 5 36 LD X 25
necessary 114 END

FX Series Programmable Controllers Points Of Technique 10
The PWM instruction may be used directly with an inverter to drive a motor. If this configuration is used the following ripple circuit will be required between the PLC’s PWM output and the inverters input terminals.

Circuit configuration for a PLC with source outputs
Key to component values:
R1 - 510 Ω (1/2 W) R2 - 3.3kΩ (1/2 W)
R3 to R8 - 1kΩ (1/4 W) R9 - 22 Ω (1/4 W)
R10 - variable dependent on configuration. In this example 1kΩ (1 W)
C1 - 470 µF

It is assumed that the input impedance of the inverter is of a high order. Having established this, the values of C1 and R10 are calculated to give τ a time result (in msec) approximately 10 times bigger than the value used for T0 in the PWM instruction:
τ = R10 (kΩ) ÅL C1 (µF)
During this calculation the value of R10 must be vastly greater than the value of R9. In the example, R9 is equal to 22Ω, where as R10 is equal to 1kΩ. This proportion is approximately 1:50 in favor of R10.

FX Series Programmable Controllers Points Of Technique 10
The maximum output voltage (to the inverter) including ripple voltage, can be found by using the following equation:
Where:
em = Maximum output voltage
E= pulse (square wave) output voltage (see circuit on the previous page)
t = PWM pulse duration (see previous page for reference)
T0 = PWM cycle time for pulse (see previous page for reference)
The average output voltage (to the inverter) including ripple voltage, can be found by using the following equation:
T0 - t
Where:
∆e = the voltage value of the ripple e = ripple output voltage T0 = PWM cycle time for pulse t = PWM pulse duration τ = ripple circuit delay
See previous page for references.
Once the system configuration has been selected and the ripple circuit has been built to suit, the motor speed may be varied by adjusting the value of 't' in the PWM instruction. The larger the value of 't' the faster the motor speed will rotate. However, this should be balanced with the knowledge that the faster the output signal changes the greater the ripple voltage will be. On the other hand a slowly changing output signal will have a more controlled, yet smaller ripple effect. The speed of the signal change is determined by the size of C1. A large capacitive value for C1 would give a smaller ripple effect as charge is stored and released over a longer time period.
R 5
R10
COM 24+
R 4
R 9
R 6
R7
Y0 COM1
R 8
Circuit configuration for a PLC with sink outputs. The component values are the same as stated previously
The following characteristics were noticed when the identified circuit was tested The PWM instruction had T0 set to K50. The value for t was varied and also the load impedance was varied to provide the following characteristics graph (see over page).

FX Series Programmable Controllers Points Of Technique 10
(e.g. inverter impedance) L1 - 100 k L2 - 10 k L3 - 4.7 k L4 - 2.2 k
20 30 10 5 2.5 1.0 40 50 t
The duration of the T0, time base also affects the ripple voltage. This can be clearly seen in the next set of test data:
PWM parameter setting Measured ripple
voltage t T0 t / T0
The behavior of the Sink switched circuit detailed above will be similar to that of the Source switched circuit detailed earlier.

FX Series Programmable Controllers Points Of Technique 10
10.14.1 Specification of the communication parameters:
Items such as baud rates, stop bits and parities must be identically set between the two communicating devices. The communication parameters are selected by a bit pattern which is stored in data register D8120.
0 (OFF) 1 (ON)
b0 Data length 7 bits 8 bits
b1 b2 Parity (b2, b1)
b3 Stop bits 1 bit 2bits
b4 b5 b6 b7
Baud rate - bps
b8 Header character None D8124, Default : STX (02H)
b9 Terminator character None D8125, Default : ETX (03H)
No Protocol (b12, b11, b10) ( 0, 0, 0) : RS Instruction is not being used (RS232C interface) ( 0, 0, 1) : Terminal mode -RS232C interface ( 0, 1, 0) : Interlink mode - RS232C interface (FX2N V2.00 or above) ( 0, 1, 1) : Normal mode 1- RS232C, RS485(422) interfaces (RS485 FX2N(C) only) ( 1, 0, 1) : Normal Mode 2 - RS232C interface (FX only)
(see timing diagrams page 10-20 onwards)
Computer Link (b12, b11, b10) ( 0, 0, 0 ) : RS485(422) interface ( 0, 1, 0 ) : RS232C interface
Sum Check No Check Added automatically
b14 Protocol No protocol Dedicated Protocol
b15 Protocol Format 1 Format 4
General note regarding the use of Data register D8120:
This data register is a general set-up register for all ADP type communications. Bits 13 to 15 in the 232ADP units should not be used. When using the FX-485 network with 485ADP units bits 13 to 15 should be used instead of bits 8 to 12.

FX Series Programmable Controllers Points Of Technique 10
The header and terminator characters can be changed by the user to suit their requirements. The default setting for the header stored in D8124 is 'STX' (or 02H)and the terminator default setting stored in D8125 is 'ETX' (or 03H). The header and terminator characters are automatically added to the 'send' message at the time of transmission. During a receive cycle, data will be ignored until the header is received. Data will be continually read until either the termination character is received or the receive buffer is filled. If the buffer is filled before the termination character is received then the message is considered incomplete. If no termination character is used, then reading will continue until the receive data buffer is full. Only at this point will a message have been accepted and complete. There is no further buffering of any communications, hence if more data is sent than the available destination buffer size then the excess will be lost once the buffer is full. It is therefore very important to specify the receive buffer length the same size as the longest message to be received.
The RS instruction should be set up and active. The data to be transmitted should be moved into the transmission data buffer. If a variable is being used to identify the message length in the RS instruction this should be set to the new message length. The send flag M8122 should then be SET ON. This will automatically reset once the message has been sent. Please see the example program right.
BMOV K 6 D50 D100
MOV D49 K6
SET M8122
Events encountered when receiving a message:
The RS instruction should be set up and active. Once data is being received and an attempt is made to send out data, the special M flag M8121 is set ON to indicate the transmission will be delayed. Once the 'incoming' message is completely received the message received flag M8123 is set ON. At the same time if M8121 was ON it is automatically reset allowing further messages (delayed or otherwise) to be transmitted. It is advisable to move the received data out of the received data buffer as soon as possible. Once this is complete M8123 should be reset by the user. This is then ready to send a message or to await receipt of a new message.
M8123
BMOV K 10 D70 D200
RST M8123

FX Series Programmable Controllers Points Of Technique 10
FX2N below version 2.0
Send data SD (TXD)
F ON Send request M8122
Send wait flag M8121
ON OFF * This period should be 100 µ s or more
Receive data RD (RXD)
Data 2 Data 3
The receive wait status is started
Reset using a program. When it is not turned off, the next data cannot be received.
*When using FX0N, FX, FX2C this should be 2 x scan time or more
RS instruction Send data SD (TXD)
Send request M8122 ON OFF
ON
ON DR(DSR)
OFF
OFF ON RS instruction
Receive data RD (RXD)
ER(DTR)
ON Receive completion M8123
ON
Reset using a program. When it is not turned off, the next data cannot be received.

FX Series Programmable Controllers Points Of Technique 10
FX2N below V2.00.
Send data SD (TXD)
OFF ON Send request M8122
Send wait flag M8121
ER(DTR)
OFF ON
Receive data RD (RXD)
ON
Reset using a program. When it is not turned off, the next data cannot be received.
R)
OFF
ON
This period should be 100 µs or more
* When using FX0N, FX, FX2C this period should be 2x scan time or more.
FX2N below V2.00
Send data SD (TXD)
OFF ON Send request M8122
Send wait flag M8121
ER(DTR)
OFF ON
DR(DSR)
OFF
ON
OFF
Receive data RD (RXD)

FX Series Programmable Controllers Points Of Technique 10
In the FX2N V2.00 or above and FX2NC, full duplex communication is performed.
Send data SD (TXD)
OFF ON Send request M8122
Receive data RD (RXD)
Data 2 Data 4
The receive wait status is started
Reset it using a program. When it is not turned off, the next data cannot be received.
OFF ON RS instruction
Send data SD (TXD)
ER(DTR)
OFF ON
Data 2 Data 3 Receive data RD (RXD)
ON Receive completion M8123
ON
DR(DSR)
OFF ON
Reset using a program. When it is not turned off, the next data cannot be received.

FX Series Programmable Controllers Points Of Technique 10
Send data SD (TXD)
OFF ON Send request M8122
DR(DSR)
Up to 30 characfers can be received *2
Data 1 Data 3 Receive data RD (RXD)
Time-out evaluation time D8129 × 10ms
Time-out evaluation flag M8129
Reset using a program. When it is not trurned off,the next data cannot be received.
ER(DTR)
OFF ON
Reset using a program. When it is not turned off, the next data cannot be received.
10.14.4 8 bit or 16 bit communications.
This is toggled using the Auxiliary relay M8161. When this relay is OFF 16 bit communications takes place. This actually means that both bytes of a 16 bit data device are used in both the transmission and the receipt of messages. If the M8161 device is activated then 8 bit mode is selected. In this mode only the lower 8 bits (or byte) is used to perform the transmission- receiving actions. The toggling of the M8161 device should only occur when the RS instruction is not active, i.e. it is OFF. When a buffer area is specified in the RS instruction it is important to check whether 8 or 16bit mode has been selected, i.e. a buffer area specified as D50 K3 would produce the following results
16 bit mode - M8161 = OFF 8 bit mode - M8161 = ON
Data register High byte Low byte Data register High byte Low byte
D51 0 D51 X
D52 0
General note regarding hardware:
Information regarding pin outs of the respective ADP special function blocks can be found along with wiring details in the appropriate hardware manuals.

FX Series Programmable Controllers Points Of Technique 10
10.15.1 Keeping MV within a set range
In the reserved registers of the PID data block S3+18 and S3+19 form a double word device that contains the previous MV x K100. The following program uses this to keep MV under control when it exceeds the operating limits. Example Program to keep MV in the range K100 to K5000
D18 D19 D20 D46 PID
MV
K100 K5000 D46 M20 ZCP
Check MV against range
MV
K100 D46 MOV
K10000 D38 DMOV
Reset PID data to lower limit
MV
K5000 D46 MOV
K500000 D38 DMOV
Reset PID data to upper limit
If data registers are used to hold the limit values, it is possible to use a MUL instruction instead of the DMOV. E.g. When D50 is upper limit use: MUL D50 K100 D38 because the result of MUL is already a double word DMUL is not needed. Resetting (S3+19, S3+18) in this way prevents runaway, which occurs if only MV is changed.
In order to switch from automatic (PID) control to manual control and back to automatic it is necessary for the PID process to perform 'Manual Tracking'. Although the FX PID instruction does not have a manual tracking feature there are two methods that can be used to make the switch from manual back to automatic as trouble free as possible. To understand the reason for the two methods the following should be noted. The PID instruction sets its initial output value based on the initial value of the output register. When the PID instruction is switched on it can only do P as it has only 1 data reading. On the first reading the current value of the output register is used as ∆MV. Thereafter the previous output value is used (stored in S3+18, S3+19).
After the next reading PI can be calculated and from the third reading full PID is performed.
Please see section 5.98, PID (FNC 88), for the complete equations.
It is recommended that if manual to auto switching is desired that the PID instruction is switched off during manual operation and the operator controls the value of the MV register (the Output Value). When returning to auto mode, the PID instruction is switched on again and uses the last MV input by the operator during the first PID calculation. After 3 readings full PID will be operating and the process should be under control quickly. (Assuming that manual control did not cause a move too far from the Set Point.)

FX Series Programmable Controllers Points Of Technique 10
During manual operations the PID instruction is kept running but the calculated MV is ignored; instead the operator controls MV. In order to prevent the PID instruction from running out of control the MV value set by the operator should be fed in to the MVn-1 registers of the PID data block in the same way as for MV range control earlier (i.e. Set S3+18, S3+19 to MV x 100). When switching back to PID control the internal values of the PID instruction are already set and full PID operation starts immediately.
Included as part of the data block there are four alarm values. These set the maximum positive and negative change that should occur to MV and PV. The PID alarm signals are used to warn of the system going out of control. When the system is starting from cold it is usually not good to include the Derivative numbers of the in the calculation; the changes to PV are large and the Derivative introduces too much correction. Also, if the system starts to move rapidly away from the SV then sometimes the use of D can over correct and cause chasing. By having an 'alarm' flag for the change in PV and MV it is possible to monitor the state of the system and adjust the PID parameters to appropriate settings. When the system is close to the SP the changes in PV (and MV) should be minimal. In this situation using full PID is very useful in keeping the system close to the SP. (Full PID is appropriate). However, if the conditions change (e.g. opening a refrigerator door, adding ingredients to a mixture, cold start, etc.) the system reacts. In some cases (especially cold start) the reaction is too much for the D to be useful (PI or sometimes just P only is better). In these cases the alarm flags can be used to change to PI control until the system returns to a more stable condition, when full PID can then be used. Basically, rather than use actual values of the PV to determine the change over point from PI to PID (or PID to PI), use the size of the change in PV (or MV). This means changes to the Set Point do not require different ranges for the PI - PID change over point (at least, in theory).

FX Series Programmable Controllers Points Of Technique 10
The following parameter table gives the additional parameters available with FX2N(C) MPUs. These are:
- S3+1 bit 4: Pre-tuning operation flag. - S3+1 bit 5: Output Value range limit flag. - S3+22: Output Value upper limit. - S3+23: Output Value lower limit.
eter S3 + P
b0 Forward operation(0), Reverse operation (1)
b1 Process Value (S2) change alarm OFF(0)/ON(1)
Action-reac- tion direction and alarm control
b2 Output Value (MV) change alarm OFF(0)/ON(1)
b4 Activate pre-tuning (auto resets on completion)
b5 Output Value (MV) range limit OFF(0)/ON(1)
Output Value, maximum positive change alarm
Active when S3+1, b2 is set ON.
This is an alarm for the quantity of positive change which can occur in one PID scan. If the Output Value (MV) exceeds this value, bit S3+24, b2 is set
Active when S3+1, b5 is set ON.
Output Value, Upper limit restriction
This is an upper limit for the Output Value (MV). During operation the PID instruction restricts the output so that it does not exceed this limit.
Output Value, maximum negative change alarm
Active when S3+1, b2 is set ON.
This is an alarm for the quantity of negative change which can occur in one PID scan. If the Output Value (MV) falls below this value, bit S3+24, b3 is set.
Active when S3+1, b5 is set ON.
This is a lower limit for the Output Value (MV). During operation, the PID instruction restricts the output so that it does not fall below this limit.
Output Value, Lower limit restriction
For the full list of other parameters refer to page 5-102.
Bit 5 of parameter S3+1, when ON, activates S3+22 and S3+23 to be upper and lower limits for the output value (MV). This feature restricts the output value to the specified limits; in effect, this automatically performs the same operation as that described in section 10.15.1.

FX Series Programmable Controllers Points Of Technique 10
10.17.1 Variable Constants
The Pre-tuning operation can be used to automatically set values for the following variables:
- The direction of the process; Forward or Reverse (S3+1, bit 0)
- The proportional gain constant; KP (S3+3)
- The integral time constant; TI (S3+4)
- The derivative time constant; TD (S3+6)
Setting bit 4 of S3+1 starts the pre-tuning process. Before starting, set all values that are not set by the pre-tuning operation: the sample time, Ts (S3+0); the input filter α (S3+2); the Derivative gain, KD (S3+5); the Set Point, SV (S1); and any alarm or limit values, (S3+20-23).
The Pre-tuning operation measures how fast the system will correct itself when in error. Because the P, I, and D equations all react with differing speed, the initial error must be large so that effective calculations can be made for each type of equation. The difference in values between SP and PVnf must be a minimum of 150 for the Pre-tuning to operate effectively. If this is not the case, then please change SV to a suitable value for the purpose of pre-tuning.
The system keeps the output value (MV) at the initial value, monitoring the process value until it reaches one third of the way to the Set Point. At this point the pre-tuning flag (bit 4) is reset and normal PID operation resumes. SV can be returned to the normal setting without turning the PID command Off.
During the course of normal operation, the Pre-tuning will NOT automatically set new values if the SV is changed. The PID command must be turned Off, and the Pre-Tuning function restarted if it is necessary to use the Pre-tune function to calculate new values.

FX Series Programmable Controllers Points Of Technique 10
The following programming code is an example of how to set up the Pre-Tuning function.
K500 D500 FNC 12 MOV P
D511: S3+1, Bits 0-3 and 5-15 Off, Bits 4 and 5 On. Bit 4 = Pre-Tune Function Bit 5 = MV Range Limit
M0 PLS
SET M1 M0
Pulse M1 to turn On PID command
FNC 79 TO K 0 K 0 H3303 K 1
Send setting to Special Function Block
Read data from Special Function Block
FNC 78 FROM K 0 K 10 D501 K 1
Reset Output data when PID command is Off
PID Instruction Command Line
RST M1 Turn Off PID Instruction
•

FX Series Programmable Logic Controllers Index 11
2 Basic Program Instructions
3 STL Programming
4 Devices in Detail
5 Applied Instructions
6 Diagnostic Devices
7 Instruction Execution Times
8 PLC Device Tables
9 Assigning System Devices
10 Points of Technique
11 Index

FX Series Programmable Logic Controllers Index 11
11.Index 11-1 11.1 Index 11-1 11.2 ASCII Character Codes 11-9 11.3 Applied Instruction List 11-10

FX Series Programmable Controllers
A
Absolute drum sequence, ABSD instruction 5-70 Addition of data values, ADD instruction 5-25 Addressing special function blocks 9-1 Advanced programming points
Examples and tips 10-1 Alternated state, ALT instruction 5-73 Alternating states using ALT, example 10-4 ANB 2-12 And block instruction 2-12 And, And inverse instructions 2-6 AND, ANI 2-6 Annunciator reset, ANR instruction 5-47 Annunciator set, ANS instruction 5-47 Applied instr' which can only be used once 7-16 Applied instruction list 11-10 Applied instructions 5-1 Arrow switch, ARWS instruction 5-87 ASCII character codes 11-9 ASCII code (Alpha to ASCII code), ASCI instr' 5-88 ASCII to HEX conversion using HEX (FNC 83) 5-99 Assigning special function block numbers 9-1 Assigning system devices 9-1 Auxiliary relays,
Battery backed/ latched 4-4 Device details and example 4-3 General information on diagnostic devices 4-5 General use 4-3
Outline of basic PLC devices 2-1 X, Y, T, C, M, S 2-1 Basic devices and instructions 2-1 BCD data words - reading 4-44 BCD output (Binary Coded Decimal), BCD instr' 5-22 BIN input (Binary), BIN instruction 5-22 Binary data - reading 4-42 Bit devices 4-40 Bit on recognition, BON instruction 5-45 Bit pattern rotation left, ROL instruction 5-35 Bit pattern rotation right, ROR instruction 5-35 Bit rotation and carry left, RCL instruction 5-36 Bit rotation and carry right, RCR instruction 5-36 Bit shift left, SFTL instruction 5-37 Bit shift right, SFTR instruction 5-37 Block data move, BMOV instruction 5-20
Index 11 · Basic devices

FX Series Programmable Controllers Index 11
See Counters Comparison of data to a range, ZCP instr' 5-17 Comparison of single data values, CMP instr' 5-17 Compliment of a data value, CML instr' 5-19 Conditional Jump instruction (CJ) 5-5 Constant scan mode - how to program, example 10-4 Constants,
Numeric decimal (K) data value entry 4-14 Numeric Hexadecimal (H) data value entry 4-14 Counters,
16 bit resolution counters 4-20 32 bit resolution bi directional counters 4-21 Basic counters 2-18 Device details and examples 4-19 Ring counters 4-21
See Data registers Data registers,
Battery backed/ latched registers 4-35 Device details and examples 4-33 Externally/manually adjustable data registers 4-37 File registers of FX and FX0N PLC’s 4-36 General description of diagnostic registers 4-35 General operation of data registers 4-34 Decode data value, DECO instruction 5-43 Decrement data, DEC instruction 5-29 Device terms
Bits, words, BCD and hexadecimal 4-40 Floating Point And Scientific Notation 4-46 Diagnostic devices
Clock devices (M8010-19 and D8010-19) 6-3 Error detection devices (M8060-69, D8060-69) 6-8 High speed counter flags (M8235-55, D8235-55) 6-14 Interrupt controls (M8050-59 and D8050-59) 6-7 Link control (M8070-99 and D8070-99) 6-9 See Also Miscellaneous (M8100-19, D8100-19) Operation flags (M8020-29 and D8020-29) 6-4 PLC operation mode (M8030-39 and D8030-39) 6-5 PLC status (M8000-9 and D8000-9) 6-2 STL/Annunciator flags (M8040-49 and D8040-49) 6-6 Up/down counter control (M8200-34, D8200-34) 6-14 Digital switch input, DSW instruction 5-83 Division of data values, DIV instruction 5-28 Double coil designation 2-5
C data devices · D data devices

FX Series Programmable Controllers Index 11
Encode data, ENCO instruction 5-44 END 2-23 End instruction 2-23 Error codes
Circuit (D8066) 6-17, 6-18 Communication (D8062 - D8063) 6-15 Hardware (D8061) 6-15 Operation (D8067) 6-19 Parameter (D8064) 6-16 Syntax (D8065) 6-16 Example of interrupt use 10-6 Example system application 10-8 Example use of a timer interrupt 10-8 Exchanging data bytes, XCH instruction 5-21 Exchanging data formats
BCD data to binary data, BIN instr' 5-22 Binary data to BCD data, BCD instr' 5-22 Floating point to scientific format, (FNC 18) 5-22 Scientific format to floating point, (FNC 19) 5-22 Exchanging data values, XCH instruction 5-21 Execution complete flag, using M8029 10-7 External setting pots - FX0, FX0S and FX0N 4-37
F-16NP/NT - FX2-24EI control instructions
Melsec net mini control, MNET instruction 5-111 F2-30GM - FX2-24EI control instructions
Block write, BLOCK instruction 5-115 Write assigned machine code, MCDE instr' 5-116 F2-32RM - FX2-24EI control instructions
RM monitor, RMMN instruction 5-114 RM read status, RMRD instruction 5-114 RM start, RMST instruction 5-112 RM write, RMWR instruction 5-113 F2-6AE - FX2-24EI control instructions
Analog data read, ANRD instruction 5-111 Analog data write, ANWR instruction 5-112 FIFO data read, SFRD instruction 5-40 FIFO data write, SFWR instruction 5-39 Fill move, FMOV instruction 5-21 Float instruction, FLT 5-49 Floating point - a numbering format 4-48 Floating point application - summary 4-49 FOR-NEXT loops, FOR, Next instructions 5-13 Forced program end, FEND instruction 5-11 FX performance specification
CPU versions 2.0 through 3.06 8-4 CPU versions from 3.07 onwards 8-6

FX Series Programmable Controllers Index 11
FX-8AV - externally adjustable data values 4-37 FX-8AV control instructions
Volume read, VRRD instruction 5-101 Volume scale, VRSC instruction 5-101 FX0 an FX0S performance specification 8-1 FX0N performance specification 8-2 FX2-40AP/AW parallel run (PRUN) instruction 5-96 FX2C performance specification 8-6 FX2N(C) performance specification 8-8
Grouped bit devices 4-41
See Constants Hex to ASCII conversion using ASCI (FNC 82) 5-98 Hexadecimal data words - reading 4-43 Hexadecimal keypad, HKY instruction 5-82 Hierarchy of program flow instructions 7-12 High speed counter reset, HSCR instruction 5-56 High speed counter set, HSCS instruction 5-55 High speed counter zone compare, HSZ instr' 5-57 High speed counters,
1 phase counter - reset and start inputs 4-30 1 phase counters - user start and reset 4-29 2 phase bi-directional counters 4-31 A/B phase counters 4-32 Available counters for FX PLC’s 4-25 Available counters for FX0, FX0S and FX0N PLC’s 4-24 Available counters for FX2N(C) PLC’s 4-28 Basic operation 4-23 Counter speeds for FX PLC’s 4-26 Glossary and examples 4-22 How to use the manual 1-2 HSZ Instruction
Combined HSZ and PLSY operation (3) 5-59 Standard Operation (1) 5-57 Using HSZ with a data table (operation 2) 5-57
I interrupt program pointer
See Interrupts Incremental drum sequence, INCD instruction 5-71 Incrementing data, INC instruction 5-29 Index registers,
Device details and examples 4-38 General use 4-38 Misuse of modifiers 4-39 Modifying a constant 4-39
H value

FX Series Programmable Controllers Index 11
Using multiple index registers 4-39 Indexing through display values, example 10-5 Initial state control, IST instruction 5-67 Input, device details and example 4-1 Instruction execution times
Applied instructions 7-3 Basic instructions 7-1 Interrupts,
Device details and pointer examples 4-11 Disabling individual interrupts 4-13 Input triggered interrupt routines 4-12 Interrupt instructions: IRET, EI, DI 5-9 Timer triggered interrupt routines 4-12
LD, LDI 2-3 Load, load inverse instructions 2-3
See Auxiliary relay Manipulating thumbwheel data (SMOV), example 10-6 Master control and master control reset 2-15 Matrix input sequence, MTR instruction 5-54 MC, MCR 2-15 Mean of a data set, MEAN instruction 5-46 Measuring high speed input pulses
Method using a 1msec timer + interrupts 10-6 Method using M8099, D8099 and interrupts 10-7 Motor control with the PWM instruction 10-15 Move data, MOV instruction 5-18 MPS, MRD, MPP 2-13 Multiple output circuits 2-13 Multiplication of data, MUL instruction 5-27
Negation of a data value, NEG instruction 5-31 No operation instruction 2-22 NOP 2-22
Or block instruction 2-11 Or, Or inverse instructions 2-7 OR, ORI 2-7 ORB 2-11
K value · See Constants · M bit device

FX Series Programmable Controllers Index 11
Timer and counter variations 2-4 Out instruction 2-4 Output, device details and example 4-2
See Pointer P Parallel link adapter, FX-40AP/AW 9-6 PLC operation - batch processing 7-14 PID control
Applied instruction 88 - PID 5-102 Configuring the PID loop 5-105 Example program 10-28 PID Setup parameters 5-104 Program techniques 10-24 PLS, PLF 2-20 PLSY initialize for FX ver2.2 or earlier 5-61 Pointer P, Device details and example use 4-10 Positive/negative logic 5-86 Power failure precautions for FX DC units 10-1 Print to display, PR instruction 5-89 Program How to read ladder logic 2-2 Program scan 2-23 Programming formats: list, ladder, STL/SFC 2-1 What do you need to program a PLC? 1-3 What is a program? 2-1 Program example featuring IST and STL control 10-8 Programmable controller What is a programmable controller 1-3 Programming tools 1-3 FX-PCS/AT-EE SW operating precautions 3-15 Pulse Leading and trailing edge instructions 2-20 Pulse Ramp (PLSR instruction) 5-63 Pulse train output, PLSY instruction 5-61 Pulse width modulation, PWM instruction 5-62
Ramped values, RAMP instruction 5-73 Reading from special blocks, FROM instruction 5-90 Real time clock memory cassettes 9-7 Refresh and filter adjust, REFF instruction 5-53 Refresh I/O status, REF instruction 5-53 Ripple circuit for use with an inverter 10-15 Rotary table control, ROTC instruction 5-75 RS communications function (FNC80) 5-95
P program pointer

FX Series Programmable Controllers Index 11
See State relays Scientific Notation - a numerical format 4-47 Search, data search utility - SER instruction 5-69 Set and reset instructions 2-17
See Also Zone reset, ZRST FNC 40 SET, RST 2-17 Seven segment decoder, SEGD instruction 5-84 Seven segment multiplexed displays 5-85 Seven segment with latch control, SEGL instr' 5-85 Shift move, SMOV instruction 5-18
Moving BCD data 5-19 Moving decimal data 5-18 Sort instruction, FNC 69 5-77 Special timer, STMR instruction 5-72 Speed detect, SPD instruction 5-60 Square root, SQR instruction 5-48 State relays,
Battery backed/ latched 4-7 Device details and example 4-6 General use 4-6 Use as annunciator flags 4-9 Use as STL step numbers 4-8 Step ladder programming 3-1
Example, simple STL flow 3-16 Example, STL selective branch 3-18 First state merge 3-11 General STL branching rules 3-14 How to start and end an STL program 3-3 Multiple state merge 3-13 Operational restrictions of some instructions 3-10 Selective branch 3-11 Some rules for the writing of STL programs 3-7 What is STL, SFC and IEC 1131 part 3? 3-1 STL
See Step ladder programming Subroutine call, CALL instruction 5-7 Subroutine return, SRET instruction 5-8 Subtraction of data values, SUB instruction 5-26 Sum active data bits, SUM instruction 5-45 Sum checking using CCD (FNC 84) 5-100
See Timers Teaching timer, TTMR instruction 5-72 Ten key keypad, TKY instruction 5-81 Thumbwheels-multiplexed
See Digital switch input Timers and counters (out and reset of) 2-18
S bit device · T data devices

FX Series Programmable Controllers Index 11
Basic timers 2-18 Device details and examples 4-15 General accuracy 4-18 General timer operation 4-16 Retentive timers 4-17 Selectable range timers 4-16 Timers used in interrupt and CALL subroutines 4-18 Two's compliment - an explanation 4-45
Unsuitable instr' for 110V AC input units 7-16 User defined MTR instruction 10-8 Using battery backed/latched devices, example 10-5 Using forced RUN mode (M8035/36/37), examples Push button configuration 10-2 Remote control with an FX graphic DU unit 10-3 Using FX2-24EI with F series special blocks 9-2 Using the F-16NP/NT net mini extension block 9-3 Using the F2-30GM pulse output unit 9-5 Using the F2-32RM CAM positioning unit 9-4 Using the F2-6A analog extension block 9-4
Watchdog timer refresh, WDT instruction 5-12 Word AND instruction 5-30 Word data - interpretation 4-42 Word devices 4-42 Word exclusive OR instruction 5-31 Word OR instruction 5-30 Word shift left, WSFL instruction 5-38 Word shift right, WSFR instruction 5-38 Writing to special blocks, TO instruction 5-91
Z data device See Index registers Zone device reset, ZRST instruction 5-43

FX Series Programmable Controllers Index 11
Table 11.1:
(HEX)
1 2 3 4 5 6 7
(SP) 0 @ P @ p
1! 1 A Q a q
2 “ 2 B R b r
3 # 3 C S c s
4 $ 4 D T d t
5 % 5 E U e u
6 & 6 F V f v
7 ‘ 7 G W g w
8 ( 8 H X h x
B + ; K [ k {
C, < L l |
D - = M ] m }
E. > N (SP) n ~
F / ? O _ o CR

FX Series Programmable Controllers Index 11

FX (CPU ver 3.07 or greater) and FX2C
FX (CPU ver 3.07 or greater) and FX2C
FX (CPU ver 3.07 or greater) and FX2C



THE FX SERIES OF PROGRAMMABLE CONTROLLER (FX 0, FX0S, FX0N, FX, FX 2C, FX 2N, FX2NC)
HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX: J24532 CABLE MELCO TOKYO HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN
Effective Nov. 1999 Specification are subject to change without notice.